Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:29:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1240.23 | 5337.91 | 5337.91 |
Net Site Energy | 1240.23 | 5337.91 | 5337.91 |
Total Source Energy | 2602.38 | 11200.60 | 11200.60 |
Net Source Energy | 2602.38 | 11200.60 | 11200.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 40.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 603.92 | 636.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 61.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 19.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 20.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 61.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 157.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 40.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 155.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1184.84 | 684.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1259.40 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2599.28 | 2738.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 155.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1184.84 | 684.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1259.40 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2599.28 | 2738.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 603.925 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 603.925 | 100.00 |
Total On-Site and Utility Electric Sources | 603.925 | 100.00 |
Total Electricity End Uses | 603.925 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1022.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6798.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.1965 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 8.9582 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.1965 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.9582 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.5774 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-JUL-10:20 | 17-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15918.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13637.09 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3051.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23294.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3931.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 37444.95 | 46277.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15918.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13046.29 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3051.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 23294.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 678.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 170.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 128.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1912.63 | 689.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2919.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 832.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 734.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 552.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8231.93 | 2968.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 8.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2919.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 281.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 832.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 734.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 552.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8231.93 | 2968.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.01 |
KITCHEN DIRECT AIR | 1.16 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 2.01 | 1.00 | 0.999935 | 2.01 |
PSZ-AC_2:2 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.16 | 1.00 | 1.00 | 1.16 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.01 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.16 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.01 | 2150.33 |
PSZ-AC_2:2_ADDAQ FAN | 1.16 | 1279.34 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.01 | 2.01 | 2.01 | 1.33 | 49902.37 | 52116.00 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 0.762641 | 28694.23 | 43860.74 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.01 | 1.00 | 1.34 | 49902.37 | 24951.19 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.16 | 0.577758 | 0.770347 | 28694.23 | 14347.11 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 52116.00 |
PSZ-AC_2:2 HEATING COIL | 43860.74 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.196 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 120.983 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 8.958 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1076.278 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 487.511 | 4.196 | 5.569 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 487.511 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1040.691 | 8.958 | 165.892 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.691 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5026_SHGC_SOUTH_0.23 | 38 | 1 | VerySmooth | 2.857 | 2.857 | 1.000 | 0.231 | ||
2 | NONRESWINDOW_U_0.5026_SHGC_NORTH_0.23 | 39 | 1 | VerySmooth | 2.857 | 2.857 | 1.000 | 0.231 | ||
3 | NONRESWINDOW_U_0.5026_SHGC_EAST_0.23 | 40 | 1 | VerySmooth | 2.857 | 2.857 | 1.000 | 0.231 | ||
4 | NONRESWINDOW_U_0.5026_SHGC_WEST_0.23 | 41 | 1 | VerySmooth | 2.857 | 2.857 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 1.94078E-002 | 0.14129 | 0.63066 | 0.63066 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10800 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 1.94078E-002 | 0.14129 | 0.63066 | 0.63066 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10800 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 1.94078E-002 | 0.14129 | 0.63066 | 0.63066 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10800 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 1.94078E-002 | 0.14129 | 0.63066 | 0.63066 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10800 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.323E-002 | 1.139E-004 | 1.424E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.323E-002 | 1.139E-004 | 1.395E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3771E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0739E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2577E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.6398E-003 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.1369E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0817E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.1721E-004 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.1066E-003 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.9246E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.8417E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.1680E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.0709E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.3449E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.2920E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.8613E-003 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.8614E-003 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.8139E-003 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1757E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 7.3983E-003 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.0142E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.3607E-003 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.2222E-004 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.1078E-003 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.1722E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 22724.35861 | 27269.23033 | 1.67453 | 2.00944 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 2039.75808 | 2447.70970 | 8.55611E-002 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 8.70000 | 6.99286E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15719.57784 | 18863.49341 | 0.96293 | 1.15552 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 8.70000 | 6.99286E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 31544.95 | 2.00957 | 2.00957 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 15738.84 | 0.41606 | 0.41606 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 28139.67 | 1.15552 | 1.15552 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 43175.09 | 1.14133 | 1.14133 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00944 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15552 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00944 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00944 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00944 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00944 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00957 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.00957 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 0.99993 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15552 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15552 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15552 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15552 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15552 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15552 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.00957 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.15552 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00957 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00957 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2150.33321 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00957 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00957 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00957 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.32632 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00957 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00478 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33971 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49902.37000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24951.18500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49902.37000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52115.99742 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 52115.99742 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15552 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15552 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1279.34029 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15552 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15552 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15552 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.76264 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15552 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57776 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.77035 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28694.23000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14347.11500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28694.23000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43860.74411 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 43860.74411 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 48474.0 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27872.9 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5026_SHGC_EAST_0.23 | N/A | 2.857 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5026_SHGC_SOUTH_0.23 | N/A | 2.857 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5026_SHGC_WEST_0.23 | N/A | 2.857 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 4.6031753689E-002 | 0.1774080872 | Pass | Pass | 6.2104643938E-002 | 0.1955518080 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1637021105 | 0.4526962083 | Pass | Pass | 0.2126271111 | 0.9251577230 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4248919720 | 0.4443734711 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 597.90 | -72.2 | -165.5 | 11.03 | 1378.16 | 1749.44 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5026_SHGC_EAST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.857 | 0.231 | 0.231 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5026_SHGC_SOUTH_0.23 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.857 | 0.231 | 0.231 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.5026_SHGC_WEST_0.23 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.857 | 0.231 | 0.231 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.857 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.857 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.1965 | 116.17 | 487.51 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 46.31 | 0.0000 | Y | 4.24 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.9582 | 116.17 | 1040.69 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 16.40 |
Interior Lighting Total | 6.5774 | 232.34 | 1528.20 | 20.64 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 166.91 | AstronomicalClock | - | 48.82 | 48.82 | 1.53 | |
EXTERIOR_LIGHTS_B | 1174.86 | AstronomicalClock | - | 83.82 | 62.82 | 13.86 | |
Exterior Lighting Total | 1341.77 | 15.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49902.37 | 34985.55 | 14916.82 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28694.23 | 20116.95 | 8577.28 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 48474.0 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 27872.9 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 52116.00 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 43860.74 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.01 | 2150.33 | 1070.05 | 1.00 | 1.31 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1279.34 | 1107.16 | 1.00 | 1.37 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 22724.36 | 27269.23 | 234.73 | 1.675 | 2.009 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.86 | 0.01210 | 33.13 | 0.01717 | 0.416 | 0.00 |
