Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:28:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1298.54 | 5588.87 | 5588.87 |
Net Site Energy | 1298.54 | 5588.87 | 5588.87 |
Total Source Energy | 2672.67 | 11503.12 | 11503.12 |
Net Source Energy | 2672.67 | 11503.12 | 11503.12 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 21.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 131.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 192.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 66.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 607.32 | 691.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 21.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 131.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 192.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 17.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 31.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 21.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 36.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 131.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 192.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 66.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 413.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 723.62 | 921.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1476.61 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2613.91 | 2974.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 413.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 723.62 | 921.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1476.61 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2613.91 | 2974.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 607.325 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 607.325 | 100.00 |
Total On-Site and Utility Electric Sources | 607.325 | 100.00 |
Total Electricity End Uses | 607.325 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 2.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3404.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 13.7183 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 12.2230 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 12.9706 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 12.9706 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 13.7183 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 12.2230 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 12.9706 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 12.9706 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 12.9706 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:20 | 29-MAR-10:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 10741.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15889.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14428.03 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4852.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21433.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 4540.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42422.86 | 58835.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 10741.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15889.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13060.45 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4852.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 21433.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1024.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 115.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 417.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 208.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 209.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1923.40 | 749.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 102.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 495.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1795.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 896.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 902.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8278.27 | 3224.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 102.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 495.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1795.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 896.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 902.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8278.27 | 3224.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.97 |
KITCHEN DIRECT AIR | 1.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.97 | 1.97 | 1.97 | 1.97 | 1.97 | 1.97 | 1.00 | 1.00 | 1.97 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.000000 | 1.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.97 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.30 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.97 | 2160.36 |
PSZ-AC_2:2_ADDAQ FAN | 1.30 | 1479.88 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.97 | 1.97 | 1.97 | 1.97 | 36413.53 | 52830.75 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 1.30 | 28075.77 | 56506.30 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.97 | 0.986913 | 1.97 | 36413.53 | 17391.64 | 36413.53 | 0.800900 | 0.800900 |
PSZ-AC_2:2 COOLING COIL | 1.30 | 0.649006 | 1.30 | 28075.77 | 13547.54 | 28075.77 | 0.746370 | 0.746370 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 52830.75 |
PSZ-AC_2:2 HEATING COIL | 56506.30 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 13.718 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 130.505 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 12.223 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1086.229 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1593.672 | 13.718 | 18.204 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1593.672 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1419.966 | 12.223 | 226.351 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1419.966 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 1.138 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6450 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.29115192E-12 | 0.14094868E-14 | -0.90631100E-13 | 0.19562047E-15 |
34 | 6 | 0.24341206E-07 | 0.30358918E-09 | 0.56122138E-08 | -0.11211253E-12 |
35 | 5 | -0.16785956E-03 | 0.26776669E-05 | -0.86595242E-04 | 0.55591463E-08 |
36 | 4 | 0.26572591 | 0.13383140E-02 | 0.90200365E-01 | -0.29883432E-04 |
37 | 3 | -6.7421581 | 0.42444411E-01 | -2.1834393 | 0.26442886E-01 |
38 | 2 | 39.141362 | 0.15401520 | 14.625099 | -0.31408072 |
39 | 1 | -79.219124 | 0.70737621E-01 | -28.567247 | 1.0503496 |
40 | 0 | 46.824348 | 0.14478936E-02 | 16.305459 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.6141_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 3.491 | 3.491 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.15729 | 0.58895 | 0.58895 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.70317E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 9.529E-002 | 8.202E-004 | 1.025E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 9.529E-002 | 8.202E-004 | 1.004E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 21992.88260 | 26391.45912 | 1.64485 | 1.97383 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.23349E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 4035.32694 | 4842.39232 | 0.17351 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 3.80000 | 5.05843E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 17348.24251 | 20817.89101 | 1.08168 | 1.29801 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.23222E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 3.80000 | 5.05843E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29646.80 | 1.97383 | 1.97383 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 17885.52 | 0.41606 | 0.41606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26455.37 | 1.29801 | 1.29801 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 49063.92 | 1.14133 | 1.14133 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.97383 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29801 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.97383 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.97383 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.97383 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97383 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97383 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97383 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29801 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29801 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29801 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29801 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29801 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29801 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.97383 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.29801 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97383 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97383 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2160.36287 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97383 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97383 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97383 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.97383 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97383 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98691 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.97383 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36413.53000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17391.64422 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36413.53000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80090 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80090 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36413.53000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52830.74543 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 52830.74543 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29801 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29801 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1479.87699 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29801 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29801 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29801 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.29801 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29801 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64901 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.29801 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28075.77000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 13547.54484 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28075.77000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74637 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74637 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28075.77000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56506.30315 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 56506.30315 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 34978.9 | 10.25 | 10.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27142.7 | 10.48 | 10.35 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | N/A | 3.491 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | N/A | 3.491 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.138 | 0.972 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 4.1136186107E-002 | 0.1449202033 | Pass | Pass | 0.2639512757 | 1.2347449495 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2433895007 | 0.6977063518 | Pass | Pass | 5.0982586779E-002 | 0.1972082952 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3084709630 | 0.3451752020 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 678.13 | 114.56 | 717.87 | 39.66 | 489.66 | 2039.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.972 | 1.138 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.6141_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.6141_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 3.491 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 3.491 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.491 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 13.7183 | 116.17 | 1593.67 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.00 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 12.2230 | 116.17 | 1419.97 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.84 |
Interior Lighting Total | 12.9706 | 232.34 | 3013.64 | 54.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.75 | 83.75 | 41.28 | |
Exterior Lighting Total | 2625.88 | 41.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36413.53 | 29163.60 | 7249.93 | 0.80 | 3.50 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28075.77 | 20954.91 | 7120.86 | 0.75 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 34978.9 | 10.25 | 10.13 | ||||
PSZ-AC_2:2 COOLING COIL | 27142.7 | 10.48 | 10.35 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 52830.75 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 56506.30 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.97 | 2160.36 | 1094.51 | 1.00 | 1.29 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.55 | 622.50 | 1.30 | 1479.88 | 1140.11 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 21992.88 | 26391.46 | 227.18 | 1.645 | 1.974 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 23.89 | 23.89 | 0.00911 | 31.30 | 0.00823 | 0.416 | 0.00 |
