Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:35:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2454.47 | 492.65 | 492.65 |
Net Site Energy | 2454.47 | 492.65 | 492.65 |
Total Source Energy | 6788.59 | 1362.57 | 1362.57 |
Net Source Energy | 6788.59 | 1362.57 | 1362.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 453.69 | 356.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 162.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 361.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 110.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1981.73 | 472.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 453.69 | 356.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 162.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 361.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 110.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 453.69 | 356.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 162.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 361.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 110.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 762.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 112.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 116.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.18 | 94.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.76 | 94.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 94.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 146.18 | 94.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 156.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 397.76 | 94.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1981.734 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1981.734 | 100.00 |
Total On-Site and Utility Electric Sources | 1981.734 | 100.00 |
Total Electricity End Uses | 1981.734 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 761.17 |
Time Setpoint Not Met During Occupied Cooling | 72.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3234.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 9.0546 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 9.0546 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 9.0546 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 9.0546 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 9.0546 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 9.0546 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 9.0546 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 9.0546 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 9.0546 | 18.58 | 8.0700 | |
Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 9.0546 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 9.0546 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 02-FEB-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 222033.68 | 185122.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21853.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7754.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8259.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 272527.51 | 193381.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 222033.68 | 185122.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 12045.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 16082.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 371.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7754.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8259.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1436.85 | 386.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 513.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1145.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2413.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 59.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 355.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6276.15 | 512.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 288.40 | 77.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 103.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1259.72 | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 288.40 | 77.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 103.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 229.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 70.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 484.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 12.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1259.72 | 102.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.07 | 0.244230 | 0.300000 | 0.920594 | 0.651279 | 0.500000 | 0.001560 |
CORE_MID VAV BOX COMPONENT | 2.28 | 0.328653 | 0.338000 | 0.770769 | 0.876408 | 0.500000 | 0.001159 |
CORE_TOP VAV BOX COMPONENT | 2.40 | 0.311708 | 0.333000 | 0.800649 | 0.831221 | 0.500000 | 0.001222 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.817423 | 0.193280 | 0.300000 | 0.245227 | 0.515414 | 0.500000 | 0.001971 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.864392 | 0.115713 | 0.300000 | 0.259318 | 0.308569 | 0.500000 | 0.003293 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.08 | 0.146590 | 0.300000 | 0.323333 | 0.390907 | 0.500000 | 0.002599 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.957102 | 0.104498 | 0.300000 | 0.287131 | 0.300000 | 0.500000 | 0.003646 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.599795 | 0.263409 | 0.300000 | 0.179939 | 0.702425 | 0.500000 | 0.001446 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.701572 | 0.142568 | 0.300000 | 0.210472 | 0.380182 | 0.500000 | 0.002672 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.852260 | 0.185380 | 0.300000 | 0.255678 | 0.494346 | 0.500000 | 0.002055 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.754736 | 0.132517 | 0.300000 | 0.226421 | 0.353378 | 0.500000 | 0.002875 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.650123 | 0.243018 | 0.300000 | 0.195037 | 0.648048 | 0.500000 | 0.001568 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.843833 | 0.118533 | 0.300000 | 0.253150 | 0.316087 | 0.500000 | 0.003214 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.976389 | 0.161812 | 0.300000 | 0.292917 | 0.431499 | 0.500000 | 0.002355 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.881113 | 0.113510 | 0.300000 | 0.264334 | 0.302694 | 0.500000 | 0.003357 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 29326.93 |
CORE_MID VAV BOX REHEAT COIL | 30086.82 |
CORE_TOP VAV BOX REHEAT COIL | 50916.31 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26040.25 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16891.98 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25774.30 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17057.30 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19107.39 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12478.91 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18900.42 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 12616.15 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 20339.34 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 13250.40 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 20107.76 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 13391.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.99 | 1.79 | 5.98 | 2.50 | 5.29 | 5.29 | 0.300000 | 0.472010 | 5.29 |
PACU_VAV_MID | 2.82 | 1.78 | 5.63 | 3.05 | 4.77 | 4.77 | 0.300000 | 0.640019 | 4.77 |
PACU_VAV_TOP | 3.06 | 1.92 | 6.12 | 4.29 | 5.48 | 5.48 | 0.300000 | 0.782889 | 5.48 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.29 |
PACU_VAV_MID_OA_CONTROLLER | 4.77 |
PACU_VAV_TOP_OA_CONTROLLER | 5.48 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.29 | 112826.66 | 0.751333 | 1.76 | 37605.12 | 0.751333 |
PACU_VAV_MID COOLING COIL | 4.77 | 106569.49 | 0.735185 | 1.59 | 35519.61 | 0.735185 |
PACU_VAV_TOP COOLING COIL | 5.48 | 118386.16 | 0.746733 | 1.83 | 39458.11 | 0.746733 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 47733.39 |
PACU_VAV_MID HEATING COIL | 52543.64 |
PACU_VAV_TOP HEATING COIL | 51362.26 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.29 |
PACU_VAV_MID FAN | 4.77 |
PACU_VAV_TOP FAN | 5.48 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 33.889 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 17.124 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 9.055 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 8905.551 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 8905.551 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1188.529 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.529 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1877.368 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1877.368 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1188.451 | 9.055 | 168.224 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1188.451 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2460 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.212 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.988 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18042418E-08 | -0.42925973E-15 | 0.63337540E-14 | -0.83764910E-16 |
66 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
67 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
68 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
69 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
70 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
71 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
72 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
73 | 7 | -0.17078159E-08 | -0.36552483E-15 | 0.71259391E-14 | -0.98899249E-16 |
74 | 6 | 0.68798867E-05 | 0.47165251E-08 | 0.31862110E-02 | -0.26728608E-04 |
75 | 5 | -0.49558197E-03 | 0.27953368E-05 | -0.22351660 | 0.19543146E-02 |
76 | 4 | 0.11404824E-01 | 0.12725100E-03 | 4.8260817 | -0.45231683E-01 |
77 | 3 | -0.10016651 | 0.10121065E-02 | -38.001848 | 0.39843745 |
78 | 2 | 0.35569192 | 0.16837830E-02 | 116.44586 | -1.4174299 |
79 | 1 | -0.51340120 | 0.51323984E-03 | -143.88489 | 2.0486714 |
80 | 0 | 0.25031121 | 0.12359947E-04 | 60.838472 | |
81 | 7 | -0.18042418E-08 | -0.42925997E-15 | 0.63337541E-14 | -0.83764912E-16 |
82 | 6 | 0.65275556E-05 | 0.44683346E-08 | 0.31872225E-02 | -0.26737093E-04 |
83 | 5 | -0.46956700E-03 | 0.26475551E-05 | -0.22357410 | 0.19548221E-02 |
84 | 4 | 0.10802233E-01 | 0.12051741E-03 | 4.8270395 | -0.45240890E-01 |
85 | 3 | -0.94862618E-01 | 0.95846847E-03 | -38.007259 | 0.39849726 |
86 | 2 | 0.33684277 | 0.15944941E-02 | 116.45640 | -1.4175707 |
87 | 1 | -0.48618543 | 0.48593727E-03 | -143.89109 | 2.0487733 |
88 | 0 | 0.23703987 | 0.11722998E-04 | 60.838472 | |
89 | 7 | -0.17076967E-08 | -0.36446083E-15 | 0.71390403E-14 | -0.94439575E-16 |
90 | 6 | 0.68803475E-05 | 0.47168467E-08 | 0.31862096E-02 | -0.26728597E-04 |
91 | 5 | -0.49561596E-03 | 0.27955299E-05 | -0.22351653 | 0.19543140E-02 |
92 | 4 | 0.11405612E-01 | 0.12725979E-03 | 4.8260805 | -0.45231671E-01 |
93 | 3 | -0.10017344 | 0.10121766E-02 | -38.001841 | 0.39843738 |
94 | 2 | 0.35571654 | 0.16838995E-02 | 116.44585 | -1.4174297 |
95 | 1 | -0.51343675 | 0.51327568E-03 | -143.88488 | 2.0486713 |
96 | 0 | 0.25032854 | 0.12360692E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.538E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.577E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 7.798E-002 | 3.761E-004 | 5.696E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 5.199E-002 | 3.961E-004 | 5.696E-004 | 0.520 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 5.696E-004 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.116 | 6.957E-005 | 6.199E-005 | 0.205 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0881E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0943E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2086E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2139E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2351E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2780E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8297E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8525E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1522 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4286E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1739 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6227E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1070 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6235E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4494E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6685E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0883E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0953E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2087E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2150E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2365E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2853E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8295E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8523E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8778E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0429E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5716E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7831E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7406E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3985E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1768E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4209E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0827E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1076E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8122E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8301E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4562E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4624E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4698E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4776E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1172E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1713E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4393E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4830E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9846E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0171E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8295E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8523E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9359E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3191E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0435E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7699E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9146E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2332E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4494E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6685E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1169E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1718E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4387E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4819E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9833E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0119E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8297E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9302E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5769E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3802E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1946E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9839E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0398E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1769E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4210E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5022E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5745E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0783E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1583E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0133E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0419E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4700E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4778E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1498 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.9954E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1682 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1135 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1131 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.7556E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0018E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3204E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6100E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8931E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3266E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6466E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5405E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2902E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0531E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3544E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4483E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9818E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5022E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3411E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3717E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7595E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0018E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3204E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6990E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4503E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1814E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0877E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8111E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9482E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0532E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3545E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1498 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.9945E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1682 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1134 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1131 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.7549E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0015E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3201E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6101E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8929E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3266E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6463E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5402E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2899E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0527E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3542E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4486E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9817E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5023E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3410E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3716E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7593E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0015E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3201E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6991E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4502E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1815E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0875E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9479E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0528E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3542E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 40614.66865 | 40614.66865 | 3.06865 | 3.06865 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 11655.87776 | 11655.87776 | 0.51595 | 0.51595 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 30214.02945 | 30214.02945 | 2.28038 | 2.28038 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 21213.65982 | 21213.65982 | 0.94445 | 0.94445 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 31563.94251 | 31563.94251 | 2.40435 | 2.40435 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.98800 | 1.53647E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35806.03040 | 35806.03040 | 1.59830 | 1.59830 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9778.29476 | 9778.29476 | 0.74495 | 0.74495 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 18271.88131 | 18271.88131 | 0.81742 | 0.81742 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11346.10886 | 11346.10886 | 0.86439 | 0.86439 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 11852.36611 | 11852.36611 | 0.53025 | 0.53025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14147.04973 | 14147.04973 | 1.07778 | 1.07778 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 18085.57266 | 18085.57266 | 0.80907 | 0.80907 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12563.06499 | 12563.06499 | 0.95710 | 0.95710 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 11968.18000 | 11968.18000 | 0.53544 | 0.53544 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7614.14629 | 7614.14629 | 0.58004 | 0.58004 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 13413.31552 | 13413.31552 | 0.59980 | 0.59980 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9209.52045 | 9209.52045 | 0.70157 | 0.70157 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.57133 | 1.53565E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8759.60707 | 8759.60707 | 0.39172 | 0.39172 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11187.57226 | 11187.57226 | 0.85226 | 0.85226 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53649E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 13268.34574 | 13268.34574 | 0.59330 | 0.59330 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9907.42529 | 9907.42529 | 0.75474 | 0.75474 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8855.73122 | 8855.73122 | 0.39603 | 0.39603 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8533.71353 | 8533.71353 | 0.65012 | 0.65012 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 14277.49428 | 14277.49428 | 0.63847 | 0.63847 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11076.51554 | 11076.51554 | 0.84383 | 0.84383 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 9300.83003 | 9300.83003 | 0.41594 | 0.41594 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12816.47381 | 12816.47381 | 0.97639 | 0.97639 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 14115.28038 | 14115.28038 | 0.63120 | 0.63120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11565.88868 | 11565.88868 | 0.88111 | 0.88111 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 9399.38095 | 9399.38095 | 0.42036 | 0.42036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 77683.35 | 5.28971 | 5.28971 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 50429.32 | 2.49680 | 2.49680 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71417.14 | 4.76612 | 4.76612 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 53618.54 | 3.05041 | 3.05041 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80534.00 | 5.48033 | 5.48033 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 53732.34 | 4.29049 | 4.29049 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.06865 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24423 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.92059 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65128 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56001E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 29326.92913 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.28038 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32865 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77077 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87641 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15928E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30086.81979 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.40435 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31171 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80065 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83122 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22230E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50916.30806 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81742 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19328 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24523 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51541 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97123E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26040.25060 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86439 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11571 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25932 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30857 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29262E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16891.97718 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07778 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14659 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32333 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39091 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59908E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25774.30241 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95710 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10450 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28713 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64600E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17057.29714 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59980 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26341 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17994 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70242 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44642E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 19107.39089 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70157 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14257 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21047 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38018 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67241E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12478.91252 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85226 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18538 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25568 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49435 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05524E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18900.42081 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75474 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13252 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22642 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35338 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87511E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12616.14666 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65012 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24302 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19504 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64805 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56778E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20339.33558 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84383 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11853 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25315 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31609 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21430E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13250.40155 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97639 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16181 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29292 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43150 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35458E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20107.76386 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88111 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11351 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26433 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30269 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35653E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13391.09052 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.98851 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79310 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.97701 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.49680 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28971 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.28971 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.47201 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81592 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.77621 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.63184 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05041 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.76612 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.76612 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.64002 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.06052 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.91566 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.12105 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 4.29049 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.48033 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.48033 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.78289 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.28971 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.76612 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.48033 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28971 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.28971 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112826.65660 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75133 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76306 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37605.12465 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75133 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 47733.38716 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.28971 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.76612 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.76612 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106569.48899 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73519 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58855 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35519.61068 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73519 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 52543.64269 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.76612 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.48033 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.48033 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 118386.15817 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74673 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.82659 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39458.10652 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74673 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 51362.25642 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.48033 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 112065.36 | 382382.90 | 11.44 | 2.91 | 3.28 | 3.45 | 3.60 | 9.94 | 11.18 | 11.78 | 12.30 | 5.8356 | 4.6502 | 3.1301 | 1.2896 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 106028.45 | 361784.09 | 11.53 | 2.93 | 3.30 | 3.48 | 3.62 | 10.00 | 11.27 | 11.89 | 12.36 | 5.2580 | 4.1864 | 2.8185 | 1.1769 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 117641.50 | 401409.47 | 11.46 | 2.92 | 3.28 | 3.46 | 3.61 | 9.96 | 11.20 | 11.81 | 12.31 | 6.0459 | 4.8158 | 3.2410 | 1.3410 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.246 | 0.232 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.233 | 0.221 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.246 | 0.232 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.3413553408E-002 | 3.2425750697E-002 | Pass | Pass | 0.4853234727 | 0.4889737907 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1929705986 | 0.1271114671 | Pass | Pass | 0.4900889651 | 0.4766867489 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4945326094E-002 | 5.3965748260E-002 | Pass | Pass | 0.4931075662 | 0.4694342913 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.5881279875E-002 | 5.3769659033E-002 | Pass | Pass | 0.4982470866 | 0.4675882787 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9909010485E-003 | 4.5553279346E-003 | Pass | Pass | 0.4974666296 | 0.4913060350 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 9.0663932140E-002 | 9.0444512944E-002 | Pass | Pass | 8.7887549387 | 32.2843466425 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4727842895 | 0.4497226436 | Pass | Pass | 10.1834363018 | 47.6006774848 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4985188238 | 0.4926672557 | Pass | Pass | 5.7006296986 | 26.8178305392 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4377112110 | 0.4548097418 | Pass | Pass | 5.9157447935 | 27.3563985126 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5028190603 | 0.4914882749 | Pass | Pass | 4.8963853395 | 22.3211979774 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3250090411 | 0.3101115476 | Pass | Pass | 9.5002181557 | 34.3057250425 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3544284363 | 0.3432348606 | Pass | Pass | 5.9305381513 | 19.7323722627 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3056114166 | 0.3095034241 | Pass | Pass | 5.1342002259 | 16.0273330318 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3610342706 | 0.3453238650 | Pass | Pass | 6.4016514883 | 21.6052898084 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3345287460 | 0.3220916663 | Pass | Pass | 13.5448235917 | 64.8516424526 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3556363553 | 0.3548153050 | Pass | Pass | 2.6074921104 | 8.3482260305 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3147606037 | 0.3304123419 | Pass | Pass | 6.2753997066 | 30.1705508851 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3608059304 | 0.3537172492 | Pass | Pass | 5.1139979283 | 23.2743795761 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3693.16 | 249.29 | 0.00 | 1829.46 | 893.93 | 6665.84 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.225 | 0.233 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.237 | 0.246 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 177.99 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 9.0546 | 983.54 | 8905.55 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 48.87 | 0.0000 | Y | 81.70 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.86 | 0.0000 | Y | 11.93 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.79 | 0.0000 | Y | 7.54 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.62 | 0.0000 | Y | 11.85 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.70 | 0.0000 | Y | 7.52 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.81 | 0.0000 | Y | 11.92 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.75 | 0.0000 | Y | 7.53 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.59 | 0.0000 | Y | 11.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.67 | 0.0000 | Y | 7.51 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.86 | 0.0000 | Y | 11.93 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 9.0546 | 131.26 | 1188.53 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.79 | 0.0000 | Y | 7.54 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 9.0546 | 207.34 | 1877.37 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.62 | 0.0000 | Y | 11.85 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 9.0546 | 131.25 | 1188.45 | LightsWired | LTG_SCH_OFFICE | 50.17 | 168.00 | 33.70 | 0.0000 | Y | 7.52 |
Interior Lighting Total | 9.0546 | 4982.19 | 45111.81 | 361.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.53 | 455.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.53 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1877.37 | 719.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1877.37 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1188.45 | 455.77 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1188.45 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.25 | AstronomicalClock | - | 42.24 | 42.24 | 3.36 | |
EXTERIOR_LIGHTS_B | 8043.62 | AstronomicalClock | - | 83.63 | 71.21 | 107.52 | |
Exterior Lighting Total | 8467.87 | 110.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112826.66 | 84770.37 | 28056.28 | 0.75 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106569.49 | 78348.29 | 28221.20 | 0.74 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 118386.16 | 88402.85 | 29983.31 | 0.75 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 112065.4 | 2.91 | 9.94 | N/A | N/A | 11.44 | |
PACU_VAV_MID COOLING COIL | 106028.5 | 2.93 | 10.00 | N/A | N/A | 11.53 | |
PACU_VAV_TOP COOLING COIL | 117641.5 | 2.92 | 9.96 | N/A | N/A | 11.46 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 29326.93 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 30086.82 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 50916.31 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 26040.25 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16891.98 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 25774.30 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17057.30 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 19107.39 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12478.91 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18900.42 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12616.15 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20339.34 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13250.40 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 20107.76 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13391.09 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 47733.39 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 52543.64 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 51362.26 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.29 | 12158.19 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.77 | 10954.75 | 2298.46 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.48 | 12596.33 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112065.36 | 2.91 | 9.94 | 11.44 | 5.8356 | 3.28 | 11.18 | 4.6502 | 3.45 | 11.78 | 3.1301 | 3.60 | 12.30 | 1.2896 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106028.45 | 2.93 | 10.00 | 11.53 | 5.2580 | 3.30 | 11.27 | 4.1864 | 3.48 | 11.89 | 2.8185 | 3.62 | 12.36 | 1.1769 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 117641.50 | 2.92 | 9.96 | 11.46 | 6.0459 | 3.28 | 11.20 | 4.8158 | 3.46 | 11.81 | 3.2410 | 3.61 | 12.31 | 1.3410 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 40614.67 | 40614.67 | 41.29 | 3.069 | 3.069 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00880 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 30214.03 | 30214.03 | 30.72 | 2.280 | 2.280 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 31563.94 | 31563.94 | 32.09 | 2.404 | 2.404 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00888 | 30.99 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9778.29 | 9778.29 | 47.16 | 0.745 | 0.745 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00916 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11346.11 | 11346.11 | 86.44 | 0.864 | 0.864 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00889 | 25.97 | 0.01536 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14147.05 | 14147.05 | 68.23 | 1.078 | 1.078 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00896 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12563.06 | 12563.06 | 95.72 | 0.957 | 0.957 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00885 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7614.15 | 7614.15 | 36.72 | 0.580 | 0.580 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00911 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9209.52 | 9209.52 | 70.16 | 0.702 | 0.702 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00883 | 26.57 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11187.57 | 11187.57 | 53.96 | 0.852 | 0.852 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00892 | 31.11 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9907.43 | 9907.43 | 75.48 | 0.755 | 0.755 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00881 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8533.71 | 8533.71 | 41.16 | 0.650 | 0.650 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00918 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11076.52 | 11076.52 | 84.38 | 0.844 | 0.844 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00885 | 25.37 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12816.47 | 12816.47 | 61.81 | 0.976 | 0.976 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00896 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11565.89 | 11565.89 | 88.12 | 0.881 | 0.881 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00884 | 29.36 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 11655.88 | 11655.88 | 11.85 | 0.516 | 0.516 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 21213.66 | 21213.66 | 21.57 | 0.944 | 0.944 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 35806.03 | 35806.03 | 36.41 | 1.598 | 1.598 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 18271.88 | 18271.88 | 88.13 | 0.817 | 0.817 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11852.37 | 11852.37 | 90.30 | 0.530 | 0.530 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 18085.57 | 18085.57 | 87.23 | 0.809 | 0.809 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11968.18 | 11968.18 | 91.18 | 0.535 | 0.535 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 13413.32 | 13413.32 | 64.69 | 0.600 | 0.600 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8759.61 | 8759.61 | 66.73 | 0.392 | 0.392 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13268.35 | 13268.35 | 63.99 | 0.593 | 0.593 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8855.73 | 8855.73 | 67.47 | 0.396 | 0.396 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 14277.49 | 14277.49 | 68.86 | 0.638 | 0.638 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9300.83 | 9300.83 | 70.86 | 0.416 | 0.416 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14115.28 | 14115.28 | 68.08 | 0.631 | 0.631 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9399.38 | 9399.38 | 71.61 | 0.420 | 0.420 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.29 | 5.29 | 2.50 | 2.50 | 5.2897 | 2.4968 | 5.2897 | 0.4720 | 0.3000 |
PACU_VAV_MID | 4.77 | 4.77 | 3.05 | 3.05 | 4.7661 | 3.0504 | 4.7661 | 0.6400 | 0.3000 |
PACU_VAV_TOP | 5.48 | 5.48 | 4.29 | 4.29 | 5.4803 | 4.2905 | 5.4803 | 0.7829 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 29326.929 | 29326.929 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29326.93 | 16436.34 | 0.515949 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 11655.88 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 30086.820 | 30086.820 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30086.82 | 30086.82 | 0.944448 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 21213.66 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50916.308 | 50916.308 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50916.31 | 50916.31 | 1.598301 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 35806.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26040.251 | 26040.251 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26040.25 | 26040.25 | 0.817423 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753990 | 46.5351 | 18271.88 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16891.977 | 16891.977 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16891.98 | 16891.98 | 0.530252 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00752778 | 46.4615 | 11852.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 25774.302 | 25774.302 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25774.30 | 25774.30 | 0.809075 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753547 | 46.5081 | 18085.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 17057.297 | 17057.297 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17057.30 | 17057.30 | 0.535441 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00753205 | 46.4875 | 11968.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19107.391 | 19107.391 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19107.39 | 19107.39 | 0.599795 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766078 | 47.2681 | 13413.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12478.913 | 12478.913 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12478.91 | 12478.91 | 0.391722 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765449 | 47.2300 | 8759.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18900.421 | 18900.421 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18900.42 | 18900.42 | 0.593298 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765705 | 47.2454 | 13268.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 12616.147 | 12616.147 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12616.15 | 12616.15 | 0.396030 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765821 | 47.2527 | 8855.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 20339.336 | 20339.336 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20339.34 | 20339.34 | 0.638467 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00751202 | 46.3639 | 14277.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 13250.402 | 13250.402 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13250.40 | 13250.40 | 0.415940 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750152 | 46.3001 | 9300.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 20107.764 | 20107.764 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20107.76 | 20107.76 | 0.631198 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750668 | 46.3313 | 14115.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 13391.091 | 13391.091 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13391.09 | 13391.09 | 0.420356 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00750646 | 46.3303 | 9399.38 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 112826.657 | 84770.372 | 5.289706 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 114828.87 | 88210.68 | 5.289706 | 25.53 | 17.87 | 0.01026972 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.2481 | 24.00 | 0.00889430 | 45.6436 | 69414.72 | 0.00 | 116339.43 | 84207.44 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 47733.387 | 47733.387 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47733.39 | 47733.39 | 1.586912 | -13.26 | -13.26 | 0.00241176 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 70.8269 | 18.12 | 0.00742700 | 54.8196 | 19830.13 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 106569.489 | 78348.292 | 4.766122 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 109269.41 | 80856.90 | 4.766122 | 25.81 | 18.22 | 0.01059955 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 25.0764 | 24.00 | 0.00900059 | 46.1823 | 62448.40 | 0.00 | 109887.45 | 77968.30 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 52543.643 | 52543.643 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52543.64 | 52543.64 | 1.429837 | -19.04 | -19.04 | 0.00148973 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 83.5879 | 17.60 | 0.00688953 | 52.5976 | 23423.90 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 118386.158 | 88402.852 | 5.480330 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 120716.53 | 91633.94 | 5.480330 | 25.57 | 17.96 | 0.01036692 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.8084 | 24.00 | 0.00896714 | 46.0134 | 71708.29 | 0.00 | 122072.02 | 87853.50 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 51362.256 | 51362.256 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51362.26 | 51362.26 | 1.644099 | -14.27 | -14.27 | 0.00220778 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 72.6945 | 15.86 | 0.00735509 | 62.6841 | 22358.22 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 29326.929 | 29326.929 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29326.93 | 16436.34 | 1.0000 | 0.59259608 | 0.515949 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29326.93 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 11655.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 30086.820 | 30086.820 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30086.82 | 30086.82 | 1.0000 | 1.08475090 | 0.944448 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30086.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 21213.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 50916.308 | 50916.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50916.31 | 50916.31 | 1.0000 | 1.83573776 | 1.598301 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50916.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 35806.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 26040.251 | 26040.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26040.25 | 26040.25 | 1.0000 | 0.93885580 | 0.817423 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26040.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753990 | 21.00 | 0.00753990 | 46.5351 | 18271.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 16891.977 | 16891.977 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16891.98 | 16891.98 | 1.0000 | 0.60902374 | 0.530252 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16891.98 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00752778 | 21.00 | 0.00752778 | 46.4615 | 11852.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 25774.302 | 25774.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25774.30 | 25774.30 | 1.0000 | 0.92926730 | 0.809075 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25774.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00753547 | 21.00 | 0.00753547 | 46.5081 | 18085.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 17057.297 | 17057.297 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17057.30 | 17057.30 | 1.0000 | 0.61498419 | 0.535441 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17057.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.94 | 0.00753205 | 21.00 | 0.00753205 | 46.4875 | 11968.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 19107.391 | 19107.391 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19107.39 | 19107.39 | 1.0000 | 0.68889832 | 0.599795 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19107.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00766078 | 21.00 | 0.00766078 | 47.2681 | 13413.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12478.913 | 12478.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12478.91 | 12478.91 | 1.0000 | 0.44991500 | 0.391722 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12478.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765449 | 21.00 | 0.00765449 | 47.2300 | 8759.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18900.421 | 18900.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18900.42 | 18900.42 | 1.0000 | 0.68143621 | 0.593298 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18900.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765705 | 21.00 | 0.00765705 | 47.2454 | 13268.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12616.147 | 12616.147 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12616.15 | 12616.15 | 1.0000 | 0.45486285 | 0.396030 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12616.15 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765821 | 21.00 | 0.00765821 | 47.2527 | 8855.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 20339.336 | 20339.336 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20339.34 | 20339.34 | 1.0000 | 0.73331488 | 0.638467 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20339.34 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00751202 | 21.00 | 0.00751202 | 46.3639 | 14277.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 13250.402 | 13250.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13250.40 | 13250.40 | 1.0000 | 0.47773029 | 0.415940 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13250.40 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750152 | 21.00 | 0.00750152 | 46.3001 | 9300.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 20107.764 | 20107.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20107.76 | 20107.76 | 1.0000 | 0.72496579 | 0.631198 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20107.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750668 | 21.00 | 0.00750668 | 46.3313 | 14115.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13391.091 | 13391.091 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13391.09 | 13391.09 | 1.0000 | 0.48280269 | 0.420356 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13391.09 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00750646 | 21.00 | 0.00750646 | 46.3303 | 9399.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112826.657 | 84770.372 | 5.289706 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9309 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.289706 | 6.07552250 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 114828.87 | 88210.68 | 1.0177 | 6.07552250 | 5.289706 | 25.53 | 17.87 | 0.01026972 | 51824.0 | 10.85 | 10.85 | 0.00850000 | 32327.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12158.185 | 102670.68 | 31.20 | 0.01536508 | 23.13 | 1.12396000 | 21.2481 | 24.00 | 0.00889430 | 24.00 | 0.00889430 | 45.6436 | 69414.72 | 0.00 | 116339.43 | 84207.44 | 5.83558529 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.54 | 12.52 | 0.00902580 | 35386.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 47733.387 | 47733.387 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.289706 | 6.07552250 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47733.39 | 47733.39 | 1.0000 | 1.82265675 | 1.586912 | -13.26 | -13.26 | 0.00241176 | -7354.3 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47733.39 | -26.20 | 0.00036134 | -26.20 | 1.12396000 | 70.8269 | 18.15 | 0.00738980 | 18.12 | 0.00742700 | 54.8196 | 19830.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106569.489 | 78348.292 | 4.766122 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5440 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.766122 | 5.47415729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 109269.41 | 80856.90 | 1.0253 | 5.47415729 | 4.766122 | 25.81 | 18.22 | 0.01059955 | 52949.6 | 10.85 | 10.85 | 0.00850000 | 32328.6 | -999.0 | -999.00 | -999.00 | -999.00 | 10954.748 | 98314.67 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 25.0764 | 24.00 | 0.00900059 | 24.00 | 0.00900059 | 46.1823 | 62448.40 | 0.00 | 109887.45 | 77968.30 | 5.25796946 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.15 | 12.13 | 0.00880451 | 34423.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52543.643 | 52543.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.766122 | 5.47415729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52543.64 | 52543.64 | 1.0000 | 1.64224719 | 1.429837 | -19.04 | -19.04 | 0.00148973 | -15459.4 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52543.64 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 83.5879 | 17.42 | 0.00723668 | 17.60 | 0.00688953 | 52.5976 | 23423.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 118386.158 | 88402.852 | 5.480330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.480330 | 6.29446496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 120716.53 | 91633.94 | 1.0197 | 6.29446496 | 5.480330 | 25.57 | 17.96 | 0.01036692 | 52117.3 | 10.85 | 10.85 | 0.00850000 | 32327.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12596.328 | 108120.20 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 21.8084 | 24.00 | 0.00896714 | 24.00 | 0.00896714 | 46.0134 | 71708.29 | 0.00 | 122072.02 | 87853.50 | 6.04588117 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.44 | 12.42 | 0.00896558 | 35131.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 51362.256 | 51362.256 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.480330 | 6.29446496 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51362.26 | 51362.26 | 1.0000 | 1.88833949 | 1.644099 | -14.27 | -14.27 | 0.00220778 | -8874.3 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 51362.26 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 72.6945 | 17.50 | 0.00712351 | 15.86 | 0.00735509 | 62.6841 | 22358.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.29 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.77 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2555.83 | 3151.67 | 485.50 |
