Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:35:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2143.77 | 430.29 | 430.29 |
Net Site Energy | 2143.77 | 430.29 | 430.29 |
Total Source Energy | 6090.07 | 1222.37 | 1222.37 |
Net Source Energy | 6090.07 | 1222.37 | 1222.37 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 303.70 | 223.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 145.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 361.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 105.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1808.08 | 335.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 303.70 | 223.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 145.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 361.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 105.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 303.70 | 223.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 145.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 361.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 110.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 105.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.40 | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 362.91 | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 111.40 | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 362.91 | 67.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1808.076 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1808.076 | 100.00 |
Total On-Site and Utility Electric Sources | 1808.076 | 100.00 |
Total Electricity End Uses | 1808.076 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 518.83 |
Time Setpoint Not Met During Occupied Cooling | 43.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2785.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.0546 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 9.0546 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 9.0546 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 208123.63 | 104587.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7013.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8189.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 257875.60 | 112777.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 208123.63 | 104587.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7013.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8189.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 961.81 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 462.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1144.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 333.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 121.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5726.18 | 363.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 193.05 | 48.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 92.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1149.33 | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 193.05 | 48.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 92.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 66.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1149.33 | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.99 | 0.250375 | 0.300000 | 0.898000 | 0.667666 | 0.500000 | 0.001522 |
CORE_MID VAV BOX COMPONENT | 2.22 | 0.337766 | 0.344000 | 0.763288 | 0.900709 | 0.500000 | 0.001128 |
CORE_TOP VAV BOX COMPONENT | 2.34 | 0.320629 | 0.339000 | 0.792397 | 0.855010 | 0.500000 | 0.001188 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.719999 | 0.219433 | 0.300000 | 0.216000 | 0.585155 | 0.500000 | 0.001736 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.818642 | 0.122180 | 0.300000 | 0.245593 | 0.325814 | 0.500000 | 0.003118 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.153299 | 0.300000 | 0.309183 | 0.408798 | 0.500000 | 0.002485 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.901699 | 0.110919 | 0.300000 | 0.270510 | 0.300000 | 0.500000 | 0.003435 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.563983 | 0.280135 | 0.300000 | 0.169195 | 0.747027 | 0.500000 | 0.001360 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.668323 | 0.149661 | 0.300000 | 0.200497 | 0.399096 | 0.500000 | 0.002546 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.820173 | 0.192632 | 0.300000 | 0.246052 | 0.513685 | 0.500000 | 0.001978 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.703416 | 0.142185 | 0.300000 | 0.211025 | 0.379160 | 0.500000 | 0.002680 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.629888 | 0.250825 | 0.300000 | 0.188966 | 0.668866 | 0.500000 | 0.001519 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.797542 | 0.125413 | 0.300000 | 0.239262 | 0.334434 | 0.500000 | 0.003038 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.934343 | 0.169094 | 0.300000 | 0.280303 | 0.450917 | 0.500000 | 0.002253 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.829844 | 0.120523 | 0.300000 | 0.248953 | 0.321395 | 0.500000 | 0.003161 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29239.04 |
CORE_MID VAV BOX REHEAT COIL | 25542.31 |
CORE_TOP VAV BOX REHEAT COIL | 43541.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21393.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13888.84 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21377.93 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14006.01 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15878.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10386.26 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15878.05 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10484.64 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16709.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10898.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16691.93 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10999.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.87 | 1.72 | 5.75 | 2.04 | 5.13 | 5.13 | 0.300000 | 0.397602 | 5.13 |
PACU_VAV_MID | 2.71 | 1.72 | 5.41 | 2.48 | 4.61 | 4.61 | 0.300000 | 0.539107 | 4.61 |
PACU_VAV_TOP | 2.90 | 1.83 | 5.81 | 3.51 | 5.29 | 5.29 | 0.300000 | 0.663440 | 5.29 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.13 |
PACU_VAV_MID_OA_CONTROLLER | 4.61 |
PACU_VAV_TOP_OA_CONTROLLER | 5.29 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.13 | 105312.41 | 0.766650 | 1.71 | 35100.63 | 0.766650 |
PACU_VAV_MID COOLING COIL | 4.61 | 97642.42 | 0.754057 | 1.54 | 32544.22 | 0.754057 |
PACU_VAV_TOP COOLING COIL | 5.29 | 108719.27 | 0.764959 | 1.76 | 36236.13 | 0.764959 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 37701.23 |
PACU_VAV_MID HEATING COIL | 39991.79 |
PACU_VAV_TOP HEATING COIL | 39646.82 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.13 |
PACU_VAV_MID FAN | 4.61 |
PACU_VAV_TOP FAN | 5.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.889 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.31435 | 0.47915 | 0.47915 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0752E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0813E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1912E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1964E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2327E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2747E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1524 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2318E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1741 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.3601E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1073 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6039E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0754E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0826E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1914E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1978E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2345E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2838E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9874E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0866E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7110E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8398E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8178E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4306E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1477E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1722E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8959E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9137E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5009E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5072E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0929E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1469E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4219E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4655E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9731E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0058E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9024E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2978E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0193E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7544E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8939E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2253E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0926E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1473E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4211E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4640E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9714E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9994E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8180E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5156E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2447E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1209E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8736E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9847E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4269E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4951E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9869E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0617E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9465E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9746E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1505 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.8367E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1690 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1113 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1135 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7423E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7164E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9348E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4617E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7007E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6153E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3209E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4131E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9573E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4768E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3234E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3497E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7498E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5916E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3918E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0517E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0173E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7050E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8955E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1505 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.8358E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1690 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1113 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1135 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7417E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7165E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9346E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4617E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7004E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6151E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3205E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4134E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9572E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4770E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3233E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3495E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7496E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5917E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3916E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0518E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0171E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7048E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8952E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40495.49077 | 40495.49077 | 2.99333 | 2.99333 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9438.45410 | 9438.45410 | 0.41549 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30051.21126 | 30051.21126 | 2.21886 | 2.21886 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18038.70739 | 18038.70739 | 0.78446 | 0.78446 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31363.57470 | 31363.57470 | 2.33745 | 2.33745 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.11400 | 1.33666E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 30641.43463 | 30641.43463 | 1.33725 | 1.33725 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9660.06290 | 9660.06290 | 0.72000 | 0.72000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15016.75117 | 15016.75117 | 0.65704 | 0.65704 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10983.59451 | 10983.59451 | 0.81864 | 0.81864 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9748.65673 | 9748.65673 | 0.42656 | 0.42656 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13827.53004 | 13827.53004 | 1.03061 | 1.03061 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15005.97362 | 15005.97362 | 0.65657 | 0.65657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12097.99487 | 12097.99487 | 0.90170 | 0.90170 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9830.72860 | 9830.72860 | 0.43016 | 0.43016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7567.12309 | 7567.12309 | 0.56398 | 0.56398 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11151.91144 | 11151.91144 | 0.48765 | 0.48765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8967.15048 | 8967.15048 | 0.66832 | 0.66832 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50250 | 1.33602E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7294.14479 | 7294.14479 | 0.31899 | 0.31899 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11004.55273 | 11004.55273 | 0.82017 | 0.82017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11151.90000 | 11151.90000 | 0.48765 | 0.48765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9438.01200 | 9438.01200 | 0.70342 | 0.70342 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7363.05031 | 7363.05031 | 0.32201 | 0.32201 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8451.17439 | 8451.17439 | 0.62989 | 0.62989 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11735.42824 | 11735.42824 | 0.51320 | 0.51320 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10700.65685 | 10700.65685 | 0.79754 | 0.79754 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7653.54599 | 7653.54599 | 0.33472 | 0.33472 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12536.09843 | 12536.09843 | 0.93434 | 0.93434 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11722.94897 | 11722.94897 | 0.51265 | 0.51265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11134.06600 | 11134.06600 | 0.82984 | 0.82984 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7724.18840 | 7724.18840 | 0.33781 | 0.33781 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76526.88 | 5.13325 | 5.13325 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40227.20 | 2.04099 | 2.04099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 69628.30 | 4.60547 | 4.60547 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40793.16 | 2.48284 | 2.48284 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 78517.37 | 5.28696 | 5.28696 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40745.78 | 3.50758 | 3.50758 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.99333 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25037 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.89800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66767 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52172E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29239.03916 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21886 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33777 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76329 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90071 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12800E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25542.31177 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33745 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32063 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79240 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85501 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18829E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 43541.19130 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21943 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21600 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58516 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.73629E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21393.31598 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81864 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12218 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24559 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32581 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11835E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13888.84478 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03061 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15330 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30918 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40880 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48534E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21377.93150 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90170 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11092 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27051 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43495E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14006.01067 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56398 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28014 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16920 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74703 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36006E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15878.06955 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66832 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14966 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20050 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39910 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54576E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10386.25784 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82017 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19263 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24605 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51369 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97786E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15878.05321 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70342 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14219 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21102 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37916 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67961E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10484.64209 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62989 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25082 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18897 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66887 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51899E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16709.74473 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79754 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12541 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23926 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33443 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03797E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10898.44431 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93434 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16909 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28030 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45092 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25319E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16691.92946 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82984 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12052 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24895 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32139 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16122E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10999.30158 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87461 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72477 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.74923 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04099 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.13325 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.13325 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.39760 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.70524 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72077 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.41048 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48284 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60547 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60547 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.53911 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.90420 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.83368 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.80840 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.50758 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28696 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.28696 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.66344 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.13325 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.60547 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.28696 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.13325 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.13325 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 105312.41134 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76665 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.71091 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35100.62670 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76665 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 37701.22613 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.13325 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60547 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.60547 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97642.41742 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75406 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53500 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32544.21772 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75406 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 39991.79163 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.60547 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28696 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.28696 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108719.26720 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76496 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76214 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36236.13176 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76496 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39646.81651 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.28696 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 104450.38 | 356399.49 | 11.31 | 2.90 | 3.24 | 3.41 | 3.58 | 9.88 | 11.05 | 11.63 | 12.21 | 5.7881 | 4.6239 | 3.1146 | 1.2584 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 96962.20 | 330848.74 | 11.38 | 2.91 | 3.26 | 3.43 | 3.59 | 9.93 | 11.12 | 11.72 | 12.26 | 5.1930 | 4.1430 | 2.7894 | 1.1409 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 107838.90 | 367961.61 | 11.32 | 2.90 | 3.24 | 3.41 | 3.58 | 9.89 | 11.06 | 11.64 | 12.21 | 5.9614 | 4.7579 | 3.2031 | 1.2991 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | N/A | 2.171 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.4 | N/A | 2.171 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.3625093094E-002 | 3.6527900970E-002 | Pass | Pass | 0.4948692912 | 0.4891545353 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1635986156 | 0.1087298596 | Pass | Pass | 0.4993058081 | 0.4704058430 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9043297056E-002 | 4.4278660352E-002 | Pass | Pass | 0.5062381273 | 0.4596503612 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1895247899E-002 | 4.6335225481E-002 | Pass | Pass | 0.4971621694 | 0.4576400353 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.3926832790E-002 | 7.5994649595E-003 | Pass | Pass | 0.5677563143 | 0.6050070729 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.8624928587E-002 | 6.3088431631E-002 | Pass | Pass | 22.1413902948 | 47.9762555964 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3881194440 | 0.3847148227 | Pass | Pass | 22.3269921028 | 75.9185578788 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4017646200 | 0.3960694501 | Pass | Pass | 17.0332356151 | 53.8043659864 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3707821261 | 0.3729118979 | Pass | Pass | 20.3565467669 | 59.6987991373 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4029086340 | 0.3998865449 | Pass | Pass | 13.0650705740 | 42.9880945336 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2669023415 | 0.2499456391 | Pass | Pass | 17.6784054479 | 40.5377264842 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2719605746 | 0.2578706595 | Pass | Pass | 12.5284177610 | 28.8291317041 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2347719072 | 0.2306420223 | Pass | Pass | 12.7983964734 | 28.5407345911 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2728301069 | 0.2601098442 | Pass | Pass | 12.6699940734 | 29.1942437401 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2788740396 | 0.2656090728 | Pass | Pass | 31.0007474635 | 113.1305455233 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2810938620 | 0.2722594359 | Pass | Pass | 11.6175734241 | 38.5992402122 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2507842208 | 0.2511734618 | Pass | Pass | 18.8451285691 | 64.5504954524 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2826408484 | 0.2752477991 | Pass | Pass | 11.8104113720 | 42.6380207887 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3586.72 | 201.07 | 0.00 | 1867.56 | 789.35 | 6444.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.171 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.171 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.171 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.171 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.74 | 0.0000 | Y | 11.89 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.67 | 0.0000 | Y | 7.51 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.56 | 0.0000 | Y | 11.83 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.64 | 0.0000 | Y | 7.51 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.70 | 0.0000 | Y | 11.88 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.64 | 0.0000 | Y | 7.51 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.53 | 0.0000 | Y | 11.82 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.61 | 0.0000 | Y | 7.50 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.74 | 0.0000 | Y | 11.89 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.67 | 0.0000 | Y | 7.51 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.56 | 0.0000 | Y | 11.83 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.64 | 0.0000 | Y | 7.51 |
Interior Lighting Total | 9.0546 | 4982.19 | 45111.81 | 361.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.25 | AstronomicalClock | - | 42.04 | 42.04 | 3.35 | |
EXTERIOR_LIGHTS_B | 8043.62 | AstronomicalClock | - | 83.67 | 71.18 | 107.47 | |
Exterior Lighting Total | 8467.87 | 110.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 105312.41 | 80737.79 | 24574.62 | 0.77 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97642.42 | 73627.90 | 24014.52 | 0.75 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108719.27 | 83165.75 | 25553.52 | 0.76 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 104450.4 | 2.90 | 9.88 | N/A | N/A | 11.31 | |
PACU_VAV_MID COOLING COIL | 96962.2 | 2.91 | 9.93 | N/A | N/A | 11.38 | |
PACU_VAV_TOP COOLING COIL | 107838.9 | 2.90 | 9.89 | N/A | N/A | 11.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 29239.04 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 25542.31 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 43541.19 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21393.32 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13888.84 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21377.93 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14006.01 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15878.07 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10386.26 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15878.05 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10484.64 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16709.74 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10898.44 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16691.93 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10999.30 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 37701.23 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 39991.79 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39646.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.13 | 11798.58 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.61 | 10654.23 | 2313.39 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.29 | 12151.86 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104450.38 | 2.90 | 9.88 | 11.31 | 5.7881 | 3.24 | 11.05 | 4.6239 | 3.41 | 11.63 | 3.1146 | 3.58 | 12.21 | 1.2584 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96962.20 | 2.91 | 9.93 | 11.38 | 5.1930 | 3.26 | 11.12 | 4.1430 | 3.43 | 11.72 | 2.7894 | 3.59 | 12.26 | 1.1409 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107838.90 | 2.90 | 9.89 | 11.32 | 5.9614 | 3.24 | 11.06 | 4.7579 | 3.41 | 11.64 | 3.2031 | 3.58 | 12.21 | 1.2991 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40495.49 | 40495.49 | 41.17 | 2.993 | 2.993 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 30051.21 | 30051.21 | 30.55 | 2.219 | 2.219 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 31363.57 | 31363.57 | 31.89 | 2.337 | 2.337 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00888 | 30.11 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9660.06 | 9660.06 | 46.59 | 0.720 | 0.720 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00901 | 30.21 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10983.59 | 10983.59 | 83.68 | 0.819 | 0.819 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00880 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13827.53 | 13827.53 | 66.69 | 1.031 | 1.031 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00886 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12097.99 | 12097.99 | 92.17 | 0.902 | 0.902 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7567.12 | 7567.12 | 36.50 | 0.564 | 0.564 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00900 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8967.15 | 8967.15 | 68.31 | 0.668 | 0.668 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00878 | 26.50 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11004.55 | 11004.55 | 53.08 | 0.820 | 0.820 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00885 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9438.01 | 9438.01 | 71.91 | 0.703 | 0.703 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00876 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8451.17 | 8451.17 | 40.76 | 0.630 | 0.630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00904 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10700.66 | 10700.66 | 81.52 | 0.798 | 0.798 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00878 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12536.10 | 12536.10 | 60.46 | 0.934 | 0.934 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00887 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11134.07 | 11134.07 | 84.83 | 0.830 | 0.830 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00877 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9438.45 | 9438.45 | 9.60 | 0.415 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 18038.71 | 18038.71 | 18.34 | 0.784 | 0.784 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 30641.43 | 30641.43 | 31.15 | 1.337 | 1.337 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15016.75 | 15016.75 | 72.43 | 0.657 | 0.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9748.66 | 9748.66 | 74.27 | 0.427 | 0.427 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15005.97 | 15005.97 | 72.37 | 0.657 | 0.657 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9830.73 | 9830.73 | 74.90 | 0.430 | 0.430 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11151.91 | 11151.91 | 53.79 | 0.488 | 0.488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7294.14 | 7294.14 | 55.57 | 0.319 | 0.319 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11151.90 | 11151.90 | 53.79 | 0.488 | 0.488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7363.05 | 7363.05 | 56.10 | 0.322 | 0.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11735.43 | 11735.43 | 56.60 | 0.513 | 0.513 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7653.55 | 7653.55 | 58.31 | 0.335 | 0.335 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11722.95 | 11722.95 | 56.54 | 0.513 | 0.513 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7724.19 | 7724.19 | 58.85 | 0.338 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.13 | 5.13 | 2.04 | 2.04 | 5.1333 | 2.0410 | 5.1333 | 0.3976 | 0.3000 |
PACU_VAV_MID | 4.61 | 4.61 | 2.48 | 2.48 | 4.6055 | 2.4828 | 4.6055 | 0.5391 | 0.3000 |
PACU_VAV_TOP | 5.29 | 5.29 | 3.51 | 3.51 | 5.2870 | 3.5076 | 5.2870 | 0.6634 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29239.039 | 29239.039 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 29239.04 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 9438.45 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25542.312 | 25542.312 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25542.31 | 25542.31 | 0.784465 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 18038.71 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 43541.191 | 43541.191 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 43541.19 | 43541.19 | 1.337253 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 30641.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21393.316 | 21393.316 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21393.32 | 21393.32 | 0.657039 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00754542 | 47.5957 | 15016.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13888.845 | 13888.845 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13888.84 | 13888.84 | 0.426559 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753414 | 47.5257 | 9748.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21377.932 | 21377.932 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21377.93 | 21377.93 | 0.656567 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00754511 | 47.5938 | 15005.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14006.011 | 14006.011 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14006.01 | 14006.01 | 0.430158 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00753784 | 47.5488 | 9830.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15878.070 | 15878.070 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15878.07 | 15878.07 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765608 | 48.2823 | 11151.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10386.258 | 10386.258 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10386.26 | 10386.26 | 0.318987 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765246 | 48.2598 | 7294.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15878.053 | 15878.053 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15878.05 | 15878.05 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765608 | 48.2823 | 11151.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10484.642 | 10484.642 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10484.64 | 10484.64 | 0.322008 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765626 | 48.2835 | 7363.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16709.745 | 16709.745 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16709.74 | 16709.74 | 0.513196 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751088 | 47.3796 | 11735.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10898.444 | 10898.444 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10898.44 | 10898.44 | 0.334717 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750231 | 47.3264 | 7653.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16691.929 | 16691.929 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16691.93 | 16691.93 | 0.512649 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751034 | 47.3763 | 11722.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10999.302 | 10999.302 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10999.30 | 10999.30 | 0.337815 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00750695 | 47.3553 | 7724.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 105312.411 | 80737.795 | 5.133250 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 107553.07 | 86468.52 | 5.133250 | 25.44 | 17.77 | 0.00988940 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.8804 | 24.00 | 0.00885736 | 46.4602 | 68861.11 | 0.00 | 108591.23 | 80951.37 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 37701.226 | 37701.226 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37701.23 | 37701.23 | 1.539975 | -7.95 | -7.95 | 0.00247737 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 76.2681 | 19.34 | 0.00720314 | 50.3595 | 20822.19 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97642.417 | 73627.900 | 4.605470 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 100179.16 | 78564.70 | 4.605470 | 25.64 | 18.00 | 0.01008893 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.9511 | 24.00 | 0.00893771 | 46.8764 | 61697.88 | 0.00 | 100682.44 | 73887.34 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 39991.792 | 39991.792 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39991.79 | 39991.79 | 1.381641 | -11.74 | -11.74 | 0.00178217 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 86.5037 | 17.60 | 0.00693411 | 54.1113 | 22573.72 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108719.267 | 83165.746 | 5.286955 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 111066.47 | 88967.77 | 5.286955 | 25.43 | 17.79 | 0.00991398 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 22.6060 | 24.00 | 0.00890152 | 46.6894 | 70726.47 | 0.00 | 112104.16 | 83397.07 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39646.817 | 39646.817 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39646.82 | 39646.82 | 1.586087 | -8.39 | -8.39 | 0.00248992 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 75.3534 | 17.38 | 0.00712107 | 56.3365 | 30198.63 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 29239.039 | 29239.039 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 29239.04 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29239.04 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.02 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 9438.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 25542.312 | 25542.312 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25542.31 | 25542.31 | 1.0000 | 0.92090311 | 0.784465 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25542.31 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 18038.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 43541.191 | 43541.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 43541.19 | 43541.19 | 1.0000 | 1.56983513 | 1.337253 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43541.19 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 30641.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21393.316 | 21393.316 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21393.32 | 21393.32 | 1.0000 | 0.77131511 | 0.657039 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21393.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754542 | 21.00 | 0.00754542 | 47.5957 | 15016.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13888.845 | 13888.845 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13888.84 | 13888.84 | 1.0000 | 0.50074873 | 0.426559 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13888.84 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753414 | 21.00 | 0.00753414 | 47.5257 | 9748.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 21377.932 | 21377.932 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21377.93 | 21377.93 | 1.0000 | 0.77076044 | 0.656567 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21377.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00754511 | 21.00 | 0.00754511 | 47.5938 | 15005.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14006.011 | 14006.011 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14006.01 | 14006.01 | 1.0000 | 0.50497304 | 0.430158 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14006.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00753784 | 21.00 | 0.00753784 | 47.5488 | 9830.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 15878.070 | 15878.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15878.07 | 15878.07 | 1.0000 | 0.57246829 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15878.07 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765608 | 21.00 | 0.00765608 | 48.2823 | 11151.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10386.258 | 10386.258 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10386.26 | 10386.26 | 1.0000 | 0.37446638 | 0.318987 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10386.26 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765246 | 21.00 | 0.00765246 | 48.2598 | 7294.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15878.053 | 15878.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15878.05 | 15878.05 | 1.0000 | 0.57246770 | 0.487653 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15878.05 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765608 | 21.00 | 0.00765608 | 48.2823 | 11151.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10484.642 | 10484.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10484.64 | 10484.64 | 1.0000 | 0.37801353 | 0.322008 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10484.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765626 | 21.00 | 0.00765626 | 48.2835 | 7363.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16709.745 | 16709.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16709.74 | 16709.74 | 1.0000 | 0.60245353 | 0.513196 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16709.74 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751088 | 21.00 | 0.00751088 | 47.3796 | 11735.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10898.444 | 10898.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10898.44 | 10898.44 | 1.0000 | 0.39293277 | 0.334717 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10898.44 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750231 | 21.00 | 0.00750231 | 47.3264 | 7653.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16691.929 | 16691.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16691.93 | 16691.93 | 1.0000 | 0.60181122 | 0.512649 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16691.93 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751034 | 21.00 | 0.00751034 | 47.3763 | 11722.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10999.302 | 10999.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10999.30 | 10999.30 | 1.0000 | 0.39656908 | 0.337815 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10999.30 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00750695 | 21.00 | 0.00750695 | 47.3553 | 7724.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 105312.411 | 80737.795 | 5.133250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2239 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.133250 | 6.02605249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 107553.07 | 86468.52 | 1.0213 | 6.02605249 | 5.133250 | 25.44 | 17.77 | 0.00988940 | 50764.3 | 10.89 | 10.89 | 0.00850000 | 32369.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11798.578 | 95754.49 | 30.30 | 0.01336696 | 21.83 | 1.17451000 | 22.8804 | 24.00 | 0.00885736 | 24.00 | 0.00885736 | 46.4602 | 68861.11 | 0.00 | 108591.23 | 80951.37 | 5.78806897 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.97 | 0.00931237 | 36561.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37701.226 | 37701.226 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.133250 | 6.02605249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37701.23 | 37701.23 | 1.0000 | 1.80781575 | 1.539975 | -7.95 | -7.95 | 0.00247737 | -1833.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37701.23 | -16.30 | 0.00092409 | -16.30 | 1.17451000 | 76.2681 | 18.87 | 0.00746919 | 19.34 | 0.00720314 | 50.3595 | 20822.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97642.417 | 73627.900 | 4.605470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5948 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.605470 | 5.40647793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 100179.16 | 78564.70 | 1.0260 | 5.40647793 | 4.605470 | 25.64 | 18.00 | 0.01008893 | 51472.9 | 10.87 | 10.87 | 0.00850000 | 32357.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10654.233 | 89524.93 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 25.9511 | 24.00 | 0.00893771 | 24.00 | 0.00893771 | 46.8764 | 61697.88 | 0.00 | 100682.44 | 73887.34 | 5.19296292 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.74 | 12.73 | 0.00916158 | 35934.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39991.792 | 39991.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.605470 | 5.40647793 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39991.79 | 39991.79 | 1.0000 | 1.62194338 | 1.381641 | -11.74 | -11.74 | 0.00178217 | -7376.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39991.79 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 86.5037 | 17.51 | 0.00728193 | 17.60 | 0.00693411 | 54.1113 | 22573.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108719.267 | 83165.746 | 5.286955 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2696 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.286955 | 6.20649061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 111066.47 | 88967.77 | 1.0216 | 6.20649061 | 5.286955 | 25.43 | 17.79 | 0.00991398 | 50813.0 | 10.89 | 10.89 | 0.00850000 | 32369.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12151.863 | 98914.60 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 22.6060 | 24.00 | 0.00890152 | 24.00 | 0.00890152 | 46.6894 | 70726.47 | 0.00 | 112104.16 | 83397.07 | 5.96138115 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.98 | 12.96 | 0.00929661 | 36517.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39646.817 | 39646.817 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.286955 | 6.20649061 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39646.82 | 39646.82 | 1.0000 | 1.86194718 | 1.586087 | -8.39 | -8.39 | 0.00248992 | -2242.5 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39646.82 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 75.3534 | 15.79 | 0.00727721 | 17.38 | 0.00712107 | 56.3365 | 30198.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.13 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.61 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.29 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2065.67 | 2925.50 | 122.83 |
CORE_MID | 2414.50 | 3611.50 | 915.00 |
CORE_TOP | 2913.00 | 3915.83 | 1569.50 |
PERIMETER_TOP_ZN_3 | 3619.33 | 4309.33 | 2435.00 |
PERIMETER_TOP_ZN_2 | 3666.17 | 4189.00 | 2299.17 |
PERIMETER_TOP_ZN_1 | 3418.83 | 4103.83 | 2047.83 |
PERIMETER_TOP_ZN_4 | 3538.83 | 4463.50 | 2355.50 |
PERIMETER_BOT_ZN_3 | 3295.00 | 4248.33 | 2124.00 |
PERIMETER_BOT_ZN_2 | 3435.00 | 4043.67 | 1983.67 |
PERIMETER_BOT_ZN_1 | 3311.33 | 4355.00 | 2094.00 |
PERIMETER_BOT_ZN_4 | 3347.83 | 4208.67 | 2020.00 |
PERIMETER_MID_ZN_3 | 3378.67 | 4058.17 | 2047.83 |
PERIMETER_MID_ZN_2 | 2885.00 | 3534.00 | 1756.83 |
PERIMETER_MID_ZN_1 | 3165.00 | 3805.83 | 1634.17 |
PERIMETER_MID_ZN_4 | 3308.33 | 4248.00 | 2001.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4874.17 | 4968.83 | 2785.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_MID | 2.33 | 0.00 | 2.17 | 0.00 |
CORE_TOP | 4.83 | 0.67 | 2.83 | 0.67 |
PERIMETER_TOP_ZN_3 | 141.50 | 1.67 | 58.17 | 1.67 |
PERIMETER_TOP_ZN_2 | 100.33 | 6.67 | 18.17 | 6.67 |
PERIMETER_TOP_ZN_1 | 81.50 | 11.17 | 14.00 | 11.17 |
PERIMETER_TOP_ZN_4 | 101.00 | 17.00 | 21.17 | 10.00 |
PERIMETER_BOT_ZN_3 | 34.17 | 0.00 | 23.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 12.33 | 2.17 | 0.50 | 2.17 |
PERIMETER_BOT_ZN_1 | 498.83 | 5.00 | 491.33 | 5.00 |
PERIMETER_BOT_ZN_4 | 12.50 | 8.00 | 0.50 | 3.17 |
PERIMETER_MID_ZN_3 | 47.50 | 0.00 | 16.83 | 0.00 |
PERIMETER_MID_ZN_2 | 30.50 | 6.67 | 0.83 | 6.67 |
PERIMETER_MID_ZN_1 | 23.33 | 8.00 | 1.17 | 8.00 |
PERIMETER_MID_ZN_4 | 31.17 | 14.00 | 1.67 | 7.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 625.83 | 55.83 | 518.83 | 43.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.983 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.696 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.696 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.887 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.556 | 0.120 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.327 | 0.114 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.639 | 0.120 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.685 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.256 | 0.064 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 1.021 | 1.350 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.258 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.821 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.425 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.250 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.531 | 0.100 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15765093.09 | 0.00 | 15765093.09 | 0.00 | 15765093.09 | 13393058.27 | 5645.15 | 164.03 | 2950.82 | 183.20 |
CORE_MID | 11131109.54 | 0.00 | 11131109.54 | 0.00 | 11131109.54 | 13393058.27 | 6402.79 | 23.96 | 2333.25 | 188.78 |
CORE_TOP | 11099225.76 | 0.00 | 11099225.76 | 0.00 | 11099225.76 | 13393058.27 | 6365.84 | 22.39 | 2371.77 | 109.01 |
PERIMETER_TOP_ZN_3 | 2985206.98 | 0.00 | 2985206.98 | 750436.27 | 3735643.26 | 2823374.22 | 4117.12 | 2.89 | 4639.99 | 108.99 |
