Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000

Simulation Timestamp: 2023-10-16 08:29:12


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 214.52 419.67 419.67
Net Site Energy 214.52 419.67 419.67
Total Source Energy 679.38 1329.10 1329.10
Net Source Energy 679.38 1329.10 1329.10


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 69.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 34.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 21.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 214.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31


End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 69.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 34.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 21.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 22.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 69.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 34.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 13.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 21.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 22.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 221.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 419.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 94.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 221.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 419.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 214.519 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 214.519 100.00
     
Total On-Site and Utility Electric Sources 214.519 100.00
Total Electricity End Uses 214.519 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1208.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 2233.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
RunPeriod RUNPERIOD 1
Weather File Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Latitude [deg] 10.82
Longitude [deg] 106.67
Elevation [m] 5.00
Time Zone 7.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 7.7125 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 7.7125 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 7.7125 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 7.7125 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 7.7125 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 7.7125 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 7.7125 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 7.7125 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 7.7125 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 7.7125 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             7.7125 9.29 6.7800  
Conditioned Total 511.16             7.7125 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 7.7125 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 12-JUN-15:20 - - - - - - - - - - - 02-JAN-12:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8518.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2288.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1822.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2715.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 18811.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8518.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2288.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1822.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2715.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 219.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 109.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 43.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 167.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 69.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 70.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 679.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 429.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 215.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 135.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 137.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1329.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 429.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 215.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 84.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 135.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 137.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1329.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.311974
PERIMETER_ZN_1 DIRECT AIR 0.360663
PERIMETER_ZN_2 DIRECT AIR 0.269683
PERIMETER_ZN_3 DIRECT AIR 0.359710
PERIMETER_ZN_4 DIRECT AIR 0.325293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.311974 0.311974 0.311974 0.311974 0.311974 0.311974 1.00 1.00 0.311974
PSZ-AC:2 0.360663 0.360663 0.360663 0.360663 0.360663 0.360663 1.00 1.00 0.360663
PSZ-AC:3 0.269683 0.269683 0.269683 0.269683 0.269683 0.269683 1.00 1.00 0.269683
PSZ-AC:4 0.359710 0.359710 0.359710 0.359710 0.359710 0.359710 1.00 1.00 0.359710
PSZ-AC:5 0.325293 0.325293 0.325293 0.325293 0.325293 0.325293 1.00 1.00 0.325293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.311974 0.064622
PSZ-AC:2_OA_CONTROLLER 0.360663 0.048988
PSZ-AC:3_OA_CONTROLLER 0.269683 0.029060
PSZ-AC:4_OA_CONTROLLER 0.359710 0.048988
PSZ-AC:5_OA_CONTROLLER 0.325293 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.311974 7342.67 0.717581
PSZ-AC:2 HP COOLING COIL 0.360663 7773.74 0.748360
PSZ-AC:3 HP COOLING COIL 0.269683 5317.02 0.781686
PSZ-AC:4 HP COOLING COIL 0.359710 7758.48 0.748168
PSZ-AC:5 HP COOLING COIL 0.325293 6313.99 0.788547
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.311974 0.311974 0.311974 0.311974 7342.67 7342.67 40.00 1555.32 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.360663 0.360663 0.360663 0.360663 7773.74 7773.74 40.00 1179.03 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.269683 0.269683 0.269683 0.269683 5317.02 5317.02 40.00 699.42 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.359710 0.359710 0.359710 0.359710 7758.48 7758.48 40.00 1179.03 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.325293 0.325293 0.325293 0.325293 6313.99 6313.99 40.00 699.42 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.311974
PSZ-AC:2 FAN 0.360663
PSZ-AC:3 FAN 0.269683
PSZ-AC:4 FAN 0.359710
PSZ-AC:5 FAN 0.325293
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.311974 7342.67
PSZ-AC:2 HEATING COIL 0.360663 7773.74
PSZ-AC:3 HEATING COIL 0.269683 5317.02
PSZ-AC:4 HEATING COIL 0.359710 7758.48
PSZ-AC:5 HEATING COIL 0.325293 6313.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 1555.32
PSZ-AC:2_SUPPHEATCOIL 1179.03
PSZ-AC:3_SUPPHEATCOIL 699.42
PSZ-AC:4_SUPPHEATCOIL 1179.03
PSZ-AC:5_SUPPHEATCOIL 699.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.90 26.70 26.00 26.40 27.50 28.30 29.20 29.00 28.90 27.20 27.50 27.60


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 10.82 106.67 7.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 27.60 3.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 7.713 6.780 0.000 0.000 0.000 0.000 14.493 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1154.233 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1154.233
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 874.984 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.984
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 519.052 7.713 143.303 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 519.052


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.983 0.4683


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 7.7095E-004
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 8.8451E-004
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 7.7097E-004
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 8.7006E-004
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 6.3594E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 7.0890E-004
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.9490E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.4114E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.9007E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.2631E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.6696E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.1271E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.1703E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 3.2406E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.3709E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.8142E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.4801E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 3.6580E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.1956E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 3.4821E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 3.9226E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.8183E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.8006E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6773E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 7.6246E-004
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 8.5941E-004
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 7.6320E-004
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 8.4621E-004
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 6.2942E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 6.9089E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.9164E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.3398E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.2063E-004
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.3201E-004
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.2844E-004
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.3786E-004
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 6.0321E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 6.0968E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.6914E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.7405E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.1751E-004
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.1977E-004
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.2589E-004
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.2774E-004
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 6.0148E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 6.0271E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.6767E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.6863E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.1904E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.4139E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.1697E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.3693E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 9.6762E-004
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.1112E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.2630E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.0214E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.2170E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.0075E-004
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.3989E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.9910E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 5.7564E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.0156E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.1908E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.6168E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.9140E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.3126E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.3457E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.8831E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 1.8369E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.4247E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0319E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9280E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.8981E-003
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.2105E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.5868E-003
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.8435E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.1557E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.5171E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.6144E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.0693E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 7.6542E-004
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 9.0093E-004
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.8943E-004
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 8.1257E-004
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.1630E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 7.0210E-004
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.2223E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.6881E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.8304E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.5574E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.1620E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.7220E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.4875E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 2.7879E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.9068E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.3116E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.4047E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.8916E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 1.9094E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.4684E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 1.5096E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 9.2213E-004
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.5564E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6125E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.3009E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.1713E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.6318E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.6881E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.1901E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.0854E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7002E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8862E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9385E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.7909E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.2522E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.9136E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.5614E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 2.9359E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9723E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.4551E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.4847E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.5968E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.8884E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.9767E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.3092E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.3613E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.6983E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.7529E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.4508E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.4737E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.8612E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.8793E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.2917E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.3025E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6816E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.6920E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.0577E-004
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.4954E-004
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.3574E-004
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.6843E-004
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.5626E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.4613E-004
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.2325E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.6949E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.4033E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.4048E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.1784E-003
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.0683E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.5122E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.6757E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.5992E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.0426E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.9641E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.3368E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.4104E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9271E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 1.9471E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.5101E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.0289E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9056E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.5720E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.3514E-004
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.8078E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.3954E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1291E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.3997E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1999E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.6233E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3541.61891 4249.94269 0.25998 0.31197 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 34.86000 1.71575E-002 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 104.41106 125.29327 4.50359E-003 6.46221E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20.10000 1.47983E-002 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4094.17871 4913.01446 0.30055 0.36066 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 34.94500 1.71577E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 179.57040 215.48448 7.74561E-003 4.89877E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20.10000 1.47983E-002 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3061.48359 3673.78031 0.22474 0.26968 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 32.18250 1.71524E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 97.49659 116.99591 4.20543E-003 2.90601E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20.10000 1.47983E-002 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 4083.36469 4900.03763 0.29976 0.35971 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 34.94500 1.71577E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 164.07336 196.88804 7.07715E-003 4.89877E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20.10000 1.47983E-002 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3692.76400 4431.31680 0.27108 0.32529 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 17:00:00 34.01000 1.71559E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 97.49659 116.99591 4.20543E-003 2.90601E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 20.10000 1.47983E-002 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 5041.64 0.31197 0.31197 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
2 PSZ-AC:1 Heating Sensible 1555.32 6.46221E-002 6.46221E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 5492.09 0.36066 0.36066 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
4 PSZ-AC:2 Heating Sensible 1179.03 4.89877E-002 4.89877E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
5 PSZ-AC:3 Cooling Sensible 3908.45 0.26968 0.26968 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
6 PSZ-AC:3 Heating Sensible 699.42 2.90601E-002 2.90601E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
7 PSZ-AC:4 Cooling Sensible 5479.31 0.35971 0.35971 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
8 PSZ-AC:4 Heating Sensible 1179.03 4.89877E-002 4.89877E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 PSZ-AC:5 Cooling Sensible 4718.50 0.32529 0.32529 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 05:00:00
10 PSZ-AC:5 Heating Sensible 699.42 2.90601E-002 2.90601E-002 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.31197
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.36066
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.26968
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.35971
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.32529
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.31197
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.31197
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.31197
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.31197
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.31197
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.31197
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.36066
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.36066
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.36066
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.36066
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.36066
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.36066
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.26968
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.26968
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.26968
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.26968
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.26968
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.26968
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.35971
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.35971
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.35971
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.35971
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.35971
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.35971
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.32529
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.32529
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.32529
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.32529
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.32529
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.32529
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.31197
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.36066
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.26968
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.35971
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.32529
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.31197
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.31197
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7342.66875
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.71758
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.31197
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.31197
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.31197
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.31197
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7342.66875
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7342.66875
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 1555.31811
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.31197
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.31197
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7342.66875
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 1555.31811
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.36066
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.36066
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7773.74002
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.74836
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.36066
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.36066
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.36066
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.36066
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7773.74002
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7773.74002
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 1179.03184
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.36066
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.36066
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7773.74002
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 1179.03184
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.26968
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26968
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5317.01939
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.78169
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.26968
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.26968
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.26968
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.26968
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5317.01939
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5317.01939
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 699.41686
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.26968
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.26968
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5317.01939
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 699.41686
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.35971
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.35971
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7758.47887
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.74817
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.35971
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.35971
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.35971
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.35971
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7758.47887
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7758.47887
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 1179.03184
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.35971
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.35971
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7758.47887
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 1179.03184
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.32529
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.32529
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6313.99157
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.78855
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.32529
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.32529
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.32529
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.32529
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6313.99157
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6313.99157
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 699.41686
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.32529
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.32529
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6313.99157
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 699.41686
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 7096.8 3.50 11.96 12.55 11.87 12.07
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 7490.0 3.46 11.79 12.36 11.69 11.81
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 5105.1 3.40 11.61 12.16 11.51 11.53
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 7475.4 3.46 11.79 12.36 11.70 11.81
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 6058.5 3.39 11.58 12.13 11.47 11.48


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 7592.8 4183.7 7.50 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 8062.1 4452.8 7.44 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5532.0 3063.3 7.41 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 8046.0 4443.8 7.48 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 6573.2 3641.6 7.43 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 0.2306835977 0.1847998140 Pass Pass 0.3544422793 1.3780533892 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 8.1759047354E-002 0.1373177781 Pass Pass 0.3165127262 1.0810684870 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 7.5772321102E-002 0.1251637910 Pass Pass 0.4566467140 1.3470308440 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 6.9507788571E-002 0.1189260462 Pass Pass 0.5694664119 1.8217205622 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 6.7530144561E-002 0.1183514655 Pass Pass 0.3865935855 1.2527702252 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2375877884 0.2395804402 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1301.03 11.56 0.00 -110.9 380.17 1581.89



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 20.10 0.00 20.10 Wetbulb [C] 1.80 0.00
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 35.20 8.50 25.80 Wetbulb [C] 4.10 160.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 57.00 12      
Feb 0.00 0      
Mar 153.60 31      
Apr 87.00 59      
May 227.22 128      
Jun 144.58 109      
Jul 42.40 24      
Aug 164.90 163      
Sep 119.60 50      
Oct 365.70 188      
Nov 70.90 67      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.5047_SHGC_SOUTH_0.25   3.91 0.00 0.00 3.91 3.91 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.869 0.251 0.251                      
North Total or Average             16.72 2.869 0.251 0.251                      
Non-North Total or Average             42.93 2.869 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.07 0.00 0.00 0.00 0.00 0.00 0.98 0.82 0.95
PERIMETER_ZN_1_WALL_SOUTH_DOOR 0.27 0.18 0.23 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.42 0.00 0.25 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.95 0.00 0.00 0.93 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.95 0.00 0.00 0.93 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.95 0.00 0.00 0.93 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.95 0.00 0.00 0.93 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 7.7125 149.66 1154.23 LightsWired LTG_SCH_OFFICE 52.79 168.00 51.86 0.0000 Y 11.24
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 44.17 0.0000 Y 7.25
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 45.18 0.0000 Y 4.40
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 7.7125 113.45 874.98 LightsWired LTG_SCH_OFFICE 52.79 168.00 45.19 0.0000 Y 7.42
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 7.7125 67.30 519.05 LightsWired LTG_SCH_OFFICE 52.79 168.00 45.09 0.0000 Y 4.39
Interior Lighting Total       7.7125 511.16 3942.30               34.71


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 874.98 209.91
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 874.98 0.00
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 519.05 124.52
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 519.05 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.73 AstronomicalClock -   41.93 41.93 0.53
EXTERIOR_LIGHTS_B 982.38 AstronomicalClock -   83.83 71.26 13.14
Exterior Lighting Total 1049.11           13.67



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7342.67 5268.96 2073.71 0.72 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7773.74 5817.56 1956.18 0.75 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5317.02 4156.24 1160.78 0.78 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7758.48 5804.65 1953.83 0.75 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6313.99 4978.88 1335.11 0.79 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   7096.8 3.50 11.96 12.55 11.87 12.07
PSZ-AC:2 HP COOLING COIL   7490.0 3.46 11.79 12.36 11.69 11.81
PSZ-AC:3 HP COOLING COIL   5105.1 3.40 11.61 12.16 11.51 11.53
PSZ-AC:4 HP COOLING COIL   7475.4 3.46 11.79 12.36 11.70 11.81
PSZ-AC:5 HP COOLING COIL   6058.5 3.39 11.58 12.13 11.47 11.48
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 7592.8 4183.7 7.50 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 8062.1 4452.8 7.44 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5532.0 3063.3 7.41 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 8046.0 4443.8 7.48 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 6573.2 3641.6 7.43 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   7342.67 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   1555.32 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   7773.74 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   1179.03 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   5317.02 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   699.42 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   7758.48 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   1179.03 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   6313.99 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   699.42 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.31 349.44 1120.11 1.00 1.87 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.36 403.98 1120.11 1.00 1.78 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.27 302.07 1120.11 1.00 1.98 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.36 402.91 1120.11 1.00 1.78 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 04:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.33 364.36 1120.11 1.00 1.84 General HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.47



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3541.62 4249.94 28.40 0.260 0.312 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 23.89 23.89 0.00901 34.86 0.01716 0.065 0.00
PERIMETER_ZN_1 4094.18 4913.01 43.31 0.301 0.361 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 23.89 23.89 0.00910 34.95 0.01716 0.049 0.00
PERIMETER_ZN_2 3061.48 3673.78 54.59 0.225 0.270 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 23.89 23.89 0.00900 32.18 0.01715 0.029 0.00
PERIMETER_ZN_3 4083.36 4900.04 43.19 0.300 0.360 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 23.89 23.89 0.00910 34.95 0.01716 0.049 0.00
PERIMETER_ZN_4 3692.76 4431.32 65.84 0.271 0.325 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 17:00:00 23.89 23.89 0.00892 34.01 0.01716 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 104.41 125.29 0.84 0.005 0.065 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00879 20.10 0.01480 0.065 0.00
PERIMETER_ZN_1 179.57 215.48 1.90 0.008 0.049 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.01053 20.10 0.01480 0.049 0.00
PERIMETER_ZN_2 97.50 117.00 1.74 0.004 0.029 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.01086 20.10 0.01480 0.029 0.00
PERIMETER_ZN_3 164.07 196.89 1.74 0.007 0.049 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.01067 20.10 0.01480 0.049 0.00
PERIMETER_ZN_4 97.50 117.00 1.74 0.004 0.029 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.01086 20.10 0.01480 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.31 0.31 0.06 0.06 0.3120 0.3120 0.3120 1.0000 1.0000
PSZ-AC:2 0.36 0.36 0.05 0.05 0.3607 0.3607 0.3607 1.0000 1.0000
PSZ-AC:3 0.27 0.27 0.03 0.03 0.2697 0.2697 0.2697 1.0000 1.0000
PSZ-AC:4 0.36 0.36 0.05 0.05 0.3597 0.3597 0.3597 1.0000 1.0000
PSZ-AC:5 0.33 0.33 0.03 0.03 0.3253 0.3253 0.3253 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 7342.669 5268.961 0.311974 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 7302.78 5392.12 0.311974 27.07 19.20 0.01069421 12.80 12.09 0.00850000 34.86 0.01715750 25.74 20.7139 23.89 0.00900720 48.7473 3535.24 0.00 7341.41 5264.53
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 7342.669 7342.669 0.311974 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 7342.67 7312.92 0.311974 20.90 16.60 0.01003314 40.00 21.18 0.00800000 20.10 0.01479830 20.10 20.7139 21.11 0.00980781 62.7666 102.94 0.00 7352.32 7352.32
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 1555.318 1555.318 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 1555.32 1555.32 0.311974 20.90 16.60 0.01003314 40.00 21.18 0.00800000 20.10 0.01479830 20.10 20.7139 21.11 0.00980781 62.7666 102.94 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7773.740 5817.559 0.360663 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 7600.36 5904.57 0.360663 26.30 18.56 0.01019087 12.80 12.09 0.00850000 34.95 0.01715766 25.76 13.5827 23.89 0.00909626 49.2235 4090.85 0.00 7772.41 5812.08
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7773.740 7773.740 0.360663 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 7773.74 7773.74 0.360663 20.97 17.52 0.01110740 40.00 21.18 0.00800000 20.10 0.01479830 20.10 13.5827 21.11 0.01055763 67.4838 179.17 0.00 7783.96 7783.96
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 1179.032 1179.032 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 1179.03 1179.03 0.360663 20.97 17.52 0.01110740 40.00 21.18 0.00800000 20.10 0.01479830 20.10 13.5827 21.11 0.01055763 67.4838 179.17 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5317.019 4156.242 0.269683 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 5254.47 4220.84 0.269683 25.69 18.12 0.00988286 12.80 12.09 0.00850000 32.18 0.01715240 25.07 10.7757 23.89 0.00900492 48.7358 3061.48 0.00 5316.11 4151.58
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5317.019 5317.019 0.269683 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 5317.02 5317.02 0.269683 21.00 17.67 0.01128497 40.00 21.18 0.00800000 20.10 0.01479830 20.10 10.7757 21.11 0.01089149 69.5811 97.29 0.00 5324.01 5324.01
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 699.417 699.417 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 699.42 699.42 0.269683 21.00 17.67 0.01128497 40.00 21.18 0.00800000 20.10 0.01479830 20.10 10.7757 21.11 0.01089149 69.5811 97.29 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7758.479 5804.649 0.359710 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 7586.35 5890.75 0.359710 26.30 18.57 0.01019510 12.80 12.09 0.00850000 34.95 0.01715766 25.76 13.6186 23.89 0.00909773 49.2313 4080.51 0.00 7757.15 5799.02
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7758.479 7758.479 0.359710 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 04:00:00 7758.48 7758.48 0.359710 20.97 17.62 0.01123523 40.00 21.18 0.00800000 20.10 0.01479830 20.10 13.6186 21.11 0.01070918 68.4362 163.66 0.00 7768.67 7768.67
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 1179.032 1179.032 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 04:00:00 1179.03 1179.03 0.359710 20.97 17.62 0.01123523 40.00 21.18 0.00800000 20.10 0.01479830 20.10 13.6186 21.11 0.01070918 68.4362 163.66 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6313.992 4978.877 0.325293 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:50:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 17:00:00 6123.08 5084.58 0.325293 25.70 17.93 0.00965424 12.80 12.09 0.00850000 34.01 0.01715587 25.53 8.9335 23.89 0.00891750 48.2689 3691.98 0.00 6312.91 4973.99
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6313.992 6313.992 0.325293 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6313.99 6313.99 0.325293 21.02 17.62 0.01121243 40.00 21.18 0.00800000 20.10 0.01479830 20.10 8.9335 21.11 0.01089149 69.5811 97.29 0.00 6322.29 6322.29
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 699.417 699.417 -999.0 -999.0 -999.000 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 699.42 699.42 0.325293 21.02 17.62 0.01121243 40.00 21.18 0.00800000 20.10 0.01479830 20.10 8.9335 21.11 0.01089149 69.5811 97.29 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7342.669 5268.961 0.311974 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.7200 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.311974 0.37549076   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:00:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:40:00 Sensible 7302.78 5392.12 0.9946 0.37549076 0.311974 27.07 19.20 0.01069421 54484.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 349.445 6953.33 34.86 0.01715750 25.74 0.06462207 20.7139 23.89 0.00900564 23.89 0.00900720 48.7473 3535.24 0.00 7341.41 5264.53 0.36066172 26.67 19.44 0.01118466 55322.4 12.38 12.35 0.00892688 34967.0
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7342.669 7342.669 0.311974 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.311974 0.37549076   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 7342.67 7312.92 1.0000 0.37549076 0.311974 20.90 16.60 0.01003314 46484.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7342.67 20.10 0.01479830 20.10 0.06462207 20.7139 21.11 0.00878822 21.11 0.00980781 62.7666 102.94 0.00 7352.32 7352.32 0.36885572 21.11 15.56 0.00875166 43444.1 40.63 21.90 0.00875166 63376.9
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1555.318 1555.318 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.311974 0.37549076   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 1555.32 1555.32 1.0000 0.37549076 0.311974 20.90 16.60 0.01003314 46484.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1555.32 20.10 0.01479830 20.10 0.06462207 20.7139 21.11 0.00878822 21.11 0.00980781 62.7666 102.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7773.740 5817.559 0.360663 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7843 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.360663 0.43409232   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 Sensible 7600.36 5904.57 0.9777 0.43409232 0.360663 26.30 18.56 0.01019087 52412.0 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 403.982 7196.38 34.95 0.01715766 25.76 0.04898771 13.5827 23.89 0.00909587 23.89 0.00909626 49.2235 4090.85 0.00 7772.41 5812.08 0.41694895 26.67 19.44 0.01118466 55322.4 13.03 13.02 0.00934127 36681.2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7773.740 7773.740 0.360663 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.360663 0.43409232   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 7773.74 7773.74 1.0000 0.43409232 0.360663 20.97 17.52 0.01110740 49286.7 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7773.74 20.10 0.01479830 20.10 0.04898771 13.5827 21.11 0.01052729 21.11 0.01055763 67.4838 179.17 0.00 7783.96 7783.96 0.42642177 21.11 15.56 0.00875166 43444.1 38.99 21.42 0.00875166 61698.2
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1179.032 1179.032 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.360663 0.43409232   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 1179.03 1179.03 1.0000 0.43409232 0.360663 20.97 17.52 0.01110740 49286.7 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1179.03 20.10 0.01479830 20.10 0.04898771 13.5827 21.11 0.01052729 21.11 0.01055763 67.4838 179.17 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5317.019 4156.242 0.269683 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2118 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.269683 0.32458932   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 10:10:00 Sensible 5254.47 4220.84 0.9882 0.32458932 0.269683 25.69 18.12 0.00988286 51005.3 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 302.074 4952.40 32.18 0.01715240 25.07 0.02906014 10.7757 23.89 0.00900492 23.89 0.00900492 48.7358 3061.48 0.00 5316.11 4151.58 0.31177050 26.67 19.44 0.01118466 55322.4 13.65 13.63 0.00972017 38271.0
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5317.019 5317.019 0.269683 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.269683 0.32458932   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 5317.02 5317.02 1.0000 0.32458932 0.269683 21.00 17.67 0.01128497 49766.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5317.02 20.10 0.01479830 20.10 0.02906014 10.7757 21.11 0.01086066 21.11 0.01089149 69.5811 97.29 0.00 5324.01 5324.01 0.31885373 21.11 15.56 0.00875166 43444.1 37.46 20.97 0.00875166 60141.4
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 699.417 699.417 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.269683 0.32458932   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 699.42 699.42 1.0000 0.32458932 0.269683 21.00 17.67 0.01128497 49766.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 699.42 20.10 0.01479830 20.10 0.02906014 10.7757 21.11 0.01086066 21.11 0.01089149 69.5811 97.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7758.479 5804.649 0.359710 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7922 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.359710 0.43294574   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:10:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 15:30:00 Sensible 7586.35 5890.75 0.9778 0.43294574 0.359710 26.30 18.57 0.01019510 52426.9 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 402.915 7183.43 34.95 0.01715766 25.76 0.04898771 13.6186 23.89 0.00909740 23.89 0.00909773 49.2313 4080.51 0.00 7757.15 5799.02 0.41584765 26.67 19.44 0.01118466 55322.4 13.02 13.02 0.00933846 36668.6
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7758.479 7758.479 0.359710 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.359710 0.43294574   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 04:00:00 Sensible 7758.48 7758.48 1.0000 0.43294574 0.359710 20.97 17.62 0.01123523 49611.0 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7758.48 20.10 0.01479830 20.10 0.04898771 13.6186 21.11 0.01067348 21.11 0.01070918 68.4362 163.66 0.00 7768.67 7768.67 0.42529545 21.11 15.56 0.00875166 43444.1 39.00 21.43 0.00875166 61710.6
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1179.032 1179.032 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.359710 0.43294574   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 04:00:00 Sensible 1179.03 1179.03 1.0000 0.43294574 0.359710 20.97 17.62 0.01123523 49611.0 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1179.03 20.10 0.01479830 20.10 0.04898771 13.6186 21.11 0.01067348 21.11 0.01070918 68.4362 163.66 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6313.992 4978.877 0.325293 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.7868 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.325293 0.39152058   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:50:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 16:50:00 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB 4/21 17:00:00 Sensible 6123.08 5084.58 0.9698 0.39152058 0.325293 25.70 17.93 0.00965424 50433.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 364.363 5758.72 34.01 0.01715587 25.53 0.02906014 8.9335 23.89 0.00891834 23.89 0.00891750 48.2689 3691.98 0.00 6312.91 4973.99 0.37605848 26.67 19.44 0.01118466 55322.4 13.74 13.73 0.00978871 38535.3
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6313.992 6313.992 0.325293 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.325293 0.39152058   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6313.99 6313.99 1.0000 0.39152058 0.325293 21.02 17.62 0.01121243 49601.7 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6313.99 20.10 0.01479830 20.10 0.02906014 8.9335 21.11 0.01086066 21.11 0.01089149 69.5811 97.29 0.00 6322.29 6322.29 0.38460229 21.11 15.56 0.00875166 43444.1 37.21 20.90 0.00875166 59882.6
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 699.417 699.417 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.325293 0.39152058   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 699.42 699.42 1.0000 0.39152058 0.325293 21.02 17.62 0.01121243 49601.7 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 699.42 20.10 0.01479830 20.10 0.02906014 8.9335 21.11 0.01086066 21.11 0.01089149 69.5811 97.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 4284.00 1675.00 1675.00
PERIMETER_ZN_1 4284.00 2215.33 2215.33
PERIMETER_ZN_2 3528.00 1671.00 1671.00
PERIMETER_ZN_3 4284.00 1613.17 1613.17
PERIMETER_ZN_4 4284.00 1721.33 1721.33
ATTIC 0.00 0.00 0.00
Facility 4284.00 2233.00 2233.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 1022.17 0.00 1020.83
PERIMETER_ZN_1 0.00 849.33 0.00 827.17
PERIMETER_ZN_2 0.00 168.50 0.00 106.67
PERIMETER_ZN_3 0.00 218.33 0.00 211.17
PERIMETER_ZN_4 0.00 60.67 0.00 3.50
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 1322.00 0.00 1208.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.403 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.403 0.377 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.376 0.042 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.402 0.034 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.402 0.038 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 763878.74 0.00 763878.74 0.00 763878.74 2037921.45 5483.94 3276.06 0.00 38.64
PERIMETER_ZN_1 587535.49 0.00 587535.49 620824.72 1208360.21 1544876.42 5481.93 3278.07 0.00 283.14
PERIMETER_ZN_2 349531.27 0.00 349531.27 86561.60 436092.87 916440.58 5482.14 3277.86 0.00 1125.40
PERIMETER_ZN_3 583553.94 0.00 583553.94 129842.40 713396.35 1544876.42 5482.98 3277.03 0.00 171.45
PERIMETER_ZN_4 349871.91 0.00 349871.91 86561.60 436433.51 916440.58 5481.01 3278.99 0.00 405.94
Total Facility 2634371.35 0.00 2634371.35 923790.33 3558161.68 6960555.45 5484.00 3283.18 0.00 1458.41


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0350 0.0724 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0023 0.0230 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0031 0.0406 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0021 0.0243 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0425 0.2098 0.2207 1008.00 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1106585.97 0.00 1106585.97 2037921.45 5483.27 0.04 3276.69 37.20
PSZ-AC:2 851127.93 0.00 851127.93 1544876.42 5476.07 0.47 3283.46 277.88
PSZ-AC:3 506345.29 0.00 506345.29 916440.58 5475.61 0.40 3283.99 1115.40
PSZ-AC:4 845360.10 0.00 845360.10 1544876.42 5479.47 0.24 3280.29 168.27
PSZ-AC:5 506838.75 0.00 506838.75 916440.58 5475.85 0.11 3284.04 391.13


