Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2023-10-16 08:29:14


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 177.83 347.89 347.89
Net Site Energy 177.83 347.89 347.89
Total Source Energy 561.36 1098.21 1098.21
Net Source Energy 561.36 1098.21 1098.21


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 6.91 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 34.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 13.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 176.95 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 6.91 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 19.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 34.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 13.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 25.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 23.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 6.91 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 19.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 34.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 13.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 25.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 95.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 147.82 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 346.18 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 95.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 147.82 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 346.18 1.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 176.953 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 176.953 100.00
     
Total On-Site and Utility Electric Sources 176.953 100.00
Total Electricity End Uses 176.953 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 32.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 1857.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
RunPeriod RUNPERIOD 1
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 7.7125 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 7.7125 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 7.7125 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 7.7125 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 7.7125 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 7.7125 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 7.7125 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 7.7125 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             7.7125 9.29 6.7800  
Conditioned Total 511.16             7.7125 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 7.7125 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 18-JAN-08:20 06-FEB-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 8710.13 16291.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2381.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2166.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2737.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 19461.25 16291.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 8710.13 16291.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2381.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2166.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2737.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 21.87 0.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 60.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 110.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 167.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 81.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 75.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 560.41 0.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 42.79 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 117.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 216.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 148.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1096.35 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 42.79 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 117.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 216.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 158.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 148.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1096.35 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.374068
PERIMETER_ZN_1 DIRECT AIR 0.413145
PERIMETER_ZN_2 DIRECT AIR 0.336061
PERIMETER_ZN_3 DIRECT AIR 0.402932
PERIMETER_ZN_4 DIRECT AIR 0.407768
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.374068 0.374068 0.374068 0.374068 0.374068 0.374068 1.00 1.00 0.374068
PSZ-AC:2 0.413145 0.413145 0.413145 0.413145 0.413145 0.413145 1.00 1.00 0.413145
PSZ-AC:3 0.336061 0.336061 0.336061 0.336061 0.336061 0.336061 1.00 1.00 0.336061
PSZ-AC:4 0.402932 0.402932 0.402932 0.402932 0.402932 0.402932 1.00 1.000000 0.402932
PSZ-AC:5 0.407768 0.407768 0.407768 0.407768 0.407768 0.407768 1.00 1.00 0.407768
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.374068 0.064622
PSZ-AC:2_OA_CONTROLLER 0.413145 0.048988
PSZ-AC:3_OA_CONTROLLER 0.336061 0.029060
PSZ-AC:4_OA_CONTROLLER 0.402932 0.048988
PSZ-AC:5_OA_CONTROLLER 0.407768 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.374068 6192.15 0.800655
PSZ-AC:2 HP COOLING COIL 0.413145 6839.01 0.800655
PSZ-AC:3 HP COOLING COIL 0.336061 5563.00 0.800655
PSZ-AC:4 HP COOLING COIL 0.402932 6669.96 0.800655
PSZ-AC:5 HP COOLING COIL 0.407768 6750.01 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.374068 0.374068 0.374068 0.374068 6192.15 6192.15 40.00 3184.94 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.413145 0.413145 0.413145 0.413145 6839.01 6839.01 40.00 5356.88 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.336061 0.336061 0.336061 0.336061 5563.00 5563.00 40.00 3378.71 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.402932 0.402932 0.402932 0.402932 6669.96 6669.96 40.00 5407.91 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.407768 0.407768 0.407768 0.407768 6750.01 6750.01 40.00 3378.71 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.374068
PSZ-AC:2 FAN 0.413145
PSZ-AC:3 FAN 0.336061
PSZ-AC:4 FAN 0.402932
PSZ-AC:5 FAN 0.407768
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.374068 6192.15
PSZ-AC:2 HEATING COIL 0.413145 6839.01
PSZ-AC:3 HEATING COIL 0.336061 5563.00
PSZ-AC:4 HEATING COIL 0.402932 6669.96
PSZ-AC:5 HEATING COIL 0.407768 6750.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 3184.94
PSZ-AC:2_SUPPHEATCOIL 5356.88
PSZ-AC:3_SUPPHEATCOIL 3378.71
PSZ-AC:4_SUPPHEATCOIL 5407.91
PSZ-AC:5_SUPPHEATCOIL 3378.71
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.70 7.00 2.10 2.60 4.30 8.80 13.90 17.80 23.20 25.60 24.10 20.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 35.04 -106.62 -7.00 1619.00 83328 0.9904


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 13.63 23.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1154.233 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1154.233
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.6674E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.8594E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.8089E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.9831E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1709E-003
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3138E-003
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 5.6170E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 6.2747E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0256E-002
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 9.6426E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0302E-002
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.0243E-002
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 9.6148E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 6.6949E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 4.7897E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 2.5957E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.7300E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 8.9625E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.7666E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 9.5193E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.0441E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.1844E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 3.9765E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.3981E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.6599E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.8407E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.8028E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.9678E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1647E-003
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.2977E-003
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 5.5714E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 6.1732E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.5916E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.6109E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.7438E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.7606E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1104E-003
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1239E-003
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 5.2581E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 5.3269E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.5866E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.5903E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.7396E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.7428E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1069E-003
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1094E-003
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 5.2377E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 5.2510E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.5012E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.0004E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.6638E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.1528E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.8041E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.1295E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 8.8953E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 9.9908E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.2016E-003
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.3396E-003
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.0948E-003
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.1962E-003
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.0380E-003
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0852E-003
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.8134E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.4186E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.7968E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.7598E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.8304E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.0819E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3845E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.7206E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.3052E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.7554E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2406E-002
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.9191E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2789E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.5593E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.0761E-002
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.2618E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.1357E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.9592E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.4004E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.7415E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.3435E-003
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.6939E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.1428E-003
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.3397E-003
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.8574E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 9.5197E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.1231E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.2870E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.9179E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.8156E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.0846E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.6755E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 5.5595E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.1347E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.7990E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.1976E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.9717E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.4252E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8281E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6759E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.6287E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.3049E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.2343E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.7437E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.0553E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.8176E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7894E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8750E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.2600E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.6997E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.2735E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.6619E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.0354E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.0980E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.1784E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.8488E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.6511E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.3380E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.5921E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.7658E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.4910E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.6276E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.7244E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.8177E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.2692E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.3457E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.5414E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.5763E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.4503E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.4780E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6931E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.7124E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.2461E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.2605E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.3746E-003
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.6909E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.3098E-003
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.6297E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.1246E-003
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.3143E-003
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.8718E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.5295E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1638E-002
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.6129E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1837E-002
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.2157E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.0384E-002
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.0444E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.1152E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.9212E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.8080E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.7154E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.8197E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.0282E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3330E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.6393E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.3019E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.7236E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1797E-003
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.3182E-003
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.0660E-003
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.1676E-003
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.0177E-003
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.0640E-003
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.8262E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.4280E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3494.33342 4193.20011 0.31172 0.37407 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 33.93000 5.69757E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 1115.59586 1338.71504 5.84767E-002 7.01721E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90000 2.34317E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3859.39404 4631.27284 0.34429 0.41314 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.69500 5.69875E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 3334.04319 4000.85182 0.17475 0.20971 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90000 2.34317E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3139.38957 3767.26748 0.28005 0.33606 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.30750 5.69198E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2147.72327 2577.26793 0.11257 0.13509 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90000 2.34317E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3764.01147 4516.81376 0.33578 0.40293 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 34.42500 5.69833E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 3377.19994 4052.63993 0.17702 0.21242 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90000 2.34317E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3809.24816 4571.09779 0.33981 0.40777 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 32.31000 5.69506E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2147.72327 2577.26793 0.11257 0.13509 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90000 2.34317E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4774.10 0.37407 0.37407 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 3184.94 7.01721E-002 7.01721E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 PSZ-AC:2 Cooling Sensible 5086.47 0.41314 0.41314 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 5356.88 0.20971 0.20971 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3894.62 0.33606 0.33606 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 3378.71 0.13509 0.13509 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 4960.61 0.40293 0.40293 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 5407.91 0.21242 0.21242 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4743.94 0.40777 0.40777 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 3378.71 0.13509 0.13509 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.37407
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.41314
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.33606
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40293
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40777
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.37407
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.37407
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.37407
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.37407
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.37407
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.37407
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.41314
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.41314
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.41314
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.41314
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.41314
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.41314
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.33606
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.33606
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.33606
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.33606
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.33606
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.33606
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40293
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40293
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40293
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.40293
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40293
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.40293
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40777
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40777
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40777
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.40777
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40777
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.40777
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.37407
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.41314
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.33606
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.40293
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.40777
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.37407
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.37407
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6192.14917
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.37407
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.37407
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.37407
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.37407
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6192.14917
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6192.14917
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3184.94223
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.37407
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.37407
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6192.14917
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 3184.94223
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.41314
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.41314
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6839.01474
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.41314
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.41314
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.41314
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.41314
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6839.01474
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6839.01474
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5356.87839
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.41314
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.41314
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6839.01474
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 5356.87839
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.33606
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.33606
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5562.99956
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.33606
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.33606
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.33606
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.33606
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5562.99956
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5562.99956
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3378.70813
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.33606
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.33606
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5562.99956
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 3378.70813
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40293
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40293
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6669.96297
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40293
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40293
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40293
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40293
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6669.96297
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6669.96297
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5407.91222
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.40293
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40293
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6669.96297
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 5407.91222
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40777
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40777
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6750.00645
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40777
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40777
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40777
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40777
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6750.00645
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6750.00645
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3378.70813
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.40777
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40777
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6750.00645
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 3378.70813
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5899.0 3.29 11.22 11.74 11.10 10.96
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6515.2 3.29 11.22 11.74 11.10 10.96
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 5299.6 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 6354.2 3.29 11.22 11.74 11.10 10.96
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 6430.4 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 6488.9 3613.9 7.35 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 7166.8 3991.5 7.32 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5829.6 3246.8 7.33 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 6989.6 3892.8 7.32 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 7073.5 3939.5 7.32 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.8172740299E-002 9.1463424077E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 8.8602348349E-002 6.4996892065E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 4.7572154914E-002 5.0655742501E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.1171959755 0.1642212677 Pass Pass 0.1688482992 0.6290021297 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 6.4714963369E-002 4.9147544690E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.4947807354 0.5315673054 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1224.99 40.98 0.00 86.27 96.71 1448.95



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 9.00 6      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 5.00 4      
Nov 9.00 7      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.228 0.237 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.256 0.267 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.228 0.237 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.256 0.267 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.3822_SHGC_SOUTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.3822_SHGC_SOUTH_0.36   3.91 0.00 0.00 3.91 3.91 2.171 0.361 0.361             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.3822_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.3822_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.3822_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.3822_SHGC_EAST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.3822_SHGC_NORTH_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.3822_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.3822_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.3822_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.3822_SHGC_WEST_0.36   2.79 0.00 0.00 2.79 2.79 2.171 0.361 0.361             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.171 0.361 0.361                      
North Total or Average             16.72 2.171 0.361 0.361                      
Non-North Total or Average             42.93 2.171 0.361 0.361                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.91 0.89 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.91 0.89 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.91 0.89 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.91 0.89 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.91 0.89 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.91 0.89 0.89 0.01 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.09 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.23 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.98 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.98 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.98 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.98 0.00 0.00 0.85 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 7.7125 149.66 1154.23 LightsWired LTG_SCH_OFFICE 52.79 168.00 51.86 0.0000 Y 11.24
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 44.05 0.0000 Y 7.23
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 45.33 0.0000 Y 4.42
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 46.52 0.0000 Y 7.64
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 45.41 0.0000 Y 4.42
Interior Lighting Total       7.7125 511.16 3942.30               34.95


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   41.81 41.81 0.52
EXTERIOR_LIGHTS_B 982.38 AstronomicalClock -   83.71 71.14 13.12
Exterior Lighting Total 1049.11           13.64



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6192.15 4957.78 1234.37 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6839.01 5475.69 1363.32 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5563.00 4454.04 1108.95 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6669.96 5340.34 1329.62 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6750.01 5404.43 1345.58 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5899.0 3.29 11.22 11.74 11.10 10.96
PSZ-AC:2 HP COOLING COIL   6515.2 3.29 11.22 11.74 11.10 10.96
PSZ-AC:3 HP COOLING COIL   5299.6 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   6354.2 3.29 11.22 11.74 11.10 10.96
PSZ-AC:5 HP COOLING COIL   6430.4 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 6488.9 3613.9 7.35 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 7166.8 3991.5 7.32 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5829.6 3246.8 7.33 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 6989.6 3892.8 7.32 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 7073.5 3939.5 7.32 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6192.15 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   3184.94 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6839.01 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   5356.88 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   5563.00 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   3378.71 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   6669.96 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   5407.91 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   6750.01 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   3378.71 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.37 419.00 1120.11 1.00 1.75 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.41 462.77 1120.11 1.00 1.70 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.34 376.42 1120.11 1.00 1.82 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.40 451.33 1120.11 1.00 1.71 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.41 456.74 1120.11 1.00 1.71 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3494.33 4193.20 28.02 0.312 0.374 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00901 33.93 0.00570 0.065 0.00
PERIMETER_ZN_1 3859.39 4631.27 40.82 0.344 0.413 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 23.89 23.89 0.00876 34.70 0.00570 0.049 0.00
PERIMETER_ZN_2 3139.39 3767.27 55.98 0.280 0.336 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 23.89 23.89 0.00868 30.31 0.00569 0.029 0.00
PERIMETER_ZN_3 3764.01 4516.81 39.81 0.336 0.403 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00876 34.43 0.00570 0.049 0.00
PERIMETER_ZN_4 3809.25 4571.10 67.92 0.340 0.408 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 23.89 23.89 0.00865 32.31 0.00570 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1115.60 1338.72 8.95 0.058 0.070 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 -7.90 0.00234 0.065 0.00
PERIMETER_ZN_1 3334.04 4000.85 35.27 0.175 0.210 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00772 -7.90 0.00234 0.049 0.00
PERIMETER_ZN_2 2147.72 2577.27 38.30 0.113 0.135 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00771 -7.90 0.00234 0.029 0.00
PERIMETER_ZN_3 3377.20 4052.64 35.72 0.177 0.212 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00772 -7.90 0.00234 0.049 0.00
PERIMETER_ZN_4 2147.72 2577.27 38.30 0.113 0.135 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00771 -7.90 0.00234 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.37 0.37 0.07 0.07 0.3741 0.3741 0.3741 1.0000 1.0000
PSZ-AC:2 0.41 0.41 0.21 0.21 0.4131 0.4131 0.4131 1.0000 1.0000
PSZ-AC:3 0.34 0.34 0.14 0.14 0.3361 0.3361 0.3361 1.0000 1.0000
PSZ-AC:4 0.40 0.40 0.21 0.21 0.4029 0.4029 0.4029 1.0000 1.0000
PSZ-AC:5 0.41 0.41 0.14 0.14 0.4078 0.4078 0.4078 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6192.149 4957.777 0.374068 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5593.06 5593.06 0.374068 26.73 15.24 0.00843960 12.80 10.28 0.00843960 33.93 0.00569757 15.40 17.2755 23.89 0.00901655 40.1547 3469.25 0.00 6191.09 4497.62
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6192.149 6192.149 0.374068 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6192.15 6192.15 0.374068 16.10 10.22 0.00702275 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 17.2755 21.11 0.00800000 42.2502 1115.60 0.00 6200.29 6200.29
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 3184.942 3184.942 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3184.94 3184.94 0.374068 16.10 10.22 0.00702275 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 17.2755 21.11 0.00800000 42.2502 1115.60 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6839.015 5475.693 0.413145 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 6095.11 6095.11 0.413145 26.28 15.06 0.00839334 12.80 10.23 0.00839334 34.70 0.00569875 15.64 11.8573 23.89 0.00875609 39.0103 3853.94 0.00 6837.84 4967.47
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6839.015 6839.015 0.413145 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6839.01 6839.01 0.413145 17.67 10.88 0.00708114 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 11.8573 21.11 0.00771851 40.7838 3334.04 0.00 6848.00 6848.00
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 5356.878 5356.878 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5356.88 5356.88 0.413145 17.67 10.88 0.00708114 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 11.8573 21.11 0.00771851 40.7838 3334.04 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5563.000 4454.045 0.336061 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 5142.91 5142.91 0.336061 25.55 14.84 0.00842002 12.80 10.26 0.00842002 30.31 0.00569198 14.20 8.6473 23.89 0.00867898 38.6709 3136.41 0.00 5562.05 4040.64
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5563.000 5563.000 0.336061 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5563.00 5563.00 0.336061 18.60 11.39 0.00724517 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 8.6473 21.11 0.00770919 40.7354 2147.72 0.00 5570.31 5570.31
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 3378.708 3378.708 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3378.71 3378.71 0.336061 18.60 11.39 0.00724517 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 8.6473 21.11 0.00770919 40.7354 2147.72 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6669.963 5340.341 0.402932 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 5961.59 5961.59 0.402932 26.28 15.05 0.00838951 12.80 10.23 0.00838951 34.43 0.00569833 15.56 12.1578 23.89 0.00876252 39.0382 3757.36 0.00 6668.82 4844.68
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6669.963 6669.963 0.402932 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6669.96 6669.96 0.402932 17.58 10.84 0.00706799 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 12.1578 21.11 0.00772193 40.8017 3377.20 0.00 6678.73 6678.73
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 5407.912 5407.912 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5407.91 5407.91 0.402932 17.58 10.84 0.00706799 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 12.1578 21.11 0.00772193 40.8017 3377.20 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6750.006 5404.428 0.407768 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 6134.00 6134.00 0.407768 25.60 14.87 0.00843763 12.80 10.28 0.00843763 32.31 0.00569506 14.87 7.1266 23.89 0.00864809 38.5350 3809.25 0.00 6748.85 4902.82
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6750.006 6750.006 0.407768 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6750.01 6750.01 0.407768 19.04 11.62 0.00732677 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 7.1266 21.11 0.00770919 40.7354 2147.72 0.00 6758.88 6758.88
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 3378.708 3378.708 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3378.71 3378.71 0.407768 19.04 11.62 0.00732677 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 7.1266 21.11 0.00770919 40.7354 2147.72 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6192.149 4957.777 0.374068 -999.0 -999.000 -999.0000 1.09396 1.00000 1020.5288 1004.8586 0.9904 PSZ-AC:1 FAN Fan:OnOff 0.374068 0.37048001   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5593.06 5593.06 0.9033 0.37048001 0.374068 26.73 15.24 0.00843960 48387.9 12.80 10.28 0.00843960 34169.7 -999.0 -999.00 -999.00 -999.00 418.996 5174.06 33.93 0.00569757 15.40 0.06462207 17.2755 23.89 0.00901222 23.89 0.00901655 40.1547 3469.25 0.00 6191.09 4497.62 0.35584885 26.67 19.44 0.01118466 55322.4 14.30 13.50 0.00931879 37924.3
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6192.149 6192.149 0.374068 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:1 FAN Fan:OnOff 0.374068 0.37048001   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6192.15 6192.15 1.0000 0.37048001 0.374068 16.10 10.22 0.00702275 33949.9 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6192.15 -7.90 0.00234317 -7.90 0.06462207 17.2755 21.11 0.00800000 21.11 0.00800000 42.2502 1115.60 0.00 6200.29 6200.29 0.36393351 21.11 15.56 0.00875166 43444.1 37.80 21.07 0.00875166 60481.0
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3184.942 3184.942 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:1 FAN Fan:OnOff 0.374068 0.37048001   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3184.94 3184.94 1.0000 0.37048001 0.374068 16.10 10.22 0.00702275 33949.9 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3184.94 -7.90 0.00234317 -7.90 0.06462207 17.2755 21.11 0.00800000 21.11 0.00800000 42.2502 1115.60 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6839.015 5475.693 0.413145 -999.0 -999.000 -999.0000 1.11406 1.00000 1020.4428 1004.8586 0.9904 PSZ-AC:2 FAN Fan:OnOff 0.413145 0.40918236   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 6095.11 6095.11 0.8912 0.40918236 0.413145 26.28 15.06 0.00839334 47807.5 12.80 10.23 0.00839334 34052.9 -999.0 -999.00 -999.00 -999.00 462.767 5632.35 34.70 0.00569875 15.64 0.04898771 11.8573 23.89 0.00875583 23.89 0.00875609 39.0103 3853.94 0.00 6837.84 4967.47 0.39302275 26.67 19.44 0.01118466 55322.4 14.30 13.50 0.00931879 37924.3
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6839.015 6839.015 0.413145 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:2 FAN Fan:OnOff 0.413145 0.40918236   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6839.01 6839.01 1.0000 0.40918236 0.413145 17.67 10.88 0.00708114 35697.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6839.01 -7.90 0.00234317 -7.90 0.04898771 11.8573 21.11 0.00771851 21.11 0.00771851 40.7838 3334.04 0.00 6848.00 6848.00 0.40195199 21.11 15.56 0.00875166 43444.1 37.80 21.07 0.00875166 60481.0
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5356.878 5356.878 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:2 FAN Fan:OnOff 0.413145 0.40918236   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5356.88 5356.88 1.0000 0.40918236 0.413145 17.67 10.88 0.00708114 35697.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5356.88 -7.90 0.00234317 -7.90 0.04898771 11.8573 21.11 0.00771851 21.11 0.00771851 40.7838 3334.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5563.000 4454.045 0.336061 -999.0 -999.000 -999.0000 1.21853 1.00000 1020.4924 1004.8586 0.9904 PSZ-AC:3 FAN Fan:OnOff 0.336061 0.33283761   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 5142.91 5142.91 0.9245 0.33283761 0.336061 25.55 14.84 0.00842002 47134.6 12.80 10.26 0.00842002 34120.3 -999.0 -999.00 -999.00 -999.00 376.424 4766.48 30.31 0.00569198 14.20 0.02906014 8.6473 23.89 0.00867826 23.89 0.00867898 38.6709 3136.41 0.00 5562.05 4040.64 0.31969304 26.67 19.44 0.01118466 55322.4 14.30 13.50 0.00931879 37924.3
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5563.000 5563.000 0.336061 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:3 FAN Fan:OnOff 0.336061 0.33283761   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5563.00 5563.00 1.0000 0.33283761 0.336061 18.60 11.39 0.00724517 37060.9 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5563.00 -7.90 0.00234317 -7.90 0.02906014 8.6473 21.11 0.00770919 21.11 0.00770919 40.7354 2147.72 0.00 5570.31 5570.31 0.32695626 21.11 15.56 0.00875166 43444.1 37.80 21.07 0.00875166 60481.0
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3378.708 3378.708 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:3 FAN Fan:OnOff 0.336061 0.33283761   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3378.71 3378.71 1.0000 0.33283761 0.336061 18.60 11.39 0.00724517 37060.9 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3378.71 -7.90 0.00234317 -7.90 0.02906014 8.6473 21.11 0.00770919 21.11 0.00770919 40.7354 2147.72 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6669.963 5340.341 0.402932 -999.0 -999.000 -999.0000 1.11730 1.00000 1020.4357 1004.8586 0.9904 PSZ-AC:4 FAN Fan:OnOff 0.402932 0.39906789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 5961.59 5961.59 0.8938 0.39906789 0.402932 26.28 15.05 0.00838951 47797.4 12.80 10.23 0.00838951 34043.2 -999.0 -999.00 -999.00 -999.00 451.328 5510.26 34.43 0.00569833 15.56 0.04898771 12.1578 23.89 0.00876199 23.89 0.00876252 39.0382 3757.36 0.00 6668.82 4844.68 0.38330773 26.67 19.44 0.01118466 55322.4 14.30 13.50 0.00931879 37924.3
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6669.963 6669.963 0.402932 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:4 FAN Fan:OnOff 0.402932 0.39906789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6669.96 6669.96 1.0000 0.39906789 0.402932 17.58 10.84 0.00706799 35575.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6669.96 -7.90 0.00234317 -7.90 0.04898771 12.1578 21.11 0.00772193 21.11 0.00772193 40.8017 3377.20 0.00 6678.73 6678.73 0.39201624 21.11 15.56 0.00875166 43444.1 37.80 21.07 0.00875166 60481.0
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5407.912 5407.912 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:4 FAN Fan:OnOff 0.402932 0.39906789   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5407.91 5407.91 1.0000 0.39906789 0.402932 17.58 10.84 0.00706799 35575.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5407.91 -7.90 0.00234317 -7.90 0.04898771 12.1578 21.11 0.00772193 21.11 0.00772193 40.8017 3377.20 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6750.006 5404.428 0.407768 -999.0 -999.000 -999.0000 1.19373 1.00000 1020.5251 1004.8586 0.9904 PSZ-AC:5 FAN Fan:OnOff 0.407768 0.40385694   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 6134.00 6134.00 0.9087 0.40385694 0.407768 25.60 14.87 0.00843763 47225.4 12.80 10.28 0.00843763 34164.7 -999.0 -999.00 -999.00 -999.00 456.744 5677.26 32.31 0.00569506 14.87 0.02906014 7.1266 23.89 0.00864809 23.89 0.00864809 38.5350 3809.25 0.00 6748.85 4902.82 0.38790765 26.67 19.44 0.01118466 55322.4 14.30 13.50 0.00931879 37924.3
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6750.006 6750.006 0.407768 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:5 FAN Fan:OnOff 0.407768 0.40385694   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6750.01 6750.01 1.0000 0.40385694 0.407768 19.04 11.62 0.00732677 37717.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6750.01 -7.90 0.00234317 -7.90 0.02906014 7.1266 21.11 0.00770919 21.11 0.00770919 40.7354 2147.72 0.00 6758.88 6758.88 0.39672067 21.11 15.56 0.00875166 43444.1 37.80 21.07 0.00875166 60481.0
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3378.708 3378.708 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 PSZ-AC:5 FAN Fan:OnOff 0.407768 0.40385694   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3378.71 3378.71 1.0000 0.40385694 0.407768 19.04 11.62 0.00732677 37717.1 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3378.71 -7.90 0.00234317 -7.90 0.02906014 7.1266 21.11 0.00770919 21.11 0.00770919 40.7354 2147.72 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2019.67 2220.50 344.00
PERIMETER_ZN_1 2050.50 2481.67 713.67
PERIMETER_ZN_2 2219.67 2128.83 1106.17
PERIMETER_ZN_3 2781.67 2701.50 1568.00
PERIMETER_ZN_4 2572.00 2697.00 1350.00
ATTIC 0.00 0.00 0.00
Facility 3368.83 3021.67 1857.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 27.67 0.00 27.67
PERIMETER_ZN_1 0.17 6.33 0.17 4.17
PERIMETER_ZN_2 3.50 8.83 0.00 0.00
PERIMETER_ZN_3 10.50 0.00 0.00 0.00
PERIMETER_ZN_4 2.50 13.00 0.00 0.67
ATTIC 0.00 0.00 0.00 0.00
Facility 16.00 55.00 0.17 32.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.395 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.394 0.416 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.368 0.067 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.393 0.054 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.394 0.061 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.79 0.00 762126.79 0.00 762126.79 2037921.45 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_1 578314.04 0.00 578314.04 752119.88 1330433.91 1544876.42 5483.93 3276.08 0.00 20.53
PERIMETER_ZN_2 344200.95 0.00 344200.95 147405.49 491606.45 916440.58 5483.68 3276.32 0.00 849.26
PERIMETER_ZN_3 580898.22 0.00 580898.22 221108.24 802006.46 1544876.42 5482.76 3277.24 0.00 63.54
PERIMETER_ZN_4 344155.44 0.00 344155.44 147405.49 491560.94 916440.58 5483.62 3276.38 0.00 80.39
Total Facility 2609695.44 0.00 2609695.44 1268039.11 3877734.54 6960555.45 5484.00 3278.01 0.00 949.90


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0396 0.0770 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0038 0.0245 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0051 0.0426 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0034 0.0257 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0519 0.2192 0.2207 1008.00 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 747577.62 0.00 747577.62 2037921.45 8760.00 0.00 0.00 0.00
PSZ-AC:2 567273.89 0.00 567273.89 1544876.42 8760.00 0.00 0.00 20.02
PSZ-AC:3 337630.08 0.00 337630.08 916440.58 8760.00 0.00 0.00 844.96
PSZ-AC:4 569808.74 0.00 569808.74 1544876.42 8760.00 0.00 0.00 60.67
PSZ-AC:5 337585.44 0.00 337585.44 916440.58 8760.00 0.00 0.00 75.45


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0485 0.0000 0.0485 0.0646 4284.00 0.00 0.00
PSZ-AC:2 0.0367 0.0000 0.0367 0.0490 4284.00 0.00 0.00
PSZ-AC:3 0.0204 0.0000 0.0204 0.0291 3528.00 0.00 0.00
PSZ-AC:4 0.0367 0.0000 0.0367 0.0490 4284.00 0.00 0.00
PSZ-AC:5 0.0218 0.0000 0.0218 0.0291 4284.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3296.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3364.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3336.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3363.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0634 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0481 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0285 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0481 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0284 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 523
Defaulted Fields 365
Fields with Defaults 1332
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
Electricity:Building 87.75 1137.89 05-FEB-12:30 6143.85 13-NOV-17:00
Electricity:Zone:CORE_ZN 26.70 359.76 01-JAN-00:10 1798.81 02-JAN-08:10
Electricity:SpaceType:GENERAL 87.75 1137.89 05-FEB-12:30 6143.85 13-NOV-17:00
InteriorLights:Electricity 34.95 444.76 05-FEB-12:30 2678.20 13-NOV-17:00
InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 34.95 444.76 05-FEB-12:30 2678.20 13-NOV-17:00
LightsWired:InteriorLights:Electricity 34.95 444.76 05-FEB-12:30 2678.20 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 34.95 444.76 05-FEB-12:30 2678.20 13-NOV-17:00
Electricity:Zone:PERIMETER_ZN_1 18.95 244.20 01-JAN-07:50 1363.61 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.23 90.36 01-JAN-07:50 594.42 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.23 90.36 01-JAN-07:50 594.42 13-NOV-17:00
Electricity:Zone:PERIMETER_ZN_2 11.37 144.86 01-JAN-08:00 808.91 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.42 53.60 01-JAN-08:00 352.62 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.42 53.60 01-JAN-08:00 352.62 13-NOV-17:00
Electricity:Zone:PERIMETER_ZN_3 19.36 244.20 05-FEB-12:30 1363.61 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.64 90.36 05-FEB-12:30 594.42 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.64 90.36 05-FEB-12:30 594.42 13-NOV-17:00
Electricity:Zone:PERIMETER_ZN_4 11.38 144.86 01-JAN-13:40 808.91 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.42 53.60 01-JAN-13:40 352.62 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.42 53.60 01-JAN-13:40 352.62 13-NOV-17:00
InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
ElectricityPurchased:Facility 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
ElectricityPurchased:Plant 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
Cogeneration:ElectricityPurchased 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
General:Cogeneration:ElectricityPurchased 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
ElectricityNet:Plant 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
Cogeneration:ElectricityNet 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
General:Cogeneration:ElectricityNet 176.95 1709.89 20-FEB-11:10 19461.25 18-JAN-08:20
ExteriorLights:Electricity 13.64 0.00 01-JAN-07:20 1049.11 01-JAN-06:10
General:ExteriorLights:Electricity 13.64 0.00 01-JAN-07:20 1049.11 01-JAN-06:10
Electricity:HVAC 51.58 0.00 01-JAN-10:10 11197.62 18-JAN-07:30
Fans:Electricity 25.63 0.00 01-JAN-00:10 2166.26 02-JAN-06:10
General:Fans:Electricity 25.63 0.00 01-JAN-00:10 2166.26 02-JAN-06:10
Cooling:Electricity 19.04 0.00 01-JAN-00:10 7109.38 28-JUN-16:00
General:Cooling:Electricity 19.04 0.00 01-JAN-00:10 7109.38 28-JUN-16:00
Heating:Electricity 6.91 0.00 01-JAN-10:10 9031.36 18-JAN-07:30
General:Heating:Electricity 6.91 0.00 01-JAN-10:10 9031.36 18-JAN-07:30
Electricity:Plant 23.98 572.00 02-MAR-09:00 2811.41 06-FEB-12:50
WaterSystems:Electricity 23.98 572.00 06-JAN-11:50 2811.41 06-FEB-12:50
Water Heater:WaterSystems:Electricity 23.98 572.00 06-JAN-11:50 2811.41 06-FEB-12:50
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 06-JAN-11:30
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 06-JAN-11:30


