Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:35:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2624.88 | 526.85 | 526.85 |
Net Site Energy | 2624.88 | 526.85 | 526.85 |
Total Source Energy | 7323.56 | 1469.95 | 1469.95 |
Net Source Energy | 7323.56 | 1469.95 | 1469.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 696.52 | 348.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 111.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 126.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2149.88 | 475.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 696.52 | 348.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 111.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 126.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 696.52 | 348.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 52.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 370.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 111.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 126.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 96.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.75 | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 162.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.51 | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 96.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.75 | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 162.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.51 | 95.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2149.877 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2149.877 | 100.00 |
Total On-Site and Utility Electric Sources | 2149.877 | 100.00 |
Total Electricity End Uses | 2149.877 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.29 | 0.04 |
Air to Air Heat Recovery for Heating | 691.25 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 691.54 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1044.17 |
Time Setpoint Not Met During Occupied Cooling | 29.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3454.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.0546 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 9.0546 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 9.0546 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 12-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 187757.69 | 272952.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47562.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1310.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5279.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2703.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8906.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 289219.99 | 281859.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 187757.69 | 272952.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1310.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5279.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2703.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8906.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 2205.89 | 377.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 166.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1172.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 353.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 83.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 136.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6808.66 | 514.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 442.76 | 75.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 235.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1366.60 | 103.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 442.76 | 75.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 235.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1366.60 | 103.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.04 | 0.246848 | 0.300000 | 0.910828 | 0.658263 | 0.500000 | 0.001543 |
CORE_MID VAV BOX COMPONENT | 2.28 | 0.328637 | 0.341000 | 0.777650 | 0.876364 | 0.500000 | 0.001159 |
CORE_TOP VAV BOX COMPONENT | 2.25 | 0.333681 | 0.354000 | 0.795091 | 0.889816 | 0.500000 | 0.001142 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.718130 | 0.220004 | 0.300000 | 0.215439 | 0.586678 | 0.500000 | 0.001732 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.875242 | 0.114279 | 0.300000 | 0.262572 | 0.304744 | 0.500000 | 0.003334 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.40 | 0.112937 | 0.300000 | 0.419681 | 0.301165 | 0.500000 | 0.003374 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.920675 | 0.108633 | 0.300000 | 0.276202 | 0.300000 | 0.500000 | 0.003507 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.575545 | 0.274508 | 0.300000 | 0.172664 | 0.732021 | 0.500000 | 0.001388 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.719811 | 0.138956 | 0.300000 | 0.215943 | 0.370548 | 0.500000 | 0.002742 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.14 | 0.138931 | 0.300000 | 0.341159 | 0.370482 | 0.500000 | 0.002742 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.767559 | 0.130303 | 0.300000 | 0.230268 | 0.347475 | 0.500000 | 0.002924 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.635798 | 0.248494 | 0.300000 | 0.190739 | 0.662649 | 0.500000 | 0.001533 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.868871 | 0.115117 | 0.300000 | 0.260661 | 0.306978 | 0.500000 | 0.003310 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.32 | 0.119650 | 0.300000 | 0.396134 | 0.319067 | 0.500000 | 0.003184 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.869018 | 0.115090 | 0.300000 | 0.260705 | 0.306907 | 0.500000 | 0.003310 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29947.59 |
CORE_MID VAV BOX REHEAT COIL | 28825.79 |
CORE_TOP VAV BOX REHEAT COIL | 51931.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23611.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15433.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23494.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15366.98 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18371.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12123.34 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18296.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12074.02 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17816.30 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11718.39 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17714.31 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11665.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.12 | 1.87 | 6.24 | 2.34 | 5.42 | 5.42 | 0.300000 | 0.431339 | 5.42 |
PACU_VAV_MID | 2.99 | 1.89 | 5.97 | 2.67 | 4.90 | 4.90 | 0.300000 | 0.544514 | 4.90 |
PACU_VAV_TOP | 3.08 | 1.97 | 6.16 | 3.95 | 5.35 | 5.35 | 0.300000 | 0.737703 | 5.35 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.42 | 1.17 |
PACU_VAV_MID_OA_CONTROLLER | 4.90 | 1.20 |
PACU_VAV_TOP_OA_CONTROLLER | 5.35 | 1.20 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.17 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.42 | 89788.47 | 0.800655 | 1.81 | 29926.50 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.90 | 81125.32 | 0.800655 | 1.63 | 27039.07 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.35 | 88610.71 | 0.800655 | 1.78 | 29533.95 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 73037.50 |
PACU_VAV_MID HEATING COIL | 76340.99 |
PACU_VAV_TOP HEATING COIL | 76505.78 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.42 |
PACU_VAV_MID FAN | 4.90 |
PACU_VAV_TOP FAN | 5.35 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.889 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7944 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7793 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.119 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1711 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1804 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.025 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.049 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6593 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.466 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.768 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.465 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.29839090E-12 | 0.94613664E-15 | -0.93984276E-13 | 0.14929621E-15 |
43 | 6 | 0.28459516E-07 | 0.22300724E-09 | 0.65212509E-08 | -0.13406672E-12 |
44 | 5 | -0.18903196E-03 | 0.19107794E-05 | -0.97244514E-04 | 0.64472671E-08 |
45 | 4 | 0.29088896 | 0.93090113E-03 | 0.99231010E-01 | -0.33393447E-04 |
46 | 3 | -7.2414209 | 0.28863778E-01 | -2.3315219 | 0.28886944E-01 |
47 | 2 | 40.789004 | 0.10268188 | 15.234791 | -0.33242551 |
48 | 1 | -80.482851 | 0.46359056E-01 | -29.114516 | 1.0772781 |
49 | 0 | 46.824339 | 0.93304599E-03 | 16.291883 | |
50 | 7 | -0.30147866E-12 | 0.32879259E-14 | -0.94788354E-13 | 0.15721988E-15 |
51 | 6 | 0.28638673E-07 | 0.21918405E-09 | 0.65607935E-08 | -0.13498453E-12 |
52 | 5 | -0.18994198E-03 | 0.18758515E-05 | -0.97700529E-04 | 0.64858157E-08 |
53 | 4 | 0.29195434 | 0.91295314E-03 | 0.99614140E-01 | -0.33543711E-04 |
54 | 3 | -7.2625212 | 0.28281717E-01 | -2.3377829 | 0.28990346E-01 |
55 | 2 | 40.858594 | 0.10053100 | 15.260475 | -0.33320057 |
56 | 1 | -80.536180 | 0.45356415E-01 | -29.137544 | 1.0784145 |
57 | 0 | 46.824339 | 0.91224283E-03 | 16.291331 | |
58 | 7 | -0.27660997E-12 | 0.14023004E-14 | -0.80712451E-13 | 0.13354543E-15 |
59 | 6 | 0.24561732E-07 | 0.29965487E-09 | 0.56608975E-08 | -0.11328042E-12 |
60 | 5 | -0.16900662E-03 | 0.26385003E-05 | -0.87174216E-04 | 0.56068092E-08 |
61 | 4 | 0.26710865 | 0.13167816E-02 | 0.90695657E-01 | -0.30074316E-04 |
62 | 3 | -6.7696400 | 0.41706905E-01 | -2.1915874 | 0.26577286E-01 |
63 | 2 | 39.232110 | 0.15116668 | 14.658763 | -0.31509082 |
64 | 1 | -79.288784 | 0.69361307E-01 | -28.597496 | 1.0518338 |
65 | 0 | 46.824347 | 0.14183552E-02 | 16.304685 | |
66 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004390E-14 | -0.93636906E-16 |
67 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
68 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
69 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
70 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
71 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
72 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
73 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
74 | 7 | -0.23440898E-08 | -0.93321999E-15 | 0.55807564E-14 | -0.85509042E-16 |
75 | 6 | 0.50995884E-05 | 0.34521263E-08 | 0.31913593E-02 | -0.26771796E-04 |
76 | 5 | -0.36354987E-03 | 0.20433482E-05 | -0.22380923 | 0.19568975E-02 |
77 | 4 | 0.83423098E-02 | 0.92983792E-04 | 4.8309558 | -0.45278535E-01 |
78 | 3 | -0.73195838E-01 | 0.73920573E-03 | -38.029382 | 0.39874180 |
79 | 2 | 0.25981955 | 0.12294351E-02 | 116.49945 | -1.4181467 |
80 | 1 | -0.37495780 | 0.37443474E-03 | -143.91643 | 2.0491899 |
81 | 0 | 0.18279742 | 0.90747285E-05 | 60.838472 | |
82 | 7 | -0.24742660E-08 | -0.10943249E-14 | 0.58004393E-14 | -0.93636910E-16 |
83 | 6 | 0.48508293E-05 | 0.32725533E-08 | 0.31920885E-02 | -0.26777914E-04 |
84 | 5 | -0.34494329E-03 | 0.19369032E-05 | -0.22385068 | 0.19572633E-02 |
85 | 4 | 0.79096117E-02 | 0.88130937E-04 | 4.8316460 | -0.45285171E-01 |
86 | 3 | -0.69381330E-01 | 0.70057705E-03 | -38.033282 | 0.39878490 |
87 | 2 | 0.24625431 | 0.11650871E-02 | 116.50704 | -1.4182482 |
88 | 1 | -0.35536509 | 0.35482444E-03 | -143.92090 | 2.0492634 |
89 | 0 | 0.17324174 | 0.85915519E-05 | 60.838472 | |
90 | 7 | -0.23439288E-08 | -0.93347870E-15 | 0.55887675E-14 | -0.85663837E-16 |
91 | 6 | 0.50999137E-05 | 0.34523603E-08 | 0.31913583E-02 | -0.26771788E-04 |
92 | 5 | -0.36357417E-03 | 0.20434871E-05 | -0.22380918 | 0.19568970E-02 |
93 | 4 | 0.83428746E-02 | 0.92990125E-04 | 4.8309549 | -0.45278527E-01 |
94 | 3 | -0.73200817E-01 | 0.73925614E-03 | -38.029377 | 0.39874175 |
95 | 2 | 0.25983726 | 0.12295191E-02 | 116.49944 | -1.4181466 |
96 | 1 | -0.37498338 | 0.37446036E-03 | -143.91643 | 2.0491898 |
97 | 0 | 0.18280989 | 0.90753466E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.661 | 1.661 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.24435E-002 | 0.36619 | 0.44086 | 0.44086 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.92517E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3855E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3935E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6359E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6431E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9592E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0066E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3410E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3672E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1467 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1040 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1701 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1257 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3036E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1978E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0374E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8858E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3862E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3981E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6368E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6488E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9633E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0245E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3408E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3669E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1009 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3290E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1053 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6078E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0244E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1017E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8621E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7388E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.7039E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.7404E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.9946E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.0227E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4792E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4888E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0663E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0753E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6825E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7600E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8126E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8810E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8570E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9021E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3408E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3669E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9469E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4510E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7630E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7398E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0889E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6874E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0374E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8858E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6815E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7639E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8097E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.8771E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8533E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8883E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3410E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3672E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2793E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5483E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5761E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0947E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5263E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3323E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8621E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7389E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7347E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.8396E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2178E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3431E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5646E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5929E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0665E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0755E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1593 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1233 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1845 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1481 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1013 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3014E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6644E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6249E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.6398E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.0750E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1006 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.3417E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.7764E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9667E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7222E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6635E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.6111E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.3437E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3589E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5151E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6591E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3545E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6644E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6249E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.9741E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3807E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3090E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9506E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3377E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2320E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7222E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6636E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1593 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1233 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1845 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1481 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1013 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3009E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6639E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6246E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.6403E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.0747E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1006 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.3414E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.7762E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9663E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7217E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6632E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.6115E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.3436E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3592E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5150E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6589E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3542E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6639E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6246E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.9744E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3805E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3092E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9504E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3374E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2317E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7218E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6633E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 41475.72038 | 41475.72038 | 3.03609 | 3.03609 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 11399.81854 | 11399.81854 | 0.48850 | 0.48850 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 31186.14744 | 31186.14744 | 2.28050 | 2.28050 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 20336.74117 | 20336.74117 | 0.87671 | 0.87671 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 30432.32879 | 30432.32879 | 2.24602 | 2.24602 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 26.78800 | 7.00621E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 36521.67694 | 36521.67694 | 1.57945 | 1.57945 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8940.44320 | 8940.44320 | 0.65982 | 0.65982 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 16569.51364 | 16569.51364 | 0.71813 | 0.71813 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11859.54652 | 11859.54652 | 0.87524 | 0.87524 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10829.59600 | 10829.59600 | 0.46939 | 0.46939 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 18955.58959 | 18955.58959 | 1.39894 | 1.39894 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 16487.51388 | 16487.51388 | 0.71457 | 0.71457 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12475.15816 | 12475.15816 | 0.92067 | 0.92067 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10783.22514 | 10783.22514 | 0.46737 | 0.46737 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7798.48830 | 7798.48830 | 0.57555 | 0.57555 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12897.55151 | 12897.55151 | 0.55874 | 0.55874 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9753.35676 | 9753.35676 | 0.71981 | 0.71981 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 22.94600 | 7.00043E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8510.51016 | 8510.51016 | 0.36872 | 0.36872 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 15408.83281 | 15408.83281 | 1.13720 | 1.13720 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12845.03190 | 12845.03190 | 0.55646 | 0.55646 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10400.32430 | 10400.32430 | 0.76756 | 0.76756 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8475.96393 | 8475.96393 | 0.36722 | 0.36722 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8614.96271 | 8614.96271 | 0.63580 | 0.63580 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12509.74246 | 12509.74246 | 0.54187 | 0.54187 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11773.19008 | 11773.19008 | 0.86887 | 0.86887 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 8227.34691 | 8227.34691 | 0.35640 | 0.35640 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 17891.97791 | 17891.97791 | 1.32045 | 1.32045 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 12438.31246 | 12438.31246 | 0.53876 | 0.53876 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11775.16141 | 11775.16141 | 0.86902 | 0.86902 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 8190.44137 | 8190.44137 | 0.35480 | 0.35480 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76975.45 | 5.42412 | 5.42412 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 75789.59 | 2.33964 | 2.33964 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 70060.84 | 4.90078 | 4.90078 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 77843.09 | 2.66854 | 2.66854 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 75854.29 | 5.35297 | 5.35297 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 77874.55 | 3.94890 | 3.94890 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.03609 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24685 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.91083 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65826 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54346E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29947.58927 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28050 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32864 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77765 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87636 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15934E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 28825.78635 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24602 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33368 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79509 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88982 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14181E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 51931.42990 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71813 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21544 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58668 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73178E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23611.78047 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87524 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11428 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26257 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30474 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33394E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15433.18125 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39894 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11294 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41968 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30117 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37356E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23494.71389 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92067 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10863 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27620 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50724E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15366.98162 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57555 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27451 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17266 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73202 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38794E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18371.03044 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71981 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13896 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21594 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37055 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74188E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12123.34190 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13720 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13893 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34116 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37048 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74237E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18296.04330 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76756 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13030 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23027 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34747 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92395E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12074.02019 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63580 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24849 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19074 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66265 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53324E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17816.29563 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86887 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11512 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26066 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30698 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30968E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11718.39212 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32045 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11965 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39613 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31907 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.18428E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17714.31261 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86902 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11509 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26071 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30691 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31045E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11665.70231 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.11810 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.87086 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.23620 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.33964 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.42412 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.42412 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43134 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.98732 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.88589 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.97463 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.66854 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.90078 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.90078 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.54451 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.07950 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96899 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.15900 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.94890 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.35297 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.35297 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.73770 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.42412 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.90078 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.35297 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.42412 |
149 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.16851 |
150 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.16851 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.42412 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89788.46963 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.80786 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29926.49693 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
157 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 73037.49691 |
158 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.42412 |
159 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.90078 |
160 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.19517 |
161 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.90078 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81125.31879 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63343 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27039.06875 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
168 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 76340.98635 |
169 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.90078 |
170 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.35297 |
171 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.19517 |
172 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.35297 |
174 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 88610.71172 |
175 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
176 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.78415 |
177 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29533.95022 |
178 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
179 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 76505.78054 |
180 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.35297 |
181 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
182 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
183 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
184 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
185 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 88243.43 | 301099.09 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 6.1760 | 4.8851 | 3.2737 | 1.3643 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 79729.35 | 272047.85 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.5801 | 4.4137 | 2.9578 | 1.2326 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 87085.94 | 297149.57 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 6.0950 | 4.8210 | 3.2307 | 1.3464 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.119 | 0.959 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.180 | 0.173 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.171 | 0.164 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.794 | 0.710 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.180 | 0.173 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_NORTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_EAST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | N/A | 1.661 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.779 | 0.698 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2925_SHGC_WEST_0.45 | N/A | 1.661 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.5900133509E-002 | 1.6196180245E-002 | Pass | Pass | 0.4875282790 | 0.4922493468 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.3064575166 | 0.2062936708 | Pass | Pass | 0.4878738373 | 0.4916770521 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1503367593 | 9.2716071366E-002 | Pass | Pass | 0.4870202748 | 0.4805005112 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1346170811 | 8.2173206627E-002 | Pass | Pass | 0.4856120445 | 0.4820502500 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.3219220786E-002 | 5.9995357951E-002 | Pass | Pass | 0.8422019176 | 0.7444025774 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2038118041 | 0.1985941347 | Pass | Pass | 0.7792643240 | 0.6992496733 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7818039429 | 0.7056666181 | Pass | Pass | 0.6207315995 | 0.5898933325 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8122222968 | 0.8063424221 | Pass | Pass | 0.6723835576 | 0.6420623345 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7695633992 | 0.7673653651 | Pass | Pass | 0.6813041712 | 0.6576159335 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8089722658 | 0.8074331608 | Pass | Pass | 0.6764844210 | 0.6474307708 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6211199265 | 0.5624498565 | Pass | Pass | 0.6312516794 | 0.6311943791 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6588711845 | 0.6474161744 | Pass | Pass | 0.7052277188 | 0.7211083058 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6142332916 | 0.6080979469 | Pass | Pass | 0.7154542794 | 0.7354438576 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6562398471 | 0.6511975894 | Pass | Pass | 0.7057543575 | 0.7189240426 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5913389508 | 0.5496531680 | Pass | Pass | 0.6760628196 | 0.5927098652 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6281541330 | 0.6260600091 | Pass | Pass | 0.7052805842 | 0.6362415755 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5909303118 | 0.5856914155 | Pass | Pass | 0.7135303654 | 0.6435310614 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6260162921 | 0.6235980574 | Pass | Pass | 0.7052361452 | 0.6363757179 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2453.61 | 216.98 | 0.00 | 3077.20 | 337.95 | 6085.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.959 | 1.119 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.166 | 0.171 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.710 | 0.794 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.175 | 0.180 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.698 | 0.779 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.2925_SHGC_EAST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.2925_SHGC_WEST_0.45 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.661 | 0.451 | 0.452 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2925_SHGC_NORTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2925_SHGC_EAST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2925_SHGC_SOUTH_0.45 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2925_SHGC_WEST_0.45 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.661 | 0.451 | 0.452 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 177.99 | 1.661 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 415.31 | 1.661 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.62 | 0.0000 | Y | 12.90 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.34 | 0.0000 | Y | 8.11 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 35.94 | 0.0000 | Y | 12.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.26 | 0.0000 | Y | 8.09 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.54 | 0.0000 | Y | 12.88 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.29 | 0.0000 | Y | 8.10 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 35.88 | 0.0000 | Y | 12.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.21 | 0.0000 | Y | 8.08 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.62 | 0.0000 | Y | 12.90 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.34 | 0.0000 | Y | 8.11 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 35.94 | 0.0000 | Y | 12.66 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 36.26 | 0.0000 | Y | 8.09 |
Interior Lighting Total | 9.0546 | 4982.19 | 45111.81 | 370.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.25 | AstronomicalClock | - | 44.84 | 44.84 | 3.57 | |
EXTERIOR_LIGHTS_B | 8043.62 | AstronomicalClock | - | 83.06 | 71.59 | 108.10 | |
Exterior Lighting Total | 8467.87 | 111.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89788.47 | 71889.61 | 17898.86 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81125.32 | 64953.41 | 16171.91 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 88610.71 | 70946.63 | 17664.08 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 88243.4 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_MID COOLING COIL | 79729.4 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_TOP COOLING COIL | 87085.9 | 2.80 | 9.54 | N/A | N/A | 10.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 29947.59 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 28825.79 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 51931.43 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23611.78 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15433.18 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 23494.71 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15366.98 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18371.03 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12123.34 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18296.04 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12074.02 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17816.30 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11718.39 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17714.31 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11665.70 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 73037.50 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 76340.99 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 76505.78 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.42 | 12467.13 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.90 | 11264.26 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.35 | 12303.60 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88243.43 | 2.80 | 9.54 | 10.81 | 6.1760 | 3.09 | 10.55 | 4.8851 | 3.26 | 11.11 | 3.2737 | 3.43 | 11.69 | 1.3643 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 79729.35 | 2.80 | 9.54 | 10.81 | 5.5801 | 3.09 | 10.55 | 4.4137 | 3.26 | 11.11 | 2.9578 | 3.43 | 11.69 | 1.2326 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 87085.94 | 2.80 | 9.54 | 10.81 | 6.0950 | 3.09 | 10.55 | 4.8210 | 3.26 | 11.11 | 3.2307 | 3.43 | 11.69 | 1.3464 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 41475.72 | 41475.72 | 42.17 | 3.036 | 3.036 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00879 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 31186.15 | 31186.15 | 31.71 | 2.280 | 2.280 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 30432.33 | 30432.33 | 30.94 | 2.246 | 2.246 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 24.00 | 24.00 | 0.00889 | 26.79 | 0.00701 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8940.44 | 8940.44 | 43.12 | 0.660 | 0.660 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00872 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11859.55 | 11859.55 | 90.35 | 0.875 | 0.875 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00861 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 18955.59 | 18955.59 | 91.42 | 1.399 | 1.399 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00861 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12475.16 | 12475.16 | 95.05 | 0.921 | 0.921 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00860 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7798.49 | 7798.49 | 37.61 | 0.576 | 0.576 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00879 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9753.36 | 9753.36 | 74.30 | 0.720 | 0.720 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00865 | 22.95 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 15408.83 | 15408.83 | 74.32 | 1.137 | 1.137 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00865 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10400.32 | 10400.32 | 79.24 | 0.768 | 0.768 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00864 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8614.96 | 8614.96 | 41.55 | 0.636 | 0.636 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00874 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11773.19 | 11773.19 | 89.69 | 0.869 | 0.869 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00861 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 17891.98 | 17891.98 | 86.29 | 1.320 | 1.320 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00862 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11775.16 | 11775.16 | 89.71 | 0.869 | 0.869 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00861 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 11399.82 | 11399.82 | 11.59 | 0.489 | 0.489 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 20336.74 | 20336.74 | 20.68 | 0.877 | 0.877 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 36521.68 | 36521.68 | 37.13 | 1.579 | 1.579 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 16569.51 | 16569.51 | 79.92 | 0.718 | 0.718 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10829.60 | 10829.60 | 82.50 | 0.469 | 0.469 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16487.51 | 16487.51 | 79.52 | 0.715 | 0.715 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10783.23 | 10783.23 | 82.16 | 0.467 | 0.467 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12897.55 | 12897.55 | 62.21 | 0.559 | 0.559 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8510.51 | 8510.51 | 64.84 | 0.369 | 0.369 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12845.03 | 12845.03 | 61.95 | 0.556 | 0.556 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8475.96 | 8475.96 | 64.58 | 0.367 | 0.367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12509.74 | 12509.74 | 60.33 | 0.542 | 0.542 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8227.35 | 8227.35 | 62.68 | 0.356 | 0.356 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12438.31 | 12438.31 | 59.99 | 0.539 | 0.539 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8190.44 | 8190.44 | 62.40 | 0.355 | 0.355 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.42 | 5.42 | 2.34 | 2.34 | 5.4241 | 2.3396 | 5.4241 | 0.4313 | 0.3000 |
PACU_VAV_MID | 4.90 | 4.90 | 2.67 | 2.67 | 4.9008 | 2.6685 | 4.9008 | 0.5445 | 0.3000 |
PACU_VAV_TOP | 5.35 | 5.35 | 3.95 | 3.95 | 5.3530 | 3.9489 | 5.3530 | 0.7377 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29947.589 | 29947.589 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29947.59 | 16061.71 | 0.488502 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 11399.82 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 28825.786 | 28825.786 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28825.79 | 28825.79 | 0.876709 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 20336.74 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 51931.430 | 51931.430 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51931.43 | 51931.43 | 1.579446 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 36521.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23611.780 | 23611.780 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23611.78 | 23611.78 | 0.718130 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796760 | 50.7101 | 16569.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15433.181 | 15433.181 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15433.18 | 15433.18 | 0.469386 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796695 | 50.7060 | 10829.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 23494.714 | 23494.714 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23494.71 | 23494.71 | 0.714570 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796743 | 50.7090 | 16487.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15366.982 | 15366.982 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15366.98 | 15366.98 | 0.467372 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796681 | 50.7051 | 10783.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18371.030 | 18371.030 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18371.03 | 18371.03 | 0.558738 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797763 | 50.7728 | 12897.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12123.342 | 12123.342 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12123.34 | 12123.34 | 0.368720 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797748 | 50.7719 | 8510.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18296.043 | 18296.043 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18296.04 | 18296.04 | 0.556457 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797752 | 50.7722 | 12845.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12074.020 | 12074.020 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12074.02 | 12074.02 | 0.367220 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797738 | 50.7713 | 8475.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17816.296 | 17816.296 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17816.30 | 17816.30 | 0.541866 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796398 | 50.6872 | 12509.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11718.392 | 11718.392 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11718.39 | 11718.39 | 0.356404 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796358 | 50.6848 | 8227.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17714.313 | 17714.313 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17714.31 | 17714.31 | 0.538764 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796375 | 50.6858 | 12438.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11665.702 | 11665.702 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11665.70 | 11665.70 | 0.354801 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00796341 | 50.6837 | 8190.44 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 89788.470 | 71889.610 | 5.424121 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 91205.32 | 91205.32 | 5.424121 | 24.73 | 16.39 | 0.00838419 | 10.90 | 10.90 | 0.00838419 | 27.40 | 0.00700714 | 16.15 | 21.5428 | 24.00 | 0.00876309 | 46.4225 | 73375.99 | 0.00 | 92583.96 | 72291.98 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 73037.497 | 73037.497 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73037.50 | 73037.50 | 1.627236 | -24.88 | -24.88 | 0.00228987 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 71.8095 | 18.08 | 0.00795993 | 60.7391 | 21933.85 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 81125.319 | 64953.413 | 4.900781 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 82405.47 | 82405.47 | 4.900781 | 24.83 | 16.39 | 0.00834936 | 10.90 | 10.90 | 0.00834936 | 27.40 | 0.00700714 | 16.15 | 24.3873 | 24.00 | 0.00878366 | 46.5298 | 66243.16 | 0.00 | 83651.09 | 65316.96 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 76340.986 | 76340.986 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76340.99 | 76340.99 | 1.470234 | -30.79 | -30.79 | 0.00153728 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 81.2911 | 17.60 | 0.00790839 | 62.2110 | 23135.31 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 88610.712 | 70946.632 | 5.352973 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 90056.39 | 90056.39 | 5.352973 | 24.74 | 16.37 | 0.00836438 | 10.90 | 10.90 | 0.00836438 | 27.30 | 0.00700699 | 16.11 | 22.3272 | 24.00 | 0.00875635 | 46.3871 | 72275.14 | 0.00 | 91369.54 | 71343.72 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 76505.781 | 76505.781 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76505.78 | 76505.78 | 1.605892 | -27.19 | -27.19 | 0.00207722 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 74.4241 | 15.60 | 0.00790937 | 70.6583 | 25647.65 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 29947.589 | 29947.589 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29947.59 | 16061.71 | 1.0000 | 0.57908924 | 0.488502 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29947.59 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 11399.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 28825.786 | 28825.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28825.79 | 28825.79 | 1.0000 | 1.03928558 | 0.876709 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28825.79 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 20336.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 51931.430 | 51931.430 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51931.43 | 51931.43 | 1.0000 | 1.87233699 | 1.579446 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51931.43 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 36521.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 23611.780 | 23611.780 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23611.78 | 23611.78 | 1.0000 | 0.85129969 | 0.718130 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23611.78 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796760 | 21.00 | 0.00796760 | 50.7101 | 16569.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 15433.181 | 15433.181 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15433.18 | 15433.18 | 1.0000 | 0.55642828 | 0.469386 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15433.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796695 | 21.00 | 0.00796695 | 50.7060 | 10829.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 23494.714 | 23494.714 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23494.71 | 23494.71 | 1.0000 | 0.84707896 | 0.714570 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23494.71 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796743 | 21.00 | 0.00796743 | 50.7090 | 16487.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 15366.982 | 15366.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15366.98 | 15366.98 | 1.0000 | 0.55404151 | 0.467372 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15366.98 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796681 | 21.00 | 0.00796681 | 50.7051 | 10783.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18371.030 | 18371.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18371.03 | 18371.03 | 1.0000 | 0.66234956 | 0.558738 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18371.03 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797763 | 21.00 | 0.00797763 | 50.7728 | 12897.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12123.342 | 12123.342 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12123.34 | 12123.34 | 1.0000 | 0.43709525 | 0.368720 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12123.34 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797748 | 21.00 | 0.00797748 | 50.7719 | 8510.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18296.043 | 18296.043 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18296.04 | 18296.04 | 1.0000 | 0.65964597 | 0.556457 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18296.04 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797752 | 21.00 | 0.00797752 | 50.7722 | 12845.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12074.020 | 12074.020 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12074.02 | 12074.02 | 1.0000 | 0.43531701 | 0.367220 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12074.02 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797738 | 21.00 | 0.00797738 | 50.7713 | 8475.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17816.296 | 17816.296 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17816.30 | 17816.30 | 1.0000 | 0.64234914 | 0.541866 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17816.30 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796398 | 21.00 | 0.00796398 | 50.6872 | 12509.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11718.392 | 11718.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11718.39 | 11718.39 | 1.0000 | 0.42249518 | 0.356404 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11718.39 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796358 | 21.00 | 0.00796358 | 50.6848 | 8227.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17714.313 | 17714.313 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17714.31 | 17714.31 | 1.0000 | 0.63867224 | 0.538764 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17714.31 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796375 | 21.00 | 0.00796375 | 50.6858 | 12438.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11665.702 | 11665.702 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11665.70 | 11665.70 | 1.0000 | 0.42059550 | 0.354801 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11665.70 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00796341 | 21.00 | 0.00796341 | 50.6837 | 8190.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89788.470 | 71889.610 | 5.424121 | -999.0 | -999.000 | -999.0000 | 1.03064 | 1.00000 | 1020.4258 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.424121 | 6.42996670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 91205.32 | 91205.32 | 1.0158 | 6.42996670 | 5.424121 | 24.73 | 16.39 | 0.00838419 | 46206.3 | 10.90 | 10.90 | 0.00838419 | 32090.9 | -999.0 | -999.00 | -999.00 | -999.00 | 12467.135 | 78738.19 | 27.40 | 0.00700714 | 16.15 | 1.16851000 | 21.5428 | 24.00 | 0.00876309 | 24.00 | 0.00876309 | 46.4225 | 73375.99 | 0.00 | 92583.96 | 72291.98 | 6.17603162 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 73037.497 | 73037.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.424121 | 6.42996670 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 73037.50 | 73037.50 | 1.0000 | 1.92899001 | 1.627236 | -24.88 | -24.88 | 0.00228987 | -19379.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 73037.50 | -41.90 | 0.00006450 | -41.90 | 1.16851000 | 71.8095 | 18.47 | 0.00795851 | 18.08 | 0.00795993 | 60.7391 | 21933.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81125.319 | 64953.413 | 4.900781 | -999.0 | -999.000 | -999.0000 | 1.02374 | 1.00000 | 1020.3610 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.900781 | 5.80957778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 82405.47 | 82405.47 | 1.0158 | 5.80957778 | 4.900781 | 24.83 | 16.39 | 0.00834936 | 46217.2 | 10.90 | 10.90 | 0.00834936 | 32003.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11264.256 | 71141.21 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 24.3873 | 24.00 | 0.00878366 | 24.00 | 0.00878366 | 46.5298 | 66243.16 | 0.00 | 83651.09 | 65316.96 | 5.58014338 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76340.986 | 76340.986 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.900781 | 5.80957778 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76340.99 | 76340.99 | 1.0000 | 1.74287334 | 1.470234 | -30.79 | -30.79 | 0.00153728 | -27182.4 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76340.99 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 81.2911 | 17.48 | 0.00793658 | 17.60 | 0.00790839 | 62.2110 | 23135.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 88610.712 | 70946.632 | 5.352973 | -999.0 | -999.000 | -999.0000 | 1.03080 | 1.00000 | 1020.3890 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.352973 | 6.34562465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 90056.39 | 90056.39 | 1.0163 | 6.34562465 | 5.352973 | 24.74 | 16.37 | 0.00836438 | 46161.4 | 10.90 | 10.90 | 0.00836438 | 32040.9 | -999.0 | -999.00 | -999.00 | -999.00 | 12303.603 | 77752.79 | 27.30 | 0.00700699 | 16.11 | 1.19517000 | 22.3272 | 24.00 | 0.00875635 | 24.00 | 0.00875635 | 46.3871 | 72275.14 | 0.00 | 91369.54 | 71343.72 | 6.09502044 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76505.781 | 76505.781 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.352973 | 6.34562465 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76505.78 | 76505.78 | 1.0000 | 1.90368739 | 1.605892 | -27.19 | -27.19 | 0.00207722 | -22235.5 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76505.78 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 74.4241 | 15.60 | 0.00793406 | 15.60 | 0.00790937 | 70.6583 | 25647.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 1.17 | 5.42 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 4.90 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.35 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1998.50 | 3714.33 | 1037.00 |
