Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:35:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2003.08 | 402.05 | 402.05 |
Net Site Energy | 2003.08 | 402.05 | 402.05 |
Total Source Energy | 5890.19 | 1182.25 | 1182.25 |
Net Source Energy | 5890.19 | 1182.25 | 1182.25 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 181.75 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 361.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 111.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 114.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 107.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1785.34 | 217.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 181.75 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 361.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 111.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 114.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 107.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 181.75 | 110.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 361.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 111.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 114.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 107.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.74 | 43.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 358.34 | 43.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 106.74 | 43.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 358.34 | 43.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1785.336 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1785.336 | 100.00 |
Total On-Site and Utility Electric Sources | 1785.336 | 100.00 |
Total Electricity End Uses | 1785.336 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 336.83 |
Time Setpoint Not Met During Occupied Cooling | 99.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2596.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.0546 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 9.0546 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 9.0546 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-07:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 221858.82 | 91491.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7472.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8147.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 272070.38 | 99639.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 221858.82 | 91491.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7472.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8147.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 575.61 | 119.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 745.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1145.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5654.16 | 236.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 115.53 | 24.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1134.88 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 115.53 | 24.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1134.88 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.94 | 0.254520 | 0.300000 | 0.883374 | 0.678720 | 0.500000 | 0.001497 |
CORE_MID VAV BOX COMPONENT | 2.20 | 0.340158 | 0.347000 | 0.764529 | 0.907089 | 0.500000 | 0.001120 |
CORE_TOP VAV BOX COMPONENT | 2.34 | 0.319709 | 0.339000 | 0.794678 | 0.852556 | 0.500000 | 0.001192 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.750122 | 0.210621 | 0.300000 | 0.225037 | 0.561656 | 0.500000 | 0.001809 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.807090 | 0.123929 | 0.300000 | 0.242127 | 0.330477 | 0.500000 | 0.003074 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.01 | 0.156431 | 0.300000 | 0.302993 | 0.417149 | 0.500000 | 0.002436 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.876289 | 0.114135 | 0.300000 | 0.262887 | 0.304360 | 0.500000 | 0.003338 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.598331 | 0.264054 | 0.300000 | 0.179499 | 0.704144 | 0.500000 | 0.001443 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.667065 | 0.149943 | 0.300000 | 0.200119 | 0.399848 | 0.500000 | 0.002541 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.817616 | 0.193234 | 0.300000 | 0.245285 | 0.515292 | 0.500000 | 0.001972 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.687098 | 0.145562 | 0.300000 | 0.206130 | 0.388165 | 0.500000 | 0.002617 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.653066 | 0.241923 | 0.300000 | 0.195920 | 0.645128 | 0.500000 | 0.001575 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.776819 | 0.128758 | 0.300000 | 0.233046 | 0.343355 | 0.500000 | 0.002959 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.908540 | 0.173896 | 0.300000 | 0.272562 | 0.463723 | 0.500000 | 0.002191 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.801104 | 0.124847 | 0.300000 | 0.240331 | 0.332925 | 0.500000 | 0.003052 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29489.77 |
CORE_MID VAV BOX REHEAT COIL | 25522.35 |
CORE_TOP VAV BOX REHEAT COIL | 40288.06 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20291.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13192.77 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20132.53 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13289.59 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14728.97 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9621.10 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14600.10 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9705.38 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15928.35 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10400.95 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15787.75 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10484.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.86 | 1.71 | 5.71 | 1.88 | 5.15 | 5.15 | 0.300000 | 0.365209 | 5.15 |
PACU_VAV_MID | 2.67 | 1.71 | 5.34 | 2.29 | 4.62 | 4.62 | 0.300000 | 0.497163 | 4.62 |
PACU_VAV_TOP | 2.89 | 1.83 | 5.79 | 3.21 | 5.33 | 5.33 | 0.300000 | 0.602317 | 5.33 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.15 |
PACU_VAV_MID_OA_CONTROLLER | 4.62 |
PACU_VAV_TOP_OA_CONTROLLER | 5.33 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.15 | 111088.19 | 0.748347 | 1.72 | 37025.69 | 0.748347 |
PACU_VAV_MID COOLING COIL | 4.62 | 104773.63 | 0.730130 | 1.54 | 34921.05 | 0.730130 |
PACU_VAV_TOP COOLING COIL | 5.33 | 116179.43 | 0.744270 | 1.78 | 38722.60 | 0.744270 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 28623.62 |
PACU_VAV_MID HEATING COIL | 32602.54 |
PACU_VAV_TOP HEATING COIL | 31721.60 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.15 |
PACU_VAV_MID FAN | 4.62 |
PACU_VAV_TOP FAN | 5.33 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.889 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0307E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0369E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1298E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1351E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2373E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2808E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1481 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7209E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1677 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6628E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1082 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5696E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0307E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0371E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1298E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1354E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2374E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2828E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3216E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7307E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8869E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4043E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3539E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2018E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7140E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7379E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3614E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3785E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2243E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2303E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9995E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0520E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3444E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3862E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9208E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9508E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7717E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2202E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9116E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6909E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8036E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1891E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9996E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0523E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3444E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3859E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9205E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9493E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0438E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5962E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5428E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2372E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1166E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0904E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5551E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6234E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1639E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2386E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0909E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1193E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1448 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.1660E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1609 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1022 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1139 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6965E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0788E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5955E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6720E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2855E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.1687E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1020E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2752E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8669E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3629E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2492E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2539E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7059E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8117E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4688E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3413E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1281E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9402E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9963E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1448 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.1652E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1609 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1022 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1139 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6958E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0788E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5953E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6720E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2853E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.1685E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1017E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2754E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8668E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3630E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2491E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2538E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7057E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8118E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4686E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3413E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1279E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9399E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9960E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40844.74808 | 40844.74808 | 2.94458 | 2.94458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8567.46809 | 8567.46809 | 0.36074 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30595.02031 | 30595.02031 | 2.20325 | 2.20325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16967.11151 | 16967.11151 | 0.71921 | 0.71921 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32248.86937 | 32248.86937 | 2.34418 | 2.34418 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 28364.62500 | 28364.62500 | 1.20684 | 1.20684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 10318.46590 | 10318.46590 | 0.75012 | 0.75012 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14246.41588 | 14246.41588 | 0.60785 | 0.60785 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11102.14438 | 11102.14438 | 0.80709 | 0.80709 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9261.83000 | 9261.83000 | 0.39519 | 0.39519 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13893.02634 | 13893.02634 | 1.00998 | 1.00998 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14134.77583 | 14134.77583 | 0.60308 | 0.60308 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12054.06931 | 12054.06931 | 0.87629 | 0.87629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9329.64810 | 9329.64810 | 0.39809 | 0.39809 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8230.83064 | 8230.83064 | 0.59833 | 0.59833 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10348.13240 | 10348.13240 | 0.44121 | 0.44121 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9176.41646 | 9176.41646 | 0.66706 | 0.66706 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 28.86867 | 1.41138E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6758.89056 | 6758.89056 | 0.28820 | 0.28820 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11247.43996 | 11247.43996 | 0.81762 | 0.81762 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.41193E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10257.87736 | 10257.87736 | 0.43735 | 0.43735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9452.01356 | 9452.01356 | 0.68710 | 0.68710 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6817.91355 | 6817.91355 | 0.29073 | 0.29073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8983.52017 | 8983.52017 | 0.65307 | 0.65307 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11189.19479 | 11189.19479 | 0.47714 | 0.47714 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10685.92616 | 10685.92616 | 0.77682 | 0.77682 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7305.77613 | 7305.77613 | 0.31156 | 0.31156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12497.85371 | 12497.85371 | 0.90854 | 0.90854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11090.71975 | 11090.71975 | 0.47293 | 0.47293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11020.00175 | 11020.00175 | 0.80110 | 0.80110 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7364.22334 | 7364.22334 | 0.31406 | 0.31406 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 80773.93 | 5.15371 | 5.15371 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 31589.96 | 1.88218 | 1.88218 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 74218.52 | 4.61600 | 4.61600 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 33736.56 | 2.29490 | 2.29490 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 83885.13 | 5.33116 | 5.33116 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 33926.16 | 3.21105 | 3.21105 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.94458 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25452 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.88337 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67872 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49694E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29489.77122 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20325 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34016 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34700 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76453 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90709 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12007E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25522.34930 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34418 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31971 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79468 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85256 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19171E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 40288.06240 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75012 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21062 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22504 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56166 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80894E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20291.90214 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80709 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12393 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24213 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33048 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07434E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13192.76892 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00998 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15643 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30299 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41715 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43558E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20132.52742 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87629 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11413 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26289 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30436 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33815E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13289.58585 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59833 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26405 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17950 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70414 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44289E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14728.97029 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66706 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14994 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20012 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39985 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54096E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9621.09923 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81762 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19323 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24528 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51529 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97170E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14600.09616 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68710 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14556 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20613 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38816 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61745E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9705.37717 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65307 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24192 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19592 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64513 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57488E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15928.34657 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77682 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12876 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23305 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34336 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.95904E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10400.94822 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90854 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17390 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27256 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46372 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19096E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15787.75417 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80110 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12485 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24033 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33292 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05174E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10484.39446 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.85735 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.71441 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.71469 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88218 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.15371 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.15371 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.36521 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.67139 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70639 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.34278 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.29490 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.61600 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.61600 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.49716 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.89383 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.82772 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.78766 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.21105 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.33116 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.33116 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.60232 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.15371 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.61600 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.33116 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.15371 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.15371 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111088.19021 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74835 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.71773 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37025.69380 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74835 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 28623.62236 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.15371 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.61600 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.61600 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104773.63474 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73013 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53851 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34921.05246 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73013 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 32602.53941 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.61600 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.33116 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.33116 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 116179.42596 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74427 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.77688 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 38722.60267 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74427 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 31721.60363 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.33116 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 110380.77 | 376634.81 | 11.37 | 2.92 | 3.25 | 3.43 | 3.59 | 9.95 | 11.11 | 11.70 | 12.24 | 5.9580 | 4.7527 | 3.1958 | 1.3122 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 104295.69 | 355871.67 | 11.47 | 2.94 | 3.29 | 3.46 | 3.61 | 10.02 | 11.21 | 11.82 | 12.31 | 5.3364 | 4.2483 | 2.8576 | 1.1937 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 115485.01 | 394051.20 | 11.39 | 2.92 | 3.26 | 3.44 | 3.59 | 9.97 | 11.13 | 11.72 | 12.25 | 6.1632 | 4.9103 | 3.3086 | 1.3619 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.4199366295E-002 | 3.3246815100E-002 | Pass | Pass | 0.4855308395 | 0.4902903527 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2217069945 | 0.1629227024 | Pass | Pass | 0.4878983633 | 0.4889481671 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1195698275 | 7.3722651296E-002 | Pass | Pass | 0.4864107368 | 0.4817023026 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1047261864 | 6.6269494715E-002 | Pass | Pass | 0.4866655691 | 0.4792632618 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.7231594625E-003 | 6.3884846183E-003 | Pass | Pass | 0.4924657597 | 0.4900048901 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1078655571 | 0.1224871085 | Pass | Pass | 2.5757624572 | 11.9407084192 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6743094745 | 0.6108490371 | Pass | Pass | 0.6953633289 | 0.6061453624 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6071307873 | 0.6491902459 | Pass | Pass | 0.7786477521 | 0.7714200796 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4985424632 | 0.5810317146 | Pass | Pass | 2.2112217986 | 17.3038576457 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6751027870 | 0.6799541857 | Pass | Pass | 0.7749124972 | 0.8067260573 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4179989346 | 0.3993886262 | Pass | Pass | 3.2538338704 | 28.6203959287 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3344661458 | 0.4002163074 | Pass | Pass | 1.2466299195 | 3.1558112744 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2452526836 | 0.2837419498 | Pass | Pass | 1.9858921545 | 15.3714389476 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4059420862 | 0.4258441842 | Pass | Pass | 2.7698024760 | 23.0554261904 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5039909071 | 0.4719936286 | Pass | Pass | 0.7743453819 | 0.7172429163 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4409180925 | 0.4991906902 | Pass | Pass | 0.9057518111 | 1.0783537473 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3714162982 | 0.4233359134 | Pass | Pass | 0.7868183513 | 0.9273835301 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5023670922 | 0.5131106613 | Pass | Pass | 0.8347563281 | 0.8982041434 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3632.50 | 141.51 | 0.00 | 1640.29 | 1210.71 | 6625.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.83 | 0.0000 | Y | 11.92 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.81 | 0.0000 | Y | 7.54 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.65 | 0.0000 | Y | 11.86 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.66 | 0.0000 | Y | 7.51 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.79 | 0.0000 | Y | 11.91 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.78 | 0.0000 | Y | 7.54 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.62 | 0.0000 | Y | 11.85 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.63 | 0.0000 | Y | 7.50 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.83 | 0.0000 | Y | 11.92 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.81 | 0.0000 | Y | 7.54 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.65 | 0.0000 | Y | 11.86 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.66 | 0.0000 | Y | 7.51 |
Interior Lighting Total | 9.0546 | 4982.19 | 45111.81 | 361.57 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.25 | AstronomicalClock | - | 42.43 | 42.43 | 3.38 | |
EXTERIOR_LIGHTS_B | 8043.62 | AstronomicalClock | - | 83.64 | 71.28 | 107.63 | |
Exterior Lighting Total | 8467.87 | 111.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111088.19 | 83132.56 | 27955.63 | 0.75 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104773.63 | 76498.42 | 28275.22 | 0.73 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 116179.43 | 86468.90 | 29710.52 | 0.74 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 110380.8 | 2.92 | 9.95 | N/A | N/A | 11.37 | |
PACU_VAV_MID COOLING COIL | 104295.7 | 2.94 | 10.02 | N/A | N/A | 11.47 | |
PACU_VAV_TOP COOLING COIL | 115485.0 | 2.92 | 9.97 | N/A | N/A | 11.39 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 29489.77 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25522.35 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 40288.06 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20291.90 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13192.77 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20132.53 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13289.59 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14728.97 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9621.10 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14600.10 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9705.38 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15928.35 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10400.95 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15787.75 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10484.39 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 28623.62 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 32602.54 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 31721.60 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.15 | 11208.74 | 2174.89 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.62 | 10678.60 | 2313.39 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.33 | 11594.69 | 2174.89 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110380.77 | 2.92 | 9.95 | 11.37 | 5.9580 | 3.25 | 11.11 | 4.7527 | 3.43 | 11.70 | 3.1958 | 3.59 | 12.24 | 1.3122 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104295.69 | 2.94 | 10.02 | 11.47 | 5.3364 | 3.29 | 11.21 | 4.2483 | 3.46 | 11.82 | 2.8576 | 3.61 | 12.31 | 1.1937 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 115485.01 | 2.92 | 9.97 | 11.39 | 6.1632 | 3.26 | 11.13 | 4.9103 | 3.44 | 11.72 | 3.3086 | 3.59 | 12.25 | 1.3619 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40844.75 | 40844.75 | 41.53 | 2.945 | 2.945 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 30595.02 | 30595.02 | 31.11 | 2.203 | 2.203 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 32248.87 | 32248.87 | 32.79 | 2.344 | 2.344 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00887 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10318.47 | 10318.47 | 49.77 | 0.750 | 0.750 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00902 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11102.14 | 11102.14 | 84.58 | 0.807 | 0.807 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00882 | 28.45 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13893.03 | 13893.03 | 67.01 | 1.010 | 1.010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00889 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12054.07 | 12054.07 | 91.84 | 0.876 | 0.876 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00880 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8230.83 | 8230.83 | 39.70 | 0.598 | 0.598 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00899 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9176.42 | 9176.42 | 69.91 | 0.667 | 0.667 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00879 | 28.87 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11247.44 | 11247.44 | 54.25 | 0.818 | 0.818 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00886 | 31.92 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9452.01 | 9452.01 | 72.01 | 0.687 | 0.687 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00878 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8983.52 | 8983.52 | 43.33 | 0.653 | 0.653 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00904 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10685.93 | 10685.93 | 81.41 | 0.777 | 0.777 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00880 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12497.85 | 12497.85 | 60.28 | 0.909 | 0.909 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00889 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11020.00 | 11020.00 | 83.96 | 0.801 | 0.801 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00879 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8567.47 | 8567.47 | 8.71 | 0.361 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 16967.11 | 16967.11 | 17.25 | 0.719 | 0.719 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 28364.62 | 28364.62 | 28.84 | 1.207 | 1.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14246.42 | 14246.42 | 68.71 | 0.608 | 0.608 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9261.83 | 9261.83 | 70.56 | 0.395 | 0.395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14134.78 | 14134.78 | 68.17 | 0.603 | 0.603 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9329.65 | 9329.65 | 71.08 | 0.398 | 0.398 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10348.13 | 10348.13 | 49.91 | 0.441 | 0.441 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6758.89 | 6758.89 | 51.49 | 0.288 | 0.288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10257.88 | 10257.88 | 49.47 | 0.437 | 0.437 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00749 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6817.91 | 6817.91 | 51.94 | 0.291 | 0.291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11189.19 | 11189.19 | 53.97 | 0.477 | 0.477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00733 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7305.78 | 7305.78 | 55.66 | 0.312 | 0.312 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11090.72 | 11090.72 | 53.49 | 0.473 | 0.473 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7364.22 | 7364.22 | 56.11 | 0.314 | 0.314 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.15 | 5.15 | 1.88 | 1.88 | 5.1537 | 1.8822 | 5.1537 | 0.3652 | 0.3000 |
PACU_VAV_MID | 4.62 | 4.62 | 2.29 | 2.29 | 4.6160 | 2.2949 | 4.6160 | 0.4972 | 0.3000 |
PACU_VAV_TOP | 5.33 | 5.33 | 3.21 | 3.21 | 5.3312 | 3.2111 | 5.3312 | 0.6023 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29489.771 | 29489.771 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29489.77 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 8567.47 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25522.349 | 25522.349 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25522.35 | 24009.56 | 0.719213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 16967.11 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 40288.062 | 40288.062 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40288.06 | 40288.06 | 1.206840 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28364.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20291.902 | 20291.902 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20291.90 | 20291.90 | 0.607850 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00737291 | 47.6984 | 14246.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13192.769 | 13192.769 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13192.77 | 13192.77 | 0.395193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00735896 | 47.6096 | 9261.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20132.527 | 20132.527 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20132.53 | 20132.53 | 0.603075 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00736832 | 47.6691 | 14134.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13289.586 | 13289.586 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13289.59 | 13289.59 | 0.398093 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00736325 | 47.6370 | 9329.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14728.970 | 14728.970 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14728.97 | 14728.97 | 0.441210 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749805 | 48.4948 | 10348.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9621.099 | 9621.099 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9621.10 | 9621.10 | 0.288203 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749443 | 48.4718 | 6758.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14600.096 | 14600.096 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14600.10 | 14600.10 | 0.437350 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749208 | 48.4567 | 10257.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9705.377 | 9705.377 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9705.38 | 9705.38 | 0.290727 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749995 | 48.5070 | 6817.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 15928.347 | 15928.347 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15928.35 | 15928.35 | 0.477138 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732644 | 47.4003 | 11189.19 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10400.948 | 10400.948 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10400.95 | 10400.95 | 0.311563 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00731663 | 47.3378 | 7305.78 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 15787.754 | 15787.754 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15787.75 | 15787.75 | 0.472927 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732029 | 47.3609 | 11090.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10484.394 | 10484.394 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10484.39 | 10484.39 | 0.314063 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732209 | 47.3727 | 7364.22 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 111088.190 | 83132.556 | 5.153707 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 113302.71 | 89598.99 | 5.153707 | 25.76 | 18.23 | 0.01000087 | 11.03 | 11.03 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 21.7284 | 24.00 | 0.00885748 | 47.6352 | 70897.93 | 0.00 | 114546.84 | 84412.07 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 28623.622 | 28623.622 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28623.62 | 28623.62 | 1.546112 | -2.51 | -2.51 | 0.00307875 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 72.4281 | 19.60 | 0.00678827 | 47.9225 | 19855.46 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 104773.635 | 76498.418 | 4.616004 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 107686.65 | 82381.56 | 4.616004 | 26.10 | 18.57 | 0.01028370 | 10.92 | 10.92 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 25.8919 | 24.00 | 0.00894321 | 48.0904 | 63489.29 | 0.00 | 108035.68 | 77739.14 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 32602.539 | 32602.539 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32602.54 | 32602.54 | 1.384801 | -6.67 | -6.67 | 0.00227166 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 86.3063 | 19.39 | 0.00683056 | 48.8624 | 25294.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 116179.426 | 86468.901 | 5.331165 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 118703.68 | 92985.39 | 5.331165 | 25.82 | 18.31 | 0.01007530 | 11.03 | 11.03 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.4186 | 24.00 | 0.00890601 | 47.8934 | 73307.62 | 0.00 | 119796.58 | 87820.33 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 31721.604 | 31721.604 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31721.60 | 31721.60 | 1.599349 | -3.60 | -3.60 | 0.00291717 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 74.7285 | 17.60 | 0.00681777 | 54.5505 | 26821.03 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 29489.771 | 29489.771 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29489.77 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29489.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 8567.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25522.349 | 25522.349 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25522.35 | 24009.56 | 1.0000 | 0.86564125 | 0.719213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25522.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 16967.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 40288.062 | 40288.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40288.06 | 40288.06 | 1.0000 | 1.45254674 | 1.206840 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40288.06 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28364.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20291.902 | 20291.902 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20291.90 | 20291.90 | 1.0000 | 0.73160471 | 0.607850 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20291.90 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00737291 | 21.00 | 0.00737291 | 47.6984 | 14246.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13192.769 | 13192.769 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13192.77 | 13192.77 | 1.0000 | 0.47565240 | 0.395193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13192.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00735896 | 21.00 | 0.00735896 | 47.6096 | 9261.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20132.527 | 20132.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20132.53 | 20132.53 | 1.0000 | 0.72585861 | 0.603075 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20132.53 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00736832 | 21.00 | 0.00736832 | 47.6691 | 14134.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13289.586 | 13289.586 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13289.59 | 13289.59 | 1.0000 | 0.47914304 | 0.398093 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13289.59 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00736325 | 21.00 | 0.00736325 | 47.6370 | 9329.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14728.970 | 14728.970 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14728.97 | 14728.97 | 1.0000 | 0.53103864 | 0.441210 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14728.97 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749805 | 21.00 | 0.00749805 | 48.4948 | 10348.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9621.099 | 9621.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9621.10 | 9621.10 | 1.0000 | 0.34687934 | 0.288203 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9621.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749443 | 21.00 | 0.00749443 | 48.4718 | 6758.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14600.096 | 14600.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14600.10 | 14600.10 | 1.0000 | 0.52639221 | 0.437350 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14600.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749208 | 21.00 | 0.00749208 | 48.4567 | 10257.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9705.377 | 9705.377 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9705.38 | 9705.38 | 1.0000 | 0.34991790 | 0.290727 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9705.38 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749995 | 21.00 | 0.00749995 | 48.5070 | 6817.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15928.347 | 15928.347 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15928.35 | 15928.35 | 1.0000 | 0.57428098 | 0.477138 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15928.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732644 | 21.00 | 0.00732644 | 47.4003 | 11189.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10400.948 | 10400.948 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10400.95 | 10400.95 | 1.0000 | 0.37499603 | 0.311563 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10400.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00731663 | 21.00 | 0.00731663 | 47.3378 | 7305.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15787.754 | 15787.754 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15787.75 | 15787.75 | 1.0000 | 0.56921206 | 0.472927 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15787.75 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732029 | 21.00 | 0.00732029 | 47.3609 | 11090.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10484.394 | 10484.394 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10484.39 | 10484.39 | 1.0000 | 0.37800460 | 0.314063 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10484.39 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00732209 | 21.00 | 0.00732209 | 47.3727 | 7364.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111088.190 | 83132.556 | 5.153707 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4311 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.153707 | 6.20297569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 113302.71 | 89598.99 | 1.0199 | 6.20297569 | 5.153707 | 25.76 | 18.23 | 0.01000087 | 51374.0 | 11.03 | 11.03 | 0.00850000 | 32520.1 | -999.0 | -999.00 | -999.00 | -999.00 | 11208.737 | 102093.97 | 32.10 | 0.01411964 | 23.13 | 1.11982000 | 21.7284 | 24.00 | 0.00885748 | 24.00 | 0.00885748 | 47.6352 | 70897.93 | 0.00 | 114546.84 | 84412.07 | 5.95800504 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.80 | 12.79 | 0.00920159 | 36096.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28623.622 | 28623.622 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.153707 | 6.20297569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 28623.62 | 28623.62 | 1.0000 | 1.86089271 | 1.546112 | -2.51 | -2.51 | 0.00307875 | 5166.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28623.62 | -10.70 | 0.00150390 | -10.70 | 1.11982000 | 72.4281 | 19.01 | 0.00721570 | 19.60 | 0.00678827 | 47.9225 | 19855.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104773.635 | 76498.418 | 4.616004 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9569 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.616004 | 5.55579888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 107686.65 | 82381.56 | 1.0278 | 5.55579888 | 4.616004 | 26.10 | 18.57 | 0.01028370 | 52440.4 | 10.92 | 10.92 | 0.00850000 | 32406.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10678.601 | 97008.05 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 25.8919 | 24.00 | 0.00894321 | 24.00 | 0.00894321 | 48.0904 | 63489.29 | 0.00 | 108035.68 | 77739.14 | 5.33638682 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.41 | 12.39 | 0.00895870 | 35077.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32602.539 | 32602.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.616004 | 5.55579888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32602.54 | 32602.54 | 1.0000 | 1.66673966 | 1.384801 | -6.67 | -6.67 | 0.00227166 | -1045.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32602.54 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 86.3063 | 18.76 | 0.00711055 | 19.39 | 0.00683056 | 48.8624 | 25294.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 116179.426 | 86468.901 | 5.331165 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5695 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.331165 | 6.41656300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 118703.68 | 92985.39 | 1.0217 | 6.41656300 | 5.331165 | 25.82 | 18.31 | 0.01007530 | 51621.4 | 11.03 | 11.03 | 0.00850000 | 32520.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11594.688 | 107108.99 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 22.4186 | 24.00 | 0.00890601 | 24.00 | 0.00890601 | 47.8934 | 73307.62 | 0.00 | 119796.58 | 87820.33 | 6.16315727 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.72 | 12.71 | 0.00915045 | 35884.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31721.604 | 31721.604 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.331165 | 6.41656300 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31721.60 | 31721.60 | 1.0000 | 1.92496890 | 1.599349 | -3.60 | -3.60 | 0.00291717 | 3659.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31721.60 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 74.7285 | 17.40 | 0.00709624 | 17.60 | 0.00681777 | 54.5505 | 26821.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.15 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.62 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.33 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2516.17 | 2482.17 | 49.67 |
CORE_MID | 2436.50 | 3178.00 | 375.33 |
CORE_TOP | 2884.83 | 3472.17 | 1024.33 |
PERIMETER_TOP_ZN_3 | 3747.33 | 3889.17 | 2106.17 |
PERIMETER_TOP_ZN_2 | 3626.33 | 3852.50 | 1879.17 |
PERIMETER_TOP_ZN_1 | 3428.83 | 3503.50 | 1541.83 |
PERIMETER_TOP_ZN_4 | 3508.00 | 3986.67 | 1931.67 |
PERIMETER_BOT_ZN_3 | 3481.83 | 3740.83 | 1731.50 |
PERIMETER_BOT_ZN_2 | 3354.17 | 3551.00 | 1423.50 |
PERIMETER_BOT_ZN_1 | 3283.33 | 3795.00 | 1557.33 |
PERIMETER_BOT_ZN_4 | 3396.33 | 3648.83 | 1515.33 |
PERIMETER_MID_ZN_3 | 3459.67 | 3635.17 | 1628.83 |
PERIMETER_MID_ZN_2 | 2802.83 | 3219.17 | 1344.83 |
PERIMETER_MID_ZN_1 | 3222.83 | 3193.00 | 1110.83 |
PERIMETER_MID_ZN_4 | 3269.67 | 3753.00 | 1512.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4974.00 | 4654.00 | 2596.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_MID | 2.33 | 0.00 | 1.83 | 0.00 |
CORE_TOP | 2.33 | 0.00 | 1.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 47.50 | 2.67 | 17.83 | 2.33 |
PERIMETER_TOP_ZN_2 | 35.33 | 18.17 | 5.17 | 18.17 |
PERIMETER_TOP_ZN_1 | 26.17 | 18.50 | 4.17 | 18.17 |
PERIMETER_TOP_ZN_4 | 36.33 | 17.83 | 8.83 | 13.67 |
PERIMETER_BOT_ZN_3 | 14.67 | 0.00 | 8.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 6.67 | 9.33 | 1.17 | 9.33 |
PERIMETER_BOT_ZN_1 | 329.67 | 41.83 | 324.50 | 41.83 |
PERIMETER_BOT_ZN_4 | 7.50 | 10.50 | 2.00 | 7.67 |
PERIMETER_MID_ZN_3 | 17.00 | 0.00 | 7.00 | 0.00 |
PERIMETER_MID_ZN_2 | 11.17 | 16.33 | 2.17 | 16.33 |
PERIMETER_MID_ZN_1 | 8.50 | 16.33 | 1.17 | 16.17 |
PERIMETER_MID_ZN_4 | 12.17 | 15.50 | 3.00 | 12.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 374.50 | 106.67 | 336.83 | 99.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.840 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.602 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.593 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.784 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.310 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.205 | 0.106 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.398 | 0.112 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.622 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.084 | 0.060 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.958 | 1.332 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.095 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.734 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.211 | 0.099 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.165 | 0.089 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.329 | 0.093 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13404608.49 | 0.00 | 13404608.49 | 0.00 | 13404608.49 | 13393058.27 | 5790.22 | 96.63 | 2873.15 | 78.25 |
