Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:29:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1280.90 | 5512.98 | 5512.98 |
Net Site Energy | 1280.90 | 5512.98 | 5512.98 |
Total Source Energy | 2300.68 | 9902.09 | 9902.09 |
Net Source Energy | 2300.68 | 9902.09 | 9902.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 37.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 437.92 | 842.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 50.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 61.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 11.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 163.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 50.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 61.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 201.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 37.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 154.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 482.86 | 1574.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1247.03 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1884.79 | 3628.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 154.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 482.86 | 1574.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1247.03 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1884.79 | 3628.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 437.917 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 437.917 | 100.00 |
Total On-Site and Utility Electric Sources | 437.917 | 100.00 |
Total Electricity End Uses | 437.917 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4067.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.1965 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 8.9582 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.1965 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.9582 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.5774 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-16:10 | 20-JAN-04:19 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 73348.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15186.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12287.48 | 4596.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3423.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7211.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1141.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32945.93 | 85156.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 73348.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15186.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11696.68 | 4596.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3423.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7211.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 362.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 585.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 177.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 159.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 195.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 218.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 119.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1386.88 | 913.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 764.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 843.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 942.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 513.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5969.12 | 3932.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 764.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 843.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 942.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 513.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5969.12 | 3932.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.48 |
KITCHEN DIRECT AIR | 1.37 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 2.48 | 1.00 | 1.00 | 2.48 |
PSZ-AC_2:2 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.00 | 1.37 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.48 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.37 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.48 | 2656.14 |
PSZ-AC_2:2_ADDAQ FAN | 1.37 | 1514.40 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.48 | 2.48 | 2.48 | 1.64 | 41090.33 | 58678.41 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 0.902765 | 29794.44 | 59403.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.48 | 1.24 | 1.65 | 41090.33 | 20545.17 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.37 | 0.683913 | 0.911887 | 29794.44 | 14897.22 | 0.744400 | 0.744400 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58678.41 |
PSZ-AC_2:2 HEATING COIL | 59403.34 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.196 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 120.983 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 8.958 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1076.278 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 487.511 | 4.196 | 5.569 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 487.511 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1040.691 | 8.958 | 165.892 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.691 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3619_SHGC_SOUTH_0.36 | 38 | 1 | VerySmooth | 2.056 | 2.056 | 1.000 | 0.361 | ||
2 | NONRESWINDOW_U_0.3619_SHGC_NORTH_0.36 | 39 | 1 | VerySmooth | 2.056 | 2.056 | 1.000 | 0.361 | ||
3 | NONRESWINDOW_U_0.3619_SHGC_EAST_0.36 | 40 | 1 | VerySmooth | 2.056 | 2.056 | 1.000 | 0.361 | ||
4 | NONRESWINDOW_U_0.3619_SHGC_WEST_0.36 | 41 | 1 | VerySmooth | 2.056 | 2.056 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.63776E-002 | 0.27318 | 0.51978 | 0.51978 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11597 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.63776E-002 | 0.27318 | 0.51978 | 0.51978 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11597 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.63776E-002 | 0.27318 | 0.51978 | 0.51978 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11597 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.63776E-002 | 0.27318 | 0.51978 | 0.51978 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11597 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.323E-002 | 1.139E-004 | 1.424E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.323E-002 | 1.139E-004 | 1.395E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0811E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5748E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.8692E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.3738E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7437E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6761E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4159E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.4170E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 6.3780E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 6.3248E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.3017E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.2342E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.2054E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.1898E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.5332E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.5332E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5417E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0420E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.3338E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.8203E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6329E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7062E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.4172E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.4159E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 23117.66337 | 27741.19604 | 2.06856 | 2.48227 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 5545.15503 | 6654.18604 | 0.28656 | 0.41606 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.90000 | 2.34317E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15279.23133 | 18335.07759 | 1.13985 | 1.36783 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 694.86990 | 833.84388 | 3.25906E-002 | 1.14133 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 32030.38 | 2.48227 | 2.48227 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 19833.85 | 0.41606 | 0.41606 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26936.55 | 1.36783 | 1.36783 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 54408.60 | 1.14133 | 1.14133 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.48227 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36783 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48227 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.48227 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.48227 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48227 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.48227 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.48227 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36783 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36783 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36783 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36783 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36783 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36783 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.48227 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.36783 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.48227 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.48227 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2656.14276 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.48227 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.48227 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.48227 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.63830 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.48227 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.24113 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.65485 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41090.33000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20545.16500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41090.33000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58678.41299 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58678.41299 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36783 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36783 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1514.40031 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36783 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36783 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36783 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90277 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36783 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68391 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.91189 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29794.44000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14897.22000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74440 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74440 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29794.44000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59403.34229 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 59403.34229 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 39274.3 | 10.85 | 10.80 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 28811.7 | 11.60 | 11.54 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3619_SHGC_EAST_0.36 | N/A | 2.056 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3619_SHGC_SOUTH_0.36 | N/A | 2.056 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3619_SHGC_WEST_0.36 | N/A | 2.056 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.7197784822E-002 | 0.2669982867 | Pass | Pass | 0.2236107749 | 0.5008180505 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2245827792 | 0.6221730009 | Pass | Pass | 3.2339067412E-002 | 8.2236011762E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.5073206296 | 0.5398960266 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 634.39 | 115.80 | 718.77 | 12.12 | 519.37 | 2000.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3619_SHGC_EAST_0.36 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.056 | 0.361 | 0.361 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3619_SHGC_SOUTH_0.36 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.056 | 0.361 | 0.361 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3619_SHGC_WEST_0.36 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.056 | 0.361 | 0.361 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.056 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.056 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.1965 | 116.17 | 487.51 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 46.12 | 0.0000 | Y | 4.22 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.9582 | 116.17 | 1040.69 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 16.40 |
Interior Lighting Total | 6.5774 | 232.34 | 1528.20 | 20.62 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 166.91 | AstronomicalClock | - | 48.81 | 48.81 | 1.53 | |
EXTERIOR_LIGHTS_B | 1174.86 | AstronomicalClock | - | 83.71 | 62.76 | 13.84 | |
Exterior Lighting Total | 1341.77 | 15.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41090.33 | 32899.38 | 8190.95 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29794.44 | 22178.98 | 7615.46 | 0.74 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 39274.3 | 10.85 | 10.80 | ||||
