Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:29:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2494.70 | 10737.17 | 10737.17 |
Net Site Energy | 2494.70 | 10737.17 | 10737.17 |
Total Source Energy | 3818.19 | 16433.42 | 16433.42 |
Net Source Energy | 3818.19 | 16433.42 | 16433.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1221.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 116.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 260.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 61.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 534.77 | 1959.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1221.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 116.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 260.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 15.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 27.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1221.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 116.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 260.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 61.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 312.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 534.10 | 6381.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1455.13 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2301.65 | 8435.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 312.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 534.10 | 6381.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1455.13 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2301.65 | 8435.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 534.771 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 534.771 | 100.00 |
Total On-Site and Utility Electric Sources | 534.771 | 100.00 |
Total Electricity End Uses | 534.771 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 24.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4670.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 11.3960 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 10.1539 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.7750 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.7750 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 11.3960 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.1539 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.7750 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 10.7750 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.7750 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:00 | 12-JAN-11:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 172699.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7649.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1793.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14428.03 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24030.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2886.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31135.66 | 223389.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 172699.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7649.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1793.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13060.45 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 24030.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 526.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1313.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1046.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1324.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 370.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 282.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1693.62 | 2124.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5700.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 433.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1593.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1217.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 834.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7289.31 | 9144.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5700.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 98.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 433.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1593.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1217.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 834.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7289.31 | 9144.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.67 |
KITCHEN DIRECT AIR | 1.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.67 | 1.00 | 1.00 | 1.67 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.67 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.25 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.67 | 1788.10 |
PSZ-AC_2:2_ADDAQ FAN | 1.25 | 1378.51 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.67 | 30075.89 | 68994.54 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 23155.82 | 114001.07 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.67 | 0.835522 | 1.67 | 30075.89 | 14334.23 | 30075.89 | 0.800140 | 0.800140 |
PSZ-AC_2:2 COOLING COIL | 1.25 | 0.622544 | 1.25 | 23155.82 | 11077.12 | 23155.82 | 0.800240 | 0.800240 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 68994.54 |
PSZ-AC_2:2 HEATING COIL | 114001.07 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 11.396 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 128.183 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 10.154 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1084.160 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1323.895 | 11.396 | 15.123 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1323.895 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1179.595 | 10.154 | 188.034 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1179.595 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7461 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1870 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1870 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.272 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.272 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.30622557E-12 | 0.12606888E-14 | -0.97473019E-13 | 0.16287023E-15 |
34 | 6 | 0.29032672E-07 | 0.21068370E-09 | 0.66477549E-08 | -0.13713916E-12 |
35 | 5 | -0.19194025E-03 | 0.17986226E-05 | -0.98701398E-04 | 0.65705654E-08 |
36 | 4 | 0.29428936 | 0.87342649E-03 | 0.10045407 | -0.33873504E-04 |
37 | 3 | -7.3087568 | 0.27004109E-01 | -2.3515030 | 0.29216952E-01 |
38 | 2 | 41.011072 | 0.95822947E-01 | 15.316732 | -0.33489883 |
39 | 1 | -80.653014 | 0.43166794E-01 | -29.187976 | 1.0809043 |
40 | 0 | 46.824338 | 0.86691132E-03 | 16.290128 | |
41 | 7 | -0.22605942E-08 | -0.83801070E-15 | 0.53658694E-14 | -0.78225131E-16 |
42 | 6 | 0.52747590E-05 | 0.35786616E-08 | 0.31908477E-02 | -0.26767504E-04 |
43 | 5 | -0.37662132E-03 | 0.21179957E-05 | -0.22378015 | 0.19566408E-02 |
44 | 4 | 0.86460756E-02 | 0.96389694E-04 | 4.8304715 | -0.45273880E-01 |
45 | 3 | -0.75873005E-01 | 0.76630192E-03 | -38.026647 | 0.39871156 |
46 | 2 | 0.26933907 | 0.12746133E-02 | 116.49413 | -1.4180755 |
47 | 1 | -0.38870643 | 0.38815562E-03 | -143.91330 | 2.0491384 |
48 | 0 | 0.18950265 | 0.94317521E-05 | 60.838472 | |
49 | 7 | -0.22605942E-08 | -0.83801070E-15 | 0.53658694E-14 | -0.78225131E-16 |
50 | 6 | 0.52747590E-05 | 0.35786616E-08 | 0.31908477E-02 | -0.26767504E-04 |
51 | 5 | -0.37662132E-03 | 0.21179957E-05 | -0.22378015 | 0.19566408E-02 |
52 | 4 | 0.86460756E-02 | 0.96389694E-04 | 4.8304715 | -0.45273880E-01 |
53 | 3 | -0.75873005E-01 | 0.76630192E-03 | -38.026647 | 0.39871156 |
54 | 2 | 0.26933907 | 0.12746133E-02 | 116.49413 | -1.4180755 |
55 | 1 | -0.38870643 | 0.38815562E-03 | -143.91330 | 2.0491384 |
56 | 0 | 0.18950265 | 0.94317521E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2917_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18621.74742 | 22346.09690 | 1.39254 | 1.67104 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 9122.29672 | 10946.75607 | 0.39514 | 0.47417 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16647.20937 | 19976.65125 | 1.03757 | 1.24509 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 2333.09951 | 2799.71942 | 9.02475E-002 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 23790.67 | 1.67104 | 1.67104 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 41905.39 | 0.47417 | 0.47417 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 20239.96 | 1.24509 | 1.24509 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 111347.57 | 1.14133 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.67104 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24509 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.67104 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.67104 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.67104 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67104 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67104 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67104 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24509 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24509 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24509 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24509 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24509 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24509 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.67104 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.24509 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67104 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67104 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1788.09500 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67104 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67104 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67104 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67104 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67104 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83552 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.67104 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30075.89000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14334.22606 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30075.89000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80014 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80014 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30075.89000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68994.53671 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 68994.53671 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24509 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24509 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1378.51111 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24509 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24509 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24509 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24509 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24509 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62254 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24509 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23155.82000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11077.12404 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23155.82000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80024 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80024 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23155.82000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 114001.07276 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 114001.07276 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 28859.4 | 10.95 | 10.82 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22251.3 | 11.01 | 10.87 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | N/A | 1.657 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | N/A | 1.657 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | N/A | 1.657 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.187 | 0.179 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.187 | 0.179 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1202227144 | 0.5118278211 | Pass | Pass | 0.1242033721 | 0.3283657586 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1206716025 | 0.5741192361 | Pass | Pass | 6.4591756059E-002 | 0.3012183371 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 5.8781340821E-002 | 4.8881565217E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 306.98 | 343.97 | 1606.50 | 11.98 | 486.15 | 2755.57 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.181 | 0.187 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.181 | 0.187 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 1.657 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 1.657 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 11.3960 | 116.17 | 1323.90 | LightsWired | LTG_SCH_DINING | 89.82 | 168.00 | 89.29 | 0.0000 | Y | 22.19 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.1539 | 116.17 | 1179.60 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 10.7750 | 232.34 | 2503.49 | 40.78 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2040.25 | AstronomicalClock | - | 83.06 | 83.06 | 31.81 | |