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0716 0.0000 0.0716 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0543 0.0000 0.0543 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0301 0.0000 0.0301 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0543 0.0000 0.0543 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0322 0.0000 0.0322 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3313.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3553.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3635.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3444.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3667.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0936 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0710 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0421 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0710 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0421 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 523
Defaulted Fields 365
Fields with Defaults 1332
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
Electricity:Building 87.51 1137.89 02-APR-11:40 6097.42 18-DEC-17:00
Electricity:Zone:CORE_ZN 26.70 359.76 01-JAN-00:10 1798.81 02-JAN-08:10
Electricity:SpaceType:GENERAL 87.51 1137.89 02-APR-11:40 6097.42 18-DEC-17:00
InteriorLights:Electricity 34.71 444.76 02-APR-11:40 2631.77 18-DEC-17:00
InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 34.71 444.76 02-APR-11:40 2631.77 18-DEC-17:00
LightsWired:InteriorLights:Electricity 34.71 444.76 02-APR-11:40 2631.77 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 11.24 156.83 01-JAN-00:10 784.13 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 34.71 444.76 02-APR-11:40 2631.77 18-DEC-17:00
Electricity:Zone:PERIMETER_ZN_1 18.97 244.20 01-JAN-07:50 1347.10 18-DEC-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.25 90.36 01-JAN-07:50 577.91 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 7.25 90.36 01-JAN-07:50 577.91 18-DEC-17:00
Electricity:Zone:PERIMETER_ZN_2 11.35 144.86 01-JAN-08:30 801.97 18-DEC-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.40 53.60 01-JAN-08:30 345.68 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 4.40 53.60 01-JAN-08:30 345.68 18-DEC-17:00
Electricity:Zone:PERIMETER_ZN_3 19.14 244.20 05-MAR-14:10 1350.85 18-DEC-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.42 90.36 05-MAR-14:10 581.66 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 7.42 90.36 05-MAR-14:10 581.66 18-DEC-17:00
Electricity:Zone:PERIMETER_ZN_4 11.34 144.86 01-JAN-12:10 798.69 18-DEC-17:00
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.39 53.60 01-JAN-12:10 342.39 18-DEC-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 4.39 53.60 01-JAN-12:10 342.39 18-DEC-17:00
InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
ElectricityPurchased:Facility 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
ElectricityPurchased:Plant 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
Cogeneration:ElectricityPurchased 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
General:Cogeneration:ElectricityPurchased 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
ElectricityNet:Plant 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
Cogeneration:ElectricityNet 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
General:Cogeneration:ElectricityNet 214.52 1709.89 29-APR-11:30 18811.29 12-JUN-15:20
ExteriorLights:Electricity 13.67 0.00 01-JAN-06:20 1049.11 01-JAN-06:10
General:ExteriorLights:Electricity 13.67 0.00 01-JAN-06:20 1049.11 01-JAN-06:10
Electricity:HVAC 91.14 0.00 01-JAN-00:10 10363.61 12-JUN-15:00
Fans:Electricity 21.83 0.00 01-JAN-00:10 1822.78 02-JAN-08:10
General:Fans:Electricity 21.83 0.00 01-JAN-00:10 1822.78 02-JAN-08:10
Cooling:Electricity 69.31 0.00 01-JAN-00:10 8540.83 12-JUN-15:00
General:Cooling:Electricity 69.31 0.00 01-JAN-00:10 8540.83 12-JUN-15:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Plant 22.21 572.00 03-MAR-09:50 2747.09 11-JAN-12:40
WaterSystems:Electricity 22.21 572.00 03-MAR-09:50 2747.09 11-JAN-12:40
Water Heater:WaterSystems:Electricity 22.21 572.00 03-MAR-09:50 2747.09 11-JAN-12:40
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 11-MAY-11:20
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 11-MAY-11:20
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 17-JAN-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 17-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 497.33 0.00 01-JAN-00:10 60203.77 21-FEB-08:10
EnergyTransfer:Building 186.47 0.00 01-JAN-00:10 25116.78 21-FEB-10:00
EnergyTransfer:Zone:CORE_ZN 41.34 0.00 01-JAN-00:10 5642.02 21-FEB-10:00
Heating:EnergyTransfer 1.99 0.00 01-JAN-00:10 3188.60 09-MAY-17:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.43 0.00 01-JAN-00:10 870.96 14-JUL-17:10
General:Heating:EnergyTransfer 1.99 0.00 01-JAN-00:10 3188.60 09-MAY-17:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.43 0.00 01-JAN-00:10 870.96 14-JUL-17:10
Cooling:EnergyTransfer 184.47 0.00 01-JAN-00:10 25116.78 21-FEB-10:00
Cooling:EnergyTransfer:Zone:CORE_ZN 40.91 0.00 01-JAN-00:10 5642.02 21-FEB-10:00
General:Cooling:EnergyTransfer 184.47 0.00 01-JAN-00:10 25116.78 21-FEB-10:00
General:Cooling:EnergyTransfer:Zone:CORE_ZN 40.91 0.00 01-JAN-00:10 5642.02 21-FEB-10:00
EnergyTransfer:Zone:PERIMETER_ZN_1 45.72 0.00 01-JAN-00:10 6147.05 21-FEB-10:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.44 0.00 01-JAN-00:10 686.47 14-JUL-17:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.44 0.00 01-JAN-00:10 686.47 14-JUL-17:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 45.28 0.00 01-JAN-00:10 6147.05 21-FEB-10:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 45.28 0.00 01-JAN-00:10 6147.05 21-FEB-10:00
EnergyTransfer:Zone:PERIMETER_ZN_2 28.99 0.00 01-JAN-00:10 4432.31 21-FEB-10:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.32 0.00 01-JAN-00:10 477.34 09-MAY-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.32 0.00 01-JAN-00:10 477.34 09-MAY-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 28.67 0.00 01-JAN-00:10 4432.31 21-FEB-10:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 28.67 0.00 01-JAN-00:10 4432.31 21-FEB-10:00
EnergyTransfer:Zone:PERIMETER_ZN_3 41.51 0.00 01-JAN-00:10 5836.02 21-FEB-09:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.46 0.00 01-JAN-00:10 718.68 09-MAY-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.46 0.00 01-JAN-00:10 718.68 09-MAY-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 41.04 0.00 01-JAN-00:10 5836.02 21-FEB-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 41.04 0.00 01-JAN-00:10 5836.02 21-FEB-09:10
EnergyTransfer:Zone:PERIMETER_ZN_4 28.91 0.00 01-JAN-00:10 4319.64 21-FEB-16:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.34 0.00 01-JAN-00:10 473.30 09-MAY-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.34 0.00 01-JAN-00:10 473.30 09-MAY-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 28.57 0.00 01-JAN-00:10 4319.64 21-FEB-16:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 28.57 0.00 01-JAN-00:10 4319.64 21-FEB-16:10
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
EnergyTransfer:HVAC 310.86 0.00 01-JAN-00:10 38454.89 22-MAY-06:10
CoolingCoils:EnergyTransfer 310.86 0.00 01-JAN-00:10 38454.89 22-MAY-06:10
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 13-JAN-07:10 49.35 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.431 -40.908 0.000 0.000 4.724 11.237 15.459 0.000 0.000 0.000 9.057 0.000 0.000 0.000 0.000 -0.000
PERIMETER_ZN_1 0.000 0.000 0.440 -45.279 0.000 0.000 3.606 7.255 11.719 13.943 0.000 2.789 8.313 0.000 -2.373 0.000 -0.412 -0.000
PERIMETER_ZN_2 0.000 0.000 0.319 -28.667 0.000 0.000 1.588 4.402 6.952 9.311 0.000 0.131 7.342 0.000 -1.227 0.000 -0.150 -0.000
PERIMETER_ZN_3 0.000 0.000 0.464 -41.042 0.000 0.000 3.681 7.423 11.719 8.711 0.000 0.201 10.860 0.000 -1.810 0.000 -0.207 -0.000
PERIMETER_ZN_4 0.000 0.000 0.339 -28.572 0.000 0.000 2.192 4.393 6.952 9.381 0.000 0.128 6.699 0.000 -1.350 0.000 -0.160 -0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.977 36.656 0.000 0.000 0.000 -44.633 -0.000
Total Facility 0.000 0.000 1.993 -184.467 0.000 0.000 15.791 34.709 52.800 41.346 0.000 11.226 78.927 0.000 -6.760 0.000 -45.563 -0.001


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:02 0.00 0.00 0.00 -6080.76 0.00 0.00 36.21 200.39 507.34 0.00 0.00 0.00 5336.83 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 16-JAN-15:32 0.00 0.00 0.00 -6976.15 0.00 0.00 0.00 90.36 153.84 1876.45 0.00 7.79 4847.71 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_2 21-FEB-10:00 0.00 0.00 0.00 -4442.68 0.00 0.00 249.14 268.02 456.29 1019.36 0.00 0.00 2453.80 0.00 -0.00 0.00 -3.94 0.00
PERIMETER_ZN_3 21-FEB-09:06 0.00 0.00 0.00 -5874.86 0.00 0.00 425.60 496.94 769.19 494.18 0.00 4.54 3684.41 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_4 16-JAN-17:12 0.00 0.00 0.00 -5765.62 0.00 0.00 0.00 64.58 91.26 1249.36 0.00 0.00 4374.04 0.00 -0.00 0.00 -13.62 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-FEB-06:02 0.00 0.00 0.00 -27758.08 0.00 0.00 117.83 684.42 1732.82 0.00 0.00 1008.12 25160.02 0.00 -850.43 0.00 -94.71 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 09-MAY-17:01 0.00 0.00 968.22 0.00 0.00 0.00 60.73 365.93 202.94 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -1597.81
PERIMETER_ZN_1 09-MAY-17:11 0.00 0.00 781.48 0.00 0.00 0.00 34.12 258.28 153.84 379.99 0.00 151.00 0.00 0.00 -0.00 0.00 0.00 -1758.71
PERIMETER_ZN_2 09-MAY-17:11 0.00 0.00 555.76 0.00 0.00 0.00 21.76 156.75 91.26 226.76 0.00 7.99 0.00 0.00 -0.00 0.00 0.00 -1060.29
PERIMETER_ZN_3 09-MAY-17:11 0.00 0.00 835.09 0.00 0.00 0.00 36.51 243.16 153.84 607.96 0.00 11.95 0.00 0.00 -0.00 0.00 0.00 -1888.51
PERIMETER_ZN_4 09-MAY-17:11 0.00 0.00 580.33 0.00 0.00 0.00 20.10 141.93 91.26 1030.55 0.00 7.38 0.00 0.00 -0.00 0.00 0.00 -1871.55
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-MAY-17:11 0.00 0.00 3688.88 0.00 0.00 0.00 161.66 1166.05 693.13 2245.26 0.00 178.31 0.00 0.00 0.00 0.00 -2300.57 -5832.72



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3120 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3120 0.2071 1.0000 Not calculated 0.0646 0.2071    
PSZ-AC:2 0.3607 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3607 0.1358 1.0000 Not calculated 0.0490 0.1358    
PSZ-AC:3 0.2697 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2697 0.1078 1.0000 Not calculated 0.0291 0.1078    
PSZ-AC:4 0.3597 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3597 0.1362 1.0000 Not calculated 0.0490 0.1362    
PSZ-AC:5 0.3253 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3253 0.0893 1.0000 Not calculated 0.0291 0.0893    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3120 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3120 1.0000 1.0000 Not calculated 0.0646 0.2071    
PSZ-AC:2 0.3607 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3607 1.0000 1.0000 Not calculated 0.0490 0.1358    
PSZ-AC:3 0.2697 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2697 1.0000 1.0000 Not calculated 0.0291 0.1078    
PSZ-AC:4 0.3597 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3597 1.0000 1.0000 Not calculated 0.0490 0.1362    
PSZ-AC:5 0.3253 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3253 1.0000 1.0000 Not calculated 0.0291 0.0893    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3120 0.3120 0.3120 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3607 0.3607 0.3607 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2697 0.2697 0.2697 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3597 0.3597 0.3597 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3253 0.3253 0.3253 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3120 0.3120 0.3120 0.3120 0.0646 1.0000
PSZ-AC:2 0.3607 0.3607 0.3607 0.3607 0.0490 1.0000
PSZ-AC:3 0.2697 0.2697 0.2697 0.2697 0.0291 1.0000
PSZ-AC:4 0.3597 0.3597 0.3597 0.3597 0.0490 1.0000
PSZ-AC:5 0.3253 0.3253 0.3253 0.3253 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3120 0.3120 0.3120 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3607 0.3607 0.3607 No 0.0490 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2697 0.2697 0.2697 No 0.0291 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3597 0.3597 0.3597 No 0.0490 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3253 0.3253 0.3253 No 0.0291 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3120 0.3120 0.3120 0.3120 0.0646 1.0000
PSZ-AC:2 0.3607 0.3607 0.3607 0.3607 0.0490 1.0000
PSZ-AC:3 0.2697 0.2697 0.2697 0.2697 0.0291 1.0000
PSZ-AC:4 0.3597 0.3597 0.3597 0.3597 0.0490 1.0000
PSZ-AC:5 0.3253 0.3253 0.3253 0.3253 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Total gross floor area [m2] 511.16


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1208.83
Number of hours not met 1208.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 69.31 8540.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 34.71 2631.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 13.67 1049.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 52.80 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 21.83 1822.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 22.21 2747.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 52.80 214.52
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 52.80 214.52


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 67.90
Space Heating 0.00
Space Cooling 135.59
Fans (All) 42.71
Service Water Heating 43.44
Receptacle Equipment 103.29
Miscellaneous (All) 419.67
Subtotal 419.67


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 16.18
Space Heating 0.00
Space Cooling 32.31
Fans (All) 10.18
Service Water Heating 10.35
Receptacle Equipment 24.61
Miscellaneous 6.37


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2752. 8760.
BLDG_EQUIP_SCH 4310. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 2918.67 5840.67 0.67 0.00 0.00
PERIMETER_ZN_1 2815.33 4748.00 1196.67 0.00 0.00
PERIMETER_ZN_2 2917.17 5152.33 690.50 0.00 0.00
PERIMETER_ZN_3 3004.83 4885.33 869.83 0.00 0.00
PERIMETER_ZN_4 2880.50 5299.00 580.50 0.00 0.00
ATTIC 3933.17 827.67 763.00 1117.00 2119.17
Min 2815.33 827.67 0.67 0.00 0.00
Max 3933.17 5840.67 1196.67 1117.00 2119.17
Average 3078.28 4458.83 683.53 186.17 353.19
Sum 18469.67 26753.00 4101.17 1117.00 2119.17


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17868.50 23.50 0.00 0.00 0.00
PERIMETER_ZN_1 13324.33 31.67 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13344.00 12.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17868.50 31.67 0.00 0.00 0.00
Average 9354.81 11.19 0.00 0.00 0.00
Sum 56128.83 67.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 2034.50 6725.50 0.00 0.00 0.00
PERIMETER_ZN_1 1808.00 6412.17 539.83 0.00 0.00
PERIMETER_ZN_2 2459.33 6064.50 236.17 0.00 0.00
PERIMETER_ZN_3 2456.83 5965.83 337.33 0.00 0.00
PERIMETER_ZN_4 2467.67 6113.83 178.50 0.00 0.00
ATTIC 513.67 4285.00 800.67 574.83 2585.83
Min 513.67 4285.00 0.00 0.00 0.00
Max 2467.67 6725.50 800.67 574.83 2585.83
Average 1956.67 5927.81 348.75 95.81 430.97
Sum 11740.00 35566.83 2092.50 574.83 2585.83


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 13720.67 4171.33 0.00 0.00 0.00
PERIMETER_ZN_1 9943.83 3412.17 0.00 0.00 0.00
PERIMETER_ZN_2 4561.50 226.50 0.00 0.00 0.00
PERIMETER_ZN_3 12545.00 811.00 0.00 0.00 0.00
PERIMETER_ZN_4 6610.00 194.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 13720.67 4171.33 0.00 0.00 0.00
Average 7896.83 1469.17 0.00 0.00 0.00
Sum 47381.00 8815.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:12

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.415
February 27.500
March 28.331
April 29.151
May 29.006
June 28.856
July 27.250
August 27.543
September 27.578
October 26.894
November 26.683
December 25.974
   
Annual Sum or Average 27.594
Minimum of Months 25.974
Maximum of Months 29.151



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.355308E+10 6080.81 02-JAN-06:02 23.28 23.00 0.310808E+09 475.88 02-JAN-08:20 25.07 23.61
February 0.317243E+10 5747.16 27-FEB-06:02 24.08 21.92 0.281502E+09 469.23 21-FEB-08:09 24.08 21.92
March 0.377429E+10 5340.74 06-MAR-06:03 24.03 21.85 0.341678E+09 470.13 27-MAR-07:19 27.47 24.94
April 0.331077E+10 5082.24 03-APR-05:01 27.00 24.88 0.306782E+09 475.89 03-APR-07:19 27.90 25.55
May 0.357295E+10 5147.55 08-MAY-05:02 27.00 26.87 0.347143E+09 496.52 30-MAY-07:30 29.65 27.81
June 0.357220E+10 5312.37 19-JUN-05:02 27.00 26.21 0.350875E+09 491.67 19-JUN-10:09 33.50 27.79
July 0.334684E+10 5076.02 17-JUL-05:02 24.08 23.28 0.300324E+09 469.22 31-JUL-07:10 25.17 23.79
August 0.357535E+10 4794.59 14-AUG-05:02 26.00 26.00 0.351974E+09 481.99 14-AUG-07:19 27.87 26.46
September 0.319108E+10 5118.48 05-SEP-05:02 26.83 26.18 0.305623E+09 486.58 05-SEP-07:19 27.07 25.96
October 0.332856E+10 5341.90 10-OCT-05:02 24.00 23.57 0.315561E+09 469.74 10-OCT-07:19 24.13 23.43
November 0.335256E+10 5091.32 24-NOV-11:20 28.00 21.40 0.310986E+09 469.21 03-NOV-07:10 28.00 21.40
December 0.315908E+10 5263.66 26-DEC-06:02 22.17 21.35 0.293298E+09 469.21 19-DEC-08:09 22.17 21.35
                     
Annual Sum or Average 0.409092E+11         0.381655E+10        
Minimum of Months 0.315908E+10 4794.59   22.17 21.35 0.281502E+09 469.21   22.17 21.35
Maximum of Months 0.377429E+10 6080.81   28.00 26.87 0.351974E+09 496.52   33.50 27.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.427540E+10 6976.45 16-JAN-15:32 31.53 21.99 0.238750E+09 363.00 30-JAN-13:09 30.75 23.68
February 0.372473E+10 6488.01 21-FEB-06:02 24.83 21.85 0.215341E+09 362.50 13-FEB-13:09 24.83 21.85
March 0.399984E+10 5771.44 19-MAR-16:12 33.80 24.85 0.256200E+09 355.70 15-MAR-07:10 33.80 24.85
April 0.358701E+10 5247.47 03-APR-16:03 31.33 24.54 0.227503E+09 356.35 03-APR-12:09 31.33 24.54
May 0.389151E+10 5562.19 29-MAY-16:33 34.20 26.81 0.257657E+09 384.51 30-MAY-12:09 33.10 27.55
June 0.388454E+10 5482.22 18-JUN-17:22 30.00 26.62 0.259990E+09 388.16 12-JUN-12:09 30.00 26.62
July 0.347599E+10 5417.86 03-JUL-13:20 23.60 22.70 0.223666E+09 355.70 21-JUL-07:10 24.63 22.84
August 0.375963E+10 5087.55 29-AUG-13:30 25.00 23.79 0.261747E+09 380.68 14-AUG-12:09 25.00 23.79
September 0.338585E+10 5351.29 05-SEP-05:02 26.83 26.18 0.227298E+09 373.56 05-SEP-12:09 33.02 26.93
October 0.349913E+10 5269.91 10-OCT-08:20 25.67 24.28 0.235938E+09 356.32 16-OCT-12:09 29.80 26.95
November 0.386050E+10 5998.54 19-NOV-16:12 29.90 25.62 0.237986E+09 362.14 13-NOV-13:09 29.90 25.62
December 0.393672E+10 6586.63 03-DEC-15:23 30.25 22.20 0.226187E+09 372.60 26-DEC-13:09 32.00 23.12
                     
Annual Sum or Average 0.452809E+11         0.286826E+10        
Minimum of Months 0.338585E+10 5087.55   23.60 21.85 0.215341E+09 355.70   24.63 21.85
Maximum of Months 0.427540E+10 6976.45   34.20 26.81 0.261747E+09 388.16   33.80 27.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.224680E+10 4134.44 17-JAN-08:48 24.03 21.27 0.101222E+09 211.00 10-JAN-08:09 24.03 21.27
February 0.218869E+10 4443.19 21-FEB-10:00 20.30 19.04 91819917.97 211.01 21-FEB-08:09 20.30 19.04
March 0.266559E+10 4059.38 20-MAR-10:05 32.83 23.62 0.111399E+09 211.00 13-MAR-07:10 32.83 23.62
April 0.253513E+10 4141.85 09-APR-12:21 33.95 25.97 97600850.46 211.00 21-APR-07:10 25.92 24.59
May 0.272156E+10 4143.42 29-MAY-16:23 34.30 26.96 0.108030E+09 211.01 01-MAY-07:10 34.30 26.96
June 0.280490E+10 4013.67 18-JUN-17:22 30.00 26.62 0.108536E+09 211.01 19-JUN-07:10 27.83 26.68
July 0.230025E+10 4031.02 31-JUL-05:02 24.15 23.23 96811166.13 211.00 31-JUL-07:10 25.17 23.79
August 0.257755E+10 3841.09 28-AUG-10:07 31.08 26.90 0.111959E+09 211.00 21-AUG-07:10 31.08 26.90
September 0.230134E+10 3947.68 04-SEP-17:32 30.67 26.92 97303400.43 211.02 05-SEP-07:10 26.83 25.82
October 0.217610E+10 3876.29 02-OCT-09:00 29.00 24.91 0.101295E+09 211.00 10-OCT-07:10 23.92 23.32
November 0.214808E+10 4066.92 06-NOV-09:00 27.00 23.38 0.101213E+09 211.00 03-NOV-07:10 27.00 23.38
December 0.200172E+10 4105.99 26-DEC-09:08 25.43 21.72 96188781.68 211.00 18-DEC-08:09 25.43 21.72
                     
Annual Sum or Average 0.286677E+11         0.122338E+10        
Minimum of Months 0.200172E+10 3841.09   20.30 19.04 91819917.97 211.00   20.30 19.04
Maximum of Months 0.280490E+10 4443.19   34.30 26.96 0.111959E+09 211.02   34.30 26.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.317285E+10 5710.58 24-JAN-07:02 19.50 17.57 0.230598E+09 355.70 10-JAN-08:09 19.50 17.57
February 0.298994E+10 5875.15 21-FEB-09:06 26.72 21.47 0.208779E+09 355.70 16-FEB-08:09 26.72 21.47
March 0.368459E+10 5501.78 20-MAR-12:05 34.20 23.37 0.253377E+09 355.70 13-MAR-07:10 34.20 23.37
April 0.346832E+10 5334.55 03-APR-12:15 32.40 25.46 0.221886E+09 355.70 21-APR-07:10 25.92 24.59
May 0.396472E+10 5759.29 29-MAY-17:33 33.33 26.83 0.247993E+09 355.71 30-MAY-07:10 29.42 27.87
June 0.411855E+10 5566.87 18-JUN-16:52 29.00 25.99 0.251861E+09 355.71 19-JUN-07:10 27.83 26.68
July 0.349072E+10 5567.21 17-JUL-09:00 27.00 24.11 0.221144E+09 355.70 31-JUL-07:10 25.17 23.79
August 0.372064E+10 5186.11 14-AUG-16:00 27.80 26.16 0.255425E+09 355.70 21-AUG-07:10 25.75 25.32
September 0.330635E+10 5508.58 11-SEP-14:52 25.00 24.24 0.221875E+09 355.70 26-SEP-07:10 27.25 26.23
October 0.318421E+10 5472.78 10-OCT-08:20 25.67 24.28 0.231051E+09 355.70 10-OCT-07:10 25.67 24.28
November 0.313022E+10 5504.35 06-NOV-08:50 26.75 23.32 0.230506E+09 355.70 03-NOV-07:10 26.75 23.32
December 0.281198E+10 5510.84 26-DEC-08:42 24.83 21.60 0.219173E+09 355.70 18-DEC-08:09 24.83 21.60
                     
Annual Sum or Average 0.410431E+11         0.279367E+10        
Minimum of Months 0.281198E+10 5186.11   19.50 17.57 0.208779E+09 355.70   19.50 17.57
Maximum of Months 0.411855E+10 5875.15   34.20 26.83 0.255425E+09 355.71   34.20 27.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.227110E+10 5765.57 16-JAN-17:12 28.53 21.96 0.137184E+09 211.00 02-JAN-08:09 28.53 21.96
February 0.216914E+10 5460.94 26-FEB-16:52 29.80 22.20 0.124279E+09 211.00 16-FEB-08:09 29.80 22.20
March 0.267568E+10 5314.89 19-MAR-17:02 31.67 23.98 0.150742E+09 211.00 13-MAR-07:10 31.67 23.98
April 0.251310E+10 5191.29 23-APR-17:22 31.25 24.89 0.131346E+09 211.00 21-APR-07:10 31.25 24.89
May 0.272094E+10 5182.12 29-MAY-17:23 33.50 26.76 0.144211E+09 211.00 18-MAY-07:10 33.50 26.76
June 0.278407E+10 5021.46 11-JUN-17:12 32.50 27.60 0.144473E+09 211.00 01-JUN-07:10 32.50 27.60
July 0.227541E+10 5036.31 04-JUL-18:02 27.18 24.74 0.130990E+09 211.00 31-JUL-07:10 25.17 23.79
August 0.253581E+10 4978.20 27-AUG-17:42 30.33 26.93 0.150544E+09 211.00 21-AUG-07:10 30.33 26.93
September 0.228362E+10 5129.77 04-SEP-17:32 30.67 26.92 0.130855E+09 211.00 26-SEP-07:10 27.25 26.23
October 0.217033E+10 4364.74 10-OCT-07:02 23.92 23.32 0.137133E+09 211.00 10-OCT-07:10 23.92 23.32
November 0.215878E+10 4914.36 19-NOV-16:12 29.90 25.62 0.136986E+09 211.00 03-NOV-07:10 29.90 25.62
December 0.201507E+10 5229.60 25-DEC-17:02 28.67 24.13 0.130358E+09 211.00 18-DEC-08:09 28.67 24.13
                     
Annual Sum or Average 0.285731E+11         0.164910E+10        
Minimum of Months 0.201507E+10 4364.74   23.92 21.96 0.124279E+09 211.00   23.92 21.96
Maximum of Months 0.278407E+10 5765.57   33.50 27.60 0.150742E+09 211.00   33.50 27.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03 23.60 0.00 0.00 01-JAN-00:10 25.03 23.60
February 0.00 0.00 01-FEB-00:10 26.43 22.46 0.00 0.00 01-FEB-00:10 26.43 22.46
March 0.00 0.00 01-MAR-00:10 25.93 22.97 0.00 0.00 01-MAR-00:10 25.93 22.97
April 0.00 0.00 01-APR-00:10 27.53 25.10 0.00 0.00 01-APR-00:10 27.53 25.10
May 0.00 0.00 01-MAY-00:05 28.62 26.40 0.00 0.00 01-MAY-00:10 28.62 26.40
June 0.00 0.00 01-JUN-00:10 24.05 23.91 0.00 0.00 01-JUN-00:10 24.05 23.91
July 0.00 0.00 01-JUL-00:10 25.40 24.33 0.00 0.00 01-JUL-00:10 25.40 24.33
August 0.00 0.00 01-AUG-00:10 25.63 24.75 0.00 0.00 01-AUG-00:10 25.63 24.75
September 0.00 0.00 01-SEP-00:10 26.53 25.66 0.00 0.00 01-SEP-00:10 26.53 25.66
October 0.00 0.00 01-OCT-00:10 26.27 25.35 0.00 0.00 01-OCT-00:10 26.27 25.35
November 0.00 0.00 01-NOV-00:10 25.22 24.37 0.00 0.00 01-NOV-00:10 25.22 24.37
December 0.00 0.00 01-DEC-00:10 23.80 23.43 0.00 0.00 01-DEC-00:10 23.80 23.43
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   23.80 22.46 0.00 0.00   23.80 22.46
Maximum of Months 0.00 0.00   28.62 26.40 0.00 0.00   28.62 26.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 32747858.85 709.00 03-JAN-18:02 30.17
February 34366507.55 784.58 06-FEB-18:02 31.22
March 45191354.21 842.76 13-MAR-17:01 31.83
April 41937408.66 907.71 11-APR-17:01 32.67
May 42634203.00 968.08 09-MAY-17:01 33.67
June 41419456.75 919.79 09-JUN-17:01 32.67
July 32665466.03 957.89 14-JUL-17:01 32.78
August 37001772.21 853.75 01-AUG-17:01 31.83
September 32754432.52 863.67 13-SEP-17:01 31.83
October 31393486.26 755.96 04-OCT-17:01 30.33
November 31205225.46 718.47 03-NOV-17:02 29.83
December 27658301.65 672.80 29-DEC-19:00 31.40
         
Annual Sum or Average 0.430975E+09      
Minimum of Months 27658301.65 672.80   29.83
Maximum of Months 45191354.21 968.08   33.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 32318686.19 606.83 31-JAN-18:11 29.50
February 34071276.78 655.42 22-FEB-18:11 30.43
March 47576373.85 709.12 13-MAR-17:11 31.67
April 38831863.42 739.67 24-APR-17:11 32.50
May 40969341.14 781.44 09-MAY-17:11 33.33
June 37586810.87 730.29 08-JUN-17:11 32.33
July 35616159.73 765.89 14-JUL-17:01 32.78
August 39869668.30 675.48 01-AUG-17:01 31.83
September 34682606.23 728.46 13-SEP-17:11 31.67
October 36292728.37 606.99 04-OCT-17:01 30.33
November 32969924.43 636.86 17-NOV-18:23 30.30
December 28750452.29 565.45 29-DEC-18:23 29.20
         
Annual Sum or Average 0.439536E+09      
Minimum of Months 28750452.29 565.45   29.20
Maximum of Months 47576373.85 781.44   33.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 25878933.79 430.46 31-JAN-18:11 29.50
February 25093902.36 456.99 22-FEB-18:11 30.43
March 32255108.48 491.93 13-MAR-17:11 31.67
April 26296001.09 518.43 24-APR-17:11 32.50
May 29684563.94 555.73 09-MAY-17:11 33.33
June 27384203.47 522.43 09-JUN-17:11 32.33
July 23916441.56 520.64 26-JUL-17:11 32.27
August 28016825.69 461.22 01-AUG-17:22 31.50
September 24533026.49 500.12 13-SEP-17:11 31.67
October 26825410.30 432.69 16-OCT-17:11 29.83
November 25466986.77 447.89 17-NOV-18:23 30.30
December 23608280.81 408.04 29-DEC-18:23 29.20
         
Annual Sum or Average 0.318960E+09      
Minimum of Months 23608280.81 408.04   29.20
Maximum of Months 32255108.48 555.73   33.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 38271244.18 636.82 31-JAN-18:11 29.50
February 38076938.14 682.28 22-FEB-18:11 30.43
March 49420486.75 740.98 13-MAR-17:11 31.67
April 40147595.22 785.56 24-APR-17:11 32.50
May 42022379.31 835.05 09-MAY-17:11 33.33
June 36859586.13 771.62 09-JUN-17:11 32.33
July 33496860.59 780.94 26-JUL-17:11 32.27
August 40312547.57 701.88 01-AUG-17:01 31.83
September 35372201.95 755.53 13-SEP-17:11 31.67
October 38572741.69 639.48 16-OCT-17:11 29.83
November 38091810.43 658.77 17-NOV-18:23 30.30
December 33213596.24 607.04 29-DEC-19:00 31.40
         
Annual Sum or Average 0.463858E+09      
Minimum of Months 33213596.24 607.04   29.50
Maximum of Months 49420486.75 835.05   33.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 30705504.40 474.26 03-JAN-07:05 25.27
February 28951967.14 493.39 22-FEB-18:11 30.43
March 31121609.94 523.00 13-MAR-17:11 31.67
April 24518059.35 553.65 24-APR-17:11 32.50
May 30066237.22 580.30 09-MAY-17:11 33.33
June 24639814.16 547.12 08-JUN-17:11 32.33
July 24878004.23 560.48 26-JUL-17:11 32.27
August 28774173.27 494.94 01-AUG-17:22 31.50
September 26129930.59 520.35 08-SEP-17:12 30.83
October 28592603.31 475.07 16-OCT-17:11 29.83
November 30631365.86 499.92 17-NOV-18:23 30.30
December 29770291.06 458.86 29-DEC-18:23 29.20
         
