Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:29:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1311.83 | 5646.09 | 5646.09 |
Net Site Energy | 1311.83 | 5646.09 | 5646.09 |
Total Source Energy | 2829.26 | 12177.08 | 12177.08 |
Net Source Energy | 2829.26 | 12177.08 | 12177.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 231.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 157.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 57.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 675.58 | 636.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 231.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 64.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 157.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 231.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 64.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 157.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 57.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1273.51 | 684.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1391.90 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2907.69 | 2738.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1273.51 | 684.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1391.90 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2907.69 | 2738.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 675.581 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 675.581 | 100.00 |
Total On-Site and Utility Electric Sources | 675.581 | 100.00 |
Total Electricity End Uses | 675.581 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 866.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6816.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 6.7540 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 10.4679 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.7540 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.4679 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6110 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-JUL-11:20 | 17-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18883.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13187.23 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3666.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23294.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2663.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 39758.48 | 46277.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18883.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12159.73 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3666.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 23294.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1393.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 734.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 93.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 842.91 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 170.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 181.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2139.57 | 689.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 366.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 873.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 734.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 780.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9208.65 | 2968.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 366.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 873.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 734.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 780.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 9208.65 | 2968.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.05 |
KITCHEN DIRECT AIR | 1.27 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 1.00 | 0.999949 | 2.05 |
PSZ-AC_2:2 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.00 | 1.27 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.05 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.27 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.05 | 2194.67 |
PSZ-AC_2:2_ADDAQ FAN | 1.27 | 1401.63 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.05 | 2.05 | 2.05 | 1.35 | 50931.31 | 53062.77 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 0.835538 | 31436.98 | 49200.29 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.05 | 1.03 | 1.37 | 50931.31 | 25465.65 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.27 | 0.632984 | 0.843980 | 31436.98 | 15718.49 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53062.77 |
PSZ-AC_2:2 HEATING COIL | 49200.29 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 6.754 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.541 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 10.468 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.547 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 784.620 | 6.754 | 8.963 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 784.620 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1216.076 | 10.468 | 193.849 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1216.076 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.5032_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.4954E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1672E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3657E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0477E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2345E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1757E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.9595E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.8974E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1785E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.0884E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.4430E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.3375E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.5485E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.4909E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0717E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0717E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.5791E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.2768E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.0406E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1014E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.0867E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0014E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8988E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.9596E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 23192.84010 | 27831.40812 | 1.70908 | 2.05090 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 1801.22567 | 2161.47081 | 7.57863E-002 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 8.70000 | 6.99286E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 17221.68577 | 20666.02293 | 1.05497 | 1.26597 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 8.70000 | 6.99286E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 32098.09 | 2.05100 | 2.05100 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 15738.84 | 0.41606 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 29304.63 | 1.26597 | 1.26597 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 43175.09 | 1.14133 | 1.14133 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.05090 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26597 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05090 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05090 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05090 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05090 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05100 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.05100 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99995 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.26597 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26597 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.26597 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26597 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.26597 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.26597 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.05100 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.26597 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05100 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.05100 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2194.67127 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.05100 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.05100 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.05100 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35366 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.05100 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02550 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36733 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 50931.31000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25465.65500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 50931.31000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53062.77423 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53062.77423 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.26597 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.26597 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1401.62654 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.26597 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.26597 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.26597 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83554 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.26597 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63298 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84398 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31436.98000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15718.49000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31436.98000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 49200.28632 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 49200.28632 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 49473.5 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30537.2 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | N/A | 2.861 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | N/A | 2.861 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | N/A | 2.861 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 4.5391409834E-002 | 0.2052770485 | Pass | Pass | 5.7849071978E-002 | 0.1567577159 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1795141704 | 0.5386694410 | Pass | Pass | 0.1917145185 | 0.5871198708 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4256566735 | 0.4441745482 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 598.30 | -74.9 | -208.9 | 9.79 | 1529.98 | 1854.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5032_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5032_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.861 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.7540 | 116.17 | 784.62 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 69.40 | 0.0000 | Y | 10.22 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.4679 | 116.17 | 1216.08 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 19.16 |
Interior Lighting Total | 8.6110 | 232.34 | 2000.70 | 29.39 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 784.62 | 298.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 784.62 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 164.64 | AstronomicalClock | - | 48.82 | 48.82 | 1.51 | |
EXTERIOR_LIGHTS_B | 1845.07 | AstronomicalClock | - | 83.82 | 73.32 | 25.40 | |
Exterior Lighting Total | 2009.71 | 26.90 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 50931.31 | 35706.92 | 15224.39 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31436.98 | 22039.84 | 9397.14 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 49473.5 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 30537.2 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53062.77 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 49200.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.05 | 2194.67 | 1070.05 | 1.00 | 1.31 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.27 | 1401.63 | 1107.16 | 1.00 | 1.35 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 23192.84 | 27831.41 | 239.57 | 1.709 | 2.051 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.86 | 0.01207 | 33.13 | 0.01717 | 0.416 | 0.00 |