CORE_MID | 3077.50 | 3713.17 | 1366.50 |
CORE_TOP | 3478.50 | 3957.33 | 1943.83 |
PERIMETER_TOP_ZN_3 | 4051.00 | 4365.67 | 2757.33 |
PERIMETER_TOP_ZN_2 | 3910.67 | 4295.83 | 2550.17 |
PERIMETER_TOP_ZN_1 | 3658.83 | 4112.83 | 2244.33 |
PERIMETER_TOP_ZN_4 | 3814.17 | 4472.50 | 2623.50 |
PERIMETER_BOT_ZN_3 | 3844.67 | 4292.00 | 2534.50 |
PERIMETER_BOT_ZN_2 | 3823.50 | 4176.50 | 2337.00 |
PERIMETER_BOT_ZN_1 | 3652.00 | 4454.83 | 2451.17 |
PERIMETER_BOT_ZN_4 | 3739.17 | 4283.17 | 2348.83 |
PERIMETER_MID_ZN_3 | 3927.33 | 4066.50 | 2386.67 |
PERIMETER_MID_ZN_2 | 3162.17 | 3591.00 | 2005.83 |
PERIMETER_MID_ZN_1 | 3513.33 | 3832.17 | 1886.00 |
PERIMETER_MID_ZN_4 | 3652.17 | 4268.33 | 2300.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5123.83 | 5075.67 | 3234.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.17 | 1.00 | 0.17 | 0.67 |
CORE_MID | 2.33 | 0.00 | 1.83 | 0.00 |
CORE_TOP | 12.00 | 0.00 | 7.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 287.50 | 2.17 | 128.00 | 1.33 |
PERIMETER_TOP_ZN_2 | 192.50 | 12.83 | 45.67 | 12.83 |
PERIMETER_TOP_ZN_1 | 164.67 | 13.33 | 39.50 | 13.17 |
PERIMETER_TOP_ZN_4 | 185.67 | 20.67 | 45.17 | 11.83 |
PERIMETER_BOT_ZN_3 | 167.50 | 0.33 | 113.00 | 0.33 |
PERIMETER_BOT_ZN_2 | 56.83 | 5.33 | 10.00 | 5.33 |
PERIMETER_BOT_ZN_1 | 696.67 | 20.83 | 656.67 | 20.83 |
PERIMETER_BOT_ZN_4 | 58.50 | 11.17 | 12.67 | 5.33 |
PERIMETER_MID_ZN_3 | 164.50 | 0.17 | 81.17 | 0.00 |
PERIMETER_MID_ZN_2 | 95.33 | 11.50 | 16.67 | 11.50 |
PERIMETER_MID_ZN_1 | 72.83 | 13.17 | 12.17 | 13.17 |
PERIMETER_MID_ZN_4 | 96.50 | 19.33 | 19.83 | 11.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1009.33 | 88.50 | 761.17 | 72.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.913 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.654 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.651 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.908 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 1.530 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 1.280 | 0.123 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 1.617 | 0.129 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.669 | 0.065 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 1.219 | 0.069 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.998 | 1.363 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 1.239 | 0.069 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.798 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 1.425 | 0.114 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 1.211 | 0.102 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 1.514 | 0.108 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.92 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.62 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.92 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.62 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.67 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14674677.03 | 0.00 | 14674677.03 | 0.00 | 14674677.03 | 13393058.27 | 6141.83 | 36.88 | 2581.30 | 356.15 |
CORE_MID | 10480619.59 | 0.00 | 10480619.59 | 0.00 | 10480619.59 | 13393058.27 | 6681.75 | 24.78 | 2053.46 | 331.75 |
CORE_TOP | 10366403.69 | 0.00 | 10366403.69 | 0.00 | 10366403.69 | 13393058.27 | 6632.02 | 23.29 | 2104.69 | 107.94 |
PERIMETER_TOP_ZN_3 | 3056045.57 | 0.00 | 3056045.57 | 834711.09 | 3890756.67 | 2823374.22 | 4136.99 | 8.44 | 4614.57 | 107.94 |
PERIMETER_TOP_ZN_2 | 3260386.46 | 0.00 | 3260386.46 | 556470.72 | 3816857.18 | 1787429.43 | 4088.62 | 1.30 | 4670.08 | 107.94 |
PERIMETER_TOP_ZN_1 | 4300835.12 | 0.00 | 4300835.12 | 834711.09 | 5135546.21 | 2823374.22 | 4099.80 | 2.03 | 4658.17 | 107.94 |
PERIMETER_TOP_ZN_4 | 3454166.75 | 0.00 | 3454166.75 | 556470.72 | 4010637.47 | 1787312.18 | 4089.69 | 3.87 | 4666.43 | 107.94 |
PERIMETER_BOT_ZN_3 | 2286942.74 | 0.00 | 2286942.74 | 443809.51 | 2730752.25 | 2823374.22 | 6080.07 | 54.64 | 2625.29 | 356.15 |
PERIMETER_BOT_ZN_2 | 2636939.69 | 0.00 | 2636939.69 | 295871.23 | 2932810.92 | 1787429.43 | 4081.94 | 6.17 | 4671.89 | 356.15 |
PERIMETER_BOT_ZN_1 | 3417159.68 | 0.00 | 3417159.68 | 4810592.74 | 8227752.42 | 2823374.22 | 4107.90 | 8.97 | 4643.13 | 356.15 |
PERIMETER_BOT_ZN_4 | 2689332.75 | 0.00 | 2689332.75 | 295871.23 | 2985203.98 | 1787312.18 | 4137.30 | 12.36 | 4610.34 | 356.15 |
PERIMETER_MID_ZN_3 | 2695289.73 | 0.00 | 2695289.73 | 694831.36 | 3390121.09 | 2823374.22 | 4180.53 | 45.93 | 4533.54 | 331.70 |
PERIMETER_MID_ZN_2 | 3239805.82 | 0.00 | 3239805.82 | 463218.12 | 3703023.94 | 1787429.43 | 4051.18 | 1.67 | 4707.16 | 1240.73 |
PERIMETER_MID_ZN_1 | 4090107.06 | 0.00 | 4090107.06 | 694831.36 | 4784938.42 | 2823374.22 | 4080.25 | 4.41 | 4675.35 | 331.73 |
PERIMETER_MID_ZN_4 | 3253449.68 | 0.00 | 3253449.68 | 463218.12 | 3716667.80 | 1787312.18 | 4057.09 | 5.48 | 4697.43 | 331.73 |
Total Facility | 73902161.37 | 0.00 | 73902161.37 | 10944607.30 | 84846768.68 | 67843644.98 | 6824.94 | 221.62 | 4826.75 | 1430.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6687 | 0.0000 | 0.6687 | 0.0000 | 0.6687 | 0.4247 | 3409.04 | 36.88 | 2497.09 |
CORE_MID | 0.4802 | 0.0000 | 0.4802 | 0.0000 | 0.4802 | 0.4247 | 3920.32 | 24.78 | 1997.90 |
CORE_TOP | 0.4777 | 0.0000 | 0.4777 | 0.0000 | 0.4777 | 0.4247 | 3862.00 | 23.29 | 2057.71 |
PERIMETER_TOP_ZN_3 | 0.1408 | 0.0000 | 0.1408 | 0.0192 | 0.1600 | 0.0895 | 1366.97 | 8.44 | 4567.59 |
PERIMETER_TOP_ZN_2 | 0.1502 | 0.0000 | 0.1502 | 0.0128 | 0.1630 | 0.0567 | 1318.60 | 1.30 | 4623.10 |
PERIMETER_TOP_ZN_1 | 0.1983 | 0.0000 | 0.1983 | 0.0192 | 0.2175 | 0.0895 | 1329.78 | 2.03 | 4611.19 |
PERIMETER_TOP_ZN_4 | 0.1589 | 0.0000 | 0.1589 | 0.0128 | 0.1717 | 0.0567 | 1319.67 | 3.87 | 4619.46 |
PERIMETER_BOT_ZN_3 | 0.1038 | 0.0000 | 0.1038 | 0.0102 | 0.1140 | 0.0895 | 3347.27 | 54.22 | 2541.50 |
PERIMETER_BOT_ZN_2 | 0.1196 | 0.0000 | 0.1196 | 0.0068 | 0.1264 | 0.0567 | 1349.35 | 6.15 | 4587.50 |
PERIMETER_BOT_ZN_1 | 0.1553 | 0.0000 | 0.1553 | 0.2143 | 0.3696 | 0.0895 | 1375.11 | 8.97 | 4558.92 |
PERIMETER_BOT_ZN_4 | 0.1218 | 0.0000 | 0.1218 | 0.0068 | 0.1286 | 0.0567 | 1405.40 | 12.14 | 4525.46 |
PERIMETER_MID_ZN_3 | 0.1236 | 0.0000 | 0.1236 | 0.0160 | 0.1396 | 0.0895 | 1419.10 | 45.93 | 4477.97 |
PERIMETER_MID_ZN_2 | 0.1400 | 0.0000 | 0.1400 | 0.0113 | 0.1513 | 0.0567 | 1291.23 | 1.63 | 3741.14 |
PERIMETER_MID_ZN_1 | 0.1876 | 0.0000 | 0.1876 | 0.0160 | 0.2036 | 0.0895 | 1319.17 | 4.41 | 4619.43 |
PERIMETER_MID_ZN_4 | 0.1488 | 0.0000 | 0.1488 | 0.0106 | 0.1594 | 0.0567 | 1297.19 | 5.45 | 4640.36 |
Total Facility | 3.3754 | 0.0000 | 3.3754 | 0.3559 | 3.7313 | 2.1513 | 4031.63 | 220.92 | 4715.51 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33909598.07 | 0.00 | 33909598.07 | 22614548.33 | 4070.82 | 2.31 | 4686.87 | 356.15 |
PACU_VAV_MID | 31342794.55 | 0.00 | 31342794.55 | 22614548.33 | 4080.59 | 4.23 | 4675.18 | 331.07 |
PACU_VAV_TOP | 32237936.12 | 0.00 | 32237936.12 | 22614548.33 | 4100.29 | 1.03 | 4658.68 | 106.88 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5423 | 0.0000 | 1.5423 | 0.7171 | 1338.03 | 2.31 | 4602.66 |
PACU_VAV_MID | 1.4361 | 0.0000 | 1.4361 | 0.7171 | 1319.51 | 4.23 | 4619.26 |
PACU_VAV_TOP | 1.4853 | 0.0000 | 1.4853 | 0.7171 | 1330.27 | 1.03 | 4611.70 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.22 | 2997.96 | 0.00 | 0.00 | 0.00 | 2148.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.08 | 2823.23 | 0.00 | 0.00 | 0.00 | 2357.94 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2575.16 | 0.00 | 0.00 | 0.00 | 2301.07 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.6208 | 0.0000 | 0.0000 | 0.0000 | 1.0443 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3746 | 0.0000 | 0.0000 | 0.0000 | 1.1102 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.5388 | 0.0000 | 0.0000 | 0.0000 | 1.1133 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 824 |
Defaulted Fields | 545 |
Fields with Defaults | 2229 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1981.73 | 16005.15 | 19-MAR-17:10 | 272527.51 | 02-JAN-07:10 |
Electricity:Building | 1123.62 | 15718.93 | 01-JAN-09:40 | 83333.05 | 03-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 329.05 | 4741.03 | 01-JAN-00:10 | 25654.28 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 1123.62 | 15718.93 | 01-JAN-09:40 | 83333.05 | 03-NOV-07:10 |
InteriorLights:Electricity | 361.58 | 1693.55 | 01-JAN-09:40 | 36137.71 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 361.58 | 1693.55 | 01-JAN-09:40 | 36137.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 361.58 | 1693.55 | 01-JAN-09:40 | 36137.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 361.58 | 1693.55 | 01-JAN-09:40 | 36137.71 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 208.30 | 2777.44 | 01-JAN-00:10 | 14277.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 81.70 | 396.30 | 01-JAN-00:10 | 7133.97 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 38.62 | 553.47 | 01-JAN-09:40 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.93 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.93 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 24.43 | 350.37 | 01-JAN-09:10 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.54 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.54 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 38.54 | 553.47 | 01-JAN-09:20 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.85 | 51.50 | 01-JAN-09:20 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.85 | 51.50 | 01-JAN-09:20 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 24.41 | 350.37 | 01-JAN-09:40 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.52 | 32.60 | 01-JAN-09:40 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.52 | 32.60 | 01-JAN-09:40 | 952.03 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 38.60 | 553.47 | 01-JAN-09:40 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.92 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.92 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 24.43 | 350.37 | 01-JAN-09:10 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.53 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.53 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 38.53 | 553.47 | 01-JAN-09:10 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.84 | 51.50 | 01-JAN-09:10 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.84 | 51.50 | 01-JAN-09:10 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 24.41 | 350.37 | 01-JAN-09:30 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.51 | 32.60 | 01-JAN-09:30 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.51 | 32.60 | 01-JAN-09:30 | 952.03 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 38.62 | 553.47 | 01-JAN-09:40 | 3009.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.93 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 11.93 | 51.50 | 01-JAN-09:40 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 24.43 | 350.37 | 01-JAN-09:10 | 1905.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.54 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 7.54 | 32.61 | 01-JAN-09:10 | 952.10 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 38.54 | 553.47 | 01-JAN-09:20 | 3009.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.85 | 51.50 | 01-JAN-09:20 | 1503.90 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 11.85 | 51.50 | 01-JAN-09:20 | 1503.90 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 24.41 | 350.37 | 01-JAN-09:40 | 1905.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.52 | 32.60 | 01-JAN-09:40 | 952.03 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 7.52 | 32.60 | 01-JAN-09:40 | 952.03 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 247.34 | 4344.73 | 01-JAN-00:10 | 18520.31 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 14025.39 | 01-JAN-00:10 | 47562.27 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 641.30 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 747.21 | 286.22 | 10-JUN-17:40 | 230159.89 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1359.99 | 03-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 18.92 | 285.40 | 01-JAN-00:10 | 1359.99 | 03-NOV-07:20 |
ElectricityPurchased:Facility | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
ElectricityNet:Plant | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1981.73 | 16005.15 | 10-JUN-18:20 | 272527.51 | 02-JAN-07:10 |
Heating:Electricity | 453.69 | 0.00 | 01-JAN-00:40 | 222033.68 | 02-JAN-07:10 |
General:Heating:Electricity | 453.69 | 0.00 | 01-JAN-00:40 | 222033.68 | 02-JAN-07:10 |
Fans:Electricity | 112.31 | 0.00 | 01-JAN-00:40 | 32225.62 | 26-JUN-15:30 |
General:Fans:Electricity | 112.31 | 0.00 | 01-JAN-00:40 | 32225.62 | 26-JUN-15:30 |
ExteriorLights:Electricity | 110.89 | 0.00 | 01-JAN-08:00 | 8467.87 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 110.89 | 0.00 | 01-JAN-08:00 | 8467.87 | 01-JAN-06:10 |
Cooling:Electricity | 162.28 | 0.00 | 01-JAN-00:10 | 86319.64 | 04-AUG-15:30 |
General:Cooling:Electricity | 162.28 | 0.00 | 01-JAN-00:10 | 86319.64 | 04-AUG-15:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 10.16 | 0.00 | 01-JAN-00:10 | 1015.47 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 641.94 | 12061.80 | 01-JAN-00:10 | 36271.65 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 472.73 | 1156.00 | 06-JAN-05:30 | 193381.86 | 02-FEB-07:20 |
NaturalGas:HVAC | 356.70 | 0.00 | 01-JAN-00:40 | 185182.10 | 02-FEB-07:30 |
Heating:NaturalGas | 356.70 | 0.00 | 01-JAN-00:40 | 185182.10 | 02-FEB-07:30 |
General:Heating:NaturalGas | 356.70 | 0.00 | 01-JAN-00:40 | 185182.10 | 02-FEB-07:30 |
NaturalGas:Plant | 116.03 | 1156.00 | 04-JAN-05:20 | 12053.54 | 21-FEB-13:00 |
WaterSystems:NaturalGas | 116.03 | 1156.00 | 04-JAN-05:20 | 12053.54 | 21-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 116.03 | 1156.00 | 04-JAN-05:20 | 12053.54 | 21-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2760.90 | 0.00 | 01-JAN-00:40 | 550075.53 | 30-JAN-07:10 |
EnergyTransfer:Building | 1305.72 | 0.00 | 01-JAN-00:40 | 224678.45 | 30-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 217.83 | 0.00 | 01-JAN-00:40 | 28284.37 | 04-AUG-08:00 |
Heating:EnergyTransfer | 385.37 | 0.00 | 01-JAN-00:40 | 223724.66 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.57 | 0.00 | 01-JAN-00:10 | 21284.89 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 385.37 | 0.00 | 01-JAN-00:40 | 223724.66 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.57 | 0.00 | 01-JAN-00:10 | 21284.89 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 920.35 | 0.00 | 01-JAN-00:40 | 175284.88 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.26 | 0.00 | 01-JAN-00:40 | 28284.37 | 04-AUG-08:00 |
General:Cooling:EnergyTransfer | 920.35 | 0.00 | 01-JAN-00:40 | 175284.88 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 217.26 | 0.00 | 01-JAN-00:40 | 28284.37 | 04-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 78.43 | 0.00 | 01-JAN-00:40 | 20139.39 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.04 | 0.00 | 01-JAN-00:40 | 20139.39 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.04 | 0.00 | 01-JAN-00:40 | 20139.39 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.39 | 0.00 | 01-JAN-00:10 | 11688.66 | 26-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.39 | 0.00 | 01-JAN-00:10 | 11688.66 | 26-JUN-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.35 | 0.00 | 01-JAN-00:40 | 11237.23 | 11-DEC-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.29 | 0.00 | 01-JAN-00:40 | 11237.23 | 11-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 21.29 | 0.00 | 01-JAN-00:40 | 11237.23 | 11-DEC-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.06 | 0.00 | 01-JAN-00:10 | 5579.78 | 26-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.06 | 0.00 | 01-JAN-00:10 | 5579.78 | 26-JUN-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 34.60 | 0.00 | 01-JAN-00:40 | 8453.94 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.69 | 0.00 | 01-JAN-00:40 | 8453.94 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 14.69 | 0.00 | 01-JAN-00:40 | 8453.94 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.91 | 0.00 | 01-JAN-00:10 | 5716.77 | 26-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.91 | 0.00 | 01-JAN-00:10 | 5716.77 | 26-JUN-15:30 |
EnergyTransfer:Zone:CORE_MID | 141.39 | 0.00 | 01-JAN-00:40 | 25819.97 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.02 | 0.00 | 01-JAN-00:20 | 25819.97 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.02 | 0.00 | 01-JAN-00:20 | 25819.97 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 136.37 | 0.00 | 01-JAN-00:40 | 19225.88 | 26-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 136.37 | 0.00 | 01-JAN-00:40 | 19225.88 | 26-JUN-15:50 |
EnergyTransfer:Zone:CORE_TOP | 142.42 | 0.00 | 01-JAN-00:40 | 30688.36 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 18.63 | 0.00 | 01-JAN-00:40 | 30688.36 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 18.63 | 0.00 | 01-JAN-00:40 | 30688.36 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 123.80 | 0.00 | 01-JAN-00:20 | 21772.36 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 123.80 | 0.00 | 01-JAN-00:20 | 21772.36 | 26-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.26 | 0.00 | 01-JAN-00:40 | 11972.17 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.57 | 0.00 | 01-JAN-00:40 | 11972.17 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.57 | 0.00 | 01-JAN-00:40 | 11972.17 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.69 | 0.00 | 01-JAN-00:10 | 7720.72 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.69 | 0.00 | 01-JAN-00:10 | 7720.72 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.85 | 0.00 | 01-JAN-00:40 | 11379.60 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.18 | 0.00 | 01-JAN-00:40 | 11379.60 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.18 | 0.00 | 01-JAN-00:40 | 11379.60 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.68 | 0.00 | 01-JAN-00:20 | 9262.14 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.68 | 0.00 | 01-JAN-00:20 | 9262.14 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 73.61 | 0.00 | 01-JAN-00:40 | 14758.05 | 09-DEC-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.14 | 0.00 | 01-JAN-00:40 | 14758.05 | 09-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 27.14 | 0.00 | 01-JAN-00:40 | 14758.05 | 09-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 46.47 | 0.00 | 01-JAN-00:20 | 14287.71 | 07-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 46.47 | 0.00 | 01-JAN-00:20 | 14287.71 | 07-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.70 | 0.00 | 01-JAN-00:40 | 12281.66 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.13 | 0.00 | 01-JAN-00:40 | 12281.66 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.13 | 0.00 | 01-JAN-00:40 | 12281.66 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.57 | 0.00 | 01-JAN-00:20 | 9853.98 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.57 | 0.00 | 01-JAN-00:20 | 9853.98 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 45.47 | 0.00 | 01-JAN-00:40 | 8621.73 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.04 | 0.00 | 01-JAN-00:40 | 8621.73 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.04 | 0.00 | 01-JAN-00:40 | 8621.73 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.42 | 0.00 | 01-JAN-00:20 | 5932.88 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 22.42 | 0.00 | 01-JAN-00:20 | 5932.88 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 39.11 | 0.00 | 01-JAN-00:40 | 8474.88 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.02 | 0.00 | 01-JAN-00:40 | 8474.88 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 13.02 | 0.00 | 01-JAN-00:40 | 8474.88 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.09 | 0.00 | 01-JAN-00:20 | 7219.76 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 26.09 | 0.00 | 01-JAN-00:20 | 7219.76 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 83.08 | 0.00 | 01-JAN-00:40 | 20277.21 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 50.71 | 0.00 | 01-JAN-00:40 | 20277.21 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 50.71 | 0.00 | 01-JAN-00:40 | 20277.21 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.37 | 0.00 | 01-JAN-00:20 | 12982.24 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 32.37 | 0.00 | 01-JAN-00:20 | 12982.24 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 39.83 | 0.00 | 01-JAN-00:40 | 8967.24 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.51 | 0.00 | 01-JAN-00:40 | 8967.24 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 13.51 | 0.00 | 01-JAN-00:40 | 8967.24 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.33 | 0.00 | 01-JAN-00:20 | 7567.54 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 26.33 | 0.00 | 01-JAN-00:20 | 7567.54 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 50.00 | 0.00 | 01-JAN-00:40 | 9331.21 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.28 | 0.00 | 01-JAN-00:40 | 9331.21 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.28 | 0.00 | 01-JAN-00:40 | 9331.21 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.72 | 0.00 | 01-JAN-00:10 | 7005.83 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.72 | 0.00 | 01-JAN-00:10 | 7005.83 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 44.01 | 0.00 | 01-JAN-00:40 | 9548.68 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.22 | 0.00 | 01-JAN-00:40 | 9548.68 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 13.22 | 0.00 | 01-JAN-00:40 | 9548.68 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.80 | 0.00 | 01-JAN-00:20 | 9020.79 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.80 | 0.00 | 01-JAN-00:20 | 9020.79 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.72 | 0.00 | 01-JAN-00:40 | 13123.92 | 07-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.77 | 0.00 | 01-JAN-00:40 | 13102.88 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 14.77 | 0.00 | 01-JAN-00:40 | 13102.88 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.94 | 0.00 | 01-JAN-00:20 | 13123.92 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 47.94 | 0.00 | 01-JAN-00:20 | 13123.92 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 45.05 | 0.00 | 01-JAN-00:40 | 9658.33 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.56 | 0.00 | 01-JAN-00:40 | 9658.33 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 13.56 | 0.00 | 01-JAN-00:40 | 9658.33 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.49 | 0.00 | 01-JAN-00:20 | 9301.18 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.49 | 0.00 | 01-JAN-00:20 | 9301.18 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
EnergyTransfer:HVAC | 1399.36 | 0.00 | 01-JAN-00:40 | 364198.07 | 04-AUG-07:10 |
HeatingCoils:EnergyTransfer | 739.06 | 0.00 | 01-JAN-00:40 | 333971.17 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 660.30 | 0.00 | 01-JAN-00:10 | 364198.07 | 04-AUG-07:10 |
EnergyTransfer:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7153.07 | 22-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.571 | -217.257 | 0.000 | 0.000 | 33.737 | 81.703 | 247.342 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -146.097 |
CORE_MID | 0.000 | 0.000 | 5.023 | -136.367 | 0.000 | 0.000 | 35.011 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -111.971 |
CORE_TOP | 0.000 | 0.000 | 18.625 | -123.797 | 0.000 | 0.000 | 35.689 | 81.703 | 126.600 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -138.821 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 37.570 | -27.685 | 0.000 | 0.000 | 7.739 | 11.933 | 26.688 | 16.908 | 0.000 | 0.120 | 0.001 | 0.000 | -38.395 | 0.000 | -15.106 | -19.772 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 22.177 | -29.678 | 0.000 | 0.000 | 4.882 | 7.538 | 16.895 | 31.606 | 0.000 | 0.083 | 0.000 | 0.000 | -23.756 | 0.000 | -10.147 | -19.600 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 27.142 | -46.473 | 0.000 | 0.000 | 7.603 | 11.850 | 26.688 | 64.946 | 0.000 | 0.109 | 0.001 | 0.000 | -34.751 | 0.000 | -15.527 | -41.587 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 23.126 | -30.573 | 0.000 | 0.000 | 4.943 | 7.518 | 16.895 | 33.031 | 0.000 | 0.079 | 0.000 | 0.000 | -24.639 | 0.000 | -10.184 | -20.196 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 23.042 | -22.424 | 0.000 | 0.000 | 7.681 | 11.915 | 26.688 | 17.147 | 0.000 | 0.073 | 0.000 | 0.000 | -39.222 | 0.000 | -8.325 | -16.578 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 13.021 | -26.091 | 0.000 | 0.000 | 4.851 | 7.531 | 16.895 | 31.787 | 0.000 | 0.047 | 0.000 | 0.000 | -24.524 | 0.000 | -5.626 | -17.890 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 50.713 | -32.370 | 0.000 | 0.000 | 7.911 | 11.838 | 26.688 | 65.996 | 0.000 | 1.694 | 0.000 | 0.000 | -35.368 | 0.000 | -74.060 | -23.041 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 13.509 | -26.325 | 0.000 | 0.000 | 4.894 | 7.511 | 16.895 | 33.248 | 0.000 | 0.043 | 0.000 | 0.000 | -25.425 | 0.000 | -5.649 | -18.702 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 22.280 | -27.717 | 0.000 | 0.000 | 7.634 | 11.933 | 26.688 | 16.608 | 0.000 | 0.099 | 0.000 | 0.000 | -39.965 | 0.000 | -13.064 | -4.496 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 13.216 | -30.795 | 0.000 | 0.000 | 3.591 | 7.538 | 16.895 | 31.437 | 0.000 | 0.073 | 0.000 | 0.000 | -24.661 | 0.000 | -8.740 | -8.553 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 14.775 | -47.944 | 0.000 | 0.000 | 7.500 | 11.850 | 26.688 | 64.627 | 0.000 | 0.092 | 0.000 | 0.000 | -36.254 | 0.000 | -13.443 | -27.891 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 13.562 | -31.485 | 0.000 | 0.000 | 4.895 | 7.518 | 16.895 | 32.881 | 0.000 | 0.065 | 0.000 | 0.000 | -25.614 | 0.000 | -8.780 | -9.937 |
TOPFLOOR_PLENUM | 51.036 | -27.390 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.093 | 0.002 | 0.000 | 0.000 | 0.000 | -22.787 | -0.951 |
MIDFLOOR_PLENUM | 21.294 | -16.058 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.141 | 16.830 | 0.000 | 0.000 | 0.000 | -22.207 | -0.000 |
FIRSTFLOOR_PLENUM | 14.694 | -19.910 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.110 | 22.998 | 0.000 | 0.000 | 0.000 | -17.893 | -0.000 |
Total Facility | 87.024 | -63.358 | 298.352 | -856.983 | 0.000 | 0.000 | 178.562 | 361.583 | 762.041 | 440.223 | 0.000 | 2.921 | 39.833 | 0.000 | -372.574 | 0.000 | -251.537 | -626.082 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -46240.17 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 40309.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-SEP-04:02 | 0.00 | 0.00 | 0.00 | -34368.61 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 30401.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-JUL-04:02 | 0.00 | 0.00 | 0.00 | -36444.60 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 32477.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 | -10454.39 | 0.00 | 0.00 | 0.00 | 51.50 | 501.96 | 3812.60 | 0.00 | 311.48 | 5776.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:52 | 0.00 | 0.00 | 0.00 | -14398.07 | 0.00 | 0.00 | 13.32 | 32.61 | 317.77 | 10503.54 | 0.00 | 0.00 | 3583.11 | 0.00 | -0.00 | 0.00 | -52.28 | 0.00 |
PERIMETER_TOP_ZN_1 | 17-SEP-13:22 | 0.00 | 0.00 | 0.00 | -19407.26 | 0.00 | 0.00 | 22.59 | 51.50 | 501.96 | 13177.49 | 0.00 | 0.00 | 5831.16 | 0.00 | -0.00 | 0.00 | -177.43 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -16875.24 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 11020.95 | 0.00 | 191.65 | 5312.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | -5933.49 | 0.00 | 0.00 | 737.23 | 927.16 | 1505.89 | 3536.29 | 0.00 | 50.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -823.86 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:21 | 0.00 | 0.00 | 0.00 | -12290.75 | 0.00 | 0.00 | 15.56 | 32.61 | 317.77 | 9616.11 | 0.00 | 0.00 | 2337.87 | 0.00 | -0.00 | 0.00 | -29.16 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:42 | 0.00 | 0.00 | 0.00 | -14942.57 | 0.00 | 0.00 | 24.76 | 51.50 | 501.96 | 13079.65 | 0.00 | 0.00 | 1385.90 | 0.00 | -0.00 | 0.00 | -101.19 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 | -13731.51 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 8644.80 | 0.00 | 0.00 | 4740.91 | 0.00 | -0.00 | 0.00 | -4.56 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-19:12 | 0.00 | 0.00 | 0.00 | -10494.01 | 0.00 | 0.00 | 0.00 | 51.50 | 501.96 | 2472.39 | 0.00 | 106.67 | 7361.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:41 | 0.00 | 0.00 | 0.00 | -15506.05 | 0.00 | 0.00 | 13.48 | 32.61 | 317.77 | 10748.41 | 0.00 | 0.00 | 4485.21 | 0.00 | -0.00 | 0.00 | -91.43 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:32 | 0.00 | 0.00 | 0.00 | -16684.69 | 0.00 | 0.00 | 24.77 | 51.50 | 501.96 | 10895.64 | 0.00 | 0.00 | 5230.76 | 0.00 | -0.00 | 0.00 | -19.95 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 | -16241.81 | 0.00 | 0.00 | 0.00 | 32.60 | 317.76 | 8573.03 | 0.00 | 0.00 | 7339.15 | 0.00 | -0.00 | 0.00 | -20.74 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:50 | 0.00 | -11688.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.07 | 11588.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 26-JUN-15:40 | 0.00 | -5579.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.28 | 5481.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 26-JUN-12:07 | 0.00 | -6306.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 6224.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-04:02 | 0.00 | 9931.63 | 0.00 | -179270.74 | 0.00 | 0.00 | 0.00 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 156489.74 | 0.00 | -6928.12 | 0.00 | -2283.89 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 26634.86 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 5138.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32565.99 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 29513.57 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33481.12 |
CORE_TOP | 17-JAN-05:11 | 0.00 | 0.00 | 33699.09 | 0.00 | 0.00 | 0.00 | 0.00 | 792.68 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37666.64 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 13207.06 | 0.00 | 0.00 | 0.00 | 124.29 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4381.86 | 0.00 | -589.01 | -9196.87 |
PERIMETER_TOP_ZN_2 | 26-NOV-04:01 | 0.00 | 0.00 | 13346.75 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 317.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2685.29 | 0.00 | -1503.55 | -9528.57 |
PERIMETER_TOP_ZN_1 | 30-JAN-06:01 | 0.00 | 0.00 | 16670.14 | 0.00 | 0.00 | 0.00 | 121.75 | 167.10 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4353.09 | 0.00 | -606.40 | -12668.79 |
PERIMETER_TOP_ZN_4 | 30-JAN-06:01 | 0.00 | 0.00 | 14727.79 | 0.00 | 0.00 | 0.00 | 77.30 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2990.69 | 0.00 | -405.60 | -11938.28 |
PERIMETER_BOT_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 9231.07 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4441.97 | 0.00 | -1417.42 | -4208.07 |
PERIMETER_BOT_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 10656.18 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2884.55 | 0.00 | -952.93 | -7348.19 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 21467.11 | 0.00 | 0.00 | 0.00 | 233.65 | 501.29 | 669.28 | 0.00 | 0.00 | 0.00 | 32755.95 | 0.00 | -5220.94 | 0.00 | -50406.35 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 11427.24 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2974.08 | 0.00 | -954.84 | -8027.78 |
PERIMETER_MID_ZN_3 | 30-JAN-01:42 | 0.00 | 0.00 | 10084.16 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 669.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4331.94 | 0.00 | -2295.81 | -4209.24 |
PERIMETER_MID_ZN_2 | 30-JAN-01:42 | 0.00 | 0.00 | 12762.68 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2797.92 | 0.00 | -1556.31 | -8885.02 |
PERIMETER_MID_ZN_1 | 29-JAN-05:42 | 0.00 | 0.00 | 14889.43 | 0.00 | 0.00 | 0.00 | 0.00 | 83.54 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3796.62 | 0.00 | -3783.34 | -7894.98 |
PERIMETER_MID_ZN_4 | 30-JAN-01:42 | 0.00 | 0.00 | 13296.21 | 0.00 | 0.00 | 0.00 | 0.00 | 52.89 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2893.69 | 0.00 | -1558.61 | -9320.48 |
TOPFLOOR_PLENUM | 02-FEB-06:06 | 21696.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -678.06 | -21018.49 |
MIDFLOOR_PLENUM | 30-JAN-07:04 | 11467.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -719.34 | -10748.07 |
FIRSTFLOOR_PLENUM | 02-JAN-06:12 | 9791.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -395.16 | -9396.61 |
Total Facility | 30-JAN-06:01 | 32270.41 | 0.00 | 221680.47 | 0.00 | 0.00 | 0.00 | 2610.01 | 4015.40 | 18045.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45617.53 | 0.00 | -17159.83 | -215844.92 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.9770 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2897 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6318 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7661 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.1210 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4803 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.9885 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7931 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8159 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.7762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.0605 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.9157 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0686 | 3.0686 | 0.9206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2804 | 2.2804 | 0.7708 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4043 | 2.4043 | 0.8006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8174 | 0.8174 | 0.2452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8644 | 0.8644 | 0.2593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0778 | 1.0778 | 0.3233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9571 | 0.9571 | 0.2871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5998 | 0.5998 | 0.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7016 | 0.7016 | 0.2105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8523 | 0.8523 | 0.2557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7547 | 0.7547 | 0.2264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6501 | 0.6501 | 0.1950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8438 | 0.8438 | 0.2531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9764 | 0.9764 | 0.2929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8811 | 0.8811 | 0.2643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.9770 | 5.2897 | 5.9770 | 1.7931 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6318 | 4.7661 | 5.6318 | 1.7762 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.1210 | 5.4803 | 6.1210 | 1.9157 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5343 | 1.5343 | 0.9206 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1402 | 1.1402 | 0.7708 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2022 | 1.2022 | 0.8006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4087 | 0.4087 | 0.2452 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4322 | 0.4322 | 0.2593 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5389 | 0.5389 | 0.3233 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4786 | 0.4786 | 0.2871 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2999 | 0.2999 | 0.1799 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3508 | 0.3508 | 0.2105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4261 | 0.4261 | 0.2557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3774 | 0.3774 | 0.2264 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3251 | 0.3251 | 0.1950 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4219 | 0.4219 | 0.2531 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4882 | 0.4882 | 0.2929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4406 | 0.4406 | 0.2643 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.9885 | 1.7931 | 1.7931 | 1.7931 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8159 | 1.7762 | 1.7762 | 1.7762 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.0605 | 1.9157 | 1.9157 | 1.9157 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 761.17 |
Number of hours cooling loads not met | 72.67 |
Number of hours not met | 833.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 453.69 | 222033.68 | 356.70 | 185182.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 162.28 | 86319.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 361.58 | 36137.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 110.89 | 8467.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.30 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 18.92 | 1359.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 112.31 | 32225.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 116.03 | 12053.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 762.04 | 1981.73 |
Natural Gas | 0.00 | 472.73 |
Additional | 0.00 | 0.00 |
Total | 762.04 | 2454.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.58 |
Space Heating | 91.06 |
Space Cooling | 32.57 |
Fans (All) | 22.54 |
Service Water Heating | 0.00 |
Receptacle Equipment | 152.95 |
Miscellaneous (All) | 397.76 |
Subtotal | 397.76 |
Natural Gas [MJ/m2] | |
Space Heating | 71.60 |
Service Water Heating | 23.29 |
Miscellaneous (All) | 94.88 |
Subtotal | 94.88 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.73 |
Space Heating | 33.02 |
Space Cooling | 6.61 |
Fans (All) | 4.58 |
Service Water Heating | 4.73 |
Receptacle Equipment | 31.05 |
Miscellaneous | 5.29 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2616. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 2357. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8646.83 | 113.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8677.33 | 82.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8700.67 | 59.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8707.00 | 53.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8667.83 | 92.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8670.00 | 90.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8646.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.17 | 0.00 | 0.00 | 0.00 |
Average | 8719.41 | 40.59 | 0.00 | 0.00 | 0.00 |
Sum | 156949.33 | 730.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128293.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 10.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.76 | 0.57 | 0.00 | 0.00 | 0.00 |
Sum | 614569.67 | 10.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8196.17 | 563.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8351.67 | 408.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8432.17 | 327.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8327.00 | 433.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8328.83 | 431.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8312.17 | 447.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8288.83 | 471.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8418.17 | 341.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8329.67 | 430.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8239.33 | 520.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8279.33 | 480.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8256.17 | 503.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8312.83 | 447.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8269.83 | 490.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8243.67 | 516.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7938.83 | 821.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8305.33 | 454.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8333.00 | 427.00 | 0.00 | 0.00 | 0.00 |
Min | 7938.83 | 327.83 | 0.00 | 0.00 | 0.00 |
Max | 8432.17 | 821.17 | 0.00 | 0.00 | 0.00 |
Average | 8286.83 | 473.17 | 0.00 | 0.00 | 0.00 |
Sum | 149163.00 | 8517.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127962.33 | 341.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128131.33 | 172.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128191.00 | 113.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24899.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24905.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24894.33 | 14.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24230.67 | 678.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14010.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24891.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24900.83 | 8.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128191.00 | 678.33 | 0.00 | 0.00 | 0.00 |
Average | 34067.10 | 76.23 | 0.00 | 0.00 | 0.00 |
Sum | 613207.83 | 1372.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101724E+11 | 10071.90 | 13-JAN-17:00 | 2.20 | 0.77 | 0.164409E+10 | 2606.55 | 13-JAN-14:09 | 2.20 | 0.77 |
February | 0.983450E+10 | 10980.66 | 24-FEB-17:00 | 7.20 | 5.13 | 0.159675E+10 | 2606.61 | 24-FEB-14:09 | 7.20 | 5.13 |
March | 0.134882E+11 | 17124.37 | 29-MAR-07:20 | 7.80 | 6.92 | 0.204990E+10 | 2606.63 | 28-MAR-13:09 | 7.80 | 6.92 |
April | 0.154261E+11 | 39481.74 | 17-APR-05:03 | 11.42 | 9.68 | 0.187797E+10 | 2606.69 | 11-APR-13:09 | 11.42 | 9.68 |
May | 0.213046E+11 | 44493.47 | 31-MAY-04:02 | 16.60 | 15.22 | 0.207318E+10 | 2606.72 | 09-MAY-13:09 | 16.60 | 15.22 |
June | 0.262796E+11 | 46004.96 | 27-JUN-04:02 | 20.50 | 19.04 | 0.206858E+10 | 2606.70 | 01-JUN-09:00 | 20.50 | 19.04 |
July | 0.273037E+11 | 46246.13 | 05-JUL-04:02 | 18.72 | 18.00 | 0.192418E+10 | 2606.65 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.288976E+11 | 45378.51 | 14-AUG-04:02 | 16.02 | 15.64 | 0.216035E+10 | 2880.80 | 04-AUG-07:49 | 16.02 | 15.64 |
September | 0.237121E+11 | 45739.91 | 11-SEP-04:02 | 20.50 | 17.33 | 0.191476E+10 | 2606.65 | 06-SEP-09:09 | 20.50 | 17.33 |
October | 0.166717E+11 | 21555.29 | 06-OCT-07:03 | 5.47 | 3.60 | 0.197674E+10 | 2608.41 | 26-OCT-09:39 | 3.20 | 1.35 |
November | 0.133005E+11 | 20819.59 | 02-NOV-07:04 | 6.78 | 5.70 | 0.187088E+10 | 2606.65 | 01-NOV-09:09 | 6.78 | 5.70 |
December | 0.108667E+11 | 10647.57 | 07-DEC-16:20 | -5.7 | -8.8 | 0.169926E+10 | 2606.55 | 06-DEC-14:09 | -5.7 | -8.8 |
Annual Sum or Average | 0.217258E+12 | 0.228566E+11 | ||||||||
Minimum of Months | 0.983450E+10 | 10071.90 | -5.7 | -8.8 | 0.159675E+10 | 2606.55 | -5.7 | -8.8 | ||
Maximum of Months | 0.288976E+11 | 46246.13 | 20.50 | 19.04 | 0.216035E+10 | 2880.80 | 21.28 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 18947354.68 | 1016.39 | 24-FEB-14:40 | 8.13 | 5.47 | 0.00 | 0.00 | 01-FEB-00:10 | 8.13 | 5.47 |
March | 0.278088E+09 | 2433.09 | 28-MAR-16:10 | 15.40 | 10.17 | 0.00 | 0.00 | 01-MAR-00:10 | 15.40 | 10.17 |
April | 0.147229E+10 | 9062.99 | 18-APR-14:20 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.332045E+10 | 10244.32 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.584446E+10 | 11688.66 | 26-JUN-13:50 | 31.60 | 21.99 | 0.00 | 0.00 | 01-JUN-00:10 | 31.60 | 21.99 |
July | 0.644271E+10 | 10953.58 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.596551E+10 | 11652.48 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.326887E+10 | 10502.12 | 07-SEP-15:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.652344E+09 | 4195.15 | 20-OCT-15:00 | 23.30 | 13.36 | 0.00 | 0.00 | 01-OCT-00:10 | 23.30 | 13.36 |
November | 0.126784E+09 | 2250.16 | 03-NOV-14:00 | 16.10 | 10.47 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.47 |
December | 85875.62 | 139.35 | 02-DEC-17:25 | 1.70 | 0.82 | 0.00 | 0.00 | 01-DEC-00:10 | 1.70 | 0.82 |
Annual Sum or Average | 0.273905E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.644271E+10 | 11688.66 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38685422.79 | 2185.44 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 19729394.66 | 2474.08 | 16-FEB-05:01 | -17.3 | -17.7 | 0.00 | 0.00 | 01-FEB-00:10 | -17.3 | -17.7 |
March | 0.106399E+09 | 1833.22 | 04-MAR-05:01 | -8.8 | -9.5 | 0.00 | 0.00 | 01-MAR-00:10 | -8.8 | -9.5 |
April | 0.662153E+09 | 3626.28 | 18-APR-15:20 | 27.20 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 20.26 |
May | 0.163226E+10 | 4321.67 | 31-MAY-15:40 | 28.87 | 19.09 | 0.00 | 0.00 | 01-MAY-00:10 | 28.87 | 19.09 |
June | 0.343759E+10 | 5579.78 | 26-JUN-15:40 | 31.50 | 22.02 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 22.02 |
July | 0.390395E+10 | 5263.40 | 03-JUL-15:30 | 29.45 | 24.36 | 0.00 | 0.00 | 01-JUL-00:10 | 29.45 | 24.36 |
August | 0.365464E+10 | 5210.79 | 04-AUG-15:40 | 33.90 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.00 |
September | 0.210669E+10 | 4797.00 | 08-SEP-15:50 | 29.50 | 18.55 | 0.00 | 0.00 | 01-SEP-00:10 | 29.50 | 18.55 |
October | 0.351691E+09 | 1969.77 | 13-OCT-06:01 | 0.75 | -0.4 | 0.00 | 0.00 | 01-OCT-00:10 | 0.75 | -0.4 |
November | 0.133186E+09 | 1660.35 | 21-NOV-05:01 | -9.0 | -9.8 | 0.00 | 0.00 | 01-NOV-00:10 | -9.0 | -9.8 |
December | 10908126.79 | 2473.42 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.160579E+11 | 0.00 | ||||||||
Minimum of Months | 10908126.79 | 1660.35 | -21.2 | -21.5 | 0.00 | 0.00 | -21.2 | -21.5 | ||
Maximum of Months | 0.390395E+10 | 5579.78 | 33.90 | 26.00 | 0.00 | 0.00 | 33.90 | 26.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78768281.26 | 3163.49 | 06-JAN-07:10 | -27.4 | -27.6 | 0.00 | 0.00 | 01-JAN-00:10 | -27.4 | -27.6 |
February | 93922785.34 | 3965.25 | 02-FEB-17:10 | -29.6 | -29.9 | 0.00 | 0.00 | 01-FEB-00:10 | -29.6 | -29.9 |
March | 0.260290E+09 | 2419.32 | 22-MAR-06:10 | -6.8 | -7.6 | 0.00 | 0.00 | 01-MAR-00:10 | -6.8 | -7.6 |
April | 0.922132E+09 | 3630.47 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.219093E+10 | 4377.35 | 31-MAY-15:10 | 29.72 | 19.55 | 0.00 | 0.00 | 01-MAY-00:10 | 29.72 | 19.55 |
June | 0.385923E+10 | 6307.85 | 26-JUN-12:07 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.438144E+10 | 5562.75 | 05-JUL-12:10 | 26.20 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 26.20 | 20.38 |
August | 0.435484E+10 | 5343.48 | 04-AUG-12:08 | 31.20 | 26.19 | 0.00 | 0.00 | 01-AUG-00:10 | 31.20 | 26.19 |
September | 0.278778E+10 | 5149.21 | 11-SEP-15:30 | 28.05 | 20.01 | 0.00 | 0.00 | 01-SEP-00:10 | 28.05 | 20.01 |
October | 0.649215E+09 | 2566.28 | 31-OCT-06:01 | 0.18 | -0.9 | 0.00 | 0.00 | 01-OCT-00:10 | 0.18 | -0.9 |
November | 0.262854E+09 | 2339.57 | 09-NOV-18:01 | 1.10 | 0.21 | 0.00 | 0.00 | 01-NOV-00:10 | 1.10 | 0.21 |
December | 68629030.80 | 2795.35 | 08-DEC-17:10 | -19.2 | -19.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.2 | -19.4 |
Annual Sum or Average | 0.199100E+11 | 0.00 | ||||||||
Minimum of Months | 68629030.80 | 2339.57 | -29.6 | -29.9 | 0.00 | 0.00 | -29.6 | -29.9 | ||
Maximum of Months | 0.438144E+10 | 6307.85 | 31.20 | 26.19 | 0.00 | 0.00 | 31.20 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463568E+10 | 6644.49 | 13-JAN-17:00 | 2.20 | 0.77 | 0.149548E+10 | 2330.11 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.524976E+10 | 6880.86 | 24-FEB-17:00 | 7.20 | 5.13 | 0.140776E+10 | 2355.40 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.806806E+10 | 8545.08 | 24-MAR-16:00 | 10.60 | 5.50 | 0.182411E+10 | 2604.52 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.995448E+10 | 31291.36 | 17-APR-05:03 | 11.42 | 9.68 | 0.175735E+10 | 2606.60 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.143569E+11 | 31989.88 | 30-MAY-05:03 | 14.50 | 14.50 | 0.204827E+10 | 2606.69 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.182991E+11 | 34322.30 | 27-JUN-04:02 | 20.50 | 19.04 | 0.206056E+10 | 2606.66 | 01-JUN-09:00 | 20.50 | 19.04 |
July | 0.193959E+11 | 34239.95 | 03-JUL-04:02 | 18.80 | 17.39 | 0.192090E+10 | 2606.65 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.196577E+11 | 32671.15 | 14-AUG-04:02 | 16.02 | 15.64 | 0.215591E+10 | 2662.16 | 04-AUG-07:30 | 16.02 | 15.64 |
September | 0.149657E+11 | 34367.05 | 11-SEP-04:02 | 20.50 | 17.33 | 0.189314E+10 | 2606.68 | 06-SEP-09:09 | 20.50 | 17.33 |
October | 0.936194E+10 | 10593.89 | 20-OCT-16:00 | 21.30 | 12.72 | 0.186027E+10 | 2606.54 | 12-OCT-13:09 | 21.30 | 12.72 |
November | 0.709228E+10 | 10144.77 | 03-NOV-16:00 | 15.00 | 9.33 | 0.167155E+10 | 2606.48 | 09-NOV-14:00 | 2.80 | 0.77 |
December | 0.532973E+10 | 6460.91 | 01-DEC-16:30 | -2.8 | -4.8 | 0.148745E+10 | 2286.47 | 07-DEC-14:00 | -3.3 | -7.2 |
Annual Sum or Average | 0.136367E+12 | 0.215828E+11 | ||||||||
Minimum of Months | 0.463568E+10 | 6460.91 | -2.8 | -4.8 | 0.140776E+10 | 2286.47 | -3.3 | -7.2 | ||
Maximum of Months | 0.196577E+11 | 34367.05 | 21.30 | 19.04 | 0.215591E+10 | 2662.16 | 23.27 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265184E+10 | 6457.19 | 13-JAN-16:50 | 2.48 | 0.97 | 0.146382E+10 | 2234.36 | 13-JAN-14:00 | 2.48 | 0.97 |
February | 0.367441E+10 | 6979.38 | 24-FEB-17:00 | 7.20 | 5.13 | 0.135695E+10 | 2316.93 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.651356E+10 | 8151.42 | 24-MAR-16:00 | 10.60 | 5.50 | 0.172731E+10 | 2554.55 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.911151E+10 | 18064.32 | 18-APR-15:40 | 26.10 | 19.83 | 0.168000E+10 | 2606.65 | 18-APR-09:09 | 26.10 | 19.83 |
May | 0.139193E+11 | 25562.11 | 30-MAY-05:03 | 14.50 | 14.50 | 0.201557E+10 | 2606.69 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.184044E+11 | 36087.76 | 26-JUN-04:02 | 21.60 | 20.40 | 0.204439E+10 | 2606.65 | 01-JUN-09:00 | 21.60 | 20.40 |
July | 0.194313E+11 | 36448.25 | 03-JUL-04:02 | 18.80 | 17.39 | 0.191617E+10 | 2606.67 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.192281E+11 | 34396.83 | 04-AUG-04:02 | 22.80 | 22.50 | 0.214736E+10 | 2606.71 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.137671E+11 | 33696.84 | 11-SEP-05:02 | 19.90 | 17.36 | 0.184121E+10 | 2606.71 | 06-SEP-09:39 | 19.90 | 17.36 |
October | 0.820544E+10 | 10159.92 | 20-OCT-16:00 | 21.30 | 12.72 | 0.171981E+10 | 2593.43 | 20-OCT-13:00 | 21.30 | 12.72 |
November | 0.558883E+10 | 9066.76 | 03-NOV-16:00 | 15.00 | 9.33 | 0.156796E+10 | 2576.32 | 03-NOV-13:00 | 15.00 | 9.33 |
December | 0.330143E+10 | 6312.82 | 01-DEC-16:10 | -2.1 | -4.3 | 0.142467E+10 | 2192.26 | 01-DEC-14:00 | -2.1 | -4.3 |
Annual Sum or Average | 0.123797E+12 | 0.209052E+11 | ||||||||
Minimum of Months | 0.265184E+10 | 6312.82 | -2.1 | -4.3 | 0.135695E+10 | 2192.26 | -2.1 | -4.3 | ||
Maximum of Months | 0.194313E+11 | 36448.25 | 26.10 | 22.50 | 0.214736E+10 | 2606.71 | 26.10 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18366317.97 | 1421.27 | 14-JAN-17:02 | -7.4 | -8.6 | 0.302043E+09 | 406.70 | 19-JAN-14:39 | -23.0 | -23.3 |
February | 52855629.95 | 1578.41 | 24-FEB-16:20 | 7.93 | 5.63 | 0.274923E+09 | 406.82 | 24-FEB-14:00 | 7.93 | 5.63 |
March | 0.541666E+09 | 2048.94 | 28-MAR-15:30 | 16.40 | 10.50 | 0.337002E+09 | 474.53 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.162498E+10 | 5937.82 | 18-APR-15:00 | 28.30 | 20.65 | 0.320544E+09 | 549.48 | 18-APR-09:39 | 28.30 | 20.65 |
May | 0.365661E+10 | 6525.37 | 31-MAY-15:00 | 30.00 | 19.70 | 0.402392E+09 | 549.50 | 08-MAY-13:00 | 30.00 | 19.70 |
June | 0.545597E+10 | 10456.19 | 25-JUN-18:02 | 30.82 | 21.76 | 0.422529E+09 | 549.50 | 01-JUN-09:00 | 30.82 | 21.76 |
July | 0.572083E+10 | 7011.75 | 03-JUL-15:00 | 30.00 | 24.25 | 0.401719E+09 | 549.50 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.541513E+10 | 7260.79 | 04-AUG-15:30 | 33.90 | 25.83 | 0.445739E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.337403E+10 | 6418.91 | 11-SEP-14:00 | 28.90 | 20.23 | 0.363172E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.127018E+10 | 2274.61 | 20-OCT-13:40 | 22.33 | 12.89 | 0.321622E+09 | 507.17 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.541936E+09 | 2064.31 | 03-NOV-15:40 | 15.37 | 9.43 | 0.307293E+09 | 481.36 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 13003559.67 | 1431.67 | 30-DEC-17:02 | -1.1 | -1.6 | 0.292837E+09 | 406.71 | 08-DEC-14:00 | -1.1 | -1.6 |
Annual Sum or Average | 0.276856E+11 | 0.419181E+10 | ||||||||
Minimum of Months | 13003559.67 | 1421.27 | -7.4 | -8.6 | 0.274923E+09 | 406.70 | -23.0 | -23.3 | ||
Maximum of Months | 0.572083E+10 | 10456.19 | 33.90 | 25.83 | 0.445739E+09 | 549.51 | 30.82 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47423961.45 | 1482.27 | 14-JAN-17:02 | -7.4 | -8.6 | 0.192649E+09 | 257.46 | 23-JAN-14:30 | -14.2 | -14.6 |
February | 0.169705E+09 | 2043.27 | 24-FEB-10:20 | 4.80 | 1.70 | 0.175681E+09 | 297.25 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.849796E+09 | 2497.11 | 28-MAR-09:50 | 9.53 | 5.99 | 0.217467E+09 | 343.50 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.191611E+10 | 7767.95 | 18-APR-09:30 | 24.20 | 19.59 | 0.208495E+09 | 347.89 | 18-APR-09:09 | 24.20 | 19.59 |
May | 0.399320E+10 | 8716.72 | 31-MAY-09:10 | 26.28 | 19.65 | 0.257937E+09 | 348.28 | 31-MAY-09:50 | 27.02 | 19.46 |
June | 0.557969E+10 | 14364.53 | 25-JUN-09:22 | 26.95 | 21.50 | 0.265389E+09 | 348.42 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.591934E+10 | 14405.66 | 02-JUL-08:52 | 25.60 | 21.00 | 0.253449E+09 | 348.53 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.546319E+10 | 8770.24 | 02-AUG-09:10 | 24.18 | 20.22 | 0.282337E+09 | 348.38 | 02-AUG-09:50 | 25.32 | 20.85 |
September | 0.373408E+10 | 12569.42 | 04-SEP-09:42 | 17.93 | 12.91 | 0.233303E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.146457E+10 | 2845.41 | 20-OCT-09:50 | 14.70 | 9.97 | 0.204912E+09 | 347.87 | 20-OCT-09:30 | 14.70 | 9.97 |
November | 0.511526E+09 | 2031.23 | 03-NOV-14:30 | 16.10 | 10.04 | 0.193049E+09 | 294.39 | 03-NOV-13:00 | 16.10 | 10.04 |
December | 29063970.73 | 1489.67 | 30-DEC-17:02 | -1.1 | -1.6 | 0.185960E+09 | 257.47 | 08-DEC-14:00 | -1.1 | -1.6 |
Annual Sum or Average | 0.296777E+11 | 0.267063E+10 | ||||||||
Minimum of Months | 29063970.73 | 1482.27 | -7.4 | -8.6 | 0.175681E+09 | 257.46 | -14.2 | -14.6 | ||