PERIMETER_TOP_ZN_2 | 3317871.68 | 0.00 | 3317871.68 | 500287.84 | 3818159.52 | 1787429.43 | 4062.01 | 1.89 | 4696.11 | 108.95 |
PERIMETER_TOP_ZN_1 | 4465399.29 | 0.00 | 4465399.29 | 750436.27 | 5215835.56 | 2823374.22 | 4080.73 | 2.10 | 4677.18 | 109.01 |
PERIMETER_TOP_ZN_4 | 3505353.41 | 0.00 | 3505353.41 | 500287.84 | 4005641.25 | 1787312.18 | 4056.50 | 2.78 | 4700.73 | 108.95 |
PERIMETER_BOT_ZN_3 | 2330221.82 | 0.00 | 2330221.82 | 399002.08 | 2729223.90 | 2823374.22 | 6141.90 | 51.31 | 2566.79 | 183.20 |
PERIMETER_BOT_ZN_2 | 2709130.11 | 0.00 | 2709130.11 | 265999.79 | 2975129.90 | 1787429.43 | 4045.29 | 10.78 | 4703.93 | 183.20 |
PERIMETER_BOT_ZN_1 | 3482071.76 | 0.00 | 3482071.76 | 4729192.30 | 8211264.06 | 2823374.22 | 4068.88 | 7.03 | 4684.10 | 183.20 |
PERIMETER_BOT_ZN_4 | 2719766.68 | 0.00 | 2719766.68 | 265999.79 | 2985766.47 | 1787312.18 | 4076.00 | 8.38 | 4675.62 | 183.20 |
PERIMETER_MID_ZN_3 | 2767754.65 | 0.00 | 2767754.65 | 624679.86 | 3392434.50 | 2823374.22 | 4145.94 | 43.35 | 4570.71 | 188.78 |
PERIMETER_MID_ZN_2 | 3261544.24 | 0.00 | 3261544.24 | 416450.74 | 3677994.97 | 1787429.43 | 4027.49 | 1.62 | 4730.89 | 1097.78 |
PERIMETER_MID_ZN_1 | 4213902.52 | 0.00 | 4213902.52 | 624679.86 | 4838582.38 | 2823374.22 | 4058.02 | 1.46 | 4700.52 | 188.78 |
PERIMETER_MID_ZN_4 | 3281938.57 | 0.00 | 3281938.57 | 416450.74 | 3698389.31 | 1787312.18 | 4028.71 | 3.20 | 4728.09 | 188.78 |
Total Facility | 77035590.10 | 0.00 | 77035590.10 | 10243903.37 | 87279493.47 | 67843644.98 | 6563.93 | 333.31 | 4853.45 | 1235.85 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7210 | 0.0000 | 0.7210 | 0.0000 | 0.7210 | 0.4247 | 2919.22 | 164.03 | 2859.75 |
CORE_MID | 0.5116 | 0.0000 | 0.5116 | 0.0000 | 0.5116 | 0.4247 | 3641.13 | 23.96 | 2277.92 |
CORE_TOP | 0.5117 | 0.0000 | 0.5117 | 0.0000 | 0.5117 | 0.4247 | 3598.04 | 22.39 | 2322.57 |
PERIMETER_TOP_ZN_3 | 0.1376 | 0.0000 | 0.1376 | 0.0178 | 0.1554 | 0.0895 | 1349.32 | 2.89 | 4590.78 |
PERIMETER_TOP_ZN_2 | 0.1529 | 0.0000 | 0.1529 | 0.0119 | 0.1648 | 0.0567 | 1294.21 | 1.89 | 4646.90 |
PERIMETER_TOP_ZN_1 | 0.2060 | 0.0000 | 0.2060 | 0.0178 | 0.2238 | 0.0895 | 1312.94 | 2.10 | 4627.97 |
PERIMETER_TOP_ZN_4 | 0.1613 | 0.0000 | 0.1613 | 0.0119 | 0.1731 | 0.0567 | 1288.87 | 2.78 | 4651.35 |
PERIMETER_BOT_ZN_3 | 0.1062 | 0.0000 | 0.1062 | 0.0095 | 0.1157 | 0.0895 | 3415.19 | 50.48 | 2477.33 |
PERIMETER_BOT_ZN_2 | 0.1234 | 0.0000 | 0.1234 | 0.0063 | 0.1297 | 0.0567 | 1319.38 | 10.76 | 4612.86 |
PERIMETER_BOT_ZN_1 | 0.1588 | 0.0000 | 0.1588 | 0.2119 | 0.3707 | 0.0895 | 1342.95 | 7.03 | 4593.03 |
PERIMETER_BOT_ZN_4 | 0.1237 | 0.0000 | 0.1237 | 0.0063 | 0.1300 | 0.0567 | 1350.10 | 8.36 | 4584.54 |
PERIMETER_MID_ZN_3 | 0.1273 | 0.0000 | 0.1273 | 0.0148 | 0.1421 | 0.0895 | 1384.27 | 43.35 | 4515.37 |
PERIMETER_MID_ZN_2 | 0.1402 | 0.0000 | 0.1402 | 0.0105 | 0.1506 | 0.0567 | 1266.90 | 1.44 | 3765.66 |
PERIMETER_MID_ZN_1 | 0.1939 | 0.0000 | 0.1939 | 0.0148 | 0.2087 | 0.0895 | 1296.35 | 1.46 | 4645.18 |
PERIMETER_MID_ZN_4 | 0.1506 | 0.0000 | 0.1506 | 0.0099 | 0.1604 | 0.0567 | 1268.12 | 3.14 | 4671.75 |
Total Facility | 3.5262 | 0.0000 | 3.5262 | 0.3433 | 3.8695 | 2.1513 | 3770.44 | 332.20 | 4734.20 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 37217373.59 | 0.00 | 37217373.59 | 22614548.33 | 4032.83 | 1.58 | 4725.59 | 183.20 |
PACU_VAV_MID | 33978817.29 | 0.00 | 33978817.29 | 22614548.33 | 4052.63 | 2.13 | 4705.24 | 188.78 |
PACU_VAV_TOP | 34966641.70 | 0.00 | 34966641.70 | 22614548.33 | 4079.09 | 1.09 | 4679.82 | 108.19 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.6994 | 0.0000 | 1.6994 | 0.7171 | 1306.90 | 1.58 | 4634.52 |
PACU_VAV_MID | 1.5617 | 0.0000 | 1.5617 | 0.7171 | 1290.96 | 2.13 | 4649.91 |
PACU_VAV_TOP | 1.6117 | 0.0000 | 1.6117 | 0.7171 | 1311.30 | 1.09 | 4630.62 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.56 | 3035.81 | 0.00 | 0.00 | 0.00 | 1874.00 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.17 | 2844.67 | 0.00 | 0.00 | 0.00 | 2117.67 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.08 | 2840.03 | 0.00 | 0.00 | 0.00 | 2054.52 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.8145 | 0.0000 | 0.0000 | 0.0000 | 1.1048 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.5781 | 0.0000 | 0.0000 | 0.0000 | 1.1503 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.6411 | 0.0000 | 0.0000 | 0.0000 | 1.1513 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1808.08 | 16005.15 | 12-MAR-17:10 | 257875.60 | 02-JAN-07:10 |
Electricity:Building | 1123.31 | 15718.93 | 01-JAN-09:00 | 83309.12 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 329.05 | 4741.03 | 01-JAN-00:10 | 25654.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1123.31 | 15718.93 | 01-JAN-09:00 | 83309.12 | 02-NOV-07:10 |
InteriorLights:Electricity | 361.27 | 1693.55 | 01-JAN-09:00 | 36137.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 361.27 | 1693.55 | 01-JAN-09:00 | 36137.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 361.27 | 1693.55 | 01-JAN-09:00 | 36137.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 361.27 | 1693.55 | 01-JAN-09:00 | 36137.71 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 38.58 | 553.47 | 01-JAN-09:00 | 3009.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.89 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.89 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.41 | 350.37 | 01-JAN-08:40 | 1905.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 38.51 | 553.47 | 01-JAN-08:40 | 3009.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.83 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.83 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.40 | 350.37 | 01-JAN-09:00 | 1905.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.51 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.51 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 38.56 | 553.47 | 01-JAN-09:00 | 3009.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.88 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.88 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.40 | 350.37 | 01-JAN-08:40 | 1905.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 38.50 | 553.47 | 01-JAN-08:40 | 3009.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.82 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.82 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.39 | 350.37 | 01-JAN-09:00 | 1905.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.50 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.50 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 38.58 | 553.47 | 01-JAN-09:00 | 3009.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.89 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.89 | 51.50 | 01-JAN-09:00 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 24.41 | 350.37 | 01-JAN-08:40 | 1905.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.51 | 32.61 | 01-JAN-08:40 | 952.10 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 38.51 | 553.47 | 01-JAN-08:40 | 3009.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.83 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.83 | 51.50 | 01-JAN-08:40 | 1503.90 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.40 | 350.37 | 01-JAN-09:00 | 1905.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.51 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.51 | 32.60 | 01-JAN-09:00 | 952.03 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 573.92 | 286.22 | 08-JUL-17:40 | 215507.97 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1359.94 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1359.94 | 02-NOV-07:20 |
ElectricityPurchased:Facility | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
ElectricityNet:Plant | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1808.08 | 16005.15 | 08-JUL-18:20 | 257875.60 | 02-JAN-07:10 |
Heating:Electricity | 303.70 | 0.00 | 01-JAN-00:40 | 208123.63 | 02-JAN-07:10 |
General:Heating:Electricity | 303.70 | 0.00 | 01-JAN-00:40 | 208123.63 | 02-JAN-07:10 |
Fans:Electricity | 105.38 | 0.00 | 01-JAN-00:40 | 34590.83 | 15-AUG-14:30 |
General:Fans:Electricity | 105.38 | 0.00 | 01-JAN-00:40 | 34590.83 | 15-AUG-14:30 |
ExteriorLights:Electricity | 110.82 | 0.00 | 01-JAN-08:00 | 8467.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 110.82 | 0.00 | 01-JAN-08:00 | 8467.87 | 01-JAN-06:10 |
Cooling:Electricity | 145.92 | 0.00 | 01-JAN-00:10 | 81617.07 | 15-AUG-14:30 |
General:Cooling:Electricity | 145.92 | 0.00 | 01-JAN-00:10 | 81617.07 | 15-AUG-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.15 | 0.00 | 01-JAN-00:10 | 1015.47 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 335.69 | 1156.00 | 09-JAN-05:10 | 112777.14 | 07-FEB-07:30 |
NaturalGas:HVAC | 223.40 | 0.00 | 01-JAN-00:40 | 105930.98 | 07-FEB-07:20 |
Heating:NaturalGas | 223.40 | 0.00 | 01-JAN-00:40 | 105930.98 | 07-FEB-07:20 |
General:Heating:NaturalGas | 223.40 | 0.00 | 01-JAN-00:40 | 105930.98 | 07-FEB-07:20 |
NaturalGas:Plant | 112.30 | 1156.00 | 02-JAN-17:20 | 10482.27 | 06-FEB-12:30 |
WaterSystems:NaturalGas | 112.30 | 1156.00 | 02-JAN-17:20 | 10482.27 | 06-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 112.30 | 1156.00 | 02-JAN-17:20 | 10482.27 | 06-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2308.05 | 0.00 | 01-JAN-00:40 | 505550.57 | 15-AUG-14:30 |
EnergyTransfer:Building | 1173.99 | 0.00 | 01-JAN-00:40 | 199976.53 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 222.67 | 0.00 | 01-JAN-00:40 | 27478.94 | 18-SEP-08:00 |
Heating:EnergyTransfer | 233.95 | 0.00 | 01-JAN-00:40 | 199976.53 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.30 | 0.00 | 01-JAN-00:10 | 20452.24 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 233.95 | 0.00 | 01-JAN-00:40 | 199976.53 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.30 | 0.00 | 01-JAN-00:10 | 20452.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 940.04 | 0.00 | 01-JAN-00:40 | 166522.60 | 09-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 222.37 | 0.00 | 01-JAN-00:40 | 27478.94 | 18-SEP-08:00 |
General:Cooling:EnergyTransfer | 940.04 | 0.00 | 01-JAN-00:40 | 166522.60 | 09-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 222.37 | 0.00 | 01-JAN-00:40 | 27478.94 | 18-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.91 | 0.00 | 01-JAN-00:40 | 16843.66 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.70 | 0.00 | 01-JAN-00:40 | 16843.66 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.70 | 0.00 | 01-JAN-00:40 | 16843.66 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.21 | 0.00 | 01-JAN-00:10 | 10749.98 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.21 | 0.00 | 01-JAN-00:10 | 10749.98 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 31.13 | 0.00 | 01-JAN-00:40 | 9711.41 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.79 | 0.00 | 01-JAN-00:40 | 9711.41 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.79 | 0.00 | 01-JAN-00:40 | 9711.41 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.34 | 0.00 | 01-JAN-00:10 | 5393.41 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.34 | 0.00 | 01-JAN-00:10 | 5393.41 | 17-JUL-12:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.45 | 0.00 | 01-JAN-00:40 | 7659.15 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.06 | 0.00 | 01-JAN-00:40 | 7659.15 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.06 | 0.00 | 01-JAN-00:40 | 7659.15 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.38 | 0.00 | 01-JAN-00:10 | 5789.52 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.38 | 0.00 | 01-JAN-00:10 | 5789.52 | 17-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 144.40 | 0.00 | 01-JAN-00:40 | 21585.75 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.19 | 0.00 | 01-JAN-00:20 | 21585.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.19 | 0.00 | 01-JAN-00:20 | 21585.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 142.21 | 0.00 | 01-JAN-00:40 | 19678.93 | 17-JUL-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 142.21 | 0.00 | 01-JAN-00:40 | 19678.93 | 17-JUL-09:10 |
EnergyTransfer:Zone:CORE_TOP | 140.59 | 0.00 | 01-JAN-00:40 | 29468.11 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 10.28 | 0.00 | 01-JAN-00:40 | 29468.11 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 10.28 | 0.00 | 01-JAN-00:40 | 29468.11 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 130.31 | 0.00 | 01-JAN-00:20 | 22402.89 | 27-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 130.31 | 0.00 | 01-JAN-00:20 | 22402.89 | 27-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.93 | 0.00 | 01-JAN-00:40 | 10409.08 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.19 | 0.00 | 01-JAN-00:40 | 10409.08 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.19 | 0.00 | 01-JAN-00:40 | 10409.08 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.74 | 0.00 | 01-JAN-00:10 | 7389.38 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.74 | 0.00 | 01-JAN-00:10 | 7389.38 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.91 | 0.00 | 01-JAN-00:40 | 9826.89 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 12.90 | 0.00 | 01-JAN-00:40 | 9826.89 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 12.90 | 0.00 | 01-JAN-00:40 | 9826.89 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.01 | 0.00 | 01-JAN-00:20 | 8641.99 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.01 | 0.00 | 01-JAN-00:20 | 8641.99 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.96 | 0.00 | 01-JAN-00:40 | 13521.43 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.44 | 0.00 | 01-JAN-00:40 | 13521.43 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 16.44 | 0.00 | 01-JAN-00:40 | 13521.43 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.53 | 0.00 | 01-JAN-00:20 | 12573.87 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 45.53 | 0.00 | 01-JAN-00:20 | 12573.87 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.34 | 0.00 | 01-JAN-00:40 | 9972.22 | 11-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.92 | 0.00 | 01-JAN-00:40 | 9972.22 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.92 | 0.00 | 01-JAN-00:40 | 9972.22 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.42 | 0.00 | 01-JAN-00:20 | 9266.84 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.42 | 0.00 | 01-JAN-00:20 | 9266.84 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.58 | 0.00 | 01-JAN-00:40 | 7263.47 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 11.89 | 0.00 | 01-JAN-00:40 | 7263.47 | 07-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 11.89 | 0.00 | 01-JAN-00:40 | 7263.47 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.69 | 0.00 | 01-JAN-00:20 | 5783.90 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.69 | 0.00 | 01-JAN-00:20 | 5783.90 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.38 | 0.00 | 01-JAN-00:40 | 7237.63 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.47 | 0.00 | 01-JAN-00:40 | 7237.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.47 | 0.00 | 01-JAN-00:40 | 7237.63 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.92 | 0.00 | 01-JAN-00:20 | 6841.64 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.92 | 0.00 | 01-JAN-00:20 | 6841.64 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 69.85 | 0.00 | 01-JAN-00:40 | 15906.14 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.22 | 0.00 | 01-JAN-00:40 | 15906.14 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 38.22 | 0.00 | 01-JAN-00:40 | 15906.14 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.62 | 0.00 | 01-JAN-00:20 | 11996.00 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.62 | 0.00 | 01-JAN-00:20 | 11996.00 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.69 | 0.00 | 01-JAN-00:40 | 7319.14 | 04-AUG-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.08 | 0.00 | 01-JAN-00:40 | 7274.96 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 7.08 | 0.00 | 01-JAN-00:40 | 7274.96 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.61 | 0.00 | 01-JAN-00:20 | 7319.14 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.61 | 0.00 | 01-JAN-00:20 | 7319.14 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.38 | 0.00 | 01-JAN-00:40 | 8858.38 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 11.61 | 0.00 | 01-JAN-00:40 | 8858.38 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 11.61 | 0.00 | 01-JAN-00:40 | 8858.38 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.77 | 0.00 | 01-JAN-00:20 | 6705.64 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.77 | 0.00 | 01-JAN-00:20 | 6705.64 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 38.00 | 0.00 | 01-JAN-00:40 | 8551.92 | 03-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 6.80 | 0.00 | 01-JAN-00:40 | 7592.55 | 11-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 6.80 | 0.00 | 01-JAN-00:40 | 7592.55 | 11-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.21 | 0.00 | 01-JAN-00:20 | 8551.92 | 03-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.21 | 0.00 | 01-JAN-00:20 | 8551.92 | 03-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.19 | 0.00 | 01-JAN-00:40 | 12121.11 | 21-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.90 | 0.00 | 01-JAN-00:40 | 10853.34 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 7.90 | 0.00 | 01-JAN-00:40 | 10853.34 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.30 | 0.00 | 01-JAN-00:20 | 12121.11 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.30 | 0.00 | 01-JAN-00:20 | 12121.11 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.64 | 0.00 | 01-JAN-00:40 | 8780.68 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.21 | 0.00 | 01-JAN-00:40 | 7604.11 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 7.21 | 0.00 | 01-JAN-00:40 | 7604.11 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.43 | 0.00 | 01-JAN-00:20 | 8780.68 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.43 | 0.00 | 01-JAN-00:20 | 8780.68 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
EnergyTransfer:HVAC | 1081.17 | 0.00 | 01-JAN-00:40 | 358518.82 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 482.42 | 0.00 | 01-JAN-00:40 | 267487.03 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 598.76 | 0.00 | 01-JAN-00:10 | 358518.82 | 15-AUG-14:30 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6713.52 | 15-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.300 | -222.368 | 0.000 | 0.000 | 33.353 | 81.703 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -140.331 |
CORE_MID | 0.000 | 0.000 | 2.190 | -142.208 | 0.000 | 0.000 | 34.716 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -103.002 |
CORE_TOP | 0.000 | 0.000 | 10.281 | -130.306 | 0.000 | 0.000 | 35.414 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -123.693 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 22.193 | -27.735 | 0.000 | 0.000 | 7.673 | 11.891 | 26.688 | 16.515 | 0.000 | 0.066 | 0.001 | 0.000 | -31.754 | 0.000 | -11.586 | -13.951 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 12.901 | -30.010 | 0.000 | 0.000 | 4.847 | 7.512 | 16.895 | 30.136 | 0.000 | 0.047 | 0.000 | 0.000 | -19.911 | 0.000 | -7.759 | -14.659 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 16.436 | -45.527 | 0.000 | 0.000 | 7.580 | 11.826 | 26.688 | 55.882 | 0.000 | 0.063 | 0.001 | 0.000 | -29.984 | 0.000 | -11.888 | -31.077 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 13.920 | -30.416 | 0.000 | 0.000 | 4.920 | 7.505 | 16.895 | 30.330 | 0.000 | 0.049 | 0.000 | 0.000 | -20.691 | 0.000 | -7.793 | -14.719 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 11.893 | -23.688 | 0.000 | 0.000 | 7.611 | 11.876 | 26.688 | 16.727 | 0.000 | 0.040 | 0.000 | 0.000 | -32.970 | 0.000 | -6.488 | -11.691 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.467 | -26.916 | 0.000 | 0.000 | 4.812 | 7.505 | 16.895 | 30.268 | 0.000 | 0.026 | 0.000 | 0.000 | -20.894 | 0.000 | -4.378 | -13.785 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 38.224 | -31.622 | 0.000 | 0.000 | 7.814 | 11.815 | 26.688 | 56.767 | 0.000 | 1.220 | 0.000 | 0.000 | -31.012 | 0.000 | -62.770 | -17.125 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 7.080 | -26.606 | 0.000 | 0.000 | 4.863 | 7.498 | 16.895 | 30.504 | 0.000 | 0.026 | 0.000 | 0.000 | -21.684 | 0.000 | -4.393 | -14.183 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 11.611 | -28.768 | 0.000 | 0.000 | 7.577 | 11.891 | 26.688 | 16.225 | 0.000 | 0.057 | 0.000 | 0.000 | -33.434 | 0.000 | -10.121 | -1.725 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 6.797 | -31.206 | 0.000 | 0.000 | 3.565 | 7.512 | 16.895 | 29.953 | 0.000 | 0.042 | 0.000 | 0.000 | -20.893 | 0.000 | -6.751 | -5.914 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 7.896 | -47.295 | 0.000 | 0.000 | 7.480 | 11.826 | 26.688 | 55.554 | 0.000 | 0.054 | 0.000 | 0.000 | -31.589 | 0.000 | -10.398 | -20.217 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 7.209 | -31.431 | 0.000 | 0.000 | 4.869 | 7.505 | 16.895 | 30.165 | 0.000 | 0.041 | 0.000 | 0.000 | -21.747 | 0.000 | -6.791 | -6.714 |
TOPFLOOR_PLENUM | 33.704 | -27.206 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.049 | 11.127 | 0.000 | 0.000 | 0.000 | -17.674 | -0.001 |
MIDFLOOR_PLENUM | 14.785 | -16.344 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.076 | 18.791 | 0.000 | 0.000 | 0.000 | -17.308 | -0.000 |
FIRSTFLOOR_PLENUM | 10.063 | -20.384 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.058 | 24.328 | 0.000 | 0.000 | 0.000 | -14.065 | -0.000 |
Total Facility | 58.553 | -63.934 | 175.400 | -876.101 | 0.000 | 0.000 | 177.094 | 361.273 | 762.041 | 399.028 | 0.000 | 1.912 | 54.249 | 0.000 | -316.563 | 0.000 | -200.162 | -532.788 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-SEP-04:02 | 0.00 | 0.00 | 0.00 | -46568.07 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 40636.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-JUL-04:03 | 0.00 | 0.00 | 0.00 | -35495.11 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 31527.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-04:03 | 0.00 | 0.00 | 0.00 | -39040.94 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 35073.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -8274.47 | 0.00 | 0.00 | 146.14 | 309.05 | 669.29 | 2517.56 | 0.00 | 0.00 | 4643.36 | 0.00 | -0.00 | 0.00 | -10.92 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -13870.97 | 0.00 | 0.00 | 13.75 | 32.61 | 317.77 | 10468.85 | 0.00 | 0.00 | 3197.17 | 0.00 | -0.00 | 0.00 | -159.16 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -18071.23 | 0.00 | 0.00 | 24.31 | 51.50 | 501.96 | 12763.82 | 0.00 | 0.00 | 5172.77 | 0.00 | -0.00 | 0.00 | -443.14 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:42 | 0.00 | 0.00 | 0.00 | -16185.90 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 7754.53 | 0.00 | 0.00 | 8113.02 | 0.00 | -0.00 | 0.00 | -32.01 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -5835.63 | 0.00 | 0.00 | 147.95 | 309.05 | 669.29 | 2573.34 | 0.00 | 0.00 | 2141.91 | 0.00 | -0.00 | 0.00 | -5.90 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-09:31 | 0.00 | 0.00 | 0.00 | -11227.29 | 0.00 | 0.00 | 15.99 | 32.61 | 317.77 | 9071.75 | 0.00 | 0.00 | 1862.98 | 0.00 | -0.00 | 0.00 | -73.80 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-14:52 | 0.00 | 0.00 | 0.00 | -13889.92 | 0.00 | 0.00 | 26.79 | 51.50 | 501.96 | 8673.45 | 0.00 | 0.00 | 4810.62 | 0.00 | -0.00 | 0.00 | -174.40 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-18:52 | 0.00 | 0.00 | 0.00 | -12028.62 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 5343.12 | 0.00 | 0.00 | 6388.33 | 0.00 | -0.00 | 0.00 | -53.20 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7193.30 | 0.00 | 0.00 | 144.48 | 309.05 | 669.29 | 2508.76 | 0.00 | 0.00 | 3572.95 | 0.00 | -0.00 | 0.00 | -11.22 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:12 | 0.00 | 0.00 | 0.00 | -13642.09 | 0.00 | 0.00 | 15.61 | 32.61 | 317.77 | 8181.38 | 0.00 | 0.00 | 5194.20 | 0.00 | -0.00 | 0.00 | -99.48 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-13:12 | 0.00 | 0.00 | 0.00 | -16123.26 | 0.00 | 0.00 | 25.65 | 51.50 | 501.96 | 9585.71 | 0.00 | 207.34 | 5751.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-17:12 | 0.00 | 0.00 | 0.00 | -14650.38 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 11418.82 | 0.00 | 0.00 | 2962.35 | 0.00 | -0.00 | 0.00 | -81.16 | 0.00 |
TOPFLOOR_PLENUM | 27-JUN-14:55 | 0.00 | -10891.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10896.52 | 0.00 | -0.00 | 0.00 | -5.04 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5393.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 5345.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:10 | 0.00 | -5787.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 5749.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-04:02 | 0.00 | 9699.37 | 0.00 | -173529.82 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 151211.25 | 0.00 | -6958.79 | 0.00 | -2483.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 26465.91 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32397.04 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24814.92 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28782.47 |
CORE_TOP | 26-DEC-05:01 | 0.00 | 0.00 | 33441.35 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37408.89 |
PERIMETER_TOP_ZN_3 | 26-DEC-01:42 | 0.00 | 0.00 | 11321.54 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2862.35 | 0.00 | -2377.84 | -6834.18 |
PERIMETER_TOP_ZN_2 | 26-DEC-01:42 | 0.00 | 0.00 | 12628.57 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.09 | 0.00 | -1617.28 | -9582.77 |
PERIMETER_TOP_ZN_1 | 26-DEC-01:42 | 0.00 | 0.00 | 15990.68 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2960.79 | 0.00 | -2411.51 | -11371.21 |
PERIMETER_TOP_ZN_4 | 26-DEC-01:42 | 0.00 | 0.00 | 13855.23 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1965.19 | 0.00 | -1623.79 | -10742.83 |
PERIMETER_BOT_ZN_3 | 02-JAN-02:62 | 0.00 | 0.00 | 8267.03 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1827.79 | 0.00 | -522.71 | -6669.35 |
PERIMETER_BOT_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 9513.13 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1806.05 | 0.00 | -388.86 | -7847.70 |
PERIMETER_BOT_ZN_1 | 07-FEB-07:10 | 0.00 | 0.00 | 16287.52 | 0.00 | 0.00 | 0.00 | 211.65 | 501.29 | 669.28 | 0.00 | 0.00 | 0.00 | 18981.83 | 0.00 | -3797.64 | 0.00 | -32853.93 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:11 | 0.00 | 0.00 | 10044.34 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1836.12 | 0.00 | -387.70 | -8349.99 |
PERIMETER_MID_ZN_3 | 05-FEB-22:22 | 0.00 | 0.00 | 9531.16 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3128.17 | 0.00 | -2162.12 | -4826.38 |
PERIMETER_MID_ZN_2 | 05-FEB-22:22 | 0.00 | 0.00 | 11292.03 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2089.73 | 0.00 | -1467.71 | -8105.25 |
PERIMETER_MID_ZN_1 | 26-DEC-01:42 | 0.00 | 0.00 | 13917.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3094.28 | 0.00 | -2088.30 | -9487.74 |
PERIMETER_MID_ZN_4 | 05-FEB-22:22 | 0.00 | 0.00 | 11415.12 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2152.30 | 0.00 | -1467.04 | -8166.43 |
TOPFLOOR_PLENUM | 11-DEC-06:12 | 17612.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -278.10 | -17334.88 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 10328.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -268.69 | -10059.43 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8993.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -212.12 | -8781.86 |
Total Facility | 02-JAN-05:01 | 11925.22 | 0.00 | 215375.93 | 0.00 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17470.98 | 0.00 | -8568.90 | -223322.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7492 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1333 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.4105 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6055 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.8084 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2870 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8746 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7248 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.7052 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7208 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.9042 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.8337 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9933 | 2.9933 | 0.8980 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2189 | 2.2189 | 0.7633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3375 | 2.3375 | 0.7924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7200 | 0.7200 | 0.2160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8186 | 0.8186 | 0.2456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0306 | 1.0306 | 0.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9017 | 0.9017 | 0.2705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5640 | 0.5640 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6683 | 0.6683 | 0.2005 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8202 | 0.8202 | 0.2461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7034 | 0.7034 | 0.2110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6299 | 0.6299 | 0.1890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7975 | 0.7975 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9343 | 0.9343 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8298 | 0.8298 | 0.2490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7492 | 5.1333 | 5.7492 | 1.7248 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.4105 | 4.6055 | 5.4105 | 1.7208 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.8084 | 5.2870 | 5.8084 | 1.8337 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4967 | 1.4967 | 0.8980 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1094 | 1.1094 | 0.7633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1687 | 1.1687 | 0.7924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3600 | 0.3600 | 0.2160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4093 | 0.4093 | 0.2456 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5153 | 0.5153 | 0.3092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4508 | 0.4508 | 0.2705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2820 | 0.2820 | 0.1692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3342 | 0.3342 | 0.2005 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4101 | 0.4101 | 0.2461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3517 | 0.3517 | 0.2110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3149 | 0.3149 | 0.1890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3988 | 0.3988 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4672 | 0.4672 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4149 | 0.4149 | 0.2490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8746 | 1.7248 | 1.7248 | 1.7248 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.7052 | 1.7208 | 1.7208 | 1.7208 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.9042 | 1.8337 | 1.8337 | 1.8337 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 518.83 |
Number of hours cooling loads not met | 43.33 |
Number of hours not met | 562.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 303.70 | 208123.63 | 223.40 | 105930.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 145.92 | 81617.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 361.27 | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.82 | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.92 | 1359.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 105.38 | 34590.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.30 | 10482.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1808.08 |
Natural Gas | 0.00 | 335.69 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2143.77 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.51 |
Space Heating | 60.96 |
Space Cooling | 29.29 |
Fans (All) | 21.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 362.91 |
Subtotal | 362.91 |
Natural Gas [MJ/m2] | |
Space Heating | 44.84 |
Service Water Heating | 22.54 |
Miscellaneous (All) | 67.38 |
Subtotal | 67.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.85 |
Space Heating | 24.59 |
Space Cooling | 6.81 |
Fans (All) | 4.92 |
Service Water Heating | 5.24 |
Receptacle Equipment | 35.55 |
Miscellaneous | 6.05 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2616. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8646.67 | 113.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8671.00 | 89.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8697.83 | 62.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8718.50 | 41.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8712.50 | 47.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8679.83 | 80.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8646.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.33 | 0.00 | 0.00 | 0.00 |
Average | 8718.41 | 41.59 | 0.00 | 0.00 | 0.00 |
Sum | 156931.33 | 748.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128284.33 | 19.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 19.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.11 | 1.22 | 0.00 | 0.00 | 0.00 |
Sum | 614558.00 | 22.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8237.67 | 522.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8334.00 | 426.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8385.50 | 374.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8332.83 | 427.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8346.67 | 413.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8329.50 | 430.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8312.50 | 447.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8358.50 | 401.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8349.50 | 410.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8244.83 | 515.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8303.33 | 456.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8295.17 | 464.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8340.17 | 419.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8306.00 | 454.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8291.00 | 469.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8024.17 | 735.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8309.83 | 450.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8282.83 | 477.17 | 0.00 | 0.00 | 0.00 |
Min | 8024.17 | 374.50 | 0.00 | 0.00 | 0.00 |
Max | 8385.50 | 735.83 | 0.00 | 0.00 | 0.00 |
Average | 8299.11 | 460.89 | 0.00 | 0.00 | 0.00 |
Sum | 149384.00 | 8296.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128038.67 | 265.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128131.33 | 172.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128112.17 | 191.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24892.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24897.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24903.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24366.17 | 542.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24898.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24904.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128131.33 | 542.83 | 0.00 | 0.00 | 0.00 |
Average | 34074.95 | 68.38 | 0.00 | 0.00 | 0.00 |
Sum | 613349.17 | 1230.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:04
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100756E+11 | 10137.44 | 20-JAN-17:00 | -1.1 | -3.7 | 0.176270E+10 | 2606.53 | 20-JAN-14:09 | -1.1 | -3.7 |
February | 0.984753E+10 | 10449.53 | 17-FEB-17:00 | 1.10 | 0.20 | 0.162514E+10 | 2606.57 | 17-FEB-14:20 | 1.10 | 0.20 |
March | 0.144035E+11 | 24989.07 | 16-MAR-05:03 | 14.03 | 11.42 | 0.210125E+10 | 2606.64 | 16-MAR-09:00 | 13.90 | 12.34 |
April | 0.156390E+11 | 26871.34 | 25-APR-05:02 | 6.70 | 5.86 | 0.189647E+10 | 2606.67 | 21-APR-13:00 | 6.70 | 5.86 |
May | 0.213909E+11 | 42204.13 | 25-MAY-05:02 | 10.10 | 9.45 | 0.207397E+10 | 2606.68 | 05-MAY-13:09 | 10.10 | 9.45 |
June | 0.266718E+11 | 45149.39 | 19-JUN-04:02 | 16.70 | 15.97 | 0.206964E+10 | 2606.84 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.276458E+11 | 45918.30 | 24-JUL-04:02 | 16.10 | 15.07 | 0.192459E+10 | 2606.69 | 12-JUL-09:00 | 16.10 | 15.07 |
August | 0.293507E+11 | 45795.81 | 21-AUG-04:02 | 14.90 | 13.34 | 0.216004E+10 | 2617.36 | 14-AUG-09:00 | 14.90 | 13.34 |
September | 0.242759E+11 | 46583.91 | 18-SEP-04:02 | 10.40 | 9.46 | 0.191700E+10 | 2606.80 | 12-SEP-13:09 | 10.40 | 9.46 |
October | 0.181153E+11 | 42001.04 | 05-OCT-05:02 | 8.80 | 8.23 | 0.198341E+10 | 2606.67 | 03-OCT-09:00 | 8.80 | 8.23 |
November | 0.140203E+11 | 19966.18 | 01-NOV-07:04 | 5.50 | 2.90 | 0.194562E+10 | 2608.44 | 30-NOV-10:30 | 6.10 | 2.30 |
December | 0.109322E+11 | 13201.20 | 01-DEC-17:00 | 7.20 | 4.89 | 0.178139E+10 | 2606.62 | 01-DEC-10:09 | 7.20 | 4.89 |
Annual Sum or Average | 0.222369E+12 | 0.232412E+11 | ||||||||
Minimum of Months | 0.984753E+10 | 10137.44 | -1.1 | -3.7 | 0.162514E+10 | 2606.53 | -1.1 | -3.7 | ||
Maximum of Months | 0.293507E+11 | 46583.91 | 16.70 | 15.97 | 0.216004E+10 | 2617.36 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 974890.52 | 426.23 | 18-FEB-17:25 | 0.25 | -0.9 | 0.00 | 0.00 | 01-FEB-00:10 | 0.25 | -0.9 |
March | 0.449831E+09 | 5724.45 | 15-MAR-14:20 | 25.93 | 16.12 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 16.12 |
April | 0.118404E+10 | 4674.16 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.296911E+10 | 7280.76 | 31-MAY-14:40 | 21.70 | 14.02 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.02 |
June | 0.555864E+10 | 10891.47 | 27-JUN-14:55 | 25.60 | 22.78 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 22.78 |
July | 0.687139E+10 | 10749.98 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.606389E+10 | 10674.09 | 09-AUG-15:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.320414E+10 | 8393.31 | 21-SEP-15:30 | 26.10 | 16.91 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.91 |
October | 0.808065E+09 | 4513.90 | 11-OCT-15:10 | 22.12 | 14.59 | 0.00 | 0.00 | 01-OCT-00:10 | 22.12 | 14.59 |
November | 95910694.29 | 1371.61 | 04-NOV-16:20 | 17.93 | 13.33 | 0.00 | 0.00 | 01-NOV-00:10 | 17.93 | 13.33 |
December | 139487.96 | 204.07 | 16-DEC-17:25 | 3.30 | 1.70 | 0.00 | 0.00 | 01-DEC-00:10 | 3.30 | 1.70 |
Annual Sum or Average | 0.272061E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.687139E+10 | 10891.47 | 31.15 | 22.78 | 0.00 | 0.00 | 31.15 | 22.78 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10843209.56 | 2189.88 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 9014811.87 | 2022.30 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.239126E+09 | 1870.22 | 16-MAR-20:50 | 12.02 | 11.20 | 0.00 | 0.00 | 01-MAR-00:10 | 12.02 | 11.20 |
April | 0.474533E+09 | 1880.66 | 22-APR-05:25 | 1.70 | 0.90 | 0.00 | 0.00 | 01-APR-00:10 | 1.70 | 0.90 |
May | 0.143994E+10 | 2402.54 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.320806E+10 | 4534.83 | 12-JUN-15:30 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
July | 0.419069E+10 | 5393.41 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.391382E+10 | 4721.27 | 14-AUG-16:00 | 27.80 | 21.01 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.01 |
September | 0.213979E+10 | 3446.03 | 18-SEP-13:00 | 18.90 | 12.42 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 12.42 |
October | 0.600897E+09 | 2196.93 | 24-OCT-06:01 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 0.105781E+09 | 1579.03 | 02-NOV-06:02 | 4.40 | 3.64 | 0.00 | 0.00 | 01-NOV-00:10 | 4.40 | 3.64 |
December | 11440492.37 | 1921.16 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.163439E+11 | 0.00 | ||||||||
Minimum of Months | 9014811.87 | 1579.03 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.419069E+10 | 5393.41 | 29.15 | 21.01 | 0.00 | 0.00 | 29.15 | 21.01 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 51162167.99 | 1772.41 | 06-JAN-07:10 | -12.4 | -13.0 | 0.00 | 0.00 | 01-JAN-00:10 | -12.4 | -13.0 |
February | 54289593.10 | 2295.51 | 10-FEB-17:10 | -7.4 | -8.0 | 0.00 | 0.00 | 01-FEB-00:10 | -7.4 | -8.0 |
March | 0.419907E+09 | 2557.50 | 17-MAR-06:03 | 9.90 | 9.56 | 0.00 | 0.00 | 01-MAR-00:10 | 9.90 | 9.56 |
April | 0.829530E+09 | 2706.78 | 10-APR-17:01 | 2.80 | 2.25 | 0.00 | 0.00 | 01-APR-00:10 | 2.80 | 2.25 |
May | 0.204894E+10 | 2811.31 | 30-MAY-16:10 | 17.70 | 14.03 | 0.00 | 0.00 | 01-MAY-00:10 | 17.70 | 14.03 |
June | 0.368228E+10 | 4637.30 | 12-JUN-15:10 | 29.72 | 20.02 | 0.00 | 0.00 | 01-JUN-00:10 | 29.72 | 20.02 |
July | 0.457094E+10 | 5789.52 | 17-JUL-12:10 | 27.30 | 21.00 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 21.00 |
August | 0.455213E+10 | 5068.69 | 14-AUG-16:00 | 27.80 | 21.01 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.01 |
September | 0.286691E+10 | 4542.25 | 18-SEP-06:08 | 10.28 | 9.20 | 0.00 | 0.00 | 01-SEP-00:10 | 10.28 | 9.20 |
October | 0.986155E+09 | 2447.33 | 23-OCT-17:01 | 4.40 | 2.51 | 0.00 | 0.00 | 01-OCT-00:10 | 4.40 | 2.51 |
November | 0.277434E+09 | 1890.65 | 07-NOV-07:01 | 1.78 | 0.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.78 | 0.46 |
December | 44722150.47 | 1470.11 | 08-DEC-07:10 | -10.4 | -10.8 | 0.00 | 0.00 | 01-DEC-00:10 | -10.4 | -10.8 |
Annual Sum or Average | 0.203844E+11 | 0.00 | ||||||||
Minimum of Months | 44722150.47 | 1470.11 | -12.4 | -13.0 | 0.00 | 0.00 | -12.4 | -13.0 | ||
Maximum of Months | 0.457094E+10 | 5789.52 | 29.72 | 21.01 | 0.00 | 0.00 | 29.72 | 21.01 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543521E+10 | 6413.51 | 12-JAN-16:50 | -6.6 | -8.3 | 0.153877E+10 | 2250.83 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.525750E+10 | 6540.64 | 17-FEB-17:00 | 1.10 | 0.20 | 0.141059E+10 | 2292.92 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.914598E+10 | 12734.00 | 16-MAR-16:00 | 15.60 | 13.95 | 0.188154E+10 | 2606.62 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.962242E+10 | 11911.01 | 21-APR-16:00 | 13.30 | 8.77 | 0.179356E+10 | 2606.63 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.138666E+11 | 30839.92 | 24-MAY-05:03 | 18.80 | 15.75 | 0.205118E+10 | 2606.65 | 05-MAY-13:09 | 18.80 | 15.75 |
June | 0.185248E+11 | 33544.56 | 19-JUN-04:02 | 16.70 | 15.97 | 0.206431E+10 | 2606.82 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.199594E+11 | 35500.23 | 17-JUL-04:03 | 23.22 | 21.05 | 0.192144E+10 | 2606.67 | 12-JUL-09:00 | 23.22 | 21.05 |
August | 0.202939E+11 | 34212.31 | 07-AUG-04:02 | 20.00 | 18.50 | 0.215690E+10 | 2606.83 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.154804E+11 | 33970.90 | 18-SEP-04:02 | 10.40 | 9.46 | 0.190620E+10 | 2606.76 | 12-SEP-13:09 | 10.40 | 9.46 |
October | 0.103982E+11 | 13477.62 | 12-OCT-16:00 | 18.30 | 14.87 | 0.189568E+10 | 2606.63 | 03-OCT-09:00 | 18.30 | 14.87 |
November | 0.814591E+10 | 8810.95 | 01-NOV-16:00 | 9.40 | 6.91 | 0.174352E+10 | 2606.58 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.607809E+10 | 6876.13 | 01-DEC-17:00 | 7.20 | 4.89 | 0.151405E+10 | 2377.84 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.142208E+12 | 0.218777E+11 | ||||||||
Minimum of Months | 0.525750E+10 | 6413.51 | -6.6 | -8.3 | 0.141059E+10 | 2250.83 | 0.60 | -3.3 | ||
Maximum of Months | 0.202939E+11 | 35500.23 | 23.22 | 21.05 | 0.215690E+10 | 2606.83 | 23.22 | 21.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361140E+10 | 6071.47 | 12-JAN-16:40 | -6.5 | -8.3 | 0.147914E+10 | 2111.20 | 06-JAN-14:00 | -6.5 | -8.3 |
February | 0.379473E+10 | 6320.74 | 28-FEB-17:00 | -0.6 | -3.0 | 0.135816E+10 | 2177.19 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.777648E+10 | 13079.43 | 15-MAR-16:00 | 25.00 | 15.96 | 0.178674E+10 | 2606.61 | 15-MAR-13:30 | 25.00 | 15.96 |
April | 0.886424E+10 | 12686.93 | 21-APR-16:00 | 13.30 | 8.77 | 0.170299E+10 | 2606.63 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.133061E+11 | 16834.41 | 31-MAY-16:00 | 22.20 | 14.47 | 0.201455E+10 | 2606.65 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.185129E+11 | 33805.11 | 12-JUN-05:02 | 22.30 | 17.71 | 0.205695E+10 | 2702.46 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.202744E+11 | 39048.09 | 17-JUL-04:03 | 23.22 | 21.05 | 0.191930E+10 | 2606.66 | 12-JUL-09:00 | 23.22 | 21.05 |
August | 0.200384E+11 | 36271.36 | 07-AUG-04:02 | 20.00 | 18.50 | 0.215135E+10 | 2606.83 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.143060E+11 | 26466.97 | 18-SEP-05:03 | 9.50 | 8.65 | 0.188322E+10 | 2606.75 | 12-SEP-13:09 | 9.50 | 8.65 |
October | 0.920535E+10 | 13070.23 | 12-OCT-16:00 | 18.30 | 14.87 | 0.178426E+10 | 2606.60 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.663515E+10 | 7602.22 | 01-NOV-16:00 | 9.40 | 6.91 | 0.160757E+10 | 2501.18 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.398084E+10 | 6602.62 | 01-DEC-15:10 | 7.20 | 5.59 | 0.143599E+10 | 2248.68 | 01-DEC-14:00 | 7.20 | 5.59 |
Annual Sum or Average | 0.130306E+12 | 0.211802E+11 | ||||||||
Minimum of Months | 0.361140E+10 | 6071.47 | -6.5 | -8.3 | 0.135816E+10 | 2111.20 | -6.5 | -8.3 | ||
Maximum of Months | 0.202744E+11 | 39048.09 | 25.00 | 21.05 | 0.215135E+10 | 2702.46 | 25.85 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18801183.55 | 1309.50 | 14-JAN-17:02 | 3.22 | 2.72 | 0.304416E+09 | 406.69 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 31469799.98 | 1301.45 | 18-FEB-17:03 | 0.82 | -0.6 | 0.275993E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.860911E+09 | 3926.93 | 15-MAR-14:50 | 25.68 | 16.21 | 0.348054E+09 | 549.50 | 15-MAR-13:30 | 25.68 | 16.21 |
April | 0.155458E+10 | 2557.97 | 21-APR-15:30 | 14.15 | 8.57 | 0.324156E+09 | 549.47 | 07-APR-13:00 | 14.15 | 8.57 |
May | 0.311284E+10 | 4931.81 | 23-MAY-14:40 | 23.90 | 13.32 | 0.403618E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.510077E+10 | 7554.16 | 27-JUN-15:47 | 26.02 | 22.57 | 0.429206E+09 | 579.97 | 27-JUN-15:30 | 26.02 | 22.57 |
July | 0.599866E+10 | 8278.80 | 17-JUL-06:03 | 22.88 | 21.17 | 0.403819E+09 | 549.51 | 24-JUL-13:39 | 25.93 | 17.98 |
August | 0.552418E+10 | 6986.11 | 14-AUG-04:02 | 23.22 | 21.98 | 0.449014E+09 | 549.54 | 02-AUG-13:09 | 23.22 | 21.98 |
September | 0.337350E+10 | 4993.50 | 15-SEP-14:00 | 25.60 | 21.03 | 0.380411E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.160377E+10 | 2584.37 | 12-OCT-15:30 | 18.30 | 15.05 | 0.339005E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.503628E+09 | 1764.54 | 16-NOV-16:50 | 18.12 | 13.51 | 0.306807E+09 | 467.80 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 52275738.18 | 1402.40 | 01-DEC-13:20 | 12.03 | 10.45 | 0.293417E+09 | 406.69 | 27-DEC-10:00 | -9.4 | -11.1 |
Annual Sum or Average | 0.277354E+11 | 0.425792E+10 | ||||||||
Minimum of Months | 18801183.55 | 1301.45 | 0.82 | -0.6 | 0.275993E+09 | 406.69 | -9.4 | -11.1 | ||
Maximum of Months | 0.599866E+10 | 8278.80 | 26.02 | 22.57 | 0.449014E+09 | 579.97 | 26.02 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21714623.49 | 1463.60 | 14-JAN-17:02 | 3.22 | 2.72 | 0.192975E+09 | 257.45 | 03-JAN-10:09 | 3.22 | 2.72 |
February | 0.135190E+09 | 1777.44 | 28-FEB-09:50 | -4.5 | -6.0 | 0.175338E+09 | 277.18 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.115783E+10 | 2997.00 | 15-MAR-14:00 | 26.10 | 16.06 | 0.221918E+09 | 347.88 | 15-MAR-13:30 | 26.10 | 16.06 |
April | 0.202833E+10 | 5230.52 | 24-APR-09:20 | 6.47 | 3.13 | 0.213891E+09 | 347.88 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.370511E+10 | 7486.51 | 31-MAY-09:00 | 17.80 | 13.21 | 0.256606E+09 | 347.88 | 26-MAY-09:00 | 17.80 | 13.21 |
June | 0.528428E+10 | 10445.30 | 11-JUN-10:43 | 24.90 | 17.26 | 0.270699E+09 | 348.34 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.596050E+10 | 13873.64 | 04-JUL-09:02 | 21.28 | 17.22 | 0.254894E+09 | 348.25 | 03-JUL-09:50 | 21.28 | 17.22 |
August | 0.556565E+10 | 8246.54 | 10-AUG-09:40 | 26.87 | 20.17 | 0.282735E+09 | 348.17 | 10-AUG-09:50 | 27.33 | 20.25 |
September | 0.374807E+10 | 6421.70 | 04-SEP-10:02 | 17.98 | 13.30 | 0.241168E+09 | 347.89 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.181865E+10 | 3989.22 | 11-OCT-09:40 | 16.13 | 11.96 | 0.215286E+09 | 347.87 | 11-OCT-09:09 | 16.13 | 11.96 |
November | 0.537987E+09 | 2009.65 | 03-NOV-09:50 | 5.32 | 2.80 | 0.194264E+09 | 300.31 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 46623411.23 | 1451.54 | 23-DEC-17:02 | 4.32 | 1.18 | 0.186124E+09 | 257.45 | 26-DEC-14:09 | -9.4 | -11.1 |
Annual Sum or Average | 0.300099E+11 | 0.270590E+10 | ||||||||
Minimum of Months | 21714623.49 | 1451.54 | -4.5 | -6.0 | 0.175338E+09 | 257.45 | -9.4 | -11.1 | ||
Maximum of Months | 0.596050E+10 | 13873.64 | 26.87 | 20.17 | 0.282735E+09 | 348.34 | 27.80 | 20.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535683E+09 | 3552.95 | 12-JAN-13:40 | -6.5 | -9.0 | 0.313172E+09 | 549.49 | 12-JAN-14:39 | -5.8 | -8.3 |
February | 0.688573E+09 | 6082.29 | 28-FEB-13:50 | 0.00 | -3.0 | 0.287234E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.237652E+10 | 10175.38 | 15-MAR-13:30 | 25.55 | 15.84 | 0.374783E+09 | 549.53 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.297741E+10 | 8148.71 | 21-APR-13:30 | 15.00 | 8.17 | 0.340436E+09 | 549.52 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.482846E+10 | 11172.69 | 14-MAY-13:42 | 24.82 | 18.07 | 0.399886E+09 | 549.52 | 10-MAY-13:00 | 24.82 | 18.07 |
June | 0.659685E+10 | 10093.92 | 12-JUN-13:10 | 29.60 | 19.81 | 0.422688E+09 | 569.39 | 27-JUN-15:20 | 25.77 | 22.70 |
July | 0.770991E+10 | 12260.92 | 30-JUL-12:43 | 25.60 | 19.42 | 0.400109E+09 | 549.94 | 31-JUL-13:50 | 25.18 | 19.30 |
August | 0.804770E+10 | 17810.36 | 13-AUG-13:12 | 30.00 | 22.88 | 0.444918E+09 | 550.06 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.634454E+10 | 18071.19 | 10-SEP-13:42 | 17.20 | 10.65 | 0.382136E+09 | 550.11 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.357593E+10 | 12048.08 | 11-OCT-12:30 | 21.95 | 13.79 | 0.362588E+09 | 549.79 | 11-OCT-13:20 | 22.20 | 14.14 |
November | 0.144026E+10 | 7494.61 | 03-NOV-12:35 | 8.53 | 4.68 | 0.324789E+09 | 549.50 | 01-NOV-13:39 | 8.53 | 4.68 |
December | 0.405646E+09 | 3623.40 | 16-DEC-13:30 | 5.60 | 3.03 | 0.297849E+09 | 521.68 | 04-DEC-14:50 | 5.60 | 3.03 |
Annual Sum or Average | 0.455275E+11 | 0.435059E+10 | ||||||||
Minimum of Months | 0.405646E+09 | 3552.95 | -6.5 | -9.0 | 0.287234E+09 | 521.68 | -5.8 | -8.3 | ||
Maximum of Months | 0.804770E+10 | 18071.19 | 30.00 | 22.88 | 0.444918E+09 | 569.39 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60933420.49 | 1605.27 | 14-JAN-17:02 | 3.22 | 2.72 | 0.192968E+09 | 257.44 | 30-JAN-10:09 | -9.9 | -11.1 |
February | 0.152262E+09 | 2401.92 | 28-FEB-16:40 | -0.2 | -2.7 | 0.175762E+09 | 310.32 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.117099E+10 | 3692.17 | 15-MAR-14:20 | 25.93 | 16.12 | 0.219608E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.195148E+10 | 6264.86 | 24-APR-16:00 | 13.30 | 7.63 | 0.202054E+09 | 345.07 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.382551E+10 | 11391.36 | 27-MAY-17:06 | 20.32 | 11.21 | 0.239765E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.550131E+10 | 16188.62 | 25-JUN-17:42 | 26.78 | 18.33 | 0.261106E+09 | 374.23 | 27-JUN-15:50 | 26.02 | 22.57 |
July | 0.588838E+10 | 15974.51 | 02-JUL-17:12 | 24.63 | 16.88 | 0.249325E+09 | 347.87 | 24-JUL-13:39 | 25.93 | 17.98 |
August | 0.564558E+10 | 15417.91 | 27-AUG-17:02 | 22.20 | 18.81 | 0.274690E+09 | 347.88 | 02-AUG-13:09 | 22.20 | 18.81 |
September | 0.379355E+10 | 15166.54 | 04-SEP-16:42 | 18.30 | 12.93 | 0.227832E+09 | 347.86 | 18-SEP-13:00 | 17.80 | 12.70 |
October | 0.179959E+10 | 6006.70 | 11-OCT-16:00 | 21.70 | 14.52 | 0.208686E+09 | 347.25 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.557302E+09 | 2382.74 | 03-NOV-15:30 | 9.45 | 5.21 | 0.194325E+09 | 307.93 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 69477355.21 | 1658.56 | 14-DEC-07:03 | 6.10 | 5.62 | 0.186085E+09 | 257.44 | 26-DEC-10:09 | -11.9 | -13.2 |
Annual Sum or Average | 0.304164E+11 | 0.263221E+10 | ||||||||
Minimum of Months | 60933420.49 | 1605.27 | -0.2 | -2.7 | 0.175762E+09 | 257.44 | -11.9 | -13.2 | ||
Maximum of Months | 0.588838E+10 | 16188.62 | 26.78 | 18.81 | 0.274690E+09 | 374.23 | 26.02 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21054176.32 | 1039.13 | 14-JAN-17:02 | 3.22 | 2.72 | 0.305221E+09 | 406.69 | 02-JAN-14:30 | 3.22 | 2.72 |
February | 25828391.70 | 1030.08 | 18-FEB-17:03 | 0.82 | -0.6 | 0.277060E+09 | 406.69 | 06-FEB-14:30 | 0.82 | -0.6 |
March | 0.646384E+09 | 1691.88 | 15-MAR-15:30 | 25.30 | 16.10 | 0.346340E+09 | 540.02 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.123179E+10 | 1549.75 | 21-APR-15:40 | 13.87 | 8.65 | 0.320928E+09 | 508.58 | 07-APR-13:00 | 13.87 | 8.65 |
May | 0.217762E+10 | 2983.73 | 23-MAY-14:40 | 23.90 | 13.32 | 0.400940E+09 | 549.49 | 10-MAY-13:09 | 23.90 | 13.32 |
June | 0.381181E+10 | 4989.40 | 27-JUN-13:30 | 28.90 | 23.32 | 0.431610E+09 | 549.53 | 22-JUN-13:09 | 28.90 | 23.32 |