CORE_MID | 2698.00 | 4248.67 | 2123.33 |
CORE_TOP | 3204.17 | 4550.83 | 2768.00 |
PERIMETER_TOP_ZN_3 | 3901.67 | 4682.00 | 3322.50 |
PERIMETER_TOP_ZN_2 | 4011.50 | 4515.00 | 3125.33 |
PERIMETER_TOP_ZN_1 | 3865.50 | 4536.17 | 2945.50 |
PERIMETER_TOP_ZN_4 | 3864.50 | 4921.50 | 3248.33 |
PERIMETER_BOT_ZN_3 | 3640.67 | 4690.33 | 3179.83 |
PERIMETER_BOT_ZN_2 | 3933.33 | 4325.67 | 2937.17 |
PERIMETER_BOT_ZN_1 | 3670.33 | 4709.17 | 2899.33 |
PERIMETER_BOT_ZN_4 | 3663.17 | 4828.17 | 3070.33 |
PERIMETER_MID_ZN_3 | 3745.17 | 4458.50 | 3054.00 |
PERIMETER_MID_ZN_2 | 3267.17 | 3792.83 | 2490.83 |
PERIMETER_MID_ZN_1 | 3673.83 | 4311.33 | 2640.00 |
PERIMETER_MID_ZN_4 | 3703.67 | 4733.00 | 2994.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5194.83 | 5313.00 | 3454.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.67 | 0.00 | 0.50 | 0.00 |
CORE_MID | 4.83 | 0.00 | 3.67 | 0.00 |
CORE_TOP | 23.33 | 0.00 | 15.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 417.83 | 0.17 | 215.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 262.00 | 5.17 | 67.83 | 5.17 |
PERIMETER_TOP_ZN_1 | 220.83 | 7.33 | 53.67 | 7.33 |
PERIMETER_TOP_ZN_4 | 264.33 | 5.50 | 73.33 | 1.67 |
PERIMETER_BOT_ZN_3 | 236.83 | 0.33 | 173.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 82.17 | 4.33 | 21.50 | 4.17 |
PERIMETER_BOT_ZN_1 | 1002.00 | 3.00 | 932.83 | 3.00 |
PERIMETER_BOT_ZN_4 | 83.83 | 0.33 | 20.83 | 0.00 |
PERIMETER_MID_ZN_3 | 148.00 | 2.33 | 80.67 | 0.00 |
PERIMETER_MID_ZN_2 | 96.83 | 7.00 | 26.50 | 6.83 |
PERIMETER_MID_ZN_1 | 74.17 | 9.00 | 18.00 | 9.00 |
PERIMETER_MID_ZN_4 | 98.00 | 6.50 | 27.17 | 1.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1316.67 | 38.17 | 1044.17 | 29.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.974 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.731 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.699 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.936 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.755 | 0.056 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.807 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.673 | 0.056 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.758 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.465 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.482 | 1.360 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 1.357 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.897 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.661 | 0.050 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.798 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.645 | 0.047 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15585583.10 | 0.00 | 15585583.10 | 0.00 | 15585583.10 | 13393058.27 | 4159.22 | 7.34 | 4593.44 | 483.60 |
CORE_MID | 11687776.01 | 0.00 | 11687776.01 | 0.00 | 11687776.01 | 13393058.27 | 4224.58 | 21.31 | 4514.12 | 416.98 |
CORE_TOP | 11122775.81 | 0.00 | 11122775.81 | 0.00 | 11122775.81 | 13393058.27 | 4252.94 | 24.71 | 4482.35 | 92.38 |
PERIMETER_TOP_ZN_3 | 3140617.39 | 0.00 | 3140617.39 | 370406.43 | 3511023.82 | 2823374.22 | 4185.45 | 2.24 | 4572.31 | 92.38 |
PERIMETER_TOP_ZN_2 | 3730437.97 | 0.00 | 3730437.97 | 246936.13 | 3977374.10 | 1787429.43 | 4146.02 | 0.94 | 4613.03 | 92.38 |
PERIMETER_TOP_ZN_1 | 6065353.19 | 0.00 | 6065353.19 | 370406.43 | 6435759.61 | 2823374.22 | 4145.61 | 0.83 | 4613.56 | 92.38 |
PERIMETER_TOP_ZN_4 | 3566341.33 | 0.00 | 3566341.33 | 246936.13 | 3813277.46 | 1787312.18 | 4144.13 | 0.92 | 4614.95 | 92.38 |
PERIMETER_BOT_ZN_3 | 2572200.90 | 0.00 | 2572200.90 | 196941.88 | 2769142.78 | 2823374.22 | 4338.89 | 37.73 | 4383.37 | 483.60 |
PERIMETER_BOT_ZN_2 | 3146568.48 | 0.00 | 3146568.48 | 131293.80 | 3277862.28 | 1787429.43 | 4106.30 | 3.15 | 4650.55 | 483.60 |
PERIMETER_BOT_ZN_1 | 5053144.05 | 0.00 | 5053144.05 | 4689941.95 | 9743086.00 | 2823374.22 | 4105.55 | 3.30 | 4651.15 | 483.60 |
PERIMETER_BOT_ZN_4 | 2928441.90 | 0.00 | 2928441.90 | 131293.80 | 3059735.70 | 1787312.18 | 4093.97 | 3.90 | 4662.13 | 483.60 |
PERIMETER_MID_ZN_3 | 3023439.52 | 0.00 | 3023439.52 | 308333.93 | 3331773.45 | 2823374.22 | 4154.30 | 6.76 | 4598.94 | 416.94 |
PERIMETER_MID_ZN_2 | 3842801.01 | 0.00 | 3842801.01 | 205554.72 | 4048355.73 | 1787429.43 | 4086.28 | 2.54 | 4671.18 | 1325.91 |
PERIMETER_MID_ZN_1 | 6064002.35 | 0.00 | 6064002.35 | 308333.93 | 6372336.28 | 2823374.22 | 4090.76 | 3.26 | 4665.97 | 416.98 |
PERIMETER_MID_ZN_4 | 3525094.33 | 0.00 | 3525094.33 | 205554.72 | 3730649.05 | 1787312.18 | 4086.21 | 2.63 | 4671.16 | 416.91 |
Total Facility | 85054577.32 | 0.00 | 85054577.32 | 7411933.84 | 92466511.17 | 67843644.98 | 4491.68 | 106.60 | 4758.49 | 1558.69 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7132 | 0.0000 | 0.7132 | 0.0000 | 0.7132 | 0.4247 | 1420.43 | 6.81 | 4515.76 |
CORE_MID | 0.5363 | 0.0000 | 0.5363 | 0.0000 | 0.5363 | 0.4247 | 1472.26 | 21.16 | 4449.58 |
CORE_TOP | 0.5131 | 0.0000 | 0.5131 | 0.0000 | 0.5131 | 0.4247 | 1486.99 | 24.37 | 4431.63 |
PERIMETER_TOP_ZN_3 | 0.1449 | 0.0000 | 0.1449 | 0.0083 | 0.1533 | 0.0895 | 1421.37 | 2.24 | 4519.39 |
PERIMETER_TOP_ZN_2 | 0.1721 | 0.0000 | 0.1721 | 0.0056 | 0.1777 | 0.0567 | 1381.95 | 0.94 | 4560.11 |
PERIMETER_TOP_ZN_1 | 0.2800 | 0.0000 | 0.2800 | 0.0083 | 0.2883 | 0.0895 | 1381.53 | 0.83 | 4560.63 |
PERIMETER_TOP_ZN_4 | 0.1643 | 0.0000 | 0.1643 | 0.0056 | 0.1698 | 0.0567 | 1380.05 | 0.92 | 4562.03 |
PERIMETER_BOT_ZN_3 | 0.1174 | 0.0000 | 0.1174 | 0.0044 | 0.1219 | 0.0895 | 1597.29 | 37.36 | 4308.35 |
PERIMETER_BOT_ZN_2 | 0.1437 | 0.0000 | 0.1437 | 0.0030 | 0.1466 | 0.0567 | 1370.25 | 3.10 | 4569.65 |
PERIMETER_BOT_ZN_1 | 0.2308 | 0.0000 | 0.2308 | 0.2144 | 0.4453 | 0.0895 | 1369.54 | 3.25 | 4570.21 |
PERIMETER_BOT_ZN_4 | 0.1332 | 0.0000 | 0.1332 | 0.0030 | 0.1362 | 0.0567 | 1358.05 | 3.88 | 4581.07 |
PERIMETER_MID_ZN_3 | 0.1388 | 0.0000 | 0.1388 | 0.0069 | 0.1457 | 0.0895 | 1403.21 | 6.76 | 4533.03 |
PERIMETER_MID_ZN_2 | 0.1629 | 0.0000 | 0.1629 | 0.0050 | 0.1679 | 0.0567 | 1335.22 | 2.54 | 3696.23 |
PERIMETER_MID_ZN_1 | 0.2785 | 0.0000 | 0.2785 | 0.0069 | 0.2854 | 0.0895 | 1339.67 | 3.26 | 4600.07 |
PERIMETER_MID_ZN_4 | 0.1614 | 0.0000 | 0.1614 | 0.0046 | 0.1660 | 0.0567 | 1335.16 | 2.63 | 4605.21 |
Total Facility | 3.8909 | 0.0000 | 3.8909 | 0.2760 | 4.1668 | 2.1513 | 1699.62 | 105.13 | 4643.95 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 41154508.21 | 0.00 | 41154508.21 | 22614548.33 | 4112.22 | 3.17 | 4644.61 | 483.60 |
PACU_VAV_MID | 39548582.64 | 0.00 | 39548582.64 | 22614548.33 | 4107.94 | 0.77 | 4651.29 | 415.76 |
PACU_VAV_TOP | 38821220.54 | 0.00 | 38821220.54 | 22614548.33 | 4157.38 | 1.73 | 4600.89 | 92.27 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.8808 | 0.0000 | 1.8808 | 0.7171 | 1376.07 | 3.17 | 4563.75 |
PACU_VAV_MID | 1.8147 | 0.0000 | 1.8147 | 0.7171 | 1356.84 | 0.77 | 4585.38 |
PACU_VAV_TOP | 1.7910 | 0.0000 | 1.7910 | 0.7171 | 1393.30 | 1.73 | 4547.97 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 2569.99 | 2770.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 2740.13 | 2558.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 2769.31 | 2036.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.6427 | 3.0436 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.6796 | 2.8863 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.6797 | 3.0827 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 830 |
Defaulted Fields | 545 |
Fields with Defaults | 2289 |
Autosized Fields | 155 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
Electricity:Building | 1132.38 | 15718.93 | 29-JAN-11:10 | 83699.98 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 329.05 | 4741.03 | 01-JAN-00:10 | 25654.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1132.38 | 15718.93 | 29-JAN-11:10 | 83699.98 | 02-JAN-08:10 |
InteriorLights:Electricity | 370.34 | 1693.55 | 29-JAN-11:10 | 36137.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 370.34 | 1693.55 | 29-JAN-11:10 | 36137.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 370.34 | 1693.55 | 29-JAN-11:10 | 36137.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 370.34 | 1693.55 | 29-JAN-11:10 | 36137.71 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 39.59 | 553.47 | 29-JAN-11:10 | 3009.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 12.90 | 51.50 | 29-JAN-11:10 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 12.90 | 51.50 | 29-JAN-11:10 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 25.00 | 350.37 | 15-JAN-11:20 | 1905.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.11 | 32.61 | 15-JAN-11:20 | 952.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.11 | 32.61 | 15-JAN-11:20 | 952.10 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 39.35 | 553.47 | 08-JAN-11:20 | 3009.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 12.66 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 12.66 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.98 | 350.37 | 22-JAN-11:40 | 1905.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.09 | 32.60 | 22-JAN-11:40 | 952.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.09 | 32.60 | 22-JAN-11:40 | 952.03 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 39.57 | 553.47 | 29-JAN-11:00 | 3009.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 12.88 | 51.50 | 29-JAN-11:00 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 12.88 | 51.50 | 29-JAN-11:00 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.99 | 350.37 | 15-JAN-11:10 | 1905.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.10 | 32.61 | 15-JAN-11:10 | 952.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.10 | 32.61 | 15-JAN-11:10 | 952.10 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 39.33 | 553.47 | 08-JAN-11:20 | 3009.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 12.64 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 12.64 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.97 | 350.37 | 22-JAN-11:30 | 1905.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.08 | 32.60 | 22-JAN-11:30 | 952.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.08 | 32.60 | 22-JAN-11:30 | 952.03 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 39.59 | 553.47 | 29-JAN-11:10 | 3009.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 12.90 | 51.50 | 29-JAN-11:10 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 12.90 | 51.50 | 29-JAN-11:10 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 25.00 | 350.37 | 15-JAN-11:20 | 1905.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 8.11 | 32.61 | 15-JAN-11:20 | 952.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 8.11 | 32.61 | 15-JAN-11:20 | 952.10 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 39.35 | 553.47 | 08-JAN-11:20 | 3009.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 12.66 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 12.66 | 51.50 | 08-JAN-11:20 | 1503.90 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.98 | 350.37 | 22-JAN-11:40 | 1905.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 8.09 | 32.60 | 22-JAN-11:40 | 952.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 8.09 | 32.60 | 22-JAN-11:40 | 952.03 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 905.81 | 286.22 | 05-FEB-12:00 | 244831.47 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 18.94 | 285.40 | 01-JAN-00:10 | 1360.76 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 18.94 | 285.40 | 01-JAN-00:10 | 1360.76 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
ElectricityNet:Plant | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 2149.88 | 16005.15 | 02-APR-17:30 | 289219.99 | 02-JAN-08:10 |
Heating:Electricity | 696.52 | 0.00 | 01-JAN-00:40 | 234755.32 | 02-JAN-06:20 |
General:Heating:Electricity | 696.52 | 0.00 | 01-JAN-00:40 | 234755.32 | 02-JAN-06:20 |
Fans:Electricity | 111.63 | 0.00 | 01-JAN-00:40 | 28869.60 | 12-JUL-15:10 |
General:Fans:Electricity | 111.63 | 0.00 | 01-JAN-00:40 | 28869.60 | 12-JUL-15:10 |
ExteriorLights:Electricity | 111.67 | 0.00 | 01-JAN-11:20 | 8467.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.67 | 0.00 | 01-JAN-11:20 | 8467.87 | 01-JAN-06:10 |
HeatRecovery:Electricity | 26.22 | 0.00 | 01-JAN-00:10 | 2703.51 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 26.22 | 0.00 | 01-JAN-00:10 | 2703.51 | 02-JAN-07:10 |
Cooling:Electricity | 52.49 | 0.00 | 01-JAN-00:10 | 49715.30 | 30-JUN-14:30 |
General:Cooling:Electricity | 52.49 | 0.00 | 01-JAN-00:10 | 49715.30 | 30-JUN-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.41 | 0.00 | 01-JAN-00:10 | 1015.47 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 475.00 | 1156.00 | 11-JAN-22:10 | 281859.73 | 12-JAN-08:10 |
NaturalGas:HVAC | 348.68 | 0.00 | 01-JAN-00:40 | 273471.97 | 12-JAN-07:40 |
Heating:NaturalGas | 348.68 | 0.00 | 01-JAN-00:40 | 273471.97 | 12-JAN-07:40 |
General:Heating:NaturalGas | 348.68 | 0.00 | 01-JAN-00:40 | 273471.97 | 12-JAN-07:40 |
NaturalGas:Plant | 126.32 | 1156.00 | 03-JAN-05:10 | 13401.28 | 27-FEB-12:30 |
WaterSystems:NaturalGas | 126.32 | 1156.00 | 03-JAN-05:10 | 13401.28 | 27-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 126.32 | 1156.00 | 03-JAN-05:10 | 13401.28 | 27-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3373.61 | 0.00 | 01-JAN-00:40 | 655530.20 | 27-FEB-07:10 |
EnergyTransfer:Building | 1426.85 | 0.00 | 01-JAN-00:40 | 235177.94 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 205.70 | 0.00 | 01-JAN-00:40 | 26771.45 | 24-JUL-08:00 |
Heating:EnergyTransfer | 602.62 | 0.00 | 01-JAN-00:40 | 235177.94 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.22 | 0.00 | 01-JAN-00:20 | 23977.85 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 602.62 | 0.00 | 01-JAN-00:40 | 235177.94 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.22 | 0.00 | 01-JAN-00:20 | 23977.85 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 824.23 | 0.00 | 01-JAN-00:40 | 164358.74 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 204.48 | 0.00 | 01-JAN-00:40 | 26771.45 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 824.23 | 0.00 | 01-JAN-00:40 | 164358.74 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 204.48 | 0.00 | 01-JAN-00:40 | 26771.45 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.27 | 0.00 | 01-JAN-00:40 | 19714.42 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.65 | 0.00 | 01-JAN-00:40 | 19714.42 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 79.65 | 0.00 | 01-JAN-00:40 | 19714.42 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.62 | 0.00 | 01-JAN-00:10 | 8645.31 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.62 | 0.00 | 01-JAN-00:10 | 8645.31 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 43.94 | 0.00 | 01-JAN-00:40 | 11839.34 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.77 | 0.00 | 01-JAN-00:40 | 11839.34 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.77 | 0.00 | 01-JAN-00:40 | 11839.34 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.17 | 0.00 | 01-JAN-00:10 | 4907.00 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.17 | 0.00 | 01-JAN-00:10 | 4907.00 | 12-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 40.62 | 0.00 | 01-JAN-00:40 | 10286.91 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.59 | 0.00 | 01-JAN-00:40 | 10286.91 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.59 | 0.00 | 01-JAN-00:40 | 10286.91 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.03 | 0.00 | 01-JAN-00:10 | 5333.53 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.03 | 0.00 | 01-JAN-00:10 | 5333.53 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 132.29 | 0.00 | 01-JAN-00:40 | 24897.55 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.77 | 0.00 | 01-JAN-00:40 | 24897.55 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.77 | 0.00 | 01-JAN-00:40 | 24897.55 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 123.52 | 0.00 | 01-JAN-00:20 | 18882.65 | 24-JUL-09:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 123.52 | 0.00 | 01-JAN-00:20 | 18882.65 | 24-JUL-09:50 |
EnergyTransfer:Zone:CORE_TOP | 135.22 | 0.00 | 01-JAN-00:40 | 29582.68 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 32.56 | 0.00 | 01-JAN-00:40 | 29582.68 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 32.56 | 0.00 | 01-JAN-00:40 | 29582.68 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 102.66 | 0.00 | 01-JAN-00:20 | 19433.46 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 102.66 | 0.00 | 01-JAN-00:20 | 19433.46 | 12-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.01 | 0.00 | 01-JAN-00:40 | 10451.52 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.77 | 0.00 | 01-JAN-00:40 | 10451.52 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.77 | 0.00 | 01-JAN-00:40 | 10451.52 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.24 | 0.00 | 01-JAN-00:10 | 6365.51 | 30-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.24 | 0.00 | 01-JAN-00:10 | 6365.51 | 30-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 59.70 | 0.00 | 01-JAN-00:40 | 10943.34 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.88 | 0.00 | 01-JAN-00:40 | 10793.79 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.88 | 0.00 | 01-JAN-00:40 | 10793.79 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.82 | 0.00 | 01-JAN-00:10 | 10943.34 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.82 | 0.00 | 01-JAN-00:10 | 10943.34 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.31 | 0.00 | 01-JAN-00:40 | 16990.97 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.61 | 0.00 | 01-JAN-00:40 | 16990.97 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 42.61 | 0.00 | 01-JAN-00:40 | 16990.97 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.70 | 0.00 | 01-JAN-00:20 | 15762.87 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.70 | 0.00 | 01-JAN-00:20 | 15762.87 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.68 | 0.00 | 01-JAN-00:40 | 11236.05 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.70 | 0.00 | 01-JAN-00:40 | 11236.05 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.70 | 0.00 | 01-JAN-00:40 | 11236.05 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.98 | 0.00 | 01-JAN-00:20 | 8801.55 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.98 | 0.00 | 01-JAN-00:20 | 8801.55 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 53.99 | 0.00 | 01-JAN-00:40 | 8074.44 | 21-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.72 | 0.00 | 01-JAN-00:40 | 8074.44 | 21-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.72 | 0.00 | 01-JAN-00:40 | 8074.44 | 21-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.26 | 0.00 | 01-JAN-00:10 | 5389.68 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.26 | 0.00 | 01-JAN-00:10 | 5389.68 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 47.30 | 0.00 | 01-JAN-00:40 | 8880.65 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.06 | 0.00 | 01-JAN-00:40 | 8880.65 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.06 | 0.00 | 01-JAN-00:40 | 8880.65 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.23 | 0.00 | 01-JAN-00:20 | 8292.92 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 25.23 | 0.00 | 01-JAN-00:20 | 8292.92 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 125.00 | 0.00 | 01-JAN-00:40 | 27655.49 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.11 | 0.00 | 01-JAN-00:40 | 27655.49 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 95.11 | 0.00 | 01-JAN-00:40 | 27655.49 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.89 | 0.00 | 01-JAN-00:20 | 13736.55 | 21-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.89 | 0.00 | 01-JAN-00:20 | 13736.55 | 21-JUL-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.80 | 0.00 | 01-JAN-00:40 | 9152.97 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.61 | 0.00 | 01-JAN-00:40 | 9152.97 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.61 | 0.00 | 01-JAN-00:40 | 9152.97 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.19 | 0.00 | 01-JAN-00:20 | 6933.61 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.19 | 0.00 | 01-JAN-00:20 | 6933.61 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.56 | 0.00 | 01-JAN-00:40 | 9035.92 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.44 | 0.00 | 01-JAN-00:40 | 9035.92 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 30.44 | 0.00 | 01-JAN-00:40 | 9035.92 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.11 | 0.00 | 01-JAN-00:10 | 6805.52 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.11 | 0.00 | 01-JAN-00:10 | 6805.52 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 49.02 | 0.00 | 01-JAN-00:40 | 10786.92 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.22 | 0.00 | 01-JAN-00:40 | 9165.89 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.22 | 0.00 | 01-JAN-00:40 | 9165.89 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.80 | 0.00 | 01-JAN-00:20 | 10786.92 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.80 | 0.00 | 01-JAN-00:20 | 10786.92 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 75.04 | 0.00 | 01-JAN-00:40 | 15324.20 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 24.08 | 0.00 | 01-JAN-00:40 | 13847.64 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 24.08 | 0.00 | 01-JAN-00:40 | 13847.64 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.97 | 0.00 | 01-JAN-00:20 | 15324.20 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.97 | 0.00 | 01-JAN-00:20 | 15324.20 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 44.40 | 0.00 | 01-JAN-00:40 | 9195.80 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.85 | 0.00 | 01-JAN-00:40 | 9195.80 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.85 | 0.00 | 01-JAN-00:40 | 9195.80 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.55 | 0.00 | 01-JAN-00:20 | 8444.05 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.55 | 0.00 | 01-JAN-00:20 | 8444.05 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
EnergyTransfer:HVAC | 1882.74 | 0.00 | 01-JAN-00:40 | 430050.23 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 975.47 | 0.00 | 01-JAN-00:40 | 430050.23 | 27-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 691.25 | 0.00 | 01-JAN-00:10 | 139404.33 | 08-DEC-17:00 |
HeatRecoveryForCooling:EnergyTransfer | 0.29 | 0.00 | 01-JAN-00:10 | 17195.15 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 215.73 | 0.00 | 01-JAN-00:10 | 205539.79 | 30-JUN-12:10 |
EnergyTransfer:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7552.20 | 03-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.218 | -204.485 | 0.000 | 0.000 | 34.318 | 81.703 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -160.097 |
CORE_MID | 0.000 | 0.000 | 8.772 | -123.520 | 0.000 | 0.000 | 35.674 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -129.230 |
CORE_TOP | 0.000 | 0.000 | 32.555 | -102.661 | 0.000 | 0.000 | 36.290 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -174.488 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 51.775 | -21.237 | 0.000 | 0.000 | 7.797 | 12.904 | 26.688 | 15.709 | 0.000 | 0.005 | 0.001 | 0.000 | -48.012 | 0.000 | -8.343 | -37.287 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 31.878 | -27.824 | 0.000 | 0.000 | 4.907 | 8.108 | 16.895 | 35.096 | 0.000 | 0.004 | 0.000 | 0.000 | -30.537 | 0.000 | -5.591 | -32.934 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 42.610 | -47.699 | 0.000 | 0.000 | 7.743 | 12.665 | 26.688 | 68.918 | 0.000 | 0.005 | 0.001 | 0.000 | -43.786 | 0.000 | -8.516 | -58.628 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 33.703 | -22.975 | 0.000 | 0.000 | 5.001 | 8.090 | 16.895 | 24.621 | 0.000 | 0.003 | 0.000 | 0.000 | -31.347 | 0.000 | -5.617 | -28.374 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 35.724 | -18.264 | 0.000 | 0.000 | 7.759 | 12.878 | 26.688 | 15.837 | 0.000 | 0.003 | 0.000 | 0.000 | -48.820 | 0.000 | -4.556 | -27.249 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 22.062 | -25.234 | 0.000 | 0.000 | 4.872 | 8.097 | 16.895 | 35.119 | 0.000 | 0.002 | 0.000 | 0.000 | -31.252 | 0.000 | -3.094 | -27.466 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 95.106 | -29.895 | 0.000 | 0.000 | 8.135 | 12.644 | 26.688 | 69.548 | 0.000 | 0.129 | 0.000 | 0.000 | -43.890 | 0.000 | -108.595 | -29.870 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 23.609 | -20.191 | 0.000 | 0.000 | 4.961 | 8.078 | 16.895 | 24.699 | 0.000 | 0.002 | 0.000 | 0.000 | -31.993 | 0.000 | -3.083 | -22.976 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 30.444 | -23.112 | 0.000 | 0.000 | 7.714 | 12.904 | 26.688 | 15.399 | 0.000 | 0.004 | 0.001 | 0.000 | -49.486 | 0.000 | -7.199 | -13.356 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 19.221 | -29.802 | 0.000 | 0.000 | 3.611 | 8.108 | 16.895 | 34.895 | 0.000 | 0.003 | 0.000 | 0.000 | -31.409 | 0.000 | -4.810 | -16.712 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 24.077 | -50.965 | 0.000 | 0.000 | 7.667 | 12.665 | 26.688 | 68.585 | 0.000 | 0.004 | 0.001 | 0.000 | -45.189 | 0.000 | -7.350 | -36.183 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 19.848 | -24.553 | 0.000 | 0.000 | 4.954 | 8.090 | 16.895 | 24.444 | 0.000 | 0.003 | 0.000 | 0.000 | -32.288 | 0.000 | -4.838 | -12.554 |
TOPFLOOR_PLENUM | 79.651 | -17.618 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -12.677 | -49.359 |
MIDFLOOR_PLENUM | 29.775 | -14.169 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.004 | 0.002 | 0.000 | 0.000 | 0.000 | -12.185 | -3.424 |
FIRSTFLOOR_PLENUM | 20.590 | -20.028 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 9.141 | 0.000 | 0.000 | 0.000 | -9.705 | -0.001 |
Total Facility | 130.016 | -51.815 | 472.603 | -772.417 | 0.000 | 0.000 | 181.401 | 370.341 | 762.041 | 432.870 | 0.000 | 0.175 | 9.148 | 0.000 | -468.009 | 0.000 | -206.159 | -860.188 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -47046.39 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 41115.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -35584.01 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 31616.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-JUL-05:03 | 0.00 | 0.00 | 0.00 | -32538.97 | 0.00 | 0.00 | 319.95 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 28251.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 20-JUN-05:02 | 0.00 | 0.00 | 0.00 | -10546.34 | 0.00 | 0.00 | 68.70 | 103.02 | 669.29 | 5853.84 | 0.00 | 0.00 | 3904.11 | 0.00 | -0.00 | 0.00 | -52.62 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:41 | 0.00 | 0.00 | 0.00 | -16119.85 | 0.00 | 0.00 | 13.90 | 32.61 | 317.77 | 10657.19 | 0.00 | 0.00 | 5345.52 | 0.00 | -0.00 | 0.00 | -247.13 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-13:42 | 0.00 | 0.00 | 0.00 | -24837.11 | 0.00 | 0.00 | 18.72 | 51.50 | 501.96 | 16947.70 | 0.00 | 0.00 | 7367.35 | 0.00 | -0.00 | 0.00 | -50.14 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-19:02 | 0.00 | 0.00 | 0.00 | -14297.44 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 8768.40 | 0.00 | 0.00 | 5550.05 | 0.00 | -0.00 | 0.00 | -371.38 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-04:02 | 0.00 | 0.00 | 0.00 | -8679.94 | 0.00 | 0.00 | 0.00 | 103.02 | 669.29 | 9354.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -179.33 | -1267.49 |
PERIMETER_BOT_ZN_2 | 14-MAY-09:41 | 0.00 | 0.00 | 0.00 | -12388.11 | 0.00 | 0.00 | 16.57 | 32.61 | 317.77 | 10767.95 | 0.00 | 0.00 | 1373.27 | 0.00 | -0.00 | 0.00 | -120.05 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-14:02 | 0.00 | 0.00 | 0.00 | -19297.88 | 0.00 | 0.00 | 23.30 | 51.50 | 501.96 | 16030.99 | 0.00 | 0.00 | 2709.39 | 0.00 | -0.00 | 0.00 | -19.28 | 0.00 |
PERIMETER_BOT_ZN_4 | 14-MAY-18:52 | 0.00 | 0.00 | 0.00 | -7325.60 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 9326.07 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -184.36 | -2166.48 |
PERIMETER_MID_ZN_3 | 07-JUN-04:02 | 0.00 | 0.00 | 0.00 | -10090.25 | 0.00 | 0.00 | 0.00 | 103.02 | 669.29 | 9248.60 | 0.00 | 0.00 | 361.43 | 0.00 | -0.00 | 0.00 | -292.08 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-10:02 | 0.00 | 0.00 | 0.00 | -14852.69 | 0.00 | 0.00 | 13.08 | 32.61 | 317.77 | 10523.13 | 0.00 | 0.00 | 4016.01 | 0.00 | -0.00 | 0.00 | -49.90 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:22 | 0.00 | 0.00 | 0.00 | -23322.27 | 0.00 | 0.00 | 19.71 | 51.50 | 501.96 | 17805.57 | 0.00 | 0.00 | 4983.70 | 0.00 | -0.00 | 0.00 | -40.17 | 0.00 |
PERIMETER_MID_ZN_4 | 10-JUN-17:42 | 0.00 | 0.00 | 0.00 | -12543.01 | 0.00 | 0.00 | 14.33 | 32.60 | 317.76 | 11107.21 | 0.00 | 0.00 | 1116.10 | 0.00 | -0.00 | 0.00 | -45.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -8646.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 8635.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUL-16:00 | 0.00 | -4907.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 4906.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 11-JAN-17:09 | 0.00 | -5832.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5832.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-06:02 | 0.00 | -7332.76 | 0.00 | -170990.04 | 0.00 | 0.00 | 3656.75 | 10162.05 | 21853.28 | 30322.50 | 0.00 | 0.00 | 123532.28 | 0.00 | 0.00 | 0.00 | -11204.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 28342.52 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34273.65 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 28554.83 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32522.38 |
CORE_TOP | 01-JAN-19:22 | 0.00 | 0.00 | 32979.89 | 0.00 | 0.00 | 0.00 | 0.00 | 396.30 | 2381.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35757.34 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 11452.50 | 0.00 | 0.00 | 0.00 | 121.15 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3470.15 | 0.00 | -363.28 | -8576.61 |
PERIMETER_TOP_ZN_2 | 26-FEB-04:12 | 0.00 | 0.00 | 13592.99 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2267.41 | 0.00 | -1280.89 | -10415.35 |
PERIMETER_TOP_ZN_1 | 26-FEB-04:12 | 0.00 | 0.00 | 21574.94 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3412.67 | 0.00 | -1930.15 | -16817.63 |
PERIMETER_TOP_ZN_4 | 26-FEB-04:12 | 0.00 | 0.00 | 14273.23 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2325.17 | 0.00 | -1282.38 | -11036.32 |
PERIMETER_BOT_ZN_3 | 01-JAN-19:22 | 0.00 | 0.00 | 8952.95 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2464.78 | 0.00 | -741.94 | -6331.75 |
PERIMETER_BOT_ZN_2 | 01-JAN-19:22 | 0.00 | 0.00 | 10967.41 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1640.79 | 0.00 | -503.95 | -9193.33 |
PERIMETER_BOT_ZN_1 | 12-JAN-07:10 | 0.00 | 0.00 | 28420.37 | 0.00 | 0.00 | 0.00 | 222.58 | 501.29 | 669.28 | 0.00 | 0.00 | 0.00 | 31363.61 | 0.00 | -4430.39 | 0.00 | -56746.74 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-19:22 | 0.00 | 0.00 | 11650.63 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1645.70 | 0.00 | -505.64 | -9869.95 |
PERIMETER_MID_ZN_3 | 01-JAN-19:22 | 0.00 | 0.00 | 9875.40 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2502.50 | 0.00 | -1163.87 | -6794.54 |
PERIMETER_MID_ZN_2 | 01-JAN-19:22 | 0.00 | 0.00 | 12320.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1666.20 | 0.00 | -792.71 | -10232.64 |
PERIMETER_MID_ZN_1 | 01-JAN-19:22 | 0.00 | 0.00 | 18576.31 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2447.03 | 0.00 | -1191.86 | -15522.92 |
PERIMETER_MID_ZN_4 | 01-JAN-19:22 | 0.00 | 0.00 | 12262.32 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1671.65 | 0.00 | -793.03 | -10168.30 |
TOPFLOOR_PLENUM | 12-JAN-06:13 | 20423.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20423.56 |
MIDFLOOR_PLENUM | 02-JAN-07:03 | 12943.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -277.93 | -12665.73 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 11254.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -214.56 | -11039.68 |
Total Facility | 30-JAN-06:01 | 29213.00 | 0.00 | 233898.49 | 0.00 | 0.00 | 0.00 | 2622.36 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35444.35 | 0.00 | -12982.25 | -239368.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.2362 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4241 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.9746 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9008 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.1590 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.1181 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.8709 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.9873 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.8859 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0795 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.9690 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0361 | 3.0361 | 0.9108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2805 | 2.2805 | 0.7776 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2460 | 2.2460 | 0.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7181 | 0.7181 | 0.2154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8752 | 0.8752 | 0.2626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3989 | 1.3989 | 0.4197 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9207 | 0.9207 | 0.2762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5755 | 0.5755 | 0.1727 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7198 | 0.7198 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1372 | 1.1372 | 0.3412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7676 | 0.7676 | 0.2303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6358 | 0.6358 | 0.1907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8689 | 0.8689 | 0.2607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3204 | 1.3204 | 0.3961 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8690 | 0.8690 | 0.2607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.2362 | 5.4241 | 6.2362 | 1.8709 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.9746 | 4.9008 | 5.9746 | 1.8859 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.1590 | 5.3530 | 6.1590 | 1.9690 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5180 | 1.5180 | 0.9108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1402 | 1.1402 | 0.7776 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1230 | 1.1230 | 0.7951 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3591 | 0.3591 | 0.2154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4376 | 0.4376 | 0.2626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6995 | 0.6995 | 0.4197 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4603 | 0.4603 | 0.2762 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2878 | 0.2878 | 0.1727 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3599 | 0.3599 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5686 | 0.5686 | 0.3412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3838 | 0.3838 | 0.2303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3179 | 0.3179 | 0.1907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4344 | 0.4344 | 0.2607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6602 | 0.6602 | 0.3961 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4345 | 0.4345 | 0.2607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.1181 | 1.8709 | 1.8709 | 1.8709 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.9873 | 1.8859 | 1.8859 | 1.8859 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0795 | 1.9690 | 1.9690 | 1.9690 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1044.17 |
Number of hours cooling loads not met | 29.00 |
Number of hours not met | 1073.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 696.52 | 234755.32 | 348.68 | 273471.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 52.49 | 49715.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 370.34 | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.67 | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.94 | 1360.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 111.63 | 28869.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 26.22 | 2703.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 126.32 | 13401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 2149.88 |
Natural Gas | 0.00 | 475.00 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2624.88 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 74.33 |
Space Heating | 139.80 |
Space Cooling | 10.54 |
Fans (All) | 22.41 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 431.51 |
Subtotal | 431.51 |
Natural Gas [MJ/m2] | |
Space Heating | 69.98 |
Service Water Heating | 25.35 |
Miscellaneous (All) | 95.34 |
Subtotal | 95.34 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.11 |
Space Heating | 39.82 |
Space Cooling | 2.00 |
Fans (All) | 4.25 |
Service Water Heating | 4.81 |
Receptacle Equipment | 29.03 |
Miscellaneous | 5.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2616. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8753.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8737.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 22.83 | 0.00 | 0.00 | 0.00 |
Average | 8754.39 | 5.61 | 0.00 | 0.00 | 0.00 |
Sum | 157579.00 | 101.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 34143.31 | 0.02 | 0.00 | 0.00 | 0.00 |
Sum | 614579.67 | 0.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8755.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8700.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 60.00 | 0.00 | 0.00 | 0.00 |
Average | 8752.91 | 7.09 | 0.00 | 0.00 | 0.00 |
Sum | 157552.33 | 127.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128274.33 | 29.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 29.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.46 | 1.87 | 0.00 | 0.00 | 0.00 |
Sum | 614546.33 | 33.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.958237E+10 | 8530.68 | 27-JAN-17:00 | -12.2 | -12.5 | 0.160780E+10 | 2414.14 | 27-JAN-14:09 | -12.2 | -12.5 |
February | 0.101584E+11 | 9091.87 | 10-FEB-17:00 | -0.6 | -2.2 | 0.153737E+10 | 2558.34 | 17-FEB-14:09 | -13.4 | -14.5 |
March | 0.123760E+11 | 12456.27 | 23-MAR-07:50 | -3.3 | -5.1 | 0.198501E+10 | 2608.41 | 22-MAR-13:30 | -3.3 | -5.1 |
April | 0.154874E+11 | 39945.54 | 28-APR-05:02 | -1.5 | -2.2 | 0.187810E+10 | 2609.28 | 26-APR-09:20 | -1.5 | -2.2 |
May | 0.239468E+11 | 43275.10 | 25-MAY-05:02 | 4.87 | 1.59 | 0.207357E+10 | 2606.66 | 19-MAY-13:39 | 4.87 | 1.59 |
June | 0.275996E+11 | 46178.82 | 21-JUN-04:02 | 13.80 | 11.59 | 0.207096E+10 | 2606.69 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.269699E+11 | 46884.36 | 17-JUL-04:02 | 8.30 | 8.30 | 0.192531E+10 | 2607.05 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.272945E+11 | 47053.94 | 14-AUG-04:02 | 11.60 | 10.40 | 0.215992E+10 | 2606.65 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.185182E+11 | 44103.57 | 05-SEP-05:02 | 5.00 | 4.09 | 0.190832E+10 | 2608.77 | 28-SEP-13:30 | 5.00 | 1.37 |
October | 0.126466E+11 | 19727.27 | 06-OCT-07:06 | 6.28 | 2.55 | 0.190840E+10 | 2608.13 | 19-OCT-13:39 | -2.6 | -3.1 |
November | 0.996325E+10 | 8954.53 | 03-NOV-16:00 | -11.1 | -11.5 | 0.167614E+10 | 2516.74 | 03-NOV-13:09 | -11.1 | -11.5 |
December | 0.994167E+10 | 8150.61 | 22-DEC-17:00 | -21.7 | -22.0 | 0.154544E+10 | 2343.81 | 22-DEC-14:09 | -21.7 | -22.0 |
Annual Sum or Average | 0.204485E+12 | 0.222764E+11 | ||||||||
Minimum of Months | 0.958237E+10 | 8150.61 | -21.7 | -22.0 | 0.153737E+10 | 2343.81 | -21.7 | -22.0 | ||
Maximum of Months | 0.275996E+11 | 47053.94 | 13.80 | 11.59 | 0.215992E+10 | 2609.28 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 19350187.44 | 1313.46 | 22-MAR-17:03 | 5.13 | 1.52 | 0.00 | 0.00 | 01-MAR-00:10 | 5.13 | 1.52 |
April | 0.890426E+09 | 4162.36 | 21-APR-15:40 | 14.23 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 14.23 | 5.51 |
May | 0.289969E+10 | 7329.89 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.500139E+10 | 8497.22 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.495969E+10 | 8645.31 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.325164E+10 | 7343.03 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.579165E+09 | 2913.74 | 07-SEP-15:40 | 16.83 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.83 | 8.91 |
October | 17158363.75 | 1327.74 | 03-OCT-16:30 | 11.40 | 5.76 | 0.00 | 0.00 | 01-OCT-00:10 | 11.40 | 5.76 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.176185E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.500139E+10 | 8645.31 | 26.95 | 16.10 | 0.00 | 0.00 | 26.95 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34689196.38 | 3149.12 | 11-JAN-05:01 | -27.4 | -27.5 | 0.00 | 0.00 | 01-JAN-00:10 | -27.4 | -27.5 |
February | 35801594.68 | 2956.80 | 18-FEB-05:01 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 30533855.47 | 3287.90 | 04-MAR-05:01 | -26.1 | -26.5 | 0.00 | 0.00 | 01-MAR-00:10 | -26.1 | -26.5 |
April | 0.470838E+09 | 3005.38 | 14-APR-06:01 | -5.8 | -7.0 | 0.00 | 0.00 | 01-APR-00:10 | -5.8 | -7.0 |
May | 0.209062E+10 | 3545.92 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.394102E+10 | 4608.19 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.387232E+10 | 4907.00 | 12-JUL-16:00 | 25.00 | 13.76 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 13.76 |
August | 0.286598E+10 | 4168.59 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.677703E+09 | 2135.15 | 02-SEP-05:25 | 6.70 | 5.91 | 0.00 | 0.00 | 01-SEP-00:10 | 6.70 | 5.91 |
October | 82486926.10 | 2278.17 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 22680756.30 | 3103.17 | 30-NOV-05:01 | -27.8 | -28.0 | 0.00 | 0.00 | 01-NOV-00:10 | -27.8 | -28.0 |
December | 44461632.50 | 3332.32 | 09-DEC-05:01 | -24.2 | -24.5 | 0.00 | 0.00 | 01-DEC-00:10 | -24.2 | -24.5 |
Annual Sum or Average | 0.141691E+11 | 0.00 | ||||||||
Minimum of Months | 22680756.30 | 2135.15 | -27.8 | -28.0 | 0.00 | 0.00 | -27.8 | -28.0 | ||
Maximum of Months | 0.394102E+10 | 4907.00 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319838E+09 | 5832.27 | 11-JAN-17:09 | -34.5 | -34.6 | 0.00 | 0.00 | 01-JAN-00:10 | -34.5 | -34.6 |
February | 0.255335E+09 | 4479.86 | 17-FEB-07:08 | -23.3 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.3 | -23.5 |
March | 0.368952E+09 | 5727.95 | 31-MAR-06:09 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.102463E+10 | 3774.23 | 13-APR-06:08 | -7.4 | -8.5 | 0.00 | 0.00 | 01-APR-00:10 | -7.4 | -8.5 |
May | 0.297787E+10 | 3706.79 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.445438E+10 | 4904.10 | 22-JUN-06:08 | 15.28 | 11.70 | 0.00 | 0.00 | 01-JUN-00:10 | 15.28 | 11.70 |
July | 0.446355E+10 | 5539.90 | 24-JUL-06:07 | 14.18 | 13.06 | 0.00 | 0.00 | 01-JUL-00:10 | 14.18 | 13.06 |
August | 0.374354E+10 | 4815.31 | 11-AUG-15:50 | 25.40 | 14.66 | 0.00 | 0.00 | 01-AUG-00:10 | 25.40 | 14.66 |
September | 0.135704E+10 | 3336.61 | 15-SEP-06:08 | -0.5 | -0.7 | 0.00 | 0.00 | 01-SEP-00:10 | -0.5 | -0.7 |
October | 0.323787E+09 | 3642.69 | 27-OCT-16:10 | -11.4 | -12.2 | 0.00 | 0.00 | 01-OCT-00:10 | -11.4 | -12.2 |
November | 0.335236E+09 | 4590.96 | 09-NOV-07:08 | -26.7 | -26.9 | 0.00 | 0.00 | 01-NOV-00:10 | -26.7 | -26.9 |
December | 0.404122E+09 | 4924.35 | 15-DEC-07:09 | -33.4 | -33.5 | 0.00 | 0.00 | 01-DEC-00:10 | -33.4 | -33.5 |
Annual Sum or Average | 0.200283E+11 | 0.00 | ||||||||
Minimum of Months | 0.255335E+09 | 3336.61 | -34.5 | -34.6 | 0.00 | 0.00 | -34.5 | -34.6 | ||
Maximum of Months | 0.446355E+10 | 5832.27 | 25.40 | 14.66 | 0.00 | 0.00 | 25.40 | 14.66 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366825E+10 | 5903.88 | 20-JAN-17:00 | -11.1 | -11.2 | 0.147370E+10 | 2098.59 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.469472E+10 | 6612.10 | 09-FEB-16:00 | 0.60 | -0.5 | 0.137938E+10 | 2291.50 | 09-FEB-14:00 | 0.60 | -0.5 |
March | 0.728556E+10 | 7267.35 | 22-MAR-15:20 | 5.60 | 2.35 | 0.173741E+10 | 2405.29 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.975758E+10 | 13337.34 | 21-APR-16:00 | 14.40 | 5.45 | 0.175132E+10 | 2608.25 | 24-APR-13:50 | 4.40 | -1.0 |
May | 0.159780E+11 | 32925.75 | 11-MAY-05:02 | 4.68 | 1.21 | 0.205912E+10 | 2606.65 | 19-MAY-13:50 | 13.58 | 8.15 |
June | 0.195945E+11 | 34134.36 | 23-JUN-04:02 | 14.08 | 9.52 | 0.206636E+10 | 2606.65 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.189363E+11 | 35580.13 | 24-JUL-04:02 | 12.80 | 12.43 | 0.192079E+10 | 2606.93 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.178276E+11 | 33734.84 | 11-AUG-05:02 | 11.02 | 6.91 | 0.215131E+10 | 2606.64 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.107031E+11 | 13453.43 | 01-SEP-16:00 | 15.60 | 10.82 | 0.183227E+10 | 2608.17 | 06-SEP-13:00 | 8.30 | 6.43 |
October | 0.730923E+10 | 7721.82 | 05-OCT-16:00 | 11.10 | 5.87 | 0.165265E+10 | 2551.72 | 04-OCT-13:00 | 11.10 | 5.87 |
November | 0.428918E+10 | 6196.11 | 02-NOV-16:00 | -8.9 | -9.4 | 0.148112E+10 | 2146.72 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.347604E+10 | 5661.36 | 21-DEC-17:00 | -16.7 | -17.3 | 0.141459E+10 | 2042.28 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.123520E+12 | 0.209200E+11 | ||||||||
Minimum of Months | 0.347604E+10 | 5661.36 | -16.7 | -17.3 | 0.137938E+10 | 2042.28 | -16.7 | -17.3 | ||
Maximum of Months | 0.195945E+11 | 35580.13 | 15.60 | 12.43 | 0.215131E+10 | 2608.25 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155704E+10 | 5304.34 | 20-JAN-17:00 | -11.1 | -11.2 | 0.144985E+10 | 1945.83 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.259590E+10 | 6314.97 | 09-FEB-15:50 | 0.50 | -0.6 | 0.133124E+10 | 2180.78 | 09-FEB-14:00 | 0.50 | -0.6 |
March | 0.519082E+10 | 7279.07 | 22-MAR-16:00 | 5.60 | 2.61 | 0.164426E+10 | 2331.24 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.832758E+10 | 13035.58 | 21-APR-16:00 | 14.40 | 5.45 | 0.165203E+10 | 2606.55 | 20-APR-13:09 | 14.40 | 5.45 |
May | 0.146017E+11 | 17663.59 | 31-MAY-16:00 | 22.20 | 10.79 | 0.203093E+10 | 2606.64 | 19-MAY-13:50 | 22.20 | 10.79 |
June | 0.189016E+11 | 31712.18 | 23-JUN-05:03 | 14.82 | 10.54 | 0.206025E+10 | 2606.62 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.180707E+11 | 32540.11 | 25-JUL-05:03 | 14.40 | 13.72 | 0.191524E+10 | 2606.88 | 19-JUL-09:09 | 14.40 | 13.72 |
August | 0.160862E+11 | 32491.10 | 03-AUG-05:02 | 14.90 | 13.04 | 0.213127E+10 | 2606.63 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.896445E+10 | 12201.08 | 01-SEP-16:00 | 15.60 | 10.82 | 0.171435E+10 | 2606.64 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.505165E+10 | 7380.23 | 03-OCT-15:50 | 11.88 | 6.46 | 0.153837E+10 | 2410.88 | 04-OCT-13:00 | 11.10 | 4.80 |
November | 0.192437E+10 | 5450.08 | 02-NOV-16:00 | -8.9 | -9.4 | 0.143822E+10 | 1974.90 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.138916E+10 | 4993.23 | 23-DEC-17:02 | -2.6 | -3.4 | 0.139825E+10 | 1928.96 | 04-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.102661E+12 | 0.203042E+11 | ||||||||
Minimum of Months | 0.138916E+10 | 4993.23 | -11.1 | -11.2 | 0.133124E+10 | 1928.96 | -13.9 | -14.6 | ||
Maximum of Months | 0.189016E+11 | 32540.11 | 22.20 | 13.72 | 0.213127E+10 | 2606.88 | 22.20 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7854028.54 | 1294.82 | 21-JAN-17:02 | -5.5 | -5.8 | 0.302302E+09 | 406.72 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 9691731.72 | 1301.48 | 11-FEB-17:02 | -1.2 | -2.7 | 0.274906E+09 | 406.71 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.106825E+09 | 1617.19 | 22-MAR-16:00 | 5.60 | 2.61 | 0.331412E+09 | 431.98 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.128913E+10 | 2207.46 | 28-APR-15:20 | 12.20 | 4.90 | 0.316002E+09 | 539.44 | 28-APR-13:00 | 12.20 | 4.90 |
May | 0.344396E+10 | 6118.04 | 31-MAY-06:03 | 14.08 | 8.75 | 0.415173E+09 | 549.50 | 19-MAY-13:50 | 14.08 | 8.75 |
June | 0.557222E+10 | 10545.76 | 20-JUN-05:02 | 11.78 | 9.39 | 0.434025E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.521928E+10 | 9998.25 | 11-JUL-06:03 | 16.38 | 12.49 | 0.402685E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.381128E+10 | 5133.89 | 02-AUG-15:40 | 22.93 | 14.75 | 0.435546E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.153859E+10 | 2249.12 | 01-SEP-16:00 | 15.60 | 10.82 | 0.322282E+09 | 543.30 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.219997E+09 | 1624.91 | 04-OCT-15:40 | 10.37 | 4.66 | 0.306828E+09 | 439.40 | 04-OCT-13:00 | 10.37 | 4.66 |
November | 7724755.07 | 1290.93 | 04-NOV-16:02 | -9.6 | -11.3 | 0.300224E+09 | 406.71 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 10712645.41 | 1295.17 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291804E+09 | 406.76 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.212372E+11 | 0.413319E+10 | ||||||||
Minimum of Months | 7724755.07 | 1290.93 | -9.6 | -11.3 | 0.274906E+09 | 406.71 | -28.5 | -28.7 | ||
Maximum of Months | 0.557222E+10 | 10545.76 | 22.93 | 14.75 | 0.435546E+09 | 549.55 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12916599.46 | 1550.08 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192709E+09 | 257.48 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 31326620.55 | 1556.39 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175082E+09 | 257.47 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.622467E+09 | 2462.47 | 22-MAR-10:30 | 2.25 | 0.43 | 0.213973E+09 | 323.48 | 22-MAR-09:00 | 2.25 | 0.43 |
April | 0.210710E+10 | 5666.85 | 22-APR-09:30 | 9.15 | 3.96 | 0.214472E+09 | 347.87 | 26-APR-09:39 | 4.03 | -0.4 |
May | 0.531173E+10 | 16120.43 | 14-MAY-09:41 | 15.92 | 8.37 | 0.268557E+09 | 348.29 | 12-MAY-09:00 | 15.92 | 8.37 |
