Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:35:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1860.19 | 373.37 | 373.37 |
Net Site Energy | 1860.19 | 373.37 | 373.37 |
Total Source Energy | 5603.64 | 1124.73 | 1124.73 |
Net Source Energy | 5603.64 | 1124.73 | 1124.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 68.94 | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 250.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 360.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 105.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1722.13 | 138.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 68.94 | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 250.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 360.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 150.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 105.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 68.94 | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 250.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 360.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 110.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 150.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 105.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.32 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 345.66 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 94.32 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 345.66 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1722.128 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1722.128 | 100.00 |
Total On-Site and Utility Electric Sources | 1722.128 | 100.00 |
Total Electricity End Uses | 1722.128 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 168.00 |
Time Setpoint Not Met During Occupied Cooling | 262.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1908.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:34 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.0546 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 9.0546 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 9.0546 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-14:50 | 21-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 46824.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 81022.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30486.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42286.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1345.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32594.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7918.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 187736.23 | 54743.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 46824.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 81022.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30486.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 6054.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 46.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1345.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 32594.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7918.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 218.34 | 35.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 793.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1141.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 476.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 114.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5453.98 | 149.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 43.82 | 7.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1094.70 | 30.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 43.82 | 7.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 22.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1094.70 | 30.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.56 | 0.210325 | 0.300000 | 1.07 | 0.560866 | 0.500000 | 0.001811 |
CORE_MID VAV BOX COMPONENT | 2.65 | 0.282655 | 0.303000 | 0.803399 | 0.753747 | 0.500000 | 0.001348 |
CORE_TOP VAV BOX COMPONENT | 2.87 | 0.260996 | 0.300000 | 0.861456 | 0.695989 | 0.500000 | 0.001460 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.935208 | 0.168937 | 0.300000 | 0.280563 | 0.450500 | 0.500000 | 0.002255 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.995440 | 0.100480 | 0.300000 | 0.298632 | 0.300000 | 0.500000 | 0.003792 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.13 | 0.140217 | 0.300000 | 0.338028 | 0.373913 | 0.500000 | 0.002717 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.13 | 0.088243 | 0.300000 | 0.340024 | 0.300000 | 0.500000 | 0.004318 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.750284 | 0.210576 | 0.300000 | 0.225085 | 0.561536 | 0.500000 | 0.001809 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.832773 | 0.120107 | 0.300000 | 0.249832 | 0.320285 | 0.500000 | 0.003172 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.914111 | 0.172836 | 0.300000 | 0.274233 | 0.460897 | 0.500000 | 0.002204 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.889830 | 0.112398 | 0.300000 | 0.266949 | 0.300000 | 0.500000 | 0.003390 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.806274 | 0.195953 | 0.300000 | 0.241882 | 0.522541 | 0.500000 | 0.001944 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.964843 | 0.103666 | 0.300000 | 0.289453 | 0.300000 | 0.500000 | 0.003675 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.997305 | 0.158419 | 0.300000 | 0.299191 | 0.422450 | 0.500000 | 0.002405 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 1.03 | 0.096933 | 0.300000 | 0.309539 | 0.300000 | 0.500000 | 0.003931 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29365.48 |
CORE_MID VAV BOX REHEAT COIL | 22069.48 |
CORE_TOP VAV BOX REHEAT COIL | 35381.94 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16135.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10549.75 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16029.36 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10549.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11663.72 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7710.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11567.68 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7710.77 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12473.95 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8204.99 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12380.62 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8503.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.48 | 2.09 | 6.95 | 2.09 | 6.27 | 6.27 | 0.300000 | 0.332714 | 6.27 |
PACU_VAV_MID | 3.23 | 1.94 | 6.45 | 2.24 | 5.59 | 5.59 | 0.300000 | 0.401480 | 5.59 |
PACU_VAV_TOP | 3.53 | 2.12 | 7.06 | 3.23 | 6.54 | 6.54 | 0.300000 | 0.493358 | 6.54 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 6.27 |
PACU_VAV_MID_OA_CONTROLLER | 5.59 |
PACU_VAV_TOP_OA_CONTROLLER | 6.54 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 6.27 | 103739.90 | 0.800655 | 2.09 | 34576.51 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.59 | 92543.01 | 0.800655 | 1.86 | 30844.59 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 6.54 | 108274.25 | 0.800655 | 2.18 | 36087.81 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 14913.97 |
PACU_VAV_MID HEATING COIL | 21673.73 |
PACU_VAV_TOP HEATING COIL | 20266.96 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 6.27 |
PACU_VAV_MID FAN | 5.59 |
PACU_VAV_TOP FAN | 6.54 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.889 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9714E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0033E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0856E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0909E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2090E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2520E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1459 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2752E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1646 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0779E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1084 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5010E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9711E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0034E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0855E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0910E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2089E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2531E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1942E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6490E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7371E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3104E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2307E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1344E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6263E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6496E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2599E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2767E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1506E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1564E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9465E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9984E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3068E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3479E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8864E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9154E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6987E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1735E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8598E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6575E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7424E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1647E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9466E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9986E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3068E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3478E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8863E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9146E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0233E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5671E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5269E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2092E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0799E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0640E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5334E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5970E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1455E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2142E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0685E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0963E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1427 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.7104E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1581 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.6225E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1139 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6285E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9581E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5176E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5298E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1959E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0507E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0375E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1985E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8131E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3085E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2108E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1890E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6762E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7938E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4408E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3278E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1012E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9055E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9709E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1427 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.7096E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1581 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.6216E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1139 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6279E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9581E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5174E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5298E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1957E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0505E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0372E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1987E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8130E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3087E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2108E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1889E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6761E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7939E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4406E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3278E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1010E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9052E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9706E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40652.64803 | 40652.64803 | 3.56332 | 3.56332 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6911.90712 | 6911.90712 | 0.35382 | 0.42469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30277.18957 | 30277.18957 | 2.65148 | 2.65148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14406.16531 | 14406.16531 | 0.74232 | 0.74232 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32506.02298 | 32506.02298 | 2.87152 | 2.87152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.69500 | 5.69875E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24902.80099 | 24902.80099 | 1.28801 | 1.28801 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10587.35000 | 10587.35000 | 0.93521 | 0.93521 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 11327.77579 | 11327.77579 | 0.58737 | 0.58737 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11269.30904 | 11269.30904 | 0.99544 | 0.99544 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.20500 | 5.69029E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7406.07110 | 7406.07110 | 0.38404 | 0.38404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12755.91102 | 12755.91102 | 1.12676 | 1.12676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11253.77965 | 11253.77965 | 0.58352 | 0.58352 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12831.28076 | 12831.28076 | 1.13341 | 1.13341 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7405.94448 | 7405.94448 | 0.38404 | 0.38404 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8493.65211 | 8493.65211 | 0.75028 | 0.75028 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8194.91407 | 8194.91407 | 0.42460 | 0.42460 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9427.56098 | 9427.56098 | 0.83277 | 0.83277 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5416.91492 | 5416.91492 | 0.28070 | 0.28070 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10348.28851 | 10348.28851 | 0.91411 | 0.91411 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8127.64889 | 8127.64889 | 0.42110 | 0.42110 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10073.48412 | 10073.48412 | 0.88983 | 0.88983 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.76000 | 5.69575E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5416.86886 | 5416.86886 | 0.28070 | 0.28070 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 9127.62719 | 9127.62719 | 0.80627 | 0.80627 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8763.06326 | 8763.06326 | 0.45409 | 0.45409 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10922.84722 | 10922.84722 | 0.96484 | 0.96484 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5763.45270 | 5763.45270 | 0.29869 | 0.29869 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11290.25320 | 11290.25320 | 0.99730 | 0.99730 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8697.69527 | 8697.69527 | 0.45069 | 0.45069 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11680.80070 | 11680.80070 | 1.03180 | 1.03180 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5763.39132 | 5763.39132 | 0.29868 | 0.29868 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 80812.82 | 6.26693 | 6.26693 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 20432.70 | 1.83178 | 1.83178 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 75168.20 | 5.59052 | 5.59052 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24384.22 | 2.24448 | 2.24448 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 85302.63 | 6.54085 | 6.54085 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 23741.88 | 3.22698 | 3.22698 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.56332 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21032 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.06900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56087 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81148E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29365.47707 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.65148 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28266 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80340 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75375 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34793E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22069.47907 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.87152 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26100 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.86146 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69599 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45979E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35381.93939 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93521 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16894 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28056 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45050 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25527E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16135.00178 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99544 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10048 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29863 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.79180E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10549.75105 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12676 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14022 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33803 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37391 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71721E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16029.35657 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13341 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.82426E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31764E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10549.57178 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75028 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21058 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22509 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56154 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80932E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11663.72385 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83277 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12011 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24983 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32028 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17218E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7710.83482 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91411 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17284 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27423 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46090 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20440E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11567.67975 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88983 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11240 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26695 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38974E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7710.77059 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80627 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19595 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24188 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52254 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94435E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12473.95137 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96484 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10367 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28945 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67525E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8204.98843 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99730 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15842 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29919 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42245 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.40502E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12380.61668 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03180 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.69331E-002 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30954 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.93054E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8503.07400 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.47516 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.08510 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.95032 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08510 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.26693 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 6.26693 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.33271 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.22585 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.94346 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.45170 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.24448 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.59052 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.59052 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.40148 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.53117 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.11870 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.06234 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.22698 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.54085 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 6.54085 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.49336 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 6.26693 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.59052 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 6.54085 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.26693 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.26693 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103739.89601 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.08877 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34576.50734 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 14913.97131 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 6.26693 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.59052 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.59052 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92543.01337 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.86332 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30844.58636 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 21673.72624 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.59052 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.54085 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 6.54085 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108274.24754 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 2.18006 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36087.80670 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 20266.95767 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 6.54085 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 101954.79 | 347884.19 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 5.9617 | 4.7140 | 3.1596 | 1.3370 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 90950.58 | 310336.26 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 5.3182 | 4.2052 | 2.8185 | 1.1927 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 106411.12 | 363089.80 | 11.20 | 2.80 | 3.21 | 3.38 | 3.53 | 9.54 | 10.95 | 11.55 | 12.05 | 6.2223 | 4.9201 | 3.2977 | 1.3955 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.8222345737E-002 | 0.1683499762 | Pass | Pass | 0.1328716627 | 0.3376799490 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1173211506 | 9.1722115681E-002 | Pass | Pass | 7.9582462704E-002 | 0.2593443321 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2762772231E-002 | 6.2046366048E-002 | Pass | Pass | 0.1395549637 | 0.3849652381 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5440954814E-002 | 4.7948885457E-002 | Pass | Pass | 2.0364047644 | 14.5503653229 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.5121134361E-002 | 0.1032263979 | Pass | Pass | 0.1050301730 | 0.3053564311 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.8705529979E-002 | 7.7708181162E-002 | Pass | Pass | 7.6796143510E-002 | 0.2640504744 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.7528867838E-002 | 6.9505554750E-002 | Pass | Pass | 7.4827964492E-002 | 0.2593869991 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1483356247 | 0.1907193715 | Pass | Pass | 7.9074965332E-002 | 0.2677021901 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2497685549 | 0.3001522311 | Pass | Pass | 7.7155094874E-002 | 0.2645603399 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1441873796 | 0.2164463813 | Pass | Pass | 7.2685896402E-002 | 0.2478753969 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.0755019867E-002 | 8.2566628956E-002 | Pass | Pass | 0.1320439727 | 0.3360132038 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1532102830 | 0.2203316287 | Pass | Pass | 0.1353432169 | 0.3406916660 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2425968907 | 0.3869616108 | Pass | Pass | 0.1407673696 | 0.3413704487 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1351712646 | 0.2212591990 | Pass | Pass | 0.1315005687 | 0.3293563377 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6066960364E-002 | 8.6261672382E-002 | Pass | Pass | 0.1040736244 | 0.3022484670 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1678711964 | 0.2461890437 | Pass | Pass | 0.1080081544 | 0.3095831385 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2539682734 | 0.3667350263 | Pass | Pass | 0.1077021585 | 0.3042713233 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1510056491 | 0.2389858354 | Pass | Pass | 0.1020483874 | 0.2928293672 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4566.48 | 100.36 | 0.00 | 2008.51 | 1219.54 | 7894.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.53 | 0.0000 | Y | 11.82 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.51 | 0.0000 | Y | 7.48 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.33 | 0.0000 | Y | 11.75 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.36 | 0.0000 | Y | 7.44 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.50 | 0.0000 | Y | 11.80 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.48 | 0.0000 | Y | 7.47 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.31 | 0.0000 | Y | 11.74 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.33 | 0.0000 | Y | 7.44 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.53 | 0.0000 | Y | 11.82 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.51 | 0.0000 | Y | 7.48 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.33 | 0.0000 | Y | 11.75 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.36 | 0.0000 | Y | 7.44 |
Interior Lighting Total | 9.0546 | 4982.19 | 45111.81 | 360.52 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.25 | AstronomicalClock | - | 41.81 | 41.81 | 3.33 | |
EXTERIOR_LIGHTS_B | 8043.62 | AstronomicalClock | - | 83.71 | 71.14 | 107.41 | |
Exterior Lighting Total | 8467.87 | 110.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103739.90 | 83059.89 | 20680.00 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92543.01 | 74095.05 | 18447.96 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108274.25 | 86690.35 | 21583.90 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 101954.8 | 2.80 | 9.54 | N/A | N/A | 11.20 | |
PACU_VAV_MID COOLING COIL | 90950.6 | 2.80 | 9.54 | N/A | N/A | 11.20 | |
PACU_VAV_TOP COOLING COIL | 106411.1 | 2.80 | 9.54 | N/A | N/A | 11.20 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 29365.48 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 22069.48 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 35381.94 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16135.00 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10549.75 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16029.36 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10549.57 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11663.72 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7710.83 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11567.68 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7710.77 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12473.95 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8204.99 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12380.62 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8503.07 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 14913.97 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 21673.73 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 20266.96 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.27 | 13629.87 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.59 | 12158.76 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.54 | 14225.61 | 2174.89 | 1.00 | 1.13 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 101954.79 | 2.80 | 9.54 | 11.20 | 5.9617 | 3.21 | 10.95 | 4.7140 | 3.38 | 11.55 | 3.1596 | 3.53 | 12.05 | 1.3370 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 90950.58 | 2.80 | 9.54 | 11.20 | 5.3182 | 3.21 | 10.95 | 4.2052 | 3.38 | 11.55 | 2.8185 | 3.53 | 12.05 | 1.1927 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106411.12 | 2.80 | 9.54 | 11.20 | 6.2223 | 3.21 | 10.95 | 4.9201 | 3.38 | 11.55 | 3.2977 | 3.53 | 12.05 | 1.3955 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40652.65 | 40652.65 | 41.33 | 3.563 | 3.563 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 25.11 | 0.00568 | 0.425 | 0.00 |
CORE_MID | 30277.19 | 30277.19 | 30.78 | 2.651 | 2.651 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 25.11 | 0.00568 | 0.425 | 0.00 |
CORE_TOP | 32506.02 | 32506.02 | 33.05 | 2.872 | 2.872 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 34.70 | 0.00570 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10587.35 | 10587.35 | 51.06 | 0.935 | 0.935 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00864 | 34.97 | 0.00570 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11269.31 | 11269.31 | 85.85 | 0.995 | 0.995 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00858 | 29.21 | 0.00569 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12755.91 | 12755.91 | 61.52 | 1.127 | 1.127 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00862 | 34.99 | 0.00570 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12831.28 | 12831.28 | 97.76 | 1.133 | 1.133 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00857 | 33.21 | 0.00570 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8493.65 | 8493.65 | 40.97 | 0.750 | 0.750 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00873 | 35.10 | 0.00570 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9427.56 | 9427.56 | 71.82 | 0.833 | 0.833 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00863 | 29.59 | 0.00569 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10348.29 | 10348.29 | 49.91 | 0.914 | 0.914 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00869 | 34.99 | 0.00570 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 10073.48 | 10073.48 | 76.75 | 0.890 | 0.890 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00862 | 32.76 | 0.00570 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9127.63 | 9127.63 | 44.02 | 0.806 | 0.806 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00868 | 35.10 | 0.00570 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10922.85 | 10922.85 | 83.21 | 0.965 | 0.965 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00859 | 28.44 | 0.00569 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11290.25 | 11290.25 | 54.45 | 0.997 | 0.997 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 34.76 | 0.00570 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11680.80 | 11680.80 | 88.99 | 1.032 | 1.032 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00859 | 33.21 | 0.00570 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6911.91 | 6911.91 | 7.03 | 0.354 | 0.425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_MID | 14406.17 | 14406.17 | 14.65 | 0.742 | 0.742 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
CORE_TOP | 24902.80 | 24902.80 | 25.32 | 1.288 | 1.288 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11327.78 | 11327.78 | 54.63 | 0.587 | 0.587 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7406.07 | 7406.07 | 56.42 | 0.384 | 0.384 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11253.78 | 11253.78 | 54.28 | 0.584 | 0.584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7405.94 | 7405.94 | 56.42 | 0.384 | 0.384 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8194.91 | 8194.91 | 39.52 | 0.425 | 0.425 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5416.91 | 5416.91 | 41.27 | 0.281 | 0.281 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8127.65 | 8127.65 | 39.20 | 0.421 | 0.421 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5416.87 | 5416.87 | 41.27 | 0.281 | 0.281 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8763.06 | 8763.06 | 42.26 | 0.454 | 0.454 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5763.45 | 5763.45 | 43.91 | 0.299 | 0.299 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -7.90 | 0.00234 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8697.70 | 8697.70 | 41.95 | 0.451 | 0.451 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -7.90 | 0.00234 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5763.39 | 5763.39 | 43.91 | 0.299 | 0.299 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -7.90 | 0.00234 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 6.27 | 6.27 | 1.83 | 1.83 | 6.2669 | 2.0851 | 6.2669 | 0.3327 | 0.3000 |
PACU_VAV_MID | 5.59 | 5.59 | 2.24 | 2.24 | 5.5905 | 2.2445 | 5.5905 | 0.4015 | 0.3000 |
PACU_VAV_TOP | 6.54 | 6.54 | 3.23 | 3.23 | 6.5408 | 3.2270 | 6.5408 | 0.4934 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29365.477 | 29365.477 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29365.48 | 11666.32 | 0.424691 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 6911.91 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 22069.479 | 22069.479 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22069.48 | 20391.74 | 0.742324 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 14406.17 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 35381.939 | 35381.939 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35381.94 | 35381.94 | 1.288015 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 24902.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16135.002 | 16135.002 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16135.00 | 16135.00 | 0.587365 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774805 | 41.2167 | 11327.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10549.751 | 10549.751 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10549.75 | 10549.75 | 0.384044 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774361 | 41.1935 | 7406.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16029.357 | 16029.357 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16029.36 | 16029.36 | 0.583519 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774640 | 41.2080 | 11253.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10549.572 | 10549.572 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10549.57 | 10549.57 | 0.384038 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00774360 | 41.1934 | 7405.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 11663.724 | 11663.724 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11663.72 | 11663.72 | 0.424597 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778444 | 41.4071 | 8194.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7710.835 | 7710.835 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7710.83 | 7710.83 | 0.280699 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778882 | 41.4300 | 5416.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11567.680 | 11567.680 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11567.68 | 11567.68 | 0.421100 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778148 | 41.3915 | 8127.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7710.771 | 7710.771 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7710.77 | 7710.77 | 0.280696 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00778882 | 41.4301 | 5416.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 12473.951 | 12473.951 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12473.95 | 12473.95 | 0.454091 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00771794 | 41.0583 | 8763.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8204.988 | 8204.988 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8204.99 | 8204.99 | 0.298688 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00771759 | 41.0565 | 5763.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 12380.617 | 12380.617 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12380.62 | 12380.62 | 0.450694 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00771516 | 41.0437 | 8697.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8503.074 | 8503.074 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8503.07 | 8204.90 | 0.298684 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00771759 | 41.0565 | 5763.39 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 103739.896 | 83059.893 | 6.266927 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 100022.29 | 100022.29 | 6.266927 | 25.77 | 14.79 | 0.00826971 | 10.65 | 9.26 | 0.00826971 | 35.10 | 0.00569938 | 15.77 | 15.9664 | 24.00 | 0.00875881 | 38.7665 | 70853.72 | 0.00 | 106969.76 | 76640.18 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 14913.971 | 14913.971 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14913.97 | 14913.97 | 1.880078 | 4.83 | 2.69 | 0.00471529 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 53.2212 | 19.61 | 0.00740969 | 42.9783 | 13243.96 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 92543.013 | 74095.050 | 5.590523 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 89226.66 | 89226.66 | 5.590523 | 26.39 | 14.87 | 0.00811366 | 10.65 | 9.10 | 0.00811366 | 35.10 | 0.00569938 | 15.77 | 21.3785 | 24.00 | 0.00877479 | 38.8359 | 62937.19 | 0.00 | 95424.27 | 68368.23 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 21673.726 | 21673.726 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21673.73 | 21673.73 | 1.677157 | -0.18 | -1.16 | 0.00382402 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 71.2617 | 19.60 | 0.00731629 | 42.4648 | 19128.56 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108274.248 | 86690.346 | 6.540847 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 104512.79 | 104512.79 | 6.540847 | 25.96 | 14.78 | 0.00818657 | 10.65 | 9.17 | 0.00818657 | 34.97 | 0.00569918 | 15.73 | 17.7793 | 24.00 | 0.00872706 | 38.6275 | 73751.46 | 0.00 | 111645.28 | 79990.03 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 20266.958 | 20266.958 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20266.96 | 20266.96 | 1.962254 | 2.42 | 1.13 | 0.00446530 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 59.2645 | 17.60 | 0.00746351 | 49.0894 | 23410.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 29365.477 | 29365.477 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29365.48 | 11666.32 | 1.0000 | 0.42061783 | 0.424691 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29365.48 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 6911.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 22069.479 | 22069.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22069.48 | 20391.74 | 1.0000 | 0.73520431 | 0.742324 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22069.48 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 14406.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 35381.939 | 35381.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 35381.94 | 35381.94 | 1.0000 | 1.27566127 | 1.288015 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35381.94 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 24902.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16135.002 | 16135.002 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16135.00 | 16135.00 | 1.0000 | 0.58173173 | 0.587365 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16135.00 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774805 | 21.00 | 0.00774805 | 41.2167 | 11327.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10549.751 | 10549.751 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10549.75 | 10549.75 | 1.0000 | 0.38036097 | 0.384044 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10549.75 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774361 | 21.00 | 0.00774361 | 41.1935 | 7406.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16029.357 | 16029.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16029.36 | 16029.36 | 1.0000 | 0.57792280 | 0.583519 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16029.36 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774640 | 21.00 | 0.00774640 | 41.2080 | 11253.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10549.572 | 10549.572 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10549.57 | 10549.57 | 1.0000 | 0.38035451 | 0.384038 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10549.57 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00774360 | 21.00 | 0.00774360 | 41.1934 | 7405.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11663.724 | 11663.724 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11663.72 | 11663.72 | 1.0000 | 0.42052417 | 0.424597 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11663.72 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778444 | 21.00 | 0.00778444 | 41.4071 | 8194.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7710.835 | 7710.835 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7710.83 | 7710.83 | 1.0000 | 0.27800662 | 0.280699 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7710.83 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778882 | 21.00 | 0.00778882 | 41.4300 | 5416.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11567.680 | 11567.680 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11567.68 | 11567.68 | 1.0000 | 0.41706140 | 0.421100 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11567.68 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778148 | 21.00 | 0.00778148 | 41.3915 | 8127.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7710.771 | 7710.771 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7710.77 | 7710.77 | 1.0000 | 0.27800430 | 0.280696 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7710.77 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00778882 | 21.00 | 0.00778882 | 41.4301 | 5416.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12473.951 | 12473.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12473.95 | 12473.95 | 1.0000 | 0.44973613 | 0.454091 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12473.95 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771794 | 21.00 | 0.00771794 | 41.0583 | 8763.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8204.988 | 8204.988 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8204.99 | 8204.99 | 1.0000 | 0.29582284 | 0.298688 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8204.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771759 | 21.00 | 0.00771759 | 41.0565 | 5763.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12380.617 | 12380.617 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12380.62 | 12380.62 | 1.0000 | 0.44637104 | 0.450694 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12380.62 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771516 | 21.00 | 0.00771516 | 41.0437 | 8697.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8503.074 | 8503.074 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8503.07 | 8204.90 | 1.0000 | 0.29581974 | 0.298684 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8503.07 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771759 | 21.00 | 0.00771759 | 41.0565 | 5763.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103739.896 | 83059.893 | 6.266927 | -999.0 | -999.000 | -999.0000 | 1.07390 | 1.00000 | 1020.2130 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.266927 | 6.20682036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 100022.29 | 100022.29 | 0.9642 | 6.20682036 | 6.266927 | 25.77 | 14.79 | 0.00826971 | 46976.6 | 10.65 | 9.26 | 0.00826971 | 31544.8 | -999.0 | -999.00 | -999.00 | -999.00 | 13629.867 | 86392.42 | 35.10 | 0.00569938 | 15.77 | 1.00060000 | 15.9664 | 24.00 | 0.00875881 | 24.00 | 0.00875881 | 38.7665 | 70853.72 | 0.00 | 106969.76 | 76640.18 | 5.96169787 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14913.971 | 14913.971 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_BOT FAN | Fan:VariableVolume | 6.266927 | 6.20682036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14913.97 | 14913.97 | 1.0000 | 1.86204611 | 1.880078 | 4.83 | 2.69 | 0.00471529 | 16687.6 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14913.97 | -7.90 | 0.00234317 | -7.90 | 1.00060000 | 53.2212 | 19.31 | 0.00741410 | 19.61 | 0.00740969 | 42.9783 | 13243.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92543.013 | 74095.050 | 5.590523 | -999.0 | -999.000 | -999.0000 | 1.03418 | 1.00000 | 1019.9229 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.590523 | 5.53690413 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 89226.66 | 89226.66 | 0.9642 | 5.53690413 | 5.590523 | 26.39 | 14.87 | 0.00811366 | 47202.8 | 10.65 | 9.10 | 0.00811366 | 31150.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12158.764 | 77067.89 | 35.10 | 0.00569938 | 15.77 | 1.19517000 | 21.3785 | 24.00 | 0.00877479 | 24.00 | 0.00877479 | 38.8359 | 62937.19 | 0.00 | 95424.27 | 68368.23 | 5.31823828 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21673.726 | 21673.726 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.590523 | 5.53690413 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21673.73 | 21673.73 | 1.0000 | 1.66107124 | 1.677157 | -0.18 | -1.16 | 0.00382402 | 9376.5 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21673.73 | -7.90 | 0.00234317 | -7.90 | 1.19517000 | 71.2617 | 18.95 | 0.00749603 | 19.60 | 0.00731629 | 42.4648 | 19128.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108274.248 | 86690.346 | 6.540847 | -999.0 | -999.000 | -999.0000 | 1.06291 | 1.00000 | 1020.0584 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.540847 | 6.47811333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 104512.79 | 104512.79 | 0.9653 | 6.47811333 | 6.540847 | 25.96 | 14.78 | 0.00818657 | 46951.3 | 10.65 | 9.17 | 0.00818657 | 31334.9 | -999.0 | -999.00 | -999.00 | -999.00 | 14225.612 | 90287.18 | 34.97 | 0.00569918 | 15.73 | 1.16292000 | 17.7793 | 24.00 | 0.00872706 | 24.00 | 0.00872706 | 38.6275 | 73751.46 | 0.00 | 111645.28 | 79990.03 | 6.22227683 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.09 | 13.30 | 0.00919000 | 37379.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20266.958 | 20266.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PACU_VAV_TOP FAN | Fan:VariableVolume | 6.540847 | 6.47811333 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20266.96 | 20266.96 | 1.0000 | 1.94343400 | 1.962254 | 2.42 | 1.13 | 0.00446530 | 13621.3 | 12.80 | 9.86 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20266.96 | -7.90 | 0.00234317 | -7.90 | 1.16292000 | 59.2645 | 17.44 | 0.00755269 | 17.60 | 0.00746351 | 49.0894 | 23410.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.27 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.59 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 6.54 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2020.83 | 2461.67 | 8.33 |
CORE_MID | 1778.50 | 3204.83 | 30.83 |
CORE_TOP | 2092.00 | 3440.17 | 464.50 |
PERIMETER_TOP_ZN_3 | 3137.33 | 3794.50 | 1597.17 |
PERIMETER_TOP_ZN_2 | 3026.50 | 3464.17 | 1211.83 |
PERIMETER_TOP_ZN_1 | 2879.00 | 2807.83 | 854.50 |
PERIMETER_TOP_ZN_4 | 2902.83 | 3817.67 | 1367.67 |
PERIMETER_BOT_ZN_3 | 2724.83 | 3761.67 | 1126.83 |
PERIMETER_BOT_ZN_2 | 2685.67 | 3173.50 | 650.83 |
PERIMETER_BOT_ZN_1 | 2377.83 | 2894.67 | 416.67 |
PERIMETER_BOT_ZN_4 | 2508.50 | 3426.00 | 693.83 |
PERIMETER_MID_ZN_3 | 2668.83 | 3557.17 | 978.00 |
PERIMETER_MID_ZN_2 | 2279.83 | 2912.17 | 754.50 |
PERIMETER_MID_ZN_1 | 2675.00 | 2466.33 | 466.83 |
PERIMETER_MID_ZN_4 | 2529.83 | 3565.00 | 861.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4647.83 | 4484.50 | 1908.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5.50 | 7.67 | 0.33 | 5.00 |
PERIMETER_TOP_ZN_2 | 5.17 | 40.00 | 0.00 | 39.33 |
PERIMETER_TOP_ZN_1 | 1.67 | 47.67 | 0.00 | 46.00 |
PERIMETER_TOP_ZN_4 | 4.33 | 31.67 | 0.00 | 20.50 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 32.83 | 0.00 | 32.50 |
PERIMETER_BOT_ZN_1 | 167.67 | 122.67 | 167.67 | 122.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 23.17 | 0.00 | 14.50 |
PERIMETER_MID_ZN_3 | 0.33 | 2.33 | 0.00 | 1.33 |
PERIMETER_MID_ZN_2 | 0.33 | 35.50 | 0.00 | 35.50 |
PERIMETER_MID_ZN_1 | 0.00 | 69.50 | 0.00 | 68.83 |
PERIMETER_MID_ZN_4 | 0.33 | 29.83 | 0.00 | 20.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 173.67 | 282.67 | 168.00 | 262.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 1.216 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.798 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.794 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 1.091 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 2.057 | 0.088 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 1.769 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 2.049 | 0.087 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.873 | 0.044 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 1.731 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 1.335 | 1.317 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 1.588 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 1.003 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 1.904 | 0.078 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 1.688 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 1.896 | 0.073 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 19764414.71 | 0.00 | 19764414.71 | 0.00 | 19764414.71 | 13393058.27 | 5093.65 | 46.29 | 3620.05 | 139.97 |
CORE_MID | 12866662.69 | 0.00 | 12866662.69 | 0.00 | 12866662.69 | 13393058.27 | 5979.99 | 36.99 | 2743.02 | 82.12 |