July | 0.479988E+10 | 5837.11 | 17-JUL-06:03 | 22.88 | 21.17 | 0.404348E+09 | 549.50 | 12-JUL-09:00 | 22.88 | 21.17 |
August | 0.480045E+10 | 5583.37 | 09-AUG-15:20 | 29.40 | 18.24 | 0.453014E+09 | 554.50 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.313126E+10 | 4316.33 | 15-SEP-14:00 | 25.60 | 21.03 | 0.395333E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.186370E+10 | 2408.44 | 05-OCT-14:40 | 18.90 | 12.59 | 0.367686E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.105549E+10 | 1475.19 | 16-NOV-17:00 | 18.30 | 13.48 | 0.321154E+09 | 492.99 | 01-NOV-13:50 | 18.30 | 13.48 |
December | 0.122734E+09 | 1267.48 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295781E+09 | 438.37 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.236880E+11 | 0.431942E+10 | ||||||||
Minimum of Months | 21054176.32 | 1030.08 | 0.82 | -0.6 | 0.277060E+09 | 406.69 | 0.82 | -0.6 | ||
Maximum of Months | 0.480045E+10 | 5837.11 | 29.40 | 23.32 | 0.453014E+09 | 554.50 | 28.90 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27868582.24 | 1213.16 | 14-JAN-17:02 | 3.22 | 2.72 | 0.193595E+09 | 257.46 | 02-JAN-10:00 | 3.22 | 2.72 |
February | 0.110777E+09 | 1342.32 | 28-FEB-09:30 | -5.8 | -7.1 | 0.175827E+09 | 262.79 | 28-FEB-10:09 | -3.6 | -5.3 |
March | 0.969526E+09 | 1906.99 | 15-MAR-14:10 | 26.02 | 16.09 | 0.220189E+09 | 332.47 | 15-MAR-13:00 | 26.02 | 16.09 |
April | 0.171634E+10 | 3643.49 | 24-APR-09:30 | 6.65 | 3.34 | 0.213036E+09 | 347.87 | 24-APR-09:00 | 7.20 | 3.99 |
May | 0.278980E+10 | 4892.57 | 31-MAY-09:20 | 17.97 | 13.39 | 0.256172E+09 | 347.88 | 26-MAY-09:00 | 17.97 | 13.39 |
June | 0.428647E+10 | 6536.06 | 12-JUN-09:30 | 27.25 | 19.42 | 0.272579E+09 | 347.90 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.507108E+10 | 11228.29 | 04-JUL-09:31 | 21.83 | 17.44 | 0.255823E+09 | 347.89 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.502575E+10 | 6729.50 | 10-AUG-10:00 | 27.80 | 20.31 | 0.285777E+09 | 348.16 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.361465E+10 | 5362.17 | 18-SEP-09:40 | 16.33 | 11.61 | 0.248440E+09 | 347.89 | 12-SEP-13:09 | 16.33 | 11.61 |
October | 0.213707E+10 | 3506.65 | 11-OCT-09:40 | 16.13 | 11.96 | 0.232191E+09 | 347.88 | 10-OCT-09:50 | 16.13 | 11.96 |
November | 0.106333E+10 | 1823.43 | 03-NOV-08:35 | 3.53 | 1.63 | 0.199967E+09 | 322.59 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 0.103157E+09 | 1345.36 | 01-DEC-07:05 | 10.68 | 9.22 | 0.187040E+09 | 257.46 | 26-DEC-14:09 | -9.4 | -11.1 |
Annual Sum or Average | 0.269158E+11 | 0.274064E+10 | ||||||||
Minimum of Months | 27868582.24 | 1213.16 | -5.8 | -7.1 | 0.175827E+09 | 257.46 | -9.4 | -11.1 | ||
Maximum of Months | 0.507108E+10 | 11228.29 | 27.80 | 20.31 | 0.285777E+09 | 348.16 | 26.02 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50919256.53 | 1710.00 | 21-JAN-12:30 | -0.6 | -3.1 | 0.278444E+09 | 406.64 | 26-JAN-10:50 | -4.6 | -6.6 |
February | 91220755.58 | 2001.61 | 18-FEB-14:40 | 2.80 | 0.63 | 0.251996E+09 | 411.07 | 22-FEB-14:00 | 10.60 | 4.92 |
March | 0.812730E+09 | 6240.73 | 15-MAR-13:40 | 25.73 | 15.91 | 0.332549E+09 | 549.50 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.124431E+10 | 3395.58 | 22-APR-13:40 | 15.20 | 6.94 | 0.309512E+09 | 549.51 | 21-APR-13:00 | 15.20 | 6.94 |
May | 0.257752E+10 | 4900.92 | 23-MAY-14:30 | 23.90 | 13.29 | 0.371068E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.29 |
June | 0.460071E+10 | 11632.09 | 27-JUN-12:00 | 30.00 | 22.87 | 0.410465E+09 | 562.94 | 27-JUN-12:09 | 30.10 | 23.02 |
July | 0.653328E+10 | 11955.50 | 21-JUL-12:00 | 30.00 | 21.57 | 0.399039E+09 | 581.08 | 21-JUL-12:09 | 30.10 | 21.65 |
August | 0.701129E+10 | 11996.00 | 10-AUG-12:00 | 30.00 | 22.51 | 0.443906E+09 | 582.62 | 10-AUG-12:09 | 29.82 | 22.08 |
September | 0.509734E+10 | 13889.82 | 10-SEP-14:52 | 17.20 | 10.67 | 0.383729E+09 | 549.80 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.258232E+10 | 9710.85 | 11-OCT-12:40 | 22.03 | 13.91 | 0.352517E+09 | 549.73 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.894130E+09 | 2452.75 | 03-NOV-14:40 | 9.80 | 5.31 | 0.310130E+09 | 541.50 | 03-NOV-13:00 | 9.80 | 5.31 |
December | 0.126352E+09 | 2326.95 | 16-DEC-13:40 | 5.60 | 2.97 | 0.273055E+09 | 406.64 | 22-DEC-10:09 | -2.0 | -2.8 |
Annual Sum or Average | 0.316221E+11 | 0.411641E+10 | ||||||||
Minimum of Months | 50919256.53 | 1710.00 | -0.6 | -3.1 | 0.251996E+09 | 406.64 | -4.6 | -6.6 | ||
Maximum of Months | 0.701129E+10 | 13889.82 | 30.00 | 22.87 | 0.443906E+09 | 582.62 | 30.10 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55899691.53 | 1410.79 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193537E+09 | 257.45 | 02-JAN-10:00 | -6.2 | -8.3 |
February | 0.109109E+09 | 1754.82 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176009E+09 | 296.09 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.937665E+09 | 2034.67 | 15-MAR-14:30 | 25.85 | 16.15 | 0.217606E+09 | 331.89 | 15-MAR-13:00 | 25.85 | 16.15 |
April | 0.160894E+10 | 3755.80 | 24-APR-17:30 | 11.70 | 7.64 | 0.202436E+09 | 338.70 | 26-APR-15:09 | 14.90 | 9.09 |
May | 0.280939E+10 | 5404.15 | 31-MAY-18:00 | 21.10 | 14.05 | 0.243121E+09 | 347.84 | 23-MAY-13:30 | 21.10 | 14.05 |
June | 0.442137E+10 | 12028.77 | 11-JUN-18:52 | 23.90 | 17.25 | 0.268386E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.490180E+10 | 11883.18 | 30-JUL-17:52 | 24.40 | 20.25 | 0.254252E+09 | 347.86 | 03-JUL-13:39 | 24.40 | 20.25 |
August | 0.497726E+10 | 9384.43 | 12-AUG-18:23 | 21.95 | 15.41 | 0.283621E+09 | 348.15 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.347546E+10 | 10839.31 | 10-SEP-17:32 | 16.10 | 10.54 | 0.243280E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.214687E+10 | 4920.96 | 11-OCT-16:00 | 21.70 | 14.52 | 0.222163E+09 | 347.85 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.104310E+10 | 1935.64 | 03-NOV-15:50 | 9.08 | 5.02 | 0.198357E+09 | 317.19 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 0.119613E+09 | 1448.90 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187024E+09 | 261.16 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.266065E+11 | 0.268979E+10 | ||||||||
Minimum of Months | 55899691.53 | 1410.79 | -6.2 | -8.3 | 0.176009E+09 | 257.45 | -6.2 | -8.3 | ||
Maximum of Months | 0.497726E+10 | 12028.77 | 25.85 | 20.25 | 0.283621E+09 | 348.15 | 25.85 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48999115.82 | 1163.52 | 14-JAN-17:02 | 3.22 | 2.72 | 0.305239E+09 | 406.68 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 94407615.53 | 1165.78 | 17-FEB-15:00 | 3.30 | 1.08 | 0.277065E+09 | 406.68 | 06-FEB-14:30 | 3.30 | 1.08 |
March | 0.109275E+10 | 3504.52 | 15-MAR-14:50 | 25.68 | 16.21 | 0.356092E+09 | 549.49 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.177811E+10 | 2477.88 | 21-APR-15:30 | 14.15 | 8.57 | 0.340116E+09 | 549.49 | 21-APR-13:00 | 14.15 | 8.57 |
May | 0.307882E+10 | 4698.34 | 23-MAY-14:40 | 23.90 | 13.32 | 0.418889E+09 | 549.50 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.498576E+10 | 6288.31 | 12-JUN-15:00 | 30.00 | 19.98 | 0.433606E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.579229E+10 | 7196.00 | 17-JUL-06:03 | 22.88 | 21.17 | 0.405000E+09 | 549.61 | 20-JUL-13:30 | 30.00 | 23.60 |
August | 0.542565E+10 | 6785.36 | 15-AUG-05:02 | 22.70 | 20.72 | 0.453001E+09 | 549.54 | 02-AUG-13:09 | 22.70 | 20.72 |
September | 0.343562E+10 | 4757.24 | 15-SEP-14:00 | 25.60 | 21.03 | 0.393152E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.194894E+10 | 2783.36 | 12-OCT-15:20 | 18.30 | 15.11 | 0.359881E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.956966E+09 | 1674.15 | 16-NOV-17:00 | 18.30 | 13.48 | 0.316432E+09 | 494.74 | 01-NOV-13:50 | 18.30 | 13.48 |
December | 0.130368E+09 | 1373.09 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294978E+09 | 429.26 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.287687E+11 | 0.435345E+10 | ||||||||
Minimum of Months | 48999115.82 | 1163.52 | 3.22 | 1.08 | 0.277065E+09 | 406.68 | -7.0 | -8.8 | ||
Maximum of Months | 0.579229E+10 | 7196.00 | 30.00 | 21.17 | 0.453001E+09 | 549.61 | 30.00 | 23.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58859761.80 | 1445.17 | 14-JAN-17:02 | 3.22 | 2.72 | 0.142289E+09 | 250.67 | 23-JAN-08:09 | -6.2 | -8.2 |
February | 0.195710E+09 | 1901.11 | 28-FEB-09:50 | -4.5 | -6.0 | 0.129424E+09 | 287.36 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.138757E+10 | 2832.07 | 14-MAR-10:20 | 20.33 | 16.97 | 0.165099E+09 | 338.71 | 15-MAR-14:50 | 25.68 | 16.21 |
April | 0.234891E+10 | 6000.97 | 24-APR-08:50 | 5.92 | 2.67 | 0.159961E+09 | 338.72 | 24-APR-10:09 | 7.67 | 4.25 |
May | 0.379796E+10 | 7661.84 | 31-MAY-08:40 | 17.60 | 13.16 | 0.191041E+09 | 338.73 | 26-MAY-10:09 | 17.60 | 13.16 |
June | 0.516833E+10 | 11417.81 | 11-JUN-10:23 | 24.70 | 17.10 | 0.200252E+09 | 338.81 | 12-JUN-08:00 | 26.70 | 19.40 |
July | 0.575244E+10 | 13548.67 | 04-JUL-08:42 | 21.10 | 17.25 | 0.188784E+09 | 339.27 | 17-JUL-08:50 | 24.82 | 20.54 |
August | 0.543715E+10 | 13642.44 | 06-AUG-09:12 | 24.47 | 17.45 | 0.209235E+09 | 340.19 | 15-AUG-14:39 | 24.23 | 21.18 |
September | 0.386728E+10 | 7480.38 | 10-SEP-09:53 | 15.60 | 10.49 | 0.179827E+09 | 338.74 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.220248E+10 | 4566.07 | 11-OCT-09:00 | 15.00 | 11.35 | 0.163574E+09 | 338.72 | 11-OCT-10:20 | 17.60 | 12.74 |
November | 0.894670E+09 | 2183.06 | 03-NOV-09:00 | 3.90 | 1.83 | 0.145142E+09 | 312.74 | 03-NOV-08:00 | 3.90 | 1.83 |
December | 94654665.28 | 1649.41 | 14-DEC-07:03 | 6.10 | 5.62 | 0.137401E+09 | 250.67 | 11-DEC-09:39 | 6.10 | 5.62 |
Annual Sum or Average | 0.312060E+11 | 0.201203E+10 | ||||||||
Minimum of Months | 58859761.80 | 1445.17 | -4.5 | -6.0 | 0.129424E+09 | 250.67 | -6.2 | -8.2 | ||
Maximum of Months | 0.575244E+10 | 13642.44 | 24.70 | 17.45 | 0.209235E+09 | 340.19 | 26.70 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697430E+09 | 4549.32 | 12-JAN-13:40 | -6.5 | -9.0 | 0.317752E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.868113E+09 | 6323.23 | 28-FEB-13:40 | 0.00 | -2.9 | 0.291806E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.275732E+10 | 9629.39 | 15-MAR-13:30 | 25.55 | 15.84 | 0.385580E+09 | 549.79 | 15-MAR-13:50 | 25.92 | 15.99 |
April | 0.332986E+10 | 8086.44 | 24-APR-13:10 | 11.38 | 6.04 | 0.352795E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.483523E+10 | 7650.96 | 26-MAY-13:30 | 20.85 | 13.56 | 0.412960E+09 | 549.51 | 05-MAY-13:09 | 20.85 | 13.56 |
June | 0.639786E+10 | 9268.02 | 12-JUN-13:10 | 29.60 | 19.81 | 0.428959E+09 | 549.54 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.738944E+10 | 15468.80 | 30-JUL-14:32 | 24.80 | 19.05 | 0.403176E+09 | 550.04 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.782000E+10 | 16122.52 | 13-AUG-13:12 | 30.00 | 22.88 | 0.450515E+09 | 550.04 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.642839E+10 | 15852.57 | 04-SEP-12:53 | 19.40 | 13.13 | 0.391922E+09 | 550.26 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.411541E+10 | 12019.43 | 11-OCT-12:30 | 21.95 | 13.79 | 0.378805E+09 | 549.77 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.203948E+10 | 8338.66 | 03-NOV-12:25 | 8.35 | 4.56 | 0.335060E+09 | 549.50 | 01-NOV-13:00 | 8.35 | 4.56 |
December | 0.616878E+09 | 4217.88 | 16-DEC-13:30 | 5.60 | 3.03 | 0.300969E+09 | 549.48 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.472954E+11 | 0.445030E+10 | ||||||||
Minimum of Months | 0.616878E+09 | 4217.88 | -6.5 | -9.0 | 0.291806E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.782000E+10 | 16122.52 | 30.00 | 22.88 | 0.450515E+09 | 550.26 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107195E+09 | 1720.09 | 12-JAN-16:00 | -6.1 | -8.3 | 0.193435E+09 | 262.56 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.214467E+09 | 2288.51 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176418E+09 | 318.37 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.139922E+10 | 3388.24 | 15-MAR-14:20 | 25.93 | 16.12 | 0.223094E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.226212E+10 | 6172.11 | 24-APR-16:00 | 13.30 | 7.63 | 0.207198E+09 | 347.37 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.385121E+10 | 10414.58 | 27-MAY-17:06 | 20.32 | 11.21 | 0.248259E+09 | 347.85 | 23-MAY-13:09 | 20.32 | 11.21 |
June | 0.532782E+10 | 13957.53 | 10-JUN-18:22 | 22.20 | 13.18 | 0.266507E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.564926E+10 | 14650.43 | 02-JUL-17:12 | 24.63 | 16.88 | 0.252422E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.545889E+10 | 14228.80 | 06-AUG-16:31 | 27.80 | 18.98 | 0.280077E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.383017E+10 | 8232.84 | 21-SEP-16:00 | 26.10 | 17.18 | 0.236521E+09 | 347.87 | 12-SEP-13:09 | 26.10 | 17.18 |
October | 0.222809E+10 | 5871.39 | 11-OCT-16:00 | 21.70 | 14.52 | 0.216344E+09 | 347.83 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.959201E+09 | 2335.41 | 03-NOV-15:30 | 9.45 | 5.21 | 0.196993E+09 | 322.52 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 0.144041E+09 | 1718.66 | 14-DEC-07:03 | 6.10 | 5.62 | 0.186659E+09 | 261.04 | 04-DEC-15:00 | 6.10 | 5.62 |
Annual Sum or Average | 0.314317E+11 | 0.268393E+10 | ||||||||
Minimum of Months | 0.107195E+09 | 1718.66 | -6.1 | -8.3 | 0.176418E+09 | 261.04 | -6.2 | -8.3 | ||
Maximum of Months | 0.564926E+10 | 14650.43 | 27.80 | 18.98 | 0.280077E+09 | 347.88 | 27.80 | 18.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275545E+09 | 26465.95 | 02-JAN-05:01 | -0.7 |
February | 16697775.95 | 22225.96 | 22-FEB-07:01 | -1.5 |
March | 400803.71 | 6680.06 | 06-MAR-07:01 | -10.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 7419501.60 | 21145.28 | 11-DEC-07:01 | -16.4 |
Annual Sum or Average | 0.300063E+09 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 0.275545E+09 | 26465.95 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854800E+10 | 15924.43 | 24-JAN-06:12 | -12.0 |
February | 0.744053E+10 | 17029.07 | 06-FEB-06:13 | -13.9 |
March | 0.358277E+10 | 15558.38 | 06-MAR-06:13 | -11.1 |
April | 0.136797E+10 | 12378.67 | 17-APR-05:12 | -4.1 |
May | 0.387573E+09 | 5103.85 | 08-MAY-05:02 | 3.40 |
June | 0.119339E+09 | 6109.95 | 28-JUN-05:03 | 17.20 |
July | 62843745.06 | 7862.43 | 03-JUL-05:03 | 11.78 |
August | 92682874.47 | 7106.78 | 01-AUG-05:03 | 11.10 |
September | 0.286580E+09 | 8510.34 | 18-SEP-05:03 | 9.50 |
October | 0.121584E+10 | 9235.57 | 30-OCT-06:01 | -0.4 |
November | 0.282091E+10 | 12777.96 | 24-NOV-06:12 | -3.7 |
December | 0.777886E+10 | 17612.97 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.337039E+11 | |||
Minimum of Months | 62843745.06 | 5103.85 | -18.2 | |
Maximum of Months | 0.854800E+10 | 17612.97 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393392E+10 | 10328.12 | 02-JAN-07:11 | -1.1 |
February | 0.337830E+10 | 9393.56 | 06-FEB-07:03 | -14.1 |
March | 0.161546E+10 | 7062.56 | 06-MAR-07:11 | -10.5 |
April | 0.595327E+09 | 4338.36 | 17-APR-06:03 | -4.2 |
May | 71219837.68 | 3722.66 | 07-MAY-13:52 | 15.00 |
June | 23929460.39 | 2917.01 | 04-JUN-12:52 | 18.90 |
July | 25252859.29 | 3262.92 | 21-JUL-04:02 | 26.52 |
August | 22272014.01 | 3467.56 | 13-AUG-15:12 | 29.80 |
September | 28201676.82 | 3225.79 | 04-SEP-13:32 | 18.33 |
October | 0.545341E+09 | 4725.71 | 09-OCT-12:32 | 12.03 |
November | 0.118327E+10 | 4383.73 | 24-NOV-07:03 | -3.2 |
December | 0.336261E+10 | 9581.47 | 26-DEC-07:03 | -12.3 |
Annual Sum or Average | 0.147851E+11 | |||
Minimum of Months | 22272014.01 | 2917.01 | -14.1 | |
Maximum of Months | 0.393392E+10 | 10328.12 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293290E+10 | 8993.98 | 02-JAN-07:01 | -1.1 |
February | 0.242020E+10 | 5250.11 | 06-FEB-07:01 | -14.1 |
March | 0.103112E+10 | 4506.95 | 06-MAR-08:23 | -8.9 |
April | 0.281232E+09 | 4194.34 | 25-APR-05:02 | 6.70 |
May | 24211673.64 | 4780.55 | 22-MAY-05:03 | 9.08 |
June | 30063621.36 | 4310.29 | 05-JUN-04:03 | 14.40 |
July | 29487019.08 | 4073.99 | 06-JUL-04:03 | 12.12 |
August | 29236278.40 | 4315.74 | 22-AUG-04:03 | 14.40 |
September | 38127887.05 | 6184.42 | 29-SEP-05:03 | 10.50 |
October | 0.197608E+09 | 5760.16 | 03-OCT-05:02 | 4.40 |
November | 0.707417E+09 | 3404.49 | 07-NOV-08:06 | 2.20 |
December | 0.234125E+10 | 5349.73 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.100629E+11 | |||
Minimum of Months | 24211673.64 | 3404.49 | -14.1 | |
Maximum of Months | 0.293290E+10 | 8993.98 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.964255E+09 | 24814.95 | 02-JAN-05:01 | -0.7 |
February | 0.635618E+09 | 22346.11 | 13-FEB-06:01 | -9.4 |
March | 84630778.59 | 21467.45 | 06-MAR-06:01 | -11.1 |
April | 8533172.11 | 19829.03 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 1138989.26 | 18983.15 | 30-OCT-06:01 | -0.4 |
November | 21493066.38 | 19920.55 | 22-NOV-07:01 | 0.68 |
December | 0.474781E+09 | 22341.94 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.219045E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.5 | |
Maximum of Months | 0.964255E+09 | 24814.95 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332358E+10 | 33262.16 | 02-JAN-05:01 | -0.7 |
February | 0.283933E+10 | 33389.96 | 06-FEB-05:01 | -14.8 |
March | 0.851437E+09 | 32143.11 | 06-MAR-05:01 | -11.1 |
April | 0.147714E+09 | 30246.43 | 17-APR-05:01 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.102131E+09 | 29376.77 | 30-OCT-05:01 | -0.1 |
November | 0.417248E+09 | 30339.40 | 24-NOV-06:01 | -3.8 |
December | 0.260000E+10 | 33441.53 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.102814E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.332358E+10 | 33441.53 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643120E+10 | 11082.92 | 09-JAN-01:52 | -8.3 |
February | 0.561367E+10 | 11321.10 | 05-FEB-22:22 | -12.8 |
March | 0.232886E+10 | 10804.02 | 06-MAR-04:23 | -11.1 |
April | 0.473283E+09 | 10283.49 | 17-APR-04:11 | -3.5 |
May | 12014017.17 | 8385.13 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 6844464.07 | 8204.51 | 30-SEP-06:03 | 7.30 |
October | 0.357933E+09 | 10065.65 | 30-OCT-04:01 | -0.5 |
November | 0.130389E+10 | 10183.46 | 24-NOV-05:01 | -3.0 |
December | 0.566526E+10 | 11321.79 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.221929E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.643120E+10 | 11321.79 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377612E+10 | 12289.33 | 09-JAN-01:52 | -8.3 |
February | 0.329444E+10 | 12608.90 | 05-FEB-22:22 | -12.8 |
March | 0.110028E+10 | 12007.55 | 06-MAR-05:01 | -11.1 |
April | 0.207849E+09 | 11493.61 | 17-APR-04:11 | -3.5 |
May | 6928584.13 | 7332.62 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4627617.62 | 5721.36 | 30-SEP-06:03 | 7.30 |
October | 0.196752E+09 | 11284.71 | 30-OCT-04:01 | -0.5 |
November | 0.762661E+09 | 11353.75 | 24-NOV-05:01 | -3.0 |
December | 0.355176E+10 | 12628.66 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.129014E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.377612E+10 | 12628.66 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472417E+10 | 15527.63 | 09-JAN-01:52 | -8.3 |
February | 0.428615E+10 | 15929.39 | 05-FEB-22:22 | -12.8 |
March | 0.141212E+10 | 15089.10 | 06-MAR-05:01 | -11.1 |
April | 0.399449E+09 | 14510.88 | 17-APR-04:11 | -3.5 |
May | 20033092.91 | 11895.65 | 01-MAY-06:01 | 2.35 |
June | 679869.69 | 3399.35 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 5748715.92 | 8757.31 | 30-SEP-06:03 | 7.30 |
October | 0.247213E+09 | 14101.24 | 30-OCT-04:01 | -0.5 |
November | 0.980064E+09 | 14410.33 | 24-NOV-05:01 | -3.0 |
December | 0.436033E+10 | 15990.89 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.164360E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.472417E+10 | 15990.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408799E+10 | 13483.47 | 09-JAN-01:52 | -8.3 |
February | 0.355022E+10 | 13843.85 | 05-FEB-22:22 | -12.8 |
March | 0.127858E+10 | 13160.74 | 06-MAR-05:01 | -11.1 |
April | 0.291291E+09 | 12537.58 | 17-APR-04:11 | -3.5 |
May | 14293668.51 | 10270.47 | 01-MAY-06:01 | 2.35 |
June | 576486.85 | 2882.43 | 14-JUN-06:03 | 7.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 5946248.26 | 5622.49 | 30-SEP-06:03 | 7.30 |
October | 0.226037E+09 | 12265.39 | 30-OCT-04:01 | -0.5 |
November | 0.838551E+09 | 12443.34 | 24-NOV-05:01 | -3.0 |
December | 0.362662E+10 | 13855.31 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.139201E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.408799E+10 | 13855.31 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.401152E+10 | 8267.06 | 02-JAN-02:62 | -1.7 |
February | 0.338397E+10 | 8257.56 | 06-FEB-04:51 | -15.0 |
March | 0.145703E+10 | 8133.81 | 06-MAR-05:01 | -11.1 |
April | 0.201162E+09 | 7400.39 | 17-APR-05:01 | -4.0 |
May | 2461419.19 | 6528.58 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 19709085.99 | 6727.43 | 30-OCT-05:01 | -0.1 |
November | 0.198278E+09 | 7158.42 | 24-NOV-06:01 | -3.8 |
December | 0.261889E+10 | 8162.30 | 26-DEC-04:51 | -12.2 |
Annual Sum or Average | 0.118930E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.401152E+10 | 8267.06 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228747E+10 | 9513.13 | 09-JAN-05:11 | -9.4 |
February | 0.185944E+10 | 9431.08 | 06-FEB-05:01 | -14.8 |
March | 0.516103E+09 | 9412.96 | 06-MAR-05:01 | -11.1 |
April | 59466118.78 | 8612.12 | 17-APR-05:01 | -4.0 |
May | 1356947.08 | 3824.54 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 140908.91 | 939.39 | 30-SEP-06:03 | 7.30 |
October | 14512441.26 | 7732.90 | 30-OCT-06:01 | -0.4 |
November | 0.120772E+09 | 8449.12 | 24-NOV-06:01 | -3.8 |
December | 0.160740E+10 | 9424.11 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.646666E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.228747E+10 | 9513.13 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895449E+10 | 15290.93 | 04-JAN-08:00 | -13.3 |
February | 0.785616E+10 | 16287.79 | 07-FEB-07:10 | -16.5 |
March | 0.455750E+10 | 15104.75 | 07-MAR-07:10 | -12.9 |
April | 0.247062E+10 | 13230.96 | 17-APR-06:10 | -4.2 |
May | 0.107995E+10 | 11496.79 | 01-MAY-06:10 | 2.35 |
June | 0.296876E+09 | 10037.60 | 14-JUN-06:10 | 7.67 |
July | 53840683.30 | 8134.77 | 13-JUL-06:07 | 13.07 |
August | 0.132117E+09 | 9363.16 | 01-AUG-06:05 | 11.57 |
September | 0.425017E+09 | 9888.47 | 06-SEP-06:10 | 6.28 |
October | 0.155807E+10 | 12497.80 | 17-OCT-06:10 | -2.8 |
November | 0.320770E+10 | 13019.39 | 24-NOV-07:10 | -3.2 |
December | 0.763238E+10 | 16115.23 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.382247E+11 | |||
Minimum of Months | 53840683.30 | 8134.77 | -16.5 | |
Maximum of Months | 0.895449E+10 | 16287.79 | 13.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253891E+10 | 10044.33 | 09-JAN-05:11 | -9.4 |
February | 0.205896E+10 | 9917.00 | 06-FEB-05:01 | -14.8 |
March | 0.587079E+09 | 9905.23 | 06-MAR-05:01 | -11.1 |
April | 86700865.30 | 8861.34 | 17-APR-05:01 | -4.0 |
May | 3297751.31 | 8066.01 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 15708685.00 | 8123.76 | 30-OCT-06:01 | -0.4 |
November | 0.130568E+09 | 8811.40 | 24-NOV-06:01 | -3.8 |
December | 0.165841E+10 | 9906.60 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.707964E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.253891E+10 | 10044.33 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378152E+10 | 9265.58 | 02-JAN-02:62 | -1.7 |
February | 0.318919E+10 | 9531.23 | 05-FEB-22:22 | -12.8 |
March | 0.101314E+10 | 9124.07 | 06-MAR-05:01 | -11.1 |
April | 0.116277E+09 | 8194.78 | 17-APR-05:01 | -4.0 |
May | 232906.51 | 3105.42 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 113620.45 | 757.47 | 30-SEP-06:03 | 7.30 |
October | 66104110.08 | 8011.61 | 30-OCT-05:01 | -0.1 |
November | 0.375881E+09 | 8363.21 | 24-NOV-05:01 | -3.0 |
December | 0.306841E+10 | 9514.99 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.116109E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.378152E+10 | 9531.23 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221693E+10 | 10877.10 | 09-JAN-05:01 | -9.4 |
February | 0.186340E+10 | 11292.12 | 05-FEB-22:22 | -12.8 |
March | 0.436503E+09 | 10817.51 | 06-MAR-05:01 | -11.1 |
April | 50484406.22 | 9640.67 | 17-APR-05:01 | -4.0 |
May | 749605.40 | 2889.38 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 1064956.47 | 4602.07 | 30-SEP-06:03 | 7.30 |
October | 45118532.35 | 9430.04 | 30-OCT-05:01 | -0.1 |
November | 0.235087E+09 | 9622.25 | 24-NOV-06:01 | -3.8 |
December | 0.194811E+10 | 11272.72 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.679745E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.221693E+10 | 11292.12 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258441E+10 | 13436.17 | 09-JAN-05:01 | -9.4 |
February | 0.224838E+10 | 13820.09 | 13-FEB-04:33 | -8.9 |
March | 0.497581E+09 | 13256.54 | 06-MAR-05:01 | -11.1 |
April | 96767806.97 | 11971.30 | 17-APR-05:01 | -4.0 |
May | 1551857.87 | 10684.25 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 389376.39 | 2595.84 | 30-SEP-06:03 | 7.30 |
October | 50329216.34 | 11638.34 | 30-OCT-05:01 | -0.1 |
November | 0.272297E+09 | 12018.23 | 24-NOV-06:01 | -3.8 |
December | 0.214471E+10 | 13917.56 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.789642E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.6 | |
Maximum of Months | 0.258441E+10 | 13917.56 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238953E+10 | 10992.02 | 09-JAN-05:01 | -9.4 |
February | 0.198182E+10 | 11415.21 | 05-FEB-22:22 | -12.8 |
March | 0.511424E+09 | 10887.41 | 06-MAR-05:01 | -11.1 |
April | 74556842.43 | 9608.91 | 17-APR-05:01 | -4.0 |
May | 2305333.47 | 8437.65 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 972463.80 | 3917.02 | 30-SEP-06:03 | 7.30 |
October | 47762409.88 | 9378.61 | 30-OCT-05:01 | -0.1 |
November | 0.255100E+09 | 9665.34 | 24-NOV-06:01 | -3.8 |
December | 0.194581E+10 | 11398.19 | 26-DEC-01:42 | -11.6 |
Annual Sum or Average | 0.720928E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.238953E+10 | 11415.21 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105898E+10 | 1503.90 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.924820E+09 | 1358.35 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105652E+10 | 1173.03 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.924527E+09 | 1046.43 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.980858E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.968020E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.910609E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102132E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936999E+09 | 1139.64 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100573E+10 | 1467.00 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.105426E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.104788E+10 | 1503.90 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118905E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.910609E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105898E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.664548E+09 | 952.10 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.583943E+09 | 865.50 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.668092E+09 | 678.23 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.585870E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.622867E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.614757E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.578076E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.648334E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.592756E+09 | 654.53 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.633258E+09 | 873.19 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.662769E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.656746E+09 | 952.10 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.751202E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.578076E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.668092E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103842E+10 | 1503.90 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.917133E+09 | 1336.04 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105252E+10 | 1148.57 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.925692E+09 | 1039.59 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.984287E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.971659E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.913839E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102375E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.936132E+09 | 1121.06 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.996513E+09 | 1346.05 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103756E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102834E+10 | 1503.90 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118258E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.913839E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105252E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.663307E+09 | 952.03 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582546E+09 | 856.43 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.667573E+09 | 770.50 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585588E+09 | 696.04 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.621472E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613407E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.577202E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.646814E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.593354E+09 | 749.65 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.635723E+09 | 928.82 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.661739E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.656654E+09 | 952.03 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.750538E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.577202E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.667573E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105628E+10 | 1503.90 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.923615E+09 | 1351.90 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105547E+10 | 1158.05 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.924168E+09 | 1026.13 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.980337E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.967597E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.910335E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102078E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936050E+09 | 1123.36 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100418E+10 | 1464.67 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.105187E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.104505E+10 | 1503.90 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118757E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.910335E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105628E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.663506E+09 | 952.10 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.583412E+09 | 862.55 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.667608E+09 | 667.52 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.585565E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.622495E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.614466E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.577834E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.647949E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.592227E+09 | 642.97 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.632632E+09 | 865.83 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.661796E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.655740E+09 | 952.10 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.750523E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.577834E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.667608E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103703E+10 | 1503.90 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.916274E+09 | 1328.28 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105185E+10 | 1132.21 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.925155E+09 | 1018.93 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.983478E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.971141E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.913352E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102314E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.935387E+09 | 1103.78 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.995649E+09 | 1337.09 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103621E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102678E+10 | 1503.90 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118155E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.913352E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105185E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.662144E+09 | 952.03 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582044E+09 | 853.20 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.667053E+09 | 764.33 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585176E+09 | 687.43 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.621121E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613192E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.576978E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.646554E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.592843E+09 | 742.82 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.634869E+09 | 927.59 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.660635E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.655630E+09 | 952.03 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.749824E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.576978E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.667053E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105898E+10 | 1503.90 | 02-JAN-16:49 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.924819E+09 | 1358.34 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105652E+10 | 1173.01 | 17-MAR-07:10 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.924526E+09 | 1046.40 | 12-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.980858E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.968019E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.910608E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102132E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.936999E+09 | 1139.61 | 26-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100573E+10 | 1467.00 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.105426E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.104788E+10 | 1503.90 | 01-DEC-16:40 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.118905E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.910608E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.105898E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.664547E+09 | 952.10 | 02-JAN-16:49 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.583942E+09 | 865.49 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.668092E+09 | 678.22 | 17-MAR-07:10 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.585870E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.622867E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.614757E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.578076E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.648334E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.592756E+09 | 654.52 | 26-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.633257E+09 | 873.20 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.662768E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.656745E+09 | 952.10 | 01-DEC-16:40 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.751201E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.578076E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.668092E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.103842E+10 | 1503.90 | 02-JAN-16:49 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.917132E+09 | 1336.03 | 01-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105252E+10 | 1148.55 | 17-MAR-07:10 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.925692E+09 | 1039.56 | 12-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.984286E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.971659E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.913839E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102375E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.936131E+09 | 1121.04 | 26-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.996512E+09 | 1346.06 | 30-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103756E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.102834E+10 | 1503.90 | 01-DEC-16:40 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118258E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.913839E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105252E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.663306E+09 | 952.03 | 02-JAN-16:49 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.582545E+09 | 856.43 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.667573E+09 | 770.49 | 17-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585588E+09 | 696.02 | 12-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.621472E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613407E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.577202E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.646814E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.593354E+09 | 749.63 | 26-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.635723E+09 | 928.82 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.661738E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.656653E+09 | 952.03 | 01-DEC-16:40 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.750538E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.577202E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.667573E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105898E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188210E+10 |
February | 0.901968E+09 | 0.924820E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200401E+10 |
March | 0.107774E+10 | 0.105652E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509644.31 | 0.122124E+10 |
April | 0.956342E+09 | 0.924527E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982361E+09 |
May | 0.103597E+10 | 0.980858E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590780.67 | 0.603052E+09 |
June | 0.103308E+10 | 0.968020E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12715301.55 | 0.356560E+09 |
July | 0.959235E+09 | 0.910609E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27439963.21 | 0.211905E+09 |
August | 0.107774E+10 | 0.102132E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23179693.48 | 0.243768E+09 |
September | 0.956342E+09 | 0.936999E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1661566.29 | 0.350144E+09 |
October | 0.994195E+09 | 0.100573E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742305E+09 |
November | 0.984487E+09 | 0.105426E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100502E+10 |
December | 0.959235E+09 | 0.104788E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198310E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118905E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66096949.51 | 0.115856E+11 |
Minimum of Months | 0.901968E+09 | 0.910609E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211905E+09 |
Maximum of Months | 0.107774E+10 | 0.105898E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27439963.21 | 0.200401E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.664548E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125612E+10 |
February | 0.571020E+09 | 0.583943E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133810E+10 |
March | 0.682301E+09 | 0.668092E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 338242.24 | 0.818559E+09 |
April | 0.605444E+09 | 0.585870E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663977E+09 |
May | 0.655854E+09 | 0.622867E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 603908.64 | 0.410533E+09 |
June | 0.654023E+09 | 0.614757E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9041191.53 | 0.236501E+09 |
July | 0.607275E+09 | 0.578076E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19069301.16 | 0.139154E+09 |
August | 0.682301E+09 | 0.648334E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16463494.45 | 0.161373E+09 |
September | 0.605444E+09 | 0.592756E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1235544.19 | 0.234497E+09 |
October | 0.629407E+09 | 0.633258E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503085E+09 |
November | 0.623262E+09 | 0.662769E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673330E+09 |
December | 0.607275E+09 | 0.656746E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132336E+10 |
Annual Sum or Average | 0.755301E+10 | 0.751202E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46751682.21 | 0.775859E+10 |
Minimum of Months | 0.571020E+09 | 0.578076E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139154E+09 |
Maximum of Months | 0.682301E+09 | 0.668092E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19069301.16 | 0.133810E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103842E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191323E+10 |
February | 0.901968E+09 | 0.917133E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202474E+10 |
March | 0.107774E+10 | 0.105252E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 438326.96 | 0.127738E+10 |
April | 0.956342E+09 | 0.925692E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101747E+10 |
May | 0.103597E+10 | 0.984287E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 228300.56 | 0.617388E+09 |
June | 0.103308E+10 | 0.971659E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12160315.68 | 0.351813E+09 |
July | 0.959235E+09 | 0.913839E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27206227.74 | 0.211511E+09 |
August | 0.107774E+10 | 0.102375E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21469772.00 | 0.249273E+09 |
September | 0.956342E+09 | 0.936132E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1565586.52 | 0.370085E+09 |
October | 0.994195E+09 | 0.996513E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795868E+09 |
November | 0.984487E+09 | 0.103756E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104282E+10 |
December | 0.959235E+09 | 0.102834E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201615E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118258E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63068529.46 | 0.118877E+11 |
Minimum of Months | 0.901968E+09 | 0.913839E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211511E+09 |
Maximum of Months | 0.107774E+10 | 0.105252E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27206227.74 | 0.202474E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.663307E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125635E+10 |
February | 0.570983E+09 | 0.582546E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133963E+10 |
March | 0.682256E+09 | 0.667573E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 565927.04 | 0.831311E+09 |
April | 0.605404E+09 | 0.585588E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672238E+09 |
May | 0.655811E+09 | 0.621472E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186570.47 | 0.413101E+09 |
June | 0.653980E+09 | 0.613407E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10300166.63 | 0.242979E+09 |
July | 0.607235E+09 | 0.577202E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19950908.49 | 0.145036E+09 |
August | 0.682256E+09 | 0.646814E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16680390.67 | 0.166478E+09 |
September | 0.605404E+09 | 0.593354E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171620.37 | 0.234509E+09 |
October | 0.629366E+09 | 0.635723E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498933E+09 |
November | 0.623221E+09 | 0.661739E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670274E+09 |
December | 0.607235E+09 | 0.656654E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132253E+10 |
Annual Sum or Average | 0.755252E+10 | 0.750538E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48855583.66 | 0.779336E+10 |
Minimum of Months | 0.570983E+09 | 0.577202E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145036E+09 |
Maximum of Months | 0.682256E+09 | 0.667573E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19950908.49 | 0.133963E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105628E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104433E+10 |
February | 0.901968E+09 | 0.923615E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110504E+10 |
March | 0.107774E+10 | 0.105547E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 488304.06 | 0.676724E+09 |
April | 0.956342E+09 | 0.924168E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538537E+09 |
May | 0.103597E+10 | 0.980337E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 476387.52 | 0.314429E+09 |
June | 0.103308E+10 | 0.967597E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8078279.70 | 0.187506E+09 |
July | 0.959235E+09 | 0.910335E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16455694.11 | 0.109258E+09 |
August | 0.107774E+10 | 0.102078E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13941048.83 | 0.131975E+09 |
September | 0.956342E+09 | 0.936050E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 892158.95 | 0.202474E+09 |
October | 0.994195E+09 | 0.100418E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450691E+09 |
November | 0.984487E+09 | 0.105187E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599825E+09 |
December | 0.959235E+09 | 0.104505E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112707E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118757E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40331873.17 | 0.648787E+10 |
Minimum of Months | 0.901968E+09 | 0.910335E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109258E+09 |
Maximum of Months | 0.107774E+10 | 0.105628E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16455694.11 | 0.112707E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.663506E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698879E+09 |
February | 0.571020E+09 | 0.583412E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738585E+09 |
March | 0.682301E+09 | 0.667608E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 342868.64 | 0.456612E+09 |
April | 0.605444E+09 | 0.585565E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370434E+09 |
May | 0.655854E+09 | 0.622495E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 233611.96 | 0.222152E+09 |
June | 0.654023E+09 | 0.614466E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4923596.05 | 0.128858E+09 |
July | 0.607275E+09 | 0.577834E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10714434.33 | 75741722.92 |
August | 0.682301E+09 | 0.647949E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9093531.96 | 90899057.44 |
September | 0.605444E+09 | 0.592227E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 622241.39 | 0.137312E+09 |
October | 0.629407E+09 | 0.632632E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305563E+09 |
November | 0.623262E+09 | 0.661796E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401077E+09 |
December | 0.607275E+09 | 0.655740E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751780E+09 |
Annual Sum or Average | 0.755301E+10 | 0.750523E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25930284.32 | 0.437789E+10 |
Minimum of Months | 0.571020E+09 | 0.577834E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75741722.92 |
Maximum of Months | 0.682301E+09 | 0.667608E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10714434.33 | 0.751780E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103703E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101406E+11 |
February | 0.901968E+09 | 0.916274E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935486E+10 |
March | 0.107774E+10 | 0.105185E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12631699.86 | 0.786724E+10 |
April | 0.956342E+09 | 0.925155E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536324E+10 |
May | 0.103597E+10 | 0.983478E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4406801.37 | 0.340198E+10 |
June | 0.103308E+10 | 0.971141E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200513E+09 | 0.177249E+10 |
July | 0.959235E+09 | 0.913352E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554729E+09 | 0.718136E+09 |
August | 0.107774E+10 | 0.102314E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426529E+09 | 0.127143E+10 |
September | 0.956342E+09 | 0.935387E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21390203.20 | 0.224643E+10 |
October | 0.994195E+09 | 0.995649E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491530E+10 |
November | 0.984487E+09 | 0.103621E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637880E+10 |
December | 0.959235E+09 | 0.102678E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933926E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118155E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122020E+10 | 0.627698E+11 |
Minimum of Months | 0.901968E+09 | 0.913352E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718136E+09 |
Maximum of Months | 0.107774E+10 | 0.105185E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554729E+09 | 0.101406E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.662144E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696680E+09 |
February | 0.570983E+09 | 0.582044E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738892E+09 |
March | 0.682256E+09 | 0.667053E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 449919.70 | 0.462867E+09 |
April | 0.605404E+09 | 0.585176E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371649E+09 |
May | 0.655811E+09 | 0.621121E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127666.59 | 0.224690E+09 |
June | 0.653980E+09 | 0.613192E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4922108.86 | 0.133793E+09 |
July | 0.607235E+09 | 0.576978E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10886549.41 | 80216687.78 |
August | 0.682256E+09 | 0.646554E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8815277.43 | 94863208.16 |
September | 0.605404E+09 | 0.592843E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570495.08 | 0.138190E+09 |
October | 0.629366E+09 | 0.634869E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301054E+09 |
November | 0.623221E+09 | 0.660635E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399083E+09 |
December | 0.607235E+09 | 0.655630E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751096E+09 |
Annual Sum or Average | 0.755252E+10 | 0.749824E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25772017.07 | 0.439307E+10 |
Minimum of Months | 0.570983E+09 | 0.576978E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80216687.78 |
Maximum of Months | 0.682256E+09 | 0.667053E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10886549.41 | 0.751096E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105898E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161308E+10 |
February | 0.901968E+09 | 0.924819E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171256E+10 |
March | 0.107774E+10 | 0.105652E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415020.30 | 0.107136E+10 |
April | 0.956342E+09 | 0.924526E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871898E+09 |
May | 0.103597E+10 | 0.980858E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 698004.02 | 0.530694E+09 |
June | 0.103308E+10 | 0.968019E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11028152.80 | 0.309191E+09 |
July | 0.959235E+09 | 0.910608E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23572896.48 | 0.182094E+09 |
August | 0.107774E+10 | 0.102132E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19663605.98 | 0.212416E+09 |
September | 0.956342E+09 | 0.936999E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410604.17 | 0.313865E+09 |
October | 0.994195E+09 | 0.100573E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678313E+09 |
November | 0.984487E+09 | 0.105426E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907338E+09 |
December | 0.959235E+09 | 0.104788E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171862E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118905E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56788283.76 | 0.101214E+11 |
Minimum of Months | 0.901968E+09 | 0.910608E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182094E+09 |
