Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 08:29:53


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 159.88 312.77 312.77
Net Site Energy 159.88 312.77 312.77
Total Source Energy 506.32 990.53 990.53
Net Source Energy 506.32 990.53 990.53


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 15.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 35.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 159.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 15.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 35.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 19.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 23.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 15.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 35.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 19.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 95.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 113.61 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 312.76 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 95.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 113.61 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 312.76 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 159.872 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 159.872 100.00
     
Total On-Site and Utility Electric Sources 159.872 100.00
Total Electricity End Uses 159.872 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 28.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 382.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 7.7125 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 7.7125 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 7.7125 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 7.7125 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 7.7125 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 7.7125 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 7.7125 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 7.7125 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             7.7125 9.29 6.7800  
Conditioned Total 511.16             7.7125 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 7.7125 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-OCT-10:00 03-JAN-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 3731.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5460.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2378.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1612.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2564.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 15482.07 3731.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 3731.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 5460.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2378.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1612.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2564.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 48.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 111.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 167.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 60.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 74.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 506.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.04 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 94.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 117.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 146.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 990.53 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.04 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 94.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 218.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 117.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 146.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 990.53 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.298884
PERIMETER_ZN_1 DIRECT AIR 0.323328
PERIMETER_ZN_2 DIRECT AIR 0.244381
PERIMETER_ZN_3 DIRECT AIR 0.280270
PERIMETER_ZN_4 DIRECT AIR 0.293027
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.298884 0.298884 0.298884 0.298884 0.298884 0.298884 1.00 1.00 0.298884
PSZ-AC:2 0.323328 0.323328 0.323328 0.323328 0.323328 0.323328 1.00 1.00 0.323328
PSZ-AC:3 0.244381 0.244381 0.244381 0.244381 0.244381 0.244381 1.00 1.00 0.244381
PSZ-AC:4 0.280270 0.280270 0.280270 0.280270 0.280270 0.280270 1.00 1.00 0.280270
PSZ-AC:5 0.293027 0.293027 0.293027 0.293027 0.293027 0.293027 1.00 1.00 0.293027
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.298884 0.064622
PSZ-AC:2_OA_CONTROLLER 0.323328 0.048988
PSZ-AC:3_OA_CONTROLLER 0.244381 0.029060
PSZ-AC:4_OA_CONTROLLER 0.280270 0.048988
PSZ-AC:5_OA_CONTROLLER 0.293027 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.298884 5168.52 0.800940
PSZ-AC:2 HP COOLING COIL 0.323328 5385.66 0.800373
PSZ-AC:3 HP COOLING COIL 0.244381 4045.38 0.800655
PSZ-AC:4 HP COOLING COIL 0.280270 4716.10 0.800681
PSZ-AC:5 HP COOLING COIL 0.293027 4850.64 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.298884 0.298884 0.298884 0.298884 5168.52 5168.52 40.00 2777.99 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.323328 0.323328 0.323328 0.323328 5385.66 5385.66 40.00 3681.05 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.244381 0.244381 0.244381 0.244381 4045.38 4045.38 40.00 2295.99 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.280270 0.280270 0.280270 0.280270 4716.10 4716.10 40.00 3656.59 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.293027 0.293027 0.293027 0.293027 4850.64 4850.64 40.00 2289.67 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.298884
PSZ-AC:2 FAN 0.323328
PSZ-AC:3 FAN 0.244381
PSZ-AC:4 FAN 0.280270
PSZ-AC:5 FAN 0.293027
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.298884 5168.52
PSZ-AC:2 HEATING COIL 0.323328 5385.66
PSZ-AC:3 HEATING COIL 0.244381 4045.38
PSZ-AC:4 HEATING COIL 0.280270 4716.10
PSZ-AC:5 HEATING COIL 0.293027 4850.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2777.99
PSZ-AC:2_SUPPHEATCOIL 3681.05
PSZ-AC:3_SUPPHEATCOIL 2295.99
PSZ-AC:4_SUPPHEATCOIL 3656.59
PSZ-AC:5_SUPPHEATCOIL 2289.67
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1154.233 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1154.233
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1263E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.2711E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2119E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3454E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.1613E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 9.2076E-004
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.9490E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.4114E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 7.8368E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.1589E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 7.9944E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.6778E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 7.0894E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.8221E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.3709E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.8142E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.5207E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.4418E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.4229E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.6302E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.2710E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.0408E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.8006E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6773E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1148E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.2299E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2008E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3034E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.0632E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 8.9243E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.9164E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.3398E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.0688E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.0816E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1618E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1727E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.7052E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.7938E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.6914E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.7405E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.0654E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.0679E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1590E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1611E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.6819E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.6985E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.6767E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.6863E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.6756E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.9785E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7689E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.0573E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.2405E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.4495E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.2630E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.0214E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.9652E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.9331E-004
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.1220E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.8293E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.8493E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.1609E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.1908E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.6168E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3118E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.5764E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.6162E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.0821E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.2312E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.7687E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0319E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9280E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.5989E-003
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.7414E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.6056E-003
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.4270E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.0070E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.3940E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.6144E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.0693E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.1024E-004
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.1127E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.5326E-004
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0538E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 7.5512E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 8.8261E-004
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.2223E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.6881E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2309E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.0530E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.4030E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.0305E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.8121E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.1943E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.9068E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.3116E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.6556E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.2186E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0643E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6763E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 1.8609E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.1097E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.5564E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6125E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.5926E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.5243E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.8087E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.9140E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.7224E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.3224E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7002E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8862E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3440E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.2887E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.4999E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.2297E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.9156E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.4000E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9723E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.4551E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.8564E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.9784E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.1064E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.2032E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.5783E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.6470E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.6983E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.7529E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.8197E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.8446E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.0766E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.0965E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.5548E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.5691E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6816E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.6920E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.0002E-003
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.2418E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.6378E-004
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.2126E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.1709E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.5498E-004
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.2325E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.6949E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 9.0482E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 4.2204E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 9.3880E-003
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.9946E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.6927E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.6822E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.5992E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.0426E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3350E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.5875E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.6856E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.1408E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.4035E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9071E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.0289E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9056E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.6051E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.5393E-004
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.9052E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.5952E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.4031E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.7359E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1999E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.6233E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3331.49289 3997.79147 0.24907 0.29888 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 30.94400 8.23292E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 761.36042 913.63250 3.34460E-002 6.46221E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3603.85683 4324.62819 0.26944 0.32333 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 31.30000 8.23349E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 2261.34038 2713.60846 9.93370E-002 0.11920 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2724.04209 3268.85051 0.20365 0.24438 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 27.66583 8.22773E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1436.46346 1723.75615 6.31014E-002 7.57216E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3124.01839 3748.82207 0.23356 0.28027 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 31.03300 8.23307E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 2240.65804 2688.78965 9.84285E-002 0.11811 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3266.28129 3919.53755 0.24419 0.29303 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 29.75733 8.23104E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1431.11979 1717.34375 6.28666E-002 7.54400E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4477.34 0.29888 0.29888 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2777.99 6.46221E-002 6.46221E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 4688.88 0.32333 0.32333 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC:2 Heating Sensible 3681.05 0.11920 0.11920 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3348.62 0.24438 0.24438 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2295.99 7.57216E-002 7.57216E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 4106.42 0.28027 0.28027 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 PSZ-AC:4 Heating Sensible 3656.59 0.11811 0.11811 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4061.42 0.29303 0.29303 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2289.67 7.54400E-002 7.54400E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29888
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.32333
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.24438
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28027
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29303
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29888
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29888
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29888
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.29888
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29888
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.29888
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.32333
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.32333
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.32333
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.32333
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.32333
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.32333
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.24438
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.24438
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.24438
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.24438
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.24438
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.24438
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28027
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28027
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28027
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.28027
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28027
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.28027
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29303
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29303
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29303
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.29303
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29303
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.29303
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.29888
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.32333
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.24438
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.28027
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.29303
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29888
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29888
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5168.51543
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80094
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29888
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29888
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29888
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29888
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5168.51543
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5168.51543
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2777.98885
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.29888
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29888
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5168.51543
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2777.98885
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.32333
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.32333
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5385.65619
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80037
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.32333
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.32333
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.32333
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.32333
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5385.65619
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5385.65619
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3681.04870
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.32333
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.32333
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5385.65619
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 3681.04870
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.24438
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.24438
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4045.37518
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.24438
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.24438
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.24438
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.24438
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4045.37518
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4045.37518
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2295.99220
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.24438
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.24438
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4045.37518
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2295.99220
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28027
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28027
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4716.09832
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80068
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28027
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28027
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28027
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28027
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4716.09832
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4716.09832
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3656.59141
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.28027
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28027
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4716.09832
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 3656.59141
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29303
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29303
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4850.64446
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29303
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29303
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29303
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29303
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4850.64446
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4850.64446
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2289.67320
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.29303
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29303
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4850.64446
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2289.67320
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 4934.1 3.32 11.32 11.85 11.21 11.11
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 5132.2 3.29 11.24 11.75 11.12 10.98
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 3853.9 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 4496.4 3.30 11.26 11.78 11.14 11.02
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4621.0 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5405.9 3006.2 7.34 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 5642.2 3141.7 7.33 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4239.3 2361.0 7.32 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 4938.5 2748.9 7.35 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5083.1 2831.0 7.33 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 8.2311560586E-003 4.8460409727E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 3.4234030619E-002 3.5287095448E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 2.9848869332E-002 4.0006315848E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 1.7890456600E-002 1.1687650158E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 2.4421772236E-002 1.4168299510E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2939037243 0.3257616692 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1316.67 39.74 0.00 80.50 0.460823E+190 0.460823E+190



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.4644_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.4644_SHGC_SOUTH_0.25   3.91 0.00 0.00 3.91 3.91 2.640 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.4644_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.4644_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.4644_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.4644_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.4644_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.4644_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.4644_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.4644_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.4644_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.640 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.640 0.251 0.251                      
North Total or Average             16.72 2.640 0.251 0.251                      
Non-North Total or Average             42.93 2.640 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.15 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 7.7125 149.66 1154.23 LightsWired LTG_SCH_OFFICE 52.79 168.00 51.86 0.0000 Y 11.24
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 44.48 0.0000 Y 7.31
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 46.16 0.0000 Y 4.50
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 47.51 0.0000 Y 7.80
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 46.00 0.0000 Y 4.48
Interior Lighting Total       7.7125 511.16 3942.30               35.33


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   42.14 42.14 0.53
EXTERIOR_LIGHTS_B 982.38 AstronomicalClock -   83.75 71.27 13.14
Exterior Lighting Total 1049.11           13.67



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5168.52 4139.67 1028.84 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5385.66 4310.53 1075.12 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4045.38 3238.95 806.42 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4716.10 3776.09 940.01 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4850.64 3883.69 966.95 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   4934.1 3.32 11.32 11.85 11.21 11.11
PSZ-AC:2 HP COOLING COIL   5132.2 3.29 11.24 11.75 11.12 10.98
PSZ-AC:3 HP COOLING COIL   3853.9 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   4496.4 3.30 11.26 11.78 11.14 11.02
PSZ-AC:5 HP COOLING COIL   4621.0 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5405.9 3006.2 7.34 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 5642.2 3141.7 7.33 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4239.3 2361.0 7.32 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 4938.5 2748.9 7.35 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5083.1 2831.0 7.33 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5168.52 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2777.99 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   5385.66 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   3681.05 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4045.38 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2295.99 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   4716.10 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   3656.59 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   4850.64 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2289.67 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.30 334.78 1120.11 1.00 1.90 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.32 362.16 1120.11 1.00 1.84 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.24 273.73 1120.11 1.00 2.06 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.28 313.93 1120.11 1.00 1.95 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.29 328.22 1120.11 1.00 1.91 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3331.49 3997.79 26.71 0.249 0.299 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 23.89 23.89 0.00904 30.94 0.00823 0.065 0.00
PERIMETER_ZN_1 3603.86 4324.63 38.12 0.269 0.323 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 23.89 23.89 0.00885 31.30 0.00823 0.049 0.00
PERIMETER_ZN_2 2724.04 3268.85 48.57 0.204 0.244 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 23.89 23.89 0.00878 27.67 0.00823 0.029 0.00
PERIMETER_ZN_3 3124.02 3748.82 33.04 0.234 0.280 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 23.89 23.89 0.00891 31.03 0.00823 0.049 0.00
PERIMETER_ZN_4 3266.28 3919.54 58.24 0.244 0.293 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 23.89 23.89 0.00873 29.76 0.00823 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 761.36 913.63 6.10 0.033 0.065 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 3.80 0.00506 0.065 0.00
PERIMETER_ZN_1 2261.34 2713.61 23.92 0.099 0.119 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00778 3.80 0.00506 0.049 0.00
PERIMETER_ZN_2 1436.46 1723.76 25.61 0.063 0.076 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 3.80 0.00506 0.029 0.00
PERIMETER_ZN_3 2240.66 2688.79 23.70 0.098 0.118 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 3.80 0.00506 0.049 0.00
PERIMETER_ZN_4 1431.12 1717.34 25.52 0.063 0.075 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 3.80 0.00506 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.30 0.30 0.06 0.06 0.2989 0.2989 0.2989 1.0000 1.0000
PSZ-AC:2 0.32 0.32 0.12 0.12 0.3233 0.3233 0.3233 1.0000 1.0000
PSZ-AC:3 0.24 0.24 0.08 0.08 0.2444 0.2444 0.2444 1.0000 1.0000
PSZ-AC:4 0.28 0.28 0.12 0.12 0.2803 0.2803 0.2803 1.0000 1.0000
PSZ-AC:5 0.29 0.29 0.08 0.08 0.2930 0.2930 0.2930 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5168.515 4139.671 0.298884 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 5054.14 4766.02 0.298884 26.34 17.31 0.00886363 12.80 11.93 0.00850000 30.94 0.00823292 18.33 21.6211 23.89 0.00903948 48.0330 3324.33 0.00 5167.63 4095.16
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5168.515 5168.515 0.298884 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 5168.52 5168.52 0.298884 17.37 12.67 0.00736400 40.00 20.96 0.00800000 3.80 0.00505843 3.80 21.6211 21.11 0.00800000 50.4139 760.59 0.00 5175.31 5175.31
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2777.989 2777.989 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 2777.99 2777.99 0.298884 17.37 12.67 0.00736400 40.00 20.96 0.00800000 3.80 0.00505843 3.80 21.6211 21.11 0.00800000 50.4139 760.59 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 5385.656 4310.532 0.323328 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 5224.69 5002.87 0.323328 25.94 17.09 0.00875963 12.80 11.93 0.00850000 31.30 0.00823349 18.45 15.1511 23.89 0.00885358 47.0592 3603.86 0.00 5384.73 4264.16
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 5385.656 5385.656 0.323328 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5385.66 5385.66 0.323328 18.49 13.11 0.00736438 40.00 20.96 0.00800000 3.80 0.00505843 3.80 15.1511 21.11 0.00777614 49.0219 2261.34 0.00 5392.73 5392.73
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 3681.049 3681.049 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3681.05 3681.05 0.323328 18.49 13.11 0.00736438 40.00 20.96 0.00800000 3.80 0.00505843 3.80 15.1511 21.11 0.00777614 49.0219 2261.34 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4045.375 3238.951 0.244381 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 3991.96 3845.90 0.244381 25.27 16.82 0.00871225 12.80 11.93 0.00850000 27.67 0.00822773 17.24 11.8913 23.89 0.00877814 46.6629 2719.95 0.00 4044.68 3203.84
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4045.375 4045.375 0.244381 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4045.38 4045.38 0.244381 19.05 13.41 0.00744398 40.00 20.96 0.00800000 3.80 0.00505843 3.80 11.8913 21.11 0.00776594 48.9585 1436.46 0.00 4050.69 4050.69
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2295.992 2295.992 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2295.99 2295.99 0.244381 19.05 13.41 0.00744398 40.00 20.96 0.00800000 3.80 0.00505843 3.80 11.8913 21.11 0.00776594 48.9585 1436.46 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4716.098 3776.089 0.280270 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 4591.48 4377.97 0.280270 26.07 17.16 0.00878801 12.80 11.93 0.00850000 31.03 0.00823307 18.36 17.4788 23.89 0.00890669 47.3370 3118.18 0.00 4715.29 3735.57
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4716.098 4716.098 0.280270 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4716.10 4716.10 0.280270 18.08 12.89 0.00729954 40.00 20.96 0.00800000 3.80 0.00505843 3.80 17.4788 21.11 0.00777423 49.0100 2240.66 0.00 4722.30 4722.30
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 3656.591 3656.591 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3656.59 3656.59 0.280270 18.08 12.89 0.00729954 40.00 20.96 0.00800000 3.80 0.00505843 3.80 17.4788 21.11 0.00777423 49.0100 2240.66 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4850.644 3883.694 0.293027 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 4728.56 4580.34 0.293027 25.40 16.84 0.00868256 12.80 11.93 0.00850000 29.76 0.00823104 17.94 9.9172 23.89 0.00873227 46.4223 3266.28 0.00 4849.81 3841.60
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4850.644 4850.644 0.293027 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4850.64 4850.64 0.293027 19.39 13.59 0.00749671 40.00 20.96 0.00800000 3.80 0.00505843 3.80 9.9172 21.11 0.00776514 48.9535 1431.12 0.00 4857.02 4857.02
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2289.673 2289.673 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2289.67 2289.67 0.293027 19.39 13.59 0.00749671 40.00 20.96 0.00800000 3.80 0.00505843 3.80 9.9172 21.11 0.00776514 48.9535 1431.12 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5168.515 4139.671 0.298884 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.3170 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.298884 0.35321459   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 5054.14 4766.02 0.9779 0.35321459 0.298884 26.34 17.31 0.00886363 49071.7 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 334.782 4719.36 30.94 0.00823292 18.33 0.06462207 21.6211 23.89 0.00903761 23.89 0.00903948 48.0330 3324.33 0.00 5167.63 4095.16 0.33926529 26.67 19.44 0.01118466 55322.4 14.87 14.31 0.00994525 40090.6
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5168.515 5168.515 0.298884 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.298884 0.35321459   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 5168.52 5168.52 1.0000 0.35321459 0.298884 17.37 12.67 0.00736400 36106.1 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5168.52 3.80 0.00505843 3.80 0.06462207 21.6211 21.11 0.00800000 21.11 0.00800000 50.4139 760.59 0.00 5175.31 5175.31 0.34697318 21.11 15.56 0.00875166 43444.1 35.72 20.44 0.00875166 58359.7
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2777.989 2777.989 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.298884 0.35321459   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 2777.99 2777.99 1.0000 0.35321459 0.298884 17.37 12.67 0.00736400 36106.1 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2777.99 3.80 0.00505843 3.80 0.06462207 21.6211 21.11 0.00800000 21.11 0.00800000 50.4139 760.59 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5385.656 4310.532 0.323328 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1237 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.323328 0.38210166   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 5224.69 5002.87 0.9701 0.38210166 0.323328 25.94 17.09 0.00875963 48395.4 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 362.162 4862.53 31.30 0.00823349 18.45 0.04898771 15.1511 23.89 0.00885358 23.89 0.00885358 47.0592 3603.86 0.00 5384.73 4264.16 0.36701153 26.67 19.44 0.01118466 55322.4 15.31 14.52 0.00998755 40650.6
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5385.656 5385.656 0.323328 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.323328 0.38210166   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5385.66 5385.66 1.0000 0.38210166 0.323328 18.49 13.11 0.00736438 37247.4 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5385.66 3.80 0.00505843 3.80 0.04898771 15.1511 21.11 0.00777614 21.11 0.00777614 49.0219 2261.34 0.00 5392.73 5392.73 0.37534980 21.11 15.56 0.00875166 43444.1 35.18 20.28 0.00875166 57811.3
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3681.049 3681.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.323328 0.38210166   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3681.05 3681.05 1.0000 0.38210166 0.323328 18.49 13.11 0.00736438 37247.4 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3681.05 3.80 0.00505843 3.80 0.04898771 15.1511 21.11 0.00777614 21.11 0.00777614 49.0219 2261.34 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4045.375 3238.951 0.244381 -999.0 -999.000 -999.0000 1.07001 1.00000 1021.0356 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.244381 0.28880439   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 Sensible 3991.96 3845.90 0.9868 0.28880439 0.244381 25.27 16.82 0.00871225 47587.3 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 273.733 3718.22 27.67 0.00822773 17.24 0.02906014 11.8913 23.89 0.00877764 23.89 0.00877814 46.6629 2719.95 0.00 4044.68 3203.84 0.27739880 26.67 19.44 0.01118466 55322.4 15.38 14.55 0.00999622 40741.6
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4045.375 4045.375 0.244381 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.244381 0.28880439   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4045.38 4045.38 1.0000 0.28880439 0.244381 19.05 13.41 0.00744398 38024.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4045.38 3.80 0.00505843 3.80 0.02906014 11.8913 21.11 0.00776594 21.11 0.00776594 48.9585 1436.46 0.00 4050.69 4050.69 0.28370112 21.11 15.56 0.00875166 43444.1 35.09 20.25 0.00875166 57722.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2295.992 2295.992 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.244381 0.28880439   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2295.99 2295.99 1.0000 0.28880439 0.244381 19.05 13.41 0.00744398 38024.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2295.99 3.80 0.00505843 3.80 0.02906014 11.8913 21.11 0.00776594 21.11 0.00776594 48.9585 1436.46 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4716.098 3776.089 0.280270 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1765 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.280270 0.33121675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 Sensible 4591.48 4377.97 0.9736 0.33121675 0.280270 26.07 17.16 0.00878801 48596.5 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 313.932 4277.55 31.03 0.00823307 18.36 0.04898771 17.4788 23.89 0.00890555 23.89 0.00890669 47.3370 3118.18 0.00 4715.29 3735.57 0.31813619 26.67 19.44 0.01118466 55322.4 15.19 14.46 0.00997723 40500.8
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4716.098 4716.098 0.280270 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.280270 0.33121675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4716.10 4716.10 1.0000 0.33121675 0.280270 18.08 12.89 0.00729954 36672.7 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4716.10 3.80 0.00505843 3.80 0.04898771 17.4788 21.11 0.00777423 21.11 0.00777423 49.0100 2240.66 0.00 4722.30 4722.30 0.32536405 21.11 15.56 0.00875166 43444.1 35.32 20.32 0.00875166 57958.0
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3656.591 3656.591 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.280270 0.33121675   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3656.59 3656.59 1.0000 0.33121675 0.280270 18.08 12.89 0.00729954 36672.7 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3656.59 3.80 0.00505843 3.80 0.04898771 17.4788 21.11 0.00777423 21.11 0.00777423 49.0100 2240.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4850.644 3883.694 0.293027 -999.0 -999.000 -999.0000 1.05267 1.00000 1020.9804 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.293027 0.34629357   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 4728.56 4580.34 0.9748 0.34629357 0.293027 25.40 16.84 0.00868256 47647.4 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 328.222 4400.33 29.76 0.00823104 17.94 0.02906014 9.9172 23.89 0.00873227 23.89 0.00873227 46.4223 3266.28 0.00 4849.81 3841.60 0.33261759 26.67 19.44 0.01118466 55322.4 15.38 14.55 0.00999622 40741.6
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4850.644 4850.644 0.293027 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.293027 0.34629357   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4850.64 4850.64 1.0000 0.34629357 0.293027 19.39 13.59 0.00749671 38505.9 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4850.64 3.80 0.00505843 3.80 0.02906014 9.9172 21.11 0.00776514 21.11 0.00776514 48.9535 1431.12 0.00 4857.02 4857.02 0.34017445 21.11 15.56 0.00875166 43444.1 35.09 20.25 0.00875166 57722.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2289.673 2289.673 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.293027 0.34629357   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2289.67 2289.67 1.0000 0.34629357 0.293027 19.39 13.59 0.00749671 38505.9 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2289.67 3.80 0.00505843 3.80 0.02906014 9.9172 21.11 0.00776514 21.11 0.00776514 48.9535 1431.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2053.67 1214.33 147.33
PERIMETER_ZN_1 1325.17 2093.83 176.33
PERIMETER_ZN_2 1021.50 2006.17 100.83
PERIMETER_ZN_3 963.50 2751.67 199.67
PERIMETER_ZN_4 1486.67 2165.17 139.50
ATTIC 0.00 0.00 0.00
Facility 2414.67 3007.33 382.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 6.33 0.00 6.33
PERIMETER_ZN_1 0.00 23.00 0.00 22.67
PERIMETER_ZN_2 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 29.17 0.00 28.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.398 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.397 0.391 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.371 0.038 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.397 0.032 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.398 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.79 0.00 762126.79 0.00 762126.79 2037921.45 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_1 577946.49 0.00 577946.49 649101.90 1227048.39 1544876.42 5484.00 3276.00 0.00 5.44
PERIMETER_ZN_2 342723.67 0.00 342723.67 85090.67 427814.34 916440.58 5484.00 3276.00 0.00 756.00
PERIMETER_ZN_3 577741.46 0.00 577741.46 127636.01 705377.47 1544876.42 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_4 342723.67 0.00 342723.67 85090.67 427814.34 916440.58 5484.00 3276.00 0.00 0.00
Total Facility 2603262.07 0.00 2603262.07 946919.26 3550181.33 6960555.45 5484.00 3276.00 0.00 761.44