KITCHEN | 17221.69 | 20666.02 | 177.89 | 1.055 | 1.266 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01018 | 32.60 | 0.01717 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 1801.23 | 2161.47 | 18.61 | 0.076 | 0.416 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00768 | 8.70 | 0.00699 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 28.10 | 0.00600 | 8.70 | 0.00699 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 0.42 | 0.42 | 2.0510 | 2.0509 | 2.0510 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.27 | 1.27 | 1.14 | 1.14 | 1.2660 | 1.2660 | 1.2660 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 50931.310 | 35706.923 | 2.051000 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 25465.65 | 14062.93 | 1.367333 | 25.75 | 20.58 | 0.01310036 | 11.94 | 11.73 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.4283 | 23.86 | 0.01206545 | 65.0548 | 23190.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53062.774 | 53062.774 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 53062.77 | 53062.77 | 2.051004 | 18.59 | 13.59 | 0.00765250 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.2855 | 20.93 | 0.00782037 | 50.7173 | 987.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31436.980 | 22039.838 | 1.265970 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 15718.49 | 7928.78 | 0.843980 | 31.95 | 24.59 | 0.01647875 | 11.91 | 11.72 | 0.00850000 | 32.60 | 0.01716606 | 25.17 | 135.2323 | 26.10 | 0.01018465 | 48.1978 | 17221.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 49200.286 | 49200.286 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 49200.29 | 49200.29 | 1.265967 | 7.84 | 7.84 | 0.00689492 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 90.1551 | 28.10 | 0.00599807 | 25.4115 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 50931.310 | 35706.923 | 2.051000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.1929 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.051004 | 2.46682241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 25465.65 | 14062.93 | 1.0000 | 1.64454504 | 1.367333 | 25.75 | 20.58 | 0.01310036 | 59263.9 | 11.94 | 11.73 | 0.00850000 | 33439.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25465.65 | 33.20 | 0.01716721 | 25.32 | 0.41605618 | 30.4283 | 23.85 | 0.01206545 | 23.86 | 0.01206545 | 65.0548 | 23190.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53062.774 | 53062.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.051004 | 2.46682241 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 53062.77 | 53062.77 | 1.0000 | 2.46682241 | 2.051004 | 18.59 | 13.59 | 0.00765250 | 38085.4 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53062.77 | 8.70 | 0.00699286 | 8.70 | 0.41605618 | 20.2855 | 21.11 | 0.00782037 | 20.93 | 0.00782037 | 50.7173 | 987.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31436.980 | 22039.838 | 1.265970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1035.4732 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.265967 | 1.52262792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 15718.49 | 7928.78 | 1.0000 | 1.01508761 | 0.843980 | 31.95 | 24.59 | 0.01647875 | 74298.9 | 11.91 | 11.72 | 0.00850000 | 33414.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15718.49 | 32.60 | 0.01716606 | 25.17 | 1.14133354 | 135.2323 | 26.06 | 0.01018465 | 26.10 | 0.01018465 | 48.1978 | 17221.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 49200.286 | 49200.286 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.265967 | 1.52262792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 49200.29 | 49200.29 | 1.0000 | 1.52262792 | 1.265967 | 7.84 | 7.84 | 0.00689492 | 25225.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49200.29 | 8.70 | 0.00699286 | 8.70 | 1.14133354 | 90.1551 | 0.00 | 0.00599807 | 28.10 | 0.00599807 | 25.4115 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6666.33 | 5089.50 | 4691.33 |
KITCHEN | 7097.33 | 6864.83 | 6815.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7097.83 | 7160.50 | 6816.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 22.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1214.17 | 0.00 | 866.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1236.17 | 0.00 | 866.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.328 | 4.141 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.303 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.172 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.345 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11022402.81 | 0.00 | 11022402.81 | 10355640.28 | 21378043.09 | 13120747.55 | 1453.46 | 7306.54 | 0.00 | 295.24 |
KITCHEN | 26842972.98 | 0.00 | 26842972.98 | 124213.67 | 26967186.65 | 35993094.65 | 6350.02 | 2393.68 | 16.30 | 1093.87 |
Total Facility | 37865375.78 | 0.00 | 37865375.78 | 10479853.95 | 48345229.73 | 49113842.20 | 6365.96 | 7307.40 | 16.30 | 1180.96 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3984 | 0.8145 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9819 | 0.0000 | 0.9819 | 0.0030 | 0.9849 | 1.1413 | 4805.34 | 2381.66 | 0.00 |
Total Facility | 1.3979 | 0.0000 | 1.3979 | 0.4014 | 1.7994 | 1.5574 | 4805.34 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15944707.11 | 0.00 | 15944707.11 | 13120747.55 | 1444.98 | 1.22 | 7313.80 | 295.18 |
PSZ-AC_2:2 | 38830257.29 | 0.00 | 38830257.29 | 35993094.65 | 1392.95 | 2.90 | 7364.14 | 1093.87 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6019 | 0.0000 | 0.6019 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.4203 | 0.0000 | 1.4203 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 175.71 | 0.00 | 7306.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 3979.63 | 4301.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.6019 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.5683 | 1.3214 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
Electricity:Building | 303.48 | 2332.77 | 01-JAN-01:10 | 18740.18 | 02-JAN-11:10 |
Electricity:Zone:DINING | 80.64 | 381.62 | 01-JAN-01:10 | 4344.76 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 295.54 | 2196.49 | 01-JAN-01:10 | 15446.13 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.39 | 268.27 | 01-JAN-01:10 | 1609.61 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 10.22 | 110.28 | 01-JAN-01:10 | 661.67 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.39 | 268.27 | 01-JAN-01:10 | 1609.61 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 29.39 | 268.27 | 01-JAN-01:10 | 1609.61 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.22 | 110.28 | 01-JAN-01:10 | 661.67 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.39 | 268.27 | 01-JAN-01:10 | 1609.61 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 222.84 | 1951.15 | 01-JAN-01:10 | 14395.42 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.74 | 1656.87 | 01-JAN-01:10 | 10153.43 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 57.25 | 910.96 | 03-FEB-23:30 | 4370.28 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 49.30 | 825.19 | 03-FEB-23:30 | 2586.77 | 19-SEP-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.34 | 0.00 | 01-JAN-11:10 | 1510.54 | 19-SEP-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 32.96 | 774.32 | 04-FEB-06:00 | 1076.23 | 01-JAN-02:00 |
ElectricityPurchased:Facility | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
ElectricityPurchased:Plant | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
Cogeneration:ElectricityPurchased | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
General:Cogeneration:ElectricityPurchased | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
ElectricityNet:Plant | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
Cogeneration:ElectricityNet | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
General:Cogeneration:ElectricityNet | 675.58 | 4684.67 | 04-FEB-01:10 | 39758.48 | 14-JUL-11:20 |
Electricity:HVAC | 295.89 | 0.00 | 01-JAN-01:10 | 22830.51 | 27-JUL-17:10 |
Fans:Electricity | 64.07 | 0.00 | 01-JAN-01:10 | 3667.40 | 14-JUL-11:30 |
General:Fans:Electricity | 64.07 | 0.00 | 01-JAN-01:10 | 3667.40 | 14-JUL-11:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 231.83 | 0.00 | 01-JAN-00:10 | 19205.81 | 27-JUL-17:10 |
General:Cooling:Electricity | 231.83 | 0.00 | 01-JAN-00:10 | 19205.81 | 27-JUL-17:10 |
ExteriorLights:Electricity | 26.90 | 0.00 | 01-JAN-07:20 | 2009.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 26.90 | 0.00 | 01-JAN-07:20 | 2009.71 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 636.25 | 2560.65 | 01-JAN-01:10 | 46277.62 | 17-JAN-13:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1.69 | 0.00 | 01-JAN-00:10 | 19801.70 | 04-FEB-07:10 |
Heating:NaturalGas | 1.69 | 0.00 | 01-JAN-00:10 | 19801.70 | 04-FEB-07:10 |
General:Heating:NaturalGas | 1.69 | 0.00 | 01-JAN-00:10 | 19801.70 | 04-FEB-07:10 |
NaturalGas:Plant | 157.40 | 722.00 | 01-JAN-01:10 | 23294.47 | 17-JAN-13:20 |
WaterSystems:NaturalGas | 157.40 | 722.00 | 01-JAN-01:10 | 23294.47 | 17-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 157.40 | 722.00 | 01-JAN-01:10 | 23294.47 | 17-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1722.89 | 3075.41 | 04-FEB-01:10 | 123457.21 | 22-AUG-13:00 |
EnergyTransfer:Building | 556.73 | 1537.70 | 04-FEB-01:10 | 36437.31 | 07-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 372.01 | 1537.70 | 04-FEB-01:10 | 21914.80 | 15-DEC-05:10 |
Refrigeration:EnergyTransfer | 162.38 | 2971.12 | 03-FEB-23:30 | 7834.84 | 02-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.19 | 1485.56 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 81.19 | 1485.56 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.19 | 1485.56 | 03-FEB-23:30 | 3917.42 | 02-JAN-11:40 |
EnergyTransfer:Plant | 182.17 | 1537.70 | 04-FEB-01:10 | 16090.59 | 23-JAN-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.52 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.67 | 1332.96 | 04-FEB-06:00 | 2238.70 | 01-JAN-02:00 |
EnergyTransfer:Zone:DINING | 184.71 | 0.00 | 01-JAN-01:10 | 19142.37 | 28-JUL-17:10 |
Heating:EnergyTransfer | 0.45 | 0.00 | 01-JAN-00:10 | 6266.05 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:DINING | 0.44 | 0.00 | 01-JAN-00:10 | 6266.05 | 04-FEB-07:10 |
General:Heating:EnergyTransfer | 0.45 | 0.00 | 01-JAN-00:10 | 6266.05 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.44 | 0.00 | 01-JAN-00:10 | 6266.05 | 04-FEB-07:10 |
Cooling:EnergyTransfer | 475.09 | 0.00 | 01-JAN-01:10 | 32519.89 | 07-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 184.28 | 0.00 | 01-JAN-01:10 | 19142.37 | 28-JUL-17:10 |
General:Cooling:EnergyTransfer | 475.09 | 0.00 | 01-JAN-01:10 | 32519.89 | 07-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 184.28 | 0.00 | 01-JAN-01:10 | 19142.37 | 28-JUL-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 525.15 | 10-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 525.15 | 10-SEP-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 290.81 | 0.00 | 01-JAN-01:10 | 17997.38 | 15-DEC-05:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 290.81 | 0.00 | 01-JAN-01:10 | 17997.38 | 15-DEC-05:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
PlantLoopHeatingDemand:Plant | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
EnergyTransfer:HVAC | 983.99 | 0.00 | 01-JAN-00:10 | 79745.52 | 14-JUL-11:20 |
HeatingCoils:EnergyTransfer | 1.35 | 0.00 | 01-JAN-00:10 | 15841.36 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 982.63 | 0.00 | 01-JAN-00:10 | 79745.52 | 14-JUL-11:20 |
WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13545.30 | 21-JAN-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.440 | -184.275 | 0.000 | 0.000 | 65.380 | 10.222 | 52.814 | 22.326 | 0.000 | 32.283 | 18.312 | 0.000 | -4.136 | 0.000 | -13.366 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.010 | -290.809 | 0.000 | 0.000 | 3.887 | 19.164 | 201.334 | 0.000 | 0.000 | 0.093 | 66.945 | 0.000 | 0.000 | 0.000 | -0.624 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.784 | 12.498 | 0.000 | 0.000 | 0.000 | -16.282 | -0.001 |
Total Facility | 0.000 | 0.000 | 0.449 | -475.084 | 0.000 | 0.000 | 69.266 | 29.385 | 254.148 | 22.326 | 0.000 | 36.161 | 97.755 | 0.000 | -4.136 | 0.000 | -30.272 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 01-SEP-04:01 | 0.00 | 0.00 | 0.00 | -22142.37 | 0.00 | 0.00 | 270.27 | 147.04 | 1221.06 | 0.00 | 0.00 | 4.45 | 20610.43 | 0.00 | -110.88 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | -47790.89 | 0.00 | 0.00 | 7.68 | 210.66 | 4933.19 | 0.00 | 0.00 | 0.00 | 42742.49 | 0.00 | -0.00 | 0.00 | -103.13 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JAN-05:01 | 0.00 | 0.00 | 0.00 | -54277.33 | 0.00 | 0.00 | 300.74 | 357.70 | 6154.25 | 0.00 | 0.00 | 607.99 | 47630.12 | 0.00 | -767.61 | 0.00 | -5.87 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-FEB-07:10 | 0.00 | 0.00 | 6267.78 | 0.00 | 0.00 | 0.00 | 3598.56 | 220.56 | 1526.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -656.30 | 0.00 | -10391.89 | -565.03 |
KITCHEN | 10-SEP-23:01 | 0.00 | 0.00 | 3022.80 | 0.00 | 0.00 | 0.00 | 18.55 | 157.99 | 2003.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5203.27 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-07:10 | -10857.93 | 10857.93 | 6267.78 | -10857.93 | 0.00 | 0.00 | 3883.16 | 536.54 | 7435.94 | 0.00 | 0.00 | 356.26 | 3500.18 | 0.00 | -656.30 | 0.00 | -10465.62 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0509 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0510 | 0.2029 | 1.0000 | Not calculated | 0.4161 | 0.2029 | ||
PSZ-AC_2:2 | 1.2660 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2660 | 0.1195 | 1.0000 | Not calculated | 0.1513 | 0.1195 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0509 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0509 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2029 | ||
PSZ-AC_2:2 | 1.2660 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2660 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1195 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0509 | 2.0509 | 2.0509 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2660 | 1.2660 | 1.2660 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0509 | 2.0510 | 2.0509 | 2.0509 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2660 | 1.2660 | 1.2660 | 1.2660 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0509 | 2.0509 | 2.0509 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2660 | 1.2660 | 1.2660 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0509 | 2.0509 | 2.0509 | 2.0509 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2660 | 1.2660 | 1.2660 | 1.2660 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 866.50 |