Maximum of Months | 0.107774E+10 | 0.105898E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23572896.48 | 0.171862E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.664547E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107710E+10 |
February | 0.421807E+09 | 0.583942E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114265E+10 |
March | 0.502994E+09 | 0.668092E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 342814.50 | 0.717789E+09 |
April | 0.447140E+09 | 0.585870E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584633E+09 |
May | 0.484071E+09 | 0.622867E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 711138.87 | 0.357012E+09 |
June | 0.482240E+09 | 0.614757E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8257685.53 | 0.203225E+09 |
July | 0.448971E+09 | 0.578076E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16826119.32 | 0.118131E+09 |
August | 0.502994E+09 | 0.648334E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14408111.49 | 0.139133E+09 |
September | 0.447140E+09 | 0.592756E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1090278.40 | 0.206813E+09 |
October | 0.465148E+09 | 0.633257E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454674E+09 |
November | 0.460569E+09 | 0.662768E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604798E+09 |
December | 0.448971E+09 | 0.656745E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114545E+10 |
Annual Sum or Average | 0.557719E+10 | 0.751201E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41636148.11 | 0.675141E+10 |
Minimum of Months | 0.421807E+09 | 0.578076E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118131E+09 |
Maximum of Months | 0.502994E+09 | 0.668092E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16826119.32 | 0.114545E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.103842E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165086E+10 |
February | 0.901968E+09 | 0.917132E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173796E+10 |
March | 0.107774E+10 | 0.105252E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375506.48 | 0.112306E+10 |
April | 0.956342E+09 | 0.925692E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898335E+09 |
May | 0.103597E+10 | 0.984286E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 232453.93 | 0.541134E+09 |
June | 0.103308E+10 | 0.971659E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10523542.69 | 0.305544E+09 |
July | 0.959235E+09 | 0.913839E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23230314.25 | 0.182258E+09 |
August | 0.107774E+10 | 0.102375E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18122983.86 | 0.217285E+09 |
September | 0.956342E+09 | 0.936131E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1333591.58 | 0.328204E+09 |
October | 0.994195E+09 | 0.996512E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719350E+09 |
November | 0.984487E+09 | 0.103756E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938642E+09 |
December | 0.959235E+09 | 0.102834E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175548E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118258E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53818392.80 | 0.103981E+11 |
Minimum of Months | 0.901968E+09 | 0.913839E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182258E+09 |
Maximum of Months | 0.107774E+10 | 0.105252E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23230314.25 | 0.175548E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.663306E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107557E+10 |
February | 0.570983E+09 | 0.582545E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114335E+10 |
March | 0.682256E+09 | 0.667573E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 461570.80 | 0.728773E+09 |
April | 0.605404E+09 | 0.585588E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592178E+09 |
May | 0.655811E+09 | 0.621472E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 233132.96 | 0.361686E+09 |
June | 0.653980E+09 | 0.613407E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8428612.27 | 0.210828E+09 |
July | 0.607235E+09 | 0.577202E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16882408.84 | 0.124987E+09 |
August | 0.682256E+09 | 0.646814E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13843486.87 | 0.145384E+09 |
September | 0.605404E+09 | 0.593354E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 924161.87 | 0.209058E+09 |
October | 0.629366E+09 | 0.635723E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451803E+09 |
November | 0.623221E+09 | 0.661738E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602445E+09 |
December | 0.607235E+09 | 0.656653E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114489E+10 |
Annual Sum or Average | 0.755252E+10 | 0.750538E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40773373.61 | 0.679095E+10 |
Minimum of Months | 0.570983E+09 | 0.577202E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124987E+09 |
Maximum of Months | 0.682256E+09 | 0.667573E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16882408.84 | 0.114489E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222145E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234535E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572933.34 | 0.149738E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121733E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567402.75 | 0.719377E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10285104.37 | 0.416590E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24545967.13 | 0.242773E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20902079.51 | 0.289621E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073272.62 | 0.441871E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974120E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130145E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239723E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57946759.71 | 0.140645E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242773E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24545967.13 | 0.239723E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274154E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289414E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815484.07 | 0.185057E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151026E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018950.48 | 0.907256E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13922258.95 | 0.530823E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31275520.28 | 0.309231E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27130112.38 | 0.366150E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1505763.51 | 0.545636E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116847E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155696E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292733E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75668089.69 | 0.173084E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309231E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31275520.28 | 0.292733E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280513E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298395E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35446.04 | 0.188040E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153992E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27392.60 | 0.963069E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7712571.19 | 0.567890E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23206301.62 | 0.337940E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16905485.36 | 0.383323E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742700.51 | 0.559518E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115802E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152982E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296478E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48629897.33 | 0.176737E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337940E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23206301.62 | 0.298395E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.33 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.35 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3666.82 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1173.03 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2009.61 | 01-MAR-22:02 |
April | 1306.65 | 03-APR-09:09 | 1046.43 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1819.48 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.25 | 14-MAY-15:10 | 1165.17 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.29 | 17-JUN-17:20 | 1042.32 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 750.89 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.48 | 13-AUG-12:55 | 476.79 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1139.64 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.96 | 16-SEP-17:20 | 811.22 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1467.00 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 968.17 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1783.24 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3359.71 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.79 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 408.48 | 3666.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.89 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 865.50 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-05:57 |
March | 827.22 | 01-MAR-10:09 | 678.23 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 15-MAR-14:00 | 1340.28 | 01-MAR-22:02 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1211.88 | 04-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.63 | 14-MAY-15:10 | 850.70 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.22 | 17-JUN-17:20 | 694.94 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 15-JUL-15:00 | 494.38 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.18 | 13-AUG-13:20 | 302.05 | 20-AUG-15:00 |
September | 827.22 | 01-SEP-09:09 | 654.53 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.76 | 16-SEP-17:20 | 532.42 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 873.19 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 675.34 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1175.40 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2221.56 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.05 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 303.18 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3589.38 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1336.04 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3754.71 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1148.57 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 15-MAR-14:00 | 2123.98 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 1039.59 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1819.03 | 04-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 | 14-MAY-15:10 | 1269.82 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.51 | 17-JUN-17:20 | 1048.47 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.94 | 15-JUL-15:00 | 750.85 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.07 | 13-AUG-12:38 | 495.31 | 20-AUG-15:00 |
September | 1306.65 | 01-SEP-09:09 | 1121.06 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.32 | 16-SEP-17:20 | 812.43 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1346.05 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1016.06 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1801.04 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3373.17 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.31 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 374.07 | 3754.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2392.89 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 856.43 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2503.13 | 13-FEB-05:57 |
March | 827.17 | 01-MAR-10:09 | 770.50 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 15-MAR-12:00 | 1438.14 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 696.04 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1211.39 | 04-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 | 14-MAY-15:10 | 897.64 | 29-MAY-15:20 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.94 | 18-JUN-11:20 | 698.91 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.48 | 16-JUL-11:40 | 504.19 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.01 | 13-AUG-12:55 | 370.64 | 27-AUG-17:00 |
September | 827.17 | 01-SEP-09:09 | 749.65 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 | 16-SEP-12:40 | 530.24 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 928.82 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 644.90 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1171.78 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2222.96 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.64 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 336.01 | 2503.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1904.56 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1351.90 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1992.56 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1158.05 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 14-MAR-14:00 | 1116.14 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 1026.13 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1071.58 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.62 | 14-MAY-15:00 | 568.88 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.19 | 17-JUN-17:03 | 574.35 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.28 | 21-JUL-03:00 | 421.00 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.11 | 13-AUG-12:55 | 271.94 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1123.36 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 | 16-SEP-17:02 | 510.02 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1464.67 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 637.55 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1095.38 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1883.90 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.94 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 247.11 | 1992.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.74 | 12-JAN-05:55 |
February | 827.22 | 01-FEB-10:09 | 862.55 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.37 | 13-FEB-05:53 |
March | 827.22 | 01-MAR-10:09 | 667.52 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | 14-MAR-14:00 | 763.59 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 715.39 | 16-APR-06:55 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.76 | 14-MAY-15:00 | 426.35 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.93 | 17-JUN-17:03 | 396.30 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.96 | 16-JUL-16:10 | 286.37 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.90 | 13-AUG-12:55 | 174.82 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 642.97 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 | 16-SEP-17:02 | 332.26 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 865.83 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 436.29 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 727.02 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1244.85 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.82 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 171.90 | 1328.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43625.10 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 1328.28 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 46679.55 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1132.21 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.21 | 15-MAR-12:00 | 44407.00 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 1018.93 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31557.85 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.52 | 10-MAY-16:10 | 22387.63 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6551.78 | 27-JUN-12:00 | 16166.15 | 06-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6726.61 | 19-JUL-16:10 | 10760.22 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6228.50 | 18-AUG-16:10 | 12232.55 | 01-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1103.78 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2569.17 | 15-SEP-12:00 | 19190.39 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1337.09 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29876.18 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 30039.50 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 47264.55 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10760.22 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6726.61 | 47264.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1269.74 | 12-JAN-05:55 |
February | 827.17 | 01-FEB-10:09 | 853.20 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.37 | 13-FEB-05:53 |
March | 827.17 | 01-MAR-10:09 | 764.33 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 15-MAR-12:00 | 772.53 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 687.43 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 708.75 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 | 14-MAY-15:00 | 428.06 | 29-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.73 | 18-JUN-11:23 | 400.74 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.29 | 16-JUL-11:30 | 293.25 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.06 | 13-AUG-12:55 | 187.40 | 27-AUG-18:43 |
September | 827.17 | 01-SEP-09:09 | 742.82 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 16-SEP-12:50 | 330.67 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 927.59 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 423.69 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 726.72 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1245.04 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.40 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 180.06 | 1328.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.82 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1358.34 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.24 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1173.01 | 17-MAR-07:10 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1756.84 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 1046.40 | 12-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1636.90 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.45 | 14-MAY-15:00 | 988.35 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.08 | 17-JUN-17:03 | 908.01 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 662.45 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.18 | 13-AUG-13:00 | 417.18 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1139.61 | 26-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 | 16-SEP-17:20 | 756.47 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1467.00 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 929.28 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1636.19 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2896.70 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.18 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 344.18 | 3122.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 952.10 | 02-JAN-16:49 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.87 | 12-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 865.49 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 678.22 | 17-MAR-07:10 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 | 15-MAR-14:00 | 1177.40 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1093.14 | 16-APR-06:55 |
May | 805.43 | 01-MAY-07:10 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 | 14-MAY-15:00 | 718.67 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.19 | 17-JUN-17:20 | 605.04 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.57 | 16-JUL-16:20 | 436.06 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.27 | 13-AUG-13:00 | 262.52 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 654.52 | 26-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 | 16-SEP-17:20 | 493.53 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 873.20 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 642.99 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1075.32 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 952.10 | 01-DEC-16:40 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1909.87 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.52 | |||||
Maximum of Months | 805.43 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 259.27 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:49 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2984.83 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 1336.03 | 01-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3122.53 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 1148.55 | 17-MAR-07:10 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 15-MAR-14:00 | 1891.54 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 1039.56 | 12-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1639.78 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 14-MAY-15:00 | 1075.74 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 | 17-JUN-17:20 | 913.40 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 15-JUL-15:00 | 662.97 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.56 | 13-AUG-12:38 | 407.82 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 1121.04 | 26-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.86 | 16-SEP-17:20 | 755.20 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 1346.06 | 30-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 968.83 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1649.53 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:40 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2906.18 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.82 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 307.56 | 3122.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:49 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1989.86 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 856.43 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2081.68 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 770.49 | 17-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 14-MAR-12:50 | 1227.69 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 696.02 | 12-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1080.11 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.78 | 14-MAY-15:20 | 758.98 | 29-MAY-15:20 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 | 18-JUN-11:20 | 609.23 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.93 | 16-JUL-11:40 | 445.03 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.46 | 13-AUG-12:55 | 301.20 | 27-AUG-16:30 |
September | 827.17 | 01-SEP-09:09 | 749.63 | 26-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 | 16-SEP-12:40 | 492.34 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 928.82 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 617.88 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1073.50 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:40 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1912.16 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.20 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 282.46 | 2081.68 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4004.10 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3924.36 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 15-MAR-14:00 | 2585.62 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2406.95 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.12 | 14-MAY-15:00 | 1208.73 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.28 | 17-JUN-17:03 | 1242.78 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.58 | 21-JUL-03:00 | 905.86 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.95 | 13-AUG-13:00 | 571.68 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 16-SEP-17:02 | 1089.99 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1348.33 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2400.04 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4034.34 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.95 | 4034.34 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4970.39 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4755.81 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.98 | 14-MAR-14:00 | 3215.32 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2931.05 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.64 | 14-MAY-15:00 | 1502.01 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.34 | 17-JUN-17:03 | 1590.41 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.39 | 21-JUL-03:00 | 1148.11 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.12 | 13-AUG-13:00 | 725.75 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.99 | 16-SEP-17:02 | 1327.91 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1595.43 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2921.83 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5027.02 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.12 | 5027.02 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4980.35 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5017.14 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 | 15-MAR-14:00 | 2974.27 | 25-MAR-17:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2756.09 | 16-APR-06:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 10-MAY-15:00 | 1999.01 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.86 | 17-JUN-17:03 | 1587.96 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.10 | 21-JUL-02:00 | 1122.51 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.14 | 13-AUG-13:00 | 738.68 | 20-AUG-15:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 16-SEP-13:00 | 1232.00 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1461.58 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2721.54 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5394.40 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.14 | 5394.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10137.44 | 20-JAN-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10449.53 | 17-FEB-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24989.07 | 16-MAR-05:03 | 2541.06 | 3170.73 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26871.34 | 25-APR-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42204.13 | 25-MAY-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45149.39 | 19-JUN-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45918.30 | 24-JUL-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45795.81 | 21-AUG-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46583.91 | 18-SEP-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42001.04 | 05-OCT-05:02 | 3176.32 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19966.18 | 01-NOV-07:04 | 42245.05 | 49937.79 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13201.20 | 01-DEC-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10137.44 | 0.00 | 3170.73 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46583.91 | 42245.05 | 49937.79 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 980.61 |
February | 426.23 | 18-FEB-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.77 |
March | 5724.45 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
April | 4674.16 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.48 |
May | 7280.76 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.17 |
June | 10891.47 | 27-JUN-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 |
July | 10749.98 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.38 | 0.00 |
August | 10674.09 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 | 0.00 |
September | 8393.31 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
October | 4513.90 | 11-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 |
November | 1371.61 | 04-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 |
December | 204.07 | 16-DEC-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10891.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.38 | 980.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2189.88 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.14 |
February | 2022.30 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.70 |
March | 1870.22 | 16-MAR-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.32 |
April | 1880.66 | 22-APR-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2402.54 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.32 |
June | 4534.83 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | 0.00 |
July | 5393.41 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.99 | 0.00 |
August | 4721.27 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 | 0.00 |
September | 3446.03 | 18-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.46 |
October | 2196.93 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.38 |
November | 1579.03 | 02-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.57 |
December | 1921.16 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1862.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1579.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5393.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | 1862.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1772.41 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.44 |
February | 2295.51 | 10-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.05 |
March | 2557.50 | 17-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.51 |
April | 2706.78 | 10-APR-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.46 |
May | 2811.31 | 30-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.45 |
June | 4637.30 | 12-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 0.00 |
July | 5789.52 | 17-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 0.00 |
August | 5068.69 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.60 | 0.00 |
September | 4542.25 | 18-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2447.33 | 23-OCT-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.03 |
November | 1890.65 | 07-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.38 |
December | 1470.11 | 08-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1470.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5789.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 386.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6413.51 | 12-JAN-16:50 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6540.64 | 17-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12734.00 | 16-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11911.01 | 21-APR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30839.92 | 24-MAY-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33544.56 | 19-JUN-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35500.23 | 17-JUL-04:03 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34212.31 | 07-AUG-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33970.90 | 18-SEP-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13477.62 | 12-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8810.95 | 01-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6876.13 | 01-DEC-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6413.51 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35500.23 | 6035.01 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6071.47 | 12-JAN-16:40 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6320.74 | 28-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13079.43 | 15-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12686.93 | 21-APR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16834.41 | 31-MAY-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33805.11 | 12-JUN-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39048.09 | 17-JUL-04:03 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36271.36 | 07-AUG-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26466.97 | 18-SEP-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13070.23 | 12-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7602.22 | 01-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6602.62 | 01-DEC-15:10 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6071.47 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39048.09 | 6035.01 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1309.50 | 14-JAN-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.82 |
February | 1301.45 | 18-FEB-17:03 | 267.84 | 262.53 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.77 |
March | 3926.93 | 15-MAR-14:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 | 0.00 |
April | 2557.97 | 21-APR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.35 |
May | 4931.81 | 23-MAY-14:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
June | 7554.16 | 27-JUN-15:47 | 3816.70 | 2781.47 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
July | 8278.80 | 17-JUL-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
August | 6986.11 | 14-AUG-04:02 | 0.00 | 1002.63 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.00 |
September | 4993.50 | 15-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
October | 2584.37 | 12-OCT-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.35 |
November | 1764.54 | 16-NOV-16:50 | 1272.23 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.24 |
December | 1402.40 | 01-DEC-13:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1301.45 | 0.00 | 262.53 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8278.80 | 3816.70 | 2781.47 | 4517.68 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 312.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1463.60 | 14-JAN-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.63 |
February | 1777.44 | 28-FEB-09:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.17 |
March | 2997.00 | 15-MAR-14:00 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 5230.52 | 24-APR-09:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.86 |
May | 7486.51 | 31-MAY-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.88 |
June | 10445.30 | 11-JUN-10:43 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 |
July | 13873.64 | 04-JUL-09:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.16 |
August | 8246.54 | 10-AUG-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 | 0.00 |
September | 6421.70 | 04-SEP-10:02 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.15 |
October | 3989.22 | 11-OCT-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.70 |
November | 2009.65 | 03-NOV-09:50 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.99 |
December | 1451.54 | 23-DEC-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1451.54 | 169.56 | 130.43 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13873.64 | 827.22 | 586.97 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 204.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3552.95 | 12-JAN-13:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 906.35 |
February | 6082.29 | 28-FEB-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
March | 10175.38 | 15-MAR-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | 0.00 |
April | 8148.71 | 21-APR-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 |
May | 11172.69 | 14-MAY-13:42 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.73 |
June | 10093.92 | 12-JUN-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 135.98 | 0.00 |
July | 12260.92 | 30-JUL-12:43 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.49 |
August | 17810.36 | 13-AUG-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 242.01 | 0.00 |
September | 18071.19 | 10-SEP-13:42 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.14 |
October | 12048.08 | 11-OCT-12:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 |
November | 7494.61 | 03-NOV-12:35 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 |
December | 3623.40 | 16-DEC-13:30 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3552.95 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18071.19 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 242.01 | 906.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1605.27 | 14-JAN-17:02 | 211.94 | 264.43 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 |
February | 2401.92 | 28-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.53 |
March | 3692.17 | 15-MAR-14:20 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
April | 6264.86 | 24-APR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
May | 11391.36 | 27-MAY-17:06 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.08 |
June | 16188.62 | 25-JUN-17:42 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 |
July | 15974.51 | 02-JUL-17:12 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 |
August | 15417.91 | 27-AUG-17:02 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.88 |
September | 15166.54 | 04-SEP-16:42 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 |
October | 6006.70 | 11-OCT-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
November | 2382.74 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 |
December | 1658.56 | 14-DEC-07:03 | 1017.32 | 1904.04 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1605.27 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16188.62 | 1017.32 | 1904.04 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 263.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1039.13 | 14-JAN-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.81 |
February | 1030.08 | 18-FEB-17:03 | 267.84 | 258.41 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.30 |
March | 1691.88 | 15-MAR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 0.00 |
April | 1549.75 | 21-APR-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
May | 2983.73 | 23-MAY-14:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4989.40 | 27-JUN-13:30 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 0.00 |
July | 5837.11 | 17-JUL-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
August | 5583.37 | 09-AUG-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 | 0.00 |
September | 4316.33 | 15-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 | 0.00 |
October | 2408.44 | 05-OCT-14:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 |
November | 1475.19 | 16-NOV-17:00 | 1272.23 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 |
December | 1267.48 | 01-DEC-13:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1030.08 | 267.84 | 258.41 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5837.11 | 1306.65 | 1503.90 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 | 167.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1213.16 | 14-JAN-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 |
February | 1342.32 | 28-FEB-09:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.29 |
March | 1906.99 | 15-MAR-14:10 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 0.00 |
April | 3643.49 | 24-APR-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
May | 4892.57 | 31-MAY-09:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.58 |
June | 6536.06 | 12-JUN-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 0.00 |
July | 11228.29 | 04-JUL-09:31 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.80 |
August | 6729.50 | 10-AUG-10:00 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | 0.00 |
September | 5362.17 | 18-SEP-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
October | 3506.65 | 11-OCT-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
November | 1823.43 | 03-NOV-08:35 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.11 |
December | 1345.36 | 01-DEC-07:05 | 678.26 | 1269.44 | 1694.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1213.16 | 211.95 | 228.24 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11228.29 | 1610.86 | 1269.44 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 117.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1710.00 | 21-JAN-12:30 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.22 |
February | 2001.61 | 18-FEB-14:40 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.31 |
March | 6240.73 | 15-MAR-13:40 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 317.04 | 0.00 |
April | 3395.58 | 22-APR-13:40 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
May | 4900.92 | 23-MAY-14:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 |
June | 11632.09 | 27-JUN-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6551.78 | 0.00 |
July | 11955.50 | 21-JUL-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6131.48 | 0.00 |
August | 11996.00 | 10-AUG-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6091.98 | 0.00 |
September | 13889.82 | 10-SEP-14:52 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.40 |
October | 9710.85 | 11-OCT-12:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.08 |
November | 2452.75 | 03-NOV-14:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2682.76 |
December | 2326.95 | 16-DEC-13:40 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1710.00 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13889.82 | 1306.65 | 927.16 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 6551.78 | 2682.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1410.79 | 12-JAN-16:10 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.78 |
February | 1754.82 | 28-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.12 |
March | 2034.67 | 15-MAR-14:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 0.00 |
April | 3755.80 | 24-APR-17:30 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
May | 5404.15 | 31-MAY-18:00 | 84.78 | 195.64 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 |
June | 12028.77 | 11-JUN-18:52 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 |
July | 11883.18 | 30-JUL-17:52 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.08 |
August | 9384.43 | 12-AUG-18:23 | 0.00 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 |
September | 10839.31 | 10-SEP-17:32 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 |
October | 4920.96 | 11-OCT-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
November | 1935.64 | 03-NOV-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 |
December | 1448.90 | 04-DEC-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1410.79 | 0.00 | 130.42 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12028.77 | 805.38 | 586.93 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 259.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1163.52 | 14-JAN-17:02 | 334.80 | 417.71 | 2509.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 |
February | 1165.78 | 17-FEB-15:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.18 |
March | 3504.52 | 15-MAR-14:50 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 0.00 |
April | 2477.88 | 21-APR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.32 |
May | 4698.34 | 23-MAY-14:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
June | 6288.31 | 12-JUN-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 0.00 |
July | 7196.00 | 17-JUL-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
August | 6785.36 | 15-AUG-05:02 | 669.60 | 835.52 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 |
September | 4757.24 | 15-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
October | 2783.36 | 12-OCT-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.93 |
November | 1674.15 | 16-NOV-17:00 | 1272.23 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.99 |
December | 1373.09 | 01-DEC-13:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1163.52 | 334.80 | 417.71 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7196.00 | 1306.65 | 1503.90 | 3346.43 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 258.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1445.17 | 14-JAN-17:02 | 211.95 | 264.45 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.41 |
February | 1901.11 | 28-FEB-09:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.27 |
March | 2832.07 | 14-MAR-10:20 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 |
April | 6000.97 | 24-APR-08:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.50 |
May | 7661.84 | 31-MAY-08:40 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
June | 11417.81 | 11-JUN-10:23 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 |
July | 13548.67 | 04-JUL-08:42 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.75 |
August | 13642.44 | 06-AUG-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.48 |
September | 7480.38 | 10-SEP-09:53 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.57 |
October | 4566.07 | 11-OCT-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
November | 2183.06 | 03-NOV-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.36 |
December | 1649.41 | 14-DEC-07:03 | 1017.38 | 1904.17 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1445.17 | 169.56 | 130.43 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | |
Maximum of Months | 13642.44 | 1017.38 | 1904.17 | 2542.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4549.32 | 12-JAN-13:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.85 |
February | 6323.23 | 28-FEB-13:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.91 |
March | 9629.39 | 15-MAR-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 | 0.00 |
April | 8086.44 | 24-APR-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.72 |
May | 7650.96 | 26-MAY-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
June | 9268.02 | 12-JUN-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 113.72 | 0.00 |
July | 15468.80 | 30-JUL-14:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.42 |
August | 16122.52 | 13-AUG-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 207.34 | 0.00 |
September | 15852.57 | 04-SEP-12:53 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.56 |
October | 12019.43 | 11-OCT-12:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.07 |
November | 8338.66 | 03-NOV-12:25 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.32 |
December | 4217.88 | 16-DEC-13:30 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4217.88 | 133.92 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16122.52 | 2544.47 | 1854.31 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 207.34 | 753.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1720.09 | 12-JAN-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.57 |
February | 2288.51 | 28-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.30 |
March | 3388.24 | 15-MAR-14:20 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 | 0.00 |
April | 6172.11 | 24-APR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 10414.58 | 27-MAY-17:06 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.52 |
June | 13957.53 | 10-JUN-18:22 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.63 |
July | 14650.43 | 02-JUL-17:12 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.16 |
August | 14228.80 | 06-AUG-16:31 | 296.72 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 0.00 |
September | 8232.84 | 21-SEP-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
October | 5871.39 | 11-OCT-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
November | 2335.41 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 |
December | 1718.66 | 14-DEC-07:03 | 1017.32 | 1904.04 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1718.66 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14650.43 | 1017.32 | 1904.04 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 414.57 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.197665E+12 | 257875.60 | 02-JAN-07:10 | 0.725496E+11 | 97826.14 | 04-JAN-08:09 |
February | 0.173416E+12 | 242345.59 | 06-FEB-07:10 | 0.669903E+11 | 112777.14 | 07-FEB-07:30 |
March | 0.150870E+12 | 191992.47 | 06-MAR-07:10 | 0.394966E+11 | 94408.14 | 07-MAR-07:30 |
April | 0.117906E+12 | 155736.50 | 17-APR-06:10 | 0.151835E+11 | 59827.36 | 17-APR-06:19 |
May | 0.121417E+12 | 116374.16 | 23-MAY-15:09 | 0.978681E+10 | 26696.25 | 01-MAY-06:19 |
June | 0.144892E+12 | 169450.45 | 27-JUN-15:20 | 0.913130E+10 | 9262.63 | 01-JUN-11:09 |
July | 0.165527E+12 | 172702.46 | 17-JUL-07:00 | 0.869862E+10 | 9139.25 | 06-JUL-11:09 |
August | 0.164846E+12 | 190327.12 | 15-AUG-14:30 | 0.910669E+10 | 9092.16 | 31-AUG-11:09 |
September | 0.129654E+12 | 144558.34 | 15-SEP-10:00 | 0.857457E+10 | 10318.55 | 30-SEP-06:30 |
October | 0.122221E+12 | 140804.79 | 30-OCT-06:10 | 0.118842E+11 | 52878.52 | 17-OCT-06:40 |
November | 0.135565E+12 | 170019.91 | 24-NOV-07:10 | 0.214534E+11 | 55510.02 | 24-NOV-07:00 |
December | 0.184094E+12 | 239953.82 | 11-DEC-07:10 | 0.628386E+11 | 108314.63 | 11-DEC-07:30 |
Annual Sum or Average | 0.180808E+13 | 0.335694E+12 | ||||
Minimum of Months | 0.117906E+12 | 116374.16 | 0.857457E+10 | 9092.16 | ||
Maximum of Months | 0.197665E+12 | 257875.60 | 0.725496E+11 | 112777.14 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.307210E+11 | 0.120670E+11 | 0.641572E+11 | 0.159088E+10 | 0.633713E+10 | 1312252.65 | 0.827908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275733E+11 | 0.993916E+10 | 0.580684E+11 | 0.143936E+10 | 0.569284E+10 | 1186778.30 | 0.707017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323753E+11 | 0.967909E+10 | 0.666107E+11 | 0.166686E+10 | 0.605328E+10 | 1343621.24 | 0.328543E+11 | 0.162892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287531E+11 | 0.802817E+10 | 0.619407E+11 | 0.153132E+10 | 0.570007E+10 | 1267813.82 | 0.113295E+11 | 0.622360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308741E+11 | 0.716437E+10 | 0.653840E+11 | 0.162821E+10 | 0.803369E+10 | 1327936.95 | 0.199537E+10 | 0.633593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306471E+11 | 0.642319E+10 | 0.641577E+11 | 0.160313E+10 | 0.133687E+11 | 1296568.36 | 0.417099E+09 | 0.282741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287303E+11 | 0.680874E+10 | 0.631525E+11 | 0.155593E+10 | 0.165788E+11 | 1299182.41 | 93098343.34 | 0.486068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320627E+11 | 0.776873E+10 | 0.666107E+11 | 0.166663E+10 | 0.160916E+11 | 1343621.24 | 0.211870E+09 | 0.404328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288646E+11 | 0.879028E+10 | 0.619118E+11 | 0.153082E+10 | 0.102107E+11 | 1267813.82 | 0.804763E+09 | 0.175403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302613E+11 | 0.104564E+11 | 0.641717E+11 | 0.159058E+10 | 0.617783E+10 | 1312252.65 | 0.748362E+10 | 0.207834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304550E+11 | 0.113103E+11 | 0.627379E+11 | 0.156214E+10 | 0.521545E+10 | 1278270.02 | 0.238846E+11 | 0.398402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299548E+11 | 0.123871E+11 | 0.631380E+11 | 0.155711E+10 | 0.592391E+10 | 1299182.41 | 0.711319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361273E+12 | 0.110823E+12 | 0.762041E+12 | 0.189230E+11 | 0.105384E+12 | 15535293.87 | 0.303699E+12 | 0.145918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.275733E+11 | 0.642319E+10 | 0.580684E+11 | 0.143936E+10 | 0.521545E+10 | 1186778.30 | 93098343.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.323753E+11 | 0.123871E+11 | 0.666107E+11 | 0.166686E+10 | 0.165788E+11 | 1343621.24 | 0.827908E+11 | 0.486068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.624850E+11 | 0.00 | 0.100646E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.577928E+11 | 0.00 | 0.919753E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.290044E+11 | 0.00 | 0.104921E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.571926E+10 | 0.00 | 0.946424E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.140654E+09 | 0.00 | 0.964616E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 402843.24 | 0.00 | 0.913090E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.869862E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.910669E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 23133489.66 | 0.00 | 0.855144E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.279556E+10 | 0.00 | 0.908862E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122378E+11 | 0.00 | 0.921552E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.531979E+11 | 0.00 | 0.964068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223397E+12 | 0.00 | 0.112297E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.855144E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.624850E+11 | 0.00 | 0.104921E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36137.71 | 02-JAN-16:49 | 8467.87 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 1358.60 | 02-JAN-16:00 | 7013.02 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 208123.63 | 02-JAN-07:10 |