Annual Sum or Average 0.338780E+09      
Minimum of Months 24518059.35 458.86   25.27
Maximum of Months 31121609.94 580.30   33.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 25.03
February 0.00 0.00 01-FEB-00:10 26.43
March 0.00 0.00 01-MAR-00:10 25.93
April 0.00 0.00 01-APR-00:10 27.53
May 0.00 0.00 01-MAY-00:05 28.62
June 0.00 0.00 01-JUN-00:10 24.05
July 0.00 0.00 01-JUL-00:10 25.40
August 0.00 0.00 01-AUG-00:10 25.63
September 0.00 0.00 01-SEP-00:10 26.53
October 0.00 0.00 01-OCT-00:10 26.27
November 0.00 0.00 01-NOV-00:10 25.22
December 0.00 0.00 01-DEC-00:10 23.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   23.80
Maximum of Months 0.00 0.00   28.62



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.944342E+09 784.13 02-JAN-08:09 0.129836E+10 1014.68 02-JAN-08:09
February 0.853760E+09 784.13 01-FEB-08:09 0.117388E+10 1014.68 01-FEB-08:09
March 0.994276E+09 784.13 01-MAR-08:09 0.137025E+10 1014.68 01-MAR-08:09
April 0.905826E+09 784.13 03-APR-07:10 0.124598E+10 1014.68 03-APR-07:10
May 0.969309E+09 784.13 01-MAY-07:10 0.133431E+10 1014.68 01-MAY-07:10
June 0.955759E+09 784.13 01-JUN-07:10 0.131568E+10 1014.68 01-JUN-07:10
July 0.919376E+09 784.13 03-JUL-07:10 0.126352E+10 1014.68 03-JUL-07:10
August 0.994276E+09 784.13 01-AUG-07:10 0.137025E+10 1014.68 01-AUG-07:10
September 0.905826E+09 784.13 01-SEP-07:10 0.124379E+10 1014.68 01-SEP-07:10
October 0.944342E+09 784.13 02-OCT-07:10 0.129946E+10 1014.68 02-OCT-07:10
November 0.930792E+09 784.13 01-NOV-07:10 0.128083E+10 1014.68 01-NOV-07:10
December 0.919376E+09 784.13 01-DEC-08:09 0.126242E+10 1014.68 01-DEC-08:09
             
Annual Sum or Average 0.112373E+11     0.154587E+11    
Minimum of Months 0.853760E+09 784.13   0.117388E+10 1014.68  
Maximum of Months 0.994276E+09 784.13   0.137025E+10 1014.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.604692E+09 567.71 02-JAN-16:00 0.984244E+09 769.19 02-JAN-08:09
February 0.547046E+09 537.84 07-FEB-16:00 0.889874E+09 769.19 01-FEB-08:09
March 0.634713E+09 555.29 01-MAR-16:00 0.103874E+10 769.19 01-MAR-08:09
April 0.581255E+09 542.20 21-APR-07:10 0.944536E+09 769.19 03-APR-07:10
May 0.634503E+09 551.50 17-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.622014E+09 548.21 20-JUN-07:10 0.997370E+09 769.19 01-JUN-07:10
July 0.607485E+09 549.57 11-JUL-07:10 0.957827E+09 769.19 03-JUL-07:10
August 0.641311E+09 547.57 21-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.584774E+09 540.14 21-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.607103E+09 545.96 23-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.598888E+09 574.93 09-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.590818E+09 577.91 18-DEC-16:00 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.725460E+10     0.117187E+11    
Minimum of Months 0.547046E+09 537.84   0.889874E+09 769.19  
Maximum of Months 0.641311E+09 577.91   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.371456E+09 343.21 02-JAN-16:00 0.583867E+09 456.29 02-JAN-08:09
February 0.335361E+09 336.38 07-FEB-16:00 0.527885E+09 456.29 01-FEB-08:09
March 0.388163E+09 337.46 01-MAR-16:00 0.616194E+09 456.29 01-MAR-08:09
April 0.352983E+09 320.61 13-APR-15:00 0.560311E+09 456.29 03-APR-07:10
May 0.379223E+09 324.32 22-MAY-15:00 0.600030E+09 456.29 01-MAY-07:10
June 0.370544E+09 319.20 01-JUN-15:00 0.591653E+09 456.29 01-JUN-07:10
July 0.360376E+09 322.96 17-JUL-15:00 0.568196E+09 456.29 03-JUL-07:10
August 0.387345E+09 320.39 24-AUG-15:00 0.616194E+09 456.29 01-AUG-07:10
September 0.355517E+09 324.33 22-SEP-15:00 0.559325E+09 456.29 01-SEP-07:10
October 0.370153E+09 333.65 30-OCT-15:00 0.584359E+09 456.29 02-OCT-07:10
November 0.366849E+09 345.21 09-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.363678E+09 345.68 18-DEC-16:00 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.440165E+10     0.695170E+10    
Minimum of Months 0.335361E+09 319.20   0.527885E+09 456.29  
Maximum of Months 0.388163E+09 345.68   0.616194E+09 456.29  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.649438E+09 575.77 02-JAN-16:00 0.984244E+09 769.19 02-JAN-08:09
February 0.580498E+09 555.41 07-FEB-16:00 0.889874E+09 769.19 01-FEB-08:09
March 0.657536E+09 563.60 01-MAR-16:00 0.103874E+10 769.19 01-MAR-08:09
April 0.581313E+09 542.76 21-APR-07:10 0.944536E+09 769.19 03-APR-07:10
May 0.620683E+09 546.72 17-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.603926E+09 538.71 20-JUN-07:10 0.997370E+09 769.19 01-JUN-07:10
July 0.588159E+09 541.56 11-JUL-07:10 0.957827E+09 769.19 03-JUL-07:10
August 0.636183E+09 544.52 21-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.596205E+09 544.78 21-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.634822E+09 556.82 30-OCT-15:00 0.985075E+09 769.19 02-OCT-07:10
November 0.637625E+09 579.69 27-NOV-16:00 0.970953E+09 769.19 01-NOV-07:10
December 0.636198E+09 581.66 18-DEC-16:00 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.742259E+10     0.117187E+11    
Minimum of Months 0.580498E+09 538.71   0.889874E+09 769.19  
Maximum of Months 0.657536E+09 581.66   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.368870E+09 335.34 02-JAN-16:00 0.583867E+09 456.29 02-JAN-08:09
February 0.333595E+09 321.24 08-FEB-08:09 0.527885E+09 456.29 01-FEB-08:09
March 0.387888E+09 330.48 28-MAR-07:10 0.616194E+09 456.29 01-MAR-08:09
April 0.353585E+09 330.65 21-APR-07:10 0.560311E+09 456.29 03-APR-07:10
May 0.379766E+09 332.97 17-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.370572E+09 331.11 20-JUN-07:10 0.591653E+09 456.29 01-JUN-07:10
July 0.361030E+09 331.94 11-JUL-07:10 0.568196E+09 456.29 03-JUL-07:10
August 0.388094E+09 332.12 21-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.355580E+09 330.85 21-SEP-07:10 0.559325E+09 456.29 01-SEP-07:10
October 0.369738E+09 333.99 23-OCT-07:10 0.584359E+09 456.29 02-OCT-07:10
November 0.363899E+09 339.49 09-NOV-16:00 0.575982E+09 456.29 01-NOV-07:10
December 0.360370E+09 342.39 18-DEC-16:00 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.439299E+10     0.695170E+10    
Minimum of Months 0.333595E+09 321.24   0.527885E+09 456.29  
Maximum of Months 0.388094E+09 342.39   0.616194E+09 456.29  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.944342E+09 0.129836E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.905826E+09 0.124598E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.969309E+09 0.133431E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.955759E+09 0.131568E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.919376E+09 0.126352E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.905826E+09 0.124379E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.944342E+09 0.129946E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.930792E+09 0.128083E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.919376E+09 0.126242E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.112373E+11 0.154587E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.853760E+09 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.994276E+09 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.604692E+09 0.984244E+09 0.00 0.00 0.00 0.00 0.208862E+09 66991742.73
February 0.488155E+09 0.547046E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.225400E+09 40906140.90
March 0.590925E+09 0.634713E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.312507E+09 32662862.39
April 0.513848E+09 0.581255E+09 0.944536E+09 0.00 0.00 0.00 0.00 0.282855E+09 12683120.49
May 0.565233E+09 0.634503E+09 0.101149E+10 0.00 0.00 0.00 0.00 0.288589E+09 20914513.92
June 0.565233E+09 0.622014E+09 0.997370E+09 0.00 0.00 0.00 0.00 0.294426E+09 24336826.14
July 0.513848E+09 0.607485E+09 0.957827E+09 0.00 0.00 0.00 0.00 0.192615E+09 28302136.96
August 0.590925E+09 0.641311E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.238720E+09 30887595.35
September 0.513848E+09 0.584774E+09 0.942874E+09 0.00 0.00 0.00 0.00 0.201503E+09 22472703.36
October 0.539540E+09 0.607103E+09 0.985075E+09 0.00 0.00 0.00 0.00 0.181694E+09 33145296.66
November 0.539540E+09 0.598888E+09 0.970953E+09 0.00 0.00 0.00 0.00 0.187687E+09 34081526.00
December 0.513848E+09 0.590818E+09 0.956997E+09 0.00 0.00 0.00 0.00 0.174375E+09 64649293.14
                   
Annual Sum or Average 0.647448E+10 0.725460E+10 0.117187E+11 0.00 0.00 0.00 0.00 0.278923E+10 0.412034E+09
Minimum of Months 0.488155E+09 0.547046E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.174375E+09 12683120.49
Maximum of Months 0.590925E+09 0.641311E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.312507E+09 66991742.73



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.371456E+09 0.583867E+09 0.00 0.00 0.00 0.00 6693139.06 19587996.44
February 0.211974E+09 0.335361E+09 0.527885E+09 0.00 0.00 0.00 0.00 9726504.47 9496171.92
March 0.256600E+09 0.388163E+09 0.616194E+09 0.00 0.00 0.00 0.00 16591925.39 16798953.08
April 0.223130E+09 0.352983E+09 0.560311E+09 0.00 0.00 0.00 0.00 14849311.98 6999738.87
May 0.245443E+09 0.379223E+09 0.600030E+09 0.00 0.00 0.00 0.00 18435492.55 9436526.11
June 0.245443E+09 0.370544E+09 0.591653E+09 0.00 0.00 0.00 0.00 16498195.55 10781818.24
July 0.223130E+09 0.360376E+09 0.568196E+09 0.00 0.00 0.00 0.00 8978500.59 9710233.20
August 0.256600E+09 0.387345E+09 0.616194E+09 0.00 0.00 0.00 0.00 12400018.82 14748903.31
September 0.223130E+09 0.355517E+09 0.559325E+09 0.00 0.00 0.00 0.00 8739134.24 9246256.45
October 0.234287E+09 0.370153E+09 0.584359E+09 0.00 0.00 0.00 0.00 6703400.29 12326694.76
November 0.234287E+09 0.366849E+09 0.575982E+09 0.00 0.00 0.00 0.00 5813068.97 12156925.44
December 0.223130E+09 0.363678E+09 0.567703E+09 0.00 0.00 0.00 0.00 5239865.15 18855784.18
                   
Annual Sum or Average 0.281144E+10 0.440165E+10 0.695170E+10 0.00 0.00 0.00 0.00 0.130669E+09 0.150146E+09
Minimum of Months 0.211974E+09 0.335361E+09 0.527885E+09 0.00 0.00 0.00 0.00 5239865.15 6999738.87
Maximum of Months 0.256600E+09 0.388163E+09 0.616194E+09 0.00 0.00 0.00 0.00 18435492.55 19587996.44



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.649438E+09 0.984244E+09 0.00 0.00 0.00 0.00 10797071.75 26597556.66
February 0.488155E+09 0.580498E+09 0.889874E+09 0.00 0.00 0.00 0.00 15064476.20 12120189.53
March 0.590925E+09 0.657536E+09 0.103874E+10 0.00 0.00 0.00 0.00 26051690.12 22110217.28
April 0.513848E+09 0.581313E+09 0.944536E+09 0.00 0.00 0.00 0.00 23249672.63 9136705.28
May 0.565233E+09 0.620683E+09 0.101149E+10 0.00 0.00 0.00 0.00 27686948.62 13726276.02
June 0.565233E+09 0.603926E+09 0.997370E+09 0.00 0.00 0.00 0.00 23868207.37 16504299.62
July 0.513848E+09 0.588159E+09 0.957827E+09 0.00 0.00 0.00 0.00 13628417.75 14123669.06
August 0.590925E+09 0.636183E+09 0.103874E+10 0.00 0.00 0.00 0.00 19250767.32 20759945.84
September 0.513848E+09 0.596205E+09 0.942874E+09 0.00 0.00 0.00 0.00 13446436.44 12767543.28
October 0.539540E+09 0.634822E+09 0.985075E+09 0.00 0.00 0.00 0.00 10418292.09 17197591.79
November 0.539540E+09 0.637625E+09 0.970953E+09 0.00 0.00 0.00 0.00 9386715.14 16365650.73
December 0.513848E+09 0.636198E+09 0.956997E+09 0.00 0.00 0.00 0.00 8359806.41 25967997.01
                   
Annual Sum or Average 0.647448E+10 0.742259E+10 0.117187E+11 0.00 0.00 0.00 0.00 0.201209E+09 0.207378E+09
Minimum of Months 0.488155E+09 0.580498E+09 0.889874E+09 0.00 0.00 0.00 0.00 8359806.41 9136705.28
Maximum of Months 0.590925E+09 0.657536E+09 0.103874E+10 0.00 0.00 0.00 0.00 27686948.62 26597556.66



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.368870E+09 0.583867E+09 0.00 0.00 0.00 0.00 6717289.37 20541689.26
February 0.289580E+09 0.333595E+09 0.527885E+09 0.00 0.00 0.00 0.00 9472071.81 10303334.89
March 0.350544E+09 0.387888E+09 0.616194E+09 0.00 0.00 0.00 0.00 16123058.98 19190182.37
April 0.304821E+09 0.353585E+09 0.560311E+09 0.00 0.00 0.00 0.00 13812910.42 8106561.93
May 0.335303E+09 0.379766E+09 0.600030E+09 0.00 0.00 0.00 0.00 17859115.16 9897519.45
June 0.335303E+09 0.370572E+09 0.591653E+09 0.00 0.00 0.00 0.00 16013103.89 11559165.02
July 0.304821E+09 0.361030E+09 0.568196E+09 0.00 0.00 0.00 0.00 8771458.32 10311573.61
August 0.350544E+09 0.388094E+09 0.616194E+09 0.00 0.00 0.00 0.00 12499043.21 15796087.68
September 0.304821E+09 0.355580E+09 0.559325E+09 0.00 0.00 0.00 0.00 8695967.58 9524164.42
October 0.320062E+09 0.369738E+09 0.584359E+09 0.00 0.00 0.00 0.00 6578289.85 12951616.92
November 0.320062E+09 0.363899E+09 0.575982E+09 0.00 0.00 0.00 0.00 5890263.37 12574322.53
December 0.304821E+09 0.360370E+09 0.567703E+09 0.00 0.00 0.00 0.00 5284376.34 19604687.25
                   
Annual Sum or Average 0.384075E+10 0.439299E+10 0.695170E+10 0.00 0.00 0.00 0.00 0.127717E+09 0.160361E+09
Minimum of Months 0.289580E+09 0.333595E+09 0.527885E+09 0.00 0.00 0.00 0.00 5284376.34 8106561.93
Maximum of Months 0.350544E+09 0.388094E+09 0.616194E+09 0.00 0.00 0.00 0.00 17859115.16 20541689.26



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.733357E+09 0.365056E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.888212E+09 0.365283E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.850382E+09 0.439465E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.736653E+09 0.431800E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.605892E+09 0.370779E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.492009E+09 0.396710E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.586714E+09 0.384025E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.608240E+09 0.351276E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.545962E+09 0.367077E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.557094E+09 0.320964E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.652589E+09 0.325864E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.720009E+09 0.345028E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.797711E+10 0.446333E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.492009E+09 0.320964E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.888212E+09 0.439465E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 784.13 02-JAN-08:09 1014.68 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 784.13 01-FEB-08:09 1014.68 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 784.13 01-MAR-08:09 1014.68 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 784.13 03-APR-07:10 1014.68 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 784.13 01-MAY-07:10 1014.68 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 784.13 01-JUN-07:10 1014.68 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 784.13 03-JUL-07:10 1014.68 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 784.13 01-AUG-07:10 1014.68 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 784.13 01-SEP-07:10 1014.68 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 784.13 02-OCT-07:10 1014.68 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 784.13 01-NOV-07:10 1014.68 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 784.13 01-DEC-08:09 1014.68 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   784.13   1014.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 567.71 02-JAN-16:00 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 1316.57 04-JAN-12:05 1161.85 23-JAN-07:01
February 732.70 01-FEB-08:09 537.84 07-FEB-16:00 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 1349.57 28-FEB-13:00 888.91 01-FEB-07:02
March 732.70 01-MAR-08:09 555.29 01-MAR-16:00 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 1554.53 21-MAR-11:53 565.58 15-MAR-06:02
April 732.70 03-APR-07:10 542.20 21-APR-07:10 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 1505.58 11-APR-16:03 373.07 24-APR-06:02
May 732.70 01-MAY-07:10 551.50 17-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 1764.08 05-MAY-11:03 512.30 17-MAY-06:02
June 732.70 01-JUN-07:10 548.21 20-JUN-07:10 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 1534.64 23-JUN-16:03 605.78 21-JUN-06:02
July 732.70 03-JUL-07:10 549.57 11-JUL-07:10 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 1355.32 14-JUL-16:52 480.46 07-JUL-06:02
August 732.70 01-AUG-07:10 547.57 21-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 1346.40 11-AUG-11:03 492.11 30-AUG-06:01
September 732.70 01-SEP-07:10 540.14 21-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 1273.96 13-SEP-16:03 498.32 19-SEP-06:01
October 732.70 02-OCT-07:10 545.96 23-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 1212.42 04-OCT-11:05 650.94 23-OCT-06:02
November 732.70 01-NOV-07:10 574.93 09-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 1185.69 10-NOV-12:10 798.87 27-NOV-07:02
December 732.70 01-DEC-08:09 577.91 18-DEC-16:00 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 1153.82 07-DEC-12:05 1094.99 21-DEC-07:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   537.84   769.19   0.00 0.00 0.00 0.00 1153.82   373.07  
Maximum of Months 732.70   577.91   769.19   0.00 0.00 0.00 0.00 1764.08   1161.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 343.21 02-JAN-16:00 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 25.52 04-JAN-13:00 145.61 07-JAN-05:00
February 434.65 01-FEB-08:09 336.38 07-FEB-16:00 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 49.53 26-FEB-15:55 42.04 01-FEB-07:00
March 434.65 01-MAR-08:09 337.46 01-MAR-16:00 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 92.00 19-MAR-15:25 40.48 06-MAR-01:00
April 434.65 03-APR-07:10 320.61 13-APR-15:00 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 45.95 02-APR-15:35 44.71 09-APR-15:55
May 434.65 01-MAY-07:10 324.32 22-MAY-15:00 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 63.69 07-MAY-15:00 81.14 08-MAY-21:55
June 434.65 01-JUN-07:10 319.20 01-JUN-15:00 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 67.94 18-JUN-14:07 79.49 20-JUN-22:55
July 434.65 03-JUL-07:10 322.96 17-JUL-15:00 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 40.07 04-JUL-13:55 51.27 02-JUL-14:00
August 434.65 01-AUG-07:10 320.39 24-AUG-15:00 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 45.55 27-AUG-14:00 64.00 23-AUG-19:53
September 434.65 01-SEP-07:10 324.33 22-SEP-15:00 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 50.25 10-SEP-14:47 48.58 03-SEP-16:10
October 434.65 02-OCT-07:10 333.65 30-OCT-15:00 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 39.53 29-OCT-13:00 45.94 29-OCT-17:10
November 434.65 01-NOV-07:10 345.21 09-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 21.56 10-NOV-12:55 35.19 26-NOV-10:00
December 434.65 01-DEC-08:09 345.68 18-DEC-16:00 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 17.95 19-DEC-14:00 51.05 21-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   319.20   456.29   0.00 0.00 0.00 0.00 17.95   35.19  
Maximum of Months 434.65   345.68   456.29   0.00 0.00 0.00 0.00 92.00   145.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 575.77 02-JAN-16:00 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 38.28 04-JAN-13:00 211.45 07-JAN-05:00
February 732.70 01-FEB-08:09 555.41 07-FEB-16:00 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 72.23 26-FEB-15:30 58.30 01-FEB-06:55
March 732.70 01-MAR-08:09 563.60 01-MAR-16:00 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 138.04 19-MAR-15:52 55.79 06-MAR-01:00
April 732.70 03-APR-07:10 542.76 21-APR-07:10 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 67.50 02-APR-15:35 60.12 09-APR-15:55
May 732.70 01-MAY-07:10 546.72 17-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 99.61 07-MAY-14:47 122.05 08-MAY-21:55
June 732.70 01-JUN-07:10 538.71 20-JUN-07:10 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 99.16 18-JUN-14:17 121.06 20-JUN-22:55
July 732.70 03-JUL-07:10 541.56 11-JUL-07:10 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 59.09 04-JUL-13:50 74.89 02-JUL-14:00
August 732.70 01-AUG-07:10 544.52 21-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 68.34 27-AUG-14:00 93.90 23-AUG-19:53
September 732.70 01-SEP-07:10 544.78 21-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 70.86 10-SEP-14:55 74.83 03-SEP-15:58
October 732.70 02-OCT-07:10 556.82 30-OCT-15:00 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 51.92 29-OCT-13:00 66.90 29-OCT-16:52
November 732.70 01-NOV-07:10 579.69 27-NOV-16:00 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 32.34 10-NOV-12:55 48.15 26-NOV-10:00
December 732.70 01-DEC-08:09 581.66 18-DEC-16:00 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 26.93 19-DEC-14:00 75.45 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   538.71   769.19   0.00 0.00 0.00 0.00 26.93   48.15  
Maximum of Months 732.70   581.66   769.19   0.00 0.00 0.00 0.00 138.04   211.45  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 335.34 02-JAN-16:00 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 25.52 04-JAN-13:00 148.93 07-JAN-05:00
February 434.65 01-FEB-08:09 321.24 08-FEB-08:09 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 47.58 26-FEB-14:57 42.04 01-FEB-07:00
March 434.65 01-MAR-08:09 330.48 28-MAR-07:10 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 94.16 19-MAR-15:52 42.73 11-MAR-19:55
April 434.65 03-APR-07:10 330.65 21-APR-07:10 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 43.98 02-APR-15:10 43.27 09-APR-16:00
May 434.65 01-MAY-07:10 332.97 17-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 63.69 07-MAY-15:00 79.77 08-MAY-21:55
June 434.65 01-JUN-07:10 331.11 20-JUN-07:10 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 65.37 18-JUN-13:47 81.12 20-JUN-22:55
July 434.65 03-JUL-07:10 331.94 11-JUL-07:10 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 38.49 04-JUL-14:10 56.91 19-JUL-18:53
August 434.65 01-AUG-07:10 332.12 21-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 45.57 27-AUG-14:00 73.36 23-AUG-19:53
September 434.65 01-SEP-07:10 330.85 21-SEP-07:10 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 45.56 10-SEP-14:50 46.14 03-SEP-16:20
October 434.65 02-OCT-07:10 333.99 23-OCT-07:10 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 39.53 29-OCT-13:00 49.53 29-OCT-17:10
November 434.65 01-NOV-07:10 339.49 09-NOV-16:00 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 21.56 10-NOV-12:55 33.52 26-NOV-10:00
December 434.65 01-DEC-08:09 342.39 18-DEC-16:00 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 17.96 19-DEC-14:00 51.36 21-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   321.24   456.29   0.00 0.00 0.00 0.00 17.96   33.52  
Maximum of Months 434.65   342.39   456.29   0.00 0.00 0.00 0.00 94.16   148.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1035.37 28-JAN-23:00 5696.47 16-JAN-13:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1419.99 28-FEB-06:20 6172.19 24-FEB-13:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1747.67 03-MAR-14:50 6339.65 08-MAR-13:45
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1247.02 09-APR-14:00 6314.05 05-APR-13:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1213.83 28-MAY-06:42 7351.82 01-MAY-12:52
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1083.24 23-JUN-04:00 5902.69 19-JUN-11:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1138.24 19-JUL-01:30 5653.26 19-JUL-13:40
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 917.22 02-AUG-03:55 6136.48 17-AUG-12:42
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 904.17 12-SEP-04:00 6600.93 11-SEP-13:52
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1277.35 20-OCT-00:55 5783.64 07-OCT-12:30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 864.20 07-NOV-04:30 5433.99 19-NOV-13:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 982.27 25-DEC-06:35 5392.25 27-DEC-12:40
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 864.20   5392.25  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1747.67   7351.82  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6080.81 02-JAN-06:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
February 5747.16 27-FEB-06:02 531.60 1001.93 2536.69 0.00 0.00 0.00 0.00 0.00 0.00
March 5340.74 06-MAR-06:03 425.28 801.55 2029.35 0.00 0.00 0.00 0.00 0.00 0.00
April 5082.24 03-APR-05:01 744.23 1402.71 3551.37 0.00 0.00 0.00 0.00 0.00 0.00
May 5147.55 08-MAY-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
June 5312.37 19-JUN-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
July 5076.02 17-JUL-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
August 4794.59 14-AUG-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
September 5118.48 05-SEP-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
October 5341.90 10-OCT-05:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
November 5091.32 24-NOV-11:20 966.54 784.13 1014.68 0.00 0.00 0.00 0.00 0.00 0.00
December 5263.66 26-DEC-06:02 637.92 1202.32 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 4794.59   425.28 784.13 1014.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6080.81   966.54 1402.71 3551.37 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6976.45 16-JAN-15:32 0.00 361.46 615.35 0.00 0.00 0.00 0.00 7.79 0.00
February 6488.01 21-FEB-06:02 483.58 911.44 2307.57 0.00 0.00 0.00 0.00 0.00 94.71
March 5771.44 19-MAR-16:12 0.00 590.91 923.03 0.00 0.00 0.00 0.00 109.61 0.00
April 5247.47 03-APR-16:03 937.85 1305.75 1538.38 0.00 0.00 0.00 0.00 1069.75 0.00
May 5562.19 29-MAY-16:33 0.00 412.97 615.35 0.00 0.00 0.00 0.00 23.41 0.00
June 5482.22 18-JUN-17:22 0.00 664.41 923.03 0.00 0.00 0.00 0.00 4.73 0.00
July 5417.86 03-JUL-13:20 2198.10 1435.76 2307.57 0.00 0.00 0.00 0.00 0.00 7.98
August 5087.55 29-AUG-13:30 732.70 451.82 769.19 0.00 0.00 0.00 0.00 28.74 0.00
September 5351.29 05-SEP-05:02 483.58 911.44 2307.57 0.00 0.00 0.00 0.00 0.00 61.13
October 5269.91 10-OCT-08:20 2198.10 1355.46 2307.57 0.00 0.00 0.00 0.00 32.04 0.00
November 5998.54 19-NOV-16:12 0.00 474.81 769.19 0.00 0.00 0.00 0.00 2.99 0.00
December 6586.63 03-DEC-15:23 0.00 361.46 615.35 0.00 0.00 0.00 0.00 5.53 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5087.55   0.00 361.46 615.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6976.45   2198.10 1435.76 2307.57 0.00 0.00 0.00 0.00 1069.75 94.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4134.44 17-JAN-08:48 2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 0.09 0.00
February 4443.19 21-FEB-10:00 869.29 536.05 912.59 0.00 0.00 0.00 0.00 0.00 3.94
March 4059.38 20-MAR-10:05 2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 23.83 0.00
April 4141.85 09-APR-12:21 0.00 574.70 912.59 0.00 0.00 0.00 0.00 22.87 0.00
May 4143.42 29-MAY-16:23 0.00 256.33 365.04 0.00 0.00 0.00 0.00 14.16 0.00
June 4013.67 18-JUN-17:22 0.00 401.86 547.55 0.00 0.00 0.00 0.00 2.48 0.00
July 4031.02 31-JUL-05:02 286.87 540.68 1368.88 0.00 0.00 0.00 0.00 0.00 9.98
August 3841.09 28-AUG-10:07 1303.94 804.07 1368.88 0.00 0.00 0.00 0.00 12.45 0.00
September 3947.68 04-SEP-17:32 0.00 349.37 456.29 0.00 0.00 0.00 0.00 7.96 0.00
October 3876.29 02-OCT-09:00 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 5.13 0.00
November 4066.92 06-NOV-09:00 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 4.22 0.00
December 4105.99 26-DEC-09:08 2173.23 1340.12 2281.47 0.00 0.00 0.00 0.00 2.90 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3841.09   0.00 256.33 365.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4443.19   2607.88 1608.15 2737.76 0.00 0.00 0.00 0.00 23.83 9.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5710.58 24-JAN-07:02 923.20 1558.24 2307.57 0.00 0.00 0.00 0.00 0.00 6.04
February 5875.15 21-FEB-09:06 3663.49 2484.70 3845.95 0.00 0.00 0.00 0.00 4.54 0.00
March 5501.78 20-MAR-12:05 1465.40 987.58 1538.38 0.00 0.00 0.00 0.00 38.55 0.00
April 5334.55 03-APR-12:15 1465.40 952.89 1538.38 0.00 0.00 0.00 0.00 30.60 0.00
May 5759.29 29-MAY-17:33 0.00 428.52 615.35 0.00 0.00 0.00 0.00 37.41 0.00
June 5566.87 18-JUN-16:52 0.00 542.18 923.03 0.00 0.00 0.00 0.00 0.00 5.96
July 5567.21 17-JUL-09:00 3663.49 2259.09 3845.95 0.00 0.00 0.00 0.00 4.87 0.00
August 5186.11 14-AUG-16:00 4396.19 2710.91 4615.15 0.00 0.00 0.00 0.00 12.81 0.00
September 5508.58 11-SEP-14:52 3663.49 2259.09 3845.95 0.00 0.00 0.00 0.00 1.75 0.00
October 5472.78 10-OCT-08:20 2198.10 1521.62 2307.57 0.00 0.00 0.00 0.00 3.54 0.00
November 5504.35 06-NOV-08:50 3663.49 2493.58 3845.95 0.00 0.00 0.00 0.00 6.18 0.00
December 5510.84 26-DEC-08:42 3663.49 2569.40 3845.95 0.00 0.00 0.00 0.00 2.74 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5186.11   0.00 428.52 615.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5875.15   4396.19 2710.91 4615.15 0.00 0.00 0.00 0.00 38.55 6.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5765.57 16-JAN-17:12 0.00 387.50 547.55 0.00 0.00 0.00 0.00 0.00 13.62
February 5460.94 26-FEB-16:52 0.00 321.63 547.55 0.00 0.00 0.00 0.00 0.00 0.58
March 5314.89 19-MAR-17:02 0.00 380.68 547.55 0.00 0.00 0.00 0.00 28.76 0.00
April 5191.29 23-APR-17:22 0.00 377.04 547.55 0.00 0.00 0.00 0.00 7.21 0.00
May 5182.12 29-MAY-17:23 0.00 244.95 365.04 0.00 0.00 0.00 0.00 21.46 0.00
June 5021.46 11-JUN-17:12 0.00 285.40 456.29 0.00 0.00 0.00 0.00 18.25 0.00
July 5036.31 04-JUL-18:02 0.00 335.92 456.29 0.00 0.00 0.00 0.00 0.00 19.33
August 4978.20 27-AUG-17:42 0.00 332.37 456.29 0.00 0.00 0.00 0.00 3.51 0.00
September 5129.77 04-SEP-17:32 0.00 342.85 456.29 0.00 0.00 0.00 0.00 3.23 0.00
October 4364.74 10-OCT-07:02 2173.23 1647.81 2281.47 0.00 0.00 0.00 0.00 0.00 1.33
November 4914.36 19-NOV-16:12 0.00 268.02 456.29 0.00 0.00 0.00 0.00 2.44 0.00
December 5229.60 25-DEC-17:02 0.00 314.60 456.29 0.00 0.00 0.00 0.00 0.00 4.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4364.74   0.00 244.95 365.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5765.57   2173.23 1647.81 2281.47 0.00 0.00 0.00 0.00 28.76 19.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.53 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 815.70 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 828.52 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 716.30 0.00
May 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 626.55 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.54 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 450.74 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 706.38 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 559.54 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 319.17 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 661.05 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 556.55 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.53 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 828.52 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.176858E+11 17769.61 02-JAN-13:00 0.00 0.00 01-JAN-00:10
February 0.161198E+11 18287.69 13-FEB-15:09 0.00 0.00 01-FEB-00:10
March 0.190238E+11 18476.86 20-MAR-15:30 0.00 0.00 01-MAR-00:10
April 0.175860E+11 18427.63 11-APR-15:00 0.00 0.00 01-APR-00:10
May 0.191991E+11 18578.06 04-MAY-12:50 0.00 0.00 01-MAY-00:10
June 0.190732E+11 18811.29 12-JUN-15:20 0.00 0.00 01-JUN-00:10
July 0.172260E+11 18055.82 03-JUL-07:19 0.00 0.00 01-JUL-00:10
August 0.191427E+11 18409.14 14-AUG-12:00 0.00 0.00 01-AUG-00:10
September 0.172980E+11 18319.00 05-SEP-12:09 0.00 0.00 01-SEP-00:10
October 0.177466E+11 18066.65 16-OCT-14:30 0.00 0.00 01-OCT-00:10
November 0.175087E+11 17950.23 13-NOV-13:30 0.00 0.00 01-NOV-00:10
December 0.169093E+11 17761.79 26-DEC-11:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.214519E+12     0.00    
Minimum of Months 0.161198E+11 17761.79   0.00 0.00  
Maximum of Months 0.191991E+11 18811.29   0.00 0.00  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.293880E+10 0.122841E+10 0.443459E+10 0.00 0.181443E+10 0.01 0.00 0.537749E+10 0.00 0.00 0.00 0.189213E+10 0.00
February 0.265026E+10 0.108880E+10 0.400939E+10 0.00 0.164250E+10 0.00 0.00 0.501963E+10 0.00 0.00 0.00 0.170917E+10 0.00
March 0.306258E+10 0.116106E+10 0.468012E+10 0.00 0.198221E+10 0.00 0.00 0.622278E+10 0.00 0.00 0.00 0.191509E+10 0.00
April 0.277496E+10 0.109144E+10 0.425568E+10 0.00 0.174008E+10 0.00 0.00 0.590982E+10 0.00 0.00 0.00 0.181402E+10 0.00
May 0.298348E+10 0.110440E+10 0.455735E+10 0.00 0.193876E+10 0.00 0.00 0.672738E+10 0.00 0.00 0.00 0.188771E+10 0.00
June 0.292282E+10 0.105367E+10 0.449372E+10 0.00 0.193280E+10 0.00 0.00 0.684096E+10 0.00 0.00 0.00 0.182924E+10 0.00
July 0.283643E+10 0.109937E+10 0.431556E+10 0.00 0.172522E+10 0.00 0.00 0.539410E+10 0.00 0.00 0.00 0.185536E+10 0.00
August 0.304721E+10 0.111636E+10 0.468012E+10 0.00 0.198149E+10 0.00 0.00 0.642095E+10 0.00 0.00 0.00 0.189652E+10 0.00
September 0.279790E+10 0.111410E+10 0.424819E+10 0.00 0.173579E+10 0.00 0.00 0.559209E+10 0.00 0.00 0.00 0.180996E+10 0.00
October 0.292616E+10 0.118749E+10 0.443833E+10 0.00 0.180925E+10 0.00 0.00 0.550390E+10 0.00 0.00 0.00 0.188145E+10 0.00
November 0.289805E+10 0.118312E+10 0.437470E+10 0.00 0.180158E+10 0.00 0.00 0.541512E+10 0.00 0.00 0.00 0.183612E+10 0.00
December 0.287044E+10 0.123807E+10 0.431182E+10 0.00 0.172564E+10 0.00 0.00 0.488424E+10 0.00 0.00 0.00 0.187908E+10 0.00
                           