KITCHEN | 15719.58 | 18863.49 | 162.38 | 0.963 | 1.156 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01028 | 32.60 | 0.01717 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 2039.76 | 2447.71 | 21.07 | 0.086 | 0.416 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00790 | 8.70 | 0.00699 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 24.98 | 0.00442 | 8.70 | 0.00699 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.01 | 2.01 | 0.42 | 0.42 | 2.0096 | 2.0094 | 2.0096 | 0.9999 | 1.0000 |
PSZ-AC_2:2 | 1.16 | 1.16 | 1.14 | 1.14 | 1.1555 | 1.1555 | 1.1555 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 49902.370 | 34985.554 | 2.009570 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24951.19 | 13734.68 | 1.339713 | 25.79 | 20.63 | 0.01314609 | 11.94 | 11.73 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 31.0556 | 23.86 | 0.01209620 | 65.2167 | 22722.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 52115.997 | 52115.997 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 52116.00 | 52116.00 | 2.009568 | 18.54 | 13.67 | 0.00775431 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 20.7038 | 20.79 | 0.00795312 | 52.0213 | 1118.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28694.230 | 20116.951 | 1.155520 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14347.11 | 7150.01 | 0.770347 | 33.20 | 25.32 | 0.01716721 | 11.91 | 11.72 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 148.1584 | 26.09 | 0.01048349 | 49.6055 | 14063.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 43860.744 | 43860.744 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 43860.74 | 43860.74 | 1.155517 | 8.59 | 8.59 | 0.00696128 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 98.7726 | 24.98 | 0.00442048 | 22.5628 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49902.370 | 34985.554 | 2.009570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.2779 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.009568 | 2.41698619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 24951.19 | 13734.68 | 1.0000 | 1.61132539 | 1.339713 | 25.79 | 20.63 | 0.01314609 | 59420.9 | 11.94 | 11.73 | 0.00850000 | 33440.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24951.19 | 33.20 | 0.01716721 | 25.32 | 0.41605618 | 31.0556 | 23.85 | 0.01209620 | 23.86 | 0.01209620 | 65.2167 | 22722.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52115.997 | 52115.997 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.009568 | 2.41698619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 52116.00 | 52116.00 | 1.0000 | 2.41698619 | 2.009568 | 18.54 | 13.67 | 0.00775431 | 38290.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52116.00 | 8.70 | 0.00699286 | 8.70 | 0.41605618 | 20.7038 | 21.11 | 0.00795312 | 20.79 | 0.00795312 | 52.0213 | 1118.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28694.230 | 20116.951 | 1.155520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7530 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.155517 | 1.38978480 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14347.11 | 7150.01 | 1.0000 | 0.92652593 | 0.770347 | 33.20 | 25.32 | 0.01716721 | 77354.4 | 11.91 | 11.72 | 0.00850000 | 33416.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14347.11 | 33.20 | 0.01716721 | 25.32 | 1.14133354 | 148.1584 | 26.04 | 0.01048349 | 26.09 | 0.01048349 | 49.6055 | 14063.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43860.744 | 43860.744 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.155517 | 1.38978480 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 43860.74 | 43860.74 | 1.0000 | 1.38978480 | 1.155517 | 8.59 | 8.59 | 0.00696128 | 26155.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43860.74 | 8.70 | 0.00699286 | 8.70 | 1.14133354 | 98.7726 | 0.00 | 0.00442048 | 24.98 | 0.00442048 | 22.5628 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 6625.33 | 5201.33 | 4770.83 |
KITCHEN | 7089.17 | 6851.33 | 6797.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7090.00 | 7160.33 | 6798.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 18.33 | 0.00 | 0.00 |
KITCHEN | 0.00 | 1344.67 | 0.00 | 1022.83 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1363.00 | 0.00 | 1022.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.329 | 4.118 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.653 | 0.008 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.170 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.618 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11015652.91 | 0.00 | 11015652.91 | 10262480.03 | 21278132.94 | 13120747.55 | 1453.35 | 7306.65 | 0.00 | 286.92 |
KITCHEN | 24949807.13 | 0.00 | 24949807.13 | 31053.42 | 24980860.55 | 35993094.65 | 7009.49 | 1741.76 | 8.75 | 1049.29 |
Total Facility | 35965460.04 | 0.00 | 35965460.04 | 10293533.45 | 46258993.48 | 49113842.20 | 7018.53 | 7307.38 | 8.75 | 1124.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4161 | 0.0000 | 0.4161 | 0.3962 | 0.8123 | 0.4161 | 0.00 | 7187.00 | 0.00 |
KITCHEN | 0.9193 | 0.0000 | 0.9193 | 0.0007 | 0.9200 | 1.1413 | 5451.54 | 1735.46 | 0.00 |
Total Facility | 1.3354 | 0.0000 | 1.3354 | 0.3969 | 1.7323 | 1.5574 | 5451.54 | 7187.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15934976.87 | 0.00 | 15934976.87 | 13120747.55 | 1445.66 | 0.76 | 7313.58 | 286.87 |
PSZ-AC_2:2 | 36091855.61 | 0.00 | 36091855.61 | 35993094.65 | 4373.81 | 133.15 | 4253.04 | 1049.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6019 | 0.0000 | 0.6019 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.3298 | 0.0000 | 1.3298 | 1.1413 | 2883.90 | 127.78 | 4175.32 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 167.23 | 0.00 | 7306.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 3317.95 | 4918.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 0.6019 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.5157 | 1.2443 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
Electricity:Building | 280.67 | 1825.29 | 01-JAN-01:10 | 17838.45 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.57 | 336.73 | 01-JAN-01:10 | 4026.33 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 272.73 | 1689.01 | 01-JAN-01:10 | 14544.40 | 02-JAN-11:10 |
InteriorLights:Electricity | 20.64 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:40 |
InteriorLights:Electricity:Zone:DINING | 4.24 | 32.03 | 01-JAN-07:50 | 400.32 | 02-JAN-17:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 20.64 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity | 20.64 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.24 | 32.03 | 01-JAN-07:50 | 400.32 | 02-JAN-17:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 20.64 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:40 |
Electricity:Zone:KITCHEN | 206.10 | 1488.56 | 01-JAN-01:10 | 13812.12 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 40.52 | 621.08 | 03-FEB-23:30 | 3931.14 | 02-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 32.58 | 535.30 | 03-FEB-23:30 | 1653.75 | 19-SEP-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 12.86 | 0.00 | 01-JAN-11:10 | 1016.65 | 19-SEP-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 19.72 | 513.13 | 04-FEB-06:00 | 637.09 | 01-JAN-02:00 |
ElectricityPurchased:Facility | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
ElectricityPurchased:Plant | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
Cogeneration:ElectricityPurchased | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
ElectricityNet:Plant | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
Cogeneration:ElectricityNet | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
General:Cogeneration:ElectricityNet | 603.92 | 3167.42 | 04-FEB-01:10 | 37444.95 | 25-JUL-10:20 |
Electricity:HVAC | 275.29 | 0.00 | 01-JAN-01:10 | 21842.92 | 27-JUL-17:10 |
Fans:Electricity | 61.09 | 0.00 | 01-JAN-01:10 | 3529.39 | 14-JUL-11:30 |
General:Fans:Electricity | 61.09 | 0.00 | 01-JAN-01:10 | 3529.39 | 14-JUL-11:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 214.20 | 0.00 | 01-JAN-00:10 | 18358.09 | 27-JUL-17:10 |
General:Cooling:Electricity | 214.20 | 0.00 | 01-JAN-00:10 | 18358.09 | 27-JUL-17:10 |
ExteriorLights:Electricity | 15.38 | 0.00 | 01-JAN-07:20 | 1341.77 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.38 | 0.00 | 01-JAN-07:20 | 1341.77 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JAN-15:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 636.30 | 2560.65 | 09-JAN-01:20 | 46277.39 | 17-JAN-13:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1.75 | 0.00 | 01-JAN-00:10 | 19556.98 | 04-FEB-07:10 |
Heating:NaturalGas | 1.75 | 0.00 | 01-JAN-00:10 | 19556.98 | 04-FEB-07:10 |
General:Heating:NaturalGas | 1.75 | 0.00 | 01-JAN-00:10 | 19556.98 | 04-FEB-07:10 |
NaturalGas:Plant | 157.39 | 722.00 | 03-JAN-04:30 | 23294.24 | 17-JAN-13:20 |
WaterSystems:NaturalGas | 157.39 | 722.00 | 03-JAN-04:30 | 23294.24 | 17-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 157.39 | 722.00 | 03-JAN-04:30 | 23294.24 | 17-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 26-APR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1607.98 | 3081.58 | 04-FEB-01:10 | 118469.62 | 22-AUG-13:00 |
EnergyTransfer:Building | 517.17 | 1540.79 | 04-FEB-01:10 | 34704.09 | 07-JUL-11:10 |
EnergyTransfer:Zone:KITCHEN | 339.75 | 1540.79 | 04-FEB-01:10 | 18425.29 | 23-OCT-11:00 |
Refrigeration:EnergyTransfer | 162.79 | 2993.25 | 03-FEB-23:30 | 7834.84 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.39 | 1496.63 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer | 81.39 | 1496.63 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 81.39 | 1496.63 | 03-FEB-23:30 | 3917.42 | 01-JAN-11:40 |
EnergyTransfer:Plant | 182.38 | 1540.79 | 04-FEB-01:10 | 16095.39 | 19-JAN-13:50 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.53 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.87 | 1335.03 | 04-FEB-06:00 | 2238.70 | 01-JAN-02:00 |
EnergyTransfer:Zone:DINING | 177.43 | 0.00 | 01-JAN-01:10 | 18843.06 | 29-JUL-18:10 |
Heating:EnergyTransfer | 0.40 | 0.00 | 01-JAN-00:10 | 6375.92 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:DINING | 0.40 | 0.00 | 01-JAN-00:10 | 6375.92 | 04-FEB-07:10 |
General:Heating:EnergyTransfer | 0.40 | 0.00 | 01-JAN-00:10 | 6375.92 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:DINING | 0.40 | 0.00 | 01-JAN-00:10 | 6375.92 | 04-FEB-07:10 |
Cooling:EnergyTransfer | 435.38 | 0.00 | 01-JAN-01:10 | 30880.64 | 07-JUL-12:00 |
Cooling:EnergyTransfer:Zone:DINING | 177.03 | 0.00 | 01-JAN-01:10 | 18843.06 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer | 435.38 | 0.00 | 01-JAN-01:10 | 30880.64 | 07-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:DINING | 177.03 | 0.00 | 01-JAN-01:10 | 18843.06 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 323.62 | 10-SEP-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.00 | 0.00 | 01-JAN-00:10 | 323.62 | 10-SEP-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 258.35 | 0.00 | 01-JAN-01:10 | 14507.87 | 23-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 258.35 | 0.00 | 01-JAN-01:10 | 14507.87 | 23-OCT-11:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
PlantLoopHeatingDemand:Plant | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
EnergyTransfer:HVAC | 908.43 | 0.00 | 01-JAN-00:10 | 76316.31 | 14-JUL-11:20 |
HeatingCoils:EnergyTransfer | 1.40 | 0.00 | 01-JAN-00:10 | 15645.58 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 907.03 | 0.00 | 01-JAN-00:10 | 76316.31 | 14-JUL-11:20 |
WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 100.98 | 0.00 | 01-JAN-00:10 | 13545.83 | 16-JAN-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 0.398 | -177.027 | 0.000 | 0.000 | 65.308 | 4.238 | 52.748 | 20.708 | 0.000 | 31.897 | 19.016 | 0.000 | -4.128 | 0.000 | -13.159 | 0.000 |
KITCHEN | 0.000 | 0.000 | 0.003 | -258.346 | 0.000 | 0.000 | 3.866 | 16.400 | 187.472 | 0.000 | 0.000 | 0.022 | 50.737 | 0.000 | 0.000 | 0.000 | -0.154 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.789 | 12.485 | 0.000 | 0.000 | 0.000 | -16.275 | -0.001 |
Total Facility | 0.000 | 0.000 | 0.401 | -435.373 | 0.000 | 0.000 | 69.174 | 20.638 | 240.220 | 20.708 | 0.000 | 35.709 | 82.238 | 0.000 | -4.128 | 0.000 | -29.588 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-MAR-05:01 | 0.00 | 0.00 | 0.00 | -22257.66 | 0.00 | 0.00 | 262.86 | 88.96 | 1219.73 | 0.00 | 0.00 | 0.00 | 21058.59 | 0.00 | -367.78 | 0.00 | -4.71 | 0.00 |
KITCHEN | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | -42192.62 | 0.00 | 0.00 | 8.46 | 180.28 | 4494.65 | 0.00 | 0.00 | 0.00 | 37531.96 | 0.00 | -0.00 | 0.00 | -22.73 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-MAR-05:01 | 0.00 | 0.00 | 0.00 | -50901.38 | 0.00 | 0.00 | 270.64 | 269.24 | 5714.39 | 0.00 | 0.00 | 299.48 | 44733.80 | 0.00 | -367.78 | 0.00 | -18.38 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-FEB-07:10 | 0.00 | 0.00 | 6377.64 | 0.00 | 0.00 | 0.00 | 3598.57 | 125.49 | 1524.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -679.83 | 0.00 | -10327.55 | -618.98 |
KITCHEN | 10-SEP-23:01 | 0.00 | 0.00 | 1709.29 | 0.00 | 0.00 | 0.00 | 16.72 | 135.21 | 1566.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3427.97 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-07:10 | -9988.76 | 9988.76 | 6377.64 | -9988.76 | 0.00 | 0.00 | 3883.16 | 395.91 | 6995.28 | 0.00 | 0.00 | 356.68 | 3005.91 | 0.00 | -679.83 | 0.00 | -10345.99 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0094 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0096 | 0.2070 | 1.0000 | Not calculated | 0.4161 | 0.2070 | ||
PSZ-AC_2:2 | 1.1555 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1555 | 0.1309 | 1.0000 | Not calculated | 0.1513 | 0.1309 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0094 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0094 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2071 | ||