PSZ-AC_2:2 COOLING COIL | 28811.7 | 11.60 | 11.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58678.41 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 59403.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.48 | 2656.14 | 1070.05 | 1.00 | 1.29 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1514.40 | 1107.16 | 1.00 | 1.33 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 23117.66 | 27741.20 | 238.80 | 2.069 | 2.482 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00735 | 35.10 | 0.00570 | 0.416 | 0.00 |
KITCHEN | 15279.23 | 18335.08 | 157.83 | 1.140 | 1.368 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00882 | 33.89 | 0.00570 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5545.16 | 6654.19 | 57.28 | 0.287 | 0.416 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00794 | -7.90 | 0.00234 | 0.416 | 0.00 |
KITCHEN | 694.87 | 833.84 | 7.18 | 0.033 | 1.141 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 18.89 | 18.89 | 0.00566 | -7.90 | 0.00234 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.48 | 2.48 | 0.42 | 0.42 | 2.4823 | 2.4823 | 2.4823 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.37 | 1.37 | 1.14 | 1.14 | 1.3678 | 1.3678 | 1.3678 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 41090.330 | 32899.384 | 2.482270 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 20545.17 | 20364.08 | 1.654847 | 25.77 | 13.80 | 0.00707062 | 11.74 | 8.43 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | 25.1417 | 23.89 | 0.00734674 | 32.8102 | 23117.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58678.413 | 58678.413 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 58678.41 | 58678.41 | 2.482267 | 16.25 | 10.24 | 0.00698539 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 16.7611 | 19.71 | 0.00792015 | 45.5997 | 3121.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 29794.440 | 22178.981 | 1.367830 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14897.22 | 14897.22 | 0.911887 | 32.59 | 15.37 | 0.00621418 | 11.70 | 7.60 | 0.00621418 | 33.89 | 0.00569749 | 15.38 | 125.1618 | 26.10 | 0.00881783 | 34.4395 | 15279.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 59403.342 | 59403.342 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | 59403.34 | 59403.34 | 1.367826 | -3.64 | -4.35 | 0.00293153 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 83.4414 | 18.69 | 0.00589635 | 36.2921 | 292.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41090.330 | 32899.384 | 2.482270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9839 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.482267 | 2.45845907 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 20545.17 | 20364.08 | 1.0000 | 1.63897486 | 1.654847 | 25.77 | 13.80 | 0.00707062 | 43912.2 | 11.74 | 8.43 | 0.00700000 | 29454.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20545.17 | 35.10 | 0.00569938 | 15.77 | 0.41605618 | 25.1417 | 23.89 | 0.00734674 | 23.89 | 0.00734674 | 32.8102 | 23117.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58678.413 | 58678.413 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.482267 | 2.45845907 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 58678.41 | 58678.41 | 1.0000 | 2.45845907 | 2.482267 | 16.25 | 10.24 | 0.00698539 | 34007.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58678.41 | -7.90 | 0.00234317 | -7.90 | 0.41605618 | 16.7611 | 21.11 | 0.00792015 | 19.71 | 0.00792015 | 45.5997 | 3121.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29794.440 | 22178.981 | 1.367830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.3918 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.367826 | 1.35470686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14897.22 | 14897.22 | 1.0000 | 0.90314066 | 0.911887 | 32.59 | 15.37 | 0.00621418 | 48663.0 | 11.70 | 7.60 | 0.00621418 | 27433.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14897.22 | 33.89 | 0.00569749 | 15.38 | 1.14133354 | 125.1618 | 26.05 | 0.00881783 | 26.10 | 0.00881783 | 34.4395 | 15279.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59403.342 | 59403.342 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.367826 | 1.35470686 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:20:00 | Sensible | 59403.34 | 59403.34 | 1.0000 | 1.35470686 | 1.367826 | -3.64 | -4.35 | 0.00293153 | 3656.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59403.34 | -7.90 | 0.00234317 | -7.90 | 1.14133354 | 83.4414 | 17.84 | 0.00589635 | 18.69 | 0.00589635 | 36.2921 | 292.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.48 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.37 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3261.83 | 4138.00 | 885.50 |
KITCHEN | 4931.83 | 6033.33 | 4034.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4964.00 | 6859.83 | 4067.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 6.67 | 1.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 129.50 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 6.67 | 130.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.408 | 4.271 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.537 | 0.007 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.098 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.902 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13861250.66 | 0.00 | 13861250.66 | 10794242.44 | 24655493.10 | 13120747.55 | 1456.07 | 5862.66 | 1441.27 | 184.28 |
KITCHEN | 24751816.01 | 0.00 | 24751816.01 | 32200.55 | 24784016.56 | 35993094.65 | 8665.98 | 92.60 | 1.42 | 491.13 |
Total Facility | 38613066.67 | 0.00 | 38613066.67 | 10826442.98 | 49439509.66 | 49113842.20 | 8666.51 | 5862.84 | 1441.89 | 526.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5270 | 0.0000 | 0.5270 | 0.4167 | 0.9437 | 0.4161 | 0.00 | 5771.46 | 1415.54 |
KITCHEN | 0.9276 | 0.0000 | 0.9276 | 0.0007 | 0.9283 | 1.1413 | 7094.03 | 92.40 | 0.58 |
Total Facility | 1.4546 | 0.0000 | 1.4546 | 0.4174 | 1.8720 | 1.5574 | 7094.03 | 5771.55 | 1415.63 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13596872.33 | 0.00 | 13596872.33 | 13120747.55 | 7318.39 | 10.40 | 1431.22 | 184.24 |
PSZ-AC_2:2 | 24279121.71 | 0.00 | 24279121.71 | 35993094.65 | 8758.58 | 0.12 | 1.31 | 491.13 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5169 | 0.0000 | 0.5169 | 0.4161 | 5771.11 | 9.43 | 1406.45 |
PSZ-AC_2:2 | 0.9099 | 0.0000 | 0.9099 | 1.1413 | 7186.42 | 0.00 | 0.58 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 924.32 | 588.60 | 5858.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 245.26 | 943.37 | 6489.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.1259 | 0.7119 | 0.4082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.9008 | 0.9334 | 0.9077 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
Electricity:Building | 280.65 | 1825.29 | 01-JAN-01:10 | 17838.45 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.55 | 336.73 | 01-JAN-01:10 | 4026.33 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 272.71 | 1689.01 | 01-JAN-01:10 | 14544.40 | 02-JAN-11:10 |
InteriorLights:Electricity | 20.62 | 162.52 | 25-JUN-05:00 | 1211.55 | 02-JAN-17:10 |
InteriorLights:Electricity:Zone:DINING | 4.22 | 27.31 | 25-JUN-05:00 | 400.32 | 02-JAN-17:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 20.62 | 162.52 | 25-JUN-05:00 | 1211.55 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity | 20.62 | 162.52 | 25-JUN-05:00 | 1211.55 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.22 | 27.31 | 25-JUN-05:00 | 400.32 | 02-JAN-17:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 20.62 | 162.52 | 25-JUN-05:00 | 1211.55 | 02-JAN-17:10 |
Electricity:Zone:KITCHEN | 206.10 | 1488.56 | 01-JAN-01:10 | 13812.12 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 37.65 | 583.58 | 11-FEB-23:30 | 3922.70 | 23-AUG-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 29.70 | 497.81 | 11-FEB-23:30 | 1659.56 | 16-MAY-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 11.51 | 0.00 | 01-JAN-11:10 | 1022.47 | 16-MAY-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 18.20 | 475.34 | 24-DEC-01:10 | 637.09 | 14-APR-03:30 |
ElectricityPurchased:Facility | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
ElectricityPurchased:Plant | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
Cogeneration:ElectricityPurchased | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
ElectricityNet:Plant | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
Cogeneration:ElectricityNet | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
General:Cogeneration:ElectricityNet | 437.92 | 3081.47 | 15-DEC-01:10 | 32945.93 | 28-JUN-16:10 |
Electricity:HVAC | 112.19 | 0.00 | 01-JAN-01:10 | 19046.51 | 21-JUL-17:10 |
Fans:Electricity | 61.86 | 0.00 | 01-JAN-01:10 | 3606.58 | 21-JUL-17:10 |
General:Fans:Electricity | 61.86 | 0.00 | 01-JAN-01:10 | 3606.58 | 21-JUL-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 50.33 | 0.00 | 01-JAN-00:10 | 15439.93 | 21-JUL-17:10 |
General:Cooling:Electricity | 50.33 | 0.00 | 01-JAN-00:10 | 15439.93 | 21-JUL-17:10 |
ExteriorLights:Electricity | 15.37 | 0.00 | 01-JAN-07:20 | 1341.77 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.37 | 0.00 | 01-JAN-07:20 | 1341.77 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-11:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-11:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 842.99 | 2560.65 | 07-JAN-01:20 | 85156.53 | 20-JAN-04:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 163.85 | 0.00 | 01-JAN-01:10 | 73348.02 | 20-JAN-04:10 |
Heating:NaturalGas | 163.85 | 0.00 | 01-JAN-01:10 | 73348.02 | 20-JAN-04:10 |
General:Heating:NaturalGas | 163.85 | 0.00 | 01-JAN-01:10 | 73348.02 | 20-JAN-04:10 |
NaturalGas:Plant | 201.98 | 722.00 | 07-JAN-01:20 | 27221.20 | 05-FEB-13:30 |
WaterSystems:NaturalGas | 201.98 | 722.00 | 07-JAN-01:20 | 27221.20 | 05-FEB-13:30 |
Water Heater:WaterSystems:NaturalGas | 201.98 | 722.00 | 07-JAN-01:20 | 27221.20 | 05-FEB-13:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 956.75 | 2416.03 | 15-DEC-01:10 | 103320.99 | 29-JUN-13:00 |
EnergyTransfer:Building | 428.24 | 1208.01 | 15-DEC-01:10 | 34591.03 | 29-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 308.80 | 1208.01 | 15-DEC-01:10 | 18833.54 | 14-APR-04:10 |
Refrigeration:EnergyTransfer | 139.70 | 2416.03 | 15-DEC-01:10 | 7834.84 | 14-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.85 | 1208.01 | 15-DEC-01:10 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer | 69.85 | 1208.01 | 15-DEC-01:10 | 3917.42 | 14-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 69.85 | 1208.01 | 15-DEC-01:10 | 3917.42 | 14-APR-03:30 |
EnergyTransfer:Plant | 206.04 | 1208.01 | 15-DEC-01:10 | 21402.62 | 14-FEB-13:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.07 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 56.79 | 1059.55 | 24-DEC-01:10 | 2238.70 | 14-APR-03:30 |
EnergyTransfer:Zone:DINING | 119.44 | 0.00 | 01-JAN-01:10 | 20115.62 | 21-JUL-17:10 |
Heating:EnergyTransfer | 28.66 | 0.00 | 01-JAN-00:10 | 16558.89 | 19-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 28.65 | 0.00 | 01-JAN-00:10 | 16558.89 | 19-JAN-21:00 |
General:Heating:EnergyTransfer | 28.66 | 0.00 | 01-JAN-00:10 | 16558.89 | 19-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 28.65 | 0.00 | 01-JAN-00:10 | 16558.89 | 19-JAN-21:00 |
Cooling:EnergyTransfer | 329.73 | 0.00 | 01-JAN-01:10 | 31628.74 | 21-JUL-17:10 |
Cooling:EnergyTransfer:Zone:DINING | 90.79 | 0.00 | 01-JAN-01:10 | 20115.62 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer | 329.73 | 0.00 | 01-JAN-01:10 | 31628.74 | 21-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 90.79 | 0.00 | 01-JAN-01:10 | 20115.62 | 21-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 738.98 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 738.98 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 238.94 | 0.00 | 01-JAN-01:10 | 15034.10 | 14-FEB-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 238.94 | 0.00 | 01-JAN-01:10 | 15034.10 | 14-FEB-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
PlantLoopHeatingDemand:Plant | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
WaterSystems:PlantLoopHeatingDemand | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
EnergyTransfer:HVAC | 322.47 | 0.00 | 01-JAN-01:10 | 58678.41 | 20-JAN-04:20 |
HeatingCoils:EnergyTransfer | 131.08 | 0.00 | 01-JAN-01:10 | 58678.41 | 20-JAN-04:20 |
CoolingCoils:EnergyTransfer | 191.39 | 0.00 | 01-JAN-00:10 | 53320.53 | 21-JUL-17:10 |
WaterSystems:EnergyTransfer | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 136.19 | 0.00 | 01-JAN-00:10 | 19004.81 | 04-FEB-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 28.650 | -90.792 | 0.000 | 0.000 | 70.417 | 4.221 | 52.748 | 34.691 | 0.000 | 11.217 | 0.000 | 0.000 | -10.631 | 0.000 | -90.859 | -9.662 |
KITCHEN | 0.000 | 0.000 | 0.008 | -238.929 | 0.000 | 0.000 | 4.781 | 16.400 | 187.472 | 0.000 | 0.000 | 0.011 | 30.644 | 0.000 | 0.000 | 0.000 | -0.385 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.195 | 11.548 | 0.000 | 0.000 | 0.000 | -15.743 | -0.000 |
Total Facility | 0.000 | 0.000 | 28.658 | -329.721 | 0.000 | 0.000 | 75.197 | 20.620 | 240.220 | 34.691 | 0.000 | 15.423 | 42.192 | 0.000 | -10.631 | 0.000 | -106.987 | -9.663 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 21-JUL-03:01 | 0.00 | 0.00 | 0.00 | -26382.47 | 0.00 | 0.00 | 0.00 | 66.72 | 506.27 | 0.00 | 0.00 | 0.00 | 26129.80 | 0.00 | -315.41 | 0.00 | -4.91 | 0.00 |