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0369 0.0743 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0021 0.0229 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0030 0.0405 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0020 0.0242 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0440 0.2113 0.2207 1008.00 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1064386.89 0.00 1064386.89 2037921.45 5484.00 0.00 3276.00 0.00
PSZ-AC:2 807160.53 0.00 807160.53 1544876.42 5483.87 0.00 3276.13 5.44
PSZ-AC:3 478648.15 0.00 478648.15 916440.58 5484.00 0.00 3276.00 756.00
PSZ-AC:4 806874.19 0.00 806874.19 1544876.42 5484.00 0.00 3276.00 0.00
PSZ-AC:5 478648.15 0.00 478648.15 916440.58 5484.00 0.00 3276.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0690 0.0000 0.0690 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0523 0.0000 0.0523 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0290 0.0000 0.0290 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0523 0.0000 0.0523 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0310 0.0000 0.0310 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3281.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0903 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0684 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0406 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0684 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0406 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 523
Defaulted Fields 365
Fields with Defaults 1332
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
Electricity:Building 88.13 1143.22 10-JUN-13:30 6143.85 02-JAN-16:50
Electricity:Zone:CORE_ZN 26.70 359.76 01-JAN-00:10 1798.81 02-JAN-08:10
Electricity:SpaceType:GENERAL 88.13 1143.22 10-JUN-13:30 6143.85 02-JAN-16:50
InteriorLights:Electricity 35.33 450.09 10-JUN-13:30 2678.20 02-JAN-16:50
InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 35.33 450.09 10-JUN-13:30 2678.20 02-JAN-16:50
LightsWired:InteriorLights:Electricity 35.33 450.09 10-JUN-13:30 2678.20 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 35.33 450.09 10-JUN-13:30 2678.20 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_1 19.02 244.20 01-JAN-07:30 1363.61 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.31 90.36 01-JAN-07:30 594.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.31 90.36 01-JAN-07:30 594.42 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_2 11.45 144.86 01-JAN-08:00 808.91 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.50 53.60 01-JAN-08:00 352.62 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.50 53.60 01-JAN-08:00 352.62 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_3 19.52 244.20 22-APR-14:10 1363.61 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.80 90.36 22-APR-14:10 594.42 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.80 90.36 22-APR-14:10 594.42 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_4 11.43 144.86 01-JAN-12:10 808.91 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.48 53.60 01-JAN-12:10 352.62 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.48 53.60 01-JAN-12:10 352.62 02-JAN-16:50
InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
ElectricityPurchased:Facility 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
ElectricityPurchased:Plant 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
Cogeneration:ElectricityPurchased 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
General:Cogeneration:ElectricityPurchased 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
ElectricityNet:Plant 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
Cogeneration:ElectricityNet 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
General:Cogeneration:ElectricityNet 159.87 1715.22 10-JUN-13:30 15482.07 16-OCT-11:00
ExteriorLights:Electricity 13.67 0.00 01-JAN-07:00 1049.11 01-JAN-06:10
General:ExteriorLights:Electricity 13.67 0.00 01-JAN-07:00 1049.11 01-JAN-06:10
Electricity:HVAC 34.40 0.00 01-JAN-00:10 7072.86 16-OCT-11:00
Fans:Electricity 19.02 0.00 01-JAN-00:10 1612.83 02-JAN-06:10
General:Fans:Electricity 19.02 0.00 01-JAN-00:10 1612.83 02-JAN-06:10
Cooling:Electricity 15.21 0.00 01-JAN-00:10 5460.02 16-OCT-11:00
General:Cooling:Electricity 15.21 0.00 01-JAN-00:10 5460.02 16-OCT-11:00
Heating:Electricity 0.17 0.00 01-JAN-00:10 3389.34 03-JAN-07:10
General:Heating:Electricity 0.17 0.00 01-JAN-00:10 3389.34 03-JAN-07:10
Electricity:Plant 23.68 572.00 18-FEB-10:40 2788.61 02-FEB-12:10
WaterSystems:Electricity 23.68 572.00 18-FEB-10:40 2788.61 02-FEB-12:10
Water Heater:WaterSystems:Electricity 23.68 572.00 18-FEB-10:40 2788.61 02-FEB-12:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-09:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-09:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 3731.84 03-JAN-07:10
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 3731.84 03-JAN-07:10
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 3731.84 03-JAN-07:10
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 3731.84 03-JAN-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 28-FEB-12:20
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 28-FEB-12:20
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 129.19 0.00 01-JAN-00:10 37898.24 16-OCT-14:20
EnergyTransfer:Building 58.34 0.00 01-JAN-00:10 17250.37 16-OCT-14:30
EnergyTransfer:Zone:CORE_ZN 19.51 0.00 01-JAN-00:10 4515.94 16-OCT-07:20
Heating:EnergyTransfer 0.62 0.00 01-JAN-00:10 10680.53 03-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.01 0.00 01-JAN-00:10 1262.71 02-JAN-08:10
General:Heating:EnergyTransfer 0.62 0.00 01-JAN-00:10 10680.53 03-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.01 0.00 01-JAN-00:10 1262.71 02-JAN-08:10
Cooling:EnergyTransfer 57.72 0.00 01-JAN-00:10 17250.37 16-OCT-14:30
Cooling:EnergyTransfer:Zone:CORE_ZN 19.51 0.00 01-JAN-00:10 4515.94 16-OCT-07:20
General:Cooling:EnergyTransfer 57.72 0.00 01-JAN-00:10 17250.37 16-OCT-14:30
General:Cooling:EnergyTransfer:Zone:CORE_ZN 19.51 0.00 01-JAN-00:10 4515.94 16-OCT-07:20
EnergyTransfer:Zone:PERIMETER_ZN_1 14.36 0.00 01-JAN-00:10 4918.36 30-OCT-12:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.21 0.00 01-JAN-00:10 4089.18 03-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.21 0.00 01-JAN-00:10 4089.18 03-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 14.15 0.00 01-JAN-00:10 4918.36 30-OCT-12:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 14.15 0.00 01-JAN-00:10 4918.36 30-OCT-12:10
EnergyTransfer:Zone:PERIMETER_ZN_2 7.76 0.00 01-JAN-00:10 2965.20 16-OCT-10:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.07 0.00 01-JAN-00:10 1560.14 03-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.07 0.00 01-JAN-00:10 1560.14 03-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 7.69 0.00 01-JAN-00:10 2965.20 16-OCT-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 7.69 0.00 01-JAN-00:10 2965.20 16-OCT-10:10
EnergyTransfer:Zone:PERIMETER_ZN_3 8.85 0.00 01-JAN-00:10 3172.71 16-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.17 0.00 01-JAN-00:10 2771.68 03-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.17 0.00 01-JAN-00:10 2771.68 03-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 8.68 0.00 01-JAN-00:10 3172.71 16-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 8.68 0.00 01-JAN-00:10 3172.71 16-OCT-13:20
EnergyTransfer:Zone:PERIMETER_ZN_4 7.85 0.00 01-JAN-00:10 3261.62 16-OCT-15:50
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.17 0.00 01-JAN-00:10 1612.52 02-JAN-08:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.17 0.00 01-JAN-00:10 1612.52 02-JAN-08:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 7.68 0.00 01-JAN-00:10 3261.62 16-OCT-15:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 7.68 0.00 01-JAN-00:10 3261.62 16-OCT-15:50
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
EnergyTransfer:HVAC 70.85 0.00 01-JAN-00:10 20891.16 02-OCT-07:10
CoolingCoils:EnergyTransfer 70.38 0.00 01-JAN-00:10 20891.16 02-OCT-07:10
HeatingCoils:EnergyTransfer 0.47 0.00 01-JAN-00:10 12668.37 03-JAN-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 03-FEB-07:10 80.55 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.009 -19.505 0.000 0.000 4.972 11.237 15.459 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -12.172
PERIMETER_ZN_1 0.000 0.000 0.207 -14.153 0.000 0.000 3.827 7.306 11.719 16.218 0.000 0.076 0.000 0.000 -8.367 0.000 -4.877 -11.957
PERIMETER_ZN_2 0.000 0.000 0.066 -7.695 0.000 0.000 1.660 4.497 6.952 6.993 0.000 0.005 0.000 0.000 -4.265 0.000 -0.798 -7.416
PERIMETER_ZN_3 0.000 0.000 0.171 -8.682 0.000 0.000 3.869 7.804 11.719 3.385 0.000 0.010 0.000 0.000 -6.381 0.000 -1.128 -10.767
PERIMETER_ZN_4 0.000 0.000 0.167 -7.682 0.000 0.000 2.265 4.482 6.952 8.026 0.000 0.006 0.000 0.000 -4.533 0.000 -0.824 -8.858
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.021 37.126 0.000 0.000 0.000 -48.147 -0.000
Total Facility 0.000 0.000 0.620 -57.716 0.000 0.000 16.593 35.327 52.800 34.622 0.000 11.117 37.127 0.000 -23.545 0.000 -55.773 -51.171


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 18-OCT-07:02 0.00 0.00 0.00 -5216.70 0.00 0.00 497.32 784.13 1014.68 0.00 0.00 0.00 2920.57 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 30-OCT-12:10 0.00 0.00 0.00 -4920.59 0.00 0.00 427.71 451.82 769.19 4434.48 0.00 10.31 0.00 0.00 -0.00 0.00 0.00 -1172.92
PERIMETER_ZN_2 18-OCT-07:02 0.00 0.00 0.00 -3745.12 0.00 0.00 230.55 268.02 456.29 1135.18 0.00 0.00 1664.41 0.00 -0.00 0.00 -9.33 0.00
PERIMETER_ZN_3 17-OCT-07:02 0.00 0.00 0.00 -4293.59 0.00 0.00 392.00 566.48 769.19 0.00 0.00 0.00 2596.66 0.00 -23.47 0.00 -7.28 0.00
PERIMETER_ZN_4 18-OCT-07:02 0.00 0.00 0.00 -4374.63 0.00 0.00 233.55 335.08 456.29 0.00 0.00 0.00 3451.72 0.00 -93.11 0.00 -8.89 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-OCT-07:02 0.00 0.00 0.00 -22023.72 0.00 0.00 1713.62 2409.06 3465.65 2607.39 0.00 1491.90 10488.15 0.00 -53.92 0.00 -98.13 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-08:62 0.00 0.00 5050.94 0.00 0.00 0.00 697.55 784.13 1014.68 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7547.30
PERIMETER_ZN_1 03-JAN-07:01 0.00 0.00 7603.84 0.00 0.00 0.00 119.23 260.51 384.60 65.75 0.00 0.00 0.00 0.00 -0.00 0.00 -2519.28 -5914.64
PERIMETER_ZN_2 03-JAN-07:01 0.00 0.00 5290.55 0.00 0.00 0.00 71.84 157.66 228.15 504.32 0.00 0.00 0.00 0.00 -0.00 0.00 -2.92 -6249.60
PERIMETER_ZN_3 03-JAN-07:01 0.00 0.00 6974.41 0.00 0.00 0.00 121.21 272.32 384.60 0.00 0.00 0.00 0.00 0.00 -498.92 0.00 -4.31 -7249.30
PERIMETER_ZN_4 03-JAN-07:01 0.00 0.00 5943.93 0.00 0.00 0.00 71.74 161.88 228.15 0.00 0.00 0.00 0.00 0.00 -336.24 0.00 -2.95 -6066.51
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-JAN-07:01 0.00 0.00 30431.42 0.00 0.00 0.00 533.48 1218.29 1732.82 570.06 0.00 1127.17 0.00 0.00 -835.16 0.00 -2529.46 -32248.62



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2989 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2989 0.2162 1.0000 Not calculated 0.0646 0.2162    
PSZ-AC:2 0.3233 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3233 0.1515 1.0000 Not calculated 0.0490 0.1515    
PSZ-AC:3 0.2444 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2444 0.1189 1.0000 Not calculated 0.0291 0.1189    
PSZ-AC:4 0.2803 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2803 0.1748 1.0000 Not calculated 0.0490 0.1748    
PSZ-AC:5 0.2930 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2930 0.0992 1.0000 Not calculated 0.0291 0.0992    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2989 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2989 1.0000 1.0000 Not calculated 0.0646 0.2162    
PSZ-AC:2 0.3233 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3233 1.0000 1.0000 Not calculated 0.0490 0.1515    
PSZ-AC:3 0.2444 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2444 1.0000 1.0000 Not calculated 0.0291 0.1189    
PSZ-AC:4 0.2803 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2803 1.0000 1.0000 Not calculated 0.0490 0.1748    
PSZ-AC:5 0.2930 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2930 1.0000 1.0000 Not calculated 0.0291 0.0992    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2989 0.2989 0.2989 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3233 0.3233 0.3233 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2444 0.2444 0.2444 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2803 0.2803 0.2803 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2930 0.2930 0.2930 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2989 0.2989 0.2989 0.2989 0.0646 1.0000
PSZ-AC:2 0.3233 0.3233 0.3233 0.3233 0.0490 1.0000
PSZ-AC:3 0.2444 0.2444 0.2444 0.2444 0.0291 1.0000
PSZ-AC:4 0.2803 0.2803 0.2803 0.2803 0.0490 1.0000
PSZ-AC:5 0.2930 0.2930 0.2930 0.2930 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2989 0.2989 0.2989 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3233 0.3233 0.3233 No 0.0490 0.4110 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2444 0.2444 0.2444 No 0.0291 0.3838 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2803 0.2803 0.2803 No 0.0490 0.4147 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2930 0.2930 0.2930 No 0.0291 0.3852 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2989 0.2989 0.2989 0.2989 0.0646 1.0000
PSZ-AC:2 0.3233 0.3233 0.3233 0.3233 0.0490 1.0000
PSZ-AC:3 0.2444 0.2444 0.2444 0.2444 0.0291 1.0000
PSZ-AC:4 0.2803 0.2803 0.2803 0.2803 0.0490 1.0000
PSZ-AC:5 0.2930 0.2930 0.2930 0.2930 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 28.83
Number of hours not met 28.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.17 3389.34 0.00 3731.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 15.21 5460.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 35.33 2678.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 13.67 1049.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 52.80 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 19.02 1612.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.68 2788.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 52.80 159.87
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 52.80 159.88


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 69.11
Space Heating 0.33
Space Cooling 29.75
Fans (All) 37.22
Service Water Heating 46.32
Receptacle Equipment 103.29
Miscellaneous (All) 312.76
Subtotal 312.76


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.01
Service Water Heating 0.00
Miscellaneous (All) 0.01
Subtotal 0.01


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 22.10
Space Heating 0.11
Space Cooling 9.51
Fans (All) 11.90
Service Water Heating 14.81
Receptacle Equipment 33.03
Miscellaneous 8.55


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2752. 8760.
BLDG_EQUIP_SCH 4310. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8660.50 99.50 0.00 0.00 0.00
PERIMETER_ZN_1 8619.50 140.50 0.00 0.00 0.00
PERIMETER_ZN_2 8590.50 169.50 0.00 0.00 0.00
PERIMETER_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 8467.33 292.67 0.00 0.00 0.00
ATTIC 6113.00 808.83 689.67 1011.50 137.00
Min 6113.00 0.00 0.00 0.00 0.00
Max 8760.00 808.83 689.67 1011.50 137.00
Average 8201.81 251.83 114.94 168.58 22.83
Sum 49210.83 1511.00 689.67 1011.50 137.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 6382.33 2377.67 0.00 0.00 0.00
PERIMETER_ZN_1 7852.67 907.33 0.00 0.00 0.00
PERIMETER_ZN_2 8040.00 720.00 0.00 0.00 0.00
PERIMETER_ZN_3 8175.00 585.00 0.00 0.00 0.00
PERIMETER_ZN_4 7855.00 905.00 0.00 0.00 0.00
ATTIC 6148.83 1255.83 401.00 426.33 528.00
Min 6148.83 585.00 0.00 0.00 0.00
Max 8175.00 2377.67 401.00 426.33 528.00
Average 7408.97 1125.14 66.83 71.06 88.00
Sum 44453.83 6750.83 401.00 426.33 528.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17719.00 173.00 0.00 0.00 0.00
PERIMETER_ZN_1 13301.67 54.33 0.00 0.00 0.00
PERIMETER_ZN_2 4786.00 2.00 0.00 0.00 0.00
PERIMETER_ZN_3 13319.83 36.17 0.00 0.00 0.00
PERIMETER_ZN_4 6802.50 1.50 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17719.00 173.00 0.00 0.00 0.00
Average 9321.50 44.50 0.00 0.00 0.00
Sum 55929.00 267.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:53

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104531E+10 4741.06 25-JAN-08:63 17.17 11.67 0.289374E+09 428.67 25-JAN-08:09 17.17 11.67
February 0.974879E+09 2694.48 03-FEB-08:62 16.33 6.16 0.266238E+09 410.22 03-FEB-08:09 16.33 6.16
March 0.112685E+10 2686.65 24-MAR-07:03 13.17 13.07 0.321010E+09 409.81 24-MAR-07:10 13.17 13.07
April 0.136507E+10 4463.51 28-APR-07:03 15.00 12.65 0.283066E+09 439.57 27-APR-07:10 15.00 12.65
May 0.165793E+10 5165.94 24-MAY-07:02 17.17 8.29 0.312375E+09 454.86 04-MAY-07:10 17.17 8.29
June 0.196763E+10 4506.27 23-JUN-07:02 17.17 13.94 0.314122E+09 469.22 27-JUN-07:10 18.17 15.51
July 0.221297E+10 4465.75 10-JUL-07:02 18.17 14.44 0.287171E+09 469.22 17-JUL-07:10 15.92 14.75
August 0.250085E+10 4543.16 22-AUG-07:02 16.22 13.67 0.330062E+09 469.22 30-AUG-07:10 18.17 15.51
September 0.191561E+10 4621.07 29-SEP-07:02 24.00 14.17 0.286029E+09 469.22 11-SEP-07:10 24.00 14.17
October 0.212672E+10 5216.57 18-OCT-07:02 17.67 10.06 0.300489E+09 469.21 18-OCT-07:10 17.67 10.06
November 0.143941E+10 4551.76 01-NOV-07:03 11.17 11.08 0.297055E+09 427.02 10-NOV-08:09 16.33 14.82
December 0.117211E+10 4915.82 05-DEC-08:62 19.83 10.42 0.281533E+09 421.74 06-DEC-08:09 16.67 8.04
                     
Annual Sum or Average 0.195053E+11         0.356852E+10        
Minimum of Months 0.974879E+09 2686.65   11.17 6.16 0.266238E+09 409.81   13.17 6.16
Maximum of Months 0.250085E+10 5216.57   24.00 14.44 0.330062E+09 469.22   24.00 15.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127512E+10 4000.46 18-JAN-14:25 23.80 14.82 0.218006E+09 305.01 25-JAN-15:30 16.00 13.69
February 0.816179E+09 3354.89 03-FEB-14:20 23.00 8.84 0.193918E+09 305.01 16-FEB-14:09 17.02 13.92
March 0.592981E+09 2856.05 23-MAR-14:10 22.83 17.30 0.227422E+09 305.02 24-MAR-12:50 19.17 15.93
April 0.629453E+09 2403.43 26-APR-13:50 26.17 16.81 0.207394E+09 305.02 27-APR-13:09 20.87 15.91
May 0.549275E+09 1909.08 04-MAY-13:53 23.00 16.67 0.229253E+09 305.13 15-MAY-10:00 21.00 15.00
June 0.833228E+09 1945.14 30-JUN-14:40 23.00 17.85 0.233466E+09 305.02 21-JUN-13:39 23.00 17.85
July 0.121924E+10 3087.33 31-JUL-11:55 28.00 21.19 0.214639E+09 305.64 25-JUL-07:10 28.00 21.19
August 0.158680E+10 3452.74 14-AUG-07:02 21.33 18.56 0.247013E+09 320.35 14-AUG-07:10 21.33 18.56
September 0.149027E+10 4812.78 29-SEP-07:02 24.00 14.17 0.214995E+09 366.33 29-SEP-12:09 36.00 18.21
October 0.214139E+10 4918.36 30-OCT-12:10 24.33 16.19 0.228857E+09 408.16 16-OCT-12:09 24.33 16.19
November 0.154950E+10 4287.29 28-NOV-13:30 24.50 10.63 0.222415E+09 305.02 09-NOV-15:09 24.50 10.63
December 0.146941E+10 4649.56 19-DEC-13:30 24.50 10.72 0.209792E+09 306.83 19-DEC-13:09 24.50 10.72
                     
Annual Sum or Average 0.141529E+11         0.264717E+10        
Minimum of Months 0.549275E+09 1909.08   21.33 8.84 0.193918E+09 305.01   16.00 10.63
Maximum of Months 0.214139E+10 4918.36   28.00 21.19 0.247013E+09 408.16   36.00 21.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.264112E+09 1072.14 20-JAN-09:52 19.00 14.77 92289028.09 181.61 04-JAN-11:00 19.00 14.77
February 0.218420E+09 891.82 01-FEB-11:55 26.00 14.67 83358987.55 180.93 01-FEB-15:20 19.00 15.14
March 0.249968E+09 1325.41 23-MAR-10:05 22.00 16.49 99637109.86 180.94 23-MAR-12:50 22.00 16.77
April 0.563996E+09 3259.38 26-APR-07:01 18.67 15.25 91717127.70 192.86 26-APR-07:10 18.67 15.25
May 0.637288E+09 3743.43 24-MAY-07:02 17.17 8.29 0.101476E+09 202.90 04-MAY-07:10 17.17 8.29
June 0.843129E+09 3570.14 05-JUN-07:01 17.17 14.01 0.102600E+09 210.01 30-JUN-07:10 18.33 16.73
July 0.114468E+10 3442.27 10-JUL-07:02 18.17 14.44 94395705.74 211.00 24-JUL-07:10 17.67 17.28
August 0.130564E+10 3380.79 22-AUG-07:02 16.22 13.67 0.108471E+09 211.00 07-AUG-07:10 16.22 13.67
September 0.833296E+09 3639.36 29-SEP-07:02 24.00 14.17 93514642.74 211.05 29-SEP-07:10 24.00 14.17
October 0.916979E+09 3745.03 18-OCT-07:02 17.67 10.06 98253691.93 211.00 17-OCT-07:10 17.67 10.06
November 0.418962E+09 967.42 20-NOV-09:55 16.00 14.13 96061325.84 180.94 13-NOV-13:50 16.00 14.13
December 0.298217E+09 1039.25 05-DEC-09:53 26.00 13.09 89808189.60 181.49 18-DEC-08:30 20.00 7.73
                     
Annual Sum or Average 0.769469E+10         0.115158E+10        
Minimum of Months 0.218420E+09 891.82   16.00 8.29 83358987.55 180.93   16.00 7.73
Maximum of Months 0.130564E+10 3745.03   26.00 16.49 0.108471E+09 211.05   24.00 17.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258371E+09 1158.16 18-JAN-15:02 22.83 14.90 0.202791E+09 305.00 26-JAN-14:09 16.83 11.93
February 0.206178E+09 944.10 03-FEB-15:35 21.67 9.69 0.185607E+09 305.01 08-FEB-16:19 14.33 10.58
March 0.279280E+09 1131.44 23-MAR-15:45 21.17 17.23 0.220706E+09 304.99 03-MAR-15:20 21.17 17.23
April 0.520638E+09 1627.04 26-APR-14:27 24.50 16.53 0.208294E+09 305.31 17-APR-10:09 24.50 16.53
May 0.748133E+09 1896.00 04-MAY-14:02 22.83 16.63 0.232540E+09 305.01 02-MAY-13:39 22.83 16.63
June 0.105203E+10 3858.40 21-JUN-07:02 18.17 15.02 0.235465E+09 328.21 30-JUN-07:10 18.33 16.73
July 0.134637E+10 3983.82 10-JUL-07:02 18.17 14.44 0.215900E+09 346.67 24-JUL-07:10 17.67 17.28
August 0.146894E+10 3620.10 01-AUG-07:02 18.00 15.44 0.247792E+09 342.03 14-AUG-07:10 21.33 18.56
September 0.997288E+09 4138.64 29-SEP-07:02 24.00 14.17 0.214138E+09 321.46 29-SEP-07:10 24.00 14.17
October 0.110011E+10 4293.46 17-OCT-07:02 21.83 11.05 0.224556E+09 355.69 02-OCT-07:10 21.83 11.05
November 0.427466E+09 1178.93 10-NOV-14:23 19.50 15.78 0.217582E+09 305.48 28-NOV-09:50 20.83 8.36
December 0.277183E+09 1073.94 05-DEC-15:23 24.00 12.83 0.199764E+09 305.04 05-DEC-09:30 24.00 12.83
                     
Annual Sum or Average 0.868198E+10         0.260513E+10        
Minimum of Months 0.206178E+09 944.10   18.00 9.69 0.185607E+09 304.99   14.33 8.36
Maximum of Months 0.146894E+10 4293.46   24.50 17.23 0.247792E+09 355.69   24.50 18.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.262904E+09 1434.88 18-JAN-15:25 22.50 15.11 0.125187E+09 180.98 24-JAN-09:30 22.00 13.54
February 0.223945E+09 1468.92 01-FEB-16:25 17.50 15.03 0.114202E+09 181.53 22-FEB-11:50 18.00 13.24
March 0.248154E+09 1831.66 23-MAR-15:55 21.00 17.19 0.136006E+09 181.51 13-MAR-10:50 21.00 17.19
April 0.527854E+09 2206.95 26-APR-15:55 22.00 16.41 0.125983E+09 188.00 27-APR-07:10 16.17 14.82
May 0.628211E+09 2692.33 04-MAY-07:02 18.17 14.03 0.139518E+09 191.41 04-MAY-07:10 18.17 14.03
June 0.854472E+09 3928.48 21-JUN-07:02 18.17 15.02 0.141022E+09 207.51 26-JUN-07:10 18.33 15.57
July 0.111034E+10 4032.04 10-JUL-07:02 18.17 14.44 0.129466E+09 211.25 05-JUL-07:10 18.17 14.44
August 0.124795E+10 3966.98 22-AUG-07:02 16.22 13.67 0.148591E+09 211.00 14-AUG-07:10 16.22 13.67
September 0.893164E+09 4238.30 29-SEP-07:02 24.00 14.17 0.128324E+09 203.00 29-SEP-07:10 24.00 14.17
October 0.916609E+09 4374.53 18-OCT-07:02 17.67 10.06 0.134330E+09 211.00 17-OCT-07:10 17.67 10.06
November 0.460551E+09 1575.85 10-NOV-15:35 18.33 15.59 0.131396E+09 180.98 06-NOV-10:39 18.33 15.59
December 0.307567E+09 1536.12 19-DEC-15:45 21.17 8.50 0.122199E+09 180.95 07-DEC-08:00 21.17 8.50
                     
Annual Sum or Average 0.768172E+10         0.157623E+10        
Minimum of Months 0.223945E+09 1434.88   16.22 8.50 0.114202E+09 180.95   16.17 8.50
Maximum of Months 0.124795E+10 4374.53   24.00 17.19 0.148591E+09 211.25   24.00 17.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83 8.36 0.00 0.00 01-JAN-00:10 8.83 8.36
February 0.00 0.00 01-FEB-00:10 13.23 11.35 0.00 0.00 01-FEB-00:10 13.23 11.35
March 0.00 0.00 01-MAR-00:10 7.63 6.62 0.00 0.00 01-MAR-00:10 7.63 6.62
April 0.00 0.00 01-APR-00:10 9.63 8.61 0.00 0.00 01-APR-00:10 9.63 8.61
May 0.00 0.00 01-MAY-00:10 15.20 14.50 0.00 0.00 01-MAY-00:10 15.20 14.50
June 0.00 0.00 01-JUN-00:10 13.07 12.03 0.00 0.00 01-JUN-00:10 13.07 12.03
July 0.00 0.00 01-JUL-00:10 16.43 15.81 0.00 0.00 01-JUL-00:10 16.43 15.81
August 0.00 0.00 01-AUG-00:10 18.07 17.20 0.00 0.00 01-AUG-00:10 18.07 17.20
September 0.00 0.00 01-SEP-00:10 16.07 14.83 0.00 0.00 01-SEP-00:10 16.07 14.83
October 0.00 0.00 01-OCT-00:10 18.42 17.39 0.00 0.00 01-OCT-00:10 18.42 17.39
November 0.00 0.00 01-NOV-00:10 14.77 11.07 0.00 0.00 01-NOV-00:10 14.77 11.07
December 0.00 0.00 01-DEC-00:10 10.63 5.44 0.00 0.00 01-DEC-00:10 10.63 5.44
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   7.63 5.44 0.00 0.00   7.63 5.44
Maximum of Months 0.00 0.00   18.42 17.39 0.00 0.00   18.42 17.39



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2743782.58 5050.82 02-JAN-08:62 11.33
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 44223.21 100.09 26-APR-17:02 21.50
May 0.00 0.00 01-MAY-00:10 15.20
June 294076.70 184.40 29-JUN-17:02 22.83
July 2173022.61 263.15 18-JUL-17:02 24.00
August 709108.10 182.75 17-AUG-17:02 22.92
September 1915942.57 678.39 29-SEP-17:02 29.50
October 1205580.09 429.78 16-OCT-17:02 26.50
November 0.00 0.00 01-NOV-00:10 14.77
December 5871.05 48.93 05-DEC-08:04 19.83
         
Annual Sum or Average 9091606.91      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 2743782.58 5050.82   29.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 45205632.34 7604.01 03-JAN-07:01 3.67
February 19502493.83 4937.96 09-FEB-08:62 9.40
March 85814972.60 6241.42 10-MAR-08:61 14.67
April 8673652.33 5915.44 20-APR-07:01 13.33
May 9168773.42 5984.79 15-MAY-07:01 13.50
June 5706674.42 239.29 29-JUN-17:02 22.83
July 8426588.74 288.82 31-JUL-17:12 23.67
August 7879324.47 218.57 17-AUG-17:02 22.92
September 3752148.99 539.26 29-SEP-17:12 29.00
October 3688491.76 337.83 16-OCT-17:12 26.00
November 278036.02 83.88 27-NOV-07:52 18.00
December 9042844.61 4282.59 13-DEC-08:62 8.50
         
Annual Sum or Average 0.207140E+09      
Minimum of Months 278036.02 83.88   3.67
Maximum of Months 85814972.60 7604.01   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20794548.63 5290.56 03-JAN-07:01 3.67
February 5006211.49 2887.49 27-FEB-08:62 9.50
March 5392777.79 3296.13 30-MAR-06:02 5.58
April 1053343.79 141.40 26-APR-17:02 21.50
May 1185658.00 86.44 18-MAY-17:02 19.50
June 3625179.27 178.69 29-JUN-17:02 22.83
July 6609851.17 222.93 31-JUL-17:12 23.67
August 6387901.04 161.61 17-AUG-17:02 22.92
September 4501012.12 395.06 29-SEP-17:12 29.00
October 6418043.11 294.75 16-OCT-17:12 26.00
November 1201198.96 117.17 27-NOV-08:12 19.00
December 3817406.64 529.26 13-DEC-08:62 8.50
         
Annual Sum or Average 65993132.02      
Minimum of Months 1053343.79 86.44   3.67
Maximum of Months 20794548.63 5290.56   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 84732102.12 6974.42 03-JAN-07:01 3.67
February 12347628.70 4958.07 21-FEB-08:62 12.33
March 27877128.55 5463.56 10-MAR-08:61 14.67
April 2903015.45 3087.08 03-APR-07:02 11.83
May 33951.77 34.67 18-MAY-17:02 19.50
June 595145.11 193.27 29-JUN-17:02 22.83
July 3477330.49 245.43 31-JUL-17:12 23.67
August 2654633.41 188.59 17-AUG-17:02 22.92
September 2339269.56 553.96 29-SEP-17:02 29.50
October 2980352.06 375.24 16-OCT-17:02 26.50
November 5261698.74 1267.80 24-NOV-08:63 10.67
December 25498988.63 4836.93 26-DEC-08:62 11.83
         
Annual Sum or Average 0.170701E+09      
Minimum of Months 33951.77 34.67   3.67
Maximum of Months 84732102.12 6974.42   29.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 50016355.23 5943.95 03-JAN-07:01 3.67
February 16435905.72 2870.73 27-FEB-08:62 9.50
March 21411050.22 4716.86 08-MAR-08:61 9.67
April 3777247.69 263.22 03-APR-10:02 22.67
May 3672452.28 175.30 04-MAY-07:04 18.17
June 6969398.91 183.92 23-JUN-07:04 17.17
July 9019772.42 232.08 31-JUL-17:12 23.67
August 11716961.52 228.49 15-AUG-07:05 19.50
September 7878820.73 418.93 29-SEP-17:12 29.00
October 9953750.19 407.29 16-OCT-07:05 25.50
November 7343076.63 252.89 27-NOV-09:43 21.83
December 18805750.02 2196.87 13-DEC-08:62 8.50
         