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.87 0.00 01-JAN-00:10 16291.78 06-FEB-07:10
NaturalGas:HVAC 0.87 0.00 01-JAN-00:10 16291.78 06-FEB-07:10
Heating:NaturalGas 0.87 0.00 01-JAN-00:10 16291.78 06-FEB-07:10
General:Heating:NaturalGas 0.87 0.00 01-JAN-00:10 16291.78 06-FEB-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-JAN-12:10
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-JAN-12:10
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 08-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 08-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 176.98 0.00 01-JAN-00:10 54214.48 06-FEB-07:10
EnergyTransfer:Building 81.90 0.00 01-JAN-00:10 25349.37 06-FEB-07:10
EnergyTransfer:Zone:CORE_ZN 20.59 0.00 01-JAN-00:10 5536.55 26-JUN-07:10
Heating:EnergyTransfer 11.47 0.00 01-JAN-00:10 25168.71 06-FEB-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.37 0.00 01-JAN-00:10 2632.81 06-FEB-07:10
General:Heating:EnergyTransfer 11.47 0.00 01-JAN-00:10 25168.71 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.37 0.00 01-JAN-00:10 2632.81 06-FEB-07:10
Cooling:EnergyTransfer 70.43 0.00 01-JAN-00:10 23628.01 21-AUG-07:20
Cooling:EnergyTransfer:Zone:CORE_ZN 20.22 0.00 01-JAN-00:10 5536.55 26-JUN-07:10
General:Cooling:EnergyTransfer 70.43 0.00 01-JAN-00:10 23628.01 21-AUG-07:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 20.22 0.00 01-JAN-00:10 5536.55 26-JUN-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 20.27 0.00 01-JAN-00:10 8197.15 06-FEB-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 2.41 0.00 01-JAN-00:10 8197.15 06-FEB-07:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 2.41 0.00 01-JAN-00:10 8197.15 06-FEB-07:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 17.87 0.00 01-JAN-00:10 6053.64 04-OCT-13:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 17.87 0.00 01-JAN-00:10 6053.64 04-OCT-13:00
EnergyTransfer:Zone:PERIMETER_ZN_2 12.94 0.00 01-JAN-00:10 4716.34 07-AUG-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.72 0.00 01-JAN-00:10 3912.51 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.72 0.00 01-JAN-00:10 3912.51 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 11.22 0.00 01-JAN-00:10 4716.34 07-AUG-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 11.22 0.00 01-JAN-00:10 4716.34 07-AUG-07:20
EnergyTransfer:Zone:PERIMETER_ZN_3 16.37 0.00 01-JAN-00:10 6591.17 06-FEB-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 4.83 0.00 01-JAN-00:10 6591.17 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 4.83 0.00 01-JAN-00:10 6591.17 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.54 0.00 01-JAN-00:10 5167.78 21-AUG-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.54 0.00 01-JAN-00:10 5167.78 21-AUG-07:20
EnergyTransfer:Zone:PERIMETER_ZN_4 11.73 0.00 01-JAN-00:10 4295.88 21-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 2.14 0.00 01-JAN-00:10 4003.38 06-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 2.14 0.00 01-JAN-00:10 4003.38 06-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 9.59 0.00 01-JAN-00:10 4295.88 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 9.59 0.00 01-JAN-00:10 4295.88 21-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
EnergyTransfer:HVAC 95.08 0.00 01-JAN-00:10 29692.15 21-AUG-07:20
CoolingCoils:EnergyTransfer 82.48 0.00 01-JAN-00:10 29692.15 21-AUG-07:20
HeatingCoils:EnergyTransfer 12.60 0.00 01-JAN-00:10 28865.09 06-FEB-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 07-FEB-07:10 95.20 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.371 -20.217 0.000 0.000 5.121 11.237 15.459 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -11.970
PERIMETER_ZN_1 0.000 0.000 2.408 -17.867 0.000 0.000 3.904 7.235 11.719 26.830 0.000 0.681 0.000 0.000 -9.110 0.000 -7.130 -18.669
PERIMETER_ZN_2 0.000 0.000 1.725 -11.217 0.000 0.000 1.715 4.416 6.952 12.739 0.000 0.036 0.000 0.000 -4.626 0.000 -1.459 -10.282
PERIMETER_ZN_3 0.000 0.000 4.825 -11.544 0.000 0.000 4.032 7.640 11.719 5.689 0.000 0.063 0.000 0.000 -7.029 0.000 -2.041 -13.355
PERIMETER_ZN_4 0.000 0.000 2.141 -9.587 0.000 0.000 2.344 4.425 6.952 11.771 0.000 0.034 0.000 0.000 -4.978 0.000 -1.488 -11.613
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.209 28.990 0.000 0.000 0.000 -40.199 -0.000
Total Facility 0.000 0.000 11.469 -70.432 0.000 0.000 17.115 34.953 52.800 57.029 0.000 12.024 28.991 0.000 -25.742 0.000 -52.317 -65.890


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 12-OCT-07:03 0.00 0.00 0.00 -6356.54 0.00 0.00 525.20 784.13 1014.68 0.00 0.00 0.00 4032.54 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 02-OCT-06:02 0.00 0.00 0.00 -6450.59 0.00 0.00 64.39 275.12 384.60 0.00 0.00 0.00 7521.21 0.00 -440.55 0.00 -1354.18 0.00
PERIMETER_ZN_2 20-AUG-08:52 0.00 0.00 0.00 -5121.82 0.00 0.00 0.00 53.60 91.26 2999.33 0.00 0.00 1993.11 0.00 -0.00 0.00 -15.48 0.00
PERIMETER_ZN_3 26-JUN-06:01 0.00 0.00 0.00 -6191.50 0.00 0.00 65.73 210.85 384.60 833.71 0.00 0.00 4712.34 0.00 -0.00 0.00 -15.73 0.00
PERIMETER_ZN_4 05-JUL-06:01 0.00 0.00 0.00 -5984.02 0.00 0.00 38.14 154.74 228.15 0.00 0.00 0.00 5590.42 0.00 -17.51 0.00 -9.92 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-JUL-06:01 0.00 0.00 0.00 -29404.57 0.00 0.00 289.66 1127.24 1732.82 3006.04 0.00 672.93 23223.26 0.00 -26.77 0.00 -620.61 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 11-DEC-07:01 0.00 0.00 7243.44 0.00 0.00 0.00 155.61 365.93 507.34 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8272.32
PERIMETER_ZN_1 06-MAR-07:01 0.00 0.00 8870.56 0.00 0.00 0.00 121.21 241.72 384.60 0.00 0.00 0.00 0.00 0.00 -197.90 0.00 -2697.99 -6722.20
PERIMETER_ZN_2 11-DEC-06:01 0.00 0.00 7322.64 0.00 0.00 0.00 39.82 90.11 228.15 0.00 0.00 0.00 0.00 0.00 -312.64 0.00 -126.93 -7241.15
PERIMETER_ZN_3 11-DEC-06:01 0.00 0.00 9422.05 0.00 0.00 0.00 68.42 151.91 384.60 0.00 0.00 0.00 0.00 0.00 -446.68 0.00 -178.36 -9401.93
PERIMETER_ZN_4 21-FEB-07:01 0.00 0.00 8375.89 0.00 0.00 0.00 71.90 162.69 228.15 0.00 0.00 0.00 0.00 0.00 -254.32 0.00 -15.46 -8568.84
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-DEC-07:01 0.00 0.00 39908.15 0.00 0.00 0.00 541.85 1249.83 1732.82 0.00 0.00 590.03 0.00 0.00 -1759.91 0.00 -2542.26 -39720.51



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3741 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3741 0.1728 1.0000 Not calculated 0.0646 0.1728    
PSZ-AC:2 0.4131 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4131 0.1186 1.0000 Not calculated 0.0490 0.1186    
PSZ-AC:3 0.3361 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3361 0.0865 1.0000 Not calculated 0.0291 0.0865    
PSZ-AC:4 0.4029 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4029 0.1216 1.0000 Not calculated 0.0490 0.1216    
PSZ-AC:5 0.4078 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.4078 0.0713 1.0000 Not calculated 0.0291 0.0713    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3741 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3741 1.0000 1.0000 Not calculated 0.0646 0.1728    
PSZ-AC:2 0.4131 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4131 1.0000 1.0000 Not calculated 0.0490 0.1186    
PSZ-AC:3 0.3361 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3361 1.0000 1.0000 Not calculated 0.0291 0.0865    
PSZ-AC:4 0.4029 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4029 1.0000 1.0000 Not calculated 0.0490 0.1216    
PSZ-AC:5 0.4078 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.4078 1.0000 1.0000 Not calculated 0.0291 0.0713    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3741 0.3741 0.3741 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4131 0.4131 0.4131 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3361 0.3361 0.3361 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4029 0.4029 0.4029 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4078 0.4078 0.4078 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3741 0.3741 0.3741 0.3741 0.0646 1.0000
PSZ-AC:2 0.4131 0.4131 0.4131 0.4131 0.0490 1.0000
PSZ-AC:3 0.3361 0.3361 0.3361 0.3361 0.0291 1.0000
PSZ-AC:4 0.4029 0.4029 0.4029 0.4029 0.0490 1.0000
PSZ-AC:5 0.4078 0.4078 0.4078 0.4078 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3741 0.3741 0.3741 No 0.0646 0.9209 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4131 0.4131 0.4131 No 0.0490 0.2336 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3361 0.3361 0.3361 No 0.0291 0.2151 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4029 0.4029 0.4029 No 0.0490 0.2306 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4078 0.4078 0.4078 No 0.0291 0.2151 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3741 0.3741 0.3741 0.3741 0.0646 1.0000
PSZ-AC:2 0.4131 0.4131 0.4131 0.4131 0.0490 1.0000
PSZ-AC:3 0.3361 0.3361 0.3361 0.3361 0.0291 1.0000
PSZ-AC:4 0.4029 0.4029 0.4029 0.4029 0.0490 1.0000
PSZ-AC:5 0.4078 0.4078 0.4078 0.4078 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 32.50
Number of hours not met 32.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 6.91 9031.36 0.87 16291.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 19.04 7109.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 34.95 2678.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 13.64 1049.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 52.80 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 25.63 2166.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.98 2811.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 52.80 176.95
Natural Gas 0.00 0.87
Additional 0.00 0.00
Total 52.80 177.83


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 68.38
Space Heating 13.51
Space Cooling 37.26
Fans (All) 50.15
Service Water Heating 46.90
Receptacle Equipment 103.29
Miscellaneous (All) 346.18
Subtotal 346.18


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.71
Service Water Heating 0.00
Miscellaneous (All) 1.71
Subtotal 1.71


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 19.66
Space Heating 4.38
Space Cooling 10.71
Fans (All) 14.41
Service Water Heating 13.48
Receptacle Equipment 29.69
Miscellaneous 7.67


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2752. 8760.
BLDG_EQUIP_SCH 4310. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 7770.50 989.50 0.00 0.00 0.00
PERIMETER_ZN_1 8119.17 640.83 0.00 0.00 0.00
PERIMETER_ZN_2 7911.67 848.33 0.00 0.00 0.00
PERIMETER_ZN_3 8268.50 491.50 0.00 0.00 0.00
PERIMETER_ZN_4 7754.00 1006.00 0.00 0.00 0.00
ATTIC 6471.33 628.00 585.67 911.17 163.83
Min 6471.33 491.50 0.00 0.00 0.00
Max 8268.50 1006.00 585.67 911.17 163.83
Average 7715.86 767.36 97.61 151.86 27.31
Sum 46295.17 4604.17 585.67 911.17 163.83


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7776.67 983.33 0.00 0.00 0.00
PERIMETER_ZN_1 8275.17 484.83 0.00 0.00 0.00
PERIMETER_ZN_2 8177.17 582.83 0.00 0.00 0.00
PERIMETER_ZN_3 8382.83 377.17 0.00 0.00 0.00
PERIMETER_ZN_4 8118.50 641.50 0.00 0.00 0.00
ATTIC 6713.33 849.83 327.33 306.50 563.00
Min 6713.33 377.17 0.00 0.00 0.00
Max 8382.83 983.33 327.33 306.50 563.00
Average 7907.28 653.25 54.56 51.08 93.83
Sum 47443.67 3919.50 327.33 306.50 563.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17890.50 1.50 0.00 0.00 0.00
PERIMETER_ZN_1 13354.67 1.33 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13355.17 0.83 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17890.50 1.50 0.00 0.00 0.00
Average 9365.39 0.61 0.00 0.00 0.00
Sum 56192.33 3.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:14

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.469634E+09 1466.83 26-JAN-08:05 -5.3 -8.0 0.242476E+09 402.33 05-JAN-16:49 -5.3 -8.0
February 0.469209E+09 1361.22 01-FEB-08:05 -4.0 -5.8 0.227547E+09 402.33 17-FEB-15:00 12.80 4.68
March 0.622145E+09 1434.06 17-MAR-15:08 14.80 5.88 0.305669E+09 402.34 15-MAR-13:39 14.80 5.88
April 0.112993E+10 5972.24 28-APR-07:01 13.45 5.73 0.281361E+09 436.85 28-APR-07:10 13.45 5.73
May 0.194593E+10 6073.42 12-MAY-07:02 11.28 3.88 0.314168E+09 469.22 22-MAY-07:10 19.60 12.50
June 0.286510E+10 6178.56 19-JUN-06:02 14.68 6.05 0.317687E+09 469.22 29-JUN-07:10 27.57 17.14
July 0.314936E+10 6003.31 24-JUL-05:02 22.20 14.87 0.292394E+09 469.23 24-JUL-07:10 22.88 15.84
August 0.344148E+10 5789.26 07-AUG-05:03 18.90 13.67 0.334897E+09 469.23 21-AUG-07:10 22.38 15.71
September 0.261055E+10 6030.56 27-SEP-07:02 14.18 8.31 0.288651E+09 469.22 15-SEP-07:10 14.18 8.31
October 0.196920E+10 6356.30 12-OCT-07:03 5.92 1.92 0.298493E+09 469.24 02-OCT-07:10 5.92 1.92
November 0.919900E+09 2111.49 02-NOV-15:58 16.70 9.78 0.286557E+09 402.36 02-NOV-14:09 16.70 9.78
December 0.625066E+09 1555.18 15-DEC-08:05 -7.2 -10.4 0.230236E+09 402.33 01-DEC-15:30 -7.2 -10.4
                     
Annual Sum or Average 0.202175E+11         0.342014E+10        
Minimum of Months 0.469209E+09 1361.22   -7.2 -10.4 0.227547E+09 402.33   -7.2 -10.4
Maximum of Months 0.344148E+10 6356.30   22.20 14.87 0.334897E+09 469.24   27.57 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.446703E+09 2446.76 03-JAN-14:35 15.40 6.10 0.192426E+09 304.99 24-JAN-15:30 15.55 4.00
February 0.388471E+09 3271.07 14-FEB-14:55 21.70 7.37 0.174831E+09 304.99 13-FEB-13:09 21.70 7.37
March 0.375294E+09 2165.80 13-MAR-14:30 21.15 7.30 0.217769E+09 305.69 27-MAR-12:39 16.33 6.30
April 0.573043E+09 2715.98 28-APR-14:27 24.70 10.35 0.201067E+09 304.99 27-APR-12:09 24.70 10.35
May 0.886129E+09 2965.46 22-MAY-07:02 19.60 12.50 0.231246E+09 315.94 22-MAY-07:10 19.60 12.50
June 0.211657E+10 6227.06 26-JUN-06:01 19.97 12.34 0.238808E+09 355.69 22-JUN-07:10 19.97 12.34
July 0.277629E+10 6286.93 05-JUL-06:01 22.57 13.90 0.219499E+09 355.70 05-JUL-07:10 24.60 15.17
August 0.320559E+10 6223.74 07-AUG-06:01 19.18 13.44 0.252109E+09 355.70 07-AUG-07:10 20.87 13.47
September 0.287592E+10 6116.97 29-SEP-07:02 17.43 10.42 0.218233E+09 355.69 05-SEP-07:10 17.43 10.42
October 0.251410E+10 6450.33 02-OCT-06:02 16.60 12.55 0.222956E+09 355.70 02-OCT-07:10 16.65 12.53
November 0.122038E+10 4897.39 01-NOV-13:30 12.75 7.49 0.216155E+09 305.00 02-NOV-13:30 15.00 9.03
December 0.488175E+09 2553.53 19-DEC-13:10 7.30 -0.6 0.185881E+09 304.99 26-DEC-15:00 9.40 3.26
                     
Annual Sum or Average 0.178667E+11         0.257098E+10        
Minimum of Months 0.375294E+09 2165.80   7.30 -0.6 0.174831E+09 304.99   9.40 3.26
Maximum of Months 0.320559E+10 6450.33   24.70 13.90 0.252109E+09 355.70   24.70 15.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7402523.41 424.93 26-JAN-08:05 -5.3 -8.0 74420057.08 168.96 05-JAN-16:10 -5.3 -8.0
February 12014701.80 423.38 01-FEB-06:04 -4.2 -5.9 69012602.36 184.04 14-FEB-13:39 20.20 6.86
March 57834726.91 482.90 17-MAR-10:45 15.73 5.64 93622624.25 182.11 23-MAR-15:50 16.02 5.31
April 0.567763E+09 4903.22 28-APR-07:01 13.45 5.73 91302349.57 211.00 28-APR-07:10 13.45 5.73
May 0.104183E+10 4957.02 23-MAY-07:01 19.40 11.63 0.103085E+09 211.00 30-MAY-07:10 16.57 11.58
June 0.199163E+10 5042.46 26-JUN-06:01 19.97 12.34 0.105309E+09 211.01 29-JUN-07:10 27.57 17.14
July 0.230306E+10 5058.77 05-JUL-06:01 22.57 13.90 96582887.13 211.01 24-JUL-07:10 22.88 15.84
August 0.242575E+10 5121.95 20-AUG-08:52 26.10 15.49 0.110726E+09 211.01 21-AUG-07:10 22.38 15.71
September 0.166195E+10 4950.02 19-SEP-07:02 14.78 10.18 95468909.48 211.01 12-SEP-07:10 14.78 10.18
October 0.973041E+09 5054.07 02-OCT-06:02 16.60 12.55 96519659.72 211.01 02-OCT-07:10 16.65 12.53
November 0.157809E+09 1325.47 01-NOV-10:02 12.88 7.66 89859230.44 181.40 09-NOV-08:09 13.07 8.56
December 17295574.18 451.22 21-DEC-07:04 -7.5 -8.5 70068914.40 176.60 01-DEC-16:19 -7.5 -8.5
                     
Annual Sum or Average 0.112174E+11         0.109598E+10        
Minimum of Months 7402523.41 423.38   -7.5 -8.5 69012602.36 168.96   -7.5 -8.5
Maximum of Months 0.242575E+10 5121.95   26.10 15.49 0.110726E+09 211.01   27.57 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 6479703.48 884.51 26-JAN-07:04 -6.1 -8.5 0.167284E+09 258.14 05-JAN-16:19 -6.1 -8.5
February 6503742.07 808.41 09-FEB-06:05 -5.4 -6.3 0.153281E+09 289.19 15-FEB-16:00 16.70 5.85
March 34349476.76 694.50 30-MAR-06:04 -1.7 -2.6 0.197157E+09 303.29 16-MAR-15:50 -1.7 -2.6
April 0.294036E+09 1730.70 28-APR-15:24 25.00 10.42 0.198235E+09 305.23 03-APR-14:00 25.00 10.42
May 0.920028E+09 6029.37 23-MAY-07:01 19.40 11.63 0.233727E+09 343.95 22-MAY-07:10 19.40 11.63
June 0.216653E+10 6191.44 26-JUN-06:01 19.97 12.34 0.239919E+09 355.70 29-JUN-07:10 27.57 17.14
July 0.265451E+10 6185.51 05-JUL-06:01 22.57 13.90 0.219665E+09 355.71 24-JUL-07:10 22.88 15.84
August 0.272138E+10 6144.18 07-AUG-06:01 19.18 13.44 0.251888E+09 355.71 21-AUG-07:10 22.38 15.71
September 0.174263E+10 6012.16 13-SEP-07:02 17.15 11.11 0.217250E+09 355.70 15-SEP-07:10 19.68 12.55
October 0.869610E+09 5813.99 02-OCT-07:02 16.65 12.53 0.215863E+09 355.70 02-OCT-07:10 16.65 12.53
November 0.119870E+09 812.96 02-NOV-15:53 16.70 9.78 0.188560E+09 305.09 08-NOV-14:00 16.70 6.97
December 7650639.59 926.34 15-DEC-06:05 -7.9 -10.9 0.159583E+09 274.05 01-DEC-16:19 -7.9 -10.9
                     
Annual Sum or Average 0.115436E+11         0.244241E+10        
Minimum of Months 6479703.48 694.50   -7.9 -10.9 0.153281E+09 258.14   -7.9 -10.9
Maximum of Months 0.272138E+10 6191.44   25.00 13.90 0.251888E+09 355.71   27.57 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7353655.40 430.43 06-JAN-07:03 -1.7 -3.7 0.104727E+09 180.92 05-JAN-16:10 -1.7 -3.7
February 35091889.24 1364.04 15-FEB-16:42 16.78 5.96 96466272.32 181.00 09-FEB-16:10 16.78 5.96
March 67271682.48 1106.71 08-MAR-16:55 22.20 8.27 0.124789E+09 182.30 31-MAR-14:09 14.50 4.66
April 0.372861E+09 2238.87 13-APR-15:53 25.60 10.08 0.122494E+09 181.27 05-APR-12:39 25.60 10.08
May 0.776706E+09 5846.79 23-MAY-07:01 19.40 11.63 0.140544E+09 211.00 22-MAY-07:10 19.40 11.63
June 0.164511E+10 5940.13 26-JUN-06:01 19.97 12.34 0.143451E+09 211.01 29-JUN-07:10 27.57 17.14
July 0.197824E+10 5983.99 05-JUL-06:01 22.57 13.90 0.131224E+09 211.01 24-JUL-07:10 22.88 15.84
August 0.212224E+10 5953.12 07-AUG-06:01 19.18 13.44 0.150715E+09 211.01 21-AUG-07:10 22.38 15.71
September 0.149122E+10 5789.16 19-SEP-07:02 14.78 10.18 0.130239E+09 211.00 11-SEP-07:10 14.78 10.18
October 0.893277E+09 5977.83 02-OCT-06:02 16.60 12.55 0.131468E+09 211.01 02-OCT-07:10 16.65 12.53
November 0.185602E+09 1867.20 02-NOV-15:55 16.70 9.78 0.121206E+09 181.91 29-NOV-14:39 12.77 3.34
December 12540005.75 413.08 19-DEC-07:03 -0.5 -3.9 99916320.54 181.48 29-DEC-15:50 11.60 3.89
                     
Annual Sum or Average 0.958750E+10         0.149724E+10        
Minimum of Months 7353655.40 413.08   -1.7 -3.9 96466272.32 180.92   -1.7 -3.7
Maximum of Months 0.212224E+10 5983.99   25.60 13.90 0.150715E+09 211.01   27.57 17.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30 -1.2 0.00 0.00 01-JAN-00:10 2.30 -1.2
February 0.00 0.00 01-FEB-00:10 -3.2 -5.2 0.00 0.00 01-FEB-00:10 -3.2 -5.2
March 0.00 0.00 01-MAR-00:10 2.47 -0.8 0.00 0.00 01-MAR-00:10 2.47 -0.8
April 0.00 0.00 01-APR-00:10 7.00 2.84 0.00 0.00 01-APR-00:10 7.00 2.84
May 0.00 0.00 01-MAY-00:10 14.45 4.92 0.00 0.00 01-MAY-00:10 14.45 4.92
June 0.00 0.00 01-JUN-00:10 18.42 8.96 0.00 0.00 01-JUN-00:10 18.42 8.96
July 0.00 0.00 01-JUL-00:10 21.95 14.90 0.00 0.00 01-JUL-00:10 21.95 14.90
August 0.00 0.00 01-AUG-00:10 20.95 16.86 0.00 0.00 01-AUG-00:10 20.95 16.86
September 0.00 0.00 01-SEP-00:10 21.88 14.47 0.00 0.00 01-SEP-00:10 21.88 14.47
October 0.00 0.00 01-OCT-00:10 17.33 10.88 0.00 0.00 01-OCT-00:10 17.33 10.88
November 0.00 0.00 01-NOV-00:10 12.83 5.34 0.00 0.00 01-NOV-00:10 12.83 5.34
December 0.00 0.00 01-DEC-00:10 5.13 1.84 0.00 0.00 01-DEC-00:10 5.13 1.84
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -3.2 -5.2 0.00 0.00   -3.2 -5.2
Maximum of Months 0.00 0.00   21.95 16.86 0.00 0.00   21.95 16.86



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 77439506.66 5724.28 09-JAN-07:01 -2.1
February 44132118.94 7123.25 08-FEB-08:62 2.07
March 6607188.91 7196.21 07-MAR-08:61 4.23
April 12216460.12 478.68 13-APR-17:12 25.73
May 19791934.12 721.36 19-MAY-17:01 29.90
June 46725002.65 1174.79 28-JUN-17:01 37.23
July 44464569.78 1196.50 21-JUL-17:01 37.52
August 45780549.65 920.22 04-AUG-17:01 33.35
September 23337329.53 735.30 20-SEP-17:01 30.13
October 7608810.29 487.98 05-OCT-17:01 26.32
November 882879.21 3506.17 27-NOV-08:62 -3.0
December 41566791.49 7243.51 11-DEC-07:01 1.70
         
Annual Sum or Average 0.370553E+09      
Minimum of Months 882879.21 478.68   -3.0
Maximum of Months 77439506.66 7243.51   37.52



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.727247E+09 8663.21 11-JAN-07:02 1.78
February 0.475096E+09 8850.21 08-FEB-07:01 -0.2
March 0.304849E+09 8870.48 06-MAR-07:01 -0.3
April 96126995.67 6026.52 24-APR-07:02 7.07
May 46470204.15 6454.98 08-MAY-07:01 12.98
June 60700224.67 952.07 28-JUN-17:01 37.23
July 54286872.10 965.90 21-JUL-17:11 37.23
August 53455904.47 744.01 04-AUG-17:01 33.35
September 27586985.96 631.60 20-SEP-17:11 29.67
October 45193890.39 8240.94 26-OCT-06:03 -1.4
November 63043721.31 8345.97 28-NOV-07:01 -1.9
December 0.454106E+09 8819.73 11-DEC-07:01 1.70
         
Annual Sum or Average 0.240816E+10      
Minimum of Months 27586985.96 631.60   -1.9
Maximum of Months 0.727247E+09 8870.48   37.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.581066E+09 6932.47 11-JAN-07:02 1.78
February 0.398638E+09 7002.96 21-FEB-07:01 3.98
March 0.130796E+09 6988.20 23-MAR-06:01 2.30
April 17618913.37 771.83 06-APR-06:03 1.88
May 24847850.74 477.71 19-MAY-17:22 29.70
June 37837881.79 655.35 28-JUN-17:11 36.67
July 37567808.18 666.64 21-JUL-17:11 37.23
August 39214987.29 536.62 18-AUG-17:22 32.50
September 24879194.74 476.55 20-SEP-17:11 29.67
October 16240591.06 2848.37 26-OCT-06:03 -1.4
November 28358377.89 6094.50 28-NOV-07:01 -1.9
December 0.387537E+09 7322.64 11-DEC-06:01 1.70
         
Annual Sum or Average 0.172460E+10      
Minimum of Months 16240591.06 476.55   -1.9
Maximum of Months 0.581066E+09 7322.64   37.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153923E+10 8563.67 09-JAN-06:01 -2.2
February 0.112474E+10 8930.69 13-FEB-06:02 1.05
March 0.452946E+09 8632.19 06-MAR-07:01 -0.3
April 57972947.70 6100.90 10-APR-07:02 8.58
May 28192260.92 1699.22 05-MAY-07:02 6.88
June 46626527.45 955.19 28-JUN-17:01 37.23
July 46903946.58 970.56 21-JUL-17:11 37.23
August 47481891.44 758.67 04-AUG-17:01 33.35
September 27074795.02 654.33 20-SEP-17:01 30.13
October 30319580.23 5634.29 26-OCT-06:03 -1.4
November 0.195198E+09 8512.47 28-NOV-07:01 -1.9
December 0.122870E+10 9422.06 11-DEC-06:01 1.70
         
Annual Sum or Average 0.482538E+10      
Minimum of Months 27074795.02 654.33   -2.2
Maximum of Months 0.153923E+10 9422.06   37.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.646627E+09 8073.45 11-JAN-07:02 1.78
February 0.475392E+09 8375.85 21-FEB-07:01 3.98
March 0.232039E+09 8247.54 23-MAR-06:01 2.30
April 49394325.12 3595.75 24-APR-07:02 7.07
May 43034085.74 513.00 19-MAY-17:22 29.70
June 37901062.22 680.43 28-JUN-17:11 36.67
July 34957316.04 676.55 21-JUL-17:11 37.23
August 37627207.89 589.44 04-AUG-17:22 32.25
September 31238652.53 496.16 20-SEP-17:11 29.67
October 26461028.23 2809.59 26-OCT-07:03 -2.1
November 64730438.06 6751.46 28-NOV-07:01 -1.9
December 0.461186E+09 8210.25 11-DEC-07:01 1.70
         