KITCHEN | 14-APR-04:01 | 0.00 | 0.00 | 0.00 | -45504.46 | 0.00 | 0.00 | 7.74 | 180.28 | 4494.65 | 0.00 | 0.00 | 0.00 | 40822.88 | 0.00 | -0.00 | 0.00 | -1.09 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUN-04:01 | 0.00 | 0.00 | 0.00 | -58444.10 | 0.00 | 0.00 | 0.00 | 201.93 | 5703.16 | 0.00 | 0.00 | 439.32 | 52658.49 | 0.00 | -557.96 | 0.00 | -0.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-FEB-05:01 | 0.00 | 0.00 | 22841.41 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 1215.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1203.81 | 0.00 | -22.69 | -22896.67 |
KITCHEN | 23-DEC-05:03 | 0.00 | 0.00 | 7379.51 | 0.00 | 0.00 | 0.00 | 0.00 | 135.21 | 4488.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -24.25 | -11978.59 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-05:01 | -24529.99 | 24529.99 | 22841.41 | -24529.99 | 0.00 | 0.00 | 0.00 | 201.93 | 5703.16 | 0.00 | 0.00 | 236.55 | 0.00 | 0.00 | -1203.81 | 0.00 | -45.94 | -3203.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4823 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4823 | 0.1676 | 1.0000 | Not calculated | 0.4161 | 0.1676 | ||
PSZ-AC_2:2 | 1.3678 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3678 | 0.1106 | 1.0000 | Not calculated | 0.1513 | 0.1106 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4823 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4823 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1676 | ||
PSZ-AC_2:2 | 1.3678 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3678 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1106 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4823 | 2.4823 | 2.4823 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3678 | 1.3678 | 1.3678 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4823 | 2.4823 | 2.4823 | 2.4823 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3678 | 1.3678 | 1.3678 | 1.3678 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4823 | 2.4823 | 2.4823 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3678 | 1.3678 | 1.3678 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4823 | 2.4823 | 2.4823 | 2.4823 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3678 | 1.3678 | 1.3678 | 1.3678 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 163.85 | 73348.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 50.33 | 15439.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 20.62 | 1211.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.37 | 1341.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 61.86 | 3606.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 201.98 | 27221.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 11.51 | 1022.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.20 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 289.74 | 437.92 |
Natural Gas | 477.16 | 842.99 |
Additional | 0.00 | 0.00 |
Total | 766.90 | 1280.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 88.75 |
Space Heating | 0.00 |
Space Cooling | 216.62 |
Fans (All) | 266.23 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 1884.79 |
Subtotal | 1884.79 |
Natural Gas [MJ/m2] | |
Space Heating | 705.22 |
Service Water Heating | 869.30 |
Miscellaneous (All) | 3628.20 |
Subtotal | 3628.20 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.61 |
Space Heating | 12.79 |
Space Cooling | 3.93 |
Fans (All) | 4.83 |
Service Water Heating | 15.77 |
Receptacle Equipment | 56.93 |
Miscellaneous | 4.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | July | 23.89 | 365 | 25.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 27.22 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7963.17 | 796.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 6370.00 | 649.33 | 584.00 | 943.67 | 213.00 |
Min | 6370.00 | 38.17 | 0.00 | 0.00 | 0.00 |
Max | 8721.83 | 796.83 | 584.00 | 943.67 | 213.00 |
Average | 7685.00 | 494.78 | 194.67 | 314.56 | 71.00 |
Sum | 23055.00 | 1484.33 | 584.00 | 943.67 | 213.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254713.00 | 12.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16218.17 | 39.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254713.00 | 39.83 | 0.00 | 0.00 | 0.00 |
Average | 90310.39 | 17.28 | 0.00 | 0.00 | 0.00 |
Sum | 270931.17 | 51.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8615.67 | 144.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7442.00 | 1318.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 6636.67 | 837.83 | 343.50 | 299.17 | 642.83 |
Min | 6636.67 | 144.33 | 0.00 | 0.00 | 0.00 |
Max | 8615.67 | 1318.00 | 343.50 | 299.17 | 642.83 |
Average | 7564.78 | 766.72 | 114.50 | 99.72 | 214.28 |
Sum | 22694.33 | 2300.17 | 343.50 | 299.17 | 642.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254165.33 | 559.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 14307.50 | 1950.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254165.33 | 1950.50 | 0.00 | 0.00 | 0.00 |
Average | 89490.94 | 836.72 | 0.00 | 0.00 | 0.00 |
Sum | 268472.83 | 2510.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149014E+10 | 8666.44 | 20-JAN-00:01 | -6.9 | -7.0 | 0.446316E+10 | 3760.48 | 05-JAN-12:00 | -6.9 | -7.0 |
February | 0.162713E+10 | 9146.60 | 04-FEB-05:02 | -6.2 | -7.7 | 0.407515E+10 | 4412.95 | 14-FEB-12:39 | 18.67 | 6.45 |
March | 0.273432E+10 | 6762.14 | 26-MAR-04:01 | 1.02 | -2.5 | 0.470393E+10 | 4680.94 | 25-MAR-18:19 | 1.02 | -2.5 |
April | 0.560446E+10 | 10410.79 | 27-APR-04:01 | 12.23 | 4.63 | 0.484807E+10 | 4681.01 | 29-APR-18:19 | 23.17 | 8.64 |
May | 0.866410E+10 | 16495.35 | 20-MAY-04:01 | 12.62 | 3.24 | 0.521847E+10 | 4681.09 | 27-MAY-18:00 | 24.40 | 12.44 |
June | 0.143039E+11 | 23218.29 | 29-JUN-03:01 | 23.07 | 14.70 | 0.524126E+10 | 4681.17 | 24-JUN-18:49 | 23.07 | 14.70 |
July | 0.171543E+11 | 26383.45 | 21-JUL-03:01 | 22.52 | 12.64 | 0.542059E+10 | 4681.53 | 08-JUL-18:00 | 22.52 | 12.64 |
August | 0.161409E+11 | 24275.98 | 18-AUG-03:01 | 22.02 | 13.93 | 0.547451E+10 | 4681.16 | 05-AUG-18:49 | 22.02 | 13.93 |
September | 0.122107E+11 | 21470.35 | 21-SEP-04:01 | 14.22 | 7.49 | 0.521587E+10 | 4681.41 | 09-SEP-18:10 | 14.22 | 7.49 |
October | 0.726981E+10 | 22051.58 | 05-OCT-04:01 | 14.72 | 8.15 | 0.501830E+10 | 4680.91 | 14-OCT-18:10 | 16.55 | 6.60 |
November | 0.241178E+10 | 8048.84 | 01-NOV-04:01 | 8.72 | 5.93 | 0.437393E+10 | 4380.26 | 09-NOV-12:00 | 18.30 | 9.35 |
December | 0.118150E+10 | 8811.27 | 15-DEC-05:00 | -9.4 | -12.1 | 0.443950E+10 | 3722.78 | 02-DEC-19:10 | -9.4 | -12.1 |
Annual Sum or Average | 0.907930E+11 | 0.584927E+11 | ||||||||
Minimum of Months | 0.118150E+10 | 6762.14 | -9.4 | -12.1 | 0.407515E+10 | 3722.78 | -9.4 | -12.1 | ||
Maximum of Months | 0.171543E+11 | 26383.45 | 23.07 | 14.70 | 0.547451E+10 | 4681.53 | 24.40 | 14.70 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190187E+11 | 25202.88 | 27-JAN-05:01 | -4.3 | -7.1 | 0.769596E+10 | 5089.32 | 05-JAN-11:00 | -4.3 | -7.1 |
February | 0.170618E+11 | 24549.93 | 04-FEB-05:01 | -6.2 | -7.7 | 0.696141E+10 | 5132.63 | 14-FEB-11:00 | 17.20 | 6.01 |
March | 0.189643E+11 | 24208.16 | 10-MAR-05:01 | -1.1 | -4.3 | 0.775342E+10 | 5135.79 | 08-MAR-11:00 | -1.1 | -4.3 |
April | 0.185583E+11 | 45520.90 | 14-APR-04:01 | 9.72 | 2.54 | 0.755432E+10 | 5135.93 | 21-APR-10:00 | 17.80 | 7.89 |
May | 0.197875E+11 | 45026.52 | 12-MAY-04:01 | 10.40 | 3.21 | 0.783724E+10 | 5136.00 | 24-MAY-10:00 | 17.80 | 14.22 |
June | 0.205655E+11 | 38721.59 | 18-JUN-04:01 | 16.10 | 7.59 | 0.760506E+10 | 5135.99 | 05-JUN-10:00 | 16.10 | 7.59 |
July | 0.221124E+11 | 32210.11 | 21-JUL-04:01 | 20.92 | 12.28 | 0.785880E+10 | 5135.96 | 10-JUL-10:09 | 20.92 | 12.28 |
August | 0.221224E+11 | 31256.22 | 25-AUG-03:11 | 16.30 | 13.82 | 0.786325E+10 | 5135.98 | 23-AUG-10:39 | 16.30 | 13.82 |
September | 0.207211E+11 | 40134.73 | 29-SEP-04:01 | 15.00 | 9.33 | 0.760135E+10 | 5135.97 | 07-SEP-10:30 | 15.00 | 9.33 |
October | 0.207050E+11 | 39177.95 | 20-OCT-04:01 | 10.50 | 7.41 | 0.780432E+10 | 5135.97 | 03-OCT-10:30 | 10.50 | 7.41 |
November | 0.198124E+11 | 23404.27 | 27-NOV-05:01 | -4.0 | -6.5 | 0.747367E+10 | 5135.80 | 09-NOV-11:00 | -4.0 | -6.5 |
December | 0.195083E+11 | 28460.80 | 15-DEC-05:01 | -9.1 | -11.9 | 0.768645E+10 | 5077.94 | 01-DEC-11:00 | -9.1 | -11.9 |
Annual Sum or Average | 0.238938E+12 | 0.916952E+11 | ||||||||
Minimum of Months | 0.170618E+11 | 23404.27 | -9.1 | -11.9 | 0.696141E+10 | 5077.94 | -9.1 | -11.9 | ||
Maximum of Months | 0.221224E+11 | 45520.90 | 20.92 | 13.82 | 0.786325E+10 | 5136.00 | 20.92 | 14.22 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2.30 | -1.2 | 0.00 | 0.00 | 01-JAN-00:10 | 2.30 | -1.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 | -5.2 | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 | -5.2 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 2.47 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 | -0.8 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 | 2.84 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 2.84 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 | 4.92 | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 | 4.92 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 | 8.96 | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 | 8.96 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 | 14.90 | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 | 14.90 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 | 16.86 | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 | 16.86 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 | 14.47 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 14.47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 | 10.88 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 10.88 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 | 5.34 | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 | 5.34 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 | 1.84 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.2 | -5.2 | 0.00 | 0.00 | -3.2 | -5.2 | ||
Maximum of Months | 0.00 | 0.00 | 21.95 | 16.86 | 0.00 | 0.00 | 21.95 | 16.86 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.804622E+10 | 18706.86 | 22-JAN-05:01 | -5.6 |
February | 0.566838E+10 | 22840.83 | 04-FEB-05:01 | -6.2 |
March | 0.251414E+10 | 15939.32 | 05-MAR-05:01 | -1.9 |
April | 0.571545E+09 | 8042.71 | 08-APR-04:06 | 2.80 |
May | 0.106563E+09 | 4602.85 | 06-MAY-06:07 | 5.78 |
June | 4297879.40 | 1343.48 | 28-JUN-23:01 | 27.12 |
July | 6983608.12 | 1515.29 | 22-JUL-23:01 | 27.70 |
August | 2405530.03 | 1001.38 | 20-AUG-23:01 | 26.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.929508E+09 | 9875.49 | 26-OCT-04:01 | -2.8 |
November | 0.280134E+10 | 10884.27 | 27-NOV-05:01 | -4.0 |
December | 0.799844E+10 | 19140.73 | 09-DEC-05:01 | -5.4 |
Annual Sum or Average | 0.286498E+11 | |||
Minimum of Months | 0.00 | 0.00 | -6.2 | |
Maximum of Months | 0.804622E+10 | 22840.83 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3018061.74 | 7342.60 | 21-JAN-05:03 | -5.2 |
February | 1799961.56 | 6340.74 | 01-FEB-05:03 | -4.0 |
March | 66309.42 | 575.81 | 30-MAR-04:04 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 26335.87 | 307.25 | 22-JUL-23:01 | 27.70 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 67531.54 | 1125.53 | 25-OCT-04:04 | -2.0 |
November | 183232.96 | 1412.19 | 27-NOV-05:03 | -4.0 |
December | 2423622.96 | 7389.80 | 23-DEC-05:03 | -5.1 |
Annual Sum or Average | 7585056.05 | |||
Minimum of Months | 0.00 | 0.00 | -5.2 | |
Maximum of Months | 3018061.74 | 7389.80 | 27.70 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:01 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.407529E+09 | 400.32 | 02-JAN-17:10 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.354375E+09 | 400.32 | 01-FEB-17:30 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.362051E+09 | 400.32 | 01-MAR-17:00 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.317153E+09 | 400.32 | 01-APR-18:30 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.321166E+09 | 400.32 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.294847E+09 | 400.32 | 01-JUN-19:10 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.310396E+09 | 400.32 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.325596E+09 | 400.32 | 01-AUG-18:00 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.333629E+09 | 400.32 | 01-SEP-18:40 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.371639E+09 | 400.32 | 02-OCT-17:49 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.393741E+09 | 400.32 | 01-NOV-17:10 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.428410E+09 | 400.32 | 01-DEC-16:00 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.422053E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.294847E+09 | 400.32 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.428410E+09 | 400.32 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138574E+10 | 811.23 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.125514E+10 | 811.23 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.140781E+10 | 811.23 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.134648E+10 | 811.23 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.139678E+10 | 811.23 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.136076E+10 | 811.23 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.138266E+10 | 811.23 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.140781E+10 | 811.23 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.134680E+10 | 811.23 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.138558E+10 | 811.23 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.134145E+10 | 811.23 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.138282E+10 | 811.23 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.163998E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.125514E+10 | 811.23 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.140781E+10 | 811.23 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.407529E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163133E+11 |