Maximum of Months | 0.591934E+10 | 14405.66 | 26.95 | 21.50 | 0.282337E+09 | 348.53 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748566E+09 | 4561.27 | 12-JAN-12:40 | 2.03 | 0.42 | 0.317775E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.107567E+10 | 8064.94 | 24-FEB-13:50 | 7.62 | 4.99 | 0.292977E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.191668E+10 | 8263.39 | 24-MAR-13:40 | 12.93 | 6.50 | 0.363162E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.323841E+10 | 14947.34 | 16-APR-12:02 | 25.28 | 19.72 | 0.337820E+09 | 549.92 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.517818E+10 | 10468.02 | 30-MAY-13:30 | 26.70 | 19.86 | 0.401886E+09 | 549.51 | 22-MAY-13:00 | 26.70 | 19.86 |
June | 0.686868E+10 | 16076.91 | 25-JUN-15:22 | 32.20 | 22.28 | 0.416576E+09 | 550.07 | 26-JUN-13:50 | 31.60 | 21.99 |
July | 0.750964E+10 | 17139.08 | 30-JUL-13:22 | 26.95 | 19.99 | 0.397831E+09 | 549.98 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.798836E+10 | 13115.12 | 29-AUG-13:30 | 23.60 | 16.39 | 0.442976E+09 | 550.00 | 11-AUG-13:30 | 23.60 | 16.39 |
September | 0.636868E+10 | 19409.11 | 17-SEP-13:22 | 26.40 | 17.95 | 0.370881E+09 | 555.17 | 07-SEP-13:39 | 26.40 | 17.95 |
October | 0.332201E+10 | 11415.49 | 20-OCT-13:30 | 22.20 | 12.82 | 0.357732E+09 | 549.49 | 19-OCT-13:00 | 22.20 | 12.82 |
November | 0.143566E+10 | 10210.62 | 03-NOV-13:30 | 15.85 | 10.76 | 0.317670E+09 | 549.48 | 03-NOV-13:09 | 15.85 | 10.76 |
December | 0.822505E+09 | 5877.08 | 01-DEC-13:30 | -0.9 | -3.3 | 0.310695E+09 | 549.49 | 05-DEC-14:00 | -3.9 | -7.4 |
Annual Sum or Average | 0.464731E+11 | 0.432798E+10 | ||||||||
Minimum of Months | 0.748566E+09 | 4561.27 | -0.9 | -3.3 | 0.292977E+09 | 549.48 | -3.9 | -7.4 | ||
Maximum of Months | 0.798836E+10 | 19409.11 | 32.20 | 22.28 | 0.442976E+09 | 555.17 | 31.60 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83853864.36 | 2038.51 | 12-JAN-15:50 | 2.80 | 1.13 | 0.192767E+09 | 269.95 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.239451E+09 | 2781.33 | 24-FEB-16:40 | 7.57 | 5.38 | 0.176567E+09 | 335.47 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.808967E+09 | 2918.00 | 23-MAR-16:00 | 17.20 | 10.15 | 0.215503E+09 | 335.93 | 22-MAR-15:00 | 17.20 | 10.15 |
April | 0.216015E+10 | 13964.27 | 16-APR-16:02 | 28.80 | 20.54 | 0.203599E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.403784E+10 | 12256.26 | 14-MAY-16:22 | 21.70 | 15.50 | 0.240793E+09 | 347.85 | 22-MAY-13:00 | 18.90 | 11.36 |
June | 0.554201E+10 | 16879.59 | 25-JUN-17:21 | 31.40 | 21.75 | 0.257055E+09 | 347.85 | 16-JUN-13:50 | 31.40 | 21.75 |
July | 0.597731E+10 | 16641.77 | 02-JUL-16:52 | 28.90 | 21.17 | 0.246560E+09 | 347.85 | 21-JUL-13:00 | 22.80 | 17.33 |
August | 0.572830E+10 | 12946.91 | 13-AUG-16:22 | 25.30 | 20.50 | 0.272483E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.379870E+10 | 16597.96 | 04-SEP-17:02 | 21.93 | 14.35 | 0.219972E+09 | 347.85 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.151351E+10 | 5439.12 | 20-OCT-15:30 | 22.30 | 13.06 | 0.205608E+09 | 338.68 | 20-OCT-15:39 | 21.97 | 12.95 |
November | 0.560481E+09 | 3443.34 | 03-NOV-15:30 | 15.55 | 9.47 | 0.192959E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.123341E+09 | 2023.29 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186041E+09 | 268.98 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.305739E+11 | 0.260991E+10 | ||||||||
Minimum of Months | 83853864.36 | 2023.29 | -1.5 | -3.9 | 0.176567E+09 | 268.98 | -1.6 | -4.0 | ||
Maximum of Months | 0.597731E+10 | 16879.59 | 31.40 | 21.75 | 0.272483E+09 | 347.86 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15906020.01 | 1063.91 | 14-JAN-17:02 | -7.4 | -8.6 | 0.300667E+09 | 406.71 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 25296374.92 | 1080.36 | 25-FEB-17:03 | 4.63 | 1.87 | 0.274287E+09 | 406.70 | 02-FEB-14:39 | 4.63 | 1.87 |
March | 0.347775E+09 | 1364.45 | 28-MAR-15:30 | 16.40 | 10.50 | 0.335814E+09 | 449.17 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.976110E+09 | 3204.35 | 18-APR-15:00 | 28.30 | 20.65 | 0.314709E+09 | 549.47 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.230557E+10 | 4150.86 | 31-MAY-15:00 | 30.00 | 19.70 | 0.397773E+09 | 549.49 | 05-MAY-13:09 | 30.00 | 19.70 |
June | 0.397470E+10 | 5651.88 | 26-JUN-14:30 | 31.40 | 21.97 | 0.426107E+09 | 549.50 | 20-JUN-13:00 | 31.40 | 21.97 |
July | 0.451942E+10 | 5845.47 | 05-JUL-06:03 | 19.60 | 18.69 | 0.403518E+09 | 549.50 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.466958E+10 | 5932.88 | 04-AUG-15:30 | 33.90 | 25.83 | 0.452278E+09 | 568.10 | 04-AUG-07:49 | 33.90 | 25.83 |
September | 0.320529E+10 | 5702.71 | 11-SEP-14:00 | 28.90 | 20.23 | 0.384223E+09 | 549.50 | 06-SEP-09:09 | 28.90 | 20.23 |
October | 0.162728E+10 | 1695.74 | 02-OCT-15:20 | 17.73 | 14.45 | 0.346751E+09 | 522.95 | 02-OCT-13:00 | 17.73 | 14.45 |
November | 0.743906E+09 | 1607.83 | 03-NOV-15:20 | 15.73 | 9.52 | 0.319462E+09 | 508.30 | 03-NOV-13:00 | 15.73 | 9.52 |
December | 13332250.27 | 1069.24 | 30-DEC-17:02 | -1.1 | -1.6 | 0.293546E+09 | 406.70 | 11-DEC-14:30 | -1.1 | -1.6 |
Annual Sum or Average | 0.224242E+11 | 0.424914E+10 | ||||||||
Minimum of Months | 13332250.27 | 1063.91 | -7.4 | -8.6 | 0.274287E+09 | 406.70 | -17.2 | -17.5 | ||
Maximum of Months | 0.466958E+10 | 5932.88 | 33.90 | 25.83 | 0.452278E+09 | 568.10 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45387402.35 | 1229.19 | 14-JAN-17:02 | -7.4 | -8.6 | 0.192891E+09 | 257.47 | 30-JAN-14:30 | -24.1 | -24.5 |
February | 0.113222E+09 | 1529.10 | 24-FEB-10:20 | 4.80 | 1.70 | 0.175821E+09 | 281.58 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.653779E+09 | 1820.24 | 28-MAR-10:00 | 10.00 | 6.30 | 0.216039E+09 | 316.66 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.137891E+10 | 5053.29 | 18-APR-09:40 | 24.67 | 19.90 | 0.204838E+09 | 347.87 | 18-APR-09:09 | 24.67 | 19.90 |
May | 0.288552E+10 | 6117.79 | 31-MAY-09:30 | 26.65 | 19.56 | 0.256340E+09 | 347.88 | 04-MAY-09:00 | 26.65 | 19.56 |
June | 0.452775E+10 | 8611.49 | 25-JUN-10:02 | 28.07 | 21.86 | 0.267284E+09 | 348.11 | 26-JUN-09:50 | 28.12 | 22.45 |
July | 0.505831E+10 | 12289.75 | 02-JUL-09:21 | 26.15 | 21.26 | 0.255076E+09 | 348.27 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.498731E+10 | 8133.26 | 20-AUG-09:02 | 20.97 | 18.46 | 0.285699E+09 | 367.95 | 04-AUG-07:49 | 20.97 | 18.46 |
September | 0.374221E+10 | 10484.65 | 04-SEP-09:42 | 17.93 | 12.91 | 0.243219E+09 | 347.88 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.188689E+10 | 2385.05 | 20-OCT-10:00 | 15.20 | 10.20 | 0.219919E+09 | 347.88 | 20-OCT-09:09 | 15.20 | 10.20 |
November | 0.757555E+09 | 1765.92 | 03-NOV-10:50 | 14.13 | 11.31 | 0.198017E+09 | 304.25 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 53925378.23 | 1233.25 | 02-DEC-17:03 | 1.70 | 0.90 | 0.186545E+09 | 257.48 | 11-DEC-14:30 | -19.4 | -20.0 |
Annual Sum or Average | 0.260908E+11 | 0.270169E+10 | ||||||||
Minimum of Months | 45387402.35 | 1229.19 | -7.4 | -8.6 | 0.175821E+09 | 257.47 | -24.1 | -24.5 | ||
Maximum of Months | 0.505831E+10 | 12289.75 | 28.07 | 21.86 | 0.285699E+09 | 367.95 | 28.12 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78401207.87 | 1728.94 | 13-JAN-14:30 | 3.90 | 1.72 | 0.249754E+09 | 424.92 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.171102E+09 | 2148.82 | 24-FEB-14:50 | 8.22 | 5.55 | 0.245609E+09 | 490.34 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.524360E+09 | 2642.29 | 24-MAR-14:00 | 13.30 | 6.51 | 0.321353E+09 | 549.30 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.135841E+10 | 10777.98 | 18-APR-12:00 | 27.80 | 20.94 | 0.308459E+09 | 549.50 | 19-APR-13:00 | 10.60 | 7.03 |
May | 0.290917E+10 | 11447.44 | 31-MAY-12:00 | 29.40 | 19.85 | 0.371356E+09 | 549.50 | 22-MAY-13:00 | 29.40 | 19.85 |
June | 0.507235E+10 | 12222.25 | 26-JUN-12:00 | 30.60 | 21.63 | 0.405627E+09 | 584.21 | 26-JUN-12:09 | 30.68 | 21.60 |
July | 0.615833E+10 | 13820.21 | 02-JUL-14:42 | 29.32 | 21.64 | 0.395767E+09 | 549.66 | 05-JUL-13:30 | 26.95 | 20.16 |
August | 0.714040E+10 | 12817.24 | 04-AUG-16:10 | 33.15 | 26.05 | 0.445411E+09 | 601.42 | 04-AUG-12:09 | 33.15 | 26.05 |
September | 0.558869E+10 | 14942.23 | 04-SEP-13:42 | 21.60 | 14.14 | 0.370400E+09 | 627.17 | 07-SEP-12:09 | 30.78 | 18.58 |
October | 0.228034E+10 | 8644.88 | 20-OCT-14:00 | 22.60 | 13.03 | 0.346347E+09 | 549.50 | 19-OCT-13:00 | 22.60 | 13.03 |
November | 0.884007E+09 | 7005.73 | 04-NOV-13:30 | 14.15 | 6.81 | 0.298610E+09 | 549.49 | 03-NOV-13:09 | 14.15 | 6.81 |
December | 0.204355E+09 | 2090.14 | 02-DEC-12:40 | 5.40 | 2.84 | 0.261256E+09 | 433.99 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.323699E+11 | 0.401995E+10 | ||||||||
Minimum of Months | 78401207.87 | 1728.94 | 3.90 | 1.72 | 0.245609E+09 | 424.92 | 3.90 | 1.72 | ||
Maximum of Months | 0.714040E+10 | 14942.23 | 33.15 | 26.05 | 0.445411E+09 | 627.17 | 33.15 | 26.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55253885.29 | 1577.46 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192959E+09 | 266.70 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.153512E+09 | 2030.53 | 24-FEB-16:40 | 7.57 | 5.38 | 0.176403E+09 | 316.54 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.599963E+09 | 1997.44 | 23-MAR-16:50 | 16.28 | 9.98 | 0.213752E+09 | 308.00 | 23-MAR-15:00 | 16.28 | 9.98 |
April | 0.155527E+10 | 7207.55 | 16-APR-17:32 | 27.23 | 20.00 | 0.201606E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.282586E+10 | 7093.81 | 21-MAY-18:03 | 16.93 | 9.12 | 0.240438E+09 | 347.85 | 31-MAY-13:09 | 29.90 | 19.66 |
June | 0.439217E+10 | 12704.16 | 25-JUN-17:21 | 31.40 | 21.75 | 0.261523E+09 | 347.86 | 20-JUN-13:00 | 31.40 | 21.75 |
July | 0.501412E+10 | 13730.32 | 02-JUL-18:01 | 28.12 | 21.02 | 0.253102E+09 | 347.85 | 31-JUL-09:39 | 20.40 | 18.47 |
August | 0.508672E+10 | 9175.04 | 05-AUG-17:05 | 25.32 | 17.94 | 0.283598E+09 | 347.85 | 30-AUG-13:39 | 23.33 | 17.60 |
September | 0.370345E+10 | 12969.98 | 04-SEP-17:02 | 21.93 | 14.35 | 0.235015E+09 | 347.85 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.199100E+10 | 4387.17 | 11-OCT-16:00 | 17.80 | 11.96 | 0.215103E+09 | 338.68 | 20-OCT-15:39 | 21.97 | 12.95 |
November | 0.826377E+09 | 2795.87 | 03-NOV-15:40 | 15.37 | 9.43 | 0.197824E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.122041E+09 | 1652.65 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186729E+09 | 275.19 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.263257E+11 | 0.265805E+10 | ||||||||
Minimum of Months | 55253885.29 | 1577.46 | -1.5 | -3.9 | 0.176403E+09 | 266.70 | -1.6 | -4.0 | ||
Maximum of Months | 0.508672E+10 | 13730.32 | 31.40 | 21.75 | 0.283598E+09 | 347.86 | 31.40 | 21.75 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34361922.52 | 1155.12 | 14-JAN-17:02 | -7.4 | -8.6 | 0.302807E+09 | 406.70 | 02-JAN-10:00 | -7.4 | -8.6 |
February | 86666963.84 | 1341.83 | 24-FEB-16:30 | 7.75 | 5.51 | 0.276215E+09 | 422.22 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.725663E+09 | 1720.25 | 24-MAR-15:30 | 11.70 | 6.01 | 0.343597E+09 | 498.56 | 24-MAR-13:00 | 11.70 | 6.01 |
April | 0.173572E+10 | 5483.61 | 18-APR-15:00 | 28.30 | 20.65 | 0.333627E+09 | 549.48 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.343783E+10 | 5907.94 | 31-MAY-15:00 | 30.00 | 19.70 | 0.418949E+09 | 549.51 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.519712E+10 | 10493.98 | 25-JUN-19:12 | 28.87 | 21.34 | 0.430146E+09 | 549.82 | 27-JUN-13:20 | 29.60 | 22.39 |
July | 0.549455E+10 | 9750.10 | 02-JUL-18:01 | 28.12 | 21.02 | 0.404430E+09 | 549.80 | 03-JUL-13:00 | 29.40 | 24.07 |
August | 0.526119E+10 | 6570.29 | 04-AUG-15:30 | 33.90 | 25.83 | 0.452210E+09 | 553.14 | 04-AUG-07:30 | 33.90 | 25.83 |
September | 0.339567E+10 | 6175.61 | 11-SEP-14:00 | 28.90 | 20.23 | 0.381026E+09 | 549.50 | 06-SEP-09:09 | 28.90 | 20.23 |
October | 0.160893E+10 | 2091.38 | 20-OCT-13:30 | 22.20 | 12.82 | 0.342271E+09 | 532.15 | 02-OCT-13:00 | 22.20 | 12.82 |
November | 0.725492E+09 | 1861.29 | 03-NOV-13:30 | 15.85 | 10.76 | 0.317522E+09 | 507.63 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 14443409.16 | 1159.85 | 30-DEC-17:02 | -1.1 | -1.6 | 0.293546E+09 | 406.70 | 11-DEC-14:30 | -1.1 | -1.6 |
Annual Sum or Average | 0.277176E+11 | 0.429635E+10 | ||||||||
Minimum of Months | 14443409.16 | 1155.12 | -7.4 | -8.6 | 0.276215E+09 | 406.70 | -7.4 | -8.6 | ||
Maximum of Months | 0.549455E+10 | 10493.98 | 33.90 | 25.83 | 0.452210E+09 | 553.14 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67284040.34 | 1589.13 | 12-JAN-10:00 | -2.8 | -3.3 | 0.141707E+09 | 250.68 | 18-JAN-08:09 | -12.3 | -12.7 |
February | 0.228362E+09 | 2163.44 | 24-FEB-10:00 | 4.40 | 1.36 | 0.129607E+09 | 306.02 | 24-FEB-09:00 | 4.40 | 1.36 |
March | 0.106311E+10 | 2945.32 | 28-MAR-09:00 | 7.20 | 4.38 | 0.161461E+09 | 338.72 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.215170E+10 | 7722.18 | 18-APR-09:00 | 22.80 | 18.62 | 0.155373E+09 | 338.72 | 18-APR-07:19 | 22.80 | 18.62 |
May | 0.404994E+10 | 10875.86 | 21-MAY-09:12 | 13.87 | 8.48 | 0.192277E+09 | 338.90 | 31-MAY-08:00 | 26.10 | 19.69 |
June | 0.545052E+10 | 15450.12 | 25-JUN-09:11 | 26.67 | 21.38 | 0.196921E+09 | 338.98 | 26-JUN-08:00 | 27.20 | 22.45 |
July | 0.578546E+10 | 15515.15 | 02-JUL-08:41 | 25.32 | 20.92 | 0.188072E+09 | 339.23 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.537874E+10 | 14104.87 | 20-AUG-09:02 | 20.97 | 18.46 | 0.208942E+09 | 349.15 | 04-AUG-07:30 | 20.97 | 18.46 |
September | 0.393614E+10 | 8480.31 | 04-SEP-09:13 | 16.83 | 13.06 | 0.175063E+09 | 338.74 | 05-SEP-07:40 | 13.93 | 11.92 |
October | 0.189257E+10 | 3485.76 | 20-OCT-08:55 | 12.20 | 8.72 | 0.155691E+09 | 338.72 | 20-OCT-10:09 | 15.68 | 10.42 |
November | 0.728114E+09 | 2194.31 | 04-NOV-09:25 | 7.50 | 4.04 | 0.143823E+09 | 300.43 | 03-NOV-10:50 | 7.50 | 4.04 |
December | 63550227.22 | 1476.56 | 30-DEC-17:02 | -1.1 | -1.6 | 0.137070E+09 | 250.68 | 11-DEC-16:00 | -1.1 | -1.6 |
Annual Sum or Average | 0.307955E+11 | 0.198601E+10 | ||||||||
Minimum of Months | 63550227.22 | 1476.56 | -2.8 | -3.3 | 0.129607E+09 | 250.68 | -12.3 | -12.7 | ||
Maximum of Months | 0.578546E+10 | 15515.15 | 26.67 | 21.38 | 0.208942E+09 | 349.15 | 27.20 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.892817E+09 | 5260.48 | 12-JAN-12:30 | 1.95 | 0.38 | 0.323100E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.122836E+10 | 8171.59 | 24-FEB-13:40 | 7.43 | 4.81 | 0.299440E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.225226E+10 | 8318.74 | 24-MAR-13:10 | 12.38 | 6.48 | 0.371557E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.351387E+10 | 13651.59 | 16-APR-11:43 | 24.82 | 19.57 | 0.345785E+09 | 550.14 | 06-APR-13:09 | 24.82 | 19.57 |
May | 0.511176E+10 | 9729.51 | 30-MAY-13:30 | 26.70 | 19.86 | 0.414466E+09 | 550.02 | 30-MAY-13:50 | 26.70 | 19.86 |
June | 0.661409E+10 | 15940.24 | 11-JUN-14:42 | 33.03 | 24.69 | 0.424323E+09 | 549.98 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.725159E+10 | 16685.39 | 30-JUL-12:32 | 26.70 | 20.87 | 0.402072E+09 | 549.96 | 05-JUL-13:50 | 26.70 | 20.87 |
August | 0.780807E+10 | 16440.20 | 13-AUG-13:32 | 25.73 | 19.92 | 0.449439E+09 | 550.20 | 21-AUG-13:50 | 29.32 | 21.76 |
September | 0.655892E+10 | 16334.02 | 04-SEP-13:12 | 21.30 | 14.06 | 0.383167E+09 | 562.69 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.395291E+10 | 11361.60 | 20-OCT-13:10 | 21.93 | 12.68 | 0.372031E+09 | 549.54 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.178593E+10 | 10307.64 | 03-NOV-13:30 | 15.85 | 10.76 | 0.329475E+09 | 549.53 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.974203E+09 | 6388.61 | 01-DEC-13:30 | -0.9 | -3.3 | 0.315802E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.479448E+11 | 0.443066E+10 | ||||||||
Minimum of Months | 0.892817E+09 | 5260.48 | -0.9 | -3.3 | 0.299440E+09 | 549.49 | 1.70 | 0.50 | ||
Maximum of Months | 0.780807E+10 | 16685.39 | 33.03 | 24.69 | 0.449439E+09 | 562.69 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115869E+09 | 1990.95 | 12-JAN-15:50 | 2.80 | 1.13 | 0.193127E+09 | 280.36 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.302110E+09 | 2789.09 | 24-FEB-16:30 | 7.75 | 5.51 | 0.177379E+09 | 338.68 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.102731E+10 | 3087.68 | 23-MAR-16:00 | 17.20 | 10.15 | 0.217590E+09 | 338.68 | 22-MAR-15:00 | 17.20 | 10.15 |
April | 0.238500E+10 | 12965.24 | 16-APR-16:22 | 28.60 | 20.44 | 0.206936E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.401313E+10 | 11492.95 | 14-MAY-16:22 | 21.70 | 15.50 | 0.248631E+09 | 347.86 | 08-MAY-13:00 | 21.70 | 15.50 |
June | 0.536169E+10 | 15865.97 | 25-JUN-17:11 | 31.50 | 21.73 | 0.262599E+09 | 347.86 | 20-JUN-13:00 | 31.50 | 21.73 |
July | 0.576235E+10 | 16241.62 | 02-JUL-18:01 | 28.12 | 21.02 | 0.250757E+09 | 347.85 | 21-JUL-13:50 | 22.70 | 17.25 |
August | 0.557303E+10 | 15368.78 | 13-AUG-16:52 | 25.00 | 20.46 | 0.278703E+09 | 347.86 | 30-AUG-13:50 | 23.62 | 17.87 |
September | 0.395372E+10 | 11847.51 | 04-SEP-17:12 | 21.67 | 14.30 | 0.227914E+09 | 347.84 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.199182E+10 | 5343.06 | 20-OCT-15:30 | 22.30 | 13.06 | 0.211298E+09 | 342.58 | 11-OCT-13:00 | 22.30 | 13.06 |
November | 0.826729E+09 | 3562.42 | 03-NOV-15:30 | 15.55 | 9.47 | 0.195788E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.173071E+09 | 1994.19 | 01-DEC-15:40 | -1.5 | -3.9 | 0.186697E+09 | 281.09 | 01-DEC-15:50 | -1.6 | -4.0 |
Annual Sum or Average | 0.314858E+11 | 0.265742E+10 | ||||||||
Minimum of Months | 0.115869E+09 | 1990.95 | -1.5 | -3.9 | 0.177379E+09 | 280.36 | -1.6 | -4.0 | ||
Maximum of Months | 0.576235E+10 | 16241.62 | 31.50 | 21.73 | 0.278703E+09 | 347.86 | 31.50 | 21.73 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421311E+09 | 26634.91 | 02-JAN-05:01 | -4.5 |
February | 62103086.70 | 23751.33 | 06-FEB-06:01 | -15.0 |
March | 4987726.86 | 21343.93 | 06-MAR-07:01 | -12.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 21860149.93 | 22896.34 | 27-NOV-06:01 | -9.4 |
December | 60368168.47 | 23079.67 | 11-DEC-06:01 | -22.1 |
Annual Sum or Average | 0.570630E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 0.421311E+09 | 26634.91 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140920E+11 | 20423.45 | 19-JAN-06:12 | -27.8 |
February | 0.922120E+10 | 21696.53 | 02-FEB-06:06 | -36.7 |
March | 0.497471E+10 | 18094.91 | 06-MAR-06:13 | -13.9 |
April | 0.209536E+10 | 14511.97 | 03-APR-05:13 | -7.2 |
May | 0.347505E+09 | 7164.21 | 30-MAY-05:03 | 14.50 |
June | 0.148667E+09 | 8608.72 | 19-JUN-05:03 | 11.78 |
July | 62700019.16 | 7211.09 | 31-JUL-05:03 | 16.88 |
August | 0.112395E+09 | 5809.98 | 14-AUG-05:03 | 15.68 |
September | 0.627373E+09 | 6617.89 | 29-SEP-05:04 | 0.92 |
October | 0.181210E+10 | 8647.94 | 23-OCT-06:01 | -3.0 |
November | 0.629639E+10 | 17707.47 | 28-NOV-06:12 | -18.1 |
December | 0.112450E+11 | 20043.96 | 09-DEC-06:11 | -22.8 |
Annual Sum or Average | 0.510355E+11 | |||
Minimum of Months | 62700019.16 | 5809.98 | -36.7 | |
Maximum of Months | 0.140920E+11 | 21696.53 | 16.88 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.600379E+10 | 11467.39 | 30-JAN-07:04 | -29.0 |
February | 0.374900E+10 | 10793.28 | 06-FEB-07:05 | -15.0 |
March | 0.234573E+10 | 8908.54 | 06-MAR-06:13 | -13.9 |
April | 0.825735E+09 | 7339.44 | 03-APR-06:11 | -7.0 |
May | 99640631.76 | 3563.92 | 21-MAY-09:12 | 13.87 |
June | 25588737.45 | 3289.12 | 11-JUN-14:42 | 33.03 |
July | 30680416.66 | 2945.40 | 30-JUL-15:51 | 27.80 |
August | 22475555.71 | 3570.47 | 13-AUG-15:32 | 25.77 |
September | 0.124181E+09 | 3362.06 | 04-SEP-15:53 | 22.20 |
October | 0.828112E+09 | 4998.84 | 01-OCT-11:43 | 18.02 |
November | 0.258759E+10 | 10662.36 | 27-NOV-07:05 | -9.4 |
December | 0.465126E+10 | 11452.15 | 11-DEC-07:03 | -21.7 |
Annual Sum or Average | 0.212938E+11 | |||
Minimum of Months | 22475555.71 | 2945.40 | -29.0 | |
Maximum of Months | 0.600379E+10 | 11467.39 | 33.03 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440020E+10 | 9791.79 | 02-JAN-06:12 | -5.2 |
February | 0.267233E+10 | 7338.06 | 06-FEB-06:03 | -15.0 |
March | 0.161569E+10 | 5284.97 | 06-MAR-09:40 | -7.8 |
April | 0.502117E+09 | 5292.03 | 20-APR-05:03 | 2.62 |
May | 35936587.80 | 5235.60 | 08-MAY-05:03 | 12.02 |
June | 22471049.30 | 5612.59 | 02-JUN-05:03 | 7.20 |
July | 28006865.20 | 4414.11 | 11-JUL-04:03 | 12.98 |
August | 34541576.23 | 4771.75 | 08-AUG-04:03 | 11.20 |
September | 50879814.85 | 6604.48 | 25-SEP-05:02 | 2.80 |
October | 0.304200E+09 | 4046.46 | 27-OCT-07:06 | 1.73 |
November | 0.171966E+10 | 7064.02 | 27-NOV-07:01 | -9.4 |
December | 0.330757E+10 | 7342.74 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.146936E+11 | |||
Minimum of Months | 22471049.30 | 4046.46 | -21.7 | |
Maximum of Months | 0.440020E+10 | 9791.79 | 12.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221164E+10 | 29513.62 | 02-JAN-05:01 | -4.5 |
February | 0.906144E+09 | 28400.13 | 06-FEB-05:01 | -14.5 |
March | 0.224511E+09 | 26773.36 | 06-MAR-06:01 | -14.1 |
April | 59033317.01 | 26057.83 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1403265.68 | 23387.76 | 16-OCT-06:01 | -0.4 |
November | 0.515617E+09 | 28418.06 | 27-NOV-05:01 | -9.4 |
December | 0.110445E+10 | 28770.20 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.502280E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.221164E+10 | 29513.62 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650828E+10 | 33699.14 | 17-JAN-05:11 | -6.9 |
February | 0.362601E+10 | 33491.86 | 06-FEB-05:01 | -14.5 |
March | 0.138168E+10 | 33459.61 | 06-MAR-05:01 | -15.4 |
April | 0.340612E+09 | 32293.70 | 03-APR-04:11 | -6.9 |
May | 1425499.49 | 21382.49 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8049013.99 | 26974.03 | 29-SEP-06:01 | 0.10 |
October | 0.137170E+09 | 29238.64 | 16-OCT-05:01 | 0.48 |
November | 0.216722E+10 | 33481.78 | 27-NOV-05:01 | -9.4 |
December | 0.445487E+10 | 33620.95 | 26-DEC-05:11 | -4.5 |
Annual Sum or Average | 0.186253E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.4 | |
Maximum of Months | 0.650828E+10 | 33699.14 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117087E+11 | 13207.24 | 30-JAN-06:01 | -28.4 |
February | 0.724702E+10 | 12634.40 | 04-FEB-05:11 | -30.6 |
March | 0.346598E+10 | 12533.01 | 06-MAR-03:42 | -16.2 |
April | 0.100590E+10 | 11972.50 | 03-APR-02:13 | -6.1 |
May | 30816244.44 | 9999.71 | 02-MAY-05:02 | 2.20 |
June | 3637192.77 | 7095.69 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.115831E+09 | 10230.91 | 30-SEP-05:01 | 0.10 |
October | 0.710375E+09 | 10834.02 | 16-OCT-04:02 | 1.78 |
November | 0.445679E+10 | 12832.61 | 26-NOV-04:01 | -25.0 |
December | 0.882531E+10 | 12744.09 | 09-DEC-00:11 | -22.8 |
Annual Sum or Average | 0.375704E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.117087E+11 | 13207.24 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.710209E+10 | 13336.14 | 30-JAN-06:01 | -28.4 |
February | 0.412219E+10 | 13224.73 | 04-FEB-05:11 | -30.6 |
March | 0.185195E+10 | 12994.21 | 06-MAR-03:42 | -16.2 |
April | 0.555372E+09 | 12391.66 | 03-APR-04:11 | -6.9 |
May | 9912985.42 | 10359.32 | 02-MAY-05:02 | 2.20 |
June | 2825826.55 | 4789.69 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 57371408.33 | 10615.29 | 30-SEP-05:01 | 0.10 |
October | 0.368260E+09 | 10875.83 | 26-OCT-05:01 | -0.8 |
November | 0.269999E+10 | 13346.82 | 26-NOV-04:01 | -25.0 |
December | 0.540732E+10 | 13306.48 | 09-DEC-00:11 | -22.8 |
Annual Sum or Average | 0.221773E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.710209E+10 | 13346.82 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839221E+10 | 16670.39 | 30-JAN-06:01 | -28.4 |
February | 0.479528E+10 | 16497.37 | 04-FEB-05:11 | -30.6 |
March | 0.254109E+10 | 16226.04 | 06-MAR-03:42 | -16.2 |
April | 0.838736E+09 | 15520.56 | 03-APR-04:11 | -6.9 |
May | 33818697.60 | 12952.79 | 02-MAY-05:02 | 2.20 |
June | 5117139.52 | 7834.85 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 86993376.45 | 13357.54 | 30-SEP-05:01 | 0.10 |
October | 0.458046E+09 | 13545.02 | 26-OCT-05:01 | -0.8 |
November | 0.326041E+10 | 16668.55 | 26-NOV-04:01 | -25.0 |
December | 0.673018E+10 | 16586.19 | 09-DEC-00:11 | -22.8 |
Annual Sum or Average | 0.271419E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.839221E+10 | 16670.39 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.729365E+10 | 14728.04 | 30-JAN-06:01 | -28.4 |
February | 0.432319E+10 | 14599.31 | 04-FEB-05:11 | -30.6 |
March | 0.205639E+10 | 14270.68 | 06-MAR-03:42 | -16.2 |
April | 0.589067E+09 | 13682.77 | 03-APR-04:11 | -6.9 |
May | 26311278.60 | 11428.36 | 02-MAY-05:02 | 2.20 |
June | 3418981.00 | 4947.67 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 81292033.00 | 11703.59 | 30-SEP-05:01 | 0.10 |
October | 0.424194E+09 | 11972.40 | 26-OCT-05:01 | -0.8 |
November | 0.278097E+10 | 14721.73 | 26-NOV-04:01 | -25.0 |
December | 0.554793E+10 | 14711.69 | 09-DEC-00:11 | -22.8 |
Annual Sum or Average | 0.231264E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.729365E+10 | 14728.04 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789344E+10 | 9231.12 | 30-JAN-05:11 | -28.0 |
February | 0.500550E+10 | 8770.96 | 02-FEB-04:01 | -35.2 |
March | 0.248180E+10 | 8669.11 | 06-MAR-05:11 | -15.2 |
April | 0.732079E+09 | 8389.87 | 03-APR-04:01 | -6.8 |
May | 14194696.13 | 7023.40 | 02-MAY-05:02 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3804127.27 | 6752.65 | 29-SEP-06:01 | 0.10 |
October | 49238413.56 | 6865.86 | 16-OCT-06:01 | -0.4 |
November | 0.191318E+10 | 8499.67 | 27-NOV-00:52 | -11.7 |
December | 0.494916E+10 | 8875.21 | 11-DEC-02:23 | -21.7 |
Annual Sum or Average | 0.230424E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.789344E+10 | 9231.12 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471898E+10 | 10656.28 | 30-JAN-05:11 | -28.0 |
February | 0.269247E+10 | 10092.11 | 02-FEB-04:01 | -35.2 |
March | 0.118162E+10 | 9985.13 | 06-MAR-05:11 | -15.2 |
April | 0.341457E+09 | 9683.04 | 03-APR-04:01 | -6.8 |
May | 946792.73 | 7865.01 | 02-MAY-06:01 | 2.30 |
June | 111198.37 | 555.99 | 06-JUN-06:03 | 11.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2866154.40 | 7894.77 | 29-SEP-06:01 | 0.10 |
October | 23308686.13 | 7915.07 | 16-OCT-06:01 | -0.4 |
November | 0.109847E+10 | 9670.70 | 27-NOV-05:01 | -9.4 |
December | 0.296034E+10 | 10094.11 | 11-DEC-02:23 | -21.7 |
Annual Sum or Average | 0.130206E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.471898E+10 | 10656.28 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127434E+11 | 20243.35 | 31-JAN-07:10 | -30.5 |
February | 0.861949E+10 | 21467.46 | 02-FEB-07:10 | -36.7 |
March | 0.668678E+10 | 15333.54 | 06-MAR-08:00 | -12.2 |
April | 0.339115E+10 | 14308.77 | 03-APR-06:50 | -6.8 |
May | 0.106254E+10 | 11803.82 | 02-MAY-06:10 | 2.30 |
June | 0.411415E+09 | 10248.71 | 02-JUN-06:10 | 7.30 |
July | 35229786.60 | 8343.72 | 24-JUL-06:07 | 12.35 |
August | 0.133291E+09 | 9606.99 | 07-AUG-06:07 | 8.87 |
September | 0.759870E+09 | 11942.03 | 29-SEP-06:10 | 0.10 |
October | 0.189368E+10 | 12516.10 | 23-OCT-06:10 | -3.0 |
November | 0.534133E+10 | 16501.37 | 28-NOV-07:10 | -17.6 |
December | 0.963516E+10 | 17761.09 | 11-DEC-07:10 | -21.7 |
Annual Sum or Average | 0.507133E+11 | |||
Minimum of Months | 35229786.60 | 8343.72 | -36.7 | |
Maximum of Months | 0.127434E+11 | 21467.46 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486160E+10 | 11427.35 | 30-JAN-05:11 | -28.0 |
February | 0.277403E+10 | 10838.16 | 02-FEB-04:01 | -35.2 |
March | 0.132131E+10 | 10682.32 | 06-MAR-05:11 | -15.2 |
April | 0.315033E+09 | 10413.93 | 03-APR-04:01 | -6.8 |
May | 7984966.14 | 8466.50 | 02-MAY-06:01 | 2.30 |
June | 763329.27 | 2175.07 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 5492381.93 | 8483.62 | 29-SEP-06:01 | 0.10 |
October | 27614658.62 | 8504.19 | 16-OCT-06:01 | -0.4 |
November | 0.114639E+10 | 10380.10 | 27-NOV-05:01 | -9.4 |
December | 0.304902E+10 | 10837.82 | 11-DEC-05:01 | -22.2 |
Annual Sum or Average | 0.135092E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.486160E+10 | 11427.35 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787144E+10 | 10084.22 | 30-JAN-01:42 | -26.6 |
February | 0.439863E+10 | 9758.77 | 06-FEB-02:22 | -17.2 |
March | 0.172309E+10 | 9410.79 | 06-MAR-04:51 | -15.6 |
April | 0.363950E+09 | 9147.55 | 03-APR-04:01 | -6.8 |
May | 3261738.48 | 7392.72 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 13924289.55 | 7583.62 | 30-SEP-05:01 | 0.10 |
October | 0.123891E+09 | 7932.08 | 16-OCT-05:01 | 0.48 |
November | 0.239182E+10 | 9588.83 | 26-NOV-01:42 | -24.4 |
December | 0.538947E+10 | 9673.98 | 10-DEC-11:22 | -15.9 |
Annual Sum or Average | 0.222795E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.6 | |
Maximum of Months | 0.787144E+10 | 10084.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472863E+10 | 12762.73 | 30-JAN-01:42 | -26.6 |
February | 0.245590E+10 | 12321.59 | 06-FEB-02:22 | -17.2 |
March | 0.922496E+09 | 11945.20 | 06-MAR-04:51 | -15.6 |
April | 0.212528E+09 | 11647.70 | 03-APR-04:01 | -6.8 |
May | 922729.20 | 9391.63 | 02-MAY-06:01 | 2.30 |
June | 113892.57 | 654.79 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 10056031.82 | 9464.22 | 29-SEP-06:01 | 0.10 |
October | 77552594.19 | 10007.65 | 16-OCT-05:01 | 0.48 |
November | 0.146648E+10 | 12090.70 | 27-NOV-05:01 | -9.4 |
December | 0.334115E+10 | 12303.58 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.132158E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.6 | |
Maximum of Months | 0.472863E+10 | 12762.73 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513260E+10 | 14889.74 | 29-JAN-05:42 | -20.9 |
February | 0.256124E+10 | 14325.29 | 06-FEB-02:22 | -17.2 |
March | 0.115698E+10 | 13883.83 | 06-MAR-04:51 | -15.6 |
April | 0.288224E+09 | 13579.12 | 03-APR-04:01 | -6.8 |
May | 3971501.14 | 11002.08 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 11870364.44 | 11047.28 | 29-SEP-06:01 | 0.10 |
October | 83896650.32 | 11613.94 | 16-OCT-05:01 | 0.48 |
November | 0.161269E+10 | 14099.89 | 26-NOV-21:03 | -12.9 |
December | 0.392318E+10 | 14272.06 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.147747E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.7 | |
Maximum of Months | 0.513260E+10 | 14889.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482011E+10 | 13296.25 | 30-JAN-01:42 | -26.6 |
February | 0.255201E+10 | 12821.53 | 02-FEB-04:01 | -35.2 |
March | 0.998433E+09 | 12099.72 | 06-MAR-05:01 | -15.4 |
April | 0.207536E+09 | 12153.19 | 03-APR-04:01 | -6.8 |
May | 4534832.63 | 9818.56 | 02-MAY-06:01 | 2.30 |
June | 451581.41 | 1511.42 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 14500568.77 | 9869.30 | 29-SEP-06:01 | 0.10 |
October | 85884421.61 | 10512.51 | 16-OCT-05:01 | 0.48 |
November | 0.149006E+10 | 12597.66 | 27-NOV-05:01 | -9.4 |
December | 0.338812E+10 | 12852.17 | 09-DEC-02:61 | -22.7 |
Annual Sum or Average | 0.135617E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.482011E+10 | 13296.25 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.208150E+11 | 18520.31 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.188385E+11 | 18520.31 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.216654E+11 | 18520.31 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.200796E+11 | 18520.31 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.212402E+11 | 18520.31 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.208620E+11 | 18520.31 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.204550E+11 | 18520.31 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.216654E+11 | 18520.31 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.200739E+11 | 18520.31 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.208179E+11 | 18520.31 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.203773E+11 | 18520.31 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.204522E+11 | 18520.31 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.247342E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.188385E+11 | 18520.31 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.216654E+11 | 18520.31 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.681718E+10 | 7133.97 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.618369E+10 | 7133.97 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.734796E+10 | 7133.97 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.656322E+10 | 7133.97 | 03-APR-07:10 | 0.102966E+11 | 7143.44 | 03-APR-07:10 |
May | 0.708257E+10 | 7133.97 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.704833E+10 | 7133.97 | 01-JUN-07:10 | 0.106494E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.659746E+10 | 7133.97 | 03-JUL-07:10 | 0.105023E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.734796E+10 | 7133.97 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.656322E+10 | 7133.97 | 01-SEP-07:10 | 0.102908E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.681718E+10 | 7133.97 | 02-OCT-07:10 | 0.106637E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.673729E+10 | 7133.97 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.659746E+10 | 7133.97 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.817035E+11 | 0.126600E+12 | ||||
Minimum of Months | 0.618369E+10 | 7133.97 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.734796E+10 | 7133.97 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107629E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.932268E+09 | 1317.74 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105558E+10 | 1139.25 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.926266E+09 | 1060.27 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.978495E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.968832E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.911524E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102007E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.935815E+09 | 1066.35 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100292E+10 | 1460.43 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.105013E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.107453E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119327E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.911524E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107629E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674740E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.586945E+09 | 844.32 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.667911E+09 | 737.25 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.587144E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.621593E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.615362E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.578498E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.647752E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.593311E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631758E+09 | 880.05 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.661904E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.671055E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.753797E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.578498E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.674740E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105351E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.918126E+09 | 1271.46 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105228E+10 | 1081.16 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.926978E+09 | 1051.21 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.981822E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.972590E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.914200E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102284E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.934903E+09 | 1039.35 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.992018E+09 | 1397.25 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103563E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.104476E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118497E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.914200E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105351E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.672988E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.584573E+09 | 789.55 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.667167E+09 | 736.97 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585782E+09 | 700.48 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.619893E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613670E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.577640E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.645945E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.591237E+09 | 709.50 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.632756E+09 | 926.61 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.658538E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.668276E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.751846E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.577640E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.672988E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107327E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.929725E+09 | 1306.36 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105463E+10 | 1123.01 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.925785E+09 | 1040.66 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.978090E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.968417E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.911280E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.101965E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.935158E+09 | 1046.81 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100104E+10 | 1458.12 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.104794E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.107019E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119152E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.911280E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107327E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.673766E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.585929E+09 | 838.73 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.667454E+09 | 729.91 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.586877E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.621288E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.615079E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.578272E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.647439E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.592958E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631125E+09 | 875.36 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.661044E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.669457E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.753069E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.578272E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.673766E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105095E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.916699E+09 | 1260.76 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105165E+10 | 1061.50 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.926501E+09 | 1031.12 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.981280E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.971993E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.913676E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102210E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.934349E+09 | 1018.34 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.991286E+09 | 1391.03 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103423E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.104281E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118375E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.913676E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105165E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.671810E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.583715E+09 | 783.37 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.666508E+09 | 726.20 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585453E+09 | 692.03 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.619592E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613409E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.577461E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.645661E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.590862E+09 | 701.32 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.632109E+09 | 925.52 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.657728E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.666757E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.751106E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.577461E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.671810E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.107629E+10 | 1503.90 | 02-JAN-16:40 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.932268E+09 | 1317.75 | 01-FEB-16:00 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.105558E+10 | 1139.23 | 01-MAR-16:00 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.926266E+09 | 1060.24 | 10-APR-07:10 | 0.217059E+10 | 1505.89 | 03-APR-07:10 |
May | 0.978495E+09 | 927.16 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.968831E+09 | 927.16 | 01-JUN-07:10 | 0.224498E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.911523E+09 | 927.16 | 03-JUL-07:10 | 0.221396E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.102007E+10 | 927.16 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.935815E+09 | 1066.33 | 21-SEP-07:10 | 0.216939E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.100292E+10 | 1460.43 | 31-OCT-07:10 | 0.224800E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.105013E+10 | 1503.90 | 06-NOV-16:00 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.107453E+10 | 1503.90 | 01-DEC-16:30 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.119327E+11 | 0.266883E+11 | ||||
Minimum of Months | 0.911523E+09 | 927.16 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.107629E+10 | 1503.90 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.674739E+09 | 952.10 | 02-JAN-16:40 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.586945E+09 | 844.32 | 01-FEB-16:00 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.667911E+09 | 737.23 | 01-MAR-16:00 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.587144E+09 | 586.97 | 03-APR-07:10 | 0.137408E+10 | 953.30 | 03-APR-07:10 |
May | 0.621593E+09 | 586.97 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.615362E+09 | 586.97 | 01-JUN-07:10 | 0.142117E+10 | 953.30 | 01-JUN-07:10 |
July | 0.578498E+09 | 586.97 | 03-JUL-07:10 | 0.140153E+10 | 953.30 | 03-JUL-07:10 |
August | 0.647752E+09 | 586.97 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.593311E+09 | 586.97 | 01-SEP-07:10 | 0.137332E+10 | 953.30 | 01-SEP-07:10 |
October | 0.631759E+09 | 880.05 | 31-OCT-07:10 | 0.142308E+10 | 953.30 | 02-OCT-07:10 |
November | 0.661904E+09 | 952.10 | 06-NOV-16:00 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.671055E+09 | 952.10 | 01-DEC-16:30 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.753797E+10 | 0.168949E+11 | ||||
Minimum of Months | 0.578498E+09 | 586.97 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.674739E+09 | 952.10 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105351E+10 | 1503.90 | 02-JAN-16:40 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.918125E+09 | 1271.44 | 14-FEB-16:00 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.105228E+10 | 1081.14 | 01-MAR-16:00 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.926978E+09 | 1051.18 | 10-APR-07:10 | 0.217058E+10 | 1505.88 | 03-APR-07:10 |
May | 0.981822E+09 | 927.16 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.972590E+09 | 927.16 | 01-JUN-07:10 | 0.224497E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.914200E+09 | 927.16 | 03-JUL-07:10 | 0.221395E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.102284E+10 | 927.16 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.934903E+09 | 1039.32 | 21-SEP-07:10 | 0.216937E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.992018E+09 | 1397.26 | 31-OCT-07:10 | 0.224798E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.103563E+10 | 1503.90 | 06-NOV-16:00 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.104476E+10 | 1503.90 | 01-DEC-16:30 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.118497E+11 | 0.266882E+11 | ||||
Minimum of Months | 0.914200E+09 | 927.16 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.105351E+10 | 1503.90 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.672988E+09 | 952.03 | 02-JAN-16:40 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.584572E+09 | 789.54 | 14-FEB-16:00 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.667167E+09 | 736.99 | 14-MAR-07:10 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.585782E+09 | 700.46 | 10-APR-07:10 | 0.137407E+10 | 953.29 | 03-APR-07:10 |
May | 0.619893E+09 | 586.93 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.613667E+09 | 586.93 | 01-JUN-07:10 | 0.142116E+10 | 953.29 | 01-JUN-07:10 |
July | 0.577640E+09 | 586.93 | 03-JUL-07:10 | 0.140153E+10 | 953.29 | 03-JUL-07:10 |
August | 0.645945E+09 | 586.93 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.591237E+09 | 709.49 | 21-SEP-07:10 | 0.137331E+10 | 953.29 | 01-SEP-07:10 |
October | 0.632755E+09 | 926.61 | 31-OCT-07:10 | 0.142307E+10 | 953.29 | 02-OCT-07:10 |
November | 0.658537E+09 | 952.03 | 06-NOV-16:00 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.668275E+09 | 952.03 | 01-DEC-16:30 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.751846E+10 | 0.168948E+11 | ||||
Minimum of Months | 0.577640E+09 | 586.93 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.672988E+09 | 952.03 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.208150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.200796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.212402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.208620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.204550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.200739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.208179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.203773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.204522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.247342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.188385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.216654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.681718E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.656322E+10 | 0.102966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.708257E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.704833E+10 | 0.106494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.659746E+10 | 0.105023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.656322E+10 | 0.102908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.681718E+10 | 0.106637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.673729E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.659746E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.817035E+11 | 0.126600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.618369E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.734796E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107629E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285426E+10 |
February | 0.901968E+09 | 0.932268E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207990E+10 |
March | 0.107774E+10 | 0.105558E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176347E+10 |
April | 0.956342E+09 | 0.926266E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12633755.42 | 0.109172E+10 |
May | 0.103597E+10 | 0.978495E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3537506.46 | 0.615318E+09 |
June | 0.103308E+10 | 0.968832E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49876307.64 | 0.366646E+09 |
July | 0.959235E+09 | 0.911524E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17908820.08 | 0.268814E+09 |
August | 0.107774E+10 | 0.102007E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18915362.25 | 0.359244E+09 |
September | 0.956342E+09 | 0.935815E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16852346.28 | 0.552085E+09 |
October | 0.994195E+09 | 0.100292E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101924E+10 |
November | 0.984487E+09 | 0.105013E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175505E+10 |
December | 0.959235E+09 | 0.107453E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238005E+10 |
Annual Sum or Average | 0.119305E+11 | 0.119327E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119724E+09 | 0.151058E+11 |
Minimum of Months | 0.901968E+09 | 0.911524E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268814E+09 |
Maximum of Months | 0.107774E+10 | 0.107629E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49876307.64 | 0.285426E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.674740E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190711E+10 |
February | 0.571020E+09 | 0.586945E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139024E+10 |
March | 0.682301E+09 | 0.667911E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118404E+10 |
April | 0.605444E+09 | 0.587144E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9215918.69 | 0.746521E+09 |
May | 0.655854E+09 | 0.621593E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2391777.75 | 0.416605E+09 |
June | 0.654023E+09 | 0.615362E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34593787.72 | 0.244516E+09 |
July | 0.607275E+09 | 0.578498E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12230364.54 | 0.179344E+09 |
August | 0.682301E+09 | 0.647752E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13227131.26 | 0.237841E+09 |
September | 0.605444E+09 | 0.593311E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11294443.31 | 0.377650E+09 |
October | 0.629407E+09 | 0.631758E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697934E+09 |
November | 0.623262E+09 | 0.661904E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117426E+10 |
December | 0.607275E+09 | 0.671055E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159134E+10 |
Annual Sum or Average | 0.755301E+10 | 0.753797E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82953423.27 | 0.101474E+11 |
Minimum of Months | 0.571020E+09 | 0.578498E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179344E+09 |
Maximum of Months | 0.682301E+09 | 0.674740E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34593787.72 | 0.190711E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105351E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287907E+10 |
February | 0.901968E+09 | 0.918126E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212194E+10 |
March | 0.107774E+10 | 0.105228E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182226E+10 |
April | 0.956342E+09 | 0.926978E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9533895.49 | 0.114311E+10 |
May | 0.103597E+10 | 0.981822E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3529051.53 | 0.627133E+09 |
June | 0.103308E+10 | 0.972590E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50048562.86 | 0.363033E+09 |
July | 0.959235E+09 | 0.914200E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16704277.59 | 0.267177E+09 |
August | 0.107774E+10 | 0.102284E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17462084.09 | 0.369443E+09 |
September | 0.956342E+09 | 0.934903E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11755529.36 | 0.591314E+09 |
October | 0.994195E+09 | 0.992018E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111422E+10 |
November | 0.984487E+09 | 0.103563E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180172E+10 |
December | 0.959235E+09 | 0.104476E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242616E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118497E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109033E+09 | 0.155266E+11 |
Minimum of Months | 0.901968E+09 | 0.914200E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267177E+09 |
Maximum of Months | 0.107774E+10 | 0.105351E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50048562.86 | 0.287907E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.672988E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190772E+10 |
February | 0.570983E+09 | 0.584573E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139624E+10 |
March | 0.682256E+09 | 0.667167E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118788E+10 |
April | 0.605404E+09 | 0.585782E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6637531.23 | 0.756740E+09 |
May | 0.655811E+09 | 0.619893E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2558932.55 | 0.415717E+09 |
June | 0.653980E+09 | 0.613670E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33904077.68 | 0.244979E+09 |
July | 0.607235E+09 | 0.577640E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11932205.09 | 0.184536E+09 |
August | 0.682256E+09 | 0.645945E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13371172.46 | 0.245878E+09 |
September | 0.605404E+09 | 0.591237E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10768323.26 | 0.380223E+09 |
October | 0.629366E+09 | 0.632756E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696752E+09 |
November | 0.623221E+09 | 0.658538E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117601E+10 |
December | 0.607235E+09 | 0.668276E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159162E+10 |
Annual Sum or Average | 0.755252E+10 | 0.751846E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79172242.27 | 0.101843E+11 |
Minimum of Months | 0.570983E+09 | 0.577640E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184536E+09 |
Maximum of Months | 0.682256E+09 | 0.672988E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33904077.68 | 0.190772E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107327E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153468E+10 |
February | 0.901968E+09 | 0.929725E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113298E+10 |
March | 0.107774E+10 | 0.105463E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960506E+09 |
April | 0.956342E+09 | 0.925785E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10195641.46 | 0.583822E+09 |
May | 0.103597E+10 | 0.978090E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2071805.12 | 0.322135E+09 |
June | 0.103308E+10 | 0.968417E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30671732.15 | 0.194460E+09 |
July | 0.959235E+09 | 0.911280E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10833478.98 | 0.142934E+09 |
August | 0.107774E+10 | 0.101965E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10143138.16 | 0.201259E+09 |
September | 0.956342E+09 | 0.935158E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9479054.31 | 0.322911E+09 |
October | 0.994195E+09 | 0.100104E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617269E+09 |
November | 0.984487E+09 | 0.104794E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100244E+10 |
December | 0.959235E+09 | 0.107019E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130914E+10 |
Annual Sum or Average | 0.119305E+11 | 0.119152E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73394850.19 | 0.832453E+10 |
Minimum of Months | 0.901968E+09 | 0.911280E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142934E+09 |