CORE_MID | 9550109.45 | 0.00 | 9550109.45 | 0.00 | 9550109.45 | 13393058.27 | 6909.07 | 37.93 | 1813.00 | 62.99 |
CORE_TOP | 9394480.96 | 0.00 | 9394480.96 | 0.00 | 9394480.96 | 13393058.27 | 6939.52 | 28.84 | 1791.63 | 70.90 |
PERIMETER_TOP_ZN_3 | 2620039.96 | 0.00 | 2620039.96 | 696839.46 | 3316879.42 | 2823374.22 | 4291.41 | 17.67 | 4450.91 | 70.90 |
PERIMETER_TOP_ZN_2 | 2774145.69 | 0.00 | 2774145.69 | 464556.85 | 3238702.54 | 1787429.43 | 4172.61 | 2.15 | 4585.24 | 70.90 |
PERIMETER_TOP_ZN_1 | 4023650.62 | 0.00 | 4023650.62 | 696839.46 | 4720490.08 | 2823374.22 | 4212.70 | 9.64 | 4537.66 | 70.90 |
PERIMETER_TOP_ZN_4 | 2963362.77 | 0.00 | 2963362.77 | 464556.85 | 3427919.61 | 1787312.18 | 4176.66 | 9.94 | 4573.40 | 70.90 |
PERIMETER_BOT_ZN_3 | 2103903.22 | 0.00 | 2103903.22 | 370505.73 | 2474408.95 | 2823374.22 | 6463.27 | 80.77 | 2215.96 | 78.25 |
PERIMETER_BOT_ZN_2 | 2320995.59 | 0.00 | 2320995.59 | 247002.33 | 2567997.93 | 1787429.43 | 4207.76 | 22.54 | 4529.70 | 78.25 |
PERIMETER_BOT_ZN_1 | 3238253.72 | 0.00 | 3238253.72 | 4635841.98 | 7874095.69 | 2823374.22 | 4345.31 | 28.87 | 4385.82 | 78.25 |
PERIMETER_BOT_ZN_4 | 2346626.81 | 0.00 | 2346626.81 | 247002.33 | 2593629.15 | 1787312.18 | 4296.26 | 39.24 | 4424.50 | 78.25 |
PERIMETER_MID_ZN_3 | 2458361.28 | 0.00 | 2458361.28 | 580065.25 | 3038426.53 | 2823374.22 | 4322.59 | 53.13 | 4384.29 | 62.99 |
PERIMETER_MID_ZN_2 | 2746094.80 | 0.00 | 2746094.80 | 386707.84 | 3132802.64 | 1787429.43 | 4103.61 | 3.58 | 4652.82 | 971.99 |
PERIMETER_MID_ZN_1 | 3897484.77 | 0.00 | 3897484.77 | 580065.25 | 4477550.02 | 2823374.22 | 4177.95 | 13.92 | 4568.14 | 62.99 |
PERIMETER_MID_ZN_4 | 2822858.08 | 0.00 | 2822858.08 | 386707.84 | 3209565.92 | 1787312.18 | 4117.02 | 12.94 | 4630.03 | 62.99 |
Total Facility | 66664976.23 | 0.00 | 66664976.23 | 9756691.16 | 76421667.39 | 67843644.98 | 7084.56 | 412.11 | 4749.70 | 1072.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6172 | 0.0000 | 0.6172 | 0.0000 | 0.6172 | 0.4247 | 3029.62 | 96.63 | 2816.76 |
CORE_MID | 0.4425 | 0.0000 | 0.4425 | 0.0000 | 0.4425 | 0.4247 | 4116.43 | 37.93 | 1788.64 |
CORE_TOP | 0.4365 | 0.0000 | 0.4365 | 0.0000 | 0.4365 | 0.4247 | 4137.87 | 28.84 | 1776.29 |
PERIMETER_TOP_ZN_3 | 0.1218 | 0.0000 | 0.1218 | 0.0166 | 0.1384 | 0.0895 | 1489.76 | 17.67 | 4435.57 |
PERIMETER_TOP_ZN_2 | 0.1289 | 0.0000 | 0.1289 | 0.0111 | 0.1400 | 0.0567 | 1370.96 | 2.15 | 4569.89 |
PERIMETER_TOP_ZN_1 | 0.1871 | 0.0000 | 0.1871 | 0.0166 | 0.2037 | 0.0895 | 1411.05 | 9.64 | 4522.31 |
PERIMETER_TOP_ZN_4 | 0.1377 | 0.0000 | 0.1377 | 0.0111 | 0.1487 | 0.0567 | 1375.01 | 9.94 | 4558.05 |
PERIMETER_BOT_ZN_3 | 0.0967 | 0.0000 | 0.0967 | 0.0088 | 0.1055 | 0.0895 | 3702.34 | 80.44 | 2160.23 |
PERIMETER_BOT_ZN_2 | 0.1066 | 0.0000 | 0.1066 | 0.0059 | 0.1125 | 0.0567 | 1447.23 | 22.54 | 4473.23 |
PERIMETER_BOT_ZN_1 | 0.1491 | 0.0000 | 0.1491 | 0.2082 | 0.3573 | 0.0895 | 1584.71 | 28.87 | 4329.43 |
PERIMETER_BOT_ZN_4 | 0.1078 | 0.0000 | 0.1078 | 0.0059 | 0.1136 | 0.0567 | 1535.73 | 39.24 | 4368.03 |
PERIMETER_MID_ZN_3 | 0.1140 | 0.0000 | 0.1140 | 0.0138 | 0.1278 | 0.0895 | 1529.94 | 53.13 | 4359.93 |
PERIMETER_MID_ZN_2 | 0.1193 | 0.0000 | 0.1193 | 0.0098 | 0.1291 | 0.0567 | 1310.12 | 3.52 | 3720.36 |
PERIMETER_MID_ZN_1 | 0.1809 | 0.0000 | 0.1809 | 0.0138 | 0.1947 | 0.0895 | 1385.31 | 13.92 | 4543.78 |
PERIMETER_MID_ZN_4 | 0.1308 | 0.0000 | 0.1308 | 0.0092 | 0.1400 | 0.0567 | 1324.52 | 12.92 | 4605.56 |
Total Facility | 3.0767 | 0.0000 | 3.0767 | 0.3308 | 3.4074 | 2.1513 | 4274.65 | 411.70 | 4683.62 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33919042.46 | 0.00 | 33919042.46 | 22614548.33 | 4093.62 | 5.06 | 4661.32 | 77.93 |
PACU_VAV_MID | 31109448.21 | 0.00 | 31109448.21 | 22614548.33 | 4127.87 | 0.95 | 4631.18 | 62.99 |
PACU_VAV_TOP | 31545148.81 | 0.00 | 31545148.81 | 22614548.33 | 4182.05 | 1.54 | 4576.41 | 70.46 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5606 | 0.0000 | 1.5606 | 0.7171 | 1333.02 | 5.06 | 4604.92 |
PACU_VAV_MID | 1.4420 | 0.0000 | 1.4420 | 0.7171 | 1335.23 | 0.95 | 4606.82 |
PACU_VAV_TOP | 1.4660 | 0.0000 | 1.4660 | 0.7171 | 1380.40 | 1.54 | 4561.06 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2603.69 | 0.00 | 0.00 | 0.00 | 2132.82 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2220.24 | 0.00 | 0.00 | 0.00 | 2518.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2266.41 | 0.00 | 0.00 | 0.00 | 2492.27 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.7185 | 0.0000 | 0.0000 | 0.0000 | 1.1306 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.5897 | 0.0000 | 0.0000 | 0.0000 | 1.1851 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.6233 | 0.0000 | 0.0000 | 0.0000 | 1.1855 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1785.34 | 16005.15 | 26-MAR-17:10 | 272070.38 | 02-JAN-07:10 |
Electricity:Building | 1123.61 | 15718.93 | 01-JAN-08:20 | 82022.57 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 329.05 | 4741.03 | 01-JAN-00:10 | 25654.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1123.61 | 15718.93 | 01-JAN-08:20 | 82022.57 | 03-JAN-08:10 |
InteriorLights:Electricity | 361.57 | 1693.55 | 01-JAN-08:20 | 36137.71 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 361.57 | 1693.55 | 01-JAN-08:20 | 36137.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 361.57 | 1693.55 | 01-JAN-08:20 | 36137.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 361.57 | 1693.55 | 01-JAN-08:20 | 36137.71 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 38.61 | 553.47 | 01-JAN-08:20 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.92 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.92 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.44 | 350.37 | 01-JAN-07:50 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 38.55 | 553.47 | 01-JAN-07:50 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.86 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.86 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.40 | 350.37 | 01-JAN-08:20 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.51 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.51 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 38.60 | 553.47 | 01-JAN-08:20 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.91 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.91 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.43 | 350.37 | 01-JAN-07:50 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 38.53 | 553.47 | 01-JAN-07:50 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.85 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.85 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.40 | 350.37 | 01-JAN-08:20 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.50 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.50 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 38.61 | 553.47 | 01-JAN-08:20 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.92 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.92 | 51.50 | 01-JAN-08:20 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 24.44 | 350.37 | 01-JAN-07:50 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.54 | 32.61 | 01-JAN-07:50 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 38.55 | 553.47 | 01-JAN-07:50 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.86 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.86 | 51.50 | 01-JAN-07:50 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.40 | 350.37 | 01-JAN-08:20 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.51 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.51 | 32.60 | 01-JAN-08:20 | 952.03 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 550.70 | 286.22 | 04-JUL-14:50 | 229702.75 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1358.60 | 02-JAN-16:50 |
Transformer:ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1358.60 | 02-JAN-16:50 |
ElectricityPurchased:Facility | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
ElectricityNet:Plant | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1785.34 | 16005.15 | 04-JUL-17:30 | 272070.38 | 02-JAN-07:10 |
Heating:Electricity | 181.75 | 0.00 | 01-JAN-00:40 | 221858.82 | 02-JAN-07:10 |
General:Heating:Electricity | 181.75 | 0.00 | 01-JAN-00:40 | 221858.82 | 02-JAN-07:10 |
Fans:Electricity | 114.51 | 0.00 | 01-JAN-00:40 | 28374.89 | 10-JUL-16:00 |
General:Fans:Electricity | 114.51 | 0.00 | 01-JAN-00:40 | 28374.89 | 10-JUL-16:00 |
ExteriorLights:Electricity | 111.00 | 0.00 | 01-JAN-07:30 | 8467.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 111.00 | 0.00 | 01-JAN-07:30 | 8467.87 | 01-JAN-06:10 |
Cooling:Electricity | 235.51 | 0.00 | 01-JAN-00:10 | 85255.29 | 19-JUN-12:20 |
General:Cooling:Electricity | 235.51 | 0.00 | 01-JAN-00:10 | 85255.29 | 19-JUN-12:20 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.16 | 0.00 | 01-JAN-00:10 | 1015.47 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 217.74 | 1156.00 | 06-FEB-05:30 | 99639.22 | 06-FEB-08:00 |
NaturalGas:HVAC | 110.46 | 0.00 | 01-JAN-00:40 | 91491.26 | 06-FEB-08:00 |
Heating:NaturalGas | 110.46 | 0.00 | 01-JAN-00:40 | 91491.26 | 06-FEB-08:00 |
General:Heating:NaturalGas | 110.46 | 0.00 | 01-JAN-00:40 | 91491.26 | 06-FEB-08:00 |
NaturalGas:Plant | 107.28 | 1156.00 | 04-JAN-18:20 | 9472.99 | 07-FEB-12:10 |
WaterSystems:NaturalGas | 107.28 | 1156.00 | 04-JAN-18:20 | 9472.99 | 07-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 107.28 | 1156.00 | 04-JAN-18:20 | 9472.99 | 07-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2544.30 | 0.00 | 01-JAN-00:40 | 498527.79 | 02-JAN-07:10 |
EnergyTransfer:Building | 1272.17 | 0.00 | 01-JAN-00:40 | 221888.50 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 246.23 | 0.00 | 01-JAN-00:40 | 28239.93 | 07-AUG-08:00 |
Heating:EnergyTransfer | 126.06 | 0.00 | 01-JAN-00:40 | 221888.50 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.29 | 0.00 | 01-JAN-00:10 | 21354.12 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 126.06 | 0.00 | 01-JAN-00:40 | 221888.50 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.29 | 0.00 | 01-JAN-00:10 | 21354.12 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 1146.11 | 0.00 | 01-JAN-00:40 | 180721.87 | 14-AUG-14:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 245.93 | 0.00 | 01-JAN-00:40 | 28239.93 | 07-AUG-08:00 |
General:Cooling:EnergyTransfer | 1146.11 | 0.00 | 01-JAN-00:40 | 180721.87 | 14-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 245.93 | 0.00 | 01-JAN-00:40 | 28239.93 | 07-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.67 | 0.00 | 01-JAN-00:40 | 16177.98 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.33 | 0.00 | 01-JAN-00:40 | 16177.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.33 | 0.00 | 01-JAN-00:40 | 16177.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.34 | 0.00 | 01-JAN-00:10 | 13042.54 | 19-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.34 | 0.00 | 01-JAN-00:10 | 13042.54 | 19-JUN-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.14 | 0.00 | 01-JAN-00:40 | 10717.28 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.47 | 0.00 | 01-JAN-00:40 | 10717.28 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.47 | 0.00 | 01-JAN-00:40 | 10717.28 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.67 | 0.00 | 01-JAN-00:10 | 6064.19 | 14-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.67 | 0.00 | 01-JAN-00:10 | 6064.19 | 14-AUG-14:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.20 | 0.00 | 01-JAN-00:40 | 8543.44 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.82 | 0.00 | 01-JAN-00:40 | 8543.44 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.82 | 0.00 | 01-JAN-00:40 | 8543.44 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.38 | 0.00 | 01-JAN-00:10 | 6141.70 | 10-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.38 | 0.00 | 01-JAN-00:10 | 6141.70 | 10-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 164.27 | 0.00 | 01-JAN-00:40 | 21745.20 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.97 | 0.00 | 01-JAN-00:20 | 21745.20 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.97 | 0.00 | 01-JAN-00:20 | 21745.20 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 163.30 | 0.00 | 01-JAN-00:40 | 20411.38 | 14-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 163.30 | 0.00 | 01-JAN-00:40 | 20411.38 | 14-AUG-09:20 |
EnergyTransfer:Zone:CORE_TOP | 159.04 | 0.00 | 01-JAN-00:40 | 30572.31 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.93 | 0.00 | 01-JAN-00:40 | 30572.31 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.93 | 0.00 | 01-JAN-00:40 | 30572.31 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 154.10 | 0.00 | 01-JAN-00:20 | 22485.93 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 154.10 | 0.00 | 01-JAN-00:20 | 22485.93 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.99 | 0.00 | 01-JAN-00:40 | 10795.45 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.58 | 0.00 | 01-JAN-00:40 | 10795.45 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.58 | 0.00 | 01-JAN-00:40 | 10795.45 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.41 | 0.00 | 01-JAN-00:10 | 8353.38 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.41 | 0.00 | 01-JAN-00:10 | 8353.38 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.74 | 0.00 | 01-JAN-00:40 | 9774.88 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.67 | 0.00 | 01-JAN-00:40 | 9774.88 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.67 | 0.00 | 01-JAN-00:40 | 9774.88 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.06 | 0.00 | 01-JAN-00:10 | 9618.57 | 02-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.06 | 0.00 | 01-JAN-00:10 | 9618.57 | 02-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 68.28 | 0.00 | 01-JAN-00:40 | 14012.99 | 28-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.23 | 0.00 | 01-JAN-00:40 | 12798.96 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.23 | 0.00 | 01-JAN-00:40 | 12798.96 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.05 | 0.00 | 01-JAN-00:10 | 14012.99 | 28-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.05 | 0.00 | 01-JAN-00:10 | 14012.99 | 28-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.52 | 0.00 | 01-JAN-00:40 | 10302.25 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.63 | 0.00 | 01-JAN-00:40 | 10002.12 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.63 | 0.00 | 01-JAN-00:40 | 10002.12 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.88 | 0.00 | 01-JAN-00:10 | 10302.25 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.88 | 0.00 | 01-JAN-00:10 | 10302.25 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.73 | 0.00 | 01-JAN-00:40 | 8354.08 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.34 | 0.00 | 01-JAN-00:40 | 8354.08 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.34 | 0.00 | 01-JAN-00:40 | 8354.08 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.39 | 0.00 | 01-JAN-00:10 | 6600.54 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.39 | 0.00 | 01-JAN-00:10 | 6600.54 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 36.87 | 0.00 | 01-JAN-00:40 | 8006.42 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.44 | 0.00 | 01-JAN-00:40 | 8006.42 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.44 | 0.00 | 01-JAN-00:40 | 8006.42 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.42 | 0.00 | 01-JAN-00:20 | 7747.70 | 22-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 34.42 | 0.00 | 01-JAN-00:20 | 7747.70 | 22-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 70.65 | 0.00 | 01-JAN-00:40 | 15628.86 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.78 | 0.00 | 01-JAN-00:40 | 15628.86 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.78 | 0.00 | 01-JAN-00:40 | 15628.86 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.87 | 0.00 | 01-JAN-00:20 | 14388.40 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.87 | 0.00 | 01-JAN-00:20 | 14388.40 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.09 | 0.00 | 01-JAN-00:40 | 8070.82 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.85 | 0.00 | 01-JAN-00:40 | 8070.82 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.85 | 0.00 | 01-JAN-00:40 | 8070.82 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.24 | 0.00 | 01-JAN-00:20 | 8063.78 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 34.24 | 0.00 | 01-JAN-00:20 | 8063.78 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.46 | 0.00 | 01-JAN-00:40 | 9100.57 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.38 | 0.00 | 01-JAN-00:40 | 9100.57 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.38 | 0.00 | 01-JAN-00:40 | 9100.57 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.09 | 0.00 | 01-JAN-00:10 | 7482.16 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.09 | 0.00 | 01-JAN-00:10 | 7482.16 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.83 | 0.00 | 01-JAN-00:40 | 9370.17 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.89 | 0.00 | 01-JAN-00:40 | 8345.88 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.89 | 0.00 | 01-JAN-00:40 | 8345.88 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.94 | 0.00 | 01-JAN-00:10 | 9370.17 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.94 | 0.00 | 01-JAN-00:10 | 9370.17 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 64.65 | 0.00 | 01-JAN-00:40 | 12908.23 | 28-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.19 | 0.00 | 01-JAN-00:40 | 11385.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.19 | 0.00 | 01-JAN-00:40 | 11385.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.45 | 0.00 | 01-JAN-00:10 | 12908.23 | 28-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 61.45 | 0.00 | 01-JAN-00:10 | 12908.23 | 28-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 41.83 | 0.00 | 01-JAN-00:40 | 9729.74 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.26 | 0.00 | 01-JAN-00:40 | 8408.84 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.26 | 0.00 | 01-JAN-00:40 | 8408.84 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.57 | 0.00 | 01-JAN-00:10 | 9729.74 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.57 | 0.00 | 01-JAN-00:10 | 9729.74 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
EnergyTransfer:HVAC | 1223.22 | 0.00 | 01-JAN-00:40 | 299909.14 | 16-AUG-12:20 |
HeatingCoils:EnergyTransfer | 270.12 | 0.00 | 01-JAN-00:40 | 284427.51 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 953.11 | 0.00 | 01-JAN-00:10 | 299909.14 | 16-AUG-12:20 |
EnergyTransfer:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6337.47 | 07-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.294 | -245.934 | 0.000 | 0.000 | 33.026 | 81.703 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -116.433 |
CORE_MID | 0.000 | 0.000 | 0.970 | -163.298 | 0.000 | 0.000 | 34.195 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -80.171 |
CORE_TOP | 0.000 | 0.000 | 4.930 | -154.105 | 0.000 | 0.000 | 34.886 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -94.015 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 12.581 | -36.408 | 0.000 | 0.000 | 7.568 | 11.921 | 26.688 | 19.599 | 0.000 | 0.143 | 0.000 | 0.000 | -25.882 | 0.000 | -9.085 | -7.126 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 6.674 | -37.063 | 0.000 | 0.000 | 4.774 | 7.544 | 16.895 | 34.371 | 0.000 | 0.098 | 0.001 | 0.000 | -16.328 | 0.000 | -6.102 | -10.862 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.229 | -60.047 | 0.000 | 0.000 | 7.397 | 11.858 | 26.688 | 69.672 | 0.000 | 0.140 | 0.001 | 0.000 | -24.667 | 0.000 | -9.480 | -29.791 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.633 | -37.882 | 0.000 | 0.000 | 4.830 | 7.509 | 16.895 | 35.040 | 0.000 | 0.102 | 0.001 | 0.000 | -16.859 | 0.000 | -6.141 | -11.127 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.343 | -32.388 | 0.000 | 0.000 | 7.502 | 11.907 | 26.688 | 19.742 | 0.000 | 0.083 | 0.001 | 0.000 | -27.278 | 0.000 | -5.186 | -6.413 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.443 | -34.424 | 0.000 | 0.000 | 4.730 | 7.537 | 16.895 | 34.457 | 0.000 | 0.053 | 0.000 | 0.000 | -17.482 | 0.000 | -3.523 | -10.685 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 22.779 | -47.873 | 0.000 | 0.000 | 7.580 | 11.847 | 26.688 | 70.383 | 0.000 | 3.090 | 0.002 | 0.000 | -26.322 | 0.000 | -49.432 | -18.740 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.849 | -34.239 | 0.000 | 0.000 | 4.768 | 7.503 | 16.895 | 35.137 | 0.000 | 0.053 | 0.000 | 0.000 | -18.047 | 0.000 | -3.545 | -11.375 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 5.378 | -37.086 | 0.000 | 0.000 | 7.478 | 11.921 | 26.688 | 19.341 | 0.000 | 0.121 | 1.750 | 0.000 | -27.543 | 0.000 | -8.048 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.890 | -37.939 | 0.000 | 0.000 | 3.508 | 7.544 | 16.895 | 34.205 | 0.000 | 0.084 | 0.001 | 0.000 | -17.299 | 0.000 | -5.385 | -4.503 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.192 | -61.453 | 0.000 | 0.000 | 7.298 | 11.858 | 26.688 | 69.383 | 0.000 | 0.117 | 0.000 | 0.000 | -26.222 | 0.000 | -8.399 | -22.463 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.258 | -38.570 | 0.000 | 0.000 | 4.780 | 7.509 | 16.895 | 34.883 | 0.000 | 0.085 | 0.001 | 0.000 | -17.900 | 0.000 | -5.426 | -5.513 |
TOPFLOOR_PLENUM | 21.331 | -37.341 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.137 | 29.849 | 0.000 | 0.000 | 0.000 | -13.975 | -0.000 |
MIDFLOOR_PLENUM | 9.471 | -22.666 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.160 | 26.958 | 0.000 | 0.000 | 0.000 | -13.924 | -0.001 |
FIRSTFLOOR_PLENUM | 5.817 | -27.384 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.125 | 32.820 | 0.000 | 0.000 | 0.000 | -11.377 | -0.001 |
Total Facility | 36.620 | -87.391 | 89.444 | -1058.710 | 0.000 | 0.000 | 174.320 | 361.570 | 762.041 | 476.213 | 0.000 | 4.590 | 91.383 | 0.000 | -261.829 | 0.000 | -159.027 | -429.220 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 24-JUL-04:02 | 0.00 | 0.00 | 0.00 | -47561.26 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 41630.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -37479.46 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 33511.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-JUL-04:03 | 0.00 | 0.00 | 0.00 | -39776.54 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 35808.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:12 | 0.00 | 0.00 | 0.00 | -11690.28 | 0.00 | 0.00 | 26.91 | 51.50 | 501.96 | 2993.40 | 0.00 | 121.06 | 7995.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:12 | 0.00 | 0.00 | 0.00 | -14159.77 | 0.00 | 0.00 | 13.23 | 32.61 | 317.77 | 9531.34 | 0.00 | 0.00 | 4296.93 | 0.00 | -0.00 | 0.00 | -32.10 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:32 | 0.00 | 0.00 | 0.00 | -18008.48 | 0.00 | 0.00 | 21.10 | 51.50 | 501.96 | 13041.77 | 0.00 | 0.00 | 4439.57 | 0.00 | -0.00 | 0.00 | -47.43 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:32 | 0.00 | 0.00 | 0.00 | -15580.99 | 0.00 | 0.00 | 12.84 | 32.60 | 317.76 | 9642.96 | 0.00 | 0.00 | 5701.47 | 0.00 | -0.00 | 0.00 | -126.65 | 0.00 |
PERIMETER_BOT_ZN_3 | 14-AUG-04:02 | 0.00 | 0.00 | 0.00 | -8003.61 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 7840.60 | 0.00 | -628.93 | 0.00 | -44.46 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-09:12 | 0.00 | 0.00 | 0.00 | -11701.91 | 0.00 | 0.00 | 16.56 | 32.61 | 317.77 | 9180.50 | 0.00 | 0.00 | 2281.97 | 0.00 | -0.00 | 0.00 | -127.49 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:12 | 0.00 | 0.00 | 0.00 | -15330.26 | 0.00 | 0.00 | 23.38 | 51.50 | 501.96 | 9708.63 | 0.00 | 0.00 | 5113.95 | 0.00 | -0.00 | 0.00 | -69.17 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-17:12 | 0.00 | 0.00 | 0.00 | -12435.54 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 7264.68 | 0.00 | 0.00 | 4933.55 | 0.00 | -0.00 | 0.00 | -113.05 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JUL-04:02 | 0.00 | 0.00 | 0.00 | -9575.71 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 9593.63 | 0.00 | -743.05 | 0.00 | -111.26 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -15059.69 | 0.00 | 0.00 | 13.43 | 32.61 | 317.77 | 9941.15 | 0.00 | 0.00 | 4810.12 | 0.00 | -0.00 | 0.00 | -55.38 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:01 | 0.00 | 0.00 | 0.00 | -17721.28 | 0.00 | 0.00 | 21.80 | 51.50 | 501.96 | 12501.09 | 0.00 | 0.00 | 4734.22 | 0.00 | -0.00 | 0.00 | -89.29 | 0.00 |
PERIMETER_MID_ZN_4 | 18-JUN-15:51 | 0.00 | 0.00 | 0.00 | -15390.23 | 0.00 | 0.00 | 13.68 | 32.60 | 317.76 | 10714.89 | 0.00 | 0.00 | 4409.55 | 0.00 | -0.00 | 0.00 | -98.25 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:40 | 0.00 | -13042.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 | 12905.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-14:40 | 0.00 | -6064.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.92 | 5996.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:09 | 0.00 | -7131.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 | 6993.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 11434.18 | 0.00 | -220986.60 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 195223.90 | 0.00 | -6667.94 | 0.00 | -1064.92 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 26805.95 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32737.08 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 25062.57 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29030.11 |
CORE_TOP | 02-JAN-01:22 | 0.00 | 0.00 | 34356.21 | 0.00 | 0.00 | 0.00 | 0.00 | 396.30 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37927.37 |
PERIMETER_TOP_ZN_3 | 02-JAN-00:42 | 0.00 | 0.00 | 12123.22 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2874.89 | 0.00 | -2032.18 | -7968.97 |
PERIMETER_TOP_ZN_2 | 02-JAN-00:42 | 0.00 | 0.00 | 12788.55 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1866.20 | 0.00 | -1383.88 | -10015.05 |
PERIMETER_TOP_ZN_1 | 02-JAN-00:42 | 0.00 | 0.00 | 16044.70 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2820.41 | 0.00 | -2070.16 | -11906.95 |
PERIMETER_TOP_ZN_4 | 02-JAN-00:42 | 0.00 | 0.00 | 13851.30 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1916.19 | 0.00 | -1387.42 | -11024.27 |
PERIMETER_BOT_ZN_3 | 02-JAN-00:42 | 0.00 | 0.00 | 9337.83 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2931.14 | 0.00 | -1119.17 | -6040.35 |
PERIMETER_BOT_ZN_2 | 02-JAN-00:42 | 0.00 | 0.00 | 9984.34 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1920.16 | 0.00 | -761.79 | -7778.96 |
PERIMETER_BOT_ZN_1 | 02-JAN-08:00 | 0.00 | 0.00 | 15629.02 | 0.00 | 0.00 | 0.00 | 260.24 | 309.05 | 669.28 | 1684.33 | 0.00 | 0.00 | 9760.46 | 0.00 | -0.00 | 0.00 | -28312.39 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-00:42 | 0.00 | 0.00 | 10118.59 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1958.53 | 0.00 | -759.02 | -7877.61 |
PERIMETER_MID_ZN_3 | 02-JAN-00:42 | 0.00 | 0.00 | 10319.54 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2937.92 | 0.00 | -1731.21 | -6403.24 |
PERIMETER_MID_ZN_2 | 02-JAN-00:42 | 0.00 | 0.00 | 11034.82 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1908.57 | 0.00 | -1175.45 | -8427.37 |
PERIMETER_MID_ZN_1 | 02-JAN-00:42 | 0.00 | 0.00 | 14109.40 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2885.88 | 0.00 | -1762.44 | -10213.91 |
PERIMETER_MID_ZN_4 | 02-JAN-00:42 | 0.00 | 0.00 | 11154.72 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1958.26 | 0.00 | -1173.87 | -8499.16 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 17193.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -822.52 | -16370.72 |
MIDFLOOR_PLENUM | 02-JAN-07:05 | 11086.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -233.59 | -10852.45 |
FIRSTFLOOR_PLENUM | 02-JAN-06:12 | 9649.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -241.09 | -9408.54 |
Total Facility | 02-JAN-05:01 | 18330.36 | 0.00 | 218108.82 | 0.00 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30251.83 | 0.00 | -9621.82 | -218626.93 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7147 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1537 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3428 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6160 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7877 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3312 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8573 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7144 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6714 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7064 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8938 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.8277 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9446 | 2.9446 | 0.8834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2033 | 2.2033 | 0.7645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3442 | 2.3442 | 0.7947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7501 | 0.7501 | 0.2250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8071 | 0.8071 | 0.2421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0100 | 1.0100 | 0.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8763 | 0.8763 | 0.2629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5983 | 0.5983 | 0.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6671 | 0.6671 | 0.2001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8176 | 0.8176 | 0.2453 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6871 | 0.6871 | 0.2061 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6531 | 0.6531 | 0.1959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7768 | 0.7768 | 0.2330 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9085 | 0.9085 | 0.2726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8011 | 0.8011 | 0.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7147 | 5.1537 | 5.7147 | 1.7144 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3428 | 4.6160 | 5.3428 | 1.7064 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7877 | 5.3312 | 5.7877 | 1.8277 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4723 | 1.4723 | 0.8834 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1016 | 1.1016 | 0.7645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1721 | 1.1721 | 0.7947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3751 | 0.3751 | 0.2250 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4035 | 0.4035 | 0.2421 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5050 | 0.5050 | 0.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4381 | 0.4381 | 0.2629 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2992 | 0.2992 | 0.1795 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3335 | 0.3335 | 0.2001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4088 | 0.4088 | 0.2453 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3435 | 0.3435 | 0.2061 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3265 | 0.3265 | 0.1959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3884 | 0.3884 | 0.2330 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4543 | 0.4543 | 0.2726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4006 | 0.4006 | 0.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8573 | 1.7144 | 1.7144 | 1.7144 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6714 | 1.7064 | 1.7064 | 1.7064 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8938 | 1.8277 | 1.8277 | 1.8277 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 336.83 |
Number of hours cooling loads not met | 99.50 |
Number of hours not met | 436.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 181.75 | 221858.82 | 110.46 | 91491.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 235.51 | 85255.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 361.57 | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 111.00 | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.92 | 1358.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 114.51 | 28374.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 107.28 | 9472.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1785.34 |
Natural Gas | 0.00 | 217.74 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2003.08 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.57 |
Space Heating | 36.48 |
Space Cooling | 47.27 |
Fans (All) | 22.98 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 358.34 |
Subtotal | 358.34 |
Natural Gas [MJ/m2] | |
Space Heating | 22.17 |
Service Water Heating | 21.53 |
Miscellaneous (All) | 43.70 |
Subtotal | 43.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.05 |
Space Heating | 14.59 |
Space Cooling | 11.76 |
Fans (All) | 5.72 |
Service Water Heating | 5.36 |
Receptacle Equipment | 38.04 |
Miscellaneous | 6.49 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2616. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8481.17 | 278.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8712.33 | 47.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8661.83 | 98.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8633.00 | 127.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8615.33 | 144.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8563.00 | 197.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8649.83 | 110.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8576.83 | 183.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8660.17 | 99.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8624.17 | 135.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8608.00 | 152.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8535.00 | 225.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8643.33 | 116.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
Min | 8481.17 | 0.33 | 0.00 | 0.00 | 0.00 |
Max | 8759.67 | 278.83 | 0.00 | 0.00 | 0.00 |
Average | 8644.57 | 115.43 | 0.00 | 0.00 | 0.00 |
Sum | 155602.33 | 2077.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128236.00 | 68.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128291.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.00 | 68.00 | 0.00 | 0.00 | 0.00 |
Average | 34138.34 | 4.99 | 0.00 | 0.00 | 0.00 |
Sum | 614490.17 | 89.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7956.50 | 803.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8145.17 | 614.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8273.50 | 486.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7962.67 | 797.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8012.17 | 747.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7980.50 | 779.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7989.00 | 771.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8023.83 | 736.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8021.50 | 738.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7658.50 | 1101.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7953.17 | 806.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7918.67 | 841.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7997.00 | 763.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7934.50 | 825.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7947.00 | 813.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7414.50 | 1345.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7876.00 | 884.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7788.67 | 971.33 | 0.00 | 0.00 | 0.00 |
Min | 7414.50 | 486.50 | 0.00 | 0.00 | 0.00 |
Max | 8273.50 | 1345.50 | 0.00 | 0.00 | 0.00 |
Average | 7936.27 | 823.73 | 0.00 | 0.00 | 0.00 |
Sum | 142852.83 | 14827.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127918.00 | 386.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128041.00 | 263.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128098.67 | 205.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24873.00 | 36.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24894.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24884.33 | 24.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23169.83 | 1739.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24875.50 | 33.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24893.17 | 15.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128098.67 | 1739.17 | 0.00 | 0.00 | 0.00 |
Average | 33992.32 | 151.01 | 0.00 | 0.00 | 0.00 |
Sum | 611861.83 | 2718.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:08
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108530E+11 | 13152.34 | 20-JAN-08:40 | 5.20 | 0.28 | 0.183492E+10 | 2606.62 | 26-JAN-14:30 | 4.40 | 1.03 |
February | 0.111127E+11 | 13897.91 | 24-FEB-17:00 | 6.70 | 1.42 | 0.172946E+10 | 2608.35 | 01-FEB-10:00 | 6.70 | 1.42 |
March | 0.159430E+11 | 20813.33 | 30-MAR-07:03 | 2.30 | 1.13 | 0.213079E+10 | 2606.67 | 27-MAR-09:09 | 2.30 | 1.13 |
April | 0.176186E+11 | 40031.45 | 13-APR-05:02 | 5.68 | 2.22 | 0.190381E+10 | 2608.50 | 03-APR-09:20 | 5.68 | 2.22 |
May | 0.234630E+11 | 45907.51 | 30-MAY-04:02 | 17.80 | 14.10 | 0.207359E+10 | 2606.78 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.279499E+11 | 46482.12 | 26-JUN-04:02 | 20.60 | 16.77 | 0.207054E+10 | 2606.66 | 08-JUN-09:00 | 20.60 | 16.77 |
July | 0.286528E+11 | 47568.68 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192460E+10 | 2606.67 | 12-JUL-13:00 | 21.02 | 20.27 |
August | 0.313071E+11 | 46434.96 | 28-AUG-04:02 | 19.90 | 17.41 | 0.216077E+10 | 2606.69 | 08-AUG-13:20 | 19.90 | 17.41 |
September | 0.262629E+11 | 45954.73 | 06-SEP-04:02 | 21.20 | 18.83 | 0.191768E+10 | 2606.73 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.239495E+11 | 43589.16 | 03-OCT-05:02 | 14.40 | 14.40 | 0.199213E+10 | 2606.74 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.158836E+11 | 38743.94 | 03-NOV-05:02 | 9.22 | 6.42 | 0.195221E+10 | 2606.71 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.129375E+11 | 16336.28 | 22-DEC-08:08 | -4.1 | -6.4 | 0.187726E+10 | 2608.60 | 15-DEC-14:50 | -4.1 | -6.4 |
Annual Sum or Average | 0.245934E+12 | 0.235678E+11 | ||||||||
Minimum of Months | 0.108530E+11 | 13152.34 | -4.1 | -6.4 | 0.172946E+10 | 2606.62 | -4.1 | -6.4 | ||
Maximum of Months | 0.313071E+11 | 47568.68 | 21.20 | 20.27 | 0.216077E+10 | 2608.60 | 21.02 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13706886.85 | 672.46 | 17-JAN-14:20 | 10.93 | 5.12 | 0.00 | 0.00 | 01-JAN-00:10 | 10.93 | 5.12 |
February | 57368430.83 | 1202.80 | 17-FEB-13:00 | 6.70 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 1.56 |
March | 0.761970E+09 | 3305.01 | 03-MAR-14:40 | 15.00 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.47 |
April | 0.182846E+10 | 7878.67 | 07-APR-14:30 | 25.85 | 15.95 | 0.00 | 0.00 | 01-APR-00:10 | 25.85 | 15.95 |
May | 0.399873E+10 | 11596.14 | 30-MAY-14:00 | 29.40 | 16.93 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 16.93 |
June | 0.657121E+10 | 13042.54 | 19-JUN-13:40 | 34.60 | 23.77 | 0.00 | 0.00 | 01-JUN-00:10 | 34.60 | 23.77 |
July | 0.805151E+10 | 12170.00 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.860964E+10 | 11682.98 | 01-AUG-14:40 | 30.97 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.97 | 22.94 |
September | 0.450276E+10 | 10423.20 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.256713E+10 | 7406.67 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.367804E+09 | 2912.27 | 04-NOV-13:10 | 17.62 | 12.77 | 0.00 | 0.00 | 01-NOV-00:10 | 17.62 | 12.77 |
December | 11502326.64 | 1447.83 | 17-DEC-13:20 | 12.20 | 5.06 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.06 |
Annual Sum or Average | 0.373418E+11 | 0.00 | ||||||||
Minimum of Months | 11502326.64 | 672.46 | 6.70 | 1.56 | 0.00 | 0.00 | 6.70 | 1.56 | ||
Maximum of Months | 0.860964E+10 | 13042.54 | 34.60 | 23.77 | 0.00 | 0.00 | 34.60 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19473627.29 | 1900.92 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 28026637.90 | 1739.41 | 09-FEB-05:02 | -8.3 | -9.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.9 |
March | 0.297978E+09 | 2722.73 | 29-MAR-06:01 | 1.88 | 0.26 | 0.00 | 0.00 | 01-MAR-00:10 | 1.88 | 0.26 |
April | 0.893372E+09 | 2496.87 | 10-APR-16:00 | 20.00 | 11.13 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.13 |
May | 0.207733E+10 | 5214.29 | 30-MAY-14:10 | 29.22 | 16.98 | 0.00 | 0.00 | 01-MAY-00:10 | 29.22 | 16.98 |
June | 0.395155E+10 | 5463.67 | 19-JUN-15:10 | 32.93 | 23.30 | 0.00 | 0.00 | 01-JUN-00:10 | 32.93 | 23.30 |
July | 0.491662E+10 | 5962.26 | 10-JUL-15:10 | 32.93 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 20.87 |
August | 0.537890E+10 | 6064.19 | 14-AUG-14:40 | 28.87 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 28.87 | 23.11 |
September | 0.312520E+10 | 5546.40 | 05-SEP-15:20 | 25.93 | 21.57 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 21.57 |
October | 0.166914E+10 | 3517.72 | 04-OCT-15:50 | 22.98 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 22.98 | 19.12 |
November | 0.282489E+09 | 1649.65 | 04-NOV-05:25 | 10.30 | 9.10 | 0.00 | 0.00 | 01-NOV-00:10 | 10.30 | 9.10 |
December | 26081613.46 | 1161.09 | 02-DEC-06:01 | 1.10 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | -2.5 |
Annual Sum or Average | 0.226662E+11 | 0.00 | ||||||||
Minimum of Months | 19473627.29 | 1161.09 | -8.3 | -9.9 | 0.00 | 0.00 | -8.3 | -9.9 | ||
Maximum of Months | 0.537890E+10 | 6064.19 | 32.93 | 23.30 | 0.00 | 0.00 | 32.93 | 23.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89186805.63 | 1904.12 | 11-JAN-17:10 | -5.1 | -8.2 | 0.00 | 0.00 | 01-JAN-00:10 | -5.1 | -8.2 |
February | 0.118455E+09 | 2569.79 | 03-FEB-07:10 | -7.7 | -9.4 | 0.00 | 0.00 | 01-FEB-00:10 | -7.7 | -9.4 |
March | 0.575057E+09 | 3070.89 | 30-MAR-06:01 | 2.20 | 1.02 | 0.00 | 0.00 | 01-MAR-00:10 | 2.20 | 1.02 |
April | 0.130361E+10 | 2947.15 | 10-APR-16:00 | 20.00 | 11.13 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.13 |
May | 0.264804E+10 | 5796.41 | 30-MAY-12:10 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.438363E+10 | 7131.87 | 19-JUN-12:09 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.525076E+10 | 6785.69 | 07-JUL-12:08 | 33.72 | 23.31 | 0.00 | 0.00 | 01-JUL-00:10 | 33.72 | 23.31 |
August | 0.590000E+10 | 6123.94 | 14-AUG-16:00 | 27.80 | 22.71 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 22.71 |
September | 0.383905E+10 | 5666.19 | 05-SEP-16:00 | 25.60 | 21.66 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 21.66 |
October | 0.254896E+10 | 4254.81 | 04-OCT-16:00 | 22.80 | 19.11 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 19.11 |
November | 0.579403E+09 | 2170.36 | 03-NOV-16:10 | 14.63 | 10.15 | 0.00 | 0.00 | 01-NOV-00:10 | 14.63 | 10.15 |
December | 0.148191E+09 | 2305.69 | 22-DEC-07:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-DEC-00:10 | -4.9 | -6.9 |
Annual Sum or Average | 0.273843E+11 | 0.00 | ||||||||
Minimum of Months | 89186805.63 | 1904.12 | -7.7 | -9.4 | 0.00 | 0.00 | -7.7 | -9.4 | ||
Maximum of Months | 0.590000E+10 | 7131.87 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.670468E+10 | 7373.64 | 20-JAN-17:00 | 5.60 | 3.19 | 0.160539E+10 | 2422.53 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.684921E+10 | 7437.70 | 24-FEB-16:40 | 7.07 | 1.55 | 0.148888E+10 | 2443.27 | 24-FEB-14:00 | 7.07 | 1.55 |
March | 0.985188E+10 | 10674.37 | 29-MAR-16:00 | 7.20 | 4.88 | 0.195402E+10 | 2606.59 | 29-MAR-13:09 | 7.20 | 4.88 |
April | 0.111886E+11 | 21704.38 | 10-APR-05:03 | 15.10 | 13.73 | 0.183508E+10 | 2606.64 | 07-APR-13:09 | 15.10 | 13.73 |
May | 0.157561E+11 | 34418.80 | 30-MAY-04:02 | 17.80 | 14.10 | 0.205580E+10 | 2606.74 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.198132E+11 | 34873.07 | 26-JUN-04:02 | 20.60 | 16.77 | 0.206730E+10 | 2606.65 | 08-JUN-09:00 | 20.60 | 16.77 |
July | 0.211795E+11 | 37096.54 | 10-JUL-04:03 | 26.10 | 21.38 | 0.192211E+10 | 2606.66 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.226920E+11 | 37480.68 | 14-AUG-04:03 | 22.20 | 19.79 | 0.215877E+10 | 2606.66 | 23-AUG-13:09 | 25.60 | 17.07 |
September | 0.176361E+11 | 35354.32 | 05-SEP-04:02 | 20.52 | 17.93 | 0.191102E+10 | 2606.70 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.146555E+11 | 32500.03 | 06-OCT-05:03 | 19.40 | 18.22 | 0.197292E+10 | 2606.71 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.900914E+10 | 12584.81 | 03-NOV-16:00 | 15.00 | 10.26 | 0.179486E+10 | 2606.66 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.796223E+10 | 7535.59 | 21-DEC-16:10 | 2.62 | -2.3 | 0.163274E+10 | 2498.95 | 21-DEC-14:00 | 2.62 | -2.3 |
Annual Sum or Average | 0.163298E+12 | 0.223989E+11 | ||||||||
Minimum of Months | 0.670468E+10 | 7373.64 | 2.62 | -2.3 | 0.148888E+10 | 2422.53 | 2.62 | -2.3 | ||
Maximum of Months | 0.226920E+11 | 37480.68 | 26.10 | 21.38 | 0.215877E+10 | 2606.74 | 27.97 | 21.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511502E+10 | 7257.98 | 20-JAN-16:30 | 6.40 | 3.51 | 0.152635E+10 | 2314.34 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.517602E+10 | 7296.07 | 17-FEB-16:30 | 5.85 | 1.66 | 0.140503E+10 | 2354.95 | 02-FEB-14:00 | 5.85 | 1.66 |
March | 0.884232E+10 | 10177.29 | 29-MAR-16:00 | 7.20 | 4.88 | 0.183708E+10 | 2606.58 | 29-MAR-13:39 | 7.20 | 4.88 |
April | 0.104699E+11 | 16358.31 | 10-APR-16:00 | 20.00 | 11.13 | 0.176416E+10 | 2606.64 | 07-APR-13:09 | 20.00 | 11.13 |
May | 0.154900E+11 | 31725.29 | 30-MAY-05:03 | 18.17 | 14.31 | 0.202822E+10 | 2606.75 | 15-MAY-13:00 | 18.17 | 14.31 |
June | 0.202060E+11 | 36816.02 | 20-JUN-04:02 | 21.02 | 18.18 | 0.206390E+10 | 2606.67 | 23-JUN-09:09 | 27.25 | 18.76 |
July | 0.221331E+11 | 39781.28 | 10-JUL-04:03 | 26.10 | 21.38 | 0.192204E+10 | 2606.66 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.232611E+11 | 37661.82 | 07-AUG-04:02 | 18.48 | 17.13 | 0.215750E+10 | 2606.70 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.168895E+11 | 36754.27 | 05-SEP-04:02 | 20.52 | 17.93 | 0.189862E+10 | 2606.69 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.130918E+11 | 17468.15 | 04-OCT-16:00 | 22.80 | 19.11 | 0.192228E+10 | 2606.70 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.754807E+10 | 11186.72 | 03-NOV-16:00 | 15.00 | 10.26 | 0.167091E+10 | 2606.58 | 03-NOV-13:09 | 15.00 | 10.26 |
December | 0.588211E+10 | 7212.62 | 21-DEC-16:10 | 2.62 | -2.3 | 0.151248E+10 | 2351.72 | 21-DEC-14:00 | 2.62 | -2.3 |
Annual Sum or Average | 0.154105E+12 | 0.217086E+11 | ||||||||
Minimum of Months | 0.511502E+10 | 7212.62 | 2.62 | -2.3 | 0.140503E+10 | 2314.34 | 2.62 | -2.3 | ||
Maximum of Months | 0.232611E+11 | 39781.28 | 26.10 | 21.38 | 0.215750E+10 | 2606.75 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171827E+09 | 1518.50 | 20-JAN-16:30 | 6.40 | 3.51 | 0.305074E+09 | 411.20 | 20-JAN-14:00 | 6.40 | 3.51 |
February | 0.202186E+09 | 1561.92 | 24-FEB-15:40 | 7.97 | 1.96 | 0.277415E+09 | 416.70 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.111804E+10 | 2177.68 | 27-MAR-16:00 | 22.20 | 16.34 | 0.347391E+09 | 523.91 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.214105E+10 | 4408.03 | 07-APR-15:20 | 25.60 | 16.01 | 0.342368E+09 | 549.50 | 07-APR-13:09 | 25.60 | 16.01 |
May | 0.409191E+10 | 6990.52 | 30-MAY-13:40 | 29.60 | 17.29 | 0.414166E+09 | 549.52 | 15-MAY-13:00 | 29.60 | 17.29 |
June | 0.605509E+10 | 8353.38 | 19-JUN-14:30 | 33.85 | 23.48 | 0.433744E+09 | 549.75 | 19-JUN-13:50 | 33.85 | 23.48 |
July | 0.708070E+10 | 10506.53 | 07-JUL-05:02 | 25.68 | 21.68 | 0.405396E+09 | 549.51 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.706387E+10 | 11691.14 | 13-AUG-15:12 | 30.40 | 20.77 | 0.453845E+09 | 549.51 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.437734E+10 | 6856.72 | 02-SEP-05:02 | 22.12 | 16.30 | 0.392029E+09 | 549.51 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.291411E+10 | 4525.98 | 04-OCT-14:00 | 24.40 | 18.95 | 0.378946E+09 | 549.50 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.100514E+10 | 2166.17 | 03-NOV-14:50 | 17.30 | 10.93 | 0.317278E+09 | 519.04 | 03-NOV-13:00 | 17.30 | 10.93 |
December | 0.187758E+09 | 1546.92 | 20-DEC-13:50 | 9.90 | 5.86 | 0.294905E+09 | 416.61 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.364090E+11 | 0.436256E+10 | ||||||||
Minimum of Months | 0.171827E+09 | 1518.50 | 6.40 | 1.96 | 0.277415E+09 | 411.20 | 6.40 | 1.96 | ||
Maximum of Months | 0.708070E+10 | 11691.14 | 33.85 | 23.48 | 0.453845E+09 | 549.75 | 33.85 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288334E+09 | 1825.93 | 19-JAN-10:20 | 7.80 | 4.36 | 0.193628E+09 | 279.60 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.423133E+09 | 1904.73 | 22-FEB-10:00 | 0.60 | -3.2 | 0.176499E+09 | 288.18 | 22-FEB-10:09 | 0.87 | -3.0 |
March | 0.149320E+10 | 3576.95 | 29-MAR-09:30 | 6.15 | 3.19 | 0.228225E+09 | 347.87 | 29-MAR-09:20 | 6.15 | 3.19 |
April | 0.246942E+10 | 6376.00 | 28-APR-08:50 | 15.82 | 8.80 | 0.223892E+09 | 347.89 | 26-APR-09:00 | 15.82 | 8.80 |
May | 0.444221E+10 | 14022.84 | 29-MAY-09:02 | 26.20 | 16.88 | 0.260849E+09 | 348.41 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.551684E+10 | 12701.89 | 25-JUN-08:52 | 25.60 | 23.63 | 0.272458E+09 | 348.40 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.633133E+10 | 14159.83 | 02-JUL-09:12 | 25.77 | 21.71 | 0.255801E+09 | 348.93 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.690305E+10 | 13000.38 | 13-AUG-09:52 | 28.90 | 19.41 | 0.287044E+09 | 348.52 | 18-AUG-09:30 | 30.00 | 19.65 |
September | 0.443918E+10 | 13975.11 | 04-SEP-09:12 | 24.47 | 18.42 | 0.246487E+09 | 348.35 | 06-SEP-09:39 | 26.33 | 19.45 |
October | 0.320516E+10 | 5673.47 | 05-OCT-09:20 | 19.27 | 16.99 | 0.245084E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.114890E+10 | 2342.04 | 03-NOV-09:50 | 13.22 | 8.34 | 0.202256E+09 | 332.56 | 03-NOV-09:50 | 13.22 | 8.34 |
December | 0.402572E+09 | 1889.41 | 20-DEC-09:40 | 7.57 | 4.72 | 0.187151E+09 | 285.50 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.370633E+11 | 0.277938E+10 | ||||||||
Minimum of Months | 0.288334E+09 | 1825.93 | 0.60 | -3.2 | 0.176499E+09 | 279.60 | 0.87 | -3.0 | ||
Maximum of Months | 0.690305E+10 | 14159.83 | 28.90 | 23.63 | 0.287044E+09 | 348.93 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122430E+10 | 6502.09 | 19-JAN-13:30 | 9.40 | 3.94 | 0.330913E+09 | 549.49 | 30-JAN-14:09 | 2.80 | -1.2 |
February | 0.156990E+10 | 6936.15 | 02-FEB-14:00 | 5.60 | -1.0 | 0.305799E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.312900E+10 | 9483.36 | 01-MAR-13:25 | 13.90 | 6.36 | 0.384114E+09 | 549.50 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.381493E+10 | 10505.43 | 07-APR-12:30 | 26.15 | 15.90 | 0.353376E+09 | 549.77 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.560221E+10 | 12136.99 | 29-MAY-12:23 | 28.05 | 17.71 | 0.408200E+09 | 550.12 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.719615E+10 | 10965.91 | 19-JUN-13:10 | 34.90 | 23.89 | 0.430152E+09 | 549.85 | 19-JUN-13:39 | 34.60 | 23.77 |
July | 0.845370E+10 | 14055.47 | 09-JUL-14:42 | 27.95 | 24.21 | 0.404171E+09 | 550.02 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.101260E+11 | 17728.97 | 13-AUG-13:12 | 31.30 | 19.70 | 0.452895E+09 | 550.01 | 17-AUG-13:50 | 31.10 | 24.82 |
September | 0.767560E+10 | 18008.65 | 04-SEP-12:32 | 26.10 | 18.14 | 0.392636E+09 | 557.08 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.696639E+10 | 17378.88 | 15-OCT-11:13 | 19.60 | 13.51 | 0.397514E+09 | 549.96 | 13-OCT-13:39 | 19.60 | 13.51 |
November | 0.272704E+10 | 11206.85 | 02-NOV-13:10 | 15.68 | 8.29 | 0.349646E+09 | 549.51 | 08-NOV-14:39 | 14.07 | 11.22 |
December | 0.156254E+10 | 6542.93 | 21-DEC-13:30 | 3.05 | -1.7 | 0.324083E+09 | 549.49 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.600477E+11 | 0.453350E+10 | ||||||||
Minimum of Months | 0.122430E+10 | 6502.09 | 3.05 | -1.7 | 0.305799E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.101260E+11 | 18008.65 | 34.90 | 24.21 | 0.452895E+09 | 557.08 | 34.60 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331348E+09 | 2281.60 | 19-JAN-15:50 | 8.40 | 3.05 | 0.194805E+09 | 299.58 | 19-JAN-15:00 | 8.30 | 2.94 |
February | 0.447533E+09 | 2517.52 | 22-FEB-16:30 | 3.85 | -0.7 | 0.178929E+09 | 322.26 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.153386E+10 | 5468.67 | 29-MAR-16:00 | 7.20 | 4.88 | 0.224463E+09 | 347.84 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.259932E+10 | 8252.14 | 07-APR-15:40 | 25.60 | 16.07 | 0.210732E+09 | 347.85 | 26-APR-13:00 | 18.30 | 12.92 |