February | 0.852256E+10 | 0.354375E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131105E+11 |
March | 0.954557E+10 | 0.362051E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103044E+11 |
April | 0.915225E+10 | 0.317153E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49971612.74 | 0.612437E+10 |
May | 0.947560E+10 | 0.321166E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538382E+09 | 0.375665E+10 |
June | 0.922788E+10 | 0.294847E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305037E+10 | 0.146442E+10 |
July | 0.939996E+10 | 0.310396E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378552E+10 | 0.584984E+09 |
August | 0.954557E+10 | 0.325596E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272183E+10 | 0.967000E+09 |
September | 0.915225E+10 | 0.333629E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928593E+09 | 0.228357E+10 |
October | 0.940563E+10 | 0.371639E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142671E+09 | 0.705185E+10 |
November | 0.909363E+10 | 0.393741E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118871E+11 |
December | 0.939996E+10 | 0.428410E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170112E+11 |
Annual Sum or Average | 0.111326E+12 | 0.422053E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112173E+11 | 0.908593E+11 |
Minimum of Months | 0.852256E+10 | 0.294847E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584984E+09 |
Maximum of Months | 0.954557E+10 | 0.428410E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378552E+10 | 0.170112E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.138574E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48019939.99 |
February | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46283965.50 |
March | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50097135.90 |
April | 0.655836E+09 | 0.134648E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34300084.56 |
May | 0.679007E+09 | 0.139678E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 397191.58 | 29527793.04 |
June | 0.661256E+09 | 0.136076E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3265204.61 | 18190585.66 |
July | 0.673587E+09 | 0.138266E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4161168.85 | 11984936.74 |
August | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2247711.19 | 15504360.78 |
September | 0.655836E+09 | 0.134680E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 553224.11 | 19144136.34 |
October | 0.673993E+09 | 0.138558E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 61561.83 | 29639544.48 |
November | 0.651635E+09 | 0.134145E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39795352.05 |
December | 0.673587E+09 | 0.138282E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42521869.77 |
Annual Sum or Average | 0.797748E+10 | 0.163998E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 10686062.16 | 0.385010E+09 |
Minimum of Months | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11984936.74 |
Maximum of Months | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4161168.85 | 50097135.90 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420944E+09 | 0.802330E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339517E+09 | 0.989219E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348515E+09 | 0.125826E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354743E+09 | 0.162549E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335998E+09 | 0.172691E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288185E+09 | 0.167897E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257412E+09 | 0.174131E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233712E+09 | 0.170344E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313374E+09 | 0.137938E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399503E+09 | 0.114189E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422433E+09 | 0.896946E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480232E+09 | 0.798716E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419457E+10 | 0.157429E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233712E+09 | 0.798716E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480232E+09 | 0.174131E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 400.32 | 02-JAN-17:10 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 21921.93 | 19-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 400.32 | 01-FEB-17:30 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 19816.89 | 04-FEB-19:55 |
March | 9454.80 | 04-MAR-19:10 | 400.32 | 01-MAR-17:00 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 14670.37 | 04-MAR-19:53 |
April | 9454.80 | 01-APR-18:10 | 400.32 | 01-APR-18:30 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.07 | 13-APR-17:02 | 11788.26 | 15-APR-18:02 |
May | 9454.80 | 06-MAY-18:10 | 400.32 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4336.16 | 19-MAY-17:10 | 9458.28 | 01-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 400.32 | 01-JUN-19:10 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9478.85 | 28-JUN-17:02 | 7788.26 | 08-JUN-20:00 |
July | 9454.80 | 01-JUL-18:10 | 400.32 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9647.64 | 21-JUL-17:03 | 4225.15 | 07-JUL-17:56 |
August | 9454.80 | 05-AUG-18:10 | 400.32 | 01-AUG-18:00 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6792.34 | 04-AUG-17:10 | 5090.53 | 25-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 400.32 | 01-SEP-18:40 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4524.08 | 20-SEP-17:10 | 6660.64 | 23-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 400.32 | 02-OCT-17:49 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.34 | 10-OCT-13:00 | 15373.72 | 24-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 400.32 | 01-NOV-17:10 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 15638.74 | 27-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 400.32 | 01-DEC-16:00 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 19680.85 | 09-DEC-19:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4225.15 | |||||
Maximum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9647.64 | 21921.93 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 811.23 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 188.68 | 17-JAN-04:10 |
February | 677.52 | 04-FEB-19:10 | 811.23 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 186.38 | 05-FEB-02:00 |
March | 677.52 | 04-MAR-19:10 | 811.23 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 209.80 | 14-MAR-03:05 |
April | 677.52 | 01-APR-18:10 | 811.23 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 212.51 | 23-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 811.23 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 6.26 | 19-MAY-15:00 | 167.02 | 18-MAY-03:10 |
June | 677.52 | 03-JUN-18:10 | 811.23 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 14.27 | 17-JUN-16:00 | 127.87 | 02-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 811.23 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 15.83 | 04-JUL-14:53 | 60.63 | 05-JUL-00:40 |
August | 677.52 | 05-AUG-18:10 | 811.23 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 8.32 | 02-AUG-13:00 | 83.14 | 08-AUG-00:50 |
September | 677.52 | 02-SEP-18:10 | 811.23 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 5.19 | 03-SEP-14:51 | 96.06 | 18-SEP-01:00 |
October | 677.52 | 07-OCT-18:10 | 811.23 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 1.99 | 01-OCT-15:53 | 128.33 | 12-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 811.23 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 201.61 | 25-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 811.23 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 277.49 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 | ||||||
Maximum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 15.83 | 277.49 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.26 | 11-JAN-00:02 | 1538.19 | 29-JAN-13:20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.92 | 14-FEB-07:23 | 1930.92 | 04-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.22 | 08-MAR-05:00 | 2152.20 | 11-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.41 | 01-APR-04:00 | 2721.05 | 08-APR-13:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.27 | 09-MAY-03:51 | 2543.47 | 28-MAY-13:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.99 | 20-JUN-01:55 | 2360.01 | 03-JUN-13:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.12 | 14-JUL-05:53 | 2299.36 | 28-JUL-13:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.52 | 17-AUG-04:10 | 2261.62 | 03-AUG-13:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.05 | 27-SEP-23:00 | 2147.13 | 13-SEP-12:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.03 | 29-OCT-22:00 | 2279.11 | 26-OCT-13:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.25 | 12-NOV-23:00 | 1794.17 | 12-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.56 | 13-DEC-02:70 | 1710.98 | 22-DEC-13:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.52 | 1538.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.26 | 2721.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8666.44 | 20-JAN-00:01 | 4202.13 | 533.77 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9146.60 | 04-FEB-05:02 | 0.00 | 667.21 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 |
March | 6762.14 | 26-MAR-04:01 | 0.00 | 667.21 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
April | 10410.79 | 27-APR-04:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 |
May | 16495.35 | 20-MAY-04:01 | 0.00 | 667.21 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.46 |
June | 23218.29 | 29-JUN-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
July | 26383.45 | 21-JUL-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 |
August | 24275.98 | 18-AUG-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 |
September | 21470.35 | 21-SEP-04:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 |
October | 22051.58 | 05-OCT-04:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
November | 8048.84 | 01-NOV-04:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
December | 8811.27 | 15-DEC-05:00 | 0.00 | 533.77 | 5400.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6762.14 | 0.00 | 533.77 | 3252.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26383.45 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25202.88 | 27-JAN-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24549.93 | 04-FEB-05:01 | 0.00 | 1352.07 | 32211.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
March | 24208.16 | 10-MAR-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
April | 45520.90 | 14-APR-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
May | 45026.52 | 12-MAY-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38721.59 | 18-JUN-04:01 | 0.00 | 1352.07 | 32211.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 32210.11 | 21-JUL-04:01 | 338.76 | 1622.51 | 29081.76 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
August | 31256.22 | 25-AUG-03:11 | 0.00 | 1352.07 | 16867.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
September | 40134.73 | 29-SEP-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 |
October | 39177.95 | 20-OCT-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
November | 23404.27 | 27-NOV-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 |
December | 28460.80 | 15-DEC-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 23404.27 | 0.00 | 1352.07 | 16867.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45520.90 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.94 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.24 | 0.00 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.83 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.80 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.30 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.43 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.54 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.40 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.27 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.14 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.47 | 0.00 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.80 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.334291E+11 | 21209.11 | 20-JAN-11:09 | 0.102913E+12 | 85156.53 | 20-JAN-04:19 |
February | 0.300074E+11 | 21031.45 | 06-FEB-11:09 | 0.855568E+11 | 78666.65 | 01-FEB-04:10 |
March | 0.328535E+11 | 20820.81 | 03-MAR-11:09 | 0.746502E+11 | 67015.22 | 05-MAR-07:10 |
April | 0.331163E+11 | 22592.06 | 28-APR-10:20 | 0.611944E+11 | 55629.20 | 06-APR-10:50 |
May | 0.366476E+11 | 26114.35 | 23-MAY-10:20 | 0.585185E+11 | 50239.78 | 05-MAY-10:09 |
June | 0.414005E+11 | 32945.93 | 28-JUN-16:10 | 0.546141E+11 | 48023.01 | 03-JUN-12:20 |
July | 0.465242E+11 | 32484.93 | 21-JUL-17:10 | 0.556634E+11 | 47294.86 | 01-JUL-12:20 |
August | 0.445258E+11 | 29753.28 | 17-AUG-10:20 | 0.555621E+11 | 47020.85 | 31-AUG-12:20 |
September | 0.387608E+11 | 27561.79 | 03-SEP-10:20 | 0.541624E+11 | 47576.80 | 30-SEP-12:00 |
October | 0.352071E+11 | 26150.37 | 11-OCT-10:20 | 0.627530E+11 | 66647.47 | 25-OCT-10:20 |
November | 0.319672E+11 | 20925.35 | 27-NOV-11:09 | 0.742226E+11 | 64913.74 | 27-NOV-08:09 |
December | 0.334777E+11 | 21142.05 | 21-DEC-11:09 | 0.103175E+12 | 85155.96 | 09-DEC-04:49 |
Annual Sum or Average | 0.437917E+12 | 0.842986E+12 | ||||
Minimum of Months | 0.300074E+11 | 20820.81 | 0.541624E+11 | 47020.85 | ||