Exterior Lighting Total | 2040.25 | 31.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30075.89 | 24064.92 | 6010.97 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23155.82 | 18530.21 | 4625.61 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 28859.4 | 10.95 | 10.82 | ||||
PSZ-AC_2:2 COOLING COIL | 22251.3 | 11.01 | 10.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 68994.54 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 114001.07 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.67 | 1788.10 | 1070.05 | 1.00 | 1.34 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1378.51 | 1107.16 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18621.75 | 22346.10 | 192.35 | 1.393 | 1.671 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.88 | 0.00778 | 27.30 | 0.00701 | 0.416 | 0.00 |
KITCHEN | 16647.21 | 19976.65 | 171.96 | 1.038 | 1.245 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00865 | 26.48 | 0.00701 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9122.30 | 10946.76 | 94.23 | 0.395 | 0.474 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00798 | -41.90 | 0.00006 | 0.416 | 0.00 |
KITCHEN | 2333.10 | 2799.72 | 24.10 | 0.090 | 1.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00649 | -41.90 | 0.00006 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.67 | 1.67 | 0.47 | 0.47 | 1.6710 | 1.6710 | 1.6710 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.25 | 1.25 | 1.14 | 1.14 | 1.2451 | 1.2451 | 1.2451 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 30075.890 | 24064.923 | 1.671040 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30075.89 | 27573.46 | 1.671040 | 24.76 | 15.71 | 0.00758966 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 24.8980 | 23.88 | 0.00778293 | 41.5834 | 18610.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 68994.537 | 68994.537 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 68994.54 | 68994.54 | 1.671043 | 5.34 | 5.34 | 0.00600747 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 24.8980 | 21.11 | 0.00797770 | 50.4313 | 9122.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23155.820 | 18530.213 | 1.245090 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 23155.82 | 22702.65 | 1.245090 | 26.45 | 15.93 | 0.00714298 | 11.88 | 10.02 | 0.00700000 | 26.48 | 0.00700575 | 15.82 | 91.6668 | 26.10 | 0.00865253 | 40.4555 | 16647.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 114001.073 | 114001.073 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 114001.07 | 114001.07 | 1.245089 | -36.86 | -36.86 | 0.00065095 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 91.6668 | 18.31 | 0.00710198 | 53.5023 | 730.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30075.890 | 24064.923 | 1.671040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9488 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.671043 | 1.98092003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 30075.89 | 27573.46 | 1.0000 | 1.98091648 | 1.671040 | 24.76 | 15.71 | 0.00758966 | 44209.5 | 11.91 | 10.04 | 0.00700000 | 29633.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30075.89 | 27.40 | 0.00700714 | 16.15 | 0.41605618 | 24.8980 | 23.88 | 0.00778293 | 23.88 | 0.00778293 | 41.5834 | 18610.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68994.537 | 68994.537 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.671043 | 1.98092003 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 68994.54 | 68994.54 | 1.0000 | 1.98092003 | 1.671043 | 5.34 | 5.34 | 0.00600747 | 20448.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68994.54 | -41.90 | 0.00006450 | -41.90 | 0.41605618 | 24.8980 | 21.00 | 0.00797770 | 21.11 | 0.00797770 | 50.4313 | 9122.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23155.820 | 18530.213 | 1.245090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1184 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.245089 | 1.47597736 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 23155.82 | 22702.65 | 1.0000 | 1.47597861 | 1.245090 | 26.45 | 15.93 | 0.00714298 | 44789.9 | 11.88 | 10.02 | 0.00700000 | 29601.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23155.82 | 26.48 | 0.00700575 | 15.82 | 1.14133354 | 91.6668 | 26.06 | 0.00865253 | 26.10 | 0.00865253 | 40.4555 | 16647.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 114001.073 | 114001.073 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.245089 | 1.47597736 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 114001.07 | 114001.07 | 1.0000 | 1.47597736 | 1.245089 | -36.86 | -36.86 | 0.00065095 | -35459.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 114001.07 | -41.90 | 0.00006450 | -41.90 | 1.14133354 | 91.6668 | 18.53 | 0.00710198 | 18.31 | 0.00710198 | 53.5023 | 730.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.67 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.25 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4229.00 | 5861.50 | 3202.33 |
KITCHEN | 5348.00 | 6296.67 | 4661.17 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5358.33 | 6703.00 | 4670.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 135.00 | 0.83 | 24.00 | 0.00 |
KITCHEN | 0.00 | 67.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 135.00 | 68.00 | 24.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.928 | 4.531 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.837 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.092 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.223 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12601219.30 | 0.00 | 12601219.30 | 11393557.54 | 23994776.84 | 13120747.55 | 1443.12 | 6476.94 | 839.94 | 272.98 |
KITCHEN | 30365137.94 | 0.00 | 30365137.94 | 85214.71 | 30450352.65 | 35993094.65 | 1457.88 | 6632.40 | 669.72 | 321.09 |
Total Facility | 42966357.24 | 0.00 | 42966357.24 | 11478772.25 | 54445129.49 | 49113842.20 | 1460.00 | 6732.17 | 925.02 | 476.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4771 | 0.0000 | 0.4771 | 0.4390 | 0.9161 | 0.4161 | 0.00 | 6348.73 | 838.27 |
KITCHEN | 1.1505 | 0.0000 | 1.1505 | 0.0019 | 1.1524 | 1.1413 | 0.00 | 6519.64 | 667.36 |
Total Facility | 1.6276 | 0.0000 | 1.6276 | 0.4408 | 2.0684 | 1.5574 | 0.00 | 6602.61 | 921.24 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17708061.12 | 0.00 | 17708061.12 | 13120747.55 | 1437.10 | 0.46 | 7322.44 | 272.98 |
PSZ-AC_2:2 | 42671105.63 | 0.00 | 42671105.63 | 35993094.65 | 1456.01 | 0.26 | 7303.73 | 321.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6705 | 0.0000 | 0.6705 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6168 | 0.0000 | 1.6168 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 545.72 | 439.88 | 6474.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 730.67 | 6777.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.6450 | 1.0195 | 0.5847 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7426 | 1.6040 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
Electricity:Building | 335.52 | 3013.54 | 01-JAN-01:10 | 19961.31 | 02-JAN-11:10 |
Electricity:Zone:DINING | 92.61 | 454.30 | 01-JAN-01:10 | 5032.19 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 317.66 | 2604.51 | 01-JAN-01:10 | 16445.21 | 02-JAN-11:10 |
InteriorLights:Electricity | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 22.19 | 182.95 | 01-JAN-01:10 | 1097.67 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 22.19 | 182.95 | 01-JAN-01:10 | 1097.67 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 242.91 | 2559.25 | 01-JAN-01:10 | 14929.12 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.25 | 01-JAN-01:10 | 919.51 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.25 | 01-JAN-01:10 | 919.51 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.21 | 1035.59 | 06-APR-22:30 | 4574.20 | 30-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 43.35 | 779.93 | 06-FEB-23:10 | 2576.59 | 09-JUN-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 15.49 | 0.00 | 01-JAN-11:10 | 1500.35 | 09-JUN-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 27.85 | 701.41 | 17-JAN-01:10 | 1076.23 | 06-JUN-03:20 |
ElectricityPurchased:Facility | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
ElectricityPurchased:Plant | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
Cogeneration:ElectricityPurchased | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
ElectricityNet:Plant | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
Cogeneration:ElectricityNet | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
General:Cogeneration:ElectricityNet | 534.77 | 4415.71 | 30-MAY-03:00 | 31135.66 | 22-JUL-11:00 |
Electricity:HVAC | 124.09 | 0.00 | 01-JAN-01:10 | 14187.39 | 29-JUL-17:10 |
Fans:Electricity | 116.88 | 0.00 | 01-JAN-01:10 | 4378.48 | 07-JAN-00:40 |
General:Fans:Electricity | 116.88 | 0.00 | 01-JAN-01:10 | 4378.48 | 07-JAN-00:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 7.21 | 0.00 | 01-JAN-00:10 | 9808.91 | 29-JUL-17:10 |
General:Cooling:Electricity | 7.21 | 0.00 | 01-JAN-00:10 | 9808.91 | 29-JUL-17:10 |
ExteriorLights:Electricity | 31.81 | 0.00 | 01-JAN-11:20 | 2040.25 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 31.81 | 0.00 | 01-JAN-11:20 | 2040.25 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1959.93 | 2560.65 | 01-JAN-01:20 | 223389.86 | 12-JAN-11:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1221.88 | 0.00 | 01-JAN-01:10 | 174058.26 | 12-JAN-07:10 |
Heating:NaturalGas | 1221.88 | 0.00 | 01-JAN-01:10 | 174058.26 | 12-JAN-07:10 |
General:Heating:NaturalGas | 1221.88 | 0.00 | 01-JAN-01:10 | 174058.26 | 12-JAN-07:10 |
NaturalGas:Plant | 260.90 | 722.00 | 01-JAN-01:20 | 33365.76 | 03-JAN-13:20 |
WaterSystems:NaturalGas | 260.90 | 722.00 | 01-JAN-01:20 | 33365.76 | 03-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 260.90 | 722.00 | 01-JAN-01:20 | 33365.76 | 03-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1855.19 | 2739.63 | 12-JAN-01:10 | 214724.77 | 12-JAN-14:00 |
EnergyTransfer:Building | 600.46 | 1369.82 | 12-JAN-01:10 | 62516.45 | 28-NOV-12:10 |
EnergyTransfer:Zone:KITCHEN | 327.13 | 1369.82 | 12-JAN-01:10 | 26668.27 | 02-JUN-04:10 |
Refrigeration:EnergyTransfer | 136.97 | 2699.60 | 06-FEB-23:10 | 7834.84 | 06-JUN-03:20 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.48 | 1349.80 | 06-FEB-23:10 | 3917.42 | 06-JUN-03:20 |
General:Refrigeration:EnergyTransfer | 68.48 | 1349.80 | 06-FEB-23:10 | 3917.42 | 06-JUN-03:20 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.48 | 1349.80 | 06-FEB-23:10 | 3917.42 | 06-JUN-03:20 |
EnergyTransfer:Plant | 251.66 | 1349.81 | 20-FEB-23:10 | 25796.26 | 12-MAY-12:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.14 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 52.34 | 1114.23 | 17-JAN-01:10 | 2238.70 | 06-JUN-03:20 |
EnergyTransfer:Zone:DINING | 273.33 | 0.00 | 01-JAN-01:10 | 47853.47 | 25-NOV-20:00 |
Heating:EnergyTransfer | 238.20 | 0.00 | 01-JAN-00:30 | 47853.47 | 25-NOV-20:00 |
Heating:EnergyTransfer:Zone:DINING | 238.06 | 0.00 | 01-JAN-00:10 | 47853.47 | 25-NOV-20:00 |
General:Heating:EnergyTransfer | 238.20 | 0.00 | 01-JAN-00:30 | 47853.47 | 25-NOV-20:00 |
General:Heating:EnergyTransfer:Zone:DINING | 238.06 | 0.00 | 01-JAN-00:10 | 47853.47 | 25-NOV-20:00 |
Cooling:EnergyTransfer | 293.77 | 0.00 | 01-JAN-01:10 | 27369.64 | 29-AUG-04:10 |
Cooling:EnergyTransfer:Zone:DINING | 35.26 | 0.00 | 01-JAN-01:10 | 17242.16 | 27-FEB-04:40 |
General:Cooling:EnergyTransfer | 293.77 | 0.00 | 01-JAN-01:10 | 27369.64 | 29-AUG-04:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 35.26 | 0.00 | 01-JAN-01:10 | 17242.16 | 27-FEB-04:40 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.14 | 0.00 | 01-JAN-00:20 | 2470.20 | 13-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.14 | 0.00 | 01-JAN-00:20 | 2470.20 | 13-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 258.51 | 0.00 | 01-JAN-01:10 | 22782.96 | 02-JUN-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 258.51 | 0.00 | 01-JAN-01:10 | 22782.96 | 02-JUN-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