May | 0.444687E+10 | 12252.38 | 21-MAY-15:12 | 20.37 | 13.43 | 0.248710E+09 | 347.88 | 15-MAY-13:00 | 20.37 | 13.43 |
June | 0.579042E+10 | 15295.62 | 18-JUN-16:02 | 25.50 | 22.07 | 0.268403E+09 | 347.86 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.635691E+10 | 15583.02 | 02-JUL-16:32 | 24.60 | 20.65 | 0.254137E+09 | 347.87 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.695913E+10 | 15336.52 | 13-AUG-15:52 | 30.00 | 20.46 | 0.283996E+09 | 347.86 | 08-AUG-13:39 | 30.00 | 20.46 |
September | 0.454740E+10 | 14182.29 | 10-SEP-16:02 | 23.22 | 12.85 | 0.238791E+09 | 347.86 | 15-SEP-13:00 | 22.80 | 15.50 |
October | 0.345546E+10 | 7681.44 | 04-OCT-15:30 | 23.35 | 19.12 | 0.231387E+09 | 347.86 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.104736E+10 | 3658.99 | 03-NOV-15:30 | 16.10 | 10.65 | 0.199616E+09 | 338.69 | 03-NOV-15:09 | 16.10 | 10.65 |
December | 0.367156E+09 | 2224.81 | 08-DEC-15:40 | 6.30 | 2.04 | 0.188124E+09 | 293.17 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.378828E+11 | 0.272209E+10 | ||||||||
Minimum of Months | 0.331348E+09 | 2224.81 | 3.85 | -0.7 | 0.178929E+09 | 293.17 | 3.67 | -0.7 | ||
Maximum of Months | 0.695913E+10 | 15583.02 | 30.00 | 22.07 | 0.283996E+09 | 347.88 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262204E+09 | 1269.24 | 20-JAN-15:00 | 7.80 | 3.97 | 0.306306E+09 | 424.19 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.231872E+09 | 1278.50 | 24-FEB-14:10 | 9.22 | 3.12 | 0.278680E+09 | 425.73 | 24-FEB-14:30 | 8.85 | 2.78 |
March | 0.106559E+10 | 1630.62 | 28-MAR-14:00 | 13.30 | 8.41 | 0.347772E+09 | 500.76 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.172089E+10 | 2467.65 | 10-APR-14:00 | 20.60 | 10.45 | 0.342719E+09 | 549.49 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.296409E+10 | 4831.26 | 30-MAY-14:00 | 29.40 | 16.93 | 0.415809E+09 | 549.51 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.476981E+10 | 6308.49 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434388E+09 | 549.50 | 23-JUN-13:00 | 21.97 | 17.81 |
July | 0.590087E+10 | 7921.39 | 10-JUL-06:03 | 26.20 | 20.78 | 0.405275E+09 | 549.50 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.625963E+10 | 8005.25 | 14-AUG-04:02 | 22.20 | 19.79 | 0.454676E+09 | 549.50 | 08-AUG-13:20 | 22.20 | 19.79 |
September | 0.422306E+10 | 5470.31 | 01-SEP-14:30 | 30.85 | 17.41 | 0.400403E+09 | 549.51 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.299581E+10 | 4139.34 | 05-OCT-14:00 | 23.30 | 18.86 | 0.403676E+09 | 549.51 | 16-OCT-09:20 | 17.07 | 14.18 |
November | 0.145172E+10 | 1882.98 | 02-NOV-12:06 | 15.10 | 8.04 | 0.340542E+09 | 545.20 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.543229E+09 | 1368.43 | 20-DEC-14:10 | 9.72 | 5.77 | 0.298468E+09 | 444.31 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.323888E+11 | 0.442871E+10 | ||||||||
Minimum of Months | 0.231872E+09 | 1269.24 | 7.80 | 3.12 | 0.278680E+09 | 424.19 | 7.80 | 2.78 | ||
Maximum of Months | 0.625963E+10 | 8005.25 | 30.85 | 20.78 | 0.454676E+09 | 549.51 | 29.40 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365819E+09 | 1544.99 | 27-JAN-10:30 | 4.70 | 1.53 | 0.194895E+09 | 284.18 | 27-JAN-10:39 | 4.80 | 1.56 |
February | 0.469687E+09 | 1564.13 | 22-FEB-10:10 | 0.87 | -3.0 | 0.177608E+09 | 286.83 | 22-FEB-10:30 | 1.40 | -2.7 |
March | 0.145725E+10 | 2250.62 | 29-MAR-09:40 | 6.33 | 3.26 | 0.228634E+09 | 347.87 | 29-MAR-09:39 | 6.33 | 3.26 |
April | 0.211330E+10 | 4287.85 | 28-APR-09:20 | 16.47 | 9.08 | 0.225471E+09 | 347.88 | 26-APR-09:00 | 16.47 | 9.08 |
May | 0.351072E+10 | 11462.34 | 29-MAY-09:31 | 26.50 | 17.38 | 0.261821E+09 | 348.14 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.459222E+10 | 7953.70 | 26-JUN-06:03 | 21.97 | 17.81 | 0.273856E+09 | 348.14 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.544591E+10 | 9926.65 | 09-JUL-10:02 | 29.90 | 25.42 | 0.256400E+09 | 348.47 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.635765E+10 | 8991.40 | 13-AUG-09:52 | 28.90 | 19.41 | 0.287918E+09 | 348.28 | 18-AUG-09:30 | 30.00 | 19.65 |
September | 0.434485E+10 | 11700.63 | 10-SEP-09:12 | 20.57 | 13.59 | 0.252302E+09 | 348.10 | 06-SEP-09:30 | 20.57 | 13.59 |
October | 0.340878E+10 | 5125.53 | 05-OCT-09:30 | 19.45 | 17.11 | 0.257855E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.160980E+10 | 2271.23 | 03-NOV-09:40 | 13.13 | 8.29 | 0.215602E+09 | 347.87 | 03-NOV-09:00 | 13.30 | 8.39 |
December | 0.748648E+09 | 1696.48 | 20-DEC-09:50 | 7.93 | 4.87 | 0.190703E+09 | 302.34 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.344246E+11 | 0.282306E+10 | ||||||||
Minimum of Months | 0.365819E+09 | 1544.99 | 0.87 | -3.0 | 0.177608E+09 | 284.18 | 1.40 | -2.7 | ||
Maximum of Months | 0.635765E+10 | 11700.63 | 29.90 | 25.42 | 0.287918E+09 | 348.47 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372791E+09 | 2210.69 | 07-JAN-14:20 | 0.60 | -4.4 | 0.295112E+09 | 499.06 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.476505E+09 | 2460.22 | 25-FEB-13:30 | 3.05 | -1.7 | 0.269595E+09 | 488.43 | 02-FEB-14:39 | 3.05 | -1.7 |
March | 0.130563E+10 | 4045.64 | 03-MAR-13:35 | 14.80 | 8.43 | 0.347520E+09 | 549.50 | 03-MAR-14:09 | 15.00 | 8.59 |
April | 0.204288E+10 | 7822.94 | 07-APR-12:00 | 25.60 | 15.40 | 0.331442E+09 | 549.51 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.349860E+10 | 11969.56 | 30-MAY-11:10 | 28.98 | 17.29 | 0.387772E+09 | 571.36 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.587182E+10 | 14388.40 | 19-JUN-12:00 | 36.70 | 24.28 | 0.426572E+09 | 697.49 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.811600E+10 | 13519.96 | 07-JUL-12:00 | 33.90 | 23.31 | 0.405790E+09 | 649.67 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.103347E+11 | 14068.82 | 13-AUG-13:12 | 31.30 | 19.70 | 0.456283E+09 | 647.24 | 18-AUG-12:09 | 32.88 | 20.21 |
September | 0.717015E+10 | 15330.09 | 04-SEP-14:12 | 25.73 | 18.51 | 0.396958E+09 | 616.00 | 01-SEP-12:09 | 25.73 | 18.51 |
October | 0.600049E+10 | 14400.63 | 15-OCT-12:53 | 20.60 | 12.82 | 0.402567E+09 | 565.51 | 04-OCT-13:30 | 20.60 | 12.82 |
November | 0.184991E+10 | 9449.56 | 02-NOV-12:06 | 15.10 | 8.04 | 0.333562E+09 | 549.51 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.834389E+09 | 4121.20 | 17-DEC-14:20 | 12.20 | 5.36 | 0.297334E+09 | 530.34 | 18-DEC-14:50 | 6.38 | 2.66 |
Annual Sum or Average | 0.478739E+11 | 0.435051E+10 | ||||||||
Minimum of Months | 0.372791E+09 | 2210.69 | 0.60 | -4.4 | 0.269595E+09 | 488.43 | 3.05 | -1.7 | ||
Maximum of Months | 0.103347E+11 | 15330.09 | 36.70 | 24.28 | 0.456283E+09 | 697.49 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360744E+09 | 1830.18 | 20-JAN-16:00 | 7.20 | 3.80 | 0.195562E+09 | 304.30 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.425728E+09 | 1930.04 | 22-FEB-16:30 | 3.85 | -0.7 | 0.178978E+09 | 316.91 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.146883E+10 | 3502.06 | 27-MAR-16:50 | 21.28 | 15.57 | 0.224314E+09 | 338.68 | 24-MAR-15:00 | 21.28 | 15.57 |
April | 0.214246E+10 | 8182.84 | 09-APR-16:42 | 16.28 | 13.85 | 0.214731E+09 | 347.85 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.337932E+10 | 7006.69 | 30-MAY-16:00 | 28.30 | 17.60 | 0.252974E+09 | 347.87 | 15-MAY-13:00 | 28.30 | 17.60 |
June | 0.477211E+10 | 7901.27 | 19-JUN-04:02 | 23.40 | 21.72 | 0.272931E+09 | 347.86 | 23-JUN-13:00 | 28.30 | 19.31 |
July | 0.543325E+10 | 11465.13 | 04-JUL-16:12 | 25.73 | 18.07 | 0.255977E+09 | 347.86 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.633867E+10 | 11820.81 | 13-AUG-15:52 | 30.00 | 20.46 | 0.287645E+09 | 347.86 | 08-AUG-13:20 | 30.00 | 20.46 |
September | 0.429556E+10 | 12433.89 | 10-SEP-17:12 | 22.43 | 12.33 | 0.249989E+09 | 347.86 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.352157E+10 | 6724.44 | 04-OCT-15:50 | 22.98 | 19.12 | 0.251328E+09 | 347.85 | 19-OCT-13:00 | 15.60 | 10.54 |
November | 0.147499E+10 | 3387.07 | 03-NOV-15:30 | 16.10 | 10.65 | 0.209349E+09 | 347.51 | 03-NOV-13:00 | 16.10 | 10.65 |
December | 0.626024E+09 | 1838.77 | 08-DEC-15:40 | 6.30 | 2.04 | 0.190585E+09 | 305.56 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.342393E+11 | 0.278436E+10 | ||||||||
Minimum of Months | 0.360744E+09 | 1830.18 | 3.85 | -0.7 | 0.178978E+09 | 304.30 | 3.67 | -0.7 | ||
Maximum of Months | 0.633867E+10 | 12433.89 | 30.00 | 21.72 | 0.287645E+09 | 347.87 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328693E+09 | 1459.13 | 20-JAN-15:10 | 7.70 | 3.95 | 0.306850E+09 | 437.90 | 20-JAN-14:00 | 7.70 | 3.95 |
February | 0.374935E+09 | 1488.88 | 24-FEB-15:40 | 7.97 | 1.96 | 0.280035E+09 | 441.84 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.151059E+10 | 1965.58 | 28-MAR-14:10 | 13.22 | 8.42 | 0.359459E+09 | 538.87 | 28-MAR-13:00 | 13.22 | 8.42 |
April | 0.231927E+10 | 3943.27 | 07-APR-15:20 | 25.60 | 16.01 | 0.357934E+09 | 549.50 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.397362E+10 | 6324.59 | 30-MAY-13:50 | 29.50 | 17.11 | 0.425605E+09 | 549.52 | 15-MAY-13:00 | 29.50 | 17.11 |
June | 0.583049E+10 | 8987.11 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435357E+09 | 549.71 | 19-JUN-13:30 | 21.97 | 17.81 |
July | 0.668338E+10 | 9577.77 | 17-JUL-04:02 | 21.70 | 19.41 | 0.405742E+09 | 549.80 | 07-JUL-13:50 | 21.70 | 19.41 |
August | 0.676019E+10 | 9161.80 | 22-AUG-04:02 | 25.92 | 17.84 | 0.454879E+09 | 549.51 | 08-AUG-13:30 | 25.92 | 17.84 |
September | 0.436700E+10 | 5983.96 | 01-SEP-14:30 | 30.85 | 17.41 | 0.398881E+09 | 549.51 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.306657E+10 | 4403.55 | 05-OCT-14:00 | 23.30 | 18.86 | 0.397839E+09 | 549.49 | 13-OCT-13:39 | 21.70 | 17.54 |
November | 0.135677E+10 | 2220.05 | 02-NOV-13:10 | 15.68 | 8.29 | 0.332623E+09 | 546.47 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.515280E+09 | 1505.51 | 20-DEC-13:50 | 9.90 | 5.86 | 0.297539E+09 | 446.74 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.370868E+11 | 0.445274E+10 | ||||||||
Minimum of Months | 0.328693E+09 | 1459.13 | 7.70 | 1.96 | 0.280035E+09 | 437.90 | 7.70 | 1.96 | ||
Maximum of Months | 0.676019E+10 | 9577.77 | 30.85 | 19.41 | 0.454879E+09 | 549.80 | 29.50 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424696E+09 | 1919.99 | 19-JAN-10:00 | 7.80 | 4.14 | 0.143403E+09 | 288.44 | 19-JAN-09:00 | 7.80 | 4.14 |
February | 0.605383E+09 | 2047.45 | 22-FEB-09:50 | 0.50 | -3.2 | 0.131324E+09 | 302.71 | 22-FEB-09:00 | 0.60 | -3.2 |
March | 0.182997E+10 | 4239.23 | 29-MAR-09:00 | 5.60 | 2.98 | 0.170654E+09 | 338.72 | 29-MAR-10:20 | 7.43 | 3.94 |
April | 0.271416E+10 | 6733.97 | 28-APR-08:40 | 15.53 | 8.75 | 0.167007E+09 | 338.73 | 26-APR-10:09 | 15.53 | 8.75 |
May | 0.441545E+10 | 13490.80 | 29-MAY-08:42 | 25.73 | 16.73 | 0.194415E+09 | 338.98 | 31-MAY-08:00 | 25.00 | 19.48 |
June | 0.528855E+10 | 14454.83 | 25-JUN-08:42 | 25.40 | 23.51 | 0.201559E+09 | 338.97 | 26-JUN-08:00 | 25.00 | 19.47 |
July | 0.597059E+10 | 15059.44 | 02-JUL-09:01 | 25.68 | 21.69 | 0.189488E+09 | 341.49 | 14-JUL-07:19 | 26.67 | 20.76 |
August | 0.658877E+10 | 13619.13 | 27-AUG-09:52 | 26.10 | 21.81 | 0.211927E+09 | 339.49 | 22-AUG-07:30 | 26.10 | 21.81 |
September | 0.445117E+10 | 14732.45 | 04-SEP-09:01 | 24.18 | 18.48 | 0.183369E+09 | 338.98 | 06-SEP-08:00 | 25.60 | 19.05 |
October | 0.346425E+10 | 6015.59 | 05-OCT-09:00 | 18.90 | 16.77 | 0.183694E+09 | 338.73 | 02-OCT-10:09 | 18.90 | 16.77 |
November | 0.151108E+10 | 2614.36 | 02-NOV-09:00 | 11.10 | 5.86 | 0.152925E+09 | 338.70 | 02-NOV-08:00 | 11.10 | 5.86 |
December | 0.675173E+09 | 2062.98 | 20-DEC-09:35 | 7.57 | 4.72 | 0.139498E+09 | 302.36 | 20-DEC-09:50 | 7.93 | 4.87 |
Annual Sum or Average | 0.379392E+11 | 0.206926E+10 | ||||||||
Minimum of Months | 0.424696E+09 | 1919.99 | 0.50 | -3.2 | 0.131324E+09 | 288.44 | 0.60 | -3.2 | ||
Maximum of Months | 0.658877E+10 | 15059.44 | 26.10 | 23.51 | 0.211927E+09 | 341.49 | 26.67 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152527E+10 | 6757.91 | 19-JAN-13:30 | 9.40 | 3.94 | 0.338523E+09 | 549.49 | 30-JAN-14:20 | 2.80 | -1.2 |
February | 0.187780E+10 | 7311.78 | 02-FEB-13:40 | 5.97 | -0.5 | 0.313910E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.366562E+10 | 9194.19 | 03-MAR-13:25 | 14.70 | 8.33 | 0.395013E+09 | 549.50 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.409550E+10 | 9863.48 | 07-APR-12:30 | 26.15 | 15.90 | 0.364680E+09 | 549.91 | 07-APR-13:30 | 26.40 | 16.17 |
May | 0.546844E+10 | 15702.61 | 29-MAY-12:43 | 27.48 | 17.22 | 0.419156E+09 | 550.22 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.688895E+10 | 11378.96 | 25-JUN-14:02 | 26.70 | 23.02 | 0.433421E+09 | 549.86 | 19-JUN-13:30 | 26.70 | 23.02 |
July | 0.795856E+10 | 14300.67 | 02-JUL-13:02 | 26.60 | 21.44 | 0.405089E+09 | 550.06 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.967698E+10 | 16375.39 | 27-AUG-12:32 | 27.97 | 22.65 | 0.454529E+09 | 555.38 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.763119E+10 | 17720.95 | 04-SEP-13:01 | 26.10 | 18.34 | 0.398774E+09 | 571.11 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.735917E+10 | 16392.34 | 22-OCT-12:12 | 21.47 | 16.46 | 0.407820E+09 | 563.74 | 04-OCT-13:09 | 21.47 | 16.46 |
November | 0.326761E+10 | 11450.38 | 02-NOV-12:50 | 15.50 | 8.17 | 0.365450E+09 | 549.58 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.203863E+10 | 7498.90 | 21-DEC-13:13 | 2.97 | -1.7 | 0.335994E+09 | 549.49 | 15-DEC-10:39 | 2.97 | -1.7 |
Annual Sum or Average | 0.614537E+11 | 0.463236E+10 | ||||||||
Minimum of Months | 0.152527E+10 | 6757.91 | 2.97 | -1.7 | 0.313910E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.967698E+10 | 17720.95 | 27.97 | 23.02 | 0.454529E+09 | 571.11 | 32.70 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465447E+09 | 2231.31 | 20-JAN-16:00 | 7.20 | 3.80 | 0.196293E+09 | 313.42 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.595802E+09 | 2437.44 | 24-FEB-15:40 | 7.97 | 1.96 | 0.180828E+09 | 336.24 | 24-FEB-15:50 | 7.88 | 1.88 |
March | 0.191444E+10 | 5491.86 | 29-MAR-16:00 | 7.20 | 4.88 | 0.228343E+09 | 347.84 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.283012E+10 | 13793.44 | 09-APR-16:12 | 16.83 | 14.03 | 0.216948E+09 | 347.85 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.434471E+10 | 9571.87 | 27-MAY-17:42 | 21.20 | 11.70 | 0.256438E+09 | 347.87 | 15-MAY-13:00 | 21.20 | 11.70 |
June | 0.554311E+10 | 15390.02 | 18-JUN-15:51 | 25.60 | 22.09 | 0.271883E+09 | 347.85 | 08-JUN-09:00 | 25.60 | 22.09 |
July | 0.600084E+10 | 15296.69 | 02-JUL-15:41 | 25.00 | 20.75 | 0.255278E+09 | 347.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.665181E+10 | 13991.90 | 13-AUG-15:52 | 30.00 | 20.46 | 0.286058E+09 | 347.87 | 08-AUG-13:30 | 30.00 | 20.46 |
September | 0.449175E+10 | 14984.81 | 10-SEP-15:51 | 23.30 | 12.88 | 0.244917E+09 | 347.86 | 15-SEP-13:00 | 22.80 | 15.50 |
October | 0.368065E+10 | 7451.44 | 04-OCT-15:30 | 23.35 | 19.12 | 0.240583E+09 | 347.85 | 13-OCT-13:39 | 21.70 | 17.54 |
November | 0.143194E+10 | 3837.53 | 03-NOV-15:30 | 16.10 | 10.65 | 0.204929E+09 | 347.62 | 03-NOV-13:00 | 16.10 | 10.65 |
December | 0.620215E+09 | 2175.38 | 08-DEC-15:40 | 6.30 | 2.04 | 0.190316E+09 | 308.57 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.385708E+11 | 0.277281E+10 | ||||||||
Minimum of Months | 0.465447E+09 | 2175.38 | 6.30 | 1.96 | 0.180828E+09 | 308.57 | 6.20 | 1.88 | ||
Maximum of Months | 0.665181E+10 | 15390.02 | 30.00 | 22.09 | 0.286058E+09 | 347.87 | 30.00 | 22.09 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292688E+09 | 26805.96 | 02-JAN-05:01 | -12.1 |
February | 1339776.46 | 22329.61 | 06-FEB-07:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.294027E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.292688E+09 | 26805.96 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604423E+10 | 17090.50 | 02-JAN-06:12 | -11.7 |
February | 0.490263E+10 | 17193.23 | 06-FEB-06:12 | -13.0 |
March | 0.214883E+10 | 10021.62 | 13-MAR-05:03 | -0.6 |
April | 0.947403E+09 | 7525.54 | 03-APR-06:01 | 2.38 |
May | 0.164412E+09 | 7248.23 | 31-MAY-05:03 | 16.38 |
June | 34877385.53 | 6385.81 | 01-JUN-05:03 | 15.18 |
July | 26321465.92 | 5314.04 | 05-JUL-04:02 | 20.60 |
August | 30920051.01 | 6372.35 | 29-AUG-05:03 | 16.88 |
September | 0.103780E+09 | 6433.36 | 15-SEP-05:03 | 15.92 |
October | 0.492860E+09 | 5182.40 | 19-OCT-05:02 | 5.37 |
November | 0.229691E+10 | 12046.88 | 24-NOV-06:13 | -4.4 |
December | 0.413789E+10 | 9744.01 | 11-DEC-06:15 | 1.70 |
Annual Sum or Average | 0.213311E+11 | |||
Minimum of Months | 26321465.92 | 5182.40 | -13.0 | |
Maximum of Months | 0.604423E+10 | 17193.23 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292594E+10 | 11086.01 | 02-JAN-07:05 | -11.6 |
February | 0.214008E+10 | 8864.39 | 06-FEB-07:11 | -13.1 |
March | 0.105120E+10 | 3145.22 | 20-MAR-06:05 | -0.6 |
April | 0.324144E+09 | 4861.31 | 16-APR-12:32 | 20.93 |
May | 57603577.91 | 3171.93 | 14-MAY-12:52 | 16.10 |
June | 19728717.48 | 2714.78 | 07-JUN-05:03 | 16.70 |
July | 23817630.06 | 3097.53 | 07-JUL-04:02 | 26.02 |
August | 21639791.38 | 3136.88 | 17-AUG-04:02 | 25.00 |
September | 29380296.06 | 3614.58 | 10-SEP-15:12 | 24.03 |
October | 0.107968E+09 | 4544.74 | 09-OCT-13:32 | 13.70 |
November | 0.104046E+10 | 4503.74 | 24-NOV-07:03 | -4.3 |
December | 0.172921E+10 | 5119.93 | 17-DEC-12:25 | 12.20 |
Annual Sum or Average | 0.947116E+10 | |||
Minimum of Months | 19728717.48 | 2714.78 | -13.1 | |
Maximum of Months | 0.292594E+10 | 11086.01 | 26.02 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212289E+10 | 9649.64 | 02-JAN-06:12 | -11.7 |
February | 0.136273E+10 | 5067.57 | 06-FEB-08:55 | -12.2 |
March | 0.524441E+09 | 3622.76 | 17-MAR-07:16 | -1.1 |
April | 0.119580E+09 | 5903.01 | 12-APR-05:03 | 4.32 |
May | 26166212.99 | 5153.65 | 15-MAY-05:02 | 8.07 |
June | 25303329.98 | 4116.34 | 12-JUN-04:02 | 18.80 |
July | 23846829.24 | 3921.37 | 27-JUL-04:02 | 21.78 |
August | 24490414.94 | 4179.00 | 17-AUG-04:02 | 25.00 |
September | 35949470.71 | 4721.90 | 25-SEP-05:03 | 14.40 |
October | 46536258.22 | 6616.18 | 27-OCT-05:02 | 6.02 |
November | 0.491679E+09 | 8008.00 | 06-NOV-06:01 | 5.00 |
December | 0.101311E+10 | 3908.66 | 22-DEC-08:08 | -4.1 |
Annual Sum or Average | 0.581672E+10 | |||
Minimum of Months | 23846829.24 | 3622.76 | -12.2 | |
Maximum of Months | 0.212289E+10 | 9649.64 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.702765E+09 | 25062.58 | 02-JAN-05:01 | -12.1 |
February | 0.185980E+09 | 22051.96 | 06-FEB-06:01 | -12.9 |
March | 8608617.65 | 19514.29 | 20-MAR-06:01 | -0.6 |
April | 1129362.70 | 18822.71 | 03-APR-06:01 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 26768150.22 | 19678.18 | 24-NOV-07:01 | -4.3 |
December | 44684447.18 | 19656.69 | 11-DEC-07:01 | 1.70 |
Annual Sum or Average | 0.969936E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.702765E+09 | 25062.58 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218683E+10 | 34356.01 | 02-JAN-01:22 | -11.4 |
February | 0.134443E+10 | 33761.99 | 06-FEB-05:01 | -13.2 |
March | 0.246480E+09 | 30491.13 | 20-MAR-05:01 | -1.5 |
April | 42606325.04 | 29210.40 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.437721E+09 | 31045.89 | 20-NOV-06:01 | 0.00 |
December | 0.672383E+09 | 31238.46 | 26-DEC-06:01 | 6.20 |
Annual Sum or Average | 0.493045E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.218683E+10 | 34356.01 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422671E+10 | 12123.34 | 02-JAN-00:42 | -11.0 |
February | 0.349439E+10 | 12106.37 | 06-FEB-00:52 | -13.3 |
March | 0.974494E+09 | 11036.84 | 13-MAR-04:01 | -0.1 |
April | 0.228133E+09 | 9877.74 | 03-APR-05:01 | 2.70 |
May | 3630078.49 | 8463.85 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 39155785.51 | 8739.35 | 28-OCT-06:03 | 3.90 |
November | 0.113919E+10 | 11036.50 | 20-NOV-05:01 | 0.50 |
December | 0.247535E+10 | 11795.76 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.125811E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.422671E+10 | 12123.34 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236591E+10 | 12788.62 | 02-JAN-00:42 | -11.0 |
February | 0.175081E+10 | 12771.58 | 06-FEB-00:52 | -13.3 |
March | 0.478174E+09 | 11678.64 | 13-MAR-04:01 | -0.1 |
April | 0.122543E+09 | 10434.73 | 03-APR-05:01 | 2.70 |
May | 2422241.04 | 4340.04 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 23840.50 | 79.47 | 30-SEP-06:05 | 11.20 |
October | 22165492.22 | 6084.37 | 28-OCT-06:03 | 3.90 |
November | 0.594023E+09 | 11684.54 | 20-NOV-05:01 | 0.50 |
December | 0.133794E+10 | 12400.65 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.667402E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.236591E+10 | 12788.62 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290223E+10 | 16044.81 | 02-JAN-00:42 | -11.0 |
February | 0.213665E+10 | 16009.83 | 06-FEB-04:52 | -13.3 |
March | 0.656381E+09 | 14537.94 | 13-MAR-04:01 | -0.1 |
April | 0.199790E+09 | 13158.68 | 03-APR-05:01 | 2.70 |
May | 6255164.09 | 8675.33 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 22254549.37 | 9453.67 | 28-OCT-06:03 | 3.90 |
November | 0.691500E+09 | 14575.52 | 20-NOV-05:01 | 0.50 |
December | 0.161407E+10 | 15451.79 | 31-DEC-23:52 | -8.3 |
Annual Sum or Average | 0.822913E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.290223E+10 | 16044.81 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260012E+10 | 13851.36 | 02-JAN-00:42 | -11.0 |
February | 0.207387E+10 | 13832.19 | 06-FEB-00:52 | -13.3 |
March | 0.550551E+09 | 12629.47 | 13-MAR-04:01 | -0.1 |
April | 0.145550E+09 | 11272.62 | 03-APR-05:01 | 2.70 |
May | 5163318.06 | 5468.28 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 203624.66 | 457.84 | 30-SEP-06:05 | 11.20 |
October | 26403496.40 | 6145.19 | 28-OCT-06:03 | 3.90 |
November | 0.715742E+09 | 12681.59 | 20-NOV-05:01 | 0.50 |
December | 0.151511E+10 | 13393.82 | 31-DEC-23:52 | -8.3 |
Annual Sum or Average | 0.763271E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.260012E+10 | 13851.36 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230654E+10 | 9337.89 | 02-JAN-00:42 | -11.0 |
February | 0.183418E+10 | 8715.63 | 06-FEB-05:01 | -13.2 |
March | 0.379088E+09 | 7859.19 | 13-MAR-05:01 | -0.6 |
April | 53748481.58 | 7523.97 | 03-APR-05:01 | 2.70 |
May | 169327.25 | 1128.85 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.188695E+09 | 7777.09 | 24-NOV-06:01 | -4.4 |
December | 0.580744E+09 | 7695.90 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.534317E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.230654E+10 | 9337.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117598E+10 | 9984.36 | 02-JAN-00:42 | -11.0 |
February | 0.745024E+09 | 9354.95 | 06-FEB-05:01 | -13.2 |
March | 0.135068E+09 | 8273.74 | 20-MAR-05:01 | -1.5 |
April | 22366945.61 | 7908.56 | 03-APR-05:01 | 2.70 |
May | 59948.30 | 299.74 | 04-MAY-06:03 | 10.93 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 77862125.11 | 8188.99 | 24-NOV-06:01 | -4.4 |
December | 0.286817E+09 | 8189.42 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.244318E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.117598E+10 | 9984.36 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564080E+10 | 15628.86 | 02-JAN-08:00 | -11.1 |
February | 0.487382E+10 | 15512.88 | 06-FEB-07:10 | -13.2 |
March | 0.336502E+10 | 13481.50 | 23-MAR-06:10 | -4.7 |
April | 0.170879E+10 | 12306.39 | 03-APR-06:10 | 2.38 |
May | 0.647955E+09 | 10552.80 | 01-MAY-06:10 | 7.67 |
June | 15707394.76 | 4678.37 | 02-JUN-06:05 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 79352236.99 | 9402.87 | 20-SEP-06:05 | 12.48 |
October | 0.474430E+09 | 10349.69 | 18-OCT-06:10 | 5.68 |
November | 0.220086E+10 | 13354.72 | 24-NOV-07:10 | -4.3 |
December | 0.377294E+10 | 13326.34 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.227797E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.564080E+10 | 15628.86 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132886E+10 | 10118.61 | 02-JAN-00:42 | -11.0 |
February | 0.924671E+09 | 9433.69 | 06-FEB-05:01 | -13.2 |
March | 0.135966E+09 | 8280.16 | 13-MAR-05:01 | -0.6 |
April | 29305227.12 | 7667.37 | 03-APR-06:01 | 2.38 |
May | 1040321.33 | 3120.12 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.105130E+09 | 8213.23 | 24-NOV-06:01 | -4.4 |
December | 0.323931E+09 | 8231.07 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.284890E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.132886E+10 | 10118.61 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224011E+10 | 10319.65 | 02-JAN-00:42 | -11.0 |
February | 0.161600E+10 | 10116.65 | 06-FEB-00:52 | -13.3 |
March | 0.267276E+09 | 8585.40 | 13-MAR-05:01 | -0.6 |
April | 35636313.60 | 8223.31 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 929038.86 | 4224.57 | 28-OCT-06:03 | 3.90 |
November | 0.356165E+09 | 9090.02 | 24-NOV-05:01 | -4.0 |
December | 0.861817E+09 | 8752.70 | 26-DEC-06:01 | 6.20 |
Annual Sum or Average | 0.537793E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.224011E+10 | 10319.65 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125483E+10 | 11034.86 | 02-JAN-00:42 | -11.0 |
February | 0.791296E+09 | 10807.33 | 06-FEB-00:52 | -13.3 |
March | 0.135391E+09 | 9009.76 | 13-MAR-05:01 | -0.6 |
April | 20042383.76 | 8537.45 | 03-APR-05:01 | 2.70 |
May | 12931.21 | 64.66 | 04-MAY-06:03 | 10.93 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 3519569.68 | 5116.61 | 28-OCT-06:03 | 3.90 |
November | 0.191755E+09 | 9582.96 | 24-NOV-05:01 | -4.0 |
December | 0.493066E+09 | 9211.02 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.288991E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.125483E+10 | 11034.86 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143684E+10 | 14109.46 | 02-JAN-00:42 | -11.0 |
February | 0.854388E+09 | 13815.43 | 06-FEB-04:52 | -13.3 |
March | 0.166616E+09 | 11819.73 | 13-MAR-05:01 | -0.6 |
April | 33581356.84 | 11134.08 | 03-APR-05:01 | 2.70 |
May | 390300.55 | 2602.00 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 539543.73 | 3429.62 | 28-OCT-06:03 | 3.90 |
November | 0.183695E+09 | 11836.28 | 24-NOV-06:01 | -4.4 |
December | 0.516167E+09 | 11963.92 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.319221E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.143684E+10 | 14109.46 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137431E+10 | 11154.76 | 02-JAN-00:42 | -11.0 |
February | 0.939106E+09 | 10922.74 | 06-FEB-00:52 | -13.3 |
March | 0.151731E+09 | 9048.09 | 13-MAR-05:01 | -0.6 |
April | 28132556.79 | 8627.83 | 03-APR-05:01 | 2.70 |
May | 572760.11 | 3039.98 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 3116756.63 | 5053.88 | 28-OCT-06:03 | 3.90 |
November | 0.227362E+09 | 9601.14 | 24-NOV-05:01 | -4.0 |
December | 0.533541E+09 | 9262.31 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.325787E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.137431E+10 | 11154.76 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107273E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.929524E+09 | 1390.78 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.106390E+10 | 1168.79 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.926661E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.985681E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.971625E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.914204E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102765E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936962E+09 | 1062.74 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.998687E+09 | 1250.29 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.104244E+10 | 1503.90 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.105112E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119212E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.914204E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107273E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675440E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.587226E+09 | 888.25 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.673613E+09 | 804.70 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.587568E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.626024E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.617348E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.580595E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.652142E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.593618E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631670E+09 | 796.77 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.659076E+09 | 952.10 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.659441E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.754376E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.580595E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.675440E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105389E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.918701E+09 | 1382.99 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105935E+10 | 1073.66 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.927764E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.988534E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.975130E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.917053E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102963E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.936115E+09 | 1031.43 | 27-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.992039E+09 | 1214.48 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103227E+10 | 1503.90 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102760E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118581E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.917053E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105935E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669753E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582998E+09 | 870.34 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.670402E+09 | 729.25 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.586758E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.623907E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.615439E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.579085E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.650343E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.592556E+09 | 703.62 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.628957E+09 | 773.47 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.654099E+09 | 952.03 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.655193E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.750949E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.579085E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.670402E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107013E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.927784E+09 | 1385.65 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.106311E+10 | 1152.87 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.926130E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.985349E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.971230E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.913737E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102733E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936279E+09 | 1043.19 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.997411E+09 | 1239.17 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.104074E+10 | 1503.90 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.104773E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119070E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.913737E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107013E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674246E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.586364E+09 | 886.05 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.673247E+09 | 799.61 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.587222E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.625802E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.617034E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.580275E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.651883E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.593215E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631081E+09 | 791.49 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.658479E+09 | 952.10 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.658150E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.753700E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.580275E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.674246E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105116E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.917836E+09 | 1377.60 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105880E+10 | 1054.07 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.927106E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.988112E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.974560E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.916491E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102920E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.935467E+09 | 927.16 | 01-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.991413E+09 | 1201.24 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103070E+10 | 1503.90 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102600E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118468E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.916491E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105880E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.668733E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582190E+09 | 867.40 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.670025E+09 | 721.71 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.586430E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.623709E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.615227E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.578871E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.650126E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.592163E+09 | 695.26 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.628643E+09 | 767.46 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.653510E+09 | 952.03 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.653841E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.750347E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.578871E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.670025E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107273E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.929524E+09 | 1390.78 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.106390E+10 | 1168.77 | 02-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.926661E+09 | 927.16 | 03-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.985681E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.971607E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.914204E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102765E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936961E+09 | 1062.71 | 27-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.998687E+09 | 1250.27 | 31-OCT-15:00 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.104244E+10 | 1503.90 | 06-NOV-16:49 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.105112E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119212E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.914204E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107273E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675440E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.587226E+09 | 888.25 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.673613E+09 | 804.69 | 02-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.587568E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.626024E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.617348E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.580595E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.652142E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.593617E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631670E+09 | 796.76 | 31-OCT-15:00 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.659076E+09 | 952.10 | 06-NOV-16:49 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.659441E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.754376E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.580595E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.675440E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105389E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.918700E+09 | 1382.98 | 15-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105935E+10 | 1073.64 | 16-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.927763E+09 | 927.16 | 03-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.988533E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.975129E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.917053E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102963E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.936115E+09 | 1031.40 | 27-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.992039E+09 | 1214.46 | 31-OCT-15:00 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103227E+10 | 1503.90 | 06-NOV-16:49 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102760E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118581E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.917053E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105935E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.669753E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582997E+09 | 870.33 | 15-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.670402E+09 | 729.23 | 16-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.586747E+09 | 586.93 | 03-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.623907E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.615439E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.579084E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.650343E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.592556E+09 | 703.60 | 27-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.628957E+09 | 773.46 | 06-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.654099E+09 | 952.03 | 06-NOV-16:49 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.655193E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.750948E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.579084E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.670402E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107273E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159601E+10 |
February | 0.901968E+09 | 0.929524E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142264E+10 |
March | 0.107774E+10 | 0.106390E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113534E+10 |
April | 0.956342E+09 | 0.926661E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 655003.56 | 0.754103E+09 |
May | 0.103597E+10 | 0.985681E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3575935.42 | 0.457946E+09 |
June | 0.103308E+10 | 0.971625E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21749162.38 | 0.247182E+09 |
July | 0.959235E+09 | 0.914204E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50161520.90 | 90805872.51 |
August | 0.107774E+10 | 0.102765E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59259260.00 | 0.114128E+09 |
September | 0.956342E+09 | 0.936962E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7632168.78 | 0.248254E+09 |
October | 0.994195E+09 | 0.998687E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108578.31 | 0.602287E+09 |
November | 0.984487E+09 | 0.104244E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108938E+10 |
December | 0.959235E+09 | 0.105112E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132661E+10 |
Annual Sum or Average | 0.119305E+11 | 0.119212E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143142E+09 | 0.908469E+10 |
Minimum of Months | 0.901968E+09 | 0.914204E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90805872.51 |
Maximum of Months | 0.107774E+10 | 0.107273E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59259260.00 | 0.159601E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.675440E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106429E+10 |
February | 0.571020E+09 | 0.587226E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954650E+09 |
March | 0.682301E+09 | 0.673613E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763676E+09 |
April | 0.605444E+09 | 0.587568E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 438371.84 | 0.517984E+09 |
May | 0.655854E+09 | 0.626024E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1778741.97 | 0.306418E+09 |
June | 0.654023E+09 | 0.617348E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15266389.50 | 0.161060E+09 |
July | 0.607275E+09 | 0.580595E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35092710.32 | 57823852.24 |
August | 0.682301E+09 | 0.652142E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39678969.13 | 76494068.22 |
September | 0.605444E+09 | 0.593618E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5180423.24 | 0.168506E+09 |
October | 0.629407E+09 | 0.631670E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72384.07 | 0.409663E+09 |
November | 0.623262E+09 | 0.659076E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734007E+09 |
December | 0.607275E+09 | 0.659441E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887805E+09 |
Annual Sum or Average | 0.755301E+10 | 0.754376E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97507990.09 | 0.610238E+10 |
Minimum of Months | 0.571020E+09 | 0.580595E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57823852.24 |
Maximum of Months | 0.682301E+09 | 0.675440E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39678969.13 | 0.106429E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105389E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163350E+10 |
February | 0.901968E+09 | 0.918701E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148228E+10 |
March | 0.107774E+10 | 0.105935E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118888E+10 |
April | 0.956342E+09 | 0.927764E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 629978.63 | 0.787731E+09 |
May | 0.103597E+10 | 0.988534E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2812230.29 | 0.459470E+09 |
June | 0.103308E+10 | 0.975130E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21473585.25 | 0.242273E+09 |
July | 0.959235E+09 | 0.917053E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50647620.65 | 89648414.15 |
August | 0.107774E+10 | 0.102963E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57303456.84 | 0.117851E+09 |
September | 0.956342E+09 | 0.936115E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7281182.18 | 0.268557E+09 |
October | 0.994195E+09 | 0.992039E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108141.96 | 0.670543E+09 |
November | 0.984487E+09 | 0.103227E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114908E+10 |
December | 0.959235E+09 | 0.102760E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138988E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118581E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140256E+09 | 0.947970E+10 |
Minimum of Months | 0.901968E+09 | 0.917053E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89648414.15 |
Maximum of Months | 0.107774E+10 | 0.105935E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57303456.84 | 0.163350E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.669753E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106819E+10 |
February | 0.570983E+09 | 0.582998E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957789E+09 |
March | 0.682256E+09 | 0.670402E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776538E+09 |
April | 0.605404E+09 | 0.586758E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 528805.47 | 0.517255E+09 |
May | 0.655811E+09 | 0.623907E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2971921.47 | 0.307271E+09 |
June | 0.653980E+09 | 0.615439E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15543088.41 | 0.168639E+09 |
July | 0.607235E+09 | 0.579085E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36790851.09 | 64994387.51 |
August | 0.682256E+09 | 0.650343E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40722173.14 | 80123990.99 |
September | 0.605404E+09 | 0.592556E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5684421.87 | 0.168283E+09 |
October | 0.629366E+09 | 0.628957E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137009.24 | 0.413525E+09 |
November | 0.623221E+09 | 0.654099E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727574E+09 |
December | 0.607235E+09 | 0.655193E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890980E+09 |
Annual Sum or Average | 0.755252E+10 | 0.750949E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102378E+09 | 0.614116E+10 |
Minimum of Months | 0.570983E+09 | 0.579085E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64994387.51 |
Maximum of Months | 0.682256E+09 | 0.670402E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40722173.14 | 0.106819E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107013E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900392E+09 |
February | 0.901968E+09 | 0.927784E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795403E+09 |
March | 0.107774E+10 | 0.106311E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635785E+09 |
April | 0.956342E+09 | 0.926130E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 431774.11 | 0.418247E+09 |
May | 0.103597E+10 | 0.985349E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2676476.73 | 0.245300E+09 |
June | 0.103308E+10 | 0.971230E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12638102.12 | 0.128951E+09 |
July | 0.959235E+09 | 0.913737E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29363917.39 | 44448624.57 |
August | 0.107774E+10 | 0.102733E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33230249.16 | 60400915.05 |
September | 0.956342E+09 | 0.936279E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4155739.43 | 0.145229E+09 |
October | 0.994195E+09 | 0.997411E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65145.21 | 0.366162E+09 |
November | 0.984487E+09 | 0.104074E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664985E+09 |
December | 0.959235E+09 | 0.104773E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780603E+09 |
Annual Sum or Average | 0.119305E+11 | 0.119070E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82561404.16 | 0.518591E+10 |
Minimum of Months | 0.901968E+09 | 0.913737E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44448624.57 |
Maximum of Months | 0.107774E+10 | 0.107013E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33230249.16 | 0.900392E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.674246E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601799E+09 |
February | 0.571020E+09 | 0.586364E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539612E+09 |
March | 0.682301E+09 | 0.673247E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432650E+09 |
April | 0.605444E+09 | 0.587222E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248457.36 | 0.291182E+09 |
May | 0.655854E+09 | 0.625802E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1077991.28 | 0.168290E+09 |
June | 0.654023E+09 | 0.617034E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8363202.40 | 87421521.42 |
July | 0.607275E+09 | 0.580275E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19042380.94 | 30877411.44 |
August | 0.682301E+09 | 0.651883E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21229504.24 | 43221016.88 |
September | 0.605444E+09 | 0.593215E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2652823.36 | 0.100972E+09 |
October | 0.629407E+09 | 0.631081E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43429.59 | 0.251383E+09 |
November | 0.623262E+09 | 0.658479E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449875E+09 |
December | 0.607275E+09 | 0.658150E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525418E+09 |
Annual Sum or Average | 0.755301E+10 | 0.753700E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52657789.16 | 0.352270E+10 |
Minimum of Months | 0.571020E+09 | 0.580275E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30877411.44 |
Maximum of Months | 0.682301E+09 | 0.674246E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21229504.24 | 0.601799E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105116E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815032E+10 |
February | 0.901968E+09 | 0.917836E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806821E+10 |
March | 0.107774E+10 | 0.105880E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725824E+10 |
April | 0.956342E+09 | 0.927106E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17322561.36 | 0.430555E+10 |
May | 0.103597E+10 | 0.988112E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70312146.77 | 0.251742E+10 |
June | 0.103308E+10 | 0.974560E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495430E+09 | 0.801728E+09 |
July | 0.959235E+09 | 0.916491E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104609E+10 | 0.108024E+09 |
August | 0.107774E+10 | 0.102920E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125053E+10 | 0.267977E+09 |
September | 0.956342E+09 | 0.935467E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207214E+09 | 0.121301E+10 |
October | 0.994195E+09 | 0.991413E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2913040.71 | 0.333101E+10 |
November | 0.984487E+09 | 0.103070E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607572E+10 |
December | 0.959235E+09 | 0.102600E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733462E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118468E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308981E+10 | 0.494318E+11 |
Minimum of Months | 0.901968E+09 | 0.916491E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108024E+09 |
Maximum of Months | 0.107774E+10 | 0.105880E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125053E+10 | 0.815032E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.668733E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604016E+09 |
February | 0.570983E+09 | 0.582190E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539193E+09 |
March | 0.682256E+09 | 0.670025E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439941E+09 |
April | 0.605404E+09 | 0.586430E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 299722.50 | 0.291550E+09 |
May | 0.655811E+09 | 0.623709E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727681.73 | 0.169518E+09 |
June | 0.653980E+09 | 0.615227E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7972471.64 | 93335231.01 |
July | 0.607235E+09 | 0.578871E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19229476.66 | 35486917.18 |
August | 0.682256E+09 | 0.650126E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21447391.69 | 45878885.61 |
September | 0.605404E+09 | 0.592163E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2771923.66 | 0.101355E+09 |
October | 0.629366E+09 | 0.628643E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44331.29 | 0.254880E+09 |
November | 0.623221E+09 | 0.653510E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443613E+09 |
December | 0.607235E+09 | 0.653841E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526025E+09 |
Annual Sum or Average | 0.755252E+10 | 0.750347E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53492999.16 | 0.354479E+10 |
Minimum of Months | 0.570983E+09 | 0.578871E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35486917.18 |
Maximum of Months | 0.682256E+09 | 0.670025E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21447391.69 | 0.604016E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107273E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138452E+10 |
February | 0.901968E+09 | 0.929524E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123436E+10 |
March | 0.107774E+10 | 0.106390E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100846E+10 |