Maximum of Months | 0.465242E+11 | 32945.93 | 0.103175E+12 | 85156.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.179327E+10 | 0.161473E+10 | 0.214106E+11 | 0.00 | 0.564056E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160951E+10 | 0.135025E+10 | 0.193386E+11 | 0.00 | 0.496054E+10 | 0.72 | 0.00 | 43206714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176986E+10 | 0.133860E+10 | 0.214107E+11 | 0.00 | 0.514146E+10 | 0.80 | 0.00 | 0.103877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166363E+10 | 0.113531E+10 | 0.207199E+11 | 0.00 | 0.482882E+10 | 0.77 | 0.00 | 0.166137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171794E+10 | 0.103851E+10 | 0.214107E+11 | 0.00 | 0.498076E+10 | 0.80 | 0.00 | 0.419130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165560E+10 | 0.944405E+09 | 0.207201E+11 | 0.00 | 0.505516E+10 | 0.77 | 0.00 | 0.975973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169306E+10 | 0.999666E+09 | 0.214105E+11 | 0.00 | 0.538764E+10 | 0.79 | 0.00 | 0.136300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173340E+10 | 0.111157E+10 | 0.214107E+11 | 0.00 | 0.523940E+10 | 0.80 | 0.00 | 0.116238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168043E+10 | 0.122789E+10 | 0.207199E+11 | 0.00 | 0.488420E+10 | 0.77 | 0.00 | 0.697921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175722E+10 | 0.143118E+10 | 0.214106E+11 | 0.00 | 0.504523E+10 | 0.79 | 0.00 | 0.232813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173519E+10 | 0.152496E+10 | 0.207200E+11 | 0.00 | 0.503919E+10 | 0.77 | 0.00 | 9997859.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181123E+10 | 0.165338E+10 | 0.214105E+11 | 0.00 | 0.565460E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206204E+11 | 0.153705E+11 | 0.252093E+12 | 0.00 | 0.618575E+11 | 9.37 | 0.00 | 0.503307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160951E+10 | 0.944405E+09 | 0.193386E+11 | 0.00 | 0.482882E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181123E+10 | 0.165338E+10 | 0.214107E+11 | 0.00 | 0.565460E+10 | 0.80 | 0.00 | 0.136300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.432100E+11 | 0.00 | 0.191772E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.315226E+11 | 0.00 | 0.174303E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.152372E+11 | 0.00 | 0.188873E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.461163E+10 | 0.00 | 0.173643E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.113490E+10 | 0.00 | 0.168579E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 67266254.24 | 0.00 | 0.153284E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.151376E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.150364E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 9384581.25 | 0.00 | 0.149346E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.587067E+10 | 0.00 | 0.163566E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.180535E+11 | 0.00 | 0.169506E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.441351E+11 | 0.00 | 0.185146E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.163852E+12 | 0.00 | 0.201976E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.149346E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.441351E+11 | 0.00 | 0.191772E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1211.55 | 02-JAN-17:10 | 1341.77 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 3193.48 | 21-JAN-07:10 | 0.00 | 06-JAN-11:39 | 0.00 | 01-JAN-00:10 |
February | 1211.55 | 01-FEB-17:30 | 1341.77 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 3138.63 | 05-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1211.55 | 01-MAR-17:00 | 1341.77 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2957.03 | 05-MAR-07:10 | 0.00 | 02-MAR-08:39 | 0.00 | 01-MAR-00:10 |
April | 1211.55 | 01-APR-18:30 | 1341.77 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 2702.14 | 08-APR-06:10 | 0.00 | 02-APR-08:30 | 0.00 | 01-APR-00:10 |
May | 1211.55 | 01-MAY-18:49 | 1341.77 | 01-MAY-05:10 | 13637.09 | 01-MAY-10:09 | 0.00 | 2490.64 | 06-MAY-06:10 | 0.00 | 07-MAY-06:49 | 0.00 | 01-MAY-00:10 |
June | 1211.55 | 01-JUN-19:10 | 1341.77 | 01-JUN-19:10 | 13637.09 | 01-JUN-10:09 | 0.00 | 3526.86 | 28-JUN-17:10 | 0.00 | 03-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 1211.55 | 01-JUL-19:19 | 1341.77 | 01-JUL-19:19 | 13637.09 | 01-JUL-10:09 | 0.00 | 3606.58 | 21-JUL-17:10 | 0.00 | 07-JUL-07:40 | 0.00 | 01-JUL-00:10 |
August | 1211.55 | 01-AUG-18:00 | 1341.77 | 01-AUG-05:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 2932.72 | 17-AUG-11:09 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1211.55 | 01-SEP-18:40 | 1341.77 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 2575.11 | 03-SEP-13:00 | 0.00 | 20-SEP-07:40 | 0.00 | 01-SEP-00:10 |
October | 1211.55 | 02-OCT-17:49 | 1341.77 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 2856.28 | 26-OCT-06:00 | 0.00 | 20-OCT-10:39 | 0.00 | 01-OCT-00:10 |
November | 1211.55 | 01-NOV-17:10 | 1341.77 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 2932.88 | 27-NOV-07:10 | 0.00 | 08-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 1211.55 | 01-DEC-16:00 | 1341.77 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 3131.04 | 15-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 2490.64 | 0.00 | 0.00 | ||||||
Maximum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 3606.58 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2358.88 | 14-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3387.19 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5733.36 | 13-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7906.97 | 19-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15186.79 | 28-JUN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15439.93 | 21-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11645.11 | 17-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9996.88 | 03-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7545.42 | 11-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1147.37 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15439.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 21209.11 | 20-JAN-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2826.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21031.45 | 06-FEB-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2656.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20820.81 | 03-MAR-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2438.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22592.06 | 28-APR-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2171.85 | 0.00 | 0.00 | 1973.81 | 0.00 |
May | 26114.35 | 23-MAY-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2171.85 | 0.00 | 0.00 | 5487.09 | 0.00 |
June | 32945.93 | 28-JUN-16:10 | 907.31 | 12287.48 | 0.00 | 0.00 | 3423.26 | 0.00 | 0.00 | 15186.79 | 0.00 |
July | 32484.93 | 21-JUL-17:10 | 907.31 | 11387.73 | 0.00 | 0.00 | 3606.58 | 0.00 | 0.00 | 15439.93 | 0.00 |
August | 29753.28 | 17-AUG-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2381.23 | 0.00 | 0.00 | 8909.78 | 0.00 |
September | 27561.79 | 03-SEP-10:20 | 705.69 | 13637.09 | 0.00 | 0.00 | 2175.37 | 0.00 | 0.00 | 7149.99 | 0.00 |
October | 26150.37 | 11-OCT-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2171.85 | 0.00 | 0.00 | 5517.21 | 0.00 |
November | 20925.35 | 27-NOV-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2549.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21142.05 | 21-DEC-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2765.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 20820.81 | 705.69 | 11387.73 | 0.00 | 0.00 | 2171.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32945.93 | 907.31 | 13637.09 | 0.00 | 0.00 | 3606.58 | 0.00 | 0.00 | 15439.93 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 73348.02 | 20-JAN-04:10 | 0.00 | 27214.26 | 31-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 73348.02 | 01-FEB-04:10 | 0.00 | 27221.20 | 05-FEB-13:30 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 45272.28 | 05-MAR-07:10 | 0.00 | 27114.10 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 29590.81 | 08-APR-06:10 | 0.00 | 26675.50 | 01-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 16698.07 | 06-MAY-06:10 | 0.00 | 25985.79 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 5419.70 | 09-JUN-06:10 | 0.00 | 25039.86 | 03-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 24311.71 | 01-JUL-12:20 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 24037.70 | 31-AUG-12:20 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 2521.73 | 09-SEP-06:10 | 0.00 | 24593.65 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 39583.97 | 26-OCT-06:00 | 0.00 | 25563.31 | 31-OCT-12:30 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 44355.15 | 27-NOV-07:10 | 0.00 | 26378.73 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 73348.02 | 05-DEC-04:10 | 0.00 | 26954.25 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 24037.70 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 73348.02 | 0.00 | 27221.20 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
February | 2.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.18 | 0.00 | 26.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.22 | 0.00 | 26.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 6.67 | 19.01 | 0.00 | 19.01 | 1.33 | 20.21 | 0.00 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.07 | 0.00 | 19.07 | 0.50 | 26.22 | 0.00 | 26.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.66 | 0.00 | 28.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 29.43 | 0.00 | 29.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 29.94 | 0.00 | 29.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.46 | 0.00 | 30.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 30.71 | 0.00 | 30.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 30.73 | 0.00 | 30.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 30.43 | 0.00 | 30.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 30.02 | 0.00 | 30.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.98 | 0.00 | 28.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 129.50 | 30.40 | 0.00 | 30.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 30.73 | 0.00 | 30.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 608.50 | 20.91 | 173.17 | 20.73 | 173.17 | 20.62 |
February | 531.83 | 20.92 | 130.83 | 20.74 | 130.83 | 20.61 |
March | 552.33 | 21.21 | 87.00 | 21.03 | 87.00 | 20.90 |
April | 390.67 | 21.66 | 48.00 | 21.67 | 26.33 | 21.57 |
May | 244.50 | 21.95 | 195.33 | 22.75 | 9.50 | 22.71 |
June | 67.00 | 22.16 | 452.67 | 23.76 | 3.00 | 23.77 |
July | 96.00 | 24.07 | 609.00 | 24.05 | 96.00 | 24.05 |
August | 76.00 | 23.95 | 608.17 | 24.00 | 74.83 | 24.00 |
September | 76.67 | 22.80 | 500.17 | 23.76 | 34.50 | 23.75 |
October | 314.83 | 21.40 | 222.50 | 22.29 | 19.83 | 22.21 |
November | 570.67 | 21.07 | 75.33 | 20.93 | 70.83 | 20.80 |
December | 609.00 | 20.84 | 159.67 | 20.67 | 159.67 | 20.56 |
Annual Sum or Average | 4138.00 | 21.32 | 3261.83 | 22.13 | 885.50 | 22.00 |
Minimum of Months | 67.00 | 20.84 | 48.00 | 20.67 | 3.00 | 20.56 |
Maximum of Months | 609.00 | 24.07 | 609.00 | 24.05 | 173.17 | 24.05 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 584.83 | 19.17 | 274.00 | 18.96 | 268.67 | 18.82 |
February | 504.17 | 19.30 | 238.17 | 19.28 | 206.83 | 19.08 |
March | 418.33 | 19.70 | 258.83 | 20.64 | 115.33 | 20.32 |
April | 372.00 | 22.75 | 354.17 | 23.85 | 183.00 | 24.07 |
May | 409.33 | 25.19 | 501.33 | 25.42 | 344.50 | 25.59 |
June | 510.67 | 26.13 | 581.83 | 26.03 | 506.33 | 26.08 |
July | 609.00 | 26.23 | 609.00 | 26.23 | 609.00 | 26.23 |
August | 604.17 | 26.18 | 612.00 | 26.17 | 604.17 | 26.17 |
September | 492.00 | 26.07 | 588.67 | 25.91 | 492.00 | 25.96 |
October | 429.17 | 23.32 | 411.17 | 24.13 | 265.83 | 24.40 |
November | 491.33 | 19.63 | 210.17 | 19.81 | 146.00 | 19.58 |
December | 608.33 | 18.97 | 292.50 | 18.80 | 292.50 | 18.71 |
Annual Sum or Average | 6033.33 | 22.72 | 4931.83 | 23.38 | 4034.17 | 23.56 |
Minimum of Months | 372.00 | 18.97 | 210.17 | 18.80 | 115.33 | 18.71 |
Maximum of Months | 609.00 | 26.23 | 612.00 | 26.23 | 609.00 | 26.23 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.91579 | 19.55491 | -0.4764 | 11.11025 |
February | 551.00000 | 21.02310 | 21.42893 | -0.4282 | 10.48626 |
March | 612.00000 | 21.46817 | 21.50755 | -0.3003 | 8.87644 |
April | 590.00000 | 22.41429 | 18.35989 | -0.0487 | 7.47116 |
May | 611.00000 | 23.11739 | 26.05405 | -0.7459 | 20.01977 |
June | 592.00000 | 23.76936 | 33.52041 | -0.4091 | 9.89382 |
July | 609.00000 | 24.04747 | 45.32420 | -0.1918 | 6.04590 |
August | 612.00000 | 24.00399 | 44.76712 | -0.1957 | 6.16075 |
September | 590.00000 | 23.75300 | 39.99010 | -0.3291 | 8.38998 |
October | 610.00000 | 22.57733 | 27.54218 | 0.10876 | 8.48922 |
November | 591.00000 | 21.15189 | 21.81278 | -0.3261 | 8.55542 |
December | 609.00000 | 20.83521 | 17.57031 | -0.4910 | 11.12287 |
Annual Sum or Average | 7187.00000 | 22.43115 | 28.17314 | -0.3191 | 9.72530 |
Minimum of Months | 551.00000 | 20.83521 | 17.57031 | -0.7459 | 6.04590 |
Maximum of Months | 612.00000 | 24.04747 | 45.32420 | 0.10876 | 20.01977 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.35027 | 28.44648 | -0.5577 | 14.24121 |
February | 551.00000 | 19.73786 | 30.16337 | -0.4601 | 13.70788 |
March | 612.00000 | 21.25099 | 28.92369 | -0.1047 | 12.07390 |
April | 590.00000 | 23.44100 | 24.16261 | 0.40057 | 15.76141 |
May | 611.00000 | 24.89052 | 29.29543 | 0.11288 | 13.56798 |
June | 592.00000 | 25.87412 | 34.39066 | 0.53316 | 13.23291 |
July | 609.00000 | 26.22956 | 43.87988 | 0.75458 | 17.35066 |
August | 612.00000 | 26.15515 | 43.56829 | 0.72548 | 16.63188 |
September | 590.00000 | 25.77424 | 39.99632 | 0.54880 | 13.36745 |
October | 610.00000 | 23.56541 | 31.69932 | 0.52310 | 19.76150 |