Number of hours not met | 866.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.69 | 19801.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 231.83 | 19205.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.39 | 1609.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 26.90 | 2009.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 64.07 | 3667.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 157.40 | 23294.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.34 | 1510.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.96 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 323.40 | 675.58 |
Natural Gas | 477.16 | 636.25 |
Additional | 0.00 | 0.00 |
Total | 800.56 | 1311.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.47 |
Space Heating | 0.00 |
Space Cooling | 997.78 |
Fans (All) | 275.74 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1145.52 |
Miscellaneous (All) | 2907.69 |
Subtotal | 2907.69 |
Natural Gas [MJ/m2] | |
Space Heating | 7.28 |
Service Water Heating | 677.45 |
Miscellaneous (All) | 2738.40 |
Subtotal | 2738.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.24 |
Space Heating | 0.13 |
Space Cooling | 17.67 |
Fans (All) | 4.88 |
Service Water Heating | 12.00 |
Receptacle Equipment | 56.66 |
Miscellaneous | 6.41 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7910.67 | 848.00 | 1.33 | 0.00 | 0.00 |
KITCHEN | 5801.67 | 2593.00 | 365.33 | 0.00 | 0.00 |
ATTIC | 4750.00 | 769.50 | 872.00 | 1263.17 | 1105.33 |
Min | 4750.00 | 769.50 | 1.33 | 0.00 | 0.00 |
Max | 7910.67 | 2593.00 | 872.00 | 1263.17 | 1105.33 |
Average | 6154.11 | 1403.50 | 412.89 | 421.06 | 368.44 |
Sum | 18462.33 | 4210.50 | 1238.67 | 1263.17 | 1105.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254183.67 | 536.67 | 4.67 | 0.00 | 0.00 |
KITCHEN | 12917.83 | 3337.50 | 2.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254183.67 | 3337.50 | 4.67 | 0.00 | 0.00 |
Average | 89033.83 | 1291.39 | 2.44 | 0.00 | 0.00 |
Sum | 267101.50 | 3874.17 | 7.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 2598.67 | 6161.17 | 0.17 | 0.00 | 0.00 |
KITCHEN | 787.67 | 7915.67 | 56.67 | 0.00 | 0.00 |
ATTIC | 2633.50 | 3213.17 | 708.17 | 649.67 | 1555.50 |
Min | 787.67 | 3213.17 | 0.17 | 0.00 | 0.00 |
Max | 2633.50 | 7915.67 | 708.17 | 649.67 | 1555.50 |
Average | 2006.61 | 5763.33 | 255.00 | 216.56 | 518.50 |
Sum | 6019.83 | 17290.00 | 765.00 | 649.67 | 1555.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 83885.67 | 170838.67 | 0.67 | 0.00 | 0.00 |
KITCHEN | 1459.83 | 14798.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 83885.67 | 170838.67 | 0.67 | 0.00 | 0.00 |
Average | 28448.50 | 61878.94 | 0.22 | 0.00 | 0.00 |
Sum | 85345.50 | 185636.83 | 0.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:32
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.969823E+10 | 18141.50 | 16-JAN-05:01 | 16.02 | 15.05 | 0.526394E+10 | 4681.82 | 07-JAN-19:10 | 16.02 | 15.05 |
February | 0.102521E+11 | 21412.50 | 17-FEB-05:01 | 22.80 | 20.79 | 0.481771E+10 | 4681.82 | 11-FEB-19:10 | 22.80 | 20.79 |
March | 0.117128E+11 | 21680.63 | 31-MAR-04:01 | 22.70 | 19.07 | 0.539457E+10 | 4681.85 | 11-MAR-19:49 | 22.70 | 19.07 |
April | 0.140702E+11 | 21565.30 | 28-APR-04:01 | 22.30 | 18.21 | 0.525500E+10 | 4682.11 | 01-APR-18:00 | 22.30 | 18.21 |
May | 0.174810E+11 | 21673.54 | 16-MAY-04:01 | 25.00 | 21.55 | 0.544501E+10 | 4681.99 | 20-MAY-18:10 | 28.03 | 21.49 |
June | 0.184773E+11 | 21860.41 | 02-JUN-04:01 | 26.02 | 22.91 | 0.529531E+10 | 4682.26 | 24-JUN-18:10 | 26.20 | 23.51 |
July | 0.203227E+11 | 21495.65 | 07-JUL-04:01 | 23.30 | 21.44 | 0.541494E+10 | 4682.21 | 22-JUL-18:10 | 26.02 | 21.82 |
August | 0.199773E+11 | 19913.28 | 11-AUG-04:01 | 27.20 | 23.94 | 0.547603E+10 | 4682.08 | 19-AUG-18:49 | 29.40 | 24.55 |
September | 0.192128E+11 | 22143.30 | 01-SEP-04:01 | 26.10 | 21.82 | 0.526335E+10 | 4682.17 | 30-SEP-18:00 | 28.90 | 23.70 |
October | 0.182472E+11 | 22090.93 | 17-OCT-04:01 | 24.32 | 19.13 | 0.541619E+10 | 4682.14 | 14-OCT-18:10 | 24.32 | 19.13 |
November | 0.142935E+11 | 22036.76 | 21-NOV-05:01 | 25.60 | 21.37 | 0.521110E+10 | 4682.61 | 18-NOV-19:49 | 25.60 | 21.37 |
December | 0.105305E+11 | 21945.15 | 01-DEC-05:01 | 22.38 | 18.19 | 0.529810E+10 | 4682.66 | 09-DEC-19:40 | 25.00 | 22.52 |
Annual Sum or Average | 0.184276E+12 | 0.635513E+11 | ||||||||
Minimum of Months | 0.969823E+10 | 18141.50 | 16.02 | 15.05 | 0.481771E+10 | 4681.82 | 16.02 | 15.05 | ||
Maximum of Months | 0.203227E+11 | 22143.30 | 27.20 | 23.94 | 0.547603E+10 | 4682.66 | 29.40 | 24.55 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234228E+11 | 46819.20 | 27-JAN-04:21 | 14.15 | 8.48 | 0.785403E+10 | 5138.46 | 18-JAN-11:39 | 14.15 | 8.48 |
February | 0.212408E+11 | 38886.24 | 22-FEB-05:01 | 12.12 | 10.32 | 0.709651E+10 | 5138.46 | 06-FEB-11:09 | 12.12 | 10.32 |
March | 0.236755E+11 | 41114.49 | 16-MAR-04:01 | 7.62 | 4.99 | 0.786241E+10 | 5150.08 | 14-MAR-10:50 | 7.62 | 4.99 |
April | 0.235325E+11 | 32121.84 | 18-APR-03:31 | 19.60 | 15.28 | 0.761085E+10 | 5149.93 | 13-APR-10:00 | 19.60 | 15.28 |
May | 0.251291E+11 | 28828.02 | 09-MAY-04:01 | 24.32 | 19.60 | 0.786766E+10 | 5160.67 | 31-MAY-10:00 | 32.80 | 24.33 |
June | 0.246514E+11 | 24260.04 | 13-JUN-04:01 | 23.90 | 22.65 | 0.762543E+10 | 5177.07 | 06-JUN-10:50 | 23.90 | 22.65 |
July | 0.257140E+11 | 26495.45 | 07-JUL-04:01 | 23.30 | 21.44 | 0.788178E+10 | 5189.35 | 14-JUL-10:50 | 31.52 | 26.32 |
August | 0.256306E+11 | 22633.82 | 14-AUG-04:01 | 22.88 | 22.36 | 0.788542E+10 | 5184.18 | 04-AUG-10:50 | 22.88 | 22.36 |
September | 0.249606E+11 | 26092.30 | 01-SEP-04:01 | 26.10 | 21.82 | 0.762283E+10 | 5178.74 | 06-SEP-10:00 | 30.60 | 26.05 |
October | 0.253346E+11 | 29661.05 | 17-OCT-04:01 | 24.32 | 19.13 | 0.786846E+10 | 5182.93 | 04-OCT-10:50 | 24.32 | 19.13 |
November | 0.237465E+11 | 31454.52 | 14-NOV-04:31 | 19.23 | 15.63 | 0.760899E+10 | 5166.90 | 30-NOV-11:50 | 27.12 | 25.09 |
December | 0.237758E+11 | 47813.23 | 15-DEC-05:01 | 7.80 | 5.52 | 0.785527E+10 | 5140.24 | 07-DEC-11:50 | 7.80 | 5.52 |
Annual Sum or Average | 0.290814E+12 | 0.926396E+11 | ||||||||
Minimum of Months | 0.212408E+11 | 22633.82 | 7.62 | 4.99 | 0.709651E+10 | 5138.46 | 7.62 | 4.99 | ||
Maximum of Months | 0.257140E+11 | 47813.23 | 26.10 | 22.65 | 0.788542E+10 | 5189.35 | 32.80 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 | 19.26 | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 | 18.63 | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 | 20.01 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 | 24.42 | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 26.83 | 23.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 28.60 | 25.82 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 27.05 | 24.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 | 23.96 | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 | 21.03 | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 | 21.22 | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.00 | 0.00 | 16.65 | 13.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.00 | 0.00 | 28.60 | 25.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8275550.28 | 1775.24 | 25-JAN-07:10 | 9.50 |
February | 43279479.35 | 6266.05 | 04-FEB-07:10 | 5.28 |
March | 31595442.69 | 3587.25 | 16-MAR-06:10 | 6.70 |
April | 4196088.47 | 1827.50 | 13-APR-04:02 | 24.40 |
May | 26191113.13 | 2429.23 | 20-MAY-04:02 | 25.68 |
June | 79702305.03 | 3110.87 | 28-JUN-04:02 | 27.62 |
July | 61784900.66 | 3015.56 | 21-JUL-04:02 | 27.20 |
August | 73448291.60 | 3085.32 | 19-AUG-04:02 | 27.80 |
September | 55960453.08 | 2984.36 | 10-SEP-23:01 | 29.40 |
October | 25011912.86 | 2721.46 | 02-OCT-04:02 | 26.70 |
November | 10823379.00 | 2455.93 | 05-NOV-04:02 | 26.10 |
December | 19217401.91 | 2298.61 | 15-DEC-07:10 | 7.88 |
Annual Sum or Average | 0.439486E+09 | |||
Minimum of Months | 4196088.47 | 1775.24 | 5.28 | |
Maximum of Months | 79702305.03 | 6266.05 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 94867.11 | 593.48 | 31-MAY-23:01 | 26.87 |
June | 2964070.14 | 2963.03 | 10-JUN-23:01 | 29.32 |
July | 1760110.72 | 2287.48 | 31-JUL-23:01 | 28.68 |
August | 2383487.70 | 2511.88 | 02-AUG-23:01 | 28.90 |
September | 2290060.04 | 3020.85 | 10-SEP-23:01 | 29.40 |
October | 165482.60 | 840.94 | 29-OCT-23:01 | 27.12 |
November | 25796.51 | 429.94 | 03-NOV-23:01 | 26.70 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 |
Annual Sum or Average | 9683874.82 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 2964070.14 | 3020.85 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:01 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898106E+09 | 661.67 | 02-JAN-17:30 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.798221E+09 | 661.67 | 01-FEB-17:00 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.869829E+09 | 661.67 | 01-MAR-18:19 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.824058E+09 | 661.67 | 01-APR-18:30 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.845582E+09 | 661.67 | 01-MAY-18:40 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.822925E+09 | 661.67 | 01-JUN-18:30 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.829928E+09 | 661.67 | 01-JUL-19:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.857698E+09 | 661.67 | 01-AUG-18:40 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.833654E+09 | 661.67 | 01-SEP-18:30 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.873233E+09 | 661.67 | 02-OCT-17:49 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.863935E+09 | 661.67 | 01-NOV-17:30 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.904636E+09 | 661.67 | 01-DEC-17:19 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.102218E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.798221E+09 | 661.67 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.904636E+09 | 661.67 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161928E+10 | 947.94 | 02-JAN-10:09 | 0.166241E+11 | 10153.43 | 01-JAN-11:09 |
February | 0.146666E+10 | 947.94 | 01-FEB-10:09 | 0.150153E+11 | 10153.43 | 01-FEB-11:09 |
March | 0.164506E+10 | 947.94 | 01-MAR-10:09 | 0.166241E+11 | 10153.43 | 01-MAR-11:09 |
April | 0.157340E+10 | 947.94 | 01-APR-16:10 | 0.160878E+11 | 10153.43 | 01-APR-10:09 |
May | 0.163217E+10 | 947.94 | 01-MAY-09:09 | 0.166241E+11 | 10153.43 | 01-MAY-10:09 |
June | 0.159008E+10 | 947.94 | 01-JUN-09:09 | 0.160878E+11 | 10153.43 | 01-JUN-10:09 |
July | 0.161568E+10 | 947.94 | 01-JUL-16:10 | 0.166241E+11 | 10153.43 | 01-JUL-10:09 |
August | 0.164506E+10 | 947.94 | 01-AUG-09:09 | 0.166241E+11 | 10153.43 | 01-AUG-10:09 |
September | 0.157378E+10 | 947.94 | 01-SEP-09:09 | 0.160878E+11 | 10153.43 | 01-SEP-10:09 |
October | 0.161909E+10 | 947.94 | 02-OCT-09:09 | 0.166241E+11 | 10153.43 | 01-OCT-10:09 |
November | 0.156752E+10 | 947.94 | 01-NOV-09:09 | 0.160878E+11 | 10153.43 | 01-NOV-10:09 |
December | 0.161587E+10 | 947.94 | 01-DEC-10:09 | 0.166241E+11 | 10153.43 | 01-DEC-11:09 |
Annual Sum or Average | 0.191636E+11 | 0.195735E+12 | ||||
Minimum of Months | 0.146666E+10 | 947.94 | 0.150153E+11 | 10153.43 | ||
Maximum of Months | 0.164506E+10 | 947.94 | 0.166241E+11 | 10153.43 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.898106E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333441E+09 | 0.382407E+10 |
February | 0.852256E+10 | 0.798221E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531392E+09 | 0.224887E+10 |
March | 0.954557E+10 | 0.869829E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635340E+09 | 0.215143E+10 |
April | 0.915225E+10 | 0.824058E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166956E+10 | 0.578233E+09 |
May | 0.947560E+10 | 0.845582E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364916E+10 | 62713491.51 |
June | 0.922788E+10 | 0.822925E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460159E+10 | 5815940.12 |
July | 0.939996E+10 | 0.829928E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552193E+10 | 28806465.63 |
August | 0.954557E+10 | 0.857698E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510006E+10 | 35123612.58 |
September | 0.915225E+10 | 0.833654E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456846E+10 | 14578834.61 |
October | 0.940563E+10 | 0.873233E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345367E+10 | 61679989.24 |
November | 0.909363E+10 | 0.863935E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173383E+10 | 0.104148E+10 |
December | 0.939996E+10 | 0.904636E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485060E+09 | 0.331291E+10 |
Annual Sum or Average | 0.111326E+12 | 0.102218E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322835E+11 | 0.133657E+11 |
Minimum of Months | 0.852256E+10 | 0.798221E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333441E+09 | 5815940.12 |
Maximum of Months | 0.954557E+10 | 0.904636E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552193E+10 | 0.382407E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.161928E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 339857.13 | 80051655.57 |
February | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 770006.78 | 0.109879E+09 |
March | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1108407.62 | 0.112838E+09 |
April | 0.655836E+09 | 0.157340E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 4036963.51 | 56704939.89 |
May | 0.679007E+09 | 0.163217E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 14166583.49 | 37440060.76 |
June | 0.661256E+09 | 0.159008E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 14889912.56 | 15346292.56 |
July | 0.673587E+09 | 0.161568E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 14645462.63 | 12993069.69 |
August | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 15913073.85 | 12000056.33 |
September | 0.655836E+09 | 0.157378E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 14881933.25 | 14718638.75 |
October | 0.673993E+09 | 0.161909E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9305510.01 | 23534484.85 |
November | 0.651635E+09 | 0.156752E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2716581.25 | 64304626.04 |