PlantLoopHeatingDemand:Plant | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
EnergyTransfer:HVAC | 1003.07 | 0.00 | 01-JAN-01:10 | 139246.61 | 12-JAN-07:10 |
HeatingCoils:EnergyTransfer | 977.50 | 0.00 | 01-JAN-01:10 | 139246.61 | 12-JAN-07:10 |
CoolingCoils:EnergyTransfer | 25.57 | 0.00 | 01-JAN-00:10 | 38382.80 | 29-JUL-17:10 |
WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23246.74 | 13-FEB-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 238.063 | -35.263 | 0.000 | 0.000 | 73.906 | 22.190 | 52.814 | 24.935 | 0.000 | 0.350 | 0.000 | 0.000 | -19.378 | 0.000 | -310.745 | -46.873 |
KITCHEN | 0.000 | 0.000 | 0.138 | -258.504 | 0.000 | 0.000 | 5.516 | 18.589 | 212.059 | 0.000 | 0.000 | 0.000 | 24.375 | 0.000 | 0.000 | 0.000 | -2.174 | -0.002 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.919 | 4.422 | 0.000 | 0.000 | 0.000 | -9.341 | -0.000 |
Total Facility | 0.000 | 0.000 | 238.201 | -293.766 | 0.000 | 0.000 | 79.422 | 40.779 | 264.873 | 24.935 | 0.000 | 5.269 | 28.797 | 0.000 | -19.378 | 0.000 | -322.260 | -46.875 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-04:58 | 0.00 | 0.00 | 0.00 | -38174.64 | 0.00 | 0.00 | 0.00 | 182.95 | 508.77 | 0.00 | 0.00 | 0.00 | 39419.05 | 0.00 | -1936.14 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | -70642.85 | 0.00 | 0.00 | 20.57 | 204.34 | 5273.28 | 0.00 | 0.00 | 0.00 | 65144.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-DEC-05:01 | -38382.22 | 38382.22 | 38382.22 | -70642.85 | 0.00 | 0.00 | 443.99 | 448.27 | 6494.33 | 0.00 | 0.00 | 479.60 | 26227.39 | 0.00 | -1832.95 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 25-NOV-20:00 | 0.00 | 0.00 | 47853.62 | 0.00 | 0.00 | 0.00 | 6477.40 | 1097.67 | 2238.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1565.80 | 0.00 | -52756.48 | -3345.03 |
KITCHEN | 13-JAN-05:02 | 0.00 | 0.00 | 24674.83 | 0.00 | 0.00 | 0.00 | 21.95 | 204.34 | 5273.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30174.40 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-NOV-20:00 | -8887.48 | 8887.48 | 47853.62 | -8887.48 | 0.00 | 0.00 | 6989.67 | 2017.17 | 10766.63 | 0.00 | 0.00 | 414.94 | 0.00 | 0.00 | -1565.80 | 0.00 | -52756.48 | -4832.28 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6710 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6710 | 0.2490 | 1.0000 | Not calculated | 0.4161 | 0.2490 | ||
PSZ-AC_2:2 | 1.2451 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2451 | 0.1215 | 1.0000 | Not calculated | 0.1513 | 0.1215 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6710 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6710 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2490 | ||
PSZ-AC_2:2 | 1.2451 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2451 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1215 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6710 | 1.6710 | 1.6710 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2451 | 1.2451 | 1.2451 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6710 | 1.6710 | 1.6710 | 1.6710 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2451 | 1.2451 | 1.2451 | 1.2451 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6710 | 1.6710 | 1.6710 | No | 0.4161 | 0.8774 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2451 | 1.2451 | 1.2451 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6710 | 1.6710 | 1.6710 | 1.6710 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2451 | 1.2451 | 1.2451 | 1.2451 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 24.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 24.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1221.88 | 174058.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7.21 | 9808.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 40.78 | 2017.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 31.81 | 2040.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 116.88 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 260.90 | 33365.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 15.49 | 1500.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 27.85 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 338.09 | 534.77 |
Natural Gas | 477.16 | 1959.93 |
Additional | 0.00 | 0.00 |
Total | 815.25 | 2494.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.51 |
Space Heating | 0.00 |
Space Cooling | 31.05 |
Fans (All) | 503.05 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2301.65 |
Subtotal | 2301.65 |
Natural Gas [MJ/m2] | |
Space Heating | 5258.94 |
Service Water Heating | 1122.90 |
Miscellaneous (All) | 8435.52 |
Subtotal | 8435.52 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.63 |
Space Heating | 48.98 |
Space Cooling | 0.29 |
Fans (All) | 4.69 |
Service Water Heating | 10.46 |
Receptacle Equipment | 30.23 |
Miscellaneous | 3.73 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4683. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8324.17 | 435.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 7874.83 | 479.67 | 334.00 | 71.50 | 0.00 |
Min | 7874.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 479.67 | 334.00 | 71.50 | 0.00 |
Average | 8319.67 | 305.17 | 111.33 | 23.83 | 0.00 |
Sum | 24959.00 | 915.50 | 334.00 | 71.50 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8202.50 | 557.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 8008.00 | 615.67 | 110.17 | 24.50 | 1.67 |
Min | 8008.00 | 26.67 | 0.00 | 0.00 | 0.00 |
Max | 8733.33 | 615.67 | 110.17 | 24.50 | 1.67 |
Average | 8314.61 | 399.94 | 36.72 | 8.17 | 0.56 |
Sum | 24943.83 | 1199.83 | 110.17 | 24.50 | 1.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254718.67 | 6.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15613.67 | 644.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254718.67 | 644.33 | 0.00 | 0.00 | 0.00 |
Average | 90110.78 | 216.89 | 0.00 | 0.00 | 0.00 |
Sum | 270332.33 | 650.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675537E+09 | 38175.54 | 12-JAN-04:58 | -37.8 | -37.9 | 0.439505E+10 | 3723.61 | 14-JAN-19:10 | -21.8 | -22.0 |
February | 0.623750E+09 | 35176.95 | 27-FEB-04:44 | -35.8 | -35.9 | 0.402307E+10 | 3723.61 | 18-FEB-19:10 | -35.8 | -35.9 |
March | 0.661281E+09 | 21454.60 | 01-MAR-04:46 | -28.2 | -28.6 | 0.449293E+10 | 3723.64 | 18-MAR-18:40 | 2.03 | 0.19 |
April | 0.131990E+10 | 14307.94 | 02-APR-23:01 | -15.8 | -17.1 | 0.434134E+10 | 4012.34 | 21-APR-17:10 | 14.40 | 5.85 |
May | 0.389415E+10 | 12641.38 | 31-MAY-04:01 | 12.12 | 7.61 | 0.480291E+10 | 4681.62 | 13-MAY-18:19 | 12.12 | 7.61 |
June | 0.775732E+10 | 24973.05 | 23-JUN-04:01 | 14.08 | 9.52 | 0.506858E+10 | 4681.82 | 10-JUN-18:00 | 14.08 | 9.52 |
July | 0.949499E+10 | 27288.13 | 25-JUL-04:01 | 14.40 | 13.72 | 0.521906E+10 | 4682.50 | 29-JUL-18:00 | 26.70 | 18.19 |
August | 0.690417E+10 | 25231.04 | 05-AUG-04:01 | 14.82 | 11.92 | 0.509845E+10 | 4682.10 | 26-AUG-18:10 | 20.60 | 14.05 |
September | 0.187603E+10 | 7875.74 | 28-SEP-23:01 | -1.2 | -2.4 | 0.439947E+10 | 4624.91 | 02-SEP-18:10 | -1.2 | -2.4 |
October | 0.753022E+09 | 18498.81 | 22-OCT-04:02 | -18.6 | -18.8 | 0.445016E+10 | 3723.63 | 14-OCT-18:40 | -18.6 | -18.8 |
November | 0.628880E+09 | 23080.73 | 29-NOV-04:09 | -28.9 | -29.1 | 0.429742E+10 | 3723.62 | 04-NOV-18:10 | -28.9 | -29.1 |
December | 0.674082E+09 | 30298.53 | 15-DEC-04:43 | -33.1 | -33.2 | 0.443646E+10 | 3723.61 | 02-DEC-19:40 | -33.1 | -33.2 |
Annual Sum or Average | 0.352631E+11 | 0.550249E+11 | ||||||||
Minimum of Months | 0.623750E+09 | 7875.74 | -37.8 | -37.9 | 0.402307E+10 | 3723.61 | -35.8 | -35.9 | ||
Maximum of Months | 0.949499E+10 | 38175.54 | 14.82 | 13.72 | 0.521906E+10 | 4682.50 | 26.70 | 18.19 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182494E+11 | 64635.81 | 13-JAN-05:01 | -32.9 | -33.0 | 0.768475E+10 | 5039.33 | 18-JAN-11:00 | -10.6 | -10.8 |
February | 0.165958E+11 | 61535.86 | 28-FEB-05:01 | -26.1 | -26.3 | 0.694154E+10 | 5039.33 | 07-FEB-11:00 | -26.1 | -26.3 |
March | 0.197348E+11 | 60783.15 | 03-MAR-05:01 | -25.6 | -26.1 | 0.768721E+10 | 5039.33 | 29-MAR-10:00 | -9.4 | -11.6 |
April | 0.215924E+11 | 54091.97 | 03-APR-04:01 | -21.1 | -21.6 | 0.744521E+10 | 5064.09 | 22-APR-10:00 | 12.80 | 6.00 |
May | 0.237245E+11 | 52031.83 | 12-MAY-03:21 | 3.60 | 0.63 | 0.775897E+10 | 5138.39 | 31-MAY-10:00 | 18.90 | 10.59 |
June | 0.238146E+11 | 49091.58 | 02-JUN-03:21 | 3.60 | 2.67 | 0.757803E+10 | 5138.44 | 29-JUN-10:50 | 22.02 | 15.69 |
July | 0.252301E+11 | 40863.80 | 21-JUL-03:31 | 9.40 | 7.88 | 0.783195E+10 | 5138.48 | 24-JUL-10:00 | 20.00 | 15.51 |
August | 0.254992E+11 | 46496.83 | 29-AUG-03:21 | 7.20 | 6.36 | 0.780998E+10 | 5138.43 | 02-AUG-10:00 | 7.20 | 6.36 |
September | 0.241128E+11 | 38751.87 | 29-SEP-04:01 | -3.9 | -4.5 | 0.746484E+10 | 5076.05 | 19-SEP-10:00 | -3.9 | -4.5 |
October | 0.227136E+11 | 53355.30 | 31-OCT-04:01 | -17.9 | -18.4 | 0.768661E+10 | 5059.59 | 04-OCT-10:00 | -17.9 | -18.4 |
November | 0.188349E+11 | 64581.32 | 28-NOV-05:01 | -27.7 | -27.9 | 0.743672E+10 | 5039.33 | 03-NOV-10:00 | -27.7 | -27.9 |
December | 0.184081E+11 | 70697.04 | 15-DEC-05:01 | -33.2 | -33.3 | 0.768465E+10 | 5039.33 | 19-DEC-11:09 | -15.4 | -15.8 |
Annual Sum or Average | 0.258510E+12 | 0.910105E+11 | ||||||||
Minimum of Months | 0.165958E+11 | 38751.87 | -33.2 | -33.3 | 0.694154E+10 | 5039.33 | -27.7 | -27.9 | ||
Maximum of Months | 0.254992E+11 | 70697.04 | 9.40 | 7.88 | 0.783195E+10 | 5138.48 | 22.02 | 15.69 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447979E+11 | 47316.77 | 13-JAN-12:04 | -30.3 |
February | 0.361783E+11 | 47166.35 | 28-FEB-20:15 | -28.1 |
March | 0.298004E+11 | 46543.67 | 03-MAR-04:01 | -25.6 |
April | 0.111627E+11 | 24527.80 | 02-APR-19:55 | -12.2 |
May | 0.141085E+10 | 11975.85 | 28-MAY-04:01 | 1.78 |
June | 28530378.34 | 2548.55 | 06-JUN-06:17 | 9.80 |
July | 50030646.55 | 2596.56 | 05-JUL-06:10 | 8.30 |
August | 0.391506E+09 | 9077.00 | 31-AUG-06:10 | -1.5 |
September | 0.499613E+10 | 15265.13 | 30-SEP-18:57 | -0.6 |
October | 0.198938E+11 | 42549.38 | 22-OCT-04:01 | -18.6 |
November | 0.418881E+11 | 47853.89 | 25-NOV-20:00 | -23.9 |
December | 0.474640E+11 | 47417.69 | 15-DEC-18:07 | -29.0 |
Annual Sum or Average | 0.238062E+12 | |||
Minimum of Months | 28530378.34 | 2548.55 | -30.3 | |
Maximum of Months | 0.474640E+11 | 47853.89 | 9.80 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28591456.91 | 24702.00 | 13-JAN-05:02 | -32.9 |
February | 26270425.36 | 22192.30 | 18-FEB-05:02 | -23.9 |
March | 19292350.58 | 22630.05 | 16-MAR-04:02 | -25.1 |
April | 4604033.56 | 14432.98 | 03-APR-04:02 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 12357.72 | 205.96 | 31-AUG-04:04 | -0.7 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 3099475.96 | 10336.88 | 21-OCT-04:03 | -5.6 |
November | 23834336.24 | 23227.86 | 29-NOV-05:02 | -28.9 |
December | 32706335.49 | 23842.48 | 14-DEC-05:02 | -26.0 |
Annual Sum or Average | 0.138411E+09 | |||
Minimum of Months | 0.00 | 0.00 | -32.9 | |
Maximum of Months | 32706335.49 | 24702.00 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187504E+10 | 1097.67 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.169832E+10 | 1097.67 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.190490E+10 | 1097.67 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.182191E+10 | 1097.67 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.188997E+10 | 1097.67 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.184123E+10 | 1097.67 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.187087E+10 | 1097.67 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.190490E+10 | 1097.67 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.182235E+10 | 1097.67 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.187482E+10 | 1097.67 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.181511E+10 | 1097.67 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.187109E+10 | 1097.67 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.221905E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.169832E+10 | 1097.67 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.190490E+10 | 1097.67 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157070E+10 | 919.51 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.142266E+10 | 919.51 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.159571E+10 | 919.51 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.152620E+10 | 919.51 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.158321E+10 | 919.51 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.154238E+10 | 919.51 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.156721E+10 | 919.51 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.159571E+10 | 919.51 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.152657E+10 | 919.51 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.157052E+10 | 919.51 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.152050E+10 | 919.51 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.156739E+10 | 919.51 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.185888E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.142266E+10 | 919.51 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.159571E+10 | 919.51 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.187504E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473137E+11 |