Annual Sum or Average 0.214059E+10      
Minimum of Months 26461028.23 496.16   -2.1
Maximum of Months 0.646627E+09 8375.85   37.23



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:10 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:10 20.95
September 0.00 0.00 01-SEP-00:10 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.944342E+09 784.13 02-JAN-08:09 0.129836E+10 1014.68 02-JAN-08:09
February 0.853760E+09 784.13 01-FEB-08:09 0.117388E+10 1014.68 01-FEB-08:09
March 0.994276E+09 784.13 01-MAR-08:09 0.137025E+10 1014.68 01-MAR-08:09
April 0.905826E+09 784.13 03-APR-07:10 0.124598E+10 1014.68 03-APR-07:10
May 0.969309E+09 784.13 01-MAY-07:10 0.133431E+10 1014.68 01-MAY-07:10
June 0.955759E+09 784.13 01-JUN-07:10 0.131568E+10 1014.68 01-JUN-07:10
July 0.919376E+09 784.13 03-JUL-07:10 0.126352E+10 1014.68 03-JUL-07:10
August 0.994276E+09 784.13 01-AUG-07:10 0.137025E+10 1014.68 01-AUG-07:10
September 0.905826E+09 784.13 01-SEP-07:10 0.124379E+10 1014.68 01-SEP-07:10
October 0.944342E+09 784.13 02-OCT-07:10 0.129946E+10 1014.68 02-OCT-07:10
November 0.930792E+09 784.13 01-NOV-07:10 0.128083E+10 1014.68 01-NOV-07:10
December 0.919376E+09 784.13 01-DEC-08:09 0.126242E+10 1014.68 01-DEC-08:09
             
Annual Sum or Average 0.112373E+11     0.154587E+11    
Minimum of Months 0.853760E+09 784.13   0.117388E+10 1014.68  
Maximum of Months 0.994276E+09 784.13   0.137025E+10 1014.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.612606E+09 581.45 04-JAN-16:00 0.984244E+09 769.19 02-JAN-08:09
February 0.553016E+09 578.29 16-FEB-08:09 0.889874E+09 769.19 01-FEB-08:09
March 0.637521E+09 569.05 20-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.573443E+09 493.80 06-APR-07:10 0.944536E+09 769.19 03-APR-07:10
May 0.618650E+09 557.36 22-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.626427E+09 561.23 08-JUN-15:00 0.997370E+09 769.19 01-JUN-07:10
July 0.594713E+09 559.62 07-JUL-15:00 0.957827E+09 769.19 03-JUL-07:10
August 0.628568E+09 530.58 03-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.579199E+09 577.66 08-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.604773E+09 575.82 25-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.603618E+09 594.42 13-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.602142E+09 594.42 01-DEC-16:00 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.723468E+10     0.117187E+11    
Minimum of Months 0.553016E+09 493.80   0.889874E+09 769.19  
Maximum of Months 0.637521E+09 594.42   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.380376E+09 347.73 04-JAN-16:00 0.583867E+09 456.29 02-JAN-08:09
February 0.341751E+09 343.41 16-FEB-08:09 0.527885E+09 456.29 01-FEB-08:09
March 0.389121E+09 337.00 20-MAR-07:10 0.616194E+09 456.29 01-MAR-08:09
April 0.347797E+09 317.03 04-APR-15:00 0.560311E+09 456.29 03-APR-07:10
May 0.374246E+09 329.34 22-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.370059E+09 334.35 08-JUN-15:00 0.591653E+09 456.29 01-JUN-07:10
July 0.354518E+09 333.55 07-JUL-15:00 0.568196E+09 456.29 03-JUL-07:10
August 0.379136E+09 312.55 30-AUG-15:00 0.616194E+09 456.29 01-AUG-07:10
September 0.353849E+09 342.96 08-SEP-07:10 0.559325E+09 456.29 01-SEP-07:10
October 0.375057E+09 341.46 25-OCT-07:10 0.584359E+09 456.29 02-OCT-07:10
November 0.374541E+09 352.62 13-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.375783E+09 352.62 01-DEC-16:00 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.441623E+10     0.695170E+10    
Minimum of Months 0.341751E+09 312.55   0.527885E+09 456.29  
Maximum of Months 0.389121E+09 352.62   0.616194E+09 456.29  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.671607E+09 585.14 04-JAN-16:00 0.984244E+09 769.19 02-JAN-08:09
February 0.599749E+09 580.01 16-FEB-08:09 0.889874E+09 769.19 01-FEB-08:09
March 0.676762E+09 572.24 20-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.593467E+09 524.00 13-APR-13:30 0.944536E+09 769.19 03-APR-07:10
May 0.629144E+09 559.01 22-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.626482E+09 563.19 08-JUN-15:00 0.997370E+09 769.19 01-JUN-07:10
July 0.598753E+09 561.76 07-JUL-15:00 0.957827E+09 769.19 03-JUL-07:10
August 0.643564E+09 530.73 03-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.614589E+09 578.92 08-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.664221E+09 578.67 25-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.659836E+09 594.42 13-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.662145E+09 594.42 01-DEC-16:00 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.764032E+10     0.117187E+11    
Minimum of Months 0.593467E+09 524.00   0.889874E+09 769.19  
Maximum of Months 0.676762E+09 594.42   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.379277E+09 344.78 04-JAN-16:00 0.583867E+09 456.29 02-JAN-08:09
February 0.339700E+09 344.06 16-FEB-08:09 0.527885E+09 456.29 01-FEB-08:09
March 0.390900E+09 340.46 20-MAR-07:10 0.616194E+09 456.29 01-MAR-08:09
April 0.349002E+09 323.46 04-APR-07:10 0.560311E+09 456.29 03-APR-07:10
May 0.375272E+09 333.63 22-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.372103E+09 336.47 08-JUN-07:10 0.591653E+09 456.29 01-JUN-07:10
July 0.356663E+09 332.61 07-JUL-15:00 0.568196E+09 456.29 03-JUL-07:10
August 0.383895E+09 328.37 03-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.355540E+09 343.52 08-SEP-07:10 0.559325E+09 456.29 01-SEP-07:10
October 0.376012E+09 343.73 25-OCT-07:10 0.584359E+09 456.29 02-OCT-07:10
November 0.372564E+09 352.62 13-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.373918E+09 352.62 01-DEC-16:00 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.442485E+10     0.695170E+10    
Minimum of Months 0.339700E+09 323.46   0.527885E+09 456.29  
Maximum of Months 0.390900E+09 352.62   0.616194E+09 456.29  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.944342E+09 0.129836E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.905826E+09 0.124598E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.969309E+09 0.133431E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.955759E+09 0.131568E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.919376E+09 0.126352E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.905826E+09 0.124379E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.944342E+09 0.129946E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.930792E+09 0.128083E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.919376E+09 0.126242E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.112373E+11 0.154587E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.612606E+09 0.984244E+09 0.00 0.00 0.00 0.00 0.00 0.111808E+10
February 0.488155E+09 0.553016E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 0.932647E+09
March 0.590925E+09 0.637521E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.00 0.828713E+09
April 0.513848E+09 0.573443E+09 0.944536E+09 0.00 0.00 0.00 0.00 4538529.48 0.507863E+09
May 0.565233E+09 0.618650E+09 0.101149E+10 0.00 0.00 0.00 0.00 32041664.59 0.375208E+09
June 0.565233E+09 0.626427E+09 0.997370E+09 0.00 0.00 0.00 0.00 0.193477E+09 0.188147E+09
July 0.513848E+09 0.594713E+09 0.957827E+09 0.00 0.00 0.00 0.00 0.214827E+09 0.109081E+09
August 0.590925E+09 0.628568E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.161409E+09 0.176217E+09
September 0.513848E+09 0.579199E+09 0.942874E+09 0.00 0.00 0.00 0.00 64278193.94 0.255765E+09
October 0.539540E+09 0.604773E+09 0.985075E+09 0.00 0.00 0.00 0.00 10887819.14 0.589659E+09
November 0.539540E+09 0.603618E+09 0.970953E+09 0.00 0.00 0.00 0.00 0.00 0.917136E+09
December 0.513848E+09 0.602142E+09 0.956997E+09 0.00 0.00 0.00 0.00 0.00 0.113191E+10
                   
Annual Sum or Average 0.647448E+10 0.723468E+10 0.117187E+11 0.00 0.00 0.00 0.00 0.681460E+09 0.713042E+10
Minimum of Months 0.488155E+09 0.553016E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 0.109081E+09
Maximum of Months 0.590925E+09 0.637521E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.214827E+09 0.113191E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.380376E+09 0.583867E+09 0.00 0.00 0.00 0.00 0.00 0.183321E+09
February 0.211974E+09 0.341751E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 0.173181E+09
March 0.256600E+09 0.389121E+09 0.616194E+09 0.00 0.00 0.00 0.00 0.00 0.175042E+09
April 0.223130E+09 0.347797E+09 0.560311E+09 0.00 0.00 0.00 0.00 290010.07 0.132312E+09
May 0.245443E+09 0.374246E+09 0.600030E+09 0.00 0.00 0.00 0.00 1902594.96 0.100610E+09
June 0.245443E+09 0.370059E+09 0.591653E+09 0.00 0.00 0.00 0.00 10386562.74 61116207.61
July 0.223130E+09 0.354518E+09 0.568196E+09 0.00 0.00 0.00 0.00 13773663.05 45214783.03
August 0.256600E+09 0.379136E+09 0.616194E+09 0.00 0.00 0.00 0.00 7053689.66 58218276.26
September 0.223130E+09 0.353849E+09 0.559325E+09 0.00 0.00 0.00 0.00 2332034.75 72995998.38
October 0.234287E+09 0.375057E+09 0.584359E+09 0.00 0.00 0.00 0.00 731723.62 0.118579E+09
November 0.234287E+09 0.374541E+09 0.575982E+09 0.00 0.00 0.00 0.00 0.00 0.167793E+09
December 0.223130E+09 0.375783E+09 0.567703E+09 0.00 0.00 0.00 0.00 0.00 0.170472E+09
                   
Annual Sum or Average 0.281144E+10 0.441623E+10 0.695170E+10 0.00 0.00 0.00 0.00 36470278.84 0.145885E+10
Minimum of Months 0.211974E+09 0.341751E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 45214783.03
Maximum of Months 0.256600E+09 0.389121E+09 0.616194E+09 0.00 0.00 0.00 0.00 13773663.05 0.183321E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.671607E+09 0.984244E+09 0.00 0.00 0.00 0.00 0.00 0.265358E+09
February 0.488155E+09 0.599749E+09 0.889874E+09 0.00 0.00 0.00 0.00 1426.15 0.250242E+09
March 0.590925E+09 0.676762E+09 0.103874E+10 0.00 0.00 0.00 0.00 35175.22 0.243764E+09
April 0.513848E+09 0.593467E+09 0.944536E+09 0.00 0.00 0.00 0.00 696967.21 0.176385E+09
May 0.565233E+09 0.629144E+09 0.101149E+10 0.00 0.00 0.00 0.00 4648943.37 0.137518E+09
June 0.565233E+09 0.626482E+09 0.997370E+09 0.00 0.00 0.00 0.00 17918598.49 85074808.02
July 0.513848E+09 0.598753E+09 0.957827E+09 0.00 0.00 0.00 0.00 22941496.30 59389533.83
August 0.590925E+09 0.643564E+09 0.103874E+10 0.00 0.00 0.00 0.00 11600383.13 78381565.44
September 0.513848E+09 0.614589E+09 0.942874E+09 0.00 0.00 0.00 0.00 3955416.31 99967921.56
October 0.539540E+09 0.664221E+09 0.985075E+09 0.00 0.00 0.00 0.00 1168681.87 0.164004E+09
November 0.539540E+09 0.659836E+09 0.970953E+09 0.00 0.00 0.00 0.00 0.00 0.235232E+09
December 0.513848E+09 0.662145E+09 0.956997E+09 0.00 0.00 0.00 0.00 0.00 0.245908E+09
                   
Annual Sum or Average 0.647448E+10 0.764032E+10 0.117187E+11 0.00 0.00 0.00 0.00 62967088.06 0.204122E+10
Minimum of Months 0.488155E+09 0.593467E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 59389533.83
Maximum of Months 0.590925E+09 0.676762E+09 0.103874E+10 0.00 0.00 0.00 0.00 22941496.30 0.265358E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.379277E+09 0.583867E+09 0.00 0.00 0.00 0.00 0.00 0.185628E+09
February 0.289580E+09 0.339700E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 0.177156E+09
March 0.350544E+09 0.390900E+09 0.616194E+09 0.00 0.00 0.00 0.00 0.00 0.177154E+09
April 0.304821E+09 0.349002E+09 0.560311E+09 0.00 0.00 0.00 0.00 257987.26 0.134131E+09
May 0.335303E+09 0.375272E+09 0.600030E+09 0.00 0.00 0.00 0.00 1733700.00 0.102942E+09
June 0.335303E+09 0.372103E+09 0.591653E+09 0.00 0.00 0.00 0.00 9636657.98 64175306.32
July 0.304821E+09 0.356663E+09 0.568196E+09 0.00 0.00 0.00 0.00 13230431.70 45404846.58
August 0.350544E+09 0.383895E+09 0.616194E+09 0.00 0.00 0.00 0.00 6534233.00 60399319.75
September 0.304821E+09 0.355540E+09 0.559325E+09 0.00 0.00 0.00 0.00 2343695.84 76133289.31
October 0.320062E+09 0.376012E+09 0.584359E+09 0.00 0.00 0.00 0.00 730121.45 0.121676E+09
November 0.320062E+09 0.372564E+09 0.575982E+09 0.00 0.00 0.00 0.00 0.00 0.169584E+09
December 0.304821E+09 0.373918E+09 0.567703E+09 0.00 0.00 0.00 0.00 0.00 0.173606E+09
                   
Annual Sum or Average 0.384075E+10 0.442485E+10 0.695170E+10 0.00 0.00 0.00 0.00 34466827.23 0.148799E+10
Minimum of Months 0.289580E+09 0.339700E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 45404846.58
Maximum of Months 0.350544E+09 0.390900E+09 0.616194E+09 0.00 0.00 0.00 0.00 13230431.70 0.185628E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112227E+10 0.203651E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.906108E+09 0.252017E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.934115E+09 0.321316E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.955136E+09 0.415000E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.905933E+09 0.443246E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.783501E+09 0.429810E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.697224E+09 0.446501E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.631812E+09 0.435294E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.839155E+09 0.352654E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.105792E+10 0.290135E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110627E+10 0.227952E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126925E+10 0.202279E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112087E+11 0.401985E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.631812E+09 0.202279E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.126925E+10 0.446501E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 784.13 02-JAN-08:09 1014.68 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 784.13 01-FEB-08:09 1014.68 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 784.13 01-MAR-08:09 1014.68 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 784.13 03-APR-07:10 1014.68 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 784.13 01-MAY-07:10 1014.68 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 784.13 01-JUN-07:10 1014.68 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 784.13 03-JUL-07:10 1014.68 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 784.13 01-AUG-07:10 1014.68 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 784.13 01-SEP-07:10 1014.68 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 784.13 02-OCT-07:10 1014.68 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 784.13 01-NOV-07:10 1014.68 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 784.13 01-DEC-08:09 1014.68 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 581.45 04-JAN-16:00 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3784.73 30-JAN-07:10
February 732.70 01-FEB-08:09 578.29 16-FEB-08:09 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3685.30 06-FEB-07:10
March 732.70 01-MAR-08:09 569.05 20-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3089.89 30-MAR-06:10
April 732.70 03-APR-07:10 493.80 06-APR-07:10 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 287.69 13-APR-17:00 2520.64 06-APR-06:10
May 732.70 01-MAY-07:10 557.36 22-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 798.95 19-MAY-16:10 1981.21 04-MAY-06:05
June 732.70 01-JUN-07:10 561.23 08-JUN-15:00 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 1825.06 28-JUN-16:03 1732.30 09-JUN-06:03
July 732.70 03-JUL-07:10 559.62 07-JUL-15:00 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 1696.01 21-JUL-16:53 958.18 17-JUL-06:01
August 732.70 01-AUG-07:10 530.58 03-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 1373.15 01-AUG-16:10 1470.87 31-AUG-06:05
September 732.70 01-SEP-07:10 577.66 08-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 862.70 20-SEP-17:00 1762.91 20-SEP-06:03
October 732.70 02-OCT-07:10 575.82 25-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 481.29 06-OCT-16:10 3258.81 27-OCT-07:00
November 732.70 01-NOV-07:10 594.42 13-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3477.80 27-NOV-07:10
December 732.70 01-DEC-08:09 594.42 01-DEC-16:00 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4091.18 15-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   493.80   769.19   0.00 0.00 0.00 0.00 0.00   958.18  
Maximum of Months 732.70   594.42   769.19   0.00 0.00 0.00 0.00 1825.06   4091.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 347.73 04-JAN-16:00 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 426.21 16-JAN-17:53
February 434.65 01-FEB-08:09 343.41 16-FEB-08:09 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 342.49 05-FEB-01:20
March 434.65 01-MAR-08:09 337.00 20-MAR-07:10 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 317.64 14-MAR-18:55
April 434.65 03-APR-07:10 317.03 04-APR-15:00 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 9.11 01-APR-17:10 364.84 07-APR-21:55
May 434.65 01-MAY-07:10 329.34 22-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 30.04 19-MAY-18:10 238.79 18-MAY-03:20
June 434.65 01-JUN-07:10 334.35 08-JUN-15:00 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 72.82 28-JUN-18:10 190.68 04-JUN-16:51
July 434.65 03-JUL-07:10 333.55 07-JUL-15:00 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 99.55 04-JUL-14:53 143.77 15-JUL-18:53
August 434.65 01-AUG-07:10 312.55 30-AUG-15:00 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 48.40 20-AUG-16:53 133.04 08-AUG-01:00
September 434.65 01-SEP-07:10 342.96 08-SEP-07:10 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 20.50 03-SEP-14:10 173.78 17-SEP-19:55
October 434.65 02-OCT-07:10 341.46 25-OCT-07:10 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 20.00 11-OCT-13:00 243.53 11-OCT-23:00
November 434.65 01-NOV-07:10 352.62 13-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 395.14 03-NOV-21:00
December 434.65 01-DEC-08:09 352.62 01-DEC-16:00 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 502.24 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   312.55   456.29   0.00 0.00 0.00 0.00 0.00   133.04  
Maximum of Months 434.65   352.62   456.29   0.00 0.00 0.00 0.00 99.55   502.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 585.14 04-JAN-16:00 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 653.70 16-JAN-17:53
February 732.70 01-FEB-08:09 580.01 16-FEB-08:09 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 1.04 12-FEB-14:55 514.81 05-FEB-01:00
March 732.70 01-MAR-08:09 572.24 20-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 11.96 12-MAR-16:52 443.32 14-MAR-18:55
April 732.70 03-APR-07:10 524.00 13-APR-13:30 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 45.56 01-APR-17:02 521.48 07-APR-21:55
May 732.70 01-MAY-07:10 559.01 22-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 56.91 14-MAY-16:52 351.01 18-MAY-03:30
June 732.70 01-JUN-07:10 563.19 08-JUN-15:00 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 113.82 28-JUN-18:10 265.65 10-JUN-01:40
July 732.70 03-JUL-07:10 561.76 07-JUL-15:00 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 155.86 04-JUL-14:53 194.06 15-JUL-18:53
August 732.70 01-AUG-07:10 530.73 03-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 78.88 04-AUG-18:10 189.41 08-AUG-01:00
September 732.70 01-SEP-07:10 578.92 08-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 40.13 03-SEP-14:12 230.77 18-SEP-01:00
October 732.70 02-OCT-07:10 578.67 25-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 30.01 11-OCT-13:00 354.77 11-OCT-23:00
November 732.70 01-NOV-07:10 594.42 13-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 573.90 03-NOV-21:00
December 732.70 01-DEC-08:09 594.42 01-DEC-16:00 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 740.22 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   524.00   769.19   0.00 0.00 0.00 0.00 0.00   189.41  
Maximum of Months 732.70   594.42   769.19   0.00 0.00 0.00 0.00 155.86   740.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 344.78 04-JAN-16:00 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 433.51 16-JAN-17:53
February 434.65 01-FEB-08:09 344.06 16-FEB-08:09 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 340.08 05-FEB-01:00
March 434.65 01-MAR-08:09 340.46 20-MAR-07:10 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 315.87 14-MAR-18:55
April 434.65 03-APR-07:10 323.46 04-APR-07:10 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 7.85 26-APR-15:00 381.30 07-APR-21:55
May 434.65 01-MAY-07:10 333.63 22-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 23.83 19-MAY-15:00 257.20 18-MAY-02:00
June 434.65 01-JUN-07:10 336.47 08-JUN-07:10 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 56.12 28-JUN-18:02 192.18 10-JUN-01:00
July 434.65 03-JUL-07:10 332.61 07-JUL-15:00 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 97.41 04-JUL-15:07 142.12 15-JUL-18:53
August 434.65 01-AUG-07:10 328.37 03-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 46.88 20-AUG-16:55 141.87 25-AUG-19:53
September 434.65 01-SEP-07:10 343.52 08-SEP-07:10 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 21.44 03-SEP-14:07 184.35 17-SEP-19:55
October 434.65 02-OCT-07:10 343.73 25-OCT-07:10 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 20.00 11-OCT-13:00 250.53 11-OCT-23:00
November 434.65 01-NOV-07:10 352.62 13-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 414.23 03-NOV-21:00
December 434.65 01-DEC-08:09 352.62 01-DEC-16:00 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 513.39 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   323.46   456.29   0.00 0.00 0.00 0.00 0.00   141.87  
Maximum of Months 434.65   352.62   456.29   0.00 0.00 0.00 0.00 97.41   513.39  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1743.52 11-JAN-00:03 3988.87 27-JAN-12:40
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1493.14 14-FEB-07:23 5028.58 04-FEB-13:30
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1351.11 08-MAR-05:00 5602.15 06-MAR-13:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1538.70 01-APR-04:00 6969.67 08-APR-13:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1660.40 09-MAY-03:55 6557.19 28-MAY-13:30
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1560.61 20-JUN-02:00 6098.29 03-JUN-13:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1287.28 14-JUL-05:53 5929.62 28-JUL-13:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1105.29 31-AUG-06:42 5832.79 03-AUG-13:20
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1361.16 27-SEP-23:00 5576.01 13-SEP-12:50
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1546.13 29-OCT-22:00 5873.57 26-OCT-13:30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1544.17 12-NOV-23:00 4675.06 12-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1591.69 13-DEC-02:00 4437.17 22-DEC-13:20
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1105.29   3988.87  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1743.52   6969.67  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1466.83 26-JAN-08:05 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
February 1361.22 01-FEB-08:05 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
March 1434.06 17-MAR-15:08 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
April 5972.24 28-APR-07:01 6765.77 5488.90 7102.74 0.00 0.00 0.00 0.00 0.00 0.00
May 6073.42 12-MAY-07:02 5799.23 4704.77 6088.06 0.00 0.00 0.00 0.00 0.00 0.00
June 6178.56 19-JUN-06:02 1217.84 2195.56 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
July 6003.31 24-JUL-05:02 531.60 1001.93 2536.69 0.00 0.00 0.00 0.00 0.00 0.00
August 5789.26 07-AUG-05:03 425.28 801.55 2029.35 0.00 0.00 0.00 0.00 0.00 0.00
September 6030.56 27-SEP-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
October 6356.30 12-OCT-07:03 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
November 2111.49 02-NOV-15:58 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
December 1555.18 15-DEC-08:05 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1361.22   425.28 801.55 2029.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6356.30   6765.77 5488.90 7102.74 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2446.76 03-JAN-14:35 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 0.00 174.28
February 3271.07 14-FEB-14:55 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 0.00 44.17
March 2165.80 13-MAR-14:30 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 0.00 58.00
April 2715.98 28-APR-14:27 2198.10 1355.46 2307.57 0.00 0.00 0.00 0.00 18.29 0.00
May 2965.46 22-MAY-07:02 3663.49 2786.81 3845.96 0.00 0.00 0.00 0.00 0.00 88.73
June 6227.06 26-JUN-06:01 1077.07 1734.44 2692.17 0.00 0.00 0.00 0.00 0.00 804.89
July 6286.93 05-JUL-06:01 1077.07 1782.55 2692.17 0.00 0.00 0.00 0.00 0.00 583.51
August 6223.74 07-AUG-06:01 1077.07 1794.09 2692.17 0.00 0.00 0.00 0.00 0.00 1027.05
September 6116.97 29-SEP-07:02 3663.49 2259.09 3845.96 0.00 0.00 0.00 0.00 0.00 135.93
October 6450.33 02-OCT-06:02 923.20 1650.71 2307.57 0.00 0.00 0.00 0.00 0.00 1354.18
November 4897.39 01-NOV-13:30 732.70 451.82 769.19 0.00 0.00 0.00 0.00 0.00 295.12
December 2553.53 19-DEC-13:10 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 0.00 362.68
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2165.80   732.70 451.82 769.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6450.33   3663.49 2786.81 3845.96 0.00 0.00 0.00 0.00 18.29 1354.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 424.93 26-JAN-08:05 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 18.75
February 423.38 01-FEB-06:04 239.06 450.56 1140.74 0.00 0.00 0.00 0.00 0.00 73.66
March 482.90 17-MAR-10:45 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 21.77
April 4903.22 28-APR-07:01 3042.52 1876.17 3194.06 0.00 0.00 0.00 0.00 0.00 0.00
May 4957.02 23-MAY-07:01 3477.17 2144.20 3650.35 0.00 0.00 0.00 0.00 0.00 26.78
June 5042.46 26-JUN-06:01 638.93 875.55 1597.03 0.00 0.00 0.00 0.00 0.00 10.60
July 5058.77 05-JUL-06:01 638.93 875.55 1597.03 0.00 0.00 0.00 0.00 0.00 10.67
August 5121.95 20-AUG-08:52 0.00 321.63 547.55 0.00 0.00 0.00 0.00 0.00 15.48
September 4950.02 19-SEP-07:02 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 9.05
October 5054.07 02-OCT-06:02 547.65 979.00 1368.88 0.00 0.00 0.00 0.00 0.00 11.91
November 1325.47 01-NOV-10:02 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 37.12
December 451.22 21-DEC-07:04 638.93 1151.88 1597.03 0.00 0.00 0.00 0.00 0.00 3.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 423.38   0.00 321.63 547.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5121.95   3477.17 2144.20 3650.35 0.00 0.00 0.00 0.00 0.00 73.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 884.51 26-JAN-07:04 1077.07 1941.77 2692.17 0.00 0.00 0.00 0.00 0.00 27.93
February 808.41 09-FEB-06:05 322.39 607.62 1538.38 0.00 0.00 0.00 0.00 0.00 107.63
March 694.50 30-MAR-06:04 1077.07 1930.91 2692.17 0.00 0.00 0.00 0.00 0.00 51.32
April 1730.70 28-APR-15:24 3663.49 2259.09 3845.95 0.00 0.00 0.00 0.00 5.47 0.00
May 6029.37 23-MAY-07:01 5861.59 3614.55 6153.53 0.00 0.00 0.00 0.00 0.00 35.67
June 6191.44 26-JUN-06:01 1077.07 1475.94 2692.17 0.00 0.00 0.00 0.00 0.00 15.73
July 6185.51 05-JUL-06:01 1077.07 1587.96 2692.17 0.00 0.00 0.00 0.00 0.00 16.52
August 6144.18 07-AUG-06:01 1077.07 1475.94 2692.17 0.00 0.00 0.00 0.00 0.00 20.23
September 6012.16 13-SEP-07:02 3663.49 2698.99 3845.95 0.00 0.00 0.00 0.00 0.00 2.10
October 5813.99 02-OCT-07:02 3663.49 2705.80 3845.95 0.00 0.00 0.00 0.00 0.00 6.73
November 812.96 02-NOV-15:53 2930.79 2237.42 3076.76 0.00 0.00 0.00 0.00 0.00 21.80
December 926.34 15-DEC-06:05 322.39 607.62 1538.38 0.00 0.00 0.00 0.00 0.00 119.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 694.50   322.39 607.62 1538.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6191.44   5861.59 3614.55 6153.53 0.00 0.00 0.00 0.00 5.47 119.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 430.43 06-JAN-07:03 547.65 987.33 1368.88 0.00 0.00 0.00 0.00 0.00 42.17
February 1364.04 15-FEB-16:42 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 12.23
March 1106.71 08-MAR-16:55 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 5.55
April 2238.87 13-APR-15:53 1303.94 804.07 1368.88 0.00 0.00 0.00 0.00 3.80 0.00
May 5846.79 23-MAY-07:01 3477.17 2500.47 3650.35 0.00 0.00 0.00 0.00 0.00 22.94
June 5940.13 26-JUN-06:01 638.93 1066.12 1597.03 0.00 0.00 0.00 0.00 0.00 10.11
July 5983.99 05-JUL-06:01 638.93 1083.16 1597.03 0.00 0.00 0.00 0.00 0.00 9.92
August 5953.12 07-AUG-06:01 638.93 1094.49 1597.03 0.00 0.00 0.00 0.00 0.00 12.69
September 5789.16 19-SEP-07:02 2173.23 1650.25 2281.47 0.00 0.00 0.00 0.00 0.00 8.68
October 5977.83 02-OCT-06:02 547.65 984.45 1368.88 0.00 0.00 0.00 0.00 0.00 11.71
November 1867.20 02-NOV-15:55 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 14.53
December 413.08 19-DEC-07:03 547.65 987.33 1368.88 0.00 0.00 0.00 0.00 0.00 35.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 413.08   547.65 804.07 1368.88 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5983.99   3477.17 2500.47 3650.35 0.00 0.00 0.00 0.00 3.80 42.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 593.18 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 414.07 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 967.45 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1184.07 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 966.16 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 863.93 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474.60 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.94 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 526.81 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 313.53 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 918.74 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 772.30 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 313.53 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1184.07 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.155133E+11 19461.25 18-JAN-08:20 0.348877E+09 13472.73 17-JAN-07:10
February 0.133582E+11 17739.52 06-FEB-08:39 0.216951E+09 16291.78 06-FEB-07:10
March 0.141282E+11 15292.08 06-MAR-08:09 40326325.16 6625.53 06-MAR-07:10
April 0.128518E+11 13553.96 28-APR-15:09 528131.54 358.72 06-APR-07:10
May 0.142656E+11 14739.15 19-MAY-15:50 0.00 0.00 01-MAY-00:10
June 0.158030E+11 17866.34 28-JUN-15:00 0.00 0.00 01-JUN-00:10
July 0.160666E+11 17546.09 21-JUL-15:20 0.00 0.00 01-JUL-00:10
August 0.172118E+11 17330.57 21-AUG-15:30 0.00 0.00 01-AUG-00:10
September 0.149464E+11 15962.61 05-SEP-14:30 0.00 0.00 01-SEP-00:10
October 0.145852E+11 15910.72 02-OCT-14:00 3491286.25 2588.65 26-OCT-06:10
November 0.135330E+11 14525.28 27-NOV-08:09 16301033.27 4223.10 27-NOV-07:10
December 0.146896E+11 17574.96 26-DEC-08:39 0.247912E+09 10546.01 26-DEC-07:10
             