PSZ-AC_2:2 | 1.1555 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1555 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1309 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0094 | 2.0094 | 2.0094 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1555 | 1.1555 | 1.1555 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0094 | 2.0096 | 2.0094 | 2.0094 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1555 | 1.1555 | 1.1555 | 1.1555 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0094 | 2.0094 | 2.0094 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1555 | 1.1555 | 1.1555 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0094 | 2.0094 | 2.0094 | 2.0094 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1555 | 1.1555 | 1.1555 | 1.1555 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1022.83 |
Number of hours not met | 1022.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1.75 | 19556.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 214.20 | 18358.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 20.64 | 1211.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.38 | 1341.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 61.09 | 3529.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 157.39 | 23294.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.86 | 1016.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 19.72 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 292.61 | 603.92 |
Natural Gas | 477.16 | 636.30 |
Additional | 0.00 | 0.00 |
Total | 769.77 | 1240.23 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 88.83 |
Space Heating | 0.00 |
Space Cooling | 921.90 |
Fans (All) | 262.94 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 2599.28 |
Subtotal | 2599.28 |
Natural Gas [MJ/m2] | |
Space Heating | 7.54 |
Service Water Heating | 677.41 |
Miscellaneous (All) | 2738.63 |
Subtotal | 2738.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.66 |
Space Heating | 0.14 |
Space Cooling | 17.27 |
Fans (All) | 4.93 |
Service Water Heating | 12.69 |
Receptacle Equipment | 58.80 |
Miscellaneous | 4.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | July | 23.89 | 365 | 25.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 27.22 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 7856.83 | 900.67 | 2.50 | 0.00 | 0.00 |
KITCHEN | 5311.17 | 3077.83 | 371.00 | 0.00 | 0.00 |
ATTIC | 4750.67 | 769.67 | 872.50 | 1263.00 | 1104.17 |
Min | 4750.67 | 769.67 | 2.50 | 0.00 | 0.00 |
Max | 7856.83 | 3077.83 | 872.50 | 1263.00 | 1104.17 |
Average | 5972.89 | 1582.72 | 415.33 | 421.00 | 368.06 |
Sum | 17918.67 | 4748.17 | 1246.00 | 1263.00 | 1104.17 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254045.67 | 670.67 | 8.67 | 0.00 | 0.00 |
KITCHEN | 12025.50 | 4226.67 | 5.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254045.67 | 4226.67 | 8.67 | 0.00 | 0.00 |
Average | 88690.39 | 1632.44 | 4.83 | 0.00 | 0.00 |
Sum | 266071.17 | 4897.33 | 14.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 2515.17 | 6244.50 | 0.33 | 0.00 | 0.00 |
KITCHEN | 721.50 | 7974.83 | 63.67 | 0.00 | 0.00 |
ATTIC | 2635.67 | 3212.50 | 706.67 | 650.00 | 1555.17 |
Min | 721.50 | 3212.50 | 0.33 | 0.00 | 0.00 |
Max | 2635.67 | 7974.83 | 706.67 | 650.00 | 1555.17 |
Average | 1957.44 | 5810.61 | 256.89 | 216.67 | 518.39 |
Sum | 5872.33 | 17431.83 | 770.67 | 650.00 | 1555.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 81661.17 | 173062.50 | 1.33 | 0.00 | 0.00 |
KITCHEN | 1312.50 | 14945.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 81661.17 | 173062.50 | 1.33 | 0.00 | 0.00 |
Average | 27657.89 | 62669.33 | 0.44 | 0.00 | 0.00 |
Sum | 82973.67 | 188008.00 | 1.33 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.918935E+10 | 19192.89 | 05-JAN-05:01 | 16.70 | 16.24 | 0.525502E+10 | 4681.02 | 07-JAN-19:10 | 21.10 | 20.05 |
February | 0.976188E+10 | 16448.20 | 20-FEB-05:01 | 16.60 | 14.98 | 0.481541E+10 | 4681.01 | 11-FEB-19:10 | 16.60 | 14.98 |
March | 0.111239E+11 | 22261.74 | 03-MAR-05:01 | 21.10 | 16.92 | 0.539521E+10 | 4681.04 | 11-MAR-19:49 | 21.70 | 15.82 |
April | 0.134321E+11 | 19479.70 | 02-APR-04:01 | 15.82 | 12.70 | 0.526299E+10 | 4681.29 | 01-APR-18:00 | 15.82 | 12.70 |
May | 0.168069E+11 | 19539.63 | 16-MAY-04:01 | 25.00 | 21.55 | 0.545385E+10 | 4681.17 | 20-MAY-18:10 | 28.03 | 21.49 |
June | 0.178514E+11 | 19769.92 | 30-JUN-04:01 | 26.10 | 23.77 | 0.530382E+10 | 4681.44 | 24-JUN-18:10 | 26.10 | 23.77 |
July | 0.196822E+11 | 19380.99 | 28-JUL-04:01 | 26.02 | 24.17 | 0.542407E+10 | 4681.40 | 22-JUL-18:10 | 26.02 | 24.17 |
August | 0.193283E+11 | 19660.30 | 08-AUG-04:01 | 26.10 | 23.70 | 0.548480E+10 | 4681.27 | 19-AUG-18:49 | 29.40 | 24.55 |
September | 0.185819E+11 | 20060.89 | 01-SEP-04:01 | 26.10 | 21.82 | 0.527216E+10 | 4681.36 | 30-SEP-18:00 | 28.90 | 23.70 |
October | 0.175749E+11 | 22006.33 | 17-OCT-04:01 | 24.32 | 19.13 | 0.542512E+10 | 4681.32 | 14-OCT-18:10 | 24.32 | 19.13 |
November | 0.136878E+11 | 19901.64 | 21-NOV-05:01 | 25.60 | 21.37 | 0.521644E+10 | 4681.79 | 18-NOV-19:49 | 25.60 | 21.37 |
December | 0.100068E+11 | 21853.83 | 01-DEC-05:01 | 22.38 | 18.19 | 0.529277E+10 | 4681.84 | 09-DEC-19:40 | 25.00 | 22.52 |
Annual Sum or Average | 0.177027E+12 | 0.636017E+11 | ||||||||
Minimum of Months | 0.918935E+10 | 16448.20 | 15.82 | 12.70 | 0.481541E+10 | 4681.01 | 15.82 | 12.70 | ||
Maximum of Months | 0.196822E+11 | 22261.74 | 26.10 | 24.17 | 0.548480E+10 | 4681.84 | 29.40 | 24.55 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207809E+11 | 40326.59 | 27-JAN-05:01 | 13.62 | 8.51 | 0.784951E+10 | 5135.98 | 18-JAN-11:39 | 13.62 | 8.51 |
February | 0.188843E+11 | 42213.99 | 03-FEB-05:01 | 11.60 | 7.49 | 0.709273E+10 | 5135.97 | 06-FEB-11:39 | 22.40 | 16.91 |
March | 0.210376E+11 | 39170.27 | 17-MAR-04:01 | 14.22 | 9.23 | 0.785849E+10 | 5148.49 | 14-MAR-10:50 | 14.22 | 9.23 |
April | 0.208916E+11 | 25526.43 | 18-APR-03:31 | 19.60 | 15.28 | 0.760744E+10 | 5148.37 | 13-APR-10:00 | 19.60 | 15.28 |
May | 0.223249E+11 | 21915.15 | 09-MAY-03:32 | 24.40 | 19.56 | 0.786480E+10 | 5158.98 | 31-MAY-10:00 | 32.80 | 24.33 |
June | 0.218725E+11 | 19230.09 | 01-JUN-04:01 | 26.02 | 22.60 | 0.762473E+10 | 5175.35 | 06-JUN-10:50 | 30.50 | 25.69 |
July | 0.228365E+11 | 22009.28 | 04-JUL-04:01 | 22.80 | 20.83 | 0.788162E+10 | 5187.63 | 14-JUL-10:50 | 31.52 | 26.32 |
August | 0.227518E+11 | 19748.78 | 14-AUG-04:01 | 22.88 | 22.36 | 0.788518E+10 | 5182.88 | 04-AUG-10:50 | 22.88 | 22.36 |
September | 0.221953E+11 | 20071.59 | 01-SEP-04:01 | 26.10 | 21.82 | 0.762213E+10 | 5176.63 | 06-SEP-10:00 | 30.60 | 26.05 |
October | 0.225329E+11 | 26253.49 | 17-OCT-04:01 | 24.32 | 19.13 | 0.786607E+10 | 5181.69 | 04-OCT-10:50 | 24.32 | 19.13 |
November | 0.211170E+11 | 38944.22 | 13-NOV-05:01 | 12.70 | 7.90 | 0.760597E+10 | 5165.41 | 30-NOV-11:50 | 27.12 | 25.09 |
December | 0.211253E+11 | 38199.13 | 27-DEC-05:01 | 9.32 | 8.48 | 0.785103E+10 | 5138.94 | 07-DEC-11:50 | 9.32 | 8.48 |
Annual Sum or Average | 0.258351E+12 | 0.926097E+11 | ||||||||
Minimum of Months | 0.188843E+11 | 19230.09 | 9.32 | 7.49 | 0.709273E+10 | 5135.97 | 9.32 | 8.48 | ||
Maximum of Months | 0.228365E+11 | 42213.99 | 26.10 | 22.60 | 0.788518E+10 | 5187.63 | 32.80 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 | 19.26 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 | 13.10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 | 13.44 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 | 18.63 | 0.00 | 0.00 | 01-APR-00:10 | 22.57 | 18.63 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 22.05 | 20.01 | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 | 20.01 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 | 24.42 | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 | 24.42 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 26.83 | 23.72 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 23.72 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 28.60 | 25.82 | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 | 25.82 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 27.05 | 24.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 | 24.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 | 23.96 | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 | 23.96 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 22.40 | 21.03 | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 21.03 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 | 21.22 | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 | 21.22 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.65 | 13.10 | 0.00 | 0.00 | 16.65 | 13.10 | ||
Maximum of Months | 0.00 | 0.00 | 28.60 | 25.82 | 0.00 | 0.00 | 28.60 | 25.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11410836.96 | 4151.27 | 25-JAN-08:44 | 10.92 |
February | 46763428.77 | 6375.92 | 04-FEB-07:10 | 5.28 |
March | 35016387.59 | 3730.32 | 16-MAR-06:10 | 6.70 |
April | 2855946.67 | 1757.78 | 12-APR-04:02 | 24.40 |
May | 20302363.66 | 2325.42 | 20-MAY-04:02 | 25.68 |
June | 70326106.12 | 3094.71 | 28-JUN-04:02 | 27.62 |
July | 51527558.72 | 2946.89 | 21-JUL-04:02 | 27.20 |
August | 61866425.87 | 3145.89 | 19-AUG-04:02 | 27.80 |
September | 48001044.67 | 2927.13 | 18-SEP-04:02 | 27.80 |
October | 18135926.66 | 2615.67 | 01-OCT-04:02 | 26.70 |
November | 7865347.40 | 2432.34 | 05-NOV-04:02 | 26.10 |
December | 23712326.40 | 2585.87 | 21-DEC-07:47 | 12.62 |
Annual Sum or Average | 0.397784E+09 | |||
Minimum of Months | 2855946.67 | 1757.78 | 5.28 | |
Maximum of Months | 70326106.12 | 6375.92 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 22.05 |
June | 1280910.82 | 1667.03 | 10-JUN-23:01 | 29.32 |
July | 428797.46 | 1075.65 | 31-JUL-23:01 | 28.68 |
August | 775582.17 | 1247.39 | 02-AUG-23:01 | 28.90 |
September | 984430.61 | 1708.07 | 10-SEP-23:01 | 29.40 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 |
Annual Sum or Average | 3469721.06 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 1280910.82 | 1708.07 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:02 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.399290E+09 | 400.32 | 02-JAN-17:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.345444E+09 | 400.32 | 01-FEB-18:10 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.355463E+09 | 400.32 | 01-MAR-18:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.330384E+09 | 400.32 | 01-APR-18:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.330909E+09 | 400.32 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.319354E+09 | 400.32 | 01-JUN-18:30 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.318231E+09 | 400.32 | 01-JUL-19:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.338973E+09 | 400.32 | 01-AUG-18:00 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.340859E+09 | 400.32 | 01-SEP-18:40 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.369951E+09 | 400.32 | 02-OCT-17:00 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.381030E+09 | 400.32 | 01-NOV-17:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.408396E+09 | 400.32 | 01-DEC-17:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.423828E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.318231E+09 | 400.32 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.408396E+09 | 400.32 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138574E+10 | 811.23 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.125514E+10 | 811.23 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.140781E+10 | 811.23 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.134648E+10 | 811.23 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.139678E+10 | 811.23 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.136076E+10 | 811.23 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.138266E+10 | 811.23 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.140781E+10 | 811.23 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.134680E+10 | 811.23 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.138558E+10 | 811.23 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.134145E+10 | 811.23 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.138282E+10 | 811.23 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.163998E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.125514E+10 | 811.23 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.140781E+10 | 811.23 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.399290E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330735E+09 | 0.376277E+10 |
February | 0.852256E+10 | 0.345444E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526890E+09 | 0.219778E+10 |
March | 0.954557E+10 | 0.355463E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628827E+09 | 0.211174E+10 |
April | 0.915225E+10 | 0.330384E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165446E+10 | 0.586626E+09 |
May | 0.947560E+10 | 0.330909E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359814E+10 | 63502404.83 |
June | 0.922788E+10 | 0.319354E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454365E+10 | 6281400.64 |
July | 0.939996E+10 | 0.318231E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546521E+10 | 29813031.68 |
August | 0.954557E+10 | 0.338973E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503859E+10 | 35051493.89 |
September | 0.915225E+10 | 0.340859E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451487E+10 | 17543032.58 |
October | 0.940563E+10 | 0.369951E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340501E+10 | 62050845.31 |
November | 0.909363E+10 | 0.381030E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171006E+10 | 0.102537E+10 |
December | 0.939996E+10 | 0.408396E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480794E+09 | 0.326027E+10 |
Annual Sum or Average | 0.111326E+12 | 0.423828E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318972E+11 | 0.131588E+11 |
Minimum of Months | 0.852256E+10 | 0.318231E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330735E+09 | 6281400.64 |