Annual Sum or Average 0.347091E+11 0.136663E+11 0.527996E+11 0.00 0.218298E+11 0.01 0.00 0.693085E+11 0.00 0.00 0.00 0.222058E+11 0.00
Minimum of Months 0.265026E+10 0.105367E+10 0.400939E+10 0.00 0.164250E+10 0.00 0.00 0.488424E+10 0.00 0.00 0.00 0.170917E+10 0.00
Maximum of Months 0.306258E+10 0.123807E+10 0.468012E+10 0.00 0.198221E+10 0.01 0.00 0.684096E+10 0.00 0.00 0.00 0.191509E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2606.16 02-JAN-16:00 1049.11 01-JAN-06:10 3465.65 02-JAN-08:09 0.00 1822.78 02-JAN-08:09 0.00 02-JAN-07:10 0.00 01-JAN-00:10
February 2523.85 07-FEB-16:00 1049.11 01-FEB-06:10 3465.65 01-FEB-08:09 0.00 1822.78 01-FEB-07:00 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 2566.86 01-MAR-16:00 1049.11 01-MAR-06:10 3465.65 01-MAR-08:09 0.00 1822.78 01-MAR-08:09 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 2510.77 21-APR-07:10 1049.11 01-APR-05:10 3465.65 03-APR-07:10 0.00 1822.78 03-APR-16:30 0.00 01-APR-00:10 0.00 01-APR-00:10
May 2533.96 17-MAY-07:10 1049.11 01-MAY-05:10 3465.65 01-MAY-07:10 0.00 1822.78 01-MAY-07:19 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 2515.25 20-JUN-07:10 1049.11 01-JUN-05:10 3465.65 01-JUN-07:10 0.00 1822.78 01-JUN-07:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2521.75 11-JUL-07:10 1049.11 01-JUL-05:10 3465.65 03-JUL-07:10 0.00 1822.78 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2522.79 21-AUG-07:10 1049.11 01-AUG-05:10 3465.65 01-AUG-07:10 0.00 1822.78 01-AUG-07:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2510.66 21-SEP-07:10 1049.11 01-SEP-05:10 3465.65 01-SEP-07:10 0.00 1822.78 01-SEP-07:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2540.21 23-OCT-07:10 1049.11 01-OCT-05:10 3465.65 02-OCT-07:10 0.00 1822.78 02-OCT-05:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 2623.26 09-NOV-16:00 1049.11 01-NOV-05:10 3465.65 01-NOV-07:10 0.00 1822.78 01-NOV-07:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 2631.77 18-DEC-16:00 1049.11 01-DEC-17:30 3465.65 01-DEC-08:09 0.00 1822.78 01-DEC-07:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2510.66   1049.11   3465.65   0.00 1822.78   0.00   0.00  
Maximum of Months 2631.77   1049.11   3465.65   0.00 1822.78   0.00   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 7505.02 11-JAN-08:09 0.00 0.00 0.00 2747.09 11-JAN-12:39 0.00
February 8002.35 21-FEB-13:00 0.00 0.00 0.00 2746.85 02-FEB-12:30 0.00
March 8227.17 20-MAR-14:00 0.00 0.00 0.00 2745.84 01-MAR-12:30 0.00
April 8164.13 17-APR-14:00 0.00 0.00 0.00 2743.56 06-APR-11:50 0.00
May 8355.79 01-MAY-11:00 0.00 0.00 0.00 2741.58 02-MAY-11:30 0.00
June 8540.83 12-JUN-14:00 0.00 0.00 0.00 2739.67 01-JUN-11:20 0.00
July 7801.31 17-JUL-12:00 0.00 0.00 0.00 2739.08 26-JUL-11:20 0.00
August 8145.38 14-AUG-12:00 0.00 0.00 0.00 2740.19 31-AUG-11:39 0.00
September 8050.50 06-SEP-14:09 0.00 0.00 0.00 2742.06 29-SEP-11:30 0.00
October 7822.52 16-OCT-14:20 0.00 0.00 0.00 2744.18 31-OCT-11:09 0.00
November 7680.76 13-NOV-13:00 0.00 0.00 0.00 2745.90 28-NOV-12:09 0.00
December 7533.81 11-DEC-13:09 0.00 0.00 0.00 2746.93 27-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 7505.02   0.00 0.00 0.00 2739.08   0.00
Maximum of Months 8540.83   0.00 0.00 0.00 2747.09   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17769.61 02-JAN-13:00 2302.10 3465.65 0.00 0.00 1822.78 0.00 0.00 7441.03 0.00
February 18287.69 13-FEB-15:09 2295.91 3465.65 0.00 0.00 1822.78 0.00 0.00 7999.28 0.00
March 18476.86 20-MAR-15:30 2262.27 3465.65 0.00 0.00 1822.78 0.00 0.00 8206.96 0.00
April 18427.63 11-APR-15:00 2291.80 3465.65 0.00 0.00 1822.78 0.00 0.00 8128.88 0.00
May 18578.06 04-MAY-12:50 2287.02 3465.65 0.00 0.00 1822.78 0.00 0.00 8269.49 0.00
June 18811.29 12-JUN-15:20 2288.25 3465.65 0.00 0.00 1822.78 0.00 0.00 8518.95 0.00
July 18055.82 03-JUL-07:19 2469.97 3465.65 0.00 0.00 1822.78 0.00 0.00 7597.33 0.00
August 18409.14 14-AUG-12:00 2244.18 3465.65 0.00 0.00 1822.78 0.00 0.00 8145.38 0.00
September 18319.00 05-SEP-12:09 2269.44 3465.65 0.00 0.00 1822.78 0.00 0.00 8028.91 0.00
October 18066.65 16-OCT-14:30 2253.91 3465.65 0.00 0.00 1822.78 0.00 0.00 7821.91 0.00
November 17950.23 13-NOV-13:30 2280.72 3465.65 0.00 0.00 1822.78 0.00 0.00 7644.68 0.00
December 17761.79 26-DEC-11:00 2281.85 3465.65 0.00 0.00 1822.78 0.00 0.00 7461.90 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 17761.79   2244.18 3465.65 0.00 0.00 1822.78 0.00 0.00 7441.03 0.00
Maximum of Months 18811.29   2469.97 3465.65 0.00 0.00 1822.78 0.00 0.00 8518.95 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 46.83 24.96 46.33 24.93
February 0.00 0.00 0.00 0.00 44.83 24.83 44.83 24.83
March 0.00 0.00 0.00 0.00 58.33 24.92 58.33 24.92
April 0.00 0.00 0.00 0.00 102.50 25.01 102.50 25.01
May 0.00 0.00 0.00 0.00 161.67 25.20 161.50 25.20
June 0.00 0.00 0.00 0.00 179.67 25.23 179.67 25.23
July 0.00 0.00 0.00 0.00 67.67 24.98 67.67 24.98
August 0.00 0.00 0.00 0.00 120.67 25.00 120.67 25.00
September 0.00 0.00 0.00 0.00 92.67 25.09 92.67 25.09
October 0.00 0.00 0.00 0.00 70.00 25.05 69.33 25.03
November 0.00 0.00 0.00 0.00 47.50 24.86 47.50 24.86
December 0.00 0.00 0.00 0.00 29.83 24.82 29.83 24.82
                 
Annual Sum or Average 0.00   0.00   1022.17 25.06 1020.83 25.06
Minimum of Months 0.00 0.00 0.00 0.00 29.83 24.82 29.83 24.82
Maximum of Months 0.00 0.00 0.00 0.00 179.67 25.23 179.67 25.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 71.33 25.24 66.00 25.05
February 0.00 0.00 0.00 0.00 58.33 25.12 55.33 24.99
March 0.00 0.00 0.00 0.00 30.50 24.73 30.50 24.73
April 0.00 0.00 0.00 0.00 67.33 24.84 67.33 24.84
May 0.00 0.00 0.00 0.00 133.67 25.19 130.83 25.13
June 0.00 0.00 0.00 0.00 148.00 25.22 146.00 25.18
July 0.00 0.00 0.00 0.00 28.33 24.76 28.33 24.76
August 0.00 0.00 0.00 0.00 75.17 25.00 75.17 25.00
September 0.00 0.00 0.00 0.00 64.17 24.93 64.17 24.93
October 0.00 0.00 0.00 0.00 47.50 24.87 47.33 24.86
November 0.00 0.00 0.00 0.00 61.83 25.03 60.00 24.96
December 0.00 0.00 0.00 0.00 63.17 25.43 56.17 25.16
                 
Annual Sum or Average 0.00   0.00   849.33 25.09 827.17 25.02
Minimum of Months 0.00 0.00 0.00 0.00 28.33 24.73 28.33 24.73
Maximum of Months 0.00 0.00 0.00 0.00 148.00 25.43 146.00 25.18



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.50 25.20 1.33 24.91
February 0.00 0.00 0.00 0.00 4.67 26.95 2.67 26.10
March 0.00 0.00 0.00 0.00 10.00 26.70 5.67 25.94
April 0.00 0.00 0.00 0.00 20.50 26.38 12.50 25.75
May 0.00 0.00 0.00 0.00 39.67 26.12 23.00 25.71
June 0.00 0.00 0.00 0.00 39.67 25.59 27.17 25.30
July 0.00 0.00 0.00 0.00 3.67 25.62 3.00 25.18
August 0.00 0.00 0.00 0.00 21.50 25.70 13.67 25.36
September 0.00 0.00 0.00 0.00 18.67 26.30 10.17 25.81
October 0.00 0.00 0.00 0.00 4.17 25.91 3.17 25.35
November 0.00 0.00 0.00 0.00 3.50 24.67 3.50 24.67
December 0.00 0.00 0.00 0.00 1.00 25.54 0.83 25.13
                 
Annual Sum or Average 0.00   0.00   168.50 25.99 106.67 25.54
Minimum of Months 0.00 0.00 0.00 0.00 1.00 24.67 0.83 24.67
Maximum of Months 0.00 0.00 0.00 0.00 39.67 26.95 27.17 26.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.00 24.63 2.00 24.63
February 0.00 0.00 0.00 0.00 1.17 24.63 1.17 24.63
March 0.00 0.00 0.00 0.00 4.33 24.68 4.33 24.68
April 0.00 0.00 0.00 0.00 8.83 24.80 8.83 24.80
May 0.00 0.00 0.00 0.00 51.50 25.26 48.17 25.10
June 0.00 0.00 0.00 0.00 89.50 25.10 85.67 24.99
July 0.00 0.00 0.00 0.00 6.00 24.84 6.00 24.84
August 0.00 0.00 0.00 0.00 25.83 24.84 25.83 24.84
September 0.00 0.00 0.00 0.00 19.50 24.72 19.50 24.72
October 0.00 0.00 0.00 0.00 5.83 24.82 5.83 24.82
November 0.00 0.00 0.00 0.00 2.83 24.71 2.83 24.71
December 0.00 0.00 0.00 0.00 1.00 24.70 1.00 24.70
                 
Annual Sum or Average 0.00   0.00   218.33 25.03 211.17 24.94
Minimum of Months 0.00 0.00 0.00 0.00 1.00 24.63 1.00 24.63
Maximum of Months 0.00 0.00 0.00 0.00 89.50 25.26 85.67 25.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.83 30.15 0.00 30.15
February 0.00 0.00 0.00 0.00 3.50 30.22 0.00 30.22
March 0.00 0.00 0.00 0.00 6.83 30.21 0.00 30.21
April 0.00 0.00 0.00 0.00 9.33 30.02 0.33 29.83
May 0.00 0.00 0.00 0.00 10.17 29.63 1.17 29.11
June 0.00 0.00 0.00 0.00 9.33 29.57 1.17 29.01
July 0.00 0.00 0.00 0.00 2.33 30.12 0.00 30.12
August 0.00 0.00 0.00 0.00 5.17 29.81 0.33 29.49
September 0.00 0.00 0.00 0.00 6.00 29.75 0.50 29.34
October 0.00 0.00 0.00 0.00 1.67 30.05 0.00 30.05
November 0.00 0.00 0.00 0.00 0.83 30.13 0.00 30.13
December 0.00 0.00 0.00 0.00 2.67 30.10 0.00 30.10
                 
Annual Sum or Average 0.00   0.00   60.67 29.89 3.50 29.60
Minimum of Months 0.00 0.00 0.00 0.00 0.83 29.57 0.00 29.01
Maximum of Months 0.00 0.00 0.00 0.00 10.17 30.22 1.17 30.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 109.33 27.02 357.00 25.68 109.33 25.93
February 103.50 27.05 323.00 25.71 103.50 25.98
March 139.83 27.03 391.00 25.77 139.83 26.04
April 136.00 27.22 340.00 26.09 136.00 26.34
May 177.33 27.11 374.00 26.28 177.33 26.48
June 176.17 27.24 374.00 26.40 176.17 26.61
July 130.17 27.07 340.00 25.88 130.17 26.14
August 171.17 26.91 391.00 25.97 171.17 26.19
September 146.33 26.94 340.00 25.97 146.33 26.19
October 143.67 26.85 357.00 25.79 143.67 26.03
November 137.67 26.78 357.00 25.66 137.67 25.91
December 103.83 26.77 340.00 25.51 103.83 25.75
             
Annual Sum or Average 1675.00 27.01 4284.00 25.91 1675.00 26.15
Minimum of Months 103.50 26.77 323.00 25.51 103.50 25.75
Maximum of Months 177.33 27.24 391.00 26.40 177.33 26.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 154.00 27.19 357.00 26.03 154.00 26.30
February 138.00 27.22 323.00 26.02 138.00 26.30
March 168.67 27.02 391.00 25.85 168.67 26.12
April 173.50 26.95 340.00 26.06 173.50 26.29
May 233.67 26.70 374.00 26.17 233.67 26.32
June 240.83 26.81 374.00 26.30 240.83 26.45
July 164.67 26.82 340.00 25.86 164.67 26.09
August 231.50 26.46 391.00 25.86 231.50 26.02
September 194.33 26.51 340.00 25.87 194.33 26.04
October 196.67 26.39 357.00 25.72 196.67 25.89
November 177.00 26.70 357.00 25.85 177.00 26.06
December 142.50 26.94 340.00 25.87 142.50 26.11
             
Annual Sum or Average 2215.33 26.78 4284.00 25.96 2215.33 26.17
Minimum of Months 138.00 26.39 323.00 25.72 138.00 25.89
Maximum of Months 240.83 27.22 391.00 26.30 240.83 26.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 117.33 27.05 294.00 25.90 117.33 26.16
February 118.33 27.20 266.00 26.03 118.33 26.31
March 150.67 27.21 322.00 26.10 150.67 26.37
April 139.33 27.43 280.00 26.29 139.33 26.58
May 161.83 27.25 308.00 26.26 161.83 26.51
June 160.50 27.45 308.00 26.40 160.50 26.67
July 136.00 27.29 280.00 26.16 136.00 26.43
August 162.17 27.13 322.00 26.12 162.17 26.37
September 139.00 27.16 280.00 26.12 139.00 26.38
October 143.67 26.88 294.00 25.91 143.67 26.15
November 137.00 26.87 294.00 25.87 137.00 26.11
December 105.17 26.84 280.00 25.74 105.17 25.98
             
Annual Sum or Average 1671.00 27.16 3528.00 26.08 1671.00 26.34
Minimum of Months 105.17 26.84 266.00 25.74 105.17 25.98
Maximum of Months 162.17 27.45 322.00 26.40 162.17 26.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 103.67 26.86 357.00 25.50 103.67 25.75
February 104.50 27.00 323.00 25.60 104.50 25.88
March 145.17 27.07 391.00 25.72 145.17 26.01
April 138.50 27.32 340.00 25.93 138.50 26.25
May 156.00 27.33 374.00 26.03 156.00 26.33
June 160.00 27.57 374.00 26.26 160.00 26.56
July 134.50 27.30 340.00 25.88 134.50 26.20
August 160.67 27.05 391.00 25.81 160.67 26.09
September 136.83 27.07 340.00 25.80 136.83 26.08
October 142.83 26.79 357.00 25.61 142.83 25.87
November 134.83 26.72 357.00 25.53 134.83 25.78
December 95.67 26.58 340.00 25.35 95.67 25.57
             
Annual Sum or Average 1613.17 27.08 4284.00 25.76 1613.17 26.05
Minimum of Months 95.67 26.58 323.00 25.35 95.67 25.57
Maximum of Months 160.67 27.57 391.00 26.26 160.67 26.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 136.50 27.30 357.00 25.83 136.50 26.15
February 125.50 27.48 323.00 25.94 125.50 26.28
March 158.50 27.63 391.00 26.08 158.50 26.42
April 140.33 27.86 340.00 26.23 140.33 26.60
May 158.17 27.53 374.00 26.07 158.17 26.40
June 156.50 27.80 374.00 26.21 156.50 26.57
July 137.83 27.55 340.00 26.03 137.83 26.37
August 163.50 27.38 391.00 25.97 163.50 26.29
September 139.67 27.36 340.00 25.94 139.67 26.26
October 147.33 27.10 357.00 25.79 147.33 26.09
November 141.67 27.02 357.00 25.72 141.67 26.00
December 115.83 26.99 340.00 25.62 115.83 25.90
             
Annual Sum or Average 1721.33 27.43 4284.00 25.96 1721.33 26.28
Minimum of Months 115.83 26.99 323.00 25.62 115.83 25.90
Maximum of Months 163.50 27.86 391.00 26.23 163.50 26.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.580502E+10 0.127861E+10 249.80 0.415091E+10 0.165411E+10 0.00 1.00 02-JAN-06:02 0.00 01-JAN-00:10 8326.06 11-JAN-07:01 6124.71 02-JAN-06:02 3851.23 12-JAN-07:05 1763.14 04-JAN-13:00 0.00
February 0.525143E+10 0.117113E+10 218.77 0.376397E+10 0.148746E+10 0.00 1.00 01-FEB-07:02 0.00 01-FEB-00:10 8394.08 16-FEB-07:02 6127.86 21-FEB-14:00 4137.77 16-FEB-07:07 1791.41 28-FEB-14:15 0.00
March 0.650171E+10 0.145779E+10 266.12 0.455622E+10 0.194549E+10 0.00 1.00 01-MAR-07:02 0.00 01-MAR-00:10 8401.31 24-MAR-06:02 5915.42 21-MAR-13:00 4130.76 24-MAR-06:07 1816.94 21-MAR-13:00 0.00
April 0.605584E+10 0.133816E+10 238.94 0.400223E+10 0.205361E+10 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 8447.99 11-APR-05:03 5589.83 05-APR-14:53 4269.43 21-APR-06:07 1795.70 26-APR-14:00 0.00
May 0.695557E+10 0.150546E+10 271.67 0.429304E+10 0.266252E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:05 8475.64 18-MAY-06:02 5476.78 01-MAY-11:55 4861.40 19-MAY-06:10 1844.12 05-MAY-12:00 0.00
June 0.697567E+10 0.151559E+10 272.51 0.431171E+10 0.266396E+10 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 8473.18 30-JUN-06:02 5623.97 19-JUN-05:02 4641.92 29-JUN-06:07 1824.25 16-JUN-13:40 0.00
July 0.589011E+10 0.126505E+10 232.44 0.389307E+10 0.199705E+10 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 8417.93 28-JUL-06:02 5514.26 31-JUL-12:55 4229.26 28-JUL-06:07 1748.10 28-JUL-13:00 0.00
August 0.699667E+10 0.149104E+10 268.44 0.424582E+10 0.275086E+10 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 8475.83 04-AUG-06:02 5187.95 30-AUG-12:20 4827.09 25-AUG-06:08 1775.95 22-AUG-15:00 0.00
September 0.605292E+10 0.129428E+10 236.53 0.376777E+10 0.228515E+10 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 8471.00 15-SEP-06:02 5420.55 05-SEP-05:02 4479.58 01-SEP-06:07 1775.13 06-SEP-14:00 0.00
October 0.620697E+10 0.131821E+10 245.36 0.388766E+10 0.231931E+10 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 8472.26 26-OCT-06:02 5407.94 10-OCT-05:02 4596.14 26-OCT-06:07 1749.59 04-OCT-13:55 0.00
November 0.599951E+10 0.129328E+10 241.04 0.393967E+10 0.205984E+10 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 8417.75 16-NOV-07:02 5761.04 24-NOV-11:30 4229.56 10-NOV-07:05 1727.27 13-NOV-14:00 0.00
December 0.527308E+10 0.115650E+10 224.95 0.370283E+10 0.157024E+10 0.00 1.00 01-DEC-07:02 0.00 01-DEC-00:10 8306.76 11-DEC-06:02 5888.17 26-DEC-11:53 4103.23 01-DEC-07:04 1723.76 12-DEC-13:55 0.00
                                       
Annual Sum or Average 0.739645E+11 0.160851E+11 2966.57 0.485149E+11 0.254496E+11 0.00                         0.00
Minimum of Months 0.525143E+10 0.115650E+10 218.77 0.370283E+10 0.148746E+10 0.00 1.00   0.00   8306.76   5187.95   3851.23   1723.76   0.00
Maximum of Months 0.699667E+10 0.151559E+10 272.51 0.455622E+10 0.275086E+10 0.00 1.00   0.00   8475.83   6127.86   4861.40   1844.12   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.646747E+10 0.142882E+10 282.42 0.485884E+10 0.160863E+10 0.00 1.00 02-JAN-06:02 0.00 01-JAN-00:10 8967.38 10-JAN-07:02 7654.09 16-JAN-15:32 4567.68 10-JAN-07:13 1875.95 04-JAN-13:10 0.00
February 0.572735E+10 0.128436E+10 246.16 0.429079E+10 0.143655E+10 0.00 1.00 01-FEB-07:02 0.00 01-FEB-00:10 8968.19 15-FEB-07:01 7061.14 20-FEB-16:02 4797.87 16-FEB-07:13 1894.21 28-FEB-14:00 0.00
March 0.661024E+10 0.149758E+10 276.86 0.473443E+10 0.187580E+10 0.00 1.00 01-MAR-07:02 0.00 01-MAR-00:10 8969.85 13-MAR-05:02 6549.59 19-MAR-16:12 4898.52 24-MAR-06:05 1913.58 21-MAR-13:00 0.00
April 0.633265E+10 0.141091E+10 255.24 0.424717E+10 0.208548E+10 0.00 1.00 02-APR-16:32 0.00 01-APR-00:10 8970.05 24-APR-05:02 6054.61 03-APR-16:00 5015.59 21-APR-06:13 1895.03 11-APR-14:00 0.00
May 0.737824E+10 0.160945E+10 298.47 0.459025E+10 0.278799E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:10 8973.91 09-MAY-05:02 6448.66 29-MAY-16:33 5756.24 19-MAY-06:07 1956.26 05-MAY-12:00 0.00
June 0.738873E+10 0.161733E+10 296.81 0.459856E+10 0.279017E+10 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 8974.37 21-JUN-06:03 6017.93 18-JUN-16:42 5545.30 29-JUN-06:07 1931.34 16-JUN-13:00 0.00
July 0.597201E+10 0.129467E+10 241.79 0.401608E+10 0.195593E+10 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 8973.76 07-JUL-06:02 6043.90 31-JUL-13:40 4861.54 28-JUL-06:05 1855.28 26-JUL-17:00 0.00
August 0.721408E+10 0.154906E+10 277.84 0.441410E+10 0.279998E+10 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 8973.42 30-AUG-06:03 5710.05 30-AUG-11:10 5674.28 25-AUG-06:07 1877.48 10-AUG-14:00 0.00
September 0.627683E+10 0.135244E+10 251.49 0.395227E+10 0.232456E+10 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 8973.60 19-SEP-06:03 5944.50 05-SEP-15:20 5288.73 01-SEP-06:07 1874.69 06-SEP-14:00 0.00
October 0.638387E+10 0.136684E+10 261.34 0.405415E+10 0.232972E+10 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 8974.30 31-OCT-06:02 5907.23 02-OCT-11:03 5310.09 26-OCT-06:05 1847.62 04-OCT-13:55 0.00
November 0.648979E+10 0.140356E+10 263.01 0.442744E+10 0.206235E+10 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 8973.80 29-NOV-07:02 6637.29 19-NOV-15:32 4875.49 09-NOV-07:05 1830.20 13-NOV-13:10 0.00
December 0.602872E+10 0.132331E+10 259.65 0.447204E+10 0.155669E+10 0.00 1.00 01-DEC-07:02 0.00 01-DEC-00:10 8944.60 12-DEC-07:02 7234.58 03-DEC-15:23 4519.25 12-DEC-07:12 1837.66 08-DEC-14:00 0.00
                                       