Annual Sum or Average 0.167001E+09      
Minimum of Months 3672452.28 175.30   3.67
Maximum of Months 50016355.23 5943.95   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.944342E+09 784.13 02-JAN-08:09 0.129836E+10 1014.68 02-JAN-08:09
February 0.853760E+09 784.13 01-FEB-08:09 0.117388E+10 1014.68 01-FEB-08:09
March 0.994276E+09 784.13 01-MAR-08:09 0.137025E+10 1014.68 01-MAR-08:09
April 0.905826E+09 784.13 03-APR-07:10 0.124598E+10 1014.68 03-APR-07:10
May 0.969309E+09 784.13 01-MAY-07:10 0.133431E+10 1014.68 01-MAY-07:10
June 0.955759E+09 784.13 01-JUN-07:10 0.131568E+10 1014.68 01-JUN-07:10
July 0.919376E+09 784.13 03-JUL-07:10 0.126352E+10 1014.68 03-JUL-07:10
August 0.994276E+09 784.13 01-AUG-07:10 0.137025E+10 1014.68 01-AUG-07:10
September 0.905826E+09 784.13 01-SEP-07:10 0.124379E+10 1014.68 01-SEP-07:10
October 0.944342E+09 784.13 02-OCT-07:10 0.129946E+10 1014.68 02-OCT-07:10
November 0.930792E+09 784.13 01-NOV-07:10 0.128083E+10 1014.68 01-NOV-07:10
December 0.919376E+09 784.13 01-DEC-08:09 0.126242E+10 1014.68 01-DEC-08:09
             
Annual Sum or Average 0.112373E+11     0.154587E+11    
Minimum of Months 0.853760E+09 784.13   0.117388E+10 1014.68  
Maximum of Months 0.994276E+09 784.13   0.137025E+10 1014.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.616943E+09 594.42 02-JAN-16:49 0.984244E+09 769.19 02-JAN-08:09
February 0.551349E+09 585.31 27-FEB-16:00 0.889874E+09 769.19 01-FEB-08:09
March 0.642410E+09 566.12 16-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.581867E+09 562.87 21-APR-15:00 0.944536E+09 769.19 03-APR-07:10
May 0.631355E+09 558.76 09-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.628434E+09 554.63 09-JUN-07:10 0.997370E+09 769.19 01-JUN-07:10
July 0.603034E+09 547.60 12-JUL-07:10 0.957827E+09 769.19 03-JUL-07:10
August 0.642179E+09 558.56 21-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.585461E+09 571.50 18-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.614415E+09 569.78 24-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.606353E+09 594.42 06-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.602424E+09 594.42 01-DEC-16:40 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.730622E+10     0.117187E+11    
Minimum of Months 0.551349E+09 547.60   0.889874E+09 769.19  
Maximum of Months 0.642410E+09 594.42   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.385213E+09 352.62 02-JAN-16:49 0.583867E+09 456.29 02-JAN-08:09
February 0.342978E+09 348.06 27-FEB-16:00 0.527885E+09 456.29 01-FEB-08:09
March 0.395773E+09 338.22 02-MAR-16:00 0.616194E+09 456.29 01-MAR-08:09
April 0.358487E+09 337.69 21-APR-15:00 0.560311E+09 456.29 03-APR-07:10
May 0.382410E+09 328.40 09-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.377403E+09 324.59 09-JUN-07:10 0.591653E+09 456.29 01-JUN-07:10
July 0.362306E+09 321.08 28-JUL-15:39 0.568196E+09 456.29 03-JUL-07:10
August 0.392484E+09 328.01 21-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.362780E+09 338.64 21-SEP-07:30 0.559325E+09 456.29 01-SEP-07:10
October 0.383959E+09 342.40 20-OCT-15:00 0.584359E+09 456.29 02-OCT-07:10
November 0.377305E+09 352.62 06-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.376360E+09 352.62 01-DEC-16:40 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.449746E+10     0.695170E+10    
Minimum of Months 0.342978E+09 321.08   0.527885E+09 456.29  
Maximum of Months 0.395773E+09 352.62   0.616194E+09 456.29  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.680947E+09 594.42 02-JAN-16:49 0.984244E+09 769.19 02-JAN-08:09
February 0.604980E+09 586.41 27-FEB-16:00 0.889874E+09 769.19 01-FEB-08:09
March 0.692403E+09 571.18 16-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.620740E+09 565.85 21-APR-15:00 0.944536E+09 769.19 03-APR-07:10
May 0.644479E+09 560.10 09-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.631866E+09 554.23 09-JUN-07:10 0.997370E+09 769.19 01-JUN-07:10
July 0.612358E+09 546.80 12-JUL-07:10 0.957827E+09 769.19 03-JUL-07:10
August 0.675570E+09 560.77 21-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.631941E+09 574.38 21-SEP-07:30 0.942874E+09 769.19 01-SEP-07:10
October 0.674908E+09 575.28 24-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.667557E+09 594.42 06-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.666248E+09 594.42 01-DEC-16:40 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.780400E+10     0.117187E+11    
Minimum of Months 0.604980E+09 546.80   0.889874E+09 769.19  
Maximum of Months 0.692403E+09 594.42   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.384772E+09 352.62 02-JAN-16:49 0.583867E+09 456.29 02-JAN-08:09
February 0.340955E+09 347.29 27-FEB-16:00 0.527885E+09 456.29 01-FEB-08:09
March 0.394754E+09 340.55 16-MAR-07:10 0.616194E+09 456.29 01-MAR-08:09
April 0.358836E+09 336.85 05-APR-07:10 0.560311E+09 456.29 03-APR-07:10
May 0.380832E+09 335.85 09-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.374860E+09 333.81 09-JUN-07:10 0.591653E+09 456.29 01-JUN-07:10
July 0.361226E+09 331.62 12-JUL-07:10 0.568196E+09 456.29 03-JUL-07:10
August 0.391698E+09 336.46 21-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.360448E+09 341.87 21-SEP-07:10 0.559325E+09 456.29 01-SEP-07:10
October 0.381753E+09 342.19 24-OCT-07:10 0.584359E+09 456.29 02-OCT-07:10
November 0.375540E+09 352.62 06-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.376236E+09 352.62 01-DEC-16:40 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.448191E+10     0.695170E+10    
Minimum of Months 0.340955E+09 331.62   0.527885E+09 456.29  
Maximum of Months 0.394754E+09 352.62   0.616194E+09 456.29  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.944342E+09 0.129836E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.905826E+09 0.124598E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.969309E+09 0.133431E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.955759E+09 0.131568E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.919376E+09 0.126352E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.905826E+09 0.124379E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.944342E+09 0.129946E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.930792E+09 0.128083E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.919376E+09 0.126242E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.112373E+11 0.154587E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.616943E+09 0.984244E+09 0.00 0.00 0.00 0.00 1229367.25 0.554125E+09
February 0.488155E+09 0.551349E+09 0.889874E+09 0.00 0.00 0.00 0.00 612141.00 0.529339E+09
March 0.590925E+09 0.642410E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.00 0.641836E+09
April 0.513848E+09 0.581867E+09 0.944536E+09 0.00 0.00 0.00 0.00 1994218.17 0.392895E+09
May 0.565233E+09 0.631355E+09 0.101149E+10 0.00 0.00 0.00 0.00 30384.39 0.411257E+09
June 0.565233E+09 0.628434E+09 0.997370E+09 0.00 0.00 0.00 0.00 541679.30 0.293609E+09
July 0.513848E+09 0.603034E+09 0.957827E+09 0.00 0.00 0.00 0.00 12237593.39 0.195141E+09
August 0.590925E+09 0.642179E+09 0.103874E+10 0.00 0.00 0.00 0.00 12291680.99 0.227386E+09
September 0.513848E+09 0.585461E+09 0.942874E+09 0.00 0.00 0.00 0.00 16877625.07 0.275643E+09
October 0.539540E+09 0.614415E+09 0.985075E+09 0.00 0.00 0.00 0.00 28481596.76 0.308303E+09
November 0.539540E+09 0.606353E+09 0.970953E+09 0.00 0.00 0.00 0.00 146614.38 0.523830E+09
December 0.513848E+09 0.602424E+09 0.956997E+09 0.00 0.00 0.00 0.00 1863556.12 0.523779E+09
                   
Annual Sum or Average 0.647448E+10 0.730622E+10 0.117187E+11 0.00 0.00 0.00 0.00 76306456.81 0.487714E+10
Minimum of Months 0.488155E+09 0.551349E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 0.195141E+09
Maximum of Months 0.590925E+09 0.642410E+09 0.103874E+10 0.00 0.00 0.00 0.00 28481596.76 0.641836E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.385213E+09 0.583867E+09 0.00 0.00 0.00 0.00 162210.87 77855834.89
February 0.211974E+09 0.342978E+09 0.527885E+09 0.00 0.00 0.00 0.00 14858.69 89632797.59
March 0.256600E+09 0.395773E+09 0.616194E+09 0.00 0.00 0.00 0.00 0.00 0.100857E+09
April 0.223130E+09 0.358487E+09 0.560311E+09 0.00 0.00 0.00 0.00 70347.44 62898565.79
May 0.245443E+09 0.382410E+09 0.600030E+09 0.00 0.00 0.00 0.00 1099.00 76338202.01
June 0.245443E+09 0.377403E+09 0.591653E+09 0.00 0.00 0.00 0.00 15143.16 45873689.55
July 0.223130E+09 0.362306E+09 0.568196E+09 0.00 0.00 0.00 0.00 548894.47 38390000.61
August 0.256600E+09 0.392484E+09 0.616194E+09 0.00 0.00 0.00 0.00 508547.76 45610634.56
September 0.223130E+09 0.362780E+09 0.559325E+09 0.00 0.00 0.00 0.00 729580.03 38752805.76
October 0.234287E+09 0.383959E+09 0.584359E+09 0.00 0.00 0.00 0.00 2517390.22 59303240.21
November 0.234287E+09 0.377305E+09 0.575982E+09 0.00 0.00 0.00 0.00 124267.27 79246019.32
December 0.223130E+09 0.376360E+09 0.567703E+09 0.00 0.00 0.00 0.00 86352.99 82799402.60
                   
Annual Sum or Average 0.281144E+10 0.449746E+10 0.695170E+10 0.00 0.00 0.00 0.00 4778691.90 0.797558E+09
Minimum of Months 0.211974E+09 0.342978E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 38390000.61
Maximum of Months 0.256600E+09 0.395773E+09 0.616194E+09 0.00 0.00 0.00 0.00 2517390.22 0.100857E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.680947E+09 0.984244E+09 0.00 0.00 0.00 0.00 460477.88 0.108735E+09
February 0.488155E+09 0.604980E+09 0.889874E+09 0.00 0.00 0.00 0.00 22287.90 0.128127E+09
March 0.590925E+09 0.692403E+09 0.103874E+10 0.00 0.00 0.00 0.00 76559.15 0.144707E+09
April 0.513848E+09 0.620740E+09 0.944536E+09 0.00 0.00 0.00 0.00 696730.64 88530658.16
May 0.565233E+09 0.644479E+09 0.101149E+10 0.00 0.00 0.00 0.00 1646.22 0.110123E+09
June 0.565233E+09 0.631866E+09 0.997370E+09 0.00 0.00 0.00 0.00 22749.05 66394883.90
July 0.513848E+09 0.612358E+09 0.957827E+09 0.00 0.00 0.00 0.00 827385.48 52631854.73
August 0.590925E+09 0.675570E+09 0.103874E+10 0.00 0.00 0.00 0.00 800631.07 62529623.02
September 0.513848E+09 0.631941E+09 0.942874E+09 0.00 0.00 0.00 0.00 1230178.35 54153647.95
October 0.539540E+09 0.674908E+09 0.985075E+09 0.00 0.00 0.00 0.00 4759183.93 83058936.49
November 0.539540E+09 0.667557E+09 0.970953E+09 0.00 0.00 0.00 0.00 613164.67 0.112647E+09
December 0.513848E+09 0.666248E+09 0.956997E+09 0.00 0.00 0.00 0.00 480966.11 0.116028E+09
                   
Annual Sum or Average 0.647448E+10 0.780400E+10 0.117187E+11 0.00 0.00 0.00 0.00 9991960.43 0.112767E+10
Minimum of Months 0.488155E+09 0.604980E+09 0.889874E+09 0.00 0.00 0.00 0.00 1646.22 52631854.73
Maximum of Months 0.590925E+09 0.692403E+09 0.103874E+10 0.00 0.00 0.00 0.00 4759183.93 0.144707E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.384772E+09 0.583867E+09 0.00 0.00 0.00 0.00 182523.43 77609626.53
February 0.289580E+09 0.340955E+09 0.527885E+09 0.00 0.00 0.00 0.00 14858.62 91240821.51
March 0.350544E+09 0.394754E+09 0.616194E+09 0.00 0.00 0.00 0.00 26719.73 0.102217E+09
April 0.304821E+09 0.358836E+09 0.560311E+09 0.00 0.00 0.00 0.00 352768.38 65716146.59
May 0.335303E+09 0.380832E+09 0.600030E+09 0.00 0.00 0.00 0.00 1095.82 79960165.11
June 0.335303E+09 0.374860E+09 0.591653E+09 0.00 0.00 0.00 0.00 15165.82 49534149.63
July 0.304821E+09 0.361226E+09 0.568196E+09 0.00 0.00 0.00 0.00 549157.84 41472486.67
August 0.350544E+09 0.391698E+09 0.616194E+09 0.00 0.00 0.00 0.00 519975.94 48655816.88
September 0.304821E+09 0.360448E+09 0.559325E+09 0.00 0.00 0.00 0.00 768594.06 41655169.21
October 0.320062E+09 0.381753E+09 0.584359E+09 0.00 0.00 0.00 0.00 2804352.60 61293895.61
November 0.320062E+09 0.375540E+09 0.575982E+09 0.00 0.00 0.00 0.00 275865.00 80727363.48
December 0.304821E+09 0.376236E+09 0.567703E+09 0.00 0.00 0.00 0.00 158489.46 83595085.20
                   
Annual Sum or Average 0.384075E+10 0.448191E+10 0.695170E+10 0.00 0.00 0.00 0.00 5669566.68 0.823677E+09
Minimum of Months 0.289580E+09 0.340955E+09 0.527885E+09 0.00 0.00 0.00 0.00 1095.82 41472486.67
Maximum of Months 0.350544E+09 0.394754E+09 0.616194E+09 0.00 0.00 0.00 0.00 2804352.60 0.102217E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131484E+10 0.251569E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.890561E+09 0.257998E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.819418E+09 0.379257E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.786892E+09 0.512515E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.715615E+09 0.523942E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.536818E+09 0.536705E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.660823E+09 0.596870E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.707212E+09 0.547712E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.872351E+09 0.419565E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110028E+10 0.303667E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118355E+10 0.258273E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143239E+10 0.226633E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110207E+11 0.481470E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.536818E+09 0.226633E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143239E+10 0.596870E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 784.13 02-JAN-08:09 1014.68 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 784.13 01-FEB-08:09 1014.68 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 784.13 01-MAR-08:09 1014.68 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 784.13 03-APR-07:10 1014.68 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 784.13 01-MAY-07:10 1014.68 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 784.13 01-JUN-07:10 1014.68 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 784.13 03-JUL-07:10 1014.68 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 784.13 01-AUG-07:10 1014.68 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 784.13 01-SEP-07:10 1014.68 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 784.13 02-OCT-07:10 1014.68 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 784.13 01-NOV-07:10 1014.68 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 784.13 01-DEC-08:09 1014.68 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 594.42 02-JAN-16:49 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 325.91 18-JAN-13:00 2722.69 09-JAN-07:10
February 732.70 01-FEB-08:09 585.31 27-FEB-16:00 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 275.29 01-FEB-12:10 2162.39 09-FEB-07:05
March 732.70 01-MAR-08:09 566.12 16-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2396.28 30-MAR-06:10
April 732.70 03-APR-07:10 562.87 21-APR-15:00 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 326.28 26-APR-11:03 1657.17 19-APR-06:05
May 732.70 01-MAY-07:10 558.76 09-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 17.10 03-MAY-12:00 1549.39 26-MAY-06:05
June 732.70 01-JUN-07:10 554.63 09-JUN-07:10 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 146.90 29-JUN-11:05 1354.20 01-JUN-06:03
July 732.70 03-JUL-07:10 547.60 12-JUL-07:10 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 633.09 19-JUL-12:00 1325.90 27-JUL-06:05
August 732.70 01-AUG-07:10 558.56 21-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 631.33 18-AUG-11:55 1469.11 28-AUG-06:05
September 732.70 01-SEP-07:10 571.50 18-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 1677.36 29-SEP-11:03 1599.98 20-SEP-06:05
October 732.70 02-OCT-07:10 569.78 24-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 1594.60 16-OCT-11:03 2048.95 30-OCT-06:03
November 732.70 01-NOV-07:10 594.42 06-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 26.60 28-NOV-14:00 2107.21 24-NOV-07:03
December 732.70 01-DEC-08:09 594.42 01-DEC-16:40 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 316.20 19-DEC-13:00 2533.99 22-DEC-07:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   547.60   769.19   0.00 0.00 0.00 0.00 0.00   1325.90  
Maximum of Months 732.70   594.42   769.19   0.00 0.00 0.00 0.00 1677.36   2722.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 352.62 02-JAN-16:49 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 17.52 15-JAN-09:52 156.26 27-JAN-04:55
February 434.65 01-FEB-08:09 348.06 27-FEB-16:00 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 4.37 01-FEB-11:55 147.26 25-FEB-03:00
March 434.65 01-MAR-08:09 338.22 02-MAR-16:00 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 168.82 28-MAR-18:55
April 434.65 03-APR-07:10 337.69 21-APR-15:00 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 6.42 26-APR-13:00 117.56 28-APR-18:53
May 434.65 01-MAY-07:10 328.40 09-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 0.23 03-MAY-12:00 135.99 12-MAY-19:00
June 434.65 01-JUN-07:10 324.59 09-JUN-07:10 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 2.59 29-JUN-10:55 78.17 13-JUN-18:02
July 434.65 03-JUL-07:10 321.08 28-JUL-15:39 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 10.51 31-JUL-13:00 105.69 20-JUL-18:02
August 434.65 01-AUG-07:10 328.01 21-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 8.46 17-AUG-14:00 60.36 27-AUG-17:52
September 434.65 01-SEP-07:10 338.64 21-SEP-07:30 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 25.28 29-SEP-14:00 73.61 06-SEP-18:02
October 434.65 02-OCT-07:10 342.40 20-OCT-15:00 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 47.45 15-OCT-08:51 121.42 30-OCT-03:00
November 434.65 01-NOV-07:10 352.62 06-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 13.81 19-NOV-13:00 148.82 23-NOV-04:00
December 434.65 01-DEC-08:09 352.62 01-DEC-16:40 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 5.51 17-DEC-13:00 141.14 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   321.08   456.29   0.00 0.00 0.00 0.00 0.00   60.36  
Maximum of Months 434.65   352.62   456.29   0.00 0.00 0.00 0.00 47.45   168.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 594.42 02-JAN-16:49 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 35.36 15-JAN-09:52 232.17 27-JAN-04:55
February 732.70 01-FEB-08:09 586.41 27-FEB-16:00 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 6.56 01-FEB-11:55 219.03 25-FEB-03:00
March 732.70 01-MAR-08:09 571.18 16-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 6.34 12-MAR-09:51 252.60 28-MAR-18:55
April 732.70 03-APR-07:10 565.85 21-APR-15:00 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 29.25 02-APR-13:00 173.46 28-APR-18:53
May 732.70 01-MAY-07:10 560.10 09-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 0.34 03-MAY-12:00 204.38 12-MAY-19:00
June 732.70 01-JUN-07:10 554.23 09-JUN-07:10 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 3.89 29-JUN-11:00 117.00 06-JUN-18:52
July 732.70 03-JUL-07:10 546.80 12-JUL-07:10 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 15.76 31-JUL-13:00 150.07 20-JUL-18:02
August 732.70 01-AUG-07:10 560.77 21-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 12.70 17-AUG-14:00 87.16 21-AUG-18:10
September 732.70 01-SEP-07:10 574.38 21-SEP-07:30 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 37.92 29-SEP-13:53 106.71 25-SEP-18:55
October 732.70 02-OCT-07:10 575.28 24-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 108.53 15-OCT-08:51 171.16 30-OCT-03:00
November 732.70 01-NOV-07:10 594.42 06-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 42.26 19-NOV-13:00 217.60 23-NOV-04:00
December 732.70 01-DEC-08:09 594.42 01-DEC-16:40 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 45.32 25-DEC-11:55 207.15 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   546.80   769.19   0.00 0.00 0.00 0.00 0.34   87.16  
Maximum of Months 732.70   594.42   769.19   0.00 0.00 0.00 0.00 108.53   252.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 352.62 02-JAN-16:49 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 19.46 15-JAN-09:52 157.07 27-JAN-04:55
February 434.65 01-FEB-08:09 347.29 27-FEB-16:00 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 4.37 01-FEB-11:55 148.93 25-FEB-03:00
March 434.65 01-MAR-08:09 340.55 16-MAR-07:10 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 2.40 11-MAR-11:03 175.06 28-MAR-18:55
April 434.65 03-APR-07:10 336.85 05-APR-07:10 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 16.31 02-APR-12:50 136.67 28-APR-18:53
May 434.65 01-MAY-07:10 335.85 09-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 0.23 03-MAY-12:00 138.23 12-MAY-19:00
June 434.65 01-JUN-07:10 333.81 09-JUN-07:10 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 2.59 29-JUN-11:00 99.51 13-JUN-18:02
July 434.65 03-JUL-07:10 331.62 12-JUL-07:10 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 10.51 31-JUL-13:00 119.39 20-JUL-18:02
August 434.65 01-AUG-07:10 336.46 21-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 8.46 17-AUG-14:00 74.59 27-AUG-17:52
September 434.65 01-SEP-07:10 341.87 21-SEP-07:10 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 25.28 29-SEP-13:53 89.33 03-SEP-16:52
October 434.65 02-OCT-07:10 342.19 24-OCT-07:10 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 67.20 15-OCT-08:51 122.68 11-OCT-02:00
November 434.65 01-NOV-07:10 352.62 06-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 19.77 19-NOV-13:00 152.26 23-NOV-04:00
December 434.65 01-DEC-08:09 352.62 01-DEC-16:40 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 19.88 25-DEC-11:55 142.82 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   331.62   456.29   0.00 0.00 0.00 0.00 0.23   74.59  
Maximum of Months 434.65   352.62   456.29   0.00 0.00 0.00 0.00 67.20   175.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2074.19 14-JAN-07:42 4866.99 30-JAN-11:50
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1783.70 01-FEB-02:30 5443.77 18-FEB-12:40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1639.09 07-MAR-06:00 6591.70 15-MAR-12:20
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1559.78 16-APR-01:00 7017.88 23-APR-12:30
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1475.90 16-MAY-24:00 7395.32 31-MAY-12:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1434.01 18-JUN-01:50 7096.65 01-JUN-12:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.58 14-JUL-05:25 7015.10 03-JUL-13:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1468.64 24-AUG-03:40 6623.83 01-AUG-13:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1661.07 29-SEP-06:42 6257.30 02-SEP-12:30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2238.05 16-OCT-06:52 5629.45 18-OCT-12:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1988.02 27-NOV-06:53 4968.38 04-NOV-11:50
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2015.84 26-DEC-05:00 4592.25 02-DEC-12:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.58   4592.25  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2238.05   7395.32  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 4741.06 25-JAN-08:63 2899.62 2352.39 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
February 2694.48 03-FEB-08:62 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
March 2686.65 24-MAR-07:03 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
April 4463.51 28-APR-07:03 3866.15 3136.51 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
May 5165.94 24-MAY-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
June 4506.27 23-JUN-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
July 4465.75 10-JUL-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
August 4543.16 22-AUG-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
September 4621.07 29-SEP-07:02 5799.23 4704.77 6088.06 0.00 0.00 0.00 0.00 0.00 0.00
October 5216.57 18-OCT-07:02 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
November 4551.76 01-NOV-07:03 2899.62 2352.39 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
December 4915.82 05-DEC-08:62 4832.69 3920.64 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2686.65   2899.62 2352.39 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5216.57   5799.23 4704.77 6088.06 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4000.46 18-JAN-14:25 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 0.00 2.25
February 3354.89 03-FEB-14:20 732.70 451.82 769.19 0.00 0.00 0.00 0.00 0.00 23.96
March 2856.05 23-MAR-14:10 732.70 451.82 769.19 0.00 0.00 0.00 0.00 0.00 26.66
April 2403.43 26-APR-13:50 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 55.96 0.00
May 1909.08 04-MAY-13:53 2930.79 1807.28 3076.76 0.00 0.00 0.00 0.00 0.00 24.24
June 1945.14 30-JUN-14:40 1465.40 970.45 1538.38 0.00 0.00 0.00 0.00 0.00 22.29
July 3087.33 31-JUL-11:55 894.47 803.24 1446.08 0.00 0.00 0.00 0.00 628.82 0.00
August 3452.74 14-AUG-07:02 4396.19 3151.40 4615.15 0.00 0.00 0.00 0.00 0.00 65.15
September 4812.78 29-SEP-07:02 4396.19 2710.91 4615.15 0.00 0.00 0.00 0.00 0.00 5.13
October 4918.36 30-OCT-12:10 732.70 451.82 769.19 0.00 0.00 0.00 0.00 10.31 0.00
November 4287.29 28-NOV-13:30 732.70 451.82 769.19 0.00 0.00 0.00 0.00 15.00 0.00
December 4649.56 19-DEC-13:30 1465.40 903.64 1538.38 0.00 0.00 0.00 0.00 15.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1909.08   732.70 451.82 769.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4918.36   4396.19 3151.40 4615.15 0.00 0.00 0.00 0.00 628.82 65.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1072.14 20-JAN-09:52 2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 0.00 3.82
February 891.82 01-FEB-11:55 869.29 577.96 912.59 0.00 0.00 0.00 0.00 4.37 0.00
March 1325.41 23-MAR-10:05 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 2.36
April 3259.38 26-APR-07:01 3477.17 2144.20 3650.35 0.00 0.00 0.00 0.00 0.00 0.00
May 3743.43 24-MAY-07:02 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 8.94
June 3570.14 05-JUN-07:01 3042.52 1876.17 3194.06 0.00 0.00 0.00 0.00 0.00 1.35
July 3442.27 10-JUL-07:02 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 8.82
August 3380.79 22-AUG-07:02 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 6.73
September 3639.36 29-SEP-07:02 2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 0.00 0.00
October 3745.03 18-OCT-07:02 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 0.00 9.33
November 967.42 20-NOV-09:55 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 10.76
December 1039.25 05-DEC-09:53 2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 3.86 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 891.82   869.29 577.96 912.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3745.03   3477.17 2144.20 3650.35 0.00 0.00 0.00 0.00 4.37 10.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1158.16 18-JAN-15:02 2930.79 2177.35 3076.76 0.00 0.00 0.00 0.00 0.00 3.33
February 944.10 03-FEB-15:35 2930.79 2160.10 3076.76 0.00 0.00 0.00 0.00 0.00 6.74
March 1131.44 23-MAR-15:45 2930.79 2105.77 3076.76 0.00 0.00 0.00 0.00 0.00 6.86
April 1627.04 26-APR-14:27 2198.10 1538.87 2307.57 0.00 0.00 0.00 0.00 1.79 0.00
May 1896.00 04-MAY-14:02 2930.79 1807.28 3076.76 0.00 0.00 0.00 0.00 0.00 5.30
June 3858.40 21-JUN-07:02 4396.19 2850.60 4615.15 0.00 0.00 0.00 0.00 0.00 10.43
July 3983.82 10-JUL-07:02 3663.49 2439.34 3845.95 0.00 0.00 0.00 0.00 0.00 11.99
August 3620.10 01-AUG-07:02 3663.49 2689.16 3845.95 0.00 0.00 0.00 0.00 0.00 7.52
September 4138.64 29-SEP-07:02 4396.19 3343.77 4615.15 0.00 0.00 0.00 0.00 0.00 0.00
October 4293.46 17-OCT-07:02 3663.49 2832.42 3845.95 0.00 0.00 0.00 0.00 0.00 7.28
November 1178.93 10-NOV-14:23 2930.79 2166.26 3076.76 0.00 0.00 0.00 0.00 0.00 17.38
December 1073.94 05-DEC-15:23 2198.10 1640.07 2307.57 0.00 0.00 0.00 0.00 0.26 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 944.10   2198.10 1538.87 2307.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4293.46   4396.19 3343.77 4615.15 0.00 0.00 0.00 0.00 1.79 17.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1434.88 18-JAN-15:25 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 2.93
February 1468.92 01-FEB-16:25 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 8.63
March 1831.66 23-MAR-15:55 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 4.61
April 2206.95 26-APR-15:55 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 3.00
May 2692.33 04-MAY-07:02 2173.23 1621.48 2281.47 0.00 0.00 0.00 0.00 0.00 7.26
June 3928.48 21-JUN-07:02 2607.88 1930.00 2737.76 0.00 0.00 0.00 0.00 0.00 7.29
July 4032.04 10-JUL-07:02 2173.23 1624.14 2281.47 0.00 0.00 0.00 0.00 0.00 8.56
August 3966.98 22-AUG-07:02 2173.23 1632.71 2281.47 0.00 0.00 0.00 0.00 0.00 6.52
September 4238.30 29-SEP-07:02 2607.88 2007.23 2737.76 0.00 0.00 0.00 0.00 0.00 0.00
October 4374.53 18-OCT-07:02 2173.23 1675.38 2281.47 0.00 0.00 0.00 0.00 0.00 8.89
November 1575.85 10-NOV-15:35 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 14.73
December 1536.12 19-DEC-15:45 1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 4.58
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1434.88   1738.59 1072.10 1825.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4374.53   2607.88 2007.23 2737.76 0.00 0.00 0.00 0.00 0.00 14.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 386.16 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1530.33 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 976.67 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.13
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 931.50 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 646.71 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 328.82 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1008.03 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1010.25 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 989.95 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 872.42 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 582.57 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1530.33 29.13