Maximum of Months | 0.954557E+10 | 0.408396E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546521E+10 | 0.376277E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.138574E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 84279.83 | 19819243.87 |
February | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 190096.29 | 27214949.82 |
March | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 274335.41 | 27958906.86 |
April | 0.655836E+09 | 0.134648E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1000555.02 | 14067754.19 |
May | 0.679007E+09 | 0.139678E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3474167.71 | 9230868.43 |
June | 0.661256E+09 | 0.136076E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3511082.78 | 3736526.80 |
July | 0.673587E+09 | 0.138266E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3467904.38 | 3184555.24 |
August | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3737266.36 | 2920037.58 |
September | 0.655836E+09 | 0.134680E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 3515565.65 | 3606025.82 |
October | 0.673993E+09 | 0.138558E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2239172.37 | 5818681.75 |
November | 0.651635E+09 | 0.134145E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 642857.57 | 15939598.22 |
December | 0.673587E+09 | 0.138282E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 146477.32 | 20759869.08 |
Annual Sum or Average | 0.797748E+10 | 0.163998E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 22283760.69 | 0.154257E+09 |
Minimum of Months | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 84279.83 | 2920037.58 |
Maximum of Months | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 3737266.36 | 27958906.86 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403813E+09 | 0.101907E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296666E+09 | 0.106830E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298738E+09 | 0.147758E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293208E+09 | 0.166443E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266055E+09 | 0.167468E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267421E+09 | 0.158951E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306355E+09 | 0.179930E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325233E+09 | 0.145421E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289624E+09 | 0.140101E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385476E+09 | 0.117749E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338328E+09 | 0.978696E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318389E+09 | 0.970241E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378931E+10 | 0.162745E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266055E+09 | 0.970241E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403813E+09 | 0.179930E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 400.32 | 02-JAN-17:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3973.57 | 02-JAN-13:55 | 8392.84 | 24-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 400.32 | 01-FEB-18:10 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3497.33 | 02-FEB-14:00 | 10327.55 | 04-FEB-07:10 |
March | 9454.80 | 04-MAR-19:10 | 400.32 | 01-MAR-18:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4331.08 | 13-MAR-17:03 | 7705.52 | 16-MAR-06:10 |
April | 9454.80 | 01-APR-18:10 | 400.32 | 01-APR-18:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6230.04 | 17-APR-17:08 | 4280.15 | 02-APR-06:10 |
May | 9454.80 | 06-MAY-18:10 | 400.32 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8196.08 | 22-MAY-12:00 | 1793.54 | 07-MAY-06:10 |
June | 9454.80 | 03-JUN-18:10 | 400.32 | 01-JUN-18:30 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6350.73 | 09-JUN-12:00 | 441.95 | 05-JUN-22:10 |
July | 9454.80 | 01-JUL-18:10 | 400.32 | 01-JUL-19:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8859.49 | 29-JUL-18:02 | 988.46 | 14-JUL-20:00 |
August | 9454.80 | 05-AUG-18:10 | 400.32 | 01-AUG-18:00 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8227.57 | 23-AUG-12:00 | 1536.59 | 28-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 400.32 | 01-SEP-18:40 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6846.83 | 13-SEP-12:00 | 757.97 | 05-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 400.32 | 02-OCT-17:00 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6827.21 | 03-OCT-12:00 | 1334.61 | 28-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 400.32 | 01-NOV-17:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4438.65 | 17-NOV-13:00 | 5748.40 | 12-NOV-20:55 |
December | 9454.80 | 02-DEC-19:10 | 400.32 | 01-DEC-17:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3106.70 | 08-DEC-14:00 | 9445.47 | 20-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3106.70 | 441.95 | |||||
Maximum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 8859.49 | 10327.55 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 811.23 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 3.57 | 07-JAN-13:00 | 96.69 | 24-JAN-02:30 |
February | 677.52 | 04-FEB-19:10 | 811.23 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 4.31 | 02-FEB-14:00 | 137.41 | 04-FEB-04:40 |
March | 677.52 | 04-MAR-19:10 | 811.23 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 5.45 | 13-MAR-16:53 | 136.07 | 16-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 811.23 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 7.79 | 15-APR-16:53 | 61.16 | 23-APR-02:10 |
May | 677.52 | 06-MAY-18:10 | 811.23 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 12.28 | 22-MAY-14:41 | 49.03 | 08-MAY-00:50 |
June | 677.52 | 03-JUN-18:10 | 811.23 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 7.19 | 16-JUN-13:00 | 43.59 | 18-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 811.23 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 8.48 | 27-JUL-15:53 | 32.78 | 04-JUL-03:20 |
August | 677.52 | 05-AUG-18:10 | 811.23 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 6.70 | 23-AUG-13:00 | 53.61 | 14-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 811.23 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 7.38 | 19-SEP-15:00 | 31.37 | 20-SEP-00:07 |
October | 677.52 | 07-OCT-18:10 | 811.23 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 6.95 | 03-OCT-12:10 | 45.74 | 17-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 811.23 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 3.35 | 17-NOV-14:53 | 109.21 | 12-NOV-04:10 |
December | 677.52 | 02-DEC-19:10 | 811.23 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 4.81 | 10-DEC-15:00 | 131.59 | 15-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 3.35 | 31.37 | ||||||
Maximum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 12.28 | 137.41 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.28 | 27-JAN-03:30 | 2226.78 | 31-JAN-13:30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.28 | 28-FEB-07:15 | 2153.88 | 25-FEB-13:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.17 | 02-MAR-04:00 | 2543.01 | 16-MAR-13:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.94 | 05-APR-05:10 | 2535.05 | 10-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.40 | 06-MAY-05:20 | 2553.56 | 06-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.10 | 10-JUN-03:00 | 2565.16 | 09-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.66 | 07-JUL-06:05 | 2554.08 | 07-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.76 | 31-AUG-03:51 | 2364.77 | 07-AUG-13:02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.57 | 12-SEP-02:20 | 2386.50 | 17-SEP-12:40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.72 | 22-OCT-04:00 | 2358.54 | 06-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.42 | 07-NOV-06:40 | 1906.73 | 10-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.85 | 13-DEC-06:00 | 1893.04 | 04-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.40 | 1893.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.28 | 2565.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19192.89 | 05-JAN-05:01 | 4202.13 | 711.69 | 13010.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 |
February | 16448.20 | 20-FEB-05:01 | 0.00 | 467.04 | 11340.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
March | 22261.74 | 03-MAR-05:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.71 |
April | 19479.70 | 02-APR-04:01 | 0.00 | 533.77 | 12960.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
May | 19539.63 | 16-MAY-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 0.00 |
June | 19769.92 | 30-JUN-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
July | 19380.99 | 28-JUL-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
August | 19660.30 | 08-AUG-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
September | 20060.89 | 01-SEP-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 |
October | 22006.33 | 17-OCT-04:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
November | 19901.64 | 21-NOV-05:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 0.00 |
December | 21853.83 | 01-DEC-05:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16448.20 | 0.00 | 467.04 | 11340.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22261.74 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 9.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40326.59 | 27-JAN-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
February | 42213.99 | 03-FEB-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 |
March | 39170.27 | 17-MAR-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
April | 25526.43 | 18-APR-03:31 | 0.00 | 946.45 | 11807.45 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 |
May | 21915.15 | 09-MAY-03:32 | 0.00 | 811.24 | 10120.67 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 |
June | 19230.09 | 01-JUN-04:01 | 301.12 | 1442.23 | 25850.46 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
July | 22009.28 | 04-JUL-04:01 | 0.00 | 1081.65 | 25769.18 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 |
August | 19748.78 | 14-AUG-04:01 | 301.12 | 1442.23 | 25850.46 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
September | 20071.59 | 01-SEP-04:01 | 338.76 | 1622.51 | 29081.76 | 29786.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
October | 26253.49 | 17-OCT-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
November | 38944.22 | 13-NOV-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 |
December | 38199.13 | 27-DEC-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 19230.09 | 0.00 | 811.24 | 10120.67 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | |
Maximum of Months | 42213.99 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 26.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.32 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.61 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.83 | 0.00 |
April | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.88 | 0.00 |
May | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.25 | 0.00 |
June | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.62 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.86 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.49 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.17 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
November | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.40 | 0.00 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.61 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.401175E+11 | 31913.27 | 07-JAN-11:20 | 0.553164E+11 | 46277.39 | 17-JAN-13:20 |
February | 0.381833E+11 | 33209.81 | 11-FEB-11:20 | 0.500186E+11 | 46226.21 | 02-FEB-13:20 |
March | 0.436567E+11 | 33426.33 | 14-MAR-10:20 | 0.548853E+11 | 45923.73 | 03-MAR-13:39 |
April | 0.459080E+11 | 33410.48 | 13-APR-10:20 | 0.522154E+11 | 45241.70 | 06-APR-12:50 |
May | 0.540884E+11 | 35706.26 | 31-MAY-10:20 | 0.534292E+11 | 44559.48 | 03-MAY-12:30 |
June | 0.571947E+11 | 35909.90 | 06-JUN-10:20 | 0.513051E+11 | 43769.37 | 04-JUN-12:50 |
July | 0.605367E+11 | 37444.95 | 25-JUL-10:20 | 0.528104E+11 | 43261.41 | 12-JUL-12:20 |
August | 0.606017E+11 | 37246.32 | 23-AUG-10:20 | 0.529547E+11 | 43664.41 | 28-AUG-12:00 |
September | 0.575947E+11 | 36166.66 | 21-SEP-10:20 | 0.515833E+11 | 44378.76 | 28-SEP-12:50 |
October | 0.555986E+11 | 36036.76 | 03-OCT-11:20 | 0.538336E+11 | 45219.24 | 31-OCT-12:50 |
November | 0.478987E+11 | 34441.31 | 10-NOV-11:20 | 0.526953E+11 | 45807.61 | 28-NOV-13:20 |
December | 0.425460E+11 | 32716.25 | 24-DEC-11:20 | 0.552541E+11 | 46171.27 | 26-DEC-13:20 |
Annual Sum or Average | 0.603925E+12 | 0.636301E+12 | ||||
Minimum of Months | 0.381833E+11 | 31913.27 | 0.500186E+11 | 43261.41 | ||