Annual Sum or Average 0.782700E+11 0.171383E+11 3211.06 0.526561E+11 0.256138E+11 0.00                         0.00
Minimum of Months 0.572735E+10 0.128436E+10 241.79 0.395227E+10 0.143655E+10 0.00 1.00   0.00   8944.60   5710.05   4519.25   1830.20   0.00
Maximum of Months 0.738873E+10 0.161733E+10 298.47 0.485884E+10 0.279998E+10 0.00 1.00   0.00   8974.37   7654.09   5756.24   1956.26   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.330355E+10 0.756590E+09 255.99 0.265446E+10 0.649086E+09 0.00 1.00 02-JAN-06:02 0.00 01-JAN-00:10 6138.23 09-JAN-06:02 4441.53 17-JAN-08:48 2796.07 10-JAN-07:03 1212.51 11-JAN-08:62 0.00
February 0.318549E+10 0.736867E+09 244.74 0.258482E+10 0.600672E+09 0.00 1.00 01-FEB-07:02 0.00 01-FEB-00:10 6132.69 16-FEB-07:02 4797.73 21-FEB-06:02 2918.29 16-FEB-07:03 1223.55 21-FEB-14:00 0.00
March 0.400898E+10 0.932527E+09 297.01 0.317626E+10 0.832718E+09 0.00 1.00 01-MAR-07:02 0.00 01-MAR-00:10 6135.12 13-MAR-05:02 4656.44 20-MAR-10:12 3061.97 24-MAR-06:05 1283.26 20-MAR-13:00 0.00
April 0.394874E+10 0.907911E+09 288.69 0.300399E+10 0.944748E+09 0.00 1.00 02-APR-09:32 0.00 01-APR-00:10 6135.26 24-APR-05:02 4600.47 09-APR-12:21 3057.63 21-APR-06:05 1283.43 17-APR-09:52 0.00
May 0.448392E+10 0.101950E+10 327.13 0.322961E+10 0.125430E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:25 6137.90 09-MAY-05:02 4813.54 29-MAY-16:23 3624.90 19-MAY-06:07 1315.96 04-MAY-13:00 0.00
June 0.458115E+10 0.104318E+10 316.37 0.332088E+10 0.126027E+10 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 6138.22 21-JUN-06:02 4447.43 18-JUN-16:42 3469.99 29-JUN-06:05 1313.83 13-JUN-15:00 0.00
July 0.353397E+10 0.791029E+09 264.14 0.268765E+10 0.846322E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 6135.46 24-JUL-05:02 4407.08 05-JUL-09:00 2963.46 28-JUL-06:05 1214.25 17-JUL-13:00 0.00
August 0.427846E+10 0.954687E+09 291.12 0.304550E+10 0.123296E+10 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 6137.57 04-AUG-06:05 4353.38 28-AUG-10:00 3566.16 25-AUG-06:05 1274.63 14-AUG-13:00 0.00
September 0.372645E+10 0.833812E+09 270.80 0.270942E+10 0.101703E+10 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 6137.57 18-SEP-06:02 4493.47 04-SEP-16:12 3227.06 21-SEP-06:03 1261.20 05-SEP-13:00 0.00
October 0.356532E+10 0.793074E+09 265.09 0.257285E+10 0.992464E+09 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 6138.02 23-OCT-06:02 4359.34 02-OCT-09:00 3205.40 26-OCT-06:03 1214.04 16-OCT-09:52 0.00
November 0.339175E+10 0.763819E+09 249.73 0.255012E+10 0.841634E+09 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 6137.88 20-NOV-06:02 4474.00 06-NOV-09:22 3198.14 13-NOV-06:03 1189.96 14-NOV-08:23 0.00
December 0.299452E+10 0.683409E+09 239.98 0.237615E+10 0.618366E+09 0.00 1.00 01-DEC-07:02 0.00 01-DEC-00:10 6138.12 11-DEC-06:02 4463.77 26-DEC-09:08 2743.61 11-DEC-06:02 1175.35 08-DEC-08:11 0.00
                                       
Annual Sum or Average 0.450023E+11 0.102164E+11 3310.80 0.339117E+11 0.110906E+11 0.00                         0.00
Minimum of Months 0.299452E+10 0.683409E+09 239.98 0.237615E+10 0.600672E+09 0.00 1.00   0.00   6132.69   4353.38   2743.61   1175.35   0.00
Maximum of Months 0.458115E+10 0.104318E+10 327.13 0.332088E+10 0.126027E+10 0.00 1.00   0.00   6138.23   4813.54   3624.90   1315.96   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.489989E+10 0.111797E+10 239.77 0.375974E+10 0.114015E+10 0.00 1.00 02-JAN-06:02 0.00 01-JAN-00:10 8956.78 09-JAN-06:02 6299.57 02-JAN-12:05 4357.36 10-JAN-07:05 1769.37 11-JAN-08:62 0.00
February 0.460249E+10 0.106284E+10 221.53 0.356203E+10 0.104046E+10 0.00 1.00 01-FEB-07:02 0.00 01-FEB-00:10 8944.65 16-FEB-07:02 6640.03 21-FEB-14:00 4504.12 16-FEB-07:05 1841.73 21-FEB-14:00 0.00
March 0.586018E+10 0.135740E+10 273.27 0.442715E+10 0.143302E+10 0.00 1.00 01-MAR-07:02 0.00 01-MAR-00:10 8952.24 13-MAR-05:02 6526.25 20-MAR-12:05 4644.19 24-MAR-06:05 1875.30 20-MAR-15:00 0.00
April 0.573347E+10 0.130989E+10 255.20 0.414538E+10 0.158809E+10 0.00 1.00 02-APR-16:12 0.00 01-APR-00:10 8952.44 24-APR-05:02 6216.36 03-APR-12:10 4692.13 21-APR-06:05 1875.60 17-APR-10:00 0.00
May 0.683081E+10 0.153333E+10 301.60 0.469510E+10 0.213571E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:10 8956.29 09-MAY-05:02 6596.39 29-MAY-16:53 5536.69 22-MAY-05:05 1929.78 05-MAY-12:10 0.00
June 0.703064E+10 0.158140E+10 306.21 0.486622E+10 0.216442E+10 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 8956.29 26-JUN-05:02 6258.71 18-JUN-14:13 5219.34 29-JUN-06:07 1923.30 13-JUN-15:00 0.00
July 0.553313E+10 0.122461E+10 250.13 0.404408E+10 0.148904E+10 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 8952.73 24-JUL-05:04 6279.82 31-JUL-13:00 4519.41 28-JUL-06:05 1816.77 31-JUL-14:00 0.00
August 0.651134E+10 0.143846E+10 277.64 0.439524E+10 0.211610E+10 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 8955.81 04-AUG-06:02 5954.99 14-AUG-13:00 5379.91 25-AUG-06:07 1863.81 14-AUG-13:00 0.00
September 0.562835E+10 0.124671E+10 249.89 0.388952E+10 0.173883E+10 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 8955.81 18-SEP-06:02 6116.14 05-SEP-15:00 4942.22 25-SEP-05:04 1860.49 06-SEP-14:00 0.00
October 0.545717E+10 0.120154E+10 246.53 0.374905E+10 0.170812E+10 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 8956.47 23-OCT-06:02 6117.20 10-OCT-13:00 4952.24 16-OCT-05:04 1814.09 16-OCT-14:00 0.00
November 0.517473E+10 0.115625E+10 239.67 0.370798E+10 0.146675E+10 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 8956.44 06-NOV-06:02 6110.19 20-NOV-11:53 4891.76 13-NOV-06:03 1772.52 13-NOV-14:00 0.00
December 0.442365E+10 0.100529E+10 223.11 0.334878E+10 0.107487E+10 0.00 1.00 01-DEC-07:02 0.00 01-DEC-00:10 8956.61 11-DEC-06:02 6024.03 26-DEC-11:53 4621.00 11-DEC-06:02 1749.89 11-DEC-13:10 0.00
                                       
Annual Sum or Average 0.676858E+11 0.152357E+11 3084.55 0.485903E+11 0.190956E+11 0.00                         0.00
Minimum of Months 0.442365E+10 0.100529E+10 221.53 0.334878E+10 0.104046E+10 0.00 1.00   0.00   8944.65   5954.99   4357.36   1749.89   0.00
Maximum of Months 0.703064E+10 0.158140E+10 306.21 0.486622E+10 0.216442E+10 0.00 1.00   0.00   8956.78   6640.03   5536.69   1929.78   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.341139E+10 0.795490E+09 265.76 0.273599E+10 0.675404E+09 0.00 1.00 02-JAN-06:02 0.00 01-JAN-00:10 7272.94 09-JAN-06:02 6250.18 16-JAN-17:12 3242.81 10-JAN-07:03 1439.76 11-JAN-08:62 0.00
February 0.323665E+10 0.764432E+09 249.07 0.261687E+10 0.619782E+09 0.00 1.00 01-FEB-07:02 0.00 01-FEB-00:10 7266.73 16-FEB-07:02 5997.30 20-FEB-17:32 3349.27 16-FEB-07:03 1489.08 20-FEB-16:12 0.00
March 0.412397E+10 0.977477E+09 307.63 0.325569E+10 0.868278E+09 0.00 1.00 01-MAR-07:02 0.00 01-MAR-00:10 7278.60 24-MAR-06:02 5943.70 19-MAR-16:21 3419.82 24-MAR-06:03 1545.80 19-MAR-15:02 0.00
April 0.401688E+10 0.942946E+09 291.29 0.304414E+10 0.972732E+09 0.00 1.00 01-APR-15:53 0.00 01-APR-00:10 7285.07 10-APR-05:02 5724.57 23-APR-17:22 3538.76 21-APR-06:03 1535.12 02-APR-15:02 0.00
May 0.457009E+10 0.105965E+10 321.34 0.329381E+10 0.127627E+10 0.00 1.00 01-MAY-05:02 0.00 01-MAY-00:05 7288.67 17-MAY-06:02 5932.40 29-MAY-17:23 4259.25 22-MAY-05:03 1546.30 06-MAY-15:43 0.00
June 0.465700E+10 0.108347E+10 316.48 0.337081E+10 0.128619E+10 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 7284.87 21-JUN-06:02 5583.00 11-JUN-17:12 4087.75 29-JUN-06:05 1551.45 12-JUN-15:00 0.00
July 0.358702E+10 0.818743E+09 273.92 0.272063E+10 0.866384E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 7271.85 28-JUL-06:02 5528.89 04-JUL-18:02 3378.93 28-JUL-06:03 1446.03 04-JUL-16:42 0.00
August 0.433808E+10 0.987708E+09 301.69 0.307272E+10 0.126535E+10 0.00 1.00 01-AUG-06:02 0.00 01-AUG-00:10 7288.40 04-AUG-06:03 5579.78 27-AUG-17:03 4161.69 25-AUG-06:05 1493.52 27-AUG-16:23 0.00
September 0.379067E+10 0.864844E+09 277.46 0.275016E+10 0.104051E+10 0.00 1.00 01-SEP-06:02 0.00 01-SEP-00:10 7288.40 18-SEP-06:03 5669.04 04-SEP-17:32 3751.97 21-SEP-06:03 1496.42 04-SEP-16:12 0.00
October 0.364166E+10 0.824237E+09 272.76 0.262548E+10 0.101619E+10 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7288.94 23-OCT-06:02 4838.90 10-OCT-05:02 3700.55 26-OCT-06:03 1416.51 05-OCT-07:12 0.00
November 0.348323E+10 0.798209E+09 255.84 0.261700E+10 0.866229E+09 0.00 1.00 01-NOV-06:02 0.00 01-NOV-00:10 7284.81 13-NOV-06:03 5514.68 19-NOV-16:12 3771.30 13-NOV-06:03 1448.29 19-NOV-16:12 0.00
December 0.308483E+10 0.715730E+09 244.07 0.244198E+10 0.642854E+09 0.00 1.00 01-DEC-07:02 0.00 01-DEC-00:10 7289.05 11-DEC-06:02 5781.23 25-DEC-17:02 3170.57 18-DEC-07:03 1428.60 25-DEC-17:02 0.00
                                       
Annual Sum or Average 0.459415E+11 0.106329E+11 3377.31 0.345453E+11 0.113962E+11 0.00                         0.00
Minimum of Months 0.308483E+10 0.715730E+09 244.07 0.244198E+10 0.619782E+09 0.00 1.00   0.00   7266.73   4838.90   3170.57   1416.51   0.00
Maximum of Months 0.465700E+10 0.108347E+10 321.34 0.337081E+10 0.128619E+10 0.00 1.00   0.00   7289.05   6250.18   4259.25   1551.45   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.85 12.18 0.00 0.00 0.00
March 22.62 0.17 22.46 48.02 8.97 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.43 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.94 8.57 0.00 0.00 0.00
September 22.50 0.16 22.34 44.24 8.77 0.00 0.00 0.00
October 26.62 2.56 24.07 49.67 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.77 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.30 5.45 24.85 58.94 10.14 0.00 0.00 0.00
Minimum of Months 22.50 0.00 22.34 43.94 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.84 12.18 0.00 0.00 0.00
March 22.39 0.09 22.30 47.48 8.97 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.42 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.93 8.57 0.00 0.00 0.00
September 22.49 0.16 22.32 44.21 8.77 0.00 0.00 0.00
October 26.60 2.55 24.05 49.63 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.76 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.28 5.44 24.83 58.89 10.14 0.00 0.00 0.00
Minimum of Months 22.39 0.00 22.30 43.93 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.84 12.18 0.00 0.00 0.00
March 22.38 0.09 22.29 47.46 8.97 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.42 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.93 8.57 0.00 0.00 0.00
September 22.49 0.16 22.32 44.21 8.77 0.00 0.00 0.00
October 26.60 2.55 24.05 49.63 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.76 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.28 5.44 24.83 58.89 10.14 0.00 0.00 0.00
Minimum of Months 22.38 0.00 22.29 43.93 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.84 12.18 0.00 0.00 0.00
March 22.38 0.09 22.29 47.46 8.97 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.42 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.93 8.57 0.00 0.00 0.00
September 22.49 0.16 22.32 44.21 8.77 0.00 0.00 0.00
October 26.60 2.55 24.05 49.63 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.76 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.28 5.44 24.83 58.89 10.14 0.00 0.00 0.00
Minimum of Months 22.38 0.00 22.29 43.93 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.84 12.18 0.00 0.00 0.00
March 22.39 0.09 22.30 47.47 8.96 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.42 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.93 8.57 0.00 0.00 0.00
September 22.49 0.16 22.32 44.21 8.77 0.00 0.00 0.00
October 26.60 2.55 24.05 49.63 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.76 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.28 5.44 24.83 58.89 10.14 0.00 0.00 0.00
Minimum of Months 22.39 0.00 22.30 43.93 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.94 20.13 29.81 92.27 15.05 0.00 0.00 0.00
February 37.39 9.88 27.51 73.85 12.18 0.00 0.00 0.00
March 22.62 0.16 22.46 48.00 8.95 0.00 0.00 0.00
April 22.66 0.00 22.66 47.84 6.13 0.00 0.00 0.00
May 22.77 0.00 22.77 48.43 7.03 0.00 0.00 0.00
June 22.86 0.00 22.86 48.43 7.70 0.00 0.00 0.00
July 23.21 0.00 23.21 44.44 9.83 0.00 0.00 0.00
August 22.73 0.00 22.73 43.94 8.57 0.00 0.00 0.00
September 22.50 0.16 22.34 44.24 8.77 0.00 0.00 0.00
October 26.62 2.56 24.07 49.67 10.28 0.00 0.00 0.00
November 39.29 11.11 28.18 73.33 11.40 0.00 0.00 0.00
December 51.27 21.51 29.77 93.58 15.75 0.00 0.00 0.00
                 
Annual Sum or Average 30.30 5.45 24.85 58.94 10.14 0.00 0.00 0.00
Minimum of Months 22.50 0.00 22.34 43.94 6.13 0.00 0.00 0.00
Maximum of Months 51.27 21.51 29.81 93.58 15.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.01 32.35 44.66 141.62 21.31 0.00 0.00 0.00
February 61.05 18.77 42.28 119.95 17.42 0.00 0.00 0.00
March 34.86 1.40 33.46 73.41 12.87 0.00 0.00 0.00
April 32.48 0.00 32.48 67.58 8.85 0.00 0.00 0.00
May 32.87 0.00 32.87 68.93 10.03 0.00 0.00 0.00
June 32.88 0.00 32.88 68.68 10.94 0.00 0.00 0.00
July 33.62 0.00 33.62 63.74 13.93 0.00 0.00 0.00
August 32.79 0.00 32.79 62.65 12.18 0.00 0.00 0.00
September 32.94 0.46 32.48 64.12 12.44 0.00 0.00 0.00
October 43.22 5.77 37.45 80.76 14.54 0.00 0.00 0.00
November 61.37 18.66 42.72 114.02 16.18 0.00 0.00 0.00
December 77.45 33.31 44.14 140.67 22.28 0.00 0.00 0.00
                 
Annual Sum or Average 45.99 9.20 36.79 88.70 14.42 0.00 0.00 0.00
Minimum of Months 32.48 0.00 32.48 62.65 8.85 0.00 0.00 0.00
Maximum of Months 77.45 33.31 44.66 141.62 22.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.63 12.71 24.92 67.67 13.63 0.00 0.00 0.00
February 42.59 15.56 27.02 78.81 11.32 0.00 0.00 0.00
March 46.21 17.82 28.39 88.21 9.11 0.00 0.00 0.00
April 46.56 17.57 28.99 89.26 6.32 0.00 0.00 0.00
May 39.97 12.03 27.94 78.84 6.84 0.00 0.00 0.00
June 42.56 13.90 28.66 83.50 7.55 0.00 0.00 0.00
July 36.16 8.11 28.05 66.81 9.88 0.00 0.00 0.00
August 39.94 11.69 28.24 73.91 8.57 0.00 0.00 0.00
September 37.52 10.22 27.29 70.27 8.75 0.00 0.00 0.00
October 35.28 9.08 26.20 63.62 9.96 0.00 0.00 0.00
November 34.30 9.55 24.75 62.38 10.46 0.00 0.00 0.00
December 35.28 11.38 23.90 63.27 14.29 0.00 0.00 0.00
                 
Annual Sum or Average 39.47 12.44 27.03 73.81 9.73 0.00 0.00 0.00
Minimum of Months 34.30 8.11 23.90 62.38 6.32 0.00 0.00 0.00
Maximum of Months 46.56 17.82 28.99 89.26 14.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.63 12.71 24.92 67.67 13.63 0.00 0.00 0.00
February 42.59 15.56 27.02 78.81 11.32 0.00 0.00 0.00
March 46.21 17.82 28.39 88.21 9.11 0.00 0.00 0.00
April 46.55 17.57 28.99 89.26 6.32 0.00 0.00 0.00
May 39.97 12.03 27.94 78.83 6.84 0.00 0.00 0.00
June 42.55 13.90 28.65 83.50 7.55 0.00 0.00 0.00
July 36.15 8.11 28.05 66.80 9.88 0.00 0.00 0.00
August 39.94 11.69 28.24 73.91 8.57 0.00 0.00 0.00
September 37.52 10.22 27.29 70.27 8.75 0.00 0.00 0.00
October 35.28 9.08 26.20 63.62 9.96 0.00 0.00 0.00
November 34.30 9.55 24.75 62.38 10.46 0.00 0.00 0.00
December 35.28 11.38 23.90 63.27 14.29 0.00 0.00 0.00
                 
Annual Sum or Average 39.46 12.44 27.02 73.81 9.73 0.00 0.00 0.00
Minimum of Months 34.30 8.11 23.90 62.38 6.32 0.00 0.00 0.00
Maximum of Months 46.55 17.82 28.99 89.26 14.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.63 12.71 24.92 67.67 13.63 0.00 0.00 0.00
February 42.59 15.56 27.02 78.81 11.32 0.00 0.00 0.00
March 46.21 17.82 28.39 88.21 9.11 0.00 0.00 0.00
April 46.55 17.57 28.99 89.26 6.32 0.00 0.00 0.00
May 39.97 12.03 27.94 78.83 6.84 0.00 0.00 0.00
June 42.55 13.90 28.65 83.50 7.55 0.00 0.00 0.00
July 36.15 8.11 28.05 66.80 9.88 0.00 0.00 0.00
August 39.94 11.69 28.24 73.91 8.57 0.00 0.00 0.00
September 37.52 10.22 27.29 70.27 8.75 0.00 0.00 0.00
October 35.28 9.08 26.20 63.62 9.96 0.00 0.00 0.00
November 34.30 9.55 24.75 62.38 10.46 0.00 0.00 0.00
December 35.28 11.38 23.90 63.27 14.29 0.00 0.00 0.00
                 
Annual Sum or Average 39.46 12.44 27.02 73.81 9.73 0.00 0.00 0.00
Minimum of Months 34.30 8.11 23.90 62.38 6.32 0.00 0.00 0.00
Maximum of Months 46.55 17.82 28.99 89.26 14.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.63 12.71 24.92 67.67 13.63 0.00 0.00 0.00
February 42.59 15.56 27.02 78.81 11.32 0.00 0.00 0.00
March 46.21 17.82 28.39 88.21 9.11 0.00 0.00 0.00
April 46.56 17.57 28.99 89.26 6.32 0.00 0.00 0.00
May 39.97 12.03 27.94 78.84 6.84 0.00 0.00 0.00
June 42.56 13.90 28.66 83.50 7.55 0.00 0.00 0.00
July 36.16 8.11 28.05 66.81 9.88 0.00 0.00 0.00
August 39.94 11.69 28.24 73.91 8.57 0.00 0.00 0.00
September 37.52 10.22 27.29 70.27 8.75 0.00 0.00 0.00
October 35.28 9.08 26.20 63.62 9.96 0.00 0.00 0.00
November 34.30 9.55 24.75 62.38 10.46 0.00 0.00 0.00
December 35.28 11.38 23.90 63.27 14.29 0.00 0.00 0.00
                 
Annual Sum or Average 39.47 12.44 27.03 73.81 9.73 0.00 0.00 0.00
Minimum of Months 34.30 8.11 23.90 62.38 6.32 0.00 0.00 0.00
Maximum of Months 46.56 17.82 28.99 89.26 14.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.22 8.97 0.00 0.00 0.00
April 23.29 0.21 23.08 49.59 6.00 0.00 0.00 0.00
May 25.55 1.50 24.05 54.87 6.75 0.00 0.00 0.00
June 29.33 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.53 1.70 24.83 51.14 9.73 0.00 0.00 0.00
August 23.91 0.52 23.39 46.93 8.24 0.00 0.00 0.00
September 22.27 0.01 22.26 44.27 8.45 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.78 10.11 0.00 0.00 0.00
December 19.33 0.00 19.33 36.73 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.95 0.65 22.30 46.07 9.57 0.00 0.00 0.00
Minimum of Months 19.33 0.00 19.33 36.73 6.00 0.00 0.00 0.00
Maximum of Months 29.33 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.21 8.97 0.00 0.00 0.00
April 23.15 0.16 22.98 49.25 6.00 0.00 0.00 0.00
May 25.54 1.50 24.05 54.86 6.75 0.00 0.00 0.00
June 29.32 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.52 1.70 24.82 51.12 9.73 0.00 0.00 0.00
August 23.84 0.50 23.34 46.76 8.24 0.00 0.00 0.00
September 22.24 0.01 22.23 44.22 8.45 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.77 10.11 0.00 0.00 0.00
December 19.32 0.00 19.32 36.72 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.93 0.65 22.28 46.02 9.57 0.00 0.00 0.00
Minimum of Months 19.32 0.00 19.32 36.72 6.00 0.00 0.00 0.00
Maximum of Months 29.32 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.21 8.97 0.00 0.00 0.00
April 23.15 0.16 22.98 49.25 6.00 0.00 0.00 0.00
May 25.54 1.50 24.05 54.86 6.75 0.00 0.00 0.00
June 29.32 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.52 1.70 24.82 51.12 9.73 0.00 0.00 0.00
August 23.83 0.50 23.34 46.75 8.24 0.00 0.00 0.00
September 22.23 0.01 22.22 44.20 8.46 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.77 10.11 0.00 0.00 0.00
December 19.32 0.00 19.32 36.72 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.93 0.65 22.28 46.02 9.57 0.00 0.00 0.00
Minimum of Months 19.32 0.00 19.32 36.72 6.00 0.00 0.00 0.00
Maximum of Months 29.32 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.21 8.97 0.00 0.00 0.00
April 23.15 0.16 22.98 49.25 6.00 0.00 0.00 0.00
May 25.54 1.50 24.05 54.86 6.75 0.00 0.00 0.00
June 29.32 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.52 1.70 24.82 51.12 9.73 0.00 0.00 0.00
August 23.83 0.50 23.34 46.75 8.24 0.00 0.00 0.00
September 22.23 0.01 22.22 44.20 8.46 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.77 10.11 0.00 0.00 0.00
December 19.32 0.00 19.32 36.72 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.93 0.65 22.28 46.02 9.57 0.00 0.00 0.00
Minimum of Months 19.32 0.00 19.32 36.72 6.00 0.00 0.00 0.00
Maximum of Months 29.32 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.21 8.97 0.00 0.00 0.00
April 23.15 0.16 22.98 49.25 6.00 0.00 0.00 0.00
May 25.54 1.50 24.05 54.86 6.75 0.00 0.00 0.00
June 29.32 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.52 1.70 24.82 51.12 9.73 0.00 0.00 0.00
August 23.84 0.50 23.34 46.76 8.24 0.00 0.00 0.00
September 22.24 0.01 22.23 44.22 8.46 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.77 10.11 0.00 0.00 0.00
December 19.32 0.00 19.32 36.72 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.93 0.65 22.28 46.02 9.57 0.00 0.00 0.00
Minimum of Months 19.32 0.00 19.32 36.72 6.00 0.00 0.00 0.00
Maximum of Months 29.32 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.95 0.00 19.95 38.21 13.66 0.00 0.00 0.00
February 21.38 0.00 21.38 43.03 11.36 0.00 0.00 0.00
March 22.11 0.00 22.11 47.22 8.97 0.00 0.00 0.00
April 23.29 0.21 23.08 49.58 6.00 0.00 0.00 0.00
May 25.55 1.50 24.05 54.87 6.75 0.00 0.00 0.00
June 29.33 3.90 25.43 61.96 7.59 0.00 0.00 0.00
July 26.53 1.70 24.83 51.13 9.73 0.00 0.00 0.00
August 23.91 0.52 23.39 46.92 8.24 0.00 0.00 0.00
September 22.26 0.01 22.25 44.26 8.46 0.00 0.00 0.00
October 21.42 0.00 21.42 40.20 9.68 0.00 0.00 0.00
November 20.29 0.00 20.29 38.78 10.11 0.00 0.00 0.00
December 19.33 0.00 19.33 36.73 14.23 0.00 0.00 0.00
                 
Annual Sum or Average 22.95 0.65 22.29 46.07 9.57 0.00 0.00 0.00
Minimum of Months 19.33 0.00 19.33 36.73 6.00 0.00 0.00 0.00
Maximum of Months 29.33 3.90 25.43 61.96 14.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 38.19 13.48 24.71 70.18 15.19 0.00 0.00 0.00
February 41.75 14.67 27.07 78.61 12.89 0.00 0.00 0.00
March 46.67 18.17 28.50 89.97 10.69 0.00 0.00 0.00
April 46.72 17.71 29.01 89.53 7.42 0.00 0.00 0.00
May 39.61 11.68 27.92 78.27 7.40 0.00 0.00 0.00
June 43.07 14.73 28.34 84.25 8.10 0.00 0.00 0.00
July 36.53 8.63 27.90 67.61 10.62 0.00 0.00 0.00
August 39.79 11.72 28.06 73.48 9.22 0.00 0.00 0.00
September 37.28 10.35 26.93 69.85 9.29 0.00 0.00 0.00
October 35.12 9.11 26.01 63.48 10.72 0.00 0.00 0.00
November 34.39 9.45 24.95 63.01 11.25 0.00 0.00 0.00
December 35.44 11.66 23.79 64.88 15.67 0.00 0.00 0.00
                 
Annual Sum or Average 39.52 12.59 26.93 74.37 10.70 0.00 0.00 0.00
Minimum of Months 34.39 8.63 23.79 63.01 7.40 0.00 0.00 0.00
Maximum of Months 46.72 18.17 29.01 89.97 15.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 38.19 13.48 24.71 70.18 15.19 0.00 0.00 0.00
February 41.74 14.67 27.07 78.61 12.89 0.00 0.00 0.00
March 46.67 18.17 28.50 89.96 10.69 0.00 0.00 0.00
April 46.72 17.71 29.01 89.53 7.42 0.00 0.00 0.00
May 39.61 11.68 27.92 78.27 7.39 0.00 0.00 0.00
June 43.07 14.73 28.34 84.25 8.10 0.00 0.00 0.00
July 36.53 8.63 27.90 67.61 10.62 0.00 0.00 0.00
August 39.79 11.72 28.06 73.47 9.22 0.00 0.00 0.00
September 37.27 10.35 26.92 69.84 9.29 0.00 0.00 0.00
October 35.12 9.11 26.01 63.48 10.72 0.00 0.00 0.00
November 34.39 9.45 24.95 63.01 11.25 0.00 0.00 0.00
December 35.44 11.66 23.78 64.88 15.67 0.00 0.00 0.00
                 
Annual Sum or Average 39.52 12.59 26.93 74.37 10.70 0.00 0.00 0.00
Minimum of Months 34.39 8.63 23.78 63.01 7.39 0.00 0.00 0.00
Maximum of Months 46.72 18.17 29.01 89.96 15.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 38.19 13.48 24.71 70.18 15.19 0.00 0.00 0.00
February 41.74 14.67 27.07 78.61 12.89 0.00 0.00 0.00
March 46.67 18.17 28.50 89.96 10.69 0.00 0.00 0.00
April 46.72 17.71 29.01 89.53 7.42 0.00 0.00 0.00
May 39.61 11.68 27.92 78.27 7.39 0.00 0.00 0.00
June 43.07 14.73 28.34 84.25 8.10 0.00 0.00 0.00
July 36.53 8.63 27.90 67.61 10.62 0.00 0.00 0.00
August 39.79 11.72 28.06 73.47 9.22 0.00 0.00 0.00
September 37.27 10.35 26.92 69.84 9.29 0.00 0.00 0.00
October 35.12 9.11 26.01 63.48 10.72 0.00 0.00 0.00
November 34.39 9.45 24.95 63.01 11.25 0.00 0.00 0.00
December 35.44 11.66 23.78 64.88 15.67 0.00 0.00 0.00
                 
Annual Sum or Average 39.52 12.59 26.93 74.37 10.70 0.00 0.00 0.00
Minimum of Months 34.39 8.63 23.78 63.01 7.39 0.00 0.00 0.00
Maximum of Months 46.72 18.17 29.01 89.96 15.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 38.19 13.48 24.71 70.18 15.19 0.00 0.00 0.00
February 41.75 14.67 27.07 78.61 12.89 0.00 0.00 0.00
March 46.67 18.17 28.50 89.97 10.69 0.00 0.00 0.00
April 46.72 17.71 29.01 89.53 7.42 0.00 0.00 0.00
May 39.61 11.68 27.92 78.27 7.40 0.00 0.00 0.00
June 43.07 14.73 28.34 84.25 8.10 0.00 0.00 0.00
July 36.53 8.63 27.90 67.61 10.62 0.00 0.00 0.00
August 39.79 11.72 28.06 73.48 9.22 0.00 0.00 0.00
September 37.28 10.35 26.93 69.85 9.29 0.00 0.00 0.00
October 35.12 9.11 26.01 63.48 10.72 0.00 0.00 0.00
November 34.39 9.45 24.95 63.01 11.25 0.00 0.00 0.00
December 35.44 11.66 23.79 64.88 15.67 0.00 0.00 0.00
                 