Annual Sum or Average 0.176953E+12     0.874386E+09    
Minimum of Months 0.128518E+11 13553.96   0.00 0.00  
Maximum of Months 0.172118E+11 19461.25   0.348877E+09 16291.78  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.298821E+10 0.140088E+10 0.443459E+10 0.00 0.215078E+10 0.02 0.238228E+10 65114952.10 0.00 0.00 0.00 0.209142E+10 0.00
February 0.268798E+10 0.118070E+10 0.400939E+10 0.00 0.194725E+10 0.00 0.155840E+10 80892413.45 0.00 0.00 0.00 0.189359E+10 0.00
March 0.308858E+10 0.118498E+10 0.468012E+10 0.00 0.233191E+10 0.00 0.542706E+09 0.174792E+09 0.00 0.00 0.00 0.212514E+10 0.00
April 0.276953E+10 0.102157E+10 0.425568E+10 0.00 0.202762E+10 0.00 70360859.54 0.727884E+09 0.00 0.00 0.00 0.197918E+10 0.00
May 0.296662E+10 0.949794E+09 0.455735E+10 0.00 0.223054E+10 0.00 3803953.61 0.151732E+10 0.00 0.00 0.00 0.204019E+10 0.00
June 0.295083E+10 0.868191E+09 0.449372E+10 0.00 0.223644E+10 0.00 0.00 0.329937E+10 0.00 0.00 0.00 0.195449E+10 0.00
July 0.282402E+10 0.919971E+09 0.431556E+10 0.00 0.204224E+10 0.00 0.00 0.401757E+10 0.00 0.00 0.00 0.194723E+10 0.00
August 0.302944E+10 0.100747E+10 0.468012E+10 0.00 0.234192E+10 0.00 0.00 0.415512E+10 0.00 0.00 0.00 0.199774E+10 0.00
September 0.280900E+10 0.109396E+10 0.424819E+10 0.00 0.203215E+10 0.00 0.00 0.285713E+10 0.00 0.00 0.00 0.190593E+10 0.00
October 0.296441E+10 0.125737E+10 0.443833E+10 0.00 0.213179E+10 0.00 0.101643E+09 0.168726E+10 0.00 0.00 0.00 0.200443E+10 0.00
November 0.294135E+10 0.132623E+10 0.437470E+10 0.00 0.212900E+10 0.00 0.364155E+09 0.411464E+09 0.00 0.00 0.00 0.198611E+10 0.00
December 0.293336E+10 0.143110E+10 0.431182E+10 0.00 0.203090E+10 0.00 0.188249E+10 50227941.11 0.00 0.00 0.00 0.204971E+10 0.00
                           
Annual Sum or Average 0.349533E+11 0.136422E+11 0.527996E+11 0.00 0.256325E+11 0.02 0.690584E+10 0.190441E+11 0.00 0.00 0.00 0.239752E+11 0.00
Minimum of Months 0.268798E+10 0.868191E+09 0.400939E+10 0.00 0.194725E+10 0.00 0.00 50227941.11 0.00 0.00 0.00 0.189359E+10 0.00
Maximum of Months 0.308858E+10 0.143110E+10 0.468012E+10 0.00 0.234192E+10 0.02 0.238228E+10 0.415512E+10 0.00 0.00 0.00 0.212514E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.348877E+09 0.00 0.00 0.00 0.00
February 0.00 0.00 0.216951E+09 0.00 0.00 0.00 0.00
March 0.00 0.00 40326325.16 0.00 0.00 0.00 0.00
April 0.00 0.00 528131.54 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 3491286.25 0.00 0.00 0.00 0.00
November 0.00 0.00 16301033.27 0.00 0.00 0.00 0.00
December 0.00 0.00 0.247912E+09 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.874386E+09 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.348877E+09 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2643.22 04-JAN-16:00 1049.11 01-JAN-06:10 3465.65 02-JAN-08:09 0.00 2166.26 02-JAN-06:10 0.00 06-JAN-11:30 9031.36 18-JAN-07:30
February 2629.89 16-FEB-08:09 1049.11 01-FEB-06:10 3465.65 01-FEB-08:09 0.00 2166.26 01-FEB-06:10 0.00 03-FEB-09:39 7887.98 06-FEB-07:30
March 2602.88 20-MAR-07:10 1049.11 01-MAR-06:10 3465.65 01-MAR-08:09 0.00 2166.26 01-MAR-06:10 0.00 01-MAR-00:10 6817.08 06-MAR-07:19
April 2378.93 06-APR-07:10 1049.11 01-APR-05:10 3465.65 03-APR-07:10 0.00 2166.26 03-APR-05:10 0.00 01-APR-00:10 1940.82 06-APR-06:10
May 2563.46 22-MAY-07:10 1049.11 01-MAY-05:10 3465.65 01-MAY-07:10 0.00 2166.26 01-MAY-05:10 0.00 01-MAY-00:10 552.10 05-MAY-06:10
June 2576.47 08-JUN-15:00 1049.11 01-JUN-19:10 3465.65 01-JUN-07:10 0.00 2166.26 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2571.67 07-JUL-15:00 1049.11 01-JUL-19:19 3465.65 03-JUL-07:10 0.00 2166.26 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2441.84 03-AUG-07:10 1049.11 01-AUG-05:10 3465.65 01-AUG-07:10 0.00 2166.26 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2627.18 08-SEP-07:10 1049.11 01-SEP-05:10 3465.65 01-SEP-07:10 0.00 2166.26 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2623.81 25-OCT-07:10 1049.11 01-OCT-05:10 3465.65 02-OCT-07:10 0.00 2166.26 02-OCT-05:10 0.00 01-OCT-00:10 3684.06 26-OCT-06:30
November 2678.20 13-NOV-16:00 1049.11 01-NOV-05:10 3465.65 01-NOV-07:10 0.00 2166.26 01-NOV-05:10 0.00 01-NOV-00:10 4992.40 27-NOV-07:30
December 2678.20 01-DEC-16:00 1049.11 01-DEC-06:10 3465.65 01-DEC-08:09 0.00 2166.26 01-DEC-06:10 0.00 01-DEC-00:10 9012.42 26-DEC-07:30
                           
Annual Sum or Average             0.00            
Minimum of Months 2378.93   1049.11   3465.65   0.00 2166.26   0.00   0.00  
Maximum of Months 2678.20   1049.11   3465.65   0.00 2166.26   0.00   9031.36  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 603.30 05-JAN-15:00 0.00 0.00 0.00 2811.34 31-JAN-12:20 0.00
February 1398.44 14-FEB-15:00 0.00 0.00 0.00 2811.41 06-FEB-12:50 0.00
March 1274.22 08-MAR-16:30 0.00 0.00 0.00 2809.68 01-MAR-12:39 0.00
April 2928.26 28-APR-14:00 0.00 0.00 0.00 2802.05 03-APR-11:50 0.00
May 4084.91 19-MAY-15:00 0.00 0.00 0.00 2792.56 01-MAY-11:50 0.00
June 7109.38 28-JUN-15:00 0.00 0.00 0.00 2781.24 01-JUN-11:09 0.00
July 6789.58 24-JUL-15:50 0.00 0.00 0.00 2772.19 05-JUL-11:30 0.00
August 6676.47 21-AUG-15:00 0.00 0.00 0.00 2770.47 31-AUG-11:09 0.00
September 5369.97 05-SEP-14:30 0.00 0.00 0.00 2776.66 29-SEP-11:30 0.00
October 5239.22 02-OCT-14:00 0.00 0.00 0.00 2787.15 31-OCT-11:50 0.00
November 2232.01 02-NOV-15:00 0.00 0.00 0.00 2797.59 29-NOV-12:30 0.00
December 553.43 01-DEC-15:50 0.00 0.00 0.00 2806.52 29-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 553.43   0.00 0.00 0.00 2770.47   0.00
Maximum of Months 7109.38   0.00 0.00 0.00 2811.41   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 19461.25 18-JAN-08:20 2381.46 3465.65 0.00 0.00 2166.26 0.00 8710.13 0.00 0.00
February 17739.52 06-FEB-08:39 2350.89 3465.65 0.00 0.00 2166.26 0.00 7018.39 0.00 0.00
March 15292.08 06-MAR-08:09 2354.82 3465.65 0.00 0.00 2166.26 0.00 4568.62 0.00 0.00
April 13553.96 28-APR-15:09 2241.78 3465.65 0.00 0.00 2166.26 0.00 0.00 2926.03 0.00
May 14739.15 19-MAY-15:50 2289.20 3465.65 0.00 0.00 2166.26 0.00 0.00 4069.12 0.00
June 17866.34 28-JUN-15:00 2384.95 3465.65 0.00 0.00 2166.26 0.00 0.00 7109.38 0.00
July 17546.09 21-JUL-15:20 2398.66 3465.65 0.00 0.00 2166.26 0.00 0.00 6778.04 0.00
August 17330.57 21-AUG-15:30 2305.33 3465.65 0.00 0.00 2166.26 0.00 0.00 6656.22 0.00
September 15962.61 05-SEP-14:30 2243.72 3465.65 0.00 0.00 2166.26 0.00 0.00 5369.97 0.00
October 15910.72 02-OCT-14:00 2319.09 3465.65 0.00 0.00 2166.26 0.00 0.00 5239.22 0.00
November 14525.28 27-NOV-08:09 2368.46 3465.65 0.00 0.00 2166.26 0.00 3794.41 0.00 0.00
December 17574.96 26-DEC-08:39 2376.58 3465.65 0.00 0.00 2166.26 0.00 6831.35 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 13553.96   2241.78 3465.65 0.00 0.00 2166.26 0.00 0.00 0.00 0.00
Maximum of Months 19461.25   2398.66 3465.65 0.00 0.00 2166.26 0.00 8710.13 7109.38 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 13472.73 17-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 16291.78 06-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 6625.53 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 358.72 06-APR-07:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 2588.65 26-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 4223.10 27-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 10546.01 26-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 16291.78   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 24.60 0.50 24.60
July 0.00 0.00 0.00 0.00 13.33 24.71 13.33 24.71
August 0.00 0.00 0.00 0.00 12.50 24.68 12.50 24.68
September 0.00 0.00 0.00 0.00 1.17 24.69 1.17 24.69
October 0.00 0.00 0.00 0.00 0.17 24.54 0.17 24.54
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   27.67 24.69 27.67 24.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.33 24.71 13.33 24.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 19.31 0.17 19.31 0.00 19.31 0.00 19.31
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.83 30.15 0.00 30.15
October 0.00 0.00 0.00 0.00 5.50 26.08 4.17 25.50
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.31 0.17 19.31 6.33 26.25 4.17 25.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.31 0.17 19.31 5.50 30.15 4.17 30.15



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 14.97 0.00 14.97 0.00 14.97 0.00 14.97
February 2.17 14.87 0.00 14.87 0.00 14.87 0.00 14.87
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 30.01 0.00 30.01
July 0.00 0.00 0.00 0.00 3.67 30.20 0.00 30.20
August 0.00 0.00 0.00 0.00 4.33 30.10 0.00 30.10
September 0.00 0.00 0.00 0.00 0.50 30.06 0.00 30.06
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 14.98 0.00 14.98 0.00 14.98 0.00 14.98
                 
Annual Sum or Average 3.50 14.91 0.00 14.91 8.83 25.81 0.00 25.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 14.98 0.00 14.98 4.33 30.20 0.00 30.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 14.95 0.00 14.95 0.00 14.95 0.00 14.95
February 4.50 14.84 0.00 14.84 0.00 14.84 0.00 14.84
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 14.98 0.00 14.98 0.00 14.98 0.00 14.98
                 
Annual Sum or Average 10.50 14.91 0.00 14.91 0.00 14.91 0.00 14.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.83 14.98 0.00 14.98 0.00 14.98 0.00 14.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 14.99 0.00 14.99 0.00 14.99 0.00 14.99
February 1.83 14.86 0.00 14.86 0.00 14.86 0.00 14.86
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 3.17 30.31 0.17 30.30
July 0.00 0.00 0.00 0.00 5.50 30.35 0.50 30.34
August 0.00 0.00 0.00 0.00 3.33 30.38 0.00 30.38
September 0.00 0.00 0.00 0.00 1.00 30.23 0.00 30.23
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.50 14.89 0.00 14.89 13.00 27.85 0.67 27.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.83 14.99 0.00 14.99 5.50 30.38 0.50 30.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 21.47 105.50 21.22 105.50 21.06
February 323.00 21.85 60.00 21.61 60.00 21.43
March 391.00 23.00 7.67 22.95 7.67 22.90
April 229.00 23.73 23.33 23.88 0.00 23.88
May 72.17 23.98 167.00 24.70 2.50 24.70
June 9.17 27.38 351.83 25.03 9.17 25.09
July 40.33 27.46 340.00 25.43 40.33 25.63
August 31.33 27.38 391.00 25.27 31.33 25.42
September 3.67 27.21 336.50 24.91 3.67 24.93
October 95.50 23.68 150.17 24.48 1.00 24.49
November 328.33 23.29 7.00 23.28 3.17 23.26
December 340.00 21.49 79.67 21.29 79.67 21.14
             
Annual Sum or Average 2220.50 22.70 2019.67 23.53 344.00 23.43
Minimum of Months 3.67 21.47 7.00 21.22 0.00 21.06
Maximum of Months 391.00 27.46 391.00 25.43 105.50 25.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 352.83 21.54 160.67 21.11 160.67 20.89
February 312.83 21.58 133.00 21.15 133.00 20.92
March 391.00 22.12 111.00 21.71 111.00 21.45
April 312.33 22.93 43.00 22.64 42.83 22.40
May 261.17 23.40 19.33 23.41 7.83 23.33
June 49.50 23.84 182.50 25.10 2.33 25.13
July 31.17 27.53 339.00 25.32 31.17 25.49
August 32.67 27.66 389.67 25.26 32.67 25.43
September 7.50 25.56 301.50 25.00 3.83 25.02
October 122.33 23.24 189.50 24.17 23.17 24.14
November 270.00 22.93 44.50 22.75 28.33 22.54
December 338.33 21.70 136.83 21.29 136.83 21.07
             
Annual Sum or Average 2481.67 22.48 2050.50 22.99 713.67 22.73
Minimum of Months 7.50 21.54 19.33 21.11 2.33 20.89
Maximum of Months 391.00 27.66 389.67 25.32 160.67 25.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.27 255.50 20.14 255.50 20.09
February 266.00 20.52 212.67 20.29 212.67 20.20
March 322.00 21.72 126.83 21.25 126.83 20.99
April 238.67 23.27 21.17 23.11 17.83 22.94
May 130.83 23.66 63.83 24.18 0.83 24.17
June 30.83 26.48 239.83 25.59 20.00 25.76
July 74.17 27.82 280.00 26.02 74.17 26.33
August 54.50 27.83 322.00 25.75 54.50 26.01
September 1.33 26.98 262.67 25.06 1.00 25.07
October 144.83 23.11 106.83 23.64 14.50 23.46
November 291.67 22.29 64.83 21.92 64.83 21.67
December 280.00 20.26 263.50 20.20 263.50 20.18
             
Annual Sum or Average 2128.83 22.09 2219.67 22.59 1106.17 22.29
Minimum of Months 1.33 20.26 21.17 20.14 0.83 20.09
Maximum of Months 322.00 27.83 322.00 26.02 263.50 26.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.21 352.83 20.20 352.83 20.20
February 323.00 20.35 300.00 20.28 300.00 20.26
March 391.00 21.08 245.67 20.80 245.67 20.68
April 334.67 22.80 59.17 22.48 59.17 22.24
May 244.33 23.56 28.33 23.71 4.17 23.67
June 33.83 24.74 225.33 25.29 8.33 25.37
July 43.50 27.75 340.00 25.44 43.50 25.68
August 23.17 27.68 388.33 25.15 23.17 25.29
September 12.00 24.22 240.33 24.82 0.83 24.83
October 242.00 22.95 102.00 23.12 30.67 22.91
November 357.00 21.54 167.83 21.19 167.83 21.01
December 340.00 20.26 331.83 20.24 331.83 20.23
             
Annual Sum or Average 2701.50 21.67 2781.67 22.09 1568.00 21.77
Minimum of Months 12.00 20.21 28.33 20.20 0.83 20.20
Maximum of Months 391.00 27.75 388.33 25.44 352.83 25.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.74 278.67 20.51 278.67 20.42
February 323.00 21.02 220.50 20.71 220.50 20.57
March 386.67 21.88 149.50 21.46 149.50 21.23
April 261.17 23.21 53.17 23.31 25.33 23.13
May 184.33 23.98 86.67 24.73 13.17 24.85
June 91.83 27.61 270.83 26.20 70.33 26.62
July 92.00 28.59 340.00 26.16 92.00 26.59
August 97.83 28.50 389.67 26.06 97.83 26.47
September 40.33 28.16 295.50 25.63 39.67 25.91
October 179.67 23.46 148.67 24.07 27.33 24.02
November 343.17 22.45 77.83 22.13 74.67 21.89
December 340.00 20.80 261.00 20.57 261.00 20.48
             
Annual Sum or Average 2697.00 22.70 2572.00 23.06 1350.00 22.90
Minimum of Months 40.33 20.74 53.17 20.51 13.17 20.42
Maximum of Months 386.67 28.59 389.67 26.20 278.67 26.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 766653.53 175798.67 1.72 744792.85 21860.69 0.00 0.03 05-JAN-16:05 0.00 01-JAN-00:05 165.69 05-JAN-16:05 161.64 05-JAN-15:58 4.70 05-JAN-16:40 37.96 05-JAN-16:05 0.00
February 38210281.46 8594202.55 18.30 38046378.58 163902.88 0.00 0.24 15-FEB-16:54 0.00 01-FEB-00:10 1233.14 15-FEB-16:54 1233.14 15-FEB-16:54 20.12 17-FEB-15:45 273.33 15-FEB-16:54 0.00
March 0.260404E+09 58349325.94 99.70 0.257209E+09 3195259.94 0.00 0.30 16-MAR-14:43 0.00 01-MAR-00:10 1586.31 16-MAR-14:23 1544.04 16-MAR-14:54 87.09 15-MAR-13:20 349.56 16-MAR-14:23 0.00
April 0.101371E+10 0.225399E+09 183.48 0.101026E+10 3448078.18 0.00 1.00 14-APR-07:02 0.00 01-APR-00:10 5827.20 14-APR-07:02 5827.20 27-APR-07:02 92.88 21-APR-13:17 1138.34 14-APR-07:02 0.00
May 0.211229E+10 0.465519E+09 224.34 0.201045E+10 0.101833E+09 0.00 1.00 01-MAY-07:03 0.00 01-MAY-00:10 6291.05 24-MAY-07:01 6012.25 19-MAY-07:01 1483.80 24-MAY-07:12 1234.07 24-MAY-07:01 0.00
June 0.354979E+10 0.830694E+09 238.78 0.335058E+10 0.199213E+09 0.00 1.00 01-JUN-07:02 0.00 01-JUN-00:10 6291.56 30-JUN-06:03 6144.04 28-JUN-06:02 1283.73 06-JUN-07:11 1509.40 29-JUN-13:00 0.00
July 0.420745E+10 0.965438E+09 226.76 0.371809E+10 0.489359E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:10 6498.52 10-JUL-06:01 6252.81 24-JUL-05:02 1633.36 27-JUL-07:08 1481.02 21-JUL-14:40 0.00
August 0.452899E+10 0.100784E+10 255.65 0.393851E+10 0.590478E+09 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 6491.38 14-AUG-06:01 5898.87 07-AUG-05:03 1926.32 30-AUG-07:12 1430.58 21-AUG-16:05 0.00
September 0.322661E+10 0.701717E+09 219.08 0.287062E+10 0.355982E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 6420.58 06-SEP-06:03 5958.86 21-SEP-07:02 1785.15 06-SEP-07:08 1281.41 05-SEP-13:55 0.00
October 0.195378E+10 0.421181E+09 204.89 0.181490E+10 0.138886E+09 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 6325.90 03-OCT-06:03 5850.16 06-OCT-07:02 1378.81 11-OCT-07:13 1239.90 03-OCT-06:03 0.00
November 0.453594E+09 0.100771E+09 136.04 0.432638E+09 20956265.39 0.00 0.42 02-NOV-16:00 0.00 01-NOV-00:10 2322.56 02-NOV-16:00 2059.81 02-NOV-15:58 326.73 02-NOV-13:20 502.38 02-NOV-16:00 0.00
December 10566634.44 2380729.29 5.83 10441334.07 125300.37 0.00 0.16 01-DEC-16:07 0.00 01-DEC-00:10 812.53 01-DEC-16:07 805.72 01-DEC-16:07 13.96 01-DEC-14:13 182.25 01-DEC-16:07 0.00
                                       
Annual Sum or Average 0.213562E+11 0.478806E+10 1814.59 0.194525E+11 0.190366E+10 0.00                         0.00
Minimum of Months 766653.53 175798.67 1.72 744792.85 21860.69 0.00 0.03   0.00   165.69   161.64   4.70   37.96   0.00
Maximum of Months 0.452899E+10 0.100784E+10 255.65 0.393851E+10 0.590478E+09 0.00 1.00   0.00   6498.52   6252.81   1926.32   1509.40   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.290456E+09 63811253.74 59.14 0.290456E+09 -0.0 0.00 0.43 03-JAN-14:45 0.00 01-JAN-00:05 2495.75 03-JAN-14:45 2495.75 03-JAN-14:45 0.00 02-JAN-11:20 536.84 03-JAN-14:45 0.00
February 0.275738E+09 59867246.94 47.25 0.275738E+09 -0.0 0.00 0.60 14-FEB-14:55 0.00 01-FEB-00:10 3625.49 14-FEB-14:55 3625.49 14-FEB-14:55 0.00 15-FEB-12:25 766.47 14-FEB-15:05 0.00
March 0.335606E+09 74179335.40 76.82 0.335606E+09 -0.0 0.00 0.43 08-MAR-14:25 0.00 01-MAR-00:10 2493.73 13-MAR-14:25 2493.73 13-MAR-14:25 0.00 08-MAR-16:45 547.00 08-MAR-14:25 0.00
April 0.653962E+09 0.147362E+09 120.37 0.653962E+09 -0.0 0.00 0.55 28-APR-14:27 0.00 01-APR-00:10 3217.84 28-APR-14:27 3217.84 28-APR-14:27 0.00 13-APR-17:00 726.26 28-APR-14:27 0.00
May 0.111388E+10 0.257192E+09 180.87 0.109360E+10 20281910.27 0.00 0.59 19-MAY-16:10 0.00 01-MAY-00:10 3568.56 22-MAY-07:02 3420.62 19-MAY-16:07 373.48 23-MAY-15:20 857.29 19-MAY-16:07 0.00
June 0.268167E+10 0.663422E+09 221.62 0.261972E+10 61955165.21 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 6831.75 29-JUN-06:01 6712.01 26-JUN-06:01 727.85 29-JUN-07:04 1622.43 27-JUN-16:03 0.00
July 0.362398E+10 0.866546E+09 218.11 0.332825E+10 0.295725E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:10 7159.49 17-JUL-06:01 6848.45 05-JUL-06:01 1953.18 17-JUL-07:13 1615.72 21-JUL-16:03 0.00
August 0.408587E+10 0.940157E+09 245.16 0.372690E+10 0.358971E+09 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 7254.54 14-AUG-06:01 6635.43 07-AUG-06:01 2195.55 14-AUG-07:06 1555.75 21-AUG-16:05 0.00
September 0.338735E+10 0.745036E+09 209.00 0.320692E+10 0.180429E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 7103.59 05-SEP-06:01 6624.19 03-SEP-14:31 2074.97 06-SEP-07:02 1537.75 03-SEP-14:31 0.00
October 0.262708E+10 0.552923E+09 190.18 0.256534E+10 61732545.97 0.00 1.00 01-OCT-15:32 0.00 01-OCT-00:10 6947.24 11-OCT-07:02 6811.82 02-OCT-06:02 1291.83 11-OCT-07:02 1494.32 01-OCT-15:32 0.00
November 0.102778E+10 0.220667E+09 147.36 0.102633E+10 1457993.03 0.00 0.78 01-NOV-13:10 0.00 01-NOV-00:10 4822.49 01-NOV-13:10 4822.49 01-NOV-13:10 112.88 02-NOV-13:00 979.26 01-NOV-13:10 0.00
December 0.210491E+09 46870662.54 65.31 0.210491E+09 -0.0 0.00 0.38 19-DEC-13:10 0.00 01-DEC-00:10 2178.30 19-DEC-13:10 2178.30 19-DEC-13:10 0.00 26-DEC-15:17 472.41 19-DEC-13:10 0.00
                                       
Annual Sum or Average 0.203139E+11 0.463803E+10 1781.19 0.193333E+11 0.980552E+09 0.00                         0.00
Minimum of Months 0.210491E+09 46870662.54 47.25 0.210491E+09 -0.0 0.00 0.38   0.00   2178.30   2178.30   0.00   472.41   0.00
Maximum of Months 0.408587E+10 0.940157E+09 245.16 0.372690E+10 0.358971E+09 0.00 1.00   0.00   7254.54   6848.45   2195.55   1622.43   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 9002181.29 2053786.34 8.57 9002181.29 -0.0 0.00 0.11 14-FEB-16:00 0.00 01-FEB-00:10 498.60 14-FEB-16:00 498.60 14-FEB-16:00 0.00 15-FEB-14:50 114.91 14-FEB-16:00 0.00
March 76680549.95 17436519.51 72.33 76680549.95 0.00 0.00 0.15 08-MAR-15:57 0.00 01-MAR-00:10 692.64 08-MAR-15:57 692.64 08-MAR-15:57 0.00 15-MAR-13:05 160.37 08-MAR-15:57 0.00
April 0.680295E+09 0.152668E+09 185.16 0.680295E+09 0.00 0.00 1.00 27-APR-07:02 0.00 01-APR-00:10 5235.13 27-APR-07:02 5235.13 27-APR-07:02 0.00 17-APR-09:28 1022.68 27-APR-07:02 0.00
May 0.126707E+10 0.286214E+09 223.42 0.124899E+10 18072919.50 0.00 1.00 10-MAY-07:01 0.00 01-MAY-00:10 5562.67 24-MAY-07:01 5412.46 23-MAY-07:01 679.72 24-MAY-07:01 1092.76 24-MAY-07:01 0.00
June 0.242512E+10 0.587159E+09 247.48 0.238555E+10 39568097.57 0.00 1.00 01-JUN-07:02 0.00 01-JUN-00:10 5609.55 05-JUN-07:02 5527.65 29-JUN-06:01 896.45 05-JUN-07:02 1188.24 29-JUN-07:02 0.00
July 0.288583E+10 0.692816E+09 258.30 0.272564E+10 0.160187E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:10 5842.28 17-JUL-06:01 5585.22 05-JUL-06:01 1179.05 27-JUL-07:02 1260.86 23-JUL-10:32 0.00
August 0.302907E+10 0.702283E+09 277.21 0.283730E+10 0.191774E+09 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 5876.63 14-AUG-06:01 5598.95 20-AUG-08:52 1413.63 30-AUG-07:02 1206.12 20-AUG-09:32 0.00
September 0.202782E+10 0.457588E+09 220.34 0.194109E+10 86735031.25 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 5794.95 05-SEP-06:01 5425.00 13-SEP-07:02 1235.68 06-SEP-07:02 1131.06 05-SEP-06:01 0.00
October 0.111231E+10 0.246694E+09 189.77 0.108534E+10 26965153.82 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 5641.26 11-OCT-07:02 5534.51 02-OCT-06:02 875.48 11-OCT-07:02 1106.87 11-OCT-07:02 0.00
November 0.134089E+09 30211063.31 87.53 0.133885E+09 204731.31 0.00 0.30 01-NOV-10:02 0.00 01-NOV-00:10 1380.04 01-NOV-10:08 1380.04 01-NOV-10:08 22.53 02-NOV-13:00 303.25 01-NOV-10:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.136473E+11 0.317512E+10 1770.11 0.131238E+11 0.523507E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.302907E+10 0.702283E+09 277.21 0.283730E+10 0.191774E+09 0.00 1.00   0.00   5876.63   5598.95   1413.63   1260.86   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00 01-FEB-00:10 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.352633E+09 81110781.88 98.04 0.352633E+09 0.00 0.00 0.40 28-APR-15:24 0.00 01-APR-00:10 2235.72 28-APR-15:24 2235.72 28-APR-15:24 0.00 12-APR-15:38 520.14 28-APR-15:24 0.00
May 0.113924E+10 0.262180E+09 196.41 0.111090E+10 28339109.73 0.00 1.00 19-MAY-07:01 0.00 01-MAY-00:10 6551.82 22-MAY-07:02 6428.98 23-MAY-07:01 375.10 23-MAY-15:20 1287.21 22-MAY-07:02 0.00
June 0.273461E+10 0.670398E+09 233.95 0.266459E+10 70025067.71 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 6677.72 29-JUN-06:01 6584.17 27-JUN-06:01 1011.03 05-JUN-07:02 1510.82 28-JUN-15:57 0.00
July 0.347318E+10 0.831183E+09 223.02 0.320237E+10 0.270811E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:10 6991.31 17-JUL-06:01 6684.04 05-JUL-06:01 1696.17 17-JUL-07:13 1478.15 24-JUL-15:00 0.00
August 0.355243E+10 0.825663E+09 249.79 0.323425E+10 0.318183E+09 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 7067.42 14-AUG-06:01 6477.27 07-AUG-06:01 1859.71 30-AUG-07:02 1431.68 21-AUG-14:00 0.00
September 0.221495E+10 0.504258E+09 204.74 0.206214E+10 0.152813E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 6905.26 05-SEP-06:01 6426.18 15-SEP-07:02 1743.14 06-SEP-07:02 1349.89 05-SEP-06:01 0.00
October 0.965017E+09 0.217304E+09 149.61 0.918961E+09 46055739.06 0.00 1.00 02-OCT-07:02 0.00 01-OCT-00:10 6749.10 11-OCT-07:02 6145.37 02-OCT-07:02 1243.31 11-OCT-07:02 1324.57 11-OCT-07:02 0.00
November 39330240.00 8915589.00 23.79 38417915.38 912324.62 0.00 0.17 02-NOV-15:50 0.00 01-NOV-00:10 959.80 02-NOV-15:50 912.52 02-NOV-15:35 49.85 02-NOV-16:00 215.80 02-NOV-15:50 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.144714E+11 0.340101E+10 1379.35 0.135843E+11 0.887140E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.355243E+10 0.831183E+09 249.79 0.323425E+10 0.318183E+09 0.00 1.00   0.00   7067.42   6684.04   1859.71   1510.82   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4953742.50 1127899.69 5.06 4953742.50 0.00 0.00 0.09 05-JAN-16:27 0.00 01-JAN-00:05 486.54 05-JAN-16:27 486.54 05-JAN-16:27 0.00 03-JAN-16:47 110.33 05-JAN-16:27 0.00
February 46204784.86 10377177.62 19.58 46204784.86 -0.0 0.00 0.29 15-FEB-16:42 0.00 01-FEB-00:10 1613.80 15-FEB-16:42 1613.80 15-FEB-16:42 0.00 08-FEB-16:33 354.97 15-FEB-16:42 0.00
March 0.110030E+09 24827279.54 52.13 0.110030E+09 -0.0 0.00 0.27 08-MAR-17:00 0.00 01-MAR-00:10 1513.92 08-MAR-16:55 1513.92 08-MAR-16:55 0.00 09-MAR-15:35 340.52 08-MAR-16:55 0.00
April 0.532002E+09 0.121343E+09 139.66 0.532002E+09 0.00 0.00 0.48 13-APR-15:53 0.00 01-APR-00:10 2744.75 13-APR-16:00 2744.75 13-APR-16:00 0.00 14-APR-09:23 637.96 13-APR-16:00 0.00
May 0.106465E+10 0.246216E+09 209.50 0.104546E+10 19192269.72 0.00 1.00 15-MAY-07:02 0.00 01-MAY-00:10 6658.83 22-MAY-07:02 6538.18 23-MAY-07:01 234.99 23-MAY-15:40 1308.38 22-MAY-07:02 0.00
June 0.217117E+10 0.547695E+09 263.00 0.212351E+10 47660686.40 0.00 1.00 07-JUN-07:02 0.00 01-JUN-00:10 6769.02 29-JUN-06:01 6720.98 29-JUN-06:01 824.62 05-JUN-07:02 1591.18 25-JUN-16:42 0.00
July 0.265536E+10 0.661587E+09 257.38 0.247707E+10 0.178293E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:10 7113.38 17-JUL-06:01 6781.65 05-JUL-06:01 1415.20 27-JUL-07:02 1627.42 04-JUL-16:23 0.00
August 0.283248E+10 0.679177E+09 282.45 0.261877E+10 0.213707E+09 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 7130.75 14-AUG-06:01 6787.68 17-AUG-06:02 1642.36 30-AUG-07:02 1617.02 20-AUG-16:03 0.00
September 0.193887E+10 0.448534E+09 224.37 0.183450E+10 0.104368E+09 0.00 1.00 01-SEP-07:02 0.00 01-SEP-00:10 7029.65 05-SEP-06:01 6590.73 13-SEP-07:02 1515.71 06-SEP-07:02 1372.14 05-SEP-06:01 0.00
October 0.110733E+10 0.249161E+09 181.78 0.107388E+10 33453363.70 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 6840.91 11-OCT-07:02 6724.36 02-OCT-06:02 1003.90 11-OCT-07:02 1342.35 11-OCT-07:02 0.00
November 0.226880E+09 50899846.17 95.13 0.225660E+09 1219687.90 0.00 0.37 02-NOV-16:00 0.00 01-NOV-00:10 2177.27 02-NOV-16:00 2113.00 02-NOV-15:55 64.29 02-NOV-15:53 474.38 02-NOV-16:00 0.00
December 4291425.15 976549.27 3.89 4291425.15 -0.0 0.00 0.09 01-DEC-15:55 0.00 01-DEC-00:10 465.68 01-DEC-15:55 465.68 01-DEC-15:55 0.00 29-DEC-16:10 105.66 01-DEC-15:55 0.00
                                       