CORE_TOP | 12742362.94 | 0.00 | 12742362.94 | 0.00 | 12742362.94 | 13393058.27 | 5927.90 | 34.55 | 2797.56 | 90.37 |
PERIMETER_TOP_ZN_3 | 3703001.67 | 0.00 | 3703001.67 | 559603.69 | 4262605.36 | 2823374.22 | 4037.63 | 15.16 | 4707.20 | 90.37 |
PERIMETER_TOP_ZN_2 | 4409057.53 | 0.00 | 4409057.53 | 373066.89 | 4782124.41 | 1787429.43 | 3918.95 | 2.32 | 4838.73 | 90.37 |
PERIMETER_TOP_ZN_1 | 5972174.88 | 0.00 | 5972174.88 | 559603.69 | 6531778.57 | 2823374.22 | 3980.83 | 5.69 | 4773.48 | 90.37 |
PERIMETER_TOP_ZN_4 | 4409942.24 | 0.00 | 4409942.24 | 373066.89 | 4783009.13 | 1787312.18 | 3913.86 | 9.57 | 4836.57 | 90.37 |
PERIMETER_BOT_ZN_3 | 3019938.95 | 0.00 | 3019938.95 | 297538.75 | 3317477.70 | 2823374.22 | 5125.88 | 75.31 | 3558.81 | 139.97 |
PERIMETER_BOT_ZN_2 | 3774699.63 | 0.00 | 3774699.63 | 198357.98 | 3973057.61 | 1787429.43 | 3787.38 | 8.88 | 4963.75 | 139.97 |
PERIMETER_BOT_ZN_1 | 4584656.58 | 0.00 | 4584656.58 | 4564926.59 | 9149583.17 | 2823374.22 | 3967.14 | 34.07 | 4758.78 | 139.97 |
PERIMETER_BOT_ZN_4 | 3484304.03 | 0.00 | 3484304.03 | 198357.98 | 3682662.01 | 1787312.18 | 3936.65 | 31.25 | 4792.10 | 139.97 |
PERIMETER_MID_ZN_3 | 3415500.16 | 0.00 | 3415500.16 | 465827.44 | 3881327.61 | 2823374.22 | 3996.78 | 30.39 | 4732.83 | 82.12 |
PERIMETER_MID_ZN_2 | 4350758.62 | 0.00 | 4350758.62 | 310549.76 | 4661308.38 | 1787429.43 | 3810.09 | 1.50 | 4948.41 | 991.12 |
PERIMETER_MID_ZN_1 | 5714425.88 | 0.00 | 5714425.88 | 465827.44 | 6180253.32 | 2823374.22 | 3898.79 | 7.97 | 4853.23 | 82.12 |
PERIMETER_MID_ZN_4 | 4102249.66 | 0.00 | 4102249.66 | 310549.76 | 4412799.42 | 1787312.18 | 3825.13 | 12.33 | 4922.54 | 82.12 |
Total Facility | 96314150.19 | 0.00 | 96314150.19 | 8677276.86 | 0.10E+09 | 67843644.98 | 6219.64 | 309.03 | 5143.75 | 1110.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.8977 | 0.0000 | 0.8977 | 0.0000 | 0.8977 | 0.4247 | 2415.79 | 46.29 | 3480.92 |
CORE_MID | 0.5895 | 0.0000 | 0.5895 | 0.0000 | 0.5895 | 0.4247 | 3243.44 | 36.99 | 2662.57 |
CORE_TOP | 0.5868 | 0.0000 | 0.5868 | 0.0000 | 0.5868 | 0.4247 | 3167.13 | 34.55 | 2741.32 |
PERIMETER_TOP_ZN_3 | 0.1703 | 0.0000 | 0.1703 | 0.0130 | 0.1833 | 0.0895 | 1276.87 | 15.16 | 4650.97 |
PERIMETER_TOP_ZN_2 | 0.2032 | 0.0000 | 0.2032 | 0.0087 | 0.2118 | 0.0567 | 1158.19 | 2.32 | 4782.49 |
PERIMETER_TOP_ZN_1 | 0.2758 | 0.0000 | 0.2758 | 0.0130 | 0.2888 | 0.0895 | 1220.06 | 5.69 | 4717.24 |
PERIMETER_TOP_ZN_4 | 0.2027 | 0.0000 | 0.2027 | 0.0087 | 0.2114 | 0.0567 | 1153.10 | 9.57 | 4780.33 |
PERIMETER_BOT_ZN_3 | 0.1362 | 0.0000 | 0.1362 | 0.0069 | 0.1431 | 0.0895 | 2448.02 | 75.31 | 3419.67 |
PERIMETER_BOT_ZN_2 | 0.1709 | 0.0000 | 0.1709 | 0.0046 | 0.1755 | 0.0567 | 1109.52 | 8.88 | 4824.61 |
PERIMETER_BOT_ZN_1 | 0.2082 | 0.0000 | 0.2082 | 0.2064 | 0.4146 | 0.0895 | 1289.28 | 34.07 | 4619.65 |
PERIMETER_BOT_ZN_4 | 0.1569 | 0.0000 | 0.1569 | 0.0046 | 0.1615 | 0.0567 | 1259.56 | 30.47 | 4652.96 |
PERIMETER_MID_ZN_3 | 0.1564 | 0.0000 | 0.1564 | 0.0108 | 0.1672 | 0.0895 | 1260.23 | 30.39 | 4652.38 |
PERIMETER_MID_ZN_2 | 0.1881 | 0.0000 | 0.1881 | 0.0078 | 0.1958 | 0.0567 | 1073.57 | 1.50 | 3958.94 |
PERIMETER_MID_ZN_1 | 0.2630 | 0.0000 | 0.2630 | 0.0108 | 0.2739 | 0.0895 | 1162.25 | 7.97 | 4772.78 |
PERIMETER_MID_ZN_4 | 0.1875 | 0.0000 | 0.1875 | 0.0072 | 0.1947 | 0.0567 | 1088.60 | 12.33 | 4842.07 |
Total Facility | 4.3932 | 0.0000 | 4.3932 | 0.3024 | 4.6956 | 2.1513 | 3433.31 | 308.24 | 4977.98 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33966971.65 | 0.00 | 33966971.65 | 22614548.33 | 3850.50 | 174.12 | 4735.38 | 139.97 |
PACU_VAV_MID | 29868352.61 | 0.00 | 29868352.61 | 22614548.33 | 3911.29 | 7.22 | 4841.49 | 82.12 |
PACU_VAV_TOP | 30640247.43 | 0.00 | 30640247.43 | 22614548.33 | 3967.23 | 5.98 | 4786.78 | 90.35 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5399 | 0.0000 | 1.5399 | 0.7171 | 1172.63 | 174.12 | 4596.24 |
PACU_VAV_MID | 1.3692 | 0.0000 | 1.3692 | 0.7171 | 1174.75 | 7.22 | 4761.03 |
PACU_VAV_TOP | 1.4114 | 0.0000 | 1.4114 | 0.7171 | 1206.47 | 5.98 | 4730.54 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3766.85 | 0.00 | 0.00 | 0.00 | 1223.22 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 3290.79 | 0.00 | 0.00 | 0.00 | 1664.64 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 3330.24 | 0.00 | 0.00 | 0.00 | 1625.25 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.2716 | 0.0000 | 0.0000 | 0.0000 | 0.7481 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.1178 | 0.0000 | 0.0000 | 0.0000 | 0.8072 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.1893 | 0.0000 | 0.0000 | 0.0000 | 0.7979 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
Electricity:Building | 1122.56 | 15718.93 | 01-JAN-08:30 | 81934.95 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 329.05 | 4741.03 | 01-JAN-00:10 | 25654.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1122.56 | 15718.93 | 01-JAN-08:30 | 81934.95 | 02-NOV-07:10 |
InteriorLights:Electricity | 360.52 | 1693.55 | 01-JAN-08:30 | 36137.71 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 360.52 | 1693.55 | 01-JAN-08:30 | 36137.71 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 360.52 | 1693.55 | 01-JAN-08:30 | 36137.71 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 360.52 | 1693.55 | 01-JAN-08:30 | 36137.71 | 13-NOV-17:00 |
Electricity:Zone:CORE_MID | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 38.51 | 553.47 | 01-JAN-08:30 | 3009.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.82 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.82 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.37 | 350.37 | 01-JAN-07:40 | 1905.39 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.48 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.48 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 38.43 | 553.47 | 01-JAN-07:40 | 3009.79 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.75 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.75 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.34 | 350.37 | 01-JAN-08:30 | 1905.32 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 38.49 | 553.47 | 01-JAN-08:30 | 3009.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.80 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.80 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.36 | 350.37 | 01-JAN-07:40 | 1905.39 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.47 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.47 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 38.43 | 553.47 | 01-JAN-07:40 | 3009.79 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.74 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.74 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.33 | 350.37 | 01-JAN-08:30 | 1905.32 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 38.51 | 553.47 | 01-JAN-08:30 | 3009.80 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.82 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.82 | 51.50 | 01-JAN-08:30 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 24.37 | 350.37 | 01-JAN-07:40 | 1905.39 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.48 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.48 | 32.61 | 01-JAN-07:40 | 952.10 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 38.43 | 553.47 | 01-JAN-07:40 | 3009.79 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.75 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.75 | 51.50 | 01-JAN-07:40 | 1503.90 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.34 | 350.37 | 01-JAN-08:30 | 1905.32 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.44 | 32.60 | 01-JAN-08:30 | 952.03 | 13-NOV-17:00 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 488.81 | 285.40 | 01-JAN-00:10 | 125172.60 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1358.60 | 05-DEC-17:00 |
Transformer:ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1358.60 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
ElectricityPurchased:Plant | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
Cogeneration:ElectricityPurchased | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
General:Cogeneration:ElectricityPurchased | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
ElectricityNet:Plant | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
Cogeneration:ElectricityNet | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
General:Cogeneration:ElectricityNet | 1722.13 | 16005.15 | 26-MAR-17:20 | 187736.23 | 28-JUN-14:50 |
Heating:Electricity | 68.94 | 0.00 | 01-JAN-00:10 | 119707.51 | 06-FEB-07:10 |
General:Heating:Electricity | 68.94 | 0.00 | 01-JAN-00:10 | 119707.51 | 06-FEB-07:10 |
Fans:Electricity | 150.51 | 0.00 | 01-JAN-00:10 | 35650.41 | 26-JUN-15:30 |
General:Fans:Electricity | 150.51 | 0.00 | 01-JAN-00:10 | 35650.41 | 26-JUN-15:30 |
ExteriorLights:Electricity | 110.74 | 0.00 | 01-JAN-07:20 | 8467.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 110.74 | 0.00 | 01-JAN-07:20 | 8467.87 | 01-JAN-06:10 |
Cooling:Electricity | 250.43 | 0.00 | 01-JAN-00:10 | 81946.00 | 28-JUN-16:00 |
General:Cooling:Electricity | 250.43 | 0.00 | 01-JAN-00:10 | 81946.00 | 28-JUN-16:00 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 10.13 | 0.00 | 01-JAN-00:10 | 1015.47 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 138.06 | 1156.00 | 08-FEB-17:10 | 54743.11 | 21-JAN-07:10 |
NaturalGas:HVAC | 32.52 | 0.00 | 01-JAN-00:10 | 47183.45 | 15-DEC-07:20 |
Heating:NaturalGas | 32.52 | 0.00 | 01-JAN-00:10 | 47183.45 | 15-DEC-07:20 |
General:Heating:NaturalGas | 32.52 | 0.00 | 01-JAN-00:10 | 47183.45 | 15-DEC-07:20 |
NaturalGas:Plant | 105.54 | 1156.00 | 02-JAN-07:10 | 9408.62 | 08-FEB-12:10 |
WaterSystems:NaturalGas | 105.54 | 1156.00 | 02-JAN-07:10 | 9408.62 | 08-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 105.54 | 1156.00 | 02-JAN-07:10 | 9408.62 | 08-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2540.19 | 0.00 | 01-JAN-00:10 | 437397.74 | 05-SEP-13:30 |
EnergyTransfer:Building | 1435.04 | 0.00 | 01-JAN-00:10 | 184492.53 | 07-AUG-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 276.28 | 0.00 | 01-JAN-00:10 | 27987.45 | 05-SEP-08:00 |
Heating:EnergyTransfer | 47.49 | 0.00 | 01-JAN-00:10 | 104498.71 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 47.49 | 0.00 | 01-JAN-00:10 | 104498.71 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1387.55 | 0.00 | 01-JAN-00:10 | 184492.53 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 276.28 | 0.00 | 01-JAN-00:10 | 27987.45 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1387.55 | 0.00 | 01-JAN-00:10 | 184492.53 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 276.28 | 0.00 | 01-JAN-00:10 | 27987.45 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.59 | 0.00 | 01-JAN-00:10 | 13112.96 | 28-JUN-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.30 | 0.00 | 01-JAN-00:10 | 10281.00 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 12.30 | 0.00 | 01-JAN-00:10 | 10281.00 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.28 | 0.00 | 01-JAN-00:10 | 13112.96 | 28-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.28 | 0.00 | 01-JAN-00:10 | 13112.96 | 28-JUN-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.34 | 0.00 | 01-JAN-00:10 | 6069.26 | 07-AUG-15:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.79 | 0.00 | 01-JAN-00:10 | 3906.83 | 26-DEC-10:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.79 | 0.00 | 01-JAN-00:10 | 3906.83 | 26-DEC-10:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.54 | 0.00 | 01-JAN-00:10 | 6069.26 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.54 | 0.00 | 01-JAN-00:10 | 6069.26 | 07-AUG-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 36.21 | 0.00 | 01-JAN-00:10 | 6025.93 | 05-JUL-15:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.80 | 0.00 | 01-JAN-00:10 | 3112.38 | 17-JAN-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.80 | 0.00 | 01-JAN-00:10 | 3112.38 | 17-JAN-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.41 | 0.00 | 01-JAN-00:10 | 6025.93 | 05-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.41 | 0.00 | 01-JAN-00:10 | 6025.93 | 05-JUL-15:30 |
EnergyTransfer:Zone:CORE_MID | 177.63 | 0.00 | 01-JAN-00:10 | 20425.57 | 05-JUL-07:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 5118.44 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 5118.44 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 177.61 | 0.00 | 01-JAN-00:10 | 20425.57 | 05-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 177.61 | 0.00 | 01-JAN-00:10 | 20425.57 | 05-JUL-07:50 |
EnergyTransfer:Zone:CORE_TOP | 172.18 | 0.00 | 01-JAN-00:10 | 22619.58 | 07-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 1.09 | 0.00 | 01-JAN-00:10 | 16987.32 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 1.09 | 0.00 | 01-JAN-00:10 | 16987.32 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 171.09 | 0.00 | 01-JAN-00:10 | 22619.58 | 07-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 171.09 | 0.00 | 01-JAN-00:10 | 22619.58 | 07-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.06 | 0.00 | 01-JAN-00:10 | 9406.53 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.07 | 0.00 | 01-JAN-00:10 | 9406.53 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 5.07 | 0.00 | 01-JAN-00:10 | 9406.53 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.99 | 0.00 | 01-JAN-00:10 | 8349.82 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.99 | 0.00 | 01-JAN-00:10 | 8349.82 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.88 | 0.00 | 01-JAN-00:10 | 10453.21 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.28 | 0.00 | 01-JAN-00:10 | 6510.90 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 2.28 | 0.00 | 01-JAN-00:10 | 6510.90 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.60 | 0.00 | 01-JAN-00:10 | 10453.21 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.60 | 0.00 | 01-JAN-00:10 | 10453.21 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.50 | 0.00 | 01-JAN-00:10 | 13706.97 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 2.61 | 0.00 | 01-JAN-00:10 | 9277.88 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 2.61 | 0.00 | 01-JAN-00:10 | 9277.88 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.90 | 0.00 | 01-JAN-00:10 | 13706.97 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.90 | 0.00 | 01-JAN-00:10 | 13706.97 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.79 | 0.00 | 01-JAN-00:10 | 11613.44 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.86 | 0.00 | 01-JAN-00:10 | 6399.17 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.86 | 0.00 | 01-JAN-00:10 | 6399.17 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.92 | 0.00 | 01-JAN-00:10 | 11613.44 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.92 | 0.00 | 01-JAN-00:10 | 11613.44 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.38 | 0.00 | 01-JAN-00:10 | 6758.99 | 31-JUL-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.19 | 0.00 | 01-JAN-00:10 | 5306.98 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.19 | 0.00 | 01-JAN-00:10 | 5306.98 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.19 | 0.00 | 01-JAN-00:10 | 6758.99 | 31-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.19 | 0.00 | 01-JAN-00:10 | 6758.99 | 31-JUL-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.31 | 0.00 | 01-JAN-00:10 | 8680.70 | 05-JUL-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 2909.58 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.33 | 0.00 | 01-JAN-00:10 | 2909.58 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.98 | 0.00 | 01-JAN-00:10 | 8680.70 | 05-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 48.98 | 0.00 | 01-JAN-00:10 | 8680.70 | 05-JUL-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 73.96 | 0.00 | 01-JAN-00:10 | 12674.86 | 28-JUN-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.85 | 0.00 | 01-JAN-00:10 | 11761.60 | 22-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 9.85 | 0.00 | 01-JAN-00:10 | 11761.60 | 22-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.11 | 0.00 | 01-JAN-00:10 | 12674.86 | 28-JUN-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 64.11 | 0.00 | 01-JAN-00:10 | 12674.86 | 28-JUN-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 45.97 | 0.00 | 01-JAN-00:10 | 8936.20 | 21-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.39 | 0.00 | 01-JAN-00:10 | 2903.05 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.39 | 0.00 | 01-JAN-00:10 | 2903.05 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 45.59 | 0.00 | 01-JAN-00:10 | 8936.20 | 21-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 45.59 | 0.00 | 01-JAN-00:10 | 8936.20 | 21-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 45.82 | 0.00 | 01-JAN-00:10 | 7476.07 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.18 | 0.00 | 01-JAN-00:10 | 5790.05 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.18 | 0.00 | 01-JAN-00:10 | 5790.05 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.64 | 0.00 | 01-JAN-00:10 | 7476.07 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 44.64 | 0.00 | 01-JAN-00:10 | 7476.07 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 53.57 | 0.00 | 01-JAN-00:10 | 10198.46 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.55 | 0.00 | 01-JAN-00:10 | 3735.63 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.55 | 0.00 | 01-JAN-00:10 | 3735.63 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 53.01 | 0.00 | 01-JAN-00:10 | 10198.46 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 53.01 | 0.00 | 01-JAN-00:10 | 10198.46 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 80.04 | 0.00 | 01-JAN-00:10 | 12472.13 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.51 | 0.00 | 01-JAN-00:10 | 5170.13 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.51 | 0.00 | 01-JAN-00:10 | 5170.13 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.54 | 0.00 | 01-JAN-00:10 | 12472.13 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 79.54 | 0.00 | 01-JAN-00:10 | 12472.13 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.54 | 0.00 | 01-JAN-00:10 | 10818.33 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.67 | 0.00 | 01-JAN-00:10 | 3679.65 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.67 | 0.00 | 01-JAN-00:10 | 3679.65 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.87 | 0.00 | 01-JAN-00:10 | 10818.33 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 50.87 | 0.00 | 01-JAN-00:10 | 10818.33 | 28-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
EnergyTransfer:HVAC | 1057.56 | 0.00 | 01-JAN-00:10 | 271397.34 | 05-SEP-13:00 |
HeatingCoils:EnergyTransfer | 94.96 | 0.00 | 01-JAN-00:10 | 151182.66 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 962.61 | 0.00 | 01-JAN-00:10 | 271397.34 | 05-SEP-13:00 |
EnergyTransfer:Plant | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
WaterSystems:EnergyTransfer | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 47.58 | 0.00 | 01-JAN-00:10 | 6168.50 | 07-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -276.276 | 0.000 | 0.000 | 32.773 | 81.703 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -85.543 |
CORE_MID | 0.000 | 0.000 | 0.020 | -177.610 | 0.000 | 0.000 | 33.254 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -63.968 |
CORE_TOP | 0.000 | 0.000 | 1.086 | -171.091 | 0.000 | 0.000 | 33.956 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -72.254 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 5.073 | -43.985 | 0.000 | 0.000 | 7.467 | 11.817 | 26.688 | 23.582 | 0.000 | 0.247 | 0.752 | 0.000 | -26.348 | 0.000 | -5.293 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 2.278 | -51.603 | 0.000 | 0.000 | 4.649 | 7.476 | 16.895 | 53.893 | 0.000 | 0.168 | 0.000 | 0.000 | -16.648 | 0.000 | -3.623 | -13.484 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 2.606 | -77.897 | 0.000 | 0.000 | 7.164 | 11.745 | 26.688 | 95.902 | 0.000 | 0.243 | 0.003 | 0.000 | -25.826 | 0.000 | -5.698 | -34.927 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.865 | -49.919 | 0.000 | 0.000 | 4.762 | 7.442 | 16.895 | 49.929 | 0.000 | 0.166 | 0.000 | 0.000 | -17.704 | 0.000 | -3.635 | -10.801 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 1.192 | -39.192 | 0.000 | 0.000 | 7.391 | 11.804 | 26.688 | 23.714 | 0.000 | 0.141 | 0.001 | 0.000 | -27.564 | 0.000 | -2.987 | -1.187 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.329 | -48.982 | 0.000 | 0.000 | 4.584 | 7.469 | 16.895 | 53.914 | 0.000 | 0.089 | 0.000 | 0.000 | -17.923 | 0.000 | -2.103 | -14.272 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 9.848 | -64.105 | 0.000 | 0.000 | 7.257 | 11.738 | 26.688 | 96.425 | 0.000 | 4.805 | 0.001 | 0.000 | -27.937 | 0.000 | -37.984 | -26.736 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.386 | -45.586 | 0.000 | 0.000 | 4.670 | 7.436 | 16.895 | 50.004 | 0.000 | 0.087 | 0.001 | 0.000 | -18.990 | 0.000 | -2.104 | -12.799 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 1.179 | -44.640 | 0.000 | 0.000 | 7.346 | 11.817 | 26.688 | 23.268 | 0.000 | 0.208 | 6.888 | 0.000 | -28.027 | 0.000 | -4.726 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.554 | -53.012 | 0.000 | 0.000 | 3.411 | 7.476 | 16.895 | 53.708 | 0.000 | 0.144 | 0.004 | 0.000 | -17.560 | 0.000 | -3.202 | -8.415 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.507 | -79.535 | 0.000 | 0.000 | 7.063 | 11.745 | 26.688 | 95.612 | 0.000 | 0.204 | 0.000 | 0.000 | -27.329 | 0.000 | -5.049 | -29.906 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.669 | -50.872 | 0.000 | 0.000 | 4.702 | 7.442 | 16.895 | 49.781 | 0.000 | 0.137 | 0.000 | 0.000 | -18.738 | 0.000 | -3.223 | -6.792 |
TOPFLOOR_PLENUM | 12.303 | -51.281 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.249 | 47.009 | 0.000 | 0.000 | 0.000 | -8.280 | -0.001 |
MIDFLOOR_PLENUM | 4.795 | -27.544 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.294 | 30.755 | 0.000 | 0.000 | 0.000 | -8.301 | -0.000 |
FIRSTFLOOR_PLENUM | 1.800 | -34.406 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.231 | 39.075 | 0.000 | 0.000 | 0.000 | -6.701 | 0.000 |
Total Facility | 18.898 | -113.231 | 28.591 | -1274.305 | 0.000 | 0.000 | 170.450 | 360.519 | 762.041 | 669.732 | 0.000 | 7.412 | 124.490 | 0.000 | -270.595 | 0.000 | -102.908 | -381.087 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-JUL-04:02 | 0.00 | 0.00 | 0.00 | -45747.45 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 39816.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:03 | 0.00 | 0.00 | 0.00 | -37361.46 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 33393.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -37449.56 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 33482.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-18:21 | 0.00 | 0.00 | 0.00 | -13179.99 | 0.00 | 0.00 | 0.00 | 51.50 | 501.96 | 4152.89 | 0.00 | 270.84 | 8202.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:01 | 0.00 | 0.00 | 0.00 | -15271.59 | 0.00 | 0.00 | 11.26 | 32.61 | 317.77 | 11067.71 | 0.00 | 0.00 | 3856.46 | 0.00 | -0.00 | 0.00 | -14.21 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-12:32 | 0.00 | 0.00 | 0.00 | -17293.90 | 0.00 | 0.00 | 18.99 | 51.50 | 501.96 | 16018.61 | 0.00 | 0.00 | 718.65 | 0.00 | -0.00 | 0.00 | -15.81 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -17758.22 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 12866.95 | 0.00 | 280.51 | 4260.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-18:11 | 0.00 | 0.00 | 0.00 | -10625.65 | 0.00 | 0.00 | 0.00 | 51.50 | 501.96 | 4286.10 | 0.00 | 151.20 | 5634.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:31 | 0.00 | 0.00 | 0.00 | -13361.82 | 0.00 | 0.00 | 13.68 | 32.61 | 317.77 | 9855.51 | 0.00 | 0.00 | 3149.35 | 0.00 | -0.00 | 0.00 | -7.09 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:21 | 0.00 | 0.00 | 0.00 | -14727.45 | 0.00 | 0.00 | 21.62 | 51.50 | 501.96 | 11585.62 | 0.00 | 0.00 | 2570.60 | 0.00 | -0.00 | 0.00 | -3.84 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-18:11 | 0.00 | 0.00 | 0.00 | -14712.58 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 9126.06 | 0.00 | 62.05 | 5174.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-17:32 | 0.00 | 0.00 | 0.00 | -11878.34 | 0.00 | 0.00 | 0.00 | 51.50 | 501.96 | 3968.84 | 0.00 | 351.31 | 7004.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -16251.55 | 0.00 | 0.00 | 11.57 | 32.61 | 317.77 | 11434.01 | 0.00 | 0.00 | 4485.85 | 0.00 | -0.00 | 0.00 | -30.24 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-11:41 | 0.00 | 0.00 | 0.00 | -16552.30 | 0.00 | 0.00 | 20.18 | 51.50 | 501.96 | 17100.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -38.09 | -1083.99 |
PERIMETER_MID_ZN_4 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -17510.46 | 0.00 | 0.00 | 9.68 | 32.60 | 317.76 | 13117.84 | 0.00 | 202.97 | 3829.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:40 | 0.00 | -13110.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.61 | 12993.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-15:30 | 0.00 | -6069.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 5981.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-12:10 | 0.00 | -6818.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | 6773.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-04:01 | 0.00 | 10891.13 | 0.00 | -215754.90 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 189563.82 | 0.00 | -5810.39 | 0.00 | -951.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-FEB-07:03 | 0.00 | 0.00 | 16862.34 | 0.00 | 0.00 | 0.00 | 916.94 | 2377.96 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23332.10 |
CORE_TOP | 26-DEC-06:01 | 0.00 | 0.00 | 31259.19 | 0.00 | 0.00 | 0.00 | 500.42 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35727.15 |
PERIMETER_TOP_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 11445.15 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2325.91 | 0.00 | -1148.44 | -8807.19 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 10505.25 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1519.57 | 0.00 | -776.40 | -8738.75 |
PERIMETER_TOP_ZN_1 | 17-JAN-05:11 | 0.00 | 0.00 | 13620.77 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2067.38 | 0.00 | -1240.19 | -11149.58 |
PERIMETER_TOP_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 10490.47 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1556.93 | 0.00 | -776.99 | -8686.03 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 8394.13 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2597.70 | 0.00 | -673.55 | -5959.26 |
PERIMETER_BOT_ZN_2 | 06-FEB-06:01 | 0.00 | 0.00 | 6506.06 | 0.00 | 0.00 | 0.00 | 66.79 | 105.79 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1735.89 | 0.00 | -95.74 | -5270.69 |
PERIMETER_BOT_ZN_1 | 22-DEC-07:10 | 0.00 | 0.00 | 12291.93 | 0.00 | 0.00 | 0.00 | 193.30 | 501.29 | 669.28 | 0.00 | 0.00 | 0.00 | 11430.16 | 0.00 | -2937.91 | 0.00 | -22148.06 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-06:01 | 0.00 | 0.00 | 6425.92 | 0.00 | 0.00 | 0.00 | 66.78 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.50 | 0.00 | -95.72 | -5150.96 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 9274.49 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2552.33 | 0.00 | -1025.14 | -6533.41 |
PERIMETER_MID_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 7531.67 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1664.72 | 0.00 | -688.99 | -5707.45 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 11113.62 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2564.62 | 0.00 | -1059.64 | -8325.75 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 7735.77 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1712.58 | 0.00 | -691.92 | -5860.74 |
TOPFLOOR_PLENUM | 17-JAN-06:13 | 12043.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -485.63 | -11558.19 |
MIDFLOOR_PLENUM | 22-JAN-14:43 | 6734.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -167.73 | -6566.39 |
FIRSTFLOOR_PLENUM | 24-NOV-06:02 | 6245.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.01 | -6131.29 |
Total Facility | 06-FEB-07:01 | 8709.95 | 6846.39 | 139670.05 | -6846.39 | 0.00 | 0.00 | 4557.10 | 10970.80 | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18333.00 | 0.00 | -30947.26 | -136480.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.9503 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.2669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 6.4517 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5905 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 7.0623 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 6.5408 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.4752 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0851 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 3.2259 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.9435 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.5312 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.1187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5633 | 3.5633 | 1.0690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6515 | 2.6515 | 0.8034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8715 | 2.8715 | 0.8615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9352 | 0.9352 | 0.2806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9954 | 0.9954 | 0.2986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1268 | 1.1268 | 0.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1334 | 1.1334 | 0.3400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7503 | 0.7503 | 0.2251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8328 | 0.8328 | 0.2498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9141 | 0.9141 | 0.2742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8898 | 0.8898 | 0.2669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8063 | 0.8063 | 0.2419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9648 | 0.9648 | 0.2895 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9973 | 0.9973 | 0.2992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0318 | 1.0318 | 0.3095 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.9503 | 6.2669 | 6.9503 | 2.0851 | 0.0000 | 1.0000 |
PACU_VAV_MID | 6.4517 | 5.5905 | 6.4517 | 1.9435 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 7.0623 | 6.5408 | 7.0623 | 2.1187 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7817 | 1.7817 | 1.0690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3257 | 1.3257 | 0.8034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4358 | 1.4358 | 0.8615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4676 | 0.4676 | 0.2806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4977 | 0.4977 | 0.2986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5634 | 0.5634 | 0.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5667 | 0.5667 | 0.3400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3751 | 0.3751 | 0.2251 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.2498 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4571 | 0.4571 | 0.2742 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4449 | 0.4449 | 0.2669 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4031 | 0.4031 | 0.2419 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4824 | 0.4824 | 0.2895 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4987 | 0.4987 | 0.2992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5159 | 0.5159 | 0.3095 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.4752 | 2.0851 | 2.0851 | 2.0851 | 0.0000 | 1.0000 |
PACU_VAV_MID | 3.2259 | 1.9435 | 1.9435 | 1.9435 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.5312 | 2.1187 | 2.1187 | 2.1187 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 168.00 |
Number of hours cooling loads not met | 262.33 |
Number of hours not met | 430.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 68.94 | 119707.51 | 32.52 | 47183.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 250.43 | 81946.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 360.52 | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.74 | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.92 | 1358.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 150.51 | 35650.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 105.54 | 9408.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1722.13 |
Natural Gas | 0.00 | 138.06 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 1860.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.36 |
Space Heating | 13.84 |
Space Cooling | 50.26 |
Fans (All) | 30.21 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 345.66 |
Subtotal | 345.66 |
Natural Gas [MJ/m2] | |
Space Heating | 6.53 |
Service Water Heating | 21.18 |
Miscellaneous (All) | 27.71 |
Subtotal | 27.71 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 19.38 |
Space Heating | 5.45 |
Space Cooling | 13.46 |
Fans (All) | 8.09 |
Service Water Heating | 5.67 |
Receptacle Equipment | 40.97 |
Miscellaneous | 6.97 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2616. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8712.17 | 47.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8731.17 | 28.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8646.67 | 113.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8646.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.33 | 0.00 | 0.00 | 0.00 |
Average | 8735.16 | 24.84 | 0.00 | 0.00 | 0.00 |
Sum | 157232.83 | 447.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.28 | 0.06 | 0.00 | 0.00 | 0.00 |
Sum | 614579.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8707.17 | 52.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8686.17 | 73.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8711.50 | 48.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8723.17 | 36.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8680.67 | 79.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8706.50 | 53.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8680.17 | 79.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
Min | 8680.17 | 4.17 | 0.00 | 0.00 | 0.00 |
Max | 8755.83 | 79.83 | 0.00 | 0.00 | 0.00 |
Average | 8717.96 | 42.04 | 0.00 | 0.00 | 0.00 |
Sum | 156923.33 | 756.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128288.67 | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128301.67 | 15.33 | 0.00 | 0.00 | 0.00 |
Average | 34141.93 | 1.41 | 0.00 | 0.00 | 0.00 |
Sum | 614554.67 | 25.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153365E+11 | 18477.80 | 06-JAN-08:04 | -1.5 | -3.6 | 0.196535E+10 | 2608.72 | 17-JAN-14:00 | 2.20 | -1.4 |
February | 0.149431E+11 | 26897.87 | 16-FEB-06:02 | 1.70 | -0.5 | 0.178914E+10 | 2606.65 | 15-FEB-10:09 | 1.70 | -0.5 |
March | 0.201752E+11 | 30629.54 | 17-MAR-05:02 | 7.02 | 1.62 | 0.214991E+10 | 2606.65 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.222783E+11 | 41792.91 | 25-APR-05:02 | 6.97 | 1.13 | 0.191564E+10 | 2606.68 | 17-APR-13:00 | 6.97 | 1.13 |
May | 0.261980E+11 | 44378.17 | 22-MAY-04:02 | 17.62 | 11.88 | 0.207443E+10 | 2606.77 | 11-MAY-09:09 | 17.62 | 11.88 |
June | 0.288628E+11 | 45263.19 | 28-JUN-04:02 | 20.73 | 12.15 | 0.206903E+10 | 2606.70 | 08-JUN-13:09 | 20.73 | 12.15 |
July | 0.294278E+11 | 45750.04 | 25-JUL-04:02 | 20.18 | 15.25 | 0.192330E+10 | 2606.63 | 21-JUL-09:09 | 20.18 | 15.25 |
August | 0.314692E+11 | 45705.46 | 15-AUG-04:02 | 20.50 | 16.45 | 0.215939E+10 | 2606.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.275484E+11 | 45005.35 | 01-SEP-04:02 | 19.32 | 13.67 | 0.191746E+10 | 2606.70 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.250360E+11 | 44651.93 | 03-OCT-04:02 | 14.27 | 11.53 | 0.199118E+10 | 2606.71 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.194630E+11 | 38568.22 | 01-NOV-05:02 | 7.70 | 5.59 | 0.196660E+10 | 2606.60 | 08-NOV-10:39 | 13.70 | 6.24 |
December | 0.155397E+11 | 18916.32 | 01-DEC-06:02 | 3.90 | -0.5 | 0.189952E+10 | 2606.62 | 20-DEC-10:09 | 1.10 | -3.7 |
Annual Sum or Average | 0.276278E+12 | 0.238210E+11 | ||||||||
Minimum of Months | 0.149431E+11 | 18477.80 | -1.5 | -3.6 | 0.178914E+10 | 2606.60 | 1.10 | -3.7 | ||
Maximum of Months | 0.314692E+11 | 45750.04 | 20.73 | 16.45 | 0.215939E+10 | 2608.72 | 23.30 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607156E+09 | 2636.15 | 03-JAN-14:00 | 15.00 | 5.83 | 0.00 | 0.00 | 01-JAN-00:10 | 15.00 | 5.83 |
February | 0.104197E+10 | 4812.21 | 14-FEB-15:40 | 22.03 | 7.70 | 0.00 | 0.00 | 01-FEB-00:10 | 22.03 | 7.70 |
March | 0.213109E+10 | 5976.20 | 08-MAR-14:50 | 22.30 | 9.20 | 0.00 | 0.00 | 01-MAR-00:10 | 22.30 | 9.20 |
April | 0.407381E+10 | 9334.93 | 28-APR-14:20 | 24.60 | 10.33 | 0.00 | 0.00 | 01-APR-00:10 | 24.60 | 10.33 |
May | 0.549442E+10 | 10719.81 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.833561E+10 | 13112.96 | 28-JUN-14:40 | 38.13 | 14.26 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 14.26 |
July | 0.945421E+10 | 12942.42 | 21-JUL-14:20 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.907928E+10 | 12827.53 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.612598E+10 | 10336.56 | 12-SEP-15:00 | 28.90 | 14.53 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 14.53 |
October | 0.341665E+10 | 8431.33 | 05-OCT-15:40 | 26.70 | 12.05 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 12.05 |
November | 0.113953E+10 | 4407.23 | 02-NOV-15:00 | 17.20 | 9.31 | 0.00 | 0.00 | 01-NOV-00:10 | 17.20 | 9.31 |
December | 0.382516E+09 | 2543.64 | 31-DEC-14:48 | 10.92 | 2.12 | 0.00 | 0.00 | 01-DEC-00:10 | 10.92 | 2.12 |
Annual Sum or Average | 0.512822E+11 | 0.00 | ||||||||
Minimum of Months | 0.382516E+09 | 2543.64 | 10.92 | 2.12 | 0.00 | 0.00 | 10.92 | 2.12 | ||
Maximum of Months | 0.945421E+10 | 13112.96 | 38.13 | 15.81 | 0.00 | 0.00 | 38.13 | 15.81 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215332E+09 | 1793.52 | 06-JAN-07:01 | -1.7 | -3.7 | 0.00 | 0.00 | 01-JAN-00:10 | -1.7 | -3.7 |
February | 0.323444E+09 | 2053.96 | 04-FEB-06:01 | -6.7 | -8.2 | 0.00 | 0.00 | 01-FEB-00:10 | -6.7 | -8.2 |
March | 0.751494E+09 | 2797.66 | 30-MAR-06:01 | -1.7 | -2.6 | 0.00 | 0.00 | 01-MAR-00:10 | -1.7 | -2.6 |
April | 0.178998E+10 | 3414.13 | 28-APR-15:20 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.280827E+10 | 4058.19 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.453009E+10 | 5729.48 | 26-JUN-15:30 | 35.55 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 35.55 | 15.63 |
July | 0.529739E+10 | 5898.11 | 05-JUL-14:50 | 33.22 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 33.22 | 17.14 |
August | 0.529308E+10 | 6069.26 | 07-AUG-15:30 | 33.05 | 15.91 | 0.00 | 0.00 | 01-AUG-00:10 | 33.05 | 15.91 |
September | 0.365286E+10 | 4923.74 | 05-SEP-15:00 | 24.40 | 17.62 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 17.62 |
October | 0.206016E+10 | 4753.83 | 02-OCT-16:00 | 23.90 | 14.76 | 0.00 | 0.00 | 01-OCT-00:10 | 23.90 | 14.76 |
November | 0.644192E+09 | 1816.95 | 01-NOV-15:40 | 11.33 | 6.68 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 6.68 |
December | 0.178080E+09 | 1669.02 | 23-DEC-06:01 | -5.5 | -7.9 | 0.00 | 0.00 | 01-DEC-00:10 | -5.5 | -7.9 |
Annual Sum or Average | 0.275444E+11 | 0.00 | ||||||||
Minimum of Months | 0.178080E+09 | 1669.02 | -6.7 | -8.2 | 0.00 | 0.00 | -6.7 | -8.2 | ||
Maximum of Months | 0.529739E+10 | 6069.26 | 35.55 | 17.62 | 0.00 | 0.00 | 35.55 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506719E+09 | 2572.25 | 06-JAN-07:01 | -1.7 | -3.7 | 0.00 | 0.00 | 01-JAN-00:10 | -1.7 | -3.7 |
February | 0.700491E+09 | 2574.19 | 10-FEB-07:01 | -1.7 | -3.7 | 0.00 | 0.00 | 01-FEB-00:10 | -1.7 | -3.7 |
March | 0.144549E+10 | 3345.12 | 24-MAR-06:01 | -0.7 | -2.9 | 0.00 | 0.00 | 01-MAR-00:10 | -0.7 | -2.9 |
April | 0.253398E+10 | 3791.08 | 28-APR-15:10 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.346892E+10 | 4319.10 | 15-MAY-16:00 | 28.90 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 28.90 | 11.34 |
June | 0.499694E+10 | 6814.48 | 29-JUN-12:06 | 35.37 | 17.08 | 0.00 | 0.00 | 01-JUN-00:10 | 35.37 | 17.08 |
July | 0.568652E+10 | 6819.09 | 05-JUL-12:10 | 30.78 | 17.16 | 0.00 | 0.00 | 01-JUL-00:10 | 30.78 | 17.16 |
August | 0.582973E+10 | 6023.77 | 07-AUG-17:05 | 32.33 | 16.04 | 0.00 | 0.00 | 01-AUG-00:10 | 32.33 | 16.04 |
September | 0.445849E+10 | 5372.22 | 05-SEP-15:30 | 24.15 | 17.41 | 0.00 | 0.00 | 01-SEP-00:10 | 24.15 | 17.41 |
October | 0.299559E+10 | 5044.12 | 02-OCT-16:10 | 23.35 | 15.07 | 0.00 | 0.00 | 01-OCT-00:10 | 23.35 | 15.07 |
November | 0.128745E+10 | 2939.20 | 01-NOV-16:09 | 10.40 | 6.16 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 6.16 |
December | 0.495794E+09 | 2314.82 | 29-DEC-07:01 | -0.6 | -2.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.6 | -2.3 |
Annual Sum or Average | 0.344061E+11 | 0.00 | ||||||||
Minimum of Months | 0.495794E+09 | 2314.82 | -1.7 | -3.7 | 0.00 | 0.00 | -1.7 | -3.7 | ||
Maximum of Months | 0.582973E+10 | 6819.09 | 35.37 | 17.41 | 0.00 | 0.00 | 35.37 | 17.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.851921E+10 | 9388.16 | 27-JAN-17:00 | 10.00 | 1.22 | 0.182098E+10 | 2606.50 | 04-JAN-14:39 | 10.00 | 1.22 |
February | 0.825494E+10 | 13144.52 | 15-FEB-17:00 | 16.70 | 5.85 | 0.170086E+10 | 2606.61 | 15-FEB-10:09 | 16.70 | 5.85 |
March | 0.116265E+11 | 12999.33 | 09-MAR-17:00 | 16.70 | 5.52 | 0.211470E+10 | 2606.62 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.142406E+11 | 31509.87 | 27-APR-05:02 | 9.40 | 3.12 | 0.190408E+10 | 2606.64 | 17-APR-13:00 | 9.40 | 3.12 |
May | 0.174908E+11 | 33230.82 | 22-MAY-04:02 | 17.62 | 11.88 | 0.206932E+10 | 2606.73 | 11-MAY-09:09 | 17.62 | 11.88 |
June | 0.205193E+11 | 34488.52 | 26-JUN-04:02 | 18.25 | 11.40 | 0.206746E+10 | 2606.68 | 08-JUN-13:09 | 18.25 | 11.40 |
July | 0.214824E+11 | 37360.34 | 24-JUL-04:03 | 22.70 | 14.94 | 0.192255E+10 | 2606.63 | 21-JUL-09:09 | 22.70 | 14.94 |
August | 0.225589E+11 | 34393.35 | 14-AUG-04:02 | 18.90 | 16.62 | 0.215831E+10 | 2606.84 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.186333E+11 | 35461.01 | 05-SEP-04:02 | 17.52 | 15.20 | 0.191542E+10 | 2606.67 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.153003E+11 | 33981.35 | 02-OCT-04:02 | 17.70 | 12.88 | 0.197684E+10 | 2606.65 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.105793E+11 | 15721.18 | 01-NOV-05:02 | 7.70 | 5.59 | 0.192064E+10 | 2606.60 | 08-NOV-10:09 | 13.40 | 6.02 |
December | 0.840522E+10 | 10140.97 | 01-DEC-16:40 | 12.40 | 4.45 | 0.176844E+10 | 2606.61 | 01-DEC-10:20 | 12.40 | 4.45 |
Annual Sum or Average | 0.177611E+12 | 0.233396E+11 | ||||||||
Minimum of Months | 0.825494E+10 | 9388.16 | 7.70 | 1.22 | 0.170086E+10 | 2606.50 | 9.40 | 1.22 | ||
Maximum of Months | 0.225589E+11 | 37360.34 | 22.70 | 16.62 | 0.215831E+10 | 2606.84 | 23.30 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.718198E+10 | 8056.53 | 26-JAN-14:10 | 10.10 | 1.50 | 0.167979E+10 | 2573.82 | 27-JAN-14:00 | 11.70 | 2.33 |
February | 0.738259E+10 | 12837.74 | 15-FEB-17:00 | 16.70 | 5.85 | 0.158588E+10 | 2606.45 | 15-FEB-14:00 | 16.70 | 5.85 |
March | 0.106595E+11 | 13273.97 | 08-MAR-17:00 | 22.20 | 8.27 | 0.202365E+10 | 2606.60 | 02-MAR-14:30 | 22.20 | 8.27 |
April | 0.135719E+11 | 18281.11 | 28-APR-15:00 | 25.00 | 10.42 | 0.187720E+10 | 2606.65 | 17-APR-13:00 | 25.00 | 10.42 |
May | 0.172901E+11 | 34756.21 | 22-MAY-05:02 | 16.78 | 12.20 | 0.205704E+10 | 2606.70 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.212758E+11 | 37002.33 | 26-JUN-04:02 | 18.25 | 11.40 | 0.206369E+10 | 2606.68 | 08-JUN-13:09 | 18.25 | 11.40 |
July | 0.227116E+11 | 37294.00 | 05-JUL-04:02 | 22.20 | 13.93 | 0.192191E+10 | 2606.63 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.232195E+11 | 37445.85 | 07-AUG-04:02 | 19.32 | 14.31 | 0.215688E+10 | 2606.86 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.180505E+11 | 37010.63 | 05-SEP-04:02 | 17.52 | 15.20 | 0.190833E+10 | 2606.64 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.136849E+11 | 35117.30 | 02-OCT-05:02 | 17.12 | 12.75 | 0.193013E+10 | 2606.63 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.904221E+10 | 14086.79 | 01-NOV-16:00 | 10.60 | 6.24 | 0.181427E+10 | 2606.60 | 01-NOV-09:09 | 10.60 | 6.24 |
December | 0.702246E+10 | 7966.36 | 29-DEC-13:50 | 10.32 | 3.31 | 0.161965E+10 | 2582.33 | 01-DEC-14:00 | 10.32 | 3.31 |
Annual Sum or Average | 0.171093E+12 | 0.226384E+11 | ||||||||
Minimum of Months | 0.702246E+10 | 7966.36 | 10.10 | 1.50 | 0.158588E+10 | 2573.82 | 10.32 | 2.33 | ||
Maximum of Months | 0.232195E+11 | 37445.85 | 25.00 | 15.20 | 0.215688E+10 | 2606.86 | 30.18 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.782581E+09 | 2091.87 | 05-JAN-14:30 | 16.10 | 6.84 | 0.312519E+09 | 459.73 | 05-JAN-16:30 | 14.70 | 6.21 |
February | 0.110085E+10 | 2754.66 | 14-FEB-14:40 | 21.33 | 7.23 | 0.291119E+09 | 514.82 | 15-FEB-16:40 | 16.87 | 6.07 |
March | 0.227114E+10 | 2745.71 | 16-MAR-15:00 | 20.00 | 8.47 | 0.379886E+09 | 549.48 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.338849E+10 | 5438.62 | 14-APR-14:30 | 23.60 | 10.45 | 0.372730E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.472068E+10 | 6202.56 | 31-MAY-15:20 | 27.57 | 11.01 | 0.422505E+09 | 549.50 | 31-MAY-13:20 | 27.57 | 11.01 |
June | 0.689494E+10 | 13049.00 | 25-JUN-17:21 | 33.05 | 15.18 | 0.433089E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.750272E+10 | 13179.40 | 04-JUL-18:21 | 33.05 | 13.57 | 0.404843E+09 | 549.50 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.707262E+10 | 11801.34 | 20-AUG-16:51 | 34.40 | 15.63 | 0.452786E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.485656E+10 | 6383.28 | 12-SEP-14:30 | 29.15 | 14.70 | 0.394497E+09 | 549.50 | 13-SEP-13:39 | 26.67 | 14.56 |
October | 0.314024E+10 | 5791.42 | 02-OCT-13:40 | 26.33 | 15.37 | 0.372614E+09 | 549.49 | 05-OCT-13:50 | 26.52 | 12.57 |
November | 0.165051E+10 | 2867.12 | 01-NOV-14:10 | 12.30 | 7.31 | 0.329316E+09 | 522.01 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.604514E+09 | 2042.04 | 29-DEC-13:40 | 10.03 | 3.18 | 0.297836E+09 | 468.79 | 01-DEC-14:00 | 10.03 | 3.18 |
Annual Sum or Average | 0.439859E+11 | 0.446374E+10 | ||||||||
Minimum of Months | 0.604514E+09 | 2042.04 | 10.03 | 3.18 | 0.291119E+09 | 459.73 | 10.03 | 2.42 | ||
Maximum of Months | 0.750272E+10 | 13179.40 | 34.40 | 15.63 | 0.452786E+09 | 549.55 | 30.18 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122752E+10 | 2297.18 | 26-JAN-13:40 | 9.63 | 1.28 | 0.203645E+09 | 324.19 | 27-JAN-10:20 | 3.90 | -1.9 |
February | 0.158065E+10 | 3764.27 | 14-FEB-09:50 | 9.45 | 2.98 | 0.193736E+09 | 347.87 | 13-FEB-10:09 | 9.45 | 2.98 |
March | 0.294348E+10 | 4981.70 | 24-MAR-09:30 | 8.60 | 2.50 | 0.256567E+09 | 347.87 | 10-MAR-10:09 | 8.60 | 2.50 |
April | 0.467904E+10 | 11760.90 | 30-APR-08:32 | 15.40 | 4.96 | 0.249627E+09 | 348.40 | 28-APR-09:00 | 15.40 | 4.96 |
May | 0.570980E+10 | 12807.93 | 29-MAY-08:52 | 18.30 | 12.78 | 0.271760E+09 | 348.37 | 19-MAY-09:00 | 18.30 | 12.78 |
June | 0.742428E+10 | 14702.81 | 18-JUN-08:42 | 25.13 | 11.87 | 0.274355E+09 | 348.57 | 22-JUN-09:00 | 30.60 | 15.11 |
July | 0.772312E+10 | 15273.93 | 04-JUL-09:01 | 26.97 | 18.48 | 0.256403E+09 | 348.59 | 06-JUL-09:39 | 28.67 | 16.27 |
August | 0.759764E+10 | 14957.52 | 20-AUG-08:52 | 26.10 | 15.49 | 0.286986E+09 | 348.48 | 07-AUG-09:00 | 26.10 | 15.49 |
September | 0.561358E+10 | 14555.64 | 03-SEP-09:12 | 26.33 | 15.30 | 0.251760E+09 | 348.32 | 13-SEP-09:30 | 23.05 | 13.86 |
October | 0.383723E+10 | 10118.70 | 01-OCT-09:12 | 18.90 | 11.69 | 0.246724E+09 | 347.88 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.207960E+10 | 4941.43 | 01-NOV-09:10 | 10.47 | 6.68 | 0.219796E+09 | 347.87 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.118780E+10 | 2291.96 | 29-DEC-13:30 | 9.75 | 3.05 | 0.192728E+09 | 319.73 | 29-DEC-10:09 | 9.75 | 3.05 |
Annual Sum or Average | 0.516037E+11 | 0.290409E+10 | ||||||||
Minimum of Months | 0.118780E+10 | 2291.96 | 8.60 | 1.28 | 0.192728E+09 | 319.73 | 3.90 | -1.9 | ||
Maximum of Months | 0.772312E+10 | 15273.93 | 26.97 | 18.48 | 0.286986E+09 | 348.59 | 30.60 | 16.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417985E+10 | 14005.19 | 01-JAN-13:53 | 15.60 | 5.65 | 0.371623E+09 | 550.50 | 09-JAN-14:09 | 14.08 | 4.55 |
February | 0.440395E+10 | 12729.16 | 14-FEB-13:50 | 20.40 | 6.90 | 0.344197E+09 | 554.53 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.519421E+10 | 14308.85 | 12-MAR-13:23 | 17.25 | 5.71 | 0.412479E+09 | 549.89 | 08-MAR-14:00 | 17.25 | 5.71 |
April | 0.581615E+10 | 10259.75 | 28-APR-13:10 | 24.40 | 9.92 | 0.380923E+09 | 550.38 | 27-APR-13:00 | 24.40 | 9.92 |
May | 0.593551E+10 | 8598.46 | 30-MAY-13:10 | 27.20 | 12.26 | 0.419659E+09 | 549.51 | 08-MAY-13:00 | 27.20 | 12.26 |
June | 0.726199E+10 | 11712.00 | 25-JUN-16:41 | 33.68 | 14.48 | 0.429356E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.837093E+10 | 15791.49 | 30-JUL-14:52 | 33.30 | 17.94 | 0.403627E+09 | 549.49 | 21-JUL-09:09 | 33.30 | 17.94 |
August | 0.951153E+10 | 16002.10 | 20-AUG-13:32 | 33.87 | 16.98 | 0.451979E+09 | 550.21 | 25-AUG-13:00 | 28.90 | 17.11 |
September | 0.888645E+10 | 17075.96 | 03-SEP-13:12 | 31.67 | 16.75 | 0.397589E+09 | 593.44 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.812505E+10 | 17295.55 | 01-OCT-12:32 | 26.67 | 14.27 | 0.400452E+09 | 590.09 | 05-OCT-13:39 | 26.33 | 12.76 |
November | 0.566140E+10 | 15857.34 | 19-NOV-12:43 | 10.82 | 2.48 | 0.388683E+09 | 567.15 | 01-NOV-13:09 | 10.82 | 2.48 |
December | 0.455158E+10 | 13039.93 | 31-DEC-14:02 | 10.18 | 1.71 | 0.365717E+09 | 549.49 | 20-DEC-14:00 | 10.18 | 1.71 |
Annual Sum or Average | 0.778986E+11 | 0.476628E+10 | ||||||||
Minimum of Months | 0.417985E+10 | 8598.46 | 10.18 | 1.71 | 0.344197E+09 | 549.49 | 10.18 | 1.71 | ||
Maximum of Months | 0.951153E+10 | 17295.55 | 33.87 | 17.94 | 0.451979E+09 | 593.44 | 33.30 | 17.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124935E+10 | 4478.13 | 26-JAN-16:30 | 10.30 | 1.40 | 0.206314E+09 | 338.68 | 09-JAN-16:00 | 10.30 | 1.40 |
February | 0.171776E+10 | 7154.57 | 15-FEB-16:30 | 16.95 | 6.18 | 0.192100E+09 | 347.81 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.299791E+10 | 7588.59 | 24-MAR-16:00 | 18.30 | 5.82 | 0.235304E+09 | 347.84 | 07-MAR-14:00 | 18.30 | 5.82 |
April | 0.441179E+10 | 14968.75 | 16-APR-17:12 | 20.20 | 7.96 | 0.225868E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.544495E+10 | 16331.99 | 14-MAY-16:32 | 28.30 | 10.81 | 0.253619E+09 | 347.86 | 08-MAY-13:00 | 28.30 | 10.81 |
June | 0.684667E+10 | 17676.15 | 25-JUN-16:41 | 33.68 | 14.48 | 0.265347E+09 | 347.86 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.714596E+10 | 17757.72 | 04-JUL-17:01 | 35.73 | 14.63 | 0.251643E+09 | 347.85 | 06-JUL-09:00 | 29.40 | 16.55 |
August | 0.712517E+10 | 17203.70 | 20-AUG-16:11 | 34.80 | 15.86 | 0.279960E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.554751E+10 | 17159.03 | 24-SEP-15:51 | 25.60 | 15.70 | 0.239601E+09 | 347.86 | 13-SEP-13:39 | 25.60 | 15.70 |
October | 0.410596E+10 | 12104.27 | 08-OCT-16:32 | 19.07 | 7.26 | 0.228641E+09 | 347.86 | 05-OCT-13:50 | 19.07 | 7.26 |
November | 0.218854E+10 | 6127.32 | 02-NOV-16:00 | 16.70 | 9.78 | 0.212997E+09 | 347.81 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.113873E+10 | 3543.95 | 29-DEC-16:10 | 11.42 | 3.74 | 0.199050E+09 | 338.68 | 29-DEC-16:00 | 10.00 | 2.99 |
Annual Sum or Average | 0.499203E+11 | 0.279044E+10 | ||||||||
Minimum of Months | 0.113873E+10 | 3543.95 | 10.30 | 1.40 | 0.192100E+09 | 338.68 | 10.00 | 1.40 | ||
Maximum of Months | 0.714596E+10 | 17757.72 | 35.73 | 15.86 | 0.279960E+09 | 347.89 | 29.47 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.898565E+09 | 1711.73 | 02-JAN-13:05 | 12.98 | 5.03 | 0.317221E+09 | 466.23 | 05-JAN-14:00 | 16.10 | 6.84 |
February | 0.102836E+10 | 2165.10 | 15-FEB-13:07 | 15.68 | 6.34 | 0.293191E+09 | 497.77 | 15-FEB-14:09 | 16.28 | 6.32 |
March | 0.192579E+10 | 1808.10 | 27-MAR-15:20 | 18.50 | 7.17 | 0.378155E+09 | 528.42 | 17-MAR-13:00 | 18.50 | 7.17 |
April | 0.254077E+10 | 3686.62 | 14-APR-14:30 | 23.60 | 10.45 | 0.374844E+09 | 549.49 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.355434E+10 | 4493.92 | 31-MAY-16:00 | 28.30 | 11.06 | 0.426337E+09 | 549.49 | 23-MAY-13:00 | 28.30 | 11.06 |
June | 0.563418E+10 | 6630.32 | 29-JUN-15:00 | 37.80 | 15.70 | 0.434395E+09 | 549.51 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.643554E+10 | 10626.06 | 04-JUL-18:11 | 33.33 | 13.61 | 0.405049E+09 | 549.49 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.635461E+10 | 9210.07 | 20-AUG-16:01 | 34.90 | 15.92 | 0.454275E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.464463E+10 | 5475.02 | 05-SEP-13:40 | 24.23 | 18.04 | 0.401689E+09 | 549.50 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.324411E+10 | 5080.49 | 02-OCT-13:40 | 26.33 | 15.37 | 0.395456E+09 | 549.49 | 06-OCT-09:00 | 21.10 | 12.27 |
