Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:28:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1794.50 | 7723.51 | 7723.51 |
Net Site Energy | 1794.50 | 7723.51 | 7723.51 |
Total Source Energy | 3203.82 | 13789.18 | 13789.18 |
Net Source Energy | 3203.82 | 13789.18 | 13789.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 492.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 41.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 221.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 63.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 604.21 | 1190.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 492.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 39.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 41.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 128.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 221.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 29.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 492.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 39.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 54.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 41.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 128.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 221.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 63.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 413.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 724.19 | 3069.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.84 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2600.53 | 5122.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 413.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 724.19 | 3069.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.84 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2600.53 | 5122.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 604.214 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 604.214 | 100.00 |
Total On-Site and Utility Electric Sources | 604.214 | 100.00 |
Total Electricity End Uses | 604.214 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4161.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 13.7183 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 12.2230 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 12.9706 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 12.9706 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 13.7183 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 12.2230 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 12.9706 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 12.9706 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 12.9706 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-11:20 | 06-FEB-13:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 91537.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18070.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13527.31 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27993.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2944.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42016.09 | 142514.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 91537.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 18070.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12159.73 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 27993.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1322.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 533.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 173.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 130.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 406.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 239.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 199.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1913.55 | 1290.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2295.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 544.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1749.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1031.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 858.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8235.87 | 5553.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2295.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 544.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 747.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 562.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1749.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1031.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 858.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 8235.87 | 5553.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.91 |
KITCHEN DIRECT AIR | 1.28 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 | 1.00 | 1.00 | 1.91 |
PSZ-AC_2:2 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.28 | 1.00 | 1.000000 | 1.28 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.91 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.28 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.91 | 2087.47 |
PSZ-AC_2:2_ADDAQ FAN | 1.28 | 1462.55 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.91 | 1.91 | 1.91 | 1.91 | 46633.96 | 61057.65 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.28 | 1.28 | 1.28 | 1.28 | 31855.31 | 79384.43 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.91 | 0.953611 | 1.91 | 46633.96 | 22566.85 | 46633.96 | 0.705900 | 0.705900 |
PSZ-AC_2:2 COOLING COIL | 1.28 | 0.641407 | 1.28 | 31855.31 | 15927.61 | 31855.31 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61057.65 |
PSZ-AC_2:2 HEATING COIL | 79384.43 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 13.718 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 130.505 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 12.223 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1086.229 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1593.672 | 13.718 | 18.204 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1593.672 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1419.966 | 12.223 | 226.351 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1419.966 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747841 | 3.9747841 | 3.9747841 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.4731_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.689 | 2.689 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.36425E-002 | 0.31435 | 0.46880 | 0.46880 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11754 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 9.529E-002 | 8.202E-004 | 1.025E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 9.529E-002 | 8.202E-004 | 1.004E-003 | 0.969 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 21074.28745 | 25289.14494 | 1.58935 | 1.90722 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 9005.06288 | 10806.07546 | 0.39384 | 0.47260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -16.30000 | 9.24091E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 17030.92595 | 20437.11114 | 1.06901 | 1.28281 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 29.46300 | 1.33655E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 2177.81045 | 2613.37254 | 8.50094E-002 | 1.14133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -16.30000 | 9.24091E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 28055.49 | 1.90722 | 1.90722 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 28899.13 | 0.47260 | 0.47260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24646.88 | 1.28281 | 1.28281 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 75799.51 | 1.14133 | 1.14133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.90722 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28281 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.90722 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.90722 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.90722 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90722 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.90722 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.90722 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28281 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28281 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28281 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28281 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28281 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.28281 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.90722 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.28281 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.90722 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.90722 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2087.46525 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.90722 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.90722 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.90722 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90722 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.90722 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.95361 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.90722 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 46633.96000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 22566.85354 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 46633.96000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70590 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70590 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 46633.96000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61057.65440 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61057.65440 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28281 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28281 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1462.54836 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28281 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28281 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28281 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28281 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28281 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64141 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28281 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31855.31000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15927.61361 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31855.31000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31855.31000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79384.42584 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 79384.42584 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 45276.5 | 10.10 | 9.97 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30943.5 | 10.66 | 10.53 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | N/A | 2.689 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | N/A | 2.689 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1255045815 | 0.4811929114 | Pass | Pass | 0.1401066049 | 0.3958352824 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1359817886 | 0.6472392496 | Pass | Pass | 5.1868683530E-002 | 0.2194938289 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1394607297 | 0.1369621021 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 490.71 | 203.82 | 979.88 | 16.66 | 520.39 | 2211.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4731_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4731_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.689 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.689 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.689 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 13.7183 | 116.17 | 1593.67 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 29.00 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 12.2230 | 116.17 | 1419.97 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 25.84 |
Interior Lighting Total | 12.9706 | 232.34 | 3013.64 | 54.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2625.88 | AstronomicalClock | - | 83.67 | 83.67 | 41.24 | |
Exterior Lighting Total | 2625.88 | 41.24 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 46633.96 | 32918.91 | 13715.05 | 0.71 | 3.30 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31855.31 | 22333.12 | 9522.19 | 0.70 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 45276.5 | 10.10 | 9.97 | ||||
PSZ-AC_2:2 COOLING COIL | 30943.5 | 10.66 | 10.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61057.65 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 79384.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.57 | 622.50 | 1.91 | 2087.47 | 1094.51 | 1.00 | 1.29 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.55 | 622.50 | 1.28 | 1462.55 | 1140.11 | 1.00 | 1.31 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 21074.29 | 25289.14 | 217.69 | 1.589 | 1.907 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01096 | 30.30 | 0.01337 | 0.416 | 0.00 |
KITCHEN | 17030.93 | 20437.11 | 175.92 | 1.069 | 1.283 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01021 | 29.46 | 0.01337 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9005.06 | 10806.08 | 93.02 | 0.394 | 0.473 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00749 | -16.30 | 0.00092 | 0.416 | 0.00 |