Annual Sum or Average 0.126942E+11 0.304192E+10 1733.93 0.120963E+11 0.597895E+09 0.00                         0.00
Minimum of Months 4291425.15 976549.27 3.89 4291425.15 -0.0 0.00 0.09   0.00   465.68   465.68   0.00   105.66   0.00
Maximum of Months 0.283248E+10 0.679177E+09 282.45 0.261877E+10 0.213707E+09 0.00 1.00   0.00   7130.75   6787.68   1642.36   1627.42   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.80 55.57 38.23 115.99 46.05 0.00 0.00 0.00
April 58.52 17.38 41.14 68.73 32.85 0.00 0.00 0.00
May 36.67 0.34 36.33 38.99 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.24 0.25 36.98 55.24 14.24 0.00 0.00 0.00
August 47.52 7.96 39.56 68.09 16.73 0.00 0.00 0.00
September 79.31 40.86 38.46 110.82 27.74 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.69 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.03 55.50 35.53 113.63 39.03 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 38.99 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.14 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.79 55.57 38.23 115.97 46.05 0.00 0.00 0.00
April 58.30 17.28 41.02 68.28 32.86 0.00 0.00 0.00
May 36.66 0.34 36.32 38.98 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.23 0.25 36.98 55.23 14.24 0.00 0.00 0.00
August 47.44 7.93 39.51 67.94 16.73 0.00 0.00 0.00
September 79.18 40.79 38.39 110.56 27.74 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.68 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.00 55.48 35.51 113.55 39.03 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 38.98 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.02 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.79 55.57 38.23 115.97 46.05 0.00 0.00 0.00
April 58.30 17.28 41.02 68.28 32.86 0.00 0.00 0.00
May 36.66 0.34 36.32 38.98 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.23 0.25 36.98 55.23 14.24 0.00 0.00 0.00
August 47.44 7.93 39.51 67.94 16.73 0.00 0.00 0.00
September 79.17 40.79 38.38 110.54 27.75 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.68 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.00 55.48 35.51 113.55 39.03 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 38.98 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.02 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.79 55.57 38.23 115.97 46.05 0.00 0.00 0.00
April 58.30 17.28 41.02 68.28 32.86 0.00 0.00 0.00
May 36.66 0.34 36.32 38.98 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.23 0.25 36.98 55.23 14.24 0.00 0.00 0.00
August 47.44 7.93 39.51 67.94 16.73 0.00 0.00 0.00
September 79.17 40.79 38.38 110.54 27.74 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.68 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.00 55.48 35.51 113.55 39.03 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 38.98 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.02 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.79 55.57 38.23 115.97 46.05 0.00 0.00 0.00
April 58.30 17.28 41.02 68.28 32.86 0.00 0.00 0.00
May 36.66 0.34 36.32 38.98 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.23 0.25 36.98 55.23 14.24 0.00 0.00 0.00
August 47.44 7.93 39.51 67.94 16.73 0.00 0.00 0.00
September 79.19 40.79 38.40 110.54 27.71 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.68 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.00 55.48 35.51 113.55 39.03 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 38.98 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.02 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.59 110.85 30.74 168.23 63.79 0.00 0.00 0.00
February 138.44 101.84 36.61 168.70 57.84 0.00 0.00 0.00
March 93.81 55.58 38.23 115.99 46.05 0.00 0.00 0.00
April 58.57 17.41 41.17 68.79 32.81 0.00 0.00 0.00
May 36.67 0.35 36.33 39.00 24.93 0.00 0.00 0.00
June 35.93 0.00 35.93 49.71 18.49 0.00 0.00 0.00
July 37.23 0.25 36.98 55.24 14.24 0.00 0.00 0.00
August 47.52 7.97 39.55 68.10 16.73 0.00 0.00 0.00
September 79.34 40.87 38.47 110.76 27.61 0.00 0.00 0.00
October 128.42 95.04 33.38 165.78 43.69 0.00 0.00 0.00
November 144.09 111.22 32.87 173.83 56.32 0.00 0.00 0.00
December 153.98 127.50 26.48 183.08 66.85 0.00 0.00 0.00
                 
Annual Sum or Average 91.04 55.51 35.54 113.63 39.02 0.00 0.00 0.00
Minimum of Months 35.93 0.00 26.48 39.00 14.24 0.00 0.00 0.00
Maximum of Months 153.98 127.50 41.17 183.08 66.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 198.97 155.30 43.66 236.26 89.13 0.00 0.00 0.00
February 194.63 142.67 51.96 236.93 80.82 0.00 0.00 0.00
March 142.94 87.01 55.93 179.52 64.42 0.00 0.00 0.00
April 98.70 36.65 62.05 123.81 46.17 0.00 0.00 0.00
May 59.61 6.13 53.47 69.38 35.12 0.00 0.00 0.00
June 51.71 0.40 51.31 71.18 26.14 0.00 0.00 0.00
July 55.96 2.41 53.55 83.61 20.17 0.00 0.00 0.00
August 80.51 20.85 59.66 119.26 23.62 0.00 0.00 0.00
September 127.92 70.72 57.20 181.50 38.95 0.00 0.00 0.00
October 181.71 134.25 47.45 234.26 61.25 0.00 0.00 0.00
November 202.45 155.83 46.62 243.95 78.80 0.00 0.00 0.00
December 216.13 178.62 37.51 256.69 93.42 0.00 0.00 0.00
                 
Annual Sum or Average 133.93 82.26 51.67 169.30 54.70 0.00 0.00 0.00
Minimum of Months 51.71 0.40 37.51 69.38 20.17 0.00 0.00 0.00
Maximum of Months 216.13 178.62 62.05 256.69 93.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.26 28.90 22.35 47.47 58.87 0.00 0.00 0.00
February 61.72 33.30 28.42 62.17 52.84 0.00 0.00 0.00
March 81.06 46.22 34.85 90.81 42.25 0.00 0.00 0.00
April 110.32 62.69 47.63 132.51 30.93 0.00 0.00 0.00
May 104.07 58.59 45.48 130.43 25.22 0.00 0.00 0.00
June 112.46 68.56 43.90 154.20 18.31 0.00 0.00 0.00
July 103.54 58.54 45.00 146.91 14.69 0.00 0.00 0.00
August 103.01 56.22 46.79 141.76 16.24 0.00 0.00 0.00
September 86.41 48.09 38.32 112.19 25.37 0.00 0.00 0.00
October 76.24 48.41 27.83 87.51 40.28 0.00 0.00 0.00
November 59.88 35.41 24.47 59.26 52.84 0.00 0.00 0.00
December 48.73 29.80 18.93 44.54 63.20 0.00 0.00 0.00
                 
Annual Sum or Average 83.30 47.95 35.35 100.98 36.67 0.00 0.00 0.00
Minimum of Months 48.73 28.90 18.93 44.54 14.69 0.00 0.00 0.00
Maximum of Months 112.46 68.56 47.63 154.20 63.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.25 28.90 22.35 47.47 58.87 0.00 0.00 0.00
February 61.72 33.30 28.42 62.17 52.83 0.00 0.00 0.00
March 81.06 46.22 34.84 90.81 42.25 0.00 0.00 0.00
April 110.32 62.69 47.63 132.51 30.93 0.00 0.00 0.00
May 104.07 58.59 45.48 130.43 25.22 0.00 0.00 0.00
June 112.46 68.56 43.90 154.20 18.31 0.00 0.00 0.00
July 103.54 58.54 44.99 146.91 14.69 0.00 0.00 0.00
August 103.01 56.22 46.78 141.76 16.24 0.00 0.00 0.00
September 86.41 48.09 38.32 112.19 25.37 0.00 0.00 0.00
October 76.24 48.41 27.83 87.51 40.28 0.00 0.00 0.00
November 59.88 35.41 24.47 59.26 52.84 0.00 0.00 0.00
December 48.73 29.80 18.93 44.54 63.19 0.00 0.00 0.00
                 
Annual Sum or Average 83.30 47.95 35.35 100.98 36.67 0.00 0.00 0.00
Minimum of Months 48.73 28.90 18.93 44.54 14.69 0.00 0.00 0.00
Maximum of Months 112.46 68.56 47.63 154.20 63.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.25 28.90 22.35 47.47 58.87 0.00 0.00 0.00
February 61.72 33.30 28.42 62.17 52.83 0.00 0.00 0.00
March 81.06 46.22 34.84 90.81 42.25 0.00 0.00 0.00
April 110.32 62.69 47.63 132.51 30.93 0.00 0.00 0.00
May 104.07 58.59 45.48 130.43 25.22 0.00 0.00 0.00
June 112.46 68.56 43.90 154.20 18.31 0.00 0.00 0.00
July 103.54 58.54 44.99 146.91 14.69 0.00 0.00 0.00
August 103.01 56.22 46.78 141.76 16.24 0.00 0.00 0.00
September 86.41 48.09 38.32 112.19 25.37 0.00 0.00 0.00
October 76.24 48.41 27.83 87.51 40.28 0.00 0.00 0.00
November 59.88 35.41 24.47 59.26 52.84 0.00 0.00 0.00
December 48.73 29.80 18.93 44.54 63.19 0.00 0.00 0.00
                 
Annual Sum or Average 83.30 47.95 35.35 100.98 36.67 0.00 0.00 0.00
Minimum of Months 48.73 28.90 18.93 44.54 14.69 0.00 0.00 0.00
Maximum of Months 112.46 68.56 47.63 154.20 63.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.32 28.95 22.37 47.61 58.87 0.00 0.00 0.00
February 61.74 33.31 28.42 62.20 52.84 0.00 0.00 0.00
March 81.06 46.22 34.85 90.81 42.25 0.00 0.00 0.00
April 110.32 62.69 47.63 132.51 30.93 0.00 0.00 0.00
May 104.07 58.59 45.48 130.43 25.22 0.00 0.00 0.00
June 112.46 68.56 43.90 154.20 18.31 0.00 0.00 0.00
July 103.54 58.54 45.00 146.91 14.69 0.00 0.00 0.00
August 103.01 56.22 46.79 141.76 16.24 0.00 0.00 0.00
September 86.41 48.09 38.32 112.19 25.37 0.00 0.00 0.00
October 76.25 48.41 27.84 87.52 40.28 0.00 0.00 0.00
November 59.92 35.44 24.49 59.36 52.84 0.00 0.00 0.00
December 48.81 29.86 18.95 44.69 63.16 0.00 0.00 0.00
                 
Annual Sum or Average 83.32 47.96 35.36 101.02 36.67 0.00 0.00 0.00
Minimum of Months 48.81 28.95 18.95 44.69 14.69 0.00 0.00 0.00
Maximum of Months 112.46 68.56 47.63 154.20 63.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.11 0.31 36.80 33.91 29.78 0.00 0.00 0.00
May 39.97 2.40 37.57 43.44 23.50 0.00 0.00 0.00
June 45.04 6.90 38.14 63.39 17.58 0.00 0.00 0.00
July 41.50 3.15 38.34 62.17 13.69 0.00 0.00 0.00
August 38.93 0.84 38.09 53.46 15.33 0.00 0.00 0.00
September 31.15 0.01 31.14 36.73 25.20 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.28 1.14 29.15 30.16 37.14 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 45.04 6.90 38.34 63.39 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.03 0.29 36.74 33.87 29.88 0.00 0.00 0.00
May 39.76 2.30 37.47 43.01 23.50 0.00 0.00 0.00
June 44.88 6.80 38.09 63.05 17.58 0.00 0.00 0.00
July 41.32 3.06 38.27 61.79 13.69 0.00 0.00 0.00
August 38.79 0.78 38.01 53.17 15.33 0.00 0.00 0.00
September 31.15 0.01 31.14 36.72 25.20 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.22 1.10 29.12 30.03 37.15 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 44.88 6.80 38.27 63.05 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.02 0.29 36.73 33.86 29.91 0.00 0.00 0.00
May 39.76 2.30 37.47 43.01 23.50 0.00 0.00 0.00
June 44.88 6.80 38.09 63.05 17.58 0.00 0.00 0.00
July 41.32 3.06 38.27 61.79 13.69 0.00 0.00 0.00
August 38.79 0.78 38.01 53.18 15.34 0.00 0.00 0.00
September 31.14 0.01 31.14 36.73 25.20 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.22 1.10 29.11 30.03 37.15 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 44.88 6.80 38.27 63.05 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.02 0.29 36.73 33.86 29.91 0.00 0.00 0.00
May 39.76 2.30 37.47 43.01 23.50 0.00 0.00 0.00
June 44.88 6.80 38.09 63.05 17.58 0.00 0.00 0.00
July 41.32 3.06 38.27 61.79 13.69 0.00 0.00 0.00
August 38.79 0.78 38.01 53.18 15.34 0.00 0.00 0.00
September 31.14 0.01 31.14 36.73 25.20 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.22 1.10 29.11 30.03 37.15 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 44.88 6.80 38.27 63.05 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.03 0.29 36.74 33.88 29.90 0.00 0.00 0.00
May 39.76 2.30 37.47 43.01 23.50 0.00 0.00 0.00
June 44.88 6.80 38.09 63.05 17.58 0.00 0.00 0.00
July 41.32 3.06 38.27 61.79 13.69 0.00 0.00 0.00
August 38.79 0.78 38.01 53.18 15.34 0.00 0.00 0.00
September 31.15 0.01 31.14 36.73 25.21 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.22 1.10 29.12 30.03 37.15 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 44.88 6.80 38.27 63.05 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.40 0.00 18.40 6.24 62.49 0.00 0.00 0.00
February 23.11 0.00 23.11 11.94 55.29 0.00 0.00 0.00
March 28.98 0.00 28.98 22.72 42.86 0.00 0.00 0.00
April 37.08 0.31 36.77 33.95 29.88 0.00 0.00 0.00
May 39.90 2.37 37.53 43.29 23.50 0.00 0.00 0.00
June 45.01 6.87 38.13 63.32 17.58 0.00 0.00 0.00
July 41.44 3.11 38.33 62.02 13.69 0.00 0.00 0.00
August 38.90 0.81 38.09 53.40 15.34 0.00 0.00 0.00
September 31.15 0.01 31.14 36.74 25.21 0.00 0.00 0.00
October 23.37 0.00 23.37 17.36 41.02 0.00 0.00 0.00
November 19.72 0.00 19.72 7.04 53.39 0.00 0.00 0.00
December 15.82 0.00 15.82 2.39 66.57 0.00 0.00 0.00
                 
Annual Sum or Average 30.27 1.13 29.14 30.12 37.15 0.00 0.00 0.00
Minimum of Months 15.82 0.00 15.82 2.39 13.69 0.00 0.00 0.00
Maximum of Months 45.01 6.87 38.33 63.32 66.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.95 30.44 22.51 53.55 63.32 0.00 0.00 0.00
February 67.71 39.25 28.46 72.95 57.01 0.00 0.00 0.00
March 74.75 39.82 34.93 84.90 45.27 0.00 0.00 0.00
April 94.89 50.17 44.72 113.32 33.37 0.00 0.00 0.00
May 88.96 45.03 43.93 111.00 26.78 0.00 0.00 0.00
June 95.52 52.52 43.00 132.89 21.00 0.00 0.00 0.00
July 85.20 40.65 44.55 122.90 15.91 0.00 0.00 0.00
August 87.92 39.96 47.96 122.72 18.18 0.00 0.00 0.00
September 80.10 41.79 38.31 105.51 27.84 0.00 0.00 0.00
October 74.86 46.58 28.28 88.73 44.03 0.00 0.00 0.00
November 59.05 34.94 24.11 60.60 55.33 0.00 0.00 0.00
December 51.44 32.42 19.02 50.32 66.51 0.00 0.00 0.00
                 
Annual Sum or Average 76.11 41.10 35.01 93.34 39.46 0.00 0.00 0.00
Minimum of Months 51.44 30.44 19.02 50.32 15.91 0.00 0.00 0.00
Maximum of Months 95.52 52.52 47.96 132.89 66.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.88 30.39 22.49 53.41 63.32 0.00 0.00 0.00
February 67.70 39.24 28.46 72.92 57.01 0.00 0.00 0.00
March 74.75 39.82 34.93 84.90 45.27 0.00 0.00 0.00
April 94.89 50.17 44.72 113.32 33.36 0.00 0.00 0.00
May 88.96 45.03 43.93 111.00 26.78 0.00 0.00 0.00
June 95.52 52.52 43.00 132.89 21.00 0.00 0.00 0.00
July 85.20 40.65 44.55 122.90 15.91 0.00 0.00 0.00
August 87.92 39.96 47.96 122.71 18.18 0.00 0.00 0.00
September 80.10 41.79 38.31 105.51 27.83 0.00 0.00 0.00
October 74.86 46.58 28.28 88.72 44.03 0.00 0.00 0.00
November 59.00 34.91 24.09 60.50 55.33 0.00 0.00 0.00
December 51.36 32.36 19.00 50.16 66.53 0.00 0.00 0.00
                 
Annual Sum or Average 76.09 41.09 35.00 93.30 39.46 0.00 0.00 0.00
Minimum of Months 51.36 30.39 19.00 50.16 15.91 0.00 0.00 0.00
Maximum of Months 95.52 52.52 47.96 132.89 66.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.88 30.39 22.49 53.41 63.32 0.00 0.00 0.00
February 67.70 39.24 28.46 72.92 57.01 0.00 0.00 0.00
March 74.75 39.82 34.93 84.90 45.27 0.00 0.00 0.00
April 94.89 50.17 44.72 113.32 33.36 0.00 0.00 0.00
May 88.96 45.03 43.93 111.00 26.78 0.00 0.00 0.00
June 95.52 52.52 43.00 132.89 21.00 0.00 0.00 0.00
July 85.20 40.65 44.55 122.90 15.91 0.00 0.00 0.00
August 87.92 39.96 47.96 122.71 18.18 0.00 0.00 0.00
September 80.10 41.79 38.31 105.51 27.83 0.00 0.00 0.00
October 74.86 46.58 28.28 88.72 44.03 0.00 0.00 0.00
November 59.00 34.91 24.09 60.50 55.33 0.00 0.00 0.00
December 51.36 32.36 19.00 50.16 66.53 0.00 0.00 0.00
                 
Annual Sum or Average 76.09 41.09 35.00 93.30 39.46 0.00 0.00 0.00
Minimum of Months 51.36 30.39 19.00 50.16 15.91 0.00 0.00 0.00
Maximum of Months 95.52 52.52 47.96 132.89 66.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.88 30.39 22.49 53.41 63.32 0.00 0.00 0.00
February 67.70 39.24 28.46 72.92 57.01 0.00 0.00 0.00
March 74.75 39.82 34.93 84.90 45.27 0.00 0.00 0.00
April 94.89 50.17 44.72 113.32 33.37 0.00 0.00 0.00
May 88.96 45.03 43.93 111.00 26.78 0.00 0.00 0.00
June 95.52 52.52 43.00 132.89 21.00 0.00 0.00 0.00
July 85.20 40.65 44.55 122.90 15.91 0.00 0.00 0.00
August 87.92 39.96 47.96 122.72 18.18 0.00 0.00 0.00
September 80.10 41.79 38.31 105.51 27.84 0.00 0.00 0.00
October 74.86 46.58 28.28 88.72 44.03 0.00 0.00 0.00
November 59.00 34.91 24.09 60.50 55.33 0.00 0.00 0.00
December 51.36 32.36 19.00 50.16 66.53 0.00 0.00 0.00
                 
Annual Sum or Average 76.10 41.09 35.00 93.31 39.46 0.00 0.00 0.00
Minimum of Months 51.36 30.39 19.00 50.16 15.91 0.00 0.00 0.00
Maximum of Months 95.52 52.52 47.96 132.89 66.53 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379227E+09 0.296902E+09 82325134.84 0.450599E+09 0.170865E+09
February 0.334923E+09 0.246362E+09 88560395.43 0.408129E+09 0.139937E+09
March 0.251246E+09 0.148849E+09 0.102397E+09 0.310665E+09 0.123346E+09
April 0.151680E+09 45055229.26 0.106625E+09 0.178144E+09 85159224.85
May 98218272.60 922254.73 97296017.87 0.104443E+09 66761987.87
June 93134636.94 17.76 93134619.18 0.128841E+09 47928250.97
July 99732230.62 678674.32 99053556.31 0.147952E+09 38145179.87
August 0.127267E+09 21315269.19 0.105952E+09 0.182380E+09 44818935.86
September 0.205578E+09 0.105899E+09 99679144.66 0.287250E+09 71898847.53
October 0.343952E+09 0.254547E+09 89404875.71 0.444031E+09 0.117006E+09
November 0.373494E+09 0.288291E+09 85202826.17 0.450562E+09 0.145976E+09
December 0.412419E+09 0.341487E+09 70932608.19 0.490349E+09 0.179050E+09
           
Annual Sum or Average 0.287087E+10 0.175031E+10 0.112056E+10 0.358334E+10 0.123089E+10
Minimum of Months 93134636.94 17.76 70932608.19 0.104443E+09 38145179.87
Maximum of Months 0.412419E+09 0.341487E+09 0.106625E+09 0.490349E+09 0.179050E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379225E+09 0.296902E+09 82322567.66 0.450597E+09 0.170863E+09
February 0.334920E+09 0.246362E+09 88557809.25 0.408127E+09 0.139936E+09
March 0.251220E+09 0.148834E+09 0.102386E+09 0.310617E+09 0.123345E+09
April 0.151111E+09 44776929.67 0.106334E+09 0.176993E+09 85170682.93
May 98197199.60 917124.88 97280074.72 0.104406E+09 66760270.65
June 93131087.02 0.00 93131087.02 0.128838E+09 47926750.83
July 99718771.22 672865.06 99045906.16 0.147927E+09 38143824.33
August 0.127061E+09 21243571.11 0.105818E+09 0.181983E+09 44817647.09
September 0.205241E+09 0.105738E+09 99502667.56 0.286576E+09 71907470.54
October 0.343949E+09 0.254547E+09 89402461.37 0.444029E+09 0.117004E+09
November 0.373492E+09 0.288291E+09 85200475.44 0.450560E+09 0.145974E+09
December 0.412417E+09 0.341487E+09 70930891.43 0.490348E+09 0.179048E+09
           
Annual Sum or Average 0.286968E+10 0.174977E+10 0.111991E+10 0.358100E+10 0.123090E+10
Minimum of Months 93131087.02 0.00 70930891.43 0.104406E+09 38143824.33
Maximum of Months 0.412417E+09 0.341487E+09 0.106334E+09 0.490348E+09 0.179048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379225E+09 0.296902E+09 82322567.66 0.450597E+09 0.170863E+09
February 0.334920E+09 0.246362E+09 88557809.25 0.408127E+09 0.139936E+09
March 0.251220E+09 0.148834E+09 0.102386E+09 0.310617E+09 0.123345E+09
April 0.151111E+09 44776929.20 0.106334E+09 0.176993E+09 85170702.44
May 98197199.60 917124.88 97280074.72 0.104406E+09 66760270.65
June 93131087.02 0.00 93131087.02 0.128838E+09 47926750.83
July 99718771.22 672865.06 99045906.16 0.147927E+09 38143824.33
August 0.127060E+09 21242844.76 0.105818E+09 0.181981E+09 44817647.09
September 0.205208E+09 0.105731E+09 99476626.86 0.286529E+09 71919330.93
October 0.343949E+09 0.254547E+09 89402461.37 0.444029E+09 0.117004E+09
November 0.373492E+09 0.288291E+09 85200475.44 0.450560E+09 0.145974E+09
December 0.412417E+09 0.341487E+09 70930891.43 0.490348E+09 0.179048E+09
           
Annual Sum or Average 0.286965E+10 0.174976E+10 0.111989E+10 0.358095E+10 0.123091E+10
Minimum of Months 93131087.02 0.00 70930891.43 0.104406E+09 38143824.33
Maximum of Months 0.412417E+09 0.341487E+09 0.106334E+09 0.490348E+09 0.179048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379225E+09 0.296902E+09 82322567.66 0.450597E+09 0.170863E+09
February 0.334920E+09 0.246362E+09 88557809.25 0.408127E+09 0.139936E+09
March 0.251220E+09 0.148834E+09 0.102386E+09 0.310617E+09 0.123345E+09
April 0.151111E+09 44776929.20 0.106334E+09 0.176993E+09 85170702.44
May 98197199.60 917124.88 97280074.72 0.104406E+09 66760270.65
June 93131087.02 0.00 93131087.02 0.128838E+09 47926750.83
July 99718771.22 672865.06 99045906.16 0.147927E+09 38143824.33
August 0.127060E+09 21242838.95 0.105818E+09 0.181981E+09 44817592.57
September 0.205212E+09 0.105731E+09 99480840.29 0.286526E+09 71910514.81
October 0.343949E+09 0.254547E+09 89402461.37 0.444029E+09 0.117004E+09
November 0.373492E+09 0.288291E+09 85200475.44 0.450560E+09 0.145974E+09
December 0.412417E+09 0.341487E+09 70930891.43 0.490348E+09 0.179048E+09
           
Annual Sum or Average 0.286965E+10 0.174976E+10 0.111989E+10 0.358095E+10 0.123090E+10
Minimum of Months 93131087.02 0.00 70930891.43 0.104406E+09 38143824.33
Maximum of Months 0.412417E+09 0.341487E+09 0.106334E+09 0.490348E+09 0.179048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379225E+09 0.296902E+09 82322567.66 0.450597E+09 0.170863E+09
February 0.334920E+09 0.246362E+09 88557809.25 0.408127E+09 0.139936E+09
March 0.251220E+09 0.148834E+09 0.102386E+09 0.310617E+09 0.123345E+09
April 0.151111E+09 44776929.20 0.106334E+09 0.176993E+09 85170702.44
May 98197199.60 917124.88 97280074.72 0.104406E+09 66760270.65
June 93131087.02 0.00 93131087.02 0.128838E+09 47926750.83
July 99718771.22 672865.06 99045906.16 0.147927E+09 38143824.33
August 0.127061E+09 21243579.80 0.105818E+09 0.181981E+09 44815458.19
September 0.205260E+09 0.105740E+09 99520133.07 0.286530E+09 71827511.52
October 0.343949E+09 0.254547E+09 89402461.37 0.444029E+09 0.117004E+09
November 0.373492E+09 0.288291E+09 85200475.44 0.450560E+09 0.145974E+09
December 0.412417E+09 0.341487E+09 70930891.43 0.490348E+09 0.179048E+09
           