Maximum of Months | 0.606017E+11 | 37444.95 | 0.553164E+11 | 46277.39 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.178503E+10 | 0.152779E+10 | 0.214106E+11 | 0.00 | 0.444720E+10 | 0.79 | 0.00 | 0.755785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160058E+10 | 0.129873E+10 | 0.193386E+11 | 0.00 | 0.405065E+10 | 0.72 | 0.00 | 0.882701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176327E+10 | 0.132813E+10 | 0.214107E+11 | 0.00 | 0.456669E+10 | 0.80 | 0.00 | 0.111785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167686E+10 | 0.117798E+10 | 0.207199E+11 | 0.00 | 0.456798E+10 | 0.77 | 0.00 | 0.144459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172769E+10 | 0.112042E+10 | 0.214107E+11 | 0.00 | 0.526219E+10 | 0.80 | 0.00 | 0.211154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168011E+10 | 0.104032E+10 | 0.207201E+11 | 0.00 | 0.566380E+10 | 0.77 | 0.00 | 0.247237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170089E+10 | 0.108903E+10 | 0.214105E+11 | 0.00 | 0.602343E+10 | 0.79 | 0.00 | 0.268310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174678E+10 | 0.117436E+10 | 0.214107E+11 | 0.00 | 0.602009E+10 | 0.80 | 0.00 | 0.267610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168766E+10 | 0.123997E+10 | 0.207199E+11 | 0.00 | 0.569010E+10 | 0.77 | 0.00 | 0.248925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175553E+10 | 0.139254E+10 | 0.214106E+11 | 0.00 | 0.540977E+10 | 0.79 | 0.00 | 0.221725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172248E+10 | 0.144687E+10 | 0.207200E+11 | 0.00 | 0.480775E+10 | 0.77 | 0.00 | 0.158813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179122E+10 | 0.154872E+10 | 0.214105E+11 | 0.00 | 0.458237E+10 | 0.79 | 0.00 | 0.981123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206381E+11 | 0.153849E+11 | 0.252093E+12 | 0.00 | 0.610920E+11 | 9.37 | 0.00 | 0.214198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160058E+10 | 0.104032E+10 | 0.193386E+11 | 0.00 | 0.405065E+10 | 0.72 | 0.00 | 0.755785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179122E+10 | 0.154872E+10 | 0.214107E+11 | 0.00 | 0.602343E+10 | 0.80 | 0.00 | 0.268310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.357973E+09 | 0.00 | 0.144327E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.479292E+09 | 0.00 | 0.129354E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.378380E+09 | 0.00 | 0.139811E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.129970E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.129035E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.120866E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.122847E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.124290E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.00 | 0.00 | 0.123648E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.133079E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 64319428.66 | 0.00 | 0.134125E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.471608E+09 | 0.00 | 0.142567E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.175157E+10 | 0.00 | 0.157392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.120866E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.479292E+09 | 0.00 | 0.144327E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1211.55 | 02-JAN-17:40 | 1341.77 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 2981.41 | 02-JAN-13:00 | 0.00 | 07-JAN-15:39 | 0.00 | 01-JAN-00:10 |
February | 1211.55 | 01-FEB-18:10 | 1341.77 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 2771.06 | 11-FEB-13:00 | 0.00 | 24-FEB-08:00 | 0.00 | 01-FEB-00:10 |
March | 1211.55 | 01-MAR-18:19 | 1341.77 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2766.57 | 13-MAR-12:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1211.55 | 01-APR-18:40 | 1341.77 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 3071.07 | 13-APR-11:00 | 0.00 | 01-APR-09:39 | 0.00 | 01-APR-00:10 |
May | 1211.55 | 01-MAY-18:49 | 1341.77 | 01-MAY-05:10 | 13637.09 | 01-MAY-10:09 | 0.00 | 3282.96 | 31-MAY-12:00 | 0.00 | 10-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 1211.55 | 01-JUN-18:30 | 1341.77 | 01-JUN-05:10 | 13637.09 | 01-JUN-10:09 | 0.00 | 3324.31 | 08-JUN-17:10 | 0.00 | 13-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 1211.55 | 01-JUL-19:19 | 1341.77 | 01-JUL-05:10 | 13637.09 | 01-JUL-10:09 | 0.00 | 3529.39 | 14-JUL-11:30 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1211.55 | 01-AUG-18:00 | 1341.77 | 01-AUG-05:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 3483.22 | 22-AUG-12:00 | 0.00 | 05-AUG-17:49 | 0.00 | 01-AUG-00:10 |
September | 1211.55 | 01-SEP-18:40 | 1341.77 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 3440.54 | 22-SEP-11:00 | 0.00 | 02-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 1211.55 | 02-OCT-17:00 | 1341.77 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 3414.85 | 03-OCT-11:00 | 0.00 | 09-OCT-12:20 | 0.00 | 01-OCT-00:10 |
November | 1211.55 | 01-NOV-17:40 | 1341.77 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 3017.99 | 03-NOV-12:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1211.55 | 01-DEC-17:30 | 1341.77 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 2702.97 | 08-DEC-13:00 | 0.00 | 25-DEC-09:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 2702.97 | 0.00 | 0.00 | ||||||
Maximum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 3529.39 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 14791.18 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13838.77 | 11-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13762.96 | 13-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15380.92 | 13-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16799.32 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16749.90 | 08-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18358.09 | 27-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18068.53 | 22-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17443.39 | 22-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17431.00 | 03-OCT-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15023.38 | 03-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13436.45 | 08-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13436.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18358.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 31913.27 | 07-JAN-11:20 | 806.50 | 13637.09 | 0.00 | 0.00 | 2403.58 | 0.00 | 0.00 | 11144.39 | 0.00 |
February | 33209.81 | 11-FEB-11:20 | 806.50 | 13637.09 | 0.00 | 0.00 | 2562.49 | 0.00 | 0.00 | 12282.01 | 0.00 |
March | 33426.33 | 14-MAR-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2583.95 | 0.00 | 0.00 | 12366.84 | 0.00 |
April | 33410.48 | 13-APR-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2541.72 | 0.00 | 0.00 | 12393.22 | 0.00 |
May | 35706.26 | 31-MAY-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2810.86 | 0.00 | 0.00 | 14419.86 | 0.00 |
June | 35909.90 | 06-JUN-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2883.98 | 0.00 | 0.00 | 14550.39 | 0.00 |
July | 37444.95 | 25-JUL-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 3051.26 | 0.00 | 0.00 | 15918.16 | 0.00 |
August | 37246.32 | 23-AUG-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 3056.29 | 0.00 | 0.00 | 15714.50 | 0.00 |
September | 36166.66 | 21-SEP-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2914.15 | 0.00 | 0.00 | 14776.97 | 0.00 |
October | 36036.76 | 03-OCT-11:20 | 907.31 | 12737.35 | 0.00 | 0.00 | 3393.18 | 0.00 | 0.00 | 17239.50 | 0.00 |
November | 34441.31 | 10-NOV-11:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2667.02 | 0.00 | 0.00 | 13298.75 | 0.00 |
December | 32716.25 | 24-DEC-11:20 | 705.69 | 13637.09 | 0.00 | 0.00 | 2597.38 | 0.00 | 0.00 | 11863.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 31913.27 | 705.69 | 12737.35 | 0.00 | 0.00 | 2403.58 | 0.00 | 0.00 | 11144.39 | 0.00 | |
Maximum of Months | 37444.95 | 907.31 | 13637.09 | 0.00 | 0.00 | 3393.18 | 0.00 | 0.00 | 17239.50 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 8535.09 | 25-JAN-07:10 | 0.00 | 23294.24 | 17-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 19556.98 | 04-FEB-07:10 | 0.00 | 23243.06 | 02-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 12409.54 | 16-MAR-06:10 | 0.00 | 22940.58 | 03-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22258.55 | 06-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 21576.33 | 03-MAY-12:30 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20786.22 | 04-JUN-12:50 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20278.26 | 12-JUL-12:20 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 20681.26 | 28-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 21395.61 | 28-SEP-12:50 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 22236.09 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 6101.19 | 27-NOV-07:10 | 0.00 | 22824.46 | 28-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 10164.08 | 15-DEC-07:10 | 0.00 | 23188.12 | 26-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 20278.26 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 19556.98 | 0.00 | 23294.24 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.23 | 0.00 | 26.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.24 | 0.00 | 26.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.24 | 0.00 | 26.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.30 | 0.00 | 26.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.35 | 0.00 | 26.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.25 | 0.00 | 26.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.22 | 0.00 | 26.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
Annual Sum or Average | 0.00 | 0.00 | 18.33 | 26.27 | 0.00 | 26.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.35 | 0.00 | 26.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 30.16 | 0.50 | 30.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 30.03 | 1.50 | 29.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 30.28 | 0.83 | 30.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 30.18 | 3.00 | 29.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 28.77 | 35.17 | 28.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 200.67 | 27.79 | 169.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 297.50 | 27.79 | 264.83 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 277.17 | 27.80 | 245.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 210.33 | 27.79 | 178.83 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 118.17 | 28.15 | 87.17 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 28.58 | 33.83 | 28.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 30.01 | 2.50 | 29.71 |
Annual Sum or Average | 0.00 | 0.00 | 1344.67 | 28.11 | 1022.83 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.79 | 0.50 | 27.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 297.50 | 30.28 | 264.83 | 30.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 319.83 | 22.99 | 434.17 | 23.53 | 179.17 | 23.62 |
February | 264.83 | 23.36 | 444.83 | 23.72 | 186.00 | 23.78 |
March | 311.50 | 23.48 | 502.00 | 23.79 | 231.67 | 23.86 |
April | 256.50 | 24.06 | 579.00 | 24.04 | 249.00 | 24.06 |
May | 454.83 | 24.13 | 611.00 | 24.10 | 454.83 | 24.11 |
June | 576.17 | 24.12 | 592.00 | 24.12 | 576.17 | 24.12 |
July | 589.67 | 24.12 | 609.00 | 24.11 | 589.67 | 24.11 |
August | 602.33 | 24.12 | 612.00 | 24.12 | 602.33 | 24.12 |
September | 575.67 | 24.11 | 590.00 | 24.11 | 575.67 | 24.11 |
October | 479.33 | 24.12 | 610.00 | 24.10 | 479.33 | 24.11 |
November | 403.17 | 23.92 | 551.83 | 23.98 | 375.33 | 24.01 |
December | 367.50 | 23.35 | 489.50 | 23.68 | 271.67 | 23.75 |
Annual Sum or Average | 5201.33 | 23.90 | 6625.33 | 23.98 | 4770.83 | 24.02 |
Minimum of Months | 256.50 | 22.99 | 434.17 | 23.53 | 179.17 | 23.62 |
Maximum of Months | 602.33 | 24.13 | 612.00 | 24.12 | 602.33 | 24.12 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 26.01 | 590.50 | 25.87 | 487.17 | 25.95 |
February | 485.67 | 26.01 | 529.83 | 25.98 | 472.33 | 26.04 |
March | 548.83 | 26.11 | 588.67 | 26.07 | 539.17 | 26.11 |
April | 582.33 | 26.25 | 590.00 | 26.24 | 582.33 | 26.25 |
May | 611.00 | 26.38 | 611.00 | 26.38 | 611.00 | 26.38 |
June | 592.00 | 26.72 | 592.00 | 26.72 | 592.00 | 26.72 |
July | 609.00 | 26.95 | 609.00 | 26.95 | 609.00 | 26.95 |
August | 612.00 | 26.90 | 612.00 | 26.90 | 612.00 | 26.90 |
September | 590.00 | 26.73 | 590.00 | 26.73 | 590.00 | 26.73 |
October | 610.00 | 26.49 | 610.00 | 26.49 | 610.00 | 26.49 |
November | 567.00 | 26.29 | 583.83 | 26.27 | 564.50 | 26.28 |
December | 545.00 | 25.98 | 582.33 | 25.95 | 528.00 | 26.01 |
Annual Sum or Average | 6851.33 | 26.42 | 7089.17 | 26.39 | 6797.50 | 26.42 |
Minimum of Months | 485.67 | 25.98 | 529.83 | 25.87 | 472.33 | 25.95 |
Maximum of Months | 612.00 | 26.95 | 612.00 | 26.95 | 612.00 | 26.95 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.36936 | 56.69073 | 0.48162 | 11.77970 |
February | 551.00000 | 23.60302 | 56.44796 | 0.54001 | 12.71532 |
March | 612.00000 | 23.66995 | 58.72119 | 0.57168 | 13.51618 |
April | 590.00000 | 24.00514 | 62.17684 | 0.68705 | 15.23163 |
May | 611.00000 | 24.07548 | 69.11303 | -0.0511 | 5.44082 |
June | 592.00000 | 24.11557 | 73.10125 | 0.00649 | 5.59904 |
July | 609.00000 | 24.10873 | 72.67446 | 0.02568 | 5.56704 |
August | 612.00000 | 24.11621 | 73.51046 | 0.03253 | 5.64065 |
September | 590.00000 | 24.10711 | 72.41995 | 0.03472 | 5.63707 |
October | 610.00000 | 24.08281 | 69.47835 | 0.80055 | 18.76072 |
November | 591.00000 | 23.90607 | 65.75489 | 0.70714 | 16.49185 |
December | 609.00000 | 23.52420 | 61.41744 | 0.55784 | 13.37457 |
Annual Sum or Average | 7187.00000 | 23.89118 | 66.01238 | 0.36471 | 10.79636 |
Minimum of Months | 551.00000 | 23.36936 | 56.44796 | -0.0511 | 5.44082 |
Maximum of Months | 612.00000 | 24.11621 | 73.51046 | 0.80055 | 18.76072 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 25.62754 | 52.47597 | 1.17974 | 36.03831 |
February | 551.00000 | 25.78097 | 52.38235 | 1.22104 | 38.05886 |
March | 612.00000 | 25.86542 | 53.93759 | 1.25713 | 39.65333 |
April | 590.00000 | 26.23013 | 56.99393 | 1.38324 | 44.76884 |
May | 611.00000 | 26.38279 | 62.45217 | 0.95572 | 24.84933 |
June | 592.00000 | 26.72068 | 65.78334 | 1.10832 | 31.84996 |
July | 609.00000 | 26.94981 | 66.08878 | 1.20453 | 36.58442 |
August | 612.00000 | 26.90148 | 66.28684 | 1.18149 | 35.46282 |
September | 590.00000 | 26.72827 | 65.37856 | 1.12066 | 32.42559 |
October | 610.00000 | 26.49040 | 62.73425 | 1.51606 | 51.75006 |
November | 591.00000 | 26.19245 | 59.10211 | 1.39646 | 45.92092 |
December | 609.00000 | 25.74003 | 55.88890 | 1.24176 | 39.04116 |
Annual Sum or Average | 7187.00000 | 26.30338 | 60.00192 | 1.23030 | 38.02289 |
Minimum of Months | 551.00000 | 25.62754 | 52.38235 | 0.95572 | 24.84933 |
Maximum of Months | 612.00000 | 26.94981 | 66.28684 | 1.51606 | 51.75006 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.126550E+11 | 0.336838E+10 | 381.72 | 0.741620E+10 | 0.523878E+10 | 0.00 | 1.00 | 02-JAN-05:01 | 0.00 | 01-JAN-00:10 | 34763.22 | 02-JAN-14:00 | 18832.44 | 05-JAN-05:01 | 17368.99 | 02-JAN-14:00 | 7976.17 | 05-JAN-05:01 | 0.00 | 01-JAN-00:10 |