February | 0.852256E+10 | 0.169832E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393930E+11 |
March | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362935E+11 |
April | 0.915225E+10 | 0.182191E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205311E+11 |
May | 0.947560E+10 | 0.188997E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105026E+11 |
June | 0.922788E+10 | 0.184123E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102161E+09 | 0.600968E+10 |
July | 0.939996E+10 | 0.187087E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218884E+09 | 0.517341E+10 |
August | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29190949.46 | 0.781319E+10 |
September | 0.915225E+10 | 0.182235E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146844E+11 |
October | 0.940563E+10 | 0.187482E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278240E+11 |
November | 0.909363E+10 | 0.181511E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455207E+11 |
December | 0.939996E+10 | 0.187109E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496859E+11 |
Annual Sum or Average | 0.111326E+12 | 0.221905E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350236E+09 | 0.310745E+12 |
Minimum of Months | 0.852256E+10 | 0.169832E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517341E+10 |
Maximum of Months | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218884E+09 | 0.496859E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157070E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230266E+09 |
February | 0.610713E+09 | 0.142266E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190444E+09 |
March | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299449E+09 |
April | 0.655836E+09 | 0.152620E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294156E+09 |
May | 0.679007E+09 | 0.158321E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191375E+09 |
June | 0.661256E+09 | 0.154238E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 55014.24 | 0.122187E+09 |
July | 0.673587E+09 | 0.156721E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306419.46 | 91018595.03 |
August | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115295E+09 |
September | 0.655836E+09 | 0.152657E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114581E+09 |
October | 0.673993E+09 | 0.157052E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254183E+09 |
November | 0.651635E+09 | 0.152050E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92813417.27 |
December | 0.673587E+09 | 0.156739E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178058E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185888E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 361433.69 | 0.217383E+10 |
Minimum of Months | 0.610713E+09 | 0.142266E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91018595.03 |
Maximum of Months | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306419.46 | 0.299449E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771508E+09 | 13280585.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551992E+09 | 0.180970E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399769E+09 | 0.779429E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277580E+09 | 0.131781E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183232E+09 | 0.158746E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93982791.81 | 0.168545E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113030E+09 | 0.158904E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191254E+09 | 0.122761E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309122E+09 | 0.638563E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368271E+09 | 0.272675E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819624E+09 | 47958814.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839252E+09 | 686800.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491862E+10 | 0.934094E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93982791.81 | 686800.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839252E+09 | 0.168545E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 1097.67 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 63078.20 | 12-JAN-12:01 |
February | 9454.80 | 04-FEB-19:10 | 1097.67 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 55235.35 | 27-FEB-12:02 |
March | 9454.80 | 04-MAR-19:10 | 1097.67 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 46056.52 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 1097.67 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 30397.61 | 03-APR-11:02 |
May | 9454.80 | 06-MAY-18:10 | 1097.67 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 16143.43 | 26-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 1097.67 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2443.08 | 20-JUN-17:55 | 9598.11 | 24-JUN-19:00 |
July | 9454.80 | 01-JUL-18:10 | 1097.67 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4372.35 | 29-JUL-17:03 | 9740.89 | 05-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 1097.67 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.67 | 11-AUG-17:05 | 13723.31 | 30-AUG-20:00 |
September | 9454.80 | 02-SEP-18:10 | 1097.67 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 23242.19 | 30-SEP-18:53 |
October | 9454.80 | 07-OCT-18:10 | 1097.67 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 39875.73 | 30-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 1097.67 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 52756.48 | 25-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 1097.67 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 58486.66 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 1097.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9598.11 | |||||
Maximum of Months | 9454.80 | 1097.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 4372.35 | 63078.20 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.51 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1499.01 | 29-JAN-01:10 |
February | 677.52 | 04-FEB-19:10 | 919.51 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1014.50 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 919.51 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 787.29 | 25-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 919.51 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 871.98 | 07-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 919.51 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 590.74 | 26-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 919.51 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 11.20 | 30-JUN-15:00 | 616.97 | 25-JUN-01:40 |
July | 677.52 | 01-JUL-18:10 | 919.51 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.20 | 21-JUL-16:00 | 383.63 | 30-JUL-02:50 |
August | 677.52 | 05-AUG-18:10 | 919.51 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 446.07 | 30-AUG-01:00 |
September | 677.52 | 02-SEP-18:10 | 919.51 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 318.37 | 30-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 919.51 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 775.54 | 21-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 919.51 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 617.95 | 10-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 919.51 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 620.22 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.51 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 318.37 | ||||||
Maximum of Months | 677.52 | 919.51 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 33.20 | 1499.01 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 776.81 | 13-JAN-01:00 | 371.12 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.21 | 17-FEB-04:53 | 943.60 | 27-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.19 | 27-MAR-07:32 | 1831.97 | 26-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.01 | 01-APR-00:45 | 1856.39 | 27-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.22 | 22-MAY-03:30 | 1994.55 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.99 | 07-JUN-01:00 | 2037.84 | 08-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.21 | 11-JUL-24:00 | 2108.60 | 23-JUL-12:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.38 | 22-AUG-05:10 | 1904.48 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.39 | 19-SEP-01:55 | 1300.66 | 07-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.06 | 31-OCT-08:00 | 799.67 | 22-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.39 | 22-NOV-03:00 | 511.15 | 06-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.08 | 23-DEC-01:53 | 123.84 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.21 | 123.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.19 | 2108.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38175.54 | 12-JAN-04:58 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35176.95 | 27-FEB-04:44 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21454.60 | 01-MAR-04:46 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 |
April | 14307.94 | 02-APR-23:01 | 5252.67 | 1829.49 | 4070.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 |
May | 12641.38 | 31-MAY-04:01 | 5252.67 | 2439.28 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24973.05 | 23-JUN-04:01 | 5252.67 | 2439.28 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 |
July | 27288.13 | 25-JUL-04:01 | 5252.67 | 2439.28 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
August | 25231.04 | 05-AUG-04:01 | 0.00 | 1829.49 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
September | 7875.74 | 28-SEP-23:01 | 3676.87 | 1280.64 | 2849.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 |
October | 18498.81 | 22-OCT-04:02 | 0.00 | 1829.49 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 |
November | 23080.73 | 29-NOV-04:09 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30298.53 | 15-DEC-04:43 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7875.74 | 0.00 | 1280.64 | 2849.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38175.54 | 5252.67 | 2439.28 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64635.81 | 13-JAN-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 61535.86 | 28-FEB-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60783.15 | 03-MAR-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 92.97 |
April | 54091.97 | 03-APR-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 105.22 |
May | 52031.83 | 12-MAY-03:21 | 0.00 | 1072.77 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 234.20 |
June | 49091.58 | 02-JUN-03:21 | 0.00 | 1072.77 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 128.25 |
July | 40863.80 | 21-JUL-03:31 | 0.00 | 1379.28 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 |
August | 46496.83 | 29-AUG-03:21 | 0.00 | 1379.28 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 61.04 |
September | 38751.87 | 29-SEP-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 |
October | 53355.30 | 31-OCT-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 142.98 |
November | 64581.32 | 28-NOV-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70697.04 | 15-DEC-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38751.87 | 0.00 | 1072.77 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 70697.04 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 234.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.88 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.66 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.00 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.95 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.06 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.66 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.08 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.07 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.80 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.86 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.30 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.462475E+11 | 27230.94 | 02-JAN-11:09 | 0.285351E+12 | 223389.86 | 12-JAN-11:09 |