November | 591.00000 | 20.32364 | 29.69535 | -0.2777 | 11.59788 |
December | 609.00000 | 18.97333 | 26.59103 | -0.6430 | 15.20511 |
Annual Sum or Average | 7187.00000 | 22.98165 | 32.59403 | 0.13272 | 14.72845 |
Minimum of Months | 551.00000 | 18.97333 | 24.16261 | -0.6430 | 11.59788 |
Maximum of Months | 612.00000 | 26.22956 | 43.87988 | 0.75458 | 19.76150 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 64760477.52 | 19700377.99 | 7.83 | 64760477.52 | 0.00 | 0.00 | 0.24 | 14-FEB-15:53 | 0.00 | 01-FEB-00:01 | 4036.51 | 14-FEB-15:53 | 4036.51 | 14-FEB-15:53 | 0.00 | 14-FEB-15:10 | 1207.09 | 14-FEB-15:53 | 0.00 | 01-FEB-00:01 |
March | 0.111773E+09 | 33908655.28 | 18.00 | 0.111773E+09 | -0.0 | 0.00 | 0.36 | 08-MAR-14:00 | 0.00 | 01-MAR-00:02 | 6175.21 | 08-MAR-14:00 | 6175.21 | 08-MAR-14:00 | 0.00 | 08-MAR-14:00 | 1793.54 | 08-MAR-14:00 | 0.00 | 01-MAR-00:02 |
April | 0.252049E+10 | 0.727406E+09 | 139.50 | 0.252038E+10 | 108220.16 | 0.00 | 0.65 | 13-APR-17:04 | 0.00 | 01-APR-00:01 | 11923.69 | 13-APR-17:04 | 11923.69 | 13-APR-17:04 | 47.72 | 14-APR-19:10 | 3214.55 | 13-APR-17:04 | 0.00 | 01-APR-00:01 |
May | 0.683493E+10 | 0.191171E+10 | 261.98 | 0.673965E+10 | 95275931.42 | 0.00 | 0.88 | 19-MAY-17:05 | 0.00 | 01-MAY-00:01 | 17086.78 | 19-MAY-17:05 | 17086.78 | 19-MAY-17:05 | 2402.64 | 22-MAY-04:01 | 4392.92 | 19-MAY-17:05 | 0.00 | 01-MAY-00:01 |
June | 0.169355E+11 | 0.462833E+10 | 408.59 | 0.163872E+11 | 0.548279E+09 | 0.00 | 1.00 | 13-JUN-17:03 | 0.00 | 01-JUN-00:01 | 40537.55 | 29-JUN-03:01 | 35838.51 | 29-JUN-03:42 | 9333.63 | 24-JUN-03:01 | 9892.25 | 24-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.242395E+11 | 0.649213E+10 | 514.29 | 0.209155E+11 | 0.332406E+10 | 0.00 | 1.00 | 02-JUL-04:01 | 0.00 | 01-JUL-00:01 | 40537.55 | 20-JUL-03:01 | 39631.70 | 21-JUL-03:01 | 11536.86 | 02-JUL-04:01 | 9892.25 | 20-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.209362E+11 | 0.556652E+10 | 478.76 | 0.181249E+11 | 0.281127E+10 | 0.00 | 1.00 | 01-AUG-11:53 | 0.00 | 01-AUG-00:01 | 40537.55 | 22-AUG-03:41 | 34986.41 | 18-AUG-03:01 | 11263.54 | 22-AUG-03:01 | 9892.25 | 10-AUG-03:02 | 0.00 | 01-AUG-00:01 |
September | 0.120049E+11 | 0.325346E+10 | 350.84 | 0.108199E+11 | 0.118501E+10 | 0.00 | 1.00 | 15-SEP-03:01 | 0.00 | 01-SEP-00:01 | 20245.52 | 15-SEP-03:01 | 18360.53 | 02-SEP-17:03 | 7967.50 | 23-SEP-04:01 | 4944.30 | 15-SEP-03:01 | 0.00 | 01-SEP-00:01 |
October | 0.375412E+10 | 0.104240E+10 | 152.65 | 0.347967E+10 | 0.274451E+09 | 0.00 | 0.89 | 01-OCT-04:01 | 0.00 | 01-OCT-00:01 | 17425.79 | 01-OCT-04:01 | 13889.65 | 05-OCT-17:04 | 4583.43 | 03-OCT-04:01 | 4395.88 | 01-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 301.06 | 95.36 | 0.02 | 285.05 | 16.01 | 0.00 | 0.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:01 | 5.02 | 01-NOV-04:01 | 4.75 | 01-NOV-04:01 | 0.27 | 01-NOV-04:01 | 1.59 | 01-NOV-04:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.874022E+11 | 0.236756E+11 | 2332.45 | 0.791638E+11 | 0.823845E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.242395E+11 | 0.649213E+10 | 514.29 | 0.209155E+11 | 0.332406E+10 | 0.00 | 1.00 | 0.00 | 40537.55 | 39631.70 | 11536.86 | 9892.25 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 79808255.50 | 23506336.01 | 9.72 | 79765122.85 | 43132.66 | 0.00 | 0.35 | 14-FEB-15:10 | 0.00 | 01-FEB-00:01 | 4342.80 | 14-FEB-15:10 | 4342.80 | 14-FEB-15:10 | 715.27 | 15-FEB-05:01 | 1242.32 | 14-FEB-15:10 | 0.00 | 01-FEB-00:01 |
March | 0.236477E+09 | 69968140.00 | 43.14 | 0.235250E+09 | 1227013.60 | 0.00 | 0.53 | 21-MAR-04:01 | 0.00 | 01-MAR-00:02 | 6815.18 | 21-MAR-04:01 | 5712.91 | 08-MAR-14:00 | 1838.15 | 21-MAR-04:01 | 1863.88 | 21-MAR-04:01 | 0.00 | 01-MAR-00:02 |
April | 0.337858E+10 | 0.933962E+09 | 201.55 | 0.336854E+10 | 10036789.46 | 0.00 | 1.00 | 12-APR-04:01 | 0.00 | 01-APR-00:01 | 29393.61 | 14-APR-03:21 | 27991.77 | 14-APR-03:21 | 7564.50 | 15-APR-04:01 | 7047.09 | 14-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.866625E+10 | 0.227959E+10 | 339.84 | 0.834428E+10 | 0.321968E+09 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:01 | 29393.61 | 09-MAY-03:21 | 29393.61 | 20-MAY-03:01 | 14488.34 | 24-MAY-04:01 | 7047.09 | 09-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.198091E+11 | 0.513140E+10 | 474.29 | 0.189849E+11 | 0.824266E+09 | 0.00 | 1.00 | 01-JUN-03:32 | 0.00 | 01-JUN-00:01 | 29393.61 | 04-JUN-03:11 | 28207.42 | 28-JUN-00:42 | 15190.78 | 05-JUN-03:11 | 8119.95 | 28-JUN-16:00 | 0.00 | 01-JUN-00:01 |
July | 0.281531E+11 | 0.713791E+10 | 581.79 | 0.244920E+11 | 0.366116E+10 | 0.00 | 1.00 | 01-JUL-01:32 | 0.00 | 01-JUL-00:01 | 29673.87 | 04-JUL-00:42 | 27644.48 | 22-JUL-14:10 | 17288.65 | 01-JUL-03:32 | 7953.09 | 21-JUL-14:00 | 0.00 | 01-JUL-00:01 |
August | 0.241105E+11 | 0.605732E+10 | 556.35 | 0.206736E+11 | 0.343695E+10 | 0.00 | 1.00 | 01-AUG-01:32 | 0.00 | 01-AUG-00:01 | 29393.61 | 05-AUG-02:11 | 26061.27 | 18-AUG-00:42 | 17578.82 | 13-AUG-02:52 | 7047.09 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 |
September | 0.146468E+11 | 0.372576E+10 | 436.31 | 0.126097E+11 | 0.203716E+10 | 0.00 | 1.00 | 01-SEP-01:32 | 0.00 | 01-SEP-00:01 | 29393.61 | 24-SEP-04:01 | 25153.67 | 22-SEP-03:31 | 16728.82 | 06-SEP-03:01 | 7047.09 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.487114E+10 | 0.128573E+10 | 222.68 | 0.435292E+10 | 0.518225E+09 | 0.00 | 1.00 | 01-OCT-02:62 | 0.00 | 01-OCT-00:01 | 29393.61 | 10-OCT-03:21 | 23083.12 | 06-OCT-03:31 | 12524.90 | 03-OCT-03:11 | 7047.09 | 01-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 34143162.30 | 9997764.05 | 4.03 | 29147415.62 | 4995746.68 | 0.00 | 0.76 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 | 10429.10 | 09-NOV-05:01 | 7610.20 | 09-NOV-05:01 | 2818.91 | 09-NOV-05:01 | 2680.03 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.103986E+12 | 0.266551E+11 | 2869.71 | 0.931700E+11 | 0.108160E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.281531E+11 | 0.713791E+10 | 581.79 | 0.244920E+11 | 0.366116E+10 | 0.00 | 1.00 | 0.00 | 29673.87 | 29393.61 | 17578.82 | 8119.95 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 124.52 | 69.62 | 54.90 | 113.69 | 151.98 | 0.00 | 0.00 | 0.00 |
February | 151.29 | 81.56 | 69.73 | 151.88 | 135.83 | 0.00 | 0.00 | 0.00 |
March | 199.58 | 113.46 | 86.12 | 227.35 | 103.96 | 0.00 | 0.00 | 0.00 |
April | 272.66 | 155.33 | 117.33 | 339.08 | 72.82 | 0.00 | 0.00 | 0.00 |
May | 260.18 | 148.27 | 111.91 | 340.50 | 56.35 | 0.00 | 0.00 | 0.00 |
June | 280.49 | 172.80 | 107.70 | 399.91 | 38.24 | 0.00 | 0.00 | 0.00 |
July | 259.55 | 148.42 | 111.13 | 385.58 | 27.02 | 0.00 | 0.00 | 0.00 |
August | 256.84 | 141.60 | 115.24 | 368.35 | 31.41 | 0.00 | 0.00 | 0.00 |
September | 213.77 | 119.61 | 94.17 | 289.07 | 53.09 | 0.00 | 0.00 | 0.00 |
October | 185.92 | 117.96 | 67.96 | 223.20 | 87.46 | 0.00 | 0.00 | 0.00 |
November | 145.30 | 85.42 | 59.88 | 149.48 | 121.65 | 0.00 | 0.00 | 0.00 |
December | 117.74 | 71.65 | 46.08 | 107.28 | 160.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.86 | 118.96 | 86.90 | 258.42 | 86.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 117.74 | 69.62 | 46.08 | 107.28 | 27.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.49 | 172.80 | 117.33 | 399.91 | 160.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 664.86 | 517.35 | 147.51 | 799.42 | 293.50 | 0.00 | 0.00 | 0.00 |
February | 650.65 | 475.28 | 175.37 | 800.73 | 265.93 | 0.00 | 0.00 | 0.00 |
March | 479.46 | 289.87 | 189.60 | 606.86 | 212.92 | 0.00 | 0.00 | 0.00 |
April | 373.92 | 153.49 | 220.43 | 490.35 | 155.54 | 0.00 | 0.00 | 0.00 |
May | 249.38 | 54.86 | 194.52 | 329.04 | 117.83 | 0.00 | 0.00 | 0.00 |
June | 210.95 | 26.00 | 184.95 | 322.60 | 81.80 | 0.00 | 0.00 | 0.00 |
July | 233.43 | 37.28 | 196.15 | 386.19 | 56.55 | 0.00 | 0.00 | 0.00 |
August | 320.98 | 104.33 | 216.64 | 505.34 | 66.16 | 0.00 | 0.00 | 0.00 |
September | 443.84 | 247.50 | 196.34 | 648.14 | 110.35 | 0.00 | 0.00 | 0.00 |
October | 607.23 | 447.22 | 160.01 | 805.80 | 173.90 | 0.00 | 0.00 | 0.00 |
November | 676.34 | 519.09 | 157.25 | 838.29 | 233.57 | 0.00 | 0.00 | 0.00 |
December | 721.35 | 595.04 | 126.31 | 871.35 | 301.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 468.35 | 287.98 | 180.36 | 615.96 | 171.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.95 | 26.00 | 126.31 | 322.60 | 56.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.35 | 595.04 | 220.43 | 871.35 | 301.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.44 | 73.25 | 55.19 | 127.22 | 159.78 | 0.00 | 0.00 | 0.00 |
February | 165.35 | 95.52 | 69.83 | 176.66 | 142.17 | 0.00 | 0.00 | 0.00 |
March | 184.67 | 98.30 | 86.37 | 210.53 | 109.58 | 0.00 | 0.00 | 0.00 |
April | 235.70 | 125.44 | 110.26 | 288.11 | 75.98 | 0.00 | 0.00 | 0.00 |
May | 223.48 | 115.15 | 108.33 | 288.77 | 58.07 | 0.00 | 0.00 | 0.00 |
June | 239.57 | 133.67 | 105.89 | 344.40 | 41.18 | 0.00 | 0.00 | 0.00 |
July | 216.08 | 105.75 | 110.33 | 324.63 | 28.27 | 0.00 | 0.00 | 0.00 |
August | 220.80 | 102.13 | 118.67 | 319.16 | 33.05 | 0.00 | 0.00 | 0.00 |
September | 199.43 | 105.03 | 94.40 | 271.56 | 55.17 | 0.00 | 0.00 | 0.00 |
October | 182.45 | 113.40 | 69.05 | 222.26 | 91.88 | 0.00 | 0.00 | 0.00 |
November | 143.22 | 84.26 | 58.96 | 150.39 | 124.93 | 0.00 | 0.00 | 0.00 |
December | 123.86 | 77.67 | 46.19 | 120.03 | 165.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 188.60 | 102.42 | 86.19 | 237.18 | 90.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 123.86 | 73.25 | 46.19 | 120.03 | 28.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 239.57 | 133.67 | 118.67 | 344.40 | 165.23 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.333521E+09 | 0.186470E+09 | 0.147052E+09 | 0.304503E+09 | 0.407063E+09 |
February | 0.366007E+09 | 0.197317E+09 | 0.168690E+09 | 0.367439E+09 | 0.328604E+09 |
March | 0.534549E+09 | 0.303881E+09 | 0.230668E+09 | 0.608923E+09 | 0.278435E+09 |
April | 0.706745E+09 | 0.402628E+09 | 0.304116E+09 | 0.878907E+09 | 0.188745E+09 |
May | 0.696864E+09 | 0.397136E+09 | 0.299728E+09 | 0.911991E+09 | 0.150927E+09 |
June | 0.727038E+09 | 0.447889E+09 | 0.279149E+09 | 0.103656E+10 | 99124585.13 |
July | 0.695166E+09 | 0.397523E+09 | 0.297643E+09 | 0.103274E+10 | 72360308.53 |
August | 0.687914E+09 | 0.379259E+09 | 0.308654E+09 | 0.986586E+09 | 84139540.90 |
September | 0.554102E+09 | 0.310025E+09 | 0.244078E+09 | 0.749277E+09 | 0.137604E+09 |
October | 0.497962E+09 | 0.315937E+09 | 0.182025E+09 | 0.597821E+09 | 0.234258E+09 |
November | 0.376628E+09 | 0.221416E+09 | 0.155211E+09 | 0.387440E+09 | 0.315310E+09 |
December | 0.315348E+09 | 0.191918E+09 | 0.123430E+09 | 0.287343E+09 | 0.429409E+09 |
Annual Sum or Average | 0.649184E+10 | 0.375140E+10 | 0.274044E+10 | 0.814954E+10 | 0.272598E+10 |
Minimum of Months | 0.315348E+09 | 0.186470E+09 | 0.123430E+09 | 0.287343E+09 | 72360308.53 |
Maximum of Months | 0.727038E+09 | 0.447889E+09 | 0.308654E+09 | 0.103656E+10 | 0.429409E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178075E+10 | 0.138567E+10 | 0.395082E+09 | 0.214117E+10 | 0.786100E+09 |
February | 0.157406E+10 | 0.114980E+10 | 0.424263E+09 | 0.193712E+10 | 0.643348E+09 |
March | 0.128420E+10 | 0.776375E+09 | 0.507822E+09 | 0.162542E+10 | 0.570293E+09 |
April | 0.969204E+09 | 0.397840E+09 | 0.571364E+09 | 0.127099E+10 | 0.403155E+09 |
May | 0.667926E+09 | 0.146931E+09 | 0.520995E+09 | 0.881303E+09 | 0.315597E+09 |
June | 0.546784E+09 | 67384852.76 | 0.479399E+09 | 0.836171E+09 | 0.212021E+09 |
July | 0.625211E+09 | 99840029.85 | 0.525371E+09 | 0.103438E+10 | 0.151471E+09 |
August | 0.859711E+09 | 0.279449E+09 | 0.580262E+09 | 0.135351E+10 | 0.177215E+09 |
September | 0.115045E+10 | 0.641521E+09 | 0.508924E+09 | 0.167998E+10 | 0.286036E+09 |
October | 0.162641E+10 | 0.119784E+10 | 0.428569E+09 | 0.215825E+10 | 0.465774E+09 |
November | 0.175308E+10 | 0.134548E+10 | 0.407597E+09 | 0.217284E+10 | 0.605422E+09 |
December | 0.193206E+10 | 0.159375E+10 | 0.338314E+09 | 0.233384E+10 | 0.807085E+09 |
Annual Sum or Average | 0.147698E+11 | 0.908188E+10 | 0.568796E+10 | 0.194250E+11 | 0.542352E+10 |
Minimum of Months | 0.546784E+09 | 67384852.76 | 0.338314E+09 | 0.836171E+09 | 0.151471E+09 |
Maximum of Months | 0.193206E+10 | 0.159375E+10 | 0.580262E+09 | 0.233384E+10 | 0.807085E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.344015E+09 | 0.196180E+09 | 0.147834E+09 | 0.340746E+09 | 0.427965E+09 |
February | 0.400005E+09 | 0.231070E+09 | 0.168934E+09 | 0.427368E+09 | 0.343927E+09 |
March | 0.494627E+09 | 0.263299E+09 | 0.231328E+09 | 0.563894E+09 | 0.293505E+09 |
April | 0.610928E+09 | 0.325138E+09 | 0.285790E+09 | 0.746783E+09 | 0.196938E+09 |
May | 0.598557E+09 | 0.308418E+09 | 0.290139E+09 | 0.773443E+09 | 0.155535E+09 |
June | 0.620953E+09 | 0.346485E+09 | 0.274468E+09 | 0.892676E+09 | 0.106748E+09 |
July | 0.578750E+09 | 0.283232E+09 | 0.295518E+09 | 0.869482E+09 | 75706129.71 |
August | 0.591380E+09 | 0.273537E+09 | 0.317843E+09 | 0.854846E+09 | 88527752.91 |
September | 0.516924E+09 | 0.272242E+09 | 0.244681E+09 | 0.703877E+09 | 0.143012E+09 |
October | 0.488679E+09 | 0.303731E+09 | 0.184948E+09 | 0.595295E+09 | 0.246102E+09 |
November | 0.371237E+09 | 0.218406E+09 | 0.152830E+09 | 0.389804E+09 | 0.323828E+09 |
December | 0.331745E+09 | 0.208040E+09 | 0.123706E+09 | 0.321486E+09 | 0.442556E+09 |
Annual Sum or Average | 0.594780E+10 | 0.322978E+10 | 0.271802E+10 | 0.747970E+10 | 0.284435E+10 |
Minimum of Months | 0.331745E+09 | 0.196180E+09 | 0.123706E+09 | 0.321486E+09 | 75706129.71 |
Maximum of Months | 0.620953E+09 | 0.346485E+09 | 0.317843E+09 | 0.892676E+09 | 0.442556E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1023.08 | 588.01 | 917.82 | 660.21 | 257.60 | 0.00 | 0.00 |
February | 1115.05 | 529.71 | 967.29 | 652.36 | 314.93 | 0.00 | 0.00 |