KITCHEN | 17348.24 | 20817.89 | 179.20 | 1.082 | 1.298 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 26.11 | 26.09 | 0.01005 | 30.50 | 0.00823 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 4035.33 | 4842.39 | 41.68 | 0.174 | 0.416 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00759 | 3.80 | 0.00506 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 25.54 | 0.00464 | 3.80 | 0.00506 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.97 | 1.97 | 0.42 | 0.42 | 1.9738 | 1.9738 | 1.9738 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.14 | 1.14 | 1.2980 | 1.2980 | 1.2980 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 36413.530 | 29163.596 | 1.973830 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 36413.53 | 33856.89 | 1.973830 | 25.45 | 17.06 | 0.00892746 | 11.89 | 11.56 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 21.0786 | 23.89 | 0.00911280 | 48.4268 | 21992.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 52830.745 | 52830.745 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 52830.75 | 52830.75 | 1.973826 | 17.46 | 12.44 | 0.00709310 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.0787 | 20.21 | 0.00763653 | 50.9097 | 2337.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28075.770 | 20954.912 | 1.298010 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28075.77 | 28075.77 | 1.298010 | 29.96 | 18.19 | 0.00845113 | 11.85 | 11.49 | 0.00845113 | 30.50 | 0.00823222 | 18.19 | 87.9295 | 26.09 | 0.01004582 | 46.7320 | 17348.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 56506.303 | 56506.303 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 56506.30 | 56506.30 | 1.298013 | 3.34 | 3.34 | 0.00500795 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 87.9293 | 25.54 | 0.00464024 | 22.5038 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36413.530 | 29163.596 | 1.973830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4357 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.973826 | 2.33262488 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 36413.53 | 33856.89 | 1.0000 | 2.33263018 | 1.973830 | 25.45 | 17.06 | 0.00892746 | 48320.7 | 11.89 | 11.56 | 0.00850000 | 33396.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36413.53 | 31.30 | 0.00823349 | 18.45 | 0.41605618 | 21.0786 | 23.89 | 0.00911280 | 23.89 | 0.00911280 | 48.4268 | 21992.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52830.745 | 52830.745 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.973826 | 2.33262488 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 52830.75 | 52830.75 | 1.0000 | 2.33262488 | 1.973826 | 17.46 | 12.44 | 0.00709310 | 35515.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52830.75 | 3.80 | 0.00505843 | 3.80 | 0.41605618 | 21.0787 | 21.11 | 0.00763653 | 20.21 | 0.00763653 | 50.9097 | 2337.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28075.770 | 20954.912 | 1.298010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5502 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.298013 | 1.53396359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 28075.77 | 28075.77 | 1.0000 | 1.53396052 | 1.298010 | 29.96 | 18.19 | 0.00845113 | 51714.5 | 11.85 | 11.49 | 0.00845113 | 33234.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28075.77 | 30.50 | 0.00823222 | 18.19 | 1.14133354 | 87.9295 | 26.06 | 0.01004582 | 26.09 | 0.01004582 | 46.7320 | 17348.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56506.303 | 56506.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.298013 | 1.53396359 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 56506.30 | 56506.30 | 1.0000 | 1.53396359 | 1.298013 | 3.34 | 3.34 | 0.00500795 | 15913.2 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56506.30 | 3.80 | 0.00505843 | 3.80 | 1.14133354 | 87.9293 | 0.00 | 0.00464024 | 25.54 | 0.00464024 | 22.5038 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.97 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3704.17 | 3511.83 | 719.50 |
KITCHEN | 5475.33 | 4769.83 | 3386.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5475.83 | 6151.83 | 3404.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.50 | 23.33 | 0.00 | 0.67 |
KITCHEN | 0.00 | 233.83 | 0.00 | 1.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.50 | 256.50 | 0.00 | 2.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 6.874 | 4.275 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.372 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.181 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.359 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 17421460.31 | 0.00 | 17421460.31 | 10727480.81 | 28148941.12 | 13120747.55 | 1445.72 | 4361.42 | 2952.86 | 268.45 |
KITCHEN | 31994743.71 | 0.00 | 31994743.71 | 140835.77 | 32135579.47 | 35993094.65 | 1438.60 | 4935.38 | 2386.01 | 779.13 |
Total Facility | 49416204.02 | 0.00 | 49416204.02 | 10868316.57 | 60284520.59 | 49113842.20 | 1458.13 | 5173.52 | 3209.40 | 828.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.6629 | 0.0000 | 0.6629 | 0.4127 | 1.0757 | 0.4161 | 0.00 | 4266.03 | 2920.97 |
KITCHEN | 1.1893 | 0.0000 | 1.1893 | 0.0036 | 1.1929 | 1.1413 | 0.00 | 4823.00 | 2364.00 |
Total Facility | 1.8522 | 0.0000 | 1.8522 | 0.4163 | 2.2685 | 1.5574 | 0.00 | 5060.33 | 3158.30 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 24330816.33 | 0.00 | 24330816.33 | 13120747.55 | 1444.96 | 0.00 | 7315.04 | 268.39 |
PSZ-AC_2:2 | 44683884.98 | 0.00 | 44683884.98 | 35993094.65 | 1416.28 | 2.10 | 7341.62 | 779.13 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.9259 | 0.0000 | 0.9259 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6610 | 0.0000 | 1.6610 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1446.77 | 1659.25 | 4349.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 2648.26 | 5317.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.9300 | 1.0294 | 0.5812 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7955 | 1.5941 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
Electricity:Building | 349.57 | 3129.39 | 01-JAN-01:10 | 20656.41 | 02-JAN-11:10 |
Electricity:Zone:DINING | 99.41 | 510.40 | 01-JAN-01:10 | 5368.82 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 331.71 | 2720.35 | 01-JAN-01:10 | 17140.31 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 29.00 | 239.05 | 01-JAN-01:10 | 1434.30 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 29.00 | 239.05 | 01-JAN-01:10 | 1434.30 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 250.16 | 2618.99 | 01-JAN-01:10 | 15287.58 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.84 | 212.99 | 01-JAN-01:10 | 1277.97 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.84 | 212.99 | 01-JAN-01:10 | 1277.97 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 66.20 | 1036.26 | 23-NOV-23:30 | 4592.33 | 27-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 48.34 | 780.61 | 23-NOV-23:30 | 2547.89 | 03-OCT-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 17.27 | 0.00 | 01-JAN-11:10 | 1471.66 | 03-OCT-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 31.07 | 713.57 | 07-JAN-01:10 | 1076.23 | 13-JAN-14:10 |
ElectricityPurchased:Facility | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
ElectricityPurchased:Plant | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
Cogeneration:ElectricityPurchased | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
General:Cogeneration:ElectricityPurchased | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
ElectricityNet:Plant | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
Cogeneration:ElectricityNet | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
General:Cogeneration:ElectricityNet | 607.32 | 6753.81 | 07-JAN-01:10 | 42422.86 | 16-OCT-10:20 |
Electricity:HVAC | 168.13 | 0.00 | 01-JAN-01:10 | 23070.93 | 16-OCT-11:10 |
Fans:Electricity | 131.74 | 0.00 | 01-JAN-01:10 | 4852.11 | 01-JAN-05:10 |
General:Fans:Electricity | 131.74 | 0.00 | 01-JAN-01:10 | 4852.11 | 01-JAN-05:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 36.38 | 0.00 | 01-JAN-00:10 | 18218.82 | 16-OCT-11:10 |
General:Cooling:Electricity | 36.38 | 0.00 | 01-JAN-00:10 | 18218.82 | 16-OCT-11:10 |
ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:00 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.28 | 0.00 | 01-JAN-07:00 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 11-FEB-16:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 691.21 | 2560.65 | 14-JAN-03:10 | 58835.18 | 29-MAR-10:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 21.89 | 0.00 | 01-JAN-00:10 | 36462.56 | 08-JAN-07:10 |
Heating:NaturalGas | 21.89 | 0.00 | 01-JAN-00:10 | 36462.56 | 08-JAN-07:10 |
General:Heating:NaturalGas | 21.89 | 0.00 | 01-JAN-00:10 | 36462.56 | 08-JAN-07:10 |
NaturalGas:Plant | 192.16 | 722.00 | 14-JAN-03:10 | 25685.14 | 29-JAN-13:20 |
WaterSystems:NaturalGas | 192.16 | 722.00 | 14-JAN-03:10 | 25685.14 | 29-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 192.16 | 722.00 | 14-JAN-03:10 | 25685.14 | 29-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 25-FEB-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 797.80 | 2819.38 | 07-JAN-01:10 | 112058.07 | 29-SEP-13:00 |
EnergyTransfer:Building | 451.08 | 1409.69 | 07-JAN-01:10 | 40315.80 | 16-OCT-11:10 |
EnergyTransfer:Zone:KITCHEN | 372.74 | 1409.69 | 07-JAN-01:10 | 23783.86 | 27-JAN-05:10 |
Refrigeration:EnergyTransfer | 157.00 | 2703.68 | 23-NOV-23:30 | 7834.84 | 28-APR-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.50 | 1351.84 | 23-NOV-23:30 | 3917.42 | 28-APR-03:50 |
General:Refrigeration:EnergyTransfer | 78.50 | 1351.84 | 23-NOV-23:30 | 3917.42 | 28-APR-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 78.50 | 1351.84 | 23-NOV-23:30 | 3917.42 | 28-APR-03:50 |
EnergyTransfer:Plant | 207.02 | 1351.84 | 23-NOV-23:30 | 19092.15 | 02-FEB-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.52 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.98 | 1150.71 | 07-JAN-01:10 | 2238.70 | 13-JAN-14:10 |
EnergyTransfer:Zone:DINING | 78.34 | 0.00 | 01-JAN-01:10 | 22350.66 | 16-OCT-11:10 |
Heating:EnergyTransfer | 2.82 | 0.00 | 01-JAN-00:10 | 8934.84 | 08-JAN-07:10 |
Heating:EnergyTransfer:Zone:DINING | 2.82 | 0.00 | 01-JAN-00:10 | 8934.84 | 08-JAN-07:10 |
General:Heating:EnergyTransfer | 2.82 | 0.00 | 01-JAN-00:10 | 8934.84 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 2.82 | 0.00 | 01-JAN-00:10 | 8934.84 | 08-JAN-07:10 |
Cooling:EnergyTransfer | 369.76 | 0.00 | 01-JAN-01:10 | 36433.36 | 16-OCT-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 75.52 | 0.00 | 01-JAN-01:10 | 22350.66 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer | 369.76 | 0.00 | 01-JAN-01:10 | 36433.36 | 16-OCT-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 75.52 | 0.00 | 01-JAN-01:10 | 22350.66 | 16-OCT-11:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 294.24 | 0.00 | 01-JAN-01:10 | 19980.57 | 27-JAN-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 294.24 | 0.00 | 01-JAN-01:10 | 19980.57 | 27-JAN-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
PlantLoopHeatingDemand:Plant | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
General:WaterSystems:PlantLoopHeatingDemand | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
EnergyTransfer:HVAC | 139.71 | 0.00 | 01-JAN-00:10 | 59101.47 | 16-OCT-11:10 |
HeatingCoils:EnergyTransfer | 17.51 | 0.00 | 01-JAN-00:10 | 29170.05 | 08-JAN-07:10 |
CoolingCoils:EnergyTransfer | 122.20 | 0.00 | 01-JAN-00:10 | 59101.47 | 16-OCT-11:10 |
WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
WaterUse:WaterSystems:EnergyTransfer | 128.52 | 0.00 | 01-JAN-00:10 | 16445.45 | 03-FEB-13:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 2.818 | -75.517 | 0.000 | 0.000 | 68.644 | 28.996 | 52.814 | 20.277 | 0.000 | 1.437 | 0.000 | 0.000 | -13.004 | 0.000 | -78.960 | -7.505 |
KITCHEN | 0.000 | 0.000 | 0.000 | -294.236 | 0.000 | 0.000 | 4.458 | 25.835 | 212.059 | 0.000 | 0.000 | 0.007 | 53.530 | 0.000 | 0.000 | 0.000 | -1.654 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.939 | 14.871 | 0.000 | 0.000 | 0.000 | -18.811 | -0.000 |
Total Facility | 0.000 | 0.000 | 2.818 | -369.752 | 0.000 | 0.000 | 73.102 | 54.831 | 264.873 | 20.277 | 0.000 | 5.384 | 68.401 | 0.000 | -13.004 | 0.000 | -99.424 | -7.505 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 15-OCT-03:21 | 0.00 | 0.00 | 0.00 | -38748.83 | 0.00 | 0.00 | 0.00 | 239.05 | 508.77 | 0.00 | 0.00 | 0.00 | 38733.78 | 0.00 | -732.78 | 0.00 | 0.00 | 0.00 |
KITCHEN | 20-DEC-03:01 | 0.00 | 0.00 | 0.00 | -53299.92 | 0.00 | 0.00 | 0.00 | 212.99 | 2018.53 | 0.00 | 0.00 | 0.00 | 51526.73 | 0.00 | -0.00 | 0.00 | -458.34 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-JUN-02:61 | 0.00 | 0.00 | 0.00 | -68250.48 | 0.00 | 0.00 | 0.00 | 452.05 | 2222.04 | 0.00 | 0.00 | 81.85 | 66166.98 | 0.00 | -672.44 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 17-OCT-02:03 | 0.00 | 0.00 | 18427.90 | 0.00 | 0.00 | 0.00 | 0.00 | 239.05 | 203.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -806.93 | 0.00 | -50.93 | -18012.60 |
KITCHEN | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-OCT-02:03 | 0.00 | 0.00 | 18427.90 | 0.00 | 0.00 | 0.00 | 0.00 | 452.05 | 2222.04 | 0.00 | 0.00 | 414.99 | 0.00 | 0.00 | -806.93 | 0.00 | -221.38 | -20488.66 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9738 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9738 | 0.2108 | 1.0000 | Not calculated | 0.4161 | 0.2108 | ||
PSZ-AC_2:2 | 1.2980 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2980 | 0.1165 | 1.0000 | Not calculated | 0.1513 | 0.1165 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9738 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9738 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2108 | ||