February | 0.410775E+11 | 25210.76 | 09-FEB-11:20 | 0.238852E+12 | 206977.12 | 27-FEB-13:09 |
March | 0.447335E+11 | 25214.50 | 22-MAR-10:20 | 0.220533E+12 | 169156.71 | 01-MAR-20:40 |
April | 0.424779E+11 | 25216.70 | 28-APR-10:20 | 0.128832E+12 | 137951.10 | 03-APR-07:10 |
May | 0.435745E+11 | 25337.62 | 31-MAY-10:09 | 0.749905E+11 | 83937.35 | 27-MAY-10:09 |
June | 0.440523E+11 | 30701.76 | 30-JUN-11:00 | 0.613297E+11 | 55809.70 | 25-JUN-10:20 |
July | 0.474317E+11 | 31135.66 | 22-JUL-10:00 | 0.625472E+11 | 56614.63 | 05-JUL-10:39 |
August | 0.459408E+11 | 28355.50 | 11-AUG-16:10 | 0.654696E+11 | 65607.35 | 31-AUG-06:30 |
September | 0.431131E+11 | 25257.95 | 01-SEP-10:20 | 0.901519E+11 | 95968.93 | 29-SEP-10:09 |
October | 0.451100E+11 | 25233.50 | 02-OCT-10:20 | 0.165234E+12 | 148495.45 | 27-OCT-10:09 |
November | 0.444600E+11 | 25193.08 | 02-NOV-10:20 | 0.270794E+12 | 191001.11 | 28-NOV-13:09 |
December | 0.465524E+11 | 27232.01 | 26-DEC-11:20 | 0.295849E+12 | 213391.15 | 15-DEC-13:20 |
Annual Sum or Average | 0.534771E+12 | 0.195993E+13 | ||||
Minimum of Months | 0.410775E+11 | 25193.08 | 0.613297E+11 | 55809.70 | ||
Maximum of Months | 0.474317E+11 | 31135.66 | 0.295849E+12 | 223389.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.344574E+10 | 0.438980E+10 | 0.235157E+11 | 0.00 | 0.992103E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312098E+10 | 0.328439E+10 | 0.212400E+11 | 0.00 | 0.893381E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350061E+10 | 0.286574E+10 | 0.235157E+11 | 0.00 | 0.985512E+10 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334811E+10 | 0.201740E+10 | 0.227571E+11 | 0.00 | 0.947150E+10 | 0.77 | 0.00 | 153360.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347318E+10 | 0.131841E+10 | 0.235157E+11 | 0.00 | 0.985661E+10 | 0.80 | 0.00 | 0.100123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338361E+10 | 0.734490E+09 | 0.227571E+11 | 0.00 | 0.977885E+10 | 0.77 | 0.00 | 0.195366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343808E+10 | 0.102094E+10 | 0.235157E+11 | 0.00 | 0.101479E+11 | 0.79 | 0.00 | 0.364615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350061E+10 | 0.176155E+10 | 0.235157E+11 | 0.00 | 0.100838E+11 | 0.80 | 0.00 | 0.151154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334892E+10 | 0.244952E+10 | 0.227571E+11 | 0.00 | 0.952136E+10 | 0.77 | 0.00 | 2570394.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344534E+10 | 0.330398E+10 | 0.235157E+11 | 0.00 | 0.980128E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333560E+10 | 0.396257E+10 | 0.227571E+11 | 0.00 | 0.958559E+10 | 0.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343848E+10 | 0.470074E+10 | 0.235157E+11 | 0.00 | 0.992255E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407793E+11 | 0.318095E+11 | 0.276879E+12 | 0.00 | 0.116879E+12 | 9.37 | 0.00 | 0.721420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312098E+10 | 0.734490E+09 | 0.212400E+11 | 0.00 | 0.893381E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350061E+10 | 0.470074E+10 | 0.235157E+11 | 0.00 | 0.101479E+11 | 0.80 | 0.00 | 0.364615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.221786E+12 | 0.00 | 0.230393E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.181438E+12 | 0.00 | 0.208106E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.156926E+12 | 0.00 | 0.230807E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.673364E+11 | 0.00 | 0.222774E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.116233E+11 | 0.00 | 0.228415E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.782761E+09 | 0.00 | 0.213285E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.762771E+09 | 0.00 | 0.212587E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.405783E+10 | 0.00 | 0.208860E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.307399E+11 | 0.00 | 0.201935E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.103455E+12 | 0.00 | 0.212532E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.210346E+12 | 0.00 | 0.212290E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.232623E+12 | 0.00 | 0.227006E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.122188E+13 | 0.00 | 0.260899E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.762771E+09 | 0.00 | 0.201935E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.232623E+12 | 0.00 | 0.230807E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2017.17 | 02-JAN-10:09 | 2040.25 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 4378.48 | 07-JAN-00:40 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2017.17 | 01-FEB-10:09 | 2040.25 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 4378.48 | 01-FEB-14:50 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2017.17 | 01-MAR-10:09 | 2040.25 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 4378.48 | 05-MAR-18:30 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 2017.17 | 01-APR-16:10 | 2040.25 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 4378.48 | 02-APR-23:49 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 2017.17 | 01-MAY-09:09 | 2040.25 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 4378.48 | 16-MAY-04:00 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 2017.17 | 01-JUN-09:09 | 2040.25 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 4378.48 | 08-JUN-19:40 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 2017.17 | 01-JUL-16:10 | 2040.25 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 4378.48 | 13-JUL-12:39 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 2017.17 | 01-AUG-09:09 | 2040.25 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 4378.48 | 02-AUG-14:20 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2017.17 | 01-SEP-09:09 | 2040.25 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 4378.48 | 08-SEP-04:49 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2017.17 | 02-OCT-09:09 | 2040.25 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 4378.48 | 01-OCT-05:30 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2017.17 | 01-NOV-09:09 | 2040.25 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 4378.48 | 01-NOV-04:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2017.17 | 01-DEC-10:09 | 2040.25 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 4378.48 | 11-DEC-19:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2017.17 | 2040.25 | 14428.03 | 0.00 | 4378.48 | 0.00 | 0.00 | ||||||
Maximum of Months | 2017.17 | 2040.25 | 14428.03 | 0.00 | 4378.48 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 176.23 | 21-APR-03:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3516.74 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8895.52 | 30-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9808.91 | 29-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7198.60 | 11-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 538.12 | 01-SEP-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9808.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27230.94 | 02-JAN-11:09 | 2017.17 | 14428.03 | 2040.25 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25210.76 | 09-FEB-11:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25214.50 | 22-MAR-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25216.70 | 28-APR-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25337.62 | 31-MAY-10:09 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30701.76 | 30-JUN-11:00 | 2017.17 | 13527.31 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 8657.61 | 0.00 |
July | 31135.66 | 22-JUL-10:00 | 1793.05 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 7649.22 | 0.00 |
August | 28355.50 | 11-AUG-16:10 | 2017.17 | 13076.95 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 6843.26 | 0.00 |
September | 25257.95 | 01-SEP-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25233.50 | 02-OCT-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25193.08 | 02-NOV-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27232.01 | 26-DEC-11:20 | 2017.17 | 14428.03 | 2040.25 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 25193.08 | 1793.05 | 13076.95 | 0.00 | 0.00 | 4378.48 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31135.66 | 2017.17 | 14428.03 | 2040.25 | 0.00 | 4378.48 | 0.00 | 0.00 | 8657.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 174058.26 | 12-JAN-07:10 | 0.00 | 33365.76 | 03-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 161505.38 | 27-FEB-07:10 | 0.00 | 33363.54 | 05-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 141744.31 | 04-MAR-07:10 | 0.00 | 33363.20 | 29-MAR-12:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 114402.70 | 03-APR-06:10 | 0.00 | 33363.76 | 03-APR-12:30 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 44432.48 | 27-MAY-06:00 | 0.00 | 33303.59 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 12702.83 | 02-JUN-06:10 | 0.00 | 30122.92 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 11957.86 | 05-JUL-06:10 | 0.00 | 28411.69 | 02-JUL-12:00 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 45513.76 | 31-AUG-06:10 | 0.00 | 28129.91 | 01-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 62125.75 | 30-SEP-06:10 | 0.00 | 28102.34 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 116558.81 | 22-OCT-06:10 | 0.00 | 28354.20 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 154880.47 | 30-NOV-20:10 | 0.00 | 28761.78 | 27-NOV-13:30 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 162401.10 | 15-DEC-12:39 | 0.00 | 33362.29 | 29-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 11957.86 | 0.00 | 28102.34 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 174058.26 | 0.00 | 33365.76 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.50 | 16.83 | 12.50 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
February | 20.33 | 17.70 | 2.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 13.83 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
April | 1.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.20 | 0.00 | 26.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
November | 25.50 | 17.97 | 4.33 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
December | 31.33 | 17.46 | 5.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
Annual Sum or Average | 135.00 | 17.48 | 24.00 | 17.49 | 0.83 | 17.54 | 0.00 | 17.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.50 | 19.24 | 12.50 | 19.24 | 0.33 | 26.20 | 0.00 | 26.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.37 | 0.00 | 28.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 29.26 | 0.00 | 29.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 30.51 | 0.00 | 30.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.66 | 0.00 | 30.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 30.51 | 0.00 | 30.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.77 | 0.00 | 28.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 67.17 | 30.41 | 0.00 | 30.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 30.66 | 0.00 | 30.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.73 | 610.00 | 20.73 | 610.00 | 20.73 |
February | 551.00 | 20.83 | 530.00 | 20.82 | 530.00 | 20.82 |
March | 612.00 | 20.84 | 407.00 | 20.79 | 407.00 | 20.76 |
April | 586.33 | 20.94 | 157.00 | 20.81 | 157.00 | 20.72 |
May | 487.50 | 21.35 | 53.83 | 21.43 | 19.50 | 21.35 |
June | 202.50 | 21.66 | 314.00 | 23.00 | 0.33 | 23.00 |
July | 154.50 | 21.58 | 411.17 | 23.22 | 1.33 | 23.22 |
August | 285.50 | 21.43 | 266.00 | 22.58 | 2.17 | 22.56 |
September | 562.17 | 21.09 | 41.50 | 21.01 | 36.50 | 20.92 |
October | 610.00 | 20.88 | 241.67 | 20.77 | 241.67 | 20.72 |
November | 591.00 | 20.83 | 587.83 | 20.83 | 587.83 | 20.83 |
December | 609.00 | 20.82 | 609.00 | 20.82 | 609.00 | 20.82 |
Annual Sum or Average | 5861.50 | 20.98 | 4229.00 | 21.19 | 3202.33 | 21.07 |
Minimum of Months | 154.50 | 20.73 | 41.50 | 20.73 | 0.33 | 20.72 |
Maximum of Months | 612.00 | 21.66 | 610.00 | 23.22 | 610.00 | 23.22 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 609.83 | 18.72 | 609.83 | 18.72 |
February | 551.00 | 18.72 | 545.83 | 18.72 | 545.83 | 18.72 |
March | 612.00 | 18.72 | 573.33 | 18.72 | 573.33 | 18.72 |
April | 586.33 | 18.99 | 355.33 | 18.85 | 355.33 | 18.79 |
May | 427.33 | 20.18 | 214.83 | 21.10 | 87.67 | 21.02 |
June | 361.33 | 24.46 | 446.17 | 24.88 | 256.83 | 25.16 |
July | 418.00 | 24.94 | 505.17 | 25.11 | 342.17 | 25.34 |
August | 403.67 | 23.25 | 400.67 | 24.04 | 228.00 | 24.40 |
September | 517.00 | 19.30 | 128.00 | 19.36 | 93.33 | 19.21 |
October | 610.00 | 18.81 | 370.17 | 18.74 | 370.17 | 18.71 |