March | 1029.63 | 411.35 | 863.71 | 501.63 | 362.09 | 0.00 | 0.00 |
April | 1100.55 | 287.34 | 882.28 | 434.26 | 448.02 | 0.00 | 0.00 |
May | 949.69 | 223.63 | 733.03 | 318.28 | 414.75 | 0.00 | 0.00 |
June | 1059.25 | 153.57 | 731.01 | 332.47 | 398.54 | 0.00 | 0.00 |
July | 1093.80 | 109.23 | 709.05 | 291.44 | 417.61 | 0.00 | 0.00 |
August | 1188.73 | 126.51 | 798.61 | 348.06 | 450.55 | 0.00 | 0.00 |
September | 1202.59 | 212.44 | 857.05 | 472.14 | 384.91 | 0.00 | 0.00 |
October | 1241.46 | 343.45 | 975.60 | 678.58 | 297.02 | 0.00 | 0.00 |
November | 1125.10 | 467.10 | 964.87 | 688.77 | 276.09 | 0.00 | 0.00 |
December | 1075.83 | 604.05 | 962.95 | 744.36 | 218.58 | 0.00 | 0.00 |
Annual Sum or Average | 1100.04 | 337.09 | 862.81 | 509.36 | 353.45 | 0.00 | 0.00 |
Minimum of Months | 949.69 | 109.23 | 709.05 | 291.44 | 218.58 | 0.00 | 0.00 |
Maximum of Months | 1241.46 | 604.05 | 975.60 | 744.36 | 450.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.274022E+10 | 0.157494E+10 | 0.245829E+10 | 0.176832E+10 | 0.689968E+09 | 0.00 | 0.00 |
February | 0.269753E+10 | 0.128148E+10 | 0.234007E+10 | 0.157818E+10 | 0.761888E+09 | 0.00 | 0.00 |
March | 0.275777E+10 | 0.110177E+10 | 0.231337E+10 | 0.134355E+10 | 0.969818E+09 | 0.00 | 0.00 |
April | 0.285262E+10 | 0.744779E+09 | 0.228688E+10 | 0.112561E+10 | 0.116127E+10 | 0.00 | 0.00 |
May | 0.254365E+10 | 0.598976E+09 | 0.196335E+10 | 0.852485E+09 | 0.111086E+10 | 0.00 | 0.00 |
June | 0.274557E+10 | 0.398051E+09 | 0.189477E+10 | 0.861759E+09 | 0.103302E+10 | 0.00 | 0.00 |
July | 0.292964E+10 | 0.292574E+09 | 0.189913E+10 | 0.780595E+09 | 0.111853E+10 | 0.00 | 0.00 |
August | 0.318389E+10 | 0.338835E+09 | 0.213900E+10 | 0.932245E+09 | 0.120676E+10 | 0.00 | 0.00 |
September | 0.311712E+10 | 0.550642E+09 | 0.222147E+10 | 0.122379E+10 | 0.997683E+09 | 0.00 | 0.00 |
October | 0.332511E+10 | 0.919884E+09 | 0.261305E+10 | 0.181751E+10 | 0.795542E+09 | 0.00 | 0.00 |
November | 0.291626E+10 | 0.121074E+10 | 0.250094E+10 | 0.178530E+10 | 0.715638E+09 | 0.00 | 0.00 |
December | 0.288150E+10 | 0.161788E+10 | 0.257916E+10 | 0.199371E+10 | 0.585450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.346909E+11 | 0.106305E+11 | 0.272095E+11 | 0.160631E+11 | 0.111464E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254365E+10 | 0.292574E+09 | 0.189477E+10 | 0.780595E+09 | 0.585450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.332511E+10 | 0.161788E+10 | 0.261305E+10 | 0.199371E+10 | 0.120676E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.139340E+11 | -0.131433E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -790699023.5 | 58.99 | 0.00 | 0.00 |
February | 0.126704E+11 | -0.119629E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -707473678.6 | 58.99 | 0.00 | 0.00 |
March | 0.136969E+11 | -0.129445E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -752354125.7 | 58.99 | 0.00 | 0.00 |
April | 0.125165E+11 | -0.118317E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -684849727.4 | 58.99 | 0.00 | 0.00 |
May | 0.120572E+11 | -0.113785E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -678655997.9 | 58.99 | 0.00 | 0.00 |
June | 0.108740E+11 | -0.102352E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -638789916.7 | 58.99 | 0.00 | 0.00 |
July | 0.106670E+11 | -0.100137E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -653325022.1 | 58.98 | 0.00 | 0.00 |
August | 0.105856E+11 | -0.993106E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -654506147.8 | 58.98 | 0.00 | 0.00 |
September | 0.105545E+11 | -0.991451E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -639956149.3 | 58.98 | 0.00 | 0.00 |
October | 0.116502E+11 | -0.109464E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -703869630.1 | 58.99 | 0.00 | 0.00 |
November | 0.121830E+11 | -0.114393E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -743701614.2 | 58.98 | 0.00 | 0.00 |
December | 0.133973E+11 | -0.126003E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -796999257.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.144787E+12 | -0.136341E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.844518E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.105545E+11 | -0.131433E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -796999257.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.139340E+11 | -0.991451E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -638789916.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.26 | 0.24 | 01-JAN-07:49 | 4539.83 | 28.99 | 172.50 | 283.00 | 5035.35 | 31.05 | 202.17 | 284.50 |
February | 282.00 | 0.26 | 0.24 | 01-FEB-07:30 | 1894.28 | 23.23 | 112.00 | 273.83 | 2350.29 | 25.04 | 125.00 | 277.50 |
March | 351.33 | 0.26 | 0.24 | 01-MAR-06:00 | 1676.69 | 20.31 | 73.00 | 335.50 | 1600.47 | 18.16 | 25.17 | 334.00 |
April | 381.83 | 0.26 | 0.24 | 01-APR-06:10 | 2273.30 | 18.43 | 5.33 | 367.33 | 2015.13 | 18.34 | 4.67 | 369.33 |
May | 378.00 | 0.27 | 0.24 | 01-MAY-05:00 | 1317.63 | 17.85 | 0.00 | 384.67 | 1502.02 | 17.80 | 0.00 | 380.83 |
June | 412.83 | 0.25 | 0.24 | 01-JUN-05:40 | 1295.61 | 17.04 | 0.00 | 393.00 | 1376.87 | 16.98 | 0.00 | 397.83 |
July | 395.33 | 0.26 | 0.24 | 01-JUL-06:19 | 1295.17 | 17.75 | 2.50 | 388.17 | 1426.60 | 17.67 | 1.67 | 389.17 |
August | 408.83 | 0.26 | 0.24 | 01-AUG-05:49 | 1460.13 | 18.25 | 4.17 | 387.17 | 2092.54 | 18.21 | 7.33 | 383.00 |
September | 359.33 | 0.25 | 0.24 | 01-SEP-06:10 | 1631.28 | 18.37 | 24.83 | 340.00 | 1691.06 | 18.36 | 28.67 | 341.17 |
October | 329.00 | 0.27 | 0.24 | 01-OCT-06:40 | 1863.63 | 21.01 | 73.33 | 319.67 | 1748.35 | 20.51 | 69.83 | 319.50 |
November | 284.17 | 0.26 | 0.24 | 01-NOV-06:49 | 3610.59 | 27.05 | 141.00 | 281.33 | 2794.26 | 24.54 | 98.17 | 283.83 |
December | 265.67 | 0.28 | 0.24 | 01-DEC-07:49 | 8442.54 | 33.37 | 192.83 | 261.00 | 8397.88 | 33.71 | 194.33 | 260.50 |
Annual Sum or Average | 4149.83 | 0.26 | 2402.55 | 21.15 | 801.50 | 4014.67 | 2476.31 | 21.02 | 757.00 | 4021.17 | ||
Minimum of Months | 265.67 | 0.25 | 0.24 | 1295.17 | 17.04 | 0.00 | 261.00 | 1376.87 | 16.98 | 0.00 | 260.50 | |
Maximum of Months | 412.83 | 0.28 | 0.24 | 8442.54 | 33.37 | 192.83 | 393.00 | 8397.88 | 33.71 | 202.17 | 397.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208178E+11 | 58678.41 | 20-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155658E+11 | 58678.41 | 01-FEB-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.855779E+10 | 25885.20 | 05-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.296974E+10 | 14783.06 | 08-APR-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.832103E+09 | 9647.94 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 53516865.20 | 4335.82 | 09-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7507665.00 | 2017.38 | 09-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349367E+10 | 19547.53 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100384E+11 | 21119.16 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214028E+11 | 58678.41 | 05-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.837391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214028E+11 | 58678.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137502E+11 | 33690.81 | 21-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965232E+10 | 32511.04 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.363194E+10 | 20399.51 | 30-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.719565E+09 | 12326.28 | 08-APR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75813046.07 | 4031.70 | 06-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 296138.20 | 2521.76 | 09-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120287E+10 | 22807.83 | 25-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.440443E+10 | 25675.70 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139053E+11 | 33578.20 | 23-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139053E+11 | 33690.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 64760477.52 | 64760477.52 | 4036.51 | 14-FEB-15:53 | 4036.51 | 0.00 |
March | 0.00 | 0.00 | 0.111773E+09 | 0.111773E+09 | 6175.21 | 08-MAR-14:00 | 6175.21 | 0.00 |
April | 0.00 | 0.00 | 0.252049E+10 | 0.252038E+10 | 11923.69 | 13-APR-17:04 | 11923.69 | 0.00 |
May | 0.00 | 0.00 | 0.683493E+10 | 0.673965E+10 | 17086.78 | 19-MAY-17:05 | 17086.78 | 0.00 |
June | 0.00 | 0.00 | 0.169355E+11 | 0.163872E+11 | 40537.55 | 29-JUN-03:01 | 34958.03 | 0.00 |
July | 0.00 | 0.00 | 0.242395E+11 | 0.209155E+11 | 40537.55 | 20-JUL-03:01 | 35543.69 | 0.00 |
August | 0.00 | 0.00 | 0.209362E+11 | 0.181249E+11 | 40537.55 | 22-AUG-03:41 | 29835.86 | 0.00 |
September | 0.00 | 0.00 | 0.120049E+11 | 0.108199E+11 | 20245.52 | 15-SEP-03:01 | 17593.79 | 0.00 |
October | 0.00 | 0.00 | 0.375412E+10 | 0.347967E+10 | 17425.79 | 01-OCT-04:01 | 13301.76 | 0.00 |
November | 0.00 | 0.00 | 301.06 | 285.05 | 5.02 | 01-NOV-04:01 | 4.75 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.874022E+11 | 0.791638E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.242395E+11 | 0.209155E+11 | 40537.55 | 35543.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 79808255.50 | 79765122.85 | 4342.80 | 14-FEB-15:10 | 4342.80 | 0.00 |
March | 0.00 | 0.00 | 0.236477E+09 | 0.235250E+09 | 6815.18 | 21-MAR-04:01 | 4977.03 | 0.00 |
April | 0.00 | 0.00 | 0.337858E+10 | 0.336854E+10 | 29393.61 | 14-APR-03:21 | 27991.77 | 0.00 |
May | 0.00 | 0.00 | 0.866625E+10 | 0.834428E+10 | 29393.61 | 09-MAY-03:21 | 29393.61 | 0.00 |
June | 0.00 | 0.00 | 0.198091E+11 | 0.189849E+11 | 29393.61 | 04-JUN-03:11 | 19676.53 | 0.00 |
July | 0.00 | 0.00 | 0.281531E+11 | 0.244920E+11 | 29673.87 | 04-JUL-00:42 | 19238.01 | 0.00 |
August | 0.00 | 0.00 | 0.241105E+11 | 0.206736E+11 | 29393.61 | 05-AUG-02:11 | 19864.38 | 0.00 |
September | 0.00 | 0.00 | 0.146468E+11 | 0.126097E+11 | 29393.61 | 24-SEP-04:01 | 14248.63 | 0.00 |
October | 0.00 | 0.00 | 0.487114E+10 | 0.435292E+10 | 29393.61 | 10-OCT-03:21 | 17595.09 | 0.00 |
November | 0.00 | 0.00 | 34143162.30 | 29147415.62 | 10429.10 | 09-NOV-05:01 | 7610.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103986E+12 | 0.931700E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.281531E+11 | 0.244920E+11 | 29673.87 | 29393.61 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 5198.84 | 19381.88 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5236.53 | 19396.50 | 06-FEB-13:50 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 5126.57 | 19213.93 | 01-MAR-13:35 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4855.66 | 18423.12 | 01-APR-12:35 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4540.68 | 17264.83 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4242.07 | 15986.49 | 01-JUN-12:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4029.21 | 15003.04 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4001.69 | 14687.79 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4116.34 | 15443.73 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4378.60 | 16633.43 | 31-OCT-12:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4705.38 | 17873.52 | 30-NOV-13:48 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4995.10 | 18899.38 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 4615.34 | ||||
Minimum of Months | 0.00 | 0.00 | 4001.69 | 14687.79 | ||
Maximum of Months | 0.00 | 0.00 | 5236.53 | 19396.50 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112411E+10 | 0.27 | 503.64 | 01-JAN-00:02 | 0.32 |
February | 0.101533E+10 | 0.27 | 503.64 | 01-FEB-00:01 | 0.32 |
March | 0.112910E+10 | 0.27 | 503.64 | 01-MAR-00:02 | 0.32 |
April | 0.112668E+10 | 0.28 | 503.64 | 01-APR-04:01 | 0.32 |
May | 0.121442E+10 | 0.29 | 503.64 | 01-MAY-02:62 | 0.32 |
June | 0.122228E+10 | 0.30 | 503.64 | 01-JUN-00:55 | 0.32 |
July | 0.128659E+10 | 0.30 | 503.64 | 01-JUL-00:13 | 0.32 |
August | 0.128551E+10 | 0.30 | 503.64 | 01-AUG-00:14 | 0.32 |
September | 0.122389E+10 | 0.30 | 503.64 | 01-SEP-00:14 | 0.32 |
October | 0.119271E+10 | 0.28 | 503.64 | 01-OCT-00:45 | 0.32 |
November | 0.109491E+10 | 0.27 | 503.64 | 01-NOV-02:65 | 0.32 |
December | 0.112411E+10 | 0.27 | 503.64 | 01-DEC-00:03 | 0.32 |
Annual Sum or Average | 0.140396E+11 | 0.28 | |||
Minimum of Months | 0.101533E+10 | 0.27 | 503.64 | 0.32 | |
Maximum of Months | 0.128659E+10 | 0.30 | 503.64 | 0.32 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.295406E+10 | 0.62 | 2656.14 | 20-JAN-04:03 | 1.07 |
February | 0.257636E+10 | 0.61 | 2656.14 | 01-FEB-04:05 | 1.07 |
March | 0.260418E+10 | 0.57 | 1765.49 | 05-MAR-05:01 | 0.88 |
April | 0.237556E+10 | 0.55 | 1463.96 | 08-APR-04:06 | 0.79 |
May | 0.239400E+10 | 0.54 | 1324.49 | 06-MAY-06:03 | 0.75 |
June | 0.231637E+10 | 0.54 | 1689.50 | 28-JUN-17:02 | 0.86 |
July | 0.241482E+10 | 0.55 | 1744.09 | 21-JUL-17:08 | 0.87 |
August | 0.238940E+10 | 0.55 | 1373.43 | 17-AUG-11:55 | 0.75 |
September | 0.229759E+10 | 0.54 | 1117.25 | 09-SEP-06:10 | 0.66 |
October | 0.246699E+10 | 0.55 | 1593.36 | 26-OCT-04:01 | 0.83 |
November | 0.256755E+10 | 0.58 | 1636.05 | 27-NOV-05:01 | 0.84 |
December | 0.296573E+10 | 0.62 | 2656.14 | 05-DEC-04:03 | 1.07 |
Annual Sum or Average | 0.303226E+11 | 0.57 | |||
Minimum of Months | 0.229759E+10 | 0.54 | 1117.25 | 0.66 | |
Maximum of Months | 0.296573E+10 | 0.62 | 2656.14 | 1.07 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156238E+10 | 0.61 | 1121.10 | 21-JAN-05:03 | 0.96 |
February | 0.136886E+10 | 0.60 | 1103.05 | 04-FEB-05:03 | 0.95 |
March | 0.140817E+10 | 0.58 | 917.79 | 30-MAR-04:04 | 0.86 |
April | 0.132657E+10 | 0.58 | 1503.72 | 28-APR-04:01 | 1.10 |
May | 0.137234E+10 | 0.60 | 1514.40 | 09-MAY-04:01 | 1.11 |
June | 0.151651E+10 | 0.65 | 1514.40 | 02-JUN-04:01 | 1.10 |
July | 0.168623E+10 | 0.68 | 1514.40 | 02-JUL-04:01 | 1.10 |
August | 0.156450E+10 | 0.65 | 1514.40 | 11-AUG-03:11 | 1.10 |
September | 0.136271E+10 | 0.62 | 1514.40 | 05-SEP-03:11 | 1.10 |