PSZ-AC_2:2 | 1.2980 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2980 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1165 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9738 | 1.9738 | 1.9738 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2980 | 1.2980 | 1.2980 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9738 | 1.9738 | 1.9738 | 1.9738 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2980 | 1.2980 | 1.2980 | 1.2980 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9738 | 1.9738 | 1.9738 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2980 | 1.2980 | 1.2980 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9738 | 1.9738 | 1.9738 | 1.9738 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2980 | 1.2980 | 1.2980 | 1.2980 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 2.50 |
Number of hours not met | 2.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 21.89 | 36462.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 36.38 | 18218.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.83 | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.28 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 131.74 | 4852.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 192.16 | 25685.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 17.27 | 1471.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 31.07 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 343.08 | 607.32 |
Natural Gas | 477.16 | 691.21 |
Additional | 0.00 | 0.00 |
Total | 820.24 | 1298.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 235.99 |
Space Heating | 0.00 |
Space Cooling | 156.60 |
Fans (All) | 567.02 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2613.91 |
Subtotal | 2613.91 |
Natural Gas [MJ/m2] | |
Space Heating | 94.21 |
Service Water Heating | 827.07 |
Miscellaneous (All) | 2974.96 |
Subtotal | 2974.96 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.22 |
Space Heating | 1.69 |
Space Cooling | 2.80 |
Fans (All) | 10.15 |
Service Water Heating | 14.80 |
Receptacle Equipment | 58.07 |
Miscellaneous | 8.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8039.00 | 717.83 | 3.17 | 0.00 | 0.00 |
ATTIC | 6000.50 | 792.67 | 730.00 | 1035.50 | 201.33 |
Min | 6000.50 | 0.17 | 0.00 | 0.00 | 0.00 |
Max | 8759.83 | 792.67 | 730.00 | 1035.50 | 201.33 |
Average | 7599.78 | 503.56 | 244.39 | 345.17 | 67.11 |
Sum | 22799.33 | 1510.67 | 733.17 | 1035.50 | 201.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16255.33 | 2.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 2.67 | 0.00 | 0.00 | 0.00 |
Average | 90326.78 | 0.89 | 0.00 | 0.00 | 0.00 |
Sum | 270980.33 | 2.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8010.67 | 749.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 5310.17 | 3449.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 6035.50 | 1270.17 | 410.50 | 410.33 | 633.50 |
Min | 5310.17 | 749.33 | 0.00 | 0.00 | 0.00 |
Max | 8010.67 | 3449.83 | 410.50 | 410.33 | 633.50 |
Average | 6452.11 | 1823.11 | 136.83 | 136.78 | 211.17 |
Sum | 19356.33 | 5469.33 | 410.50 | 410.33 | 633.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 232207.00 | 22518.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 9346.17 | 6911.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 232207.00 | 22518.00 | 0.00 | 0.00 | 0.00 |
Average | 80517.72 | 9809.94 | 0.00 | 0.00 | 0.00 |
Sum | 241553.17 | 29429.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429146E+10 | 11898.86 | 18-JAN-12:55 | 26.00 | 14.69 | 0.490728E+10 | 4681.74 | 14-JAN-19:40 | 26.00 | 14.69 |
February | 0.316101E+10 | 10172.43 | 01-FEB-12:05 | 25.67 | 14.54 | 0.435123E+10 | 4414.27 | 21-FEB-12:00 | 21.00 | 13.54 |
March | 0.342910E+10 | 7780.53 | 10-MAR-13:00 | 23.00 | 12.77 | 0.481100E+10 | 4414.14 | 23-MAR-11:50 | 22.00 | 16.49 |
April | 0.541151E+10 | 27546.73 | 27-APR-02:61 | 15.83 | 15.22 | 0.488709E+10 | 4681.79 | 01-APR-18:30 | 15.83 | 15.22 |
May | 0.530886E+10 | 30481.92 | 04-MAY-02:61 | 15.67 | 13.92 | 0.511933E+10 | 4681.78 | 27-MAY-18:10 | 16.50 | 12.42 |
June | 0.678905E+10 | 32549.96 | 23-JUN-02:61 | 15.17 | 12.72 | 0.517750E+10 | 4681.78 | 03-JUN-18:19 | 15.17 | 12.72 |
July | 0.958449E+10 | 30199.48 | 08-JUL-02:61 | 16.00 | 14.13 | 0.538842E+10 | 4681.82 | 22-JUL-18:10 | 21.67 | 18.43 |
August | 0.101056E+11 | 29973.63 | 22-AUG-02:61 | 16.00 | 14.04 | 0.545027E+10 | 4681.91 | 05-AUG-18:10 | 16.00 | 14.04 |
September | 0.829519E+10 | 32414.15 | 30-SEP-02:61 | 24.18 | 13.94 | 0.517425E+10 | 4681.82 | 30-SEP-18:49 | 21.33 | 17.57 |
October | 0.959055E+10 | 38753.49 | 15-OCT-03:21 | 17.50 | 8.27 | 0.531070E+10 | 4681.82 | 14-OCT-18:30 | 17.50 | 8.27 |
November | 0.483695E+10 | 10584.23 | 19-NOV-13:00 | 27.00 | 14.96 | 0.481022E+10 | 4676.41 | 18-NOV-19:10 | 27.00 | 14.96 |
December | 0.471324E+10 | 12374.31 | 19-DEC-13:00 | 26.00 | 11.60 | 0.489996E+10 | 4620.02 | 16-DEC-19:10 | 26.00 | 11.60 |
Annual Sum or Average | 0.755170E+11 | 0.602872E+11 | ||||||||
Minimum of Months | 0.316101E+10 | 7780.53 | 15.17 | 8.27 | 0.435123E+10 | 4414.14 | 15.17 | 8.27 | ||
Maximum of Months | 0.101056E+11 | 38753.49 | 27.00 | 15.22 | 0.545027E+10 | 4681.91 | 27.00 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245035E+11 | 49426.87 | 06-JAN-04:21 | 10.00 | 2.95 | 0.778363E+10 | 5138.46 | 19-JAN-11:00 | 23.00 | 15.75 |
February | 0.220321E+11 | 48868.90 | 04-FEB-03:01 | 10.50 | 3.38 | 0.702720E+10 | 5138.41 | 03-FEB-11:00 | 10.50 | 3.38 |
March | 0.246672E+11 | 44426.77 | 12-MAR-02:61 | 8.83 | 6.48 | 0.777540E+10 | 5138.41 | 22-MAR-10:39 | 21.00 | 16.08 |
April | 0.239448E+11 | 46096.67 | 02-APR-02:61 | 10.58 | 5.70 | 0.756429E+10 | 5138.45 | 28-APR-10:00 | 19.00 | 14.76 |
May | 0.249336E+11 | 42676.09 | 27-MAY-02:61 | 8.83 | 7.77 | 0.782583E+10 | 5138.45 | 19-MAY-10:39 | 8.83 | 7.77 |
June | 0.243850E+11 | 37681.65 | 13-JUN-03:41 | 11.17 | 10.03 | 0.759705E+10 | 5138.44 | 09-JUN-10:00 | 11.17 | 10.03 |
July | 0.258392E+11 | 36200.01 | 06-JUL-02:61 | 13.00 | 12.44 | 0.785560E+10 | 5138.45 | 28-JUL-10:00 | 24.00 | 19.89 |
August | 0.258194E+11 | 33336.57 | 22-AUG-02:61 | 16.00 | 14.04 | 0.786107E+10 | 5138.45 | 17-AUG-10:50 | 16.00 | 14.04 |
September | 0.245362E+11 | 38895.29 | 20-SEP-02:11 | 11.67 | 10.55 | 0.759626E+10 | 5151.11 | 29-SEP-10:00 | 36.00 | 17.91 |
October | 0.251724E+11 | 48327.83 | 27-OCT-03:31 | 10.00 | 4.07 | 0.784658E+10 | 5159.34 | 16-OCT-10:00 | 10.00 | 4.07 |
November | 0.239153E+11 | 52793.78 | 24-NOV-04:21 | 7.50 | 1.09 | 0.754992E+10 | 5138.45 | 09-NOV-11:00 | 7.50 | 1.09 |
December | 0.244931E+11 | 53325.32 | 20-DEC-03:01 | 7.17 | 0.46 | 0.778546E+10 | 5138.45 | 07-DEC-11:50 | 7.17 | 0.46 |
Annual Sum or Average | 0.294242E+12 | 0.920683E+11 | ||||||||
Minimum of Months | 0.220321E+11 | 33336.57 | 7.17 | 0.46 | 0.702720E+10 | 5138.41 | 7.17 | 0.46 | ||
Maximum of Months | 0.258392E+11 | 53325.32 | 16.00 | 14.04 | 0.786107E+10 | 5159.34 | 36.00 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 | 8.36 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 | 6.62 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.62 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 | 8.61 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 | 12.03 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 | 15.81 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 | 17.20 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 14.83 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.83 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 | 17.39 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 | 11.07 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.44 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.63 | 5.44 | 0.00 | 0.00 | 7.63 | 5.44 | ||
Maximum of Months | 0.00 | 0.00 | 18.42 | 17.39 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.775856E+09 | 8934.84 | 08-JAN-07:10 | 1.83 |
February | 0.418880E+09 | 4581.54 | 05-FEB-07:10 | 7.17 |
March | 0.873967E+09 | 7036.24 | 30-MAR-02:62 | 4.25 |
April | 50344768.08 | 5012.77 | 01-APR-06:05 | 7.67 |
May | 13670806.65 | 1855.45 | 14-MAY-06:02 | 11.17 |
June | 199498.74 | 3324.98 | 23-JUN-02:03 | 15.17 |
July | 1196959.35 | 8602.90 | 04-JUL-02:04 | 17.83 |
August | 1240909.46 | 6897.26 | 30-AUG-02:04 | 18.00 |
September | 6082256.24 | 13654.85 | 29-SEP-02:04 | 18.47 |
October | 13733026.37 | 18431.65 | 17-OCT-02:03 | 17.00 |
November | 95087181.20 | 4792.75 | 05-NOV-06:10 | 7.17 |
December | 0.568105E+09 | 5238.76 | 23-DEC-07:10 | 6.33 |
Annual Sum or Average | 0.281836E+10 | |||
Minimum of Months | 199498.74 | 1855.45 | 1.83 | |
Maximum of Months | 0.873967E+09 | 18431.65 | 18.47 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:01 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.245008E+10 | 1434.30 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.221916E+10 | 1434.30 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.248909E+10 | 1434.30 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.238066E+10 | 1434.30 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.246959E+10 | 1434.30 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.240590E+10 | 1434.30 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.244463E+10 | 1434.30 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.248909E+10 | 1434.30 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.238123E+10 | 1434.30 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.244979E+10 | 1434.30 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.237177E+10 | 1434.30 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.244492E+10 | 1434.30 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.289959E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.221916E+10 | 1434.30 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.248909E+10 | 1434.30 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.218303E+10 | 1277.97 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.197727E+10 | 1277.97 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.221779E+10 | 1277.97 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.212117E+10 | 1277.97 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.220041E+10 | 1277.97 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.214367E+10 | 1277.97 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.217817E+10 | 1277.97 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.221779E+10 | 1277.97 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.212169E+10 | 1277.97 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.218277E+10 | 1277.97 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.211325E+10 | 1277.97 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.217843E+10 | 1277.97 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.258354E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.197727E+10 | 1277.97 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.221779E+10 | 1277.97 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.245008E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29887081.10 | 0.888793E+10 |
February | 0.852256E+10 | 0.221916E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5011964.08 | 0.809199E+10 |
March | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 687459.62 | 0.938891E+10 |
April | 0.915225E+10 | 0.238066E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29684445.57 | 0.688631E+10 |
May | 0.947560E+10 | 0.246959E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 424932.83 | 0.696516E+10 |
June | 0.922788E+10 | 0.240590E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5312046.60 | 0.527899E+10 |
July | 0.939996E+10 | 0.244463E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166270E+09 | 0.384985E+10 |
August | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189806E+09 | 0.377385E+10 |
September | 0.915225E+10 | 0.238123E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335793E+09 | 0.501479E+10 |
October | 0.940563E+10 | 0.244979E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620306E+09 | 0.461673E+10 |
November | 0.909363E+10 | 0.237177E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29751996.32 | 0.773190E+10 |
December | 0.939996E+10 | 0.244492E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24146648.14 | 0.847361E+10 |
Annual Sum or Average | 0.111326E+12 | 0.289959E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143708E+10 | 0.789600E+11 |
Minimum of Months | 0.852256E+10 | 0.221916E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 424932.83 | 0.377385E+10 |
Maximum of Months | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620306E+09 | 0.938891E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.218303E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169541E+09 |
February | 0.610713E+09 | 0.197727E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188592E+09 |
March | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203515E+09 |
April | 0.655836E+09 | 0.212117E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 16902.06 | 0.131055E+09 |
May | 0.679007E+09 | 0.220041E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159655E+09 |
June | 0.661256E+09 | 0.214367E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88764599.59 |
July | 0.673587E+09 | 0.217817E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 326016.25 | 63282675.76 |
August | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 237642.21 | 89135631.07 |
September | 0.655836E+09 | 0.212169E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1898820.04 | 82700140.13 |