June | 0.623477E+10 | 11174.12 | 13-JUN-06:03 | 13.27 | 9.79 | 0.272724E+09 | 348.82 | 12-JUN-09:09 | 13.27 | 9.79 |
July | 0.616687E+10 | 14985.07 | 23-JUL-09:42 | 20.63 | 14.69 | 0.252700E+09 | 348.60 | 07-JUL-09:50 | 20.63 | 14.69 |
August | 0.488167E+10 | 9866.06 | 10-AUG-08:50 | 14.22 | 9.95 | 0.277325E+09 | 348.32 | 10-AUG-09:00 | 17.80 | 11.30 |
September | 0.200894E+10 | 5231.87 | 10-SEP-10:04 | 13.07 | 7.24 | 0.206970E+09 | 348.15 | 07-SEP-09:50 | 13.07 | 7.24 |
October | 0.416692E+09 | 2377.52 | 03-OCT-10:20 | 4.63 | 3.18 | 0.195193E+09 | 319.18 | 03-OCT-09:00 | 4.63 | 3.18 |
November | 12984975.04 | 1545.58 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190930E+09 | 257.48 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 16761626.68 | 1549.95 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185779E+09 | 257.50 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.278242E+11 | 0.264641E+10 | ||||||||
Minimum of Months | 12916599.46 | 1545.58 | -9.6 | -11.3 | 0.175082E+09 | 257.47 | -28.6 | -28.8 | ||
Maximum of Months | 0.623477E+10 | 16120.43 | 20.63 | 14.69 | 0.277325E+09 | 348.82 | 20.63 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56524596.23 | 2488.30 | 21-JAN-17:02 | -5.5 | -5.8 | 0.304465E+09 | 406.69 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 0.591642E+09 | 4221.40 | 15-FEB-13:50 | -8.5 | -9.4 | 0.281761E+09 | 546.85 | 15-FEB-14:09 | -8.1 | -9.1 |
March | 0.210684E+10 | 8316.65 | 31-MAR-14:00 | -11.1 | -13.1 | 0.361805E+09 | 550.25 | 28-MAR-13:39 | -11.1 | -13.1 |
April | 0.502131E+10 | 13941.78 | 20-APR-14:00 | 14.40 | 6.23 | 0.349281E+09 | 550.53 | 12-APR-13:30 | 14.40 | 6.23 |
May | 0.775979E+10 | 24822.02 | 14-MAY-12:22 | 18.35 | 9.42 | 0.405670E+09 | 549.51 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.906737E+10 | 13798.23 | 29-JUN-14:00 | 25.60 | 16.24 | 0.420266E+09 | 549.50 | 28-JUN-13:00 | 25.60 | 16.24 |
July | 0.900777E+10 | 24838.16 | 23-JUL-13:42 | 25.00 | 15.26 | 0.389658E+09 | 549.99 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.845647E+10 | 22011.86 | 27-AUG-13:22 | 18.60 | 13.91 | 0.425168E+09 | 549.67 | 11-AUG-13:39 | 18.60 | 13.91 |
September | 0.410387E+10 | 10899.91 | 07-SEP-14:30 | 15.85 | 8.58 | 0.334869E+09 | 549.52 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.134161E+10 | 9550.45 | 03-OCT-13:30 | 10.85 | 6.24 | 0.318848E+09 | 549.60 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 0.157809E+09 | 3528.83 | 08-NOV-13:50 | -13.4 | -14.2 | 0.302434E+09 | 480.83 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 27953111.25 | 2481.94 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293487E+09 | 406.72 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.476990E+11 | 0.418771E+10 | ||||||||
Minimum of Months | 27953111.25 | 2481.94 | -13.4 | -14.2 | 0.281761E+09 | 406.69 | -13.4 | -14.2 | ||
Maximum of Months | 0.906737E+10 | 24838.16 | 25.60 | 16.24 | 0.425168E+09 | 550.53 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13625882.06 | 1626.31 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192694E+09 | 257.46 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 28599558.65 | 1632.10 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175050E+09 | 257.46 | 27-FEB-10:09 | -33.8 | -33.9 |
March | 0.319054E+09 | 2242.42 | 22-MAR-16:00 | 5.60 | 2.61 | 0.210815E+09 | 286.49 | 22-MAR-15:50 | 5.60 | 2.61 |
April | 0.211727E+10 | 7057.49 | 21-APR-17:50 | 14.40 | 5.94 | 0.200270E+09 | 338.68 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.399176E+10 | 14296.55 | 14-MAY-19:02 | 16.52 | 8.80 | 0.242137E+09 | 347.83 | 31-MAY-13:20 | 19.60 | 10.29 |
June | 0.534210E+10 | 13198.46 | 10-JUN-17:05 | 21.20 | 10.81 | 0.262811E+09 | 347.85 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.495077E+10 | 8801.55 | 11-JUL-17:40 | 26.10 | 15.25 | 0.242413E+09 | 347.85 | 21-JUL-13:50 | 25.82 | 14.23 |
August | 0.420319E+10 | 8877.68 | 27-AUG-17:23 | 20.85 | 12.52 | 0.257085E+09 | 347.84 | 02-AUG-13:00 | 20.85 | 12.52 |
September | 0.171982E+10 | 4480.75 | 02-SEP-17:20 | 16.70 | 10.26 | 0.197211E+09 | 338.68 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.256916E+09 | 2227.85 | 03-OCT-15:10 | 12.62 | 6.83 | 0.193905E+09 | 287.27 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 14546329.03 | 1625.00 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190920E+09 | 257.46 | 27-NOV-10:09 | -27.2 | -27.4 |
December | 17806806.43 | 1626.68 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185765E+09 | 257.48 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.229754E+11 | 0.255107E+10 | ||||||||
Minimum of Months | 13625882.06 | 1625.00 | -9.6 | -11.3 | 0.175050E+09 | 257.46 | -33.8 | -33.9 | ||
Maximum of Months | 0.534210E+10 | 14296.55 | 26.10 | 15.25 | 0.262811E+09 | 347.85 | 25.82 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10393001.19 | 1046.64 | 21-JAN-17:02 | -5.5 | -5.8 | 0.299968E+09 | 406.72 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 8661091.13 | 1047.87 | 11-FEB-17:02 | -1.2 | -2.7 | 0.272765E+09 | 406.69 | 23-FEB-14:30 | -18.0 | -18.6 |
March | 53328570.22 | 1160.75 | 22-MAR-15:20 | 5.60 | 2.35 | 0.331380E+09 | 409.66 | 22-MAR-13:00 | 5.60 | 2.35 |
April | 0.956257E+09 | 1579.43 | 28-APR-15:40 | 12.20 | 5.02 | 0.310755E+09 | 505.84 | 28-APR-13:00 | 12.20 | 5.02 |
May | 0.255326E+10 | 3077.73 | 31-MAY-14:30 | 20.55 | 10.45 | 0.414495E+09 | 549.49 | 19-MAY-13:00 | 20.55 | 10.45 |
June | 0.433952E+10 | 8506.73 | 07-JUN-04:02 | 5.87 | 4.55 | 0.434480E+09 | 549.50 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.447523E+10 | 8680.32 | 11-JUL-04:02 | 12.25 | 10.71 | 0.404238E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.356190E+10 | 4672.52 | 02-AUG-06:02 | 11.28 | 10.30 | 0.447333E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.177844E+10 | 2021.21 | 01-SEP-16:00 | 15.60 | 10.82 | 0.349925E+09 | 549.47 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.497150E+09 | 1425.96 | 06-OCT-15:00 | 10.60 | 4.90 | 0.312889E+09 | 473.36 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 9205096.70 | 1055.26 | 04-NOV-16:02 | -9.6 | -11.3 | 0.300995E+09 | 406.70 | 30-NOV-14:00 | -26.1 | -26.4 |
December | 20763455.58 | 1048.44 | 23-DEC-17:02 | -2.6 | -3.4 | 0.291928E+09 | 406.74 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.182641E+11 | 0.417115E+10 | ||||||||
Minimum of Months | 8661091.13 | 1046.64 | -9.6 | -11.3 | 0.272765E+09 | 406.69 | -26.1 | -26.4 | ||
Maximum of Months | 0.447523E+10 | 8680.32 | 20.55 | 10.82 | 0.447333E+09 | 549.55 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13880618.07 | 1287.90 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192904E+09 | 257.49 | 30-JAN-14:20 | -23.7 | -24.2 |
February | 23628146.95 | 1289.23 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175256E+09 | 257.49 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.461160E+09 | 1990.14 | 31-MAR-09:30 | -17.0 | -18.1 | 0.213667E+09 | 325.95 | 31-MAR-09:39 | -16.7 | -17.8 |
April | 0.175364E+10 | 3855.12 | 22-APR-08:30 | 6.65 | 2.48 | 0.214656E+09 | 348.11 | 24-APR-09:09 | 0.78 | -3.3 |
May | 0.441877E+10 | 12388.47 | 14-MAY-09:41 | 15.92 | 8.37 | 0.271455E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.527196E+10 | 9551.62 | 13-JUN-06:03 | 13.27 | 9.79 | 0.273454E+09 | 348.15 | 13-JUN-09:39 | 20.53 | 12.04 |
July | 0.552311E+10 | 11462.30 | 09-JUL-06:32 | 14.07 | 12.30 | 0.255192E+09 | 348.35 | 07-JUL-09:50 | 14.07 | 12.30 |
August | 0.466792E+10 | 9443.90 | 11-AUG-06:02 | 10.97 | 7.10 | 0.284676E+09 | 348.19 | 10-AUG-09:50 | 10.97 | 7.10 |
September | 0.234407E+10 | 4808.41 | 10-SEP-10:04 | 13.07 | 7.24 | 0.223296E+09 | 347.88 | 08-SEP-13:09 | 13.07 | 7.24 |
October | 0.723296E+09 | 2179.35 | 03-OCT-09:35 | 2.97 | 2.01 | 0.199600E+09 | 345.42 | 03-OCT-09:50 | 3.43 | 2.35 |
November | 11532224.68 | 1298.68 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191283E+09 | 257.48 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 20594958.98 | 1289.11 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186039E+09 | 257.49 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.252336E+11 | 0.268148E+10 | ||||||||
Minimum of Months | 11532224.68 | 1287.90 | -17.0 | -18.1 | 0.175256E+09 | 257.48 | -28.6 | -28.8 | ||
Maximum of Months | 0.552311E+10 | 12388.47 | 15.92 | 12.30 | 0.284676E+09 | 348.35 | 20.53 | 12.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19781749.52 | 2035.39 | 21-JAN-17:02 | -5.5 | -5.8 | 0.241328E+09 | 406.62 | 19-JAN-10:09 | -5.5 | -5.8 |
February | 0.116381E+09 | 2291.91 | 18-FEB-13:30 | -14.4 | -15.8 | 0.240428E+09 | 406.62 | 07-FEB-10:09 | -14.4 | -15.8 |
March | 0.275429E+09 | 2788.23 | 11-MAR-13:40 | -3.7 | -5.7 | 0.305269E+09 | 437.17 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.230034E+10 | 8017.81 | 22-APR-14:00 | 15.60 | 7.03 | 0.317966E+09 | 549.50 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.449930E+10 | 17219.39 | 14-MAY-13:02 | 18.98 | 9.42 | 0.383094E+09 | 549.50 | 30-MAY-13:00 | 17.80 | 9.24 |
June | 0.606781E+10 | 10407.85 | 30-JUN-12:00 | 25.60 | 18.33 | 0.409117E+09 | 549.53 | 29-JUN-13:30 | 25.60 | 18.33 |
July | 0.684178E+10 | 19298.65 | 23-JUL-14:02 | 25.10 | 15.30 | 0.385122E+09 | 549.53 | 21-JUL-13:30 | 25.10 | 15.30 |
August | 0.625711E+10 | 15182.73 | 27-AUG-13:42 | 19.13 | 14.11 | 0.418530E+09 | 549.59 | 25-AUG-13:00 | 19.13 | 14.11 |
September | 0.282943E+10 | 8782.93 | 09-SEP-14:10 | 14.08 | 8.86 | 0.324047E+09 | 549.52 | 08-SEP-13:09 | 14.08 | 8.86 |
October | 0.641206E+09 | 5079.06 | 03-OCT-13:50 | 11.42 | 6.47 | 0.296225E+09 | 549.49 | 03-OCT-13:09 | 11.42 | 6.47 |
November | 26960585.37 | 2056.16 | 04-NOV-16:02 | -9.6 | -11.3 | 0.252598E+09 | 406.61 | 22-NOV-14:30 | -11.1 | -11.7 |
December | 19135839.00 | 2021.19 | 23-DEC-17:02 | -2.6 | -3.4 | 0.222041E+09 | 406.61 | 29-DEC-10:30 | -11.4 | -11.9 |
Annual Sum or Average | 0.298947E+11 | 0.379577E+10 | ||||||||
Minimum of Months | 19135839.00 | 2021.19 | -14.4 | -15.8 | 0.222041E+09 | 406.61 | -14.4 | -15.8 | ||
Maximum of Months | 0.684178E+10 | 19298.65 | 25.60 | 18.33 | 0.418530E+09 | 549.59 | 25.60 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15060502.69 | 1369.39 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192887E+09 | 257.47 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 15577722.25 | 1368.85 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175185E+09 | 257.47 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.172558E+09 | 1716.55 | 31-MAR-17:00 | -9.4 | -11.7 | 0.210512E+09 | 260.97 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.175059E+10 | 5415.61 | 21-APR-18:20 | 14.03 | 5.87 | 0.200105E+09 | 338.68 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.318085E+10 | 7325.46 | 14-MAY-18:52 | 16.70 | 9.05 | 0.244779E+09 | 347.83 | 31-MAY-13:00 | 20.00 | 10.15 |
June | 0.431624E+10 | 6153.08 | 21-JUN-17:00 | 26.10 | 14.35 | 0.267263E+09 | 347.85 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.420732E+10 | 6933.61 | 31-JUL-18:30 | 25.00 | 14.57 | 0.248749E+09 | 347.85 | 07-JUL-13:09 | 25.00 | 14.57 |
August | 0.389553E+10 | 6471.56 | 10-AUG-18:20 | 22.43 | 12.03 | 0.271297E+09 | 347.85 | 01-AUG-09:00 | 22.43 | 12.03 |
September | 0.211347E+10 | 3269.85 | 08-SEP-16:00 | 14.40 | 9.03 | 0.208078E+09 | 338.68 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.487357E+09 | 1904.53 | 03-OCT-15:30 | 12.25 | 6.65 | 0.195648E+09 | 292.60 | 03-OCT-15:39 | 12.07 | 6.56 |
November | 14102137.96 | 1383.42 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191271E+09 | 257.46 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 22022369.24 | 1371.56 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186024E+09 | 257.47 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.201907E+11 | 0.259180E+10 | ||||||||
Minimum of Months | 14102137.96 | 1368.85 | -9.6 | -11.7 | 0.175185E+09 | 257.46 | -28.6 | -28.8 | ||
Maximum of Months | 0.431624E+10 | 7325.46 | 26.10 | 14.57 | 0.271297E+09 | 347.85 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10052754.89 | 1166.65 | 21-JAN-17:02 | -5.5 | -5.8 | 0.303960E+09 | 406.71 | 11-JAN-14:00 | -5.5 | -5.8 |
February | 25865525.97 | 1174.02 | 11-FEB-17:02 | -1.2 | -2.7 | 0.276267E+09 | 406.71 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.244230E+09 | 1516.62 | 22-MAR-15:20 | 5.60 | 2.35 | 0.333493E+09 | 452.75 | 22-MAR-13:00 | 5.60 | 2.35 |
April | 0.156138E+10 | 2567.85 | 28-APR-15:20 | 12.20 | 4.90 | 0.331529E+09 | 549.47 | 21-APR-13:00 | 12.20 | 4.90 |
May | 0.365015E+10 | 9448.12 | 31-MAY-05:02 | 12.07 | 7.63 | 0.429032E+09 | 549.50 | 19-MAY-13:50 | 12.07 | 7.63 |
June | 0.577012E+10 | 10090.57 | 07-JUN-04:02 | 5.87 | 4.55 | 0.435555E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.538370E+10 | 9804.93 | 11-JUL-04:02 | 12.25 | 10.71 | 0.404906E+09 | 549.56 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.405683E+10 | 6540.07 | 11-AUG-06:02 | 10.97 | 7.10 | 0.447321E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.189897E+10 | 2720.26 | 01-SEP-15:50 | 15.50 | 10.82 | 0.347704E+09 | 549.48 | 01-SEP-13:00 | 15.50 | 10.82 |
October | 0.489790E+09 | 1607.87 | 04-OCT-15:30 | 10.55 | 4.70 | 0.312046E+09 | 474.90 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 8905851.08 | 1165.34 | 04-NOV-16:02 | -9.6 | -11.3 | 0.301552E+09 | 406.70 | 27-NOV-14:39 | -23.9 | -24.2 |
December | 12335422.37 | 1164.45 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293438E+09 | 406.74 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.231123E+11 | 0.421680E+10 | ||||||||
Minimum of Months | 8905851.08 | 1164.45 | -9.6 | -11.3 | 0.276267E+09 | 406.70 | -28.5 | -28.7 | ||
Maximum of Months | 0.577012E+10 | 10090.57 | 15.50 | 10.82 | 0.447321E+09 | 549.56 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15283257.37 | 1563.08 | 21-JAN-17:02 | -5.5 | -5.8 | 0.141843E+09 | 250.70 | 10-JAN-16:00 | -5.5 | -5.8 |
February | 74467335.66 | 1570.47 | 11-FEB-17:02 | -1.2 | -2.7 | 0.128946E+09 | 250.68 | 27-FEB-16:00 | -26.7 | -27.0 |
March | 0.862387E+09 | 2739.24 | 31-MAR-10:20 | -15.7 | -17.0 | 0.158747E+09 | 338.71 | 31-MAR-10:39 | -15.4 | -16.7 |
April | 0.250544E+10 | 6390.61 | 22-APR-09:20 | 8.87 | 3.75 | 0.160639E+09 | 339.10 | 24-APR-08:39 | -0.2 | -3.9 |
May | 0.557129E+10 | 13957.05 | 14-MAY-09:12 | 15.37 | 8.02 | 0.199504E+09 | 338.79 | 11-MAY-07:49 | 15.37 | 8.02 |
June | 0.625004E+10 | 11564.53 | 13-JUN-06:03 | 13.27 | 9.79 | 0.201661E+09 | 339.49 | 13-JUN-10:30 | 21.65 | 12.28 |
July | 0.618244E+10 | 14853.41 | 23-JUL-10:02 | 21.38 | 14.90 | 0.187830E+09 | 339.63 | 12-JUL-10:30 | 21.38 | 14.90 |
August | 0.508815E+10 | 10065.70 | 10-AUG-08:50 | 14.22 | 9.95 | 0.206507E+09 | 339.49 | 10-AUG-10:30 | 18.60 | 11.60 |
September | 0.254145E+10 | 10039.78 | 10-SEP-10:02 | 13.07 | 7.24 | 0.157952E+09 | 338.72 | 15-SEP-10:20 | 6.10 | 4.26 |
October | 0.679825E+09 | 2593.63 | 03-OCT-10:30 | 5.00 | 3.43 | 0.145502E+09 | 335.12 | 03-OCT-10:39 | 5.37 | 3.67 |
November | 13738353.24 | 1561.40 | 04-NOV-16:02 | -9.6 | -11.3 | 0.140522E+09 | 250.68 | 27-NOV-09:00 | -27.2 | -27.4 |
December | 17463270.39 | 1559.44 | 23-DEC-17:02 | -2.6 | -3.4 | 0.136760E+09 | 250.69 | 27-DEC-13:50 | -23.8 | -24.0 |
Annual Sum or Average | 0.298020E+11 | 0.196641E+10 | ||||||||
Minimum of Months | 13738353.24 | 1559.44 | -15.7 | -17.0 | 0.128946E+09 | 250.68 | -27.2 | -27.4 | ||
Maximum of Months | 0.625004E+10 | 14853.41 | 21.38 | 14.90 | 0.206507E+09 | 339.63 | 21.65 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115428E+09 | 2751.57 | 25-JAN-13:40 | -19.5 | -19.7 | 0.304993E+09 | 419.03 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.820560E+09 | 5047.83 | 15-FEB-13:50 | -8.5 | -9.4 | 0.285276E+09 | 549.49 | 15-FEB-14:00 | -7.2 | -8.6 |
March | 0.253642E+10 | 9318.49 | 31-MAR-13:30 | -11.4 | -13.3 | 0.368504E+09 | 549.59 | 29-MAR-13:09 | -11.4 | -13.3 |
April | 0.565725E+10 | 13696.07 | 20-APR-14:00 | 14.40 | 6.23 | 0.357715E+09 | 550.39 | 24-APR-13:50 | 4.40 | -1.0 |
May | 0.804233E+10 | 19305.13 | 14-MAY-12:32 | 18.53 | 9.40 | 0.416445E+09 | 550.46 | 12-MAY-13:50 | 18.53 | 9.40 |
June | 0.903676E+10 | 13189.39 | 29-JUN-14:00 | 25.60 | 16.24 | 0.426306E+09 | 549.55 | 29-JUN-13:30 | 25.60 | 16.24 |
July | 0.897586E+10 | 23323.87 | 23-JUL-13:22 | 25.00 | 15.26 | 0.395966E+09 | 550.00 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.868856E+10 | 22086.06 | 27-AUG-13:02 | 18.07 | 13.70 | 0.436315E+09 | 549.75 | 31-AUG-13:00 | 13.30 | 4.88 |
September | 0.494153E+10 | 11001.80 | 09-SEP-13:30 | 13.35 | 8.71 | 0.349457E+09 | 549.52 | 08-SEP-13:09 | 13.35 | 8.71 |
October | 0.186861E+10 | 10164.19 | 03-OCT-13:30 | 10.85 | 6.24 | 0.325404E+09 | 549.51 | 12-OCT-13:09 | -1.1 | -3.6 |
November | 0.254889E+09 | 3660.38 | 08-NOV-13:50 | -13.4 | -14.2 | 0.303612E+09 | 514.41 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 27416161.39 | 2378.01 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293914E+09 | 406.70 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.509656E+11 | 0.426391E+10 | ||||||||
Minimum of Months | 27416161.39 | 2378.01 | -19.5 | -19.7 | 0.285276E+09 | 406.70 | -18.9 | -19.2 | ||
Maximum of Months | 0.903676E+10 | 23323.87 | 25.60 | 16.24 | 0.436315E+09 | 550.46 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15317410.08 | 1562.16 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192948E+09 | 257.45 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 54262888.30 | 1569.10 | 11-FEB-17:02 | -1.2 | -2.7 | 0.175296E+09 | 257.45 | 27-FEB-10:00 | -33.3 | -33.4 |
March | 0.465276E+09 | 2250.03 | 31-MAR-17:00 | -9.4 | -11.7 | 0.211841E+09 | 297.53 | 31-MAR-15:00 | -9.4 | -11.7 |
April | 0.248717E+10 | 7562.29 | 22-APR-17:10 | 14.13 | 6.18 | 0.205319E+09 | 338.77 | 18-APR-15:00 | 14.13 | 6.18 |
May | 0.414025E+10 | 8562.84 | 29-MAY-18:23 | 14.15 | 8.15 | 0.252243E+09 | 347.84 | 22-MAY-13:00 | 14.15 | 8.15 |
June | 0.532320E+10 | 12542.48 | 10-JUN-17:42 | 21.60 | 11.19 | 0.268113E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.493502E+10 | 8444.05 | 11-JUL-17:40 | 26.10 | 15.25 | 0.248031E+09 | 347.85 | 07-JUL-13:09 | 26.10 | 15.25 |
August | 0.433837E+10 | 9020.51 | 27-AUG-17:03 | 21.02 | 12.75 | 0.266913E+09 | 347.84 | 02-AUG-13:00 | 21.02 | 12.75 |
September | 0.226025E+10 | 4934.11 | 02-SEP-17:16 | 16.70 | 10.26 | 0.205236E+09 | 338.68 | 18-SEP-15:00 | 16.10 | 9.39 |
October | 0.499424E+09 | 2241.93 | 03-OCT-15:10 | 12.62 | 6.83 | 0.195404E+09 | 300.20 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 17512641.06 | 1563.39 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191144E+09 | 257.45 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 17430075.64 | 1559.11 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186017E+09 | 257.47 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.245535E+11 | 0.259851E+10 | ||||||||
Minimum of Months | 15317410.08 | 1559.11 | -9.6 | -11.7 | 0.175296E+09 | 257.45 | -33.3 | -33.4 | ||
Maximum of Months | 0.532320E+10 | 12542.48 | 26.10 | 15.25 | 0.268113E+09 | 347.86 | 26.10 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763910E+09 | 28342.53 | 02-JAN-05:01 | -15.6 |
February | 0.145740E+09 | 24271.25 | 21-FEB-06:01 | -23.3 |
March | 14156530.74 | 21833.00 | 01-MAR-07:01 | -28.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 3216166.10 | 21170.50 | 30-OCT-06:01 | -15.1 |
November | 90729103.69 | 24491.87 | 28-NOV-06:01 | -27.4 |
December | 0.200524E+09 | 24198.66 | 04-DEC-06:03 | -19.4 |
Annual Sum or Average | 0.121827E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.8 | |
Maximum of Months | 0.763910E+09 | 28342.53 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158620E+11 | 20423.54 | 12-JAN-06:13 | -38.3 |
February | 0.120599E+11 | 20405.68 | 27-FEB-06:06 | -35.9 |
March | 0.875965E+10 | 18690.21 | 13-MAR-05:12 | -24.1 |
April | 0.292180E+10 | 17300.45 | 03-APR-05:13 | -21.3 |
May | 0.389947E+09 | 6018.57 | 21-MAY-06:20 | 5.97 |
June | 78908709.63 | 7777.11 | 23-JUN-05:03 | 14.82 |
July | 70801498.11 | 6991.82 | 10-JUL-05:03 | 9.78 |
August | 0.270167E+09 | 7418.34 | 01-AUG-05:02 | 10.00 |
September | 0.153483E+10 | 7862.07 | 28-SEP-05:04 | -2.3 |
October | 0.655116E+10 | 17426.07 | 30-OCT-05:12 | -14.6 |
November | 0.143831E+11 | 19184.65 | 30-NOV-06:12 | -28.2 |
December | 0.167683E+11 | 19739.35 | 15-DEC-06:13 | -33.0 |
Annual Sum or Average | 0.796506E+11 | |||
Minimum of Months | 70801498.11 | 6018.57 | -38.3 | |
Maximum of Months | 0.167683E+11 | 20423.54 | 14.82 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.636486E+10 | 12943.63 | 02-JAN-07:03 | -14.4 |
February | 0.451646E+10 | 12087.30 | 27-FEB-07:04 | -34.9 |
March | 0.333366E+10 | 8913.20 | 06-MAR-07:02 | -20.9 |
April | 0.110555E+10 | 6441.87 | 03-APR-06:02 | -21.5 |
May | 56778454.20 | 5311.58 | 21-MAY-13:42 | 15.40 |
June | 24577734.73 | 4406.68 | 12-JUN-04:02 | 7.38 |
July | 28539547.44 | 4922.22 | 23-JUL-11:22 | 23.35 |
August | 35587084.53 | 4356.57 | 27-AUG-13:02 | 18.07 |
September | 0.346151E+09 | 5183.90 | 17-SEP-11:42 | 13.22 |
October | 0.254634E+10 | 9500.30 | 30-OCT-05:12 | -14.6 |
November | 0.524954E+10 | 11821.48 | 27-NOV-07:03 | -26.7 |
December | 0.616649E+10 | 11543.50 | 04-DEC-07:03 | -19.4 |
Annual Sum or Average | 0.297745E+11 | |||
Minimum of Months | 24577734.73 | 4356.57 | -34.9 | |
Maximum of Months | 0.636486E+10 | 12943.63 | 23.35 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473202E+10 | 11254.23 | 02-JAN-07:01 | -14.4 |
February | 0.330848E+10 | 7541.76 | 21-FEB-07:01 | -23.2 |
March | 0.221068E+10 | 5562.61 | 06-MAR-09:10 | -15.2 |
April | 0.524654E+09 | 6374.48 | 24-APR-05:02 | -3.4 |
May | 28918870.48 | 6330.12 | 30-MAY-05:02 | 7.57 |
June | 26557754.92 | 5419.48 | 07-JUN-04:02 | 5.87 |
July | 32646398.34 | 5726.95 | 11-JUL-04:02 | 12.25 |
August | 36846308.22 | 6280.22 | 30-AUG-05:02 | 0.00 |
September | 0.145380E+09 | 6470.87 | 05-SEP-05:02 | 5.00 |
October | 0.155091E+10 | 5455.78 | 30-OCT-07:23 | -16.1 |
November | 0.362225E+10 | 7540.92 | 13-NOV-07:01 | -17.1 |
December | 0.437020E+10 | 7799.22 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.205895E+11 | |||
Minimum of Months | 26557754.92 | 5419.48 | -23.2 | |
Maximum of Months | 0.473202E+10 | 11254.23 | 12.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271026E+10 | 28554.85 | 02-JAN-05:01 | -15.6 |
February | 0.138119E+10 | 27511.29 | 21-FEB-05:01 | -22.9 |
March | 0.341590E+09 | 25508.23 | 06-MAR-06:01 | -21.1 |
April | 47722704.89 | 24144.67 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 284046.83 | 4260.70 | 25-SEP-06:01 | -1.8 |
October | 0.243103E+09 | 25542.02 | 30-OCT-05:01 | -14.5 |
November | 0.158864E+10 | 27410.46 | 13-NOV-05:11 | -19.8 |
December | 0.245956E+10 | 27449.74 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.877235E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.271026E+10 | 28554.85 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816274E+10 | 32979.82 | 01-JAN-19:22 | -14.4 |
February | 0.503309E+10 | 32818.96 | 27-FEB-04:12 | -35.0 |
March | 0.249407E+10 | 32061.84 | 06-MAR-05:01 | -20.2 |
April | 0.502981E+09 | 30943.12 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 68536112.94 | 27482.78 | 25-SEP-05:01 | -1.2 |
October | 0.179284E+10 | 32076.89 | 30-OCT-04:01 | -14.4 |
November | 0.632538E+10 | 32706.84 | 27-NOV-05:11 | -26.0 |
December | 0.817592E+10 | 32636.04 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.325556E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.817592E+10 | 32979.82 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111246E+11 | 11452.60 | 30-JAN-06:01 | -25.6 |
February | 0.834321E+10 | 11420.37 | 26-FEB-04:12 | -25.6 |
March | 0.562943E+10 | 10908.58 | 13-MAR-01:03 | -21.0 |
April | 0.141838E+10 | 10874.65 | 03-APR-00:12 | -16.9 |
May | 5546400.72 | 8214.69 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 8531964.05 | 8336.93 | 30-AUG-06:02 | 0.10 |
September | 0.393418E+09 | 9469.07 | 28-SEP-05:01 | -2.3 |
October | 0.395126E+10 | 10926.88 | 22-OCT-23:33 | -14.5 |
November | 0.952135E+10 | 11194.06 | 13-NOV-03:52 | -20.0 |
December | 0.113790E+11 | 11152.29 | 03-DEC-10:22 | -22.8 |
Annual Sum or Average | 0.517747E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.113790E+11 | 11452.60 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740029E+10 | 13578.33 | 29-JAN-16:42 | -22.2 |
February | 0.496768E+10 | 13593.01 | 26-FEB-04:12 | -25.6 |
March | 0.254928E+10 | 13014.55 | 06-MAR-05:01 | -20.2 |
April | 0.624303E+09 | 12953.66 | 03-APR-04:11 | -21.1 |
May | 1351295.46 | 4964.43 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3324188.45 | 8350.36 | 31-AUG-06:02 | -1.5 |
September | 0.178721E+09 | 11341.21 | 28-SEP-05:01 | -2.3 |
October | 0.218913E+10 | 12857.48 | 23-OCT-04:11 | -11.1 |
November | 0.627157E+10 | 13249.89 | 13-NOV-03:52 | -20.0 |
December | 0.769238E+10 | 13220.40 | 03-DEC-10:22 | -22.8 |
Annual Sum or Average | 0.318780E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.769238E+10 | 13593.01 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101853E+11 | 21517.45 | 29-JAN-19:22 | -22.5 |
February | 0.602059E+10 | 21574.97 | 26-FEB-04:12 | -25.6 |
March | 0.329352E+10 | 20709.19 | 06-MAR-05:01 | -20.2 |
April | 0.874085E+09 | 20448.43 | 03-APR-04:11 | -21.1 |
May | 14560910.93 | 8849.40 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 8832674.67 | 12858.41 | 30-AUG-06:02 | 0.10 |
September | 0.261786E+09 | 17983.87 | 28-SEP-05:01 | -2.3 |
October | 0.275734E+10 | 20385.40 | 23-OCT-04:11 | -11.1 |
November | 0.801677E+10 | 21048.24 | 13-NOV-03:52 | -20.0 |
December | 0.111776E+11 | 21038.14 | 03-DEC-10:22 | -22.8 |
Annual Sum or Average | 0.426103E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.6 | |
Maximum of Months | 0.111776E+11 | 21574.97 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.749449E+10 | 14239.84 | 29-JAN-10:42 | -25.7 |
February | 0.538005E+10 | 14273.25 | 26-FEB-04:12 | -25.6 |
March | 0.331477E+10 | 13668.14 | 06-MAR-05:01 | -20.2 |
April | 0.761399E+09 | 13505.45 | 03-APR-04:11 | -21.1 |
May | 12324167.06 | 5759.25 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 7371338.45 | 8284.36 | 30-AUG-06:02 | 0.10 |
September | 0.244143E+09 | 11913.00 | 28-SEP-05:01 | -2.3 |
October | 0.251826E+10 | 13496.01 | 23-OCT-04:11 | -11.1 |
November | 0.626136E+10 | 13877.85 | 13-NOV-03:52 | -20.0 |
December | 0.770857E+10 | 13869.95 | 03-DEC-10:22 | -22.8 |
Annual Sum or Average | 0.337027E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.7 | |
Maximum of Months | 0.770857E+10 | 14273.25 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.840779E+10 | 8952.97 | 01-JAN-19:22 | -14.4 |
February | 0.661448E+10 | 8870.28 | 27-FEB-04:12 | -35.0 |
March | 0.457935E+10 | 8490.15 | 06-MAR-05:01 | -20.2 |
April | 0.882980E+09 | 8397.83 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 31000453.46 | 6794.20 | 28-SEP-06:01 | -2.8 |
October | 0.154946E+10 | 8306.85 | 30-OCT-04:01 | -14.4 |
November | 0.583025E+10 | 8553.41 | 13-NOV-03:52 | -20.0 |
December | 0.782878E+10 | 8558.77 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.357241E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.840779E+10 | 8952.97 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581440E+10 | 10967.42 | 01-JAN-19:22 | -14.4 |
February | 0.398548E+10 | 10858.87 | 27-FEB-04:12 | -35.0 |
March | 0.174654E+10 | 10441.92 | 06-MAR-05:01 | -20.2 |
April | 0.264230E+09 | 10199.58 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 16374331.35 | 8367.93 | 28-SEP-06:01 | -2.8 |
October | 0.805797E+09 | 10245.33 | 30-OCT-04:01 | -14.4 |
November | 0.394015E+10 | 10527.63 | 27-NOV-05:11 | -26.0 |
December | 0.548889E+10 | 10399.55 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.220619E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.581440E+10 | 10967.42 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191235E+11 | 28420.69 | 12-JAN-07:10 | -38.3 |
February | 0.134489E+11 | 27009.73 | 27-FEB-07:10 | -34.9 |
March | 0.106869E+11 | 24908.52 | 01-MAR-07:10 | -28.8 |
April | 0.374228E+10 | 22311.50 | 03-APR-06:10 | -21.5 |
May | 0.126174E+10 | 14373.05 | 04-MAY-06:10 | 4.18 |
June | 0.429955E+09 | 13100.50 | 02-JUN-06:10 | 7.15 |
July | 0.346223E+09 | 12426.87 | 05-JUL-11:05 | 10.60 |
August | 0.792885E+09 | 15288.80 | 31-AUG-06:10 | -1.5 |
September | 0.241112E+10 | 16906.67 | 29-SEP-07:00 | -5.6 |
October | 0.731284E+10 | 21663.22 | 31-OCT-07:00 | -19.4 |
November | 0.161498E+11 | 24786.98 | 29-NOV-08:00 | -28.9 |
December | 0.193992E+11 | 26643.32 | 15-DEC-07:10 | -33.4 |
Annual Sum or Average | 0.951053E+11 | |||
Minimum of Months | 0.346223E+09 | 12426.87 | -38.3 | |
Maximum of Months | 0.193992E+11 | 28420.69 | 10.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591021E+10 | 11650.64 | 01-JAN-19:22 | -14.4 |
February | 0.439412E+10 | 11538.03 | 27-FEB-04:12 | -35.0 |
March | 0.253911E+10 | 11149.47 | 06-MAR-05:01 | -20.2 |
April | 0.304220E+09 | 10544.49 | 03-APR-04:11 | -21.1 |
May | 1762829.14 | 4907.26 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 22233489.40 | 8906.41 | 28-SEP-06:01 | -2.8 |
October | 0.994203E+09 | 10949.47 | 30-OCT-04:01 | -14.4 |
November | 0.393725E+10 | 11202.11 | 27-NOV-05:11 | -26.0 |
December | 0.550552E+10 | 11062.73 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.236086E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.591021E+10 | 11650.64 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.734637E+10 | 9875.43 | 01-JAN-19:22 | -14.4 |
February | 0.494211E+10 | 9649.45 | 21-FEB-02:62 | -23.8 |
March | 0.286584E+10 | 9350.12 | 06-MAR-05:01 | -20.2 |
April | 0.479689E+09 | 9271.44 | 03-APR-04:11 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 56367195.29 | 7740.25 | 30-SEP-05:01 | -4.5 |
October | 0.176888E+10 | 9288.89 | 30-OCT-02:23 | -13.1 |
November | 0.567210E+10 | 9584.52 | 13-NOV-03:52 | -20.0 |
December | 0.731283E+10 | 9544.72 | 11-DEC-02:52 | -21.1 |
Annual Sum or Average | 0.304442E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.8 | |
Maximum of Months | 0.734637E+10 | 9875.43 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497858E+10 | 12320.91 | 01-JAN-19:22 | -14.4 |
February | 0.289566E+10 | 12015.72 | 27-FEB-05:01 | -36.1 |
March | 0.122043E+10 | 11723.30 | 06-MAR-05:01 | -20.2 |
April | 0.208987E+09 | 11581.10 | 03-APR-04:11 | -21.1 |
May | 19101.26 | 127.34 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1056278.76 | 5411.76 | 31-AUG-06:02 | -1.5 |
September | 38116895.11 | 9182.76 | 26-SEP-06:01 | 0.00 |
October | 0.100159E+10 | 11511.38 | 31-OCT-04:01 | -17.9 |
November | 0.382191E+10 | 11950.73 | 13-NOV-05:11 | -19.8 |
December | 0.505498E+10 | 11963.89 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.192213E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.505498E+10 | 12320.91 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647958E+10 | 18576.33 | 01-JAN-19:22 | -14.4 |
February | 0.323755E+10 | 18057.61 | 27-FEB-05:01 | -36.1 |
March | 0.143707E+10 | 17664.35 | 06-MAR-05:01 | -20.2 |
April | 0.262691E+09 | 17151.19 | 03-APR-04:11 | -21.1 |
May | 953624.54 | 5819.59 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 876325.97 | 5972.29 | 30-AUG-06:02 | 0.10 |
September | 44722617.03 | 13863.63 | 28-SEP-06:01 | -2.8 |
October | 0.112240E+10 | 17167.23 | 30-OCT-04:01 | -14.4 |
November | 0.445756E+10 | 18020.09 | 27-NOV-05:11 | -26.0 |
December | 0.703413E+10 | 18059.72 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.240775E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.703413E+10 | 18576.33 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496428E+10 | 12262.34 | 01-JAN-19:22 | -14.4 |
February | 0.314298E+10 | 11957.97 | 27-FEB-05:01 | -36.1 |
March | 0.162267E+10 | 11683.71 | 06-MAR-05:01 | -20.2 |
April | 0.246609E+09 | 11406.59 | 03-APR-04:11 | -21.1 |
May | 959014.69 | 4646.91 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 886002.99 | 5232.30 | 30-AUG-06:02 | 0.10 |
September | 43951094.34 | 9143.57 | 26-SEP-06:01 | 0.00 |
October | 0.113136E+10 | 11444.91 | 31-OCT-04:01 | -17.9 |
November | 0.372068E+10 | 11898.25 | 27-NOV-05:11 | -26.0 |
December | 0.497350E+10 | 11916.57 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.198479E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.497350E+10 | 12262.34 | 14.88 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136153E+10 | 1503.90 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.107232E+10 | 1503.90 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.109492E+10 | 1503.90 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.904218E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.953747E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.936515E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.884772E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.100621E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.947249E+09 | 1444.51 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.109556E+10 | 1503.90 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.128075E+10 | 1503.90 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.136632E+10 | 1503.90 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.129041E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.884772E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.136632E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.841229E+09 | 952.10 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.666190E+09 | 952.10 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.688901E+09 | 952.10 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.573532E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.608619E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.596597E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.563680E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.640205E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.598924E+09 | 847.75 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.687038E+09 | 952.10 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.785425E+09 | 952.10 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.857926E+09 | 952.10 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.810827E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.563680E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.857926E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129734E+10 | 1503.90 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.102933E+10 | 1503.90 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.107896E+10 | 1503.90 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.906860E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.960739E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.943042E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.890345E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.100966E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.940799E+09 | 1398.14 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.107097E+10 | 1503.90 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.120456E+10 | 1503.90 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.133202E+10 | 1503.90 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.126646E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.890345E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.133202E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.845995E+09 | 952.03 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.659576E+09 | 952.03 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.687590E+09 | 952.03 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.573985E+09 | 717.03 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.604170E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.593698E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.560465E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.636444E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.596820E+09 | 916.78 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.683567E+09 | 952.03 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.786944E+09 | 952.03 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.860728E+09 | 952.03 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.808998E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.560465E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.860728E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135725E+10 | 1503.90 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.106789E+10 | 1503.90 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.109294E+10 | 1503.90 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.903506E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.953348E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.935725E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.883900E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.100562E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.945937E+09 | 1440.73 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.109186E+10 | 1503.90 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.127517E+10 | 1503.90 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.136491E+10 | 1503.90 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.128780E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.883900E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.136491E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.839054E+09 | 952.10 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.664952E+09 | 952.10 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.688043E+09 | 952.10 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.573165E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.608250E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.596295E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.563352E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.639811E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.598314E+09 | 839.92 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.685859E+09 | 952.10 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.782968E+09 | 952.10 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.856831E+09 | 952.10 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.809689E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.563352E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.856831E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129383E+10 | 1503.90 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.102707E+10 | 1503.90 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.107808E+10 | 1503.90 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.906242E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.960066E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.942427E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.889777E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.100898E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.940082E+09 | 1390.65 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.106876E+10 | 1503.90 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.120162E+10 | 1503.90 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.132689E+10 | 1503.90 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.126438E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.889777E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.132689E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.843805E+09 | 952.03 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.658194E+09 | 952.03 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.686563E+09 | 952.03 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.573515E+09 | 707.35 | 04-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.603854E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.593439E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.560228E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.635984E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.596264E+09 | 914.86 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.682288E+09 | 952.03 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.784287E+09 | 952.03 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.859809E+09 | 952.03 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.807823E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.560228E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.859809E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136153E+10 | 1503.90 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.107232E+10 | 1503.90 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.109492E+10 | 1503.90 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.904218E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.953747E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.936515E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.884772E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.100621E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.947249E+09 | 1444.51 | 28-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.109556E+10 | 1503.90 | 03-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.128075E+10 | 1503.90 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.136632E+10 | 1503.90 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.129041E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.884772E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.136632E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.841228E+09 | 952.10 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.666190E+09 | 952.10 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.688901E+09 | 952.10 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.573532E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.608619E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.596597E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.563680E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.640204E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.598924E+09 | 847.76 | 28-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.687038E+09 | 952.10 | 03-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.785425E+09 | 952.10 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.857926E+09 | 952.10 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.810826E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.563680E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.857926E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129734E+10 | 1503.90 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.102933E+10 | 1503.90 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.107896E+10 | 1503.90 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.906859E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.960739E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.943042E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.890345E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.100966E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.940799E+09 | 1398.15 | 28-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.107097E+10 | 1503.90 | 03-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.120456E+10 | 1503.90 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.133202E+10 | 1503.90 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.126646E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.890345E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.133202E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.845995E+09 | 952.03 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.659576E+09 | 952.03 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.687590E+09 | 952.03 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.573985E+09 | 717.03 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.604170E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.593698E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.560465E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.636444E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.596819E+09 | 916.78 | 29-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.683566E+09 | 952.03 | 03-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.786943E+09 | 952.03 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.860728E+09 | 952.03 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.808998E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.560465E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.860728E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.136153E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939817E+09 |
February | 0.901968E+09 | 0.107232E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754476E+09 |
March | 0.107774E+10 | 0.109492E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110404E+10 |
April | 0.956342E+09 | 0.904218E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121403E+10 |
May | 0.103597E+10 | 0.953747E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742820E+09 |
June | 0.103308E+10 | 0.936515E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007883.43 | 0.451978E+09 |
July | 0.959235E+09 | 0.884772E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3289709.51 | 0.338517E+09 |
August | 0.107774E+10 | 0.100621E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 459413.66 | 0.388269E+09 |
September | 0.956342E+09 | 0.947249E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440659E+09 |
October | 0.994195E+09 | 0.109556E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941287E+09 |
November | 0.984487E+09 | 0.128075E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345082E+09 |
December | 0.959235E+09 | 0.136632E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682131E+09 |
Annual Sum or Average | 0.119305E+11 | 0.129041E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4757006.60 | 0.834310E+10 |
Minimum of Months | 0.901968E+09 | 0.884772E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338517E+09 |
Maximum of Months | 0.107774E+10 | 0.136632E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3289709.51 | 0.121403E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.841229E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627235E+09 |
February | 0.571020E+09 | 0.666190E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503462E+09 |
March | 0.682301E+09 | 0.688901E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740440E+09 |
April | 0.605444E+09 | 0.573532E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825567E+09 |
May | 0.655854E+09 | 0.608619E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502141E+09 |
June | 0.654023E+09 | 0.596597E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 700150.46 | 0.295727E+09 |
July | 0.607275E+09 | 0.563680E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513289.63 | 0.223297E+09 |
August | 0.682301E+09 | 0.640205E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 378889.36 | 0.257421E+09 |
September | 0.605444E+09 | 0.598924E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300452E+09 |
October | 0.629407E+09 | 0.687038E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630377E+09 |
November | 0.623262E+09 | 0.785425E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230013E+09 |
December | 0.607275E+09 | 0.857926E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454983E+09 |
Annual Sum or Average | 0.755301E+10 | 0.810827E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3592329.44 | 0.559112E+10 |
Minimum of Months | 0.571020E+09 | 0.563680E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223297E+09 |
Maximum of Months | 0.682301E+09 | 0.857926E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513289.63 | 0.825567E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.129734E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.942296E+09 |
February | 0.901968E+09 | 0.102933E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759444E+09 |
March | 0.107774E+10 | 0.107896E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113205E+10 |
April | 0.956342E+09 | 0.906860E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128953E+10 |
May | 0.103597E+10 | 0.960739E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760159E+09 |
June | 0.103308E+10 | 0.943042E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021882.51 | 0.444338E+09 |
July | 0.959235E+09 | 0.890345E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3349456.90 | 0.336636E+09 |
August | 0.107774E+10 | 0.100966E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 471909.90 | 0.396669E+09 |
September | 0.956342E+09 | 0.940799E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463724E+09 |
October | 0.994195E+09 | 0.107097E+10 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962117E+09 |
November | 0.984487E+09 | 0.120456E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345909E+09 |
December | 0.959235E+09 | 0.133202E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683140E+09 |
Annual Sum or Average | 0.119305E+11 | 0.126646E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4843249.31 | 0.851601E+10 |
Minimum of Months | 0.901968E+09 | 0.890345E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336636E+09 |
Maximum of Months | 0.107774E+10 | 0.133202E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3349456.90 | 0.128953E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.845995E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627249E+09 |
February | 0.570983E+09 | 0.659576E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503372E+09 |
March | 0.682256E+09 | 0.687590E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739351E+09 |
April | 0.605404E+09 | 0.573985E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846170E+09 |
May | 0.655811E+09 | 0.604170E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505145E+09 |
June | 0.653980E+09 | 0.593698E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 671942.88 | 0.299624E+09 |
July | 0.607235E+09 | 0.560465E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121446.66 | 0.225241E+09 |
August | 0.682256E+09 | 0.636444E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306034.21 | 0.259280E+09 |
September | 0.605404E+09 | 0.596820E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297952E+09 |
October | 0.629366E+09 | 0.683567E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628293E+09 |
November | 0.623221E+09 | 0.786944E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230081E+09 |
December | 0.607235E+09 | 0.860728E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454972E+09 |
Annual Sum or Average | 0.755252E+10 | 0.808998E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3099423.76 | 0.561673E+10 |
Minimum of Months | 0.570983E+09 | 0.560465E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225241E+09 |
Maximum of Months | 0.682256E+09 | 0.860728E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121446.66 | 0.846170E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.135725E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504313E+09 |
February | 0.901968E+09 | 0.106789E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404442E+09 |
March | 0.107774E+10 | 0.109294E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598454E+09 |
April | 0.956342E+09 | 0.903506E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659928E+09 |
May | 0.103597E+10 | 0.953348E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398965E+09 |
June | 0.103308E+10 | 0.935725E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 555317.00 | 0.242921E+09 |
July | 0.959235E+09 | 0.883900E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1910768.77 | 0.182035E+09 |
August | 0.107774E+10 | 0.100562E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260374.56 | 0.217795E+09 |
September | 0.956342E+09 | 0.945937E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255157E+09 |
October | 0.994195E+09 | 0.109186E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535523E+09 |
November | 0.984487E+09 | 0.127517E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188340E+09 |
December | 0.959235E+09 | 0.136491E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367942E+09 |
Annual Sum or Average | 0.119305E+11 | 0.128780E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2726460.34 | 0.455582E+10 |
Minimum of Months | 0.901968E+09 | 0.883900E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182035E+09 |
Maximum of Months | 0.107774E+10 | 0.136491E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1910768.77 | 0.659928E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.839054E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336298E+09 |
February | 0.571020E+09 | 0.664952E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269964E+09 |
March | 0.682301E+09 | 0.688043E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404419E+09 |
April | 0.605444E+09 | 0.573165E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459245E+09 |
May | 0.655854E+09 | 0.608250E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281120E+09 |
June | 0.654023E+09 | 0.596295E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377915.11 | 0.164126E+09 |
July | 0.607275E+09 | 0.563352E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199909.27 | 0.124938E+09 |
August | 0.682301E+09 | 0.639811E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 178166.62 | 0.148083E+09 |
September | 0.605444E+09 | 0.598314E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175646E+09 |
October | 0.629407E+09 | 0.685859E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360619E+09 |
November | 0.623262E+09 | 0.782968E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125208E+09 |
December | 0.607275E+09 | 0.856831E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244790E+09 |
Annual Sum or Average | 0.755301E+10 | 0.809689E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1755991.00 | 0.309446E+10 |
Minimum of Months | 0.571020E+09 | 0.563352E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124938E+09 |
Maximum of Months | 0.682301E+09 | 0.856831E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199909.27 | 0.459245E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.129383E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154231E+11 |
February | 0.901968E+09 | 0.102707E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122077E+11 |