April | 0.956342E+09 | 0.926661E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535954.89 | 0.674785E+09 |
May | 0.103597E+10 | 0.985681E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074266.27 | 0.405277E+09 |
June | 0.103308E+10 | 0.971607E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18306700.19 | 0.215082E+09 |
July | 0.959235E+09 | 0.914204E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42650608.86 | 78158659.72 |
August | 0.107774E+10 | 0.102765E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49913437.70 | 99604107.95 |
September | 0.956342E+09 | 0.936961E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6248901.13 | 0.224087E+09 |
October | 0.994195E+09 | 0.998687E+09 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95980.01 | 0.550645E+09 |
November | 0.984487E+09 | 0.104244E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991945E+09 |
December | 0.959235E+09 | 0.105112E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118086E+10 |
Annual Sum or Average | 0.119305E+11 | 0.119212E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120826E+09 | 0.804779E+10 |
Minimum of Months | 0.901968E+09 | 0.914204E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78158659.72 |
Maximum of Months | 0.107774E+10 | 0.107273E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49913437.70 | 0.138452E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.675440E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922848E+09 |
February | 0.421807E+09 | 0.587226E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831741E+09 |
March | 0.502994E+09 | 0.673613E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675995E+09 |
April | 0.447140E+09 | 0.587568E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 378198.50 | 0.458353E+09 |
May | 0.484071E+09 | 0.626024E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1634278.17 | 0.268069E+09 |
June | 0.482240E+09 | 0.617348E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13089664.26 | 0.139141E+09 |
July | 0.448971E+09 | 0.580595E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30431798.18 | 49348341.98 |
August | 0.502994E+09 | 0.652142E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33790317.65 | 65814359.34 |
September | 0.447140E+09 | 0.593617E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4403523.82 | 0.149551E+09 |
October | 0.465148E+09 | 0.631670E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64659.91 | 0.368414E+09 |
November | 0.460569E+09 | 0.659076E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664889E+09 |
December | 0.448971E+09 | 0.659441E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790461E+09 |
Annual Sum or Average | 0.557719E+10 | 0.754376E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83792440.50 | 0.538462E+10 |
Minimum of Months | 0.421807E+09 | 0.580595E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49348341.98 |
Maximum of Months | 0.502994E+09 | 0.675440E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33790317.65 | 0.922848E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105389E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142515E+10 |
February | 0.901968E+09 | 0.918700E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130008E+10 |
March | 0.107774E+10 | 0.105935E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105274E+10 |
April | 0.956342E+09 | 0.927763E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530076.01 | 0.700035E+09 |
May | 0.103597E+10 | 0.988533E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2317401.04 | 0.405661E+09 |
June | 0.103308E+10 | 0.975129E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18002901.80 | 0.211391E+09 |
July | 0.959235E+09 | 0.917053E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42386226.26 | 77439960.93 |
August | 0.107774E+10 | 0.102963E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48046226.76 | 0.102599E+09 |
September | 0.956342E+09 | 0.936115E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6039885.75 | 0.239662E+09 |
October | 0.994195E+09 | 0.992039E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78162.66 | 0.599172E+09 |
November | 0.984487E+09 | 0.103227E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104313E+10 |
December | 0.959235E+09 | 0.102760E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124191E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118581E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117401E+09 | 0.839897E+10 |
Minimum of Months | 0.901968E+09 | 0.917053E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77439960.93 |
Maximum of Months | 0.107774E+10 | 0.105935E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48046226.76 | 0.142515E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.669753E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926809E+09 |
February | 0.570983E+09 | 0.582997E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.831989E+09 |
March | 0.682256E+09 | 0.670402E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686770E+09 |
April | 0.605404E+09 | 0.586747E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 424754.13 | 0.459428E+09 |
May | 0.655811E+09 | 0.623907E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2463155.92 | 0.271302E+09 |
June | 0.653980E+09 | 0.615439E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12772517.34 | 0.147042E+09 |
July | 0.607235E+09 | 0.579084E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30503239.51 | 56179631.32 |
August | 0.682256E+09 | 0.650343E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33936769.73 | 69509542.62 |
September | 0.605404E+09 | 0.592556E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4535728.70 | 0.151160E+09 |
October | 0.629366E+09 | 0.628957E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96879.21 | 0.373318E+09 |
November | 0.623221E+09 | 0.654099E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659828E+09 |
December | 0.607235E+09 | 0.655193E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792676E+09 |
Annual Sum or Average | 0.755252E+10 | 0.750948E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84733044.54 | 0.542601E+10 |
Minimum of Months | 0.570983E+09 | 0.579084E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56179631.32 |
Maximum of Months | 0.682256E+09 | 0.670402E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33936769.73 | 0.926809E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192333E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173979E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142658E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488241.85 | 0.950372E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3230444.15 | 0.555246E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18309565.93 | 0.289196E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45130588.22 | 97215168.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52453663.01 | 0.132386E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5060178.14 | 0.319165E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7248.92 | 0.801336E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143956E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170310E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124680E+09 | 0.113773E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97215168.91 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52453663.01 | 0.192333E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235721E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213479E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175627E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641650.08 | 0.117172E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4016298.61 | 0.698538E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23531308.88 | 0.368595E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57470125.98 | 0.124748E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67811657.50 | 0.167701E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6638994.63 | 0.392641E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17309.71 | 0.976186E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172418E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205124E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160127E+09 | 0.139238E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124748E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67811657.50 | 0.235721E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238206E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215849E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176721E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157565.07 | 0.119141E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1613391.57 | 0.731213E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19252753.04 | 0.388278E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47734704.18 | 0.136214E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62375073.05 | 0.166223E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5726118.75 | 0.396728E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967437E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167492E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201522E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136860E+09 | 0.139754E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136214E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62375073.05 | 0.238206E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2699.20 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 1390.78 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.67 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1168.79 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2216.94 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 07-APR-13:00 | 1651.08 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.47 | 29-MAY-11:50 | 962.25 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.02 | 19-JUN-21:03 | 602.92 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.42 | 09-JUL-14:10 | 280.95 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.20 | 04-AUG-21:03 | 385.78 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 1062.74 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.07 | 14-SEP-14:00 | 502.61 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1250.29 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 25-OCT-11:00 | 1361.56 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2170.81 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.05 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.95 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 347.20 | 2938.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1799.46 | 01-JAN-21:00 |
February | 827.22 | 01-FEB-10:09 | 888.25 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1969.69 | 06-FEB-00:55 |
March | 827.22 | 01-MAR-10:09 | 804.70 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1477.88 | 21-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 07-APR-13:00 | 1092.59 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.14 | 29-MAY-11:50 | 638.68 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.48 | 25-JUN-19:00 | 392.19 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.27 | 09-JUL-14:10 | 187.05 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.90 | 04-AUG-21:03 | 268.92 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 382.35 | 10-SEP-08:00 |
October | 827.22 | 02-OCT-09:09 | 796.77 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 25-OCT-11:00 | 992.83 | 08-OCT-08:20 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1447.09 | 22-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.02 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.05 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 234.90 | 1969.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2699.21 | 01-JAN-21:00 |
February | 1306.65 | 01-FEB-10:09 | 1382.99 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2938.67 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1073.66 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2226.03 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 | 07-APR-13:00 | 1674.13 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 29-MAY-11:50 | 972.95 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.92 | 19-JUN-21:03 | 595.32 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.72 | 09-JUL-14:08 | 272.44 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.09 | 04-AUG-21:03 | 387.78 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 1031.43 | 27-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 | 14-SEP-14:00 | 533.82 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 1214.48 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 25-OCT-11:00 | 1417.45 | 08-OCT-10:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2177.03 | 22-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2919.06 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.44 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 346.09 | 2938.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1799.46 | 01-JAN-21:00 |
February | 827.17 | 01-FEB-10:09 | 870.34 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1966.34 | 06-FEB-00:55 |
March | 827.17 | 01-MAR-10:09 | 729.25 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1482.30 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 08-APR-10:00 | 1111.93 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.47 | 29-MAY-11:50 | 653.38 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.12 | 19-JUN-21:03 | 457.54 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.16 | 09-JUL-14:08 | 268.04 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.19 | 04-AUG-21:03 | 262.40 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 703.62 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.38 | 14-SEP-14:00 | 358.22 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 773.47 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 25-OCT-11:00 | 917.13 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1446.89 | 22-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1946.03 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.40 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 232.19 | 1966.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1546.06 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1385.65 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1559.68 | 06-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 1152.87 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1184.00 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 07-APR-13:00 | 957.78 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.59 | 29-MAY-12:00 | 539.51 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.58 | 19-JUN-21:03 | 331.98 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.34 | 09-JUL-13:52 | 143.36 | 11-JUL-04:43 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.94 | 12-AUG-19:00 | 224.14 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 1043.19 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.56 | 14-SEP-14:00 | 302.86 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1239.17 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 859.84 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1299.26 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1583.88 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.36 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 195.94 | 1583.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1040.16 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 886.05 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1060.52 | 05-FEB-08:30 |
March | 827.22 | 01-MAR-10:09 | 799.61 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 815.71 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 07-APR-13:00 | 650.52 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.50 | 29-MAY-12:00 | 375.71 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.77 | 19-JUN-21:03 | 227.10 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.48 | 09-JUL-13:50 | 101.62 | 02-JUL-18:47 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.48 | 12-AUG-19:00 | 160.98 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 202.08 | 17-SEP-10:00 |
October | 827.22 | 02-OCT-09:09 | 791.49 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 632.56 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 877.05 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1064.72 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.62 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 140.48 | 1064.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 40462.37 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1377.60 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 43717.48 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1054.07 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 33272.08 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2610.65 | 07-APR-17:00 | 23353.84 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5882.09 | 30-MAY-11:10 | 16055.11 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13943.33 | 19-JUN-11:02 | 9558.57 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10696.71 | 07-JUL-11:02 | 3117.94 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11143.36 | 24-AUG-16:03 | 6231.37 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 927.16 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6417.78 | 14-SEP-16:05 | 13241.64 | 11-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1201.24 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.93 | 25-OCT-11:10 | 20077.84 | 31-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32716.87 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 33577.78 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3117.94 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13943.33 | 43717.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1042.20 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 867.40 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1039.79 | 06-FEB-00:52 |
March | 827.17 | 01-MAR-10:09 | 721.71 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 793.88 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 07-APR-13:00 | 673.02 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.42 | 29-MAY-12:00 | 378.57 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.22 | 19-JUN-21:03 | 241.61 | 02-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.27 | 09-JUL-13:50 | 128.34 | 02-JUL-18:47 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.55 | 12-AUG-19:00 | 161.04 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 695.26 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | 14-SEP-14:00 | 210.36 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 767.46 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 25-OCT-11:00 | 585.83 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 869.61 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1068.59 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.34 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 133.55 | 1068.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2340.22 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1390.78 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2444.02 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1168.77 | 02-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1856.03 | 21-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 | 07-APR-13:00 | 1499.29 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.99 | 29-MAY-12:10 | 878.07 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.53 | 19-JUN-21:03 | 527.57 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.13 | 09-JUL-13:52 | 235.41 | 11-JUL-04:50 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.70 | 04-AUG-21:03 | 350.06 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 1062.71 | 27-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 14-SEP-14:00 | 453.84 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1250.27 | 31-OCT-15:00 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 | 25-OCT-11:00 | 1248.19 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1922.28 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.15 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.41 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 290.70 | 2444.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1558.24 | 31-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 888.25 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.34 | 06-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 804.69 | 02-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1298.24 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 07-APR-13:00 | 991.45 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 29-MAY-12:10 | 581.52 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.10 | 25-JUN-19:00 | 342.55 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.50 | 09-JUL-14:10 | 153.38 | 11-JUL-04:50 |
August | 805.43 | 01-AUG-07:10 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.14 | 12-AUG-18:53 | 243.13 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 309.48 | 10-SEP-07:50 |
October | 805.43 | 02-OCT-07:10 | 796.76 | 31-OCT-15:00 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 25-OCT-11:00 | 934.52 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 952.10 | 06-NOV-16:49 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1279.88 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.10 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.38 | |||||
Maximum of Months | 805.43 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 217.14 | 1629.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2419.88 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 1382.98 | 15-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2449.81 | 06-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 1073.64 | 16-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1958.13 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 927.16 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 07-APR-13:00 | 1517.42 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.97 | 29-MAY-12:10 | 885.98 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.42 | 19-JUN-21:03 | 521.82 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.41 | 09-JUL-14:08 | 230.21 | 11-JUL-04:50 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.02 | 12-AUG-18:53 | 351.72 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 1031.40 | 27-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.84 | 14-SEP-14:00 | 475.93 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 1214.46 | 31-OCT-15:00 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | 25-OCT-11:00 | 1345.41 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:49 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1969.51 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.14 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.21 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 303.02 | 2449.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1561.54 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 870.33 | 15-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1629.34 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 729.23 | 16-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1241.48 | 21-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 586.93 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 07-APR-13:00 | 1008.60 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.99 | 29-MAY-12:10 | 594.28 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 | 19-JUN-21:03 | 377.09 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.34 | 09-JUL-13:30 | 211.01 | 02-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.83 | 12-AUG-18:53 | 237.78 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 703.60 | 27-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 | 14-SEP-14:00 | 310.87 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 773.46 | 06-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 25-OCT-11:00 | 836.63 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:49 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1278.16 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1618.10 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.01 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 201.83 | 1629.34 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3424.37 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3370.63 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2519.26 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 | 07-APR-13:00 | 2157.23 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.30 | 29-MAY-12:00 | 1247.87 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.18 | 19-JUN-21:03 | 716.87 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 | 09-JUL-13:52 | 323.29 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.34 | 12-AUG-19:00 | 478.53 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 14-SEP-14:00 | 636.75 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 25-OCT-11:00 | 1839.61 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2851.16 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3484.75 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.34 | 3484.75 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4206.86 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4082.45 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3162.76 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 07-APR-13:00 | 2709.37 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.00 | 29-MAY-11:53 | 1557.45 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.02 | 19-JUN-21:03 | 914.13 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.10 | 09-JUL-13:52 | 414.72 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.37 | 12-AUG-18:53 | 603.10 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.82 | 14-SEP-14:00 | 789.10 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 25-OCT-11:00 | 2245.40 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3480.38 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4172.09 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.72 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.37 | 4206.86 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3969.17 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4129.54 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3335.26 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 08-APR-10:00 | 2494.86 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.77 | 29-MAY-12:00 | 1450.00 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.29 | 19-JUN-21:03 | 854.67 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.35 | 07-JUL-22:00 | 483.00 | 02-JUL-17:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.22 | 04-AUG-21:03 | 534.70 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 | 14-SEP-14:00 | 752.60 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2062.77 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3190.70 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4141.89 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.22 | 4141.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 13152.34 | 20-JAN-08:40 | 6035.01 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13897.91 | 24-FEB-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20813.33 | 30-MAR-07:03 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40031.45 | 13-APR-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45907.51 | 30-MAY-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46482.12 | 26-JUN-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47568.68 | 24-JUL-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46434.96 | 28-AUG-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45954.73 | 06-SEP-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43589.16 | 03-OCT-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38743.94 | 03-NOV-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16336.28 | 22-DEC-08:08 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13152.34 | 0.00 | 3963.42 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47568.68 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 672.46 | 17-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.71 |
February | 1202.80 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.99 |
March | 3305.01 | 03-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.60 |
April | 7878.67 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 0.00 |
May | 11596.14 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.72 | 0.00 |
June | 13042.54 | 19-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 | 0.00 |
July | 12170.00 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.25 | 0.00 |
August | 11682.98 | 01-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 | 0.00 |
September | 10423.20 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.45 | 0.00 |
October | 7406.67 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
November | 2912.27 | 04-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.14 |
December | 1447.83 | 17-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 672.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13042.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.25 | 556.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1900.92 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1959.60 |
February | 1739.41 | 09-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2339.59 |
March | 2722.73 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.93 |
April | 2496.87 | 10-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.61 |
May | 5214.29 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.80 | 0.00 |
June | 5463.67 | 19-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.75 | 0.00 |
July | 5962.26 | 10-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.01 | 0.00 |
August | 6064.19 | 14-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.92 | 0.00 |
September | 5546.40 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 | 0.00 |
October | 3517.72 | 04-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.40 |
November | 1649.65 | 04-NOV-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 |
December | 1161.09 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1161.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6064.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.01 | 2339.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1904.12 | 11-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.11 |
February | 2569.79 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.08 |
March | 3070.89 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.66 |
April | 2947.15 | 10-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.07 |
May | 5796.41 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 0.00 |
June | 7131.87 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 | 0.00 |
July | 6785.69 | 07-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.11 | 0.00 |
August | 6123.94 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.68 | 0.00 |
September | 5666.19 | 05-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
October | 4254.81 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 |
November | 2170.36 | 03-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.32 |
December | 2305.69 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1904.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7131.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.99 | 539.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7373.64 | 20-JAN-17:00 | 12070.02 | 14267.94 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7437.70 | 24-FEB-16:40 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10674.37 | 29-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21704.38 | 10-APR-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34418.80 | 30-MAY-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34873.07 | 26-JUN-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37096.54 | 10-JUL-04:03 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37480.68 | 14-AUG-04:03 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35354.32 | 05-SEP-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32500.03 | 06-OCT-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12584.81 | 03-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7535.59 | 21-DEC-16:10 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7373.64 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37480.68 | 12070.02 | 14267.94 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7257.98 | 20-JAN-16:30 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7296.07 | 17-FEB-16:30 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10177.29 | 29-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16358.31 | 10-APR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31725.29 | 30-MAY-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36816.02 | 20-JUN-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39781.28 | 10-JUL-04:03 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37661.82 | 07-AUG-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36754.27 | 05-SEP-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17468.15 | 04-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11186.72 | 03-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7212.62 | 21-DEC-16:10 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7212.62 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39781.28 | 6035.01 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1518.50 | 20-JAN-16:30 | 1272.23 | 1387.26 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.37 |
February | 1561.92 | 24-FEB-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.00 |
March | 2177.68 | 27-MAR-16:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 |
April | 4408.03 | 07-APR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 |
May | 6990.52 | 30-MAY-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 60.26 | 0.00 |
June | 8353.38 | 19-JUN-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 | 0.00 |
July | 10506.53 | 07-JUL-05:02 | 669.60 | 618.69 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 | 0.00 |
August | 11691.14 | 13-AUG-15:12 | 401.76 | 309.03 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 0.00 |
September | 6856.72 | 02-SEP-05:02 | 669.60 | 835.52 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.40 |
October | 4525.98 | 04-OCT-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
November | 2166.17 | 03-NOV-14:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 |
December | 1546.92 | 20-DEC-13:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1518.50 | 401.76 | 309.03 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11691.14 | 1306.65 | 1387.26 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 121.06 | 299.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1825.93 | 19-JAN-10:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.21 |
February | 1904.73 | 22-FEB-10:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.31 |
March | 3576.95 | 29-MAR-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 |
April | 6376.00 | 28-APR-08:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 |
May | 14022.84 | 29-MAY-09:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
June | 12701.89 | 25-JUN-08:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.06 |
July | 14159.83 | 02-JUL-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 |
August | 13000.38 | 13-AUG-09:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 0.00 |
September | 13975.11 | 04-SEP-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
October | 5673.47 | 05-OCT-09:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
November | 2342.04 | 03-NOV-09:50 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.70 |
December | 1889.41 | 20-DEC-09:40 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1825.93 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14159.83 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 221.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6502.09 | 19-JAN-13:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.56 |
February | 6936.15 | 02-FEB-14:00 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.89 |
March | 9483.36 | 01-MAR-13:25 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.63 |
April | 10505.43 | 07-APR-12:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 0.00 |
May | 12136.99 | 29-MAY-12:23 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 | 0.00 |
June | 10965.91 | 19-JUN-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 130.15 | 0.00 |
July | 14055.47 | 09-JUL-14:42 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 | 0.00 |
August | 17728.97 | 13-AUG-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 134.89 | 0.00 |
September | 18008.65 | 04-SEP-12:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 |
October | 17378.88 | 15-OCT-11:13 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.97 |
November | 11206.85 | 02-NOV-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.03 |
December | 6542.93 | 21-DEC-13:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6502.09 | 267.84 | 206.02 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18008.65 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 134.89 | 505.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2281.60 | 19-JAN-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.80 |
February | 2517.52 | 22-FEB-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.20 |
March | 5468.67 | 29-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.31 |
April | 8252.14 | 07-APR-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
May | 12252.38 | 21-MAY-15:12 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.16 |
June | 15295.62 | 18-JUN-16:02 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 |
July | 15583.02 | 02-JUL-16:32 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.65 |
August | 15336.52 | 13-AUG-15:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 | 0.00 |
September | 14182.29 | 10-SEP-16:02 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.19 |
October | 7681.44 | 04-OCT-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
November | 3658.99 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 |
December | 2224.81 | 08-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2224.81 | 211.94 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15583.02 | 805.38 | 586.93 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 61.61 | 249.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1269.24 | 20-JAN-15:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 |
February | 1278.50 | 24-FEB-14:10 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 |
March | 1630.62 | 28-MAR-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 |
April | 2467.65 | 10-APR-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
May | 4831.26 | 30-MAY-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 0.00 |
June | 6308.49 | 26-JUN-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 |
July | 7921.39 | 10-JUL-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
August | 8005.25 | 14-AUG-04:02 | 0.00 | 1002.63 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.46 |
September | 5470.31 | 01-SEP-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 0.00 |
October | 4139.34 | 05-OCT-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
November | 1882.98 | 02-NOV-12:06 | 6361.16 | 4635.78 | 7529.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.84 |
December | 1368.43 | 20-DEC-14:10 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1269.24 | 0.00 | 927.14 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8005.25 | 6361.16 | 4635.78 | 7529.46 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 150.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1544.99 | 27-JAN-10:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 |
February | 1564.13 | 22-FEB-10:10 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.56 |
March | 2250.62 | 29-MAR-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
April | 4287.85 | 28-APR-09:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
May | 11462.34 | 29-MAY-09:31 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
June | 7953.70 | 26-JUN-06:03 | 508.69 | 586.96 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
July | 9926.65 | 09-JUL-10:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
August | 8991.40 | 13-AUG-09:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 | 0.00 |
September | 11700.63 | 10-SEP-09:12 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.49 |
October | 5125.53 | 05-OCT-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 |
November | 2271.23 | 03-NOV-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
December | 1696.48 | 20-DEC-09:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1544.99 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11700.63 | 827.22 | 586.97 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 127.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2210.69 | 07-JAN-14:20 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.86 |
February | 2460.22 | 25-FEB-13:30 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.65 |
March | 4045.64 | 03-MAR-13:35 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1817.54 |
April | 7822.94 | 07-APR-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1995.23 | 0.00 |
May | 11969.56 | 30-MAY-11:10 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5882.09 | 0.00 |
June | 14388.40 | 19-JUN-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 11618.37 | 0.00 |
July | 13519.96 | 07-JUL-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 9367.77 | 0.00 |
August | 14068.82 | 13-AUG-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 79.46 | 0.00 |
September | 15330.09 | 04-SEP-14:12 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 |
October | 14400.63 | 15-OCT-12:53 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.47 |
November | 9449.56 | 02-NOV-12:06 | 6361.16 | 4635.78 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.86 |
December | 4121.20 | 17-DEC-14:20 | 200.88 | 154.51 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2210.69 | 133.92 | 154.51 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15330.09 | 6361.16 | 4635.78 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 11618.37 | 1817.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1830.18 | 20-JAN-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.92 |
February | 1930.04 | 22-FEB-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.89 |
March | 3502.06 | 27-MAR-16:50 | 254.33 | 326.07 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 |
April | 8182.84 | 09-APR-16:42 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 |
May | 7006.69 | 30-MAY-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
June | 7901.27 | 19-JUN-04:02 | 0.00 | 634.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 |
July | 11465.13 | 04-JUL-16:12 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.03 |
August | 11820.81 | 13-AUG-15:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 | 0.00 |
September | 12433.89 | 10-SEP-17:12 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.05 |
October | 6724.44 | 04-OCT-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
November | 3387.07 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
December | 1838.77 | 08-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1830.18 | 0.00 | 163.02 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12433.89 | 805.38 | 634.70 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 | 113.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1459.13 | 20-JAN-15:10 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.37 |
February | 1488.88 | 24-FEB-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.35 |
March | 1965.58 | 28-MAR-14:10 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.69 |
April | 3943.27 | 07-APR-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
May | 6324.59 | 30-MAY-13:50 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48.48 | 0.00 |
June | 8987.11 | 26-JUN-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
July | 9577.77 | 17-JUL-04:02 | 0.00 | 1002.63 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.26 |
August | 9161.80 | 22-AUG-04:02 | 0.00 | 1002.63 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 | 0.00 |
September | 5983.96 | 01-SEP-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 0.00 |
October | 4403.55 | 05-OCT-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
November | 2220.05 | 02-NOV-13:10 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.29 |
December | 1505.51 | 20-DEC-13:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1459.13 | 0.00 | 927.14 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9577.77 | 1306.65 | 1002.63 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 258.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1919.99 | 19-JAN-10:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.67 |
February | 2047.45 | 22-FEB-09:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.54 |
March | 4239.23 | 29-MAR-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 |
April | 6733.97 | 28-APR-08:40 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 |
May | 13490.80 | 29-MAY-08:42 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 |
June | 14454.83 | 25-JUN-08:42 | 254.35 | 195.64 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.99 |
July | 15059.44 | 02-JUL-09:01 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.38 |
August | 13619.13 | 27-AUG-09:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.86 |
September | 14732.45 | 04-SEP-09:01 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.04 |
October | 6015.59 | 05-OCT-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 |
November | 2614.36 | 02-NOV-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.60 |
December | 2062.98 | 20-DEC-09:35 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1919.99 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | |
Maximum of Months | 15059.44 | 1610.86 | 1173.93 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6757.91 | 19-JAN-13:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 |
February | 7311.78 | 02-FEB-13:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.63 |
March | 9194.19 | 03-MAR-13:25 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.74 |
April | 9863.48 | 07-APR-12:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 |
May | 15702.61 | 29-MAY-12:43 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 21.10 | 0.00 |
June | 11378.96 | 25-JUN-14:02 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
July | 14300.67 | 02-JUL-13:02 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
August | 16375.39 | 27-AUG-12:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
September | 17720.95 | 04-SEP-13:01 | 468.72 | 360.53 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.29 |
October | 16392.34 | 22-OCT-12:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.18 |
November | 11450.38 | 02-NOV-12:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 |
December | 7498.90 | 21-DEC-13:13 | 5088.93 | 3708.63 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6757.91 | 267.84 | 206.02 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17720.95 | 5088.93 | 3708.63 | 6023.53 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 255.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2231.31 | 20-JAN-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 |
February | 2437.44 | 24-FEB-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.19 |
March | 5491.86 | 29-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.38 |
April | 13793.44 | 09-APR-16:12 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.47 |
May | 9571.87 | 27-MAY-17:42 | 169.55 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.24 |
June | 15390.02 | 18-JUN-15:51 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.25 |
July | 15296.69 | 02-JUL-15:41 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 |
August | 13991.90 | 13-AUG-15:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 | 0.00 |
September | 14984.81 | 10-SEP-15:51 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.56 |
October | 7451.44 | 04-OCT-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
November | 3837.53 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
December | 2175.38 | 08-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2175.38 | 169.55 | 130.42 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15390.02 | 805.38 | 586.93 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 54.59 | 205.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.170949E+12 | 272070.38 | 02-JAN-07:10 | 0.433368E+11 | 96729.18 | 02-JAN-08:30 |
February | 0.145341E+12 | 217009.04 | 06-FEB-07:10 | 0.418573E+11 | 99639.22 | 06-FEB-07:00 |
March | 0.135513E+12 | 151036.87 | 13-MAR-06:10 | 0.230402E+11 | 59839.25 | 23-MAR-06:10 |
April | 0.118021E+12 | 123934.91 | 07-APR-15:39 | 0.106655E+11 | 33955.68 | 03-APR-06:19 |
May | 0.129454E+12 | 169216.42 | 30-MAY-13:00 | 0.914235E+10 | 9219.57 | 02-MAY-11:20 |
June | 0.161930E+12 | 183136.11 | 19-JUN-12:09 | 0.860092E+10 | 9074.42 | 02-JUN-11:09 |
July | 0.181152E+12 | 175196.70 | 07-JUL-14:30 | 0.820882E+10 | 8955.55 | 03-JUL-11:50 |
August | 0.192047E+12 | 179254.30 | 16-AUG-15:09 | 0.860016E+10 | 8919.01 | 31-AUG-11:00 |
September | 0.144964E+12 | 156836.71 | 07-SEP-15:20 | 0.813752E+10 | 8991.81 | 29-SEP-11:30 |
October | 0.130326E+12 | 133055.96 | 04-OCT-15:39 | 0.893673E+10 | 22789.98 | 28-OCT-06:19 |
November | 0.129009E+12 | 158524.23 | 24-NOV-07:10 | 0.171044E+11 | 62224.34 | 24-NOV-07:30 |
December | 0.146631E+12 | 166733.51 | 11-DEC-07:10 | 0.301093E+11 | 61447.81 | 22-DEC-07:19 |
Annual Sum or Average | 0.178534E+13 | 0.217740E+12 | ||||
Minimum of Months | 0.118021E+12 | 123934.91 | 0.813752E+10 | 8919.01 | ||
Maximum of Months | 0.192047E+12 | 272070.38 | 0.433368E+11 | 99639.22 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.308594E+11 | 0.118587E+11 | 0.641572E+11 | 0.159116E+10 | 0.566095E+10 | 1312252.65 | 0.568206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276021E+11 | 0.982230E+10 | 0.580684E+11 | 0.143943E+10 | 0.496416E+10 | 1186778.30 | 0.434433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324436E+11 | 0.965368E+10 | 0.666107E+11 | 0.166691E+10 | 0.571190E+10 | 1343621.24 | 0.190211E+11 | 0.403480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287740E+11 | 0.811962E+10 | 0.619407E+11 | 0.153133E+10 | 0.630554E+10 | 1267813.82 | 0.768998E+10 | 0.365814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309190E+11 | 0.741704E+10 | 0.653840E+11 | 0.162824E+10 | 0.924565E+10 | 1327936.95 | 0.108508E+10 | 0.137736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306821E+11 | 0.668443E+10 | 0.641577E+11 | 0.160316E+10 | 0.143247E+11 | 1296568.36 | 35988735.35 | 0.444402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287636E+11 | 0.708853E+10 | 0.631525E+11 | 0.155596E+10 | 0.175001E+11 | 1299182.41 | 0.00 | 0.630901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.321219E+11 | 0.790426E+10 | 0.666107E+11 | 0.166667E+10 | 0.195353E+11 | 1343621.24 | 0.00 | 0.642064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288653E+11 | 0.880552E+10 | 0.619118E+11 | 0.153080E+10 | 0.117886E+11 | 1267813.82 | 0.135943E+09 | 0.319251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302028E+11 | 0.103701E+11 | 0.641717E+11 | 0.159047E+10 | 0.898959E+10 | 1312252.65 | 0.135781E+10 | 0.136426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303711E+11 | 0.111528E+11 | 0.627379E+11 | 0.156206E+10 | 0.536807E+10 | 1278270.02 | 0.174416E+11 | 0.374569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299648E+11 | 0.121280E+11 | 0.631380E+11 | 0.155716E+10 | 0.512049E+10 | 1299182.41 | 0.347207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361570E+12 | 0.111005E+12 | 0.762041E+12 | 0.189233E+11 | 0.114515E+12 | 15535293.87 | 0.181752E+12 | 0.235514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276021E+11 | 0.668443E+10 | 0.580684E+11 | 0.143943E+10 | 0.496416E+10 | 1186778.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.324436E+11 | 0.121280E+11 | 0.666107E+11 | 0.166691E+10 | 0.195353E+11 | 1343621.24 | 0.568206E+11 | 0.642064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.336006E+11 | 0.00 | 0.973617E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.329935E+11 | 0.00 | 0.886389E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.129848E+11 | 0.00 | 0.100554E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.163629E+10 | 0.00 | 0.902925E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 3310951.83 | 0.00 | 0.913904E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.860092E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.820882E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.860016E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.813752E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.228645E+09 | 0.00 | 0.870809E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.821784E+10 | 0.00 | 0.888660E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207928E+11 | 0.00 | 0.931648E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.110458E+12 | 0.00 | 0.107282E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.813752E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.336006E+11 | 0.00 | 0.100554E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36137.71 | 02-JAN-16:40 | 8467.87 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 1358.60 | 02-JAN-16:49 | 7472.61 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 221858.82 | 02-JAN-07:10 |