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.131815E+11 12635.78 18-JAN-13:30 3513714.26 3731.84 03-JAN-07:10
February 0.116284E+11 12246.66 01-FEB-15:30 0.00 0.00 01-FEB-00:10
March 0.133118E+11 12736.79 23-MAR-15:09 0.00 0.00 01-MAR-00:10
April 0.124918E+11 13096.49 26-APR-12:00 0.00 0.00 01-APR-00:10
May 0.132973E+11 12740.39 04-MAY-12:30 0.00 0.00 01-MAY-00:10
June 0.135616E+11 13299.50 29-JUN-12:20 0.00 0.00 01-JUN-00:10
July 0.137053E+11 14433.23 31-JUL-12:09 0.00 0.00 01-JUL-00:10
August 0.150214E+11 14330.23 14-AUG-10:50 0.00 0.00 01-AUG-00:10
September 0.133838E+11 15029.73 29-SEP-12:50 0.00 0.00 01-SEP-00:10
October 0.142342E+11 15482.07 16-OCT-10:00 0.00 0.00 01-OCT-00:10
November 0.131400E+11 13484.03 10-NOV-16:00 0.00 0.00 01-NOV-00:10
December 0.129147E+11 13502.23 05-DEC-16:49 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.159872E+12     3513714.26    
Minimum of Months 0.116284E+11 12246.66   0.00 0.00  
Maximum of Months 0.150214E+11 15482.07   3513714.26 3731.84  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.301222E+10 0.138326E+10 0.443459E+10 0.00 0.158509E+10 0.02 82160084.94 0.660866E+09 0.00 0.00 0.00 0.202329E+10 0.00
February 0.269402E+10 0.117063E+10 0.400939E+10 0.00 0.143413E+10 0.00 13547335.32 0.476916E+09 0.00 0.00 0.00 0.182972E+10 0.00
March 0.311962E+10 0.118183E+10 0.468012E+10 0.00 0.173605E+10 0.00 60862696.54 0.473732E+09 0.00 0.00 0.00 0.205963E+10 0.00
April 0.282576E+10 0.103164E+10 0.425568E+10 0.00 0.150961E+10 0.00 2384085.16 0.927224E+09 0.00 0.00 0.00 0.193956E+10 0.00
May 0.300838E+10 0.973925E+09 0.455735E+10 0.00 0.166057E+10 0.00 1177496.72 0.107741E+10 0.00 0.00 0.00 0.201847E+10 0.00
June 0.296832E+10 0.899246E+09 0.449372E+10 0.00 0.166057E+10 0.00 0.00 0.158378E+10 0.00 0.00 0.00 0.195593E+10 0.00
July 0.285830E+10 0.943669E+09 0.431556E+10 0.00 0.150961E+10 0.00 0.00 0.211483E+10 0.00 0.00 0.00 0.196333E+10 0.00
August 0.309621E+10 0.102132E+10 0.468012E+10 0.00 0.173605E+10 0.00 0.00 0.246857E+10 0.00 0.00 0.00 0.201917E+10 0.00
September 0.284646E+10 0.109585E+10 0.424819E+10 0.00 0.151032E+10 0.00 0.00 0.176634E+10 0.00 0.00 0.00 0.191669E+10 0.00
October 0.299938E+10 0.124855E+10 0.443833E+10 0.00 0.158606E+10 0.00 0.00 0.196561E+10 0.00 0.00 0.00 0.199628E+10 0.00
November 0.295755E+10 0.130986E+10 0.437470E+10 0.00 0.158509E+10 0.00 132429.50 0.956253E+09 0.00 0.00 0.00 0.195640E+10 0.00
December 0.294064E+10 0.141095E+10 0.431182E+10 0.00 0.150961E+10 0.00 8001691.31 0.736678E+09 0.00 0.00 0.00 0.199699E+10 0.00
                           
Annual Sum or Average 0.353268E+11 0.136707E+11 0.527996E+11 0.00 0.190228E+11 0.02 0.168266E+09 0.152082E+11 0.00 0.00 0.00 0.236755E+11 0.00
Minimum of Months 0.269402E+10 0.899246E+09 0.400939E+10 0.00 0.143413E+10 0.00 0.00 0.473732E+09 0.00 0.00 0.00 0.182972E+10 0.00
Maximum of Months 0.311962E+10 0.141095E+10 0.468012E+10 0.00 0.173605E+10 0.02 82160084.94 0.246857E+10 0.00 0.00 0.00 0.205963E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 3513714.26 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 3513714.26 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 3513714.26 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2678.20 02-JAN-16:49 1049.11 01-JAN-06:10 3465.65 02-JAN-08:09 0.00 1612.83 02-JAN-06:10 0.00 05-JAN-09:39 3389.34 03-JAN-07:10
February 2651.21 27-FEB-16:00 1049.11 01-FEB-06:10 3465.65 01-FEB-08:09 0.00 1612.83 01-FEB-06:10 0.00 01-FEB-07:10 1280.10 27-FEB-08:09
March 2596.45 16-MAR-07:10 1049.11 01-MAR-06:10 3465.65 01-MAR-08:09 0.00 1612.83 01-MAR-06:10 0.00 01-MAR-00:10 2854.37 30-MAR-06:10
April 2583.54 21-APR-15:00 1049.11 01-APR-05:10 3465.65 03-APR-07:10 0.00 1612.83 03-APR-05:10 0.00 01-APR-00:10 544.24 03-APR-07:10
May 2567.24 09-MAY-07:10 1049.11 01-MAY-18:30 3465.65 01-MAY-07:10 0.00 1612.83 01-MAY-05:10 0.00 01-MAY-00:10 246.31 15-MAY-07:10
June 2551.37 09-JUN-07:10 1049.11 01-JUN-18:49 3465.65 01-JUN-07:10 0.00 1612.83 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2528.09 12-JUL-07:10 1049.11 01-JUL-18:00 3465.65 03-JUL-07:10 0.00 1612.83 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2567.93 21-AUG-07:10 1049.11 01-AUG-18:49 3465.65 01-AUG-07:10 0.00 1612.83 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2610.11 18-SEP-07:10 1049.11 01-SEP-05:10 3465.65 01-SEP-07:10 0.00 1612.83 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2608.80 24-OCT-07:10 1049.11 01-OCT-05:10 3465.65 02-OCT-07:10 0.00 1612.83 02-OCT-05:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 2678.20 06-NOV-16:00 1049.11 01-NOV-05:10 3465.65 01-NOV-07:10 0.00 1612.83 01-NOV-05:10 0.00 01-NOV-00:10 180.87 24-NOV-08:09
December 2678.20 01-DEC-16:40 1049.11 01-DEC-06:10 3465.65 01-DEC-08:09 0.00 1612.83 01-DEC-06:10 0.00 01-DEC-00:10 1000.83 13-DEC-08:09
                           
Annual Sum or Average             0.00            
Minimum of Months 2528.09   1049.11   3465.65   0.00 1612.83   0.00   0.00  
Maximum of Months 2678.20   1049.11   3465.65   0.00 1612.83   0.00   3389.34  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 2450.10 18-JAN-13:00 0.00 0.00 0.00 2788.61 31-JAN-12:00 0.00
February 2150.18 01-FEB-11:00 0.00 0.00 0.00 2788.61 02-FEB-12:09 0.00
March 2555.21 23-MAR-15:09 0.00 0.00 0.00 2787.87 01-MAR-12:30 0.00
April 2899.60 26-APR-12:00 0.00 0.00 0.00 2785.15 04-APR-11:39 0.00
May 2706.41 04-MAY-14:09 0.00 0.00 0.00 2782.15 01-MAY-11:50 0.00
June 3114.11 29-JUN-12:00 0.00 0.00 0.00 2778.60 01-JUN-11:50 0.00
July 4314.95 31-JUL-12:00 0.00 0.00 0.00 2775.88 03-JUL-11:39 0.00
August 4150.21 14-AUG-10:00 0.00 0.00 0.00 2775.49 31-AUG-11:00 0.00
September 4885.84 29-SEP-12:00 0.00 0.00 0.00 2777.86 29-SEP-11:39 0.00
October 5460.02 16-OCT-10:00 0.00 0.00 0.00 2781.39 31-OCT-11:09 0.00
November 2469.42 28-NOV-13:00 0.00 0.00 0.00 2784.69 30-NOV-12:09 0.00
December 2519.84 05-DEC-15:09 0.00 0.00 0.00 2787.31 29-DEC-12:09 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 2150.18   0.00 0.00 0.00 2775.49   0.00
Maximum of Months 5460.02   0.00 0.00 0.00 2788.61   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 12635.78 18-JAN-13:30 2368.21 3465.65 0.00 0.00 1612.83 0.00 0.00 2413.83 0.00
February 12246.66 01-FEB-15:30 2369.26 3465.65 0.00 0.00 1612.83 0.00 0.00 2072.60 0.00
March 12736.79 23-MAR-15:09 2353.94 3465.65 0.00 0.00 1612.83 0.00 0.00 2555.21 0.00
April 13096.49 26-APR-12:00 2348.02 3465.65 0.00 0.00 1612.83 0.00 0.00 2899.60 0.00
May 12740.39 04-MAY-12:30 2273.30 3465.65 0.00 0.00 1612.83 0.00 0.00 2619.28 0.00
June 13299.50 29-JUN-12:20 2382.98 3465.65 0.00 0.00 1612.83 0.00 0.00 3073.51 0.00
July 14433.23 31-JUL-12:09 2337.50 3465.65 0.00 0.00 1612.83 0.00 0.00 4253.80 0.00
August 14330.23 14-AUG-10:50 2393.65 3465.65 0.00 0.00 1612.83 0.00 0.00 4105.77 0.00
September 15029.73 29-SEP-12:50 2323.40 3465.65 0.00 0.00 1612.83 0.00 0.00 4861.83 0.00
October 15482.07 16-OCT-10:00 2378.89 3465.65 0.00 0.00 1612.83 0.00 0.00 5460.02 0.00
November 13484.03 10-NOV-16:00 2678.20 3465.65 1049.11 0.00 1612.83 0.00 0.00 1931.90 0.00
December 13502.23 05-DEC-16:49 2678.20 3465.65 1049.11 0.00 1612.83 0.00 0.00 1948.36 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 12246.66   2273.30 3465.65 0.00 0.00 1612.83 0.00 0.00 1931.90 0.00
Maximum of Months 15482.07   2678.20 3465.65 1049.11 0.00 1612.83 0.00 0.00 5460.02 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 3731.84 03-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 3731.84   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.50 0.17 24.50
July 0.00 0.00 0.00 0.00 2.00 24.54 2.00 24.54
August 0.00 0.00 0.00 0.00 2.67 24.54 2.67 24.54
September 0.00 0.00 0.00 0.00 0.33 24.49 0.33 24.49
October 0.00 0.00 0.00 0.00 1.17 24.63 1.17 24.63
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.33 24.55 6.33 24.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 24.63 2.67 24.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 5.50 25.29 5.33 25.22
October 0.00 0.00 0.00 0.00 17.50 25.38 17.33 25.36
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   23.00 25.36 22.67 25.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 17.50 25.38 17.33 25.36



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 204.50 23.17 32.33 23.27 4.67 23.21
February 204.83 23.62 16.50 23.63 12.67 23.63
March 255.33 23.50 32.33 23.59 0.00 23.59
April 51.00 23.69 117.83 24.24 0.00 24.24
May 26.67 23.78 157.00 24.48 0.00 24.48
June 4.00 25.56 307.00 24.56 4.00 24.57
July 41.67 25.81 340.00 24.79 41.67 24.89
August 53.17 25.72 391.00 24.77 53.17 24.87
September 11.00 25.38 327.00 24.54 11.00 24.57
October 30.33 25.16 255.50 24.77 19.67 24.84
November 104.00 23.86 68.00 24.12 0.50 24.13
December 227.83 23.77 9.17 23.80 0.00 23.80
             
Annual Sum or Average 1214.33 23.80 2053.67 24.29 147.33 24.34
Minimum of Months 4.00 23.17 9.17 23.27 0.00 23.21
Maximum of Months 255.33 25.81 391.00 24.79 53.17 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 215.00 22.84 60.17 22.84 17.83 22.67
February 239.00 22.73 23.00 22.73 7.33 22.66
March 327.67 22.36 50.67 22.28 29.17 22.12
April 239.67 23.03 7.33 23.05 1.00 23.04
May 303.00 23.21 3.33 23.20 2.00 23.18
June 164.00 23.43 68.17 23.67 0.00 23.67
July 59.50 24.24 243.83 24.29 38.17 24.34
August 61.17 24.16 330.83 24.26 43.67 24.28
September 40.83 23.39 232.83 24.19 5.33 24.19
October 72.50 24.28 218.67 24.64 28.50 24.74
November 164.00 23.37 64.50 23.56 0.00 23.56
December 207.50 23.18 21.83 23.19 3.33 23.15
             
Annual Sum or Average 2093.83 23.09 1325.17 23.50 176.33 23.48
Minimum of Months 40.83 22.36 3.33 22.28 0.00 22.12
Maximum of Months 327.67 24.28 330.83 24.64 43.67 24.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 283.33 22.69 29.00 22.44 29.00 22.23
February 266.00 22.70 15.83 22.56 15.83 22.44
March 302.67 22.48 27.00 22.28 27.00 22.11
April 183.17 23.27 8.33 23.32 0.00 23.32
May 186.00 23.44 14.17 23.52 0.00 23.52
June 86.17 23.64 111.33 24.07 0.00 24.07
July 5.50 24.96 255.00 24.55 3.83 24.56
August 7.83 25.18 302.83 24.50 6.50 24.52
September 40.33 23.75 139.33 24.23 0.33 24.23
October 89.00 23.80 105.83 24.26 5.50 24.28
November 279.50 23.33 1.33 23.32 1.33 23.31
December 276.67 22.98 11.50 22.88 11.50 22.79
             
Annual Sum or Average 2006.17 23.04 1021.50 23.41 100.83 23.33
Minimum of Months 5.50 22.48 1.33 22.28 0.00 22.11
Maximum of Months 302.67 25.18 302.83 24.55 29.00 24.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 22.32 67.17 22.00 67.17 21.76
February 323.00 22.42 26.83 22.25 26.83 22.10
March 385.67 22.25 44.33 22.03 44.33 21.85
April 296.83 23.23 3.00 23.21 2.00 23.20
May 281.83 23.47 3.83 23.49 0.00 23.49
June 118.50 23.66 82.17 23.98 0.00 23.98
July 7.67 24.66 251.83 24.46 5.67 24.47
August 22.17 24.21 290.50 24.32 10.17 24.33
September 84.67 23.74 65.50 23.99 1.00 23.99
October 181.67 23.72 92.67 23.98 6.83 24.01
November 352.67 23.13 6.83 23.08 6.83 23.03
December 340.00 22.66 28.83 22.49 28.83 22.34
             
Annual Sum or Average 2751.67 22.90 963.50 23.09 199.67 22.98
Minimum of Months 7.67 22.25 3.00 22.00 0.00 21.76
Maximum of Months 385.67 24.66 290.50 24.46 67.17 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 326.33 22.78 37.33 22.53 37.33 22.32
February 300.33 22.92 12.83 22.82 12.50 22.73
March 343.17 22.69 39.33 22.59 25.17 22.45
April 190.83 23.46 73.83 23.84 0.00 23.84
May 183.83 23.59 86.00 24.03 0.00 24.03
June 67.33 23.83 185.50 24.69 2.33 24.72
July 24.00 27.25 307.83 25.09 24.00 25.24
August 18.83 26.90 353.67 24.92 18.83 25.02
September 14.00 23.84 212.50 24.66 0.17 24.66
October 84.17 23.78 157.17 24.42 3.00 24.44
November 284.33 23.44 6.00 23.43 2.00 23.42
December 328.00 23.13 14.67 23.03 14.17 22.94
             
Annual Sum or Average 2165.17 23.22 1486.67 23.77 139.50 23.73
Minimum of Months 14.00 22.69 6.00 22.53 0.00 22.32
Maximum of Months 343.17 27.25 353.67 25.09 37.33 25.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.918670E+09 0.201142E+09 164.74 0.770025E+09 0.148645E+09 0.00 1.00 25-JAN-08:63 0.00 01-JAN-00:10 5165.69 25-JAN-08:63 4721.82 25-JAN-08:63 1105.69 20-JAN-08:62 1014.80 25-JAN-08:63 0.00
February 0.807346E+09 0.177337E+09 167.05 0.673411E+09 0.133935E+09 0.00 0.54 03-FEB-08:62 0.00 01-FEB-00:10 2522.22 01-FEB-16:00 2493.66 03-FEB-08:62 598.50 01-FEB-16:30 538.63 01-FEB-12:00 0.00
March 0.910105E+09 0.198993E+09 192.25 0.702665E+09 0.207440E+09 0.00 0.63 24-MAR-07:03 0.00 01-MAR-00:10 3158.29 24-MAR-07:03 2387.19 23-MAR-14:00 928.54 24-MAR-07:03 660.03 23-MAR-14:00 0.00
April 0.151213E+10 0.325215E+09 198.22 0.119960E+10 0.312530E+09 0.00 1.00 13-APR-07:02 0.00 01-APR-00:10 5396.46 27-APR-07:03 4185.06 28-APR-07:03 1597.63 27-APR-07:12 1052.60 27-APR-07:03 0.00
May 0.184288E+10 0.393274E+09 219.34 0.150107E+10 0.341809E+09 0.00 1.00 01-MAY-07:03 0.00 01-MAY-00:10 5405.00 03-MAY-07:02 5055.60 24-MAY-07:02 1500.39 03-MAY-07:05 1053.78 03-MAY-07:02 0.00
June 0.248580E+10 0.520537E+09 221.61 0.193998E+10 0.545819E+09 0.00 1.00 01-JUN-07:02 0.00 01-JUN-00:10 5515.30 30-JUN-07:02 4361.44 13-JUN-07:01 1960.51 28-JUN-07:08 1067.53 30-JUN-07:02 0.00
July 0.304139E+10 0.627038E+09 213.85 0.231368E+10 0.727709E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5552.89 20-JUL-07:02 4338.56 10-JUL-07:02 2099.30 20-JUL-07:08 1147.72 31-JUL-13:00 0.00
August 0.349268E+10 0.720254E+09 244.81 0.262237E+10 0.870306E+09 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 5591.06 18-AUG-07:02 4268.08 22-AUG-07:02 2198.38 18-AUG-07:10 1133.71 14-AUG-11:00 0.00
September 0.248781E+10 0.522191E+09 200.80 0.192334E+10 0.564464E+09 0.00 1.00 01-SEP-07:03 0.00 01-SEP-00:10 5581.58 22-SEP-07:03 4944.71 29-SEP-07:02 2105.62 22-SEP-07:17 1128.90 29-SEP-13:00 0.00
October 0.260045E+10 0.553350E+09 216.87 0.220159E+10 0.398866E+09 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 5593.71 05-OCT-07:02 5138.31 16-OCT-06:03 2094.67 05-OCT-07:08 1268.02 16-OCT-11:00 0.00
November 0.139613E+10 0.302682E+09 209.30 0.119296E+10 0.203166E+09 0.00 1.00 01-NOV-07:03 0.00 01-NOV-00:10 5405.03 10-NOV-08:63 4296.03 09-NOV-08:62 1645.19 10-NOV-08:63 1053.79 10-NOV-08:63 0.00
December 0.102650E+10 0.226087E+09 192.59 0.935045E+09 91457429.27 0.00 1.00 05-DEC-08:62 0.00 01-DEC-00:10 5051.53 05-DEC-08:62 5051.53 05-DEC-08:62 693.33 08-DEC-08:63 992.23 05-DEC-08:62 0.00
                                       
Annual Sum or Average 0.225219E+11 0.476810E+10 2441.41 0.179757E+11 0.454615E+10 0.00                         0.00
Minimum of Months 0.807346E+09 0.177337E+09 164.74 0.673411E+09 91457429.27 0.00 0.54   0.00   2522.22   2387.19   598.50   538.63   0.00
Maximum of Months 0.349268E+10 0.720254E+09 244.81 0.262237E+10 0.870306E+09 0.00 1.00   0.00   5593.71   5138.31   2198.38   1268.02   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.126770E+10 0.271775E+09 164.72 0.119865E+10 69051992.18 0.00 0.87 20-JAN-13:05 0.00 01-JAN-00:10 4664.61 20-JAN-13:05 4369.66 18-JAN-14:05 654.10 20-JAN-13:05 935.70 20-JAN-13:05 0.00
February 0.770407E+09 0.166194E+09 123.00 0.722783E+09 47623867.91 0.00 0.75 03-FEB-14:20 0.00 01-FEB-00:10 3664.17 03-FEB-14:20 3664.17 03-FEB-14:20 480.63 01-FEB-16:00 806.96 01-FEB-12:05 0.00
March 0.549229E+09 0.119467E+09 108.07 0.474506E+09 74722719.90 0.00 0.71 23-MAR-14:00 0.00 01-MAR-00:10 3711.30 23-MAR-14:00 3162.75 23-MAR-14:00 627.80 24-MAR-12:40 783.76 23-MAR-14:00 0.00
April 0.748269E+09 0.164717E+09 143.68 0.639442E+09 0.108827E+09 0.00 0.63 26-APR-13:20 0.00 01-APR-00:10 3191.37 26-APR-13:30 2907.33 26-APR-13:30 493.25 27-APR-10:55 726.89 26-APR-13:00 0.00
May 0.662669E+09 0.146867E+09 158.00 0.575530E+09 87139015.85 0.00 0.51 04-MAY-14:00 0.00 01-MAY-00:10 2580.09 04-MAY-14:00 2217.24 04-MAY-13:53 376.44 05-MAY-14:50 563.33 04-MAY-14:00 0.00
June 0.118044E+10 0.258862E+09 197.07 0.946632E+09 0.233813E+09 0.00 0.58 29-JUN-13:00 0.00 01-JUN-00:10 3023.57 29-JUN-13:00 2276.50 27-JUN-13:00 853.57 28-JUN-12:10 655.06 29-JUN-13:00 0.00
July 0.183977E+10 0.398797E+09 198.29 0.141011E+10 0.429659E+09 0.00 0.90 31-JUL-12:00 0.00 01-JUL-00:10 4986.51 31-JUL-12:00 3687.32 31-JUL-11:55 1299.91 31-JUL-12:00 1080.46 31-JUL-12:00 0.00
August 0.236516E+10 0.507929E+09 228.30 0.180932E+10 0.555839E+09 0.00 1.00 14-AUG-07:02 0.00 01-AUG-00:10 5780.24 14-AUG-07:02 3742.24 14-AUG-07:02 2038.00 14-AUG-07:02 1118.25 14-AUG-07:02 0.00
September 0.196419E+10 0.422218E+09 198.10 0.161183E+10 0.352360E+09 0.00 1.00 29-SEP-07:02 0.00 01-SEP-00:10 5321.41 29-SEP-07:02 5321.41 29-SEP-07:02 1359.68 22-SEP-12:00 1301.02 29-SEP-12:05 0.00
October 0.257039E+10 0.549325E+09 210.19 0.230934E+10 0.261052E+09 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 5835.91 05-OCT-07:02 5321.22 31-OCT-13:35 2296.79 05-OCT-07:02 1315.79 16-OCT-11:10 0.00
November 0.159000E+10 0.336562E+09 186.44 0.148691E+10 0.103091E+09 0.00 0.94 20-NOV-13:05 0.00 01-NOV-00:10 5098.29 20-NOV-13:05 4693.24 28-NOV-13:50 801.32 20-NOV-13:05 1010.44 20-NOV-13:05 0.00
December 0.144893E+10 0.307246E+09 165.53 0.141499E+10 33932338.90 0.00 1.00 19-DEC-12:50 0.00 01-DEC-00:10 5073.51 19-DEC-13:15 5073.51 19-DEC-13:15 568.63 07-DEC-13:20 1083.26 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.169572E+11 0.364996E+10 2081.41 0.146000E+11 0.235711E+10 0.00                         0.00
Minimum of Months 0.549229E+09 0.119467E+09 108.07 0.474506E+09 33932338.90 0.00 0.51   0.00   2580.09   2217.24   376.44   563.33   0.00
Maximum of Months 0.257039E+10 0.549325E+09 228.30 0.230934E+10 0.555839E+09 0.00 1.00   0.00   5835.91   5321.41   2296.79   1315.79   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.289369E+09 65373455.52 141.31 0.268828E+09 20541105.17 0.00 0.39 20-JAN-12:00 0.00 01-JAN-00:10 1423.45 20-JAN-12:00 1267.97 20-JAN-11:55 199.65 20-JAN-09:52 313.29 20-JAN-12:00 0.00
February 0.221391E+09 49972690.20 121.87 0.206899E+09 14491735.28 0.00 0.35 01-FEB-11:55 0.00 01-FEB-00:10 1238.91 01-FEB-11:55 1238.91 01-FEB-11:55 145.60 01-FEB-16:30 294.27 01-FEB-11:55 0.00
March 0.249913E+09 55846343.22 120.71 0.216781E+09 33132475.63 0.00 0.46 23-MAR-10:20 0.00 01-MAR-00:10 1729.02 23-MAR-10:20 1532.36 23-MAR-10:05 259.50 23-MAR-16:00 375.81 23-MAR-10:20 0.00
April 0.688876E+09 0.152418E+09 187.99 0.610395E+09 78481171.20 0.00 1.00 26-APR-07:01 0.00 01-APR-00:10 4159.25 26-APR-07:01 3451.93 26-APR-07:01 707.32 26-APR-07:01 814.30 26-APR-07:01 0.00
May 0.774018E+09 0.170461E+09 208.62 0.699064E+09 74953895.59 0.00 1.00 03-MAY-07:02 0.00 01-MAY-00:10 4199.40 03-MAY-07:02 3952.85 24-MAY-07:02 890.07 03-MAY-07:02 820.39 03-MAY-07:02 0.00
June 0.111931E+10 0.244065E+09 217.36 0.959340E+09 0.159967E+09 0.00 1.00 05-JUN-07:01 0.00 01-JUN-00:10 4294.54 30-JUN-07:02 3688.94 05-JUN-07:01 1169.65 30-JUN-07:03 832.99 30-JUN-07:02 0.00
July 0.155905E+10 0.336276E+09 204.19 0.130243E+10 0.256614E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 4339.15 31-JUL-07:02 3654.49 10-JUL-07:02 1372.12 20-JUL-07:02 837.97 31-JUL-07:02 0.00
August 0.180307E+10 0.388943E+09 234.52 0.148996E+10 0.313104E+09 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 4372.39 07-AUG-07:02 3546.02 22-AUG-07:02 1448.48 18-AUG-07:12 841.27 07-AUG-07:02 0.00
September 0.112719E+10 0.248486E+09 199.54 0.953571E+09 0.173617E+09 0.00 1.00 06-SEP-07:03 0.00 01-SEP-00:10 4343.97 22-SEP-07:03 4051.99 29-SEP-07:02 1412.64 22-SEP-07:03 838.47 22-SEP-07:03 0.00
October 0.118204E+10 0.265603E+09 211.89 0.107123E+10 0.110815E+09 0.00 1.00 02-OCT-07:02 0.00 01-OCT-00:10 4385.09 05-OCT-07:02 3992.20 18-OCT-07:02 1527.30 05-OCT-07:04 969.18 16-OCT-10:53 0.00
November 0.469972E+09 0.105440E+09 195.67 0.437013E+09 32959050.57 0.00 0.35 28-NOV-13:55 0.00 01-NOV-00:10 1208.52 20-NOV-12:00 1201.26 28-NOV-13:55 202.05 10-NOV-12:00 281.44 28-NOV-13:55 0.00
December 0.323333E+09 73312123.88 152.85 0.316192E+09 7141025.84 0.00 0.40 05-DEC-09:52 0.00 01-DEC-00:10 1386.08 05-DEC-09:53 1386.08 05-DEC-09:53 155.94 07-DEC-16:10 327.73 05-DEC-09:53 0.00
                                       