February | 34562.34 | 01-FEB-16:00 | 8467.87 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 1357.29 | 01-FEB-08:20 | 6670.42 | 06-FEB-07:10 | 0.73 | 01-FEB-08:09 | 192936.22 | 06-FEB-07:10 |
March | 32664.64 | 17-MAR-07:10 | 8467.87 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 1353.46 | 17-MAR-07:19 | 8981.96 | 15-MAR-13:50 | 0.73 | 01-MAR-06:10 | 153917.43 | 06-MAR-06:10 |
April | 31459.36 | 12-APR-07:10 | 8467.87 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 1350.93 | 12-APR-07:19 | 8316.07 | 21-APR-15:30 | 0.73 | 03-APR-06:10 | 118647.08 | 17-APR-06:10 |
May | 30486.53 | 01-MAY-07:10 | 8467.87 | 01-MAY-05:10 | 47562.27 | 01-MAY-07:10 | 1348.89 | 01-MAY-07:19 | 14621.96 | 31-MAY-15:00 | 0.73 | 01-MAY-07:10 | 34390.65 | 01-MAY-06:10 |
June | 30486.53 | 01-JUN-07:10 | 8467.87 | 01-JUN-19:49 | 47562.27 | 01-JUN-07:10 | 1348.89 | 01-JUN-07:19 | 28234.88 | 27-JUN-15:20 | 0.73 | 01-JUN-05:10 | 15632.70 | 14-JUN-06:10 |
July | 30486.53 | 03-JUL-07:10 | 8467.87 | 01-JUL-19:00 | 47562.27 | 03-JUL-07:10 | 1348.89 | 03-JUL-07:30 | 30178.07 | 17-JUL-12:09 | 0.73 | 01-JUL-05:10 | 6869.77 | 13-JUL-06:19 |
August | 30486.53 | 01-AUG-07:10 | 8467.87 | 01-AUG-19:40 | 47562.27 | 01-AUG-07:10 | 1348.89 | 01-AUG-07:30 | 34590.83 | 15-AUG-14:30 | 0.73 | 01-AUG-05:10 | 10617.98 | 31-AUG-06:10 |
September | 32344.52 | 26-SEP-07:10 | 8467.87 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 1352.78 | 26-SEP-07:19 | 20894.22 | 21-SEP-15:00 | 0.73 | 01-SEP-05:10 | 26042.23 | 29-SEP-06:10 |
October | 35207.33 | 31-OCT-07:10 | 8467.87 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 1358.80 | 31-OCT-07:19 | 11417.92 | 11-OCT-15:50 | 0.73 | 16-OCT-07:10 | 93724.82 | 30-OCT-06:10 |
November | 36137.71 | 06-NOV-16:00 | 8467.87 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 1359.94 | 02-NOV-07:19 | 5550.97 | 03-NOV-12:39 | 0.73 | 02-NOV-07:10 | 122638.91 | 24-NOV-07:10 |
December | 36137.71 | 01-DEC-16:40 | 8467.87 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 1358.60 | 01-DEC-16:49 | 6604.64 | 11-DEC-07:10 | 0.73 | 04-DEC-06:10 | 190610.23 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30486.53 | 8467.87 | 47562.27 | 1348.89 | 5550.97 | 0.73 | 6869.77 | |||||||
Maximum of Months | 36137.71 | 8467.87 | 47562.27 | 1359.94 | 34590.83 | 0.73 | 208123.63 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26329.70 | 15-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11593.91 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29499.20 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65611.59 | 27-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73008.14 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81617.07 | 15-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53948.46 | 15-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20748.32 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9190.46 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81617.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 257875.60 | 02-JAN-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7013.02 | 0.73 | 208123.63 | 0.00 | 0.00 |
February | 242345.59 | 06-FEB-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 6670.42 | 0.73 | 192936.22 | 0.00 | 0.00 |
March | 191992.47 | 06-MAR-07:10 | 10642.03 | 21853.28 | 0.00 | 371.09 | 5257.36 | 0.73 | 153867.99 | 0.00 | 0.00 |
April | 155736.50 | 17-APR-06:10 | 10270.22 | 21853.28 | 0.00 | 370.97 | 4594.23 | 0.73 | 118647.08 | 0.00 | 0.00 |
May | 116374.16 | 23-MAY-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 13702.42 | 0.73 | 0.00 | 27067.75 | 0.00 |
June | 169450.45 | 27-JUN-15:20 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 28234.88 | 0.73 | 0.00 | 65611.59 | 0.00 |
July | 172702.46 | 17-JUL-07:00 | 30486.53 | 47562.27 | 0.00 | 1348.89 | 21663.26 | 0.73 | 0.00 | 71640.78 | 0.00 |
August | 190327.12 | 15-AUG-14:30 | 30486.53 | 42286.04 | 0.00 | 1345.91 | 34590.83 | 0.73 | 0.00 | 81617.07 | 0.00 |
September | 144558.34 | 15-SEP-10:00 | 30486.53 | 43275.33 | 0.00 | 1346.47 | 16394.05 | 0.73 | 0.00 | 53055.23 | 0.00 |
October | 140804.79 | 30-OCT-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4341.02 | 0.73 | 93724.82 | 0.00 | 0.00 |
November | 170019.91 | 24-NOV-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4642.05 | 0.73 | 122638.91 | 0.00 | 0.00 |
December | 239953.82 | 11-DEC-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 6604.64 | 0.73 | 190610.23 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 116374.16 | 10270.22 | 21853.28 | 0.00 | 370.97 | 4341.02 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 257875.60 | 30486.53 | 47562.27 | 8467.87 | 1348.89 | 34590.83 | 0.73 | 208123.63 | 81617.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 89683.47 | 04-JAN-07:00 | 0.00 | 10269.46 | 24-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 105930.98 | 07-FEB-07:19 | 0.00 | 10482.27 | 06-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 87055.19 | 07-MAR-07:19 | 0.00 | 10124.30 | 13-MAR-11:00 | 0.00 |
April | 0.00 | 0.00 | 51642.19 | 17-APR-06:19 | 0.00 | 9513.03 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 20285.02 | 01-MAY-06:10 | 0.00 | 9395.58 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 671.41 | 14-JUN-06:10 | 0.00 | 9262.63 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9139.25 | 06-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9092.16 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 2964.27 | 30-SEP-06:10 | 0.00 | 9139.81 | 27-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 44803.78 | 17-OCT-06:19 | 0.00 | 9263.96 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 48717.32 | 24-NOV-07:30 | 0.00 | 9399.07 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 100760.23 | 11-DEC-07:19 | 0.00 | 9522.85 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9092.16 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 105930.98 | 0.00 | 10482.27 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.25 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.25 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.25 | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.23 | 1.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.50 | 19.36 | 0.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.34 | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 2.33 | 19.28 | 2.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.36 | 1.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 17.79 | 0.83 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
February | 1.50 | 18.54 | 1.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
March | 0.17 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.65 | 0.67 | 24.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 18.31 | 0.83 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
Annual Sum or Average | 4.83 | 18.22 | 2.83 | 18.57 | 0.67 | 19.06 | 0.67 | 19.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.33 | 1.00 | 19.33 | 0.67 | 24.65 | 0.67 | 24.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.50 | 16.08 | 19.83 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
February | 46.33 | 16.13 | 18.50 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
March | 10.50 | 16.61 | 4.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
April | 0.50 | 17.05 | 0.17 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.85 | 0.67 | 24.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.35 | 1.00 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
November | 1.00 | 17.24 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
December | 36.50 | 16.02 | 15.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 141.50 | 16.13 | 58.17 | 16.55 | 1.67 | 16.63 | 1.67 | 16.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.50 | 17.24 | 19.83 | 17.55 | 1.00 | 27.35 | 1.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.50 | 15.04 | 6.67 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
February | 30.50 | 14.83 | 4.33 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
March | 7.00 | 15.40 | 0.33 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
April | 0.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.65 | 1.17 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.89 | 4.50 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.76 | 1.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
November | 1.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
December | 27.83 | 14.99 | 6.83 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
Annual Sum or Average | 100.33 | 15.01 | 18.17 | 15.04 | 6.67 | 15.72 | 6.67 | 16.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.50 | 16.90 | 6.83 | 16.90 | 4.50 | 27.89 | 4.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.50 | 15.22 | 4.83 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
February | 26.33 | 15.08 | 4.33 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
March | 4.67 | 16.13 | 0.67 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
April | 0.33 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.35 | 1.33 | 26.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.62 | 4.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.73 | 2.50 | 27.73 |
October | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
November | 0.67 | 17.40 | 0.17 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
December | 21.83 | 15.29 | 4.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
Annual Sum or Average | 81.50 | 15.27 | 14.00 | 15.42 | 11.17 | 16.69 | 11.17 | 17.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.50 | 17.40 | 4.83 | 17.80 | 4.00 | 27.76 | 4.00 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.17 | 14.99 | 8.83 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
February | 30.83 | 14.80 | 5.67 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
March | 6.33 | 15.48 | 0.83 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
April | 0.33 | 16.15 | 0.00 | 16.15 | 0.33 | 21.71 | 0.17 | 22.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.76 | 0.50 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.66 | 3.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.34 | 2.67 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.04 | 2.17 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.00 | 27.55 |
October | 0.17 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
November | 1.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
December | 27.17 | 14.93 | 5.83 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
Annual Sum or Average | 101.00 | 14.98 | 21.17 | 14.98 | 17.00 | 16.56 | 10.00 | 17.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 | 14.82 |
Maximum of Months | 35.17 | 16.94 | 8.83 | 16.94 | 5.83 | 28.34 | 3.50 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 18.13 | 8.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
February | 13.17 | 18.32 | 8.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 2.50 | 19.23 | 2.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
April | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.17 | 19.00 | 4.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 34.17 | 18.42 | 23.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 19.38 | 8.67 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.87 | 0.33 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 4.17 | 15.85 | 0.17 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
March | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.67 | 1.67 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Annual Sum or Average | 12.33 | 15.94 | 0.50 | 16.07 | 2.17 | 17.74 | 2.17 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 16.97 | 0.33 | 16.97 | 1.67 | 27.67 | 1.67 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.00 | 16.04 | 107.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 97.67 | 15.94 | 95.17 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
March | 65.83 | 17.19 | 65.83 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
April | 41.33 | 18.40 | 41.33 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
May | 12.67 | 19.32 | 12.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
June | 2.33 | 20.05 | 2.33 | 20.05 | 0.00 | 20.05 | 0.00 | 20.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.79 | 0.83 | 24.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.31 | 2.33 | 26.31 |
September | 3.00 | 20.26 | 3.00 | 20.26 | 1.83 | 21.97 | 1.83 | 23.04 |
October | 22.67 | 18.85 | 22.67 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
November | 52.33 | 18.20 | 52.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
December | 90.00 | 16.08 | 89.00 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
Annual Sum or Average | 498.83 | 16.86 | 491.33 | 16.86 | 5.00 | 16.91 | 5.00 | 16.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 | 15.94 |
Maximum of Months | 111.00 | 20.26 | 107.00 | 20.26 | 2.33 | 26.31 | 2.33 | 26.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.85 | 0.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 4.33 | 15.78 | 0.17 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
March | 0.33 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.60 | 0.83 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.90 | 1.17 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.00 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.62 | 0.17 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
Annual Sum or Average | 12.50 | 15.91 | 0.50 | 16.04 | 8.00 | 20.49 | 3.17 | 21.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 17.02 | 0.33 | 17.02 | 3.33 | 27.90 | 1.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.00 | 16.71 | 5.00 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
February | 17.83 | 16.93 | 6.67 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
March | 1.17 | 18.42 | 0.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.50 | 16.85 | 4.50 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
Annual Sum or Average | 47.50 | 16.87 | 16.83 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.83 | 18.42 | 6.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 15.49 | 0.67 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
February | 10.33 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
March | 0.33 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.67 | 1.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.95 | 3.50 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.71 | 1.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.33 | 15.34 | 0.17 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
Annual Sum or Average | 30.50 | 15.35 | 0.83 | 15.41 | 6.67 | 17.58 | 6.67 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.50 | 16.77 | 0.67 | 16.77 | 3.50 | 27.95 | 3.50 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 15.75 | 0.33 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
February | 9.17 | 15.42 | 0.33 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
March | 0.33 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.54 | 2.17 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.71 | 2.67 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.79 | 2.67 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.00 | 15.79 | 0.50 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Annual Sum or Average | 23.33 | 15.65 | 1.17 | 15.82 | 8.00 | 18.74 | 8.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 16.99 | 0.50 | 16.99 | 2.67 | 27.79 | 2.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 15.43 | 1.00 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
February | 10.00 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
March | 0.33 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.82 | 0.50 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.08 | 2.17 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.23 | 2.33 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.92 | 1.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.73 | 0.67 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.33 | 15.33 | 0.67 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
Annual Sum or Average | 31.17 | 15.33 | 1.67 | 15.38 | 14.00 | 19.17 | 7.67 | 20.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 16.85 | 1.00 | 16.85 | 4.83 | 28.23 | 2.33 | 28.21 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.21 | 73.00 | 21.96 | 73.00 | 21.78 |
February | 454.00 | 22.44 | 30.67 | 22.34 | 30.67 | 22.26 |
March | 445.17 | 23.36 | 18.83 | 23.38 | 2.33 | 23.37 |
April | 318.50 | 23.66 | 12.17 | 23.72 | 0.00 | 23.72 |
May | 102.33 | 23.88 | 161.00 | 24.51 | 0.00 | 24.51 |
June | 0.33 | 23.97 | 356.17 | 24.46 | 0.00 | 24.46 |
July | 0.00 | 0.00 | 488.00 | 24.44 | 0.00 | 24.44 |
August | 0.00 | 0.00 | 488.00 | 24.39 | 0.00 | 24.39 |
September | 9.00 | 23.73 | 342.50 | 24.49 | 0.00 | 24.49 |
October | 179.33 | 23.79 | 75.67 | 24.07 | 0.00 | 24.07 |
November | 425.00 | 23.66 | 2.83 | 23.67 | 0.00 | 23.67 |
December | 489.83 | 22.73 | 16.83 | 22.67 | 16.83 | 22.61 |
Annual Sum or Average | 2925.50 | 23.04 | 2065.67 | 23.54 | 122.83 | 23.47 |
Minimum of Months | 0.00 | 0.00 | 2.83 | 21.96 | 0.00 | 21.78 |
Maximum of Months | 502.00 | 23.97 | 488.00 | 24.51 | 73.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.92 | 326.50 | 20.76 | 326.50 | 20.69 |
February | 454.00 | 21.09 | 256.50 | 20.92 | 256.50 | 20.84 |
March | 477.50 | 22.07 | 77.50 | 21.94 | 70.17 | 21.81 |
April | 455.33 | 22.96 | 3.17 | 22.94 | 3.17 | 22.93 |
May | 239.00 | 23.56 | 65.50 | 23.76 | 0.00 | 23.76 |
June | 38.00 | 23.77 | 283.50 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 472.50 | 24.31 | 0.00 | 24.31 |
August | 0.17 | 23.59 | 433.50 | 24.31 | 0.00 | 24.31 |
September | 69.33 | 23.42 | 226.50 | 24.16 | 0.00 | 24.16 |
October | 390.67 | 23.01 | 10.67 | 23.04 | 0.00 | 23.04 |
November | 488.50 | 22.34 | 10.00 | 22.31 | 10.00 | 22.27 |
December | 497.00 | 21.15 | 248.67 | 20.97 | 248.67 | 20.88 |
Annual Sum or Average | 3611.50 | 22.05 | 2414.50 | 22.40 | 915.00 | 22.16 |
Minimum of Months | 0.00 | 0.00 | 3.17 | 20.76 | 0.00 | 20.69 |
Maximum of Months | 502.00 | 23.77 | 472.50 | 24.31 | 326.50 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 431.67 | 20.33 | 431.67 | 20.30 |
February | 454.00 | 20.54 | 359.83 | 20.42 | 359.83 | 20.37 |
March | 486.33 | 21.43 | 190.33 | 21.19 | 184.83 | 21.04 |
April | 471.67 | 22.34 | 40.83 | 22.17 | 40.83 | 22.03 |
May | 304.00 | 23.28 | 50.00 | 23.42 | 0.00 | 23.42 |
June | 75.00 | 23.54 | 263.50 | 24.08 | 0.67 | 24.08 |
July | 4.33 | 23.55 | 456.00 | 24.30 | 0.00 | 24.30 |
August | 16.83 | 23.40 | 399.67 | 24.23 | 0.00 | 24.23 |
September | 161.17 | 23.15 | 165.83 | 23.73 | 0.00 | 23.73 |
October | 454.50 | 22.25 | 41.33 | 22.12 | 37.67 | 22.00 |
November | 489.00 | 21.42 | 134.00 | 21.19 | 134.00 | 21.04 |
December | 497.00 | 20.51 | 380.00 | 20.39 | 380.00 | 20.35 |
Annual Sum or Average | 3915.83 | 21.55 | 2913.00 | 21.80 | 1569.50 | 21.51 |
Minimum of Months | 4.33 | 20.41 | 40.83 | 20.33 | 0.00 | 20.30 |
Maximum of Months | 502.00 | 23.55 | 456.00 | 24.30 | 431.67 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 494.17 | 19.78 | 494.17 | 19.77 |
February | 454.00 | 19.84 | 451.33 | 19.83 | 451.33 | 19.83 |
March | 497.67 | 20.56 | 341.17 | 20.40 | 331.83 | 20.30 |
April | 478.83 | 21.30 | 146.83 | 21.00 | 146.83 | 20.82 |
May | 365.67 | 22.54 | 57.50 | 22.66 | 11.67 | 22.60 |
June | 118.83 | 23.24 | 261.00 | 23.91 | 11.50 | 23.95 |
July | 50.83 | 24.68 | 442.17 | 24.37 | 34.00 | 24.43 |
August | 84.17 | 23.19 | 360.67 | 24.03 | 8.83 | 24.06 |
September | 283.50 | 22.67 | 131.67 | 23.15 | 14.50 | 23.21 |
October | 487.83 | 21.22 | 136.50 | 20.95 | 134.00 | 20.76 |
November | 489.00 | 20.42 | 317.00 | 20.27 | 317.00 | 20.20 |
December | 497.00 | 19.79 | 479.33 | 19.76 | 479.33 | 19.76 |
Annual Sum or Average | 4309.33 | 20.93 | 3619.33 | 21.14 | 2435.00 | 20.88 |
Minimum of Months | 50.83 | 19.79 | 57.50 | 19.76 | 8.83 | 19.76 |
Maximum of Months | 502.00 | 24.68 | 494.17 | 24.37 | 494.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 494.50 | 19.83 | 494.50 | 19.82 |
February | 454.00 | 19.90 | 438.00 | 19.87 | 438.00 | 19.87 |
March | 495.50 | 20.62 | 292.83 | 20.46 | 280.17 | 20.34 |
April | 426.00 | 21.26 | 120.50 | 21.08 | 105.17 | 20.87 |
May | 308.50 | 22.22 | 127.50 | 22.77 | 10.67 | 22.72 |
June | 127.83 | 23.02 | 305.17 | 23.90 | 13.17 | 23.97 |
July | 69.67 | 24.92 | 430.83 | 24.43 | 44.67 | 24.57 |
August | 103.83 | 22.96 | 363.17 | 23.95 | 11.33 | 24.00 |
September | 240.00 | 22.30 | 200.67 | 23.17 | 14.00 | 23.22 |
October | 475.67 | 21.24 | 109.00 | 21.03 | 103.50 | 20.85 |
November | 489.00 | 20.49 | 303.67 | 20.33 | 303.67 | 20.26 |
December | 497.00 | 19.84 | 480.33 | 19.82 | 480.33 | 19.81 |
Annual Sum or Average | 4189.00 | 20.89 | 3666.17 | 21.24 | 2299.17 | 20.98 |
Minimum of Months | 69.67 | 19.83 | 109.00 | 19.82 | 10.67 | 19.81 |
Maximum of Months | 502.00 | 24.92 | 494.50 | 24.43 | 494.50 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 439.67 | 19.97 | 439.67 | 19.93 |
February | 449.67 | 20.10 | 378.17 | 19.95 | 378.17 | 19.89 |
March | 468.67 | 21.03 | 242.67 | 20.79 | 227.33 | 20.62 |
April | 401.50 | 21.29 | 144.17 | 21.22 | 114.50 | 21.01 |
May | 323.17 | 22.25 | 113.67 | 22.66 | 16.83 | 22.59 |
June | 159.17 | 22.91 | 268.67 | 23.74 | 14.00 | 23.80 |
July | 89.83 | 24.34 | 409.17 | 24.36 | 45.83 | 24.49 |
August | 115.33 | 23.24 | 364.67 | 24.04 | 18.67 | 24.12 |
September | 224.33 | 22.64 | 227.00 | 23.50 | 21.17 | 23.60 |
October | 404.50 | 21.42 | 144.50 | 21.48 | 88.00 | 21.26 |
November | 470.33 | 20.82 | 244.00 | 20.58 | 241.17 | 20.46 |
December | 495.33 | 20.06 | 442.50 | 19.97 | 442.50 | 19.94 |
Annual Sum or Average | 4103.83 | 21.13 | 3418.83 | 21.44 | 2047.83 | 21.17 |
Minimum of Months | 89.83 | 20.06 | 113.67 | 19.95 | 14.00 | 19.89 |
Maximum of Months | 502.00 | 24.34 | 442.50 | 24.36 | 442.50 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 491.50 | 19.83 | 491.50 | 19.82 |
February | 454.00 | 19.91 | 431.00 | 19.88 | 431.00 | 19.86 |
March | 502.83 | 20.71 | 289.00 | 20.50 | 283.17 | 20.39 |
April | 431.33 | 21.07 | 162.33 | 21.03 | 132.17 | 20.85 |
May | 362.83 | 22.02 | 113.50 | 22.45 | 19.83 | 22.40 |
June | 184.83 | 22.82 | 272.00 | 23.67 | 20.67 | 23.77 |
July | 106.00 | 23.71 | 389.67 | 24.18 | 39.17 | 24.30 |
August | 148.33 | 22.78 | 321.67 | 23.79 | 16.17 | 23.87 |
September | 312.50 | 22.23 | 149.33 | 22.88 | 17.17 | 22.96 |
October | 472.83 | 21.04 | 140.17 | 20.88 | 126.00 | 20.71 |
November | 489.00 | 20.45 | 303.00 | 20.29 | 303.00 | 20.22 |
December | 497.00 | 19.82 | 475.67 | 19.80 | 475.67 | 19.79 |
Annual Sum or Average | 4463.50 | 20.91 | 3538.83 | 21.16 | 2355.50 | 20.93 |
Minimum of Months | 106.00 | 19.82 | 113.50 | 19.80 | 16.17 | 19.79 |
Maximum of Months | 502.83 | 23.71 | 491.50 | 24.18 | 491.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 494.00 | 20.05 | 494.00 | 20.05 |
February | 454.00 | 20.14 | 454.00 | 20.14 | 454.00 | 20.14 |
March | 512.00 | 20.79 | 340.00 | 20.62 | 340.00 | 20.55 |
April | 485.00 | 21.34 | 127.17 | 21.14 | 127.17 | 21.01 |
May | 443.33 | 22.67 | 14.50 | 22.68 | 4.17 | 22.66 |
June | 131.33 | 23.54 | 221.67 | 23.95 | 7.83 | 23.98 |
July | 27.33 | 24.83 | 450.00 | 24.33 | 22.67 | 24.36 |
August | 39.50 | 23.63 | 383.50 | 24.19 | 6.83 | 24.20 |
September | 200.67 | 23.32 | 151.33 | 23.72 | 10.67 | 23.78 |
October | 467.17 | 22.16 | 25.67 | 22.10 | 23.50 | 22.03 |
November | 489.00 | 21.09 | 173.00 | 20.93 | 173.00 | 20.83 |
December | 497.00 | 20.24 | 460.17 | 20.21 | 460.17 | 20.19 |
Annual Sum or Average | 4248.33 | 21.27 | 3295.00 | 21.46 | 2124.00 | 21.21 |
Minimum of Months | 27.33 | 20.06 | 14.50 | 20.05 | 4.17 | 20.05 |
Maximum of Months | 512.00 | 24.83 | 494.00 | 24.33 | 494.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 494.33 | 20.13 | 494.33 | 20.12 |
February | 454.00 | 20.21 | 445.50 | 20.20 | 445.50 | 20.20 |
March | 512.17 | 20.88 | 282.67 | 20.71 | 282.67 | 20.63 |
April | 452.83 | 21.56 | 75.00 | 21.39 | 72.00 | 21.25 |
May | 348.83 | 22.48 | 74.33 | 22.85 | 1.67 | 22.84 |
June | 105.83 | 23.20 | 291.67 | 24.03 | 6.50 | 24.06 |
July | 34.83 | 25.55 | 463.50 | 24.45 | 28.33 | 24.54 |
August | 52.83 | 23.44 | 408.17 | 24.20 | 8.33 | 24.23 |
September | 160.67 | 22.92 | 251.17 | 23.78 | 10.00 | 23.83 |
October | 433.67 | 22.00 | 32.00 | 22.02 | 17.67 | 21.96 |
November | 489.00 | 21.05 | 150.83 | 20.91 | 150.83 | 20.83 |
December | 497.00 | 20.27 | 465.83 | 20.25 | 465.83 | 20.24 |
Annual Sum or Average | 4043.67 | 21.21 | 3435.00 | 21.59 | 1983.67 | 21.34 |
Minimum of Months | 34.83 | 20.13 | 32.00 | 20.13 | 1.67 | 20.12 |
Maximum of Months | 512.17 | 25.55 | 494.33 | 24.45 | 494.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.27 | 472.17 | 19.20 | 472.17 | 19.18 |
February | 454.00 | 19.27 | 425.67 | 19.21 | 425.67 | 19.19 |
March | 501.50 | 20.48 | 263.33 | 20.22 | 255.33 | 20.07 |
April | 460.67 | 21.05 | 122.33 | 20.86 | 112.67 | 20.66 |
May | 429.00 | 21.99 | 51.50 | 22.12 | 16.83 | 22.04 |
June | 238.17 | 22.72 | 207.83 | 23.41 | 35.17 | 23.43 |
July | 112.17 | 23.69 | 423.50 | 24.21 | 75.33 | 24.23 |
August | 118.00 | 23.13 | 393.17 | 24.05 | 49.67 | 24.07 |
September | 164.17 | 22.78 | 267.00 | 23.82 | 27.50 | 23.90 |
October | 400.67 | 21.70 | 85.67 | 21.94 | 24.50 | 21.80 |
November | 477.67 | 20.96 | 154.67 | 20.66 | 154.67 | 20.48 |
December | 497.00 | 19.61 | 444.50 | 19.50 | 444.50 | 19.46 |
Annual Sum or Average | 4355.00 | 20.85 | 3311.33 | 21.12 | 2094.00 | 20.84 |
Minimum of Months | 112.17 | 19.27 | 51.50 | 19.20 | 16.83 | 19.18 |
Maximum of Months | 502.00 | 23.69 | 472.17 | 24.21 | 472.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 491.67 | 20.09 | 491.67 | 20.09 |
February | 454.00 | 20.20 | 440.50 | 20.18 | 440.50 | 20.18 |
March | 511.83 | 20.89 | 277.00 | 20.72 | 277.00 | 20.64 |
April | 455.17 | 21.37 | 96.83 | 21.22 | 92.00 | 21.09 |
May | 386.33 | 22.32 | 64.67 | 22.64 | 2.67 | 22.62 |
June | 125.17 | 23.10 | 280.17 | 23.94 | 9.33 | 23.98 |
July | 51.00 | 24.53 | 435.50 | 24.38 | 28.00 | 24.45 |
August | 72.33 | 23.45 | 398.83 | 24.18 | 12.50 | 24.23 |
September | 203.83 | 22.91 | 192.67 | 23.62 | 10.67 | 23.69 |
October | 461.00 | 21.84 | 39.17 | 21.84 | 24.83 | 21.78 |
November | 489.00 | 20.99 | 167.50 | 20.86 | 167.50 | 20.79 |
December | 497.00 | 20.26 | 463.33 | 20.23 | 463.33 | 20.22 |
Annual Sum or Average | 4208.67 | 21.20 | 3347.83 | 21.53 | 2020.00 | 21.29 |
Minimum of Months | 51.00 | 20.10 | 39.17 | 20.09 | 2.67 | 20.09 |
Maximum of Months | 511.83 | 24.53 | 491.67 | 24.38 | 491.67 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 487.67 | 19.97 | 487.67 | 19.97 |
February | 454.00 | 20.07 | 435.67 | 20.05 | 435.67 | 20.04 |
March | 494.33 | 20.89 | 287.17 | 20.72 | 276.50 | 20.61 |
April | 477.33 | 21.80 | 70.50 | 21.58 | 70.50 | 21.41 |
May | 330.17 | 23.02 | 56.33 | 23.20 | 0.00 | 23.20 |
June | 72.17 | 23.68 | 276.83 | 24.13 | 7.17 | 24.15 |
July | 29.83 | 25.41 | 466.50 | 24.42 | 28.83 | 24.48 |
August | 36.67 | 23.50 | 405.17 | 24.21 | 4.67 | 24.21 |
September | 207.00 | 23.15 | 162.50 | 23.63 | 11.83 | 23.70 |
October | 468.67 | 21.83 | 67.33 | 21.68 | 62.00 | 21.54 |
November | 489.00 | 20.88 | 208.33 | 20.69 | 208.33 | 20.59 |
December | 497.00 | 20.07 | 454.67 | 20.02 | 454.67 | 20.01 |
Annual Sum or Average | 4058.17 | 21.19 | 3378.67 | 21.47 | 2047.83 | 21.20 |
Minimum of Months | 29.83 | 19.99 | 56.33 | 19.97 | 0.00 | 19.97 |
Maximum of Months | 502.00 | 25.41 | 487.67 | 24.42 | 487.67 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.87 | 419.00 | 19.86 | 419.00 | 19.86 |
February | 385.00 | 19.98 | 365.67 | 19.95 | 365.67 | 19.94 |
March | 420.83 | 20.85 | 213.83 | 20.68 | 208.50 | 20.57 |
April | 363.50 | 21.49 | 75.00 | 21.44 | 57.00 | 21.27 |
May | 268.83 | 22.46 | 90.00 | 23.01 | 1.83 | 23.01 |
June | 104.50 | 23.22 | 247.17 | 24.01 | 11.00 | 24.08 |
July | 52.33 | 25.27 | 368.17 | 24.52 | 36.83 | 24.66 |
August | 79.17 | 23.11 | 304.17 | 24.06 | 7.67 | 24.11 |
September | 201.33 | 22.68 | 159.50 | 23.44 | 14.00 | 23.53 |
October | 392.50 | 21.56 | 57.00 | 21.47 | 49.83 | 21.34 |
November | 417.00 | 20.79 | 188.17 | 20.62 | 188.17 | 20.53 |
December | 422.00 | 19.94 | 397.33 | 19.91 | 397.33 | 19.90 |
Annual Sum or Average | 3534.00 | 21.08 | 2885.00 | 21.41 | 1756.83 | 21.16 |
Minimum of Months | 52.33 | 19.87 | 57.00 | 19.86 | 1.83 | 19.86 |
Maximum of Months | 427.00 | 25.27 | 419.00 | 24.52 | 419.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 20.36 | 409.33 | 20.21 | 408.50 | 20.16 |
February | 449.00 | 20.43 | 349.00 | 20.24 | 349.00 | 20.17 |
March | 452.33 | 21.37 | 178.50 | 21.17 | 161.17 | 21.00 |
April | 390.50 | 21.73 | 82.17 | 21.74 | 54.00 | 21.58 |
May | 279.33 | 22.61 | 103.67 | 23.11 | 0.83 | 23.12 |
June | 113.83 | 23.21 | 287.33 | 23.95 | 8.50 | 23.99 |
July | 58.83 | 24.93 | 442.50 | 24.44 | 38.00 | 24.55 |
August | 75.50 | 23.75 | 398.00 | 24.23 | 16.33 | 24.31 |
September | 173.67 | 23.17 | 258.83 | 23.91 | 20.83 | 24.03 |
October | 367.67 | 21.91 | 107.33 | 22.18 | 34.17 | 22.05 |
November | 455.00 | 21.23 | 151.17 | 21.03 | 145.67 | 20.89 |
December | 493.50 | 20.39 | 397.17 | 20.26 | 397.17 | 20.21 |
Annual Sum or Average | 3805.83 | 21.40 | 3165.00 | 21.80 | 1634.17 | 21.54 |
Minimum of Months | 58.83 | 20.36 | 82.17 | 20.21 | 0.83 | 20.16 |
Maximum of Months | 496.67 | 24.93 | 442.50 | 24.44 | 408.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 484.83 | 20.00 | 484.83 | 20.00 |
February | 454.00 | 20.13 | 416.83 | 20.08 | 416.83 | 20.06 |
March | 498.33 | 20.99 | 235.50 | 20.80 | 230.67 | 20.68 |
April | 427.33 | 21.42 | 98.50 | 21.44 | 68.67 | 21.29 |
May | 331.67 | 22.36 | 105.17 | 22.87 | 2.50 | 22.88 |
June | 141.50 | 23.13 | 290.83 | 23.91 | 17.17 | 24.00 |
July | 68.50 | 24.30 | 414.50 | 24.32 | 32.83 | 24.43 |
August | 109.00 | 23.17 | 358.17 | 24.02 | 14.17 | 24.10 |
September | 266.67 | 22.63 | 167.00 | 23.30 | 14.50 | 23.39 |
October | 463.00 | 21.49 | 75.00 | 21.45 | 56.83 | 21.33 |
November | 489.00 | 20.82 | 205.00 | 20.65 | 205.00 | 20.56 |
December | 497.00 | 20.09 | 457.00 | 20.05 | 457.00 | 20.03 |
Annual Sum or Average | 4248.00 | 21.15 | 3308.33 | 21.46 | 2001.00 | 21.22 |
Minimum of Months | 68.50 | 20.02 | 75.00 | 20.00 | 2.50 | 20.00 |
Maximum of Months | 502.00 | 24.30 | 484.83 | 24.32 | 484.83 | 24.43 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20591 | 18.81746 | -0.3186 | 8.70700 |
February | 454.00000 | 22.43759 | 18.20437 | -0.2596 | 7.18108 |
March | 514.00000 | 23.46073 | 24.82011 | 0.06097 | 5.98277 |
April | 485.00000 | 23.91286 | 28.31530 | 0.21888 | 6.37219 |
May | 508.00000 | 24.32771 | 32.29692 | -0.4910 | 10.65104 |
June | 496.00000 | 24.34137 | 43.46846 | -0.3523 | 8.09634 |
July | 497.00000 | 24.43621 | 51.56672 | -0.2502 | 6.84138 |
August | 514.00000 | 24.37229 | 48.11708 | -0.2924 | 7.26509 |
September | 485.00000 | 24.37410 | 43.61024 | -0.3535 | 8.23949 |
October | 502.00000 | 24.14716 | 33.51271 | 0.32729 | 7.52101 |
November | 489.00000 | 23.74876 | 28.01115 | 0.15905 | 5.91135 |
December | 497.00000 | 22.74815 | 21.66001 | -0.1565 | 6.41952 |
Annual Sum or Average | 5943.00000 | 23.71813 | 32.80607 | -0.1424 | 7.43910 |
Minimum of Months | 454.00000 | 22.20591 | 18.20437 | -0.4910 | 5.91135 |
Maximum of Months | 514.00000 | 24.43621 | 51.56672 | 0.32729 | 10.65104 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.91742 | 20.05358 | -0.6193 | 14.35042 |
February | 454.00000 | 21.08832 | 19.53528 | -0.5769 | 12.90037 |
March | 514.00000 | 22.20783 | 26.97763 | -0.2253 | 7.85009 |
April | 485.00000 | 23.02421 | 30.79950 | 0.00964 | 6.00948 |
May | 508.00000 | 23.91943 | 33.95880 | -0.6402 | 14.32831 |
June | 496.00000 | 24.16686 | 44.40010 | -0.4309 | 9.31393 |
July | 497.00000 | 24.29986 | 52.48840 | -0.3141 | 7.40483 |
August | 514.00000 | 24.26063 | 49.10540 | -0.3558 | 7.96490 |
September | 485.00000 | 24.09730 | 44.92552 | -0.4761 | 10.45856 |
October | 502.00000 | 23.23835 | 36.46948 | 0.10312 | 6.07800 |
November | 489.00000 | 22.33978 | 31.32840 | -0.1704 | 6.50495 |
December | 497.00000 | 21.15010 | 23.49995 | -0.5314 | 11.95533 |
Annual Sum or Average | 5943.00000 | 22.90588 | 34.56776 | -0.3514 | 9.57919 |
Minimum of Months | 454.00000 | 20.91742 | 19.53528 | -0.6402 | 6.00948 |
Maximum of Months | 514.00000 | 24.29986 | 52.48840 | 0.10312 | 14.35042 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41036 | 20.14186 | -0.7726 | 19.43325 |
February | 454.00000 | 20.53888 | 19.96471 | -0.7359 | 18.21711 |
March | 514.00000 | 21.56420 | 27.59589 | -0.3944 | 10.95807 |
April | 485.00000 | 22.38868 | 31.66737 | -0.1457 | 7.16949 |
May | 508.00000 | 23.62463 | 34.53166 | -0.7408 | 17.86197 |
June | 496.00000 | 24.06792 | 44.67119 | -0.4600 | 10.09285 |
July | 497.00000 | 24.27112 | 52.38045 | -0.3176 | 7.48784 |
August | 514.00000 | 24.17802 | 49.14054 | -0.3844 | 8.45925 |
September | 485.00000 | 23.81004 | 45.62855 | -0.5820 | 13.43891 |
October | 502.00000 | 22.41127 | 38.10071 | -0.0991 | 7.00394 |
November | 489.00000 | 21.41617 | 32.67540 | -0.4050 | 9.74975 |
December | 497.00000 | 20.51134 | 24.14085 | -0.7161 | 17.53646 |
Annual Sum or Average | 5943.00000 | 22.44782 | 35.15752 | -0.4781 | 12.25008 |
Minimum of Months | 454.00000 | 20.41036 | 19.96471 | -0.7726 | 7.00394 |
Maximum of Months | 514.00000 | 24.27112 | 52.38045 | -0.0991 | 19.43325 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78606 | 20.45179 | -1.0003 | 28.46592 |
February | 454.00000 | 19.83738 | 20.53300 | -0.9706 | 27.31655 |
March | 514.00000 | 20.66366 | 28.87931 | -0.6394 | 17.42087 |
April | 485.00000 | 21.33647 | 33.06685 | -0.3924 | 10.79936 |
May | 508.00000 | 22.96089 | 36.75054 | -0.9335 | 26.10358 |
June | 496.00000 | 23.90495 | 45.85547 | -0.4783 | 11.52044 |
July | 497.00000 | 24.25531 | 53.84262 | -0.2732 | 7.49850 |
August | 514.00000 | 23.99754 | 50.40417 | -0.4120 | 9.84818 |
September | 485.00000 | 23.21855 | 47.98529 | -0.7607 | 20.34963 |
October | 502.00000 | 21.29814 | 39.92565 | -0.3625 | 10.42587 |
November | 489.00000 | 20.42474 | 33.44329 | -0.6719 | 16.40546 |
December | 497.00000 | 19.78583 | 24.61487 | -0.9592 | 27.04768 |
Annual Sum or Average | 5943.00000 | 21.80592 | 36.42170 | -0.6523 | 17.70409 |
Minimum of Months | 454.00000 | 19.78583 | 20.45179 | -1.0003 | 7.49850 |
Maximum of Months | 514.00000 | 24.25531 | 53.84262 | -0.2732 | 28.46592 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83479 | 19.75478 | -0.9767 | 27.47641 |
February | 454.00000 | 19.89529 | 19.90091 | -0.9366 | 26.04291 |
March | 514.00000 | 20.73515 | 28.21760 | -0.5828 | 15.62458 |
April | 485.00000 | 21.62393 | 32.03337 | -0.2798 | 10.20590 |
May | 508.00000 | 22.99665 | 35.98325 | -0.8350 | 23.99272 |
June | 496.00000 | 23.81394 | 45.59788 | -0.4121 | 11.36837 |
July | 497.00000 | 24.19213 | 53.47153 | -0.1980 | 7.79852 |
August | 514.00000 | 23.86827 | 50.27790 | -0.3613 | 10.04519 |
September | 485.00000 | 23.19224 | 47.49152 | -0.6855 | 19.18896 |
October | 502.00000 | 21.37781 | 39.14899 | -0.3114 | 9.64077 |
November | 489.00000 | 20.48798 | 32.73187 | -0.6458 | 15.59751 |
December | 497.00000 | 19.83675 | 23.99524 | -0.9440 | 26.31621 |
Annual Sum or Average | 5943.00000 | 21.83715 | 35.82767 | -0.5952 | 16.87974 |
Minimum of Months | 454.00000 | 19.83479 | 19.75478 | -0.9767 | 7.79852 |
Maximum of Months | 514.00000 | 24.19213 | 53.47153 | -0.1980 | 27.47641 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10397 | 19.44780 | -0.8744 | 24.43094 |
February | 454.00000 | 20.13718 | 19.60280 | -0.8444 | 23.82122 |
March | 514.00000 | 21.28497 | 27.45627 | -0.4373 | 13.57300 |
April | 485.00000 | 21.80922 | 31.55064 | -0.2469 | 10.35926 |
May | 508.00000 | 22.95378 | 36.04929 | -0.8812 | 25.68519 |
June | 496.00000 | 23.70945 | 45.90850 | -0.4964 | 13.19283 |
July | 497.00000 | 24.14835 | 53.72580 | -0.2589 | 8.48345 |
August | 514.00000 | 23.92440 | 50.05412 | -0.3629 | 10.28299 |
September | 485.00000 | 23.43223 | 46.65794 | -0.5962 | 17.43724 |
October | 502.00000 | 21.95786 | 37.73601 | -0.1620 | 9.65835 |
November | 489.00000 | 20.94501 | 31.85801 | -0.5177 | 13.72198 |
December | 497.00000 | 20.06846 | 23.65465 | -0.8560 | 23.39473 |
Annual Sum or Average | 5943.00000 | 22.05541 | 35.41944 | -0.5426 | 16.12252 |
Minimum of Months | 454.00000 | 20.06846 | 19.44780 | -0.8812 | 8.48345 |
Maximum of Months | 514.00000 | 24.14835 | 53.72580 | -0.1620 | 25.68519 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83730 | 19.60494 | -0.9855 | 27.84780 |
February | 454.00000 | 19.91259 | 19.73127 | -0.9422 | 26.33803 |
March | 514.00000 | 20.77408 | 28.10082 | -0.5829 | 15.70649 |
April | 485.00000 | 21.43865 | 32.14917 | -0.3325 | 10.98731 |
May | 508.00000 | 22.64793 | 36.64582 | -0.9457 | 28.82251 |
June | 496.00000 | 23.57072 | 46.24381 | -0.4844 | 14.12848 |
July | 497.00000 | 23.97376 | 54.28274 | -0.2759 | 9.33780 |
August | 514.00000 | 23.67281 | 50.94119 | -0.4237 | 12.03981 |
September | 485.00000 | 22.85098 | 48.38066 | -0.7961 | 23.23888 |
October | 502.00000 | 21.20714 | 39.37584 | -0.3552 | 10.43285 |
November | 489.00000 | 20.45266 | 32.65890 | -0.6569 | 16.03429 |
December | 497.00000 | 19.82297 | 23.88394 | -0.9485 | 26.55768 |
Annual Sum or Average | 5943.00000 | 21.69533 | 36.11357 | -0.6421 | 18.40250 |
Minimum of Months | 454.00000 | 19.82297 | 19.60494 | -0.9855 | 9.33780 |
Maximum of Months | 514.00000 | 23.97376 | 54.28274 | -0.2759 | 28.82251 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05824 | 21.02297 | -0.9118 | 24.21909 |
February | 454.00000 | 20.13582 | 21.11026 | -0.8832 | 22.98411 |
March | 514.00000 | 20.79716 | 29.70797 | -0.6129 | 15.20320 |
April | 485.00000 | 21.33604 | 33.82658 | -0.4060 | 9.65158 |
May | 508.00000 | 22.83592 | 37.93614 | -1.0221 | 28.72886 |
June | 496.00000 | 23.94877 | 46.23867 | -0.5177 | 11.51326 |
July | 497.00000 | 24.25630 | 53.96757 | -0.3201 | 7.61211 |
August | 514.00000 | 24.13515 | 50.08313 | -0.3954 | 8.76270 |
September | 485.00000 | 23.74240 | 47.02850 | -0.6013 | 13.95845 |
October | 502.00000 | 22.28347 | 38.42626 | -0.1184 | 6.76558 |
November | 489.00000 | 21.08850 | 33.02625 | -0.4700 | 10.48064 |
December | 497.00000 | 20.23991 | 24.94636 | -0.8079 | 20.26919 |
Annual Sum or Average | 5943.00000 | 22.08676 | 36.55240 | -0.5875 | 14.98322 |
Minimum of Months | 454.00000 | 20.05824 | 21.02297 | -1.0221 | 6.76558 |
Maximum of Months | 514.00000 | 24.25630 | 53.96757 | -0.1184 | 28.72886 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13269 | 20.03411 | -0.8879 | 23.17392 |
February | 454.00000 | 20.20996 | 20.17882 | -0.8515 | 21.71253 |
March | 514.00000 | 20.88586 | 28.65074 | -0.5522 | 13.21872 |
April | 485.00000 | 21.75004 | 32.21524 | -0.2646 | 8.56440 |
May | 508.00000 | 23.05479 | 36.35841 | -0.8703 | 24.09826 |
June | 496.00000 | 23.96434 | 45.40545 | -0.4199 | 10.38309 |
July | 497.00000 | 24.30149 | 53.11329 | -0.2123 | 7.07339 |
August | 514.00000 | 24.10526 | 49.59588 | -0.3147 | 8.27720 |
September | 485.00000 | 23.73230 | 46.27687 | -0.5201 | 12.95842 |
October | 502.00000 | 22.27633 | 37.48269 | -0.0836 | 6.83571 |
November | 489.00000 | 21.05359 | 32.15994 | -0.4630 | 10.33372 |
December | 497.00000 | 20.27469 | 24.03751 | -0.8004 | 19.82662 |
Annual Sum or Average | 5943.00000 | 22.15997 | 35.56846 | -0.5184 | 13.83547 |
Minimum of Months | 454.00000 | 20.13269 | 20.03411 | -0.8879 | 6.83571 |
Maximum of Months | 514.00000 | 24.30149 | 53.11329 | -0.0836 | 24.09826 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.26857 | 18.81461 | -1.0047 | 28.86505 |
February | 454.00000 | 19.27471 | 19.20399 | -0.9883 | 27.85851 |
March | 514.00000 | 20.55944 | 27.20064 | -0.5667 | 14.83305 |
April | 485.00000 | 21.24313 | 31.78356 | -0.3624 | 10.26460 |
May | 508.00000 | 22.37622 | 36.98243 | -1.0867 | 32.83757 |
June | 496.00000 | 23.46123 | 47.29538 | -0.6100 | 15.48866 |
July | 497.00000 | 24.13977 | 55.25890 | -0.2953 | 8.39372 |
August | 514.00000 | 23.99090 | 50.62693 | -0.3529 | 9.59841 |
September | 485.00000 | 23.72560 | 46.26678 | -0.4880 | 13.37738 |
October | 502.00000 | 22.23413 | 36.26636 | -0.0502 | 7.81995 |
November | 489.00000 | 21.03304 | 30.47804 | -0.4253 | 10.94175 |
December | 497.00000 | 19.60953 | 23.00889 | -0.8884 | 24.21301 |
Annual Sum or Average | 5943.00000 | 21.76110 | 35.38204 | -0.5913 | 16.99608 |
Minimum of Months | 454.00000 | 19.26857 | 18.81461 | -1.0867 | 7.81995 |
Maximum of Months | 514.00000 | 24.13977 | 55.25890 | -0.0502 | 32.83757 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10075 | 19.95898 | -0.9029 | 23.86460 |
February | 454.00000 | 20.19788 | 20.07663 | -0.8624 | 22.21665 |
March | 514.00000 | 20.89701 | 28.57657 | -0.5548 | 13.27510 |
April | 485.00000 | 21.54602 | 32.40526 | -0.3192 | 9.09084 |
May | 508.00000 | 22.81508 | 36.81470 | -0.9482 | 27.22001 |
June | 496.00000 | 23.88664 | 45.65250 | -0.4403 | 11.11626 |
July | 497.00000 | 24.22184 | 53.53747 | -0.2483 | 7.60305 |
August | 514.00000 | 24.07022 | 49.83148 | -0.3299 | 8.72904 |
September | 485.00000 | 23.58023 | 46.80592 | -0.5775 | 14.46674 |
October | 502.00000 | 22.01343 | 37.89339 | -0.1447 | 7.06842 |
November | 489.00000 | 20.99222 | 32.16328 | -0.4792 | 10.56404 |
December | 497.00000 | 20.25797 | 23.95964 | -0.8055 | 20.05377 |
Annual Sum or Average | 5943.00000 | 22.06294 | 35.75051 | -0.5494 | 14.57227 |
Minimum of Months | 454.00000 | 20.10075 | 19.95898 | -0.9482 | 7.06842 |
Maximum of Months | 514.00000 | 24.22184 | 53.53747 | -0.1447 | 27.22001 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98548 | 20.48129 | -0.9087 | 24.47039 |
February | 454.00000 | 20.06630 | 20.53863 | -0.8732 | 23.04790 |
March | 514.00000 | 21.00776 | 28.67986 | -0.5249 | 13.92767 |
April | 485.00000 | 21.83803 | 32.49730 | -0.2584 | 8.40102 |
May | 508.00000 | 23.39776 | 36.01838 | -0.7925 | 20.03746 |
June | 496.00000 | 24.08161 | 45.36260 | -0.4277 | 9.69725 |
July | 497.00000 | 24.33649 | 53.66488 | -0.2565 | 7.00782 |
August | 514.00000 | 24.15906 | 50.06697 | -0.3632 | 8.44653 |
September | 485.00000 | 23.65321 | 47.00251 | -0.6154 | 14.80546 |
October | 502.00000 | 21.96708 | 38.78547 | -0.1873 | 7.73118 |
November | 489.00000 | 20.88271 | 32.98381 | -0.5222 | 11.90623 |
December | 497.00000 | 20.06913 | 24.44510 | -0.8450 | 22.13460 |
Annual Sum or Average | 5943.00000 | 22.13715 | 35.98463 | -0.5459 | 14.24856 |
Minimum of Months | 454.00000 | 19.98548 | 20.48129 | -0.9087 | 7.00782 |
Maximum of Months | 514.00000 | 24.33649 | 53.66488 | -0.1873 | 24.47039 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.87406 | 19.22636 | -0.9274 | 25.20080 |
February | 385.00000 | 19.97725 | 19.35711 | -0.8812 | 23.39198 |
March | 433.00000 | 20.93255 | 27.59667 | -0.5140 | 13.01019 |
April | 410.00000 | 21.82146 | 31.39974 | -0.2217 | 8.76701 |
May | 430.00000 | 23.16374 | 35.37689 | -0.7887 | 21.86507 |
June | 418.00000 | 23.90138 | 45.16517 | -0.4074 | 10.80691 |
July | 422.00000 | 24.26841 | 53.27533 | -0.2053 | 7.76788 |
August | 433.00000 | 23.96475 | 49.91591 | -0.3549 | 9.55692 |
September | 410.00000 | 23.39998 | 46.93935 | -0.6230 | 16.63406 |
October | 427.00000 | 21.76101 | 37.96332 | -0.2066 | 7.86658 |
November | 417.00000 | 20.79216 | 31.66188 | -0.5387 | 12.20028 |
December | 422.00000 | 19.94005 | 23.22821 | -0.8743 | 23.14410 |
Annual Sum or Average | 5034.00000 | 21.99607 | 35.18734 | -0.5435 | 14.97086 |
Minimum of Months | 385.00000 | 19.87406 | 19.22636 | -0.9274 | 7.76788 |
Maximum of Months | 433.00000 | 24.26841 | 53.27533 | -0.2053 | 25.20080 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40818 | 19.21039 | -0.7651 | 20.35265 |
February | 454.00000 | 20.46672 | 19.31201 | -0.7306 | 19.32942 |
March | 514.00000 | 21.68345 | 27.03323 | -0.3161 | 10.73297 |
April | 485.00000 | 22.23102 | 30.91244 | -0.1309 | 8.43726 |
May | 508.00000 | 23.32878 | 35.31158 | -0.7590 | 20.30312 |
June | 496.00000 | 23.91130 | 45.34881 | -0.4403 | 10.86870 |
July | 497.00000 | 24.26772 | 53.41837 | -0.2338 | 7.54276 |
August | 514.00000 | 24.10735 | 49.66578 | -0.3109 | 8.61401 |
September | 485.00000 | 23.78740 | 45.82623 | -0.4761 | 13.01947 |
October | 502.00000 | 22.53163 | 36.60979 | -0.0087 | 8.05415 |
November | 489.00000 | 21.42373 | 31.21196 | -0.3675 | 10.26124 |
December | 497.00000 | 20.41254 | 23.25325 | -0.7319 | 18.63479 |
Annual Sum or Average | 5943.00000 | 22.39549 | 34.86971 | -0.4376 | 12.97652 |
Minimum of Months | 454.00000 | 20.40818 | 19.21039 | -0.7651 | 7.54276 |
Maximum of Months | 514.00000 | 24.26772 | 53.41837 | -0.0087 | 20.35265 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02336 | 19.42800 | -0.8980 | 24.08793 |
February | 454.00000 | 20.12729 | 19.53077 | -0.8494 | 22.34862 |
March | 514.00000 | 21.07795 | 27.78221 | -0.4780 | 12.57313 |
April | 485.00000 | 21.77449 | 31.65186 | -0.2314 | 8.95445 |
May | 508.00000 | 23.00547 | 35.94908 | -0.8274 | 23.42088 |
June | 496.00000 | 23.79576 | 45.63109 | -0.4226 | 11.57502 |
July | 497.00000 | 24.11500 | 53.91783 | -0.2452 | 8.20154 |
August | 514.00000 | 23.89237 | 50.47213 | -0.3614 | 9.92511 |
September | 485.00000 | 23.25193 | 47.47500 | -0.6612 | 17.78528 |
October | 502.00000 | 21.68246 | 38.44146 | -0.2177 | 8.01146 |
November | 489.00000 | 20.81704 | 32.17238 | -0.5265 | 11.92863 |
December | 497.00000 | 20.08723 | 23.50522 | -0.8397 | 21.85551 |
Annual Sum or Average | 5943.00000 | 21.98623 | 35.60885 | -0.5446 | 15.00984 |
Minimum of Months | 454.00000 | 20.02336 | 19.42800 | -0.8980 | 8.01146 |
Maximum of Months | 514.00000 | 24.11500 | 53.91783 | -0.2177 | 24.08793 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.217397E+10 | 0.549874E+09 | 33.50 | 0.185418E+10 | 0.319798E+09 | 0.00 | 0.93 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 32844.37 | 15-MAR-14:00 | 32844.37 | 15-MAR-14:00 | 8797.97 | 14-MAR-10:40 | 8086.73 | 15-MAR-14:00 | 0.00 |
April | 0.757559E+09 | 0.208938E+09 | 35.00 | 0.695127E+09 | 62431624.69 | 0.00 | 0.47 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 14761.66 | 07-APR-13:00 | 14761.66 | 07-APR-13:00 | 2503.39 | 08-APR-14:00 | 3900.50 | 07-APR-13:00 | 0.00 |
May | 0.806638E+10 | 0.208783E+10 | 188.33 | 0.736719E+10 | 0.699188E+09 | 0.00 | 1.00 | 10-MAY-14:10 | 0.00 | 01-MAY-00:10 | 39549.42 | 23-MAY-15:10 | 39549.42 | 23-MAY-15:10 | 10264.33 | 24-MAY-05:03 | 9143.60 | 10-MAY-15:10 | 0.00 |
June | 0.390687E+11 | 0.952588E+10 | 374.51 | 0.297042E+11 | 0.936454E+10 | 0.00 | 1.00 | 01-JUN-14:10 | 0.00 | 01-JUN-00:10 | 100713.55 | 27-JUN-07:40 | 63407.82 | 12-JUN-15:10 | 57190.37 | 27-JUN-07:40 | 22787.10 | 27-JUN-11:30 | 0.00 |
July | 0.693189E+11 | 0.166826E+11 | 428.64 | 0.492119E+11 | 0.201070E+11 | 0.00 | 1.00 | 03-JUL-10:10 | 0.00 | 01-JUL-00:10 | 123483.25 | 20-JUL-04:02 | 67881.40 | 19-JUL-15:30 | 73735.77 | 20-JUL-06:03 | 28179.65 | 21-JUL-04:02 | 0.00 |
August | 0.589747E+11 | 0.142691E+11 | 422.86 | 0.455453E+11 | 0.134295E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 123456.62 | 14-AUG-08:00 | 67838.75 | 10-AUG-16:00 | 77354.01 | 14-AUG-04:02 | 27715.33 | 14-AUG-08:00 | 0.00 |
September | 0.261236E+11 | 0.633997E+10 | 305.26 | 0.196598E+11 | 0.646374E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 84645.41 | 15-SEP-14:50 | 57997.93 | 21-SEP-16:00 | 38813.17 | 15-SEP-14:50 | 19480.81 | 15-SEP-14:50 | 0.00 |
October | 0.280812E+10 | 0.745130E+09 | 84.75 | 0.240788E+10 | 0.400239E+09 | 0.00 | 0.91 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 32300.80 | 11-OCT-15:10 | 32300.80 | 11-OCT-15:10 | 5777.51 | 12-OCT-15:00 | 7564.93 | 11-OCT-15:10 | 0.00 |
November | 0.504721E+09 | 0.139556E+09 | 18.83 | 0.377544E+09 | 0.127177E+09 | 0.00 | 0.40 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 12177.19 | 16-NOV-18:00 | 10506.33 | 16-NOV-13:00 | 3035.92 | 04-NOV-14:50 | 3279.56 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.207797E+12 | 0.505489E+11 | 1891.68 | 0.156823E+12 | 0.509736E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.693189E+11 | 0.166826E+11 | 428.64 | 0.492119E+11 | 0.201070E+11 | 0.00 | 1.00 | 0.00 | 123483.25 | 67881.40 | 77354.01 | 28179.65 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.203711E+10 | 0.513540E+09 | 33.50 | 0.173013E+10 | 0.306984E+09 | 0.00 | 1.00 | 15-MAR-13:40 | 0.00 | 01-MAR-00:10 | 34187.46 | 15-MAR-13:50 | 34187.46 | 15-MAR-13:50 | 8227.55 | 14-MAR-10:40 | 8232.13 | 15-MAR-14:00 | 0.00 |
April | 0.732973E+09 | 0.202461E+09 | 37.90 | 0.678899E+09 | 54074115.56 | 0.00 | 0.49 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 14388.24 | 08-APR-13:30 | 13307.00 | 07-APR-14:00 | 1958.42 | 08-APR-14:40 | 3780.91 | 08-APR-13:30 | 0.00 |
May | 0.803921E+10 | 0.207215E+10 | 194.11 | 0.733451E+10 | 0.704701E+09 | 0.00 | 1.00 | 10-MAY-13:30 | 0.00 | 01-MAY-00:10 | 40081.55 | 23-MAY-14:30 | 40081.55 | 23-MAY-14:30 | 10426.12 | 24-MAY-05:03 | 9461.47 | 10-MAY-15:00 | 0.00 |
June | 0.371717E+11 | 0.905664E+10 | 379.38 | 0.283979E+11 | 0.877381E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 87363.01 | 27-JUN-07:40 | 61622.86 | 12-JUN-15:00 | 49576.98 | 27-JUN-07:40 | 20837.37 | 27-JUN-13:00 | 0.00 |
July | 0.641051E+11 | 0.154164E+11 | 433.44 | 0.455289E+11 | 0.185761E+11 | 0.00 | 1.00 | 02-JUL-15:52 | 0.00 | 01-JUL-00:10 | 114489.86 | 20-JUL-04:02 | 63803.60 | 21-JUL-13:40 | 68140.89 | 20-JUL-05:02 | 26247.47 | 21-JUL-04:02 | 0.00 |
August | 0.523552E+11 | 0.126903E+11 | 419.95 | 0.406628E+11 | 0.116924E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 114317.08 | 14-AUG-04:02 | 65132.36 | 09-AUG-15:20 | 71806.20 | 14-AUG-04:02 | 25569.30 | 15-AUG-14:30 | 0.00 |
September | 0.226811E+11 | 0.553322E+10 | 300.91 | 0.170481E+11 | 0.563294E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 76384.36 | 16-SEP-05:02 | 53709.55 | 21-SEP-15:40 | 43602.30 | 14-SEP-05:02 | 17532.41 | 16-SEP-05:02 | 0.00 |
October | 0.251329E+10 | 0.671539E+09 | 84.47 | 0.212669E+10 | 0.386600E+09 | 0.00 | 0.86 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27843.08 | 11-OCT-15:00 | 27843.08 | 11-OCT-15:00 | 5532.52 | 12-OCT-15:00 | 6618.30 | 11-OCT-15:00 | 0.00 |
November | 0.449901E+09 | 0.124803E+09 | 18.83 | 0.327068E+09 | 0.122834E+09 | 0.00 | 0.37 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 10478.01 | 16-NOV-18:00 | 7990.20 | 16-NOV-13:00 | 2850.32 | 04-NOV-14:30 | 2840.48 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.190086E+12 | 0.462811E+11 | 1902.49 | 0.143835E+12 | 0.462504E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.641051E+11 | 0.154164E+11 | 433.44 | 0.455289E+11 | 0.185761E+11 | 0.00 | 1.00 | 0.00 | 114489.86 | 65132.36 | 71806.20 | 26247.47 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.224327E+10 | 0.565509E+09 | 33.50 | 0.192010E+10 | 0.323165E+09 | 0.00 | 1.00 | 15-MAR-13:20 | 0.00 | 01-MAR-00:10 | 41473.01 | 15-MAR-14:00 | 41473.01 | 15-MAR-14:00 | 9080.78 | 14-MAR-10:40 | 10010.85 | 15-MAR-14:00 | 0.00 |
April | 0.761276E+09 | 0.210960E+09 | 37.06 | 0.694200E+09 | 67075948.12 | 0.00 | 0.48 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 15399.95 | 08-APR-13:30 | 13609.47 | 08-APR-13:00 | 2357.56 | 08-APR-14:10 | 4064.53 | 08-APR-13:30 | 0.00 |
May | 0.840454E+10 | 0.217595E+10 | 193.73 | 0.757674E+10 | 0.827807E+09 | 0.00 | 1.00 | 10-MAY-13:10 | 0.00 | 01-MAY-00:10 | 45739.43 | 10-MAY-15:00 | 45618.12 | 10-MAY-14:30 | 7709.11 | 14-MAY-16:05 | 11026.13 | 10-MAY-15:00 | 0.00 |
June | 0.396829E+11 | 0.969160E+10 | 374.75 | 0.299973E+11 | 0.968569E+10 | 0.00 | 1.00 | 01-JUN-13:50 | 0.00 | 01-JUN-00:10 | 127223.44 | 27-JUN-15:00 | 76252.35 | 27-JUN-15:43 | 71160.20 | 27-JUN-14:55 | 29072.66 | 27-JUN-15:40 | 0.00 |
July | 0.684600E+11 | 0.165078E+11 | 428.78 | 0.485931E+11 | 0.198669E+11 | 0.00 | 1.00 | 02-JUL-15:52 | 0.00 | 01-JUL-00:10 | 127477.93 | 20-JUL-04:02 | 75524.08 | 21-JUL-13:30 | 76595.04 | 20-JUL-05:02 | 29265.99 | 21-JUL-04:02 | 0.00 |
August | 0.553442E+11 | 0.134734E+11 | 415.99 | 0.426914E+11 | 0.126528E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 127285.55 | 14-AUG-04:02 | 74303.47 | 09-AUG-15:10 | 79871.38 | 14-AUG-04:02 | 28708.19 | 15-AUG-14:20 | 0.00 |
September | 0.230438E+11 | 0.566709E+10 | 298.27 | 0.168546E+11 | 0.618921E+10 | 0.00 | 1.00 | 08-SEP-12:40 | 0.00 | 01-SEP-00:10 | 88743.83 | 15-SEP-12:30 | 60178.99 | 21-SEP-15:30 | 39360.62 | 15-SEP-12:30 | 20620.15 | 15-SEP-12:30 | 0.00 |
October | 0.245131E+10 | 0.661672E+09 | 82.21 | 0.200981E+10 | 0.441503E+09 | 0.00 | 0.78 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 27252.09 | 11-OCT-15:00 | 27252.09 | 11-OCT-15:00 | 6048.33 | 12-OCT-15:00 | 6636.33 | 11-OCT-15:00 | 0.00 |