December | 0.673587E+09 | 0.161587E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 601193.08 | 83924334.53 |
Annual Sum or Average | 0.797748E+10 | 0.191636E+11 | 0.146736E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 93375485.14 | 0.623735E+09 |
Minimum of Months | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 339857.13 | 12000056.33 |
Maximum of Months | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 15913073.85 | 0.112838E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402874E+09 | 0.101989E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296055E+09 | 0.106905E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298009E+09 | 0.147856E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292750E+09 | 0.166518E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265868E+09 | 0.167541E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267350E+09 | 0.158996E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306324E+09 | 0.179983E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325087E+09 | 0.145468E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289496E+09 | 0.140141E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385095E+09 | 0.117807E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337654E+09 | 0.979303E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317481E+09 | 0.971038E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378404E+10 | 0.162824E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265868E+09 | 0.971038E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402874E+09 | 0.179983E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 661.67 | 02-JAN-17:30 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3976.38 | 02-JAN-13:55 | 8408.46 | 24-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 661.67 | 01-FEB-17:00 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3523.34 | 02-FEB-14:00 | 10391.89 | 04-FEB-07:10 |
March | 9454.80 | 04-MAR-19:10 | 661.67 | 01-MAR-18:19 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4358.54 | 13-MAR-17:03 | 7761.66 | 16-MAR-06:10 |
April | 9454.80 | 01-APR-18:10 | 661.67 | 01-APR-18:30 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6253.69 | 17-APR-17:08 | 4321.93 | 02-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 661.67 | 01-MAY-18:40 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8232.42 | 22-MAY-12:00 | 1793.63 | 07-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 661.67 | 01-JUN-18:30 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6367.08 | 09-JUN-12:00 | 359.25 | 13-JUN-16:58 |
July | 9454.80 | 01-JUL-18:10 | 661.67 | 01-JUL-19:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8889.35 | 29-JUL-18:02 | 989.59 | 14-JUL-17:55 |
August | 9454.80 | 05-AUG-18:10 | 661.67 | 01-AUG-18:40 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8254.63 | 23-AUG-12:00 | 1540.00 | 28-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 661.67 | 01-SEP-18:30 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6872.30 | 13-SEP-12:00 | 760.58 | 05-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 661.67 | 02-OCT-17:49 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6864.77 | 03-OCT-12:00 | 1338.88 | 28-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 661.67 | 01-NOV-17:30 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4451.67 | 17-NOV-13:00 | 5836.20 | 12-NOV-20:55 |
December | 9454.80 | 02-DEC-19:10 | 661.67 | 01-DEC-17:19 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3114.90 | 08-DEC-14:00 | 9455.61 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 3114.90 | 359.25 | |||||
Maximum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 8889.35 | 10391.89 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 947.94 | 02-JAN-10:09 | 7415.65 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 14.28 | 07-JAN-13:00 | 401.30 | 24-JAN-02:30 |
February | 677.52 | 04-FEB-19:10 | 947.94 | 01-FEB-10:09 | 7415.65 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 17.23 | 02-FEB-14:00 | 565.46 | 04-FEB-04:40 |
March | 677.52 | 04-MAR-19:10 | 947.94 | 01-MAR-10:09 | 7415.65 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 21.80 | 13-MAR-16:53 | 561.01 | 16-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 947.94 | 01-APR-16:10 | 7415.65 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 31.18 | 15-APR-16:53 | 284.12 | 23-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 947.94 | 01-MAY-09:09 | 7415.65 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 50.72 | 22-MAY-14:41 | 253.90 | 25-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 947.94 | 01-JUN-09:09 | 7415.65 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 30.45 | 16-JUN-13:00 | 188.83 | 18-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 947.94 | 01-JUL-16:10 | 7415.65 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 34.74 | 27-JUL-15:53 | 141.23 | 04-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 947.94 | 01-AUG-09:09 | 7415.65 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 27.78 | 23-AUG-13:00 | 228.79 | 14-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 947.94 | 01-SEP-09:09 | 7415.65 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.81 | 19-SEP-15:00 | 126.82 | 26-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 947.94 | 02-OCT-09:09 | 7415.65 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 28.80 | 03-OCT-12:10 | 203.09 | 17-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 947.94 | 01-NOV-09:09 | 7415.65 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 13.40 | 17-NOV-14:53 | 433.28 | 12-NOV-04:30 |
December | 677.52 | 02-DEC-19:10 | 947.94 | 01-DEC-10:09 | 7415.65 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 19.23 | 10-DEC-15:00 | 554.64 | 15-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 13.40 | 126.82 | ||||||
Maximum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 50.72 | 565.46 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.66 | 27-JAN-03:30 | 2227.71 | 31-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.24 | 28-FEB-07:15 | 2154.67 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.84 | 02-MAR-04:00 | 2544.00 | 16-MAR-13:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.02 | 05-APR-05:10 | 2535.65 | 10-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.76 | 06-MAY-05:20 | 2554.10 | 06-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.09 | 10-JUN-03:00 | 2565.53 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.39 | 07-JUL-06:05 | 2555.67 | 07-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.30 | 31-AUG-03:51 | 2365.36 | 07-AUG-13:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.95 | 12-SEP-02:20 | 2386.88 | 17-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.32 | 22-OCT-04:00 | 2359.03 | 06-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.83 | 07-NOV-06:40 | 1910.27 | 10-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.24 | 13-DEC-06:00 | 1893.77 | 04-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.76 | 1893.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.66 | 2565.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18141.50 | 16-JAN-05:01 | 0.00 | 882.23 | 13024.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
February | 21412.50 | 17-FEB-05:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 |
March | 21680.63 | 31-MAR-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
April | 21565.30 | 28-APR-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 |
May | 21673.54 | 16-MAY-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 |
June | 21860.41 | 02-JUN-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 0.00 |
July | 21495.65 | 07-JUL-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19913.28 | 11-AUG-04:01 | 4727.40 | 1323.34 | 14652.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 0.00 |
September | 22143.30 | 01-SEP-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 0.00 |
October | 22090.93 | 17-OCT-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 |
November | 22036.76 | 21-NOV-05:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 21945.15 | 01-DEC-05:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18141.50 | 0.00 | 882.23 | 13024.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22143.30 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10.31 | 10.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46819.20 | 27-JAN-04:21 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38886.24 | 22-FEB-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 |
March | 41114.49 | 16-MAR-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 |
April | 32121.84 | 18-APR-03:31 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 110.23 |
May | 28828.02 | 09-MAY-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
June | 24260.04 | 13-JUN-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 |
July | 26495.45 | 07-JUL-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22633.82 | 14-AUG-04:01 | 338.76 | 1895.95 | 33037.85 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 |
September | 26092.30 | 01-SEP-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
October | 29661.05 | 17-OCT-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 |
November | 31454.52 | 14-NOV-04:31 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 125.96 |
December | 47813.23 | 15-DEC-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 103.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22633.82 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47813.23 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 125.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.32 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.86 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.26 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.22 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.55 | 0.00 |
June | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.44 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.59 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.10 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.25 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.90 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.86 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.455644E+11 | 34044.72 | 02-JAN-13:00 | 0.552864E+11 | 46277.62 | 17-JAN-13:20 |
February | 0.431733E+11 | 35169.73 | 11-FEB-11:20 | 0.500132E+11 | 46225.63 | 02-FEB-13:20 |
March | 0.493000E+11 | 35445.09 | 14-MAR-10:20 | 0.548650E+11 | 45923.76 | 03-MAR-13:39 |
April | 0.515724E+11 | 35836.54 | 13-APR-11:20 | 0.522155E+11 | 45339.12 | 02-APR-12:39 |
May | 0.603162E+11 | 37976.26 | 31-MAY-10:20 | 0.534295E+11 | 44518.81 | 04-MAY-12:00 |
June | 0.634903E+11 | 38164.36 | 06-JUN-10:20 | 0.513073E+11 | 43747.89 | 05-JUN-12:30 |
July | 0.670599E+11 | 39758.48 | 14-JUL-11:20 | 0.528128E+11 | 43346.10 | 02-JUL-12:50 |
August | 0.672105E+11 | 39527.97 | 23-AUG-10:20 | 0.529566E+11 | 43638.14 | 27-AUG-12:39 |
September | 0.639347E+11 | 38677.39 | 22-SEP-11:20 | 0.515863E+11 | 44420.37 | 30-SEP-12:39 |
October | 0.619761E+11 | 38781.42 | 03-OCT-11:20 | 0.538339E+11 | 45220.06 | 31-OCT-12:50 |
November | 0.537849E+11 | 36712.02 | 10-NOV-11:20 | 0.526952E+11 | 45807.64 | 28-NOV-13:20 |
December | 0.481982E+11 | 34591.78 | 24-DEC-11:20 | 0.552473E+11 | 46171.23 | 26-DEC-13:20 |
Annual Sum or Average | 0.675581E+12 | 0.636249E+12 | ||||
Minimum of Months | 0.431733E+11 | 34044.72 | 0.500132E+11 | 43346.10 | ||
Maximum of Months | 0.672105E+11 | 39758.48 | 0.552864E+11 | 46277.62 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.251739E+10 | 0.261624E+10 | 0.226048E+11 | 0.00 | 0.464093E+10 | 0.79 | 0.00 | 0.841499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.226488E+10 | 0.224143E+10 | 0.204173E+11 | 0.00 | 0.422479E+10 | 0.72 | 0.00 | 0.970738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.251489E+10 | 0.231720E+10 | 0.226048E+11 | 0.00 | 0.476205E+10 | 0.80 | 0.00 | 0.122989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239746E+10 | 0.208172E+10 | 0.218757E+11 | 0.00 | 0.476059E+10 | 0.77 | 0.00 | 0.157723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247775E+10 | 0.200609E+10 | 0.226048E+11 | 0.00 | 0.552334E+10 | 0.80 | 0.00 | 0.228208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241301E+10 | 0.187553E+10 | 0.218757E+11 | 0.00 | 0.597428E+10 | 0.77 | 0.00 | 0.265830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.244561E+10 | 0.195907E+10 | 0.226048E+11 | 0.00 | 0.634598E+10 | 0.79 | 0.00 | 0.287712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250276E+10 | 0.208689E+10 | 0.226048E+11 | 0.00 | 0.634941E+10 | 0.80 | 0.00 | 0.287228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240743E+10 | 0.217457E+10 | 0.218757E+11 | 0.00 | 0.599017E+10 | 0.77 | 0.00 | 0.267216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249232E+10 | 0.241366E+10 | 0.226048E+11 | 0.00 | 0.568030E+10 | 0.79 | 0.00 | 0.238923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243146E+10 | 0.248447E+10 | 0.218757E+11 | 0.00 | 0.503185E+10 | 0.77 | 0.00 | 0.172732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252050E+10 | 0.264759E+10 | 0.226048E+11 | 0.00 | 0.478245E+10 | 0.79 | 0.00 | 0.108477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293855E+11 | 0.269045E+11 | 0.266154E+12 | 0.00 | 0.640662E+11 | 9.37 | 0.00 | 0.231826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.226488E+10 | 0.187553E+10 | 0.204173E+11 | 0.00 | 0.422479E+10 | 0.72 | 0.00 | 0.841499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252050E+10 | 0.264759E+10 | 0.226048E+11 | 0.00 | 0.634941E+10 | 0.80 | 0.00 | 0.287712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.329132E+09 | 0.00 | 0.144316E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.474510E+09 | 0.00 | 0.129348E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.358403E+09 | 0.00 | 0.139809E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.129970E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.129038E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.120889E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.122871E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.124309E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.123679E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.133082E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 62800570.50 | 0.00 | 0.134139E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.466425E+09 | 0.00 | 0.142551E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.169127E+10 | 0.00 | 0.157400E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.120889E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.474510E+09 | 0.00 | 0.144316E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1609.61 | 02-JAN-17:30 | 2009.71 | 01-JAN-00:10 | 14087.95 | 01-JAN-11:09 | 0.00 | 3117.14 | 02-JAN-13:00 | 0.00 | 07-JAN-15:39 | 0.00 | 01-JAN-00:10 |