February | 34962.52 | 15-FEB-16:00 | 8467.87 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 1355.42 | 15-FEB-16:00 | 5791.51 | 06-FEB-06:10 | 0.73 | 01-FEB-07:10 | 177998.70 | 06-FEB-07:10 |
March | 32191.22 | 02-MAR-16:00 | 8467.87 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 1351.76 | 16-MAR-07:19 | 6737.47 | 29-MAR-15:30 | 0.73 | 07-MAR-08:09 | 107374.18 | 20-MAR-06:10 |
April | 30486.53 | 03-APR-07:10 | 8467.87 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 1348.89 | 03-APR-07:19 | 14634.30 | 10-APR-15:20 | 0.73 | 03-APR-06:10 | 77972.46 | 03-APR-06:10 |
May | 30486.53 | 01-MAY-07:10 | 8467.87 | 01-MAY-18:49 | 47562.27 | 01-MAY-07:10 | 1348.89 | 01-MAY-07:19 | 27715.17 | 30-MAY-14:30 | 0.73 | 01-MAY-05:10 | 29107.89 | 01-MAY-06:10 |
June | 30486.53 | 01-JUN-07:10 | 8467.87 | 01-JUN-19:19 | 47562.27 | 01-JUN-07:10 | 1348.89 | 01-JUN-07:30 | 27517.26 | 19-JUN-15:39 | 0.73 | 01-JUN-05:10 | 5690.35 | 02-JUN-06:19 |
July | 30486.53 | 03-JUL-07:10 | 8467.87 | 01-JUL-19:30 | 47562.27 | 03-JUL-07:10 | 1348.89 | 03-JUL-07:19 | 28374.89 | 10-JUL-15:00 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 30486.53 | 01-AUG-07:10 | 8467.87 | 01-AUG-19:10 | 47562.27 | 01-AUG-07:10 | 1348.89 | 01-AUG-07:19 | 28214.01 | 14-AUG-15:09 | 0.73 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 31423.93 | 27-SEP-07:10 | 8467.87 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 1350.85 | 27-SEP-07:19 | 23691.86 | 05-SEP-15:20 | 0.73 | 01-SEP-05:10 | 6733.29 | 20-SEP-06:10 |
October | 33416.76 | 31-OCT-15:00 | 8467.87 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 1354.31 | 06-OCT-07:19 | 18106.69 | 04-OCT-15:50 | 0.73 | 27-OCT-16:10 | 32244.21 | 31-OCT-06:10 |
November | 36137.71 | 06-NOV-16:49 | 8467.87 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 1358.60 | 06-NOV-16:00 | 7960.46 | 02-NOV-14:30 | 0.73 | 15-NOV-08:09 | 121299.72 | 24-NOV-07:10 |
December | 36137.71 | 01-DEC-16:30 | 8467.87 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 1358.60 | 01-DEC-16:40 | 4802.34 | 21-DEC-13:09 | 0.73 | 01-DEC-08:09 | 119675.74 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30486.53 | 8467.87 | 47562.27 | 1348.89 | 4802.34 | 0.73 | 0.00 | |||||||
Maximum of Months | 36137.71 | 8467.87 | 47562.27 | 1358.60 | 28374.89 | 0.73 | 221858.82 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18305.45 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35198.93 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68799.48 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85255.29 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75362.92 | 07-JUL-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79915.66 | 16-AUG-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62571.44 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 44195.18 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8228.69 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85255.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 272070.38 | 02-JAN-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7472.61 | 0.73 | 221858.82 | 0.00 | 0.00 |
February | 217009.04 | 06-FEB-07:10 | 11146.68 | 21853.28 | 0.00 | 371.32 | 5638.33 | 0.73 | 177998.70 | 0.00 | 0.00 |
March | 151036.87 | 13-MAR-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4168.42 | 0.73 | 104129.50 | 0.00 | 0.00 |
April | 123934.91 | 07-APR-15:39 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 13674.24 | 0.73 | 0.00 | 34656.69 | 0.00 |
May | 169216.42 | 30-MAY-13:00 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 26297.72 | 0.73 | 0.00 | 68799.48 | 0.00 |
June | 183136.11 | 19-JUN-12:09 | 30486.53 | 44099.74 | 0.00 | 1346.94 | 22710.20 | 0.73 | 0.00 | 84491.97 | 0.00 |
July | 175196.70 | 07-JUL-14:30 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 26157.76 | 0.73 | 0.00 | 74919.73 | 0.00 |
August | 179254.30 | 16-AUG-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 25867.08 | 0.73 | 0.00 | 77783.23 | 0.00 |
September | 156836.71 | 07-SEP-15:20 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 22936.10 | 0.73 | 0.00 | 58296.62 | 0.00 |
October | 133055.96 | 04-OCT-15:39 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 17747.71 | 0.73 | 0.00 | 39704.27 | 0.00 |
November | 158524.23 | 24-NOV-07:10 | 10604.37 | 21853.28 | 0.00 | 371.10 | 4395.04 | 0.73 | 121299.72 | 0.00 | 0.00 |
December | 166733.51 | 11-DEC-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4318.82 | 0.73 | 119675.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 123934.91 | 10604.37 | 21853.28 | 0.00 | 371.10 | 4168.42 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 272070.38 | 30486.53 | 44099.74 | 8467.87 | 1346.94 | 26297.72 | 0.73 | 221858.82 | 84491.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 88571.61 | 02-JAN-08:20 | 0.00 | 9467.78 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 91491.26 | 06-FEB-07:00 | 0.00 | 9472.99 | 07-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 51883.70 | 23-MAR-06:19 | 0.00 | 9443.76 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 25802.58 | 03-APR-06:19 | 0.00 | 9343.27 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 2411.83 | 01-MAY-06:10 | 0.00 | 9219.57 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9074.42 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8955.55 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8919.01 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8991.81 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 14881.14 | 28-OCT-06:19 | 0.00 | 9128.38 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 54124.59 | 24-NOV-07:30 | 0.00 | 9272.25 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 53288.44 | 22-DEC-07:19 | 0.00 | 9397.36 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8919.01 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 91491.26 | 0.00 | 9472.99 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.08 | 1.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.08 | 1.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.08 | 1.83 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.45 | 1.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
February | 0.83 | 18.35 | 0.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 18.41 | 1.50 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 18.45 | 1.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.67 | 15.67 | 8.17 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
February | 20.00 | 15.92 | 8.00 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
March | 0.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.17 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.51 | 1.17 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 16.67 | 0.17 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
December | 4.83 | 15.59 | 1.50 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
Annual Sum or Average | 47.50 | 15.81 | 17.83 | 16.06 | 2.67 | 16.51 | 2.33 | 16.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.67 | 17.01 | 8.17 | 17.01 | 1.33 | 27.51 | 1.17 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.33 | 14.91 | 3.33 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
February | 11.83 | 15.00 | 1.17 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
March | 0.83 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.86 | 3.67 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.00 | 1.50 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.02 | 6.17 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.90 | 4.00 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.13 | 2.83 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
December | 5.33 | 15.67 | 0.67 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
Annual Sum or Average | 35.33 | 15.15 | 5.17 | 15.11 | 18.17 | 19.10 | 18.17 | 21.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.33 | 17.03 | 3.33 | 17.03 | 6.17 | 28.13 | 6.17 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 15.10 | 2.17 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 9.17 | 15.38 | 1.50 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
March | 0.33 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.69 | 1.67 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.82 | 5.17 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.10 | 3.83 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.25 | 5.00 | 28.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.82 | 2.00 | 27.82 |
November | 0.83 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 3.00 | 15.54 | 0.50 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
Annual Sum or Average | 26.17 | 15.33 | 4.17 | 15.40 | 18.50 | 20.16 | 18.17 | 22.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.83 | 17.00 | 2.17 | 17.00 | 5.17 | 28.25 | 5.17 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 14.85 | 4.67 | 14.83 | 0.00 | 14.83 | 0.00 | 14.83 |
February | 13.00 | 14.93 | 3.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
March | 0.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.75 | 0.50 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 2.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.19 | 2.67 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.19 | 4.17 | 28.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.35 | 2.00 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.18 | 2.33 | 28.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
December | 5.50 | 15.59 | 1.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
Annual Sum or Average | 36.33 | 15.06 | 8.83 | 15.01 | 17.83 | 18.72 | 13.67 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 17.00 | 4.67 | 17.00 | 6.33 | 28.35 | 4.17 | 28.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.83 | 16.39 | 6.67 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 2.83 | 18.67 | 2.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.67 | 16.83 | 8.67 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.83 | 18.67 | 6.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 15.01 | 1.00 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
February | 0.83 | 17.20 | 0.17 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.74 | 1.00 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.50 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.74 | 3.17 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.71 | 2.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.67 | 15.28 | 1.17 | 15.40 | 9.33 | 22.08 | 9.33 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.83 | 17.20 | 1.00 | 17.56 | 3.17 | 27.74 | 3.17 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.67 | 16.88 | 73.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
February | 67.50 | 16.78 | 67.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
March | 54.17 | 17.99 | 54.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
April | 24.17 | 18.96 | 24.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
May | 2.83 | 19.84 | 2.83 | 19.84 | 0.67 | 20.35 | 0.67 | 20.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.56 | 2.67 | 25.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 25.57 | 7.33 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 25.51 | 18.50 | 25.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.34 | 10.00 | 26.34 |
October | 4.00 | 19.58 | 4.00 | 19.58 | 2.67 | 21.60 | 2.67 | 22.81 |
November | 39.00 | 18.60 | 39.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
December | 60.33 | 17.81 | 60.33 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
Annual Sum or Average | 329.67 | 17.63 | 324.50 | 17.64 | 41.83 | 18.14 | 41.83 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 | 16.78 |
Maximum of Months | 77.67 | 19.84 | 73.00 | 19.84 | 18.50 | 26.34 | 18.50 | 26.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 14.94 | 1.83 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
February | 0.83 | 17.15 | 0.17 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.17 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.68 | 2.83 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.79 | 1.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.80 | 2.00 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.50 | 15.18 | 2.00 | 15.26 | 10.50 | 21.81 | 7.67 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 17.15 | 1.83 | 17.51 | 4.00 | 27.80 | 2.83 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 15.89 | 5.50 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
February | 4.67 | 16.64 | 1.50 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 17.00 | 16.06 | 7.00 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.67 | 16.64 | 5.50 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 15.04 | 2.17 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
February | 2.50 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.00 | 3.00 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.92 | 1.67 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.99 | 5.00 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.88 | 3.17 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.14 | 3.00 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
Annual Sum or Average | 11.17 | 15.06 | 2.17 | 15.07 | 16.33 | 22.17 | 16.33 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 15.15 | 2.17 | 15.15 | 5.00 | 28.14 | 5.00 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.18 | 1.17 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
February | 2.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.64 | 1.00 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 3.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 3.83 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.16 | 5.00 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.83 | 2.33 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 8.50 | 15.20 | 1.17 | 15.30 | 16.33 | 23.21 | 16.17 | 25.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 15.29 | 1.17 | 15.30 | 5.00 | 28.16 | 5.00 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 15.03 | 3.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
February | 2.67 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 | 0.00 | 15.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.83 | 0.33 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.67 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 2.33 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.10 | 3.83 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.14 | 1.67 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.16 | 2.17 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
Annual Sum or Average | 12.17 | 15.05 | 3.00 | 15.04 | 15.50 | 21.60 | 12.00 | 23.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 15.10 | 3.00 | 15.10 | 5.17 | 28.16 | 3.83 | 28.20 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 22.63 | 45.83 | 22.40 | 45.83 | 22.20 |
February | 454.00 | 23.21 | 3.33 | 23.20 | 3.33 | 23.18 |
March | 445.33 | 23.68 | 2.50 | 23.69 | 0.00 | 23.69 |
April | 214.33 | 23.70 | 57.17 | 23.98 | 0.00 | 23.98 |
May | 28.33 | 23.92 | 239.67 | 24.50 | 0.00 | 24.50 |
June | 0.00 | 0.00 | 438.00 | 24.41 | 0.00 | 24.41 |
July | 0.00 | 0.00 | 497.00 | 24.43 | 0.00 | 24.43 |
August | 0.50 | 27.19 | 488.67 | 24.43 | 0.50 | 24.43 |
September | 3.50 | 23.92 | 395.67 | 24.47 | 0.00 | 24.47 |
October | 55.83 | 23.99 | 281.67 | 24.38 | 0.00 | 24.38 |
November | 284.00 | 23.60 | 66.67 | 23.88 | 0.00 | 23.88 |
December | 497.00 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 2482.17 | 23.34 | 2516.17 | 23.87 | 49.67 | 23.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.40 | 0.00 | 22.20 |
Maximum of Months | 499.33 | 27.19 | 497.00 | 24.50 | 45.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.26 | 166.67 | 20.99 | 166.67 | 20.82 |
February | 454.00 | 21.67 | 114.67 | 21.50 | 114.67 | 21.39 |
March | 511.67 | 22.63 | 4.67 | 22.62 | 4.67 | 22.60 |
April | 370.67 | 23.06 | 19.50 | 23.13 | 0.17 | 23.13 |
May | 156.50 | 23.52 | 142.50 | 23.86 | 0.00 | 23.86 |
June | 2.33 | 23.83 | 419.00 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 497.00 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 468.00 | 24.35 | 0.00 | 24.35 |
September | 38.00 | 23.66 | 321.17 | 24.27 | 0.00 | 24.27 |
October | 192.17 | 23.58 | 190.50 | 23.90 | 0.00 | 23.90 |
November | 453.67 | 22.62 | 32.17 | 22.52 | 28.50 | 22.42 |
December | 497.00 | 21.84 | 60.67 | 21.71 | 60.67 | 21.60 |
Annual Sum or Average | 3178.00 | 22.32 | 2436.50 | 22.93 | 375.33 | 22.78 |
Minimum of Months | 0.00 | 0.00 | 4.67 | 20.99 | 0.00 | 20.82 |
Maximum of Months | 511.67 | 23.83 | 497.00 | 24.35 | 166.67 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.65 | 292.50 | 20.43 | 292.50 | 20.32 |
February | 454.00 | 20.94 | 271.50 | 20.75 | 271.50 | 20.67 |
March | 513.17 | 21.89 | 74.17 | 21.72 | 74.17 | 21.59 |
April | 404.83 | 22.51 | 32.83 | 22.49 | 18.00 | 22.40 |
May | 221.50 | 23.23 | 113.67 | 23.56 | 0.00 | 23.56 |
June | 16.33 | 23.55 | 396.83 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 493.67 | 24.34 | 0.00 | 24.34 |
August | 1.67 | 23.56 | 452.33 | 24.34 | 0.00 | 24.34 |
September | 87.17 | 23.24 | 263.83 | 24.00 | 0.00 | 24.00 |
October | 297.17 | 22.99 | 129.33 | 23.30 | 4.00 | 23.28 |
November | 477.33 | 21.78 | 103.50 | 21.52 | 103.50 | 21.33 |
December | 497.00 | 20.99 | 260.67 | 20.77 | 260.67 | 20.66 |
Annual Sum or Average | 3472.17 | 21.74 | 2884.83 | 22.25 | 1024.33 | 21.98 |
Minimum of Months | 0.00 | 0.00 | 32.83 | 20.43 | 0.00 | 20.32 |
Maximum of Months | 513.17 | 23.56 | 493.67 | 24.34 | 292.50 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 439.50 | 19.86 | 439.50 | 19.83 |
February | 454.00 | 20.08 | 420.67 | 20.04 | 420.67 | 20.03 |
March | 514.00 | 20.80 | 265.67 | 20.59 | 265.67 | 20.49 |
April | 424.00 | 21.54 | 113.67 | 21.40 | 92.50 | 21.22 |
May | 280.67 | 22.64 | 108.33 | 23.07 | 2.00 | 23.05 |
June | 52.83 | 23.79 | 387.17 | 24.20 | 16.83 | 24.23 |
July | 59.50 | 25.76 | 492.67 | 24.57 | 59.50 | 24.68 |
August | 51.00 | 24.97 | 446.83 | 24.41 | 32.33 | 24.50 |
September | 175.00 | 22.86 | 233.33 | 23.61 | 10.00 | 23.63 |
October | 390.17 | 22.03 | 119.50 | 22.14 | 47.17 | 21.97 |
November | 489.00 | 20.69 | 256.67 | 20.45 | 256.67 | 20.33 |
December | 497.00 | 20.09 | 463.33 | 20.06 | 463.33 | 20.05 |
Annual Sum or Average | 3889.17 | 21.10 | 3747.33 | 21.55 | 2106.17 | 21.28 |
Minimum of Months | 51.00 | 19.93 | 108.33 | 19.86 | 2.00 | 19.83 |
Maximum of Months | 514.00 | 25.76 | 492.67 | 24.57 | 463.33 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 417.83 | 19.86 | 417.83 | 19.82 |
February | 454.00 | 20.21 | 374.83 | 20.13 | 374.83 | 20.09 |
March | 504.17 | 20.95 | 196.33 | 20.68 | 196.33 | 20.52 |
April | 374.50 | 21.50 | 141.50 | 21.73 | 71.83 | 21.56 |
May | 265.17 | 22.40 | 186.17 | 23.22 | 13.67 | 23.29 |
June | 85.67 | 23.52 | 377.83 | 24.13 | 21.17 | 24.20 |
July | 75.17 | 25.79 | 462.33 | 24.62 | 65.67 | 24.79 |
August | 67.83 | 24.92 | 449.17 | 24.41 | 39.67 | 24.55 |
September | 187.17 | 22.81 | 258.67 | 23.69 | 22.33 | 23.79 |
October | 350.83 | 22.00 | 134.33 | 22.35 | 28.50 | 22.22 |
November | 489.00 | 20.79 | 209.17 | 20.52 | 209.17 | 20.38 |
December | 497.00 | 20.18 | 418.17 | 20.11 | 418.17 | 20.08 |
Annual Sum or Average | 3852.50 | 21.18 | 3626.33 | 21.70 | 1879.17 | 21.46 |
Minimum of Months | 67.83 | 19.96 | 134.33 | 19.86 | 13.67 | 19.82 |
Maximum of Months | 504.17 | 25.79 | 462.33 | 24.62 | 418.17 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.83 | 20.38 | 329.67 | 20.08 | 329.67 | 19.95 |
February | 422.50 | 20.69 | 293.50 | 20.42 | 293.50 | 20.31 |
March | 429.50 | 21.04 | 206.50 | 20.93 | 176.50 | 20.75 |
April | 362.50 | 21.49 | 143.17 | 21.73 | 71.83 | 21.54 |
May | 286.50 | 22.42 | 153.83 | 23.08 | 8.00 | 23.11 |
June | 91.33 | 23.43 | 363.17 | 24.09 | 20.67 | 24.14 |
July | 72.00 | 25.75 | 465.00 | 24.59 | 66.33 | 24.74 |
August | 69.17 | 25.01 | 447.67 | 24.47 | 42.67 | 24.61 |
September | 158.33 | 23.21 | 291.17 | 23.97 | 27.83 | 24.11 |
October | 240.00 | 22.22 | 229.83 | 23.08 | 31.17 | 23.01 |
November | 424.33 | 21.08 | 186.67 | 20.89 | 161.67 | 20.69 |
December | 459.50 | 20.61 | 318.67 | 20.41 | 312.00 | 20.28 |
Annual Sum or Average | 3503.50 | 21.43 | 3428.83 | 22.01 | 1541.83 | 21.76 |
Minimum of Months | 69.17 | 20.38 | 143.17 | 20.08 | 8.00 | 19.95 |
Maximum of Months | 487.83 | 25.75 | 465.00 | 24.59 | 329.67 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 410.50 | 19.91 | 410.50 | 19.87 |
February | 454.00 | 20.27 | 372.67 | 20.15 | 372.67 | 20.10 |
March | 482.50 | 20.88 | 227.67 | 20.70 | 219.50 | 20.57 |
April | 399.00 | 21.32 | 137.00 | 21.43 | 86.67 | 21.27 |
May | 314.33 | 22.23 | 144.17 | 22.86 | 10.50 | 22.91 |
June | 113.50 | 23.33 | 350.00 | 24.04 | 24.50 | 24.13 |
July | 79.17 | 25.02 | 440.00 | 24.47 | 55.00 | 24.62 |
August | 76.50 | 24.21 | 426.67 | 24.32 | 33.17 | 24.44 |
September | 228.83 | 22.58 | 206.50 | 23.37 | 17.83 | 23.47 |
October | 356.83 | 21.72 | 130.83 | 22.03 | 40.33 | 21.89 |
November | 483.00 | 20.65 | 241.00 | 20.43 | 240.00 | 20.31 |
December | 497.00 | 20.21 | 421.00 | 20.12 | 421.00 | 20.09 |
Annual Sum or Average | 3986.67 | 21.13 | 3508.00 | 21.58 | 1931.67 | 21.34 |
Minimum of Months | 76.50 | 20.02 | 130.83 | 19.91 | 10.50 | 19.87 |
Maximum of Months | 502.00 | 25.02 | 440.00 | 24.47 | 421.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 417.17 | 20.18 | 417.17 | 20.15 |
February | 454.00 | 20.39 | 413.67 | 20.36 | 413.67 | 20.35 |
March | 514.00 | 20.97 | 245.17 | 20.82 | 245.17 | 20.75 |
April | 466.00 | 21.85 | 58.67 | 21.71 | 56.33 | 21.58 |
May | 343.33 | 22.92 | 63.83 | 23.12 | 0.00 | 23.12 |
June | 37.83 | 24.07 | 374.67 | 24.21 | 12.67 | 24.24 |
July | 36.17 | 25.66 | 497.00 | 24.47 | 36.17 | 24.54 |
August | 22.33 | 25.83 | 466.67 | 24.40 | 21.00 | 24.47 |
September | 93.83 | 23.48 | 293.50 | 24.06 | 5.83 | 24.08 |
October | 286.33 | 22.91 | 128.00 | 23.25 | 0.00 | 23.25 |
November | 488.00 | 21.60 | 129.33 | 21.35 | 129.33 | 21.18 |
December | 497.00 | 20.60 | 394.17 | 20.53 | 394.17 | 20.51 |
Annual Sum or Average | 3740.83 | 21.44 | 3481.83 | 21.91 | 1731.50 | 21.65 |
Minimum of Months | 22.33 | 20.25 | 58.67 | 20.18 | 0.00 | 20.15 |
Maximum of Months | 514.00 | 25.83 | 497.00 | 24.47 | 417.17 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 394.50 | 20.21 | 394.50 | 20.18 |
February | 454.00 | 20.59 | 348.00 | 20.51 | 348.00 | 20.48 |
March | 512.00 | 21.21 | 141.83 | 21.02 | 141.83 | 20.90 |
April | 386.17 | 21.84 | 65.50 | 21.95 | 30.50 | 21.85 |
May | 269.67 | 22.51 | 140.50 | 23.24 | 3.17 | 23.27 |
June | 54.00 | 23.59 | 385.67 | 24.20 | 11.50 | 24.24 |
July | 45.00 | 26.31 | 486.83 | 24.59 | 45.00 | 24.72 |
August | 28.67 | 26.36 | 487.00 | 24.50 | 27.33 | 24.60 |
September | 97.17 | 23.46 | 332.33 | 24.19 | 15.33 | 24.27 |
October | 226.67 | 22.84 | 166.00 | 23.39 | 0.33 | 23.40 |
November | 478.67 | 21.61 | 103.33 | 21.40 | 103.33 | 21.25 |
December | 497.00 | 20.73 | 302.67 | 20.61 | 302.67 | 20.56 |
Annual Sum or Average | 3551.00 | 21.47 | 3354.17 | 22.10 | 1423.50 | 21.87 |
Minimum of Months | 28.67 | 20.31 | 65.50 | 20.21 | 0.33 | 20.18 |
Maximum of Months | 512.00 | 26.36 | 487.00 | 24.59 | 394.50 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.17 | 19.96 | 337.67 | 19.71 | 337.67 | 19.60 |
February | 445.67 | 20.30 | 289.00 | 20.04 | 286.83 | 19.92 |
March | 492.50 | 20.89 | 152.33 | 20.60 | 150.00 | 20.42 |
April | 412.83 | 21.42 | 89.67 | 21.47 | 53.67 | 21.30 |
May | 369.33 | 22.19 | 68.83 | 22.54 | 8.00 | 22.52 |
June | 158.83 | 23.40 | 348.17 | 23.93 | 90.00 | 23.92 |
July | 139.17 | 24.53 | 487.00 | 24.44 | 137.17 | 24.46 |
August | 86.67 | 24.83 | 484.50 | 24.52 | 77.83 | 24.59 |
September | 127.17 | 23.68 | 365.67 | 24.27 | 59.00 | 24.35 |
October | 156.33 | 22.72 | 284.50 | 23.83 | 16.17 | 23.86 |
November | 424.50 | 21.30 | 109.00 | 21.18 | 84.33 | 20.97 |
December | 480.83 | 20.63 | 267.00 | 20.45 | 256.67 | 20.31 |
Annual Sum or Average | 3795.00 | 21.39 | 3283.33 | 22.00 | 1557.33 | 21.79 |
Minimum of Months | 86.67 | 19.96 | 68.83 | 19.71 | 8.00 | 19.60 |
Maximum of Months | 501.17 | 24.83 | 487.00 | 24.52 | 337.67 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 391.00 | 20.24 | 391.00 | 20.20 |
February | 454.00 | 20.60 | 359.50 | 20.50 | 359.50 | 20.46 |
March | 502.33 | 21.22 | 166.50 | 21.07 | 163.17 | 20.97 |
April | 413.17 | 21.72 | 73.00 | 21.80 | 38.83 | 21.69 |
May | 315.33 | 22.49 | 113.67 | 23.01 | 0.00 | 23.01 |
June | 58.67 | 23.82 | 391.83 | 24.25 | 16.33 | 24.31 |
July | 45.83 | 26.07 | 475.33 | 24.56 | 43.33 | 24.69 |
August | 30.83 | 25.97 | 482.33 | 24.49 | 26.00 | 24.58 |
September | 114.17 | 23.27 | 303.67 | 24.04 | 12.67 | 24.11 |
October | 237.00 | 22.71 | 175.00 | 23.32 | 0.00 | 23.32 |
November | 478.50 | 21.40 | 123.33 | 21.20 | 123.33 | 21.07 |
December | 497.00 | 20.72 | 341.17 | 20.62 | 341.17 | 20.58 |
Annual Sum or Average | 3648.83 | 21.45 | 3396.33 | 22.04 | 1515.33 | 21.81 |
Minimum of Months | 30.83 | 20.35 | 73.00 | 20.24 | 0.00 | 20.20 |
Maximum of Months | 502.33 | 26.07 | 482.33 | 24.56 | 391.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 389.17 | 20.05 | 389.17 | 20.01 |
February | 454.00 | 20.37 | 373.83 | 20.29 | 373.83 | 20.26 |
March | 513.50 | 21.20 | 167.17 | 20.99 | 167.17 | 20.87 |
April | 415.17 | 22.04 | 60.67 | 22.00 | 38.83 | 21.87 |
May | 227.00 | 23.08 | 126.50 | 23.49 | 0.00 | 23.49 |
June | 26.00 | 24.55 | 423.50 | 24.29 | 14.50 | 24.32 |
July | 48.33 | 25.76 | 497.00 | 24.56 | 48.33 | 24.66 |
August | 30.00 | 25.82 | 470.17 | 24.45 | 27.67 | 24.54 |
September | 117.00 | 23.29 | 282.00 | 23.96 | 8.17 | 23.98 |
October | 316.17 | 22.60 | 117.00 | 22.93 | 8.50 | 22.89 |
November | 489.00 | 21.28 | 154.17 | 21.00 | 154.17 | 20.84 |
December | 497.00 | 20.43 | 398.50 | 20.36 | 398.50 | 20.33 |
Annual Sum or Average | 3635.17 | 21.39 | 3459.67 | 21.92 | 1628.83 | 21.65 |
Minimum of Months | 26.00 | 20.17 | 60.67 | 20.05 | 0.00 | 20.01 |
Maximum of Months | 513.50 | 25.82 | 497.00 | 24.56 | 398.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.06 | 335.00 | 19.93 | 335.00 | 19.89 |
February | 385.00 | 20.45 | 282.33 | 20.32 | 282.33 | 20.27 |
March | 422.33 | 21.14 | 123.83 | 20.93 | 122.83 | 20.79 |
April | 319.33 | 21.75 | 76.17 | 22.05 | 23.83 | 21.94 |
May | 230.17 | 22.72 | 141.50 | 23.44 | 9.67 | 23.53 |
June | 62.33 | 23.72 | 311.33 | 24.25 | 15.67 | 24.32 |
July | 56.17 | 26.18 | 395.83 | 24.70 | 54.17 | 24.87 |
August | 51.00 | 25.39 | 379.67 | 24.53 | 35.50 | 24.67 |
September | 150.33 | 23.12 | 221.83 | 23.92 | 20.00 | 24.04 |
October | 282.17 | 22.31 | 98.17 | 22.73 | 8.67 | 22.69 |
November | 411.33 | 21.12 | 131.67 | 20.87 | 131.67 | 20.72 |
December | 422.00 | 20.44 | 305.50 | 20.32 | 305.50 | 20.27 |
Annual Sum or Average | 3219.17 | 21.39 | 2802.83 | 21.93 | 1344.83 | 21.70 |
Minimum of Months | 51.00 | 20.06 | 76.17 | 19.93 | 8.67 | 19.89 |
Maximum of Months | 427.00 | 26.18 | 395.83 | 24.70 | 335.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.17 | 20.66 | 279.83 | 20.36 | 278.67 | 20.21 |
February | 408.50 | 21.07 | 230.50 | 20.85 | 223.50 | 20.70 |
March | 417.83 | 21.44 | 133.00 | 21.39 | 102.50 | 21.23 |
April | 351.67 | 21.95 | 99.83 | 22.27 | 26.33 | 22.16 |
May | 242.67 | 22.80 | 161.83 | 23.42 | 3.17 | 23.44 |
June | 49.33 | 23.97 | 392.00 | 24.24 | 16.67 | 24.29 |
July | 56.33 | 26.05 | 487.50 | 24.59 | 56.33 | 24.73 |
August | 48.00 | 25.84 | 470.17 | 24.54 | 39.50 | 24.67 |
September | 114.00 | 23.77 | 340.50 | 24.25 | 27.33 | 24.38 |
October | 187.67 | 22.83 | 252.83 | 23.74 | 10.50 | 23.79 |
November | 395.00 | 21.56 | 130.17 | 21.50 | 92.00 | 21.30 |
December | 444.83 | 21.04 | 244.67 | 20.86 | 234.33 | 20.71 |
Annual Sum or Average | 3193.00 | 21.75 | 3222.83 | 22.44 | 1110.83 | 22.22 |
Minimum of Months | 48.00 | 20.66 | 99.83 | 20.36 | 3.17 | 20.21 |
Maximum of Months | 477.17 | 26.05 | 487.50 | 24.59 | 278.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.27 | 361.50 | 20.11 | 361.50 | 20.05 |
February | 453.67 | 20.58 | 326.33 | 20.42 | 326.33 | 20.35 |
March | 476.50 | 21.18 | 152.50 | 21.05 | 143.17 | 20.92 |
April | 390.33 | 21.68 | 88.50 | 21.87 | 37.33 | 21.77 |
May | 283.17 | 22.57 | 158.17 | 23.20 | 4.17 | 23.24 |
June | 77.00 | 23.79 | 384.33 | 24.20 | 22.50 | 24.29 |
July | 56.67 | 25.81 | 461.17 | 24.53 | 50.50 | 24.68 |
August | 52.67 | 24.91 | 450.50 | 24.41 | 30.83 | 24.52 |
September | 174.83 | 22.94 | 249.17 | 23.73 | 16.83 | 23.83 |
October | 312.50 | 22.21 | 127.50 | 22.68 | 10.00 | 22.64 |
November | 476.67 | 21.06 | 151.17 | 20.84 | 150.00 | 20.71 |
December | 497.00 | 20.55 | 358.83 | 20.44 | 358.83 | 20.39 |
Annual Sum or Average | 3753.00 | 21.39 | 3269.67 | 21.93 | 1512.00 | 21.71 |
Minimum of Months | 52.67 | 20.27 | 88.50 | 20.11 | 4.17 | 20.05 |
Maximum of Months | 502.00 | 25.81 | 461.17 | 24.53 | 361.50 | 24.68 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64037 | 23.58168 | -0.1727 | 7.97974 |
February | 454.00000 | 23.21200 | 19.55011 | -0.0489 | 5.65727 |
March | 514.00000 | 23.75558 | 26.81290 | 0.16168 | 5.89627 |
April | 485.00000 | 24.05746 | 32.36102 | 0.29829 | 7.27549 |
May | 508.00000 | 24.28755 | 40.04078 | -0.4271 | 9.25236 |
June | 496.00000 | 24.37359 | 49.68450 | -0.2840 | 7.18745 |
July | 497.00000 | 24.42958 | 53.21713 | -0.2299 | 6.61691 |
August | 514.00000 | 24.40247 | 49.67918 | -0.2535 | 6.96151 |
September | 485.00000 | 24.39795 | 45.31328 | -0.3147 | 7.61256 |
October | 502.00000 | 24.35025 | 38.68306 | 0.45630 | 9.83064 |
November | 489.00000 | 23.94168 | 29.57347 | 0.23301 | 6.93898 |
December | 497.00000 | 23.45935 | 22.49755 | 0.04214 | 5.39007 |
Annual Sum or Average | 5943.00000 | 23.94705 | 36.04198 | -0.0458 | 7.22945 |
Minimum of Months | 454.00000 | 22.64037 | 19.55011 | -0.4271 | 5.39007 |
Maximum of Months | 514.00000 | 24.42958 | 53.21713 | 0.45630 | 9.83064 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26083 | 25.46937 | -0.4863 | 12.04820 |
February | 454.00000 | 21.66829 | 21.29151 | -0.4043 | 9.25800 |
March | 514.00000 | 22.64030 | 29.41303 | -0.0985 | 6.03751 |
April | 485.00000 | 23.31183 | 34.78361 | 0.11979 | 6.32785 |
May | 508.00000 | 23.94916 | 41.56302 | -0.5565 | 12.10172 |
June | 496.00000 | 24.24855 | 50.41193 | -0.3482 | 7.90101 |
July | 497.00000 | 24.32490 | 54.37838 | -0.2803 | 6.99618 |
August | 514.00000 | 24.31964 | 50.76791 | -0.3019 | 7.37914 |
September | 485.00000 | 24.19849 | 46.30483 | -0.4098 | 9.05154 |
October | 502.00000 | 23.93257 | 40.00020 | 0.33457 | 8.05744 |
November | 489.00000 | 22.72468 | 32.66130 | -0.0585 | 6.75063 |
December | 497.00000 | 21.84443 | 25.00582 | -0.3306 | 8.04639 |
Annual Sum or Average | 5943.00000 | 23.21326 | 37.79516 | -0.2345 | 8.32831 |
Minimum of Months | 454.00000 | 21.26083 | 21.29151 | -0.5565 | 6.03751 |
Maximum of Months | 514.00000 | 24.32490 | 54.37838 | 0.33457 | 12.10172 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65256 | 26.28920 | -0.6540 | 16.46895 |
February | 454.00000 | 20.94154 | 21.21827 | -0.6047 | 14.21592 |
March | 514.00000 | 21.89481 | 30.40899 | -0.2831 | 8.07393 |
April | 485.00000 | 22.76617 | 35.76749 | -0.0125 | 6.80245 |
May | 508.00000 | 23.71884 | 42.23100 | -0.6318 | 14.51265 |
June | 496.00000 | 24.19405 | 50.39533 | -0.3595 | 8.11224 |
July | 497.00000 | 24.33372 | 54.44840 | -0.2647 | 6.83966 |
August | 514.00000 | 24.29821 | 50.82469 | -0.2998 | 7.37903 |
September | 485.00000 | 24.00721 | 46.61010 | -0.4778 | 10.66799 |
October | 502.00000 | 23.40583 | 41.28296 | 0.20390 | 7.39905 |
November | 489.00000 | 21.83265 | 34.07211 | -0.2842 | 8.93788 |
December | 497.00000 | 20.98514 | 25.66398 | -0.5600 | 12.97437 |
Annual Sum or Average | 5943.00000 | 22.76664 | 38.39612 | -0.3510 | 10.17433 |
Minimum of Months | 454.00000 | 20.65256 | 21.21827 | -0.6540 | 6.80245 |
Maximum of Months | 514.00000 | 24.33372 | 54.44840 | 0.20390 | 16.46895 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92850 | 26.92943 | -0.8857 | 24.30271 |
February | 454.00000 | 20.07958 | 21.55821 | -0.8686 | 23.14998 |
March | 514.00000 | 20.80197 | 31.63237 | -0.5582 | 13.40668 |
April | 485.00000 | 21.85009 | 37.23250 | -0.2230 | 8.99732 |
May | 508.00000 | 23.28801 | 43.52189 | -0.7447 | 19.37894 |
June | 496.00000 | 24.11647 | 52.19926 | -0.3304 | 8.23323 |
July | 497.00000 | 24.41617 | 56.96777 | -0.1635 | 6.57950 |
August | 514.00000 | 24.25849 | 52.55090 | -0.2572 | 7.46137 |
September | 485.00000 | 23.63919 | 48.95351 | -0.5714 | 14.06584 |
October | 502.00000 | 22.44565 | 43.64201 | -0.0089 | 8.12811 |
November | 489.00000 | 20.69355 | 35.46750 | -0.5706 | 14.42729 |
December | 497.00000 | 20.09228 | 26.83385 | -0.8230 | 21.25198 |
Annual Sum or Average | 5943.00000 | 22.15098 | 39.92557 | -0.4980 | 14.05310 |
Minimum of Months | 454.00000 | 19.92850 | 21.55821 | -0.8857 | 6.57950 |
Maximum of Months | 514.00000 | 24.41617 | 56.96777 | -0.0089 | 24.30271 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95921 | 26.33854 | -0.8567 | 23.34653 |
February | 454.00000 | 20.21073 | 20.90411 | -0.8017 | 20.81764 |
March | 514.00000 | 21.00925 | 30.82220 | -0.4719 | 12.16191 |
April | 485.00000 | 22.13053 | 36.12399 | -0.1163 | 9.04567 |
May | 508.00000 | 23.23075 | 43.33257 | -0.6737 | 19.37720 |
June | 496.00000 | 23.98604 | 52.14589 | -0.2986 | 8.80538 |
July | 497.00000 | 24.33235 | 56.50843 | -0.1149 | 7.30320 |
August | 514.00000 | 24.20673 | 52.12059 | -0.1725 | 7.38047 |
September | 485.00000 | 23.57607 | 48.65065 | -0.5091 | 14.31791 |
October | 502.00000 | 22.58849 | 42.87374 | 0.07261 | 8.30524 |
November | 489.00000 | 20.79404 | 34.79833 | -0.5194 | 13.29620 |
December | 497.00000 | 20.18287 | 26.21976 | -0.7784 | 19.71446 |
Annual Sum or Average | 5943.00000 | 22.19990 | 39.37286 | -0.4342 | 13.60546 |
Minimum of Months | 454.00000 | 19.95921 | 20.90411 | -0.8567 | 7.30320 |
Maximum of Months | 514.00000 | 24.33235 | 56.50843 | 0.07261 | 23.34653 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48008 | 25.70218 | -0.6971 | 20.08498 |
February | 454.00000 | 20.94091 | 20.10807 | -0.5938 | 17.17173 |
March | 514.00000 | 21.53541 | 29.79638 | -0.3327 | 11.46884 |
April | 485.00000 | 22.19126 | 35.90461 | -0.1057 | 9.38023 |
May | 508.00000 | 23.16589 | 43.41630 | -0.7372 | 20.53733 |
June | 496.00000 | 23.97967 | 52.19707 | -0.3424 | 9.17353 |
July | 497.00000 | 24.33905 | 56.67749 | -0.1520 | 7.11897 |
August | 514.00000 | 24.25395 | 51.97848 | -0.1756 | 7.47270 |
September | 485.00000 | 23.80349 | 47.82703 | -0.4165 | 12.71568 |
October | 502.00000 | 23.25375 | 41.02184 | 0.26212 | 10.38788 |
November | 489.00000 | 21.46479 | 33.46902 | -0.3361 | 11.68126 |
December | 497.00000 | 20.90669 | 25.22987 | -0.5736 | 16.36906 |
Annual Sum or Average | 5943.00000 | 22.53918 | 38.74915 | -0.3486 | 12.77377 |
Minimum of Months | 454.00000 | 20.48008 | 20.10807 | -0.7372 | 7.11897 |
Maximum of Months | 514.00000 | 24.33905 | 56.67749 | 0.26212 | 20.53733 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02355 | 26.11599 | -0.8499 | 23.14540 |
February | 454.00000 | 20.27178 | 20.73761 | -0.8017 | 21.39365 |
March | 514.00000 | 21.07439 | 30.52553 | -0.4621 | 12.48720 |
April | 485.00000 | 21.81689 | 36.70018 | -0.1865 | 9.66388 |
May | 508.00000 | 22.92051 | 44.03169 | -0.7759 | 22.52113 |
June | 496.00000 | 23.87881 | 52.35199 | -0.3224 | 9.85944 |
July | 497.00000 | 24.20979 | 56.90731 | -0.1555 | 7.73394 |
August | 514.00000 | 24.12291 | 52.44670 | -0.1997 | 8.03483 |
September | 485.00000 | 23.31359 | 49.25886 | -0.5909 | 16.61786 |
October | 502.00000 | 22.35631 | 43.33133 | 0.02566 | 8.62375 |
November | 489.00000 | 20.68625 | 34.88920 | -0.5560 | 14.11055 |
December | 497.00000 | 20.20504 | 26.04352 | -0.7835 | 20.02857 |
Annual Sum or Average | 5943.00000 | 22.08902 | 39.58226 | -0.4690 | 14.46825 |
Minimum of Months | 454.00000 | 20.02355 | 20.73761 | -0.8499 | 7.73394 |
Maximum of Months | 514.00000 | 24.20979 | 56.90731 | 0.02566 | 23.14540 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24918 | 27.31824 | -0.7828 | 19.81184 |
February | 454.00000 | 20.39250 | 22.19223 | -0.7739 | 18.86088 |
March | 514.00000 | 20.97150 | 32.18073 | -0.5148 | 11.44847 |
April | 485.00000 | 21.93557 | 37.82088 | -0.2163 | 7.68581 |
May | 508.00000 | 23.28886 | 44.14407 | -0.7948 | 19.93667 |
June | 496.00000 | 24.12969 | 52.42701 | -0.3759 | 8.46774 |
July | 497.00000 | 24.37891 | 56.07773 | -0.2254 | 6.64182 |
August | 514.00000 | 24.29860 | 51.75413 | -0.2789 | 7.25455 |
September | 485.00000 | 24.02922 | 47.98884 | -0.4560 | 10.19090 |
October | 502.00000 | 23.35017 | 42.10973 | 0.20199 | 7.26593 |
November | 489.00000 | 21.60402 | 34.22739 | -0.3222 | 9.11850 |
December | 497.00000 | 20.59549 | 26.78301 | -0.6518 | 14.58062 |
Annual Sum or Average | 5943.00000 | 22.45037 | 39.71669 | -0.4309 | 11.74050 |
Minimum of Months | 454.00000 | 20.24918 | 22.19223 | -0.7948 | 6.64182 |
Maximum of Months | 514.00000 | 24.37891 | 56.07773 | 0.20199 | 19.93667 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30779 | 26.49618 | -0.7498 | 18.71330 |
February | 454.00000 | 20.59040 | 21.23214 | -0.6934 | 16.20258 |
March | 514.00000 | 21.22433 | 31.01702 | -0.4156 | 9.84498 |
April | 485.00000 | 22.33098 | 36.10940 | -0.0822 | 7.69394 |
May | 508.00000 | 23.34360 | 43.33039 | -0.6899 | 18.54441 |
June | 496.00000 | 24.08214 | 52.00771 | -0.3190 | 8.30994 |
July | 497.00000 | 24.40467 | 55.21617 | -0.1451 | 6.62761 |
August | 514.00000 | 24.35010 | 50.96445 | -0.1607 | 6.54132 |
September | 485.00000 | 24.04880 | 47.39711 | -0.3690 | 9.83254 |
October | 502.00000 | 23.48567 | 41.10628 | 0.28543 | 8.18170 |
November | 489.00000 | 21.66578 | 33.38741 | -0.2775 | 8.60542 |
December | 497.00000 | 20.72901 | 25.84857 | -0.5989 | 13.22909 |
Annual Sum or Average | 5943.00000 | 22.56118 | 38.80839 | -0.3495 | 11.00442 |
Minimum of Months | 454.00000 | 20.30779 | 21.23214 | -0.7498 | 6.54132 |
Maximum of Months | 514.00000 | 24.40467 | 55.21617 | 0.28543 | 18.71330 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96818 | 24.99945 | -0.7519 | 19.91874 |
February | 454.00000 | 20.39088 | 19.58751 | -0.6545 | 17.18559 |
March | 514.00000 | 21.01643 | 29.67228 | -0.4103 | 10.91097 |
April | 485.00000 | 21.86202 | 35.96473 | -0.1720 | 8.53565 |
May | 508.00000 | 22.76441 | 44.63898 | -0.8921 | 24.92430 |
June | 496.00000 | 23.90561 | 55.08487 | -0.3930 | 9.65163 |
July | 497.00000 | 24.38939 | 59.62420 | -0.1592 | 6.43578 |
August | 514.00000 | 24.39489 | 53.61571 | -0.1425 | 6.67447 |
September | 485.00000 | 24.12581 | 48.53405 | -0.2978 | 9.41529 |
October | 502.00000 | 23.82340 | 40.30351 | 0.42907 | 11.00775 |
November | 489.00000 | 21.68425 | 31.83435 | -0.2169 | 9.16824 |
December | 497.00000 | 20.79772 | 24.00910 | -0.5187 | 13.42776 |
Annual Sum or Average | 5943.00000 | 22.44143 | 39.13818 | -0.3470 | 12.26261 |
Minimum of Months | 454.00000 | 19.96818 | 19.58751 | -0.8921 | 6.43578 |
Maximum of Months | 514.00000 | 24.39489 | 59.62420 | 0.42907 | 24.92430 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34648 | 26.37396 | -0.7476 | 18.72825 |
February | 454.00000 | 20.59927 | 21.15350 | -0.7020 | 16.82623 |
March | 514.00000 | 21.28725 | 30.76738 | -0.4030 | 9.88152 |
April | 485.00000 | 22.09003 | 36.59191 | -0.1376 | 7.89489 |
May | 508.00000 | 23.13648 | 43.81087 | -0.7642 | 20.42110 |
June | 496.00000 | 24.11807 | 51.84581 | -0.2994 | 8.20401 |
July | 497.00000 | 24.36525 | 55.38614 | -0.1592 | 6.78386 |
August | 514.00000 | 24.34717 | 51.09678 | -0.1638 | 6.64083 |
September | 485.00000 | 23.93978 | 47.70002 | -0.4079 | 10.44216 |
October | 502.00000 | 23.40462 | 41.22834 | 0.27007 | 8.21319 |
November | 489.00000 | 21.45379 | 33.69879 | -0.3352 | 9.12733 |
December | 497.00000 | 20.72084 | 25.78082 | -0.6099 | 13.57740 |
Annual Sum or Average | 5943.00000 | 22.49878 | 38.91804 | -0.3697 | 11.37062 |
Minimum of Months | 454.00000 | 20.34648 | 21.15350 | -0.7642 | 6.64083 |
Maximum of Months | 514.00000 | 24.36525 | 55.38614 | 0.27007 | 20.42110 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16776 | 26.90880 | -0.7864 | 20.36318 |
February | 454.00000 | 20.36837 | 21.46663 | -0.7544 | 18.69095 |
March | 514.00000 | 21.20258 | 31.30113 | -0.4329 | 10.29442 |
April | 485.00000 | 22.33131 | 36.56933 | -0.0987 | 7.43330 |
May | 508.00000 | 23.64321 | 42.66017 | -0.6345 | 14.97115 |
June | 496.00000 | 24.22587 | 51.92265 | -0.3052 | 7.54936 |
July | 497.00000 | 24.44830 | 56.56750 | -0.1702 | 6.44569 |
August | 514.00000 | 24.32860 | 52.23514 | -0.2478 | 7.09386 |
September | 485.00000 | 23.93844 | 48.27606 | -0.4761 | 10.96211 |
October | 502.00000 | 23.09246 | 42.22919 | 0.14545 | 7.38380 |
November | 489.00000 | 21.27972 | 34.59345 | -0.4014 | 10.61049 |
December | 497.00000 | 20.43264 | 26.48949 | -0.6924 | 16.23751 |
Annual Sum or Average | 5943.00000 | 22.47116 | 39.40119 | -0.4024 | 11.45649 |
Minimum of Months | 454.00000 | 20.16776 | 21.46663 | -0.7864 | 6.44569 |
Maximum of Months | 514.00000 | 24.44830 | 56.56750 | 0.14545 | 20.36318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.05925 | 25.61592 | -0.7987 | 20.92323 |
February | 385.00000 | 20.44765 | 20.06372 | -0.7134 | 17.46823 |
March | 433.00000 | 21.21842 | 30.13165 | -0.4016 | 10.15667 |
April | 410.00000 | 22.33533 | 35.60401 | -0.0593 | 8.11387 |
May | 430.00000 | 23.41429 | 42.56684 | -0.6274 | 17.23061 |
June | 418.00000 | 24.07623 | 51.66342 | -0.3000 | 8.64430 |
July | 422.00000 | 24.40887 | 56.06195 | -0.1301 | 7.31952 |
August | 433.00000 | 24.28843 | 51.86310 | -0.1869 | 7.42700 |
September | 410.00000 | 23.76025 | 48.17733 | -0.4646 | 12.72100 |
October | 427.00000 | 22.90032 | 41.58956 | 0.14348 | 7.71070 |
November | 417.00000 | 21.15877 | 33.76006 | -0.4070 | 10.58914 |
December | 422.00000 | 20.43942 | 25.27812 | -0.6774 | 15.88855 |
Annual Sum or Average | 5034.00000 | 22.38795 | 38.65273 | -0.3833 | 11.98648 |
Minimum of Months | 385.00000 | 20.05925 | 20.06372 | -0.7987 | 7.31952 |
Maximum of Months | 433.00000 | 24.40887 | 56.06195 | 0.14348 | 20.92323 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.83355 | 25.40728 | -0.5795 | 16.39951 |
February | 454.00000 | 21.40290 | 19.71633 | -0.4524 | 13.27415 |
March | 514.00000 | 21.93419 | 29.27014 | -0.2127 | 9.07409 |
April | 485.00000 | 22.58692 | 35.21915 | -0.0002 | 8.11765 |
May | 508.00000 | 23.49923 | 42.52654 | -0.6344 | 16.09099 |
June | 496.00000 | 24.11756 | 51.83287 | -0.3104 | 8.10910 |
July | 497.00000 | 24.40254 | 56.16258 | -0.1517 | 6.71852 |
August | 514.00000 | 24.33885 | 51.59342 | -0.1655 | 6.92071 |
September | 485.00000 | 24.06316 | 47.20926 | -0.3357 | 10.08414 |
October | 502.00000 | 23.69716 | 39.88842 | 0.37348 | 10.41851 |
November | 489.00000 | 22.04607 | 32.45382 | -0.1730 | 9.17406 |
December | 497.00000 | 21.40216 | 24.55065 | -0.4194 | 12.31403 |
Annual Sum or Average | 5943.00000 | 22.87167 | 38.12355 | -0.2542 | 10.54685 |
Minimum of Months | 454.00000 | 20.83355 | 19.71633 | -0.6344 | 6.71852 |
Maximum of Months | 514.00000 | 24.40254 | 56.16258 | 0.37348 | 16.39951 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.26629 | 25.94592 | -0.7516 | 19.38832 |
February | 454.00000 | 20.57886 | 20.44184 | -0.6868 | 17.18828 |
March | 514.00000 | 21.38781 | 30.14739 | -0.3559 | 9.90675 |
April | 485.00000 | 22.16836 | 36.10027 | -0.0883 | 8.22453 |
May | 508.00000 | 23.25418 | 43.15696 | -0.6731 | 17.97546 |
June | 496.00000 | 24.04270 | 51.93571 | -0.2844 | 8.55841 |
July | 497.00000 | 24.28919 | 56.34459 | -0.1515 | 7.20392 |
August | 514.00000 | 24.22723 | 52.04976 | -0.1842 | 7.30742 |
September | 485.00000 | 23.62741 | 48.55174 | -0.4939 | 13.08549 |
October | 502.00000 | 22.85958 | 42.07995 | 0.15116 | 7.94595 |
November | 489.00000 | 21.12877 | 34.11537 | -0.4153 | 10.64698 |
December | 497.00000 | 20.55268 | 25.49904 | -0.6542 | 15.29134 |
Annual Sum or Average | 5943.00000 | 22.38024 | 39.00012 | -0.3802 | 11.85794 |
Minimum of Months | 454.00000 | 20.26629 | 20.44184 | -0.7516 | 7.20392 |
Maximum of Months | 514.00000 | 24.28919 | 56.34459 | 0.15116 | 19.38832 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.529582E+09 | 0.137902E+09 | 13.17 | 0.371008E+09 | 0.158575E+09 | 0.00 | 0.72 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 25491.30 | 27-MAR-16:00 | 21632.76 | 27-MAR-16:00 | 8683.01 | 27-MAR-12:45 | 6302.33 | 27-MAR-16:00 | 0.00 |
April | 0.456297E+10 | 0.117831E+10 | 88.39 | 0.412868E+10 | 0.434293E+09 | 0.00 | 1.00 | 07-APR-11:50 | 0.00 | 01-APR-00:10 | 46110.52 | 07-APR-15:40 | 46110.52 | 07-APR-15:40 | 5936.00 | 10-APR-08:65 | 10990.79 | 07-APR-15:40 | 0.00 |
May | 0.180594E+11 | 0.461222E+10 | 286.65 | 0.151629E+11 | 0.289645E+10 | 0.00 | 1.00 | 30-MAY-07:05 | 0.00 | 01-MAY-00:10 | 83690.32 | 30-MAY-14:00 | 83690.32 | 30-MAY-14:00 | 19388.77 | 18-MAY-10:00 | 21997.14 | 30-MAY-13:40 | 0.00 |
June | 0.626865E+11 | 0.152781E+11 | 434.89 | 0.490376E+11 | 0.136488E+11 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 102652.39 | 27-JUN-04:02 | 79505.04 | 01-JUN-15:00 | 49607.13 | 28-JUN-04:02 | 29815.42 | 19-JUN-12:03 | 0.00 |
July | 0.885899E+11 | 0.217980E+11 | 451.29 | 0.665681E+11 | 0.220218E+11 | 0.00 | 1.00 | 01-JUL-09:50 | 0.00 | 01-JUL-00:10 | 128767.83 | 22-JUL-04:02 | 88900.83 | 10-JUL-04:02 | 65858.96 | 22-JUL-04:02 | 29093.03 | 22-JUL-04:02 | 0.00 |
August | 0.905460E+11 | 0.226177E+11 | 468.26 | 0.726840E+11 | 0.178620E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 124899.53 | 04-AUG-04:02 | 91659.23 | 22-AUG-15:50 | 51438.47 | 04-AUG-04:02 | 29070.56 | 03-AUG-04:02 | 0.00 |
September | 0.477768E+11 | 0.115850E+11 | 396.98 | 0.388690E+11 | 0.890782E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 109298.85 | 08-SEP-04:02 | 81466.35 | 05-SEP-04:02 | 48433.40 | 06-SEP-04:02 | 24996.00 | 08-SEP-04:02 | 0.00 |
October | 0.206076E+11 | 0.499216E+10 | 230.13 | 0.146168E+11 | 0.599083E+10 | 0.00 | 1.00 | 02-OCT-13:00 | 0.00 | 01-OCT-00:10 | 71533.61 | 05-OCT-12:20 | 55469.89 | 04-OCT-15:30 | 31681.68 | 06-OCT-04:03 | 16448.21 | 05-OCT-12:20 | 0.00 |
November | 0.475274E+09 | 0.133794E+09 | 25.17 | 0.384216E+09 | 91057605.25 | 0.00 | 0.36 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 11443.78 | 03-NOV-14:00 | 11443.78 | 03-NOV-14:00 | 5106.87 | 10-NOV-10:00 | 3112.85 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.333834E+12 | 0.823332E+11 | 2394.93 | 0.261822E+12 | 0.720117E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.905460E+11 | 0.226177E+11 | 468.26 | 0.726840E+11 | 0.220218E+11 | 0.00 | 1.00 | 0.00 | 128767.83 | 91659.23 | 65858.96 | 29815.42 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.496203E+09 | 0.129606E+09 | 14.33 | 0.344755E+09 | 0.151448E+09 | 0.00 | 0.71 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 23412.40 | 27-MAR-16:00 | 19185.25 | 27-MAR-16:00 | 8251.10 | 27-MAR-12:50 | 5813.53 | 27-MAR-16:00 | 0.00 |
April | 0.470562E+10 | 0.121376E+10 | 95.15 | 0.423883E+10 | 0.466792E+09 | 0.00 | 1.00 | 07-APR-12:10 | 0.00 | 01-APR-00:10 | 48368.38 | 07-APR-14:30 | 48368.38 | 07-APR-14:30 | 7641.82 | 09-APR-11:55 | 11598.11 | 07-APR-14:30 | 0.00 |
May | 0.175629E+11 | 0.448302E+10 | 294.28 | 0.149454E+11 | 0.261754E+10 | 0.00 | 1.00 | 29-MAY-08:42 | 0.00 | 01-MAY-00:10 | 85277.05 | 30-MAY-14:10 | 85277.05 | 30-MAY-14:10 | 17576.71 | 18-MAY-15:00 | 22275.97 | 30-MAY-14:10 | 0.00 |
June | 0.581711E+11 | 0.141834E+11 | 434.60 | 0.452525E+11 | 0.129186E+11 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 108547.90 | 19-JUN-04:02 | 76533.52 | 01-JUN-15:00 | 43844.42 | 30-JUN-05:02 | 26334.02 | 19-JUN-12:04 | 0.00 |
July | 0.815573E+11 | 0.200291E+11 | 450.97 | 0.606027E+11 | 0.209546E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 122565.27 | 22-JUL-04:02 | 78946.91 | 10-JUL-04:02 | 72696.75 | 24-JUL-04:02 | 27496.18 | 22-JUL-04:02 | 0.00 |
August | 0.811530E+11 | 0.202489E+11 | 461.24 | 0.650192E+11 | 0.161338E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 118629.41 | 17-AUG-04:02 | 91346.86 | 22-AUG-14:50 | 51532.66 | 04-AUG-04:02 | 27563.47 | 05-AUG-05:02 | 0.00 |
September | 0.413605E+11 | 0.100744E+11 | 388.64 | 0.332293E+11 | 0.813123E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 89946.03 | 01-SEP-05:02 | 64782.83 | 01-SEP-14:40 | 38035.34 | 14-SEP-05:02 | 20736.33 | 01-SEP-05:02 | 0.00 |
October | 0.179185E+11 | 0.436882E+10 | 228.07 | 0.126484E+11 | 0.527017E+10 | 0.00 | 1.00 | 03-OCT-10:10 | 0.00 | 01-OCT-00:10 | 65469.64 | 06-OCT-05:03 | 50121.43 | 04-OCT-15:00 | 37559.41 | 06-OCT-05:03 | 15053.26 | 06-OCT-05:03 | 0.00 |
November | 0.453492E+09 | 0.127557E+09 | 25.33 | 0.378693E+09 | 74799790.96 | 0.00 | 0.33 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9841.78 | 03-NOV-14:00 | 9841.78 | 03-NOV-14:00 | 3463.25 | 10-NOV-08:00 | 2696.50 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.303379E+12 | 0.748585E+11 | 2392.62 | 0.236660E+12 | 0.667190E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.815573E+11 | 0.202489E+11 | 461.24 | 0.650192E+11 | 0.209546E+11 | 0.00 | 1.00 | 0.00 | 122565.27 | 91346.86 | 72696.75 | 27563.47 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.517691E+09 | 0.135972E+09 | 13.17 | 0.353137E+09 | 0.164554E+09 | 0.00 | 0.68 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 24736.84 | 27-MAR-16:00 | 19669.52 | 27-MAR-16:00 | 8856.82 | 27-MAR-13:00 | 6189.59 | 27-MAR-16:00 | 0.00 |
April | 0.488536E+10 | 0.126607E+10 | 93.11 | 0.436318E+10 | 0.522174E+09 | 0.00 | 1.00 | 07-APR-12:10 | 0.00 | 01-APR-00:10 | 53093.15 | 07-APR-14:30 | 53093.15 | 07-APR-14:30 | 8470.16 | 09-APR-11:52 | 12731.32 | 07-APR-14:30 | 0.00 |
May | 0.182152E+11 | 0.467841E+10 | 292.03 | 0.155398E+11 | 0.267539E+10 | 0.00 | 1.00 | 29-MAY-09:02 | 0.00 | 01-MAY-00:10 | 94000.76 | 30-MAY-14:00 | 94000.76 | 30-MAY-14:00 | 16608.70 | 18-MAY-15:00 | 24684.25 | 30-MAY-14:00 | 0.00 |
June | 0.610766E+11 | 0.149787E+11 | 430.76 | 0.480851E+11 | 0.129916E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 105264.19 | 19-JUN-04:02 | 85205.74 | 19-JUN-13:40 | 44171.53 | 24-JUN-05:02 | 29770.79 | 19-JUN-12:04 | 0.00 |
July | 0.863920E+11 | 0.212631E+11 | 449.27 | 0.652410E+11 | 0.211510E+11 | 0.00 | 1.00 | 01-JUL-09:40 | 0.00 | 01-JUL-00:10 | 129352.39 | 31-JUL-04:02 | 87166.65 | 10-JUL-04:02 | 63958.84 | 24-JUL-04:02 | 30322.35 | 10-JUL-04:02 | 0.00 |
August | 0.852770E+11 | 0.213398E+11 | 454.82 | 0.692683E+11 | 0.160086E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 132379.72 | 17-AUG-04:02 | 99587.91 | 22-AUG-14:40 | 61257.65 | 17-AUG-04:02 | 30639.47 | 05-AUG-05:02 | 0.00 |