November | 0.482143E+09 | 0.134043E+09 | 18.83 | 0.345441E+09 | 0.136703E+09 | 0.00 | 0.36 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 11295.69 | 16-NOV-18:00 | 8759.57 | 27-NOV-07:03 | 3154.23 | 04-NOV-14:40 | 3070.42 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.200874E+12 | 0.490879E+11 | 1883.12 | 0.150683E+12 | 0.501908E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.684600E+11 | 0.165078E+11 | 428.78 | 0.485931E+11 | 0.198669E+11 | 0.00 | 1.00 | 0.00 | 127477.93 | 76252.35 | 79871.38 | 29265.99 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.25 | 0.00 | 353.25 | 7.63 | 1945.76 | 0.00 | 0.00 | 0.00 |
February | 538.23 | 0.00 | 538.23 | 45.34 | 1814.33 | 0.00 | 0.00 | 0.00 |
March | 652.71 | 0.00 | 652.71 | 231.44 | 1297.07 | 0.00 | 0.00 | 0.00 |
April | 831.69 | 3.32 | 828.37 | 481.73 | 913.02 | 0.00 | 0.00 | 0.00 |
May | 966.39 | 40.98 | 925.41 | 779.27 | 598.77 | 0.00 | 0.00 | 0.00 |
June | 1162.36 | 98.95 | 1063.41 | 1248.08 | 401.19 | 0.00 | 0.00 | 0.00 |
July | 1078.24 | 69.60 | 1008.64 | 1327.66 | 285.52 | 0.00 | 0.00 | 0.00 |
August | 932.98 | 14.19 | 918.79 | 1088.76 | 373.05 | 0.00 | 0.00 | 0.00 |
September | 710.02 | 0.15 | 709.87 | 651.53 | 588.97 | 0.00 | 0.00 | 0.00 |
October | 530.77 | 0.00 | 530.77 | 287.73 | 900.35 | 0.00 | 0.00 | 0.00 |
November | 356.66 | 0.00 | 356.66 | 92.33 | 1171.26 | 0.00 | 0.00 | 0.00 |
December | 330.63 | 0.00 | 330.63 | 8.57 | 1841.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 704.35 | 19.01 | 685.33 | 523.68 | 1006.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.63 | 0.00 | 330.63 | 7.63 | 285.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1162.36 | 98.95 | 1063.41 | 1327.66 | 1945.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 430.96 | 138.97 | 292.00 | 175.95 | 1178.18 | 0.00 | 0.00 | 0.00 |
February | 632.36 | 189.75 | 442.60 | 315.59 | 1114.19 | 0.00 | 0.00 | 0.00 |
March | 907.41 | 380.02 | 527.40 | 727.56 | 795.71 | 0.00 | 0.00 | 0.00 |
April | 1201.02 | 530.67 | 670.35 | 1145.46 | 578.46 | 0.00 | 0.00 | 0.00 |
May | 1345.57 | 595.22 | 750.36 | 1459.15 | 401.19 | 0.00 | 0.00 | 0.00 |
June | 1502.78 | 664.15 | 838.63 | 1806.89 | 267.38 | 0.00 | 0.00 | 0.00 |
July | 1443.06 | 635.36 | 807.70 | 1857.92 | 188.62 | 0.00 | 0.00 | 0.00 |
August | 1303.24 | 547.03 | 756.21 | 1644.12 | 243.43 | 0.00 | 0.00 | 0.00 |
September | 1084.52 | 481.05 | 603.47 | 1247.27 | 373.00 | 0.00 | 0.00 | 0.00 |
October | 735.94 | 304.40 | 431.54 | 679.16 | 566.48 | 0.00 | 0.00 | 0.00 |
November | 417.44 | 133.91 | 283.53 | 273.17 | 745.79 | 0.00 | 0.00 | 0.00 |
December | 336.06 | 69.44 | 266.62 | 94.03 | 1152.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 946.43 | 390.11 | 556.32 | 955.60 | 631.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.06 | 69.44 | 266.62 | 94.03 | 188.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1502.78 | 664.15 | 838.63 | 1857.92 | 1178.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1518.97 | 886.67 | 632.30 | 1244.73 | 1663.62 | 0.00 | 0.00 | 0.00 |
February | 1734.28 | 836.25 | 898.03 | 1404.50 | 1633.40 | 0.00 | 0.00 | 0.00 |
March | 2116.81 | 1189.42 | 927.39 | 2088.58 | 1203.99 | 0.00 | 0.00 | 0.00 |
April | 1753.05 | 700.52 | 1052.53 | 1805.40 | 947.89 | 0.00 | 0.00 | 0.00 |
May | 1534.08 | 445.56 | 1088.52 | 1704.35 | 654.04 | 0.00 | 0.00 | 0.00 |
June | 1490.63 | 315.87 | 1174.76 | 1835.82 | 434.07 | 0.00 | 0.00 | 0.00 |
July | 1521.69 | 369.21 | 1152.48 | 2063.21 | 305.61 | 0.00 | 0.00 | 0.00 |
August | 1708.35 | 553.89 | 1154.46 | 2279.93 | 391.00 | 0.00 | 0.00 | 0.00 |
September | 1986.30 | 967.47 | 1018.82 | 2456.39 | 601.78 | 0.00 | 0.00 | 0.00 |
October | 1900.59 | 1085.65 | 814.94 | 2061.39 | 876.34 | 0.00 | 0.00 | 0.00 |
November | 1361.16 | 768.42 | 592.74 | 1305.31 | 1112.84 | 0.00 | 0.00 | 0.00 |
December | 1270.16 | 657.36 | 612.80 | 989.22 | 1628.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1657.49 | 730.97 | 926.52 | 1772.02 | 950.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1270.16 | 315.87 | 592.74 | 989.22 | 305.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2116.81 | 1189.42 | 1174.76 | 2456.39 | 1663.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.76 | 86.81 | 282.96 | 109.61 | 1224.25 | 0.00 | 0.00 | 0.00 |
February | 599.28 | 154.02 | 445.26 | 272.67 | 1151.18 | 0.00 | 0.00 | 0.00 |
March | 939.27 | 402.17 | 537.09 | 768.18 | 818.20 | 0.00 | 0.00 | 0.00 |
April | 1150.00 | 471.55 | 678.46 | 1097.22 | 606.12 | 0.00 | 0.00 | 0.00 |
May | 1356.61 | 613.10 | 743.51 | 1489.32 | 426.41 | 0.00 | 0.00 | 0.00 |
June | 1636.79 | 769.88 | 866.92 | 1996.43 | 293.38 | 0.00 | 0.00 | 0.00 |
July | 1463.36 | 641.58 | 821.77 | 1897.38 | 209.70 | 0.00 | 0.00 | 0.00 |
August | 1323.52 | 562.77 | 760.75 | 1691.68 | 261.17 | 0.00 | 0.00 | 0.00 |
September | 1039.37 | 448.86 | 590.51 | 1204.90 | 392.43 | 0.00 | 0.00 | 0.00 |
October | 673.77 | 237.34 | 436.43 | 610.85 | 587.07 | 0.00 | 0.00 | 0.00 |
November | 399.28 | 115.06 | 284.22 | 252.86 | 761.07 | 0.00 | 0.00 | 0.00 |
December | 346.14 | 75.42 | 270.72 | 106.17 | 1171.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.98 | 382.65 | 560.33 | 961.77 | 656.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 346.14 | 75.42 | 270.72 | 106.17 | 209.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1636.79 | 769.88 | 866.92 | 1996.43 | 1224.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.75 | 0.00 | 117.75 | 1.67 | 663.77 | 0.00 | 0.00 | 0.00 |
February | 179.40 | 0.00 | 179.40 | 14.38 | 619.01 | 0.00 | 0.00 | 0.00 |
March | 217.56 | 0.00 | 217.56 | 80.80 | 440.23 | 0.00 | 0.00 | 0.00 |
April | 277.22 | 1.11 | 276.11 | 167.66 | 307.55 | 0.00 | 0.00 | 0.00 |
May | 322.11 | 13.66 | 308.45 | 272.00 | 195.55 | 0.00 | 0.00 | 0.00 |
June | 387.43 | 32.98 | 354.45 | 425.14 | 131.62 | 0.00 | 0.00 | 0.00 |
July | 359.40 | 23.20 | 336.20 | 450.52 | 92.76 | 0.00 | 0.00 | 0.00 |
August | 310.98 | 4.73 | 306.25 | 366.36 | 126.65 | 0.00 | 0.00 | 0.00 |
September | 236.66 | 0.05 | 236.61 | 215.15 | 211.29 | 0.00 | 0.00 | 0.00 |
October | 176.91 | 0.00 | 176.91 | 87.82 | 335.89 | 0.00 | 0.00 | 0.00 |
November | 118.88 | 0.00 | 118.88 | 26.50 | 428.98 | 0.00 | 0.00 | 0.00 |
December | 110.21 | 0.00 | 110.21 | 1.99 | 644.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.77 | 6.34 | 228.43 | 176.80 | 348.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.21 | 0.00 | 110.21 | 1.67 | 92.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.43 | 32.98 | 354.45 | 450.52 | 663.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.75 | 0.00 | 117.75 | 1.67 | 663.81 | 0.00 | 0.00 | 0.00 |
February | 179.41 | 0.00 | 179.41 | 14.38 | 619.05 | 0.00 | 0.00 | 0.00 |
March | 217.58 | 0.00 | 217.58 | 80.80 | 440.26 | 0.00 | 0.00 | 0.00 |
April | 277.24 | 1.11 | 276.13 | 167.67 | 307.57 | 0.00 | 0.00 | 0.00 |
May | 322.13 | 13.66 | 308.47 | 272.01 | 195.56 | 0.00 | 0.00 | 0.00 |
June | 387.46 | 32.98 | 354.48 | 425.17 | 131.63 | 0.00 | 0.00 | 0.00 |
July | 359.42 | 23.20 | 336.22 | 450.55 | 92.77 | 0.00 | 0.00 | 0.00 |
August | 311.00 | 4.73 | 306.27 | 366.38 | 126.66 | 0.00 | 0.00 | 0.00 |
September | 236.68 | 0.05 | 236.63 | 215.17 | 211.31 | 0.00 | 0.00 | 0.00 |
October | 176.93 | 0.00 | 176.93 | 87.83 | 335.91 | 0.00 | 0.00 | 0.00 |
November | 118.89 | 0.00 | 118.89 | 26.50 | 429.00 | 0.00 | 0.00 | 0.00 |
December | 110.21 | 0.00 | 110.21 | 1.99 | 644.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.79 | 6.34 | 228.45 | 176.81 | 348.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.21 | 0.00 | 110.21 | 1.67 | 92.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.46 | 32.98 | 354.48 | 450.55 | 663.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.75 | 0.00 | 117.75 | 1.67 | 663.81 | 0.00 | 0.00 | 0.00 |
February | 179.41 | 0.00 | 179.41 | 14.38 | 619.05 | 0.00 | 0.00 | 0.00 |
March | 217.58 | 0.00 | 217.58 | 80.80 | 440.26 | 0.00 | 0.00 | 0.00 |
April | 277.24 | 1.11 | 276.13 | 167.67 | 307.57 | 0.00 | 0.00 | 0.00 |
May | 322.13 | 13.66 | 308.47 | 272.01 | 195.56 | 0.00 | 0.00 | 0.00 |
June | 387.46 | 32.98 | 354.48 | 425.17 | 131.63 | 0.00 | 0.00 | 0.00 |
July | 359.42 | 23.20 | 336.22 | 450.55 | 92.77 | 0.00 | 0.00 | 0.00 |
August | 311.00 | 4.73 | 306.27 | 366.38 | 126.66 | 0.00 | 0.00 | 0.00 |
September | 236.68 | 0.05 | 236.63 | 215.17 | 211.31 | 0.00 | 0.00 | 0.00 |
October | 176.93 | 0.00 | 176.93 | 87.83 | 335.91 | 0.00 | 0.00 | 0.00 |
November | 118.89 | 0.00 | 118.89 | 26.50 | 429.00 | 0.00 | 0.00 | 0.00 |
December | 110.21 | 0.00 | 110.21 | 1.99 | 644.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 234.79 | 6.34 | 228.45 | 176.81 | 348.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.21 | 0.00 | 110.21 | 1.67 | 92.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.46 | 32.98 | 354.48 | 450.55 | 663.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.57 | 133.68 | 280.89 | 168.34 | 1166.02 | 0.00 | 0.00 | 0.00 |
February | 608.30 | 182.53 | 425.76 | 303.88 | 1101.52 | 0.00 | 0.00 | 0.00 |
March | 872.89 | 365.56 | 507.33 | 710.39 | 788.88 | 0.00 | 0.00 | 0.00 |
April | 1155.33 | 510.48 | 644.84 | 1115.35 | 575.34 | 0.00 | 0.00 | 0.00 |
May | 1294.38 | 572.57 | 721.81 | 1423.90 | 390.31 | 0.00 | 0.00 | 0.00 |
June | 1445.61 | 638.88 | 806.72 | 1754.29 | 262.32 | 0.00 | 0.00 | 0.00 |
July | 1388.16 | 611.19 | 776.98 | 1801.22 | 185.17 | 0.00 | 0.00 | 0.00 |
August | 1253.66 | 526.22 | 727.45 | 1588.71 | 246.94 | 0.00 | 0.00 | 0.00 |
September | 1043.27 | 462.75 | 580.52 | 1196.61 | 393.41 | 0.00 | 0.00 | 0.00 |
October | 707.94 | 292.82 | 415.12 | 636.48 | 612.21 | 0.00 | 0.00 | 0.00 |
November | 401.56 | 128.81 | 272.74 | 252.95 | 788.90 | 0.00 | 0.00 | 0.00 |
December | 323.27 | 66.80 | 256.48 | 87.48 | 1164.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 910.43 | 375.27 | 535.16 | 923.28 | 637.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.27 | 66.80 | 256.48 | 87.48 | 185.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1445.61 | 638.88 | 806.72 | 1801.22 | 1166.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.39 | 5.29 | 11.11 | 6.66 | 46.10 | 0.00 | 0.00 | 0.00 |
February | 24.05 | 7.22 | 16.83 | 12.02 | 43.55 | 0.00 | 0.00 | 0.00 |
March | 34.51 | 14.45 | 20.06 | 28.09 | 31.19 | 0.00 | 0.00 | 0.00 |
April | 45.68 | 20.18 | 25.50 | 44.10 | 22.75 | 0.00 | 0.00 | 0.00 |
May | 51.18 | 22.64 | 28.54 | 56.30 | 15.43 | 0.00 | 0.00 | 0.00 |
June | 57.16 | 25.26 | 31.90 | 69.36 | 10.37 | 0.00 | 0.00 | 0.00 |
July | 54.89 | 24.17 | 30.72 | 71.22 | 7.32 | 0.00 | 0.00 | 0.00 |
August | 49.57 | 20.81 | 28.76 | 62.82 | 9.76 | 0.00 | 0.00 | 0.00 |
September | 41.25 | 18.30 | 22.95 | 47.31 | 15.56 | 0.00 | 0.00 | 0.00 |
October | 27.99 | 11.58 | 16.41 | 25.17 | 24.21 | 0.00 | 0.00 | 0.00 |
November | 15.88 | 5.09 | 10.78 | 10.00 | 31.19 | 0.00 | 0.00 | 0.00 |
December | 12.78 | 2.64 | 10.14 | 3.46 | 46.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.00 | 14.84 | 21.16 | 36.51 | 25.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.78 | 2.64 | 10.14 | 3.46 | 7.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.16 | 25.26 | 31.90 | 71.22 | 46.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.34 | 295.57 | 210.77 | 424.43 | 560.11 | 0.00 | 0.00 | 0.00 |
February | 578.11 | 278.76 | 299.35 | 481.66 | 548.24 | 0.00 | 0.00 | 0.00 |
March | 705.62 | 396.49 | 309.14 | 714.26 | 412.63 | 0.00 | 0.00 | 0.00 |
April | 584.37 | 233.52 | 350.85 | 617.58 | 320.55 | 0.00 | 0.00 | 0.00 |
May | 511.37 | 148.52 | 362.85 | 586.72 | 213.63 | 0.00 | 0.00 | 0.00 |
June | 496.89 | 105.29 | 391.60 | 626.53 | 142.36 | 0.00 | 0.00 | 0.00 |
July | 507.24 | 123.07 | 384.17 | 697.29 | 101.65 | 0.00 | 0.00 | 0.00 |
August | 569.47 | 184.64 | 384.83 | 766.18 | 136.31 | 0.00 | 0.00 | 0.00 |
September | 662.12 | 322.50 | 339.62 | 821.49 | 219.72 | 0.00 | 0.00 | 0.00 |
October | 633.55 | 361.90 | 271.65 | 687.52 | 326.49 | 0.00 | 0.00 | 0.00 |
November | 453.74 | 256.15 | 197.59 | 434.62 | 406.44 | 0.00 | 0.00 | 0.00 |
December | 423.40 | 219.13 | 204.27 | 333.89 | 559.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.51 | 243.66 | 308.85 | 600.03 | 327.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.40 | 105.29 | 197.59 | 333.89 | 101.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.62 | 396.49 | 391.60 | 821.49 | 560.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.34 | 295.57 | 210.77 | 424.43 | 560.11 | 0.00 | 0.00 | 0.00 |
February | 578.11 | 278.76 | 299.35 | 481.66 | 548.24 | 0.00 | 0.00 | 0.00 |
March | 705.62 | 396.49 | 309.14 | 714.26 | 412.63 | 0.00 | 0.00 | 0.00 |
April | 584.37 | 233.52 | 350.85 | 617.58 | 320.55 | 0.00 | 0.00 | 0.00 |
May | 511.37 | 148.52 | 362.85 | 586.72 | 213.63 | 0.00 | 0.00 | 0.00 |
June | 496.89 | 105.29 | 391.60 | 626.53 | 142.36 | 0.00 | 0.00 | 0.00 |
July | 507.24 | 123.07 | 384.17 | 697.29 | 101.65 | 0.00 | 0.00 | 0.00 |
August | 569.47 | 184.64 | 384.83 | 766.18 | 136.31 | 0.00 | 0.00 | 0.00 |
September | 662.12 | 322.50 | 339.62 | 821.49 | 219.72 | 0.00 | 0.00 | 0.00 |
October | 633.55 | 361.90 | 271.65 | 687.52 | 326.49 | 0.00 | 0.00 | 0.00 |
November | 453.74 | 256.15 | 197.59 | 434.62 | 406.44 | 0.00 | 0.00 | 0.00 |
December | 423.40 | 219.13 | 204.27 | 333.89 | 559.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.51 | 243.66 | 308.85 | 600.03 | 327.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.40 | 105.29 | 197.59 | 333.89 | 101.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.62 | 396.49 | 391.60 | 821.49 | 560.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.31 | 295.55 | 210.76 | 424.41 | 560.08 | 0.00 | 0.00 | 0.00 |
February | 578.08 | 278.74 | 299.33 | 481.63 | 548.21 | 0.00 | 0.00 | 0.00 |
March | 705.58 | 396.46 | 309.12 | 714.21 | 412.60 | 0.00 | 0.00 | 0.00 |
April | 584.33 | 233.50 | 350.83 | 617.54 | 320.53 | 0.00 | 0.00 | 0.00 |
May | 511.34 | 148.52 | 362.83 | 586.68 | 213.62 | 0.00 | 0.00 | 0.00 |
June | 496.86 | 105.29 | 391.57 | 626.49 | 142.35 | 0.00 | 0.00 | 0.00 |
July | 507.21 | 123.07 | 384.15 | 697.25 | 101.64 | 0.00 | 0.00 | 0.00 |
August | 569.43 | 184.62 | 384.81 | 766.13 | 136.31 | 0.00 | 0.00 | 0.00 |
September | 662.08 | 322.48 | 339.60 | 821.44 | 219.70 | 0.00 | 0.00 | 0.00 |
October | 633.51 | 361.87 | 271.64 | 687.48 | 326.47 | 0.00 | 0.00 | 0.00 |
November | 453.71 | 256.13 | 197.57 | 434.59 | 406.41 | 0.00 | 0.00 | 0.00 |
December | 423.37 | 219.11 | 204.26 | 333.87 | 559.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 552.48 | 243.65 | 308.83 | 599.99 | 327.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 423.37 | 105.29 | 197.57 | 333.87 | 101.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.58 | 396.46 | 391.57 | 821.44 | 560.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 355.69 | 83.50 | 272.19 | 105.86 | 1206.51 | 0.00 | 0.00 | 0.00 |
February | 576.48 | 148.16 | 428.32 | 266.63 | 1135.58 | 0.00 | 0.00 | 0.00 |
March | 903.53 | 386.87 | 516.66 | 754.00 | 812.81 | 0.00 | 0.00 | 0.00 |
April | 1106.25 | 453.61 | 652.65 | 1073.55 | 601.09 | 0.00 | 0.00 | 0.00 |
May | 1305.00 | 589.77 | 715.23 | 1453.24 | 416.06 | 0.00 | 0.00 | 0.00 |
June | 1574.53 | 740.59 | 833.94 | 1936.07 | 290.59 | 0.00 | 0.00 | 0.00 |
July | 1407.69 | 617.18 | 790.51 | 1837.69 | 206.81 | 0.00 | 0.00 | 0.00 |
August | 1273.17 | 541.36 | 731.81 | 1631.23 | 266.53 | 0.00 | 0.00 | 0.00 |
September | 999.83 | 431.78 | 568.05 | 1153.38 | 413.90 | 0.00 | 0.00 | 0.00 |
October | 648.14 | 228.31 | 419.83 | 575.49 | 630.40 | 0.00 | 0.00 | 0.00 |
November | 384.09 | 110.68 | 273.41 | 235.80 | 803.18 | 0.00 | 0.00 | 0.00 |
December | 332.97 | 72.55 | 260.42 | 100.63 | 1182.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 907.11 | 368.09 | 539.02 | 930.50 | 661.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.97 | 72.55 | 260.42 | 100.63 | 206.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1574.53 | 740.59 | 833.94 | 1936.07 | 1206.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.06 | 3.30 | 10.76 | 4.19 | 47.70 | 0.00 | 0.00 | 0.00 |
February | 22.79 | 5.86 | 16.94 | 10.54 | 44.90 | 0.00 | 0.00 | 0.00 |
March | 35.72 | 15.30 | 20.43 | 29.81 | 32.14 | 0.00 | 0.00 | 0.00 |
April | 43.74 | 17.94 | 25.81 | 42.45 | 23.77 | 0.00 | 0.00 | 0.00 |
May | 51.60 | 23.32 | 28.28 | 57.46 | 16.45 | 0.00 | 0.00 | 0.00 |
June | 62.26 | 29.28 | 32.97 | 76.55 | 11.49 | 0.00 | 0.00 | 0.00 |
July | 55.66 | 24.40 | 31.26 | 72.66 | 8.18 | 0.00 | 0.00 | 0.00 |
August | 50.34 | 21.40 | 28.93 | 64.50 | 10.54 | 0.00 | 0.00 | 0.00 |
September | 39.53 | 17.07 | 22.46 | 45.60 | 16.37 | 0.00 | 0.00 | 0.00 |
October | 25.63 | 9.03 | 16.60 | 22.75 | 24.93 | 0.00 | 0.00 | 0.00 |
November | 15.19 | 4.38 | 10.81 | 9.32 | 31.76 | 0.00 | 0.00 | 0.00 |
December | 13.17 | 2.87 | 10.30 | 3.98 | 46.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.87 | 14.55 | 21.31 | 36.79 | 26.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.17 | 2.87 | 10.30 | 3.98 | 8.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.26 | 29.28 | 32.97 | 76.55 | 47.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.25 | 0.00 | 353.25 | 5.04 | 2011.98 | 0.00 | 0.00 | 0.00 |
February | 538.23 | 0.00 | 538.23 | 39.41 | 1880.14 | 0.00 | 0.00 | 0.00 |
March | 652.71 | 0.00 | 652.71 | 220.37 | 1368.07 | 0.00 | 0.00 | 0.00 |
April | 831.69 | 3.32 | 828.37 | 462.62 | 975.43 | 0.00 | 0.00 | 0.00 |
May | 966.39 | 40.98 | 925.41 | 762.47 | 635.17 | 0.00 | 0.00 | 0.00 |
June | 1162.36 | 98.95 | 1063.41 | 1243.72 | 417.25 | 0.00 | 0.00 | 0.00 |
July | 1078.24 | 69.60 | 1008.64 | 1329.15 | 293.43 | 0.00 | 0.00 | 0.00 |
August | 932.98 | 14.19 | 918.79 | 1086.08 | 389.29 | 0.00 | 0.00 | 0.00 |
September | 710.02 | 0.15 | 709.87 | 639.02 | 632.04 | 0.00 | 0.00 | 0.00 |
October | 530.77 | 0.00 | 530.77 | 265.71 | 981.24 | 0.00 | 0.00 | 0.00 |
November | 356.66 | 0.00 | 356.66 | 80.32 | 1263.99 | 0.00 | 0.00 | 0.00 |
December | 330.63 | 0.00 | 330.63 | 6.05 | 1922.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 704.35 | 19.01 | 685.33 | 514.51 | 1060.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.63 | 0.00 | 330.63 | 5.04 | 293.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1162.36 | 98.95 | 1063.41 | 1329.15 | 2011.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 430.96 | 138.97 | 292.00 | 171.26 | 1219.60 | 0.00 | 0.00 | 0.00 |
February | 632.36 | 189.75 | 442.60 | 307.81 | 1153.97 | 0.00 | 0.00 | 0.00 |
March | 907.41 | 380.02 | 527.40 | 717.60 | 838.41 | 0.00 | 0.00 | 0.00 |
April | 1201.02 | 530.67 | 670.35 | 1134.20 | 612.50 | 0.00 | 0.00 | 0.00 |
May | 1345.57 | 595.22 | 750.36 | 1453.50 | 421.59 | 0.00 | 0.00 | 0.00 |
June | 1502.78 | 664.15 | 838.63 | 1807.52 | 276.77 | 0.00 | 0.00 | 0.00 |
July | 1443.06 | 635.36 | 807.70 | 1861.58 | 192.87 | 0.00 | 0.00 | 0.00 |
August | 1303.24 | 547.03 | 756.21 | 1644.83 | 252.52 | 0.00 | 0.00 | 0.00 |
September | 1084.52 | 481.05 | 603.47 | 1241.25 | 395.36 | 0.00 | 0.00 | 0.00 |
October | 735.94 | 304.40 | 431.54 | 664.11 | 611.22 | 0.00 | 0.00 | 0.00 |
November | 417.44 | 133.91 | 283.53 | 262.89 | 801.59 | 0.00 | 0.00 | 0.00 |
December | 336.06 | 69.44 | 266.62 | 89.81 | 1203.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 946.43 | 390.11 | 556.32 | 949.80 | 662.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 336.06 | 69.44 | 266.62 | 89.81 | 192.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1502.78 | 664.15 | 838.63 | 1861.58 | 1219.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1518.97 | 886.67 | 632.30 | 1232.87 | 1728.06 | 0.00 | 0.00 | 0.00 |
February | 1734.28 | 836.25 | 898.03 | 1390.79 | 1696.49 | 0.00 | 0.00 | 0.00 |
March | 2116.81 | 1189.42 | 927.39 | 2072.74 | 1272.37 | 0.00 | 0.00 | 0.00 |
April | 1753.05 | 700.52 | 1052.53 | 1790.20 | 1006.80 | 0.00 | 0.00 | 0.00 |
May | 1534.08 | 445.56 | 1088.52 | 1695.11 | 692.59 | 0.00 | 0.00 | 0.00 |
June | 1490.63 | 315.87 | 1174.76 | 1835.29 | 453.64 | 0.00 | 0.00 | 0.00 |
July | 1521.69 | 369.21 | 1152.48 | 2066.91 | 315.68 | 0.00 | 0.00 | 0.00 |
August | 1708.35 | 553.89 | 1154.46 | 2280.15 | 408.60 | 0.00 | 0.00 | 0.00 |
September | 1986.30 | 967.47 | 1018.82 | 2448.36 | 641.05 | 0.00 | 0.00 | 0.00 |
October | 1900.59 | 1085.65 | 814.94 | 2039.20 | 948.09 | 0.00 | 0.00 | 0.00 |
November | 1361.16 | 768.42 | 592.74 | 1285.79 | 1197.70 | 0.00 | 0.00 | 0.00 |
December | 1270.16 | 657.36 | 612.80 | 976.20 | 1703.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1657.49 | 730.97 | 926.52 | 1761.62 | 1001.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1270.16 | 315.87 | 592.74 | 976.20 | 315.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2116.81 | 1189.42 | 1174.76 | 2448.36 | 1728.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.76 | 86.81 | 282.96 | 106.66 | 1265.93 | 0.00 | 0.00 | 0.00 |
February | 599.28 | 154.02 | 445.26 | 267.88 | 1192.16 | 0.00 | 0.00 | 0.00 |
March | 939.27 | 402.17 | 537.09 | 760.71 | 863.59 | 0.00 | 0.00 | 0.00 |
April | 1150.00 | 471.55 | 678.46 | 1088.47 | 643.99 | 0.00 | 0.00 | 0.00 |
May | 1356.61 | 613.10 | 743.51 | 1482.89 | 450.70 | 0.00 | 0.00 | 0.00 |
June | 1636.79 | 769.88 | 866.92 | 1995.93 | 305.87 | 0.00 | 0.00 | 0.00 |
July | 1463.36 | 641.58 | 821.77 | 1899.43 | 216.03 | 0.00 | 0.00 | 0.00 |
August | 1323.52 | 562.77 | 760.75 | 1690.19 | 272.47 | 0.00 | 0.00 | 0.00 |
September | 1039.37 | 448.86 | 590.51 | 1197.17 | 418.66 | 0.00 | 0.00 | 0.00 |
October | 673.77 | 237.34 | 436.43 | 598.07 | 635.10 | 0.00 | 0.00 | 0.00 |
November | 399.28 | 115.06 | 284.22 | 244.15 | 818.24 | 0.00 | 0.00 | 0.00 |
December | 346.14 | 75.42 | 270.72 | 102.72 | 1222.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 942.98 | 382.65 | 560.33 | 956.53 | 689.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 346.14 | 75.42 | 270.72 | 102.72 | 216.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1636.79 | 769.88 | 866.92 | 1995.93 | 1265.93 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.946153E+09 | 0.00 | 0.946153E+09 | 20444316.10 | 0.521154E+10 |
February | 0.130207E+10 | 0.00 | 0.130207E+10 | 0.109676E+09 | 0.438923E+10 |
March | 0.174823E+10 | 0.00 | 0.174823E+10 | 0.619878E+09 | 0.347409E+10 |
April | 0.215575E+10 | 8602286.50 | 0.214715E+10 | 0.124864E+10 | 0.236654E+10 |
May | 0.258837E+10 | 0.109762E+09 | 0.247861E+10 | 0.208721E+10 | 0.160374E+10 |
June | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.323503E+10 | 0.103988E+10 |
July | 0.288796E+10 | 0.186425E+09 | 0.270154E+10 | 0.355601E+10 | 0.764749E+09 |
August | 0.249889E+10 | 38015207.11 | 0.246088E+10 | 0.291613E+10 | 0.999184E+09 |
September | 0.184036E+10 | 382348.08 | 0.183998E+10 | 0.168877E+10 | 0.152662E+10 |
October | 0.142161E+10 | 0.00 | 0.142161E+10 | 0.770650E+09 | 0.241149E+10 |
November | 0.924471E+09 | 0.00 | 0.924471E+09 | 0.239308E+09 | 0.303590E+10 |
December | 0.885571E+09 | 0.00 | 0.885571E+09 | 22962625.61 | 0.493120E+10 |
Annual Sum or Average | 0.222123E+11 | 0.599654E+09 | 0.216126E+11 | 0.165147E+11 | 0.317542E+11 |
Minimum of Months | 0.885571E+09 | 0.00 | 0.885571E+09 | 20444316.10 | 0.764749E+09 |
Maximum of Months | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.355601E+10 | 0.521154E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115429E+10 | 0.372208E+09 | 0.782087E+09 | 0.471252E+09 | 0.315564E+10 |
February | 0.152980E+10 | 0.459053E+09 | 0.107074E+10 | 0.763469E+09 | 0.269546E+10 |
March | 0.243042E+10 | 0.101784E+10 | 0.141258E+10 | 0.194870E+10 | 0.213124E+10 |
April | 0.311304E+10 | 0.137551E+10 | 0.173754E+10 | 0.296902E+10 | 0.149936E+10 |
May | 0.360398E+10 | 0.159423E+10 | 0.200975E+10 | 0.390818E+10 | 0.107454E+10 |
June | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.468346E+10 | 0.693042E+09 |
July | 0.386509E+10 | 0.170174E+10 | 0.216335E+10 | 0.497625E+10 | 0.505207E+09 |
August | 0.349060E+10 | 0.146516E+10 | 0.202544E+10 | 0.440360E+10 | 0.651999E+09 |
September | 0.281108E+10 | 0.124689E+10 | 0.156420E+10 | 0.323292E+10 | 0.966808E+09 |
October | 0.197114E+10 | 0.815314E+09 | 0.115582E+10 | 0.181906E+10 | 0.151726E+10 |
November | 0.108200E+10 | 0.347092E+09 | 0.734907E+09 | 0.708068E+09 | 0.193310E+10 |
December | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.251837E+09 | 0.308723E+10 |
Annual Sum or Average | 0.298467E+11 | 0.123025E+11 | 0.175443E+11 | 0.301358E+11 | 0.199109E+11 |
Minimum of Months | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.251837E+09 | 0.505207E+09 |
Maximum of Months | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.497625E+10 | 0.315564E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406841E+10 | 0.237485E+10 | 0.169356E+10 | 0.333389E+10 | 0.445583E+10 |
February | 0.419558E+10 | 0.202307E+10 | 0.217251E+10 | 0.339778E+10 | 0.395151E+10 |
March | 0.566966E+10 | 0.318574E+10 | 0.248392E+10 | 0.559406E+10 | 0.322476E+10 |
April | 0.454391E+10 | 0.181575E+10 | 0.272815E+10 | 0.467959E+10 | 0.245692E+10 |
May | 0.410887E+10 | 0.119339E+10 | 0.291549E+10 | 0.456492E+10 | 0.175179E+10 |
June | 0.386371E+10 | 0.818736E+09 | 0.304498E+10 | 0.475844E+10 | 0.112510E+10 |
July | 0.407570E+10 | 0.988893E+09 | 0.308680E+10 | 0.552611E+10 | 0.818550E+09 |
August | 0.457564E+10 | 0.148353E+10 | 0.309210E+10 | 0.610656E+10 | 0.104725E+10 |
September | 0.514848E+10 | 0.250769E+10 | 0.264079E+10 | 0.636696E+10 | 0.155982E+10 |
October | 0.509054E+10 | 0.290781E+10 | 0.218273E+10 | 0.552123E+10 | 0.234719E+10 |
November | 0.352814E+10 | 0.199175E+10 | 0.153639E+10 | 0.338337E+10 | 0.288448E+10 |
December | 0.340200E+10 | 0.176068E+10 | 0.164131E+10 | 0.264952E+10 | 0.436092E+10 |
Annual Sum or Average | 0.522706E+11 | 0.230519E+11 | 0.292187E+11 | 0.558824E+11 | 0.299841E+11 |
Minimum of Months | 0.340200E+10 | 0.818736E+09 | 0.153639E+10 | 0.264952E+10 | 0.818550E+09 |
Maximum of Months | 0.566966E+10 | 0.318574E+10 | 0.309210E+10 | 0.636696E+10 | 0.445583E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990367E+09 | 0.232499E+09 | 0.757868E+09 | 0.293581E+09 | 0.327903E+10 |
February | 0.144978E+10 | 0.372603E+09 | 0.107718E+10 | 0.659636E+09 | 0.278493E+10 |
March | 0.251573E+10 | 0.107717E+10 | 0.143855E+10 | 0.205749E+10 | 0.219148E+10 |
April | 0.298081E+10 | 0.122225E+10 | 0.175856E+10 | 0.284399E+10 | 0.157108E+10 |
May | 0.363355E+10 | 0.164213E+10 | 0.199142E+10 | 0.398901E+10 | 0.114210E+10 |
June | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.517474E+10 | 0.760449E+09 |
July | 0.391945E+10 | 0.171842E+10 | 0.220103E+10 | 0.508194E+10 | 0.561661E+09 |
August | 0.354491E+10 | 0.150733E+10 | 0.203758E+10 | 0.453101E+10 | 0.699507E+09 |
September | 0.269405E+10 | 0.116344E+10 | 0.153061E+10 | 0.312311E+10 | 0.101717E+10 |
October | 0.180463E+10 | 0.635692E+09 | 0.116894E+10 | 0.163609E+10 | 0.157240E+10 |
November | 0.103493E+10 | 0.298230E+09 | 0.736702E+09 | 0.655422E+09 | 0.197268E+10 |
December | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.284354E+09 | 0.313864E+10 |
Annual Sum or Average | 0.297379E+11 | 0.120673E+11 | 0.176706E+11 | 0.303304E+11 | 0.206911E+11 |
Minimum of Months | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.284354E+09 | 0.561661E+09 |
Maximum of Months | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.517474E+10 | 0.327903E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315369E+09 | 0.00 | 0.315369E+09 | 4478192.36 | 0.177784E+10 |
February | 0.434004E+09 | 0.00 | 0.434004E+09 | 34785910.73 | 0.149750E+10 |
March | 0.582716E+09 | 0.00 | 0.582716E+09 | 0.216411E+09 | 0.117912E+10 |
April | 0.718548E+09 | 2867293.17 | 0.715681E+09 | 0.434578E+09 | 0.797163E+09 |
May | 0.862749E+09 | 36585443.19 | 0.826163E+09 | 0.728516E+09 | 0.523765E+09 |
June | 0.100423E+10 | 85485211.63 | 0.918745E+09 | 0.110197E+10 | 0.341172E+09 |
July | 0.962609E+09 | 62138579.50 | 0.900471E+09 | 0.120668E+10 | 0.248448E+09 |
August | 0.832924E+09 | 12671136.18 | 0.820253E+09 | 0.981257E+09 | 0.339227E+09 |
September | 0.613426E+09 | 127443.33 | 0.613298E+09 | 0.557674E+09 | 0.547671E+09 |
October | 0.473847E+09 | 0.00 | 0.473847E+09 | 0.235229E+09 | 0.899644E+09 |
November | 0.308142E+09 | 0.00 | 0.308142E+09 | 68689328.69 | 0.111191E+10 |
December | 0.295176E+09 | 0.00 | 0.295176E+09 | 5318333.94 | 0.172595E+10 |
Annual Sum or Average | 0.740374E+10 | 0.199875E+09 | 0.720387E+10 | 0.557558E+10 | 0.109894E+11 |
Minimum of Months | 0.295176E+09 | 0.00 | 0.295176E+09 | 4478192.36 | 0.248448E+09 |
Maximum of Months | 0.100423E+10 | 85485211.63 | 0.918745E+09 | 0.120668E+10 | 0.177784E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315389E+09 | 0.00 | 0.315389E+09 | 4478475.37 | 0.177795E+10 |
February | 0.434032E+09 | 0.00 | 0.434032E+09 | 34788109.14 | 0.149760E+10 |
March | 0.582753E+09 | 0.00 | 0.582753E+09 | 0.216425E+09 | 0.117920E+10 |
April | 0.718594E+09 | 2867474.38 | 0.715726E+09 | 0.434605E+09 | 0.797214E+09 |
May | 0.862803E+09 | 36587755.33 | 0.826215E+09 | 0.728562E+09 | 0.523798E+09 |
June | 0.100429E+10 | 85490614.15 | 0.918803E+09 | 0.110204E+10 | 0.341193E+09 |
July | 0.962670E+09 | 62142506.55 | 0.900527E+09 | 0.120675E+10 | 0.248463E+09 |
August | 0.832977E+09 | 12671936.97 | 0.820305E+09 | 0.981319E+09 | 0.339249E+09 |
September | 0.613465E+09 | 127451.38 | 0.613337E+09 | 0.557709E+09 | 0.547705E+09 |
October | 0.473877E+09 | 0.00 | 0.473877E+09 | 0.235244E+09 | 0.899701E+09 |
November | 0.308162E+09 | 0.00 | 0.308162E+09 | 68693669.75 | 0.111198E+10 |
December | 0.295195E+09 | 0.00 | 0.295195E+09 | 5318670.05 | 0.172606E+10 |
Annual Sum or Average | 0.740421E+10 | 0.199888E+09 | 0.720432E+10 | 0.557593E+10 | 0.109901E+11 |
Minimum of Months | 0.295195E+09 | 0.00 | 0.295195E+09 | 4478475.37 | 0.248463E+09 |
Maximum of Months | 0.100429E+10 | 85490614.15 | 0.918803E+09 | 0.120675E+10 | 0.177795E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315389E+09 | 0.00 | 0.315389E+09 | 4478475.37 | 0.177795E+10 |
February | 0.434032E+09 | 0.00 | 0.434032E+09 | 34788109.14 | 0.149760E+10 |
March | 0.582753E+09 | 0.00 | 0.582753E+09 | 0.216425E+09 | 0.117920E+10 |
April | 0.718594E+09 | 2867474.38 | 0.715726E+09 | 0.434605E+09 | 0.797214E+09 |
May | 0.862803E+09 | 36587755.33 | 0.826215E+09 | 0.728562E+09 | 0.523798E+09 |
June | 0.100429E+10 | 85490614.15 | 0.918803E+09 | 0.110204E+10 | 0.341193E+09 |
July | 0.962670E+09 | 62142506.55 | 0.900527E+09 | 0.120675E+10 | 0.248463E+09 |
August | 0.832977E+09 | 12671936.97 | 0.820305E+09 | 0.981319E+09 | 0.339249E+09 |
September | 0.613465E+09 | 127451.38 | 0.613337E+09 | 0.557709E+09 | 0.547705E+09 |
October | 0.473877E+09 | 0.00 | 0.473877E+09 | 0.235244E+09 | 0.899701E+09 |
November | 0.308162E+09 | 0.00 | 0.308162E+09 | 68693669.75 | 0.111198E+10 |
December | 0.295195E+09 | 0.00 | 0.295195E+09 | 5318670.05 | 0.172606E+10 |
Annual Sum or Average | 0.740421E+10 | 0.199888E+09 | 0.720432E+10 | 0.557593E+10 | 0.109901E+11 |
Minimum of Months | 0.295195E+09 | 0.00 | 0.295195E+09 | 4478475.37 | 0.248463E+09 |
Maximum of Months | 0.100429E+10 | 85490614.15 | 0.918803E+09 | 0.120675E+10 | 0.177795E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111038E+10 | 0.358048E+09 | 0.752335E+09 | 0.450878E+09 | 0.312306E+10 |
February | 0.147160E+10 | 0.441588E+09 | 0.103001E+10 | 0.735149E+09 | 0.266479E+10 |
March | 0.233796E+10 | 0.979117E+09 | 0.135884E+10 | 0.190271E+10 | 0.211294E+10 |
April | 0.299461E+10 | 0.132317E+10 | 0.167144E+10 | 0.289098E+10 | 0.149127E+10 |
May | 0.346688E+10 | 0.153358E+10 | 0.193330E+10 | 0.381378E+10 | 0.104541E+10 |
June | 0.374702E+10 | 0.165599E+10 | 0.209103E+10 | 0.454713E+10 | 0.679944E+09 |
July | 0.371806E+10 | 0.163700E+10 | 0.208106E+10 | 0.482439E+10 | 0.495971E+09 |
August | 0.335781E+10 | 0.140942E+10 | 0.194839E+10 | 0.425520E+10 | 0.661399E+09 |
September | 0.270414E+10 | 0.119945E+10 | 0.150470E+10 | 0.310162E+10 | 0.101972E+10 |
October | 0.189615E+10 | 0.784296E+09 | 0.111186E+10 | 0.170474E+10 | 0.163974E+10 |
November | 0.104084E+10 | 0.333887E+09 | 0.706950E+09 | 0.655635E+09 | 0.204484E+10 |
December | 0.865857E+09 | 0.178904E+09 | 0.686954E+09 | 0.234305E+09 | 0.312018E+10 |
Annual Sum or Average | 0.287113E+11 | 0.118344E+11 | 0.168769E+11 | 0.291165E+11 | 0.200993E+11 |
Minimum of Months | 0.865857E+09 | 0.178904E+09 | 0.686954E+09 | 0.234305E+09 | 0.495971E+09 |
Maximum of Months | 0.374702E+10 | 0.165599E+10 | 0.209103E+10 | 0.482439E+10 | 0.312306E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43903514.79 | 14156881.25 | 29746633.54 | 17827302.18 | 0.123483E+09 |
February | 58185660.24 | 17459998.40 | 40725661.84 | 29067115.16 | 0.105363E+09 |
March | 92440707.43 | 38713399.14 | 53727308.29 | 75231256.99 | 83543564.03 |
April | 0.118404E+09 | 52317124.53 | 66087160.98 | 0.114307E+09 | 58963437.11 |
May | 0.137077E+09 | 60636233.07 | 76440911.68 | 0.150794E+09 | 41334601.05 |
June | 0.148154E+09 | 65476269.95 | 82677404.89 | 0.179790E+09 | 26884375.40 |
July | 0.147009E+09 | 64725484.45 | 82283095.85 | 0.190752E+09 | 19610255.54 |
August | 0.132765E+09 | 55727151.14 | 77037725.17 | 0.168247E+09 | 26151134.00 |
September | 0.106919E+09 | 47425110.79 | 59494289.32 | 0.122635E+09 | 40318838.31 |
October | 74972114.35 | 31010342.74 | 43961771.61 | 67403981.89 | 64833706.68 |
November | 41153735.66 | 13201580.22 | 27952155.44 | 25923235.10 | 80851156.15 |
December | 34235223.81 | 7073698.31 | 27161525.50 | 9264207.87 | 0.123369E+09 |
Annual Sum or Average | 0.113522E+10 | 0.467923E+09 | 0.667296E+09 | 0.115124E+10 | 0.794706E+09 |
Minimum of Months | 34235223.81 | 7073698.31 | 27161525.50 | 9264207.87 | 19610255.54 |
Maximum of Months | 0.148154E+09 | 65476269.95 | 82677404.89 | 0.190752E+09 | 0.123483E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135618E+10 | 0.791641E+09 | 0.564537E+09 | 0.113680E+10 | 0.150020E+10 |
February | 0.139857E+10 | 0.674378E+09 | 0.724191E+09 | 0.116523E+10 | 0.132631E+10 |
March | 0.188994E+10 | 0.106195E+10 | 0.827996E+09 | 0.191306E+10 | 0.110519E+10 |
April | 0.151468E+10 | 0.605271E+09 | 0.909410E+09 | 0.160076E+10 | 0.830874E+09 |
May | 0.136966E+10 | 0.397808E+09 | 0.971856E+09 | 0.157147E+10 | 0.572192E+09 |
June | 0.128794E+10 | 0.272921E+09 | 0.101502E+10 | 0.162396E+10 | 0.368985E+09 |
July | 0.135860E+10 | 0.329642E+09 | 0.102896E+10 | 0.186762E+10 | 0.272254E+09 |
August | 0.152526E+10 | 0.494527E+09 | 0.103073E+10 | 0.205213E+10 | 0.365104E+09 |
September | 0.171621E+10 | 0.835923E+09 | 0.880290E+09 | 0.212930E+10 | 0.569511E+09 |
October | 0.169690E+10 | 0.969302E+09 | 0.727598E+09 | 0.184146E+10 | 0.874471E+09 |
November | 0.117608E+10 | 0.663938E+09 | 0.512144E+09 | 0.112653E+10 | 0.105349E+10 |
December | 0.113403E+10 | 0.586914E+09 | 0.547120E+09 | 0.894292E+09 | 0.149909E+10 |
Annual Sum or Average | 0.174241E+11 | 0.768421E+10 | 0.973985E+10 | 0.189226E+11 | 0.103377E+11 |
Minimum of Months | 0.113403E+10 | 0.272921E+09 | 0.512144E+09 | 0.894292E+09 | 0.272254E+09 |
Maximum of Months | 0.188994E+10 | 0.106195E+10 | 0.103073E+10 | 0.212930E+10 | 0.150020E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135618E+10 | 0.791641E+09 | 0.564537E+09 | 0.113680E+10 | 0.150020E+10 |
February | 0.139857E+10 | 0.674378E+09 | 0.724191E+09 | 0.116523E+10 | 0.132631E+10 |
March | 0.188994E+10 | 0.106195E+10 | 0.827996E+09 | 0.191306E+10 | 0.110519E+10 |
April | 0.151468E+10 | 0.605271E+09 | 0.909410E+09 | 0.160076E+10 | 0.830874E+09 |
May | 0.136966E+10 | 0.397808E+09 | 0.971856E+09 | 0.157147E+10 | 0.572192E+09 |
June | 0.128794E+10 | 0.272921E+09 | 0.101502E+10 | 0.162396E+10 | 0.368985E+09 |
July | 0.135860E+10 | 0.329642E+09 | 0.102896E+10 | 0.186762E+10 | 0.272254E+09 |
August | 0.152526E+10 | 0.494527E+09 | 0.103073E+10 | 0.205213E+10 | 0.365104E+09 |
September | 0.171621E+10 | 0.835923E+09 | 0.880290E+09 | 0.212930E+10 | 0.569511E+09 |
October | 0.169690E+10 | 0.969302E+09 | 0.727598E+09 | 0.184146E+10 | 0.874471E+09 |
November | 0.117608E+10 | 0.663938E+09 | 0.512144E+09 | 0.112653E+10 | 0.105349E+10 |
December | 0.113403E+10 | 0.586914E+09 | 0.547120E+09 | 0.894292E+09 | 0.149909E+10 |
Annual Sum or Average | 0.174241E+11 | 0.768421E+10 | 0.973985E+10 | 0.189226E+11 | 0.103377E+11 |
Minimum of Months | 0.113403E+10 | 0.272921E+09 | 0.512144E+09 | 0.894292E+09 | 0.272254E+09 |
Maximum of Months | 0.188994E+10 | 0.106195E+10 | 0.103073E+10 | 0.212930E+10 | 0.150020E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135609E+10 | 0.791591E+09 | 0.564501E+09 | 0.113673E+10 | 0.150011E+10 |
February | 0.139848E+10 | 0.674335E+09 | 0.724145E+09 | 0.116516E+10 | 0.132623E+10 |
March | 0.188982E+10 | 0.106188E+10 | 0.827944E+09 | 0.191294E+10 | 0.110512E+10 |
April | 0.151459E+10 | 0.605233E+09 | 0.909353E+09 | 0.160066E+10 | 0.830821E+09 |
May | 0.136958E+10 | 0.397783E+09 | 0.971794E+09 | 0.157137E+10 | 0.572156E+09 |
June | 0.128786E+10 | 0.272904E+09 | 0.101496E+10 | 0.162386E+10 | 0.368962E+09 |
July | 0.135852E+10 | 0.329621E+09 | 0.102890E+10 | 0.186751E+10 | 0.272236E+09 |
August | 0.152516E+10 | 0.494495E+09 | 0.103066E+10 | 0.205200E+10 | 0.365081E+09 |
September | 0.171610E+10 | 0.835870E+09 | 0.880234E+09 | 0.212917E+10 | 0.569475E+09 |
October | 0.169679E+10 | 0.969241E+09 | 0.727552E+09 | 0.184134E+10 | 0.874416E+09 |
November | 0.117601E+10 | 0.663896E+09 | 0.512112E+09 | 0.112646E+10 | 0.105342E+10 |
December | 0.113396E+10 | 0.586877E+09 | 0.547085E+09 | 0.894235E+09 | 0.149899E+10 |
Annual Sum or Average | 0.174230E+11 | 0.768373E+10 | 0.973924E+10 | 0.189214E+11 | 0.103370E+11 |
Minimum of Months | 0.113396E+10 | 0.272904E+09 | 0.512112E+09 | 0.894235E+09 | 0.272236E+09 |
Maximum of Months | 0.188982E+10 | 0.106188E+10 | 0.103066E+10 | 0.212917E+10 | 0.150011E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.952691E+09 | 0.223654E+09 | 0.729038E+09 | 0.283548E+09 | 0.323151E+10 |
February | 0.139463E+10 | 0.358428E+09 | 0.103620E+10 | 0.645023E+09 | 0.274720E+10 |
March | 0.242002E+10 | 0.103619E+10 | 0.138383E+10 | 0.201952E+10 | 0.217702E+10 |
April | 0.286741E+10 | 0.117575E+10 | 0.169166E+10 | 0.278264E+10 | 0.155802E+10 |
May | 0.349532E+10 | 0.157965E+10 | 0.191567E+10 | 0.389236E+10 | 0.111439E+10 |
June | 0.408117E+10 | 0.191961E+10 | 0.216157E+10 | 0.501829E+10 | 0.753220E+09 |
July | 0.377035E+10 | 0.165304E+10 | 0.211731E+10 | 0.492207E+10 | 0.553910E+09 |
August | 0.341006E+10 | 0.144998E+10 | 0.196007E+10 | 0.436908E+10 | 0.713878E+09 |
September | 0.259156E+10 | 0.111918E+10 | 0.147239E+10 | 0.298957E+10 | 0.107284E+10 |
October | 0.173598E+10 | 0.611507E+09 | 0.112447E+10 | 0.154139E+10 | 0.168846E+10 |
November | 0.995560E+09 | 0.286884E+09 | 0.708677E+09 | 0.611182E+09 | 0.208183E+10 |
December | 0.891831E+09 | 0.194319E+09 | 0.697512E+09 | 0.269531E+09 | 0.316668E+10 |
Annual Sum or Average | 0.286066E+11 | 0.116082E+11 | 0.169984E+11 | 0.293442E+11 | 0.208590E+11 |
Minimum of Months | 0.891831E+09 | 0.194319E+09 | 0.697512E+09 | 0.269531E+09 | 0.553910E+09 |
Maximum of Months | 0.408117E+10 | 0.191961E+10 | 0.216157E+10 | 0.501829E+10 | 0.323151E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 37668460.14 | 8843030.56 | 28825429.57 | 11211147.51 | 0.127771E+09 |
February | 55142120.25 | 14171855.93 | 40970264.32 | 25503495.68 | 0.108622E+09 |
March | 95685262.75 | 40969997.94 | 54715264.81 | 79849550.80 | 86077481.09 |
April | 0.113375E+09 | 46487891.17 | 66886647.07 | 0.110023E+09 | 61602553.25 |
May | 0.138201E+09 | 62457813.59 | 75743682.49 | 0.153900E+09 | 44061882.73 |
June | 0.161365E+09 | 75899229.23 | 85466195.70 | 0.198418E+09 | 29781626.87 |
July | 0.149076E+09 | 65359562.17 | 83716159.64 | 0.194614E+09 | 21901097.25 |
August | 0.134830E+09 | 57330775.70 | 77499368.98 | 0.172749E+09 | 28226087.34 |
September | 0.102468E+09 | 44251178.65 | 58216688.67 | 0.118205E+09 | 42419158.91 |
October | 68638732.25 | 24178368.51 | 44460363.74 | 60944978.59 | 66760302.29 |
November | 39363456.75 | 11343086.90 | 28020369.85 | 24165489.84 | 82313737.84 |
December | 35262090.87 | 7683177.17 | 27578913.71 | 10656924.54 | 0.125208E+09 |
Annual Sum or Average | 0.113108E+10 | 0.458976E+09 | 0.672099E+09 | 0.116024E+10 | 0.824744E+09 |
Minimum of Months | 35262090.87 | 7683177.17 | 27578913.71 | 10656924.54 | 21901097.25 |
Maximum of Months | 0.161365E+09 | 75899229.23 | 85466195.70 | 0.198418E+09 | 0.127771E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.946153E+09 | 0.00 | 0.946153E+09 | 13486613.18 | 0.538887E+10 |
February | 0.130207E+10 | 0.00 | 0.130207E+10 | 95349515.40 | 0.454844E+10 |
March | 0.174823E+10 | 0.00 | 0.174823E+10 | 0.590226E+09 | 0.366423E+10 |
April | 0.215575E+10 | 8602286.50 | 0.214715E+10 | 0.119910E+10 | 0.252832E+10 |
May | 0.258837E+10 | 0.109762E+09 | 0.247861E+10 | 0.204219E+10 | 0.170124E+10 |
June | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.322373E+10 | 0.108150E+10 |
July | 0.288796E+10 | 0.186425E+09 | 0.270154E+10 | 0.356000E+10 | 0.785921E+09 |
August | 0.249889E+10 | 38015207.11 | 0.246088E+10 | 0.290895E+10 | 0.104267E+10 |
September | 0.184036E+10 | 382348.08 | 0.183998E+10 | 0.165634E+10 | 0.163825E+10 |
October | 0.142161E+10 | 0.00 | 0.142161E+10 | 0.711685E+09 | 0.262817E+10 |
November | 0.924471E+09 | 0.00 | 0.924471E+09 | 0.208197E+09 | 0.327625E+10 |
December | 0.885571E+09 | 0.00 | 0.885571E+09 | 16214210.59 | 0.515006E+10 |
Annual Sum or Average | 0.222123E+11 | 0.599654E+09 | 0.216126E+11 | 0.162255E+11 | 0.334339E+11 |
Minimum of Months | 0.885571E+09 | 0.00 | 0.885571E+09 | 13486613.18 | 0.785921E+09 |
Maximum of Months | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.356000E+10 | 0.538887E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115429E+10 | 0.372208E+09 | 0.782087E+09 | 0.458705E+09 | 0.326657E+10 |
February | 0.152980E+10 | 0.459053E+09 | 0.107074E+10 | 0.744642E+09 | 0.279169E+10 |
March | 0.243042E+10 | 0.101784E+10 | 0.141258E+10 | 0.192201E+10 | 0.224559E+10 |
April | 0.311304E+10 | 0.137551E+10 | 0.173754E+10 | 0.293985E+10 | 0.158759E+10 |
May | 0.360398E+10 | 0.159423E+10 | 0.200975E+10 | 0.389304E+10 | 0.112918E+10 |
June | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.468510E+10 | 0.717381E+09 |
July | 0.386509E+10 | 0.170174E+10 | 0.216335E+10 | 0.498607E+10 | 0.516575E+09 |
August | 0.349060E+10 | 0.146516E+10 | 0.202544E+10 | 0.440551E+10 | 0.676352E+09 |
September | 0.281108E+10 | 0.124689E+10 | 0.156420E+10 | 0.321733E+10 | 0.102476E+10 |
October | 0.197114E+10 | 0.815314E+09 | 0.115582E+10 | 0.177875E+10 | 0.163710E+10 |
November | 0.108200E+10 | 0.347092E+09 | 0.734907E+09 | 0.681409E+09 | 0.207772E+10 |
December | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.240550E+09 | 0.322270E+10 |
Annual Sum or Average | 0.298467E+11 | 0.123025E+11 | 0.175443E+11 | 0.299530E+11 | 0.208932E+11 |
Minimum of Months | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.240550E+09 | 0.516575E+09 |
Maximum of Months | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.498607E+10 | 0.326657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406841E+10 | 0.237485E+10 | 0.169356E+10 | 0.330213E+10 | 0.462844E+10 |
February | 0.419558E+10 | 0.202307E+10 | 0.217251E+10 | 0.336460E+10 | 0.410415E+10 |
March | 0.566966E+10 | 0.318574E+10 | 0.248392E+10 | 0.555162E+10 | 0.340790E+10 |
April | 0.454391E+10 | 0.181575E+10 | 0.272815E+10 | 0.464019E+10 | 0.260963E+10 |
May | 0.410887E+10 | 0.119339E+10 | 0.291549E+10 | 0.454018E+10 | 0.185503E+10 |
June | 0.386371E+10 | 0.818736E+09 | 0.304498E+10 | 0.475707E+10 | 0.117584E+10 |
July | 0.407570E+10 | 0.988893E+09 | 0.308680E+10 | 0.553602E+10 | 0.845524E+09 |
August | 0.457564E+10 | 0.148353E+10 | 0.309210E+10 | 0.610715E+10 | 0.109439E+10 |
September | 0.514848E+10 | 0.250769E+10 | 0.264079E+10 | 0.634615E+10 | 0.166159E+10 |
October | 0.509054E+10 | 0.290781E+10 | 0.218273E+10 | 0.546179E+10 | 0.253935E+10 |
November | 0.352814E+10 | 0.199175E+10 | 0.153639E+10 | 0.333276E+10 | 0.310444E+10 |
December | 0.340200E+10 | 0.176068E+10 | 0.164131E+10 | 0.261467E+10 | 0.456263E+10 |
Annual Sum or Average | 0.522706E+11 | 0.230519E+11 | 0.292187E+11 | 0.555543E+11 | 0.315889E+11 |
Minimum of Months | 0.340200E+10 | 0.818736E+09 | 0.153639E+10 | 0.261467E+10 | 0.845524E+09 |
Maximum of Months | 0.566966E+10 | 0.318574E+10 | 0.309210E+10 | 0.634615E+10 | 0.462844E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990367E+09 | 0.232499E+09 | 0.757868E+09 | 0.285678E+09 | 0.339067E+10 |
February | 0.144978E+10 | 0.372603E+09 | 0.107718E+10 | 0.648055E+09 | 0.288407E+10 |
March | 0.251573E+10 | 0.107717E+10 | 0.143855E+10 | 0.203748E+10 | 0.231303E+10 |
April | 0.298081E+10 | 0.122225E+10 | 0.175856E+10 | 0.282132E+10 | 0.166921E+10 |
May | 0.363355E+10 | 0.164213E+10 | 0.199142E+10 | 0.397176E+10 | 0.120716E+10 |
June | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.517346E+10 | 0.792814E+09 |
July | 0.391945E+10 | 0.171842E+10 | 0.220103E+10 | 0.508742E+10 | 0.578604E+09 |
August | 0.354491E+10 | 0.150733E+10 | 0.203758E+10 | 0.452702E+10 | 0.729778E+09 |
September | 0.269405E+10 | 0.116344E+10 | 0.153061E+10 | 0.310306E+10 | 0.108517E+10 |
October | 0.180463E+10 | 0.635692E+09 | 0.116894E+10 | 0.160188E+10 | 0.170106E+10 |
November | 0.103493E+10 | 0.298230E+09 | 0.736702E+09 | 0.632847E+09 | 0.212087E+10 |
December | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.275123E+09 | 0.327495E+10 |
Annual Sum or Average | 0.297379E+11 | 0.120673E+11 | 0.176706E+11 | 0.301651E+11 | 0.217474E+11 |
Minimum of Months | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.275123E+09 | 0.578604E+09 |
Maximum of Months | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.517346E+10 | 0.339067E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.63 | 1945.76 | 353.25 | 0.00 | 353.25 | 0.00 | 0.00 |
February | 45.34 | 1814.33 | 538.23 | 0.00 | 538.23 | 0.00 | 0.00 |
March | 231.44 | 1297.07 | 652.71 | 0.00 | 652.71 | 0.00 | 0.00 |
April | 481.73 | 913.02 | 831.69 | 3.32 | 828.37 | 0.00 | 0.00 |
May | 779.27 | 598.77 | 966.39 | 40.98 | 925.41 | 0.00 | 0.00 |
June | 1248.08 | 401.19 | 1162.36 | 98.95 | 1063.41 | 0.00 | 0.00 |
July | 1327.66 | 285.52 | 1078.24 | 69.60 | 1008.64 | 0.00 | 0.00 |
August | 1088.76 | 373.05 | 932.98 | 14.19 | 918.79 | 0.00 | 0.00 |
September | 651.53 | 588.97 | 710.02 | 0.15 | 709.87 | 0.00 | 0.00 |
October | 287.73 | 900.35 | 530.77 | 0.00 | 530.77 | 0.00 | 0.00 |
November | 92.33 | 1171.26 | 356.66 | 0.00 | 356.66 | 0.00 | 0.00 |
December | 8.57 | 1841.10 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Annual Sum or Average | 523.68 | 1006.92 | 704.35 | 19.01 | 685.33 | 0.00 | 0.00 |
Minimum of Months | 7.63 | 285.52 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Maximum of Months | 1327.66 | 1945.76 | 1162.36 | 98.95 | 1063.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.95 | 1178.18 | 430.96 | 138.97 | 292.00 | 0.00 | 0.00 |
February | 315.59 | 1114.19 | 632.36 | 189.75 | 442.60 | 0.00 | 0.00 |
March | 727.56 | 795.71 | 907.41 | 380.02 | 527.40 | 0.00 | 0.00 |
April | 1145.46 | 578.46 | 1201.02 | 530.67 | 670.35 | 0.00 | 0.00 |
May | 1459.15 | 401.19 | 1345.57 | 595.22 | 750.36 | 0.00 | 0.00 |
June | 1806.89 | 267.38 | 1502.78 | 664.15 | 838.63 | 0.00 | 0.00 |
July | 1857.92 | 188.62 | 1443.06 | 635.36 | 807.70 | 0.00 | 0.00 |
August | 1644.12 | 243.43 | 1303.24 | 547.03 | 756.21 | 0.00 | 0.00 |
September | 1247.27 | 373.00 | 1084.52 | 481.05 | 603.47 | 0.00 | 0.00 |
October | 679.16 | 566.48 | 735.94 | 304.40 | 431.54 | 0.00 | 0.00 |
November | 273.17 | 745.79 | 417.44 | 133.91 | 283.53 | 0.00 | 0.00 |
December | 94.03 | 1152.64 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Annual Sum or Average | 955.60 | 631.37 | 946.43 | 390.11 | 556.32 | 0.00 | 0.00 |
Minimum of Months | 94.03 | 188.62 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Maximum of Months | 1857.92 | 1178.18 | 1502.78 | 664.15 | 838.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1244.73 | 1663.62 | 1518.97 | 886.67 | 632.30 | 0.00 | 0.00 |
February | 1404.50 | 1633.40 | 1734.28 | 836.25 | 898.03 | 0.00 | 0.00 |
March | 2088.58 | 1203.99 | 2116.81 | 1189.42 | 927.39 | 0.00 | 0.00 |
April | 1805.40 | 947.89 | 1753.05 | 700.52 | 1052.53 | 0.00 | 0.00 |
May | 1704.35 | 654.04 | 1534.08 | 445.56 | 1088.52 | 0.00 | 0.00 |
June | 1835.82 | 434.07 | 1490.63 | 315.87 | 1174.76 | 0.00 | 0.00 |
July | 2063.21 | 305.61 | 1521.69 | 369.21 | 1152.48 | 0.00 | 0.00 |
August | 2279.93 | 391.00 | 1708.35 | 553.89 | 1154.46 | 0.00 | 0.00 |
September | 2456.39 | 601.78 | 1986.30 | 967.47 | 1018.82 | 0.00 | 0.00 |
October | 2061.39 | 876.34 | 1900.59 | 1085.65 | 814.94 | 0.00 | 0.00 |
November | 1305.31 | 1112.84 | 1361.16 | 768.42 | 592.74 | 0.00 | 0.00 |
December | 989.22 | 1628.18 | 1270.16 | 657.36 | 612.80 | 0.00 | 0.00 |
Annual Sum or Average | 1772.02 | 950.79 | 1657.49 | 730.97 | 926.52 | 0.00 | 0.00 |
Minimum of Months | 989.22 | 305.61 | 1270.16 | 315.87 | 592.74 | 0.00 | 0.00 |
Maximum of Months | 2456.39 | 1663.62 | 2116.81 | 1189.42 | 1174.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.61 | 1224.25 | 369.76 | 86.81 | 282.96 | 0.00 | 0.00 |
February | 272.67 | 1151.18 | 599.28 | 154.02 | 445.26 | 0.00 | 0.00 |
March | 768.18 | 818.20 | 939.27 | 402.17 | 537.09 | 0.00 | 0.00 |
April | 1097.22 | 606.12 | 1150.00 | 471.55 | 678.46 | 0.00 | 0.00 |
May | 1489.32 | 426.41 | 1356.61 | 613.10 | 743.51 | 0.00 | 0.00 |
June | 1996.43 | 293.38 | 1636.79 | 769.88 | 866.92 | 0.00 | 0.00 |
July | 1897.38 | 209.70 | 1463.36 | 641.58 | 821.77 | 0.00 | 0.00 |
August | 1691.68 | 261.17 | 1323.52 | 562.77 | 760.75 | 0.00 | 0.00 |
September | 1204.90 | 392.43 | 1039.37 | 448.86 | 590.51 | 0.00 | 0.00 |
October | 610.85 | 587.07 | 673.77 | 237.34 | 436.43 | 0.00 | 0.00 |
November | 252.86 | 761.07 | 399.28 | 115.06 | 284.22 | 0.00 | 0.00 |
December | 106.17 | 1171.83 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Annual Sum or Average | 961.77 | 656.11 | 942.98 | 382.65 | 560.33 | 0.00 | 0.00 |
Minimum of Months | 106.17 | 209.70 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Maximum of Months | 1996.43 | 1224.25 | 1636.79 | 769.88 | 866.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.02 | 1991.39 | 353.25 | 0.00 | 353.25 | 0.00 | 0.00 |
February | 43.14 | 1857.10 | 538.22 | 0.00 | 538.22 | 0.00 | 0.00 |
March | 242.41 | 1320.76 | 652.71 | 0.00 | 652.71 | 0.00 | 0.00 |
April | 503.00 | 922.68 | 831.69 | 3.32 | 828.37 | 0.00 | 0.00 |
May | 816.02 | 586.68 | 966.38 | 40.98 | 925.40 | 0.00 | 0.00 |
June | 1275.48 | 394.89 | 1162.35 | 98.95 | 1063.41 | 0.00 | 0.00 |
July | 1351.62 | 278.29 | 1078.24 | 69.60 | 1008.63 | 0.00 | 0.00 |
August | 1099.12 | 379.97 | 932.97 | 14.19 | 918.78 | 0.00 | 0.00 |
September | 645.48 | 633.90 | 710.01 | 0.15 | 709.87 | 0.00 | 0.00 |
October | 263.48 | 1007.71 | 530.77 | 0.00 | 530.77 | 0.00 | 0.00 |
November | 79.50 | 1286.98 | 356.66 | 0.00 | 356.66 | 0.00 | 0.00 |
December | 5.96 | 1933.27 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Annual Sum or Average | 530.42 | 1045.46 | 704.34 | 19.01 | 685.33 | 0.00 | 0.00 |
Minimum of Months | 5.02 | 278.29 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Maximum of Months | 1351.62 | 1991.39 | 1162.35 | 98.95 | 1063.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.99 | 1212.12 | 430.96 | 138.97 | 292.00 | 0.00 | 0.00 |
February | 315.90 | 1145.07 | 632.35 | 189.75 | 442.60 | 0.00 | 0.00 |
March | 738.48 | 820.07 | 907.41 | 380.01 | 527.39 | 0.00 | 0.00 |
April | 1159.45 | 598.08 | 1201.01 | 530.67 | 670.34 | 0.00 | 0.00 |
May | 1480.20 | 405.74 | 1345.56 | 595.21 | 750.35 | 0.00 | 0.00 |
June | 1823.66 | 272.70 | 1502.77 | 664.15 | 838.62 | 0.00 | 0.00 |
July | 1872.44 | 192.50 | 1443.05 | 635.35 | 807.70 | 0.00 | 0.00 |
August | 1651.53 | 256.70 | 1303.23 | 547.02 | 756.21 | 0.00 | 0.00 |
September | 1243.93 | 408.97 | 1084.52 | 481.05 | 603.47 | 0.00 | 0.00 |
October | 661.64 | 636.41 | 735.93 | 304.40 | 431.53 | 0.00 | 0.00 |
November | 262.95 | 820.10 | 417.43 | 133.91 | 283.53 | 0.00 | 0.00 |
December | 90.94 | 1211.00 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Annual Sum or Average | 959.78 | 662.54 | 946.43 | 390.11 | 556.32 | 0.00 | 0.00 |
Minimum of Months | 90.94 | 192.50 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Maximum of Months | 1872.44 | 1212.12 | 1502.77 | 664.15 | 838.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1273.28 | 1680.30 | 1518.99 | 886.68 | 632.31 | 0.00 | 0.00 |
February | 1444.95 | 1644.70 | 1734.30 | 836.26 | 898.04 | 0.00 | 0.00 |
March | 2142.72 | 1237.87 | 2116.83 | 1189.43 | 927.40 | 0.00 | 0.00 |
April | 1852.69 | 961.64 | 1753.07 | 700.53 | 1052.54 | 0.00 | 0.00 |
May | 1760.12 | 640.88 | 1534.09 | 445.56 | 1088.53 | 0.00 | 0.00 |
June | 1879.54 | 427.06 | 1490.64 | 315.87 | 1174.77 | 0.00 | 0.00 |
July | 2091.83 | 304.94 | 1521.70 | 369.21 | 1152.49 | 0.00 | 0.00 |
August | 2298.49 | 408.93 | 1708.36 | 553.89 | 1154.47 | 0.00 | 0.00 |
September | 2464.42 | 659.14 | 1986.32 | 967.48 | 1018.83 | 0.00 | 0.00 |
October | 2062.52 | 979.45 | 1900.61 | 1085.66 | 814.94 | 0.00 | 0.00 |
November | 1303.83 | 1219.29 | 1361.18 | 768.43 | 592.75 | 0.00 | 0.00 |
December | 1001.65 | 1679.05 | 1270.17 | 657.37 | 612.80 | 0.00 | 0.00 |
Annual Sum or Average | 1800.06 | 983.40 | 1657.51 | 730.98 | 926.53 | 0.00 | 0.00 |
Minimum of Months | 1001.65 | 304.94 | 1270.17 | 315.87 | 592.75 | 0.00 | 0.00 |
Maximum of Months | 2464.42 | 1680.30 | 2116.83 | 1189.43 | 1174.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 110.05 | 1254.21 | 369.76 | 86.80 | 282.95 | 0.00 | 0.00 |