February | 0.154927E+11 | 0.411531E+10 | 414.86 | 0.957699E+10 | 0.591572E+10 | 0.00 | 1.00 | 02-FEB-12:20 | 0.00 | 01-FEB-00:10 | 29532.37 | 11-FEB-14:00 | 15736.55 | 11-FEB-14:00 | 13795.82 | 11-FEB-14:00 | 6807.10 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.198078E+11 | 0.517091E+10 | 489.08 | 0.113410E+11 | 0.846679E+10 | 0.00 | 1.00 | 03-MAR-05:01 | 0.00 | 01-MAR-00:10 | 37015.93 | 03-MAR-05:01 | 24651.07 | 03-MAR-05:01 | 15749.10 | 07-MAR-05:02 | 8796.96 | 03-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.267555E+11 | 0.687654E+10 | 563.49 | 0.158384E+11 | 0.109171E+11 | 0.00 | 1.00 | 01-APR-17:02 | 0.00 | 01-APR-00:02 | 46028.74 | 13-APR-04:01 | 21489.70 | 13-APR-04:01 | 24539.03 | 13-APR-04:01 | 10429.34 | 13-APR-04:01 | 0.00 | 01-APR-00:02 |
May | 0.407061E+11 | 0.995910E+10 | 605.92 | 0.218480E+11 | 0.188581E+11 | 0.00 | 1.00 | 01-MAY-11:03 | 0.00 | 01-MAY-00:02 | 54698.93 | 30-MAY-04:01 | 24187.11 | 16-MAY-04:01 | 31665.85 | 30-MAY-04:01 | 12392.05 | 30-MAY-04:01 | 0.00 | 01-MAY-00:02 |
June | 0.486431E+11 | 0.115566E+11 | 589.87 | 0.240312E+11 | 0.246118E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:02 | 54698.93 | 06-JUN-04:01 | 25535.50 | 30-JUN-04:01 | 31847.82 | 26-JUN-04:01 | 12392.05 | 06-JUN-04:01 | 0.00 | 01-JUN-00:02 |
July | 0.534723E+11 | 0.127783E+11 | 609.63 | 0.269330E+11 | 0.265392E+11 | 0.00 | 1.00 | 01-JUL-03:02 | 0.00 | 01-JUL-00:02 | 54698.93 | 11-JUL-04:01 | 25677.96 | 28-JUL-17:10 | 31955.79 | 26-JUL-04:01 | 12392.05 | 11-JUL-04:01 | 0.00 | 01-JUL-00:02 |
August | 0.532405E+11 | 0.126413E+11 | 610.55 | 0.262016E+11 | 0.270389E+11 | 0.00 | 1.00 | 01-AUG-03:02 | 0.00 | 01-AUG-00:02 | 54698.93 | 04-AUG-04:01 | 25697.07 | 11-AUG-04:01 | 31553.83 | 05-AUG-04:01 | 12392.05 | 01-AUG-04:01 | 0.00 | 01-AUG-00:02 |
September | 0.492962E+11 | 0.117492E+11 | 590.19 | 0.247266E+11 | 0.245695E+11 | 0.00 | 1.00 | 01-SEP-03:02 | 0.00 | 01-SEP-00:02 | 54698.93 | 19-SEP-04:01 | 25474.26 | 01-SEP-04:01 | 31938.51 | 23-SEP-03:02 | 12392.05 | 19-SEP-04:01 | 0.00 | 01-SEP-00:02 |
October | 0.433035E+11 | 0.104794E+11 | 608.07 | 0.225345E+11 | 0.207689E+11 | 0.00 | 1.00 | 01-OCT-03:02 | 0.00 | 01-OCT-00:02 | 54698.93 | 03-OCT-04:01 | 26104.95 | 17-OCT-04:01 | 32997.56 | 04-OCT-04:01 | 12392.05 | 03-OCT-04:01 | 0.00 | 01-OCT-00:02 |
November | 0.299758E+11 | 0.740334E+10 | 533.21 | 0.156729E+11 | 0.143030E+11 | 0.00 | 1.00 | 02-NOV-11:05 | 0.00 | 01-NOV-00:02 | 52980.18 | 10-NOV-05:01 | 24633.59 | 21-NOV-05:01 | 29991.41 | 05-NOV-04:01 | 12002.97 | 10-NOV-05:01 | 0.00 | 01-NOV-00:02 |
December | 0.167953E+11 | 0.434480E+10 | 438.68 | 0.907666E+10 | 0.771867E+10 | 0.00 | 1.00 | 01-DEC-05:01 | 0.00 | 01-DEC-00:02 | 46152.60 | 09-DEC-05:01 | 24891.68 | 01-DEC-05:01 | 24282.14 | 09-DEC-05:01 | 10457.38 | 09-DEC-05:01 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.410144E+12 | 0.100443E+12 | 6435.26 | 0.215197E+12 | 0.194947E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.126550E+11 | 0.336838E+10 | 381.72 | 0.741620E+10 | 0.523878E+10 | 0.00 | 1.00 | 0.00 | 29532.37 | 15736.55 | 13795.82 | 6807.10 | 0.00 | |||||||
Maximum of Months | 0.534723E+11 | 0.127783E+11 | 610.55 | 0.269330E+11 | 0.270389E+11 | 0.00 | 1.00 | 0.00 | 54698.93 | 26104.95 | 32997.56 | 12392.05 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.173844E+11 | 0.418947E+10 | 486.66 | 0.957184E+10 | 0.781259E+10 | 0.00 | 1.00 | 01-JAN-05:03 | 0.00 | 01-JAN-00:10 | 31452.28 | 02-JAN-13:55 | 22500.11 | 27-JAN-05:01 | 18627.03 | 03-JAN-04:32 | 7000.61 | 02-JAN-13:45 | 0.00 | 01-JAN-00:10 |
February | 0.196971E+11 | 0.471169E+10 | 486.93 | 0.114584E+11 | 0.823862E+10 | 0.00 | 1.00 | 01-FEB-04:23 | 0.00 | 01-FEB-00:10 | 31452.28 | 11-FEB-11:47 | 22016.99 | 24-FEB-05:01 | 18004.30 | 11-FEB-17:22 | 7031.67 | 11-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.254873E+11 | 0.600764E+10 | 579.51 | 0.137519E+11 | 0.117354E+11 | 0.00 | 1.00 | 01-MAR-05:01 | 0.00 | 01-MAR-00:10 | 31452.28 | 13-MAR-12:13 | 22036.93 | 17-MAR-04:01 | 19913.57 | 14-MAR-04:03 | 7000.61 | 04-MAR-11:32 | 0.00 | 01-MAR-00:10 |
April | 0.324445E+11 | 0.756933E+10 | 635.77 | 0.186615E+11 | 0.137831E+11 | 0.00 | 1.00 | 01-APR-02:12 | 0.00 | 01-APR-00:02 | 31452.28 | 01-APR-15:43 | 20759.77 | 14-APR-13:00 | 19484.35 | 25-APR-03:32 | 7132.49 | 14-APR-13:03 | 0.00 | 01-APR-00:02 |
May | 0.492664E+11 | 0.111563E+11 | 674.82 | 0.256686E+11 | 0.235978E+11 | 0.00 | 1.00 | 01-MAY-03:02 | 0.00 | 01-MAY-00:02 | 31452.28 | 12-MAY-10:27 | 25117.58 | 22-MAY-13:00 | 21497.36 | 29-MAY-02:62 | 7523.41 | 22-MAY-13:00 | 0.00 | 01-MAY-00:02 |
June | 0.584297E+11 | 0.131671E+11 | 669.55 | 0.277558E+11 | 0.306738E+11 | 0.00 | 1.00 | 01-JUN-02:62 | 0.00 | 01-JUN-00:02 | 31452.28 | 06-JUN-04:13 | 21157.30 | 11-JUN-12:55 | 21546.87 | 06-JUN-19:55 | 7284.21 | 11-JUN-12:55 | 0.00 | 01-JUN-00:02 |
July | 0.617083E+11 | 0.140526E+11 | 689.28 | 0.303602E+11 | 0.313481E+11 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:02 | 31452.28 | 12-JUL-18:42 | 24620.11 | 29-JUL-15:53 | 21380.11 | 03-JUL-03:22 | 7667.93 | 29-JUL-15:53 | 0.00 | 01-JUL-00:02 |
August | 0.623772E+11 | 0.141197E+11 | 693.80 | 0.294768E+11 | 0.329003E+11 | 0.00 | 1.00 | 01-AUG-00:06 | 0.00 | 01-AUG-00:02 | 31452.28 | 12-AUG-13:40 | 22493.22 | 23-AUG-12:00 | 21594.95 | 28-AUG-02:62 | 7466.06 | 23-AUG-13:00 | 0.00 | 01-AUG-00:02 |
September | 0.581260E+11 | 0.131432E+11 | 666.38 | 0.279246E+11 | 0.302014E+11 | 0.00 | 1.00 | 01-SEP-02:62 | 0.00 | 01-SEP-00:02 | 31452.28 | 28-SEP-04:02 | 22158.73 | 08-SEP-15:53 | 21709.24 | 27-SEP-19:15 | 7284.21 | 08-SEP-15:15 | 0.00 | 01-SEP-00:02 |
October | 0.517202E+11 | 0.116931E+11 | 676.27 | 0.254212E+11 | 0.262990E+11 | 0.00 | 1.00 | 01-OCT-01:23 | 0.00 | 01-OCT-00:02 | 31452.28 | 01-OCT-15:11 | 22055.48 | 23-OCT-11:10 | 22426.03 | 04-OCT-04:06 | 7284.21 | 09-OCT-10:53 | 0.00 | 01-OCT-00:02 |
November | 0.370611E+11 | 0.847796E+10 | 606.82 | 0.179686E+11 | 0.190926E+11 | 0.00 | 1.00 | 01-NOV-02:12 | 0.00 | 01-NOV-00:02 | 31452.28 | 03-NOV-18:03 | 21258.52 | 13-NOV-05:01 | 21289.07 | 04-NOV-03:22 | 7031.67 | 03-NOV-13:00 | 0.00 | 01-NOV-00:02 |
December | 0.231853E+11 | 0.546643E+10 | 532.30 | 0.114729E+11 | 0.117124E+11 | 0.00 | 1.00 | 01-DEC-03:01 | 0.00 | 01-DEC-00:02 | 31452.28 | 07-DEC-11:40 | 17981.06 | 10-DEC-13:55 | 19739.01 | 23-DEC-11:32 | 7000.61 | 07-DEC-11:35 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.496888E+12 | 0.113755E+12 | 7398.08 | 0.249492E+12 | 0.247395E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.173844E+11 | 0.418947E+10 | 486.66 | 0.957184E+10 | 0.781259E+10 | 0.00 | 1.00 | 0.00 | 31452.28 | 17981.06 | 18004.30 | 7000.61 | 0.00 | |||||||
Maximum of Months | 0.623772E+11 | 0.141197E+11 | 693.80 | 0.303602E+11 | 0.329003E+11 | 0.00 | 1.00 | 0.00 | 31452.28 | 25117.58 | 22426.03 | 7667.93 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.55 | 33.32 | 36.23 | 102.47 | 70.87 | 0.00 | 0.00 | 0.00 |
February | 80.30 | 37.17 | 43.13 | 128.10 | 58.97 | 0.00 | 0.00 | 0.00 |
March | 98.04 | 46.35 | 51.69 | 158.46 | 48.01 | 0.00 | 0.00 | 0.00 |
April | 106.40 | 47.48 | 58.93 | 192.53 | 33.87 | 0.00 | 0.00 | 0.00 |
May | 100.66 | 40.09 | 60.58 | 200.19 | 17.25 | 0.00 | 0.00 | 0.00 |
June | 99.35 | 38.16 | 61.19 | 207.94 | 8.74 | 0.00 | 0.00 | 0.00 |
July | 102.09 | 36.81 | 65.27 | 221.47 | 12.34 | 0.00 | 0.00 | 0.00 |
August | 93.35 | 31.21 | 62.14 | 194.44 | 9.75 | 0.00 | 0.00 | 0.00 |
September | 90.00 | 32.53 | 57.46 | 190.55 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 82.84 | 35.67 | 47.16 | 161.95 | 21.95 | 0.00 | 0.00 | 0.00 |
November | 67.23 | 26.81 | 40.43 | 116.67 | 38.23 | 0.00 | 0.00 | 0.00 |
December | 54.31 | 19.17 | 35.14 | 80.74 | 62.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87.03 | 35.37 | 51.65 | 163.09 | 32.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.31 | 19.17 | 35.14 | 80.74 | 8.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.40 | 47.48 | 65.27 | 221.47 | 70.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.51 | 176.39 | 95.12 | 449.50 | 138.76 | 0.00 | 0.00 | 0.00 |
February | 245.62 | 142.12 | 103.50 | 428.80 | 117.60 | 0.00 | 0.00 | 0.00 |
March | 188.58 | 79.73 | 108.85 | 333.62 | 98.68 | 0.00 | 0.00 | 0.00 |
April | 128.23 | 22.49 | 105.75 | 248.56 | 69.59 | 0.00 | 0.00 | 0.00 |
May | 102.76 | 2.22 | 100.53 | 218.59 | 35.52 | 0.00 | 0.00 | 0.00 |
June | 97.97 | 0.18 | 97.79 | 224.21 | 18.44 | 0.00 | 0.00 | 0.00 |
July | 104.90 | 0.97 | 103.93 | 252.71 | 25.08 | 0.00 | 0.00 | 0.00 |
August | 119.06 | 10.05 | 109.01 | 270.02 | 20.13 | 0.00 | 0.00 | 0.00 |
September | 152.41 | 37.35 | 115.06 | 346.99 | 29.25 | 0.00 | 0.00 | 0.00 |
October | 209.59 | 98.33 | 111.26 | 423.48 | 44.96 | 0.00 | 0.00 | 0.00 |
November | 238.47 | 133.09 | 105.38 | 432.84 | 76.95 | 0.00 | 0.00 | 0.00 |
December | 261.66 | 165.04 | 96.62 | 442.51 | 122.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.41 | 72.02 | 104.39 | 338.87 | 66.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.97 | 0.18 | 95.12 | 218.59 | 18.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 271.51 | 176.39 | 115.06 | 449.50 | 138.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.48 | 26.93 | 35.54 | 91.04 | 73.88 | 0.00 | 0.00 | 0.00 |
February | 78.12 | 35.36 | 42.77 | 127.87 | 61.78 | 0.00 | 0.00 | 0.00 |
March | 97.29 | 44.43 | 52.86 | 161.39 | 50.90 | 0.00 | 0.00 | 0.00 |
April | 107.09 | 49.58 | 57.50 | 195.36 | 34.36 | 0.00 | 0.00 | 0.00 |
May | 97.62 | 37.58 | 60.04 | 196.20 | 18.08 | 0.00 | 0.00 | 0.00 |
June | 82.72 | 23.20 | 59.51 | 177.22 | 9.37 | 0.00 | 0.00 | 0.00 |
July | 92.44 | 28.60 | 63.85 | 203.43 | 12.39 | 0.00 | 0.00 | 0.00 |
August | 92.23 | 30.06 | 62.18 | 192.58 | 10.16 | 0.00 | 0.00 | 0.00 |
September | 78.68 | 23.20 | 55.48 | 169.55 | 14.54 | 0.00 | 0.00 | 0.00 |
October | 78.27 | 30.51 | 47.76 | 154.19 | 22.72 | 0.00 | 0.00 | 0.00 |
November | 64.57 | 23.68 | 40.88 | 114.18 | 40.52 | 0.00 | 0.00 | 0.00 |
December | 64.68 | 28.92 | 35.76 | 100.97 | 63.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.05 | 31.83 | 51.22 | 157.16 | 34.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 62.48 | 23.20 | 35.54 | 91.04 | 9.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.09 | 49.58 | 63.85 | 203.43 | 73.88 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186274E+09 | 89236778.67 | 97037547.90 | 0.274456E+09 | 0.189829E+09 |
February | 0.194271E+09 | 89928048.50 | 0.104342E+09 | 0.309893E+09 | 0.142671E+09 |
March | 0.262603E+09 | 0.124147E+09 | 0.138456E+09 | 0.424413E+09 | 0.128584E+09 |
April | 0.275797E+09 | 0.123059E+09 | 0.152738E+09 | 0.499035E+09 | 87803115.09 |
May | 0.269612E+09 | 0.107366E+09 | 0.162247E+09 | 0.536182E+09 | 46196073.93 |
June | 0.257527E+09 | 98914328.81 | 0.158613E+09 | 0.538989E+09 | 22652577.49 |
July | 0.273432E+09 | 98605159.65 | 0.174827E+09 | 0.593182E+09 | 33054058.17 |
August | 0.250030E+09 | 83604612.69 | 0.166426E+09 | 0.520778E+09 | 26114223.29 |
September | 0.233270E+09 | 84327711.19 | 0.148942E+09 | 0.493906E+09 | 36912644.74 |
October | 0.221872E+09 | 95551600.38 | 0.126321E+09 | 0.433763E+09 | 58794956.13 |
November | 0.174270E+09 | 69487909.69 | 0.104782E+09 | 0.302399E+09 | 99103379.35 |
December | 0.145464E+09 | 51355836.69 | 94108437.05 | 0.216262E+09 | 0.167473E+09 |
Annual Sum or Average | 0.274442E+10 | 0.111558E+10 | 0.162884E+10 | 0.514326E+10 | 0.103919E+10 |
Minimum of Months | 0.145464E+09 | 51355836.69 | 94108437.05 | 0.216262E+09 | 22652577.49 |
Maximum of Months | 0.275797E+09 | 0.124147E+09 | 0.174827E+09 | 0.593182E+09 | 0.189829E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.727216E+09 | 0.472455E+09 | 0.254760E+09 | 0.120393E+10 | 0.371643E+09 |
February | 0.594208E+09 | 0.343822E+09 | 0.250386E+09 | 0.103736E+10 | 0.284495E+09 |
March | 0.505098E+09 | 0.213551E+09 | 0.291547E+09 | 0.893566E+09 | 0.264309E+09 |
April | 0.332378E+09 | 58286166.70 | 0.274092E+09 | 0.644262E+09 | 0.180367E+09 |
May | 0.275226E+09 | 5954427.09 | 0.269272E+09 | 0.585467E+09 | 95125585.46 |
June | 0.253939E+09 | 479224.57 | 0.253460E+09 | 0.581140E+09 | 47799460.36 |
July | 0.280964E+09 | 2604277.42 | 0.278359E+09 | 0.676861E+09 | 67170804.11 |
August | 0.318885E+09 | 26909133.90 | 0.291975E+09 | 0.723230E+09 | 53907224.41 |
September | 0.395046E+09 | 96806670.67 | 0.298239E+09 | 0.899399E+09 | 75816259.33 |
October | 0.561376E+09 | 0.263380E+09 | 0.297996E+09 | 0.113426E+10 | 0.120424E+09 |
November | 0.618118E+09 | 0.344978E+09 | 0.273140E+09 | 0.112192E+10 | 0.199461E+09 |
December | 0.700832E+09 | 0.442045E+09 | 0.258787E+09 | 0.118523E+10 | 0.326980E+09 |
Annual Sum or Average | 0.556329E+10 | 0.227127E+10 | 0.329201E+10 | 0.106866E+11 | 0.208750E+10 |
Minimum of Months | 0.253939E+09 | 479224.57 | 0.250386E+09 | 0.581140E+09 | 47799460.36 |
Maximum of Months | 0.727216E+09 | 0.472455E+09 | 0.298239E+09 | 0.120393E+10 | 0.371643E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167337E+09 | 72141064.99 | 95195525.66 | 0.243853E+09 | 0.197888E+09 |
February | 0.189000E+09 | 85533114.92 | 0.103467E+09 | 0.309335E+09 | 0.149467E+09 |
March | 0.260580E+09 | 0.118994E+09 | 0.141586E+09 | 0.432273E+09 | 0.136326E+09 |
April | 0.277571E+09 | 0.128524E+09 | 0.149047E+09 | 0.506363E+09 | 89051672.65 |
May | 0.261476E+09 | 0.100656E+09 | 0.160820E+09 | 0.525492E+09 | 48437224.79 |
June | 0.214404E+09 | 60142129.75 | 0.154262E+09 | 0.459367E+09 | 24288034.74 |
July | 0.247603E+09 | 76600471.73 | 0.171003E+09 | 0.544857E+09 | 33190695.67 |
August | 0.247040E+09 | 80509729.17 | 0.166530E+09 | 0.515817E+09 | 27218625.78 |
September | 0.203940E+09 | 60135399.20 | 0.143805E+09 | 0.439486E+09 | 37682645.90 |
October | 0.209646E+09 | 81726181.78 | 0.127919E+09 | 0.412980E+09 | 60856900.99 |
November | 0.167357E+09 | 61387443.49 | 0.105970E+09 | 0.295962E+09 | 0.105029E+09 |
December | 0.173245E+09 | 77456445.60 | 95788625.49 | 0.270447E+09 | 0.169965E+09 |
Annual Sum or Average | 0.261920E+10 | 0.100381E+10 | 0.161539E+10 | 0.495623E+10 | 0.107940E+10 |
Minimum of Months | 0.167337E+09 | 60135399.20 | 95195525.66 | 0.243853E+09 | 24288034.74 |