November | 0.199267E+10 | 2460.36 | 01-NOV-12:10 | 13.30 | 7.71 | 0.353933E+09 | 548.83 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.938512E+09 | 1706.33 | 31-DEC-14:22 | 10.55 | 1.91 | 0.305203E+09 | 496.16 | 01-DEC-14:00 | 10.55 | 1.91 |
Annual Sum or Average | 0.391921E+11 | 0.453975E+10 | ||||||||
Minimum of Months | 0.898565E+09 | 1706.33 | 10.55 | 1.91 | 0.293191E+09 | 466.23 | 10.55 | 1.91 | ||
Maximum of Months | 0.643554E+10 | 10626.06 | 37.80 | 18.04 | 0.454275E+09 | 549.55 | 30.18 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140843E+10 | 2223.34 | 01-JAN-12:43 | 12.85 | 4.69 | 0.211070E+09 | 326.81 | 27-JAN-10:20 | 3.90 | -1.9 |
February | 0.155529E+10 | 2679.71 | 14-FEB-08:35 | 5.57 | 0.88 | 0.197042E+09 | 347.86 | 14-FEB-10:09 | 10.83 | 3.59 |
March | 0.260847E+10 | 3500.88 | 31-MAR-08:20 | 8.33 | 3.28 | 0.259200E+09 | 347.87 | 10-MAR-10:09 | 8.33 | 3.28 |
April | 0.395066E+10 | 9397.53 | 30-APR-10:22 | 17.50 | 5.68 | 0.251921E+09 | 347.88 | 17-APR-13:00 | 17.50 | 5.68 |
May | 0.488617E+10 | 12353.32 | 29-MAY-09:21 | 19.45 | 13.10 | 0.274305E+09 | 347.91 | 15-MAY-09:09 | 19.45 | 13.10 |
June | 0.657090E+10 | 12164.52 | 18-JUN-09:11 | 25.97 | 11.91 | 0.275563E+09 | 348.23 | 22-JUN-09:00 | 30.60 | 15.11 |
July | 0.707393E+10 | 13361.45 | 04-JUL-09:31 | 27.77 | 17.84 | 0.257085E+09 | 348.26 | 12-JUL-09:00 | 28.30 | 16.24 |
August | 0.721324E+10 | 13256.13 | 20-AUG-09:21 | 27.20 | 16.00 | 0.288095E+09 | 348.23 | 18-AUG-09:39 | 27.20 | 16.00 |
September | 0.557322E+10 | 12814.99 | 03-SEP-09:01 | 25.97 | 15.10 | 0.254676E+09 | 348.27 | 13-SEP-09:00 | 23.90 | 14.23 |
October | 0.413793E+10 | 11786.48 | 01-OCT-09:42 | 20.55 | 12.28 | 0.257208E+09 | 347.88 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.249620E+10 | 4419.52 | 01-NOV-09:10 | 10.47 | 6.68 | 0.238524E+09 | 347.87 | 06-NOV-10:09 | 7.57 | 2.16 |
December | 0.150778E+10 | 2215.22 | 31-DEC-14:22 | 10.55 | 1.91 | 0.203867E+09 | 327.00 | 29-DEC-10:09 | 10.55 | 1.91 |
Annual Sum or Average | 0.489822E+11 | 0.296856E+10 | ||||||||
Minimum of Months | 0.140843E+10 | 2215.22 | 5.57 | 0.88 | 0.197042E+09 | 326.81 | 3.90 | -1.9 | ||
Maximum of Months | 0.721324E+10 | 13361.45 | 27.77 | 17.84 | 0.288095E+09 | 348.27 | 30.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260494E+10 | 13037.28 | 01-JAN-14:43 | 16.02 | 5.80 | 0.351236E+09 | 550.37 | 23-JAN-14:30 | 15.00 | 4.55 |
February | 0.252384E+10 | 10737.52 | 19-FEB-14:23 | 16.65 | 7.00 | 0.324025E+09 | 549.56 | 15-FEB-14:50 | 16.65 | 7.00 |
March | 0.302782E+10 | 7573.86 | 13-MAR-14:30 | 21.15 | 7.30 | 0.391775E+09 | 549.50 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.370793E+10 | 7489.21 | 28-APR-13:40 | 24.40 | 10.14 | 0.370051E+09 | 549.51 | 17-APR-13:00 | 24.40 | 10.14 |
May | 0.426318E+10 | 10270.54 | 19-MAY-16:10 | 30.00 | 12.47 | 0.407646E+09 | 549.51 | 19-MAY-13:00 | 30.00 | 12.47 |
June | 0.679425E+10 | 12713.57 | 28-JUN-16:20 | 38.53 | 14.14 | 0.428221E+09 | 638.25 | 29-JUN-12:09 | 35.37 | 17.08 |
July | 0.843796E+10 | 12772.26 | 30-JUL-15:21 | 33.60 | 17.71 | 0.406126E+09 | 629.35 | 20-JUL-12:09 | 33.60 | 17.71 |
August | 0.950333E+10 | 13238.83 | 20-AUG-16:01 | 34.90 | 15.92 | 0.454453E+09 | 608.60 | 18-AUG-12:09 | 34.90 | 15.92 |
September | 0.878561E+10 | 14474.59 | 03-SEP-13:41 | 32.52 | 16.77 | 0.402678E+09 | 605.35 | 28-SEP-13:50 | 29.82 | 14.91 |
October | 0.742605E+10 | 14727.24 | 01-OCT-14:21 | 28.30 | 13.27 | 0.403813E+09 | 601.81 | 05-OCT-13:00 | 26.70 | 12.37 |
November | 0.429817E+10 | 13471.21 | 19-NOV-14:22 | 14.15 | 3.69 | 0.385683E+09 | 553.96 | 01-NOV-13:20 | 14.15 | 3.69 |
December | 0.273383E+10 | 12884.01 | 31-DEC-14:22 | 10.55 | 1.91 | 0.347834E+09 | 549.51 | 14-DEC-14:09 | 10.55 | 1.91 |
Annual Sum or Average | 0.641069E+11 | 0.467354E+10 | ||||||||
Minimum of Months | 0.252384E+10 | 7489.21 | 10.55 | 1.91 | 0.324025E+09 | 549.50 | 10.55 | 1.91 | ||
Maximum of Months | 0.950333E+10 | 14727.24 | 38.53 | 17.71 | 0.454453E+09 | 638.25 | 35.37 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141540E+10 | 3721.24 | 26-JAN-16:30 | 10.30 | 1.40 | 0.208496E+09 | 338.68 | 09-JAN-16:00 | 10.30 | 1.40 |
February | 0.164324E+10 | 5563.11 | 15-FEB-16:40 | 16.87 | 6.07 | 0.193485E+09 | 347.82 | 15-FEB-14:00 | 16.87 | 6.07 |
March | 0.255557E+10 | 5251.24 | 07-MAR-17:00 | 20.60 | 8.53 | 0.238994E+09 | 347.83 | 08-MAR-14:00 | 22.20 | 9.10 |
April | 0.352616E+10 | 12561.34 | 16-APR-17:21 | 20.00 | 7.87 | 0.234581E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.437596E+10 | 12889.84 | 29-MAY-16:41 | 26.28 | 13.29 | 0.262370E+09 | 347.85 | 09-MAY-13:30 | 26.28 | 13.29 |
June | 0.579479E+10 | 13579.01 | 18-JUN-17:51 | 30.00 | 10.70 | 0.271547E+09 | 347.86 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.624453E+10 | 14713.46 | 04-JUL-18:11 | 33.33 | 13.61 | 0.255625E+09 | 347.85 | 21-JUL-09:09 | 30.18 | 16.59 |
August | 0.650363E+10 | 14431.76 | 20-AUG-17:21 | 34.40 | 15.47 | 0.286836E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.522632E+10 | 13517.99 | 04-SEP-17:31 | 25.97 | 15.84 | 0.252950E+09 | 347.85 | 28-SEP-09:50 | 25.22 | 13.97 |
October | 0.418106E+10 | 12854.80 | 15-OCT-16:22 | 20.60 | 7.82 | 0.247259E+09 | 347.85 | 04-OCT-13:00 | 20.60 | 7.82 |
November | 0.262306E+10 | 5761.30 | 02-NOV-16:00 | 16.70 | 9.78 | 0.227085E+09 | 347.84 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.149782E+10 | 3038.57 | 29-DEC-16:10 | 11.42 | 3.74 | 0.202925E+09 | 338.68 | 13-DEC-16:40 | 11.42 | 3.74 |
Annual Sum or Average | 0.455875E+11 | 0.288215E+10 | ||||||||
Minimum of Months | 0.141540E+10 | 3038.57 | 10.30 | 1.40 | 0.193485E+09 | 338.68 | 10.30 | 1.40 | ||
Maximum of Months | 0.650363E+10 | 14713.46 | 34.40 | 15.84 | 0.286836E+09 | 347.89 | 30.18 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122129E+10 | 2192.07 | 05-JAN-14:10 | 16.10 | 6.84 | 0.321362E+09 | 481.21 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.144202E+10 | 2578.60 | 15-FEB-15:10 | 17.20 | 6.64 | 0.302848E+09 | 528.88 | 15-FEB-16:00 | 16.70 | 5.85 |
March | 0.249456E+10 | 2964.70 | 27-MAR-14:50 | 18.22 | 7.02 | 0.400830E+09 | 549.49 | 28-MAR-13:20 | 16.13 | 7.51 |
April | 0.336190E+10 | 5179.61 | 14-APR-14:30 | 23.60 | 10.45 | 0.387210E+09 | 549.50 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.457081E+10 | 5703.99 | 31-MAY-15:30 | 27.75 | 11.03 | 0.430968E+09 | 549.50 | 11-MAY-09:20 | 27.75 | 11.03 |
June | 0.653298E+10 | 11466.15 | 25-JUN-17:51 | 32.80 | 15.93 | 0.435177E+09 | 549.72 | 29-JUN-13:30 | 36.95 | 16.75 |
July | 0.701921E+10 | 11877.80 | 04-JUL-17:32 | 34.63 | 14.06 | 0.405433E+09 | 549.88 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.674080E+10 | 11022.47 | 20-AUG-18:01 | 33.67 | 15.16 | 0.454303E+09 | 549.55 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.476268E+10 | 6576.34 | 03-SEP-14:22 | 31.70 | 16.46 | 0.400664E+09 | 549.50 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.330646E+10 | 5498.24 | 02-OCT-13:40 | 26.33 | 15.37 | 0.390475E+09 | 549.49 | 24-OCT-13:30 | 12.20 | 5.98 |
November | 0.212151E+10 | 2614.81 | 01-NOV-15:00 | 12.80 | 7.53 | 0.349807E+09 | 549.48 | 03-NOV-13:00 | 12.20 | 2.42 |
December | 0.106682E+10 | 2147.57 | 29-DEC-14:20 | 10.77 | 3.61 | 0.305236E+09 | 502.53 | 01-DEC-14:00 | 10.77 | 3.61 |
Annual Sum or Average | 0.446410E+11 | 0.458431E+10 | ||||||||
Minimum of Months | 0.106682E+10 | 2147.57 | 10.77 | 3.61 | 0.302848E+09 | 481.21 | 10.77 | 2.42 | ||
Maximum of Months | 0.701921E+10 | 11877.80 | 34.63 | 16.46 | 0.454303E+09 | 549.88 | 36.95 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160952E+10 | 2697.64 | 27-JAN-12:00 | 7.20 | 0.10 | 0.154041E+09 | 338.71 | 27-JAN-09:50 | 7.20 | 0.10 |
February | 0.192289E+10 | 4679.77 | 14-FEB-09:30 | 8.35 | 2.46 | 0.146001E+09 | 338.71 | 13-FEB-11:09 | 8.35 | 2.46 |
March | 0.336115E+10 | 5723.43 | 31-MAR-08:30 | 8.60 | 3.38 | 0.190705E+09 | 338.74 | 07-MAR-08:30 | 8.60 | 3.38 |
April | 0.481178E+10 | 12597.09 | 30-APR-08:12 | 15.20 | 5.08 | 0.184871E+09 | 339.06 | 27-APR-08:00 | 15.20 | 5.08 |
May | 0.565213E+10 | 15176.24 | 29-MAY-08:41 | 17.93 | 12.73 | 0.201248E+09 | 338.93 | 23-MAY-08:00 | 17.93 | 12.73 |
June | 0.710659E+10 | 15626.72 | 25-JUN-08:31 | 25.77 | 15.91 | 0.202696E+09 | 340.21 | 26-JUN-10:30 | 30.25 | 15.69 |
July | 0.733850E+10 | 16247.48 | 04-JUL-08:51 | 26.70 | 18.67 | 0.189950E+09 | 341.92 | 05-JUL-07:19 | 24.80 | 15.16 |
August | 0.729075E+10 | 16177.46 | 20-AUG-08:41 | 25.82 | 15.35 | 0.211886E+09 | 340.39 | 07-AUG-10:30 | 25.82 | 15.35 |
September | 0.555709E+10 | 15517.38 | 03-SEP-09:01 | 25.97 | 15.10 | 0.186583E+09 | 339.06 | 11-SEP-08:39 | 20.53 | 13.10 |
October | 0.415746E+10 | 14270.10 | 01-OCT-08:22 | 16.70 | 10.70 | 0.183822E+09 | 338.73 | 06-OCT-10:09 | 21.57 | 12.33 |
November | 0.261691E+10 | 5656.01 | 01-NOV-09:00 | 10.00 | 6.46 | 0.166828E+09 | 339.04 | 17-NOV-09:09 | 2.67 | -1.7 |
December | 0.158775E+10 | 2558.34 | 29-DEC-13:10 | 9.18 | 2.77 | 0.147124E+09 | 338.71 | 29-DEC-09:39 | 9.18 | 2.77 |
Annual Sum or Average | 0.530125E+11 | 0.216575E+10 | ||||||||
Minimum of Months | 0.158775E+10 | 2558.34 | 7.20 | 0.10 | 0.146001E+09 | 338.71 | 2.67 | -1.7 | ||
Maximum of Months | 0.733850E+10 | 16247.48 | 26.70 | 18.67 | 0.211886E+09 | 341.92 | 30.25 | 15.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484322E+10 | 14189.97 | 01-JAN-12:53 | 13.30 | 4.92 | 0.382051E+09 | 561.54 | 26-JAN-14:09 | 10.10 | 1.50 |
February | 0.493881E+10 | 14910.33 | 12-FEB-13:32 | 16.67 | 5.61 | 0.354486E+09 | 577.55 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.558510E+10 | 14408.37 | 12-MAR-13:52 | 17.80 | 6.05 | 0.426986E+09 | 549.91 | 10-MAR-14:00 | 17.80 | 6.05 |
April | 0.584374E+10 | 12196.92 | 30-APR-12:53 | 20.60 | 7.16 | 0.390869E+09 | 550.33 | 27-APR-13:00 | 20.60 | 7.16 |
May | 0.573964E+10 | 9494.46 | 21-MAY-13:52 | 27.80 | 12.36 | 0.428491E+09 | 549.51 | 09-MAY-13:20 | 27.80 | 12.36 |
June | 0.684574E+10 | 13384.69 | 25-JUN-16:31 | 34.07 | 14.58 | 0.432975E+09 | 549.51 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.782068E+10 | 14238.75 | 30-JUL-14:01 | 32.38 | 17.78 | 0.404871E+09 | 550.07 | 25-JUL-13:50 | 32.38 | 17.78 |
August | 0.905826E+10 | 14659.89 | 13-AUG-13:42 | 29.72 | 18.15 | 0.454090E+09 | 551.49 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.869593E+10 | 15869.27 | 03-SEP-13:41 | 32.52 | 16.77 | 0.403105E+09 | 611.59 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.838076E+10 | 16554.33 | 01-OCT-11:41 | 25.32 | 14.37 | 0.412508E+09 | 608.58 | 05-OCT-13:30 | 26.15 | 12.94 |
November | 0.641543E+10 | 14956.33 | 19-NOV-13:12 | 11.83 | 2.88 | 0.400406E+09 | 597.85 | 01-NOV-13:09 | 11.83 | 2.88 |
December | 0.536922E+10 | 14395.39 | 31-DEC-13:42 | 9.72 | 1.51 | 0.376931E+09 | 556.19 | 29-DEC-14:09 | 9.72 | 1.51 |
Annual Sum or Average | 0.795365E+11 | 0.486777E+10 | ||||||||
Minimum of Months | 0.484322E+10 | 9494.46 | 9.72 | 1.51 | 0.354486E+09 | 549.51 | 9.72 | 1.50 | ||
Maximum of Months | 0.905826E+10 | 16554.33 | 34.07 | 18.15 | 0.454090E+09 | 611.59 | 32.38 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166202E+10 | 4666.29 | 26-JAN-16:30 | 10.30 | 1.40 | 0.209527E+09 | 338.69 | 24-JAN-16:49 | 10.30 | 1.40 |
February | 0.208114E+10 | 7012.74 | 15-FEB-16:30 | 16.95 | 6.18 | 0.195272E+09 | 347.82 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.335882E+10 | 12381.66 | 12-MAR-15:52 | 19.40 | 6.09 | 0.242153E+09 | 347.84 | 09-MAR-14:00 | 19.40 | 6.09 |
April | 0.445179E+10 | 12072.33 | 09-APR-17:02 | 18.80 | 5.96 | 0.233270E+09 | 347.86 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.527095E+10 | 15984.01 | 29-MAY-16:41 | 26.28 | 13.29 | 0.260981E+09 | 347.86 | 09-MAY-13:20 | 26.28 | 13.29 |
June | 0.648326E+10 | 17207.60 | 25-JUN-17:11 | 33.13 | 14.92 | 0.269252E+09 | 347.86 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.672011E+10 | 17512.15 | 04-JUL-16:51 | 36.10 | 14.82 | 0.253838E+09 | 347.85 | 21-JUL-09:39 | 30.73 | 16.84 |
August | 0.678895E+10 | 17030.66 | 20-AUG-16:01 | 34.90 | 15.92 | 0.283354E+09 | 347.89 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.540533E+10 | 15720.47 | 04-SEP-17:31 | 25.97 | 15.84 | 0.245399E+09 | 347.84 | 07-SEP-13:00 | 21.70 | 15.53 |
October | 0.434077E+10 | 15277.45 | 01-OCT-15:01 | 28.40 | 12.95 | 0.236199E+09 | 347.85 | 04-OCT-13:00 | 25.60 | 13.67 |
November | 0.274225E+10 | 6176.42 | 02-NOV-16:00 | 16.70 | 9.78 | 0.218802E+09 | 347.83 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.156756E+10 | 3720.67 | 29-DEC-16:00 | 11.70 | 3.88 | 0.202763E+09 | 338.68 | 13-DEC-16:40 | 11.70 | 3.88 |
Annual Sum or Average | 0.508730E+11 | 0.285081E+10 | ||||||||
Minimum of Months | 0.156756E+10 | 3720.67 | 10.30 | 1.40 | 0.195272E+09 | 338.68 | 10.30 | 1.40 | ||
Maximum of Months | 0.678895E+10 | 17512.15 | 36.10 | 15.92 | 0.283354E+09 | 347.89 | 30.73 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293319E+10 | 12043.81 | 17-JAN-06:13 | -3.5 |
February | 0.204718E+10 | 11815.79 | 06-FEB-07:02 | -5.4 |
March | 0.124457E+10 | 7564.66 | 06-MAR-07:01 | -0.3 |
April | 0.508316E+09 | 4870.15 | 06-APR-05:02 | 2.12 |
May | 0.256469E+09 | 7153.11 | 30-MAY-05:02 | 14.72 |
June | 93772784.59 | 7403.49 | 14-JUN-05:02 | 16.28 |
July | 38430973.09 | 6386.59 | 13-JUL-05:02 | 17.57 |
August | 39584682.84 | 6411.74 | 28-AUG-05:02 | 16.52 |
September | 0.136815E+09 | 6635.19 | 11-SEP-05:02 | 15.00 |
October | 0.738608E+09 | 7314.57 | 26-OCT-06:01 | -1.4 |
November | 0.134413E+10 | 9752.75 | 27-NOV-07:01 | -4.2 |
December | 0.292188E+10 | 10126.44 | 15-DEC-07:01 | -8.1 |
Annual Sum or Average | 0.123030E+11 | |||
Minimum of Months | 38430973.09 | 4870.15 | -8.1 | |
Maximum of Months | 0.293319E+10 | 12043.81 | 17.57 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137133E+10 | 6734.02 | 22-JAN-14:43 | 13.43 |
February | 0.895480E+09 | 5644.66 | 12-FEB-14:12 | 17.57 |
March | 0.349785E+09 | 6565.45 | 12-MAR-15:52 | 19.40 |
April | 41498005.21 | 4209.56 | 16-APR-16:12 | 19.80 |
May | 29175745.73 | 3923.94 | 07-MAY-15:52 | 24.40 |
June | 25664332.91 | 3239.32 | 11-JUN-16:42 | 28.22 |
July | 30135497.24 | 3655.50 | 30-JUL-15:21 | 33.60 |
August | 24411114.01 | 3974.98 | 20-AUG-15:21 | 35.00 |
September | 30322918.70 | 4100.83 | 24-SEP-15:22 | 25.60 |
October | 0.132920E+09 | 6060.62 | 15-OCT-15:42 | 20.68 |
November | 0.503960E+09 | 5765.92 | 05-NOV-11:32 | 9.43 |
December | 0.136001E+10 | 6586.14 | 24-DEC-14:32 | 12.93 |
Annual Sum or Average | 0.479470E+10 | |||
Minimum of Months | 24411114.01 | 3239.32 | 9.43 | |
Maximum of Months | 0.137133E+10 | 6734.02 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594521E+09 | 4194.84 | 01-JAN-14:02 | 15.68 |
February | 0.302560E+09 | 4522.82 | 16-FEB-06:02 | 1.70 |
March | 59821480.02 | 4787.60 | 17-MAR-05:02 | 7.02 |
April | 23496343.74 | 5425.02 | 24-APR-05:02 | 6.20 |
May | 28704540.41 | 4902.40 | 04-MAY-05:03 | 5.60 |
June | 25364754.82 | 4183.98 | 10-JUN-05:03 | 12.30 |
July | 26352142.02 | 3886.42 | 28-JUL-04:02 | 18.22 |
August | 26945494.17 | 4154.19 | 29-AUG-04:02 | 16.02 |
September | 33642902.32 | 4613.74 | 08-SEP-04:03 | 15.60 |
October | 61904474.60 | 6064.70 | 25-OCT-05:02 | -1.1 |
November | 0.110626E+09 | 6245.08 | 24-NOV-06:02 | 2.88 |
December | 0.506235E+09 | 4207.06 | 24-DEC-14:13 | 12.57 |
Annual Sum or Average | 0.180017E+10 | |||
Minimum of Months | 23496343.74 | 3886.42 | -1.1 | |
Maximum of Months | 0.594521E+09 | 6245.08 | 18.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8690956.52 | 16828.92 | 23-JAN-07:01 | -3.2 |
February | 5229935.26 | 16862.44 | 06-FEB-07:03 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 5607409.97 | 16217.73 | 26-DEC-07:01 | -1.8 |
Annual Sum or Average | 19528301.75 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 8690956.52 | 16862.44 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426327E+09 | 31217.83 | 17-JAN-06:01 | -3.4 |
February | 0.202735E+09 | 31102.87 | 06-FEB-06:01 | -4.6 |
March | 12530593.04 | 28060.64 | 06-MAR-07:01 | -0.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 2802062.51 | 27827.00 | 26-OCT-06:01 | -1.4 |
November | 51323993.36 | 29427.87 | 27-NOV-06:01 | -4.4 |
December | 0.390638E+09 | 31259.11 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.108636E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.426327E+09 | 31259.11 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160550E+10 | 11418.45 | 17-JAN-05:11 | -3.3 |
February | 0.981783E+09 | 11445.13 | 06-FEB-05:01 | -4.4 |
March | 0.278544E+09 | 10189.77 | 04-MAR-06:01 | -1.7 |
April | 25063083.90 | 8968.89 | 06-APR-06:02 | 1.88 |
May | 2148733.05 | 6045.26 | 06-MAY-06:03 | 5.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.105400E+09 | 9975.96 | 26-OCT-05:01 | -2.5 |
November | 0.416352E+09 | 10819.02 | 27-NOV-05:02 | -4.0 |
December | 0.165832E+10 | 11220.20 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.507311E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.165832E+10 | 11445.13 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.784683E+09 | 10480.08 | 17-JAN-05:11 | -3.3 |
February | 0.422897E+09 | 10505.22 | 06-FEB-05:01 | -4.4 |
March | 98200246.61 | 9202.02 | 04-MAR-06:01 | -1.7 |
April | 5792999.05 | 5658.86 | 06-APR-06:02 | 1.88 |
May | 336257.89 | 1031.27 | 06-MAY-06:03 | 5.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 55652369.85 | 8982.59 | 26-OCT-05:01 | -2.5 |
November | 0.153020E+09 | 9708.64 | 27-NOV-05:02 | -4.0 |
December | 0.757783E+09 | 10271.78 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.227836E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.784683E+09 | 10505.22 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.888824E+09 | 13620.75 | 17-JAN-05:11 | -3.3 |
February | 0.509852E+09 | 13617.18 | 06-FEB-05:01 | -4.4 |
March | 0.169796E+09 | 12164.07 | 04-MAR-06:01 | -1.7 |
April | 22580707.10 | 10609.24 | 06-APR-06:02 | 1.88 |
May | 4194318.56 | 6974.35 | 06-MAY-06:03 | 5.78 |
June | 185448.15 | 927.24 | 09-JUN-06:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 68216396.88 | 11898.75 | 26-OCT-05:01 | -2.5 |
November | 0.149727E+09 | 12029.06 | 27-NOV-06:01 | -4.4 |
December | 0.792725E+09 | 13329.73 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.260610E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.888824E+09 | 13620.75 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.911433E+09 | 10453.96 | 17-JAN-05:11 | -3.3 |
February | 0.552860E+09 | 10490.45 | 06-FEB-05:01 | -4.4 |
March | 0.172228E+09 | 9018.94 | 04-MAR-06:01 | -1.7 |
April | 16874052.93 | 6739.14 | 06-APR-06:02 | 1.88 |
May | 3494093.13 | 4347.77 | 05-MAY-06:03 | 6.20 |
June | 512084.21 | 2560.42 | 09-JUN-06:03 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 68573478.03 | 8757.80 | 26-OCT-05:01 | -2.5 |
November | 0.234455E+09 | 9612.93 | 27-NOV-05:02 | -4.0 |
December | 0.904277E+09 | 10148.22 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.286471E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.911433E+09 | 10490.45 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471046E+09 | 8183.77 | 17-JAN-06:01 | -3.4 |
February | 0.316575E+09 | 8394.19 | 06-FEB-05:01 | -4.4 |
March | 62054880.12 | 7650.95 | 06-MAR-06:01 | -2.9 |
April | 1743870.35 | 4637.87 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1345994.99 | 7227.63 | 26-OCT-06:01 | -1.4 |
November | 24029486.30 | 7336.89 | 27-NOV-07:01 | -4.2 |
December | 0.315241E+09 | 7840.32 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.119204E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.471046E+09 | 8394.19 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159319E+09 | 6446.93 | 17-JAN-06:01 | -3.4 |
February | 70362844.26 | 6506.00 | 06-FEB-06:01 | -4.6 |
March | 11973362.46 | 6315.84 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1282547.79 | 5682.68 | 26-OCT-06:01 | -1.4 |
November | 1964146.00 | 5682.68 | 28-NOV-07:01 | -1.9 |
December | 84142920.23 | 6256.82 | 09-DEC-06:01 | -4.2 |
Annual Sum or Average | 0.329045E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.159319E+09 | 6506.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222111E+10 | 12181.30 | 20-JAN-07:10 | -4.3 |
February | 0.168479E+10 | 12284.57 | 06-FEB-07:10 | -5.4 |
March | 0.126376E+10 | 11061.33 | 30-MAR-06:10 | -1.7 |
April | 0.682488E+09 | 10171.89 | 06-APR-06:10 | 1.88 |
May | 0.396936E+09 | 9576.76 | 05-MAY-06:10 | 6.20 |
June | 51359460.09 | 8878.32 | 09-JUN-06:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 1144567.57 | 2050.19 | 31-AUG-06:05 | 13.63 |
September | 28852023.13 | 7660.98 | 25-SEP-06:05 | 11.75 |
October | 0.589625E+09 | 11088.80 | 26-OCT-07:00 | -2.8 |
November | 0.892409E+09 | 10885.73 | 27-NOV-07:10 | -4.2 |
December | 0.203605E+10 | 12292.32 | 22-DEC-07:10 | -6.1 |
Annual Sum or Average | 0.984852E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 0.222111E+10 | 12292.32 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161555E+09 | 6305.45 | 17-JAN-06:01 | -3.4 |
February | 93739514.95 | 6425.87 | 06-FEB-06:01 | -4.6 |
March | 24017446.79 | 6278.16 | 04-MAR-06:01 | -1.7 |
April | 220510.07 | 1174.95 | 08-APR-06:03 | 1.78 |
May | 123325.73 | 822.17 | 05-MAY-06:03 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1780944.69 | 5548.82 | 26-OCT-06:01 | -1.4 |
November | 6311192.79 | 5541.78 | 27-NOV-07:01 | -4.2 |
December | 97831756.04 | 6182.63 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.385579E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 0.161555E+09 | 6425.87 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448657E+09 | 9024.60 | 17-JAN-05:03 | -3.3 |
February | 0.228228E+09 | 9274.50 | 06-FEB-05:01 | -4.4 |
March | 32861256.88 | 8161.81 | 04-MAR-06:01 | -1.7 |
April | 496666.37 | 3281.18 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 9003829.26 | 7903.17 | 26-OCT-06:01 | -1.4 |
November | 53345105.77 | 8424.01 | 27-NOV-06:01 | -4.4 |
December | 0.405933E+09 | 8791.06 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.117853E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.448657E+09 | 9274.50 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227250E+09 | 6905.74 | 17-JAN-05:03 | -3.3 |
February | 88795272.45 | 7531.69 | 06-FEB-05:01 | -4.4 |
March | 15661878.26 | 6420.56 | 04-MAR-06:01 | -1.7 |
April | 346639.85 | 1804.64 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 6943422.51 | 6177.11 | 25-OCT-06:01 | -0.8 |
November | 19007808.88 | 6721.49 | 28-NOV-06:01 | -2.1 |
December | 0.196364E+09 | 6990.10 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.554368E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.227250E+09 | 7531.69 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208873E+09 | 10728.26 | 17-JAN-06:01 | -3.4 |
February | 93452510.29 | 11113.64 | 06-FEB-05:01 | -4.4 |
March | 16224864.33 | 9655.64 | 30-MAR-06:01 | -1.7 |
April | 629290.21 | 3616.78 | 08-APR-06:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 5637344.03 | 9724.41 | 26-OCT-06:01 | -1.4 |
November | 11611401.81 | 9669.24 | 27-NOV-07:01 | -4.2 |
December | 0.170092E+09 | 10702.97 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.506520E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.208873E+09 | 11113.64 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251003E+09 | 7078.93 | 17-JAN-06:01 | -3.4 |
February | 0.127096E+09 | 7735.80 | 06-FEB-05:01 | -4.4 |
March | 26220793.40 | 6760.60 | 04-MAR-06:01 | -1.7 |
April | 1753357.80 | 3897.86 | 08-APR-06:03 | 1.78 |
May | 315978.84 | 1670.66 | 05-MAY-06:03 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 8161093.16 | 6470.98 | 25-OCT-06:01 | -0.8 |
November | 31316739.12 | 6625.02 | 13-NOV-07:02 | 0.97 |
December | 0.222944E+09 | 7104.93 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.668811E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.251003E+09 | 7735.80 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103202E+10 | 1374.84 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.915029E+09 | 1241.94 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105444E+10 | 1108.55 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.923295E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.988599E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.974269E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.918971E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102672E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.935392E+09 | 1222.02 | 08-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.997093E+09 | 1222.19 | 25-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.102170E+10 | 1503.90 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.102978E+10 | 1503.90 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118173E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.915029E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105444E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.649457E+09 | 869.44 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.577570E+09 | 773.79 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.666778E+09 | 656.53 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.586005E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.628753E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.619168E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.583505E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.651453E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.591894E+09 | 763.30 | 08-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.627506E+09 | 735.20 | 25-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.645616E+09 | 952.10 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.647830E+09 | 952.10 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.747553E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.577570E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.666778E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101215E+10 | 1302.44 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.905579E+09 | 1231.54 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105127E+10 | 1088.03 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.925234E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.992745E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.979258E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.922583E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102898E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.934530E+09 | 1219.86 | 08-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.985440E+09 | 1198.28 | 25-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.100480E+10 | 1503.90 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.100260E+10 | 1503.90 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117452E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.905579E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105127E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644242E+09 | 806.31 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.574873E+09 | 786.69 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.665929E+09 | 744.49 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.583972E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.625831E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.617817E+09 | 657.80 | 08-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.582507E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.650129E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.591207E+09 | 775.73 | 08-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.627785E+09 | 784.18 | 25-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.637169E+09 | 952.03 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.640761E+09 | 952.03 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.744222E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.574873E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.665929E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.102952E+10 | 1366.35 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.913609E+09 | 1230.67 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105327E+10 | 1091.03 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.923046E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.988322E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.973975E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.918610E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102682E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.934516E+09 | 1209.88 | 08-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.995431E+09 | 1209.82 | 25-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.101968E+10 | 1503.90 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.102764E+10 | 1503.90 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118044E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.913609E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105327E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.648356E+09 | 864.81 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.576862E+09 | 767.62 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.666288E+09 | 646.66 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.585806E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.628504E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.618828E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.583269E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.651240E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.591578E+09 | 756.77 | 08-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.626930E+09 | 727.22 | 25-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.644636E+09 | 952.10 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.646963E+09 | 952.10 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.746926E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.576862E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.666288E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101149E+10 | 1292.47 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.905004E+09 | 1219.70 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105061E+10 | 1069.36 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.924830E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.992368E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.978546E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.921962E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102852E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.933873E+09 | 1207.61 | 08-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.985078E+09 | 1184.58 | 25-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.100417E+10 | 1503.90 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.100197E+10 | 1503.90 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117384E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.905004E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105061E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.643636E+09 | 800.27 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.574292E+09 | 781.14 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.665498E+09 | 737.40 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.583697E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.625640E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.617549E+09 | 648.02 | 08-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.582284E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.649853E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.590772E+09 | 769.83 | 08-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.627098E+09 | 778.52 | 25-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.636331E+09 | 952.03 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.639603E+09 | 952.03 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.743625E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.574292E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.665498E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103202E+10 | 1374.84 | 09-JAN-16:00 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.915029E+09 | 1241.92 | 16-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105443E+10 | 1108.53 | 20-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.923295E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.988599E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.974269E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.918970E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102672E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.935392E+09 | 1222.00 | 08-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.997094E+09 | 1222.18 | 25-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.102170E+10 | 1503.90 | 13-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.102978E+10 | 1503.90 | 01-DEC-16:00 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118173E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.915029E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105443E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.649457E+09 | 869.45 | 09-JAN-16:00 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.577570E+09 | 773.78 | 16-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.666779E+09 | 656.51 | 14-MAR-15:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.586005E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.628753E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.619168E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.583505E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.651453E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.591894E+09 | 763.29 | 08-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.627506E+09 | 735.19 | 25-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.645617E+09 | 952.10 | 13-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.647830E+09 | 952.10 | 01-DEC-16:00 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.747554E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.577570E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.666779E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101215E+10 | 1302.43 | 04-JAN-16:00 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.905579E+09 | 1231.52 | 16-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105127E+10 | 1088.00 | 20-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.925234E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.992745E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.979258E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.922583E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102898E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.934530E+09 | 1219.84 | 08-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.985440E+09 | 1198.26 | 25-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.100480E+10 | 1503.90 | 13-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.100260E+10 | 1503.90 | 01-DEC-16:00 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.117452E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.905579E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105127E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644242E+09 | 806.30 | 04-JAN-16:00 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.574873E+09 | 786.67 | 16-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.665929E+09 | 744.48 | 22-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.583973E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.625831E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.617817E+09 | 657.78 | 08-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.582507E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.650129E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.591207E+09 | 775.71 | 08-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.627786E+09 | 784.17 | 25-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.637169E+09 | 952.03 | 13-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.640761E+09 | 952.03 | 01-DEC-16:00 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.744222E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.574873E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.665929E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103202E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738874E+09 |
February | 0.901968E+09 | 0.915029E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696637E+09 |
March | 0.107774E+10 | 0.105444E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685811E+09 |
April | 0.956342E+09 | 0.923295E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1593756.64 | 0.504641E+09 |
May | 0.103597E+10 | 0.988599E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14900823.26 | 0.353284E+09 |
June | 0.103308E+10 | 0.974269E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65726888.25 | 0.195211E+09 |
July | 0.959235E+09 | 0.918971E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94576703.16 | 0.114050E+09 |
August | 0.107774E+10 | 0.102672E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48767598.15 | 0.148264E+09 |
September | 0.956342E+09 | 0.935392E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16854789.17 | 0.212737E+09 |
October | 0.994195E+09 | 0.997093E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4109399.82 | 0.378152E+09 |
November | 0.984487E+09 | 0.102170E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591148E+09 |
December | 0.959235E+09 | 0.102978E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674070E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118173E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246530E+09 | 0.529288E+10 |
Minimum of Months | 0.901968E+09 | 0.915029E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114050E+09 |
Maximum of Months | 0.107774E+10 | 0.105444E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94576703.16 | 0.738874E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.649457E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503617E+09 |
February | 0.571020E+09 | 0.577570E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473133E+09 |
March | 0.682301E+09 | 0.666778E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468952E+09 |
April | 0.605444E+09 | 0.586005E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1176990.89 | 0.355071E+09 |
May | 0.655854E+09 | 0.628753E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10137245.22 | 0.243317E+09 |
June | 0.654023E+09 | 0.619168E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45409797.69 | 0.130343E+09 |
July | 0.607275E+09 | 0.583505E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64004957.74 | 78552569.09 |
August | 0.682301E+09 | 0.651453E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33198975.95 | 0.101520E+09 |
September | 0.605444E+09 | 0.591894E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11585485.88 | 0.143951E+09 |
October | 0.629407E+09 | 0.627506E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2927238.79 | 0.261092E+09 |
November | 0.623262E+09 | 0.645616E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406408E+09 |
December | 0.607275E+09 | 0.647830E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457532E+09 |
Annual Sum or Average | 0.755301E+10 | 0.747553E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168441E+09 | 0.362349E+10 |
Minimum of Months | 0.571020E+09 | 0.577570E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78552569.09 |
Maximum of Months | 0.682301E+09 | 0.666778E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64004957.74 | 0.503617E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101215E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811481E+09 |
February | 0.901968E+09 | 0.905579E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759497E+09 |
March | 0.107774E+10 | 0.105127E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731693E+09 |
April | 0.956342E+09 | 0.925234E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1345220.75 | 0.530186E+09 |
May | 0.103597E+10 | 0.992745E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13410446.03 | 0.354965E+09 |
June | 0.103308E+10 | 0.979258E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68157157.11 | 0.189730E+09 |
July | 0.959235E+09 | 0.922583E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94830426.05 | 0.112032E+09 |
August | 0.107774E+10 | 0.102898E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47047229.92 | 0.151492E+09 |
September | 0.956342E+09 | 0.934530E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14550506.44 | 0.228131E+09 |
October | 0.994195E+09 | 0.985440E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3298417.74 | 0.418430E+09 |
November | 0.984487E+09 | 0.100480E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665284E+09 |
December | 0.959235E+09 | 0.100260E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745361E+09 |
Annual Sum or Average | 0.119305E+11 | 0.117452E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242639E+09 | 0.569828E+10 |
Minimum of Months | 0.901968E+09 | 0.905579E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112032E+09 |
Maximum of Months | 0.107774E+10 | 0.105127E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94830426.05 | 0.811481E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.644242E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506409E+09 |
February | 0.570983E+09 | 0.574873E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478811E+09 |
March | 0.682256E+09 | 0.665929E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471018E+09 |
April | 0.605404E+09 | 0.583972E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 880334.35 | 0.351950E+09 |
May | 0.655811E+09 | 0.625831E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9450966.62 | 0.238969E+09 |
June | 0.653980E+09 | 0.617817E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43576989.65 | 0.131960E+09 |
July | 0.607235E+09 | 0.582507E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64694039.45 | 76803848.23 |
August | 0.682256E+09 | 0.650129E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32716423.23 | 0.100788E+09 |
September | 0.605404E+09 | 0.591207E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11473067.78 | 0.146237E+09 |
October | 0.629366E+09 | 0.627785E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2830756.27 | 0.260678E+09 |
November | 0.623221E+09 | 0.637169E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408677E+09 |
December | 0.607235E+09 | 0.640761E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462485E+09 |
Annual Sum or Average | 0.755252E+10 | 0.744222E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165623E+09 | 0.363479E+10 |
Minimum of Months | 0.570983E+09 | 0.574873E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76803848.23 |
Maximum of Months | 0.682256E+09 | 0.665929E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64694039.45 | 0.506409E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.102952E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425032E+09 |
February | 0.901968E+09 | 0.913609E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390873E+09 |
March | 0.107774E+10 | 0.105327E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375291E+09 |
April | 0.956342E+09 | 0.923046E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1140306.96 | 0.271781E+09 |
May | 0.103597E+10 | 0.988322E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9378670.61 | 0.189365E+09 |
June | 0.103308E+10 | 0.973975E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37698150.53 | 0.104302E+09 |
July | 0.959235E+09 | 0.918610E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53646536.79 | 59322350.51 |
August | 0.107774E+10 | 0.102682E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27295903.05 | 80608706.51 |
September | 0.956342E+09 | 0.934516E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9293714.45 | 0.120788E+09 |
October | 0.994195E+09 | 0.995431E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213578.18 | 0.221450E+09 |
November | 0.984487E+09 | 0.101968E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352725E+09 |
December | 0.959235E+09 | 0.102764E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395395E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118044E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140667E+09 | 0.298693E+10 |
Minimum of Months | 0.901968E+09 | 0.913609E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59322350.51 |
Maximum of Months | 0.107774E+10 | 0.105327E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53646536.79 | 0.425032E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.648356E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293975E+09 |
February | 0.571020E+09 | 0.576862E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270157E+09 |
March | 0.682301E+09 | 0.666288E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264901E+09 |
April | 0.605444E+09 | 0.585806E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 627540.27 | 0.200550E+09 |
May | 0.655854E+09 | 0.628504E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5245470.50 | 0.137196E+09 |
June | 0.654023E+09 | 0.618828E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24289603.49 | 73285925.86 |
July | 0.607275E+09 | 0.583269E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33865588.35 | 44730739.68 |
August | 0.682301E+09 | 0.651240E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17314145.07 | 59290257.83 |
September | 0.605444E+09 | 0.591578E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5927861.84 | 85457532.20 |
October | 0.629407E+09 | 0.626930E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1393046.08 | 0.155891E+09 |
November | 0.623262E+09 | 0.644636E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245524E+09 |
December | 0.607275E+09 | 0.646963E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272036E+09 |
Annual Sum or Average | 0.755301E+10 | 0.746926E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88663255.59 | 0.210299E+10 |
Minimum of Months | 0.571020E+09 | 0.576862E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44730739.68 |
Maximum of Months | 0.682301E+09 | 0.666288E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33865588.35 | 0.293975E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101149E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637647E+10 |
February | 0.901968E+09 | 0.905004E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524578E+10 |
March | 0.107774E+10 | 0.105061E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449720E+10 |
April | 0.956342E+09 | 0.924830E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31228450.13 | 0.269596E+10 |
May | 0.103597E+10 | 0.992368E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228631E+09 | 0.185236E+10 |
June | 0.103308E+10 | 0.978546E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136663E+10 | 0.690867E+09 |
July | 0.959235E+09 | 0.921962E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149932E+10 | 0.247330E+09 |
August | 0.107774E+10 | 0.102852E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115197E+10 | 0.558389E+09 |
September | 0.956342E+09 | 0.933873E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459396E+09 | 0.979179E+09 |
October | 0.994195E+09 | 0.985078E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67846586.64 | 0.306862E+10 |
November | 0.984487E+09 | 0.100417E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507581E+10 |
December | 0.959235E+09 | 0.100197E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669593E+10 |
Annual Sum or Average | 0.119305E+11 | 0.117384E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480502E+10 | 0.379839E+11 |
Minimum of Months | 0.901968E+09 | 0.905004E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247330E+09 |
Maximum of Months | 0.107774E+10 | 0.105061E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149932E+10 | 0.669593E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.643636E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295096E+09 |
February | 0.570983E+09 | 0.574292E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273429E+09 |
March | 0.682256E+09 | 0.665498E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264105E+09 |
April | 0.605404E+09 | 0.583697E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 513077.93 | 0.198307E+09 |
May | 0.655811E+09 | 0.625640E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4955865.06 | 0.134244E+09 |
June | 0.653980E+09 | 0.617549E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23245586.64 | 74341979.95 |
July | 0.607235E+09 | 0.582284E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34297068.41 | 43266547.24 |
August | 0.682256E+09 | 0.649853E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17215592.45 | 58778554.87 |
September | 0.605404E+09 | 0.590772E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5759681.33 | 86902323.60 |
October | 0.629366E+09 | 0.627098E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339332.84 | 0.156056E+09 |
November | 0.623221E+09 | 0.636331E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245086E+09 |
December | 0.607235E+09 | 0.639603E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274148E+09 |
Annual Sum or Average | 0.755252E+10 | 0.743625E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87326204.65 | 0.210376E+10 |
Minimum of Months | 0.570983E+09 | 0.574292E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43266547.24 |
Maximum of Months | 0.682256E+09 | 0.665498E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34297068.41 | 0.295096E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103202E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662713E+09 |
February | 0.901968E+09 | 0.915029E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620855E+09 |
March | 0.107774E+10 | 0.105443E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611814E+09 |
April | 0.956342E+09 | 0.923295E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1343204.55 | 0.446846E+09 |
May | 0.103597E+10 | 0.988599E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12677673.78 | 0.311741E+09 |
June | 0.103308E+10 | 0.974269E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55677840.75 | 0.170234E+09 |
July | 0.959235E+09 | 0.918970E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79441824.18 | 98907903.25 |
August | 0.107774E+10 | 0.102672E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41128357.96 | 0.128789E+09 |
September | 0.956342E+09 | 0.935392E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14136407.70 | 0.188166E+09 |
October | 0.994195E+09 | 0.997094E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3397600.61 | 0.340773E+09 |
November | 0.984487E+09 | 0.102170E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537137E+09 |
December | 0.959235E+09 | 0.102978E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608253E+09 |
Annual Sum or Average | 0.119305E+11 | 0.118173E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207803E+09 | 0.472623E+10 |
Minimum of Months | 0.901968E+09 | 0.915029E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98907903.25 |
Maximum of Months | 0.107774E+10 | 0.105443E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79441824.18 | 0.662713E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.649457E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449734E+09 |
February | 0.421807E+09 | 0.577570E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419616E+09 |
March | 0.502994E+09 | 0.666779E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412878E+09 |
April | 0.447140E+09 | 0.586005E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1067699.93 | 0.308475E+09 |
May | 0.484071E+09 | 0.628753E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8822294.95 | 0.211583E+09 |
June | 0.482240E+09 | 0.619168E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39143302.85 | 0.112487E+09 |
July | 0.448971E+09 | 0.583505E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54501562.47 | 67313690.73 |
August | 0.502994E+09 | 0.651453E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28398965.17 | 86907550.71 |
September | 0.447140E+09 | 0.591894E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9986789.68 | 0.125467E+09 |
October | 0.465148E+09 | 0.627506E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2455892.67 | 0.231023E+09 |
November | 0.460569E+09 | 0.645617E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364870E+09 |
December | 0.448971E+09 | 0.647830E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411284E+09 |
Annual Sum or Average | 0.557719E+10 | 0.747554E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144377E+09 | 0.320164E+10 |
Minimum of Months | 0.421807E+09 | 0.577570E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67313690.73 |
Maximum of Months | 0.502994E+09 | 0.666779E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54501562.47 | 0.449734E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.101215E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723320E+09 |