February | 277.17 | 1180.48 | 599.28 | 154.02 | 445.26 | 0.00 | 0.00 |
March | 783.81 | 844.94 | 939.26 | 402.17 | 537.09 | 0.00 | 0.00 |
April | 1116.00 | 624.85 | 1149.99 | 471.54 | 678.45 | 0.00 | 0.00 |
May | 1510.70 | 432.52 | 1356.60 | 613.09 | 743.51 | 0.00 | 0.00 |
June | 2012.62 | 302.08 | 1636.78 | 769.87 | 866.91 | 0.00 | 0.00 |
July | 1910.35 | 214.98 | 1463.34 | 641.58 | 821.77 | 0.00 | 0.00 |
August | 1695.73 | 277.07 | 1323.51 | 562.77 | 760.74 | 0.00 | 0.00 |
September | 1198.99 | 430.27 | 1039.36 | 448.85 | 590.51 | 0.00 | 0.00 |
October | 598.24 | 655.33 | 673.77 | 237.34 | 436.43 | 0.00 | 0.00 |
November | 245.12 | 834.93 | 399.28 | 115.06 | 284.22 | 0.00 | 0.00 |
December | 104.61 | 1229.05 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Annual Sum or Average | 967.29 | 687.59 | 942.97 | 382.65 | 560.33 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 214.98 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Maximum of Months | 2012.62 | 1254.21 | 1636.78 | 769.87 | 866.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.04 | 2011.98 | 353.25 | 0.00 | 353.25 | 0.00 | 0.00 |
February | 39.41 | 1880.14 | 538.23 | 0.00 | 538.23 | 0.00 | 0.00 |
March | 220.37 | 1368.07 | 652.71 | 0.00 | 652.71 | 0.00 | 0.00 |
April | 462.62 | 975.43 | 831.69 | 3.32 | 828.37 | 0.00 | 0.00 |
May | 762.47 | 635.17 | 966.39 | 40.98 | 925.41 | 0.00 | 0.00 |
June | 1243.72 | 417.25 | 1162.36 | 98.95 | 1063.41 | 0.00 | 0.00 |
July | 1329.15 | 293.43 | 1078.24 | 69.60 | 1008.64 | 0.00 | 0.00 |
August | 1086.08 | 389.29 | 932.98 | 14.19 | 918.79 | 0.00 | 0.00 |
September | 639.02 | 632.04 | 710.02 | 0.15 | 709.87 | 0.00 | 0.00 |
October | 265.71 | 981.24 | 530.77 | 0.00 | 530.77 | 0.00 | 0.00 |
November | 80.32 | 1263.99 | 356.66 | 0.00 | 356.66 | 0.00 | 0.00 |
December | 6.05 | 1922.81 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Annual Sum or Average | 514.51 | 1060.18 | 704.35 | 19.01 | 685.33 | 0.00 | 0.00 |
Minimum of Months | 5.04 | 293.43 | 330.63 | 0.00 | 330.63 | 0.00 | 0.00 |
Maximum of Months | 1329.15 | 2011.98 | 1162.36 | 98.95 | 1063.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.26 | 1219.60 | 430.96 | 138.97 | 292.00 | 0.00 | 0.00 |
February | 307.81 | 1153.97 | 632.36 | 189.75 | 442.60 | 0.00 | 0.00 |
March | 717.60 | 838.41 | 907.41 | 380.02 | 527.40 | 0.00 | 0.00 |
April | 1134.20 | 612.50 | 1201.02 | 530.67 | 670.35 | 0.00 | 0.00 |
May | 1453.50 | 421.59 | 1345.57 | 595.22 | 750.36 | 0.00 | 0.00 |
June | 1807.52 | 276.77 | 1502.78 | 664.15 | 838.63 | 0.00 | 0.00 |
July | 1861.58 | 192.87 | 1443.06 | 635.36 | 807.70 | 0.00 | 0.00 |
August | 1644.83 | 252.52 | 1303.24 | 547.03 | 756.21 | 0.00 | 0.00 |
September | 1241.25 | 395.36 | 1084.52 | 481.05 | 603.47 | 0.00 | 0.00 |
October | 664.11 | 611.22 | 735.94 | 304.40 | 431.54 | 0.00 | 0.00 |
November | 262.89 | 801.59 | 417.44 | 133.91 | 283.53 | 0.00 | 0.00 |
December | 89.81 | 1203.22 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Annual Sum or Average | 949.80 | 662.52 | 946.43 | 390.11 | 556.32 | 0.00 | 0.00 |
Minimum of Months | 89.81 | 192.87 | 336.06 | 69.44 | 266.62 | 0.00 | 0.00 |
Maximum of Months | 1861.58 | 1219.60 | 1502.78 | 664.15 | 838.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1232.87 | 1728.06 | 1518.97 | 886.67 | 632.30 | 0.00 | 0.00 |
February | 1390.79 | 1696.49 | 1734.28 | 836.25 | 898.03 | 0.00 | 0.00 |
March | 2072.74 | 1272.37 | 2116.81 | 1189.42 | 927.39 | 0.00 | 0.00 |
April | 1790.20 | 1006.80 | 1753.05 | 700.52 | 1052.53 | 0.00 | 0.00 |
May | 1695.11 | 692.59 | 1534.08 | 445.56 | 1088.52 | 0.00 | 0.00 |
June | 1835.29 | 453.64 | 1490.63 | 315.87 | 1174.76 | 0.00 | 0.00 |
July | 2066.91 | 315.68 | 1521.69 | 369.21 | 1152.48 | 0.00 | 0.00 |
August | 2280.15 | 408.60 | 1708.35 | 553.89 | 1154.46 | 0.00 | 0.00 |
September | 2448.36 | 641.05 | 1986.30 | 967.47 | 1018.82 | 0.00 | 0.00 |
October | 2039.20 | 948.09 | 1900.59 | 1085.65 | 814.94 | 0.00 | 0.00 |
November | 1285.79 | 1197.70 | 1361.16 | 768.42 | 592.74 | 0.00 | 0.00 |
December | 976.20 | 1703.49 | 1270.16 | 657.36 | 612.80 | 0.00 | 0.00 |
Annual Sum or Average | 1761.62 | 1001.68 | 1657.49 | 730.97 | 926.52 | 0.00 | 0.00 |
Minimum of Months | 976.20 | 315.68 | 1270.16 | 315.87 | 592.74 | 0.00 | 0.00 |
Maximum of Months | 2448.36 | 1728.06 | 2116.81 | 1189.42 | 1174.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 106.66 | 1265.93 | 369.76 | 86.81 | 282.96 | 0.00 | 0.00 |
February | 267.88 | 1192.16 | 599.28 | 154.02 | 445.26 | 0.00 | 0.00 |
March | 760.71 | 863.59 | 939.27 | 402.17 | 537.09 | 0.00 | 0.00 |
April | 1088.47 | 643.99 | 1150.00 | 471.55 | 678.46 | 0.00 | 0.00 |
May | 1482.89 | 450.70 | 1356.61 | 613.10 | 743.51 | 0.00 | 0.00 |
June | 1995.93 | 305.87 | 1636.79 | 769.88 | 866.92 | 0.00 | 0.00 |
July | 1899.43 | 216.03 | 1463.36 | 641.58 | 821.77 | 0.00 | 0.00 |
August | 1690.19 | 272.47 | 1323.52 | 562.77 | 760.75 | 0.00 | 0.00 |
September | 1197.17 | 418.66 | 1039.37 | 448.86 | 590.51 | 0.00 | 0.00 |
October | 598.07 | 635.10 | 673.77 | 237.34 | 436.43 | 0.00 | 0.00 |
November | 244.15 | 818.24 | 399.28 | 115.06 | 284.22 | 0.00 | 0.00 |
December | 102.72 | 1222.73 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Annual Sum or Average | 956.53 | 689.61 | 942.98 | 382.65 | 560.33 | 0.00 | 0.00 |
Minimum of Months | 102.72 | 216.03 | 346.14 | 75.42 | 270.72 | 0.00 | 0.00 |
Maximum of Months | 1995.93 | 1265.93 | 1636.79 | 769.88 | 866.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20444316.10 | 0.521154E+10 | 0.946153E+09 | 0.00 | 0.946153E+09 | 0.00 | 0.00 |
February | 0.109676E+09 | 0.438923E+10 | 0.130207E+10 | 0.00 | 0.130207E+10 | 0.00 | 0.00 |
March | 0.619878E+09 | 0.347409E+10 | 0.174823E+10 | 0.00 | 0.174823E+10 | 0.00 | 0.00 |
April | 0.124864E+10 | 0.236654E+10 | 0.215575E+10 | 8602286.50 | 0.214715E+10 | 0.00 | 0.00 |
May | 0.208721E+10 | 0.160374E+10 | 0.258837E+10 | 0.109762E+09 | 0.247861E+10 | 0.00 | 0.00 |
June | 0.323503E+10 | 0.103988E+10 | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.00 | 0.00 |
July | 0.355601E+10 | 0.764749E+09 | 0.288796E+10 | 0.186425E+09 | 0.270154E+10 | 0.00 | 0.00 |
August | 0.291613E+10 | 0.999184E+09 | 0.249889E+10 | 38015207.11 | 0.246088E+10 | 0.00 | 0.00 |
September | 0.168877E+10 | 0.152662E+10 | 0.184036E+10 | 382348.08 | 0.183998E+10 | 0.00 | 0.00 |
October | 0.770650E+09 | 0.241149E+10 | 0.142161E+10 | 0.00 | 0.142161E+10 | 0.00 | 0.00 |
November | 0.239308E+09 | 0.303590E+10 | 0.924471E+09 | 0.00 | 0.924471E+09 | 0.00 | 0.00 |
December | 22962625.61 | 0.493120E+10 | 0.885571E+09 | 0.00 | 0.885571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165147E+11 | 0.317542E+11 | 0.222123E+11 | 0.599654E+09 | 0.216126E+11 | 0.00 | 0.00 |
Minimum of Months | 20444316.10 | 0.764749E+09 | 0.885571E+09 | 0.00 | 0.885571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355601E+10 | 0.521154E+10 | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.471252E+09 | 0.315564E+10 | 0.115429E+10 | 0.372208E+09 | 0.782087E+09 | 0.00 | 0.00 |
February | 0.763469E+09 | 0.269546E+10 | 0.152980E+10 | 0.459053E+09 | 0.107074E+10 | 0.00 | 0.00 |
March | 0.194870E+10 | 0.213124E+10 | 0.243042E+10 | 0.101784E+10 | 0.141258E+10 | 0.00 | 0.00 |
April | 0.296902E+10 | 0.149936E+10 | 0.311304E+10 | 0.137551E+10 | 0.173754E+10 | 0.00 | 0.00 |
May | 0.390818E+10 | 0.107454E+10 | 0.360398E+10 | 0.159423E+10 | 0.200975E+10 | 0.00 | 0.00 |
June | 0.468346E+10 | 0.693042E+09 | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.00 | 0.00 |
July | 0.497625E+10 | 0.505207E+09 | 0.386509E+10 | 0.170174E+10 | 0.216335E+10 | 0.00 | 0.00 |
August | 0.440360E+10 | 0.651999E+09 | 0.349060E+10 | 0.146516E+10 | 0.202544E+10 | 0.00 | 0.00 |
September | 0.323292E+10 | 0.966808E+09 | 0.281108E+10 | 0.124689E+10 | 0.156420E+10 | 0.00 | 0.00 |
October | 0.181906E+10 | 0.151726E+10 | 0.197114E+10 | 0.815314E+09 | 0.115582E+10 | 0.00 | 0.00 |
November | 0.708068E+09 | 0.193310E+10 | 0.108200E+10 | 0.347092E+09 | 0.734907E+09 | 0.00 | 0.00 |
December | 0.251837E+09 | 0.308723E+10 | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.301358E+11 | 0.199109E+11 | 0.298467E+11 | 0.123025E+11 | 0.175443E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251837E+09 | 0.505207E+09 | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497625E+10 | 0.315564E+10 | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333389E+10 | 0.445583E+10 | 0.406841E+10 | 0.237485E+10 | 0.169356E+10 | 0.00 | 0.00 |
February | 0.339778E+10 | 0.395151E+10 | 0.419558E+10 | 0.202307E+10 | 0.217251E+10 | 0.00 | 0.00 |
March | 0.559406E+10 | 0.322476E+10 | 0.566966E+10 | 0.318574E+10 | 0.248392E+10 | 0.00 | 0.00 |
April | 0.467959E+10 | 0.245692E+10 | 0.454391E+10 | 0.181575E+10 | 0.272815E+10 | 0.00 | 0.00 |
May | 0.456492E+10 | 0.175179E+10 | 0.410887E+10 | 0.119339E+10 | 0.291549E+10 | 0.00 | 0.00 |
June | 0.475844E+10 | 0.112510E+10 | 0.386371E+10 | 0.818736E+09 | 0.304498E+10 | 0.00 | 0.00 |
July | 0.552611E+10 | 0.818550E+09 | 0.407570E+10 | 0.988893E+09 | 0.308680E+10 | 0.00 | 0.00 |
August | 0.610656E+10 | 0.104725E+10 | 0.457564E+10 | 0.148353E+10 | 0.309210E+10 | 0.00 | 0.00 |
September | 0.636696E+10 | 0.155982E+10 | 0.514848E+10 | 0.250769E+10 | 0.264079E+10 | 0.00 | 0.00 |
October | 0.552123E+10 | 0.234719E+10 | 0.509054E+10 | 0.290781E+10 | 0.218273E+10 | 0.00 | 0.00 |
November | 0.338337E+10 | 0.288448E+10 | 0.352814E+10 | 0.199175E+10 | 0.153639E+10 | 0.00 | 0.00 |
December | 0.264952E+10 | 0.436092E+10 | 0.340200E+10 | 0.176068E+10 | 0.164131E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.558824E+11 | 0.299841E+11 | 0.522706E+11 | 0.230519E+11 | 0.292187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264952E+10 | 0.818550E+09 | 0.340200E+10 | 0.818736E+09 | 0.153639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.636696E+10 | 0.445583E+10 | 0.566966E+10 | 0.318574E+10 | 0.309210E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.293581E+09 | 0.327903E+10 | 0.990367E+09 | 0.232499E+09 | 0.757868E+09 | 0.00 | 0.00 |
February | 0.659636E+09 | 0.278493E+10 | 0.144978E+10 | 0.372603E+09 | 0.107718E+10 | 0.00 | 0.00 |
March | 0.205749E+10 | 0.219148E+10 | 0.251573E+10 | 0.107717E+10 | 0.143855E+10 | 0.00 | 0.00 |
April | 0.284399E+10 | 0.157108E+10 | 0.298081E+10 | 0.122225E+10 | 0.175856E+10 | 0.00 | 0.00 |
May | 0.398901E+10 | 0.114210E+10 | 0.363355E+10 | 0.164213E+10 | 0.199142E+10 | 0.00 | 0.00 |
June | 0.517474E+10 | 0.760449E+09 | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.00 | 0.00 |
July | 0.508194E+10 | 0.561661E+09 | 0.391945E+10 | 0.171842E+10 | 0.220103E+10 | 0.00 | 0.00 |
August | 0.453101E+10 | 0.699507E+09 | 0.354491E+10 | 0.150733E+10 | 0.203758E+10 | 0.00 | 0.00 |
September | 0.312311E+10 | 0.101717E+10 | 0.269405E+10 | 0.116344E+10 | 0.153061E+10 | 0.00 | 0.00 |
October | 0.163609E+10 | 0.157240E+10 | 0.180463E+10 | 0.635692E+09 | 0.116894E+10 | 0.00 | 0.00 |
November | 0.655422E+09 | 0.197268E+10 | 0.103493E+10 | 0.298230E+09 | 0.736702E+09 | 0.00 | 0.00 |
December | 0.284354E+09 | 0.313864E+10 | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.303304E+11 | 0.206911E+11 | 0.297379E+11 | 0.120673E+11 | 0.176706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.284354E+09 | 0.561661E+09 | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517474E+10 | 0.327903E+10 | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13435143.10 | 0.533374E+10 | 0.946148E+09 | 0.00 | 0.946148E+09 | 0.00 | 0.00 |
February | 0.104362E+09 | 0.449270E+10 | 0.130207E+10 | 0.00 | 0.130207E+10 | 0.00 | 0.00 |
March | 0.649262E+09 | 0.353752E+10 | 0.174822E+10 | 0.00 | 0.174822E+10 | 0.00 | 0.00 |
April | 0.130379E+10 | 0.239159E+10 | 0.215574E+10 | 8602241.92 | 0.214713E+10 | 0.00 | 0.00 |
May | 0.218564E+10 | 0.157136E+10 | 0.258835E+10 | 0.109761E+09 | 0.247859E+10 | 0.00 | 0.00 |
June | 0.330604E+10 | 0.102356E+10 | 0.301282E+10 | 0.256466E+09 | 0.275635E+10 | 0.00 | 0.00 |
July | 0.362018E+10 | 0.745374E+09 | 0.288795E+10 | 0.186424E+09 | 0.270153E+10 | 0.00 | 0.00 |
August | 0.294390E+10 | 0.101772E+10 | 0.249888E+10 | 38015010.12 | 0.246086E+10 | 0.00 | 0.00 |
September | 0.167309E+10 | 0.164308E+10 | 0.184036E+10 | 382346.09 | 0.183997E+10 | 0.00 | 0.00 |
October | 0.705716E+09 | 0.269905E+10 | 0.142160E+10 | 0.00 | 0.142160E+10 | 0.00 | 0.00 |
November | 0.206077E+09 | 0.333586E+10 | 0.924466E+09 | 0.00 | 0.924466E+09 | 0.00 | 0.00 |
December | 15955674.03 | 0.517807E+10 | 0.885566E+09 | 0.00 | 0.885566E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167274E+11 | 0.329696E+11 | 0.222122E+11 | 0.599651E+09 | 0.216125E+11 | 0.00 | 0.00 |
Minimum of Months | 13435143.10 | 0.745374E+09 | 0.885566E+09 | 0.00 | 0.885566E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362018E+10 | 0.533374E+10 | 0.301282E+10 | 0.256466E+09 | 0.275635E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.468705E+09 | 0.324654E+10 | 0.115429E+10 | 0.372205E+09 | 0.782081E+09 | 0.00 | 0.00 |
February | 0.764216E+09 | 0.277015E+10 | 0.152978E+10 | 0.459048E+09 | 0.107074E+10 | 0.00 | 0.00 |
March | 0.197794E+10 | 0.219648E+10 | 0.243040E+10 | 0.101783E+10 | 0.141257E+10 | 0.00 | 0.00 |
April | 0.300528E+10 | 0.155023E+10 | 0.311302E+10 | 0.137549E+10 | 0.173753E+10 | 0.00 | 0.00 |
May | 0.396458E+10 | 0.108675E+10 | 0.360395E+10 | 0.159421E+10 | 0.200974E+10 | 0.00 | 0.00 |
June | 0.472692E+10 | 0.706828E+09 | 0.389517E+10 | 0.172146E+10 | 0.217371E+10 | 0.00 | 0.00 |
July | 0.501514E+10 | 0.515581E+09 | 0.386506E+10 | 0.170172E+10 | 0.216334E+10 | 0.00 | 0.00 |
August | 0.442345E+10 | 0.687550E+09 | 0.349058E+10 | 0.146515E+10 | 0.202543E+10 | 0.00 | 0.00 |
September | 0.322426E+10 | 0.106004E+10 | 0.281106E+10 | 0.124687E+10 | 0.156419E+10 | 0.00 | 0.00 |
October | 0.177215E+10 | 0.170457E+10 | 0.197112E+10 | 0.815306E+09 | 0.115582E+10 | 0.00 | 0.00 |
November | 0.681559E+09 | 0.212569E+10 | 0.108199E+10 | 0.347088E+09 | 0.734902E+09 | 0.00 | 0.00 |
December | 0.243569E+09 | 0.324355E+10 | 0.900093E+09 | 0.185978E+09 | 0.714115E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.302678E+11 | 0.208940E+11 | 0.298465E+11 | 0.123024E+11 | 0.175442E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243569E+09 | 0.515581E+09 | 0.900093E+09 | 0.185978E+09 | 0.714115E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501514E+10 | 0.324654E+10 | 0.389517E+10 | 0.172146E+10 | 0.217371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341034E+10 | 0.450052E+10 | 0.406845E+10 | 0.237487E+10 | 0.169358E+10 | 0.00 | 0.00 |
February | 0.349562E+10 | 0.397885E+10 | 0.419562E+10 | 0.202309E+10 | 0.217253E+10 | 0.00 | 0.00 |
March | 0.573907E+10 | 0.331550E+10 | 0.566971E+10 | 0.318578E+10 | 0.248394E+10 | 0.00 | 0.00 |
April | 0.480218E+10 | 0.249257E+10 | 0.454395E+10 | 0.181578E+10 | 0.272817E+10 | 0.00 | 0.00 |
May | 0.471432E+10 | 0.171654E+10 | 0.410890E+10 | 0.119340E+10 | 0.291551E+10 | 0.00 | 0.00 |
June | 0.487177E+10 | 0.110693E+10 | 0.386374E+10 | 0.818746E+09 | 0.304499E+10 | 0.00 | 0.00 |
July | 0.560275E+10 | 0.816743E+09 | 0.407573E+10 | 0.988905E+09 | 0.308682E+10 | 0.00 | 0.00 |
August | 0.615626E+10 | 0.109529E+10 | 0.457567E+10 | 0.148355E+10 | 0.309213E+10 | 0.00 | 0.00 |
September | 0.638778E+10 | 0.170850E+10 | 0.514853E+10 | 0.250772E+10 | 0.264081E+10 | 0.00 | 0.00 |
October | 0.552427E+10 | 0.262336E+10 | 0.509059E+10 | 0.290784E+10 | 0.218275E+10 | 0.00 | 0.00 |
November | 0.337952E+10 | 0.316040E+10 | 0.352817E+10 | 0.199177E+10 | 0.153640E+10 | 0.00 | 0.00 |
December | 0.268282E+10 | 0.449716E+10 | 0.340203E+10 | 0.176071E+10 | 0.164133E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567667E+11 | 0.310124E+11 | 0.522711E+11 | 0.230522E+11 | 0.292189E+11 | 0.00 | 0.00 |
Minimum of Months | 0.268282E+10 | 0.816743E+09 | 0.340203E+10 | 0.818746E+09 | 0.153640E+10 | 0.00 | 0.00 |
Maximum of Months | 0.638778E+10 | 0.450052E+10 | 0.566971E+10 | 0.318578E+10 | 0.309213E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294759E+09 | 0.335928E+10 | 0.990360E+09 | 0.232497E+09 | 0.757863E+09 | 0.00 | 0.00 |
February | 0.670527E+09 | 0.285582E+10 | 0.144977E+10 | 0.372599E+09 | 0.107717E+10 | 0.00 | 0.00 |
March | 0.209937E+10 | 0.226310E+10 | 0.251571E+10 | 0.107716E+10 | 0.143855E+10 | 0.00 | 0.00 |
April | 0.289266E+10 | 0.161962E+10 | 0.298079E+10 | 0.122224E+10 | 0.175855E+10 | 0.00 | 0.00 |
May | 0.404626E+10 | 0.115845E+10 | 0.363352E+10 | 0.164211E+10 | 0.199141E+10 | 0.00 | 0.00 |
June | 0.521671E+10 | 0.783002E+09 | 0.424254E+10 | 0.199550E+10 | 0.224703E+10 | 0.00 | 0.00 |
July | 0.511668E+10 | 0.575811E+09 | 0.391942E+10 | 0.171840E+10 | 0.220102E+10 | 0.00 | 0.00 |
August | 0.454183E+10 | 0.742104E+09 | 0.354489E+10 | 0.150731E+10 | 0.203757E+10 | 0.00 | 0.00 |
September | 0.310778E+10 | 0.111526E+10 | 0.269403E+10 | 0.116343E+10 | 0.153060E+10 | 0.00 | 0.00 |
October | 0.160234E+10 | 0.175522E+10 | 0.180461E+10 | 0.635686E+09 | 0.116893E+10 | 0.00 | 0.00 |
November | 0.635348E+09 | 0.216414E+10 | 0.103492E+10 | 0.298227E+09 | 0.736697E+09 | 0.00 | 0.00 |
December | 0.280187E+09 | 0.329188E+10 | 0.927093E+09 | 0.202002E+09 | 0.725091E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.305044E+11 | 0.216837E+11 | 0.297377E+11 | 0.120672E+11 | 0.176705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.280187E+09 | 0.575811E+09 | 0.927093E+09 | 0.202002E+09 | 0.725091E+09 | 0.00 | 0.00 |
Maximum of Months | 0.521671E+10 | 0.335928E+10 | 0.424254E+10 | 0.199550E+10 | 0.224703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13486613.18 | 0.538887E+10 | 0.946153E+09 | 0.00 | 0.946153E+09 | 0.00 | 0.00 |
February | 95349515.40 | 0.454844E+10 | 0.130207E+10 | 0.00 | 0.130207E+10 | 0.00 | 0.00 |
March | 0.590226E+09 | 0.366423E+10 | 0.174823E+10 | 0.00 | 0.174823E+10 | 0.00 | 0.00 |
April | 0.119910E+10 | 0.252832E+10 | 0.215575E+10 | 8602286.50 | 0.214715E+10 | 0.00 | 0.00 |
May | 0.204219E+10 | 0.170124E+10 | 0.258837E+10 | 0.109762E+09 | 0.247861E+10 | 0.00 | 0.00 |
June | 0.322373E+10 | 0.108150E+10 | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.00 | 0.00 |
July | 0.356000E+10 | 0.785921E+09 | 0.288796E+10 | 0.186425E+09 | 0.270154E+10 | 0.00 | 0.00 |
August | 0.290895E+10 | 0.104267E+10 | 0.249889E+10 | 38015207.11 | 0.246088E+10 | 0.00 | 0.00 |
September | 0.165634E+10 | 0.163825E+10 | 0.184036E+10 | 382348.08 | 0.183998E+10 | 0.00 | 0.00 |
October | 0.711685E+09 | 0.262817E+10 | 0.142161E+10 | 0.00 | 0.142161E+10 | 0.00 | 0.00 |
November | 0.208197E+09 | 0.327625E+10 | 0.924471E+09 | 0.00 | 0.924471E+09 | 0.00 | 0.00 |
December | 16214210.59 | 0.515006E+10 | 0.885571E+09 | 0.00 | 0.885571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162255E+11 | 0.334339E+11 | 0.222123E+11 | 0.599654E+09 | 0.216126E+11 | 0.00 | 0.00 |
Minimum of Months | 13486613.18 | 0.785921E+09 | 0.885571E+09 | 0.00 | 0.885571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356000E+10 | 0.538887E+10 | 0.301283E+10 | 0.256468E+09 | 0.275637E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.458705E+09 | 0.326657E+10 | 0.115429E+10 | 0.372208E+09 | 0.782087E+09 | 0.00 | 0.00 |
February | 0.744642E+09 | 0.279169E+10 | 0.152980E+10 | 0.459053E+09 | 0.107074E+10 | 0.00 | 0.00 |
March | 0.192201E+10 | 0.224559E+10 | 0.243042E+10 | 0.101784E+10 | 0.141258E+10 | 0.00 | 0.00 |
April | 0.293985E+10 | 0.158759E+10 | 0.311304E+10 | 0.137551E+10 | 0.173754E+10 | 0.00 | 0.00 |
May | 0.389304E+10 | 0.112918E+10 | 0.360398E+10 | 0.159423E+10 | 0.200975E+10 | 0.00 | 0.00 |
June | 0.468510E+10 | 0.717381E+09 | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.00 | 0.00 |
July | 0.498607E+10 | 0.516575E+09 | 0.386509E+10 | 0.170174E+10 | 0.216335E+10 | 0.00 | 0.00 |
August | 0.440551E+10 | 0.676352E+09 | 0.349060E+10 | 0.146516E+10 | 0.202544E+10 | 0.00 | 0.00 |
September | 0.321733E+10 | 0.102476E+10 | 0.281108E+10 | 0.124689E+10 | 0.156420E+10 | 0.00 | 0.00 |
October | 0.177875E+10 | 0.163710E+10 | 0.197114E+10 | 0.815314E+09 | 0.115582E+10 | 0.00 | 0.00 |
November | 0.681409E+09 | 0.207772E+10 | 0.108200E+10 | 0.347092E+09 | 0.734907E+09 | 0.00 | 0.00 |
December | 0.240550E+09 | 0.322270E+10 | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299530E+11 | 0.208932E+11 | 0.298467E+11 | 0.123025E+11 | 0.175443E+11 | 0.00 | 0.00 |
Minimum of Months | 0.240550E+09 | 0.516575E+09 | 0.900100E+09 | 0.185979E+09 | 0.714120E+09 | 0.00 | 0.00 |
Maximum of Months | 0.498607E+10 | 0.326657E+10 | 0.389520E+10 | 0.172148E+10 | 0.217372E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.330213E+10 | 0.462844E+10 | 0.406841E+10 | 0.237485E+10 | 0.169356E+10 | 0.00 | 0.00 |
February | 0.336460E+10 | 0.410415E+10 | 0.419558E+10 | 0.202307E+10 | 0.217251E+10 | 0.00 | 0.00 |
March | 0.555162E+10 | 0.340790E+10 | 0.566966E+10 | 0.318574E+10 | 0.248392E+10 | 0.00 | 0.00 |
April | 0.464019E+10 | 0.260963E+10 | 0.454391E+10 | 0.181575E+10 | 0.272815E+10 | 0.00 | 0.00 |
May | 0.454018E+10 | 0.185503E+10 | 0.410887E+10 | 0.119339E+10 | 0.291549E+10 | 0.00 | 0.00 |
June | 0.475707E+10 | 0.117584E+10 | 0.386371E+10 | 0.818736E+09 | 0.304498E+10 | 0.00 | 0.00 |
July | 0.553602E+10 | 0.845524E+09 | 0.407570E+10 | 0.988893E+09 | 0.308680E+10 | 0.00 | 0.00 |
August | 0.610715E+10 | 0.109439E+10 | 0.457564E+10 | 0.148353E+10 | 0.309210E+10 | 0.00 | 0.00 |
September | 0.634615E+10 | 0.166159E+10 | 0.514848E+10 | 0.250769E+10 | 0.264079E+10 | 0.00 | 0.00 |
October | 0.546179E+10 | 0.253935E+10 | 0.509054E+10 | 0.290781E+10 | 0.218273E+10 | 0.00 | 0.00 |
November | 0.333276E+10 | 0.310444E+10 | 0.352814E+10 | 0.199175E+10 | 0.153639E+10 | 0.00 | 0.00 |
December | 0.261467E+10 | 0.456263E+10 | 0.340200E+10 | 0.176068E+10 | 0.164131E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.555543E+11 | 0.315889E+11 | 0.522706E+11 | 0.230519E+11 | 0.292187E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261467E+10 | 0.845524E+09 | 0.340200E+10 | 0.818736E+09 | 0.153639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.634615E+10 | 0.462844E+10 | 0.566966E+10 | 0.318574E+10 | 0.309210E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.285678E+09 | 0.339067E+10 | 0.990367E+09 | 0.232499E+09 | 0.757868E+09 | 0.00 | 0.00 |
February | 0.648055E+09 | 0.288407E+10 | 0.144978E+10 | 0.372603E+09 | 0.107718E+10 | 0.00 | 0.00 |
March | 0.203748E+10 | 0.231303E+10 | 0.251573E+10 | 0.107717E+10 | 0.143855E+10 | 0.00 | 0.00 |
April | 0.282132E+10 | 0.166921E+10 | 0.298081E+10 | 0.122225E+10 | 0.175856E+10 | 0.00 | 0.00 |
May | 0.397176E+10 | 0.120716E+10 | 0.363355E+10 | 0.164213E+10 | 0.199142E+10 | 0.00 | 0.00 |
June | 0.517346E+10 | 0.792814E+09 | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.00 | 0.00 |
July | 0.508742E+10 | 0.578604E+09 | 0.391945E+10 | 0.171842E+10 | 0.220103E+10 | 0.00 | 0.00 |
August | 0.452702E+10 | 0.729778E+09 | 0.354491E+10 | 0.150733E+10 | 0.203758E+10 | 0.00 | 0.00 |
September | 0.310306E+10 | 0.108517E+10 | 0.269405E+10 | 0.116344E+10 | 0.153061E+10 | 0.00 | 0.00 |
October | 0.160188E+10 | 0.170106E+10 | 0.180463E+10 | 0.635692E+09 | 0.116894E+10 | 0.00 | 0.00 |
November | 0.632847E+09 | 0.212087E+10 | 0.103493E+10 | 0.298230E+09 | 0.736702E+09 | 0.00 | 0.00 |
December | 0.275123E+09 | 0.327495E+10 | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.301651E+11 | 0.217474E+11 | 0.297379E+11 | 0.120673E+11 | 0.176706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.275123E+09 | 0.578604E+09 | 0.927100E+09 | 0.202004E+09 | 0.725096E+09 | 0.00 | 0.00 |
Maximum of Months | 0.517346E+10 | 0.339067E+10 | 0.424257E+10 | 0.199552E+10 | 0.224704E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.563132E+10 | -0.488354E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -747779127.4 | 58.98 | 0.00 | 0.00 |
February | 0.517263E+10 | -0.450243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -670205650.9 | 58.98 | 0.00 | 0.00 |
March | 0.597452E+10 | -0.525703E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717491975.7 | 58.98 | 0.00 | 0.00 |
April | 0.522633E+10 | -0.454427E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682051430.2 | 58.98 | 0.00 | 0.00 |
May | 0.529172E+10 | -0.459893E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692781896.8 | 58.98 | 0.00 | 0.00 |
June | 0.495363E+10 | -0.428519E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668439799.0 | 58.98 | 0.00 | 0.00 |
July | 0.452766E+10 | -0.384049E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -687170264.0 | 58.98 | 0.00 | 0.00 |
August | 0.485622E+10 | -0.416744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688783988.3 | 58.98 | 0.00 | 0.00 |
September | 0.448777E+10 | -0.382042E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667340915.7 | 58.98 | 0.00 | 0.00 |
October | 0.484144E+10 | -0.414287E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698568905.4 | 58.98 | 0.00 | 0.00 |
November | 0.502496E+10 | -0.433781E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -687154893.6 | 58.98 | 0.00 | 0.00 |
December | 0.528711E+10 | -0.455272E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -734390156.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.612753E+11 | -0.529331E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.834216E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448777E+10 | -0.525703E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -747779127.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.597452E+10 | -0.382042E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667340915.7 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.62 | 0.62 | 01-JAN-08:39 | 4105.44 | 32.22 | 234.67 | 245.67 | 3334.23 | 33.55 | 242.17 | 219.17 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 5174.25 | 32.43 | 244.33 | 253.00 | 1700.83 | 26.70 | 235.17 | 234.17 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 7464.69 | 29.27 | 248.00 | 323.17 | 1355.76 | 21.33 | 168.50 | 287.83 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 1877.07 | 17.69 | 0.00 | 341.00 | 1049.78 | 20.44 | 165.67 | 303.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:10 | 1692.44 | 17.73 | 0.00 | 377.67 | 995.21 | 20.56 | 140.50 | 326.83 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1526.41 | 17.53 | 0.00 | 386.33 | 877.03 | 20.31 | 168.67 | 343.50 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:49 | 1603.43 | 17.57 | 0.00 | 394.17 | 908.12 | 20.35 | 181.00 | 344.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1905.69 | 18.07 | 0.00 | 371.50 | 1055.72 | 20.83 | 218.67 | 330.50 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2733.49 | 19.62 | 17.00 | 319.50 | 1391.27 | 21.49 | 189.00 | 285.33 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 6016.09 | 31.82 | 273.33 | 295.50 | 1435.02 | 21.93 | 171.33 | 273.67 |
November | 258.33 | 0.63 | 0.62 | 01-NOV-07:40 | 3871.93 | 32.05 | 238.50 | 238.50 | 1553.80 | 27.51 | 205.17 | 212.33 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 3430.01 | 29.98 | 197.83 | 234.17 | 2724.07 | 32.47 | 217.50 | 201.83 |
Annual Sum or Average | 3928.50 | 0.63 | 3259.67 | 23.57 | 1453.67 | 3780.17 | 1416.74 | 23.18 | 2303.33 | 3363.67 | ||
Minimum of Months | 230.67 | 0.62 | 0.62 | 1526.41 | 17.53 | 0.00 | 234.17 | 877.03 | 20.31 | 140.50 | 201.83 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 7464.69 | 32.43 | 273.33 | 394.17 | 3334.23 | 33.55 | 242.17 | 344.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 1387.00 | 19.87 | 69.50 | 231.00 | 690.89 | 21.04 | 73.67 | 178.00 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-08:00 | 1886.25 | 19.81 | 68.67 | 243.33 | 995.79 | 22.38 | 89.67 | 209.83 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2601.36 | 20.68 | 102.00 | 313.17 | 1105.58 | 21.06 | 57.67 | 274.33 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2831.62 | 20.22 | 103.83 | 344.67 | 1583.82 | 21.90 | 78.50 | 306.33 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3729.78 | 20.43 | 86.67 | 385.50 | 1588.03 | 21.87 | 56.83 | 338.33 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3447.97 | 20.90 | 131.17 | 396.83 | 1499.32 | 21.61 | 76.00 | 364.00 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 3191.91 | 19.91 | 114.00 | 402.67 | 1417.01 | 21.62 | 75.50 | 363.50 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2981.72 | 20.31 | 106.50 | 373.00 | 1317.93 | 21.86 | 67.50 | 338.50 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2923.87 | 20.19 | 67.17 | 318.33 | 1670.72 | 23.24 | 73.17 | 279.67 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 1902.88 | 19.61 | 78.00 | 283.50 | 1011.60 | 21.26 | 64.83 | 242.17 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1350.11 | 18.67 | 69.83 | 223.67 | 769.32 | 21.47 | 80.67 | 165.00 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1192.63 | 19.17 | 59.33 | 219.50 | 596.70 | 20.52 | 59.00 | 161.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2592.84 | 20.06 | 1056.67 | 3735.17 | 1239.29 | 21.67 | 853.00 | 3221.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1192.63 | 18.67 | 59.33 | 219.50 | 596.70 | 20.52 | 56.83 | 161.67 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3729.78 | 20.90 | 131.17 | 402.67 | 1670.72 | 23.24 | 89.67 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:00 | 589.20 | 14.62 | 0.00 | 211.33 | 330.93 | 17.45 | 0.00 | 108.50 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:30 | 775.22 | 15.77 | 0.00 | 236.17 | 432.28 | 18.48 | 0.00 | 178.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 816.25 | 16.33 | 0.00 | 308.33 | 479.88 | 19.13 | 0.00 | 251.50 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 942.06 | 16.95 | 0.00 | 344.67 | 556.55 | 19.63 | 5.50 | 303.83 |
May | 332.17 | 0.62 | 0.62 | 01-MAY-05:40 | 1119.20 | 18.08 | 3.33 | 395.50 | 686.62 | 21.91 | 97.00 | 355.17 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1268.74 | 20.84 | 74.50 | 410.50 | 745.35 | 22.20 | 166.33 | 384.33 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1207.01 | 20.48 | 71.00 | 416.17 | 707.53 | 21.93 | 152.33 | 383.83 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 1066.03 | 17.69 | 0.00 | 383.33 | 636.21 | 20.40 | 61.83 | 346.00 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 885.30 | 17.15 | 0.00 | 315.83 | 552.12 | 19.95 | 1.83 | 259.83 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 717.30 | 15.50 | 0.00 | 272.67 | 414.35 | 18.30 | 0.00 | 201.00 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 571.88 | 14.13 | 0.00 | 208.67 | 319.41 | 16.85 | 0.00 | 104.00 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-09:30 | 594.61 | 14.57 | 0.00 | 198.00 | 326.20 | 17.31 | 0.00 | 94.67 |
Annual Sum or Average | 3928.50 | 0.63 | 923.43 | 17.23 | 148.83 | 3701.17 | 542.95 | 19.78 | 484.83 | 2971.17 | ||
Minimum of Months | 230.67 | 0.62 | 0.62 | 571.88 | 14.13 | 0.00 | 198.00 | 319.41 | 16.85 | 0.00 | 94.67 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1268.74 | 20.84 | 74.50 | 416.17 | 745.35 | 22.20 | 166.33 | 384.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:00 | 1262.99 | 18.81 | 64.00 | 228.17 | 709.82 | 21.71 | 76.50 | 173.50 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:30 | 1754.22 | 19.47 | 67.33 | 244.33 | 948.28 | 22.24 | 82.33 | 208.83 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2559.35 | 20.62 | 100.17 | 316.67 | 1444.69 | 22.27 | 80.00 | 278.17 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:00 | 2983.13 | 19.96 | 104.00 | 341.00 | 1271.09 | 20.38 | 49.50 | 303.17 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:19 | 3234.73 | 17.11 | 43.00 | 385.00 | 1770.00 | 18.35 | 0.00 | 341.33 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3391.33 | 16.88 | 52.50 | 395.50 | 1455.78 | 18.32 | 0.00 | 361.17 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 3024.08 | 16.95 | 54.50 | 400.33 | 1372.12 | 18.51 | 3.67 | 363.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2854.77 | 18.96 | 84.83 | 376.33 | 1544.70 | 20.79 | 54.33 | 334.17 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 3130.59 | 21.48 | 83.50 | 316.50 | 1327.45 | 21.68 | 46.50 | 282.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1784.91 | 19.19 | 74.33 | 280.67 | 965.05 | 21.93 | 68.33 | 244.00 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:00 | 1306.37 | 18.51 | 71.67 | 221.17 | 713.27 | 21.04 | 71.33 | 169.83 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-09:30 | 1231.68 | 18.62 | 51.67 | 214.67 | 662.62 | 21.18 | 65.50 | 160.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2511.90 | 18.77 | 851.50 | 3720.33 | 1237.31 | 20.50 | 598.00 | 3220.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1231.68 | 16.88 | 43.00 | 214.67 | 662.62 | 18.32 | 0.00 | 160.67 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3391.33 | 21.48 | 104.00 | 400.33 | 1770.00 | 22.27 | 82.33 | 363.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 3970.01 | 31.84 | 232.50 | 244.17 | 3242.35 | 33.08 | 232.33 | 217.17 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 5026.34 | 32.14 | 241.00 | 252.00 | 1604.05 | 24.70 | 106.50 | 232.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 7325.66 | 28.26 | 228.83 | 321.50 | 1259.40 | 18.55 | 12.17 | 285.00 |
April | 371.17 | 0.64 | 0.62 | 01-APR-06:40 | 1776.23 | 13.98 | 0.00 | 338.17 | 982.63 | 17.89 | 1.00 | 297.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:19 | 1605.99 | 14.25 | 0.00 | 374.50 | 939.14 | 18.26 | 0.00 | 322.50 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1453.71 | 14.07 | 0.00 | 383.67 | 832.58 | 18.01 | 0.00 | 340.33 |
July | 439.00 | 0.64 | 0.62 | 01-JUL-05:49 | 1525.65 | 14.03 | 0.00 | 390.33 | 859.89 | 17.96 | 0.00 | 341.00 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1808.02 | 14.48 | 0.00 | 368.83 | 993.18 | 18.39 | 0.67 | 325.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2591.86 | 16.22 | 17.00 | 318.00 | 1293.48 | 19.04 | 8.67 | 281.50 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 5881.75 | 31.31 | 268.50 | 294.33 | 1339.66 | 19.04 | 22.00 | 271.00 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 3750.83 | 31.79 | 235.50 | 236.33 | 1474.52 | 25.82 | 133.67 | 209.67 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 3295.31 | 29.08 | 191.00 | 231.67 | 2641.00 | 32.02 | 211.50 | 199.17 |
Annual Sum or Average | 3928.50 | 0.63 | 3148.35 | 21.29 | 1414.33 | 3753.50 | 1343.25 | 21.02 | 728.50 | 3323.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1453.71 | 13.98 | 0.00 | 231.67 | 832.58 | 17.89 | 0.00 | 199.17 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 7325.66 | 32.14 | 268.50 | 390.33 | 3242.35 | 33.08 | 232.33 | 341.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 1340.58 | 19.43 | 69.00 | 228.17 | 658.02 | 20.78 | 68.83 | 172.67 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-08:00 | 1824.72 | 19.38 | 68.33 | 241.50 | 952.39 | 22.16 | 78.17 | 207.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2530.03 | 20.28 | 101.83 | 311.33 | 1052.67 | 20.84 | 50.17 | 269.33 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2750.01 | 19.82 | 103.67 | 342.83 | 1522.21 | 21.72 | 78.00 | 302.17 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3621.93 | 19.93 | 85.67 | 382.33 | 1517.25 | 21.70 | 56.50 | 334.00 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3271.99 | 19.20 | 107.50 | 393.83 | 1435.70 | 21.44 | 75.83 | 360.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 3103.18 | 19.51 | 113.83 | 400.00 | 1349.32 | 21.39 | 74.67 | 359.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2894.49 | 19.91 | 106.50 | 370.50 | 1223.74 | 20.81 | 54.67 | 334.00 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2831.29 | 19.76 | 67.17 | 315.17 | 1600.83 | 23.05 | 66.17 | 276.67 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-06:00 | 1839.98 | 19.18 | 77.67 | 281.00 | 965.38 | 21.03 | 57.00 | 237.83 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1305.84 | 18.24 | 69.67 | 221.50 | 738.58 | 21.24 | 75.33 | 160.33 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1143.99 | 18.40 | 55.17 | 217.83 | 568.55 | 20.25 | 54.50 | 156.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2506.88 | 19.48 | 1026.00 | 3706.00 | 1181.08 | 21.37 | 789.83 | 3171.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1143.99 | 18.24 | 55.17 | 217.83 | 568.55 | 20.25 | 50.17 | 156.67 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3621.93 | 20.28 | 113.83 | 400.00 | 1600.83 | 23.05 | 78.17 | 360.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:00 | 563.48 | 10.72 | 0.00 | 207.33 | 317.08 | 14.77 | 0.00 | 92.50 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:30 | 742.44 | 12.14 | 0.00 | 234.00 | 414.66 | 16.01 | 0.00 | 170.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 782.09 | 12.92 | 0.00 | 304.00 | 461.87 | 16.89 | 0.00 | 244.33 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 907.97 | 13.62 | 0.00 | 344.00 | 535.88 | 17.51 | 0.00 | 298.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:40 | 1072.93 | 14.83 | 3.33 | 393.83 | 662.00 | 20.05 | 25.50 | 350.33 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1216.35 | 18.16 | 73.83 | 408.83 | 716.62 | 20.20 | 42.33 | 381.67 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1157.00 | 17.75 | 71.00 | 413.50 | 680.32 | 19.92 | 41.50 | 380.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 1021.06 | 14.40 | 0.00 | 380.83 | 612.31 | 18.35 | 0.00 | 341.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 847.09 | 14.18 | 0.00 | 312.50 | 532.23 | 18.13 | 0.00 | 253.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 686.76 | 11.92 | 0.00 | 270.33 | 398.11 | 15.88 | 0.00 | 191.50 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 547.14 | 10.30 | 0.00 | 204.50 | 306.09 | 14.19 | 0.00 | 90.50 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-11:20 | 568.87 | 10.63 | 0.00 | 192.50 | 312.26 | 14.60 | 0.00 | 84.67 |
Annual Sum or Average | 3928.50 | 0.63 | 885.11 | 13.93 | 148.17 | 3666.17 | 522.16 | 17.57 | 109.33 | 2880.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 547.14 | 10.30 | 0.00 | 192.50 | 306.09 | 14.19 | 0.00 | 84.67 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1216.35 | 18.16 | 73.83 | 413.50 | 716.62 | 20.20 | 42.33 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:00 | 1222.25 | 18.46 | 63.83 | 224.83 | 682.01 | 21.60 | 75.33 | 168.33 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:30 | 1694.78 | 19.12 | 67.33 | 242.00 | 906.80 | 22.14 | 80.50 | 204.83 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2484.83 | 20.27 | 99.83 | 314.17 | 1388.66 | 22.14 | 79.00 | 274.17 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:00 | 2907.17 | 19.59 | 103.67 | 337.33 | 1213.95 | 20.23 | 49.33 | 300.50 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:30 | 3135.53 | 16.69 | 43.00 | 381.67 | 1696.91 | 18.19 | 0.00 | 337.17 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3292.13 | 16.46 | 52.50 | 392.50 | 1383.72 | 18.15 | 0.00 | 357.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 2919.45 | 16.52 | 54.50 | 397.67 | 1306.80 | 18.33 | 3.67 | 360.33 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2663.55 | 18.58 | 84.50 | 374.50 | 1480.91 | 20.64 | 53.67 | 331.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 3043.97 | 21.12 | 83.50 | 313.83 | 1256.34 | 21.42 | 43.00 | 279.17 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1725.21 | 18.81 | 73.83 | 278.50 | 900.21 | 20.89 | 57.17 | 237.17 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:00 | 1264.31 | 18.17 | 71.33 | 218.67 | 684.36 | 20.90 | 70.33 | 163.67 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-09:30 | 1189.49 | 18.27 | 50.67 | 212.67 | 617.53 | 20.23 | 55.17 | 155.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2424.55 | 18.39 | 848.50 | 3688.33 | 1179.55 | 20.22 | 567.17 | 3169.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1189.49 | 16.46 | 43.00 | 212.67 | 617.53 | 18.15 | 0.00 | 155.00 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3292.13 | 21.12 | 103.67 | 397.67 | 1696.91 | 22.14 | 80.50 | 360.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 3970.03 | 31.84 | 232.50 | 244.17 | 3242.27 | 33.08 | 232.33 | 217.17 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:09 | 5026.30 | 32.14 | 241.00 | 252.00 | 1603.94 | 24.70 | 106.50 | 232.50 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 7325.59 | 28.26 | 228.83 | 321.50 | 1259.32 | 18.55 | 12.17 | 285.00 |
April | 371.17 | 0.64 | 0.62 | 01-APR-06:40 | 1776.15 | 13.98 | 0.00 | 338.17 | 982.55 | 17.89 | 1.00 | 297.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:19 | 1605.93 | 14.25 | 0.00 | 374.50 | 939.08 | 18.26 | 0.00 | 322.50 |
June | 430.67 | 0.64 | 0.62 | 01-JUN-05:49 | 1453.66 | 14.08 | 0.00 | 383.67 | 832.53 | 18.01 | 0.00 | 340.33 |
July | 439.00 | 0.64 | 0.62 | 01-JUL-05:49 | 1525.59 | 14.03 | 0.00 | 390.33 | 859.83 | 17.96 | 0.00 | 341.00 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:00 | 1807.94 | 14.48 | 0.00 | 368.83 | 993.11 | 18.39 | 0.67 | 325.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2591.77 | 16.22 | 17.00 | 318.00 | 1293.39 | 19.04 | 8.67 | 281.50 |
October | 314.33 | 0.63 | 0.62 | 01-OCT-06:00 | 5881.71 | 31.31 | 268.50 | 294.33 | 1339.57 | 19.04 | 22.00 | 271.00 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 3750.83 | 31.79 | 235.50 | 236.33 | 1474.44 | 25.82 | 133.67 | 209.67 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 3295.32 | 29.08 | 191.00 | 231.67 | 2640.92 | 32.02 | 211.50 | 199.17 |
Annual Sum or Average | 3928.50 | 0.63 | 3148.30 | 21.29 | 1414.33 | 3753.50 | 1343.17 | 21.02 | 728.50 | 3323.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1453.66 | 13.98 | 0.00 | 231.67 | 832.53 | 17.89 | 0.00 | 199.17 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 7325.59 | 32.14 | 268.50 | 390.33 | 3242.27 | 33.08 | 232.33 | 341.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:39 | 1340.56 | 19.43 | 69.00 | 228.17 | 657.98 | 20.78 | 68.83 | 172.67 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-08:00 | 1824.70 | 19.39 | 68.33 | 241.50 | 952.33 | 22.16 | 78.17 | 207.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:30 | 2530.01 | 20.28 | 101.83 | 311.33 | 1052.61 | 20.84 | 50.17 | 269.33 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:19 | 2749.99 | 19.82 | 103.67 | 342.83 | 1522.15 | 21.72 | 78.00 | 302.17 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:30 | 3621.91 | 19.94 | 85.67 | 382.33 | 1517.19 | 21.70 | 56.50 | 334.00 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:40 | 3271.96 | 19.20 | 107.67 | 393.83 | 1435.64 | 21.45 | 75.83 | 360.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-04:00 | 3103.14 | 19.51 | 113.83 | 400.00 | 1349.26 | 21.39 | 74.67 | 359.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 2894.46 | 19.91 | 106.50 | 370.50 | 1223.68 | 20.81 | 54.67 | 334.00 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 2831.28 | 19.76 | 67.17 | 315.17 | 1600.77 | 23.05 | 66.17 | 276.67 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-06:00 | 1839.96 | 19.18 | 77.67 | 281.00 | 965.33 | 21.03 | 57.00 | 237.83 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:40 | 1305.82 | 18.24 | 69.67 | 221.50 | 738.54 | 21.24 | 75.33 | 160.33 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-07:00 | 1143.97 | 18.40 | 55.17 | 217.83 | 568.51 | 20.25 | 54.50 | 156.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2506.86 | 19.48 | 1026.17 | 3706.00 | 1181.03 | 21.38 | 789.83 | 3171.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1143.97 | 18.24 | 55.17 | 217.83 | 568.51 | 20.25 | 50.17 | 156.67 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3621.91 | 20.28 | 113.83 | 400.00 | 1600.77 | 23.05 | 78.17 | 360.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.62 | 01-JAN-08:00 | 563.46 | 10.72 | 0.00 | 207.33 | 317.06 | 14.77 | 0.00 | 92.50 |
February | 262.50 | 0.64 | 0.62 | 01-FEB-09:30 | 742.42 | 12.14 | 0.00 | 234.00 | 414.63 | 16.02 | 0.00 | 170.33 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 782.07 | 12.92 | 0.00 | 304.00 | 461.85 | 16.89 | 0.00 | 244.33 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:40 | 907.95 | 13.62 | 0.00 | 344.00 | 535.85 | 17.52 | 0.00 | 298.83 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-05:40 | 1072.92 | 14.83 | 3.33 | 393.83 | 661.97 | 20.05 | 25.50 | 350.33 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:49 | 1216.33 | 18.17 | 73.83 | 408.83 | 716.58 | 20.20 | 42.50 | 381.67 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:10 | 1156.98 | 17.75 | 71.00 | 413.50 | 680.28 | 19.92 | 41.50 | 380.67 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-05:49 | 1021.05 | 14.40 | 0.00 | 380.83 | 612.27 | 18.35 | 0.00 | 341.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 847.09 | 14.18 | 0.00 | 312.50 | 532.21 | 18.13 | 0.00 | 253.33 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:10 | 686.75 | 11.92 | 0.00 | 270.33 | 398.09 | 15.88 | 0.00 | 191.50 |
November | 258.33 | 0.65 | 0.62 | 01-NOV-07:00 | 547.12 | 10.30 | 0.00 | 204.50 | 306.06 | 14.19 | 0.00 | 90.50 |
December | 230.67 | 0.64 | 0.62 | 01-DEC-11:20 | 568.85 | 10.63 | 0.00 | 192.50 | 312.24 | 14.60 | 0.00 | 84.67 |
Annual Sum or Average | 3928.50 | 0.63 | 885.10 | 13.93 | 148.17 | 3666.17 | 522.13 | 17.57 | 109.50 | 2880.33 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 547.12 | 10.30 | 0.00 | 192.50 | 306.06 | 14.19 | 0.00 | 84.67 | |
Maximum of Months | 439.00 | 0.65 | 0.62 | 1216.33 | 18.17 | 73.83 | 413.50 | 716.58 | 20.20 | 42.50 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.62 | 01-JAN-08:00 | 1222.23 | 18.46 | 63.83 | 224.83 | 681.97 | 21.60 | 75.33 | 168.33 |
February | 262.50 | 0.63 | 0.62 | 01-FEB-09:30 | 1694.76 | 19.12 | 67.33 | 242.00 | 906.74 | 22.14 | 80.50 | 204.83 |
March | 339.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2484.81 | 20.27 | 99.83 | 314.33 | 1388.60 | 22.14 | 79.00 | 274.00 |
April | 371.17 | 0.63 | 0.62 | 01-APR-06:00 | 2907.14 | 19.59 | 103.67 | 337.17 | 1213.89 | 20.23 | 49.33 | 300.50 |
May | 332.17 | 0.63 | 0.62 | 01-MAY-06:30 | 3135.51 | 16.70 | 43.00 | 381.67 | 1696.85 | 18.19 | 0.00 | 337.17 |
June | 430.67 | 0.63 | 0.62 | 01-JUN-05:00 | 3292.11 | 16.46 | 52.50 | 392.50 | 1383.66 | 18.15 | 0.00 | 357.83 |
July | 439.00 | 0.63 | 0.62 | 01-JUL-05:00 | 2919.42 | 16.52 | 54.50 | 397.67 | 1306.73 | 18.33 | 3.67 | 360.33 |
August | 406.00 | 0.63 | 0.62 | 01-AUG-06:10 | 2663.52 | 18.58 | 84.50 | 374.50 | 1480.84 | 20.64 | 53.67 | 331.67 |
September | 289.17 | 0.63 | 0.62 | 01-SEP-07:40 | 3043.97 | 21.12 | 83.50 | 313.83 | 1256.29 | 21.42 | 43.17 | 279.17 |
October | 314.33 | 0.64 | 0.62 | 01-OCT-07:19 | 1725.19 | 18.82 | 73.83 | 278.50 | 900.16 | 20.89 | 57.17 | 237.17 |
November | 258.33 | 0.64 | 0.62 | 01-NOV-07:00 | 1264.29 | 18.17 | 71.33 | 218.67 | 684.32 | 20.90 | 70.33 | 163.67 |
December | 230.67 | 0.63 | 0.62 | 01-DEC-09:30 | 1189.47 | 18.28 | 50.67 | 212.67 | 617.49 | 20.23 | 55.17 | 155.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2424.53 | 18.39 | 848.50 | 3688.33 | 1179.49 | 20.23 | 567.33 | 3169.67 | ||
Minimum of Months | 230.67 | 0.63 | 0.62 | 1189.47 | 16.46 | 43.00 | 212.67 | 617.49 | 18.15 | 0.00 | 155.00 | |