February | 1609.61 | 01-FEB-17:00 | 2009.71 | 01-FEB-00:10 | 14087.95 | 01-FEB-11:09 | 0.00 | 2910.70 | 11-FEB-13:00 | 0.00 | 24-FEB-08:00 | 0.00 | 01-FEB-00:10 |
March | 1609.61 | 01-MAR-18:19 | 2009.71 | 01-MAR-00:10 | 14087.95 | 01-MAR-11:09 | 0.00 | 2907.76 | 13-MAR-12:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1609.61 | 01-APR-18:30 | 2009.71 | 01-APR-05:10 | 14087.95 | 01-APR-10:09 | 0.00 | 3210.49 | 13-APR-11:00 | 0.00 | 01-APR-09:39 | 0.00 | 01-APR-00:10 |
May | 1609.61 | 01-MAY-18:40 | 2009.71 | 01-MAY-05:10 | 14087.95 | 01-MAY-10:09 | 0.00 | 3423.18 | 31-MAY-12:00 | 0.00 | 10-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 1609.61 | 01-JUN-18:30 | 2009.71 | 01-JUN-05:10 | 14087.95 | 01-JUN-10:09 | 0.00 | 3464.00 | 08-JUN-17:10 | 0.00 | 13-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 1609.61 | 01-JUL-19:10 | 2009.71 | 01-JUL-05:10 | 14087.95 | 01-JUL-10:09 | 0.00 | 3667.40 | 14-JUL-11:30 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1609.61 | 01-AUG-18:40 | 2009.71 | 01-AUG-05:10 | 14087.95 | 01-AUG-10:09 | 0.00 | 3623.92 | 22-AUG-12:00 | 0.00 | 05-AUG-17:49 | 0.00 | 01-AUG-00:10 |
September | 1609.61 | 01-SEP-18:30 | 2009.71 | 01-SEP-05:10 | 14087.95 | 01-SEP-10:09 | 0.00 | 3578.96 | 22-SEP-11:00 | 0.00 | 02-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 1609.61 | 02-OCT-17:49 | 2009.71 | 01-OCT-05:10 | 14087.95 | 01-OCT-10:09 | 0.00 | 3555.91 | 03-OCT-11:00 | 0.00 | 09-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 1609.61 | 01-NOV-17:30 | 2009.71 | 01-NOV-05:10 | 14087.95 | 01-NOV-10:09 | 0.00 | 3159.98 | 03-NOV-12:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1609.61 | 01-DEC-17:19 | 2009.71 | 01-DEC-00:10 | 14087.95 | 01-DEC-11:09 | 0.00 | 2830.81 | 08-DEC-12:09 | 0.00 | 25-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 2830.81 | 0.00 | 0.00 | ||||||
Maximum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 3667.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 15563.12 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14634.57 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14562.92 | 13-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16181.25 | 13-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17621.29 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17556.46 | 08-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 19205.81 | 27-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18905.56 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18250.03 | 22-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18256.92 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15830.33 | 03-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14161.99 | 08-DEC-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14161.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19205.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 34044.72 | 02-JAN-13:00 | 1358.18 | 12286.51 | 0.00 | 0.00 | 3117.14 | 0.00 | 0.00 | 15563.12 | 0.00 |
February | 35169.73 | 11-FEB-11:20 | 1207.27 | 14087.95 | 0.00 | 0.00 | 2656.88 | 0.00 | 0.00 | 12856.76 | 0.00 |
March | 35445.09 | 14-MAR-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2678.29 | 0.00 | 0.00 | 12950.39 | 0.00 |
April | 35836.54 | 13-APR-11:20 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3112.07 | 0.00 | 0.00 | 15573.26 | 0.00 |
May | 37976.26 | 31-MAY-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2945.58 | 0.00 | 0.00 | 15214.26 | 0.00 |
June | 38164.36 | 06-JUN-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3018.15 | 0.00 | 0.00 | 15329.80 | 0.00 |
July | 39758.48 | 14-JUL-11:20 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3666.05 | 0.00 | 0.00 | 18883.77 | 0.00 |
August | 39527.97 | 23-AUG-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3192.58 | 0.00 | 0.00 | 16518.98 | 0.00 |
September | 38677.39 | 22-SEP-11:20 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3532.48 | 0.00 | 0.00 | 17951.08 | 0.00 |
October | 38781.42 | 03-OCT-11:20 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3534.00 | 0.00 | 0.00 | 18059.92 | 0.00 |
November | 36712.02 | 10-NOV-11:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2806.24 | 0.00 | 0.00 | 14089.37 | 0.00 |
December | 34591.78 | 24-DEC-11:20 | 1056.37 | 14087.95 | 0.00 | 0.00 | 2686.26 | 0.00 | 0.00 | 12409.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 34044.72 | 1056.37 | 12286.51 | 0.00 | 0.00 | 2656.88 | 0.00 | 0.00 | 12409.77 | 0.00 | |
Maximum of Months | 39758.48 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3666.05 | 0.00 | 0.00 | 18883.77 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 8260.60 | 25-JAN-07:10 | 0.00 | 23294.47 | 17-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 19801.70 | 04-FEB-07:10 | 0.00 | 23242.48 | 02-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 12212.70 | 16-MAR-06:10 | 0.00 | 22940.61 | 03-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22355.97 | 02-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 21535.66 | 04-MAY-12:00 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20764.74 | 05-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20362.95 | 02-JUL-12:50 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 20654.99 | 27-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 21437.22 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 22236.91 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 5872.12 | 27-NOV-07:10 | 0.00 | 22824.49 | 28-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 9920.26 | 15-DEC-07:10 | 0.00 | 23188.08 | 26-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 20362.95 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 19801.70 | 0.00 | 23294.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.19 | 0.00 | 26.19 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.22 | 0.00 | 26.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.16 | 0.00 | 26.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.26 | 0.00 | 26.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.26 | 0.00 | 26.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.31 | 0.00 | 26.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.35 | 0.00 | 26.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.26 | 0.00 | 26.26 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.23 | 0.00 | 26.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
Annual Sum or Average | 0.00 | 0.00 | 22.00 | 26.27 | 0.00 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.35 | 0.00 | 26.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 30.59 | 0.50 | 30.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 30.51 | 0.83 | 30.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 30.59 | 1.00 | 30.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 30.64 | 2.50 | 30.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 29.18 | 29.00 | 28.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 164.67 | 27.98 | 133.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 271.00 | 27.79 | 238.17 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 245.67 | 27.84 | 214.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 178.83 | 27.91 | 147.33 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 | 28.39 | 72.83 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 29.14 | 24.67 | 28.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.50 | 1.83 | 30.28 |
Annual Sum or Average | 0.00 | 0.00 | 1214.17 | 28.33 | 866.50 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.79 | 0.50 | 27.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 271.00 | 30.64 | 238.17 | 30.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.00 | 22.99 | 445.50 | 23.52 | 172.67 | 23.60 |
February | 246.67 | 23.32 | 452.17 | 23.69 | 175.50 | 23.75 |
March | 296.83 | 23.42 | 507.33 | 23.75 | 222.00 | 23.80 |
April | 242.33 | 23.97 | 580.17 | 23.97 | 235.17 | 23.98 |
May | 448.00 | 24.04 | 611.00 | 24.02 | 448.00 | 24.03 |
June | 574.00 | 24.05 | 592.00 | 24.05 | 574.00 | 24.05 |
July | 587.67 | 24.05 | 609.00 | 24.04 | 587.67 | 24.04 |
August | 601.83 | 24.05 | 612.00 | 24.05 | 601.83 | 24.05 |
September | 572.00 | 24.04 | 590.00 | 24.04 | 572.00 | 24.04 |
October | 468.83 | 24.04 | 610.00 | 24.03 | 468.83 | 24.03 |
November | 393.33 | 23.85 | 557.67 | 23.92 | 366.67 | 23.95 |
December | 354.00 | 23.35 | 499.50 | 23.67 | 267.00 | 23.73 |
Annual Sum or Average | 5089.50 | 23.84 | 6666.33 | 23.92 | 4691.33 | 23.95 |
Minimum of Months | 242.33 | 22.99 | 445.50 | 23.52 | 172.67 | 23.60 |
Maximum of Months | 601.83 | 24.05 | 612.00 | 24.05 | 601.83 | 24.05 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.17 | 26.00 | 592.83 | 25.87 | 491.00 | 25.94 |
February | 491.17 | 25.98 | 530.50 | 25.96 | 478.17 | 26.01 |
March | 551.00 | 26.07 | 591.17 | 26.03 | 541.83 | 26.07 |
April | 583.00 | 26.20 | 590.00 | 26.19 | 583.00 | 26.19 |
May | 611.00 | 26.32 | 611.00 | 26.32 | 611.00 | 26.32 |
June | 592.00 | 26.59 | 592.00 | 26.59 | 592.00 | 26.59 |
July | 609.00 | 26.80 | 609.00 | 26.80 | 609.00 | 26.80 |
August | 612.00 | 26.76 | 612.00 | 26.76 | 612.00 | 26.76 |
September | 590.00 | 26.60 | 590.00 | 26.60 | 590.00 | 26.60 |
October | 610.00 | 26.41 | 610.00 | 26.41 | 610.00 | 26.41 |
November | 567.50 | 26.24 | 584.00 | 26.21 | 565.33 | 26.23 |
December | 547.00 | 25.97 | 584.83 | 25.94 | 532.00 | 26.00 |
Annual Sum or Average | 6864.83 | 26.34 | 7097.33 | 26.32 | 6815.33 | 26.34 |
Minimum of Months | 491.17 | 25.97 | 530.50 | 25.87 | 478.17 | 25.94 |
Maximum of Months | 612.00 | 26.80 | 612.00 | 26.80 | 612.00 | 26.80 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.38581 | 56.35823 | 0.49992 | 12.01315 |
February | 551.00000 | 23.59847 | 56.16847 | 0.55385 | 12.91156 |
March | 612.00000 | 23.64384 | 58.43166 | 0.58077 | 13.60198 |
April | 590.00000 | 23.94201 | 61.92196 | 0.68752 | 15.21824 |
May | 611.00000 | 24.00723 | 68.80285 | -0.0520 | 5.38090 |
June | 592.00000 | 24.04762 | 72.77419 | 0.00464 | 5.50261 |
July | 609.00000 | 24.03974 | 72.35680 | 0.02327 | 5.47836 |
August | 612.00000 | 24.04779 | 73.17864 | 0.03034 | 5.53994 |
September | 590.00000 | 24.03834 | 72.08441 | 0.03241 | 5.55227 |
October | 610.00000 | 24.01430 | 69.15856 | 0.79841 | 18.65056 |
November | 591.00000 | 23.85766 | 65.42345 | 0.70960 | 16.48639 |
December | 609.00000 | 23.52965 | 61.03594 | 0.57292 | 13.54758 |
Annual Sum or Average | 7187.00000 | 23.84677 | 65.69440 | 0.36863 | 10.80619 |
Minimum of Months | 551.00000 | 23.38581 | 56.16847 | -0.0520 | 5.38090 |
Maximum of Months | 612.00000 | 24.04779 | 73.17864 | 0.79841 | 18.65056 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.63912 | 51.37521 | 1.18828 | 36.32002 |
February | 551.00000 | 25.77340 | 51.33537 | 1.22503 | 38.18273 |
March | 612.00000 | 25.84158 | 52.86864 | 1.25760 | 39.61151 |
April | 590.00000 | 26.18053 | 55.98710 | 1.37822 | 44.50541 |
May | 611.00000 | 26.31555 | 61.51990 | 0.94655 | 24.50420 |
June | 592.00000 | 26.59347 | 64.92308 | 1.07909 | 30.51575 |
July | 609.00000 | 26.80278 | 65.22223 | 1.16813 | 34.86425 |
August | 612.00000 | 26.75858 | 65.42891 | 1.14663 | 33.82426 |
September | 590.00000 | 26.59748 | 64.50436 | 1.08974 | 31.00516 |
October | 610.00000 | 26.40823 | 61.81717 | 1.50265 | 51.04008 |
November | 591.00000 | 26.13930 | 58.09430 | 1.38967 | 45.54130 |
December | 609.00000 | 25.73596 | 54.76188 | 1.24630 | 39.16455 |
Annual Sum or Average | 7187.00000 | 26.23444 | 59.02997 | 1.21786 | 37.40895 |
Minimum of Months | 551.00000 | 25.63912 | 51.33537 | 0.94655 | 24.50420 |
Maximum of Months | 612.00000 | 26.80278 | 65.42891 | 1.50265 | 51.04008 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.134554E+11 | 0.358638E+10 | 400.93 | 0.792338E+10 | 0.553206E+10 | 0.00 | 1.00 | 02-JAN-05:02 | 0.00 | 01-JAN-00:05 | 43281.14 | 07-JAN-05:01 | 20859.55 | 14-JAN-05:01 | 23437.65 | 07-JAN-05:01 | 9825.90 | 07-JAN-05:01 | 0.00 | 01-JAN-00:05 |
February | 0.163025E+11 | 0.433253E+10 | 426.17 | 0.101032E+11 | 0.619933E+10 | 0.00 | 1.00 | 02-FEB-12:20 | 0.00 | 01-FEB-00:10 | 48127.66 | 17-FEB-05:01 | 25052.64 | 17-FEB-05:01 | 23075.02 | 17-FEB-05:01 | 11043.88 | 17-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.208524E+11 | 0.544896E+10 | 500.04 | 0.119849E+11 | 0.886757E+10 | 0.00 | 1.00 | 04-MAR-05:01 | 0.00 | 01-MAR-00:10 | 55826.78 | 14-MAR-04:01 | 25368.31 | 14-MAR-04:01 | 30458.47 | 14-MAR-04:01 | 12647.56 | 14-MAR-04:01 | 0.00 | 01-MAR-00:10 |
April | 0.279383E+11 | 0.719042E+10 | 568.65 | 0.165769E+11 | 0.113614E+11 | 0.00 | 1.00 | 01-APR-17:02 | 0.00 | 01-APR-00:01 | 52832.54 | 14-APR-04:01 | 25975.93 | 14-APR-04:01 | 26856.61 | 14-APR-04:01 | 12023.33 | 14-APR-04:01 | 0.00 | 01-APR-00:01 |