February | 0.901968E+09 | 0.905579E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672618E+09 |
March | 0.107774E+10 | 0.105127E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646671E+09 |
April | 0.956342E+09 | 0.925234E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1155216.58 | 0.465755E+09 |
May | 0.103597E+10 | 0.992745E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11377865.27 | 0.312899E+09 |
June | 0.103308E+10 | 0.979258E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57889961.26 | 0.165988E+09 |
July | 0.959235E+09 | 0.922583E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79386183.38 | 97408780.48 |
August | 0.107774E+10 | 0.102898E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39556762.01 | 0.131470E+09 |
September | 0.956342E+09 | 0.934530E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12090842.58 | 0.200031E+09 |
October | 0.994195E+09 | 0.985440E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2650375.52 | 0.370975E+09 |
November | 0.984487E+09 | 0.100480E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594789E+09 |
December | 0.959235E+09 | 0.100260E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666646E+09 |
Annual Sum or Average | 0.119305E+11 | 0.117452E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204107E+09 | 0.504857E+10 |
Minimum of Months | 0.901968E+09 | 0.905579E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97408780.48 |
Maximum of Months | 0.107774E+10 | 0.105127E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79386183.38 | 0.723320E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.644242E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452144E+09 |
February | 0.570983E+09 | 0.574873E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424398E+09 |
March | 0.682256E+09 | 0.665929E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415759E+09 |
April | 0.605404E+09 | 0.583973E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 747480.17 | 0.308736E+09 |
May | 0.655811E+09 | 0.625831E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7584613.05 | 0.210487E+09 |
June | 0.653980E+09 | 0.617817E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36348311.70 | 0.114984E+09 |
July | 0.607235E+09 | 0.582507E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53491078.76 | 66733368.46 |
August | 0.682256E+09 | 0.650129E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27201478.39 | 87241184.56 |
September | 0.605404E+09 | 0.591207E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9459688.24 | 0.128536E+09 |
October | 0.629366E+09 | 0.627786E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2240298.07 | 0.232164E+09 |
November | 0.623221E+09 | 0.637169E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366843E+09 |
December | 0.607235E+09 | 0.640761E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415225E+09 |
Annual Sum or Average | 0.755252E+10 | 0.744222E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137073E+09 | 0.322325E+10 |
Minimum of Months | 0.570983E+09 | 0.574873E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66733368.46 |
Maximum of Months | 0.682256E+09 | 0.665929E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53491078.76 | 0.452144E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954026E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886220E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864088E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543288.08 | 0.624180E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12374315.25 | 0.426723E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64793673.40 | 0.227142E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93693082.05 | 0.126702E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44152300.36 | 0.173610E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12923777.05 | 0.263349E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2355839.31 | 0.489984E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783074E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881577E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230836E+09 | 0.670067E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126702E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93693082.05 | 0.954026E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116369E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109303E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107751E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757586.88 | 0.785149E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15882629.68 | 0.542685E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82094522.07 | 0.290370E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118799E+09 | 0.163697E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56477821.00 | 0.220934E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17177783.38 | 0.330225E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3290061.13 | 0.605778E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955474E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107203E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294480E+09 | 0.830057E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163697E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118799E+09 | 0.116369E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114914E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109120E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108472E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22119.71 | 0.812496E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8407434.02 | 0.554659E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72917534.31 | 0.289345E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105412E+09 | 0.162013E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48962252.69 | 0.219018E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11546926.32 | 0.331837E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1626894.94 | 0.599731E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939168E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104699E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248895E+09 | 0.828031E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162013E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105412E+09 | 0.114914E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1374.84 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1950.25 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1241.94 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1567.16 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1108.55 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1404.83 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 | 01-APR-17:02 | 1643.99 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.67 | 14-MAY-16:40 | 1033.91 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.29 | 18-JUN-16:10 | 777.12 | 04-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 636.46 | 04-JUL-15:05 | 461.46 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.73 | 20-AUG-16:56 | 427.17 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1222.02 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.30 | 03-SEP-14:40 | 575.05 | 18-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1222.19 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.73 | 01-OCT-16:00 | 975.81 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1657.29 | 03-NOV-21:03 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2177.81 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.17 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 636.46 | 2177.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 869.44 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1312.29 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 773.79 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1052.16 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 656.53 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 945.09 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 | 01-APR-17:50 | 1160.67 | 23-APR-09:00 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.40 | 14-MAY-16:40 | 675.52 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.03 | 18-JUN-16:10 | 524.20 | 04-JUN-17:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.73 | 04-JUL-15:10 | 313.17 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.38 | 20-AUG-17:00 | 358.62 | 27-AUG-07:40 |
September | 827.22 | 01-SEP-09:09 | 763.30 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.65 | 03-SEP-14:40 | 398.91 | 17-SEP-20:00 |
October | 827.22 | 02-OCT-09:09 | 735.20 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 01-OCT-16:00 | 647.33 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1105.64 | 03-NOV-21:03 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1452.06 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.17 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 455.73 | 1452.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1302.44 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2090.46 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1231.54 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1680.26 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1088.03 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1458.49 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 29-APR-16:00 | 1682.11 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.81 | 14-MAY-16:40 | 1019.33 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.24 | 18-JUN-16:10 | 770.93 | 04-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 643.46 | 04-JUL-15:05 | 464.48 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.23 | 20-AUG-16:56 | 433.85 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1219.86 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.93 | 03-SEP-14:36 | 652.10 | 17-SEP-20:00 |
October | 1306.65 | 02-OCT-09:09 | 1198.28 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 | 01-OCT-15:56 | 1003.99 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1709.38 | 03-NOV-21:13 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2272.19 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.85 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 643.46 | 2272.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 806.31 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1336.94 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 786.69 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1078.98 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 744.49 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 941.13 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 29-APR-16:00 | 1243.52 | 15-APR-17:10 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 21-MAY-17:20 | 682.25 | 18-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 657.80 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.13 | 18-JUN-16:04 | 537.94 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.19 | 04-JUL-15:03 | 320.00 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.28 | 20-AUG-16:54 | 302.17 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 775.73 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.63 | 03-SEP-16:40 | 440.65 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 784.18 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 | 01-OCT-15:56 | 657.61 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1112.62 | 03-NOV-21:03 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1465.60 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.17 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 399.19 | 1465.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1366.35 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1197.07 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1230.67 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 929.28 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1091.03 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 783.09 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 | 01-APR-17:02 | 909.03 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.50 | 14-MAY-16:50 | 577.05 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.61 | 18-JUN-16:00 | 440.94 | 10-JUN-01:40 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.12 | 04-JUL-15:00 | 241.04 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.19 | 05-AUG-17:02 | 240.41 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1209.88 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.23 | 03-SEP-14:50 | 340.20 | 07-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 1209.82 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 01-OCT-16:30 | 559.26 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 973.52 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1319.18 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.41 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 362.12 | 1319.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 864.81 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 825.68 | 16-JAN-18:00 |
February | 827.22 | 01-FEB-10:09 | 767.62 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 640.44 | 05-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 646.66 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 566.57 | 14-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.42 | 01-APR-17:50 | 633.79 | 07-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.28 | 14-MAY-17:10 | 390.75 | 03-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.37 | 18-JUN-16:00 | 301.73 | 10-JUN-01:30 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 | 04-JUL-15:00 | 175.15 | 15-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.88 | 05-AUG-17:02 | 174.03 | 22-AUG-22:00 |
September | 827.22 | 01-SEP-09:09 | 756.77 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.31 | 03-SEP-15:10 | 244.48 | 18-SEP-01:00 |
October | 827.22 | 02-OCT-09:09 | 727.22 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 | 01-OCT-16:30 | 381.22 | 11-OCT-23:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 657.44 | 03-NOV-24:00 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 900.27 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.03 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 | 900.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1292.47 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 29192.84 | 30-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1219.70 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 27859.85 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1069.36 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23743.33 | 30-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2152.75 | 13-APR-17:00 | 19406.47 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6103.88 | 19-MAY-16:10 | 15109.23 | 04-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13835.26 | 28-JUN-16:02 | 12568.52 | 09-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12481.73 | 21-JUL-16:02 | 4319.71 | 28-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10073.65 | 01-AUG-16:03 | 9116.59 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 1207.61 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5907.48 | 20-SEP-17:00 | 11225.34 | 20-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1184.58 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2924.31 | 06-OCT-16:10 | 23474.06 | 26-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26902.61 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31450.73 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4319.71 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13835.26 | 31450.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 800.27 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 836.92 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 781.14 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 652.28 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 737.40 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 555.40 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 29-APR-16:00 | 652.03 | 15-APR-17:20 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 14-MAY-13:00 | 403.38 | 18-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 648.02 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.54 | 18-JUN-15:53 | 312.99 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.48 | 04-JUL-14:53 | 174.74 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 | 20-AUG-16:57 | 177.66 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 769.83 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.86 | 03-SEP-15:10 | 249.00 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 778.52 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.12 | 11-OCT-13:00 | 388.56 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 674.52 | 03-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 908.27 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.74 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 229.48 | 908.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1374.84 | 09-JAN-16:00 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1813.89 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1241.92 | 16-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1439.96 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1108.53 | 20-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1276.58 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.06 | 01-APR-17:02 | 1450.61 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.30 | 14-MAY-16:30 | 915.74 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.83 | 18-JUN-15:50 | 690.07 | 10-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.92 | 04-JUL-14:54 | 383.95 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.21 | 05-AUG-17:02 | 369.75 | 08-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 1222.00 | 08-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.66 | 03-SEP-14:50 | 514.79 | 18-SEP-01:00 |
October | 1306.65 | 02-OCT-09:09 | 1222.18 | 25-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.76 | 01-OCT-16:30 | 852.75 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1452.88 | 03-NOV-24:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1999.52 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.75 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 551.92 | 1999.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 869.45 | 09-JAN-16:00 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1218.71 | 16-JAN-18:00 |
February | 805.43 | 01-FEB-08:09 | 773.78 | 16-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 966.13 | 05-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 656.51 | 14-MAR-15:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 854.51 | 14-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 | 01-APR-17:50 | 972.85 | 23-APR-09:10 |
May | 805.43 | 01-MAY-07:10 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.31 | 14-MAY-17:10 | 596.67 | 03-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.73 | 18-JUN-16:30 | 452.75 | 10-JUN-01:30 |
July | 805.43 | 03-JUL-07:10 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.85 | 04-JUL-15:00 | 262.56 | 15-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.69 | 05-AUG-17:10 | 309.71 | 27-AUG-08:10 |
September | 805.43 | 01-SEP-07:10 | 763.29 | 08-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.00 | 03-SEP-15:10 | 350.53 | 18-SEP-01:00 |
October | 805.43 | 02-OCT-07:10 | 735.19 | 25-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 | 01-OCT-16:30 | 564.33 | 11-OCT-23:00 |
November | 805.43 | 01-NOV-07:10 | 952.10 | 13-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 960.47 | 03-NOV-24:00 |
December | 805.43 | 01-DEC-08:09 | 952.10 | 01-DEC-16:00 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1332.41 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.56 | |||||
Maximum of Months | 805.43 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 405.85 | 1332.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1302.43 | 04-JAN-16:00 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1926.78 | 16-JAN-18:00 |
February | 1306.65 | 01-FEB-10:09 | 1231.52 | 16-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1532.25 | 05-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1088.00 | 20-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1318.70 | 14-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 | 29-APR-16:00 | 1476.18 | 07-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.80 | 14-MAY-17:10 | 904.97 | 03-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 441.41 | 18-JUN-15:50 | 681.50 | 10-JUN-01:30 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.15 | 04-JUL-14:54 | 388.15 | 15-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.98 | 05-AUG-17:02 | 378.18 | 22-AUG-22:00 |
September | 1306.65 | 01-SEP-09:09 | 1219.84 | 08-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.06 | 03-SEP-14:25 | 557.55 | 17-SEP-20:00 |
October | 1306.65 | 02-OCT-09:09 | 1198.26 | 25-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.68 | 11-OCT-14:00 | 874.92 | 11-OCT-23:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 13-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1508.26 | 03-NOV-21:13 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:00 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2079.81 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.18 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 544.15 | 2079.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 806.30 | 04-JAN-16:00 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1237.72 | 16-JAN-18:00 |
February | 827.17 | 01-FEB-10:09 | 786.67 | 16-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 988.27 | 05-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 744.48 | 22-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 853.27 | 14-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 29-APR-16:00 | 1063.79 | 15-APR-17:10 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.26 | 14-MAY-13:10 | 604.50 | 18-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 657.78 | 08-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.33 | 18-JUN-16:00 | 478.74 | 10-JUN-01:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.69 | 04-JUL-14:53 | 269.70 | 15-JUL-19:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 20-AUG-16:59 | 261.01 | 08-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 775.71 | 08-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 | 03-SEP-15:10 | 375.68 | 17-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 784.17 | 25-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 11-OCT-13:00 | 574.10 | 11-OCT-23:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 13-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 980.79 | 03-NOV-24:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:00 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1343.26 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.01 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 359.69 | 1343.26 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2685.20 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2130.06 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1841.89 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 | 17-APR-15:00 | 2039.42 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.21 | 14-MAY-16:52 | 1255.76 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.73 | 18-JUN-16:00 | 962.58 | 10-JUN-01:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.93 | 04-JUL-15:00 | 484.40 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.43 | 05-AUG-17:02 | 491.67 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.37 | 03-SEP-14:50 | 723.46 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.35 | 01-OCT-16:00 | 1173.13 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2121.84 | 03-NOV-24:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2958.40 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691.93 | 2958.40 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3196.18 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2618.46 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2291.60 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 17-APR-15:00 | 2578.85 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.35 | 14-MAY-16:52 | 1586.47 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.46 | 18-JUN-16:00 | 1211.87 | 10-JUN-01:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.86 | 04-JUL-15:00 | 620.34 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.40 | 05-AUG-17:02 | 621.97 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.24 | 03-SEP-14:50 | 901.94 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.78 | 01-OCT-16:00 | 1482.71 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2633.41 | 03-NOV-24:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3631.48 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.34 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872.86 | 3631.48 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3136.08 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2399.08 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2142.40 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 13-APR-17:00 | 2549.39 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.58 | 19-MAY-15:00 | 1547.49 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.03 | 18-JUN-16:10 | 1297.01 | 04-JUN-17:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.46 | 04-JUL-14:51 | 743.45 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.01 | 20-AUG-17:00 | 611.09 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.92 | 03-SEP-14:20 | 926.98 | 17-SEP-20:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.69 | 01-OCT-16:00 | 1479.84 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2643.32 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3351.03 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.46 | 3351.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18477.80 | 06-JAN-08:04 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26897.87 | 16-FEB-06:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30629.54 | 17-MAR-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41792.91 | 25-APR-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44378.17 | 22-MAY-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45263.19 | 28-JUN-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45750.04 | 25-JUL-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45705.46 | 15-AUG-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45005.35 | 01-SEP-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44651.93 | 03-OCT-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38568.22 | 01-NOV-05:02 | 3811.58 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18916.32 | 01-DEC-06:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18477.80 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45750.04 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2636.15 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 |
February | 4812.21 | 14-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 |
March | 5976.20 | 08-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 |
April | 9334.93 | 28-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.30 |
May | 10719.81 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 | 0.00 |
June | 13112.96 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.61 | 0.00 |
July | 12942.42 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.78 | 0.00 |
August | 12827.53 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 | 0.00 |
September | 10336.56 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.47 | 0.00 |
October | 8431.33 | 05-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
November | 4407.23 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 |
December | 2543.64 | 31-DEC-14:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2543.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13112.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.78 | 99.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1793.52 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.30 |
February | 2053.96 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.22 |
March | 2797.66 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.35 |
April | 3414.13 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.00 |
May | 4058.19 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
June | 5729.48 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.26 | 0.00 |
July | 5898.11 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 | 0.00 |
August | 6069.26 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.76 | 0.00 |
September | 4923.74 | 05-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 |
October | 4753.83 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
November | 1816.95 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.04 |
December | 1669.02 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1669.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6069.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.26 | 425.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2572.25 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.86 |
February | 2574.19 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.29 |
March | 3345.12 | 24-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.25 |
April | 3791.08 | 28-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 0.00 |
May | 4319.10 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.32 | 0.00 |
June | 6814.48 | 29-JUN-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 | 0.00 |
July | 6819.09 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | 0.00 |
August | 6023.77 | 07-AUG-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 | 0.00 |
September | 5372.22 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 |
October | 5044.12 | 02-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 |
November | 2939.20 | 01-NOV-16:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.90 |
December | 2314.82 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2314.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6819.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.32 | 350.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9388.16 | 27-JAN-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13144.52 | 15-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12999.33 | 09-MAR-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31509.87 | 27-APR-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33230.82 | 22-MAY-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34488.52 | 26-JUN-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37360.34 | 24-JUL-04:03 | 0.00 | 5548.78 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34393.35 | 14-AUG-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35461.01 | 05-SEP-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33981.35 | 02-OCT-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15721.18 | 01-NOV-05:02 | 3811.58 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10140.97 | 01-DEC-16:40 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9388.16 | 0.00 | 3963.42 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37360.34 | 6035.01 | 7133.97 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8056.53 | 26-JAN-14:10 | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12837.74 | 15-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13273.97 | 08-MAR-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18281.11 | 28-APR-15:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34756.21 | 22-MAY-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37002.33 | 26-JUN-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37294.00 | 05-JUL-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37445.85 | 07-AUG-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37010.63 | 05-SEP-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35117.30 | 02-OCT-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14086.79 | 01-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7966.36 | 29-DEC-13:50 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7966.36 | 0.00 | 3963.42 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37445.85 | 6198.29 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2091.87 | 05-JAN-14:30 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.42 |
February | 2754.66 | 14-FEB-14:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
March | 2745.71 | 16-MAR-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.66 |
April | 5438.62 | 14-APR-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 |
May | 6202.56 | 31-MAY-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 55.34 | 0.00 |
June | 13049.00 | 25-JUN-17:21 | 0.00 | 360.53 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 290.65 | 0.00 |
July | 13179.40 | 04-JUL-18:21 | 0.00 | 360.53 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 270.84 | 0.00 |
August | 11801.34 | 20-AUG-16:51 | 468.72 | 360.53 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 316.84 | 0.00 |
September | 6383.28 | 12-SEP-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 0.00 |
October | 5791.42 | 02-OCT-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 |
November | 2867.12 | 01-NOV-14:10 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.39 |
December | 2042.04 | 29-DEC-13:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2042.04 | 0.00 | 360.53 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13179.40 | 1306.65 | 927.16 | 3513.75 | 0.00 | 0.00 | 0.00 | 0.00 | 316.84 | 242.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2297.18 | 26-JAN-13:40 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.81 |
February | 3764.27 | 14-FEB-09:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
March | 4981.70 | 24-MAR-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.06 |
April | 11760.90 | 30-APR-08:32 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.65 |
May | 12807.93 | 29-MAY-08:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 |
June | 14702.81 | 18-JUN-08:42 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 |
July | 15273.93 | 04-JUL-09:01 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 |
August | 14957.52 | 20-AUG-08:52 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.75 |
September | 14555.64 | 03-SEP-09:12 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
October | 10118.70 | 01-OCT-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.08 |
November | 4941.43 | 01-NOV-09:10 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 |
December | 2291.96 | 29-DEC-13:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2291.96 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | |
Maximum of Months | 15273.93 | 827.22 | 586.97 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14005.19 | 01-JAN-13:53 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.56 |
February | 12729.16 | 14-FEB-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.16 |
March | 14308.85 | 12-MAR-13:23 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.67 |
April | 10259.75 | 28-APR-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
May | 8598.46 | 30-MAY-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 0.00 |
June | 11712.00 | 25-JUN-16:41 | 535.68 | 412.03 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 346.72 | 0.00 |
July | 15791.49 | 30-JUL-14:52 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 166.40 | 0.00 |
August | 16002.10 | 20-AUG-13:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 95.98 | 0.00 |
September | 17075.96 | 03-SEP-13:12 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 99.61 | 0.00 |
October | 17295.55 | 01-OCT-12:32 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
November | 15857.34 | 19-NOV-12:43 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.73 |
December | 13039.93 | 31-DEC-14:02 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8598.46 | 267.84 | 206.02 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17295.55 | 1306.65 | 927.16 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 346.72 | 366.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4478.13 | 26-JAN-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.89 |
February | 7154.57 | 15-FEB-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.89 |
March | 7588.59 | 24-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 |
April | 14968.75 | 16-APR-17:12 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 |
May | 16331.99 | 14-MAY-16:32 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 | 0.00 |
June | 17676.15 | 25-JUN-16:41 | 339.11 | 260.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.53 | 0.00 |
July | 17757.72 | 04-JUL-17:01 | 0.00 | 260.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.51 | 0.00 |
August | 17203.70 | 20-AUG-16:11 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 125.19 | 0.00 |
September | 17159.03 | 24-SEP-15:51 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 |
October | 12104.27 | 08-OCT-16:32 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.40 |
November | 6127.32 | 02-NOV-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
December | 3543.95 | 29-DEC-16:10 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3543.95 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17757.72 | 805.38 | 586.93 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 280.51 | 222.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1711.73 | 02-JAN-13:05 | 7633.40 | 5562.94 | 9035.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.28 |
February | 2165.10 | 15-FEB-13:07 | 3816.70 | 2781.47 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 |
March | 1808.10 | 27-MAR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
April | 3686.62 | 14-APR-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 |
May | 4493.92 | 31-MAY-16:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
June | 6630.32 | 29-JUN-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 89.01 | 0.00 |
July | 10626.06 | 04-JUL-18:11 | 0.00 | 515.04 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 151.20 | 0.00 |
August | 9210.07 | 20-AUG-16:01 | 669.60 | 515.04 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 0.00 |
September | 5475.02 | 05-SEP-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
October | 5080.49 | 02-OCT-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
November | 2460.36 | 01-NOV-12:10 | 2544.47 | 1854.31 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 |
December | 1706.33 | 31-DEC-14:22 | 334.80 | 257.52 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1706.33 | 0.00 | 257.52 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10626.06 | 7633.40 | 5562.94 | 9035.35 | 0.00 | 0.00 | 0.00 | 0.00 | 151.20 | 114.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2223.34 | 01-JAN-12:43 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.92 |
February | 2679.71 | 14-FEB-08:35 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
March | 3500.88 | 31-MAR-08:20 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 |
April | 9397.53 | 30-APR-10:22 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 |
May | 12353.32 | 29-MAY-09:21 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.85 |
June | 12164.52 | 18-JUN-09:11 | 381.52 | 293.46 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 |
July | 13361.45 | 04-JUL-09:31 | 381.52 | 293.46 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
August | 13256.13 | 20-AUG-09:21 | 381.52 | 293.46 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.73 |
September | 12814.99 | 03-SEP-09:01 | 339.13 | 260.85 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
October | 11786.48 | 01-OCT-09:42 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 |
November | 4419.52 | 01-NOV-09:10 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 |
December | 2215.22 | 31-DEC-14:22 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2215.22 | 169.56 | 130.43 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13361.45 | 1610.86 | 1173.93 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13037.28 | 01-JAN-14:43 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.83 |
February | 10737.52 | 19-FEB-14:23 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.40 |
March | 7573.86 | 13-MAR-14:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.03 |
April | 7489.21 | 28-APR-13:40 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 61.84 | 0.00 |
May | 10270.54 | 19-MAY-16:10 | 401.76 | 515.09 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 6103.88 | 0.00 |
June | 12713.57 | 28-JUN-16:20 | 1607.03 | 2060.35 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 11716.30 | 0.00 |
July | 12772.26 | 30-JUL-15:21 | 669.60 | 515.04 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 94.42 | 0.00 |
August | 13238.83 | 20-AUG-16:01 | 669.60 | 515.04 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 99.59 | 0.00 |
September | 14474.59 | 03-SEP-13:41 | 535.68 | 412.03 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 52.20 | 0.00 |
October | 14727.24 | 01-OCT-14:21 | 535.68 | 412.03 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 13471.21 | 19-NOV-14:22 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.17 |
December | 12884.01 | 31-DEC-14:22 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7489.21 | 267.84 | 206.02 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14727.24 | 1607.03 | 2060.35 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11716.30 | 438.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3721.24 | 26-JAN-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 |
February | 5563.11 | 15-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
March | 5251.24 | 07-MAR-17:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
April | 12561.34 | 16-APR-17:21 | 0.00 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 |
May | 12889.84 | 29-MAY-16:41 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
June | 13579.01 | 18-JUN-17:51 | 0.00 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 | 0.00 |
July | 14713.46 | 04-JUL-18:11 | 0.00 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 | 0.00 |
August | 14431.76 | 20-AUG-17:21 | 0.00 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 | 0.00 |
September | 13517.99 | 04-SEP-17:31 | 0.00 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.26 |
October | 12854.80 | 15-OCT-16:22 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
November | 5761.30 | 02-NOV-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 |
December | 3038.57 | 29-DEC-16:10 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3038.57 | 0.00 | 195.63 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14713.46 | 805.38 | 586.93 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 | 34.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2192.07 | 05-JAN-14:10 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
February | 2578.60 | 15-FEB-15:10 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.82 |
March | 2964.70 | 27-MAR-14:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 |
April | 5179.61 | 14-APR-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
May | 5703.99 | 31-MAY-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.81 | 0.00 |
June | 11466.15 | 25-JUN-17:51 | 0.00 | 463.54 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 174.80 | 0.00 |
July | 11877.80 | 04-JUL-17:32 | 0.00 | 515.04 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 351.31 | 0.00 |
August | 11022.47 | 20-AUG-18:01 | 0.00 | 463.54 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 0.00 |
September | 6576.34 | 03-SEP-14:22 | 401.76 | 309.03 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 157.06 | 0.00 |
October | 5498.24 | 02-OCT-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
November | 2614.81 | 01-NOV-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.56 |
December | 2147.57 | 29-DEC-14:20 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2147.57 | 0.00 | 309.03 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11877.80 | 1306.65 | 927.16 | 5019.64 | 0.00 | 0.00 | 0.00 | 0.00 | 351.31 | 218.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2697.64 | 27-JAN-12:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 |
February | 4679.77 | 14-FEB-09:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.99 |
March | 5723.43 | 31-MAR-08:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.69 |
April | 12597.09 | 30-APR-08:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.39 |
May | 15176.24 | 29-MAY-08:41 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 |
June | 15626.72 | 25-JUN-08:31 | 339.13 | 260.85 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 |
July | 16247.48 | 04-JUL-08:51 | 381.52 | 293.46 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 |
August | 16177.46 | 20-AUG-08:41 | 381.52 | 293.46 | 2859.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 |
September | 15517.38 | 03-SEP-09:01 | 339.13 | 260.85 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
October | 14270.10 | 01-OCT-08:22 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 |
November | 5656.01 | 01-NOV-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 |
December | 2558.34 | 29-DEC-13:10 | 7248.86 | 5282.70 | 8579.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2558.34 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | |
Maximum of Months | 16247.48 | 7248.86 | 5282.70 | 8579.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14189.97 | 01-JAN-12:53 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.49 |
February | 14910.33 | 12-FEB-13:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.27 |
March | 14408.37 | 12-MAR-13:52 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.06 |
April | 12196.92 | 30-APR-12:53 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.72 |
May | 9494.46 | 21-MAY-13:52 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 | 0.00 |
June | 13384.69 | 25-JUN-16:31 | 669.60 | 515.04 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 265.25 | 0.00 |
July | 14238.75 | 30-JUL-14:01 | 468.72 | 360.53 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 117.39 | 0.00 |
August | 14659.89 | 13-AUG-13:42 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | 0.00 |
September | 15869.27 | 03-SEP-13:41 | 535.68 | 412.03 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 73.42 | 0.00 |
October | 16554.33 | 01-OCT-11:41 | 535.68 | 412.03 | 4015.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 |
November | 14956.33 | 19-NOV-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.03 |
December | 14395.39 | 31-DEC-13:42 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9494.46 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16554.33 | 669.60 | 515.04 | 5019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 265.25 | 330.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4666.29 | 26-JAN-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.44 |
February | 7012.74 | 15-FEB-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.28 |
March | 12381.66 | 12-MAR-15:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.09 |
April | 12072.33 | 09-APR-17:02 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 |
May | 15984.01 | 29-MAY-16:41 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 |
June | 17207.60 | 25-JUN-17:11 | 0.00 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 88.12 | 0.00 |
July | 17512.15 | 04-JUL-16:51 | 423.88 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 | 0.00 |
August | 17030.66 | 20-AUG-16:01 | 423.88 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 71.14 | 0.00 |
September | 15720.47 | 04-SEP-17:31 | 0.00 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.28 |
October | 15277.45 | 01-OCT-15:01 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 0.00 |
November | 6176.42 | 02-NOV-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 |
December | 3720.67 | 29-DEC-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3720.67 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17512.15 | 805.38 | 586.93 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 | 153.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.135073E+12 | 166366.49 | 17-JAN-07:10 | 0.207348E+11 | 54743.11 | 21-JAN-07:10 |
February | 0.116806E+12 | 157997.40 | 06-FEB-07:10 | 0.148419E+11 | 51089.30 | 04-FEB-07:19 |
March | 0.126799E+12 | 108930.40 | 08-MAR-16:10 | 0.112654E+11 | 32030.14 | 04-MAR-07:19 |
April | 0.123985E+12 | 136401.50 | 13-APR-15:20 | 0.905380E+10 | 18312.46 | 08-APR-06:30 |
May | 0.141549E+12 | 151825.31 | 19-MAY-15:09 | 0.897740E+10 | 9180.76 | 06-MAY-06:30 |
June | 0.170557E+12 | 187736.23 | 28-JUN-14:50 | 0.845142E+10 | 9016.04 | 01-JUN-11:50 |
July | 0.183697E+12 | 185548.26 | 21-JUL-14:50 | 0.808715E+10 | 8909.77 | 03-JUL-11:30 |
August | 0.186819E+12 | 177731.43 | 07-AUG-15:39 | 0.847727E+10 | 8881.18 | 30-AUG-11:20 |
September | 0.151307E+12 | 156574.80 | 05-SEP-14:39 | 0.803792E+10 | 8955.37 | 29-SEP-11:30 |
October | 0.134393E+12 | 140487.83 | 02-OCT-15:09 | 0.953261E+10 | 34477.16 | 27-OCT-06:00 |
November | 0.119086E+12 | 115081.76 | 27-NOV-07:10 | 0.108465E+11 | 43395.95 | 27-NOV-07:19 |
December | 0.132057E+12 | 156617.71 | 26-DEC-07:10 | 0.197545E+11 | 54017.28 | 15-DEC-07:40 |
Annual Sum or Average | 0.172213E+13 | 0.138061E+12 | ||||
Minimum of Months | 0.116806E+12 | 108930.40 | 0.803792E+10 | 8881.18 | ||
Maximum of Months | 0.186819E+12 | 187736.23 | 0.207348E+11 | 54743.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.304603E+11 | 0.113608E+11 | 0.641572E+11 | 0.159046E+10 | 0.662780E+10 | 1312252.65 | 0.207140E+11 | 0.160641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274669E+11 | 0.957842E+10 | 0.580684E+11 | 0.143925E+10 | 0.627333E+10 | 1186778.30 | 0.130693E+11 | 0.909153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323564E+11 | 0.961812E+10 | 0.666107E+11 | 0.166684E+10 | 0.809068E+10 | 1343621.24 | 0.566186E+10 | 0.279290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287440E+11 | 0.829745E+10 | 0.619407E+11 | 0.153131E+10 | 0.108483E+11 | 1267813.82 | 0.136393E+10 | 0.112581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309544E+11 | 0.771966E+10 | 0.653840E+11 | 0.162827E+10 | 0.136536E+11 | 1327936.95 | 0.653812E+09 | 0.215543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.307149E+11 | 0.705802E+10 | 0.641577E+11 | 0.160318E+10 | 0.197509E+11 | 1296568.36 | 98121690.92 | 0.471727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.288136E+11 | 0.747913E+10 | 0.631525E+11 | 0.155599E+10 | 0.221679E+11 | 1299182.41 | 0.00 | 0.605263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.321149E+11 | 0.818535E+10 | 0.666107E+11 | 0.166666E+10 | 0.221586E+11 | 1343621.24 | 5986895.69 | 0.560754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288464E+11 | 0.888173E+10 | 0.619118E+11 | 0.153080E+10 | 0.153897E+11 | 1267813.82 | 68647837.63 | 0.346772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.301617E+11 | 0.102024E+11 | 0.641717E+11 | 0.159045E+10 | 0.112755E+11 | 1312252.65 | 0.228116E+10 | 0.147090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.301352E+11 | 0.107565E+11 | 0.627379E+11 | 0.156162E+10 | 0.765703E+10 | 1278270.02 | 0.564283E+10 | 0.593246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297505E+11 | 0.116047E+11 | 0.631380E+11 | 0.155672E+10 | 0.662156E+10 | 1299182.41 | 0.193839E+11 | 91896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360519E+12 | 0.110742E+12 | 0.762041E+12 | 0.189215E+11 | 0.150515E+12 | 15535293.87 | 0.689436E+11 | 0.250429E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274669E+11 | 0.705802E+10 | 0.580684E+11 | 0.143925E+10 | 0.627333E+10 | 1186778.30 | 0.00 | 91896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.323564E+11 | 0.116047E+11 | 0.666107E+11 | 0.166684E+10 | 0.221679E+11 | 1343621.24 | 0.207140E+11 | 0.605263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.111809E+11 | 0.00 | 0.955388E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.614356E+10 | 0.00 | 0.869830E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140265E+10 | 0.00 | 0.986279E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199041E+09 | 0.00 | 0.885476E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 6514269.88 | 0.00 | 0.897088E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.845142E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.808715E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.847727E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.803792E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.925898E+09 | 0.00 | 0.860671E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.208515E+10 | 0.00 | 0.876134E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.105726E+11 | 0.00 | 0.918189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.325163E+11 | 0.00 | 0.105544E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.803792E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.111809E+11 | 0.00 | 0.986279E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 34354.59 | 04-JAN-16:00 | 8467.87 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 1353.80 | 04-JAN-16:00 | 8157.47 | 26-JAN-16:30 | 0.73 | 02-JAN-08:09 | 118547.60 | 17-JAN-07:10 |