Maximum of Months | 0.277571E+09 | 0.128524E+09 | 0.171003E+09 | 0.544857E+09 | 0.197888E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 636.99 | 277.49 | 403.53 | 236.65 | 166.89 | 0.00 | 0.00 |
February | 680.47 | 234.06 | 404.05 | 214.65 | 189.40 | 0.00 | 0.00 |
March | 645.96 | 190.07 | 383.92 | 170.51 | 213.41 | 0.00 | 0.00 |
April | 633.37 | 134.74 | 341.72 | 119.55 | 222.17 | 0.00 | 0.00 |
May | 613.89 | 69.77 | 301.04 | 79.89 | 221.15 | 0.00 | 0.00 |
June | 608.64 | 35.82 | 280.04 | 61.55 | 218.49 | 0.00 | 0.00 |
July | 677.25 | 49.45 | 299.43 | 66.39 | 233.05 | 0.00 | 0.00 |
August | 656.90 | 39.89 | 304.64 | 71.32 | 233.32 | 0.00 | 0.00 |
September | 706.56 | 57.50 | 321.09 | 93.08 | 228.00 | 0.00 | 0.00 |
October | 739.02 | 89.03 | 370.70 | 164.52 | 206.18 | 0.00 | 0.00 |
November | 661.58 | 153.60 | 370.27 | 183.59 | 186.69 | 0.00 | 0.00 |
December | 621.07 | 244.91 | 380.65 | 213.13 | 167.52 | 0.00 | 0.00 |
Annual Sum or Average | 656.66 | 130.91 | 346.49 | 139.23 | 207.26 | 0.00 | 0.00 |
Minimum of Months | 608.64 | 35.82 | 280.04 | 61.55 | 166.89 | 0.00 | 0.00 |
Maximum of Months | 739.02 | 277.49 | 404.05 | 236.65 | 233.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170610E+10 | 0.743218E+09 | 0.108083E+10 | 0.633833E+09 | 0.446993E+09 | 0.00 | 0.00 |
February | 0.164620E+10 | 0.566239E+09 | 0.977479E+09 | 0.519283E+09 | 0.458195E+09 | 0.00 | 0.00 |
March | 0.173013E+10 | 0.509097E+09 | 0.102828E+10 | 0.456692E+09 | 0.571588E+09 | 0.00 | 0.00 |
April | 0.164169E+10 | 0.349247E+09 | 0.885746E+09 | 0.309869E+09 | 0.575877E+09 | 0.00 | 0.00 |
May | 0.164425E+10 | 0.186866E+09 | 0.806315E+09 | 0.213976E+09 | 0.592339E+09 | 0.00 | 0.00 |
June | 0.157760E+10 | 92842667.76 | 0.725871E+09 | 0.159536E+09 | 0.566335E+09 | 0.00 | 0.00 |
July | 0.181394E+10 | 0.132456E+09 | 0.801999E+09 | 0.177810E+09 | 0.624189E+09 | 0.00 | 0.00 |
August | 0.175943E+10 | 0.106850E+09 | 0.815955E+09 | 0.191023E+09 | 0.624931E+09 | 0.00 | 0.00 |
September | 0.183141E+10 | 0.149030E+09 | 0.832256E+09 | 0.241270E+09 | 0.590986E+09 | 0.00 | 0.00 |
October | 0.197938E+10 | 0.238454E+09 | 0.992894E+09 | 0.440658E+09 | 0.552236E+09 | 0.00 | 0.00 |
November | 0.171483E+10 | 0.398133E+09 | 0.959744E+09 | 0.475853E+09 | 0.483891E+09 | 0.00 | 0.00 |
December | 0.166348E+10 | 0.655967E+09 | 0.101954E+10 | 0.570857E+09 | 0.448684E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.207084E+11 | 0.412840E+10 | 0.109269E+11 | 0.439066E+10 | 0.653625E+10 | 0.00 | 0.00 |
Minimum of Months | 0.157760E+10 | 92842667.76 | 0.725871E+09 | 0.159536E+09 | 0.446993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197938E+10 | 0.743218E+09 | 0.108083E+10 | 0.633833E+09 | 0.624931E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.101005E+11 | -0.943665E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -663831185.9 | 58.98 | 0.00 | 0.00 |
February | 0.903766E+10 | -0.844025E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -597408258.9 | 58.98 | 0.00 | 0.00 |
March | 0.973512E+10 | -0.907576E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -659358456.6 | 58.99 | 0.00 | 0.00 |
April | 0.898703E+10 | -0.835551E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -631515804.2 | 58.98 | 0.00 | 0.00 |
May | 0.886164E+10 | -0.821194E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -649702847.6 | 58.98 | 0.00 | 0.00 |
June | 0.825284E+10 | -0.762984E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -622996914.9 | 58.98 | 0.00 | 0.00 |
July | 0.836223E+10 | -0.772226E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -639965139.5 | 58.98 | 0.00 | 0.00 |
August | 0.847980E+10 | -0.783906E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -640740865.1 | 58.99 | 0.00 | 0.00 |
September | 0.847832E+10 | -0.785550E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -622821855.6 | 58.98 | 0.00 | 0.00 |
October | 0.919056E+10 | -0.854287E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -647685893.4 | 58.98 | 0.00 | 0.00 |
November | 0.932443E+10 | -0.869216E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -632276291.6 | 58.98 | 0.00 | 0.00 |
December | 0.995405E+10 | -0.929237E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -661678361.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.108764E+12 | -0.101094E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.766998E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.825284E+10 | -0.943665E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -663831185.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.101005E+11 | -0.762984E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -597408258.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.28 | 0.24 | 01-JAN-07:49 | 1411.14 | 24.41 | 119.33 | 290.33 | 1413.50 | 24.09 | 116.17 | 288.83 |
February | 304.33 | 0.27 | 0.24 | 01-FEB-07:49 | 1195.52 | 21.94 | 86.00 | 279.33 | 1120.29 | 19.88 | 45.67 | 272.67 |
March | 362.67 | 0.26 | 0.24 | 01-MAR-07:40 | 1006.22 | 17.93 | 3.67 | 341.50 | 1015.12 | 17.83 | 1.83 | 341.00 |
April | 357.50 | 0.27 | 0.24 | 01-APR-06:00 | 945.24 | 17.34 | 0.00 | 335.83 | 1019.98 | 17.45 | 0.00 | 333.50 |
May | 389.00 | 0.27 | 0.24 | 01-MAY-06:19 | 841.69 | 16.99 | 0.00 | 364.17 | 1016.28 | 17.00 | 0.00 | 362.17 |
June | 388.17 | 0.28 | 0.24 | 01-JUN-06:40 | 741.12 | 16.45 | 0.00 | 339.33 | 989.79 | 16.39 | 0.00 | 345.17 |
July | 403.83 | 0.27 | 0.24 | 01-JUL-06:30 | 831.95 | 17.24 | 0.00 | 364.17 | 901.07 | 17.22 | 0.00 | 364.83 |
August | 348.33 | 0.27 | 0.24 | 01-AUG-06:49 | 919.64 | 17.62 | 0.00 | 348.00 | 957.78 | 17.67 | 0.00 | 351.00 |
September | 349.67 | 0.27 | 0.24 | 01-SEP-06:49 | 894.23 | 18.13 | 5.00 | 320.83 | 1012.63 | 18.03 | 5.67 | 321.67 |
October | 323.50 | 0.28 | 0.24 | 02-OCT-07:10 | 1088.54 | 20.61 | 60.33 | 313.83 | 1077.75 | 20.41 | 51.83 | 313.33 |
November | 314.83 | 0.27 | 0.24 | 01-NOV-06:00 | 1108.20 | 22.87 | 104.67 | 289.00 | 1012.18 | 20.71 | 53.33 | 288.17 |
December | 282.67 | 0.27 | 0.24 | 01-DEC-08:39 | 1370.47 | 24.14 | 109.00 | 276.67 | 1313.48 | 23.67 | 97.67 | 273.50 |
Annual Sum or Average | 4111.50 | 0.27 | 1007.95 | 19.34 | 488.00 | 3863.00 | 1057.80 | 18.94 | 372.17 | 3855.83 | ||
Minimum of Months | 282.67 | 0.26 | 0.24 | 741.12 | 16.45 | 0.00 | 276.67 | 901.07 | 16.39 | 0.00 | 272.67 | |
Maximum of Months | 403.83 | 0.28 | 0.24 | 1411.14 | 24.41 | 119.33 | 364.17 | 1413.50 | 24.09 | 116.17 | 364.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286378E+09 | 8649.78 | 25-JAN-08:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.368922E+09 | 13194.64 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302330E+09 | 9927.63 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51455542.93 | 4880.95 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377286E+09 | 8131.27 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377286E+09 | 13194.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14511433.09 | 5091.35 | 04-FEB-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 373827.96 | 3421.59 | 16-MAR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14885261.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14511433.09 | 5091.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.126550E+11 | 0.741620E+10 | 34763.22 | 02-JAN-14:00 | 17394.23 | 0.00 |
February | 0.00 | 0.00 | 0.154927E+11 | 0.957699E+10 | 29532.37 | 11-FEB-14:00 | 15736.55 | 0.00 |
March | 0.00 | 0.00 | 0.198078E+11 | 0.113410E+11 | 37015.93 | 03-MAR-05:01 | 24651.07 | 0.00 |
April | 0.00 | 0.00 | 0.267555E+11 | 0.158384E+11 | 46028.74 | 13-APR-04:01 | 21489.70 | 0.00 |
May | 0.00 | 0.00 | 0.407061E+11 | 0.218480E+11 | 54698.93 | 30-MAY-04:01 | 23033.08 | 0.00 |
June | 0.00 | 0.00 | 0.486431E+11 | 0.240312E+11 | 54698.93 | 06-JUN-04:01 | 23160.31 | 0.00 |
July | 0.00 | 0.00 | 0.534723E+11 | 0.269330E+11 | 54698.93 | 11-JUL-04:01 | 23678.10 | 0.00 |
August | 0.00 | 0.00 | 0.532405E+11 | 0.262016E+11 | 54698.93 | 04-AUG-04:01 | 24694.08 | 0.00 |
September | 0.00 | 0.00 | 0.492962E+11 | 0.247266E+11 | 54698.93 | 19-SEP-04:01 | 24758.70 | 0.00 |
October | 0.00 | 0.00 | 0.433035E+11 | 0.225345E+11 | 54698.93 | 03-OCT-04:01 | 21907.69 | 0.00 |
November | 0.00 | 0.00 | 0.299758E+11 | 0.156729E+11 | 52980.18 | 10-NOV-05:01 | 23839.14 | 0.00 |
December | 0.00 | 0.00 | 0.167953E+11 | 0.907666E+10 | 46152.60 | 09-DEC-05:01 | 21870.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.410144E+12 | 0.215197E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.126550E+11 | 0.741620E+10 | 29532.37 | 15736.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.534723E+11 | 0.269330E+11 | 54698.93 | 24758.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.173844E+11 | 0.957184E+10 | 31452.28 | 02-JAN-13:55 | 14856.12 | 0.00 |
February | 0.00 | 0.00 | 0.196971E+11 | 0.114584E+11 | 31452.28 | 11-FEB-11:47 | 15107.31 | 0.00 |
March | 0.00 | 0.00 | 0.254873E+11 | 0.137519E+11 | 31452.28 | 13-MAR-12:13 | 15571.70 | 0.00 |
April | 0.00 | 0.00 | 0.324445E+11 | 0.186615E+11 | 31452.28 | 01-APR-15:43 | 14152.10 | 0.00 |
May | 0.00 | 0.00 | 0.492664E+11 | 0.256686E+11 | 31452.28 | 12-MAY-10:27 | 15936.66 | 0.00 |
June | 0.00 | 0.00 | 0.584297E+11 | 0.277558E+11 | 31452.28 | 06-JUN-04:13 | 10425.90 | 0.00 |
July | 0.00 | 0.00 | 0.617083E+11 | 0.303602E+11 | 31452.28 | 12-JUL-18:42 | 13984.72 | 0.00 |
August | 0.00 | 0.00 | 0.623772E+11 | 0.294768E+11 | 31452.28 | 12-AUG-13:40 | 10004.85 | 0.00 |
September | 0.00 | 0.00 | 0.581260E+11 | 0.279246E+11 | 31452.28 | 28-SEP-04:02 | 10664.27 | 0.00 |
October | 0.00 | 0.00 | 0.517202E+11 | 0.254212E+11 | 31452.28 | 01-OCT-15:11 | 10416.22 | 0.00 |
November | 0.00 | 0.00 | 0.370611E+11 | 0.179686E+11 | 31452.28 | 03-NOV-18:03 | 13995.36 | 0.00 |
December | 0.00 | 0.00 | 0.231853E+11 | 0.114729E+11 | 31452.28 | 07-DEC-11:40 | 15402.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.496888E+12 | 0.249492E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.173844E+11 | 0.957184E+10 | 31452.28 | 10004.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.623772E+11 | 0.303602E+11 | 31452.28 | 15936.66 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3815.76 | 13889.39 | 18-JAN-13:53 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3781.06 | 13853.35 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3683.72 | 13580.04 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 3515.95 | 13037.88 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 3361.35 | 12409.97 | 01-MAY-12:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 3239.84 | 11831.05 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 3176.20 | 11488.60 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 3224.10 | 11742.65 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 3324.60 | 12268.44 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3483.01 | 12916.40 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 3647.81 | 13476.39 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 3760.76 | 13830.75 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 3499.64 | ||||
Minimum of Months | 0.00 | 0.00 | 3176.20 | 11488.60 | ||
Maximum of Months | 0.00 | 0.00 | 3815.76 | 13889.39 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:02 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:02 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.125188E+10 | 0.24 | 503.64 | 01-JAN-00:10 | 0.26 |
February | 0.113411E+10 | 0.24 | 503.64 | 01-FEB-00:10 | 0.26 |
March | 0.126658E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.26 |
April | 0.124567E+10 | 0.25 | 503.64 | 01-APR-00:15 | 0.26 |
May | 0.128834E+10 | 0.25 | 503.64 | 01-MAY-00:30 | 0.26 |
June | 0.124644E+10 | 0.25 | 503.64 | 01-JUN-00:06 | 0.26 |
July | 0.128788E+10 | 0.25 | 503.64 | 01-JUL-00:06 | 0.26 |
August | 0.128811E+10 | 0.25 | 503.64 | 01-AUG-00:06 | 0.26 |
September | 0.124615E+10 | 0.25 | 503.64 | 01-SEP-00:06 | 0.26 |
October | 0.128731E+10 | 0.25 | 503.64 | 01-OCT-00:06 | 0.26 |
November | 0.123928E+10 | 0.25 | 503.64 | 01-NOV-00:19 | 0.26 |
December | 0.125972E+10 | 0.24 | 503.64 | 01-DEC-00:02 | 0.26 |
Annual Sum or Average | 0.150415E+11 | 0.25 | |||
Minimum of Months | 0.113411E+10 | 0.24 | 503.64 | 0.26 | |
Maximum of Months | 0.128834E+10 | 0.25 | 503.64 | 0.26 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192832E+10 | 0.44 | 1257.82 | 05-JAN-05:01 | 0.67 |
February | 0.174455E+10 | 0.45 | 1186.78 | 04-FEB-07:10 | 0.65 |
March | 0.193032E+10 | 0.45 | 1439.85 | 03-MAR-05:01 | 0.72 |
April | 0.187199E+10 | 0.45 | 1741.79 | 13-APR-04:01 | 0.79 |
May | 0.198597E+10 | 0.46 | 2150.33 | 30-MAY-04:01 | 0.87 |
June | 0.205199E+10 | 0.48 | 2150.33 | 06-JUN-04:01 | 0.87 |
July | 0.220978E+10 | 0.49 | 2150.33 | 11-JUL-04:01 | 0.87 |
August | 0.219043E+10 | 0.49 | 2150.33 | 01-AUG-04:01 | 0.87 |
September | 0.208308E+10 | 0.48 | 2150.33 | 19-SEP-04:01 | 0.87 |
October | 0.202300E+10 | 0.47 | 2150.33 | 03-OCT-04:01 | 0.87 |
November | 0.188934E+10 | 0.45 | 2069.34 | 10-NOV-05:01 | 0.85 |
December | 0.193218E+10 | 0.45 | 1747.63 | 09-DEC-05:01 | 0.79 |
Annual Sum or Average | 0.238410E+11 | 0.46 | |||
Minimum of Months | 0.174455E+10 | 0.44 | 1186.78 | 0.65 | |
Maximum of Months | 0.220978E+10 | 0.49 | 2150.33 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126700E+10 | 0.53 | 1279.34 | 02-JAN-13:45 | 0.90 |
February | 0.117200E+10 | 0.54 | 1279.34 | 01-FEB-05:01 | 0.90 |
March | 0.136979E+10 | 0.55 | 1279.34 | 03-MAR-04:21 | 0.90 |
April | 0.145031E+10 | 0.59 | 1279.34 | 01-APR-14:55 | 0.89 |
May | 0.198787E+10 | 0.67 | 1279.34 | 02-MAY-03:32 | 0.90 |
June | 0.236537E+10 | 0.74 | 1279.34 | 01-JUN-02:62 | 0.90 |
July | 0.252577E+10 | 0.75 | 1279.34 | 01-JUL-02:62 | 0.90 |
August | 0.254155E+10 | 0.76 | 1279.34 | 01-AUG-02:62 | 0.89 |
September | 0.236088E+10 | 0.74 | 1279.34 | 01-SEP-02:62 | 0.90 |
October | 0.209946E+10 | 0.69 | 1279.34 | 01-OCT-02:62 | 0.89 |
November | 0.167912E+10 | 0.62 | 1279.34 | 03-NOV-03:22 | 0.90 |
December | 0.139047E+10 | 0.55 | 1279.34 | 01-DEC-04:21 | 0.90 |
Annual Sum or Average | 0.222096E+11 | 0.64 | |||
Minimum of Months | 0.117200E+10 | 0.53 | 1279.34 | 0.89 | |