Annual Sum or Average 0.980752E+10 0.215620E+10 2196.53 0.853170E+10 0.127582E+10 0.00                         0.00
Minimum of Months 0.221391E+09 49972690.20 120.71 0.206899E+09 7141025.84 0.00 0.35   0.00   1208.52   1201.26   145.60   281.44   0.00
Maximum of Months 0.180307E+10 0.388943E+09 234.52 0.148996E+10 0.313104E+09 0.00 1.00   0.00   4385.09   4051.99   1527.30   969.18   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.207985E+09 47008220.05 73.93 0.182620E+09 25365178.06 0.00 0.36 18-JAN-14:20 0.00 01-JAN-00:10 1507.30 18-JAN-14:30 1466.15 18-JAN-13:55 253.81 20-JAN-15:30 347.32 24-JAN-15:00 0.00
February 98922837.85 22395545.13 50.08 87941391.44 10981446.41 0.00 0.30 03-FEB-14:55 0.00 01-FEB-00:10 1194.07 03-FEB-14:55 1194.07 03-FEB-14:55 225.23 01-FEB-16:00 283.62 01-FEB-11:55 0.00
March 0.141703E+09 31616027.56 56.67 0.112045E+09 29657904.87 0.00 0.38 23-MAR-15:00 0.00 01-MAR-00:10 1691.81 23-MAR-15:10 1325.49 23-MAR-14:25 389.33 23-MAR-16:00 370.67 23-MAR-14:50 0.00
April 0.572379E+09 0.127160E+09 154.71 0.475659E+09 96720321.94 0.00 0.52 26-APR-13:55 0.00 01-APR-00:10 2301.67 26-APR-13:55 2052.36 26-APR-14:00 395.00 27-APR-10:55 527.23 26-APR-13:30 0.00
May 0.828858E+09 0.182579E+09 194.90 0.712393E+09 0.116465E+09 0.00 0.56 04-MAY-14:00 0.00 01-MAY-00:10 2502.44 04-MAY-14:00 2150.73 04-MAY-13:53 389.93 05-MAY-14:50 541.92 04-MAY-14:00 0.00
June 0.136472E+10 0.296530E+09 215.77 0.110796E+10 0.256759E+09 0.00 1.00 21-JUN-07:02 0.00 01-JUN-00:10 4982.24 30-JUN-07:02 3921.75 21-JUN-07:02 1509.85 30-JUN-07:02 968.14 30-JUN-07:02 0.00
July 0.189204E+10 0.405805E+09 199.69 0.148786E+10 0.404183E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5052.11 24-JUL-07:02 4054.40 10-JUL-07:02 1793.36 20-JUL-07:04 976.22 24-JUL-07:02 0.00
August 0.211857E+10 0.455255E+09 229.77 0.163785E+10 0.480719E+09 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 5106.45 07-AUG-07:02 3660.14 01-AUG-07:02 1968.16 07-AUG-07:04 981.60 07-AUG-07:02 0.00
September 0.134528E+10 0.295634E+09 198.23 0.107440E+10 0.270882E+09 0.00 1.00 22-SEP-07:03 0.00 01-SEP-00:10 5047.98 22-SEP-07:03 4573.88 29-SEP-07:02 1832.96 22-SEP-07:03 975.78 22-SEP-07:03 0.00
October 0.142192E+10 0.315889E+09 202.83 0.123173E+10 0.190188E+09 0.00 1.00 02-OCT-07:02 0.00 01-OCT-00:10 5106.05 05-OCT-07:02 4597.01 17-OCT-07:02 1903.67 05-OCT-07:13 1072.60 16-OCT-10:53 0.00
November 0.371563E+09 83440632.22 142.86 0.329309E+09 42254474.60 0.00 0.37 10-NOV-13:10 0.00 01-NOV-00:10 1605.14 10-NOV-13:10 1343.25 28-NOV-13:55 330.44 10-NOV-13:10 349.15 10-NOV-13:10 0.00
December 0.197275E+09 44924580.12 84.71 0.189454E+09 7820980.21 0.00 0.35 05-DEC-14:55 0.00 01-DEC-00:10 1449.85 05-DEC-14:55 1449.85 05-DEC-14:55 242.24 07-DEC-15:50 338.34 05-DEC-14:55 0.00
                                       
Annual Sum or Average 0.105612E+11 0.230824E+10 1804.17 0.862922E+10 0.193199E+10 0.00                         0.00
Minimum of Months 98922837.85 22395545.13 50.08 87941391.44 7820980.21 0.00 0.30   0.00   1194.07   1194.07   225.23   283.62   0.00
Maximum of Months 0.211857E+10 0.455255E+09 229.77 0.163785E+10 0.480719E+09 0.00 1.00   0.00   5106.45   4597.01   1968.16   1072.60   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.335102E+09 75566616.16 127.82 0.304373E+09 30729287.88 0.00 0.41 18-JAN-15:30 0.00 01-JAN-00:10 1822.23 18-JAN-15:30 1714.02 18-JAN-15:25 248.83 20-JAN-15:25 402.72 18-JAN-15:30 0.00
February 0.272236E+09 61016878.21 111.44 0.246866E+09 25370039.31 0.00 0.41 01-FEB-16:25 0.00 01-FEB-00:10 1837.92 01-FEB-16:25 1643.93 03-FEB-16:08 266.19 01-FEB-16:30 397.97 01-FEB-16:25 0.00
March 0.304595E+09 67809115.01 112.08 0.259516E+09 45078859.75 0.00 0.54 23-MAR-15:53 0.00 01-MAR-00:10 2460.91 23-MAR-15:53 2057.01 23-MAR-15:55 404.09 23-MAR-15:53 521.59 23-MAR-15:53 0.00
April 0.713195E+09 0.157714E+09 177.61 0.618304E+09 94890787.71 0.00 0.60 26-APR-15:53 0.00 01-APR-00:10 2758.16 26-APR-15:53 2467.74 26-APR-15:55 509.01 27-APR-07:03 586.21 26-APR-15:53 0.00
May 0.834135E+09 0.184228E+09 208.03 0.738272E+09 95862699.25 0.00 0.73 03-MAY-07:02 0.00 01-MAY-00:10 3478.58 03-MAY-07:02 2986.12 04-MAY-07:02 718.90 03-MAY-07:02 712.83 03-MAY-07:02 0.00
June 0.120400E+10 0.263782E+09 217.31 0.101631E+10 0.187691E+09 0.00 1.00 19-JUN-07:02 0.00 01-JUN-00:10 5133.06 30-JUN-07:02 4268.82 21-JUN-07:02 1423.97 28-JUN-07:03 996.83 30-JUN-07:02 0.00
July 0.159070E+10 0.346912E+09 204.25 0.130969E+10 0.281010E+09 0.00 1.00 03-JUL-07:02 0.00 01-JUL-00:10 5208.26 24-JUL-07:02 4409.31 10-JUL-07:02 1563.18 24-JUL-07:02 1005.33 24-JUL-07:02 0.00
August 0.181742E+10 0.396187E+09 232.59 0.147858E+10 0.338839E+09 0.00 1.00 01-AUG-07:02 0.00 01-AUG-00:10 5270.39 07-AUG-07:02 4292.93 22-AUG-07:02 1867.73 07-AUG-07:04 1011.24 07-AUG-07:02 0.00
September 0.125858E+10 0.277812E+09 199.28 0.105507E+10 0.203507E+09 0.00 1.00 06-SEP-07:03 0.00 01-SEP-00:10 5198.10 22-SEP-07:03 4817.85 29-SEP-07:02 1660.86 22-SEP-07:03 1004.27 22-SEP-07:03 0.00
October 0.124926E+10 0.281445E+09 212.20 0.111732E+10 0.131949E+09 0.00 1.00 02-OCT-06:02 0.00 01-OCT-00:10 5250.98 05-OCT-07:02 4792.75 18-OCT-07:02 1709.69 05-OCT-07:04 1009.50 05-OCT-07:02 0.00
November 0.574683E+09 0.128128E+09 184.30 0.524884E+09 49798784.24 0.00 0.45 10-NOV-15:23 0.00 01-NOV-00:10 2030.73 10-NOV-15:23 1707.93 10-NOV-15:35 324.48 10-NOV-15:13 436.73 10-NOV-15:23 0.00
December 0.377262E+09 85107846.29 141.40 0.363516E+09 13745702.38 0.00 0.42 19-DEC-15:40 0.00 01-DEC-00:10 1846.42 07-DEC-15:32 1781.14 05-DEC-15:40 253.51 07-DEC-15:43 403.91 05-DEC-15:30 0.00
                                       
Annual Sum or Average 0.105312E+11 0.232571E+10 2128.30 0.903270E+10 0.149847E+10 0.00                         0.00
Minimum of Months 0.272236E+09 61016878.21 111.44 0.246866E+09 13745702.38 0.00 0.41   0.00   1822.23   1643.93   248.83   397.97   0.00
Maximum of Months 0.181742E+10 0.396187E+09 232.59 0.147858E+10 0.338839E+09 0.00 1.00   0.00   5270.39   4817.85   1867.73   1011.24   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.17 21.51 24.66 62.77 42.48 0.00 0.00 0.00
April 29.94 6.99 22.95 37.79 35.00 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.33 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.30 2.93 21.37 31.62 25.10 0.00 0.00 0.00
September 41.34 18.74 22.60 62.94 29.86 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.25 0.00 0.00 0.00
November 78.57 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.78 26.31 22.46 68.66 35.85 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.66 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.16 21.51 24.65 62.75 42.49 0.00 0.00 0.00
April 29.80 6.93 22.87 37.44 35.01 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.32 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.27 2.91 21.35 31.53 25.10 0.00 0.00 0.00
September 41.22 18.69 22.52 62.72 29.93 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.24 0.00 0.00 0.00
November 78.56 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.75 26.30 22.45 68.60 35.86 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.65 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.16 21.51 24.65 62.75 42.49 0.00 0.00 0.00
April 29.80 6.93 22.87 37.44 35.01 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.32 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.27 2.91 21.35 31.53 25.10 0.00 0.00 0.00
September 41.21 18.69 22.51 62.71 29.96 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.24 0.00 0.00 0.00
November 78.56 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.75 26.30 22.45 68.60 35.86 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.65 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.16 21.51 24.65 62.75 42.49 0.00 0.00 0.00
April 29.80 6.93 22.87 37.44 35.01 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.32 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.27 2.91 21.35 31.53 25.10 0.00 0.00 0.00
September 41.20 18.69 22.51 62.71 29.96 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.24 0.00 0.00 0.00
November 78.56 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.75 26.30 22.45 68.60 35.86 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.65 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.16 21.51 24.65 62.75 42.49 0.00 0.00 0.00
April 29.80 6.93 22.87 37.44 35.01 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.32 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.27 2.91 21.35 31.53 25.10 0.00 0.00 0.00
September 41.21 18.69 22.52 62.71 29.95 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.24 0.00 0.00 0.00
November 78.56 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.75 26.30 22.45 68.60 35.86 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.65 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 82.17 60.67 21.49 121.59 47.51 0.00 0.00 0.00
February 64.17 40.04 24.13 90.25 41.74 0.00 0.00 0.00
March 46.17 21.51 24.66 62.76 42.47 0.00 0.00 0.00
April 29.92 6.98 22.94 37.70 34.98 0.00 0.00 0.00
May 23.11 0.00 23.11 21.90 31.80 0.00 0.00 0.00
June 22.91 0.00 22.91 24.33 25.33 0.00 0.00 0.00
July 22.59 0.07 22.52 26.08 23.84 0.00 0.00 0.00
August 24.30 2.93 21.37 31.61 25.09 0.00 0.00 0.00
September 41.26 18.72 22.55 62.79 29.89 0.00 0.00 0.00
October 62.92 42.21 20.72 99.99 34.25 0.00 0.00 0.00
November 78.57 55.89 22.67 115.29 44.94 0.00 0.00 0.00
December 87.89 67.25 20.64 130.30 48.69 0.00 0.00 0.00
                 
Annual Sum or Average 48.77 26.31 22.46 68.63 35.85 0.00 0.00 0.00
Minimum of Months 22.59 0.00 20.64 21.90 23.84 0.00 0.00 0.00
Maximum of Months 87.89 67.25 24.66 130.30 48.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 115.49 85.00 30.49 170.45 66.55 0.00 0.00 0.00
February 90.48 56.10 34.38 127.07 58.33 0.00 0.00 0.00
March 71.86 35.07 36.79 100.78 59.16 0.00 0.00 0.00
April 51.32 16.63 34.69 71.99 48.93 0.00 0.00 0.00
May 34.86 1.06 33.80 35.48 44.38 0.00 0.00 0.00
June 32.77 0.00 32.77 34.80 35.38 0.00 0.00 0.00
July 32.51 0.40 32.12 37.71 33.41 0.00 0.00 0.00
August 41.45 9.41 32.04 60.02 35.19 0.00 0.00 0.00
September 67.17 33.24 33.93 105.77 41.88 0.00 0.00 0.00
October 90.80 61.01 29.79 144.13 48.05 0.00 0.00 0.00
November 110.49 78.31 32.18 161.75 62.95 0.00 0.00 0.00
December 123.46 94.22 29.24 182.52 68.25 0.00 0.00 0.00
                 
Annual Sum or Average 71.81 39.14 32.66 102.61 50.17 0.00 0.00 0.00
Minimum of Months 32.51 0.00 29.24 34.80 33.41 0.00 0.00 0.00
Maximum of Months 123.46 94.22 36.79 182.52 68.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.34 17.41 14.93 39.76 43.67 0.00 0.00 0.00
February 33.66 15.54 18.12 38.88 38.86 0.00 0.00 0.00
March 40.71 18.25 22.46 49.04 39.93 0.00 0.00 0.00
April 51.47 25.40 26.07 69.21 33.24 0.00 0.00 0.00
May 48.10 19.76 28.35 61.71 30.86 0.00 0.00 0.00
June 47.53 20.00 27.53 64.76 25.01 0.00 0.00 0.00
July 54.07 26.19 27.88 78.28 24.12 0.00 0.00 0.00
August 53.89 28.05 25.84 79.43 24.61 0.00 0.00 0.00
September 39.22 17.62 21.60 54.67 27.72 0.00 0.00 0.00
October 35.38 18.18 17.20 50.74 31.40 0.00 0.00 0.00
November 32.53 16.63 15.90 39.11 41.75 0.00 0.00 0.00
December 31.25 17.47 13.78 38.19 44.77 0.00 0.00 0.00
                 
Annual Sum or Average 41.73 20.08 21.65 55.43 33.81 0.00 0.00 0.00
Minimum of Months 31.25 15.54 13.78 38.19 24.12 0.00 0.00 0.00
Maximum of Months 54.07 28.05 28.35 79.43 44.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.34 17.41 14.93 39.75 43.67 0.00 0.00 0.00
February 33.66 15.54 18.12 38.88 38.86 0.00 0.00 0.00
March 40.71 18.25 22.46 49.04 39.93 0.00 0.00 0.00
April 51.47 25.40 26.07 69.21 33.24 0.00 0.00 0.00
May 48.10 19.76 28.34 61.71 30.86 0.00 0.00 0.00
June 47.52 20.00 27.53 64.75 25.01 0.00 0.00 0.00
July 54.07 26.19 27.88 78.28 24.12 0.00 0.00 0.00
August 53.89 28.05 25.84 79.43 24.61 0.00 0.00 0.00
September 39.22 17.62 21.60 54.67 27.72 0.00 0.00 0.00
October 35.38 18.18 17.20 50.74 31.40 0.00 0.00 0.00
November 32.53 16.63 15.90 39.11 41.75 0.00 0.00 0.00
December 31.25 17.47 13.78 38.19 44.77 0.00 0.00 0.00
                 
Annual Sum or Average 41.73 20.08 21.65 55.43 33.81 0.00 0.00 0.00
Minimum of Months 31.25 15.54 13.78 38.19 24.12 0.00 0.00 0.00
Maximum of Months 54.07 28.05 28.34 79.43 44.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.34 17.41 14.93 39.75 43.67 0.00 0.00 0.00
February 33.66 15.54 18.12 38.88 38.86 0.00 0.00 0.00
March 40.71 18.25 22.46 49.04 39.93 0.00 0.00 0.00
April 51.47 25.40 26.07 69.21 33.24 0.00 0.00 0.00
May 48.10 19.76 28.34 61.71 30.86 0.00 0.00 0.00
June 47.52 20.00 27.53 64.75 25.01 0.00 0.00 0.00
July 54.07 26.19 27.88 78.28 24.12 0.00 0.00 0.00
August 53.89 28.05 25.84 79.43 24.61 0.00 0.00 0.00
September 39.22 17.62 21.60 54.67 27.72 0.00 0.00 0.00
October 35.38 18.18 17.20 50.74 31.40 0.00 0.00 0.00
November 32.53 16.63 15.90 39.11 41.75 0.00 0.00 0.00
December 31.25 17.47 13.78 38.19 44.77 0.00 0.00 0.00
                 
Annual Sum or Average 41.73 20.08 21.65 55.43 33.81 0.00 0.00 0.00
Minimum of Months 31.25 15.54 13.78 38.19 24.12 0.00 0.00 0.00
Maximum of Months 54.07 28.05 28.34 79.43 44.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.37 17.43 14.94 39.83 43.67 0.00 0.00 0.00
February 33.66 15.54 18.12 38.89 38.86 0.00 0.00 0.00
March 40.71 18.25 22.46 49.04 39.93 0.00 0.00 0.00
April 51.47 25.40 26.07 69.21 33.24 0.00 0.00 0.00
May 48.10 19.76 28.35 61.71 30.86 0.00 0.00 0.00
June 47.53 20.00 27.53 64.76 25.01 0.00 0.00 0.00
July 54.07 26.19 27.88 78.28 24.12 0.00 0.00 0.00
August 53.89 28.05 25.84 79.43 24.61 0.00 0.00 0.00
September 39.22 17.62 21.60 54.67 27.72 0.00 0.00 0.00
October 35.38 18.18 17.20 50.75 31.40 0.00 0.00 0.00
November 32.55 16.64 15.91 39.16 41.75 0.00 0.00 0.00
December 31.29 17.49 13.80 38.30 44.77 0.00 0.00 0.00
                 
Annual Sum or Average 41.74 20.08 21.66 55.45 33.81 0.00 0.00 0.00
Minimum of Months 31.29 15.54 13.80 38.30 24.12 0.00 0.00 0.00
Maximum of Months 54.07 28.05 28.35 79.43 44.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.73 44.25 0.00 0.00 0.00
February 14.90 0.00 14.90 10.16 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.35 0.08 21.27 20.09 33.10 0.00 0.00 0.00
May 25.15 1.08 24.07 23.65 29.67 0.00 0.00 0.00
June 26.51 2.33 24.19 28.81 23.67 0.00 0.00 0.00
July 25.43 1.87 23.56 29.74 22.47 0.00 0.00 0.00
August 21.58 0.39 21.19 25.10 23.57 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.51 0.48 18.02 17.92 33.72 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.51 2.33 24.19 29.74 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.72 44.25 0.00 0.00 0.00
February 14.89 0.00 14.89 10.15 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.32 0.07 21.25 20.08 33.16 0.00 0.00 0.00
May 25.06 1.04 24.02 23.46 29.69 0.00 0.00 0.00
June 26.45 2.30 24.15 28.67 23.67 0.00 0.00 0.00
July 25.34 1.83 23.52 29.52 22.47 0.00 0.00 0.00
August 21.51 0.36 21.15 24.97 23.60 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.48 0.47 18.01 17.87 33.72 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.45 2.30 24.15 29.52 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.72 44.25 0.00 0.00 0.00
February 14.89 0.00 14.89 10.15 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.32 0.07 21.25 20.08 33.17 0.00 0.00 0.00
May 25.06 1.04 24.02 23.46 29.69 0.00 0.00 0.00
June 26.45 2.30 24.15 28.67 23.67 0.00 0.00 0.00
July 25.34 1.83 23.52 29.52 22.47 0.00 0.00 0.00
August 21.51 0.36 21.15 24.97 23.60 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.48 0.47 18.01 17.87 33.73 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.45 2.30 24.15 29.52 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.72 44.25 0.00 0.00 0.00
February 14.89 0.00 14.89 10.15 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.32 0.07 21.25 20.08 33.17 0.00 0.00 0.00
May 25.06 1.04 24.02 23.46 29.69 0.00 0.00 0.00
June 26.45 2.30 24.15 28.67 23.67 0.00 0.00 0.00
July 25.34 1.83 23.52 29.52 22.47 0.00 0.00 0.00
August 21.51 0.36 21.15 24.97 23.60 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.48 0.47 18.01 17.87 33.73 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.45 2.30 24.15 29.52 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.72 44.25 0.00 0.00 0.00
February 14.89 0.00 14.89 10.15 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.33 0.07 21.26 20.09 33.16 0.00 0.00 0.00
May 25.06 1.04 24.02 23.46 29.69 0.00 0.00 0.00
June 26.45 2.30 24.15 28.67 23.67 0.00 0.00 0.00
July 25.34 1.83 23.52 29.52 22.47 0.00 0.00 0.00
August 21.51 0.36 21.15 24.97 23.60 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.48 0.47 18.01 17.87 33.72 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.45 2.30 24.15 29.52 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.99 0.00 11.99 8.73 44.25 0.00 0.00 0.00
February 14.90 0.00 14.90 10.16 39.67 0.00 0.00 0.00
March 18.23 0.00 18.23 14.54 40.87 0.00 0.00 0.00
April 21.38 0.08 21.30 20.13 33.10 0.00 0.00 0.00
May 25.18 1.09 24.09 23.73 29.68 0.00 0.00 0.00
June 26.54 2.35 24.20 28.88 23.67 0.00 0.00 0.00
July 25.46 1.88 23.58 29.81 22.47 0.00 0.00 0.00
August 21.61 0.40 21.21 25.19 23.60 0.00 0.00 0.00
September 18.20 0.00 18.20 19.80 27.71 0.00 0.00 0.00
October 14.36 0.00 14.36 17.06 31.52 0.00 0.00 0.00
November 12.99 0.00 12.99 9.15 42.60 0.00 0.00 0.00
December 11.20 0.00 11.20 7.72 45.81 0.00 0.00 0.00
                 
Annual Sum or Average 18.52 0.49 18.03 17.95 33.72 0.00 0.00 0.00
Minimum of Months 11.20 0.00 11.20 7.72 22.47 0.00 0.00 0.00
Maximum of Months 26.54 2.35 24.20 29.81 45.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.75 15.60 15.15 39.55 45.94 0.00 0.00 0.00
February 36.47 17.00 19.46 44.67 41.06 0.00 0.00 0.00
March 41.29 18.36 22.94 51.15 42.01 0.00 0.00 0.00
April 56.67 29.13 27.54 78.19 35.72 0.00 0.00 0.00
May 55.24 25.20 30.04 73.30 33.02 0.00 0.00 0.00
June 58.58 28.96 29.61 81.76 26.72 0.00 0.00 0.00
July 62.08 32.69 29.39 90.36 25.72 0.00 0.00 0.00
August 58.50 31.23 27.27 86.82 26.69 0.00 0.00 0.00
September 50.35 26.77 23.57 72.58 29.83 0.00 0.00 0.00
October 38.85 21.22 17.63 57.61 33.47 0.00 0.00 0.00
November 35.36 18.62 16.74 45.62 43.97 0.00 0.00 0.00
December 31.47 16.98 14.49 40.99 47.37 0.00 0.00 0.00
                 
Annual Sum or Average 46.34 23.51 22.83 63.64 35.94 0.00 0.00 0.00
Minimum of Months 30.75 15.60 14.49 39.55 25.72 0.00 0.00 0.00
Maximum of Months 62.08 32.69 30.04 90.36 47.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.72 15.58 15.14 39.48 45.94 0.00 0.00 0.00
February 36.46 17.00 19.46 44.67 41.06 0.00 0.00 0.00
March 41.29 18.36 22.94 51.15 42.01 0.00 0.00 0.00
April 56.67 29.13 27.54 78.19 35.72 0.00 0.00 0.00
May 55.23 25.20 30.03 73.30 33.02 0.00 0.00 0.00
June 58.58 28.96 29.61 81.76 26.72 0.00 0.00 0.00
July 62.08 32.69 29.39 90.36 25.72 0.00 0.00 0.00
August 58.50 31.23 27.27 86.82 26.69 0.00 0.00 0.00
September 50.35 26.77 23.57 72.58 29.83 0.00 0.00 0.00
October 38.85 21.22 17.62 57.60 33.47 0.00 0.00 0.00
November 35.34 18.61 16.73 45.57 43.97 0.00 0.00 0.00
December 31.43 16.95 14.48 40.89 47.37 0.00 0.00 0.00
                 
Annual Sum or Average 46.33 23.50 22.83 63.62 35.94 0.00 0.00 0.00
Minimum of Months 30.72 15.58 14.48 39.48 25.72 0.00 0.00 0.00
Maximum of Months 62.08 32.69 30.03 90.36 47.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.72 15.58 15.14 39.48 45.94 0.00 0.00 0.00
February 36.46 17.00 19.46 44.67 41.06 0.00 0.00 0.00
March 41.29 18.36 22.94 51.15 42.01 0.00 0.00 0.00
April 56.67 29.13 27.54 78.19 35.72 0.00 0.00 0.00
May 55.23 25.20 30.03 73.30 33.02 0.00 0.00 0.00
June 58.58 28.96 29.61 81.76 26.72 0.00 0.00 0.00
July 62.08 32.69 29.39 90.36 25.72 0.00 0.00 0.00
August 58.50 31.23 27.27 86.82 26.69 0.00 0.00 0.00
September 50.35 26.77 23.57 72.58 29.83 0.00 0.00 0.00
October 38.85 21.22 17.62 57.60 33.47 0.00 0.00 0.00
November 35.34 18.61 16.73 45.57 43.97 0.00 0.00 0.00
December 31.43 16.95 14.48 40.89 47.37 0.00 0.00 0.00
                 
Annual Sum or Average 46.33 23.50 22.83 63.62 35.94 0.00 0.00 0.00
Minimum of Months 30.72 15.58 14.48 39.48 25.72 0.00 0.00 0.00
Maximum of Months 62.08 32.69 30.03 90.36 47.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.72 15.58 15.14 39.48 45.94 0.00 0.00 0.00
February 36.46 17.00 19.46 44.67 41.06 0.00 0.00 0.00
March 41.29 18.36 22.94 51.15 42.01 0.00 0.00 0.00
April 56.67 29.13 27.54 78.19 35.72 0.00 0.00 0.00
May 55.24 25.20 30.04 73.30 33.02 0.00 0.00 0.00
June 58.58 28.96 29.61 81.76 26.72 0.00 0.00 0.00
July 62.08 32.69 29.39 90.36 25.72 0.00 0.00 0.00
August 58.50 31.23 27.27 86.82 26.69 0.00 0.00 0.00
September 50.35 26.77 23.57 72.58 29.83 0.00 0.00 0.00
October 38.85 21.22 17.63 57.60 33.47 0.00 0.00 0.00
November 35.35 18.61 16.73 45.57 43.97 0.00 0.00 0.00
December 31.43 16.95 14.48 40.89 47.37 0.00 0.00 0.00
                 
Annual Sum or Average 46.33 23.50 22.83 63.62 35.94 0.00 0.00 0.00
Minimum of Months 30.72 15.58 14.48 39.48 25.72 0.00 0.00 0.00
Maximum of Months 62.08 32.69 30.04 90.36 47.37 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220075E+09 0.162503E+09 57572100.37 0.325676E+09 0.127242E+09
February 0.155237E+09 96864755.11 58372210.30 0.218329E+09 0.100987E+09
March 0.123670E+09 57624463.61 66045624.80 0.168120E+09 0.113769E+09
April 77609317.43 18127535.00 59481782.43 97950800.01 90730775.82
May 61911186.80 919.79 61910267.01 58666438.79 85183974.99
June 59374623.81 0.34 59374623.46 63050446.67 65643265.82
July 60500544.08 190196.36 60310347.72 69864069.30 63843568.51
August 65088118.91 7848308.08 57239810.82 84694526.11 67218861.80
September 0.107164E+09 48585637.65 58578142.24 0.163139E+09 77390955.61
October 0.168535E+09 0.113048E+09 55486873.04 0.267808E+09 91722294.71
November 0.203641E+09 0.144878E+09 58762404.61 0.298838E+09 0.116497E+09
December 0.235405E+09 0.180133E+09 55271611.95 0.348987E+09 0.130415E+09
           
Annual Sum or Average 0.153821E+10 0.829804E+09 0.708406E+09 0.216512E+10 0.113064E+10
Minimum of Months 59374623.81 0.34 55271611.95 58666438.79 63843568.51
Maximum of Months 0.235405E+09 0.180133E+09 66045624.80 0.348987E+09 0.130415E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220073E+09 0.162503E+09 57570494.87 0.325674E+09 0.127240E+09
February 0.155235E+09 96864755.11 58369977.25 0.218327E+09 0.100986E+09
March 0.123634E+09 57608333.39 66025572.21 0.168068E+09 0.113795E+09
April 77229854.63 17957549.04 59272305.59 97048765.99 90754407.06
May 61902604.27 0.00 61902604.27 58651642.66 85183076.71
June 59371818.96 0.00 59371818.96 63047624.78 65642515.74
July 60496121.22 188538.86 60307582.36 69855402.22 63842442.25
August 64993209.89 7806148.04 57187061.85 84459708.88 67221175.39
September 0.106834E+09 48455740.19 58378667.60 0.162558E+09 77580868.78
October 0.168533E+09 0.113048E+09 55484935.81 0.267807E+09 91720417.77
November 0.203639E+09 0.144878E+09 58760668.69 0.298836E+09 0.116495E+09
December 0.235403E+09 0.180133E+09 55270221.57 0.348987E+09 0.130413E+09
           