November | 591.00 | 18.72 | 590.50 | 18.72 | 590.50 | 18.72 |
December | 609.00 | 18.72 | 608.17 | 18.72 | 608.17 | 18.72 |
Annual Sum or Average | 6296.67 | 19.94 | 5348.00 | 20.20 | 4661.17 | 20.14 |
Minimum of Months | 361.33 | 18.72 | 128.00 | 18.72 | 87.67 | 18.71 |
Maximum of Months | 612.00 | 24.94 | 609.83 | 25.11 | 609.83 | 25.34 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.72833 | 10.09090 | -0.8439 | 20.98547 |
February | 551.00000 | 20.82960 | 11.35199 | -0.7737 | 18.55054 |
March | 612.00000 | 20.84066 | 12.66480 | -0.6475 | 14.99075 |
April | 590.00000 | 20.95556 | 17.91679 | -0.4411 | 10.55055 |
May | 611.00000 | 21.84343 | 26.51144 | -1.1372 | 35.13372 |
June | 592.00000 | 23.05682 | 39.11280 | -0.5828 | 15.12782 |
July | 609.00000 | 23.20069 | 47.39205 | -0.4614 | 12.61571 |
August | 612.00000 | 22.63882 | 43.53606 | -0.6938 | 19.39165 |
September | 590.00000 | 21.20019 | 33.59432 | -1.3704 | 44.69444 |
October | 610.00000 | 20.87611 | 20.76964 | -0.5287 | 11.91146 |
November | 591.00000 | 20.82689 | 9.25216 | -0.7784 | 18.54309 |
December | 609.00000 | 20.81612 | 9.11820 | -0.8380 | 20.52325 |
Annual Sum or Average | 7187.00000 | 21.48992 | 23.52893 | -0.7575 | 20.24322 |
Minimum of Months | 551.00000 | 20.72833 | 9.11820 | -1.3704 | 10.55055 |
Maximum of Months | 612.00000 | 23.20069 | 47.39205 | -0.4411 | 44.69444 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72305 | 15.71184 | -0.8859 | 22.12424 |
February | 551.00000 | 18.72338 | 17.51966 | -0.8711 | 21.66817 |
March | 612.00000 | 18.72467 | 19.29662 | -0.8179 | 19.82028 |
April | 590.00000 | 19.01729 | 25.13632 | -0.6451 | 15.37721 |
May | 611.00000 | 21.36874 | 31.54058 | -1.0354 | 36.49970 |
June | 592.00000 | 24.18758 | 40.18589 | -0.0118 | 13.48767 |
July | 609.00000 | 24.48284 | 46.98892 | 0.15770 | 14.23049 |
August | 612.00000 | 23.33022 | 44.86901 | -0.2394 | 19.27687 |
September | 590.00000 | 19.78118 | 39.93855 | -1.4804 | 51.48308 |
October | 610.00000 | 18.81161 | 27.37399 | -0.6750 | 15.51837 |
November | 591.00000 | 18.72348 | 14.98442 | -0.8555 | 20.99575 |
December | 609.00000 | 18.72219 | 14.47153 | -0.8895 | 22.24015 |
Annual Sum or Average | 7187.00000 | 20.39713 | 28.23790 | -0.6851 | 22.70506 |
Minimum of Months | 551.00000 | 18.72219 | 14.47153 | -1.4804 | 13.48767 |
Maximum of Months | 612.00000 | 24.48284 | 46.98892 | 0.15770 | 51.48308 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 |
May | 0.149137E+09 | 44746807.88 | 18.83 | 0.149137E+09 | 0.00 | 0.00 | 0.27 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 | 6641.78 | 31-MAY-16:05 | 6641.78 | 31-MAY-16:05 | 0.00 | 31-MAY-17:13 | 1936.57 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 |
June | 0.324627E+10 | 0.925460E+09 | 159.33 | 0.310175E+10 | 0.144519E+09 | 0.00 | 0.74 | 30-JUN-04:01 | 0.00 | 01-JUN-00:01 | 20489.47 | 30-JUN-04:01 | 15462.75 | 20-JUN-17:55 | 7597.63 | 30-JUN-04:01 | 5286.99 | 30-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.628976E+10 | 0.177072E+10 | 220.95 | 0.581758E+10 | 0.472186E+09 | 0.00 | 0.96 | 25-JUL-04:01 | 0.00 | 01-JUL-00:01 | 28068.36 | 25-JUL-04:01 | 18825.69 | 29-JUL-17:03 | 11741.07 | 25-JUL-04:01 | 6813.66 | 25-JUL-04:01 | 0.00 | 01-JUL-00:01 |
August | 0.247785E+10 | 0.713104E+09 | 124.78 | 0.232038E+10 | 0.157468E+09 | 0.00 | 0.88 | 13-AUG-04:01 | 0.00 | 01-AUG-00:01 | 25126.53 | 13-AUG-04:01 | 14942.77 | 11-AUG-17:05 | 11443.43 | 13-AUG-04:01 | 6243.04 | 13-AUG-04:01 | 0.00 | 01-AUG-00:01 |
September | 2338.58 | 727.17 | 0.17 | 2338.58 | 0.00 | 0.00 | 0.00 | 10-SEP-14:00 | 0.00 | 01-SEP-00:01 | 3.90 | 10-SEP-14:00 | 3.90 | 10-SEP-14:00 | 0.00 | 01-SEP-00:01 | 1.21 | 10-SEP-14:00 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.121630E+11 | 0.345403E+10 | 524.06 | 0.113889E+11 | 0.774174E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.628976E+10 | 0.177072E+10 | 220.95 | 0.581758E+10 | 0.472186E+09 | 0.00 | 0.96 | 0.00 | 28068.36 | 18825.69 | 11741.07 | 6813.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 498781.09 | 153360.19 | 0.25 | 372362.57 | 126418.52 | 0.00 | 0.06 | 21-APR-03:40 | 0.00 | 01-APR-00:01 | 1150.41 | 21-APR-03:40 | 865.40 | 21-APR-03:40 | 285.02 | 21-APR-03:40 | 352.46 | 21-APR-03:40 | 0.00 | 01-APR-00:01 |
May | 0.186541E+09 | 55376580.71 | 27.44 | 0.183294E+09 | 3247118.98 | 0.00 | 1.00 | 12-MAY-03:21 | 0.00 | 01-MAY-00:01 | 22844.31 | 14-MAY-04:01 | 19375.40 | 12-MAY-04:01 | 5448.74 | 23-MAY-03:41 | 5476.90 | 12-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.364436E+10 | 0.102820E+10 | 204.77 | 0.346777E+10 | 0.176594E+09 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:01 | 22844.31 | 03-JUN-04:01 | 18675.61 | 14-JUN-02:11 | 10520.57 | 29-JUN-04:01 | 5476.90 | 01-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.677499E+10 | 0.187544E+10 | 262.98 | 0.619031E+10 | 0.584682E+09 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 22844.31 | 14-JUL-03:01 | 19514.27 | 13-JUL-02:11 | 12389.22 | 27-JUL-03:01 | 5476.90 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.279162E+10 | 0.798432E+09 | 159.61 | 0.250181E+10 | 0.289810E+09 | 0.00 | 1.00 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 | 22844.31 | 01-AUG-03:31 | 18509.45 | 11-AUG-03:31 | 12245.55 | 13-AUG-02:11 | 5476.90 | 01-AUG-03:31 | 0.00 | 01-AUG-00:01 |
September | 8488601.69 | 2569666.85 | 2.03 | 5566240.71 | 2922360.98 | 0.00 | 0.23 | 01-SEP-03:08 | 0.00 | 01-SEP-00:01 | 4223.85 | 01-SEP-03:08 | 2683.54 | 19-SEP-03:08 | 1837.34 | 01-SEP-03:08 | 1245.07 | 01-SEP-03:08 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.134065E+11 | 0.376017E+10 | 657.08 | 0.123491E+11 | 0.105738E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.677499E+10 | 0.187544E+10 | 262.98 | 0.619031E+10 | 0.584682E+09 | 0.00 | 1.00 | 0.00 | 22844.31 | 19514.27 | 12389.22 | 5476.90 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.44 | 3.92 | 8.52 | 1.26 | 322.00 | 0.00 | 0.00 | 0.00 |
February | 68.74 | 32.81 | 35.93 | 37.31 | 267.13 | 0.00 | 0.00 | 0.00 |
March | 196.03 | 99.27 | 96.77 | 169.40 | 195.00 | 0.00 | 0.00 | 0.00 |
April | 269.45 | 136.30 | 133.15 | 258.58 | 103.80 | 0.00 | 0.00 | 0.00 |
May | 391.41 | 220.32 | 171.09 | 440.65 | 50.77 | 0.00 | 0.00 | 0.00 |
June | 360.13 | 167.76 | 192.37 | 414.97 | 26.49 | 0.00 | 0.00 | 0.00 |
July | 342.07 | 165.63 | 176.44 | 402.68 | 30.70 | 0.00 | 0.00 | 0.00 |
August | 270.93 | 131.74 | 139.19 | 307.01 | 48.39 | 0.00 | 0.00 | 0.00 |
September | 167.62 | 73.37 | 94.25 | 163.22 | 88.26 | 0.00 | 0.00 | 0.00 |
October | 88.55 | 35.53 | 53.01 | 65.35 | 170.59 | 0.00 | 0.00 | 0.00 |
November | 18.84 | 6.59 | 12.25 | 1.69 | 314.73 | 0.00 | 0.00 | 0.00 |
December | 2.69 | 0.65 | 2.05 | 0.00 | 348.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183.11 | 89.88 | 93.22 | 189.52 | 163.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.69 | 0.65 | 2.05 | 0.00 | 26.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 391.41 | 220.32 | 192.37 | 440.65 | 348.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.26 | 74.60 | 38.66 | 68.64 | 596.14 | 0.00 | 0.00 | 0.00 |
February | 389.77 | 271.08 | 118.68 | 337.52 | 475.43 | 0.00 | 0.00 | 0.00 |
March | 669.43 | 453.71 | 215.72 | 667.46 | 359.72 | 0.00 | 0.00 | 0.00 |
April | 816.82 | 508.15 | 308.67 | 909.18 | 223.73 | 0.00 | 0.00 | 0.00 |
May | 673.64 | 349.10 | 324.54 | 774.90 | 113.35 | 0.00 | 0.00 | 0.00 |
June | 615.07 | 252.16 | 362.91 | 721.93 | 64.92 | 0.00 | 0.00 | 0.00 |
July | 592.59 | 258.12 | 334.46 | 710.26 | 69.92 | 0.00 | 0.00 | 0.00 |
August | 613.62 | 338.19 | 275.43 | 724.40 | 102.86 | 0.00 | 0.00 | 0.00 |
September | 495.85 | 298.61 | 197.24 | 538.56 | 177.16 | 0.00 | 0.00 | 0.00 |
October | 356.95 | 226.45 | 130.51 | 332.51 | 313.52 | 0.00 | 0.00 | 0.00 |
November | 191.35 | 133.59 | 57.76 | 130.35 | 560.30 | 0.00 | 0.00 | 0.00 |
December | 33.96 | 23.93 | 10.03 | 6.79 | 666.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.41 | 265.24 | 198.17 | 493.93 | 309.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.96 | 23.93 | 10.03 | 6.79 | 64.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 816.82 | 508.15 | 362.91 | 909.18 | 666.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.55 | 1.17 | 5.38 | 0.00 | 328.05 | 0.00 | 0.00 | 0.00 |
February | 38.64 | 13.44 | 25.20 | 8.12 | 276.39 | 0.00 | 0.00 | 0.00 |
March | 115.95 | 49.85 | 66.10 | 68.71 | 198.58 | 0.00 | 0.00 | 0.00 |
April | 275.10 | 142.54 | 132.55 | 272.05 | 110.12 | 0.00 | 0.00 | 0.00 |
May | 267.49 | 121.80 | 145.69 | 282.24 | 52.93 | 0.00 | 0.00 | 0.00 |
June | 293.17 | 124.99 | 168.18 | 330.17 | 30.09 | 0.00 | 0.00 | 0.00 |
July | 245.30 | 92.78 | 152.52 | 278.44 | 33.26 | 0.00 | 0.00 | 0.00 |
August | 201.61 | 85.36 | 116.24 | 218.13 | 49.94 | 0.00 | 0.00 | 0.00 |
September | 122.02 | 51.10 | 70.92 | 105.65 | 89.92 | 0.00 | 0.00 | 0.00 |
October | 47.79 | 14.37 | 33.42 | 18.72 | 177.11 | 0.00 | 0.00 | 0.00 |
November | 19.12 | 6.95 | 12.17 | 2.16 | 313.82 | 0.00 | 0.00 | 0.00 |
December | 1.72 | 0.18 | 1.54 | 0.00 | 349.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.55 | 58.83 | 77.72 | 132.55 | 166.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.72 | 0.18 | 1.54 | 0.00 | 30.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 293.17 | 142.54 | 168.18 | 330.17 | 349.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33329763.45 | 10496894.43 | 22832869.01 | 3368987.85 | 0.862456E+09 |
February | 0.166297E+09 | 79364243.88 | 86932743.04 | 90271730.36 | 0.646244E+09 |
March | 0.525056E+09 | 0.265878E+09 | 0.259178E+09 | 0.453720E+09 | 0.522282E+09 |
April | 0.698407E+09 | 0.353284E+09 | 0.345122E+09 | 0.670242E+09 | 0.269051E+09 |
May | 0.104835E+10 | 0.590098E+09 | 0.458254E+09 | 0.118024E+10 | 0.135972E+09 |
June | 0.933456E+09 | 0.434829E+09 | 0.498627E+09 | 0.107560E+10 | 68665943.18 |
July | 0.916197E+09 | 0.443625E+09 | 0.472572E+09 | 0.107854E+10 | 82232865.28 |
August | 0.725671E+09 | 0.352861E+09 | 0.372810E+09 | 0.822298E+09 | 0.129601E+09 |
September | 0.434459E+09 | 0.190162E+09 | 0.244296E+09 | 0.423073E+09 | 0.228776E+09 |
October | 0.237161E+09 | 95167863.96 | 0.141993E+09 | 0.175031E+09 | 0.456911E+09 |
November | 48832550.85 | 17073161.93 | 31759388.92 | 4391594.75 | 0.815769E+09 |
December | 7210060.57 | 1728200.15 | 5481860.42 | 0.00 | 0.933500E+09 |
Annual Sum or Average | 0.577443E+10 | 0.283457E+10 | 0.293986E+10 | 0.597677E+10 | 0.515146E+10 |
Minimum of Months | 7210060.57 | 1728200.15 | 5481860.42 | 0.00 | 68665943.18 |
Maximum of Months | 0.104835E+10 | 0.590098E+09 | 0.498627E+09 | 0.118024E+10 | 0.933500E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303352E+09 | 0.199814E+09 | 0.103538E+09 | 0.183852E+09 | 0.159671E+10 |
February | 0.942924E+09 | 0.655803E+09 | 0.287121E+09 | 0.816540E+09 | 0.115016E+10 |
March | 0.179299E+10 | 0.121521E+10 | 0.577778E+09 | 0.178772E+10 | 0.963476E+09 |
April | 0.211721E+10 | 0.131713E+10 | 0.800083E+09 | 0.235660E+10 | 0.579896E+09 |
May | 0.180426E+10 | 0.935020E+09 | 0.869245E+09 | 0.207550E+10 | 0.303595E+09 |
June | 0.159426E+10 | 0.653606E+09 | 0.940651E+09 | 0.187125E+10 | 0.168272E+09 |
July | 0.158718E+10 | 0.691349E+09 | 0.895831E+09 | 0.190235E+10 | 0.187271E+09 |
August | 0.164353E+10 | 0.905810E+09 | 0.737718E+09 | 0.194022E+10 | 0.275509E+09 |
September | 0.128525E+10 | 0.774000E+09 | 0.511249E+09 | 0.139594E+10 | 0.459212E+09 |
October | 0.956068E+09 | 0.606511E+09 | 0.349557E+09 | 0.890601E+09 | 0.839728E+09 |
November | 0.495988E+09 | 0.346264E+09 | 0.149724E+09 | 0.337870E+09 | 0.145231E+10 |
December | 90969552.78 | 64107475.90 | 26862076.88 | 18177075.05 | 0.178432E+10 |
Annual Sum or Average | 0.146140E+11 | 0.836462E+10 | 0.624936E+10 | 0.155766E+11 | 0.976044E+10 |
Minimum of Months | 90969552.78 | 64107475.90 | 26862076.88 | 18177075.05 | 0.168272E+09 |
Maximum of Months | 0.211721E+10 | 0.131713E+10 | 0.940651E+09 | 0.235660E+10 | 0.178432E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 17531122.69 | 3132162.29 | 14398960.40 | 0.00 | 0.878642E+09 |
February | 93471118.92 | 32515746.87 | 60955372.05 | 19642486.16 | 0.668652E+09 |
March | 0.310564E+09 | 0.133517E+09 | 0.177047E+09 | 0.184033E+09 | 0.531869E+09 |
April | 0.713054E+09 | 0.369474E+09 | 0.343580E+09 | 0.705165E+09 | 0.285421E+09 |
May | 0.716449E+09 | 0.326235E+09 | 0.390213E+09 | 0.755940E+09 | 0.141770E+09 |
June | 0.759884E+09 | 0.323965E+09 | 0.435919E+09 | 0.855805E+09 | 77986544.62 |
July | 0.657003E+09 | 0.248504E+09 | 0.408499E+09 | 0.745780E+09 | 89091725.54 |
August | 0.539981E+09 | 0.228636E+09 | 0.311345E+09 | 0.584241E+09 | 0.133748E+09 |
September | 0.316269E+09 | 0.132438E+09 | 0.183831E+09 | 0.273846E+09 | 0.233072E+09 |