September | 0.417880E+11 | 0.102657E+11 | 383.21 | 0.334021E+11 | 0.838589E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 99488.89 | 14-SEP-05:02 | 93182.15 | 01-SEP-14:10 | 46098.77 | 14-SEP-05:02 | 25500.93 | 01-SEP-14:10 | 0.00 |
October | 0.173422E+11 | 0.428160E+10 | 222.97 | 0.120577E+11 | 0.528445E+10 | 0.00 | 1.00 | 03-OCT-11:40 | 0.00 | 01-OCT-00:10 | 63970.50 | 04-OCT-14:00 | 55417.44 | 04-OCT-15:00 | 22553.63 | 24-OCT-09:30 | 14912.68 | 04-OCT-13:50 | 0.00 |
November | 0.399527E+09 | 0.113217E+09 | 23.83 | 0.320800E+09 | 78726903.23 | 0.00 | 0.29 | 04-NOV-12:40 | 0.00 | 01-NOV-00:10 | 9647.50 | 04-NOV-12:40 | 8695.69 | 03-NOV-14:00 | 3520.20 | 10-NOV-08:00 | 2666.45 | 04-NOV-12:40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.315894E+12 | 0.783224E+11 | 2363.17 | 0.248631E+12 | 0.672624E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.863920E+11 | 0.213398E+11 | 454.82 | 0.692683E+11 | 0.211510E+11 | 0.00 | 1.00 | 0.00 | 132379.72 | 99587.91 | 63958.84 | 30639.47 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.10 | 0.00 | 344.10 | 35.89 | 1582.68 | 0.00 | 0.00 | 0.00 |
February | 470.89 | 0.00 | 470.89 | 62.28 | 1636.54 | 0.00 | 0.00 | 0.00 |
March | 653.01 | 0.00 | 653.01 | 275.23 | 1082.26 | 0.00 | 0.00 | 0.00 |
April | 784.35 | 2.23 | 782.12 | 531.98 | 771.62 | 0.00 | 0.00 | 0.00 |
May | 1040.58 | 34.67 | 1005.91 | 994.16 | 488.96 | 0.00 | 0.00 | 0.00 |
June | 1103.53 | 59.30 | 1044.23 | 1337.58 | 275.52 | 0.00 | 0.00 | 0.00 |
July | 1066.45 | 38.57 | 1027.89 | 1466.67 | 157.87 | 0.00 | 0.00 | 0.00 |
August | 944.83 | 11.24 | 933.58 | 1284.96 | 212.58 | 0.00 | 0.00 | 0.00 |
September | 712.24 | 0.13 | 712.11 | 760.95 | 408.36 | 0.00 | 0.00 | 0.00 |
October | 616.39 | 0.00 | 616.39 | 483.34 | 734.69 | 0.00 | 0.00 | 0.00 |
November | 432.34 | 0.00 | 432.34 | 155.49 | 1096.35 | 0.00 | 0.00 | 0.00 |
December | 300.15 | 0.00 | 300.15 | 24.81 | 1456.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 707.10 | 12.24 | 694.85 | 621.48 | 820.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 300.15 | 0.00 | 300.15 | 24.81 | 157.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1103.53 | 59.30 | 1044.23 | 1466.67 | 1636.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 479.19 | 192.12 | 287.08 | 311.07 | 984.30 | 0.00 | 0.00 | 0.00 |
February | 743.12 | 346.67 | 396.46 | 540.36 | 986.56 | 0.00 | 0.00 | 0.00 |
March | 947.99 | 403.19 | 544.81 | 844.47 | 697.34 | 0.00 | 0.00 | 0.00 |
April | 1137.66 | 498.33 | 639.33 | 1156.87 | 500.16 | 0.00 | 0.00 | 0.00 |
May | 1379.74 | 551.43 | 828.32 | 1580.75 | 327.61 | 0.00 | 0.00 | 0.00 |
June | 1278.73 | 462.89 | 815.84 | 1626.93 | 183.31 | 0.00 | 0.00 | 0.00 |
July | 1284.33 | 463.48 | 820.85 | 1758.96 | 102.91 | 0.00 | 0.00 | 0.00 |
August | 1446.18 | 652.08 | 794.10 | 1969.25 | 139.80 | 0.00 | 0.00 | 0.00 |
September | 1078.57 | 483.91 | 594.66 | 1320.71 | 260.63 | 0.00 | 0.00 | 0.00 |
October | 977.80 | 443.17 | 534.63 | 1082.54 | 472.89 | 0.00 | 0.00 | 0.00 |
November | 604.70 | 232.21 | 372.49 | 509.60 | 690.34 | 0.00 | 0.00 | 0.00 |
December | 471.09 | 221.20 | 249.90 | 332.31 | 898.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.33 | 413.02 | 574.30 | 1089.90 | 517.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.09 | 192.12 | 249.90 | 311.07 | 102.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1446.18 | 652.08 | 828.32 | 1969.25 | 986.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1780.09 | 1165.62 | 614.48 | 1753.56 | 1426.42 | 0.00 | 0.00 | 0.00 |
February | 2347.88 | 1554.11 | 793.78 | 2349.09 | 1444.31 | 0.00 | 0.00 | 0.00 |
March | 2118.24 | 1175.66 | 942.58 | 2232.88 | 1061.90 | 0.00 | 0.00 | 0.00 |
April | 1643.68 | 649.96 | 993.72 | 1792.76 | 798.33 | 0.00 | 0.00 | 0.00 |
May | 1440.44 | 300.45 | 1139.99 | 1664.80 | 518.26 | 0.00 | 0.00 | 0.00 |
June | 1351.81 | 206.64 | 1145.17 | 1774.63 | 289.76 | 0.00 | 0.00 | 0.00 |
July | 1416.97 | 246.13 | 1170.84 | 2045.82 | 158.82 | 0.00 | 0.00 | 0.00 |
August | 1892.20 | 701.85 | 1190.36 | 2750.10 | 223.69 | 0.00 | 0.00 | 0.00 |
September | 2053.08 | 1061.93 | 991.14 | 2669.45 | 419.48 | 0.00 | 0.00 | 0.00 |
October | 2812.54 | 1763.66 | 1048.88 | 3424.84 | 745.52 | 0.00 | 0.00 | 0.00 |
November | 1950.25 | 1171.22 | 779.04 | 2075.38 | 1041.57 | 0.00 | 0.00 | 0.00 |
December | 1929.35 | 1369.71 | 559.64 | 1974.85 | 1303.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1892.58 | 944.17 | 948.40 | 2209.30 | 782.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1351.81 | 206.64 | 559.64 | 1664.80 | 158.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2812.54 | 1763.66 | 1190.36 | 3424.84 | 1444.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.07 | 193.77 | 279.30 | 305.64 | 1005.66 | 0.00 | 0.00 | 0.00 |
February | 697.61 | 306.39 | 391.22 | 495.63 | 1030.94 | 0.00 | 0.00 | 0.00 |
March | 1030.11 | 475.57 | 554.54 | 943.52 | 697.47 | 0.00 | 0.00 | 0.00 |
April | 1125.86 | 481.73 | 644.13 | 1158.63 | 516.74 | 0.00 | 0.00 | 0.00 |
May | 1311.51 | 498.06 | 813.45 | 1515.10 | 341.05 | 0.00 | 0.00 | 0.00 |
June | 1435.41 | 578.94 | 856.47 | 1841.03 | 196.33 | 0.00 | 0.00 | 0.00 |
July | 1344.34 | 506.24 | 838.10 | 1841.55 | 111.03 | 0.00 | 0.00 | 0.00 |
August | 1487.20 | 688.48 | 798.73 | 2037.25 | 152.36 | 0.00 | 0.00 | 0.00 |
September | 1055.80 | 461.38 | 594.42 | 1310.97 | 273.91 | 0.00 | 0.00 | 0.00 |
October | 1046.74 | 509.00 | 537.74 | 1181.96 | 489.95 | 0.00 | 0.00 | 0.00 |
November | 491.55 | 142.06 | 349.49 | 359.27 | 708.97 | 0.00 | 0.00 | 0.00 |
December | 437.22 | 189.19 | 248.03 | 290.42 | 924.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 996.79 | 420.20 | 576.59 | 1111.10 | 534.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 437.22 | 142.06 | 248.03 | 290.42 | 111.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1487.20 | 688.48 | 856.47 | 2037.25 | 1030.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.70 | 0.00 | 114.70 | 11.31 | 550.19 | 0.00 | 0.00 | 0.00 |
February | 156.96 | 0.00 | 156.96 | 20.61 | 565.40 | 0.00 | 0.00 | 0.00 |
March | 217.66 | 0.00 | 217.66 | 94.65 | 372.45 | 0.00 | 0.00 | 0.00 |
April | 261.44 | 0.74 | 260.69 | 182.41 | 262.78 | 0.00 | 0.00 | 0.00 |
May | 346.85 | 11.56 | 335.29 | 341.36 | 161.26 | 0.00 | 0.00 | 0.00 |
June | 367.82 | 19.76 | 348.06 | 454.01 | 89.90 | 0.00 | 0.00 | 0.00 |
July | 355.47 | 12.85 | 342.61 | 496.40 | 50.17 | 0.00 | 0.00 | 0.00 |
August | 314.93 | 3.75 | 311.18 | 432.02 | 71.20 | 0.00 | 0.00 | 0.00 |
September | 237.40 | 0.04 | 237.36 | 251.78 | 147.36 | 0.00 | 0.00 | 0.00 |
October | 205.45 | 0.00 | 205.45 | 153.33 | 273.16 | 0.00 | 0.00 | 0.00 |
November | 144.11 | 0.00 | 144.11 | 44.57 | 409.33 | 0.00 | 0.00 | 0.00 |
December | 100.05 | 0.00 | 100.05 | 6.52 | 525.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.69 | 4.08 | 231.61 | 208.67 | 288.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.05 | 0.00 | 100.05 | 6.52 | 50.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.82 | 19.76 | 348.06 | 496.40 | 565.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.70 | 0.00 | 114.70 | 11.31 | 550.23 | 0.00 | 0.00 | 0.00 |
February | 156.97 | 0.00 | 156.97 | 20.61 | 565.44 | 0.00 | 0.00 | 0.00 |
March | 217.67 | 0.00 | 217.67 | 94.65 | 372.48 | 0.00 | 0.00 | 0.00 |
April | 261.45 | 0.74 | 260.71 | 182.42 | 262.79 | 0.00 | 0.00 | 0.00 |
May | 346.87 | 11.56 | 335.31 | 341.38 | 161.27 | 0.00 | 0.00 | 0.00 |
June | 367.85 | 19.77 | 348.08 | 454.04 | 89.90 | 0.00 | 0.00 | 0.00 |
July | 355.49 | 12.86 | 342.63 | 496.43 | 50.17 | 0.00 | 0.00 | 0.00 |
August | 314.95 | 3.75 | 311.20 | 432.05 | 71.21 | 0.00 | 0.00 | 0.00 |
September | 237.42 | 0.04 | 237.37 | 251.79 | 147.37 | 0.00 | 0.00 | 0.00 |
October | 205.47 | 0.00 | 205.47 | 153.34 | 273.17 | 0.00 | 0.00 | 0.00 |
November | 144.12 | 0.00 | 144.12 | 44.58 | 409.36 | 0.00 | 0.00 | 0.00 |
December | 100.05 | 0.00 | 100.05 | 6.52 | 525.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.70 | 4.08 | 231.62 | 208.68 | 288.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.05 | 0.00 | 100.05 | 6.52 | 50.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.85 | 19.77 | 348.08 | 496.43 | 565.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.70 | 0.00 | 114.70 | 11.31 | 550.23 | 0.00 | 0.00 | 0.00 |
February | 156.97 | 0.00 | 156.97 | 20.61 | 565.44 | 0.00 | 0.00 | 0.00 |
March | 217.67 | 0.00 | 217.67 | 94.65 | 372.48 | 0.00 | 0.00 | 0.00 |
April | 261.45 | 0.74 | 260.71 | 182.42 | 262.79 | 0.00 | 0.00 | 0.00 |
May | 346.87 | 11.56 | 335.31 | 341.38 | 161.27 | 0.00 | 0.00 | 0.00 |
June | 367.85 | 19.77 | 348.08 | 454.04 | 89.90 | 0.00 | 0.00 | 0.00 |
July | 355.49 | 12.86 | 342.63 | 496.43 | 50.17 | 0.00 | 0.00 | 0.00 |
August | 314.95 | 3.75 | 311.20 | 432.05 | 71.21 | 0.00 | 0.00 | 0.00 |
September | 237.42 | 0.04 | 237.37 | 251.79 | 147.37 | 0.00 | 0.00 | 0.00 |
October | 205.47 | 0.00 | 205.47 | 153.34 | 273.17 | 0.00 | 0.00 | 0.00 |
November | 144.12 | 0.00 | 144.12 | 44.58 | 409.36 | 0.00 | 0.00 | 0.00 |
December | 100.05 | 0.00 | 100.05 | 6.52 | 525.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.70 | 4.08 | 231.62 | 208.68 | 288.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 100.05 | 0.00 | 100.05 | 6.52 | 50.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.85 | 19.77 | 348.08 | 496.43 | 565.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 460.96 | 184.81 | 276.15 | 298.44 | 994.58 | 0.00 | 0.00 | 0.00 |
February | 714.85 | 333.48 | 381.38 | 519.15 | 997.06 | 0.00 | 0.00 | 0.00 |
March | 911.93 | 387.85 | 524.08 | 820.23 | 703.46 | 0.00 | 0.00 | 0.00 |
April | 1094.38 | 479.37 | 615.01 | 1122.93 | 503.12 | 0.00 | 0.00 | 0.00 |
May | 1327.25 | 530.45 | 796.81 | 1539.39 | 321.16 | 0.00 | 0.00 | 0.00 |
June | 1230.08 | 445.28 | 784.81 | 1580.49 | 179.09 | 0.00 | 0.00 | 0.00 |
July | 1235.47 | 445.85 | 789.62 | 1705.38 | 101.33 | 0.00 | 0.00 | 0.00 |
August | 1391.17 | 627.27 | 763.89 | 1902.80 | 144.21 | 0.00 | 0.00 | 0.00 |
September | 1037.54 | 465.50 | 572.04 | 1268.00 | 279.44 | 0.00 | 0.00 | 0.00 |
October | 940.61 | 426.31 | 514.29 | 1027.99 | 516.82 | 0.00 | 0.00 | 0.00 |
November | 581.69 | 223.37 | 358.32 | 472.36 | 747.21 | 0.00 | 0.00 | 0.00 |
December | 453.17 | 212.78 | 240.39 | 311.74 | 942.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.76 | 397.31 | 552.46 | 1051.05 | 533.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 453.17 | 184.81 | 240.39 | 298.44 | 101.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1391.17 | 627.27 | 796.81 | 1902.80 | 997.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.23 | 7.31 | 10.92 | 11.80 | 39.32 | 0.00 | 0.00 | 0.00 |
February | 28.26 | 13.19 | 15.08 | 20.53 | 39.42 | 0.00 | 0.00 | 0.00 |
March | 36.06 | 15.34 | 20.72 | 32.43 | 27.81 | 0.00 | 0.00 | 0.00 |
April | 43.27 | 18.95 | 24.32 | 44.40 | 19.89 | 0.00 | 0.00 | 0.00 |
May | 52.48 | 20.97 | 31.50 | 60.87 | 12.70 | 0.00 | 0.00 | 0.00 |
June | 48.64 | 17.61 | 31.03 | 62.49 | 7.08 | 0.00 | 0.00 | 0.00 |
July | 48.85 | 17.63 | 31.22 | 67.43 | 4.01 | 0.00 | 0.00 | 0.00 |
August | 55.01 | 24.80 | 30.20 | 75.24 | 5.70 | 0.00 | 0.00 | 0.00 |
September | 41.02 | 18.41 | 22.62 | 50.14 | 11.05 | 0.00 | 0.00 | 0.00 |
October | 37.19 | 16.86 | 20.33 | 40.65 | 20.43 | 0.00 | 0.00 | 0.00 |
November | 23.00 | 8.83 | 14.17 | 18.68 | 29.54 | 0.00 | 0.00 | 0.00 |
December | 17.92 | 8.41 | 9.50 | 12.33 | 37.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.55 | 15.71 | 21.84 | 41.56 | 21.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.92 | 7.31 | 9.50 | 11.80 | 4.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.01 | 24.80 | 31.50 | 75.24 | 39.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 593.38 | 388.55 | 204.83 | 595.07 | 498.18 | 0.00 | 0.00 | 0.00 |
February | 782.65 | 518.05 | 264.60 | 795.08 | 507.98 | 0.00 | 0.00 | 0.00 |
March | 706.10 | 391.90 | 314.20 | 758.91 | 370.38 | 0.00 | 0.00 | 0.00 |
April | 547.91 | 216.66 | 331.25 | 609.48 | 273.44 | 0.00 | 0.00 | 0.00 |
May | 480.16 | 100.15 | 380.01 | 570.95 | 170.30 | 0.00 | 0.00 | 0.00 |
June | 450.62 | 68.88 | 381.74 | 602.09 | 95.19 | 0.00 | 0.00 | 0.00 |
July | 472.34 | 82.04 | 390.29 | 689.32 | 52.55 | 0.00 | 0.00 | 0.00 |
August | 630.75 | 233.96 | 396.80 | 920.95 | 79.53 | 0.00 | 0.00 | 0.00 |
September | 684.38 | 353.99 | 330.39 | 891.18 | 156.56 | 0.00 | 0.00 | 0.00 |
October | 937.54 | 587.91 | 349.64 | 1141.16 | 286.31 | 0.00 | 0.00 | 0.00 |
November | 650.11 | 390.42 | 259.69 | 691.10 | 389.98 | 0.00 | 0.00 | 0.00 |
December | 643.14 | 456.59 | 186.55 | 661.27 | 474.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.88 | 314.73 | 316.14 | 743.96 | 278.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.62 | 68.88 | 186.55 | 570.95 | 52.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 937.54 | 587.91 | 396.80 | 1141.16 | 507.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 593.38 | 388.55 | 204.83 | 595.07 | 498.18 | 0.00 | 0.00 | 0.00 |
February | 782.65 | 518.05 | 264.60 | 795.08 | 507.98 | 0.00 | 0.00 | 0.00 |
March | 706.10 | 391.90 | 314.20 | 758.91 | 370.38 | 0.00 | 0.00 | 0.00 |
April | 547.91 | 216.66 | 331.25 | 609.48 | 273.44 | 0.00 | 0.00 | 0.00 |
May | 480.16 | 100.15 | 380.01 | 570.95 | 170.30 | 0.00 | 0.00 | 0.00 |
June | 450.62 | 68.88 | 381.74 | 602.09 | 95.19 | 0.00 | 0.00 | 0.00 |
July | 472.34 | 82.04 | 390.29 | 689.32 | 52.55 | 0.00 | 0.00 | 0.00 |
August | 630.75 | 233.96 | 396.80 | 920.95 | 79.53 | 0.00 | 0.00 | 0.00 |
September | 684.38 | 353.99 | 330.39 | 891.18 | 156.56 | 0.00 | 0.00 | 0.00 |
October | 937.54 | 587.91 | 349.64 | 1141.16 | 286.31 | 0.00 | 0.00 | 0.00 |
November | 650.11 | 390.42 | 259.69 | 691.10 | 389.98 | 0.00 | 0.00 | 0.00 |
December | 643.14 | 456.59 | 186.55 | 661.27 | 474.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.88 | 314.73 | 316.14 | 743.96 | 278.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.62 | 68.88 | 186.55 | 570.95 | 52.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 937.54 | 587.91 | 396.80 | 1141.16 | 507.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 593.35 | 388.53 | 204.82 | 595.03 | 498.15 | 0.00 | 0.00 | 0.00 |
February | 782.60 | 518.02 | 264.58 | 795.03 | 507.95 | 0.00 | 0.00 | 0.00 |
March | 706.06 | 391.87 | 314.18 | 758.86 | 370.35 | 0.00 | 0.00 | 0.00 |
April | 547.87 | 216.65 | 331.23 | 609.44 | 273.43 | 0.00 | 0.00 | 0.00 |
May | 480.13 | 100.15 | 379.98 | 570.91 | 170.29 | 0.00 | 0.00 | 0.00 |
June | 450.59 | 68.88 | 381.71 | 602.05 | 95.18 | 0.00 | 0.00 | 0.00 |
July | 472.31 | 82.04 | 390.27 | 689.27 | 52.55 | 0.00 | 0.00 | 0.00 |
August | 630.71 | 233.94 | 396.77 | 920.89 | 79.53 | 0.00 | 0.00 | 0.00 |
September | 684.34 | 353.97 | 330.37 | 891.12 | 156.55 | 0.00 | 0.00 | 0.00 |
October | 937.48 | 587.87 | 349.61 | 1141.09 | 286.30 | 0.00 | 0.00 | 0.00 |
November | 650.06 | 390.39 | 259.67 | 691.06 | 389.96 | 0.00 | 0.00 | 0.00 |
December | 643.10 | 456.56 | 186.54 | 661.22 | 474.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 630.84 | 314.71 | 316.12 | 743.91 | 278.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.59 | 68.88 | 186.54 | 570.91 | 52.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 937.48 | 587.87 | 396.77 | 1141.09 | 507.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.07 | 186.40 | 268.67 | 295.92 | 1015.02 | 0.00 | 0.00 | 0.00 |
February | 671.07 | 294.74 | 376.34 | 481.59 | 1039.84 | 0.00 | 0.00 | 0.00 |
March | 990.92 | 457.48 | 533.44 | 917.98 | 706.59 | 0.00 | 0.00 | 0.00 |
April | 1083.03 | 463.40 | 619.63 | 1125.14 | 520.35 | 0.00 | 0.00 | 0.00 |
May | 1261.62 | 479.11 | 782.51 | 1473.00 | 334.48 | 0.00 | 0.00 | 0.00 |
June | 1380.80 | 556.92 | 823.89 | 1783.87 | 194.64 | 0.00 | 0.00 | 0.00 |
July | 1293.20 | 486.98 | 806.22 | 1783.26 | 110.26 | 0.00 | 0.00 | 0.00 |
August | 1430.63 | 662.28 | 768.34 | 1965.43 | 157.03 | 0.00 | 0.00 | 0.00 |
September | 1015.63 | 443.83 | 571.81 | 1254.80 | 292.95 | 0.00 | 0.00 | 0.00 |
October | 1006.92 | 489.64 | 517.28 | 1121.84 | 535.96 | 0.00 | 0.00 | 0.00 |
November | 472.85 | 136.66 | 336.19 | 332.67 | 762.99 | 0.00 | 0.00 | 0.00 |
December | 420.59 | 181.99 | 238.60 | 275.93 | 969.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 958.87 | 404.21 | 554.66 | 1071.82 | 550.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 420.59 | 136.66 | 238.60 | 275.93 | 110.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1430.63 | 662.28 | 823.89 | 1965.43 | 1039.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.99 | 7.37 | 10.62 | 11.70 | 40.13 | 0.00 | 0.00 | 0.00 |
February | 26.53 | 11.65 | 14.88 | 19.04 | 41.11 | 0.00 | 0.00 | 0.00 |
March | 39.18 | 18.09 | 21.09 | 36.30 | 27.94 | 0.00 | 0.00 | 0.00 |
April | 42.82 | 18.32 | 24.50 | 44.49 | 20.57 | 0.00 | 0.00 | 0.00 |
May | 49.88 | 18.94 | 30.94 | 58.24 | 13.23 | 0.00 | 0.00 | 0.00 |
June | 54.60 | 22.02 | 32.58 | 70.53 | 7.70 | 0.00 | 0.00 | 0.00 |
July | 51.13 | 19.25 | 31.88 | 70.51 | 4.36 | 0.00 | 0.00 | 0.00 |
August | 56.57 | 26.19 | 30.38 | 77.71 | 6.21 | 0.00 | 0.00 | 0.00 |
September | 40.16 | 17.55 | 22.61 | 49.61 | 11.58 | 0.00 | 0.00 | 0.00 |
October | 39.81 | 19.36 | 20.45 | 44.36 | 21.19 | 0.00 | 0.00 | 0.00 |
November | 18.70 | 5.40 | 13.29 | 13.15 | 30.17 | 0.00 | 0.00 | 0.00 |
December | 16.63 | 7.20 | 9.43 | 10.91 | 38.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.91 | 15.98 | 21.93 | 42.38 | 21.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.63 | 5.40 | 9.43 | 10.91 | 4.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.57 | 26.19 | 32.58 | 77.71 | 41.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.10 | 0.00 | 344.10 | 31.99 | 1657.05 | 0.00 | 0.00 | 0.00 |
February | 470.89 | 0.00 | 470.89 | 56.22 | 1722.07 | 0.00 | 0.00 | 0.00 |
March | 653.01 | 0.00 | 653.01 | 261.82 | 1157.13 | 0.00 | 0.00 | 0.00 |
April | 784.35 | 2.23 | 782.12 | 514.69 | 829.29 | 0.00 | 0.00 | 0.00 |
May | 1040.58 | 34.67 | 1005.91 | 980.66 | 517.77 | 0.00 | 0.00 | 0.00 |
June | 1103.53 | 59.30 | 1044.23 | 1337.97 | 286.98 | 0.00 | 0.00 | 0.00 |
July | 1066.45 | 38.57 | 1027.89 | 1472.27 | 162.45 | 0.00 | 0.00 | 0.00 |
August | 944.83 | 11.24 | 933.58 | 1287.43 | 220.69 | 0.00 | 0.00 | 0.00 |
September | 712.24 | 0.13 | 712.11 | 752.89 | 437.65 | 0.00 | 0.00 | 0.00 |
October | 616.39 | 0.00 | 616.39 | 462.15 | 799.31 | 0.00 | 0.00 | 0.00 |
November | 432.34 | 0.00 | 432.34 | 137.32 | 1190.71 | 0.00 | 0.00 | 0.00 |
December | 300.15 | 0.00 | 300.15 | 19.64 | 1557.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 707.10 | 12.24 | 694.85 | 613.30 | 873.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 300.15 | 0.00 | 300.15 | 19.64 | 162.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1103.53 | 59.30 | 1044.23 | 1472.27 | 1722.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 479.19 | 192.12 | 287.08 | 305.48 | 1030.85 | 0.00 | 0.00 | 0.00 |
February | 743.12 | 346.67 | 396.46 | 530.52 | 1038.80 | 0.00 | 0.00 | 0.00 |
March | 947.99 | 403.19 | 544.81 | 834.93 | 742.04 | 0.00 | 0.00 | 0.00 |
April | 1137.66 | 498.33 | 639.33 | 1147.98 | 531.69 | 0.00 | 0.00 | 0.00 |
May | 1379.74 | 551.43 | 828.32 | 1576.65 | 344.17 | 0.00 | 0.00 | 0.00 |
June | 1278.73 | 462.89 | 815.84 | 1629.15 | 190.13 | 0.00 | 0.00 | 0.00 |
July | 1284.33 | 463.48 | 820.85 | 1764.32 | 105.62 | 0.00 | 0.00 | 0.00 |
August | 1446.18 | 652.08 | 794.10 | 1973.42 | 144.23 | 0.00 | 0.00 | 0.00 |
September | 1078.57 | 483.91 | 594.66 | 1317.81 | 276.38 | 0.00 | 0.00 | 0.00 |
October | 977.80 | 443.17 | 534.63 | 1071.60 | 508.36 | 0.00 | 0.00 | 0.00 |
November | 604.70 | 232.21 | 372.49 | 494.87 | 743.72 | 0.00 | 0.00 | 0.00 |
December | 471.09 | 221.20 | 249.90 | 323.20 | 959.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.33 | 413.02 | 574.30 | 1084.62 | 548.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.09 | 192.12 | 249.90 | 305.48 | 105.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1446.18 | 652.08 | 828.32 | 1973.42 | 1038.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1780.09 | 1165.62 | 614.48 | 1741.96 | 1499.62 | 0.00 | 0.00 | 0.00 |
February | 2347.88 | 1554.11 | 793.78 | 2330.21 | 1525.41 | 0.00 | 0.00 | 0.00 |
March | 2118.24 | 1175.66 | 942.58 | 2219.94 | 1132.39 | 0.00 | 0.00 | 0.00 |
April | 1643.68 | 649.96 | 993.72 | 1780.20 | 852.55 | 0.00 | 0.00 | 0.00 |
May | 1440.44 | 300.45 | 1139.99 | 1656.54 | 549.05 | 0.00 | 0.00 | 0.00 |
June | 1351.81 | 206.64 | 1145.17 | 1776.44 | 302.70 | 0.00 | 0.00 | 0.00 |
July | 1416.97 | 246.13 | 1170.84 | 2052.29 | 164.49 | 0.00 | 0.00 | 0.00 |
August | 1892.20 | 701.85 | 1190.36 | 2755.46 | 232.11 | 0.00 | 0.00 | 0.00 |
September | 2053.08 | 1061.93 | 991.14 | 2665.46 | 446.15 | 0.00 | 0.00 | 0.00 |
October | 2812.54 | 1763.66 | 1048.88 | 3412.70 | 801.02 | 0.00 | 0.00 | 0.00 |
November | 1950.25 | 1171.22 | 779.04 | 2051.33 | 1125.54 | 0.00 | 0.00 | 0.00 |
December | 1929.35 | 1369.71 | 559.64 | 1954.57 | 1394.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1892.58 | 944.17 | 948.40 | 2200.13 | 831.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1351.81 | 206.64 | 559.64 | 1656.54 | 164.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2812.54 | 1763.66 | 1190.36 | 3412.70 | 1525.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.07 | 193.77 | 279.30 | 301.87 | 1053.59 | 0.00 | 0.00 | 0.00 |
February | 697.61 | 306.39 | 391.22 | 489.49 | 1085.26 | 0.00 | 0.00 | 0.00 |
March | 1030.11 | 475.57 | 554.54 | 935.73 | 743.36 | 0.00 | 0.00 | 0.00 |
April | 1125.86 | 481.73 | 644.13 | 1150.15 | 551.55 | 0.00 | 0.00 | 0.00 |
May | 1311.51 | 498.06 | 813.45 | 1508.63 | 360.55 | 0.00 | 0.00 | 0.00 |
June | 1435.41 | 578.94 | 856.47 | 1841.83 | 204.72 | 0.00 | 0.00 | 0.00 |
July | 1344.34 | 506.24 | 838.10 | 1845.65 | 114.84 | 0.00 | 0.00 | 0.00 |
August | 1487.20 | 688.48 | 798.73 | 2039.78 | 157.65 | 0.00 | 0.00 | 0.00 |
September | 1055.80 | 461.38 | 594.42 | 1305.69 | 291.95 | 0.00 | 0.00 | 0.00 |
October | 1046.74 | 509.00 | 537.74 | 1170.62 | 528.54 | 0.00 | 0.00 | 0.00 |
November | 491.55 | 142.06 | 349.49 | 347.28 | 765.92 | 0.00 | 0.00 | 0.00 |
December | 437.22 | 189.19 | 248.03 | 284.38 | 988.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 996.79 | 420.20 | 576.59 | 1106.14 | 567.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 437.22 | 142.06 | 248.03 | 284.38 | 114.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1487.20 | 688.48 | 856.47 | 2039.78 | 1085.26 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921647E+09 | 0.00 | 0.921647E+09 | 96126365.23 | 0.423906E+10 |
February | 0.113918E+10 | 0.00 | 0.113918E+10 | 0.150662E+09 | 0.395911E+10 |
March | 0.174902E+10 | 0.00 | 0.174902E+10 | 0.737180E+09 | 0.289873E+10 |
April | 0.203304E+10 | 5782587.89 | 0.202726E+10 | 0.137888E+10 | 0.200005E+10 |
May | 0.278710E+10 | 92867775.32 | 0.269423E+10 | 0.266275E+10 | 0.130963E+10 |
June | 0.286034E+10 | 0.153698E+09 | 0.270664E+10 | 0.346700E+10 | 0.714136E+09 |
July | 0.285638E+10 | 0.103296E+09 | 0.275309E+10 | 0.392834E+10 | 0.422841E+09 |
August | 0.253062E+10 | 30117947.12 | 0.250050E+10 | 0.344164E+10 | 0.569386E+09 |
September | 0.184613E+10 | 345705.13 | 0.184578E+10 | 0.197238E+10 | 0.105848E+10 |
October | 0.165095E+10 | 0.00 | 0.165095E+10 | 0.129458E+10 | 0.196778E+10 |
November | 0.112063E+10 | 0.00 | 0.112063E+10 | 0.403043E+09 | 0.284175E+10 |
December | 0.803921E+09 | 0.00 | 0.803921E+09 | 66450853.79 | 0.390066E+10 |
Annual Sum or Average | 0.222990E+11 | 0.386109E+09 | 0.219128E+11 | 0.195990E+11 | 0.258816E+11 |
Minimum of Months | 0.803921E+09 | 0.00 | 0.803921E+09 | 66450853.79 | 0.422841E+09 |
Maximum of Months | 0.286034E+10 | 0.153698E+09 | 0.275309E+10 | 0.392834E+10 | 0.423906E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128347E+10 | 0.514566E+09 | 0.768902E+09 | 0.833160E+09 | 0.263635E+10 |
February | 0.179776E+10 | 0.838656E+09 | 0.959109E+09 | 0.130724E+10 | 0.238668E+10 |
March | 0.253911E+10 | 0.107990E+10 | 0.145921E+10 | 0.226184E+10 | 0.186777E+10 |
April | 0.294881E+10 | 0.129167E+10 | 0.165715E+10 | 0.299861E+10 | 0.129642E+10 |
May | 0.369550E+10 | 0.147694E+10 | 0.221856E+10 | 0.423389E+10 | 0.877474E+09 |
June | 0.331447E+10 | 0.119981E+10 | 0.211466E+10 | 0.421699E+10 | 0.475132E+09 |
July | 0.343994E+10 | 0.124139E+10 | 0.219856E+10 | 0.471119E+10 | 0.275623E+09 |
August | 0.387346E+10 | 0.174654E+10 | 0.212692E+10 | 0.527445E+10 | 0.374453E+09 |
September | 0.279566E+10 | 0.125430E+10 | 0.154136E+10 | 0.342328E+10 | 0.675551E+09 |
October | 0.261895E+10 | 0.118700E+10 | 0.143196E+10 | 0.289947E+10 | 0.126658E+10 |
November | 0.156737E+10 | 0.601886E+09 | 0.965487E+09 | 0.132089E+10 | 0.178937E+10 |
December | 0.126178E+10 | 0.592451E+09 | 0.669324E+09 | 0.890060E+09 | 0.240617E+10 |
Annual Sum or Average | 0.311363E+11 | 0.130251E+11 | 0.181112E+11 | 0.343711E+11 | 0.163276E+11 |
Minimum of Months | 0.126178E+10 | 0.514566E+09 | 0.669324E+09 | 0.833160E+09 | 0.275623E+09 |
Maximum of Months | 0.387346E+10 | 0.174654E+10 | 0.221856E+10 | 0.527445E+10 | 0.263635E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476780E+10 | 0.312199E+10 | 0.164582E+10 | 0.469672E+10 | 0.382052E+10 |
February | 0.568000E+10 | 0.375969E+10 | 0.192031E+10 | 0.568293E+10 | 0.349408E+10 |
March | 0.567348E+10 | 0.314887E+10 | 0.252461E+10 | 0.598054E+10 | 0.284419E+10 |
April | 0.426041E+10 | 0.168469E+10 | 0.257572E+10 | 0.464682E+10 | 0.206928E+10 |
May | 0.385808E+10 | 0.804731E+09 | 0.305335E+10 | 0.445899E+10 | 0.138811E+10 |
June | 0.350390E+10 | 0.535604E+09 | 0.296829E+10 | 0.459984E+10 | 0.751057E+09 |
July | 0.379521E+10 | 0.659224E+09 | 0.313599E+10 | 0.547953E+10 | 0.425387E+09 |
August | 0.506808E+10 | 0.187983E+10 | 0.318825E+10 | 0.736588E+10 | 0.599141E+09 |
September | 0.532158E+10 | 0.275253E+10 | 0.256905E+10 | 0.691922E+10 | 0.108728E+10 |
October | 0.753311E+10 | 0.472379E+10 | 0.280931E+10 | 0.917308E+10 | 0.199681E+10 |
November | 0.505506E+10 | 0.303580E+10 | 0.201926E+10 | 0.537938E+10 | 0.269974E+10 |
December | 0.516758E+10 | 0.366864E+10 | 0.149895E+10 | 0.528944E+10 | 0.349174E+10 |
Annual Sum or Average | 0.596843E+11 | 0.297754E+11 | 0.299089E+11 | 0.696724E+11 | 0.246673E+11 |
Minimum of Months | 0.350390E+10 | 0.535604E+09 | 0.149895E+10 | 0.445899E+10 | 0.425387E+09 |
Maximum of Months | 0.753311E+10 | 0.472379E+10 | 0.318825E+10 | 0.917308E+10 | 0.382052E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126707E+10 | 0.518996E+09 | 0.748077E+09 | 0.818619E+09 | 0.269357E+10 |
February | 0.168766E+10 | 0.741225E+09 | 0.946434E+09 | 0.119904E+10 | 0.249404E+10 |
March | 0.275904E+10 | 0.127377E+10 | 0.148527E+10 | 0.252712E+10 | 0.186810E+10 |
April | 0.291823E+10 | 0.124863E+10 | 0.166960E+10 | 0.300317E+10 | 0.133939E+10 |
May | 0.351275E+10 | 0.133400E+10 | 0.217875E+10 | 0.405805E+10 | 0.913479E+09 |
June | 0.372058E+10 | 0.150062E+10 | 0.221997E+10 | 0.477195E+10 | 0.508880E+09 |
July | 0.360068E+10 | 0.135590E+10 | 0.224478E+10 | 0.493240E+10 | 0.297371E+09 |
August | 0.398333E+10 | 0.184402E+10 | 0.213931E+10 | 0.545657E+10 | 0.408089E+09 |
September | 0.273663E+10 | 0.119590E+10 | 0.154073E+10 | 0.339802E+10 | 0.709971E+09 |
October | 0.280360E+10 | 0.136332E+10 | 0.144028E+10 | 0.316576E+10 | 0.131229E+10 |
November | 0.127409E+10 | 0.368220E+09 | 0.905870E+09 | 0.931239E+09 | 0.183764E+10 |
December | 0.117105E+10 | 0.506717E+09 | 0.664336E+09 | 0.777860E+09 | 0.247662E+10 |
Annual Sum or Average | 0.314347E+11 | 0.132513E+11 | 0.181834E+11 | 0.350398E+11 | 0.168594E+11 |
Minimum of Months | 0.117105E+10 | 0.368220E+09 | 0.664336E+09 | 0.777860E+09 | 0.297371E+09 |
Maximum of Months | 0.398333E+10 | 0.184402E+10 | 0.224478E+10 | 0.545657E+10 | 0.269357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307201E+09 | 0.00 | 0.307201E+09 | 30279325.52 | 0.147363E+10 |
February | 0.379709E+09 | 0.00 | 0.379709E+09 | 49851778.71 | 0.136782E+10 |
March | 0.582977E+09 | 0.00 | 0.582977E+09 | 0.253499E+09 | 0.997579E+09 |
April | 0.677647E+09 | 1927438.10 | 0.675720E+09 | 0.472813E+09 | 0.681120E+09 |
May | 0.928990E+09 | 30954460.52 | 0.898035E+09 | 0.914302E+09 | 0.431920E+09 |
June | 0.953402E+09 | 51230279.77 | 0.902172E+09 | 0.117680E+10 | 0.233009E+09 |
July | 0.952083E+09 | 34430508.61 | 0.917653E+09 | 0.132956E+10 | 0.134365E+09 |
August | 0.843500E+09 | 10038840.73 | 0.833461E+09 | 0.115713E+10 | 0.190710E+09 |
September | 0.615347E+09 | 115229.59 | 0.615232E+09 | 0.652603E+09 | 0.381963E+09 |
October | 0.550290E+09 | 0.00 | 0.550290E+09 | 0.410687E+09 | 0.731621E+09 |
November | 0.373525E+09 | 0.00 | 0.373525E+09 | 0.115535E+09 | 0.106099E+10 |
December | 0.267961E+09 | 0.00 | 0.267961E+09 | 17460679.76 | 0.140762E+10 |
Annual Sum or Average | 0.743263E+10 | 0.128697E+09 | 0.730394E+10 | 0.658052E+10 | 0.909235E+10 |
Minimum of Months | 0.267961E+09 | 0.00 | 0.267961E+09 | 17460679.76 | 0.134365E+09 |
Maximum of Months | 0.953402E+09 | 51230279.77 | 0.917653E+09 | 0.132956E+10 | 0.147363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307221E+09 | 0.00 | 0.307221E+09 | 30281239.13 | 0.147373E+10 |
February | 0.379733E+09 | 0.00 | 0.379733E+09 | 49854929.26 | 0.136791E+10 |
March | 0.583014E+09 | 0.00 | 0.583014E+09 | 0.253515E+09 | 0.997642E+09 |
April | 0.677690E+09 | 1927559.91 | 0.675763E+09 | 0.472843E+09 | 0.681163E+09 |
May | 0.929048E+09 | 30956416.79 | 0.898092E+09 | 0.914360E+09 | 0.431948E+09 |
June | 0.953462E+09 | 51233517.44 | 0.902229E+09 | 0.117687E+10 | 0.233024E+09 |
July | 0.952143E+09 | 34432684.56 | 0.917711E+09 | 0.132965E+10 | 0.134373E+09 |
August | 0.843554E+09 | 10039475.16 | 0.833514E+09 | 0.115720E+10 | 0.190722E+09 |
September | 0.615386E+09 | 115236.87 | 0.615271E+09 | 0.652644E+09 | 0.381987E+09 |
October | 0.550325E+09 | 0.00 | 0.550325E+09 | 0.410713E+09 | 0.731667E+09 |
November | 0.373549E+09 | 0.00 | 0.373549E+09 | 0.115542E+09 | 0.106106E+10 |
December | 0.267978E+09 | 0.00 | 0.267978E+09 | 17461783.24 | 0.140771E+10 |
Annual Sum or Average | 0.743310E+10 | 0.128705E+09 | 0.730440E+10 | 0.658094E+10 | 0.909293E+10 |
Minimum of Months | 0.267978E+09 | 0.00 | 0.267978E+09 | 17461783.24 | 0.134373E+09 |
Maximum of Months | 0.953462E+09 | 51233517.44 | 0.917711E+09 | 0.132965E+10 | 0.147373E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307221E+09 | 0.00 | 0.307221E+09 | 30281239.13 | 0.147373E+10 |
February | 0.379733E+09 | 0.00 | 0.379733E+09 | 49854929.26 | 0.136791E+10 |
March | 0.583014E+09 | 0.00 | 0.583014E+09 | 0.253515E+09 | 0.997642E+09 |
April | 0.677690E+09 | 1927559.91 | 0.675763E+09 | 0.472843E+09 | 0.681163E+09 |
May | 0.929048E+09 | 30956416.79 | 0.898092E+09 | 0.914360E+09 | 0.431948E+09 |
June | 0.953462E+09 | 51233517.44 | 0.902229E+09 | 0.117687E+10 | 0.233024E+09 |
July | 0.952143E+09 | 34432684.56 | 0.917711E+09 | 0.132965E+10 | 0.134373E+09 |
August | 0.843554E+09 | 10039475.16 | 0.833514E+09 | 0.115720E+10 | 0.190722E+09 |
September | 0.615386E+09 | 115236.87 | 0.615271E+09 | 0.652644E+09 | 0.381987E+09 |
October | 0.550325E+09 | 0.00 | 0.550325E+09 | 0.410713E+09 | 0.731667E+09 |
November | 0.373549E+09 | 0.00 | 0.373549E+09 | 0.115542E+09 | 0.106106E+10 |
December | 0.267978E+09 | 0.00 | 0.267978E+09 | 17461783.24 | 0.140771E+10 |
Annual Sum or Average | 0.743310E+10 | 0.128705E+09 | 0.730440E+10 | 0.658094E+10 | 0.909293E+10 |
Minimum of Months | 0.267978E+09 | 0.00 | 0.267978E+09 | 17461783.24 | 0.134373E+09 |
Maximum of Months | 0.953462E+09 | 51233517.44 | 0.917711E+09 | 0.132965E+10 | 0.147373E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123464E+10 | 0.494989E+09 | 0.739652E+09 | 0.799354E+09 | 0.266388E+10 |
February | 0.172937E+10 | 0.806750E+09 | 0.922623E+09 | 0.125594E+10 | 0.241208E+10 |
March | 0.244251E+10 | 0.103881E+10 | 0.140370E+10 | 0.219690E+10 | 0.188415E+10 |
April | 0.283663E+10 | 0.124253E+10 | 0.159411E+10 | 0.291063E+10 | 0.130409E+10 |
May | 0.355492E+10 | 0.142075E+10 | 0.213417E+10 | 0.412311E+10 | 0.860183E+09 |
June | 0.318838E+10 | 0.115416E+10 | 0.203421E+10 | 0.409664E+10 | 0.464208E+09 |
July | 0.330908E+10 | 0.119416E+10 | 0.211492E+10 | 0.456770E+10 | 0.271391E+09 |
August | 0.372610E+10 | 0.168009E+10 | 0.204601E+10 | 0.509647E+10 | 0.386252E+09 |
September | 0.268930E+10 | 0.120658E+10 | 0.148272E+10 | 0.328665E+10 | 0.724299E+09 |
October | 0.251932E+10 | 0.114184E+10 | 0.137748E+10 | 0.275336E+10 | 0.138425E+10 |
November | 0.150775E+10 | 0.578987E+09 | 0.928758E+09 | 0.122435E+10 | 0.193678E+10 |
December | 0.121377E+10 | 0.569911E+09 | 0.643862E+09 | 0.834965E+09 | 0.252526E+10 |
Annual Sum or Average | 0.299518E+11 | 0.125296E+11 | 0.174222E+11 | 0.331461E+11 | 0.168168E+11 |
Minimum of Months | 0.121377E+10 | 0.494989E+09 | 0.643862E+09 | 0.799354E+09 | 0.271391E+09 |
Maximum of Months | 0.372610E+10 | 0.168009E+10 | 0.213417E+10 | 0.509647E+10 | 0.266388E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48816610.02 | 19571431.67 | 29245178.35 | 31605733.75 | 0.105327E+09 |
February | 68377843.85 | 31898158.95 | 36479684.90 | 49658622.62 | 95371548.89 |
March | 96574836.40 | 41073740.71 | 55501095.69 | 86863417.48 | 74497699.10 |
April | 0.112158E+09 | 49128376.49 | 63029535.44 | 0.115084E+09 | 51562473.63 |
May | 0.140558E+09 | 56175208.88 | 84382965.61 | 0.163024E+09 | 34010857.34 |
June | 0.126066E+09 | 45634558.75 | 80431016.34 | 0.161977E+09 | 18354352.20 |
July | 0.130838E+09 | 47215924.70 | 83622110.27 | 0.180603E+09 | 10730547.90 |
August | 0.147327E+09 | 66429269.15 | 80897467.32 | 0.201510E+09 | 15272069.96 |
September | 0.106333E+09 | 47707027.62 | 58625578.25 | 0.129951E+09 | 28638122.85 |
October | 99611656.57 | 45147166.62 | 54464489.95 | 0.108865E+09 | 54732164.77 |
November | 59614900.85 | 22892630.34 | 36722270.51 | 48409627.92 | 76578441.37 |
December | 47991507.80 | 22533778.32 | 25457729.49 | 33013774.05 | 99846658.59 |
Annual Sum or Average | 0.118427E+10 | 0.495407E+09 | 0.688859E+09 | 0.131057E+10 | 0.664922E+09 |
Minimum of Months | 47991507.80 | 19571431.67 | 25457729.49 | 31605733.75 | 10730547.90 |
Maximum of Months | 0.147327E+09 | 66429269.15 | 84382965.61 | 0.201510E+09 | 0.105327E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158932E+10 | 0.104070E+10 | 0.548622E+09 | 0.159383E+10 | 0.133433E+10 |
February | 0.189339E+10 | 0.125327E+10 | 0.640120E+09 | 0.192345E+10 | 0.122891E+10 |
March | 0.189122E+10 | 0.104966E+10 | 0.841560E+09 | 0.203267E+10 | 0.992019E+09 |
April | 0.142018E+10 | 0.561582E+09 | 0.858598E+09 | 0.157977E+10 | 0.708769E+09 |
May | 0.128606E+10 | 0.268252E+09 | 0.101781E+10 | 0.152923E+10 | 0.456122E+09 |
June | 0.116800E+10 | 0.178541E+09 | 0.989458E+09 | 0.156061E+10 | 0.246723E+09 |
July | 0.126511E+10 | 0.219749E+09 | 0.104536E+10 | 0.184627E+10 | 0.140762E+09 |
August | 0.168941E+10 | 0.626630E+09 | 0.106278E+10 | 0.246667E+10 | 0.213024E+09 |
September | 0.177391E+10 | 0.917540E+09 | 0.856373E+09 | 0.230993E+10 | 0.405797E+09 |
October | 0.251111E+10 | 0.157465E+10 | 0.936465E+09 | 0.305648E+10 | 0.766866E+09 |
November | 0.168507E+10 | 0.101197E+10 | 0.673106E+09 | 0.179134E+10 | 0.101083E+10 |
December | 0.172258E+10 | 0.122292E+10 | 0.499664E+09 | 0.177113E+10 | 0.126989E+10 |
Annual Sum or Average | 0.198954E+11 | 0.992546E+10 | 0.996991E+10 | 0.234614E+11 | 0.877405E+10 |
Minimum of Months | 0.116800E+10 | 0.178541E+09 | 0.499664E+09 | 0.152923E+10 | 0.140762E+09 |
Maximum of Months | 0.251111E+10 | 0.157465E+10 | 0.106278E+10 | 0.305648E+10 | 0.133433E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158932E+10 | 0.104070E+10 | 0.548622E+09 | 0.159383E+10 | 0.133433E+10 |
February | 0.189339E+10 | 0.125327E+10 | 0.640120E+09 | 0.192345E+10 | 0.122891E+10 |
March | 0.189122E+10 | 0.104966E+10 | 0.841560E+09 | 0.203267E+10 | 0.992019E+09 |
April | 0.142018E+10 | 0.561582E+09 | 0.858598E+09 | 0.157977E+10 | 0.708769E+09 |
May | 0.128606E+10 | 0.268252E+09 | 0.101781E+10 | 0.152923E+10 | 0.456122E+09 |
June | 0.116800E+10 | 0.178541E+09 | 0.989458E+09 | 0.156061E+10 | 0.246723E+09 |
July | 0.126511E+10 | 0.219749E+09 | 0.104536E+10 | 0.184627E+10 | 0.140762E+09 |
August | 0.168941E+10 | 0.626630E+09 | 0.106278E+10 | 0.246667E+10 | 0.213024E+09 |
September | 0.177391E+10 | 0.917540E+09 | 0.856373E+09 | 0.230993E+10 | 0.405797E+09 |
October | 0.251111E+10 | 0.157465E+10 | 0.936465E+09 | 0.305648E+10 | 0.766866E+09 |
November | 0.168507E+10 | 0.101197E+10 | 0.673106E+09 | 0.179134E+10 | 0.101083E+10 |
December | 0.172258E+10 | 0.122292E+10 | 0.499664E+09 | 0.177113E+10 | 0.126989E+10 |
Annual Sum or Average | 0.198954E+11 | 0.992546E+10 | 0.996991E+10 | 0.234614E+11 | 0.877405E+10 |
Minimum of Months | 0.116800E+10 | 0.178541E+09 | 0.499664E+09 | 0.152923E+10 | 0.140762E+09 |
Maximum of Months | 0.251111E+10 | 0.157465E+10 | 0.106278E+10 | 0.305648E+10 | 0.133433E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158922E+10 | 0.104063E+10 | 0.548587E+09 | 0.159372E+10 | 0.133425E+10 |
February | 0.189327E+10 | 0.125319E+10 | 0.640080E+09 | 0.192333E+10 | 0.122884E+10 |
March | 0.189110E+10 | 0.104959E+10 | 0.841506E+09 | 0.203254E+10 | 0.991957E+09 |
April | 0.142009E+10 | 0.561546E+09 | 0.858544E+09 | 0.157967E+10 | 0.708725E+09 |
May | 0.128598E+10 | 0.268235E+09 | 0.101775E+10 | 0.152913E+10 | 0.456094E+09 |
June | 0.116792E+10 | 0.178529E+09 | 0.989395E+09 | 0.156051E+10 | 0.246708E+09 |
July | 0.126503E+10 | 0.219735E+09 | 0.104529E+10 | 0.184615E+10 | 0.140754E+09 |
August | 0.168930E+10 | 0.626590E+09 | 0.106271E+10 | 0.246652E+10 | 0.213011E+09 |
September | 0.177380E+10 | 0.917482E+09 | 0.856318E+09 | 0.230979E+10 | 0.405771E+09 |
October | 0.251096E+10 | 0.157455E+10 | 0.936406E+09 | 0.305629E+10 | 0.766817E+09 |
November | 0.168497E+10 | 0.101190E+10 | 0.673064E+09 | 0.179122E+10 | 0.101077E+10 |
December | 0.172247E+10 | 0.122284E+10 | 0.499632E+09 | 0.177102E+10 | 0.126981E+10 |
Annual Sum or Average | 0.198941E+11 | 0.992483E+10 | 0.996928E+10 | 0.234599E+11 | 0.877350E+10 |
Minimum of Months | 0.116792E+10 | 0.178529E+09 | 0.499632E+09 | 0.152913E+10 | 0.140754E+09 |
Maximum of Months | 0.251096E+10 | 0.157455E+10 | 0.106271E+10 | 0.305629E+10 | 0.133425E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121887E+10 | 0.499251E+09 | 0.719619E+09 | 0.792601E+09 | 0.271864E+10 |
February | 0.162346E+10 | 0.713025E+09 | 0.910431E+09 | 0.116507E+10 | 0.251558E+10 |
March | 0.265408E+10 | 0.122531E+10 | 0.142877E+10 | 0.245872E+10 | 0.189253E+10 |
April | 0.280721E+10 | 0.120113E+10 | 0.160608E+10 | 0.291635E+10 | 0.134874E+10 |
May | 0.337912E+10 | 0.128325E+10 | 0.209587E+10 | 0.394529E+10 | 0.895871E+09 |
June | 0.357905E+10 | 0.144352E+10 | 0.213552E+10 | 0.462379E+10 | 0.504510E+09 |
July | 0.346370E+10 | 0.130432E+10 | 0.215938E+10 | 0.477629E+10 | 0.295322E+09 |
August | 0.383179E+10 | 0.177386E+10 | 0.205793E+10 | 0.526420E+10 | 0.420594E+09 |
September | 0.263252E+10 | 0.115040E+10 | 0.148212E+10 | 0.325245E+10 | 0.759323E+09 |
October | 0.269694E+10 | 0.131145E+10 | 0.138549E+10 | 0.300473E+10 | 0.143550E+10 |
November | 0.122562E+10 | 0.354211E+09 | 0.871410E+09 | 0.862275E+09 | 0.197767E+10 |
December | 0.112650E+10 | 0.487439E+09 | 0.639064E+09 | 0.739039E+09 | 0.259648E+10 |
Annual Sum or Average | 0.302389E+11 | 0.127472E+11 | 0.174917E+11 | 0.338008E+11 | 0.173608E+11 |
Minimum of Months | 0.112650E+10 | 0.354211E+09 | 0.639064E+09 | 0.739039E+09 | 0.295322E+09 |
Maximum of Months | 0.383179E+10 | 0.177386E+10 | 0.215938E+10 | 0.526420E+10 | 0.271864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48192870.27 | 19739859.52 | 28453010.75 | 31338588.02 | 0.107493E+09 |
February | 64189823.94 | 28192283.68 | 35997540.26 | 46065726.23 | 99463953.95 |
March | 0.104940E+09 | 48447499.64 | 56492071.91 | 97215298.30 | 74828793.55 |
April | 0.110994E+09 | 47491376.34 | 63502944.38 | 0.115310E+09 | 53327834.33 |
May | 0.133607E+09 | 50738496.52 | 82868556.05 | 0.155993E+09 | 35421934.40 |
June | 0.141512E+09 | 57075478.25 | 84436382.93 | 0.182820E+09 | 19947869.72 |
July | 0.136951E+09 | 51571336.09 | 85379918.41 | 0.188850E+09 | 11676740.48 |
August | 0.151505E+09 | 70136614.69 | 81368664.64 | 0.208141E+09 | 16629880.19 |
September | 0.104087E+09 | 45485600.08 | 58601534.98 | 0.128599E+09 | 30022911.17 |
October | 0.106634E+09 | 51853446.60 | 54780906.06 | 0.118804E+09 | 56758507.03 |
November | 48459817.94 | 14005154.00 | 34454663.94 | 34093445.61 | 78195158.83 |
December | 44540787.86 | 19272842.93 | 25267944.93 | 29220812.06 | 0.102662E+09 |
Annual Sum or Average | 0.119561E+10 | 0.504010E+09 | 0.691604E+09 | 0.133645E+10 | 0.686429E+09 |
Minimum of Months | 44540787.86 | 14005154.00 | 25267944.93 | 29220812.06 | 11676740.48 |
Maximum of Months | 0.151505E+09 | 70136614.69 | 85379918.41 | 0.208141E+09 | 0.107493E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921647E+09 | 0.00 | 0.921647E+09 | 85679202.14 | 0.443824E+10 |
February | 0.113918E+10 | 0.00 | 0.113918E+10 | 0.136008E+09 | 0.416603E+10 |
March | 0.174902E+10 | 0.00 | 0.174902E+10 | 0.701265E+09 | 0.309926E+10 |
April | 0.203304E+10 | 5782587.89 | 0.202726E+10 | 0.133408E+10 | 0.214952E+10 |
May | 0.278710E+10 | 92867775.32 | 0.269423E+10 | 0.262661E+10 | 0.138680E+10 |
June | 0.286034E+10 | 0.153698E+09 | 0.270664E+10 | 0.346802E+10 | 0.743851E+09 |
July | 0.285638E+10 | 0.103296E+09 | 0.275309E+10 | 0.394333E+10 | 0.435118E+09 |
August | 0.253062E+10 | 30117947.12 | 0.250050E+10 | 0.344825E+10 | 0.591106E+09 |
September | 0.184613E+10 | 345705.13 | 0.184578E+10 | 0.195150E+10 | 0.113440E+10 |
October | 0.165095E+10 | 0.00 | 0.165095E+10 | 0.123782E+10 | 0.214088E+10 |
November | 0.112063E+10 | 0.00 | 0.112063E+10 | 0.355932E+09 | 0.308632E+10 |
December | 0.803921E+09 | 0.00 | 0.803921E+09 | 52608129.10 | 0.417120E+10 |
Annual Sum or Average | 0.222990E+11 | 0.386109E+09 | 0.219128E+11 | 0.193411E+11 | 0.275427E+11 |
Minimum of Months | 0.803921E+09 | 0.00 | 0.803921E+09 | 52608129.10 | 0.435118E+09 |
Maximum of Months | 0.286034E+10 | 0.153698E+09 | 0.275309E+10 | 0.394333E+10 | 0.443824E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128347E+10 | 0.514566E+09 | 0.768902E+09 | 0.818199E+09 | 0.276104E+10 |
February | 0.179776E+10 | 0.838656E+09 | 0.959109E+09 | 0.128344E+10 | 0.251306E+10 |
March | 0.253911E+10 | 0.107990E+10 | 0.145921E+10 | 0.223628E+10 | 0.198747E+10 |
April | 0.294881E+10 | 0.129167E+10 | 0.165715E+10 | 0.297555E+10 | 0.137815E+10 |
May | 0.369550E+10 | 0.147694E+10 | 0.221856E+10 | 0.422289E+10 | 0.921819E+09 |
June | 0.331447E+10 | 0.119981E+10 | 0.211466E+10 | 0.422276E+10 | 0.492828E+09 |
July | 0.343994E+10 | 0.124139E+10 | 0.219856E+10 | 0.472555E+10 | 0.282885E+09 |
August | 0.387346E+10 | 0.174654E+10 | 0.212692E+10 | 0.528560E+10 | 0.386307E+09 |
September | 0.279566E+10 | 0.125430E+10 | 0.154136E+10 | 0.341577E+10 | 0.716386E+09 |
October | 0.261895E+10 | 0.118700E+10 | 0.143196E+10 | 0.287016E+10 | 0.136159E+10 |
November | 0.156737E+10 | 0.601886E+09 | 0.965487E+09 | 0.128270E+10 | 0.192773E+10 |
December | 0.126178E+10 | 0.592451E+09 | 0.669324E+09 | 0.865665E+09 | 0.256948E+10 |
Annual Sum or Average | 0.311363E+11 | 0.130251E+11 | 0.181112E+11 | 0.342046E+11 | 0.172987E+11 |
Minimum of Months | 0.126178E+10 | 0.514566E+09 | 0.669324E+09 | 0.818199E+09 | 0.282885E+09 |
Maximum of Months | 0.387346E+10 | 0.174654E+10 | 0.221856E+10 | 0.528560E+10 | 0.276104E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.476780E+10 | 0.312199E+10 | 0.164582E+10 | 0.466565E+10 | 0.401659E+10 |
February | 0.568000E+10 | 0.375969E+10 | 0.192031E+10 | 0.563725E+10 | 0.369026E+10 |
March | 0.567348E+10 | 0.314887E+10 | 0.252461E+10 | 0.594589E+10 | 0.303299E+10 |
April | 0.426041E+10 | 0.168469E+10 | 0.257572E+10 | 0.461427E+10 | 0.220981E+10 |
May | 0.385808E+10 | 0.804731E+09 | 0.305335E+10 | 0.443687E+10 | 0.147057E+10 |
June | 0.350390E+10 | 0.535604E+09 | 0.296829E+10 | 0.460453E+10 | 0.784588E+09 |
July | 0.379521E+10 | 0.659224E+09 | 0.313599E+10 | 0.549684E+10 | 0.440581E+09 |
August | 0.506808E+10 | 0.187983E+10 | 0.318825E+10 | 0.738022E+10 | 0.621692E+09 |
September | 0.532158E+10 | 0.275253E+10 | 0.256905E+10 | 0.690888E+10 | 0.115643E+10 |
October | 0.753311E+10 | 0.472379E+10 | 0.280931E+10 | 0.914058E+10 | 0.214546E+10 |
November | 0.505506E+10 | 0.303580E+10 | 0.201926E+10 | 0.531706E+10 | 0.291741E+10 |
December | 0.516758E+10 | 0.366864E+10 | 0.149895E+10 | 0.523511E+10 | 0.373585E+10 |
Annual Sum or Average | 0.596843E+11 | 0.297754E+11 | 0.299089E+11 | 0.693832E+11 | 0.262222E+11 |
Minimum of Months | 0.350390E+10 | 0.535604E+09 | 0.149895E+10 | 0.443687E+10 | 0.440581E+09 |
Maximum of Months | 0.753311E+10 | 0.472379E+10 | 0.318825E+10 | 0.914058E+10 | 0.401659E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126707E+10 | 0.518996E+09 | 0.748077E+09 | 0.808526E+09 | 0.282193E+10 |
February | 0.168766E+10 | 0.741225E+09 | 0.946434E+09 | 0.118418E+10 | 0.262545E+10 |
March | 0.275904E+10 | 0.127377E+10 | 0.148527E+10 | 0.250625E+10 | 0.199103E+10 |
April | 0.291823E+10 | 0.124863E+10 | 0.166960E+10 | 0.298119E+10 | 0.142963E+10 |
May | 0.351275E+10 | 0.133400E+10 | 0.217875E+10 | 0.404071E+10 | 0.965709E+09 |
June | 0.372058E+10 | 0.150062E+10 | 0.221997E+10 | 0.477403E+10 | 0.530631E+09 |
July | 0.360068E+10 | 0.135590E+10 | 0.224478E+10 | 0.494339E+10 | 0.307587E+09 |
August | 0.398333E+10 | 0.184402E+10 | 0.213931E+10 | 0.546335E+10 | 0.422256E+09 |
September | 0.273663E+10 | 0.119590E+10 | 0.154073E+10 | 0.338435E+10 | 0.756738E+09 |
October | 0.280360E+10 | 0.136332E+10 | 0.144028E+10 | 0.313539E+10 | 0.141564E+10 |
November | 0.127409E+10 | 0.368220E+09 | 0.905870E+09 | 0.900140E+09 | 0.198526E+10 |
December | 0.117105E+10 | 0.506717E+09 | 0.664336E+09 | 0.761692E+09 | 0.264841E+10 |
Annual Sum or Average | 0.314347E+11 | 0.132513E+11 | 0.181834E+11 | 0.348832E+11 | 0.179003E+11 |
Minimum of Months | 0.117105E+10 | 0.368220E+09 | 0.664336E+09 | 0.761692E+09 | 0.307587E+09 |
Maximum of Months | 0.398333E+10 | 0.184402E+10 | 0.224478E+10 | 0.546335E+10 | 0.282193E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.89 | 1582.68 | 344.10 | 0.00 | 344.10 | 0.00 | 0.00 |
February | 62.28 | 1636.54 | 470.89 | 0.00 | 470.89 | 0.00 | 0.00 |
March | 275.23 | 1082.26 | 653.01 | 0.00 | 653.01 | 0.00 | 0.00 |
April | 531.98 | 771.62 | 784.35 | 2.23 | 782.12 | 0.00 | 0.00 |
May | 994.16 | 488.96 | 1040.58 | 34.67 | 1005.91 | 0.00 | 0.00 |
June | 1337.58 | 275.52 | 1103.53 | 59.30 | 1044.23 | 0.00 | 0.00 |
July | 1466.67 | 157.87 | 1066.45 | 38.57 | 1027.89 | 0.00 | 0.00 |
August | 1284.96 | 212.58 | 944.83 | 11.24 | 933.58 | 0.00 | 0.00 |
September | 760.95 | 408.36 | 712.24 | 0.13 | 712.11 | 0.00 | 0.00 |
October | 483.34 | 734.69 | 616.39 | 0.00 | 616.39 | 0.00 | 0.00 |
November | 155.49 | 1096.35 | 432.34 | 0.00 | 432.34 | 0.00 | 0.00 |
December | 24.81 | 1456.34 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Annual Sum or Average | 621.48 | 820.70 | 707.10 | 12.24 | 694.85 | 0.00 | 0.00 |
Minimum of Months | 24.81 | 157.87 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Maximum of Months | 1466.67 | 1636.54 | 1103.53 | 59.30 | 1044.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 311.07 | 984.30 | 479.19 | 192.12 | 287.08 | 0.00 | 0.00 |
February | 540.36 | 986.56 | 743.12 | 346.67 | 396.46 | 0.00 | 0.00 |
March | 844.47 | 697.34 | 947.99 | 403.19 | 544.81 | 0.00 | 0.00 |
April | 1156.87 | 500.16 | 1137.66 | 498.33 | 639.33 | 0.00 | 0.00 |
May | 1580.75 | 327.61 | 1379.74 | 551.43 | 828.32 | 0.00 | 0.00 |
June | 1626.93 | 183.31 | 1278.73 | 462.89 | 815.84 | 0.00 | 0.00 |
July | 1758.96 | 102.91 | 1284.33 | 463.48 | 820.85 | 0.00 | 0.00 |
August | 1969.25 | 139.80 | 1446.18 | 652.08 | 794.10 | 0.00 | 0.00 |
September | 1320.71 | 260.63 | 1078.57 | 483.91 | 594.66 | 0.00 | 0.00 |
October | 1082.54 | 472.89 | 977.80 | 443.17 | 534.63 | 0.00 | 0.00 |
November | 509.60 | 690.34 | 604.70 | 232.21 | 372.49 | 0.00 | 0.00 |
December | 332.31 | 898.36 | 471.09 | 221.20 | 249.90 | 0.00 | 0.00 |
Annual Sum or Average | 1089.90 | 517.74 | 987.33 | 413.02 | 574.30 | 0.00 | 0.00 |
Minimum of Months | 311.07 | 102.91 | 471.09 | 192.12 | 249.90 | 0.00 | 0.00 |
Maximum of Months | 1969.25 | 986.56 | 1446.18 | 652.08 | 828.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1753.56 | 1426.42 | 1780.09 | 1165.62 | 614.48 | 0.00 | 0.00 |
February | 2349.09 | 1444.31 | 2347.88 | 1554.11 | 793.78 | 0.00 | 0.00 |
March | 2232.88 | 1061.90 | 2118.24 | 1175.66 | 942.58 | 0.00 | 0.00 |
April | 1792.76 | 798.33 | 1643.68 | 649.96 | 993.72 | 0.00 | 0.00 |
May | 1664.80 | 518.26 | 1440.44 | 300.45 | 1139.99 | 0.00 | 0.00 |
June | 1774.63 | 289.76 | 1351.81 | 206.64 | 1145.17 | 0.00 | 0.00 |
July | 2045.82 | 158.82 | 1416.97 | 246.13 | 1170.84 | 0.00 | 0.00 |
August | 2750.10 | 223.69 | 1892.20 | 701.85 | 1190.36 | 0.00 | 0.00 |
September | 2669.45 | 419.48 | 2053.08 | 1061.93 | 991.14 | 0.00 | 0.00 |
October | 3424.84 | 745.52 | 2812.54 | 1763.66 | 1048.88 | 0.00 | 0.00 |
November | 2075.38 | 1041.57 | 1950.25 | 1171.22 | 779.04 | 0.00 | 0.00 |
December | 1974.85 | 1303.67 | 1929.35 | 1369.71 | 559.64 | 0.00 | 0.00 |
Annual Sum or Average | 2209.30 | 782.20 | 1892.58 | 944.17 | 948.40 | 0.00 | 0.00 |
Minimum of Months | 1664.80 | 158.82 | 1351.81 | 206.64 | 559.64 | 0.00 | 0.00 |
Maximum of Months | 3424.84 | 1444.31 | 2812.54 | 1763.66 | 1190.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.64 | 1005.66 | 473.07 | 193.77 | 279.30 | 0.00 | 0.00 |
February | 495.63 | 1030.94 | 697.61 | 306.39 | 391.22 | 0.00 | 0.00 |
March | 943.52 | 697.47 | 1030.11 | 475.57 | 554.54 | 0.00 | 0.00 |
April | 1158.63 | 516.74 | 1125.86 | 481.73 | 644.13 | 0.00 | 0.00 |
May | 1515.10 | 341.05 | 1311.51 | 498.06 | 813.45 | 0.00 | 0.00 |
June | 1841.03 | 196.33 | 1435.41 | 578.94 | 856.47 | 0.00 | 0.00 |
July | 1841.55 | 111.03 | 1344.34 | 506.24 | 838.10 | 0.00 | 0.00 |
August | 2037.25 | 152.36 | 1487.20 | 688.48 | 798.73 | 0.00 | 0.00 |
September | 1310.97 | 273.91 | 1055.80 | 461.38 | 594.42 | 0.00 | 0.00 |
October | 1181.96 | 489.95 | 1046.74 | 509.00 | 537.74 | 0.00 | 0.00 |
November | 359.27 | 708.97 | 491.55 | 142.06 | 349.49 | 0.00 | 0.00 |
December | 290.42 | 924.66 | 437.22 | 189.19 | 248.03 | 0.00 | 0.00 |
Annual Sum or Average | 1111.10 | 534.61 | 996.79 | 420.20 | 576.59 | 0.00 | 0.00 |
Minimum of Months | 290.42 | 111.03 | 437.22 | 142.06 | 248.03 | 0.00 | 0.00 |
Maximum of Months | 2037.25 | 1030.94 | 1487.20 | 688.48 | 856.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.92 | 1650.64 | 344.10 | 0.00 | 344.10 | 0.00 | 0.00 |
February | 61.82 | 1696.28 | 470.89 | 0.00 | 470.89 | 0.00 | 0.00 |
March | 283.95 | 1117.41 | 653.00 | 0.00 | 653.00 | 0.00 | 0.00 |
April | 547.26 | 788.37 | 784.35 | 2.23 | 782.12 | 0.00 | 0.00 |
May | 1024.13 | 483.80 | 1040.58 | 34.67 | 1005.91 | 0.00 | 0.00 |
June | 1362.09 | 269.70 | 1103.52 | 59.30 | 1044.22 | 0.00 | 0.00 |
July | 1489.27 | 150.50 | 1066.45 | 38.57 | 1027.88 | 0.00 | 0.00 |
August | 1296.12 | 213.62 | 944.82 | 11.24 | 933.58 | 0.00 | 0.00 |
September | 755.36 | 442.10 | 712.24 | 0.13 | 712.10 | 0.00 | 0.00 |
October | 460.02 | 819.50 | 616.39 | 0.00 | 616.39 | 0.00 | 0.00 |
November | 133.73 | 1228.05 | 432.34 | 0.00 | 432.34 | 0.00 | 0.00 |
December | 19.56 | 1576.70 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Annual Sum or Average | 626.03 | 864.99 | 707.09 | 12.24 | 694.85 | 0.00 | 0.00 |
Minimum of Months | 19.56 | 150.50 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Maximum of Months | 1489.27 | 1696.28 | 1103.52 | 59.30 | 1044.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 310.24 | 1033.90 | 479.19 | 192.11 | 287.07 | 0.00 | 0.00 |
February | 539.68 | 1036.48 | 743.12 | 346.66 | 396.45 | 0.00 | 0.00 |
March | 852.66 | 731.28 | 947.99 | 403.18 | 544.80 | 0.00 | 0.00 |
April | 1167.33 | 523.01 | 1137.65 | 498.32 | 639.33 | 0.00 | 0.00 |
May | 1600.26 | 333.85 | 1379.73 | 551.42 | 828.31 | 0.00 | 0.00 |
June | 1642.98 | 186.17 | 1278.72 | 462.88 | 815.84 | 0.00 | 0.00 |
July | 1772.81 | 105.33 | 1284.32 | 463.48 | 820.84 | 0.00 | 0.00 |
August | 1978.04 | 149.91 | 1446.17 | 652.08 | 794.10 | 0.00 | 0.00 |
September | 1318.13 | 290.48 | 1078.56 | 483.91 | 594.66 | 0.00 | 0.00 |
October | 1068.63 | 537.26 | 977.80 | 443.17 | 534.63 | 0.00 | 0.00 |
November | 491.03 | 776.76 | 604.69 | 232.21 | 372.48 | 0.00 | 0.00 |
December | 324.07 | 980.10 | 471.09 | 221.19 | 249.90 | 0.00 | 0.00 |
Annual Sum or Average | 1092.61 | 554.34 | 987.32 | 413.02 | 574.30 | 0.00 | 0.00 |
Minimum of Months | 310.24 | 105.33 | 471.09 | 192.11 | 249.90 | 0.00 | 0.00 |
Maximum of Months | 1978.04 | 1036.48 | 1446.17 | 652.08 | 828.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1785.16 | 1494.52 | 1780.11 | 1165.63 | 614.48 | 0.00 | 0.00 |