Annual Sum or Average 0.153735E+10 0.829443E+09 0.707902E+09 0.216332E+10 0.113087E+10
Minimum of Months 59371818.96 0.00 55270221.57 58651642.66 63842442.25
Maximum of Months 0.235403E+09 0.180133E+09 66025572.21 0.348987E+09 0.130413E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220073E+09 0.162503E+09 57570494.87 0.325674E+09 0.127240E+09
February 0.155235E+09 96864755.11 58369977.25 0.218327E+09 0.100986E+09
March 0.123634E+09 57608333.39 66025572.21 0.168068E+09 0.113795E+09
April 77229854.63 17957549.04 59272305.59 97048765.99 90754407.06
May 61902604.27 0.00 61902604.27 58651642.66 85183076.71
June 59371818.96 0.00 59371818.96 63047624.78 65642515.74
July 60496121.22 188538.86 60307582.36 69855402.22 63842442.25
August 64992608.30 7805561.33 57187046.97 84459255.21 67223038.69
September 0.106804E+09 48451360.57 58352705.64 0.162557E+09 77643561.65
October 0.168533E+09 0.113048E+09 55484935.81 0.267807E+09 91720417.77
November 0.203639E+09 0.144878E+09 58760668.69 0.298836E+09 0.116495E+09
December 0.235403E+09 0.180133E+09 55270221.57 0.348987E+09 0.130413E+09
           
Annual Sum or Average 0.153731E+10 0.829438E+09 0.707876E+09 0.216332E+10 0.113094E+10
Minimum of Months 59371818.96 0.00 55270221.57 58651642.66 63842442.25
Maximum of Months 0.235403E+09 0.180133E+09 66025572.21 0.348987E+09 0.130413E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220073E+09 0.162503E+09 57570494.87 0.325674E+09 0.127240E+09
February 0.155235E+09 96864755.11 58369977.25 0.218327E+09 0.100986E+09
March 0.123634E+09 57608333.39 66025572.21 0.168068E+09 0.113795E+09
April 77229854.63 17957549.04 59272305.59 97048765.99 90754407.06
May 61902604.27 0.00 61902604.27 58651642.66 85183076.71
June 59371818.96 0.00 59371818.96 63047624.78 65642515.74
July 60496121.22 188538.86 60307582.36 69855402.22 63842442.25
August 64992607.87 7805560.90 57187046.97 84459255.21 67223041.04
September 0.106803E+09 48451329.90 58351723.71 0.162557E+09 77645454.37
October 0.168533E+09 0.113048E+09 55484935.81 0.267807E+09 91720417.77
November 0.203639E+09 0.144878E+09 58760668.69 0.298836E+09 0.116495E+09
December 0.235403E+09 0.180133E+09 55270221.57 0.348987E+09 0.130413E+09
           
Annual Sum or Average 0.153731E+10 0.829438E+09 0.707875E+09 0.216332E+10 0.113094E+10
Minimum of Months 59371818.96 0.00 55270221.57 58651642.66 63842442.25
Maximum of Months 0.235403E+09 0.180133E+09 66025572.21 0.348987E+09 0.130413E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220073E+09 0.162503E+09 57570494.87 0.325674E+09 0.127240E+09
February 0.155235E+09 96864755.11 58369977.25 0.218327E+09 0.100986E+09
March 0.123634E+09 57608333.39 66025572.21 0.168068E+09 0.113795E+09
April 77229854.63 17957549.04 59272305.59 97048765.99 90754407.06
May 61902604.27 0.00 61902604.27 58651642.66 85183076.71
June 59371818.96 0.00 59371818.96 63047624.78 65642515.74
July 60496121.22 188538.86 60307582.36 69855402.22 63842442.25
August 64993107.79 7806060.82 57187046.97 84459250.64 67221057.39
September 0.106813E+09 48453336.26 58359973.32 0.162557E+09 77622399.00
October 0.168533E+09 0.113048E+09 55484935.81 0.267807E+09 91720417.77
November 0.203639E+09 0.144878E+09 58760668.69 0.298836E+09 0.116495E+09
December 0.235403E+09 0.180133E+09 55270221.57 0.348987E+09 0.130413E+09
           
Annual Sum or Average 0.153732E+10 0.829441E+09 0.707883E+09 0.216332E+10 0.113091E+10
Minimum of Months 59371818.96 0.00 55270221.57 58651642.66 63842442.25
Maximum of Months 0.235403E+09 0.180133E+09 66025572.21 0.348987E+09 0.130413E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.220075E+09 0.162503E+09 57572100.29 0.325676E+09 0.127242E+09
February 0.155237E+09 96864755.11 58372210.19 0.218329E+09 0.100987E+09
March 0.123666E+09 57624492.97 66041455.92 0.168097E+09 0.113753E+09
April 77546162.21 18093211.77 59452950.44 97716097.83 90655315.29
May 61910419.14 683.00 61909736.14 58664705.39 85183831.19
June 59374623.40 0.39 59374623.01 63050446.15 65643265.78
July 60500201.16 190016.77 60310184.40 69862915.22 63843568.45
August 65075325.67 7840343.73 57234981.94 84651573.86 67212652.62
September 0.106954E+09 48512986.45 58440618.59 0.162741E+09 77472454.24
October 0.168535E+09 0.113048E+09 55486872.94 0.267808E+09 91722294.62
November 0.203641E+09 0.144878E+09 58762404.52 0.298838E+09 0.116497E+09
December 0.235405E+09 0.180133E+09 55271611.88 0.348987E+09 0.130415E+09
           
Annual Sum or Average 0.153792E+10 0.829689E+09 0.708230E+09 0.216442E+10 0.113063E+10
Minimum of Months 59374623.40 0.39 55271611.88 58664705.39 63843568.45
Maximum of Months 0.235405E+09 0.180133E+09 66041455.92 0.348987E+09 0.130415E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.309335E+09 0.227668E+09 81666690.54 0.456538E+09 0.178239E+09
February 0.218890E+09 0.135709E+09 83181434.26 0.307416E+09 0.141114E+09
March 0.192478E+09 93938328.56 98539927.02 0.269937E+09 0.158448E+09
April 0.133010E+09 43096871.09 89912768.48 0.186599E+09 0.126817E+09
May 93359442.54 2829228.98 90530213.55 95024527.23 0.118867E+09
June 84944207.76 0.00 84944207.76 90213242.63 91708444.55
July 87088047.06 1063682.74 86024364.33 0.100998E+09 89490071.39
August 0.111019E+09 25195440.25 85823620.60 0.160759E+09 94255499.89
September 0.174108E+09 86165169.57 87942388.61 0.274160E+09 0.108551E+09
October 0.243195E+09 0.163415E+09 79779936.67 0.386051E+09 0.128701E+09
November 0.286392E+09 0.202976E+09 83416155.65 0.419255E+09 0.163167E+09
December 0.330677E+09 0.252369E+09 78308694.11 0.488854E+09 0.182799E+09
           
Annual Sum or Average 0.226450E+10 0.123443E+10 0.103007E+10 0.323580E+10 0.158216E+10
Minimum of Months 84944207.76 0.00 78308694.11 90213242.63 89490071.39
Maximum of Months 0.330677E+09 0.252369E+09 98539927.02 0.488854E+09 0.182799E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86619361.97 46640417.30 39978944.68 0.106481E+09 0.116955E+09
February 81425982.11 37596490.28 43829491.83 94066194.83 94020124.73
March 0.109041E+09 48891003.96 60150029.01 0.131344E+09 0.106955E+09
April 0.133408E+09 65827736.44 67580422.30 0.179382E+09 86152361.57
May 0.128843E+09 52921604.79 75921832.67 0.165296E+09 82660842.58
June 0.123187E+09 51829837.59 71357454.87 0.167846E+09 64817765.45
July 0.144811E+09 70146223.37 74664298.01 0.209677E+09 64616081.14
August 0.144341E+09 75129925.41 69211572.83 0.212740E+09 65905235.41
September 0.101650E+09 45662210.37 55987779.59 0.141697E+09 71841499.14
October 94766343.22 48694594.61 46071748.61 0.135906E+09 84099013.19
November 84320716.82 43107047.37 41213669.45 0.101380E+09 0.108222E+09
December 83696156.32 46783531.34 36912624.98 0.102284E+09 0.119910E+09
           
Annual Sum or Average 0.131611E+10 0.633231E+09 0.682880E+09 0.174810E+10 0.106615E+10
Minimum of Months 81425982.11 37596490.28 36912624.98 94066194.83 64616081.14
Maximum of Months 0.144811E+09 75129925.41 75921832.67 0.212740E+09 0.119910E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86617756.55 46640417.30 39977339.26 0.106480E+09 0.116952E+09
February 81423749.17 37596490.28 43827258.90 94063919.09 94018879.59
March 0.109038E+09 48891003.96 60146929.42 0.131340E+09 0.106954E+09
April 0.133406E+09 65827736.44 67578145.94 0.179380E+09 86151117.98
May 0.128840E+09 52921604.79 75918588.26 0.165292E+09 82659832.20
June 0.123184E+09 51829837.59 71354650.82 0.167843E+09 64816922.85
July 0.144809E+09 70146223.37 74662288.12 0.209676E+09 64614869.42
August 0.144340E+09 75129925.41 69209765.61 0.212739E+09 65903877.11
September 0.101648E+09 45662210.37 55985703.83 0.141695E+09 71840090.91
October 94764406.08 48694594.61 46069811.48 0.135904E+09 84097109.28
November 84318981.00 43107047.37 41211933.63 0.101378E+09 0.108220E+09
December 83694766.01 46783531.34 36911234.67 0.102284E+09 0.119908E+09
           
Annual Sum or Average 0.131608E+10 0.633231E+09 0.682854E+09 0.174807E+10 0.106614E+10
Minimum of Months 81423749.17 37596490.28 36911234.67 94063919.09 64614869.42
Maximum of Months 0.144809E+09 75129925.41 75918588.26 0.212739E+09 0.119908E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86617756.55 46640417.30 39977339.26 0.106480E+09 0.116952E+09
February 81423749.17 37596490.28 43827258.90 94063919.09 94018879.59
March 0.109038E+09 48891003.96 60146929.42 0.131340E+09 0.106954E+09
April 0.133406E+09 65827736.44 67578145.94 0.179380E+09 86151117.98
May 0.128840E+09 52921604.79 75918588.26 0.165292E+09 82659832.20
June 0.123184E+09 51829837.59 71354650.82 0.167843E+09 64816922.85
July 0.144809E+09 70146223.37 74662288.12 0.209676E+09 64614869.42
August 0.144340E+09 75129925.41 69209765.61 0.212739E+09 65903877.11
September 0.101648E+09 45662210.37 55985703.83 0.141695E+09 71840090.91
October 94764406.08 48694594.61 46069811.48 0.135904E+09 84097109.28
November 84318981.00 43107047.37 41211933.63 0.101378E+09 0.108220E+09
December 83694766.01 46783531.34 36911234.67 0.102284E+09 0.119908E+09
           
Annual Sum or Average 0.131608E+10 0.633231E+09 0.682854E+09 0.174807E+10 0.106614E+10
Minimum of Months 81423749.17 37596490.28 36911234.67 94063919.09 64614869.42
Maximum of Months 0.144809E+09 75129925.41 75918588.26 0.212739E+09 0.119908E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86696153.05 46685714.77 40010438.28 0.106683E+09 0.116955E+09
February 81431319.55 37599174.36 43832145.18 94079113.54 94020124.79
March 0.109041E+09 48891166.18 60150107.75 0.131344E+09 0.106955E+09
April 0.133408E+09 65827736.44 67580422.41 0.179382E+09 86152361.64
May 0.128843E+09 52921604.79 75921832.83 0.165296E+09 82660842.63
June 0.123187E+09 51829837.59 71357455.01 0.167846E+09 64817765.50
July 0.144811E+09 70146223.37 74664298.12 0.209677E+09 64616081.21
August 0.144341E+09 75129925.41 69211572.92 0.212740E+09 65905235.48
September 0.101650E+09 45662210.37 55987779.70 0.141697E+09 71841499.21
October 94771951.93 48699016.29 46072935.64 0.135922E+09 84099013.29
November 84366750.92 43134379.85 41232371.07 0.101498E+09 0.108222E+09
December 83808631.21 46850664.91 36957966.30 0.102579E+09 0.119910E+09
           
Annual Sum or Average 0.131636E+10 0.633378E+09 0.682979E+09 0.174874E+10 0.106615E+10
Minimum of Months 81431319.55 37599174.36 36957966.30 94079113.54 64616081.21
Maximum of Months 0.144811E+09 75129925.41 75921832.83 0.212740E+09 0.119910E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32113160.54 0.00 32113160.54 23369309.08 0.118528E+09
February 36035391.32 0.00 36035391.32 24567681.02 95977145.32
March 48826254.26 0.00 48826254.26 38936517.04 0.109463E+09
April 55344381.02 202830.50 55141550.53 52063079.23 85791535.80
May 67358705.95 2880379.61 64478326.34 63331219.23 79466305.17
June 68722259.59 6034391.21 62687868.38 74679155.39 61358524.58
July 68120271.15 5006478.27 63113792.88 79650031.90 60180280.06
August 57794910.16 1040739.14 56754171.01 67236816.15 63128854.66
September 47173853.72 6940.86 47166912.87 51317590.60 71833401.97
October 38459007.85 0.00 38459007.85 45686033.98 84417843.19
November 33663716.72 0.00 33663716.72 23719773.39 0.110416E+09
December 29989077.67 0.00 29989077.67 20669369.21 0.122690E+09
           
Annual Sum or Average 0.583601E+09 15171759.58 0.568429E+09 0.565227E+09 0.106325E+10
Minimum of Months 29989077.67 0.00 29989077.67 20669369.21 60180280.06
Maximum of Months 68722259.59 6034391.21 64478326.34 79650031.90 0.122690E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32111555.04 0.00 32111555.04 23368163.14 0.118526E+09
February 36033158.27 0.00 36033158.27 24565494.60 95975882.12
March 48823154.51 0.00 48823154.51 38932970.22 0.109462E+09
April 55274383.86 186806.96 55087576.90 52057590.88 85941632.50
May 67129244.62 2789334.55 64339910.07 62837094.98 79515174.22
June 68563074.18 5961093.41 62601980.76 74303491.96 61359458.48
July 67877626.62 4893094.09 62984532.53 79072135.83 60187060.71
August 57618951.60 973954.38 56644997.22 66892962.53 63211146.82
September 47170864.90 6918.57 47163946.34 51315753.72 71833840.76
October 38457070.62 0.00 38457070.62 45684402.78 84415845.84
November 33661980.80 0.00 33661980.80 23718427.31 0.110414E+09
December 29987687.29 0.00 29987687.29 20668776.81 0.122688E+09
           
Annual Sum or Average 0.582709E+09 14811201.95 0.567898E+09 0.563417E+09 0.106353E+10
Minimum of Months 29987687.29 0.00 29987687.29 20668776.81 60187060.71
Maximum of Months 68563074.18 5961093.41 64339910.07 79072135.83 0.122688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32111555.04 0.00 32111555.04 23368163.14 0.118526E+09
February 36033158.27 0.00 36033158.27 24565494.60 95975882.12
March 48823154.51 0.00 48823154.51 38932970.22 0.109462E+09
April 55263620.35 184265.21 55079355.13 52057471.41 85966624.41
May 67129244.62 2789334.55 64339910.07 62837094.98 79515174.22
June 68563074.18 5961093.41 62601980.76 74303491.96 61359458.48
July 67877626.62 4893094.09 62984532.53 79072135.83 60187060.71
August 57616371.56 973912.47 56642459.09 66892962.54 63215917.93
September 47169071.17 6957.42 47162113.75 51315753.72 71837089.47
October 38457070.62 0.00 38457070.62 45684402.78 84415845.84
November 33661980.80 0.00 33661980.80 23718427.31 0.110414E+09
December 29987687.29 0.00 29987687.29 20668776.81 0.122688E+09
           
Annual Sum or Average 0.582694E+09 14808657.15 0.567885E+09 0.563417E+09 0.106356E+10
Minimum of Months 29987687.29 0.00 29987687.29 20668776.81 60187060.71
Maximum of Months 68563074.18 5961093.41 64339910.07 79072135.83 0.122688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32111555.04 0.00 32111555.04 23368163.14 0.118526E+09
February 36033158.27 0.00 36033158.27 24565494.60 95975882.12
March 48823154.51 0.00 48823154.51 38932970.22 0.109462E+09
April 55263620.35 184265.21 55079355.13 52057471.41 85966624.41
May 67129244.62 2789334.55 64339910.07 62837094.98 79515174.22
June 68563074.18 5961093.41 62601980.76 74303491.96 61359458.48
July 67877626.62 4893094.09 62984532.53 79072135.83 60187060.71
August 57614753.77 973884.33 56640869.44 66892962.53 63218916.77
September 47169156.36 7087.70 47162068.66 51315753.72 71836629.11
October 38457070.62 0.00 38457070.62 45684402.78 84415845.84
November 33661980.80 0.00 33661980.80 23718427.31 0.110414E+09
December 29987687.29 0.00 29987687.29 20668776.81 0.122688E+09
           
Annual Sum or Average 0.582692E+09 14808759.29 0.567883E+09 0.563417E+09 0.106356E+10
Minimum of Months 29987687.29 0.00 29987687.29 20668776.81 60187060.71
Maximum of Months 68563074.18 5961093.41 64339910.07 79072135.83 0.122688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32111555.04 0.00 32111555.04 23368163.14 0.118526E+09
February 36033158.27 0.00 36033158.27 24565494.60 95975882.12
March 48823154.51 0.00 48823154.51 38932970.22 0.109462E+09
April 55281954.70 186739.43 55095215.27 52067932.71 85939217.74
May 67129244.62 2789334.55 64339910.07 62837094.98 79515174.22
June 68563074.18 5961093.41 62601980.76 74303491.96 61359458.48
July 67877626.62 4893094.09 62984532.53 79072135.83 60187060.71
August 57614245.59 973859.82 56640385.77 66892962.53 63219907.16
September 47170222.83 7243.23 47162979.60 51315753.72 71834320.38
October 38457070.62 0.00 38457070.62 45684402.78 84415845.84
November 33661980.80 0.00 33661980.80 23718427.31 0.110414E+09
December 29987687.29 0.00 29987687.29 20668776.81 0.122688E+09
           
Annual Sum or Average 0.582711E+09 14811364.53 0.567900E+09 0.563428E+09 0.106354E+10
Minimum of Months 29987687.29 0.00 29987687.29 20668776.81 60187060.71
Maximum of Months 68563074.18 5961093.41 64339910.07 79072135.83 0.122688E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 32113160.46 0.00 32113160.46 23369309.02 0.118528E+09
February 36035391.21 0.00 36035391.21 24567680.91 95977145.26
March 48826254.10 0.00 48826254.10 38936516.86 0.109463E+09
April 55414393.05 201434.60 55212958.45 52188916.38 85799151.95
May 67442785.42 2910347.56 64532437.86 63546711.43 79504031.96
June 68799061.38 6078978.23 62720083.15 74862673.54 61360231.30
July 68197483.60 5042805.02 63154678.58 79841266.06 60188168.73
August 57871154.08 1062355.35 56808798.73 67470243.27 63198748.42
September 47173088.95 7275.01 47165813.94 51317590.50 71834145.04
October 38459007.75 0.00 38459007.75 45686033.90 84417843.09
November 33663716.63 0.00 33663716.63 23719773.32 0.110416E+09
December 29989077.60 0.00 29989077.60 20669369.18 0.122690E+09
           
Annual Sum or Average 0.583985E+09 15303195.77 0.568681E+09 0.566176E+09 0.106338E+10
Minimum of Months 29989077.60 0.00 29989077.60 20669369.18 60188168.73
Maximum of Months 68799061.38 6078978.23 64532437.86 79841266.06 0.122690E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 82368659.61 41782948.37 40585711.24 0.105931E+09 0.123036E+09
February 88219768.05 41134747.03 47085021.02 0.108071E+09 99335839.54
March 0.110604E+09 49166644.16 61437080.60 0.137012E+09 0.112508E+09
April 0.146894E+09 75505541.56 71388759.70 0.202680E+09 92596454.81
May 0.147942E+09 67493442.87 80448671.90 0.196318E+09 88443279.92
June 0.151838E+09 75076888.46 76761160.08 0.211924E+09 69252167.29
July 0.166267E+09 87555563.00 78711214.08 0.242019E+09 68880342.46
August 0.156697E+09 83650214.57 73046800.24 0.232548E+09 71474719.22
September 0.130503E+09 69399275.16 61103730.93 0.188117E+09 77307841.51
October 0.104051E+09 56841784.98 47209139.84 0.154292E+09 89638394.22
November 91662874.71 48275023.25 43387851.46 0.118240E+09 0.113976E+09
December 84287010.71 45468513.92 38818496.79 0.109798E+09 0.126872E+09
           
Annual Sum or Average 0.146133E+10 0.741351E+09 0.719984E+09 0.200695E+10 0.113332E+10
Minimum of Months 82368659.61 41134747.03 38818496.79 0.105931E+09 68880342.46
Maximum of Months 0.166267E+09 87555563.00 80448671.90 0.242019E+09 0.126872E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 82291789.64 41738635.21 40553154.44 0.105739E+09 0.123034E+09
February 88213339.39 41132666.57 47080672.82 0.108059E+09 99334520.56
March 0.110600E+09 49166506.16 61433898.85 0.137008E+09 0.112507E+09
April 0.146892E+09 75505541.56 71386483.34 0.202678E+09 92595262.84
May 0.147939E+09 67493442.87 80445427.50 0.196314E+09 88442299.67
June 0.151835E+09 75076888.46 76758356.04 0.211921E+09 69251415.44
July 0.166265E+09 87555563.00 78709204.18 0.242017E+09 68879396.45
August 0.156695E+09 83650214.57 73044993.03 0.232547E+09 71473520.17
September 0.130501E+09 69399275.16 61101655.17 0.188115E+09 77306582.70
October 0.104044E+09 56837928.94 47206056.27 0.154277E+09 89636455.33
November 91612578.36 48248500.45 43364077.91 0.118119E+09 0.113974E+09
December 84173225.77 45400647.86 38772577.91 0.109508E+09 0.126869E+09
           
Annual Sum or Average 0.146106E+10 0.741206E+09 0.719857E+09 0.200630E+10 0.113330E+10
Minimum of Months 82291789.64 41132666.57 38772577.91 0.105739E+09 68879396.45
Maximum of Months 0.166265E+09 87555563.00 80445427.50 0.242017E+09 0.126869E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 82291789.64 41738635.21 40553154.44 0.105739E+09 0.123034E+09
February 88213339.39 41132666.57 47080672.82 0.108059E+09 99334520.56
March 0.110600E+09 49166506.16 61433898.85 0.137008E+09 0.112507E+09
April 0.146892E+09 75505541.56 71386483.34 0.202678E+09 92595262.84
May 0.147939E+09 67493442.87 80445427.50 0.196314E+09 88442299.67
June 0.151835E+09 75076888.46 76758356.04 0.211921E+09 69251415.44
July 0.166265E+09 87555563.00 78709204.18 0.242017E+09 68879396.45
August 0.156695E+09 83650214.57 73044993.03 0.232547E+09 71473520.17
September 0.130501E+09 69399275.16 61101655.17 0.188115E+09 77306582.70
October 0.104044E+09 56837928.94 47206056.27 0.154277E+09 89636455.33
November 91612578.36 48248500.45 43364077.91 0.118119E+09 0.113974E+09
December 84173225.77 45400647.86 38772577.91 0.109508E+09 0.126869E+09
           
Annual Sum or Average 0.146106E+10 0.741206E+09 0.719857E+09 0.200630E+10 0.113330E+10
Minimum of Months 82291789.64 41132666.57 38772577.91 0.105739E+09 68879396.45
Maximum of Months 0.166265E+09 87555563.00 80445427.50 0.242017E+09 0.126869E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 82293395.15 41738635.21 40554759.94 0.105740E+09 0.123036E+09
February 88215572.44 41132666.57 47082905.87 0.108061E+09 99335857.94
March 0.110604E+09 49166506.16 61436998.60 0.137012E+09 0.112508E+09
April 0.146894E+09 75505541.56 71388759.82 0.202680E+09 92596454.87
May 0.147942E+09 67493442.87 80448672.07 0.196318E+09 88443279.97
June 0.151838E+09 75076888.46 76761160.22 0.211924E+09 69252167.32
July 0.166267E+09 87555563.00 78711214.18 0.242019E+09 68880342.50
August 0.156697E+09 83650214.57 73046800.33 0.232548E+09 71474719.28
September 0.130503E+09 69399275.16 61103731.04 0.188117E+09 77307841.57
October 0.104046E+09 56837928.94 47207993.50 0.154278E+09 89638394.32
November 91614314.27 48248500.45 43365813.82 0.118120E+09 0.113976E+09
December 84174616.16 45400647.86 38773968.30 0.109509E+09 0.126872E+09
           
Annual Sum or Average 0.146109E+10 0.741206E+09 0.719883E+09 0.200633E+10 0.113332E+10
Minimum of Months 82293395.15 41132666.57 38773968.30 0.105740E+09 68880342.50
Maximum of Months 0.166267E+09 87555563.00 80448672.07 0.242019E+09 0.126872E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 900.01 351.58 608.49 449.03 159.46 0.00 0.00
February 668.56 308.79 475.49 296.34 179.15 0.00 0.00
March 477.29 314.03 348.85 164.14 184.71 0.00 0.00
April 297.23 258.94 230.36 58.31 172.04 0.00 0.00
May 166.87 235.20 173.53 1.06 172.48 0.00 0.00
June 180.75 187.33 170.21 0.00 170.21 0.00 0.00
July 194.20 176.43 168.04 0.82 167.22 0.00 0.00
August 249.38 185.77 187.11 26.92 160.19 0.00 0.00
September 482.32 221.38 314.61 145.48 169.14 0.00 0.00
October 744.06 253.52 468.34 314.26 154.08 0.00 0.00
November 853.50 332.61 581.88 413.67 168.20 0.00 0.00
December 964.30 360.39 650.80 497.75 153.05 0.00 0.00
               
Annual Sum or Average 514.28 265.31 364.34 196.97 167.37 0.00 0.00
Minimum of Months 166.87 176.43 168.04 0.00 153.05 0.00 0.00
Maximum of Months 964.30 360.39 650.80 497.75 184.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 159.10 174.66 129.39 69.67 59.72 0.00 0.00
February 155.54 155.46 134.63 62.16 72.47 0.00 0.00
March 196.15 159.73 162.84 73.02 89.83 0.00 0.00
April 276.82 132.95 205.88 101.59 104.29 0.00 0.00
May 246.85 123.45 192.42 79.03 113.38 0.00 0.00
June 259.02 100.03 190.10 79.98 110.12 0.00 0.00
July 313.14 96.50 216.26 104.76 111.50 0.00 0.00
August 317.71 98.42 215.56 112.20 103.36 0.00 0.00
September 218.67 110.87 156.87 70.47 86.40 0.00 0.00
October 202.97 125.59 141.53 72.72 68.80 0.00 0.00
November 156.49 167.01 130.14 66.53 63.61 0.00 0.00
December 152.86 179.08 125.04 69.89 55.14 0.00 0.00
               
Annual Sum or Average 221.75 135.23 166.94 80.32 86.62 0.00 0.00
Minimum of Months 152.86 96.50 125.04 62.16 55.14 0.00 0.00
Maximum of Months 317.71 179.08 216.26 112.20 113.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 52.35 265.52 71.94 0.00 71.94 0.00 0.00
February 60.93 238.04 89.37 0.00 89.37 0.00 0.00
March 87.22 245.21 109.37 0.00 109.37 0.00 0.00
April 120.55 198.83 128.03 0.44 127.58 0.00 0.00
May 141.20 178.09 150.58 6.33 144.25 0.00 0.00
June 172.36 142.04 158.86 13.87 144.99 0.00 0.00
July 177.64 134.83 152.27 11.06 141.21 0.00 0.00
August 150.17 141.56 129.23 2.24 126.99 0.00 0.00
September 118.79 166.28 109.19 0.02 109.18 0.00 0.00
October 102.34 189.11 86.15 0.00 86.15 0.00 0.00
November 54.90 255.59 77.92 0.00 77.92 0.00 0.00
December 46.30 274.84 67.18 0.00 67.18 0.00 0.00
               