October | 0.673993E+09 | 0.218277E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4595442.90 | 0.130447E+09 |
November | 0.651635E+09 | 0.211325E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 13262.25 | 0.167232E+09 |
December | 0.673587E+09 | 0.217843E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179720E+09 |
Annual Sum or Average | 0.797748E+10 | 0.258354E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 7088085.72 | 0.165364E+10 |
Minimum of Months | 0.610713E+09 | 0.197727E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63282675.76 |
Maximum of Months | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 4595442.90 | 0.203515E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470530E+09 | 0.996131E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315932E+09 | 0.101491E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289833E+09 | 0.148863E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282203E+09 | 0.199570E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253318E+09 | 0.203957E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188405E+09 | 0.208482E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238500E+09 | 0.231954E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252125E+09 | 0.213051E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314805E+09 | 0.163946E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395151E+09 | 0.118705E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425009E+09 | 0.101698E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513648E+09 | 0.897224E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393946E+10 | 0.188105E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188405E+09 | 0.897224E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513648E+09 | 0.231954E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 1434.30 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.14 | 18-JAN-12:55 | 14333.23 | 02-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 1434.30 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.46 | 01-FEB-12:05 | 11294.52 | 21-FEB-20:55 |
March | 9454.80 | 04-MAR-19:10 | 1434.30 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 11-MAR-13:25 | 13571.80 | 29-MAR-19:55 |
April | 9454.80 | 01-APR-18:10 | 1434.30 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.23 | 26-APR-13:00 | 9274.77 | 15-APR-18:52 |
May | 9454.80 | 06-MAY-18:10 | 1434.30 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 04-MAY-12:00 | 9353.81 | 10-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 1434.30 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 834.65 | 29-JUN-11:05 | 7808.76 | 06-JUN-18:52 |
July | 9454.80 | 01-JUL-18:10 | 1434.30 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3597.75 | 19-JUL-12:00 | 6898.41 | 15-JUL-18:57 |
August | 9454.80 | 05-AUG-18:10 | 1434.30 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3598.78 | 18-AUG-12:00 | 7200.83 | 21-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 1434.30 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10290.70 | 29-SEP-11:05 | 7946.59 | 02-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 1434.30 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.45 | 16-OCT-11:03 | 8398.78 | 07-OCT-18:53 |
November | 9454.80 | 04-NOV-18:10 | 1434.30 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.80 | 19-NOV-13:00 | 10932.49 | 04-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 1434.30 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1858.96 | 19-DEC-13:00 | 13276.02 | 28-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 1434.30 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 6898.41 | |||||
Maximum of Months | 9454.80 | 1434.30 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 11027.45 | 14333.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1277.97 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 752.21 | 02-JAN-03:00 |
February | 677.52 | 04-FEB-19:10 | 1277.97 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.05 | 25-FEB-03:00 |
March | 677.52 | 04-MAR-19:10 | 1277.97 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 649.03 | 29-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 1277.97 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 5.44 | 26-APR-13:00 | 476.83 | 17-APR-03:20 |
May | 677.52 | 06-MAY-18:10 | 1277.97 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 532.52 | 26-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 1277.97 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 366.76 | 07-JUN-01:00 |
July | 677.52 | 01-JUL-18:10 | 1277.97 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 14.33 | 31-JUL-13:00 | 273.71 | 21-JUL-01:30 |
August | 677.52 | 05-AUG-18:10 | 1277.97 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 11.54 | 17-AUG-14:00 | 241.27 | 29-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 1277.97 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 59.26 | 29-SEP-13:40 | 325.99 | 02-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 1277.97 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 89.17 | 16-OCT-10:23 | 679.85 | 11-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 1277.97 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 5.46 | 19-NOV-13:00 | 731.54 | 23-NOV-04:20 |
December | 677.52 | 02-DEC-19:10 | 1277.97 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 597.79 | 19-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1277.97 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 241.27 | ||||||
Maximum of Months | 677.52 | 1277.97 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 89.17 | 797.05 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.78 | 06-JAN-04:00 | 1876.81 | 30-JAN-11:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.19 | 01-FEB-03:01 | 2097.56 | 18-FEB-12:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.44 | 07-MAR-06:00 | 2561.33 | 15-MAR-12:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.27 | 16-APR-00:55 | 2689.45 | 23-APR-12:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.90 | 16-MAY-24:00 | 2822.30 | 31-MAY-12:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.38 | 18-JUN-01:35 | 2713.66 | 01-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.03 | 14-JUL-05:25 | 2674.76 | 03-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 566.94 | 24-AUG-03:51 | 2534.47 | 11-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.16 | 29-SEP-22:50 | 2384.02 | 07-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 16-OCT-06:52 | 2155.62 | 18-OCT-12:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.74 | 27-NOV-06:53 | 1917.94 | 04-NOV-11:40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.94 | 26-DEC-05:00 | 1772.51 | 02-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.03 | 1772.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 2822.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11898.86 | 18-JAN-12:55 | 16808.53 | 2868.61 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.14 | 0.00 |
February | 10172.43 | 01-FEB-12:05 | 16808.53 | 2868.61 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.46 | 0.00 |
March | 7780.53 | 10-MAR-13:00 | 8404.27 | 1434.30 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.06 |
April | 27546.73 | 27-APR-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30481.92 | 04-MAY-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32549.96 | 23-JUN-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30199.48 | 08-JUL-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29973.63 | 22-AUG-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
September | 32414.15 | 30-SEP-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
October | 38753.49 | 15-OCT-03:21 | 0.00 | 2390.51 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10584.23 | 19-NOV-13:00 | 5252.67 | 1115.57 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1841.80 | 0.00 |
December | 12374.31 | 19-DEC-13:00 | 8404.27 | 1434.30 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1858.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7780.53 | 0.00 | 1115.57 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38753.49 | 16808.53 | 2868.61 | 7326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1861.14 | 794.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49426.87 | 06-JAN-04:21 | 0.00 | 1490.96 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
February | 48868.90 | 04-FEB-03:01 | 0.00 | 1916.95 | 16273.31 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 254.76 |
March | 44426.77 | 12-MAR-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 218.32 |
April | 46096.67 | 02-APR-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 352.76 |
May | 42676.09 | 27-MAY-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 |
June | 37681.65 | 13-JUN-03:41 | 0.00 | 1703.96 | 19751.91 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 207.76 |
July | 36200.01 | 06-JUL-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33336.57 | 22-AUG-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 117.53 |
September | 38895.29 | 20-SEP-02:11 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 150.43 |
October | 48327.83 | 27-OCT-03:31 | 0.00 | 1916.95 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 305.44 |
November | 52793.78 | 24-NOV-04:21 | 0.00 | 1490.96 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 503.36 |
December | 53325.32 | 20-DEC-03:01 | 0.00 | 1916.95 | 16273.31 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 458.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 33336.57 | 0.00 | 1490.96 | 16273.31 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53325.32 | 0.00 | 2129.95 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 503.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.88 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.76 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.26 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.97 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.02 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.23 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.73 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.53 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.76 | 24.48 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.497253E+11 | 32584.81 | 17-JAN-11:00 | 0.630974E+11 | 54626.31 | 08-JAN-07:19 |
February | 0.440877E+11 | 32647.70 | 01-FEB-11:00 | 0.551853E+11 | 52504.99 | 25-FEB-13:30 |
March | 0.487656E+11 | 31149.55 | 11-MAR-11:20 | 0.629126E+11 | 58835.18 | 29-MAR-10:20 |
April | 0.481687E+11 | 34948.41 | 26-APR-10:00 | 0.560909E+11 | 48407.75 | 01-APR-12:39 |
May | 0.492714E+11 | 31800.92 | 03-MAY-10:20 | 0.572922E+11 | 48105.75 | 03-MAY-12:20 |
June | 0.501574E+11 | 35585.72 | 29-JUN-10:00 | 0.545781E+11 | 47793.98 | 03-JUN-12:00 |
July | 0.557550E+11 | 37853.81 | 19-JUL-10:20 | 0.561512E+11 | 47565.56 | 02-JUL-12:39 |
August | 0.568211E+11 | 38448.63 | 14-AUG-10:20 | 0.561657E+11 | 47535.26 | 31-AUG-12:30 |
September | 0.518890E+11 | 41986.34 | 29-SEP-10:20 | 0.544991E+11 | 47690.56 | 23-SEP-12:30 |
October | 0.547048E+11 | 42422.86 | 16-OCT-10:20 | 0.567782E+11 | 48060.38 | 31-OCT-12:39 |
November | 0.480359E+11 | 32802.61 | 19-NOV-11:20 | 0.567390E+11 | 48351.61 | 30-NOV-13:39 |
December | 0.499427E+11 | 33260.89 | 19-DEC-11:20 | 0.617206E+11 | 48573.29 | 31-DEC-13:30 |
Annual Sum or Average | 0.607325E+12 | 0.691210E+12 | ||||
Minimum of Months | 0.440877E+11 | 31149.55 | 0.544991E+11 | 47535.26 | ||
Maximum of Months | 0.568211E+11 | 42422.86 | 0.630974E+11 | 58835.18 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.463311E+10 | 0.406801E+10 | 0.235157E+11 | 0.00 | 0.110807E+11 | 0.79 | 0.00 | 0.965765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419643E+10 | 0.347719E+10 | 0.212400E+11 | 0.00 | 0.999706E+10 | 0.72 | 0.00 | 0.236548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470688E+10 | 0.356384E+10 | 0.235157E+11 | 0.00 | 0.110477E+11 | 0.80 | 0.00 | 0.469984E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.450183E+10 | 0.316839E+10 | 0.227571E+11 | 0.00 | 0.107445E+11 | 0.77 | 0.00 | 0.156863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466999E+10 | 0.302501E+10 | 0.235157E+11 | 0.00 | 0.111240E+11 | 0.80 | 0.00 | 0.129764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.454957E+10 | 0.280444E+10 | 0.227571E+11 | 0.00 | 0.109004E+11 | 0.77 | 0.00 | 0.358588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.462280E+10 | 0.295254E+10 | 0.235157E+11 | 0.00 | 0.113748E+11 | 0.79 | 0.00 | 0.749849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.470688E+10 | 0.316208E+10 | 0.235157E+11 | 0.00 | 0.113888E+11 | 0.80 | 0.00 | 0.823090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450292E+10 | 0.332909E+10 | 0.227571E+11 | 0.00 | 0.109575E+11 | 0.77 | 0.00 | 0.476441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463256E+10 | 0.373085E+10 | 0.235157E+11 | 0.00 | 0.113035E+11 | 0.79 | 0.00 | 0.580730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448502E+10 | 0.386477E+10 | 0.227571E+11 | 0.00 | 0.107423E+11 | 0.77 | 0.00 | 0.832412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462334E+10 | 0.413734E+10 | 0.235157E+11 | 0.00 | 0.110829E+11 | 0.79 | 0.00 | 0.112704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548313E+11 | 0.412836E+11 | 0.276879E+12 | 0.00 | 0.131744E+12 | 9.37 | 0.00 | 0.363850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.419643E+10 | 0.280444E+10 | 0.212400E+11 | 0.00 | 0.999706E+10 | 0.72 | 0.00 | 0.236548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.470688E+10 | 0.413734E+10 | 0.235157E+11 | 0.00 | 0.113888E+11 | 0.80 | 0.00 | 0.823090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.557445E+10 | 0.00 | 0.169973E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.321149E+10 | 0.00 | 0.153699E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.548689E+10 | 0.00 | 0.169000E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.871903E+09 | 0.00 | 0.160006E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.575427E+09 | 0.00 | 0.161911E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 7654975.45 | 0.00 | 0.153520E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 1676173.63 | 0.00 | 0.156237E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 1728529.75 | 0.00 | 0.156383E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 12267704.85 | 0.00 | 0.152683E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.171294E+09 | 0.00 | 0.160812E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.156836E+10 | 0.00 | 0.159522E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.440524E+10 | 0.00 | 0.167896E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.218884E+11 | 0.00 | 0.192164E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 1676173.63 | 0.00 | 0.152683E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.557445E+10 | 0.00 | 0.169973E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2712.27 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 4852.11 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2712.27 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 4852.11 | 01-FEB-00:10 | 0.00 | 11-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 2712.27 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 4852.11 | 01-MAR-00:10 | 0.00 | 22-MAR-08:09 | 0.00 | 01-MAR-00:10 |