March | 0.107774E+10 | 0.107808E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135648E+11 |
April | 0.956342E+09 | 0.906242E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788140E+10 |
May | 0.103597E+10 | 0.960066E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465106E+10 |
June | 0.103308E+10 | 0.942427E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45862741.01 | 0.267901E+10 |
July | 0.959235E+09 | 0.889777E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67462545.65 | 0.205173E+10 |
August | 0.107774E+10 | 0.100898E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15665012.39 | 0.376808E+10 |
September | 0.956342E+09 | 0.940082E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582929E+10 |
October | 0.994195E+09 | 0.106876E+10 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989653E+10 |
November | 0.984487E+09 | 0.120162E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150685E+11 |
December | 0.959235E+09 | 0.132689E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155736E+11 |
Annual Sum or Average | 0.119305E+11 | 0.126438E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128990E+09 | 0.108595E+12 |
Minimum of Months | 0.901968E+09 | 0.889777E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205173E+10 |
Maximum of Months | 0.107774E+10 | 0.132689E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67462545.65 | 0.155736E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.843805E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336272E+09 |
February | 0.570983E+09 | 0.658194E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269707E+09 |
March | 0.682256E+09 | 0.686563E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401674E+09 |
April | 0.605404E+09 | 0.573515E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468553E+09 |
May | 0.655811E+09 | 0.603854E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274410E+09 |
June | 0.653980E+09 | 0.593439E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370223.29 | 0.163789E+09 |
July | 0.607235E+09 | 0.560228E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216508.59 | 0.123066E+09 |
August | 0.682256E+09 | 0.635984E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173264.92 | 0.146532E+09 |
September | 0.605404E+09 | 0.596264E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171966E+09 |
October | 0.629366E+09 | 0.682288E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357362E+09 |
November | 0.623221E+09 | 0.784287E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125296E+09 |
December | 0.607235E+09 | 0.859809E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244781E+09 |
Annual Sum or Average | 0.755252E+10 | 0.807823E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1759996.79 | 0.308341E+10 |
Minimum of Months | 0.570983E+09 | 0.560228E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123066E+09 |
Maximum of Months | 0.682256E+09 | 0.859809E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216508.59 | 0.468553E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.136153E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790795E+09 |
February | 0.901968E+09 | 0.107232E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637233E+09 |
March | 0.107774E+10 | 0.109492E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946248E+09 |
April | 0.956342E+09 | 0.904218E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106272E+10 |
May | 0.103597E+10 | 0.953747E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652915E+09 |
June | 0.103308E+10 | 0.936515E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854168.48 | 0.391442E+09 |
July | 0.959235E+09 | 0.884772E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2821299.39 | 0.291505E+09 |
August | 0.107774E+10 | 0.100621E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 394408.71 | 0.341272E+09 |
September | 0.956342E+09 | 0.947249E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395521E+09 |
October | 0.994195E+09 | 0.109556E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822831E+09 |
November | 0.984487E+09 | 0.128075E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291844E+09 |
December | 0.959235E+09 | 0.136632E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574498E+09 |
Annual Sum or Average | 0.119305E+11 | 0.129041E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4069876.58 | 0.719883E+10 |
Minimum of Months | 0.901968E+09 | 0.884772E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291505E+09 |
Maximum of Months | 0.107774E+10 | 0.136632E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2821299.39 | 0.106272E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.841228E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526921E+09 |
February | 0.421807E+09 | 0.666190E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424797E+09 |
March | 0.502994E+09 | 0.688901E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.636511E+09 |
April | 0.447140E+09 | 0.573532E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721203E+09 |
May | 0.484071E+09 | 0.608619E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436637E+09 |
June | 0.482240E+09 | 0.596597E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 600751.48 | 0.254932E+09 |
July | 0.448971E+09 | 0.563680E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2237530.71 | 0.191149E+09 |
August | 0.502994E+09 | 0.640204E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 330337.17 | 0.224256E+09 |
September | 0.447140E+09 | 0.598924E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266277E+09 |
October | 0.465148E+09 | 0.687038E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550825E+09 |
November | 0.460569E+09 | 0.785425E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194167E+09 |
December | 0.448971E+09 | 0.857926E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382382E+09 |
Annual Sum or Average | 0.557719E+10 | 0.810826E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3168619.36 | 0.481006E+10 |
Minimum of Months | 0.421807E+09 | 0.563680E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191149E+09 |
Maximum of Months | 0.502994E+09 | 0.857926E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2237530.71 | 0.721203E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.129734E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792264E+09 |
February | 0.901968E+09 | 0.102933E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643363E+09 |
March | 0.107774E+10 | 0.107896E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978518E+09 |
April | 0.956342E+09 | 0.906859E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112751E+10 |
May | 0.103597E+10 | 0.960739E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663273E+09 |
June | 0.103308E+10 | 0.943042E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 864223.38 | 0.385242E+09 |
July | 0.959235E+09 | 0.890345E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2882353.44 | 0.289960E+09 |
August | 0.107774E+10 | 0.100966E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400846.05 | 0.346429E+09 |
September | 0.956342E+09 | 0.940799E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410694E+09 |
October | 0.994195E+09 | 0.107097E+10 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844037E+09 |
November | 0.984487E+09 | 0.120456E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293175E+09 |
December | 0.959235E+09 | 0.133202E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575048E+09 |
Annual Sum or Average | 0.119305E+11 | 0.126646E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4147422.88 | 0.734952E+10 |
Minimum of Months | 0.901968E+09 | 0.890345E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289960E+09 |
Maximum of Months | 0.107774E+10 | 0.133202E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2882353.44 | 0.112751E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.845995E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526906E+09 |
February | 0.570983E+09 | 0.659576E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424600E+09 |
March | 0.682256E+09 | 0.687590E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634773E+09 |
April | 0.605404E+09 | 0.573985E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738891E+09 |
May | 0.655811E+09 | 0.604170E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441706E+09 |
June | 0.653980E+09 | 0.593698E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 569463.42 | 0.259745E+09 |
July | 0.607235E+09 | 0.560465E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1816069.82 | 0.194115E+09 |
August | 0.682256E+09 | 0.636444E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262950.39 | 0.227163E+09 |
September | 0.605404E+09 | 0.596819E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264626E+09 |
October | 0.629366E+09 | 0.683566E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548598E+09 |
November | 0.623221E+09 | 0.786943E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194315E+09 |
December | 0.607235E+09 | 0.860728E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382392E+09 |
Annual Sum or Average | 0.755252E+10 | 0.808998E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2648483.63 | 0.483783E+10 |
Minimum of Months | 0.570983E+09 | 0.560465E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194115E+09 |
Maximum of Months | 0.682256E+09 | 0.860728E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1816069.82 | 0.738891E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103157E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841192E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128215E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147267E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.880165E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561518.57 | 0.516574E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2283432.72 | 0.383976E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123375.24 | 0.463722E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549629E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113737E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391640E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754838E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2968326.53 | 0.970549E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383976E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2283432.72 | 0.147267E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130756E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106665E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161567E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184113E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111217E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711736.32 | 0.655579E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3070145.19 | 0.486991E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168151.21 | 0.582342E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675142E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139525E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491269E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955688E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3950032.72 | 0.121854E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486991E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3070145.19 | 0.184113E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138102E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112056E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167516E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189537E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115914E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467382.39 | 0.697126E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251283.83 | 0.525182E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36224.73 | 0.605192E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681198E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141807E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511333E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100737E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2754890.95 | 0.126767E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511333E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2251283.83 | 0.189537E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4206.21 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2520.29 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1886.10 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2546.65 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1212.34 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1148.75 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 21-JUL-16:00 | 899.31 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 948.52 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1444.51 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 718.50 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.59 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1343.82 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1449.42 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.50 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 144.46 | 4206.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2802.42 | 28-JAN-23:51 |
February | 827.22 | 01-FEB-10:09 | 952.10 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1680.19 | 25-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 952.10 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1257.65 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1692.85 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 806.83 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 750.10 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 | 29-JUL-20:10 | 602.79 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 625.08 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 847.75 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 486.19 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 952.10 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1040.39 | 21-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.51 | 09-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 966.28 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.19 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 | 2802.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4208.50 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2520.29 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1897.04 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2789.39 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1222.56 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.16 | 30-JUN-15:00 | 1140.80 | 18-JUN-14:20 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 29-JUL-20:10 | 917.13 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.41 | 11-AUG-16:00 | 945.53 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1398.14 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 750.83 | 30-SEP-21:00 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1560.59 | 21-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1344.93 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1449.42 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.83 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 149.28 | 4208.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2802.88 | 28-JAN-23:51 |
February | 827.17 | 01-FEB-10:09 | 952.03 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1680.19 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 952.03 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1257.99 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 717.03 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2078.96 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 803.22 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 30-JUN-15:00 | 746.71 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 21-JUL-16:00 | 611.50 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 11-AUG-16:00 | 623.31 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 916.78 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 477.28 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 952.03 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1040.39 | 21-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.70 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 966.28 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.28 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 2802.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2248.84 | 28-JAN-23:51 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1338.34 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1003.24 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1399.99 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 683.21 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 30-JUN-15:00 | 665.85 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 29-JUL-17:02 | 487.32 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 11-AUG-16:00 | 555.20 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1440.73 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 430.58 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 859.25 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 729.77 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 769.69 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.58 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 | 2248.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1498.43 | 28-JAN-23:51 |
February | 827.22 | 01-FEB-10:09 | 952.10 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 892.22 | 25-FEB-00:55 |
March | 827.22 | 01-MAR-10:09 | 952.10 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 669.69 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 945.58 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 469.71 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 441.96 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 29-JUL-20:00 | 333.80 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 372.46 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 839.92 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 299.33 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 952.10 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 573.27 | 21-OCT-04:01 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 484.47 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 513.12 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.33 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 1498.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 80491.01 | 12-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 73851.80 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 66440.60 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 57215.69 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 21865.65 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.29 | 21-JUN-17:00 | 17988.07 | 02-JUN-06:10 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6051.02 | 21-JUL-16:10 | 16479.84 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1956.78 | 11-AUG-16:10 | 28472.91 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1390.65 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31782.69 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 52555.11 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 67137.34 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 74332.72 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16479.84 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6051.02 | 80491.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1498.61 | 28-JAN-23:51 |
February | 827.17 | 01-FEB-10:09 | 952.03 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 892.22 | 25-FEB-00:55 |
March | 827.17 | 01-MAR-10:09 | 952.03 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 669.45 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 707.35 | 04-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1118.18 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 448.62 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 30-JUN-15:00 | 436.73 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 21-JUL-16:00 | 335.68 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 11-AUG-16:00 | 369.45 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 914.86 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 291.61 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 952.03 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 570.43 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 485.42 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 513.12 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.61 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 1498.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.01 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2097.00 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1574.42 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2215.98 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1085.57 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1038.11 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 21-JUL-16:00 | 782.40 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 849.33 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1444.51 | 28-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 663.16 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1298.76 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1121.27 | 09-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1205.78 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.16 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 120.83 | 3537.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 952.10 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 952.10 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1397.74 | 25-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 952.10 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1049.92 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1474.88 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 720.64 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 685.50 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 | 29-JUL-20:10 | 524.43 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 558.71 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 847.76 | 28-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 447.62 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 952.10 | 03-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 863.29 | 21-OCT-04:01 |
November | 805.43 | 01-NOV-07:10 | 952.10 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.24 | 09-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 952.10 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 803.85 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.62 | |||||
Maximum of Months | 805.43 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 101.21 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3537.01 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1503.90 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2096.63 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1503.90 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1722.24 | 12-MAR-14:53 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2415.13 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1092.01 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 | 30-JUN-15:00 | 1019.26 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 | 29-JUL-20:10 | 797.80 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 11-AUG-16:00 | 846.13 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1398.15 | 28-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 677.30 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1503.90 | 03-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1312.48 | 21-OCT-04:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1130.01 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1205.78 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.30 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 | 3537.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2357.99 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 952.03 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1397.74 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 952.03 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1050.11 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 717.03 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1789.32 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 719.48 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 30-JUN-15:00 | 674.52 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 21-JUL-16:00 | 532.32 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 | 11-AUG-16:00 | 558.35 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 916.78 | 29-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 440.69 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 952.03 | 03-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 861.69 | 21-OCT-04:01 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 747.38 | 09-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 803.85 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.69 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 2357.99 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4690.30 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2823.56 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2002.32 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3127.77 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1495.31 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.59 | 30-JUN-15:00 | 1431.00 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 29-JUL-17:02 | 994.70 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 11-AUG-16:00 | 1173.27 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 897.89 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1856.28 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1554.37 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1612.92 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 4690.30 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5894.43 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3599.81 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2556.22 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3912.00 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1891.42 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.56 | 30-JUN-15:00 | 1760.23 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.75 | 29-JUL-17:02 | 1245.56 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 11-AUG-16:00 | 1474.31 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1075.36 | 30-SEP-21:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2283.32 | 21-OCT-04:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1959.21 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2057.96 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.75 | 5894.43 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6110.65 | 28-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3779.79 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2782.64 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4211.45 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1839.40 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.55 | 30-JUN-15:00 | 1749.16 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 21-JUL-16:00 | 1417.67 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 11-AUG-16:00 | 1413.97 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1133.25 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2287.61 | 21-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2006.17 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2148.49 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.25 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 6110.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8530.68 | 27-JAN-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9091.87 | 10-FEB-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12456.27 | 23-MAR-07:50 | 6035.01 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39945.54 | 28-APR-05:02 | 3811.58 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43275.10 | 25-MAY-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46178.82 | 21-JUN-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46884.36 | 17-JUL-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47053.94 | 14-AUG-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44103.57 | 05-SEP-05:02 | 3811.58 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19727.27 | 06-OCT-07:06 | 30175.04 | 35669.85 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8954.53 | 03-NOV-16:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8150.61 | 22-DEC-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 8150.61 | 0.00 | 3963.42 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47053.94 | 30175.04 | 35669.85 | 92601.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.24 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 996.79 |
March | 1313.46 | 22-MAR-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.37 |
April | 4162.36 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.03 |
May | 7329.89 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.02 |
June | 8497.22 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
July | 8645.31 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
August | 7343.03 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 |
September | 2913.74 | 07-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 |
October | 1327.74 | 03-OCT-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.95 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.47 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8645.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 1240.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3149.12 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2956.80 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1161.18 |
March | 3287.90 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.91 |
April | 3005.38 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.29 |
May | 3545.92 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 |
June | 4608.19 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 0.00 |
July | 4907.00 | 12-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
August | 4168.59 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
September | 2135.15 | 02-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.82 |
October | 2278.17 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2074.96 |
November | 3103.17 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3332.32 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2135.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4907.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.63 | 2074.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5832.27 | 11-JAN-17:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4479.86 | 17-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5727.95 | 31-MAR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3774.23 | 13-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.95 |
May | 3706.79 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 |
June | 4904.10 | 22-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 |
July | 5539.90 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.81 |
August | 4815.31 | 11-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 0.00 |
September | 3336.61 | 15-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 |
October | 3642.69 | 27-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.51 |
November | 4590.96 | 09-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4924.35 | 15-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3336.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5832.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 195.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5903.88 | 20-JAN-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6612.10 | 09-FEB-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7267.35 | 22-MAR-15:20 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13337.34 | 21-APR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32925.75 | 11-MAY-05:02 | 3811.58 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34134.36 | 23-JUN-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35580.13 | 24-JUL-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33734.84 | 11-AUG-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13453.43 | 01-SEP-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7721.82 | 05-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6196.11 | 02-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5661.36 | 21-DEC-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5661.36 | 0.00 | 3963.42 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35580.13 | 6035.01 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5304.34 | 20-JAN-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6314.97 | 09-FEB-15:50 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7279.07 | 22-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13035.58 | 21-APR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17663.59 | 31-MAY-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31712.18 | 23-JUN-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32540.11 | 25-JUL-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32491.10 | 03-AUG-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12201.08 | 01-SEP-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7380.23 | 03-OCT-15:50 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5450.08 | 02-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4993.23 | 23-DEC-17:02 | 1905.79 | 2377.78 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4993.23 | 1905.79 | 2377.78 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32540.11 | 6035.01 | 7133.97 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1294.82 | 21-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 |
February | 1301.48 | 11-FEB-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 |
March | 1617.19 | 22-MAR-16:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2207.46 | 28-APR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 |
May | 6118.04 | 31-MAY-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
June | 10545.76 | 20-JUN-05:02 | 669.60 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 |
July | 9998.25 | 11-JUL-06:03 | 1071.35 | 1236.19 | 2677.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 |
August | 5133.89 | 02-AUG-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
September | 2249.12 | 01-SEP-16:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 |
October | 1624.91 | 04-OCT-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.65 |
November | 1290.93 | 04-NOV-16:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1295.17 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1290.93 | 334.80 | 417.71 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10545.76 | 1272.23 | 1236.19 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1550.08 | 21-JAN-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
February | 1556.39 | 11-FEB-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 |
March | 2462.47 | 22-MAR-10:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 |
April | 5666.85 | 22-APR-09:30 | 261.23 | 195.65 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
May | 16120.43 | 14-MAY-09:41 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.13 |
June | 11174.12 | 13-JUN-06:03 | 678.26 | 782.61 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 |
July | 14985.07 | 23-JUL-09:42 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.14 |
August | 9866.06 | 10-AUG-08:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 |
September | 5231.87 | 10-SEP-10:04 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.37 |
October | 2377.52 | 03-OCT-10:20 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.22 |
November | 1545.58 | 04-NOV-16:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1549.95 | 23-DEC-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1545.58 | 211.95 | 163.03 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16120.43 | 805.43 | 782.61 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2488.30 | 21-JAN-17:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 |
February | 4221.40 | 15-FEB-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8316.65 | 31-MAR-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.27 |
April | 13941.78 | 20-APR-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
May | 24822.02 | 14-MAY-12:22 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.65 |
June | 13798.23 | 29-JUN-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 0.00 |
July | 24838.16 | 23-JUL-13:42 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 |
August | 22011.86 | 27-AUG-13:22 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.36 |
September | 10899.91 | 07-SEP-14:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
October | 9550.45 | 03-OCT-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.47 |
November | 3528.83 | 08-NOV-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.76 |
December | 2481.94 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2481.94 | 334.80 | 257.52 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24838.16 | 1306.65 | 927.16 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | 331.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1626.31 | 21-JAN-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.68 |
February | 1632.10 | 11-FEB-17:02 | 211.94 | 264.43 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.81 |
March | 2242.42 | 22-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7057.49 | 21-APR-17:50 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 |
May | 14296.55 | 14-MAY-19:02 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.38 |
June | 13198.46 | 10-JUN-17:05 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 |
July | 8801.55 | 11-JUL-17:40 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 0.00 |
August | 8877.68 | 27-AUG-17:23 | 0.00 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.77 |
September | 4480.75 | 02-SEP-17:20 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.80 |
October | 2227.85 | 03-OCT-15:10 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
November | 1625.00 | 04-NOV-16:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1626.68 | 23-DEC-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1625.00 | 0.00 | 130.42 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14296.55 | 805.38 | 586.93 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 371.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1046.64 | 21-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 |
February | 1047.87 | 11-FEB-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 |
March | 1160.75 | 22-MAR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1579.43 | 28-APR-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.21 |
May | 3077.73 | 31-MAY-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
June | 8506.73 | 07-JUN-04:02 | 0.00 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.79 |
July | 8680.32 | 11-JUL-04:02 | 0.00 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.33 |
August | 4672.52 | 02-AUG-06:02 | 1339.19 | 1545.24 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
September | 2021.21 | 01-SEP-16:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.63 |
October | 1425.96 | 06-OCT-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 |
November | 1055.26 | 04-NOV-16:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1048.44 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1046.64 | 0.00 | 417.71 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8680.32 | 1339.19 | 1545.24 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1287.90 | 21-JAN-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
February | 1289.23 | 11-FEB-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
March | 1990.14 | 31-MAR-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.53 |
April | 3855.12 | 22-APR-08:30 | 254.35 | 195.65 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.18 |
May | 12388.47 | 14-MAY-09:41 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.05 |
June | 9551.62 | 13-JUN-06:03 | 678.26 | 782.61 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
July | 11462.30 | 09-JUL-06:32 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 |
August | 9443.90 | 11-AUG-06:02 | 847.82 | 978.27 | 2118.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 |
September | 4808.41 | 10-SEP-10:04 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.12 |
October | 2179.35 | 03-OCT-09:35 | 1654.44 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.51 |
November | 1298.68 | 04-NOV-16:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1289.11 | 23-DEC-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1287.90 | 211.95 | 163.03 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12388.47 | 1654.44 | 1173.93 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2035.39 | 21-JAN-17:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
February | 2291.91 | 18-FEB-13:30 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.41 |
March | 2788.23 | 11-MAR-13:40 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.02 |
April | 8017.81 | 22-APR-14:00 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 |
May | 17219.39 | 14-MAY-13:02 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.78 |
June | 10407.85 | 30-JUN-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1952.57 | 0.00 |
July | 19298.65 | 23-JUL-14:02 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 |
August | 15182.73 | 27-AUG-13:42 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.41 |
September | 8782.93 | 09-SEP-14:10 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 |
October | 5079.06 | 03-OCT-13:50 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2391.68 |
November | 2056.16 | 04-NOV-16:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2021.19 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2021.19 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19298.65 | 1306.65 | 927.16 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1952.57 | 2391.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1369.39 | 21-JAN-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
February | 1368.85 | 11-FEB-17:02 | 211.94 | 264.43 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.71 |
March | 1716.55 | 31-MAR-17:00 | 254.33 | 326.07 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.86 |
April | 5415.61 | 21-APR-18:20 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 7325.46 | 14-MAY-18:52 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.36 |
June | 6153.08 | 21-JUN-17:00 | 254.33 | 326.07 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
July | 6933.61 | 31-JUL-18:30 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
August | 6471.56 | 10-AUG-18:20 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
September | 3269.85 | 08-SEP-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 |
October | 1904.53 | 03-OCT-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.59 |
November | 1383.42 | 04-NOV-16:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1371.56 | 23-DEC-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1368.85 | 0.00 | 163.02 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7325.46 | 805.38 | 586.93 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 184.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1166.65 | 21-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
February | 1174.02 | 11-FEB-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 |
March | 1516.62 | 22-MAR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2567.85 | 28-APR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
May | 9448.12 | 31-MAY-05:02 | 669.60 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
June | 10090.57 | 07-JUN-04:02 | 0.00 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.08 |
July | 9804.93 | 11-JUL-04:02 | 0.00 | 515.10 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.06 |
August | 6540.07 | 11-AUG-06:02 | 1339.19 | 1545.24 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.38 |
September | 2720.26 | 01-SEP-15:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 |
October | 1607.87 | 04-OCT-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.01 |
November | 1165.34 | 04-NOV-16:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1164.45 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1164.45 | 0.00 | 417.71 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10090.57 | 1339.19 | 1545.24 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1563.08 | 21-JAN-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
February | 1570.47 | 11-FEB-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.28 |
March | 2739.24 | 31-MAR-10:20 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.24 |
April | 6390.61 | 22-APR-09:20 | 0.00 | 195.65 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.51 |
May | 13957.05 | 14-MAY-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.54 |
June | 11564.53 | 13-JUN-06:03 | 678.26 | 782.61 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 |
July | 14853.41 | 23-JUL-10:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 |
August | 10065.70 | 10-AUG-08:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 |
September | 10039.78 | 10-SEP-10:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.42 |
October | 2593.63 | 03-OCT-10:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 |
November | 1561.40 | 04-NOV-16:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1559.44 | 23-DEC-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1559.44 | 0.00 | 163.03 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14853.41 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2751.57 | 25-JAN-13:40 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.26 |
February | 5047.83 | 15-FEB-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9318.49 | 31-MAR-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.91 |
April | 13696.07 | 20-APR-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 |
May | 19305.13 | 14-MAY-12:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.28 |
June | 13189.39 | 29-JUN-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
July | 23323.87 | 23-JUL-13:22 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 |
August | 22086.06 | 27-AUG-13:02 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.51 |
September | 11001.80 | 09-SEP-13:30 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 |
October | 10164.19 | 03-OCT-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.96 |
November | 3660.38 | 08-NOV-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.80 |
December | 2378.01 | 23-DEC-17:02 | 401.76 | 501.26 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2378.01 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23323.87 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 261.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1562.16 | 21-JAN-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
February | 1569.10 | 11-FEB-17:02 | 211.94 | 264.43 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.27 |
March | 2250.03 | 31-MAR-17:00 | 254.33 | 326.07 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 |
April | 7562.29 | 22-APR-17:10 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.26 |
May | 8562.84 | 29-MAY-18:23 | 0.00 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.34 |
June | 12542.48 | 10-JUN-17:42 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 |
July | 8444.05 | 11-JUL-17:40 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
August | 9020.51 | 27-AUG-17:03 | 0.00 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.36 |
September | 4934.11 | 02-SEP-17:16 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.12 |
October | 2241.93 | 03-OCT-15:10 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.02 |
November | 1563.39 | 04-NOV-16:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1559.11 | 23-DEC-17:02 | 254.33 | 317.32 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1559.11 | 0.00 | 130.42 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12542.48 | 805.38 | 586.93 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 474.26 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.278826E+12 | 289219.99 | 02-JAN-08:09 | 0.950926E+11 | 281859.73 | 12-JAN-08:09 |
February | 0.217641E+12 | 281450.02 | 27-FEB-07:10 | 0.609380E+11 | 262456.36 | 27-FEB-07:19 |
March | 0.195523E+12 | 246208.69 | 06-MAR-07:10 | 0.296820E+11 | 228648.91 | 01-MAR-07:30 |
April | 0.128763E+12 | 213346.31 | 03-APR-06:10 | 0.118170E+11 | 43209.20 | 03-APR-06:30 |
May | 0.118398E+12 | 122323.04 | 31-MAY-15:00 | 0.111494E+11 | 16085.01 | 18-MAY-06:10 |
June | 0.130325E+12 | 153655.61 | 30-JUN-12:30 | 0.106376E+11 | 12666.15 | 02-JUN-11:00 |
July | 0.133396E+12 | 153338.26 | 11-JUL-15:00 | 0.101278E+11 | 11583.29 | 05-JUL-11:50 |
August | 0.131212E+12 | 148120.78 | 11-AUG-15:50 | 0.106684E+11 | 12799.69 | 31-AUG-08:39 |
September | 0.119612E+12 | 134036.83 | 25-SEP-06:10 | 0.998315E+10 | 12761.56 | 05-SEP-06:10 |
October | 0.172541E+12 | 235691.02 | 30-OCT-06:10 | 0.150776E+11 | 38154.43 | 31-OCT-06:49 |
November | 0.244555E+12 | 272367.53 | 27-NOV-07:10 | 0.859927E+11 | 233964.00 | 29-NOV-09:50 |
December | 0.279086E+12 | 268494.06 | 04-DEC-07:10 | 0.123833E+12 | 257388.42 | 15-DEC-07:00 |
Annual Sum or Average | 0.214988E+13 | 0.475000E+12 | ||||
Minimum of Months | 0.118398E+12 | 122323.04 | 0.998315E+10 | 11583.29 | ||
Maximum of Months | 0.279086E+12 | 289219.99 | 0.123833E+12 | 281859.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.334777E+11 | 0.163196E+11 | 0.641572E+11 | 0.159636E+10 | 0.842310E+10 | 1312252.65 | 0.151355E+12 | 1385629.19 | 0.00 | 0.00 | 0.349402E+10 | 0.00 | 0.00 |
February | 0.288240E+11 | 0.119156E+11 | 0.580684E+11 | 0.144172E+10 | 0.721789E+10 | 1186778.30 | 0.106966E+12 | 3754264.61 | 0.00 | 0.00 | 0.320204E+10 | 0.00 | 0.00 |
March | 0.326902E+11 | 0.999409E+10 | 0.666107E+11 | 0.166732E+10 | 0.700932E+10 | 1343621.24 | 0.737506E+11 | 13245644.31 | 0.00 | 0.00 | 0.378600E+10 | 0.00 | 0.00 |
April | 0.285633E+11 | 0.655997E+10 | 0.619407E+11 | 0.153120E+10 | 0.683556E+10 | 1267813.82 | 0.208357E+11 | 46394384.89 | 0.00 | 0.00 | 0.244866E+10 | 0.00 | 0.00 |
May | 0.306278E+11 | 0.400957E+10 | 0.653840E+11 | 0.162805E+10 | 0.106173E+11 | 1327936.95 | 0.226532E+10 | 0.334861E+10 | 0.00 | 0.00 | 0.516460E+09 | 0.00 | 0.00 |
June | 0.303526E+11 | 0.204061E+10 | 0.641577E+11 | 0.160294E+10 | 0.153512E+11 | 1296568.36 | 0.620228E+09 | 0.160098E+11 | 0.00 | 0.00 | 0.188561E+09 | 0.00 | 0.00 |
July | 0.284881E+11 | 0.294350E+10 | 0.631525E+11 | 0.155578E+10 | 0.150277E+11 | 1299182.41 | 0.496782E+09 | 0.214315E+11 | 0.00 | 0.00 | 0.299090E+09 | 0.00 | 0.00 |
August | 0.319193E+11 | 0.552874E+10 | 0.666107E+11 | 0.166653E+10 | 0.125223E+11 | 1343621.24 | 0.129762E+10 | 0.114026E+11 | 0.00 | 0.00 | 0.262697E+09 | 0.00 | 0.00 |
September | 0.289378E+11 | 0.832793E+10 | 0.619118E+11 | 0.153089E+10 | 0.662561E+10 | 1267813.82 | 0.101754E+11 | 0.212452E+09 | 0.00 | 0.00 | 0.188861E+10 | 0.00 | 0.00 |
October | 0.310546E+11 | 0.118130E+11 | 0.641717E+11 | 0.159192E+10 | 0.617516E+10 | 1312252.65 | 0.544242E+11 | 17273558.32 | 0.00 | 0.00 | 0.329169E+10 | 0.00 | 0.00 |
November | 0.323713E+11 | 0.146077E+11 | 0.627379E+11 | 0.156594E+10 | 0.742601E+10 | 1278270.02 | 0.122457E+12 | 1047793.98 | 0.00 | 0.00 | 0.338696E+10 | 0.00 | 0.00 |
December | 0.330348E+11 | 0.176101E+11 | 0.631380E+11 | 0.156315E+10 | 0.840324E+10 | 1299182.41 | 0.151879E+12 | 430966.22 | 0.00 | 0.00 | 0.345509E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.370341E+12 | 0.111670E+12 | 0.762041E+12 | 0.189418E+11 | 0.111634E+12 | 15535293.87 | 0.696524E+12 | 0.524885E+11 | 0.00 | 0.00 | 0.262199E+11 | 0.00 | 0.00 |
Minimum of Months | 0.284881E+11 | 0.204061E+10 | 0.580684E+11 | 0.144172E+10 | 0.617516E+10 | 1186778.30 | 0.496782E+09 | 430966.22 | 0.00 | 0.00 | 0.188561E+09 | 0.00 | 0.00 |
Maximum of Months | 0.334777E+11 | 0.176101E+11 | 0.666107E+11 | 0.166732E+10 | 0.153512E+11 | 1343621.24 | 0.151879E+12 | 0.214315E+11 | 0.00 | 0.00 | 0.378600E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.841414E+11 | 0.00 | 0.109512E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.510206E+11 | 0.00 | 0.991740E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182480E+11 | 0.00 | 0.114341E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.128922E+10 | 0.00 | 0.105278E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 78955327.02 | 0.00 | 0.110705E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7983028.86 | 0.00 | 0.106296E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 7468548.67 | 0.00 | 0.101203E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 58585664.36 | 0.00 | 0.106098E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.175720E+09 | 0.00 | 0.980743E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.479462E+10 | 0.00 | 0.102830E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.756783E+11 | 0.00 | 0.103145E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.113177E+12 | 0.00 | 0.106566E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.348677E+12 | 0.00 | 0.126322E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 7468548.67 | 0.00 | 0.980743E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.113177E+12 | 0.00 | 0.114341E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36137.71 | 02-JAN-08:09 | 8467.87 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 1360.76 | 02-JAN-08:20 | 8344.64 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 234755.32 | 02-JAN-06:19 |