February | 33468.91 | 16-FEB-08:09 | 8467.87 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 1355.14 | 16-FEB-08:20 | 13581.50 | 15-FEB-16:30 | 0.73 | 01-FEB-07:10 | 119707.51 | 06-FEB-07:10 |
March | 31997.32 | 20-MAR-07:10 | 8467.87 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 1352.06 | 20-MAR-07:19 | 11967.94 | 24-MAR-15:39 | 0.73 | 03-MAR-08:09 | 60654.29 | 06-MAR-07:10 |
April | 30486.53 | 03-APR-07:10 | 8467.87 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 1348.89 | 03-APR-07:30 | 22696.29 | 13-APR-15:20 | 0.73 | 06-APR-07:10 | 26250.89 | 06-APR-06:10 |
May | 30486.53 | 01-MAY-07:10 | 8467.87 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 1348.89 | 01-MAY-07:30 | 26087.41 | 30-MAY-14:30 | 0.73 | 01-MAY-05:10 | 21907.06 | 05-MAY-06:10 |
June | 30689.35 | 08-JUN-07:10 | 8467.87 | 01-JUN-19:10 | 47562.27 | 01-JUN-07:10 | 1349.32 | 08-JUN-07:19 | 35650.41 | 26-JUN-15:30 | 0.73 | 11-JUN-16:00 | 14203.70 | 09-JUN-06:10 |
July | 30486.53 | 03-JUL-07:10 | 8467.87 | 01-JUL-19:19 | 47562.27 | 03-JUL-07:10 | 1348.89 | 03-JUL-07:19 | 35160.29 | 05-JUL-15:09 | 0.73 | 02-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 30486.53 | 01-AUG-07:10 | 8467.87 | 01-AUG-05:10 | 47562.27 | 01-AUG-07:10 | 1348.89 | 01-AUG-07:19 | 33376.22 | 07-AUG-15:39 | 0.73 | 13-AUG-16:30 | 1983.10 | 31-AUG-06:10 |
September | 33307.74 | 08-SEP-07:10 | 8467.87 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 1354.81 | 08-SEP-07:19 | 26629.74 | 01-SEP-15:00 | 0.73 | 01-SEP-05:10 | 4475.00 | 25-SEP-06:19 |
October | 33181.71 | 25-OCT-07:10 | 8467.87 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 1354.54 | 25-OCT-07:19 | 21806.38 | 02-OCT-15:00 | 0.73 | 25-OCT-07:10 | 59487.81 | 26-OCT-06:10 |
November | 36137.71 | 13-NOV-16:00 | 8467.87 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 1357.89 | 29-NOV-16:00 | 14570.61 | 02-NOV-15:00 | 0.73 | 14-NOV-17:10 | 76584.68 | 27-NOV-07:10 |
December | 36137.71 | 01-DEC-16:00 | 8467.87 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 1358.60 | 05-DEC-16:00 | 7610.82 | 29-DEC-16:10 | 0.73 | 04-DEC-07:10 | 108980.82 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30486.53 | 8467.87 | 47562.27 | 1348.89 | 7610.82 | 0.73 | 0.00 | |||||||
Maximum of Months | 36137.71 | 8467.87 | 47562.27 | 1358.60 | 35650.41 | 0.73 | 119707.51 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 5921.31 | 05-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21455.96 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21657.76 | 08-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38587.68 | 13-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50334.01 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81946.00 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79523.09 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69631.50 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62758.45 | 05-SEP-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48110.58 | 02-OCT-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12154.38 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 153.16 | 24-DEC-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 153.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81946.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 166366.49 | 17-JAN-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 5079.94 | 0.73 | 118547.60 | 0.00 | 0.00 |
February | 157997.40 | 06-FEB-07:10 | 10970.80 | 21853.28 | 0.00 | 371.32 | 5093.77 | 0.73 | 119707.51 | 0.00 | 0.00 |
March | 108930.40 | 08-MAR-16:10 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 11668.66 | 0.73 | 0.00 | 21657.76 | 0.00 |
April | 136401.50 | 13-APR-15:20 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 22696.29 | 0.73 | 0.00 | 38101.22 | 0.00 |
May | 151825.31 | 19-MAY-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 26025.62 | 0.73 | 0.00 | 50195.70 | 0.00 |
June | 187736.23 | 28-JUN-14:50 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 32594.34 | 0.73 | 0.00 | 81022.68 | 0.00 |
July | 185548.26 | 21-JUL-14:50 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 31905.96 | 0.73 | 0.00 | 79523.09 | 0.00 |
August | 177731.43 | 07-AUG-15:39 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 33376.22 | 0.73 | 0.00 | 68751.23 | 0.00 |
September | 156574.80 | 05-SEP-14:39 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 23914.77 | 0.73 | 0.00 | 58540.81 | 0.00 |
October | 140487.83 | 02-OCT-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 17827.46 | 0.73 | 0.00 | 47056.39 | 0.00 |
November | 115081.76 | 27-NOV-07:10 | 11720.40 | 21853.28 | 0.00 | 371.32 | 4551.35 | 0.73 | 76584.68 | 0.00 | 0.00 |
December | 156617.71 | 26-DEC-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4897.94 | 0.73 | 108980.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 108930.40 | 10970.80 | 21853.28 | 0.00 | 371.32 | 4551.35 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 187736.23 | 30486.53 | 43769.98 | 8467.87 | 1346.75 | 33376.22 | 0.73 | 119707.51 | 81022.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 46824.88 | 21-JAN-07:10 | 0.00 | 9403.51 | 26-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 43145.00 | 04-FEB-07:19 | 0.00 | 9408.62 | 08-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 24102.25 | 04-MAR-07:19 | 0.00 | 9385.87 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 11924.37 | 08-APR-06:10 | 0.00 | 9283.22 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 1923.23 | 06-MAY-06:10 | 0.00 | 9153.61 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9016.04 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8909.77 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8881.18 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8955.37 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 27954.99 | 26-OCT-06:00 | 0.00 | 9084.86 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 35279.51 | 27-NOV-07:19 | 0.00 | 9231.40 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 47183.45 | 15-DEC-07:19 | 0.00 | 9344.32 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8881.18 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 47183.45 | 0.00 | 9408.62 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.40 | 0.17 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
February | 1.50 | 16.03 | 0.17 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 0.67 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.62 | 2.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.46 | 1.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 1.33 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
Annual Sum or Average | 5.50 | 16.50 | 0.33 | 16.66 | 7.67 | 22.85 | 5.00 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 17.07 | 0.17 | 17.07 | 3.83 | 27.62 | 2.67 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 1.33 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.26 | 1.17 | 28.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.20 | 4.67 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.20 | 6.67 | 28.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 28.31 | 14.17 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.26 | 8.67 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.09 | 3.17 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.06 | 0.83 | 28.06 |
November | 0.33 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
December | 1.33 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Annual Sum or Average | 5.17 | 16.29 | 0.00 | 16.29 | 40.00 | 26.88 | 39.33 | 27.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 17.08 | 0.00 | 17.08 | 14.50 | 28.31 | 14.17 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 16.38 | 0.00 | 16.38 | 2.50 | 25.13 | 2.50 | 26.16 |
February | 0.50 | 16.19 | 0.00 | 16.19 | 1.67 | 25.12 | 1.67 | 26.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.68 | 1.67 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.45 | 1.83 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.85 | 5.83 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.01 | 5.67 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.02 | 10.00 | 27.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.64 | 11.50 | 26.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 3.33 | 27.73 |
December | 0.50 | 16.96 | 0.00 | 16.96 | 1.00 | 24.31 | 1.00 | 25.78 |
Annual Sum or Average | 1.67 | 16.50 | 0.00 | 16.50 | 47.67 | 26.98 | 46.00 | 27.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.31 | 0.33 | 25.78 |
Maximum of Months | 0.67 | 16.96 | 0.00 | 16.96 | 11.67 | 28.01 | 11.50 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 1.17 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.33 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.17 | 1.67 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.42 | 2.33 | 28.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 29.01 | 3.00 | 29.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.78 | 4.67 | 28.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.72 | 3.00 | 28.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.23 | 3.33 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.02 | 2.17 | 28.04 |
November | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
December | 1.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
Annual Sum or Average | 4.33 | 16.25 | 0.00 | 16.25 | 31.67 | 27.09 | 20.50 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 | 15.70 |
Maximum of Months | 2.00 | 17.06 | 0.00 | 17.06 | 7.67 | 29.01 | 4.67 | 29.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.69 | 1.00 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.70 | 3.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.96 | 4.00 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.98 | 12.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.95 | 8.00 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.87 | 2.83 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.83 | 27.91 | 32.50 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.98 | 12.50 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.33 | 17.49 | 39.33 | 17.49 | 1.83 | 17.72 | 1.83 | 17.94 |
February | 28.83 | 17.93 | 28.83 | 17.93 | 1.17 | 18.12 | 1.17 | 18.30 |
March | 25.67 | 18.71 | 25.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 10.00 | 19.24 | 10.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
May | 3.00 | 19.63 | 3.00 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 25.19 | 18.50 | 25.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 25.36 | 24.17 | 25.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 25.49 | 25.50 | 25.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.94 | 19.67 | 25.94 |
October | 9.50 | 18.73 | 9.50 | 18.73 | 25.33 | 22.72 | 25.00 | 23.80 |
November | 17.00 | 18.91 | 17.00 | 18.91 | 4.00 | 19.82 | 4.00 | 20.56 |
December | 34.33 | 17.61 | 34.33 | 17.61 | 2.33 | 17.94 | 2.33 | 18.25 |
Annual Sum or Average | 167.67 | 18.13 | 167.67 | 18.13 | 122.67 | 20.16 | 122.17 | 21.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 | 17.94 |
Maximum of Months | 39.33 | 19.63 | 39.33 | 19.63 | 25.67 | 25.94 | 25.50 | 25.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.72 | 0.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.91 | 1.17 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.37 | 2.17 | 28.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.28 | 3.67 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.25 | 2.17 | 28.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.81 | 2.83 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.80 | 2.00 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.17 | 28.12 | 14.50 | 28.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.37 | 3.67 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
February | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.00 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.33 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.20 | 0.00 | 17.20 | 2.33 | 26.21 | 1.33 | 26.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.22 | 0.00 | 17.22 | 1.83 | 27.53 | 1.33 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
February | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.41 | 1.17 | 28.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.23 | 5.33 | 28.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.37 | 5.00 | 28.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.40 | 11.50 | 28.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.24 | 7.67 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.15 | 3.00 | 28.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.85 | 1.50 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.18 | 0.00 | 17.18 | 35.50 | 28.18 | 35.50 | 28.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.18 | 0.00 | 17.18 | 11.50 | 28.41 | 11.50 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.83 | 4.83 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.96 | 2.17 | 27.96 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.77 | 2.00 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.70 | 4.50 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.81 | 5.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.61 | 13.33 | 26.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 25.82 | 24.83 | 25.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.88 | 8.00 | 26.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.96 | 3.00 | 27.96 |
Annual Sum or Average | 0.00 | 0.00 | 69.50 | 26.76 | 68.83 | 26.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.96 | 24.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
February | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.33 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.04 | 2.17 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.35 | 2.17 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.80 | 2.67 | 28.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.66 | 4.17 | 28.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.50 | 3.00 | 28.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.16 | 3.17 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.05 | 2.67 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.19 | 0.00 | 17.19 | 29.83 | 28.31 | 20.33 | 28.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.19 | 0.00 | 17.19 | 6.67 | 28.80 | 4.17 | 28.85 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.50 | 23.71 | 0.00 | 23.71 | 0.00 | 23.71 |
February | 405.33 | 23.82 | 0.00 | 23.82 | 0.00 | 23.82 |
March | 356.50 | 23.92 | 3.67 | 23.94 | 0.00 | 23.94 |
April | 198.17 | 23.99 | 27.00 | 24.24 | 0.00 | 24.24 |
May | 80.83 | 24.00 | 128.00 | 24.53 | 0.00 | 24.53 |
June | 0.00 | 0.00 | 315.50 | 24.45 | 0.00 | 24.45 |
July | 5.50 | 24.08 | 484.50 | 24.39 | 5.50 | 24.38 |
August | 2.83 | 24.30 | 506.50 | 24.36 | 2.83 | 24.36 |
September | 0.00 | 0.00 | 396.50 | 24.47 | 0.00 | 24.47 |
October | 113.17 | 23.96 | 149.67 | 24.41 | 0.00 | 24.41 |
November | 316.83 | 23.93 | 9.50 | 23.99 | 0.00 | 23.99 |
December | 489.00 | 23.80 | 0.00 | 23.80 | 0.00 | 23.80 |
Annual Sum or Average | 2461.67 | 23.85 | 2020.83 | 24.14 | 8.33 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.71 | 0.00 | 23.71 |
Maximum of Months | 493.50 | 24.30 | 506.50 | 24.53 | 5.50 | 24.53 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.64 | 8.67 | 22.61 | 8.67 | 22.58 |
February | 454.00 | 23.03 | 3.00 | 23.01 | 3.00 | 23.00 |
March | 504.50 | 23.58 | 0.00 | 23.58 | 0.00 | 23.58 |
April | 356.67 | 23.88 | 2.33 | 23.89 | 0.00 | 23.89 |
May | 167.00 | 23.90 | 81.67 | 24.12 | 0.00 | 24.12 |
June | 15.83 | 23.89 | 274.50 | 24.36 | 0.00 | 24.36 |
July | 9.00 | 24.20 | 477.83 | 24.35 | 9.00 | 24.34 |
August | 4.17 | 24.05 | 495.50 | 24.31 | 4.17 | 24.30 |
September | 2.33 | 24.00 | 334.83 | 24.41 | 1.67 | 24.41 |
October | 241.33 | 23.73 | 95.83 | 23.94 | 0.00 | 23.94 |
November | 451.00 | 23.43 | 0.00 | 23.43 | 0.00 | 23.43 |
December | 497.00 | 22.70 | 4.33 | 22.68 | 4.33 | 22.67 |
Annual Sum or Average | 3204.83 | 23.26 | 1778.50 | 23.65 | 30.83 | 23.64 |
Minimum of Months | 2.33 | 22.64 | 0.00 | 22.61 | 0.00 | 22.58 |
Maximum of Months | 504.50 | 24.20 | 495.50 | 24.41 | 9.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.65 | 158.67 | 21.36 | 158.67 | 21.19 |
February | 454.00 | 22.12 | 78.83 | 21.89 | 78.83 | 21.71 |
March | 509.50 | 22.95 | 11.83 | 22.90 | 11.83 | 22.85 |
April | 386.33 | 23.59 | 0.50 | 23.59 | 0.00 | 23.59 |
May | 207.83 | 23.66 | 59.00 | 23.82 | 0.00 | 23.82 |
June | 38.50 | 23.65 | 264.50 | 24.25 | 0.00 | 24.25 |
July | 7.33 | 24.00 | 482.33 | 24.32 | 7.33 | 24.32 |
August | 5.00 | 23.89 | 491.00 | 24.28 | 5.00 | 24.27 |
September | 37.00 | 23.59 | 271.50 | 24.24 | 2.00 | 24.24 |
October | 322.33 | 23.25 | 75.33 | 23.42 | 2.33 | 23.41 |
November | 473.33 | 22.56 | 34.50 | 22.43 | 34.50 | 22.32 |
December | 497.00 | 21.62 | 164.00 | 21.35 | 164.00 | 21.18 |
Annual Sum or Average | 3440.17 | 22.57 | 2092.00 | 22.92 | 464.50 | 22.74 |
Minimum of Months | 5.00 | 21.62 | 0.50 | 21.35 | 0.00 | 21.18 |
Maximum of Months | 509.50 | 24.00 | 491.00 | 24.32 | 164.00 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 385.67 | 20.27 | 385.67 | 20.23 |
February | 454.00 | 20.79 | 256.83 | 20.59 | 256.83 | 20.50 |
March | 513.17 | 21.66 | 141.67 | 21.40 | 141.67 | 21.23 |
April | 401.33 | 22.64 | 37.33 | 22.47 | 37.00 | 22.33 |
May | 256.17 | 22.99 | 76.83 | 23.25 | 5.83 | 23.21 |
June | 63.17 | 23.19 | 307.50 | 24.16 | 1.83 | 24.17 |
July | 33.67 | 25.15 | 472.33 | 24.44 | 30.83 | 24.49 |
August | 34.83 | 23.93 | 450.83 | 24.25 | 16.50 | 24.27 |
September | 144.00 | 23.02 | 239.00 | 23.76 | 5.00 | 23.76 |
October | 406.17 | 22.14 | 113.17 | 22.17 | 59.83 | 22.01 |
November | 489.00 | 21.05 | 229.17 | 20.80 | 229.17 | 20.67 |
December | 497.00 | 20.33 | 427.00 | 20.26 | 427.00 | 20.24 |
Annual Sum or Average | 3794.50 | 21.51 | 3137.33 | 21.87 | 1597.17 | 21.60 |
Minimum of Months | 33.67 | 20.33 | 37.33 | 20.26 | 1.83 | 20.23 |
Maximum of Months | 513.17 | 25.15 | 472.33 | 24.44 | 427.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 291.33 | 20.58 | 291.33 | 20.49 |
February | 444.00 | 21.12 | 168.50 | 20.85 | 168.50 | 20.70 |
March | 436.50 | 21.85 | 88.83 | 21.70 | 77.50 | 21.53 |
April | 239.67 | 22.61 | 102.67 | 23.03 | 21.33 | 22.94 |
May | 196.50 | 23.09 | 195.17 | 23.80 | 20.83 | 23.91 |
June | 70.83 | 23.98 | 368.83 | 24.36 | 20.83 | 24.48 |
July | 82.67 | 25.93 | 456.00 | 24.76 | 72.67 | 24.95 |
August | 66.83 | 25.05 | 450.50 | 24.47 | 42.67 | 24.61 |
September | 134.17 | 23.14 | 313.00 | 23.95 | 17.17 | 24.04 |
October | 315.50 | 22.20 | 152.00 | 22.60 | 42.17 | 22.47 |
November | 478.50 | 21.47 | 135.83 | 21.24 | 133.00 | 21.08 |
December | 497.00 | 20.60 | 303.83 | 20.42 | 303.83 | 20.35 |
Annual Sum or Average | 3464.17 | 21.78 | 3026.50 | 22.35 | 1211.83 | 22.16 |
Minimum of Months | 66.83 | 20.60 | 88.83 | 20.42 | 17.17 | 20.35 |
Maximum of Months | 502.00 | 25.93 | 456.00 | 24.76 | 303.83 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 364.83 | 21.18 | 256.50 | 21.30 | 192.50 | 21.05 |
February | 302.83 | 21.38 | 183.00 | 21.51 | 123.00 | 21.27 |
March | 359.17 | 21.90 | 136.17 | 21.95 | 84.17 | 21.74 |
April | 277.83 | 22.52 | 86.50 | 22.72 | 30.50 | 22.56 |
May | 251.33 | 22.80 | 112.50 | 23.26 | 9.33 | 23.20 |
June | 107.00 | 23.01 | 278.67 | 23.99 | 4.33 | 24.02 |
July | 61.17 | 25.03 | 440.17 | 24.48 | 45.17 | 24.58 |
August | 66.67 | 24.46 | 441.17 | 24.36 | 32.83 | 24.46 |
September | 131.17 | 23.73 | 317.83 | 24.24 | 34.33 | 24.39 |
October | 233.17 | 22.66 | 232.00 | 23.39 | 50.33 | 23.37 |
November | 308.00 | 21.76 | 162.00 | 22.17 | 68.00 | 21.95 |
December | 344.67 | 21.13 | 232.50 | 21.15 | 180.00 | 20.90 |
Annual Sum or Average | 2807.83 | 22.10 | 2879.00 | 22.79 | 854.50 | 22.59 |
Minimum of Months | 61.17 | 21.13 | 86.50 | 21.15 | 4.33 | 20.90 |
Maximum of Months | 364.83 | 25.03 | 441.17 | 24.48 | 192.50 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.33 | 20.71 | 314.67 | 20.48 | 314.67 | 20.38 |
February | 413.17 | 20.95 | 209.33 | 20.74 | 203.50 | 20.61 |
March | 440.67 | 21.37 | 154.17 | 21.35 | 122.17 | 21.19 |
April | 342.17 | 22.18 | 114.83 | 22.45 | 44.50 | 22.36 |
May | 294.17 | 22.49 | 139.33 | 23.04 | 18.00 | 23.07 |
June | 153.17 | 22.95 | 285.67 | 23.92 | 16.17 | 24.03 |
July | 90.50 | 23.85 | 403.83 | 24.24 | 36.50 | 24.34 |
August | 97.67 | 23.29 | 393.50 | 24.07 | 24.33 | 24.15 |
September | 197.17 | 22.72 | 227.17 | 23.56 | 17.67 | 23.66 |
October | 362.00 | 21.85 | 144.83 | 22.16 | 60.67 | 22.06 |
November | 447.17 | 21.10 | 179.67 | 20.89 | 173.67 | 20.75 |
December | 491.50 | 20.71 | 335.83 | 20.49 | 335.83 | 20.39 |
Annual Sum or Average | 3817.67 | 21.57 | 2902.83 | 22.00 | 1367.67 | 21.79 |
Minimum of Months | 90.50 | 20.71 | 114.83 | 20.48 | 16.17 | 20.38 |
Maximum of Months | 491.50 | 23.85 | 403.83 | 24.24 | 335.83 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 343.67 | 20.67 | 343.67 | 20.63 |
February | 454.00 | 21.01 | 236.50 | 20.87 | 236.50 | 20.79 |
March | 514.00 | 21.69 | 97.33 | 21.52 | 97.33 | 21.40 |
April | 474.33 | 22.92 | 13.67 | 22.86 | 13.67 | 22.81 |
May | 329.17 | 23.39 | 33.83 | 23.47 | 0.00 | 23.47 |
June | 56.17 | 23.52 | 266.00 | 24.19 | 0.00 | 24.19 |
July | 17.17 | 24.45 | 485.33 | 24.36 | 17.17 | 24.36 |
August | 11.67 | 24.13 | 483.33 | 24.27 | 9.83 | 24.27 |
September | 51.67 | 23.47 | 292.33 | 24.16 | 2.50 | 24.16 |
October | 365.50 | 22.90 | 70.67 | 23.07 | 4.00 | 23.05 |
November | 489.00 | 21.91 | 61.50 | 21.78 | 61.50 | 21.67 |
December | 497.00 | 20.85 | 340.67 | 20.75 | 340.67 | 20.71 |
Annual Sum or Average | 3761.67 | 21.90 | 2724.83 | 22.28 | 1126.83 | 22.04 |
Minimum of Months | 11.67 | 20.79 | 13.67 | 20.67 | 0.00 | 20.63 |
Maximum of Months | 514.00 | 24.45 | 485.33 | 24.36 | 343.67 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.28 | 182.17 | 21.10 | 182.17 | 20.99 |
February | 449.50 | 21.50 | 108.67 | 21.31 | 108.67 | 21.17 |
March | 460.83 | 22.25 | 37.00 | 22.20 | 29.83 | 22.11 |
April | 232.00 | 23.09 | 66.17 | 23.55 | 2.00 | 23.55 |
May | 159.83 | 23.37 | 177.17 | 24.06 | 7.67 | 24.12 |
June | 41.00 | 24.26 | 386.50 | 24.45 | 12.50 | 24.52 |
July | 63.00 | 26.40 | 486.67 | 24.77 | 63.00 | 24.94 |
August | 40.33 | 26.33 | 498.67 | 24.57 | 38.17 | 24.69 |
September | 45.33 | 24.26 | 387.17 | 24.39 | 14.50 | 24.47 |
October | 230.67 | 22.91 | 161.00 | 23.56 | 4.00 | 23.56 |
November | 452.00 | 22.36 | 17.83 | 22.34 | 11.67 | 22.30 |
December | 497.00 | 21.30 | 176.67 | 21.12 | 176.67 | 21.02 |
Annual Sum or Average | 3173.50 | 22.21 | 2685.67 | 22.93 | 650.83 | 22.82 |
Minimum of Months | 40.33 | 21.28 | 17.83 | 21.10 | 2.00 | 20.99 |
Maximum of Months | 502.00 | 26.40 | 498.67 | 24.77 | 182.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.50 | 21.35 | 140.00 | 21.34 | 99.33 | 21.03 |
February | 354.17 | 21.62 | 85.83 | 21.64 | 51.67 | 21.37 |
March | 415.00 | 21.90 | 64.17 | 21.83 | 46.17 | 21.62 |
April | 333.50 | 22.60 | 32.67 | 22.65 | 14.83 | 22.54 |
May | 310.33 | 22.71 | 52.00 | 22.94 | 4.67 | 22.91 |
June | 121.67 | 22.84 | 215.67 | 23.87 | 0.00 | 23.87 |
July | 31.67 | 24.44 | 457.33 | 24.44 | 26.17 | 24.46 |
August | 46.50 | 24.21 | 474.50 | 24.41 | 29.00 | 24.47 |
September | 72.67 | 24.14 | 393.50 | 24.52 | 33.33 | 24.64 |
October | 161.83 | 22.70 | 265.67 | 23.93 | 26.50 | 23.97 |
November | 289.67 | 22.37 | 94.50 | 22.88 | 14.50 | 22.77 |
December | 369.17 | 21.54 | 102.00 | 21.51 | 70.50 | 21.21 |
Annual Sum or Average | 2894.67 | 22.17 | 2377.83 | 22.98 | 416.67 | 22.84 |
Minimum of Months | 31.67 | 21.35 | 32.67 | 21.34 | 0.00 | 21.03 |
Maximum of Months | 415.00 | 24.44 | 474.50 | 24.52 | 99.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.67 | 21.19 | 217.00 | 21.01 | 217.00 | 20.91 |
February | 432.33 | 21.42 | 116.17 | 21.24 | 116.17 | 21.13 |
March | 463.83 | 21.79 | 55.67 | 21.72 | 49.50 | 21.62 |
April | 343.33 | 22.76 | 41.17 | 22.98 | 1.33 | 22.98 |
May | 264.17 | 22.92 | 107.00 | 23.40 | 2.33 | 23.42 |
June | 92.33 | 23.28 | 317.17 | 24.17 | 8.67 | 24.23 |
July | 34.00 | 25.37 | 470.33 | 24.42 | 31.83 | 24.49 |
August | 22.83 | 25.18 | 481.33 | 24.35 | 18.83 | 24.40 |
September | 63.00 | 23.73 | 347.83 | 24.32 | 13.50 | 24.38 |
October | 275.50 | 22.71 | 121.17 | 23.22 | 7.33 | 23.23 |
November | 442.83 | 22.03 | 26.33 | 22.00 | 20.00 | 21.94 |
December | 494.17 | 21.29 | 207.33 | 21.11 | 207.33 | 21.01 |
Annual Sum or Average | 3426.00 | 22.01 | 2508.50 | 22.63 | 693.83 | 22.48 |
Minimum of Months | 22.83 | 21.19 | 26.33 | 21.01 | 1.33 | 20.91 |
Maximum of Months | 497.67 | 25.37 | 481.33 | 24.42 | 217.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 295.33 | 20.68 | 295.33 | 20.61 |
February | 454.00 | 21.27 | 152.17 | 21.06 | 152.17 | 20.94 |
March | 513.17 | 22.23 | 54.50 | 22.07 | 54.50 | 21.94 |
April | 395.50 | 23.17 | 2.67 | 23.17 | 1.50 | 23.16 |
May | 206.83 | 23.41 | 80.67 | 23.69 | 0.00 | 23.69 |
June | 26.67 | 23.41 | 325.67 | 24.31 | 0.17 | 24.31 |
July | 22.33 | 24.86 | 488.83 | 24.44 | 22.33 | 24.46 |
August | 14.50 | 24.32 | 484.33 | 24.29 | 11.67 | 24.30 |
September | 72.00 | 23.35 | 282.33 | 24.09 | 3.17 | 24.08 |
October | 364.33 | 22.66 | 78.00 | 22.82 | 12.83 | 22.76 |
November | 488.83 | 21.72 | 99.33 | 21.51 | 99.33 | 21.36 |
December | 497.00 | 20.78 | 325.00 | 20.65 | 325.00 | 20.60 |
Annual Sum or Average | 3557.17 | 21.91 | 2668.83 | 22.37 | 978.00 | 22.13 |
Minimum of Months | 14.50 | 20.78 | 2.67 | 20.65 | 0.00 | 20.60 |
Maximum of Months | 513.17 | 24.86 | 488.83 | 24.44 | 325.00 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.67 | 21.11 | 191.83 | 20.91 | 191.83 | 20.80 |
February | 369.17 | 21.36 | 101.33 | 21.18 | 98.67 | 21.04 |
March | 373.50 | 22.03 | 51.17 | 22.02 | 34.00 | 21.90 |
April | 217.00 | 22.86 | 80.83 | 23.38 | 7.67 | 23.38 |
May | 177.50 | 23.35 | 154.33 | 24.01 | 18.50 | 24.17 |
June | 60.33 | 24.11 | 296.17 | 24.48 | 16.83 | 24.60 |
July | 64.50 | 26.26 | 389.33 | 24.86 | 61.17 | 25.05 |
August | 49.33 | 25.42 | 376.00 | 24.58 | 34.17 | 24.72 |
September | 104.00 | 23.36 | 255.83 | 24.12 | 15.00 | 24.21 |
October | 264.83 | 22.44 | 113.67 | 22.96 | 17.00 | 22.92 |
November | 385.00 | 21.67 | 52.67 | 21.62 | 43.00 | 21.50 |
December | 420.33 | 20.98 | 216.67 | 20.79 | 216.67 | 20.70 |
Annual Sum or Average | 2912.17 | 22.03 | 2279.83 | 22.67 | 754.50 | 22.55 |
Minimum of Months | 49.33 | 20.98 | 51.17 | 20.79 | 7.67 | 20.70 |
Maximum of Months | 426.67 | 26.26 | 389.33 | 24.86 | 216.67 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 345.17 | 21.69 | 180.17 | 21.95 | 106.00 | 21.73 |
February | 286.00 | 21.92 | 129.50 | 22.23 | 60.33 | 22.05 |
March | 337.67 | 22.44 | 76.00 | 22.63 | 24.50 | 22.53 |
April | 250.50 | 23.00 | 51.33 | 23.32 | 1.50 | 23.30 |
May | 205.83 | 23.18 | 107.67 | 23.66 | 0.00 | 23.66 |
June | 73.00 | 23.25 | 288.33 | 24.14 | 0.83 | 24.15 |
July | 37.50 | 25.68 | 469.33 | 24.51 | 37.33 | 24.59 |
August | 37.17 | 25.61 | 471.00 | 24.45 | 31.17 | 24.54 |
September | 89.83 | 24.47 | 354.17 | 24.49 | 35.00 | 24.64 |
October | 197.67 | 23.24 | 231.67 | 24.01 | 27.67 | 24.12 |
November | 282.33 | 22.44 | 140.33 | 23.00 | 34.17 | 22.92 |
December | 323.67 | 21.71 | 175.50 | 21.89 | 108.33 | 21.66 |
Annual Sum or Average | 2466.33 | 22.56 | 2675.00 | 23.34 | 466.83 | 23.25 |
Minimum of Months | 37.17 | 21.69 | 51.33 | 21.89 | 0.00 | 21.66 |
Maximum of Months | 345.17 | 25.68 | 471.00 | 24.51 | 108.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.50 | 21.05 | 231.50 | 20.85 | 231.50 | 20.74 |
February | 406.83 | 21.29 | 126.50 | 21.14 | 120.33 | 21.01 |
March | 436.00 | 21.75 | 84.17 | 21.79 | 53.33 | 21.67 |
April | 326.50 | 22.58 | 76.17 | 22.93 | 9.67 | 22.95 |
May | 262.17 | 22.87 | 136.83 | 23.41 | 9.17 | 23.47 |
June | 122.83 | 23.26 | 306.50 | 24.10 | 14.67 | 24.19 |
July | 57.50 | 24.59 | 430.00 | 24.37 | 36.50 | 24.45 |
August | 59.67 | 23.83 | 424.33 | 24.22 | 22.00 | 24.28 |
September | 145.83 | 23.11 | 264.50 | 23.91 | 17.17 | 24.00 |
October | 342.00 | 22.28 | 115.00 | 22.71 | 20.83 | 22.71 |
November | 436.83 | 21.51 | 85.17 | 21.39 | 77.33 | 21.26 |
December | 486.33 | 21.09 | 249.17 | 20.88 | 249.17 | 20.78 |
Annual Sum or Average | 3565.00 | 21.88 | 2529.83 | 22.43 | 861.67 | 22.28 |
Minimum of Months | 57.50 | 21.05 | 76.17 | 20.85 | 9.17 | 20.74 |
Maximum of Months | 486.33 | 24.59 | 430.00 | 24.37 | 249.17 | 24.45 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73261 | 15.87013 | 0.08341 | 5.40852 |
February | 454.00000 | 23.89920 | 16.59243 | 0.13819 | 5.62737 |
March | 514.00000 | 24.11359 | 15.93086 | 0.20778 | 6.04900 |
April | 485.00000 | 24.32754 | 13.76861 | 0.26875 | 6.70396 |
May | 508.00000 | 24.30269 | 21.50285 | -0.5261 | 11.26883 |
June | 496.00000 | 24.31488 | 31.67020 | -0.4224 | 9.14869 |
July | 497.00000 | 24.38032 | 41.85225 | -0.3201 | 7.53669 |
August | 514.00000 | 24.35084 | 41.49947 | -0.3282 | 7.64801 |
September | 485.00000 | 24.39110 | 36.15803 | -0.3692 | 8.37494 |
October | 502.00000 | 24.32634 | 22.42667 | 0.34185 | 7.81188 |
November | 489.00000 | 24.17190 | 16.53497 | 0.22957 | 6.28519 |
December | 497.00000 | 23.81775 | 13.97360 | 0.09554 | 5.39897 |
Annual Sum or Average | 5943.00000 | 24.17896 | 24.05426 | -0.0523 | 7.28753 |
Minimum of Months | 454.00000 | 23.73261 | 13.76861 | -0.5261 | 5.39897 |
Maximum of Months | 514.00000 | 24.39110 | 41.85225 | 0.34185 | 11.26883 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64001 | 17.99100 | -0.1802 | 6.48385 |
February | 454.00000 | 23.03008 | 18.71284 | -0.0767 | 5.85979 |
March | 514.00000 | 23.59585 | 17.50582 | 0.07001 | 5.53376 |
April | 485.00000 | 24.02920 | 14.59247 | 0.18199 | 5.92359 |
May | 508.00000 | 24.15356 | 22.22952 | -0.6027 | 13.11546 |
June | 496.00000 | 24.24571 | 32.49767 | -0.4684 | 9.92949 |
July | 497.00000 | 24.33751 | 42.90648 | -0.3532 | 7.91803 |
August | 514.00000 | 24.29747 | 42.54661 | -0.3689 | 8.13903 |
September | 485.00000 | 24.29542 | 36.87989 | -0.4326 | 9.30827 |
October | 502.00000 | 24.02377 | 23.51637 | 0.24634 | 6.80318 |
November | 489.00000 | 23.48924 | 18.41977 | 0.04750 | 5.55944 |
December | 497.00000 | 22.70126 | 16.10209 | -0.1768 | 6.36728 |
Annual Sum or Average | 5943.00000 | 23.74152 | 25.39279 | -0.1776 | 7.59747 |
Minimum of Months | 454.00000 | 22.64001 | 14.59247 | -0.6027 | 5.53376 |
Maximum of Months | 514.00000 | 24.33751 | 42.90648 | 0.24634 | 13.11546 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.64843 | 18.72850 | -0.4267 | 10.34913 |
February | 454.00000 | 22.12130 | 19.37696 | -0.2979 | 8.43074 |
March | 514.00000 | 22.95942 | 18.12010 | -0.0841 | 6.26724 |
April | 485.00000 | 23.71806 | 14.77747 | 0.10569 | 5.83203 |
May | 508.00000 | 23.98459 | 22.11456 | -0.6588 | 14.95533 |
June | 496.00000 | 24.18753 | 32.47289 | -0.4768 | 10.19390 |
July | 497.00000 | 24.32055 | 43.04106 | -0.3411 | 7.76230 |
August | 514.00000 | 24.26896 | 42.76713 | -0.3661 | 8.09559 |
September | 485.00000 | 24.16515 | 36.75235 | -0.4797 | 10.26810 |
October | 502.00000 | 23.57102 | 23.96087 | 0.13014 | 6.55258 |
November | 489.00000 | 22.60589 | 19.51730 | -0.1694 | 6.98384 |
December | 497.00000 | 21.61930 | 16.79143 | -0.4449 | 10.59305 |
Annual Sum or Average | 5943.00000 | 23.27268 | 25.76757 | -0.2930 | 8.86664 |
Minimum of Months | 454.00000 | 21.61930 | 14.77747 | -0.6588 | 5.83203 |
Maximum of Months | 514.00000 | 24.32055 | 43.04106 | 0.13014 | 14.95533 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40065 | 19.36225 | -0.7555 | 18.82300 |
February | 454.00000 | 20.78655 | 20.46329 | -0.6295 | 15.06309 |
March | 514.00000 | 21.66736 | 19.35680 | -0.3791 | 9.89134 |
April | 485.00000 | 22.89489 | 15.64024 | -0.0683 | 6.96361 |
May | 508.00000 | 23.56846 | 22.99437 | -0.7642 | 19.63815 |
June | 496.00000 | 24.12242 | 32.65213 | -0.4403 | 10.26839 |
July | 497.00000 | 24.35196 | 43.26201 | -0.2679 | 7.37007 |
August | 514.00000 | 24.17825 | 43.18244 | -0.3492 | 8.36775 |
September | 485.00000 | 23.80999 | 37.90925 | -0.5716 | 13.51488 |
October | 502.00000 | 22.50088 | 25.49464 | -0.1125 | 8.00065 |
November | 489.00000 | 21.04882 | 20.39802 | -0.5390 | 12.86582 |
December | 497.00000 | 20.32904 | 17.60275 | -0.7900 | 19.75582 |
Annual Sum or Average | 5943.00000 | 22.48477 | 26.59030 | -0.4715 | 12.52963 |
Minimum of Months | 454.00000 | 20.32904 | 15.64024 | -0.7900 | 6.96361 |
Maximum of Months | 514.00000 | 24.35196 | 43.26201 | -0.0683 | 19.75582 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77276 | 18.50409 | -0.6285 | 15.06500 |
February | 454.00000 | 21.18712 | 19.56000 | -0.4863 | 12.40994 |
March | 514.00000 | 22.20356 | 18.26116 | -0.1963 | 8.59615 |
April | 485.00000 | 23.44760 | 14.48024 | 0.14979 | 7.93778 |
May | 508.00000 | 23.78045 | 22.13949 | -0.5669 | 16.06225 |
June | 496.00000 | 24.17732 | 32.33563 | -0.2869 | 9.29529 |
July | 497.00000 | 24.43977 | 42.76642 | -0.1083 | 8.00304 |
August | 514.00000 | 24.22734 | 42.73155 | -0.1977 | 8.12547 |
September | 485.00000 | 23.85722 | 37.32140 | -0.4316 | 11.89502 |
October | 502.00000 | 22.94457 | 24.40910 | 0.05566 | 8.50723 |
November | 489.00000 | 21.52335 | 19.41849 | -0.3821 | 10.09178 |
December | 497.00000 | 20.59591 | 16.91904 | -0.6788 | 16.41395 |
Annual Sum or Average | 5943.00000 | 22.77527 | 25.80201 | -0.3123 | 11.02497 |
Minimum of Months | 454.00000 | 20.59591 | 14.48024 | -0.6788 | 7.93778 |
Maximum of Months | 514.00000 | 24.43977 | 42.76642 | 0.14979 | 16.41395 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.09796 | 17.07211 | -0.2657 | 12.88825 |
February | 454.00000 | 22.35421 | 18.09765 | -0.1701 | 11.39506 |
March | 514.00000 | 22.60682 | 17.73122 | -0.0955 | 9.09669 |
April | 485.00000 | 23.25911 | 14.71496 | 0.07059 | 7.77126 |
May | 508.00000 | 23.53590 | 22.76151 | -0.7375 | 19.81566 |
June | 496.00000 | 23.95963 | 32.88945 | -0.4838 | 11.91597 |
July | 497.00000 | 24.28914 | 43.32871 | -0.2637 | 7.99844 |
August | 514.00000 | 24.19346 | 42.88902 | -0.2753 | 8.36244 |
September | 485.00000 | 24.05067 | 36.81024 | -0.3698 | 11.51005 |
October | 502.00000 | 23.52657 | 23.37792 | 0.22902 | 10.49735 |
November | 489.00000 | 22.75995 | 17.89251 | -0.0452 | 10.08126 |
December | 497.00000 | 22.11653 | 15.36298 | -0.2584 | 13.13512 |
Annual Sum or Average | 5943.00000 | 23.23513 | 25.31819 | -0.2234 | 11.21456 |
Minimum of Months | 454.00000 | 22.09796 | 14.71496 | -0.7375 | 7.77126 |
Maximum of Months | 514.00000 | 24.28914 | 43.32871 | 0.22902 | 19.81566 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79702 | 18.34244 | -0.6296 | 16.55294 |
February | 454.00000 | 21.22700 | 19.37117 | -0.4826 | 13.53420 |
March | 514.00000 | 21.78130 | 18.58129 | -0.2993 | 10.14130 |
April | 485.00000 | 22.78370 | 15.17301 | -0.0161 | 8.39610 |
May | 508.00000 | 23.19861 | 23.17161 | -0.7722 | 22.52960 |
June | 496.00000 | 23.77802 | 33.26325 | -0.4490 | 13.45153 |
July | 497.00000 | 24.05354 | 43.94053 | -0.2662 | 9.36145 |
August | 514.00000 | 23.92055 | 43.68449 | -0.3227 | 9.94760 |
September | 485.00000 | 23.50021 | 38.23945 | -0.5542 | 15.71528 |
October | 502.00000 | 22.48076 | 25.02885 | -0.0459 | 9.02583 |
November | 489.00000 | 21.35781 | 19.46117 | -0.4230 | 11.78285 |
December | 497.00000 | 20.74561 | 16.61459 | -0.6560 | 17.09711 |
Annual Sum or Average | 5943.00000 | 22.47836 | 26.30973 | -0.4097 | 13.13032 |
Minimum of Months | 454.00000 | 20.74561 | 15.17301 | -0.7722 | 8.39610 |
Maximum of Months | 514.00000 | 24.05354 | 43.94053 | -0.0161 | 22.52960 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79101 | 19.47979 | -0.6391 | 14.24688 |
February | 454.00000 | 21.01497 | 20.60718 | -0.5690 | 12.53884 |
March | 514.00000 | 21.68615 | 19.76833 | -0.3850 | 8.98122 |
April | 485.00000 | 22.94122 | 16.31290 | -0.0850 | 6.13782 |
May | 508.00000 | 23.64336 | 23.62741 | -0.7867 | 19.35008 |
June | 496.00000 | 24.14591 | 32.50432 | -0.4806 | 10.37297 |
July | 497.00000 | 24.34855 | 42.49763 | -0.3140 | 7.47282 |
August | 514.00000 | 24.25053 | 42.28073 | -0.3589 | 8.03747 |
September | 485.00000 | 24.12735 | 37.50153 | -0.4805 | 10.42084 |
October | 502.00000 | 23.22736 | 24.89467 | 0.05974 | 6.60096 |
November | 489.00000 | 21.91436 | 19.84935 | -0.3178 | 8.07562 |
December | 497.00000 | 20.85030 | 17.45552 | -0.6259 | 13.73848 |
Annual Sum or Average | 5943.00000 | 22.75700 | 26.46017 | -0.4150 | 10.50019 |
Minimum of Months | 454.00000 | 20.79101 | 16.31290 | -0.7867 | 6.13782 |
Maximum of Months | 514.00000 | 24.34855 | 42.49763 | 0.05974 | 19.35008 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.28113 | 18.29260 | -0.4812 | 10.83957 |
February | 454.00000 | 21.53408 | 19.38199 | -0.3956 | 9.63491 |
March | 514.00000 | 22.47192 | 18.24540 | -0.1452 | 7.17757 |
April | 485.00000 | 23.76466 | 14.56247 | 0.19474 | 7.13551 |
May | 508.00000 | 24.02369 | 22.22594 | -0.5311 | 13.36804 |
June | 496.00000 | 24.30312 | 31.85705 | -0.2915 | 8.21695 |
July | 497.00000 | 24.54762 | 41.62537 | -0.1162 | 7.00251 |
August | 514.00000 | 24.39326 | 41.51211 | -0.1740 | 6.98908 |
September | 485.00000 | 24.24858 | 36.71273 | -0.3139 | 8.46363 |
October | 502.00000 | 23.66593 | 23.56652 | 0.23146 | 8.04673 |
November | 489.00000 | 22.50968 | 18.52639 | -0.1314 | 6.63325 |
December | 497.00000 | 21.29781 | 16.37914 | -0.4757 | 10.55841 |
Annual Sum or Average | 5943.00000 | 23.18119 | 25.30305 | -0.2187 | 8.67246 |
Minimum of Months | 454.00000 | 21.28113 | 14.56247 | -0.5311 | 6.63325 |
Maximum of Months | 514.00000 | 24.54762 | 41.62537 | 0.23146 | 13.36804 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12780 | 16.40396 | -0.1892 | 10.47520 |
February | 454.00000 | 22.28396 | 17.62440 | -0.1400 | 9.29177 |
March | 514.00000 | 22.39706 | 17.65406 | -0.1246 | 7.97180 |
April | 485.00000 | 23.15144 | 14.81311 | 0.03405 | 6.89348 |
May | 508.00000 | 23.30306 | 22.98191 | -0.8411 | 22.48735 |
June | 496.00000 | 23.91551 | 31.96432 | -0.5513 | 12.93755 |
July | 497.00000 | 24.36174 | 42.28124 | -0.2896 | 7.64753 |
August | 514.00000 | 24.30925 | 41.82578 | -0.2675 | 7.74782 |
September | 485.00000 | 24.32449 | 36.11459 | -0.2770 | 9.01673 |
October | 502.00000 | 23.92918 | 22.50832 | 0.35419 | 10.87333 |
November | 489.00000 | 23.24390 | 16.91612 | 0.12429 | 8.04050 |
December | 497.00000 | 22.32156 | 14.23444 | -0.1373 | 9.65654 |
Annual Sum or Average | 5943.00000 | 23.31117 | 24.68407 | -0.1939 | 10.28172 |
Minimum of Months | 454.00000 | 22.12780 | 14.23444 | -0.8411 | 6.89348 |
Maximum of Months | 514.00000 | 24.36174 | 42.28124 | 0.35419 | 22.48735 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21269 | 18.25549 | -0.4978 | 11.53665 |
February | 454.00000 | 21.54958 | 19.25985 | -0.3926 | 9.98227 |
March | 514.00000 | 22.04100 | 18.59565 | -0.2493 | 8.06649 |
April | 485.00000 | 23.22630 | 15.21049 | 0.05431 | 6.69201 |
May | 508.00000 | 23.57628 | 23.20260 | -0.7036 | 18.04608 |
June | 496.00000 | 24.06412 | 32.53518 | -0.4097 | 10.55149 |
July | 497.00000 | 24.29760 | 42.47961 | -0.2394 | 7.48262 |
August | 514.00000 | 24.25405 | 42.06699 | -0.2539 | 7.43354 |
September | 485.00000 | 24.16150 | 37.06167 | -0.3621 | 9.30478 |
October | 502.00000 | 23.38530 | 23.95136 | 0.16620 | 7.75844 |
November | 489.00000 | 22.22320 | 18.67371 | -0.1938 | 7.24801 |
December | 497.00000 | 21.30229 | 16.26030 | -0.4784 | 11.08593 |
Annual Sum or Average | 5943.00000 | 22.95024 | 25.69644 | -0.2970 | 9.61086 |
Minimum of Months | 454.00000 | 21.21269 | 15.21049 | -0.7036 | 6.69201 |
Maximum of Months | 514.00000 | 24.29760 | 42.47961 | 0.16620 | 18.04608 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84699 | 19.18743 | -0.6078 | 13.75094 |
February | 454.00000 | 21.26802 | 20.29297 | -0.4836 | 11.05619 |
March | 514.00000 | 22.22945 | 19.06783 | -0.2344 | 7.47342 |
April | 485.00000 | 23.35270 | 15.50717 | 0.03775 | 6.03757 |
May | 508.00000 | 23.86437 | 22.95286 | -0.6734 | 15.84473 |
June | 496.00000 | 24.23160 | 32.49186 | -0.4194 | 9.34509 |
July | 497.00000 | 24.41450 | 42.93934 | -0.2686 | 7.14609 |
August | 514.00000 | 24.26537 | 42.74384 | -0.3371 | 7.85404 |
September | 485.00000 | 24.07030 | 37.70471 | -0.4911 | 10.86791 |
October | 502.00000 | 23.05097 | 25.07302 | 0.02379 | 6.87217 |
November | 489.00000 | 21.71853 | 19.88974 | -0.3574 | 8.95734 |
December | 497.00000 | 20.77568 | 17.43361 | -0.6371 | 14.30560 |
Annual Sum or Average | 5943.00000 | 22.85257 | 26.33656 | -0.3704 | 9.95721 |
Minimum of Months | 454.00000 | 20.77568 | 15.50717 | -0.6734 | 6.03757 |
Maximum of Months | 514.00000 | 24.41450 | 42.93934 | 0.03775 | 15.84473 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.11003 | 17.73871 | -0.5203 | 12.03797 |
February | 385.00000 | 21.49449 | 18.84598 | -0.3947 | 10.17065 |
March | 433.00000 | 22.35291 | 17.70883 | -0.1511 | 7.67245 |
April | 410.00000 | 23.58244 | 14.29815 | 0.17259 | 7.62687 |
May | 430.00000 | 23.90304 | 22.28405 | -0.5463 | 15.24927 |
June | 418.00000 | 24.25853 | 31.81347 | -0.3015 | 9.32478 |
July | 422.00000 | 24.53221 | 42.02114 | -0.1294 | 8.23686 |
August | 433.00000 | 24.30477 | 42.00084 | -0.2195 | 8.30141 |
September | 410.00000 | 23.99205 | 37.02713 | -0.4151 | 11.18368 |
October | 427.00000 | 23.15689 | 23.78386 | 0.10717 | 8.11115 |
November | 417.00000 | 21.88867 | 18.63663 | -0.2755 | 8.38247 |
December | 422.00000 | 20.99094 | 16.14564 | -0.5565 | 12.71778 |
Annual Sum or Average | 5034.00000 | 22.97227 | 25.24464 | -0.2689 | 9.92087 |
Minimum of Months | 385.00000 | 20.99094 | 14.29815 | -0.5565 | 7.62687 |
Maximum of Months | 433.00000 | 24.53221 | 42.02114 | 0.17259 | 15.24927 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.58531 | 16.64064 | -0.1177 | 10.37398 |
February | 454.00000 | 22.82209 | 17.69243 | -0.0344 | 9.31063 |
March | 514.00000 | 23.05331 | 17.31001 | 0.02242 | 7.63785 |
April | 485.00000 | 23.61861 | 14.54292 | 0.15504 | 7.05602 |
May | 508.00000 | 23.82627 | 22.71245 | -0.6496 | 15.96493 |
June | 496.00000 | 24.10068 | 32.66739 | -0.4546 | 10.45621 |
July | 497.00000 | 24.37570 | 42.92181 | -0.2593 | 7.47120 |
August | 514.00000 | 24.29320 | 42.39231 | -0.2627 | 7.64597 |
September | 485.00000 | 24.27317 | 36.64684 | -0.3041 | 9.36512 |
October | 502.00000 | 23.92044 | 22.98164 | 0.32984 | 10.36053 |
November | 489.00000 | 23.29424 | 17.24246 | 0.10216 | 8.79755 |
December | 497.00000 | 22.62896 | 14.88527 | -0.1029 | 10.16650 |
Annual Sum or Average | 5943.00000 | 23.57069 | 24.96036 | -0.1330 | 9.56087 |
Minimum of Months | 454.00000 | 22.58531 | 14.54292 | -0.6496 | 7.05602 |
Maximum of Months | 514.00000 | 24.37570 | 42.92181 | 0.32984 | 15.96493 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16992 | 18.03342 | -0.4988 | 12.36204 |
February | 454.00000 | 21.58494 | 19.13902 | -0.3629 | 10.37328 |
March | 514.00000 | 22.13194 | 18.31255 | -0.1962 | 8.22581 |
April | 485.00000 | 23.14050 | 15.03278 | 0.06916 | 7.46460 |
May | 508.00000 | 23.51198 | 23.10524 | -0.6785 | 18.27028 |
June | 496.00000 | 23.94835 | 32.99161 | -0.4138 | 11.54426 |
July | 497.00000 | 24.17300 | 43.44377 | -0.2540 | 8.42436 |
August | 514.00000 | 24.05894 | 43.12772 | -0.3000 | 8.79412 |
September | 485.00000 | 23.78273 | 37.98195 | -0.4709 | 12.51482 |
October | 502.00000 | 22.87016 | 24.63744 | 0.05754 | 8.08664 |
November | 489.00000 | 21.78781 | 18.97276 | -0.2893 | 8.89690 |
December | 497.00000 | 21.15564 | 16.27183 | -0.5141 | 12.55238 |
Annual Sum or Average | 5943.00000 | 22.78523 | 25.99023 | -0.3213 | 10.63373 |
Minimum of Months | 454.00000 | 21.15564 | 15.03278 | -0.6785 | 7.46460 |
Maximum of Months | 514.00000 | 24.17300 | 43.44377 | 0.06916 | 18.27028 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 98836999.47 | 28507411.28 | 12.01 | 98836999.47 | 0.00 | 0.00 | 0.35 | 01-JAN-14:43 | 0.00 | 01-JAN-00:10 | 10549.78 | 01-JAN-14:43 | 10549.78 | 01-JAN-14:43 | 0.00 | 05-JAN-14:10 | 2872.68 | 01-JAN-14:43 | 0.00 |
February | 0.114979E+10 | 0.292281E+09 | 25.83 | 0.114966E+10 | 127934.57 | 0.00 | 0.92 | 14-FEB-16:10 | 0.00 | 01-FEB-00:10 | 32016.00 | 14-FEB-16:10 | 32016.00 | 14-FEB-16:10 | 37.14 | 19-FEB-13:44 | 7488.50 | 14-FEB-16:10 | 0.00 |
March | 0.359451E+10 | 0.957129E+09 | 111.46 | 0.359410E+10 | 413401.30 | 0.00 | 0.92 | 08-MAR-16:10 | 0.00 | 01-MAR-00:10 | 31926.93 | 08-MAR-16:10 | 31926.93 | 08-MAR-16:10 | 114.63 | 07-MAR-18:40 | 7472.04 | 08-MAR-16:10 | 0.00 |
April | 0.154815E+11 | 0.382669E+10 | 221.31 | 0.154752E+11 | 6260282.49 | 0.00 | 1.00 | 11-APR-13:00 | 0.00 | 01-APR-00:10 | 53164.52 | 28-APR-15:10 | 53164.52 | 28-APR-15:10 | 578.35 | 14-APR-20:00 | 12577.51 | 13-APR-16:00 | 0.00 |
May | 0.293848E+11 | 0.731818E+10 | 329.56 | 0.288549E+11 | 0.529960E+09 | 0.00 | 1.00 | 08-MAY-12:00 | 0.00 | 01-MAY-00:10 | 61774.90 | 19-MAY-16:00 | 61774.90 | 19-MAY-16:00 | 7795.16 | 24-MAY-14:50 | 16539.73 | 19-MAY-16:00 | 0.00 |
June | 0.592521E+11 | 0.161022E+11 | 432.26 | 0.579310E+11 | 0.132113E+10 | 0.00 | 1.00 | 02-JUN-13:50 | 0.00 | 01-JUN-00:10 | 78834.03 | 28-JUN-15:50 | 78834.03 | 28-JUN-15:50 | 11703.39 | 24-JUN-04:02 | 27520.79 | 28-JUN-15:50 | 0.00 |
July | 0.779301E+11 | 0.209195E+11 | 470.28 | 0.697733E+11 | 0.815682E+10 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 81599.18 | 31-JUL-15:20 | 78361.03 | 21-JUL-15:50 | 38653.13 | 01-JUL-04:02 | 26101.13 | 21-JUL-15:50 | 0.00 |
August | 0.762462E+11 | 0.196608E+11 | 481.26 | 0.677247E+11 | 0.852148E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 87723.42 | 23-AUG-15:10 | 75253.74 | 07-AUG-16:00 | 41764.42 | 14-AUG-04:02 | 23066.41 | 01-AUG-16:00 | 0.00 |
September | 0.503784E+11 | 0.124579E+11 | 406.82 | 0.463701E+11 | 0.400828E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 97236.17 | 05-SEP-13:00 | 65739.07 | 13-SEP-16:00 | 41159.02 | 05-SEP-13:00 | 22376.63 | 05-SEP-13:00 | 0.00 |
October | 0.220029E+11 | 0.537916E+10 | 249.79 | 0.209753E+11 | 0.102767E+10 | 0.00 | 1.00 | 01-OCT-11:01 | 0.00 | 01-OCT-00:10 | 66428.57 | 02-OCT-15:10 | 63596.46 | 06-OCT-16:00 | 12157.96 | 02-OCT-17:00 | 16240.83 | 02-OCT-15:10 | 0.00 |
November | 0.743411E+09 | 0.207019E+09 | 39.31 | 0.725100E+09 | 18311861.27 | 0.00 | 0.51 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 15727.54 | 02-NOV-15:00 | 15727.54 | 02-NOV-15:00 | 858.03 | 01-NOV-12:10 | 4119.45 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.336263E+12 | 0.871494E+11 | 2779.90 | 0.312672E+12 | 0.235904E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.779301E+11 | 0.209195E+11 | 481.26 | 0.697733E+11 | 0.852148E+10 | 0.00 | 1.00 | 0.00 | 97236.17 | 78834.03 | 41764.42 | 27520.79 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.321501E+09 | 90540023.75 | 22.13 | 0.321484E+09 | 16940.55 | 0.00 | 0.39 | 01-JAN-14:53 | 0.00 | 01-JAN-00:10 | 10498.53 | 01-JAN-14:53 | 10498.53 | 01-JAN-14:53 | 17.52 | 05-JAN-12:30 | 2832.32 | 01-JAN-14:53 | 0.00 |
February | 0.125008E+10 | 0.317596E+09 | 29.83 | 0.125008E+10 | 5732.26 | 0.00 | 0.96 | 14-FEB-15:40 | 0.00 | 01-FEB-00:10 | 30163.97 | 14-FEB-15:40 | 30163.97 | 14-FEB-15:40 | 18.64 | 19-FEB-13:15 | 6972.98 | 14-FEB-15:40 | 0.00 |
March | 0.349871E+10 | 0.926112E+09 | 115.28 | 0.349802E+10 | 681018.96 | 0.00 | 0.95 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 29844.95 | 08-MAR-16:00 | 29844.95 | 08-MAR-16:00 | 139.58 | 20-MAR-12:13 | 6915.28 | 08-MAR-16:00 | 0.00 |
April | 0.146748E+11 | 0.361371E+10 | 227.13 | 0.146685E+11 | 6343856.82 | 0.00 | 1.00 | 11-APR-13:00 | 0.00 | 01-APR-00:10 | 51885.59 | 13-APR-15:20 | 51885.59 | 13-APR-15:20 | 577.57 | 14-APR-20:00 | 12247.03 | 26-APR-15:00 | 0.00 |
May | 0.274150E+11 | 0.680095E+10 | 332.37 | 0.269530E+11 | 0.462004E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 58436.26 | 19-MAY-15:10 | 58436.26 | 19-MAY-15:10 | 6764.11 | 24-MAY-14:40 | 15643.17 | 19-MAY-15:10 | 0.00 |
June | 0.540005E+11 | 0.146633E+11 | 430.25 | 0.529054E+11 | 0.109515E+10 | 0.00 | 1.00 | 01-JUN-13:40 | 0.00 | 01-JUN-00:10 | 79619.76 | 29-JUN-06:03 | 73769.10 | 26-JUN-15:00 | 15271.55 | 29-JUN-06:03 | 25241.97 | 28-JUN-14:50 | 0.00 |
July | 0.697555E+11 | 0.187369E+11 | 462.93 | 0.629075E+11 | 0.684799E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 79782.86 | 31-JUL-15:00 | 73599.04 | 21-JUL-14:50 | 32110.60 | 01-JUL-05:02 | 24895.80 | 21-JUL-14:50 | 0.00 |
August | 0.672488E+11 | 0.173752E+11 | 474.72 | 0.601959E+11 | 0.705291E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 77751.79 | 23-AUG-15:10 | 73880.41 | 07-AUG-15:30 | 37325.44 | 14-AUG-06:03 | 21755.80 | 01-AUG-15:10 | 0.00 |
September | 0.433055E+11 | 0.107329E+11 | 399.11 | 0.399562E+11 | 0.334934E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 86119.84 | 05-SEP-13:30 | 61988.49 | 13-SEP-16:00 | 36263.96 | 05-SEP-13:00 | 19912.59 | 05-SEP-13:30 | 0.00 |
October | 0.188930E+11 | 0.463041E+10 | 243.26 | 0.180596E+11 | 0.833462E+09 | 0.00 | 1.00 | 01-OCT-10:22 | 0.00 | 01-OCT-00:10 | 61833.50 | 02-OCT-14:50 | 58277.63 | 02-OCT-15:00 | 11033.33 | 11-OCT-05:03 | 15320.54 | 02-OCT-15:00 | 0.00 |
November | 0.821339E+09 | 0.228612E+09 | 48.30 | 0.786953E+09 | 34385917.08 | 0.00 | 0.60 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 17152.14 | 02-NOV-15:00 | 17152.14 | 02-NOV-15:00 | 1676.16 | 02-NOV-13:00 | 4379.82 | 02-NOV-15:00 | 0.00 |
December | 316360.06 | 91896.85 | 0.04 | 316360.06 | -0.0 | 0.00 | 0.08 | 24-DEC-14:32 | 0.00 | 01-DEC-00:10 | 2109.07 | 24-DEC-14:32 | 2109.07 | 24-DEC-14:32 | 0.00 | 01-DEC-00:10 | 612.65 | 24-DEC-14:32 | 0.00 |
Annual Sum or Average | 0.301185E+12 | 0.781163E+11 | 2785.34 | 0.281503E+12 | 0.196823E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 316360.06 | 91896.85 | 0.04 | 316360.06 | -0.0 | 0.00 | 0.08 | 0.00 | 2109.07 | 2109.07 | 0.00 | 612.65 | 0.00 | ||||||
Maximum of Months | 0.697555E+11 | 0.187369E+11 | 474.72 | 0.629075E+11 | 0.705291E+10 | 0.00 | 1.00 | 0.00 | 86119.84 | 73880.41 | 37325.44 | 25241.97 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144718E+09 | 41593469.58 | 14.83 | 0.144718E+09 | 0.00 | 0.00 | 0.23 | 05-JAN-14:10 | 0.00 | 01-JAN-00:10 | 6831.85 | 05-JAN-14:10 | 6831.85 | 05-JAN-14:10 | 0.00 | 05-JAN-15:20 | 1919.06 | 05-JAN-14:10 | 0.00 |
February | 0.115807E+10 | 0.299276E+09 | 28.00 | 0.115778E+10 | 283674.42 | 0.00 | 0.83 | 14-FEB-15:50 | 0.00 | 01-FEB-00:10 | 29552.47 | 14-FEB-15:50 | 29552.47 | 14-FEB-15:50 | 53.73 | 19-FEB-13:55 | 7084.54 | 14-FEB-15:50 | 0.00 |
March | 0.338759E+10 | 0.909654E+09 | 111.50 | 0.338496E+10 | 2628035.74 | 0.00 | 0.86 | 08-MAR-16:00 | 0.00 | 01-MAR-00:10 | 30934.72 | 08-MAR-16:00 | 30934.72 | 08-MAR-16:00 | 288.73 | 20-MAR-12:13 | 7350.36 | 08-MAR-16:00 | 0.00 |
April | 0.153654E+11 | 0.381773E+10 | 224.20 | 0.153543E+11 | 11047014.38 | 0.00 | 1.00 | 11-APR-13:20 | 0.00 | 01-APR-00:10 | 59176.14 | 26-APR-15:00 | 59176.14 | 26-APR-15:00 | 963.09 | 14-APR-20:00 | 14096.48 | 26-APR-15:00 | 0.00 |
May | 0.297158E+11 | 0.743515E+10 | 331.38 | 0.291718E+11 | 0.544041E+09 | 0.00 | 1.00 | 08-MAY-12:10 | 0.00 | 01-MAY-00:10 | 68862.24 | 19-MAY-15:20 | 68862.24 | 19-MAY-15:20 | 7026.54 | 24-MAY-13:00 | 18433.77 | 19-MAY-15:20 | 0.00 |
June | 0.598678E+11 | 0.164072E+11 | 425.22 | 0.586509E+11 | 0.121694E+10 | 0.00 | 1.00 | 02-JUN-14:20 | 0.00 | 01-JUN-00:10 | 87714.66 | 28-JUN-14:50 | 87714.66 | 28-JUN-14:50 | 12173.37 | 24-JUN-05:02 | 30057.92 | 28-JUN-14:50 | 0.00 |
July | 0.770489E+11 | 0.208700E+11 | 459.27 | 0.700014E+11 | 0.704751E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 90230.94 | 31-JUL-15:20 | 86915.60 | 21-JUL-15:00 | 34890.40 | 01-JUL-05:02 | 29399.19 | 21-JUL-15:00 | 0.00 |
August | 0.730306E+11 | 0.190394E+11 | 466.40 | 0.660086E+11 | 0.702201E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 86837.93 | 21-AUG-15:10 | 86169.71 | 07-AUG-15:40 | 32896.97 | 23-AUG-16:00 | 25571.12 | 01-AUG-15:10 | 0.00 |
September | 0.459129E+11 | 0.114864E+11 | 392.79 | 0.425703E+11 | 0.334263E+10 | 0.00 | 1.00 | 01-SEP-08:50 | 0.00 | 01-SEP-00:10 | 90079.37 | 05-SEP-13:30 | 71552.65 | 01-SEP-15:30 | 36155.05 | 05-SEP-13:00 | 20837.36 | 05-SEP-13:30 | 0.00 |
October | 0.189676E+11 | 0.469940E+10 | 237.21 | 0.181620E+11 | 0.805664E+09 | 0.00 | 1.00 | 01-OCT-11:52 | 0.00 | 01-OCT-00:10 | 68096.54 | 02-OCT-14:30 | 64780.97 | 02-OCT-15:00 | 10737.98 | 02-OCT-17:00 | 16778.93 | 02-OCT-14:30 | 0.00 |