April | 2712.27 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 4852.11 | 01-APR-04:10 | 0.00 | 05-APR-17:40 | 0.00 | 01-APR-00:10 |
May | 2712.27 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 4852.11 | 01-MAY-04:10 | 0.00 | 06-MAY-08:00 | 0.00 | 01-MAY-00:10 |
June | 2712.27 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 4852.11 | 01-JUN-04:10 | 0.00 | 15-JUN-08:30 | 0.00 | 01-JUN-00:10 |
July | 2712.27 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 4852.11 | 01-JUL-04:10 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 2712.27 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 4852.11 | 01-AUG-04:10 | 0.00 | 05-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 2712.27 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 4852.11 | 01-SEP-04:10 | 0.00 | 05-SEP-10:20 | 0.00 | 01-SEP-00:10 |
October | 2712.27 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 4852.11 | 01-OCT-04:10 | 0.00 | 10-OCT-08:30 | 0.00 | 01-OCT-00:10 |
November | 2712.27 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 4852.11 | 01-NOV-04:10 | 0.00 | 01-NOV-10:09 | 0.00 | 01-NOV-00:10 |
December | 2712.27 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 4852.11 | 01-DEC-00:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2712.27 | 2625.88 | 14428.03 | 0.00 | 4852.11 | 0.00 | 0.00 | ||||||
Maximum of Months | 2712.27 | 2625.88 | 14428.03 | 0.00 | 4852.11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 8291.74 | 18-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8044.89 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6618.47 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10598.65 | 26-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7901.17 | 04-MAY-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11145.24 | 29-JUN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13597.67 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14101.68 | 14-AUG-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17602.43 | 29-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18218.82 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8474.60 | 19-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8397.63 | 19-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6618.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18218.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 32584.81 | 17-JAN-11:00 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 7685.01 | 0.00 |
February | 32647.70 | 01-FEB-11:00 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 7761.05 | 0.00 |
March | 31149.55 | 11-MAR-11:20 | 2410.91 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 4932.82 | 0.00 |
April | 34948.41 | 26-APR-10:00 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 10041.81 | 0.00 |
May | 31800.92 | 03-MAY-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 5246.09 | 0.00 |
June | 35585.72 | 29-JUN-10:00 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 10658.50 | 0.00 |
July | 37853.81 | 19-JUL-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 11269.06 | 0.00 |
August | 38448.63 | 14-AUG-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 11863.87 | 0.00 |
September | 41986.34 | 29-SEP-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 15452.78 | 0.00 |
October | 42422.86 | 16-OCT-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 15889.75 | 0.00 |
November | 32802.61 | 19-NOV-11:20 | 2109.55 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 6903.58 | 0.00 |
December | 33260.89 | 19-DEC-11:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 6742.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 31149.55 | 2109.55 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 4932.82 | 0.00 | |
Maximum of Months | 42422.86 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4852.11 | 0.00 | 0.00 | 15889.75 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 36462.56 | 08-JAN-07:10 | 0.00 | 25685.14 | 29-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 17104.62 | 05-FEB-07:10 | 0.00 | 25681.51 | 07-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 24771.32 | 30-MAR-06:10 | 0.00 | 25621.70 | 02-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 17927.15 | 01-APR-06:10 | 0.00 | 25424.60 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 7544.39 | 14-MAY-05:10 | 0.00 | 25122.60 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 1436.78 | 01-JUN-06:10 | 0.00 | 24810.83 | 03-JUN-12:00 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2412.16 | 04-JUL-02:09 | 0.00 | 24582.41 | 02-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 1918.14 | 30-AUG-02:09 | 0.00 | 24552.11 | 31-AUG-12:30 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 3578.53 | 29-SEP-02:09 | 0.00 | 24707.41 | 23-SEP-12:30 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 7183.19 | 29-OCT-06:10 | 0.00 | 25077.23 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 17497.99 | 05-NOV-06:10 | 0.00 | 25368.46 | 30-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 21006.74 | 22-DEC-07:10 | 0.00 | 25590.14 | 31-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1436.78 | 0.00 | 24552.11 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 36462.56 | 0.00 | 25685.14 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.54 | 0.00 | 24.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.48 | 0.00 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.51 | 0.00 | 24.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.60 | 0.00 | 24.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.64 | 0.67 | 24.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.00 | 24.47 |
December | 0.17 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 0.50 | 20.51 | 0.00 | 20.51 | 23.33 | 24.46 | 0.67 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.00 | 20.52 | 7.50 | 24.64 | 0.67 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.15 | 0.00 | 28.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.88 | 0.00 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.88 | 0.00 | 27.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.58 | 0.00 | 28.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 28.87 | 0.00 | 28.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 29.68 | 0.00 | 29.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 30.12 | 0.00 | 30.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 30.16 | 0.00 | 30.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 29.80 | 0.83 | 29.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 29.70 | 1.00 | 29.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.45 | 0.00 | 28.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 28.00 | 0.00 | 28.00 |
Annual Sum or Average | 0.00 | 0.00 | 233.83 | 29.14 | 1.83 | 29.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.88 | 0.00 | 27.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 30.16 | 1.00 | 30.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.17 | 21.45 | 162.83 | 22.09 | 8.67 | 22.04 |
February | 401.67 | 21.47 | 98.67 | 21.90 | 7.67 | 21.90 |
March | 459.83 | 21.33 | 125.17 | 21.78 | 9.67 | 21.74 |
April | 290.17 | 21.55 | 248.00 | 22.59 | 0.00 | 22.59 |
May | 273.00 | 21.69 | 280.17 | 22.77 | 0.00 | 22.77 |
June | 140.50 | 22.58 | 427.50 | 23.50 | 28.83 | 23.51 |
July | 207.17 | 23.83 | 572.33 | 23.85 | 196.17 | 23.86 |
August | 265.67 | 23.85 | 587.83 | 23.86 | 259.67 | 23.86 |
September | 159.83 | 23.28 | 480.00 | 23.69 | 100.67 | 23.71 |
October | 213.67 | 23.01 | 428.83 | 23.58 | 102.50 | 23.63 |
November | 332.17 | 21.61 | 181.33 | 22.37 | 0.83 | 22.37 |
December | 390.00 | 21.55 | 111.50 | 22.01 | 4.83 | 21.98 |
Annual Sum or Average | 3511.83 | 22.03 | 3704.17 | 22.94 | 719.50 | 23.01 |
Minimum of Months | 140.50 | 21.33 | 98.67 | 21.78 | 0.00 | 21.74 |
Maximum of Months | 459.83 | 23.85 | 587.83 | 23.86 | 259.67 | 23.86 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.33 | 21.72 | 347.67 | 22.93 | 138.67 | 23.14 |
February | 293.17 | 21.57 | 290.83 | 22.84 | 80.50 | 23.08 |
March | 379.83 | 21.40 | 297.83 | 22.56 | 104.33 | 22.83 |
April | 370.83 | 24.14 | 427.00 | 24.56 | 241.33 | 24.87 |
May | 378.33 | 24.65 | 477.33 | 24.85 | 284.17 | 25.12 |
June | 401.67 | 25.80 | 568.33 | 25.49 | 392.33 | 25.61 |
July | 512.00 | 25.90 | 608.83 | 25.76 | 512.00 | 25.81 |
August | 536.17 | 25.87 | 612.00 | 25.76 | 536.17 | 25.80 |
September | 427.50 | 25.84 | 580.00 | 25.57 | 421.67 | 25.67 |
October | 456.17 | 25.55 | 551.83 | 25.59 | 413.83 | 25.71 |
November | 310.83 | 22.95 | 384.17 | 23.89 | 148.17 | 24.21 |
December | 344.00 | 21.77 | 329.50 | 23.13 | 113.17 | 23.41 |
Annual Sum or Average | 4769.83 | 24.18 | 5475.33 | 24.66 | 3386.33 | 24.93 |
Minimum of Months | 293.17 | 21.40 | 290.83 | 22.56 | 80.50 | 22.83 |
Maximum of Months | 536.17 | 25.90 | 612.00 | 25.76 | 536.17 | 25.81 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.31797 | 41.91069 | 0.09464 | 7.73960 |
February | 551.00000 | 22.06916 | 45.63356 | 0.04193 | 7.03826 |
March | 612.00000 | 21.91244 | 49.48518 | 0.02349 | 7.28188 |
April | 590.00000 | 22.65286 | 51.66558 | 0.25115 | 8.37159 |
May | 611.00000 | 22.81834 | 50.71186 | -0.6813 | 18.10584 |
June | 592.00000 | 23.45932 | 55.50790 | -0.4114 | 10.19570 |
July | 609.00000 | 23.81619 | 60.66921 | -0.2133 | 6.55067 |
August | 612.00000 | 23.82650 | 62.63235 | -0.1839 | 6.31975 |
September | 590.00000 | 23.62041 | 57.37243 | -0.3023 | 8.36131 |
October | 610.00000 | 23.52517 | 47.66370 | 0.47802 | 11.19537 |
November | 591.00000 | 22.52446 | 43.05472 | 0.17060 | 7.74726 |
December | 609.00000 | 22.33137 | 36.72016 | 0.07056 | 7.27644 |
Annual Sum or Average | 7187.00000 | 22.91131 | 50.27604 | -0.0559 | 8.86641 |
Minimum of Months | 551.00000 | 21.91244 | 36.72016 | -0.6813 | 6.31975 |
Maximum of Months | 612.00000 | 23.82650 | 62.63235 | 0.47802 | 18.10584 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.59689 | 44.29355 | 0.36678 | 15.51326 |
February | 551.00000 | 22.49669 | 47.41610 | 0.35962 | 13.32939 |
March | 612.00000 | 22.16854 | 51.63963 | 0.31256 | 13.70356 |
April | 590.00000 | 23.86524 | 50.92857 | 0.72808 | 21.07250 |
May | 611.00000 | 24.18485 | 49.53900 | 0.05921 | 13.63001 |
June | 592.00000 | 25.13682 | 52.37512 | 0.41444 | 13.08434 |
July | 609.00000 | 25.64086 | 56.03222 | 0.63750 | 15.86942 |
August | 612.00000 | 25.66480 | 57.66871 | 0.65410 | 16.17210 |
September | 590.00000 | 25.31320 | 53.81622 | 0.48835 | 13.70115 |
October | 610.00000 | 25.21427 | 45.24360 | 1.03369 | 30.61601 |
November | 591.00000 | 23.34410 | 43.95138 | 0.55310 | 16.99054 |
December | 609.00000 | 22.72615 | 39.45802 | 0.36340 | 14.47107 |
Annual Sum or Average | 7187.00000 | 24.03779 | 49.37294 | 0.49808 | 16.54047 |
Minimum of Months | 551.00000 | 22.16854 | 39.45802 | 0.05921 | 13.08434 |
Maximum of Months | 612.00000 | 25.66480 | 57.66871 | 1.03369 | 30.61601 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.135426E+10 | 0.426763E+09 | 59.86 | 0.127553E+10 | 78733283.39 | 0.00 | 0.48 | 18-JAN-12:55 | 0.00 | 01-JAN-00:03 | 15106.56 | 18-JAN-12:55 | 15106.56 | 18-JAN-12:55 | 2444.13 | 17-JAN-14:00 | 4533.55 | 18-JAN-12:55 | 0.00 | 01-JAN-00:03 |
February | 0.287589E+09 | 91578243.40 | 18.57 | 0.285094E+09 | 2494910.30 | 0.00 | 0.43 | 01-FEB-12:05 | 0.00 | 01-FEB-00:10 | 13215.11 | 01-FEB-12:05 | 13215.11 | 01-FEB-12:05 | 971.65 | 01-FEB-13:30 | 4021.83 | 01-FEB-12:05 | 0.00 | 01-FEB-00:10 |
March | 0.596434E+09 | 0.190406E+09 | 31.33 | 0.517634E+09 | 78800085.25 | 0.00 | 0.33 | 23-MAR-14:00 | 0.00 | 01-MAR-00:03 | 10030.55 | 23-MAR-14:00 | 9847.68 | 11-MAR-14:00 | 2659.07 | 22-MAR-13:00 | 3109.63 | 23-MAR-14:00 | 0.00 | 01-MAR-00:03 |