October | 0.128009E+09 | 38496497.14 | 89512770.21 | 50138437.13 | 0.474384E+09 |
November | 49571909.52 | 18020209.55 | 31551699.97 | 5602959.83 | 0.813428E+09 |
December | 4598434.10 | 484276.56 | 4114157.53 | 0.00 | 0.936531E+09 |
Annual Sum or Average | 0.430639E+10 | 0.185542E+10 | 0.245097E+10 | 0.418019E+10 | 0.526460E+10 |
Minimum of Months | 4598434.10 | 484276.56 | 4114157.53 | 0.00 | 77986544.62 |
Maximum of Months | 0.759884E+09 | 0.369474E+09 | 0.435919E+09 | 0.855805E+09 | 0.936531E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 43.23 | 1219.52 | 132.25 | 79.69 | 52.56 | 0.00 | 0.00 |
February | 329.83 | 965.83 | 497.14 | 317.33 | 179.82 | 0.00 | 0.00 |
March | 864.49 | 712.21 | 981.41 | 602.83 | 378.59 | 0.00 | 0.00 |
April | 1403.96 | 401.79 | 1361.37 | 786.99 | 574.38 | 0.00 | 0.00 |
May | 1476.35 | 195.61 | 1332.54 | 691.22 | 641.32 | 0.00 | 0.00 |
June | 1452.01 | 106.44 | 1268.36 | 544.91 | 723.46 | 0.00 | 0.00 |
July | 1380.79 | 123.30 | 1179.95 | 516.53 | 663.42 | 0.00 | 0.00 |
August | 1238.12 | 189.77 | 1086.16 | 555.30 | 530.87 | 0.00 | 0.00 |
September | 793.29 | 341.21 | 785.48 | 423.07 | 362.41 | 0.00 | 0.00 |
October | 389.01 | 633.66 | 493.29 | 276.35 | 216.94 | 0.00 | 0.00 |
November | 90.00 | 1144.64 | 229.32 | 147.13 | 82.19 | 0.00 | 0.00 |
December | 1.15 | 1358.74 | 38.37 | 24.76 | 13.61 | 0.00 | 0.00 |
Annual Sum or Average | 790.69 | 614.47 | 783.07 | 413.96 | 369.11 | 0.00 | 0.00 |
Minimum of Months | 1.15 | 106.44 | 38.37 | 24.76 | 13.61 | 0.00 | 0.00 |
Maximum of Months | 1476.35 | 1358.74 | 1361.37 | 786.99 | 723.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115778E+09 | 0.326636E+10 | 0.354213E+09 | 0.213443E+09 | 0.140770E+09 | 0.00 | 0.00 |
February | 0.797934E+09 | 0.233653E+10 | 0.120269E+10 | 0.767683E+09 | 0.435009E+09 | 0.00 | 0.00 |
March | 0.231544E+10 | 0.190759E+10 | 0.262861E+10 | 0.161461E+10 | 0.101400E+10 | 0.00 | 0.00 |
April | 0.363907E+10 | 0.104143E+10 | 0.352867E+10 | 0.203988E+10 | 0.148879E+10 | 0.00 | 0.00 |
May | 0.395427E+10 | 0.523927E+09 | 0.356906E+10 | 0.185135E+10 | 0.171771E+10 | 0.00 | 0.00 |
June | 0.376361E+10 | 0.275884E+09 | 0.328760E+10 | 0.141240E+10 | 0.187520E+10 | 0.00 | 0.00 |
July | 0.369832E+10 | 0.330243E+09 | 0.316038E+10 | 0.138348E+10 | 0.177690E+10 | 0.00 | 0.00 |
August | 0.331619E+10 | 0.508288E+09 | 0.290918E+10 | 0.148731E+10 | 0.142187E+10 | 0.00 | 0.00 |
September | 0.205621E+10 | 0.884411E+09 | 0.203598E+10 | 0.109660E+10 | 0.939376E+09 | 0.00 | 0.00 |
October | 0.104193E+10 | 0.169719E+10 | 0.132124E+10 | 0.740175E+09 | 0.581062E+09 | 0.00 | 0.00 |
November | 0.233273E+09 | 0.296691E+10 | 0.594393E+09 | 0.381358E+09 | 0.213035E+09 | 0.00 | 0.00 |
December | 3086410.02 | 0.363926E+10 | 0.102778E+09 | 66319952.62 | 36458094.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.249351E+11 | 0.193780E+11 | 0.246948E+11 | 0.130546E+11 | 0.116402E+11 | 0.00 | 0.00 |
Minimum of Months | 3086410.02 | 0.275884E+09 | 0.102778E+09 | 66319952.62 | 36458094.83 | 0.00 | 0.00 |
Maximum of Months | 0.395427E+10 | 0.363926E+10 | 0.356906E+10 | 0.203988E+10 | 0.187520E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.170534E+11 | -0.162503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803116487.4 | 58.99 | 0.00 | 0.00 |
February | 0.154036E+11 | -0.146781E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -725489624.8 | 58.99 | 0.00 | 0.00 |
March | 0.170863E+11 | -0.162845E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -801834697.7 | 58.99 | 0.00 | 0.00 |
April | 0.164873E+11 | -0.157202E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -767046390.3 | 58.99 | 0.00 | 0.00 |
May | 0.168914E+11 | -0.161466E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -744832991.9 | 59.00 | 0.00 | 0.00 |
June | 0.157222E+11 | -0.150551E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -667094370.4 | 58.99 | 0.00 | 0.00 |
July | 0.156136E+11 | -0.149295E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -684086224.1 | 58.99 | 0.00 | 0.00 |
August | 0.153109E+11 | -0.146063E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -704561584.5 | 59.00 | 0.00 | 0.00 |
September | 0.148036E+11 | -0.140556E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -748019565.2 | 58.99 | 0.00 | 0.00 |
October | 0.156097E+11 | -0.148147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795004706.4 | 58.98 | 0.00 | 0.00 |
November | 0.156413E+11 | -0.148660E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -775342518.8 | 58.99 | 0.00 | 0.00 |
December | 0.167771E+11 | -0.159741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803023137.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.192400E+12 | -0.183381E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.901945E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.148036E+11 | -0.162845E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -803116487.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.170863E+11 | -0.140556E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -667094370.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.880406E+11 | 68994.54 | 01-JAN-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716811E+11 | 68994.54 | 01-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619178E+11 | 68994.54 | 01-MAR-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.270480E+11 | 68994.54 | 02-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.577167E+10 | 21607.81 | 27-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580942E+09 | 7425.29 | 02-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.568752E+09 | 7235.61 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221022E+10 | 18554.29 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143219E+11 | 25771.36 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.423923E+11 | 68994.54 | 22-OCT-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.832774E+11 | 68994.54 | 03-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.924928E+11 | 68994.54 | 01-DEC-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.490303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.568752E+09 | 7235.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.924928E+11 | 68994.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.893879E+11 | 93595.20 | 13-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.734692E+11 | 85650.11 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.636230E+11 | 80955.63 | 16-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.268212E+11 | 67425.03 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.352698E+10 | 21115.46 | 28-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45266849.93 | 6783.19 | 08-JUN-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41465182.27 | 4942.06 | 19-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103604E+10 | 25606.07 | 31-AUG-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102700E+11 | 27027.52 | 30-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403719E+11 | 51948.79 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.849995E+11 | 86711.79 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936054E+11 | 92150.71 | 15-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.487198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 41465182.27 | 4942.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.936054E+11 | 93595.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.149137E+09 | 0.149137E+09 | 6641.78 | 31-MAY-16:05 | 6641.78 | 0.00 |
June | 0.00 | 0.00 | 0.324627E+10 | 0.310175E+10 | 20489.47 | 30-JUN-04:01 | 12891.84 | 0.00 |
July | 0.00 | 0.00 | 0.628976E+10 | 0.581758E+10 | 28068.36 | 25-JUL-04:01 | 16327.29 | 0.00 |
August | 0.00 | 0.00 | 0.247785E+10 | 0.232038E+10 | 25126.53 | 13-AUG-04:01 | 13683.10 | 0.00 |
September | 0.00 | 0.00 | 2338.58 | 2338.58 | 3.90 | 10-SEP-14:00 | 3.90 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121630E+11 | 0.113889E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.628976E+10 | 0.581758E+10 | 28068.36 | 16327.29 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 498781.09 | 372362.57 | 1150.41 | 21-APR-03:40 | 865.40 | 0.00 |
May | 0.00 | 0.00 | 0.186541E+09 | 0.183294E+09 | 22844.31 | 14-MAY-04:01 | 19208.84 | 0.00 |
June | 0.00 | 0.00 | 0.364436E+10 | 0.346777E+10 | 22844.31 | 03-JUN-04:01 | 15787.64 | 0.00 |
July | 0.00 | 0.00 | 0.677499E+10 | 0.619031E+10 | 22844.31 | 14-JUL-03:01 | 12101.92 | 0.00 |
August | 0.00 | 0.00 | 0.279162E+10 | 0.250181E+10 | 22844.31 | 01-AUG-03:31 | 11510.77 | 0.00 |
September | 0.00 | 0.00 | 8488601.69 | 5566240.71 | 4223.85 | 01-SEP-03:08 | 2386.51 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134065E+11 | 0.123491E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677499E+10 | 0.619031E+10 | 22844.31 | 19208.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6367.10 | 23784.68 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6366.92 | 23784.33 | 05-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6381.20 | 23784.91 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6363.62 | 23785.73 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6328.01 | 23785.59 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6106.24 | 23161.56 | 01-JUN-12:23 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5867.27 | 22208.24 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5748.99 | 21475.00 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5715.99 | 21341.52 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5825.63 | 21971.02 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6032.23 | 22879.06 | 30-NOV-13:15 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 6261.43 | 23782.64 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.29 | ||||
Minimum of Months | 0.00 | 0.00 | 5715.99 | 21341.52 | ||
Maximum of Months | 0.00 | 0.00 | 6381.20 | 23785.73 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270490E+10 | 0.54 | 1211.87 | 01-JAN-00:01 | 0.65 |
February | 0.244314E+10 | 0.54 | 1211.87 | 01-FEB-00:01 | 0.65 |
March | 0.270490E+10 | 0.54 | 1211.87 | 01-MAR-00:01 | 0.65 |
April | 0.262164E+10 | 0.54 | 1211.87 | 01-APR-04:01 | 0.65 |
May | 0.278179E+10 | 0.55 | 1211.87 | 01-MAY-04:01 | 0.64 |
June | 0.289475E+10 | 0.59 | 1211.87 | 01-JUN-01:30 | 0.65 |
July | 0.302651E+10 | 0.60 | 1211.87 | 01-JUL-00:25 | 0.64 |
August | 0.297379E+10 | 0.59 | 1211.87 | 01-AUG-00:20 | 0.65 |
September | 0.267745E+10 | 0.55 | 1211.87 | 01-SEP-03:08 | 0.64 |
October | 0.270854E+10 | 0.54 | 1211.87 | 01-OCT-04:01 | 0.64 |
November | 0.261765E+10 | 0.54 | 1211.87 | 01-NOV-04:01 | 0.65 |
December | 0.270490E+10 | 0.54 | 1211.87 | 01-DEC-00:01 | 0.65 |
Annual Sum or Average | 0.328600E+11 | 0.56 | |||
Minimum of Months | 0.244314E+10 | 0.54 | 1211.87 | 0.64 | |
Maximum of Months | 0.302651E+10 | 0.60 | 1211.87 | 0.65 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.413929E+10 | 0.79 | 1788.10 | 01-JAN-05:06 | 0.90 |
February | 0.371160E+10 | 0.78 | 1788.10 | 01-FEB-00:13 | 0.90 |
March | 0.407338E+10 | 0.77 | 1788.10 | 01-MAR-05:06 | 0.90 |
April | 0.387215E+10 | 0.75 | 1788.10 | 04-APR-04:01 | 0.90 |
May | 0.399103E+10 | 0.74 | 1788.10 | 01-MAY-04:16 | 0.89 |
June | 0.386277E+10 | 0.74 | 1788.10 | 01-JUN-07:16 | 0.89 |
July | 0.399180E+10 | 0.74 | 1788.10 | 02-JUL-05:50 | 0.88 |
August | 0.399145E+10 | 0.74 | 1788.10 | 01-AUG-05:50 | 0.89 |
September | 0.386229E+10 | 0.74 | 1788.10 | 01-SEP-06:53 | 0.89 |
October | 0.401572E+10 | 0.76 | 1788.10 | 01-OCT-05:00 | 0.89 |
November | 0.399036E+10 | 0.78 | 1788.10 | 07-NOV-00:10 | 0.90 |
December | 0.414081E+10 | 0.78 | 1788.10 | 01-DEC-05:05 | 0.90 |
Annual Sum or Average | 0.476426E+11 | 0.76 | |||
Minimum of Months | 0.371160E+10 | 0.74 | 1788.10 | 0.88 | |
Maximum of Months | 0.414081E+10 | 0.79 | 1788.10 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307684E+10 | 0.77 | 1378.51 | 08-JAN-00:20 | 0.93 |
February | 0.277908E+10 | 0.77 | 1378.51 | 02-FEB-05:07 | 0.93 |
March | 0.307684E+10 | 0.77 | 1378.51 | 19-MAR-16:37 | 0.92 |
April | 0.297770E+10 | 0.77 | 1378.51 | 06-APR-18:10 | 0.93 |
May | 0.308379E+10 | 0.79 | 1378.51 | 02-MAY-05:57 | 0.92 |
June | 0.302133E+10 | 0.84 | 1378.51 | 01-JUN-05:10 | 0.92 |
July | 0.312955E+10 | 0.85 | 1378.51 | 03-JUL-12:20 | 0.92 |
August | 0.311855E+10 | 0.84 | 1378.51 | 12-AUG-16:17 | 0.92 |
September | 0.298163E+10 | 0.78 | 1378.51 | 14-SEP-04:20 | 0.92 |
October | 0.307702E+10 | 0.77 | 1378.51 | 08-OCT-19:50 | 0.92 |
November | 0.297758E+10 | 0.77 | 1378.51 | 24-NOV-00:05 | 0.93 |
December | 0.307684E+10 | 0.77 | 1378.51 | 01-DEC-00:02 | 0.93 |
Annual Sum or Average | 0.363768E+11 | 0.79 | |||
Minimum of Months | 0.277908E+10 | 0.77 | 1378.51 | 0.92 | |