November | 0.557927E+09 | 0.157615E+09 | 39.33 | 0.520077E+09 | 37849561.45 | 0.00 | 0.43 | 02-NOV-15:00 | 0.00 | 01-NOV-00:10 | 13686.37 | 02-NOV-15:00 | 13574.37 | 02-NOV-15:00 | 1460.90 | 02-NOV-13:30 | 3655.11 | 02-NOV-15:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.325157E+12 | 0.851634E+11 | 2730.13 | 0.305127E+12 | 0.200306E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.770489E+11 | 0.208700E+11 | 466.40 | 0.700014E+11 | 0.704751E+10 | 0.00 | 1.00 | 0.00 | 90230.94 | 87714.66 | 36155.05 | 30057.92 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 471.93 | 0.00 | 471.93 | 143.50 | 1481.29 | 0.00 | 0.00 | 0.00 |
February | 589.84 | 0.00 | 589.84 | 264.04 | 1343.07 | 0.00 | 0.00 | 0.00 |
March | 744.01 | 0.00 | 744.01 | 511.00 | 1059.61 | 0.00 | 0.00 | 0.00 |
April | 943.91 | 8.08 | 935.83 | 790.92 | 716.02 | 0.00 | 0.00 | 0.00 |
May | 1026.04 | 66.15 | 959.89 | 1070.58 | 532.65 | 0.00 | 0.00 | 0.00 |
June | 1165.86 | 190.79 | 975.07 | 1603.54 | 360.69 | 0.00 | 0.00 | 0.00 |
July | 1070.08 | 89.06 | 981.01 | 1581.45 | 248.44 | 0.00 | 0.00 | 0.00 |
August | 992.67 | 22.22 | 970.45 | 1346.70 | 279.33 | 0.00 | 0.00 | 0.00 |
September | 793.83 | 0.20 | 793.63 | 929.52 | 483.34 | 0.00 | 0.00 | 0.00 |
October | 592.36 | 0.00 | 592.36 | 452.71 | 837.43 | 0.00 | 0.00 | 0.00 |
November | 503.05 | 0.00 | 503.05 | 193.15 | 1172.91 | 0.00 | 0.00 | 0.00 |
December | 401.69 | 0.00 | 401.69 | 56.56 | 1540.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.28 | 31.43 | 743.85 | 747.79 | 835.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.69 | 0.00 | 401.69 | 56.56 | 248.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1165.86 | 190.79 | 981.01 | 1603.54 | 1540.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 871.31 | 487.14 | 384.17 | 777.87 | 912.85 | 0.00 | 0.00 | 0.00 |
February | 1058.63 | 570.71 | 487.91 | 1020.10 | 834.81 | 0.00 | 0.00 | 0.00 |
March | 1396.49 | 793.88 | 602.61 | 1493.88 | 664.12 | 0.00 | 0.00 | 0.00 |
April | 1907.89 | 1086.91 | 820.98 | 2216.34 | 468.59 | 0.00 | 0.00 | 0.00 |
May | 1820.53 | 1037.50 | 783.03 | 2227.34 | 358.63 | 0.00 | 0.00 | 0.00 |
June | 1962.67 | 1209.09 | 753.57 | 2627.25 | 236.21 | 0.00 | 0.00 | 0.00 |
July | 1816.09 | 1038.51 | 777.58 | 2529.87 | 164.53 | 0.00 | 0.00 | 0.00 |
August | 1797.15 | 990.80 | 806.35 | 2431.72 | 184.69 | 0.00 | 0.00 | 0.00 |
September | 1495.82 | 836.92 | 658.90 | 1921.90 | 309.15 | 0.00 | 0.00 | 0.00 |
October | 1300.90 | 825.37 | 475.53 | 1487.14 | 525.07 | 0.00 | 0.00 | 0.00 |
November | 1016.72 | 597.72 | 419.00 | 1003.41 | 739.72 | 0.00 | 0.00 | 0.00 |
December | 823.83 | 501.38 | 322.46 | 733.74 | 954.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1440.41 | 832.36 | 608.05 | 1708.93 | 527.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 823.83 | 487.14 | 322.46 | 733.74 | 164.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1962.67 | 1209.09 | 820.98 | 2627.25 | 954.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3488.96 | 2714.89 | 774.07 | 3953.15 | 1388.48 | 0.00 | 0.00 | 0.00 |
February | 3414.43 | 2494.12 | 920.31 | 3944.99 | 1285.33 | 0.00 | 0.00 | 0.00 |
March | 2516.08 | 1521.12 | 994.96 | 2975.65 | 1052.14 | 0.00 | 0.00 | 0.00 |
April | 1962.23 | 805.46 | 1156.77 | 2404.64 | 760.51 | 0.00 | 0.00 | 0.00 |
May | 1308.65 | 287.88 | 1020.77 | 1618.18 | 563.93 | 0.00 | 0.00 | 0.00 |
June | 1107.01 | 136.43 | 970.58 | 1596.29 | 378.07 | 0.00 | 0.00 | 0.00 |
July | 1224.96 | 195.61 | 1029.34 | 1900.72 | 257.05 | 0.00 | 0.00 | 0.00 |
August | 1684.40 | 547.51 | 1136.89 | 2502.93 | 295.90 | 0.00 | 0.00 | 0.00 |
September | 2329.16 | 1298.81 | 1030.36 | 3218.48 | 501.67 | 0.00 | 0.00 | 0.00 |
October | 3186.57 | 2346.89 | 839.68 | 3992.01 | 826.64 | 0.00 | 0.00 | 0.00 |
November | 3549.24 | 2724.03 | 825.21 | 4136.08 | 1128.80 | 0.00 | 0.00 | 0.00 |
December | 3785.42 | 3122.58 | 662.85 | 4310.60 | 1417.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2457.75 | 1511.25 | 946.50 | 3041.03 | 818.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1107.01 | 136.43 | 662.85 | 1596.29 | 257.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3785.42 | 3122.58 | 1156.77 | 4310.60 | 1417.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 898.73 | 512.51 | 386.21 | 867.05 | 971.04 | 0.00 | 0.00 | 0.00 |
February | 1156.96 | 668.34 | 488.62 | 1187.62 | 888.78 | 0.00 | 0.00 | 0.00 |
March | 1292.20 | 687.86 | 604.34 | 1401.84 | 709.43 | 0.00 | 0.00 | 0.00 |
April | 1649.23 | 877.73 | 771.50 | 1908.88 | 501.05 | 0.00 | 0.00 | 0.00 |
May | 1563.71 | 805.73 | 757.98 | 1913.06 | 379.07 | 0.00 | 0.00 | 0.00 |
June | 1676.29 | 935.35 | 740.94 | 2278.91 | 265.43 | 0.00 | 0.00 | 0.00 |
July | 1511.96 | 739.93 | 772.03 | 2144.10 | 177.69 | 0.00 | 0.00 | 0.00 |
August | 1544.96 | 714.60 | 830.35 | 2121.64 | 202.08 | 0.00 | 0.00 | 0.00 |
September | 1395.46 | 734.93 | 660.53 | 1822.26 | 332.67 | 0.00 | 0.00 | 0.00 |
October | 1276.66 | 793.49 | 483.17 | 1502.90 | 565.85 | 0.00 | 0.00 | 0.00 |
November | 1002.17 | 589.60 | 412.57 | 1019.13 | 770.07 | 0.00 | 0.00 | 0.00 |
December | 866.67 | 543.50 | 323.18 | 815.70 | 993.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1319.70 | 716.62 | 603.08 | 1583.24 | 561.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 866.67 | 512.51 | 323.18 | 815.70 | 177.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1676.29 | 935.35 | 830.35 | 2278.91 | 993.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.30 | 0.00 | 157.30 | 45.44 | 519.42 | 0.00 | 0.00 | 0.00 |
February | 196.60 | 0.00 | 196.60 | 88.56 | 462.96 | 0.00 | 0.00 | 0.00 |
March | 247.99 | 0.00 | 247.99 | 175.66 | 358.15 | 0.00 | 0.00 | 0.00 |
April | 314.62 | 2.69 | 311.93 | 270.70 | 240.36 | 0.00 | 0.00 | 0.00 |
May | 342.00 | 22.05 | 319.95 | 363.86 | 177.35 | 0.00 | 0.00 | 0.00 |
June | 388.60 | 63.59 | 325.01 | 540.70 | 119.69 | 0.00 | 0.00 | 0.00 |
July | 356.67 | 29.69 | 326.99 | 532.59 | 81.60 | 0.00 | 0.00 | 0.00 |
August | 330.88 | 7.41 | 323.47 | 451.91 | 94.47 | 0.00 | 0.00 | 0.00 |
September | 264.60 | 0.07 | 264.53 | 308.97 | 170.70 | 0.00 | 0.00 | 0.00 |
October | 197.44 | 0.00 | 197.44 | 145.71 | 303.48 | 0.00 | 0.00 | 0.00 |
November | 167.68 | 0.00 | 167.68 | 57.50 | 427.53 | 0.00 | 0.00 | 0.00 |
December | 133.89 | 0.00 | 133.89 | 16.07 | 550.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.41 | 10.48 | 247.94 | 250.64 | 291.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.89 | 0.00 | 133.89 | 16.07 | 81.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 388.60 | 63.59 | 326.99 | 540.70 | 550.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.31 | 0.00 | 157.31 | 45.44 | 519.45 | 0.00 | 0.00 | 0.00 |
February | 196.62 | 0.00 | 196.62 | 88.57 | 462.99 | 0.00 | 0.00 | 0.00 |
March | 248.01 | 0.00 | 248.01 | 175.67 | 358.18 | 0.00 | 0.00 | 0.00 |
April | 314.64 | 2.69 | 311.95 | 270.71 | 240.37 | 0.00 | 0.00 | 0.00 |
May | 342.02 | 22.05 | 319.97 | 363.89 | 177.36 | 0.00 | 0.00 | 0.00 |
June | 388.63 | 63.60 | 325.03 | 540.73 | 119.70 | 0.00 | 0.00 | 0.00 |
July | 356.70 | 29.69 | 327.01 | 532.62 | 81.60 | 0.00 | 0.00 | 0.00 |
August | 330.90 | 7.41 | 323.49 | 451.94 | 94.48 | 0.00 | 0.00 | 0.00 |
September | 264.61 | 0.07 | 264.55 | 308.99 | 170.71 | 0.00 | 0.00 | 0.00 |
October | 197.46 | 0.00 | 197.46 | 145.72 | 303.50 | 0.00 | 0.00 | 0.00 |
November | 167.69 | 0.00 | 167.69 | 57.50 | 427.55 | 0.00 | 0.00 | 0.00 |
December | 133.90 | 0.00 | 133.90 | 16.07 | 550.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.43 | 10.48 | 247.95 | 250.66 | 291.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.90 | 0.00 | 133.90 | 16.07 | 81.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 388.63 | 63.60 | 327.01 | 540.73 | 550.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 157.31 | 0.00 | 157.31 | 45.44 | 519.45 | 0.00 | 0.00 | 0.00 |
February | 196.62 | 0.00 | 196.62 | 88.57 | 462.99 | 0.00 | 0.00 | 0.00 |
March | 248.01 | 0.00 | 248.01 | 175.67 | 358.18 | 0.00 | 0.00 | 0.00 |
April | 314.64 | 2.69 | 311.95 | 270.71 | 240.37 | 0.00 | 0.00 | 0.00 |
May | 342.02 | 22.05 | 319.97 | 363.89 | 177.36 | 0.00 | 0.00 | 0.00 |
June | 388.63 | 63.60 | 325.03 | 540.73 | 119.70 | 0.00 | 0.00 | 0.00 |
July | 356.70 | 29.69 | 327.01 | 532.62 | 81.60 | 0.00 | 0.00 | 0.00 |
August | 330.90 | 7.41 | 323.49 | 451.94 | 94.48 | 0.00 | 0.00 | 0.00 |
September | 264.61 | 0.07 | 264.55 | 308.99 | 170.71 | 0.00 | 0.00 | 0.00 |
October | 197.46 | 0.00 | 197.46 | 145.72 | 303.50 | 0.00 | 0.00 | 0.00 |
November | 167.69 | 0.00 | 167.69 | 57.50 | 427.55 | 0.00 | 0.00 | 0.00 |
December | 133.90 | 0.00 | 133.90 | 16.07 | 550.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.43 | 10.48 | 247.95 | 250.66 | 291.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 133.90 | 0.00 | 133.90 | 16.07 | 81.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 388.63 | 63.60 | 327.01 | 540.73 | 550.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 838.16 | 468.61 | 369.55 | 738.35 | 938.25 | 0.00 | 0.00 | 0.00 |
February | 1018.35 | 549.00 | 469.35 | 980.78 | 847.42 | 0.00 | 0.00 | 0.00 |
March | 1343.36 | 763.67 | 579.69 | 1444.75 | 669.96 | 0.00 | 0.00 | 0.00 |
April | 1835.30 | 1045.56 | 789.75 | 2141.65 | 476.95 | 0.00 | 0.00 | 0.00 |
May | 1751.27 | 998.03 | 753.24 | 2154.56 | 363.70 | 0.00 | 0.00 | 0.00 |
June | 1888.00 | 1163.09 | 724.91 | 2539.18 | 239.38 | 0.00 | 0.00 | 0.00 |
July | 1747.00 | 999.00 | 748.00 | 2442.92 | 169.02 | 0.00 | 0.00 | 0.00 |
August | 1728.78 | 953.10 | 775.67 | 2346.33 | 193.12 | 0.00 | 0.00 | 0.00 |
September | 1438.92 | 805.08 | 633.83 | 1848.58 | 327.52 | 0.00 | 0.00 | 0.00 |
October | 1251.41 | 793.97 | 457.44 | 1420.92 | 562.00 | 0.00 | 0.00 | 0.00 |
November | 978.04 | 574.98 | 403.06 | 947.11 | 791.68 | 0.00 | 0.00 | 0.00 |
December | 792.49 | 482.30 | 310.19 | 694.54 | 999.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1385.61 | 800.69 | 584.92 | 1644.58 | 546.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 792.49 | 468.61 | 310.19 | 694.54 | 169.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1888.00 | 1163.09 | 789.75 | 2539.18 | 999.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.14 | 18.53 | 14.61 | 29.19 | 37.10 | 0.00 | 0.00 | 0.00 |
February | 40.26 | 21.71 | 18.56 | 38.78 | 33.51 | 0.00 | 0.00 | 0.00 |
March | 53.12 | 30.19 | 22.92 | 57.12 | 26.49 | 0.00 | 0.00 | 0.00 |
April | 72.57 | 41.34 | 31.23 | 84.68 | 18.86 | 0.00 | 0.00 | 0.00 |
May | 69.24 | 39.46 | 29.78 | 85.19 | 14.38 | 0.00 | 0.00 | 0.00 |
June | 74.65 | 45.99 | 28.66 | 100.40 | 9.47 | 0.00 | 0.00 | 0.00 |
July | 69.07 | 39.50 | 29.58 | 96.59 | 6.68 | 0.00 | 0.00 | 0.00 |
August | 68.35 | 37.68 | 30.67 | 92.77 | 7.64 | 0.00 | 0.00 | 0.00 |
September | 56.89 | 31.83 | 25.06 | 73.09 | 12.95 | 0.00 | 0.00 | 0.00 |
October | 49.48 | 31.39 | 18.09 | 56.18 | 22.22 | 0.00 | 0.00 | 0.00 |
November | 38.67 | 22.73 | 15.94 | 37.45 | 31.30 | 0.00 | 0.00 | 0.00 |
December | 31.33 | 19.07 | 12.26 | 27.46 | 39.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.79 | 31.66 | 23.13 | 65.03 | 21.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.33 | 18.53 | 12.26 | 27.46 | 6.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.65 | 45.99 | 31.23 | 100.40 | 39.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1163.02 | 904.99 | 258.03 | 1321.57 | 507.88 | 0.00 | 0.00 | 0.00 |
February | 1138.18 | 831.40 | 306.78 | 1323.37 | 464.12 | 0.00 | 0.00 | 0.00 |
March | 838.72 | 507.06 | 331.66 | 1003.14 | 368.82 | 0.00 | 0.00 | 0.00 |
April | 654.09 | 268.49 | 385.60 | 812.63 | 261.97 | 0.00 | 0.00 | 0.00 |
May | 436.23 | 95.96 | 340.27 | 551.03 | 188.06 | 0.00 | 0.00 | 0.00 |
June | 369.01 | 45.48 | 323.53 | 539.20 | 125.13 | 0.00 | 0.00 | 0.00 |
July | 408.33 | 65.21 | 343.12 | 638.55 | 85.97 | 0.00 | 0.00 | 0.00 |
August | 561.48 | 182.51 | 378.97 | 838.41 | 103.94 | 0.00 | 0.00 | 0.00 |
September | 776.41 | 432.95 | 343.46 | 1075.02 | 184.36 | 0.00 | 0.00 | 0.00 |
October | 1062.22 | 782.32 | 279.90 | 1330.49 | 309.65 | 0.00 | 0.00 | 0.00 |
November | 1183.12 | 908.04 | 275.08 | 1377.57 | 426.67 | 0.00 | 0.00 | 0.00 |
December | 1261.85 | 1040.89 | 220.96 | 1440.45 | 527.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 819.28 | 503.77 | 315.51 | 1019.23 | 295.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 369.01 | 45.48 | 220.96 | 539.20 | 85.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1261.85 | 1040.89 | 385.60 | 1440.45 | 527.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1163.02 | 904.99 | 258.03 | 1321.57 | 507.88 | 0.00 | 0.00 | 0.00 |
February | 1138.18 | 831.40 | 306.78 | 1323.37 | 464.12 | 0.00 | 0.00 | 0.00 |
March | 838.72 | 507.06 | 331.66 | 1003.14 | 368.82 | 0.00 | 0.00 | 0.00 |
April | 654.09 | 268.49 | 385.60 | 812.63 | 261.97 | 0.00 | 0.00 | 0.00 |
May | 436.23 | 95.96 | 340.27 | 551.03 | 188.06 | 0.00 | 0.00 | 0.00 |
June | 369.01 | 45.48 | 323.53 | 539.20 | 125.13 | 0.00 | 0.00 | 0.00 |
July | 408.33 | 65.21 | 343.12 | 638.55 | 85.97 | 0.00 | 0.00 | 0.00 |
August | 561.48 | 182.51 | 378.97 | 838.41 | 103.94 | 0.00 | 0.00 | 0.00 |
September | 776.41 | 432.95 | 343.46 | 1075.02 | 184.36 | 0.00 | 0.00 | 0.00 |
October | 1062.22 | 782.32 | 279.90 | 1330.49 | 309.65 | 0.00 | 0.00 | 0.00 |
November | 1183.12 | 908.04 | 275.08 | 1377.57 | 426.67 | 0.00 | 0.00 | 0.00 |
December | 1261.85 | 1040.89 | 220.96 | 1440.45 | 527.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 819.28 | 503.77 | 315.51 | 1019.23 | 295.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 369.01 | 45.48 | 220.96 | 539.20 | 85.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1261.85 | 1040.89 | 385.60 | 1440.45 | 527.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1162.95 | 904.94 | 258.01 | 1321.48 | 507.85 | 0.00 | 0.00 | 0.00 |
February | 1138.11 | 831.35 | 306.76 | 1323.28 | 464.09 | 0.00 | 0.00 | 0.00 |
March | 838.67 | 507.03 | 331.64 | 1003.08 | 368.80 | 0.00 | 0.00 | 0.00 |
April | 654.05 | 268.48 | 385.58 | 812.58 | 261.95 | 0.00 | 0.00 | 0.00 |
May | 436.20 | 95.96 | 340.24 | 550.99 | 188.04 | 0.00 | 0.00 | 0.00 |
June | 368.99 | 45.47 | 323.51 | 539.17 | 125.13 | 0.00 | 0.00 | 0.00 |
July | 408.30 | 65.20 | 343.10 | 638.51 | 85.96 | 0.00 | 0.00 | 0.00 |
August | 561.45 | 182.50 | 378.95 | 838.35 | 103.94 | 0.00 | 0.00 | 0.00 |
September | 776.36 | 432.92 | 343.44 | 1074.95 | 184.34 | 0.00 | 0.00 | 0.00 |
October | 1062.16 | 782.27 | 279.88 | 1330.41 | 309.63 | 0.00 | 0.00 | 0.00 |
November | 1183.04 | 907.98 | 275.06 | 1377.48 | 426.64 | 0.00 | 0.00 | 0.00 |
December | 1261.77 | 1040.83 | 220.94 | 1440.35 | 527.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 819.22 | 503.74 | 315.49 | 1019.17 | 295.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 368.99 | 45.47 | 220.94 | 539.17 | 85.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1261.77 | 1040.83 | 385.58 | 1440.35 | 527.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 864.54 | 493.02 | 371.52 | 833.69 | 998.76 | 0.00 | 0.00 | 0.00 |
February | 1112.95 | 642.91 | 470.03 | 1148.55 | 904.41 | 0.00 | 0.00 | 0.00 |
March | 1243.04 | 661.69 | 581.35 | 1360.38 | 711.36 | 0.00 | 0.00 | 0.00 |
April | 1586.49 | 844.33 | 742.16 | 1846.75 | 506.47 | 0.00 | 0.00 | 0.00 |
May | 1504.22 | 775.08 | 729.15 | 1850.59 | 378.93 | 0.00 | 0.00 | 0.00 |
June | 1612.52 | 899.77 | 712.76 | 2199.71 | 266.39 | 0.00 | 0.00 | 0.00 |
July | 1454.45 | 711.78 | 742.66 | 2069.38 | 178.70 | 0.00 | 0.00 | 0.00 |
August | 1486.19 | 687.42 | 798.77 | 2043.90 | 208.78 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 706.97 | 635.40 | 1747.59 | 351.99 | 0.00 | 0.00 | 0.00 |
October | 1228.09 | 763.30 | 464.79 | 1436.00 | 603.90 | 0.00 | 0.00 | 0.00 |
November | 964.04 | 567.17 | 396.88 | 969.73 | 821.94 | 0.00 | 0.00 | 0.00 |
December | 833.70 | 522.82 | 310.88 | 782.38 | 1038.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1269.50 | 689.36 | 580.14 | 1525.31 | 579.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 833.70 | 493.02 | 310.88 | 782.38 | 178.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1612.52 | 899.77 | 798.77 | 2199.71 | 1038.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.18 | 19.49 | 14.69 | 32.96 | 39.49 | 0.00 | 0.00 | 0.00 |
February | 44.00 | 25.42 | 18.58 | 45.41 | 35.76 | 0.00 | 0.00 | 0.00 |
March | 49.15 | 26.16 | 22.99 | 53.79 | 28.13 | 0.00 | 0.00 | 0.00 |
April | 62.73 | 33.38 | 29.34 | 73.02 | 20.03 | 0.00 | 0.00 | 0.00 |
May | 59.48 | 30.65 | 28.83 | 73.17 | 14.98 | 0.00 | 0.00 | 0.00 |
June | 63.76 | 35.58 | 28.18 | 86.97 | 10.53 | 0.00 | 0.00 | 0.00 |
July | 57.51 | 28.14 | 29.36 | 81.82 | 7.07 | 0.00 | 0.00 | 0.00 |
August | 58.76 | 27.18 | 31.58 | 80.81 | 8.25 | 0.00 | 0.00 | 0.00 |
September | 53.08 | 27.95 | 25.12 | 69.10 | 13.92 | 0.00 | 0.00 | 0.00 |
October | 48.56 | 30.18 | 18.38 | 56.78 | 23.88 | 0.00 | 0.00 | 0.00 |
November | 38.12 | 22.43 | 15.69 | 38.34 | 32.50 | 0.00 | 0.00 | 0.00 |
December | 32.96 | 20.67 | 12.29 | 30.93 | 41.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.19 | 27.26 | 22.94 | 60.31 | 22.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.96 | 19.49 | 12.29 | 30.93 | 7.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.76 | 35.58 | 31.58 | 86.97 | 41.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 471.93 | 0.00 | 471.93 | 128.10 | 1578.34 | 0.00 | 0.00 | 0.00 |
February | 589.84 | 0.00 | 589.84 | 246.51 | 1429.58 | 0.00 | 0.00 | 0.00 |
March | 744.01 | 0.00 | 744.01 | 491.80 | 1128.38 | 0.00 | 0.00 | 0.00 |
April | 943.91 | 8.08 | 935.83 | 775.67 | 760.71 | 0.00 | 0.00 | 0.00 |
May | 1026.04 | 66.15 | 959.89 | 1060.79 | 558.30 | 0.00 | 0.00 | 0.00 |
June | 1165.86 | 190.79 | 975.07 | 1603.65 | 372.10 | 0.00 | 0.00 | 0.00 |
July | 1070.08 | 89.06 | 981.01 | 1586.07 | 254.46 | 0.00 | 0.00 | 0.00 |
August | 992.67 | 22.22 | 970.45 | 1348.93 | 288.10 | 0.00 | 0.00 | 0.00 |
September | 793.83 | 0.20 | 793.63 | 924.38 | 509.07 | 0.00 | 0.00 | 0.00 |
October | 592.36 | 0.00 | 592.36 | 437.47 | 899.20 | 0.00 | 0.00 | 0.00 |
November | 503.05 | 0.00 | 503.05 | 172.66 | 1268.44 | 0.00 | 0.00 | 0.00 |
December | 401.69 | 0.00 | 401.69 | 47.08 | 1649.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.28 | 31.43 | 743.85 | 737.81 | 888.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.69 | 0.00 | 401.69 | 47.08 | 254.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1165.86 | 190.79 | 981.01 | 1603.65 | 1649.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 871.31 | 487.14 | 384.17 | 760.46 | 967.56 | 0.00 | 0.00 | 0.00 |
February | 1058.63 | 570.71 | 487.91 | 1004.86 | 883.81 | 0.00 | 0.00 | 0.00 |
March | 1396.49 | 793.88 | 602.61 | 1483.92 | 699.76 | 0.00 | 0.00 | 0.00 |
April | 1907.89 | 1086.91 | 820.98 | 2211.97 | 491.30 | 0.00 | 0.00 | 0.00 |
May | 1820.53 | 1037.50 | 783.03 | 2227.07 | 373.50 | 0.00 | 0.00 | 0.00 |
June | 1962.67 | 1209.09 | 753.57 | 2631.53 | 242.96 | 0.00 | 0.00 | 0.00 |
July | 1816.09 | 1038.51 | 777.58 | 2536.13 | 167.90 | 0.00 | 0.00 | 0.00 |
August | 1797.15 | 990.80 | 806.35 | 2436.79 | 189.28 | 0.00 | 0.00 | 0.00 |
September | 1495.82 | 836.92 | 658.90 | 1921.62 | 322.14 | 0.00 | 0.00 | 0.00 |
October | 1300.90 | 825.37 | 475.53 | 1479.66 | 555.77 | 0.00 | 0.00 | 0.00 |
November | 1016.72 | 597.72 | 419.00 | 986.89 | 789.89 | 0.00 | 0.00 | 0.00 |
December | 823.83 | 501.38 | 322.46 | 718.82 | 1017.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1440.41 | 832.36 | 608.05 | 1703.08 | 556.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 823.83 | 487.14 | 322.46 | 718.82 | 167.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1962.67 | 1209.09 | 820.98 | 2631.53 | 1017.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3488.96 | 2714.89 | 774.07 | 3930.10 | 1473.50 | 0.00 | 0.00 | 0.00 |
February | 3414.43 | 2494.12 | 920.31 | 3926.61 | 1363.24 | 0.00 | 0.00 | 0.00 |
March | 2516.08 | 1521.12 | 994.96 | 2961.10 | 1113.50 | 0.00 | 0.00 | 0.00 |
April | 1962.23 | 805.46 | 1156.77 | 2397.09 | 803.95 | 0.00 | 0.00 | 0.00 |
May | 1308.65 | 287.88 | 1020.77 | 1613.08 | 592.36 | 0.00 | 0.00 | 0.00 |
June | 1107.01 | 136.43 | 970.58 | 1597.77 | 392.59 | 0.00 | 0.00 | 0.00 |
July | 1224.96 | 195.61 | 1029.34 | 1906.12 | 264.18 | 0.00 | 0.00 | 0.00 |
August | 1684.40 | 547.51 | 1136.89 | 2507.98 | 305.54 | 0.00 | 0.00 | 0.00 |
September | 2329.16 | 1298.81 | 1030.36 | 3217.89 | 525.26 | 0.00 | 0.00 | 0.00 |
October | 3186.57 | 2346.89 | 839.68 | 3980.06 | 876.29 | 0.00 | 0.00 | 0.00 |
November | 3549.24 | 2724.03 | 825.21 | 4114.53 | 1207.81 | 0.00 | 0.00 | 0.00 |
December | 3785.42 | 3122.58 | 662.85 | 4290.39 | 1511.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2457.75 | 1511.25 | 946.50 | 3031.83 | 866.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1107.01 | 136.43 | 662.85 | 1597.77 | 264.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3785.42 | 3122.58 | 1156.77 | 4290.39 | 1511.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 898.73 | 512.51 | 386.21 | 857.73 | 1031.67 | 0.00 | 0.00 | 0.00 |
February | 1156.96 | 668.34 | 488.62 | 1178.88 | 942.45 | 0.00 | 0.00 | 0.00 |
March | 1292.20 | 687.86 | 604.34 | 1394.18 | 750.00 | 0.00 | 0.00 | 0.00 |
April | 1649.23 | 877.73 | 771.50 | 1903.20 | 528.65 | 0.00 | 0.00 | 0.00 |
May | 1563.71 | 805.73 | 757.98 | 1909.07 | 397.23 | 0.00 | 0.00 | 0.00 |
June | 1676.29 | 935.35 | 740.94 | 2279.95 | 274.49 | 0.00 | 0.00 | 0.00 |
July | 1511.96 | 739.93 | 772.03 | 2147.30 | 182.40 | 0.00 | 0.00 | 0.00 |
August | 1544.96 | 714.60 | 830.35 | 2123.67 | 208.07 | 0.00 | 0.00 | 0.00 |
September | 1395.46 | 734.93 | 660.53 | 1819.37 | 348.40 | 0.00 | 0.00 | 0.00 |
October | 1276.66 | 793.49 | 483.17 | 1496.12 | 601.77 | 0.00 | 0.00 | 0.00 |
November | 1002.17 | 589.60 | 412.57 | 1008.91 | 825.64 | 0.00 | 0.00 | 0.00 |
December | 866.67 | 543.50 | 323.18 | 808.12 | 1060.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1319.70 | 716.62 | 603.08 | 1578.56 | 594.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 866.67 | 512.51 | 323.18 | 808.12 | 182.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1676.29 | 935.35 | 830.35 | 2279.95 | 1060.37 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126403E+10 | 0.00 | 0.126403E+10 | 0.384353E+09 | 0.396749E+10 |
February | 0.142694E+10 | 0.00 | 0.142694E+10 | 0.638776E+09 | 0.324914E+10 |
March | 0.199275E+10 | 0.00 | 0.199275E+10 | 0.136865E+10 | 0.283806E+10 |
April | 0.244662E+10 | 20946919.64 | 0.242567E+10 | 0.205008E+10 | 0.185592E+10 |
May | 0.274815E+10 | 0.177182E+09 | 0.257096E+10 | 0.286745E+10 | 0.142664E+10 |
June | 0.302190E+10 | 0.494529E+09 | 0.252738E+10 | 0.415639E+10 | 0.934908E+09 |
July | 0.286609E+10 | 0.238545E+09 | 0.262754E+10 | 0.423575E+10 | 0.665408E+09 |
August | 0.265878E+10 | 59524296.00 | 0.259925E+10 | 0.360699E+10 | 0.748149E+09 |
September | 0.205761E+10 | 528088.29 | 0.205708E+10 | 0.240932E+10 | 0.125282E+10 |
October | 0.158657E+10 | 0.00 | 0.158657E+10 | 0.121254E+10 | 0.224297E+10 |
November | 0.130391E+10 | 0.00 | 0.130391E+10 | 0.500658E+09 | 0.304018E+10 |
December | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.151485E+09 | 0.412681E+10 |
Annual Sum or Average | 0.244492E+11 | 0.991255E+09 | 0.234580E+11 | 0.235824E+11 | 0.263485E+11 |
Minimum of Months | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.151485E+09 | 0.665408E+09 |
Maximum of Months | 0.302190E+10 | 0.494529E+09 | 0.262754E+10 | 0.423575E+10 | 0.412681E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233372E+10 | 0.130477E+10 | 0.102895E+10 | 0.208344E+10 | 0.244498E+10 |
February | 0.256103E+10 | 0.138066E+10 | 0.118036E+10 | 0.246783E+10 | 0.201956E+10 |
March | 0.374035E+10 | 0.212631E+10 | 0.161403E+10 | 0.400121E+10 | 0.177877E+10 |
April | 0.494524E+10 | 0.281727E+10 | 0.212797E+10 | 0.574475E+10 | 0.121459E+10 |
May | 0.487610E+10 | 0.277884E+10 | 0.209726E+10 | 0.596570E+10 | 0.960555E+09 |
June | 0.508724E+10 | 0.313397E+10 | 0.195326E+10 | 0.680983E+10 | 0.612264E+09 |
July | 0.486422E+10 | 0.278155E+10 | 0.208267E+10 | 0.677601E+10 | 0.440671E+09 |
August | 0.481347E+10 | 0.265375E+10 | 0.215972E+10 | 0.651313E+10 | 0.494680E+09 |
September | 0.387717E+10 | 0.216930E+10 | 0.170786E+10 | 0.498155E+10 | 0.801317E+09 |
October | 0.348434E+10 | 0.221067E+10 | 0.127367E+10 | 0.398315E+10 | 0.140635E+10 |
November | 0.263534E+10 | 0.154930E+10 | 0.108605E+10 | 0.260085E+10 | 0.191736E+10 |
December | 0.220655E+10 | 0.134289E+10 | 0.863668E+09 | 0.196525E+10 | 0.255690E+10 |
Annual Sum or Average | 0.454248E+11 | 0.262493E+11 | 0.191755E+11 | 0.538927E+11 | 0.166480E+11 |
Minimum of Months | 0.220655E+10 | 0.130477E+10 | 0.863668E+09 | 0.196525E+10 | 0.440671E+09 |
Maximum of Months | 0.508724E+10 | 0.313397E+10 | 0.215972E+10 | 0.680983E+10 | 0.255690E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.934484E+10 | 0.727157E+10 | 0.207327E+10 | 0.105881E+11 | 0.371890E+10 |
February | 0.826018E+10 | 0.603377E+10 | 0.222641E+10 | 0.954373E+10 | 0.310946E+10 |
March | 0.673908E+10 | 0.407418E+10 | 0.266490E+10 | 0.796998E+10 | 0.281806E+10 |
April | 0.508609E+10 | 0.208774E+10 | 0.299835E+10 | 0.623282E+10 | 0.197124E+10 |
May | 0.350508E+10 | 0.771049E+09 | 0.273403E+10 | 0.433413E+10 | 0.151044E+10 |
June | 0.286936E+10 | 0.353615E+09 | 0.251575E+10 | 0.413758E+10 | 0.979949E+09 |
July | 0.328092E+10 | 0.523930E+09 | 0.275699E+10 | 0.509090E+10 | 0.688476E+09 |
August | 0.451151E+10 | 0.146646E+10 | 0.304504E+10 | 0.670384E+10 | 0.792540E+09 |
September | 0.603719E+10 | 0.336651E+10 | 0.267068E+10 | 0.834231E+10 | 0.130032E+10 |
October | 0.853492E+10 | 0.628591E+10 | 0.224900E+10 | 0.106922E+11 | 0.221407E+10 |
November | 0.919962E+10 | 0.706067E+10 | 0.213895E+10 | 0.107207E+11 | 0.292586E+10 |
December | 0.101389E+11 | 0.836351E+10 | 0.177537E+10 | 0.115455E+11 | 0.379712E+10 |
Annual Sum or Average | 0.775077E+11 | 0.476589E+11 | 0.298488E+11 | 0.959018E+11 | 0.258264E+11 |
Minimum of Months | 0.286936E+10 | 0.353615E+09 | 0.177537E+10 | 0.413758E+10 | 0.688476E+09 |
Maximum of Months | 0.101389E+11 | 0.836351E+10 | 0.304504E+10 | 0.115455E+11 | 0.379712E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240715E+10 | 0.137272E+10 | 0.103443E+10 | 0.232231E+10 | 0.260084E+10 |
February | 0.279892E+10 | 0.161685E+10 | 0.118207E+10 | 0.287309E+10 | 0.215014E+10 |
March | 0.346102E+10 | 0.184236E+10 | 0.161865E+10 | 0.375470E+10 | 0.190014E+10 |
April | 0.427480E+10 | 0.227506E+10 | 0.199974E+10 | 0.494783E+10 | 0.129872E+10 |
May | 0.418824E+10 | 0.215807E+10 | 0.203017E+10 | 0.512394E+10 | 0.101531E+10 |
June | 0.434495E+10 | 0.242443E+10 | 0.192052E+10 | 0.590692E+10 | 0.688000E+09 |
July | 0.404964E+10 | 0.198184E+10 | 0.206781E+10 | 0.574277E+10 | 0.475912E+09 |
August | 0.413802E+10 | 0.191400E+10 | 0.222402E+10 | 0.568261E+10 | 0.541260E+09 |
September | 0.361703E+10 | 0.190494E+10 | 0.171209E+10 | 0.472331E+10 | 0.862281E+09 |
October | 0.341940E+10 | 0.212528E+10 | 0.129412E+10 | 0.402535E+10 | 0.151558E+10 |
November | 0.259763E+10 | 0.152824E+10 | 0.106939E+10 | 0.264158E+10 | 0.199601E+10 |
December | 0.232130E+10 | 0.145570E+10 | 0.865599E+09 | 0.218477E+10 | 0.265979E+10 |
Annual Sum or Average | 0.416181E+11 | 0.225995E+11 | 0.190186E+11 | 0.499292E+11 | 0.177040E+11 |
Minimum of Months | 0.232130E+10 | 0.137272E+10 | 0.865599E+09 | 0.218477E+10 | 0.475912E+09 |
Maximum of Months | 0.434495E+10 | 0.242443E+10 | 0.222402E+10 | 0.590692E+10 | 0.265979E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.421323E+09 | 0.00 | 0.421323E+09 | 0.121696E+09 | 0.139121E+10 |
February | 0.475623E+09 | 0.00 | 0.475623E+09 | 0.214243E+09 | 0.111998E+10 |
March | 0.664217E+09 | 0.00 | 0.664217E+09 | 0.470476E+09 | 0.959278E+09 |
April | 0.815501E+09 | 6981976.20 | 0.808519E+09 | 0.701645E+09 | 0.623009E+09 |
May | 0.916005E+09 | 59057852.45 | 0.856948E+09 | 0.974572E+09 | 0.475016E+09 |
June | 0.100725E+10 | 0.164835E+09 | 0.842419E+09 | 0.140149E+10 | 0.310247E+09 |
July | 0.955318E+09 | 79511123.74 | 0.875807E+09 | 0.142648E+10 | 0.218555E+09 |
August | 0.886217E+09 | 19840493.26 | 0.866376E+09 | 0.121041E+10 | 0.253037E+09 |
September | 0.685838E+09 | 176021.10 | 0.685662E+09 | 0.800847E+09 | 0.442444E+09 |
October | 0.528831E+09 | 0.00 | 0.528831E+09 | 0.390272E+09 | 0.812847E+09 |
November | 0.434616E+09 | 0.00 | 0.434616E+09 | 0.149039E+09 | 0.110815E+10 |
December | 0.358609E+09 | 0.00 | 0.358609E+09 | 43051330.61 | 0.147385E+10 |
Annual Sum or Average | 0.814935E+10 | 0.330403E+09 | 0.781895E+10 | 0.790421E+10 | 0.918763E+10 |
Minimum of Months | 0.358609E+09 | 0.00 | 0.358609E+09 | 43051330.61 | 0.218555E+09 |
Maximum of Months | 0.100725E+10 | 0.164835E+09 | 0.875807E+09 | 0.142648E+10 | 0.147385E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.421349E+09 | 0.00 | 0.421349E+09 | 0.121704E+09 | 0.139129E+10 |
February | 0.475653E+09 | 0.00 | 0.475653E+09 | 0.214257E+09 | 0.112005E+10 |
March | 0.664259E+09 | 0.00 | 0.664259E+09 | 0.470506E+09 | 0.959338E+09 |
April | 0.815553E+09 | 6982417.45 | 0.808570E+09 | 0.701689E+09 | 0.623048E+09 |
May | 0.916063E+09 | 59061584.81 | 0.857002E+09 | 0.974634E+09 | 0.475046E+09 |
June | 0.100732E+10 | 0.164846E+09 | 0.842472E+09 | 0.140158E+10 | 0.310267E+09 |
July | 0.955378E+09 | 79516148.72 | 0.875862E+09 | 0.142657E+10 | 0.218569E+09 |
August | 0.886273E+09 | 19841747.15 | 0.866431E+09 | 0.121048E+10 | 0.253053E+09 |
September | 0.685881E+09 | 176032.23 | 0.685705E+09 | 0.800897E+09 | 0.442472E+09 |
October | 0.528865E+09 | 0.00 | 0.528865E+09 | 0.390297E+09 | 0.812898E+09 |
November | 0.434644E+09 | 0.00 | 0.434644E+09 | 0.149048E+09 | 0.110822E+10 |
December | 0.358632E+09 | 0.00 | 0.358632E+09 | 43054051.38 | 0.147395E+10 |
Annual Sum or Average | 0.814987E+10 | 0.330424E+09 | 0.781944E+10 | 0.790471E+10 | 0.918821E+10 |
Minimum of Months | 0.358632E+09 | 0.00 | 0.358632E+09 | 43054051.38 | 0.218569E+09 |
Maximum of Months | 0.100732E+10 | 0.164846E+09 | 0.875862E+09 | 0.142657E+10 | 0.147395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.421349E+09 | 0.00 | 0.421349E+09 | 0.121704E+09 | 0.139129E+10 |
February | 0.475653E+09 | 0.00 | 0.475653E+09 | 0.214257E+09 | 0.112005E+10 |
March | 0.664259E+09 | 0.00 | 0.664259E+09 | 0.470506E+09 | 0.959338E+09 |
April | 0.815553E+09 | 6982417.45 | 0.808570E+09 | 0.701689E+09 | 0.623048E+09 |
May | 0.916063E+09 | 59061584.81 | 0.857002E+09 | 0.974634E+09 | 0.475046E+09 |
June | 0.100732E+10 | 0.164846E+09 | 0.842472E+09 | 0.140158E+10 | 0.310267E+09 |
July | 0.955378E+09 | 79516148.72 | 0.875862E+09 | 0.142657E+10 | 0.218569E+09 |
August | 0.886273E+09 | 19841747.15 | 0.866431E+09 | 0.121048E+10 | 0.253053E+09 |
September | 0.685881E+09 | 176032.23 | 0.685705E+09 | 0.800897E+09 | 0.442472E+09 |
October | 0.528865E+09 | 0.00 | 0.528865E+09 | 0.390297E+09 | 0.812898E+09 |
November | 0.434644E+09 | 0.00 | 0.434644E+09 | 0.149048E+09 | 0.110822E+10 |
December | 0.358632E+09 | 0.00 | 0.358632E+09 | 43054051.38 | 0.147395E+10 |
Annual Sum or Average | 0.814987E+10 | 0.330424E+09 | 0.781944E+10 | 0.790471E+10 | 0.918821E+10 |
Minimum of Months | 0.358632E+09 | 0.00 | 0.358632E+09 | 43054051.38 | 0.218569E+09 |
Maximum of Months | 0.100732E+10 | 0.164846E+09 | 0.875862E+09 | 0.142657E+10 | 0.147395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.224494E+10 | 0.125513E+10 | 0.989811E+09 | 0.197761E+10 | 0.251300E+10 |
February | 0.246360E+10 | 0.132814E+10 | 0.113546E+10 | 0.237270E+10 | 0.205009E+10 |
March | 0.359806E+10 | 0.204542E+10 | 0.155264E+10 | 0.386962E+10 | 0.179441E+10 |
April | 0.475711E+10 | 0.271009E+10 | 0.204702E+10 | 0.555114E+10 | 0.123625E+10 |
May | 0.469060E+10 | 0.267312E+10 | 0.201748E+10 | 0.577078E+10 | 0.974133E+09 |
June | 0.489370E+10 | 0.301474E+10 | 0.187896E+10 | 0.658155E+10 | 0.620482E+09 |
July | 0.467917E+10 | 0.267573E+10 | 0.200345E+10 | 0.654312E+10 | 0.452696E+09 |
August | 0.463036E+10 | 0.255279E+10 | 0.207757E+10 | 0.628442E+10 | 0.517252E+09 |
September | 0.372967E+10 | 0.208677E+10 | 0.164290E+10 | 0.479153E+10 | 0.848934E+09 |
October | 0.335179E+10 | 0.212657E+10 | 0.122522E+10 | 0.380578E+10 | 0.150527E+10 |
November | 0.253509E+10 | 0.149035E+10 | 0.104473E+10 | 0.245490E+10 | 0.205204E+10 |
December | 0.212261E+10 | 0.129180E+10 | 0.830814E+09 | 0.186026E+10 | 0.267691E+10 |
Annual Sum or Average | 0.436967E+11 | 0.252506E+11 | 0.184461E+11 | 0.518634E+11 | 0.172415E+11 |
Minimum of Months | 0.212261E+10 | 0.125513E+10 | 0.830814E+09 | 0.186026E+10 | 0.452696E+09 |
Maximum of Months | 0.489370E+10 | 0.301474E+10 | 0.207757E+10 | 0.658155E+10 | 0.267691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 88762762.60 | 49626542.69 | 39136219.91 | 78192774.46 | 99361874.17 |
February | 97408428.90 | 52513334.98 | 44895093.93 | 93814265.91 | 81058680.38 |
March | 0.142264E+09 | 80874037.19 | 61389857.77 | 0.153001E+09 | 70949486.33 |
April | 0.188092E+09 | 0.107154E+09 | 80937330.44 | 0.219487E+09 | 48880346.56 |
May | 0.185462E+09 | 0.105693E+09 | 79769365.24 | 0.228172E+09 | 38516322.52 |
June | 0.193493E+09 | 0.119200E+09 | 74292527.79 | 0.260228E+09 | 24533280.58 |
July | 0.185010E+09 | 0.105796E+09 | 79214474.68 | 0.258709E+09 | 17899189.14 |
August | 0.183080E+09 | 0.100935E+09 | 82145092.75 | 0.248480E+09 | 20451693.88 |
September | 0.147468E+09 | 82509131.05 | 64958715.47 | 0.189453E+09 | 33566099.36 |
October | 0.132527E+09 | 84082628.53 | 48444060.89 | 0.150477E+09 | 59517134.22 |
November | 0.100235E+09 | 58927192.81 | 41307865.48 | 97064414.35 | 81135749.91 |
December | 83926134.77 | 51076496.02 | 32849638.75 | 73553175.04 | 0.105842E+09 |
Annual Sum or Average | 0.172773E+10 | 0.998388E+09 | 0.729340E+09 | 0.205063E+10 | 0.681712E+09 |
Minimum of Months | 83926134.77 | 49626542.69 | 32849638.75 | 73553175.04 | 17899189.14 |
Maximum of Months | 0.193493E+09 | 0.119200E+09 | 82145092.75 | 0.260228E+09 | 0.105842E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311505E+10 | 0.242393E+10 | 0.691110E+09 | 0.353968E+10 | 0.136031E+10 |
February | 0.275348E+10 | 0.201132E+10 | 0.742156E+09 | 0.320149E+10 | 0.112279E+10 |
March | 0.224643E+10 | 0.135810E+10 | 0.888325E+09 | 0.268681E+10 | 0.987846E+09 |
April | 0.169541E+10 | 0.695936E+09 | 0.999477E+09 | 0.210633E+10 | 0.679017E+09 |
May | 0.116839E+10 | 0.257025E+09 | 0.911366E+09 | 0.147587E+10 | 0.503688E+09 |
June | 0.956478E+09 | 0.117876E+09 | 0.838602E+09 | 0.139761E+10 | 0.324346E+09 |
July | 0.109367E+10 | 0.174649E+09 | 0.919021E+09 | 0.171029E+10 | 0.230250E+09 |
August | 0.150388E+10 | 0.488837E+09 | 0.101504E+10 | 0.224559E+10 | 0.278401E+09 |
September | 0.201246E+10 | 0.112221E+10 | 0.890252E+09 | 0.278644E+10 | 0.477852E+09 |
October | 0.284506E+10 | 0.209537E+10 | 0.749688E+09 | 0.356359E+10 | 0.829356E+09 |
November | 0.306664E+10 | 0.235363E+10 | 0.713002E+09 | 0.357066E+10 | 0.110592E+10 |
December | 0.337973E+10 | 0.278793E+10 | 0.591806E+09 | 0.385809E+10 | 0.141266E+10 |
Annual Sum or Average | 0.258367E+11 | 0.158868E+11 | 0.994985E+10 | 0.321424E+11 | 0.931244E+10 |
Minimum of Months | 0.956478E+09 | 0.117876E+09 | 0.591806E+09 | 0.139761E+10 | 0.230250E+09 |
Maximum of Months | 0.337973E+10 | 0.278793E+10 | 0.101504E+10 | 0.385809E+10 | 0.141266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311505E+10 | 0.242393E+10 | 0.691110E+09 | 0.353968E+10 | 0.136031E+10 |
February | 0.275348E+10 | 0.201132E+10 | 0.742156E+09 | 0.320149E+10 | 0.112279E+10 |
March | 0.224643E+10 | 0.135810E+10 | 0.888325E+09 | 0.268681E+10 | 0.987846E+09 |
April | 0.169541E+10 | 0.695936E+09 | 0.999477E+09 | 0.210633E+10 | 0.679017E+09 |
May | 0.116839E+10 | 0.257025E+09 | 0.911366E+09 | 0.147587E+10 | 0.503688E+09 |
June | 0.956478E+09 | 0.117876E+09 | 0.838602E+09 | 0.139761E+10 | 0.324346E+09 |
July | 0.109367E+10 | 0.174649E+09 | 0.919021E+09 | 0.171029E+10 | 0.230250E+09 |
August | 0.150388E+10 | 0.488837E+09 | 0.101504E+10 | 0.224559E+10 | 0.278401E+09 |
September | 0.201246E+10 | 0.112221E+10 | 0.890252E+09 | 0.278644E+10 | 0.477852E+09 |
October | 0.284506E+10 | 0.209537E+10 | 0.749688E+09 | 0.356359E+10 | 0.829356E+09 |
November | 0.306664E+10 | 0.235363E+10 | 0.713002E+09 | 0.357066E+10 | 0.110592E+10 |
December | 0.337973E+10 | 0.278793E+10 | 0.591806E+09 | 0.385809E+10 | 0.141266E+10 |
Annual Sum or Average | 0.258367E+11 | 0.158868E+11 | 0.994985E+10 | 0.321424E+11 | 0.931244E+10 |
Minimum of Months | 0.956478E+09 | 0.117876E+09 | 0.591806E+09 | 0.139761E+10 | 0.230250E+09 |
Maximum of Months | 0.337973E+10 | 0.278793E+10 | 0.101504E+10 | 0.385809E+10 | 0.141266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.311485E+10 | 0.242378E+10 | 0.691067E+09 | 0.353946E+10 | 0.136023E+10 |
February | 0.275331E+10 | 0.201120E+10 | 0.742109E+09 | 0.320129E+10 | 0.112272E+10 |
March | 0.224629E+10 | 0.135802E+10 | 0.888269E+09 | 0.268664E+10 | 0.987784E+09 |
April | 0.169531E+10 | 0.695892E+09 | 0.999414E+09 | 0.210620E+10 | 0.678974E+09 |
May | 0.116832E+10 | 0.257008E+09 | 0.911309E+09 | 0.147577E+10 | 0.503656E+09 |
June | 0.956417E+09 | 0.117868E+09 | 0.838549E+09 | 0.139753E+10 | 0.324326E+09 |
July | 0.109360E+10 | 0.174638E+09 | 0.918963E+09 | 0.171018E+10 | 0.230236E+09 |
August | 0.150378E+10 | 0.488806E+09 | 0.101498E+10 | 0.224545E+10 | 0.278383E+09 |
September | 0.201233E+10 | 0.112214E+10 | 0.890196E+09 | 0.278627E+10 | 0.477822E+09 |
October | 0.284488E+10 | 0.209524E+10 | 0.749641E+09 | 0.356336E+10 | 0.829303E+09 |
November | 0.306644E+10 | 0.235349E+10 | 0.712957E+09 | 0.357043E+10 | 0.110585E+10 |
December | 0.337952E+10 | 0.278775E+10 | 0.591769E+09 | 0.385785E+10 | 0.141257E+10 |
Annual Sum or Average | 0.258350E+11 | 0.158858E+11 | 0.994922E+10 | 0.321404E+11 | 0.931185E+10 |
Minimum of Months | 0.956417E+09 | 0.117868E+09 | 0.591769E+09 | 0.139753E+10 | 0.230236E+09 |
Maximum of Months | 0.337952E+10 | 0.278775E+10 | 0.101498E+10 | 0.385785E+10 | 0.141257E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231557E+10 | 0.132049E+10 | 0.995080E+09 | 0.223296E+10 | 0.267507E+10 |
February | 0.269244E+10 | 0.155534E+10 | 0.113711E+10 | 0.277857E+10 | 0.218795E+10 |
March | 0.332935E+10 | 0.177227E+10 | 0.155708E+10 | 0.364363E+10 | 0.190532E+10 |
April | 0.411218E+10 | 0.218851E+10 | 0.192367E+10 | 0.478678E+10 | 0.131276E+10 |
May | 0.402891E+10 | 0.207596E+10 | 0.195294E+10 | 0.495663E+10 | 0.101491E+10 |
June | 0.417966E+10 | 0.233219E+10 | 0.184746E+10 | 0.570165E+10 | 0.690480E+09 |
July | 0.389559E+10 | 0.190644E+10 | 0.198915E+10 | 0.554262E+10 | 0.478635E+09 |
August | 0.398060E+10 | 0.184118E+10 | 0.213942E+10 | 0.547439E+10 | 0.559195E+09 |
September | 0.347943E+10 | 0.183247E+10 | 0.164696E+10 | 0.452975E+10 | 0.912367E+09 |
October | 0.328931E+10 | 0.204442E+10 | 0.124489E+10 | 0.384619E+10 | 0.161748E+10 |
November | 0.249880E+10 | 0.147010E+10 | 0.102871E+10 | 0.251355E+10 | 0.213046E+10 |
December | 0.223299E+10 | 0.140032E+10 | 0.832672E+09 | 0.209554E+10 | 0.278277E+10 |
Annual Sum or Average | 0.400348E+11 | 0.217397E+11 | 0.182951E+11 | 0.481023E+11 | 0.182674E+11 |
Minimum of Months | 0.223299E+10 | 0.132049E+10 | 0.832672E+09 | 0.209554E+10 | 0.478635E+09 |
Maximum of Months | 0.417966E+10 | 0.233219E+10 | 0.213942E+10 | 0.570165E+10 | 0.278277E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91555430.20 | 52210937.21 | 39344492.99 | 88288784.34 | 0.105770E+09 |
February | 0.106457E+09 | 61496468.38 | 44960048.95 | 0.109862E+09 | 86509713.66 |
March | 0.131639E+09 | 70073753.66 | 61565381.68 | 0.144066E+09 | 75334472.79 |
April | 0.162591E+09 | 86531428.42 | 76059895.23 | 0.189265E+09 | 51905279.77 |
May | 0.159299E+09 | 82081514.64 | 77217483.04 | 0.195980E+09 | 40128797.16 |
June | 0.165259E+09 | 92212525.83 | 73046952.02 | 0.225438E+09 | 27300918.50 |
July | 0.154028E+09 | 75378610.50 | 78649007.03 | 0.219150E+09 | 18924780.44 |
August | 0.157389E+09 | 72798358.61 | 84590492.92 | 0.216452E+09 | 22110065.13 |
September | 0.137573E+09 | 72453866.55 | 65119348.55 | 0.179102E+09 | 36074133.41 |
October | 0.130056E+09 | 80834246.81 | 49221887.63 | 0.152075E+09 | 63953631.02 |
November | 98800200.28 | 58126119.33 | 40674080.96 | 99383191.24 | 84236326.00 |
December | 88290118.90 | 55367091.40 | 32923027.51 | 82855341.75 | 0.110028E+09 |
Annual Sum or Average | 0.158294E+10 | 0.859565E+09 | 0.723372E+09 | 0.190191E+10 | 0.722276E+09 |
Minimum of Months | 88290118.90 | 52210937.21 | 32923027.51 | 82855341.75 | 18924780.44 |
Maximum of Months | 0.165259E+09 | 92212525.83 | 84590492.92 | 0.225438E+09 | 0.110028E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126403E+10 | 0.00 | 0.126403E+10 | 0.343112E+09 | 0.422743E+10 |
February | 0.142694E+10 | 0.00 | 0.142694E+10 | 0.596348E+09 | 0.345843E+10 |
March | 0.199275E+10 | 0.00 | 0.199275E+10 | 0.131723E+10 | 0.302224E+10 |
April | 0.244662E+10 | 20946919.64 | 0.242567E+10 | 0.201052E+10 | 0.197176E+10 |
May | 0.274815E+10 | 0.177182E+09 | 0.257096E+10 | 0.284122E+10 | 0.149534E+10 |
June | 0.302190E+10 | 0.494529E+09 | 0.252738E+10 | 0.415666E+10 | 0.964491E+09 |
July | 0.286609E+10 | 0.238545E+09 | 0.262754E+10 | 0.424812E+10 | 0.681541E+09 |
August | 0.265878E+10 | 59524296.00 | 0.259925E+10 | 0.361297E+10 | 0.771642E+09 |
September | 0.205761E+10 | 528088.29 | 0.205708E+10 | 0.239598E+10 | 0.131950E+10 |
October | 0.158657E+10 | 0.00 | 0.158657E+10 | 0.117172E+10 | 0.240842E+10 |
November | 0.130391E+10 | 0.00 | 0.130391E+10 | 0.447524E+09 | 0.328780E+10 |
December | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.126107E+09 | 0.441819E+10 |
Annual Sum or Average | 0.244492E+11 | 0.991255E+09 | 0.234580E+11 | 0.232675E+11 | 0.280268E+11 |
Minimum of Months | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.126107E+09 | 0.681541E+09 |
Maximum of Months | 0.302190E+10 | 0.494529E+09 | 0.262754E+10 | 0.424812E+10 | 0.441819E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233372E+10 | 0.130477E+10 | 0.102895E+10 | 0.203682E+10 | 0.259152E+10 |
February | 0.256103E+10 | 0.138066E+10 | 0.118036E+10 | 0.243095E+10 | 0.213811E+10 |
March | 0.374035E+10 | 0.212631E+10 | 0.161403E+10 | 0.397454E+10 | 0.187424E+10 |
April | 0.494524E+10 | 0.281727E+10 | 0.212797E+10 | 0.573343E+10 | 0.127346E+10 |
May | 0.487610E+10 | 0.277884E+10 | 0.209726E+10 | 0.596499E+10 | 0.100038E+10 |
June | 0.508724E+10 | 0.313397E+10 | 0.195326E+10 | 0.682093E+10 | 0.629751E+09 |
July | 0.486422E+10 | 0.278155E+10 | 0.208267E+10 | 0.679277E+10 | 0.449714E+09 |
August | 0.481347E+10 | 0.265375E+10 | 0.215972E+10 | 0.652670E+10 | 0.506960E+09 |
September | 0.387717E+10 | 0.216930E+10 | 0.170786E+10 | 0.498085E+10 | 0.834990E+09 |
October | 0.348434E+10 | 0.221067E+10 | 0.127367E+10 | 0.396312E+10 | 0.148857E+10 |
November | 0.263534E+10 | 0.154930E+10 | 0.108605E+10 | 0.255803E+10 | 0.204741E+10 |
December | 0.220655E+10 | 0.134289E+10 | 0.863668E+09 | 0.192529E+10 | 0.272495E+10 |
Annual Sum or Average | 0.454248E+11 | 0.262493E+11 | 0.191755E+11 | 0.537084E+11 | 0.175601E+11 |
Minimum of Months | 0.220655E+10 | 0.130477E+10 | 0.863668E+09 | 0.192529E+10 | 0.449714E+09 |
Maximum of Months | 0.508724E+10 | 0.313397E+10 | 0.215972E+10 | 0.682093E+10 | 0.272495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.934484E+10 | 0.727157E+10 | 0.207327E+10 | 0.105264E+11 | 0.394663E+10 |
February | 0.826018E+10 | 0.603377E+10 | 0.222641E+10 | 0.949925E+10 | 0.329795E+10 |
March | 0.673908E+10 | 0.407418E+10 | 0.266490E+10 | 0.793100E+10 | 0.298239E+10 |
April | 0.508609E+10 | 0.208774E+10 | 0.299835E+10 | 0.621325E+10 | 0.208383E+10 |
May | 0.350508E+10 | 0.771049E+09 | 0.273403E+10 | 0.432047E+10 | 0.158659E+10 |
June | 0.286936E+10 | 0.353615E+09 | 0.251575E+10 | 0.414143E+10 | 0.101760E+10 |
July | 0.328092E+10 | 0.523930E+09 | 0.275699E+10 | 0.510535E+10 | 0.707569E+09 |
August | 0.451151E+10 | 0.146646E+10 | 0.304504E+10 | 0.671737E+10 | 0.818351E+09 |
September | 0.603719E+10 | 0.336651E+10 | 0.267068E+10 | 0.834077E+10 | 0.136147E+10 |
October | 0.853492E+10 | 0.628591E+10 | 0.224900E+10 | 0.106602E+11 | 0.234706E+10 |
November | 0.919962E+10 | 0.706067E+10 | 0.213895E+10 | 0.106649E+11 | 0.313065E+10 |
December | 0.101389E+11 | 0.836351E+10 | 0.177537E+10 | 0.114914E+11 | 0.404887E+10 |
Annual Sum or Average | 0.775077E+11 | 0.476589E+11 | 0.298488E+11 | 0.956117E+11 | 0.273290E+11 |
Minimum of Months | 0.286936E+10 | 0.353615E+09 | 0.177537E+10 | 0.414143E+10 | 0.707569E+09 |
Maximum of Months | 0.101389E+11 | 0.836351E+10 | 0.304504E+10 | 0.114914E+11 | 0.404887E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240715E+10 | 0.137272E+10 | 0.103443E+10 | 0.229734E+10 | 0.276324E+10 |
February | 0.279892E+10 | 0.161685E+10 | 0.118207E+10 | 0.285194E+10 | 0.227997E+10 |
March | 0.346102E+10 | 0.184236E+10 | 0.161865E+10 | 0.373416E+10 | 0.200880E+10 |
April | 0.427480E+10 | 0.227506E+10 | 0.199974E+10 | 0.493308E+10 | 0.137027E+10 |
May | 0.418824E+10 | 0.215807E+10 | 0.203017E+10 | 0.511325E+10 | 0.106393E+10 |
June | 0.434495E+10 | 0.242443E+10 | 0.192052E+10 | 0.590963E+10 | 0.711490E+09 |
July | 0.404964E+10 | 0.198184E+10 | 0.206781E+10 | 0.575133E+10 | 0.488527E+09 |
August | 0.413802E+10 | 0.191400E+10 | 0.222402E+10 | 0.568805E+10 | 0.557294E+09 |
September | 0.361703E+10 | 0.190494E+10 | 0.171209E+10 | 0.471580E+10 | 0.903062E+09 |
October | 0.341940E+10 | 0.212528E+10 | 0.129412E+10 | 0.400721E+10 | 0.161177E+10 |
November | 0.259763E+10 | 0.152824E+10 | 0.106939E+10 | 0.261508E+10 | 0.214005E+10 |
December | 0.232130E+10 | 0.145570E+10 | 0.865599E+09 | 0.216446E+10 | 0.284010E+10 |
Annual Sum or Average | 0.416181E+11 | 0.225995E+11 | 0.190186E+11 | 0.497813E+11 | 0.187385E+11 |
Minimum of Months | 0.232130E+10 | 0.137272E+10 | 0.865599E+09 | 0.216446E+10 | 0.488527E+09 |
Maximum of Months | 0.434495E+10 | 0.242443E+10 | 0.222402E+10 | 0.590963E+10 | 0.284010E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 143.50 | 1481.29 | 471.93 | 0.00 | 471.93 | 0.00 | 0.00 |
February | 264.04 | 1343.07 | 589.84 | 0.00 | 589.84 | 0.00 | 0.00 |
March | 511.00 | 1059.61 | 744.01 | 0.00 | 744.01 | 0.00 | 0.00 |
April | 790.92 | 716.02 | 943.91 | 8.08 | 935.83 | 0.00 | 0.00 |
May | 1070.58 | 532.65 | 1026.04 | 66.15 | 959.89 | 0.00 | 0.00 |
June | 1603.54 | 360.69 | 1165.86 | 190.79 | 975.07 | 0.00 | 0.00 |
July | 1581.45 | 248.44 | 1070.08 | 89.06 | 981.01 | 0.00 | 0.00 |
August | 1346.70 | 279.33 | 992.67 | 22.22 | 970.45 | 0.00 | 0.00 |
September | 929.52 | 483.34 | 793.83 | 0.20 | 793.63 | 0.00 | 0.00 |
October | 452.71 | 837.43 | 592.36 | 0.00 | 592.36 | 0.00 | 0.00 |
November | 193.15 | 1172.91 | 503.05 | 0.00 | 503.05 | 0.00 | 0.00 |
December | 56.56 | 1540.77 | 401.69 | 0.00 | 401.69 | 0.00 | 0.00 |
Annual Sum or Average | 747.79 | 835.51 | 775.28 | 31.43 | 743.85 | 0.00 | 0.00 |
Minimum of Months | 56.56 | 248.44 | 401.69 | 0.00 | 401.69 | 0.00 | 0.00 |
Maximum of Months | 1603.54 | 1540.77 | 1165.86 | 190.79 | 981.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 777.87 | 912.85 | 871.31 | 487.14 | 384.17 | 0.00 | 0.00 |
February | 1020.10 | 834.81 | 1058.63 | 570.71 | 487.91 | 0.00 | 0.00 |
March | 1493.88 | 664.12 | 1396.49 | 793.88 | 602.61 | 0.00 | 0.00 |
April | 2216.34 | 468.59 | 1907.89 | 1086.91 | 820.98 | 0.00 | 0.00 |
May | 2227.34 | 358.63 | 1820.53 | 1037.50 | 783.03 | 0.00 | 0.00 |
June | 2627.25 | 236.21 | 1962.67 | 1209.09 | 753.57 | 0.00 | 0.00 |
July | 2529.87 | 164.53 | 1816.09 | 1038.51 | 777.58 | 0.00 | 0.00 |
August | 2431.72 | 184.69 | 1797.15 | 990.80 | 806.35 | 0.00 | 0.00 |
September | 1921.90 | 309.15 | 1495.82 | 836.92 | 658.90 | 0.00 | 0.00 |
October | 1487.14 | 525.07 | 1300.90 | 825.37 | 475.53 | 0.00 | 0.00 |
November | 1003.41 | 739.72 | 1016.72 | 597.72 | 419.00 | 0.00 | 0.00 |
December | 733.74 | 954.64 | 823.83 | 501.38 | 322.46 | 0.00 | 0.00 |
Annual Sum or Average | 1708.93 | 527.90 | 1440.41 | 832.36 | 608.05 | 0.00 | 0.00 |
Minimum of Months | 733.74 | 164.53 | 823.83 | 487.14 | 322.46 | 0.00 | 0.00 |
Maximum of Months | 2627.25 | 954.64 | 1962.67 | 1209.09 | 820.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3953.15 | 1388.48 | 3488.96 | 2714.89 | 774.07 | 0.00 | 0.00 |
February | 3944.99 | 1285.33 | 3414.43 | 2494.12 | 920.31 | 0.00 | 0.00 |
March | 2975.65 | 1052.14 | 2516.08 | 1521.12 | 994.96 | 0.00 | 0.00 |
April | 2404.64 | 760.51 | 1962.23 | 805.46 | 1156.77 | 0.00 | 0.00 |
May | 1618.18 | 563.93 | 1308.65 | 287.88 | 1020.77 | 0.00 | 0.00 |
June | 1596.29 | 378.07 | 1107.01 | 136.43 | 970.58 | 0.00 | 0.00 |
July | 1900.72 | 257.05 | 1224.96 | 195.61 | 1029.34 | 0.00 | 0.00 |
August | 2502.93 | 295.90 | 1684.40 | 547.51 | 1136.89 | 0.00 | 0.00 |
September | 3218.48 | 501.67 | 2329.16 | 1298.81 | 1030.36 | 0.00 | 0.00 |
October | 3992.01 | 826.64 | 3186.57 | 2346.89 | 839.68 | 0.00 | 0.00 |
November | 4136.08 | 1128.80 | 3549.24 | 2724.03 | 825.21 | 0.00 | 0.00 |
December | 4310.60 | 1417.68 | 3785.42 | 3122.58 | 662.85 | 0.00 | 0.00 |
Annual Sum or Average | 3041.03 | 818.95 | 2457.75 | 1511.25 | 946.50 | 0.00 | 0.00 |
Minimum of Months | 1596.29 | 257.05 | 1107.01 | 136.43 | 662.85 | 0.00 | 0.00 |
Maximum of Months | 4310.60 | 1417.68 | 3785.42 | 3122.58 | 1156.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 867.05 | 971.04 | 898.73 | 512.51 | 386.21 | 0.00 | 0.00 |
February | 1187.62 | 888.78 | 1156.96 | 668.34 | 488.62 | 0.00 | 0.00 |
March | 1401.84 | 709.43 | 1292.20 | 687.86 | 604.34 | 0.00 | 0.00 |
April | 1908.88 | 501.05 | 1649.23 | 877.73 | 771.50 | 0.00 | 0.00 |
May | 1913.06 | 379.07 | 1563.71 | 805.73 | 757.98 | 0.00 | 0.00 |
June | 2278.91 | 265.43 | 1676.29 | 935.35 | 740.94 | 0.00 | 0.00 |
July | 2144.10 | 177.69 | 1511.96 | 739.93 | 772.03 | 0.00 | 0.00 |
August | 2121.64 | 202.08 | 1544.96 | 714.60 | 830.35 | 0.00 | 0.00 |
September | 1822.26 | 332.67 | 1395.46 | 734.93 | 660.53 | 0.00 | 0.00 |
October | 1502.90 | 565.85 | 1276.66 | 793.49 | 483.17 | 0.00 | 0.00 |
November | 1019.13 | 770.07 | 1002.17 | 589.60 | 412.57 | 0.00 | 0.00 |
December | 815.70 | 993.05 | 866.67 | 543.50 | 323.18 | 0.00 | 0.00 |
Annual Sum or Average | 1583.24 | 561.39 | 1319.70 | 716.62 | 603.08 | 0.00 | 0.00 |
Minimum of Months | 815.70 | 177.69 | 866.67 | 512.51 | 323.18 | 0.00 | 0.00 |
Maximum of Months | 2278.91 | 993.05 | 1676.29 | 935.35 | 830.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.31 | 1558.32 | 471.93 | 0.00 | 471.93 | 0.00 | 0.00 |
February | 265.69 | 1388.93 | 589.83 | 0.00 | 589.83 | 0.00 | 0.00 |
March | 526.99 | 1074.50 | 744.00 | 0.00 | 744.00 | 0.00 | 0.00 |
April | 812.12 | 721.11 | 943.91 | 8.08 | 935.83 | 0.00 | 0.00 |
May | 1091.64 | 532.07 | 1026.03 | 66.15 | 959.88 | 0.00 | 0.00 |
June | 1622.16 | 359.10 | 1165.85 | 190.79 | 975.06 | 0.00 | 0.00 |
July | 1597.82 | 244.81 | 1070.07 | 89.06 | 981.01 | 0.00 | 0.00 |
August | 1355.80 | 283.43 | 992.67 | 22.22 | 970.44 | 0.00 | 0.00 |
September | 926.94 | 512.11 | 793.83 | 0.20 | 793.62 | 0.00 | 0.00 |
October | 437.15 | 910.48 | 592.35 | 0.00 | 592.35 | 0.00 | 0.00 |
November | 172.51 | 1282.64 | 503.05 | 0.00 | 503.05 | 0.00 | 0.00 |
December | 48.22 | 1650.89 | 401.68 | 0.00 | 401.68 | 0.00 | 0.00 |
Annual Sum or Average | 751.95 | 874.05 | 775.28 | 31.43 | 743.84 | 0.00 | 0.00 |
Minimum of Months | 48.22 | 244.81 | 401.68 | 0.00 | 401.68 | 0.00 | 0.00 |
Maximum of Months | 1622.16 | 1650.89 | 1165.85 | 190.79 | 981.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 767.55 | 975.35 | 871.30 | 487.14 | 384.16 | 0.00 | 0.00 |
February | 1019.56 | 880.93 | 1058.62 | 570.71 | 487.91 | 0.00 | 0.00 |
March | 1501.88 | 696.45 | 1396.48 | 793.87 | 602.61 | 0.00 | 0.00 |
April | 2226.32 | 495.81 | 1907.87 | 1086.90 | 820.97 | 0.00 | 0.00 |
May | 2239.75 | 378.08 | 1820.51 | 1037.49 | 783.02 | 0.00 | 0.00 |
June | 2639.57 | 248.85 | 1962.65 | 1209.08 | 753.57 | 0.00 | 0.00 |
July | 2539.51 | 175.70 | 1816.08 | 1038.50 | 777.58 | 0.00 | 0.00 |
August | 2439.10 | 200.76 | 1797.13 | 990.79 | 806.34 | 0.00 | 0.00 |
September | 1921.68 | 340.47 | 1495.81 | 836.91 | 658.90 | 0.00 | 0.00 |
October | 1477.10 | 584.23 | 1300.89 | 825.36 | 475.53 | 0.00 | 0.00 |
November | 984.55 | 822.98 | 1016.71 | 597.72 | 419.00 | 0.00 | 0.00 |
December | 722.00 | 1038.96 | 823.83 | 501.37 | 322.46 | 0.00 | 0.00 |
Annual Sum or Average | 1709.60 | 568.34 | 1440.40 | 832.35 | 608.05 | 0.00 | 0.00 |
Minimum of Months | 722.00 | 175.70 | 823.83 | 487.14 | 322.46 | 0.00 | 0.00 |
Maximum of Months | 2639.57 | 1038.96 | 1962.65 | 1209.08 | 820.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3964.61 | 1523.61 | 3489.00 | 2714.92 | 774.08 | 0.00 | 0.00 |
February | 3970.02 | 1392.32 | 3414.46 | 2494.15 | 920.31 | 0.00 | 0.00 |
March | 3009.36 | 1106.44 | 2516.11 | 1521.14 | 994.97 | 0.00 | 0.00 |
April | 2437.83 | 785.88 | 1962.24 | 805.47 | 1156.78 | 0.00 | 0.00 |
May | 1653.04 | 564.15 | 1308.65 | 287.88 | 1020.77 | 0.00 | 0.00 |
June | 1617.58 | 375.39 | 1107.01 | 136.43 | 970.58 | 0.00 | 0.00 |
July | 1915.60 | 257.89 | 1224.96 | 195.62 | 1029.35 | 0.00 | 0.00 |
August | 2515.17 | 311.82 | 1684.42 | 547.52 | 1136.90 | 0.00 | 0.00 |