Maximum of Months | 439.00 | 0.64 | 0.62 | 3292.11 | 21.12 | 103.67 | 397.67 | 1696.85 | 22.14 | 80.50 | 360.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.722212E+09 | 29239.04 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77620121.53 | 29239.04 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 741965.47 | 12366.09 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 32044033.32 | 29239.04 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.832618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.722212E+09 | 29239.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107279E+11 | 11977.55 | 11-JAN-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.941359E+10 | 11936.63 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612528E+10 | 12006.23 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354266E+10 | 12021.23 | 11-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148658E+10 | 11977.26 | 10-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402690E+09 | 12090.49 | 13-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93098343.34 | 10712.33 | 13-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209710E+09 | 12283.30 | 01-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.561301E+09 | 12255.86 | 18-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204695E+10 | 11995.22 | 13-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450477E+10 | 11984.51 | 20-NOV-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.933386E+10 | 11956.80 | 01-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.484484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 93098343.34 | 10712.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107279E+11 | 12283.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.403850E+10 | 9742.36 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338100E+10 | 9726.28 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155118E+10 | 9709.43 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397916E+09 | 9678.38 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15898822.98 | 5101.02 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1026682.51 | 2226.59 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95766366.87 | 9675.46 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.826655E+09 | 9687.08 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325145E+10 | 9709.91 | 12-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.403850E+10 | 9742.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.557485E+10 | 8223.68 | 03-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481403E+10 | 8207.70 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252478E+10 | 8242.27 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.588359E+09 | 8203.65 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10913244.50 | 8195.93 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76232928.61 | 8195.65 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.670914E+09 | 8202.48 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401656E+10 | 8205.09 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.557485E+10 | 8242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435392E+10 | 10253.92 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367197E+10 | 10236.97 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174984E+10 | 10219.15 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555414E+09 | 10184.27 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31209661.75 | 10219.36 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1159857.72 | 1025.85 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140094E+09 | 10183.50 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936081E+09 | 10185.21 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337742E+10 | 10219.75 | 12-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435392E+10 | 10253.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312155E+10 | 25542.31 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241817E+10 | 25542.31 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357875E+09 | 25542.31 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34252750.56 | 25542.31 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6856923.69 | 25542.31 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138962E+09 | 25542.31 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204784E+10 | 25542.31 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.812552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.312155E+10 | 25542.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450979E+10 | 13593.57 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385464E+10 | 13579.11 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131059E+10 | 13577.78 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405241E+09 | 13578.49 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12080712.80 | 13557.60 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3524510.82 | 4394.79 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204150E+09 | 13476.69 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111335E+10 | 13582.35 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409425E+10 | 13609.59 | 13-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450979E+10 | 13609.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428313E+10 | 10898.44 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361671E+10 | 10898.44 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150820E+10 | 10898.44 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373099E+09 | 10898.44 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8253312.50 | 4414.65 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8039767.19 | 6129.39 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342868E+09 | 10898.44 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141815E+10 | 10898.44 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395148E+10 | 10898.44 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428313E+10 | 10898.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545845E+10 | 9189.89 | 17-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468341E+10 | 9211.32 | 15-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192744E+10 | 9198.64 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341651E+09 | 9186.84 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 746997.59 | 4300.43 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1477395.20 | 1972.60 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199856E+09 | 9217.98 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110058E+10 | 9233.58 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463156E+10 | 9234.95 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545845E+10 | 9234.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.449123E+10 | 10999.30 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380458E+10 | 10999.30 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168299E+10 | 10999.30 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520360E+09 | 10999.30 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24322451.50 | 10999.30 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12875847.96 | 5507.18 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420345E+09 | 10999.30 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146259E+10 | 10999.30 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398568E+10 | 10999.30 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.449123E+10 | 10999.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.761736E+10 | 34065.02 | 18-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642107E+10 | 34079.86 | 23-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231344E+10 | 34149.52 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435803E+09 | 34065.67 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 347837.83 | 4637.84 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.271048E+09 | 34140.14 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152848E+10 | 34120.60 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643652E+10 | 34091.37 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.761736E+10 | 34149.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.706645E+10 | 15014.88 | 18-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.630462E+10 | 15049.75 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275283E+10 | 15016.72 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112666E+10 | 15056.44 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128119E+09 | 14940.06 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5344781.43 | 5375.29 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41625910.97 | 11205.90 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.835047E+09 | 15056.49 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252151E+10 | 15060.21 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677192E+10 | 15064.55 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706645E+10 | 15064.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594772E+10 | 11891.39 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.517529E+10 | 11879.23 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245449E+10 | 11864.15 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790756E+09 | 11862.05 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61835038.43 | 9353.49 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50172886.17 | 7320.33 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.823750E+09 | 11885.90 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235171E+10 | 11882.52 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567215E+10 | 11941.61 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594772E+10 | 11941.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844135E+10 | 10526.73 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744273E+10 | 10514.02 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.372935E+10 | 10521.64 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106232E+10 | 10536.14 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50575139.94 | 10438.35 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32508816.23 | 10458.70 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922509E+09 | 10518.25 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268392E+10 | 10535.65 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759050E+10 | 10524.20 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.844135E+10 | 10536.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.643635E+10 | 13071.44 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.562226E+10 | 13084.50 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286526E+10 | 13052.16 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115498E+10 | 13044.65 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164488E+09 | 13070.47 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9064356.61 | 4603.19 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2159986.12 | 1451.39 | 31-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91050461.49 | 7338.18 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109814E+10 | 13008.30 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262696E+10 | 13088.21 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.593862E+10 | 13067.08 | 22-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.643635E+10 | 13088.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144484E+11 | 22415.51 | 04-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134229E+11 | 26263.67 | 07-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628559E+10 | 21207.00 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.851836E+09 | 11604.79 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9583314.08 | 3802.86 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.335097E+09 | 9783.67 | 17-OCT-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187519E+10 | 11074.18 | 24-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120037E+11 | 26528.09 | 11-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144484E+11 | 26528.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171188E+11 | 24178.48 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158353E+11 | 28565.26 | 07-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.831584E+10 | 24591.62 | 07-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173889E+10 | 15015.08 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31484351.30 | 5596.19 | 01-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 150007.45 | 262.99 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.813552E+09 | 12179.34 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372982E+10 | 14001.97 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146573E+11 | 29151.72 | 11-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.622412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171188E+11 | 29151.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184208E+11 | 26548.02 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169761E+11 | 31638.53 | 07-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.860213E+10 | 27140.50 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198468E+10 | 16949.89 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71455722.06 | 7684.91 | 01-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 322274.59 | 587.70 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18356784.28 | 2274.85 | 30-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108780E+10 | 14829.17 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418526E+10 | 15734.96 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158974E+11 | 27745.62 | 11-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.672443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184208E+11 | 31638.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.217397E+10 | 0.185418E+10 | 32844.37 | 15-MAR-14:00 | 32844.37 | 0.00 |
April | 0.00 | 0.00 | 0.757559E+09 | 0.695127E+09 | 14761.66 | 07-APR-13:00 | 14761.66 | 0.00 |
May | 0.00 | 0.00 | 0.806638E+10 | 0.736719E+10 | 39549.42 | 23-MAY-15:10 | 39549.42 | 0.00 |
June | 0.00 | 0.00 | 0.390687E+11 | 0.297042E+11 | 100713.55 | 27-JUN-07:40 | 43523.18 | 0.00 |
July | 0.00 | 0.00 | 0.693189E+11 | 0.492119E+11 | 123483.25 | 20-JUL-04:02 | 50511.44 | 0.00 |
August | 0.00 | 0.00 | 0.589747E+11 | 0.455453E+11 | 123456.62 | 14-AUG-08:00 | 52104.49 | 0.00 |
September | 0.00 | 0.00 | 0.261236E+11 | 0.196598E+11 | 84645.41 | 15-SEP-14:50 | 45832.24 | 0.00 |
October | 0.00 | 0.00 | 0.280812E+10 | 0.240788E+10 | 32300.80 | 11-OCT-15:10 | 32300.80 | 0.00 |
November | 0.00 | 0.00 | 0.504721E+09 | 0.377544E+09 | 12177.19 | 16-NOV-18:00 | 9713.51 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207797E+12 | 0.156823E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.693189E+11 | 0.492119E+11 | 123483.25 | 52104.49 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.203711E+10 | 0.173013E+10 | 34187.46 | 15-MAR-13:50 | 34187.46 | 0.00 |
April | 0.00 | 0.00 | 0.732973E+09 | 0.678899E+09 | 14388.24 | 08-APR-13:30 | 13069.41 | 0.00 |
May | 0.00 | 0.00 | 0.803921E+10 | 0.733451E+10 | 40081.55 | 23-MAY-14:30 | 40081.55 | 0.00 |
June | 0.00 | 0.00 | 0.371717E+11 | 0.283979E+11 | 87363.01 | 27-JUN-07:40 | 37786.03 | 0.00 |
July | 0.00 | 0.00 | 0.641051E+11 | 0.455289E+11 | 114489.86 | 20-JUL-04:02 | 47601.94 | 0.00 |
August | 0.00 | 0.00 | 0.523552E+11 | 0.406628E+11 | 114317.08 | 14-AUG-04:02 | 42510.88 | 0.00 |
September | 0.00 | 0.00 | 0.226811E+11 | 0.170481E+11 | 76384.36 | 16-SEP-05:02 | 34319.30 | 0.00 |
October | 0.00 | 0.00 | 0.251329E+10 | 0.212669E+10 | 27843.08 | 11-OCT-15:00 | 27843.08 | 0.00 |
November | 0.00 | 0.00 | 0.449901E+09 | 0.327068E+09 | 10478.01 | 16-NOV-18:00 | 7989.19 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190086E+12 | 0.143835E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.641051E+11 | 0.455289E+11 | 114489.86 | 47601.94 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.224327E+10 | 0.192010E+10 | 41473.01 | 15-MAR-14:00 | 41473.01 | 0.00 |
April | 0.00 | 0.00 | 0.761276E+09 | 0.694200E+09 | 15399.95 | 08-APR-13:30 | 13549.88 | 0.00 |
May | 0.00 | 0.00 | 0.840454E+10 | 0.757674E+10 | 45739.43 | 10-MAY-15:00 | 45145.90 | 0.00 |
June | 0.00 | 0.00 | 0.396829E+11 | 0.299973E+11 | 127223.44 | 27-JUN-15:00 | 56063.25 | 0.00 |
July | 0.00 | 0.00 | 0.684600E+11 | 0.485931E+11 | 127477.93 | 20-JUL-04:02 | 51929.50 | 0.00 |
August | 0.00 | 0.00 | 0.553442E+11 | 0.426914E+11 | 127285.55 | 14-AUG-04:02 | 47414.17 | 0.00 |
September | 0.00 | 0.00 | 0.230438E+11 | 0.168546E+11 | 88743.83 | 15-SEP-12:30 | 49383.21 | 0.00 |
October | 0.00 | 0.00 | 0.245131E+10 | 0.200981E+10 | 27252.09 | 11-OCT-15:00 | 27252.09 | 0.00 |
November | 0.00 | 0.00 | 0.482143E+09 | 0.345441E+09 | 11295.69 | 16-NOV-18:00 | 8471.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200874E+12 | 0.150683E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.684600E+11 | 0.485931E+11 | 127477.93 | 56063.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1975.43 | 6957.32 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2013.75 | 6981.28 | 15-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2118.77 | 6957.12 | 01-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1905.60 | 6733.55 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1871.67 | 6421.19 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1809.19 | 6020.51 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1585.65 | 5668.80 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1712.80 | 5521.79 | 31-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1626.93 | 5684.93 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1700.23 | 6031.81 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1827.56 | 6410.64 | 29-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1851.27 | 6743.61 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1832.20 | ||||
Minimum of Months | 0.00 | 0.00 | 1585.65 | 5521.79 | ||
Maximum of Months | 0.00 | 0.00 | 2118.77 | 6981.28 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.189235E+10 | 0.33 | 2748.44 | 02-JAN-05:01 | 0.81 |
February | 0.168979E+10 | 0.33 | 2748.44 | 06-FEB-07:02 | 0.81 |
March | 0.200231E+10 | 0.33 | 3292.42 | 16-MAR-05:03 | 0.88 |
April | 0.204219E+10 | 0.32 | 3818.79 | 25-APR-05:02 | 0.96 |
May | 0.290475E+10 | 0.37 | 5366.64 | 09-MAY-05:02 | 1.18 |
June | 0.468512E+10 | 0.50 | 8731.05 | 12-JUN-12:10 | 1.58 |
July | 0.587627E+10 | 0.55 | 11793.86 | 17-JUL-04:02 | 1.91 |
August | 0.596477E+10 | 0.56 | 11793.86 | 14-AUG-04:02 | 1.91 |
September | 0.406858E+10 | 0.46 | 7834.15 | 18-SEP-12:10 | 1.49 |
October | 0.240168E+10 | 0.33 | 5366.64 | 02-OCT-05:02 | 1.18 |
November | 0.184662E+10 | 0.31 | 3125.67 | 02-NOV-07:03 | 0.86 |
December | 0.174028E+10 | 0.30 | 2748.44 | 11-DEC-07:01 | 0.81 |
Annual Sum or Average | 0.371147E+11 | 0.39 | |||
Minimum of Months | 0.168979E+10 | 0.30 | 2748.44 | 0.81 | |
Maximum of Months | 0.596477E+10 | 0.56 | 11793.86 | 1.91 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199368E+10 | 0.36 | 2755.18 | 02-JAN-05:01 | 0.86 |
February | 0.176992E+10 | 0.35 | 2755.18 | 01-FEB-07:01 | 0.86 |
March | 0.193352E+10 | 0.34 | 3147.31 | 15-MAR-13:50 | 0.92 |
April | 0.182115E+10 | 0.32 | 3001.62 | 21-APR-15:30 | 0.90 |
May | 0.265371E+10 | 0.38 | 5245.35 | 23-MAY-14:30 | 1.25 |
June | 0.451005E+10 | 0.52 | 8957.46 | 12-JUN-15:20 | 1.72 |
July | 0.554423E+10 | 0.56 | 10649.97 | 17-JUL-04:02 | 1.92 |
August | 0.531158E+10 | 0.56 | 10649.97 | 14-AUG-04:02 | 1.92 |
September | 0.328886E+10 | 0.43 | 7782.78 | 21-SEP-15:40 | 1.58 |
October | 0.191833E+10 | 0.32 | 3769.73 | 11-OCT-15:20 | 1.02 |
November | 0.163933E+10 | 0.31 | 2755.18 | 21-NOV-07:01 | 0.86 |
December | 0.188201E+10 | 0.34 | 2755.18 | 04-DEC-06:01 | 0.86 |
Annual Sum or Average | 0.342664E+11 | 0.40 | |||
Minimum of Months | 0.163933E+10 | 0.31 | 2755.18 | 0.86 | |
Maximum of Months | 0.554423E+10 | 0.56 | 10649.97 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245110E+10 | 0.41 | 2716.72 | 02-JAN-05:01 | 0.79 |
February | 0.223313E+10 | 0.41 | 2716.72 | 01-FEB-06:01 | 0.79 |
March | 0.211744E+10 | 0.35 | 3327.32 | 15-MAR-13:50 | 0.87 |
April | 0.183673E+10 | 0.31 | 2818.28 | 21-APR-15:30 | 0.80 |
May | 0.247524E+10 | 0.35 | 5060.62 | 31-MAY-16:00 | 1.11 |
June | 0.417353E+10 | 0.46 | 12147.00 | 27-JUN-14:55 | 1.90 |
July | 0.515825E+10 | 0.50 | 12147.00 | 17-JUL-04:02 | 1.91 |
August | 0.481528E+10 | 0.49 | 12147.00 | 14-AUG-04:02 | 1.91 |
September | 0.285323E+10 | 0.38 | 7297.96 | 21-SEP-15:30 | 1.39 |
October | 0.185782E+10 | 0.30 | 3126.52 | 11-OCT-15:30 | 0.84 |
November | 0.172949E+10 | 0.30 | 2716.72 | 03-NOV-06:01 | 0.79 |
December | 0.230162E+10 | 0.39 | 2716.72 | 02-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.340028E+11 | 0.39 | |||
Minimum of Months | 0.172949E+10 | 0.30 | 2716.72 | 0.79 | |
Maximum of Months | 0.515825E+10 | 0.50 | 12147.00 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 56.86 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.11 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.50 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 56.51 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.88 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.29 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.06 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.41 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.93 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.62 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 56.65 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 55.65 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.50 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.62 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.19 | 56.19 | 1975.43 | 6957.32 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.62 | 56.62 | 2013.75 | 6981.28 | 15-FEB-12:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.89 | 55.89 | 2118.77 | 6957.12 | 01-MAR-12:06 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.98 | 56.98 | 1905.60 | 6733.55 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.55 | 56.55 | 1871.67 | 6421.19 | 02-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.72 | 56.72 | 1809.19 | 6020.51 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.45 | 56.45 | 1585.65 | 5668.80 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.52 | 57.52 | 1712.80 | 5521.79 | 31-AUG-11:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.32 | 57.32 | 1626.93 | 5684.93 | 28-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.52 | 55.52 | 1700.23 | 6031.81 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.09 | 57.09 | 1827.56 | 6410.64 | 29-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.10 | 56.10 | 1851.27 | 6743.61 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1832.20 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.52 | 55.52 | 1585.65 | 5521.79 | ||
Maximum of Months | 0.00 | 0.00 | 57.52 | 57.52 | 2118.77 | 6981.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.273098E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.230480E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145040E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.733548E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.653718E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.146137E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.226520E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.204436E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.109720E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.550585E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.892460E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.217516E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.183598E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.550585E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.273098E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.238578E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201474E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.923416E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.369822E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.477126E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.135667E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.209606E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.180019E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.884800E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.376395E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.699777E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.205928E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154441E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.369822E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.238578E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.379603E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.331991E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167983E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.661820E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.505655E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138795E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.216660E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182908E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.873567E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.646999E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135761E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.347113E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.216962E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.505655E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.379603E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.189235E+10 | 0.00 | 0.398658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168979E+10 | 0.00 | 0.347811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200231E+10 | 0.217397E+10 | 0.182374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204219E+10 | 0.757559E+09 | 0.593619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290475E+10 | 0.806638E+10 | 0.155418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468512E+10 | 0.390687E+11 | 0.402690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587627E+10 | 0.693189E+11 | 93098343.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.596477E+10 | 0.589747E+11 | 0.209710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406858E+10 | 0.261236E+11 | 0.563487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240168E+10 | 0.280812E+10 | 0.269414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184662E+10 | 0.504721E+09 | 0.881361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174028E+10 | 0.00 | 0.320150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371147E+11 | 0.207797E+12 | 0.145166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168979E+10 | 0.00 | 93098343.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.596477E+10 | 0.693189E+11 | 0.398658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199368E+10 | 0.00 | 0.389830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176992E+10 | 0.00 | 0.342128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193352E+10 | 0.203711E+10 | 0.151029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182115E+10 | 0.732973E+09 | 0.341349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265371E+10 | 0.803921E+10 | 76887825.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451005E+10 | 0.371717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.554423E+10 | 0.641051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.531158E+10 | 0.523552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328886E+10 | 0.226811E+11 | 26067528.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191833E+10 | 0.251329E+10 | 0.198763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163933E+10 | 0.449901E+09 | 0.896346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188201E+10 | 0.00 | 0.333681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342664E+11 | 0.190086E+12 | 0.136134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.554423E+10 | 0.641051E+11 | 0.389830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.245110E+10 | 0.00 | 0.539301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223313E+10 | 0.00 | 0.479421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211744E+10 | 0.224327E+10 | 0.227175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183673E+10 | 0.761276E+09 | 0.655520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247524E+10 | 0.840454E+10 | 0.476821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.417353E+10 | 0.396829E+11 | 14731412.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.515825E+10 | 0.684600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.481528E+10 | 0.553442E+11 | 2159986.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285323E+10 | 0.230438E+11 | 0.233715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185782E+10 | 0.245131E+10 | 0.503830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172949E+10 | 0.482143E+09 | 0.158978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230162E+10 | 0.00 | 0.483071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340028E+11 | 0.200874E+12 | 0.201115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.515825E+10 | 0.684600E+11 | 0.539301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.189235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200231E+10 | 0.00 | 0.00 | 0.00 | 0.549874E+09 | 0.119518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204219E+10 | 0.00 | 0.00 | 0.00 | 0.208938E+09 | 0.508435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290475E+10 | 0.00 | 0.00 | 0.00 | 0.208783E+10 | 0.154460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.468512E+10 | 0.00 | 0.00 | 0.00 | 0.952588E+10 | 0.402690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587627E+10 | 0.00 | 0.00 | 0.00 | 0.166826E+11 | 93098343.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.596477E+10 | 0.00 | 0.00 | 0.00 | 0.142691E+11 | 0.209710E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406858E+10 | 0.00 | 0.00 | 0.00 | 0.633997E+10 | 0.563487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.240168E+10 | 0.00 | 0.00 | 0.00 | 0.745130E+09 | 0.235904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.184662E+10 | 0.00 | 0.00 | 0.00 | 0.139556E+09 | 0.693842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371147E+11 | 0.00 | 0.00 | 0.00 | 0.505489E+11 | 0.959342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93098343.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.596477E+10 | 0.00 | 0.00 | 0.00 | 0.166826E+11 | 0.254174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193352E+10 | 0.00 | 0.00 | 0.00 | 0.513540E+09 | 0.678710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182115E+10 | 0.00 | 0.00 | 0.00 | 0.202461E+09 | 0.167460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265371E+10 | 0.00 | 0.00 | 0.00 | 0.207215E+10 | 45403474.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451005E+10 | 0.00 | 0.00 | 0.00 | 0.905664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.554423E+10 | 0.00 | 0.00 | 0.00 | 0.154164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.531158E+10 | 0.00 | 0.00 | 0.00 | 0.126903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328886E+10 | 0.00 | 0.00 | 0.00 | 0.553322E+10 | 25917521.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191833E+10 | 0.00 | 0.00 | 0.00 | 0.671539E+09 | 0.117408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163933E+10 | 0.00 | 0.00 | 0.00 | 0.124803E+09 | 0.523364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342664E+11 | 0.00 | 0.00 | 0.00 | 0.462811E+11 | 0.738932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.554423E+10 | 0.00 | 0.00 | 0.00 | 0.154164E+11 | 0.218642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.245110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211744E+10 | 0.00 | 0.00 | 0.00 | 0.565509E+09 | 0.141154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183673E+10 | 0.00 | 0.00 | 0.00 | 0.210960E+09 | 0.457052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247524E+10 | 0.00 | 0.00 | 0.00 | 0.217595E+10 | 0.405365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.417353E+10 | 0.00 | 0.00 | 0.00 | 0.969160E+10 | 14409138.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.515825E+10 | 0.00 | 0.00 | 0.00 | 0.165078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.481528E+10 | 0.00 | 0.00 | 0.00 | 0.134734E+11 | 2159986.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285323E+10 | 0.00 | 0.00 | 0.00 | 0.566709E+10 | 0.215358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185782E+10 | 0.00 | 0.00 | 0.00 | 0.661672E+09 | 0.395050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172949E+10 | 0.00 | 0.00 | 0.00 | 0.134043E+09 | 0.117126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340028E+11 | 0.00 | 0.00 | 0.00 | 0.490879E+11 | 0.133871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.515825E+10 | 0.00 | 0.00 | 0.00 | 0.165078E+11 | 0.355092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138796E+11 | 0.00 | 0.00 | 1562869.46 | 0.00 | 0.405482E+09 | 0.268506E+10 | 0.00 | 0.28 |
February | 0.130027E+11 | 0.00 | 0.00 | 1828062.38 | 0.00 | 12824110.01 | 0.284550E+10 | 0.00 | 0.28 |
March | 0.717275E+10 | 7497152.67 | 0.00 | 18346718.43 | 0.00 | 752561.07 | 0.978082E+10 | 0.00 | 0.40 |
April | 0.323157E+10 | 0.00 | 0.00 | 25775577.88 | 0.00 | 0.00 | 0.139669E+11 | 0.00 | 0.53 |
May | 0.114781E+10 | 1871785.80 | 0.00 | 40698766.01 | 5561127.15 | 0.00 | 0.195376E+11 | 0.00 | 0.95 |
June | 0.859546E+09 | 0.170279E+10 | 0.00 | 36662126.48 | 0.144126E+09 | 0.00 | 0.125144E+11 | 0.00 | 1.17 |
July | 0.419916E+09 | 0.608777E+10 | 0.00 | 19244741.31 | 0.415860E+09 | 0.00 | 0.400788E+10 | 0.00 | 0.92 |
August | 0.650290E+09 | 0.343204E+10 | 0.00 | 35344966.81 | 0.180459E+09 | 0.00 | 0.843143E+10 | 0.00 | 1.12 |
September | 0.157652E+10 | 0.121874E+10 | 0.00 | 37794428.97 | 18204009.42 | 0.00 | 0.148321E+11 | 0.00 | 1.16 |
October | 0.170583E+10 | 0.00 | 0.00 | 33390201.77 | 150714.98 | 0.00 | 0.176263E+11 | 0.00 | 0.67 |
November | 0.435753E+10 | 0.00 | 0.00 | 22417370.76 | 3233722.59 | 0.00 | 0.110068E+11 | 0.00 | 0.40 |
December | 0.112442E+11 | 0.00 | 0.00 | 5501248.94 | 0.00 | 6336698.81 | 0.507866E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.592483E+11 | 0.124507E+11 | 0.00 | 0.278567E+09 | 0.767594E+09 | 0.425395E+09 | 0.122314E+12 | 0.00 | 0.68 |
Minimum of Months | 0.419916E+09 | 0.00 | 0.00 | 1562869.46 | 0.00 | 0.00 | 0.268506E+10 | 0.00 | 0.28 |
Maximum of Months | 0.138796E+11 | 0.608777E+10 | 0.00 | 40698766.01 | 0.415860E+09 | 0.405482E+09 | 0.195376E+11 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191767E+10 | 0.00 | 0.00 | 0.25 |
February | 0.122824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179468E+10 | 0.00 | 0.00 | 0.25 |
March | 0.119869E+11 | 2672903.33 | 0.00 | 2058065.31 | 3585103.15 | 0.152367E+09 | 0.133834E+10 | 0.00 | 0.31 |
April | 0.734858E+10 | 0.00 | 0.00 | 5540945.52 | 0.00 | 37843791.46 | 0.423719E+10 | 0.00 | 0.36 |
May | 0.340618E+10 | 441243.51 | 0.00 | 19001150.08 | 14308820.54 | 0.00 | 0.102266E+11 | 0.00 | 0.63 |
June | 0.869342E+09 | 0.130926E+10 | 0.00 | 22814513.50 | 0.127450E+09 | 0.00 | 0.809050E+10 | 0.00 | 0.81 |
July | 0.475321E+09 | 0.460050E+10 | 0.00 | 13291115.46 | 0.387537E+09 | 0.00 | 0.257657E+10 | 0.00 | 0.68 |
August | 0.716299E+09 | 0.252285E+10 | 0.00 | 23242306.81 | 0.115083E+09 | 0.00 | 0.527100E+10 | 0.00 | 0.77 |
September | 0.207088E+10 | 0.830841E+09 | 0.00 | 19958254.54 | 21722764.63 | 0.00 | 0.806005E+10 | 0.00 | 0.75 |
October | 0.616664E+10 | 0.00 | 0.00 | 7873903.64 | 1800965.84 | 548271.07 | 0.530958E+10 | 0.00 | 0.40 |
November | 0.944327E+10 | 0.00 | 0.00 | 758013.40 | 5336878.00 | 49433875.09 | 0.114250E+10 | 0.00 | 0.29 |
December | 0.130631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120010E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.811525E+11 | 0.926657E+10 | 0.00 | 0.114538E+09 | 0.676825E+09 | 0.515264E+10 | 0.462523E+11 | 0.00 | 0.48 |
Minimum of Months | 0.475321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.133236E+11 | 0.460050E+10 | 0.00 | 23242306.81 | 0.387537E+09 | 0.191767E+10 | 0.102266E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.831765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563170E+10 | 0.00 | 0.00 | 0.24 |
February | 0.841156E+10 | 0.00 | 0.00 | 0.00 | 21594.96 | 0.457337E+10 | 0.00 | 0.00 | 0.24 |
March | 0.106130E+11 | 296352.45 | 0.00 | 1606336.27 | 297545.96 | 0.114496E+10 | 0.804629E+09 | 0.00 | 0.31 |
April | 0.829918E+10 | 0.00 | 0.00 | 2669027.86 | 0.00 | 0.146465E+09 | 0.273017E+10 | 0.00 | 0.35 |
May | 0.439589E+10 | 489873.27 | 0.00 | 15526074.00 | 14557364.10 | 0.00 | 0.881745E+10 | 0.00 | 0.61 |
June | 0.140141E+10 | 0.139523E+10 | 0.00 | 20631124.87 | 0.201818E+09 | 0.00 | 0.746405E+10 | 0.00 | 0.84 |
July | 0.524425E+09 | 0.473665E+10 | 0.00 | 11907908.56 | 0.410104E+09 | 0.00 | 0.232768E+10 | 0.00 | 0.73 |
August | 0.995682E+09 | 0.257553E+10 | 0.00 | 19843885.64 | 0.207567E+09 | 0.00 | 0.442289E+10 | 0.00 | 0.79 |
September | 0.307207E+10 | 0.836104E+09 | 0.00 | 14368390.23 | 54810900.73 | 0.00 | 0.592962E+10 | 0.00 | 0.71 |
October | 0.742514E+10 | 0.00 | 0.00 | 3570816.13 | 37981.19 | 0.112656E+09 | 0.282666E+10 | 0.00 | 0.38 |
November | 0.923437E+10 | 0.00 | 288913.13 | 44781.24 | 8980652.00 | 0.454666E+09 | 0.137133E+09 | 31203.73 | 0.28 |
December | 0.840806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456674E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.710985E+11 | 0.954430E+10 | 288913.13 | 90168344.80 | 0.898194E+09 | 0.166306E+11 | 0.354603E+11 | 31203.73 | 0.48 |
Minimum of Months | 0.524425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.106130E+11 | 0.473665E+10 | 288913.13 | 20631124.87 | 0.410104E+09 | 0.563170E+10 | 0.881745E+10 | 31203.73 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 60404600.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394193E+10 | 0.00 | 0.00 | 0.32 |
February | 0.193084E+09 | 0.00 | 0.00 | 0.00 | 966.51 | 0.357559E+10 | 0.00 | 5884.54 | 0.33 |
March | 0.133136E+10 | 80782.78 | 0.00 | 236205.46 | 81108.12 | 0.206518E+10 | 69123621.07 | 0.00 | 0.40 |
April | 0.223728E+10 | 0.00 | 0.00 | 177226.36 | 0.00 | 0.551816E+09 | 0.210445E+09 | 0.00 | 0.44 |
May | 0.186073E+10 | 0.00 | 0.00 | 2556080.69 | 4039964.50 | 20353834.38 | 0.141073E+10 | 0.00 | 0.73 |
June | 0.560714E+09 | 0.447217E+09 | 0.00 | 4861169.05 | 59081119.00 | 0.00 | 0.164268E+10 | 0.00 | 1.08 |
July | 0.190747E+09 | 0.144802E+10 | 0.00 | 2889344.30 | 0.119829E+09 | 0.00 | 0.557384E+09 | 0.00 | 0.98 |
August | 0.455955E+09 | 0.739886E+09 | 0.00 | 4490175.60 | 70398216.64 | 0.00 | 0.916331E+09 | 0.00 | 1.01 |
September | 0.128162E+10 | 0.204207E+09 | 0.00 | 2289947.26 | 38428517.35 | 10765271.16 | 0.911073E+09 | 0.00 | 0.84 |
October | 0.216700E+10 | 0.00 | 0.00 | 187791.73 | 10353.30 | 0.413553E+09 | 0.190852E+09 | 0.00 | 0.48 |
November | 0.121172E+10 | 0.00 | 254690.18 | 0.00 | 2278311.18 | 0.147848E+10 | 0.00 | 9861.78 | 0.37 |
December | 0.176338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352618E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.117270E+11 | 0.283941E+10 | 254690.18 | 17687940.45 | 0.294148E+09 | 0.155838E+11 | 0.590862E+10 | 15746.32 | 0.61 |
Minimum of Months | 60404600.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.223728E+10 | 0.144802E+10 | 254690.18 | 4861169.05 | 0.119829E+09 | 0.394193E+10 | 0.164268E+10 | 9861.78 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421987E+10 | 0.00 | 0.00 | 0.55 |
February | 0.742175E+09 | 0.00 | 0.00 | 0.00 | 2875.54 | 0.328701E+10 | 0.00 | 4801.90 | 0.56 |
March | 0.224861E+10 | 188523.37 | 0.00 | 209616.70 | 0.00 | 0.153455E+10 | 79509083.90 | 0.00 | 0.71 |
April | 0.227756E+10 | 0.00 | 0.00 | 1070224.38 | 0.00 | 0.365003E+09 | 0.858301E+09 | 0.00 | 0.82 |
May | 0.182645E+10 | 0.00 | 0.00 | 3767646.39 | 4593457.81 | 8343538.19 | 0.218709E+10 | 0.00 | 1.39 |
June | 0.663005E+09 | 0.397634E+09 | 0.00 | 5122303.64 | 70086587.94 | 0.00 | 0.207073E+10 | 0.00 | 1.84 |
July | 0.180504E+09 | 0.121542E+10 | 0.00 | 4090413.54 | 0.198287E+09 | 0.00 | 0.834006E+09 | 0.00 | 1.68 |
August | 0.490205E+09 | 0.575553E+09 | 0.00 | 4830895.43 | 0.122147E+09 | 0.00 | 0.109299E+10 | 0.00 | 1.69 |
September | 0.130635E+10 | 0.156797E+09 | 0.00 | 3087846.26 | 78632465.80 | 11529469.62 | 0.133932E+10 | 0.00 | 1.51 |
October | 0.252037E+10 | 0.00 | 0.00 | 270491.13 | 11771.75 | 0.368911E+09 | 0.261973E+09 | 0.00 | 0.86 |
November | 0.158667E+10 | 0.00 | 390023.31 | 0.00 | 2453681.06 | 0.145940E+10 | 0.00 | 6994.27 | 0.65 |
December | 0.244829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377983E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.141915E+11 | 0.234559E+10 | 390023.31 | 22449437.46 | 0.476215E+09 | 0.150345E+11 | 0.872391E+10 | 11796.17 | 1.07 |
Minimum of Months | 0.104805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.252037E+10 | 0.121542E+10 | 390023.31 | 5122303.64 | 0.198287E+09 | 0.421987E+10 | 0.218709E+10 | 6994.27 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130066E+10 | 0.00 | 0.00 | 89061.97 | 0.00 | 0.406418E+10 | 0.115455E+09 | 0.00 | 0.44 |
February | 0.151263E+10 | 0.00 | 0.00 | 387230.61 | 3620.09 | 0.340845E+10 | 0.233756E+09 | 6186.53 | 0.46 |
March | 0.260088E+10 | 531463.49 | 0.00 | 1840679.81 | 0.00 | 0.152531E+10 | 0.930125E+09 | 0.00 | 0.61 |
April | 0.249898E+10 | 0.00 | 0.00 | 2757698.39 | 0.00 | 0.573218E+09 | 0.178671E+10 | 0.00 | 0.73 |
May | 0.241379E+10 | 675675.48 | 0.00 | 5301394.78 | 5481531.95 | 48368644.80 | 0.273181E+10 | 0.00 | 1.16 |
June | 0.105892E+10 | 0.500564E+09 | 0.00 | 5937730.06 | 0.104257E+09 | 448284.96 | 0.207727E+10 | 0.00 | 1.44 |
July | 0.350747E+09 | 0.169694E+10 | 0.00 | 3493955.00 | 0.229300E+09 | 0.00 | 0.679335E+09 | 0.00 | 1.26 |
August | 0.724975E+09 | 0.909265E+09 | 0.00 | 6661029.52 | 0.120562E+09 | 0.00 | 0.130847E+10 | 0.00 | 1.44 |
September | 0.146086E+10 | 0.302462E+09 | 0.00 | 7063341.34 | 67781160.54 | 8809625.95 | 0.257676E+10 | 0.00 | 1.54 |
October | 0.248041E+10 | 0.00 | 0.00 | 3627554.95 | 14819.76 | 0.344155E+09 | 0.186869E+10 | 0.00 | 0.87 |
November | 0.200570E+10 | 0.00 | 327560.93 | 888728.35 | 3261184.34 | 0.147046E+10 | 0.486383E+09 | 10696.38 | 0.54 |
December | 0.108093E+10 | 0.00 | 0.00 | 54151.17 | 0.00 | 0.394482E+10 | 68035947.46 | 0.00 | 0.45 |
Annual Sum or Average | 0.194895E+11 | 0.341043E+10 | 327560.93 | 38102555.95 | 0.530661E+09 | 0.153882E+11 | 0.148628E+11 | 16882.92 | 0.91 |
Minimum of Months | 0.350747E+09 | 0.00 | 0.00 | 54151.17 | 0.00 | 0.00 | 68035947.46 | 0.00 | 0.44 |
Maximum of Months | 0.260088E+10 | 0.169694E+10 | 327560.93 | 7063341.34 | 0.229300E+09 | 0.406418E+10 | 0.273181E+10 | 10696.38 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.332632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442401E+10 | 0.00 | 0.00 | 0.61 |
February | 0.630844E+09 | 0.00 | 0.00 | 845.10 | 3167.28 | 0.379371E+10 | 9095765.37 | 5032.05 | 0.62 |
March | 0.214345E+10 | 0.00 | 0.00 | 237526.77 | 202745.97 | 0.194843E+10 | 0.162688E+09 | 0.00 | 0.78 |
April | 0.251456E+10 | 0.00 | 0.00 | 1215411.73 | 0.00 | 0.604837E+09 | 0.811028E+09 | 0.00 | 0.92 |
May | 0.258159E+10 | 93073.69 | 0.00 | 3257311.80 | 5001274.74 | 33051228.55 | 0.181096E+10 | 0.00 | 1.54 |
June | 0.103985E+10 | 0.398565E+09 | 0.00 | 5098158.73 | 0.101752E+09 | 392212.68 | 0.168078E+10 | 0.00 | 1.94 |
July | 0.327823E+09 | 0.121400E+10 | 0.00 | 2885409.36 | 0.254381E+09 | 0.00 | 0.456973E+09 | 0.00 | 1.57 |
August | 0.744540E+09 | 0.598836E+09 | 0.00 | 3916308.01 | 0.141102E+09 | 0.00 | 0.751693E+09 | 0.00 | 1.67 |
September | 0.181385E+10 | 0.134579E+09 | 0.00 | 2457469.25 | 0.102428E+09 | 19446870.62 | 0.958590E+09 | 0.00 | 1.60 |
October | 0.266811E+10 | 0.00 | 0.00 | 537905.28 | 12966.08 | 0.479623E+09 | 0.346262E+09 | 0.00 | 0.96 |
November | 0.158911E+10 | 0.00 | 430386.58 | 372.08 | 2702624.41 | 0.175398E+10 | 11542528.59 | 6911.25 | 0.72 |
December | 0.340931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408620E+10 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.167273E+11 | 0.234608E+10 | 430386.58 | 19606718.10 | 0.607585E+09 | 0.171437E+11 | 0.699961E+10 | 11943.30 | 1.13 |
Minimum of Months | 0.327823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.266811E+10 | 0.121400E+10 | 430386.58 | 5098158.73 | 0.254381E+09 | 0.442401E+10 | 0.181096E+10 | 6911.25 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328932E+10 | 0.00 | 0.00 | 0.26 |
February | 0.165162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304100E+10 | 0.00 | 0.00 | 0.27 |
March | 0.116641E+10 | 0.00 | 0.00 | 33931.94 | 1038480.53 | 0.174415E+10 | 17723033.58 | 0.00 | 0.31 |
April | 0.207431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388070E+09 | 0.00 | 0.00 | 0.35 |
May | 0.191130E+10 | 0.00 | 0.00 | 862332.05 | 1240865.95 | 4203432.54 | 0.520793E+09 | 0.00 | 0.52 |
June | 0.490445E+09 | 0.288057E+09 | 0.00 | 3451554.26 | 36366400.71 | 0.00 | 0.117891E+10 | 0.00 | 0.77 |
July | 0.181514E+09 | 0.107712E+10 | 0.00 | 2341434.82 | 0.101254E+09 | 0.00 | 0.457813E+09 | 0.00 | 0.71 |
August | 0.371884E+09 | 0.615272E+09 | 0.00 | 4161516.72 | 46745245.01 | 0.00 | 0.884371E+09 | 0.00 | 0.82 |
September | 0.962584E+09 | 0.186897E+09 | 0.00 | 2743371.26 | 7383098.79 | 0.00 | 0.109358E+10 | 0.00 | 0.73 |
October | 0.212622E+10 | 0.00 | 0.00 | 470086.32 | 28396.69 | 36760562.99 | 0.325085E+09 | 0.00 | 0.40 |
November | 0.190088E+10 | 0.00 | 892.15 | 0.00 | 605180.34 | 0.481342E+09 | 0.00 | 3203.45 | 0.29 |
December | 0.406403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275697E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.118700E+11 | 0.216734E+10 | 892.15 | 14064227.38 | 0.194662E+09 | 0.117418E+11 | 0.447828E+10 | 3203.45 | 0.48 |
Minimum of Months | 0.112903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.212622E+10 | 0.107712E+10 | 892.15 | 4161516.72 | 0.101254E+09 | 0.328932E+10 | 0.117891E+10 | 3203.45 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352316E+10 | 0.00 | 0.00 | 0.46 |
February | 0.663483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289264E+10 | 0.00 | 0.00 | 0.47 |
March | 0.213167E+10 | 222902.06 | 0.00 | 26316.64 | 1007702.32 | 0.126911E+10 | 6771169.82 | 0.00 | 0.57 |
April | 0.231001E+10 | 0.00 | 0.00 | 508173.65 | 0.00 | 0.204432E+09 | 0.439899E+09 | 0.00 | 0.66 |
May | 0.182170E+10 | 0.00 | 0.00 | 2249901.79 | 1470432.06 | 1651292.17 | 0.127762E+10 | 0.00 | 1.05 |
June | 0.568510E+09 | 0.279746E+09 | 0.00 | 4133941.60 | 43649588.88 | 0.00 | 0.162955E+10 | 0.00 | 1.42 |
July | 0.189751E+09 | 0.967375E+09 | 0.00 | 3346375.57 | 0.142642E+09 | 0.00 | 0.718073E+09 | 0.00 | 1.29 |
August | 0.434969E+09 | 0.508436E+09 | 0.00 | 4708353.38 | 66447400.46 | 0.00 | 0.107297E+10 | 0.00 | 1.41 |
September | 0.112752E+10 | 0.169183E+09 | 0.00 | 3481829.95 | 13719329.70 | 294884.08 | 0.147607E+10 | 0.00 | 1.36 |
October | 0.236367E+10 | 0.00 | 0.00 | 625917.64 | 33650.21 | 36737716.83 | 0.542827E+09 | 0.00 | 0.75 |
November | 0.231824E+10 | 0.00 | 1574.70 | 490.20 | 717141.58 | 0.499192E+09 | 3688793.51 | 3278.60 | 0.55 |
December | 0.574684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304452E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.147828E+11 | 0.192496E+10 | 1574.70 | 19081300.42 | 0.269688E+09 | 0.114717E+11 | 0.716747E+10 | 3278.60 | 0.87 |
Minimum of Months | 0.189751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.236367E+10 | 0.967375E+09 | 1574.70 | 4708353.38 | 0.142642E+09 | 0.352316E+10 | 0.162955E+10 | 3278.60 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563939E+10 | 0.00 | 0.00 | 0.44 |
February | 0.249923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513084E+10 | 0.00 | 0.00 | 0.44 |
March | 0.130287E+10 | 2185330.47 | 0.00 | 216840.65 | 102371.38 | 0.341656E+10 | 12360910.61 | 0.00 | 0.50 |
April | 0.198844E+10 | 0.00 | 0.00 | 265866.85 | 0.00 | 0.167836E+10 | 0.224703E+09 | 0.00 | 0.55 |
May | 0.259075E+10 | 70856.79 | 0.00 | 970560.38 | 1733673.51 | 0.650798E+09 | 0.450376E+09 | 0.00 | 0.79 |
June | 0.136125E+10 | 0.339499E+09 | 0.00 | 2231140.89 | 79447056.75 | 0.179062E+09 | 0.645807E+09 | 0.00 | 0.97 |
July | 0.361479E+09 | 0.132752E+10 | 0.00 | 2307523.73 | 0.189493E+09 | 56053734.37 | 0.377182E+09 | 0.00 | 0.89 |
August | 0.723446E+09 | 0.821421E+09 | 0.00 | 4979357.98 | 78158970.38 | 0.116127E+09 | 0.822301E+09 | 0.00 | 1.12 |
September | 0.136619E+10 | 0.265738E+09 | 0.00 | 5066082.52 | 16371664.79 | 0.255187E+09 | 0.172553E+10 | 0.00 | 1.22 |
October | 0.235444E+10 | 32636.54 | 0.00 | 1517162.63 | 16220.80 | 0.925557E+09 | 0.821842E+09 | 0.00 | 0.69 |
November | 0.140042E+10 | 0.00 | 8143.87 | 83484.40 | 875393.25 | 0.233437E+10 | 0.113134E+09 | 2502.90 | 0.47 |
December | 0.282852E+09 | 0.00 | 0.00 | 4247.91 | 0.00 | 0.504358E+10 | 10911602.21 | 0.00 | 0.43 |
Annual Sum or Average | 0.141820E+11 | 0.275647E+10 | 8143.87 | 17642267.94 | 0.366199E+09 | 0.254259E+11 | 0.520415E+10 | 2502.90 | 0.71 |
Minimum of Months | 0.199948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56053734.37 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.259075E+10 | 0.132752E+10 | 8143.87 | 5066082.52 | 0.189493E+09 | 0.563939E+10 | 0.172553E+10 | 2502.90 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365989E+10 | 0.00 | 0.00 | 0.48 |
February | 0.543281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319913E+10 | 0.00 | 0.00 | 0.50 |
March | 0.209241E+10 | 0.00 | 0.00 | 18244.26 | 1295221.30 | 0.148727E+10 | 6403258.38 | 0.00 | 0.60 |
April | 0.245939E+10 | 0.00 | 0.00 | 478579.29 | 0.00 | 0.303496E+09 | 0.336674E+09 | 0.00 | 0.70 |
May | 0.231948E+10 | 76149.71 | 0.00 | 1745964.31 | 1486872.13 | 6621208.61 | 0.888688E+09 | 0.00 | 1.10 |
June | 0.749276E+09 | 0.288812E+09 | 0.00 | 3709286.52 | 54973976.92 | 0.00 | 0.134395E+10 | 0.00 | 1.45 |
July | 0.290411E+09 | 0.983781E+09 | 0.00 | 2407269.41 | 0.140760E+09 | 0.00 | 0.388285E+09 | 0.00 | 1.16 |
August | 0.585955E+09 | 0.563643E+09 | 0.00 | 3611725.43 | 62015943.61 | 0.00 | 0.737231E+09 | 0.00 | 1.33 |
September | 0.132091E+10 | 0.137462E+09 | 0.00 | 2776209.85 | 35698732.61 | 0.00 | 0.116034E+10 | 0.00 | 1.32 |
October | 0.270137E+10 | 0.00 | 0.00 | 543500.03 | 35417.12 | 48586658.50 | 0.355555E+09 | 0.00 | 0.79 |
November | 0.237737E+10 | 0.00 | 1552.52 | 2867.52 | 754797.46 | 0.575191E+09 | 16567913.13 | 3555.62 | 0.58 |
December | 0.608791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319853E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.163880E+11 | 0.197377E+10 | 1552.52 | 15293646.63 | 0.297021E+09 | 0.124787E+11 | 0.523370E+10 | 3555.62 | 0.88 |
Minimum of Months | 0.290411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.270137E+10 | 0.983781E+09 | 1552.52 | 3709286.52 | 0.140760E+09 | 0.365989E+10 | 0.134395E+10 | 3555.62 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.276968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360390E+10 | 0.00 | 0.00 | 0.30 |
February | 0.576399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305260E+10 | 0.00 | 0.00 | 0.31 |
March | 0.175105E+10 | 747037.59 | 0.00 | 277282.29 | 802251.26 | 0.145129E+10 | 0.120890E+09 | 0.00 | 0.36 |
April | 0.233345E+10 | 0.00 | 0.00 | 263356.93 | 0.00 | 0.218223E+09 | 0.244359E+09 | 0.00 | 0.40 |
May | 0.140781E+10 | 0.00 | 0.00 | 3183263.94 | 3579999.37 | 193403.38 | 0.166669E+10 | 0.00 | 0.69 |
June | 0.388697E+09 | 0.422534E+09 | 0.00 | 5222068.76 | 32626214.99 | 0.00 | 0.171916E+10 | 0.00 | 1.00 |
July | 0.161881E+09 | 0.140477E+10 | 0.00 | 3096629.67 | 98841263.76 | 0.00 | 0.582258E+09 | 0.00 | 0.88 |
August | 0.349540E+09 | 0.732106E+09 | 0.00 | 4872981.32 | 30454768.75 | 0.00 | 0.102209E+10 | 0.00 | 0.94 |
September | 0.999105E+09 | 0.214894E+09 | 0.00 | 3022599.37 | 9882508.67 | 250465.42 | 0.117214E+10 | 0.00 | 0.81 |
October | 0.222602E+10 | 0.00 | 0.00 | 485111.22 | 445863.44 | 0.118266E+09 | 0.331196E+09 | 0.00 | 0.44 |
November | 0.185546E+10 | 0.00 | 28807.46 | 0.00 | 1291904.11 | 0.780069E+09 | 0.00 | 5139.02 | 0.34 |
December | 0.465871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316082E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.127923E+11 | 0.277505E+10 | 28807.46 | 20423293.50 | 0.177925E+09 | 0.123856E+11 | 0.685878E+10 | 5139.02 | 0.57 |
Minimum of Months | 0.161881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.233345E+10 | 0.140477E+10 | 28807.46 | 5222068.76 | 98841263.76 | 0.360390E+10 | 0.171916E+10 | 5139.02 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419981E+10 | 0.00 | 0.00 | 0.59 |
February | 0.114657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327157E+10 | 0.00 | 0.00 | 0.60 |
March | 0.282927E+10 | 2019375.04 | 0.00 | 186458.10 | 0.00 | 0.122959E+10 | 0.102978E+09 | 0.00 | 0.71 |
April | 0.256728E+10 | 0.00 | 0.00 | 1317770.04 | 0.00 | 0.162367E+09 | 0.960093E+09 | 0.00 | 0.84 |
May | 0.188215E+10 | 0.00 | 0.00 | 3885958.31 | 4532865.14 | 641829.18 | 0.219023E+10 | 0.00 | 1.38 |
June | 0.650776E+09 | 0.366299E+09 | 0.00 | 5026152.23 | 45409820.19 | 0.00 | 0.205396E+10 | 0.00 | 1.72 |
July | 0.206850E+09 | 0.116517E+10 | 0.00 | 4009955.45 | 0.170755E+09 | 0.00 | 0.839556E+09 | 0.00 | 1.54 |
August | 0.509203E+09 | 0.550664E+09 | 0.00 | 4880146.19 | 84515483.12 | 0.00 | 0.114895E+10 | 0.00 | 1.58 |
September | 0.137450E+10 | 0.157845E+09 | 0.00 | 3332103.41 | 55324133.20 | 975879.14 | 0.144166E+10 | 0.00 | 1.50 |
October | 0.282696E+10 | 0.00 | 0.00 | 486425.49 | 564536.09 | 0.123598E+09 | 0.424439E+09 | 0.00 | 0.88 |
November | 0.241067E+10 | 0.00 | 83653.30 | 1643.06 | 1583484.76 | 0.911328E+09 | 11045787.16 | 5775.53 | 0.67 |
December | 0.567132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390992E+10 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.175488E+11 | 0.224200E+10 | 83653.30 | 23126612.28 | 0.362686E+09 | 0.138098E+11 | 0.917291E+10 | 5775.53 | 1.05 |
Minimum of Months | 0.206850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.282927E+10 | 0.116517E+10 | 83653.30 | 5026152.23 | 0.170755E+09 | 0.419981E+10 | 0.219023E+10 | 5775.53 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177883E+10 | 0.00 | 0.00 | 288452.03 | 0.00 | 0.364270E+10 | 0.222960E+09 | 0.00 | 0.44 |
February | 0.196835E+10 | 0.00 | 0.00 | 548640.94 | 0.00 | 0.297175E+10 | 0.329345E+09 | 0.00 | 0.45 |
March | 0.296628E+10 | 5757334.14 | 0.00 | 2399181.51 | 0.00 | 0.949990E+09 | 0.124843E+10 | 0.00 | 0.57 |
April | 0.275294E+10 | 0.00 | 0.00 | 3105024.90 | 0.00 | 0.235790E+09 | 0.175648E+10 | 0.00 | 0.71 |
May | 0.215835E+10 | 861120.52 | 0.00 | 5735005.48 | 4642992.50 | 3389252.42 | 0.272931E+10 | 0.00 | 1.10 |
June | 0.873322E+09 | 0.471276E+09 | 0.00 | 6030797.84 | 56755748.13 | 0.00 | 0.202971E+10 | 0.00 | 1.31 |
July | 0.357255E+09 | 0.164252E+10 | 0.00 | 3353259.84 | 0.163933E+09 | 0.00 | 0.612135E+09 | 0.00 | 1.10 |
August | 0.648977E+09 | 0.896445E+09 | 0.00 | 6644993.59 | 58519622.52 | 0.00 | 0.130190E+10 | 0.00 | 1.31 |
September | 0.131907E+10 | 0.314512E+09 | 0.00 | 7607556.18 | 23535154.80 | 371527.24 | 0.266930E+10 | 0.00 | 1.48 |
October | 0.254483E+10 | 186592.81 | 0.00 | 4514857.09 | 525301.15 | 0.107480E+09 | 0.215262E+10 | 0.00 | 0.87 |
November | 0.261777E+10 | 0.00 | 38446.46 | 1380686.82 | 1916342.68 | 0.795924E+09 | 0.713850E+09 | 5077.66 | 0.53 |
December | 0.175044E+10 | 0.00 | 0.00 | 169712.35 | 0.00 | 0.340208E+10 | 0.118060E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.217364E+11 | 0.333155E+10 | 38446.46 | 41778168.58 | 0.309828E+09 | 0.121095E+11 | 0.158841E+11 | 5077.66 | 0.86 |
Minimum of Months | 0.357255E+09 | 0.00 | 0.00 | 169712.35 | 0.00 | 0.00 | 0.118060E+09 | 0.00 | 0.44 |
Maximum of Months | 0.296628E+10 | 0.164252E+10 | 38446.46 | 7607556.18 | 0.163933E+09 | 0.364270E+10 | 0.272931E+10 | 5077.66 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.674847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429504E+10 | 0.00 | 0.00 | 0.61 |
February | 0.105778E+10 | 0.00 | 0.00 | 3422.30 | 0.00 | 0.352585E+10 | 12682585.91 | 0.00 | 0.62 |
March | 0.274252E+10 | 253396.08 | 0.00 | 302538.48 | 1787708.62 | 0.139489E+10 | 0.195735E+09 | 0.00 | 0.74 |
April | 0.281838E+10 | 0.00 | 0.00 | 1253887.95 | 0.00 | 0.260821E+09 | 0.780766E+09 | 0.00 | 0.89 |
May | 0.232603E+10 | 74759.62 | 0.00 | 3349548.08 | 4641696.93 | 3685102.08 | 0.183976E+10 | 0.00 | 1.45 |
June | 0.875930E+09 | 0.369757E+09 | 0.00 | 4707040.40 | 61517028.67 | 0.00 | 0.164163E+10 | 0.00 | 1.75 |
July | 0.336479E+09 | 0.119915E+10 | 0.00 | 2767704.32 | 0.173196E+09 | 0.00 | 0.420114E+09 | 0.00 | 1.38 |
August | 0.703846E+09 | 0.589821E+09 | 0.00 | 3835780.68 | 81580984.07 | 0.00 | 0.748155E+09 | 0.00 | 1.49 |
September | 0.166613E+10 | 0.145982E+09 | 0.00 | 2664771.17 | 66188957.43 | 1015404.48 | 0.106654E+10 | 0.00 | 1.50 |
October | 0.303908E+10 | 0.00 | 0.00 | 659153.24 | 587401.09 | 0.150557E+09 | 0.346756E+09 | 0.00 | 0.93 |
November | 0.246233E+10 | 0.00 | 87335.07 | 16267.78 | 1647619.52 | 0.968474E+09 | 37043656.11 | 5715.83 | 0.70 |
December | 0.819486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383770E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.195228E+11 | 0.230504E+10 | 87335.07 | 19560114.40 | 0.391147E+09 | 0.144380E+11 | 0.708919E+10 | 5715.83 | 1.06 |
Minimum of Months | 0.336479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.303908E+10 | 0.119915E+10 | 87335.07 | 4707040.40 | 0.173196E+09 | 0.429504E+10 | 0.183976E+10 | 5715.83 | 1.75 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:04
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.144198E+12 | 0.337137E+11 | 0.00 | 0.147058E+12 | 0.124970E+11 |
February | 0.218368E+12 | 0.341511E+11 | 0.00 | 0.136734E+12 | 0.115586E+11 |
March | 0.318785E+12 | 0.237811E+11 | 0.00 | 0.174756E+12 | 0.138842E+11 |
April | 0.374371E+12 | 0.183801E+11 | 0.00 | 0.209108E+12 | 0.401802E+10 |
May | 0.453776E+12 | 0.109052E+11 | 0.00 | 0.234623E+12 | 0.308742E+11 |
June | 0.486837E+12 | 0.415689E+10 | 0.00 | 0.133157E+12 | 0.144198E+12 |
July | 0.452103E+12 | -0.128229E+10 | 0.00 | 0.155683E+11 | 0.250491E+12 |
August | 0.388156E+12 | 0.146755E+10 | 0.00 | 0.915592E+11 | 0.207107E+12 |
September | 0.300187E+12 | 0.621405E+10 | 0.00 | 0.185912E+12 | 0.893934E+11 |
October | 0.207898E+12 | 0.150811E+11 | 0.00 | 0.216581E+12 | 0.104102E+11 |
November | 0.112568E+12 | 0.201088E+11 | 0.00 | 0.171561E+12 | 0.428274E+10 |
December | 0.129472E+12 | 0.343960E+11 | 0.00 | 0.150942E+12 | 0.106396E+11 |
Annual Sum or Average | 0.358672E+13 | 0.201073E+12 | 0.00 | 0.186756E+13 | 0.789353E+12 |
Minimum of Months | 0.112568E+12 | -0.128229E+10 | 0.00 | 0.155683E+11 | 0.401802E+10 |