Maximum of Months | 0.107774E+10 | 0.107327E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30671732.15 | 0.153468E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.673766E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102559E+10 |
February | 0.571020E+09 | 0.585929E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760047E+09 |
March | 0.682301E+09 | 0.667454E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648662E+09 |
April | 0.605444E+09 | 0.586877E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6420803.81 | 0.403579E+09 |
May | 0.655854E+09 | 0.621288E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1326111.07 | 0.226740E+09 |
June | 0.654023E+09 | 0.615079E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19462388.17 | 0.133309E+09 |
July | 0.607275E+09 | 0.578272E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6677105.58 | 98988294.42 |
August | 0.682301E+09 | 0.647439E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6923548.75 | 0.136797E+09 |
September | 0.605444E+09 | 0.592958E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5911071.41 | 0.223639E+09 |
October | 0.629407E+09 | 0.631125E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423842E+09 |
November | 0.623262E+09 | 0.661044E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670063E+09 |
December | 0.607275E+09 | 0.669457E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875211E+09 |
Annual Sum or Average | 0.755301E+10 | 0.753069E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46721028.79 | 0.562647E+10 |
Minimum of Months | 0.571020E+09 | 0.578272E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98988294.42 |
Maximum of Months | 0.682301E+09 | 0.673766E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19462388.17 | 0.102559E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105095E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138887E+11 |
February | 0.901968E+09 | 0.916699E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105680E+11 |
March | 0.107774E+10 | 0.105165E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919406E+10 |
April | 0.956342E+09 | 0.926501E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36462514.06 | 0.571186E+10 |
May | 0.103597E+10 | 0.981280E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106926E+09 | 0.312660E+10 |
June | 0.103308E+10 | 0.971993E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417715E+09 | 0.169986E+10 |
July | 0.959235E+09 | 0.913676E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366247E+09 | 0.803042E+09 |
August | 0.107774E+10 | 0.102210E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505780E+09 | 0.125715E+10 |
September | 0.956342E+09 | 0.934349E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260418E+09 | 0.289493E+10 |
October | 0.994195E+09 | 0.991286E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572995E+10 |
November | 0.984487E+09 | 0.103423E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805964E+10 |
December | 0.959235E+09 | 0.104281E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111263E+11 |
Annual Sum or Average | 0.119305E+11 | 0.118375E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169355E+10 | 0.740600E+11 |
Minimum of Months | 0.901968E+09 | 0.913676E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803042E+09 |
Maximum of Months | 0.107774E+10 | 0.105165E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505780E+09 | 0.138887E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.671810E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102588E+10 |
February | 0.570983E+09 | 0.583715E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762786E+09 |
March | 0.682256E+09 | 0.666508E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649969E+09 |
April | 0.605404E+09 | 0.585453E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4363428.55 | 0.411755E+09 |
May | 0.655811E+09 | 0.619592E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1389916.92 | 0.224944E+09 |
June | 0.653980E+09 | 0.613409E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18861761.70 | 0.133488E+09 |
July | 0.607235E+09 | 0.577461E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6345763.13 | 0.104204E+09 |
August | 0.682256E+09 | 0.645661E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6722536.66 | 0.142943E+09 |
September | 0.605404E+09 | 0.590862E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5465241.21 | 0.224607E+09 |
October | 0.629366E+09 | 0.632109E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421530E+09 |
November | 0.623221E+09 | 0.657728E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671085E+09 |
December | 0.607235E+09 | 0.666757E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875563E+09 |
Annual Sum or Average | 0.755252E+10 | 0.751106E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43148648.16 | 0.564876E+10 |
Minimum of Months | 0.570983E+09 | 0.577461E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104204E+09 |
Maximum of Months | 0.682256E+09 | 0.671810E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18861761.70 | 0.102588E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.107629E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239734E+10 |
February | 0.901968E+09 | 0.932268E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177098E+10 |
March | 0.107774E+10 | 0.105558E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152882E+10 |
April | 0.956342E+09 | 0.926266E+09 | 0.217059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10789708.81 | 0.963744E+09 |
May | 0.103597E+10 | 0.978495E+09 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2967626.34 | 0.545337E+09 |
June | 0.103308E+10 | 0.968831E+09 | 0.224498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41398256.52 | 0.323165E+09 |
July | 0.959235E+09 | 0.911523E+09 | 0.221396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14871886.98 | 0.235977E+09 |
August | 0.107774E+10 | 0.102007E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15441271.07 | 0.318812E+09 |
September | 0.956342E+09 | 0.935815E+09 | 0.216939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13769294.17 | 0.497628E+09 |
October | 0.994195E+09 | 0.100292E+10 | 0.224800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933069E+09 |
November | 0.984487E+09 | 0.105013E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152510E+10 |
December | 0.959235E+09 | 0.107453E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202443E+10 |
Annual Sum or Average | 0.119305E+11 | 0.119327E+11 | 0.266883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99238043.90 | 0.130644E+11 |
Minimum of Months | 0.901968E+09 | 0.911523E+09 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235977E+09 |
Maximum of Months | 0.107774E+10 | 0.107629E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41398256.52 | 0.239734E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.674739E+09 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159989E+10 |
February | 0.421807E+09 | 0.586945E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118470E+10 |
March | 0.502994E+09 | 0.667911E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102570E+10 |
April | 0.447140E+09 | 0.587144E+09 | 0.137408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8446376.92 | 0.653302E+09 |
May | 0.484071E+09 | 0.621593E+09 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2033643.81 | 0.362962E+09 |
June | 0.482240E+09 | 0.615362E+09 | 0.142117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30280224.07 | 0.213124E+09 |
July | 0.448971E+09 | 0.578498E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10976762.98 | 0.154638E+09 |
August | 0.502994E+09 | 0.647752E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11291873.95 | 0.208048E+09 |
September | 0.447140E+09 | 0.593311E+09 | 0.137332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10170262.06 | 0.334532E+09 |
October | 0.465148E+09 | 0.631759E+09 | 0.142308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.60 | 0.632271E+09 |
November | 0.460569E+09 | 0.661904E+09 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101827E+10 |
December | 0.448971E+09 | 0.671055E+09 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135255E+10 |
Annual Sum or Average | 0.557719E+10 | 0.753797E+10 | 0.168949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73199382.41 | 0.873998E+10 |
Minimum of Months | 0.421807E+09 | 0.578498E+09 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154638E+09 |
Maximum of Months | 0.502994E+09 | 0.674739E+09 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30280224.07 | 0.159989E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.105351E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242839E+10 |
February | 0.901968E+09 | 0.918125E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181886E+10 |
March | 0.107774E+10 | 0.105228E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158373E+10 |
April | 0.956342E+09 | 0.926978E+09 | 0.217058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8246159.73 | 0.100332E+10 |
May | 0.103597E+10 | 0.981822E+09 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2966251.74 | 0.550938E+09 |
June | 0.103308E+10 | 0.972590E+09 | 0.224497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42372643.57 | 0.319203E+09 |
July | 0.959235E+09 | 0.914200E+09 | 0.221395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14124585.30 | 0.233341E+09 |
August | 0.107774E+10 | 0.102284E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14593195.76 | 0.325421E+09 |
September | 0.956342E+09 | 0.934903E+09 | 0.216937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9792796.20 | 0.525111E+09 |
October | 0.994195E+09 | 0.992018E+09 | 0.224798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100720E+10 |
November | 0.984487E+09 | 0.103563E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157181E+10 |
December | 0.959235E+09 | 0.104476E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207518E+10 |
Annual Sum or Average | 0.119305E+11 | 0.118497E+11 | 0.266882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92095632.29 | 0.134425E+11 |
Minimum of Months | 0.901968E+09 | 0.914200E+09 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233341E+09 |
Maximum of Months | 0.107774E+10 | 0.105351E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42372643.57 | 0.242839E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.672988E+09 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160089E+10 |
February | 0.570983E+09 | 0.584572E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118955E+10 |
March | 0.682256E+09 | 0.667167E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102840E+10 |
April | 0.605404E+09 | 0.585782E+09 | 0.137407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5609081.82 | 0.662534E+09 |
May | 0.655811E+09 | 0.619893E+09 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125902.60 | 0.364922E+09 |
June | 0.653980E+09 | 0.613667E+09 | 0.142116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28305451.35 | 0.214953E+09 |
July | 0.607235E+09 | 0.577640E+09 | 0.140153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9776700.18 | 0.160924E+09 |
August | 0.682256E+09 | 0.645945E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10732611.70 | 0.216485E+09 |
September | 0.605404E+09 | 0.591237E+09 | 0.137331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8831761.08 | 0.337665E+09 |
October | 0.629366E+09 | 0.632755E+09 | 0.142307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631210E+09 |
November | 0.623221E+09 | 0.658537E+09 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101962E+10 |
December | 0.607235E+09 | 0.668275E+09 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135283E+10 |
Annual Sum or Average | 0.755252E+10 | 0.751846E+10 | 0.168948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65381508.73 | 0.877997E+10 |
Minimum of Months | 0.570983E+09 | 0.577640E+09 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160924E+09 |
Maximum of Months | 0.682256E+09 | 0.672988E+09 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28305451.35 | 0.160089E+10 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317830E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240309E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210964E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13463048.98 | 0.134542E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2812730.07 | 0.742665E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52472909.60 | 0.431316E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14840897.59 | 0.316189E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14209392.76 | 0.438861E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12266576.24 | 0.702829E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135032E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212806E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274583E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110066E+09 | 0.178925E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316189E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52472909.60 | 0.317830E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398974E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299622E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261825E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16327987.67 | 0.167071E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3602869.71 | 0.940728E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65600645.47 | 0.547851E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18692902.46 | 0.402045E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18984936.55 | 0.550870E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17332947.92 | 0.865346E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161856E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259639E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341004E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140542E+09 | 0.222068E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402045E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65600645.47 | 0.398974E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418648E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310501E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268611E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8390932.51 | 0.170368E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2586499.46 | 0.973755E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47337449.20 | 0.556803E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9726268.55 | 0.415755E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14244805.67 | 0.559765E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10269690.38 | 0.862747E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158968E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263050E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351674E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92555645.77 | 0.227870E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415755E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47337449.20 | 0.418648E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 18520.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 18520.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 18520.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 18520.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 18520.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 18520.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 18520.31 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 18520.31 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 18520.31 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 18520.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 18520.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 18520.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 18520.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 7133.97 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 7133.97 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 7133.97 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 7133.97 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 7133.97 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 7133.97 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 7133.97 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 7133.97 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 7133.97 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 7133.97 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 7133.97 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 7133.97 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5618.93 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 1317.74 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3922.83 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 1139.25 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2972.36 | 20-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 1060.27 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.56 | 15-APR-17:02 | 2238.37 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1442.55 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.65 | 11-JUN-14:58 | 1209.57 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.85 | 02-JUL-15:40 | 572.66 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 734.14 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 1066.35 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.94 | 17-SEP-14:50 | 1086.31 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1460.43 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1580.76 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4295.43 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.90 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.66 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 610.65 | 6589.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.94 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 844.32 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2613.52 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 737.25 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2007.63 | 06-MAR-06:00 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.52 | 15-APR-17:10 | 1492.24 | 02-APR-23:55 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 963.93 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.33 | 18-JUN-16:20 | 803.64 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.74 | 02-JUL-15:40 | 375.98 | 09-JUL-21:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 | 13-AUG-14:30 | 499.59 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.50 | 17-SEP-14:50 | 716.98 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 880.05 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1053.82 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2861.79 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.24 | 09-DEC-01:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.98 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 463.33 | 4393.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5618.95 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 1271.46 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3924.89 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 1081.16 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3128.32 | 05-MAR-14:20 |
April | 1306.65 | 03-APR-09:09 | 1051.21 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.47 | 15-APR-17:10 | 2238.38 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 | 31-MAY-13:00 | 1461.94 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 621.32 | 11-JUN-14:56 | 1210.96 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.89 | 02-JUL-15:40 | 576.46 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 04-AUG-16:40 | 778.53 | 06-AUG-14:00 |
September | 1306.65 | 01-SEP-09:09 | 1039.35 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.87 | 17-SEP-14:48 | 1090.83 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1397.25 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1580.77 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4297.92 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6589.91 | 09-DEC-01:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.46 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 621.32 | 6589.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3745.93 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 789.55 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2612.84 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 736.97 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2007.63 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 700.48 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.53 | 15-APR-17:05 | 1492.24 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 | 31-MAY-13:00 | 961.07 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.31 | 11-JUN-14:56 | 792.91 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.45 | 02-JUL-11:00 | 398.58 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | 04-AUG-16:40 | 502.15 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 709.50 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.58 | 17-SEP-11:30 | 787.25 | 24-SEP-17:25 |
October | 827.17 | 02-OCT-09:09 | 926.61 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1053.82 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2861.44 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.24 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.58 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 424.31 | 4393.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2983.43 | 29-JAN-10:53 |
February | 1306.65 | 01-FEB-10:09 | 1306.36 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2095.18 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 1123.01 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1598.59 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 1040.66 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.32 | 15-APR-17:02 | 1183.45 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 31-MAY-13:00 | 792.91 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.60 | 11-JUN-14:52 | 710.43 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.04 | 02-JUL-15:30 | 296.99 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 | 04-AUG-16:40 | 416.23 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 1046.81 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.33 | 17-SEP-15:00 | 648.18 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1458.12 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 949.31 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2296.56 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3484.59 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.99 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 389.32 | 3484.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-10:51 |
February | 827.22 | 01-FEB-10:09 | 838.73 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1396.61 | 10-FEB-22:01 |
March | 827.22 | 01-MAR-10:09 | 729.91 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1066.70 | 05-MAR-09:55 |
April | 827.22 | 03-APR-09:09 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.33 | 15-APR-17:02 | 785.56 | 02-APR-23:55 |
May | 827.22 | 01-MAY-09:09 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 549.24 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.88 | 18-JUN-16:10 | 485.49 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.38 | 02-JUL-16:10 | 200.43 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.03 | 13-AUG-14:00 | 285.38 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.88 | 17-SEP-15:00 | 437.44 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 875.36 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 643.09 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.48 | 20-NOV-22:01 |
December | 827.22 | 01-DEC-10:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2321.92 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.43 | |||||
Maximum of Months | 827.22 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 268.88 | 2321.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 64197.30 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1260.76 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 73763.44 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1061.50 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 40764.24 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 1031.12 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4489.26 | 18-APR-12:00 | 34310.74 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6075.17 | 31-MAY-12:00 | 22412.97 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8437.88 | 26-JUN-16:05 | 15665.12 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6823.49 | 26-JUL-16:10 | 10849.02 | 24-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9927.99 | 04-AUG-16:03 | 15403.33 | 07-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 1018.34 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7928.95 | 07-SEP-16:03 | 25198.90 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1391.03 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29607.70 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 47088.60 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 52974.94 | 08-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10849.02 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 9927.99 | 73763.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1988.94 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 783.37 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1396.28 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 726.20 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1065.72 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 692.03 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.98 | 15-APR-17:02 | 780.93 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 | 31-MAY-13:00 | 538.18 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.57 | 11-JUN-14:52 | 469.37 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.85 | 02-JUL-11:30 | 216.22 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 | 04-AUG-16:40 | 295.64 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 701.32 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.14 | 17-SEP-11:40 | 436.47 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 925.52 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 643.39 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.47 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2321.46 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.22 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 211.57 | 2321.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4622.63 | 29-JAN-10:51 |
February | 1306.65 | 01-FEB-10:09 | 1317.75 | 01-FEB-16:00 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3278.67 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 1139.23 | 01-MAR-16:00 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2504.79 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 1060.24 | 10-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.22 | 15-APR-17:02 | 1841.91 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1291.03 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 504.64 | 11-JUN-14:52 | 1107.51 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.84 | 02-JUL-15:30 | 488.17 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 649.87 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 1066.33 | 21-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.10 | 17-SEP-15:00 | 975.52 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1460.43 | 31-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1399.27 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3587.15 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5423.05 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.17 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 504.64 | 5423.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 952.10 | 02-JAN-16:40 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3097.66 | 29-JAN-10:51 |
February | 805.43 | 01-FEB-08:09 | 844.32 | 01-FEB-16:00 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2184.55 | 10-FEB-22:01 |
March | 805.43 | 01-MAR-08:09 | 737.23 | 01-MAR-16:00 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1682.97 | 05-MAR-09:55 |
April | 805.43 | 03-APR-07:10 | 586.97 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.42 | 15-APR-17:02 | 1225.98 | 02-APR-23:55 |
May | 805.43 | 01-MAY-07:10 | 586.97 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 858.88 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 586.97 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.81 | 18-JUN-16:20 | 734.29 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 586.97 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.79 | 02-JUL-16:10 | 336.92 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 586.97 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.25 | 13-AUG-14:20 | 441.16 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 586.97 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.69 | 17-SEP-15:00 | 641.35 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 880.05 | 31-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 20-OCT-15:00 | 930.96 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 952.10 | 06-NOV-16:00 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2390.14 | 20-NOV-22:01 |
December | 805.43 | 01-DEC-08:09 | 952.10 | 01-DEC-16:30 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3612.60 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.92 | |||||
Maximum of Months | 805.43 | 952.10 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 415.81 | 3612.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1503.90 | 02-JAN-16:40 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4763.64 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 1271.44 | 14-FEB-16:00 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3280.16 | 10-FEB-22:01 |
March | 1306.65 | 01-MAR-10:09 | 1081.14 | 01-MAR-16:00 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2725.35 | 05-MAR-14:18 |
April | 1306.65 | 03-APR-09:09 | 1051.18 | 10-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.02 | 15-APR-17:02 | 1844.67 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 927.16 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 31-MAY-13:00 | 1304.25 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 927.16 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.59 | 18-JUN-16:00 | 1108.21 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 927.16 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.93 | 02-JUL-15:30 | 491.24 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 927.16 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.60 | 04-AUG-16:40 | 660.16 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 1039.32 | 21-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.79 | 17-SEP-14:58 | 977.03 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1397.26 | 31-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1439.81 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1503.90 | 06-NOV-16:00 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3589.43 | 20-NOV-22:01 |
December | 1306.65 | 01-DEC-10:09 | 1503.90 | 01-DEC-16:30 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5425.35 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.24 | |||||
Maximum of Months | 1306.65 | 1503.90 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 517.59 | 5425.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 952.03 | 02-JAN-16:40 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3080.79 | 29-JAN-10:51 |
February | 827.17 | 01-FEB-10:09 | 789.54 | 14-FEB-16:00 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2184.12 | 10-FEB-22:01 |
March | 827.17 | 01-MAR-10:09 | 736.99 | 14-MAR-07:10 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1669.85 | 06-MAR-06:00 |
April | 827.17 | 03-APR-09:09 | 700.46 | 10-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.42 | 16-APR-13:10 | 1224.89 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 586.93 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.84 | 31-MAY-13:00 | 857.72 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 586.93 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.59 | 11-JUN-15:24 | 726.61 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 586.93 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.88 | 02-JUL-11:30 | 338.29 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 586.93 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 04-AUG-16:40 | 443.77 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 709.49 | 21-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.86 | 17-SEP-11:40 | 656.44 | 24-SEP-16:30 |
October | 827.17 | 02-OCT-09:09 | 926.61 | 31-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 935.45 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 952.03 | 06-NOV-16:00 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2389.99 | 20-NOV-22:01 |
December | 827.17 | 01-DEC-10:09 | 952.03 | 01-DEC-16:30 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3611.48 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.29 | |||||
Maximum of Months | 827.17 | 952.03 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 333.59 | 3611.48 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6100.65 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4268.26 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3456.56 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.91 | 15-APR-17:02 | 2689.37 | 02-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.57 | 31-MAY-13:00 | 1819.66 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.82 | 11-JUN-14:52 | 1570.61 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.02 | 02-JUL-15:10 | 636.85 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.69 | 04-AUG-16:25 | 872.03 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.71 | 17-SEP-14:40 | 1373.35 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2091.69 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4555.51 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7426.20 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.82 | 7426.20 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7585.53 | 29-JAN-10:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5380.06 | 04-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4349.28 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.13 | 15-APR-17:02 | 3216.86 | 02-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.29 | 31-MAY-13:00 | 2294.49 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.28 | 18-JUN-16:00 | 1963.56 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.47 | 02-JUL-15:10 | 803.49 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 | 04-AUG-16:25 | 1097.45 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.82 | 17-SEP-14:42 | 1727.33 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2512.08 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5693.32 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9253.80 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.28 | 9253.80 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8019.03 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5724.99 | 10-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 4474.19 | 20-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.72 | 15-APR-17:02 | 3246.69 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.14 | 31-MAY-13:00 | 2186.76 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.57 | 18-JUN-16:00 | 1838.80 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.38 | 25-JUL-21:03 | 869.44 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.28 | 04-AUG-16:30 | 1121.42 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 06-SEP-16:00 | 1629.81 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2358.94 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6217.02 | 20-NOV-22:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9388.12 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.44 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.57 | 9388.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10071.90 | 13-JAN-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10980.66 | 24-FEB-17:00 | 6035.01 | 7133.97 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17124.37 | 29-MAR-07:20 | 12070.02 | 14267.94 | 37040.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39481.74 | 17-APR-05:03 | 2541.06 | 3170.73 | 20553.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44493.47 | 31-MAY-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46004.96 | 27-JUN-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46246.13 | 05-JUL-04:02 | 0.00 | 4756.10 | 30830.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 45378.51 | 14-AUG-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45739.91 | 11-SEP-04:02 | 0.00 | 3963.42 | 25692.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21555.29 | 06-OCT-07:03 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20819.59 | 02-NOV-07:04 | 42245.05 | 49937.79 | 129642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10647.57 | 07-DEC-16:20 | 12070.02 | 14267.94 | 29456.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10071.90 | 0.00 | 3170.73 | 14728.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46246.13 | 60350.08 | 71339.70 | 185203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1345.66 |
February | 1016.39 | 24-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.69 |
March | 2433.09 | 28-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.36 |
April | 9062.99 | 18-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.28 | 0.00 |
May | 10244.32 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.30 | 0.00 |
June | 11688.66 | 26-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.07 | 0.00 |
July | 10953.58 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 0.00 |
August | 11652.48 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 0.00 |
September | 10502.12 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 0.00 |
October | 4195.15 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.80 |
November | 2250.16 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.82 |
December | 139.35 | 02-DEC-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11688.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.64 | 1345.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2185.44 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1771.44 |
February | 2474.08 | 16-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1989.78 |
March | 1833.22 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.90 |
April | 3626.28 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 0.00 |
May | 4321.67 | 31-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.18 | 0.00 |
June | 5579.78 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.28 | 0.00 |
July | 5263.40 | 03-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 0.00 |
August | 5210.79 | 04-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.78 | 0.00 |
September | 4797.00 | 08-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.24 | 0.00 |
October | 1969.77 | 13-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.57 |
November | 1660.35 | 21-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.64 |
December | 2473.42 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1566.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5579.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.78 | 3661.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3163.49 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.63 |
February | 3965.25 | 02-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.36 |
March | 2419.32 | 22-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.59 |
April | 3630.47 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.91 | 0.00 |
May | 4377.35 | 31-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.53 | 0.00 |
June | 6307.85 | 26-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.06 | 0.00 |
July | 5562.75 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 | 0.00 |
August | 5343.48 | 04-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 0.00 |
September | 5149.21 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.45 | 0.00 |
October | 2566.28 | 31-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.94 |
November | 2339.57 | 09-NOV-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.66 |
December | 2795.35 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2339.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6307.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 1444.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6644.49 | 13-JAN-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6880.86 | 24-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8545.08 | 24-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31291.36 | 17-APR-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31989.88 | 30-MAY-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34322.30 | 27-JUN-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34239.95 | 03-JUL-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32671.15 | 14-AUG-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34367.05 | 11-SEP-04:02 | 0.00 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10593.89 | 20-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10144.77 | 03-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6460.91 | 01-DEC-16:30 | 12070.02 | 14267.94 | 14286.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6460.91 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34367.05 | 12070.02 | 14267.94 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6457.19 | 13-JAN-16:50 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6979.38 | 24-FEB-17:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8151.42 | 24-MAR-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18064.32 | 18-APR-15:40 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25562.11 | 30-MAY-05:03 | 2541.06 | 3170.73 | 12699.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36087.76 | 26-JUN-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36448.25 | 03-JUL-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34396.83 | 04-AUG-04:02 | 0.00 | 4756.10 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33696.84 | 11-SEP-05:02 | 3176.32 | 3963.42 | 15874.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10159.92 | 20-OCT-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9066.76 | 03-NOV-16:00 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6312.82 | 01-DEC-16:10 | 6035.01 | 7133.97 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6312.82 | 0.00 | 3170.73 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36448.25 | 6035.01 | 7133.97 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1421.27 | 14-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.97 |
February | 1578.41 | 24-FEB-16:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.07 |
March | 2048.94 | 28-MAR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.12 |
April | 5937.82 | 18-APR-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 116.87 | 0.00 |
May | 6525.37 | 31-MAY-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.23 | 0.00 |
June | 10456.19 | 25-JUN-18:02 | 0.00 | 309.03 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 311.48 | 0.00 |
July | 7011.75 | 03-JUL-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 0.00 |
August | 7260.79 | 04-AUG-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 0.00 |
September | 6418.91 | 11-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 0.00 |
October | 2274.61 | 20-OCT-13:40 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 |
November | 2064.31 | 03-NOV-15:40 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.10 |
December | 1431.67 | 30-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1421.27 | 0.00 | 309.03 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10456.19 | 1306.65 | 927.16 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 311.48 | 442.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1482.27 | 14-JAN-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.59 |
February | 2043.27 | 24-FEB-10:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.61 |
March | 2497.11 | 28-MAR-09:50 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.51 |
April | 7767.95 | 18-APR-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 0.00 |
May | 8716.72 | 31-MAY-09:10 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 0.00 |
June | 14364.53 | 25-JUN-09:22 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 |
July | 14405.66 | 02-JUL-08:52 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.28 |
August | 8770.24 | 02-AUG-09:10 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 0.00 |
September | 12569.42 | 04-SEP-09:42 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.66 |
October | 2845.41 | 20-OCT-09:50 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.20 |
November | 2031.23 | 03-NOV-14:30 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 |
December | 1489.67 | 30-DEC-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1482.27 | 211.95 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14405.66 | 827.22 | 586.97 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 294.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4561.27 | 12-JAN-12:40 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.34 |
February | 8064.94 | 24-FEB-13:50 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.43 |
March | 8263.39 | 24-MAR-13:40 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.78 |
April | 14947.34 | 16-APR-12:02 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.79 |
May | 10468.02 | 30-MAY-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 23.81 | 0.00 |
June | 16076.91 | 25-JUN-15:22 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 447.57 | 0.00 |
July | 17139.08 | 30-JUL-13:22 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
August | 13115.12 | 29-AUG-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
September | 19409.11 | 17-SEP-13:22 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.43 |
October | 11415.49 | 20-OCT-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 |
November | 10210.62 | 03-NOV-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.37 |
December | 5877.08 | 01-DEC-13:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4561.27 | 267.84 | 206.02 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19409.11 | 1306.65 | 927.16 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 447.57 | 322.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2038.51 | 12-JAN-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.91 |
February | 2781.33 | 24-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 |
March | 2918.00 | 23-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.06 |
April | 13964.27 | 16-APR-16:02 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 138.39 | 0.00 |
May | 12256.26 | 14-MAY-16:22 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 |
June | 16879.59 | 25-JUN-17:21 | 0.00 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 191.65 | 0.00 |
July | 16641.77 | 02-JUL-16:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 41.81 | 0.00 |
August | 12946.91 | 13-AUG-16:22 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 |
September | 16597.96 | 04-SEP-17:02 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.62 |
October | 5439.12 | 20-OCT-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 3443.34 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 |
December | 2023.29 | 01-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2023.29 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16879.59 | 805.38 | 586.93 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 191.65 | 216.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1063.91 | 14-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.92 |
February | 1080.36 | 25-FEB-17:03 | 267.84 | 245.85 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.54 |
March | 1364.45 | 28-MAR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.40 |
April | 3204.35 | 18-APR-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 0.00 |
May | 4150.86 | 31-MAY-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
June | 5651.88 | 26-JUN-14:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
July | 5845.47 | 05-JUL-06:03 | 803.52 | 927.14 | 2007.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
August | 5932.88 | 04-AUG-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 | 0.00 |
September | 5702.71 | 11-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 52.04 | 0.00 |
October | 1695.74 | 02-OCT-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
November | 1607.83 | 03-NOV-15:20 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 |
December | 1069.24 | 30-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1063.91 | 267.84 | 245.85 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5932.88 | 1306.65 | 927.16 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 | 235.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1229.19 | 14-JAN-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.94 |
February | 1529.10 | 24-FEB-10:20 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.72 |
March | 1820.24 | 28-MAR-10:00 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.99 |
April | 5053.29 | 18-APR-09:40 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
May | 6117.79 | 31-MAY-09:30 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 0.00 |
June | 8611.49 | 25-JUN-10:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 0.00 |
July | 12289.75 | 02-JUL-09:21 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.16 |
August | 8133.26 | 20-AUG-09:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.64 |
September | 10484.65 | 04-SEP-09:42 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.59 |
October | 2385.05 | 20-OCT-10:00 | 827.22 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.72 |
November | 1765.92 | 03-NOV-10:50 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 |
December | 1233.25 | 02-DEC-17:03 | 169.56 | 211.56 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1229.19 | 169.56 | 163.03 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12289.75 | 827.22 | 586.97 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 156.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1728.94 | 13-JAN-14:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3322.26 |
February | 2148.82 | 24-FEB-14:50 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2723.49 |
March | 2642.29 | 24-MAR-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.02 |
April | 10777.98 | 18-APR-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 4489.26 | 0.00 |
May | 11447.44 | 31-MAY-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6075.17 | 0.00 |
June | 12222.25 | 26-JUN-12:00 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 6668.58 | 0.00 |
July | 13820.21 | 02-JUL-14:42 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 72.17 | 0.00 |
August | 12817.24 | 04-AUG-16:10 | 1607.03 | 2060.35 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8805.51 | 0.00 |
September | 14942.23 | 04-SEP-13:42 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 |
October | 8644.88 | 20-OCT-14:00 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.55 |
November | 7005.73 | 04-NOV-13:30 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.35 |
December | 2090.14 | 02-DEC-12:40 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1728.94 | 137.54 | 154.52 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14942.23 | 1607.03 | 2060.35 | 3346.41 | 0.00 | 0.00 | 0.00 | 0.00 | 8805.51 | 3322.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1577.46 | 12-JAN-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.49 |
February | 2030.53 | 24-FEB-16:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 |
March | 1997.44 | 23-MAR-16:50 | 254.33 | 326.07 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 |
April | 7207.55 | 16-APR-17:32 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
May | 7093.81 | 21-MAY-18:03 | 0.00 | 130.42 | 1271.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.32 |
June | 12704.16 | 25-JUN-17:21 | 0.00 | 228.23 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 128.61 | 0.00 |
July | 13730.32 | 02-JUL-18:01 | 0.00 | 260.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
August | 9175.04 | 05-AUG-17:05 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.54 |
September | 12969.98 | 04-SEP-17:02 | 0.00 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 |
October | 4387.17 | 11-OCT-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 |
November | 2795.87 | 03-NOV-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
December | 1652.65 | 01-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1577.46 | 0.00 | 130.42 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13730.32 | 805.38 | 586.93 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.61 | 119.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1155.12 | 14-JAN-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.83 |
February | 1341.83 | 24-FEB-16:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.67 |
March | 1720.25 | 24-MAR-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.30 |
April | 5483.61 | 18-APR-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 0.00 |
May | 5907.94 | 31-MAY-15:00 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 60.39 | 0.00 |
June | 10493.98 | 25-JUN-19:12 | 0.00 | 309.03 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 | 0.00 |
July | 9750.10 | 02-JUL-18:01 | 0.00 | 412.03 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 | 0.00 |
August | 6570.29 | 04-AUG-15:30 | 1272.23 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 | 0.00 |
September | 6175.61 | 11-SEP-14:00 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 81.04 | 0.00 |
October | 2091.38 | 20-OCT-13:30 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 |
November | 1861.29 | 03-NOV-13:30 | 1306.65 | 927.16 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.98 |
December | 1159.85 | 30-DEC-17:02 | 401.76 | 501.26 | 3011.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1155.12 | 0.00 | 309.03 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10493.98 | 1306.65 | 927.16 | 4015.71 | 0.00 | 0.00 | 0.00 | 0.00 | 106.67 | 369.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1589.13 | 12-JAN-10:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.15 |
February | 2163.44 | 24-FEB-10:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.33 |
March | 2945.32 | 28-MAR-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.39 |
April | 7722.18 | 18-APR-09:00 | 805.43 | 586.97 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 |
May | 10875.86 | 21-MAY-09:12 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.05 |
June | 15450.12 | 25-JUN-09:11 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 |
July | 15515.15 | 02-JUL-08:41 | 296.74 | 228.24 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 |
August | 14104.87 | 20-AUG-09:02 | 211.95 | 163.03 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.60 |