February | 36137.71 | 01-FEB-08:09 | 8467.87 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 1360.76 | 01-FEB-08:20 | 8043.47 | 27-FEB-07:10 | 0.73 | 01-FEB-07:10 | 227964.09 | 27-FEB-07:10 |
March | 36137.71 | 01-MAR-08:09 | 8467.87 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 1360.76 | 01-MAR-08:20 | 6420.88 | 06-MAR-06:10 | 0.73 | 01-MAR-06:10 | 194359.21 | 06-MAR-07:10 |
April | 30867.00 | 03-APR-07:10 | 8467.87 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 1349.69 | 03-APR-07:19 | 12765.69 | 21-APR-15:00 | 0.73 | 03-APR-06:10 | 162261.77 | 03-APR-06:10 |
May | 30486.53 | 01-MAY-07:10 | 8467.87 | 01-MAY-21:10 | 47562.27 | 01-MAY-07:10 | 1348.89 | 01-MAY-07:19 | 20756.34 | 31-MAY-15:09 | 0.73 | 01-MAY-05:10 | 27419.78 | 03-MAY-06:10 |
June | 30486.53 | 01-JUN-07:10 | 8467.87 | 01-JUN-22:49 | 47562.27 | 01-JUN-07:10 | 1348.89 | 01-JUN-07:19 | 26375.33 | 20-JUN-15:30 | 0.73 | 01-JUN-05:10 | 16718.44 | 02-JUN-06:19 |
July | 30486.53 | 03-JUL-07:10 | 8467.87 | 11-JUL-22:00 | 47562.27 | 03-JUL-07:10 | 1348.89 | 03-JUL-07:19 | 28869.60 | 12-JUL-15:09 | 0.73 | 01-JUL-05:10 | 14621.71 | 05-JUL-06:19 |
August | 30486.53 | 01-AUG-07:10 | 8467.87 | 01-AUG-21:00 | 47562.27 | 01-AUG-07:10 | 1348.89 | 01-AUG-07:30 | 26202.71 | 11-AUG-15:50 | 0.73 | 30-AUG-07:10 | 37018.69 | 30-AUG-06:10 |
September | 35202.13 | 28-SEP-07:10 | 8467.87 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 1358.79 | 28-SEP-07:19 | 9844.41 | 08-SEP-15:30 | 0.73 | 15-SEP-07:10 | 83651.91 | 25-SEP-06:10 |
October | 36137.71 | 03-OCT-07:10 | 8467.87 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 1360.76 | 23-OCT-07:19 | 6204.24 | 30-OCT-05:10 | 0.73 | 03-OCT-07:10 | 184183.13 | 30-OCT-06:10 |
November | 36137.71 | 01-NOV-07:10 | 8467.87 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 1360.76 | 01-NOV-07:19 | 7752.86 | 27-NOV-06:10 | 0.73 | 01-NOV-06:10 | 219402.78 | 27-NOV-06:10 |
December | 36137.71 | 01-DEC-08:09 | 8467.87 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 1360.76 | 01-DEC-08:20 | 7266.08 | 04-DEC-07:10 | 0.73 | 01-DEC-07:10 | 215785.52 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30486.53 | 8467.87 | 47562.27 | 1348.89 | 6204.24 | 0.73 | 14621.71 | |||||||
Maximum of Months | 36137.71 | 8467.87 | 47562.27 | 1360.76 | 28869.60 | 0.73 | 234755.32 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 337.88 | 07-JAN-07:10 | 0.00 | 0.00 | 2703.51 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 463.95 | 11-FEB-07:10 | 0.00 | 0.00 | 2703.51 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 552.39 | 23-MAR-07:49 | 0.00 | 0.00 | 2703.51 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 1845.89 | 22-APR-13:00 | 0.00 | 0.00 | 2703.51 | 01-APR-06:10 | 0.00 | 0.00 |
May | 27093.59 | 31-MAY-15:00 | 0.00 | 0.00 | 2703.51 | 01-MAY-19:40 | 0.00 | 0.00 |
June | 49715.30 | 30-JUN-14:30 | 0.00 | 0.00 | 2703.51 | 20-JUN-15:50 | 0.00 | 0.00 |
July | 48080.91 | 21-JUL-15:09 | 0.00 | 0.00 | 2703.51 | 11-JUL-12:50 | 0.00 | 0.00 |
August | 43627.96 | 11-AUG-15:00 | 0.00 | 0.00 | 2703.51 | 11-AUG-15:50 | 0.00 | 0.00 |
September | 7222.51 | 07-SEP-15:00 | 0.00 | 0.00 | 2703.51 | 02-SEP-06:19 | 0.00 | 0.00 |
October | 688.64 | 05-OCT-07:19 | 0.00 | 0.00 | 2703.51 | 02-OCT-06:10 | 0.00 | 0.00 |
November | 327.92 | 04-NOV-06:10 | 0.00 | 0.00 | 2703.51 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 413.78 | 23-DEC-07:10 | 0.00 | 0.00 | 2703.51 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 327.92 | 0.00 | 0.00 | 2703.51 | 0.00 | 0.00 | ||
Maximum of Months | 49715.30 | 0.00 | 0.00 | 2703.51 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 289219.99 | 02-JAN-08:09 | 36137.71 | 47562.27 | 8467.87 | 1310.73 | 5279.49 | 0.73 | 187757.69 | 0.00 | 0.00 |
February | 281450.02 | 27-FEB-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 8043.47 | 0.73 | 227964.09 | 0.00 | 0.00 |
March | 246208.69 | 06-MAR-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 6407.02 | 0.73 | 194359.21 | 0.00 | 0.00 |
April | 213346.31 | 03-APR-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 5642.08 | 0.73 | 162261.77 | 0.00 | 0.00 |
May | 122323.04 | 31-MAY-15:00 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 19625.46 | 0.73 | 0.00 | 27093.59 | 0.00 |
June | 153655.61 | 30-JUN-12:30 | 30486.53 | 44099.74 | 0.00 | 1346.94 | 25392.26 | 0.73 | 0.00 | 49625.90 | 0.00 |
July | 153338.26 | 11-JUL-15:00 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 27569.34 | 0.73 | 0.00 | 47461.42 | 0.00 |
August | 148120.78 | 11-AUG-15:50 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 26202.71 | 0.73 | 0.00 | 43610.57 | 0.00 |
September | 134036.83 | 25-SEP-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4627.44 | 0.73 | 83651.91 | 315.02 | 0.00 |
October | 235691.02 | 30-OCT-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 6065.43 | 0.73 | 184183.13 | 0.00 | 0.00 |
November | 272367.53 | 27-NOV-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7533.02 | 0.73 | 219392.04 | 0.00 | 0.00 |
December | 268494.06 | 04-DEC-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7266.08 | 0.73 | 215785.52 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 122323.04 | 12045.75 | 21853.28 | 0.00 | 371.32 | 4627.44 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 289219.99 | 36137.71 | 47562.27 | 8467.87 | 1346.94 | 27569.34 | 0.73 | 227964.09 | 49625.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 273471.97 | 12-JAN-07:40 | 0.00 | 13384.83 | 02-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 254650.99 | 27-FEB-07:30 | 0.00 | 13401.28 | 27-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 220686.16 | 01-MAR-07:19 | 0.00 | 13373.24 | 06-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 34944.62 | 03-APR-06:19 | 0.00 | 13333.71 | 21-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 14929.01 | 18-MAY-06:10 | 0.00 | 13323.67 | 03-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 9303.87 | 02-JUN-06:10 | 0.00 | 12666.15 | 02-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 2500.26 | 05-JUL-07:30 | 0.00 | 11583.29 | 05-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 3965.68 | 31-AUG-08:39 | 0.00 | 10890.43 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 6988.34 | 28-SEP-17:10 | 0.00 | 10702.51 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 30274.42 | 31-OCT-06:00 | 0.00 | 11448.71 | 30-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 225516.20 | 29-NOV-09:00 | 0.00 | 12430.72 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 249121.64 | 15-DEC-07:00 | 0.00 | 13356.48 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 2500.26 | 0.00 | 10702.51 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 273471.97 | 0.00 | 13401.28 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.89 | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.89 | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.89 | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 18.82 | 2.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
February | 0.50 | 19.23 | 0.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 17.94 | 0.33 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 0.67 | 19.22 | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 4.83 | 18.80 | 3.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.23 | 2.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 18.65 | 4.33 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 4.00 | 18.57 | 2.67 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
March | 1.00 | 18.56 | 0.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 0.33 | 17.96 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 17.61 | 0.33 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
November | 5.17 | 18.36 | 3.17 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
December | 6.00 | 18.68 | 4.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Annual Sum or Average | 23.33 | 18.53 | 15.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 18.68 | 4.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.17 | 16.28 | 49.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
February | 73.50 | 16.26 | 37.67 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
March | 40.50 | 17.05 | 19.00 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
April | 8.17 | 16.42 | 3.83 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.35 | 0.00 | 26.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21.67 | 16.23 | 10.33 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
November | 81.33 | 16.34 | 44.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
December | 99.50 | 16.51 | 51.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 417.83 | 16.42 | 215.17 | 16.88 | 0.17 | 16.88 | 0.00 | 16.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.50 | 17.05 | 51.17 | 17.69 | 0.17 | 26.35 | 0.00 | 26.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.17 | 14.53 | 16.67 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
February | 43.67 | 14.68 | 10.83 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
March | 20.67 | 15.16 | 1.67 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
April | 4.33 | 15.17 | 0.33 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.11 | 2.33 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.70 | 0.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.05 | 2.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14.50 | 15.15 | 3.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
November | 54.67 | 14.80 | 18.00 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
December | 65.00 | 14.77 | 17.33 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
Annual Sum or Average | 262.00 | 14.77 | 67.83 | 14.76 | 5.17 | 14.96 | 5.17 | 15.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.00 | 15.17 | 18.00 | 15.21 | 2.50 | 28.11 | 2.50 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.50 | 14.59 | 15.67 | 14.56 | 0.00 | 14.56 | 0.00 | 14.56 |
February | 33.83 | 14.78 | 5.33 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
March | 13.00 | 15.49 | 1.00 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
April | 2.67 | 15.38 | 0.67 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.02 | 2.00 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.50 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.25 | 2.50 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.35 | 1.33 | 28.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11.50 | 15.26 | 2.33 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
November | 45.17 | 14.89 | 12.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 60.17 | 14.83 | 16.33 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
Annual Sum or Average | 220.83 | 14.84 | 53.67 | 14.83 | 7.33 | 15.18 | 7.33 | 15.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.17 | 15.49 | 16.33 | 15.55 | 2.50 | 28.35 | 2.50 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.50 | 14.52 | 17.17 | 14.48 | 0.00 | 14.48 | 0.00 | 14.48 |
February | 46.17 | 14.65 | 13.00 | 14.63 | 0.00 | 14.63 | 0.00 | 14.63 |
March | 20.67 | 15.17 | 2.67 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
April | 3.33 | 15.30 | 1.00 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.63 | 0.17 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.84 | 0.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.47 | 0.50 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.02 | 0.17 | 28.00 |
September | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
October | 16.00 | 15.12 | 4.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
November | 53.50 | 14.78 | 17.83 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
December | 65.00 | 14.77 | 17.67 | 14.78 | 0.00 | 14.78 | 0.00 | 14.78 |
Annual Sum or Average | 264.33 | 14.76 | 73.33 | 14.74 | 5.50 | 14.95 | 1.67 | 15.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 | 14.48 |
Maximum of Months | 65.00 | 17.24 | 17.83 | 17.24 | 2.50 | 28.02 | 0.83 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.33 | 17.80 | 62.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
February | 65.67 | 18.02 | 48.33 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
March | 18.83 | 18.99 | 15.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
April | 2.33 | 18.77 | 1.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.43 | 0.00 | 26.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.33 | 18.56 | 0.83 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
November | 23.50 | 18.42 | 16.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
December | 40.83 | 18.42 | 29.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Annual Sum or Average | 236.83 | 18.14 | 173.83 | 18.54 | 0.33 | 18.54 | 0.00 | 18.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.33 | 18.99 | 62.00 | 19.27 | 0.17 | 26.43 | 0.00 | 26.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 14.98 | 12.67 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 19.17 | 15.33 | 4.50 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
March | 3.50 | 16.76 | 0.33 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
April | 0.33 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.48 | 1.83 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.61 | 2.17 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
November | 9.00 | 15.76 | 0.83 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
December | 14.50 | 15.54 | 3.17 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 82.17 | 15.34 | 21.50 | 15.34 | 4.33 | 15.83 | 4.17 | 16.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.17 | 17.00 | 12.67 | 17.00 | 2.33 | 27.61 | 2.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.67 | 15.11 | 197.83 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
February | 129.50 | 14.94 | 116.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 99.83 | 15.20 | 96.83 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
April | 36.33 | 17.03 | 36.33 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
May | 10.83 | 19.78 | 10.83 | 19.78 | 0.17 | 19.84 | 0.17 | 19.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.04 | 1.33 | 28.04 |
August | 3.00 | 18.64 | 3.00 | 18.64 | 1.33 | 20.34 | 1.33 | 21.52 |
September | 28.33 | 18.83 | 28.33 | 18.83 | 0.17 | 18.86 | 0.17 | 18.88 |
October | 63.67 | 16.01 | 63.33 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
November | 160.17 | 15.02 | 153.50 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
December | 245.67 | 15.61 | 226.83 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
Annual Sum or Average | 1002.00 | 15.50 | 932.83 | 15.50 | 3.00 | 15.52 | 3.00 | 15.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 245.67 | 19.78 | 226.83 | 19.78 | 1.33 | 28.04 | 1.33 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.00 | 14.98 | 12.67 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 22.00 | 15.19 | 5.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 3.17 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
April | 0.33 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.00 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 8.17 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
December | 14.67 | 15.48 | 3.00 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
Annual Sum or Average | 83.83 | 15.26 | 20.83 | 15.22 | 0.33 | 15.26 | 0.00 | 15.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.00 | 16.95 | 12.67 | 16.95 | 0.33 | 27.39 | 0.00 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.67 | 16.31 | 27.83 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
February | 30.17 | 16.57 | 16.50 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 6.67 | 18.33 | 3.83 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
April | 1.00 | 17.93 | 0.50 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.54 | 0.00 | 26.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.46 | 0.00 | 26.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.50 | 17.75 | 1.17 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
November | 22.83 | 17.04 | 13.33 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
December | 33.17 | 16.93 | 17.50 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Annual Sum or Average | 148.00 | 16.74 | 80.67 | 17.15 | 2.33 | 17.24 | 0.00 | 17.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.67 | 18.33 | 27.83 | 18.79 | 1.83 | 26.54 | 0.00 | 26.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.83 | 14.85 | 12.50 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
February | 17.33 | 15.08 | 3.67 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
March | 2.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
April | 0.33 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.26 | 2.50 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.93 | 2.83 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
October | 1.67 | 16.44 | 0.17 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
November | 14.67 | 15.28 | 4.17 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
December | 23.17 | 15.19 | 6.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
Annual Sum or Average | 96.83 | 15.12 | 26.50 | 15.07 | 7.00 | 15.76 | 6.83 | 16.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 | 14.81 |
Maximum of Months | 36.83 | 16.49 | 12.50 | 16.72 | 3.00 | 28.26 | 2.83 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 14.94 | 9.50 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
February | 10.50 | 15.22 | 2.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
March | 2.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
April | 0.33 | 16.31 | 0.00 | 16.31 | 0.50 | 22.92 | 0.50 | 24.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.01 | 2.17 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.66 | 1.83 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.12 | 2.67 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.17 | 1.67 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
October | 0.83 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
November | 9.83 | 15.55 | 1.50 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
December | 19.67 | 15.34 | 5.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
Annual Sum or Average | 74.17 | 15.25 | 18.00 | 15.19 | 9.00 | 16.33 | 9.00 | 17.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 | 0.00 | 14.90 |
Maximum of Months | 31.00 | 16.84 | 9.50 | 16.84 | 2.67 | 28.17 | 2.67 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.83 | 14.85 | 12.50 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
February | 18.17 | 15.03 | 4.17 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
March | 3.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
April | 0.33 | 16.10 | 0.00 | 16.10 | 0.33 | 21.72 | 0.17 | 22.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.54 | 0.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 0.67 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.93 | 0.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 16.43 | 0.17 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
November | 14.67 | 15.29 | 4.17 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
December | 23.33 | 15.22 | 6.17 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 98.00 | 15.12 | 27.17 | 15.07 | 6.50 | 15.69 | 1.83 | 15.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.83 | 16.55 | 12.50 | 16.71 | 2.67 | 27.93 | 0.67 | 27.94 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.20 | 301.17 | 20.96 | 301.17 | 20.85 |
February | 454.00 | 21.76 | 169.33 | 21.47 | 169.33 | 21.31 |
March | 514.00 | 22.67 | 50.50 | 22.53 | 50.50 | 22.41 |
April | 436.50 | 23.59 | 2.00 | 23.58 | 2.00 | 23.57 |
May | 120.17 | 23.98 | 31.00 | 24.40 | 0.00 | 24.40 |
June | 0.00 | 0.00 | 213.17 | 24.87 | 0.00 | 24.87 |
July | 0.00 | 0.00 | 390.67 | 24.59 | 0.00 | 24.59 |
August | 16.00 | 23.94 | 278.00 | 24.62 | 0.00 | 24.62 |
September | 188.00 | 23.80 | 48.67 | 24.22 | 0.00 | 24.22 |
October | 497.67 | 23.25 | 5.83 | 23.22 | 5.83 | 23.20 |
November | 489.00 | 21.82 | 173.83 | 21.58 | 173.83 | 21.44 |
December | 497.00 | 21.27 | 334.33 | 21.09 | 334.33 | 21.02 |
Annual Sum or Average | 3714.33 | 22.35 | 1998.50 | 22.47 | 1037.00 | 22.21 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 20.96 | 0.00 | 20.85 |
Maximum of Months | 514.00 | 23.98 | 390.67 | 24.87 | 334.33 | 24.87 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.44 | 464.67 | 20.40 | 464.67 | 20.39 |
February | 454.00 | 20.77 | 333.17 | 20.63 | 333.17 | 20.58 |
March | 514.00 | 21.41 | 238.83 | 21.21 | 238.83 | 21.11 |
April | 480.00 | 22.76 | 52.17 | 22.58 | 52.17 | 22.43 |
May | 316.67 | 23.73 | 2.33 | 23.75 | 0.00 | 23.75 |
June | 21.67 | 23.82 | 132.83 | 24.62 | 0.00 | 24.62 |
July | 0.17 | 23.71 | 283.17 | 24.52 | 0.00 | 24.52 |
August | 77.50 | 23.68 | 156.33 | 24.31 | 0.00 | 24.31 |
September | 394.67 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
October | 502.00 | 21.70 | 127.67 | 21.49 | 127.67 | 21.35 |
November | 489.00 | 20.69 | 420.67 | 20.62 | 420.67 | 20.59 |
December | 497.00 | 20.48 | 486.17 | 20.47 | 486.17 | 20.47 |
Annual Sum or Average | 4248.67 | 21.61 | 2698.00 | 21.52 | 2123.33 | 21.29 |
Minimum of Months | 0.17 | 20.44 | 0.00 | 20.40 | 0.00 | 20.39 |
Maximum of Months | 514.00 | 23.82 | 486.17 | 24.62 | 486.17 | 24.62 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 502.00 | 20.08 | 502.00 | 20.08 |
February | 454.00 | 20.25 | 414.17 | 20.20 | 414.17 | 20.18 |
March | 514.00 | 20.80 | 383.67 | 20.66 | 383.67 | 20.61 |
April | 485.00 | 22.05 | 141.00 | 21.68 | 141.00 | 21.45 |
May | 381.83 | 23.44 | 1.17 | 23.44 | 0.33 | 23.44 |
June | 77.83 | 23.70 | 98.00 | 24.20 | 0.00 | 24.20 |
July | 24.00 | 23.42 | 239.33 | 24.36 | 0.00 | 24.36 |
August | 151.50 | 23.30 | 98.00 | 23.77 | 0.00 | 23.77 |
September | 472.67 | 22.50 | 32.33 | 22.38 | 32.33 | 22.28 |
October | 502.00 | 20.86 | 310.00 | 20.66 | 310.00 | 20.57 |
November | 489.00 | 20.14 | 487.50 | 20.14 | 487.50 | 20.13 |
December | 497.00 | 20.07 | 497.00 | 20.07 | 497.00 | 20.07 |
Annual Sum or Average | 4550.83 | 21.20 | 3204.17 | 21.03 | 2768.00 | 20.81 |
Minimum of Months | 24.00 | 20.07 | 1.17 | 20.07 | 0.00 | 20.07 |
Maximum of Months | 514.00 | 23.70 | 502.00 | 24.36 | 502.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.62 | 502.00 | 19.62 | 502.00 | 19.62 |
February | 454.00 | 19.73 | 454.00 | 19.73 | 454.00 | 19.73 |
March | 514.00 | 20.09 | 501.33 | 20.08 | 501.33 | 20.07 |
April | 485.00 | 20.97 | 267.50 | 20.66 | 267.50 | 20.51 |
May | 406.50 | 22.93 | 10.83 | 22.87 | 10.83 | 22.81 |
June | 63.83 | 23.26 | 170.67 | 24.09 | 0.00 | 24.09 |
July | 47.33 | 23.29 | 315.83 | 24.21 | 0.00 | 24.21 |
August | 239.00 | 22.77 | 98.50 | 23.15 | 5.83 | 23.11 |
September | 482.33 | 21.42 | 145.17 | 21.20 | 145.17 | 21.06 |
October | 502.00 | 20.09 | 449.83 | 20.04 | 449.83 | 20.01 |
November | 489.00 | 19.66 | 489.00 | 19.66 | 489.00 | 19.66 |
December | 497.00 | 19.59 | 497.00 | 19.59 | 497.00 | 19.59 |
Annual Sum or Average | 4682.00 | 20.59 | 3901.67 | 20.55 | 3322.50 | 20.35 |
Minimum of Months | 47.33 | 19.59 | 10.83 | 19.59 | 0.00 | 19.59 |
Maximum of Months | 514.00 | 23.29 | 502.00 | 24.21 | 502.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.83 | 452.83 | 19.83 | 452.83 | 19.82 |
March | 514.00 | 20.33 | 441.67 | 20.24 | 441.67 | 20.20 |
April | 444.50 | 21.28 | 202.67 | 20.98 | 195.50 | 20.79 |
May | 261.67 | 22.66 | 110.33 | 23.13 | 13.17 | 23.16 |
June | 106.67 | 22.99 | 263.00 | 23.90 | 1.83 | 23.91 |
July | 89.67 | 23.24 | 339.50 | 24.16 | 11.33 | 24.23 |
August | 212.67 | 22.49 | 184.17 | 23.29 | 2.50 | 23.27 |
September | 441.83 | 21.40 | 113.83 | 21.29 | 103.00 | 21.14 |
October | 502.00 | 20.20 | 415.50 | 20.10 | 415.50 | 20.07 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4515.00 | 20.61 | 4011.50 | 20.74 | 3125.33 | 20.52 |
Minimum of Months | 89.67 | 19.67 | 110.33 | 19.67 | 1.83 | 19.67 |
Maximum of Months | 514.00 | 23.24 | 502.00 | 24.16 | 502.00 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 20.05 | 418.83 | 19.98 | 418.83 | 19.95 |
March | 481.50 | 20.64 | 356.67 | 20.42 | 356.67 | 20.33 |
April | 358.83 | 21.27 | 223.17 | 21.30 | 164.17 | 21.06 |
May | 299.67 | 22.26 | 131.00 | 22.76 | 23.33 | 22.71 |
June | 172.00 | 22.73 | 222.67 | 23.62 | 5.00 | 23.66 |
July | 152.83 | 22.80 | 287.67 | 23.86 | 9.67 | 23.92 |
August | 250.50 | 22.41 | 210.17 | 23.27 | 10.83 | 23.28 |
September | 391.67 | 21.42 | 152.17 | 21.56 | 97.50 | 21.39 |
October | 487.17 | 20.39 | 379.67 | 20.26 | 376.00 | 20.20 |
November | 489.00 | 19.79 | 484.50 | 19.78 | 484.50 | 19.77 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4536.17 | 20.73 | 3865.50 | 20.85 | 2945.50 | 20.62 |
Minimum of Months | 152.83 | 19.68 | 131.00 | 19.68 | 5.00 | 19.68 |
Maximum of Months | 502.00 | 22.80 | 502.00 | 23.86 | 502.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.82 | 452.17 | 19.81 | 452.17 | 19.81 |
March | 514.00 | 20.21 | 474.83 | 20.16 | 474.83 | 20.14 |
April | 428.50 | 20.97 | 239.33 | 20.77 | 222.17 | 20.61 |
May | 384.83 | 22.16 | 65.17 | 22.30 | 21.83 | 22.21 |
June | 192.83 | 22.70 | 186.83 | 23.55 | 3.00 | 23.58 |
July | 176.17 | 22.60 | 243.17 | 23.63 | 1.67 | 23.64 |
August | 319.33 | 22.25 | 130.83 | 22.80 | 7.83 | 22.78 |
September | 461.83 | 21.22 | 144.33 | 21.09 | 137.00 | 20.98 |
October | 502.00 | 20.11 | 439.83 | 20.05 | 439.83 | 20.03 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.67 | 497.00 | 19.67 | 497.00 | 19.67 |
Annual Sum or Average | 4921.50 | 20.64 | 3864.50 | 20.62 | 3248.33 | 20.43 |
Minimum of Months | 176.17 | 19.67 | 65.17 | 19.67 | 1.67 | 19.67 |
Maximum of Months | 514.00 | 22.70 | 502.00 | 23.63 | 502.00 | 23.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 502.00 | 19.67 | 502.00 | 19.67 |
February | 454.00 | 19.76 | 454.00 | 19.76 | 454.00 | 19.76 |
March | 514.00 | 20.22 | 510.33 | 20.22 | 510.33 | 20.22 |
April | 485.00 | 20.95 | 288.83 | 20.74 | 288.83 | 20.65 |
May | 501.33 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
June | 81.00 | 23.67 | 96.00 | 24.10 | 0.00 | 24.10 |
July | 16.00 | 23.50 | 280.17 | 24.38 | 0.00 | 24.38 |
August | 167.17 | 23.29 | 84.67 | 23.68 | 0.00 | 23.68 |
September | 481.83 | 22.26 | 48.33 | 22.13 | 48.33 | 22.01 |
October | 502.00 | 20.62 | 390.33 | 20.52 | 390.33 | 20.48 |
November | 489.00 | 19.87 | 489.00 | 19.87 | 489.00 | 19.87 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4690.33 | 20.85 | 3640.67 | 20.72 | 3179.83 | 20.51 |
Minimum of Months | 16.00 | 19.67 | 0.00 | 19.67 | 0.00 | 19.67 |
Maximum of Months | 514.00 | 23.67 | 510.33 | 24.38 | 510.33 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.80 | 502.00 | 19.80 | 502.00 | 19.80 |
February | 454.00 | 19.93 | 454.00 | 19.93 | 454.00 | 19.93 |
March | 514.00 | 20.50 | 464.17 | 20.44 | 464.17 | 20.42 |
April | 461.17 | 21.59 | 180.67 | 21.32 | 177.17 | 21.14 |
May | 242.33 | 23.06 | 80.33 | 23.46 | 1.33 | 23.48 |
June | 88.33 | 23.15 | 252.17 | 24.07 | 0.00 | 24.07 |
July | 47.33 | 23.64 | 391.17 | 24.39 | 7.83 | 24.44 |
August | 120.17 | 23.06 | 255.50 | 23.94 | 0.00 | 23.94 |
September | 408.33 | 22.12 | 48.00 | 22.22 | 25.33 | 22.14 |
October | 502.00 | 20.76 | 319.33 | 20.63 | 319.33 | 20.56 |
November | 489.00 | 19.90 | 489.00 | 19.90 | 489.00 | 19.90 |
December | 497.00 | 19.79 | 497.00 | 19.79 | 497.00 | 19.79 |
Annual Sum or Average | 4325.67 | 20.81 | 3933.33 | 20.99 | 2937.17 | 20.74 |
Minimum of Months | 47.33 | 19.79 | 48.00 | 19.79 | 0.00 | 19.79 |
Maximum of Months | 514.00 | 23.64 | 502.00 | 24.39 | 502.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.59 | 502.00 | 17.59 | 502.00 | 17.59 |
February | 454.00 | 18.57 | 444.00 | 18.54 | 444.00 | 18.53 |
March | 514.00 | 19.51 | 436.17 | 19.36 | 436.17 | 19.30 |
April | 427.83 | 21.13 | 160.00 | 20.89 | 141.67 | 20.64 |
May | 373.17 | 22.12 | 57.83 | 22.39 | 12.83 | 22.32 |
June | 203.33 | 22.51 | 159.33 | 23.37 | 0.00 | 23.37 |
July | 128.67 | 22.47 | 296.33 | 23.89 | 5.67 | 23.93 |
August | 229.17 | 22.31 | 216.17 | 23.36 | 8.00 | 23.38 |
September | 394.33 | 21.53 | 87.00 | 21.73 | 38.33 | 21.55 |
October | 496.67 | 20.23 | 325.50 | 19.97 | 324.67 | 19.85 |
November | 489.00 | 18.04 | 489.00 | 18.04 | 489.00 | 18.04 |
December | 497.00 | 17.33 | 497.00 | 17.33 | 497.00 | 17.33 |
Annual Sum or Average | 4709.17 | 19.78 | 3670.33 | 19.74 | 2899.33 | 19.39 |
Minimum of Months | 128.67 | 17.33 | 57.83 | 17.33 | 0.00 | 17.33 |
Maximum of Months | 514.00 | 22.51 | 502.00 | 23.89 | 502.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.89 | 454.00 | 19.89 | 454.00 | 19.89 |
March | 514.00 | 20.32 | 496.33 | 20.30 | 496.33 | 20.29 |
April | 454.17 | 21.34 | 197.17 | 21.08 | 195.67 | 20.94 |
May | 423.00 | 22.50 | 14.33 | 22.54 | 5.17 | 22.51 |
June | 171.50 | 23.04 | 162.50 | 23.76 | 0.17 | 23.76 |
July | 114.83 | 22.93 | 262.33 | 23.96 | 0.00 | 23.96 |
August | 247.00 | 22.83 | 154.83 | 23.44 | 0.00 | 23.44 |
September | 459.67 | 21.87 | 44.83 | 21.79 | 42.17 | 21.71 |
October | 502.00 | 20.58 | 388.83 | 20.50 | 388.83 | 20.47 |
November | 489.00 | 19.90 | 489.00 | 19.90 | 489.00 | 19.90 |
December | 497.00 | 19.79 | 497.00 | 19.79 | 497.00 | 19.79 |
Annual Sum or Average | 4828.17 | 20.87 | 3663.17 | 20.82 | 3070.33 | 20.61 |
Minimum of Months | 114.83 | 19.79 | 14.33 | 19.79 | 0.00 | 19.79 |
Maximum of Months | 514.00 | 23.04 | 502.00 | 23.96 | 502.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.80 | 502.00 | 19.80 | 502.00 | 19.80 |
February | 454.00 | 19.91 | 453.00 | 19.91 | 453.00 | 19.91 |
March | 514.00 | 20.35 | 476.83 | 20.32 | 476.83 | 20.30 |
April | 485.00 | 21.53 | 189.17 | 21.16 | 189.17 | 20.96 |
May | 365.33 | 23.46 | 1.00 | 23.46 | 0.00 | 23.46 |
June | 21.00 | 23.51 | 200.17 | 24.41 | 0.00 | 24.41 |
July | 4.50 | 23.50 | 362.33 | 24.41 | 0.00 | 24.41 |
August | 146.00 | 23.14 | 127.67 | 23.71 | 0.00 | 23.71 |
September | 478.67 | 22.16 | 57.50 | 22.00 | 57.50 | 21.87 |
October | 502.00 | 20.47 | 389.50 | 20.36 | 389.50 | 20.32 |
November | 489.00 | 19.82 | 489.00 | 19.82 | 489.00 | 19.82 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 4458.50 | 20.82 | 3745.17 | 20.81 | 3054.00 | 20.59 |
Minimum of Months | 4.50 | 19.77 | 1.00 | 19.77 | 0.00 | 19.77 |
Maximum of Months | 514.00 | 23.51 | 502.00 | 24.41 | 502.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.62 | 427.00 | 19.62 | 427.00 | 19.62 |
February | 385.00 | 19.81 | 381.00 | 19.80 | 381.00 | 19.80 |
March | 432.33 | 20.51 | 350.17 | 20.41 | 350.17 | 20.37 |
April | 372.50 | 21.53 | 131.00 | 21.31 | 120.50 | 21.12 |
May | 227.00 | 22.98 | 96.33 | 23.49 | 8.33 | 23.58 |
June | 87.00 | 23.20 | 212.00 | 24.06 | 2.67 | 24.09 |
July | 64.00 | 23.60 | 292.17 | 24.38 | 12.00 | 24.46 |
August | 172.00 | 22.77 | 168.00 | 23.55 | 2.17 | 23.54 |
September | 360.83 | 21.71 | 60.33 | 21.81 | 37.83 | 21.71 |
October | 426.17 | 20.46 | 310.17 | 20.33 | 310.17 | 20.28 |
November | 417.00 | 19.63 | 417.00 | 19.63 | 417.00 | 19.63 |
December | 422.00 | 19.57 | 422.00 | 19.57 | 422.00 | 19.57 |
Annual Sum or Average | 3792.83 | 20.71 | 3267.17 | 20.84 | 2490.83 | 20.60 |
Minimum of Months | 64.00 | 19.57 | 60.33 | 19.57 | 2.17 | 19.57 |
Maximum of Months | 432.33 | 23.60 | 427.00 | 24.38 | 427.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 498.83 | 19.87 | 498.83 | 19.86 |
February | 451.17 | 20.31 | 401.33 | 20.21 | 401.33 | 20.18 |
March | 463.50 | 20.90 | 315.67 | 20.70 | 313.00 | 20.60 |
April | 340.17 | 21.69 | 170.00 | 21.80 | 101.67 | 21.56 |
May | 269.50 | 22.70 | 121.17 | 23.24 | 8.83 | 23.28 |
June | 137.17 | 23.07 | 247.67 | 23.90 | 5.50 | 23.94 |
July | 116.17 | 23.18 | 317.00 | 24.12 | 10.50 | 24.19 |
August | 198.50 | 22.77 | 230.67 | 23.66 | 6.17 | 23.70 |
September | 365.17 | 21.86 | 103.83 | 22.20 | 30.50 | 22.11 |
October | 482.00 | 20.82 | 291.00 | 20.64 | 287.00 | 20.54 |
November | 489.00 | 19.97 | 479.67 | 19.95 | 479.67 | 19.94 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4311.33 | 20.95 | 3673.83 | 21.12 | 2640.00 | 20.87 |
Minimum of Months | 116.17 | 19.81 | 103.83 | 19.81 | 5.50 | 19.81 |
Maximum of Months | 502.00 | 23.18 | 498.83 | 24.12 | 498.83 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 502.00 | 19.83 | 502.00 | 19.83 |
February | 454.00 | 19.95 | 450.67 | 19.94 | 450.67 | 19.94 |
March | 514.00 | 20.45 | 443.00 | 20.38 | 443.00 | 20.35 |
April | 421.00 | 21.36 | 177.33 | 21.18 | 157.17 | 21.00 |
May | 360.00 | 22.62 | 48.33 | 22.82 | 3.17 | 22.81 |
June | 141.33 | 22.98 | 207.67 | 23.87 | 3.00 | 23.90 |
July | 125.67 | 22.86 | 278.67 | 23.93 | 1.33 | 23.94 |
August | 270.67 | 22.62 | 153.50 | 23.24 | 2.33 | 23.24 |
September | 456.33 | 21.67 | 65.67 | 21.64 | 54.50 | 21.54 |
October | 502.00 | 20.44 | 390.83 | 20.35 | 390.83 | 20.32 |
November | 489.00 | 19.83 | 489.00 | 19.83 | 489.00 | 19.83 |
December | 497.00 | 19.79 | 497.00 | 19.79 | 497.00 | 19.79 |
Annual Sum or Average | 4733.00 | 20.83 | 3703.67 | 20.84 | 2994.00 | 20.63 |
Minimum of Months | 125.67 | 19.79 | 48.33 | 19.79 | 1.33 | 19.79 |
Maximum of Months | 514.00 | 22.98 | 502.00 | 23.93 | 502.00 | 23.94 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19801 | 12.57003 | -0.6088 | 14.43945 |
February | 454.00000 | 21.75924 | 13.88394 | -0.4507 | 10.77610 |
March | 514.00000 | 22.66861 | 14.74319 | -0.2194 | 6.97716 |
April | 485.00000 | 23.74161 | 15.40837 | 0.08624 | 5.93176 |
May | 508.00000 | 24.28470 | 20.78649 | -0.5610 | 11.90820 |
June | 496.00000 | 24.39307 | 32.81008 | -0.4020 | 8.90808 |
July | 497.00000 | 24.46196 | 40.98338 | -0.3230 | 7.81731 |
August | 514.00000 | 24.37484 | 36.17307 | -0.3954 | 8.84955 |
September | 485.00000 | 24.17540 | 26.91744 | -0.5983 | 13.28865 |
October | 502.00000 | 23.26670 | 20.40611 | -0.0244 | 5.91091 |
November | 489.00000 | 21.82000 | 12.43888 | -0.4503 | 10.18298 |
December | 497.00000 | 21.26857 | 10.49761 | -0.5994 | 13.23467 |
Annual Sum or Average | 5943.00000 | 23.12867 | 21.54775 | -0.3786 | 9.83933 |
Minimum of Months | 454.00000 | 21.19801 | 10.49761 | -0.6088 | 5.91091 |
Maximum of Months | 514.00000 | 24.46196 | 40.98338 | 0.08624 | 14.43945 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44280 | 13.94066 | -0.7965 | 20.05260 |
February | 454.00000 | 20.77292 | 15.67903 | -0.6866 | 16.52575 |
March | 514.00000 | 21.40953 | 16.75924 | -0.5034 | 11.22226 |
April | 485.00000 | 22.78520 | 17.11769 | -0.1363 | 7.08375 |
May | 508.00000 | 23.94481 | 21.87979 | -0.6926 | 15.65659 |
June | 496.00000 | 24.23402 | 33.61990 | -0.4763 | 10.05330 |
July | 497.00000 | 24.29375 | 41.90515 | -0.4009 | 8.72866 |
August | 514.00000 | 24.15151 | 37.34468 | -0.4994 | 10.76760 |
September | 485.00000 | 23.36388 | 29.47674 | -0.8892 | 23.17661 |
October | 502.00000 | 21.70111 | 23.23740 | -0.3872 | 9.43194 |
November | 489.00000 | 20.68861 | 14.11308 | -0.7252 | 17.13427 |
December | 497.00000 | 20.48490 | 11.56574 | -0.8020 | 19.62395 |
Annual Sum or Average | 5943.00000 | 22.36978 | 23.12908 | -0.5821 | 14.08260 |
Minimum of Months | 454.00000 | 20.44280 | 11.56574 | -0.8892 | 7.08375 |
Maximum of Months | 514.00000 | 24.29375 | 41.90515 | -0.1363 | 23.17661 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07620 | 14.38151 | -0.9250 | 25.17656 |
February | 454.00000 | 20.25492 | 16.26366 | -0.8461 | 22.38586 |
March | 514.00000 | 20.79558 | 16.99337 | -0.6815 | 16.28489 |
April | 485.00000 | 22.05145 | 17.58237 | -0.3229 | 9.89375 |
May | 508.00000 | 23.61672 | 22.48353 | -0.8125 | 20.13222 |
June | 496.00000 | 24.12203 | 33.76382 | -0.5184 | 10.98080 |
July | 497.00000 | 24.18597 | 42.11035 | -0.4430 | 9.44703 |
August | 514.00000 | 23.91145 | 37.96558 | -0.5937 | 13.40585 |
September | 485.00000 | 22.53294 | 31.11423 | -1.1823 | 35.90888 |
October | 502.00000 | 20.85803 | 24.20053 | -0.6156 | 14.81298 |
November | 489.00000 | 20.13680 | 14.71354 | -0.8976 | 23.96203 |
December | 497.00000 | 20.07292 | 12.07153 | -0.9427 | 25.60375 |
Annual Sum or Average | 5943.00000 | 21.90021 | 23.71032 | -0.7304 | 18.93397 |
Minimum of Months | 454.00000 | 20.07292 | 12.07153 | -1.1823 | 9.44703 |
Maximum of Months | 514.00000 | 24.18597 | 42.11035 | -0.3229 | 35.90888 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.62066 | 14.46664 | -1.1586 | 34.89977 |
February | 454.00000 | 19.73355 | 16.54295 | -1.0855 | 31.95890 |
March | 514.00000 | 20.08917 | 17.35249 | -0.9338 | 25.51190 |
April | 485.00000 | 20.97029 | 18.21566 | -0.5935 | 15.76548 |
May | 508.00000 | 23.15316 | 23.04916 | -0.9480 | 25.87067 |
June | 496.00000 | 24.07407 | 34.04645 | -0.4875 | 10.67249 |
July | 497.00000 | 24.15017 | 42.10360 | -0.4180 | 9.26996 |
August | 514.00000 | 23.47335 | 39.26953 | -0.7248 | 18.37099 |
September | 485.00000 | 21.42912 | 33.05013 | -1.5605 | 54.08126 |
October | 502.00000 | 20.09432 | 24.60509 | -0.8651 | 23.08777 |
November | 489.00000 | 19.66268 | 14.97965 | -1.1355 | 33.92840 |
December | 497.00000 | 19.58869 | 12.06821 | -1.1879 | 36.12981 |
Annual Sum or Average | 5943.00000 | 21.35396 | 24.21952 | -0.9226 | 26.52551 |
Minimum of Months | 454.00000 | 19.58869 | 12.06821 | -1.5605 | 9.26996 |
Maximum of Months | 514.00000 | 24.15017 | 42.10360 | -0.4180 | 54.08126 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70494 | 13.84959 | -1.1469 | 34.29964 |
February | 454.00000 | 19.82655 | 15.77063 | -1.0490 | 30.41185 |
March | 514.00000 | 20.32805 | 16.36119 | -0.8175 | 21.55487 |
April | 485.00000 | 21.52416 | 16.89744 | -0.4027 | 12.78035 |
May | 508.00000 | 23.37161 | 21.84607 | -0.7278 | 20.29599 |
June | 496.00000 | 23.89611 | 34.01826 | -0.4238 | 10.69232 |
July | 497.00000 | 24.02278 | 41.93576 | -0.3302 | 9.66815 |
August | 514.00000 | 23.41339 | 38.70070 | -0.6256 | 16.41739 |
September | 485.00000 | 21.67918 | 31.83533 | -1.4129 | 47.98271 |
October | 502.00000 | 20.19843 | 23.72178 | -0.8175 | 21.45701 |
November | 489.00000 | 19.72550 | 14.21875 | -1.1268 | 33.48404 |
December | 497.00000 | 19.66949 | 11.55192 | -1.1800 | 35.69274 |
Annual Sum or Average | 5943.00000 | 21.46316 | 23.46712 | -0.8356 | 24.45170 |
Minimum of Months | 454.00000 | 19.66949 | 11.55192 | -1.4129 | 9.66815 |
Maximum of Months | 514.00000 | 24.02278 | 41.93576 | -0.3302 | 47.98271 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72952 | 13.49795 | -1.1192 | 33.22100 |
February | 454.00000 | 20.05341 | 15.22447 | -0.9467 | 26.78062 |
March | 514.00000 | 20.85547 | 15.54798 | -0.6581 | 18.84526 |
April | 485.00000 | 22.05004 | 15.93336 | -0.2466 | 12.54481 |
May | 508.00000 | 23.05277 | 22.01353 | -0.8500 | 25.72610 |
June | 496.00000 | 23.66086 | 34.36182 | -0.5193 | 13.62743 |
July | 497.00000 | 23.77078 | 42.43719 | -0.4301 | 12.17957 |
August | 514.00000 | 23.31862 | 38.61026 | -0.6379 | 18.48118 |
September | 485.00000 | 21.98115 | 30.86689 | -1.2856 | 43.47343 |
October | 502.00000 | 20.49518 | 22.97377 | -0.7201 | 19.29538 |
November | 489.00000 | 19.78598 | 13.82185 | -1.0773 | 31.58401 |
December | 497.00000 | 19.68388 | 11.21404 | -1.1673 | 35.15542 |
Annual Sum or Average | 5943.00000 | 21.55083 | 23.12066 | -0.8030 | 24.17540 |
Minimum of Months | 454.00000 | 19.68388 | 11.21404 | -1.2856 | 12.17957 |
Maximum of Months | 514.00000 | 23.77078 | 42.43719 | -0.2466 | 43.47343 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70426 | 13.77208 | -1.1504 | 34.43318 |
February | 454.00000 | 19.81599 | 15.70421 | -1.0673 | 31.11511 |
March | 514.00000 | 20.20602 | 16.39348 | -0.8884 | 23.91067 |
April | 485.00000 | 21.33516 | 17.00337 | -0.4568 | 14.50803 |
May | 508.00000 | 22.65132 | 22.98094 | -1.0253 | 30.82019 |
June | 496.00000 | 23.61550 | 34.89328 | -0.5558 | 14.39015 |
July | 497.00000 | 23.61407 | 43.23897 | -0.5176 | 13.15076 |
August | 514.00000 | 22.95413 | 39.89925 | -0.8082 | 22.47406 |
September | 485.00000 | 21.36000 | 32.32040 | -1.5408 | 53.76672 |
October | 502.00000 | 20.11196 | 23.77972 | -0.8577 | 22.80522 |
November | 489.00000 | 19.72791 | 14.13302 | -1.1264 | 33.47006 |
December | 497.00000 | 19.66950 | 11.47406 | -1.1810 | 35.73016 |
Annual Sum or Average | 5943.00000 | 21.24427 | 23.88053 | -0.9297 | 27.47262 |
Minimum of Months | 454.00000 | 19.66950 | 11.47406 | -1.5408 | 13.15076 |
Maximum of Months | 514.00000 | 23.61550 | 43.23897 | -0.4568 | 53.76672 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67354 | 14.00535 | -1.1288 | 33.42395 |
February | 454.00000 | 19.76016 | 15.93776 | -1.0776 | 31.37066 |
March | 514.00000 | 20.22184 | 17.26784 | -0.9136 | 24.09789 |
April | 485.00000 | 20.95472 | 18.79898 | -0.6125 | 14.74159 |
May | 508.00000 | 23.12343 | 23.91279 | -1.0014 | 27.28219 |
June | 496.00000 | 24.09884 | 34.44158 | -0.5265 | 11.16414 |
July | 497.00000 | 24.22662 | 42.32789 | -0.4218 | 9.05645 |
August | 514.00000 | 23.85828 | 38.71248 | -0.6115 | 13.91623 |
September | 485.00000 | 22.27518 | 31.70306 | -1.2586 | 39.36583 |
October | 502.00000 | 20.61673 | 23.97064 | -0.6938 | 16.55741 |
November | 489.00000 | 19.87263 | 14.51146 | -1.0385 | 29.41417 |
December | 497.00000 | 19.74223 | 11.82623 | -1.1174 | 32.74585 |
Annual Sum or Average | 5943.00000 | 21.55317 | 24.02970 | -0.8646 | 23.50165 |
Minimum of Months | 454.00000 | 19.67354 | 11.82623 | -1.2586 | 9.05645 |
Maximum of Months | 514.00000 | 24.22662 | 42.32789 | -0.4218 | 39.36583 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79738 | 13.36671 | -1.1142 | 32.68500 |
February | 454.00000 | 19.92529 | 15.07190 | -1.0321 | 29.30286 |
March | 514.00000 | 20.49999 | 16.02015 | -0.7924 | 19.71297 |
April | 485.00000 | 21.73043 | 16.97870 | -0.3699 | 10.88518 |
May | 508.00000 | 23.67828 | 21.70746 | -0.6741 | 17.06134 |
June | 496.00000 | 24.05510 | 33.95441 | -0.4201 | 9.87233 |
July | 497.00000 | 24.26998 | 41.59067 | -0.2829 | 8.08585 |
August | 514.00000 | 23.92583 | 37.67714 | -0.4740 | 11.27173 |
September | 485.00000 | 22.51513 | 30.11587 | -1.1098 | 34.15072 |
October | 502.00000 | 20.76329 | 22.73219 | -0.6379 | 15.05850 |
November | 489.00000 | 19.90041 | 13.53192 | -1.0425 | 29.53478 |
December | 497.00000 | 19.78790 | 11.28309 | -1.1218 | 32.90784 |
Annual Sum or Average | 5943.00000 | 21.75492 | 22.91262 | -0.7531 | 20.76720 |
Minimum of Months | 454.00000 | 19.78790 | 11.28309 | -1.1218 | 8.08585 |
Maximum of Months | 514.00000 | 24.26998 | 41.59067 | -0.2829 | 34.15072 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.59490 | 12.14682 | -1.5187 | 49.17108 |
February | 454.00000 | 18.56777 | 13.51799 | -1.2408 | 37.74761 |
March | 514.00000 | 19.51489 | 14.00325 | -0.9257 | 25.69693 |
April | 485.00000 | 21.54046 | 15.51647 | -0.3342 | 11.83951 |
May | 508.00000 | 22.73751 | 22.27878 | -0.9615 | 28.29712 |
June | 496.00000 | 23.52346 | 34.71944 | -0.5970 | 14.85730 |
July | 497.00000 | 23.81005 | 42.48895 | -0.4404 | 11.75102 |
August | 514.00000 | 23.41426 | 38.16887 | -0.5927 | 16.26430 |
September | 485.00000 | 22.10842 | 29.40073 | -1.1694 | 37.56692 |
October | 502.00000 | 20.27338 | 21.03061 | -0.6955 | 18.50056 |
November | 489.00000 | 18.03561 | 11.85261 | -1.3720 | 43.14228 |
December | 497.00000 | 17.32744 | 10.17505 | -1.5910 | 51.83449 |
Annual Sum or Average | 5943.00000 | 20.72320 | 22.19451 | -0.9506 | 28.78706 |
Minimum of Months | 454.00000 | 17.32744 | 10.17505 | -1.5910 | 11.75102 |
Maximum of Months | 514.00000 | 23.81005 | 42.48895 | -0.3342 | 51.83449 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79493 | 13.24854 | -1.1183 | 32.85523 |
February | 454.00000 | 19.88903 | 14.97707 | -1.0561 | 30.31580 |
March | 514.00000 | 20.31526 | 16.03310 | -0.8771 | 22.68532 |
April | 485.00000 | 21.51282 | 17.04570 | -0.4231 | 11.77037 |
May | 508.00000 | 22.79486 | 23.10346 | -1.0210 | 29.24835 |
June | 496.00000 | 23.81590 | 34.76273 | -0.5417 | 12.74591 |
July | 497.00000 | 23.89388 | 42.90992 | -0.4651 | 10.80918 |
August | 514.00000 | 23.52282 | 38.79210 | -0.6413 | 15.65299 |
September | 485.00000 | 21.99130 | 30.90066 | -1.2947 | 41.57259 |
October | 502.00000 | 20.57893 | 22.83702 | -0.7003 | 16.60966 |
November | 489.00000 | 19.90154 | 13.39431 | -1.0428 | 29.54993 |
December | 497.00000 | 19.78735 | 11.16104 | -1.1232 | 32.96264 |
Annual Sum or Average | 5943.00000 | 21.49814 | 23.34690 | -0.8569 | 23.81905 |
Minimum of Months | 454.00000 | 19.78735 | 11.16104 | -1.2947 | 10.80918 |
Maximum of Months | 514.00000 | 23.89388 | 42.90992 | -0.4231 | 41.57259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79862 | 14.53821 | -1.0640 | 30.76991 |
February | 454.00000 | 19.91375 | 16.46056 | -0.9885 | 27.81897 |
March | 514.00000 | 20.34830 | 17.37974 | -0.8229 | 20.88610 |
April | 485.00000 | 21.52633 | 17.96695 | -0.4355 | 11.96586 |
May | 508.00000 | 23.63455 | 22.41694 | -0.7835 | 19.06589 |
June | 496.00000 | 24.20190 | 33.79406 | -0.4411 | 9.48516 |
July | 497.00000 | 24.30273 | 41.81238 | -0.3637 | 8.19476 |
August | 514.00000 | 23.85847 | 38.42812 | -0.5907 | 13.60845 |
September | 485.00000 | 22.18221 | 31.82972 | -1.2809 | 40.65803 |
October | 502.00000 | 20.47373 | 24.20372 | -0.7232 | 17.89107 |
November | 489.00000 | 19.81773 | 14.99684 | -1.0363 | 29.62375 |
December | 497.00000 | 19.77474 | 12.23030 | -1.0875 | 31.62741 |
Annual Sum or Average | 5943.00000 | 21.67026 | 23.91057 | -0.7992 | 21.70253 |
Minimum of Months | 454.00000 | 19.77474 | 12.23030 | -1.2809 | 8.19476 |
Maximum of Months | 514.00000 | 24.30273 | 41.81238 | -0.3637 | 40.65803 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.62227 | 13.23245 | -1.1090 | 32.80073 |
February | 385.00000 | 19.80742 | 14.97479 | -1.0024 | 28.43048 |
March | 433.00000 | 20.51869 | 15.72447 | -0.7420 | 18.42925 |
April | 410.00000 | 21.79108 | 16.17268 | -0.3228 | 10.66061 |
May | 430.00000 | 23.57113 | 21.30727 | -0.6677 | 18.01351 |
June | 418.00000 | 24.01026 | 33.74682 | -0.4068 | 10.15569 |
July | 422.00000 | 24.16986 | 41.67602 | -0.3031 | 9.04896 |
August | 433.00000 | 23.61165 | 37.98661 | -0.5688 | 14.35458 |
September | 410.00000 | 22.07692 | 30.54634 | -1.2514 | 40.82125 |
October | 427.00000 | 20.46643 | 22.73767 | -0.7120 | 17.54798 |
November | 417.00000 | 19.63220 | 13.64031 | -1.0817 | 31.66615 |
December | 422.00000 | 19.57160 | 11.03509 | -1.1387 | 33.99134 |
Annual Sum or Average | 5034.00000 | 21.58432 | 22.79234 | -0.7734 | 22.07117 |
Minimum of Months | 385.00000 | 19.57160 | 11.03509 | -1.2514 | 9.04896 |
Maximum of Months | 433.00000 | 24.16986 | 41.67602 | -0.3031 | 40.82125 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86933 | 13.17439 | -1.0336 | 29.51768 |
February | 454.00000 | 20.33041 | 14.71424 | -0.8346 | 22.44048 |
March | 514.00000 | 21.23063 | 15.19618 | -0.5294 | 15.08950 |
April | 485.00000 | 22.46311 | 15.57722 | -0.1218 | 10.24784 |
May | 508.00000 | 23.41729 | 21.54070 | -0.7211 | 20.09579 |
June | 496.00000 | 23.87518 | 33.98864 | -0.4521 | 11.27221 |
July | 497.00000 | 23.98505 | 42.03670 | -0.3623 | 10.05408 |
August | 514.00000 | 23.64428 | 37.88071 | -0.5243 | 14.24339 |
September | 485.00000 | 22.47312 | 29.83749 | -1.0823 | 34.26736 |
October | 502.00000 | 20.94448 | 22.28249 | -0.5686 | 14.66861 |
November | 489.00000 | 19.96904 | 13.33944 | -0.9757 | 27.23274 |
December | 497.00000 | 19.81047 | 10.91158 | -1.0807 | 31.30490 |
Annual Sum or Average | 5943.00000 | 21.84883 | 22.61932 | -0.6888 | 19.97449 |
Minimum of Months | 454.00000 | 19.81047 | 10.91158 | -1.0823 | 10.05408 |
Maximum of Months | 514.00000 | 23.98505 | 42.03670 | -0.1218 | 34.26736 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82612 | 13.50884 | -1.0688 | 30.90056 |
February | 454.00000 | 19.94736 | 15.32286 | -0.9816 | 27.49232 |
March | 514.00000 | 20.44613 | 16.17778 | -0.7832 | 19.71821 |
April | 485.00000 | 21.72959 | 16.67328 | -0.3321 | 11.38495 |
May | 508.00000 | 23.08688 | 22.45826 | -0.8739 | 23.99187 |
June | 496.00000 | 23.85542 | 34.49513 | -0.4800 | 11.76128 |
July | 497.00000 | 23.86210 | 42.77454 | -0.4386 | 10.72772 |
August | 514.00000 | 23.34283 | 39.05485 | -0.6745 | 17.25507 |
September | 485.00000 | 21.82640 | 31.33110 | -1.3396 | 44.04997 |
October | 502.00000 | 20.44219 | 23.21743 | -0.7272 | 17.85938 |
November | 489.00000 | 19.83425 | 13.79906 | -1.0393 | 29.71310 |
December | 497.00000 | 19.78720 | 11.21737 | -1.0967 | 31.98064 |
Annual Sum or Average | 5943.00000 | 21.51372 | 23.41662 | -0.8179 | 22.98947 |
Minimum of Months | 454.00000 | 19.78720 | 11.21737 | -1.3396 | 10.72772 |
Maximum of Months | 514.00000 | 23.86210 | 42.77454 | -0.3321 | 44.04997 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3752597.80 | 1094404.25 | 1.37 | 3752597.80 | 0.00 | 0.00 | 0.20 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5048.40 | 20-JAN-07:01 | 5048.40 | 20-JAN-07:01 | 0.00 | 20-JAN-08:25 | 1426.11 | 20-JAN-07:01 | 0.00 |
February | 10678114.99 | 3128310.72 | 4.04 | 10676780.17 | 1334.82 | 0.00 | 0.19 | 02-FEB-07:01 | 0.00 | 01-FEB-00:10 | 4784.65 | 02-FEB-07:01 | 4784.65 | 02-FEB-07:01 | 10.85 | 09-FEB-17:12 | 1354.88 | 02-FEB-07:01 | 0.00 |
March | 28424233.33 | 8332207.99 | 11.23 | 28370420.50 | 53812.83 | 0.00 | 0.20 | 07-MAR-07:01 | 0.00 | 01-MAR-00:05 | 5029.28 | 07-MAR-07:01 | 5029.28 | 07-MAR-07:01 | 61.93 | 21-MAR-17:13 | 1420.96 | 07-MAR-07:01 | 0.00 |
April | 60975423.22 | 17807233.76 | 22.76 | 60972108.69 | 3314.53 | 0.00 | 0.37 | 14-APR-07:04 | 0.00 | 01-APR-00:10 | 9650.16 | 14-APR-07:04 | 9650.16 | 14-APR-07:04 | 4.93 | 29-APR-10:10 | 2615.71 | 14-APR-07:04 | 0.00 |
May | 0.411832E+10 | 0.107471E+10 | 136.47 | 0.411602E+10 | 2299965.79 | 0.00 | 1.00 | 31-MAY-14:50 | 0.00 | 01-MAY-00:10 | 38226.11 | 31-MAY-16:00 | 38226.11 | 31-MAY-16:00 | 251.28 | 31-MAY-21:00 | 8726.28 | 31-MAY-16:00 | 0.00 |
June | 0.218849E+11 | 0.535697E+10 | 311.21 | 0.210201E+11 | 0.864797E+09 | 0.00 | 1.00 | 09-JUN-12:10 | 0.00 | 01-JUN-00:10 | 67635.42 | 30-JUN-11:40 | 60326.79 | 20-JUN-16:00 | 13531.25 | 30-JUN-11:40 | 16166.60 | 30-JUN-12:30 | 0.00 |
July | 0.307206E+11 | 0.735310E+10 | 328.84 | 0.283722E+11 | 0.234836E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 67225.52 | 11-JUL-16:00 | 65810.68 | 12-JUL-16:00 | 32847.27 | 03-JUL-15:00 | 16691.67 | 21-JUL-16:00 | 0.00 |
August | 0.165016E+11 | 0.401683E+10 | 242.13 | 0.153117E+11 | 0.118989E+10 | 0.00 | 1.00 | 01-AUG-14:30 | 0.00 | 01-AUG-00:10 | 63966.46 | 11-AUG-15:50 | 63966.46 | 11-AUG-15:50 | 8912.53 | 03-AUG-04:02 | 15209.35 | 11-AUG-16:00 | 0.00 |
September | 0.281610E+09 | 80660630.75 | 39.09 | 0.268778E+09 | 12832550.02 | 0.00 | 0.37 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 9731.61 | 07-SEP-16:00 | 9731.61 | 07-SEP-16:00 | 603.27 | 02-SEP-14:50 | 2635.90 | 07-SEP-16:00 | 0.00 |
October | 44170353.38 | 12914725.51 | 16.66 | 43700108.08 | 470245.30 | 0.00 | 0.24 | 05-OCT-07:05 | 0.00 | 01-OCT-00:10 | 6141.52 | 05-OCT-07:05 | 6141.52 | 05-OCT-07:05 | 102.73 | 02-OCT-07:02 | 1717.69 | 05-OCT-07:05 | 0.00 |
November | 2938916.55 | 861208.84 | 1.12 | 2938916.55 | 0.00 | 0.00 | 0.11 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 | 2785.13 | 04-NOV-06:03 | 2785.13 | 04-NOV-06:03 | 0.00 | 03-NOV-17:40 | 803.43 | 04-NOV-06:03 | 0.00 |
December | 1003420.99 | 292344.71 | 0.37 | 1003420.99 | 0.00 | 0.00 | 0.11 | 21-DEC-07:01 | 0.00 | 01-DEC-00:05 | 2738.74 | 21-DEC-07:01 | 2738.74 | 21-DEC-07:01 | 0.00 | 20-DEC-07:01 | 790.40 | 21-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.736589E+11 | 0.179267E+11 | 1115.29 | 0.692402E+11 | 0.441871E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1003420.99 | 292344.71 | 0.37 | 1003420.99 | 0.00 | 0.00 | 0.11 | 0.00 | 2738.74 | 2738.74 | 0.00 | 790.40 | 0.00 | ||||||
Maximum of Months | 0.307206E+11 | 0.735310E+10 | 328.84 | 0.283722E+11 | 0.234836E+10 | 0.00 | 1.00 | 0.00 | 67635.42 | 65810.68 | 32847.27 | 16691.67 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1013616.93 | 291224.94 | 0.12 | 1013616.93 | 0.00 | 0.00 | 0.19 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 4373.56 | 19-JAN-07:01 | 4373.56 | 19-JAN-07:01 | 0.00 | 19-JAN-07:01 | 1237.84 | 19-JAN-07:01 | 0.00 |
February | 1993333.29 | 565566.37 | 0.18 | 1993333.29 | -0.0 | 0.00 | 0.27 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 6283.25 | 09-FEB-07:01 | 6283.25 | 09-FEB-07:01 | 0.00 | 03-FEB-07:01 | 1744.47 | 09-FEB-07:01 | 0.00 |
March | 9112984.46 | 2651421.70 | 5.19 | 9108694.11 | 4290.35 | 0.00 | 0.29 | 21-MAR-06:01 | 0.00 | 01-MAR-00:05 | 6580.16 | 21-MAR-06:01 | 6580.16 | 21-MAR-06:01 | 4.02 | 22-MAR-11:30 | 1821.51 | 21-MAR-06:01 | 0.00 |
April | 53938954.07 | 15804024.33 | 28.39 | 53938954.07 | -0.0 | 0.00 | 0.27 | 17-APR-06:01 | 0.00 | 01-APR-00:10 | 6303.60 | 17-APR-06:01 | 6303.60 | 17-APR-06:01 | 0.00 | 11-APR-12:00 | 1749.76 | 17-APR-06:01 | 0.00 |
May | 0.442927E+10 | 0.114310E+10 | 152.89 | 0.442762E+10 | 1655246.76 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 39223.65 | 31-MAY-16:00 | 39223.65 | 31-MAY-16:00 | 428.26 | 31-MAY-06:03 | 8951.62 | 31-MAY-16:00 | 0.00 |
June | 0.216576E+11 | 0.526596E+10 | 319.74 | 0.208323E+11 | 0.825384E+09 | 0.00 | 1.00 | 09-JUN-12:05 | 0.00 | 01-JUN-00:10 | 66714.64 | 30-JUN-12:10 | 60065.58 | 30-JUN-14:30 | 12942.37 | 30-JUN-11:40 | 16084.22 | 30-JUN-14:30 | 0.00 |
July | 0.291000E+11 | 0.695337E+10 | 336.96 | 0.269182E+11 | 0.218178E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 63818.78 | 11-JUL-15:30 | 61047.01 | 12-JUL-16:00 | 32601.37 | 03-JUL-15:00 | 15317.28 | 11-JUL-16:00 | 0.00 |
August | 0.151473E+11 | 0.368487E+10 | 247.94 | 0.140612E+11 | 0.108618E+10 | 0.00 | 1.00 | 01-AUG-13:00 | 0.00 | 01-AUG-00:10 | 58892.18 | 11-AUG-15:20 | 58892.18 | 11-AUG-15:20 | 7663.69 | 03-AUG-05:02 | 13816.48 | 11-AUG-15:40 | 0.00 |
September | 0.246194E+09 | 70279120.84 | 35.77 | 0.235331E+09 | 10863412.99 | 0.00 | 0.37 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 8822.93 | 07-SEP-16:00 | 8822.93 | 07-SEP-16:00 | 487.68 | 02-SEP-14:10 | 2389.08 | 07-SEP-16:00 | 0.00 |
October | 9925053.09 | 2863132.62 | 4.10 | 9736233.83 | 188819.26 | 0.00 | 0.29 | 19-OCT-06:01 | 0.00 | 01-OCT-00:10 | 6612.58 | 19-OCT-06:01 | 6612.58 | 19-OCT-06:01 | 63.29 | 03-OCT-10:30 | 1829.89 | 19-OCT-06:01 | 0.00 |
November | 641644.47 | 186585.14 | 0.13 | 641644.47 | -0.0 | 0.00 | 0.12 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 2694.50 | 02-NOV-06:01 | 2694.50 | 02-NOV-06:01 | 0.00 | 01-NOV-06:01 | 775.86 | 02-NOV-06:01 | 0.00 |