Annual Sum or Average 0.286970E+10 0.174977E+10 0.111993E+10 0.358095E+10 0.123081E+10
Minimum of Months 93131087.02 0.00 70930891.43 0.104406E+09 38143824.33
Maximum of Months 0.412417E+09 0.341487E+09 0.106334E+09 0.490348E+09 0.179048E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.379227E+09 0.296902E+09 82325134.71 0.450599E+09 0.170865E+09
February 0.334923E+09 0.246362E+09 88560395.30 0.408129E+09 0.139937E+09
March 0.251250E+09 0.148852E+09 0.102398E+09 0.310658E+09 0.123332E+09
April 0.151818E+09 45115005.85 0.106703E+09 0.178308E+09 85030669.70
May 98225485.07 924300.98 97301184.09 0.104457E+09 66762000.67
June 93134690.14 35.33 93134654.81 0.128841E+09 47928250.89
July 99729859.49 677094.87 99052764.62 0.147947E+09 38145179.80
August 0.127267E+09 21335827.95 0.105931E+09 0.182404E+09 44813758.31
September 0.205660E+09 0.105933E+09 99726854.00 0.287090E+09 71570876.59
October 0.343952E+09 0.254547E+09 89404875.58 0.444031E+09 0.117006E+09
November 0.373494E+09 0.288291E+09 85202826.05 0.450562E+09 0.145976E+09
December 0.412419E+09 0.341487E+09 70932608.10 0.490349E+09 0.179050E+09
           
Annual Sum or Average 0.287110E+10 0.175043E+10 0.112067E+10 0.358338E+10 0.123042E+10
Minimum of Months 93134690.14 35.33 70932608.10 0.104457E+09 38145179.80
Maximum of Months 0.412419E+09 0.341487E+09 0.106703E+09 0.490349E+09 0.179050E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.532913E+09 0.415964E+09 0.116949E+09 0.632796E+09 0.238716E+09
February 0.470854E+09 0.345157E+09 0.125697E+09 0.573172E+09 0.195508E+09
March 0.382856E+09 0.233060E+09 0.149796E+09 0.480839E+09 0.172553E+09
April 0.255841E+09 94996965.97 0.160844E+09 0.320913E+09 0.119685E+09
May 0.159649E+09 16423949.84 0.143225E+09 0.185817E+09 94074792.34
June 0.134027E+09 1025369.94 0.133002E+09 0.184504E+09 67748807.43
July 0.149880E+09 6458932.88 0.143421E+09 0.223928E+09 54033102.32
August 0.215627E+09 55846140.21 0.159781E+09 0.319419E+09 63263315.92
September 0.331562E+09 0.183293E+09 0.148268E+09 0.470457E+09 0.100971E+09
October 0.486680E+09 0.359580E+09 0.127100E+09 0.627444E+09 0.164063E+09
November 0.524745E+09 0.403900E+09 0.120845E+09 0.632325E+09 0.204258E+09
December 0.578882E+09 0.478427E+09 0.100455E+09 0.687531E+09 0.250214E+09
           
Annual Sum or Average 0.422352E+10 0.259413E+10 0.162938E+10 0.533914E+10 0.172509E+10
Minimum of Months 0.134027E+09 1025369.94 0.100455E+09 0.184504E+09 54033102.32
Maximum of Months 0.578882E+09 0.478427E+09 0.160844E+09 0.687531E+09 0.250214E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137283E+09 77418493.91 59864769.73 0.127141E+09 0.157669E+09
February 0.149319E+09 80571180.95 68747891.60 0.150404E+09 0.127819E+09
March 0.217115E+09 0.123783E+09 93331908.11 0.243221E+09 0.113161E+09
April 0.285954E+09 0.162496E+09 0.123458E+09 0.343467E+09 80164834.24
May 0.278737E+09 0.156927E+09 0.121809E+09 0.349354E+09 67538601.50
June 0.291500E+09 0.177708E+09 0.113792E+09 0.399698E+09 47470943.70
July 0.277312E+09 0.156797E+09 0.120515E+09 0.393481E+09 39343690.68
August 0.275903E+09 0.150591E+09 0.125313E+09 0.379692E+09 43503805.45
September 0.223984E+09 0.124651E+09 99333433.64 0.290799E+09 65764037.44
October 0.204212E+09 0.129661E+09 74551509.12 0.234376E+09 0.107876E+09
November 0.155205E+09 91778225.02 63426971.68 0.153613E+09 0.136957E+09
December 0.130511E+09 79817825.35 50693276.44 0.119297E+09 0.169263E+09
           
Annual Sum or Average 0.262704E+10 0.151220E+10 0.111484E+10 0.318454E+10 0.115653E+10
Minimum of Months 0.130511E+09 77418493.91 50693276.44 0.119297E+09 39343690.68
Maximum of Months 0.291500E+09 0.177708E+09 0.125313E+09 0.399698E+09 0.169263E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137281E+09 77418493.91 59862202.68 0.127140E+09 0.157667E+09
February 0.149316E+09 80571180.95 68745305.55 0.150402E+09 0.127818E+09
March 0.217111E+09 0.123783E+09 93327790.35 0.243217E+09 0.113159E+09
April 0.285950E+09 0.162496E+09 0.123454E+09 0.343463E+09 80162800.72
May 0.278733E+09 0.156927E+09 0.121805E+09 0.349350E+09 67536864.00
June 0.291496E+09 0.177708E+09 0.113789E+09 0.399696E+09 47469475.32
July 0.277309E+09 0.156797E+09 0.120511E+09 0.393478E+09 39342349.10
August 0.275899E+09 0.150591E+09 0.125309E+09 0.379688E+09 43502492.37
September 0.223980E+09 0.124651E+09 99329845.76 0.290796E+09 65762388.32
October 0.204210E+09 0.129661E+09 74549094.90 0.234374E+09 0.107874E+09
November 0.155203E+09 91778225.02 63424621.07 0.153611E+09 0.136955E+09
December 0.130509E+09 79817825.35 50691559.78 0.119296E+09 0.169261E+09
           
Annual Sum or Average 0.262700E+10 0.151220E+10 0.111480E+10 0.318451E+10 0.115651E+10
Minimum of Months 0.130509E+09 77418493.91 50691559.78 0.119296E+09 39342349.10
Maximum of Months 0.291496E+09 0.177708E+09 0.125309E+09 0.399696E+09 0.169261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137281E+09 77418493.91 59862202.68 0.127140E+09 0.157667E+09
February 0.149316E+09 80571180.95 68745305.55 0.150402E+09 0.127818E+09
March 0.217111E+09 0.123783E+09 93327790.35 0.243217E+09 0.113159E+09
April 0.285950E+09 0.162496E+09 0.123454E+09 0.343463E+09 80162800.72
May 0.278733E+09 0.156927E+09 0.121805E+09 0.349350E+09 67536864.00
June 0.291496E+09 0.177708E+09 0.113789E+09 0.399696E+09 47469475.32
July 0.277309E+09 0.156797E+09 0.120511E+09 0.393478E+09 39342349.10
August 0.275899E+09 0.150591E+09 0.125309E+09 0.379688E+09 43502492.37
September 0.223980E+09 0.124651E+09 99329845.76 0.290796E+09 65762388.32
October 0.204210E+09 0.129661E+09 74549094.90 0.234374E+09 0.107874E+09
November 0.155203E+09 91778225.02 63424621.07 0.153611E+09 0.136955E+09
December 0.130509E+09 79817825.35 50691559.78 0.119296E+09 0.169261E+09
           
Annual Sum or Average 0.262700E+10 0.151220E+10 0.111480E+10 0.318451E+10 0.115651E+10
Minimum of Months 0.130509E+09 77418493.91 50691559.78 0.119296E+09 39342349.10
Maximum of Months 0.291496E+09 0.177708E+09 0.125309E+09 0.399696E+09 0.169261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137456E+09 77527554.21 59928759.89 0.127521E+09 0.157669E+09
February 0.149351E+09 80591361.57 68759845.91 0.150474E+09 0.127819E+09
March 0.217116E+09 0.123783E+09 93332437.98 0.243222E+09 0.113161E+09
April 0.285954E+09 0.162496E+09 0.123458E+09 0.343467E+09 80164834.34
May 0.278737E+09 0.156927E+09 0.121809E+09 0.349354E+09 67538601.59
June 0.291500E+09 0.177708E+09 0.113792E+09 0.399698E+09 47470943.78
July 0.277312E+09 0.156797E+09 0.120515E+09 0.393481E+09 39343690.75
August 0.275903E+09 0.150591E+09 0.125313E+09 0.379692E+09 43503805.52
September 0.223984E+09 0.124651E+09 99333433.83 0.290799E+09 65764037.53
October 0.204227E+09 0.129671E+09 74556006.29 0.234408E+09 0.107876E+09
November 0.155319E+09 91848971.67 63469840.83 0.153857E+09 0.136955E+09
December 0.130732E+09 79967517.77 50764835.59 0.119695E+09 0.169159E+09
           
Annual Sum or Average 0.262759E+10 0.151256E+10 0.111503E+10 0.318567E+10 0.115642E+10
Minimum of Months 0.130732E+09 77527554.21 50764835.59 0.119695E+09 39343690.75
Maximum of Months 0.291500E+09 0.177708E+09 0.125313E+09 0.399698E+09 0.169159E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49282725.22 0.00 49282725.22 16710309.74 0.167369E+09
February 55916996.30 0.00 55916996.30 28877671.11 0.133747E+09
March 77630256.95 0.00 77630256.95 60843946.00 0.114799E+09
April 96201083.95 809712.91 95391371.04 87901692.23 77180316.70
May 0.107067E+09 6434762.87 0.100632E+09 0.116344E+09 62930368.89
June 0.116737E+09 17883221.66 98854125.48 0.164306E+09 45570186.12
July 0.111146E+09 8449992.67 0.102696E+09 0.166504E+09 36658959.70
August 0.104258E+09 2241534.87 0.102017E+09 0.143176E+09 41067156.03
September 80736510.65 20189.76 80716320.89 95192818.72 65306155.01
October 62590590.79 0.00 62590590.79 46488076.85 0.109857E+09
November 51107359.03 0.00 51107359.03 18242672.84 0.138383E+09
December 42371557.66 0.00 42371557.66 6404425.55 0.178297E+09
           
Annual Sum or Average 0.955046E+09 35839414.74 0.919206E+09 0.950992E+09 0.117117E+10
Minimum of Months 42371557.66 0.00 42371557.66 6404425.55 36658959.70
Maximum of Months 0.116737E+09 17883221.66 0.102696E+09 0.166504E+09 0.178297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49280158.04 0.00 49280158.04 16708774.08 0.167367E+09
February 55914410.11 0.00 55914410.11 28875855.51 0.133746E+09
March 77626138.98 0.00 77626138.98 60840078.14 0.114797E+09
April 95993732.60 759635.55 95234097.06 87781230.31 77444824.40
May 0.106506E+09 6156725.09 0.100349E+09 0.115198E+09 62941626.62
June 0.116339E+09 17618716.29 98720274.17 0.163424E+09 45568980.93
July 0.110678E+09 8186352.28 0.102492E+09 0.165500E+09 36657660.40
August 0.103887E+09 2086199.73 0.101801E+09 0.142422E+09 41070809.41
September 80731302.51 20112.73 80711189.78 95189655.75 65307218.59
October 62588176.44 0.00 62588176.44 46486594.23 0.109855E+09
November 51105008.29 0.00 51105008.29 18241076.82 0.138382E+09
December 42369840.91 0.00 42369840.91 6403814.88 0.178296E+09
           
Annual Sum or Average 0.953018E+09 34827741.67 0.918191E+09 0.947071E+09 0.117143E+10
Minimum of Months 42369840.91 0.00 42369840.91 6403814.88 36657660.40
Maximum of Months 0.116339E+09 17618716.29 0.102492E+09 0.165500E+09 0.178296E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49280158.04 0.00 49280158.04 16708774.08 0.167367E+09
February 55914410.11 0.00 55914410.11 28875855.51 0.133746E+09
March 77626138.98 0.00 77626138.98 60840078.14 0.114797E+09
April 95951523.21 749665.05 95201858.16 87771564.30 77515676.17
May 0.106506E+09 6156725.09 0.100349E+09 0.115198E+09 62941626.62
June 0.116339E+09 17618716.29 98720274.17 0.163424E+09 45568980.93
July 0.110678E+09 8186352.28 0.102492E+09 0.165500E+09 36657660.40
August 0.103885E+09 2086180.48 0.101799E+09 0.142425E+09 41076577.73
September 80726505.60 19666.16 80706839.45 95194520.29 65320244.86
October 62588176.44 0.00 62588176.44 46486594.23 0.109855E+09
November 51105008.29 0.00 51105008.29 18241076.82 0.138382E+09
December 42369840.91 0.00 42369840.91 6403814.88 0.178296E+09
           
Annual Sum or Average 0.952969E+09 34817305.35 0.918152E+09 0.947069E+09 0.117152E+10
Minimum of Months 42369840.91 0.00 42369840.91 6403814.88 36657660.40
Maximum of Months 0.116339E+09 17618716.29 0.102492E+09 0.165500E+09 0.178296E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49280158.04 0.00 49280158.04 16708774.08 0.167367E+09
February 55914410.11 0.00 55914410.11 28875855.51 0.133746E+09
March 77626138.98 0.00 77626138.98 60840078.14 0.114797E+09
April 95951523.21 749665.05 95201858.16 87771564.30 77515676.17
May 0.106506E+09 6156725.09 0.100349E+09 0.115198E+09 62941626.62
June 0.116339E+09 17618716.29 98720274.17 0.163424E+09 45568980.93
July 0.110678E+09 8186352.28 0.102492E+09 0.165500E+09 36657660.40
August 0.103885E+09 2086181.74 0.101799E+09 0.142430E+09 41081658.70
September 80725959.55 19440.39 80706519.16 95204042.86 65331199.46
October 62588176.44 0.00 62588176.44 46486594.23 0.109855E+09
November 51105008.29 0.00 51105008.29 18241076.82 0.138382E+09
December 42369840.91 0.00 42369840.91 6403814.88 0.178296E+09
           
Annual Sum or Average 0.952969E+09 34817080.84 0.918152E+09 0.947084E+09 0.117154E+10
Minimum of Months 42369840.91 0.00 42369840.91 6403814.88 36657660.40
Maximum of Months 0.116339E+09 17618716.29 0.102492E+09 0.165500E+09 0.178296E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49280158.04 0.00 49280158.04 16708774.08 0.167367E+09
February 55914410.11 0.00 55914410.11 28875855.51 0.133746E+09
March 77626138.98 0.00 77626138.98 60840078.14 0.114797E+09
April 95976258.84 756469.92 95219788.92 87809781.60 77505941.36
May 0.106506E+09 6156725.09 0.100349E+09 0.115198E+09 62941626.62
June 0.116339E+09 17618716.29 98720274.17 0.163424E+09 45568980.93
July 0.110678E+09 8186352.28 0.102492E+09 0.165500E+09 36657660.40
August 0.103887E+09 2086219.52 0.101800E+09 0.142435E+09 41084651.04
September 80729075.11 19649.07 80709426.04 95213457.86 65335734.75
October 62588176.44 0.00 62588176.44 46486594.23 0.109855E+09
November 51105008.29 0.00 51105008.29 18241076.82 0.138382E+09
December 42369840.91 0.00 42369840.91 6403814.88 0.178296E+09
           
Annual Sum or Average 0.952998E+09 34824132.17 0.918174E+09 0.947137E+09 0.117154E+10
Minimum of Months 42369840.91 0.00 42369840.91 6403814.88 36657660.40
Maximum of Months 0.116339E+09 17618716.29 0.102492E+09 0.165500E+09 0.178296E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49282725.09 0.00 49282725.09 16710309.66 0.167369E+09
February 55916996.16 0.00 55916996.16 28877671.02 0.133747E+09
March 77630256.74 0.00 77630256.74 60843945.80 0.114799E+09
April 96104055.09 792313.16 95311741.94 88001760.65 77457739.83
May 0.106863E+09 6336969.01 0.100526E+09 0.115939E+09 62940827.15
June 0.116660E+09 17818292.64 98841402.37 0.164115E+09 45570472.13
July 0.110988E+09 8332307.86 0.102656E+09 0.166121E+09 36658766.49
August 0.104199E+09 2180462.51 0.102019E+09 0.143022E+09 41085883.94
September 80734778.80 19700.86 80715077.94 95219544.82 65337004.36
October 62590590.66 0.00 62590590.66 46488076.77 0.109857E+09
November 51107358.91 0.00 51107358.91 18242672.76 0.138383E+09
December 42371557.57 0.00 42371557.57 6404425.52 0.178297E+09
           
Annual Sum or Average 0.954448E+09 35480046.04 0.918968E+09 0.949985E+09 0.117150E+10
Minimum of Months 42371557.57 0.00 42371557.57 6404425.52 36658766.49
Maximum of Months 0.116660E+09 17818292.64 0.102656E+09 0.166121E+09 0.178297E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141808E+09 81517628.32 60290320.61 0.143415E+09 0.169589E+09
February 0.163814E+09 94953534.66 68860823.78 0.176478E+09 0.137920E+09
March 0.200208E+09 0.106651E+09 93557203.15 0.227409E+09 0.121248E+09
April 0.245946E+09 0.130032E+09 0.115914E+09 0.293738E+09 86483197.13
May 0.238268E+09 0.120604E+09 0.117664E+09 0.297294E+09 71719965.82
June 0.247588E+09 0.136121E+09 0.111467E+09 0.344446E+09 54442582.25
July 0.228208E+09 0.108874E+09 0.119333E+09 0.329170E+09 42621149.67
August 0.235480E+09 0.107019E+09 0.128461E+09 0.328682E+09 48683755.66
September 0.207630E+09 0.108322E+09 99308206.15 0.273492E+09 72148330.64
October 0.200513E+09 0.124764E+09 75749311.19 0.237651E+09 0.117938E+09
November 0.153049E+09 90564057.88 62484497.81 0.157073E+09 0.143417E+09
December 0.137770E+09 86825810.58 50944306.77 0.134788E+09 0.178144E+09
           
Annual Sum or Average 0.240028E+10 0.129625E+10 0.110403E+10 0.294364E+10 0.124435E+10
Minimum of Months 0.137770E+09 81517628.32 50944306.77 0.134788E+09 42621149.67
Maximum of Months 0.247588E+09 0.136121E+09 0.128461E+09 0.344446E+09 0.178144E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141636E+09 81409674.81 60226300.49 0.143045E+09 0.169588E+09
February 0.163780E+09 94933762.33 68846077.63 0.176409E+09 0.137918E+09
March 0.200204E+09 0.106651E+09 93552829.63 0.227404E+09 0.121246E+09
April 0.245942E+09 0.130032E+09 0.115910E+09 0.293735E+09 86481384.61
May 0.238264E+09 0.120604E+09 0.117660E+09 0.297290E+09 71718169.11
June 0.247585E+09 0.136121E+09 0.111464E+09 0.344444E+09 54440993.62
July 0.228204E+09 0.108874E+09 0.119329E+09 0.329166E+09 42619724.74
August 0.235476E+09 0.107019E+09 0.128457E+09 0.328678E+09 48682405.85
September 0.207627E+09 0.108322E+09 99304618.27 0.273489E+09 72146624.69
October 0.200499E+09 0.124755E+09 75743775.00 0.237621E+09 0.117936E+09
November 0.152929E+09 90490280.62 62438348.44 0.156821E+09 0.143418E+09
December 0.137555E+09 86674035.22 50880889.10 0.134360E+09 0.178199E+09
           
Annual Sum or Average 0.239970E+10 0.129589E+10 0.110381E+10 0.294246E+10 0.124439E+10
Minimum of Months 0.137555E+09 81409674.81 50880889.10 0.134360E+09 42619724.74
Maximum of Months 0.247585E+09 0.136121E+09 0.128457E+09 0.344444E+09 0.178199E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141636E+09 81409674.81 60226300.49 0.143045E+09 0.169588E+09
February 0.163780E+09 94933762.33 68846077.63 0.176409E+09 0.137918E+09
March 0.200204E+09 0.106651E+09 93552829.63 0.227404E+09 0.121246E+09
April 0.245942E+09 0.130032E+09 0.115910E+09 0.293735E+09 86481384.61
May 0.238264E+09 0.120604E+09 0.117660E+09 0.297290E+09 71718169.11
June 0.247585E+09 0.136121E+09 0.111464E+09 0.344444E+09 54440993.62
July 0.228204E+09 0.108874E+09 0.119329E+09 0.329166E+09 42619724.74
August 0.235476E+09 0.107019E+09 0.128457E+09 0.328678E+09 48682405.85
September 0.207627E+09 0.108322E+09 99304618.27 0.273489E+09 72146624.69
October 0.200499E+09 0.124755E+09 75743775.00 0.237621E+09 0.117936E+09
November 0.152929E+09 90490280.62 62438348.44 0.156821E+09 0.143418E+09
December 0.137555E+09 86674035.22 50880889.10 0.134360E+09 0.178199E+09
           
Annual Sum or Average 0.239970E+10 0.129589E+10 0.110381E+10 0.294246E+10 0.124439E+10
Minimum of Months 0.137555E+09 81409674.81 50880889.10 0.134360E+09 42619724.74
Maximum of Months 0.247585E+09 0.136121E+09 0.128457E+09 0.344444E+09 0.178199E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141639E+09 81409674.81 60228867.67 0.143047E+09 0.169589E+09
February 0.163782E+09 94933762.33 68848663.81 0.176411E+09 0.137920E+09
March 0.200208E+09 0.106651E+09 93556947.61 0.227408E+09 0.121248E+09
April 0.245946E+09 0.130032E+09 0.115914E+09 0.293738E+09 86483197.23
May 0.238268E+09 0.120604E+09 0.117664E+09 0.297294E+09 71719965.91
June 0.247588E+09 0.136121E+09 0.111467E+09 0.344446E+09 54442582.33
July 0.228208E+09 0.108874E+09 0.119333E+09 0.329170E+09 42621149.75
August 0.235480E+09 0.107019E+09 0.128461E+09 0.328682E+09 48683755.73
September 0.207630E+09 0.108322E+09 99308206.34 0.273492E+09 72148330.73
October 0.200501E+09 0.124755E+09 75746189.35 0.237623E+09 0.117938E+09
November 0.152931E+09 90490280.62 62440699.17 0.156823E+09 0.143420E+09
December 0.137557E+09 86674035.22 50882605.85 0.134360E+09 0.178201E+09
           
Annual Sum or Average 0.239974E+10 0.129589E+10 0.110385E+10 0.294249E+10 0.124441E+10
Minimum of Months 0.137557E+09 81409674.81 50882605.85 0.134360E+09 42621149.75
Maximum of Months 0.247588E+09 0.136121E+09 0.128461E+09 0.344446E+09 0.178201E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1245.66 471.88 1048.49 820.41 228.08 0.00 0.00
February 1249.14 427.87 1025.29 753.69 271.60 0.00 0.00
March 875.38 340.73 705.73 420.44 285.30 0.00 0.00
April 534.44 243.25 448.99 140.54 308.45 0.00 0.00
May 303.29 184.68 279.60 8.19 271.41 0.00 0.00
June 369.42 137.08 267.29 0.40 266.90 0.00 0.00
July 415.00 105.62 279.35 3.92 275.43 0.00 0.00
August 527.23 124.01 365.29 68.50 296.79 0.00 0.00
September 845.25 205.23 603.29 315.61 287.68 0.00 0.00
October 1228.95 323.36 952.20 704.47 247.73 0.00 0.00
November 1286.92 416.71 1067.01 823.17 243.85 0.00 0.00
December 1355.15 494.51 1140.01 943.60 196.40 0.00 0.00
               
Annual Sum or Average 850.76 288.87 679.99 415.21 264.78 0.00 0.00
Minimum of Months 303.29 105.62 267.29 0.40 196.40 0.00 0.00
Maximum of Months 1355.15 494.51 1140.01 943.60 308.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 190.02 235.47 205.09 115.66 89.43 0.00 0.00
February 248.71 211.34 246.90 133.23 113.67 0.00 0.00
March 363.23 169.00 324.24 184.86 139.38 0.00 0.00
April 530.04 123.71 441.28 250.77 190.52 0.00 0.00
May 521.73 100.86 416.27 234.36 181.91 0.00 0.00
June 616.82 73.26 449.84 274.24 175.60 0.00 0.00
July 587.63 58.76 414.14 234.17 179.98 0.00 0.00
August 567.04 64.97 412.04 224.90 187.14 0.00 0.00
September 448.76 101.49 345.65 192.36 153.29 0.00 0.00
October 350.03 161.10 304.98 193.64 111.34 0.00 0.00
November 237.15 211.35 239.56 141.66 97.90 0.00 0.00
December 178.29 252.73 194.99 119.26 75.73 0.00 0.00
               
Annual Sum or Average 403.96 146.69 333.23 191.82 141.41 0.00 0.00
Minimum of Months 178.29 58.76 194.99 115.66 75.73 0.00 0.00
Maximum of Months 616.82 252.73 449.84 274.24 190.52 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 37.43 374.93 110.40 0.00 110.40 0.00 0.00
February 71.62 331.71 138.68 0.00 138.68 0.00 0.00
March 136.29 257.16 173.90 0.00 173.90 0.00 0.00
April 203.31 179.23 222.29 1.78 220.51 0.00 0.00
May 258.75 140.98 238.93 13.96 224.97 0.00 0.00
June 378.90 105.48 269.58 40.96 228.62 0.00 0.00
July 371.35 82.12 248.23 18.49 229.73 0.00 0.00
August 319.56 92.02 232.98 4.77 228.21 0.00 0.00
September 220.38 151.21 186.88 0.05 186.83 0.00 0.00
October 104.14 246.09 140.21 0.00 140.21 0.00 0.00
November 42.23 320.33 118.30 0.00 118.30 0.00 0.00
December 14.35 399.41 94.92 0.00 94.92 0.00 0.00
               
Annual Sum or Average 180.41 222.88 181.43 6.68 174.75 0.00 0.00
Minimum of Months 14.35 82.12 94.92 0.00 94.92 0.00 0.00
Maximum of Months 378.90 399.41 269.58 40.96 229.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 213.77 253.27 211.59 121.62 89.97 0.00 0.00
February 291.71 228.04 270.82 156.98 113.84 0.00 0.00
March 339.62 181.07 298.99 159.28 139.72 0.00 0.00
April 453.30 133.46 379.54 200.67 178.88 0.00 0.00
May 443.98 107.11 355.83 180.11 175.72 0.00 0.00
June 531.55 84.02 382.08 210.06 172.02 0.00 0.00
July 491.59 63.65 340.81 162.60 178.21 0.00 0.00
August 490.86 72.70 351.67 159.82 191.84 0.00 0.00
September 422.05 111.34 320.41 167.16 153.25 0.00 0.00
October 354.88 176.13 299.44 186.32 113.12 0.00 0.00
November 242.10 221.32 236.05 139.67 96.37 0.00 0.00
December 200.81 266.10 205.51 129.50 76.01 0.00 0.00
               
Annual Sum or Average 373.26 157.84 304.40 164.38 140.02 0.00 0.00
Minimum of Months 200.81 63.65 205.51 121.62 76.01 0.00 0.00
Maximum of Months 531.55 266.10 382.08 210.06 191.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.333637E+10 0.126389E+10 0.280827E+10 0.219738E+10 0.610890E+09 0.00 0.00
February 0.302193E+10 0.103511E+10 0.248038E+10 0.182333E+10 0.657049E+09 0.00 0.00
March 0.234462E+10 0.912605E+09 0.189023E+10 0.112610E+10 0.764135E+09 0.00 0.00
April 0.138527E+10 0.630491E+09 0.116378E+10 0.364275E+09 0.799509E+09 0.00 0.00
May 0.812336E+09 0.494636E+09 0.748882E+09 21939005.07 0.726943E+09 0.00 0.00
June 0.957535E+09 0.355311E+09 0.692821E+09 1025423.03 0.691796E+09 0.00 0.00
July 0.111153E+10 0.282897E+09 0.748217E+09 10506162.31 0.737711E+09 0.00 0.00
August 0.141213E+10 0.332161E+09 0.978405E+09 0.183470E+09 0.794935E+09 0.00 0.00
September 0.219090E+10 0.531947E+09 0.156372E+10 0.818066E+09 0.745655E+09 0.00 0.00
October 0.329162E+10 0.866088E+09 0.255038E+10 0.188686E+10 0.663520E+09 0.00 0.00
November 0.333569E+10 0.108010E+10 0.276570E+10 0.213365E+10 0.632053E+09 0.00 0.00
December 0.362962E+10 0.132451E+10 0.305339E+10 0.252735E+10 0.526044E+09 0.00 0.00
               
Annual Sum or Average 0.268295E+11 0.910975E+10 0.214442E+11 0.130939E+11 0.835024E+10 0.00 0.00
Minimum of Months 0.812336E+09 0.282897E+09 0.692821E+09 1025423.03 0.526044E+09 0.00 0.00
Maximum of Months 0.362962E+10 0.132451E+10 0.305339E+10 0.252735E+10 0.799509E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.508942E+09 0.630671E+09 0.549301E+09 0.309783E+09 0.239518E+09 0.00 0.00
February 0.601682E+09 0.511274E+09 0.597303E+09 0.322305E+09 0.274998E+09 0.00 0.00
March 0.972875E+09 0.452639E+09 0.868453E+09 0.495133E+09 0.373320E+09 0.00 0.00
April 0.137386E+10 0.320655E+09 0.114381E+10 0.649983E+09 0.493825E+09 0.00 0.00
May 0.139741E+10 0.270151E+09 0.111494E+10 0.627709E+09 0.487230E+09 0.00 0.00
June 0.159879E+10 0.189881E+09 0.116599E+10 0.710830E+09 0.455161E+09 0.00 0.00
July 0.157392E+10 0.157372E+09 0.110924E+10 0.627190E+09 0.482052E+09 0.00 0.00
August 0.151876E+10 0.174013E+09 0.110361E+10 0.602362E+09 0.501243E+09 0.00 0.00
September 0.116319E+10 0.263053E+09 0.895929E+09 0.498603E+09 0.397327E+09 0.00 0.00
October 0.937532E+09 0.431499E+09 0.816858E+09 0.518652E+09 0.298206E+09 0.00 0.00
November 0.614689E+09 0.547819E+09 0.620930E+09 0.367184E+09 0.253746E+09 0.00 0.00
December 0.477545E+09 0.676904E+09 0.522262E+09 0.319421E+09 0.202841E+09 0.00 0.00
               