September | 8480.31 | 04-SEP-09:13 | 169.56 | 130.43 | 1271.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.06 |
October | 3485.76 | 20-OCT-08:55 | 1610.86 | 1173.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 |
November | 2194.31 | 04-NOV-09:25 | 0.00 | 391.31 | 1059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 |
December | 1476.56 | 30-DEC-17:02 | 254.35 | 317.34 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1476.56 | 0.00 | 130.43 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.07 | |
Maximum of Months | 15515.15 | 1610.86 | 1173.93 | 2224.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5260.48 | 12-JAN-12:30 | 687.71 | 927.16 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.95 |
February | 8171.59 | 24-FEB-13:40 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
March | 8318.74 | 24-MAR-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.04 |
April | 13651.59 | 16-APR-11:43 | 267.84 | 206.02 | 2007.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 |
May | 9729.51 | 30-MAY-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 | 0.00 |
June | 15940.24 | 11-JUN-14:42 | 401.76 | 309.03 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 373.05 | 0.00 |
July | 16685.39 | 30-JUL-12:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
August | 16440.20 | 13-AUG-13:32 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 |
September | 16334.02 | 04-SEP-13:12 | 334.80 | 257.52 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.82 |
October | 11361.60 | 20-OCT-13:10 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
November | 10307.64 | 03-NOV-13:30 | 1306.65 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.53 |
December | 6388.61 | 01-DEC-13:30 | 1272.23 | 927.16 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5260.48 | 267.84 | 206.02 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16685.39 | 1306.65 | 927.16 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 373.05 | 268.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1990.95 | 12-JAN-15:50 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.80 |
February | 2789.09 | 24-FEB-16:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 |
March | 3087.68 | 23-MAR-16:00 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.96 |
April | 12965.24 | 16-APR-16:22 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 103.76 | 0.00 |
May | 11492.95 | 14-MAY-16:22 | 211.94 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 |
June | 15865.97 | 25-JUN-17:11 | 0.00 | 326.04 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 156.68 | 0.00 |
July | 16241.62 | 02-JUL-18:01 | 0.00 | 260.83 | 2542.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
August | 15368.78 | 13-AUG-16:52 | 254.33 | 195.63 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.02 |
September | 11847.51 | 04-SEP-17:12 | 0.00 | 163.02 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
October | 5343.06 | 20-OCT-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.53 |
November | 3562.42 | 03-NOV-15:30 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 |
December | 1994.19 | 01-DEC-15:40 | 805.38 | 586.93 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1990.95 | 0.00 | 163.02 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16241.62 | 805.38 | 586.93 | 3177.63 | 0.00 | 0.00 | 0.00 | 0.00 | 156.68 | 183.80 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.247829E+12 | 272527.51 | 02-JAN-07:10 | 0.121052E+12 | 166484.71 | 31-JAN-07:00 |
February | 0.186354E+12 | 263410.66 | 06-FEB-07:10 | 0.821686E+11 | 193381.86 | 02-FEB-07:19 |
March | 0.166510E+12 | 231585.27 | 06-MAR-07:10 | 0.493192E+11 | 93916.74 | 06-MAR-08:09 |
April | 0.131492E+12 | 196768.87 | 03-APR-06:10 | 0.226544E+11 | 71472.92 | 03-APR-06:30 |
May | 0.127709E+12 | 153828.53 | 31-MAY-15:09 | 0.103441E+11 | 28352.93 | 02-MAY-06:19 |
June | 0.152582E+12 | 180491.06 | 26-JUN-07:49 | 0.945813E+10 | 9845.49 | 03-JUN-06:19 |
July | 0.162813E+12 | 179364.59 | 03-JUL-15:09 | 0.894961E+10 | 9242.21 | 03-JUL-11:20 |
August | 0.168851E+12 | 190905.71 | 04-AUG-15:30 | 0.933543E+10 | 9162.57 | 01-AUG-11:20 |
September | 0.132919E+12 | 161528.92 | 07-SEP-15:00 | 0.953841E+10 | 36173.83 | 30-SEP-06:30 |
October | 0.125515E+12 | 135400.89 | 16-OCT-06:10 | 0.150379E+11 | 49584.13 | 23-OCT-06:10 |
November | 0.164918E+12 | 252553.94 | 27-NOV-07:10 | 0.461512E+11 | 123636.28 | 25-NOV-17:00 |
December | 0.214242E+12 | 265393.59 | 11-DEC-07:10 | 0.887249E+11 | 135471.97 | 09-DEC-07:30 |
Annual Sum or Average | 0.198173E+13 | 0.472734E+12 | ||||
Minimum of Months | 0.125515E+12 | 135400.89 | 0.894961E+10 | 9162.57 | ||
Maximum of Months | 0.247829E+12 | 272527.51 | 0.121052E+12 | 193381.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.308764E+11 | 0.121432E+11 | 0.641572E+11 | 0.159118E+10 | 0.821644E+10 | 1312252.65 | 0.130844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276110E+11 | 0.998488E+10 | 0.580684E+11 | 0.143941E+10 | 0.635199E+10 | 1186778.30 | 0.828976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323700E+11 | 0.969433E+10 | 0.666107E+11 | 0.166685E+10 | 0.636366E+10 | 1343621.24 | 0.496567E+11 | 0.146151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287666E+11 | 0.798752E+10 | 0.619407E+11 | 0.153133E+10 | 0.670659E+10 | 1267813.82 | 0.200437E+11 | 0.451413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308516E+11 | 0.711542E+10 | 0.653840E+11 | 0.162820E+10 | 0.874782E+10 | 1327936.95 | 0.219080E+10 | 0.117902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.306548E+11 | 0.635232E+10 | 0.641577E+11 | 0.160314E+10 | 0.143835E+11 | 1296568.36 | 0.772077E+09 | 0.346569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287368E+11 | 0.675985E+10 | 0.631525E+11 | 0.155594E+10 | 0.157077E+11 | 1299182.41 | 65327183.29 | 0.468333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320519E+11 | 0.771793E+10 | 0.666107E+11 | 0.166662E+10 | 0.159237E+11 | 1343621.24 | 0.204142E+09 | 0.446746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288535E+11 | 0.875979E+10 | 0.619118E+11 | 0.153080E+10 | 0.105557E+11 | 1267813.82 | 0.289508E+10 | 0.184109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.302260E+11 | 0.104920E+11 | 0.641717E+11 | 0.159052E+10 | 0.604600E+10 | 1312252.65 | 0.117763E+11 | 0.121102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304252E+11 | 0.113967E+11 | 0.627379E+11 | 0.156209E+10 | 0.625648E+10 | 1278270.02 | 0.524914E+11 | 46592039.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301588E+11 | 0.124836E+11 | 0.631380E+11 | 0.155751E+10 | 0.704626E+10 | 1299182.41 | 0.998566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361583E+12 | 0.110888E+12 | 0.762041E+12 | 0.189236E+11 | 0.112306E+12 | 15535293.87 | 0.453693E+12 | 0.162284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.276110E+11 | 0.635232E+10 | 0.580684E+11 | 0.143941E+10 | 0.604600E+10 | 1186778.30 | 65327183.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.323700E+11 | 0.124836E+11 | 0.666107E+11 | 0.166685E+10 | 0.159237E+11 | 1343621.24 | 0.130844E+12 | 0.468333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.110609E+12 | 0.00 | 0.104428E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.726040E+11 | 0.00 | 0.956463E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.383713E+11 | 0.00 | 0.109479E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.127898E+11 | 0.00 | 0.986462E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.317820E+09 | 0.00 | 0.100263E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7419452.31 | 0.00 | 0.945071E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.894961E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.933543E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.801050E+09 | 0.00 | 0.873736E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.574063E+10 | 0.00 | 0.929731E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.366825E+11 | 0.00 | 0.946868E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.787785E+11 | 0.00 | 0.994643E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.356702E+12 | 0.00 | 0.116032E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.873736E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.110609E+12 | 0.00 | 0.109479E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36137.71 | 02-JAN-16:40 | 8467.87 | 01-JAN-06:10 | 47562.27 | 02-JAN-08:09 | 1358.60 | 02-JAN-16:49 | 7784.07 | 30-JAN-07:10 | 0.73 | 02-JAN-06:10 | 222033.68 | 02-JAN-07:10 |
February | 33942.45 | 14-FEB-16:00 | 8467.87 | 01-FEB-06:10 | 47562.27 | 01-FEB-08:09 | 1354.14 | 22-FEB-08:20 | 7369.69 | 06-FEB-07:10 | 0.73 | 01-FEB-06:10 | 213302.02 | 06-FEB-07:10 |
March | 32124.02 | 01-MAR-16:00 | 8467.87 | 01-MAR-06:10 | 47562.27 | 01-MAR-08:09 | 1350.96 | 14-MAR-07:19 | 6553.01 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 191882.24 | 06-MAR-07:10 |
April | 31550.47 | 10-APR-07:10 | 8467.87 | 01-APR-05:10 | 47562.27 | 03-APR-07:10 | 1351.12 | 10-APR-07:19 | 22294.97 | 18-APR-15:09 | 0.73 | 03-APR-06:10 | 158310.75 | 03-APR-06:10 |
May | 30486.53 | 01-MAY-07:10 | 8467.87 | 01-MAY-19:10 | 47562.27 | 01-MAY-07:10 | 1348.89 | 01-MAY-07:19 | 24588.02 | 31-MAY-15:09 | 0.73 | 02-MAY-07:10 | 52823.76 | 02-MAY-06:10 |
June | 30486.53 | 01-JUN-07:10 | 8467.87 | 01-JUN-19:40 | 47562.27 | 01-JUN-07:10 | 1348.89 | 01-JUN-07:19 | 32225.62 | 26-JUN-15:30 | 0.73 | 25-JUN-16:40 | 26848.85 | 05-JUN-06:10 |
July | 30486.53 | 03-JUL-07:10 | 8467.87 | 01-JUL-19:00 | 47562.27 | 03-JUL-07:10 | 1348.89 | 03-JUL-07:19 | 31671.89 | 03-JUL-15:09 | 0.73 | 01-JUL-05:10 | 6849.69 | 24-JUL-06:10 |
August | 30486.53 | 01-AUG-07:10 | 8467.87 | 01-AUG-19:40 | 47562.27 | 01-AUG-07:10 | 1348.89 | 01-AUG-07:30 | 29221.59 | 04-AUG-15:20 | 0.73 | 01-AUG-05:10 | 11300.46 | 07-AUG-06:19 |
September | 31559.60 | 21-SEP-07:10 | 8467.87 | 01-SEP-05:10 | 47562.27 | 01-SEP-07:10 | 1351.14 | 21-SEP-07:19 | 25797.81 | 07-SEP-15:00 | 0.73 | 25-SEP-07:10 | 62503.69 | 30-SEP-06:10 |
October | 35380.64 | 31-OCT-07:10 | 8467.87 | 01-OCT-05:10 | 47562.27 | 02-OCT-07:10 | 1359.16 | 31-OCT-07:19 | 9913.85 | 20-OCT-15:09 | 0.73 | 06-OCT-07:10 | 88247.00 | 16-OCT-06:10 |
November | 36137.71 | 06-NOV-16:00 | 8467.87 | 01-NOV-05:10 | 47562.27 | 01-NOV-07:10 | 1359.99 | 03-NOV-07:19 | 7264.84 | 03-NOV-15:09 | 0.73 | 09-NOV-18:10 | 202951.07 | 27-NOV-07:10 |
December | 36137.71 | 01-DEC-16:30 | 8467.87 | 01-DEC-06:10 | 47562.27 | 01-DEC-08:09 | 1358.78 | 22-DEC-08:20 | 7623.03 | 11-DEC-07:10 | 0.73 | 01-DEC-07:10 | 215031.61 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 30486.53 | 8467.87 | 47562.27 | 1348.89 | 6553.01 | 0.73 | 6849.69 | |||||||
Maximum of Months | 36137.71 | 8467.87 | 47562.27 | 1359.99 | 32225.62 | 0.73 | 222033.68 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7344.94 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 51808.78 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53978.31 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80874.99 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76995.19 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86319.64 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64928.39 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22238.00 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3960.84 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86319.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 272527.51 | 02-JAN-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7754.88 | 0.73 | 222033.68 | 0.00 | 0.00 |
February | 263410.66 | 06-FEB-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7369.69 | 0.73 | 213302.02 | 0.00 | 0.00 |
March | 231585.27 | 06-MAR-07:10 | 10924.90 | 21853.28 | 0.00 | 371.12 | 6553.01 | 0.73 | 191882.24 | 0.00 | 0.00 |
April | 196768.87 | 03-APR-06:10 | 10806.97 | 21853.28 | 0.00 | 371.12 | 5426.04 | 0.73 | 158310.75 | 0.00 | 0.00 |
May | 153828.53 | 31-MAY-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 24588.02 | 0.73 | 0.00 | 53636.51 | 0.00 |
June | 180491.06 | 26-JUN-07:49 | 30486.53 | 47562.27 | 0.00 | 1348.89 | 20217.65 | 0.73 | 0.00 | 80874.99 | 0.00 |
July | 179364.59 | 03-JUL-15:09 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 31671.89 | 0.73 | 0.00 | 72088.71 | 0.00 |
August | 190905.71 | 04-AUG-15:30 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 28982.08 | 0.73 | 0.00 | 86319.64 | 0.00 |
September | 161528.92 | 07-SEP-15:00 | 30486.53 | 43769.98 | 0.00 | 1346.75 | 25797.81 | 0.73 | 0.00 | 60127.12 | 0.00 |
October | 135400.89 | 16-OCT-06:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 4414.94 | 0.73 | 88247.00 | 0.00 | 0.00 |
November | 252553.94 | 27-NOV-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 6863.93 | 0.73 | 202951.07 | 0.00 | 0.00 |
December | 265393.59 | 11-DEC-07:10 | 12045.75 | 21853.28 | 8467.87 | 371.32 | 7623.03 | 0.73 | 215031.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 135400.89 | 10806.97 | 21853.28 | 0.00 | 371.12 | 4414.94 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 272527.51 | 30486.53 | 47562.27 | 8467.87 | 1348.89 | 31671.89 | 0.73 | 222033.68 | 86319.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 158248.46 | 31-JAN-07:00 | 0.00 | 11924.34 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 185182.10 | 02-FEB-07:30 | 0.00 | 12053.54 | 21-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 85416.36 | 06-MAR-07:30 | 0.00 | 12010.64 | 02-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 63644.50 | 03-APR-06:40 | 0.00 | 11267.68 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 20157.61 | 02-MAY-06:19 | 0.00 | 9907.95 | 03-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 2238.63 | 03-JUN-06:10 | 0.00 | 9398.33 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9242.21 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9162.57 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 28998.88 | 30-SEP-06:19 | 0.00 | 9217.61 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 41810.07 | 23-OCT-06:19 | 0.00 | 9345.49 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 115801.99 | 25-NOV-17:00 | 0.00 | 9507.36 | 29-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 127999.67 | 09-DEC-07:19 | 0.00 | 10881.41 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9162.57 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 185182.10 | 0.00 | 12053.54 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.20 | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.42 | 0.67 | 25.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.20 | 0.17 | 19.20 | 1.00 | 23.87 | 0.67 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.20 | 0.17 | 19.20 | 1.00 | 25.42 | 0.67 | 25.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 18.66 | 1.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 0.17 | 19.31 | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.33 | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
December | 0.33 | 19.19 | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 2.33 | 18.83 | 1.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.33 | 1.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.36 | 2.83 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 2.50 | 18.42 | 1.67 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
March | 0.50 | 18.53 | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
April | 0.33 | 17.94 | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 18.46 | 1.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
December | 2.67 | 18.20 | 1.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
Annual Sum or Average | 12.00 | 18.34 | 7.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 18.53 | 2.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.83 | 15.95 | 55.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
February | 59.00 | 16.25 | 28.67 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
March | 19.33 | 15.86 | 6.83 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
April | 3.50 | 15.58 | 0.50 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 1.33 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
November | 29.83 | 15.74 | 11.00 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
December | 60.83 | 15.78 | 26.00 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
Annual Sum or Average | 287.50 | 15.94 | 128.00 | 16.40 | 2.17 | 16.46 | 1.33 | 16.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.83 | 17.19 | 55.00 | 17.19 | 2.17 | 27.39 | 1.33 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.50 | 14.54 | 21.67 | 14.61 | 0.00 | 14.61 | 0.00 | 14.61 |
February | 33.67 | 14.70 | 6.83 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
March | 12.83 | 15.03 | 1.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
April | 3.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.62 | 0.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.04 | 4.83 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.11 | 4.83 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.59 | 1.17 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
October | 0.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
November | 23.67 | 14.67 | 4.83 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
December | 45.50 | 14.66 | 11.17 | 14.68 | 0.00 | 14.68 | 0.00 | 14.68 |
Annual Sum or Average | 192.50 | 14.65 | 45.67 | 14.70 | 12.83 | 15.38 | 12.83 | 15.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 0.00 | 14.61 |
Maximum of Months | 73.50 | 17.22 | 21.67 | 17.22 | 4.83 | 28.11 | 4.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.00 | 14.91 | 16.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
February | 30.67 | 15.35 | 7.67 | 15.75 | 0.00 | 15.75 | 0.00 | 15.75 |
March | 11.83 | 15.38 | 1.17 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
April | 3.00 | 15.12 | 0.17 | 15.34 | 1.33 | 19.08 | 1.33 | 21.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.82 | 3.67 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.94 | 3.17 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.05 | 3.67 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18.17 | 14.87 | 4.33 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
December | 37.00 | 15.04 | 10.00 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
Annual Sum or Average | 164.67 | 15.05 | 39.50 | 15.28 | 13.33 | 16.05 | 13.17 | 16.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.00 | 15.38 | 16.17 | 15.75 | 3.83 | 28.05 | 3.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.00 | 14.45 | 19.83 | 14.48 | 0.00 | 14.48 | 0.00 | 14.48 |
February | 33.50 | 14.60 | 7.67 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
March | 12.83 | 15.03 | 1.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
April | 3.33 | 15.03 | 0.17 | 15.03 | 1.33 | 18.75 | 0.83 | 20.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.98 | 1.00 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.63 | 2.83 | 28.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.35 | 3.67 | 28.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.96 | 1.17 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.33 | 27.75 |
October | 0.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
November | 23.00 | 14.62 | 5.17 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
December | 42.67 | 14.56 | 10.50 | 14.56 | 0.00 | 14.56 | 0.00 | 14.56 |
Annual Sum or Average | 185.67 | 14.58 | 45.17 | 14.59 | 20.67 | 15.71 | 11.83 | 16.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 0.00 | 14.48 |
Maximum of Months | 70.00 | 17.19 | 19.83 | 17.19 | 7.83 | 28.63 | 3.67 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.67 | 17.93 | 52.17 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
February | 52.67 | 18.06 | 37.83 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
March | 7.67 | 17.42 | 3.83 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
April | 0.50 | 18.73 | 0.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.61 | 0.33 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9.67 | 16.90 | 4.83 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
December | 23.33 | 17.19 | 14.00 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
Annual Sum or Average | 167.50 | 17.79 | 113.00 | 18.27 | 0.33 | 18.27 | 0.33 | 18.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.67 | 18.73 | 52.17 | 19.14 | 0.33 | 24.61 | 0.33 | 24.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.83 | 15.27 | 5.83 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
February | 13.67 | 15.30 | 1.67 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
March | 2.83 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
April | 0.17 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.67 | 1.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 2.67 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.85 | 0.33 | 24.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.50 | 15.23 | 0.83 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
December | 9.83 | 15.18 | 1.67 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 56.83 | 15.29 | 10.00 | 15.38 | 5.33 | 16.28 | 5.33 | 17.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.83 | 16.65 | 5.83 | 16.65 | 2.67 | 27.77 | 2.67 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.33 | 15.48 | 182.67 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
February | 123.33 | 15.45 | 115.00 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
March | 82.50 | 16.54 | 81.33 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
April | 46.33 | 17.67 | 46.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
May | 10.67 | 19.19 | 10.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
June | 2.00 | 19.66 | 2.00 | 19.66 | 1.83 | 21.26 | 1.83 | 22.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.00 | 1.83 | 25.00 |
September | 8.33 | 18.97 | 8.33 | 18.97 | 16.00 | 22.19 | 16.00 | 23.29 |
October | 29.00 | 18.66 | 29.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
November | 67.33 | 16.50 | 65.17 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
December | 125.83 | 15.60 | 116.33 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
Annual Sum or Average | 696.67 | 16.11 | 656.67 | 16.14 | 20.83 | 16.28 | 20.83 | 16.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 0.00 | 15.46 |
Maximum of Months | 201.33 | 19.66 | 182.67 | 19.66 | 16.00 | 27.43 | 16.00 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.17 | 15.23 | 5.83 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
February | 13.83 | 15.37 | 2.67 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 2.33 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
April | 0.17 | 16.60 | 0.00 | 16.60 | 0.50 | 24.73 | 0.33 | 25.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.97 | 1.50 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 2.33 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 0.50 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.69 | 0.67 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.83 | 15.20 | 1.17 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
December | 11.17 | 15.12 | 3.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
Annual Sum or Average | 58.50 | 15.27 | 12.67 | 15.33 | 11.17 | 17.02 | 5.33 | 17.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.17 | 16.60 | 5.83 | 16.60 | 5.50 | 27.97 | 2.33 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.33 | 16.62 | 35.67 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
February | 35.67 | 16.87 | 18.50 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
March | 6.67 | 16.90 | 2.33 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
April | 0.33 | 17.93 | 0.17 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.83 | 16.08 | 6.67 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
December | 36.67 | 16.32 | 17.83 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
Annual Sum or Average | 164.50 | 16.57 | 81.17 | 17.08 | 0.17 | 17.09 | 0.00 | 17.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 70.33 | 17.93 | 35.67 | 18.37 | 0.17 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.50 | 14.89 | 8.33 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
February | 17.17 | 14.90 | 1.67 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 4.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
April | 0.17 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.28 | 2.83 | 28.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.23 | 4.17 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.78 | 1.33 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.83 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 14.89 | 2.50 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
December | 22.17 | 14.93 | 4.17 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
Annual Sum or Average | 95.33 | 14.93 | 16.67 | 14.94 | 11.50 | 16.16 | 11.50 | 17.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.50 | 16.54 | 8.33 | 16.54 | 4.17 | 28.28 | 4.17 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.17 | 15.17 | 5.33 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
February | 13.33 | 15.29 | 1.50 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
March | 2.50 | 15.85 | 0.17 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
April | 0.17 | 16.62 | 0.00 | 16.62 | 1.50 | 26.58 | 1.50 | 27.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.70 | 2.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.74 | 3.17 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.98 | 3.83 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
November | 9.17 | 15.23 | 2.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
December | 16.50 | 15.19 | 2.83 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
Annual Sum or Average | 72.83 | 15.23 | 12.17 | 15.37 | 13.17 | 17.03 | 13.17 | 18.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.17 | 16.62 | 5.33 | 16.62 | 3.83 | 27.98 | 3.83 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.50 | 14.89 | 9.17 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
February | 17.83 | 14.91 | 2.17 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
March | 3.00 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
April | 0.17 | 16.52 | 0.00 | 16.52 | 1.67 | 27.00 | 1.17 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.94 | 1.17 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.43 | 2.50 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.26 | 3.33 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.93 | 1.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.70 | 1.83 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.17 | 14.87 | 3.17 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
December | 22.83 | 14.90 | 5.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
Annual Sum or Average | 96.50 | 14.91 | 19.83 | 14.92 | 19.33 | 16.80 | 11.33 | 17.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.50 | 16.52 | 9.17 | 16.52 | 7.17 | 28.43 | 3.33 | 28.42 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.46 | 261.00 | 21.19 | 261.00 | 21.06 |
February | 454.00 | 22.21 | 84.67 | 21.98 | 84.67 | 21.82 |
March | 497.33 | 23.08 | 10.17 | 23.03 | 10.17 | 22.99 |
April | 353.00 | 23.50 | 43.83 | 23.62 | 0.33 | 23.61 |
May | 65.17 | 23.82 | 283.00 | 24.40 | 0.00 | 24.40 |
June | 3.50 | 23.60 | 441.67 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 490.33 | 24.42 | 0.00 | 24.42 |
August | 1.33 | 24.63 | 504.33 | 24.37 | 1.33 | 24.37 |
September | 51.50 | 23.75 | 271.83 | 24.44 | 0.00 | 24.44 |
October | 333.00 | 23.83 | 23.50 | 23.91 | 0.00 | 23.91 |
November | 393.83 | 22.96 | 50.33 | 22.82 | 36.83 | 22.66 |
December | 497.00 | 22.16 | 91.17 | 21.94 | 91.17 | 21.78 |
Annual Sum or Average | 3151.67 | 22.69 | 2555.83 | 23.16 | 485.50 | 22.97 |
Minimum of Months | 0.00 | 0.00 | 10.17 | 21.19 | 0.00 | 21.06 |
Maximum of Months | 502.00 | 24.63 | 504.33 | 24.44 | 261.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.55 | 437.83 | 20.47 | 437.83 | 20.44 |
February | 454.00 | 21.02 | 273.00 | 20.84 | 273.00 | 20.76 |
March | 514.00 | 21.90 | 124.33 | 21.66 | 124.33 | 21.51 |
April | 407.83 | 22.51 | 63.17 | 22.51 | 32.50 | 22.40 |
May | 179.00 | 23.41 | 179.17 | 23.82 | 0.00 | 23.82 |
June | 43.83 | 23.30 | 372.67 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 468.67 | 24.31 | 0.00 | 24.31 |
August | 0.67 | 24.11 | 475.17 | 24.24 | 0.67 | 24.24 |
September | 152.33 | 23.36 | 185.33 | 23.93 | 0.00 | 23.93 |
October | 486.17 | 22.91 | 0.17 | 22.91 | 0.17 | 22.90 |
November | 476.33 | 21.79 | 158.83 | 21.49 | 158.83 | 21.31 |
December | 497.00 | 20.88 | 339.17 | 20.71 | 339.17 | 20.64 |
Annual Sum or Average | 3713.17 | 21.81 | 3077.50 | 22.17 | 1366.50 | 21.89 |
Minimum of Months | 0.00 | 0.00 | 0.17 | 20.47 | 0.00 | 20.44 |
Maximum of Months | 514.00 | 24.11 | 475.17 | 24.31 | 437.83 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 472.83 | 20.10 | 472.83 | 20.09 |
February | 454.00 | 20.49 | 350.83 | 20.36 | 350.83 | 20.30 |
March | 514.00 | 21.32 | 237.00 | 21.08 | 237.00 | 20.95 |
April | 416.50 | 21.89 | 118.50 | 21.76 | 88.17 | 21.55 |
May | 246.67 | 23.10 | 146.50 | 23.48 | 0.17 | 23.48 |
June | 85.17 | 23.03 | 346.00 | 24.00 | 0.00 | 24.00 |
July | 13.67 | 23.42 | 440.00 | 24.25 | 0.00 | 24.25 |
August | 21.33 | 23.30 | 418.17 | 24.15 | 0.00 | 24.15 |
September | 221.00 | 22.81 | 158.33 | 23.39 | 4.50 | 23.36 |
October | 497.00 | 21.97 | 74.83 | 21.78 | 74.83 | 21.63 |
November | 489.00 | 21.01 | 260.17 | 20.70 | 260.17 | 20.55 |
December | 497.00 | 20.32 | 455.33 | 20.26 | 455.33 | 20.23 |
Annual Sum or Average | 3957.33 | 21.30 | 3478.50 | 21.62 | 1943.83 | 21.33 |
Minimum of Months | 13.67 | 20.15 | 74.83 | 20.10 | 0.00 | 20.09 |
Maximum of Months | 514.00 | 23.42 | 472.83 | 24.25 | 472.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.58 | 500.33 | 19.58 | 500.33 | 19.57 |
February | 454.00 | 19.75 | 441.00 | 19.73 | 441.00 | 19.73 |
March | 514.00 | 20.46 | 391.83 | 20.35 | 391.83 | 20.31 |
April | 437.33 | 20.91 | 232.83 | 20.79 | 204.00 | 20.61 |
May | 326.33 | 22.33 | 134.67 | 22.73 | 17.17 | 22.64 |
June | 147.00 | 22.86 | 324.50 | 23.83 | 23.50 | 23.90 |
July | 72.00 | 23.75 | 414.67 | 24.18 | 29.33 | 24.22 |
August | 121.83 | 23.14 | 354.17 | 23.85 | 25.33 | 23.87 |
September | 303.17 | 21.95 | 169.00 | 22.48 | 36.83 | 22.35 |
October | 502.00 | 20.79 | 233.17 | 20.56 | 233.17 | 20.44 |
November | 489.00 | 20.04 | 357.83 | 19.85 | 357.83 | 19.77 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4365.67 | 20.69 | 4051.00 | 20.98 | 2757.33 | 20.73 |
Minimum of Months | 72.00 | 19.58 | 134.67 | 19.58 | 17.17 | 19.57 |
Maximum of Months | 514.00 | 23.75 | 500.33 | 24.18 | 500.33 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 492.33 | 19.66 | 492.33 | 19.66 |
February | 454.00 | 19.86 | 414.33 | 19.80 | 414.33 | 19.78 |
March | 512.67 | 20.60 | 324.33 | 20.41 | 324.33 | 20.33 |
April | 411.50 | 21.10 | 209.33 | 21.10 | 160.83 | 20.90 |
May | 277.67 | 22.23 | 167.17 | 22.98 | 16.50 | 22.99 |
June | 164.00 | 22.91 | 329.00 | 23.82 | 33.17 | 23.96 |
July | 95.50 | 24.38 | 407.00 | 24.35 | 47.17 | 24.50 |
August | 126.67 | 23.03 | 358.67 | 23.82 | 21.17 | 23.88 |
September | 266.50 | 21.87 | 199.83 | 22.73 | 31.67 | 22.64 |
October | 499.33 | 20.95 | 165.67 | 20.74 | 165.67 | 20.61 |
November | 489.00 | 20.09 | 346.00 | 19.92 | 346.00 | 19.85 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4295.83 | 20.77 | 3910.67 | 21.12 | 2550.17 | 20.88 |
Minimum of Months | 95.50 | 19.68 | 165.67 | 19.66 | 16.50 | 19.66 |
Maximum of Months | 512.67 | 24.38 | 497.00 | 24.35 | 497.00 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 19.88 | 433.17 | 19.73 | 433.17 | 19.67 |
February | 440.00 | 20.19 | 353.17 | 20.02 | 347.50 | 19.94 |
March | 470.00 | 20.76 | 302.17 | 20.60 | 290.17 | 20.48 |
April | 378.50 | 21.10 | 225.33 | 21.20 | 163.17 | 20.99 |
May | 293.00 | 22.16 | 160.83 | 22.81 | 19.00 | 22.75 |
June | 178.50 | 22.76 | 298.83 | 23.68 | 28.67 | 23.78 |
July | 108.17 | 23.78 | 391.00 | 24.19 | 38.83 | 24.31 |
August | 131.83 | 23.16 | 358.33 | 23.91 | 31.33 | 23.99 |
September | 253.17 | 22.19 | 222.00 | 23.07 | 40.50 | 23.07 |
October | 405.83 | 21.14 | 192.17 | 21.20 | 142.00 | 21.00 |
November | 471.00 | 20.43 | 301.50 | 20.22 | 289.67 | 20.08 |
December | 486.83 | 20.11 | 420.33 | 19.94 | 420.33 | 19.88 |
Annual Sum or Average | 4112.83 | 20.98 | 3658.83 | 21.32 | 2244.33 | 21.06 |
Minimum of Months | 108.17 | 19.88 | 160.83 | 19.73 | 19.00 | 19.67 |
Maximum of Months | 496.00 | 23.78 | 433.17 | 24.19 | 433.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 492.67 | 19.67 | 492.67 | 19.67 |
February | 452.83 | 19.94 | 413.50 | 19.87 | 413.50 | 19.85 |
March | 508.00 | 20.58 | 352.83 | 20.42 | 351.50 | 20.35 |
April | 406.33 | 20.96 | 226.17 | 20.98 | 177.83 | 20.80 |
May | 349.00 | 21.93 | 138.83 | 22.47 | 22.33 | 22.45 |
June | 184.00 | 22.44 | 291.83 | 23.52 | 26.83 | 23.61 |
July | 132.67 | 23.51 | 364.67 | 24.08 | 42.50 | 24.23 |
August | 157.50 | 22.66 | 319.50 | 23.63 | 22.17 | 23.71 |
September | 316.67 | 21.78 | 175.33 | 22.45 | 45.17 | 22.41 |
October | 481.67 | 20.84 | 213.83 | 20.65 | 204.17 | 20.51 |
November | 484.83 | 20.08 | 341.00 | 19.90 | 340.83 | 19.82 |
December | 497.00 | 19.76 | 484.00 | 19.74 | 484.00 | 19.73 |
Annual Sum or Average | 4472.50 | 20.76 | 3814.17 | 21.03 | 2623.50 | 20.80 |
Minimum of Months | 132.67 | 19.69 | 138.83 | 19.67 | 22.17 | 19.67 |
Maximum of Months | 508.00 | 23.51 | 492.67 | 24.08 | 492.67 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.64 | 502.00 | 19.64 | 502.00 | 19.64 |
February | 454.00 | 19.91 | 449.67 | 19.91 | 449.67 | 19.91 |
March | 514.00 | 20.52 | 407.17 | 20.45 | 407.17 | 20.42 |
April | 470.00 | 21.03 | 244.17 | 20.85 | 235.17 | 20.73 |
May | 406.67 | 22.48 | 73.33 | 22.65 | 13.17 | 22.60 |
June | 138.50 | 22.99 | 287.33 | 23.81 | 15.67 | 23.84 |
July | 33.17 | 24.17 | 433.17 | 24.23 | 15.33 | 24.26 |
August | 46.33 | 23.74 | 415.17 | 24.11 | 17.33 | 24.12 |
September | 239.33 | 22.66 | 158.00 | 23.25 | 4.33 | 23.22 |
October | 502.00 | 21.64 | 81.67 | 21.49 | 81.67 | 21.38 |
November | 489.00 | 20.71 | 296.00 | 20.46 | 296.00 | 20.35 |
December | 497.00 | 19.97 | 497.00 | 19.97 | 497.00 | 19.97 |
Annual Sum or Average | 4292.00 | 20.95 | 3844.67 | 21.21 | 2534.50 | 20.95 |
Minimum of Months | 33.17 | 19.64 | 73.33 | 19.64 | 4.33 | 19.64 |
Maximum of Months | 514.00 | 24.17 | 502.00 | 24.23 | 502.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 495.50 | 19.78 | 495.50 | 19.78 |
February | 454.00 | 20.09 | 425.50 | 20.06 | 425.50 | 20.05 |
March | 514.00 | 20.69 | 349.83 | 20.56 | 349.83 | 20.51 |
April | 445.17 | 21.23 | 188.50 | 21.12 | 162.17 | 20.96 |
May | 327.50 | 22.39 | 121.83 | 23.03 | 5.67 | 23.04 |
June | 135.50 | 22.86 | 328.83 | 23.87 | 18.17 | 23.96 |
July | 49.83 | 25.01 | 440.67 | 24.43 | 31.00 | 24.54 |
August | 48.00 | 23.70 | 429.83 | 24.14 | 14.00 | 24.18 |
September | 218.67 | 22.54 | 214.00 | 23.46 | 6.17 | 23.46 |
October | 495.83 | 21.74 | 39.67 | 21.64 | 39.67 | 21.56 |
November | 489.00 | 20.68 | 292.33 | 20.49 | 292.33 | 20.40 |
December | 497.00 | 20.04 | 497.00 | 20.04 | 497.00 | 20.04 |
Annual Sum or Average | 4176.50 | 21.01 | 3823.50 | 21.39 | 2337.00 | 21.14 |
Minimum of Months | 48.00 | 19.79 | 39.67 | 19.78 | 5.67 | 19.78 |
Maximum of Months | 514.00 | 25.01 | 497.00 | 24.43 | 497.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.97 | 487.00 | 17.93 | 487.00 | 17.91 |
February | 454.00 | 18.99 | 394.33 | 18.82 | 394.33 | 18.76 |
March | 507.33 | 20.08 | 339.33 | 19.82 | 339.33 | 19.70 |
April | 434.83 | 20.76 | 232.33 | 20.64 | 199.00 | 20.43 |
May | 403.00 | 21.86 | 93.50 | 22.24 | 17.00 | 22.17 |
June | 246.17 | 22.52 | 257.67 | 23.35 | 63.17 | 23.40 |
July | 152.33 | 23.52 | 403.83 | 24.05 | 97.33 | 24.06 |
August | 136.50 | 23.39 | 430.67 | 24.03 | 88.50 | 24.03 |
September | 230.83 | 22.27 | 227.33 | 23.37 | 26.00 | 23.41 |
October | 428.17 | 21.60 | 79.50 | 21.66 | 42.00 | 21.48 |
November | 465.50 | 20.17 | 269.67 | 19.86 | 260.67 | 19.67 |
December | 494.17 | 19.02 | 436.83 | 18.88 | 436.83 | 18.83 |
Annual Sum or Average | 4454.83 | 20.47 | 3652.00 | 20.72 | 2451.17 | 20.40 |
Minimum of Months | 136.50 | 17.97 | 79.50 | 17.93 | 17.00 | 17.91 |
Maximum of Months | 507.33 | 23.52 | 487.00 | 24.05 | 487.00 | 24.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 494.17 | 19.78 | 494.17 | 19.78 |
February | 454.00 | 20.15 | 425.50 | 20.11 | 425.50 | 20.09 |
March | 514.00 | 20.67 | 359.33 | 20.56 | 359.33 | 20.51 |
April | 435.83 | 21.16 | 195.00 | 21.08 | 165.33 | 20.91 |
May | 388.00 | 22.12 | 90.83 | 22.50 | 10.17 | 22.46 |
June | 164.83 | 22.65 | 296.83 | 23.69 | 15.83 | 23.76 |
July | 62.33 | 24.36 | 423.33 | 24.35 | 26.67 | 24.45 |
August | 57.17 | 23.57 | 424.17 | 24.14 | 15.33 | 24.18 |
September | 243.50 | 22.33 | 195.17 | 23.21 | 10.50 | 23.21 |
October | 479.00 | 21.56 | 64.17 | 21.50 | 55.50 | 21.40 |
November | 485.50 | 20.65 | 285.17 | 20.45 | 285.00 | 20.36 |
December | 497.00 | 20.04 | 485.50 | 20.03 | 485.50 | 20.02 |
Annual Sum or Average | 4283.17 | 20.98 | 3739.17 | 21.33 | 2348.83 | 21.08 |
Minimum of Months | 57.17 | 19.79 | 64.17 | 19.78 | 10.17 | 19.78 |
Maximum of Months | 514.00 | 24.36 | 494.17 | 24.35 | 494.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 496.17 | 19.68 | 496.17 | 19.67 |
February | 454.00 | 19.96 | 420.33 | 19.91 | 420.33 | 19.90 |
March | 514.00 | 20.73 | 331.67 | 20.57 | 331.67 | 20.50 |
April | 424.67 | 21.31 | 172.67 | 21.21 | 138.50 | 21.02 |
May | 267.00 | 22.83 | 160.67 | 23.30 | 3.67 | 23.28 |
June | 91.17 | 23.23 | 365.33 | 24.07 | 16.67 | 24.12 |
July | 33.17 | 24.79 | 459.50 | 24.35 | 24.50 | 24.39 |
August | 47.83 | 23.82 | 426.50 | 24.12 | 20.33 | 24.14 |
September | 247.17 | 22.46 | 169.67 | 23.11 | 10.00 | 23.05 |
October | 499.50 | 21.43 | 120.67 | 21.21 | 120.67 | 21.07 |
November | 489.00 | 20.51 | 307.17 | 20.24 | 307.17 | 20.12 |
December | 497.00 | 19.87 | 497.00 | 19.87 | 497.00 | 19.87 |
Annual Sum or Average | 4066.50 | 20.90 | 3927.33 | 21.29 | 2386.67 | 21.01 |
Minimum of Months | 33.17 | 19.68 | 120.67 | 19.68 | 3.67 | 19.67 |
Maximum of Months | 514.00 | 24.79 | 497.00 | 24.35 | 497.00 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.54 | 416.33 | 19.53 | 416.33 | 19.52 |
February | 385.00 | 19.90 | 350.00 | 19.84 | 350.00 | 19.82 |
March | 431.00 | 20.72 | 250.50 | 20.52 | 250.50 | 20.43 |
April | 339.50 | 21.21 | 143.50 | 21.27 | 102.67 | 21.07 |
May | 247.50 | 22.55 | 138.50 | 23.26 | 12.33 | 23.34 |
June | 124.67 | 23.08 | 276.17 | 23.98 | 24.50 | 24.12 |
July | 64.67 | 24.92 | 354.00 | 24.48 | 38.50 | 24.64 |
August | 86.33 | 23.36 | 302.50 | 23.99 | 20.33 | 24.07 |
September | 224.17 | 22.24 | 156.83 | 23.09 | 18.00 | 23.11 |
October | 422.17 | 21.31 | 83.17 | 21.16 | 82.00 | 21.05 |
November | 417.00 | 20.33 | 270.50 | 20.13 | 270.50 | 20.04 |
December | 422.00 | 19.75 | 420.17 | 19.75 | 420.17 | 19.75 |
Annual Sum or Average | 3591.00 | 20.89 | 3162.17 | 21.24 | 2005.83 | 20.99 |
Minimum of Months | 64.67 | 19.54 | 83.17 | 19.53 | 12.33 | 19.52 |
Maximum of Months | 431.00 | 24.92 | 420.17 | 24.48 | 420.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 20.09 | 415.00 | 19.90 | 415.00 | 19.83 |
February | 439.17 | 20.55 | 317.50 | 20.33 | 311.83 | 20.22 |
March | 463.00 | 21.07 | 254.83 | 20.90 | 241.50 | 20.76 |
April | 364.50 | 21.41 | 179.50 | 21.60 | 111.50 | 21.40 |
May | 249.33 | 22.55 | 177.33 | 23.27 | 6.17 | 23.27 |
June | 136.83 | 23.13 | 322.67 | 23.94 | 22.83 | 24.04 |
July | 64.17 | 24.45 | 428.50 | 24.34 | 31.17 | 24.45 |
August | 77.17 | 23.72 | 413.17 | 24.15 | 25.83 | 24.22 |
September | 221.83 | 22.69 | 228.67 | 23.57 | 23.00 | 23.65 |
October | 386.17 | 21.70 | 117.83 | 21.93 | 56.83 | 21.79 |
November | 458.67 | 20.84 | 255.33 | 20.62 | 239.50 | 20.44 |
December | 477.67 | 20.35 | 403.00 | 20.19 | 400.83 | 20.12 |
Annual Sum or Average | 3832.17 | 21.23 | 3513.33 | 21.67 | 1886.00 | 21.39 |
Minimum of Months | 64.17 | 20.09 | 117.83 | 19.90 | 6.17 | 19.83 |
Maximum of Months | 493.67 | 24.45 | 428.50 | 24.34 | 415.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 489.17 | 19.76 | 489.17 | 19.75 |
February | 452.33 | 20.13 | 395.00 | 20.05 | 395.00 | 20.02 |
March | 502.67 | 20.77 | 303.00 | 20.61 | 301.50 | 20.53 |
April | 397.00 | 21.22 | 174.83 | 21.32 | 122.83 | 21.15 |
May | 323.17 | 22.29 | 139.00 | 22.87 | 9.33 | 22.88 |
June | 154.00 | 22.80 | 314.50 | 23.78 | 20.17 | 23.88 |
July | 94.50 | 24.07 | 400.67 | 24.27 | 37.50 | 24.41 |
August | 109.00 | 23.11 | 370.67 | 23.92 | 19.67 | 23.99 |
September | 285.67 | 22.11 | 168.00 | 22.87 | 20.67 | 22.88 |
October | 467.33 | 21.20 | 121.83 | 21.09 | 110.50 | 20.97 |
November | 483.67 | 20.42 | 300.50 | 20.22 | 299.50 | 20.13 |
December | 497.00 | 19.94 | 475.00 | 19.91 | 475.00 | 19.90 |
Annual Sum or Average | 4268.33 | 20.95 | 3652.17 | 21.28 | 2300.83 | 21.05 |
Minimum of Months | 94.50 | 19.77 | 121.83 | 19.76 | 9.33 | 19.75 |
Maximum of Months | 502.67 | 24.07 | 489.17 | 24.27 | 489.17 | 24.41 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.45713 | 13.69185 | -0.5372 | 12.54194 |
February | 454.00000 | 22.21029 | 17.45049 | -0.3201 | 8.51765 |
March | 514.00000 | 23.11720 | 21.99589 | -0.0512 | 6.17247 |
April | 485.00000 | 23.69788 | 28.50137 | 0.16432 | 6.46906 |
May | 508.00000 | 24.30595 | 40.73756 | -0.4391 | 9.75682 |
June | 496.00000 | 24.30594 | 47.84091 | -0.3360 | 7.81180 |
July | 497.00000 | 24.41468 | 51.99002 | -0.2589 | 6.90777 |
August | 514.00000 | 24.36242 | 50.91464 | -0.2802 | 7.08766 |
September | 485.00000 | 24.32061 | 37.48627 | -0.4201 | 9.52866 |
October | 502.00000 | 23.98894 | 27.13530 | 0.23349 | 6.38556 |
November | 489.00000 | 23.19379 | 23.75644 | -0.0125 | 7.12220 |
December | 497.00000 | 22.15774 | 15.83103 | -0.3413 | 8.65040 |
Annual Sum or Average | 5943.00000 | 23.47002 | 31.57421 | -0.2165 | 8.07496 |
Minimum of Months | 454.00000 | 21.45713 | 13.69185 | -0.5372 | 6.17247 |
Maximum of Months | 514.00000 | 24.41468 | 51.99002 | 0.23349 | 12.54194 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55041 | 14.34639 | -0.7601 | 18.90097 |
February | 454.00000 | 21.02432 | 18.61647 | -0.6005 | 14.02276 |
March | 514.00000 | 21.89799 | 23.76985 | -0.3336 | 8.90222 |
April | 485.00000 | 22.76742 | 30.80465 | -0.0506 | 7.12533 |
May | 508.00000 | 23.86829 | 42.58624 | -0.5924 | 13.27025 |
June | 496.00000 | 24.12755 | 49.21608 | -0.4146 | 9.24098 |
July | 497.00000 | 24.28510 | 53.07771 | -0.3216 | 7.51580 |
August | 514.00000 | 24.22182 | 52.10288 | -0.3535 | 7.90333 |
September | 485.00000 | 23.95459 | 39.19157 | -0.5714 | 13.36866 |
October | 502.00000 | 22.94097 | 30.09607 | -0.0208 | 5.81187 |
November | 489.00000 | 21.84481 | 26.04886 | -0.3365 | 10.24225 |
December | 497.00000 | 20.87549 | 16.95934 | -0.6491 | 15.25478 |
Annual Sum or Average | 5943.00000 | 22.70953 | 33.19873 | -0.4161 | 10.93725 |
Minimum of Months | 454.00000 | 20.55041 | 14.34639 | -0.7601 | 5.81187 |
Maximum of Months | 514.00000 | 24.28510 | 53.07771 | -0.0208 | 18.90097 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14836 | 14.64559 | -0.8897 | 24.02623 |
February | 454.00000 | 20.49220 | 19.15710 | -0.7566 | 19.22916 |
March | 514.00000 | 21.31944 | 24.38355 | -0.4910 | 11.90316 |
April | 485.00000 | 22.20183 | 31.58605 | -0.1908 | 9.04588 |
May | 508.00000 | 23.59303 | 43.12318 | -0.6852 | 16.52282 |
June | 496.00000 | 23.98374 | 49.56576 | -0.4584 | 10.69417 |
July | 497.00000 | 24.20800 | 53.25523 | -0.3428 | 7.89222 |
August | 514.00000 | 24.09392 | 52.43422 | -0.3966 | 8.67372 |
September | 485.00000 | 23.54421 | 40.08000 | -0.7182 | 18.66206 |
October | 502.00000 | 21.99164 | 31.35633 | -0.2535 | 7.85097 |
November | 489.00000 | 21.01167 | 26.55524 | -0.5581 | 15.05175 |
December | 497.00000 | 20.31656 | 17.22752 | -0.8190 | 21.17883 |
Annual Sum or Average | 5943.00000 | 22.25671 | 33.74378 | -0.5452 | 14.17698 |
Minimum of Months | 454.00000 | 20.14836 | 14.64559 | -0.8897 | 7.85097 |
Maximum of Months | 514.00000 | 24.20800 | 53.25523 | -0.1908 | 24.02623 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.57783 | 14.45600 | -1.1422 | 34.44729 |
February | 454.00000 | 19.75084 | 19.29516 | -1.0196 | 29.51074 |
March | 514.00000 | 20.45968 | 25.10659 | -0.7380 | 18.66260 |
April | 485.00000 | 21.22957 | 32.68777 | -0.4289 | 13.66548 |
May | 508.00000 | 22.93058 | 44.50587 | -0.8735 | 24.68704 |
June | 496.00000 | 23.74624 | 50.76320 | -0.4904 | 13.44051 |
July | 497.00000 | 24.09025 | 54.77361 | -0.3340 | 8.50229 |
August | 514.00000 | 23.80469 | 54.05465 | -0.4530 | 10.62761 |
September | 485.00000 | 22.76794 | 41.88264 | -0.9568 | 29.21365 |
October | 502.00000 | 20.79175 | 33.09768 | -0.5420 | 13.07375 |
November | 489.00000 | 20.03913 | 27.79467 | -0.8331 | 23.52596 |
December | 497.00000 | 19.68020 | 17.39248 | -1.0713 | 31.33914 |
Annual Sum or Average | 5943.00000 | 21.58893 | 34.78599 | -0.7379 | 20.80058 |
Minimum of Months | 454.00000 | 19.57783 | 14.45600 | -1.1422 | 8.50229 |
Maximum of Months | 514.00000 | 24.09025 | 54.77361 | -0.3340 | 34.44729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67659 | 14.07617 | -1.1005 | 32.70411 |
February | 454.00000 | 19.85997 | 18.86973 | -0.9642 | 27.39531 |
March | 514.00000 | 20.60404 | 24.42569 | -0.6670 | 17.06845 |
April | 485.00000 | 21.57695 | 31.64313 | -0.3117 | 12.71320 |
May | 508.00000 | 23.07621 | 43.85339 | -0.7418 | 21.54287 |
June | 496.00000 | 23.65831 | 50.48695 | -0.4216 | 13.90382 |
July | 497.00000 | 24.08683 | 54.28944 | -0.2318 | 8.74585 |
August | 514.00000 | 23.71817 | 53.80361 | -0.3888 | 10.43419 |
September | 485.00000 | 22.91209 | 41.04781 | -0.8253 | 26.26308 |
October | 502.00000 | 20.96652 | 32.34120 | -0.4699 | 11.25803 |
November | 489.00000 | 20.09220 | 27.35570 | -0.8080 | 22.24366 |
December | 497.00000 | 19.75613 | 16.91949 | -1.0418 | 30.07963 |
Annual Sum or Average | 5943.00000 | 21.68103 | 34.22853 | -0.6620 | 19.44469 |
Minimum of Months | 454.00000 | 19.67659 | 14.07617 | -1.1005 | 8.74585 |
Maximum of Months | 514.00000 | 24.08683 | 54.28944 | -0.2318 | 32.70411 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92865 | 13.86913 | -0.9678 | 28.96915 |
February | 454.00000 | 20.30883 | 18.24255 | -0.8006 | 23.22933 |
March | 514.00000 | 21.05531 | 23.71997 | -0.5424 | 15.65013 |
April | 485.00000 | 21.79354 | 31.13772 | -0.2567 | 13.31289 |
May | 508.00000 | 22.99610 | 43.99078 | -0.8040 | 23.51777 |
June | 496.00000 | 23.57613 | 50.86306 | -0.5037 | 14.86608 |
July | 497.00000 | 24.00426 | 54.65490 | -0.3099 | 9.45434 |
August | 514.00000 | 23.79905 | 53.55099 | -0.3810 | 10.70083 |
September | 485.00000 | 23.15781 | 40.43440 | -0.7336 | 24.32563 |
October | 502.00000 | 21.75788 | 30.77005 | -0.2621 | 10.91385 |
November | 489.00000 | 20.57739 | 26.61259 | -0.6598 | 19.31109 |
December | 497.00000 | 20.18953 | 16.46169 | -0.8852 | 25.88657 |
Annual Sum or Average | 5943.00000 | 21.94276 | 33.83050 | -0.5907 | 18.28952 |
Minimum of Months | 454.00000 | 19.92865 | 13.86913 | -0.9678 | 9.45434 |
Maximum of Months | 514.00000 | 24.00426 | 54.65490 | -0.2567 | 28.96915 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68536 | 13.92272 | -1.1024 | 32.82572 |
February | 454.00000 | 19.94823 | 18.58373 | -0.9495 | 27.00439 |
March | 514.00000 | 20.61762 | 24.28261 | -0.6763 | 17.53690 |
April | 485.00000 | 21.47633 | 31.73246 | -0.3287 | 13.65147 |
May | 508.00000 | 22.58591 | 44.98384 | -0.9032 | 27.55055 |
June | 496.00000 | 23.41213 | 51.28540 | -0.5073 | 16.19523 |
July | 497.00000 | 23.84005 | 55.16818 | -0.3149 | 10.74419 |
August | 514.00000 | 23.52778 | 54.48365 | -0.4417 | 12.41311 |
September | 485.00000 | 22.58769 | 41.81004 | -0.9339 | 30.60290 |
October | 502.00000 | 20.96705 | 32.17686 | -0.4734 | 12.53718 |
November | 489.00000 | 20.11452 | 27.18474 | -0.8043 | 22.47950 |
December | 497.00000 | 19.75630 | 16.78257 | -1.0417 | 30.17239 |
Annual Sum or Average | 5943.00000 | 21.55733 | 34.50701 | -0.7045 | 21.07460 |
Minimum of Months | 454.00000 | 19.68536 | 13.92272 | -1.1024 | 10.74419 |
Maximum of Months | 514.00000 | 23.84005 | 55.16818 | -0.3149 | 32.82572 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.64196 | 15.19409 | -1.1000 | 32.40403 |
February | 454.00000 | 19.91374 | 20.09031 | -0.9708 | 26.89401 |
March | 514.00000 | 20.52488 | 26.11268 | -0.7319 | 17.72887 |
April | 485.00000 | 21.11554 | 33.94642 | -0.4843 | 12.69409 |
May | 508.00000 | 22.79113 | 45.95301 | -0.9824 | 27.80245 |
June | 496.00000 | 23.79888 | 50.89448 | -0.5328 | 12.80427 |
July | 497.00000 | 24.16342 | 54.41459 | -0.3593 | 8.19403 |
August | 514.00000 | 24.05769 | 53.18712 | -0.4030 | 8.82951 |
September | 485.00000 | 23.40805 | 40.77049 | -0.7522 | 19.99750 |
October | 502.00000 | 21.64478 | 32.13111 | -0.3175 | 8.22669 |
November | 489.00000 | 20.70797 | 27.66385 | -0.6359 | 16.69842 |
December | 497.00000 | 19.96527 | 18.10711 | -0.9596 | 26.15076 |
Annual Sum or Average | 5943.00000 | 21.82677 | 35.00501 | -0.6840 | 18.14275 |
Minimum of Months | 454.00000 | 19.64196 | 15.19409 | -1.1000 | 8.19403 |
Maximum of Months | 514.00000 | 24.16342 | 54.41459 | -0.3175 | 32.40403 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79186 | 14.65418 | -1.0532 | 30.35020 |
February | 454.00000 | 20.09435 | 19.33209 | -0.9059 | 24.19178 |
March | 514.00000 | 20.69156 | 24.97244 | -0.6592 | 15.79395 |
April | 485.00000 | 21.48316 | 32.31706 | -0.3615 | 11.40039 |
May | 508.00000 | 23.11446 | 44.41048 | -0.7936 | 22.20949 |
June | 496.00000 | 23.76606 | 50.09713 | -0.4441 | 12.55715 |
July | 497.00000 | 24.23839 | 53.51602 | -0.2325 | 7.66775 |
August | 514.00000 | 24.03351 | 52.57615 | -0.3179 | 8.13909 |
September | 485.00000 | 23.50112 | 39.72861 | -0.6332 | 18.16100 |
October | 502.00000 | 21.77425 | 31.03946 | -0.2531 | 7.42680 |
November | 489.00000 | 20.67998 | 27.02517 | -0.6278 | 15.87762 |
December | 497.00000 | 20.04127 | 17.30985 | -0.9342 | 25.10004 |
Annual Sum or Average | 5943.00000 | 21.94930 | 34.04704 | -0.5994 | 16.51464 |
Minimum of Months | 454.00000 | 19.79186 | 14.65418 | -1.0532 | 7.42680 |
Maximum of Months | 514.00000 | 24.23839 | 53.51602 | -0.2325 | 30.35020 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.97411 | 13.73846 | -1.3235 | 41.48311 |
February | 454.00000 | 18.99232 | 18.07938 | -1.0367 | 29.95000 |
March | 514.00000 | 20.13749 | 23.70895 | -0.7230 | 19.63400 |
April | 485.00000 | 21.12692 | 31.44382 | -0.4115 | 13.79937 |
May | 508.00000 | 22.40765 | 45.77733 | -1.0230 | 30.77510 |
June | 496.00000 | 23.33242 | 52.45778 | -0.6175 | 16.93579 |
July | 497.00000 | 23.99781 | 56.45497 | -0.3407 | 9.14149 |
August | 514.00000 | 23.97796 | 54.52366 | -0.3304 | 9.01008 |
September | 485.00000 | 23.38356 | 39.52215 | -0.6316 | 20.36602 |
October | 502.00000 | 22.03059 | 29.31370 | -0.1413 | 8.28076 |
November | 489.00000 | 20.39683 | 25.67342 | -0.6224 | 18.55196 |
December | 497.00000 | 19.05989 | 16.18559 | -1.0508 | 31.12799 |
Annual Sum or Average | 5943.00000 | 21.41974 | 34.05366 | -0.6857 | 20.69523 |
Minimum of Months | 454.00000 | 17.97411 | 13.73846 | -1.3235 | 8.28076 |
Maximum of Months | 514.00000 | 23.99781 | 56.45497 | -0.1413 | 41.48311 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79288 | 14.50938 | -1.0572 | 30.54882 |
February | 454.00000 | 20.14646 | 19.10158 | -0.8962 | 23.99532 |
March | 514.00000 | 20.67492 | 24.85580 | -0.6727 | 16.24698 |
April | 485.00000 | 21.46614 | 32.22080 | -0.3557 | 11.61527 |
May | 508.00000 | 22.64538 | 45.45235 | -0.9513 | 27.74288 |
June | 496.00000 | 23.59017 | 50.70265 | -0.5100 | 14.20076 |
July | 497.00000 | 24.16455 | 53.84753 | -0.2620 | 8.12627 |
August | 514.00000 | 24.02291 | 52.75692 | -0.3189 | 8.31043 |
September | 485.00000 | 23.28060 | 40.19677 | -0.7100 | 20.81892 |
October | 502.00000 | 21.67850 | 30.99191 | -0.2727 | 8.06684 |
November | 489.00000 | 20.67347 | 26.88652 | -0.6282 | 16.11668 |
December | 497.00000 | 20.03899 | 17.17989 | -0.9348 | 25.20245 |
Annual Sum or Average | 5943.00000 | 21.86186 | 34.19412 | -0.6292 | 17.53566 |
Minimum of Months | 454.00000 | 19.79288 | 14.50938 | -1.0572 | 8.06684 |
Maximum of Months | 514.00000 | 24.16455 | 53.84753 | -0.2620 | 30.54882 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68433 | 14.79120 | -1.0658 | 31.14374 |
February | 454.00000 | 19.95541 | 19.48846 | -0.9240 | 25.35666 |
March | 514.00000 | 20.73310 | 25.14932 | -0.6352 | 15.48285 |
April | 485.00000 | 21.65637 | 32.39080 | -0.3089 | 10.87393 |
May | 508.00000 | 23.41683 | 43.70969 | -0.7221 | 18.49077 |
June | 496.00000 | 24.01409 | 50.16875 | -0.4130 | 10.51675 |
July | 497.00000 | 24.26704 | 54.21484 | -0.2869 | 7.38824 |
August | 514.00000 | 24.06109 | 53.32082 | -0.3767 | 8.50212 |
September | 485.00000 | 23.29496 | 40.98042 | -0.7772 | 21.52112 |
October | 502.00000 | 21.44005 | 32.41672 | -0.3622 | 9.25702 |
November | 489.00000 | 20.50551 | 27.46543 | -0.6830 | 18.62101 |
December | 497.00000 | 19.86918 | 17.59263 | -0.9739 | 27.08002 |
Annual Sum or Average | 5943.00000 | 21.92486 | 34.43916 | -0.6252 | 16.94077 |
Minimum of Months | 454.00000 | 19.68433 | 14.79120 | -1.0658 | 7.38824 |
Maximum of Months | 514.00000 | 24.26704 | 54.21484 | -0.2869 | 31.14374 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.54388 | 13.77240 | -1.0815 | 31.99902 |
February | 385.00000 | 19.89722 | 18.36624 | -0.9143 | 25.08299 |
March | 433.00000 | 20.73650 | 23.93459 | -0.6090 | 15.09402 |
April | 410.00000 | 21.75657 | 30.86946 | -0.2533 | 11.18973 |
May | 430.00000 | 23.25006 | 43.26407 | -0.6930 | 19.56719 |
June | 418.00000 | 23.79382 | 49.99579 | -0.4019 | 12.64338 |
July | 422.00000 | 24.19060 | 53.75973 | -0.2259 | 8.48678 |
August | 433.00000 | 23.83607 | 53.23215 | -0.3737 | 9.69927 |
September | 410.00000 | 23.12833 | 40.32854 | -0.7525 | 23.07758 |
October | 427.00000 | 21.34382 | 31.18173 | -0.3597 | 8.95812 |
November | 417.00000 | 20.32747 | 26.25578 | -0.7163 | 18.82003 |
December | 422.00000 | 19.75232 | 16.46139 | -0.9908 | 27.83208 |
Annual Sum or Average | 5034.00000 | 21.80890 | 33.56269 | -0.6125 | 17.64086 |
Minimum of Months | 385.00000 | 19.54388 | 13.77240 | -1.0815 | 8.48678 |
Maximum of Months | 433.00000 | 24.19060 | 53.75973 | -0.2259 | 31.99902 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15352 | 13.77889 | -0.8733 | 25.28956 |
February | 454.00000 | 20.65944 | 17.96163 | -0.6819 | 18.99070 |
March | 514.00000 | 21.38414 | 23.34820 | -0.4344 | 12.79283 |
April | 485.00000 | 22.12419 | 30.67970 | -0.1587 | 11.02771 |
May | 508.00000 | 23.35806 | 43.28266 | -0.6877 | 18.57253 |
June | 496.00000 | 23.81808 | 50.23802 | -0.4346 | 11.91259 |
July | 497.00000 | 24.17213 | 54.05303 | -0.2672 | 8.04155 |
August | 514.00000 | 24.02058 | 52.86411 | -0.3166 | 8.66088 |
September | 485.00000 | 23.52909 | 39.64354 | -0.6004 | 18.67480 |
October | 502.00000 | 22.31745 | 29.85686 | -0.1053 | 8.66913 |
November | 489.00000 | 21.07636 | 25.99964 | -0.5065 | 15.34204 |
December | 497.00000 | 20.50084 | 16.20882 | -0.7684 | 21.68339 |
Annual Sum or Average | 5943.00000 | 22.27295 | 33.29619 | -0.4850 | 14.92866 |
Minimum of Months | 454.00000 | 20.15352 | 13.77889 | -0.8733 | 8.04155 |
Maximum of Months | 514.00000 | 24.17213 | 54.05303 | -0.1053 | 25.28956 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.77395 | 13.86052 | -1.0321 | 29.83373 |
February | 454.00000 | 20.14743 | 18.39616 | -0.8578 | 23.21247 |
March | 514.00000 | 20.84750 | 24.00964 | -0.5850 | 14.64959 |
April | 485.00000 | 21.75506 | 31.33743 | -0.2395 | 11.27083 |
May | 508.00000 | 22.93065 | 44.29249 | -0.7908 | 22.48170 |
June | 496.00000 | 23.64882 | 50.66104 | -0.4399 | 13.20316 |
July | 497.00000 | 24.03508 | 54.49248 | -0.2653 | 9.01418 |
August | 514.00000 | 23.78723 | 53.70111 | -0.3669 | 9.91376 |