December | 484074.36 | 138621.50 | 0.04 | 484074.36 | 0.00 | 0.00 | 0.14 | 23-DEC-07:03 | 0.00 | 01-DEC-00:05 | 3227.16 | 23-DEC-07:03 | 3227.16 | 23-DEC-07:03 | 0.00 | 23-DEC-07:03 | 924.14 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.706576E+11 | 0.171401E+11 | 1131.45 | 0.665515E+11 | 0.410605E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 484074.36 | 138621.50 | 0.04 | 484074.36 | -0.0 | 0.00 | 0.12 | 0.00 | 2694.50 | 2694.50 | 0.00 | 775.86 | 0.00 | ||||||
Maximum of Months | 0.291000E+11 | 0.695337E+10 | 336.96 | 0.269182E+11 | 0.218178E+10 | 0.00 | 1.00 | 0.00 | 66714.64 | 61047.01 | 32601.37 | 16084.22 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 210855.56 | 60387.52 | 0.02 | 210855.56 | 0.00 | 0.00 | 0.14 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 3514.26 | 09-FEB-07:01 | 3514.26 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 1006.46 | 09-FEB-07:01 | 0.00 |
March | 7668274.86 | 2262014.62 | 6.22 | 7666871.58 | 1403.28 | 0.00 | 0.11 | 23-MAR-06:01 | 0.00 | 01-MAR-00:05 | 2612.08 | 23-MAR-06:01 | 2612.08 | 23-MAR-06:01 | 9.36 | 22-MAR-12:05 | 754.49 | 23-MAR-06:01 | 0.00 |
April | 43493888.24 | 12783126.79 | 22.90 | 43489123.96 | 4764.28 | 0.00 | 0.19 | 18-APR-06:01 | 0.00 | 01-APR-00:10 | 4559.87 | 18-APR-06:01 | 4559.87 | 18-APR-06:01 | 4.37 | 28-APR-11:00 | 1293.18 | 18-APR-06:01 | 0.00 |
May | 0.435084E+10 | 0.113079E+10 | 153.22 | 0.434757E+10 | 3269570.41 | 0.00 | 1.00 | 12-MAY-13:20 | 0.00 | 01-MAY-00:10 | 41253.62 | 31-MAY-16:00 | 41253.62 | 31-MAY-16:00 | 270.87 | 31-MAY-20:10 | 9415.68 | 31-MAY-16:00 | 0.00 |
June | 0.220194E+11 | 0.538684E+10 | 316.55 | 0.211659E+11 | 0.853452E+09 | 0.00 | 1.00 | 12-JUN-13:10 | 0.00 | 01-JUN-00:10 | 72302.74 | 30-JUN-12:30 | 66168.85 | 30-JUN-14:30 | 13564.43 | 30-JUN-11:50 | 17632.74 | 30-JUN-14:30 | 0.00 |
July | 0.296594E+11 | 0.712504E+10 | 334.45 | 0.274371E+11 | 0.222234E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 67513.15 | 21-JUL-14:30 | 67513.15 | 21-JUL-14:30 | 32413.65 | 03-JUL-15:00 | 16681.82 | 21-JUL-15:10 | 0.00 |
August | 0.151123E+11 | 0.370094E+10 | 244.45 | 0.139472E+11 | 0.116513E+10 | 0.00 | 1.00 | 02-AUG-12:10 | 0.00 | 01-AUG-00:10 | 61902.68 | 11-AUG-15:50 | 61902.68 | 11-AUG-15:50 | 7692.42 | 03-AUG-05:02 | 14663.41 | 11-AUG-15:50 | 0.00 |
September | 0.214897E+09 | 61512675.80 | 27.89 | 0.203884E+09 | 11012423.75 | 0.00 | 0.32 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 7997.07 | 07-SEP-16:00 | 7997.07 | 07-SEP-16:00 | 558.81 | 02-SEP-14:30 | 2197.54 | 07-SEP-16:00 | 0.00 |
October | 5109481.74 | 1495700.19 | 2.41 | 4929460.79 | 180020.95 | 0.00 | 0.19 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 | 4798.38 | 05-OCT-06:01 | 4798.38 | 05-OCT-06:01 | 84.95 | 03-OCT-11:00 | 1357.80 | 05-OCT-06:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.714133E+11 | 0.174217E+11 | 1108.10 | 0.671579E+11 | 0.425539E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.296594E+11 | 0.712504E+10 | 334.45 | 0.274371E+11 | 0.222234E+10 | 0.00 | 1.00 | 0.00 | 72302.74 | 67513.15 | 32413.65 | 17632.74 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.04 | 0.00 | 43.04 | 0.00 | 2952.06 | 0.00 | 0.00 | 0.00 |
February | 190.26 | 0.00 | 190.26 | 0.00 | 2628.35 | 0.00 | 0.00 | 0.00 |
March | 508.87 | 0.00 | 508.87 | 50.98 | 1920.47 | 0.00 | 0.00 | 0.00 |
April | 920.69 | 20.27 | 900.42 | 401.74 | 1002.31 | 0.00 | 0.00 | 0.00 |
May | 1411.11 | 224.35 | 1186.76 | 1107.45 | 456.49 | 0.00 | 0.00 | 0.00 |
June | 1841.11 | 409.44 | 1431.66 | 1785.23 | 216.21 | 0.00 | 0.00 | 0.00 |
July | 1545.21 | 251.16 | 1294.05 | 1530.37 | 264.72 | 0.00 | 0.00 | 0.00 |
August | 986.68 | 55.14 | 931.54 | 810.94 | 434.14 | 0.00 | 0.00 | 0.00 |
September | 550.46 | 0.55 | 549.90 | 230.68 | 851.26 | 0.00 | 0.00 | 0.00 |
October | 267.85 | 0.00 | 267.85 | 25.84 | 1619.31 | 0.00 | 0.00 | 0.00 |
November | 83.12 | 0.00 | 83.12 | 0.00 | 2882.22 | 0.00 | 0.00 | 0.00 |
December | 13.06 | 0.00 | 13.06 | 0.00 | 3112.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.29 | 80.43 | 618.85 | 498.14 | 1522.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.06 | 0.00 | 13.06 | 0.00 | 216.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.11 | 409.44 | 1431.66 | 1785.23 | 3112.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.59 | 23.79 | 51.80 | 7.24 | 1907.55 | 0.00 | 0.00 | 0.00 |
February | 417.63 | 199.28 | 218.35 | 224.40 | 1583.76 | 0.00 | 0.00 | 0.00 |
March | 1191.24 | 603.26 | 587.98 | 1005.85 | 1151.09 | 0.00 | 0.00 | 0.00 |
April | 1637.41 | 828.36 | 809.06 | 1513.74 | 619.45 | 0.00 | 0.00 | 0.00 |
May | 2378.69 | 1339.08 | 1039.61 | 2568.63 | 327.16 | 0.00 | 0.00 | 0.00 |
June | 2188.45 | 1019.53 | 1168.91 | 2436.35 | 162.89 | 0.00 | 0.00 | 0.00 |
July | 2078.74 | 1006.64 | 1072.10 | 2369.67 | 187.93 | 0.00 | 0.00 | 0.00 |
August | 1646.50 | 800.73 | 845.77 | 1803.07 | 290.16 | 0.00 | 0.00 | 0.00 |
September | 1018.56 | 445.87 | 572.69 | 952.59 | 535.17 | 0.00 | 0.00 | 0.00 |
October | 538.01 | 215.88 | 322.13 | 391.50 | 982.07 | 0.00 | 0.00 | 0.00 |
November | 114.44 | 39.99 | 74.45 | 10.34 | 1847.25 | 0.00 | 0.00 | 0.00 |
December | 16.35 | 3.91 | 12.44 | 0.00 | 2062.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1112.71 | 546.26 | 566.45 | 1112.87 | 968.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.35 | 3.91 | 12.44 | 0.00 | 162.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2378.69 | 1339.08 | 1168.91 | 2568.63 | 2062.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.35 | 340.19 | 176.16 | 305.40 | 2647.81 | 0.00 | 0.00 | 0.00 |
February | 1776.79 | 1235.94 | 540.85 | 1506.55 | 2117.78 | 0.00 | 0.00 | 0.00 |
March | 3051.12 | 2068.08 | 983.04 | 2964.64 | 1610.01 | 0.00 | 0.00 | 0.00 |
April | 3722.27 | 2315.63 | 1406.65 | 4012.75 | 1039.56 | 0.00 | 0.00 | 0.00 |
May | 3069.34 | 1590.39 | 1478.95 | 3401.02 | 564.98 | 0.00 | 0.00 | 0.00 |
June | 2802.42 | 1148.64 | 1653.78 | 3187.30 | 306.99 | 0.00 | 0.00 | 0.00 |
July | 2700.05 | 1175.87 | 1524.18 | 3143.94 | 329.23 | 0.00 | 0.00 | 0.00 |
August | 2796.18 | 1541.01 | 1255.16 | 3210.48 | 479.09 | 0.00 | 0.00 | 0.00 |
September | 2259.81 | 1360.97 | 898.84 | 2373.75 | 825.09 | 0.00 | 0.00 | 0.00 |
October | 1627.07 | 1032.33 | 594.74 | 1485.80 | 1366.34 | 0.00 | 0.00 | 0.00 |
November | 872.38 | 609.15 | 263.23 | 584.52 | 2461.05 | 0.00 | 0.00 | 0.00 |
December | 154.85 | 109.15 | 45.70 | 28.51 | 2954.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2111.84 | 1208.78 | 903.05 | 2185.39 | 1388.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 154.85 | 109.15 | 45.70 | 28.51 | 306.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3722.27 | 2315.63 | 1653.78 | 4012.75 | 2954.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.76 | 7.10 | 32.67 | 0.00 | 1945.90 | 0.00 | 0.00 | 0.00 |
February | 234.72 | 81.62 | 153.10 | 50.89 | 1644.47 | 0.00 | 0.00 | 0.00 |
March | 704.52 | 302.87 | 401.66 | 410.65 | 1175.28 | 0.00 | 0.00 | 0.00 |
April | 1671.76 | 866.32 | 805.44 | 1599.20 | 668.73 | 0.00 | 0.00 | 0.00 |
May | 1625.52 | 740.27 | 885.26 | 1646.29 | 347.21 | 0.00 | 0.00 | 0.00 |
June | 1781.49 | 759.58 | 1021.91 | 1942.68 | 191.25 | 0.00 | 0.00 | 0.00 |
July | 1490.59 | 563.85 | 926.74 | 1642.40 | 207.73 | 0.00 | 0.00 | 0.00 |
August | 1225.10 | 518.77 | 706.33 | 1289.41 | 304.84 | 0.00 | 0.00 | 0.00 |
September | 741.43 | 310.48 | 430.95 | 620.64 | 548.01 | 0.00 | 0.00 | 0.00 |
October | 290.37 | 87.29 | 203.07 | 116.08 | 1022.78 | 0.00 | 0.00 | 0.00 |
November | 116.18 | 42.21 | 73.97 | 13.86 | 1842.36 | 0.00 | 0.00 | 0.00 |
December | 10.43 | 1.10 | 9.33 | 0.00 | 2069.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 829.79 | 357.54 | 472.25 | 780.73 | 994.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.43 | 1.10 | 9.33 | 0.00 | 191.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1781.49 | 866.32 | 1021.91 | 1942.68 | 2069.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 988.82 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 877.22 | 0.00 | 0.00 | 0.00 |
March | 169.62 | 0.00 | 169.62 | 17.64 | 642.51 | 0.00 | 0.00 | 0.00 |
April | 306.88 | 6.76 | 300.13 | 139.73 | 337.02 | 0.00 | 0.00 | 0.00 |
May | 470.35 | 74.78 | 395.57 | 377.39 | 151.69 | 0.00 | 0.00 | 0.00 |
June | 613.67 | 136.47 | 477.20 | 602.83 | 71.46 | 0.00 | 0.00 | 0.00 |
July | 515.05 | 83.72 | 431.33 | 513.98 | 89.08 | 0.00 | 0.00 | 0.00 |
August | 328.88 | 18.38 | 310.50 | 267.90 | 151.54 | 0.00 | 0.00 | 0.00 |
September | 183.48 | 0.18 | 183.29 | 70.71 | 307.63 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.86 | 569.07 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 980.70 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1048.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.08 | 26.81 | 206.27 | 167.38 | 516.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.67 | 136.47 | 477.20 | 602.83 | 1048.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 988.88 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 877.27 | 0.00 | 0.00 | 0.00 |
March | 169.63 | 0.00 | 169.63 | 17.64 | 642.55 | 0.00 | 0.00 | 0.00 |
April | 306.90 | 6.76 | 300.15 | 139.74 | 337.04 | 0.00 | 0.00 | 0.00 |
May | 470.38 | 74.78 | 395.59 | 377.41 | 151.70 | 0.00 | 0.00 | 0.00 |
June | 613.71 | 136.48 | 477.23 | 602.87 | 71.47 | 0.00 | 0.00 | 0.00 |
July | 515.08 | 83.72 | 431.36 | 514.02 | 89.09 | 0.00 | 0.00 | 0.00 |
August | 328.90 | 18.38 | 310.52 | 267.92 | 151.55 | 0.00 | 0.00 | 0.00 |
September | 183.49 | 0.18 | 183.30 | 70.71 | 307.65 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.86 | 569.11 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 980.76 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1048.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.10 | 26.81 | 206.29 | 167.39 | 516.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.71 | 136.48 | 477.23 | 602.87 | 1048.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.35 | 0.00 | 14.35 | 0.00 | 988.88 | 0.00 | 0.00 | 0.00 |
February | 63.42 | 0.00 | 63.42 | 0.00 | 877.27 | 0.00 | 0.00 | 0.00 |
March | 169.63 | 0.00 | 169.63 | 17.64 | 642.55 | 0.00 | 0.00 | 0.00 |
April | 306.90 | 6.76 | 300.15 | 139.74 | 337.04 | 0.00 | 0.00 | 0.00 |
May | 470.38 | 74.78 | 395.59 | 377.41 | 151.70 | 0.00 | 0.00 | 0.00 |
June | 613.71 | 136.48 | 477.23 | 602.87 | 71.47 | 0.00 | 0.00 | 0.00 |
July | 515.08 | 83.72 | 431.36 | 514.02 | 89.09 | 0.00 | 0.00 | 0.00 |
August | 328.90 | 18.38 | 310.52 | 267.92 | 151.55 | 0.00 | 0.00 | 0.00 |
September | 183.49 | 0.18 | 183.30 | 70.71 | 307.65 | 0.00 | 0.00 | 0.00 |
October | 89.28 | 0.00 | 89.28 | 6.86 | 569.11 | 0.00 | 0.00 | 0.00 |
November | 27.71 | 0.00 | 27.71 | 0.00 | 980.76 | 0.00 | 0.00 | 0.00 |
December | 4.35 | 0.00 | 4.35 | 0.00 | 1048.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 233.10 | 26.81 | 206.29 | 167.39 | 516.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.35 | 0.00 | 4.35 | 0.00 | 71.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.71 | 136.48 | 477.23 | 602.87 | 1048.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.71 | 22.88 | 49.83 | 7.16 | 1844.53 | 0.00 | 0.00 | 0.00 |
February | 401.74 | 191.70 | 210.04 | 216.88 | 1528.96 | 0.00 | 0.00 | 0.00 |
March | 1145.92 | 580.31 | 565.61 | 973.73 | 1121.62 | 0.00 | 0.00 | 0.00 |
April | 1575.12 | 796.84 | 778.28 | 1464.20 | 616.95 | 0.00 | 0.00 | 0.00 |
May | 2288.20 | 1288.13 | 1000.06 | 2478.48 | 329.60 | 0.00 | 0.00 | 0.00 |
June | 2105.19 | 980.75 | 1124.45 | 2353.40 | 161.79 | 0.00 | 0.00 | 0.00 |
July | 1999.66 | 968.35 | 1031.31 | 2282.92 | 190.08 | 0.00 | 0.00 | 0.00 |
August | 1583.86 | 770.26 | 813.60 | 1729.48 | 300.50 | 0.00 | 0.00 | 0.00 |
September | 979.81 | 428.90 | 550.91 | 901.20 | 563.11 | 0.00 | 0.00 | 0.00 |
October | 517.54 | 207.67 | 309.88 | 369.52 | 1002.25 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 38.47 | 71.62 | 9.70 | 1812.54 | 0.00 | 0.00 | 0.00 |
December | 15.73 | 3.77 | 11.96 | 0.00 | 2002.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1070.38 | 525.48 | 544.90 | 1071.25 | 953.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.73 | 3.77 | 11.96 | 0.00 | 161.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2288.20 | 1288.13 | 1124.45 | 2478.48 | 2002.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.87 | 0.90 | 1.97 | 0.28 | 72.93 | 0.00 | 0.00 | 0.00 |
February | 15.88 | 7.58 | 8.30 | 8.58 | 60.45 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 22.94 | 22.36 | 38.50 | 44.35 | 0.00 | 0.00 | 0.00 |
April | 62.28 | 31.51 | 30.77 | 57.89 | 24.39 | 0.00 | 0.00 | 0.00 |
May | 90.47 | 50.93 | 39.54 | 98.00 | 13.03 | 0.00 | 0.00 | 0.00 |
June | 83.24 | 38.78 | 44.46 | 93.05 | 6.40 | 0.00 | 0.00 | 0.00 |
July | 79.06 | 38.29 | 40.78 | 90.26 | 7.52 | 0.00 | 0.00 | 0.00 |
August | 62.62 | 30.46 | 32.17 | 68.38 | 11.88 | 0.00 | 0.00 | 0.00 |
September | 38.74 | 16.96 | 21.78 | 35.63 | 22.26 | 0.00 | 0.00 | 0.00 |
October | 20.46 | 8.21 | 12.25 | 14.61 | 39.63 | 0.00 | 0.00 | 0.00 |
November | 4.35 | 1.52 | 2.83 | 0.38 | 71.67 | 0.00 | 0.00 | 0.00 |
December | 0.62 | 0.15 | 0.47 | 0.00 | 79.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.32 | 20.78 | 21.54 | 42.36 | 37.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.62 | 0.15 | 0.47 | 0.00 | 6.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.47 | 50.93 | 44.46 | 98.00 | 79.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.12 | 113.40 | 58.72 | 106.02 | 855.80 | 0.00 | 0.00 | 0.00 |
February | 592.28 | 411.99 | 180.29 | 511.36 | 693.76 | 0.00 | 0.00 | 0.00 |
March | 1017.07 | 689.38 | 327.69 | 1005.71 | 537.17 | 0.00 | 0.00 | 0.00 |
April | 1240.80 | 771.90 | 468.90 | 1350.17 | 362.34 | 0.00 | 0.00 | 0.00 |
May | 1023.14 | 530.15 | 493.00 | 1145.89 | 195.01 | 0.00 | 0.00 | 0.00 |
June | 934.17 | 382.89 | 551.28 | 1072.27 | 104.68 | 0.00 | 0.00 | 0.00 |
July | 900.04 | 391.97 | 508.07 | 1053.25 | 114.47 | 0.00 | 0.00 | 0.00 |
August | 932.09 | 513.69 | 418.40 | 1073.82 | 171.98 | 0.00 | 0.00 | 0.00 |
September | 753.29 | 453.67 | 299.62 | 790.75 | 299.13 | 0.00 | 0.00 | 0.00 |
October | 542.38 | 344.12 | 198.25 | 494.67 | 478.30 | 0.00 | 0.00 | 0.00 |
November | 290.80 | 203.06 | 87.75 | 199.60 | 812.83 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.65 | 954.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.97 | 402.94 | 301.03 | 735.13 | 463.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.65 | 104.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.80 | 771.90 | 551.28 | 1350.17 | 954.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.12 | 113.40 | 58.72 | 106.02 | 855.80 | 0.00 | 0.00 | 0.00 |
February | 592.28 | 411.99 | 180.29 | 511.36 | 693.76 | 0.00 | 0.00 | 0.00 |
March | 1017.07 | 689.38 | 327.69 | 1005.71 | 537.17 | 0.00 | 0.00 | 0.00 |
April | 1240.80 | 771.90 | 468.90 | 1350.17 | 362.34 | 0.00 | 0.00 | 0.00 |
May | 1023.14 | 530.15 | 493.00 | 1145.89 | 195.01 | 0.00 | 0.00 | 0.00 |
June | 934.17 | 382.89 | 551.28 | 1072.27 | 104.68 | 0.00 | 0.00 | 0.00 |
July | 900.04 | 391.97 | 508.07 | 1053.25 | 114.47 | 0.00 | 0.00 | 0.00 |
August | 932.09 | 513.69 | 418.40 | 1073.82 | 171.98 | 0.00 | 0.00 | 0.00 |
September | 753.29 | 453.67 | 299.62 | 790.75 | 299.13 | 0.00 | 0.00 | 0.00 |
October | 542.38 | 344.12 | 198.25 | 494.67 | 478.30 | 0.00 | 0.00 | 0.00 |
November | 290.80 | 203.06 | 87.75 | 199.60 | 812.83 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.65 | 954.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.97 | 402.94 | 301.03 | 735.13 | 463.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.65 | 104.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.80 | 771.90 | 551.28 | 1350.17 | 954.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.11 | 113.39 | 58.72 | 106.01 | 855.74 | 0.00 | 0.00 | 0.00 |
February | 592.25 | 411.97 | 180.28 | 511.33 | 693.72 | 0.00 | 0.00 | 0.00 |
March | 1017.01 | 689.34 | 327.67 | 1005.65 | 537.14 | 0.00 | 0.00 | 0.00 |
April | 1240.72 | 771.85 | 468.87 | 1350.08 | 362.32 | 0.00 | 0.00 | 0.00 |
May | 1023.08 | 530.11 | 492.96 | 1145.81 | 195.00 | 0.00 | 0.00 | 0.00 |
June | 934.11 | 382.87 | 551.24 | 1072.20 | 104.67 | 0.00 | 0.00 | 0.00 |
July | 899.99 | 391.95 | 508.04 | 1053.19 | 114.46 | 0.00 | 0.00 | 0.00 |
August | 932.03 | 513.65 | 418.37 | 1073.75 | 171.97 | 0.00 | 0.00 | 0.00 |
September | 753.25 | 453.64 | 299.60 | 790.70 | 299.11 | 0.00 | 0.00 | 0.00 |
October | 542.34 | 344.10 | 198.24 | 494.63 | 478.27 | 0.00 | 0.00 | 0.00 |
November | 290.78 | 203.04 | 87.74 | 199.59 | 812.78 | 0.00 | 0.00 | 0.00 |
December | 51.62 | 36.38 | 15.23 | 11.65 | 954.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.92 | 402.92 | 301.01 | 735.08 | 463.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 51.62 | 36.38 | 15.23 | 11.65 | 104.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1240.72 | 771.85 | 551.24 | 1350.08 | 954.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 38.25 | 6.83 | 31.42 | 0.00 | 1881.72 | 0.00 | 0.00 | 0.00 |
February | 225.79 | 78.51 | 147.28 | 49.93 | 1586.87 | 0.00 | 0.00 | 0.00 |
March | 677.72 | 291.34 | 386.38 | 401.76 | 1140.45 | 0.00 | 0.00 | 0.00 |
April | 1608.16 | 833.36 | 774.80 | 1550.71 | 666.77 | 0.00 | 0.00 | 0.00 |
May | 1563.68 | 712.10 | 851.58 | 1597.01 | 341.44 | 0.00 | 0.00 | 0.00 |
June | 1713.72 | 730.68 | 983.04 | 1879.25 | 186.88 | 0.00 | 0.00 | 0.00 |
July | 1433.89 | 542.40 | 891.49 | 1584.31 | 204.95 | 0.00 | 0.00 | 0.00 |
August | 1178.50 | 499.04 | 679.46 | 1235.13 | 312.10 | 0.00 | 0.00 | 0.00 |
September | 713.22 | 298.67 | 414.55 | 587.08 | 570.58 | 0.00 | 0.00 | 0.00 |
October | 279.32 | 83.97 | 195.35 | 107.40 | 1038.70 | 0.00 | 0.00 | 0.00 |
November | 111.76 | 40.60 | 71.15 | 12.99 | 1808.83 | 0.00 | 0.00 | 0.00 |
December | 10.03 | 1.05 | 8.98 | 0.00 | 2009.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 798.22 | 343.94 | 454.29 | 753.40 | 975.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.03 | 1.05 | 8.98 | 0.00 | 186.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1713.72 | 833.36 | 983.04 | 1879.25 | 2009.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.51 | 0.27 | 1.24 | 0.00 | 74.40 | 0.00 | 0.00 | 0.00 |
February | 8.93 | 3.10 | 5.82 | 1.97 | 62.74 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 11.52 | 15.28 | 15.88 | 45.09 | 0.00 | 0.00 | 0.00 |
April | 63.59 | 32.95 | 30.63 | 61.31 | 26.36 | 0.00 | 0.00 | 0.00 |
May | 61.83 | 28.16 | 33.67 | 63.14 | 13.50 | 0.00 | 0.00 | 0.00 |
June | 67.76 | 28.89 | 38.87 | 74.30 | 7.39 | 0.00 | 0.00 | 0.00 |
July | 56.69 | 21.45 | 35.25 | 62.64 | 8.10 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 19.73 | 26.87 | 48.84 | 12.34 | 0.00 | 0.00 | 0.00 |
September | 28.20 | 11.81 | 16.39 | 23.21 | 22.56 | 0.00 | 0.00 | 0.00 |
October | 11.04 | 3.32 | 7.72 | 4.25 | 41.07 | 0.00 | 0.00 | 0.00 |
November | 4.42 | 1.61 | 2.81 | 0.51 | 71.52 | 0.00 | 0.00 | 0.00 |
December | 0.40 | 0.04 | 0.36 | 0.00 | 79.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.56 | 13.60 | 17.96 | 29.79 | 38.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.40 | 0.04 | 0.36 | 0.00 | 7.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.76 | 32.95 | 38.87 | 74.30 | 79.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 43.04 | 0.00 | 43.04 | 0.00 | 3003.88 | 0.00 | 0.00 | 0.00 |
February | 190.26 | 0.00 | 190.26 | 0.00 | 2685.95 | 0.00 | 0.00 | 0.00 |
March | 508.87 | 0.00 | 508.87 | 47.05 | 1983.60 | 0.00 | 0.00 | 0.00 |
April | 920.69 | 20.27 | 900.42 | 380.60 | 1062.03 | 0.00 | 0.00 | 0.00 |
May | 1411.11 | 224.35 | 1186.76 | 1079.07 | 481.25 | 0.00 | 0.00 | 0.00 |
June | 1841.11 | 409.44 | 1431.66 | 1775.23 | 225.17 | 0.00 | 0.00 | 0.00 |
July | 1545.21 | 251.16 | 1294.05 | 1520.74 | 275.53 | 0.00 | 0.00 | 0.00 |
August | 986.68 | 55.14 | 931.54 | 793.58 | 458.81 | 0.00 | 0.00 | 0.00 |
September | 550.46 | 0.55 | 549.90 | 209.11 | 919.13 | 0.00 | 0.00 | 0.00 |
October | 267.85 | 0.00 | 267.85 | 20.37 | 1697.70 | 0.00 | 0.00 | 0.00 |
November | 83.12 | 0.00 | 83.12 | 0.00 | 2943.71 | 0.00 | 0.00 | 0.00 |
December | 13.06 | 0.00 | 13.06 | 0.00 | 3165.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 699.29 | 80.43 | 618.85 | 488.31 | 1569.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.06 | 0.00 | 13.06 | 0.00 | 225.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.11 | 409.44 | 1431.66 | 1775.23 | 3165.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.59 | 23.79 | 51.80 | 7.05 | 1939.98 | 0.00 | 0.00 | 0.00 |
February | 417.63 | 199.28 | 218.35 | 221.10 | 1618.55 | 0.00 | 0.00 | 0.00 |
March | 1191.24 | 603.26 | 587.98 | 996.71 | 1189.29 | 0.00 | 0.00 | 0.00 |
April | 1637.41 | 828.36 | 809.06 | 1498.76 | 652.18 | 0.00 | 0.00 | 0.00 |
May | 2378.69 | 1339.08 | 1039.61 | 2558.27 | 342.01 | 0.00 | 0.00 | 0.00 |
June | 2188.45 | 1019.53 | 1168.91 | 2432.20 | 168.84 | 0.00 | 0.00 | 0.00 |
July | 2078.74 | 1006.64 | 1072.10 | 2366.19 | 194.76 | 0.00 | 0.00 | 0.00 |
August | 1646.50 | 800.73 | 845.77 | 1795.62 | 303.90 | 0.00 | 0.00 | 0.00 |
September | 1018.56 | 445.87 | 572.69 | 938.14 | 569.81 | 0.00 | 0.00 | 0.00 |
October | 538.01 | 215.88 | 322.13 | 383.02 | 1029.13 | 0.00 | 0.00 | 0.00 |
November | 114.44 | 39.99 | 74.45 | 9.89 | 1885.93 | 0.00 | 0.00 | 0.00 |
December | 16.35 | 3.91 | 12.44 | 0.00 | 2094.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1112.71 | 546.26 | 566.45 | 1106.50 | 995.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.35 | 3.91 | 12.44 | 0.00 | 168.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2378.69 | 1339.08 | 1168.91 | 2558.27 | 2094.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 516.35 | 340.19 | 176.16 | 302.12 | 2696.05 | 0.00 | 0.00 | 0.00 |
February | 1776.79 | 1235.94 | 540.85 | 1494.72 | 2171.29 | 0.00 | 0.00 | 0.00 |
March | 3051.12 | 2068.08 | 983.04 | 2947.69 | 1669.52 | 0.00 | 0.00 | 0.00 |
April | 3722.27 | 2315.63 | 1406.65 | 3996.86 | 1094.31 | 0.00 | 0.00 | 0.00 |
May | 3069.34 | 1590.39 | 1478.95 | 3389.64 | 597.40 | 0.00 | 0.00 | 0.00 |
June | 2802.42 | 1148.64 | 1653.78 | 3181.25 | 321.61 | 0.00 | 0.00 | 0.00 |
July | 2700.05 | 1175.87 | 1524.18 | 3138.09 | 343.85 | 0.00 | 0.00 | 0.00 |
August | 2796.18 | 1541.01 | 1255.16 | 3200.82 | 504.86 | 0.00 | 0.00 | 0.00 |
September | 2259.81 | 1360.97 | 898.84 | 2353.96 | 879.04 | 0.00 | 0.00 | 0.00 |
October | 1627.07 | 1032.33 | 594.74 | 1466.86 | 1434.78 | 0.00 | 0.00 | 0.00 |
November | 872.38 | 609.15 | 263.23 | 577.55 | 2519.08 | 0.00 | 0.00 | 0.00 |
December | 154.85 | 109.15 | 45.70 | 28.00 | 3005.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2111.84 | 1208.78 | 903.05 | 2174.82 | 1432.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 154.85 | 109.15 | 45.70 | 28.00 | 321.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3722.27 | 2315.63 | 1653.78 | 3996.86 | 3005.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.76 | 7.10 | 32.67 | 0.00 | 1978.26 | 0.00 | 0.00 | 0.00 |
February | 234.72 | 81.62 | 153.10 | 49.89 | 1680.42 | 0.00 | 0.00 | 0.00 |
March | 704.52 | 302.87 | 401.66 | 405.83 | 1215.02 | 0.00 | 0.00 | 0.00 |
April | 1671.76 | 866.32 | 805.44 | 1588.11 | 705.41 | 0.00 | 0.00 | 0.00 |
May | 1625.52 | 740.27 | 885.26 | 1634.68 | 368.02 | 0.00 | 0.00 | 0.00 |
June | 1781.49 | 759.58 | 1021.91 | 1936.93 | 200.26 | 0.00 | 0.00 | 0.00 |
July | 1490.59 | 563.85 | 926.74 | 1636.62 | 217.06 | 0.00 | 0.00 | 0.00 |
August | 1225.10 | 518.77 | 706.33 | 1280.03 | 321.92 | 0.00 | 0.00 | 0.00 |
September | 741.43 | 310.48 | 430.95 | 608.45 | 585.83 | 0.00 | 0.00 | 0.00 |
October | 290.37 | 87.29 | 203.07 | 111.02 | 1071.78 | 0.00 | 0.00 | 0.00 |
November | 116.18 | 42.21 | 73.97 | 13.35 | 1880.94 | 0.00 | 0.00 | 0.00 |
December | 10.43 | 1.10 | 9.33 | 0.00 | 2101.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 829.79 | 357.54 | 472.25 | 775.11 | 1023.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.43 | 1.10 | 9.33 | 0.00 | 200.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1781.49 | 866.32 | 1021.91 | 1936.93 | 2101.57 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.790680E+10 |
February | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.635850E+10 |
March | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.136553E+09 | 0.514379E+10 |
April | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.104131E+10 | 0.259798E+10 |
May | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.296620E+10 | 0.122265E+10 |
June | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.462732E+10 | 0.560422E+09 |
July | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.409894E+10 | 0.709033E+09 |
August | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.217203E+10 | 0.116280E+10 |
September | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.597913E+09 | 0.220646E+10 |
October | 0.717401E+09 | 0.00 | 0.717401E+09 | 69205385.80 | 0.433717E+10 |
November | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.747072E+10 |
December | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.833557E+10 |
Annual Sum or Average | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.157095E+11 | 0.480119E+11 |
Minimum of Months | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.560422E+09 |
Maximum of Months | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.462732E+10 | 0.833557E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 19396923.39 | 0.510919E+10 |
February | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.542860E+09 | 0.383144E+10 |
March | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.269408E+10 | 0.308307E+10 |
April | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.392362E+10 | 0.160562E+10 |
May | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.687981E+10 | 0.876262E+09 |
June | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.631501E+10 | 0.422207E+09 |
July | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.634694E+10 | 0.503342E+09 |
August | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.482934E+10 | 0.777164E+09 |
September | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.246911E+10 | 0.138715E+10 |
October | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.104859E+10 | 0.263039E+10 |
November | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 26812754.49 | 0.478808E+10 |
December | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.552315E+10 |
Annual Sum or Average | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.350956E+11 | 0.305371E+11 |
Minimum of Months | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.422207E+09 |
Maximum of Months | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.687981E+10 | 0.552315E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.817992E+09 | 0.709188E+10 |
February | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.364465E+10 | 0.512333E+10 |
March | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.794048E+10 | 0.431226E+10 |
April | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.104010E+11 | 0.269455E+10 |
May | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.910929E+10 | 0.151325E+10 |
June | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.826147E+10 | 0.795713E+09 |
July | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.842072E+10 | 0.881811E+09 |
August | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.859894E+10 | 0.128320E+10 |
September | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.615277E+10 | 0.213863E+10 |
October | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.397957E+10 | 0.365960E+10 |
November | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.151507E+10 | 0.637905E+10 |
December | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 76350836.32 | 0.791278E+10 |
Annual Sum or Average | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.689184E+11 | 0.437861E+11 |
Minimum of Months | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 76350836.32 | 0.795713E+09 |
Maximum of Months | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.104010E+11 | 0.791278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.521189E+10 |
February | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.123112E+09 | 0.397829E+10 |
March | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.109988E+10 | 0.314786E+10 |
April | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.414513E+10 | 0.173336E+10 |
May | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.440943E+10 | 0.929957E+09 |
June | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.503542E+10 | 0.495718E+09 |
July | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.439900E+10 | 0.556378E+09 |
August | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.345357E+10 | 0.816482E+09 |
September | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.160871E+10 | 0.142045E+10 |
October | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.310920E+09 | 0.273942E+10 |
November | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 35920734.45 | 0.477539E+10 |
December | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.554161E+10 |
Annual Sum or Average | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.246211E+11 | 0.313468E+11 |
Minimum of Months | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.495718E+09 |
Maximum of Months | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.503542E+10 | 0.554161E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38425449.03 | 0.00 | 38425449.03 | 0.00 | 0.264845E+10 |
February | 0.153421E+09 | 0.00 | 0.153421E+09 | 0.00 | 0.212216E+10 |
March | 0.454299E+09 | 0.00 | 0.454299E+09 | 47255575.88 | 0.172089E+10 |
April | 0.795442E+09 | 17514663.76 | 0.777928E+09 | 0.362178E+09 | 0.873562E+09 |
May | 0.125978E+10 | 0.200289E+09 | 0.105949E+10 | 0.101080E+10 | 0.406298E+09 |
June | 0.159064E+10 | 0.353742E+09 | 0.123690E+10 | 0.156255E+10 | 0.185230E+09 |
July | 0.137950E+10 | 0.224226E+09 | 0.115527E+10 | 0.137666E+10 | 0.238602E+09 |
August | 0.880868E+09 | 49229389.61 | 0.831639E+09 | 0.717549E+09 | 0.405888E+09 |
September | 0.475574E+09 | 478870.05 | 0.475095E+09 | 0.183270E+09 | 0.797372E+09 |
October | 0.239122E+09 | 0.00 | 0.239122E+09 | 18369002.05 | 0.152420E+10 |
November | 71814425.66 | 0.00 | 71814425.66 | 0.00 | 0.254197E+10 |
December | 11656275.08 | 0.00 | 11656275.08 | 0.00 | 0.280817E+10 |
Annual Sum or Average | 0.735054E+10 | 0.845480E+09 | 0.650506E+10 | 0.527863E+10 | 0.162728E+11 |
Minimum of Months | 11656275.08 | 0.00 | 11656275.08 | 0.00 | 0.185230E+09 |
Maximum of Months | 0.159064E+10 | 0.353742E+09 | 0.123690E+10 | 0.156255E+10 | 0.280817E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38427877.45 | 0.00 | 38427877.45 | 0.00 | 0.264862E+10 |
February | 0.153431E+09 | 0.00 | 0.153431E+09 | 0.00 | 0.212229E+10 |
March | 0.454328E+09 | 0.00 | 0.454328E+09 | 47258562.35 | 0.172100E+10 |
April | 0.795493E+09 | 17515770.65 | 0.777977E+09 | 0.362201E+09 | 0.873618E+09 |
May | 0.125986E+10 | 0.200302E+09 | 0.105956E+10 | 0.101087E+10 | 0.406324E+09 |
June | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156265E+10 | 0.185242E+09 |
July | 0.137959E+10 | 0.224240E+09 | 0.115535E+10 | 0.137674E+10 | 0.238617E+09 |
August | 0.880924E+09 | 49232500.83 | 0.831691E+09 | 0.717595E+09 | 0.405913E+09 |
September | 0.475604E+09 | 478900.31 | 0.475125E+09 | 0.183282E+09 | 0.797423E+09 |
October | 0.239138E+09 | 0.00 | 0.239138E+09 | 18370162.94 | 0.152430E+10 |
November | 71818964.21 | 0.00 | 71818964.21 | 0.00 | 0.254213E+10 |
December | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.280835E+10 |
Annual Sum or Average | 0.735101E+10 | 0.845533E+09 | 0.650547E+10 | 0.527896E+10 | 0.162738E+11 |
Minimum of Months | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.185242E+09 |
Maximum of Months | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156265E+10 | 0.280835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38427877.45 | 0.00 | 38427877.45 | 0.00 | 0.264862E+10 |
February | 0.153431E+09 | 0.00 | 0.153431E+09 | 0.00 | 0.212229E+10 |
March | 0.454328E+09 | 0.00 | 0.454328E+09 | 47258562.35 | 0.172100E+10 |
April | 0.795493E+09 | 17515770.65 | 0.777977E+09 | 0.362201E+09 | 0.873618E+09 |
May | 0.125986E+10 | 0.200302E+09 | 0.105956E+10 | 0.101087E+10 | 0.406324E+09 |
June | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156265E+10 | 0.185242E+09 |
July | 0.137959E+10 | 0.224240E+09 | 0.115535E+10 | 0.137674E+10 | 0.238617E+09 |
August | 0.880924E+09 | 49232500.83 | 0.831691E+09 | 0.717595E+09 | 0.405913E+09 |
September | 0.475604E+09 | 478900.31 | 0.475125E+09 | 0.183282E+09 | 0.797423E+09 |
October | 0.239138E+09 | 0.00 | 0.239138E+09 | 18370162.94 | 0.152430E+10 |
November | 71818964.21 | 0.00 | 71818964.21 | 0.00 | 0.254213E+10 |
December | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.280835E+10 |
Annual Sum or Average | 0.735101E+10 | 0.845533E+09 | 0.650547E+10 | 0.527896E+10 | 0.162738E+11 |
Minimum of Months | 11657011.74 | 0.00 | 11657011.74 | 0.00 | 0.185242E+09 |
Maximum of Months | 0.159074E+10 | 0.353765E+09 | 0.123698E+10 | 0.156265E+10 | 0.280835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.194753E+09 | 61291100.40 | 0.133462E+09 | 19182765.53 | 0.494038E+10 |
February | 0.971893E+09 | 0.463757E+09 | 0.508136E+09 | 0.524677E+09 | 0.369885E+10 |
March | 0.306923E+10 | 0.155429E+10 | 0.151494E+10 | 0.260803E+10 | 0.300415E+10 |
April | 0.408272E+10 | 0.206541E+10 | 0.201730E+10 | 0.379521E+10 | 0.159914E+10 |
May | 0.612871E+10 | 0.345013E+10 | 0.267857E+10 | 0.663837E+10 | 0.882800E+09 |
June | 0.545666E+10 | 0.254210E+10 | 0.291456E+10 | 0.610002E+10 | 0.419348E+09 |
July | 0.535589E+10 | 0.259362E+10 | 0.276227E+10 | 0.611456E+10 | 0.509115E+09 |
August | 0.424221E+10 | 0.206307E+10 | 0.217914E+10 | 0.463223E+10 | 0.804853E+09 |
September | 0.253967E+10 | 0.111172E+10 | 0.142795E+10 | 0.233590E+10 | 0.145957E+10 |
October | 0.138619E+10 | 0.556220E+09 | 0.829972E+09 | 0.989733E+09 | 0.268443E+10 |
November | 0.285349E+09 | 99710194.74 | 0.185639E+09 | 25139886.93 | 0.469810E+10 |
December | 42126734.43 | 10084357.56 | 32042376.87 | 0.00 | 0.536225E+10 |
Annual Sum or Average | 0.337554E+11 | 0.165714E+11 | 0.171840E+11 | 0.337831E+11 | 0.300630E+11 |
Minimum of Months | 42126734.43 | 10084357.56 | 32042376.87 | 0.00 | 0.419348E+09 |
Maximum of Months | 0.612871E+10 | 0.345013E+10 | 0.291456E+10 | 0.663837E+10 | 0.536225E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7700356.42 | 2423394.93 | 5276961.49 | 758469.28 | 0.195338E+09 |
February | 38427777.84 | 18336519.76 | 20091258.08 | 20745244.48 | 0.146249E+09 |
March | 0.121355E+09 | 61455198.34 | 59899307.21 | 0.103119E+09 | 0.118781E+09 |
April | 0.161427E+09 | 81664603.48 | 79762303.54 | 0.150059E+09 | 63228707.74 |
May | 0.242324E+09 | 0.136415E+09 | 0.105908E+09 | 0.262475E+09 | 34905114.95 |
June | 0.215751E+09 | 0.100512E+09 | 0.115239E+09 | 0.241189E+09 | 16580657.57 |
July | 0.211767E+09 | 0.102549E+09 | 0.109218E+09 | 0.241764E+09 | 20129939.95 |
August | 0.167733E+09 | 81571912.55 | 86161249.25 | 0.183154E+09 | 31823175.27 |
September | 0.100416E+09 | 43956269.44 | 56460008.77 | 92359317.30 | 57710192.83 |
October | 54808781.96 | 21992444.70 | 32816337.26 | 39133132.80 | 0.106140E+09 |
November | 11282449.76 | 3942451.33 | 7339998.43 | 994008.50 | 0.185759E+09 |
December | 1665653.15 | 398726.42 | 1266926.73 | 0.00 | 0.212019E+09 |
Annual Sum or Average | 0.133466E+10 | 0.655218E+09 | 0.679440E+09 | 0.133575E+10 | 0.118866E+10 |
Minimum of Months | 1665653.15 | 398726.42 | 1266926.73 | 0.00 | 16580657.57 |
Maximum of Months | 0.242324E+09 | 0.136415E+09 | 0.115239E+09 | 0.262475E+09 | 0.212019E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.461014E+09 | 0.303733E+09 | 0.157281E+09 | 0.283955E+09 | 0.229217E+10 |
February | 0.143285E+10 | 0.996696E+09 | 0.436156E+09 | 0.123708E+10 | 0.167834E+10 |
March | 0.272413E+10 | 0.184644E+10 | 0.877684E+09 | 0.269369E+10 | 0.143876E+10 |
April | 0.321615E+10 | 0.200077E+10 | 0.121538E+10 | 0.349964E+10 | 0.939193E+09 |
May | 0.274039E+10 | 0.141995E+10 | 0.132044E+10 | 0.306914E+10 | 0.522321E+09 |
June | 0.242137E+10 | 0.992457E+09 | 0.142891E+10 | 0.277932E+10 | 0.271331E+09 |
July | 0.241068E+10 | 0.104985E+10 | 0.136083E+10 | 0.282103E+10 | 0.306596E+09 |
August | 0.249650E+10 | 0.137586E+10 | 0.112064E+10 | 0.287611E+10 | 0.460636E+09 |
September | 0.195254E+10 | 0.117592E+10 | 0.776621E+09 | 0.204963E+10 | 0.775335E+09 |
October | 0.145270E+10 | 0.921697E+09 | 0.531001E+09 | 0.132491E+10 | 0.128107E+10 |
November | 0.753761E+09 | 0.526320E+09 | 0.227441E+09 | 0.517363E+09 | 0.210686E+10 |
December | 0.138259E+09 | 97453346.43 | 40805366.93 | 31206427.45 | 0.255762E+10 |
Annual Sum or Average | 0.222003E+11 | 0.127071E+11 | 0.949319E+10 | 0.231831E+11 | 0.146302E+11 |
Minimum of Months | 0.138259E+09 | 97453346.43 | 40805366.93 | 31206427.45 | 0.271331E+09 |
Maximum of Months | 0.321615E+10 | 0.200077E+10 | 0.142891E+10 | 0.349964E+10 | 0.255762E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.461014E+09 | 0.303733E+09 | 0.157281E+09 | 0.283955E+09 | 0.229217E+10 |
February | 0.143285E+10 | 0.996696E+09 | 0.436156E+09 | 0.123708E+10 | 0.167834E+10 |
March | 0.272413E+10 | 0.184644E+10 | 0.877684E+09 | 0.269369E+10 | 0.143876E+10 |
April | 0.321615E+10 | 0.200077E+10 | 0.121538E+10 | 0.349964E+10 | 0.939193E+09 |
May | 0.274039E+10 | 0.141995E+10 | 0.132044E+10 | 0.306914E+10 | 0.522321E+09 |
June | 0.242137E+10 | 0.992457E+09 | 0.142891E+10 | 0.277932E+10 | 0.271331E+09 |
July | 0.241068E+10 | 0.104985E+10 | 0.136083E+10 | 0.282103E+10 | 0.306596E+09 |
August | 0.249650E+10 | 0.137586E+10 | 0.112064E+10 | 0.287611E+10 | 0.460636E+09 |
September | 0.195254E+10 | 0.117592E+10 | 0.776621E+09 | 0.204963E+10 | 0.775335E+09 |
October | 0.145270E+10 | 0.921697E+09 | 0.531001E+09 | 0.132491E+10 | 0.128107E+10 |
November | 0.753761E+09 | 0.526320E+09 | 0.227441E+09 | 0.517363E+09 | 0.210686E+10 |
December | 0.138259E+09 | 97453346.43 | 40805366.93 | 31206427.45 | 0.255762E+10 |
Annual Sum or Average | 0.222003E+11 | 0.127071E+11 | 0.949319E+10 | 0.231831E+11 | 0.146302E+11 |
Minimum of Months | 0.138259E+09 | 97453346.43 | 40805366.93 | 31206427.45 | 0.271331E+09 |
Maximum of Months | 0.321615E+10 | 0.200077E+10 | 0.142891E+10 | 0.349964E+10 | 0.255762E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.460985E+09 | 0.303714E+09 | 0.157271E+09 | 0.283937E+09 | 0.229203E+10 |
February | 0.143276E+10 | 0.996633E+09 | 0.436129E+09 | 0.123701E+10 | 0.167824E+10 |
March | 0.272395E+10 | 0.184632E+10 | 0.877629E+09 | 0.269352E+10 | 0.143867E+10 |
April | 0.321594E+10 | 0.200064E+10 | 0.121530E+10 | 0.349942E+10 | 0.939134E+09 |
May | 0.274022E+10 | 0.141986E+10 | 0.132036E+10 | 0.306895E+10 | 0.522288E+09 |
June | 0.242121E+10 | 0.992394E+09 | 0.142882E+10 | 0.277914E+10 | 0.271314E+09 |
July | 0.241053E+10 | 0.104979E+10 | 0.136074E+10 | 0.282085E+10 | 0.306576E+09 |
August | 0.249635E+10 | 0.137577E+10 | 0.112057E+10 | 0.287593E+10 | 0.460607E+09 |
September | 0.195242E+10 | 0.117584E+10 | 0.776572E+09 | 0.204950E+10 | 0.775286E+09 |
October | 0.145261E+10 | 0.921638E+09 | 0.530967E+09 | 0.132483E+10 | 0.128099E+10 |
November | 0.753713E+09 | 0.526287E+09 | 0.227427E+09 | 0.517330E+09 | 0.210673E+10 |
December | 0.138250E+09 | 97447187.93 | 40802788.27 | 31204455.38 | 0.255746E+10 |
Annual Sum or Average | 0.221989E+11 | 0.127063E+11 | 0.949259E+10 | 0.231816E+11 | 0.146293E+11 |
Minimum of Months | 0.138250E+09 | 97447187.93 | 40802788.27 | 31204455.38 | 0.271314E+09 |
Maximum of Months | 0.321594E+10 | 0.200064E+10 | 0.142882E+10 | 0.349942E+10 | 0.255746E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102446E+09 | 18281573.28 | 84164624.60 | 0.00 | 0.503999E+10 |
February | 0.546239E+09 | 0.189943E+09 | 0.356296E+09 | 0.120785E+09 | 0.383895E+10 |
March | 0.181521E+10 | 0.780334E+09 | 0.103487E+10 | 0.107606E+10 | 0.305459E+10 |
April | 0.416836E+10 | 0.216007E+10 | 0.200829E+10 | 0.401945E+10 | 0.172827E+10 |
May | 0.418817E+10 | 0.190730E+10 | 0.228087E+10 | 0.427744E+10 | 0.914509E+09 |
June | 0.444196E+10 | 0.189393E+10 | 0.254803E+10 | 0.487101E+10 | 0.484402E+09 |
July | 0.384053E+10 | 0.145277E+10 | 0.238776E+10 | 0.424340E+10 | 0.548931E+09 |
August | 0.315649E+10 | 0.133662E+10 | 0.181987E+10 | 0.330816E+10 | 0.835919E+09 |
September | 0.184868E+10 | 0.774150E+09 | 0.107453E+10 | 0.152172E+10 | 0.147894E+10 |
October | 0.748135E+09 | 0.224916E+09 | 0.523219E+09 | 0.287658E+09 | 0.278205E+10 |
November | 0.289674E+09 | 0.105248E+09 | 0.184426E+09 | 33680315.91 | 0.468847E+10 |
December | 26872825.67 | 2824811.10 | 24048014.58 | 0.00 | 0.538094E+10 |
Annual Sum or Average | 0.251728E+11 | 0.108464E+11 | 0.143264E+11 | 0.237594E+11 | 0.307760E+11 |
Minimum of Months | 26872825.67 | 2824811.10 | 24048014.58 | 0.00 | 0.484402E+09 |
Maximum of Months | 0.444196E+10 | 0.216007E+10 | 0.254803E+10 | 0.487101E+10 | 0.538094E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 4050619.46 | 722834.60 | 3327784.86 | 0.00 | 0.199277E+09 |
February | 21597725.53 | 7510146.99 | 14087578.54 | 4775694.29 | 0.151789E+09 |
March | 71771443.10 | 30853587.48 | 40917855.62 | 42546334.14 | 0.120776E+09 |
April | 0.164813E+09 | 85406933.25 | 79405888.08 | 0.158925E+09 | 68334254.76 |
May | 0.165596E+09 | 75412635.58 | 90183438.78 | 0.169126E+09 | 36158877.52 |
June | 0.175631E+09 | 74884125.96 | 0.100747E+09 | 0.192595E+09 | 19152821.83 |
July | 0.151850E+09 | 57440944.61 | 94409550.51 | 0.167780E+09 | 21704251.75 |
August | 0.124804E+09 | 52848511.70 | 71955899.77 | 0.130801E+09 | 33051490.15 |
September | 73094754.77 | 30609083.16 | 42485671.61 | 60167283.27 | 58476152.98 |
October | 29580495.59 | 8892928.46 | 20687567.14 | 11373683.19 | 0.110000E+09 |
November | 11453402.50 | 4161403.46 | 7291999.05 | 1331674.66 | 0.185378E+09 |
December | 1062524.45 | 111690.13 | 950834.32 | 0.00 | 0.212757E+09 |
Annual Sum or Average | 0.995305E+09 | 0.428855E+09 | 0.566451E+09 | 0.939421E+09 | 0.121685E+10 |
Minimum of Months | 1062524.45 | 111690.13 | 950834.32 | 0.00 | 19152821.83 |
Maximum of Months | 0.175631E+09 | 85406933.25 | 0.100747E+09 | 0.192595E+09 | 0.212757E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.804560E+10 |
February | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.649784E+10 |
March | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.126016E+09 | 0.531288E+10 |
April | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.986515E+09 | 0.275278E+10 |
May | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.289018E+10 | 0.128899E+10 |
June | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.460140E+10 | 0.583648E+09 |
July | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.407314E+10 | 0.737969E+09 |
August | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.212552E+10 | 0.122887E+10 |
September | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.542008E+09 | 0.238239E+10 |
October | 0.717401E+09 | 0.00 | 0.717401E+09 | 54554187.65 | 0.454711E+10 |
November | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.763009E+10 |
December | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.847824E+10 |
Annual Sum or Average | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.153993E+11 | 0.494864E+11 |
Minimum of Months | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.583648E+09 |
Maximum of Months | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.460140E+10 | 0.847824E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 18894350.57 | 0.519603E+10 |
February | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.534875E+09 | 0.391560E+10 |
March | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.266960E+10 | 0.318541E+10 |
April | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.388478E+10 | 0.169044E+10 |
May | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.685208E+10 | 0.916049E+09 |
June | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.630427E+10 | 0.437641E+09 |
July | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.633760E+10 | 0.521654E+09 |
August | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.480938E+10 | 0.813970E+09 |
September | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.243166E+10 | 0.147695E+10 |
October | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.102588E+10 | 0.275642E+10 |
November | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 25646201.14 | 0.488834E+10 |
December | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.561081E+10 |
Annual Sum or Average | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.348947E+11 | 0.314093E+11 |
Minimum of Months | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.437641E+09 |
Maximum of Months | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.685208E+10 | 0.561081E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.809200E+09 | 0.722110E+10 |
February | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.361604E+10 | 0.525277E+10 |
March | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.789510E+10 | 0.447166E+10 |
April | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.103599E+11 | 0.283644E+10 |
May | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.907880E+10 | 0.160007E+10 |
June | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.824580E+10 | 0.833601E+09 |
July | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.840506E+10 | 0.920964E+09 |
August | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.857308E+10 | 0.135223E+10 |
September | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.610145E+10 | 0.227847E+10 |
October | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.392883E+10 | 0.384291E+10 |
November | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.149701E+10 | 0.652945E+10 |
December | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 74991540.43 | 0.804923E+10 |
Annual Sum or Average | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.685852E+11 | 0.451889E+11 |
Minimum of Months | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 74991540.43 | 0.833601E+09 |
Maximum of Months | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.103599E+11 | 0.804923E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.529858E+10 |
February | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.120698E+09 | 0.406528E+10 |
March | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.108697E+10 | 0.325432E+10 |
April | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.411639E+10 | 0.182843E+10 |
May | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.437832E+10 | 0.985717E+09 |
June | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.502053E+10 | 0.519078E+09 |
July | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.438353E+10 | 0.581360E+09 |
August | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.342844E+10 | 0.862219E+09 |
September | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.157710E+10 | 0.151847E+10 |
October | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.297344E+09 | 0.287065E+10 |
November | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 34604220.63 | 0.487540E+10 |
December | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.562884E+10 |
Annual Sum or Average | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.244439E+11 | 0.322883E+11 |
Minimum of Months | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.519078E+09 |
Maximum of Months | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.502053E+10 | 0.562884E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2952.06 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2628.35 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 50.98 | 1920.47 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 401.74 | 1002.31 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1107.45 | 456.49 | 1411.11 | 224.35 | 1186.76 | 0.00 | 0.00 |
June | 1785.23 | 216.21 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1530.37 | 264.72 | 1545.21 | 251.16 | 1294.05 | 0.00 | 0.00 |
August | 810.94 | 434.14 | 986.68 | 55.14 | 931.54 | 0.00 | 0.00 |
September | 230.68 | 851.26 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 25.84 | 1619.31 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2882.22 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3112.14 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 498.14 | 1522.45 | 699.29 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 216.21 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1785.23 | 3112.14 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.24 | 1907.55 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 224.40 | 1583.76 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 1005.85 | 1151.09 | 1191.24 | 603.26 | 587.98 | 0.00 | 0.00 |
April | 1513.74 | 619.45 | 1637.41 | 828.36 | 809.06 | 0.00 | 0.00 |
May | 2568.63 | 327.16 | 2378.69 | 1339.08 | 1039.61 | 0.00 | 0.00 |
June | 2436.35 | 162.89 | 2188.45 | 1019.53 | 1168.91 | 0.00 | 0.00 |
July | 2369.67 | 187.93 | 2078.74 | 1006.64 | 1072.10 | 0.00 | 0.00 |
August | 1803.07 | 290.16 | 1646.50 | 800.73 | 845.77 | 0.00 | 0.00 |
September | 952.59 | 535.17 | 1018.56 | 445.87 | 572.69 | 0.00 | 0.00 |
October | 391.50 | 982.07 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 10.34 | 1847.25 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2062.11 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1112.87 | 968.32 | 1112.71 | 546.26 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 162.89 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2568.63 | 2062.11 | 2378.69 | 1339.08 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.40 | 2647.81 | 516.35 | 340.19 | 176.16 | 0.00 | 0.00 |
February | 1506.55 | 2117.78 | 1776.79 | 1235.94 | 540.85 | 0.00 | 0.00 |
March | 2964.64 | 1610.01 | 3051.12 | 2068.08 | 983.04 | 0.00 | 0.00 |
April | 4012.75 | 1039.56 | 3722.27 | 2315.63 | 1406.65 | 0.00 | 0.00 |
May | 3401.02 | 564.98 | 3069.34 | 1590.39 | 1478.95 | 0.00 | 0.00 |
June | 3187.30 | 306.99 | 2802.42 | 1148.64 | 1653.78 | 0.00 | 0.00 |
July | 3143.94 | 329.23 | 2700.05 | 1175.87 | 1524.18 | 0.00 | 0.00 |
August | 3210.48 | 479.09 | 2796.18 | 1541.01 | 1255.16 | 0.00 | 0.00 |
September | 2373.75 | 825.09 | 2259.81 | 1360.97 | 898.84 | 0.00 | 0.00 |
October | 1485.80 | 1366.34 | 1627.07 | 1032.33 | 594.74 | 0.00 | 0.00 |
November | 584.52 | 2461.05 | 872.38 | 609.15 | 263.23 | 0.00 | 0.00 |
December | 28.51 | 2954.29 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2185.39 | 1388.45 | 2111.84 | 1208.78 | 903.05 | 0.00 | 0.00 |
Minimum of Months | 28.51 | 306.99 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 4012.75 | 2954.29 | 3722.27 | 2315.63 | 1653.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1945.90 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 50.89 | 1644.47 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 410.65 | 1175.28 | 704.52 | 302.87 | 401.66 | 0.00 | 0.00 |
April | 1599.20 | 668.73 | 1671.76 | 866.32 | 805.44 | 0.00 | 0.00 |
May | 1646.29 | 347.21 | 1625.52 | 740.27 | 885.26 | 0.00 | 0.00 |
June | 1942.68 | 191.25 | 1781.49 | 759.58 | 1021.91 | 0.00 | 0.00 |
July | 1642.40 | 207.73 | 1490.59 | 563.85 | 926.74 | 0.00 | 0.00 |
August | 1289.41 | 304.84 | 1225.10 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 620.64 | 548.01 | 741.43 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 116.08 | 1022.78 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.86 | 1842.36 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2069.00 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 780.73 | 994.00 | 829.79 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 191.25 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1942.68 | 2069.00 | 1781.49 | 866.32 | 1021.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2966.58 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2631.76 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 52.93 | 1927.61 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 419.20 | 1011.11 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1132.22 | 455.10 | 1411.10 | 224.35 | 1186.75 | 0.00 | 0.00 |
June | 1808.58 | 214.40 | 1841.10 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1542.02 | 267.26 | 1545.20 | 251.16 | 1294.04 | 0.00 | 0.00 |
August | 803.74 | 454.64 | 986.68 | 55.14 | 931.53 | 0.00 | 0.00 |
September | 212.13 | 922.92 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 20.58 | 1707.29 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2942.22 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3145.48 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 502.17 | 1548.09 | 699.28 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 214.40 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1808.58 | 3145.48 | 1841.10 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.45 | 1917.46 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 225.46 | 1589.41 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 1012.23 | 1165.97 | 1191.23 | 603.25 | 587.98 | 0.00 | 0.00 |
April | 1522.09 | 641.35 | 1637.40 | 828.35 | 809.05 | 0.00 | 0.00 |
May | 2576.48 | 342.63 | 2378.67 | 1339.06 | 1039.61 | 0.00 | 0.00 |
June | 2446.46 | 168.18 | 2188.43 | 1019.52 | 1168.91 | 0.00 | 0.00 |
July | 2373.18 | 197.60 | 2078.72 | 1006.63 | 1072.09 | 0.00 | 0.00 |
August | 1797.86 | 312.38 | 1646.48 | 800.72 | 845.77 | 0.00 | 0.00 |
September | 936.83 | 585.37 | 1018.55 | 445.86 | 572.69 | 0.00 | 0.00 |
October | 384.13 | 1041.88 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 10.08 | 1884.21 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2081.19 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1113.61 | 990.98 | 1112.70 | 546.25 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 168.18 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2576.48 | 2081.19 | 2378.67 | 1339.06 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.04 | 2567.34 | 516.36 | 340.20 | 176.16 | 0.00 | 0.00 |
February | 1534.05 | 2081.24 | 1776.81 | 1235.96 | 540.86 | 0.00 | 0.00 |
March | 3017.06 | 1611.48 | 3051.15 | 2068.10 | 983.05 | 0.00 | 0.00 |
April | 4050.42 | 1087.01 | 3722.31 | 2315.65 | 1406.66 | 0.00 | 0.00 |
May | 3437.59 | 585.02 | 3069.37 | 1590.41 | 1478.96 | 0.00 | 0.00 |
June | 3216.73 | 314.03 | 2802.45 | 1148.65 | 1653.80 | 0.00 | 0.00 |