Maximum of Months | 0.254155E+10 | 0.76 | 1279.34 | 0.90 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 53.03 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 53.77 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:05 | 0.00 | 0.00 | 53.50 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 54.27 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 53.16 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.58 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 54.29 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 54.74 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 54.22 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.93 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.36 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.51 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 53.03 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 54.74 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 44.27 | 44.27 | 3815.76 | 13889.39 | 18-JAN-13:53 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53.91 | 53.91 | 3781.06 | 13853.35 | 01-FEB-13:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 53.70 | 53.70 | 3683.72 | 13580.04 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:02 | 54.56 | 54.56 | 3515.95 | 13037.88 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:02 | 45.89 | 45.89 | 3361.35 | 12409.97 | 01-MAY-12:50 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 54.54 | 54.54 | 3239.84 | 11831.05 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 54.62 | 54.62 | 3176.20 | 11488.60 | 01-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 54.68 | 54.68 | 3224.10 | 11742.65 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 54.17 | 54.17 | 3324.60 | 12268.44 | 30-SEP-12:45 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 46.06 | 46.06 | 3483.01 | 12916.40 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 54.35 | 54.35 | 3647.81 | 13476.39 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:02 | 53.57 | 53.57 | 3760.76 | 13830.75 | 31-DEC-14:00 |
Annual Sum or Average | 0.00 | 3499.64 | ||||||
Minimum of Months | 0.00 | 0.00 | 44.27 | 44.27 | 3176.20 | 11488.60 | ||
Maximum of Months | 0.00 | 0.00 | 54.68 | 54.68 | 3815.76 | 13889.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.529671E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.585986E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.710124E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.874854E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119451E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.136086E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149881E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148318E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138323E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.125024E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.929269E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.627698E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.124284E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.529671E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.149881E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.545646E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.588369E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.737742E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.901964E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.131442E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.155325E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.165784E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166613E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155041E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.137925E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.101571E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.685690E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135964E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.545646E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166613E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192832E+10 | 0.126550E+11 | 0.286378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174455E+10 | 0.154927E+11 | 0.368922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193032E+10 | 0.198078E+11 | 0.302330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187199E+10 | 0.267555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198597E+10 | 0.407061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205199E+10 | 0.486431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220978E+10 | 0.534723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.219043E+10 | 0.532405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208308E+10 | 0.492962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202300E+10 | 0.433035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188934E+10 | 0.299758E+11 | 51455542.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193218E+10 | 0.167953E+11 | 0.377286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238410E+11 | 0.410144E+12 | 0.138637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174455E+10 | 0.126550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220978E+10 | 0.534723E+11 | 0.377286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126700E+10 | 0.173844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117200E+10 | 0.196971E+11 | 14511433.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136979E+10 | 0.254873E+11 | 373827.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145031E+10 | 0.324445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198787E+10 | 0.492664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236537E+10 | 0.584297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.252577E+10 | 0.617083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254155E+10 | 0.623772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236088E+10 | 0.581260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209946E+10 | 0.517202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167912E+10 | 0.370611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139047E+10 | 0.231853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222096E+11 | 0.496888E+12 | 14885261.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117200E+10 | 0.173844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254155E+10 | 0.623772E+11 | 14511433.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192832E+10 | 0.00 | 0.00 | 0.00 | 0.336838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174455E+10 | 0.00 | 0.00 | 0.00 | 0.411531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193032E+10 | 0.00 | 0.00 | 0.00 | 0.517091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187199E+10 | 0.00 | 0.00 | 0.00 | 0.687654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198597E+10 | 0.00 | 0.00 | 0.00 | 0.995910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205199E+10 | 0.00 | 0.00 | 0.00 | 0.115566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220978E+10 | 0.00 | 0.00 | 0.00 | 0.127783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.219043E+10 | 0.00 | 0.00 | 0.00 | 0.126413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208308E+10 | 0.00 | 0.00 | 0.00 | 0.117492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202300E+10 | 0.00 | 0.00 | 0.00 | 0.104794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188934E+10 | 0.00 | 0.00 | 0.00 | 0.740334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193218E+10 | 0.00 | 0.00 | 0.00 | 0.434480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238410E+11 | 0.00 | 0.00 | 0.00 | 0.100443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174455E+10 | 0.00 | 0.00 | 0.00 | 0.336838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220978E+10 | 0.00 | 0.00 | 0.00 | 0.127783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126700E+10 | 0.00 | 0.00 | 0.00 | 0.418947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117200E+10 | 0.00 | 0.00 | 0.00 | 0.471169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136979E+10 | 0.00 | 0.00 | 0.00 | 0.600764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145031E+10 | 0.00 | 0.00 | 0.00 | 0.756933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198787E+10 | 0.00 | 0.00 | 0.00 | 0.111563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.236537E+10 | 0.00 | 0.00 | 0.00 | 0.131671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.252577E+10 | 0.00 | 0.00 | 0.00 | 0.140526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.254155E+10 | 0.00 | 0.00 | 0.00 | 0.141197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.236088E+10 | 0.00 | 0.00 | 0.00 | 0.131432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209946E+10 | 0.00 | 0.00 | 0.00 | 0.116931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167912E+10 | 0.00 | 0.00 | 0.00 | 0.847796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.546643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222096E+11 | 0.00 | 0.00 | 0.00 | 0.113755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117200E+10 | 0.00 | 0.00 | 0.00 | 0.418947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254155E+10 | 0.00 | 0.00 | 0.00 | 0.141197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302696E+10 | 0.137872E+10 | 0.00 | 13280787.18 | 1762346.00 | 67535356.72 | 0.224907E+10 | 0.00 | 3.59 |
February | 0.173991E+10 | 0.161849E+10 | 0.00 | 13571096.68 | 2279996.32 | 0.191241E+09 | 0.135317E+10 | 0.00 | 3.59 |
March | 0.157389E+10 | 0.264235E+10 | 0.00 | 11431182.30 | 6755473.52 | 0.167777E+09 | 0.126838E+10 | 0.00 | 3.60 |
April | 0.301344E+09 | 0.433684E+10 | 0.00 | 7368933.16 | 13340526.79 | 0.00 | 0.578268E+09 | 0.00 | 3.61 |
May | 49927164.47 | 0.100548E+11 | 0.00 | 669843.27 | 83306847.06 | 0.00 | 36246285.23 | 0.00 | 3.64 |
June | 10185127.29 | 0.140662E+11 | 0.00 | 266955.49 | 0.206178E+09 | 0.00 | 4373666.24 | 0.00 | 3.66 |
July | 20911454.25 | 0.160338E+11 | 0.00 | 384054.19 | 0.191795E+09 | 0.00 | 9020829.82 | 0.00 | 3.66 |
August | 8304354.58 | 0.158368E+11 | 0.00 | 267435.93 | 0.216047E+09 | 0.00 | 3845978.06 | 0.00 | 3.67 |
September | 18941924.02 | 0.140812E+11 | 0.00 | 344497.74 | 0.172446E+09 | 0.00 | 6735636.91 | 0.00 | 3.67 |
October | 45010689.53 | 0.110202E+11 | 0.00 | 721174.12 | 0.105112E+09 | 0.00 | 19388160.77 | 0.00 | 3.67 |
November | 0.702558E+09 | 0.621673E+10 | 0.00 | 7003097.80 | 44602044.41 | 7196601.65 | 0.869944E+09 | 0.00 | 3.63 |
December | 0.226389E+10 | 0.252285E+10 | 0.00 | 10366949.77 | 6303876.67 | 0.146750E+09 | 0.198809E+10 | 0.00 | 3.60 |
Annual Sum or Average | 0.976185E+10 | 0.998089E+11 | 0.00 | 65676007.61 | 0.104993E+10 | 0.580501E+09 | 0.838653E+10 | 0.00 | 3.63 |
Minimum of Months | 8304354.58 | 0.137872E+10 | 0.00 | 266955.49 | 1762346.00 | 0.00 | 3845978.06 | 0.00 | 3.59 |
Maximum of Months | 0.302696E+10 | 0.160338E+11 | 0.00 | 13571096.68 | 0.216047E+09 | 0.191241E+09 | 0.224907E+10 | 0.00 | 3.67 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335189E+10 | 0.144540E+10 | 0.00 | 51029496.66 | 738822.18 | 0.00 | 0.130871E+11 | 0.00 | 6.96 |
February | 0.247724E+10 | 0.175603E+10 | 0.00 | 49649040.33 | 317805.21 | 0.00 | 0.886799E+10 | 0.00 | 7.02 |
March | 0.269946E+10 | 0.332621E+10 | 0.00 | 47753840.42 | 1381671.78 | 0.00 | 0.782049E+10 | 0.00 | 7.19 |
April | 0.494659E+09 | 0.480768E+10 | 0.00 | 46462259.31 | 4023531.32 | 0.00 | 0.384171E+10 | 0.00 | 7.49 |
May | 0.173511E+09 | 0.175803E+11 | 0.00 | 4775580.91 | 31585359.25 | 0.00 | 0.369271E+09 | 0.00 | 8.55 |
June | 33683857.02 | 0.312099E+11 | 0.00 | 803265.19 | 59726162.90 | 0.00 | 0.101959E+09 | 0.00 | 9.50 |
July | 44430104.91 | 0.339320E+11 | 0.00 | 1132908.96 | 57577840.85 | 0.00 | 0.158599E+09 | 0.00 | 9.65 |
August | 22450973.77 | 0.342961E+11 | 0.00 | 828294.32 | 63193336.69 | 0.00 | 0.123714E+09 | 0.00 | 9.71 |
September | 77967304.10 | 0.304987E+11 | 0.00 | 1017044.05 | 48223398.91 | 0.00 | 0.116636E+09 | 0.00 | 9.51 |
October | 0.139414E+09 | 0.213518E+11 | 0.00 | 7896984.79 | 39337084.28 | 0.00 | 0.414746E+09 | 0.00 | 8.81 |
November | 0.112075E+10 | 0.116138E+11 | 0.00 | 23874256.11 | 17290222.00 | 0.00 | 0.437298E+10 | 0.00 | 8.00 |
December | 0.284889E+10 | 0.435413E+10 | 0.00 | 45748156.52 | 4262017.43 | 0.00 | 0.105154E+11 | 0.00 | 7.23 |
Annual Sum or Average | 0.134844E+11 | 0.196172E+12 | 0.00 | 0.280971E+09 | 0.327657E+09 | 0.00 | 0.497906E+11 | 0.00 | 8.31 |
Minimum of Months | 22450973.77 | 0.144540E+10 | 0.00 | 803265.19 | 317805.21 | 0.00 | 0.101959E+09 | 0.00 | 6.96 |
Maximum of Months | 0.335189E+10 | 0.342961E+11 | 0.00 | 51029496.66 | 63193336.69 | 0.00 | 0.130871E+11 | 0.00 | 9.71 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.356390E+11 | 0.394385E+10 | 0.408286E+11 | 0.227293E+10 | 0.569312E+11 |
February | 0.399115E+11 | 0.188604E+10 | 0.267896E+11 | 0.173996E+10 | 0.619543E+11 |
March | 0.559688E+11 | 0.112709E+10 | 0.209713E+11 | 0.156808E+10 | 0.770705E+11 |
April | 0.624671E+11 | -0.257888E+10 | 0.182297E+10 | 0.101479E+10 | 0.953695E+11 |
May | 0.613601E+11 | -0.884131E+10 | -0.318933E+11 | 0.520862E+09 | 0.133373E+12 |
June | 0.553665E+11 | -0.128347E+11 | -0.506762E+11 | 25663505.55 | 0.154641E+12 |
July | 0.605154E+11 | -0.144110E+11 | -0.543603E+11 | 0.113208E+09 | 0.166866E+12 |
August | 0.631947E+11 | -0.145080E+11 | -0.557916E+11 | 19544771.47 | 0.166876E+12 |
September | 0.486276E+11 | -0.130486E+11 | -0.494426E+11 | 0.176168E+09 | 0.154929E+12 |
October | 0.464652E+11 | -0.102343E+11 | -0.357543E+11 | 0.408332E+09 | 0.139771E+12 |
November | 0.340149E+11 | -0.481403E+10 | -0.578968E+10 | 0.127056E+10 | 0.101570E+12 |
December | 0.343739E+11 | 0.214178E+10 | 0.278154E+11 | 0.189687E+10 | 0.688089E+11 |
Annual Sum or Average | 0.597905E+12 | -0.721720E+11 | -0.165480E+12 | 0.110270E+11 | 0.137816E+13 |
Minimum of Months | 0.340149E+11 | -0.145080E+11 | -0.557916E+11 | 19544771.47 | 0.569312E+11 |
Maximum of Months | 0.631947E+11 | 0.394385E+10 | 0.408286E+11 | 0.227293E+10 | 0.166876E+12 |