February | 2385.18 | 1523.92 | 2347.91 | 1554.12 | 793.78 | 0.00 | 0.00 |
March | 2276.69 | 1111.11 | 2118.26 | 1175.67 | 942.59 | 0.00 | 0.00 |
April | 1828.40 | 820.32 | 1643.69 | 649.96 | 993.73 | 0.00 | 0.00 |
May | 1712.81 | 510.88 | 1440.45 | 300.46 | 1140.00 | 0.00 | 0.00 |
June | 1806.23 | 285.55 | 1351.82 | 206.64 | 1145.18 | 0.00 | 0.00 |
July | 2067.91 | 157.66 | 1416.98 | 246.13 | 1170.85 | 0.00 | 0.00 |
August | 2762.79 | 238.60 | 1892.22 | 701.86 | 1190.36 | 0.00 | 0.00 |
September | 2673.48 | 469.66 | 2053.10 | 1061.95 | 991.15 | 0.00 | 0.00 |
October | 3423.41 | 858.93 | 2812.57 | 1763.68 | 1048.89 | 0.00 | 0.00 |
November | 2073.26 | 1169.92 | 1950.28 | 1171.23 | 779.04 | 0.00 | 0.00 |
December | 1983.75 | 1422.34 | 1929.38 | 1369.73 | 559.65 | 0.00 | 0.00 |
Annual Sum or Average | 2231.82 | 834.65 | 1892.59 | 944.18 | 948.41 | 0.00 | 0.00 |
Minimum of Months | 1712.81 | 157.66 | 1351.82 | 206.64 | 559.65 | 0.00 | 0.00 |
Maximum of Months | 3423.41 | 1523.92 | 2812.57 | 1763.68 | 1190.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.62 | 1055.16 | 473.07 | 193.77 | 279.30 | 0.00 | 0.00 |
February | 500.64 | 1080.96 | 697.61 | 306.39 | 391.22 | 0.00 | 0.00 |
March | 954.28 | 734.53 | 1030.10 | 475.57 | 554.53 | 0.00 | 0.00 |
April | 1169.62 | 540.92 | 1125.85 | 481.72 | 644.13 | 0.00 | 0.00 |
May | 1531.24 | 347.71 | 1311.50 | 498.06 | 813.45 | 0.00 | 0.00 |
June | 1854.40 | 202.34 | 1435.40 | 578.94 | 856.47 | 0.00 | 0.00 |
July | 1853.77 | 114.62 | 1344.33 | 506.23 | 838.10 | 0.00 | 0.00 |
August | 2043.14 | 163.24 | 1487.19 | 688.47 | 798.72 | 0.00 | 0.00 |
September | 1304.42 | 304.53 | 1055.79 | 461.38 | 594.41 | 0.00 | 0.00 |
October | 1166.19 | 557.15 | 1046.74 | 509.00 | 537.74 | 0.00 | 0.00 |
November | 345.82 | 793.16 | 491.54 | 142.06 | 349.48 | 0.00 | 0.00 |
December | 286.84 | 1007.74 | 437.22 | 189.18 | 248.03 | 0.00 | 0.00 |
Annual Sum or Average | 1114.19 | 572.27 | 996.78 | 420.19 | 576.59 | 0.00 | 0.00 |
Minimum of Months | 286.84 | 114.62 | 437.22 | 142.06 | 248.03 | 0.00 | 0.00 |
Maximum of Months | 2043.14 | 1080.96 | 1487.19 | 688.47 | 856.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 31.99 | 1657.05 | 344.10 | 0.00 | 344.10 | 0.00 | 0.00 |
February | 56.22 | 1722.07 | 470.89 | 0.00 | 470.89 | 0.00 | 0.00 |
March | 261.82 | 1157.13 | 653.01 | 0.00 | 653.01 | 0.00 | 0.00 |
April | 514.69 | 829.29 | 784.35 | 2.23 | 782.12 | 0.00 | 0.00 |
May | 980.66 | 517.77 | 1040.58 | 34.67 | 1005.91 | 0.00 | 0.00 |
June | 1337.97 | 286.98 | 1103.53 | 59.30 | 1044.23 | 0.00 | 0.00 |
July | 1472.27 | 162.45 | 1066.45 | 38.57 | 1027.89 | 0.00 | 0.00 |
August | 1287.43 | 220.69 | 944.83 | 11.24 | 933.58 | 0.00 | 0.00 |
September | 752.89 | 437.65 | 712.24 | 0.13 | 712.11 | 0.00 | 0.00 |
October | 462.15 | 799.31 | 616.39 | 0.00 | 616.39 | 0.00 | 0.00 |
November | 137.32 | 1190.71 | 432.34 | 0.00 | 432.34 | 0.00 | 0.00 |
December | 19.64 | 1557.35 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Annual Sum or Average | 613.30 | 873.37 | 707.10 | 12.24 | 694.85 | 0.00 | 0.00 |
Minimum of Months | 19.64 | 162.45 | 300.15 | 0.00 | 300.15 | 0.00 | 0.00 |
Maximum of Months | 1472.27 | 1722.07 | 1103.53 | 59.30 | 1044.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.48 | 1030.85 | 479.19 | 192.12 | 287.08 | 0.00 | 0.00 |
February | 530.52 | 1038.80 | 743.12 | 346.67 | 396.46 | 0.00 | 0.00 |
March | 834.93 | 742.04 | 947.99 | 403.19 | 544.81 | 0.00 | 0.00 |
April | 1147.98 | 531.69 | 1137.66 | 498.33 | 639.33 | 0.00 | 0.00 |
May | 1576.65 | 344.17 | 1379.74 | 551.43 | 828.32 | 0.00 | 0.00 |
June | 1629.15 | 190.13 | 1278.73 | 462.89 | 815.84 | 0.00 | 0.00 |
July | 1764.32 | 105.62 | 1284.33 | 463.48 | 820.85 | 0.00 | 0.00 |
August | 1973.42 | 144.23 | 1446.18 | 652.08 | 794.10 | 0.00 | 0.00 |
September | 1317.81 | 276.38 | 1078.57 | 483.91 | 594.66 | 0.00 | 0.00 |
October | 1071.60 | 508.36 | 977.80 | 443.17 | 534.63 | 0.00 | 0.00 |
November | 494.87 | 743.72 | 604.70 | 232.21 | 372.49 | 0.00 | 0.00 |
December | 323.20 | 959.34 | 471.09 | 221.20 | 249.90 | 0.00 | 0.00 |
Annual Sum or Average | 1084.62 | 548.54 | 987.33 | 413.02 | 574.30 | 0.00 | 0.00 |
Minimum of Months | 305.48 | 105.62 | 471.09 | 192.12 | 249.90 | 0.00 | 0.00 |
Maximum of Months | 1973.42 | 1038.80 | 1446.18 | 652.08 | 828.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1741.96 | 1499.62 | 1780.09 | 1165.62 | 614.48 | 0.00 | 0.00 |
February | 2330.21 | 1525.41 | 2347.88 | 1554.11 | 793.78 | 0.00 | 0.00 |
March | 2219.94 | 1132.39 | 2118.24 | 1175.66 | 942.58 | 0.00 | 0.00 |
April | 1780.20 | 852.55 | 1643.68 | 649.96 | 993.72 | 0.00 | 0.00 |
May | 1656.54 | 549.05 | 1440.44 | 300.45 | 1139.99 | 0.00 | 0.00 |
June | 1776.44 | 302.70 | 1351.81 | 206.64 | 1145.17 | 0.00 | 0.00 |
July | 2052.29 | 164.49 | 1416.97 | 246.13 | 1170.84 | 0.00 | 0.00 |
August | 2755.46 | 232.11 | 1892.20 | 701.85 | 1190.36 | 0.00 | 0.00 |
September | 2665.46 | 446.15 | 2053.08 | 1061.93 | 991.14 | 0.00 | 0.00 |
October | 3412.70 | 801.02 | 2812.54 | 1763.66 | 1048.88 | 0.00 | 0.00 |
November | 2051.33 | 1125.54 | 1950.25 | 1171.22 | 779.04 | 0.00 | 0.00 |
December | 1954.57 | 1394.81 | 1929.35 | 1369.71 | 559.64 | 0.00 | 0.00 |
Annual Sum or Average | 2200.13 | 831.50 | 1892.58 | 944.17 | 948.40 | 0.00 | 0.00 |
Minimum of Months | 1656.54 | 164.49 | 1351.81 | 206.64 | 559.64 | 0.00 | 0.00 |
Maximum of Months | 3412.70 | 1525.41 | 2812.54 | 1763.66 | 1190.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.87 | 1053.59 | 473.07 | 193.77 | 279.30 | 0.00 | 0.00 |
February | 489.49 | 1085.26 | 697.61 | 306.39 | 391.22 | 0.00 | 0.00 |
March | 935.73 | 743.36 | 1030.11 | 475.57 | 554.54 | 0.00 | 0.00 |
April | 1150.15 | 551.55 | 1125.86 | 481.73 | 644.13 | 0.00 | 0.00 |
May | 1508.63 | 360.55 | 1311.51 | 498.06 | 813.45 | 0.00 | 0.00 |
June | 1841.83 | 204.72 | 1435.41 | 578.94 | 856.47 | 0.00 | 0.00 |
July | 1845.65 | 114.84 | 1344.34 | 506.24 | 838.10 | 0.00 | 0.00 |
August | 2039.78 | 157.65 | 1487.20 | 688.48 | 798.73 | 0.00 | 0.00 |
September | 1305.69 | 291.95 | 1055.80 | 461.38 | 594.42 | 0.00 | 0.00 |
October | 1170.62 | 528.54 | 1046.74 | 509.00 | 537.74 | 0.00 | 0.00 |
November | 347.28 | 765.92 | 491.55 | 142.06 | 349.49 | 0.00 | 0.00 |
December | 284.38 | 988.80 | 437.22 | 189.19 | 248.03 | 0.00 | 0.00 |
Annual Sum or Average | 1106.14 | 567.61 | 996.79 | 420.20 | 576.59 | 0.00 | 0.00 |
Minimum of Months | 284.38 | 114.84 | 437.22 | 142.06 | 248.03 | 0.00 | 0.00 |
Maximum of Months | 2039.78 | 1085.26 | 1487.20 | 688.48 | 856.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 96126365.23 | 0.423906E+10 | 0.921647E+09 | 0.00 | 0.921647E+09 | 0.00 | 0.00 |
February | 0.150662E+09 | 0.395911E+10 | 0.113918E+10 | 0.00 | 0.113918E+10 | 0.00 | 0.00 |
March | 0.737180E+09 | 0.289873E+10 | 0.174902E+10 | 0.00 | 0.174902E+10 | 0.00 | 0.00 |
April | 0.137888E+10 | 0.200005E+10 | 0.203304E+10 | 5782587.89 | 0.202726E+10 | 0.00 | 0.00 |
May | 0.266275E+10 | 0.130963E+10 | 0.278710E+10 | 92867775.32 | 0.269423E+10 | 0.00 | 0.00 |
June | 0.346700E+10 | 0.714136E+09 | 0.286034E+10 | 0.153698E+09 | 0.270664E+10 | 0.00 | 0.00 |
July | 0.392834E+10 | 0.422841E+09 | 0.285638E+10 | 0.103296E+09 | 0.275309E+10 | 0.00 | 0.00 |
August | 0.344164E+10 | 0.569386E+09 | 0.253062E+10 | 30117947.12 | 0.250050E+10 | 0.00 | 0.00 |
September | 0.197238E+10 | 0.105848E+10 | 0.184613E+10 | 345705.13 | 0.184578E+10 | 0.00 | 0.00 |
October | 0.129458E+10 | 0.196778E+10 | 0.165095E+10 | 0.00 | 0.165095E+10 | 0.00 | 0.00 |
November | 0.403043E+09 | 0.284175E+10 | 0.112063E+10 | 0.00 | 0.112063E+10 | 0.00 | 0.00 |
December | 66450853.79 | 0.390066E+10 | 0.803921E+09 | 0.00 | 0.803921E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.195990E+11 | 0.258816E+11 | 0.222990E+11 | 0.386109E+09 | 0.219128E+11 | 0.00 | 0.00 |
Minimum of Months | 66450853.79 | 0.422841E+09 | 0.803921E+09 | 0.00 | 0.803921E+09 | 0.00 | 0.00 |
Maximum of Months | 0.392834E+10 | 0.423906E+10 | 0.286034E+10 | 0.153698E+09 | 0.275309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.833160E+09 | 0.263635E+10 | 0.128347E+10 | 0.514566E+09 | 0.768902E+09 | 0.00 | 0.00 |
February | 0.130724E+10 | 0.238668E+10 | 0.179776E+10 | 0.838656E+09 | 0.959109E+09 | 0.00 | 0.00 |
March | 0.226184E+10 | 0.186777E+10 | 0.253911E+10 | 0.107990E+10 | 0.145921E+10 | 0.00 | 0.00 |
April | 0.299861E+10 | 0.129642E+10 | 0.294881E+10 | 0.129167E+10 | 0.165715E+10 | 0.00 | 0.00 |
May | 0.423389E+10 | 0.877474E+09 | 0.369550E+10 | 0.147694E+10 | 0.221856E+10 | 0.00 | 0.00 |
June | 0.421699E+10 | 0.475132E+09 | 0.331447E+10 | 0.119981E+10 | 0.211466E+10 | 0.00 | 0.00 |
July | 0.471119E+10 | 0.275623E+09 | 0.343994E+10 | 0.124139E+10 | 0.219856E+10 | 0.00 | 0.00 |
August | 0.527445E+10 | 0.374453E+09 | 0.387346E+10 | 0.174654E+10 | 0.212692E+10 | 0.00 | 0.00 |
September | 0.342328E+10 | 0.675551E+09 | 0.279566E+10 | 0.125430E+10 | 0.154136E+10 | 0.00 | 0.00 |
October | 0.289947E+10 | 0.126658E+10 | 0.261895E+10 | 0.118700E+10 | 0.143196E+10 | 0.00 | 0.00 |
November | 0.132089E+10 | 0.178937E+10 | 0.156737E+10 | 0.601886E+09 | 0.965487E+09 | 0.00 | 0.00 |
December | 0.890060E+09 | 0.240617E+10 | 0.126178E+10 | 0.592451E+09 | 0.669324E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.343711E+11 | 0.163276E+11 | 0.311363E+11 | 0.130251E+11 | 0.181112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.833160E+09 | 0.275623E+09 | 0.126178E+10 | 0.514566E+09 | 0.669324E+09 | 0.00 | 0.00 |
Maximum of Months | 0.527445E+10 | 0.263635E+10 | 0.387346E+10 | 0.174654E+10 | 0.221856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469672E+10 | 0.382052E+10 | 0.476780E+10 | 0.312199E+10 | 0.164582E+10 | 0.00 | 0.00 |
February | 0.568293E+10 | 0.349408E+10 | 0.568000E+10 | 0.375969E+10 | 0.192031E+10 | 0.00 | 0.00 |
March | 0.598054E+10 | 0.284419E+10 | 0.567348E+10 | 0.314887E+10 | 0.252461E+10 | 0.00 | 0.00 |
April | 0.464682E+10 | 0.206928E+10 | 0.426041E+10 | 0.168469E+10 | 0.257572E+10 | 0.00 | 0.00 |
May | 0.445899E+10 | 0.138811E+10 | 0.385808E+10 | 0.804731E+09 | 0.305335E+10 | 0.00 | 0.00 |
June | 0.459984E+10 | 0.751057E+09 | 0.350390E+10 | 0.535604E+09 | 0.296829E+10 | 0.00 | 0.00 |
July | 0.547953E+10 | 0.425387E+09 | 0.379521E+10 | 0.659224E+09 | 0.313599E+10 | 0.00 | 0.00 |
August | 0.736588E+10 | 0.599141E+09 | 0.506808E+10 | 0.187983E+10 | 0.318825E+10 | 0.00 | 0.00 |
September | 0.691922E+10 | 0.108728E+10 | 0.532158E+10 | 0.275253E+10 | 0.256905E+10 | 0.00 | 0.00 |
October | 0.917308E+10 | 0.199681E+10 | 0.753311E+10 | 0.472379E+10 | 0.280931E+10 | 0.00 | 0.00 |
November | 0.537938E+10 | 0.269974E+10 | 0.505506E+10 | 0.303580E+10 | 0.201926E+10 | 0.00 | 0.00 |
December | 0.528944E+10 | 0.349174E+10 | 0.516758E+10 | 0.366864E+10 | 0.149895E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.696724E+11 | 0.246673E+11 | 0.596843E+11 | 0.297754E+11 | 0.299089E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445899E+10 | 0.425387E+09 | 0.350390E+10 | 0.535604E+09 | 0.149895E+10 | 0.00 | 0.00 |
Maximum of Months | 0.917308E+10 | 0.382052E+10 | 0.753311E+10 | 0.472379E+10 | 0.318825E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818619E+09 | 0.269357E+10 | 0.126707E+10 | 0.518996E+09 | 0.748077E+09 | 0.00 | 0.00 |
February | 0.119904E+10 | 0.249404E+10 | 0.168766E+10 | 0.741225E+09 | 0.946434E+09 | 0.00 | 0.00 |
March | 0.252712E+10 | 0.186810E+10 | 0.275904E+10 | 0.127377E+10 | 0.148527E+10 | 0.00 | 0.00 |
April | 0.300317E+10 | 0.133939E+10 | 0.291823E+10 | 0.124863E+10 | 0.166960E+10 | 0.00 | 0.00 |
May | 0.405805E+10 | 0.913479E+09 | 0.351275E+10 | 0.133400E+10 | 0.217875E+10 | 0.00 | 0.00 |
June | 0.477195E+10 | 0.508880E+09 | 0.372058E+10 | 0.150062E+10 | 0.221997E+10 | 0.00 | 0.00 |
July | 0.493240E+10 | 0.297371E+09 | 0.360068E+10 | 0.135590E+10 | 0.224478E+10 | 0.00 | 0.00 |
August | 0.545657E+10 | 0.408089E+09 | 0.398333E+10 | 0.184402E+10 | 0.213931E+10 | 0.00 | 0.00 |
September | 0.339802E+10 | 0.709971E+09 | 0.273663E+10 | 0.119590E+10 | 0.154073E+10 | 0.00 | 0.00 |
October | 0.316576E+10 | 0.131229E+10 | 0.280360E+10 | 0.136332E+10 | 0.144028E+10 | 0.00 | 0.00 |
November | 0.931239E+09 | 0.183764E+10 | 0.127409E+10 | 0.368220E+09 | 0.905870E+09 | 0.00 | 0.00 |
December | 0.777860E+09 | 0.247662E+10 | 0.117105E+10 | 0.506717E+09 | 0.664336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.350398E+11 | 0.168594E+11 | 0.314347E+11 | 0.132513E+11 | 0.181834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.777860E+09 | 0.297371E+09 | 0.117105E+10 | 0.368220E+09 | 0.664336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.545657E+10 | 0.269357E+10 | 0.398333E+10 | 0.184402E+10 | 0.224478E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 90841803.77 | 0.442108E+10 | 0.921642E+09 | 0.00 | 0.921642E+09 | 0.00 | 0.00 |
February | 0.149562E+09 | 0.410365E+10 | 0.113917E+10 | 0.00 | 0.113917E+10 | 0.00 | 0.00 |
March | 0.760530E+09 | 0.299286E+10 | 0.174901E+10 | 0.00 | 0.174901E+10 | 0.00 | 0.00 |
April | 0.141850E+10 | 0.204345E+10 | 0.203303E+10 | 5782557.93 | 0.202724E+10 | 0.00 | 0.00 |
May | 0.274302E+10 | 0.129582E+10 | 0.278709E+10 | 92867294.10 | 0.269422E+10 | 0.00 | 0.00 |
June | 0.353054E+10 | 0.699057E+09 | 0.286033E+10 | 0.153697E+09 | 0.270663E+10 | 0.00 | 0.00 |
July | 0.398885E+10 | 0.403111E+09 | 0.285637E+10 | 0.103296E+09 | 0.275307E+10 | 0.00 | 0.00 |
August | 0.347154E+10 | 0.572155E+09 | 0.253061E+10 | 30117791.05 | 0.250049E+10 | 0.00 | 0.00 |
September | 0.195789E+10 | 0.114594E+10 | 0.184612E+10 | 345703.34 | 0.184577E+10 | 0.00 | 0.00 |
October | 0.123211E+10 | 0.219495E+10 | 0.165094E+10 | 0.00 | 0.165094E+10 | 0.00 | 0.00 |
November | 0.346619E+09 | 0.318311E+10 | 0.112062E+10 | 0.00 | 0.112062E+10 | 0.00 | 0.00 |
December | 52384246.24 | 0.422303E+10 | 0.803917E+09 | 0.00 | 0.803917E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.197424E+11 | 0.272782E+11 | 0.222988E+11 | 0.386107E+09 | 0.219127E+11 | 0.00 | 0.00 |
Minimum of Months | 52384246.24 | 0.403111E+09 | 0.803917E+09 | 0.00 | 0.803917E+09 | 0.00 | 0.00 |
Maximum of Months | 0.398885E+10 | 0.442108E+10 | 0.286033E+10 | 0.153697E+09 | 0.275307E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.830960E+09 | 0.276921E+10 | 0.128346E+10 | 0.514561E+09 | 0.768897E+09 | 0.00 | 0.00 |
February | 0.130560E+10 | 0.250745E+10 | 0.179775E+10 | 0.838648E+09 | 0.959103E+09 | 0.00 | 0.00 |
March | 0.228376E+10 | 0.195865E+10 | 0.253909E+10 | 0.107989E+10 | 0.145920E+10 | 0.00 | 0.00 |
April | 0.302571E+10 | 0.135565E+10 | 0.294879E+10 | 0.129165E+10 | 0.165714E+10 | 0.00 | 0.00 |
May | 0.428614E+10 | 0.894194E+09 | 0.369547E+10 | 0.147693E+10 | 0.221855E+10 | 0.00 | 0.00 |
June | 0.425861E+10 | 0.482562E+09 | 0.331444E+10 | 0.119980E+10 | 0.211465E+10 | 0.00 | 0.00 |
July | 0.474831E+10 | 0.282121E+09 | 0.343992E+10 | 0.124137E+10 | 0.219854E+10 | 0.00 | 0.00 |
August | 0.529798E+10 | 0.401524E+09 | 0.387343E+10 | 0.174652E+10 | 0.212691E+10 | 0.00 | 0.00 |
September | 0.341660E+10 | 0.752937E+09 | 0.279564E+10 | 0.125429E+10 | 0.154135E+10 | 0.00 | 0.00 |
October | 0.286223E+10 | 0.143899E+10 | 0.261893E+10 | 0.118698E+10 | 0.143195E+10 | 0.00 | 0.00 |
November | 0.127276E+10 | 0.201336E+10 | 0.156736E+10 | 0.601880E+09 | 0.965481E+09 | 0.00 | 0.00 |
December | 0.867979E+09 | 0.262511E+10 | 0.126176E+10 | 0.592445E+09 | 0.669320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344566E+11 | 0.174818E+11 | 0.311360E+11 | 0.130250E+11 | 0.181111E+11 | 0.00 | 0.00 |
Minimum of Months | 0.830960E+09 | 0.282121E+09 | 0.126176E+10 | 0.514561E+09 | 0.669320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529798E+10 | 0.276921E+10 | 0.387343E+10 | 0.174652E+10 | 0.221855E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.478138E+10 | 0.400291E+10 | 0.476785E+10 | 0.312202E+10 | 0.164583E+10 | 0.00 | 0.00 |
February | 0.577022E+10 | 0.368666E+10 | 0.568006E+10 | 0.375974E+10 | 0.192032E+10 | 0.00 | 0.00 |
March | 0.609789E+10 | 0.297600E+10 | 0.567354E+10 | 0.314891E+10 | 0.252463E+10 | 0.00 | 0.00 |
April | 0.473921E+10 | 0.212626E+10 | 0.426045E+10 | 0.168471E+10 | 0.257574E+10 | 0.00 | 0.00 |
May | 0.458759E+10 | 0.136834E+10 | 0.385811E+10 | 0.804740E+09 | 0.305337E+10 | 0.00 | 0.00 |
June | 0.468174E+10 | 0.740154E+09 | 0.350392E+10 | 0.535610E+09 | 0.296831E+10 | 0.00 | 0.00 |
July | 0.553869E+10 | 0.422279E+09 | 0.379524E+10 | 0.659232E+09 | 0.313601E+10 | 0.00 | 0.00 |
August | 0.739986E+10 | 0.639059E+09 | 0.506812E+10 | 0.187985E+10 | 0.318827E+10 | 0.00 | 0.00 |
September | 0.692965E+10 | 0.121737E+10 | 0.532163E+10 | 0.275256E+10 | 0.256906E+10 | 0.00 | 0.00 |
October | 0.916926E+10 | 0.230055E+10 | 0.753318E+10 | 0.472385E+10 | 0.280934E+10 | 0.00 | 0.00 |
November | 0.537390E+10 | 0.303243E+10 | 0.505511E+10 | 0.303584E+10 | 0.201928E+10 | 0.00 | 0.00 |
December | 0.531329E+10 | 0.380960E+10 | 0.516764E+10 | 0.366868E+10 | 0.149896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.703827E+11 | 0.263216E+11 | 0.596848E+11 | 0.297757E+11 | 0.299091E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458759E+10 | 0.422279E+09 | 0.350392E+10 | 0.535610E+09 | 0.149896E+10 | 0.00 | 0.00 |
Maximum of Months | 0.916926E+10 | 0.400291E+10 | 0.753318E+10 | 0.472385E+10 | 0.318827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.823940E+09 | 0.282613E+10 | 0.126706E+10 | 0.518991E+09 | 0.748072E+09 | 0.00 | 0.00 |
February | 0.121114E+10 | 0.261505E+10 | 0.168765E+10 | 0.741218E+09 | 0.946429E+09 | 0.00 | 0.00 |
March | 0.255594E+10 | 0.196736E+10 | 0.275902E+10 | 0.127376E+10 | 0.148526E+10 | 0.00 | 0.00 |
April | 0.303166E+10 | 0.140206E+10 | 0.291821E+10 | 0.124862E+10 | 0.166959E+10 | 0.00 | 0.00 |
May | 0.410128E+10 | 0.931293E+09 | 0.351273E+10 | 0.133399E+10 | 0.217874E+10 | 0.00 | 0.00 |
June | 0.480661E+10 | 0.524458E+09 | 0.372056E+10 | 0.150060E+10 | 0.221996E+10 | 0.00 | 0.00 |
July | 0.496514E+10 | 0.306998E+09 | 0.360065E+10 | 0.135589E+10 | 0.224476E+10 | 0.00 | 0.00 |
August | 0.547234E+10 | 0.437224E+09 | 0.398330E+10 | 0.184400E+10 | 0.213930E+10 | 0.00 | 0.00 |
September | 0.338105E+10 | 0.789345E+09 | 0.273661E+10 | 0.119588E+10 | 0.154072E+10 | 0.00 | 0.00 |
October | 0.312353E+10 | 0.149226E+10 | 0.280358E+10 | 0.136331E+10 | 0.144027E+10 | 0.00 | 0.00 |
November | 0.896369E+09 | 0.205586E+10 | 0.127408E+10 | 0.368217E+09 | 0.905864E+09 | 0.00 | 0.00 |
December | 0.768260E+09 | 0.269914E+10 | 0.117104E+10 | 0.506712E+09 | 0.664332E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.351372E+11 | 0.180472E+11 | 0.314345E+11 | 0.132512E+11 | 0.181833E+11 | 0.00 | 0.00 |
Minimum of Months | 0.768260E+09 | 0.306998E+09 | 0.117104E+10 | 0.368217E+09 | 0.664332E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547234E+10 | 0.282613E+10 | 0.398330E+10 | 0.184400E+10 | 0.224476E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 85679202.14 | 0.443824E+10 | 0.921647E+09 | 0.00 | 0.921647E+09 | 0.00 | 0.00 |
February | 0.136008E+09 | 0.416603E+10 | 0.113918E+10 | 0.00 | 0.113918E+10 | 0.00 | 0.00 |
March | 0.701265E+09 | 0.309926E+10 | 0.174902E+10 | 0.00 | 0.174902E+10 | 0.00 | 0.00 |
April | 0.133408E+10 | 0.214952E+10 | 0.203304E+10 | 5782587.89 | 0.202726E+10 | 0.00 | 0.00 |
May | 0.262661E+10 | 0.138680E+10 | 0.278710E+10 | 92867775.32 | 0.269423E+10 | 0.00 | 0.00 |
June | 0.346802E+10 | 0.743851E+09 | 0.286034E+10 | 0.153698E+09 | 0.270664E+10 | 0.00 | 0.00 |
July | 0.394333E+10 | 0.435118E+09 | 0.285638E+10 | 0.103296E+09 | 0.275309E+10 | 0.00 | 0.00 |
August | 0.344825E+10 | 0.591106E+09 | 0.253062E+10 | 30117947.12 | 0.250050E+10 | 0.00 | 0.00 |
September | 0.195150E+10 | 0.113440E+10 | 0.184613E+10 | 345705.13 | 0.184578E+10 | 0.00 | 0.00 |
October | 0.123782E+10 | 0.214088E+10 | 0.165095E+10 | 0.00 | 0.165095E+10 | 0.00 | 0.00 |
November | 0.355932E+09 | 0.308632E+10 | 0.112063E+10 | 0.00 | 0.112063E+10 | 0.00 | 0.00 |
December | 52608129.10 | 0.417120E+10 | 0.803921E+09 | 0.00 | 0.803921E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193411E+11 | 0.275427E+11 | 0.222990E+11 | 0.386109E+09 | 0.219128E+11 | 0.00 | 0.00 |
Minimum of Months | 52608129.10 | 0.435118E+09 | 0.803921E+09 | 0.00 | 0.803921E+09 | 0.00 | 0.00 |
Maximum of Months | 0.394333E+10 | 0.443824E+10 | 0.286034E+10 | 0.153698E+09 | 0.275309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818199E+09 | 0.276104E+10 | 0.128347E+10 | 0.514566E+09 | 0.768902E+09 | 0.00 | 0.00 |
February | 0.128344E+10 | 0.251306E+10 | 0.179776E+10 | 0.838656E+09 | 0.959109E+09 | 0.00 | 0.00 |
March | 0.223628E+10 | 0.198747E+10 | 0.253911E+10 | 0.107990E+10 | 0.145921E+10 | 0.00 | 0.00 |
April | 0.297555E+10 | 0.137815E+10 | 0.294881E+10 | 0.129167E+10 | 0.165715E+10 | 0.00 | 0.00 |
May | 0.422289E+10 | 0.921819E+09 | 0.369550E+10 | 0.147694E+10 | 0.221856E+10 | 0.00 | 0.00 |
June | 0.422276E+10 | 0.492828E+09 | 0.331447E+10 | 0.119981E+10 | 0.211466E+10 | 0.00 | 0.00 |
July | 0.472555E+10 | 0.282885E+09 | 0.343994E+10 | 0.124139E+10 | 0.219856E+10 | 0.00 | 0.00 |
August | 0.528560E+10 | 0.386307E+09 | 0.387346E+10 | 0.174654E+10 | 0.212692E+10 | 0.00 | 0.00 |
September | 0.341577E+10 | 0.716386E+09 | 0.279566E+10 | 0.125430E+10 | 0.154136E+10 | 0.00 | 0.00 |
October | 0.287016E+10 | 0.136159E+10 | 0.261895E+10 | 0.118700E+10 | 0.143196E+10 | 0.00 | 0.00 |
November | 0.128270E+10 | 0.192773E+10 | 0.156737E+10 | 0.601886E+09 | 0.965487E+09 | 0.00 | 0.00 |
December | 0.865665E+09 | 0.256948E+10 | 0.126178E+10 | 0.592451E+09 | 0.669324E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342046E+11 | 0.172987E+11 | 0.311363E+11 | 0.130251E+11 | 0.181112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.818199E+09 | 0.282885E+09 | 0.126178E+10 | 0.514566E+09 | 0.669324E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528560E+10 | 0.276104E+10 | 0.387346E+10 | 0.174654E+10 | 0.221856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.466565E+10 | 0.401659E+10 | 0.476780E+10 | 0.312199E+10 | 0.164582E+10 | 0.00 | 0.00 |
February | 0.563725E+10 | 0.369026E+10 | 0.568000E+10 | 0.375969E+10 | 0.192031E+10 | 0.00 | 0.00 |
March | 0.594589E+10 | 0.303299E+10 | 0.567348E+10 | 0.314887E+10 | 0.252461E+10 | 0.00 | 0.00 |
April | 0.461427E+10 | 0.220981E+10 | 0.426041E+10 | 0.168469E+10 | 0.257572E+10 | 0.00 | 0.00 |
May | 0.443687E+10 | 0.147057E+10 | 0.385808E+10 | 0.804731E+09 | 0.305335E+10 | 0.00 | 0.00 |
June | 0.460453E+10 | 0.784588E+09 | 0.350390E+10 | 0.535604E+09 | 0.296829E+10 | 0.00 | 0.00 |
July | 0.549684E+10 | 0.440581E+09 | 0.379521E+10 | 0.659224E+09 | 0.313599E+10 | 0.00 | 0.00 |
August | 0.738022E+10 | 0.621692E+09 | 0.506808E+10 | 0.187983E+10 | 0.318825E+10 | 0.00 | 0.00 |
September | 0.690888E+10 | 0.115643E+10 | 0.532158E+10 | 0.275253E+10 | 0.256905E+10 | 0.00 | 0.00 |
October | 0.914058E+10 | 0.214546E+10 | 0.753311E+10 | 0.472379E+10 | 0.280931E+10 | 0.00 | 0.00 |
November | 0.531706E+10 | 0.291741E+10 | 0.505506E+10 | 0.303580E+10 | 0.201926E+10 | 0.00 | 0.00 |
December | 0.523511E+10 | 0.373585E+10 | 0.516758E+10 | 0.366864E+10 | 0.149895E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.693832E+11 | 0.262222E+11 | 0.596843E+11 | 0.297754E+11 | 0.299089E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443687E+10 | 0.440581E+09 | 0.350390E+10 | 0.535604E+09 | 0.149895E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914058E+10 | 0.401659E+10 | 0.753311E+10 | 0.472379E+10 | 0.318825E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.808526E+09 | 0.282193E+10 | 0.126707E+10 | 0.518996E+09 | 0.748077E+09 | 0.00 | 0.00 |
February | 0.118418E+10 | 0.262545E+10 | 0.168766E+10 | 0.741225E+09 | 0.946434E+09 | 0.00 | 0.00 |
March | 0.250625E+10 | 0.199103E+10 | 0.275904E+10 | 0.127377E+10 | 0.148527E+10 | 0.00 | 0.00 |
April | 0.298119E+10 | 0.142963E+10 | 0.291823E+10 | 0.124863E+10 | 0.166960E+10 | 0.00 | 0.00 |
May | 0.404071E+10 | 0.965709E+09 | 0.351275E+10 | 0.133400E+10 | 0.217875E+10 | 0.00 | 0.00 |
June | 0.477403E+10 | 0.530631E+09 | 0.372058E+10 | 0.150062E+10 | 0.221997E+10 | 0.00 | 0.00 |
July | 0.494339E+10 | 0.307587E+09 | 0.360068E+10 | 0.135590E+10 | 0.224478E+10 | 0.00 | 0.00 |
August | 0.546335E+10 | 0.422256E+09 | 0.398333E+10 | 0.184402E+10 | 0.213931E+10 | 0.00 | 0.00 |
September | 0.338435E+10 | 0.756738E+09 | 0.273663E+10 | 0.119590E+10 | 0.154073E+10 | 0.00 | 0.00 |
October | 0.313539E+10 | 0.141564E+10 | 0.280360E+10 | 0.136332E+10 | 0.144028E+10 | 0.00 | 0.00 |
November | 0.900140E+09 | 0.198526E+10 | 0.127409E+10 | 0.368220E+09 | 0.905870E+09 | 0.00 | 0.00 |
December | 0.761692E+09 | 0.264841E+10 | 0.117105E+10 | 0.506717E+09 | 0.664336E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348832E+11 | 0.179003E+11 | 0.314347E+11 | 0.132513E+11 | 0.181834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.761692E+09 | 0.307587E+09 | 0.117105E+10 | 0.368220E+09 | 0.664336E+09 | 0.00 | 0.00 |
Maximum of Months | 0.546335E+10 | 0.282193E+10 | 0.398333E+10 | 0.184402E+10 | 0.224478E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.536545E+10 | -0.462770E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -737750364.5 | 58.98 | 0.00 | 0.00 |
February | 0.490147E+10 | -0.424800E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -653466142.5 | 58.98 | 0.00 | 0.00 |
March | 0.562409E+10 | -0.491447E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -709615244.7 | 58.98 | 0.00 | 0.00 |
April | 0.487367E+10 | -0.419565E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -678017940.2 | 58.98 | 0.00 | 0.00 |
May | 0.488296E+10 | -0.419030E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692658952.5 | 58.98 | 0.00 | 0.00 |
June | 0.452683E+10 | -0.385999E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666838385.4 | 58.99 | 0.00 | 0.00 |
July | 0.413126E+10 | -0.344448E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -686779464.4 | 58.98 | 0.00 | 0.00 |
August | 0.444417E+10 | -0.375688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687288023.6 | 58.98 | 0.00 | 0.00 |
September | 0.415555E+10 | -0.348968E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -665871298.1 | 58.98 | 0.00 | 0.00 |
October | 0.453322E+10 | -0.384253E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690685131.2 | 58.98 | 0.00 | 0.00 |
November | 0.475709E+10 | -0.407523E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -681857587.5 | 58.98 | 0.00 | 0.00 |
December | 0.502629E+10 | -0.430913E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717165563.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.572220E+11 | -0.489540E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826799E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.413126E+10 | -0.491447E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -737750364.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.562409E+10 | -0.344448E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -653466142.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 6354.11 | 35.11 | 184.67 | 238.17 | 3323.11 | 33.25 | 181.50 | 194.33 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 9172.14 | 36.59 | 203.17 | 256.00 | 2034.92 | 26.37 | 168.00 | 231.83 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 3154.38 | 20.76 | 45.33 | 316.50 | 1509.40 | 21.40 | 156.67 | 279.83 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:10 | 1970.99 | 18.04 | 0.00 | 338.17 | 1162.60 | 20.84 | 123.17 | 294.50 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1718.20 | 17.95 | 0.00 | 388.83 | 962.87 | 20.68 | 192.00 | 342.83 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:10 | 1633.86 | 17.91 | 0.00 | 379.33 | 928.54 | 20.71 | 172.67 | 336.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:19 | 1806.19 | 18.18 | 0.00 | 388.17 | 1004.34 | 20.97 | 206.50 | 340.50 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 2003.32 | 18.16 | 0.00 | 368.33 | 1159.33 | 20.93 | 209.33 | 335.50 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3702.27 | 20.47 | 29.50 | 322.00 | 1389.10 | 21.15 | 160.83 | 286.67 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 10048.45 | 35.68 | 281.00 | 306.33 | 1952.85 | 23.31 | 250.17 | 287.83 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:49 | 6338.97 | 35.33 | 227.83 | 255.83 | 2199.78 | 29.33 | 218.83 | 234.50 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5878.59 | 34.12 | 179.17 | 237.50 | 5374.44 | 39.07 | 208.17 | 212.00 |
Annual Sum or Average | 3472.67 | 0.63 | 4082.86 | 24.32 | 1150.67 | 3795.17 | 1722.50 | 23.87 | 2247.83 | 3376.33 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1633.86 | 17.91 | 0.00 | 237.50 | 928.54 | 20.68 | 123.17 | 194.33 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 10048.45 | 36.59 | 281.00 | 388.83 | 5374.44 | 39.07 | 250.17 | 342.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1915.63 | 20.60 | 61.00 | 218.17 | 1088.74 | 23.41 | 82.00 | 155.33 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:30 | 2745.56 | 23.34 | 80.67 | 242.00 | 1584.39 | 24.36 | 81.00 | 201.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:49 | 2732.97 | 19.30 | 58.83 | 309.83 | 1580.81 | 22.28 | 63.33 | 251.50 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3739.31 | 21.57 | 80.67 | 338.00 | 1492.68 | 22.63 | 51.67 | 296.67 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 3081.15 | 20.45 | 99.17 | 394.67 | 1664.02 | 22.15 | 72.50 | 350.67 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2740.61 | 19.71 | 80.50 | 384.33 | 1516.78 | 21.82 | 60.83 | 349.33 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2829.30 | 20.31 | 89.17 | 393.50 | 1527.13 | 22.21 | 65.83 | 352.83 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:30 | 3767.77 | 21.15 | 111.67 | 369.50 | 1560.61 | 22.44 | 72.50 | 343.00 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:49 | 3282.22 | 21.13 | 79.67 | 319.17 | 1407.75 | 21.60 | 47.50 | 280.00 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 2857.49 | 21.07 | 78.33 | 289.50 | 1541.80 | 23.58 | 115.67 | 260.17 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1968.39 | 21.16 | 72.00 | 241.33 | 1008.33 | 22.26 | 97.50 | 196.50 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-07:40 | 1755.98 | 20.15 | 64.00 | 213.00 | 1073.37 | 23.80 | 85.67 | 150.50 |
Annual Sum or Average | 3472.67 | 0.64 | 2870.30 | 20.76 | 955.67 | 3713.00 | 1452.45 | 22.60 | 896.00 | 3188.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1755.98 | 19.30 | 58.83 | 213.00 | 1008.33 | 21.60 | 47.50 | 150.50 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3767.77 | 23.34 | 111.67 | 394.67 | 1664.02 | 24.36 | 115.67 | 352.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-08:20 | 598.24 | 14.52 | 0.00 | 202.67 | 365.42 | 17.51 | 0.00 | 110.67 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:09 | 645.26 | 15.43 | 0.00 | 225.83 | 418.43 | 18.54 | 0.00 | 155.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:10 | 858.40 | 16.41 | 0.00 | 306.33 | 534.03 | 19.23 | 1.33 | 229.17 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:10 | 965.93 | 17.40 | 0.00 | 342.33 | 603.08 | 20.18 | 21.83 | 290.17 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1253.60 | 18.17 | 1.83 | 401.83 | 720.17 | 20.92 | 132.83 | 359.00 |
June | 351.83 | 0.62 | 0.62 | 01-JUN-04:00 | 1404.52 | 19.93 | 42.33 | 398.50 | 794.48 | 23.37 | 196.50 | 371.50 |
July | 365.17 | 0.62 | 0.62 | 01-JUL-04:00 | 1390.93 | 18.36 | 0.00 | 405.00 | 786.58 | 22.92 | 197.67 | 368.17 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 1140.87 | 17.84 | 0.00 | 377.50 | 687.36 | 20.58 | 103.67 | 346.33 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 884.69 | 16.95 | 0.00 | 317.17 | 558.05 | 19.80 | 4.17 | 263.17 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 800.52 | 16.56 | 0.00 | 286.17 | 517.41 | 19.56 | 0.00 | 239.00 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 668.76 | 15.24 | 0.00 | 230.50 | 399.70 | 18.14 | 0.00 | 144.83 |
December | 211.17 | 0.67 | 0.62 | 01-DEC-08:09 | 481.23 | 13.46 | 0.00 | 188.33 | 303.60 | 16.65 | 0.00 | 79.33 |
Annual Sum or Average | 3472.67 | 0.64 | 984.58 | 17.02 | 44.17 | 3682.17 | 589.60 | 20.14 | 658.00 | 2956.83 | ||
Minimum of Months | 199.50 | 0.62 | 0.62 | 481.23 | 13.46 | 0.00 | 188.33 | 303.60 | 16.65 | 0.00 | 79.33 | |
Maximum of Months | 389.17 | 0.67 | 0.62 | 1404.52 | 19.93 | 42.33 | 405.00 | 794.48 | 23.37 | 197.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-08:20 | 1826.33 | 20.26 | 57.17 | 222.83 | 1077.28 | 23.51 | 71.83 | 157.33 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:20 | 2122.28 | 20.65 | 57.00 | 241.67 | 1105.71 | 21.96 | 52.67 | 198.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:10 | 2926.59 | 20.27 | 70.83 | 313.50 | 1741.33 | 24.25 | 81.33 | 264.33 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:30 | 3526.99 | 21.24 | 76.83 | 337.17 | 1408.11 | 21.20 | 37.50 | 294.67 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:49 | 3263.03 | 18.44 | 69.17 | 391.50 | 1456.13 | 18.66 | 0.00 | 353.00 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:19 | 3196.33 | 14.96 | 1.83 | 389.00 | 1721.24 | 18.84 | 0.67 | 347.00 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 2999.96 | 17.71 | 49.00 | 394.17 | 1601.57 | 18.96 | 2.17 | 351.83 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:00 | 3842.48 | 19.56 | 86.33 | 370.50 | 1672.44 | 19.10 | 9.50 | 342.17 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-06:19 | 3130.15 | 21.70 | 85.17 | 319.17 | 1624.63 | 22.85 | 63.17 | 279.50 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 3358.77 | 23.45 | 109.33 | 301.17 | 1402.93 | 23.15 | 95.33 | 272.17 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 1606.39 | 20.32 | 68.83 | 242.67 | 875.53 | 22.93 | 81.83 | 197.67 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-08:09 | 1509.04 | 20.43 | 67.50 | 216.00 | 819.04 | 21.40 | 59.17 | 153.33 |
Annual Sum or Average | 3472.67 | 0.63 | 2909.22 | 19.69 | 799.00 | 3739.33 | 1428.10 | 21.08 | 555.17 | 3211.50 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1509.04 | 14.96 | 1.83 | 216.00 | 819.04 | 18.66 | 0.00 | 153.33 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3842.48 | 23.45 | 109.33 | 394.17 | 1741.33 | 24.25 | 95.33 | 353.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 6094.26 | 32.57 | 169.00 | 233.67 | 3193.82 | 32.15 | 144.17 | 191.17 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 8981.88 | 36.24 | 203.17 | 253.67 | 1912.07 | 24.80 | 80.17 | 231.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 3024.92 | 17.48 | 45.00 | 317.00 | 1397.22 | 18.90 | 31.33 | 274.83 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 1860.68 | 14.49 | 0.00 | 335.17 | 1086.66 | 18.50 | 1.50 | 290.33 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1635.12 | 14.48 | 0.00 | 386.67 | 911.75 | 18.34 | 0.00 | 338.00 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:19 | 1557.45 | 14.46 | 0.00 | 377.00 | 882.81 | 18.39 | 0.00 | 333.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:19 | 1720.49 | 14.66 | 0.00 | 384.50 | 952.63 | 18.58 | 0.00 | 335.67 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 1896.92 | 14.77 | 0.00 | 365.17 | 1089.15 | 18.68 | 6.50 | 332.17 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3560.66 | 17.19 | 29.50 | 319.83 | 1288.03 | 18.67 | 8.50 | 282.67 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 9835.71 | 35.04 | 278.50 | 303.67 | 1808.73 | 20.60 | 33.67 | 285.00 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:49 | 6142.05 | 33.73 | 217.17 | 253.83 | 2075.39 | 27.31 | 119.83 | 231.33 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5702.86 | 33.30 | 178.83 | 236.00 | 5214.35 | 37.65 | 198.67 | 207.17 |
Annual Sum or Average | 3472.67 | 0.63 | 3945.28 | 21.67 | 1121.17 | 3766.17 | 1630.08 | 21.68 | 624.33 | 3333.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1557.45 | 14.46 | 0.00 | 233.67 | 882.81 | 18.34 | 0.00 | 191.17 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 9835.71 | 36.24 | 278.50 | 386.67 | 5214.35 | 37.65 | 198.67 | 338.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1847.26 | 20.10 | 60.50 | 215.33 | 1044.85 | 23.18 | 74.00 | 150.83 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-07:40 | 2491.71 | 20.53 | 61.33 | 239.67 | 1529.67 | 24.16 | 72.17 | 196.83 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:49 | 2634.01 | 18.78 | 57.83 | 308.33 | 1517.99 | 22.08 | 56.17 | 245.50 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3643.93 | 21.18 | 80.67 | 335.50 | 1420.49 | 22.46 | 50.67 | 293.17 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 2879.02 | 18.56 | 75.67 | 392.50 | 1594.50 | 21.98 | 72.50 | 344.67 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2651.08 | 19.30 | 80.50 | 382.17 | 1454.71 | 21.65 | 60.83 | 344.83 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2731.76 | 19.92 | 89.17 | 391.33 | 1461.92 | 22.04 | 65.00 | 349.67 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:30 | 3667.15 | 20.76 | 111.67 | 368.00 | 1487.11 | 22.27 | 69.50 | 340.00 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:49 | 3192.75 | 20.71 | 79.67 | 316.33 | 1339.37 | 21.40 | 44.67 | 275.50 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 2768.06 | 20.64 | 78.33 | 287.50 | 1476.10 | 23.38 | 97.00 | 256.67 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1900.94 | 20.73 | 71.83 | 238.00 | 959.83 | 22.02 | 83.83 | 191.67 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-07:40 | 1703.67 | 19.70 | 64.00 | 211.17 | 1034.40 | 23.58 | 81.33 | 144.17 |
Annual Sum or Average | 3472.67 | 0.64 | 2760.24 | 20.03 | 911.17 | 3685.83 | 1390.15 | 22.41 | 827.67 | 3133.50 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1703.67 | 18.56 | 57.83 | 211.17 | 959.83 | 21.40 | 44.67 | 144.17 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3667.15 | 21.18 | 111.67 | 392.50 | 1594.50 | 24.16 | 97.00 | 349.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.62 | 01-JAN-08:20 | 570.94 | 11.10 | 0.00 | 196.33 | 350.98 | 15.17 | 0.00 | 103.50 |
February | 216.00 | 0.65 | 0.62 | 01-FEB-08:20 | 616.33 | 12.15 | 0.00 | 221.50 | 403.47 | 16.40 | 0.00 | 148.00 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-07:10 | 821.76 | 13.33 | 0.00 | 304.33 | 515.01 | 17.27 | 0.00 | 220.83 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:10 | 925.54 | 14.35 | 0.00 | 339.33 | 582.17 | 18.35 | 0.00 | 283.17 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1200.59 | 14.85 | 1.83 | 399.17 | 691.64 | 18.82 | 11.83 | 354.00 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1346.68 | 16.98 | 41.00 | 396.33 | 762.67 | 21.56 | 59.67 | 368.00 |
July | 365.17 | 0.62 | 0.62 | 01-JUL-04:00 | 1332.84 | 14.97 | 0.00 | 402.33 | 754.78 | 21.04 | 49.67 | 364.17 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 1092.97 | 14.81 | 0.00 | 375.00 | 662.17 | 18.75 | 1.50 | 343.33 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 847.09 | 13.93 | 0.00 | 314.00 | 538.61 | 17.94 | 0.00 | 256.50 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 764.04 | 13.53 | 0.00 | 283.17 | 498.45 | 17.61 | 0.00 | 231.33 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 638.85 | 11.71 | 0.00 | 226.33 | 383.82 | 15.75 | 0.00 | 137.33 |
December | 211.17 | 0.67 | 0.62 | 01-DEC-08:09 | 458.71 | 9.95 | 0.00 | 181.00 | 291.75 | 14.21 | 0.00 | 71.50 |
Annual Sum or Average | 3472.67 | 0.64 | 942.52 | 13.83 | 42.83 | 3638.83 | 567.23 | 18.13 | 122.67 | 2881.67 | ||
Minimum of Months | 199.50 | 0.62 | 0.62 | 458.71 | 9.95 | 0.00 | 181.00 | 291.75 | 14.21 | 0.00 | 71.50 | |
Maximum of Months | 389.17 | 0.67 | 0.62 | 1346.68 | 16.98 | 41.00 | 402.33 | 762.67 | 21.56 | 59.67 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-08:20 | 1768.66 | 19.91 | 57.17 | 220.00 | 1035.54 | 23.42 | 70.83 | 153.00 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:20 | 2050.22 | 20.29 | 57.00 | 238.50 | 1052.56 | 21.85 | 51.50 | 193.17 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:10 | 2836.68 | 19.91 | 70.83 | 312.17 | 1673.77 | 24.15 | 80.00 | 257.00 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:30 | 3433.00 | 20.88 | 76.83 | 334.33 | 1336.26 | 21.06 | 37.17 | 291.33 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:49 | 3170.38 | 18.03 | 69.17 | 390.33 | 1391.34 | 18.48 | 0.00 | 347.33 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:30 | 3086.91 | 14.51 | 1.83 | 387.33 | 1647.99 | 18.67 | 0.00 | 342.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 2898.27 | 17.30 | 49.00 | 390.50 | 1532.15 | 18.79 | 1.33 | 347.33 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:00 | 3708.39 | 18.95 | 83.33 | 367.50 | 1596.49 | 18.94 | 9.17 | 339.17 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-06:19 | 2933.53 | 19.65 | 67.50 | 317.00 | 1556.59 | 22.73 | 62.00 | 276.50 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 3262.49 | 23.13 | 109.33 | 298.83 | 1333.34 | 23.05 | 91.50 | 268.67 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 1553.20 | 19.97 | 68.67 | 241.33 | 837.70 | 22.83 | 79.67 | 191.17 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-08:09 | 1458.22 | 20.10 | 67.50 | 212.50 | 781.99 | 21.30 | 58.67 | 149.17 |
Annual Sum or Average | 3472.67 | 0.63 | 2809.10 | 19.15 | 778.17 | 3710.33 | 1364.88 | 20.94 | 541.83 | 3156.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1458.22 | 14.51 | 1.83 | 212.50 | 781.99 | 18.48 | 0.00 | 149.17 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3708.39 | 23.13 | 109.33 | 390.50 | 1673.77 | 24.15 | 91.50 | 347.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-07:49 | 6094.31 | 32.57 | 169.00 | 233.67 | 3193.73 | 32.15 | 144.17 | 191.17 |
February | 216.00 | 0.63 | 0.62 | 01-FEB-07:40 | 8981.88 | 36.24 | 203.17 | 253.67 | 1911.97 | 24.80 | 80.17 | 231.50 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:00 | 3024.85 | 17.48 | 45.00 | 317.00 | 1397.13 | 18.90 | 31.33 | 274.83 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:19 | 1860.61 | 14.50 | 0.00 | 335.17 | 1086.59 | 18.50 | 1.50 | 290.33 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 1635.05 | 14.48 | 0.00 | 386.67 | 911.69 | 18.34 | 0.00 | 338.00 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:19 | 1557.39 | 14.46 | 0.00 | 377.00 | 882.76 | 18.39 | 0.00 | 333.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:19 | 1720.41 | 14.66 | 0.00 | 384.50 | 952.56 | 18.58 | 0.00 | 335.67 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:49 | 1896.85 | 14.77 | 0.00 | 365.17 | 1089.08 | 18.68 | 6.67 | 332.17 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 3560.59 | 17.19 | 29.50 | 319.83 | 1287.95 | 18.67 | 8.50 | 282.67 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 9835.68 | 35.04 | 278.50 | 303.67 | 1808.61 | 20.60 | 33.67 | 285.00 |
November | 240.83 | 0.63 | 0.62 | 01-NOV-06:49 | 6142.06 | 33.73 | 217.17 | 253.83 | 2075.28 | 27.31 | 119.83 | 231.33 |
December | 211.17 | 0.64 | 0.62 | 01-DEC-07:40 | 5702.92 | 33.30 | 178.83 | 236.00 | 5214.28 | 37.65 | 198.67 | 207.17 |
Annual Sum or Average | 3472.67 | 0.63 | 3945.24 | 21.67 | 1121.17 | 3766.17 | 1630.00 | 21.68 | 624.50 | 3333.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1557.39 | 14.46 | 0.00 | 233.67 | 882.76 | 18.34 | 0.00 | 191.17 | |
Maximum of Months | 389.17 | 0.64 | 0.62 | 9835.68 | 36.24 | 278.50 | 386.67 | 5214.28 | 37.65 | 198.67 | 338.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.62 | 01-JAN-07:49 | 1847.26 | 20.10 | 60.50 | 215.33 | 1044.81 | 23.18 | 74.00 | 150.83 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-07:40 | 2491.72 | 20.53 | 61.33 | 239.67 | 1529.63 | 24.16 | 72.33 | 196.83 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-06:49 | 2634.01 | 18.78 | 57.83 | 308.33 | 1517.94 | 22.08 | 56.17 | 245.50 |
April | 261.17 | 0.63 | 0.62 | 01-APR-05:00 | 3643.91 | 21.18 | 80.67 | 335.50 | 1420.43 | 22.46 | 50.67 | 293.17 |
May | 372.00 | 0.64 | 0.62 | 01-MAY-05:40 | 2878.99 | 18.56 | 75.67 | 392.50 | 1594.43 | 21.98 | 72.50 | 344.67 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 2651.05 | 19.30 | 80.50 | 382.17 | 1454.64 | 21.65 | 60.83 | 344.83 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-04:49 | 2731.72 | 19.92 | 89.17 | 391.33 | 1461.85 | 22.04 | 65.00 | 349.67 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:30 | 3667.13 | 20.76 | 111.67 | 368.00 | 1487.05 | 22.27 | 69.50 | 340.00 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:49 | 3192.75 | 20.71 | 79.67 | 316.33 | 1339.31 | 21.40 | 44.67 | 275.50 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 2768.07 | 20.64 | 78.33 | 287.50 | 1476.05 | 23.38 | 97.00 | 256.67 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-06:49 | 1900.94 | 20.73 | 71.83 | 238.00 | 959.78 | 22.02 | 84.00 | 191.67 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-07:40 | 1703.68 | 19.71 | 64.00 | 211.17 | 1034.38 | 23.58 | 81.33 | 144.17 |
Annual Sum or Average | 3472.67 | 0.64 | 2760.23 | 20.03 | 911.17 | 3685.83 | 1390.10 | 22.41 | 828.00 | 3133.50 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1703.68 | 18.56 | 57.83 | 211.17 | 959.78 | 21.40 | 44.67 | 144.17 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3667.13 | 21.18 | 111.67 | 392.50 | 1594.43 | 24.16 | 97.00 | 349.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.62 | 01-JAN-08:20 | 570.94 | 11.10 | 0.00 | 196.33 | 350.96 | 15.17 | 0.00 | 103.50 |
February | 216.00 | 0.65 | 0.62 | 01-FEB-08:20 | 616.34 | 12.15 | 0.00 | 221.50 | 403.46 | 16.40 | 0.00 | 148.00 |
March | 275.00 | 0.65 | 0.62 | 01-MAR-07:10 | 821.75 | 13.33 | 0.00 | 304.33 | 514.98 | 17.27 | 0.00 | 220.67 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:10 | 925.53 | 14.35 | 0.00 | 339.33 | 582.14 | 18.35 | 0.00 | 283.17 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:40 | 1200.57 | 14.85 | 1.83 | 399.17 | 691.60 | 18.83 | 11.83 | 354.00 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-04:00 | 1346.65 | 16.98 | 41.00 | 396.33 | 762.63 | 21.56 | 59.67 | 368.00 |
July | 365.17 | 0.62 | 0.62 | 01-JUL-04:00 | 1332.82 | 14.98 | 0.00 | 402.33 | 754.73 | 21.04 | 49.67 | 364.00 |
August | 389.17 | 0.63 | 0.62 | 01-AUG-05:40 | 1092.97 | 14.81 | 0.00 | 375.00 | 662.14 | 18.75 | 1.50 | 343.33 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-05:00 | 847.09 | 13.94 | 0.00 | 314.00 | 538.58 | 17.94 | 0.00 | 256.50 |
October | 305.50 | 0.64 | 0.62 | 01-OCT-14:39 | 764.05 | 13.54 | 0.00 | 283.17 | 498.43 | 17.61 | 0.00 | 231.33 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 638.84 | 11.71 | 0.00 | 226.33 | 383.79 | 15.75 | 0.00 | 137.33 |
December | 211.17 | 0.67 | 0.62 | 01-DEC-08:09 | 458.71 | 9.96 | 0.00 | 181.00 | 291.74 | 14.21 | 0.00 | 71.50 |
Annual Sum or Average | 3472.67 | 0.64 | 942.51 | 13.83 | 42.83 | 3638.83 | 567.19 | 18.13 | 122.67 | 2881.33 | ||
Minimum of Months | 199.50 | 0.62 | 0.62 | 458.71 | 9.96 | 0.00 | 181.00 | 291.74 | 14.21 | 0.00 | 71.50 | |
Maximum of Months | 389.17 | 0.67 | 0.62 | 1346.65 | 16.98 | 41.00 | 402.33 | 762.63 | 21.56 | 59.67 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.62 | 01-JAN-08:20 | 1768.66 | 19.92 | 57.17 | 220.00 | 1035.50 | 23.42 | 70.83 | 153.00 |
February | 216.00 | 0.64 | 0.62 | 01-FEB-08:20 | 2050.23 | 20.29 | 57.00 | 238.50 | 1052.52 | 21.85 | 51.83 | 193.17 |
March | 275.00 | 0.64 | 0.62 | 01-MAR-07:10 | 2836.68 | 19.91 | 70.83 | 312.17 | 1673.71 | 24.15 | 80.00 | 257.00 |
April | 261.17 | 0.63 | 0.62 | 01-APR-06:30 | 3432.99 | 20.88 | 76.83 | 334.33 | 1336.20 | 21.06 | 37.17 | 291.33 |
May | 372.00 | 0.63 | 0.62 | 01-MAY-05:49 | 3170.34 | 18.04 | 69.17 | 390.33 | 1391.27 | 18.48 | 0.00 | 347.33 |
June | 351.83 | 0.63 | 0.62 | 01-JUN-05:30 | 3086.88 | 14.52 | 1.83 | 387.33 | 1647.91 | 18.67 | 0.00 | 342.17 |
July | 365.17 | 0.63 | 0.62 | 01-JUL-05:30 | 2898.23 | 17.30 | 49.00 | 390.50 | 1532.07 | 18.79 | 1.33 | 347.33 |
August | 389.17 | 0.64 | 0.62 | 01-AUG-05:00 | 3708.37 | 18.95 | 83.33 | 367.50 | 1596.42 | 18.95 | 9.17 | 339.17 |
September | 285.33 | 0.63 | 0.62 | 01-SEP-06:19 | 2933.52 | 19.65 | 67.50 | 317.00 | 1556.53 | 22.73 | 62.00 | 276.50 |
October | 305.50 | 0.63 | 0.62 | 01-OCT-14:39 | 3262.50 | 23.13 | 109.33 | 298.83 | 1333.29 | 23.05 | 91.67 | 268.67 |
November | 240.83 | 0.64 | 0.62 | 01-NOV-07:10 | 1553.19 | 19.97 | 68.67 | 241.33 | 837.65 | 22.83 | 79.67 | 191.17 |
December | 211.17 | 0.65 | 0.62 | 01-DEC-08:09 | 1458.23 | 20.10 | 67.50 | 212.50 | 781.96 | 21.30 | 58.67 | 149.17 |
Annual Sum or Average | 3472.67 | 0.63 | 2809.09 | 19.16 | 778.17 | 3710.33 | 1364.82 | 20.94 | 542.33 | 3156.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.62 | 1458.23 | 14.52 | 1.83 | 212.50 | 781.96 | 18.48 | 0.00 | 149.17 | |