September | 485.00000 | 22.94321 | 41.05559 | -0.8020 | 24.64410 |
October | 502.00000 | 21.39839 | 31.48985 | -0.3371 | 9.41863 |
November | 489.00000 | 20.45929 | 26.74224 | -0.6791 | 18.02090 |
December | 497.00000 | 19.93842 | 16.62067 | -0.9482 | 26.14371 |
Annual Sum or Average | 5943.00000 | 21.81968 | 34.02664 | -0.6102 | 17.59088 |
Minimum of Months | 454.00000 | 19.77395 | 13.86052 | -1.0321 | 9.01418 |
Maximum of Months | 514.00000 | 24.03508 | 54.49248 | -0.2395 | 29.83373 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.172551E+09 | 49110352.39 | 11.00 | 0.154755E+09 | 17795955.12 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 8617.59 | 25-MAR-15:00 | 8093.24 | 25-MAR-15:00 | 815.96 | 25-MAR-16:05 | 2394.64 | 25-MAR-15:00 | 0.00 |
April | 0.540289E+10 | 0.138796E+10 | 73.31 | 0.420923E+10 | 0.119366E+10 | 0.00 | 1.00 | 18-APR-08:50 | 0.00 | 01-APR-00:10 | 73923.97 | 18-APR-12:00 | 53826.10 | 18-APR-15:10 | 24199.51 | 18-APR-12:00 | 18357.71 | 18-APR-12:00 | 0.00 |
May | 0.147970E+11 | 0.375552E+10 | 212.41 | 0.111223E+11 | 0.367472E+10 | 0.00 | 1.00 | 05-MAY-12:50 | 0.00 | 01-MAY-00:10 | 75548.21 | 31-MAY-11:30 | 60070.77 | 31-MAY-15:10 | 27377.21 | 30-MAY-10:10 | 19344.49 | 31-MAY-11:30 | 0.00 |
June | 0.470073E+11 | 0.116404E+11 | 350.13 | 0.346109E+11 | 0.123964E+11 | 0.00 | 1.00 | 09-JUN-09:10 | 0.00 | 01-JUN-00:10 | 124464.88 | 26-JUN-07:50 | 72259.25 | 26-JUN-15:30 | 72070.44 | 26-JUN-04:02 | 28161.93 | 26-JUN-07:50 | 0.00 |
July | 0.671018E+11 | 0.161384E+11 | 436.40 | 0.450147E+11 | 0.220871E+11 | 0.00 | 1.00 | 02-JUL-07:22 | 0.00 | 01-JUL-00:10 | 114016.35 | 05-JUL-10:50 | 69962.54 | 03-JUL-15:10 | 66145.99 | 07-JUL-12:10 | 26320.88 | 05-JUL-10:50 | 0.00 |
August | 0.659289E+11 | 0.159606E+11 | 428.76 | 0.450921E+11 | 0.208368E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 132604.17 | 04-AUG-04:02 | 72814.25 | 04-AUG-15:40 | 94518.07 | 04-AUG-07:07 | 29887.58 | 04-AUG-07:40 | 0.00 |
September | 0.259682E+11 | 0.656315E+10 | 238.06 | 0.229200E+11 | 0.304815E+10 | 0.00 | 1.00 | 01-SEP-11:30 | 0.00 | 01-SEP-00:10 | 98466.06 | 11-SEP-09:50 | 69211.56 | 07-SEP-16:00 | 39373.04 | 11-SEP-09:50 | 22879.41 | 11-SEP-09:50 | 0.00 |
October | 0.160999E+10 | 0.429186E+09 | 48.21 | 0.139569E+10 | 0.214305E+09 | 0.00 | 0.90 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 33745.91 | 20-OCT-15:00 | 33745.91 | 20-OCT-15:00 | 5310.74 | 02-OCT-15:00 | 7944.69 | 20-OCT-15:00 | 0.00 |
November | 55810706.39 | 16100286.76 | 5.25 | 50658358.10 | 5152348.29 | 0.00 | 0.15 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4636.17 | 03-NOV-14:00 | 4372.40 | 03-NOV-14:40 | 562.60 | 03-NOV-12:15 | 1326.18 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.228044E+12 | 0.559404E+11 | 1803.53 | 0.164570E+12 | 0.634741E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.671018E+11 | 0.161384E+11 | 436.40 | 0.450921E+11 | 0.220871E+11 | 0.00 | 1.00 | 0.00 | 132604.17 | 72814.25 | 94518.07 | 29887.58 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.165689E+09 | 47109994.00 | 11.00 | 0.149956E+09 | 15732658.04 | 0.00 | 0.29 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 8646.16 | 25-MAR-15:00 | 8449.23 | 25-MAR-15:00 | 712.67 | 28-MAR-15:10 | 2393.37 | 25-MAR-15:00 | 0.00 |
April | 0.582247E+10 | 0.148286E+10 | 78.49 | 0.464089E+10 | 0.118158E+10 | 0.00 | 1.00 | 16-APR-11:43 | 0.00 | 01-APR-00:10 | 67590.59 | 18-APR-12:40 | 57048.09 | 18-APR-15:00 | 24302.28 | 18-APR-09:30 | 16764.80 | 18-APR-15:00 | 0.00 |
May | 0.151865E+11 | 0.384846E+10 | 232.46 | 0.114128E+11 | 0.377375E+10 | 0.00 | 1.00 | 04-MAY-15:00 | 0.00 | 01-MAY-00:10 | 68838.85 | 30-MAY-11:00 | 59971.86 | 31-MAY-15:00 | 28791.82 | 30-MAY-10:00 | 17252.37 | 31-MAY-15:00 | 0.00 |
June | 0.448051E+11 | 0.110757E+11 | 349.70 | 0.334635E+11 | 0.113416E+11 | 0.00 | 1.00 | 08-JUN-15:30 | 0.00 | 01-JUN-00:10 | 120518.84 | 26-JUN-06:03 | 68723.05 | 26-JUN-15:30 | 73228.94 | 26-JUN-04:02 | 27345.20 | 26-JUN-06:03 | 0.00 |
July | 0.615918E+11 | 0.148219E+11 | 436.88 | 0.416618E+11 | 0.199300E+11 | 0.00 | 1.00 | 02-JUL-07:22 | 0.00 | 01-JUL-00:10 | 108491.96 | 05-JUL-10:50 | 66472.84 | 03-JUL-15:10 | 57821.49 | 07-JUL-11:00 | 25044.77 | 05-JUL-10:50 | 0.00 |
August | 0.577554E+11 | 0.140283E+11 | 425.68 | 0.399528E+11 | 0.178026E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 125250.18 | 03-AUG-05:02 | 72064.40 | 04-AUG-15:20 | 89121.38 | 04-AUG-07:07 | 28077.07 | 04-AUG-07:15 | 0.00 |
September | 0.227702E+11 | 0.577732E+10 | 235.39 | 0.202311E+11 | 0.253908E+10 | 0.00 | 1.00 | 01-SEP-12:00 | 0.00 | 01-SEP-00:10 | 84101.45 | 11-SEP-09:40 | 66884.49 | 07-SEP-16:00 | 33743.37 | 11-SEP-09:40 | 20696.61 | 06-SEP-14:10 | 0.00 |
October | 0.144042E+10 | 0.386023E+09 | 48.08 | 0.124211E+10 | 0.198308E+09 | 0.00 | 0.84 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29624.89 | 20-OCT-15:00 | 29624.89 | 20-OCT-15:00 | 4678.72 | 02-OCT-15:00 | 7076.96 | 20-OCT-15:00 | 0.00 |
November | 61027624.47 | 17505976.87 | 5.38 | 53950745.08 | 7076879.39 | 0.00 | 0.19 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 5551.52 | 03-NOV-13:30 | 4857.81 | 03-NOV-13:40 | 886.45 | 03-NOV-13:00 | 1573.59 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.209599E+12 | 0.514852E+11 | 1823.06 | 0.152809E+12 | 0.567898E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.615918E+11 | 0.148219E+11 | 436.88 | 0.416618E+11 | 0.199300E+11 | 0.00 | 1.00 | 0.00 | 125250.18 | 72064.40 | 89121.38 | 28077.07 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.175355E+09 | 49930744.58 | 11.00 | 0.155234E+09 | 20120611.10 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:03 | 9212.27 | 25-MAR-15:00 | 8745.05 | 25-MAR-15:00 | 848.65 | 28-MAR-15:00 | 2556.92 | 25-MAR-15:00 | 0.00 |
April | 0.646552E+10 | 0.164331E+10 | 78.46 | 0.511782E+10 | 0.134770E+10 | 0.00 | 1.00 | 16-APR-12:02 | 0.00 | 01-APR-00:10 | 83265.33 | 18-APR-15:50 | 64943.67 | 18-APR-15:00 | 25718.18 | 18-APR-15:50 | 19671.46 | 18-APR-15:50 | 0.00 |
May | 0.164910E+11 | 0.418620E+10 | 232.77 | 0.123323E+11 | 0.415869E+10 | 0.00 | 1.00 | 04-MAY-14:30 | 0.00 | 01-MAY-00:10 | 78357.08 | 30-MAY-12:10 | 69764.51 | 31-MAY-15:00 | 27809.40 | 30-MAY-10:00 | 19816.54 | 31-MAY-15:00 | 0.00 |
June | 0.481749E+11 | 0.119408E+11 | 347.12 | 0.361715E+11 | 0.120034E+11 | 0.00 | 1.00 | 08-JUN-15:40 | 0.00 | 01-JUN-00:10 | 114988.56 | 26-JUN-07:50 | 80884.05 | 26-JUN-14:00 | 69685.89 | 26-JUN-04:02 | 26031.89 | 26-JUN-07:50 | 0.00 |
July | 0.658462E+11 | 0.158729E+11 | 431.70 | 0.442391E+11 | 0.216071E+11 | 0.00 | 1.00 | 01-JUL-13:30 | 0.00 | 01-JUL-00:10 | 117613.31 | 06-JUL-15:10 | 74848.91 | 03-JUL-15:20 | 58363.24 | 17-JUL-16:10 | 27220.47 | 06-JUL-15:10 | 0.00 |
August | 0.602059E+11 | 0.146857E+11 | 421.66 | 0.418525E+11 | 0.183535E+11 | 0.00 | 1.00 | 01-AUG-07:17 | 0.00 | 01-AUG-00:10 | 139138.21 | 04-AUG-05:02 | 83710.16 | 04-AUG-15:20 | 95128.02 | 04-AUG-05:02 | 31001.93 | 04-AUG-05:02 | 0.00 |
September | 0.237934E+11 | 0.607046E+10 | 230.61 | 0.210017E+11 | 0.279172E+10 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 84278.81 | 11-SEP-10:00 | 76032.55 | 07-SEP-16:00 | 32094.55 | 11-SEP-10:00 | 22606.33 | 06-SEP-14:00 | 0.00 |
October | 0.146459E+10 | 0.395807E+09 | 47.29 | 0.124008E+10 | 0.224504E+09 | 0.00 | 0.78 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29625.07 | 20-OCT-15:00 | 29625.07 | 20-OCT-15:00 | 4947.77 | 02-OCT-15:00 | 7216.36 | 20-OCT-15:00 | 0.00 |
November | 44858185.78 | 12985776.09 | 4.33 | 38721872.24 | 6136313.54 | 0.00 | 0.13 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4123.79 | 03-NOV-14:00 | 3634.34 | 03-NOV-14:00 | 559.78 | 03-NOV-13:20 | 1185.80 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.222662E+12 | 0.548582E+11 | 1804.95 | 0.162149E+12 | 0.605128E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.658462E+11 | 0.158729E+11 | 431.70 | 0.442391E+11 | 0.216071E+11 | 0.00 | 1.00 | 0.00 | 139138.21 | 83710.16 | 95128.02 | 31001.93 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.55 | 0.00 | 354.55 | 2.01 | 2750.49 | 0.00 | 0.00 | 0.00 |
February | 449.50 | 0.00 | 449.50 | 31.49 | 2193.81 | 0.00 | 0.00 | 0.00 |
March | 673.66 | 0.00 | 673.66 | 227.06 | 1381.61 | 0.00 | 0.00 | 0.00 |
April | 777.69 | 3.83 | 773.86 | 450.46 | 940.31 | 0.00 | 0.00 | 0.00 |
May | 1014.13 | 38.12 | 976.01 | 907.77 | 552.42 | 0.00 | 0.00 | 0.00 |
June | 1185.28 | 107.58 | 1077.70 | 1345.67 | 387.54 | 0.00 | 0.00 | 0.00 |
July | 1111.61 | 74.35 | 1037.25 | 1314.63 | 342.45 | 0.00 | 0.00 | 0.00 |
August | 930.74 | 16.50 | 914.25 | 1097.85 | 398.85 | 0.00 | 0.00 | 0.00 |
September | 713.61 | 0.18 | 713.44 | 674.63 | 679.78 | 0.00 | 0.00 | 0.00 |
October | 530.58 | 0.00 | 530.58 | 274.72 | 1016.45 | 0.00 | 0.00 | 0.00 |
November | 371.15 | 0.00 | 371.15 | 70.65 | 1611.96 | 0.00 | 0.00 | 0.00 |
December | 240.75 | 0.00 | 240.75 | 0.79 | 2408.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.41 | 20.13 | 677.28 | 536.15 | 1217.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.75 | 0.00 | 240.75 | 0.79 | 342.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1185.28 | 107.58 | 1077.70 | 1345.67 | 2750.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.48 | 208.42 | 298.06 | 222.22 | 1654.27 | 0.00 | 0.00 | 0.00 |
February | 671.34 | 295.20 | 376.14 | 391.43 | 1297.79 | 0.00 | 0.00 | 0.00 |
March | 912.14 | 362.06 | 550.09 | 710.49 | 846.17 | 0.00 | 0.00 | 0.00 |
April | 1120.03 | 490.49 | 629.53 | 1076.19 | 603.29 | 0.00 | 0.00 | 0.00 |
May | 1406.66 | 614.65 | 792.02 | 1570.14 | 368.57 | 0.00 | 0.00 | 0.00 |
June | 1547.99 | 674.13 | 873.87 | 1909.09 | 256.83 | 0.00 | 0.00 | 0.00 |
July | 1564.63 | 721.95 | 842.67 | 1972.61 | 226.30 | 0.00 | 0.00 | 0.00 |
August | 1318.95 | 568.63 | 750.32 | 1668.78 | 262.25 | 0.00 | 0.00 | 0.00 |
September | 1176.38 | 555.90 | 620.48 | 1382.03 | 435.10 | 0.00 | 0.00 | 0.00 |
October | 749.67 | 313.13 | 436.54 | 683.54 | 636.07 | 0.00 | 0.00 | 0.00 |
November | 442.31 | 143.67 | 298.64 | 244.43 | 998.47 | 0.00 | 0.00 | 0.00 |
December | 342.62 | 147.13 | 195.49 | 155.92 | 1483.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 981.47 | 425.22 | 556.24 | 1002.21 | 753.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.62 | 143.67 | 195.49 | 155.92 | 226.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.63 | 721.95 | 873.87 | 1972.61 | 1654.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2204.89 | 1508.85 | 696.04 | 1947.26 | 2242.49 | 0.00 | 0.00 | 0.00 |
February | 2362.50 | 1596.12 | 766.38 | 2177.09 | 1793.76 | 0.00 | 0.00 | 0.00 |
March | 2055.91 | 1082.57 | 973.34 | 1990.87 | 1289.51 | 0.00 | 0.00 | 0.00 |
April | 1852.24 | 865.96 | 986.28 | 1992.87 | 961.03 | 0.00 | 0.00 | 0.00 |
May | 1534.52 | 416.03 | 1118.49 | 1757.59 | 599.10 | 0.00 | 0.00 | 0.00 |
June | 1489.78 | 303.33 | 1186.46 | 1889.65 | 411.55 | 0.00 | 0.00 | 0.00 |
July | 1577.04 | 397.37 | 1179.67 | 2083.49 | 361.89 | 0.00 | 0.00 | 0.00 |
August | 1776.80 | 637.20 | 1139.60 | 2383.23 | 424.86 | 0.00 | 0.00 | 0.00 |
September | 2153.11 | 1134.51 | 1018.60 | 2699.17 | 691.03 | 0.00 | 0.00 | 0.00 |
October | 2248.29 | 1410.49 | 837.81 | 2485.26 | 982.90 | 0.00 | 0.00 | 0.00 |
November | 1696.33 | 1061.94 | 634.40 | 1600.85 | 1433.80 | 0.00 | 0.00 | 0.00 |
December | 1808.89 | 1370.21 | 438.68 | 1715.41 | 2069.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1893.95 | 978.54 | 915.41 | 2059.43 | 1101.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1489.78 | 303.33 | 438.68 | 1600.85 | 361.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2362.50 | 1596.12 | 1186.46 | 2699.17 | 2242.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.31 | 203.24 | 299.07 | 229.93 | 1694.69 | 0.00 | 0.00 | 0.00 |
February | 736.54 | 362.95 | 373.60 | 481.97 | 1346.88 | 0.00 | 0.00 | 0.00 |
March | 879.28 | 327.14 | 552.14 | 672.09 | 874.95 | 0.00 | 0.00 | 0.00 |
April | 1282.61 | 634.23 | 648.38 | 1309.10 | 628.92 | 0.00 | 0.00 | 0.00 |
May | 1286.32 | 513.85 | 772.47 | 1448.49 | 389.83 | 0.00 | 0.00 | 0.00 |
June | 1509.34 | 654.11 | 855.23 | 1877.58 | 277.31 | 0.00 | 0.00 | 0.00 |
July | 1620.58 | 769.80 | 850.78 | 2069.54 | 249.62 | 0.00 | 0.00 | 0.00 |
August | 1416.79 | 650.21 | 766.58 | 1822.74 | 283.62 | 0.00 | 0.00 | 0.00 |
September | 1146.85 | 544.35 | 602.50 | 1358.11 | 455.85 | 0.00 | 0.00 | 0.00 |
October | 799.17 | 355.30 | 443.87 | 759.82 | 665.70 | 0.00 | 0.00 | 0.00 |
November | 478.36 | 176.90 | 301.46 | 304.56 | 1022.76 | 0.00 | 0.00 | 0.00 |
December | 367.88 | 173.42 | 194.46 | 201.57 | 1516.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1003.23 | 447.21 | 556.02 | 1047.41 | 781.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.88 | 173.42 | 194.46 | 201.57 | 249.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.58 | 769.80 | 855.23 | 2069.54 | 1694.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.72 | 917.84 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.68 | 735.09 | 0.00 | 0.00 | 0.00 |
March | 224.54 | 0.00 | 224.54 | 80.63 | 462.67 | 0.00 | 0.00 | 0.00 |
April | 259.22 | 1.28 | 257.94 | 160.38 | 309.39 | 0.00 | 0.00 | 0.00 |
May | 338.03 | 12.71 | 325.32 | 316.45 | 178.13 | 0.00 | 0.00 | 0.00 |
June | 395.08 | 35.86 | 359.22 | 457.45 | 127.48 | 0.00 | 0.00 | 0.00 |
July | 370.52 | 24.78 | 345.73 | 444.43 | 113.75 | 0.00 | 0.00 | 0.00 |
August | 310.23 | 5.50 | 304.73 | 367.00 | 137.57 | 0.00 | 0.00 | 0.00 |
September | 237.86 | 0.06 | 237.80 | 220.66 | 245.01 | 0.00 | 0.00 | 0.00 |
October | 176.85 | 0.00 | 176.85 | 83.81 | 372.76 | 0.00 | 0.00 | 0.00 |
November | 123.71 | 0.00 | 123.71 | 20.35 | 570.61 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 822.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.46 | 6.71 | 225.75 | 181.24 | 414.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.08 | 35.86 | 359.22 | 457.45 | 917.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.72 | 917.90 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.68 | 735.14 | 0.00 | 0.00 | 0.00 |
March | 224.56 | 0.00 | 224.56 | 80.63 | 462.70 | 0.00 | 0.00 | 0.00 |
April | 259.24 | 1.28 | 257.96 | 160.39 | 309.41 | 0.00 | 0.00 | 0.00 |
May | 338.05 | 12.71 | 325.34 | 316.47 | 178.14 | 0.00 | 0.00 | 0.00 |
June | 395.10 | 35.86 | 359.24 | 457.48 | 127.49 | 0.00 | 0.00 | 0.00 |
July | 370.54 | 24.79 | 345.76 | 444.46 | 113.76 | 0.00 | 0.00 | 0.00 |
August | 310.25 | 5.50 | 304.75 | 367.02 | 137.58 | 0.00 | 0.00 | 0.00 |
September | 237.87 | 0.06 | 237.82 | 220.67 | 245.03 | 0.00 | 0.00 | 0.00 |
October | 176.86 | 0.00 | 176.86 | 83.82 | 372.78 | 0.00 | 0.00 | 0.00 |
November | 123.72 | 0.00 | 123.72 | 20.35 | 570.65 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 822.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.47 | 6.71 | 225.77 | 181.25 | 414.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.10 | 35.86 | 359.24 | 457.48 | 917.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.18 | 0.00 | 118.18 | 0.72 | 917.90 | 0.00 | 0.00 | 0.00 |
February | 149.83 | 0.00 | 149.83 | 10.68 | 735.14 | 0.00 | 0.00 | 0.00 |
March | 224.56 | 0.00 | 224.56 | 80.63 | 462.70 | 0.00 | 0.00 | 0.00 |
April | 259.24 | 1.28 | 257.96 | 160.39 | 309.41 | 0.00 | 0.00 | 0.00 |
May | 338.05 | 12.71 | 325.34 | 316.47 | 178.14 | 0.00 | 0.00 | 0.00 |
June | 395.10 | 35.86 | 359.24 | 457.48 | 127.49 | 0.00 | 0.00 | 0.00 |
July | 370.54 | 24.79 | 345.76 | 444.46 | 113.76 | 0.00 | 0.00 | 0.00 |
August | 310.25 | 5.50 | 304.75 | 367.02 | 137.58 | 0.00 | 0.00 | 0.00 |
September | 237.87 | 0.06 | 237.82 | 220.67 | 245.03 | 0.00 | 0.00 | 0.00 |
October | 176.86 | 0.00 | 176.86 | 83.82 | 372.78 | 0.00 | 0.00 | 0.00 |
November | 123.72 | 0.00 | 123.72 | 20.35 | 570.65 | 0.00 | 0.00 | 0.00 |
December | 80.25 | 0.00 | 80.25 | 0.09 | 822.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 232.47 | 6.71 | 225.77 | 181.25 | 414.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.25 | 0.00 | 80.25 | 0.09 | 113.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 395.10 | 35.86 | 359.24 | 457.48 | 917.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 487.21 | 200.49 | 286.72 | 217.09 | 1600.42 | 0.00 | 0.00 | 0.00 |
February | 645.80 | 283.97 | 361.83 | 380.75 | 1266.98 | 0.00 | 0.00 | 0.00 |
March | 877.44 | 348.28 | 529.16 | 697.20 | 826.36 | 0.00 | 0.00 | 0.00 |
April | 1077.42 | 471.83 | 605.58 | 1058.59 | 582.98 | 0.00 | 0.00 | 0.00 |
May | 1353.15 | 591.26 | 761.89 | 1533.74 | 355.85 | 0.00 | 0.00 | 0.00 |
June | 1489.10 | 648.48 | 840.63 | 1853.52 | 252.07 | 0.00 | 0.00 | 0.00 |
July | 1505.10 | 694.49 | 810.62 | 1909.30 | 225.87 | 0.00 | 0.00 | 0.00 |
August | 1268.77 | 546.99 | 721.78 | 1608.97 | 268.79 | 0.00 | 0.00 | 0.00 |
September | 1131.63 | 534.75 | 596.88 | 1323.17 | 459.67 | 0.00 | 0.00 | 0.00 |
October | 721.15 | 301.22 | 419.93 | 639.65 | 678.23 | 0.00 | 0.00 | 0.00 |
November | 425.49 | 138.21 | 287.28 | 226.32 | 1021.43 | 0.00 | 0.00 | 0.00 |
December | 329.59 | 141.53 | 188.05 | 149.04 | 1466.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.13 | 409.04 | 535.08 | 969.63 | 748.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.59 | 138.21 | 188.05 | 149.04 | 225.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1505.10 | 694.49 | 840.63 | 1909.30 | 1600.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.26 | 7.93 | 11.34 | 8.58 | 63.28 | 0.00 | 0.00 | 0.00 |
February | 25.53 | 11.23 | 14.31 | 15.05 | 50.10 | 0.00 | 0.00 | 0.00 |
March | 34.69 | 13.77 | 20.92 | 27.57 | 32.67 | 0.00 | 0.00 | 0.00 |
April | 42.60 | 18.66 | 23.94 | 41.86 | 23.05 | 0.00 | 0.00 | 0.00 |
May | 53.50 | 23.38 | 30.12 | 60.64 | 14.07 | 0.00 | 0.00 | 0.00 |
June | 58.88 | 25.64 | 33.24 | 73.29 | 9.97 | 0.00 | 0.00 | 0.00 |
July | 59.51 | 27.46 | 32.05 | 75.49 | 8.93 | 0.00 | 0.00 | 0.00 |
August | 50.17 | 21.63 | 28.54 | 63.62 | 10.63 | 0.00 | 0.00 | 0.00 |
September | 44.74 | 21.14 | 23.60 | 52.32 | 18.17 | 0.00 | 0.00 | 0.00 |
October | 28.51 | 11.91 | 16.60 | 25.29 | 26.82 | 0.00 | 0.00 | 0.00 |
November | 16.82 | 5.46 | 11.36 | 8.95 | 40.39 | 0.00 | 0.00 | 0.00 |
December | 13.03 | 5.60 | 7.44 | 5.89 | 57.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.33 | 16.17 | 21.16 | 38.34 | 29.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.03 | 5.46 | 7.44 | 5.89 | 8.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.51 | 27.46 | 33.24 | 75.49 | 63.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.99 | 502.97 | 232.02 | 669.63 | 730.08 | 0.00 | 0.00 | 0.00 |
February | 787.53 | 532.06 | 255.47 | 745.83 | 599.11 | 0.00 | 0.00 | 0.00 |
March | 685.32 | 360.87 | 324.46 | 682.13 | 430.72 | 0.00 | 0.00 | 0.00 |
April | 617.43 | 288.66 | 328.77 | 681.98 | 318.57 | 0.00 | 0.00 | 0.00 |
May | 511.52 | 138.68 | 372.84 | 604.92 | 194.42 | 0.00 | 0.00 | 0.00 |
June | 496.61 | 101.11 | 395.50 | 642.91 | 134.82 | 0.00 | 0.00 | 0.00 |
July | 525.70 | 132.46 | 393.23 | 702.73 | 122.13 | 0.00 | 0.00 | 0.00 |
August | 592.28 | 212.41 | 379.88 | 798.76 | 150.43 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 378.18 | 339.54 | 901.64 | 251.99 | 0.00 | 0.00 | 0.00 |
October | 749.45 | 470.18 | 279.28 | 828.37 | 365.91 | 0.00 | 0.00 | 0.00 |
November | 565.46 | 353.99 | 211.47 | 535.30 | 506.02 | 0.00 | 0.00 | 0.00 |
December | 602.98 | 456.75 | 146.23 | 580.56 | 694.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.34 | 326.19 | 305.14 | 697.58 | 373.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.61 | 101.11 | 146.23 | 535.30 | 122.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.53 | 532.06 | 395.50 | 901.64 | 730.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.99 | 502.97 | 232.02 | 669.63 | 730.08 | 0.00 | 0.00 | 0.00 |
February | 787.53 | 532.06 | 255.47 | 745.83 | 599.11 | 0.00 | 0.00 | 0.00 |
March | 685.32 | 360.87 | 324.46 | 682.13 | 430.72 | 0.00 | 0.00 | 0.00 |
April | 617.43 | 288.66 | 328.77 | 681.98 | 318.57 | 0.00 | 0.00 | 0.00 |
May | 511.52 | 138.68 | 372.84 | 604.92 | 194.42 | 0.00 | 0.00 | 0.00 |
June | 496.61 | 101.11 | 395.50 | 642.91 | 134.82 | 0.00 | 0.00 | 0.00 |
July | 525.70 | 132.46 | 393.23 | 702.73 | 122.13 | 0.00 | 0.00 | 0.00 |
August | 592.28 | 212.41 | 379.88 | 798.76 | 150.43 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 378.18 | 339.54 | 901.64 | 251.99 | 0.00 | 0.00 | 0.00 |
October | 749.45 | 470.18 | 279.28 | 828.37 | 365.91 | 0.00 | 0.00 | 0.00 |
November | 565.46 | 353.99 | 211.47 | 535.30 | 506.02 | 0.00 | 0.00 | 0.00 |
December | 602.98 | 456.75 | 146.23 | 580.56 | 694.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.34 | 326.19 | 305.14 | 697.58 | 373.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.61 | 101.11 | 146.23 | 535.30 | 122.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.53 | 532.06 | 395.50 | 901.64 | 730.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.94 | 502.94 | 232.00 | 669.59 | 730.04 | 0.00 | 0.00 | 0.00 |
February | 787.48 | 532.03 | 255.45 | 745.78 | 599.07 | 0.00 | 0.00 | 0.00 |
March | 685.28 | 360.85 | 324.43 | 682.09 | 430.69 | 0.00 | 0.00 | 0.00 |
April | 617.39 | 288.64 | 328.75 | 681.93 | 318.55 | 0.00 | 0.00 | 0.00 |
May | 511.49 | 138.67 | 372.82 | 604.89 | 194.41 | 0.00 | 0.00 | 0.00 |
June | 496.58 | 101.11 | 395.47 | 642.86 | 134.81 | 0.00 | 0.00 | 0.00 |
July | 525.66 | 132.45 | 393.21 | 702.68 | 122.12 | 0.00 | 0.00 | 0.00 |
August | 592.25 | 212.39 | 379.85 | 798.71 | 150.42 | 0.00 | 0.00 | 0.00 |
September | 717.68 | 378.16 | 339.52 | 901.59 | 251.97 | 0.00 | 0.00 | 0.00 |
October | 749.41 | 470.15 | 279.26 | 828.32 | 365.89 | 0.00 | 0.00 | 0.00 |
November | 565.43 | 353.97 | 211.46 | 535.27 | 505.99 | 0.00 | 0.00 | 0.00 |
December | 602.95 | 456.72 | 146.22 | 580.52 | 694.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 631.30 | 326.17 | 305.12 | 697.54 | 373.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 496.58 | 101.11 | 146.22 | 535.27 | 122.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 787.48 | 532.03 | 395.47 | 901.59 | 730.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.20 | 195.51 | 287.69 | 226.82 | 1638.10 | 0.00 | 0.00 | 0.00 |
February | 708.52 | 349.14 | 359.39 | 472.48 | 1312.89 | 0.00 | 0.00 | 0.00 |
March | 845.83 | 314.69 | 531.14 | 663.70 | 853.71 | 0.00 | 0.00 | 0.00 |
April | 1233.81 | 610.10 | 623.72 | 1283.41 | 611.98 | 0.00 | 0.00 | 0.00 |
May | 1237.39 | 494.30 | 743.08 | 1416.75 | 373.95 | 0.00 | 0.00 | 0.00 |
June | 1451.92 | 629.23 | 822.70 | 1821.03 | 270.63 | 0.00 | 0.00 | 0.00 |
July | 1558.93 | 740.51 | 818.41 | 1998.53 | 250.39 | 0.00 | 0.00 | 0.00 |
August | 1362.89 | 625.48 | 737.42 | 1753.77 | 292.40 | 0.00 | 0.00 | 0.00 |
September | 1103.22 | 523.64 | 579.58 | 1298.90 | 479.62 | 0.00 | 0.00 | 0.00 |
October | 768.77 | 341.79 | 426.99 | 720.24 | 708.55 | 0.00 | 0.00 | 0.00 |
November | 460.16 | 170.17 | 289.99 | 287.34 | 1045.94 | 0.00 | 0.00 | 0.00 |
December | 353.89 | 166.83 | 187.06 | 195.35 | 1497.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.07 | 430.20 | 534.87 | 1014.19 | 775.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.89 | 166.83 | 187.06 | 195.35 | 250.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1558.93 | 740.51 | 822.70 | 1998.53 | 1638.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.11 | 7.73 | 11.37 | 8.97 | 64.77 | 0.00 | 0.00 | 0.00 |
February | 28.01 | 13.80 | 14.21 | 18.68 | 51.91 | 0.00 | 0.00 | 0.00 |
March | 33.44 | 12.44 | 21.00 | 26.24 | 33.76 | 0.00 | 0.00 | 0.00 |
April | 48.78 | 24.12 | 24.66 | 50.74 | 24.20 | 0.00 | 0.00 | 0.00 |
May | 48.92 | 19.54 | 29.38 | 56.02 | 14.79 | 0.00 | 0.00 | 0.00 |
June | 57.41 | 24.88 | 32.53 | 72.00 | 10.70 | 0.00 | 0.00 | 0.00 |
July | 61.64 | 29.28 | 32.36 | 79.02 | 9.90 | 0.00 | 0.00 | 0.00 |
August | 53.89 | 24.73 | 29.16 | 69.34 | 11.56 | 0.00 | 0.00 | 0.00 |
September | 43.62 | 20.70 | 22.92 | 51.36 | 18.96 | 0.00 | 0.00 | 0.00 |
October | 30.40 | 13.51 | 16.88 | 28.48 | 28.02 | 0.00 | 0.00 | 0.00 |
November | 18.19 | 6.73 | 11.47 | 11.36 | 41.36 | 0.00 | 0.00 | 0.00 |
December | 13.99 | 6.60 | 7.40 | 7.72 | 59.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.16 | 17.01 | 21.15 | 40.10 | 30.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.99 | 6.60 | 7.40 | 7.72 | 9.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.64 | 29.28 | 32.53 | 79.02 | 64.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 354.55 | 0.00 | 354.55 | 1.68 | 2797.74 | 0.00 | 0.00 | 0.00 |
February | 449.50 | 0.00 | 449.50 | 28.50 | 2255.51 | 0.00 | 0.00 | 0.00 |
March | 673.66 | 0.00 | 673.66 | 217.42 | 1443.56 | 0.00 | 0.00 | 0.00 |
April | 777.69 | 3.83 | 773.86 | 438.41 | 999.29 | 0.00 | 0.00 | 0.00 |
May | 1014.13 | 38.12 | 976.01 | 889.66 | 585.00 | 0.00 | 0.00 | 0.00 |
June | 1185.28 | 107.58 | 1077.70 | 1337.55 | 406.89 | 0.00 | 0.00 | 0.00 |
July | 1111.61 | 74.35 | 1037.25 | 1310.43 | 356.35 | 0.00 | 0.00 | 0.00 |
August | 930.74 | 16.50 | 914.25 | 1090.00 | 419.41 | 0.00 | 0.00 | 0.00 |
September | 713.61 | 0.18 | 713.44 | 658.00 | 728.84 | 0.00 | 0.00 | 0.00 |
October | 530.58 | 0.00 | 530.58 | 251.44 | 1099.86 | 0.00 | 0.00 | 0.00 |
November | 371.15 | 0.00 | 371.15 | 60.67 | 1694.18 | 0.00 | 0.00 | 0.00 |
December | 240.75 | 0.00 | 240.75 | 0.22 | 2476.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.41 | 20.13 | 677.28 | 526.64 | 1267.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 240.75 | 0.00 | 240.75 | 0.22 | 356.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1185.28 | 107.58 | 1077.70 | 1337.55 | 2797.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.48 | 208.42 | 298.06 | 220.04 | 1683.02 | 0.00 | 0.00 | 0.00 |
February | 671.34 | 295.20 | 376.14 | 386.24 | 1336.04 | 0.00 | 0.00 | 0.00 |
March | 912.14 | 362.06 | 550.09 | 702.00 | 883.46 | 0.00 | 0.00 | 0.00 |
April | 1120.03 | 490.49 | 629.53 | 1069.77 | 636.09 | 0.00 | 0.00 | 0.00 |
May | 1406.66 | 614.65 | 792.02 | 1565.04 | 385.89 | 0.00 | 0.00 | 0.00 |
June | 1547.99 | 674.13 | 873.87 | 1908.40 | 267.50 | 0.00 | 0.00 | 0.00 |
July | 1564.63 | 721.95 | 842.67 | 1974.12 | 233.75 | 0.00 | 0.00 | 0.00 |
August | 1318.95 | 568.63 | 750.32 | 1667.32 | 273.36 | 0.00 | 0.00 | 0.00 |
September | 1176.38 | 555.90 | 620.48 | 1374.82 | 460.13 | 0.00 | 0.00 | 0.00 |
October | 749.67 | 313.13 | 436.54 | 667.02 | 682.36 | 0.00 | 0.00 | 0.00 |
November | 442.31 | 143.67 | 298.64 | 235.00 | 1046.69 | 0.00 | 0.00 | 0.00 |
December | 342.62 | 147.13 | 195.49 | 152.83 | 1526.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 981.47 | 425.22 | 556.24 | 996.86 | 782.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 342.62 | 143.67 | 195.49 | 152.83 | 233.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.63 | 721.95 | 873.87 | 1974.12 | 1683.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2204.89 | 1508.85 | 696.04 | 1939.49 | 2289.46 | 0.00 | 0.00 | 0.00 |
February | 2362.50 | 1596.12 | 766.38 | 2164.50 | 1855.56 | 0.00 | 0.00 | 0.00 |
March | 2055.91 | 1082.57 | 973.34 | 1978.73 | 1349.50 | 0.00 | 0.00 | 0.00 |
April | 1852.24 | 865.96 | 986.28 | 1984.87 | 1016.14 | 0.00 | 0.00 | 0.00 |
May | 1534.52 | 416.03 | 1118.49 | 1748.52 | 632.19 | 0.00 | 0.00 | 0.00 |
June | 1489.78 | 303.33 | 1186.46 | 1885.95 | 432.67 | 0.00 | 0.00 | 0.00 |
July | 1577.04 | 397.37 | 1179.67 | 2082.89 | 376.79 | 0.00 | 0.00 | 0.00 |
August | 1776.80 | 637.20 | 1139.60 | 2380.63 | 446.13 | 0.00 | 0.00 | 0.00 |
September | 2153.11 | 1134.51 | 1018.60 | 2688.91 | 734.07 | 0.00 | 0.00 | 0.00 |
October | 2248.29 | 1410.49 | 837.81 | 2461.92 | 1057.28 | 0.00 | 0.00 | 0.00 |
November | 1696.33 | 1061.94 | 634.40 | 1580.31 | 1508.69 | 0.00 | 0.00 | 0.00 |
December | 1808.89 | 1370.21 | 438.68 | 1704.45 | 2136.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1893.95 | 978.54 | 915.41 | 2049.32 | 1149.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1489.78 | 303.33 | 438.68 | 1580.31 | 376.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2362.50 | 1596.12 | 1186.46 | 2688.91 | 2289.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 502.31 | 203.24 | 299.07 | 229.15 | 1724.30 | 0.00 | 0.00 | 0.00 |
February | 736.54 | 362.95 | 373.60 | 478.91 | 1386.03 | 0.00 | 0.00 | 0.00 |
March | 879.28 | 327.14 | 552.14 | 666.52 | 914.35 | 0.00 | 0.00 | 0.00 |
April | 1282.61 | 634.23 | 648.38 | 1304.74 | 664.67 | 0.00 | 0.00 | 0.00 |
May | 1286.32 | 513.85 | 772.47 | 1442.15 | 410.95 | 0.00 | 0.00 | 0.00 |
June | 1509.34 | 654.11 | 855.23 | 1874.88 | 290.41 | 0.00 | 0.00 | 0.00 |
July | 1620.58 | 769.80 | 850.78 | 2068.54 | 259.19 | 0.00 | 0.00 | 0.00 |
August | 1416.79 | 650.21 | 766.58 | 1819.38 | 297.25 | 0.00 | 0.00 | 0.00 |
September | 1146.85 | 544.35 | 602.50 | 1350.14 | 483.84 | 0.00 | 0.00 | 0.00 |
October | 799.17 | 355.30 | 443.87 | 747.36 | 715.84 | 0.00 | 0.00 | 0.00 |
November | 478.36 | 176.90 | 301.46 | 297.17 | 1072.19 | 0.00 | 0.00 | 0.00 |
December | 367.88 | 173.42 | 194.46 | 199.48 | 1559.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1003.23 | 447.21 | 556.02 | 1042.65 | 812.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.88 | 173.42 | 194.46 | 199.48 | 259.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1620.58 | 769.80 | 855.23 | 2068.54 | 1724.30 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949622E+09 | 0.00 | 0.949622E+09 | 5377189.26 | 0.736691E+10 |
February | 0.108742E+10 | 0.00 | 0.108742E+10 | 76174593.61 | 0.530726E+10 |
March | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.608149E+09 | 0.370051E+10 |
April | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.116758E+10 | 0.243728E+10 |
May | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.243137E+10 | 0.147960E+10 |
June | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.348799E+10 | 0.100452E+10 |
July | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.352109E+10 | 0.917224E+09 |
August | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.294047E+10 | 0.106829E+10 |
September | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.174863E+10 | 0.176199E+10 |
October | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.735814E+09 | 0.272247E+10 |
November | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.183113E+09 | 0.417820E+10 |
December | 0.644823E+09 | 0.00 | 0.644823E+09 | 2122025.75 | 0.645100E+10 |
Annual Sum or Average | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.169079E+11 | 0.383952E+11 |
Minimum of Months | 0.644823E+09 | 0.00 | 0.644823E+09 | 2122025.75 | 0.917224E+09 |
Maximum of Months | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.352109E+10 | 0.736691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.595203E+09 | 0.443080E+10 |
February | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.946947E+09 | 0.313962E+10 |
March | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.190298E+10 | 0.226638E+10 |
April | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.278949E+10 | 0.156374E+10 |
May | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.420547E+10 | 0.987185E+09 |
June | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.494837E+10 | 0.665700E+09 |
July | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.528343E+10 | 0.606119E+09 |
August | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.446967E+10 | 0.702411E+09 |
September | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.358223E+10 | 0.112779E+10 |
October | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.183079E+10 | 0.170366E+10 |
November | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.633561E+09 | 0.258803E+10 |
December | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.417618E+09 | 0.397462E+10 |
Annual Sum or Average | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.316057E+11 | 0.237560E+11 |
Minimum of Months | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.417618E+09 | 0.606119E+09 |
Maximum of Months | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.528343E+10 | 0.443080E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.521554E+10 | 0.600628E+10 |
February | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.526683E+10 | 0.433947E+10 |
March | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.533235E+10 | 0.345381E+10 |
April | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.516552E+10 | 0.249100E+10 |
May | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.470753E+10 | 0.160463E+10 |
June | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.489796E+10 | 0.106673E+10 |
July | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.558042E+10 | 0.969291E+09 |
August | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.638324E+10 | 0.113795E+10 |
September | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.699625E+10 | 0.179115E+10 |
October | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.665651E+10 | 0.263259E+10 |
November | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.414940E+10 | 0.371642E+10 |
December | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.459457E+10 | 0.554210E+10 |
Annual Sum or Average | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.649461E+11 | 0.347514E+11 |
Minimum of Months | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.414940E+10 | 0.969291E+09 |
Maximum of Months | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.699625E+10 | 0.600628E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.615832E+09 | 0.453907E+10 |
February | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.116597E+10 | 0.325836E+10 |
March | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.180012E+10 | 0.234347E+10 |
April | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.339318E+10 | 0.163015E+10 |
May | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.387965E+10 | 0.104412E+10 |
June | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.486669E+10 | 0.718781E+09 |
July | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.554306E+10 | 0.668575E+09 |
August | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.488202E+10 | 0.759636E+09 |
September | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.352022E+10 | 0.118156E+10 |
October | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.203510E+10 | 0.178302E+10 |
November | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.789408E+09 | 0.265100E+10 |
December | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.539882E+09 | 0.406159E+10 |
Annual Sum or Average | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.330311E+11 | 0.246393E+11 |
Minimum of Months | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.539882E+09 | 0.668575E+09 |
Maximum of Months | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.554306E+10 | 0.453907E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316526E+09 | 0.00 | 0.316526E+09 | 1941332.17 | 0.245835E+10 |
February | 0.362458E+09 | 0.00 | 0.362458E+09 | 25847112.50 | 0.177833E+10 |
March | 0.601414E+09 | 0.00 | 0.601414E+09 | 0.215950E+09 | 0.123921E+10 |
April | 0.671895E+09 | 3310394.98 | 0.668584E+09 | 0.415714E+09 | 0.801932E+09 |
May | 0.905369E+09 | 34030729.52 | 0.871338E+09 | 0.847587E+09 | 0.477101E+09 |
June | 0.102403E+10 | 92944440.68 | 0.931090E+09 | 0.118571E+10 | 0.330429E+09 |
July | 0.992397E+09 | 66380465.61 | 0.926016E+09 | 0.119037E+10 | 0.304668E+09 |
August | 0.830927E+09 | 14726350.73 | 0.816201E+09 | 0.982965E+09 | 0.368479E+09 |
September | 0.616532E+09 | 152872.31 | 0.616379E+09 | 0.571950E+09 | 0.635074E+09 |
October | 0.473683E+09 | 0.00 | 0.473683E+09 | 0.224483E+09 | 0.998403E+09 |
November | 0.320658E+09 | 0.00 | 0.320658E+09 | 52736825.23 | 0.147903E+10 |
December | 0.214931E+09 | 0.00 | 0.214931E+09 | 240294.11 | 0.220239E+10 |
Annual Sum or Average | 0.733082E+10 | 0.211545E+09 | 0.711928E+10 | 0.571550E+10 | 0.130734E+11 |
Minimum of Months | 0.214931E+09 | 0.00 | 0.214931E+09 | 240294.11 | 0.304668E+09 |
Maximum of Months | 0.102403E+10 | 92944440.68 | 0.931090E+09 | 0.119037E+10 | 0.245835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316546E+09 | 0.00 | 0.316546E+09 | 1941454.86 | 0.245850E+10 |
February | 0.362481E+09 | 0.00 | 0.362481E+09 | 25848745.99 | 0.177844E+10 |
March | 0.601452E+09 | 0.00 | 0.601452E+09 | 0.215963E+09 | 0.123929E+10 |
April | 0.671937E+09 | 3310604.19 | 0.668627E+09 | 0.415741E+09 | 0.801983E+09 |
May | 0.905426E+09 | 34032880.20 | 0.871393E+09 | 0.847640E+09 | 0.477131E+09 |
June | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.118579E+10 | 0.330450E+09 |
July | 0.992460E+09 | 66384660.75 | 0.926075E+09 | 0.119045E+10 | 0.304687E+09 |
August | 0.830980E+09 | 14727281.41 | 0.816252E+09 | 0.983027E+09 | 0.368503E+09 |
September | 0.616571E+09 | 152881.97 | 0.616418E+09 | 0.571986E+09 | 0.635115E+09 |
October | 0.473713E+09 | 0.00 | 0.473713E+09 | 0.224497E+09 | 0.998466E+09 |
November | 0.320678E+09 | 0.00 | 0.320678E+09 | 52740158.11 | 0.147913E+10 |
December | 0.214945E+09 | 0.00 | 0.214945E+09 | 240309.29 | 0.220253E+10 |
Annual Sum or Average | 0.733129E+10 | 0.211559E+09 | 0.711973E+10 | 0.571586E+10 | 0.130742E+11 |
Minimum of Months | 0.214945E+09 | 0.00 | 0.214945E+09 | 240309.29 | 0.304687E+09 |
Maximum of Months | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.119045E+10 | 0.245850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316546E+09 | 0.00 | 0.316546E+09 | 1941454.86 | 0.245850E+10 |
February | 0.362481E+09 | 0.00 | 0.362481E+09 | 25848745.99 | 0.177844E+10 |
March | 0.601452E+09 | 0.00 | 0.601452E+09 | 0.215963E+09 | 0.123929E+10 |
April | 0.671937E+09 | 3310604.19 | 0.668627E+09 | 0.415741E+09 | 0.801983E+09 |
May | 0.905426E+09 | 34032880.20 | 0.871393E+09 | 0.847640E+09 | 0.477131E+09 |
June | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.118579E+10 | 0.330450E+09 |
July | 0.992460E+09 | 66384660.75 | 0.926075E+09 | 0.119045E+10 | 0.304687E+09 |
August | 0.830980E+09 | 14727281.41 | 0.816252E+09 | 0.983027E+09 | 0.368503E+09 |
September | 0.616571E+09 | 152881.97 | 0.616418E+09 | 0.571986E+09 | 0.635115E+09 |
October | 0.473713E+09 | 0.00 | 0.473713E+09 | 0.224497E+09 | 0.998466E+09 |
November | 0.320678E+09 | 0.00 | 0.320678E+09 | 52740158.11 | 0.147913E+10 |
December | 0.214945E+09 | 0.00 | 0.214945E+09 | 240309.29 | 0.220253E+10 |
Annual Sum or Average | 0.733129E+10 | 0.211559E+09 | 0.711973E+10 | 0.571586E+10 | 0.130742E+11 |
Minimum of Months | 0.214945E+09 | 0.00 | 0.214945E+09 | 240309.29 | 0.304687E+09 |
Maximum of Months | 0.102410E+10 | 92950314.62 | 0.931149E+09 | 0.119045E+10 | 0.245850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130495E+10 | 0.536989E+09 | 0.767963E+09 | 0.581444E+09 | 0.428656E+10 |
February | 0.156232E+10 | 0.686978E+09 | 0.875337E+09 | 0.921107E+09 | 0.306507E+10 |
March | 0.235014E+10 | 0.932837E+09 | 0.141731E+10 | 0.186738E+10 | 0.221332E+10 |
April | 0.279266E+10 | 0.122299E+10 | 0.156967E+10 | 0.274386E+10 | 0.151110E+10 |
May | 0.362427E+10 | 0.158364E+10 | 0.204064E+10 | 0.410797E+10 | 0.953120E+09 |
June | 0.385976E+10 | 0.168086E+10 | 0.217890E+10 | 0.480433E+10 | 0.653360E+09 |
July | 0.403127E+10 | 0.186011E+10 | 0.217116E+10 | 0.511387E+10 | 0.604962E+09 |
August | 0.339828E+10 | 0.146507E+10 | 0.193321E+10 | 0.430948E+10 | 0.719916E+09 |
September | 0.293319E+10 | 0.138608E+10 | 0.154711E+10 | 0.342964E+10 | 0.119145E+10 |
October | 0.193154E+10 | 0.806784E+09 | 0.112475E+10 | 0.171323E+10 | 0.181658E+10 |
November | 0.110286E+10 | 0.358228E+09 | 0.744634E+09 | 0.586624E+09 | 0.264755E+10 |
December | 0.882763E+09 | 0.379078E+09 | 0.503685E+09 | 0.399191E+09 | 0.392829E+10 |
Annual Sum or Average | 0.297740E+11 | 0.128996E+11 | 0.168744E+11 | 0.305781E+11 | 0.235913E+11 |
Minimum of Months | 0.882763E+09 | 0.358228E+09 | 0.503685E+09 | 0.399191E+09 | 0.604962E+09 |
Maximum of Months | 0.403127E+10 | 0.186011E+10 | 0.217890E+10 | 0.511387E+10 | 0.428656E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51596621.93 | 21232073.00 | 30364548.93 | 22989765.44 | 0.169487E+09 |
February | 61772548.54 | 27162502.69 | 34610045.85 | 36419754.62 | 0.121190E+09 |
March | 92922567.74 | 36883552.92 | 56039014.82 | 73834488.53 | 87512782.60 |
April | 0.110419E+09 | 48355943.15 | 62063460.04 | 0.108490E+09 | 59747394.10 |
May | 0.143301E+09 | 62615530.52 | 80685009.18 | 0.162425E+09 | 37685497.08 |
June | 0.152611E+09 | 66459530.08 | 86151818.62 | 0.189959E+09 | 25833255.25 |
July | 0.159393E+09 | 73547039.82 | 85845646.08 | 0.202198E+09 | 23919633.54 |
August | 0.134365E+09 | 57927429.67 | 76437569.58 | 0.170393E+09 | 28464828.26 |
September | 0.115976E+09 | 54804259.11 | 61171327.77 | 0.135605E+09 | 47108929.48 |
October | 76371238.38 | 31899528.86 | 44471709.52 | 67739562.01 | 71826048.84 |
November | 43606186.80 | 14164032.29 | 29442154.51 | 23194577.14 | 0.104682E+09 |
December | 34903658.97 | 14988410.26 | 19915248.71 | 15783650.45 | 0.155321E+09 |
Annual Sum or Average | 0.117724E+10 | 0.510040E+09 | 0.667198E+09 | 0.120903E+10 | 0.932778E+09 |
Minimum of Months | 34903658.97 | 14164032.29 | 19915248.71 | 15783650.45 | 23919633.54 |
Maximum of Months | 0.159393E+09 | 73547039.82 | 86151818.62 | 0.202198E+09 | 0.169487E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+10 | 0.134715E+10 | 0.621441E+09 | 0.179355E+10 | 0.195546E+10 |
February | 0.190518E+10 | 0.128716E+10 | 0.618026E+09 | 0.180431E+10 | 0.144937E+10 |
March | 0.183557E+10 | 0.966552E+09 | 0.869020E+09 | 0.182703E+10 | 0.115364E+10 |
April | 0.160038E+10 | 0.748210E+09 | 0.852172E+09 | 0.176768E+10 | 0.825733E+09 |
May | 0.137006E+10 | 0.371441E+09 | 0.998616E+09 | 0.162023E+10 | 0.520746E+09 |
June | 0.128721E+10 | 0.262083E+09 | 0.102513E+10 | 0.166641E+10 | 0.349445E+09 |
July | 0.140802E+10 | 0.354785E+09 | 0.105324E+10 | 0.188219E+10 | 0.327118E+09 |
August | 0.158638E+10 | 0.568912E+09 | 0.101746E+10 | 0.213939E+10 | 0.402914E+09 |
September | 0.186034E+10 | 0.980247E+09 | 0.880094E+09 | 0.233706E+10 | 0.653152E+09 |
October | 0.200734E+10 | 0.125932E+10 | 0.748016E+09 | 0.221870E+10 | 0.980057E+09 |
November | 0.146568E+10 | 0.917542E+09 | 0.548136E+09 | 0.138750E+10 | 0.131160E+10 |
December | 0.161503E+10 | 0.122337E+10 | 0.391664E+09 | 0.155498E+10 | 0.186023E+10 |
Annual Sum or Average | 0.199098E+11 | 0.102868E+11 | 0.962302E+10 | 0.219990E+11 | 0.117895E+11 |
Minimum of Months | 0.128721E+10 | 0.262083E+09 | 0.391664E+09 | 0.138750E+10 | 0.327118E+09 |
Maximum of Months | 0.200734E+10 | 0.134715E+10 | 0.105324E+10 | 0.233706E+10 | 0.195546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+10 | 0.134715E+10 | 0.621441E+09 | 0.179355E+10 | 0.195546E+10 |
February | 0.190518E+10 | 0.128716E+10 | 0.618026E+09 | 0.180431E+10 | 0.144937E+10 |
March | 0.183557E+10 | 0.966552E+09 | 0.869020E+09 | 0.182703E+10 | 0.115364E+10 |
April | 0.160038E+10 | 0.748210E+09 | 0.852172E+09 | 0.176768E+10 | 0.825733E+09 |
May | 0.137006E+10 | 0.371441E+09 | 0.998616E+09 | 0.162023E+10 | 0.520746E+09 |
June | 0.128721E+10 | 0.262083E+09 | 0.102513E+10 | 0.166641E+10 | 0.349445E+09 |
July | 0.140802E+10 | 0.354785E+09 | 0.105324E+10 | 0.188219E+10 | 0.327118E+09 |
August | 0.158638E+10 | 0.568912E+09 | 0.101746E+10 | 0.213939E+10 | 0.402914E+09 |
September | 0.186034E+10 | 0.980247E+09 | 0.880094E+09 | 0.233706E+10 | 0.653152E+09 |
October | 0.200734E+10 | 0.125932E+10 | 0.748016E+09 | 0.221870E+10 | 0.980057E+09 |
November | 0.146568E+10 | 0.917542E+09 | 0.548136E+09 | 0.138750E+10 | 0.131160E+10 |
December | 0.161503E+10 | 0.122337E+10 | 0.391664E+09 | 0.155498E+10 | 0.186023E+10 |
Annual Sum or Average | 0.199098E+11 | 0.102868E+11 | 0.962302E+10 | 0.219990E+11 | 0.117895E+11 |
Minimum of Months | 0.128721E+10 | 0.262083E+09 | 0.391664E+09 | 0.138750E+10 | 0.327118E+09 |
Maximum of Months | 0.200734E+10 | 0.134715E+10 | 0.105324E+10 | 0.233706E+10 | 0.195546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196847E+10 | 0.134706E+10 | 0.621402E+09 | 0.179344E+10 | 0.195533E+10 |
February | 0.190506E+10 | 0.128708E+10 | 0.617987E+09 | 0.180419E+10 | 0.144928E+10 |
March | 0.183546E+10 | 0.966491E+09 | 0.868965E+09 | 0.182691E+10 | 0.115357E+10 |
April | 0.160028E+10 | 0.748163E+09 | 0.852118E+09 | 0.176757E+10 | 0.825681E+09 |
May | 0.136997E+10 | 0.371418E+09 | 0.998553E+09 | 0.162013E+10 | 0.520713E+09 |
June | 0.128713E+10 | 0.262067E+09 | 0.102506E+10 | 0.166631E+10 | 0.349423E+09 |
July | 0.140793E+10 | 0.354763E+09 | 0.105317E+10 | 0.188207E+10 | 0.327098E+09 |
August | 0.158628E+10 | 0.568876E+09 | 0.101740E+10 | 0.213926E+10 | 0.402888E+09 |
September | 0.186022E+10 | 0.980185E+09 | 0.880038E+09 | 0.233691E+10 | 0.653111E+09 |
October | 0.200721E+10 | 0.125924E+10 | 0.747969E+09 | 0.221856E+10 | 0.979995E+09 |
November | 0.146559E+10 | 0.917484E+09 | 0.548101E+09 | 0.138741E+10 | 0.131152E+10 |
December | 0.161493E+10 | 0.122329E+10 | 0.391640E+09 | 0.155488E+10 | 0.186012E+10 |
Annual Sum or Average | 0.199085E+11 | 0.102861E+11 | 0.962241E+10 | 0.219976E+11 | 0.117887E+11 |
Minimum of Months | 0.128713E+10 | 0.262067E+09 | 0.391640E+09 | 0.138741E+10 | 0.327098E+09 |
Maximum of Months | 0.200721E+10 | 0.134706E+10 | 0.105317E+10 | 0.233691E+10 | 0.195533E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129420E+10 | 0.523645E+09 | 0.770550E+09 | 0.607528E+09 | 0.438750E+10 |
February | 0.171406E+10 | 0.844634E+09 | 0.869425E+09 | 0.114303E+10 | 0.317615E+10 |
March | 0.226547E+10 | 0.842876E+09 | 0.142260E+10 | 0.177766E+10 | 0.228658E+10 |
April | 0.319805E+10 | 0.158137E+10 | 0.161668E+10 | 0.332660E+10 | 0.158626E+10 |
May | 0.331421E+10 | 0.132394E+10 | 0.199027E+10 | 0.379463E+10 | 0.100160E+10 |
June | 0.376339E+10 | 0.163095E+10 | 0.213244E+10 | 0.472011E+10 | 0.701479E+09 |
July | 0.417543E+10 | 0.198338E+10 | 0.219204E+10 | 0.535287E+10 | 0.670653E+09 |
August | 0.365037E+10 | 0.167528E+10 | 0.197510E+10 | 0.469731E+10 | 0.783165E+09 |
September | 0.285955E+10 | 0.135729E+10 | 0.150227E+10 | 0.336675E+10 | 0.124317E+10 |
October | 0.205908E+10 | 0.915439E+09 | 0.114364E+10 | 0.192909E+10 | 0.189779E+10 |
November | 0.119274E+10 | 0.441071E+09 | 0.751664E+09 | 0.744785E+09 | 0.271107E+10 |
December | 0.947851E+09 | 0.446829E+09 | 0.501022E+09 | 0.523223E+09 | 0.401208E+10 |
Annual Sum or Average | 0.304344E+11 | 0.135667E+11 | 0.168677E+11 | 0.319836E+11 | 0.244575E+11 |
Minimum of Months | 0.947851E+09 | 0.441071E+09 | 0.501022E+09 | 0.523223E+09 | 0.670653E+09 |
Maximum of Months | 0.417543E+10 | 0.198338E+10 | 0.219204E+10 | 0.535287E+10 | 0.438750E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 51171174.57 | 20704391.81 | 30466782.76 | 24020958.58 | 0.173478E+09 |
February | 67772152.36 | 33395940.93 | 34376211.43 | 45194024.40 | 0.125582E+09 |
March | 89574520.26 | 33326463.27 | 56248056.99 | 70286644.68 | 90409445.39 |
April | 0.126448E+09 | 62525836.95 | 63921762.13 | 0.131530E+09 | 62719109.16 |
May | 0.131041E+09 | 52347344.96 | 78693297.11 | 0.150036E+09 | 39602292.66 |
June | 0.148801E+09 | 64486185.81 | 84314374.07 | 0.186628E+09 | 27735821.49 |
July | 0.165092E+09 | 78420958.81 | 86671142.14 | 0.211647E+09 | 26516982.97 |
August | 0.144332E+09 | 66238656.53 | 78093356.14 | 0.185727E+09 | 30965610.94 |
September | 0.113064E+09 | 53665679.25 | 59398210.88 | 0.133118E+09 | 49153848.75 |
October | 81413805.37 | 36195505.22 | 45218300.15 | 76273998.71 | 75037028.68 |
November | 47159554.11 | 17439491.87 | 29720062.24 | 29448005.58 | 0.107193E+09 |
December | 37477073.33 | 17667157.90 | 19809915.43 | 20687659.02 | 0.158634E+09 |
Annual Sum or Average | 0.120335E+10 | 0.536414E+09 | 0.666931E+09 | 0.126460E+10 | 0.967028E+09 |
Minimum of Months | 37477073.33 | 17439491.87 | 19809915.43 | 20687659.02 | 26516982.97 |
Maximum of Months | 0.165092E+09 | 78420958.81 | 86671142.14 | 0.211647E+09 | 0.173478E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.949622E+09 | 0.00 | 0.949622E+09 | 4497764.77 | 0.749346E+10 |
February | 0.108742E+10 | 0.00 | 0.108742E+10 | 68954962.28 | 0.545653E+10 |
March | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.582350E+09 | 0.386643E+10 |
April | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.113636E+10 | 0.259016E+10 |
May | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.238285E+10 | 0.156686E+10 |
June | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.346693E+10 | 0.105467E+10 |
July | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.350986E+10 | 0.954453E+09 |
August | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.291945E+10 | 0.112336E+10 |
September | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.170553E+10 | 0.188915E+10 |
October | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.673461E+09 | 0.294587E+10 |
November | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.157267E+09 | 0.439131E+10 |
December | 0.644823E+09 | 0.00 | 0.644823E+09 | 581105.92 | 0.663232E+10 |
Annual Sum or Average | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.166081E+11 | 0.399646E+11 |
Minimum of Months | 0.644823E+09 | 0.00 | 0.644823E+09 | 581105.92 | 0.954453E+09 |
Maximum of Months | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.350986E+10 | 0.749346E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.589367E+09 | 0.450781E+10 |
February | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.934391E+09 | 0.323215E+10 |
March | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.188024E+10 | 0.236625E+10 |
April | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.277284E+10 | 0.164875E+10 |
May | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.419181E+10 | 0.103357E+10 |
June | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.494657E+10 | 0.693366E+09 |
July | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.528748E+10 | 0.626079E+09 |
August | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.446576E+10 | 0.732172E+09 |
September | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.356354E+10 | 0.119267E+10 |
October | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.178654E+10 | 0.182764E+10 |
November | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.609124E+09 | 0.271302E+10 |
December | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.409331E+09 | 0.408803E+10 |
Annual Sum or Average | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.314370E+11 | 0.246615E+11 |
Minimum of Months | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.409331E+09 | 0.626079E+09 |
Maximum of Months | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.528748E+10 | 0.450781E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.519473E+10 | 0.613210E+10 |
February | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.523637E+10 | 0.448896E+10 |
March | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.529982E+10 | 0.361451E+10 |
April | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.514479E+10 | 0.263385E+10 |
May | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.468323E+10 | 0.169326E+10 |
June | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.488838E+10 | 0.112149E+10 |
July | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.557881E+10 | 0.100920E+10 |
August | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.637629E+10 | 0.119490E+10 |
September | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.696967E+10 | 0.190270E+10 |
October | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.659400E+10 | 0.283182E+10 |
November | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.409615E+10 | 0.391054E+10 |
December | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.456521E+10 | 0.572110E+10 |
Annual Sum or Average | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.646275E+11 | 0.362544E+11 |
Minimum of Months | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.409615E+10 | 0.100920E+10 |
Maximum of Months | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.696967E+10 | 0.613210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.613763E+09 | 0.461836E+10 |
February | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.115858E+10 | 0.335308E+10 |
March | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.178522E+10 | 0.244900E+10 |
April | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.338188E+10 | 0.172281E+10 |
May | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.386264E+10 | 0.110069E+10 |
June | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.485968E+10 | 0.752755E+09 |
July | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.554037E+10 | 0.694218E+09 |
August | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.487302E+10 | 0.796147E+09 |
September | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.349955E+10 | 0.125411E+10 |
October | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.200172E+10 | 0.191731E+10 |
November | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.770260E+09 | 0.277912E+10 |
December | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.534281E+09 | 0.417605E+10 |
Annual Sum or Average | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.328810E+11 | 0.256137E+11 |
Minimum of Months | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.534281E+09 | 0.694218E+09 |
Maximum of Months | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.554037E+10 | 0.461836E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.01 | 2750.49 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 31.49 | 2193.81 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 227.06 | 1381.61 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 450.46 | 940.31 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 907.77 | 552.42 | 1014.13 | 38.12 | 976.01 | 0.00 | 0.00 |
June | 1345.67 | 387.54 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1314.63 | 342.45 | 1111.61 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1097.85 | 398.85 | 930.74 | 16.50 | 914.25 | 0.00 | 0.00 |
September | 674.63 | 679.78 | 713.61 | 0.18 | 713.44 | 0.00 | 0.00 |
October | 274.72 | 1016.45 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 70.65 | 1611.96 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.79 | 2408.53 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 536.15 | 1217.51 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.79 | 342.45 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1345.67 | 2750.49 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.22 | 1654.27 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 391.43 | 1297.79 | 671.34 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 710.49 | 846.17 | 912.14 | 362.06 | 550.09 | 0.00 | 0.00 |
April | 1076.19 | 603.29 | 1120.03 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1570.14 | 368.57 | 1406.66 | 614.65 | 792.02 | 0.00 | 0.00 |
June | 1909.09 | 256.83 | 1547.99 | 674.13 | 873.87 | 0.00 | 0.00 |
July | 1972.61 | 226.30 | 1564.63 | 721.95 | 842.67 | 0.00 | 0.00 |
August | 1668.78 | 262.25 | 1318.95 | 568.63 | 750.32 | 0.00 | 0.00 |
September | 1382.03 | 435.10 | 1176.38 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 683.54 | 636.07 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 244.43 | 998.47 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 155.92 | 1483.95 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 1002.21 | 753.30 | 981.47 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 155.92 | 226.30 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1972.61 | 1654.27 | 1564.63 | 721.95 | 873.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1947.26 | 2242.49 | 2204.89 | 1508.85 | 696.04 | 0.00 | 0.00 |
February | 2177.09 | 1793.76 | 2362.50 | 1596.12 | 766.38 | 0.00 | 0.00 |
March | 1990.87 | 1289.51 | 2055.91 | 1082.57 | 973.34 | 0.00 | 0.00 |
April | 1992.87 | 961.03 | 1852.24 | 865.96 | 986.28 | 0.00 | 0.00 |
May | 1757.59 | 599.10 | 1534.52 | 416.03 | 1118.49 | 0.00 | 0.00 |
June | 1889.65 | 411.55 | 1489.78 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2083.49 | 361.89 | 1577.04 | 397.37 | 1179.67 | 0.00 | 0.00 |
August | 2383.23 | 424.86 | 1776.80 | 637.20 | 1139.60 | 0.00 | 0.00 |
September | 2699.17 | 691.03 | 2153.11 | 1134.51 | 1018.60 | 0.00 | 0.00 |
October | 2485.26 | 982.90 | 2248.29 | 1410.49 | 837.81 | 0.00 | 0.00 |