May | 0.420693E+11 | 0.103023E+11 | 607.68 | 0.226305E+11 | 0.194388E+11 | 0.00 | 1.00 | 01-MAY-11:03 | 0.00 | 01-MAY-00:01 | 55826.78 | 30-MAY-04:01 | 26764.02 | 16-MAY-04:01 | 33932.04 | 29-MAY-04:01 | 12647.56 | 29-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.499633E+11 | 0.118760E+11 | 590.60 | 0.247629E+11 | 0.252004E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:02 | 55826.78 | 23-JUN-04:01 | 27685.73 | 02-JUN-04:01 | 33207.52 | 07-JUN-04:01 | 12647.56 | 06-JUN-04:01 | 0.00 | 01-JUN-00:02 |
July | 0.548051E+11 | 0.131046E+11 | 610.41 | 0.276821E+11 | 0.271231E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:02 | 55826.78 | 11-JUL-04:01 | 26219.88 | 21-JUL-04:01 | 32338.34 | 12-JUL-04:01 | 12647.56 | 11-JUL-04:01 | 0.00 | 01-JUL-00:02 |
August | 0.546097E+11 | 0.129715E+11 | 611.05 | 0.269593E+11 | 0.276504E+11 | 0.00 | 1.00 | 01-AUG-03:02 | 0.00 | 01-AUG-00:02 | 55826.78 | 01-AUG-04:01 | 26361.61 | 11-AUG-04:01 | 31087.97 | 05-AUG-04:01 | 12647.56 | 01-AUG-04:01 | 0.00 | 01-AUG-00:02 |
September | 0.506093E+11 | 0.120705E+11 | 590.74 | 0.254642E+11 | 0.251451E+11 | 0.00 | 1.00 | 01-SEP-03:02 | 0.00 | 01-SEP-00:02 | 55826.78 | 12-SEP-04:01 | 27990.39 | 01-SEP-04:01 | 32310.12 | 23-SEP-03:02 | 12647.56 | 08-SEP-04:01 | 0.00 | 01-SEP-00:02 |
October | 0.446574E+11 | 0.108164E+11 | 609.34 | 0.233158E+11 | 0.213416E+11 | 0.00 | 1.00 | 01-OCT-03:02 | 0.00 | 01-OCT-00:02 | 55826.78 | 04-OCT-04:01 | 26510.57 | 10-OCT-04:01 | 33759.27 | 04-OCT-04:01 | 12647.56 | 03-OCT-04:01 | 0.00 | 01-OCT-00:02 |
November | 0.311673E+11 | 0.770901E+10 | 542.41 | 0.163623E+11 | 0.148050E+11 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:01 | 55826.78 | 10-NOV-05:01 | 27191.66 | 21-NOV-05:01 | 31091.33 | 24-NOV-05:01 | 12647.56 | 10-NOV-05:01 | 0.00 | 01-NOV-00:01 |
December | 0.177414E+11 | 0.459706E+10 | 454.28 | 0.963230E+10 | 0.810913E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:01 | 55826.78 | 26-DEC-05:01 | 25642.36 | 08-DEC-05:01 | 30704.36 | 26-DEC-05:01 | 12647.56 | 26-DEC-05:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.424171E+12 | 0.104006E+12 | 6512.29 | 0.223398E+12 | 0.200774E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.134554E+11 | 0.358638E+10 | 400.93 | 0.792338E+10 | 0.553206E+10 | 0.00 | 1.00 | 0.00 | 43281.14 | 20859.55 | 23075.02 | 9825.90 | 0.00 | |||||||
Maximum of Months | 0.548051E+11 | 0.131046E+11 | 611.05 | 0.276821E+11 | 0.276504E+11 | 0.00 | 1.00 | 0.00 | 55826.78 | 27990.39 | 33932.04 | 12647.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.200023E+11 | 0.482861E+10 | 514.58 | 0.109748E+11 | 0.902746E+10 | 0.00 | 1.00 | 01-JAN-03:11 | 0.00 | 01-JAN-00:05 | 34458.66 | 02-JAN-13:55 | 25493.27 | 27-JAN-05:01 | 22117.74 | 07-JAN-04:22 | 7669.77 | 02-JAN-13:50 | 0.00 | 01-JAN-00:05 |
February | 0.224510E+11 | 0.537484E+10 | 510.40 | 0.130127E+11 | 0.943830E+10 | 0.00 | 1.00 | 01-FEB-04:11 | 0.00 | 01-FEB-00:10 | 34458.66 | 11-FEB-11:53 | 19588.59 | 22-FEB-05:01 | 20813.30 | 11-FEB-04:22 | 7703.80 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.290789E+11 | 0.684992E+10 | 594.61 | 0.156457E+11 | 0.134332E+11 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 34458.66 | 04-MAR-12:10 | 22126.64 | 12-MAR-04:01 | 22465.25 | 06-MAR-03:11 | 7669.77 | 04-MAR-11:32 | 0.00 | 01-MAR-00:10 |
April | 0.368046E+11 | 0.858185E+10 | 640.77 | 0.210801E+11 | 0.157245E+11 | 0.00 | 1.00 | 01-APR-02:11 | 0.00 | 01-APR-00:01 | 34458.66 | 01-APR-15:50 | 22349.45 | 16-APR-12:53 | 22368.39 | 01-APR-02:11 | 7814.25 | 14-APR-13:22 | 0.00 | 01-APR-00:01 |
May | 0.553521E+11 | 0.125185E+11 | 677.62 | 0.287115E+11 | 0.266406E+11 | 0.00 | 1.00 | 01-MAY-02:11 | 0.00 | 01-MAY-00:01 | 34458.66 | 02-MAY-10:48 | 26838.27 | 22-MAY-13:00 | 23552.19 | 29-MAY-02:61 | 8242.54 | 22-MAY-13:00 | 0.00 | 01-MAY-00:01 |
June | 0.652891E+11 | 0.147070E+11 | 672.99 | 0.310599E+11 | 0.342292E+11 | 0.00 | 1.00 | 01-JUN-00:05 | 0.00 | 01-JUN-00:02 | 34458.66 | 05-JUN-19:50 | 22866.43 | 11-JUN-12:55 | 23585.02 | 25-JUN-03:22 | 7980.47 | 11-JUN-12:55 | 0.00 | 01-JUN-00:02 |
July | 0.688341E+11 | 0.156666E+11 | 694.11 | 0.337964E+11 | 0.350378E+11 | 0.00 | 1.00 | 01-JUL-00:05 | 0.00 | 01-JUL-00:02 | 34458.66 | 10-JUL-18:30 | 26212.23 | 29-JUL-15:53 | 23423.74 | 03-JUL-03:22 | 8400.87 | 29-JUL-15:53 | 0.00 | 01-JUL-00:02 |
August | 0.696107E+11 | 0.157513E+11 | 697.85 | 0.329380E+11 | 0.366727E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:02 | 34458.66 | 03-AUG-19:25 | 24124.80 | 23-AUG-12:00 | 23659.12 | 28-AUG-02:61 | 8179.70 | 23-AUG-13:00 | 0.00 | 01-AUG-00:02 |
September | 0.648357E+11 | 0.146511E+11 | 669.81 | 0.311355E+11 | 0.337002E+11 | 0.00 | 1.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:02 | 34458.66 | 06-SEP-20:40 | 23254.01 | 08-SEP-15:53 | 23461.33 | 06-SEP-02:61 | 7980.47 | 13-SEP-12:55 | 0.00 | 01-SEP-00:02 |
October | 0.578910E+11 | 0.130759E+11 | 679.80 | 0.284517E+11 | 0.294393E+11 | 0.00 | 1.00 | 01-OCT-00:05 | 0.00 | 01-OCT-00:02 | 34458.66 | 04-OCT-07:13 | 23637.85 | 23-OCT-11:10 | 24218.00 | 04-OCT-03:22 | 7980.47 | 09-OCT-10:53 | 0.00 | 01-OCT-00:02 |
November | 0.418179E+11 | 0.956419E+10 | 617.50 | 0.203138E+11 | 0.215041E+11 | 0.00 | 1.00 | 01-NOV-02:61 | 0.00 | 01-NOV-00:01 | 34458.66 | 03-NOV-10:45 | 20619.36 | 29-NOV-05:01 | 23323.99 | 04-NOV-03:22 | 7703.80 | 03-NOV-13:00 | 0.00 | 01-NOV-00:01 |
December | 0.264943E+11 | 0.625066E+10 | 553.17 | 0.130806E+11 | 0.134137E+11 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:01 | 34458.66 | 23-DEC-11:38 | 22670.50 | 15-DEC-05:01 | 23547.13 | 24-DEC-03:01 | 7669.77 | 07-DEC-11:35 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.558462E+12 | 0.127820E+12 | 7523.22 | 0.280201E+12 | 0.278261E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.200023E+11 | 0.482861E+10 | 510.40 | 0.109748E+11 | 0.902746E+10 | 0.00 | 1.00 | 0.00 | 34458.66 | 19588.59 | 20813.30 | 7669.77 | 0.00 | |||||||
Maximum of Months | 0.696107E+11 | 0.157513E+11 | 697.85 | 0.337964E+11 | 0.366727E+11 | 0.00 | 1.00 | 0.00 | 34458.66 | 26838.27 | 24218.00 | 8400.87 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.44 | 38.06 | 41.38 | 112.21 | 71.42 | 0.00 | 0.00 | 0.00 |
February | 91.73 | 42.46 | 49.27 | 139.60 | 59.42 | 0.00 | 0.00 | 0.00 |
March | 111.99 | 52.95 | 59.05 | 172.56 | 48.22 | 0.00 | 0.00 | 0.00 |
April | 121.54 | 54.23 | 67.31 | 208.14 | 33.76 | 0.00 | 0.00 | 0.00 |
May | 114.98 | 45.79 | 69.19 | 215.08 | 17.08 | 0.00 | 0.00 | 0.00 |
June | 113.49 | 43.59 | 69.90 | 222.83 | 8.63 | 0.00 | 0.00 | 0.00 |
July | 116.61 | 42.05 | 74.56 | 236.78 | 12.15 | 0.00 | 0.00 | 0.00 |
August | 106.63 | 35.66 | 70.98 | 208.31 | 9.57 | 0.00 | 0.00 | 0.00 |
September | 102.80 | 37.16 | 65.64 | 204.04 | 14.11 | 0.00 | 0.00 | 0.00 |
October | 94.62 | 40.75 | 53.87 | 174.16 | 21.78 | 0.00 | 0.00 | 0.00 |
November | 76.80 | 30.62 | 46.18 | 126.50 | 38.23 | 0.00 | 0.00 | 0.00 |
December | 62.04 | 21.90 | 40.14 | 88.33 | 63.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99.41 | 40.41 | 59.00 | 175.85 | 33.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.04 | 21.90 | 40.14 | 88.33 | 8.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.54 | 54.23 | 74.56 | 236.78 | 71.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.14 | 201.49 | 108.65 | 488.54 | 139.99 | 0.00 | 0.00 | 0.00 |
February | 280.57 | 162.34 | 118.23 | 464.90 | 118.42 | 0.00 | 0.00 | 0.00 |
March | 215.41 | 91.07 | 124.34 | 362.02 | 98.97 | 0.00 | 0.00 | 0.00 |
April | 146.48 | 25.69 | 120.79 | 268.20 | 69.23 | 0.00 | 0.00 | 0.00 |
May | 117.38 | 2.54 | 114.84 | 233.90 | 35.11 | 0.00 | 0.00 | 0.00 |
June | 111.91 | 0.21 | 111.70 | 239.00 | 18.17 | 0.00 | 0.00 | 0.00 |
July | 119.82 | 1.11 | 118.71 | 268.59 | 24.67 | 0.00 | 0.00 | 0.00 |
August | 136.00 | 11.48 | 124.52 | 288.23 | 19.74 | 0.00 | 0.00 | 0.00 |
September | 174.09 | 42.66 | 131.43 | 370.79 | 28.94 | 0.00 | 0.00 | 0.00 |
October | 239.41 | 112.33 | 127.09 | 455.24 | 44.59 | 0.00 | 0.00 | 0.00 |
November | 272.40 | 152.03 | 120.37 | 467.95 | 76.91 | 0.00 | 0.00 | 0.00 |
December | 298.89 | 188.52 | 110.37 | 480.17 | 123.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 201.51 | 82.27 | 119.24 | 365.13 | 66.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 111.91 | 0.21 | 108.65 | 233.90 | 18.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 310.14 | 201.49 | 131.43 | 488.54 | 139.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.37 | 30.77 | 40.60 | 99.56 | 74.28 | 0.00 | 0.00 | 0.00 |
February | 89.24 | 40.39 | 48.85 | 138.94 | 62.09 | 0.00 | 0.00 | 0.00 |
March | 111.13 | 50.75 | 60.38 | 175.31 | 50.96 | 0.00 | 0.00 | 0.00 |
April | 122.32 | 56.64 | 65.68 | 211.05 | 34.20 | 0.00 | 0.00 | 0.00 |
May | 111.51 | 42.93 | 68.59 | 210.67 | 17.88 | 0.00 | 0.00 | 0.00 |
June | 94.49 | 26.50 | 67.98 | 189.69 | 9.23 | 0.00 | 0.00 | 0.00 |
July | 105.60 | 32.67 | 72.93 | 217.33 | 12.19 | 0.00 | 0.00 | 0.00 |
August | 105.36 | 34.34 | 71.02 | 206.34 | 9.96 | 0.00 | 0.00 | 0.00 |
September | 89.88 | 26.50 | 63.37 | 181.39 | 14.38 | 0.00 | 0.00 | 0.00 |
October | 89.41 | 34.85 | 54.55 | 165.75 | 22.52 | 0.00 | 0.00 | 0.00 |
November | 73.75 | 27.05 | 46.70 | 123.55 | 40.40 | 0.00 | 0.00 | 0.00 |
December | 73.89 | 33.03 | 40.85 | 110.03 | 63.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.87 | 36.36 | 58.51 | 169.30 | 34.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.37 | 26.50 | 40.60 | 99.56 | 9.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.32 | 56.64 | 72.93 | 217.33 | 74.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.212777E+09 | 0.101933E+09 | 0.110844E+09 | 0.300534E+09 | 0.191279E+09 |
February | 0.221911E+09 | 0.102723E+09 | 0.119188E+09 | 0.337715E+09 | 0.143746E+09 |
March | 0.299966E+09 | 0.141811E+09 | 0.158155E+09 | 0.462194E+09 | 0.129155E+09 |
April | 0.315037E+09 | 0.140568E+09 | 0.174469E+09 | 0.539495E+09 | 87516145.14 |
May | 0.307973E+09 | 0.122642E+09 | 0.185331E+09 | 0.576073E+09 | 45749908.94 |
June | 0.294168E+09 | 0.112988E+09 | 0.181180E+09 | 0.577581E+09 | 22369139.09 |
July | 0.312336E+09 | 0.112635E+09 | 0.199701E+09 | 0.634181E+09 | 32546411.38 |
August | 0.285604E+09 | 95499837.23 | 0.190105E+09 | 0.557947E+09 | 25622450.52 |
September | 0.266459E+09 | 96325817.84 | 0.170133E+09 | 0.528872E+09 | 36574051.06 |
October | 0.253440E+09 | 0.109147E+09 | 0.144294E+09 | 0.466468E+09 | 58332150.42 |
November | 0.199065E+09 | 79374616.44 | 0.119690E+09 | 0.327879E+09 | 99081185.98 |
December | 0.166161E+09 | 58662720.71 | 0.107498E+09 | 0.236577E+09 | 0.168753E+09 |
Annual Sum or Average | 0.313490E+10 | 0.127431E+10 | 0.186059E+10 | 0.554552E+10 | 0.104072E+10 |
Minimum of Months | 0.166161E+09 | 58662720.71 | 0.107498E+09 | 0.236577E+09 | 22369139.09 |
Maximum of Months | 0.315037E+09 | 0.141811E+09 | 0.199701E+09 | 0.634181E+09 | 0.191279E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.830684E+09 | 0.539676E+09 | 0.291008E+09 | 0.130849E+10 | 0.374941E+09 |
February | 0.678752E+09 | 0.392741E+09 | 0.286011E+09 | 0.112469E+10 | 0.286480E+09 |
March | 0.576963E+09 | 0.243935E+09 | 0.333028E+09 | 0.969625E+09 | 0.265075E+09 |
April | 0.379669E+09 | 66579094.78 | 0.313090E+09 | 0.695179E+09 | 0.179451E+09 |
May | 0.314385E+09 | 6801620.14 | 0.307583E+09 | 0.626484E+09 | 94045367.94 |
June | 0.290070E+09 | 547408.41 | 0.289522E+09 | 0.619492E+09 | 47090330.54 |
July | 0.320939E+09 | 2974812.78 | 0.317964E+09 | 0.719392E+09 | 66065122.63 |
August | 0.364255E+09 | 30737752.68 | 0.333518E+09 | 0.772007E+09 | 52869992.89 |
September | 0.451253E+09 | 0.110580E+09 | 0.340673E+09 | 0.961090E+09 | 75020655.81 |
October | 0.641248E+09 | 0.300853E+09 | 0.340395E+09 | 0.121931E+10 | 0.119427E+09 |
November | 0.706063E+09 | 0.394061E+09 | 0.312002E+09 | 0.121294E+10 | 0.199357E+09 |
December | 0.800547E+09 | 0.504939E+09 | 0.295607E+09 | 0.128609E+10 | 0.329928E+09 |
Annual Sum or Average | 0.635483E+10 | 0.259443E+10 | 0.376040E+10 | 0.115148E+11 | 0.208975E+10 |
Minimum of Months | 0.290070E+09 | 547408.41 | 0.286011E+09 | 0.619492E+09 | 47090330.54 |
Maximum of Months | 0.830684E+09 | 0.539676E+09 | 0.340673E+09 | 0.130849E+10 | 0.374941E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191145E+09 | 82405261.42 | 0.108740E+09 | 0.266662E+09 | 0.198965E+09 |
February | 0.215891E+09 | 97702725.84 | 0.118188E+09 | 0.336129E+09 | 0.150207E+09 |
March | 0.297655E+09 | 0.135925E+09 | 0.161731E+09 | 0.469552E+09 | 0.136492E+09 |
April | 0.317063E+09 | 0.146810E+09 | 0.170253E+09 | 0.547030E+09 | 88655407.05 |
May | 0.298679E+09 | 0.114977E+09 | 0.183702E+09 | 0.564268E+09 | 47899210.41 |
June | 0.244909E+09 | 68699123.37 | 0.176210E+09 | 0.491668E+09 | 23933952.89 |
July | 0.282832E+09 | 87499150.42 | 0.195333E+09 | 0.582086E+09 | 32642067.13 |
August | 0.282189E+09 | 91964615.15 | 0.190224E+09 | 0.552663E+09 | 26678871.13 |
September | 0.232957E+09 | 68691435.21 | 0.164265E+09 | 0.470163E+09 | 37263186.28 |
October | 0.239474E+09 | 93354144.07 | 0.146120E+09 | 0.443932E+09 | 60315633.13 |
November | 0.191169E+09 | 70121619.76 | 0.121047E+09 | 0.320230E+09 | 0.104713E+09 |
December | 0.197894E+09 | 88476911.85 | 0.109417E+09 | 0.294697E+09 | 0.171088E+09 |
Annual Sum or Average | 0.299186E+10 | 0.114663E+10 | 0.184523E+10 | 0.533908E+10 | 0.107885E+10 |
Minimum of Months | 0.191145E+09 | 68691435.21 | 0.108740E+09 | 0.266662E+09 | 23933952.89 |
Maximum of Months | 0.317063E+09 | 0.146810E+09 | 0.195333E+09 | 0.582086E+09 | 0.198965E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 694.61 | 280.00 | 460.95 | 270.32 | 190.63 | 0.00 | 0.00 |
February | 739.28 | 235.76 | 461.54 | 245.19 | 216.35 | 0.00 | 0.00 |
March | 702.73 | 190.99 | 438.54 | 194.77 | 243.77 | 0.00 | 0.00 |
April | 684.50 | 134.32 | 390.34 | 136.56 | 253.79 | 0.00 | 0.00 |