Maximum of Months | 389.17 | 0.65 | 0.62 | 3708.37 | 23.13 | 109.33 | 390.50 | 1673.71 | 24.15 | 91.67 | 347.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.690780E+09 | 29489.77 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1716120.80 | 28602.01 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.690780E+09 | 29489.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.733899E+10 | 12261.19 | 18-JAN-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.628346E+10 | 12236.64 | 28-FEB-18:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459517E+10 | 12257.12 | 06-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252706E+10 | 12236.35 | 14-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.900896E+09 | 12273.56 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35988735.35 | 6457.95 | 02-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121082E+09 | 12339.48 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.635661E+09 | 12475.58 | 16-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306121E+10 | 12264.36 | 14-NOV-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.515403E+10 | 12212.44 | 04-DEC-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.733899E+10 | 12475.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262827E+10 | 9621.10 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193946E+10 | 9621.10 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.791597E+09 | 9621.10 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.295372E+09 | 9621.10 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7147549.46 | 1620.24 | 04-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51318.38 | 44.86 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.465959E+09 | 9621.10 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134525E+10 | 9621.10 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.747311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.262827E+10 | 9621.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369940E+10 | 8952.05 | 24-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310894E+10 | 8913.97 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114471E+10 | 8932.73 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.286313E+09 | 8921.05 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 487790.81 | 2310.35 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.543466E+09 | 8928.44 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164777E+10 | 8938.45 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.369940E+10 | 8952.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.284818E+10 | 9705.38 | 01-JAN-01:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223145E+10 | 9705.38 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870995E+09 | 9705.38 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316949E+09 | 9705.38 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12782193.75 | 4469.91 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 182603.19 | 77.78 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632389E+09 | 9705.38 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155948E+10 | 9705.38 | 01-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.847241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284818E+10 | 9705.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190079E+10 | 25522.35 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.782427E+09 | 25522.35 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42559615.25 | 25522.35 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5887879.93 | 25522.35 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186383E+09 | 25522.35 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290907E+09 | 25522.35 | 07-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190079E+10 | 25522.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283934E+10 | 13566.20 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189761E+10 | 13568.50 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.675769E+09 | 13483.05 | 31-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.255044E+09 | 13482.12 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2000564.63 | 4426.51 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5823291.74 | 5214.53 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.666226E+09 | 13495.92 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160076E+10 | 13551.40 | 11-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283934E+10 | 13568.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295432E+10 | 10400.95 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213616E+10 | 10400.95 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.852628E+09 | 10400.95 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.310307E+09 | 10400.95 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2207079.83 | 1601.74 | 04-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23204823.16 | 6634.96 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.901403E+09 | 10400.95 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191659E+10 | 10400.95 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.909682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295432E+10 | 10400.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.370857E+10 | 9807.13 | 19-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288922E+10 | 9798.11 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.841067E+09 | 9762.38 | 09-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182205E+09 | 9782.13 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7418174.14 | 5508.14 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.918078E+09 | 9797.40 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210725E+10 | 9792.67 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370857E+10 | 9807.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311344E+10 | 10484.39 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238813E+10 | 10484.39 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949269E+09 | 10484.39 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334853E+09 | 10484.39 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7744455.13 | 4643.50 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36336565.86 | 6619.39 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106723E+10 | 10484.39 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209100E+10 | 10484.39 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311344E+10 | 10484.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519439E+10 | 35120.66 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371018E+10 | 35032.50 | 21-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.832498E+09 | 35055.41 | 09-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241834E+09 | 34952.03 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137782E+10 | 35055.22 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277911E+10 | 35092.82 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519439E+10 | 35120.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.478682E+10 | 15126.71 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363026E+10 | 15105.89 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177503E+10 | 15078.61 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797418E+09 | 15074.42 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40653509.75 | 11091.82 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100841.88 | 336.14 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115004E+09 | 12093.23 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163379E+10 | 15110.94 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323715E+10 | 15138.19 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.478682E+10 | 15138.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428869E+10 | 12033.38 | 24-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336416E+10 | 12000.97 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156796E+10 | 12007.05 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646274E+09 | 11978.02 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28987335.13 | 5915.38 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2566474.94 | 1668.97 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147454E+09 | 7782.11 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168729E+10 | 12018.53 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312444E+10 | 12023.46 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428869E+10 | 12033.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.614611E+10 | 11266.51 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521037E+10 | 11234.21 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217760E+10 | 11245.09 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.694529E+09 | 11215.92 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18622222.93 | 10820.36 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 210552.33 | 184.62 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153845E+09 | 11171.43 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222421E+10 | 11226.56 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.433018E+10 | 11243.18 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.614611E+10 | 11266.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468252E+10 | 13065.12 | 24-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.386977E+10 | 13007.87 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190423E+10 | 13029.62 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.795936E+09 | 13005.00 | 22-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63553537.78 | 7176.59 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11982970.66 | 2182.75 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232827E+09 | 7860.01 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207609E+10 | 13027.65 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353680E+10 | 13054.37 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.468252E+10 | 13065.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.697984E+10 | 24179.21 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674291E+10 | 23228.76 | 06-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199939E+10 | 11320.10 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110494E+09 | 4756.56 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7389178.70 | 1671.36 | 28-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124788E+10 | 12092.27 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337017E+10 | 11369.60 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697984E+10 | 24179.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.951319E+10 | 24019.74 | 02-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.950302E+10 | 25849.68 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403926E+10 | 14319.03 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.478881E+09 | 7649.87 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48801987.76 | 3955.69 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251283E+10 | 15697.24 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.633336E+10 | 14660.78 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.951319E+10 | 25849.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103875E+11 | 23939.87 | 02-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101488E+11 | 25869.18 | 06-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.434919E+10 | 17481.09 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.719655E+09 | 9593.83 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2648761.46 | 2078.85 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126725E+09 | 6385.54 | 28-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281356E+10 | 17432.98 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693072E+10 | 17567.08 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103875E+11 | 25869.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.529582E+09 | 0.371008E+09 | 25491.30 | 27-MAR-16:00 | 21632.76 | 0.00 |
April | 0.00 | 0.00 | 0.456297E+10 | 0.412868E+10 | 46110.52 | 07-APR-15:40 | 46110.52 | 0.00 |
May | 0.00 | 0.00 | 0.180594E+11 | 0.151629E+11 | 83690.32 | 30-MAY-14:00 | 83690.32 | 0.00 |
June | 0.00 | 0.00 | 0.626865E+11 | 0.490376E+11 | 102652.39 | 27-JUN-04:02 | 62594.01 | 0.00 |
July | 0.00 | 0.00 | 0.885899E+11 | 0.665681E+11 | 128767.83 | 22-JUL-04:02 | 62908.87 | 0.00 |
August | 0.00 | 0.00 | 0.905460E+11 | 0.726840E+11 | 124899.53 | 04-AUG-04:02 | 73461.07 | 0.00 |
September | 0.00 | 0.00 | 0.477768E+11 | 0.388690E+11 | 109298.85 | 08-SEP-04:02 | 68459.20 | 0.00 |
October | 0.00 | 0.00 | 0.206076E+11 | 0.146168E+11 | 71533.61 | 05-OCT-12:20 | 50555.06 | 0.00 |
November | 0.00 | 0.00 | 0.475274E+09 | 0.384216E+09 | 11443.78 | 03-NOV-14:00 | 11443.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.333834E+12 | 0.261822E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.905460E+11 | 0.726840E+11 | 128767.83 | 83690.32 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.496203E+09 | 0.344755E+09 | 23412.40 | 27-MAR-16:00 | 19185.25 | 0.00 |
April | 0.00 | 0.00 | 0.470562E+10 | 0.423883E+10 | 48368.38 | 07-APR-14:30 | 48368.38 | 0.00 |
May | 0.00 | 0.00 | 0.175629E+11 | 0.149454E+11 | 85277.05 | 30-MAY-14:10 | 85277.05 | 0.00 |
June | 0.00 | 0.00 | 0.581711E+11 | 0.452525E+11 | 108547.90 | 19-JUN-04:02 | 67282.91 | 0.00 |
July | 0.00 | 0.00 | 0.815573E+11 | 0.606027E+11 | 122565.27 | 22-JUL-04:02 | 55932.67 | 0.00 |
August | 0.00 | 0.00 | 0.811530E+11 | 0.650192E+11 | 118629.41 | 17-AUG-04:02 | 67830.13 | 0.00 |
September | 0.00 | 0.00 | 0.413605E+11 | 0.332293E+11 | 89946.03 | 01-SEP-05:02 | 58923.66 | 0.00 |
October | 0.00 | 0.00 | 0.179185E+11 | 0.126484E+11 | 65469.64 | 06-OCT-05:03 | 27910.23 | 0.00 |
November | 0.00 | 0.00 | 0.453492E+09 | 0.378693E+09 | 9841.78 | 03-NOV-14:00 | 9841.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.303379E+12 | 0.236660E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.815573E+11 | 0.650192E+11 | 122565.27 | 85277.05 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.517691E+09 | 0.353137E+09 | 24736.84 | 27-MAR-16:00 | 19669.52 | 0.00 |
April | 0.00 | 0.00 | 0.488536E+10 | 0.436318E+10 | 53093.15 | 07-APR-14:30 | 53093.15 | 0.00 |
May | 0.00 | 0.00 | 0.182152E+11 | 0.155398E+11 | 94000.76 | 30-MAY-14:00 | 94000.76 | 0.00 |
June | 0.00 | 0.00 | 0.610766E+11 | 0.480851E+11 | 105264.19 | 19-JUN-04:02 | 62487.94 | 0.00 |
July | 0.00 | 0.00 | 0.863920E+11 | 0.652410E+11 | 129352.39 | 31-JUL-04:02 | 80793.58 | 0.00 |
August | 0.00 | 0.00 | 0.852770E+11 | 0.692683E+11 | 132379.72 | 17-AUG-04:02 | 71122.07 | 0.00 |
September | 0.00 | 0.00 | 0.417880E+11 | 0.334021E+11 | 99488.89 | 14-SEP-05:02 | 53390.11 | 0.00 |
October | 0.00 | 0.00 | 0.173422E+11 | 0.120577E+11 | 63970.50 | 04-OCT-14:00 | 54258.96 | 0.00 |
November | 0.00 | 0.00 | 0.399527E+09 | 0.320800E+09 | 9647.50 | 04-NOV-12:40 | 7750.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315894E+12 | 0.248631E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.863920E+11 | 0.692683E+11 | 132379.72 | 94000.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1880.44 | 6599.94 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1908.71 | 6609.81 | 08-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1991.40 | 6546.52 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1771.41 | 6245.14 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1719.64 | 5924.72 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1646.18 | 5483.74 | 02-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1438.43 | 5117.05 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1560.07 | 4996.92 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.32 | 5228.50 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1587.83 | 5634.10 | 30-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1726.39 | 6050.75 | 30-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1760.14 | 6407.45 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1706.35 | ||||
Minimum of Months | 0.00 | 0.00 | 1438.43 | 4996.92 | ||
Maximum of Months | 0.00 | 0.00 | 1991.40 | 6609.81 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169384E+10 | 0.29 | 2555.70 | 02-JAN-05:01 | 0.74 |
February | 0.151023E+10 | 0.28 | 1744.43 | 06-FEB-07:01 | 0.61 |
March | 0.194047E+10 | 0.30 | 3033.26 | 30-MAR-07:03 | 0.81 |
April | 0.220520E+10 | 0.31 | 4900.43 | 08-APR-05:03 | 1.06 |
May | 0.321059E+10 | 0.38 | 8902.95 | 30-MAY-12:10 | 1.53 |
June | 0.495462E+10 | 0.49 | 10039.31 | 19-JUN-12:09 | 1.64 |
July | 0.603707E+10 | 0.53 | 11204.25 | 10-JUL-04:02 | 1.77 |
August | 0.668749E+10 | 0.57 | 11204.25 | 03-AUG-04:02 | 1.77 |
September | 0.449511E+10 | 0.46 | 8692.28 | 05-SEP-04:02 | 1.51 |
October | 0.361060E+10 | 0.39 | 7284.30 | 05-OCT-16:00 | 1.34 |
November | 0.195822E+10 | 0.29 | 4900.43 | 02-NOV-05:02 | 1.07 |
December | 0.164777E+10 | 0.27 | 2143.31 | 22-DEC-08:08 | 0.67 |
Annual Sum or Average | 0.399512E+11 | 0.38 | |||
Minimum of Months | 0.151023E+10 | 0.27 | 1744.43 | 0.61 | |
Maximum of Months | 0.668749E+10 | 0.57 | 11204.25 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184894E+10 | 0.33 | 2672.07 | 02-JAN-05:01 | 0.83 |
February | 0.163091E+10 | 0.32 | 2672.07 | 01-FEB-07:01 | 0.82 |
March | 0.191193E+10 | 0.33 | 2672.07 | 13-MAR-06:01 | 0.82 |
April | 0.213715E+10 | 0.34 | 5460.42 | 10-APR-15:20 | 1.24 |
May | 0.319157E+10 | 0.41 | 10160.28 | 30-MAY-14:10 | 1.83 |
June | 0.496604E+10 | 0.53 | 9286.88 | 19-JUN-16:00 | 1.72 |
July | 0.602707E+10 | 0.57 | 10674.33 | 07-JUL-04:02 | 1.88 |
August | 0.676401E+10 | 0.62 | 10674.33 | 05-AUG-04:02 | 1.88 |
September | 0.394781E+10 | 0.46 | 9744.28 | 05-SEP-15:20 | 1.77 |
October | 0.295405E+10 | 0.38 | 6908.57 | 04-OCT-15:50 | 1.43 |
November | 0.172467E+10 | 0.30 | 2763.74 | 02-NOV-14:30 | 0.84 |
December | 0.169141E+10 | 0.30 | 2672.07 | 07-DEC-07:01 | 0.82 |
Annual Sum or Average | 0.387956E+11 | 0.41 | |||
Minimum of Months | 0.163091E+10 | 0.30 | 2672.07 | 0.82 | |
Maximum of Months | 0.676401E+10 | 0.62 | 10674.33 | 1.88 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.211816E+10 | 0.35 | 2527.90 | 02-JAN-05:01 | 0.72 |
February | 0.182301E+10 | 0.33 | 2527.90 | 01-FEB-06:01 | 0.72 |
March | 0.185950E+10 | 0.30 | 2527.90 | 01-MAR-07:01 | 0.72 |
April | 0.196319E+10 | 0.30 | 4976.73 | 07-APR-15:20 | 1.05 |
May | 0.284349E+10 | 0.36 | 9732.28 | 30-MAY-14:00 | 1.59 |
June | 0.440400E+10 | 0.45 | 10004.98 | 19-JUN-13:40 | 1.61 |
July | 0.543596E+10 | 0.49 | 11590.05 | 10-JUL-04:02 | 1.77 |
August | 0.608379E+10 | 0.52 | 11590.05 | 05-AUG-04:02 | 1.76 |
September | 0.334566E+10 | 0.38 | 8574.57 | 05-SEP-15:10 | 1.46 |
October | 0.242494E+10 | 0.32 | 5926.78 | 04-OCT-15:30 | 1.16 |
November | 0.168518E+10 | 0.28 | 2527.90 | 15-NOV-07:01 | 0.72 |
December | 0.178131E+10 | 0.30 | 2527.90 | 02-DEC-06:01 | 0.72 |
Annual Sum or Average | 0.357682E+11 | 0.37 | |||
Minimum of Months | 0.168518E+10 | 0.28 | 2527.90 | 0.72 | |
Maximum of Months | 0.608379E+10 | 0.52 | 11590.05 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.49 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.60 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.80 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 56.46 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.61 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.37 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.18 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 56.74 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:02 | 0.22 | 0.22 | 56.24 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.73 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.85 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.64 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.24 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.73 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.41 | 57.41 | 1880.44 | 6599.94 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.05 | 57.05 | 1908.71 | 6609.81 | 08-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.16 | 57.16 | 1991.40 | 6546.52 | 03-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.89 | 56.89 | 1771.41 | 6245.14 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.15 | 57.15 | 1719.64 | 5924.72 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.73 | 56.73 | 1646.18 | 5483.74 | 02-JUN-11:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.52 | 57.52 | 1438.43 | 5117.05 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.03 | 57.03 | 1560.07 | 4996.92 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.53 | 56.53 | 1499.32 | 5228.50 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.02 | 57.02 | 1587.83 | 5634.10 | 30-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.27 | 57.27 | 1726.39 | 6050.75 | 30-NOV-12:06 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.36 | 57.36 | 1760.14 | 6407.45 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1706.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.53 | 56.53 | 1438.43 | 4996.92 | ||
Maximum of Months | 0.00 | 0.00 | 57.52 | 57.52 | 1991.40 | 6609.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188995E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150753E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.948084E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.680921E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.874413E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.202687E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.278351E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.293052E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.162012E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.923865E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.679504E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.113543E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180007E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.679504E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293052E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163654E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.117245E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.540283E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.443921E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.768654E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.191495E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.260561E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270129E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140222E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.739566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.559155E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.969792E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154544E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.443921E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270129E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.272167E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.216077E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.102528E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.640525E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.767372E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.193827E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.266990E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.274236E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.136262E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.735566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107976E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187890E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.197230E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.640525E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.274236E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169384E+10 | 0.00 | 0.241855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151023E+10 | 0.00 | 0.203079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194047E+10 | 0.529582E+09 | 0.940186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220520E+10 | 0.456297E+10 | 0.353619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.321059E+10 | 0.180594E+11 | 0.921313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.495462E+10 | 0.626865E+11 | 35988735.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603707E+10 | 0.885899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668749E+10 | 0.905460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.449511E+10 | 0.477768E+11 | 0.121082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361060E+10 | 0.206076E+11 | 0.643284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195822E+10 | 0.475274E+09 | 0.595091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164777E+10 | 0.00 | 0.130767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399512E+11 | 0.333834E+12 | 0.781807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668749E+10 | 0.905460E+11 | 0.241855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.184894E+10 | 0.00 | 0.240296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163091E+10 | 0.00 | 0.195966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191193E+10 | 0.496203E+09 | 0.740056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213715E+10 | 0.470562E+10 | 0.156718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.319157E+10 | 0.175629E+11 | 11952099.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.496604E+10 | 0.581711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602707E+10 | 0.815573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.676401E+10 | 0.811530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394781E+10 | 0.413605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295405E+10 | 0.179185E+11 | 0.121585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172467E+10 | 0.453492E+09 | 0.625215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169141E+10 | 0.00 | 0.143399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387956E+11 | 0.303379E+12 | 0.733195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676401E+10 | 0.815573E+11 | 0.240296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.211816E+10 | 0.00 | 0.354860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182301E+10 | 0.00 | 0.299336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185950E+10 | 0.517691E+09 | 0.126065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196319E+10 | 0.488536E+10 | 0.389565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284349E+10 | 0.182152E+11 | 0.154465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440400E+10 | 0.610766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543596E+10 | 0.863920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.608379E+10 | 0.852770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334566E+10 | 0.417880E+11 | 14860839.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242494E+10 | 0.173422E+11 | 0.775856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168518E+10 | 0.399527E+09 | 0.118128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178131E+10 | 0.00 | 0.239384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357682E+11 | 0.315894E+12 | 0.118618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.608379E+10 | 0.863920E+11 | 0.354860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194047E+10 | 0.00 | 0.00 | 0.00 | 0.137902E+09 | 0.740247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220520E+10 | 0.00 | 0.00 | 0.00 | 0.117831E+10 | 0.342570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.321059E+10 | 0.00 | 0.00 | 0.00 | 0.461222E+10 | 0.921313E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.495462E+10 | 0.00 | 0.00 | 0.00 | 0.152781E+11 | 35988735.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603707E+10 | 0.00 | 0.00 | 0.00 | 0.217980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668749E+10 | 0.00 | 0.00 | 0.00 | 0.226177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.449511E+10 | 0.00 | 0.00 | 0.00 | 0.115850E+11 | 0.121082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361060E+10 | 0.00 | 0.00 | 0.00 | 0.499216E+10 | 0.635895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.195822E+10 | 0.00 | 0.00 | 0.00 | 0.133794E+09 | 0.470303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399512E+11 | 0.00 | 0.00 | 0.00 | 0.823332E+11 | 0.577227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668749E+10 | 0.00 | 0.00 | 0.00 | 0.226177E+11 | 0.172056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.184894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191193E+10 | 0.00 | 0.00 | 0.00 | 0.129606E+09 | 0.336129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213715E+10 | 0.00 | 0.00 | 0.00 | 0.121376E+10 | 0.108830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.319157E+10 | 0.00 | 0.00 | 0.00 | 0.448302E+10 | 11952099.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.496604E+10 | 0.00 | 0.00 | 0.00 | 0.141834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602707E+10 | 0.00 | 0.00 | 0.00 | 0.200291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.676401E+10 | 0.00 | 0.00 | 0.00 | 0.202489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394781E+10 | 0.00 | 0.00 | 0.00 | 0.100744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295405E+10 | 0.00 | 0.00 | 0.00 | 0.436882E+10 | 72782854.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172467E+10 | 0.00 | 0.00 | 0.00 | 0.127557E+09 | 0.373932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387956E+11 | 0.00 | 0.00 | 0.00 | 0.748585E+11 | 0.408902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.676401E+10 | 0.00 | 0.00 | 0.00 | 0.202489E+11 | 0.145165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.211816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185950E+10 | 0.00 | 0.00 | 0.00 | 0.135972E+09 | 0.825732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196319E+10 | 0.00 | 0.00 | 0.00 | 0.126607E+10 | 0.317599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.284349E+10 | 0.00 | 0.00 | 0.00 | 0.467841E+10 | 0.151817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440400E+10 | 0.00 | 0.00 | 0.00 | 0.149787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543596E+10 | 0.00 | 0.00 | 0.00 | 0.212631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.608379E+10 | 0.00 | 0.00 | 0.00 | 0.213398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334566E+10 | 0.00 | 0.00 | 0.00 | 0.102657E+11 | 14860839.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242494E+10 | 0.00 | 0.00 | 0.00 | 0.428160E+10 | 0.649131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168518E+10 | 0.00 | 0.00 | 0.00 | 0.113217E+09 | 0.899920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357682E+11 | 0.00 | 0.00 | 0.00 | 0.783224E+11 | 0.831393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.608379E+10 | 0.00 | 0.00 | 0.00 | 0.213398E+11 | 0.250985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.885514E+10 | 0.00 | 0.00 | 8094310.20 | 0.00 | 0.465868E+09 | 0.507923E+10 | 0.00 | 0.29 |
February | 0.791248E+10 | 0.00 | 0.00 | 10134935.61 | 0.00 | 818186.22 | 0.628832E+10 | 0.00 | 0.29 |
March | 0.509498E+10 | 0.00 | 0.00 | 26461228.11 | 0.00 | 0.00 | 0.125300E+11 | 0.00 | 0.44 |
April | 0.251381E+10 | 9047171.76 | 0.00 | 30042539.22 | 0.00 | 0.00 | 0.150019E+11 | 0.00 | 0.66 |
May | 0.129269E+10 | 0.102747E+09 | 0.00 | 39615739.56 | 0.00 | 0.00 | 0.165809E+11 | 0.00 | 1.03 |
June | 0.439925E+09 | 0.317095E+10 | 0.00 | 17324492.90 | 41099698.84 | 0.00 | 0.369891E+10 | 0.00 | 0.69 |
July | 16914288.21 | 0.790918E+10 | 0.00 | 1268825.01 | 0.105921E+09 | 0.00 | 0.137141E+09 | 0.00 | 0.29 |
August | 0.268469E+09 | 0.622619E+10 | 0.00 | 14552729.99 | 86658029.37 | 0.00 | 0.170529E+10 | 0.00 | 0.59 |
September | 0.964666E+09 | 0.197636E+10 | 0.00 | 27603338.42 | 18718218.21 | 0.00 | 0.842694E+10 | 0.00 | 0.86 |
October | 0.166804E+10 | 0.155163E+09 | 0.00 | 43782318.67 | 0.00 | 0.00 | 0.163991E+11 | 0.00 | 0.96 |
November | 0.303009E+10 | 0.00 | 0.00 | 28766343.13 | 0.00 | 0.00 | 0.147788E+11 | 0.00 | 0.53 |
December | 0.632484E+10 | 0.00 | 0.00 | 17428148.50 | 0.00 | 0.00 | 0.844056E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.383821E+11 | 0.195496E+11 | 0.00 | 0.265075E+09 | 0.252397E+09 | 0.466686E+09 | 0.109067E+12 | 0.00 | 0.58 |
Minimum of Months | 16914288.21 | 0.00 | 0.00 | 1268825.01 | 0.00 | 0.00 | 0.137141E+09 | 0.00 | 0.29 |
Maximum of Months | 0.885514E+10 | 0.790918E+10 | 0.00 | 43782318.67 | 0.105921E+09 | 0.465868E+09 | 0.165809E+11 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117311E+11 | 0.00 | 0.00 | 2802.35 | 0.00 | 0.908224E+09 | 20583159.14 | 0.00 | 0.26 |
February | 0.117579E+11 | 0.00 | 0.00 | 13668.82 | 0.00 | 0.384104E+09 | 82934898.82 | 0.00 | 0.25 |
March | 0.105214E+11 | 0.00 | 0.00 | 1951096.47 | 0.00 | 9675810.45 | 0.229469E+10 | 0.00 | 0.32 |
April | 0.549835E+10 | 4997729.16 | 0.00 | 9788461.13 | 0.00 | 483208.82 | 0.609835E+10 | 0.00 | 0.45 |
May | 0.283096E+10 | 91944932.21 | 0.00 | 19996142.04 | 0.00 | 0.00 | 0.908348E+10 | 0.00 | 0.69 |
June | 0.422715E+09 | 0.260257E+10 | 0.00 | 11492874.82 | 36263241.85 | 0.00 | 0.239277E+10 | 0.00 | 0.51 |
July | 24792495.99 | 0.680454E+10 | 0.00 | 1056215.03 | 95653560.74 | 0.00 | 92673262.46 | 0.00 | 0.25 |
August | 0.252309E+09 | 0.545776E+10 | 0.00 | 9892581.98 | 80208990.73 | 0.00 | 0.110592E+10 | 0.00 | 0.45 |
September | 0.117778E+10 | 0.168786E+10 | 0.00 | 15142455.05 | 18006479.11 | 0.00 | 0.468320E+10 | 0.00 | 0.58 |
October | 0.272470E+10 | 0.156122E+09 | 0.00 | 18779894.10 | 2453840.34 | 0.00 | 0.776734E+10 | 0.00 | 0.58 |
November | 0.810643E+10 | 0.00 | 0.00 | 4301842.98 | 0.00 | 53549741.56 | 0.319896E+10 | 0.00 | 0.34 |
December | 0.116258E+11 | 0.00 | 0.00 | 56465.44 | 0.00 | 64360521.13 | 0.195771E+09 | 0.00 | 0.25 |
Annual Sum or Average | 0.666742E+11 | 0.168058E+11 | 0.00 | 92474500.21 | 0.232586E+09 | 0.142040E+10 | 0.370167E+11 | 0.00 | 0.41 |
Minimum of Months | 24792495.99 | 0.00 | 0.00 | 2802.35 | 0.00 | 0.00 | 20583159.14 | 0.00 | 0.25 |
Maximum of Months | 0.117579E+11 | 0.680454E+10 | 0.00 | 19996142.04 | 95653560.74 | 0.908224E+09 | 0.908348E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.942566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236071E+10 | 0.00 | 0.00 | 0.25 |
February | 0.934354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199944E+10 | 0.00 | 0.00 | 0.25 |
March | 0.108733E+11 | 0.00 | 0.00 | 853197.16 | 0.00 | 0.341335E+09 | 0.106225E+10 | 0.00 | 0.32 |
April | 0.661131E+10 | 1454380.27 | 0.00 | 7391273.28 | 1304295.60 | 47000244.98 | 0.446121E+10 | 0.00 | 0.44 |
May | 0.394051E+10 | 72808068.33 | 0.00 | 16818655.33 | 0.00 | 0.00 | 0.794499E+10 | 0.00 | 0.70 |
June | 0.555566E+09 | 0.247581E+10 | 0.00 | 10415388.66 | 32618546.25 | 0.00 | 0.234787E+10 | 0.00 | 0.51 |
July | 31538236.80 | 0.650541E+10 | 0.00 | 1242886.78 | 87751788.92 | 0.00 | 86346022.22 | 0.00 | 0.26 |
August | 0.212153E+09 | 0.518584E+10 | 0.00 | 9327337.93 | 73970549.85 | 0.00 | 0.104214E+10 | 0.00 | 0.46 |
September | 0.172040E+10 | 0.161718E+10 | 0.00 | 11255615.02 | 30149914.36 | 0.00 | 0.366473E+10 | 0.00 | 0.56 |
October | 0.413287E+10 | 99478616.95 | 0.00 | 11463674.50 | 5562960.40 | 0.00 | 0.502435E+10 | 0.00 | 0.55 |
November | 0.850624E+10 | 0.00 | 0.00 | 1149199.83 | 0.00 | 0.601471E+09 | 0.123224E+10 | 0.00 | 0.32 |
December | 0.992594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102703E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.652790E+11 | 0.159580E+11 | 0.00 | 69917228.49 | 0.231358E+09 | 0.637699E+10 | 0.268661E+11 | 0.00 | 0.40 |
Minimum of Months | 31538236.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.108733E+11 | 0.650541E+10 | 0.00 | 16818655.33 | 87751788.92 | 0.236071E+10 | 0.794499E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.530711E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287097E+10 | 0.00 | 0.00 | 0.34 |
February | 0.617778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266025E+10 | 0.00 | 0.00 | 0.33 |
March | 0.216887E+10 | 0.00 | 0.00 | 6286.72 | 0.00 | 0.127181E+10 | 31027304.23 | 0.00 | 0.42 |
April | 0.215381E+10 | 409959.33 | 0.00 | 1073536.93 | 369350.35 | 0.344122E+09 | 0.516164E+09 | 0.00 | 0.56 |
May | 0.154228E+10 | 22949067.71 | 0.00 | 3653142.55 | 0.00 | 5296413.74 | 0.163350E+10 | 0.00 | 0.90 |
June | 0.199793E+09 | 0.776228E+09 | 0.00 | 2660466.63 | 22276980.85 | 0.00 | 0.606345E+09 | 0.00 | 0.71 |
July | 10186729.41 | 0.212762E+10 | 0.00 | 351009.41 | 25443425.15 | 0.00 | 21644348.34 | 0.00 | 0.39 |
August | 89346657.54 | 0.167468E+10 | 0.00 | 2242268.89 | 28249796.10 | 0.00 | 0.246283E+09 | 0.00 | 0.64 |
September | 0.707425E+09 | 0.411310E+09 | 0.00 | 2093611.10 | 35943973.48 | 0.00 | 0.677536E+09 | 0.00 | 0.70 |
October | 0.177073E+10 | 19547485.53 | 0.00 | 1191110.57 | 7191929.29 | 58837649.59 | 0.518823E+09 | 0.00 | 0.66 |
November | 0.176302E+10 | 0.00 | 0.00 | 3952.70 | 0.00 | 0.114580E+10 | 20151020.15 | 0.00 | 0.43 |
December | 0.766915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234664E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.123209E+11 | 0.503274E+10 | 0.00 | 13275385.50 | 0.119475E+09 | 0.107037E+11 | 0.427148E+10 | 0.00 | 0.53 |
Minimum of Months | 10186729.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.216887E+10 | 0.212762E+10 | 0.00 | 3653142.55 | 35943973.48 | 0.287097E+10 | 0.163350E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253379E+10 | 0.00 | 0.00 | 0.56 |
February | 0.138981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206543E+10 | 0.00 | 0.00 | 0.56 |
March | 0.258202E+10 | 0.00 | 0.00 | 215997.65 | 0.00 | 0.904941E+09 | 0.251095E+09 | 0.00 | 0.72 |
April | 0.198225E+10 | 1204132.91 | 0.00 | 1992443.74 | 0.00 | 0.325740E+09 | 0.108048E+10 | 0.00 | 1.01 |
May | 0.164859E+10 | 23326162.54 | 0.00 | 4335378.35 | 0.00 | 3299196.31 | 0.196758E+10 | 0.00 | 1.56 |
June | 0.188583E+09 | 0.617769E+09 | 0.00 | 2834951.25 | 81611030.31 | 0.00 | 0.711514E+09 | 0.00 | 1.10 |
July | 10703673.17 | 0.178096E+10 | 0.00 | 391585.54 | 86676533.22 | 0.00 | 30955005.43 | 0.00 | 0.56 |
August | 79633425.03 | 0.151212E+10 | 0.00 | 2433093.21 | 51433601.63 | 0.00 | 0.315064E+09 | 0.00 | 1.02 |
September | 0.687295E+09 | 0.321023E+09 | 0.00 | 2603045.94 | 98872137.79 | 517428.24 | 0.863376E+09 | 0.00 | 1.17 |
October | 0.154958E+10 | 16316555.19 | 0.00 | 1977155.12 | 9788411.68 | 42765344.58 | 0.979246E+09 | 0.00 | 1.15 |
November | 0.218885E+10 | 0.00 | 0.00 | 29171.76 | 0.00 | 0.868132E+09 | 81129288.71 | 0.00 | 0.73 |
December | 0.137493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196234E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.147372E+11 | 0.427272E+10 | 0.00 | 16812822.56 | 0.328382E+09 | 0.870695E+10 | 0.628045E+10 | 0.00 | 0.89 |
Minimum of Months | 10703673.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.258202E+10 | 0.178096E+10 | 0.00 | 4335378.35 | 98872137.79 | 0.253379E+10 | 0.196758E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157118E+10 | 0.00 | 0.00 | 966797.00 | 0.00 | 0.238327E+10 | 0.655851E+09 | 0.00 | 0.46 |
February | 0.170373E+10 | 0.00 | 0.00 | 1579154.37 | 0.00 | 0.193739E+10 | 0.923591E+09 | 0.00 | 0.47 |
March | 0.246544E+10 | 0.00 | 0.00 | 4058641.18 | 0.00 | 0.903591E+09 | 0.219817E+10 | 0.00 | 0.70 |
April | 0.231444E+10 | 1519460.59 | 0.00 | 4280198.76 | 0.00 | 0.377910E+09 | 0.209214E+10 | 0.00 | 0.93 |
May | 0.219007E+10 | 28351026.34 | 0.00 | 5468637.70 | 795783.48 | 10587172.11 | 0.232947E+10 | 0.00 | 1.26 |
June | 0.324468E+09 | 0.850613E+09 | 0.00 | 2945728.10 | 83817977.10 | 0.00 | 0.712846E+09 | 0.00 | 0.87 |
July | 14497412.14 | 0.243614E+10 | 0.00 | 453492.95 | 80973343.89 | 0.00 | 23495677.00 | 0.00 | 0.46 |
August | 0.123144E+09 | 0.219792E+10 | 0.00 | 3575707.52 | 51701733.21 | 0.00 | 0.370976E+09 | 0.00 | 0.92 |
September | 0.763010E+09 | 0.595170E+09 | 0.00 | 6392247.97 | 74981999.44 | 0.00 | 0.179368E+10 | 0.00 | 1.24 |
October | 0.134586E+10 | 55745571.74 | 0.00 | 8717017.53 | 6244310.26 | 43339563.21 | 0.347642E+10 | 0.00 | 1.39 |
November | 0.213107E+10 | 0.00 | 0.00 | 2971472.91 | 0.00 | 0.858501E+09 | 0.154518E+10 | 0.00 | 0.69 |
December | 0.168665E+10 | 0.00 | 0.00 | 1352033.31 | 0.00 | 0.193338E+10 | 0.710842E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.166336E+11 | 0.616546E+10 | 0.00 | 42761129.31 | 0.298515E+09 | 0.844797E+10 | 0.168327E+11 | 0.00 | 0.82 |
Minimum of Months | 14497412.14 | 0.00 | 0.00 | 453492.95 | 0.00 | 0.00 | 23495677.00 | 0.00 | 0.46 |
Maximum of Months | 0.246544E+10 | 0.243614E+10 | 0.00 | 8717017.53 | 83817977.10 | 0.238327E+10 | 0.347642E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283535E+10 | 0.00 | 0.00 | 0.61 |
February | 0.113503E+10 | 0.00 | 0.00 | 30741.36 | 0.00 | 0.253155E+10 | 85914913.43 | 0.00 | 0.61 |
March | 0.237106E+10 | 0.00 | 0.00 | 886197.68 | 0.00 | 0.113863E+10 | 0.628308E+09 | 0.00 | 0.80 |
April | 0.225486E+10 | 164135.57 | 0.00 | 2333113.78 | 678031.34 | 0.367096E+09 | 0.116743E+10 | 0.00 | 1.13 |
May | 0.205553E+10 | 21710163.54 | 0.00 | 3644090.49 | 766521.91 | 11364995.42 | 0.172501E+10 | 0.00 | 1.64 |
June | 0.286001E+09 | 0.653861E+09 | 0.00 | 2305599.50 | 78197703.60 | 0.00 | 0.563125E+09 | 0.00 | 1.13 |
July | 14214584.40 | 0.176923E+10 | 0.00 | 382431.18 | 0.142025E+09 | 0.00 | 14479725.32 | 0.00 | 0.55 |
August | 0.117335E+09 | 0.154793E+10 | 0.00 | 2029887.32 | 72747921.27 | 0.00 | 0.210579E+09 | 0.00 | 1.02 |
September | 0.905934E+09 | 0.353358E+09 | 0.00 | 2356719.34 | 0.107287E+09 | 1116889.86 | 0.733679E+09 | 0.00 | 1.25 |
October | 0.191517E+10 | 25262431.31 | 0.00 | 2008071.67 | 8437071.83 | 67473848.47 | 0.915366E+09 | 0.00 | 1.28 |
November | 0.208075E+10 | 0.00 | 0.00 | 159461.97 | 0.00 | 0.116921E+10 | 0.163190E+09 | 0.00 | 0.79 |
December | 0.116427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245854E+10 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.153604E+11 | 0.437151E+10 | 0.00 | 16136314.29 | 0.410139E+09 | 0.105803E+11 | 0.620708E+10 | 0.00 | 0.95 |
Minimum of Months | 14214584.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.237106E+10 | 0.176923E+10 | 0.00 | 3644090.49 | 0.142025E+09 | 0.283535E+10 | 0.172501E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.663490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227214E+10 | 0.00 | 0.00 | 0.27 |
February | 0.658624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214864E+10 | 0.00 | 0.00 | 0.27 |
March | 0.212460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802068E+09 | 0.00 | 0.00 | 0.34 |
April | 0.217669E+10 | 679066.55 | 0.00 | 277737.37 | 388312.95 | 0.132881E+09 | 0.186025E+09 | 0.00 | 0.43 |
May | 0.152086E+10 | 18284053.20 | 0.00 | 1943917.73 | 0.00 | 363175.75 | 0.849084E+09 | 0.00 | 0.65 |
June | 0.179658E+09 | 0.586059E+09 | 0.00 | 1954965.04 | 11466244.50 | 0.00 | 0.452628E+09 | 0.00 | 0.53 |
July | 10681055.62 | 0.166303E+10 | 0.00 | 203663.23 | 21522895.49 | 0.00 | 16815764.17 | 0.00 | 0.28 |
August | 0.105705E+09 | 0.137387E+10 | 0.00 | 1996039.70 | 17891727.74 | 0.00 | 0.219832E+09 | 0.00 | 0.52 |
September | 0.521108E+09 | 0.350774E+09 | 0.00 | 2640152.30 | 3803492.21 | 0.00 | 0.841457E+09 | 0.00 | 0.63 |
October | 0.142305E+10 | 24661673.04 | 0.00 | 2149969.24 | 266310.82 | 0.00 | 0.923788E+09 | 0.00 | 0.60 |
November | 0.214493E+10 | 0.00 | 0.00 | 51260.66 | 0.00 | 0.397035E+09 | 0.114415E+09 | 0.00 | 0.36 |
December | 0.136020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134101E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.128896E+11 | 0.401735E+10 | 0.00 | 11217705.28 | 55338983.72 | 0.709414E+10 | 0.360405E+10 | 0.00 | 0.43 |
Minimum of Months | 10681055.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.217669E+10 | 0.166303E+10 | 0.00 | 2640152.30 | 21522895.49 | 0.227214E+10 | 0.923788E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194130E+10 | 0.00 | 0.00 | 0.47 |
February | 0.142582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164797E+10 | 0.00 | 0.00 | 0.46 |
March | 0.265819E+10 | 0.00 | 0.00 | 89854.92 | 0.00 | 0.494118E+09 | 0.107131E+09 | 0.00 | 0.60 |
April | 0.206819E+10 | 1593483.66 | 0.00 | 1325249.71 | 0.00 | 0.105958E+09 | 0.725677E+09 | 0.00 | 0.80 |
May | 0.152446E+10 | 20805885.68 | 0.00 | 2988926.27 | 0.00 | 265675.58 | 0.133086E+10 | 0.00 | 1.22 |
June | 0.186230E+09 | 0.491090E+09 | 0.00 | 2238058.29 | 46577508.34 | 0.00 | 0.568242E+09 | 0.00 | 0.87 |
July | 8338269.95 | 0.145125E+10 | 0.00 | 256895.70 | 26137684.41 | 0.00 | 26966797.34 | 0.00 | 0.42 |
August | 0.111772E+09 | 0.128165E+10 | 0.00 | 2267600.20 | 19631487.17 | 0.00 | 0.284166E+09 | 0.00 | 0.87 |
September | 0.558994E+09 | 0.303858E+09 | 0.00 | 3083051.96 | 19670900.19 | 0.00 | 0.101326E+10 | 0.00 | 1.06 |
October | 0.128315E+10 | 23752639.37 | 0.00 | 3136959.11 | 6847.63 | 0.00 | 0.142801E+10 | 0.00 | 1.09 |
November | 0.228105E+10 | 0.00 | 0.00 | 220875.94 | 0.00 | 0.356671E+09 | 0.323834E+09 | 0.00 | 0.63 |
December | 0.186936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113865E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.152283E+11 | 0.357401E+10 | 0.00 | 15607472.10 | 0.112024E+09 | 0.568493E+10 | 0.580815E+10 | 0.00 | 0.75 |
Minimum of Months | 8338269.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.265819E+10 | 0.145125E+10 | 0.00 | 3136959.11 | 46577508.34 | 0.194130E+10 | 0.142801E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.841294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366696E+10 | 0.00 | 0.00 | 0.42 |
February | 0.916228E+09 | 0.00 | 0.00 | 24006.44 | 0.00 | 0.337283E+10 | 37412923.28 | 0.00 | 0.41 |
March | 0.194679E+10 | 0.00 | 0.00 | 294777.83 | 0.00 | 0.220523E+10 | 0.250452E+09 | 0.00 | 0.51 |
April | 0.215783E+10 | 3113008.04 | 0.00 | 988731.00 | 0.00 | 0.111400E+10 | 0.452024E+09 | 0.00 | 0.66 |
May | 0.229974E+10 | 28293451.91 | 0.00 | 1415107.16 | 139350.18 | 0.371329E+09 | 0.573005E+09 | 0.00 | 0.87 |
June | 0.389215E+09 | 0.716807E+09 | 0.00 | 1468024.09 | 64604038.40 | 29046257.96 | 0.338597E+09 | 0.00 | 0.65 |
July | 18158060.08 | 0.221933E+10 | 0.00 | 218518.19 | 57757701.08 | 0.00 | 13080643.78 | 0.00 | 0.38 |
August | 0.173790E+09 | 0.222347E+10 | 0.00 | 2902227.82 | 31163325.36 | 0.00 | 0.274077E+09 | 0.00 | 0.80 |
September | 0.713007E+09 | 0.567329E+09 | 0.00 | 5481466.92 | 26975931.03 | 64226386.59 | 0.145383E+10 | 0.00 | 1.05 |
October | 0.122772E+10 | 64570000.80 | 0.00 | 6993437.86 | 2350.39 | 0.261997E+09 | 0.284292E+10 | 0.00 | 1.19 |
November | 0.209168E+10 | 0.00 | 0.00 | 1085923.83 | 0.00 | 0.136190E+10 | 0.728696E+09 | 0.00 | 0.58 |
December | 0.139440E+10 | 0.00 | 0.00 | 131776.43 | 0.00 | 0.262703E+10 | 96605647.23 | 0.00 | 0.40 |
Annual Sum or Average | 0.141698E+11 | 0.582291E+10 | 0.00 | 21003997.58 | 0.180643E+09 | 0.150745E+11 | 0.706071E+10 | 0.00 | 0.66 |
Minimum of Months | 18158060.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.229974E+10 | 0.222347E+10 | 0.00 | 6993437.86 | 64604038.40 | 0.366696E+10 | 0.284292E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213317E+10 | 0.00 | 0.00 | 0.49 |
February | 0.122657E+10 | 0.00 | 0.00 | 1795.71 | 0.00 | 0.192843E+10 | 12818949.04 | 0.00 | 0.48 |
March | 0.263352E+10 | 0.00 | 0.00 | 342027.97 | 0.00 | 0.499582E+09 | 0.241523E+09 | 0.00 | 0.62 |
April | 0.222455E+10 | 806930.45 | 0.00 | 1327148.08 | 469883.06 | 0.133143E+09 | 0.653138E+09 | 0.00 | 0.84 |
May | 0.176442E+10 | 19476529.03 | 0.00 | 2286973.41 | 21680.57 | 1853287.18 | 0.108034E+10 | 0.00 | 1.21 |
June | 0.239507E+09 | 0.561817E+09 | 0.00 | 1780622.04 | 22081409.98 | 0.00 | 0.438070E+09 | 0.00 | 0.87 |
July | 12265677.48 | 0.150148E+10 | 0.00 | 155540.54 | 31129903.50 | 0.00 | 11908163.36 | 0.00 | 0.41 |
August | 0.127007E+09 | 0.135922E+10 | 0.00 | 1814921.83 | 19022751.63 | 0.00 | 0.191318E+09 | 0.00 | 0.84 |
September | 0.685801E+09 | 0.336978E+09 | 0.00 | 2556899.90 | 12172454.70 | 0.00 | 0.818894E+09 | 0.00 | 1.05 |
October | 0.153596E+10 | 31482795.65 | 0.00 | 2749346.33 | 3655.62 | 0.00 | 0.126340E+10 | 0.00 | 1.13 |
November | 0.245452E+10 | 0.00 | 0.00 | 204725.04 | 0.00 | 0.432860E+09 | 0.173677E+09 | 0.00 | 0.65 |
December | 0.181772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128043E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.158818E+11 | 0.381126E+10 | 0.00 | 13220000.86 | 84901739.07 | 0.640947E+10 | 0.488508E+10 | 0.00 | 0.76 |
Minimum of Months | 12265677.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.263352E+10 | 0.150148E+10 | 0.00 | 2749346.33 | 31129903.50 | 0.213317E+10 | 0.126340E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.831995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244779E+10 | 0.00 | 0.00 | 0.31 |
February | 0.992385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217972E+10 | 0.00 | 0.00 | 0.31 |
March | 0.263349E+10 | 0.00 | 0.00 | 26121.39 | 0.00 | 0.606160E+09 | 33186560.54 | 0.00 | 0.39 |
April | 0.214897E+10 | 1381846.56 | 0.00 | 1187402.98 | 0.00 | 69457170.94 | 0.600569E+09 | 0.00 | 0.52 |
May | 0.113868E+10 | 29780742.19 | 0.00 | 4278687.83 | 0.00 | 0.00 | 0.178131E+10 | 0.00 | 0.83 |
June | 0.130210E+09 | 0.841637E+09 | 0.00 | 2782544.02 | 9559177.14 | 0.00 | 0.606196E+09 | 0.00 | 0.68 |
July | 7764197.42 | 0.225007E+10 | 0.00 | 248901.53 | 24512391.05 | 0.00 | 22608312.11 | 0.00 | 0.38 |
August | 92931101.72 | 0.178472E+10 | 0.00 | 2172695.41 | 20646610.09 | 0.00 | 0.237699E+09 | 0.00 | 0.61 |
September | 0.585881E+09 | 0.446179E+09 | 0.00 | 2579723.70 | 7589275.81 | 0.00 | 0.769823E+09 | 0.00 | 0.67 |
October | 0.149552E+10 | 37517537.84 | 0.00 | 1873415.99 | 2038909.40 | 2344676.90 | 0.802633E+09 | 0.00 | 0.61 |
November | 0.214689E+10 | 0.00 | 0.00 | 42610.11 | 0.00 | 0.622086E+09 | 70573527.72 | 0.00 | 0.39 |
December | 0.140743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164576E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.136122E+11 | 0.539128E+10 | 0.00 | 15192102.96 | 64346363.48 | 0.757331E+10 | 0.492460E+10 | 0.00 | 0.50 |
Minimum of Months | 7764197.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.263349E+10 | 0.225007E+10 | 0.00 | 4278687.83 | 24512391.05 | 0.244779E+10 | 0.178131E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229309E+10 | 0.00 | 0.00 | 0.58 |
February | 0.183678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189262E+10 | 0.00 | 0.00 | 0.58 |
March | 0.307349E+10 | 0.00 | 0.00 | 386457.32 | 0.00 | 0.500176E+09 | 0.349720E+09 | 0.00 | 0.73 |
April | 0.231436E+10 | 1789805.29 | 0.00 | 2120077.27 | 0.00 | 78434761.26 | 0.110843E+10 | 0.00 | 1.01 |
May | 0.162491E+10 | 27657700.25 | 0.00 | 4423166.97 | 0.00 | 299447.05 | 0.192498E+10 | 0.00 | 1.51 |
June | 0.193043E+09 | 0.660919E+09 | 0.00 | 2733243.97 | 62108890.95 | 0.00 | 0.669015E+09 | 0.00 | 1.05 |
July | 10421335.42 | 0.186334E+10 | 0.00 | 286555.06 | 59179354.74 | 0.00 | 30497049.51 | 0.00 | 0.53 |
August | 0.110600E+09 | 0.157486E+10 | 0.00 | 2288649.67 | 32890533.32 | 0.00 | 0.302475E+09 | 0.00 | 0.98 |
September | 0.718262E+09 | 0.341067E+09 | 0.00 | 2964788.29 | 71625261.06 | 0.00 | 0.911952E+09 | 0.00 | 1.15 |
October | 0.164228E+10 | 29878356.29 | 0.00 | 2352874.94 | 5751709.27 | 4995638.94 | 0.113948E+10 | 0.00 | 1.15 |
November | 0.262122E+10 | 0.00 | 0.00 | 133121.67 | 0.00 | 0.583253E+09 | 0.169469E+09 | 0.00 | 0.74 |
December | 0.199850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162820E+10 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.177094E+11 | 0.449951E+10 | 0.00 | 17688935.16 | 0.231556E+09 | 0.698107E+10 | 0.660601E+10 | 0.00 | 0.88 |
Minimum of Months | 10421335.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.307349E+10 | 0.186334E+10 | 0.00 | 4423166.97 | 71625261.06 | 0.229309E+10 | 0.192498E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202593E+10 | 0.00 | 0.00 | 1510248.64 | 0.00 | 0.181614E+10 | 0.888032E+09 | 0.00 | 0.45 |
February | 0.215752E+10 | 0.00 | 0.00 | 2136109.19 | 0.00 | 0.144641E+10 | 0.115982E+10 | 0.00 | 0.47 |
March | 0.282055E+10 | 0.00 | 0.00 | 4728246.43 | 0.00 | 0.427532E+09 | 0.232596E+10 | 0.00 | 0.69 |
April | 0.246045E+10 | 3467781.77 | 0.00 | 4408017.48 | 0.00 | 89786652.21 | 0.206786E+10 | 0.00 | 0.89 |
May | 0.184883E+10 | 38559732.07 | 0.00 | 5626132.68 | 0.00 | 507266.21 | 0.231736E+10 | 0.00 | 1.17 |
June | 0.301538E+09 | 0.965133E+09 | 0.00 | 2826824.74 | 28263717.53 | 0.00 | 0.622615E+09 | 0.00 | 0.82 |
July | 15364012.68 | 0.261086E+10 | 0.00 | 257873.47 | 38876270.88 | 0.00 | 19082911.64 | 0.00 | 0.44 |
August | 0.148765E+09 | 0.238315E+10 | 0.00 | 3169268.89 | 29358750.91 | 0.00 | 0.312947E+09 | 0.00 | 0.86 |
September | 0.708459E+09 | 0.663260E+09 | 0.00 | 6921968.31 | 29660637.55 | 0.00 | 0.174368E+10 | 0.00 | 1.20 |
October | 0.130136E+10 | 0.102501E+09 | 0.00 | 9654285.90 | 169736.05 | 1370661.65 | 0.371127E+10 | 0.00 | 1.37 |
November | 0.229122E+10 | 0.00 | 0.00 | 3930681.70 | 0.00 | 0.450942E+09 | 0.205280E+10 | 0.00 | 0.70 |
December | 0.224017E+10 | 0.00 | 0.00 | 2006415.29 | 0.00 | 0.128279E+10 | 0.105313E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.183202E+11 | 0.676693E+10 | 0.00 | 47176072.73 | 0.126329E+09 | 0.551548E+10 | 0.182746E+11 | 0.00 | 0.80 |
Minimum of Months | 15364012.68 | 0.00 | 0.00 | 257873.47 | 0.00 | 0.00 | 19082911.64 | 0.00 | 0.44 |
Maximum of Months | 0.282055E+10 | 0.261086E+10 | 0.00 | 9654285.90 | 38876270.88 | 0.181614E+10 | 0.371127E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143635E+10 | 0.00 | 0.00 | 1396.82 | 0.00 | 0.253540E+10 | 7786294.38 | 0.00 | 0.60 |
February | 0.156880E+10 | 0.00 | 0.00 | 74320.19 | 0.00 | 0.216650E+10 | 0.111267E+09 | 0.00 | 0.60 |
March | 0.294680E+10 | 0.00 | 0.00 | 1036331.06 | 0.00 | 0.535940E+09 | 0.641400E+09 | 0.00 | 0.78 |
April | 0.249335E+10 | 808128.97 | 0.00 | 2315604.02 | 580184.50 | 0.110879E+09 | 0.107855E+10 | 0.00 | 1.08 |
May | 0.187577E+10 | 29839897.46 | 0.00 | 3678837.43 | 95218.54 | 1077244.82 | 0.162439E+10 | 0.00 | 1.52 |
June | 0.265738E+09 | 0.734559E+09 | 0.00 | 2135186.85 | 40734453.39 | 0.00 | 0.496473E+09 | 0.00 | 1.07 |
July | 14488481.45 | 0.193278E+10 | 0.00 | 171132.53 | 71472789.84 | 0.00 | 12039850.79 | 0.00 | 0.53 |
August | 0.151330E+09 | 0.168534E+10 | 0.00 | 1754491.05 | 33953962.63 | 0.00 | 0.171669E+09 | 0.00 | 0.96 |
September | 0.847587E+09 | 0.394394E+09 | 0.00 | 2472579.30 | 58821273.40 | 0.00 | 0.747573E+09 | 0.00 | 1.18 |
October | 0.196596E+10 | 47308538.19 | 0.00 | 2207118.77 | 2330937.60 | 5151815.05 | 0.967443E+09 | 0.00 | 1.23 |
November | 0.257208E+10 | 0.00 | 0.00 | 240326.66 | 0.00 | 0.733180E+09 | 0.188468E+09 | 0.00 | 0.76 |
December | 0.196496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177496E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.181032E+11 | 0.482502E+10 | 0.00 | 16087324.69 | 0.207989E+09 | 0.786308E+10 | 0.604706E+10 | 0.00 | 0.91 |
Minimum of Months | 14488481.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.294680E+10 | 0.193278E+10 | 0.00 | 3678837.43 | 71472789.84 | 0.253540E+10 | 0.162439E+10 | 0.00 | 1.52 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:08
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.138543E+12 | 0.283773E+11 | 0.00 | 0.147603E+12 | 0.672012E+10 |
February | 0.212488E+12 | 0.264700E+11 | 0.00 | 0.152176E+12 | 0.659869E+10 |
March | 0.341220E+12 | 0.224786E+11 | 0.00 | 0.198754E+12 | 0.454392E+10 |
April | 0.358634E+12 | 0.143041E+11 | 0.00 | 0.212954E+12 | 0.181393E+11 |
May | 0.453337E+12 | 0.798791E+10 | 0.00 | 0.219611E+12 | 0.676118E+11 |
June | 0.435890E+12 | -0.129930E+10 | 0.00 | 0.480904E+11 | 0.226374E+12 |
July | 0.427335E+12 | -0.927304E+10 | 0.00 | -0.422059E+11 | 0.319629E+12 |
August | 0.414971E+12 | -0.590274E+10 | 0.00 | 0.724334E+09 | 0.321182E+12 |
September | 0.296594E+12 | 0.186217E+10 | 0.00 | 0.114155E+12 | 0.162850E+12 |
October | 0.292319E+12 | 0.107887E+11 | 0.00 | 0.223794E+12 | 0.695567E+11 |
November | 0.148477E+12 | 0.208946E+11 | 0.00 | 0.199021E+12 | 0.334643E+10 |
December | 0.112693E+12 | 0.248262E+11 | 0.00 | 0.165616E+12 | 0.415856E+10 |
Annual Sum or Average | 0.363250E+13 | 0.141514E+12 | 0.00 | 0.164029E+13 | 0.121071E+13 |
Minimum of Months | 0.112693E+12 | -0.927304E+10 | 0.00 | -0.422059E+11 | 0.334643E+10 |
Maximum of Months | 0.453337E+12 | 0.283773E+11 | 0.00 | 0.223794E+12 | 0.321182E+12 |