KITCHEN | 2177.81 | 2613.37 | 22.50 | 0.085 | 1.141 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00489 | -16.30 | 0.00092 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.91 | 1.91 | 0.47 | 0.47 | 1.9072 | 1.9072 | 1.9072 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.28 | 1.28 | 1.14 | 1.14 | 1.2828 | 1.2828 | 1.2828 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 46633.960 | 32918.912 | 1.907220 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 46633.96 | 30473.95 | 1.907220 | 25.27 | 18.96 | 0.01148572 | 11.89 | 11.50 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 21.8148 | 23.87 | 0.01096083 | 57.7445 | 21074.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61057.654 | 61057.654 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 61057.65 | 61057.65 | 1.907222 | 12.86 | 9.36 | 0.00606013 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.8148 | 21.11 | 0.00749315 | 46.9526 | 9005.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31855.310 | 22333.121 | 1.282810 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31855.31 | 19511.06 | 1.282810 | 29.09 | 21.24 | 0.01301709 | 11.86 | 11.48 | 0.00850000 | 29.46 | 0.01336548 | 21.59 | 88.9714 | 26.10 | 0.01020664 | 47.1440 | 17030.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 79384.426 | 79384.426 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 79384.43 | 79384.43 | 1.282813 | -12.46 | -12.46 | 0.00141622 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 88.9711 | 18.29 | 0.00538624 | 40.3287 | 717.64 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 46633.960 | 32918.912 | 1.907220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.1914 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.907222 | 2.23893650 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 46633.96 | 30473.95 | 1.0000 | 2.23893384 | 1.907220 | 25.27 | 18.96 | 0.01148572 | 54657.1 | 11.89 | 11.50 | 0.00850000 | 33394.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46633.96 | 30.30 | 0.01336696 | 21.83 | 0.41605618 | 21.8148 | 23.87 | 0.01096083 | 23.87 | 0.01096083 | 57.7445 | 21074.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61057.654 | 61057.654 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.907222 | 2.23893650 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 61057.65 | 61057.65 | 1.0000 | 2.23893650 | 1.907222 | 12.86 | 9.36 | 0.00606013 | 28224.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61057.65 | -16.30 | 0.00092409 | -16.30 | 0.41605618 | 21.8148 | 21.00 | 0.00749315 | 21.11 | 0.00749315 | 46.9526 | 9005.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31855.310 | 22333.121 | 1.282810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1029.0381 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.282813 | 1.50592724 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 31855.31 | 19511.06 | 1.0000 | 1.50592313 | 1.282810 | 29.09 | 21.24 | 0.01301709 | 62487.1 | 11.86 | 11.48 | 0.00850000 | 33358.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31855.31 | 29.46 | 0.01336548 | 21.59 | 1.14133354 | 88.9714 | 26.06 | 0.01020664 | 26.10 | 0.01020664 | 47.1440 | 17030.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79384.426 | 79384.426 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.282813 | 1.50592724 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 79384.43 | 79384.43 | 1.0000 | 1.50592724 | 1.282813 | -12.46 | -12.46 | 0.00141622 | -9011.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79384.43 | -16.30 | 0.00092409 | -16.30 | 1.14133354 | 88.9711 | 18.52 | 0.00538624 | 18.29 | 0.00538624 | 40.3287 | 717.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.91 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3569.17 | 5388.50 | 2040.33 |
KITCHEN | 4928.50 | 6209.33 | 4144.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4944.33 | 6774.83 | 4161.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 104.33 | 20.67 | 0.00 | 1.00 |
KITCHEN | 0.00 | 127.67 | 0.00 | 0.33 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 104.33 | 145.00 | 0.00 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.631 | 4.416 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.014 | 0.074 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.047 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.092 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 14539485.12 | 0.00 | 14539485.12 | 11229322.41 | 25768807.54 | 13120747.55 | 1422.84 | 5873.75 | 1463.42 | 429.07 |
KITCHEN | 31164166.77 | 0.00 | 31164166.77 | 313866.10 | 31478032.86 | 35993094.65 | 1433.49 | 5896.57 | 1429.93 | 488.84 |
Total Facility | 45703651.89 | 0.00 | 45703651.89 | 11543188.51 | 57246840.40 | 49113842.20 | 1455.03 | 6203.94 | 1776.39 | 726.21 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5458 | 0.0000 | 0.5458 | 0.4291 | 0.9749 | 0.4161 | 0.00 | 5763.28 | 1423.72 |
KITCHEN | 1.1676 | 0.0000 | 1.1676 | 0.0072 | 1.1748 | 1.1413 | 0.00 | 5792.11 | 1394.89 |
Total Facility | 1.7134 | 0.0000 | 1.7134 | 0.4363 | 2.1497 | 1.5574 | 0.00 | 6083.81 | 1715.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 20036857.64 | 0.00 | 20036857.64 | 13120747.55 | 1416.23 | 0.92 | 7342.84 | 429.07 |
PSZ-AC_2:2 | 42947358.22 | 0.00 | 42947358.22 | 35993094.65 | 1416.75 | 0.80 | 7342.45 | 488.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7522 | 0.0000 | 0.7522 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.6091 | 0.0000 | 1.6091 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1039.37 | 708.09 | 5868.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 1558.04 | 6117.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.8410 | 1.0778 | 0.5735 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7585 | 1.5731 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
Electricity:Building | 349.57 | 3129.39 | 01-JAN-01:10 | 20656.41 | 02-JAN-11:10 |
Electricity:Zone:DINING | 99.41 | 510.40 | 01-JAN-01:10 | 5368.82 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 331.71 | 2720.35 | 01-JAN-01:10 | 17140.31 | 02-JAN-11:10 |
InteriorLights:Electricity | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 29.00 | 239.05 | 01-JAN-01:10 | 1434.30 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 29.00 | 239.05 | 01-JAN-01:10 | 1434.30 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 54.83 | 452.05 | 01-JAN-01:10 | 2712.27 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 250.16 | 2618.99 | 01-JAN-01:10 | 15287.58 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 25.84 | 212.99 | 01-JAN-01:10 | 1277.97 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 25.84 | 212.99 | 01-JAN-01:10 | 1277.97 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 63.00 | 1035.59 | 09-JAN-23:30 | 4592.33 | 02-JUN-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 45.14 | 779.94 | 08-FEB-23:10 | 2552.36 | 21-JUL-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.07 | 0.00 | 01-JAN-11:10 | 1476.12 | 21-JUL-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 29.07 | 701.41 | 07-FEB-00:20 | 1076.23 | 14-MAR-12:10 |
ElectricityPurchased:Facility | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
ElectricityPurchased:Plant | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
Cogeneration:ElectricityPurchased | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
General:Cogeneration:ElectricityPurchased | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
ElectricityNet:Plant | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
Cogeneration:ElectricityNet | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
General:Cogeneration:ElectricityNet | 604.21 | 6738.01 | 07-FEB-01:10 | 42016.09 | 20-JUL-11:20 |
Electricity:HVAC | 168.26 | 0.00 | 01-JAN-01:10 | 23603.94 | 27-JUN-13:00 |
Fans:Electricity | 128.32 | 0.00 | 01-JAN-01:10 | 4761.89 | 01-JAN-00:10 |
General:Fans:Electricity | 128.32 | 0.00 | 01-JAN-01:10 | 4761.89 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 39.94 | 0.00 | 01-JAN-00:10 | 18842.06 | 27-JUN-13:00 |
General:Cooling:Electricity | 39.94 | 0.00 | 01-JAN-00:10 | 18842.06 | 27-JUN-13:00 |
ExteriorLights:Electricity | 41.24 | 0.00 | 01-JAN-08:00 | 2625.88 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 41.24 | 0.00 | 01-JAN-08:00 | 2625.88 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAY-17:50 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 10-MAY-17:50 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1190.29 | 2560.65 | 02-JAN-01:20 | 142514.46 | 06-FEB-14:00 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 492.02 | 0.00 | 01-JAN-01:10 | 106670.51 | 06-FEB-20:10 |
Heating:NaturalGas | 492.02 | 0.00 | 01-JAN-01:10 | 106670.51 | 06-FEB-20:10 |
General:Heating:NaturalGas | 492.02 | 0.00 | 01-JAN-01:10 | 106670.51 | 06-FEB-20:10 |
NaturalGas:Plant | 221.11 | 722.00 | 02-JAN-01:20 | 28006.41 | 13-FEB-13:30 |
WaterSystems:NaturalGas | 221.11 | 722.00 | 02-JAN-01:20 | 28006.41 | 13-FEB-13:30 |
Water Heater:WaterSystems:NaturalGas | 221.11 | 722.00 | 02-JAN-01:20 | 28006.41 | 13-FEB-13:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUL-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1250.04 | 2741.04 | 07-FEB-01:10 | 139358.23 | 06-FEB-21:00 |
EnergyTransfer:Building | 498.49 | 1370.52 | 07-FEB-01:10 | 46424.66 | 06-FEB-12:10 |
EnergyTransfer:Zone:KITCHEN | 346.39 | 1370.52 | 07-FEB-01:10 | 24885.78 | 05-SEP-04:10 |
Refrigeration:EnergyTransfer | 144.54 | 2699.61 | 08-FEB-23:10 | 7834.84 | 08-JUN-10:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.27 | 1349.81 | 08-FEB-23:10 | 3917.42 | 08-JUN-10:40 |
General:Refrigeration:EnergyTransfer | 72.27 | 1349.81 | 08-FEB-23:10 | 3917.42 | 08-JUN-10:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.27 | 1349.81 | 08-FEB-23:10 | 3917.42 | 08-JUN-10:40 |
EnergyTransfer:Plant | 223.59 | 1349.81 | 29-JAN-23:10 | 23091.46 | 14-MAR-12:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.29 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.98 | 1114.23 | 07-FEB-00:20 | 2238.70 | 14-MAR-12:10 |
EnergyTransfer:Zone:DINING | 152.10 | 0.00 | 01-JAN-01:10 | 33413.37 | 06-FEB-21:00 |
Heating:EnergyTransfer | 98.13 | 0.00 | 01-JAN-00:10 | 33413.37 | 06-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 98.11 | 0.00 | 01-JAN-00:10 | 33413.37 | 06-FEB-21:00 |
General:Heating:EnergyTransfer | 98.13 | 0.00 | 01-JAN-00:10 | 33413.37 | 06-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 98.11 | 0.00 | 01-JAN-00:10 | 33413.37 | 06-FEB-21:00 |
Cooling:EnergyTransfer | 328.08 | 0.00 | 01-JAN-01:10 | 31458.58 | 21-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 53.98 | 0.00 | 01-JAN-01:10 | 16199.93 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer | 328.08 | 0.00 | 01-JAN-01:10 | 31458.58 | 21-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 53.98 | 0.00 | 01-JAN-01:10 | 16199.93 | 10-AUG-12:00 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1455.74 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 1455.74 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 274.10 | 0.00 | 01-JAN-01:10 | 21039.51 | 05-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 274.10 | 0.00 | 01-JAN-01:10 | 21039.51 | 05-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
PlantLoopHeatingDemand:Plant | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
WaterSystems:PlantLoopHeatingDemand | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
General:WaterSystems:PlantLoopHeatingDemand | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
EnergyTransfer:HVAC | 527.96 | 0.00 | 01-JAN-01:10 | 85336.41 | 06-FEB-20:10 |
HeatingCoils:EnergyTransfer | 393.62 | 0.00 | 01-JAN-01:10 | 85336.41 | 06-FEB-20:10 |
CoolingCoils:EnergyTransfer | 134.34 | 0.00 | 01-JAN-00:10 | 70247.62 | 27-JUN-13:00 |
WaterSystems:EnergyTransfer | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
WaterUse:WaterSystems:EnergyTransfer | 151.32 | 0.00 | 01-JAN-00:10 | 20672.25 | 12-FEB-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 98.114 | -53.983 | 0.000 | 0.000 | 72.086 | 28.996 | 52.814 | 21.257 | 0.000 | 2.639 | 0.001 | 0.000 | -16.561 | 0.000 | -171.521 | -33.841 |
KITCHEN | 0.000 | 0.000 | 0.020 | -274.092 | 0.000 | 0.000 | 5.180 | 25.835 | 212.059 | 0.000 | 0.000 | 0.015 | 36.755 | 0.000 | 0.000 | 0.000 | -5.772 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.868 | 10.311 | 0.000 | 0.000 | 0.000 | -13.179 | -0.000 |
Total Facility | 0.000 | 0.000 | 98.133 | -328.074 | 0.000 | 0.000 | 77.266 | 54.831 | 264.873 | 21.257 | 0.000 | 5.522 | 47.067 | 0.000 | -16.561 | 0.000 | -190.472 | -33.842 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 13-AUG-02:61 | 0.00 | 0.00 | 0.00 | -40317.97 | 0.00 | 0.00 | 0.00 | 239.05 | 203.51 | 0.00 | 0.00 | 0.00 | 40746.01 | 0.00 | -740.21 | 0.00 | -130.39 | 0.00 |
KITCHEN | 11-DEC-05:01 | 0.00 | 0.00 | 0.00 | -48815.21 | 0.00 | 0.00 | 22.57 | 283.99 | 5273.28 | 0.00 | 0.00 | 0.00 | 43341.49 | 0.00 | -0.00 | 0.00 | -106.12 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-AUG-02:61 | 0.00 | 0.00 | 0.00 | -79303.76 | 0.00 | 0.00 | 0.00 | 452.05 | 2222.04 | 0.00 | 0.00 | 253.08 | 77475.24 | 0.00 | -740.21 | 0.00 | -358.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 08-FEB-03:01 | 0.00 | 0.00 | 45360.86 | 0.00 | 0.00 | 0.00 | 0.00 | 239.05 | 203.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1340.04 | 0.00 | -1579.98 | -42883.41 |