Annual Sum or Average 39.52 12.59 26.93 74.37 10.70 0.00 0.00 0.00
Minimum of Months 34.39 8.63 23.79 63.01 7.40 0.00 0.00 0.00
Maximum of Months 46.72 18.17 29.01 89.97 15.67 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133751E+09 53908973.40 79842050.33 0.247138E+09 40306144.58
February 90447296.34 23892437.56 66554858.78 0.178650E+09 29460316.46
March 60593114.65 444356.60 60148758.05 0.128615E+09 24032085.65
April 58740730.20 0.00 58740730.20 0.124000E+09 15879682.18
May 60999324.29 0.00 60999324.29 0.129725E+09 18823312.91
June 59256209.19 0.00 59256209.19 0.125520E+09 19967603.12
July 62159114.36 0.00 62159114.36 0.119040E+09 26336308.69
August 60875351.00 288.79 60875062.21 0.117678E+09 22949929.18
September 58331804.75 426902.18 57904902.57 0.114667E+09 22730744.86
October 71307688.45 6848133.03 64459555.42 0.133035E+09 27541846.21
November 0.101831E+09 28795413.94 73035657.91 0.190078E+09 29559065.70
December 0.137324E+09 57600859.05 79723087.00 0.250640E+09 42178486.47
           
Annual Sum or Average 0.955617E+09 0.171917E+09 0.783699E+09 0.185879E+10 0.319766E+09
Minimum of Months 58331804.75 0.00 57904902.57 0.114667E+09 15879682.18
Maximum of Months 0.137324E+09 57600859.05 79842050.33 0.250640E+09 42178486.47



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133748E+09 53908973.40 79838612.41 0.247133E+09 40304569.12
February 90444242.14 23892437.56 66551804.58 0.178646E+09 29458589.19
March 59974694.91 237193.93 59737500.98 0.127184E+09 24030666.05
April 58737721.55 0.00 58737721.55 0.123996E+09 15878444.22
May 60995196.28 0.00 60995196.28 0.129719E+09 18822300.70
June 59252710.88 0.00 59252710.88 0.125515E+09 19966709.94
July 62154377.33 0.00 62154377.33 0.119033E+09 26335218.14
August 60871032.52 0.00 60871032.52 0.117671E+09 22948841.92
September 58286557.90 422239.64 57864318.26 0.114580E+09 22729736.15
October 71257490.28 6828935.97 64428554.31 0.132927E+09 27541397.84
November 0.101827E+09 28795413.94 73031765.56 0.190073E+09 29557717.10
December 0.137320E+09 57600859.05 79719572.51 0.250635E+09 42176908.01
           
Annual Sum or Average 0.954869E+09 0.171686E+09 0.783183E+09 0.185711E+10 0.319751E+09
Minimum of Months 58286557.90 0.00 57864318.26 0.114580E+09 15878444.22
Maximum of Months 0.137320E+09 57600859.05 79838612.41 0.250635E+09 42176908.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133748E+09 53908973.40 79838612.41 0.247133E+09 40304569.12
February 90444242.14 23892437.56 66551804.58 0.178646E+09 29458589.19
March 59945864.69 232977.75 59712886.94 0.127126E+09 24032478.17
April 58737721.55 0.00 58737721.55 0.123996E+09 15878444.22
May 60995196.28 0.00 60995196.28 0.129719E+09 18822300.70
June 59252710.88 0.00 59252710.88 0.125515E+09 19966709.94
July 62154377.33 0.00 62154377.33 0.119033E+09 26335218.14
August 60871032.52 0.00 60871032.52 0.117671E+09 22948841.92
September 58286557.90 422239.64 57864318.26 0.114580E+09 22729736.15
October 71257490.28 6828935.97 64428554.31 0.132927E+09 27541397.84
November 0.101827E+09 28795413.94 73031765.56 0.190073E+09 29557717.10
December 0.137320E+09 57600859.05 79719572.51 0.250635E+09 42176908.01
           
Annual Sum or Average 0.954840E+09 0.171682E+09 0.783159E+09 0.185705E+10 0.319753E+09
Minimum of Months 58286557.90 0.00 57864318.26 0.114580E+09 15878444.22
Maximum of Months 0.137320E+09 57600859.05 79838612.41 0.250635E+09 42176908.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133748E+09 53908973.40 79838612.41 0.247133E+09 40304569.12
February 90444242.14 23892437.56 66551804.58 0.178646E+09 29458589.19
March 59945579.54 232985.38 59712594.16 0.127124E+09 24030920.51
April 58737721.55 0.00 58737721.55 0.123996E+09 15878444.22
May 60995196.28 0.00 60995196.28 0.129719E+09 18822300.70
June 59252710.88 0.00 59252710.88 0.125515E+09 19966709.94
July 62154377.33 0.00 62154377.33 0.119033E+09 26335218.14
August 60871032.52 0.00 60871032.52 0.117671E+09 22948841.92
September 58286557.90 422239.64 57864318.26 0.114580E+09 22729736.15
October 71257490.28 6828935.97 64428554.31 0.132927E+09 27541397.84
November 0.101827E+09 28795413.94 73031765.56 0.190073E+09 29557717.10
December 0.137320E+09 57600859.05 79719572.51 0.250635E+09 42176908.01
           
Annual Sum or Average 0.954840E+09 0.171682E+09 0.783158E+09 0.185705E+10 0.319751E+09
Minimum of Months 58286557.90 0.00 57864318.26 0.114580E+09 15878444.22
Maximum of Months 0.137320E+09 57600859.05 79838612.41 0.250635E+09 42176908.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133748E+09 53908973.40 79838612.41 0.247133E+09 40304569.12
February 90444242.14 23892437.56 66551804.58 0.178646E+09 29458589.19
March 59969985.43 236977.61 59733007.82 0.127149E+09 24003225.84
April 58737721.55 0.00 58737721.55 0.123996E+09 15878444.22
May 60995196.28 0.00 60995196.28 0.129719E+09 18822300.70
June 59252710.88 0.00 59252710.88 0.125515E+09 19966709.94
July 62154377.33 0.00 62154377.33 0.119033E+09 26335218.14
August 60871032.52 0.00 60871032.52 0.117671E+09 22948841.92
September 58286557.90 422239.64 57864318.26 0.114580E+09 22729736.15
October 71257490.28 6828935.97 64428554.31 0.132927E+09 27541397.84
November 0.101827E+09 28795413.94 73031765.56 0.190073E+09 29557717.10
December 0.137320E+09 57600859.05 79719572.51 0.250635E+09 42176908.01
           
Annual Sum or Average 0.954865E+09 0.171686E+09 0.783179E+09 0.185708E+10 0.319724E+09
Minimum of Months 58286557.90 0.00 57864318.26 0.114580E+09 15878444.22
Maximum of Months 0.137320E+09 57600859.05 79838612.41 0.250635E+09 42176908.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.133751E+09 53908973.40 79842050.15 0.247138E+09 40306144.50
February 90447296.18 23892437.56 66554858.62 0.178650E+09 29460316.38
March 60586418.48 440427.51 60145990.97 0.128574E+09 23977906.85
April 58740730.05 0.00 58740730.05 0.124000E+09 15879682.11
May 60999324.07 0.00 60999324.07 0.129725E+09 18823312.86
June 59256209.01 0.00 59256209.01 0.125520E+09 19967603.07
July 62159114.11 0.00 62159114.11 0.119040E+09 26336308.63
August 60875270.43 208.43 60875062.01 0.117678E+09 22949929.13
September 58331389.86 425650.79 57905739.07 0.114667E+09 22730744.87
October 71308276.10 6848749.94 64459526.16 0.133040E+09 27542296.67
November 0.101831E+09 28795413.94 73035657.71 0.190078E+09 29559065.63
December 0.137324E+09 57600859.05 79723086.82 0.250640E+09 42178486.39
           
Annual Sum or Average 0.955610E+09 0.171913E+09 0.783697E+09 0.185875E+10 0.319712E+09
Minimum of Months 58331389.86 0.00 57905739.07 0.114667E+09 15879682.11
Maximum of Months 0.137324E+09 57600859.05 79842050.15 0.250640E+09 42178486.39



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206254E+09 86646635.18 0.119608E+09 0.379312E+09 57076664.19
February 0.147685E+09 45401342.22 0.102283E+09 0.290188E+09 42135934.62
March 93375878.48 3759499.10 89616379.38 0.196616E+09 34474917.13
April 84184417.36 0.00 84184417.36 0.175180E+09 22947135.50
May 88051113.41 0.00 88051113.41 0.184625E+09 26868288.28
June 85213858.64 0.00 85213858.64 0.178017E+09 28362152.08
July 90058147.43 0.00 90058147.43 0.170710E+09 37316011.69
August 87815328.25 0.00 87815328.25 0.167789E+09 32625897.34
September 85372513.48 1192062.22 84180451.26 0.166203E+09 32249819.44
October 0.115757E+09 15456032.27 0.100301E+09 0.216310E+09 38931461.92
November 0.159083E+09 48364251.77 0.110719E+09 0.295546E+09 41928680.16
December 0.207433E+09 89215124.21 0.118218E+09 0.376778E+09 59683394.57
           
Annual Sum or Average 0.145028E+10 0.290035E+09 0.116025E+10 0.279727E+10 0.454600E+09
Minimum of Months 84184417.36 0.00 84180451.26 0.166203E+09 22947135.50
Maximum of Months 0.207433E+09 89215124.21 0.119608E+09 0.379312E+09 59683394.57



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100796E+09 34044224.74 66752170.05 0.181260E+09 36506096.10
February 0.103027E+09 37649920.88 65377551.31 0.190666E+09 27392330.69
March 0.123769E+09 47736393.65 76032656.38 0.236254E+09 24409436.60
April 0.120671E+09 45531406.28 75139330.87 0.231357E+09 16373579.91
May 0.107059E+09 32230924.34 74827833.80 0.211158E+09 18318021.35
June 0.110304E+09 36028479.83 74275226.30 0.216428E+09 19577517.76
July 96840898.35 21713538.34 75127360.01 0.178936E+09 26461924.29
August 0.106967E+09 31323419.29 75643135.49 0.197971E+09 22963750.85
September 97250425.88 26501833.40 70748592.48 0.182147E+09 22690689.72
October 94495220.13 24322514.60 70172705.53 0.170411E+09 26665767.11
November 88898587.09 24740886.69 64157700.41 0.161698E+09 27120234.93
December 94506866.23 30490839.96 64016026.27 0.169460E+09 38269966.25
           
Annual Sum or Average 0.124458E+10 0.392314E+09 0.852270E+09 0.232774E+10 0.306749E+09
Minimum of Months 88898587.09 21713538.34 64016026.27 0.161698E+09 16373579.91
Maximum of Months 0.123769E+09 47736393.65 76032656.38 0.236254E+09 38269966.25



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100793E+09 34044224.74 66748732.31 0.181255E+09 36504562.23
February 0.103024E+09 37649920.88 65374497.27 0.190661E+09 27390659.89
March 0.123766E+09 47736393.65 76029670.80 0.236250E+09 24407874.05
April 0.120668E+09 45531406.28 75136322.37 0.231353E+09 16372344.45
May 0.107055E+09 32230924.34 74823706.01 0.211152E+09 18316976.18
June 0.110300E+09 36028479.83 74271728.17 0.216423E+09 19576570.61
July 96836161.56 21713538.34 75122623.23 0.178929E+09 26460770.18
August 0.106963E+09 31323419.29 75639106.01 0.197965E+09 22962593.80
September 97246310.89 26501833.40 70744477.49 0.182140E+09 22689659.90
October 94490898.12 24322514.60 70168383.52 0.170404E+09 26664764.10
November 88894694.95 24740886.69 64153808.26 0.161692E+09 27118984.46
December 94503351.91 30490839.96 64012511.95 0.169455E+09 38268511.31
           
Annual Sum or Average 0.124454E+10 0.392314E+09 0.852226E+09 0.232768E+10 0.306734E+09
Minimum of Months 88894694.95 21713538.34 64012511.95 0.161692E+09 16372344.45
Maximum of Months 0.123766E+09 47736393.65 76029670.80 0.236250E+09 38268511.31



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100793E+09 34044224.74 66748732.31 0.181255E+09 36504562.23
February 0.103024E+09 37649920.88 65374497.27 0.190661E+09 27390659.89
March 0.123766E+09 47736393.65 76029670.80 0.236250E+09 24407874.05
April 0.120668E+09 45531406.28 75136322.37 0.231353E+09 16372344.45
May 0.107055E+09 32230924.34 74823706.01 0.211152E+09 18316976.18
June 0.110300E+09 36028479.83 74271728.17 0.216423E+09 19576570.61
July 96836161.56 21713538.34 75122623.23 0.178929E+09 26460770.18
August 0.106963E+09 31323419.29 75639106.01 0.197965E+09 22962593.80
September 97246310.89 26501833.40 70744477.49 0.182140E+09 22689659.90
October 94490898.12 24322514.60 70168383.52 0.170404E+09 26664764.10
November 88894694.95 24740886.69 64153808.26 0.161692E+09 27118984.46
December 94503351.91 30490839.96 64012511.95 0.169455E+09 38268511.31
           
Annual Sum or Average 0.124454E+10 0.392314E+09 0.852226E+09 0.232768E+10 0.306734E+09
Minimum of Months 88894694.95 21713538.34 64012511.95 0.161692E+09 16372344.45
Maximum of Months 0.123766E+09 47736393.65 76029670.80 0.236250E+09 38268511.31



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100796E+09 34044224.74 66752170.23 0.181260E+09 36506096.18
February 0.103027E+09 37649920.88 65377551.47 0.190666E+09 27392330.78
March 0.123769E+09 47736393.65 76032656.53 0.236254E+09 24409436.68
April 0.120671E+09 45531406.28 75139331.03 0.231357E+09 16373579.98
May 0.107059E+09 32230924.34 74827834.02 0.211158E+09 18318021.40
June 0.110304E+09 36028479.83 74275226.48 0.216428E+09 19577517.81
July 96840898.59 21713538.34 75127360.26 0.178936E+09 26461924.35
August 0.106967E+09 31323419.29 75643135.70 0.197971E+09 22963750.91
September 97250426.10 26501833.40 70748592.69 0.182147E+09 22690689.77
October 94495220.36 24322514.60 70172705.76 0.170411E+09 26665767.16
November 88898587.30 24740886.69 64157700.61 0.161698E+09 27120235.00
December 94506866.41 30490839.96 64016026.45 0.169460E+09 38269966.33
           
Annual Sum or Average 0.124458E+10 0.392314E+09 0.852270E+09 0.232774E+10 0.306749E+09
Minimum of Months 88898587.30 21713538.34 64016026.45 0.161698E+09 16373579.98
Maximum of Months 0.123769E+09 47736393.65 76032656.53 0.236254E+09 38269966.33



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53442333.29 0.00 53442333.29 0.102340E+09 36586196.86
February 51725465.47 0.00 51725465.47 0.104106E+09 27472306.31
March 59213319.48 0.00 59213319.48 0.126461E+09 24016331.13
April 60370696.23 536508.64 59834187.59 0.128538E+09 15551406.73
May 68429104.90 4015066.93 64414037.97 0.146968E+09 18079462.88
June 76011843.91 10105707.57 65906136.34 0.160609E+09 19684798.38
July 71060153.16 4564186.78 66495966.38 0.136960E+09 26051650.57
August 64045996.60 1395053.79 62650942.81 0.125685E+09 22075426.39
September 57723977.67 22979.67 57700998.00 0.114747E+09 21908691.97
October 57364688.69 0.00 57364688.69 0.107679E+09 25932212.37
November 52588057.98 0.00 52588057.98 0.100508E+09 26202803.63
December 51760210.69 0.00 51760210.69 98366549.37 38117919.76
           
Annual Sum or Average 0.723736E+09 20639503.37 0.703096E+09 0.145297E+10 0.301679E+09
Minimum of Months 51725465.47 0.00 51725465.47 98366549.37 15551406.73
Maximum of Months 76011843.91 10105707.57 66495966.38 0.160609E+09 38117919.76



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53438895.37 0.00 53438895.37 0.102335E+09 36584656.97
February 51722411.27 0.00 51722411.27 0.104102E+09 27470560.16
March 59210333.74 0.00 59210333.74 0.126457E+09 24014631.31
April 59995537.42 426765.01 59568772.41 0.127653E+09 15550096.47
May 68411024.43 4008394.61 64402629.83 0.146930E+09 18078399.46
June 76008345.60 10105707.57 65902638.03 0.160604E+09 19683828.04
July 71041269.81 4560572.06 66480697.75 0.136922E+09 26050489.41
August 63846195.53 1327806.59 62518388.94 0.125239E+09 22075889.51
September 57651542.29 19641.34 57631900.95 0.114614E+09 21914330.94
October 57360366.45 0.00 57360366.45 0.107672E+09 25931231.44
November 52584165.64 0.00 52584165.64 0.100503E+09 26201597.44
December 51756696.19 0.00 51756696.19 98361648.90 38116428.12
           
Annual Sum or Average 0.723027E+09 20448887.17 0.702578E+09 0.145139E+10 0.301672E+09
Minimum of Months 51722411.27 0.00 51722411.27 98361648.90 15550096.47
Maximum of Months 76008345.60 10105707.57 66480697.75 0.160604E+09 38116428.12



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53438895.37 0.00 53438895.37 0.102335E+09 36584656.97
February 51722411.27 0.00 51722411.27 0.104102E+09 27470560.16
March 59210333.74 0.00 59210333.74 0.126457E+09 24014631.31
April 59995537.42 426765.01 59568772.41 0.127653E+09 15550096.47
May 68411024.43 4008394.61 64402629.83 0.146930E+09 18078399.46
June 76008345.60 10105707.57 65902638.03 0.160604E+09 19683828.04
July 71041269.81 4560572.06 66480697.75 0.136922E+09 26050489.41
August 63837706.88 1327508.73 62510198.15 0.125226E+09 22080148.46
September 57623837.64 17068.66 57606768.98 0.114568E+09 21926204.78
October 57360366.45 0.00 57360366.45 0.107672E+09 25931231.44
November 52584165.64 0.00 52584165.64 0.100503E+09 26201597.44
December 51756696.19 0.00 51756696.19 98361648.90 38116428.12
           
Annual Sum or Average 0.722991E+09 20446016.64 0.702545E+09 0.145134E+10 0.301688E+09
Minimum of Months 51722411.27 0.00 51722411.27 98361648.90 15550096.47
Maximum of Months 76008345.60 10105707.57 66480697.75 0.160604E+09 38116428.12



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53438895.37 0.00 53438895.37 0.102335E+09 36584656.97
February 51722411.27 0.00 51722411.27 0.104102E+09 27470560.16
March 59210333.74 0.00 59210333.74 0.126457E+09 24014631.31
April 59995537.42 426765.01 59568772.41 0.127653E+09 15550096.47
May 68411024.43 4008394.61 64402629.83 0.146930E+09 18078399.46
June 76008345.60 10105707.57 65902638.03 0.160604E+09 19683828.04
July 71041269.81 4560572.06 66480697.75 0.136922E+09 26050489.41
August 63837637.70 1327507.68 62510130.02 0.125226E+09 22080439.73
September 57623492.16 17054.78 57606437.38 0.114568E+09 21926399.16
October 57360366.45 0.00 57360366.45 0.107672E+09 25931231.44
November 52584165.64 0.00 52584165.64 0.100503E+09 26201597.44
December 51756696.19 0.00 51756696.19 98361648.90 38116428.12
           
Annual Sum or Average 0.722990E+09 20446001.71 0.702544E+09 0.145134E+10 0.301689E+09
Minimum of Months 51722411.27 0.00 51722411.27 98361648.90 15550096.47
Maximum of Months 76008345.60 10105707.57 66480697.75 0.160604E+09 38116428.12



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53438895.37 0.00 53438895.37 0.102335E+09 36584656.97
February 51722411.27 0.00 51722411.27 0.104102E+09 27470560.16
March 59210333.74 0.00 59210333.74 0.126457E+09 24014631.31
April 59995537.42 426765.01 59568772.41 0.127653E+09 15550096.47
May 68411024.43 4008394.61 64402629.83 0.146930E+09 18078399.46
June 76008345.60 10105707.57 65902638.03 0.160604E+09 19683828.04
July 71041269.81 4560572.06 66480697.75 0.136922E+09 26050489.41
August 63845224.45 1327830.30 62517394.14 0.125240E+09 22080438.90
September 57644037.59 19650.30 57624387.29 0.114608E+09 21924162.17
October 57360366.45 0.00 57360366.45 0.107672E+09 25931231.44
November 52584165.64 0.00 52584165.64 0.100503E+09 26201597.44
December 51756696.19 0.00 51756696.19 98361648.90 38116428.12
           
Annual Sum or Average 0.723018E+09 20448919.85 0.702569E+09 0.145139E+10 0.301687E+09
Minimum of Months 51722411.27 0.00 51722411.27 98361648.90 15550096.47
Maximum of Months 76008345.60 10105707.57 66480697.75 0.160604E+09 38116428.12



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53442333.11 0.00 53442333.11 0.102340E+09 36586196.78
February 51725465.31 0.00 51725465.31 0.104106E+09 27472306.22
March 59213319.32 0.00 59213319.32 0.126461E+09 24016331.04
April 60366053.35 539970.89 59826082.46 0.128503E+09 15546826.05
May 68428864.74 4014720.74 64414144.00 0.146966E+09 18079462.83
June 76011843.73 10105707.57 65906136.15 0.160609E+09 19684798.33
July 71058171.41 4563274.73 66494896.68 0.136955E+09 26051650.51
August 64041500.79 1395042.95 62646457.84 0.125669E+09 22081157.14
September 57698385.73 22970.95 57675414.78 0.114711E+09 21922553.68
October 57364688.46 0.00 57364688.46 0.107679E+09 25932212.31
November 52588057.78 0.00 52588057.78 0.100508E+09 26202803.57
December 51760210.51 0.00 51760210.51 98366549.12 38117919.68
           
Annual Sum or Average 0.723699E+09 20641687.83 0.703057E+09 0.145288E+10 0.301694E+09
Minimum of Months 51725465.31 0.00 51725465.31 98366549.12 15546826.05
Maximum of Months 76011843.73 10105707.57 66494896.68 0.160609E+09 38117919.68



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102295E+09 36102620.76 66192070.03 0.187975E+09 40698108.09
February 0.100991E+09 35498448.19 65492521.49 0.190180E+09 31186992.54
March 0.124999E+09 48675126.72 76324244.85 0.240964E+09 28626447.78
April 0.121094E+09 45898783.78 75194983.60 0.232068E+09 19229998.53
May 0.106083E+09 31292879.34 74789808.18 0.209643E+09 19807422.29
June 0.111640E+09 38190864.51 73449423.68 0.218388E+09 20988277.87
July 97848046.78 23119888.83 74728157.95 0.181088E+09 28445698.33
August 0.106565E+09 31400272.43 75164363.94 0.196799E+09 24702039.82
September 96620139.07 26829407.59 69790731.48 0.181039E+09 24076104.33
October 94056845.11 24389465.22 69667379.89 0.170022E+09 28708356.50
November 89148971.43 24483905.09 64665066.34 0.163315E+09 29151623.43
December 94924469.54 31216788.61 63707680.93 0.173768E+09 41963160.46
           
Annual Sum or Average 0.124626E+10 0.397098E+09 0.849166E+09 0.234525E+10 0.337584E+09
Minimum of Months 89148971.43 23119888.83 63707680.93 0.163315E+09 19229998.53
Maximum of Months 0.124999E+09 48675126.72 76324244.85 0.240964E+09 41963160.46



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102291E+09 36102620.76 66188632.29 0.187971E+09 40696538.52
February 0.100988E+09 35498448.19 65489467.45 0.190176E+09 31185226.95
March 0.124996E+09 48675126.72 76321259.27 0.240960E+09 28624701.92
April 0.121091E+09 45898783.78 75191975.09 0.232064E+09 19228592.55
May 0.106079E+09 31292879.34 74785680.39 0.209637E+09 19806333.48
June 0.111637E+09 38190864.51 73445925.55 0.218383E+09 20987350.37
July 97843310.00 23119888.83 74723421.17 0.181081E+09 28445266.36
August 0.106561E+09 31400272.43 75160334.46 0.196793E+09 24700923.96
September 96616024.08 26829407.59 69786616.49 0.181032E+09 24075072.11
October 94052523.10 24389465.22 69663057.88 0.170015E+09 28707325.03
November 89145079.28 24483905.09 64661174.20 0.163309E+09 29150378.30
December 94920955.22 31216788.61 63704166.62 0.173763E+09 41961641.18
           
Annual Sum or Average 0.124622E+10 0.397098E+09 0.849122E+09 0.234518E+10 0.337569E+09
Minimum of Months 89145079.28 23119888.83 63704166.62 0.163309E+09 19228592.55
Maximum of Months 0.124996E+09 48675126.72 76321259.27 0.240960E+09 41961641.18



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102291E+09 36102620.76 66188632.29 0.187971E+09 40696538.52
February 0.100988E+09 35498448.19 65489467.45 0.190176E+09 31185226.95
March 0.124996E+09 48675126.72 76321259.27 0.240960E+09 28624701.92
April 0.121091E+09 45898783.78 75191975.09 0.232064E+09 19228592.55
May 0.106079E+09 31292879.34 74785680.39 0.209637E+09 19806333.48
June 0.111637E+09 38190864.51 73445925.55 0.218383E+09 20987350.37
July 97843310.00 23119888.83 74723421.17 0.181081E+09 28445266.36
August 0.106561E+09 31400272.43 75160334.46 0.196793E+09 24700923.96
September 96616024.08 26829407.59 69786616.49 0.181032E+09 24075072.11
October 94052523.10 24389465.22 69663057.88 0.170015E+09 28707325.03
November 89145079.28 24483905.09 64661174.20 0.163309E+09 29150378.30
December 94920955.22 31216788.61 63704166.62 0.173763E+09 41961641.18
           
Annual Sum or Average 0.124622E+10 0.397098E+09 0.849122E+09 0.234518E+10 0.337569E+09
Minimum of Months 89145079.28 23119888.83 63704166.62 0.163309E+09 19228592.55
Maximum of Months 0.124996E+09 48675126.72 76321259.27 0.240960E+09 41961641.18



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102295E+09 36102620.76 66192070.21 0.187975E+09 40698108.18
February 0.100991E+09 35498448.19 65492521.65 0.190180E+09 31186992.63
March 0.124999E+09 48675126.72 76324245.01 0.240964E+09 28626447.87
April 0.121094E+09 45898783.78 75194983.75 0.232068E+09 19229998.60
May 0.106083E+09 31292879.34 74789808.40 0.209643E+09 19807422.35
June 0.111640E+09 38190864.51 73449423.86 0.218388E+09 20988277.92
July 97848047.03 23119888.83 74728158.19 0.181088E+09 28445698.39
August 0.106565E+09 31400272.43 75164364.15 0.196799E+09 24702039.88
September 96620139.29 26829407.59 69790731.70 0.181039E+09 24076104.38
October 94056845.33 24389465.22 69667380.11 0.170022E+09 28708356.55
November 89148971.63 24483905.09 64665066.55 0.163315E+09 29151623.49
December 94924469.72 31216788.61 63707681.11 0.173768E+09 41963160.54
           
Annual Sum or Average 0.124626E+10 0.397098E+09 0.849166E+09 0.234525E+10 0.337584E+09
Minimum of Months 89148971.63 23119888.83 63707681.11 0.163315E+09 19229998.60
Maximum of Months 0.124999E+09 48675126.72 76324245.01 0.240964E+09 41963160.54



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 695.24 111.60 376.62 153.11 223.51 0.00 0.00
February 563.02 90.48 285.37 78.02 207.34 0.00 0.00
March 359.31 66.67 169.65 2.08 167.57 0.00 0.00
April 354.62 45.61 168.45 0.00 168.45 0.00 0.00
May 359.52 52.19 169.52 0.00 169.52 0.00 0.00
June 359.23 57.16 170.04 0.00 170.04 0.00 0.00
July 330.39 72.93 172.86 0.00 172.86 0.00 0.00
August 326.25 63.59 169.15 0.00 169.15 0.00 0.00
September 329.42 65.06 167.89 1.44 166.45 0.00 0.00
October 378.62 76.23 202.88 21.08 181.80 0.00 0.00
November 554.01 84.60 297.09 85.32 211.77 0.00 0.00
December 702.14 116.77 385.07 162.34 222.72 0.00 0.00
               
Annual Sum or Average 442.13 75.25 227.71 41.88 185.83 0.00 0.00
Minimum of Months 326.25 45.61 167.89 0.00 166.45 0.00 0.00
Maximum of Months 702.14 116.77 385.07 162.34 223.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 270.70 54.52 150.53 50.84 99.69 0.00 0.00
February 315.25 45.29 170.35 62.25 108.10 0.00 0.00
March 352.83 36.45 184.84 71.29 113.55 0.00 0.00
April 357.03 25.27 186.22 70.26 115.95 0.00 0.00
May 315.34 27.36 159.88 48.13 111.75 0.00 0.00
June 333.99 30.21 170.22 55.60 114.62 0.00 0.00
July 267.22 39.52 144.62 32.43 112.19 0.00 0.00
August 295.65 34.29 159.74 46.78 112.96 0.00 0.00
September 281.09 35.02 150.07 40.90 109.18 0.00 0.00
October 254.49 39.82 141.12 36.32 104.79 0.00 0.00
November 249.53 41.85 137.19 38.18 99.01 0.00 0.00
December 253.07 57.15 141.14 45.54 95.60 0.00 0.00
               
Annual Sum or Average 295.25 38.91 157.86 49.76 108.10 0.00 0.00
Minimum of Months 249.53 25.27 137.19 32.43 95.60 0.00 0.00
Maximum of Months 357.03 57.15 186.22 71.29 115.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 229.25 81.96 119.71 0.00 119.71 0.00 0.00
February 258.19 68.13 128.28 0.00 128.28 0.00 0.00
March 283.29 53.80 132.64 0.00 132.64 0.00 0.00
April 296.16 35.99 139.17 1.07 138.09 0.00 0.00
May 329.17 40.50 153.26 8.98 144.28 0.00 0.00
June 371.77 45.57 175.95 23.39 152.56 0.00 0.00
July 306.75 58.36 159.16 10.22 148.94 0.00 0.00
August 280.87 49.46 143.17 3.02 140.14 0.00 0.00
September 265.36 50.74 133.47 0.05 133.43 0.00 0.00
October 241.21 58.09 128.50 0.00 128.50 0.00 0.00
November 232.65 60.65 121.73 0.00 121.73 0.00 0.00
December 220.35 85.39 115.95 0.00 115.95 0.00 0.00
               