Maximum of Months | 0.312955E+10 | 0.85 | 1378.51 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.32 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.13 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.21 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 49.84 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:03 | 0.00 | 0.00 | 45.67 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:05 | 0.00 | 0.00 | 49.85 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 50.62 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 51.00 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 51.29 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 49.39 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 50.66 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.58 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 45.67 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 51.29 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 33.61 | 33.61 | 6367.10 | 23784.68 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 49.97 | 49.97 | 6366.92 | 23784.33 | 05-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.87 | 49.87 | 6381.20 | 23784.91 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.87 | 49.87 | 6363.62 | 23785.73 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 33.71 | 33.71 | 6328.01 | 23785.59 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 49.99 | 49.99 | 6106.24 | 23161.56 | 01-JUN-12:23 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.87 | 50.87 | 5867.27 | 22208.24 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 51.06 | 51.06 | 5748.99 | 21475.00 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.00 | 51.00 | 5715.99 | 21341.52 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 36.14 | 36.14 | 5825.63 | 21971.02 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.80 | 50.80 | 6032.23 | 22879.06 | 30-NOV-13:15 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 50.35 | 50.35 | 6261.43 | 23782.64 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.29 | ||||||
Minimum of Months | 0.00 | 0.00 | 33.61 | 33.61 | 5715.99 | 21341.52 | ||
Maximum of Months | 0.00 | 0.00 | 51.06 | 51.06 | 6381.20 | 23785.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.413929E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.371160E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.407338E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.387215E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.403577E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.478823E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.576251E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.470456E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.386229E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401572E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.399036E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.414081E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.510967E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.371160E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.576251E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.307684E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.277908E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.307684E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.297786E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.313917E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.404953E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.500499E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.391699E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.298420E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.307702E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.297758E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.307684E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.401369E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.277908E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.500499E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.413929E+10 | 0.00 | 0.880406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371160E+10 | 0.00 | 0.716811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407338E+10 | 0.00 | 0.619178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387215E+10 | 0.00 | 0.270480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399103E+10 | 0.149137E+09 | 0.577167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386277E+10 | 0.324627E+10 | 0.580942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399180E+10 | 0.628976E+10 | 0.568752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399145E+10 | 0.247785E+10 | 0.221022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.386229E+10 | 2338.58 | 0.143219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401572E+10 | 0.00 | 0.423923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399036E+10 | 0.00 | 0.832774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414081E+10 | 0.00 | 0.924928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476426E+11 | 0.121630E+11 | 0.490303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371160E+10 | 0.00 | 0.568752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.414081E+10 | 0.628976E+10 | 0.924928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307684E+10 | 0.00 | 0.893879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277908E+10 | 0.00 | 0.734692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307684E+10 | 0.00 | 0.636230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297770E+10 | 498781.09 | 0.268212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308379E+10 | 0.186541E+09 | 0.352698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.302133E+10 | 0.364436E+10 | 45266849.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.312955E+10 | 0.677499E+10 | 41465182.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311855E+10 | 0.279162E+10 | 0.103604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.298163E+10 | 8488601.69 | 0.102700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307702E+10 | 0.00 | 0.403719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297758E+10 | 0.00 | 0.849995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307684E+10 | 0.00 | 0.936054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363768E+11 | 0.134065E+11 | 0.487198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277908E+10 | 0.00 | 41465182.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312955E+10 | 0.677499E+10 | 0.936054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.413929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.387215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399103E+10 | 0.00 | 0.00 | 0.00 | 44746807.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386277E+10 | 0.00 | 0.00 | 0.00 | 0.925460E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399180E+10 | 0.00 | 0.00 | 0.00 | 0.177072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399145E+10 | 0.00 | 0.00 | 0.00 | 0.713104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.386229E+10 | 0.00 | 0.00 | 0.00 | 727.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.401572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.476426E+11 | 0.00 | 0.00 | 0.00 | 0.345403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.414081E+10 | 0.00 | 0.00 | 0.00 | 0.177072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.307684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297770E+10 | 0.00 | 0.00 | 0.00 | 153360.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308379E+10 | 0.00 | 0.00 | 0.00 | 55376580.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.302133E+10 | 0.00 | 0.00 | 0.00 | 0.102820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.312955E+10 | 0.00 | 0.00 | 0.00 | 0.187544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311855E+10 | 0.00 | 0.00 | 0.00 | 0.798432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.298163E+10 | 0.00 | 0.00 | 0.00 | 2569666.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.307702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.363768E+11 | 0.00 | 0.00 | 0.00 | 0.376017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312955E+10 | 0.00 | 0.00 | 0.00 | 0.187544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482538E+11 | 0.00 | 0.00 | 3.66 |
February | 0.161754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400935E+11 | 0.00 | 0.00 | 3.62 |
March | 0.170940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372608E+11 | 0.00 | 0.00 | 3.60 |
April | 0.376385E+10 | 0.00 | 0.00 | 45850.15 | 0.00 | 0.193224E+11 | 0.105543E+09 | 0.00 | 3.59 |
May | 0.735991E+10 | 0.00 | 0.00 | 4404074.52 | 0.00 | 0.460386E+10 | 0.262017E+10 | 0.00 | 4.07 |
June | 0.489244E+10 | 14255864.00 | 0.00 | 19227214.24 | 0.00 | 0.262328E+09 | 0.679783E+10 | 0.00 | 5.63 |
July | 0.422079E+10 | 61912542.11 | 0.00 | 25509531.22 | 0.00 | 0.374977E+09 | 0.643829E+10 | 0.00 | 5.72 |
August | 0.619518E+10 | 0.00 | 0.00 | 15373776.35 | 0.00 | 0.154373E+10 | 0.547913E+10 | 0.00 | 5.15 |
September | 0.572782E+10 | 0.00 | 0.00 | 282696.01 | 0.00 | 0.111612E+11 | 0.382232E+09 | 0.00 | 3.59 |
October | 0.217884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272575E+11 | 0.00 | 0.00 | 3.59 |
November | 0.185787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461699E+11 | 0.00 | 0.00 | 3.62 |
December | 0.197695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499160E+11 | 0.00 | 0.00 | 3.65 |
Annual Sum or Average | 0.433618E+11 | 76168406.12 | 0.00 | 64843142.49 | 0.00 | 0.286220E+12 | 0.218232E+11 | 0.00 | 4.13 |
Minimum of Months | 0.161754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262328E+09 | 0.00 | 0.00 | 3.59 |
Maximum of Months | 0.735991E+10 | 61912542.11 | 0.00 | 25509531.22 | 0.00 | 0.499160E+11 | 0.679783E+10 | 0.00 | 5.72 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119562E+12 | 0.00 | 0.00 | 13139.56 | 0.00 | 0.165371E+09 | 7390557.22 | 0.00 | 9.79 |
February | 0.101157E+12 | 0.00 | 0.00 | 15531.89 | 0.00 | 0.152933E+09 | 11124008.12 | 0.00 | 9.68 |
March | 0.960951E+11 | 0.00 | 0.00 | 39460.27 | 0.00 | 0.117033E+09 | 18875419.59 | 0.00 | 9.68 |
April | 0.608853E+11 | 0.00 | 0.00 | 306107.24 | 0.00 | 35787282.76 | 0.459771E+09 | 0.00 | 9.75 |
May | 0.305222E+11 | 0.00 | 0.00 | 11894819.00 | 0.00 | 0.00 | 0.995838E+10 | 0.00 | 9.88 |
June | 0.110684E+11 | 0.00 | 0.00 | 46459598.80 | 0.00 | 0.00 | 0.218081E+11 | 0.00 | 10.38 |
July | 0.103046E+11 | 2176142.48 | 0.00 | 56371862.83 | 0.00 | 0.00 | 0.208112E+11 | 0.00 | 10.50 |
August | 0.169411E+11 | 0.00 | 0.00 | 37697966.91 | 0.00 | 0.00 | 0.194702E+11 | 0.00 | 10.21 |
September | 0.428554E+11 | 0.00 | 0.00 | 1825258.58 | 0.00 | 0.00 | 0.319094E+10 | 0.00 | 9.79 |
October | 0.749107E+11 | 0.00 | 0.00 | 333324.14 | 0.00 | 40986782.81 | 0.146128E+09 | 0.00 | 9.74 |
November | 0.115587E+12 | 0.00 | 0.00 | 46025.65 | 0.00 | 0.149003E+09 | 22443701.06 | 0.00 | 9.72 |
December | 0.123704E+12 | 0.00 | 0.00 | 7083.73 | 0.00 | 0.176684E+09 | 4174735.69 | 0.00 | 9.74 |
Annual Sum or Average | 0.803592E+12 | 2176142.48 | 0.00 | 0.155010E+09 | 0.00 | 0.837798E+09 | 0.759087E+11 | 0.00 | 9.91 |
Minimum of Months | 0.103046E+11 | 0.00 | 0.00 | 7083.73 | 0.00 | 0.00 | 4174735.69 | 0.00 | 9.68 |
Maximum of Months | 0.123704E+12 | 2176142.48 | 0.00 | 56371862.83 | 0.00 | 0.176684E+09 | 0.218081E+11 | 0.00 | 10.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.522689E+10 | 0.490783E+11 | 0.214791E+12 | 0.00 | 0.577864E+11 |
February | 0.292024E+10 | 0.413291E+11 | 0.182005E+12 | 0.00 | 0.505597E+11 |
March | 0.239115E+11 | 0.394042E+11 | 0.173060E+12 | 0.00 | 0.488336E+11 |
April | 0.468168E+11 | 0.241978E+11 | 0.111205E+12 | 41742.39 | 0.321871E+11 |
May | 0.607449E+11 | 0.145304E+11 | 0.760146E+11 | 0.111928E+10 | 0.237109E+11 |
June | 0.632854E+11 | 0.971092E+10 | 0.642067E+11 | 0.398185E+10 | 0.316481E+11 |
July | 0.572623E+11 | 0.847056E+10 | 0.621504E+11 | 0.376149E+10 | 0.407824E+11 |
August | 0.419747E+11 | 0.110864E+11 | 0.712951E+11 | 0.309497E+10 | 0.296662E+11 |
September | 0.182768E+11 | 0.173686E+11 | 0.867673E+11 | 19700198.43 | 0.221391E+11 |
October | 0.586167E+10 | 0.303290E+11 | 0.135685E+12 | 0.00 | 0.338298E+11 |
November | -0.204589E+10 | 0.470970E+11 | 0.207130E+12 | 0.00 | 0.554234E+11 |
December | -0.679974E+10 | 0.513683E+11 | 0.222187E+12 | 0.00 | 0.595773E+11 |
Annual Sum or Average | 0.306982E+12 | 0.343971E+12 | 0.160650E+13 | 0.119773E+11 | 0.486144E+12 |
Minimum of Months | -0.679974E+10 | 0.847056E+10 | 0.621504E+11 | 0.00 | 0.221391E+11 |
Maximum of Months | 0.632854E+11 | 0.513683E+11 | 0.222187E+12 | 0.398185E+10 | 0.595773E+11 |