KITCHEN | 07-FEB-05:02 | 0.00 | 0.00 | 11637.74 | 0.00 | 0.00 | 0.00 | 23.61 | 283.99 | 5273.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -462.79 | -16755.83 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 08-FEB-03:01 | 0.00 | 0.00 | 45360.86 | 0.00 | 0.00 | 0.00 | 0.00 | 452.05 | 2222.04 | 0.00 | 0.00 | 67.74 | 0.00 | 0.00 | -1340.04 | 0.00 | -3283.38 | -43479.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9072 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9072 | 0.2181 | 1.0000 | Not calculated | 0.4161 | 0.2181 | ||
PSZ-AC_2:2 | 1.2828 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2828 | 0.1179 | 1.0000 | Not calculated | 0.1513 | 0.1179 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9072 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9072 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2181 | ||
PSZ-AC_2:2 | 1.2828 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2828 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1179 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9072 | 1.9072 | 1.9072 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2828 | 1.2828 | 1.2828 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9072 | 1.9072 | 1.9072 | 1.9072 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2828 | 1.2828 | 1.2828 | 1.2828 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9072 | 1.9072 | 1.9072 | No | 0.4161 | 0.8804 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2828 | 1.2828 | 1.2828 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9072 | 1.9072 | 1.9072 | 1.9072 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2828 | 1.2828 | 1.2828 | 1.2828 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 1.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 492.02 | 106670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 39.94 | 18842.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 54.83 | 2712.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 41.24 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 128.32 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 221.11 | 28006.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.07 | 1476.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 29.07 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 339.88 | 604.21 |
Natural Gas | 477.16 | 1190.29 |
Additional | 0.00 | 0.00 |
Total | 817.04 | 1794.50 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 235.99 |
Space Heating | 0.00 |
Space Cooling | 171.90 |
Fans (All) | 552.29 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2600.53 |
Subtotal | 2600.53 |
Natural Gas [MJ/m2] | |
Space Heating | 2117.67 |
Service Water Heating | 951.63 |
Miscellaneous (All) | 5122.98 |
Subtotal | 5122.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.06 |
Space Heating | 27.42 |
Space Cooling | 2.23 |
Fans (All) | 7.15 |
Service Water Heating | 12.32 |
Receptacle Equipment | 42.02 |
Miscellaneous | 5.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 5084. | 8760. |
LTG_SCH_KITCHEN | 5084. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8368.17 | 378.00 | 13.83 | 0.00 | 0.00 |
ATTIC | 7216.17 | 478.50 | 481.50 | 512.17 | 71.67 |
Min | 7216.17 | 26.67 | 0.00 | 0.00 | 0.00 |
Max | 8733.33 | 478.50 | 481.50 | 512.17 | 71.67 |
Average | 8105.89 | 294.39 | 165.11 | 170.72 | 23.89 |
Sum | 24317.67 | 883.17 | 495.33 | 512.17 | 71.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254697.67 | 27.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16255.00 | 3.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254697.67 | 27.33 | 0.00 | 0.00 | 0.00 |
Average | 90317.56 | 10.11 | 0.00 | 0.00 | 0.00 |
Sum | 270952.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8065.67 | 694.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6900.17 | 1858.00 | 1.83 | 0.00 | 0.00 |
ATTIC | 7132.50 | 875.67 | 291.00 | 245.33 | 215.50 |
Min | 6900.17 | 694.33 | 0.00 | 0.00 | 0.00 |
Max | 8065.67 | 1858.00 | 291.00 | 245.33 | 215.50 |
Average | 7366.11 | 1142.67 | 97.61 | 81.78 | 71.83 |
Sum | 22098.33 | 3428.00 | 292.83 | 245.33 | 215.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 235711.67 | 19013.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12764.17 | 3493.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 235711.67 | 19013.33 | 0.00 | 0.00 | 0.00 |
Average | 82825.28 | 7502.39 | 0.00 | 0.00 | 0.00 |
Sum | 248475.83 | 22507.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:28:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588387E+09 | 13544.42 | 25-JAN-05:02 | -9.1 | -10.7 | 0.444898E+10 | 3723.61 | 28-JAN-19:10 | -7.1 | -8.8 |
February | 0.569901E+09 | 17663.18 | 07-FEB-03:42 | -16.0 | -16.5 | 0.402705E+10 | 3723.62 | 25-FEB-19:30 | -6.7 | -7.8 |
March | 0.115706E+10 | 12704.02 | 01-MAR-05:02 | -8.3 | -9.0 | 0.456074E+10 | 4414.13 | 14-MAR-11:00 | 23.90 | 17.56 |
April | 0.129074E+10 | 8091.85 | 16-APR-23:01 | -2.9 | -4.7 | 0.441466E+10 | 4489.86 | 08-APR-18:10 | -2.9 | -4.7 |
May | 0.356185E+10 | 34526.41 | 24-MAY-02:61 | 18.95 | 14.13 | 0.491500E+10 | 4681.97 | 13-MAY-18:19 | 18.95 | 14.13 |
June | 0.887391E+10 | 29774.37 | 21-JUN-02:62 | 18.22 | 15.26 | 0.516184E+10 | 4681.82 | 17-JUN-18:00 | 18.22 | 15.26 |
July | 0.136844E+11 | 36291.53 | 13-JUL-02:61 | 14.72 | 12.91 | 0.539541E+10 | 4681.85 | 22-JUL-18:00 | 21.70 | 19.38 |
August | 0.127447E+11 | 40344.52 | 13-AUG-02:61 | 14.50 | 11.66 | 0.541700E+10 | 4681.83 | 26-AUG-18:49 | 22.30 | 20.12 |
September | 0.742449E+10 | 39710.45 | 23-SEP-02:61 | 14.32 | 11.53 | 0.503436E+10 | 4681.82 | 16-SEP-18:00 | 14.32 | 11.53 |
October | 0.247764E+10 | 35717.48 | 23-OCT-02:61 | 16.60 | 13.37 | 0.466142E+10 | 4593.26 | 21-OCT-18:10 | 16.60 | 13.37 |
November | 0.987745E+09 | 7540.29 | 23-NOV-00:01 | -1.6 | -2.4 | 0.436061E+10 | 4414.04 | 16-NOV-12:50 | -1.6 | -2.4 |
December | 0.622418E+09 | 19952.56 | 11-DEC-03:53 | -17.2 | -17.3 | 0.444787E+10 | 3723.61 | 23-DEC-19:10 | 3.90 | 1.49 |
Annual Sum or Average | 0.539832E+11 | 0.568449E+11 | ||||||||
Minimum of Months | 0.569901E+09 | 7540.29 | -17.2 | -17.3 | 0.402705E+10 | 3723.61 | -7.1 | -8.8 | ||
Maximum of Months | 0.136844E+11 | 40344.52 | 18.95 | 15.26 | 0.541700E+10 | 4681.97 | 23.90 | 20.12 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204712E+11 | 45672.29 | 10-JAN-05:01 | -13.3 | -14.3 | 0.768497E+10 | 5050.25 | 11-JAN-11:00 | 9.40 | 8.22 |
February | 0.181196E+11 | 43765.08 | 28-FEB-05:01 | -11.2 | -11.6 | 0.694194E+10 | 5039.33 | 14-FEB-11:00 | -11.2 | -11.6 |
March | 0.215227E+11 | 45445.42 | 07-MAR-05:01 | -13.3 | -13.9 | 0.770396E+10 | 5138.41 | 15-MAR-10:50 | 23.62 | 15.52 |
April | 0.219838E+11 | 38475.86 | 09-APR-02:61 | 12.20 | 10.62 | 0.746496E+10 | 5131.64 | 07-APR-10:00 | 12.20 | 10.62 |
May | 0.229813E+11 | 46647.24 | 18-MAY-02:61 | 8.48 | 6.22 | 0.778754E+10 | 5138.44 | 31-MAY-10:50 | 19.22 | 14.13 |
June | 0.236949E+11 | 47751.52 | 04-JUN-02:61 | 9.22 | 6.15 | 0.759265E+10 | 5140.54 | 27-JUN-10:00 | 28.30 | 22.79 |
July | 0.254529E+11 | 38195.81 | 12-JUL-02:11 | 15.03 | 12.21 | 0.785879E+10 | 5141.39 | 20-JUL-10:00 | 29.40 | 22.73 |
August | 0.257563E+11 | 41827.07 | 03-AUG-02:61 | 11.70 | 10.11 | 0.785888E+10 | 5138.87 | 15-AUG-10:50 | 26.70 | 22.40 |
September | 0.244154E+11 | 47404.89 | 05-SEP-04:01 | 6.70 | 6.12 | 0.757701E+10 | 5138.43 | 12-SEP-10:00 | 20.60 | 13.52 |
October | 0.250169E+11 | 47852.29 | 03-OCT-03:21 | 5.00 | 5.00 | 0.773788E+10 | 5138.41 | 11-OCT-10:00 | 19.40 | 13.65 |
November | 0.232734E+11 | 37791.63 | 27-NOV-03:01 | 15.87 | 10.38 | 0.745272E+10 | 5137.34 | 16-NOV-11:00 | 15.87 | 10.38 |
December | 0.214093E+11 | 48848.39 | 11-DEC-05:01 | -17.5 | -18.0 | 0.768539E+10 | 5095.54 | 01-DEC-11:00 | -17.5 | -18.0 |
Annual Sum or Average | 0.274098E+12 | 0.913467E+11 | ||||||||
Minimum of Months | 0.181196E+11 | 37791.63 | -17.5 | -18.0 | 0.694194E+10 | 5039.33 | -17.5 | -18.0 | ||
Maximum of Months | 0.257563E+11 | 48848.39 | 15.87 | 12.21 | 0.785888E+10 | 5141.39 | 29.40 | 22.79 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231449E+11 | 45055.42 | 12-JAN-03:01 | -5.8 |
February | 0.219062E+11 | 45362.47 | 08-FEB-03:01 | -5.3 |
March | 0.137914E+11 | 42395.53 | 20-MAR-02:61 | -2.2 |
April | 0.603708E+10 | 39221.15 | 16-APR-02:61 | 0.32 |
May | 0.749684E+09 | 8474.70 | 24-MAY-02:02 | 18.95 |
June | 53996280.82 | 9416.92 | 21-JUN-02:03 | 18.22 |
July | 20981254.44 | 8750.59 | 26-JUL-02:30 | 21.15 |
August | 14337130.28 | 14055.34 | 18-AUG-02:03 | 16.70 |
September | 0.118391E+09 | 8467.81 | 23-SEP-02:02 | 14.32 |
October | 0.329627E+10 | 12410.85 | 16-OCT-20:00 | 1.10 |
November | 0.792371E+10 | 18193.64 | 24-NOV-03:02 | -2.9 |
December | 0.210568E+11 | 44928.43 | 09-DEC-03:01 | -0.5 |
Annual Sum or Average | 0.981138E+11 | |||
Minimum of Months | 14337130.28 | 8467.81 | -5.8 | |
Maximum of Months | 0.231449E+11 | 45362.47 | 21.15 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4253390.85 | 8504.33 | 13-JAN-05:03 | -7.8 |
February | 7209115.95 | 11645.95 | 07-FEB-05:02 | -15.7 |
March | 2152611.99 | 7997.68 | 06-MAR-05:02 | -11.1 |
April | 851222.13 | 9184.80 | 17-APR-04:03 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 51655.09 | 688.73 | 19-JUL-23:01 | 26.60 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 53025.84 | 883.76 | 18-OCT-04:04 | 1.70 |
November | 53390.32 | 889.84 | 12-NOV-05:04 | 1.70 |
December | 5148948.57 | 11586.81 | 27-DEC-05:02 | -11.6 |
Annual Sum or Average | 19773360.74 | |||
Minimum of Months | 0.00 | 0.00 | -15.7 | |
Maximum of Months | 7209115.95 | 11645.95 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.245008E+10 | 1434.30 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.221916E+10 | 1434.30 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.248909E+10 | 1434.30 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.238066E+10 | 1434.30 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.246959E+10 | 1434.30 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.240590E+10 | 1434.30 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.244463E+10 | 1434.30 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.248909E+10 | 1434.30 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.238123E+10 | 1434.30 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.244979E+10 | 1434.30 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.237177E+10 | 1434.30 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.244492E+10 | 1434.30 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.289959E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.221916E+10 | 1434.30 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.248909E+10 | 1434.30 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.218303E+10 | 1277.97 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.197727E+10 | 1277.97 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.221779E+10 | 1277.97 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.212117E+10 | 1277.97 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.220041E+10 | 1277.97 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.214367E+10 | 1277.97 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.217817E+10 | 1277.97 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.221779E+10 | 1277.97 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.212169E+10 | 1277.97 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.218277E+10 | 1277.97 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.211325E+10 | 1277.97 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.217843E+10 | 1277.97 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.258354E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.197727E+10 | 1277.97 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.221779E+10 | 1277.97 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.245008E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290272E+11 |
February | 0.852256E+10 | 0.221916E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271164E+11 |
March | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20922231.66 | 0.212105E+11 |
April | 0.915225E+10 | 0.238066E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142903E+11 |
May | 0.947560E+10 | 0.246959E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13373128.35 | 0.836193E+10 |
June | 0.922788E+10 | 0.240590E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429319E+09 | 0.429324E+10 |
July | 0.939996E+10 | 0.244463E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117756E+10 | 0.170245E+10 |
August | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927661E+09 | 0.275846E+10 |
September | 0.915225E+10 | 0.238123E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69810019.42 | 0.596050E+10 |
October | 0.940563E+10 | 0.244979E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127111E+11 |
November | 0.909363E+10 | 0.237177E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165636E+11 |
December | 0.939996E+10 | 0.244492E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275250E+11 |
Annual Sum or Average | 0.111326E+12 | 0.289959E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263865E+10 | 0.171521E+12 |