Annual Sum or Average 276.23 57.40 137.60 3.90 133.70 0.00 0.00
Minimum of Months 220.35 35.99 115.95 0.00 115.95 0.00 0.00
Maximum of Months 371.77 85.39 175.95 23.39 152.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 280.72 60.78 152.77 53.92 98.85 0.00 0.00
February 314.45 51.56 166.98 58.69 108.29 0.00 0.00
March 359.86 42.75 186.68 72.69 113.98 0.00 0.00
April 358.13 29.67 186.87 70.83 116.04 0.00 0.00
May 313.08 29.58 158.42 46.73 111.69 0.00 0.00
June 337.01 32.39 172.28 58.94 113.35 0.00 0.00
July 270.44 42.48 146.13 34.53 111.60 0.00 0.00
August 293.90 36.89 159.14 46.89 112.25 0.00 0.00
September 279.38 37.15 149.10 41.40 107.70 0.00 0.00
October 253.91 42.87 140.46 36.42 104.04 0.00 0.00
November 252.02 44.99 137.57 37.78 99.79 0.00 0.00
December 259.51 62.67 141.76 46.62 95.14 0.00 0.00
               
Annual Sum or Average 297.47 42.82 158.07 50.37 107.70 0.00 0.00
Minimum of Months 252.02 29.58 137.57 34.53 95.14 0.00 0.00
Maximum of Months 359.86 62.67 186.87 72.69 116.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.186212E+10 0.298907E+09 0.100875E+10 0.410100E+09 0.598646E+09 0.00 0.00
February 0.136207E+10 0.218891E+09 0.690356E+09 0.188756E+09 0.501600E+09 0.00 0.00
March 0.962367E+09 0.178562E+09 0.454392E+09 5584417.88 0.448807E+09 0.00 0.00
April 0.919162E+09 0.118218E+09 0.436617E+09 0.00 0.436617E+09 0.00 0.00
May 0.962947E+09 0.139797E+09 0.454031E+09 0.00 0.454031E+09 0.00 0.00
June 0.931117E+09 0.148162E+09 0.440737E+09 0.00 0.440737E+09 0.00 0.00
July 0.884918E+09 0.195328E+09 0.462994E+09 0.00 0.462994E+09 0.00 0.00
August 0.873827E+09 0.170320E+09 0.453050E+09 497.22 0.453050E+09 0.00 0.00
September 0.853858E+09 0.168630E+09 0.435182E+09 3733573.75 0.431448E+09 0.00 0.00
October 0.101409E+10 0.204178E+09 0.543403E+09 56468659.11 0.486934E+09 0.00 0.00
November 0.143599E+10 0.219277E+09 0.770054E+09 0.221137E+09 0.548918E+09 0.00 0.00
December 0.188060E+10 0.312747E+09 0.103136E+10 0.434820E+09 0.596542E+09 0.00 0.00
               
Annual Sum or Average 0.139431E+11 0.237302E+10 0.718092E+10 0.132060E+10 0.586032E+10 0.00 0.00
Minimum of Months 0.853858E+09 0.118218E+09 0.435182E+09 0.00 0.431448E+09 0.00 0.00
Maximum of Months 0.188060E+10 0.312747E+09 0.103136E+10 0.434820E+09 0.598646E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.725031E+09 0.146021E+09 0.403179E+09 0.136177E+09 0.267002E+09 0.00 0.00
February 0.762654E+09 0.109566E+09 0.412104E+09 0.150600E+09 0.261504E+09 0.00 0.00
March 0.945008E+09 97634621.37 0.495070E+09 0.190946E+09 0.304125E+09 0.00 0.00
April 0.925421E+09 65491848.79 0.482677E+09 0.182126E+09 0.300551E+09 0.00 0.00
May 0.844618E+09 73269995.12 0.428227E+09 0.128924E+09 0.299303E+09 0.00 0.00
June 0.865703E+09 78308176.80 0.441208E+09 0.144114E+09 0.297094E+09 0.00 0.00
July 0.715729E+09 0.105845E+09 0.387354E+09 86854153.34 0.300500E+09 0.00 0.00
August 0.791872E+09 91852689.35 0.427858E+09 0.125294E+09 0.302564E+09 0.00 0.00
September 0.728574E+09 90760699.28 0.388993E+09 0.106007E+09 0.282986E+09 0.00 0.00
October 0.681630E+09 0.106661E+09 0.377972E+09 97290058.41 0.280682E+09 0.00 0.00
November 0.646779E+09 0.108478E+09 0.355587E+09 98963546.74 0.256623E+09 0.00 0.00
December 0.677830E+09 0.153077E+09 0.378020E+09 0.121963E+09 0.256057E+09 0.00 0.00
               
Annual Sum or Average 0.931085E+10 0.122697E+10 0.497825E+10 0.156926E+10 0.340899E+10 0.00 0.00
Minimum of Months 0.646779E+09 65491848.79 0.355587E+09 86854153.34 0.256057E+09 0.00 0.00
Maximum of Months 0.945008E+09 0.153077E+09 0.495070E+09 0.190946E+09 0.304125E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.614021E+09 0.219511E+09 0.320640E+09 0.00 0.320640E+09 0.00 0.00
February 0.624622E+09 0.164827E+09 0.310341E+09 0.00 0.310341E+09 0.00 0.00
March 0.758751E+09 0.144091E+09 0.355268E+09 0.00 0.355268E+09 0.00 0.00
April 0.767651E+09 93298061.09 0.360719E+09 2783539.57 0.357935E+09 0.00 0.00
May 0.881654E+09 0.108473E+09 0.410502E+09 24063366.09 0.386439E+09 0.00 0.00
June 0.963635E+09 0.118105E+09 0.456057E+09 60634245.43 0.395423E+09 0.00 0.00
July 0.821605E+09 0.156305E+09 0.426283E+09 27369749.75 0.398914E+09 0.00 0.00
August 0.752282E+09 0.132470E+09 0.383454E+09 8100750.04 0.375354E+09 0.00 0.00
September 0.687814E+09 0.131520E+09 0.345965E+09 119365.70 0.345846E+09 0.00 0.00
October 0.646048E+09 0.155589E+09 0.344171E+09 0.00 0.344171E+09 0.00 0.00
November 0.603028E+09 0.157212E+09 0.315513E+09 0.00 0.315513E+09 0.00 0.00
December 0.590180E+09 0.228702E+09 0.310547E+09 0.00 0.310547E+09 0.00 0.00
               
Annual Sum or Average 0.871129E+10 0.181010E+10 0.433946E+10 0.123071E+09 0.421639E+10 0.00 0.00
Minimum of Months 0.590180E+09 93298061.09 0.310341E+09 0.00 0.310341E+09 0.00 0.00
Maximum of Months 0.963635E+09 0.228702E+09 0.456057E+09 60634245.43 0.398914E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.751892E+09 0.162789E+09 0.409172E+09 0.144410E+09 0.264761E+09 0.00 0.00
February 0.760710E+09 0.124744E+09 0.403958E+09 0.141994E+09 0.261964E+09 0.00 0.00
March 0.963847E+09 0.114502E+09 0.499992E+09 0.194701E+09 0.305291E+09 0.00 0.00
April 0.928265E+09 76917182.23 0.484369E+09 0.183595E+09 0.300774E+09 0.00 0.00
May 0.838559E+09 79227511.59 0.424322E+09 0.125172E+09 0.299151E+09 0.00 0.00
June 0.873543E+09 83951256.52 0.446554E+09 0.152763E+09 0.293791E+09 0.00 0.00
July 0.724337E+09 0.113782E+09 0.391383E+09 92479555.34 0.298903E+09 0.00 0.00
August 0.787186E+09 98805927.61 0.426250E+09 0.125601E+09 0.300649E+09 0.00 0.00
September 0.724142E+09 96302352.95 0.386472E+09 0.107318E+09 0.279155E+09 0.00 0.00
October 0.680075E+09 0.114831E+09 0.376219E+09 97557860.89 0.278661E+09 0.00 0.00
November 0.653248E+09 0.116604E+09 0.356588E+09 97935620.35 0.258652E+09 0.00 0.00
December 0.695064E+09 0.167850E+09 0.379691E+09 0.124867E+09 0.254824E+09 0.00 0.00
               
Annual Sum or Average 0.938087E+10 0.135031E+10 0.498497E+10 0.158839E+10 0.339658E+10 0.00 0.00
Minimum of Months 0.653248E+09 76917182.23 0.356588E+09 92479555.34 0.254824E+09 0.00 0.00
Maximum of Months 0.963847E+09 0.167850E+09 0.499992E+09 0.194701E+09 0.305291E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 26.42 22.38 20.70 2.25 18.66 103.85 146.57 0.01
February 27.50 22.91 21.01 2.37 18.54 110.59 164.59 0.00
March 28.33 23.63 21.77 3.67 19.85 110.33 194.39 0.01
April 29.15 25.37 24.04 2.98 21.51 118.69 185.56 0.03
May 29.01 26.53 25.72 3.19 23.00 127.71 124.87 0.08
June 28.86 26.50 25.74 3.10 22.78 123.38 156.09 0.05
July 27.25 24.29 23.20 2.32 21.53 137.39 88.28 0.02
August 27.54 25.86 25.31 3.22 21.55 129.55 122.00 0.07
September 27.58 25.59 24.93 2.22 22.01 128.30 103.37 0.04
October 26.89 25.07 24.46 2.18 21.39 123.79 92.41 0.11
November 26.68 24.14 23.20 1.94 20.29 113.70 103.30 0.02
December 25.97 22.85 21.57 2.00 18.63 101.83 131.96 0.00
                 
Annual Sum or Average 27.59 24.60 23.48 2.62 20.82 119.14 134.17 0.04
Minimum of Months 25.97 22.38 20.70 1.94 18.54 101.83 88.28 0.00
Maximum of Months 29.15 26.53 25.74 3.67 23.00 137.39 194.39 0.11



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 34.10 04-JAN-12:00 23.67 19.40 5.00 24.66 266.50 576.50
February 35.00 21-FEB-13:00 22.02 16.00 2.10 24.16 230.00 672.50
March 36.40 21-MAR-12:00 23.01 17.00 5.00 26.97 269.50 658.50
April 35.50 01-APR-13:00 26.96 24.00 2.50 27.14 295.50 519.50
May 37.60 06-MAY-12:00 26.43 22.60 4.00 29.39 317.00 525.50
June 36.00 12-JUN-14:00 27.60 25.00 4.00 28.43 235.00 472.00
July 33.20 15-JUL-15:00 25.63 23.00 2.00 27.95 219.00 181.00
August 34.00 10-AUG-13:00 27.86 26.00 5.00 26.65 344.50 278.50
September 34.00 06-SEP-13:00 26.51 24.00 4.00 25.00 258.00 581.50
October 33.00 04-OCT-13:00 26.23 24.00 4.00 25.16 303.00 428.50
November 34.30 18-NOV-12:00 25.34 22.20 3.00 25.49 289.50 511.50
December 33.00 07-DEC-13:00 23.23 19.00 3.00 22.98 215.00 596.00
                 
Annual Sum or Average                
Minimum of Months 33.00   22.02 16.00 2.00 22.98 215.00 181.00
Maximum of Months 37.60   27.86 26.00 5.00 29.39 344.50 672.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 18.70 23-JAN-05:00 16.92 16.00 2.00 7.75 0.00 0.00
February 20.30 21-FEB-09:00 19.04 18.40 2.00 10.50 258.50 564.00
March 22.00 03-MAR-05:00 19.94 19.00 3.00 13.35 0.00 0.00
April 22.90 14-APR-15:00 22.90 22.90 3.00 14.65 199.50 264.50
May 22.00 10-MAY-19:00 22.00 22.00 2.00 18.28 0.00 0.00
June 23.00 20-JUN-23:00 23.00 23.00 2.00 19.35 0.00 0.00
July 23.00 13-JUL-04:00 22.27 22.00 0.00 13.91 0.00 0.00
August 22.00 20-AUG-10:00 22.00 22.00 5.00 18.28 430.50 41.50
September 22.90 19-SEP-03:00 22.78 22.78 0.00 21.27 0.00 0.00
October 22.50 23-OCT-04:00 22.50 22.50 2.80 18.82 0.00 0.00
November 20.00 25-NOV-04:00 18.63 18.00 2.00 10.69 0.00 0.00
December 18.00 21-DEC-04:00 17.36 17.00 3.00 9.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 18.00   16.92 16.00 0.00 7.75 0.00 0.00
Maximum of Months 23.00   23.00 23.00 5.00 21.27 430.50 564.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 25.53 12-JAN-12:00 32.40 23.10 2.00 25.00 353.00 347.00
February 26.17 14-FEB-15:00 32.30 24.20 2.00 25.16 200.00 199.00
March 26.28 27-MAR-12:00 34.20 23.60 4.00 26.32 326.00 535.00
April 27.93 10-APR-16:49 31.52 26.85 4.08 27.70 110.67 57.00
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 30.11 15-JUN-09:00 33.20 29.20 5.00 26.48 320.50 421.00
July 26.43 20-JUL-14:00 32.80 24.20 1.00 26.65 305.00 253.00
August 28.81 14-AUG-16:00 32.00 28.00 1.00 25.16 107.50 223.00
September 30.06 30-SEP-10:00 32.80 29.40 3.00 25.66 398.00 359.50
October 27.36 16-OCT-14:00 31.50 26.00 3.00 24.16 239.00 346.50
November 27.56 10-NOV-12:00 31.00 26.40 6.00 28.11 388.00 95.50
December 26.86 03-DEC-12:00 31.50 25.30 1.00 23.49 301.00 468.50
                 
Annual Sum or Average                
Minimum of Months 25.53   29.00 23.10 1.00 22.47 0.00 0.00
Maximum of Months 30.11   34.20 29.40 6.00 28.11 398.00 535.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.20 09-JAN-21:00 26.50 24.77 4.00 25.16 0.00 0.00
February 24.40 15-FEB-18:00 28.30 25.33 4.00 20.75 0.00 0.00
March 25.30 28-MAR-06:00 27.20 25.72 3.00 19.87 103.00 28.00
April 27.00 10-APR-17:00 30.50 27.87 4.50 25.00 20.00 20.50
May 29.00 28-MAY-20:00 29.00 29.00 3.00 22.47 0.00 0.00
June 29.20 15-JUN-09:00 33.20 30.11 5.00 26.48 320.50 421.00
July 26.00 10-JUL-14:00 26.50 26.11 2.30 23.49 286.00 36.50
August 28.00 02-AUG-10:00 31.00 28.65 4.00 24.16 419.00 195.50
September 29.40 30-SEP-10:00 32.80 30.06 3.00 25.66 398.00 359.50
October 26.50 16-OCT-08:00 29.00 27.04 2.50 21.78 300.00 326.00
November 26.40 10-NOV-12:00 31.00 27.56 6.00 28.11 388.00 95.50
December 26.00 10-DEC-17:00 29.00 26.74 3.00 21.78 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 24.20   26.50 24.77 2.30 19.87 0.00 0.00
Maximum of Months 29.40   33.20 30.11 6.00 28.11 419.00 421.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 29.71 38.82 0.00
February 18.00 13.00 16.00 29.90 44.34 0.00
March 18.00 13.00 16.00 30.35 50.49 0.00
April 18.00 13.00 16.00 30.97 51.18 0.00
May 18.00 13.00 16.00 31.58 43.47 0.00
June 18.00 13.00 16.00 32.02 46.77 0.00
July 18.00 13.00 16.00 32.16 39.95 0.00
August 18.00 13.00 16.00 31.97 43.65 0.00
September 18.00 13.00 16.00 31.50 40.53 0.00
October 18.00 13.00 16.00 30.87 37.35 0.00
November 18.00 13.00 16.00 30.27 35.77 0.00
December 18.00 13.00 16.00 29.84 36.19 0.00
             
Annual Sum or Average 18.00 13.00 16.00 30.93 42.35 0.00
Minimum of Months 18.00 13.00 16.00 29.71 35.77 0.00
Maximum of Months 18.00 13.00 16.00 32.16 51.18 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.361135E+09 -297694137.4 0.00 0.00 744.00 0.00 -63441346.0 58.99 0.00 0.00
February 0.324967E+09 -267645939.7 0.00 0.00 672.00 0.00 -57320605.5 58.99 0.00 0.00
March 0.382482E+09 -318793055.8 0.00 0.00 744.00 0.00 -63689191.3 58.99 0.00 0.00
April 0.332027E+09 -271282679.7 0.00 0.00 720.00 0.00 -60744533.0 58.98 0.00 0.00
May 0.354519E+09 -291981997.3 0.00 0.00 744.00 0.00 -62537044.8 59.03 0.00 0.00
June 0.347501E+09 -287199571.0 0.00 0.00 720.00 0.00 -60301845.6 58.99 0.00 0.00
July 0.322801E+09 -259753339.1 0.00 0.00 744.00 0.00 -63047873.8 58.99 0.00 0.00
August 0.364319E+09 -300900523.8 0.00 0.00 744.00 0.00 -63418700.5 58.99 0.00 0.00
September 0.327360E+09 -266359747.9 0.00 0.00 720.00 0.00 -61000071.0 58.98 0.00 0.00
October 0.349266E+09 -285914251.3 0.00 0.00 744.00 0.00 -63351798.0 58.99 0.00 0.00
November 0.353691E+09 -291975865.9 0.00 0.00 720.00 0.00 -61715148.3 58.99 0.00 0.00
December 0.345976E+09 -282194605.9 0.00 0.00 744.00 0.00 -63780984.0 58.99 0.00 0.00
                     
Annual Sum or Average 0.416604E+10 -0.342170E+10 0.00 0.00 8760.00 0.00 -744349141.7 58.99 0.00 0.00
Minimum of Months 0.322801E+09 -318793055.8 0.00 0.00 672.00 0.00 -63780984.0 58.98 0.00 0.00
Maximum of Months 0.382482E+09 -259753339.1 0.00 0.00 744.00 0.00 -57320605.5 59.03 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.79 0.76 01-JAN-07:49 785.42 22.75 109.50 287.50 459.68 26.40 335.50 260.50
February 321.17 0.79 0.76 01-FEB-07:30 478.77 18.04 0.00 242.00 347.14 22.21 249.33 192.33
March 361.17 0.79 0.76 01-MAR-08:20 376.10 17.48 0.00 242.33 268.36 21.64 265.83 10.00
April 358.33 0.80 0.76 01-APR-07:00 315.15 16.93 0.00 125.67 228.87 21.14 227.00 0.00
May 376.33 0.83 0.76 01-MAY-08:20 262.50 15.78 0.00 12.17 190.18 19.91 100.33 0.00
June 370.50 0.83 0.76 01-JUN-13:00 260.31 15.90 0.00 0.00 191.69 20.13 112.83 0.00
July 383.17 0.84 0.76 01-JUL-08:30 244.93 15.33 0.00 3.17 175.28 19.38 26.00 0.00
August 369.33 0.81 0.76 01-AUG-08:09 293.33 16.35 0.00 87.67 210.99 20.48 155.67 0.00
September 357.83 0.81 0.76 01-SEP-07:40 324.58 16.35 0.00 158.50 230.63 20.40 172.50 11.33
October 356.83 0.80 0.76 01-OCT-08:09 410.99 17.71 6.67 234.00 289.55 21.61 239.67 113.83
November 337.67 0.79 0.76 01-NOV-06:00 549.52 20.72 59.17 258.83 364.57 22.86 258.00 186.33
December 349.33 0.78 0.76 01-DEC-06:49 819.09 24.36 136.00 293.17 461.35 26.35 329.33 252.50
                         
Annual Sum or Average 4292.33 0.80     421.65 18.07 311.33 1945.00 281.76 21.82 2472.00 1026.83
Minimum of Months 321.17 0.78 0.76   244.93 15.33 0.00 0.00 175.28 19.38 26.00 0.00
Maximum of Months 383.17 0.84 0.76   819.09 24.36 136.00 293.17 461.35 26.40 335.50 260.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.82 0.76 01-JAN-08:30 361.06 17.54 25.50 146.00 464.50 20.37 74.50 112.33
February 321.17 0.82 0.76 01-FEB-07:10 360.06 17.17 0.00 129.67 286.74 16.62 0.00 95.00
March 361.17 0.83 0.76 01-MAR-08:09 346.56 16.58 0.00 132.33 290.73 16.13 0.00 106.50
April 358.33 0.82 0.76 01-APR-06:49 343.72 16.09 0.00 128.50 292.90 15.68 0.00 108.33
May 376.33 0.83 0.76 01-MAY-06:40 310.91 15.09 0.00 111.00 254.06 14.40 0.00 75.33
June 370.50 0.83 0.76 01-JUN-07:00 336.12 15.20 0.00 134.17 278.07 14.70 0.00 101.17
July 383.17 0.84 0.76 01-JUL-07:10 295.29 14.62 0.00 111.50 232.44 13.75 0.00 75.50
August 369.33 0.83 0.76 01-AUG-06:40 323.52 15.66 0.00 119.33 263.29 14.98 0.00 86.83
September 357.83 0.83 0.76 01-SEP-06:40 309.34 15.68 0.00 112.00 246.06 14.86 0.00 71.50
October 356.83 0.83 0.76 01-OCT-06:40 328.90 16.82 3.33 123.00 251.51 15.91 0.00 76.17
November 337.67 0.82 0.76 01-NOV-07:30 373.70 17.82 11.00 133.00 263.25 16.99 5.83 80.00
December 349.33 0.83 0.76 01-DEC-06:00 577.51 19.31 62.17 145.33 353.97 19.48 54.50 93.17
                         
Annual Sum or Average 4292.33 0.83     354.29 16.42 102.00 1525.83 288.94 16.10 134.83 1081.83
Minimum of Months 321.17 0.82 0.76   295.29 14.62 0.00 111.00 232.44 13.75 0.00 71.50
Maximum of Months 383.17 0.84 0.76   577.51 19.31 62.17 146.00 464.50 20.37 74.50 112.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.87 0.82 26-JAN-14:09 196.68 0.00 0.00 0.00 138.72 0.00 0.00 0.00
February 321.17 0.86 0.76 14-FEB-14:20 218.19 0.00 0.00 0.00 153.12 0.00 0.00 0.00
March 361.17 0.83 0.76 02-MAR-13:50 253.08 0.00 0.00 0.00 175.87 0.00 0.00 0.00
April 358.33 0.80 0.76 01-APR-07:49 310.78 0.00 0.00 93.67 209.35 0.00 0.00 0.00
May 376.33 0.80 0.76 01-MAY-06:00 340.96 0.00 0.00 164.83 225.63 0.00 0.00 0.00
June 370.50 0.79 0.76 01-JUN-08:20 395.66 0.00 0.00 262.83 269.88 0.00 0.00 2.67
July 383.17 0.80 0.76 01-JUL-07:30 335.53 0.00 0.00 174.67 223.02 0.00 0.00 0.00
August 369.33 0.80 0.76 01-AUG-07:19 326.30 0.00 0.00 134.33 215.31 0.00 0.00 0.00
September 357.83 0.83 0.76 01-SEP-07:00 260.98 0.00 0.00 15.83 175.05 0.00 0.00 0.00
October 356.83 0.85 0.76 02-OCT-13:20 230.79 0.00 0.00 0.00 155.71 0.00 0.00 0.00
November 337.67 0.87 0.81 23-NOV-13:50 208.13 0.00 0.00 0.00 142.15 0.00 0.00 0.00
December 349.33 0.88 0.83 12-DEC-13:30 190.63 0.00 0.00 0.00 133.77 0.00 0.00 0.00
                         
Annual Sum or Average 4292.33 0.83     274.54 0.00 0.00 846.17 186.18 0.00 0.00 2.67
Minimum of Months 321.17 0.79 0.76   190.63 0.00 0.00 0.00 133.77 0.00 0.00 0.00
Maximum of Months 383.17 0.88 0.83   395.66 0.00 0.00 262.83 269.88 0.00 0.00 2.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 350.67 0.82 0.76 01-JAN-12:09 360.37 17.56 21.33 145.00 498.09 20.52 75.33 110.00
February 321.17 0.83 0.76 01-FEB-11:30 357.25 17.12 0.00 126.17 281.03 16.52 0.00 93.83
March 361.17 0.83 0.76 01-MAR-11:09 348.26 16.57 0.00 132.17 290.77 16.10 0.00 105.33
April 358.33 0.83 0.76 01-APR-11:50 340.95 16.09 0.00 125.50 287.77 15.64 0.00 102.00
May 376.33 0.83 0.76 01-MAY-11:50 311.15 15.09 0.00 117.50 251.50 14.36 0.00 82.33
June 370.50 0.83 0.76 01-JUN-12:20 332.87 15.20 0.00 129.00 273.54 14.68 0.00 90.83
July 383.17 0.84 0.76 01-JUL-12:39 294.13 14.58 0.00 111.00 230.25 13.68 0.00 68.67
August 369.33 0.83 0.76 01-AUG-11:00 319.94 15.63 0.00 117.83 258.13 14.91 0.00 82.17
September 357.83 0.84 0.76 01-SEP-12:20 305.93 15.69 0.00 111.33 240.72 14.84 0.00 63.17
October 356.83 0.83 0.76 01-OCT-10:50 326.45 16.87 1.50 124.67 259.86 16.22 6.83 68.83
November 337.67 0.82 0.76 01-NOV-10:39 348.32 17.60 6.00 135.00 347.69 19.16 56.17 94.50
December 349.33 0.83 0.76 01-DEC-10:20 356.15 17.55 36.17 145.00 418.76 20.20 70.83 97.00
                         
Annual Sum or Average 4292.33 0.83     332.77 16.26 65.00 1520.17 301.74 16.34 209.17 1058.67
Minimum of Months 321.17 0.82 0.76   294.13 14.58 0.00 111.00 230.25 13.68 0.00 63.17
Maximum of Months 383.17 0.84 0.76   360.37 17.60 36.17 145.00 498.09 20.52 75.33 110.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.580502E+10 0.415091E+10 8326.06 11-JAN-07:01 4581.63 0.00
February 0.00 0.00 0.525143E+10 0.376397E+10 8394.08 16-FEB-07:02 4347.01 0.00
March 0.00 0.00 0.650171E+10 0.455622E+10 8401.31 24-MAR-06:02 4354.37 0.00
April 0.00 0.00 0.605584E+10 0.400223E+10 8447.99 11-APR-05:03 4578.28 0.00
May 0.00 0.00 0.695557E+10 0.429304E+10 8475.64 18-MAY-06:02 3971.90 0.00
June 0.00 0.00 0.697567E+10 0.431171E+10 8473.18 30-JUN-06:02 4087.33 0.00
July 0.00 0.00 0.589011E+10 0.389307E+10 8417.93 28-JUL-06:02 4260.91 0.00
August 0.00 0.00 0.699667E+10 0.424582E+10 8475.83 04-AUG-06:02 3904.07 0.00
September 0.00 0.00 0.605292E+10 0.376777E+10 8471.00 15-SEP-06:02 4099.15 0.00
October 0.00 0.00 0.620697E+10 0.388766E+10 8472.26 26-OCT-06:02 3933.57 0.00
November 0.00 0.00 0.599951E+10 0.393967E+10 8417.75 16-NOV-07:02 4304.68 0.00
December 0.00 0.00 0.527308E+10 0.370283E+10 8306.76 11-DEC-06:02 4938.34 0.00
                 
Annual Sum or Average 0.00 0.00 0.739645E+11 0.485149E+11       0.00
Minimum of Months 0.00 0.00 0.525143E+10 0.370283E+10 8306.76   3904.07 0.00
Maximum of Months 0.00 0.00 0.699667E+10 0.455622E+10 8475.83   4938.34 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.646747E+10 0.485884E+10 8967.38 10-JAN-07:02 4562.16 0.00
February 0.00 0.00 0.572735E+10 0.429079E+10 8968.19 15-FEB-07:01 4588.39 0.00
March 0.00 0.00 0.661024E+10 0.473443E+10 8969.85 13-MAR-05:02 5040.16 0.00
April 0.00 0.00 0.633265E+10 0.424717E+10 8970.05 24-APR-05:02 4802.15 0.00
May 0.00 0.00 0.737824E+10 0.459025E+10 8973.91 09-MAY-05:02 4356.83 0.00
June 0.00 0.00 0.738873E+10 0.459856E+10 8974.37 21-JUN-06:03 4160.02 0.00
July 0.00 0.00 0.597201E+10 0.401608E+10 8973.76 07-JUL-06:02 4443.97 0.00
August 0.00 0.00 0.721408E+10 0.441410E+10 8973.42 30-AUG-06:03 4125.47 0.00
September 0.00 0.00 0.627683E+10 0.395227E+10 8973.60 19-SEP-06:03 4118.24 0.00
October 0.00 0.00 0.638387E+10 0.405415E+10 8974.30 31-OCT-06:02 4378.37 0.00
November 0.00 0.00 0.648979E+10 0.442744E+10 8973.80 29-NOV-07:02 4468.00 0.00
December 0.00 0.00 0.602872E+10 0.447204E+10 8944.60 12-DEC-07:02 4607.07 0.00
                 
Annual Sum or Average 0.00 0.00 0.782700E+11 0.526561E+11       0.00
Minimum of Months 0.00 0.00 0.572735E+10 0.395227E+10 8944.60   4118.24 0.00
Maximum of Months 0.00 0.00 0.738873E+10 0.485884E+10 8974.37   5040.16 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.330355E+10 0.265446E+10 6138.23 09-JAN-06:02 3454.41 0.00
February 0.00 0.00 0.318549E+10 0.258482E+10 6132.69 16-FEB-07:02 3265.47 0.00
March 0.00 0.00 0.400898E+10 0.317626E+10 6135.12 13-MAR-05:02 3712.75 0.00
April 0.00 0.00 0.394874E+10 0.300399E+10 6135.26 24-APR-05:02 3703.69 0.00
May 0.00 0.00 0.448392E+10 0.322961E+10 6137.90 09-MAY-05:02 3312.00 0.00
June 0.00 0.00 0.458115E+10 0.332088E+10 6138.22 21-JUN-06:02 3189.29 0.00
July 0.00 0.00 0.353397E+10 0.268765E+10 6135.46 24-JUL-05:02 3625.65 0.00
August 0.00 0.00 0.427846E+10 0.304550E+10 6137.57 04-AUG-06:05 2741.21 0.00
September 0.00 0.00 0.372645E+10 0.270942E+10 6137.57 18-SEP-06:02 3156.92 0.00
October 0.00 0.00 0.356532E+10 0.257285E+10 6138.02 23-OCT-06:02 3060.74 0.00
November 0.00 0.00 0.339175E+10 0.255012E+10 6137.88 20-NOV-06:02 3628.79 0.00
December 0.00 0.00 0.299452E+10 0.237615E+10 6138.12 11-DEC-06:02 3394.51 0.00
                 