May | 658.66 | 69.08 | 343.88 | 91.26 | 252.62 | 0.00 | 0.00 |
June | 650.86 | 35.37 | 319.89 | 70.31 | 249.58 | 0.00 | 0.00 |
July | 722.37 | 48.68 | 342.04 | 75.83 | 266.20 | 0.00 | 0.00 |
August | 702.76 | 39.13 | 347.99 | 81.47 | 266.52 | 0.00 | 0.00 |
September | 755.73 | 56.94 | 366.77 | 106.33 | 260.44 | 0.00 | 0.00 |
October | 794.59 | 88.34 | 423.45 | 187.93 | 235.52 | 0.00 | 0.00 |
November | 716.01 | 153.55 | 422.95 | 209.71 | 213.25 | 0.00 | 0.00 |
December | 675.59 | 247.13 | 434.81 | 243.46 | 191.35 | 0.00 | 0.00 |
Annual Sum or Average | 707.96 | 131.15 | 395.79 | 159.04 | 236.75 | 0.00 | 0.00 |
Minimum of Months | 650.86 | 35.37 | 319.89 | 70.31 | 190.63 | 0.00 | 0.00 |
Maximum of Months | 794.59 | 280.00 | 461.54 | 270.32 | 266.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.186045E+10 | 0.749947E+09 | 0.123461E+10 | 0.724015E+09 | 0.510591E+09 | 0.00 | 0.00 |
February | 0.178846E+10 | 0.570355E+09 | 0.111655E+10 | 0.593167E+09 | 0.523387E+09 | 0.00 | 0.00 |
March | 0.188219E+10 | 0.511542E+09 | 0.117458E+10 | 0.521670E+09 | 0.652914E+09 | 0.00 | 0.00 |
April | 0.177423E+10 | 0.348148E+09 | 0.101177E+10 | 0.353958E+09 | 0.657812E+09 | 0.00 | 0.00 |
May | 0.176416E+10 | 0.185032E+09 | 0.921037E+09 | 0.244421E+09 | 0.676616E+09 | 0.00 | 0.00 |
June | 0.168702E+10 | 91671210.52 | 0.829147E+09 | 0.182234E+09 | 0.646913E+09 | 0.00 | 0.00 |
July | 0.193480E+10 | 0.130397E+09 | 0.916107E+09 | 0.203109E+09 | 0.712998E+09 | 0.00 | 0.00 |
August | 0.188226E+10 | 0.104817E+09 | 0.932048E+09 | 0.218202E+09 | 0.713846E+09 | 0.00 | 0.00 |
September | 0.195886E+10 | 0.147595E+09 | 0.950669E+09 | 0.275598E+09 | 0.675071E+09 | 0.00 | 0.00 |
October | 0.212824E+10 | 0.236602E+09 | 0.113416E+10 | 0.503354E+09 | 0.630808E+09 | 0.00 | 0.00 |
November | 0.185589E+10 | 0.398000E+09 | 0.109630E+10 | 0.543557E+09 | 0.552739E+09 | 0.00 | 0.00 |
December | 0.180951E+10 | 0.661907E+09 | 0.116460E+10 | 0.652079E+09 | 0.512523E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223261E+11 | 0.413601E+10 | 0.124816E+11 | 0.501536E+10 | 0.746622E+10 | 0.00 | 0.00 |
Minimum of Months | 0.168702E+10 | 91671210.52 | 0.829147E+09 | 0.182234E+09 | 0.510591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.212824E+10 | 0.749947E+09 | 0.123461E+10 | 0.724015E+09 | 0.713846E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.100995E+11 | -0.943667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -662823189.4 | 58.98 | 0.00 | 0.00 |
February | 0.903722E+10 | -0.844025E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -596968655.7 | 58.98 | 0.00 | 0.00 |
March | 0.973496E+10 | -0.907579E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -659169335.2 | 58.99 | 0.00 | 0.00 |
April | 0.898724E+10 | -0.835545E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -631788062.8 | 58.98 | 0.00 | 0.00 |
May | 0.886206E+10 | -0.821183E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -650228074.3 | 58.98 | 0.00 | 0.00 |
June | 0.825442E+10 | -0.762992E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -624502770.1 | 58.98 | 0.00 | 0.00 |
July | 0.836415E+10 | -0.772221E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -641939094.4 | 58.98 | 0.00 | 0.00 |
August | 0.848179E+10 | -0.783919E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -642597918.8 | 58.99 | 0.00 | 0.00 |
September | 0.848002E+10 | -0.785559E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -624425988.9 | 58.98 | 0.00 | 0.00 |
October | 0.919127E+10 | -0.854276E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -648508720.9 | 58.98 | 0.00 | 0.00 |
November | 0.932479E+10 | -0.869223E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -632556586.2 | 58.98 | 0.00 | 0.00 |
December | 0.995337E+10 | -0.929236E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -661011601.5 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.108771E+12 | -0.101094E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.767652E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.825442E+10 | -0.943667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -662823189.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.100995E+11 | -0.762992E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -596968655.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.64 | 0.62 | 01-JAN-07:40 | 1533.58 | 24.65 | 119.50 | 292.00 | 1536.14 | 24.34 | 116.33 | 290.50 |
February | 304.33 | 0.64 | 0.62 | 01-FEB-07:49 | 1299.24 | 22.20 | 87.00 | 282.83 | 1217.46 | 20.14 | 46.83 | 274.83 |
March | 362.67 | 0.63 | 0.62 | 01-MAR-07:19 | 1093.49 | 18.20 | 3.67 | 343.17 | 1103.17 | 18.10 | 1.83 | 343.17 |
April | 357.50 | 0.64 | 0.62 | 01-APR-07:10 | 1027.23 | 17.63 | 0.00 | 337.50 | 1108.48 | 17.74 | 0.00 | 336.67 |
May | 389.00 | 0.64 | 0.62 | 01-MAY-06:19 | 914.71 | 17.31 | 0.00 | 366.33 | 1104.49 | 17.32 | 0.00 | 363.83 |
June | 388.17 | 0.65 | 0.62 | 01-JUN-06:40 | 805.41 | 16.78 | 0.00 | 343.00 | 1075.71 | 16.73 | 0.00 | 348.67 |
July | 403.83 | 0.64 | 0.62 | 01-JUL-06:40 | 904.12 | 17.56 | 0.00 | 367.50 | 979.26 | 17.54 | 0.00 | 368.67 |
August | 348.33 | 0.64 | 0.62 | 01-AUG-06:49 | 999.42 | 17.92 | 0.00 | 351.17 | 1040.88 | 17.97 | 0.00 | 353.50 |
September | 349.67 | 0.64 | 0.62 | 01-SEP-06:00 | 971.79 | 18.41 | 7.00 | 323.00 | 1100.49 | 18.32 | 6.67 | 324.00 |
October | 323.50 | 0.64 | 0.62 | 02-OCT-07:10 | 1182.96 | 20.86 | 61.00 | 315.83 | 1171.23 | 20.67 | 53.17 | 315.00 |
November | 314.83 | 0.64 | 0.62 | 01-NOV-06:00 | 1204.33 | 23.12 | 105.83 | 291.83 | 1099.96 | 20.97 | 54.50 | 291.00 |
December | 282.67 | 0.64 | 0.62 | 01-DEC-08:39 | 1489.37 | 24.39 | 109.17 | 278.67 | 1427.43 | 23.92 | 97.67 | 277.17 |
Annual Sum or Average | 4111.50 | 0.64 | 1095.39 | 19.62 | 493.17 | 3892.83 | 1149.57 | 19.23 | 377.00 | 3887.00 | ||
Minimum of Months | 282.67 | 0.63 | 0.62 | 805.41 | 16.78 | 0.00 | 278.67 | 979.26 | 16.73 | 0.00 | 274.83 | |
Maximum of Months | 403.83 | 0.65 | 0.62 | 1533.58 | 24.65 | 119.50 | 367.50 | 1536.14 | 24.34 | 116.33 | 368.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263306E+09 | 6608.48 | 25-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362403E+09 | 13069.37 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286722E+09 | 9770.16 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 50240456.40 | 4697.69 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373140E+09 | 7936.21 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373140E+09 | 13069.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17204989.25 | 6371.20 | 04-FEB-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17204989.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17204989.25 | 6371.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134554E+11 | 0.792338E+10 | 43281.14 | 07-JAN-05:01 | 19843.48 | 0.00 |
February | 0.00 | 0.00 | 0.163025E+11 | 0.101032E+11 | 48127.66 | 17-FEB-05:01 | 25052.64 | 0.00 |
March | 0.00 | 0.00 | 0.208524E+11 | 0.119849E+11 | 55826.78 | 14-MAR-04:01 | 25368.31 | 0.00 |
April | 0.00 | 0.00 | 0.279383E+11 | 0.165769E+11 | 52832.54 | 14-APR-04:01 | 25975.93 | 0.00 |
May | 0.00 | 0.00 | 0.420693E+11 | 0.226305E+11 | 55826.78 | 30-MAY-04:01 | 23660.99 | 0.00 |
June | 0.00 | 0.00 | 0.499633E+11 | 0.247629E+11 | 55826.78 | 23-JUN-04:01 | 24208.84 | 0.00 |
July | 0.00 | 0.00 | 0.548051E+11 | 0.276821E+11 | 55826.78 | 11-JUL-04:01 | 24478.76 | 0.00 |
August | 0.00 | 0.00 | 0.546097E+11 | 0.269593E+11 | 55826.78 | 01-AUG-04:01 | 25326.44 | 0.00 |
September | 0.00 | 0.00 | 0.506093E+11 | 0.254642E+11 | 55826.78 | 12-SEP-04:01 | 26355.89 | 0.00 |
October | 0.00 | 0.00 | 0.446574E+11 | 0.233158E+11 | 55826.78 | 04-OCT-04:01 | 22067.52 | 0.00 |
November | 0.00 | 0.00 | 0.311673E+11 | 0.163623E+11 | 55826.78 | 10-NOV-05:01 | 25503.92 | 0.00 |
December | 0.00 | 0.00 | 0.177414E+11 | 0.963230E+10 | 55826.78 | 26-DEC-05:01 | 25122.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.424171E+12 | 0.223398E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.134554E+11 | 0.792338E+10 | 43281.14 | 19843.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548051E+11 | 0.276821E+11 | 55826.78 | 26355.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200023E+11 | 0.109748E+11 | 34458.66 | 02-JAN-13:55 | 16575.72 | 0.00 |
February | 0.00 | 0.00 | 0.224510E+11 | 0.130127E+11 | 34458.66 | 11-FEB-11:53 | 16894.46 | 0.00 |
March | 0.00 | 0.00 | 0.290789E+11 | 0.156457E+11 | 34458.66 | 04-MAR-12:10 | 17793.06 | 0.00 |
April | 0.00 | 0.00 | 0.368046E+11 | 0.210801E+11 | 34458.66 | 01-APR-15:50 | 15723.34 | 0.00 |
May | 0.00 | 0.00 | 0.553521E+11 | 0.287115E+11 | 34458.66 | 02-MAY-10:48 | 19891.69 | 0.00 |
June | 0.00 | 0.00 | 0.652891E+11 | 0.310599E+11 | 34458.66 | 05-JUN-19:50 | 15418.93 | 0.00 |
July | 0.00 | 0.00 | 0.688341E+11 | 0.337964E+11 | 34458.66 | 10-JUL-18:30 | 16756.89 | 0.00 |
August | 0.00 | 0.00 | 0.696107E+11 | 0.329380E+11 | 34458.66 | 03-AUG-19:25 | 15236.56 | 0.00 |
September | 0.00 | 0.00 | 0.648357E+11 | 0.311355E+11 | 34458.66 | 06-SEP-20:40 | 16900.53 | 0.00 |
October | 0.00 | 0.00 | 0.578910E+11 | 0.284517E+11 | 34458.66 | 04-OCT-07:13 | 11183.87 | 0.00 |
November | 0.00 | 0.00 | 0.418179E+11 | 0.203138E+11 | 34458.66 | 03-NOV-10:45 | 16928.28 | 0.00 |
December | 0.00 | 0.00 | 0.264943E+11 | 0.130806E+11 | 34458.66 | 23-DEC-11:38 | 13379.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.558462E+12 | 0.280201E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200023E+11 | 0.109748E+11 | 34458.66 | 11183.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.696107E+11 | 0.337964E+11 | 34458.66 | 19891.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3815.81 | 13889.39 | 18-JAN-13:53 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3781.14 | 13853.27 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3683.75 | 13580.02 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3515.90 | 13037.87 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 3361.31 | 12410.08 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 3239.81 | 11831.06 | 01-JUN-12:43 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 3176.57 | 11488.53 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 3223.92 | 11742.25 | 31-AUG-12:25 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 3324.15 | 12267.96 | 30-SEP-12:17 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3482.87 | 12916.36 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 3647.78 | 13476.36 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 3760.72 | 13830.75 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 3499.60 | ||||
Minimum of Months | 0.00 | 0.00 | 3176.57 | 11488.53 | ||
Maximum of Months | 0.00 | 0.00 | 3815.81 | 13889.39 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127238E+10 | 0.25 | 503.64 | 01-JAN-00:05 | 0.26 |
February | 0.115017E+10 | 0.25 | 503.64 | 01-FEB-00:10 | 0.26 |
March | 0.127707E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.26 |
April | 0.124591E+10 | 0.25 | 503.64 | 01-APR-00:15 | 0.26 |
May | 0.128770E+10 | 0.25 | 503.64 | 01-MAY-00:13 | 0.26 |
June | 0.124753E+10 | 0.25 | 503.64 | 01-JUN-00:05 | 0.26 |
July | 0.128898E+10 | 0.25 | 503.64 | 01-JUL-00:05 | 0.26 |
August | 0.128917E+10 | 0.25 | 503.64 | 01-AUG-00:05 | 0.26 |
September | 0.124704E+10 | 0.25 | 503.64 | 01-SEP-00:05 | 0.26 |
October | 0.128789E+10 | 0.25 | 503.64 | 01-OCT-00:05 | 0.26 |
November | 0.124248E+10 | 0.25 | 503.64 | 01-NOV-00:10 | 0.26 |
December | 0.127221E+10 | 0.25 | 503.64 | 01-DEC-00:01 | 0.26 |
Annual Sum or Average | 0.151085E+11 | 0.25 | |||
Minimum of Months | 0.115017E+10 | 0.25 | 503.64 | 0.26 | |
Maximum of Months | 0.128917E+10 | 0.25 | 503.64 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196782E+10 | 0.44 | 1609.22 | 07-JAN-05:01 | 0.75 |
February | 0.178066E+10 | 0.45 | 1874.64 | 17-FEB-05:01 | 0.81 |
March | 0.197078E+10 | 0.45 | 2194.67 | 14-MAR-04:01 | 0.87 |
April | 0.191165E+10 | 0.45 | 2070.19 | 14-APR-04:01 | 0.85 |
May | 0.202678E+10 | 0.46 | 2194.67 | 29-MAY-04:01 | 0.87 |
June | 0.208913E+10 | 0.48 | 2194.67 | 06-JUN-04:01 | 0.87 |
July | 0.224692E+10 | 0.49 | 2194.67 | 11-JUL-04:01 | 0.87 |
August | 0.222825E+10 | 0.49 | 2194.67 | 01-AUG-04:01 | 0.87 |
September | 0.212036E+10 | 0.48 | 2194.67 | 08-SEP-04:01 | 0.87 |
October | 0.206297E+10 | 0.47 | 2194.67 | 03-OCT-04:01 | 0.87 |
November | 0.192868E+10 | 0.46 | 2194.67 | 10-NOV-05:01 | 0.87 |
December | 0.197282E+10 | 0.45 | 2194.67 | 26-DEC-05:01 | 0.87 |
Annual Sum or Average | 0.243068E+11 | 0.46 | |||
Minimum of Months | 0.178066E+10 | 0.44 | 1609.22 | 0.75 | |
Maximum of Months | 0.224692E+10 | 0.49 | 2194.67 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140073E+10 | 0.54 | 1401.63 | 02-JAN-13:50 | 0.90 |
February | 0.129395E+10 | 0.55 | 1401.63 | 07-FEB-04:31 | 0.90 |
March | 0.151420E+10 | 0.57 | 1401.63 | 04-MAR-05:01 | 0.90 |
April | 0.160302E+10 | 0.59 | 1401.63 | 01-APR-02:11 | 0.90 |
May | 0.220887E+10 | 0.68 | 1401.63 | 02-MAY-03:21 | 0.90 |
June | 0.263762E+10 | 0.75 | 1401.63 | 01-JUN-02:61 | 0.90 |
July | 0.281008E+10 | 0.76 | 1401.63 | 01-JUL-02:61 | 0.90 |
August | 0.283199E+10 | 0.77 | 1401.63 | 01-AUG-02:62 | 0.89 |
September | 0.262278E+10 | 0.75 | 1401.63 | 01-SEP-02:61 | 0.90 |
October | 0.232944E+10 | 0.70 | 1401.63 | 01-OCT-02:62 | 0.89 |
November | 0.186070E+10 | 0.63 | 1401.63 | 01-NOV-04:01 | 0.90 |
December | 0.153742E+10 | 0.57 | 1401.63 | 01-DEC-04:21 | 0.90 |
Annual Sum or Average | 0.246508E+11 | 0.66 | |||
Minimum of Months | 0.129395E+10 | 0.54 | 1401.63 | 0.89 | |