Minimum of Months | 0.852256E+10 | 0.221916E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170245E+10 |
Maximum of Months | 0.954557E+10 | 0.248909E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117756E+10 | 0.290272E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.218303E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908914E+09 |
February | 0.610713E+09 | 0.197727E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962127E+09 |
March | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594226E+09 |
April | 0.655836E+09 | 0.212117E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450584E+09 |
May | 0.679007E+09 | 0.220041E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284294E+09 |
June | 0.661256E+09 | 0.214367E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2468035.05 | 0.217916E+09 |
July | 0.673587E+09 | 0.217817E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 7148328.06 | 0.134240E+09 |
August | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 5348877.63 | 0.153039E+09 |
September | 0.655836E+09 | 0.212169E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 184064.90 | 0.206948E+09 |
October | 0.673993E+09 | 0.218277E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383706E+09 |
November | 0.651635E+09 | 0.211325E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523712E+09 |
December | 0.673587E+09 | 0.217843E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952754E+09 |
Annual Sum or Average | 0.797748E+10 | 0.258354E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 15149305.65 | 0.577246E+10 |
Minimum of Months | 0.610713E+09 | 0.197727E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134240E+09 |
Maximum of Months | 0.684021E+09 | 0.221779E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 7148328.06 | 0.962127E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270036E+09 | 0.502666E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204647E+09 | 0.721843E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293321E+09 | 0.113018E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209570E+09 | 0.139071E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231435E+09 | 0.163116E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198890E+09 | 0.180635E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194833E+09 | 0.173981E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201536E+09 | 0.148993E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269921E+09 | 0.112618E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272665E+09 | 0.763458E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281414E+09 | 0.436656E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239443E+09 | 0.439912E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286771E+10 | 0.131788E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194833E+09 | 0.436656E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293321E+09 | 0.180635E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 1434.30 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 34295.12 | 30-JAN-18:55 |
February | 9454.80 | 04-FEB-19:10 | 1434.30 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37295.55 | 06-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 1434.30 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.66 | 15-MAR-14:00 | 32310.72 | 06-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 1434.30 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 19781.55 | 16-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 1434.30 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1074.11 | 10-MAY-14:00 | 11294.28 | 11-MAY-19:00 |
June | 9454.80 | 03-JUN-18:10 | 1434.30 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.05 | 27-JUN-12:00 | 10368.39 | 13-JUN-12:00 |
July | 9454.80 | 01-JUL-18:10 | 1434.30 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5300.66 | 21-JUL-12:00 | 4476.22 | 06-JUL-19:54 |
August | 9454.80 | 05-AUG-18:10 | 1434.30 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5293.39 | 10-AUG-12:00 | 7849.54 | 30-AUG-17:55 |
September | 9454.80 | 02-SEP-18:10 | 1434.30 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1974.80 | 16-SEP-13:00 | 9523.39 | 28-SEP-17:10 |
October | 9454.80 | 07-OCT-18:10 | 1434.30 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 19255.33 | 16-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 1434.30 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 22133.39 | 22-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 1434.30 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 37821.72 | 11-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 1434.30 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4476.22 | |||||
Maximum of Months | 9454.80 | 1434.30 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 5305.05 | 37821.72 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 1277.97 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2696.42 | 12-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 1277.97 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2682.51 | 13-FEB-03:52 |
March | 677.52 | 04-MAR-19:10 | 1277.97 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1768.25 | 02-MAR-05:00 |
April | 677.52 | 01-APR-18:10 | 1277.97 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1732.78 | 16-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 1277.97 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 731.27 | 30-MAY-04:00 |
June | 677.52 | 03-JUN-18:10 | 1277.97 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 57.52 | 12-JUN-13:10 | 1114.73 | 13-JUN-03:30 |
July | 677.52 | 01-JUL-18:10 | 1277.97 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 152.79 | 21-JUL-03:00 | 871.48 | 06-JUL-02:00 |
August | 677.52 | 05-AUG-18:10 | 1277.97 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 64.82 | 13-AUG-13:00 | 539.65 | 27-AUG-02:10 |
September | 677.52 | 02-SEP-18:10 | 1277.97 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 19.91 | 17-SEP-02:25 | 1056.60 | 29-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 1277.97 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 981.77 | 07-OCT-02:00 |
November | 677.52 | 04-NOV-18:10 | 1277.97 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1796.04 | 17-NOV-04:40 |
December | 677.52 | 02-DEC-19:10 | 1277.97 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2265.89 | 26-DEC-04:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 1277.97 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 539.65 | ||||||
Maximum of Months | 677.52 | 1277.97 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 152.79 | 2696.42 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.89 | 10-JAN-07:50 | 1519.11 | 30-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.65 | 14-FEB-19:55 | 2107.37 | 08-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.26 | 08-MAR-07:13 | 2372.54 | 07-MAR-13:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.07 | 07-APR-04:55 | 2716.51 | 06-APR-12:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.50 | 27-MAY-05:05 | 2509.27 | 08-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.29 | 12-JUN-00:01 | 2535.43 | 10-JUN-12:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.03 | 13-JUL-02:00 | 2488.00 | 03-JUL-12:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.26 | 12-AUG-03:00 | 2296.75 | 16-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.11 | 10-SEP-22:30 | 2183.83 | 10-SEP-13:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.21 | 09-OCT-22:55 | 1766.24 | 17-OCT-13:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.17 | 10-NOV-06:55 | 1266.61 | 24-NOV-13:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.40 | 16-DEC-08:00 | 1391.80 | 10-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.26 | 1266.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.07 | 2716.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13544.42 | 25-JAN-05:02 | 5252.67 | 3187.34 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.81 |
February | 17663.18 | 07-FEB-03:42 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.01 |
March | 12704.02 | 01-MAR-05:02 | 5252.67 | 3187.34 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.41 |
April | 8091.85 | 16-APR-23:01 | 4727.40 | 2151.46 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.80 |
May | 34526.41 | 24-MAY-02:61 | 0.00 | 2151.46 | 2442.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.93 |
June | 29774.37 | 21-JUN-02:62 | 0.00 | 1434.30 | 1628.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.86 |
July | 36291.53 | 13-JUL-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
August | 40344.52 | 13-AUG-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.39 |
September | 39710.45 | 23-SEP-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.55 |
October | 35717.48 | 23-OCT-02:61 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.28 |
November | 7540.29 | 23-NOV-00:01 | 4202.13 | 2549.87 | 3256.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.97 |
December | 19952.56 | 11-DEC-03:53 | 0.00 | 2390.51 | 2713.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7540.29 | 0.00 | 1434.30 | 1628.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | |
Maximum of Months | 40344.52 | 5252.67 | 3187.34 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1733.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 45672.29 | 10-JAN-05:01 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 205.20 |
February | 43765.08 | 28-FEB-05:01 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 168.90 |
March | 45445.42 | 07-MAR-05:01 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 155.19 |
April | 38475.86 | 09-APR-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 485.22 |
May | 46647.24 | 18-MAY-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 47751.52 | 04-JUN-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 264.08 |
July | 38195.81 | 12-JUL-02:11 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 310.05 |
August | 41827.07 | 03-AUG-02:61 | 0.00 | 2129.95 | 18081.45 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 307.34 |
September | 47404.89 | 05-SEP-04:01 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 51.45 |
October | 47852.29 | 03-OCT-03:21 | 0.00 | 1490.96 | 17282.92 | 9652.92 | 0.00 | 0.00 | 0.00 | 0.00 | 334.96 |
November | 37791.63 | 27-NOV-03:01 | 0.00 | 1916.95 | 16273.31 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 392.61 |
December | 48848.39 | 11-DEC-05:01 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 106.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 37791.63 | 0.00 | 1490.96 | 16273.31 | 4964.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48848.39 | 376.40 | 2839.93 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 485.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.62 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.50 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.72 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.67 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.92 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.60 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.07 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.15 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.45 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.50 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.482749E+11 | 26324.61 | 11-JAN-11:20 | 0.175379E+12 | 131531.51 | 31-JAN-13:50 |
February | 0.433398E+11 | 26309.44 | 01-FEB-11:09 | 0.164749E+12 | 142514.46 | 06-FEB-13:00 |
March | 0.481109E+11 | 31864.22 | 15-MAR-10:00 | 0.131393E+12 | 119292.46 | 06-MAR-20:30 |
April | 0.457180E+11 | 26372.30 | 20-APR-10:20 | 0.894321E+11 | 94574.96 | 16-APR-12:09 |
May | 0.481454E+11 | 31360.44 | 10-MAY-12:00 | 0.643960E+11 | 56704.93 | 11-MAY-12:50 |
June | 0.533389E+11 | 41631.87 | 27-JUN-11:20 | 0.571113E+11 | 52491.43 | 13-JUN-12:50 |
July | 0.633424E+11 | 42016.09 | 20-JUL-11:20 | 0.575239E+11 | 48919.86 | 01-JUL-12:39 |
August | 0.598615E+11 | 41062.37 | 15-AUG-10:20 | 0.573139E+11 | 48512.26 | 01-AUG-12:39 |
September | 0.507790E+11 | 37663.33 | 15-SEP-11:20 | 0.568050E+11 | 50391.44 | 29-SEP-12:50 |
October | 0.482900E+11 | 27417.53 | 11-OCT-12:00 | 0.768087E+11 | 73819.46 | 17-OCT-07:10 |
November | 0.466757E+11 | 26399.03 | 10-NOV-11:09 | 0.962488E+11 | 82112.40 | 28-NOV-13:20 |
December | 0.483376E+11 | 26386.94 | 01-DEC-11:09 | 0.163127E+12 | 134760.25 | 11-DEC-20:10 |
Annual Sum or Average | 0.604214E+12 | 0.119029E+13 | ||||
Minimum of Months | 0.433398E+11 | 26309.44 | 0.568050E+11 | 48512.26 | ||