April | 0.193241E+10 | 0.610949E+09 | 92.56 | 0.160422E+10 | 0.328195E+09 | 0.00 | 1.00 | 27-APR-02:61 | 0.00 | 01-APR-00:01 | 35923.66 | 27-APR-02:61 | 19193.50 | 27-APR-02:61 | 16730.16 | 27-APR-02:61 | 9350.22 | 27-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.115872E+10 | 0.372581E+09 | 83.03 | 0.948438E+09 | 0.210285E+09 | 0.00 | 1.00 | 03-MAY-02:61 | 0.00 | 01-MAY-00:01 | 35923.66 | 03-MAY-02:61 | 22357.20 | 04-MAY-02:61 | 15437.81 | 03-MAY-02:61 | 9350.22 | 03-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.435018E+10 | 0.135436E+10 | 182.96 | 0.313904E+10 | 0.121114E+10 | 0.00 | 1.00 | 19-JUN-02:61 | 0.00 | 01-JUN-00:01 | 35923.66 | 19-JUN-02:61 | 24092.71 | 23-JUN-02:61 | 18141.79 | 29-JUN-02:61 | 9350.22 | 19-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.105592E+11 | 0.315979E+10 | 300.88 | 0.703340E+10 | 0.352575E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 37060.05 | 30-JUL-02:62 | 23642.22 | 04-JUL-02:62 | 19882.00 | 20-JUL-02:62 | 9432.90 | 30-JUL-02:62 | 0.00 | 01-JUL-00:01 |
August | 0.121422E+11 | 0.360145E+10 | 303.22 | 0.794706E+10 | 0.419517E+10 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 37473.34 | 07-AUG-02:62 | 22435.12 | 22-AUG-02:61 | 21163.78 | 07-AUG-02:62 | 9462.62 | 07-AUG-02:62 | 0.00 | 01-AUG-00:01 |
September | 0.628234E+10 | 0.193928E+10 | 217.81 | 0.478013E+10 | 0.150221E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 37777.78 | 22-SEP-02:62 | 35923.66 | 30-SEP-02:42 | 20752.62 | 22-SEP-02:62 | 9484.53 | 22-SEP-02:62 | 0.00 | 01-SEP-00:01 |
October | 0.815386E+10 | 0.250133E+10 | 255.45 | 0.694109E+10 | 0.121277E+10 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 38110.51 | 05-OCT-02:61 | 35923.66 | 16-OCT-03:21 | 20428.10 | 01-OCT-03:21 | 9703.79 | 16-OCT-11:07 | 0.00 | 01-OCT-00:01 |
November | 0.114000E+10 | 0.359442E+09 | 52.63 | 0.111643E+10 | 23569792.71 | 0.00 | 0.46 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 | 14291.71 | 19-NOV-13:00 | 14291.71 | 19-NOV-13:00 | 1897.83 | 10-NOV-13:00 | 4314.85 | 19-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.166709E+10 | 0.528831E+09 | 89.90 | 0.165582E+10 | 11273711.33 | 0.00 | 0.50 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 | 15576.45 | 19-DEC-13:00 | 15576.45 | 19-DEC-13:00 | 1298.80 | 07-DEC-13:55 | 4658.48 | 19-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.496243E+11 | 0.151368E+11 | 1688.21 | 0.372439E+11 | 0.123804E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.287589E+09 | 91578243.40 | 18.57 | 0.285094E+09 | 2494910.30 | 0.00 | 0.33 | 0.00 | 10030.55 | 9847.68 | 971.65 | 3109.63 | 0.00 | |||||||
Maximum of Months | 0.121422E+11 | 0.360145E+10 | 303.22 | 0.794706E+10 | 0.419517E+10 | 0.00 | 1.00 | 0.00 | 38110.51 | 35923.66 | 21163.78 | 9703.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.175245E+10 | 0.539002E+09 | 81.91 | 0.153611E+10 | 0.216338E+09 | 0.00 | 1.00 | 06-JAN-04:21 | 0.00 | 01-JAN-00:03 | 27698.08 | 15-JAN-04:22 | 27698.08 | 15-JAN-03:01 | 15755.15 | 26-JAN-03:01 | 7209.27 | 06-JAN-04:21 | 0.00 | 01-JAN-00:03 |
February | 0.467650E+09 | 0.144969E+09 | 33.41 | 0.411928E+09 | 55721146.28 | 0.00 | 1.00 | 01-FEB-03:01 | 0.00 | 01-FEB-00:10 | 27698.08 | 18-FEB-03:01 | 27698.08 | 03-FEB-03:01 | 15388.81 | 14-FEB-04:21 | 7209.27 | 01-FEB-03:01 | 0.00 | 01-FEB-00:10 |
March | 0.897779E+09 | 0.279578E+09 | 48.50 | 0.683869E+09 | 0.213910E+09 | 0.00 | 1.00 | 03-MAR-03:01 | 0.00 | 01-MAR-00:03 | 27698.08 | 14-MAR-04:01 | 18990.74 | 12-MAR-02:61 | 15353.03 | 24-MAR-02:61 | 7209.27 | 03-MAR-03:01 | 0.00 | 01-MAR-00:03 |
April | 0.311609E+10 | 0.957683E+09 | 144.58 | 0.234512E+10 | 0.770977E+09 | 0.00 | 1.00 | 02-APR-02:61 | 0.00 | 01-APR-00:01 | 27698.08 | 09-APR-02:61 | 23261.87 | 02-APR-02:61 | 15458.82 | 27-APR-02:61 | 7209.27 | 02-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.297745E+10 | 0.925054E+09 | 159.35 | 0.216975E+10 | 0.807702E+09 | 0.00 | 1.00 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 | 27698.08 | 04-MAY-03:21 | 26466.14 | 24-MAY-03:31 | 15265.59 | 05-MAY-02:41 | 7209.27 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 |
June | 0.745705E+10 | 0.223152E+10 | 251.34 | 0.496124E+10 | 0.249582E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 27698.08 | 24-JUN-02:51 | 16983.36 | 23-JUN-03:21 | 16512.81 | 28-JUN-02:11 | 7209.27 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.152333E+11 | 0.433870E+10 | 360.77 | 0.930195E+10 | 0.593139E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 27935.84 | 23-JUL-02:11 | 19635.07 | 19-JUL-11:07 | 17218.83 | 25-JUL-02:52 | 7226.74 | 23-JUL-02:11 | 0.00 | 01-JUL-00:01 |
August | 0.164220E+11 | 0.462945E+10 | 364.61 | 0.980368E+10 | 0.661837E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 29300.81 | 14-AUG-10:53 | 19681.43 | 14-AUG-11:00 | 18031.31 | 07-AUG-02:52 | 7257.62 | 07-AUG-02:11 | 0.00 | 01-AUG-00:01 |
September | 0.956435E+10 | 0.282514E+10 | 274.72 | 0.658204E+10 | 0.298231E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 28366.72 | 22-SEP-02:11 | 28230.40 | 29-SEP-13:00 | 17008.40 | 22-SEP-02:11 | 8352.18 | 29-SEP-10:55 | 0.00 | 01-SEP-00:01 |
October | 0.112355E+11 | 0.330597E+10 | 316.80 | 0.873567E+10 | 0.249983E+10 | 0.00 | 1.00 | 01-OCT-01:32 | 0.00 | 01-OCT-00:01 | 28984.85 | 05-OCT-02:11 | 28149.51 | 16-OCT-11:00 | 18275.02 | 01-OCT-03:31 | 8545.07 | 16-OCT-10:53 | 0.00 | 01-OCT-00:01 |
November | 0.153219E+10 | 0.472969E+09 | 83.07 | 0.135973E+10 | 0.172456E+09 | 0.00 | 1.00 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 | 27698.08 | 20-NOV-03:01 | 27698.08 | 28-NOV-03:42 | 16303.57 | 12-NOV-03:11 | 7209.27 | 01-NOV-02:11 | 0.00 | 01-NOV-00:01 |
December | 0.191706E+10 | 0.598209E+09 | 104.51 | 0.185623E+10 | 60827482.06 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 | 27698.08 | 02-DEC-03:01 | 27698.08 | 28-DEC-03:01 | 14391.54 | 02-DEC-03:01 | 7209.27 | 01-DEC-03:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.725730E+11 | 0.212482E+11 | 2223.58 | 0.497473E+11 | 0.228256E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.467650E+09 | 0.144969E+09 | 33.41 | 0.411928E+09 | 55721146.28 | 0.00 | 1.00 | 0.00 | 27698.08 | 16983.36 | 14391.54 | 7209.27 | 0.00 | |||||||
Maximum of Months | 0.164220E+11 | 0.462945E+10 | 364.61 | 0.980368E+10 | 0.661837E+10 | 0.00 | 1.00 | 0.00 | 29300.81 | 28230.40 | 18275.02 | 8545.07 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.27 | 41.34 | 35.93 | 89.98 | 142.37 | 0.00 | 0.00 | 0.00 |
February | 81.48 | 37.33 | 44.15 | 89.01 | 128.51 | 0.00 | 0.00 | 0.00 |
March | 98.93 | 44.06 | 54.88 | 116.60 | 126.55 | 0.00 | 0.00 | 0.00 |
April | 126.50 | 63.43 | 63.08 | 173.54 | 103.63 | 0.00 | 0.00 | 0.00 |
May | 119.39 | 49.81 | 69.58 | 155.59 | 95.06 | 0.00 | 0.00 | 0.00 |
June | 118.67 | 51.49 | 67.18 | 166.68 | 78.60 | 0.00 | 0.00 | 0.00 |
July | 134.45 | 66.80 | 67.64 | 206.80 | 72.04 | 0.00 | 0.00 | 0.00 |
August | 132.76 | 70.50 | 62.26 | 206.18 | 74.49 | 0.00 | 0.00 | 0.00 |
September | 96.69 | 44.31 | 52.38 | 138.24 | 87.14 | 0.00 | 0.00 | 0.00 |
October | 85.58 | 43.98 | 41.60 | 125.93 | 96.52 | 0.00 | 0.00 | 0.00 |
November | 78.04 | 39.66 | 38.38 | 90.72 | 130.56 | 0.00 | 0.00 | 0.00 |
December | 74.47 | 41.40 | 33.08 | 86.26 | 142.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 102.16 | 49.61 | 52.55 | 137.47 | 106.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.47 | 37.33 | 33.08 | 86.26 | 72.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.45 | 70.50 | 69.58 | 206.80 | 142.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 377.35 | 276.65 | 100.71 | 574.85 | 273.41 | 0.00 | 0.00 | 0.00 |
February | 296.95 | 182.87 | 114.08 | 419.09 | 250.39 | 0.00 | 0.00 | 0.00 |
March | 237.26 | 114.83 | 122.42 | 329.02 | 259.54 | 0.00 | 0.00 | 0.00 |
April | 198.94 | 76.52 | 122.42 | 291.44 | 219.17 | 0.00 | 0.00 | 0.00 |
May | 141.43 | 17.88 | 123.56 | 156.00 | 203.91 | 0.00 | 0.00 | 0.00 |
June | 123.94 | 7.80 | 116.14 | 134.85 | 165.14 | 0.00 | 0.00 | 0.00 |
July | 131.47 | 15.28 | 116.19 | 174.34 | 149.81 | 0.00 | 0.00 | 0.00 |
August | 169.20 | 54.06 | 115.15 | 270.46 | 156.90 | 0.00 | 0.00 | 0.00 |
September | 234.86 | 119.41 | 115.45 | 384.34 | 177.96 | 0.00 | 0.00 | 0.00 |
October | 297.76 | 199.10 | 98.67 | 498.08 | 191.14 | 0.00 | 0.00 | 0.00 |
November | 361.35 | 254.98 | 106.37 | 547.03 | 250.84 | 0.00 | 0.00 | 0.00 |
December | 403.06 | 306.61 | 96.45 | 619.53 | 272.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 247.59 | 135.34 | 112.25 | 366.45 | 214.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 123.94 | 7.80 | 96.45 | 134.85 | 149.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.06 | 306.61 | 123.56 | 619.53 | 273.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.55 | 37.12 | 36.44 | 86.47 | 146.48 | 0.00 | 0.00 | 0.00 |
February | 87.69 | 40.47 | 47.22 | 100.04 | 130.05 | 0.00 | 0.00 | 0.00 |
March | 100.50 | 44.44 | 56.06 | 119.75 | 129.41 | 0.00 | 0.00 | 0.00 |
April | 138.54 | 72.11 | 66.43 | 191.40 | 104.78 | 0.00 | 0.00 | 0.00 |
May | 136.10 | 62.84 | 73.26 | 181.36 | 95.51 | 0.00 | 0.00 | 0.00 |
June | 144.17 | 72.05 | 72.12 | 205.55 | 77.45 | 0.00 | 0.00 | 0.00 |
July | 152.62 | 81.64 | 70.98 | 233.18 | 70.87 | 0.00 | 0.00 | 0.00 |
August | 143.18 | 77.57 | 65.61 | 220.78 | 75.55 | 0.00 | 0.00 | 0.00 |
September | 122.59 | 65.57 | 57.02 | 180.01 | 86.72 | 0.00 | 0.00 | 0.00 |
October | 93.74 | 51.17 | 42.57 | 140.99 | 98.07 | 0.00 | 0.00 | 0.00 |
November | 84.70 | 44.31 | 40.39 | 104.18 | 132.13 | 0.00 | 0.00 | 0.00 |
December | 74.83 | 40.15 | 34.68 | 90.85 | 146.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.78 | 57.53 | 55.26 | 154.82 | 107.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.55 | 37.12 | 34.68 | 86.47 | 70.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.62 | 81.64 | 73.26 | 233.18 | 146.60 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206957E+09 | 0.110723E+09 | 96234301.66 | 0.241003E+09 | 0.381334E+09 |
February | 0.197119E+09 | 90304614.47 | 0.106815E+09 | 0.215336E+09 | 0.310888E+09 |
March | 0.264984E+09 | 0.118003E+09 | 0.146980E+09 | 0.312312E+09 | 0.338957E+09 |
April | 0.327896E+09 | 0.164403E+09 | 0.163493E+09 | 0.449818E+09 | 0.268608E+09 |
May | 0.319775E+09 | 0.133412E+09 | 0.186363E+09 | 0.416729E+09 | 0.254610E+09 |
June | 0.307587E+09 | 0.133453E+09 | 0.174134E+09 | 0.432024E+09 | 0.203725E+09 |
July | 0.360102E+09 | 0.178923E+09 | 0.181179E+09 | 0.553901E+09 | 0.192965E+09 |
August | 0.355585E+09 | 0.188834E+09 | 0.166751E+09 | 0.552235E+09 | 0.199505E+09 |
September | 0.250616E+09 | 0.114848E+09 | 0.135768E+09 | 0.358320E+09 | 0.225874E+09 |
October | 0.229212E+09 | 0.117802E+09 | 0.111409E+09 | 0.337296E+09 | 0.258513E+09 |
November | 0.202272E+09 | 0.102786E+09 | 99486186.79 | 0.235150E+09 | 0.338411E+09 |
December | 0.199465E+09 | 0.110876E+09 | 88588718.57 | 0.231041E+09 | 0.382295E+09 |
Annual Sum or Average | 0.322157E+10 | 0.156437E+10 | 0.165720E+10 | 0.433517E+10 | 0.335569E+10 |
Minimum of Months | 0.197119E+09 | 90304614.47 | 88588718.57 | 0.215336E+09 | 0.192965E+09 |
Maximum of Months | 0.360102E+09 | 0.188834E+09 | 0.186363E+09 | 0.553901E+09 | 0.382295E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101070E+10 | 0.740972E+09 | 0.269730E+09 | 0.153967E+10 | 0.732296E+09 |
February | 0.718381E+09 | 0.442395E+09 | 0.275986E+09 | 0.101387E+10 | 0.605742E+09 |
March | 0.635467E+09 | 0.307571E+09 | 0.327896E+09 | 0.881251E+09 | 0.695148E+09 |
April | 0.515653E+09 | 0.198347E+09 | 0.317306E+09 | 0.755417E+09 | 0.568098E+09 |
May | 0.378818E+09 | 47884912.69 | 0.330933E+09 | 0.417820E+09 | 0.546144E+09 |
June | 0.321244E+09 | 20209321.72 | 0.301035E+09 | 0.349535E+09 | 0.428045E+09 |
July | 0.352124E+09 | 40919658.65 | 0.311204E+09 | 0.466950E+09 | 0.401252E+09 |
August | 0.453198E+09 | 0.144787E+09 | 0.308412E+09 | 0.724408E+09 | 0.420238E+09 |
September | 0.608759E+09 | 0.309508E+09 | 0.299252E+09 | 0.996197E+09 | 0.461273E+09 |
October | 0.797533E+09 | 0.533261E+09 | 0.264272E+09 | 0.133406E+10 | 0.511956E+09 |
November | 0.936626E+09 | 0.660916E+09 | 0.275709E+09 | 0.141791E+10 | 0.650166E+09 |
December | 0.107955E+10 | 0.821225E+09 | 0.258327E+09 | 0.165934E+10 | 0.728615E+09 |
Annual Sum or Average | 0.780805E+10 | 0.426799E+10 | 0.354006E+10 | 0.115564E+11 | 0.674897E+10 |
Minimum of Months | 0.321244E+09 | 20209321.72 | 0.258327E+09 | 0.349535E+09 | 0.401252E+09 |
Maximum of Months | 0.107955E+10 | 0.821225E+09 | 0.330933E+09 | 0.165934E+10 | 0.732296E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197008E+09 | 99410172.27 | 97597783.02 | 0.231599E+09 | 0.392319E+09 |
February | 0.212142E+09 | 97913542.20 | 0.114229E+09 | 0.242023E+09 | 0.314626E+09 |
March | 0.269183E+09 | 0.119040E+09 | 0.150144E+09 | 0.320747E+09 | 0.346612E+09 |
April | 0.359101E+09 | 0.186918E+09 | 0.172183E+09 | 0.496102E+09 | 0.271602E+09 |
May | 0.364520E+09 | 0.168304E+09 | 0.196217E+09 | 0.485751E+09 | 0.255823E+09 |
June | 0.373690E+09 | 0.186762E+09 | 0.186928E+09 | 0.532779E+09 | 0.200763E+09 |
July | 0.408773E+09 | 0.218657E+09 | 0.190116E+09 | 0.624559E+09 | 0.189812E+09 |
August | 0.383501E+09 | 0.207770E+09 | 0.175731E+09 | 0.591336E+09 | 0.202365E+09 |
September | 0.317759E+09 | 0.169969E+09 | 0.147790E+09 | 0.466592E+09 | 0.224773E+09 |
October | 0.251077E+09 | 0.137062E+09 | 0.114015E+09 | 0.377639E+09 | 0.262679E+09 |
November | 0.219551E+09 | 0.114860E+09 | 0.104691E+09 | 0.270046E+09 | 0.342482E+09 |
December | 0.200430E+09 | 0.107549E+09 | 92881183.59 | 0.243324E+09 | 0.392650E+09 |
Annual Sum or Average | 0.355674E+10 | 0.181421E+10 | 0.174252E+10 | 0.488250E+10 | 0.339651E+10 |
Minimum of Months | 0.197008E+09 | 97913542.20 | 92881183.59 | 0.231599E+09 | 0.189812E+09 |