Annual Sum or Average 0.127392E+11 0.462593E+10 0.105086E+11 0.604915E+10 0.445947E+10 0.00 0.00
Minimum of Months 0.477545E+09 0.157372E+09 0.522262E+09 0.309783E+09 0.202841E+09 0.00 0.00
Maximum of Months 0.159879E+10 0.676904E+09 0.116599E+10 0.710830E+09 0.501243E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100256E+09 0.100421E+10 0.295686E+09 0.00 0.295686E+09 0.00 0.00
February 0.173259E+09 0.802478E+09 0.335492E+09 0.00 0.335492E+09 0.00 0.00
March 0.365048E+09 0.688788E+09 0.465765E+09 0.00 0.465765E+09 0.00 0.00
April 0.526988E+09 0.464570E+09 0.576178E+09 4617461.63 0.571561E+09 0.00 0.00
May 0.693042E+09 0.377606E+09 0.639952E+09 37398632.26 0.602553E+09 0.00 0.00
June 0.982117E+09 0.273417E+09 0.698753E+09 0.106176E+09 0.592577E+09 0.00 0.00
July 0.994627E+09 0.219948E+09 0.664846E+09 49527709.65 0.615319E+09 0.00 0.00
August 0.855909E+09 0.246466E+09 0.624001E+09 12766778.86 0.611234E+09 0.00 0.00
September 0.571213E+09 0.391936E+09 0.484384E+09 118758.97 0.484265E+09 0.00 0.00
October 0.278923E+09 0.659134E+09 0.375534E+09 0.00 0.375534E+09 0.00 0.00
November 0.109450E+09 0.830293E+09 0.306635E+09 0.00 0.306635E+09 0.00 0.00
December 38424110.60 0.106978E+10 0.254222E+09 0.00 0.254222E+09 0.00 0.00
               
Annual Sum or Average 0.568925E+10 0.702862E+10 0.572145E+10 0.210606E+09 0.551084E+10 0.00 0.00
Minimum of Months 38424110.60 0.219948E+09 0.254222E+09 0.00 0.254222E+09 0.00 0.00
Maximum of Months 0.994627E+09 0.106978E+10 0.698753E+09 0.106176E+09 0.615319E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.572552E+09 0.678354E+09 0.566718E+09 0.325747E+09 0.240972E+09 0.00 0.00
February 0.705707E+09 0.551676E+09 0.655156E+09 0.379755E+09 0.275402E+09 0.00 0.00
March 0.909625E+09 0.484989E+09 0.800823E+09 0.426603E+09 0.374220E+09 0.00 0.00
April 0.117495E+10 0.345929E+09 0.983777E+09 0.520130E+09 0.463648E+09 0.00 0.00
May 0.118917E+10 0.286876E+09 0.953066E+09 0.482417E+09 0.470649E+09 0.00 0.00
June 0.137778E+10 0.217767E+09 0.990347E+09 0.544484E+09 0.445863E+09 0.00 0.00
July 0.131667E+10 0.170482E+09 0.912823E+09 0.435497E+09 0.477326E+09 0.00 0.00
August 0.131472E+10 0.194732E+09 0.941910E+09 0.428075E+09 0.513836E+09 0.00 0.00
September 0.109396E+10 0.288590E+09 0.830514E+09 0.433288E+09 0.397226E+09 0.00 0.00
October 0.950516E+09 0.471747E+09 0.802012E+09 0.499029E+09 0.302983E+09 0.00 0.00
November 0.627531E+09 0.573665E+09 0.611837E+09 0.362035E+09 0.249802E+09 0.00 0.00
December 0.537857E+09 0.712732E+09 0.550437E+09 0.346848E+09 0.203589E+09 0.00 0.00
               
Annual Sum or Average 0.117710E+11 0.497754E+10 0.959942E+10 0.518391E+10 0.441551E+10 0.00 0.00
Minimum of Months 0.537857E+09 0.170482E+09 0.550437E+09 0.325747E+09 0.203589E+09 0.00 0.00
Maximum of Months 0.137778E+10 0.712732E+09 0.990347E+09 0.544484E+09 0.513836E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 2.60 -1.3 -7.5 3.29 -12.5 38.91 220.14 0.00
February 4.28 0.13 -5.8 3.80 -10.7 48.21 247.44 0.00
March 8.76 2.64 -5.5 4.72 -6.0 66.36 249.43 0.00
April 13.90 4.70 -6.4 4.61 -1.8 81.54 308.98 0.00
May 17.82 8.42 -1.1 4.68 3.61 77.67 310.50 0.00
June 23.21 12.42 4.15 4.28 9.16 70.88 348.57 0.00
July 25.63 16.13 10.74 4.00 14.07 80.74 308.61 0.00
August 24.08 15.39 10.38 3.96 13.00 86.20 290.42 0.00
September 20.49 12.87 7.70 3.48 8.22 67.00 274.65 0.00
October 13.71 6.72 -0.1 3.54 -0.8 42.11 283.53 0.00
November 6.96 1.72 -4.9 3.43 -7.6 39.44 239.51 0.01
December 2.07 -2.2 -8.9 2.95 -13.5 27.44 240.96 0.00
                 
Annual Sum or Average 13.68 6.50 -0.6 3.90 -0.3 60.60 276.96 0.00
Minimum of Months 2.07 -2.2 -8.9 2.95 -13.5 27.44 220.14 0.00
Maximum of Months 25.63 16.13 10.74 4.72 14.07 86.20 348.57 0.01



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.10 01-JAN-14:00 5.83 -6.7 5.20 -2.3 27.00 880.00
February 22.20 14-FEB-15:00 7.86 -10.0 4.60 4.72 61.50 778.50
March 22.80 08-MAR-13:00 9.68 -2.8 3.60 4.92 122.50 851.50
April 26.10 13-APR-16:00 10.32 -4.4 5.20 7.55 95.00 507.00
May 30.00 19-MAY-15:20 12.71 -1.5 8.93 13.35 108.33 887.00
June 38.90 28-JUN-15:00 14.16 -8.9 3.10 20.75 70.00 888.00
July 38.30 22-JUL-14:00 16.71 3.30 5.20 24.16 99.00 907.50
August 35.00 01-AUG-14:00 16.30 4.40 2.60 19.52 113.00 840.50
September 32.80 03-SEP-13:00 16.76 7.80 3.60 21.78 263.50 532.50
October 28.90 01-OCT-15:00 13.26 1.70 4.10 15.94 85.00 435.00
November 19.40 09-NOV-13:00 9.81 1.70 10.80 8.35 157.50 0.00
December 13.30 24-DEC-14:00 4.02 -8.3 8.20 -2.5 40.50 792.50
                 
Annual Sum or Average                
Minimum of Months 13.30   4.02 -10.0 2.60 -2.5 27.00 0.00
Maximum of Months 38.90   16.76 7.80 10.80 24.16 263.50 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -8.3 20-JAN-01:00 -8.3 -8.3 2.10 -25.6 0.00 0.00
February -6.7 04-FEB-06:10 -8.2 -11.7 5.10 -25.0 0.00 0.00
March -3.9 05-MAR-06:00 -5.7 -9.4 1.50 -21.6 17.00 434.50
April 1.70 06-APR-05:00 -2.4 -8.3 2.60 -12.9 28.00 215.00
May 4.40 07-MAY-04:00 -1.0 -8.3 1.50 -13.7 0.00 0.00
June 7.80 09-JUN-04:40 5.54 3.30 4.83 -7.8 0.00 0.00
July 16.10 08-JUL-02:00 14.67 13.90 0.00 4.72 0.00 0.00
August 12.80 31-AUG-05:00 10.77 9.40 3.10 -1.7 24.50 228.50
September 10.60 09-SEP-05:00 9.95 9.40 2.10 -2.5 15.50 177.00
October -2.8 26-OCT-04:10 -4.1 -6.1 2.42 -17.7 0.00 0.00
November -4.4 27-NOV-05:00 -6.9 -11.7 2.60 -22.7 0.00 0.00
December -9.4 15-DEC-04:00 -12.1 -21.7 0.00 -29.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -9.4   -12.1 -21.7 0.00 -29.7 0.00 0.00
Maximum of Months 16.10   14.67 13.90 5.10 4.72 28.00 434.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 6.84 05-JAN-13:00 16.10 -2.8 3.10 -0.1 62.00 873.00
February 7.86 14-FEB-15:00 22.20 -10.0 4.60 4.72 61.50 778.50
March 9.68 08-MAR-13:00 22.80 -2.8 3.60 4.92 122.50 851.50
April 10.95 14-APR-15:00 24.40 -0.6 8.20 17.21 237.00 154.00
May 15.08 22-MAY-12:30 28.60 6.40 5.15 16.76 167.00 0.00
June 18.19 24-JUN-13:00 31.70 11.70 2.60 19.17 130.00 891.50
July 19.21 31-JUL-14:00 32.80 12.80 6.20 22.98 264.50 624.50
August 19.18 26-AUG-12:00 27.80 15.60 3.60 17.03 289.00 426.50
September 18.19 05-SEP-12:00 23.90 15.60 3.10 13.35 196.50 796.00
October 16.16 11-OCT-10:00 23.90 12.20 13.40 13.73 219.50 450.00
November 9.81 09-NOV-13:00 19.40 1.70 10.80 8.35 157.50 0.00
December 4.92 01-DEC-15:00 12.80 -3.9 2.10 1.58 50.00 276.00
                 
Annual Sum or Average                
Minimum of Months 4.92   12.80 -10.0 2.10 -0.1 50.00 0.00
Maximum of Months 19.21   32.80 15.60 13.40 22.98 289.00 891.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.6 28-JAN-17:00 6.10 3.01 4.60 -5.0 0.00 0.00
February 2.20 17-FEB-10:00 7.20 4.72 3.10 -4.1 212.50 561.00
March 5.60 28-MAR-17:10 8.80 7.05 4.60 3.37 35.00 0.67
April 7.20 15-APR-06:00 13.30 9.79 7.20 6.35 116.00 422.00
May 13.90 24-MAY-14:00 16.70 14.90 4.60 11.07 128.00 0.00
June 13.30 30-JUN-13:00 26.70 17.72 6.70 20.75 170.00 126.50
July 17.80 01-JUL-13:00 22.20 19.05 3.60 13.91 361.00 125.00
August 17.20 26-AUG-09:00 21.70 18.59 2.60 11.65 243.50 681.50
September 15.60 05-SEP-11:00 22.20 17.61 3.10 12.79 231.00 705.00
October 13.90 02-OCT-16:00 20.60 16.04 6.20 13.54 38.50 65.00
November 6.10 09-NOV-21:00 8.90 7.38 11.80 3.69 0.00 0.00
December 1.10 25-DEC-08:00 2.20 1.65 2.10 -4.1 54.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.6   2.20 1.65 2.10 -5.0 0.00 0.00
Maximum of Months 17.80   26.70 19.05 11.80 20.75 361.00 705.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.28 25.87 0.00
February 18.00 13.00 16.00 10.91 34.17 0.00
March 18.00 13.00 16.00 12.10 41.92 0.00
April 18.00 13.00 16.00 14.59 56.24 0.00
May 18.00 13.00 16.00 17.73 59.47 0.00
June 18.00 13.00 16.00 20.66 62.98 0.00
July 18.00 13.00 16.00 22.59 61.22 0.00
August 18.00 13.00 16.00 23.01 57.83 0.00
September 18.00 13.00 16.00 21.78 48.11 0.00
October 18.00 13.00 16.00 19.25 37.89 0.00
November 18.00 13.00 16.00 16.11 28.37 0.00
December 18.00 13.00 16.00 13.20 24.17 0.00
             
Annual Sum or Average 18.00 13.00 16.00 16.97 44.90 0.00
Minimum of Months 18.00 13.00 16.00 10.91 24.17 0.00
Maximum of Months 18.00 13.00 16.00 23.01 62.98 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.560137E+09 -485095936.7 0.00 0.00 744.00 0.00 -75041506.1 58.99 0.00 0.00
February 0.509261E+09 -442331484.0 0.00 0.00 672.00 0.00 -66929042.5 58.99 0.00 0.00
March 0.593446E+09 -521924675.4 0.00 0.00 744.00 0.00 -71521483.7 58.99 0.00 0.00
April 0.496526E+09 -429996380.0 0.00 0.00 720.00 0.00 -66529398.3 58.98 0.00 0.00
May 0.507579E+09 -440585826.1 0.00 0.00 744.00 0.00 -66993456.3 58.99 0.00 0.00
June 0.471007E+09 -407824474.9 0.00 0.00 720.00 0.00 -63182847.0 58.97 0.00 0.00
July 0.415897E+09 -351972960.6 0.00 0.00 744.00 0.00 -63924426.3 59.00 0.00 0.00
August 0.465145E+09 -400728056.5 0.00 0.00 744.00 0.00 -64417311.5 58.99 0.00 0.00
September 0.423714E+09 -360785190.8 0.00 0.00 720.00 0.00 -62929243.1 58.99 0.00 0.00
October 0.471304E+09 -404345828.2 0.00 0.00 744.00 0.00 -66958026.4 58.98 0.00 0.00
November 0.503971E+09 -435803800.8 0.00 0.00 720.00 0.00 -68166751.3 59.01 0.00 0.00
December 0.517548E+09 -442916807.8 0.00 0.00 744.00 0.00 -74631618.1 59.00 0.00 0.00
                     
Annual Sum or Average 0.593554E+10 -0.512431E+10 0.00 0.00 8760.00 0.00 -811225110.6 58.99 0.00 0.00
Minimum of Months 0.415897E+09 -521924675.4 0.00 0.00 672.00 0.00 -75041506.1 58.97 0.00 0.00
Maximum of Months 0.593446E+09 -351972960.6 0.00 0.00 744.00 0.00 -62929243.1 59.01 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.78 0.76 01-JAN-07:49 2259.29 27.37 159.17 262.17 775.98 24.37 184.17 235.33
February 282.00 0.78 0.76 01-FEB-08:09 2685.66 25.50 123.00 231.67 806.86 24.25 171.67 225.83
March 351.33 0.79 0.76 01-MAR-07:30 597.87 17.43 5.00 250.00 474.73 21.70 162.33 214.33
April 381.83 0.80 0.76 01-APR-08:30 466.05 17.63 0.00 250.50 354.90 21.92 254.50 186.83
May 378.00 0.80 0.76 01-MAY-07:10 343.34 16.71 0.00 151.50 258.95 21.03 199.00 50.33
June 412.83 0.84 0.76 01-JUN-06:00 272.32 15.50 0.00 89.83 207.86 19.94 102.83 44.50
July 395.33 0.82 0.76 01-JUL-07:40 331.41 16.45 0.00 139.50 250.59 20.85 165.00 70.83
August 408.83 0.80 0.76 01-AUG-07:19 425.16 17.27 0.00 235.33 317.66 21.59 248.17 149.17
September 359.33 0.80 0.76 01-SEP-07:19 675.46 17.88 11.00 245.50 419.99 21.72 193.83 204.00
October 329.00 0.78 0.76 01-OCT-07:10 2549.51 23.50 115.17 274.00 584.43 21.51 145.50 231.33
November 284.17 0.77 0.76 01-NOV-07:10 2686.20 28.17 153.17 255.50 952.25 24.98 203.17 226.00
December 265.67 0.77 0.76 01-DEC-07:49 2542.38 28.55 146.67 243.33 2293.89 30.17 182.83 227.50
                         
Annual Sum or Average 4149.83 0.80     1179.28 20.32 713.17 2628.83 578.25 22.51 2213.00 2066.00
Minimum of Months 265.67 0.77 0.76   272.32 15.50 0.00 89.83 207.86 19.94 102.83 44.50
Maximum of Months 412.83 0.84 0.76   2686.20 28.55 159.17 274.00 2293.89 30.17 254.50 235.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.84 0.76 01-JAN-07:00 1506.47 22.15 101.00 117.17 862.31 21.12 89.33 85.50
February 282.00 0.84 0.76 01-FEB-07:00 1314.51 20.06 71.17 110.83 1118.40 21.02 93.33 94.00
March 351.33 0.83 0.76 01-MAR-07:30 440.82 16.58 31.50 154.17 360.07 16.15 17.17 118.50
April 381.83 0.82 0.76 01-APR-06:30 479.78 16.49 4.67 179.17 428.74 16.27 0.00 147.17
May 378.00 0.82 0.76 01-MAY-06:40 440.98 15.61 0.00 155.67 403.45 15.40 0.00 135.83
June 412.83 0.83 0.76 01-JUN-05:00 386.83 14.35 0.00 155.67 356.12 14.12 0.00 135.83
July 395.33 0.82 0.76 01-JUL-07:19 421.88 15.39 1.17 169.33 381.56 15.15 0.00 145.83
August 408.83 0.81 0.76 01-AUG-06:19 437.00 16.23 4.50 178.83 387.09 15.94 1.17 145.50
September 359.33 0.83 0.76 01-SEP-06:49 408.18 16.39 20.00 146.17 416.91 16.30 14.17 115.33
October 329.00 0.84 0.76 01-OCT-06:49 523.20 16.33 23.67 130.67 977.60 18.98 63.17 104.83
November 284.17 0.83 0.76 01-NOV-06:00 1291.14 20.87 76.00 113.33 726.54 20.61 76.67 94.00
December 265.67 0.85 0.76 01-DEC-08:09 1920.83 22.48 89.83 96.33 457.53 19.00 60.50 80.00
                         
Annual Sum or Average 4149.83 0.83     730.34 17.39 423.50 1707.33 547.89 17.19 415.50 1402.33
Minimum of Months 265.67 0.81 0.76   386.83 14.35 0.00 96.33 356.12 14.12 0.00 80.00
Maximum of Months 412.83 0.85 0.76   1920.83 22.48 101.00 179.17 1118.40 21.12 93.33 147.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.91 0.76 12-JAN-12:20 143.79 0.00 0.00 0.00 109.26 0.00 0.00 0.00
February 282.00 0.89 0.76 01-FEB-14:30 170.29 0.00 0.00 0.00 130.58 0.00 0.00 0.00
March 351.33 0.87 0.76 01-MAR-10:09 203.56 0.00 0.00 14.33 148.43 0.00 0.00 0.00
April 381.83 0.83 0.76 01-APR-11:30 262.92 0.00 0.00 26.83 189.23 0.00 0.00 0.00
May 378.00 0.81 0.76 01-MAY-06:00 333.02 0.00 0.00 84.67 205.72 0.00 0.00 0.50
June 412.83 0.83 0.76 01-JUN-06:19 273.32 0.00 0.00 85.50 210.94 0.00 0.00 13.00
July 395.33 0.82 0.76 01-JUL-07:40 295.73 0.00 0.00 99.50 216.30 0.00 0.00 8.00
August 408.83 0.82 0.76 01-AUG-06:10 302.96 0.00 0.00 101.83 200.48 0.00 0.00 0.00
September 359.33 0.86 0.76 01-SEP-14:20 219.53 0.00 0.00 19.33 160.66 0.00 0.00 0.00
October 329.00 0.90 0.76 02-OCT-13:20 155.03 0.00 0.00 0.17 120.31 0.00 0.00 0.00
November 284.17 0.90 0.76 08-NOV-13:30 153.77 0.00 0.00 0.00 119.91 0.00 0.00 0.00
December 265.67 0.92 0.84 01-DEC-11:30 125.47 0.00 0.00 0.00 101.46 0.00 0.00 0.00
                         
Annual Sum or Average 4149.83 0.86     228.85 0.00 0.00 432.17 165.02 0.00 0.00 21.50
Minimum of Months 265.67 0.81 0.76   125.47 0.00 0.00 0.00 101.46 0.00 0.00 0.00
Maximum of Months 412.83 0.92 0.84   333.02 0.00 0.00 101.83 216.30 0.00 0.00 13.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.84 0.76 01-JAN-13:39 1005.47 20.44 74.83 113.83 559.58 19.65 68.83 80.00
February 282.00 0.83 0.76 01-FEB-11:39 1351.21 20.37 74.17 122.00 1049.84 21.31 89.17 99.67
March 351.33 0.83 0.76 01-MAR-09:39 395.71 16.52 32.83 147.83 327.42 16.06 15.00 108.33
April 381.83 0.82 0.76 01-APR-11:09 430.44 16.48 4.33 164.67 372.95 16.23 0.00 128.17
May 378.00 0.82 0.76 01-MAY-12:30 393.43 15.70 0.00 133.33 348.78 15.48 0.00 112.00
June 412.83 0.84 0.76 01-JUN-08:30 364.99 14.44 0.00 149.33 352.48 14.17 0.00 133.33
July 395.33 0.83 0.76 01-JUL-08:20 391.62 15.55 0.33 161.00 358.99 15.26 0.00 135.00
August 408.83 0.83 0.76 01-AUG-12:20 427.18 16.36 6.67 172.00 369.39 16.04 2.17 143.67
September 359.33 0.83 0.76 01-SEP-12:20 411.17 16.41 30.00 147.17 376.82 16.25 16.33 120.83
October 329.00 0.84 0.76 01-OCT-12:39 630.84 16.57 35.67 130.00 824.15 18.61 67.83 106.67
November 284.17 0.83 0.76 01-NOV-12:50 1869.84 22.74 92.33 108.33 547.46 20.31 70.67 90.00
December 265.67 0.84 0.76 01-DEC-11:09 1804.11 22.71 84.17 94.00 496.18 20.26 63.67 80.50
                         
Annual Sum or Average 4149.83 0.83     718.67 17.49 435.33 1643.50 478.68 17.15 393.67 1338.17
Minimum of Months 265.67 0.82 0.76   364.99 14.44 0.00 94.00 327.42 14.17 0.00 80.00
Maximum of Months 412.83 0.84 0.76   1869.84 22.74 92.33 172.00 1049.84 21.31 89.17 143.67



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.246379E+09 5126.21 11-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.115629E+09 5486.37 21-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 9090118.46 5456.25 07-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1091290.05 3670.56 27-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.147746E+09 5020.79 11-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.519934E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.246379E+09 5486.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.816229E+09 5661.72 11-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.548722E+09 5976.47 21-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.336351E+09 7066.53 08-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 85306623.68 6602.40 24-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 10963856.25 6754.24 08-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 48400699.46 4398.72 25-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 85401092.28 5494.53 13-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.518528E+09 5545.29 11-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.244990E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.816229E+09 7066.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.653314E+09 4510.66 11-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.433605E+09 4861.38 21-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 88821344.54 5509.20 20-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 363125.06 1039.27 06-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3582644.07 3327.47 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 24697852.85 3998.35 29-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.497238E+09 4502.34 11-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170162E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.653314E+09 5509.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.176686E+10 5521.77 11-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.129027E+10 5909.72 21-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.458811E+09 6891.85 08-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 33141619.65 6626.67 10-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 208349.18 2083.49 05-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 27543514.47 5036.40 30-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 0.272019E+09 6264.92 14-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 0.155480E+10 5408.22 11-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.540365E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176686E+10 6891.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.659094E+09 5473.12 11-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.464404E+09 5898.68 21-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.126686E+09 6220.28 20-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 1998859.35 3911.28 24-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 22116.12 221.16 05-MAY-07:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 6538899.06 3393.19 26-OCT-07:03 0.00 0.00 0.00 0.00 0.00
November 46478508.19 4324.04 13-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.518953E+09 5457.23 11-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.182418E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.659094E+09 6220.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 15274195.37 3184.94 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 9699544.56 3184.94 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 1086368.01 3184.94 06-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 199531.23 1241.29 27-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 12458798.43 3184.94 11-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 38718437.60     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 15274195.37 3184.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122245E+09 5356.88 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 74525993.16 5356.88 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 12401908.23 5356.88 30-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 277926.04 1132.15 06-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1457751.43 5175.05 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 1534803.86 5356.88 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 95690472.30 5356.88 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.308134E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122245E+09 5356.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 18134666.58 3378.71 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 12489489.16 3378.71 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 3306990.64 3378.71 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 11902.56 79.35 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 910740.60 3378.71 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 12837557.76 3378.71 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 47691347.30     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18134666.58 3378.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111221E+09 5407.91 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 68511803.21 5407.91 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 12413273.40 5407.91 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 144579.19 794.42 06-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1323375.01 2672.14 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 9683169.28 5407.91 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 68541836.18 5407.91 05-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.271840E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111221E+09 5407.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 12225854.41 3378.71 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 8333571.84 3378.71 01-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 3052519.84 3378.71 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 712581.65 3378.71 27-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 8801225.80 3378.71 04-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 33125753.54     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 12225854.41 3378.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 766653.53 744792.85 165.69 05-JAN-16:05 161.61 0.00
February 0.00 0.00 38210281.46 38046378.58 1233.14 15-FEB-16:54 1233.14 0.00
March 0.00 0.00 0.260404E+09 0.257209E+09 1586.31 16-MAR-14:23 1534.44 0.00
April 0.00 0.00 0.101371E+10 0.101026E+10 5827.20 14-APR-07:02 5827.20 0.00
May 0.00 0.00 0.211229E+10 0.201045E+10 6291.05 24-MAY-07:01 4901.43 0.00
June 0.00 0.00 0.354979E+10 0.335058E+10 6291.56 30-JUN-06:03 5546.26 0.00
July 0.00 0.00 0.420745E+10 0.371809E+10 6498.52 10-JUL-06:01 5171.02 0.00
August 0.00 0.00 0.452899E+10 0.393851E+10 6491.38 14-AUG-06:01 5081.33 0.00
September 0.00 0.00 0.322661E+10 0.287062E+10 6420.58 06-SEP-06:03 4834.07 0.00
October 0.00 0.00 0.195378E+10 0.181490E+10 6325.90 03-OCT-06:03 5081.77 0.00
November 0.00 0.00 0.453594E+09 0.432638E+09 2322.56 02-NOV-16:00 2059.65 0.00
December 0.00 0.00 10566634.44 10441334.07 812.53 01-DEC-16:07 805.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.213562E+11 0.194525E+11       0.00
Minimum of Months 0.00 0.00 766653.53 744792.85 165.69   161.61 0.00
Maximum of Months 0.00 0.00 0.452899E+10 0.393851E+10 6498.52   5827.20 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.290456E+09 0.290456E+09 2495.75 03-JAN-14:45 2495.75 0.00
February 0.00 0.00 0.275738E+09 0.275738E+09 3625.49 14-FEB-14:55 3625.49 0.00
March 0.00 0.00 0.335606E+09 0.335606E+09 2493.73 13-MAR-14:25 2493.73 0.00
April 0.00 0.00 0.653962E+09 0.653962E+09 3217.84 28-APR-14:27 3217.84 0.00
May 0.00 0.00 0.111388E+10 0.109360E+10 3568.56 22-MAY-07:02 3337.92 0.00
June 0.00 0.00 0.268167E+10 0.261972E+10 6831.75 29-JUN-06:01 6633.38 0.00
July 0.00 0.00 0.362398E+10 0.332825E+10 7159.49 17-JUL-06:01 5540.99 0.00
August 0.00 0.00 0.408587E+10 0.372690E+10 7254.54 14-AUG-06:01 5429.89 0.00
September 0.00 0.00 0.338735E+10 0.320692E+10 7103.59 05-SEP-06:01 5735.62 0.00
October 0.00 0.00 0.262708E+10 0.256534E+10 6947.24 11-OCT-07:02 5655.41 0.00
November 0.00 0.00 0.102778E+10 0.102633E+10 4822.49 01-NOV-13:10 4822.49 0.00
December 0.00 0.00 0.210491E+09 0.210491E+09 2178.30 19-DEC-13:10 2178.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.203139E+11 0.193333E+11       0.00
Minimum of Months 0.00 0.00 0.210491E+09 0.210491E+09 2178.30   2178.30 0.00
Maximum of Months 0.00 0.00 0.408587E+10 0.372690E+10 7254.54   6633.38 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 9002181.29 9002181.29 498.60 14-FEB-16:00 498.60 0.00
March 0.00 0.00 76680549.95 76680549.95 692.64 08-MAR-15:57 692.64 0.00
April 0.00 0.00 0.680295E+09 0.680295E+09 5235.13 27-APR-07:02 5235.13 0.00
May 0.00 0.00 0.126707E+10 0.124899E+10 5562.67 24-MAY-07:01 4882.95 0.00
June 0.00 0.00 0.242512E+10 0.238555E+10 5609.55 05-JUN-07:02 4713.10 0.00
July 0.00 0.00 0.288583E+10 0.272564E+10 5842.28 17-JUL-06:01 4760.00 0.00
August 0.00 0.00 0.302907E+10 0.283730E+10 5876.63 14-AUG-06:01 4646.52 0.00
September 0.00 0.00 0.202782E+10 0.194109E+10 5794.95 05-SEP-06:01 4796.91 0.00
October 0.00 0.00 0.111231E+10 0.108534E+10 5641.26 11-OCT-07:02 4765.78 0.00
November 0.00 0.00 0.134089E+09 0.133885E+09 1380.04 01-NOV-10:08 1380.04 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.136473E+11 0.131238E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.302907E+10 0.283730E+10 5876.63   5235.13 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.352633E+09 0.352633E+09 2235.72 28-APR-15:24 2235.72 0.00
May 0.00 0.00 0.113924E+10 0.111090E+10 6551.82 22-MAY-07:02 6248.13 0.00
June 0.00 0.00 0.273461E+10 0.266459E+10 6677.72 29-JUN-06:01 6542.34 0.00
July 0.00 0.00 0.347318E+10 0.320237E+10 6991.31 17-JUL-06:01 5443.72 0.00
August 0.00 0.00 0.355243E+10 0.323425E+10 7067.42 14-AUG-06:01 5305.55 0.00
September 0.00 0.00 0.221495E+10 0.206214E+10 6905.26 05-SEP-06:01 5484.92 0.00
October 0.00 0.00 0.965017E+09 0.918961E+09 6749.10 11-OCT-07:02 5505.78 0.00
November 0.00 0.00 39330240.00 38417915.38 959.80 02-NOV-15:50 911.78 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.144714E+11 0.135843E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.355243E+10 0.323425E+10 7067.42   6542.34 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4953742.50 4953742.50 486.54 05-JAN-16:27 486.54 0.00
February 0.00 0.00 46204784.86 46204784.86 1613.80 15-FEB-16:42 1613.80 0.00
March 0.00 0.00 0.110030E+09 0.110030E+09 1513.92 08-MAR-16:55 1513.92 0.00
April 0.00 0.00 0.532002E+09 0.532002E+09 2744.75 13-APR-16:00 2744.75 0.00
May 0.00 0.00 0.106465E+10 0.104546E+10 6658.83 22-MAY-07:02 6468.68 0.00
June 0.00 0.00 0.217117E+10 0.212351E+10 6769.02 29-JUN-06:01 6720.98 0.00
July 0.00 0.00 0.265536E+10 0.247707E+10 7113.38 17-JUL-06:01 5745.43 0.00
August 0.00 0.00 0.283248E+10 0.261877E+10 7130.75 14-AUG-06:01 5685.57 0.00
September 0.00 0.00 0.193887E+10 0.183450E+10 7029.65 05-SEP-06:01 5913.75 0.00
October 0.00 0.00 0.110733E+10 0.107388E+10 6840.91 11-OCT-07:02 5837.00 0.00
November 0.00 0.00 0.226880E+09 0.225660E+09 2177.27 02-NOV-16:00 2112.99 0.00
December 0.00 0.00 4291425.15 4291425.15 465.68 01-DEC-15:55 465.68 0.00
                 