Annual Sum or Average 107.34 202.33 110.93 2.84 108.09 0.00 0.00
Minimum of Months 46.30 134.83 67.18 0.00 67.18 0.00 0.00
Maximum of Months 177.64 274.84 158.86 13.87 144.99 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 157.99 183.74 122.93 62.35 60.58 0.00 0.00
February 178.68 164.24 145.86 68.01 77.85 0.00 0.00
March 204.61 168.02 165.18 73.43 91.75 0.00 0.00
April 312.78 142.89 226.69 116.52 110.17 0.00 0.00
May 293.18 132.08 220.94 100.80 120.14 0.00 0.00
June 327.04 106.87 234.32 115.86 118.46 0.00 0.00
July 361.44 102.87 248.31 130.76 117.55 0.00 0.00
August 347.29 106.74 234.01 124.93 109.09 0.00 0.00
September 290.30 119.30 201.39 107.10 94.29 0.00 0.00
October 230.41 133.87 155.39 84.88 70.50 0.00 0.00
November 182.33 175.89 141.40 74.47 66.93 0.00 0.00
December 163.65 189.47 125.75 67.83 57.92 0.00 0.00
               
Annual Sum or Average 254.50 143.75 185.33 94.02 91.31 0.00 0.00
Minimum of Months 157.99 102.87 122.93 62.35 57.92 0.00 0.00
Maximum of Months 361.44 189.47 248.31 130.76 120.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.241059E+10 0.941682E+09 0.162978E+10 0.120268E+10 0.427093E+09 0.00 0.00
February 0.161737E+10 0.747022E+09 0.115030E+10 0.716897E+09 0.433406E+09 0.00 0.00
March 0.127838E+10 0.841106E+09 0.934350E+09 0.439621E+09 0.494729E+09 0.00 0.00
April 0.770423E+09 0.671182E+09 0.597085E+09 0.151148E+09 0.445937E+09 0.00 0.00
May 0.446950E+09 0.629955E+09 0.464791E+09 2830831.78 0.461961E+09 0.00 0.00
June 0.468494E+09 0.485554E+09 0.441181E+09 0.73 0.441181E+09 0.00 0.00
July 0.520143E+09 0.472543E+09 0.450073E+09 2198051.31 0.447875E+09 0.00 0.00
August 0.667937E+09 0.497570E+09 0.501154E+09 72107423.15 0.429047E+09 0.00 0.00
September 0.125018E+10 0.573819E+09 0.815480E+09 0.377076E+09 0.438404E+09 0.00 0.00
October 0.199289E+10 0.679023E+09 0.125440E+10 0.841705E+09 0.412693E+09 0.00 0.00
November 0.221227E+10 0.862137E+09 0.150823E+10 0.107225E+10 0.435984E+09 0.00 0.00
December 0.258277E+10 0.965277E+09 0.174310E+10 0.133317E+10 0.409933E+09 0.00 0.00
               
Annual Sum or Average 0.162184E+11 0.836687E+10 0.114899E+11 0.621168E+10 0.527824E+10 0.00 0.00
Minimum of Months 0.446950E+09 0.472543E+09 0.441181E+09 0.73 0.409933E+09 0.00 0.00
Maximum of Months 0.258277E+10 0.965277E+09 0.174310E+10 0.133317E+10 0.494729E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.426123E+09 0.467815E+09 0.346551E+09 0.186607E+09 0.159944E+09 0.00 0.00
February 0.376273E+09 0.376078E+09 0.325705E+09 0.150389E+09 0.175316E+09 0.00 0.00
March 0.525367E+09 0.427816E+09 0.436158E+09 0.195564E+09 0.240594E+09 0.00 0.00
April 0.717523E+09 0.344607E+09 0.533628E+09 0.263311E+09 0.270317E+09 0.00 0.00
May 0.661175E+09 0.330641E+09 0.515367E+09 0.211686E+09 0.303681E+09 0.00 0.00
June 0.671379E+09 0.259269E+09 0.492744E+09 0.207319E+09 0.285424E+09 0.00 0.00
July 0.838706E+09 0.258462E+09 0.579238E+09 0.280585E+09 0.298653E+09 0.00 0.00
August 0.850960E+09 0.263618E+09 0.577362E+09 0.300520E+09 0.276843E+09 0.00 0.00
September 0.566784E+09 0.287363E+09 0.406596E+09 0.182649E+09 0.223947E+09 0.00 0.00
October 0.543637E+09 0.336392E+09 0.379067E+09 0.194783E+09 0.184284E+09 0.00 0.00
November 0.405634E+09 0.432885E+09 0.337325E+09 0.172456E+09 0.164870E+09 0.00 0.00
December 0.409431E+09 0.479636E+09 0.334894E+09 0.187201E+09 0.147693E+09 0.00 0.00
               
Annual Sum or Average 0.699299E+10 0.426458E+10 0.526464E+10 0.253307E+10 0.273157E+10 0.00 0.00
Minimum of Months 0.376273E+09 0.258462E+09 0.325705E+09 0.150389E+09 0.147693E+09 0.00 0.00
Maximum of Months 0.850960E+09 0.479636E+09 0.579238E+09 0.300520E+09 0.303681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.140211E+09 0.711160E+09 0.192673E+09 0.00 0.192673E+09 0.00 0.00
February 0.147397E+09 0.575858E+09 0.216203E+09 0.00 0.216203E+09 0.00 0.00
March 0.233605E+09 0.656775E+09 0.292945E+09 0.00 0.292945E+09 0.00 0.00
April 0.312464E+09 0.515376E+09 0.331842E+09 1146341.91 0.330696E+09 0.00 0.00
May 0.378188E+09 0.476993E+09 0.403318E+09 16948065.37 0.386370E+09 0.00 0.00
June 0.446756E+09 0.368157E+09 0.411774E+09 35957743.10 0.375816E+09 0.00 0.00
July 0.475779E+09 0.361116E+09 0.407828E+09 29621659.63 0.378207E+09 0.00 0.00
August 0.402228E+09 0.379143E+09 0.346130E+09 5998705.49 0.340132E+09 0.00 0.00
September 0.307898E+09 0.431009E+09 0.283026E+09 42422.78 0.282984E+09 0.00 0.00
October 0.274110E+09 0.506499E+09 0.230746E+09 0.00 0.230746E+09 0.00 0.00
November 0.142313E+09 0.662485E+09 0.201975E+09 0.00 0.201975E+09 0.00 0.00
December 0.124014E+09 0.736132E+09 0.179929E+09 0.00 0.179929E+09 0.00 0.00
               
Annual Sum or Average 0.338496E+10 0.638070E+10 0.349839E+10 89714938.28 0.340868E+10 0.00 0.00
Minimum of Months 0.124014E+09 0.361116E+09 0.179929E+09 0.00 0.179929E+09 0.00 0.00
Maximum of Months 0.475779E+09 0.736132E+09 0.411774E+09 35957743.10 0.386370E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.423149E+09 0.492141E+09 0.329246E+09 0.166999E+09 0.162247E+09 0.00 0.00
February 0.432251E+09 0.397341E+09 0.352862E+09 0.164533E+09 0.188329E+09 0.00 0.00
March 0.548039E+09 0.450028E+09 0.442408E+09 0.196666E+09 0.245742E+09 0.00 0.00
April 0.810715E+09 0.370383E+09 0.587573E+09 0.302022E+09 0.285550E+09 0.00 0.00
May 0.785265E+09 0.353771E+09 0.591762E+09 0.269974E+09 0.321788E+09 0.00 0.00
June 0.847692E+09 0.277007E+09 0.607347E+09 0.300308E+09 0.307039E+09 0.00 0.00
July 0.968072E+09 0.275519E+09 0.665063E+09 0.350222E+09 0.314841E+09 0.00 0.00
August 0.930190E+09 0.285896E+09 0.626784E+09 0.334601E+09 0.292184E+09 0.00 0.00
September 0.752466E+09 0.309229E+09 0.522008E+09 0.277597E+09 0.244411E+09 0.00 0.00
October 0.617124E+09 0.358550E+09 0.416185E+09 0.227356E+09 0.188829E+09 0.00 0.00
November 0.472599E+09 0.455898E+09 0.366502E+09 0.193021E+09 0.173482E+09 0.00 0.00
December 0.438324E+09 0.507483E+09 0.336808E+09 0.181670E+09 0.155138E+09 0.00 0.00
               
Annual Sum or Average 0.802589E+10 0.453325E+10 0.584455E+10 0.296497E+10 0.287958E+10 0.00 0.00
Minimum of Months 0.423149E+09 0.275519E+09 0.329246E+09 0.164533E+09 0.155138E+09 0.00 0.00
Maximum of Months 0.968072E+09 0.507483E+09 0.665063E+09 0.350222E+09 0.321788E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.492321E+09 -422577225.0 0.00 0.00 744.00 0.00 -69743799.5 58.99 0.00 0.00
February 0.445471E+09 -382797606.8 0.00 0.00 672.00 0.00 -62673576.1 58.99 0.00 0.00
March 0.527558E+09 -458201082.4 0.00 0.00 744.00 0.00 -69356574.2 58.99 0.00 0.00
April 0.456345E+09 -390207158.6 0.00 0.00 720.00 0.00 -66138267.1 59.00 0.00 0.00
May 0.486452E+09 -418584209.6 0.00 0.00 744.00 0.00 -67867353.4 58.98 0.00 0.00
June 0.473118E+09 -408245086.1 0.00 0.00 720.00 0.00 -64872453.3 58.97 0.00 0.00
July 0.431566E+09 -365575993.4 0.00 0.00 744.00 0.00 -65990045.3 58.99 0.00 0.00
August 0.486145E+09 -419924770.7 0.00 0.00 744.00 0.00 -66220016.3 58.99 0.00 0.00
September 0.434348E+09 -369857700.7 0.00 0.00 720.00 0.00 -64490324.6 59.00 0.00 0.00
October 0.463663E+09 -397109906.0 0.00 0.00 744.00 0.00 -66552884.9 58.99 0.00 0.00
November 0.473540E+09 -407466933.6 0.00 0.00 720.00 0.00 -66073222.3 58.99 0.00 0.00
December 0.465831E+09 -396858369.3 0.00 0.00 744.00 0.00 -68972160.4 58.99 0.00 0.00
                     
Annual Sum or Average 0.563636E+10 -0.483741E+10 0.00 0.00 8760.00 0.00 -798950677.3 58.99 0.00 0.00
Minimum of Months 0.431566E+09 -458201082.4 0.00 0.00 672.00 0.00 -69743799.5 58.97 0.00 0.00
Maximum of Months 0.527558E+09 -365575993.4 0.00 0.00 744.00 0.00 -62673576.1 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.78 0.76 01-JAN-07:30 1700.86 27.66 160.33 253.33 678.23 25.09 227.50 227.17
February 279.67 0.78 0.76 01-FEB-07:19 1623.50 27.05 153.67 230.50 437.60 21.95 186.67 164.00
March 338.17 0.80 0.76 01-MAR-06:00 513.87 17.16 6.33 223.33 338.10 20.94 205.67 152.83
April 358.33 0.80 0.76 01-APR-09:20 328.95 16.45 0.00 150.50 245.71 20.65 140.00 28.33
May 393.83 0.83 0.76 01-MAY-07:00 275.69 15.91 0.00 77.00 202.10 20.10 105.00 0.00
June 381.00 0.84 0.76 03-JUN-08:09 248.84 15.44 0.00 24.83 185.04 19.64 49.83 0.00
July 408.67 0.84 0.76 01-JUL-08:00 252.88 15.52 0.00 29.00 189.66 19.74 80.67 0.33
August 390.67 0.82 0.76 01-AUG-07:00 281.72 15.91 0.00 74.00 210.54 20.07 95.83 12.83
September 328.83 0.80 0.76 01-SEP-07:30 455.71 16.95 5.50 208.83 304.20 20.85 157.67 117.33
October 296.17 0.79 0.76 01-OCT-09:39 1067.67 20.17 57.00 227.83 441.58 21.90 136.50 175.50
November 300.00 0.78 0.76 01-NOV-06:49 1658.89 26.26 148.50 250.17 618.89 26.36 248.50 240.33
December 297.00 0.78 0.76 01-DEC-07:30 1162.26 26.04 138.17 257.33 727.37 24.85 220.00 229.83
                         
Annual Sum or Average 4065.67 0.81     730.58 19.49 669.50 2006.67 360.60 21.62 1853.83 1348.50
Minimum of Months 279.67 0.78 0.76   248.84 15.44 0.00 24.83 185.04 19.64 49.83 0.00
Maximum of Months 408.67 0.84 0.76   1700.86 27.66 160.33 257.33 727.37 26.36 248.50 240.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.85 0.76 01-JAN-07:00 733.30 20.31 62.50 89.33 392.55 19.76 64.50 70.00
February 279.67 0.84 0.76 01-FEB-07:49 305.61 16.79 17.00 84.67 421.40 18.72 46.33 64.67
March 338.17 0.84 0.76 01-MAR-06:00 307.01 15.95 1.17 106.17 259.37 15.45 1.83 72.33
April 358.33 0.84 0.76 01-APR-06:30 308.42 15.40 0.00 111.17 268.49 15.00 0.00 92.50
May 393.83 0.84 0.76 01-MAY-06:49 291.81 15.04 0.00 108.83 249.03 14.54 0.00 87.50
June 381.00 0.85 0.76 01-JUN-06:49 278.16 14.59 0.00 92.00 242.19 14.19 0.00 78.00
July 408.67 0.85 0.76 01-JUL-05:00 292.65 14.59 0.00 119.67 262.10 14.36 0.00 104.67
August 390.67 0.85 0.76 01-AUG-07:40 294.25 14.82 0.00 115.33 263.08 14.56 0.00 101.67
September 328.83 0.85 0.76 01-SEP-07:10 376.72 15.84 5.50 85.17 236.16 15.01 0.00 64.17
October 296.17 0.86 0.76 01-OCT-09:39 881.27 18.06 47.17 84.50 331.27 15.65 11.00 58.33
November 300.00 0.85 0.76 01-NOV-07:10 772.23 19.20 57.83 91.83 561.02 20.14 71.00 71.83
December 297.00 0.85 0.76 01-DEC-07:00 744.73 19.99 61.33 84.33 438.07 20.26 67.67 70.17
                         
Annual Sum or Average 4065.67 0.85     444.72 16.49 252.50 1173.00 317.62 16.22 262.33 935.83
Minimum of Months 279.67 0.84 0.76   278.16 14.59 0.00 84.33 236.16 14.19 0.00 58.33
Maximum of Months 408.67 0.86 0.76   881.27 20.31 62.50 119.67 561.02 20.26 71.00 104.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.92 0.86 30-JAN-12:30 121.33 0.00 0.00 0.00 93.12 0.00 0.00 0.00
February 279.67 0.91 0.84 26-FEB-13:30 146.68 0.00 0.00 0.00 106.84 0.00 0.00 0.00
March 338.17 0.89 0.82 26-MAR-14:30 172.54 0.00 0.00 0.00 121.95 0.00 0.00 0.00
April 358.33 0.87 0.76 17-APR-14:30 197.30 0.00 0.00 0.00 141.13 0.00 0.00 0.00
May 393.83 0.84 0.76 02-MAY-06:10 266.10 0.00 0.00 21.33 163.48 0.00 0.00 0.00
June 381.00 0.84 0.76 01-JUN-07:19 252.81 0.00 0.00 20.83 171.27 0.00 0.00 0.00
July 408.67 0.84 0.76 01-JUL-16:19 241.65 0.00 0.00 5.67 165.77 0.00 0.00 0.00
August 390.67 0.87 0.76 01-AUG-17:10 210.81 0.00 0.00 10.83 143.51 0.00 0.00 0.00
September 328.83 0.89 0.81 08-SEP-14:30 173.01 0.00 0.00 0.00 126.37 0.00 0.00 0.00
October 296.17 0.92 0.82 07-OCT-13:30 128.79 0.00 0.00 0.00 96.96 0.00 0.00 0.00
November 300.00 0.92 0.84 02-NOV-13:30 123.65 0.00 0.00 0.00 93.73 0.00 0.00 0.00
December 297.00 0.93 0.88 11-DEC-12:30 109.89 0.00 0.00 0.00 86.01 0.00 0.00 0.00
                         
Annual Sum or Average 4065.67 0.88     185.12 0.00 0.00 58.67 129.47 0.00 0.00 0.00
Minimum of Months 279.67 0.84 0.76   109.89 0.00 0.00 0.00 86.01 0.00 0.00 0.00
Maximum of Months 408.67 0.93 0.88   266.10 0.00 0.00 21.33 171.27 0.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.85 0.76 01-JAN-12:09 1227.88 21.75 87.67 94.33 349.81 18.72 59.33 71.17
February 279.67 0.84 0.76 01-FEB-12:20 755.23 19.38 57.00 98.83 479.83 18.77 53.33 71.17
March 338.17 0.84 0.76 01-MAR-12:50 343.27 16.04 3.67 110.50 267.16 15.39 1.83 77.50
April 358.33 0.84 0.76 01-APR-12:09 323.68 15.47 0.00 114.67 284.51 15.03 0.00 99.83
May 393.83 0.84 0.76 01-MAY-13:09 314.34 15.13 0.00 122.17 272.71 14.59 0.00 104.33
June 381.00 0.84 0.76 01-JUN-13:09 316.09 14.66 0.00 121.33 282.62 14.26 0.00 108.83
July 408.67 0.84 0.76 01-JUL-13:39 315.75 14.63 0.00 133.67 287.33 14.39 0.00 121.50
August 390.67 0.84 0.76 01-AUG-13:20 312.41 14.89 0.00 124.83 281.99 14.61 0.00 113.67
September 328.83 0.84 0.76 01-SEP-12:00 332.23 15.89 0.17 117.67 285.00 15.41 0.00 96.33
October 296.17 0.85 0.76 01-OCT-12:50 423.75 16.24 8.83 91.00 360.30 16.06 11.17 72.17
November 300.00 0.85 0.76 01-NOV-12:20 888.56 19.51 63.17 104.33 651.72 20.46 77.67 79.17
December 297.00 0.86 0.76 01-DEC-11:09 1098.72 21.25 90.33 93.17 536.89 20.07 80.00 75.50
                         
Annual Sum or Average 4065.67 0.84     523.02 16.80 310.83 1326.50 351.03 16.24 283.33 1091.17
Minimum of Months 279.67 0.84 0.76   312.41 14.63 0.00 91.00 267.16 14.26 0.00 71.17
Maximum of Months 408.67 0.86 0.76   1227.88 21.75 90.33 133.67 651.72 20.46 80.00 121.50



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6129175.81 5681.18 02-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 6129175.81     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 6129175.81 5681.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 58491880.06 6096.03 04-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 23927760.99 5587.37 09-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 0.111754E+09 6518.97 10-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 7455832.98 6275.20 20-APR-07:01 0.00 0.00 0.00 0.00 0.00
May 3796458.73 6305.36 15-MAY-07:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 12100151.68 5000.20 13-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.217526E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111754E+09 6518.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 17303166.78 4403.02 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 2244990.15 3280.49 27-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 6880558.16 3725.30 30-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 147271.57 788.81 13-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 26575986.66     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 17303166.78 4403.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104816E+09 5338.16 04-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 14833330.87 5338.16 06-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 45453481.87 5708.51 10-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 419376.30 3494.80 03-APR-07:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 416283.27 1706.43 24-NOV-08:63 0.00 0.00 0.00 0.00 0.00
December 11299563.07 5260.70 26-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.177239E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104816E+09 5708.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 28132564.32 5279.48 02-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 1598052.43 3262.39 27-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 10874938.70 5073.08 08-MAR-08:61 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 1077135.35 2562.42 13-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 41682690.79     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 28132564.32 5279.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 102680.93 1197.94 03-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 102680.93     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 102680.93 1197.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 631036.92 3681.05 03-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 631036.92     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 631036.92 3681.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 431261.86 2295.99 03-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 431261.86     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 431261.86 2295.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1253476.29 3656.59 03-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1253476.29     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1253476.29 3656.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 392515.41 2289.67 03-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 392515.41     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 392515.41 2289.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.918670E+09 0.770025E+09 5165.69 25-JAN-08:63 4721.82 0.00
February 0.00 0.00 0.807346E+09 0.673411E+09 2522.22 01-FEB-16:00 1925.80 0.00
March 0.00 0.00 0.910105E+09 0.702665E+09 3158.29 24-MAR-07:03 2229.75 0.00
April 0.00 0.00 0.151213E+10 0.119960E+10 5396.46 27-APR-07:03 3857.71 0.00
May 0.00 0.00 0.184288E+10 0.150107E+10 5405.00 03-MAY-07:02 3969.94 0.00
June 0.00 0.00 0.248580E+10 0.193998E+10 5515.30 30-JUN-07:02 3759.11 0.00
July 0.00 0.00 0.304139E+10 0.231368E+10 5552.89 20-JUL-07:02 3527.44 0.00
August 0.00 0.00 0.349268E+10 0.262237E+10 5591.06 18-AUG-07:02 3474.24 0.00
September 0.00 0.00 0.248781E+10 0.192334E+10 5581.58 22-SEP-07:03 3547.95 0.00
October 0.00 0.00 0.260045E+10 0.220159E+10 5593.71 05-OCT-07:02 3576.36 0.00
November 0.00 0.00 0.139613E+10 0.119296E+10 5405.03 10-NOV-08:63 3759.84 0.00
December 0.00 0.00 0.102650E+10 0.935045E+09 5051.53 05-DEC-08:62 5051.53 0.00
                 
Annual Sum or Average 0.00 0.00 0.225219E+11 0.179757E+11       0.00
Minimum of Months 0.00 0.00 0.807346E+09 0.673411E+09 2522.22   1925.80 0.00
Maximum of Months 0.00 0.00 0.349268E+10 0.262237E+10 5593.71   5051.53 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.126770E+10 0.119865E+10 4664.61 20-JAN-13:05 4010.51 0.00
February 0.00 0.00 0.770407E+09 0.722783E+09 3664.17 03-FEB-14:20 3664.17 0.00
March 0.00 0.00 0.549229E+09 0.474506E+09 3711.30 23-MAR-14:00 3162.75 0.00
April 0.00 0.00 0.748269E+09 0.639442E+09 3191.37 26-APR-13:30 2907.33 0.00
May 0.00 0.00 0.662669E+09 0.575530E+09 2580.09 04-MAY-14:00 2217.21 0.00
June 0.00 0.00 0.118044E+10 0.946632E+09 3023.57 29-JUN-13:00 2234.03 0.00
July 0.00 0.00 0.183977E+10 0.141011E+10 4986.51 31-JUL-12:00 3686.61 0.00
August 0.00 0.00 0.236516E+10 0.180932E+10 5780.24 14-AUG-07:02 3742.24 0.00
September 0.00 0.00 0.196419E+10 0.161183E+10 5321.41 29-SEP-07:02 5321.41 0.00
October 0.00 0.00 0.257039E+10 0.230934E+10 5835.91 05-OCT-07:02 3539.11 0.00
November 0.00 0.00 0.159000E+10 0.148691E+10 5098.29 20-NOV-13:05 4296.97 0.00
December 0.00 0.00 0.144893E+10 0.141499E+10 5073.51 19-DEC-13:15 5073.51 0.00
                 
Annual Sum or Average 0.00 0.00 0.169572E+11 0.146000E+11       0.00
Minimum of Months 0.00 0.00 0.549229E+09 0.474506E+09 2580.09   2217.21 0.00
Maximum of Months 0.00 0.00 0.257039E+10 0.230934E+10 5835.91   5321.41 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.289369E+09 0.268828E+09 1423.45 20-JAN-12:00 1267.90 0.00
February 0.00 0.00 0.221391E+09 0.206899E+09 1238.91 01-FEB-11:55 1238.91 0.00
March 0.00 0.00 0.249913E+09 0.216781E+09 1729.02 23-MAR-10:20 1525.57 0.00
April 0.00 0.00 0.688876E+09 0.610395E+09 4159.25 26-APR-07:01 3451.93 0.00
May 0.00 0.00 0.774018E+09 0.699064E+09 4199.40 03-MAY-07:02 3309.33 0.00
June 0.00 0.00 0.111931E+10 0.959340E+09 4294.54 30-JUN-07:02 3169.23 0.00
July 0.00 0.00 0.155905E+10 0.130243E+10 4339.15 31-JUL-07:02 3017.75 0.00
August 0.00 0.00 0.180307E+10 0.148996E+10 4372.39 07-AUG-07:02 2945.17 0.00
September 0.00 0.00 0.112719E+10 0.953571E+09 4343.97 22-SEP-07:03 2931.33 0.00
October 0.00 0.00 0.118204E+10 0.107123E+10 4385.09 05-OCT-07:02 2900.76 0.00
November 0.00 0.00 0.469972E+09 0.437013E+09 1208.52 20-NOV-12:00 1052.15 0.00
December 0.00 0.00 0.323333E+09 0.316192E+09 1386.08 05-DEC-09:53 1386.08 0.00
                 
Annual Sum or Average 0.00 0.00 0.980752E+10 0.853170E+10       0.00
Minimum of Months 0.00 0.00 0.221391E+09 0.206899E+09 1208.52   1052.15 0.00
Maximum of Months 0.00 0.00 0.180307E+10 0.148996E+10 4385.09   3451.93 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.207985E+09 0.182620E+09 1507.30 18-JAN-14:30 1448.78 0.00
February 0.00 0.00 98922837.85 87941391.44 1194.07 03-FEB-14:55 1194.07 0.00
March 0.00 0.00 0.141703E+09 0.112045E+09 1691.81 23-MAR-15:10 1315.13 0.00
April 0.00 0.00 0.572379E+09 0.475659E+09 2301.67 26-APR-13:55 2052.14 0.00
May 0.00 0.00 0.828858E+09 0.712393E+09 2502.44 04-MAY-14:00 2150.71 0.00
June 0.00 0.00 0.136472E+10 0.110796E+10 4982.24 30-JUN-07:02 3472.39 0.00
July 0.00 0.00 0.189204E+10 0.148786E+10 5052.11 24-JUL-07:02 3332.45 0.00
August 0.00 0.00 0.211857E+10 0.163785E+10 5106.45 07-AUG-07:02 3163.86 0.00
September 0.00 0.00 0.134528E+10 0.107440E+10 5047.98 22-SEP-07:03 3215.02 0.00
October 0.00 0.00 0.142192E+10 0.123173E+10 5106.05 05-OCT-07:02 3265.95 0.00
November 0.00 0.00 0.371563E+09 0.329309E+09 1605.14 10-NOV-13:10 1274.70 0.00
December 0.00 0.00 0.197275E+09 0.189454E+09 1449.85 05-DEC-14:55 1449.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.105612E+11 0.862922E+10       0.00
Minimum of Months 0.00 0.00 98922837.85 87941391.44 1194.07   1194.07 0.00
Maximum of Months 0.00 0.00 0.211857E+10 0.163785E+10 5106.45   3472.39 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.335102E+09 0.304373E+09 1822.23 18-JAN-15:30 1713.95 0.00
February 0.00 0.00 0.272236E+09 0.246866E+09 1837.92 01-FEB-16:25 1571.99 0.00
March 0.00 0.00 0.304595E+09 0.259516E+09 2460.91 23-MAR-15:53 2056.82 0.00
April 0.00 0.00 0.713195E+09 0.618304E+09 2758.16 26-APR-15:53 2467.67 0.00
May 0.00 0.00 0.834135E+09 0.738272E+09 3478.58 03-MAY-07:02 2759.68 0.00
June 0.00 0.00 0.120400E+10 0.101631E+10 5133.06 30-JUN-07:02 3845.80 0.00
July 0.00 0.00 0.159070E+10 0.130969E+10 5208.26 24-JUL-07:02 3645.08 0.00
August 0.00 0.00 0.181742E+10 0.147858E+10 5270.39 07-AUG-07:02 3463.63 0.00
September 0.00 0.00 0.125858E+10 0.105507E+10 5198.10 22-SEP-07:03 3537.24 0.00
October 0.00 0.00 0.124926E+10 0.111732E+10 5250.98 05-OCT-07:02 3550.50 0.00
November 0.00 0.00 0.574683E+09 0.524884E+09 2030.73 10-NOV-15:23 1706.42 0.00
December 0.00 0.00 0.377262E+09 0.363516E+09 1846.42 07-DEC-15:32 1593.17 0.00
                 
Annual Sum or Average 0.00 0.00 0.105312E+11 0.903270E+10       0.00
Minimum of Months 0.00 0.00 0.272236E+09 0.246866E+09 1822.23   1571.99 0.00
Maximum of Months 0.00 0.00 0.181742E+10 0.147858E+10 5270.39   3845.80 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 225.45 534.56 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 35.80 534.58 02-FEB-12:15
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     21.89    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   225.45 534.58  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.329024E+09 0.34 334.78 02-JAN-06:10 0.93
February 0.297688E+09 0.34 334.78 01-FEB-06:10 0.93
March 0.360360E+09 0.37 334.78 01-MAR-06:05 0.93
April 0.313356E+09 0.33 334.78 03-APR-05:10 0.93
May 0.344692E+09 0.36 334.78 01-MAY-05:10 0.93
June 0.344692E+09 0.37 334.78 01-JUN-05:10 0.93
July 0.313356E+09 0.32 334.78 03-JUL-05:10 0.92
August 0.360360E+09 0.37 334.78 01-AUG-05:10 0.92
September 0.313356E+09 0.33 334.78 01-SEP-05:10 0.92
October 0.329024E+09 0.34 334.78 02-OCT-05:10 0.93
November 0.329024E+09 0.35 334.78 01-NOV-05:10 0.93
December 0.313356E+09 0.33 334.78 01-DEC-06:05 0.93
           