Maximum of Months | 0.408773E+09 | 0.218657E+09 | 0.196217E+09 | 0.624559E+09 | 0.392650E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 734.63 | 545.59 | 528.18 | 355.10 | 173.07 | 0.00 | 0.00 |
February | 594.81 | 495.61 | 466.12 | 260.67 | 205.45 | 0.00 | 0.00 |
March | 547.00 | 497.13 | 436.69 | 203.34 | 233.36 | 0.00 | 0.00 |
April | 635.83 | 407.04 | 463.99 | 212.06 | 251.92 | 0.00 | 0.00 |
May | 471.33 | 372.86 | 396.92 | 130.53 | 266.39 | 0.00 | 0.00 |
June | 490.05 | 304.17 | 386.78 | 131.34 | 255.44 | 0.00 | 0.00 |
July | 599.63 | 278.03 | 418.53 | 163.72 | 254.82 | 0.00 | 0.00 |
August | 684.17 | 293.69 | 445.15 | 202.13 | 243.02 | 0.00 | 0.00 |
September | 691.23 | 340.46 | 454.14 | 229.29 | 224.85 | 0.00 | 0.00 |
October | 755.33 | 376.05 | 477.08 | 294.25 | 182.83 | 0.00 | 0.00 |
November | 727.05 | 498.64 | 524.09 | 338.95 | 185.14 | 0.00 | 0.00 |
December | 779.28 | 544.01 | 552.36 | 388.16 | 164.20 | 0.00 | 0.00 |
Annual Sum or Average | 642.99 | 412.37 | 462.53 | 242.47 | 220.06 | 0.00 | 0.00 |
Minimum of Months | 471.33 | 278.03 | 386.78 | 130.53 | 164.20 | 0.00 | 0.00 |
Maximum of Months | 779.28 | 545.59 | 552.36 | 388.16 | 266.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196763E+10 | 0.146131E+10 | 0.141467E+10 | 0.951104E+09 | 0.463562E+09 | 0.00 | 0.00 |
February | 0.143895E+10 | 0.119898E+10 | 0.112764E+10 | 0.630613E+09 | 0.497029E+09 | 0.00 | 0.00 |
March | 0.146509E+10 | 0.133150E+10 | 0.116963E+10 | 0.544613E+09 | 0.625020E+09 | 0.00 | 0.00 |
April | 0.164807E+10 | 0.105504E+10 | 0.120265E+10 | 0.549668E+09 | 0.652981E+09 | 0.00 | 0.00 |
May | 0.126240E+10 | 0.998677E+09 | 0.106311E+10 | 0.349601E+09 | 0.713512E+09 | 0.00 | 0.00 |
June | 0.127022E+10 | 0.788415E+09 | 0.100252E+10 | 0.340424E+09 | 0.662097E+09 | 0.00 | 0.00 |
July | 0.160605E+10 | 0.744668E+09 | 0.112100E+10 | 0.438500E+09 | 0.682500E+09 | 0.00 | 0.00 |
August | 0.183248E+10 | 0.786608E+09 | 0.119228E+10 | 0.541390E+09 | 0.650894E+09 | 0.00 | 0.00 |
September | 0.179166E+10 | 0.882470E+09 | 0.117713E+10 | 0.594324E+09 | 0.582810E+09 | 0.00 | 0.00 |
October | 0.202307E+10 | 0.100722E+10 | 0.127782E+10 | 0.788126E+09 | 0.489695E+09 | 0.00 | 0.00 |
November | 0.188452E+10 | 0.129247E+10 | 0.135845E+10 | 0.878563E+09 | 0.479886E+09 | 0.00 | 0.00 |
December | 0.208723E+10 | 0.145708E+10 | 0.147945E+10 | 0.103965E+10 | 0.439796E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202774E+11 | 0.130044E+11 | 0.145864E+11 | 0.764658E+10 | 0.693978E+10 | 0.00 | 0.00 |
Minimum of Months | 0.126240E+10 | 0.744668E+09 | 0.100252E+10 | 0.340424E+09 | 0.439796E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208723E+10 | 0.146131E+10 | 0.147945E+10 | 0.103965E+10 | 0.713512E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121722E+11 | -0.114485E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -723711287.5 | 58.99 | 0.00 | 0.00 |
February | 0.110071E+11 | -0.103522E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -654830106.9 | 58.99 | 0.00 | 0.00 |
March | 0.120910E+11 | -0.113599E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -731145330.0 | 58.99 | 0.00 | 0.00 |
April | 0.114146E+11 | -0.107376E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -676954321.3 | 58.99 | 0.00 | 0.00 |
May | 0.115203E+11 | -0.108268E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -693515143.8 | 58.99 | 0.00 | 0.00 |
June | 0.108911E+11 | -0.102374E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -653697945.5 | 58.99 | 0.00 | 0.00 |
July | 0.110577E+11 | -0.103914E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -666299801.4 | 58.99 | 0.00 | 0.00 |
August | 0.110738E+11 | -0.104080E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -665781470.9 | 58.99 | 0.00 | 0.00 |
September | 0.108233E+11 | -0.101727E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -650594156.6 | 58.99 | 0.00 | 0.00 |
October | 0.114302E+11 | -0.107557E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -674425611.4 | 58.99 | 0.00 | 0.00 |
November | 0.113779E+11 | -0.106916E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -686324414.6 | 58.99 | 0.00 | 0.00 |
December | 0.120023E+11 | -0.112809E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -721473164.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.136862E+12 | -0.128663E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.819875E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.108233E+11 | -0.114485E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -731145330.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.121722E+11 | -0.101727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -650594156.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331537E+10 | 16355.84 | 08-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223039E+10 | 9348.27 | 05-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357737E+10 | 14914.59 | 30-MAR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661505E+09 | 9545.62 | 01-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450221E+09 | 4673.59 | 14-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6123980.36 | 4296.58 | 23-JUN-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1340938.90 | 9648.64 | 04-JUL-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1382823.80 | 7672.56 | 30-AUG-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9814163.88 | 14314.12 | 29-SEP-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137035E+09 | 19622.82 | 17-OCT-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114628E+10 | 9582.58 | 05-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284349E+10 | 10423.27 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1340938.90 | 4296.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357737E+10 | 19622.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114419E+10 | 15798.85 | 08-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338808E+09 | 6796.70 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.812145E+09 | 15027.18 | 30-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36016717.98 | 5795.55 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10120644.78 | 2224.50 | 14-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108412E+09 | 4703.18 | 05-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.680697E+09 | 7643.19 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114419E+10 | 15798.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.135426E+10 | 0.127553E+10 | 15106.56 | 18-JAN-12:55 | 15106.56 | 0.00 |
February | 0.00 | 0.00 | 0.287589E+09 | 0.285094E+09 | 13215.11 | 01-FEB-12:05 | 13215.11 | 0.00 |
March | 0.00 | 0.00 | 0.596434E+09 | 0.517634E+09 | 10030.55 | 23-MAR-14:00 | 7536.43 | 0.00 |
April | 0.00 | 0.00 | 0.193241E+10 | 0.160422E+10 | 35923.66 | 27-APR-02:61 | 19193.50 | 0.00 |
May | 0.00 | 0.00 | 0.115872E+10 | 0.948438E+09 | 35923.66 | 03-MAY-02:61 | 20485.84 | 0.00 |
June | 0.00 | 0.00 | 0.435018E+10 | 0.313904E+10 | 35923.66 | 19-JUN-02:61 | 20519.83 | 0.00 |
July | 0.00 | 0.00 | 0.105592E+11 | 0.703340E+10 | 37060.05 | 30-JUL-02:62 | 17848.93 | 0.00 |
August | 0.00 | 0.00 | 0.121422E+11 | 0.794706E+10 | 37473.34 | 07-AUG-02:62 | 16309.56 | 0.00 |
September | 0.00 | 0.00 | 0.628234E+10 | 0.478013E+10 | 37777.78 | 22-SEP-02:62 | 17025.16 | 0.00 |
October | 0.00 | 0.00 | 0.815386E+10 | 0.694109E+10 | 38110.51 | 05-OCT-02:61 | 19858.32 | 0.00 |
November | 0.00 | 0.00 | 0.114000E+10 | 0.111643E+10 | 14291.71 | 19-NOV-13:00 | 14291.71 | 0.00 |
December | 0.00 | 0.00 | 0.166709E+10 | 0.165582E+10 | 15576.45 | 19-DEC-13:00 | 15576.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.496243E+11 | 0.372439E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.287589E+09 | 0.285094E+09 | 10030.55 | 7536.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121422E+11 | 0.794706E+10 | 38110.51 | 20519.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.175245E+10 | 0.153611E+10 | 27698.08 | 15-JAN-04:22 | 27698.08 | 0.00 |
February | 0.00 | 0.00 | 0.467650E+09 | 0.411928E+09 | 27698.08 | 18-FEB-03:01 | 14023.24 | 0.00 |
March | 0.00 | 0.00 | 0.897779E+09 | 0.683869E+09 | 27698.08 | 14-MAR-04:01 | 16518.47 | 0.00 |
April | 0.00 | 0.00 | 0.311609E+10 | 0.234512E+10 | 27698.08 | 09-APR-02:61 | 12890.95 | 0.00 |
May | 0.00 | 0.00 | 0.297745E+10 | 0.216975E+10 | 27698.08 | 04-MAY-03:21 | 14451.21 | 0.00 |
June | 0.00 | 0.00 | 0.745705E+10 | 0.496124E+10 | 27698.08 | 24-JUN-02:51 | 15846.63 | 0.00 |
July | 0.00 | 0.00 | 0.152333E+11 | 0.930195E+10 | 27935.84 | 23-JUL-02:11 | 11471.30 | 0.00 |
August | 0.00 | 0.00 | 0.164220E+11 | 0.980368E+10 | 29300.81 | 14-AUG-10:53 | 19676.83 | 0.00 |
September | 0.00 | 0.00 | 0.956435E+10 | 0.658204E+10 | 28366.72 | 22-SEP-02:11 | 11358.32 | 0.00 |
October | 0.00 | 0.00 | 0.112355E+11 | 0.873567E+10 | 28984.85 | 05-OCT-02:11 | 13357.32 | 0.00 |
November | 0.00 | 0.00 | 0.153219E+10 | 0.135973E+10 | 27698.08 | 20-NOV-03:01 | 13081.04 | 0.00 |
December | 0.00 | 0.00 | 0.191706E+10 | 0.185623E+10 | 27698.08 | 02-DEC-03:01 | 13306.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.725730E+11 | 0.497473E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.467650E+09 | 0.411928E+09 | 27698.08 | 11358.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164220E+11 | 0.980368E+10 | 29300.81 | 27698.08 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 4566.03 | 16800.31 | 31-JAN-13:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4571.02 | 16800.97 | 02-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 4535.13 | 16717.53 | 01-MAR-14:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4433.72 | 16437.16 | 01-APR-13:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4335.09 | 16049.02 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4243.13 | 15638.38 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4170.34 | 15336.07 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4179.79 | 15291.50 | 31-AUG-12:50 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4216.23 | 15561.45 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4307.42 | 15959.92 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4417.44 | 16359.52 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4502.58 | 16673.17 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4372.03 | ||||
Minimum of Months | 0.00 | 0.00 | 4170.34 | 15291.50 | ||
Maximum of Months | 0.00 | 0.00 | 4571.02 | 16800.97 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.291867E+10 | 0.58 | 1211.87 | 01-JAN-00:03 | 0.65 |
February | 0.262637E+10 | 0.58 | 1211.87 | 01-FEB-00:10 | 0.64 |
March | 0.289141E+10 | 0.57 | 1211.87 | 01-MAR-00:03 | 0.65 |
April | 0.283033E+10 | 0.58 | 1211.87 | 01-APR-02:62 | 0.65 |
May | 0.293976E+10 | 0.58 | 1211.87 | 01-MAY-01:00 | 0.64 |
June | 0.293460E+10 | 0.60 | 1211.87 | 01-JUN-01:55 | 0.64 |
July | 0.308526E+10 | 0.61 | 1211.87 | 01-JUL-00:30 | 0.64 |
August | 0.308613E+10 | 0.61 | 1211.87 | 01-AUG-00:16 | 0.64 |
September | 0.296130E+10 | 0.61 | 1211.87 | 01-SEP-00:40 | 0.64 |
October | 0.303382E+10 | 0.60 | 1211.87 | 01-OCT-00:14 | 0.64 |
November | 0.283469E+10 | 0.58 | 1211.87 | 01-NOV-01:00 | 0.65 |
December | 0.292049E+10 | 0.58 | 1211.87 | 01-DEC-00:10 | 0.65 |
Annual Sum or Average | 0.350628E+11 | 0.59 | |||
Minimum of Months | 0.262637E+10 | 0.57 | 1211.87 | 0.64 | |
Maximum of Months | 0.308613E+10 | 0.61 | 1211.87 | 0.65 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.482266E+10 | 0.76 | 2160.36 | 26-JAN-08:62 | 0.91 |
February | 0.435529E+10 | 0.76 | 2160.36 | 13-FEB-07:30 | 0.90 |
March | 0.482369E+10 | 0.76 | 2160.36 | 01-MAR-05:04 | 0.91 |
April | 0.466708E+10 | 0.76 | 2160.36 | 01-APR-04:12 | 0.91 |
May | 0.482336E+10 | 0.76 | 2160.36 | 01-MAY-10:53 | 0.91 |
June | 0.467743E+10 | 0.78 | 2160.36 | 01-JUN-05:45 | 0.91 |
July | 0.485482E+10 | 0.80 | 2160.36 | 01-JUL-08:13 | 0.90 |
August | 0.485987E+10 | 0.80 | 2160.36 | 01-AUG-09:22 | 0.90 |
September | 0.468853E+10 | 0.79 | 2160.36 | 01-SEP-09:36 | 0.91 |
October | 0.485510E+10 | 0.78 | 2160.36 | 01-OCT-08:57 | 0.90 |
November | 0.466708E+10 | 0.76 | 2160.36 | 01-NOV-06:10 | 0.91 |
December | 0.482275E+10 | 0.76 | 2160.36 | 01-DEC-07:15 | 0.91 |
Annual Sum or Average | 0.569177E+11 | 0.77 | |||
Minimum of Months | 0.435529E+10 | 0.76 | 2160.36 | 0.90 | |
Maximum of Months | 0.485987E+10 | 0.80 | 2160.36 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333932E+10 | 0.85 | 1479.88 | 03-JAN-08:18 | 0.95 |
February | 0.301540E+10 | 0.84 | 1479.88 | 01-FEB-08:53 | 0.95 |
March | 0.333260E+10 | 0.84 | 1479.88 | 10-MAR-12:20 | 0.95 |
April | 0.324709E+10 | 0.85 | 1479.88 | 17-APR-12:20 | 0.95 |
May | 0.336090E+10 | 0.85 | 1479.88 | 01-MAY-10:28 | 0.95 |
June | 0.328837E+10 | 0.88 | 1479.88 | 04-JUN-10:30 | 0.95 |
July | 0.343468E+10 | 0.89 | 1479.88 | 01-JUL-08:18 | 0.94 |
August | 0.344279E+10 | 0.89 | 1479.88 | 11-AUG-17:17 | 0.94 |
September | 0.330768E+10 | 0.88 | 1479.88 | 04-SEP-11:35 | 0.94 |
October | 0.341456E+10 | 0.88 | 1479.88 | 05-OCT-17:20 | 0.94 |
November | 0.324054E+10 | 0.85 | 1479.88 | 10-NOV-13:40 | 0.94 |
December | 0.333970E+10 | 0.85 | 1479.88 | 03-DEC-08:05 | 0.95 |
Annual Sum or Average | 0.397636E+11 | 0.86 | |||
Minimum of Months | 0.301540E+10 | 0.84 | 1479.88 | 0.94 | |