July | 3159.69 | 343.40 | 2700.08 | 1175.89 | 1524.19 | 0.00 | 0.00 |
August | 3221.39 | 515.93 | 2796.20 | 1541.03 | 1255.17 | 0.00 | 0.00 |
September | 2372.20 | 897.36 | 2259.84 | 1360.99 | 898.85 | 0.00 | 0.00 |
October | 1483.97 | 1434.86 | 1627.09 | 1032.34 | 594.75 | 0.00 | 0.00 |
November | 598.79 | 2438.45 | 872.39 | 609.15 | 263.24 | 0.00 | 0.00 |
December | 34.95 | 2864.66 | 154.86 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2205.35 | 1391.74 | 2111.86 | 1208.80 | 903.06 | 0.00 | 0.00 |
Minimum of Months | 34.95 | 314.03 | 154.86 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 4050.42 | 2864.66 | 3722.31 | 2315.65 | 1653.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1956.12 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 51.90 | 1649.61 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 417.64 | 1185.55 | 704.52 | 302.86 | 401.65 | 0.00 | 0.00 |
April | 1612.03 | 693.13 | 1671.75 | 866.31 | 805.44 | 0.00 | 0.00 |
May | 1660.16 | 354.94 | 1625.51 | 740.26 | 885.25 | 0.00 | 0.00 |
June | 1953.55 | 194.27 | 1781.48 | 759.57 | 1021.90 | 0.00 | 0.00 |
July | 1646.95 | 213.05 | 1490.58 | 563.85 | 926.73 | 0.00 | 0.00 |
August | 1283.96 | 324.44 | 1225.09 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 610.30 | 593.14 | 741.42 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 111.65 | 1079.77 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.51 | 1880.34 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2088.45 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 783.19 | 1014.49 | 829.78 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 194.27 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1953.55 | 2088.45 | 1781.48 | 866.31 | 1021.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3003.88 | 43.04 | 0.00 | 43.04 | 0.00 | 0.00 |
February | 0.00 | 2685.95 | 190.26 | 0.00 | 190.26 | 0.00 | 0.00 |
March | 47.05 | 1983.60 | 508.87 | 0.00 | 508.87 | 0.00 | 0.00 |
April | 380.60 | 1062.03 | 920.69 | 20.27 | 900.42 | 0.00 | 0.00 |
May | 1079.07 | 481.25 | 1411.11 | 224.35 | 1186.76 | 0.00 | 0.00 |
June | 1775.23 | 225.17 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
July | 1520.74 | 275.53 | 1545.21 | 251.16 | 1294.05 | 0.00 | 0.00 |
August | 793.58 | 458.81 | 986.68 | 55.14 | 931.54 | 0.00 | 0.00 |
September | 209.11 | 919.13 | 550.46 | 0.55 | 549.90 | 0.00 | 0.00 |
October | 20.37 | 1697.70 | 267.85 | 0.00 | 267.85 | 0.00 | 0.00 |
November | 0.00 | 2943.71 | 83.12 | 0.00 | 83.12 | 0.00 | 0.00 |
December | 0.00 | 3165.41 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Annual Sum or Average | 488.31 | 1569.20 | 699.29 | 80.43 | 618.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 225.17 | 13.06 | 0.00 | 13.06 | 0.00 | 0.00 |
Maximum of Months | 1775.23 | 3165.41 | 1841.11 | 409.44 | 1431.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.05 | 1939.98 | 75.59 | 23.79 | 51.80 | 0.00 | 0.00 |
February | 221.10 | 1618.55 | 417.63 | 199.28 | 218.35 | 0.00 | 0.00 |
March | 996.71 | 1189.29 | 1191.24 | 603.26 | 587.98 | 0.00 | 0.00 |
April | 1498.76 | 652.18 | 1637.41 | 828.36 | 809.06 | 0.00 | 0.00 |
May | 2558.27 | 342.01 | 2378.69 | 1339.08 | 1039.61 | 0.00 | 0.00 |
June | 2432.20 | 168.84 | 2188.45 | 1019.53 | 1168.91 | 0.00 | 0.00 |
July | 2366.19 | 194.76 | 2078.74 | 1006.64 | 1072.10 | 0.00 | 0.00 |
August | 1795.62 | 303.90 | 1646.50 | 800.73 | 845.77 | 0.00 | 0.00 |
September | 938.14 | 569.81 | 1018.56 | 445.87 | 572.69 | 0.00 | 0.00 |
October | 383.02 | 1029.13 | 538.01 | 215.88 | 322.13 | 0.00 | 0.00 |
November | 9.89 | 1885.93 | 114.44 | 39.99 | 74.45 | 0.00 | 0.00 |
December | 0.00 | 2094.84 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Annual Sum or Average | 1106.50 | 995.98 | 1112.71 | 546.26 | 566.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 168.84 | 16.35 | 3.91 | 12.44 | 0.00 | 0.00 |
Maximum of Months | 2558.27 | 2094.84 | 2378.69 | 1339.08 | 1168.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.12 | 2696.05 | 516.35 | 340.19 | 176.16 | 0.00 | 0.00 |
February | 1494.72 | 2171.29 | 1776.79 | 1235.94 | 540.85 | 0.00 | 0.00 |
March | 2947.69 | 1669.52 | 3051.12 | 2068.08 | 983.04 | 0.00 | 0.00 |
April | 3996.86 | 1094.31 | 3722.27 | 2315.63 | 1406.65 | 0.00 | 0.00 |
May | 3389.64 | 597.40 | 3069.34 | 1590.39 | 1478.95 | 0.00 | 0.00 |
June | 3181.25 | 321.61 | 2802.42 | 1148.64 | 1653.78 | 0.00 | 0.00 |
July | 3138.09 | 343.85 | 2700.05 | 1175.87 | 1524.18 | 0.00 | 0.00 |
August | 3200.82 | 504.86 | 2796.18 | 1541.01 | 1255.16 | 0.00 | 0.00 |
September | 2353.96 | 879.04 | 2259.81 | 1360.97 | 898.84 | 0.00 | 0.00 |
October | 1466.86 | 1434.78 | 1627.07 | 1032.33 | 594.74 | 0.00 | 0.00 |
November | 577.55 | 2519.08 | 872.38 | 609.15 | 263.23 | 0.00 | 0.00 |
December | 28.00 | 3005.24 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Annual Sum or Average | 2174.82 | 1432.93 | 2111.84 | 1208.78 | 903.05 | 0.00 | 0.00 |
Minimum of Months | 28.00 | 321.61 | 154.85 | 109.15 | 45.70 | 0.00 | 0.00 |
Maximum of Months | 3996.86 | 3005.24 | 3722.27 | 2315.63 | 1653.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1978.26 | 39.76 | 7.10 | 32.67 | 0.00 | 0.00 |
February | 49.89 | 1680.42 | 234.72 | 81.62 | 153.10 | 0.00 | 0.00 |
March | 405.83 | 1215.02 | 704.52 | 302.87 | 401.66 | 0.00 | 0.00 |
April | 1588.11 | 705.41 | 1671.76 | 866.32 | 805.44 | 0.00 | 0.00 |
May | 1634.68 | 368.02 | 1625.52 | 740.27 | 885.26 | 0.00 | 0.00 |
June | 1936.93 | 200.26 | 1781.49 | 759.58 | 1021.91 | 0.00 | 0.00 |
July | 1636.62 | 217.06 | 1490.59 | 563.85 | 926.74 | 0.00 | 0.00 |
August | 1280.03 | 321.92 | 1225.10 | 518.77 | 706.33 | 0.00 | 0.00 |
September | 608.45 | 585.83 | 741.43 | 310.48 | 430.95 | 0.00 | 0.00 |
October | 111.02 | 1071.78 | 290.37 | 87.29 | 203.07 | 0.00 | 0.00 |
November | 13.35 | 1880.94 | 116.18 | 42.21 | 73.97 | 0.00 | 0.00 |
December | 0.00 | 2101.57 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Annual Sum or Average | 775.11 | 1023.86 | 829.79 | 357.54 | 472.25 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 200.26 | 10.43 | 1.10 | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1936.93 | 2101.57 | 1781.49 | 866.32 | 1021.91 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.790680E+10 | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.00 |
February | 0.00 | 0.635850E+10 | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.00 |
March | 0.136553E+09 | 0.514379E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.104131E+10 | 0.259798E+10 | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.00 | 0.00 |
May | 0.296620E+10 | 0.122265E+10 | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.00 | 0.00 |
June | 0.462732E+10 | 0.560422E+09 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
July | 0.409894E+10 | 0.709033E+09 | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.00 | 0.00 |
August | 0.217203E+10 | 0.116280E+10 | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.00 | 0.00 |
September | 0.597913E+09 | 0.220646E+10 | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.00 | 0.00 |
October | 69205385.80 | 0.433717E+10 | 0.717401E+09 | 0.00 | 0.717401E+09 | 0.00 | 0.00 |
November | 0.00 | 0.747072E+10 | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.00 |
December | 0.00 | 0.833557E+10 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.157095E+11 | 0.480119E+11 | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.560422E+09 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Maximum of Months | 0.462732E+10 | 0.833557E+10 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19396923.39 | 0.510919E+10 | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 0.00 | 0.00 |
February | 0.542860E+09 | 0.383144E+10 | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.00 | 0.00 |
March | 0.269408E+10 | 0.308307E+10 | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.00 | 0.00 |
April | 0.392362E+10 | 0.160562E+10 | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.00 | 0.00 |
May | 0.687981E+10 | 0.876262E+09 | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.00 | 0.00 |
June | 0.631501E+10 | 0.422207E+09 | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.00 | 0.00 |
July | 0.634694E+10 | 0.503342E+09 | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.00 | 0.00 |
August | 0.482934E+10 | 0.777164E+09 | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.00 | 0.00 |
September | 0.246911E+10 | 0.138715E+10 | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.00 | 0.00 |
October | 0.104859E+10 | 0.263039E+10 | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.00 | 0.00 |
November | 26812754.49 | 0.478808E+10 | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 0.00 | 0.00 |
December | 0.00 | 0.552315E+10 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.350956E+11 | 0.305371E+11 | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.422207E+09 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Maximum of Months | 0.687981E+10 | 0.552315E+10 | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.817992E+09 | 0.709188E+10 | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.00 | 0.00 |
February | 0.364465E+10 | 0.512333E+10 | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.00 | 0.00 |
March | 0.794048E+10 | 0.431226E+10 | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.00 | 0.00 |
April | 0.104010E+11 | 0.269455E+10 | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.00 | 0.00 |
May | 0.910929E+10 | 0.151325E+10 | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.00 | 0.00 |
June | 0.826147E+10 | 0.795713E+09 | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.00 | 0.00 |
July | 0.842072E+10 | 0.881811E+09 | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.00 | 0.00 |
August | 0.859894E+10 | 0.128320E+10 | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.00 | 0.00 |
September | 0.615277E+10 | 0.213863E+10 | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.00 | 0.00 |
October | 0.397957E+10 | 0.365960E+10 | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.00 | 0.00 |
November | 0.151507E+10 | 0.637905E+10 | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.00 | 0.00 |
December | 76350836.32 | 0.791278E+10 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.689184E+11 | 0.437861E+11 | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.00 | 0.00 |
Minimum of Months | 76350836.32 | 0.795713E+09 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104010E+11 | 0.791278E+10 | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.521189E+10 | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.00 |
February | 0.123112E+09 | 0.397829E+10 | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.00 | 0.00 |
March | 0.109988E+10 | 0.314786E+10 | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.00 | 0.00 |
April | 0.414513E+10 | 0.173336E+10 | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.00 | 0.00 |
May | 0.440943E+10 | 0.929957E+09 | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.00 | 0.00 |
June | 0.503542E+10 | 0.495718E+09 | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.00 | 0.00 |
July | 0.439900E+10 | 0.556378E+09 | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.00 | 0.00 |
August | 0.345357E+10 | 0.816482E+09 | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.00 | 0.00 |
September | 0.160871E+10 | 0.142045E+10 | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.00 | 0.00 |
October | 0.310920E+09 | 0.273942E+10 | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.00 | 0.00 |
November | 35920734.45 | 0.477539E+10 | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 0.00 | 0.00 |
December | 0.00 | 0.554161E+10 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.246211E+11 | 0.313468E+11 | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.495718E+09 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Maximum of Months | 0.503542E+10 | 0.554161E+10 | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.794568E+10 | 0.115281E+09 | 0.00 | 0.115281E+09 | 0.00 | 0.00 |
February | 0.00 | 0.636675E+10 | 0.460282E+09 | 0.00 | 0.460282E+09 | 0.00 | 0.00 |
March | 0.141773E+09 | 0.516290E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.108658E+10 | 0.262080E+10 | 0.238643E+10 | 52546205.06 | 0.233388E+10 | 0.00 | 0.00 |
May | 0.303253E+10 | 0.121895E+10 | 0.377950E+10 | 0.600892E+09 | 0.317860E+10 | 0.00 | 0.00 |
June | 0.468784E+10 | 0.555714E+09 | 0.477212E+10 | 0.106127E+10 | 0.371085E+10 | 0.00 | 0.00 |
July | 0.413014E+10 | 0.715836E+09 | 0.413867E+10 | 0.672705E+09 | 0.346597E+10 | 0.00 | 0.00 |
August | 0.215274E+10 | 0.121771E+10 | 0.264272E+10 | 0.147694E+09 | 0.249502E+10 | 0.00 | 0.00 |
September | 0.549833E+09 | 0.239222E+10 | 0.142678E+10 | 1436670.68 | 0.142534E+10 | 0.00 | 0.00 |
October | 55109327.92 | 0.457280E+10 | 0.717398E+09 | 0.00 | 0.717398E+09 | 0.00 | 0.00 |
November | 0.00 | 0.762622E+10 | 0.215452E+09 | 0.00 | 0.215452E+09 | 0.00 | 0.00 |
December | 0.00 | 0.842487E+10 | 34970298.56 | 0.00 | 34970298.56 | 0.00 | 0.00 |
Annual Sum or Average | 0.158365E+11 | 0.488204E+11 | 0.220526E+11 | 0.253655E+10 | 0.195160E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.555714E+09 | 34970298.56 | 0.00 | 34970298.56 | 0.00 | 0.00 |
Maximum of Months | 0.468784E+10 | 0.842487E+10 | 0.477212E+10 | 0.106127E+10 | 0.371085E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19941234.81 | 0.513572E+10 | 0.202453E+09 | 63714495.33 | 0.138739E+09 | 0.00 | 0.00 |
February | 0.545422E+09 | 0.384510E+10 | 0.101032E+10 | 0.482093E+09 | 0.528228E+09 | 0.00 | 0.00 |
March | 0.271115E+10 | 0.312293E+10 | 0.319058E+10 | 0.161574E+10 | 0.157484E+10 | 0.00 | 0.00 |
April | 0.394526E+10 | 0.166237E+10 | 0.424414E+10 | 0.214708E+10 | 0.209706E+10 | 0.00 | 0.00 |
May | 0.690085E+10 | 0.917705E+09 | 0.637103E+10 | 0.358655E+10 | 0.278448E+10 | 0.00 | 0.00 |
June | 0.634121E+10 | 0.435929E+09 | 0.567241E+10 | 0.264261E+10 | 0.302980E+10 | 0.00 | 0.00 |
July | 0.635633E+10 | 0.529245E+09 | 0.556766E+10 | 0.269617E+10 | 0.287149E+10 | 0.00 | 0.00 |
August | 0.481539E+10 | 0.836676E+09 | 0.440994E+10 | 0.214464E+10 | 0.226530E+10 | 0.00 | 0.00 |
September | 0.242826E+10 | 0.151728E+10 | 0.264009E+10 | 0.115567E+10 | 0.148441E+10 | 0.00 | 0.00 |
October | 0.102887E+10 | 0.279057E+10 | 0.144100E+10 | 0.578213E+09 | 0.862788E+09 | 0.00 | 0.00 |
November | 26133895.43 | 0.488386E+10 | 0.296632E+09 | 0.103653E+09 | 0.192979E+09 | 0.00 | 0.00 |
December | 0.00 | 0.557427E+10 | 43792387.58 | 10483083.98 | 33309303.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.351188E+11 | 0.312517E+11 | 0.350900E+11 | 0.172266E+11 | 0.178634E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.435929E+09 | 43792387.58 | 10483083.98 | 33309303.61 | 0.00 | 0.00 |
Maximum of Months | 0.690085E+10 | 0.557427E+10 | 0.637103E+10 | 0.358655E+10 | 0.302980E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851847E+09 | 0.687637E+10 | 0.138301E+10 | 0.911180E+09 | 0.471834E+09 | 0.00 | 0.00 |
February | 0.371117E+10 | 0.503493E+10 | 0.429847E+10 | 0.299003E+10 | 0.130844E+10 | 0.00 | 0.00 |
March | 0.808090E+10 | 0.431619E+10 | 0.817220E+10 | 0.553921E+10 | 0.263300E+10 | 0.00 | 0.00 |
April | 0.104987E+11 | 0.281752E+10 | 0.964824E+10 | 0.600217E+10 | 0.364606E+10 | 0.00 | 0.00 |
May | 0.920723E+10 | 0.156693E+10 | 0.822099E+10 | 0.425976E+10 | 0.396124E+10 | 0.00 | 0.00 |
June | 0.833777E+10 | 0.813977E+09 | 0.726395E+10 | 0.297731E+10 | 0.428664E+10 | 0.00 | 0.00 |
July | 0.846292E+10 | 0.919768E+09 | 0.723189E+10 | 0.314949E+10 | 0.408239E+10 | 0.00 | 0.00 |
August | 0.862816E+10 | 0.138188E+10 | 0.748935E+10 | 0.412749E+10 | 0.336186E+10 | 0.00 | 0.00 |
September | 0.614875E+10 | 0.232596E+10 | 0.585750E+10 | 0.352768E+10 | 0.232981E+10 | 0.00 | 0.00 |
October | 0.397466E+10 | 0.384313E+10 | 0.435800E+10 | 0.276503E+10 | 0.159297E+10 | 0.00 | 0.00 |
November | 0.155206E+10 | 0.632045E+10 | 0.226123E+10 | 0.157893E+10 | 0.682308E+09 | 0.00 | 0.00 |
December | 93617310.27 | 0.767270E+10 | 0.414767E+09 | 0.292354E+09 | 0.122414E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.695478E+11 | 0.438898E+11 | 0.665996E+11 | 0.381206E+11 | 0.284790E+11 | 0.00 | 0.00 |
Minimum of Months | 93617310.27 | 0.813977E+09 | 0.414767E+09 | 0.292354E+09 | 0.122414E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104987E+11 | 0.767270E+10 | 0.964824E+10 | 0.600217E+10 | 0.428664E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.523927E+10 | 0.106497E+09 | 19004407.89 | 87492409.46 | 0.00 | 0.00 |
February | 0.125561E+09 | 0.399074E+10 | 0.567836E+09 | 0.197453E+09 | 0.370383E+09 | 0.00 | 0.00 |
March | 0.111861E+10 | 0.317537E+10 | 0.188698E+10 | 0.811187E+09 | 0.107579E+10 | 0.00 | 0.00 |
April | 0.417838E+10 | 0.179660E+10 | 0.433318E+10 | 0.224548E+10 | 0.208770E+10 | 0.00 | 0.00 |
May | 0.444657E+10 | 0.950668E+09 | 0.435377E+10 | 0.198271E+10 | 0.237106E+10 | 0.00 | 0.00 |
June | 0.506360E+10 | 0.503555E+09 | 0.461759E+10 | 0.196882E+10 | 0.264878E+10 | 0.00 | 0.00 |
July | 0.441118E+10 | 0.570636E+09 | 0.399238E+10 | 0.151021E+10 | 0.248217E+10 | 0.00 | 0.00 |
August | 0.343896E+10 | 0.868971E+09 | 0.328129E+10 | 0.138947E+10 | 0.189183E+10 | 0.00 | 0.00 |
September | 0.158189E+10 | 0.153742E+10 | 0.192177E+10 | 0.804759E+09 | 0.111701E+10 | 0.00 | 0.00 |
October | 0.299032E+09 | 0.289205E+10 | 0.777715E+09 | 0.233808E+09 | 0.543907E+09 | 0.00 | 0.00 |
November | 35011990.58 | 0.487385E+10 | 0.301127E+09 | 0.109410E+09 | 0.191718E+09 | 0.00 | 0.00 |
December | 0.00 | 0.559369E+10 | 27935350.12 | 2936501.22 | 24998848.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.246988E+11 | 0.319928E+11 | 0.261681E+11 | 0.112752E+11 | 0.148928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.503555E+09 | 27935350.12 | 2936501.22 | 24998848.90 | 0.00 | 0.00 |
Maximum of Months | 0.506360E+10 | 0.559369E+10 | 0.461759E+10 | 0.224548E+10 | 0.264878E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.804560E+10 | 0.115282E+09 | 0.00 | 0.115282E+09 | 0.00 | 0.00 |
February | 0.00 | 0.649784E+10 | 0.460285E+09 | 0.00 | 0.460285E+09 | 0.00 | 0.00 |
March | 0.126016E+09 | 0.531288E+10 | 0.136296E+10 | 0.00 | 0.136296E+10 | 0.00 | 0.00 |
April | 0.986515E+09 | 0.275278E+10 | 0.238644E+10 | 52546477.35 | 0.233389E+10 | 0.00 | 0.00 |
May | 0.289018E+10 | 0.128899E+10 | 0.377951E+10 | 0.600895E+09 | 0.317862E+10 | 0.00 | 0.00 |
June | 0.460140E+10 | 0.583648E+09 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
July | 0.407314E+10 | 0.737969E+09 | 0.413869E+10 | 0.672709E+09 | 0.346598E+10 | 0.00 | 0.00 |
August | 0.212552E+10 | 0.122887E+10 | 0.264273E+10 | 0.147695E+09 | 0.249503E+10 | 0.00 | 0.00 |
September | 0.542008E+09 | 0.238239E+10 | 0.142679E+10 | 1436678.12 | 0.142535E+10 | 0.00 | 0.00 |
October | 54554187.65 | 0.454711E+10 | 0.717401E+09 | 0.00 | 0.717401E+09 | 0.00 | 0.00 |
November | 0.00 | 0.763009E+10 | 0.215453E+09 | 0.00 | 0.215453E+09 | 0.00 | 0.00 |
December | 0.00 | 0.847824E+10 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.153993E+11 | 0.494864E+11 | 0.220527E+11 | 0.253656E+10 | 0.195161E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.583648E+09 | 34970479.77 | 0.00 | 34970479.77 | 0.00 | 0.00 |
Maximum of Months | 0.460140E+10 | 0.847824E+10 | 0.477215E+10 | 0.106128E+10 | 0.371087E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18894350.57 | 0.519603E+10 | 0.202455E+09 | 63715139.11 | 0.138740E+09 | 0.00 | 0.00 |
February | 0.534875E+09 | 0.391560E+10 | 0.101033E+10 | 0.482098E+09 | 0.528232E+09 | 0.00 | 0.00 |
March | 0.266960E+10 | 0.318541E+10 | 0.319061E+10 | 0.161576E+10 | 0.157485E+10 | 0.00 | 0.00 |
April | 0.388478E+10 | 0.169044E+10 | 0.424418E+10 | 0.214710E+10 | 0.209708E+10 | 0.00 | 0.00 |
May | 0.685208E+10 | 0.916049E+09 | 0.637108E+10 | 0.358659E+10 | 0.278450E+10 | 0.00 | 0.00 |
June | 0.630427E+10 | 0.437641E+09 | 0.567246E+10 | 0.264263E+10 | 0.302982E+10 | 0.00 | 0.00 |
July | 0.633760E+10 | 0.521654E+09 | 0.556770E+10 | 0.269620E+10 | 0.287151E+10 | 0.00 | 0.00 |
August | 0.480938E+10 | 0.813970E+09 | 0.440998E+10 | 0.214466E+10 | 0.226532E+10 | 0.00 | 0.00 |
September | 0.243166E+10 | 0.147695E+10 | 0.264011E+10 | 0.115568E+10 | 0.148442E+10 | 0.00 | 0.00 |
October | 0.102588E+10 | 0.275642E+10 | 0.144101E+10 | 0.578218E+09 | 0.862795E+09 | 0.00 | 0.00 |
November | 25646201.14 | 0.488834E+10 | 0.296634E+09 | 0.103654E+09 | 0.192980E+09 | 0.00 | 0.00 |
December | 0.00 | 0.561081E+10 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.348947E+11 | 0.314093E+11 | 0.350903E+11 | 0.172268E+11 | 0.178636E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.437641E+09 | 43792763.19 | 10483189.90 | 33309573.29 | 0.00 | 0.00 |
Maximum of Months | 0.685208E+10 | 0.561081E+10 | 0.637108E+10 | 0.358659E+10 | 0.302982E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809200E+09 | 0.722110E+10 | 0.138300E+10 | 0.911169E+09 | 0.471828E+09 | 0.00 | 0.00 |
February | 0.361604E+10 | 0.525277E+10 | 0.429842E+10 | 0.298999E+10 | 0.130843E+10 | 0.00 | 0.00 |
March | 0.789510E+10 | 0.447166E+10 | 0.817212E+10 | 0.553914E+10 | 0.263297E+10 | 0.00 | 0.00 |
April | 0.103599E+11 | 0.283644E+10 | 0.964814E+10 | 0.600211E+10 | 0.364603E+10 | 0.00 | 0.00 |
May | 0.907880E+10 | 0.160007E+10 | 0.822091E+10 | 0.425971E+10 | 0.396121E+10 | 0.00 | 0.00 |
June | 0.824580E+10 | 0.833601E+09 | 0.726388E+10 | 0.297727E+10 | 0.428661E+10 | 0.00 | 0.00 |
July | 0.840506E+10 | 0.920964E+09 | 0.723182E+10 | 0.314945E+10 | 0.408236E+10 | 0.00 | 0.00 |
August | 0.857308E+10 | 0.135223E+10 | 0.748928E+10 | 0.412745E+10 | 0.336183E+10 | 0.00 | 0.00 |
September | 0.610145E+10 | 0.227847E+10 | 0.585744E+10 | 0.352764E+10 | 0.232979E+10 | 0.00 | 0.00 |
October | 0.392883E+10 | 0.384291E+10 | 0.435795E+10 | 0.276500E+10 | 0.159295E+10 | 0.00 | 0.00 |
November | 0.149701E+10 | 0.652945E+10 | 0.226121E+10 | 0.157891E+10 | 0.682301E+09 | 0.00 | 0.00 |
December | 74991540.43 | 0.804923E+10 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.685852E+11 | 0.451889E+11 | 0.665989E+11 | 0.381202E+11 | 0.284787E+11 | 0.00 | 0.00 |
Minimum of Months | 74991540.43 | 0.833601E+09 | 0.414763E+09 | 0.292350E+09 | 0.122412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.103599E+11 | 0.804923E+10 | 0.964814E+10 | 0.600211E+10 | 0.428661E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.529858E+10 | 0.106498E+09 | 19004597.74 | 87493026.84 | 0.00 | 0.00 |
February | 0.120698E+09 | 0.406528E+10 | 0.567841E+09 | 0.197455E+09 | 0.370386E+09 | 0.00 | 0.00 |
March | 0.108697E+10 | 0.325432E+10 | 0.188699E+10 | 0.811195E+09 | 0.107580E+10 | 0.00 | 0.00 |
April | 0.411639E+10 | 0.182843E+10 | 0.433321E+10 | 0.224550E+10 | 0.208771E+10 | 0.00 | 0.00 |
May | 0.437832E+10 | 0.985717E+09 | 0.435380E+10 | 0.198273E+10 | 0.237107E+10 | 0.00 | 0.00 |
June | 0.502053E+10 | 0.519078E+09 | 0.461763E+10 | 0.196884E+10 | 0.264879E+10 | 0.00 | 0.00 |
July | 0.438353E+10 | 0.581360E+09 | 0.399241E+10 | 0.151022E+10 | 0.248218E+10 | 0.00 | 0.00 |
August | 0.342844E+10 | 0.862219E+09 | 0.328132E+10 | 0.138948E+10 | 0.189184E+10 | 0.00 | 0.00 |
September | 0.157710E+10 | 0.151847E+10 | 0.192179E+10 | 0.804767E+09 | 0.111702E+10 | 0.00 | 0.00 |
October | 0.297344E+09 | 0.287065E+10 | 0.777721E+09 | 0.233811E+09 | 0.543910E+09 | 0.00 | 0.00 |
November | 34604220.63 | 0.487540E+10 | 0.301130E+09 | 0.109411E+09 | 0.191719E+09 | 0.00 | 0.00 |
December | 0.00 | 0.562884E+10 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Annual Sum or Average | 0.244439E+11 | 0.322883E+11 | 0.261683E+11 | 0.112754E+11 | 0.148929E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.519078E+09 | 27935562.83 | 2936530.56 | 24999032.28 | 0.00 | 0.00 |
Maximum of Months | 0.502053E+10 | 0.562884E+10 | 0.461763E+10 | 0.224550E+10 | 0.264879E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.634839E+10 | -0.557598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -772400740.2 | 58.99 | 0.00 | 0.00 |
February | 0.575279E+10 | -0.506757E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -685217769.9 | 58.99 | 0.00 | 0.00 |
March | 0.673719E+10 | -0.600003E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -737159317.5 | 58.99 | 0.00 | 0.00 |
April | 0.608480E+10 | -0.539872E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -686079740.2 | 58.98 | 0.00 | 0.00 |
May | 0.644134E+10 | -0.574804E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693299650.7 | 58.99 | 0.00 | 0.00 |
June | 0.616848E+10 | -0.550144E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667043579.0 | 58.98 | 0.00 | 0.00 |
July | 0.567406E+10 | -0.498728E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686775626.7 | 58.98 | 0.00 | 0.00 |
August | 0.607141E+10 | -0.538184E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689570728.0 | 58.98 | 0.00 | 0.00 |
September | 0.550170E+10 | -0.482759E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -674115236.1 | 58.98 | 0.00 | 0.00 |
October | 0.580621E+10 | -0.508455E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -721652585.8 | 58.98 | 0.00 | 0.00 |
November | 0.591228E+10 | -0.518044E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -731831100.8 | 58.98 | 0.00 | 0.00 |
December | 0.610717E+10 | -0.533728E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -769886241.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.726058E+11 | -0.640908E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.851503E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.550170E+10 | -0.600003E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -772400740.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.673719E+10 | -0.482759E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667043579.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:20 | 583.45 | 10.33 | 2.83 | 62.33 | 454.74 | 15.43 | 6.00 | 38.67 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:39 | 1940.03 | 21.99 | 76.33 | 167.83 | 2301.36 | 35.99 | 191.33 | 156.00 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5921.86 | 31.96 | 272.00 | 298.00 | 5264.15 | 33.94 | 286.17 | 281.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8501.27 | 30.66 | 283.67 | 379.17 | 1628.52 | 20.93 | 245.33 | 334.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:49 | 4098.36 | 20.70 | 114.67 | 447.67 | 1178.68 | 19.66 | 253.33 | 391.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-03:00 | 1936.52 | 16.65 | 0.00 | 471.33 | 1074.82 | 19.41 | 267.50 | 404.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:00 | 2326.75 | 17.29 | 15.67 | 468.50 | 1099.31 | 19.45 | 260.00 | 396.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 6058.86 | 26.09 | 241.50 | 403.17 | 1249.63 | 20.05 | 223.67 | 350.67 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4887.25 | 30.10 | 270.33 | 315.83 | 1669.95 | 21.63 | 188.33 | 277.33 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2624.55 | 29.30 | 205.33 | 232.50 | 2255.50 | 33.21 | 234.50 | 209.00 |
November | 135.83 | 0.67 | 0.62 | 01-NOV-09:50 | 712.67 | 11.83 | 0.00 | 113.33 | 813.02 | 29.70 | 94.17 | 86.50 |
December | 71.17 | 0.83 | 0.62 | 04-DEC-10:00 | 166.57 | 5.23 | 0.00 | 4.50 | 117.80 | 9.64 | 0.00 | 0.17 |
Annual Sum or Average | 4053.17 | 0.66 | 3960.04 | 22.82 | 1482.33 | 3364.17 | 1660.28 | 22.87 | 2250.33 | 2926.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 166.57 | 5.23 | 0.00 | 4.50 | 117.80 | 9.64 | 0.00 | 0.17 | |
Maximum of Months | 583.50 | 0.83 | 0.62 | 8501.27 | 31.96 | 283.67 | 471.33 | 5264.15 | 35.99 | 286.17 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.77 | 0.62 | 10-JAN-10:00 | 279.06 | 9.80 | 1.67 | 27.17 | 173.03 | 13.06 | 2.83 | 11.17 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 931.11 | 16.51 | 45.67 | 137.83 | 633.73 | 21.48 | 78.50 | 94.83 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2170.20 | 18.77 | 83.33 | 275.00 | 1474.01 | 22.24 | 131.00 | 234.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2964.01 | 20.71 | 109.67 | 382.17 | 1879.81 | 23.99 | 178.67 | 341.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 4037.70 | 21.72 | 180.33 | 457.33 | 2110.67 | 23.22 | 189.00 | 414.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3422.49 | 20.23 | 168.17 | 490.83 | 1538.53 | 22.07 | 191.00 | 431.33 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3435.79 | 20.41 | 173.00 | 476.00 | 1799.38 | 22.15 | 192.67 | 419.50 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:30 | 2809.54 | 20.44 | 143.67 | 404.17 | 1441.13 | 22.07 | 158.50 | 354.33 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2105.71 | 19.00 | 104.67 | 294.83 | 1133.13 | 21.04 | 121.33 | 248.67 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1104.02 | 17.64 | 73.50 | 207.17 | 683.84 | 20.60 | 82.17 | 149.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 382.04 | 15.42 | 33.83 | 65.67 | 226.07 | 18.25 | 35.50 | 18.50 |
December | 71.17 | 0.90 | 0.69 | 04-DEC-11:30 | 93.94 | 5.67 | 0.00 | 0.00 | 55.28 | 8.29 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2648.12 | 19.25 | 1117.50 | 3218.17 | 1426.52 | 21.62 | 1361.17 | 2717.83 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 93.94 | 5.67 | 0.00 | 0.00 | 55.28 | 8.29 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.69 | 4037.70 | 21.72 | 180.33 | 490.83 | 2110.67 | 23.99 | 192.67 | 431.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 21-JAN-12:30 | 161.43 | 7.13 | 0.00 | 3.33 | 94.45 | 10.02 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-11:00 | 355.35 | 11.40 | 0.00 | 100.17 | 210.32 | 14.35 | 0.00 | 19.50 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 654.75 | 14.77 | 0.00 | 265.17 | 389.41 | 17.60 | 0.83 | 188.17 |
April | 421.83 | 0.63 | 0.62 | 01-APR-06:00 | 861.00 | 17.09 | 0.00 | 393.17 | 536.44 | 19.91 | 24.17 | 333.67 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1046.97 | 20.06 | 104.83 | 497.67 | 642.02 | 23.47 | 193.33 | 465.83 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1280.32 | 21.38 | 150.67 | 532.83 | 741.59 | 23.27 | 250.17 | 496.50 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1162.06 | 21.05 | 138.83 | 515.17 | 650.58 | 22.08 | 184.83 | 459.83 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 894.18 | 18.79 | 63.83 | 421.50 | 510.43 | 19.39 | 52.17 | 356.33 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 641.76 | 14.88 | 0.00 | 290.83 | 371.28 | 17.56 | 1.50 | 189.00 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:40 | 449.01 | 12.86 | 0.00 | 180.67 | 249.46 | 15.59 | 0.00 | 24.83 |
November | 135.83 | 0.79 | 0.62 | 01-NOV-09:00 | 216.13 | 8.88 | 0.00 | 20.67 | 124.55 | 12.05 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.81 | 04-DEC-11:30 | 63.60 | 2.80 | 0.00 | 0.00 | 37.65 | 5.21 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 848.93 | 17.11 | 458.17 | 3221.17 | 496.78 | 19.37 | 707.00 | 2533.67 | ||
Minimum of Months | 71.17 | 0.63 | 0.62 | 63.60 | 2.80 | 0.00 | 0.00 | 37.65 | 5.21 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.81 | 1280.32 | 21.38 | 150.67 | 532.83 | 741.59 | 23.47 | 250.17 | 496.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 21-JAN-11:39 | 235.33 | 9.24 | 1.33 | 19.00 | 142.97 | 12.55 | 1.83 | 4.17 |
February | 205.83 | 0.67 | 0.62 | 01-FEB-11:20 | 756.31 | 16.64 | 44.67 | 146.50 | 493.97 | 21.70 | 68.33 | 79.33 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1674.06 | 18.60 | 75.67 | 285.50 | 1054.45 | 21.94 | 102.17 | 247.67 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3473.23 | 22.27 | 139.50 | 382.67 | 1747.26 | 22.62 | 141.67 | 340.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2708.75 | 18.95 | 117.83 | 474.00 | 1354.54 | 20.03 | 72.17 | 427.17 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:49 | 2889.44 | 18.37 | 111.33 | 500.17 | 1459.92 | 19.75 | 64.33 | 446.33 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2496.78 | 18.32 | 114.50 | 492.67 | 1292.60 | 19.63 | 78.50 | 434.00 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2259.66 | 19.40 | 114.50 | 417.17 | 1374.17 | 21.51 | 115.00 | 367.17 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1765.43 | 19.75 | 101.00 | 310.17 | 1103.98 | 22.83 | 111.33 | 254.00 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:49 | 878.88 | 17.39 | 67.50 | 210.00 | 526.68 | 20.74 | 65.17 | 130.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 365.97 | 14.97 | 33.83 | 61.83 | 248.14 | 19.98 | 45.17 | 24.17 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 81.83 | 4.96 | 0.00 | 0.00 | 47.62 | 7.59 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2156.12 | 18.36 | 921.67 | 3299.67 | 1167.38 | 20.49 | 865.67 | 2754.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 81.83 | 4.96 | 0.00 | 0.00 | 47.62 | 7.59 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 3473.23 | 22.27 | 139.50 | 500.17 | 1747.26 | 22.83 | 141.67 | 446.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:30 | 513.96 | 5.41 | 0.00 | 57.33 | 413.70 | 11.56 | 5.83 | 35.50 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:50 | 1258.03 | 9.28 | 0.00 | 165.33 | 2136.53 | 33.59 | 171.17 | 150.67 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5694.26 | 31.10 | 266.83 | 295.50 | 5122.54 | 33.50 | 280.00 | 279.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8324.36 | 29.63 | 283.67 | 375.83 | 1501.12 | 18.41 | 30.83 | 330.17 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:00 | 3979.03 | 18.14 | 114.67 | 444.50 | 1095.63 | 17.29 | 10.67 | 385.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-04:10 | 1830.72 | 13.13 | 0.00 | 466.17 | 1005.40 | 16.94 | 8.33 | 398.17 |
July | 562.83 | 0.66 | 0.62 | 01-JUL-03:00 | 2217.91 | 13.85 | 15.67 | 462.83 | 1026.79 | 16.94 | 9.83 | 389.83 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 5929.27 | 24.48 | 238.50 | 399.17 | 1158.58 | 17.44 | 10.67 | 346.50 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4705.22 | 28.96 | 261.67 | 314.17 | 1574.22 | 19.06 | 38.67 | 272.50 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2430.15 | 25.39 | 170.83 | 228.33 | 2148.31 | 32.12 | 224.83 | 206.33 |
November | 135.83 | 0.68 | 0.62 | 01-NOV-09:50 | 647.60 | 7.24 | 0.00 | 108.00 | 653.25 | 21.78 | 56.00 | 76.33 |
December | 71.17 | 0.84 | 0.62 | 04-DEC-11:09 | 151.70 | 1.82 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 3794.12 | 19.79 | 1351.83 | 3319.17 | 1563.38 | 20.39 | 846.83 | 2870.50 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 151.70 | 1.82 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.84 | 0.62 | 8324.36 | 31.10 | 283.67 | 466.17 | 5122.54 | 33.59 | 280.00 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 10-JAN-11:09 | 266.88 | 9.23 | 1.67 | 25.33 | 164.89 | 12.67 | 1.83 | 10.33 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 894.15 | 16.06 | 45.67 | 134.33 | 539.80 | 19.10 | 56.33 | 87.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2088.08 | 18.36 | 83.17 | 272.83 | 1401.89 | 21.95 | 123.50 | 230.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2868.20 | 20.29 | 109.67 | 379.00 | 1806.49 | 23.80 | 166.83 | 337.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 3807.04 | 19.98 | 150.17 | 454.33 | 2031.07 | 23.06 | 175.17 | 409.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3328.75 | 19.86 | 167.83 | 487.33 | 1470.94 | 21.91 | 172.33 | 426.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3327.00 | 19.95 | 171.00 | 471.50 | 1730.10 | 21.98 | 171.17 | 414.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:40 | 2622.07 | 18.72 | 116.17 | 401.17 | 1377.03 | 21.89 | 139.33 | 349.67 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2035.92 | 18.61 | 104.33 | 291.33 | 1081.81 | 20.82 | 116.00 | 242.17 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1063.91 | 17.22 | 73.00 | 203.50 | 655.20 | 20.38 | 80.50 | 144.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 366.81 | 14.96 | 33.83 | 61.33 | 215.95 | 17.99 | 35.17 | 15.33 |
December | 71.17 | 0.91 | 0.70 | 04-DEC-11:30 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.67 | 2538.70 | 18.50 | 1056.50 | 3182.00 | 1363.82 | 21.31 | 1238.17 | 2667.00 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.70 | 3807.04 | 20.29 | 171.00 | 487.33 | 2031.07 | 23.80 | 175.17 | 426.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 28-JAN-11:30 | 152.90 | 3.74 | 0.00 | 2.00 | 89.77 | 7.36 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-12:09 | 337.82 | 7.88 | 0.00 | 89.17 | 200.84 | 11.84 | 0.00 | 14.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 624.88 | 11.54 | 0.00 | 261.83 | 373.52 | 15.44 | 0.00 | 177.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 814.62 | 14.09 | 0.00 | 388.00 | 516.11 | 18.12 | 1.50 | 326.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1001.63 | 17.50 | 104.00 | 494.83 | 612.79 | 20.99 | 116.00 | 459.67 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1212.79 | 17.75 | 124.17 | 526.33 | 693.46 | 20.69 | 111.00 | 490.67 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1072.76 | 16.63 | 93.33 | 508.67 | 629.13 | 20.41 | 103.83 | 455.17 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 855.48 | 16.03 | 62.83 | 417.83 | 512.48 | 19.52 | 68.00 | 352.17 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 613.21 | 11.58 | 0.00 | 287.00 | 356.04 | 15.40 | 0.00 | 174.50 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:49 | 428.89 | 9.18 | 0.00 | 172.67 | 238.55 | 13.05 | 0.00 | 19.67 |
November | 135.83 | 0.80 | 0.62 | 01-NOV-09:00 | 205.17 | 5.19 | 0.00 | 15.17 | 118.55 | 9.25 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 803.62 | 13.78 | 384.33 | 3163.50 | 476.87 | 17.40 | 400.33 | 2469.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 1212.79 | 17.75 | 124.17 | 526.33 | 693.46 | 20.99 | 116.00 | 490.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.62 | 21-JAN-11:50 | 225.36 | 8.91 | 1.33 | 17.50 | 136.49 | 12.56 | 1.83 | 3.67 |
February | 205.83 | 0.68 | 0.62 | 01-FEB-11:30 | 728.10 | 16.31 | 44.67 | 142.67 | 474.04 | 21.64 | 68.33 | 74.50 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1616.85 | 18.25 | 75.33 | 283.17 | 1011.98 | 21.83 | 100.83 | 242.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3380.61 | 21.92 | 139.50 | 378.50 | 1678.08 | 22.49 | 139.83 | 336.00 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2633.25 | 18.56 | 117.83 | 469.33 | 1297.09 | 19.87 | 68.67 | 421.50 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:00 | 2812.42 | 17.96 | 111.17 | 496.83 | 1402.49 | 19.57 | 59.33 | 438.83 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2411.62 | 17.92 | 114.50 | 487.83 | 1236.55 | 19.47 | 74.67 | 425.67 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2141.41 | 19.02 | 114.33 | 412.33 | 1316.76 | 21.37 | 113.33 | 360.00 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1711.67 | 19.40 | 101.00 | 308.17 | 1064.22 | 22.72 | 110.50 | 248.33 |
October | 265.50 | 0.66 | 0.62 | 01-OCT-07:49 | 849.02 | 17.05 | 67.50 | 205.67 | 503.94 | 20.32 | 62.50 | 122.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 349.87 | 14.69 | 33.83 | 57.67 | 220.06 | 17.76 | 34.50 | 18.50 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 78.10 | 4.78 | 0.00 | 0.00 | 45.26 | 7.69 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2086.14 | 17.99 | 921.00 | 3259.67 | 1119.18 | 20.27 | 834.33 | 2691.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 78.10 | 4.78 | 0.00 | 0.00 | 45.26 | 7.69 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 3380.61 | 21.92 | 139.50 | 496.83 | 1678.08 | 22.72 | 139.83 | 438.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.62 | 03-JAN-11:30 | 513.99 | 5.41 | 0.00 | 57.33 | 413.70 | 11.56 | 5.83 | 35.50 |
February | 205.83 | 0.66 | 0.62 | 01-FEB-10:50 | 1258.09 | 9.28 | 0.00 | 165.33 | 2136.50 | 33.59 | 171.17 | 150.67 |
March | 329.50 | 0.64 | 0.62 | 01-MAR-09:20 | 5694.31 | 31.10 | 266.83 | 295.50 | 5122.46 | 33.50 | 280.00 | 279.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 8324.35 | 29.63 | 283.67 | 375.83 | 1501.02 | 18.41 | 30.83 | 330.17 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:00 | 3978.96 | 18.14 | 114.67 | 444.50 | 1095.55 | 17.29 | 10.67 | 385.17 |
June | 583.50 | 0.66 | 0.62 | 01-JUN-04:10 | 1830.65 | 13.13 | 0.00 | 466.17 | 1005.32 | 16.94 | 8.33 | 398.17 |
July | 562.83 | 0.66 | 0.62 | 01-JUL-03:00 | 2217.83 | 13.85 | 15.67 | 462.83 | 1026.71 | 16.95 | 9.83 | 389.83 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:49 | 5929.22 | 24.48 | 238.50 | 399.17 | 1158.49 | 17.44 | 10.67 | 346.50 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:40 | 4705.22 | 28.96 | 261.67 | 314.17 | 1574.14 | 19.06 | 38.67 | 272.50 |
October | 265.50 | 0.65 | 0.62 | 01-OCT-07:40 | 2430.17 | 25.39 | 170.83 | 228.33 | 2148.27 | 32.12 | 224.83 | 206.33 |
November | 135.83 | 0.68 | 0.62 | 01-NOV-09:50 | 647.63 | 7.24 | 0.00 | 108.00 | 653.24 | 21.78 | 56.00 | 76.33 |
December | 71.17 | 0.84 | 0.62 | 04-DEC-11:09 | 151.71 | 1.83 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 3794.10 | 19.79 | 1351.83 | 3319.17 | 1563.31 | 20.39 | 846.83 | 2870.50 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 151.71 | 1.83 | 0.00 | 2.00 | 109.87 | 5.70 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.84 | 0.62 | 8324.35 | 31.10 | 283.67 | 466.17 | 5122.46 | 33.59 | 280.00 | 398.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.78 | 0.62 | 10-JAN-11:09 | 266.88 | 9.23 | 1.67 | 25.33 | 164.88 | 12.67 | 1.83 | 10.33 |
February | 205.83 | 0.69 | 0.62 | 01-FEB-10:50 | 894.16 | 16.06 | 45.67 | 134.33 | 539.78 | 19.11 | 56.33 | 87.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:20 | 2088.10 | 18.36 | 83.17 | 272.83 | 1401.85 | 21.95 | 123.50 | 230.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-06:49 | 2868.22 | 20.29 | 109.67 | 379.00 | 1806.44 | 23.80 | 166.83 | 337.67 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:40 | 3807.05 | 19.98 | 150.17 | 454.33 | 2031.01 | 23.06 | 175.50 | 409.00 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:09 | 3328.73 | 19.86 | 167.83 | 487.33 | 1470.87 | 21.91 | 172.50 | 426.83 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:39 | 3326.98 | 19.95 | 171.00 | 471.50 | 1730.03 | 21.98 | 171.33 | 414.17 |
August | 467.17 | 0.65 | 0.62 | 01-AUG-04:40 | 2622.06 | 18.72 | 116.17 | 401.17 | 1376.97 | 21.89 | 139.50 | 349.67 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:19 | 2035.92 | 18.61 | 104.33 | 291.33 | 1081.76 | 20.82 | 116.17 | 242.17 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:30 | 1063.90 | 17.22 | 73.00 | 203.50 | 655.17 | 20.38 | 80.50 | 144.50 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:50 | 366.81 | 14.96 | 33.83 | 61.33 | 215.94 | 18.00 | 35.17 | 15.33 |
December | 71.17 | 0.91 | 0.70 | 04-DEC-11:30 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.67 | 2538.69 | 18.50 | 1056.50 | 3182.00 | 1363.77 | 21.31 | 1239.17 | 2667.00 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 89.50 | 5.21 | 0.00 | 0.00 | 52.45 | 7.99 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.70 | 3807.05 | 20.29 | 171.00 | 487.33 | 2031.01 | 23.80 | 175.50 | 426.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.62 | 28-JAN-11:30 | 152.90 | 3.74 | 0.00 | 2.00 | 89.77 | 7.36 | 0.00 | 0.00 |
February | 205.83 | 0.71 | 0.62 | 01-FEB-12:09 | 337.82 | 7.89 | 0.00 | 89.17 | 200.82 | 11.84 | 0.00 | 14.33 |
March | 329.50 | 0.66 | 0.62 | 01-MAR-09:50 | 624.88 | 11.54 | 0.00 | 261.83 | 373.50 | 15.44 | 0.00 | 177.00 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 814.62 | 14.09 | 0.00 | 388.00 | 516.08 | 18.12 | 1.50 | 326.17 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:40 | 1001.62 | 17.51 | 104.00 | 494.83 | 612.76 | 20.99 | 116.00 | 459.67 |
June | 583.50 | 0.64 | 0.62 | 01-JUN-03:09 | 1212.78 | 17.75 | 124.17 | 526.33 | 693.42 | 20.69 | 111.00 | 490.67 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:39 | 1072.74 | 16.63 | 93.33 | 508.67 | 629.09 | 20.41 | 103.83 | 455.17 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:40 | 855.47 | 16.03 | 62.83 | 417.83 | 512.45 | 19.52 | 68.00 | 352.17 |
September | 356.33 | 0.66 | 0.62 | 01-SEP-06:40 | 613.20 | 11.59 | 0.00 | 287.00 | 356.02 | 15.40 | 0.00 | 174.50 |
October | 265.50 | 0.67 | 0.62 | 01-OCT-07:49 | 428.88 | 9.18 | 0.00 | 172.67 | 238.54 | 13.05 | 0.00 | 19.67 |
November | 135.83 | 0.80 | 0.62 | 01-NOV-09:00 | 205.17 | 5.19 | 0.00 | 15.17 | 118.54 | 9.26 | 0.00 | 0.00 |
December | 71.17 | 0.94 | 0.82 | 04-DEC-11:30 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 803.61 | 13.78 | 384.33 | 3163.50 | 476.84 | 17.40 | 400.33 | 2469.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 60.04 | 0.66 | 0.00 | 0.00 | 35.68 | 3.02 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.94 | 0.82 | 1212.78 | 17.75 | 124.17 | 526.33 | 693.42 | 20.99 | 116.00 | 490.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.62 | 21-JAN-11:50 | 225.36 | 8.91 | 1.33 | 17.50 | 136.48 | 12.56 | 1.83 | 3.67 |
February | 205.83 | 0.68 | 0.62 | 01-FEB-11:30 | 728.10 | 16.31 | 44.67 | 142.67 | 474.02 | 21.64 | 68.33 | 74.50 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:50 | 1616.85 | 18.25 | 75.33 | 283.17 | 1011.95 | 21.83 | 100.83 | 242.17 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:30 | 3380.62 | 21.92 | 139.50 | 378.50 | 1678.03 | 22.49 | 140.00 | 336.00 |
May | 545.00 | 0.64 | 0.62 | 01-MAY-04:00 | 2633.25 | 18.56 | 117.83 | 469.33 | 1297.04 | 19.87 | 68.83 | 421.50 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:00 | 2812.40 | 17.96 | 111.17 | 496.83 | 1402.43 | 19.57 | 59.33 | 438.83 |
July | 562.83 | 0.64 | 0.62 | 01-JUL-03:00 | 2411.59 | 17.92 | 114.50 | 487.83 | 1236.49 | 19.47 | 74.67 | 425.67 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:00 | 2141.40 | 19.02 | 114.33 | 412.33 | 1316.71 | 21.37 | 113.33 | 360.00 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:49 | 1711.67 | 19.40 | 101.00 | 308.17 | 1064.18 | 22.72 | 110.50 | 248.33 |
October | 265.50 | 0.66 | 0.62 | 01-OCT-07:49 | 849.01 | 17.05 | 67.50 | 205.83 | 503.91 | 20.32 | 62.50 | 122.17 |
November | 135.83 | 0.73 | 0.62 | 01-NOV-09:00 | 349.87 | 14.69 | 33.83 | 57.67 | 220.05 | 17.76 | 34.50 | 18.50 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 78.10 | 4.78 | 0.00 | 0.00 | 45.25 | 7.69 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2086.14 | 17.99 | 921.00 | 3259.83 | 1119.14 | 20.27 | 834.67 | 2691.33 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 78.10 | 4.78 | 0.00 | 0.00 | 45.25 | 7.69 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 3380.62 | 21.92 | 139.50 | 496.83 | 1678.03 | 22.72 | 140.00 | 438.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234932E+10 | 29947.59 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830440E+09 | 29947.59 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93553473.67 | 29947.59 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9120798.17 | 29947.59 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658266E+09 | 29947.59 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160220E+10 | 29947.59 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234932E+10 | 29947.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208418E+11 | 16745.21 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153534E+11 | 16717.36 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129832E+11 | 16706.68 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500210E+10 | 16694.90 | 28-APR-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174749E+10 | 17042.21 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.619934E+09 | 16718.44 | 02-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.496782E+09 | 16392.82 | 31-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109419E+10 | 17088.41 | 25-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346757E+10 | 16795.79 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941963E+10 | 16713.67 | 02-OCT-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179996E+11 | 16724.36 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209160E+11 | 16701.78 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.496782E+09 | 16392.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209160E+11 | 17088.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.777179E+10 | 10569.42 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576249E+10 | 10575.21 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341310E+10 | 10550.10 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.812360E+09 | 10498.72 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4878927.12 | 308.27 | 27-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170803E+09 | 10505.49 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204492E+10 | 10563.00 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.581655E+10 | 10568.52 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740473E+10 | 10570.77 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.777179E+10 | 10575.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103538E+11 | 8479.01 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828326E+10 | 8462.19 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632639E+10 | 8457.43 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157383E+10 | 8439.65 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 795136.66 | 346.40 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.176495E+09 | 8443.67 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263237E+10 | 8455.33 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753259E+10 | 8467.55 | 14-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.979883E+10 | 8455.83 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103538E+11 | 8479.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.798498E+10 | 11270.49 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628821E+10 | 11276.63 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460491E+10 | 11249.89 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983830E+09 | 11182.18 | 06-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43110248.22 | 6385.23 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46536.29 | 132.46 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318489E+09 | 11202.22 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255717E+10 | 11263.67 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593144E+10 | 11250.06 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753957E+10 | 11271.94 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.798498E+10 | 11276.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686235E+10 | 28825.79 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411038E+10 | 28825.79 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166216E+10 | 28825.79 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235409E+09 | 28825.79 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1127238.55 | 9132.24 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114043E+10 | 28825.79 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491562E+10 | 28825.79 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.680577E+10 | 28825.79 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686235E+10 | 28825.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.992551E+10 | 17714.31 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584202E+10 | 17714.31 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352242E+10 | 17714.31 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.898473E+09 | 17714.31 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25819720.21 | 8364.72 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7591697.59 | 8525.64 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.426133E+09 | 17714.31 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318612E+10 | 17714.31 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.767520E+10 | 17714.31 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105156E+11 | 17714.31 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.420249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105156E+11 | 17714.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730361E+10 | 11718.39 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.496513E+10 | 11718.39 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.295501E+10 | 11718.39 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.746699E+09 | 11718.39 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10998367.76 | 1810.05 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2026956.54 | 7087.95 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339520E+09 | 11718.39 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267654E+10 | 11718.39 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607573E+10 | 11718.39 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734559E+10 | 11718.39 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.734559E+10 | 11718.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.923400E+10 | 9380.08 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658316E+10 | 9377.39 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.452103E+10 | 9390.51 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.944909E+09 | 9387.06 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10726.03 | 17.88 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 122563.16 | 1225.63 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264363E+09 | 9361.14 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302231E+10 | 9408.65 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743612E+10 | 9383.53 | 07-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.919777E+10 | 9373.34 | 26-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.923400E+10 | 9408.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.728956E+10 | 11665.70 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.522619E+10 | 11665.70 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370689E+10 | 11665.70 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.876755E+09 | 11665.70 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29039827.02 | 6319.08 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7435564.48 | 6910.60 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482881E+09 | 11665.70 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295789E+10 | 11665.70 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.597094E+10 | 11665.70 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.726433E+10 | 11665.70 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.728956E+10 | 11665.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144087E+11 | 33037.87 | 23-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.966334E+10 | 33082.43 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.604718E+10 | 33105.24 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138128E+10 | 33049.51 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327825E+09 | 33110.70 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.467510E+10 | 33168.48 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120405E+11 | 33022.47 | 02-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147211E+11 | 33049.49 | 30-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147211E+11 | 33168.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139089E+11 | 20504.77 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.901204E+10 | 20449.83 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592239E+10 | 20454.84 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196715E+10 | 20374.96 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166659E+09 | 11531.67 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83132.83 | 138.55 | 26-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68633525.06 | 16423.08 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121837E+10 | 20354.21 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.549244E+10 | 20493.65 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115447E+11 | 20497.40 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148813E+11 | 20464.80 | 02-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148813E+11 | 20504.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.975750E+10 | 12828.76 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.711264E+10 | 12818.63 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455273E+10 | 12822.69 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139492E+10 | 12806.74 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49346234.50 | 6642.97 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18684094.25 | 10663.87 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.817715E+09 | 12818.22 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414793E+10 | 12821.77 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855704E+10 | 12824.15 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100178E+11 | 12824.11 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100178E+11 | 12828.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133970E+11 | 10579.65 | 18-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103001E+11 | 10602.46 | 09-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.773015E+10 | 10596.88 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225783E+10 | 10577.43 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50239974.16 | 10495.95 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28418687.09 | 10473.25 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.975480E+09 | 10609.24 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.572173E+10 | 10611.30 | 20-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116448E+11 | 10608.93 | 17-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137231E+11 | 10566.38 | 22-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137231E+11 | 10611.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.996651E+10 | 13494.69 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763339E+10 | 13458.51 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.570942E+10 | 13461.85 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176010E+10 | 13409.26 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136932E+09 | 7523.74 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 210814.97 | 187.23 | 26-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70470618.77 | 10580.32 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118861E+10 | 13395.63 | 28-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474049E+10 | 13487.39 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.865806E+10 | 13489.89 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101458E+11 | 13468.37 | 02-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101458E+11 | 13494.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191133E+11 | 71705.14 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112930E+11 | 67281.45 | 27-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.351470E+10 | 57329.75 | 01-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200335E+09 | 9109.04 | 14-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22157837.27 | 5616.09 | 16-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16734686.71 | 5876.89 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76068918.10 | 5737.74 | 22-SEP-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.473830E+09 | 6989.12 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169569E+11 | 58344.87 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267668E+11 | 65221.50 | 15-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.784339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267668E+11 | 71705.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212735E+11 | 72418.58 | 12-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126771E+11 | 68032.10 | 27-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438835E+10 | 58845.81 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209278E+09 | 8739.37 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23627119.93 | 4980.76 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3267413.30 | 3022.46 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2780800.89 | 1868.87 | 05-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19545509.59 | 5345.39 | 28-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23589089.56 | 4890.90 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992944E+09 | 7658.04 | 30-OCT-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192098E+11 | 60703.77 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290306E+11 | 65920.87 | 15-DEC-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.878545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2780800.89 | 1868.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290306E+11 | 72418.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269263E+11 | 75716.42 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168464E+11 | 70624.40 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.669532E+10 | 61227.01 | 01-MAR-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621766E+09 | 13111.36 | 03-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17379304.41 | 6962.44 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3119009.79 | 4420.63 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3194038.05 | 2000.21 | 05-JUL-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10588335.19 | 2623.73 | 30-AUG-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40918186.46 | 3590.41 | 26-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236892E+10 | 11172.49 | 31-OCT-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243758E+11 | 62027.86 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347438E+11 | 68308.12 | 15-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3119009.79 | 2000.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.347438E+11 | 75716.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3752597.80 | 3752597.80 | 5048.40 | 20-JAN-07:01 | 5048.40 | 0.00 |