Maximum of Months | 0.633424E+11 | 42016.09 | 0.175379E+12 | 142514.46 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.463311E+10 | 0.433113E+10 | 0.235157E+11 | 0.00 | 0.107945E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419643E+10 | 0.361426E+10 | 0.212400E+11 | 0.00 | 0.977713E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470688E+10 | 0.359063E+10 | 0.235157E+11 | 0.00 | 0.107675E+11 | 0.80 | 0.00 | 0.415136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.450183E+10 | 0.305968E+10 | 0.227571E+11 | 0.00 | 0.103665E+11 | 0.77 | 0.00 | 20912407.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466999E+10 | 0.279656E+10 | 0.235157E+11 | 0.00 | 0.108502E+11 | 0.80 | 0.00 | 0.849013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.454957E+10 | 0.253030E+10 | 0.227571E+11 | 0.00 | 0.107216E+11 | 0.77 | 0.00 | 0.725205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.462280E+10 | 0.268470E+10 | 0.235157E+11 | 0.00 | 0.112423E+11 | 0.79 | 0.00 | 0.154672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.470688E+10 | 0.299823E+10 | 0.235157E+11 | 0.00 | 0.112083E+11 | 0.80 | 0.00 | 0.116464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450292E+10 | 0.329600E+10 | 0.227571E+11 | 0.00 | 0.106709E+11 | 0.77 | 0.00 | 0.407479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463256E+10 | 0.383168E+10 | 0.235157E+11 | 0.00 | 0.108037E+11 | 0.79 | 0.00 | 0.203284E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.448502E+10 | 0.407747E+10 | 0.227571E+11 | 0.00 | 0.103710E+11 | 0.77 | 0.00 | 11675622.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462334E+10 | 0.443038E+10 | 0.235157E+11 | 0.00 | 0.107462E+11 | 0.79 | 0.00 | 347010.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548313E+11 | 0.412410E+11 | 0.276879E+12 | 0.00 | 0.128320E+12 | 9.37 | 0.00 | 0.399408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.419643E+10 | 0.253030E+10 | 0.212400E+11 | 0.00 | 0.977713E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.470688E+10 | 0.443038E+10 | 0.235157E+11 | 0.00 | 0.112423E+11 | 0.80 | 0.00 | 0.154672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.114313E+12 | 0.00 | 0.205411E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.109360E+12 | 0.00 | 0.187853E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.702950E+11 | 0.00 | 0.205724E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.310340E+11 | 0.00 | 0.191797E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.506744E+10 | 0.00 | 0.188029E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.687243E+09 | 0.00 | 0.172056E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 12481831.49 | 0.00 | 0.169857E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 30343412.88 | 0.00 | 0.167578E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.112723E+10 | 0.00 | 0.164594E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.184796E+11 | 0.00 | 0.178034E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.388127E+11 | 0.00 | 0.182176E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.102807E+12 | 0.00 | 0.197945E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.492025E+12 | 0.00 | 0.221105E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 12481831.49 | 0.00 | 0.164594E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.114313E+12 | 0.00 | 0.205724E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2712.27 | 02-JAN-10:09 | 2625.88 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 4761.89 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2712.27 | 01-FEB-10:09 | 2625.88 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 4761.89 | 01-FEB-00:40 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 2712.27 | 01-MAR-10:09 | 2625.88 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 4761.89 | 01-MAR-00:30 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 2712.27 | 01-APR-16:10 | 2625.88 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 4761.89 | 01-APR-04:10 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 2712.27 | 01-MAY-09:09 | 2625.88 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 4761.89 | 01-MAY-04:40 | 0.00 | 10-MAY-17:49 | 0.00 | 01-MAY-00:10 |
June | 2712.27 | 01-JUN-09:09 | 2625.88 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 4761.89 | 01-JUN-10:39 | 0.00 | 01-JUN-11:39 | 0.00 | 01-JUN-00:10 |
July | 2712.27 | 01-JUL-16:10 | 2625.88 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 4761.89 | 01-JUL-09:20 | 0.00 | 15-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 2712.27 | 01-AUG-09:09 | 2625.88 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 4761.89 | 01-AUG-09:20 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2712.27 | 01-SEP-09:09 | 2625.88 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 4761.89 | 01-SEP-12:20 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 2712.27 | 02-OCT-09:09 | 2625.88 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 4761.89 | 01-OCT-19:00 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2712.27 | 01-NOV-09:09 | 2625.88 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 4761.89 | 01-NOV-04:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2712.27 | 01-DEC-10:09 | 2625.88 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 4761.89 | 01-DEC-00:40 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2712.27 | 2625.88 | 14428.03 | 0.00 | 4761.89 | 0.00 | 0.00 | ||||||
Maximum of Months | 2712.27 | 2625.88 | 14428.03 | 0.00 | 4761.89 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8855.59 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2360.40 | 08-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9138.26 | 10-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 18842.06 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18461.32 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17619.19 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14499.19 | 15-SEP-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5193.79 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1467.11 | 27-NOV-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 250.89 | 01-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18842.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 26324.61 | 11-JAN-11:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26309.44 | 01-FEB-11:09 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31864.22 | 15-MAR-10:00 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 7060.78 | 0.00 |
April | 26372.30 | 20-APR-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31360.44 | 10-MAY-12:00 | 2712.27 | 12626.59 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 9123.89 | 0.00 |
June | 41631.87 | 27-JUN-11:20 | 2712.27 | 13527.31 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 17690.32 | 0.00 |
July | 42016.09 | 20-JUL-11:20 | 2712.27 | 13527.31 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 18070.48 | 0.00 |
August | 41062.37 | 15-AUG-10:20 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 14567.84 | 0.00 |
September | 37663.33 | 15-SEP-11:20 | 2712.27 | 13527.31 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 13727.05 | 0.00 |
October | 27417.53 | 11-OCT-12:00 | 2712.27 | 12626.59 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 5193.79 | 0.00 |
November | 26399.03 | 10-NOV-11:09 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26386.94 | 01-DEC-11:09 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 26309.44 | 2712.27 | 12626.59 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42016.09 | 2712.27 | 14428.03 | 0.00 | 0.00 | 4761.89 | 0.00 | 0.00 | 18070.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 94917.25 | 31-JAN-20:10 | 0.00 | 27971.78 | 31-JAN-13:50 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 106670.51 | 06-FEB-20:10 | 0.00 | 28006.41 | 13-FEB-13:30 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 87350.15 | 07-MAR-07:10 | 0.00 | 27974.42 | 01-MAR-13:50 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 59647.08 | 16-APR-06:00 | 0.00 | 27710.35 | 01-APR-12:39 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 33863.24 | 01-MAY-06:10 | 0.00 | 27222.38 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 14410.84 | 14-JUN-06:10 | 0.00 | 26556.99 | 01-JUN-12:30 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2644.64 | 26-JUL-02:30 | 0.00 | 25936.71 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 3754.86 | 06-AUG-02:00 | 0.00 | 25529.11 | 01-AUG-12:39 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 17962.29 | 30-SEP-06:10 | 0.00 | 25906.55 | 30-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 50961.58 | 17-OCT-06:10 | 0.00 | 26536.16 | 30-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 53241.40 | 24-NOV-07:10 | 0.00 | 27198.65 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 105963.23 | 11-DEC-19:00 | 0.00 | 27703.29 | 31-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 2644.64 | 0.00 | 25529.11 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 106670.51 | 0.00 | 28006.41 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 27.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 15.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 6.50 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
May | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.47 | 0.00 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.69 | 0.50 | 24.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.64 | 0.33 | 24.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.68 | 0.17 | 24.68 |
October | 0.83 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
November | 5.50 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
December | 20.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Annual Sum or Average | 104.33 | 19.49 | 0.00 | 19.49 | 20.67 | 20.35 | 1.00 | 20.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 | 19.22 |
Maximum of Months | 27.83 | 20.54 | 0.00 | 20.54 | 9.50 | 24.69 | 0.50 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.50 | 0.00 | 28.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.28 | 0.00 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.03 | 0.00 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 29.53 | 0.00 | 29.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.15 | 0.33 | 30.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 30.23 | 0.00 | 30.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 29.44 | 0.00 | 29.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.99 | 0.00 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.33 | 0.00 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.90 | 0.00 | 26.90 |
Annual Sum or Average | 0.00 | 0.00 | 127.67 | 29.39 | 0.33 | 29.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.23 | 0.33 | 30.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.86 | 401.00 | 20.80 | 401.00 | 20.78 |
February | 551.00 | 20.85 | 355.17 | 20.80 | 355.17 | 20.77 |
March | 584.00 | 20.96 | 211.00 | 20.93 | 187.00 | 20.85 |
April | 561.83 | 21.11 | 90.83 | 21.00 | 86.17 | 20.90 |
May | 428.83 | 21.58 | 124.17 | 21.99 | 19.17 | 21.95 |
June | 248.83 | 22.84 | 427.17 | 23.51 | 124.83 | 23.57 |
July | 257.83 | 23.87 | 574.17 | 23.93 | 237.67 | 23.95 |
August | 203.17 | 23.50 | 536.00 | 23.81 | 151.00 | 23.84 |
September | 259.00 | 22.28 | 362.67 | 23.21 | 73.83 | 23.28 |
October | 505.67 | 21.16 | 102.00 | 21.41 | 27.33 | 21.33 |
November | 569.33 | 21.04 | 75.50 | 20.95 | 67.67 | 20.85 |
December | 609.00 | 20.87 | 309.50 | 20.79 | 309.50 | 20.75 |
Annual Sum or Average | 5388.50 | 21.40 | 3569.17 | 21.86 | 2040.33 | 21.81 |
Minimum of Months | 203.17 | 20.85 | 75.50 | 20.79 | 19.17 | 20.75 |
Maximum of Months | 610.00 | 23.87 | 574.17 | 23.93 | 401.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.74 | 512.83 | 18.72 | 512.83 | 18.71 |
February | 551.00 | 18.74 | 469.17 | 18.72 | 469.17 | 18.71 |
March | 584.17 | 19.20 | 383.00 | 19.25 | 367.67 | 19.21 |
April | 520.50 | 19.29 | 216.50 | 19.44 | 171.50 | 19.29 |
May | 378.00 | 21.85 | 326.33 | 22.98 | 140.83 | 23.20 |
June | 460.67 | 25.32 | 513.33 | 25.47 | 404.50 | 25.63 |
July | 558.17 | 26.08 | 599.67 | 26.01 | 555.67 | 26.04 |
August | 507.00 | 26.00 | 593.00 | 25.86 | 499.33 | 25.93 |
September | 418.50 | 24.75 | 472.50 | 25.04 | 328.00 | 25.29 |
October | 473.17 | 20.04 | 223.33 | 20.84 | 117.00 | 20.90 |
November | 540.67 | 19.04 | 200.50 | 19.24 | 159.67 | 19.14 |
December | 607.50 | 18.74 | 418.33 | 18.71 | 417.83 | 18.69 |
Annual Sum or Average | 6209.33 | 21.29 | 4928.50 | 21.81 | 4144.00 | 21.90 |
Minimum of Months | 378.00 | 18.74 | 200.50 | 18.71 | 117.00 | 18.69 |
Maximum of Months | 610.00 | 26.08 | 599.67 | 26.01 | 555.67 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.85501 | 18.77019 | -0.6299 | 14.30547 |
February | 551.00000 | 20.85434 | 18.94628 | -0.6306 | 14.37865 |
March | 612.00000 | 21.09051 | 28.03917 | -0.4351 | 11.13349 |
April | 590.00000 | 21.23195 | 33.93038 | -0.3191 | 8.79993 |
May | 611.00000 | 22.24021 | 40.25876 | -1.0082 | 30.15331 |
June | 592.00000 | 23.42913 | 50.59802 | -0.4278 | 12.08021 |
July | 609.00000 | 23.87672 | 60.17296 | -0.1577 | 6.39785 |
August | 612.00000 | 23.74377 | 54.54326 | -0.2330 | 7.57414 |
September | 590.00000 | 23.10924 | 51.12423 | -0.5129 | 14.51822 |
October | 610.00000 | 21.59187 | 39.78486 | -0.1166 | 7.61008 |
November | 591.00000 | 21.13854 | 31.80472 | -0.3476 | 8.83176 |
December | 609.00000 | 20.87128 | 22.58439 | -0.5765 | 12.91174 |
Annual Sum or Average | 7187.00000 | 22.01008 | 37.65529 | -0.4487 | 12.39073 |
Minimum of Months | 551.00000 | 20.85434 | 18.77019 | -1.0082 | 6.39785 |
Maximum of Months | 612.00000 | 23.87672 | 60.17296 | -0.1166 | 30.15331 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.73515 | 25.57103 | -0.7549 | 17.74103 |
February | 551.00000 | 18.73999 | 25.94936 | -0.7609 | 17.94144 |
March | 612.00000 | 19.38435 | 34.89305 | -0.5269 | 15.79322 |
April | 590.00000 | 19.82366 | 40.85895 | -0.3645 | 12.22104 |
May | 611.00000 | 22.64540 | 42.67672 | -0.5776 | 24.35416 |