Maximum of Months | 0.344279E+10 | 0.89 | 1479.88 | 0.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.58 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 52.58 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 52.49 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:05 | 0.00 | 0.00 | 52.84 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 51.81 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 53.23 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 53.48 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 53.21 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.43 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 52.38 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 53.00 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 52.70 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.58 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.48 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 41.19 | 41.19 | 4566.03 | 16800.31 | 31-JAN-13:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 52.96 | 52.96 | 4571.02 | 16800.97 | 02-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.80 | 52.80 | 4535.13 | 16717.53 | 01-MAR-14:00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 52.78 | 52.78 | 4433.72 | 16437.16 | 01-APR-13:00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 41.86 | 41.86 | 4335.09 | 16049.02 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 53.48 | 53.48 | 4243.13 | 15638.38 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.61 | 53.61 | 4170.34 | 15336.07 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.38 | 53.38 | 4179.79 | 15291.50 | 31-AUG-12:50 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 53.29 | 53.29 | 4216.23 | 15561.45 | 30-SEP-12:20 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 42.41 | 42.41 | 4307.42 | 15959.92 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.86 | 52.86 | 4417.44 | 16359.52 | 30-NOV-14:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 52.66 | 52.66 | 4502.58 | 16673.17 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 4372.03 | ||||||
Minimum of Months | 0.00 | 0.00 | 41.19 | 41.19 | 4170.34 | 15291.50 | ||
Maximum of Months | 0.00 | 0.00 | 53.61 | 53.61 | 4571.02 | 16800.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.524942E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.444687E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.501409E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.527803E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.519594E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.603179E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.801461E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.846132E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.662781E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.735644E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.502653E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.535158E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.720544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.444687E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.846132E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.387832E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.316036E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.361217E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.420478E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.428596E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.551989E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.777337E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.807224E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.613281E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.672053E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.371351E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.393791E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.610119E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.316036E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.807224E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.482266E+10 | 0.135426E+10 | 0.331537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435529E+10 | 0.287589E+09 | 0.223039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482369E+10 | 0.596434E+09 | 0.357737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466708E+10 | 0.193241E+10 | 0.661505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482336E+10 | 0.115872E+10 | 0.450221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.467743E+10 | 0.435018E+10 | 6123980.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.485482E+10 | 0.105592E+11 | 1340938.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485987E+10 | 0.121422E+11 | 1382823.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468853E+10 | 0.628234E+10 | 9814163.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485510E+10 | 0.815386E+10 | 0.137035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466708E+10 | 0.114000E+10 | 0.114628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.482275E+10 | 0.166709E+10 | 0.284349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569177E+11 | 0.496243E+11 | 0.143803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.435529E+10 | 0.287589E+09 | 1340938.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485987E+10 | 0.121422E+11 | 0.357737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333932E+10 | 0.175245E+10 | 0.114419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301540E+10 | 0.467650E+09 | 0.338808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333260E+10 | 0.897779E+09 | 0.812145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324709E+10 | 0.311609E+10 | 36016717.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336090E+10 | 0.297745E+10 | 10120644.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.328837E+10 | 0.745705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343468E+10 | 0.152333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344279E+10 | 0.164220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330768E+10 | 0.956435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341456E+10 | 0.112355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324054E+10 | 0.153219E+10 | 0.108412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333970E+10 | 0.191706E+10 | 0.680697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397636E+11 | 0.725730E+11 | 0.313039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301540E+10 | 0.467650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344279E+10 | 0.164220E+11 | 0.114419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.482266E+10 | 0.00 | 0.00 | 0.00 | 0.426763E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435529E+10 | 0.00 | 0.00 | 0.00 | 91578243.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482369E+10 | 0.00 | 0.00 | 0.00 | 0.190406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466708E+10 | 0.00 | 0.00 | 0.00 | 0.610949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.482336E+10 | 0.00 | 0.00 | 0.00 | 0.372581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.467743E+10 | 0.00 | 0.00 | 0.00 | 0.135436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.485482E+10 | 0.00 | 0.00 | 0.00 | 0.315979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.485987E+10 | 0.00 | 0.00 | 0.00 | 0.360145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.468853E+10 | 0.00 | 0.00 | 0.00 | 0.193928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485510E+10 | 0.00 | 0.00 | 0.00 | 0.250133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466708E+10 | 0.00 | 0.00 | 0.00 | 0.359442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.482275E+10 | 0.00 | 0.00 | 0.00 | 0.528831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569177E+11 | 0.00 | 0.00 | 0.00 | 0.151368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.435529E+10 | 0.00 | 0.00 | 0.00 | 91578243.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485987E+10 | 0.00 | 0.00 | 0.00 | 0.360145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.333932E+10 | 0.00 | 0.00 | 0.00 | 0.539002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.301540E+10 | 0.00 | 0.00 | 0.00 | 0.144969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.333260E+10 | 0.00 | 0.00 | 0.00 | 0.279578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324709E+10 | 0.00 | 0.00 | 0.00 | 0.957683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336090E+10 | 0.00 | 0.00 | 0.00 | 0.925054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.328837E+10 | 0.00 | 0.00 | 0.00 | 0.223152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343468E+10 | 0.00 | 0.00 | 0.00 | 0.433870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344279E+10 | 0.00 | 0.00 | 0.00 | 0.462945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330768E+10 | 0.00 | 0.00 | 0.00 | 0.282514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341456E+10 | 0.00 | 0.00 | 0.00 | 0.330597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324054E+10 | 0.00 | 0.00 | 0.00 | 0.472969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333970E+10 | 0.00 | 0.00 | 0.00 | 0.598209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.397636E+11 | 0.00 | 0.00 | 0.00 | 0.212482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301540E+10 | 0.00 | 0.00 | 0.00 | 0.144969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344279E+10 | 0.00 | 0.00 | 0.00 | 0.462945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570062E+10 | 332054.48 | 0.00 | 11241356.52 | 0.00 | 0.340278E+10 | 0.390599E+10 | 0.00 | 4.53 |
February | 0.647122E+10 | 0.00 | 0.00 | 5713499.11 | 0.00 | 0.226024E+10 | 0.261225E+10 | 0.00 | 4.12 |
March | 0.700215E+10 | 0.00 | 0.00 | 6780980.07 | 0.00 | 0.349451E+10 | 0.240810E+10 | 0.00 | 4.26 |
April | 0.620460E+10 | 11171979.07 | 0.00 | 16246489.51 | 0.00 | 0.383602E+09 | 0.510042E+10 | 0.00 | 5.43 |
May | 0.608331E+10 | 70928.29 | 0.00 | 16239368.76 | 0.00 | 0.159550E+09 | 0.618650E+10 | 0.00 | 5.55 |
June | 0.363816E+10 | 29736056.57 | 0.00 | 25571089.23 | 0.00 | 84026.96 | 0.700148E+10 | 0.00 | 6.76 |
July | 0.132787E+10 | 0.590109E+09 | 0.00 | 33820608.52 | 0.00 | 271132.62 | 0.779082E+10 | 0.00 | 7.32 |
August | 0.116836E+10 | 0.724535E+09 | 0.00 | 34336834.14 | 0.00 | 283519.64 | 0.723145E+10 | 0.00 | 7.29 |
September | 0.263307E+10 | 0.258165E+09 | 209567.57 | 30711637.63 | 0.00 | 502670.39 | 0.789775E+10 | 14209.50 | 6.92 |
October | 0.294194E+10 | 0.499153E+09 | 0.00 | 27982664.95 | 0.00 | 60105834.15 | 0.755755E+10 | 0.00 | 6.87 |
November | 0.684869E+10 | 2867879.04 | 0.00 | 12851116.52 | 0.00 | 0.720939E+09 | 0.452517E+10 | 0.00 | 4.68 |
December | 0.630564E+10 | 21524.14 | 0.00 | 13266118.36 | 0.00 | 0.265599E+10 | 0.390139E+10 | 0.00 | 4.89 |
Annual Sum or Average | 0.563256E+11 | 0.211616E+10 | 209567.57 | 0.234762E+09 | 0.00 | 0.131389E+11 | 0.661189E+11 | 14209.50 | 5.73 |
Minimum of Months | 0.116836E+10 | 0.00 | 0.00 | 5713499.11 | 0.00 | 84026.96 | 0.240810E+10 | 0.00 | 4.12 |
Maximum of Months | 0.700215E+10 | 0.724535E+09 | 209567.57 | 34336834.14 | 0.00 | 0.349451E+10 | 0.789775E+10 | 14209.50 | 7.32 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223919E+11 | 0.00 | 0.00 | 29840251.54 | 0.00 | 0.00 | 0.148860E+11 | 0.00 | 10.09 |
February | 0.196887E+11 | 0.00 | 0.00 | 20480024.80 | 0.00 | 0.00 | 0.141585E+11 | 0.00 | 10.05 |
March | 0.244320E+11 | 0.00 | 0.00 | 23028954.89 | 0.00 | 0.00 | 0.131596E+11 | 0.00 | 10.05 |
April | 0.139698E+11 | 0.00 | 0.00 | 53708026.60 | 0.00 | 0.00 | 0.198238E+11 | 0.00 | 10.40 |
May | 0.124772E+11 | 0.00 | 0.00 | 60774274.30 | 0.00 | 0.00 | 0.230030E+11 | 0.00 | 10.47 |
June | 0.499986E+10 | 1431.26 | 0.00 | 85197546.17 | 0.00 | 0.00 | 0.247145E+11 | 0.00 | 10.87 |
July | 0.249143E+10 | 0.310593E+09 | 0.00 | 0.105987E+09 | 0.00 | 0.00 | 0.214859E+11 | 0.00 | 11.20 |
August | 0.191261E+10 | 0.383454E+09 | 0.00 | 0.106871E+09 | 0.00 | 0.00 | 0.208000E+11 | 0.00 | 11.26 |
September | 0.363030E+10 | 0.195573E+09 | 0.00 | 89903814.10 | 0.00 | 0.00 | 0.242152E+11 | 0.00 | 10.97 |
October | 0.494159E+10 | 0.264963E+09 | 0.00 | 85656047.68 | 0.00 | 0.00 | 0.227707E+11 | 0.00 | 10.93 |
November | 0.148424E+11 | 0.00 | 0.00 | 38856696.35 | 0.00 | 0.00 | 0.206936E+11 | 0.00 | 10.18 |
December | 0.204974E+11 | 0.00 | 0.00 | 32442879.39 | 0.00 | 0.00 | 0.163115E+11 | 0.00 | 10.14 |
Annual Sum or Average | 0.146275E+12 | 0.115459E+10 | 0.00 | 0.732746E+09 | 0.00 | 0.00 | 0.236022E+12 | 0.00 | 10.56 |
Minimum of Months | 0.191261E+10 | 0.00 | 0.00 | 20480024.80 | 0.00 | 0.00 | 0.131596E+11 | 0.00 | 10.05 |
Maximum of Months | 0.244320E+11 | 0.383454E+09 | 0.00 | 0.106871E+09 | 0.00 | 0.00 | 0.247145E+11 | 0.00 | 11.26 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.321842E+11 | 0.117573E+11 | 0.714939E+11 | 0.187554E+10 | 0.294477E+11 |
February | 0.390076E+11 | 0.110782E+11 | 0.641463E+11 | 0.110616E+10 | 0.237562E+11 |
March | 0.541530E+11 | 0.130254E+11 | 0.716014E+11 | 0.131082E+10 | 0.285984E+11 |
April | 0.731190E+11 | 0.105911E+11 | 0.621272E+11 | 0.336734E+10 | 0.360726E+11 |
May | 0.769104E+11 | 0.109926E+11 | 0.648956E+11 | 0.409736E+10 | 0.353903E+11 |
June | 0.768971E+11 | 0.888360E+10 | 0.554354E+11 | 0.462926E+10 | 0.439656E+11 |
July | 0.833007E+11 | 0.636250E+10 | 0.452444E+11 | 0.461530E+10 | 0.641458E+11 |
August | 0.767533E+11 | 0.588206E+10 | 0.428385E+11 | 0.408260E+10 | 0.674454E+11 |
September | 0.591798E+11 | 0.750454E+10 | 0.519262E+11 | 0.481998E+10 | 0.494438E+11 |
October | 0.418715E+11 | 0.663543E+10 | 0.512010E+11 | 0.505097E+10 | 0.532867E+11 |
November | 0.353370E+11 | 0.106159E+11 | 0.668661E+11 | 0.234528E+10 | 0.284071E+11 |
December | 0.294204E+11 | 0.112304E+11 | 0.700977E+11 | 0.236057E+10 | 0.297027E+11 |
Annual Sum or Average | 0.678134E+12 | 0.114559E+12 | 0.717874E+12 | 0.396612E+11 | 0.489662E+12 |
Minimum of Months | 0.294204E+11 | 0.588206E+10 | 0.428385E+11 | 0.110616E+10 | 0.237562E+11 |
Maximum of Months | 0.833007E+11 | 0.130254E+11 | 0.716014E+11 | 0.505097E+10 | 0.674454E+11 |