Maximum of Months | 0.283199E+10 | 0.77 | 1401.63 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 53.01 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.82 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:05 | 0.00 | 0.00 | 53.51 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 54.27 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 53.21 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.38 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 54.27 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 54.72 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 54.25 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.91 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.25 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.51 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 53.01 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 54.72 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 44.26 | 44.26 | 3815.81 | 13889.39 | 18-JAN-13:53 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53.94 | 53.94 | 3781.14 | 13853.27 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.70 | 53.70 | 3683.75 | 13580.02 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 54.56 | 54.56 | 3515.90 | 13037.87 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 45.90 | 45.90 | 3361.31 | 12410.08 | 01-MAY-12:20 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 54.34 | 54.34 | 3239.81 | 11831.06 | 01-JUN-12:43 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 54.57 | 54.57 | 3176.57 | 11488.53 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 54.66 | 54.66 | 3223.92 | 11742.25 | 31-AUG-12:25 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 54.56 | 54.56 | 3324.15 | 12267.96 | 30-SEP-12:17 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 46.08 | 46.08 | 3482.87 | 12916.36 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.26 | 54.26 | 3647.78 | 13476.36 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 53.55 | 53.55 | 3760.72 | 13830.75 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 3499.60 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.26 | 44.26 | 3176.57 | 11488.53 | ||
Maximum of Months | 0.00 | 0.00 | 54.66 | 54.66 | 3815.81 | 13889.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.555420E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.611320E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.741973E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.910207E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123290E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.139652E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.153515E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.151997E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.141908E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.128794E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.963769E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.656989E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.128312E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.555420E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.153515E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.622934E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.666879E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.836412E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.101849E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.147274E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.173446E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184767E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.185833E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.172739E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.154053E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.114249E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.778808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152471E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.622934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.185833E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196782E+10 | 0.134554E+11 | 0.263306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178066E+10 | 0.163025E+11 | 0.362403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197078E+10 | 0.208524E+11 | 0.286722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191165E+10 | 0.279383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202678E+10 | 0.420693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208913E+10 | 0.499633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224692E+10 | 0.548051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222825E+10 | 0.546097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212036E+10 | 0.506093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206297E+10 | 0.446574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192868E+10 | 0.311673E+11 | 50240456.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197282E+10 | 0.177414E+11 | 0.373140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243068E+11 | 0.424171E+12 | 0.133581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178066E+10 | 0.134554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224692E+10 | 0.548051E+11 | 0.373140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140073E+10 | 0.200023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129395E+10 | 0.224510E+11 | 17204989.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151420E+10 | 0.290789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160302E+10 | 0.368046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220887E+10 | 0.553521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263762E+10 | 0.652891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281008E+10 | 0.688341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.283199E+10 | 0.696107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262278E+10 | 0.648357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232944E+10 | 0.578910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186070E+10 | 0.418179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153742E+10 | 0.264943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246508E+11 | 0.558462E+12 | 17204989.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129395E+10 | 0.200023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.283199E+10 | 0.696107E+11 | 17204989.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.196782E+10 | 0.00 | 0.00 | 0.00 | 0.358638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178066E+10 | 0.00 | 0.00 | 0.00 | 0.433253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197078E+10 | 0.00 | 0.00 | 0.00 | 0.544896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191165E+10 | 0.00 | 0.00 | 0.00 | 0.719042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202678E+10 | 0.00 | 0.00 | 0.00 | 0.103023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.208913E+10 | 0.00 | 0.00 | 0.00 | 0.118760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.224692E+10 | 0.00 | 0.00 | 0.00 | 0.131046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222825E+10 | 0.00 | 0.00 | 0.00 | 0.129715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212036E+10 | 0.00 | 0.00 | 0.00 | 0.120705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206297E+10 | 0.00 | 0.00 | 0.00 | 0.108164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192868E+10 | 0.00 | 0.00 | 0.00 | 0.770901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197282E+10 | 0.00 | 0.00 | 0.00 | 0.459706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243068E+11 | 0.00 | 0.00 | 0.00 | 0.104006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178066E+10 | 0.00 | 0.00 | 0.00 | 0.358638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.224692E+10 | 0.00 | 0.00 | 0.00 | 0.131046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140073E+10 | 0.00 | 0.00 | 0.00 | 0.482861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129395E+10 | 0.00 | 0.00 | 0.00 | 0.537484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151420E+10 | 0.00 | 0.00 | 0.00 | 0.684992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160302E+10 | 0.00 | 0.00 | 0.00 | 0.858185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220887E+10 | 0.00 | 0.00 | 0.00 | 0.125185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263762E+10 | 0.00 | 0.00 | 0.00 | 0.147070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281008E+10 | 0.00 | 0.00 | 0.00 | 0.156666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.283199E+10 | 0.00 | 0.00 | 0.00 | 0.157513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262278E+10 | 0.00 | 0.00 | 0.00 | 0.146511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232944E+10 | 0.00 | 0.00 | 0.00 | 0.130759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186070E+10 | 0.00 | 0.00 | 0.00 | 0.956419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153742E+10 | 0.00 | 0.00 | 0.00 | 0.625066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246508E+11 | 0.00 | 0.00 | 0.00 | 0.127820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129395E+10 | 0.00 | 0.00 | 0.00 | 0.482861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.283199E+10 | 0.00 | 0.00 | 0.00 | 0.157513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280524E+10 | 0.144425E+10 | 0.00 | 14408960.08 | 4334759.51 | 55976549.42 | 0.239288E+10 | 0.00 | 3.60 |
February | 0.156051E+10 | 0.169623E+10 | 0.00 | 14417873.07 | 4238430.34 | 0.188522E+09 | 0.144334E+10 | 0.00 | 3.59 |
March | 0.148151E+10 | 0.279463E+10 | 0.00 | 11996275.08 | 10764477.28 | 0.142406E+09 | 0.127509E+10 | 0.00 | 3.60 |
April | 0.226320E+09 | 0.452675E+10 | 0.00 | 7654399.70 | 22788961.70 | 0.00 | 0.514985E+09 | 0.00 | 3.61 |
May | 19586969.22 | 0.103990E+11 | 0.00 | 722016.80 | 0.118762E+09 | 0.00 | 28149055.47 | 0.00 | 3.65 |
June | 3332192.68 | 0.144289E+11 | 0.00 | 226503.11 | 0.255384E+09 | 0.00 | 2958943.35 | 0.00 | 3.67 |
July | 8590640.39 | 0.164008E+11 | 0.00 | 322248.30 | 0.240038E+09 | 0.00 | 5210019.62 | 0.00 | 3.66 |
August | 1907812.65 | 0.162168E+11 | 0.00 | 222219.25 | 0.270371E+09 | 0.00 | 2652516.45 | 0.00 | 3.68 |
September | 4047042.88 | 0.144411E+11 | 0.00 | 298037.59 | 0.221670E+09 | 0.00 | 4214288.91 | 0.00 | 3.68 |
October | 19985149.77 | 0.113751E+11 | 0.00 | 781199.26 | 0.144786E+09 | 0.00 | 13883995.65 | 0.00 | 3.67 |
November | 0.618470E+09 | 0.644522E+10 | 0.00 | 7473698.81 | 62449833.28 | 3624222.90 | 0.852302E+09 | 0.00 | 3.63 |
December | 0.210087E+10 | 0.265071E+10 | 0.00 | 11169092.32 | 15749484.33 | 0.116850E+09 | 0.209638E+10 | 0.00 | 3.60 |
Annual Sum or Average | 0.885038E+10 | 0.102819E+12 | 0.00 | 69692523.35 | 0.137134E+10 | 0.507379E+09 | 0.863204E+10 | 0.00 | 3.64 |
Minimum of Months | 1907812.65 | 0.144425E+10 | 0.00 | 222219.25 | 4238430.34 | 0.00 | 2652516.45 | 0.00 | 3.59 |
Maximum of Months | 0.280524E+10 | 0.164008E+11 | 0.00 | 14417873.07 | 0.270371E+09 | 0.188522E+09 | 0.239288E+10 | 0.00 | 3.68 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286272E+10 | 0.204590E+10 | 0.00 | 58267599.51 | 3393647.69 | 0.00 | 0.141762E+11 | 0.00 | 7.67 |
February | 0.224726E+10 | 0.208672E+10 | 0.00 | 55960555.31 | 3622237.99 | 0.00 | 0.928290E+10 | 0.00 | 7.72 |
March | 0.243282E+10 | 0.464812E+10 | 0.00 | 52090453.75 | 12121697.00 | 0.00 | 0.819101E+10 | 0.00 | 7.90 |
April | 0.435591E+09 | 0.599856E+10 | 0.00 | 46989464.21 | 14789888.75 | 0.00 | 0.350532E+10 | 0.00 | 8.21 |
May | 0.109282E+09 | 0.202862E+11 | 0.00 | 5340470.36 | 57996260.22 | 0.00 | 0.368813E+09 | 0.00 | 9.25 |
June | 9975333.30 | 0.302307E+11 | 0.00 | 937878.83 | 85018942.16 | 0.00 | 0.118859E+09 | 0.00 | 10.03 |
July | 28091050.85 | 0.321761E+11 | 0.00 | 1398713.01 | 83182191.36 | 0.00 | 0.151774E+09 | 0.00 | 10.10 |
August | 6264057.29 | 0.333888E+11 | 0.00 | 920973.05 | 89283160.67 | 0.00 | 0.115641E+09 | 0.00 | 10.19 |
September | 25136989.15 | 0.297684E+11 | 0.00 | 1168873.39 | 73982216.04 | 0.00 | 0.144952E+09 | 0.00 | 10.00 |
October | 90276706.99 | 0.224454E+11 | 0.00 | 7965551.82 | 63664465.80 | 0.00 | 0.369412E+09 | 0.00 | 9.45 |
November | 0.958722E+09 | 0.131863E+11 | 0.00 | 26708853.75 | 31999638.32 | 0.00 | 0.451890E+10 | 0.00 | 8.68 |
December | 0.263319E+10 | 0.523907E+10 | 0.00 | 52092482.99 | 15510610.27 | 0.00 | 0.111067E+11 | 0.00 | 7.94 |
Annual Sum or Average | 0.118393E+11 | 0.201500E+12 | 0.00 | 0.309842E+09 | 0.534565E+09 | 0.00 | 0.520505E+11 | 0.00 | 8.93 |
Minimum of Months | 6264057.29 | 0.204590E+10 | 0.00 | 920973.05 | 3393647.69 | 0.00 | 0.115641E+09 | 0.00 | 7.67 |
Maximum of Months | 0.286272E+10 | 0.333888E+11 | 0.00 | 58267599.51 | 89283160.67 | 0.00 | 0.141762E+11 | 0.00 | 10.19 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:32
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.356982E+11 | 0.394252E+10 | 0.387564E+11 | 0.221438E+10 | 0.654924E+11 |
February | 0.399594E+11 | 0.188194E+10 | 0.247038E+11 | 0.167964E+10 | 0.702034E+11 |
March | 0.560172E+11 | 0.105474E+10 | 0.180808E+11 | 0.146032E+10 | 0.875031E+11 |
April | 0.625001E+11 | -0.277468E+10 | -0.176803E+10 | 0.896520E+09 | 0.107469E+12 |
May | 0.613851E+11 | -0.919749E+10 | -0.357861E+11 | 0.415354E+09 | 0.148085E+12 |
June | 0.553804E+11 | -0.132225E+11 | -0.550132E+11 | -76084602.5 | 0.169700E+12 |
July | 0.605253E+11 | -0.147788E+11 | -0.591718E+11 | -15511941.1 | 0.182664E+12 |
August | 0.632153E+11 | -0.149130E+11 | -0.605509E+11 | -122804509.9 | 0.182761E+12 |
September | 0.486421E+11 | -0.134224E+11 | -0.539114E+11 | 59528172.65 | 0.169931E+12 |
October | 0.464932E+11 | -0.105754E+11 | -0.398201E+11 | 0.301760E+09 | 0.154345E+12 |
November | 0.340506E+11 | -0.501963E+10 | -0.937583E+10 | 0.115198E+10 | 0.113326E+12 |
December | 0.344290E+11 | 0.208205E+10 | 0.249305E+11 | 0.182689E+10 | 0.785031E+11 |
Annual Sum or Average | 0.598296E+12 | -0.749428E+11 | -0.208926E+12 | 0.979198E+10 | 0.152998E+13 |
Minimum of Months | 0.340506E+11 | -0.149130E+11 | -0.605509E+11 | -122804509.9 | 0.654924E+11 |
Maximum of Months | 0.632153E+11 | 0.394252E+10 | 0.387564E+11 | 0.221438E+10 | 0.182761E+12 |