October | 0.138553E+10 | 0.59 | 1514.40 | 01-OCT-04:01 | 1.10 |
November | 0.137674E+10 | 0.58 | 998.50 | 27-NOV-05:03 | 0.91 |
December | 0.156475E+10 | 0.61 | 1119.38 | 23-DEC-05:03 | 0.96 |
Annual Sum or Average | 0.174953E+11 | 0.61 | |||
Minimum of Months | 0.132657E+10 | 0.58 | 917.79 | 0.86 | |
Maximum of Months | 0.168623E+10 | 0.68 | 1514.40 | 1.11 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 50.42 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.76 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.57 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.96 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.22 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.62 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 53.14 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.99 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.96 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.85 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.42 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.48 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 50.42 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.99 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 38.82 | 38.82 | 5198.84 | 19381.88 | 31-JAN-13:50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.78 | 51.78 | 5236.53 | 19396.50 | 06-FEB-13:50 |
March | 0.00 | 0.00 | 01-MAR-00:02 | 52.05 | 52.05 | 5126.57 | 19213.93 | 01-MAR-13:35 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.86 | 51.86 | 4855.66 | 18423.12 | 01-APR-12:35 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 40.51 | 40.51 | 4540.68 | 17264.83 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.80 | 52.80 | 4242.07 | 15986.49 | 01-JUN-12:45 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.58 | 53.58 | 4029.21 | 15003.04 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.98 | 53.98 | 4001.69 | 14687.79 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.91 | 53.91 | 4116.34 | 15443.73 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.54 | 42.54 | 4378.60 | 16633.43 | 31-OCT-12:15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.66 | 52.66 | 4705.38 | 17873.52 | 30-NOV-13:48 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.22 | 52.22 | 4995.10 | 18899.38 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 4615.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 38.82 | 38.82 | 4001.69 | 14687.79 | ||
Maximum of Months | 0.00 | 0.00 | 53.98 | 53.98 | 5236.53 | 19396.50 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.295406E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.259606E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.263809E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.310297E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.430571E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.694470E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.890695E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.795592E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.555105E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.350939E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.256755E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.296573E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.539982E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.256755E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.890695E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156238E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139236E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.147814E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226053E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.365193E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664791E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.882414E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.762181E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.508847E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.267126E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138674E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156475E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.441504E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.138674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.882414E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.295406E+10 | 0.00 | 0.208178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257636E+10 | 64760477.52 | 0.155658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260418E+10 | 0.111773E+09 | 0.855779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237556E+10 | 0.252049E+10 | 0.296974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239400E+10 | 0.683493E+10 | 0.832103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231637E+10 | 0.169304E+11 | 53516865.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241482E+10 | 0.242342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238940E+10 | 0.209277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229759E+10 | 0.120049E+11 | 7507665.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246699E+10 | 0.375412E+10 | 0.349367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256755E+10 | 301.06 | 0.100384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296573E+10 | 0.00 | 0.214028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303226E+11 | 0.873833E+11 | 0.837391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.296573E+10 | 0.242342E+11 | 0.214028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156238E+10 | 0.00 | 0.137502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136886E+10 | 79808255.50 | 0.965232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140817E+10 | 0.236477E+09 | 0.363194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132657E+10 | 0.337708E+10 | 0.719565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137234E+10 | 0.865804E+10 | 75813046.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151651E+10 | 0.197619E+11 | 296138.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168623E+10 | 0.280563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156450E+10 | 0.240182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136271E+10 | 0.146262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138553E+10 | 0.486864E+10 | 0.120287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137674E+10 | 34143162.30 | 0.440443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156475E+10 | 0.00 | 0.139053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174953E+11 | 0.103717E+12 | 0.473427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168623E+10 | 0.280563E+11 | 0.139053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.295406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257636E+10 | 0.00 | 0.00 | 0.00 | 19700377.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260418E+10 | 0.00 | 0.00 | 0.00 | 33908655.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237556E+10 | 0.00 | 0.00 | 0.00 | 0.727406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239400E+10 | 0.00 | 0.00 | 0.00 | 0.191171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231637E+10 | 0.00 | 0.00 | 0.00 | 0.462833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.241482E+10 | 0.00 | 0.00 | 0.00 | 0.649213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.238940E+10 | 0.00 | 0.00 | 0.00 | 0.556652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229759E+10 | 0.00 | 0.00 | 0.00 | 0.325346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246699E+10 | 0.00 | 0.00 | 0.00 | 0.104240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256755E+10 | 0.00 | 0.00 | 0.00 | 95.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.303226E+11 | 0.00 | 0.00 | 0.00 | 0.236756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.229759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.296573E+10 | 0.00 | 0.00 | 0.00 | 0.649213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.156238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136886E+10 | 0.00 | 0.00 | 0.00 | 23506336.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140817E+10 | 0.00 | 0.00 | 0.00 | 69968140.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132657E+10 | 0.00 | 0.00 | 0.00 | 0.933962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137234E+10 | 0.00 | 0.00 | 0.00 | 0.227959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151651E+10 | 0.00 | 0.00 | 0.00 | 0.513140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168623E+10 | 0.00 | 0.00 | 0.00 | 0.713791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156450E+10 | 0.00 | 0.00 | 0.00 | 0.605732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136271E+10 | 0.00 | 0.00 | 0.00 | 0.372576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138553E+10 | 0.00 | 0.00 | 0.00 | 0.128573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137674E+10 | 0.00 | 0.00 | 0.00 | 9997764.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174953E+11 | 0.00 | 0.00 | 0.00 | 0.266551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168623E+10 | 0.00 | 0.00 | 0.00 | 0.713791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.377739E+10 | 0.00 | 0.00 | 82785.57 | 0.00 | 0.155412E+11 | 92233067.61 | 0.00 | 3.53 |
February | 0.362950E+10 | 0.00 | 0.00 | 1168678.65 | 0.00 | 0.120380E+11 | 0.402577E+09 | 0.00 | 3.66 |
March | 0.536855E+10 | 0.00 | 0.00 | 3916926.50 | 0.00 | 0.679011E+10 | 0.151799E+10 | 0.00 | 3.91 |
April | 0.494867E+10 | 0.00 | 0.00 | 18837072.42 | 0.00 | 0.211958E+10 | 0.353205E+10 | 0.00 | 4.89 |
May | 0.358246E+10 | 66865627.65 | 0.00 | 30929319.26 | 0.00 | 0.525876E+09 | 0.384154E+10 | 0.00 | 5.08 |
June | 0.136887E+10 | 0.147154E+10 | 0.00 | 25429525.89 | 434689.17 | 10226808.96 | 0.286858E+10 | 0.00 | 4.89 |
July | 0.238837E+09 | 0.277434E+10 | 0.00 | 15532646.55 | 6207396.42 | 0.00 | 0.225328E+10 | 0.00 | 5.12 |
August | 0.427141E+09 | 0.175676E+10 | 0.00 | 23500712.55 | 1979839.32 | 0.00 | 0.316311E+10 | 0.00 | 5.40 |
September | 0.150835E+10 | 0.356023E+09 | 0.00 | 40433725.20 | 0.00 | 0.00 | 0.484535E+10 | 0.00 | 5.60 |
October | 0.484567E+10 | 26419664.02 | 0.00 | 22884330.78 | 0.00 | 0.251355E+10 | 0.415560E+10 | 0.00 | 4.94 |
November | 0.628554E+10 | 0.00 | 0.00 | 448670.03 | 0.00 | 0.779845E+10 | 0.300164E+09 | 0.00 | 3.53 |
December | 0.336244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163921E+11 | 0.00 | 0.00 | 3.53 |
Annual Sum or Average | 0.393434E+11 | 0.645194E+10 | 0.00 | 0.183164E+09 | 8621924.92 | 0.637292E+11 | 0.269725E+11 | 0.00 | 4.51 |
Minimum of Months | 0.238837E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 |
Maximum of Months | 0.628554E+10 | 0.277434E+10 | 0.00 | 40433725.20 | 6207396.42 | 0.163921E+11 | 0.484535E+10 | 0.00 | 5.60 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444237E+11 | 0.00 | 0.00 | 332176.49 | 0.00 | 26826066.86 | 0.100957E+10 | 0.00 | 8.02 |
February | 0.363147E+11 | 0.00 | 0.00 | 2088199.25 | 0.00 | 15905502.71 | 0.180577E+10 | 0.00 | 7.96 |
March | 0.291007E+11 | 0.00 | 0.00 | 10145154.49 | 0.00 | 3934598.46 | 0.652366E+10 | 0.00 | 7.81 |
April | 0.163384E+11 | 0.00 | 0.00 | 35968379.09 | 0.00 | 0.00 | 0.128573E+11 | 0.00 | 7.82 |
May | 0.842143E+10 | 0.00 | 0.00 | 66644604.15 | 0.00 | 0.00 | 0.163862E+11 | 0.00 | 7.90 |
June | 0.228642E+10 | 0.108637E+10 | 0.00 | 86374401.09 | 0.00 | 0.00 | 0.124368E+11 | 0.00 | 8.37 |
July | 0.528314E+09 | 0.159852E+10 | 0.00 | 96221731.78 | 11807.34 | 0.00 | 0.765783E+10 | 0.00 | 8.73 |
August | 0.680582E+09 | 0.522591E+09 | 0.00 | 0.104216E+09 | 0.00 | 0.00 | 0.107988E+11 | 0.00 | 8.50 |
September | 0.227748E+10 | 1926861.40 | 0.00 | 92045002.40 | 0.00 | 0.00 | 0.163940E+11 | 0.00 | 8.07 |
October | 0.152678E+11 | 4084739.19 | 0.00 | 45468749.85 | 0.00 | 2268744.99 | 0.148612E+11 | 0.00 | 7.88 |
November | 0.327890E+11 | 0.00 | 0.00 | 2521946.89 | 0.00 | 6504326.03 | 0.369117E+10 | 0.00 | 7.77 |
December | 0.458035E+11 | 0.00 | 0.00 | 36165.28 | 0.00 | 26196344.83 | 0.116511E+09 | 0.00 | 8.01 |
Annual Sum or Average | 0.234232E+12 | 0.321350E+10 | 0.00 | 0.542063E+09 | 11807.34 | 81635583.88 | 0.104539E+12 | 0.00 | 8.07 |
Minimum of Months | 0.528314E+09 | 0.00 | 0.00 | 36165.28 | 0.00 | 0.00 | 0.116511E+09 | 0.00 | 7.77 |
Maximum of Months | 0.458035E+11 | 0.159852E+10 | 0.00 | 0.104216E+09 | 11807.34 | 26826066.86 | 0.163940E+11 | 0.00 | 8.73 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.307428E+11 | 0.190880E+11 | 0.937787E+11 | 0.00 | 0.245222E+11 |
February | 0.391566E+11 | 0.159155E+11 | 0.793097E+11 | 0.157743E+09 | 0.219391E+11 |
March | 0.527416E+11 | 0.136692E+11 | 0.752103E+11 | 0.547269E+09 | 0.228810E+11 |
April | 0.678708E+11 | 0.957041E+10 | 0.627863E+11 | 0.166337E+10 | 0.294949E+11 |
May | 0.728140E+11 | 0.694693E+10 | 0.547135E+11 | 0.168059E+10 | 0.434672E+11 |
June | 0.695791E+11 | 0.203208E+10 | 0.314918E+11 | 0.125511E+10 | 0.711867E+11 |
July | 0.711069E+11 | -738140996.2 | 0.155222E+11 | 0.115021E+10 | 0.918642E+11 |
August | 0.692742E+11 | 0.928829E+09 | 0.245019E+11 | 0.154057E+10 | 0.817488E+11 |
September | 0.555632E+11 | 0.413092E+10 | 0.424346E+11 | 0.217806E+10 | 0.570958E+11 |
October | 0.437614E+11 | 0.983932E+10 | 0.662353E+11 | 0.192623E+10 | 0.325923E+11 |
November | 0.334870E+11 | 0.147113E+11 | 0.776668E+11 | 25618134.00 | 0.190393E+11 |
December | 0.282888E+11 | 0.197088E+11 | 0.951204E+11 | 0.00 | 0.235420E+11 |
Annual Sum or Average | 0.634386E+12 | 0.115803E+12 | 0.718771E+12 | 0.121248E+11 | 0.519374E+12 |
Minimum of Months | 0.282888E+11 | -738140996.2 | 0.155222E+11 | 0.00 | 0.190393E+11 |
Maximum of Months | 0.728140E+11 | 0.197088E+11 | 0.951204E+11 | 0.217806E+10 | 0.918642E+11 |