February | 0.00 | 0.00 | 10678114.99 | 10676780.17 | 4784.65 | 02-FEB-07:01 | 4784.65 | 0.00 |
March | 0.00 | 0.00 | 28424233.33 | 28370420.50 | 5029.28 | 07-MAR-07:01 | 5029.28 | 0.00 |
April | 0.00 | 0.00 | 60975423.22 | 60972108.69 | 9650.16 | 14-APR-07:04 | 9650.16 | 0.00 |
May | 0.00 | 0.00 | 0.411832E+10 | 0.411602E+10 | 38226.11 | 31-MAY-16:00 | 38226.11 | 0.00 |
June | 0.00 | 0.00 | 0.218849E+11 | 0.210201E+11 | 67635.42 | 30-JUN-11:40 | 54104.18 | 0.00 |
July | 0.00 | 0.00 | 0.307206E+11 | 0.283722E+11 | 67225.52 | 11-JUL-16:00 | 64401.94 | 0.00 |
August | 0.00 | 0.00 | 0.165016E+11 | 0.153117E+11 | 63966.46 | 11-AUG-15:50 | 63966.46 | 0.00 |
September | 0.00 | 0.00 | 0.281610E+09 | 0.268778E+09 | 9731.61 | 07-SEP-16:00 | 9731.61 | 0.00 |
October | 0.00 | 0.00 | 44170353.38 | 43700108.08 | 6141.52 | 05-OCT-07:05 | 6141.52 | 0.00 |
November | 0.00 | 0.00 | 2938916.55 | 2938916.55 | 2785.13 | 04-NOV-06:03 | 2785.13 | 0.00 |
December | 0.00 | 0.00 | 1003420.99 | 1003420.99 | 2738.74 | 21-DEC-07:01 | 2738.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.736589E+11 | 0.692402E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1003420.99 | 1003420.99 | 2738.74 | 2738.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.307206E+11 | 0.283722E+11 | 67635.42 | 64401.94 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1013616.93 | 1013616.93 | 4373.56 | 19-JAN-07:01 | 4373.56 | 0.00 |
February | 0.00 | 0.00 | 1993333.29 | 1993333.29 | 6283.25 | 09-FEB-07:01 | 6283.25 | 0.00 |
March | 0.00 | 0.00 | 9112984.46 | 9108694.11 | 6580.16 | 21-MAR-06:01 | 6580.16 | 0.00 |
April | 0.00 | 0.00 | 53938954.07 | 53938954.07 | 6303.60 | 17-APR-06:01 | 6303.60 | 0.00 |
May | 0.00 | 0.00 | 0.442927E+10 | 0.442762E+10 | 39223.65 | 31-MAY-16:00 | 39223.65 | 0.00 |
June | 0.00 | 0.00 | 0.216576E+11 | 0.208323E+11 | 66714.64 | 30-JUN-12:10 | 58680.44 | 0.00 |
July | 0.00 | 0.00 | 0.291000E+11 | 0.269182E+11 | 63818.78 | 11-JUL-15:30 | 60550.66 | 0.00 |
August | 0.00 | 0.00 | 0.151473E+11 | 0.140612E+11 | 58892.18 | 11-AUG-15:20 | 58892.18 | 0.00 |
September | 0.00 | 0.00 | 0.246194E+09 | 0.235331E+09 | 8822.93 | 07-SEP-16:00 | 8822.93 | 0.00 |
October | 0.00 | 0.00 | 9925053.09 | 9736233.83 | 6612.58 | 19-OCT-06:01 | 6612.58 | 0.00 |
November | 0.00 | 0.00 | 641644.47 | 641644.47 | 2694.50 | 02-NOV-06:01 | 2694.50 | 0.00 |
December | 0.00 | 0.00 | 484074.36 | 484074.36 | 3227.16 | 23-DEC-07:03 | 3227.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.706576E+11 | 0.665515E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 484074.36 | 484074.36 | 2694.50 | 2694.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.291000E+11 | 0.269182E+11 | 66714.64 | 60550.66 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 210855.56 | 210855.56 | 3514.26 | 09-FEB-07:01 | 3514.26 | 0.00 |
March | 0.00 | 0.00 | 7668274.86 | 7666871.58 | 2612.08 | 23-MAR-06:01 | 2612.08 | 0.00 |
April | 0.00 | 0.00 | 43493888.24 | 43489123.96 | 4559.87 | 18-APR-06:01 | 4559.87 | 0.00 |
May | 0.00 | 0.00 | 0.435084E+10 | 0.434757E+10 | 41253.62 | 31-MAY-16:00 | 41253.62 | 0.00 |
June | 0.00 | 0.00 | 0.220194E+11 | 0.211659E+11 | 72302.74 | 30-JUN-12:30 | 64480.15 | 0.00 |
July | 0.00 | 0.00 | 0.296594E+11 | 0.274371E+11 | 67513.15 | 21-JUL-14:30 | 67513.15 | 0.00 |
August | 0.00 | 0.00 | 0.151123E+11 | 0.139472E+11 | 61902.68 | 11-AUG-15:50 | 61902.68 | 0.00 |
September | 0.00 | 0.00 | 0.214897E+09 | 0.203884E+09 | 7997.07 | 07-SEP-16:00 | 7997.07 | 0.00 |
October | 0.00 | 0.00 | 5109481.74 | 4929460.79 | 4798.38 | 05-OCT-06:01 | 4798.38 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.714133E+11 | 0.671579E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.296594E+11 | 0.274371E+11 | 72302.74 | 67513.15 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2233.63 | 7810.34 | 12-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2246.79 | 7810.31 | 22-FEB-12:14 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2395.42 | 7809.82 | 24-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2234.12 | 7808.31 | 07-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2299.76 | 7806.86 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2277.75 | 7610.56 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2012.67 | 7269.82 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2165.45 | 7062.83 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2014.76 | 7032.86 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2050.81 | 7253.91 | 31-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2151.70 | 7534.45 | 30-NOV-12:18 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2143.07 | 7809.20 | 29-DEC-12:11 |
Annual Sum or Average | 0.00 | 2185.17 | ||||
Minimum of Months | 0.00 | 0.00 | 2012.67 | 7032.86 | ||
Maximum of Months | 0.00 | 0.00 | 2395.42 | 7810.34 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279619E+10 | 0.43 | 3074.03 | 02-JAN-05:01 | 0.83 |
February | 0.235623E+10 | 0.41 | 3074.03 | 01-FEB-07:01 | 0.83 |
March | 0.218783E+10 | 0.35 | 3074.03 | 01-MAR-07:01 | 0.83 |
April | 0.224721E+10 | 0.33 | 5528.31 | 21-APR-05:01 | 1.16 |
May | 0.368770E+10 | 0.42 | 6721.31 | 12-MAY-12:07 | 1.30 |
June | 0.522318E+10 | 0.51 | 9446.67 | 22-JUN-06:02 | 1.60 |
July | 0.539492E+10 | 0.50 | 9992.61 | 12-JUL-15:10 | 1.66 |
August | 0.478500E+10 | 0.48 | 9433.58 | 11-AUG-15:50 | 1.60 |
September | 0.256318E+10 | 0.34 | 5528.31 | 05-SEP-05:02 | 1.15 |
October | 0.194601E+10 | 0.30 | 3074.03 | 30-OCT-06:01 | 0.83 |
November | 0.225261E+10 | 0.36 | 3074.03 | 06-NOV-07:01 | 0.83 |
December | 0.275958E+10 | 0.42 | 3074.03 | 01-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.381996E+11 | 0.40 | |||
Minimum of Months | 0.194601E+10 | 0.30 | 3074.03 | 0.83 | |
Maximum of Months | 0.539492E+10 | 0.51 | 9992.61 | 1.66 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.257984E+10 | 0.42 | 3166.29 | 07-JAN-06:01 | 0.89 |
February | 0.222765E+10 | 0.40 | 3166.29 | 24-FEB-06:02 | 0.89 |
March | 0.217747E+10 | 0.35 | 3166.29 | 01-MAR-06:01 | 0.89 |
April | 0.228417E+10 | 0.35 | 4882.58 | 21-APR-15:50 | 1.14 |
May | 0.369484E+10 | 0.44 | 7375.14 | 31-MAY-14:50 | 1.47 |
June | 0.533175E+10 | 0.55 | 9159.61 | 30-JUN-12:10 | 1.66 |
July | 0.506810E+10 | 0.51 | 9655.45 | 12-JUL-12:10 | 1.73 |
August | 0.415640E+10 | 0.46 | 9068.98 | 11-AUG-15:20 | 1.66 |
September | 0.208485E+10 | 0.33 | 3524.29 | 08-SEP-15:30 | 0.94 |
October | 0.196102E+10 | 0.32 | 3166.29 | 30-OCT-05:02 | 0.89 |
November | 0.229087E+10 | 0.39 | 3166.29 | 18-NOV-06:01 | 0.89 |
December | 0.250539E+10 | 0.41 | 3166.29 | 29-DEC-06:01 | 0.89 |
Annual Sum or Average | 0.363623E+11 | 0.41 | |||
Minimum of Months | 0.196102E+10 | 0.32 | 3166.29 | 0.89 | |
Maximum of Months | 0.533175E+10 | 0.55 | 9655.45 | 1.73 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304707E+10 | 0.47 | 3038.68 | 01-JAN-01:22 | 0.83 |
February | 0.263401E+10 | 0.45 | 3038.68 | 01-FEB-05:01 | 0.83 |
March | 0.264402E+10 | 0.41 | 3038.68 | 01-MAR-05:01 | 0.83 |
April | 0.230419E+10 | 0.35 | 4190.29 | 21-APR-16:00 | 0.99 |
May | 0.323478E+10 | 0.40 | 7432.66 | 31-MAY-15:20 | 1.39 |
June | 0.479631E+10 | 0.49 | 9114.58 | 20-JUN-15:30 | 1.58 |
July | 0.456464E+10 | 0.46 | 9378.28 | 12-JUL-15:20 | 1.61 |
August | 0.358086E+10 | 0.41 | 8332.19 | 11-AUG-15:30 | 1.49 |
September | 0.197758E+10 | 0.31 | 3038.68 | 25-SEP-05:01 | 0.82 |
October | 0.226813E+10 | 0.35 | 3038.68 | 03-OCT-06:01 | 0.82 |
November | 0.288252E+10 | 0.46 | 3038.68 | 01-NOV-05:01 | 0.83 |
December | 0.313827E+10 | 0.48 | 3038.68 | 01-DEC-05:11 | 0.83 |
Annual Sum or Average | 0.370724E+11 | 0.42 | |||
Minimum of Months | 0.197758E+10 | 0.31 | 3038.68 | 0.82 | |
Maximum of Months | 0.479631E+10 | 0.49 | 9378.28 | 1.61 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:02 | 0.22 | 0.22 | 57.05 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.29 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.54 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 55.64 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:02 | 0.22 | 0.22 | 55.49 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:02 | 0.22 | 0.22 | 55.41 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:02 | 0.22 | 0.22 | 55.87 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 55.90 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.97 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.72 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:01 | 0.22 | 0.22 | 55.65 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.09 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.29 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.05 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 56.97 | 56.97 | 2233.63 | 7810.34 | 12-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.90 | 55.90 | 2246.79 | 7810.31 | 22-FEB-12:14 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 56.01 | 56.01 | 2395.42 | 7809.82 | 24-MAR-11:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.19 | 56.19 | 2234.12 | 7808.31 | 07-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.24 | 56.24 | 2299.76 | 7806.86 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.15 | 56.15 | 2277.75 | 7610.56 | 01-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.39 | 56.39 | 2012.67 | 7269.82 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.93 | 56.93 | 2165.45 | 7062.83 | 01-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.52 | 56.52 | 2014.76 | 7032.86 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.23 | 55.23 | 2050.81 | 7253.91 | 31-OCT-11:09 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.17 | 56.17 | 2151.70 | 7534.45 | 30-NOV-12:18 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 56.57 | 56.57 | 2143.07 | 7809.20 | 29-DEC-12:11 |
Annual Sum or Average | 0.00 | 2185.17 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.23 | 55.23 | 2012.67 | 7032.86 | ||
Maximum of Months | 0.00 | 0.00 | 56.97 | 56.97 | 2395.42 | 7810.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.520990E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.388771E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.296174E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106371E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.655868E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.112001E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.132448E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.989606E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.677720E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.186221E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.401919E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.500212E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.287743E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.655868E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.520990E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.431952E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.289551E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.185476E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.600222E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.490381E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105977E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.120215E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.785845E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.366915E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149472E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.343647E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.436346E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228697E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.366915E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.436346E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.644857E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.463556E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.326081E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.110783E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.476875E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.101834E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.116897E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.746800E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.656710E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.270473E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.553276E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.666273E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.344207E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.476875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.666273E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.279619E+10 | 3752597.80 | 0.684150E+11 | 0.374446E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235623E+10 | 10678114.99 | 0.478108E+11 | 0.323915E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218783E+10 | 28424233.33 | 0.309359E+11 | 0.384269E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224721E+10 | 60975423.22 | 0.857246E+10 | 0.119136E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368770E+10 | 0.411832E+10 | 0.181843E+10 | 0.656949E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522318E+10 | 0.218849E+11 | 0.619934E+09 | 59567158.59 | 9786391.52 | 0.00 | 0.00 | 0.00 |
July | 0.539492E+10 | 0.307206E+11 | 0.496782E+09 | 0.157080E+09 | 96981547.89 | 0.00 | 0.00 | 0.00 |
August | 0.478500E+10 | 0.165016E+11 | 0.111097E+10 | 0.130818E+09 | 404051.68 | 0.00 | 0.00 | 0.00 |
September | 0.256318E+10 | 0.281610E+09 | 0.420943E+10 | 0.482617E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194601E+10 | 44170353.38 | 0.171370E+11 | 0.256907E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225261E+10 | 2938916.55 | 0.548954E+11 | 0.368595E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.275958E+10 | 1003420.99 | 0.740282E+11 | 0.326225E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381996E+11 | 0.736589E+11 | 0.310050E+12 | 0.221180E+12 | 0.107172E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194601E+10 | 1003420.99 | 0.496782E+09 | 59567158.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.539492E+10 | 0.307206E+11 | 0.740282E+11 | 0.384269E+11 | 96981547.89 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.257984E+10 | 1013616.93 | 0.618885E+11 | 0.387019E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222765E+10 | 1993333.29 | 0.394040E+11 | 0.338341E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217747E+10 | 9112984.46 | 0.207559E+11 | 0.403754E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228417E+10 | 53938954.07 | 0.391152E+10 | 0.143276E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369484E+10 | 0.442927E+10 | 89495760.95 | 0.109993E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533175E+10 | 0.216576E+11 | 3267413.30 | 80129642.61 | 11316195.97 | 0.00 | 0.00 | 0.00 |
July | 0.506810E+10 | 0.291000E+11 | 2780800.89 | 0.195860E+09 | 93595401.53 | 0.00 | 0.00 | 0.00 |
August | 0.415640E+10 | 0.151473E+11 | 36722291.37 | 0.451539E+09 | 132429.41 | 0.00 | 0.00 | 0.00 |
September | 0.208485E+10 | 0.246194E+09 | 0.153761E+10 | 0.797141E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196102E+10 | 9925053.09 | 0.139762E+11 | 0.283713E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229087E+10 | 641644.47 | 0.512834E+11 | 0.379172E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250539E+10 | 484074.36 | 0.701596E+11 | 0.335930E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363623E+11 | 0.706576E+11 | 0.263049E+12 | 0.236919E+12 | 0.105044E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196102E+10 | 484074.36 | 2780800.89 | 80129642.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.533175E+10 | 0.291000E+11 | 0.701596E+11 | 0.403754E+11 | 93595401.53 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304707E+10 | 0.00 | 0.883649E+11 | 0.375083E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263401E+10 | 210855.56 | 0.605679E+11 | 0.330751E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264402E+10 | 7668274.86 | 0.366572E+11 | 0.395402E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230419E+10 | 43493888.24 | 0.938306E+10 | 0.145632E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.323478E+10 | 0.435084E+10 | 0.420557E+09 | 0.145748E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.479631E+10 | 0.220194E+11 | 3412957.58 | 56035842.31 | 10613581.55 | 0.00 | 0.00 | 0.00 |
July | 0.456464E+10 | 0.296594E+11 | 3194038.05 | 0.157558E+09 | 70253676.29 | 0.00 | 0.00 | 0.00 |
August | 0.358086E+10 | 0.151123E+11 | 0.196795E+09 | 0.713505E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197758E+10 | 0.214897E+09 | 0.456892E+10 | 0.867411E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226813E+10 | 5109481.74 | 0.271466E+11 | 0.281822E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288252E+10 | 0.00 | 0.768209E+11 | 0.367066E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313827E+10 | 0.00 | 0.982329E+11 | 0.325150E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370724E+11 | 0.714133E+11 | 0.402366E+12 | 0.233149E+12 | 80867257.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197758E+10 | 0.00 | 3194038.05 | 56035842.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.479631E+10 | 0.296594E+11 | 0.982329E+11 | 0.395402E+11 | 70253676.29 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.279619E+10 | 0.00 | 0.00 | 0.00 | 1094404.25 | 0.493017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235623E+10 | 0.00 | 0.00 | 0.00 | 3128310.72 | 0.365178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218783E+10 | 0.00 | 0.00 | 0.00 | 8332207.99 | 0.274212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224721E+10 | 0.00 | 0.00 | 0.00 | 17807233.76 | 0.837212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.368770E+10 | 0.00 | 0.00 | 0.00 | 0.107471E+10 | 0.179627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.522318E+10 | 0.00 | 0.00 | 0.00 | 0.535697E+10 | 0.619934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.539492E+10 | 0.00 | 0.00 | 0.00 | 0.735310E+10 | 0.496782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.478500E+10 | 0.00 | 0.00 | 0.00 | 0.401683E+10 | 0.109423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256318E+10 | 0.00 | 0.00 | 0.00 | 80660630.75 | 0.413336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194601E+10 | 0.00 | 0.00 | 0.00 | 12914725.51 | 0.166632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225261E+10 | 0.00 | 0.00 | 0.00 | 861208.84 | 0.379384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.275958E+10 | 0.00 | 0.00 | 0.00 | 292344.71 | 0.472613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381996E+11 | 0.00 | 0.00 | 0.00 | 0.179267E+11 | 0.231616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194601E+10 | 0.00 | 0.00 | 0.00 | 292344.71 | 0.496782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.539492E+10 | 0.00 | 0.00 | 0.00 | 0.735310E+10 | 0.493017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.257984E+10 | 0.00 | 0.00 | 0.00 | 291224.94 | 0.406150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222765E+10 | 0.00 | 0.00 | 0.00 | 565566.37 | 0.267269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217747E+10 | 0.00 | 0.00 | 0.00 | 2651421.70 | 0.163675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228417E+10 | 0.00 | 0.00 | 0.00 | 15804024.33 | 0.370224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.369484E+10 | 0.00 | 0.00 | 0.00 | 0.114310E+10 | 65868641.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.533175E+10 | 0.00 | 0.00 | 0.00 | 0.526596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.506810E+10 | 0.00 | 0.00 | 0.00 | 0.695337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.415640E+10 | 0.00 | 0.00 | 0.00 | 0.368487E+10 | 17176781.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208485E+10 | 0.00 | 0.00 | 0.00 | 70279120.84 | 0.151402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196102E+10 | 0.00 | 0.00 | 0.00 | 2863132.62 | 0.129833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229087E+10 | 0.00 | 0.00 | 0.00 | 186585.14 | 0.320736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250539E+10 | 0.00 | 0.00 | 0.00 | 138621.50 | 0.411290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363623E+11 | 0.00 | 0.00 | 0.00 | 0.171401E+11 | 0.175195E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196102E+10 | 0.00 | 0.00 | 0.00 | 138621.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.533175E+10 | 0.00 | 0.00 | 0.00 | 0.695337E+10 | 0.411290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.304707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263401E+10 | 0.00 | 0.00 | 0.00 | 60387.52 | 0.437215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264402E+10 | 0.00 | 0.00 | 0.00 | 2262014.62 | 0.299619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230419E+10 | 0.00 | 0.00 | 0.00 | 12783126.79 | 0.876129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.323478E+10 | 0.00 | 0.00 | 0.00 | 0.113079E+10 | 0.403178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.479631E+10 | 0.00 | 0.00 | 0.00 | 0.538684E+10 | 293947.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.456464E+10 | 0.00 | 0.00 | 0.00 | 0.712504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.358086E+10 | 0.00 | 0.00 | 0.00 | 0.370094E+10 | 0.186207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197758E+10 | 0.00 | 0.00 | 0.00 | 61512675.80 | 0.452800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226813E+10 | 0.00 | 0.00 | 0.00 | 1495700.19 | 0.247777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370724E+11 | 0.00 | 0.00 | 0.00 | 0.174217E+11 | 0.289713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.479631E+10 | 0.00 | 0.00 | 0.00 | 0.712504E+10 | 0.634891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123402E+10 | 0.00 | 0.00 | 0.36 |
February | 0.124609E+11 | 0.00 | 0.00 | 625005.38 | 0.00 | 0.729846E+09 | 0.826227E+09 | 0.00 | 0.37 |
March | 0.943720E+10 | 0.00 | 0.00 | 6403849.34 | 0.00 | 16838464.12 | 0.366446E+10 | 0.00 | 0.40 |
April | 0.385838E+10 | 0.00 | 0.00 | 25468581.46 | 0.00 | 0.00 | 0.129989E+11 | 0.00 | 0.49 |
May | 0.205911E+10 | 0.00 | 0.00 | 46924849.14 | 0.00 | 0.00 | 0.246109E+11 | 0.00 | 0.99 |
June | 0.148141E+10 | 7622073.20 | 0.00 | 51182106.57 | 0.00 | 0.00 | 0.215394E+11 | 0.00 | 1.31 |
July | 0.169563E+10 | 72075281.96 | 0.00 | 46849780.76 | 8738251.12 | 0.00 | 0.164330E+11 | 0.00 | 1.22 |
August | 0.149303E+10 | 189406.18 | 0.00 | 53561928.19 | 0.00 | 0.00 | 0.237095E+11 | 0.00 | 1.19 |
September | 0.243789E+10 | 0.00 | 0.00 | 35082526.39 | 0.00 | 0.00 | 0.183911E+11 | 0.00 | 0.63 |
October | 0.571838E+10 | 0.00 | 0.00 | 13432579.81 | 0.00 | 1185501.79 | 0.684532E+10 | 0.00 | 0.40 |
November | 0.156037E+11 | 0.00 | 0.00 | 180192.90 | 0.00 | 0.238121E+09 | 0.400778E+09 | 0.00 | 0.36 |
December | 0.199499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491029E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.918491E+11 | 79886761.33 | 0.00 | 0.279711E+09 | 8738251.12 | 0.271104E+10 | 0.129420E+12 | 0.00 | 0.67 |
Minimum of Months | 0.148141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.199499E+11 | 72075281.96 | 0.00 | 53561928.19 | 8738251.12 | 0.123402E+10 | 0.246109E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.949874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612573E+10 | 0.00 | 0.00 | 0.33 |
February | 0.818862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403767E+10 | 0.00 | 0.00 | 0.33 |
March | 0.100715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815005E+09 | 0.00 | 0.00 | 0.35 |
April | 0.707442E+10 | 0.00 | 0.00 | 6078431.73 | 0.00 | 53483711.13 | 0.430055E+10 | 0.00 | 0.37 |
May | 0.320970E+10 | 0.00 | 0.00 | 25720385.21 | 0.00 | 0.00 | 0.147227E+11 | 0.00 | 0.68 |
June | 0.195822E+10 | 6459017.00 | 0.00 | 33797157.80 | 0.00 | 0.00 | 0.143525E+11 | 0.00 | 0.93 |
July | 0.195462E+10 | 50251374.78 | 0.00 | 30683783.67 | 6950574.09 | 0.00 | 0.105819E+11 | 0.00 | 0.86 |
August | 0.188665E+10 | 198604.40 | 0.00 | 30988429.91 | 0.00 | 0.00 | 0.143116E+11 | 0.00 | 0.79 |
September | 0.617184E+10 | 0.00 | 0.00 | 9347663.80 | 0.00 | 280208.79 | 0.608330E+10 | 0.00 | 0.42 |
October | 0.820515E+10 | 0.00 | 0.00 | 357549.93 | 0.00 | 0.323958E+09 | 0.550523E+09 | 0.00 | 0.33 |
November | 0.104688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458372E+10 | 0.00 | 0.00 | 0.33 |
December | 0.115173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729418E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.802056E+11 | 56908996.19 | 0.00 | 0.136973E+09 | 6950574.09 | 0.232340E+11 | 0.649031E+11 | 0.00 | 0.51 |
Minimum of Months | 0.188665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.115173E+11 | 50251374.78 | 0.00 | 33797157.80 | 6950574.09 | 0.729418E+10 | 0.147227E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107022E+11 | 0.00 | 0.00 | 0.31 |
February | 0.354048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717659E+10 | 0.00 | 0.00 | 0.32 |
March | 0.672323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304173E+10 | 0.00 | 0.00 | 0.34 |
April | 0.747240E+10 | 0.00 | 0.00 | 2650288.16 | 0.00 | 0.384676E+09 | 0.242207E+10 | 0.00 | 0.36 |
May | 0.426363E+10 | 0.00 | 0.00 | 20026081.29 | 0.00 | 0.00 | 0.121306E+11 | 0.00 | 0.64 |
June | 0.209811E+10 | 13599081.87 | 0.00 | 30417749.39 | 0.00 | 0.00 | 0.134817E+11 | 0.00 | 0.91 |
July | 0.226651E+10 | 45825678.06 | 0.00 | 26815378.04 | 5391944.41 | 0.00 | 0.931733E+10 | 0.00 | 0.83 |
August | 0.279612E+10 | 528608.28 | 0.00 | 23120058.69 | 0.00 | 0.00 | 0.112597E+11 | 0.00 | 0.73 |
September | 0.769970E+10 | 0.00 | 0.00 | 2591051.81 | 0.00 | 71250098.69 | 0.250321E+10 | 0.00 | 0.38 |
October | 0.624290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171459E+10 | 0.00 | 0.00 | 0.32 |
November | 0.398109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940371E+10 | 0.00 | 0.00 | 0.31 |
December | 0.398195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126653E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.542524E+11 | 59953368.21 | 0.00 | 0.105621E+09 | 5391944.41 | 0.451601E+11 | 0.511146E+11 | 0.00 | 0.48 |
Minimum of Months | 0.209811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.769970E+10 | 45825678.06 | 0.00 | 30417749.39 | 5391944.41 | 0.126653E+11 | 0.134817E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22370195.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487575E+10 | 0.00 | 0.00 | 0.48 |
February | 31492119.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351799E+10 | 0.00 | 0.00 | 0.46 |
March | 0.304693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259693E+10 | 0.00 | 0.00 | 0.46 |
April | 0.194044E+10 | 0.00 | 0.00 | 86858.79 | 0.00 | 0.650676E+09 | 0.149164E+09 | 0.00 | 0.45 |
May | 0.171087E+10 | 0.00 | 0.00 | 3588633.44 | 0.00 | 14058368.93 | 0.230533E+10 | 0.00 | 0.75 |
June | 0.483355E+09 | 5062251.08 | 0.00 | 9615471.82 | 0.00 | 0.00 | 0.395327E+10 | 0.00 | 1.26 |
July | 0.595365E+09 | 14576207.83 | 0.00 | 7867959.90 | 1461008.65 | 0.00 | 0.257911E+10 | 0.00 | 1.14 |
August | 0.132652E+10 | 143232.42 | 0.00 | 4373118.77 | 0.00 | 13064328.74 | 0.204625E+10 | 0.00 | 0.86 |
September | 0.225479E+10 | 0.00 | 0.00 | 44945.18 | 0.00 | 0.413160E+09 | 75275429.90 | 0.00 | 0.48 |
October | 0.483773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172424E+10 | 0.00 | 0.00 | 0.42 |
November | 17725893.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440345E+10 | 0.00 | 0.00 | 0.46 |
December | 28104817.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580019E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.919950E+10 | 19781691.34 | 0.00 | 25576987.90 | 1461008.65 | 0.240095E+11 | 0.111084E+11 | 0.00 | 0.64 |
Minimum of Months | 17725893.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.225479E+10 | 14576207.83 | 0.00 | 9615471.82 | 1461008.65 | 0.580019E+10 | 0.395327E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26660146.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458814E+10 | 0.00 | 0.00 | 0.77 |
February | 0.103432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345726E+10 | 0.00 | 0.00 | 0.78 |
March | 0.120731E+10 | 0.00 | 0.00 | 12860.63 | 0.00 | 0.200942E+10 | 22909433.68 | 0.00 | 0.84 |
April | 0.210003E+10 | 0.00 | 0.00 | 1329422.98 | 0.00 | 0.431635E+09 | 0.914403E+09 | 0.00 | 0.89 |
May | 0.158613E+10 | 0.00 | 0.00 | 8073605.90 | 0.00 | 1634316.13 | 0.452036E+10 | 0.00 | 1.73 |
June | 0.787662E+09 | 4194376.25 | 0.00 | 9767783.16 | 0.00 | 0.00 | 0.467904E+10 | 0.00 | 2.27 |
July | 0.881201E+09 | 12279214.94 | 0.00 | 9359964.54 | 1816469.64 | 0.00 | 0.324424E+10 | 0.00 | 2.17 |
August | 0.135481E+10 | 0.00 | 0.00 | 5991873.41 | 174568.60 | 7441415.45 | 0.324874E+10 | 0.00 | 1.72 |
September | 0.258296E+10 | 0.00 | 0.00 | 601333.79 | 0.00 | 0.256364E+09 | 0.535445E+09 | 0.00 | 0.94 |
October | 0.957747E+09 | 0.00 | 0.00 | 2961.49 | 0.00 | 0.165937E+10 | 9601604.60 | 0.00 | 0.79 |
November | 21680954.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441114E+10 | 0.00 | 0.00 | 0.77 |
December | 34257766.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548780E+10 | 0.00 | 0.00 | 0.75 |
Annual Sum or Average | 0.116439E+11 | 16473591.19 | 0.00 | 35139805.89 | 1991038.24 | 0.223102E+11 | 0.171747E+11 | 0.00 | 1.21 |
Minimum of Months | 21680954.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
Maximum of Months | 0.258296E+10 | 12279214.94 | 0.00 | 9767783.16 | 1816469.64 | 0.548780E+10 | 0.467904E+10 | 0.00 | 2.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712090E+10 | 0.00 | 0.00 | 0.78 |
February | 0.969353E+09 | 0.00 | 0.00 | 65472.90 | 0.00 | 0.463298E+10 | 63580146.48 | 0.00 | 0.79 |
March | 0.181734E+10 | 0.00 | 0.00 | 1771753.84 | 0.00 | 0.258053E+10 | 0.936859E+09 | 0.00 | 0.87 |
April | 0.221068E+10 | 0.00 | 0.00 | 7274699.52 | 0.00 | 0.630114E+09 | 0.423332E+10 | 0.00 | 1.12 |
May | 0.303142E+10 | 0.00 | 0.00 | 11468671.18 | 0.00 | 33685771.09 | 0.624166E+10 | 0.00 | 1.75 |
June | 0.210183E+10 | 7366742.45 | 0.00 | 12286609.99 | 0.00 | 0.00 | 0.537533E+10 | 0.00 | 2.15 |
July | 0.221823E+10 | 26868408.27 | 0.00 | 11782658.21 | 2846084.15 | 0.00 | 0.333982E+10 | 0.00 | 2.03 |
August | 0.277005E+10 | 279020.62 | 0.00 | 11320206.90 | 0.00 | 19962324.16 | 0.479510E+10 | 0.00 | 1.94 |
September | 0.331788E+10 | 0.00 | 0.00 | 3871555.21 | 0.00 | 0.436962E+09 | 0.234869E+10 | 0.00 | 1.07 |
October | 0.182340E+10 | 0.00 | 0.00 | 814495.47 | 0.00 | 0.206439E+10 | 0.418398E+09 | 0.00 | 0.82 |
November | 0.390901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667356E+10 | 0.00 | 0.00 | 0.78 |
December | 54773400.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874737E+10 | 0.00 | 0.00 | 0.76 |
Annual Sum or Average | 0.209335E+11 | 34514171.33 | 0.00 | 60656123.21 | 2846084.15 | 0.329405E+11 | 0.277528E+11 | 0.00 | 1.24 |
Minimum of Months | 54773400.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
Maximum of Months | 0.331788E+10 | 26868408.27 | 0.00 | 12286609.99 | 2846084.15 | 0.874737E+10 | 0.624166E+10 | 0.00 | 2.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 28778809.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480979E+10 | 0.00 | 0.00 | 0.81 |
February | 97768546.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363502E+10 | 0.00 | 0.00 | 0.82 |
March | 0.799947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259754E+10 | 0.00 | 0.00 | 0.88 |
April | 0.206595E+10 | 0.00 | 0.00 | 2053118.22 | 0.00 | 0.615467E+09 | 0.116514E+10 | 0.00 | 0.99 |
May | 0.286867E+10 | 0.00 | 0.00 | 3287145.79 | 0.00 | 39120191.41 | 0.215118E+10 | 0.00 | 1.49 |
June | 0.154929E+10 | 5465367.51 | 0.00 | 6415859.99 | 0.00 | 0.00 | 0.271817E+10 | 0.00 | 1.99 |
July | 0.159602E+10 | 17548930.96 | 0.00 | 4744844.15 | 1661418.32 | 0.00 | 0.153108E+10 | 0.00 | 1.79 |
August | 0.249518E+10 | 183630.29 | 0.00 | 3413346.09 | 0.00 | 16034960.96 | 0.149813E+10 | 0.00 | 1.60 |
September | 0.274349E+10 | 0.00 | 0.00 | 485090.37 | 0.00 | 0.454553E+09 | 0.342268E+09 | 0.00 | 0.98 |
October | 0.732690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202959E+10 | 0.00 | 0.00 | 0.83 |
November | 30325814.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462067E+10 | 0.00 | 0.00 | 0.81 |
December | 36036054.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575834E+10 | 0.00 | 0.00 | 0.79 |
Annual Sum or Average | 0.150441E+11 | 23197928.76 | 0.00 | 20399404.60 | 1661418.32 | 0.245761E+11 | 0.940597E+10 | 0.00 | 1.15 |
Minimum of Months | 28778809.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
Maximum of Months | 0.286867E+10 | 17548930.96 | 0.00 | 6415859.99 | 1661418.32 | 0.575834E+10 | 0.271817E+10 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56462666.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438886E+10 | 0.00 | 0.00 | 0.41 |
February | 40477187.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346712E+10 | 0.00 | 0.00 | 0.40 |
March | 0.204311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255836E+10 | 0.00 | 0.00 | 0.38 |
April | 0.175388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749090E+09 | 0.00 | 0.00 | 0.35 |
May | 0.191305E+10 | 0.00 | 0.00 | 1640786.17 | 0.00 | 0.00 | 0.119717E+10 | 0.00 | 0.55 |
June | 0.399624E+09 | 1353519.03 | 0.00 | 7460448.06 | 0.00 | 0.00 | 0.308054E+10 | 0.00 | 0.98 |
July | 0.474527E+09 | 13261227.12 | 0.00 | 7083105.37 | 1656491.14 | 0.00 | 0.232262E+10 | 0.00 | 0.96 |
August | 0.935107E+09 | 29730.76 | 0.00 | 4935555.43 | 0.00 | 0.00 | 0.229340E+10 | 0.00 | 0.77 |
September | 0.225824E+10 | 0.00 | 0.00 | 178394.03 | 0.00 | 94516497.13 | 0.309081E+09 | 0.00 | 0.39 |
October | 0.989063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119720E+10 | 0.00 | 0.00 | 0.33 |
November | 44209574.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371337E+10 | 0.00 | 0.00 | 0.37 |
December | 0.132625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503829E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.920157E+10 | 14644476.91 | 0.00 | 21298289.05 | 1656491.14 | 0.212068E+11 | 0.920282E+10 | 0.00 | 0.53 |
Minimum of Months | 40477187.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.225824E+10 | 13261227.12 | 0.00 | 7460448.06 | 1656491.14 | 0.503829E+10 | 0.308054E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68296881.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401950E+10 | 0.00 | 0.00 | 0.64 |
February | 0.113986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328890E+10 | 0.00 | 0.00 | 0.66 |
March | 0.102115E+10 | 0.00 | 0.00 | 2202.42 | 0.00 | 0.206943E+10 | 7365745.69 | 0.00 | 0.71 |
April | 0.206520E+10 | 0.00 | 0.00 | 779883.95 | 0.00 | 0.425544E+09 | 0.673233E+09 | 0.00 | 0.71 |
May | 0.119889E+10 | 0.00 | 0.00 | 6644029.27 | 0.00 | 0.00 | 0.391852E+10 | 0.00 | 1.41 |
June | 0.651197E+09 | 1613603.38 | 0.00 | 8582342.82 | 0.00 | 0.00 | 0.392709E+10 | 0.00 | 1.90 |
July | 0.675754E+09 | 13072012.30 | 0.00 | 8825981.55 | 2007914.70 | 0.00 | 0.297804E+10 | 0.00 | 1.89 |
August | 0.970378E+09 | 34247.98 | 0.00 | 7002433.11 | 0.00 | 0.00 | 0.345101E+10 | 0.00 | 1.56 |
September | 0.248642E+10 | 0.00 | 0.00 | 1084961.00 | 0.00 | 43827963.77 | 0.878395E+09 | 0.00 | 0.78 |
October | 0.145237E+10 | 0.00 | 0.00 | 24111.55 | 0.00 | 0.123141E+10 | 19879005.41 | 0.00 | 0.65 |
November | 52948455.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383511E+10 | 0.00 | 0.00 | 0.64 |
December | 0.141993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474829E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.108986E+11 | 14719863.66 | 0.00 | 32945945.68 | 2007914.70 | 0.196620E+11 | 0.158535E+11 | 0.00 | 1.02 |
Minimum of Months | 52948455.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.248642E+10 | 13072012.30 | 0.00 | 8825981.55 | 2007914.70 | 0.474829E+10 | 0.392709E+10 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 86607700.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919501E+10 | 0.00 | 0.00 | 0.88 |
February | 0.240647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660699E+10 | 0.00 | 0.00 | 0.83 |
March | 0.567953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522890E+10 | 0.00 | 0.00 | 0.81 |
April | 0.250794E+10 | 0.00 | 0.00 | 1122109.68 | 0.00 | 0.205831E+10 | 0.923488E+09 | 0.00 | 0.79 |
May | 0.371265E+10 | 0.00 | 0.00 | 3045522.68 | 0.00 | 0.754218E+09 | 0.207182E+10 | 0.00 | 1.16 |
June | 0.249292E+10 | 2744741.13 | 0.00 | 6042464.14 | 0.00 | 0.303982E+09 | 0.242759E+10 | 0.00 | 1.49 |
July | 0.214225E+10 | 25474212.83 | 0.00 | 7778007.58 | 3097249.00 | 0.255367E+09 | 0.190262E+10 | 0.00 | 1.53 |
August | 0.279491E+10 | 54106.74 | 0.00 | 6883982.17 | 0.00 | 0.525079E+09 | 0.268094E+10 | 0.00 | 1.50 |
September | 0.320206E+10 | 0.00 | 0.00 | 1425400.48 | 0.00 | 0.156263E+10 | 0.108655E+10 | 0.00 | 0.85 |
October | 0.105827E+10 | 0.00 | 0.00 | 159880.60 | 0.00 | 0.365715E+10 | 0.118083E+09 | 0.00 | 0.74 |
November | 0.118732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857958E+10 | 0.00 | 0.00 | 0.86 |
December | 0.107441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112319E+11 | 0.00 | 0.00 | 0.88 |
Annual Sum or Average | 0.190324E+11 | 28273060.70 | 0.00 | 26457367.33 | 3097249.00 | 0.499591E+11 | 0.112111E+11 | 0.00 | 1.03 |
Minimum of Months | 86607700.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255367E+09 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.371265E+10 | 25474212.83 | 0.00 | 7778007.58 | 3097249.00 | 0.112319E+11 | 0.268094E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72964740.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425806E+10 | 0.00 | 0.00 | 0.68 |
February | 91050250.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352254E+10 | 0.00 | 0.00 | 0.71 |
March | 0.556984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273918E+10 | 0.00 | 0.00 | 0.75 |
April | 0.228990E+10 | 0.00 | 0.00 | 956054.95 | 0.00 | 0.524366E+09 | 0.615806E+09 | 0.00 | 0.77 |
May | 0.286736E+10 | 0.00 | 0.00 | 1741735.41 | 0.00 | 3494210.35 | 0.128462E+10 | 0.00 | 1.16 |
June | 0.120773E+10 | 993336.20 | 0.00 | 5054152.21 | 0.00 | 0.00 | 0.224096E+10 | 0.00 | 1.57 |
July | 0.123528E+10 | 16338370.75 | 0.00 | 4205042.47 | 2391010.80 | 0.00 | 0.146441E+10 | 0.00 | 1.46 |
August | 0.180313E+10 | 36519.74 | 0.00 | 3497285.66 | 0.00 | 0.00 | 0.184700E+10 | 0.00 | 1.37 |
September | 0.313398E+10 | 0.00 | 0.00 | 387181.28 | 0.00 | 99595944.14 | 0.327972E+09 | 0.00 | 0.82 |
October | 0.139130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149163E+10 | 0.00 | 0.00 | 0.70 |
November | 66064586.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406622E+10 | 0.00 | 0.00 | 0.68 |
December | 0.150662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504601E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.148664E+11 | 17368226.70 | 0.00 | 15841451.97 | 2391010.80 | 0.217511E+11 | 0.778077E+10 | 0.00 | 0.95 |
Minimum of Months | 66064586.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.313398E+10 | 16338370.75 | 0.00 | 5054152.21 | 2391010.80 | 0.504601E+10 | 0.224096E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29638767.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444119E+10 | 0.00 | 0.00 | 0.42 |
February | 0.103086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329581E+10 | 0.00 | 0.00 | 0.41 |
March | 0.578957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224338E+10 | 0.00 | 0.00 | 0.42 |
April | 0.202182E+10 | 0.00 | 0.00 | 244589.96 | 0.00 | 0.417243E+09 | 0.250334E+09 | 0.00 | 0.42 |
May | 0.111628E+10 | 0.00 | 0.00 | 5277344.07 | 0.00 | 0.00 | 0.301283E+10 | 0.00 | 0.76 |
June | 0.310613E+09 | 2101869.58 | 0.00 | 10872645.53 | 0.00 | 0.00 | 0.433618E+10 | 0.00 | 1.29 |
July | 0.405367E+09 | 15720483.72 | 0.00 | 8992126.24 | 1704814.40 | 0.00 | 0.293522E+10 | 0.00 | 1.15 |
August | 0.886116E+09 | 50779.07 | 0.00 | 5927531.25 | 0.00 | 172822.04 | 0.270926E+10 | 0.00 | 0.88 |
September | 0.226550E+10 | 0.00 | 0.00 | 347444.16 | 0.00 | 0.129474E+09 | 0.395787E+09 | 0.00 | 0.45 |
October | 0.953154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129845E+10 | 0.00 | 0.00 | 0.39 |
November | 29513479.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404511E+10 | 0.00 | 0.00 | 0.41 |
December | 38549290.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518420E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.873860E+10 | 17873132.37 | 0.00 | 31661681.21 | 1704814.40 | 0.210550E+11 | 0.136396E+11 | 0.00 | 0.62 |
Minimum of Months | 29513479.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.226550E+10 | 15720483.72 | 0.00 | 10872645.53 | 1704814.40 | 0.518420E+10 | 0.433618E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43158832.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519480E+10 | 0.00 | 0.00 | 0.82 |
February | 0.362750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374255E+10 | 0.00 | 0.00 | 0.84 |
March | 0.168636E+10 | 0.00 | 0.00 | 69977.04 | 0.00 | 0.188323E+10 | 83118330.94 | 0.00 | 0.88 |
April | 0.229538E+10 | 0.00 | 0.00 | 1860534.29 | 0.00 | 0.345824E+09 | 0.123063E+10 | 0.00 | 0.94 |
May | 0.148639E+10 | 0.00 | 0.00 | 8733660.12 | 0.00 | 348482.77 | 0.497867E+10 | 0.00 | 1.79 |
June | 0.792467E+09 | 2279977.37 | 0.00 | 9991824.20 | 0.00 | 0.00 | 0.474323E+10 | 0.00 | 2.26 |
July | 0.855860E+09 | 13498264.93 | 0.00 | 9520870.24 | 2329772.58 | 0.00 | 0.336592E+10 | 0.00 | 2.14 |
August | 0.131829E+10 | 0.00 | 0.00 | 6718618.96 | 64067.94 | 508454.95 | 0.363366E+10 | 0.00 | 1.75 |
September | 0.302858E+10 | 0.00 | 0.00 | 1014928.76 | 0.00 | 0.120521E+09 | 0.739987E+09 | 0.00 | 0.98 |
October | 0.156969E+10 | 0.00 | 0.00 | 21459.48 | 0.00 | 0.145385E+10 | 21851713.21 | 0.00 | 0.83 |
November | 43060935.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500517E+10 | 0.00 | 0.00 | 0.83 |
December | 54694132.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625195E+10 | 0.00 | 0.00 | 0.81 |
Annual Sum or Average | 0.135367E+11 | 15778242.30 | 0.00 | 37931873.10 | 2393840.52 | 0.239987E+11 | 0.187971E+11 | 0.00 | 1.24 |
Minimum of Months | 43060935.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
Maximum of Months | 0.302858E+10 | 13498264.93 | 0.00 | 9991824.20 | 2329772.58 | 0.625195E+10 | 0.497867E+10 | 0.00 | 2.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755771E+10 | 0.00 | 0.00 | 0.79 |
February | 0.147911E+10 | 0.00 | 0.00 | 196719.73 | 0.00 | 0.465277E+10 | 0.107309E+09 | 0.00 | 0.81 |
March | 0.229057E+10 | 0.00 | 0.00 | 2769397.80 | 0.00 | 0.238833E+10 | 0.116708E+10 | 0.00 | 0.89 |
April | 0.252206E+10 | 0.00 | 0.00 | 8284031.32 | 0.00 | 0.424408E+09 | 0.457471E+10 | 0.00 | 1.15 |
May | 0.283148E+10 | 0.00 | 0.00 | 12260963.18 | 0.00 | 1061570.88 | 0.648539E+10 | 0.00 | 1.75 |
June | 0.189304E+10 | 4397910.31 | 0.00 | 12831366.55 | 0.00 | 0.00 | 0.538970E+10 | 0.00 | 2.10 |
July | 0.198783E+10 | 30490856.11 | 0.00 | 12077379.42 | 3363103.87 | 0.00 | 0.343308E+10 | 0.00 | 1.95 |
August | 0.235803E+10 | 97365.70 | 0.00 | 12435445.61 | 0.00 | 772712.09 | 0.533679E+10 | 0.00 | 1.92 |
September | 0.364380E+10 | 0.00 | 0.00 | 4937432.00 | 0.00 | 0.128693E+09 | 0.299960E+10 | 0.00 | 1.10 |
October | 0.245913E+10 | 0.00 | 0.00 | 1188917.36 | 0.00 | 0.175416E+10 | 0.591385E+09 | 0.00 | 0.82 |
November | 0.686167E+09 | 0.00 | 0.00 | 9977.36 | 0.00 | 0.696518E+10 | 19485834.83 | 0.00 | 0.80 |
December | 82872385.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950149E+10 | 0.00 | 0.00 | 0.78 |
Annual Sum or Average | 0.226351E+11 | 34986132.12 | 0.00 | 66991630.32 | 3363103.87 | 0.333746E+11 | 0.301045E+11 | 0.00 | 1.24 |
Minimum of Months | 82872385.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
Maximum of Months | 0.364380E+10 | 30490856.11 | 0.00 | 12831366.55 | 3363103.87 | 0.950149E+10 | 0.648539E+10 | 0.00 | 2.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 43048933.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519587E+10 | 0.00 | 0.00 | 0.82 |
February | 0.239614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386600E+10 | 0.00 | 0.00 | 0.84 |
March | 0.120802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244525E+10 | 0.00 | 0.00 | 0.88 |
April | 0.238211E+10 | 0.00 | 0.00 | 2251950.41 | 0.00 | 0.411604E+09 | 0.125950E+10 | 0.00 | 0.99 |
May | 0.251843E+10 | 0.00 | 0.00 | 3741865.13 | 0.00 | 1206397.54 | 0.249020E+10 | 0.00 | 1.46 |
June | 0.128697E+10 | 1343023.89 | 0.00 | 7021470.24 | 0.00 | 0.00 | 0.286920E+10 | 0.00 | 1.93 |
July | 0.138140E+10 | 18606879.05 | 0.00 | 5131030.80 | 2253600.71 | 0.00 | 0.169340E+10 | 0.00 | 1.71 |
August | 0.213205E+10 | 64078.72 | 0.00 | 3976334.28 | 0.00 | 508540.51 | 0.191069E+10 | 0.00 | 1.56 |
September | 0.322120E+10 | 0.00 | 0.00 | 665692.23 | 0.00 | 0.150352E+09 | 0.479080E+09 | 0.00 | 0.98 |
October | 0.139035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165561E+10 | 0.00 | 0.00 | 0.83 |
November | 58227191.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499081E+10 | 0.00 | 0.00 | 0.83 |
December | 54482231.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625326E+10 | 0.00 | 0.00 | 0.81 |
Annual Sum or Average | 0.159159E+11 | 20013981.66 | 0.00 | 22788343.10 | 2253600.71 | 0.249705E+11 | 0.107021E+11 | 0.00 | 1.14 |
Minimum of Months | 43048933.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
Maximum of Months | 0.322120E+10 | 18606879.05 | 0.00 | 7021470.24 | 2253600.71 | 0.625326E+10 | 0.286920E+10 | 0.00 | 1.93 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:07
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.374370E+09 | 0.272978E+11 | 0.00 | 0.252463E+12 | 0.168344E+11 |
February | 0.555244E+11 | 0.219846E+11 | 0.00 | 0.220552E+12 | 0.102208E+11 |
March | 0.216854E+12 | 0.282163E+11 | 0.00 | 0.258011E+12 | 0.370805E+10 |
April | 0.361392E+12 | 0.236225E+11 | 0.00 | 0.246291E+12 | 0.462648E+09 |
May | 0.435699E+12 | 0.141747E+11 | 0.00 | 0.294893E+12 | 0.162628E+11 |
June | 0.443837E+12 | 0.796268E+10 | 0.00 | 0.256431E+12 | 0.815733E+11 |
July | 0.403231E+12 | 0.615931E+10 | 0.00 | 0.264832E+12 | 0.110913E+12 |
August | 0.306112E+12 | 0.878104E+10 | 0.00 | 0.271872E+12 | 0.581756E+11 |
September | 0.151288E+12 | 0.119206E+11 | 0.00 | 0.261774E+12 | 0.990298E+09 |
October | 0.729694E+11 | 0.225543E+11 | 0.00 | 0.234867E+12 | 0.103540E+10 |
November | 0.150928E+11 | 0.200235E+11 | 0.00 | 0.255927E+12 | 0.151403E+11 |
December | -0.875915E+10 | 0.242782E+11 | 0.00 | 0.259285E+12 | 0.226372E+11 |
Annual Sum or Average | 0.245361E+13 | 0.216976E+12 | 0.00 | 0.307720E+13 | 0.337954E+12 |
Minimum of Months | -0.875915E+10 | 0.615931E+10 | 0.00 | 0.220552E+12 | 0.462648E+09 |
Maximum of Months | 0.443837E+12 | 0.282163E+11 | 0.00 | 0.294893E+12 | 0.110913E+12 |