Annual Sum or Average 0.00 0.00 0.450023E+11 0.339117E+11       0.00
Minimum of Months 0.00 0.00 0.299452E+10 0.237615E+10 6132.69   2741.21 0.00
Maximum of Months 0.00 0.00 0.458115E+10 0.332088E+10 6138.23   3712.75 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.489989E+10 0.375974E+10 8956.78 09-JAN-06:02 4674.71 0.00
February 0.00 0.00 0.460249E+10 0.356203E+10 8944.65 16-FEB-07:02 4535.41 0.00
March 0.00 0.00 0.586018E+10 0.442715E+10 8952.24 13-MAR-05:02 4941.21 0.00
April 0.00 0.00 0.573347E+10 0.414538E+10 8952.44 24-APR-05:02 4761.25 0.00
May 0.00 0.00 0.683081E+10 0.469510E+10 8956.29 09-MAY-05:02 4691.64 0.00
June 0.00 0.00 0.703064E+10 0.486622E+10 8956.29 26-JUN-05:02 5112.11 0.00
July 0.00 0.00 0.553313E+10 0.404408E+10 8952.73 24-JUL-05:04 4840.63 0.00
August 0.00 0.00 0.651134E+10 0.439524E+10 8955.81 04-AUG-06:02 3978.96 0.00
September 0.00 0.00 0.562835E+10 0.388952E+10 8955.81 18-SEP-06:02 4324.03 0.00
October 0.00 0.00 0.545717E+10 0.374905E+10 8956.47 23-OCT-06:02 4239.84 0.00
November 0.00 0.00 0.517473E+10 0.370798E+10 8956.44 06-NOV-06:02 4698.63 0.00
December 0.00 0.00 0.442365E+10 0.334878E+10 8956.61 11-DEC-06:02 4335.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.676858E+11 0.485903E+11       0.00
Minimum of Months 0.00 0.00 0.442365E+10 0.334878E+10 8944.65   3978.96 0.00
Maximum of Months 0.00 0.00 0.703064E+10 0.486622E+10 8956.78   5112.11 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.341139E+10 0.273599E+10 7272.94 09-JAN-06:02 4368.19 0.00
February 0.00 0.00 0.323665E+10 0.261687E+10 7266.73 16-FEB-07:02 3995.09 0.00
March 0.00 0.00 0.412397E+10 0.325569E+10 7278.60 24-MAR-06:02 3930.48 0.00
April 0.00 0.00 0.401688E+10 0.304414E+10 7285.07 10-APR-05:02 4251.22 0.00
May 0.00 0.00 0.457009E+10 0.329381E+10 7288.67 17-MAY-06:02 3593.59 0.00
June 0.00 0.00 0.465700E+10 0.337081E+10 7284.87 21-JUN-06:02 3867.62 0.00
July 0.00 0.00 0.358702E+10 0.272063E+10 7271.85 28-JUL-06:02 3966.05 0.00
August 0.00 0.00 0.433808E+10 0.307272E+10 7288.40 04-AUG-06:03 3449.90 0.00
September 0.00 0.00 0.379067E+10 0.275016E+10 7288.40 18-SEP-06:03 3674.50 0.00
October 0.00 0.00 0.364166E+10 0.262548E+10 7288.94 23-OCT-06:02 3718.82 0.00
November 0.00 0.00 0.348323E+10 0.261700E+10 7284.81 13-NOV-06:03 3513.51 0.00
December 0.00 0.00 0.308483E+10 0.244198E+10 7289.05 11-DEC-06:02 4304.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.459415E+11 0.345453E+11       0.00
Minimum of Months 0.00 0.00 0.308483E+10 0.244198E+10 7266.73   3449.90 0.00
Maximum of Months 0.00 0.00 0.465700E+10 0.337081E+10 7289.05   4368.19 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 65.42 324.83 12-JAN-12:20
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     5.56    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   65.42 324.83  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.345489E+09 0.35 349.44 02-JAN-06:02 0.91
February 0.311171E+09 0.34 349.44 01-FEB-06:10 0.90
March 0.376143E+09 0.36 349.44 01-MAR-06:10 0.90
April 0.327080E+09 0.33 349.44 03-APR-05:01 0.90
May 0.363030E+09 0.36 349.44 01-MAY-05:02 0.90
June 0.362855E+09 0.37 349.44 01-JUN-05:03 0.90
July 0.327080E+09 0.32 349.44 03-JUL-05:02 0.90
August 0.376233E+09 0.36 349.44 01-AUG-05:03 0.90
September 0.328265E+09 0.33 349.44 01-SEP-05:10 0.90
October 0.343815E+09 0.33 349.44 02-OCT-05:02 0.90
November 0.343434E+09 0.34 349.44 01-NOV-05:10 0.90
December 0.327080E+09 0.32 349.44 01-DEC-06:10 0.90
           
Annual Sum or Average 0.413168E+10 0.34      
Minimum of Months 0.311171E+09 0.32 349.44   0.90
Maximum of Months 0.376233E+09 0.37 349.44   0.91



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.409971E+09 0.39 403.98 02-JAN-06:02 0.90
February 0.367996E+09 0.38 403.98 01-FEB-06:10 0.90
March 0.437869E+09 0.38 403.98 01-MAR-06:10 0.90
April 0.383200E+09 0.35 403.98 02-APR-16:32 0.90
May 0.428398E+09 0.40 403.98 01-MAY-05:02 0.90
June 0.426866E+09 0.41 403.98 01-JUN-05:03 0.90
July 0.380840E+09 0.33 403.98 03-JUL-05:02 0.90
August 0.438344E+09 0.38 403.98 01-AUG-05:03 0.90
September 0.383586E+09 0.35 403.98 01-SEP-05:10 0.90
October 0.402848E+09 0.36 403.98 02-OCT-05:02 0.90
November 0.403252E+09 0.37 403.98 01-NOV-05:10 0.90
December 0.390938E+09 0.37 403.98 01-DEC-06:10 0.90
           
Annual Sum or Average 0.485411E+10 0.37      
Minimum of Months 0.367996E+09 0.33 403.98   0.90
Maximum of Months 0.438344E+09 0.41 403.98   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.299137E+09 0.35 302.07 02-JAN-06:02 0.90
February 0.273235E+09 0.37 302.07 01-FEB-06:10 0.90
March 0.331009E+09 0.40 302.07 01-MAR-06:10 0.90
April 0.293496E+09 0.40 302.07 02-APR-09:32 0.90
May 0.327366E+09 0.44 302.07 01-MAY-05:02 0.90
June 0.324036E+09 0.44 302.07 01-JUN-05:03 0.90
July 0.287888E+09 0.36 302.07 03-JUL-05:02 0.90
August 0.330114E+09 0.39 302.07 01-AUG-05:03 0.90
September 0.290842E+09 0.38 302.07 01-SEP-05:10 0.90
October 0.301307E+09 0.36 302.07 02-OCT-05:02 0.90
November 0.298040E+09 0.35 302.07 01-NOV-05:10 0.90
December 0.285094E+09 0.34 302.07 01-DEC-06:10 0.90
           
Annual Sum or Average 0.364156E+10 0.38      
Minimum of Months 0.273235E+09 0.34 302.07   0.90
Maximum of Months 0.331009E+09 0.44 302.07   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.396768E+09 0.34 402.91 02-JAN-06:02 0.90
February 0.359935E+09 0.34 402.91 01-FEB-06:10 0.90
March 0.436083E+09 0.38 402.91 01-MAR-06:10 0.90
April 0.382158E+09 0.35 402.91 02-APR-16:12 0.90
May 0.428654E+09 0.41 402.91 01-MAY-05:02 0.90
June 0.429801E+09 0.42 402.91 01-JUN-05:03 0.90
July 0.381311E+09 0.34 402.91 03-JUL-05:02 0.90
August 0.437286E+09 0.38 402.91 01-AUG-05:03 0.90
September 0.382103E+09 0.35 402.91 01-SEP-05:10 0.90
October 0.397763E+09 0.34 402.91 02-OCT-05:02 0.90
November 0.395984E+09 0.34 402.91 01-NOV-05:10 0.90
December 0.377128E+09 0.32 402.91 01-DEC-06:10 0.90
           
Annual Sum or Average 0.480497E+10 0.36      
Minimum of Months 0.359935E+09 0.32 402.91   0.90
Maximum of Months 0.437286E+09 0.42 402.91   0.90



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.363064E+09 0.37 364.36 02-JAN-06:02 0.90
February 0.330167E+09 0.38 364.36 01-FEB-06:10 0.90
March 0.401103E+09 0.41 364.36 01-MAR-06:10 0.90
April 0.354146E+09 0.40 364.36 01-APR-15:53 0.90
May 0.391309E+09 0.43 364.36 01-MAY-05:02 0.90
June 0.389240E+09 0.43 364.36 01-JUN-05:03 0.90
July 0.348101E+09 0.37 364.36 03-JUL-05:02 0.90
August 0.399516E+09 0.40 364.36 01-AUG-05:03 0.90
September 0.350995E+09 0.38 364.36 01-SEP-05:10 0.90
October 0.363518E+09 0.37 364.36 02-OCT-05:02 0.90
November 0.360872E+09 0.36 364.36 01-NOV-05:10 0.90
December 0.345400E+09 0.34 364.36 01-DEC-06:10 0.90
           
Annual Sum or Average 0.439743E+10 0.39      
Minimum of Months 0.330167E+09 0.34 364.36   0.90
Maximum of Months 0.401103E+09 0.43 364.36   0.90



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.01 0.00 0.00 02-JAN-07:02 0.00 0.00 45.62 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 29.69 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 29.69 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 29.69 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 29.69 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 29.69 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 29.69 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 29.69 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 29.69 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 29.69 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 29.69 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 29.69 0.00
                 
Annual Sum or Average 0.01 0.00            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 29.69 0.00
Maximum of Months 0.01 0.00 0.00   0.00 0.00 45.62 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 65.42 324.83 12-JAN-12:20
February 0.00 0.00 01-FEB-00:10 29.69 29.69 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 29.69 29.69 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 29.69 29.69 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:05 29.69 29.69 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 29.69 29.69 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 29.69 29.69 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 29.69 29.69 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 29.69 29.69 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 29.69 29.69 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 29.69 29.69 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 29.69 29.69 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         5.56    
Minimum of Months 0.00 0.00   29.69 29.69 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 65.42 324.83  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.162410E+10 0.00 0.00
February 0.00 0.00 0.00 0.148230E+10 0.00 0.00
March 0.00 0.00 0.00 0.183393E+10 0.00 0.00
April 0.00 0.00 0.00 0.166524E+10 0.00 0.00
May 0.00 0.00 0.00 0.186849E+10 0.00 0.00
June 0.00 0.00 0.00 0.187845E+10 0.00 0.00
July 0.00 0.00 0.00 0.159213E+10 0.00 0.00
August 0.00 0.00 0.00 0.186727E+10 0.00 0.00
September 0.00 0.00 0.00 0.162255E+10 0.00 0.00
October 0.00 0.00 0.00 0.166202E+10 0.00 0.00
November 0.00 0.00 0.00 0.163672E+10 0.00 0.00
December 0.00 0.00 0.00 0.148358E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.202168E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.148230E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.187845E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.183879E+10 0.00 0.00
February 0.00 0.00 0.00 0.165236E+10 0.00 0.00
March 0.00 0.00 0.00 0.193545E+10 0.00 0.00
April 0.00 0.00 0.00 0.179411E+10 0.00 0.00
May 0.00 0.00 0.00 0.203785E+10 0.00 0.00
June 0.00 0.00 0.00 0.204419E+10 0.00 0.00
July 0.00 0.00 0.00 0.167551E+10 0.00 0.00
August 0.00 0.00 0.00 0.198741E+10 0.00 0.00
September 0.00 0.00 0.00 0.173602E+10 0.00 0.00
October 0.00 0.00 0.00 0.176968E+10 0.00 0.00
November 0.00 0.00 0.00 0.180682E+10 0.00 0.00
December 0.00 0.00 0.00 0.171425E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.219924E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.165236E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.204419E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.105573E+10 0.00 0.00
February 0.00 0.00 0.00 0.101010E+10 0.00 0.00
March 0.00 0.00 0.00 0.126354E+10 0.00 0.00
April 0.00 0.00 0.00 0.120141E+10 0.00 0.00
May 0.00 0.00 0.00 0.134686E+10 0.00 0.00
June 0.00 0.00 0.00 0.136722E+10 0.00 0.00
July 0.00 0.00 0.00 0.107892E+10 0.00 0.00
August 0.00 0.00 0.00 0.128480E+10 0.00 0.00
September 0.00 0.00 0.00 0.112465E+10 0.00 0.00
October 0.00 0.00 0.00 0.109438E+10 0.00 0.00
November 0.00 0.00 0.00 0.106186E+10 0.00 0.00
December 0.00 0.00 0.00 0.968503E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.138580E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.968503E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.136722E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.151474E+10 0.00 0.00
February 0.00 0.00 0.00 0.142277E+10 0.00 0.00
March 0.00 0.00 0.00 0.179348E+10 0.00 0.00
April 0.00 0.00 0.00 0.169205E+10 0.00 0.00
May 0.00 0.00 0.00 0.196198E+10 0.00 0.00
June 0.00 0.00 0.00 0.201120E+10 0.00 0.00
July 0.00 0.00 0.00 0.160592E+10 0.00 0.00
August 0.00 0.00 0.00 0.187574E+10 0.00 0.00
September 0.00 0.00 0.00 0.162882E+10 0.00 0.00
October 0.00 0.00 0.00 0.159931E+10 0.00 0.00
November 0.00 0.00 0.00 0.155223E+10 0.00 0.00
December 0.00 0.00 0.00 0.138242E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.200407E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.138242E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.201120E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.115855E+10 0.00 0.00
February 0.00 0.00 0.00 0.109460E+10 0.00 0.00
March 0.00 0.00 0.00 0.137858E+10 0.00 0.00
April 0.00 0.00 0.00 0.129709E+10 0.00 0.00
May 0.00 0.00 0.00 0.145096E+10 0.00 0.00
June 0.00 0.00 0.00 0.147271E+10 0.00 0.00
July 0.00 0.00 0.00 0.116684E+10 0.00 0.00
August 0.00 0.00 0.00 0.138722E+10 0.00 0.00
September 0.00 0.00 0.00 0.121584E+10 0.00 0.00
October 0.00 0.00 0.00 0.118775E+10 0.00 0.00
November 0.00 0.00 0.00 0.115908E+10 0.00 0.00
December 0.00 0.00 0.00 0.106113E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.150304E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.106113E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.147271E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.345489E+09 0.580502E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.311171E+09 0.525143E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.376143E+09 0.650171E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.327080E+09 0.605584E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.363030E+09 0.695557E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.362855E+09 0.697567E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.327080E+09 0.589011E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.376233E+09 0.699667E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.328265E+09 0.605292E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.343815E+09 0.620697E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.343434E+09 0.599951E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.327080E+09 0.527308E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.413168E+10 0.739645E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.311171E+09 0.525143E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.376233E+09 0.699667E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.409971E+09 0.646747E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.367996E+09 0.572735E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.437869E+09 0.661024E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.383200E+09 0.633265E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.428398E+09 0.737824E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.426866E+09 0.738873E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.380840E+09 0.597201E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.438344E+09 0.721408E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.383586E+09 0.627683E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.402848E+09 0.638387E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.403252E+09 0.648979E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.390938E+09 0.602872E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.485411E+10 0.782700E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.367996E+09 0.572735E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.438344E+09 0.738873E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.299137E+09 0.330355E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.273235E+09 0.318549E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.331009E+09 0.400898E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.293496E+09 0.394874E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.327366E+09 0.448392E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.324036E+09 0.458115E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.287888E+09 0.353397E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.330114E+09 0.427846E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.290842E+09 0.372645E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.301307E+09 0.356532E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.298040E+09 0.339175E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.285094E+09 0.299452E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.364156E+10 0.450023E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.273235E+09 0.299452E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331009E+09 0.458115E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.396768E+09 0.489989E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.359935E+09 0.460249E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.436083E+09 0.586018E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.382158E+09 0.573347E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.428654E+09 0.683081E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.429801E+09 0.703064E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.381311E+09 0.553313E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.437286E+09 0.651134E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.382103E+09 0.562835E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.397763E+09 0.545717E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.395984E+09 0.517473E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.377128E+09 0.442365E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.480497E+10 0.676858E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.359935E+09 0.442365E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.437286E+09 0.703064E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.363064E+09 0.341139E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.330167E+09 0.323665E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.401103E+09 0.412397E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.354146E+09 0.401688E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.391309E+09 0.457009E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.389240E+09 0.465700E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.348101E+09 0.358702E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.399516E+09 0.433808E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350995E+09 0.379067E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.363518E+09 0.364166E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.360872E+09 0.348323E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.345400E+09 0.308483E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.439743E+10 0.459415E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.330167E+09 0.308483E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.401103E+09 0.465700E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.345489E+09 0.00 0.00 0.00 0.127861E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.311171E+09 0.00 0.00 0.00 0.117113E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.376143E+09 0.00 0.00 0.00 0.145779E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.327080E+09 0.00 0.00 0.00 0.133816E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.363030E+09 0.00 0.00 0.00 0.150546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.362855E+09 0.00 0.00 0.00 0.151559E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.327080E+09 0.00 0.00 0.00 0.126505E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.376233E+09 0.00 0.00 0.00 0.149104E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.328265E+09 0.00 0.00 0.00 0.129428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.343815E+09 0.00 0.00 0.00 0.131821E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.343434E+09 0.00 0.00 0.00 0.129328E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.327080E+09 0.00 0.00 0.00 0.115650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.413168E+10 0.00 0.00 0.00 0.160851E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.311171E+09 0.00 0.00 0.00 0.115650E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.376233E+09 0.00 0.00 0.00 0.151559E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.409971E+09 0.00 0.00 0.00 0.142882E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.367996E+09 0.00 0.00 0.00 0.128436E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.437869E+09 0.00 0.00 0.00 0.149758E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.383200E+09 0.00 0.00 0.00 0.141091E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.428398E+09 0.00 0.00 0.00 0.160945E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.426866E+09 0.00 0.00 0.00 0.161733E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.380840E+09 0.00 0.00 0.00 0.129467E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.438344E+09 0.00 0.00 0.00 0.154906E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.383586E+09 0.00 0.00 0.00 0.135244E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.402848E+09 0.00 0.00 0.00 0.136684E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.403252E+09 0.00 0.00 0.00 0.140356E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.390938E+09 0.00 0.00 0.00 0.132331E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.485411E+10 0.00 0.00 0.00 0.171383E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.367996E+09 0.00 0.00 0.00 0.128436E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.438344E+09 0.00 0.00 0.00 0.161733E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.299137E+09 0.00 0.00 0.00 0.756590E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.273235E+09 0.00 0.00 0.00 0.736867E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.331009E+09 0.00 0.00 0.00 0.932527E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.293496E+09 0.00 0.00 0.00 0.907911E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.327366E+09 0.00 0.00 0.00 0.101950E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.324036E+09 0.00 0.00 0.00 0.104318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.287888E+09 0.00 0.00 0.00 0.791029E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.330114E+09 0.00 0.00 0.00 0.954687E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.290842E+09 0.00 0.00 0.00 0.833812E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.301307E+09 0.00 0.00 0.00 0.793074E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.298040E+09 0.00 0.00 0.00 0.763819E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.285094E+09 0.00 0.00 0.00 0.683409E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.364156E+10 0.00 0.00 0.00 0.102164E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.273235E+09 0.00 0.00 0.00 0.683409E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331009E+09 0.00 0.00 0.00 0.104318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.396768E+09 0.00 0.00 0.00 0.111797E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.359935E+09 0.00 0.00 0.00 0.106284E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.436083E+09 0.00 0.00 0.00 0.135740E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.382158E+09 0.00 0.00 0.00 0.130989E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.428654E+09 0.00 0.00 0.00 0.153333E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.429801E+09 0.00 0.00 0.00 0.158140E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.381311E+09 0.00 0.00 0.00 0.122461E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.437286E+09 0.00 0.00 0.00 0.143846E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.382103E+09 0.00 0.00 0.00 0.124671E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.397763E+09 0.00 0.00 0.00 0.120154E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.395984E+09 0.00 0.00 0.00 0.115625E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.377128E+09 0.00 0.00 0.00 0.100529E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.480497E+10 0.00 0.00 0.00 0.152357E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.359935E+09 0.00 0.00 0.00 0.100529E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.437286E+09 0.00 0.00 0.00 0.158140E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.363064E+09 0.00 0.00 0.00 0.795490E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.330167E+09 0.00 0.00 0.00 0.764432E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.401103E+09 0.00 0.00 0.00 0.977477E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.354146E+09 0.00 0.00 0.00 0.942946E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.391309E+09 0.00 0.00 0.00 0.105965E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.389240E+09 0.00 0.00 0.00 0.108347E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.348101E+09 0.00 0.00 0.00 0.818743E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.399516E+09 0.00 0.00 0.00 0.987708E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.350995E+09 0.00 0.00 0.00 0.864844E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.363518E+09 0.00 0.00 0.00 0.824237E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.360872E+09 0.00 0.00 0.00 0.798209E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.345400E+09 0.00 0.00 0.00 0.715730E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.439743E+10 0.00 0.00 0.00 0.106329E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.330167E+09 0.00 0.00 0.00 0.715730E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.401103E+09 0.00 0.00 0.00 0.108347E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 4561923.66 0.124900E+10 0.00 451539.97 0.100826E+09 0.00 6093578.47 0.00 0.19
February 5180847.92 0.116637E+10 0.00 342714.20 92421851.38 0.00 2856801.30 0.00 0.19
March 750922.15 0.158832E+10 0.00 29981.56 0.128109E+09 0.00 19287.70 0.00 0.21
April 0.00 0.171183E+10 0.00 0.00 0.137678E+09 0.00 0.00 0.00 0.19
May 0.00 0.221693E+10 0.00 0.00 0.175969E+09 0.00 0.00 0.00 0.21
June 0.00 0.224423E+10 0.00 4761.08 0.164699E+09 0.00 1987.77 0.00 0.21
July 0.00 0.151851E+10 0.00 0.00 0.125096E+09 0.00 0.00 0.00 0.18
August 0.00 0.220446E+10 0.00 0.00 0.179940E+09 0.00 0.00 0.00 0.21
September 0.00 0.182685E+10 0.00 0.00 0.143850E+09 0.00 0.00 0.00 0.19
October 0.00 0.179260E+10 0.00 0.00 0.148871E+09 0.00 0.00 0.00 0.19
November 165941.52 0.159276E+10 0.00 42247.96 0.136614E+09 0.00 440952.29 0.00 0.20
December 9250020.12 0.115992E+10 0.00 358826.02 98986633.92 0.00 2696287.49 0.00 0.18
                   
Annual Sum or Average 19909655.37 0.202718E+11 0.00 1230070.79 0.163306E+10 0.00 12108895.01 0.00 0.20
Minimum of Months 0.00 0.115992E+10 0.00 0.00 92421851.38 0.00 0.00 0.00 0.18
Maximum of Months 9250020.12 0.224423E+10 0.00 451539.97 0.179940E+09 0.00 6093578.47 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 7639521.32 0.901126E+09 0.00 486894.24 50763420.09 0.00 5602262.53 0.00 0.20
February 8801030.29 0.852774E+09 0.00 394619.37 47704254.31 0.00 4092127.74 0.00 0.20
March 3132929.44 0.112852E+10 0.00 165652.26 62164464.34 0.00 1628473.85 0.00 0.21
April 154870.71 0.121671E+10 0.00 40001.06 69721263.02 0.00 269622.65 0.00 0.19
May 1231366.43 0.156460E+10 0.00 90661.52 87374175.38 0.00 1438510.37 0.00 0.21
June 641456.47 0.158501E+10 0.00 69309.24 81210210.09 0.00 1182394.43 0.00 0.22
July 707174.06 0.106440E+10 0.00 102169.76 61099212.58 0.00 221139.74 0.00 0.19
August 1535857.24 0.153999E+10 0.00 80299.78 85651209.59 0.00 579907.25 0.00 0.21
September 622502.61 0.127993E+10 0.00 31107.16 68531051.80 0.00 33650.01 0.00 0.19
October 1246317.92 0.124961E+10 0.00 85778.38 70437894.15 0.00 977361.07 0.00 0.20
November 2599535.55 0.113615E+10 0.00 164173.83 65604286.95 0.00 2665499.89 0.00 0.20
December 14049758.33 0.856167E+09 0.00 380752.17 50635695.24 0.00 3003886.32 0.00 0.19
                   
Annual Sum or Average 42362320.35 0.143750E+11 0.00 2091418.78 0.800897E+09 0.00 21694835.85 0.00 0.20
Minimum of Months 154870.71 0.852774E+09 0.00 31107.16 47704254.31 0.00 33650.01 0.00 0.19
Maximum of Months 14049758.33 0.158501E+10 0.00 486894.24 87374175.38 0.00 5602262.53 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 3099462.52 0.579116E+09 0.00 278864.51 42043010.29 0.00 3422644.39 0.00 0.19
February 2834940.80 0.555362E+09 0.00 204153.46 39121337.14 0.00 2066293.51 0.00 0.20
March 881697.62 0.744483E+09 0.00 79368.39 51917119.81 0.00 662077.28 0.00 0.21
April 0.00 0.830371E+09 0.00 7300.15 59453597.97 0.00 9257.28 0.00 0.20
May 220306.60 0.108274E+10 0.00 11668.95 77571078.27 0.00 376531.01 0.00 0.21
June 26758.03 0.110550E+10 0.00 8290.22 74439032.98 0.00 395202.15 0.00 0.22
July 6051.97 0.721611E+09 0.00 13110.10 53743176.75 0.00 0.00 0.00 0.19
August 192373.55 0.105178E+10 0.00 22058.02 77681534.44 0.00 356804.01 0.00 0.22
September 3543.41 0.876666E+09 0.00 2775.20 62971343.29 0.00 18176.19 0.00 0.19
October 57771.37 0.836030E+09 0.00 35837.48 65477782.96 0.00 727020.58 0.00 0.20
November 584956.28 0.741858E+09 0.00 111630.01 58862040.66 0.00 1730242.15 0.00 0.20
December 4939733.46 0.542520E+09 0.00 175729.70 42362731.02 0.00 1104434.04 0.00 0.18
                   
Annual Sum or Average 12847595.60 0.966804E+10 0.00 950786.19 0.705644E+09 0.00 10868682.58 0.00 0.20
Minimum of Months 0.00 0.542520E+09 0.00 2775.20 39121337.14 0.00 0.00 0.00 0.18
Maximum of Months 4939733.46 0.110550E+10 0.00 278864.51 77681534.44 0.00 3422644.39 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 6927976.68 0.975477E+09 0.00 357165.66 76726036.60 0.00 4564413.96 0.00 0.19
February 4968488.24 0.928593E+09 0.00 284045.05 70996084.47 0.00 3280972.04 0.00 0.19
March 1115424.96 0.124754E+10 0.00 88185.44 93634160.98 0.00 1214987.05 0.00 0.21
April 5357.83 0.138000E+10 0.00 25473.18 0.105103E+09 0.00 32776.08 0.00 0.19
May 203432.40 0.181518E+10 0.00 14477.26 0.136091E+09 0.00 407305.87 0.00 0.21
June 138094.96 0.185832E+10 0.00 11197.08 0.126066E+09 0.00 443630.42 0.00 0.22
July 0.00 0.123179E+10 0.00 41260.14 96374196.59 0.00 137852.15 0.00 0.19
August 233796.75 0.176761E+10 0.00 34830.74 0.137587E+09 0.00 690752.38 0.00 0.21
September 0.00 0.147057E+10 0.00 3517.37 0.111468E+09 0.00 4118.59 0.00 0.19
October 366087.51 0.140689E+10 0.00 81420.23 0.116712E+09 0.00 1363780.66 0.00 0.19
November 1171575.21 0.125042E+10 0.00 172735.10 0.106107E+09 0.00 3531956.59 0.00 0.20
December 7213964.18 0.908970E+09 0.00 249200.26 76112986.14 0.00 3143654.99 0.00 0.18
                   
Annual Sum or Average 22344198.72 0.162414E+11 0.00 1363507.52 0.125298E+10 0.00 18816200.79 0.00 0.20
Minimum of Months 0.00 0.908970E+09 0.00 3517.37 70996084.47 0.00 4118.59 0.00 0.18
Maximum of Months 7213964.18 0.185832E+10 0.00 357165.66 0.137587E+09 0.00 4564413.96 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2908877.73 0.561414E+09 0.00 222210.98 42672335.15 0.00 3053638.00 0.00 0.19
February 3167419.20 0.538586E+09 0.00 166152.44 39657498.37 0.00 1579884.77 0.00 0.20
March 827076.25 0.731776E+09 0.00 43625.28 49807460.33 0.00 351505.31 0.00 0.22
April 0.00 0.819721E+09 0.00 5944.79 57351859.86 0.00 2058.39 0.00 0.20
May 84489.42 0.106863E+10 0.00 4650.54 76980689.65 0.00 332278.89 0.00 0.21
June 25710.66 0.109634E+10 0.00 5970.46 71117633.45 0.00 361550.50 0.00 0.22
July 0.00 0.705143E+09 0.00 9980.88 53497822.51 0.00 38429.23 0.00 0.19
August 166930.81 0.103459E+10 0.00 19711.98 78021591.34 0.00 281371.40 0.00 0.22
September 3278.86 0.862916E+09 0.00 2389.41 62337923.99 0.00 6743.65 0.00 0.19
October 53108.11 0.819034E+09 0.00 28558.31 66009585.24 0.00 681096.52 0.00 0.20
November 776839.75 0.724754E+09 0.00 79665.49 60583356.14 0.00 1391122.53 0.00 0.20
December 4818500.16 0.525313E+09 0.00 144614.08 43254140.51 0.00 853216.57 0.00 0.19
                   
Annual Sum or Average 12832230.96 0.948822E+10 0.00 733474.63 0.701292E+09 0.00 8932895.75 0.00 0.20
Minimum of Months 0.00 0.525313E+09 0.00 2389.41 39657498.37 0.00 2058.39 0.00 0.19
Maximum of Months 4818500.16 0.109634E+10 0.00 222210.98 78021591.34 0.00 3053638.00 0.00 0.22



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:29:12

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.908814E+11 0.161660E+10 0.00 -0.580227E+10 0.292648E+11
February 0.933110E+11 0.150679E+10 0.00 -0.611049E+10 0.270230E+11
March 0.125657E+12 0.195795E+10 0.00 -0.819432E+10 0.333279E+11
April 0.128130E+12 0.177062E+10 0.00 -0.101737E+11 0.319974E+11
May 0.120925E+12 -97273644.1 0.00 -0.128757E+11 0.369460E+11
June 0.124247E+12 0.561499E+09 0.00 -0.126555E+11 0.374742E+11
July 0.103533E+12 0.153765E+10 0.00 -0.850717E+10 0.299103E+11
August 0.130830E+12 -57345544.8 0.00 -0.115038E+11 0.357596E+11
September 0.103491E+12 0.779653E+09 0.00 -0.108534E+11 0.310673E+11
October 0.107807E+12 0.394520E+09 0.00 -0.987737E+10 0.307589E+11
November 0.874770E+11 0.700563E+09 0.00 -0.825433E+10 0.299541E+11
December 0.847440E+11 0.887018E+09 0.00 -0.607000E+10 0.266890E+11
           
Annual Sum or Average 0.130103E+13 0.115582E+11 0.00 -0.110878E+12 0.380173E+12
Minimum of Months 0.847440E+11 -97273644.1 0.00 -0.128757E+11 0.266890E+11
Maximum of Months 0.130830E+12 0.195795E+10 0.00 -0.580227E+10 0.374742E+11