September | 3224.98 | 553.06 | 2329.19 | 1298.82 | 1030.36 | 0.00 | 0.00 |
October | 3991.39 | 928.92 | 3186.61 | 2346.92 | 839.69 | 0.00 | 0.00 |
November | 4132.62 | 1279.98 | 3549.27 | 2724.06 | 825.22 | 0.00 | 0.00 |
December | 4321.25 | 1582.25 | 3785.46 | 3122.61 | 662.85 | 0.00 | 0.00 |
Annual Sum or Average | 3057.63 | 885.87 | 2457.78 | 1511.27 | 946.50 | 0.00 | 0.00 |
Minimum of Months | 1617.58 | 257.89 | 1107.01 | 136.43 | 662.85 | 0.00 | 0.00 |
Maximum of Months | 4321.25 | 1582.25 | 3785.46 | 3122.61 | 1156.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 866.65 | 1038.25 | 898.72 | 512.51 | 386.21 | 0.00 | 0.00 |
February | 1193.96 | 940.17 | 1156.95 | 668.33 | 488.62 | 0.00 | 0.00 |
March | 1414.16 | 739.49 | 1292.19 | 687.85 | 604.33 | 0.00 | 0.00 |
April | 1919.77 | 526.49 | 1649.22 | 877.72 | 771.50 | 0.00 | 0.00 |
May | 1923.76 | 393.91 | 1563.70 | 805.72 | 757.98 | 0.00 | 0.00 |
June | 2286.69 | 276.92 | 1676.28 | 935.34 | 740.94 | 0.00 | 0.00 |
July | 2151.20 | 185.77 | 1511.95 | 739.93 | 772.03 | 0.00 | 0.00 |
August | 2124.72 | 217.03 | 1544.95 | 714.60 | 830.35 | 0.00 | 0.00 |
September | 1816.69 | 365.91 | 1395.45 | 734.92 | 660.53 | 0.00 | 0.00 |
October | 1492.78 | 627.77 | 1276.65 | 793.48 | 483.17 | 0.00 | 0.00 |
November | 1008.08 | 854.43 | 1002.16 | 589.59 | 412.57 | 0.00 | 0.00 |
December | 813.32 | 1080.05 | 866.67 | 543.49 | 323.18 | 0.00 | 0.00 |
Annual Sum or Average | 1585.62 | 602.16 | 1319.69 | 716.62 | 603.07 | 0.00 | 0.00 |
Minimum of Months | 813.32 | 185.77 | 866.67 | 512.51 | 323.18 | 0.00 | 0.00 |
Maximum of Months | 2286.69 | 1080.05 | 1676.28 | 935.34 | 830.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 128.10 | 1578.34 | 471.93 | 0.00 | 471.93 | 0.00 | 0.00 |
February | 246.51 | 1429.58 | 589.84 | 0.00 | 589.84 | 0.00 | 0.00 |
March | 491.80 | 1128.38 | 744.01 | 0.00 | 744.01 | 0.00 | 0.00 |
April | 775.67 | 760.71 | 943.91 | 8.08 | 935.83 | 0.00 | 0.00 |
May | 1060.79 | 558.30 | 1026.04 | 66.15 | 959.89 | 0.00 | 0.00 |
June | 1603.65 | 372.10 | 1165.86 | 190.79 | 975.07 | 0.00 | 0.00 |
July | 1586.07 | 254.46 | 1070.08 | 89.06 | 981.01 | 0.00 | 0.00 |
August | 1348.93 | 288.10 | 992.67 | 22.22 | 970.45 | 0.00 | 0.00 |
September | 924.38 | 509.07 | 793.83 | 0.20 | 793.63 | 0.00 | 0.00 |
October | 437.47 | 899.20 | 592.36 | 0.00 | 592.36 | 0.00 | 0.00 |
November | 172.66 | 1268.44 | 503.05 | 0.00 | 503.05 | 0.00 | 0.00 |
December | 47.08 | 1649.56 | 401.69 | 0.00 | 401.69 | 0.00 | 0.00 |
Annual Sum or Average | 737.81 | 888.72 | 775.28 | 31.43 | 743.85 | 0.00 | 0.00 |
Minimum of Months | 47.08 | 254.46 | 401.69 | 0.00 | 401.69 | 0.00 | 0.00 |
Maximum of Months | 1603.65 | 1649.56 | 1165.86 | 190.79 | 981.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 760.46 | 967.56 | 871.31 | 487.14 | 384.17 | 0.00 | 0.00 |
February | 1004.86 | 883.81 | 1058.63 | 570.71 | 487.91 | 0.00 | 0.00 |
March | 1483.92 | 699.76 | 1396.49 | 793.88 | 602.61 | 0.00 | 0.00 |
April | 2211.97 | 491.30 | 1907.89 | 1086.91 | 820.98 | 0.00 | 0.00 |
May | 2227.07 | 373.50 | 1820.53 | 1037.50 | 783.03 | 0.00 | 0.00 |
June | 2631.53 | 242.96 | 1962.67 | 1209.09 | 753.57 | 0.00 | 0.00 |
July | 2536.13 | 167.90 | 1816.09 | 1038.51 | 777.58 | 0.00 | 0.00 |
August | 2436.79 | 189.28 | 1797.15 | 990.80 | 806.35 | 0.00 | 0.00 |
September | 1921.62 | 322.14 | 1495.82 | 836.92 | 658.90 | 0.00 | 0.00 |
October | 1479.66 | 555.77 | 1300.90 | 825.37 | 475.53 | 0.00 | 0.00 |
November | 986.89 | 789.89 | 1016.72 | 597.72 | 419.00 | 0.00 | 0.00 |
December | 718.82 | 1017.38 | 823.83 | 501.38 | 322.46 | 0.00 | 0.00 |
Annual Sum or Average | 1703.08 | 556.83 | 1440.41 | 832.36 | 608.05 | 0.00 | 0.00 |
Minimum of Months | 718.82 | 167.90 | 823.83 | 487.14 | 322.46 | 0.00 | 0.00 |
Maximum of Months | 2631.53 | 1017.38 | 1962.67 | 1209.09 | 820.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3930.10 | 1473.50 | 3488.96 | 2714.89 | 774.07 | 0.00 | 0.00 |
February | 3926.61 | 1363.24 | 3414.43 | 2494.12 | 920.31 | 0.00 | 0.00 |
March | 2961.10 | 1113.50 | 2516.08 | 1521.12 | 994.96 | 0.00 | 0.00 |
April | 2397.09 | 803.95 | 1962.23 | 805.46 | 1156.77 | 0.00 | 0.00 |
May | 1613.08 | 592.36 | 1308.65 | 287.88 | 1020.77 | 0.00 | 0.00 |
June | 1597.77 | 392.59 | 1107.01 | 136.43 | 970.58 | 0.00 | 0.00 |
July | 1906.12 | 264.18 | 1224.96 | 195.61 | 1029.34 | 0.00 | 0.00 |
August | 2507.98 | 305.54 | 1684.40 | 547.51 | 1136.89 | 0.00 | 0.00 |
September | 3217.89 | 525.26 | 2329.16 | 1298.81 | 1030.36 | 0.00 | 0.00 |
October | 3980.06 | 876.29 | 3186.57 | 2346.89 | 839.68 | 0.00 | 0.00 |
November | 4114.53 | 1207.81 | 3549.24 | 2724.03 | 825.21 | 0.00 | 0.00 |
December | 4290.39 | 1511.67 | 3785.42 | 3122.58 | 662.85 | 0.00 | 0.00 |
Annual Sum or Average | 3031.83 | 866.60 | 2457.75 | 1511.25 | 946.50 | 0.00 | 0.00 |
Minimum of Months | 1597.77 | 264.18 | 1107.01 | 136.43 | 662.85 | 0.00 | 0.00 |
Maximum of Months | 4290.39 | 1511.67 | 3785.42 | 3122.58 | 1156.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 857.73 | 1031.67 | 898.73 | 512.51 | 386.21 | 0.00 | 0.00 |
February | 1178.88 | 942.45 | 1156.96 | 668.34 | 488.62 | 0.00 | 0.00 |
March | 1394.18 | 750.00 | 1292.20 | 687.86 | 604.34 | 0.00 | 0.00 |
April | 1903.20 | 528.65 | 1649.23 | 877.73 | 771.50 | 0.00 | 0.00 |
May | 1909.07 | 397.23 | 1563.71 | 805.73 | 757.98 | 0.00 | 0.00 |
June | 2279.95 | 274.49 | 1676.29 | 935.35 | 740.94 | 0.00 | 0.00 |
July | 2147.30 | 182.40 | 1511.96 | 739.93 | 772.03 | 0.00 | 0.00 |
August | 2123.67 | 208.07 | 1544.96 | 714.60 | 830.35 | 0.00 | 0.00 |
September | 1819.37 | 348.40 | 1395.46 | 734.93 | 660.53 | 0.00 | 0.00 |
October | 1496.12 | 601.77 | 1276.66 | 793.49 | 483.17 | 0.00 | 0.00 |
November | 1008.91 | 825.64 | 1002.17 | 589.60 | 412.57 | 0.00 | 0.00 |
December | 808.12 | 1060.37 | 866.67 | 543.50 | 323.18 | 0.00 | 0.00 |
Annual Sum or Average | 1578.56 | 594.19 | 1319.70 | 716.62 | 603.08 | 0.00 | 0.00 |
Minimum of Months | 808.12 | 182.40 | 866.67 | 512.51 | 323.18 | 0.00 | 0.00 |
Maximum of Months | 2279.95 | 1060.37 | 1676.29 | 935.35 | 830.35 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.384353E+09 | 0.396749E+10 | 0.126403E+10 | 0.00 | 0.126403E+10 | 0.00 | 0.00 |
February | 0.638776E+09 | 0.324914E+10 | 0.142694E+10 | 0.00 | 0.142694E+10 | 0.00 | 0.00 |
March | 0.136865E+10 | 0.283806E+10 | 0.199275E+10 | 0.00 | 0.199275E+10 | 0.00 | 0.00 |
April | 0.205008E+10 | 0.185592E+10 | 0.244662E+10 | 20946919.64 | 0.242567E+10 | 0.00 | 0.00 |
May | 0.286745E+10 | 0.142664E+10 | 0.274815E+10 | 0.177182E+09 | 0.257096E+10 | 0.00 | 0.00 |
June | 0.415639E+10 | 0.934908E+09 | 0.302190E+10 | 0.494529E+09 | 0.252738E+10 | 0.00 | 0.00 |
July | 0.423575E+10 | 0.665408E+09 | 0.286609E+10 | 0.238545E+09 | 0.262754E+10 | 0.00 | 0.00 |
August | 0.360699E+10 | 0.748149E+09 | 0.265878E+10 | 59524296.00 | 0.259925E+10 | 0.00 | 0.00 |
September | 0.240932E+10 | 0.125282E+10 | 0.205761E+10 | 528088.29 | 0.205708E+10 | 0.00 | 0.00 |
October | 0.121254E+10 | 0.224297E+10 | 0.158657E+10 | 0.00 | 0.158657E+10 | 0.00 | 0.00 |
November | 0.500658E+09 | 0.304018E+10 | 0.130391E+10 | 0.00 | 0.130391E+10 | 0.00 | 0.00 |
December | 0.151485E+09 | 0.412681E+10 | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.235824E+11 | 0.263485E+11 | 0.244492E+11 | 0.991255E+09 | 0.234580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151485E+09 | 0.665408E+09 | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.00 | 0.00 |
Maximum of Months | 0.423575E+10 | 0.412681E+10 | 0.302190E+10 | 0.494529E+09 | 0.262754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.208344E+10 | 0.244498E+10 | 0.233372E+10 | 0.130477E+10 | 0.102895E+10 | 0.00 | 0.00 |
February | 0.246783E+10 | 0.201956E+10 | 0.256103E+10 | 0.138066E+10 | 0.118036E+10 | 0.00 | 0.00 |
March | 0.400121E+10 | 0.177877E+10 | 0.374035E+10 | 0.212631E+10 | 0.161403E+10 | 0.00 | 0.00 |
April | 0.574475E+10 | 0.121459E+10 | 0.494524E+10 | 0.281727E+10 | 0.212797E+10 | 0.00 | 0.00 |
May | 0.596570E+10 | 0.960555E+09 | 0.487610E+10 | 0.277884E+10 | 0.209726E+10 | 0.00 | 0.00 |
June | 0.680983E+10 | 0.612264E+09 | 0.508724E+10 | 0.313397E+10 | 0.195326E+10 | 0.00 | 0.00 |
July | 0.677601E+10 | 0.440671E+09 | 0.486422E+10 | 0.278155E+10 | 0.208267E+10 | 0.00 | 0.00 |
August | 0.651313E+10 | 0.494680E+09 | 0.481347E+10 | 0.265375E+10 | 0.215972E+10 | 0.00 | 0.00 |
September | 0.498155E+10 | 0.801317E+09 | 0.387717E+10 | 0.216930E+10 | 0.170786E+10 | 0.00 | 0.00 |
October | 0.398315E+10 | 0.140635E+10 | 0.348434E+10 | 0.221067E+10 | 0.127367E+10 | 0.00 | 0.00 |
November | 0.260085E+10 | 0.191736E+10 | 0.263534E+10 | 0.154930E+10 | 0.108605E+10 | 0.00 | 0.00 |
December | 0.196525E+10 | 0.255690E+10 | 0.220655E+10 | 0.134289E+10 | 0.863668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.538927E+11 | 0.166480E+11 | 0.454248E+11 | 0.262493E+11 | 0.191755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196525E+10 | 0.440671E+09 | 0.220655E+10 | 0.130477E+10 | 0.863668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.680983E+10 | 0.255690E+10 | 0.508724E+10 | 0.313397E+10 | 0.215972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105881E+11 | 0.371890E+10 | 0.934484E+10 | 0.727157E+10 | 0.207327E+10 | 0.00 | 0.00 |
February | 0.954373E+10 | 0.310946E+10 | 0.826018E+10 | 0.603377E+10 | 0.222641E+10 | 0.00 | 0.00 |
March | 0.796998E+10 | 0.281806E+10 | 0.673908E+10 | 0.407418E+10 | 0.266490E+10 | 0.00 | 0.00 |
April | 0.623282E+10 | 0.197124E+10 | 0.508609E+10 | 0.208774E+10 | 0.299835E+10 | 0.00 | 0.00 |
May | 0.433413E+10 | 0.151044E+10 | 0.350508E+10 | 0.771049E+09 | 0.273403E+10 | 0.00 | 0.00 |
June | 0.413758E+10 | 0.979949E+09 | 0.286936E+10 | 0.353615E+09 | 0.251575E+10 | 0.00 | 0.00 |
July | 0.509090E+10 | 0.688476E+09 | 0.328092E+10 | 0.523930E+09 | 0.275699E+10 | 0.00 | 0.00 |
August | 0.670384E+10 | 0.792540E+09 | 0.451151E+10 | 0.146646E+10 | 0.304504E+10 | 0.00 | 0.00 |
September | 0.834231E+10 | 0.130032E+10 | 0.603719E+10 | 0.336651E+10 | 0.267068E+10 | 0.00 | 0.00 |
October | 0.106922E+11 | 0.221407E+10 | 0.853492E+10 | 0.628591E+10 | 0.224900E+10 | 0.00 | 0.00 |
November | 0.107207E+11 | 0.292586E+10 | 0.919962E+10 | 0.706067E+10 | 0.213895E+10 | 0.00 | 0.00 |
December | 0.115455E+11 | 0.379712E+10 | 0.101389E+11 | 0.836351E+10 | 0.177537E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.959018E+11 | 0.258264E+11 | 0.775077E+11 | 0.476589E+11 | 0.298488E+11 | 0.00 | 0.00 |
Minimum of Months | 0.413758E+10 | 0.688476E+09 | 0.286936E+10 | 0.353615E+09 | 0.177537E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115455E+11 | 0.379712E+10 | 0.101389E+11 | 0.836351E+10 | 0.304504E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232231E+10 | 0.260084E+10 | 0.240715E+10 | 0.137272E+10 | 0.103443E+10 | 0.00 | 0.00 |
February | 0.287309E+10 | 0.215014E+10 | 0.279892E+10 | 0.161685E+10 | 0.118207E+10 | 0.00 | 0.00 |
March | 0.375470E+10 | 0.190014E+10 | 0.346102E+10 | 0.184236E+10 | 0.161865E+10 | 0.00 | 0.00 |
April | 0.494783E+10 | 0.129872E+10 | 0.427480E+10 | 0.227506E+10 | 0.199974E+10 | 0.00 | 0.00 |
May | 0.512394E+10 | 0.101531E+10 | 0.418824E+10 | 0.215807E+10 | 0.203017E+10 | 0.00 | 0.00 |
June | 0.590692E+10 | 0.688000E+09 | 0.434495E+10 | 0.242443E+10 | 0.192052E+10 | 0.00 | 0.00 |
July | 0.574277E+10 | 0.475912E+09 | 0.404964E+10 | 0.198184E+10 | 0.206781E+10 | 0.00 | 0.00 |
August | 0.568261E+10 | 0.541260E+09 | 0.413802E+10 | 0.191400E+10 | 0.222402E+10 | 0.00 | 0.00 |
September | 0.472331E+10 | 0.862281E+09 | 0.361703E+10 | 0.190494E+10 | 0.171209E+10 | 0.00 | 0.00 |
October | 0.402535E+10 | 0.151558E+10 | 0.341940E+10 | 0.212528E+10 | 0.129412E+10 | 0.00 | 0.00 |
November | 0.264158E+10 | 0.199601E+10 | 0.259763E+10 | 0.152824E+10 | 0.106939E+10 | 0.00 | 0.00 |
December | 0.218477E+10 | 0.265979E+10 | 0.232130E+10 | 0.145570E+10 | 0.865599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.499292E+11 | 0.177040E+11 | 0.416181E+11 | 0.225995E+11 | 0.190186E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218477E+10 | 0.475912E+09 | 0.232130E+10 | 0.137272E+10 | 0.865599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.590692E+10 | 0.265979E+10 | 0.434495E+10 | 0.242443E+10 | 0.222402E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.365103E+09 | 0.417379E+10 | 0.126402E+10 | 0.00 | 0.126402E+10 | 0.00 | 0.00 |
February | 0.642756E+09 | 0.336009E+10 | 0.142693E+10 | 0.00 | 0.142693E+10 | 0.00 | 0.00 |
March | 0.141149E+10 | 0.287795E+10 | 0.199274E+10 | 0.00 | 0.199274E+10 | 0.00 | 0.00 |
April | 0.210502E+10 | 0.186911E+10 | 0.244661E+10 | 20946811.09 | 0.242566E+10 | 0.00 | 0.00 |
May | 0.292384E+10 | 0.142511E+10 | 0.274813E+10 | 0.177181E+09 | 0.257095E+10 | 0.00 | 0.00 |
June | 0.420464E+10 | 0.930781E+09 | 0.302189E+10 | 0.494526E+09 | 0.252736E+10 | 0.00 | 0.00 |
July | 0.427961E+10 | 0.655693E+09 | 0.286607E+10 | 0.238543E+09 | 0.262753E+10 | 0.00 | 0.00 |
August | 0.363138E+10 | 0.759144E+09 | 0.265876E+10 | 59523987.55 | 0.259924E+10 | 0.00 | 0.00 |
September | 0.240264E+10 | 0.132739E+10 | 0.205760E+10 | 528085.55 | 0.205707E+10 | 0.00 | 0.00 |
October | 0.117087E+10 | 0.243864E+10 | 0.158656E+10 | 0.00 | 0.158656E+10 | 0.00 | 0.00 |
November | 0.447135E+09 | 0.332459E+10 | 0.130390E+10 | 0.00 | 0.130390E+10 | 0.00 | 0.00 |
December | 0.129159E+09 | 0.442174E+10 | 0.107587E+10 | 0.00 | 0.107587E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.237136E+11 | 0.275640E+11 | 0.244491E+11 | 0.991250E+09 | 0.234578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129159E+09 | 0.655693E+09 | 0.107587E+10 | 0.00 | 0.107587E+10 | 0.00 | 0.00 |
Maximum of Months | 0.427961E+10 | 0.442174E+10 | 0.302189E+10 | 0.494526E+09 | 0.262753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205580E+10 | 0.261236E+10 | 0.233370E+10 | 0.130475E+10 | 0.102895E+10 | 0.00 | 0.00 |
February | 0.246651E+10 | 0.213115E+10 | 0.256101E+10 | 0.138065E+10 | 0.118036E+10 | 0.00 | 0.00 |
March | 0.402262E+10 | 0.186536E+10 | 0.374032E+10 | 0.212629E+10 | 0.161403E+10 | 0.00 | 0.00 |
April | 0.577063E+10 | 0.128513E+10 | 0.494520E+10 | 0.281724E+10 | 0.212796E+10 | 0.00 | 0.00 |
May | 0.599895E+10 | 0.101265E+10 | 0.487606E+10 | 0.277881E+10 | 0.209725E+10 | 0.00 | 0.00 |
June | 0.684177E+10 | 0.645015E+09 | 0.508720E+10 | 0.313394E+10 | 0.195326E+10 | 0.00 | 0.00 |
July | 0.680182E+10 | 0.470595E+09 | 0.486418E+10 | 0.278152E+10 | 0.208266E+10 | 0.00 | 0.00 |
August | 0.653290E+10 | 0.537704E+09 | 0.481344E+10 | 0.265373E+10 | 0.215971E+10 | 0.00 | 0.00 |
September | 0.498098E+10 | 0.882500E+09 | 0.387714E+10 | 0.216928E+10 | 0.170786E+10 | 0.00 | 0.00 |
October | 0.395626E+10 | 0.156479E+10 | 0.348431E+10 | 0.221065E+10 | 0.127366E+10 | 0.00 | 0.00 |
November | 0.255196E+10 | 0.213317E+10 | 0.263532E+10 | 0.154928E+10 | 0.108604E+10 | 0.00 | 0.00 |
December | 0.193382E+10 | 0.278275E+10 | 0.220654E+10 | 0.134287E+10 | 0.863664E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.539140E+11 | 0.179232E+11 | 0.454244E+11 | 0.262490E+11 | 0.191754E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193382E+10 | 0.470595E+09 | 0.220654E+10 | 0.130475E+10 | 0.863664E+09 | 0.00 | 0.00 |
Maximum of Months | 0.684177E+10 | 0.278275E+10 | 0.508720E+10 | 0.313394E+10 | 0.215971E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106188E+11 | 0.408085E+10 | 0.934494E+10 | 0.727165E+10 | 0.207329E+10 | 0.00 | 0.00 |
February | 0.960427E+10 | 0.336829E+10 | 0.826027E+10 | 0.603384E+10 | 0.222642E+10 | 0.00 | 0.00 |
March | 0.806027E+10 | 0.296348E+10 | 0.673914E+10 | 0.407423E+10 | 0.266492E+10 | 0.00 | 0.00 |
April | 0.631886E+10 | 0.203701E+10 | 0.508613E+10 | 0.208777E+10 | 0.299837E+10 | 0.00 | 0.00 |
May | 0.442750E+10 | 0.151103E+10 | 0.350510E+10 | 0.771058E+09 | 0.273404E+10 | 0.00 | 0.00 |
June | 0.419275E+10 | 0.973018E+09 | 0.286937E+10 | 0.353619E+09 | 0.251575E+10 | 0.00 | 0.00 |
July | 0.513075E+10 | 0.690737E+09 | 0.328094E+10 | 0.523936E+09 | 0.275701E+10 | 0.00 | 0.00 |
August | 0.673662E+10 | 0.835184E+09 | 0.451154E+10 | 0.146648E+10 | 0.304506E+10 | 0.00 | 0.00 |
September | 0.835915E+10 | 0.143353E+10 | 0.603725E+10 | 0.336655E+10 | 0.267070E+10 | 0.00 | 0.00 |
October | 0.106905E+11 | 0.248802E+10 | 0.853500E+10 | 0.628599E+10 | 0.224902E+10 | 0.00 | 0.00 |
November | 0.107118E+11 | 0.331770E+10 | 0.919972E+10 | 0.706076E+10 | 0.213896E+10 | 0.00 | 0.00 |
December | 0.115740E+11 | 0.423790E+10 | 0.101390E+11 | 0.836360E+10 | 0.177538E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.964253E+11 | 0.279367E+11 | 0.775084E+11 | 0.476595E+11 | 0.298489E+11 | 0.00 | 0.00 |
Minimum of Months | 0.419275E+10 | 0.690737E+09 | 0.286937E+10 | 0.353619E+09 | 0.177538E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115740E+11 | 0.423790E+10 | 0.101390E+11 | 0.836360E+10 | 0.304506E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232125E+10 | 0.278084E+10 | 0.240713E+10 | 0.137270E+10 | 0.103442E+10 | 0.00 | 0.00 |
February | 0.288843E+10 | 0.227446E+10 | 0.279890E+10 | 0.161683E+10 | 0.118207E+10 | 0.00 | 0.00 |
March | 0.378770E+10 | 0.198065E+10 | 0.346099E+10 | 0.184234E+10 | 0.161864E+10 | 0.00 | 0.00 |
April | 0.497605E+10 | 0.136466E+10 | 0.427477E+10 | 0.227504E+10 | 0.199973E+10 | 0.00 | 0.00 |
May | 0.515261E+10 | 0.105504E+10 | 0.418821E+10 | 0.215805E+10 | 0.203016E+10 | 0.00 | 0.00 |
June | 0.592709E+10 | 0.717781E+09 | 0.434492E+10 | 0.242441E+10 | 0.192051E+10 | 0.00 | 0.00 |
July | 0.576177E+10 | 0.497560E+09 | 0.404961E+10 | 0.198182E+10 | 0.206780E+10 | 0.00 | 0.00 |
August | 0.569084E+10 | 0.581306E+09 | 0.413799E+10 | 0.191398E+10 | 0.222401E+10 | 0.00 | 0.00 |
September | 0.470885E+10 | 0.948441E+09 | 0.361700E+10 | 0.190492E+10 | 0.171208E+10 | 0.00 | 0.00 |
October | 0.399827E+10 | 0.168143E+10 | 0.341937E+10 | 0.212525E+10 | 0.129412E+10 | 0.00 | 0.00 |
November | 0.261293E+10 | 0.221469E+10 | 0.259760E+10 | 0.152822E+10 | 0.106938E+10 | 0.00 | 0.00 |
December | 0.217839E+10 | 0.289280E+10 | 0.232128E+10 | 0.145568E+10 | 0.865595E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.500042E+11 | 0.189897E+11 | 0.416178E+11 | 0.225993E+11 | 0.190185E+11 | 0.00 | 0.00 |
Minimum of Months | 0.217839E+10 | 0.497560E+09 | 0.232128E+10 | 0.137270E+10 | 0.865595E+09 | 0.00 | 0.00 |
Maximum of Months | 0.592709E+10 | 0.289280E+10 | 0.434492E+10 | 0.242441E+10 | 0.222401E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343112E+09 | 0.422743E+10 | 0.126403E+10 | 0.00 | 0.126403E+10 | 0.00 | 0.00 |
February | 0.596348E+09 | 0.345843E+10 | 0.142694E+10 | 0.00 | 0.142694E+10 | 0.00 | 0.00 |
March | 0.131723E+10 | 0.302224E+10 | 0.199275E+10 | 0.00 | 0.199275E+10 | 0.00 | 0.00 |
April | 0.201052E+10 | 0.197176E+10 | 0.244662E+10 | 20946919.64 | 0.242567E+10 | 0.00 | 0.00 |
May | 0.284122E+10 | 0.149534E+10 | 0.274815E+10 | 0.177182E+09 | 0.257096E+10 | 0.00 | 0.00 |
June | 0.415666E+10 | 0.964491E+09 | 0.302190E+10 | 0.494529E+09 | 0.252738E+10 | 0.00 | 0.00 |
July | 0.424812E+10 | 0.681541E+09 | 0.286609E+10 | 0.238545E+09 | 0.262754E+10 | 0.00 | 0.00 |
August | 0.361297E+10 | 0.771642E+09 | 0.265878E+10 | 59524296.00 | 0.259925E+10 | 0.00 | 0.00 |
September | 0.239598E+10 | 0.131950E+10 | 0.205761E+10 | 528088.29 | 0.205708E+10 | 0.00 | 0.00 |
October | 0.117172E+10 | 0.240842E+10 | 0.158657E+10 | 0.00 | 0.158657E+10 | 0.00 | 0.00 |
November | 0.447524E+09 | 0.328780E+10 | 0.130391E+10 | 0.00 | 0.130391E+10 | 0.00 | 0.00 |
December | 0.126107E+09 | 0.441819E+10 | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.232675E+11 | 0.280268E+11 | 0.244492E+11 | 0.991255E+09 | 0.234580E+11 | 0.00 | 0.00 |
Minimum of Months | 0.126107E+09 | 0.681541E+09 | 0.107588E+10 | 0.00 | 0.107588E+10 | 0.00 | 0.00 |
Maximum of Months | 0.424812E+10 | 0.441819E+10 | 0.302190E+10 | 0.494529E+09 | 0.262754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203682E+10 | 0.259152E+10 | 0.233372E+10 | 0.130477E+10 | 0.102895E+10 | 0.00 | 0.00 |
February | 0.243095E+10 | 0.213811E+10 | 0.256103E+10 | 0.138066E+10 | 0.118036E+10 | 0.00 | 0.00 |
March | 0.397454E+10 | 0.187424E+10 | 0.374035E+10 | 0.212631E+10 | 0.161403E+10 | 0.00 | 0.00 |
April | 0.573343E+10 | 0.127346E+10 | 0.494524E+10 | 0.281727E+10 | 0.212797E+10 | 0.00 | 0.00 |
May | 0.596499E+10 | 0.100038E+10 | 0.487610E+10 | 0.277884E+10 | 0.209726E+10 | 0.00 | 0.00 |
June | 0.682093E+10 | 0.629751E+09 | 0.508724E+10 | 0.313397E+10 | 0.195326E+10 | 0.00 | 0.00 |
July | 0.679277E+10 | 0.449714E+09 | 0.486422E+10 | 0.278155E+10 | 0.208267E+10 | 0.00 | 0.00 |
August | 0.652670E+10 | 0.506960E+09 | 0.481347E+10 | 0.265375E+10 | 0.215972E+10 | 0.00 | 0.00 |
September | 0.498085E+10 | 0.834990E+09 | 0.387717E+10 | 0.216930E+10 | 0.170786E+10 | 0.00 | 0.00 |
October | 0.396312E+10 | 0.148857E+10 | 0.348434E+10 | 0.221067E+10 | 0.127367E+10 | 0.00 | 0.00 |
November | 0.255803E+10 | 0.204741E+10 | 0.263534E+10 | 0.154930E+10 | 0.108605E+10 | 0.00 | 0.00 |
December | 0.192529E+10 | 0.272495E+10 | 0.220655E+10 | 0.134289E+10 | 0.863668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.537084E+11 | 0.175601E+11 | 0.454248E+11 | 0.262493E+11 | 0.191755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192529E+10 | 0.449714E+09 | 0.220655E+10 | 0.130477E+10 | 0.863668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.682093E+10 | 0.272495E+10 | 0.508724E+10 | 0.313397E+10 | 0.215972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105264E+11 | 0.394663E+10 | 0.934484E+10 | 0.727157E+10 | 0.207327E+10 | 0.00 | 0.00 |
February | 0.949925E+10 | 0.329795E+10 | 0.826018E+10 | 0.603377E+10 | 0.222641E+10 | 0.00 | 0.00 |
March | 0.793100E+10 | 0.298239E+10 | 0.673908E+10 | 0.407418E+10 | 0.266490E+10 | 0.00 | 0.00 |
April | 0.621325E+10 | 0.208383E+10 | 0.508609E+10 | 0.208774E+10 | 0.299835E+10 | 0.00 | 0.00 |
May | 0.432047E+10 | 0.158659E+10 | 0.350508E+10 | 0.771049E+09 | 0.273403E+10 | 0.00 | 0.00 |
June | 0.414143E+10 | 0.101760E+10 | 0.286936E+10 | 0.353615E+09 | 0.251575E+10 | 0.00 | 0.00 |
July | 0.510535E+10 | 0.707569E+09 | 0.328092E+10 | 0.523930E+09 | 0.275699E+10 | 0.00 | 0.00 |
August | 0.671737E+10 | 0.818351E+09 | 0.451151E+10 | 0.146646E+10 | 0.304504E+10 | 0.00 | 0.00 |
September | 0.834077E+10 | 0.136147E+10 | 0.603719E+10 | 0.336651E+10 | 0.267068E+10 | 0.00 | 0.00 |
October | 0.106602E+11 | 0.234706E+10 | 0.853492E+10 | 0.628591E+10 | 0.224900E+10 | 0.00 | 0.00 |
November | 0.106649E+11 | 0.313065E+10 | 0.919962E+10 | 0.706067E+10 | 0.213895E+10 | 0.00 | 0.00 |
December | 0.114914E+11 | 0.404887E+10 | 0.101389E+11 | 0.836351E+10 | 0.177537E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.956117E+11 | 0.273290E+11 | 0.775077E+11 | 0.476589E+11 | 0.298488E+11 | 0.00 | 0.00 |
Minimum of Months | 0.414143E+10 | 0.707569E+09 | 0.286936E+10 | 0.353615E+09 | 0.177537E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114914E+11 | 0.404887E+10 | 0.101389E+11 | 0.836351E+10 | 0.304504E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229734E+10 | 0.276324E+10 | 0.240715E+10 | 0.137272E+10 | 0.103443E+10 | 0.00 | 0.00 |
February | 0.285194E+10 | 0.227997E+10 | 0.279892E+10 | 0.161685E+10 | 0.118207E+10 | 0.00 | 0.00 |
March | 0.373416E+10 | 0.200880E+10 | 0.346102E+10 | 0.184236E+10 | 0.161865E+10 | 0.00 | 0.00 |
April | 0.493308E+10 | 0.137027E+10 | 0.427480E+10 | 0.227506E+10 | 0.199974E+10 | 0.00 | 0.00 |
May | 0.511325E+10 | 0.106393E+10 | 0.418824E+10 | 0.215807E+10 | 0.203017E+10 | 0.00 | 0.00 |
June | 0.590963E+10 | 0.711490E+09 | 0.434495E+10 | 0.242443E+10 | 0.192052E+10 | 0.00 | 0.00 |
July | 0.575133E+10 | 0.488527E+09 | 0.404964E+10 | 0.198184E+10 | 0.206781E+10 | 0.00 | 0.00 |
August | 0.568805E+10 | 0.557294E+09 | 0.413802E+10 | 0.191400E+10 | 0.222402E+10 | 0.00 | 0.00 |
September | 0.471580E+10 | 0.903062E+09 | 0.361703E+10 | 0.190494E+10 | 0.171209E+10 | 0.00 | 0.00 |
October | 0.400721E+10 | 0.161177E+10 | 0.341940E+10 | 0.212528E+10 | 0.129412E+10 | 0.00 | 0.00 |
November | 0.261508E+10 | 0.214005E+10 | 0.259763E+10 | 0.152824E+10 | 0.106939E+10 | 0.00 | 0.00 |
December | 0.216446E+10 | 0.284010E+10 | 0.232130E+10 | 0.145570E+10 | 0.865599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.497813E+11 | 0.187385E+11 | 0.416181E+11 | 0.225995E+11 | 0.190186E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216446E+10 | 0.488527E+09 | 0.232130E+10 | 0.137272E+10 | 0.865599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.590963E+10 | 0.284010E+10 | 0.434495E+10 | 0.242443E+10 | 0.222402E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.521925E+10 | -0.450959E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -709660469.5 | 58.98 | 0.00 | 0.00 |
February | 0.476704E+10 | -0.413020E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -636835478.1 | 58.98 | 0.00 | 0.00 |
March | 0.546636E+10 | -0.476758E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698775212.2 | 58.98 | 0.00 | 0.00 |
April | 0.473293E+10 | -0.406350E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669428836.2 | 58.98 | 0.00 | 0.00 |
May | 0.474669E+10 | -0.405561E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691074227.9 | 58.98 | 0.00 | 0.00 |
June | 0.440703E+10 | -0.373901E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668020170.9 | 58.98 | 0.00 | 0.00 |
July | 0.403197E+10 | -0.334429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687682225.0 | 58.98 | 0.00 | 0.00 |
August | 0.434784E+10 | -0.365913E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688708017.3 | 58.98 | 0.00 | 0.00 |
September | 0.407397E+10 | -0.340832E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665656091.2 | 58.98 | 0.00 | 0.00 |
October | 0.444934E+10 | -0.375834E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691000247.1 | 58.98 | 0.00 | 0.00 |
November | 0.465999E+10 | -0.398543E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -674561780.7 | 58.98 | 0.00 | 0.00 |
December | 0.491559E+10 | -0.420832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -707261098.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.558180E+11 | -0.476293E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.818866E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.403197E+10 | -0.476758E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -709660469.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.546636E+10 | -0.334429E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -636835478.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.62 | 01-JAN-07:40 | 10402.03 | 37.34 | 288.67 | 285.83 | 2652.72 | 27.31 | 197.33 | 276.17 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:30 | 12769.17 | 37.45 | 272.17 | 273.67 | 2015.47 | 24.65 | 168.00 | 262.50 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:00 | 2237.67 | 17.66 | 11.00 | 328.50 | 1326.35 | 20.28 | 129.83 | 297.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:19 | 1779.24 | 17.90 | 0.00 | 350.17 | 1090.87 | 20.68 | 147.33 | 324.00 |
May | 378.00 | 0.64 | 0.62 | 01-MAY-05:00 | 1353.96 | 17.24 | 0.00 | 367.00 | 843.80 | 20.07 | 86.33 | 332.17 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:40 | 1072.79 | 16.29 | 0.00 | 366.83 | 674.03 | 19.21 | 66.83 | 317.00 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:19 | 1306.02 | 17.05 | 0.00 | 371.83 | 803.96 | 19.93 | 101.33 | 330.50 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1647.96 | 17.65 | 0.00 | 369.83 | 996.12 | 20.46 | 169.67 | 338.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 2196.04 | 18.17 | 16.50 | 326.17 | 1228.55 | 20.26 | 123.67 | 299.33 |
October | 329.00 | 0.63 | 0.62 | 01-OCT-06:40 | 6173.29 | 27.49 | 181.17 | 317.33 | 1684.43 | 20.55 | 93.00 | 302.67 |
November | 284.17 | 0.62 | 0.62 | 01-NOV-06:49 | 11726.35 | 37.83 | 273.17 | 282.67 | 2643.76 | 27.42 | 169.67 | 273.17 |
December | 265.67 | 0.63 | 0.62 | 01-DEC-07:49 | 11899.45 | 39.78 | 263.50 | 269.17 | 3894.53 | 30.68 | 171.17 | 261.00 |
Annual Sum or Average | 4149.83 | 0.63 | 4737.79 | 23.84 | 1306.17 | 3909.00 | 1531.27 | 22.16 | 1624.17 | 3614.67 | ||
Minimum of Months | 265.67 | 0.62 | 0.62 | 1072.79 | 16.29 | 0.00 | 269.17 | 674.03 | 19.21 | 66.83 | 261.00 | |
Maximum of Months | 412.83 | 0.64 | 0.62 | 12769.17 | 39.78 | 288.67 | 371.83 | 3894.53 | 30.68 | 197.33 | 338.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-07:40 | 2467.61 | 20.29 | 86.33 | 256.67 | 1458.25 | 23.28 | 94.50 | 228.00 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:19 | 3326.25 | 22.22 | 96.83 | 261.67 | 1848.16 | 23.25 | 93.33 | 232.50 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:49 | 3228.02 | 19.67 | 86.17 | 321.33 | 1810.37 | 22.56 | 86.33 | 290.50 |
April | 381.83 | 0.63 | 0.62 | 01-APR-05:00 | 4740.27 | 21.62 | 114.83 | 354.33 | 1824.94 | 21.27 | 54.83 | 334.00 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-05:49 | 3665.95 | 18.95 | 81.00 | 371.17 | 2120.28 | 21.77 | 66.33 | 343.17 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:10 | 3657.94 | 19.78 | 111.00 | 385.33 | 2072.22 | 21.40 | 82.67 | 350.33 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:10 | 3522.27 | 18.99 | 84.83 | 380.00 | 1933.26 | 21.78 | 74.17 | 349.00 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:40 | 4373.44 | 21.23 | 118.83 | 377.50 | 1781.60 | 22.17 | 76.17 | 354.33 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3747.70 | 21.11 | 106.67 | 327.67 | 2096.56 | 22.70 | 88.50 | 302.17 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:30 | 3261.14 | 19.56 | 82.67 | 295.67 | 1885.90 | 22.69 | 79.83 | 271.17 |
November | 284.17 | 0.64 | 0.62 | 01-NOV-06:49 | 2696.50 | 20.75 | 77.00 | 259.33 | 1452.10 | 22.22 | 72.17 | 233.17 |
December | 265.67 | 0.65 | 0.62 | 01-DEC-07:49 | 2849.94 | 20.62 | 80.33 | 239.17 | 1775.60 | 23.36 | 82.00 | 200.67 |
Annual Sum or Average | 4149.83 | 0.63 | 3529.15 | 20.35 | 1126.50 | 3829.83 | 1855.86 | 22.29 | 950.83 | 3489.00 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2467.61 | 18.95 | 77.00 | 239.17 | 1452.10 | 21.27 | 54.83 | 200.67 | |
Maximum of Months | 412.83 | 0.65 | 0.62 | 4740.27 | 22.22 | 118.83 | 385.33 | 2120.28 | 23.36 | 94.50 | 354.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.62 | 01-JAN-08:30 | 598.33 | 14.27 | 0.00 | 233.33 | 386.26 | 17.54 | 0.00 | 172.33 |
February | 282.00 | 0.64 | 0.62 | 01-FEB-07:40 | 701.16 | 15.21 | 0.00 | 247.00 | 466.05 | 18.39 | 0.00 | 194.00 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:00 | 839.97 | 16.03 | 0.00 | 312.83 | 528.21 | 18.95 | 7.00 | 260.17 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:10 | 1054.98 | 17.63 | 0.00 | 359.67 | 675.51 | 20.40 | 64.50 | 337.00 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-05:00 | 1237.50 | 17.79 | 0.00 | 387.67 | 718.86 | 20.63 | 102.33 | 353.67 |
June | 412.83 | 0.62 | 0.62 | 01-JUN-05:19 | 1277.84 | 19.04 | 49.83 | 400.83 | 701.49 | 21.33 | 119.33 | 378.33 |
July | 395.33 | 0.62 | 0.62 | 01-JUL-06:19 | 1259.19 | 19.12 | 35.00 | 392.83 | 738.19 | 21.31 | 122.17 | 370.00 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:49 | 1120.34 | 17.70 | 0.00 | 381.17 | 715.63 | 20.48 | 119.17 | 364.17 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 884.63 | 16.58 | 0.00 | 322.00 | 570.67 | 19.49 | 19.33 | 282.17 |
October | 329.00 | 0.65 | 0.62 | 01-OCT-06:00 | 637.15 | 14.73 | 0.00 | 276.83 | 439.01 | 17.89 | 0.00 | 221.83 |
November | 284.17 | 0.64 | 0.62 | 01-NOV-07:10 | 630.22 | 14.97 | 0.00 | 246.33 | 423.53 | 18.25 | 0.00 | 192.00 |
December | 265.67 | 0.66 | 0.62 | 01-DEC-07:00 | 520.79 | 13.40 | 0.00 | 219.83 | 363.82 | 16.87 | 0.00 | 150.17 |
Annual Sum or Average | 4149.83 | 0.63 | 933.08 | 16.62 | 84.83 | 3780.33 | 579.21 | 19.49 | 553.83 | 3275.83 | ||
Minimum of Months | 265.67 | 0.62 | 0.62 | 520.79 | 13.40 | 0.00 | 219.83 | 363.82 | 16.87 | 0.00 | 150.17 | |
Maximum of Months | 412.83 | 0.66 | 0.62 | 1277.84 | 19.12 | 49.83 | 400.83 | 738.19 | 21.33 | 122.17 | 378.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-08:30 | 2237.86 | 20.54 | 84.83 | 262.67 | 1119.32 | 21.46 | 67.83 | 227.83 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:49 | 3132.09 | 20.45 | 75.00 | 259.50 | 1809.46 | 23.42 | 86.33 | 230.00 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-07:10 | 3481.89 | 20.90 | 105.17 | 322.00 | 1306.12 | 20.55 | 51.17 | 290.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:30 | 4224.92 | 20.98 | 110.33 | 356.17 | 1741.55 | 21.05 | 51.00 | 336.50 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-06:10 | 3024.73 | 16.40 | 46.67 | 381.50 | 1759.88 | 17.90 | 0.00 | 361.00 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:49 | 3344.20 | 12.60 | 0.00 | 378.83 | 1918.21 | 16.92 | 0.00 | 349.67 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:30 | 3205.07 | 13.74 | 3.67 | 380.50 | 1750.92 | 17.71 | 0.00 | 351.83 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-06:10 | 3093.98 | 17.41 | 62.50 | 370.50 | 1656.92 | 18.48 | 5.17 | 348.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:30 | 3594.44 | 20.99 | 107.67 | 329.00 | 1386.70 | 20.93 | 60.17 | 303.67 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:00 | 3174.45 | 19.78 | 86.17 | 297.17 | 1669.25 | 22.02 | 69.50 | 269.33 |
November | 284.17 | 0.63 | 0.62 | 01-NOV-07:10 | 3180.37 | 22.96 | 101.67 | 270.83 | 1260.13 | 22.46 | 64.67 | 241.50 |
December | 265.67 | 0.64 | 0.62 | 01-DEC-08:09 | 2766.59 | 21.15 | 85.17 | 245.33 | 1593.84 | 24.00 | 82.67 | 214.67 |
Annual Sum or Average | 4149.83 | 0.63 | 3235.11 | 18.67 | 868.83 | 3854.00 | 1597.01 | 20.28 | 538.50 | 3525.17 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2237.86 | 12.60 | 0.00 | 245.33 | 1119.32 | 16.92 | 0.00 | 214.67 | |
Maximum of Months | 412.83 | 0.64 | 0.62 | 4224.92 | 22.96 | 110.33 | 381.50 | 1918.21 | 24.00 | 86.33 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.62 | 01-JAN-07:40 | 10196.66 | 37.04 | 288.33 | 284.00 | 2488.87 | 25.07 | 127.17 | 274.67 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:30 | 12567.59 | 37.23 | 271.67 | 272.50 | 1858.52 | 22.14 | 79.67 | 261.50 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:00 | 2102.30 | 13.90 | 10.67 | 326.83 | 1225.35 | 17.69 | 10.17 | 293.17 |
April | 381.83 | 0.64 | 0.62 | 01-APR-06:19 | 1682.69 | 14.56 | 0.00 | 347.67 | 1025.16 | 18.56 | 7.17 | 320.83 |
May | 378.00 | 0.64 | 0.62 | 01-MAY-05:00 | 1291.76 | 13.94 | 0.00 | 365.33 | 805.81 | 17.96 | 0.00 | 328.17 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:40 | 1029.16 | 12.85 | 0.00 | 360.67 | 649.33 | 16.99 | 0.00 | 312.17 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:19 | 1248.97 | 13.66 | 0.00 | 368.33 | 770.44 | 17.73 | 1.17 | 327.50 |
August | 408.83 | 0.64 | 0.62 | 01-AUG-05:00 | 1564.62 | 14.28 | 0.00 | 368.33 | 942.01 | 18.27 | 1.50 | 335.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 2076.89 | 14.66 | 16.50 | 324.67 | 1141.08 | 17.85 | 9.50 | 296.83 |
October | 329.00 | 0.63 | 0.62 | 01-OCT-06:40 | 6005.79 | 25.45 | 181.17 | 316.50 | 1547.71 | 17.89 | 18.33 | 301.33 |
November | 284.17 | 0.63 | 0.62 | 01-NOV-06:49 | 11511.74 | 37.56 | 273.17 | 280.67 | 2472.29 | 25.13 | 112.83 | 272.33 |
December | 265.67 | 0.63 | 0.62 | 01-DEC-07:49 | 11621.12 | 39.15 | 259.67 | 267.83 | 3696.95 | 28.77 | 146.67 | 259.83 |
Annual Sum or Average | 4149.83 | 0.63 | 4609.06 | 21.36 | 1301.17 | 3883.33 | 1436.86 | 19.87 | 514.17 | 3583.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 1029.16 | 12.85 | 0.00 | 267.83 | 649.33 | 16.99 | 0.00 | 259.83 | |
Maximum of Months | 412.83 | 0.64 | 0.62 | 12567.59 | 39.15 | 288.33 | 368.33 | 3696.95 | 28.77 | 146.67 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-07:40 | 2401.81 | 19.80 | 85.83 | 253.67 | 1406.93 | 23.08 | 90.50 | 224.17 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:19 | 3024.95 | 19.72 | 74.33 | 259.17 | 1789.07 | 23.06 | 86.67 | 229.17 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:49 | 3134.17 | 19.18 | 85.17 | 317.83 | 1736.44 | 22.38 | 79.17 | 287.83 |
April | 381.83 | 0.63 | 0.62 | 01-APR-05:00 | 4616.05 | 21.23 | 114.83 | 351.50 | 1728.65 | 21.10 | 54.83 | 330.33 |
May | 378.00 | 0.64 | 0.62 | 01-MAY-05:49 | 3544.00 | 18.55 | 81.00 | 369.50 | 2032.42 | 21.61 | 66.33 | 339.83 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:19 | 3351.99 | 17.63 | 83.83 | 380.50 | 1991.04 | 21.25 | 82.83 | 347.33 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:10 | 3414.89 | 18.58 | 84.83 | 378.00 | 1841.80 | 21.52 | 71.00 | 346.67 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:40 | 4260.63 | 20.84 | 118.83 | 376.00 | 1638.34 | 20.97 | 59.83 | 350.83 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3657.99 | 20.71 | 106.67 | 325.50 | 2023.57 | 22.52 | 85.83 | 299.83 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:30 | 3174.80 | 19.13 | 82.67 | 293.50 | 1813.78 | 22.51 | 76.50 | 268.67 |
November | 284.17 | 0.64 | 0.62 | 01-NOV-06:49 | 2613.96 | 20.31 | 77.00 | 257.50 | 1387.53 | 22.01 | 67.50 | 230.83 |
December | 265.67 | 0.65 | 0.62 | 01-DEC-07:49 | 2781.07 | 20.20 | 80.33 | 236.67 | 1720.82 | 23.16 | 78.00 | 198.00 |
Annual Sum or Average | 4149.83 | 0.63 | 3396.96 | 19.62 | 1075.33 | 3799.33 | 1774.12 | 22.00 | 899.00 | 3453.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2401.81 | 17.63 | 74.33 | 236.67 | 1387.53 | 20.97 | 54.83 | 198.00 | |
Maximum of Months | 412.83 | 0.65 | 0.62 | 4616.05 | 21.23 | 118.83 | 380.50 | 2032.42 | 23.16 | 90.50 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.62 | 01-JAN-08:30 | 573.75 | 10.76 | 0.00 | 227.00 | 373.81 | 15.14 | 0.00 | 165.00 |
February | 282.00 | 0.64 | 0.62 | 01-FEB-07:49 | 672.86 | 11.90 | 0.00 | 243.67 | 451.92 | 16.19 | 0.00 | 188.67 |
March | 351.33 | 0.64 | 0.62 | 01-MAR-06:00 | 807.69 | 12.77 | 0.00 | 309.17 | 511.90 | 16.86 | 0.00 | 255.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:10 | 1013.25 | 14.69 | 0.00 | 358.50 | 654.22 | 18.72 | 2.67 | 335.33 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-05:00 | 1191.68 | 14.53 | 0.00 | 386.83 | 694.30 | 18.65 | 19.00 | 349.83 |
June | 412.83 | 0.62 | 0.62 | 01-JUN-05:19 | 1233.36 | 15.93 | 49.17 | 396.67 | 657.72 | 18.00 | 7.67 | 370.83 |
July | 395.33 | 0.62 | 0.62 | 01-JUL-06:19 | 1212.79 | 16.07 | 35.00 | 392.00 | 712.74 | 19.31 | 27.67 | 367.33 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:49 | 1094.89 | 14.57 | 0.00 | 381.00 | 692.14 | 18.63 | 4.50 | 361.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 850.14 | 13.50 | 0.00 | 320.17 | 553.37 | 17.58 | 0.00 | 279.17 |
October | 329.00 | 0.65 | 0.62 | 01-OCT-06:00 | 612.88 | 11.54 | 0.00 | 272.00 | 427.27 | 15.84 | 0.00 | 216.00 |
November | 284.17 | 0.65 | 0.62 | 01-NOV-07:10 | 603.42 | 11.65 | 0.00 | 242.00 | 410.03 | 16.02 | 0.00 | 186.00 |
December | 265.67 | 0.66 | 0.62 | 01-DEC-07:00 | 498.72 | 10.01 | 0.00 | 213.83 | 352.90 | 14.48 | 0.00 | 143.17 |
Annual Sum or Average | 4149.83 | 0.64 | 899.12 | 13.42 | 84.17 | 3742.83 | 558.62 | 17.32 | 61.50 | 3218.50 | ||
Minimum of Months | 265.67 | 0.62 | 0.62 | 498.72 | 10.01 | 0.00 | 213.83 | 352.90 | 14.48 | 0.00 | 143.17 | |
Maximum of Months | 412.83 | 0.66 | 0.62 | 1233.36 | 16.07 | 49.17 | 396.67 | 712.74 | 19.31 | 27.67 | 370.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-08:30 | 2174.07 | 20.20 | 84.83 | 258.50 | 1069.56 | 21.37 | 67.00 | 225.50 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:00 | 3045.36 | 20.09 | 75.00 | 256.00 | 1742.55 | 23.32 | 84.33 | 227.33 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-07:10 | 3400.38 | 20.54 | 105.17 | 320.17 | 1241.98 | 20.42 | 50.33 | 286.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:30 | 4124.40 | 20.60 | 110.33 | 354.33 | 1580.86 | 20.90 | 51.00 | 330.50 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-06:10 | 2925.77 | 15.97 | 46.50 | 379.50 | 1689.23 | 17.72 | 0.00 | 358.00 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:49 | 3252.99 | 12.14 | 0.00 | 375.67 | 1847.40 | 16.74 | 0.00 | 346.17 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:30 | 3107.89 | 13.29 | 3.67 | 378.67 | 1681.28 | 17.53 | 0.00 | 349.17 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-06:10 | 2992.00 | 16.99 | 62.33 | 368.83 | 1583.04 | 18.31 | 5.17 | 346.17 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:30 | 3507.64 | 20.63 | 107.67 | 326.17 | 1306.05 | 20.64 | 57.17 | 300.67 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:00 | 3033.62 | 19.06 | 82.17 | 294.83 | 1491.90 | 20.59 | 54.67 | 265.33 |
November | 284.17 | 0.63 | 0.62 | 01-NOV-07:10 | 2861.33 | 20.31 | 78.67 | 266.67 | 1201.99 | 22.37 | 63.83 | 237.67 |
December | 265.67 | 0.65 | 0.62 | 01-DEC-08:09 | 2636.31 | 20.19 | 80.17 | 243.00 | 1540.69 | 23.92 | 82.17 | 212.33 |
Annual Sum or Average | 4149.83 | 0.63 | 3122.17 | 18.05 | 836.50 | 3822.33 | 1512.81 | 20.03 | 515.67 | 3485.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2174.07 | 12.14 | 0.00 | 243.00 | 1069.56 | 16.74 | 0.00 | 212.33 | |
Maximum of Months | 412.83 | 0.65 | 0.62 | 4124.40 | 20.63 | 110.33 | 379.50 | 1847.40 | 23.92 | 84.33 | 358.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.62 | 01-JAN-07:40 | 10196.67 | 37.04 | 288.33 | 284.00 | 2488.80 | 25.07 | 127.17 | 274.67 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:30 | 12567.56 | 37.23 | 271.67 | 272.50 | 1858.44 | 22.14 | 79.67 | 261.50 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:00 | 2102.24 | 13.90 | 10.67 | 326.83 | 1225.28 | 17.70 | 10.17 | 293.17 |
April | 381.83 | 0.64 | 0.62 | 01-APR-06:19 | 1682.64 | 14.56 | 0.00 | 347.67 | 1025.10 | 18.56 | 7.17 | 320.83 |
May | 378.00 | 0.64 | 0.62 | 01-MAY-05:00 | 1291.73 | 13.95 | 0.00 | 365.33 | 805.77 | 17.96 | 0.00 | 328.17 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:40 | 1029.14 | 12.86 | 0.00 | 360.67 | 649.29 | 16.99 | 0.00 | 312.17 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:19 | 1248.94 | 13.66 | 0.00 | 368.33 | 770.40 | 17.73 | 1.17 | 327.50 |
August | 408.83 | 0.64 | 0.62 | 01-AUG-05:00 | 1564.57 | 14.28 | 0.00 | 368.33 | 941.96 | 18.27 | 1.50 | 335.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 2076.83 | 14.66 | 16.50 | 324.67 | 1141.02 | 17.85 | 9.50 | 296.83 |
October | 329.00 | 0.63 | 0.62 | 01-OCT-06:40 | 6005.75 | 25.45 | 181.17 | 316.50 | 1547.65 | 17.89 | 18.33 | 301.33 |
November | 284.17 | 0.63 | 0.62 | 01-NOV-06:49 | 11511.75 | 37.56 | 273.17 | 280.67 | 2472.21 | 25.13 | 112.83 | 272.33 |
December | 265.67 | 0.63 | 0.62 | 01-DEC-07:49 | 11621.17 | 39.15 | 259.67 | 267.83 | 3696.88 | 28.77 | 146.67 | 259.83 |
Annual Sum or Average | 4149.83 | 0.63 | 4609.04 | 21.36 | 1301.17 | 3883.33 | 1436.80 | 19.88 | 514.17 | 3583.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 1029.14 | 12.86 | 0.00 | 267.83 | 649.29 | 16.99 | 0.00 | 259.83 | |
Maximum of Months | 412.83 | 0.64 | 0.62 | 12567.56 | 39.15 | 288.33 | 368.33 | 3696.88 | 28.77 | 146.67 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-07:40 | 2401.81 | 19.80 | 85.83 | 253.67 | 1406.89 | 23.08 | 90.50 | 224.17 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:19 | 3024.95 | 19.72 | 74.33 | 259.17 | 1789.03 | 23.06 | 86.67 | 229.17 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-06:49 | 3134.16 | 19.18 | 85.17 | 317.83 | 1736.39 | 22.38 | 79.17 | 287.83 |
April | 381.83 | 0.63 | 0.62 | 01-APR-05:00 | 4616.05 | 21.23 | 114.83 | 351.50 | 1728.59 | 21.10 | 54.83 | 330.33 |
May | 378.00 | 0.64 | 0.62 | 01-MAY-05:49 | 3544.01 | 18.55 | 81.00 | 369.50 | 2032.36 | 21.61 | 66.33 | 339.83 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:19 | 3351.98 | 17.64 | 83.83 | 380.50 | 1991.00 | 21.25 | 82.83 | 347.33 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:10 | 3414.88 | 18.58 | 84.83 | 378.00 | 1841.75 | 21.52 | 71.00 | 346.67 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:40 | 4260.63 | 20.84 | 118.83 | 376.00 | 1638.28 | 20.97 | 59.83 | 350.83 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3657.99 | 20.71 | 106.67 | 325.50 | 2023.52 | 22.52 | 85.83 | 299.83 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:30 | 3174.81 | 19.13 | 82.67 | 293.50 | 1813.75 | 22.51 | 76.50 | 268.67 |
November | 284.17 | 0.64 | 0.62 | 01-NOV-06:49 | 2613.98 | 20.32 | 77.00 | 257.50 | 1387.50 | 22.01 | 67.50 | 230.83 |
December | 265.67 | 0.65 | 0.62 | 01-DEC-07:49 | 2781.08 | 20.20 | 80.33 | 236.67 | 1720.79 | 23.16 | 78.00 | 198.00 |
Annual Sum or Average | 4149.83 | 0.63 | 3396.96 | 19.62 | 1075.33 | 3799.33 | 1774.08 | 22.00 | 899.00 | 3453.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2401.81 | 17.64 | 74.33 | 236.67 | 1387.50 | 20.97 | 54.83 | 198.00 | |
Maximum of Months | 412.83 | 0.65 | 0.62 | 4616.05 | 21.23 | 118.83 | 380.50 | 2032.36 | 23.16 | 90.50 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.65 | 0.62 | 01-JAN-08:30 | 573.75 | 10.76 | 0.00 | 227.00 | 373.79 | 15.14 | 0.00 | 164.83 |
February | 282.00 | 0.64 | 0.62 | 01-FEB-07:49 | 672.86 | 11.90 | 0.00 | 243.67 | 451.90 | 16.19 | 0.00 | 188.50 |
March | 351.33 | 0.64 | 0.62 | 01-MAR-06:00 | 807.68 | 12.77 | 0.00 | 309.17 | 511.87 | 16.86 | 0.00 | 255.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:10 | 1013.24 | 14.70 | 0.00 | 358.50 | 654.19 | 18.72 | 2.67 | 335.33 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-05:00 | 1191.68 | 14.54 | 0.00 | 386.83 | 694.27 | 18.65 | 19.00 | 349.83 |
June | 412.83 | 0.62 | 0.62 | 01-JUN-05:19 | 1233.35 | 15.93 | 49.17 | 396.67 | 657.69 | 18.00 | 7.67 | 370.83 |
July | 395.33 | 0.62 | 0.62 | 01-JUL-06:19 | 1212.78 | 16.07 | 35.00 | 392.00 | 712.70 | 19.31 | 27.67 | 367.33 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-05:49 | 1094.88 | 14.57 | 0.00 | 381.00 | 692.11 | 18.63 | 4.50 | 361.50 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:10 | 850.13 | 13.50 | 0.00 | 320.17 | 553.34 | 17.58 | 0.00 | 279.17 |
October | 329.00 | 0.65 | 0.62 | 01-OCT-06:00 | 612.89 | 11.54 | 0.00 | 272.00 | 427.25 | 15.84 | 0.00 | 216.00 |
November | 284.17 | 0.65 | 0.62 | 01-NOV-07:10 | 603.42 | 11.66 | 0.00 | 242.00 | 410.02 | 16.02 | 0.00 | 186.00 |
December | 265.67 | 0.66 | 0.62 | 01-DEC-07:00 | 498.73 | 10.02 | 0.00 | 213.83 | 352.89 | 14.48 | 0.00 | 143.17 |
Annual Sum or Average | 4149.83 | 0.64 | 899.11 | 13.42 | 84.17 | 3742.83 | 558.60 | 17.32 | 61.50 | 3218.17 | ||
Minimum of Months | 265.67 | 0.62 | 0.62 | 498.73 | 10.02 | 0.00 | 213.83 | 352.89 | 14.48 | 0.00 | 143.17 | |
Maximum of Months | 412.83 | 0.66 | 0.62 | 1233.35 | 16.07 | 49.17 | 396.67 | 712.70 | 19.31 | 27.67 | 370.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.62 | 01-JAN-08:30 | 2174.07 | 20.20 | 84.83 | 258.50 | 1069.52 | 21.37 | 67.00 | 225.50 |
February | 282.00 | 0.63 | 0.62 | 01-FEB-07:00 | 3045.36 | 20.09 | 75.00 | 256.00 | 1742.51 | 23.32 | 84.33 | 227.33 |
March | 351.33 | 0.63 | 0.62 | 01-MAR-07:10 | 3400.36 | 20.54 | 105.17 | 320.17 | 1241.93 | 20.42 | 50.33 | 286.67 |
April | 381.83 | 0.63 | 0.62 | 01-APR-06:30 | 4124.40 | 20.60 | 110.33 | 354.33 | 1580.81 | 20.91 | 51.00 | 330.50 |
May | 378.00 | 0.63 | 0.62 | 01-MAY-06:10 | 2925.76 | 15.98 | 46.50 | 379.50 | 1689.18 | 17.72 | 0.00 | 358.00 |
June | 412.83 | 0.63 | 0.62 | 01-JUN-05:49 | 3252.98 | 12.14 | 0.00 | 375.83 | 1847.36 | 16.74 | 0.00 | 346.17 |
July | 395.33 | 0.63 | 0.62 | 01-JUL-06:30 | 3107.88 | 13.29 | 3.67 | 378.67 | 1681.22 | 17.53 | 0.00 | 349.17 |
August | 408.83 | 0.63 | 0.62 | 01-AUG-06:10 | 2991.99 | 16.99 | 62.33 | 368.83 | 1582.98 | 18.31 | 5.17 | 346.17 |
September | 359.33 | 0.63 | 0.62 | 01-SEP-06:30 | 3507.64 | 20.63 | 107.67 | 326.17 | 1306.00 | 20.64 | 57.17 | 300.67 |
October | 329.00 | 0.64 | 0.62 | 01-OCT-06:00 | 3033.63 | 19.06 | 82.17 | 294.83 | 1491.86 | 20.59 | 54.67 | 265.33 |
November | 284.17 | 0.63 | 0.62 | 01-NOV-07:10 | 2861.34 | 20.31 | 78.67 | 266.67 | 1201.96 | 22.37 | 63.83 | 237.67 |
December | 265.67 | 0.65 | 0.62 | 01-DEC-08:09 | 2636.32 | 20.20 | 80.17 | 243.00 | 1540.67 | 23.92 | 82.33 | 212.33 |
Annual Sum or Average | 4149.83 | 0.63 | 3122.17 | 18.05 | 836.50 | 3822.50 | 1512.77 | 20.03 | 515.83 | 3485.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.62 | 2174.07 | 12.14 | 0.00 | 243.00 | 1069.52 | 16.74 | 0.00 | 212.33 | |