June | 592.00000 | 24.97306 | 48.78335 | 0.30578 | 15.73541 |
July | 609.00000 | 25.87253 | 55.56999 | 0.69495 | 17.38840 |
August | 612.00000 | 25.60894 | 51.36604 | 0.58250 | 15.58907 |
September | 590.00000 | 24.37479 | 49.72055 | 0.13471 | 16.04259 |
October | 610.00000 | 20.82089 | 44.54350 | -0.0450 | 12.31347 |
November | 591.00000 | 19.45340 | 38.45023 | -0.4283 | 12.60710 |
December | 609.00000 | 18.75240 | 29.53752 | -0.7059 | 16.32555 |
Annual Sum or Average | 7187.00000 | 21.61706 | 40.74164 | -0.2004 | 16.17905 |
Minimum of Months | 551.00000 | 18.73515 | 25.57103 | -0.7609 | 12.22104 |
Maximum of Months | 612.00000 | 25.87253 | 55.56999 | 0.69495 | 24.35416 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.639012E+09 | 0.213192E+09 | 18.55 | 0.496068E+09 | 0.142944E+09 | 0.00 | 0.38 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 15159.25 | 14-MAR-13:00 | 11424.62 | 15-MAR-12:00 | 4475.56 | 14-MAR-13:00 | 4905.79 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 6548076.77 | 2324062.34 | 1.92 | 5389446.69 | 1158630.08 | 0.00 | 0.06 | 08-APR-12:55 | 0.00 | 01-APR-00:01 | 2224.84 | 08-APR-12:55 | 1860.79 | 08-APR-13:00 | 364.10 | 08-APR-12:55 | 785.28 | 08-APR-12:55 | 0.00 | 01-APR-00:01 |
May | 0.110578E+10 | 0.376315E+09 | 57.55 | 0.907304E+09 | 0.198480E+09 | 0.00 | 1.00 | 24-MAY-02:61 | 0.00 | 01-MAY-00:01 | 46006.61 | 24-MAY-02:61 | 33475.86 | 24-MAY-02:61 | 12530.75 | 24-MAY-02:61 | 12699.65 | 24-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.107557E+11 | 0.342513E+10 | 254.11 | 0.707916E+10 | 0.367650E+10 | 0.00 | 1.00 | 02-JUN-02:62 | 0.00 | 01-JUN-00:01 | 50145.46 | 18-JUN-02:61 | 30516.69 | 12-JUN-02:62 | 27098.69 | 18-JUN-02:61 | 13019.53 | 18-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.238404E+11 | 0.743778E+10 | 463.09 | 0.145084E+11 | 0.933198E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 51116.37 | 20-JUL-02:61 | 30621.83 | 08-JUL-02:62 | 30486.76 | 29-JUL-03:21 | 13099.61 | 16-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.177765E+11 | 0.564679E+10 | 378.77 | 0.122002E+11 | 0.557633E+10 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 51116.37 | 14-AUG-02:61 | 32847.84 | 20-AUG-02:61 | 29621.67 | 14-AUG-02:02 | 13099.61 | 14-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.559462E+10 | 0.181393E+10 | 169.86 | 0.355228E+10 | 0.204234E+10 | 0.00 | 1.00 | 08-SEP-02:61 | 0.00 | 01-SEP-00:01 | 49752.34 | 16-SEP-02:61 | 31120.06 | 23-SEP-02:61 | 28294.37 | 16-SEP-02:61 | 12988.24 | 16-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.246500E+09 | 84912777.43 | 15.58 | 0.199665E+09 | 46834244.42 | 0.00 | 1.00 | 23-OCT-02:61 | 0.00 | 01-OCT-00:01 | 46006.61 | 23-OCT-02:61 | 30457.95 | 23-OCT-02:61 | 15548.67 | 23-OCT-02:61 | 12699.65 | 23-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 100.98 | 36.15 | 0.14 | 75.06 | 25.91 | 0.00 | 0.00 | 16-NOV-13:33 | 0.00 | 01-NOV-00:01 | 0.27 | 16-NOV-13:33 | 0.20 | 16-NOV-13:33 | 0.06 | 16-NOV-13:33 | 0.10 | 16-NOV-13:33 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.599650E+11 | 0.190004E+11 | 1359.56 | 0.389485E+11 | 0.210166E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.238404E+11 | 0.743778E+10 | 463.09 | 0.145084E+11 | 0.933198E+10 | 0.00 | 1.00 | 0.00 | 51116.37 | 33475.86 | 30486.76 | 13099.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.661459E+09 | 0.201944E+09 | 20.88 | 0.518907E+09 | 0.142553E+09 | 0.00 | 1.00 | 15-MAR-02:61 | 0.00 | 01-MAR-00:01 | 31426.78 | 15-MAR-02:61 | 22637.93 | 16-MAR-03:52 | 14764.34 | 17-MAR-03:21 | 8179.77 | 15-MAR-02:61 | 0.00 | 01-MAR-00:01 |
April | 57089619.55 | 18588344.69 | 8.18 | 44254781.70 | 12834837.84 | 0.00 | 1.00 | 09-APR-02:61 | 0.00 | 01-APR-00:01 | 31426.78 | 09-APR-02:61 | 17955.22 | 09-APR-02:61 | 13471.56 | 09-APR-02:61 | 8179.77 | 09-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.151978E+10 | 0.472698E+09 | 78.70 | 0.120367E+10 | 0.316102E+09 | 0.00 | 1.00 | 11-MAY-02:61 | 0.00 | 01-MAY-00:01 | 31426.78 | 17-MAY-02:61 | 23472.79 | 28-MAY-03:22 | 16487.20 | 29-MAY-03:22 | 8179.77 | 11-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.134725E+11 | 0.382692E+10 | 320.19 | 0.847935E+10 | 0.499310E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 34917.22 | 27-JUN-10:32 | 22541.61 | 04-JUN-02:61 | 19509.12 | 18-JUN-02:53 | 8596.32 | 27-JUN-12:55 | 0.00 | 01-JUN-00:01 |
July | 0.292803E+11 | 0.802947E+10 | 508.74 | 0.169233E+11 | 0.123570E+11 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 34917.22 | 16-JUL-02:11 | 23328.09 | 21-JUL-13:55 | 22313.26 | 29-JUL-03:52 | 8605.27 | 15-JUL-14:10 | 0.00 | 01-JUL-00:01 |
August | 0.212226E+11 | 0.599957E+10 | 431.06 | 0.139969E+11 | 0.722576E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 34917.22 | 14-AUG-03:33 | 21535.22 | 10-AUG-13:55 | 21931.69 | 14-AUG-03:41 | 8437.39 | 14-AUG-00:42 | 0.00 | 01-AUG-00:01 |
September | 0.774355E+10 | 0.226086E+10 | 231.88 | 0.461814E+10 | 0.312542E+10 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 33550.08 | 16-SEP-00:52 | 20139.07 | 17-SEP-02:61 | 20200.85 | 16-SEP-00:52 | 8333.59 | 16-SEP-00:52 | 0.00 | 01-SEP-00:01 |
October | 0.378391E+09 | 0.118372E+09 | 24.21 | 0.282573E+09 | 95818272.92 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 31426.78 | 13-OCT-02:61 | 22901.71 | 22-OCT-03:22 | 16598.03 | 01-OCT-02:61 | 8179.77 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 37033718.04 | 11675585.86 | 5.45 | 26108361.51 | 10925356.53 | 0.00 | 1.00 | 05-NOV-02:61 | 0.00 | 01-NOV-00:01 | 31426.78 | 27-NOV-03:01 | 24039.30 | 27-NOV-03:01 | 11068.11 | 05-NOV-02:61 | 8179.77 | 05-NOV-02:61 | 0.00 | 01-NOV-00:01 |
December | 1049871.45 | 347010.37 | 0.20 | 648981.99 | 400889.46 | 0.00 | 0.15 | 01-DEC-04:10 | 0.00 | 01-DEC-00:01 | 3851.20 | 01-DEC-04:10 | 2313.57 | 01-DEC-04:10 | 1537.64 | 01-DEC-04:10 | 1254.46 | 01-DEC-04:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.743738E+11 | 0.209404E+11 | 1629.50 | 0.460939E+11 | 0.282799E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.292803E+11 | 0.802947E+10 | 508.74 | 0.169233E+11 | 0.123570E+11 | 0.00 | 1.00 | 0.00 | 34917.22 | 24039.30 | 22313.26 | 8605.27 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.87 | 22.85 | 48.02 | 23.00 | 262.09 | 0.00 | 0.00 | 0.00 |
February | 103.99 | 31.21 | 72.79 | 42.12 | 246.23 | 0.00 | 0.00 | 0.00 |
March | 149.22 | 62.49 | 86.73 | 112.29 | 171.01 | 0.00 | 0.00 | 0.00 |
April | 197.51 | 87.27 | 110.24 | 185.37 | 116.54 | 0.00 | 0.00 | 0.00 |
May | 221.28 | 97.88 | 123.40 | 243.07 | 76.26 | 0.00 | 0.00 | 0.00 |
June | 247.13 | 109.22 | 137.91 | 301.66 | 53.45 | 0.00 | 0.00 | 0.00 |
July | 237.31 | 104.48 | 132.83 | 312.19 | 37.86 | 0.00 | 0.00 | 0.00 |
August | 214.32 | 89.96 | 124.36 | 273.26 | 51.10 | 0.00 | 0.00 | 0.00 |
September | 178.35 | 79.11 | 99.24 | 203.11 | 79.56 | 0.00 | 0.00 | 0.00 |
October | 121.03 | 50.06 | 70.97 | 104.52 | 123.40 | 0.00 | 0.00 | 0.00 |
November | 68.65 | 22.02 | 46.63 | 38.50 | 167.38 | 0.00 | 0.00 | 0.00 |
December | 55.26 | 11.42 | 43.85 | 11.18 | 259.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.64 | 64.15 | 91.49 | 154.80 | 136.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.26 | 11.42 | 43.85 | 11.18 | 37.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 247.13 | 109.22 | 137.91 | 312.19 | 262.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.07 | 194.42 | 138.65 | 255.38 | 482.93 | 0.00 | 0.00 | 0.00 |
February | 380.29 | 183.37 | 196.92 | 283.79 | 469.80 | 0.00 | 0.00 | 0.00 |
March | 464.16 | 260.81 | 203.35 | 448.16 | 332.02 | 0.00 | 0.00 | 0.00 |
April | 384.40 | 153.61 | 230.79 | 393.90 | 250.52 | 0.00 | 0.00 | 0.00 |
May | 336.38 | 97.70 | 238.68 | 376.57 | 164.32 | 0.00 | 0.00 | 0.00 |
June | 326.86 | 69.26 | 257.60 | 404.55 | 115.11 | 0.00 | 0.00 | 0.00 |
July | 333.67 | 80.96 | 252.71 | 460.58 | 81.19 | 0.00 | 0.00 | 0.00 |
August | 374.60 | 121.45 | 253.14 | 505.84 | 107.16 | 0.00 | 0.00 | 0.00 |
September | 435.55 | 212.14 | 223.40 | 540.63 | 165.19 | 0.00 | 0.00 | 0.00 |
October | 416.75 | 238.06 | 178.70 | 447.04 | 245.39 | 0.00 | 0.00 | 0.00 |
November | 298.47 | 168.50 | 129.97 | 276.35 | 322.55 | 0.00 | 0.00 | 0.00 |
December | 278.51 | 144.14 | 134.37 | 200.01 | 477.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 363.45 | 160.28 | 203.16 | 383.31 | 266.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 278.51 | 69.26 | 129.97 | 200.01 | 81.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 464.16 | 260.81 | 257.60 | 540.63 | 482.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.81 | 14.28 | 46.53 | 13.67 | 273.83 | 0.00 | 0.00 | 0.00 |
February | 98.55 | 25.33 | 73.22 | 35.22 | 255.08 | 0.00 | 0.00 | 0.00 |
March | 154.46 | 66.14 | 88.32 | 118.07 | 173.92 | 0.00 | 0.00 | 0.00 |
April | 189.12 | 77.55 | 111.57 | 176.26 | 121.28 | 0.00 | 0.00 | 0.00 |
May | 223.09 | 100.82 | 122.27 | 245.47 | 79.30 | 0.00 | 0.00 | 0.00 |
June | 269.17 | 126.61 | 142.56 | 331.41 | 56.00 | 0.00 | 0.00 | 0.00 |
July | 240.65 | 105.51 | 135.14 | 317.26 | 40.15 | 0.00 | 0.00 | 0.00 |
August | 217.65 | 92.55 | 125.10 | 280.07 | 52.80 | 0.00 | 0.00 | 0.00 |
September | 170.92 | 73.81 | 97.11 | 193.37 | 81.94 | 0.00 | 0.00 | 0.00 |
October | 110.80 | 39.03 | 71.77 | 91.82 | 127.81 | 0.00 | 0.00 | 0.00 |
November | 65.66 | 18.92 | 46.74 | 34.96 | 170.86 | 0.00 | 0.00 | 0.00 |
December | 56.92 | 12.40 | 44.52 | 12.69 | 263.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 155.07 | 62.93 | 92.15 | 154.84 | 140.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.92 | 12.40 | 44.52 | 12.69 | 40.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 269.17 | 126.61 | 142.56 | 331.41 | 273.83 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189824E+09 | 61209666.54 | 0.128614E+09 | 61590262.33 | 0.701982E+09 |
February | 0.251575E+09 | 75491251.28 | 0.176083E+09 | 0.101890E+09 | 0.595685E+09 |
March | 0.399682E+09 | 0.167384E+09 | 0.232298E+09 | 0.300765E+09 | 0.458046E+09 |
April | 0.511939E+09 | 0.226202E+09 | 0.285737E+09 | 0.480484E+09 | 0.302066E+09 |
May | 0.592674E+09 | 0.262171E+09 | 0.330503E+09 | 0.651032E+09 | 0.204254E+09 |
June | 0.640565E+09 | 0.283098E+09 | 0.357467E+09 | 0.781892E+09 | 0.138539E+09 |
July | 0.635614E+09 | 0.279852E+09 | 0.355763E+09 | 0.836158E+09 | 0.101408E+09 |
August | 0.574029E+09 | 0.240946E+09 | 0.333084E+09 | 0.731893E+09 | 0.136860E+09 |
September | 0.462283E+09 | 0.205050E+09 | 0.257232E+09 | 0.526466E+09 | 0.206227E+09 |
October | 0.324154E+09 | 0.134078E+09 | 0.190075E+09 | 0.279957E+09 | 0.330514E+09 |
November | 0.177935E+09 | 57079261.23 | 0.120855E+09 | 99803731.38 | 0.433850E+09 |
December | 0.148021E+09 | 30584329.08 | 0.117437E+09 | 29955680.92 | 0.694716E+09 |
Annual Sum or Average | 0.490829E+10 | 0.202315E+10 | 0.288515E+10 | 0.488189E+10 | 0.430415E+10 |
Minimum of Months | 0.148021E+09 | 30584329.08 | 0.117437E+09 | 29955680.92 | 0.101408E+09 |
Maximum of Months | 0.640565E+09 | 0.283098E+09 | 0.357467E+09 | 0.836158E+09 | 0.701982E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.892101E+09 | 0.520745E+09 | 0.371355E+09 | 0.683998E+09 | 0.129348E+10 |
February | 0.919986E+09 | 0.443609E+09 | 0.476377E+09 | 0.686556E+09 | 0.113655E+10 |
March | 0.124321E+10 | 0.698554E+09 | 0.544661E+09 | 0.120034E+10 | 0.889278E+09 |
April | 0.996366E+09 | 0.398150E+09 | 0.598216E+09 | 0.102100E+10 | 0.649340E+09 |
May | 0.900973E+09 | 0.261680E+09 | 0.639293E+09 | 0.100859E+10 | 0.440119E+09 |
June | 0.847215E+09 | 0.179529E+09 | 0.667687E+09 | 0.104859E+10 | 0.298359E+09 |
July | 0.893698E+09 | 0.216840E+09 | 0.676858E+09 | 0.123361E+10 | 0.217470E+09 |
August | 0.100332E+10 | 0.325302E+09 | 0.678021E+09 | 0.135484E+10 | 0.287008E+09 |
September | 0.112893E+10 | 0.549874E+09 | 0.579060E+09 | 0.140133E+10 | 0.428181E+09 |
October | 0.111623E+10 | 0.637611E+09 | 0.478618E+09 | 0.119735E+10 | 0.657247E+09 |
November | 0.773633E+09 | 0.436741E+09 | 0.336891E+09 | 0.716292E+09 | 0.836045E+09 |
December | 0.745973E+09 | 0.386075E+09 | 0.359898E+09 | 0.535706E+09 | 0.127873E+10 |
Annual Sum or Average | 0.114616E+11 | 0.505471E+10 | 0.640694E+10 | 0.120882E+11 | 0.841180E+10 |
Minimum of Months | 0.745973E+09 | 0.179529E+09 | 0.336891E+09 | 0.535706E+09 | 0.217470E+09 |
Maximum of Months | 0.124321E+10 | 0.698554E+09 | 0.678021E+09 | 0.140133E+10 | 0.129348E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162865E+09 | 38234335.83 | 0.124631E+09 | 36600740.18 | 0.733427E+09 |
February | 0.238415E+09 | 61274412.09 | 0.177141E+09 | 85194200.51 | 0.617081E+09 |
March | 0.413710E+09 | 0.177141E+09 | 0.236569E+09 | 0.316235E+09 | 0.465816E+09 |
April | 0.490192E+09 | 0.200998E+09 | 0.289194E+09 | 0.456872E+09 | 0.314363E+09 |
May | 0.597535E+09 | 0.270047E+09 | 0.327488E+09 | 0.657472E+09 | 0.212387E+09 |
June | 0.697688E+09 | 0.328163E+09 | 0.369525E+09 | 0.859017E+09 | 0.145155E+09 |
July | 0.644552E+09 | 0.282593E+09 | 0.361959E+09 | 0.849739E+09 | 0.107534E+09 |
August | 0.582959E+09 | 0.247879E+09 | 0.335080E+09 | 0.750153E+09 | 0.141417E+09 |
September | 0.443036E+09 | 0.191327E+09 | 0.251708E+09 | 0.501213E+09 | 0.212382E+09 |
October | 0.296770E+09 | 0.104539E+09 | 0.192231E+09 | 0.245921E+09 | 0.342313E+09 |
November | 0.170194E+09 | 49043751.53 | 0.121150E+09 | 90604164.52 | 0.442866E+09 |
December | 0.152461E+09 | 33219513.83 | 0.119242E+09 | 33992653.16 | 0.706197E+09 |