November | 1600.85 | 1433.80 | 1696.33 | 1061.94 | 634.40 | 0.00 | 0.00 |
December | 1715.41 | 2069.18 | 1808.89 | 1370.21 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2059.43 | 1101.96 | 1893.95 | 978.54 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1600.85 | 361.89 | 1489.78 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2699.17 | 2242.49 | 2362.50 | 1596.12 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.93 | 1694.69 | 502.31 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 481.97 | 1346.88 | 736.54 | 362.95 | 373.60 | 0.00 | 0.00 |
March | 672.09 | 874.95 | 879.28 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1309.10 | 628.92 | 1282.61 | 634.23 | 648.38 | 0.00 | 0.00 |
May | 1448.49 | 389.83 | 1286.32 | 513.85 | 772.47 | 0.00 | 0.00 |
June | 1877.58 | 277.31 | 1509.34 | 654.11 | 855.23 | 0.00 | 0.00 |
July | 2069.54 | 249.62 | 1620.58 | 769.80 | 850.78 | 0.00 | 0.00 |
August | 1822.74 | 283.62 | 1416.79 | 650.21 | 766.58 | 0.00 | 0.00 |
September | 1358.11 | 455.85 | 1146.85 | 544.35 | 602.50 | 0.00 | 0.00 |
October | 759.82 | 665.70 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 304.56 | 1022.76 | 478.36 | 176.90 | 301.46 | 0.00 | 0.00 |
December | 201.57 | 1516.42 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1047.41 | 781.31 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 201.57 | 249.62 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2069.54 | 1694.69 | 1620.58 | 769.80 | 855.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.17 | 2753.64 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 32.05 | 2205.36 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 241.89 | 1388.06 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 481.17 | 928.20 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 949.40 | 534.41 | 1014.12 | 38.12 | 976.00 | 0.00 | 0.00 |
June | 1372.41 | 382.46 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1333.36 | 341.26 | 1111.60 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1101.04 | 412.74 | 930.74 | 16.50 | 914.24 | 0.00 | 0.00 |
September | 662.01 | 735.07 | 713.61 | 0.18 | 713.43 | 0.00 | 0.00 |
October | 251.45 | 1118.33 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 61.04 | 1711.91 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.27 | 2466.94 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 543.73 | 1243.72 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.27 | 341.26 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1372.41 | 2753.64 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 225.67 | 1663.70 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 395.80 | 1317.07 | 671.33 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 724.77 | 859.03 | 912.14 | 362.05 | 550.08 | 0.00 | 0.00 |
April | 1100.44 | 606.04 | 1120.02 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1594.38 | 369.92 | 1406.65 | 614.64 | 792.01 | 0.00 | 0.00 |
June | 1926.81 | 262.03 | 1547.98 | 674.12 | 873.86 | 0.00 | 0.00 |
July | 1984.79 | 234.80 | 1564.61 | 721.94 | 842.67 | 0.00 | 0.00 |
August | 1672.59 | 279.41 | 1318.94 | 568.62 | 750.32 | 0.00 | 0.00 |
September | 1375.48 | 477.84 | 1176.37 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 664.94 | 705.05 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 235.27 | 1061.82 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 154.93 | 1524.65 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 1007.96 | 777.65 | 981.46 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 154.93 | 234.80 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1984.79 | 1663.70 | 1564.61 | 721.94 | 873.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2008.86 | 2190.20 | 2204.92 | 1508.87 | 696.04 | 0.00 | 0.00 |
February | 2237.44 | 1797.29 | 2362.53 | 1596.14 | 766.39 | 0.00 | 0.00 |
March | 2046.36 | 1292.13 | 2055.93 | 1082.58 | 973.34 | 0.00 | 0.00 |
April | 2045.89 | 955.69 | 1852.26 | 865.97 | 986.29 | 0.00 | 0.00 |
May | 1814.74 | 583.26 | 1534.53 | 416.03 | 1118.50 | 0.00 | 0.00 |
June | 1928.68 | 404.44 | 1489.80 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2108.14 | 366.39 | 1577.05 | 397.38 | 1179.68 | 0.00 | 0.00 |
August | 2396.22 | 451.28 | 1776.82 | 637.21 | 1139.61 | 0.00 | 0.00 |
September | 2704.87 | 755.95 | 2153.13 | 1134.52 | 1018.61 | 0.00 | 0.00 |
October | 2485.05 | 1097.71 | 2248.32 | 1410.50 | 837.81 | 0.00 | 0.00 |
November | 1605.87 | 1518.02 | 1696.35 | 1061.95 | 634.40 | 0.00 | 0.00 |
December | 1741.65 | 2083.55 | 1808.91 | 1370.23 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2092.71 | 1121.50 | 1893.97 | 978.55 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1605.87 | 366.39 | 1489.80 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2704.87 | 2190.20 | 2362.53 | 1596.14 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 235.79 | 1702.87 | 502.30 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 491.16 | 1364.80 | 736.54 | 362.94 | 373.60 | 0.00 | 0.00 |
March | 689.94 | 887.47 | 879.27 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1334.15 | 636.18 | 1282.60 | 634.22 | 648.38 | 0.00 | 0.00 |
May | 1472.77 | 388.74 | 1286.31 | 513.85 | 772.46 | 0.00 | 0.00 |
June | 1893.03 | 281.33 | 1509.33 | 654.10 | 855.23 | 0.00 | 0.00 |
July | 2077.55 | 260.29 | 1620.56 | 769.79 | 850.77 | 0.00 | 0.00 |
August | 1823.12 | 303.96 | 1416.78 | 650.21 | 766.57 | 0.00 | 0.00 |
September | 1350.26 | 498.58 | 1146.84 | 544.35 | 602.49 | 0.00 | 0.00 |
October | 748.72 | 736.57 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 298.70 | 1087.29 | 478.35 | 176.89 | 301.46 | 0.00 | 0.00 |
December | 203.07 | 1557.17 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1054.29 | 806.21 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 203.07 | 260.29 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2077.55 | 1702.87 | 1620.56 | 769.79 | 855.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.68 | 2797.74 | 354.55 | 0.00 | 354.55 | 0.00 | 0.00 |
February | 28.50 | 2255.51 | 449.50 | 0.00 | 449.50 | 0.00 | 0.00 |
March | 217.42 | 1443.56 | 673.66 | 0.00 | 673.66 | 0.00 | 0.00 |
April | 438.41 | 999.29 | 777.69 | 3.83 | 773.86 | 0.00 | 0.00 |
May | 889.66 | 585.00 | 1014.13 | 38.12 | 976.01 | 0.00 | 0.00 |
June | 1337.55 | 406.89 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
July | 1310.43 | 356.35 | 1111.61 | 74.35 | 1037.25 | 0.00 | 0.00 |
August | 1090.00 | 419.41 | 930.74 | 16.50 | 914.25 | 0.00 | 0.00 |
September | 658.00 | 728.84 | 713.61 | 0.18 | 713.44 | 0.00 | 0.00 |
October | 251.44 | 1099.86 | 530.58 | 0.00 | 530.58 | 0.00 | 0.00 |
November | 60.67 | 1694.18 | 371.15 | 0.00 | 371.15 | 0.00 | 0.00 |
December | 0.22 | 2476.23 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Annual Sum or Average | 526.64 | 1267.27 | 697.41 | 20.13 | 677.28 | 0.00 | 0.00 |
Minimum of Months | 0.22 | 356.35 | 240.75 | 0.00 | 240.75 | 0.00 | 0.00 |
Maximum of Months | 1337.55 | 2797.74 | 1185.28 | 107.58 | 1077.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.04 | 1683.02 | 506.48 | 208.42 | 298.06 | 0.00 | 0.00 |
February | 386.24 | 1336.04 | 671.34 | 295.20 | 376.14 | 0.00 | 0.00 |
March | 702.00 | 883.46 | 912.14 | 362.06 | 550.09 | 0.00 | 0.00 |
April | 1069.77 | 636.09 | 1120.03 | 490.49 | 629.53 | 0.00 | 0.00 |
May | 1565.04 | 385.89 | 1406.66 | 614.65 | 792.02 | 0.00 | 0.00 |
June | 1908.40 | 267.50 | 1547.99 | 674.13 | 873.87 | 0.00 | 0.00 |
July | 1974.12 | 233.75 | 1564.63 | 721.95 | 842.67 | 0.00 | 0.00 |
August | 1667.32 | 273.36 | 1318.95 | 568.63 | 750.32 | 0.00 | 0.00 |
September | 1374.82 | 460.13 | 1176.38 | 555.90 | 620.48 | 0.00 | 0.00 |
October | 667.02 | 682.36 | 749.67 | 313.13 | 436.54 | 0.00 | 0.00 |
November | 235.00 | 1046.69 | 442.31 | 143.67 | 298.64 | 0.00 | 0.00 |
December | 152.83 | 1526.30 | 342.62 | 147.13 | 195.49 | 0.00 | 0.00 |
Annual Sum or Average | 996.86 | 782.01 | 981.47 | 425.22 | 556.24 | 0.00 | 0.00 |
Minimum of Months | 152.83 | 233.75 | 342.62 | 143.67 | 195.49 | 0.00 | 0.00 |
Maximum of Months | 1974.12 | 1683.02 | 1564.63 | 721.95 | 873.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1939.49 | 2289.46 | 2204.89 | 1508.85 | 696.04 | 0.00 | 0.00 |
February | 2164.50 | 1855.56 | 2362.50 | 1596.12 | 766.38 | 0.00 | 0.00 |
March | 1978.73 | 1349.50 | 2055.91 | 1082.57 | 973.34 | 0.00 | 0.00 |
April | 1984.87 | 1016.14 | 1852.24 | 865.96 | 986.28 | 0.00 | 0.00 |
May | 1748.52 | 632.19 | 1534.52 | 416.03 | 1118.49 | 0.00 | 0.00 |
June | 1885.95 | 432.67 | 1489.78 | 303.33 | 1186.46 | 0.00 | 0.00 |
July | 2082.89 | 376.79 | 1577.04 | 397.37 | 1179.67 | 0.00 | 0.00 |
August | 2380.63 | 446.13 | 1776.80 | 637.20 | 1139.60 | 0.00 | 0.00 |
September | 2688.91 | 734.07 | 2153.11 | 1134.51 | 1018.60 | 0.00 | 0.00 |
October | 2461.92 | 1057.28 | 2248.29 | 1410.49 | 837.81 | 0.00 | 0.00 |
November | 1580.31 | 1508.69 | 1696.33 | 1061.94 | 634.40 | 0.00 | 0.00 |
December | 1704.45 | 2136.01 | 1808.89 | 1370.21 | 438.68 | 0.00 | 0.00 |
Annual Sum or Average | 2049.32 | 1149.62 | 1893.95 | 978.54 | 915.41 | 0.00 | 0.00 |
Minimum of Months | 1580.31 | 376.79 | 1489.78 | 303.33 | 438.68 | 0.00 | 0.00 |
Maximum of Months | 2688.91 | 2289.46 | 2362.50 | 1596.12 | 1186.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.15 | 1724.30 | 502.31 | 203.24 | 299.07 | 0.00 | 0.00 |
February | 478.91 | 1386.03 | 736.54 | 362.95 | 373.60 | 0.00 | 0.00 |
March | 666.52 | 914.35 | 879.28 | 327.14 | 552.14 | 0.00 | 0.00 |
April | 1304.74 | 664.67 | 1282.61 | 634.23 | 648.38 | 0.00 | 0.00 |
May | 1442.15 | 410.95 | 1286.32 | 513.85 | 772.47 | 0.00 | 0.00 |
June | 1874.88 | 290.41 | 1509.34 | 654.11 | 855.23 | 0.00 | 0.00 |
July | 2068.54 | 259.19 | 1620.58 | 769.80 | 850.78 | 0.00 | 0.00 |
August | 1819.38 | 297.25 | 1416.79 | 650.21 | 766.58 | 0.00 | 0.00 |
September | 1350.14 | 483.84 | 1146.85 | 544.35 | 602.50 | 0.00 | 0.00 |
October | 747.36 | 715.84 | 799.17 | 355.30 | 443.87 | 0.00 | 0.00 |
November | 297.17 | 1072.19 | 478.36 | 176.90 | 301.46 | 0.00 | 0.00 |
December | 199.48 | 1559.16 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Annual Sum or Average | 1042.65 | 812.20 | 1003.23 | 447.21 | 556.02 | 0.00 | 0.00 |
Minimum of Months | 199.48 | 259.19 | 367.88 | 173.42 | 194.46 | 0.00 | 0.00 |
Maximum of Months | 2068.54 | 1724.30 | 1620.58 | 769.80 | 855.23 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5377189.26 | 0.736691E+10 | 0.949622E+09 | 0.00 | 0.949622E+09 | 0.00 | 0.00 |
February | 76174593.61 | 0.530726E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.608149E+09 | 0.370051E+10 | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.00 | 0.00 |
April | 0.116758E+10 | 0.243728E+10 | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.00 | 0.00 |
May | 0.243137E+10 | 0.147960E+10 | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.00 | 0.00 |
June | 0.348799E+10 | 0.100452E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
July | 0.352109E+10 | 0.917224E+09 | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.00 | 0.00 |
August | 0.294047E+10 | 0.106829E+10 | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.00 | 0.00 |
September | 0.174863E+10 | 0.176199E+10 | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.00 | 0.00 |
October | 0.735814E+09 | 0.272247E+10 | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.00 | 0.00 |
November | 0.183113E+09 | 0.417820E+10 | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.00 | 0.00 |
December | 2122025.75 | 0.645100E+10 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169079E+11 | 0.383952E+11 | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.00 | 0.00 |
Minimum of Months | 2122025.75 | 0.917224E+09 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Maximum of Months | 0.352109E+10 | 0.736691E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595203E+09 | 0.443080E+10 | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.00 | 0.00 |
February | 0.946947E+09 | 0.313962E+10 | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.00 | 0.00 |
March | 0.190298E+10 | 0.226638E+10 | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.278949E+10 | 0.156374E+10 | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.00 | 0.00 |
May | 0.420547E+10 | 0.987185E+09 | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.00 | 0.00 |
June | 0.494837E+10 | 0.665700E+09 | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.00 | 0.00 |
July | 0.528343E+10 | 0.606119E+09 | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.00 | 0.00 |
August | 0.446967E+10 | 0.702411E+09 | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.00 | 0.00 |
September | 0.358223E+10 | 0.112779E+10 | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.00 | 0.00 |
October | 0.183079E+10 | 0.170366E+10 | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.00 | 0.00 |
November | 0.633561E+09 | 0.258803E+10 | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.00 | 0.00 |
December | 0.417618E+09 | 0.397462E+10 | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.316057E+11 | 0.237560E+11 | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.417618E+09 | 0.606119E+09 | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528343E+10 | 0.443080E+10 | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.521554E+10 | 0.600628E+10 | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.00 | 0.00 |
February | 0.526683E+10 | 0.433947E+10 | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.00 | 0.00 |
March | 0.533235E+10 | 0.345381E+10 | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.00 | 0.00 |
April | 0.516552E+10 | 0.249100E+10 | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.00 | 0.00 |
May | 0.470753E+10 | 0.160463E+10 | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.00 | 0.00 |
June | 0.489796E+10 | 0.106673E+10 | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.00 | 0.00 |
July | 0.558042E+10 | 0.969291E+09 | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.00 | 0.00 |
August | 0.638324E+10 | 0.113795E+10 | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.00 | 0.00 |
September | 0.699625E+10 | 0.179115E+10 | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.00 | 0.00 |
October | 0.665651E+10 | 0.263259E+10 | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.00 | 0.00 |
November | 0.414940E+10 | 0.371642E+10 | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.00 | 0.00 |
December | 0.459457E+10 | 0.554210E+10 | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.649461E+11 | 0.347514E+11 | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.414940E+10 | 0.969291E+09 | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.699625E+10 | 0.600628E+10 | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.615832E+09 | 0.453907E+10 | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.00 | 0.00 |
February | 0.116597E+10 | 0.325836E+10 | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.00 | 0.00 |
March | 0.180012E+10 | 0.234347E+10 | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.00 | 0.00 |
April | 0.339318E+10 | 0.163015E+10 | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.00 | 0.00 |
May | 0.387965E+10 | 0.104412E+10 | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.00 | 0.00 |
June | 0.486669E+10 | 0.718781E+09 | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.00 | 0.00 |
July | 0.554306E+10 | 0.668575E+09 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
August | 0.488202E+10 | 0.759636E+09 | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.00 | 0.00 |
September | 0.352022E+10 | 0.118156E+10 | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.00 | 0.00 |
October | 0.203510E+10 | 0.178302E+10 | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.789408E+09 | 0.265100E+10 | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.00 | 0.00 |
December | 0.539882E+09 | 0.406159E+10 | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330311E+11 | 0.246393E+11 | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.539882E+09 | 0.668575E+09 | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554306E+10 | 0.453907E+10 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5824241.90 | 0.737536E+10 | 0.949617E+09 | 0.00 | 0.949617E+09 | 0.00 | 0.00 |
February | 77544604.49 | 0.533520E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.647876E+09 | 0.371778E+10 | 0.180432E+10 | 0.00 | 0.180432E+10 | 0.00 | 0.00 |
April | 0.124720E+10 | 0.240590E+10 | 0.201577E+10 | 9931603.37 | 0.200584E+10 | 0.00 | 0.00 |
May | 0.254287E+10 | 0.143136E+10 | 0.271622E+10 | 0.102096E+09 | 0.261412E+10 | 0.00 | 0.00 |
June | 0.355729E+10 | 0.991330E+09 | 0.307223E+10 | 0.278845E+09 | 0.279339E+10 | 0.00 | 0.00 |
July | 0.357127E+10 | 0.914043E+09 | 0.297732E+10 | 0.199150E+09 | 0.277817E+10 | 0.00 | 0.00 |
August | 0.294902E+10 | 0.110548E+10 | 0.249289E+10 | 44180913.56 | 0.244871E+10 | 0.00 | 0.00 |
September | 0.171592E+10 | 0.190530E+10 | 0.184967E+10 | 458636.24 | 0.184921E+10 | 0.00 | 0.00 |
October | 0.673478E+09 | 0.299533E+10 | 0.142111E+10 | 0.00 | 0.142111E+10 | 0.00 | 0.00 |
November | 0.158217E+09 | 0.443728E+10 | 0.962013E+09 | 0.00 | 0.962013E+09 | 0.00 | 0.00 |
December | 720912.70 | 0.660745E+10 | 0.644820E+09 | 0.00 | 0.644820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171472E+11 | 0.392218E+11 | 0.219934E+11 | 0.634663E+09 | 0.213587E+11 | 0.00 | 0.00 |
Minimum of Months | 720912.70 | 0.914043E+09 | 0.644820E+09 | 0.00 | 0.644820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.357127E+10 | 0.737536E+10 | 0.307223E+10 | 0.278845E+09 | 0.279339E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.604434E+09 | 0.445605E+10 | 0.135655E+10 | 0.558221E+09 | 0.798327E+09 | 0.00 | 0.00 |
February | 0.957527E+09 | 0.318626E+10 | 0.162409E+10 | 0.714141E+09 | 0.909947E+09 | 0.00 | 0.00 |
March | 0.194121E+10 | 0.230084E+10 | 0.244307E+10 | 0.969721E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.285235E+10 | 0.157084E+10 | 0.290308E+10 | 0.127135E+10 | 0.163174E+10 | 0.00 | 0.00 |
May | 0.427039E+10 | 0.990805E+09 | 0.376757E+10 | 0.164625E+10 | 0.212132E+10 | 0.00 | 0.00 |
June | 0.499429E+10 | 0.679193E+09 | 0.401237E+10 | 0.174732E+10 | 0.226505E+10 | 0.00 | 0.00 |
July | 0.531607E+10 | 0.628881E+09 | 0.419066E+10 | 0.193366E+10 | 0.225700E+10 | 0.00 | 0.00 |
August | 0.447987E+10 | 0.748381E+09 | 0.353265E+10 | 0.152299E+10 | 0.200965E+10 | 0.00 | 0.00 |
September | 0.356525E+10 | 0.123856E+10 | 0.304916E+10 | 0.144088E+10 | 0.160828E+10 | 0.00 | 0.00 |
October | 0.178097E+10 | 0.188841E+10 | 0.200791E+10 | 0.838684E+09 | 0.116922E+10 | 0.00 | 0.00 |
November | 0.609818E+09 | 0.275223E+10 | 0.114647E+10 | 0.372393E+09 | 0.774076E+09 | 0.00 | 0.00 |
December | 0.414975E+09 | 0.408361E+10 | 0.917667E+09 | 0.394067E+09 | 0.523600E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.317872E+11 | 0.245241E+11 | 0.309512E+11 | 0.134097E+11 | 0.175416E+11 | 0.00 | 0.00 |
Minimum of Months | 0.414975E+09 | 0.628881E+09 | 0.917667E+09 | 0.372393E+09 | 0.523600E+09 | 0.00 | 0.00 |
Maximum of Months | 0.531607E+10 | 0.445605E+10 | 0.419066E+10 | 0.193366E+10 | 0.226505E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538054E+10 | 0.586624E+10 | 0.590565E+10 | 0.404136E+10 | 0.186428E+10 | 0.00 | 0.00 |
February | 0.541280E+10 | 0.434801E+10 | 0.571543E+10 | 0.386139E+10 | 0.185404E+10 | 0.00 | 0.00 |
March | 0.548096E+10 | 0.346084E+10 | 0.550660E+10 | 0.289959E+10 | 0.260701E+10 | 0.00 | 0.00 |
April | 0.530294E+10 | 0.247715E+10 | 0.480105E+10 | 0.224458E+10 | 0.255646E+10 | 0.00 | 0.00 |
May | 0.486059E+10 | 0.156220E+10 | 0.411009E+10 | 0.111430E+10 | 0.299579E+10 | 0.00 | 0.00 |
June | 0.499913E+10 | 0.104831E+10 | 0.386155E+10 | 0.786234E+09 | 0.307532E+10 | 0.00 | 0.00 |
July | 0.564645E+10 | 0.981334E+09 | 0.422398E+10 | 0.106433E+10 | 0.315965E+10 | 0.00 | 0.00 |
August | 0.641804E+10 | 0.120872E+10 | 0.475903E+10 | 0.170670E+10 | 0.305232E+10 | 0.00 | 0.00 |
September | 0.701102E+10 | 0.195941E+10 | 0.558090E+10 | 0.294068E+10 | 0.264023E+10 | 0.00 | 0.00 |
October | 0.665596E+10 | 0.294011E+10 | 0.602189E+10 | 0.377789E+10 | 0.224400E+10 | 0.00 | 0.00 |
November | 0.416240E+10 | 0.393472E+10 | 0.439694E+10 | 0.275257E+10 | 0.164437E+10 | 0.00 | 0.00 |
December | 0.466483E+10 | 0.558058E+10 | 0.484499E+10 | 0.367002E+10 | 0.117497E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659957E+11 | 0.353676E+11 | 0.597281E+11 | 0.308597E+11 | 0.288684E+11 | 0.00 | 0.00 |
Minimum of Months | 0.416240E+10 | 0.981334E+09 | 0.386155E+10 | 0.786234E+09 | 0.117497E+10 | 0.00 | 0.00 |
Maximum of Months | 0.701102E+10 | 0.586624E+10 | 0.602189E+10 | 0.404136E+10 | 0.315965E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.631549E+09 | 0.456097E+10 | 0.134537E+10 | 0.544350E+09 | 0.801017E+09 | 0.00 | 0.00 |
February | 0.118822E+10 | 0.330174E+10 | 0.178183E+10 | 0.878029E+09 | 0.903801E+09 | 0.00 | 0.00 |
March | 0.184794E+10 | 0.237699E+10 | 0.235505E+10 | 0.876203E+09 | 0.147884E+10 | 0.00 | 0.00 |
April | 0.345813E+10 | 0.164897E+10 | 0.332450E+10 | 0.164390E+10 | 0.168060E+10 | 0.00 | 0.00 |
May | 0.394466E+10 | 0.104120E+10 | 0.344525E+10 | 0.137629E+10 | 0.206896E+10 | 0.00 | 0.00 |
June | 0.490674E+10 | 0.729214E+09 | 0.391219E+10 | 0.169544E+10 | 0.221675E+10 | 0.00 | 0.00 |
July | 0.556452E+10 | 0.697170E+09 | 0.434052E+10 | 0.206180E+10 | 0.227871E+10 | 0.00 | 0.00 |
August | 0.488303E+10 | 0.814130E+09 | 0.379470E+10 | 0.174151E+10 | 0.205319E+10 | 0.00 | 0.00 |
September | 0.349987E+10 | 0.129232E+10 | 0.297262E+10 | 0.141095E+10 | 0.156167E+10 | 0.00 | 0.00 |
October | 0.200536E+10 | 0.197283E+10 | 0.214049E+10 | 0.951634E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.774233E+09 | 0.281826E+10 | 0.123989E+10 | 0.458510E+09 | 0.781385E+09 | 0.00 | 0.00 |
December | 0.543911E+09 | 0.417072E+10 | 0.985328E+09 | 0.464496E+09 | 0.520832E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.332482E+11 | 0.254245E+11 | 0.316377E+11 | 0.141031E+11 | 0.175346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.543911E+09 | 0.697170E+09 | 0.985328E+09 | 0.458510E+09 | 0.520832E+09 | 0.00 | 0.00 |
Maximum of Months | 0.556452E+10 | 0.456097E+10 | 0.434052E+10 | 0.206180E+10 | 0.227871E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4497764.77 | 0.749346E+10 | 0.949622E+09 | 0.00 | 0.949622E+09 | 0.00 | 0.00 |
February | 68954962.28 | 0.545653E+10 | 0.108742E+10 | 0.00 | 0.108742E+10 | 0.00 | 0.00 |
March | 0.582350E+09 | 0.386643E+10 | 0.180433E+10 | 0.00 | 0.180433E+10 | 0.00 | 0.00 |
April | 0.113636E+10 | 0.259016E+10 | 0.201578E+10 | 9931654.83 | 0.200585E+10 | 0.00 | 0.00 |
May | 0.238285E+10 | 0.156686E+10 | 0.271624E+10 | 0.102097E+09 | 0.261414E+10 | 0.00 | 0.00 |
June | 0.346693E+10 | 0.105467E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
July | 0.350986E+10 | 0.954453E+09 | 0.297733E+10 | 0.199151E+09 | 0.277818E+10 | 0.00 | 0.00 |
August | 0.291945E+10 | 0.112336E+10 | 0.249290E+10 | 44181142.49 | 0.244872E+10 | 0.00 | 0.00 |
September | 0.170553E+10 | 0.188915E+10 | 0.184968E+10 | 458638.62 | 0.184922E+10 | 0.00 | 0.00 |
October | 0.673461E+09 | 0.294587E+10 | 0.142112E+10 | 0.00 | 0.142112E+10 | 0.00 | 0.00 |
November | 0.157267E+09 | 0.439131E+10 | 0.962018E+09 | 0.00 | 0.962018E+09 | 0.00 | 0.00 |
December | 581105.92 | 0.663232E+10 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166081E+11 | 0.399646E+11 | 0.219935E+11 | 0.634666E+09 | 0.213588E+11 | 0.00 | 0.00 |
Minimum of Months | 581105.92 | 0.954453E+09 | 0.644823E+09 | 0.00 | 0.644823E+09 | 0.00 | 0.00 |
Maximum of Months | 0.350986E+10 | 0.749346E+10 | 0.307225E+10 | 0.278847E+09 | 0.279340E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589367E+09 | 0.450781E+10 | 0.135656E+10 | 0.558227E+09 | 0.798332E+09 | 0.00 | 0.00 |
February | 0.934391E+09 | 0.323215E+10 | 0.162410E+10 | 0.714148E+09 | 0.909953E+09 | 0.00 | 0.00 |
March | 0.188024E+10 | 0.236625E+10 | 0.244309E+10 | 0.969731E+09 | 0.147335E+10 | 0.00 | 0.00 |
April | 0.277284E+10 | 0.164875E+10 | 0.290310E+10 | 0.127136E+10 | 0.163175E+10 | 0.00 | 0.00 |
May | 0.419181E+10 | 0.103357E+10 | 0.376760E+10 | 0.164627E+10 | 0.212134E+10 | 0.00 | 0.00 |
June | 0.494657E+10 | 0.693366E+09 | 0.401240E+10 | 0.174733E+10 | 0.226507E+10 | 0.00 | 0.00 |
July | 0.528748E+10 | 0.626079E+09 | 0.419069E+10 | 0.193368E+10 | 0.225702E+10 | 0.00 | 0.00 |
August | 0.446576E+10 | 0.732172E+09 | 0.353267E+10 | 0.152301E+10 | 0.200966E+10 | 0.00 | 0.00 |
September | 0.356354E+10 | 0.119267E+10 | 0.304919E+10 | 0.144090E+10 | 0.160829E+10 | 0.00 | 0.00 |
October | 0.178654E+10 | 0.182764E+10 | 0.200792E+10 | 0.838692E+09 | 0.116923E+10 | 0.00 | 0.00 |
November | 0.609124E+09 | 0.271302E+10 | 0.114648E+10 | 0.372396E+09 | 0.774081E+09 | 0.00 | 0.00 |
December | 0.409331E+09 | 0.408803E+10 | 0.917674E+09 | 0.394071E+09 | 0.523603E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314370E+11 | 0.246615E+11 | 0.309515E+11 | 0.134098E+11 | 0.175417E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409331E+09 | 0.626079E+09 | 0.917674E+09 | 0.372396E+09 | 0.523603E+09 | 0.00 | 0.00 |
Maximum of Months | 0.528748E+10 | 0.450781E+10 | 0.419069E+10 | 0.193368E+10 | 0.226507E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519473E+10 | 0.613210E+10 | 0.590558E+10 | 0.404132E+10 | 0.186427E+10 | 0.00 | 0.00 |
February | 0.523637E+10 | 0.448896E+10 | 0.571537E+10 | 0.386134E+10 | 0.185402E+10 | 0.00 | 0.00 |
March | 0.529982E+10 | 0.361451E+10 | 0.550655E+10 | 0.289956E+10 | 0.260699E+10 | 0.00 | 0.00 |
April | 0.514479E+10 | 0.263385E+10 | 0.480100E+10 | 0.224456E+10 | 0.255645E+10 | 0.00 | 0.00 |
May | 0.468323E+10 | 0.169326E+10 | 0.411005E+10 | 0.111429E+10 | 0.299577E+10 | 0.00 | 0.00 |
June | 0.488838E+10 | 0.112149E+10 | 0.386152E+10 | 0.786225E+09 | 0.307530E+10 | 0.00 | 0.00 |
July | 0.557881E+10 | 0.100920E+10 | 0.422395E+10 | 0.106432E+10 | 0.315963E+10 | 0.00 | 0.00 |
August | 0.637629E+10 | 0.119490E+10 | 0.475899E+10 | 0.170668E+10 | 0.305230E+10 | 0.00 | 0.00 |
September | 0.696967E+10 | 0.190270E+10 | 0.558085E+10 | 0.294064E+10 | 0.264021E+10 | 0.00 | 0.00 |
October | 0.659400E+10 | 0.283182E+10 | 0.602183E+10 | 0.377785E+10 | 0.224398E+10 | 0.00 | 0.00 |
November | 0.409615E+10 | 0.391054E+10 | 0.439690E+10 | 0.275254E+10 | 0.164436E+10 | 0.00 | 0.00 |
December | 0.456521E+10 | 0.572110E+10 | 0.484494E+10 | 0.366998E+10 | 0.117496E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646275E+11 | 0.362544E+11 | 0.597275E+11 | 0.308593E+11 | 0.288682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409615E+10 | 0.100920E+10 | 0.386152E+10 | 0.786225E+09 | 0.117496E+10 | 0.00 | 0.00 |
Maximum of Months | 0.696967E+10 | 0.613210E+10 | 0.602183E+10 | 0.404132E+10 | 0.315963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.613763E+09 | 0.461836E+10 | 0.134538E+10 | 0.544355E+09 | 0.801022E+09 | 0.00 | 0.00 |
February | 0.115858E+10 | 0.335308E+10 | 0.178185E+10 | 0.878038E+09 | 0.903807E+09 | 0.00 | 0.00 |
March | 0.178522E+10 | 0.244900E+10 | 0.235507E+10 | 0.876212E+09 | 0.147885E+10 | 0.00 | 0.00 |
April | 0.338188E+10 | 0.172281E+10 | 0.332452E+10 | 0.164391E+10 | 0.168061E+10 | 0.00 | 0.00 |
May | 0.386264E+10 | 0.110069E+10 | 0.344528E+10 | 0.137630E+10 | 0.206897E+10 | 0.00 | 0.00 |
June | 0.485968E+10 | 0.752755E+09 | 0.391222E+10 | 0.169546E+10 | 0.221676E+10 | 0.00 | 0.00 |
July | 0.554037E+10 | 0.694218E+09 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
August | 0.487302E+10 | 0.796147E+09 | 0.379473E+10 | 0.174153E+10 | 0.205320E+10 | 0.00 | 0.00 |
September | 0.349955E+10 | 0.125411E+10 | 0.297264E+10 | 0.141097E+10 | 0.156168E+10 | 0.00 | 0.00 |
October | 0.200172E+10 | 0.191731E+10 | 0.214051E+10 | 0.951644E+09 | 0.118886E+10 | 0.00 | 0.00 |
November | 0.770260E+09 | 0.277912E+10 | 0.123990E+10 | 0.458515E+09 | 0.781390E+09 | 0.00 | 0.00 |
December | 0.534281E+09 | 0.417605E+10 | 0.985336E+09 | 0.464501E+09 | 0.520835E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.328810E+11 | 0.256137E+11 | 0.316380E+11 | 0.141033E+11 | 0.175347E+11 | 0.00 | 0.00 |
Minimum of Months | 0.534281E+09 | 0.694218E+09 | 0.985336E+09 | 0.458515E+09 | 0.520835E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554037E+10 | 0.461836E+10 | 0.434055E+10 | 0.206183E+10 | 0.227872E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.593702E+10 | -0.517007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -766955465.6 | 58.99 | 0.00 | 0.00 |
February | 0.546882E+10 | -0.479335E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -675470257.3 | 58.98 | 0.00 | 0.00 |
March | 0.634346E+10 | -0.561757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -725887170.8 | 58.98 | 0.00 | 0.00 |
April | 0.554793E+10 | -0.486067E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -687263325.4 | 58.98 | 0.00 | 0.00 |
May | 0.560056E+10 | -0.490721E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693349555.8 | 58.98 | 0.00 | 0.00 |
June | 0.521400E+10 | -0.454477E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669230795.7 | 58.99 | 0.00 | 0.00 |
July | 0.472813E+10 | -0.404000E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688134794.0 | 58.98 | 0.00 | 0.00 |
August | 0.503966E+10 | -0.435019E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689471408.2 | 58.99 | 0.00 | 0.00 |
September | 0.463869E+10 | -0.397022E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668469740.7 | 58.98 | 0.00 | 0.00 |
October | 0.501036E+10 | -0.430727E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703097712.5 | 58.99 | 0.00 | 0.00 |
November | 0.523000E+10 | -0.452979E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -700207212.0 | 58.98 | 0.00 | 0.00 |
December | 0.553410E+10 | -0.478529E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -748815388.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.642928E+11 | -0.558764E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.841635E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463869E+10 | -0.561757E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -766955465.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.634346E+10 | -0.397022E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -668469740.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6687.30 | 36.99 | 205.17 | 240.33 | 5558.63 | 37.99 | 202.17 | 218.33 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7968.16 | 37.24 | 222.33 | 253.33 | 2270.95 | 28.64 | 180.00 | 234.33 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 7279.81 | 29.91 | 261.50 | 323.67 | 1336.51 | 21.21 | 183.00 | 287.17 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 2098.73 | 18.08 | 0.00 | 342.33 | 1250.45 | 20.86 | 142.33 | 291.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1622.07 | 17.66 | 0.00 | 389.00 | 904.18 | 20.42 | 166.17 | 341.83 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1649.24 | 17.89 | 0.00 | 390.00 | 934.35 | 20.67 | 184.50 | 345.83 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1711.61 | 18.20 | 0.00 | 401.33 | 979.35 | 20.98 | 202.67 | 355.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1905.05 | 18.12 | 0.00 | 373.83 | 1068.11 | 20.88 | 213.50 | 337.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2792.20 | 19.94 | 26.00 | 328.67 | 1357.23 | 21.41 | 186.33 | 297.00 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6861.56 | 32.86 | 292.00 | 301.83 | 1793.21 | 22.66 | 179.33 | 279.83 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4771.68 | 32.30 | 231.33 | 244.67 | 2589.89 | 30.66 | 221.50 | 221.83 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5814.22 | 35.63 | 167.50 | 215.33 | 5367.23 | 38.59 | 177.33 | 175.33 |
Annual Sum or Average | 3807.33 | 0.63 | 3824.36 | 24.51 | 1405.83 | 3804.33 | 1786.20 | 23.99 | 2238.83 | 3385.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1622.07 | 17.66 | 0.00 | 215.33 | 904.18 | 20.42 | 142.33 | 175.33 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7968.16 | 37.24 | 292.00 | 401.33 | 5558.63 | 38.59 | 221.50 | 355.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1722.75 | 21.28 | 65.67 | 224.17 | 876.99 | 22.22 | 81.83 | 173.00 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2068.07 | 20.37 | 62.83 | 233.67 | 1182.25 | 23.48 | 82.67 | 195.50 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2732.11 | 20.84 | 100.33 | 314.83 | 1116.23 | 21.13 | 67.33 | 272.17 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 3203.61 | 20.53 | 77.17 | 342.67 | 1882.34 | 22.36 | 60.00 | 299.83 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:10 | 3292.10 | 20.01 | 112.00 | 396.67 | 1428.73 | 21.73 | 77.50 | 352.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 3009.59 | 20.04 | 95.67 | 398.83 | 1636.35 | 21.89 | 68.33 | 362.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3834.91 | 21.58 | 123.33 | 408.17 | 1651.06 | 22.18 | 70.00 | 371.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 3035.26 | 20.34 | 110.50 | 376.00 | 1364.74 | 22.13 | 73.33 | 348.50 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 3061.69 | 21.36 | 95.17 | 324.00 | 1727.41 | 23.04 | 83.33 | 285.50 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1885.59 | 19.67 | 84.00 | 285.50 | 1048.21 | 22.57 | 90.67 | 251.00 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1460.52 | 18.93 | 64.50 | 226.83 | 802.04 | 21.74 | 74.00 | 179.17 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1354.35 | 20.88 | 63.83 | 186.83 | 697.90 | 21.51 | 60.50 | 113.17 |
Annual Sum or Average | 3807.33 | 0.63 | 2719.45 | 20.48 | 1055.00 | 3718.17 | 1344.10 | 22.14 | 889.50 | 3203.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1354.35 | 18.93 | 62.83 | 186.83 | 697.90 | 21.13 | 60.00 | 113.17 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3834.91 | 21.58 | 123.33 | 408.17 | 1882.34 | 23.48 | 90.67 | 371.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 588.69 | 14.46 | 0.00 | 203.83 | 362.64 | 17.56 | 0.00 | 114.50 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:30 | 620.28 | 14.83 | 0.00 | 218.50 | 389.01 | 17.90 | 0.00 | 144.33 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 847.69 | 16.47 | 0.00 | 311.50 | 494.41 | 19.25 | 0.00 | 249.67 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 992.27 | 17.47 | 0.00 | 345.00 | 614.94 | 20.22 | 27.33 | 278.00 |
May | 428.67 | 0.62 | 0.62 | 01-MAY-05:30 | 1128.73 | 17.87 | 3.17 | 408.67 | 644.63 | 21.54 | 112.17 | 370.00 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1360.62 | 21.21 | 75.50 | 409.67 | 801.90 | 23.65 | 203.17 | 387.50 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1284.53 | 19.77 | 30.67 | 419.33 | 760.71 | 22.46 | 181.50 | 391.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1062.50 | 17.80 | 0.00 | 385.50 | 623.31 | 20.51 | 60.17 | 352.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 877.40 | 17.14 | 0.00 | 325.83 | 542.97 | 19.91 | 1.17 | 266.00 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 693.29 | 15.41 | 0.00 | 274.00 | 412.60 | 18.30 | 0.00 | 207.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 590.29 | 14.40 | 0.00 | 213.17 | 336.79 | 17.24 | 0.00 | 119.50 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 427.70 | 12.96 | 0.00 | 156.17 | 272.30 | 16.24 | 0.00 | 40.33 |
Annual Sum or Average | 3807.33 | 0.63 | 938.30 | 17.15 | 109.33 | 3671.17 | 557.65 | 20.05 | 585.50 | 2920.33 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 427.70 | 12.96 | 0.00 | 156.17 | 272.30 | 16.24 | 0.00 | 40.33 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1360.62 | 21.21 | 75.50 | 419.33 | 801.90 | 23.65 | 203.17 | 391.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1780.90 | 20.66 | 67.17 | 220.17 | 1089.40 | 23.83 | 84.83 | 172.00 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2141.97 | 20.54 | 63.33 | 234.17 | 1137.58 | 21.67 | 58.67 | 197.67 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2326.29 | 20.54 | 93.67 | 316.33 | 1255.10 | 22.12 | 86.67 | 275.50 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:49 | 4120.30 | 21.51 | 84.50 | 344.17 | 1726.28 | 21.32 | 39.50 | 288.50 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2490.39 | 16.72 | 49.67 | 396.67 | 1349.77 | 18.34 | 0.00 | 357.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:19 | 3153.06 | 17.20 | 50.33 | 398.50 | 1444.36 | 18.78 | 0.00 | 362.17 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3553.69 | 17.70 | 56.00 | 407.50 | 1552.50 | 19.01 | 2.17 | 372.50 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2973.82 | 19.17 | 84.33 | 380.00 | 1666.04 | 21.07 | 55.83 | 344.83 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3103.90 | 21.58 | 96.67 | 328.17 | 1789.83 | 23.16 | 73.50 | 292.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:10 | 1945.43 | 19.75 | 82.17 | 286.50 | 1040.89 | 21.44 | 72.00 | 249.17 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1508.34 | 18.97 | 68.83 | 230.50 | 843.26 | 21.46 | 68.33 | 184.17 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:20 | 1428.56 | 19.81 | 55.00 | 191.50 | 769.32 | 20.90 | 44.00 | 110.00 |
Annual Sum or Average | 3807.33 | 0.63 | 2663.33 | 19.26 | 851.67 | 3734.17 | 1357.57 | 20.83 | 585.50 | 3206.33 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1428.56 | 16.72 | 49.67 | 191.50 | 769.32 | 18.34 | 0.00 | 110.00 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4120.30 | 21.58 | 96.67 | 407.50 | 1789.83 | 23.83 | 86.67 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6391.49 | 34.41 | 188.00 | 236.33 | 5412.56 | 37.61 | 200.00 | 216.17 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7739.07 | 35.81 | 211.50 | 249.67 | 2135.56 | 26.63 | 105.67 | 232.17 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 7136.34 | 29.13 | 248.00 | 322.50 | 1239.89 | 18.40 | 5.33 | 283.50 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 1976.40 | 14.56 | 0.00 | 340.00 | 1164.75 | 18.54 | 10.00 | 285.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1542.31 | 14.04 | 0.00 | 386.67 | 853.94 | 17.95 | 0.00 | 336.67 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1570.34 | 14.50 | 0.00 | 388.00 | 886.15 | 18.41 | 0.00 | 341.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1627.31 | 14.82 | 0.00 | 397.50 | 926.88 | 18.75 | 1.17 | 350.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1805.29 | 14.58 | 0.00 | 371.33 | 1003.19 | 18.50 | 1.33 | 333.83 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2654.42 | 16.59 | 26.00 | 326.67 | 1260.13 | 18.97 | 22.83 | 293.17 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6698.25 | 32.11 | 287.00 | 301.17 | 1685.33 | 19.90 | 30.83 | 277.33 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4592.29 | 30.85 | 216.83 | 241.50 | 2490.49 | 29.44 | 181.00 | 218.50 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5628.86 | 34.66 | 164.67 | 213.00 | 5190.01 | 37.07 | 169.00 | 170.17 |
Annual Sum or Average | 3807.33 | 0.63 | 3688.26 | 21.93 | 1342.00 | 3774.33 | 1698.72 | 21.81 | 727.17 | 3338.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1542.31 | 14.04 | 0.00 | 213.00 | 853.94 | 17.95 | 0.00 | 170.17 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7739.07 | 35.81 | 287.00 | 397.50 | 5412.56 | 37.61 | 200.00 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1666.43 | 20.85 | 65.67 | 220.67 | 836.31 | 21.98 | 75.00 | 166.67 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2005.25 | 19.93 | 62.83 | 230.67 | 1134.45 | 23.27 | 75.17 | 191.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2658.20 | 20.44 | 99.67 | 312.33 | 1062.22 | 20.91 | 56.33 | 268.00 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 3109.29 | 20.13 | 77.00 | 341.00 | 1811.83 | 22.17 | 57.17 | 290.83 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:19 | 3204.48 | 19.61 | 111.83 | 395.17 | 1365.28 | 21.55 | 77.67 | 347.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 2903.81 | 19.59 | 94.67 | 397.17 | 1565.41 | 21.72 | 68.33 | 359.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3646.92 | 19.95 | 101.83 | 406.17 | 1579.88 | 22.01 | 70.00 | 367.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 2937.12 | 19.79 | 108.17 | 373.33 | 1300.90 | 21.95 | 72.17 | 345.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 2832.89 | 19.34 | 74.67 | 321.83 | 1645.54 | 22.70 | 76.00 | 280.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1823.15 | 19.23 | 84.00 | 283.00 | 975.36 | 21.30 | 66.67 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1414.77 | 18.49 | 64.17 | 224.00 | 770.20 | 21.51 | 71.33 | 173.00 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1310.16 | 20.45 | 63.83 | 183.33 | 665.16 | 21.26 | 55.50 | 109.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2616.78 | 19.77 | 1008.33 | 3688.67 | 1282.72 | 21.84 | 821.33 | 3145.00 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1310.16 | 18.49 | 62.83 | 183.33 | 665.16 | 20.91 | 55.50 | 109.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3646.92 | 20.85 | 111.83 | 406.17 | 1811.83 | 23.27 | 77.67 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.62 | 01-JAN-09:39 | 561.63 | 10.97 | 0.00 | 199.00 | 348.35 | 15.16 | 0.00 | 107.67 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:39 | 592.84 | 11.47 | 0.00 | 213.00 | 374.70 | 15.65 | 0.00 | 134.00 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 812.04 | 13.05 | 0.00 | 307.33 | 475.54 | 16.99 | 0.00 | 241.33 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 950.84 | 14.45 | 0.00 | 343.33 | 593.53 | 18.41 | 1.33 | 270.00 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:30 | 1081.95 | 14.42 | 3.17 | 406.50 | 619.39 | 19.47 | 31.00 | 365.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1303.23 | 18.52 | 75.17 | 408.50 | 770.15 | 21.86 | 86.00 | 384.17 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1230.62 | 16.79 | 30.67 | 417.67 | 731.50 | 20.59 | 55.00 | 387.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1017.65 | 14.58 | 0.00 | 384.67 | 599.53 | 18.53 | 1.00 | 346.17 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 839.57 | 14.12 | 0.00 | 322.83 | 523.29 | 18.07 | 0.00 | 260.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 663.37 | 11.93 | 0.00 | 269.33 | 396.81 | 15.98 | 0.00 | 199.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 564.67 | 10.65 | 0.00 | 209.17 | 323.08 | 14.65 | 0.00 | 109.33 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 407.64 | 9.22 | 0.00 | 146.33 | 261.79 | 13.61 | 0.00 | 33.50 |
Annual Sum or Average | 3807.33 | 0.64 | 898.40 | 13.89 | 109.00 | 3627.67 | 536.34 | 17.95 | 174.33 | 2838.17 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 407.64 | 9.22 | 0.00 | 146.33 | 261.79 | 13.61 | 0.00 | 33.50 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1303.23 | 18.52 | 75.17 | 417.67 | 770.15 | 21.86 | 86.00 | 387.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 1725.44 | 20.32 | 67.17 | 218.17 | 1048.89 | 23.75 | 84.50 | 166.83 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2072.83 | 20.20 | 63.33 | 232.33 | 1084.95 | 21.56 | 57.67 | 192.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2153.97 | 18.60 | 70.83 | 314.50 | 1205.07 | 22.00 | 83.50 | 271.83 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:00 | 4018.64 | 21.14 | 84.50 | 342.00 | 1646.50 | 21.18 | 39.17 | 282.50 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2410.03 | 16.29 | 49.50 | 394.33 | 1291.79 | 18.16 | 0.00 | 354.17 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:30 | 3055.89 | 16.79 | 50.33 | 397.17 | 1373.90 | 18.61 | 0.00 | 359.33 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:49 | 3440.30 | 17.28 | 56.00 | 404.83 | 1474.67 | 18.85 | 2.17 | 369.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2775.59 | 18.78 | 84.00 | 377.83 | 1597.50 | 20.93 | 55.17 | 341.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3016.05 | 21.22 | 96.67 | 326.33 | 1722.41 | 23.02 | 72.50 | 287.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:19 | 1878.97 | 19.39 | 82.17 | 284.50 | 992.24 | 21.32 | 70.17 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1459.82 | 18.62 | 68.50 | 227.00 | 808.73 | 21.35 | 67.33 | 178.83 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:30 | 1383.70 | 19.47 | 55.00 | 187.33 | 735.39 | 20.80 | 43.50 | 104.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2561.70 | 18.74 | 828.00 | 3706.33 | 1298.08 | 20.69 | 575.67 | 3153.00 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1383.70 | 16.29 | 49.50 | 187.33 | 735.39 | 18.16 | 0.00 | 104.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4018.64 | 21.22 | 96.67 | 404.83 | 1722.41 | 23.75 | 84.50 | 369.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.63 | 0.62 | 01-JAN-09:39 | 6391.55 | 34.41 | 188.00 | 236.33 | 5412.48 | 37.61 | 200.00 | 216.17 |
February | 226.83 | 0.63 | 0.62 | 01-FEB-07:49 | 7739.08 | 35.81 | 211.50 | 249.67 | 2135.47 | 26.63 | 105.67 | 232.17 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 7136.26 | 29.13 | 248.00 | 322.50 | 1239.80 | 18.40 | 5.33 | 283.50 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 1976.33 | 14.56 | 0.00 | 340.00 | 1164.67 | 18.54 | 10.17 | 285.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:00 | 1542.24 | 14.04 | 0.00 | 386.67 | 853.88 | 17.95 | 0.00 | 336.67 |
June | 400.67 | 0.64 | 0.62 | 01-JUN-05:19 | 1570.28 | 14.50 | 0.00 | 388.00 | 886.09 | 18.41 | 0.00 | 341.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 1627.24 | 14.82 | 0.00 | 397.50 | 926.82 | 18.75 | 1.17 | 350.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 1805.21 | 14.59 | 0.00 | 371.33 | 1003.11 | 18.50 | 1.33 | 333.67 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:10 | 2654.35 | 16.59 | 26.00 | 326.67 | 1260.04 | 18.97 | 22.83 | 293.17 |
October | 325.17 | 0.63 | 0.62 | 01-OCT-06:40 | 6698.23 | 32.11 | 287.00 | 301.17 | 1685.25 | 19.90 | 30.83 | 277.33 |
November | 254.83 | 0.63 | 0.62 | 01-NOV-07:40 | 4592.30 | 30.85 | 216.83 | 241.50 | 2490.41 | 29.44 | 181.00 | 218.50 |
December | 186.17 | 0.63 | 0.62 | 01-DEC-07:00 | 5628.92 | 34.66 | 164.67 | 213.00 | 5189.96 | 37.07 | 169.00 | 170.17 |
Annual Sum or Average | 3807.33 | 0.63 | 3688.22 | 21.93 | 1342.00 | 3774.33 | 1698.64 | 21.81 | 727.33 | 3338.50 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1542.24 | 14.04 | 0.00 | 213.00 | 853.88 | 17.95 | 0.00 | 170.17 | |
Maximum of Months | 428.67 | 0.64 | 0.62 | 7739.08 | 35.81 | 287.00 | 397.50 | 5412.48 | 37.61 | 200.00 | 350.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.62 | 01-JAN-09:39 | 1666.44 | 20.85 | 65.67 | 220.67 | 836.27 | 21.98 | 75.00 | 166.67 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-07:49 | 2005.25 | 19.93 | 62.83 | 230.67 | 1134.40 | 23.27 | 75.17 | 191.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:40 | 2658.18 | 20.44 | 99.67 | 312.33 | 1062.16 | 20.91 | 56.33 | 268.00 |
April | 285.17 | 0.64 | 0.62 | 01-APR-06:40 | 3109.29 | 20.13 | 77.00 | 341.00 | 1811.78 | 22.17 | 57.17 | 290.67 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:19 | 3204.45 | 19.61 | 111.83 | 395.17 | 1365.22 | 21.55 | 77.67 | 347.83 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 2903.78 | 19.59 | 94.67 | 397.17 | 1565.34 | 21.72 | 68.33 | 359.00 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:40 | 3646.90 | 19.95 | 101.83 | 406.17 | 1579.81 | 22.01 | 70.00 | 367.83 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 2937.09 | 19.79 | 108.17 | 373.33 | 1300.84 | 21.95 | 72.17 | 345.33 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 2832.89 | 19.34 | 74.67 | 321.83 | 1645.48 | 22.70 | 76.17 | 280.33 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:40 | 1823.13 | 19.23 | 84.00 | 283.00 | 975.32 | 21.30 | 66.67 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:40 | 1414.76 | 18.49 | 64.17 | 224.00 | 770.16 | 21.51 | 71.33 | 173.00 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-07:00 | 1310.17 | 20.45 | 63.83 | 183.33 | 665.14 | 21.26 | 55.67 | 109.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2616.77 | 19.78 | 1008.33 | 3688.67 | 1282.67 | 21.84 | 821.67 | 3144.83 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1310.17 | 18.49 | 62.83 | 183.33 | 665.14 | 20.91 | 55.67 | 109.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 3646.90 | 20.85 | 111.83 | 406.17 | 1811.78 | 23.27 | 77.67 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.62 | 01-JAN-09:39 | 561.63 | 10.97 | 0.00 | 199.00 | 348.33 | 15.16 | 0.00 | 107.67 |
February | 226.83 | 0.65 | 0.62 | 01-FEB-08:39 | 592.84 | 11.47 | 0.00 | 213.00 | 374.68 | 15.65 | 0.00 | 134.00 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:49 | 812.02 | 13.06 | 0.00 | 307.33 | 475.51 | 16.99 | 0.00 | 241.33 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:40 | 950.83 | 14.45 | 0.00 | 343.33 | 593.50 | 18.41 | 1.33 | 270.00 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-05:30 | 1081.92 | 14.43 | 3.17 | 406.50 | 619.35 | 19.47 | 31.00 | 365.50 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-04:00 | 1303.21 | 18.53 | 75.17 | 408.50 | 770.10 | 21.86 | 86.00 | 384.17 |
July | 414.00 | 0.62 | 0.62 | 01-JUL-05:40 | 1230.60 | 16.79 | 30.67 | 417.67 | 731.46 | 20.59 | 55.33 | 387.17 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:40 | 1017.63 | 14.58 | 0.00 | 384.67 | 599.50 | 18.53 | 1.00 | 346.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-05:00 | 839.57 | 14.13 | 0.00 | 322.83 | 523.27 | 18.07 | 0.00 | 260.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-06:00 | 663.36 | 11.94 | 0.00 | 269.33 | 396.79 | 15.98 | 0.00 | 199.17 |
November | 254.83 | 0.65 | 0.62 | 01-NOV-07:00 | 564.66 | 10.65 | 0.00 | 209.17 | 323.06 | 14.65 | 0.00 | 109.17 |
December | 186.17 | 0.67 | 0.62 | 01-DEC-08:20 | 407.65 | 9.22 | 0.00 | 146.33 | 261.78 | 13.61 | 0.00 | 33.50 |
Annual Sum or Average | 3807.33 | 0.64 | 898.39 | 13.90 | 109.00 | 3627.67 | 536.31 | 17.95 | 174.67 | 2837.83 | ||
Minimum of Months | 186.17 | 0.62 | 0.62 | 407.65 | 9.22 | 0.00 | 146.33 | 261.78 | 13.61 | 0.00 | 33.50 | |
Maximum of Months | 428.67 | 0.67 | 0.62 | 1303.21 | 18.53 | 75.17 | 417.67 | 770.10 | 21.86 | 86.00 | 387.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.65 | 0.62 | 01-JAN-09:39 | 1725.44 | 20.32 | 67.17 | 218.17 | 1048.85 | 23.75 | 84.50 | 166.83 |
February | 226.83 | 0.64 | 0.62 | 01-FEB-08:39 | 2072.83 | 20.20 | 63.33 | 232.33 | 1084.91 | 21.56 | 57.83 | 192.83 |
March | 334.33 | 0.63 | 0.62 | 01-MAR-07:00 | 2153.95 | 18.60 | 70.83 | 314.50 | 1205.02 | 22.00 | 83.50 | 271.83 |
April | 285.17 | 0.63 | 0.62 | 01-APR-06:00 | 4018.63 | 21.15 | 84.50 | 342.00 | 1646.44 | 21.18 | 39.17 | 282.33 |
May | 428.67 | 0.63 | 0.62 | 01-MAY-06:40 | 2409.99 | 16.29 | 49.50 | 394.33 | 1291.73 | 18.16 | 0.00 | 354.17 |
June | 400.67 | 0.63 | 0.62 | 01-JUN-05:30 | 3055.87 | 16.79 | 50.33 | 397.17 | 1373.83 | 18.61 | 0.00 | 359.33 |
July | 414.00 | 0.63 | 0.62 | 01-JUL-05:49 | 3440.28 | 17.29 | 56.00 | 404.83 | 1474.60 | 18.85 | 2.17 | 369.00 |
August | 410.83 | 0.63 | 0.62 | 01-AUG-05:00 | 2775.57 | 18.78 | 84.00 | 377.83 | 1597.43 | 20.93 | 55.17 | 341.00 |
September | 326.50 | 0.63 | 0.62 | 01-SEP-06:19 | 3016.06 | 21.22 | 96.67 | 326.33 | 1722.35 | 23.03 | 72.50 | 287.17 |
October | 325.17 | 0.64 | 0.62 | 01-OCT-07:19 | 1878.96 | 19.39 | 82.17 | 284.50 | 992.20 | 21.32 | 70.17 | 244.83 |
November | 254.83 | 0.64 | 0.62 | 01-NOV-07:00 | 1459.80 | 18.62 | 68.50 | 227.00 | 808.69 | 21.35 | 67.50 | 178.83 |
December | 186.17 | 0.65 | 0.62 | 01-DEC-08:30 | 1383.70 | 19.47 | 55.00 | 187.33 | 735.37 | 20.80 | 43.50 | 104.50 |
Annual Sum or Average | 3807.33 | 0.63 | 2561.69 | 18.74 | 828.00 | 3706.33 | 1298.02 | 20.69 | 576.00 | 3152.67 | ||
Minimum of Months | 186.17 | 0.63 | 0.62 | 1383.70 | 16.29 | 49.50 | 187.33 | 735.37 | 18.16 | 0.00 | 104.50 | |