Annual Sum or Average 0.394829E+10 0.35      
Minimum of Months 0.297688E+09 0.32 334.78   0.92
Maximum of Months 0.360360E+09 0.37 334.78   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.355933E+09 0.34 362.16 02-JAN-06:10 0.93
February 0.322034E+09 0.34 362.16 01-FEB-06:10 0.93
March 0.389831E+09 0.37 362.16 01-MAR-06:05 0.93
April 0.338983E+09 0.34 362.16 03-APR-05:10 0.93
May 0.372882E+09 0.36 362.16 01-MAY-05:10 0.93
June 0.372882E+09 0.37 362.16 01-JUN-05:10 0.93
July 0.338983E+09 0.32 362.16 03-JUL-05:10 0.93
August 0.389831E+09 0.37 362.16 01-AUG-05:10 0.92
September 0.339690E+09 0.34 362.16 01-SEP-05:10 0.92
October 0.356906E+09 0.35 362.16 02-OCT-05:10 0.92
November 0.355933E+09 0.35 362.16 01-NOV-05:10 0.93
December 0.338983E+09 0.33 362.16 01-DEC-06:05 0.93
           
Annual Sum or Average 0.427287E+10 0.35      
Minimum of Months 0.322034E+09 0.32 362.16   0.92
Maximum of Months 0.389831E+09 0.37 362.16   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.269025E+09 0.34 273.73 02-JAN-06:10 0.93
February 0.243404E+09 0.34 273.73 01-FEB-06:10 0.93
March 0.294646E+09 0.37 273.73 01-MAR-06:05 0.93
April 0.256214E+09 0.34 273.73 03-APR-05:10 0.93
May 0.281836E+09 0.36 273.73 01-MAY-05:10 0.93
June 0.281836E+09 0.37 273.73 01-JUN-05:10 0.93
July 0.256214E+09 0.32 273.73 03-JUL-05:10 0.93
August 0.294646E+09 0.37 273.73 01-AUG-05:10 0.92
September 0.256214E+09 0.33 273.73 01-SEP-05:10 0.93
October 0.269025E+09 0.34 273.73 02-OCT-05:10 0.92
November 0.269025E+09 0.35 273.73 01-NOV-05:10 0.93
December 0.256214E+09 0.33 273.73 01-DEC-06:05 0.93
           
Annual Sum or Average 0.322830E+10 0.35      
Minimum of Months 0.243404E+09 0.32 273.73   0.92
Maximum of Months 0.294646E+09 0.37 273.73   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.308533E+09 0.34 313.93 02-JAN-06:10 0.93
February 0.279149E+09 0.34 313.93 01-FEB-06:10 0.93
March 0.337917E+09 0.37 313.93 01-MAR-06:05 0.93
April 0.293841E+09 0.34 313.93 03-APR-05:10 0.93
May 0.323225E+09 0.36 313.93 01-MAY-05:10 0.93
June 0.323225E+09 0.37 313.93 01-JUN-05:10 0.93
July 0.293841E+09 0.32 313.93 03-JUL-05:10 0.93
August 0.337917E+09 0.37 313.93 01-AUG-05:10 0.92
September 0.293841E+09 0.33 313.93 01-SEP-05:10 0.93
October 0.308533E+09 0.34 313.93 02-OCT-05:10 0.92
November 0.308533E+09 0.35 313.93 01-NOV-05:10 0.93
December 0.293841E+09 0.33 313.93 01-DEC-06:05 0.93
           
Annual Sum or Average 0.370239E+10 0.35      
Minimum of Months 0.279149E+09 0.32 313.93   0.92
Maximum of Months 0.337917E+09 0.37 313.93   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.322577E+09 0.34 328.22 02-JAN-06:10 0.93
February 0.291855E+09 0.34 328.22 01-FEB-06:10 0.93
March 0.353299E+09 0.37 328.22 01-MAR-06:05 0.93
April 0.307216E+09 0.34 328.22 03-APR-05:10 0.93
May 0.337938E+09 0.36 328.22 01-MAY-05:10 0.93
June 0.337938E+09 0.37 328.22 01-JUN-05:10 0.93
July 0.307216E+09 0.32 328.22 03-JUL-05:10 0.93
August 0.353299E+09 0.37 328.22 01-AUG-05:10 0.92
September 0.307216E+09 0.33 328.22 01-SEP-05:10 0.93
October 0.322577E+09 0.34 328.22 02-OCT-05:10 0.92
November 0.322577E+09 0.35 328.22 01-NOV-05:10 0.93
December 0.307216E+09 0.33 328.22 01-DEC-06:05 0.93
           
Annual Sum or Average 0.387092E+10 0.35      
Minimum of Months 0.291855E+09 0.32 328.22   0.92
Maximum of Months 0.353299E+09 0.37 328.22   0.93



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:01 0.00 0.00 44.21 0.00
February 0.00 0.00 0.00 01-FEB-07:05 0.00 0.00 17.32 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 17.32 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 17.32 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 17.32 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 17.32 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 17.32 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 17.32 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 17.32 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 17.32 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 17.32 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 17.32 0.00
                 
Annual Sum or Average 0.02 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 17.32 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 44.21 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 225.45 534.56 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 17.32 17.32 35.80 534.58 02-FEB-12:15
March 0.00 0.00 01-MAR-00:10 17.32 17.32 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 17.32 17.32 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 17.32 17.32 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 17.32 17.32 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 17.32 17.32 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 17.32 17.32 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 17.32 17.32 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 17.32 17.32 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 17.32 17.32 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 17.32 17.32 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         21.89    
Minimum of Months 0.00 0.00   17.32 17.32 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 225.45 534.58  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.532663E+09 0.00 0.00
February 0.00 0.00 0.00 0.475026E+09 0.00 0.00
March 0.00 0.00 0.00 0.559353E+09 0.00 0.00
April 0.00 0.00 0.00 0.638571E+09 0.00 0.00
May 0.00 0.00 0.00 0.737966E+09 0.00 0.00
June 0.00 0.00 0.00 0.865229E+09 0.00 0.00
July 0.00 0.00 0.00 0.940395E+09 0.00 0.00
August 0.00 0.00 0.00 0.108061E+10 0.00 0.00
September 0.00 0.00 0.00 0.835548E+09 0.00 0.00
October 0.00 0.00 0.00 0.882374E+09 0.00 0.00
November 0.00 0.00 0.00 0.631706E+09 0.00 0.00
December 0.00 0.00 0.00 0.539444E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.871889E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.475026E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.108061E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.647444E+09 0.00 0.00
February 0.00 0.00 0.00 0.495898E+09 0.00 0.00
March 0.00 0.00 0.00 0.545648E+09 0.00 0.00
April 0.00 0.00 0.00 0.505961E+09 0.00 0.00
May 0.00 0.00 0.00 0.520926E+09 0.00 0.00
June 0.00 0.00 0.00 0.631744E+09 0.00 0.00
July 0.00 0.00 0.00 0.737780E+09 0.00 0.00
August 0.00 0.00 0.00 0.897760E+09 0.00 0.00
September 0.00 0.00 0.00 0.761908E+09 0.00 0.00
October 0.00 0.00 0.00 0.906231E+09 0.00 0.00
November 0.00 0.00 0.00 0.692495E+09 0.00 0.00
December 0.00 0.00 0.00 0.650259E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.799405E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.495898E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.906231E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.340598E+09 0.00 0.00
February 0.00 0.00 0.00 0.294095E+09 0.00 0.00
March 0.00 0.00 0.00 0.352767E+09 0.00 0.00
April 0.00 0.00 0.00 0.408633E+09 0.00 0.00
May 0.00 0.00 0.00 0.452297E+09 0.00 0.00
June 0.00 0.00 0.00 0.525901E+09 0.00 0.00
July 0.00 0.00 0.00 0.592491E+09 0.00 0.00
August 0.00 0.00 0.00 0.683590E+09 0.00 0.00
September 0.00 0.00 0.00 0.504700E+09 0.00 0.00
October 0.00 0.00 0.00 0.534628E+09 0.00 0.00
November 0.00 0.00 0.00 0.374465E+09 0.00 0.00
December 0.00 0.00 0.00 0.329577E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.539374E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.294095E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.683590E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.389928E+09 0.00 0.00
February 0.00 0.00 0.00 0.306195E+09 0.00 0.00
March 0.00 0.00 0.00 0.384417E+09 0.00 0.00
April 0.00 0.00 0.00 0.421125E+09 0.00 0.00
May 0.00 0.00 0.00 0.505804E+09 0.00 0.00
June 0.00 0.00 0.00 0.619755E+09 0.00 0.00
July 0.00 0.00 0.00 0.699646E+09 0.00 0.00
August 0.00 0.00 0.00 0.793172E+09 0.00 0.00
September 0.00 0.00 0.00 0.589475E+09 0.00 0.00
October 0.00 0.00 0.00 0.624421E+09 0.00 0.00
November 0.00 0.00 0.00 0.392106E+09 0.00 0.00
December 0.00 0.00 0.00 0.342342E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.606839E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.306195E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.793172E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.407883E+09 0.00 0.00
February 0.00 0.00 0.00 0.353380E+09 0.00 0.00
March 0.00 0.00 0.00 0.424712E+09 0.00 0.00
April 0.00 0.00 0.00 0.464930E+09 0.00 0.00
May 0.00 0.00 0.00 0.522166E+09 0.00 0.00
June 0.00 0.00 0.00 0.601720E+09 0.00 0.00
July 0.00 0.00 0.00 0.654128E+09 0.00 0.00
August 0.00 0.00 0.00 0.749486E+09 0.00 0.00
September 0.00 0.00 0.00 0.585029E+09 0.00 0.00
October 0.00 0.00 0.00 0.604022E+09 0.00 0.00
November 0.00 0.00 0.00 0.450705E+09 0.00 0.00
December 0.00 0.00 0.00 0.392669E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.621083E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.353380E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.749486E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.329024E+09 0.918670E+09 6231856.74 0.00 0.00 0.00 0.00 0.00
February 0.297688E+09 0.807346E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360360E+09 0.910105E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.313356E+09 0.151213E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.344692E+09 0.184288E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.344692E+09 0.248580E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.313356E+09 0.304139E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.360360E+09 0.349268E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.313356E+09 0.248781E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.329024E+09 0.260045E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.329024E+09 0.139613E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.313356E+09 0.102650E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.394829E+10 0.225219E+11 6231856.74 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.297688E+09 0.807346E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.360360E+09 0.349268E+10 6231856.74 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.355933E+09 0.126770E+10 59122916.98 0.00 0.00 0.00 0.00 0.00
February 0.322034E+09 0.770407E+09 23927760.99 0.00 0.00 0.00 0.00 0.00
March 0.389831E+09 0.549229E+09 0.111754E+09 0.00 0.00 0.00 0.00 0.00
April 0.338983E+09 0.748269E+09 7455832.98 0.00 0.00 0.00 0.00 0.00
May 0.372882E+09 0.662669E+09 3796458.73 0.00 0.00 0.00 0.00 0.00
June 0.372882E+09 0.118044E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.338983E+09 0.183977E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.389831E+09 0.236516E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339690E+09 0.196419E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.356906E+09 0.257039E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.355933E+09 0.159000E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.338983E+09 0.144893E+10 12100151.68 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.427287E+10 0.169572E+11 0.218157E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.322034E+09 0.549229E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.389831E+09 0.257039E+10 0.111754E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.269025E+09 0.289369E+09 17734428.64 0.00 0.00 0.00 0.00 0.00
February 0.243404E+09 0.221391E+09 2244990.15 0.00 0.00 0.00 0.00 0.00
March 0.294646E+09 0.249913E+09 6880558.16 0.00 0.00 0.00 0.00 0.00
April 0.256214E+09 0.688876E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.281836E+09 0.774018E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.281836E+09 0.111931E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.256214E+09 0.155905E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.294646E+09 0.180307E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.256214E+09 0.112719E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.269025E+09 0.118204E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.269025E+09 0.469972E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.256214E+09 0.323333E+09 147271.57 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.322830E+10 0.980752E+10 27007248.52 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.243404E+09 0.221391E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.294646E+09 0.180307E+10 17734428.64 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.308533E+09 0.207985E+09 0.106070E+09 0.00 0.00 0.00 0.00 0.00
February 0.279149E+09 98922837.85 14833330.87 0.00 0.00 0.00 0.00 0.00
March 0.337917E+09 0.141703E+09 45453481.87 0.00 0.00 0.00 0.00 0.00
April 0.293841E+09 0.572379E+09 419376.30 0.00 0.00 0.00 0.00 0.00
May 0.323225E+09 0.828858E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.323225E+09 0.136472E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.293841E+09 0.189204E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.337917E+09 0.211857E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293841E+09 0.134528E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.308533E+09 0.142192E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308533E+09 0.371563E+09 416283.27 0.00 0.00 0.00 0.00 0.00
December 0.293841E+09 0.197275E+09 11299563.07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.370239E+10 0.105612E+11 0.178492E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.279149E+09 98922837.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337917E+09 0.211857E+10 0.106070E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.322577E+09 0.335102E+09 28525079.72 0.00 0.00 0.00 0.00 0.00
February 0.291855E+09 0.272236E+09 1598052.43 0.00 0.00 0.00 0.00 0.00
March 0.353299E+09 0.304595E+09 10874938.70 0.00 0.00 0.00 0.00 0.00
April 0.307216E+09 0.713195E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.337938E+09 0.834135E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.337938E+09 0.120400E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.307216E+09 0.159070E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.353299E+09 0.181742E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.307216E+09 0.125858E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.322577E+09 0.124926E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.322577E+09 0.574683E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.307216E+09 0.377262E+09 1077135.35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.387092E+10 0.105312E+11 42075206.20 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.291855E+09 0.272236E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.353299E+09 0.181742E+10 28525079.72 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.329024E+09 0.00 0.00 2496719.98 0.201142E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.297688E+09 0.00 0.00 0.00 0.177337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.360360E+09 0.00 0.00 0.00 0.198993E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.313356E+09 0.00 0.00 0.00 0.325215E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.344692E+09 0.00 0.00 0.00 0.393274E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.344692E+09 0.00 0.00 0.00 0.520537E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.313356E+09 0.00 0.00 0.00 0.627038E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.360360E+09 0.00 0.00 0.00 0.720254E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.313356E+09 0.00 0.00 0.00 0.522191E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.329024E+09 0.00 0.00 0.00 0.553350E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.329024E+09 0.00 0.00 0.00 0.302682E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.313356E+09 0.00 0.00 0.00 0.226087E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.394829E+10 0.00 0.00 2496719.98 0.476810E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.297688E+09 0.00 0.00 0.00 0.177337E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.360360E+09 0.00 0.00 2496719.98 0.720254E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.355933E+09 0.00 0.00 19736376.57 0.271775E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.322034E+09 0.00 0.00 7669879.73 0.166194E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.389831E+09 0.00 0.00 36350422.29 0.119467E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.338983E+09 0.00 0.00 2260038.94 0.164717E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.372882E+09 0.00 0.00 1177496.72 0.146867E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.372882E+09 0.00 0.00 0.00 0.258862E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.338983E+09 0.00 0.00 0.00 0.398797E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.389831E+09 0.00 0.00 0.00 0.507929E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339690E+09 0.00 0.00 0.00 0.422218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.356906E+09 0.00 0.00 0.00 0.549325E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.355933E+09 0.00 0.00 0.00 0.336562E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.338983E+09 0.00 0.00 4029330.85 0.307246E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.427287E+10 0.00 0.00 71223545.09 0.364996E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.322034E+09 0.00 0.00 0.00 0.119467E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.389831E+09 0.00 0.00 36350422.29 0.549325E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.269025E+09 0.00 0.00 6199907.85 65373455.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.243404E+09 0.00 0.00 718602.27 49972690.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.294646E+09 0.00 0.00 2273789.94 55846343.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.256214E+09 0.00 0.00 0.00 0.152418E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.281836E+09 0.00 0.00 0.00 0.170461E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.281836E+09 0.00 0.00 0.00 0.244065E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.256214E+09 0.00 0.00 0.00 0.336276E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.294646E+09 0.00 0.00 0.00 0.388943E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.256214E+09 0.00 0.00 0.00 0.248486E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.269025E+09 0.00 0.00 0.00 0.265603E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.269025E+09 0.00 0.00 0.00 0.105440E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.256214E+09 0.00 0.00 50297.97 73312123.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.322830E+10 0.00 0.00 9242598.03 0.215620E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.243404E+09 0.00 0.00 0.00 49972690.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.294646E+09 0.00 0.00 6199907.85 0.388943E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.308533E+09 0.00 0.00 34387511.69 47008220.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.279149E+09 0.00 0.00 4650872.57 22395545.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.337917E+09 0.00 0.00 14883971.55 31616027.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.293841E+09 0.00 0.00 124046.21 0.127160E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.323225E+09 0.00 0.00 0.00 0.182579E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.323225E+09 0.00 0.00 0.00 0.296530E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.293841E+09 0.00 0.00 0.00 0.405805E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.337917E+09 0.00 0.00 0.00 0.455255E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293841E+09 0.00 0.00 0.00 0.295634E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.308533E+09 0.00 0.00 0.00 0.315889E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308533E+09 0.00 0.00 132429.50 83440632.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.293841E+09 0.00 0.00 3576587.35 44924580.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.370239E+10 0.00 0.00 57755418.88 0.230824E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.279149E+09 0.00 0.00 0.00 22395545.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.337917E+09 0.00 0.00 34387511.69 0.455255E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.322577E+09 0.00 0.00 9739568.84 75566616.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.291855E+09 0.00 0.00 507980.75 61016878.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.353299E+09 0.00 0.00 3604512.77 67809115.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.307216E+09 0.00 0.00 0.00 0.157714E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.337938E+09 0.00 0.00 0.00 0.184228E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.337938E+09 0.00 0.00 0.00 0.263782E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.307216E+09 0.00 0.00 0.00 0.346912E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.353299E+09 0.00 0.00 0.00 0.396187E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.307216E+09 0.00 0.00 0.00 0.277812E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.322577E+09 0.00 0.00 0.00 0.281445E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.322577E+09 0.00 0.00 0.00 0.128128E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.307216E+09 0.00 0.00 345475.14 85107846.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.387092E+10 0.00 0.00 14197537.50 0.232571E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.291855E+09 0.00 0.00 0.00 61016878.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.353299E+09 0.00 0.00 9739568.84 0.396187E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.526513E+09 0.00 0.00 4598483.33 0.00 1801499.04 0.526383E+09 0.00 0.19
February 0.379131E+09 0.00 0.00 4372153.24 0.00 0.00 0.632196E+09 0.00 0.19
March 0.493911E+09 0.00 0.00 4568546.03 0.00 0.00 0.741435E+09 0.00 0.21
April 0.246177E+09 265521.14 0.00 7226600.90 0.00 0.00 0.486375E+09 0.00 0.19
May 0.255572E+09 0.00 0.00 8473240.21 0.00 0.00 0.526358E+09 0.00 0.20
June 0.188286E+09 24545082.39 0.00 8044456.99 253405.46 0.00 0.285968E+09 0.00 0.21
July 89503730.72 0.143171E+09 0.00 6298590.15 4176328.42 0.00 0.110889E+09 0.00 0.18
August 0.100492E+09 0.176885E+09 0.00 5688983.88 2310297.89 0.00 0.103973E+09 0.00 0.21
September 0.166174E+09 36303114.67 0.00 7924435.46 8367.28 0.00 0.183617E+09 0.00 0.19
October 0.204737E+09 56544612.74 0.00 8949609.76 955077.86 0.00 0.308365E+09 0.00 0.19
November 0.315299E+09 0.00 0.00 7258610.72 0.00 0.00 0.674143E+09 0.00 0.20
December 0.358833E+09 0.00 0.00 5609872.91 0.00 0.00 0.678213E+09 0.00 0.18
                   
Annual Sum or Average 0.332463E+10 0.437714E+09 0.00 79013583.58 7703476.91 1801499.04 0.525792E+10 0.00 0.19
Minimum of Months 89503730.72 0.00 0.00 4372153.24 0.00 0.00 0.103973E+09 0.00 0.18
Maximum of Months 0.526513E+09 0.176885E+09 0.00 8949609.76 4176328.42 1801499.04 0.741435E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.242867E+09 588883.47 0.00 5989938.11 0.00 29926007.07 0.238634E+09 0.00 0.19
February 0.260860E+09 398483.22 0.00 3490922.23 0.00 15929823.00 0.207248E+09 0.00 0.19
March 0.392335E+09 1352905.66 0.00 2024939.36 0.00 52350412.63 0.164067E+09 0.00 0.21
April 0.220793E+09 1859614.12 0.00 2473499.89 0.00 2711875.13 0.156043E+09 0.00 0.19
May 0.226491E+09 715458.90 0.00 2364633.36 0.00 1925130.28 0.185069E+09 0.00 0.20
June 0.136237E+09 18032539.49 0.00 2665962.53 48178.38 0.00 0.134108E+09 0.00 0.21
July 79090361.18 99898166.77 0.00 2489108.72 1197893.47 0.00 43395597.08 0.00 0.18
August 89657365.47 0.136366E+09 0.00 2225864.85 390500.42 0.00 40621262.50 0.00 0.21
September 0.106221E+09 51567995.59 0.00 3747337.44 376543.26 0.00 89601121.57 0.00 0.19
October 0.126728E+09 70083923.49 0.00 5417919.11 154412.08 0.00 0.101792E+09 0.00 0.19
November 0.200763E+09 2318.16 0.00 7626330.36 0.00 0.00 0.267425E+09 0.00 0.20
December 0.219875E+09 87581.95 0.00 6961598.98 0.00 7713849.66 0.237392E+09 0.00 0.18
                   
Annual Sum or Average 0.230192E+10 0.380954E+09 0.00 47478054.95 2167527.60 0.110557E+09 0.186540E+10 0.00 0.19
Minimum of Months 79090361.18 2318.16 0.00 2024939.36 0.00 0.00 40621262.50 0.00 0.18
Maximum of Months 0.392335E+09 0.136366E+09 0.00 7626330.36 1197893.47 52350412.63 0.267425E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186592E+09 446553.46 0.00 1192163.86 0.00 10784476.42 0.115107E+09 0.00 0.19
February 0.172374E+09 214792.98 0.00 966702.82 0.00 2280650.69 0.123468E+09 0.00 0.19
March 0.262875E+09 1580143.95 0.00 918390.78 0.00 4105318.44 0.109471E+09 0.00 0.21
April 92143272.36 4038703.73 0.00 2768802.71 4550.18 0.00 0.123129E+09 0.00 0.19
May 95221808.89 1921573.56 0.00 3222745.53 0.00 0.00 0.139915E+09 0.00 0.20
June 64675304.16 32706731.18 0.00 2577374.44 369150.32 0.00 72113518.29 0.00 0.21
July 39149261.21 0.113296E+09 0.00 1682913.77 3385539.52 0.00 17321498.60 0.00 0.18
August 43944272.65 0.144438E+09 0.00 1690425.18 2535630.02 0.00 18545968.15 0.00 0.21
September 56644460.34 45534445.92 0.00 2501927.56 263281.88 0.00 48217986.02 0.00 0.19
October 69344816.42 53376454.76 0.00 2601265.25 1020605.62 0.00 70118145.11 0.00 0.19
November 0.111416E+09 40154.52 0.00 2162226.20 0.00 0.00 0.182242E+09 0.00 0.20
December 0.163989E+09 376434.87 0.00 1337109.06 0.00 70155.93 0.120279E+09 0.00 0.18
                   
Annual Sum or Average 0.135837E+10 0.397970E+09 0.00 23622047.16 7578757.53 17240601.47 0.113993E+10 0.00 0.19
Minimum of Months 39149261.21 40154.52 0.00 918390.78 0.00 0.00 17321498.60 0.00 0.18
Maximum of Months 0.262875E+09 0.144438E+09 0.00 3222745.53 3385539.52 10784476.42 0.182242E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.379778E+09 55955.24 0.00 804398.05 0.00 66347222.79 0.101468E+09 0.00 0.19
February 0.422365E+09 87167.61 0.00 393649.02 0.00 9398453.29 0.102180E+09 0.00 0.19
March 0.550524E+09 0.00 0.00 491918.65 0.00 31872622.33 93387004.68 0.00 0.21
April 0.218148E+09 911042.76 0.00 2085041.31 0.00 44767.50 0.209455E+09 0.00 0.19
May 0.183635E+09 501619.68 0.00 3321021.33 0.00 0.00 0.268427E+09 0.00 0.20
June 0.112000E+09 27814982.31 0.00 3530111.32 477832.02 0.00 0.156678E+09 0.00 0.21
July 72702785.72 0.132186E+09 0.00 2745782.37 4883945.53 0.00 36088539.57 0.00 0.18
August 78759893.25 0.161420E+09 0.00 2277181.87 3328867.76 0.00 38792835.23 0.00 0.21
September 97890085.69 42970523.14 0.00 3258057.70 309375.51 0.00 0.110210E+09 0.00 0.19
October 0.134799E+09 67322638.99 0.00 2865689.24 1501068.36 0.00 0.123034E+09 0.00 0.19
November 0.291990E+09 0.00 0.00 1678146.63 0.00 240176.30 0.251975E+09 0.00 0.20
December 0.381611E+09 1257.81 0.00 765405.12 0.00 5727287.45 0.117739E+09 0.00 0.18
                   
Annual Sum or Average 0.292420E+10 0.433271E+09 0.00 24216402.60 10501089.19 0.113631E+09 0.160943E+10 0.00 0.19
Minimum of Months 72702785.72 0.00 0.00 393649.02 0.00 0.00 36088539.57 0.00 0.18
Maximum of Months 0.550524E+09 0.161420E+09 0.00 3530111.32 4883945.53 66347222.79 0.268427E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.191922E+09 41919.07 0.00 1328986.09 0.00 22426728.13 0.115862E+09 0.00 0.19
February 0.193033E+09 73622.32 0.00 1102100.44 0.00 645134.49 0.122090E+09 0.00 0.19
March 0.272413E+09 409514.63 0.00 1109215.90 0.00 10057824.46 0.115206E+09 0.00 0.21
April 0.105985E+09 1583194.41 0.00 2511766.36 17667.93 0.00 0.128408E+09 0.00 0.19
May 96836137.21 552128.78 0.00 3140813.22 0.00 0.00 0.157060E+09 0.00 0.20
June 65625430.94 23834108.94 0.00 2589598.42 469656.33 0.00 80667385.54 0.00 0.21
July 41106180.34 95587337.51 0.00 1693743.88 3672419.66 0.00 17897105.80 0.00 0.18
August 45522239.41 0.120674E+09 0.00 1496875.56 3064495.26 0.00 18807395.32 0.00 0.21
September 56475535.49 36431030.07 0.00 2472363.74 311026.33 0.00 50473649.79 0.00 0.19
October 75342023.33 45716023.08 0.00 2406254.08 1065814.33 0.00 74094191.13 0.00 0.19
November 0.130001E+09 0.00 0.00 2390497.45 0.00 0.00 0.179942E+09 0.00 0.20
December 0.177865E+09 3353.93 0.00 1537021.83 0.00 231568.37 0.125278E+09 0.00 0.18
                   
Annual Sum or Average 0.145213E+10 0.324907E+09 0.00 23779236.97 8601079.83 33361255.45 0.118578E+10 0.00 0.19
Minimum of Months 41106180.34 0.00 0.00 1102100.44 0.00 0.00 17897105.80 0.00 0.18
Maximum of Months 0.272413E+09 0.120674E+09 0.00 3140813.22 3672419.66 22426728.13 0.179942E+09 0.00 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:29:53

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.577373E+11 0.171609E+10 0.00 0.932700E+10 0.364608E+198
February 0.721109E+11 0.235024E+10 0.00 0.823379E+10 0.320888E+198
March 0.103204E+12 0.361988E+10 0.00 0.932022E+10 0.381962E+198
April 0.144583E+12 0.443744E+10 0.00 0.700386E+10 0.420670E+198
May 0.152709E+12 0.488553E+10 0.00 0.721120E+10 0.417491E+198
June 0.154290E+12 0.496887E+10 0.00 0.503408E+10 0.388918E+198
July 0.167957E+12 0.489315E+10 0.00 0.338495E+10 0.419474E+198
August 0.153163E+12 0.424311E+10 0.00 0.265885E+10 0.415247E+198
September 0.116181E+12 0.310662E+10 0.00 0.441282E+10 0.385926E+198
October 0.788679E+11 0.223026E+10 0.00 0.528432E+10 0.381924E+198
November 0.643038E+11 0.187067E+10 0.00 0.870604E+10 0.351107E+198
December 0.515615E+11 0.142001E+10 0.00 0.991935E+10 0.359971E+198
           
Annual Sum or Average 0.131667E+13 0.397419E+11 0.00 0.804965E+11 0.460819E+199
Minimum of Months 0.515615E+11 0.142001E+10 0.00 0.265885E+10 0.320888E+198
Maximum of Months 0.167957E+12 0.496887E+10 0.00 0.991935E+10 0.420670E+198