Annual Sum or Average | 0.489038E+10 | 0.198446E+10 | 0.290592E+10 | 0.488301E+10 | 0.444094E+10 |
Minimum of Months | 0.152461E+09 | 33219513.83 | 0.119242E+09 | 33992653.16 | 0.107534E+09 |
Maximum of Months | 0.697688E+09 | 0.328163E+09 | 0.369525E+09 | 0.859017E+09 | 0.733427E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.96 | 983.77 | 464.75 | 231.55 | 233.20 | 0.00 | 0.00 |
February | 330.37 | 940.35 | 582.83 | 239.90 | 342.92 | 0.00 | 0.00 |
March | 644.51 | 642.94 | 767.85 | 389.44 | 378.41 | 0.00 | 0.00 |
April | 729.78 | 462.58 | 771.03 | 318.42 | 452.60 | 0.00 | 0.00 |
May | 849.10 | 303.87 | 780.76 | 296.41 | 484.35 | 0.00 | 0.00 |
June | 1025.67 | 212.61 | 843.16 | 305.09 | 538.07 | 0.00 | 0.00 |
July | 1083.28 | 152.47 | 811.63 | 290.95 | 520.68 | 0.00 | 0.00 |
August | 1052.43 | 204.31 | 806.57 | 303.96 | 502.61 | 0.00 | 0.00 |
September | 926.61 | 316.19 | 784.82 | 365.07 | 419.75 | 0.00 | 0.00 |
October | 633.26 | 486.47 | 648.58 | 327.15 | 321.43 | 0.00 | 0.00 |
November | 337.95 | 648.93 | 432.78 | 209.44 | 223.34 | 0.00 | 0.00 |
December | 196.03 | 972.61 | 390.70 | 167.97 | 222.74 | 0.00 | 0.00 |
Annual Sum or Average | 674.06 | 525.15 | 674.16 | 287.36 | 386.80 | 0.00 | 0.00 |
Minimum of Months | 196.03 | 152.47 | 390.70 | 167.97 | 222.74 | 0.00 | 0.00 |
Maximum of Months | 1083.28 | 983.77 | 843.16 | 389.44 | 538.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.688244E+09 | 0.263494E+10 | 0.124479E+10 | 0.620189E+09 | 0.624601E+09 | 0.00 | 0.00 |
February | 0.799229E+09 | 0.227490E+10 | 0.140998E+10 | 0.580374E+09 | 0.829601E+09 | 0.00 | 0.00 |
March | 0.172626E+10 | 0.172206E+10 | 0.205661E+10 | 0.104308E+10 | 0.101353E+10 | 0.00 | 0.00 |
April | 0.189159E+10 | 0.119900E+10 | 0.199850E+10 | 0.825350E+09 | 0.117315E+10 | 0.00 | 0.00 |
May | 0.227422E+10 | 0.813884E+09 | 0.209118E+10 | 0.793898E+09 | 0.129728E+10 | 0.00 | 0.00 |
June | 0.265854E+10 | 0.551092E+09 | 0.218547E+10 | 0.790789E+09 | 0.139468E+10 | 0.00 | 0.00 |
July | 0.290146E+10 | 0.408364E+09 | 0.217386E+10 | 0.779284E+09 | 0.139458E+10 | 0.00 | 0.00 |
August | 0.281882E+10 | 0.547218E+09 | 0.216031E+10 | 0.814127E+09 | 0.134618E+10 | 0.00 | 0.00 |
September | 0.240177E+10 | 0.819552E+09 | 0.203425E+10 | 0.946252E+09 | 0.108800E+10 | 0.00 | 0.00 |
October | 0.169613E+10 | 0.130297E+10 | 0.173715E+10 | 0.876229E+09 | 0.860924E+09 | 0.00 | 0.00 |
November | 0.875976E+09 | 0.168204E+10 | 0.112176E+10 | 0.542864E+09 | 0.578897E+09 | 0.00 | 0.00 |
December | 0.525052E+09 | 0.260504E+10 | 0.104646E+10 | 0.449879E+09 | 0.596577E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.212573E+11 | 0.165611E+11 | 0.212603E+11 | 0.906231E+10 | 0.121980E+11 | 0.00 | 0.00 |
Minimum of Months | 0.525052E+09 | 0.408364E+09 | 0.104646E+10 | 0.449879E+09 | 0.578897E+09 | 0.00 | 0.00 |
Maximum of Months | 0.290146E+10 | 0.263494E+10 | 0.218547E+10 | 0.104308E+10 | 0.139468E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.150350E+11 | -0.142325E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -802498450.9 | 58.99 | 0.00 | 0.00 |
February | 0.137681E+11 | -0.130421E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -725935876.8 | 58.99 | 0.00 | 0.00 |
March | 0.150593E+11 | -0.142716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -787697929.8 | 58.99 | 0.00 | 0.00 |
April | 0.139835E+11 | -0.132312E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -752255863.5 | 58.99 | 0.00 | 0.00 |
May | 0.136295E+11 | -0.129065E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -722960092.2 | 58.99 | 0.00 | 0.00 |
June | 0.123864E+11 | -0.117290E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -657415433.9 | 58.99 | 0.00 | 0.00 |
July | 0.121611E+11 | -0.114988E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -662316569.3 | 58.98 | 0.00 | 0.00 |
August | 0.119774E+11 | -0.113104E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -666943023.8 | 59.00 | 0.00 | 0.00 |
September | 0.117844E+11 | -0.111171E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -667273577.3 | 58.98 | 0.00 | 0.00 |
October | 0.128236E+11 | -0.120680E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -755582699.4 | 58.99 | 0.00 | 0.00 |
November | 0.132075E+11 | -0.124502E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -757321459.7 | 58.99 | 0.00 | 0.00 |
December | 0.144312E+11 | -0.136305E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800679315.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.160247E+12 | -0.151488E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.875888E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.117844E+11 | -0.142716E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -802498450.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.150593E+11 | -0.111171E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -657415433.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486809E+11 | 61057.65 | 04-JAN-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464359E+11 | 61057.65 | 03-FEB-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.308209E+11 | 61057.65 | 01-MAR-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148640E+11 | 51956.15 | 16-APR-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.310649E+10 | 14498.00 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.466868E+09 | 10197.52 | 21-JUN-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9985465.20 | 8656.22 | 09-JUL-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24274730.31 | 15620.42 | 18-AUG-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.767689E+09 | 10861.30 | 23-SEP-02:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.962432E+10 | 33056.56 | 17-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186258E+11 | 34001.94 | 25-NOV-03:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437837E+11 | 61057.65 | 05-DEC-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9985465.20 | 8656.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486809E+11 | 61057.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427692E+11 | 45034.02 | 06-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410519E+11 | 56792.70 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254151E+11 | 46975.22 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.996319E+10 | 37831.83 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.947464E+09 | 16117.67 | 01-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82926768.58 | 5844.49 | 14-JUN-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134095E+09 | 4856.79 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.515938E+10 | 22730.32 | 18-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124244E+11 | 24559.30 | 25-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.384615E+11 | 57455.49 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427692E+11 | 57455.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.639012E+09 | 0.496068E+09 | 15159.25 | 14-MAR-13:00 | 10683.69 | 0.00 |
April | 0.00 | 0.00 | 6548076.77 | 5389446.69 | 2224.84 | 08-APR-12:55 | 1860.74 | 0.00 |
May | 0.00 | 0.00 | 0.110578E+10 | 0.907304E+09 | 46006.61 | 24-MAY-02:61 | 33475.86 | 0.00 |
June | 0.00 | 0.00 | 0.107557E+11 | 0.707916E+10 | 50145.46 | 18-JUN-02:61 | 23046.77 | 0.00 |
July | 0.00 | 0.00 | 0.238404E+11 | 0.145084E+11 | 51116.37 | 20-JUL-02:61 | 23029.55 | 0.00 |
August | 0.00 | 0.00 | 0.177765E+11 | 0.122002E+11 | 51116.37 | 14-AUG-02:61 | 21698.37 | 0.00 |
September | 0.00 | 0.00 | 0.559462E+10 | 0.355228E+10 | 49752.34 | 16-SEP-02:61 | 21457.97 | 0.00 |
October | 0.00 | 0.00 | 0.246500E+09 | 0.199665E+09 | 46006.61 | 23-OCT-02:61 | 30457.95 | 0.00 |
November | 0.00 | 0.00 | 100.98 | 75.06 | 0.27 | 16-NOV-13:33 | 0.20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.599650E+11 | 0.389485E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.238404E+11 | 0.145084E+11 | 51116.37 | 33475.86 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.661459E+09 | 0.518907E+09 | 31426.78 | 15-MAR-02:61 | 18478.98 | 0.00 |
April | 0.00 | 0.00 | 57089619.55 | 44254781.70 | 31426.78 | 09-APR-02:61 | 17955.22 | 0.00 |
May | 0.00 | 0.00 | 0.151978E+10 | 0.120367E+10 | 31426.78 | 17-MAY-02:61 | 22413.65 | 0.00 |
June | 0.00 | 0.00 | 0.134725E+11 | 0.847935E+10 | 34917.22 | 27-JUN-10:32 | 18848.07 | 0.00 |
July | 0.00 | 0.00 | 0.292803E+11 | 0.169233E+11 | 34917.22 | 16-JUL-02:11 | 13470.53 | 0.00 |
August | 0.00 | 0.00 | 0.212226E+11 | 0.139969E+11 | 34917.22 | 14-AUG-03:33 | 13073.60 | 0.00 |
September | 0.00 | 0.00 | 0.774355E+10 | 0.461814E+10 | 33550.08 | 16-SEP-00:52 | 13349.23 | 0.00 |
October | 0.00 | 0.00 | 0.378391E+09 | 0.282573E+09 | 31426.78 | 13-OCT-02:61 | 16134.13 | 0.00 |
November | 0.00 | 0.00 | 37033718.04 | 26108361.51 | 31426.78 | 27-NOV-03:01 | 24039.30 | 0.00 |
December | 0.00 | 0.00 | 1049871.45 | 648981.99 | 3851.20 | 01-DEC-04:10 | 2313.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.743738E+11 | 0.460939E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.292803E+11 | 0.169233E+11 | 34917.22 | 24039.30 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5607.36 | 21033.89 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5684.97 | 21109.02 | 16-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5623.59 | 21040.51 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5396.68 | 20444.49 | 01-APR-12:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5111.41 | 19428.93 | 01-MAY-12:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4818.51 | 18212.78 | 01-JUN-12:14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4583.23 | 17192.08 | 01-JUL-12:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4516.83 | 16577.57 | 01-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4580.10 | 17139.50 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4797.24 | 18180.17 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5096.53 | 19357.64 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5381.25 | 20420.21 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 5096.39 | ||||
Minimum of Months | 0.00 | 0.00 | 4516.83 | 16577.57 | ||
Maximum of Months | 0.00 | 0.00 | 5684.97 | 21109.02 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270708E+10 | 0.55 | 1211.87 | 01-JAN-00:01 | 0.66 |
February | 0.244314E+10 | 0.55 | 1211.87 | 01-FEB-00:01 | 0.66 |
March | 0.274307E+10 | 0.55 | 1211.87 | 01-MAR-00:01 | 0.66 |
April | 0.267549E+10 | 0.56 | 1211.87 | 01-APR-04:01 | 0.65 |
May | 0.289159E+10 | 0.58 | 1211.87 | 01-MAY-03:10 | 0.65 |
June | 0.293211E+10 | 0.60 | 1211.87 | 01-JUN-01:05 | 0.65 |
July | 0.309518E+10 | 0.62 | 1211.87 | 01-JUL-00:30 | 0.65 |
August | 0.308818E+10 | 0.62 | 1211.87 | 01-AUG-00:13 | 0.65 |
September | 0.289903E+10 | 0.60 | 1211.87 | 01-SEP-02:61 | 0.65 |
October | 0.285109E+10 | 0.57 | 1211.87 | 01-OCT-02:61 | 0.65 |
November | 0.268091E+10 | 0.56 | 1211.87 | 01-NOV-02:63 | 0.65 |
December | 0.271232E+10 | 0.55 | 1211.87 | 01-DEC-00:01 | 0.65 |
Annual Sum or Average | 0.337192E+11 | 0.57 | |||
Minimum of Months | 0.244314E+10 | 0.55 | 1211.87 | 0.65 | |
Maximum of Months | 0.309518E+10 | 0.62 | 1211.87 | 0.66 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.482285E+10 | 0.82 | 2087.47 | 01-JAN-00:19 | 0.92 |
February | 0.438549E+10 | 0.82 | 2087.47 | 01-FEB-05:10 | 0.92 |
March | 0.475216E+10 | 0.81 | 2087.47 | 01-MAR-00:25 | 0.92 |
April | 0.452645E+10 | 0.80 | 2087.47 | 01-APR-10:06 | 0.92 |
May | 0.466074E+10 | 0.77 | 2087.47 | 01-MAY-04:45 | 0.92 |
June | 0.453283E+10 | 0.78 | 2087.47 | 01-JUN-18:32 | 0.91 |
July | 0.472338E+10 | 0.80 | 2087.47 | 01-JUL-09:50 | 0.91 |
August | 0.471380E+10 | 0.80 | 2087.47 | 01-AUG-10:35 | 0.91 |
September | 0.453062E+10 | 0.78 | 2087.47 | 02-SEP-06:20 | 0.92 |
October | 0.466418E+10 | 0.78 | 2087.47 | 01-OCT-20:00 | 0.91 |
November | 0.452399E+10 | 0.80 | 2087.47 | 01-NOV-04:02 | 0.92 |
December | 0.476898E+10 | 0.82 | 2087.47 | 01-DEC-08:50 | 0.91 |
Annual Sum or Average | 0.556055E+11 | 0.80 | |||
Minimum of Months | 0.438549E+10 | 0.77 | 2087.47 | 0.91 | |
Maximum of Months | 0.482285E+10 | 0.82 | 2087.47 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.326455E+10 | 0.80 | 1462.55 | 01-JAN-00:13 | 0.96 |
February | 0.294850E+10 | 0.80 | 1462.55 | 01-FEB-00:13 | 0.96 |
March | 0.327230E+10 | 0.81 | 1462.55 | 01-MAR-00:40 | 0.96 |
April | 0.316460E+10 | 0.81 | 1462.55 | 01-APR-04:04 | 0.96 |
May | 0.329783E+10 | 0.85 | 1462.55 | 01-MAY-04:04 | 0.96 |
June | 0.325664E+10 | 0.88 | 1462.55 | 01-JUN-10:40 | 0.95 |
July | 0.342372E+10 | 0.89 | 1462.55 | 01-JUL-09:18 | 0.95 |
August | 0.340635E+10 | 0.89 | 1462.55 | 01-AUG-09:10 | 0.95 |
September | 0.324123E+10 | 0.87 | 1462.55 | 01-SEP-13:32 | 0.95 |
October | 0.328847E+10 | 0.84 | 1462.55 | 03-OCT-04:30 | 0.96 |
November | 0.316613E+10 | 0.82 | 1462.55 | 01-NOV-06:50 | 0.96 |
December | 0.326490E+10 | 0.80 | 1462.55 | 01-DEC-06:40 | 0.95 |
Annual Sum or Average | 0.389952E+11 | 0.84 | |||
Minimum of Months | 0.294850E+10 | 0.80 | 1462.55 | 0.95 | |