Maximum of Months | 428.67 | 0.65 | 0.62 | 4018.63 | 21.22 | 96.67 | 404.83 | 1722.35 | 23.75 | 84.50 | 369.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154478E+10 | 29326.93 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.409426E+09 | 29326.93 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27013248.82 | 29326.93 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146281E+09 | 29326.93 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378015E+09 | 29326.93 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.154478E+10 | 29326.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140707E+11 | 12173.07 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.995503E+10 | 12173.01 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839007E+10 | 12196.84 | 20-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466797E+10 | 12206.29 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147476E+10 | 12210.14 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.572638E+09 | 12483.50 | 19-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65327183.29 | 10833.54 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202934E+09 | 12439.54 | 07-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101574E+10 | 12444.06 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251975E+10 | 12230.57 | 13-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.665286E+10 | 12187.59 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112124E+11 | 12174.63 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.608002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 65327183.29 | 10833.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140707E+11 | 12483.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.653439E+10 | 10004.05 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427238E+10 | 9969.75 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254876E+10 | 9969.96 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109539E+10 | 9961.35 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19651265.24 | 9917.40 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3991211.52 | 1884.29 | 06-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20436829.75 | 9921.75 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233892E+09 | 9946.96 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217631E+10 | 9989.03 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472130E+10 | 9995.27 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.653439E+10 | 10004.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.980125E+10 | 8574.02 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657306E+10 | 8567.47 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386898E+10 | 8546.51 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148417E+10 | 8561.05 | 24-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54062985.13 | 8521.34 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18072684.17 | 8488.59 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232244E+09 | 8526.35 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282425E+10 | 8548.37 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.660686E+10 | 8568.15 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.980125E+10 | 8574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680194E+10 | 10762.17 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444877E+10 | 10725.22 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288961E+10 | 10725.47 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107112E+10 | 10716.18 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73758467.60 | 10681.31 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12934545.37 | 3599.35 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68474099.00 | 10673.57 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307093E+09 | 10700.70 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229694E+10 | 10719.60 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487987E+10 | 10752.68 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680194E+10 | 10762.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.571307E+10 | 30086.82 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282269E+10 | 30086.82 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100891E+10 | 30086.82 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204480E+09 | 30086.82 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6121290.95 | 30086.82 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160336E+10 | 30086.82 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350955E+10 | 30086.82 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571307E+10 | 30086.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.706793E+10 | 13970.09 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406230E+10 | 13948.16 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239614E+10 | 13931.12 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.875636E+09 | 13875.88 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25130182.39 | 13794.67 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 130054.89 | 450.79 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64436128.27 | 13760.26 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364490E+09 | 13762.34 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280156E+10 | 13990.73 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.584248E+10 | 13931.60 | 19-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.706793E+10 | 13990.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686753E+10 | 11972.76 | 23-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425393E+10 | 12006.33 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234214E+10 | 11938.18 | 15-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.898052E+09 | 11934.92 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15441935.68 | 11885.86 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5928578.12 | 2249.20 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87476051.67 | 11892.31 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.600703E+09 | 11896.23 | 24-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291196E+10 | 11997.22 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.545829E+10 | 11985.02 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686753E+10 | 12006.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.974047E+10 | 9304.70 | 13-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.598275E+10 | 9303.43 | 09-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290697E+10 | 9307.70 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.817733E+09 | 9294.78 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13394132.60 | 9156.78 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55206712.94 | 9269.70 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.450870E+09 | 9318.26 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.344507E+10 | 9315.76 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715563E+10 | 9277.53 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.974047E+10 | 9318.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.701023E+10 | 12496.66 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438282E+10 | 12536.78 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256794E+10 | 12480.72 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.893457E+09 | 12462.22 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42822593.99 | 12411.00 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11088229.90 | 3173.88 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147857E+09 | 12417.70 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.701365E+09 | 12419.38 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295073E+10 | 12527.29 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.549681E+10 | 12514.53 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.701023E+10 | 12536.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118046E+11 | 34246.11 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.729443E+10 | 34333.13 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.354711E+10 | 34318.87 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105646E+10 | 34327.81 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4967503.05 | 27227.74 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51011105.64 | 33856.46 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.528264E+09 | 34304.28 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460433E+10 | 34396.25 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900405E+10 | 34237.89 | 30-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378952E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118046E+11 | 34396.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107144E+11 | 15369.42 | 18-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.666221E+10 | 15964.31 | 02-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.426878E+10 | 15400.49 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187174E+10 | 15357.88 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137380E+09 | 15208.19 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39988716.72 | 10036.51 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.315028E+09 | 15320.89 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122704E+10 | 15398.26 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493835E+10 | 15412.56 | 20-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.899568E+10 | 15341.19 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107144E+11 | 15964.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.934730E+10 | 12304.70 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605132E+10 | 12803.61 | 02-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.353285E+10 | 12278.36 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149480E+10 | 12277.87 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56576756.43 | 12183.48 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39357019.55 | 6411.43 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267802E+09 | 12193.24 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128158E+10 | 12255.68 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439785E+10 | 12266.85 | 25-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.762380E+10 | 12291.41 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.340932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.934730E+10 | 12803.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140912E+11 | 11689.89 | 18-JAN-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.930869E+10 | 12107.90 | 02-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.530724E+10 | 11723.08 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194183E+10 | 11668.20 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95229920.84 | 11534.48 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20222294.79 | 9094.10 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339664E+09 | 11696.35 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169434E+10 | 11677.40 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.607776E+10 | 11689.81 | 20-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110712E+11 | 11674.18 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140912E+11 | 12107.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.973385E+10 | 13624.59 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641779E+10 | 13565.89 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405417E+10 | 13595.52 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167090E+10 | 13542.14 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177622E+09 | 13505.49 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65798566.54 | 6739.09 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1208752.44 | 1104.77 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.443885E+09 | 13500.98 | 29-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162856E+10 | 13510.33 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466379E+10 | 13582.13 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.790076E+10 | 13609.77 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.973385E+10 | 13624.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256171E+11 | 40851.65 | 30-JAN-07:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165052E+11 | 47370.68 | 02-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811166E+10 | 21946.82 | 06-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225615E+10 | 15192.60 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23991990.92 | 3203.00 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76967771.21 | 5257.71 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.684976E+09 | 8517.51 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.766354E+10 | 27918.21 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176245E+11 | 32787.98 | 11-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.785641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256171E+11 | 47370.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294075E+11 | 44526.76 | 31-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197378E+11 | 51004.73 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110271E+11 | 24292.77 | 06-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.385260E+10 | 18226.79 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92170233.38 | 5788.57 | 02-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218987E+09 | 7936.50 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174267E+10 | 11994.02 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101622E+11 | 31208.28 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213450E+11 | 35454.02 | 09-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.975861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294075E+11 | 51004.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334627E+11 | 45717.02 | 31-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218401E+11 | 51362.26 | 02-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115583E+11 | 24750.90 | 08-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412308E+10 | 19081.40 | 03-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138094E+09 | 7932.78 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5935561.84 | 1865.52 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.344885E+09 | 10655.21 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216485E+10 | 14717.01 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115203E+11 | 33930.64 | 25-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240533E+11 | 38690.96 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.334627E+11 | 51362.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172551E+09 | 0.154755E+09 | 8617.59 | 25-MAR-15:00 | 8093.24 | 0.00 |
April | 0.00 | 0.00 | 0.540289E+10 | 0.420923E+10 | 73923.97 | 18-APR-12:00 | 49724.46 | 0.00 |
May | 0.00 | 0.00 | 0.147970E+11 | 0.111223E+11 | 75548.21 | 31-MAY-11:30 | 56079.07 | 0.00 |
June | 0.00 | 0.00 | 0.470073E+11 | 0.346109E+11 | 124464.88 | 26-JUN-07:50 | 54317.36 | 0.00 |
July | 0.00 | 0.00 | 0.671018E+11 | 0.450147E+11 | 114016.35 | 05-JUL-10:50 | 60664.62 | 0.00 |
August | 0.00 | 0.00 | 0.659289E+11 | 0.450921E+11 | 132604.17 | 04-AUG-04:02 | 42171.54 | 0.00 |
September | 0.00 | 0.00 | 0.259682E+11 | 0.229200E+11 | 98466.06 | 11-SEP-09:50 | 59093.03 | 0.00 |
October | 0.00 | 0.00 | 0.160999E+10 | 0.139569E+10 | 33745.91 | 20-OCT-15:00 | 33745.91 | 0.00 |
November | 0.00 | 0.00 | 55810706.39 | 50658358.10 | 4636.17 | 03-NOV-14:00 | 4339.38 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228044E+12 | 0.164570E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671018E+11 | 0.450921E+11 | 132604.17 | 60664.62 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.165689E+09 | 0.149956E+09 | 8646.16 | 25-MAR-15:00 | 8449.23 | 0.00 |
April | 0.00 | 0.00 | 0.582247E+10 | 0.464089E+10 | 67590.59 | 18-APR-12:40 | 49964.12 | 0.00 |
May | 0.00 | 0.00 | 0.151865E+11 | 0.114128E+11 | 68838.85 | 30-MAY-11:00 | 43615.27 | 0.00 |
June | 0.00 | 0.00 | 0.448051E+11 | 0.334635E+11 | 120518.84 | 26-JUN-06:03 | 48195.03 | 0.00 |
July | 0.00 | 0.00 | 0.615918E+11 | 0.416618E+11 | 108491.96 | 05-JUL-10:50 | 57515.09 | 0.00 |
August | 0.00 | 0.00 | 0.577554E+11 | 0.399528E+11 | 125250.18 | 03-AUG-05:02 | 41818.84 | 0.00 |
September | 0.00 | 0.00 | 0.227702E+11 | 0.202311E+11 | 84101.45 | 11-SEP-09:40 | 50358.08 | 0.00 |
October | 0.00 | 0.00 | 0.144042E+10 | 0.124211E+10 | 29624.89 | 20-OCT-15:00 | 29624.89 | 0.00 |
November | 0.00 | 0.00 | 61027624.47 | 53950745.08 | 5551.52 | 03-NOV-13:30 | 4778.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209599E+12 | 0.152809E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.615918E+11 | 0.416618E+11 | 125250.18 | 57515.09 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175355E+09 | 0.155234E+09 | 9212.27 | 25-MAR-15:00 | 8745.05 | 0.00 |
April | 0.00 | 0.00 | 0.646552E+10 | 0.511782E+10 | 83265.33 | 18-APR-15:50 | 57547.15 | 0.00 |
May | 0.00 | 0.00 | 0.164910E+11 | 0.123323E+11 | 78357.08 | 30-MAY-12:10 | 56494.55 | 0.00 |
June | 0.00 | 0.00 | 0.481749E+11 | 0.361715E+11 | 114988.56 | 26-JUN-07:50 | 50293.48 | 0.00 |
July | 0.00 | 0.00 | 0.658462E+11 | 0.442391E+11 | 117613.31 | 06-JUL-15:10 | 60582.93 | 0.00 |
August | 0.00 | 0.00 | 0.602059E+11 | 0.418525E+11 | 139138.21 | 04-AUG-05:02 | 44010.18 | 0.00 |
September | 0.00 | 0.00 | 0.237934E+11 | 0.210017E+11 | 84278.81 | 11-SEP-10:00 | 52184.27 | 0.00 |
October | 0.00 | 0.00 | 0.146459E+10 | 0.124008E+10 | 29625.07 | 20-OCT-15:00 | 29625.07 | 0.00 |
November | 0.00 | 0.00 | 44858185.78 | 38721872.24 | 4123.79 | 03-NOV-14:00 | 3634.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222662E+12 | 0.162149E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.658462E+11 | 0.442391E+11 | 139138.21 | 60582.93 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2082.27 | 7368.84 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 2133.75 | 7415.74 | 22-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2253.17 | 7402.10 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2027.49 | 7201.59 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1986.65 | 6820.81 | 03-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1909.61 | 6404.23 | 01-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1660.07 | 5969.31 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1780.67 | 5737.27 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1684.87 | 5892.60 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1761.51 | 6255.87 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1901.10 | 6715.18 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1937.68 | 7093.89 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1925.37 | ||||
Minimum of Months | 0.00 | 0.00 | 1660.07 | 5737.27 | ||
Maximum of Months | 0.00 | 0.00 | 2253.17 | 7415.74 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.255566E+10 | 0.43 | 2886.66 | 02-JAN-05:01 | 0.83 |
February | 0.193518E+10 | 0.36 | 2886.66 | 01-FEB-07:01 | 0.84 |
March | 0.207534E+10 | 0.35 | 2886.66 | 06-MAR-07:01 | 0.83 |
April | 0.224228E+10 | 0.34 | 6397.17 | 18-APR-15:10 | 1.30 |
May | 0.306788E+10 | 0.39 | 7618.10 | 31-MAY-15:10 | 1.45 |
June | 0.492051E+10 | 0.52 | 11486.14 | 26-JUN-12:07 | 1.88 |
July | 0.565057E+10 | 0.54 | 10848.68 | 05-JUL-12:10 | 1.82 |
August | 0.597326E+10 | 0.56 | 12153.32 | 03-AUG-07:20 | 1.95 |
September | 0.409021E+10 | 0.46 | 9826.13 | 11-SEP-15:30 | 1.71 |
October | 0.225870E+10 | 0.33 | 3962.96 | 20-OCT-15:10 | 0.99 |
November | 0.205753E+10 | 0.34 | 3054.63 | 02-NOV-07:04 | 0.85 |
December | 0.211949E+10 | 0.36 | 2886.66 | 11-DEC-06:01 | 0.84 |
Annual Sum or Average | 0.389466E+11 | 0.42 | |||
Minimum of Months | 0.193518E+10 | 0.33 | 2886.66 | 0.83 | |
Maximum of Months | 0.597326E+10 | 0.56 | 12153.32 | 1.95 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.260193E+10 | 0.46 | 2869.82 | 09-JAN-06:01 | 0.88 |
February | 0.195542E+10 | 0.38 | 2869.82 | 01-FEB-07:02 | 0.88 |
March | 0.202593E+10 | 0.36 | 2869.82 | 09-MAR-07:01 | 0.88 |
April | 0.218901E+10 | 0.36 | 8099.69 | 18-APR-14:50 | 1.61 |
May | 0.288765E+10 | 0.40 | 8407.32 | 30-MAY-15:30 | 1.65 |
June | 0.486154E+10 | 0.54 | 10027.26 | 30-JUN-15:20 | 1.85 |
July | 0.522654E+10 | 0.55 | 10592.11 | 03-JUL-15:10 | 1.91 |
August | 0.522753E+10 | 0.55 | 10950.37 | 04-AUG-07:07 | 1.94 |
September | 0.339099E+10 | 0.44 | 10024.44 | 08-SEP-16:00 | 1.85 |
October | 0.186900E+10 | 0.32 | 3175.82 | 20-OCT-15:10 | 0.92 |
November | 0.190152E+10 | 0.35 | 2869.82 | 20-NOV-06:01 | 0.87 |
December | 0.218586E+10 | 0.39 | 2869.82 | 04-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.363229E+11 | 0.42 | |||
Minimum of Months | 0.186900E+10 | 0.32 | 2869.82 | 0.87 | |
Maximum of Months | 0.522753E+10 | 0.55 | 10950.37 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.305885E+10 | 0.49 | 2916.94 | 02-JAN-05:01 | 0.82 |
February | 0.246138E+10 | 0.44 | 2916.94 | 01-FEB-05:01 | 0.82 |
March | 0.226239E+10 | 0.37 | 2916.94 | 01-MAR-06:01 | 0.82 |
April | 0.227530E+10 | 0.35 | 7916.05 | 18-APR-15:00 | 1.46 |
May | 0.279229E+10 | 0.38 | 8681.33 | 31-MAY-15:00 | 1.54 |
June | 0.460150E+10 | 0.49 | 11677.17 | 26-JUN-15:30 | 1.86 |
July | 0.483062E+10 | 0.48 | 10381.53 | 03-JUL-15:20 | 1.73 |
August | 0.472295E+10 | 0.48 | 11843.53 | 04-AUG-15:20 | 1.88 |
September | 0.307455E+10 | 0.39 | 10201.29 | 07-SEP-16:00 | 1.71 |
October | 0.191829E+10 | 0.31 | 2916.94 | 16-OCT-05:01 | 0.82 |
November | 0.229743E+10 | 0.39 | 2916.94 | 10-NOV-07:01 | 0.82 |
December | 0.274091E+10 | 0.45 | 2916.94 | 01-DEC-06:01 | 0.82 |
Annual Sum or Average | 0.370365E+11 | 0.42 | |||
Minimum of Months | 0.191829E+10 | 0.31 | 2916.94 | 0.82 | |
Maximum of Months | 0.483062E+10 | 0.49 | 11843.53 | 1.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 56.63 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.84 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.36 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 56.14 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.74 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:02 | 0.22 | 0.22 | 56.12 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.63 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.44 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.98 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.60 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 56.31 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.74 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.36 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 56.63 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.13 | 56.13 | 2082.27 | 7368.84 | 31-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.28 | 56.28 | 2133.75 | 7415.74 | 22-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 55.89 | 55.89 | 2253.17 | 7402.10 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.62 | 56.62 | 2027.49 | 7201.59 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.50 | 57.50 | 1986.65 | 6820.81 | 03-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.55 | 56.55 | 1909.61 | 6404.23 | 01-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.05 | 57.05 | 1660.07 | 5969.31 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.47 | 57.47 | 1780.67 | 5737.27 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.38 | 56.38 | 1684.87 | 5892.60 | 28-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.09 | 56.09 | 1761.51 | 6255.87 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.27 | 57.27 | 1901.10 | 6715.18 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.18 | 56.18 | 1937.68 | 7093.89 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1925.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.89 | 55.89 | 1660.07 | 5737.27 | ||
Maximum of Months | 0.00 | 0.00 | 57.50 | 57.50 | 2253.17 | 7415.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.413087E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.275939E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198489E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119489E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.844564E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.171505E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.218543E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.221368E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.117761E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.598087E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.161703E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.299179E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.234133E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.598087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.413087E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.390012E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234599E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132951E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.736122E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.683290E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159543E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.200485E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.192558E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.952329E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.437857E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156317E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.296486E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.204391E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.437857E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.390012E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.587502E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.381958E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.230225E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.119543E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.745027E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167077E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.207036E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.194099E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.105624E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.867387E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.269925E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.473363E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.289759E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.745027E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.587502E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.255566E+10 | 0.00 | 0.643702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193518E+10 | 0.00 | 0.421639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207534E+10 | 0.172551E+09 | 0.258361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224228E+10 | 0.540289E+10 | 0.105748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306788E+10 | 0.147970E+11 | 0.164623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.492051E+10 | 0.470073E+11 | 0.589564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565057E+10 | 0.671018E+11 | 65327183.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.597326E+10 | 0.659289E+11 | 0.202934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409021E+10 | 0.259682E+11 | 0.119969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225870E+10 | 0.160999E+10 | 0.397795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205753E+10 | 55810706.39 | 0.217602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211949E+10 | 0.00 | 0.454229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389466E+11 | 0.228044E+12 | 0.217810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.193518E+10 | 0.00 | 65327183.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.597326E+10 | 0.671018E+11 | 0.643702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.260193E+10 | 0.00 | 0.658067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195542E+10 | 0.00 | 0.412423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202593E+10 | 0.165689E+09 | 0.222492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218901E+10 | 0.582247E+10 | 0.754196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288765E+10 | 0.151865E+11 | 0.188959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.486154E+10 | 0.448051E+11 | 17146862.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.522654E+10 | 0.615918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.522753E+10 | 0.577554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339099E+10 | 0.227702E+11 | 0.573962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186900E+10 | 0.144042E+10 | 0.386622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190152E+10 | 61027624.47 | 0.238749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218586E+10 | 0.00 | 0.488078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363229E+11 | 0.209599E+12 | 0.214169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.522753E+10 | 0.615918E+11 | 0.658067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.305885E+10 | 0.00 | 0.891540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246138E+10 | 0.00 | 0.575745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226239E+10 | 0.175355E+09 | 0.322684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227530E+10 | 0.646552E+10 | 0.121588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279229E+10 | 0.164910E+11 | 0.609870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.460150E+10 | 0.481749E+11 | 0.171302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.483062E+10 | 0.658462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.472295E+10 | 0.602059E+11 | 1208752.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.307455E+10 | 0.237934E+11 | 0.176228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191829E+10 | 0.146459E+10 | 0.852462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229743E+10 | 44858185.78 | 0.362024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274091E+10 | 0.00 | 0.686487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370365E+11 | 0.222662E+12 | 0.307076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483062E+10 | 0.658462E+11 | 0.891540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.255566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207534E+10 | 0.00 | 0.00 | 0.00 | 49110352.39 | 0.177244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.224228E+10 | 0.00 | 0.00 | 0.00 | 0.138796E+10 | 0.831865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306788E+10 | 0.00 | 0.00 | 0.00 | 0.375552E+10 | 0.162223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.492051E+10 | 0.00 | 0.00 | 0.00 | 0.116404E+11 | 0.589564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.565057E+10 | 0.00 | 0.00 | 0.00 | 0.161384E+11 | 65327183.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.597326E+10 | 0.00 | 0.00 | 0.00 | 0.159606E+11 | 0.202934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409021E+10 | 0.00 | 0.00 | 0.00 | 0.656315E+10 | 0.112272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225870E+10 | 0.00 | 0.00 | 0.00 | 0.429186E+09 | 0.329298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205753E+10 | 0.00 | 0.00 | 0.00 | 16100286.76 | 0.140966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389466E+11 | 0.00 | 0.00 | 0.00 | 0.559404E+11 | 0.139246E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.193518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65327183.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.597326E+10 | 0.00 | 0.00 | 0.00 | 0.161384E+11 | 0.387530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.260193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215045E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202593E+10 | 0.00 | 0.00 | 0.00 | 47109994.00 | 0.112221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218901E+10 | 0.00 | 0.00 | 0.00 | 0.148286E+10 | 0.368936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288765E+10 | 0.00 | 0.00 | 0.00 | 0.384846E+10 | 96788844.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.486154E+10 | 0.00 | 0.00 | 0.00 | 0.110757E+11 | 17146862.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.522654E+10 | 0.00 | 0.00 | 0.00 | 0.148219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.522753E+10 | 0.00 | 0.00 | 0.00 | 0.140283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.339099E+10 | 0.00 | 0.00 | 0.00 | 0.577732E+10 | 0.354976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186900E+10 | 0.00 | 0.00 | 0.00 | 0.386023E+09 | 0.212355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190152E+10 | 0.00 | 0.00 | 0.00 | 17505976.87 | 0.137127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363229E+11 | 0.00 | 0.00 | 0.00 | 0.514852E+11 | 0.116583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.522753E+10 | 0.00 | 0.00 | 0.00 | 0.148219E+11 | 0.363992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.305885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226239E+10 | 0.00 | 0.00 | 0.00 | 49930744.58 | 0.207102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.227530E+10 | 0.00 | 0.00 | 0.00 | 0.164331E+10 | 0.803572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.279229E+10 | 0.00 | 0.00 | 0.00 | 0.418620E+10 | 0.471776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.460150E+10 | 0.00 | 0.00 | 0.00 | 0.119408E+11 | 0.165367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.483062E+10 | 0.00 | 0.00 | 0.00 | 0.158729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.472295E+10 | 0.00 | 0.00 | 0.00 | 0.146857E+11 | 1208752.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.307455E+10 | 0.00 | 0.00 | 0.00 | 0.607046E+10 | 0.141739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191829E+10 | 0.00 | 0.00 | 0.00 | 0.395807E+09 | 0.635977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229743E+10 | 0.00 | 0.00 | 0.00 | 12985776.09 | 0.246821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370365E+11 | 0.00 | 0.00 | 0.00 | 0.548582E+11 | 0.197865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.191829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.483062E+10 | 0.00 | 0.00 | 0.00 | 0.158729E+11 | 0.556913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199254E+11 | 0.00 | 0.00 | 445751.98 | 0.00 | 0.853144E+09 | 0.457302E+09 | 0.00 | 0.27 |
February | 0.146627E+11 | 0.00 | 0.00 | 1723337.32 | 0.00 | 98196792.33 | 0.221158E+10 | 0.00 | 0.27 |
March | 0.964001E+10 | 0.00 | 0.00 | 12780428.85 | 0.00 | 4597488.47 | 0.770185E+10 | 0.00 | 0.36 |
April | 0.490880E+10 | 0.239853E+09 | 0.00 | 21936503.97 | 16581556.31 | 0.00 | 0.105741E+11 | 0.00 | 0.49 |
May | 0.135409E+10 | 0.308638E+09 | 0.00 | 34480116.69 | 16706413.86 | 0.00 | 0.155927E+11 | 0.00 | 0.92 |
June | 0.697642E+09 | 0.318273E+10 | 0.00 | 29080244.59 | 0.173233E+09 | 0.00 | 0.102231E+11 | 0.00 | 1.03 |
July | 0.617258E+09 | 0.563552E+10 | 0.00 | 20013111.62 | 0.525580E+09 | 0.00 | 0.421622E+10 | 0.00 | 1.02 |
August | 0.798748E+09 | 0.573708E+10 | 0.00 | 28133816.17 | 0.256853E+09 | 0.00 | 0.655846E+10 | 0.00 | 1.10 |
September | 0.146419E+10 | 0.547881E+09 | 0.00 | 36467552.57 | 51702758.76 | 0.00 | 0.149935E+11 | 0.00 | 0.92 |
October | 0.253977E+10 | 0.00 | 0.00 | 28863393.92 | 752919.20 | 0.00 | 0.153971E+11 | 0.00 | 0.55 |
November | 0.766831E+10 | 0.00 | 0.00 | 15014071.60 | 0.00 | 49776348.04 | 0.955717E+10 | 0.00 | 0.41 |
December | 0.150173E+11 | 0.00 | 0.00 | 2417319.20 | 0.00 | 0.137018E+09 | 0.323993E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.792943E+11 | 0.156517E+11 | 0.00 | 0.231356E+09 | 0.104141E+10 | 0.114273E+10 | 0.100723E+12 | 0.00 | 0.64 |
Minimum of Months | 0.617258E+09 | 0.00 | 0.00 | 445751.98 | 0.00 | 0.00 | 0.457302E+09 | 0.00 | 0.27 |
Maximum of Months | 0.199254E+11 | 0.573708E+10 | 0.00 | 36467552.57 | 0.525580E+09 | 0.853144E+09 | 0.155927E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641978E+10 | 0.00 | 0.00 | 0.25 |
February | 0.128803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255454E+10 | 0.00 | 0.00 | 0.25 |
March | 0.129124E+11 | 0.00 | 0.00 | 490358.10 | 0.00 | 0.508660E+09 | 0.825676E+09 | 0.00 | 0.29 |
April | 0.756589E+10 | 98703756.18 | 0.00 | 5604023.36 | 0.103139E+09 | 78242199.15 | 0.376780E+10 | 0.00 | 0.36 |
May | 0.340765E+10 | 0.209248E+09 | 0.00 | 15300594.28 | 89153602.68 | 0.00 | 0.798896E+10 | 0.00 | 0.63 |
June | 0.121783E+10 | 0.241804E+10 | 0.00 | 17665588.38 | 0.145020E+09 | 0.00 | 0.596955E+10 | 0.00 | 0.71 |
July | 0.604248E+09 | 0.428871E+10 | 0.00 | 13051437.00 | 0.429433E+09 | 0.00 | 0.263893E+10 | 0.00 | 0.73 |
August | 0.778988E+09 | 0.415827E+10 | 0.00 | 18058030.53 | 0.217446E+09 | 0.00 | 0.387311E+10 | 0.00 | 0.75 |
September | 0.273939E+10 | 0.403977E+09 | 0.00 | 17157674.75 | 36386689.69 | 0.00 | 0.708209E+10 | 0.00 | 0.58 |
October | 0.745547E+10 | 0.00 | 0.00 | 3608706.03 | 1692770.90 | 500038.51 | 0.339135E+10 | 0.00 | 0.34 |
November | 0.100825E+11 | 0.00 | 0.00 | 1349659.51 | 0.00 | 0.132208E+10 | 0.151889E+10 | 0.00 | 0.29 |
December | 0.133142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318708E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.862406E+11 | 0.115769E+11 | 0.00 | 92286071.94 | 0.102227E+10 | 0.140709E+11 | 0.370563E+11 | 0.00 | 0.45 |
Minimum of Months | 0.604248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.133142E+11 | 0.428871E+10 | 0.00 | 18058030.53 | 0.429433E+09 | 0.641978E+10 | 0.798896E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.697753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106462E+11 | 0.00 | 0.00 | 0.23 |
February | 0.774159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623632E+10 | 0.00 | 0.00 | 0.23 |
March | 0.109893E+11 | 0.00 | 0.00 | 164646.17 | 0.00 | 0.202422E+10 | 0.231530E+09 | 0.00 | 0.28 |
April | 0.790671E+10 | 0.116605E+09 | 0.00 | 3590986.98 | 0.116825E+09 | 0.460686E+09 | 0.244085E+10 | 0.00 | 0.36 |
May | 0.419854E+10 | 0.191560E+09 | 0.00 | 12890632.33 | 62987746.83 | 412586.74 | 0.662439E+10 | 0.00 | 0.62 |
June | 0.173137E+10 | 0.238613E+10 | 0.00 | 14532322.82 | 0.199425E+09 | 0.00 | 0.504764E+10 | 0.00 | 0.72 |
July | 0.781268E+09 | 0.458372E+10 | 0.00 | 10004590.11 | 0.507658E+09 | 0.00 | 0.219979E+10 | 0.00 | 0.77 |
August | 0.103721E+10 | 0.381240E+10 | 0.00 | 14567658.39 | 0.453620E+09 | 0.00 | 0.306001E+10 | 0.00 | 0.75 |
September | 0.404072E+10 | 0.349468E+09 | 0.00 | 10561174.68 | 69511394.99 | 15346757.02 | 0.435861E+10 | 0.00 | 0.55 |
October | 0.879766E+10 | 0.00 | 0.00 | 768739.17 | 984192.56 | 0.202739E+09 | 0.108477E+10 | 0.00 | 0.33 |
November | 0.825560E+10 | 0.00 | 0.00 | 153521.14 | 0.00 | 0.327366E+10 | 0.233507E+09 | 0.00 | 0.28 |
December | 0.772658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706427E+10 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.701841E+11 | 0.114399E+11 | 0.00 | 67234271.78 | 0.141101E+10 | 0.299239E+11 | 0.252811E+11 | 0.00 | 0.45 |
Minimum of Months | 0.781268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.109893E+11 | 0.458372E+10 | 0.00 | 14567658.39 | 0.507658E+09 | 0.106462E+11 | 0.662439E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620137E+10 | 0.00 | 0.00 | 0.38 |
February | 0.215091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469075E+10 | 0.00 | 0.00 | 0.37 |
March | 0.126841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284901E+10 | 0.00 | 0.00 | 0.41 |
April | 0.186751E+10 | 43617963.48 | 0.00 | 383130.14 | 26228349.29 | 0.107896E+10 | 0.239036E+09 | 0.00 | 0.49 |
May | 0.198175E+10 | 58479141.71 | 0.00 | 2000634.06 | 18419221.33 | 39095246.29 | 0.102883E+10 | 0.00 | 0.84 |
June | 0.782606E+09 | 0.759185E+09 | 0.00 | 3280031.78 | 66686170.48 | 4000652.51 | 0.107502E+10 | 0.00 | 0.99 |
July | 0.318931E+09 | 0.137283E+10 | 0.00 | 2243906.85 | 0.164980E+09 | 0.00 | 0.495691E+09 | 0.00 | 1.05 |
August | 0.497363E+09 | 0.113261E+10 | 0.00 | 2966491.75 | 0.141371E+09 | 0.00 | 0.600623E+09 | 0.00 | 0.99 |
September | 0.164240E+10 | 0.102474E+09 | 0.00 | 1448275.36 | 19211117.64 | 0.153178E+09 | 0.551748E+09 | 0.00 | 0.71 |
October | 0.218899E+10 | 0.00 | 0.00 | 2740.65 | 301443.70 | 0.896699E+09 | 5348663.18 | 0.00 | 0.48 |
November | 0.102227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272058E+10 | 0.00 | 0.00 | 0.42 |
December | 52652766.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490182E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.119546E+11 | 0.346920E+10 | 0.00 | 12325210.60 | 0.437197E+09 | 0.235355E+11 | 0.399630E+10 | 0.00 | 0.62 |
Minimum of Months | 52652766.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.218899E+10 | 0.137283E+10 | 0.00 | 3280031.78 | 0.164980E+09 | 0.620137E+10 | 0.107502E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231057E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552367E+10 | 0.00 | 0.00 | 0.55 |
February | 0.545202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401643E+10 | 0.00 | 0.00 | 0.57 |
March | 0.202349E+10 | 0.00 | 0.00 | 30621.97 | 0.00 | 0.221952E+10 | 47068761.11 | 0.00 | 0.68 |
April | 0.196839E+10 | 64964262.22 | 0.00 | 775491.37 | 16798634.64 | 0.922011E+09 | 0.556804E+09 | 0.00 | 0.86 |
May | 0.189720E+10 | 67424802.40 | 0.00 | 2675282.80 | 15388817.38 | 13627048.68 | 0.144853E+10 | 0.00 | 1.45 |
June | 0.851438E+09 | 0.713638E+09 | 0.00 | 3757388.57 | 64710855.35 | 2934276.95 | 0.129355E+10 | 0.00 | 1.70 |
July | 0.298776E+09 | 0.125123E+10 | 0.00 | 2876388.23 | 0.191955E+09 | 0.00 | 0.662491E+09 | 0.00 | 1.84 |
August | 0.498069E+09 | 0.102813E+10 | 0.00 | 3479132.33 | 0.196087E+09 | 0.00 | 0.762230E+09 | 0.00 | 1.67 |
September | 0.159237E+10 | 0.108818E+09 | 0.00 | 2204563.49 | 17329416.86 | 0.105433E+09 | 0.810490E+09 | 0.00 | 1.26 |
October | 0.255330E+10 | 0.00 | 0.00 | 69063.73 | 318764.84 | 0.666201E+09 | 45486572.00 | 0.00 | 0.79 |
November | 0.116210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264816E+10 | 0.00 | 0.00 | 0.68 |
December | 0.210823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460345E+10 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.138322E+11 | 0.323421E+10 | 0.00 | 15867932.48 | 0.502588E+09 | 0.207214E+11 | 0.562665E+10 | 0.00 | 1.05 |
Minimum of Months | 0.210823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.255330E+10 | 0.125123E+10 | 0.00 | 3757388.57 | 0.196087E+09 | 0.552367E+10 | 0.144853E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184771E+10 | 0.00 | 0.00 | 346775.17 | 0.00 | 0.521762E+10 | 0.247732E+09 | 0.00 | 0.44 |
February | 0.188083E+10 | 0.00 | 0.00 | 750294.75 | 0.00 | 0.357679E+10 | 0.426419E+09 | 0.00 | 0.47 |
March | 0.224196E+10 | 0.00 | 0.00 | 1604453.98 | 0.00 | 0.240643E+10 | 0.987428E+09 | 0.00 | 0.58 |
April | 0.207920E+10 | 0.115283E+09 | 0.00 | 2780928.34 | 20268990.63 | 0.107510E+10 | 0.157932E+10 | 0.00 | 0.77 |
May | 0.237963E+10 | 83619911.85 | 0.00 | 3767347.07 | 20829569.64 | 49870775.21 | 0.184035E+10 | 0.00 | 1.18 |
June | 0.115340E+10 | 0.880016E+09 | 0.00 | 3792743.77 | 0.109952E+09 | 5231384.24 | 0.131372E+10 | 0.00 | 1.27 |
July | 0.463085E+09 | 0.165329E+10 | 0.00 | 2792891.51 | 0.237937E+09 | 0.00 | 0.621731E+09 | 0.00 | 1.37 |
August | 0.656695E+09 | 0.146181E+10 | 0.00 | 4926350.55 | 0.205218E+09 | 0.00 | 0.102226E+10 | 0.00 | 1.43 |
September | 0.176691E+10 | 0.212000E+09 | 0.00 | 5323930.57 | 13565282.24 | 0.126799E+09 | 0.169527E+10 | 0.00 | 1.19 |
October | 0.237976E+10 | 0.00 | 0.00 | 3686682.63 | 397455.79 | 0.567063E+09 | 0.183441E+10 | 0.00 | 0.78 |
November | 0.199376E+10 | 0.00 | 0.00 | 740939.29 | 0.00 | 0.252911E+10 | 0.467438E+09 | 0.00 | 0.58 |
December | 0.107482E+10 | 0.00 | 0.00 | 867940.08 | 0.00 | 0.458550E+10 | 0.514355E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.199178E+11 | 0.440602E+10 | 0.00 | 31381277.71 | 0.608169E+09 | 0.201395E+11 | 0.125504E+11 | 0.00 | 0.88 |
Minimum of Months | 0.463085E+09 | 0.00 | 0.00 | 346775.17 | 0.00 | 0.00 | 0.247732E+09 | 0.00 | 0.44 |
Maximum of Months | 0.237976E+10 | 0.165329E+10 | 0.00 | 5323930.57 | 0.237937E+09 | 0.521762E+10 | 0.184035E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.433439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591511E+10 | 0.00 | 0.00 | 0.61 |
February | 0.729765E+09 | 0.00 | 0.00 | 22056.62 | 0.00 | 0.428458E+10 | 31283362.86 | 0.00 | 0.63 |
March | 0.179367E+10 | 0.00 | 0.00 | 131875.51 | 0.00 | 0.274421E+10 | 0.209629E+09 | 0.00 | 0.75 |
April | 0.202618E+10 | 45077802.74 | 0.00 | 1439859.87 | 33797534.37 | 0.101657E+10 | 0.850027E+09 | 0.00 | 0.97 |
May | 0.256377E+10 | 57503821.56 | 0.00 | 2287282.52 | 24440124.23 | 51894153.12 | 0.104438E+10 | 0.00 | 1.55 |
June | 0.110821E+10 | 0.627353E+09 | 0.00 | 2950508.73 | 0.113438E+09 | 7788896.01 | 0.101045E+10 | 0.00 | 1.69 |
July | 0.449894E+09 | 0.131520E+10 | 0.00 | 2501698.26 | 0.221816E+09 | 0.00 | 0.470433E+09 | 0.00 | 1.77 |
August | 0.621999E+09 | 0.967105E+09 | 0.00 | 3282095.65 | 0.280619E+09 | 0.00 | 0.684152E+09 | 0.00 | 1.76 |
September | 0.198424E+10 | 0.112130E+09 | 0.00 | 1901250.69 | 21182804.12 | 0.189182E+09 | 0.617675E+09 | 0.00 | 1.35 |
October | 0.243480E+10 | 0.00 | 0.00 | 483690.65 | 352953.62 | 0.842993E+09 | 0.366831E+09 | 0.00 | 0.89 |
November | 0.135945E+10 | 0.00 | 0.00 | 59034.38 | 0.00 | 0.280125E+10 | 57571531.18 | 0.00 | 0.75 |
December | 0.487650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482516E+10 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.159931E+11 | 0.312437E+10 | 0.00 | 15059352.89 | 0.695647E+09 | 0.226787E+11 | 0.534243E+10 | 0.00 | 1.11 |
Minimum of Months | 0.433439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.256377E+10 | 0.131520E+10 | 0.00 | 3282095.65 | 0.280619E+09 | 0.591511E+10 | 0.104438E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525882E+10 | 0.00 | 0.00 | 0.31 |
February | 0.115158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388714E+10 | 0.00 | 0.00 | 0.29 |
March | 0.860095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238245E+10 | 0.00 | 0.00 | 0.31 |
April | 0.138381E+10 | 15715530.23 | 0.00 | 36197.27 | 23057844.02 | 0.997991E+09 | 38497405.22 | 0.00 | 0.35 |
May | 0.180974E+10 | 40252549.10 | 0.00 | 462250.29 | 5502216.66 | 34161247.86 | 0.320169E+09 | 0.00 | 0.54 |
June | 0.696450E+09 | 0.552408E+09 | 0.00 | 2353462.86 | 43972259.03 | 0.00 | 0.729472E+09 | 0.00 | 0.70 |
July | 0.285539E+09 | 0.986353E+09 | 0.00 | 1966265.35 | 0.107877E+09 | 0.00 | 0.407611E+09 | 0.00 | 0.76 |
August | 0.403198E+09 | 0.100522E+10 | 0.00 | 2769148.03 | 73434873.17 | 0.00 | 0.622019E+09 | 0.00 | 0.80 |
September | 0.134579E+10 | 0.103914E+09 | 0.00 | 2016157.85 | 10174293.63 | 11550120.85 | 0.779374E+09 | 0.00 | 0.59 |
October | 0.239634E+10 | 0.00 | 0.00 | 16416.46 | 147164.96 | 0.122275E+09 | 65650492.55 | 0.00 | 0.37 |
November | 0.128543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176982E+10 | 0.00 | 0.00 | 0.32 |
December | 62070141.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392262E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.107448E+11 | 0.270386E+10 | 0.00 | 9619898.11 | 0.264166E+09 | 0.183868E+11 | 0.296279E+10 | 0.00 | 0.47 |
Minimum of Months | 62070141.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.239634E+10 | 0.100522E+10 | 0.00 | 2769148.03 | 0.107877E+09 | 0.525882E+10 | 0.779374E+09 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.230805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471313E+10 | 0.00 | 0.00 | 0.46 |
February | 0.476160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346092E+10 | 0.00 | 0.00 | 0.47 |
March | 0.166120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204252E+10 | 0.00 | 0.00 | 0.56 |
April | 0.176208E+10 | 31632259.34 | 0.00 | 323230.37 | 20464180.84 | 0.857920E+09 | 0.234479E+09 | 0.00 | 0.66 |
May | 0.180548E+10 | 51836660.39 | 0.00 | 1368493.97 | 5971014.87 | 1607751.32 | 0.818749E+09 | 0.00 | 1.06 |
June | 0.829025E+09 | 0.573280E+09 | 0.00 | 2987028.05 | 44560075.39 | 398305.14 | 0.972424E+09 | 0.00 | 1.32 |
July | 0.312246E+09 | 0.984694E+09 | 0.00 | 2604433.49 | 0.121823E+09 | 0.00 | 0.568423E+09 | 0.00 | 1.43 |
August | 0.426196E+09 | 0.955712E+09 | 0.00 | 3479453.07 | 95018819.59 | 0.00 | 0.845548E+09 | 0.00 | 1.41 |
September | 0.141198E+10 | 0.109164E+09 | 0.00 | 2866926.76 | 11219136.45 | 6844641.02 | 0.108833E+10 | 0.00 | 1.11 |
October | 0.289120E+10 | 0.00 | 0.00 | 94698.59 | 172136.77 | 69812612.81 | 62321732.14 | 0.00 | 0.68 |
November | 0.155368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189239E+10 | 0.00 | 0.00 | 0.57 |
December | 0.383864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384203E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.137439E+11 | 0.270632E+10 | 0.00 | 13724264.29 | 0.299228E+09 | 0.168876E+11 | 0.459027E+10 | 0.00 | 0.85 |
Minimum of Months | 0.230805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.289120E+10 | 0.984694E+09 | 0.00 | 3479453.07 | 0.121823E+09 | 0.471313E+10 | 0.108833E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802225E+10 | 0.00 | 0.00 | 0.48 |
February | 0.352447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576974E+10 | 0.00 | 0.00 | 0.44 |
March | 0.892457E+09 | 0.00 | 0.00 | 68903.11 | 0.00 | 0.428235E+10 | 83040119.56 | 0.00 | 0.49 |
April | 0.116661E+10 | 84223327.45 | 0.00 | 332597.01 | 8882167.92 | 0.249245E+10 | 0.194839E+09 | 0.00 | 0.56 |
May | 0.237520E+10 | 70931994.36 | 0.00 | 541287.39 | 8636502.05 | 0.644134E+09 | 0.196654E+09 | 0.00 | 0.81 |
June | 0.125312E+10 | 0.716534E+09 | 0.00 | 1488899.52 | 91719525.45 | 0.245468E+09 | 0.411638E+09 | 0.00 | 0.90 |
July | 0.560696E+09 | 0.128697E+10 | 0.00 | 1654408.49 | 0.181847E+09 | 33076780.09 | 0.297412E+09 | 0.00 | 0.98 |
August | 0.591172E+09 | 0.142901E+10 | 0.00 | 3695456.72 | 0.122674E+09 | 0.109924E+09 | 0.759046E+09 | 0.00 | 1.13 |
September | 0.172031E+10 | 0.235475E+09 | 0.00 | 3731421.52 | 12601457.56 | 0.446607E+09 | 0.104301E+10 | 0.00 | 0.99 |
October | 0.235603E+10 | 61833.11 | 0.00 | 1126095.56 | 166865.02 | 0.107812E+10 | 0.685554E+09 | 0.00 | 0.61 |
November | 0.129432E+10 | 0.00 | 0.00 | 379391.72 | 0.00 | 0.342723E+10 | 0.243046E+09 | 0.00 | 0.52 |
December | 0.469337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608817E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.132877E+11 | 0.382320E+10 | 0.00 | 13018461.03 | 0.426527E+09 | 0.326395E+11 | 0.391424E+10 | 0.00 | 0.70 |
Minimum of Months | 0.256029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33076780.09 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.237520E+10 | 0.142901E+10 | 0.00 | 3731421.52 | 0.181847E+09 | 0.802225E+10 | 0.104301E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503638E+10 | 0.00 | 0.00 | 0.50 |
February | 0.513041E+09 | 0.00 | 0.00 | 1733.63 | 0.00 | 0.371107E+10 | 7148256.36 | 0.00 | 0.50 |
March | 0.157088E+10 | 0.00 | 0.00 | 563.56 | 0.00 | 0.240587E+10 | 4820264.06 | 0.00 | 0.60 |
April | 0.193015E+10 | 27795608.16 | 0.00 | 534612.62 | 21789500.89 | 0.824061E+09 | 0.315761E+09 | 0.00 | 0.71 |
May | 0.233381E+10 | 48144467.22 | 0.00 | 864802.88 | 7568377.01 | 25608327.16 | 0.396957E+09 | 0.00 | 1.09 |
June | 0.102338E+10 | 0.521125E+09 | 0.00 | 2300590.29 | 59701123.62 | 1115940.31 | 0.713384E+09 | 0.00 | 1.28 |
July | 0.425320E+09 | 0.105440E+10 | 0.00 | 1899719.23 | 0.110264E+09 | 0.00 | 0.373806E+09 | 0.00 | 1.33 |
August | 0.540029E+09 | 0.959572E+09 | 0.00 | 3100121.04 | 91043121.04 | 0.00 | 0.684722E+09 | 0.00 | 1.41 |
September | 0.181714E+10 | 0.118749E+09 | 0.00 | 2008004.58 | 11334572.05 | 24987653.97 | 0.737980E+09 | 0.00 | 1.12 |
October | 0.282740E+10 | 0.00 | 0.00 | 448663.41 | 185181.07 | 0.103271E+09 | 0.342317E+09 | 0.00 | 0.74 |
November | 0.171395E+10 | 0.00 | 0.00 | 44706.13 | 0.00 | 0.195252E+10 | 40688790.97 | 0.00 | 0.62 |
December | 0.485535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405455E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.154468E+11 | 0.272979E+10 | 0.00 | 11203517.37 | 0.301886E+09 | 0.181394E+11 | 0.361759E+10 | 0.00 | 0.87 |
Minimum of Months | 0.266170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.282740E+10 | 0.105440E+10 | 0.00 | 3100121.04 | 0.110264E+09 | 0.503638E+10 | 0.737980E+09 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563841E+10 | 0.00 | 0.00 | 0.34 |
February | 0.366145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407402E+10 | 0.00 | 0.00 | 0.33 |
March | 0.154681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210048E+10 | 0.00 | 0.00 | 0.35 |
April | 0.188468E+10 | 44443903.90 | 0.00 | 545151.84 | 11940428.88 | 0.591216E+09 | 0.301058E+09 | 0.00 | 0.41 |
May | 0.134340E+10 | 66172616.57 | 0.00 | 2848867.92 | 20489926.96 | 8127783.33 | 0.133856E+10 | 0.00 | 0.73 |
June | 0.526871E+09 | 0.778890E+09 | 0.00 | 3897986.97 | 37303600.65 | 0.00 | 0.121349E+10 | 0.00 | 0.91 |
July | 0.221525E+09 | 0.129205E+10 | 0.00 | 2768397.83 | 0.108702E+09 | 0.00 | 0.566505E+09 | 0.00 | 0.93 |
August | 0.349885E+09 | 0.121165E+10 | 0.00 | 3262479.13 | 66607489.94 | 0.00 | 0.704814E+09 | 0.00 | 0.90 |
September | 0.136789E+10 | 0.118967E+09 | 0.00 | 2108207.90 | 9295741.91 | 33664275.08 | 0.797302E+09 | 0.00 | 0.63 |
October | 0.236691E+10 | 0.00 | 0.00 | 51083.61 | 428341.86 | 0.267960E+09 | 85023113.43 | 0.00 | 0.40 |
November | 0.127031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211268E+10 | 0.00 | 0.00 | 0.36 |
December | 87936658.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443930E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.114789E+11 | 0.351217E+10 | 0.00 | 15482175.21 | 0.254767E+09 | 0.192659E+11 | 0.500676E+10 | 0.00 | 0.55 |
Minimum of Months | 87936658.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.236691E+10 | 0.129205E+10 | 0.00 | 3897986.97 | 0.108702E+09 | 0.563841E+10 | 0.133856E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.317715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617145E+10 | 0.00 | 0.00 | 0.61 |
February | 0.931208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415783E+10 | 0.00 | 0.00 | 0.62 |
March | 0.249204E+10 | 0.00 | 0.00 | 95712.86 | 0.00 | 0.209665E+10 | 94432931.80 | 0.00 | 0.72 |
April | 0.239348E+10 | 60217689.63 | 0.00 | 975261.92 | 10188256.82 | 0.638289E+09 | 0.633992E+09 | 0.00 | 0.87 |
May | 0.189649E+10 | 71381831.16 | 0.00 | 2900144.59 | 23840263.48 | 1101768.98 | 0.155950E+10 | 0.00 | 1.43 |
June | 0.895815E+09 | 0.708561E+09 | 0.00 | 3830322.30 | 45963990.40 | 778436.29 | 0.130502E+10 | 0.00 | 1.62 |
July | 0.327687E+09 | 0.116460E+10 | 0.00 | 3158157.98 | 0.159737E+09 | 0.00 | 0.693633E+09 | 0.00 | 1.70 |
August | 0.534021E+09 | 0.106686E+10 | 0.00 | 3571254.18 | 0.134269E+09 | 0.00 | 0.835918E+09 | 0.00 | 1.58 |
September | 0.169286E+10 | 0.114735E+09 | 0.00 | 2723894.03 | 10442618.63 | 32646530.69 | 0.105867E+10 | 0.00 | 1.25 |
October | 0.318635E+10 | 0.00 | 0.00 | 100291.03 | 555970.29 | 0.262307E+09 | 85011604.34 | 0.00 | 0.82 |
November | 0.161648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262325E+10 | 0.00 | 0.00 | 0.71 |
December | 0.490741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493687E+10 | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.167749E+11 | 0.318636E+10 | 0.00 | 17355038.90 | 0.384997E+09 | 0.209212E+11 | 0.626618E+10 | 0.00 | 1.05 |
Minimum of Months | 0.317715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.318635E+10 | 0.116460E+10 | 0.00 | 3830322.30 | 0.159737E+09 | 0.617145E+10 | 0.155950E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210835E+10 | 0.00 | 0.00 | 518304.64 | 0.00 | 0.517978E+10 | 0.371069E+09 | 0.00 | 0.45 |
February | 0.230111E+10 | 0.00 | 0.00 | 988554.44 | 0.00 | 0.329213E+10 | 0.516904E+09 | 0.00 | 0.47 |
March | 0.261863E+10 | 0.00 | 0.00 | 2096742.43 | 0.00 | 0.201439E+10 | 0.117998E+10 | 0.00 | 0.58 |
April | 0.249303E+10 | 0.118966E+09 | 0.00 | 3039336.47 | 10962527.59 | 0.652120E+09 | 0.154788E+10 | 0.00 | 0.74 |
May | 0.206226E+10 | 97166172.92 | 0.00 | 4200479.60 | 27497605.40 | 13829867.73 | 0.198232E+10 | 0.00 | 1.11 |
June | 0.104991E+10 | 0.904692E+09 | 0.00 | 4042012.63 | 66214561.87 | 0.00 | 0.130783E+10 | 0.00 | 1.17 |
July | 0.478983E+09 | 0.155288E+10 | 0.00 | 2856774.23 | 0.168969E+09 | 0.00 | 0.574891E+09 | 0.00 | 1.21 |
August | 0.612858E+09 | 0.154860E+10 | 0.00 | 4761073.52 | 0.112109E+09 | 0.00 | 0.102236E+10 | 0.00 | 1.30 |
September | 0.176441E+10 | 0.240756E+09 | 0.00 | 5683694.09 | 12312297.45 | 39030579.11 | 0.190712E+10 | 0.00 | 1.15 |
October | 0.268244E+10 | 200101.74 | 0.00 | 4749955.28 | 479832.10 | 0.211688E+09 | 0.211969E+10 | 0.00 | 0.79 |
November | 0.254331E+10 | 0.00 | 0.00 | 1057190.79 | 0.00 | 0.201158E+10 | 0.630457E+09 | 0.00 | 0.58 |
December | 0.125597E+10 | 0.00 | 0.00 | 1366757.43 | 0.00 | 0.452757E+10 | 0.740367E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.219713E+11 | 0.446326E+10 | 0.00 | 35360875.53 | 0.398544E+09 | 0.179421E+11 | 0.139009E+11 | 0.00 | 0.84 |
Minimum of Months | 0.478983E+09 | 0.00 | 0.00 | 518304.64 | 0.00 | 0.00 | 0.371069E+09 | 0.00 | 0.45 |
Maximum of Months | 0.268244E+10 | 0.155288E+10 | 0.00 | 5683694.09 | 0.168969E+09 | 0.517978E+10 | 0.211969E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.666970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610662E+10 | 0.00 | 0.00 | 0.63 |
February | 0.113114E+10 | 0.00 | 0.00 | 30785.18 | 0.00 | 0.414344E+10 | 37889761.06 | 0.00 | 0.64 |
March | 0.228415E+10 | 0.00 | 0.00 | 279100.27 | 0.00 | 0.236753E+10 | 0.238424E+09 | 0.00 | 0.75 |
April | 0.242158E+10 | 42612104.20 | 0.00 | 1494842.89 | 24575578.18 | 0.632559E+09 | 0.838314E+09 | 0.00 | 0.93 |
May | 0.234942E+10 | 65840106.63 | 0.00 | 2231796.88 | 29585537.51 | 16048996.11 | 0.112023E+10 | 0.00 | 1.45 |
June | 0.101178E+10 | 0.658422E+09 | 0.00 | 3093779.58 | 63680616.49 | 1200095.21 | 0.102759E+10 | 0.00 | 1.54 |
July | 0.460375E+09 | 0.123104E+10 | 0.00 | 2374210.26 | 0.140968E+09 | 0.00 | 0.437359E+09 | 0.00 | 1.55 |
August | 0.599765E+09 | 0.106461E+10 | 0.00 | 3125579.05 | 0.147917E+09 | 0.00 | 0.696116E+09 | 0.00 | 1.57 |
September | 0.211588E+10 | 0.130711E+09 | 0.00 | 1874967.48 | 12887438.90 | 56359593.52 | 0.676885E+09 | 0.00 | 1.27 |
October | 0.297369E+10 | 0.00 | 0.00 | 679772.53 | 580532.58 | 0.313991E+09 | 0.436184E+09 | 0.00 | 0.87 |
November | 0.182949E+10 | 0.00 | 0.00 | 83008.81 | 0.00 | 0.254140E+10 | 61077637.00 | 0.00 | 0.75 |
December | 0.667388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499762E+10 | 0.00 | 0.00 | 0.63 |
Annual Sum or Average | 0.185116E+11 | 0.319323E+10 | 0.00 | 15267842.94 | 0.420195E+09 | 0.211768E+11 | 0.557006E+10 | 0.00 | 1.05 |
Minimum of Months | 0.460375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
Maximum of Months | 0.297369E+10 | 0.123104E+10 | 0.00 | 3125579.05 | 0.147917E+09 | 0.610662E+10 | 0.112023E+10 | 0.00 | 1.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.221473E+12 | 0.479854E+11 | 0.00 | 0.156691E+12 | 0.221218E+11 |
February | 0.237080E+12 | 0.361413E+11 | 0.00 | 0.145350E+12 | 0.145208E+11 |
March | 0.334711E+12 | 0.318694E+11 | 0.00 | 0.172323E+12 | 0.833400E+10 |
April | 0.385510E+12 | 0.193423E+11 | 0.00 | 0.184216E+12 | 0.247630E+11 |
May | 0.433952E+12 | 0.106912E+11 | 0.00 | 0.221642E+12 | 0.583283E+11 |
June | 0.446839E+12 | 0.238885E+10 | 0.00 | 0.114447E+12 | 0.174646E+12 |
July | 0.448964E+12 | -151571514.9 | 0.00 | 0.450686E+11 | 0.241373E+12 |
August | 0.393471E+12 | 0.188892E+10 | 0.00 | 0.875799E+11 | 0.228565E+12 |
September | 0.284204E+12 | 0.934173E+10 | 0.00 | 0.186296E+12 | 0.911029E+11 |
October | 0.226894E+12 | 0.194814E+11 | 0.00 | 0.202100E+12 | 0.687414E+10 |
November | 0.149752E+12 | 0.300834E+11 | 0.00 | 0.161808E+12 | 0.754480E+10 |
December | 0.130313E+12 | 0.402237E+11 | 0.00 | 0.151942E+12 | 0.157557E+11 |
Annual Sum or Average | 0.369316E+13 | 0.249286E+12 | 0.00 | 0.182946E+13 | 0.893929E+12 |
Minimum of Months | 0.130313E+12 | -151571514.9 | 0.00 | 0.450686E+11 | 0.687414E+10 |
Maximum of Months | 0.448964E+12 | 0.479854E+11 | 0.00 | 0.221642E+12 | 0.241373E+12 |