Maximum of Months | 412.83 | 0.65 | 0.62 | 4124.40 | 20.63 | 110.33 | 379.50 | 1847.36 | 23.92 | 84.33 | 358.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.284877E+10 | 11237.43 | 19-JAN-12:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217512E+10 | 11241.71 | 17-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167022E+10 | 11258.64 | 24-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.873890E+09 | 11212.80 | 20-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.545973E+09 | 11348.31 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89826392.18 | 11298.40 | 09-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5986895.69 | 3550.63 | 31-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65597711.20 | 9832.68 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.774164E+09 | 11375.29 | 19-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111957E+10 | 11277.57 | 01-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258387E+10 | 11202.88 | 29-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284877E+10 | 11375.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.829970E+09 | 7710.83 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.478026E+09 | 7710.83 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114154E+09 | 7710.83 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 116741.75 | 778.28 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13821432.42 | 7710.83 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29919007.09 | 7710.83 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.618343E+09 | 7710.83 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.829970E+09 | 7710.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134745E+10 | 9194.49 | 12-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944059E+09 | 9196.37 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.269701E+09 | 9182.22 | 15-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11065874.20 | 5948.54 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10418694.59 | 9139.55 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109050E+09 | 9161.32 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111498E+10 | 9195.63 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134745E+10 | 9196.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.976073E+09 | 7710.77 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.629840E+09 | 7710.77 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255490E+09 | 7710.77 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7334420.33 | 2611.01 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1820560.52 | 2265.72 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25207655.09 | 7710.77 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73860098.91 | 7710.77 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796372E+09 | 7710.77 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.976073E+09 | 7710.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 42819720.39 | 22069.48 | 17-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19670499.71 | 22069.48 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23200023.87 | 22069.48 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85690243.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42819720.39 | 22069.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623586E+09 | 12195.01 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303824E+09 | 12188.56 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88227318.72 | 12147.70 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4412313.61 | 5226.77 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3149.19 | 20.99 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34764167.28 | 12154.93 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53882091.61 | 12113.40 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492744E+09 | 12193.06 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.623586E+09 | 12195.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109084E+10 | 8204.99 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561919E+09 | 8204.99 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136628E+09 | 8204.99 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1565304.23 | 3358.29 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75136038.80 | 8204.99 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224002E+09 | 8204.99 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990955E+09 | 8204.99 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109084E+10 | 8204.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123391E+10 | 9960.38 | 19-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694569E+09 | 9903.00 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139862E+09 | 9838.79 | 03-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2934580.94 | 4583.98 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44442544.40 | 9826.92 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203176E+09 | 9873.07 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126531E+10 | 9906.00 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126531E+10 | 9960.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129755E+10 | 8503.07 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.777659E+09 | 8503.07 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.293147E+09 | 8503.07 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27556889.79 | 5553.60 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6003425.45 | 3333.80 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17090.75 | 85.45 | 09-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111256E+09 | 8503.07 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345905E+09 | 8503.07 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127898E+10 | 8503.07 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129755E+10 | 8503.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121538E+10 | 35250.12 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594605E+09 | 35313.89 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49788916.85 | 34692.42 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15930166.71 | 34754.57 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146516E+09 | 35211.97 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112948E+10 | 35290.96 | 27-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121538E+10 | 35313.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171367E+10 | 13872.91 | 20-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106447E+10 | 13847.15 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.534462E+09 | 13774.26 | 15-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112033E+09 | 13568.58 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29227450.38 | 8936.14 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1642422.10 | 2757.80 | 09-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216319E+09 | 13738.35 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470092E+09 | 13829.30 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149834E+10 | 13893.86 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.564026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171367E+10 | 13893.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.197046E+10 | 10549.75 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117467E+10 | 10549.75 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.469101E+09 | 10549.75 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36879624.27 | 7246.86 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3918159.34 | 2631.12 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237238E+09 | 10549.75 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.693508E+09 | 10549.75 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188787E+10 | 10549.75 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.647364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197046E+10 | 10549.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.303160E+10 | 11542.25 | 13-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196663E+10 | 11549.93 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745154E+09 | 11445.15 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105416E+09 | 11385.23 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11731695.93 | 7749.07 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.319884E+09 | 11531.07 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109283E+10 | 11512.58 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319168E+10 | 11531.87 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.319168E+10 | 11549.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249195E+10 | 10549.57 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168422E+10 | 10549.57 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895922E+09 | 10549.57 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180724E+09 | 8619.27 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55133955.79 | 6164.54 | 05-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6635785.89 | 4383.11 | 09-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3050126.43 | 1382.16 | 09-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402583E+09 | 10549.57 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108052E+10 | 10549.57 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251180E+10 | 10549.57 | 04-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251180E+10 | 10549.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104392E+10 | 8979.25 | 21-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414087E+09 | 7907.99 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27424189.75 | 3160.25 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16889353.94 | 3400.66 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39142122.11 | 5166.35 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.742823E+09 | 8280.90 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104392E+10 | 8979.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.372246E+10 | 13911.92 | 21-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.200870E+10 | 13029.45 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.399744E+09 | 7389.95 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41410920.04 | 3657.67 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277297E+09 | 8382.73 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644912E+09 | 10846.33 | 27-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358249E+10 | 13705.32 | 15-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.372246E+10 | 13911.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.417832E+10 | 16210.98 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249206E+10 | 15170.13 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.694951E+09 | 9991.52 | 04-MAR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117822E+09 | 6020.08 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5211415.90 | 1627.24 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.446532E+09 | 10580.60 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.984069E+09 | 13342.88 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.413280E+10 | 16919.97 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.417832E+10 | 16919.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 98836999.47 | 98836999.47 | 10549.78 | 01-JAN-14:43 | 10549.78 | 0.00 |
February | 0.00 | 0.00 | 0.114979E+10 | 0.114966E+10 | 32016.00 | 14-FEB-16:10 | 32016.00 | 0.00 |
March | 0.00 | 0.00 | 0.359451E+10 | 0.359410E+10 | 31926.93 | 08-MAR-16:10 | 31926.93 | 0.00 |
April | 0.00 | 0.00 | 0.154815E+11 | 0.154752E+11 | 53164.52 | 28-APR-15:10 | 53164.52 | 0.00 |
May | 0.00 | 0.00 | 0.293848E+11 | 0.288549E+11 | 61774.90 | 19-MAY-16:00 | 61774.90 | 0.00 |
June | 0.00 | 0.00 | 0.592521E+11 | 0.579310E+11 | 78834.03 | 28-JUN-15:50 | 78834.03 | 0.00 |
July | 0.00 | 0.00 | 0.779301E+11 | 0.697733E+11 | 81599.18 | 31-JUL-15:20 | 72911.98 | 0.00 |
August | 0.00 | 0.00 | 0.762462E+11 | 0.677247E+11 | 87723.42 | 23-AUG-15:10 | 58707.92 | 0.00 |
September | 0.00 | 0.00 | 0.503784E+11 | 0.463701E+11 | 97236.17 | 05-SEP-13:00 | 56077.15 | 0.00 |
October | 0.00 | 0.00 | 0.220029E+11 | 0.209753E+11 | 66428.57 | 02-OCT-15:10 | 62617.09 | 0.00 |
November | 0.00 | 0.00 | 0.743411E+09 | 0.725100E+09 | 15727.54 | 02-NOV-15:00 | 15727.54 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.336263E+12 | 0.312672E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.779301E+11 | 0.697733E+11 | 97236.17 | 78834.03 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321501E+09 | 0.321484E+09 | 10498.53 | 01-JAN-14:53 | 10498.53 | 0.00 |
February | 0.00 | 0.00 | 0.125008E+10 | 0.125008E+10 | 30163.97 | 14-FEB-15:40 | 30163.97 | 0.00 |
March | 0.00 | 0.00 | 0.349871E+10 | 0.349802E+10 | 29844.95 | 08-MAR-16:00 | 29844.95 | 0.00 |
April | 0.00 | 0.00 | 0.146748E+11 | 0.146685E+11 | 51885.59 | 13-APR-15:20 | 51885.59 | 0.00 |
May | 0.00 | 0.00 | 0.274150E+11 | 0.269530E+11 | 58436.26 | 19-MAY-15:10 | 58436.26 | 0.00 |
June | 0.00 | 0.00 | 0.540005E+11 | 0.529054E+11 | 79619.76 | 29-JUN-06:03 | 64348.20 | 0.00 |
July | 0.00 | 0.00 | 0.697555E+11 | 0.629075E+11 | 79782.86 | 31-JUL-15:00 | 72108.31 | 0.00 |
August | 0.00 | 0.00 | 0.672488E+11 | 0.601959E+11 | 77751.79 | 23-AUG-15:10 | 51948.49 | 0.00 |
September | 0.00 | 0.00 | 0.433055E+11 | 0.399562E+11 | 86119.84 | 05-SEP-13:30 | 51316.37 | 0.00 |
October | 0.00 | 0.00 | 0.188930E+11 | 0.180596E+11 | 61833.50 | 02-OCT-14:50 | 58166.99 | 0.00 |
November | 0.00 | 0.00 | 0.821339E+09 | 0.786953E+09 | 17152.14 | 02-NOV-15:00 | 17152.14 | 0.00 |
December | 0.00 | 0.00 | 316360.06 | 316360.06 | 2109.07 | 24-DEC-14:32 | 2109.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.301185E+12 | 0.281503E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 316360.06 | 316360.06 | 2109.07 | 2109.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.697555E+11 | 0.629075E+11 | 86119.84 | 72108.31 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144718E+09 | 0.144718E+09 | 6831.85 | 05-JAN-14:10 | 6831.85 | 0.00 |
February | 0.00 | 0.00 | 0.115807E+10 | 0.115778E+10 | 29552.47 | 14-FEB-15:50 | 29552.47 | 0.00 |
March | 0.00 | 0.00 | 0.338759E+10 | 0.338496E+10 | 30934.72 | 08-MAR-16:00 | 30934.72 | 0.00 |
April | 0.00 | 0.00 | 0.153654E+11 | 0.153543E+11 | 59176.14 | 26-APR-15:00 | 59176.14 | 0.00 |
May | 0.00 | 0.00 | 0.297158E+11 | 0.291718E+11 | 68862.24 | 19-MAY-15:20 | 68862.24 | 0.00 |
June | 0.00 | 0.00 | 0.598678E+11 | 0.586509E+11 | 87714.66 | 28-JUN-14:50 | 87714.66 | 0.00 |
July | 0.00 | 0.00 | 0.770489E+11 | 0.700014E+11 | 90230.94 | 31-JUL-15:20 | 82318.73 | 0.00 |
August | 0.00 | 0.00 | 0.730306E+11 | 0.660086E+11 | 86837.93 | 21-AUG-15:10 | 83856.35 | 0.00 |
September | 0.00 | 0.00 | 0.459129E+11 | 0.425703E+11 | 90079.37 | 05-SEP-13:30 | 55164.90 | 0.00 |
October | 0.00 | 0.00 | 0.189676E+11 | 0.181620E+11 | 68096.54 | 02-OCT-14:30 | 63957.14 | 0.00 |
November | 0.00 | 0.00 | 0.557927E+09 | 0.520077E+09 | 13686.37 | 02-NOV-15:00 | 13574.37 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.325157E+12 | 0.305127E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.770489E+11 | 0.700014E+11 | 90230.94 | 87714.66 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1836.30 | 6422.90 | 26-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1860.31 | 6437.79 | 08-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1936.42 | 6369.22 | 01-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1720.39 | 6083.68 | 04-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1669.23 | 5747.95 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1599.07 | 5301.99 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1401.17 | 4969.19 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1523.12 | 4885.77 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1468.55 | 5117.10 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1556.84 | 5508.64 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1691.57 | 5934.26 | 29-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1723.15 | 6254.15 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1664.41 | ||||
Minimum of Months | 0.00 | 0.00 | 1401.17 | 4885.77 | ||
Maximum of Months | 0.00 | 0.00 | 1936.42 | 6437.79 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237868E+10 | 0.36 | 3402.93 | 26-JAN-16:30 | 0.94 |
February | 0.228534E+10 | 0.37 | 5086.73 | 15-FEB-16:30 | 1.18 |
March | 0.305869E+10 | 0.42 | 5623.16 | 17-MAR-05:02 | 1.25 |
April | 0.395820E+10 | 0.47 | 7380.00 | 28-APR-15:10 | 1.47 |
May | 0.496496E+10 | 0.53 | 8709.31 | 19-MAY-16:00 | 1.63 |
June | 0.694125E+10 | 0.66 | 13600.39 | 22-JUN-12:07 | 2.15 |
July | 0.761437E+10 | 0.67 | 13624.41 | 05-JUL-12:10 | 2.15 |
August | 0.766571E+10 | 0.69 | 13624.41 | 21-AUG-04:02 | 2.15 |
September | 0.581154E+10 | 0.59 | 10087.36 | 05-SEP-15:50 | 1.77 |
October | 0.453930E+10 | 0.50 | 8510.58 | 02-OCT-08:00 | 1.60 |
November | 0.311424E+10 | 0.42 | 6165.95 | 02-NOV-16:00 | 1.32 |
December | 0.237730E+10 | 0.36 | 3267.04 | 29-DEC-16:10 | 0.92 |
Annual Sum or Average | 0.547096E+11 | 0.50 | |||
Minimum of Months | 0.228534E+10 | 0.36 | 3267.04 | 0.92 | |
Maximum of Months | 0.766571E+10 | 0.69 | 13624.41 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.206683E+10 | 0.36 | 3022.79 | 17-JAN-07:01 | 0.94 |
February | 0.196297E+10 | 0.37 | 4533.37 | 15-FEB-16:40 | 1.18 |
March | 0.256989E+10 | 0.41 | 4243.64 | 24-MAR-15:40 | 1.14 |
April | 0.360508E+10 | 0.48 | 8019.44 | 13-APR-15:20 | 1.67 |
May | 0.451987E+10 | 0.53 | 8989.74 | 30-MAY-14:30 | 1.78 |
June | 0.653857E+10 | 0.67 | 11982.42 | 26-JUN-14:50 | 2.13 |
July | 0.739366E+10 | 0.69 | 12153.90 | 05-JUL-14:40 | 2.15 |
August | 0.740538E+10 | 0.71 | 12153.90 | 07-AUG-15:30 | 2.15 |
September | 0.498536E+10 | 0.56 | 10091.32 | 01-SEP-16:00 | 1.91 |
October | 0.355756E+10 | 0.46 | 8652.21 | 02-OCT-16:00 | 1.73 |
November | 0.233774E+10 | 0.39 | 4751.62 | 01-NOV-15:50 | 1.21 |
December | 0.208258E+10 | 0.36 | 3022.79 | 26-DEC-07:01 | 0.94 |
Annual Sum or Average | 0.490255E+11 | 0.50 | |||
Minimum of Months | 0.196297E+10 | 0.36 | 3022.79 | 0.94 | |
Maximum of Months | 0.740538E+10 | 0.71 | 12153.90 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.218229E+10 | 0.36 | 3066.30 | 02-JAN-06:01 | 0.87 |
February | 0.202502E+10 | 0.36 | 4037.37 | 15-FEB-16:20 | 1.01 |
March | 0.246209E+10 | 0.38 | 3867.96 | 24-MAR-15:50 | 0.99 |
April | 0.328502E+10 | 0.42 | 7782.96 | 28-APR-14:30 | 1.49 |
May | 0.416875E+10 | 0.48 | 9179.76 | 30-MAY-14:30 | 1.64 |
June | 0.627110E+10 | 0.60 | 12796.05 | 26-JUN-15:20 | 2.01 |
July | 0.715989E+10 | 0.62 | 12818.49 | 31-JUL-15:20 | 2.01 |
August | 0.708755E+10 | 0.63 | 13640.48 | 07-AUG-15:40 | 2.09 |
September | 0.459276E+10 | 0.50 | 10234.85 | 13-SEP-16:00 | 1.75 |
October | 0.317859E+10 | 0.41 | 8248.83 | 02-OCT-15:50 | 1.52 |
November | 0.220506E+10 | 0.36 | 3919.44 | 02-NOV-15:40 | 0.99 |
December | 0.216168E+10 | 0.35 | 3066.30 | 04-DEC-06:01 | 0.87 |
Annual Sum or Average | 0.467798E+11 | 0.46 | |||
Minimum of Months | 0.202502E+10 | 0.35 | 3066.30 | 0.87 | |
Maximum of Months | 0.715989E+10 | 0.63 | 13640.48 | 2.09 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 56.59 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.02 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:02 | 0.22 | 0.22 | 56.56 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 55.49 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.70 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.55 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:02 | 0.22 | 0.22 | 56.87 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 56.77 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:02 | 0.22 | 0.22 | 56.84 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.71 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 56.15 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 55.76 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.49 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.71 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.63 | 57.63 | 1836.30 | 6422.90 | 26-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.43 | 56.43 | 1860.31 | 6437.79 | 08-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.03 | 57.03 | 1936.42 | 6369.22 | 01-MAR-12:07 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.99 | 55.99 | 1720.39 | 6083.68 | 04-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.88 | 57.88 | 1669.23 | 5747.95 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.45 | 57.45 | 1599.07 | 5301.99 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.45 | 57.45 | 1401.17 | 4969.19 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.28 | 57.28 | 1523.12 | 4885.77 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.73 | 57.73 | 1468.55 | 5117.10 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.95 | 56.95 | 1556.84 | 5508.64 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.49 | 56.49 | 1691.57 | 5934.26 | 29-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.18 | 56.18 | 1723.15 | 6254.15 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1664.41 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.99 | 55.99 | 1401.17 | 4885.77 | ||
Maximum of Months | 0.00 | 0.00 | 57.88 | 57.88 | 1936.42 | 6437.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.840946E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.680467E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.632539E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.867730E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128309E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.231333E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285338E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.273325E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.183350E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107421E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.465365E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.749087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.163269E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.465365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285338E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.644606E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.463820E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.415387E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.725526E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.113268E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.212019E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.261305E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247806E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.157182E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.845357E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.339332E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.613385E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.139632E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.339332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.261305E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.126469E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.880889E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.606617E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.753781E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.117039E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226865E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.280299E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.261269E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.160823E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.906995E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.584614E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123808E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.166986E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.584614E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.280299E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.237868E+10 | 98836999.47 | 0.704618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228534E+10 | 0.114979E+10 | 0.464113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305869E+10 | 0.359451E+10 | 0.233699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395820E+10 | 0.154815E+11 | 0.892407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.496496E+10 | 0.293848E+11 | 0.547794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694125E+10 | 0.592521E+11 | 89826392.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761437E+10 | 0.779301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.766571E+10 | 0.762462E+11 | 5986895.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581154E+10 | 0.503784E+11 | 65597711.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.453930E+10 | 0.220029E+11 | 0.840501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311424E+10 | 0.743411E+09 | 0.137154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237730E+10 | 0.00 | 0.585640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547096E+11 | 0.336263E+12 | 0.236943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.766571E+10 | 0.779301E+11 | 0.704618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.206683E+10 | 0.321501E+09 | 0.801116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196297E+10 | 0.125008E+10 | 0.436634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256989E+10 | 0.349871E+10 | 0.105761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360508E+10 | 0.146748E+11 | 77880008.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451987E+10 | 0.274150E+11 | 6006574.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653857E+10 | 0.540005E+11 | 17090.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.739366E+10 | 0.697555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740538E+10 | 0.672488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.498536E+10 | 0.433055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355756E+10 | 0.188930E+11 | 0.542895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233774E+10 | 0.821339E+09 | 0.147188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208258E+10 | 316360.06 | 0.763367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.490255E+11 | 0.301185E+12 | 0.231675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196297E+10 | 316360.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740538E+10 | 0.697555E+11 | 0.801116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.218229E+10 | 0.144718E+09 | 0.146014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202502E+10 | 0.115807E+10 | 0.897665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246209E+10 | 0.338759E+10 | 0.338938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328502E+10 | 0.153654E+11 | 0.552875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416875E+10 | 0.297158E+11 | 0.105223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627110E+10 | 0.598678E+11 | 8278207.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715989E+10 | 0.770489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.708755E+10 | 0.730306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.459276E+10 | 0.459129E+11 | 3050126.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317859E+10 | 0.189676E+11 | 0.163849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220506E+10 | 0.557927E+09 | 0.446754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216168E+10 | 0.00 | 0.143520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467798E+11 | 0.325157E+12 | 0.480948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715989E+10 | 0.770489E+11 | 0.146014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.237868E+10 | 0.00 | 0.00 | 0.00 | 28507411.28 | 0.600227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228534E+10 | 0.00 | 0.00 | 0.00 | 0.292281E+09 | 0.422704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305869E+10 | 0.00 | 0.00 | 0.00 | 0.957129E+09 | 0.230956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395820E+10 | 0.00 | 0.00 | 0.00 | 0.382669E+10 | 0.892407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.496496E+10 | 0.00 | 0.00 | 0.00 | 0.731818E+10 | 0.547794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.694125E+10 | 0.00 | 0.00 | 0.00 | 0.161022E+11 | 89826392.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.761437E+10 | 0.00 | 0.00 | 0.00 | 0.209195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.766571E+10 | 0.00 | 0.00 | 0.00 | 0.196608E+11 | 5986895.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581154E+10 | 0.00 | 0.00 | 0.00 | 0.124579E+11 | 65597711.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.453930E+10 | 0.00 | 0.00 | 0.00 | 0.537916E+10 | 0.823612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311424E+10 | 0.00 | 0.00 | 0.00 | 0.207019E+09 | 0.133240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547096E+11 | 0.00 | 0.00 | 0.00 | 0.871494E+11 | 0.214101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.766571E+10 | 0.00 | 0.00 | 0.00 | 0.209195E+11 | 0.600227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.206683E+10 | 0.00 | 0.00 | 0.00 | 90540023.75 | 0.428870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196297E+10 | 0.00 | 0.00 | 0.00 | 0.317596E+09 | 0.235764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256989E+10 | 0.00 | 0.00 | 0.00 | 0.926112E+09 | 0.657865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360508E+10 | 0.00 | 0.00 | 0.00 | 0.361371E+10 | 36469088.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451987E+10 | 0.00 | 0.00 | 0.00 | 0.680095E+10 | 6006574.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.653857E+10 | 0.00 | 0.00 | 0.00 | 0.146633E+11 | 17090.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.739366E+10 | 0.00 | 0.00 | 0.00 | 0.187369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.740538E+10 | 0.00 | 0.00 | 0.00 | 0.173752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.498536E+10 | 0.00 | 0.00 | 0.00 | 0.107329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355756E+10 | 0.00 | 0.00 | 0.00 | 0.463041E+10 | 0.265599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233774E+10 | 0.00 | 0.00 | 0.00 | 0.228612E+09 | 0.826966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208258E+10 | 0.00 | 0.00 | 0.00 | 91896.85 | 0.405118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.490255E+11 | 0.00 | 0.00 | 0.00 | 0.781163E+11 | 0.124904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196297E+10 | 0.00 | 0.00 | 0.00 | 91896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.740538E+10 | 0.00 | 0.00 | 0.00 | 0.187369E+11 | 0.428870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.218229E+10 | 0.00 | 0.00 | 0.00 | 41593469.58 | 0.104231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202502E+10 | 0.00 | 0.00 | 0.00 | 0.299276E+09 | 0.648459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246209E+10 | 0.00 | 0.00 | 0.00 | 0.909654E+09 | 0.269443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328502E+10 | 0.00 | 0.00 | 0.00 | 0.381773E+10 | 0.435053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.416875E+10 | 0.00 | 0.00 | 0.00 | 0.743515E+10 | 0.100011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627110E+10 | 0.00 | 0.00 | 0.00 | 0.164072E+11 | 8278207.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.715989E+10 | 0.00 | 0.00 | 0.00 | 0.208700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.708755E+10 | 0.00 | 0.00 | 0.00 | 0.190394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.459276E+10 | 0.00 | 0.00 | 0.00 | 0.114864E+11 | 3050126.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317859E+10 | 0.00 | 0.00 | 0.00 | 0.469940E+10 | 0.119195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220506E+10 | 0.00 | 0.00 | 0.00 | 0.157615E+09 | 0.348347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467798E+11 | 0.00 | 0.00 | 0.00 | 0.851634E+11 | 0.350431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715989E+10 | 0.00 | 0.00 | 0.00 | 0.208700E+11 | 0.104231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.461557E+10 | 0.00 | 0.00 | 26573412.16 | 0.00 | 0.00 | 0.125506E+11 | 0.00 | 0.49 |
February | 0.308066E+10 | 0.00 | 0.00 | 27236886.05 | 0.00 | 0.00 | 0.132111E+11 | 0.00 | 0.56 |
March | 0.152353E+10 | 0.00 | 0.00 | 40711014.65 | 0.00 | 0.00 | 0.200044E+11 | 0.00 | 0.91 |
April | 0.142055E+10 | 1419150.92 | 0.00 | 42807670.20 | 0.00 | 0.00 | 0.173350E+11 | 0.00 | 1.15 |
May | 0.134570E+10 | 24680668.67 | 0.00 | 45613788.56 | 5150235.83 | 0.00 | 0.149419E+11 | 0.00 | 1.21 |
June | 0.770670E+09 | 0.625359E+09 | 0.00 | 29438474.56 | 20366252.40 | 0.00 | 0.602807E+10 | 0.00 | 0.86 |
July | 0.252946E+09 | 0.198580E+10 | 0.00 | 10640930.41 | 0.206259E+09 | 0.00 | 0.800884E+09 | 0.00 | 0.65 |
August | 0.400489E+09 | 0.132642E+10 | 0.00 | 23296008.15 | 77782853.65 | 0.00 | 0.321476E+10 | 0.00 | 0.91 |
September | 0.821913E+09 | 0.264965E+09 | 0.00 | 43290362.61 | 38424692.11 | 0.00 | 0.861177E+10 | 0.00 | 1.11 |
October | 0.193079E+10 | 10021742.19 | 0.00 | 47870345.02 | 1873295.56 | 0.00 | 0.176150E+11 | 0.00 | 1.10 |
November | 0.182663E+10 | 0.00 | 0.00 | 42598355.29 | 0.00 | 0.00 | 0.206236E+11 | 0.00 | 0.80 |
December | 0.418329E+10 | 0.00 | 0.00 | 28969898.00 | 0.00 | 0.00 | 0.131677E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.221727E+11 | 0.423866E+10 | 0.00 | 0.409047E+09 | 0.349856E+09 | 0.00 | 0.148105E+12 | 0.00 | 0.85 |
Minimum of Months | 0.252946E+09 | 0.00 | 0.00 | 10640930.41 | 0.00 | 0.00 | 0.800884E+09 | 0.00 | 0.42 |
Maximum of Months | 0.461557E+10 | 0.198580E+10 | 0.00 | 47870345.02 | 0.206259E+09 | 0.00 | 0.206236E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.842837E+10 | 0.00 | 0.00 | 2486288.71 | 0.00 | 14122029.41 | 0.263352E+10 | 0.00 | 0.31 |
February | 0.621391E+10 | 0.00 | 0.00 | 4686467.85 | 0.00 | 13363584.54 | 0.362379E+10 | 0.00 | 0.34 |
March | 0.428091E+10 | 0.00 | 0.00 | 14515183.37 | 0.00 | 0.00 | 0.834454E+10 | 0.00 | 0.53 |
April | 0.200518E+10 | 836272.26 | 0.00 | 22749393.04 | 638806.62 | 0.00 | 0.979967E+10 | 0.00 | 0.74 |
May | 0.127970E+10 | 18405657.44 | 0.00 | 28721079.83 | 4950109.18 | 0.00 | 0.930148E+10 | 0.00 | 0.80 |
June | 0.585819E+09 | 0.428381E+09 | 0.00 | 21747624.59 | 14658417.68 | 0.00 | 0.397017E+10 | 0.00 | 0.61 |
July | 0.205270E+09 | 0.146882E+10 | 0.00 | 9199125.97 | 0.129737E+09 | 0.00 | 0.580558E+09 | 0.00 | 0.49 |
August | 0.364400E+09 | 0.915587E+09 | 0.00 | 18283971.34 | 51236124.22 | 0.00 | 0.212953E+10 | 0.00 | 0.66 |
September | 0.599303E+09 | 0.202303E+09 | 0.00 | 28957473.66 | 28349426.45 | 0.00 | 0.548235E+10 | 0.00 | 0.75 |
October | 0.236568E+10 | 6204983.18 | 0.00 | 24268252.43 | 1741697.30 | 0.00 | 0.889829E+10 | 0.00 | 0.67 |
November | 0.469510E+10 | 0.00 | 0.00 | 12255304.87 | 0.00 | 0.00 | 0.752594E+10 | 0.00 | 0.44 |
December | 0.823765E+10 | 0.00 | 0.00 | 2701043.85 | 0.00 | 11235869.93 | 0.271621E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.392613E+11 | 0.304054E+10 | 0.00 | 0.190571E+09 | 0.231311E+09 | 38721483.88 | 0.650060E+11 | 0.00 | 0.55 |
Minimum of Months | 0.205270E+09 | 0.00 | 0.00 | 2486288.71 | 0.00 | 0.00 | 0.580558E+09 | 0.00 | 0.27 |
Maximum of Months | 0.842837E+10 | 0.146882E+10 | 0.00 | 28957473.66 | 0.129737E+09 | 14122029.41 | 0.979967E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.887888E+10 | 0.00 | 0.00 | 717804.24 | 0.00 | 0.532611E+09 | 0.105166E+10 | 0.00 | 0.30 |
February | 0.740339E+10 | 0.00 | 0.00 | 1910151.10 | 0.00 | 0.231805E+09 | 0.188235E+10 | 0.00 | 0.34 |
March | 0.607195E+10 | 0.00 | 0.00 | 8210963.81 | 0.00 | 18592896.68 | 0.585281E+10 | 0.00 | 0.51 |
April | 0.279730E+10 | 0.00 | 0.00 | 18567381.31 | 0.00 | 0.00 | 0.856247E+10 | 0.00 | 0.76 |
May | 0.189502E+10 | 7561571.74 | 0.00 | 25066440.42 | 6805859.77 | 0.00 | 0.832274E+10 | 0.00 | 0.83 |
June | 0.802346E+09 | 0.310798E+09 | 0.00 | 23072183.94 | 23659213.78 | 0.00 | 0.338249E+10 | 0.00 | 0.61 |
July | 0.190332E+09 | 0.129600E+10 | 0.00 | 7857726.57 | 0.176599E+09 | 0.00 | 0.301100E+09 | 0.00 | 0.48 |
August | 0.342065E+09 | 0.676175E+09 | 0.00 | 19946583.03 | 62029978.35 | 0.00 | 0.166077E+10 | 0.00 | 0.66 |
September | 0.103600E+10 | 0.119772E+09 | 0.00 | 25080308.54 | 17385605.82 | 0.00 | 0.419124E+10 | 0.00 | 0.76 |
October | 0.363185E+10 | 6445987.30 | 0.00 | 16394518.30 | 0.00 | 4019821.21 | 0.615636E+10 | 0.00 | 0.64 |
November | 0.654446E+10 | 0.00 | 0.00 | 5045209.70 | 0.00 | 61409047.63 | 0.420421E+10 | 0.00 | 0.40 |
December | 0.892795E+10 | 0.00 | 0.00 | 466017.78 | 0.00 | 0.543822E+09 | 0.759750E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.485215E+11 | 0.241675E+10 | 0.00 | 0.152335E+09 | 0.286479E+09 | 0.139226E+10 | 0.463280E+11 | 0.00 | 0.55 |
Minimum of Months | 0.190332E+09 | 0.00 | 0.00 | 466017.78 | 0.00 | 0.00 | 0.301100E+09 | 0.00 | 0.26 |
Maximum of Months | 0.892795E+10 | 0.129600E+10 | 0.00 | 25080308.54 | 0.176599E+09 | 0.543822E+09 | 0.856247E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164338E+10 | 0.00 | 0.00 | 0.47 |
February | 0.206274E+10 | 0.00 | 0.00 | 13235.12 | 0.00 | 0.985773E+09 | 29259347.35 | 0.00 | 0.51 |
March | 0.286869E+10 | 0.00 | 0.00 | 364653.64 | 0.00 | 0.324970E+09 | 0.421319E+09 | 0.00 | 0.72 |
April | 0.174815E+10 | 0.00 | 0.00 | 2885388.03 | 0.00 | 47638540.92 | 0.127791E+10 | 0.00 | 0.98 |
May | 0.107323E+10 | 2992650.52 | 0.00 | 5402775.93 | 2216561.23 | 1597046.59 | 0.162447E+10 | 0.00 | 1.09 |
June | 0.399986E+09 | 0.113864E+09 | 0.00 | 6428132.25 | 7484176.97 | 0.00 | 0.766829E+09 | 0.00 | 0.87 |
July | 86320688.42 | 0.431057E+09 | 0.00 | 1816074.39 | 58200847.42 | 0.00 | 59673179.01 | 0.00 | 0.71 |
August | 0.201083E+09 | 0.211577E+09 | 0.00 | 4695185.87 | 20781873.46 | 0.00 | 0.341059E+09 | 0.00 | 0.89 |
September | 0.590691E+09 | 34528338.59 | 0.00 | 5173833.99 | 5636700.22 | 0.00 | 0.795941E+09 | 0.00 | 0.97 |
October | 0.199373E+10 | 1519267.64 | 0.00 | 1972052.87 | 413763.03 | 0.162714E+09 | 0.596113E+09 | 0.00 | 0.83 |
November | 0.283316E+10 | 0.00 | 0.00 | 16156.84 | 0.00 | 0.477833E+09 | 64895106.35 | 0.00 | 0.58 |
December | 0.158426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175772E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.172178E+11 | 0.795539E+09 | 0.00 | 28767488.93 | 94733922.33 | 0.540162E+10 | 0.597746E+10 | 0.00 | 0.75 |
Minimum of Months | 86320688.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.286869E+10 | 0.431057E+09 | 0.00 | 6428132.25 | 58200847.42 | 0.175772E+10 | 0.162447E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243500E+10 | 0.00 | 0.00 | 8058.53 | 0.00 | 0.116137E+10 | 28639715.57 | 0.00 | 0.79 |
February | 0.237371E+10 | 0.00 | 0.00 | 300137.08 | 0.00 | 0.615678E+09 | 0.288634E+09 | 0.00 | 0.86 |
March | 0.226174E+10 | 0.00 | 0.00 | 2215896.35 | 0.00 | 0.182417E+09 | 0.161712E+10 | 0.00 | 1.27 |
April | 0.105848E+10 | 0.00 | 0.00 | 6757005.46 | 0.00 | 6815144.60 | 0.319332E+10 | 0.00 | 1.99 |
May | 0.793664E+09 | 2705291.55 | 0.00 | 8427821.96 | 2266181.61 | 912445.78 | 0.291938E+10 | 0.00 | 2.17 |
June | 0.331493E+09 | 0.105365E+09 | 0.00 | 8425226.23 | 4588890.37 | 0.00 | 0.114348E+10 | 0.00 | 1.68 |
July | 88085079.17 | 0.500996E+09 | 0.00 | 2019874.63 | 30480454.93 | 0.00 | 73346160.38 | 0.00 | 1.30 |
August | 0.175930E+09 | 0.244738E+09 | 0.00 | 6156599.03 | 16883925.40 | 0.00 | 0.503499E+09 | 0.00 | 1.73 |
September | 0.541153E+09 | 27738876.51 | 0.00 | 7153367.97 | 6017137.11 | 0.00 | 0.129921E+10 | 0.00 | 1.97 |
October | 0.156052E+10 | 1427020.32 | 0.00 | 3867190.33 | 440411.21 | 0.118651E+09 | 0.161323E+10 | 0.00 | 1.54 |
November | 0.286962E+10 | 0.00 | 0.00 | 400095.05 | 0.00 | 0.265466E+09 | 0.475693E+09 | 0.00 | 0.98 |
December | 0.245218E+10 | 0.00 | 0.00 | 2635.61 | 0.00 | 0.108272E+10 | 10184169.06 | 0.00 | 0.67 |
Annual Sum or Average | 0.169416E+11 | 0.882971E+09 | 0.00 | 45733908.24 | 60677000.63 | 0.343403E+10 | 0.131657E+11 | 0.00 | 1.42 |
Minimum of Months | 88085079.17 | 0.00 | 0.00 | 2635.61 | 0.00 | 0.00 | 10184169.06 | 0.00 | 0.67 |
Maximum of Months | 0.286962E+10 | 0.500996E+09 | 0.00 | 8427821.96 | 30480454.93 | 0.116137E+10 | 0.319332E+10 | 0.00 | 2.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162994E+10 | 0.00 | 0.00 | 7094259.53 | 0.00 | 0.838604E+09 | 0.358506E+10 | 0.00 | 0.91 |
February | 0.137273E+10 | 0.00 | 0.00 | 7757199.26 | 0.00 | 0.474210E+09 | 0.391484E+10 | 0.00 | 1.03 |
March | 0.184734E+10 | 0.00 | 0.00 | 7864994.37 | 0.00 | 0.258294E+09 | 0.430103E+10 | 0.00 | 1.35 |
April | 0.145140E+10 | 0.00 | 0.00 | 8262596.48 | 0.00 | 46844775.27 | 0.351308E+10 | 0.00 | 1.63 |
May | 0.130210E+10 | 4429679.00 | 0.00 | 6899483.32 | 2565143.44 | 5482863.28 | 0.215685E+10 | 0.00 | 1.39 |
June | 0.584454E+09 | 0.109933E+09 | 0.00 | 6138581.36 | 12558561.51 | 618737.70 | 0.736422E+09 | 0.00 | 0.94 |
July | 0.114759E+09 | 0.472206E+09 | 0.00 | 1731801.44 | 78628178.22 | 0.00 | 53487679.85 | 0.00 | 0.77 |
August | 0.267887E+09 | 0.288531E+09 | 0.00 | 6186576.22 | 23873918.83 | 0.00 | 0.411012E+09 | 0.00 | 1.14 |
September | 0.592523E+09 | 68026485.59 | 0.00 | 12023486.61 | 4242829.97 | 0.00 | 0.151048E+10 | 0.00 | 1.61 |
October | 0.115432E+10 | 2946371.32 | 0.00 | 14163051.11 | 0.00 | 0.116194E+09 | 0.456726E+10 | 0.00 | 1.82 |
November | 0.149499E+10 | 0.00 | 0.00 | 10077395.00 | 0.00 | 0.224811E+09 | 0.537833E+10 | 0.00 | 1.23 |
December | 0.152810E+10 | 0.00 | 0.00 | 8760658.34 | 0.00 | 0.684684E+09 | 0.395959E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.133405E+11 | 0.946072E+09 | 0.00 | 96960083.05 | 0.121869E+09 | 0.264974E+10 | 0.340875E+11 | 0.00 | 1.21 |
Minimum of Months | 0.114759E+09 | 0.00 | 0.00 | 1731801.44 | 0.00 | 0.00 | 53487679.85 | 0.00 | 0.76 |
Maximum of Months | 0.184734E+10 | 0.472206E+09 | 0.00 | 14163051.11 | 78628178.22 | 0.838604E+09 | 0.537833E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212724E+10 | 0.00 | 0.00 | 445202.04 | 0.00 | 0.153797E+10 | 0.487020E+09 | 0.00 | 0.90 |
February | 0.212822E+10 | 0.00 | 0.00 | 1304008.66 | 0.00 | 0.911007E+09 | 0.861587E+09 | 0.00 | 1.05 |
March | 0.295713E+10 | 0.00 | 0.00 | 2384246.51 | 0.00 | 0.392020E+09 | 0.144834E+10 | 0.00 | 1.55 |
April | 0.212156E+10 | 0.00 | 0.00 | 5078939.26 | 0.00 | 61287551.91 | 0.188267E+10 | 0.00 | 2.08 |
May | 0.167472E+10 | 5051778.54 | 0.00 | 5575937.20 | 2255824.50 | 10128804.31 | 0.157233E+10 | 0.00 | 2.06 |
June | 0.690820E+09 | 0.108499E+09 | 0.00 | 5145361.77 | 12172323.15 | 622389.79 | 0.554641E+09 | 0.00 | 1.42 |
July | 0.125560E+09 | 0.359252E+09 | 0.00 | 1579422.46 | 0.103611E+09 | 0.00 | 41217948.89 | 0.00 | 1.09 |
August | 0.314428E+09 | 0.198627E+09 | 0.00 | 4070694.24 | 34368154.96 | 0.00 | 0.269666E+09 | 0.00 | 1.43 |
September | 0.873249E+09 | 34494169.40 | 0.00 | 5854116.15 | 7005303.36 | 0.00 | 0.715270E+09 | 0.00 | 1.72 |
October | 0.219433E+10 | 1956685.45 | 0.00 | 3717408.45 | 372087.16 | 0.190456E+09 | 0.122525E+10 | 0.00 | 1.72 |
November | 0.284622E+10 | 0.00 | 0.00 | 1121587.73 | 0.00 | 0.470657E+09 | 0.939830E+09 | 0.00 | 1.17 |
December | 0.198881E+10 | 0.00 | 0.00 | 293456.98 | 0.00 | 0.159091E+10 | 0.459969E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.200423E+11 | 0.707881E+09 | 0.00 | 36570381.44 | 0.159785E+09 | 0.516506E+10 | 0.104578E+11 | 0.00 | 1.41 |
Minimum of Months | 0.125560E+09 | 0.00 | 0.00 | 293456.98 | 0.00 | 0.00 | 41217948.89 | 0.00 | 0.77 |
Maximum of Months | 0.295713E+10 | 0.359252E+09 | 0.00 | 5854116.15 | 0.103611E+09 | 0.159091E+10 | 0.188267E+10 | 0.00 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934238E+09 | 0.00 | 0.00 | 0.38 |
February | 0.196163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642869E+09 | 0.00 | 0.00 | 0.41 |
March | 0.284152E+10 | 0.00 | 0.00 | 22005.48 | 0.00 | 0.134896E+09 | 61156213.85 | 0.00 | 0.59 |
April | 0.180797E+10 | 208176.47 | 0.00 | 1344983.53 | 26918.99 | 2604365.90 | 0.574680E+09 | 0.00 | 0.70 |
May | 0.103315E+10 | 4763051.03 | 0.00 | 3662482.98 | 1084420.66 | 0.00 | 0.108379E+10 | 0.00 | 0.78 |
June | 0.393378E+09 | 0.149943E+09 | 0.00 | 3892258.47 | 6246490.32 | 0.00 | 0.644836E+09 | 0.00 | 0.70 |
July | 0.115629E+09 | 0.460433E+09 | 0.00 | 1236421.82 | 45028387.71 | 0.00 | 74567312.50 | 0.00 | 0.61 |
August | 0.208345E+09 | 0.294109E+09 | 0.00 | 2981737.17 | 17120099.03 | 0.00 | 0.368638E+09 | 0.00 | 0.78 |
September | 0.484354E+09 | 54977219.23 | 0.00 | 5284488.72 | 7980103.96 | 0.00 | 0.915291E+09 | 0.00 | 0.84 |
October | 0.172334E+10 | 1636118.52 | 0.00 | 2600561.58 | 394436.39 | 4290478.76 | 0.878831E+09 | 0.00 | 0.73 |
November | 0.279952E+10 | 0.00 | 0.00 | 132555.51 | 0.00 | 54640106.25 | 0.218955E+09 | 0.00 | 0.50 |
December | 0.200072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862749E+09 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.173529E+11 | 0.966070E+09 | 0.00 | 21157495.25 | 77880857.06 | 0.263629E+10 | 0.482074E+10 | 0.00 | 0.61 |
Minimum of Months | 0.115629E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.284152E+10 | 0.460433E+09 | 0.00 | 5284488.72 | 45028387.71 | 0.934238E+09 | 0.108379E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273162E+10 | 0.00 | 0.00 | 8661.42 | 0.00 | 0.466200E+09 | 36370981.27 | 0.00 | 0.67 |
February | 0.238610E+10 | 0.00 | 0.00 | 187052.27 | 0.00 | 0.275409E+09 | 0.230287E+09 | 0.00 | 0.73 |
March | 0.226728E+10 | 0.00 | 0.00 | 1546894.31 | 0.00 | 27965950.75 | 0.118759E+10 | 0.00 | 1.07 |
April | 0.920190E+09 | 319111.96 | 0.00 | 5674822.92 | 0.00 | 0.00 | 0.260870E+10 | 0.00 | 1.60 |
May | 0.690645E+09 | 5983582.22 | 0.00 | 7093400.48 | 1203646.37 | 0.00 | 0.243509E+10 | 0.00 | 1.74 |
June | 0.357333E+09 | 0.142664E+09 | 0.00 | 5816362.94 | 5768233.36 | 0.00 | 0.100412E+10 | 0.00 | 1.41 |
July | 0.110998E+09 | 0.507395E+09 | 0.00 | 1776530.55 | 27409255.18 | 0.00 | 0.117270E+09 | 0.00 | 1.14 |
August | 0.203193E+09 | 0.317612E+09 | 0.00 | 4433094.00 | 14440508.30 | 0.00 | 0.542045E+09 | 0.00 | 1.52 |
September | 0.424984E+09 | 48747529.55 | 0.00 | 7564774.80 | 8594243.59 | 0.00 | 0.147177E+10 | 0.00 | 1.72 |
October | 0.126426E+10 | 1547822.92 | 0.00 | 5175981.42 | 417788.77 | 2787870.53 | 0.211891E+10 | 0.00 | 1.46 |
November | 0.238548E+10 | 0.00 | 0.00 | 1066785.53 | 0.00 | 2116787.17 | 0.108589E+10 | 0.00 | 0.90 |
December | 0.280180E+10 | 0.00 | 0.00 | 7537.38 | 0.00 | 0.352174E+09 | 20503371.39 | 0.00 | 0.57 |
Annual Sum or Average | 0.165439E+11 | 0.102427E+10 | 0.00 | 40351898.02 | 57833675.57 | 0.112665E+10 | 0.128586E+11 | 0.00 | 1.21 |
Minimum of Months | 0.110998E+09 | 0.00 | 0.00 | 7537.38 | 0.00 | 0.00 | 20503371.39 | 0.00 | 0.57 |
Maximum of Months | 0.280180E+10 | 0.507395E+09 | 0.00 | 7564774.80 | 27409255.18 | 0.466200E+09 | 0.260870E+10 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164406E+10 | 0.00 | 0.00 | 2800291.47 | 0.00 | 0.131304E+10 | 0.164515E+10 | 0.00 | 0.65 |
February | 0.159401E+10 | 0.00 | 0.00 | 2441475.45 | 0.00 | 0.900890E+09 | 0.148918E+10 | 0.00 | 0.70 |
March | 0.228514E+10 | 0.00 | 0.00 | 2467861.18 | 0.00 | 0.679398E+09 | 0.141154E+10 | 0.00 | 0.90 |
April | 0.172221E+10 | 496333.08 | 0.00 | 3607023.37 | 0.00 | 0.340761E+09 | 0.121113E+10 | 0.00 | 1.05 |
May | 0.163378E+10 | 8170858.32 | 0.00 | 3645247.04 | 1321207.29 | 0.239628E+09 | 0.689067E+09 | 0.00 | 0.96 |
June | 0.733140E+09 | 0.186298E+09 | 0.00 | 3085181.66 | 9960734.58 | 57047969.27 | 0.311342E+09 | 0.00 | 0.75 |
July | 0.172144E+09 | 0.602513E+09 | 0.00 | 882372.97 | 57991661.00 | 0.00 | 41892739.68 | 0.00 | 0.70 |
August | 0.348017E+09 | 0.457303E+09 | 0.00 | 3165302.86 | 20929453.17 | 2482186.78 | 0.309796E+09 | 0.00 | 1.00 |
September | 0.606035E+09 | 0.111782E+09 | 0.00 | 10834414.05 | 4798084.51 | 54131053.31 | 0.135210E+10 | 0.00 | 1.37 |
October | 0.115367E+10 | 3877977.73 | 0.00 | 12757167.14 | 0.00 | 0.344309E+09 | 0.356137E+10 | 0.00 | 1.59 |
November | 0.163740E+10 | 0.00 | 0.00 | 5923181.23 | 0.00 | 0.435555E+09 | 0.366428E+10 | 0.00 | 0.97 |
December | 0.152209E+10 | 0.00 | 0.00 | 3226276.85 | 0.00 | 0.114087E+10 | 0.185996E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.150517E+11 | 0.137044E+10 | 0.00 | 54835795.28 | 95001140.56 | 0.550811E+10 | 0.175468E+11 | 0.00 | 0.93 |
Minimum of Months | 0.172144E+09 | 0.00 | 0.00 | 882372.97 | 0.00 | 0.00 | 41892739.68 | 0.00 | 0.54 |
Maximum of Months | 0.228514E+10 | 0.602513E+09 | 0.00 | 12757167.14 | 57991661.00 | 0.131304E+10 | 0.366428E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257952E+10 | 0.00 | 0.00 | 282702.11 | 0.00 | 0.573582E+09 | 0.317925E+09 | 0.00 | 0.72 |
February | 0.237213E+10 | 0.00 | 0.00 | 758953.46 | 0.00 | 0.323666E+09 | 0.468523E+09 | 0.00 | 0.81 |
March | 0.292614E+10 | 0.00 | 0.00 | 1345914.71 | 0.00 | 90414643.83 | 0.747487E+09 | 0.00 | 1.18 |
April | 0.178344E+10 | 305707.72 | 0.00 | 3428313.81 | 0.00 | 886573.36 | 0.128685E+10 | 0.00 | 1.48 |
May | 0.130917E+10 | 8564517.01 | 0.00 | 4155420.83 | 966455.30 | 365941.02 | 0.123889E+10 | 0.00 | 1.51 |
June | 0.609901E+09 | 0.166650E+09 | 0.00 | 2990615.21 | 8171375.09 | 0.00 | 0.467149E+09 | 0.00 | 1.12 |
July | 0.142163E+09 | 0.436580E+09 | 0.00 | 860869.24 | 51350987.62 | 0.00 | 64158058.08 | 0.00 | 0.91 |
August | 0.271693E+09 | 0.301331E+09 | 0.00 | 2481534.84 | 17732661.79 | 0.00 | 0.312128E+09 | 0.00 | 1.21 |
September | 0.618161E+09 | 56550968.50 | 0.00 | 5673502.99 | 7919739.21 | 0.00 | 0.889092E+09 | 0.00 | 1.39 |
October | 0.174375E+10 | 2042943.19 | 0.00 | 4254617.46 | 460917.97 | 8617519.86 | 0.151632E+10 | 0.00 | 1.45 |
November | 0.282672E+10 | 0.00 | 0.00 | 1178475.58 | 0.00 | 20498367.22 | 0.981335E+09 | 0.00 | 1.00 |
December | 0.262612E+10 | 0.00 | 0.00 | 297584.07 | 0.00 | 0.408770E+09 | 0.364954E+09 | 0.00 | 0.62 |
Annual Sum or Average | 0.198089E+11 | 0.972025E+09 | 0.00 | 27708504.31 | 86602136.97 | 0.142680E+10 | 0.865481E+10 | 0.00 | 1.12 |
Minimum of Months | 0.142163E+09 | 0.00 | 0.00 | 282702.11 | 0.00 | 0.00 | 64158058.08 | 0.00 | 0.62 |
Maximum of Months | 0.292614E+10 | 0.436580E+09 | 0.00 | 5673502.99 | 51350987.62 | 0.573582E+09 | 0.151632E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839869E+09 | 0.00 | 0.00 | 0.44 |
February | 0.236959E+10 | 0.00 | 0.00 | 31917.59 | 0.00 | 0.464737E+09 | 50615456.46 | 0.00 | 0.46 |
March | 0.265506E+10 | 0.00 | 0.00 | 653272.96 | 0.00 | 78342581.19 | 0.596317E+09 | 0.00 | 0.66 |
April | 0.133796E+10 | 344316.44 | 0.00 | 3504875.92 | 192327.84 | 651293.94 | 0.145918E+10 | 0.00 | 0.87 |
May | 0.765490E+09 | 7860488.78 | 0.00 | 5997036.12 | 1490347.42 | 0.00 | 0.175978E+10 | 0.00 | 0.97 |
June | 0.322760E+09 | 0.160571E+09 | 0.00 | 5494310.01 | 4866499.43 | 0.00 | 0.861520E+09 | 0.00 | 0.84 |
July | 0.114267E+09 | 0.514458E+09 | 0.00 | 1796725.35 | 39494380.87 | 0.00 | 95359895.04 | 0.00 | 0.70 |
August | 0.215381E+09 | 0.300005E+09 | 0.00 | 3741972.37 | 15628776.85 | 0.00 | 0.387010E+09 | 0.00 | 0.85 |
September | 0.468342E+09 | 59894182.30 | 0.00 | 5290813.64 | 8401433.92 | 0.00 | 0.911152E+09 | 0.00 | 0.86 |
October | 0.175875E+10 | 1858349.14 | 0.00 | 2568060.47 | 524379.16 | 26365861.84 | 0.848366E+09 | 0.00 | 0.74 |
November | 0.287347E+10 | 0.00 | 0.00 | 162268.78 | 0.00 | 0.124625E+09 | 0.256178E+09 | 0.00 | 0.54 |
December | 0.228831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983791E+09 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.176407E+11 | 0.104499E+10 | 0.00 | 29241253.21 | 70598145.49 | 0.251838E+10 | 0.722547E+10 | 0.00 | 0.69 |
Minimum of Months | 0.114267E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.287347E+10 | 0.514458E+09 | 0.00 | 5997036.12 | 39494380.87 | 0.983791E+09 | 0.175978E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308729E+10 | 0.00 | 0.00 | 114585.58 | 0.00 | 0.730229E+09 | 0.140715E+09 | 0.00 | 0.83 |
February | 0.279410E+10 | 0.00 | 0.00 | 562104.61 | 0.00 | 0.304022E+09 | 0.389956E+09 | 0.00 | 0.88 |
March | 0.250255E+10 | 0.00 | 0.00 | 2700793.45 | 0.00 | 32964534.24 | 0.178846E+10 | 0.00 | 1.32 |
April | 0.109598E+10 | 500811.52 | 0.00 | 7166509.78 | 46432.47 | 941059.27 | 0.328215E+10 | 0.00 | 1.93 |
May | 0.791535E+09 | 7143342.94 | 0.00 | 8993680.36 | 1783452.78 | 0.00 | 0.295322E+10 | 0.00 | 2.05 |
June | 0.373187E+09 | 0.136846E+09 | 0.00 | 7275522.98 | 4338291.05 | 0.00 | 0.119652E+10 | 0.00 | 1.64 |
July | 0.138053E+09 | 0.538167E+09 | 0.00 | 2188933.33 | 24829144.06 | 0.00 | 0.121474E+09 | 0.00 | 1.29 |
August | 0.252200E+09 | 0.308015E+09 | 0.00 | 5062871.34 | 15106775.66 | 0.00 | 0.553703E+09 | 0.00 | 1.67 |
September | 0.563603E+09 | 47323394.76 | 0.00 | 7113717.23 | 9955325.29 | 0.00 | 0.142279E+10 | 0.00 | 1.83 |
October | 0.175647E+10 | 1575485.77 | 0.00 | 4424135.37 | 604117.25 | 29471073.32 | 0.181516E+10 | 0.00 | 1.55 |
November | 0.316323E+10 | 0.00 | 0.00 | 954072.99 | 0.00 | 56959361.60 | 0.748543E+09 | 0.00 | 1.04 |
December | 0.310714E+10 | 0.00 | 0.00 | 52817.73 | 0.00 | 0.734554E+09 | 69685653.64 | 0.00 | 0.72 |
Annual Sum or Average | 0.196253E+11 | 0.103957E+10 | 0.00 | 46609744.74 | 56663538.56 | 0.188914E+10 | 0.144824E+11 | 0.00 | 1.40 |
Minimum of Months | 0.138053E+09 | 0.00 | 0.00 | 52817.73 | 0.00 | 0.00 | 69685653.64 | 0.00 | 0.72 |
Maximum of Months | 0.316323E+10 | 0.538167E+09 | 0.00 | 8993680.36 | 24829144.06 | 0.734554E+09 | 0.328215E+10 | 0.00 | 2.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187553E+10 | 0.00 | 0.00 | 9225614.84 | 0.00 | 0.485503E+09 | 0.395342E+10 | 0.00 | 0.94 |
February | 0.158054E+10 | 0.00 | 0.00 | 9183444.31 | 0.00 | 0.186461E+09 | 0.409674E+10 | 0.00 | 1.04 |
March | 0.186251E+10 | 0.00 | 0.00 | 8933300.35 | 0.00 | 34700680.74 | 0.433327E+10 | 0.00 | 1.34 |
April | 0.127540E+10 | 874740.43 | 0.00 | 8583593.35 | 47994.64 | 1078785.81 | 0.338257E+10 | 0.00 | 1.50 |
May | 0.105671E+10 | 12106564.10 | 0.00 | 7237121.30 | 1843455.07 | 0.00 | 0.213179E+10 | 0.00 | 1.23 |
June | 0.568565E+09 | 0.163857E+09 | 0.00 | 4892126.22 | 7790077.10 | 0.00 | 0.730893E+09 | 0.00 | 0.88 |
July | 0.160862E+09 | 0.582211E+09 | 0.00 | 1528591.76 | 49186349.94 | 0.00 | 76358197.98 | 0.00 | 0.75 |
August | 0.297552E+09 | 0.418519E+09 | 0.00 | 4266190.74 | 18916479.74 | 0.00 | 0.425014E+09 | 0.00 | 1.07 |
September | 0.564105E+09 | 0.123341E+09 | 0.00 | 10705878.98 | 6247704.12 | 0.00 | 0.144089E+10 | 0.00 | 1.40 |
October | 0.110883E+10 | 4624011.83 | 0.00 | 15251996.33 | 15855.81 | 20954981.48 | 0.458843E+10 | 0.00 | 1.71 |
November | 0.157455E+10 | 0.00 | 0.00 | 12621842.67 | 0.00 | 20187329.24 | 0.585751E+10 | 0.00 | 1.27 |
December | 0.172409E+10 | 0.00 | 0.00 | 10989226.13 | 0.00 | 0.397405E+09 | 0.464620E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.136492E+11 | 0.130553E+10 | 0.00 | 0.103419E+09 | 84047916.43 | 0.114629E+10 | 0.356631E+11 | 0.00 | 1.16 |
Minimum of Months | 0.160862E+09 | 0.00 | 0.00 | 1528591.76 | 0.00 | 0.00 | 76358197.98 | 0.00 | 0.75 |
Maximum of Months | 0.187553E+10 | 0.582211E+09 | 0.00 | 15251996.33 | 49186349.94 | 0.485503E+09 | 0.585751E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287899E+10 | 0.00 | 0.00 | 569056.99 | 0.00 | 0.889312E+09 | 0.505944E+09 | 0.00 | 0.90 |
February | 0.258238E+10 | 0.00 | 0.00 | 1441483.95 | 0.00 | 0.455279E+09 | 0.848585E+09 | 0.00 | 1.02 |
March | 0.317250E+10 | 0.00 | 0.00 | 2495054.86 | 0.00 | 0.102793E+09 | 0.136224E+10 | 0.00 | 1.49 |
April | 0.202719E+10 | 793606.31 | 0.00 | 5034853.51 | 19926.38 | 2567096.98 | 0.175162E+10 | 0.00 | 1.86 |
May | 0.139162E+10 | 13334727.54 | 0.00 | 5379779.99 | 693880.39 | 742660.46 | 0.160340E+10 | 0.00 | 1.80 |
June | 0.691322E+09 | 0.163434E+09 | 0.00 | 3736213.82 | 7436892.85 | 0.00 | 0.527443E+09 | 0.00 | 1.32 |
July | 0.190290E+09 | 0.466059E+09 | 0.00 | 1027730.75 | 52428426.20 | 0.00 | 49632172.99 | 0.00 | 1.04 |
August | 0.381836E+09 | 0.297340E+09 | 0.00 | 2628987.37 | 17673431.46 | 0.00 | 0.261698E+09 | 0.00 | 1.33 |
September | 0.798138E+09 | 63748766.91 | 0.00 | 5044376.48 | 8548145.01 | 0.00 | 0.780504E+09 | 0.00 | 1.49 |
October | 0.227286E+10 | 2255266.38 | 0.00 | 3858477.06 | 461274.54 | 45726032.10 | 0.126215E+10 | 0.00 | 1.59 |
November | 0.324370E+10 | 0.00 | 0.00 | 1316215.02 | 0.00 | 0.113477E+09 | 0.101448E+10 | 0.00 | 1.16 |
December | 0.283395E+10 | 0.00 | 0.00 | 490905.60 | 0.00 | 0.851977E+09 | 0.512204E+09 | 0.00 | 0.77 |
Annual Sum or Average | 0.224648E+11 | 0.100696E+10 | 0.00 | 33023135.39 | 87261976.82 | 0.246187E+10 | 0.104799E+11 | 0.00 | 1.32 |
Minimum of Months | 0.190290E+09 | 0.00 | 0.00 | 490905.60 | 0.00 | 0.00 | 49632172.99 | 0.00 | 0.77 |
Maximum of Months | 0.324370E+10 | 0.466059E+09 | 0.00 | 5379779.99 | 52428426.20 | 0.889312E+09 | 0.175162E+10 | 0.00 | 1.86 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.260894E+12 | 0.164105E+11 | 0.00 | 0.193394E+12 | 0.296187E+10 |
February | 0.311895E+12 | 0.145261E+11 | 0.00 | 0.186705E+12 | 0.569580E+10 |
March | 0.390906E+12 | 0.134202E+11 | 0.00 | 0.226243E+12 | 0.135542E+11 |
April | 0.472784E+12 | 0.922183E+10 | 0.00 | 0.236062E+12 | 0.568196E+11 |
May | 0.493191E+12 | 0.598447E+10 | 0.00 | 0.193236E+12 | 0.108071E+12 |
June | 0.458793E+12 | 0.179782E+10 | 0.00 | 0.108789E+12 | 0.220293E+12 |
July | 0.469786E+12 | -0.153584E+10 | 0.00 | 0.809233E+10 | 0.285261E+12 |
August | 0.466327E+12 | 0.296070E+09 | 0.00 | 0.556776E+11 | 0.272601E+12 |
September | 0.388389E+12 | 0.301210E+10 | 0.00 | 0.146527E+12 | 0.174274E+12 |
October | 0.330526E+12 | 0.805026E+10 | 0.00 | 0.228700E+12 | 0.747578E+11 |
November | 0.273867E+12 | 0.132314E+11 | 0.00 | 0.228329E+12 | 0.313295E+10 |
December | 0.249120E+12 | 0.159423E+11 | 0.00 | 0.196711E+12 | 0.211494E+10 |
Annual Sum or Average | 0.456648E+13 | 0.100357E+12 | 0.00 | 0.200847E+13 | 0.121954E+13 |
Minimum of Months | 0.249120E+12 | -0.153584E+10 | 0.00 | 0.809233E+10 | 0.211494E+10 |
Maximum of Months | 0.493191E+12 | 0.164105E+11 | 0.00 | 0.236062E+12 | 0.285261E+12 |