Annual Sum or Average 0.00 0.00 0.126942E+11 0.120963E+11       0.00
Minimum of Months 0.00 0.00 4291425.15 4291425.15 465.68   465.68 0.00
Maximum of Months 0.00 0.00 0.283248E+10 0.261877E+10 7130.75   6720.98 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 269.91 645.45 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 72.09 646.10 06-FEB-12:13
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     28.45    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   269.91 646.10  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.411790E+09 0.41 419.00 02-JAN-06:01 1.12
February 0.372571E+09 0.41 419.00 01-FEB-06:02 1.11
March 0.451008E+09 0.45 419.00 01-MAR-06:05 1.11
April 0.392180E+09 0.40 419.00 03-APR-05:10 1.11
May 0.431399E+09 0.43 419.00 01-MAY-05:10 1.11
June 0.431399E+09 0.44 419.00 01-JUN-05:10 1.11
July 0.392180E+09 0.39 419.00 03-JUL-05:10 1.11
August 0.451008E+09 0.44 419.00 01-AUG-05:10 1.10
September 0.392180E+09 0.40 419.00 01-SEP-05:10 1.11
October 0.411790E+09 0.41 419.00 02-OCT-05:05 1.10
November 0.411790E+09 0.42 419.00 01-NOV-05:05 1.11
December 0.392180E+09 0.39 419.00 01-DEC-06:05 1.11
           
Annual Sum or Average 0.494147E+10 0.42      
Minimum of Months 0.372571E+09 0.39 419.00   1.10
Maximum of Months 0.451008E+09 0.45 419.00   1.12



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.454807E+09 0.41 462.77 02-JAN-06:01 1.12
February 0.411492E+09 0.41 462.77 01-FEB-06:02 1.12
March 0.498122E+09 0.45 462.77 01-MAR-06:05 1.12
April 0.433150E+09 0.40 462.77 03-APR-05:10 1.12
May 0.476465E+09 0.43 462.77 01-MAY-05:10 1.12
June 0.476465E+09 0.44 462.77 01-JUN-05:10 1.11
July 0.433469E+09 0.39 462.77 03-JUL-05:10 1.11
August 0.499022E+09 0.45 462.77 01-AUG-05:10 1.10
September 0.435356E+09 0.41 462.77 01-SEP-05:10 1.11
October 0.457433E+09 0.42 462.77 01-OCT-15:32 1.11
November 0.454807E+09 0.42 462.77 01-NOV-05:05 1.12
December 0.433150E+09 0.39 462.77 01-DEC-06:05 1.12
           
Annual Sum or Average 0.546374E+10 0.42      
Minimum of Months 0.411492E+09 0.39 462.77   1.10
Maximum of Months 0.499022E+09 0.45 462.77   1.12



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.373202E+09 0.43 376.42 02-JAN-06:01 1.12
February 0.339437E+09 0.43 376.42 01-FEB-06:02 1.12
March 0.405183E+09 0.45 376.42 01-MAR-06:05 1.12
April 0.352333E+09 0.40 376.42 03-APR-05:10 1.12
May 0.387567E+09 0.43 376.42 01-MAY-05:10 1.12
June 0.388820E+09 0.46 376.42 01-JUN-05:10 1.11
July 0.359032E+09 0.44 376.42 03-JUL-05:10 1.11
August 0.409531E+09 0.48 376.42 01-AUG-05:10 1.10
September 0.353342E+09 0.41 376.42 01-SEP-05:10 1.11
October 0.369950E+09 0.41 376.42 02-OCT-05:05 1.11
November 0.369950E+09 0.42 376.42 01-NOV-05:05 1.12
December 0.352581E+09 0.39 376.42 01-DEC-06:05 1.12
           
Annual Sum or Average 0.446093E+10 0.43      
Minimum of Months 0.339437E+09 0.39 376.42   1.10
Maximum of Months 0.409531E+09 0.48 376.42   1.12



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.459711E+09 0.47 451.33 02-JAN-06:01 1.12
February 0.413318E+09 0.44 451.33 01-FEB-06:02 1.12
March 0.485959E+09 0.45 451.33 01-MAR-06:05 1.12
April 0.422443E+09 0.40 451.33 03-APR-05:10 1.12
May 0.464687E+09 0.43 451.33 01-MAY-05:10 1.12
June 0.464687E+09 0.44 451.33 01-JUN-05:10 1.11
July 0.422818E+09 0.39 451.33 03-JUL-05:10 1.11
August 0.485809E+09 0.44 451.33 01-AUG-05:10 1.10
September 0.422443E+09 0.40 451.33 01-SEP-05:10 1.11
October 0.443565E+09 0.41 451.33 02-OCT-05:05 1.11
November 0.443565E+09 0.42 451.33 01-NOV-05:05 1.12
December 0.425473E+09 0.41 451.33 01-DEC-06:05 1.12
           
Annual Sum or Average 0.535448E+10 0.43      
Minimum of Months 0.413318E+09 0.39 451.33   1.10
Maximum of Months 0.485959E+09 0.47 451.33   1.12



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.451275E+09 0.43 456.74 02-JAN-06:01 1.12
February 0.410429E+09 0.43 456.74 01-FEB-06:02 1.12
March 0.491639E+09 0.45 456.74 01-MAR-06:05 1.12
April 0.427512E+09 0.40 456.74 03-APR-05:10 1.12
May 0.470422E+09 0.43 456.74 01-MAY-05:10 1.12
June 0.475073E+09 0.48 456.74 01-JUN-05:10 1.11
July 0.434737E+09 0.43 456.74 03-JUL-05:10 1.11
August 0.496554E+09 0.48 456.74 01-AUG-05:10 1.10
September 0.428824E+09 0.41 456.74 01-SEP-05:10 1.11
October 0.449051E+09 0.41 456.74 02-OCT-05:05 1.11
November 0.448888E+09 0.42 456.74 01-NOV-05:05 1.12
December 0.427512E+09 0.39 456.74 01-DEC-06:05 1.12
           
Annual Sum or Average 0.541192E+10 0.43      
Minimum of Months 0.410429E+09 0.39 456.74   1.10
Maximum of Months 0.496554E+09 0.48 456.74   1.12



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:01 0.00 0.00 43.35 0.00
February 0.00 0.00 0.00 01-FEB-07:01 0.00 0.00 10.83 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 10.79 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 10.79 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 10.79 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 10.79 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 10.79 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 10.79 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 10.79 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 10.79 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 10.79 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 10.79 0.00
                 
Annual Sum or Average 0.02 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 10.79 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 43.35 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.89 48.89 269.91 645.45 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 10.83 10.83 72.09 646.10 06-FEB-12:13
March 0.00 0.00 01-MAR-00:10 10.79 10.79 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 10.79 10.79 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 10.79 10.79 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 10.79 10.79 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 10.79 10.79 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 10.79 10.79 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 10.79 10.79 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 10.79 10.79 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 10.79 10.79 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 10.79 10.79 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         28.45    
Minimum of Months 0.00 0.00   10.79 10.79 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 269.91 646.10  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.563560E+09 0.00 0.00
February 0.00 0.00 0.00 0.449939E+09 0.00 0.00
March 0.00 0.00 0.00 0.519192E+09 0.00 0.00
April 0.00 0.00 0.00 0.619139E+09 0.00 0.00
May 0.00 0.00 0.00 0.896917E+09 0.00 0.00
June 0.00 0.00 0.00 0.126209E+10 0.00 0.00
July 0.00 0.00 0.00 0.135762E+10 0.00 0.00
August 0.00 0.00 0.00 0.145884E+10 0.00 0.00
September 0.00 0.00 0.00 0.109390E+10 0.00 0.00
October 0.00 0.00 0.00 0.837801E+09 0.00 0.00
November 0.00 0.00 0.00 0.522001E+09 0.00 0.00
December 0.00 0.00 0.00 0.491591E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.100726E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.449939E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.145884E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.940272E+09 0.00 0.00
February 0.00 0.00 0.00 0.728812E+09 0.00 0.00
March 0.00 0.00 0.00 0.704385E+09 0.00 0.00
April 0.00 0.00 0.00 0.611558E+09 0.00 0.00
May 0.00 0.00 0.00 0.737382E+09 0.00 0.00
June 0.00 0.00 0.00 0.113989E+10 0.00 0.00
July 0.00 0.00 0.00 0.130002E+10 0.00 0.00
August 0.00 0.00 0.00 0.143918E+10 0.00 0.00
September 0.00 0.00 0.00 0.118039E+10 0.00 0.00
October 0.00 0.00 0.00 0.103744E+10 0.00 0.00
November 0.00 0.00 0.00 0.719902E+09 0.00 0.00
December 0.00 0.00 0.00 0.742400E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.112816E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.611558E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.143918E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.716996E+09 0.00 0.00
February 0.00 0.00 0.00 0.553758E+09 0.00 0.00
March 0.00 0.00 0.00 0.463375E+09 0.00 0.00
April 0.00 0.00 0.00 0.506694E+09 0.00 0.00
May 0.00 0.00 0.00 0.673781E+09 0.00 0.00
June 0.00 0.00 0.00 0.975979E+09 0.00 0.00
July 0.00 0.00 0.00 0.105185E+10 0.00 0.00
August 0.00 0.00 0.00 0.111181E+10 0.00 0.00
September 0.00 0.00 0.00 0.810930E+09 0.00 0.00
October 0.00 0.00 0.00 0.623413E+09 0.00 0.00
November 0.00 0.00 0.00 0.419783E+09 0.00 0.00
December 0.00 0.00 0.00 0.604810E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.851318E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.419783E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.111181E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.125910E+10 0.00 0.00
February 0.00 0.00 0.00 0.958140E+09 0.00 0.00
March 0.00 0.00 0.00 0.659612E+09 0.00 0.00
April 0.00 0.00 0.00 0.516670E+09 0.00 0.00
May 0.00 0.00 0.00 0.726939E+09 0.00 0.00
June 0.00 0.00 0.00 0.113509E+10 0.00 0.00
July 0.00 0.00 0.00 0.125400E+10 0.00 0.00
August 0.00 0.00 0.00 0.131147E+10 0.00 0.00
September 0.00 0.00 0.00 0.926701E+09 0.00 0.00
October 0.00 0.00 0.00 0.678263E+09 0.00 0.00
November 0.00 0.00 0.00 0.567072E+09 0.00 0.00
December 0.00 0.00 0.00 0.110112E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.110942E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.516670E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.131147E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.797502E+09 0.00 0.00
February 0.00 0.00 0.00 0.646463E+09 0.00 0.00
March 0.00 0.00 0.00 0.571071E+09 0.00 0.00
April 0.00 0.00 0.00 0.551102E+09 0.00 0.00
May 0.00 0.00 0.00 0.716646E+09 0.00 0.00
June 0.00 0.00 0.00 0.102277E+10 0.00 0.00
July 0.00 0.00 0.00 0.109632E+10 0.00 0.00
August 0.00 0.00 0.00 0.117573E+10 0.00 0.00
September 0.00 0.00 0.00 0.877359E+09 0.00 0.00
October 0.00 0.00 0.00 0.706427E+09 0.00 0.00
November 0.00 0.00 0.00 0.528860E+09 0.00 0.00
December 0.00 0.00 0.00 0.695384E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.938564E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.528860E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.117573E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.411790E+09 766653.53 0.261653E+09 0.00 0.00 0.00 0.00 0.00
February 0.372571E+09 38210281.46 0.125328E+09 0.00 0.00 0.00 0.00 0.00
March 0.451008E+09 0.260404E+09 10176486.47 0.00 0.00 0.00 0.00 0.00
April 0.392180E+09 0.101371E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.431399E+09 0.211229E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.431399E+09 0.354979E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.392180E+09 0.420745E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.451008E+09 0.452899E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.392180E+09 0.322661E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.411790E+09 0.195378E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.411790E+09 0.453594E+09 1290821.28 0.00 0.00 0.00 0.00 0.00
December 0.392180E+09 10566634.44 0.160204E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.494147E+10 0.213562E+11 0.558653E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.372571E+09 766653.53 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.451008E+09 0.452899E+10 0.261653E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.454807E+09 0.290456E+09 0.938474E+09 0.00 0.00 0.00 0.00 0.00
February 0.411492E+09 0.275738E+09 0.623248E+09 0.00 0.00 0.00 0.00 0.00
March 0.498122E+09 0.335606E+09 0.348753E+09 0.00 0.00 0.00 0.00 0.00
April 0.433150E+09 0.653962E+09 85584549.72 0.00 0.00 0.00 0.00 0.00
May 0.476465E+09 0.111388E+10 10963856.25 0.00 0.00 0.00 0.00 0.00
June 0.476465E+09 0.268167E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.433469E+09 0.362398E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.499022E+09 0.408587E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.435356E+09 0.338735E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.457433E+09 0.262708E+10 49858450.89 0.00 0.00 0.00 0.00 0.00
November 0.454807E+09 0.102778E+10 86935896.14 0.00 0.00 0.00 0.00 0.00
December 0.433150E+09 0.210491E+09 0.614218E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.546374E+10 0.203139E+11 0.275804E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.411492E+09 0.210491E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.499022E+09 0.408587E+10 0.938474E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.373202E+09 0.00 0.671449E+09 0.00 0.00 0.00 0.00 0.00
February 0.339437E+09 9002181.29 0.446094E+09 0.00 0.00 0.00 0.00 0.00
March 0.405183E+09 76680549.95 92128335.18 0.00 0.00 0.00 0.00 0.00
April 0.352333E+09 0.680295E+09 363125.06 0.00 0.00 0.00 0.00 0.00
May 0.387567E+09 0.126707E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.388820E+09 0.242512E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.359032E+09 0.288583E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409531E+09 0.302907E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.353342E+09 0.202782E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.369950E+09 0.111231E+10 3594546.63 0.00 0.00 0.00 0.00 0.00
November 0.369950E+09 0.134089E+09 25608593.45 0.00 0.00 0.00 0.00 0.00
December 0.352581E+09 0.00 0.510075E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.446093E+10 0.136473E+11 0.174931E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339437E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409531E+09 0.302907E+10 0.671449E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.459711E+09 0.00 0.187808E+10 0.00 0.00 0.00 0.00 0.00
February 0.413318E+09 0.00 0.135878E+10 0.00 0.00 0.00 0.00 0.00
March 0.485959E+09 0.00 0.471224E+09 0.00 0.00 0.00 0.00 0.00
April 0.422443E+09 0.352633E+09 33286198.84 0.00 0.00 0.00 0.00 0.00
May 0.464687E+09 0.113924E+10 208349.18 0.00 0.00 0.00 0.00 0.00
June 0.464687E+09 0.273461E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.422818E+09 0.347318E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.485809E+09 0.355243E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.422443E+09 0.221495E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.443565E+09 0.965017E+09 28866889.48 0.00 0.00 0.00 0.00 0.00
November 0.443565E+09 39330240.00 0.281703E+09 0.00 0.00 0.00 0.00 0.00
December 0.425473E+09 0.00 0.162334E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.535448E+10 0.144714E+11 0.567549E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.413318E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.485959E+09 0.355243E+10 0.187808E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.451275E+09 4953742.50 0.671319E+09 0.00 0.00 0.00 0.00 0.00
February 0.410429E+09 46204784.86 0.472737E+09 0.00 0.00 0.00 0.00 0.00
March 0.491639E+09 0.110030E+09 0.129739E+09 0.00 0.00 0.00 0.00 0.00
April 0.427512E+09 0.532002E+09 1998859.35 0.00 0.00 0.00 0.00 0.00
May 0.470422E+09 0.106465E+10 22116.12 0.00 0.00 0.00 0.00 0.00
June 0.475073E+09 0.217117E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.434737E+09 0.265536E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.496554E+09 0.283248E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.428824E+09 0.193887E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.449051E+09 0.110733E+10 6538899.06 0.00 0.00 0.00 0.00 0.00
November 0.448888E+09 0.226880E+09 47191089.84 0.00 0.00 0.00 0.00 0.00
December 0.427512E+09 4291425.15 0.527754E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.541192E+10 0.126942E+11 0.185730E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.410429E+09 4291425.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.496554E+09 0.283248E+10 0.671319E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.411790E+09 0.00 0.00 0.151595E+09 175798.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.372571E+09 0.00 0.00 68773163.11 8594202.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.451008E+09 0.00 0.00 9835452.26 58349325.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.392180E+09 0.00 0.00 1560000.00 0.225399E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.431399E+09 0.00 0.00 0.00 0.465519E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.431399E+09 0.00 0.00 0.00 0.830694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.392180E+09 0.00 0.00 0.00 0.965438E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.451008E+09 0.00 0.00 0.00 0.100784E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.392180E+09 0.00 0.00 0.00 0.701717E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.411790E+09 0.00 0.00 4829812.03 0.421181E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.411790E+09 0.00 0.00 9441295.60 0.100771E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.392180E+09 0.00 0.00 97030019.88 2380729.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.494147E+10 0.00 0.00 0.343065E+09 0.478806E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.372571E+09 0.00 0.00 0.00 175798.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.451008E+09 0.00 0.00 0.151595E+09 0.100784E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.454807E+09 0.00 0.00 0.421654E+09 63811253.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.411492E+09 0.00 0.00 0.257452E+09 59867246.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.498122E+09 0.00 0.00 0.132083E+09 74179335.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.433150E+09 0.00 0.00 31045592.12 0.147362E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.476465E+09 0.00 0.00 3725160.34 0.257192E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.476465E+09 0.00 0.00 0.00 0.663422E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.433469E+09 0.00 0.00 0.00 0.866546E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.499022E+09 0.00 0.00 0.00 0.940157E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.435356E+09 0.00 0.00 0.00 0.745036E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.457433E+09 0.00 0.00 27085396.83 0.552923E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.454807E+09 0.00 0.00 44427942.77 0.220667E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.433150E+09 0.00 0.00 0.262379E+09 46870662.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.546374E+10 0.00 0.00 0.117985E+10 0.463803E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.411492E+09 0.00 0.00 0.00 46870662.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.499022E+09 0.00 0.00 0.421654E+09 0.940157E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.373202E+09 0.00 0.00 0.343794E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339437E+09 0.00 0.00 0.212268E+09 2053786.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.405183E+09 0.00 0.00 40755045.44 17436519.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.352333E+09 0.00 0.00 1693021.36 0.152668E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.387567E+09 0.00 0.00 0.00 0.286214E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.388820E+09 0.00 0.00 0.00 0.587159E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.359032E+09 0.00 0.00 0.00 0.692816E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409531E+09 0.00 0.00 0.00 0.702283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.353342E+09 0.00 0.00 0.00 0.457588E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.369950E+09 0.00 0.00 6768942.11 0.246694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.369950E+09 0.00 0.00 19622229.85 30211063.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.352581E+09 0.00 0.00 0.252228E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.446093E+10 0.00 0.00 0.877129E+09 0.317512E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339437E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409531E+09 0.00 0.00 0.343794E+09 0.702283E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.459711E+09 0.00 0.00 0.799392E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.413318E+09 0.00 0.00 0.544822E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.485959E+09 0.00 0.00 0.173653E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.422443E+09 0.00 0.00 13115915.43 81110781.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.464687E+09 0.00 0.00 70884.46 0.262180E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.464687E+09 0.00 0.00 0.00 0.670398E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.422818E+09 0.00 0.00 0.00 0.831183E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.485809E+09 0.00 0.00 0.00 0.825663E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.422443E+09 0.00 0.00 0.00 0.504258E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.443565E+09 0.00 0.00 17394345.76 0.217304E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.443565E+09 0.00 0.00 0.114591E+09 8915589.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.425473E+09 0.00 0.00 0.675648E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.535448E+10 0.00 0.00 0.233869E+10 0.340101E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.413318E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.485959E+09 0.00 0.00 0.799392E+09 0.831183E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.451275E+09 0.00 0.00 0.345100E+09 1127899.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.410429E+09 0.00 0.00 0.225657E+09 10377177.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.491639E+09 0.00 0.00 54604545.77 24827279.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.427512E+09 0.00 0.00 2246330.62 0.121343E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.470422E+09 0.00 0.00 7908.82 0.246216E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.475073E+09 0.00 0.00 0.00 0.547695E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.434737E+09 0.00 0.00 0.00 0.661587E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.496554E+09 0.00 0.00 0.00 0.679177E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.428824E+09 0.00 0.00 0.00 0.448534E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.449051E+09 0.00 0.00 8214553.46 0.249161E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.448888E+09 0.00 0.00 29071749.79 50899846.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.427512E+09 0.00 0.00 0.266895E+09 976549.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.541192E+10 0.00 0.00 0.931796E+09 0.304192E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.410429E+09 0.00 0.00 0.00 976549.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.496554E+09 0.00 0.00 0.345100E+09 0.679177E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.141981E+10 0.00 0.00 10923.83 0.00 0.192894E+09 8349930.15 0.00 0.19
February 0.124040E+10 0.00 0.00 201978.76 0.00 75242644.74 79007375.04 0.00 0.19
March 0.991690E+09 0.00 0.00 1438975.69 0.00 8418378.73 0.458625E+09 0.00 0.21
April 0.357753E+09 0.00 0.00 5599661.04 0.00 0.00 0.708776E+09 0.00 0.19
May 0.232631E+09 0.00 0.00 10708456.47 0.00 0.00 0.640853E+09 0.00 0.20
June 0.106481E+09 22324475.38 0.00 13236082.99 1784066.45 0.00 0.240156E+09 0.00 0.21
July 29826916.86 0.195669E+09 0.00 3442136.03 6851530.39 0.00 35623773.80 0.00 0.18
August 55679387.94 0.134780E+09 0.00 6466713.93 3652979.91 0.00 64087241.10 0.00 0.21
September 0.106012E+09 17886679.86 0.00 13699766.30 166733.29 0.00 0.232268E+09 0.00 0.19
October 0.318959E+09 932219.08 0.00 10137328.63 108779.25 0.00 0.703780E+09 0.00 0.19
November 0.759234E+09 0.00 0.00 2734923.77 0.00 590288.03 0.718596E+09 0.00 0.20
December 0.154751E+10 0.00 0.00 70424.93 0.00 75245387.59 36442454.20 0.00 0.18
                   
Annual Sum or Average 0.716598E+10 0.371592E+09 0.00 67747372.35 12564089.29 0.352390E+09 0.392656E+10 0.00 0.19
Minimum of Months 29826916.86 0.00 0.00 10923.83 0.00 0.00 8349930.15 0.00 0.18
Maximum of Months 0.154751E+10 0.195669E+09 0.00 13699766.30 6851530.39 0.192894E+09 0.718596E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.386045E+09 0.00 0.00 1358969.33 0.00 0.372036E+09 0.155649E+09 0.00 0.19
February 0.363771E+09 0.00 0.00 1246949.56 0.00 0.278375E+09 0.113421E+09 0.00 0.19
March 0.400760E+09 0.00 0.00 1321940.67 0.00 0.150425E+09 0.136753E+09 0.00 0.21
April 0.256570E+09 72924.84 0.00 2278856.46 10335.30 41456075.10 0.142993E+09 0.00 0.19
May 0.172292E+09 3013660.25 0.00 3857991.11 626962.33 6207210.17 0.168010E+09 0.00 0.20
June 59514568.15 98702192.45 0.00 3580453.87 12702577.09 0.00 61335235.12 0.00 0.21
July 24965121.69 0.225057E+09 0.00 866473.21 14244414.18 0.00 7511970.84 0.00 0.18
August 45092628.83 0.179688E+09 0.00 2467304.73 9528020.58 0.00 18357948.28 0.00 0.21
September 79266871.50 41888306.05 0.00 7665785.55 758350.86 0.00 55271749.05 0.00 0.19
October 0.215952E+09 6537770.44 0.00 10835328.41 53934.11 22057653.20 0.260204E+09 0.00 0.19
November 0.328987E+09 0.00 0.00 5143816.73 0.00 47179140.74 0.399201E+09 0.00 0.19
December 0.481393E+09 0.00 0.00 1307094.02 0.00 0.241760E+09 0.241277E+09 0.00 0.18
                   
Annual Sum or Average 0.281461E+10 0.554960E+09 0.00 41930963.64 37924594.46 0.115950E+10 0.175999E+10 0.00 0.19
Minimum of Months 24965121.69 0.00 0.00 866473.21 0.00 0.00 7511970.84 0.00 0.18
Maximum of Months 0.481393E+09 0.225057E+09 0.00 10835328.41 14244414.18 0.372036E+09 0.399201E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.149279E+09 0.00 0.00 0.00 0.00 0.375286E+09 0.00 0.00 0.19
February 0.160141E+09 0.00 0.00 14961.77 0.00 0.275551E+09 5104659.42 0.00 0.19
March 0.281680E+09 0.00 0.00 208506.54 0.00 67861664.47 67510922.63 0.00 0.21
April 0.102821E+09 0.00 0.00 3351302.25 0.00 220639.73 0.181999E+09 0.00 0.19
May 65670214.29 1272593.62 0.00 5874364.46 19118.69 0.00 0.151230E+09 0.00 0.20
June 29313298.60 56828750.21 0.00 4759844.19 3140363.03 0.00 40482181.30 0.00 0.21
July 10088902.23 0.163054E+09 0.00 904491.93 6798539.24 0.00 8311599.23 0.00 0.18
August 18306938.06 0.137085E+09 0.00 1880177.75 4261775.79 0.00 15812045.15 0.00 0.21
September 37477670.93 31868640.74 0.00 5702226.69 286385.50 0.00 42546704.95 0.00 0.19
October 0.137215E+09 6147320.96 0.00 4572287.09 142134.92 2228637.40 0.168233E+09 0.00 0.19
November 0.314316E+09 0.00 0.00 524203.57 0.00 21419865.86 0.122823E+09 0.00 0.19
December 0.165627E+09 0.00 0.00 0.00 0.00 0.383065E+09 0.00 0.00 0.18
                   
Annual Sum or Average 0.147194E+10 0.396256E+09 0.00 27792366.25 14648317.17 0.112563E+10 0.804053E+09 0.00 0.19
Minimum of Months 10088902.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.314316E+09 0.163054E+09 0.00 5874364.46 6798539.24 0.383065E+09 0.181999E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 72868767.87 0.00 0.00 0.00 0.00 0.862482E+09 0.00 0.00 0.19
February 95591952.88 0.00 0.00 0.00 0.00 0.678065E+09 0.00 0.00 0.19
March 0.408119E+09 0.00 0.00 0.00 0.00 0.283549E+09 0.00 0.00 0.21
April 0.342187E+09 0.00 0.00 1110954.90 0.00 30548111.25 0.121139E+09 0.00 0.19
May 0.168993E+09 314520.96 0.00 4615971.42 5843.32 81735.91 0.243746E+09 0.00 0.20
June 52165153.19 65097976.65 0.00 5292783.18 4751250.49 0.00 84318306.43 0.00 0.21
July 19906223.62 0.229133E+09 0.00 1000007.93 11286187.63 0.00 11211858.41 0.00 0.18
August 35504521.20 0.178601E+09 0.00 2462314.05 7031324.53 0.00 26733213.41 0.00 0.21
September 79523398.61 30840000.45 0.00 6543062.31 438103.30 0.00 75609981.76 0.00 0.19
October 0.299221E+09 3570726.25 0.00 3521509.83 219613.63 25316933.48 0.219904E+09 0.00 0.19
November 0.489531E+09 0.00 0.00 120688.37 0.00 0.212606E+09 59364367.41 0.00 0.19
December 44050372.06 0.00 0.00 0.00 0.00 0.917367E+09 0.00 0.00 0.18
                   
Annual Sum or Average 0.210766E+10 0.507557E+09 0.00 24667291.99 23732322.90 0.301002E+10 0.842026E+09 0.00 0.19
Minimum of Months 19906223.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.489531E+09 0.229133E+09 0.00 6543062.31 11286187.63 0.917367E+09 0.243746E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.172633E+09 0.00 0.00 17813.22 0.00 0.373004E+09 7217251.89 0.00 0.19
February 0.174672E+09 0.00 0.00 204369.45 0.00 0.266488E+09 23245453.60 0.00 0.19
March 0.278707E+09 0.00 0.00 389762.92 0.00 0.103627E+09 51383905.49 0.00 0.21
April 0.182033E+09 0.00 0.00 1838542.34 0.00 1497422.31 0.123655E+09 0.00 0.19
May 95950186.33 299220.41 0.00 3934548.40 1506.89 49131.94 0.152376E+09 0.00 0.20
June 32970890.83 41416041.51 0.00 3870991.99 1175076.43 0.00 48741486.49 0.00 0.21
July 12040556.62 0.146572E+09 0.00 792793.20 4995698.25 0.00 7029188.77 0.00 0.18
August 19725725.41 0.118461E+09 0.00 1744697.98 3072197.47 0.00 17569161.40 0.00 0.21
September 39722554.01 22938617.14 0.00 4925959.71 232009.58 0.00 52480638.84 0.00 0.19
October 0.157917E+09 3826013.59 0.00 4072842.71 140073.16 8089774.10 0.165272E+09 0.00 0.19
November 0.286934E+09 0.00 0.00 926632.49 0.00 51182429.18 0.141292E+09 0.00 0.19
December 0.201105E+09 0.00 0.00 12904.44 0.00 0.373141E+09 6472470.47 0.00 0.18
                   
Annual Sum or Average 0.165441E+10 0.333513E+09 0.00 22731858.86 9616561.79 0.117708E+10 0.796735E+09 0.00 0.19
Minimum of Months 12040556.62 0.00 0.00 12904.44 0.00 0.00 6472470.47 0.00 0.18
Maximum of Months 0.286934E+09 0.146572E+09 0.00 4925959.71 4995698.25 0.373141E+09 0.165272E+09 0.00 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:29:14

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.544903E+11 0.274839E+10 0.00 0.123243E+11 -0.132860E+10
February 0.727811E+11 0.321181E+10 0.00 0.103475E+11 -800791350.9
March 0.100297E+12 0.384352E+10 0.00 0.976948E+10 0.488524E+09
April 0.132100E+12 0.432015E+10 0.00 0.767778E+10 0.391015E+10
May 0.144852E+12 0.432331E+10 0.00 0.585231E+10 0.820706E+10
June 0.138601E+12 0.373761E+10 0.00 0.275139E+10 0.168617E+11
July 0.143088E+12 0.362332E+10 0.00 0.181106E+09 0.208634E+11
August 0.137580E+12 0.378339E+10 0.00 0.120537E+10 0.221840E+11
September 0.108526E+12 0.307538E+10 0.00 0.396443E+10 0.156527E+11
October 0.819526E+11 0.292539E+10 0.00 0.812755E+10 0.946905E+10
November 0.609457E+11 0.281227E+10 0.00 0.110490E+11 0.223087E+10
December 0.497761E+11 0.257558E+10 0.00 0.130139E+11 -0.102961E+10
           
Annual Sum or Average 0.122499E+13 0.409801E+11 0.00 0.862641E+11 0.967084E+11
Minimum of Months 0.497761E+11 0.257558E+10 0.00 0.181106E+09 -0.132860E+10
Maximum of Months 0.144852E+12 0.432331E+10 0.00 0.130139E+11 0.221840E+11