Maximum of Months | 0.342372E+10 | 0.89 | 1462.55 | 0.96 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.71 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.07 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.18 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.44 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:05 | 0.00 | 0.00 | 49.12 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.20 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.27 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 52.36 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.00 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.42 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.31 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.68 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.12 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.00 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.13 | 37.13 | 5607.36 | 21033.89 | 31-JAN-13:40 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.51 | 51.51 | 5684.97 | 21109.02 | 16-FEB-13:40 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.17 | 51.17 | 5623.59 | 21040.51 | 01-MAR-13:20 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.60 | 51.60 | 5396.68 | 20444.49 | 01-APR-12:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.16 | 38.16 | 5111.41 | 19428.93 | 01-MAY-12:28 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.48 | 52.48 | 4818.51 | 18212.78 | 01-JUN-12:14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.48 | 52.48 | 4583.23 | 17192.08 | 01-JUL-12:47 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.45 | 52.45 | 4516.83 | 16577.57 | 01-AUG-13:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.79 | 52.79 | 4580.10 | 17139.50 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.72 | 40.72 | 4797.24 | 18180.17 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.22 | 52.22 | 5096.53 | 19357.64 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.78 | 51.78 | 5381.25 | 20420.21 | 31-DEC-13:40 |
Annual Sum or Average | 0.00 | 5096.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.13 | 37.13 | 4516.83 | 16577.57 | ||
Maximum of Months | 0.00 | 0.00 | 52.79 | 52.79 | 5684.97 | 21109.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.482285E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.438549E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.496536E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.452877E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.503706E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.795796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.121612E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.103606E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.634455E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.474909E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.452399E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.476898E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.746059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438549E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.121612E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.326455E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.294850E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.347425E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.318319E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.377052E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.708356E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.114532E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.940592E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.550209E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.340684E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.317781E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.326525E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.599357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.294850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.482285E+10 | 0.00 | 0.486809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438549E+10 | 0.00 | 0.464359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.475216E+10 | 0.639012E+09 | 0.308209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452645E+10 | 6548076.77 | 0.148640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466074E+10 | 0.110578E+10 | 0.310649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.453283E+10 | 0.107557E+11 | 0.466868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472338E+10 | 0.238404E+11 | 9985465.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.471380E+10 | 0.177765E+11 | 24274730.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453062E+10 | 0.559462E+10 | 0.767689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466418E+10 | 0.246500E+09 | 0.962432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452399E+10 | 100.98 | 0.186258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476898E+10 | 0.00 | 0.437837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556055E+11 | 0.599650E+11 | 0.217211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438549E+10 | 0.00 | 9985465.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482285E+10 | 0.238404E+11 | 0.486809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.326455E+10 | 0.00 | 0.427692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294850E+10 | 0.00 | 0.410519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327230E+10 | 0.661459E+09 | 0.254151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316460E+10 | 57089619.55 | 0.996319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329783E+10 | 0.151978E+10 | 0.947464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.325664E+10 | 0.134725E+11 | 82926768.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.342372E+10 | 0.292803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340635E+10 | 0.212226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.324123E+10 | 0.774355E+10 | 0.134095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328847E+10 | 0.378391E+09 | 0.515938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316613E+10 | 37033718.04 | 0.124244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326490E+10 | 1049871.45 | 0.384615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389952E+11 | 0.743738E+11 | 0.176409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.342372E+10 | 0.292803E+11 | 0.427692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.482285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.475216E+10 | 0.00 | 0.00 | 0.00 | 0.213192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452645E+10 | 0.00 | 0.00 | 0.00 | 2324062.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466074E+10 | 0.00 | 0.00 | 0.00 | 0.376315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.453283E+10 | 0.00 | 0.00 | 0.00 | 0.342513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.472338E+10 | 0.00 | 0.00 | 0.00 | 0.743778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.471380E+10 | 0.00 | 0.00 | 0.00 | 0.564679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453062E+10 | 0.00 | 0.00 | 0.00 | 0.181393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466418E+10 | 0.00 | 0.00 | 0.00 | 84912777.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.452399E+10 | 0.00 | 0.00 | 0.00 | 36.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556055E+11 | 0.00 | 0.00 | 0.00 | 0.190004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482285E+10 | 0.00 | 0.00 | 0.00 | 0.743778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.326455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.294850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327230E+10 | 0.00 | 0.00 | 0.00 | 0.201944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.316460E+10 | 0.00 | 0.00 | 0.00 | 18588344.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.329783E+10 | 0.00 | 0.00 | 0.00 | 0.472698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.325664E+10 | 0.00 | 0.00 | 0.00 | 0.382692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.342372E+10 | 0.00 | 0.00 | 0.00 | 0.802947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.340635E+10 | 0.00 | 0.00 | 0.00 | 0.599957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.324123E+10 | 0.00 | 0.00 | 0.00 | 0.226086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.328847E+10 | 0.00 | 0.00 | 0.00 | 0.118372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316613E+10 | 0.00 | 0.00 | 0.00 | 11675585.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326490E+10 | 0.00 | 0.00 | 0.00 | 347010.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389952E+11 | 0.00 | 0.00 | 0.00 | 0.209404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.294850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.342372E+10 | 0.00 | 0.00 | 0.00 | 0.802947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318084E+11 | 0.00 | 0.00 | 3.64 |
February | 0.117060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301967E+11 | 0.00 | 0.00 | 3.65 |
March | 0.203123E+10 | 14498575.33 | 0.00 | 1337120.04 | 0.00 | 0.222705E+11 | 0.274139E+09 | 0.00 | 3.72 |
April | 0.379747E+10 | 0.00 | 0.00 | 667044.97 | 0.00 | 0.124592E+11 | 0.527214E+09 | 0.00 | 3.69 |
May | 0.606941E+10 | 33412072.89 | 0.00 | 7227362.97 | 0.00 | 0.298378E+10 | 0.315103E+10 | 0.00 | 4.51 |
June | 0.290986E+10 | 0.117349E+10 | 260836.13 | 18600971.19 | 1101113.03 | 0.335722E+09 | 0.559944E+10 | 14520.81 | 6.31 |
July | 0.911697E+09 | 0.338611E+10 | 1220659.91 | 18633380.10 | 14794114.18 | 515028.98 | 0.417113E+10 | 59057.75 | 7.23 |
August | 0.158662E+10 | 0.195240E+10 | 353337.42 | 24576737.70 | 4410859.81 | 1720106.49 | 0.560934E+10 | 28668.22 | 6.77 |
September | 0.432427E+10 | 0.308994E+09 | 780584.41 | 18953181.44 | 324932.73 | 0.533061E+09 | 0.615415E+10 | 19597.76 | 6.24 |
October | 0.557123E+10 | 0.00 | 0.00 | 3076249.11 | 0.00 | 0.836495E+10 | 0.167369E+10 | 0.00 | 3.95 |
November | 0.296486E+10 | 0.00 | 0.00 | 304084.97 | 0.00 | 0.149740E+11 | 0.384643E+09 | 0.00 | 3.64 |
December | 0.123139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289815E+11 | 0.00 | 0.00 | 3.64 |
Annual Sum or Average | 0.337940E+11 | 0.686890E+10 | 2615417.87 | 93376132.51 | 20631019.75 | 0.152910E+12 | 0.275448E+11 | 121844.53 | 4.76 |
Minimum of Months | 0.911697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 515028.98 | 0.00 | 0.00 | 3.64 |
Maximum of Months | 0.606941E+10 | 0.338611E+10 | 1220659.91 | 24576737.70 | 14794114.18 | 0.318084E+11 | 0.615415E+10 | 59057.75 | 7.23 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.756759E+11 | 0.00 | 0.00 | 13911.13 | 0.00 | 46042699.37 | 12450155.67 | 0.00 | 9.64 |
February | 0.705677E+11 | 0.00 | 0.00 | 1350.37 | 0.00 | 53831485.13 | 2732471.92 | 0.00 | 9.65 |
March | 0.572436E+11 | 0.00 | 0.00 | 4493742.46 | 0.00 | 24156267.40 | 0.182377E+10 | 0.00 | 9.69 |
April | 0.411511E+11 | 0.00 | 0.00 | 2856643.88 | 0.00 | 6658608.96 | 0.319063E+10 | 0.00 | 9.78 |
May | 0.210059E+11 | 0.00 | 0.00 | 26339730.79 | 0.00 | 0.00 | 0.147976E+11 | 0.00 | 10.11 |
June | 0.735263E+10 | 0.116984E+10 | 0.00 | 62870729.35 | 596687.90 | 0.00 | 0.171253E+11 | 0.00 | 10.83 |
July | 0.239543E+10 | 0.410934E+10 | 0.00 | 67849201.21 | 7343970.97 | 0.00 | 0.109649E+11 | 0.00 | 11.28 |
August | 0.305504E+10 | 0.180494E+10 | 0.00 | 77394307.69 | 2399950.83 | 0.00 | 0.163844E+11 | 0.00 | 11.07 |
September | 0.967490E+10 | 0.173215E+09 | 0.00 | 55857003.03 | 216273.28 | 0.00 | 0.197979E+11 | 0.00 | 10.65 |
October | 0.337206E+11 | 0.00 | 0.00 | 12057456.32 | 0.00 | 1979524.39 | 0.848452E+10 | 0.00 | 9.88 |
November | 0.445199E+11 | 0.00 | 0.00 | 2588926.96 | 0.00 | 1989008.67 | 0.290130E+10 | 0.00 | 9.76 |
December | 0.719174E+11 | 0.00 | 0.00 | 77643.72 | 0.00 | 40047960.73 | 98275606.55 | 0.00 | 9.69 |
Annual Sum or Average | 0.438280E+12 | 0.725733E+10 | 0.00 | 0.312401E+09 | 10556882.99 | 0.174706E+09 | 0.955838E+11 | 0.00 | 10.17 |
Minimum of Months | 0.239543E+10 | 0.00 | 0.00 | 1350.37 | 0.00 | 0.00 | 2732471.92 | 0.00 | 9.64 |
Maximum of Months | 0.756759E+11 | 0.410934E+10 | 0.00 | 77394307.69 | 7343970.97 | 53831485.13 | 0.197979E+11 | 0.00 | 11.28 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:28:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.152881E+11 | 0.326812E+11 | 0.137620E+12 | 0.00 | 0.379288E+11 |
February | 0.262802E+11 | 0.308788E+11 | 0.128127E+12 | 0.00 | 0.367059E+11 |
March | 0.415168E+11 | 0.250290E+11 | 0.108653E+12 | 0.202360E+09 | 0.347027E+11 |
April | 0.515031E+11 | 0.183111E+11 | 0.834091E+11 | 0.192300E+09 | 0.260971E+11 |
May | 0.650459E+11 | 0.123748E+11 | 0.677770E+11 | 0.173040E+10 | 0.288922E+11 |
June | 0.718753E+11 | 0.621469E+10 | 0.442011E+11 | 0.358327E+10 | 0.580189E+11 |
July | 0.670789E+11 | 0.246362E+09 | 0.192743E+11 | 0.264817E+10 | 0.973787E+11 |
August | 0.567929E+11 | 0.301819E+10 | 0.344024E+11 | 0.355260E+10 | 0.783236E+11 |
September | 0.420435E+11 | 0.823044E+10 | 0.552223E+11 | 0.384635E+10 | 0.421912E+11 |
October | 0.268371E+11 | 0.159963E+11 | 0.803976E+11 | 0.787773E+09 | 0.231118E+11 |
November | 0.128360E+11 | 0.196488E+11 | 0.892929E+11 | 0.118653E+09 | 0.221372E+11 |
December | 0.136132E+11 | 0.311878E+11 | 0.131503E+12 | 0.00 | 0.348963E+11 |
Annual Sum or Average | 0.490711E+12 | 0.203817E+12 | 0.979880E+12 | 0.166619E+11 | 0.520384E+12 |
Minimum of Months | 0.128360E+11 | 0.246362E+09 | 0.192743E+11 | 0.00 | 0.221372E+11 |
Maximum of Months | 0.718753E+11 | 0.326812E+11 | 0.137620E+12 | 0.384635E+10 | 0.973787E+11 |