Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:29:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1953.27 | 8406.82 | 8406.82 |
Net Site Energy | 1953.27 | 8406.82 | 8406.82 |
Total Source Energy | 3329.33 | 14329.36 | 14329.36 |
Net Source Energy | 3329.33 | 14329.36 | 14329.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 662.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 128.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 62.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 581.85 | 1371.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 662.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 128.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 16.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 662.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 40.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 40.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 32.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 276.88 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 128.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 231.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 62.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 313.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 728.47 | 3848.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.42 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2504.26 | 5902.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 313.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 728.47 | 3848.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1462.42 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2504.26 | 5902.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 581.846 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 581.846 | 100.00 |
Total On-Site and Utility Electric Sources | 581.846 | 100.00 |
Total Electricity End Uses | 581.846 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 10.83 |
Time Setpoint Not Met During Occupied Cooling | 21.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4597.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 11.3960 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 10.1539 | 18.52 | 1074.0064 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.7750 | 2.48 | 595.3967 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 10.7750 | 2.48 | 595.3967 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 11.3960 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.1539 | 18.52 | 1074.0064 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 10.7750 | 1.24 | 595.3967 | |||||||
Conditioned Total | 232.34 | 10.7750 | 1.24 | 595.3967 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 10.7750 | 2.48 | 595.3967 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-11:20 | 02-FEB-13:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 152054.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 19003.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2017.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13527.31 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25590.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 3002.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 42352.40 | 200627.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 152054.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 19003.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2017.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12159.73 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 25590.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 544.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1381.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 718.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 128.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 101.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 876.87 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 407.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 250.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 199.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1842.71 | 1486.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3091.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 554.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 436.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1752.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1080.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 857.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7930.98 | 6398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3091.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 554.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 555.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 436.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3774.05 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1752.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1080.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 857.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7930.98 | 6398.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.00 |
KITCHEN DIRECT AIR | 1.31 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 1.00 | 1.00 | 2.00 |
PSZ-AC_2:2 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.00 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.31 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.00 | 2145.08 |
PSZ-AC_2:2_ADDAQ FAN | 1.31 | 1445.38 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.00 | 2.00 | 2.00 | 2.00 | 49780.42 | 66628.69 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 32418.42 | 91267.31 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.00 | 1.00 | 2.00 | 49780.42 | 24890.21 | 49780.42 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.31 | 0.652745 | 1.31 | 32418.42 | 16209.21 | 32418.42 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 66628.69 |
PSZ-AC_2:2 HEATING COIL | 91267.31 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 11.396 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 128.183 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 10.154 | 282.654 | 791.353 | 0.000 | 0.000 | 0.000 | 1084.160 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 1323.895 | 11.396 | 15.123 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1323.895 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1179.595 | 10.154 | 188.034 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1179.595 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 515.917 | 4.441 | 82.240 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 851.667 | 7.331 | 135.761 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 851.667 | 851.667 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.8529 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9385 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.29578988E-12 | 0.13928100E-14 | -0.86482567E-13 | 0.14810105E-15 |
34 | 6 | 0.27762991E-07 | 0.23763811E-09 | 0.63675155E-08 | -0.13032604E-12 |
35 | 5 | -0.18548592E-03 | 0.20454088E-05 | -0.95466282E-04 | 0.62973390E-08 |
36 | 4 | 0.28672537 | 0.10005169E-02 | 0.97734299E-01 | -0.32807465E-04 |
37 | 3 | -7.1589309 | 0.31133244E-01 | -2.3070469 | 0.28482786E-01 |
38 | 2 | 40.516912 | 0.11110460 | 15.134319 | -0.32939531 |
39 | 1 | -80.274307 | 0.50299422E-01 | -29.024413 | 1.0728340 |
40 | 0 | 46.824340 | 0.10150812E-02 | 16.294057 | |
41 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
42 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
43 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
44 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
45 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
46 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
47 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
48 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 | |
49 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
50 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
51 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
52 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
53 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
54 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
55 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
56 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3615_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.054 | 2.054 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.64160E-002 | 0.31435 | 0.48138 | 0.48138 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11590 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 21658.32626 | 25989.99151 | 1.67055 | 2.00466 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 9079.06687 | 10894.88025 | 0.40595 | 0.48715 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16957.07575 | 20348.49090 | 1.08791 | 1.30549 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 2403.57189 | 2884.28627 | 9.60104E-002 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29112.84 | 2.00466 | 2.00466 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 33347.38 | 0.48715 | 0.48715 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25492.55 | 1.30549 | 1.30549 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87202.24 | 1.14133 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.00466 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30549 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.00466 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.00466 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.00466 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.00466 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.00466 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.00466 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30549 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30549 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30549 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30549 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30549 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30549 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.00466 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.30549 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.00466 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.00466 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2145.07831 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.00466 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.00466 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.00466 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.00466 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.00466 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.00233 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.00466 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 49780.42000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 24890.21013 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 49780.42000 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49780.42000 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 66628.69125 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
41 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 66628.69125 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30549 |
43 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30549 |
45 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1445.38448 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30549 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30549 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30549 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30549 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30549 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65274 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30549 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32418.42000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16209.21079 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32418.42000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32418.42000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 91267.30841 |
60 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
62 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 91267.30841 |
63 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
64 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
65 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
66 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
67 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 48355.6 | 11.29 | 11.15 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 31490.5 | 11.47 | 11.32 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | N/A | 2.054 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | N/A | 2.054 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | N/A | 2.054 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.853 | 0.756 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 9.1681112616E-002 | 0.4080492507 | Pass | Pass | 0.1353744309 | 0.4325624237 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1376645818 | 0.6676544072 | Pass | Pass | 5.1443476427E-002 | 0.2165939277 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1708166229 | 0.1910710470 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 489.81 | 227.97 | 1093.29 | 15.73 | 577.81 | 2404.61 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.756 | 0.853 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3615_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3615_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3615_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.054 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.054 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.054 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 11.3960 | 116.17 | 1323.90 | LightsWired | LTG_SCH_DINING | 89.82 | 168.00 | 89.29 | 0.0000 | Y | 22.19 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.1539 | 116.17 | 1179.60 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 18.59 |
Interior Lighting Total | 10.7750 | 232.34 | 2503.49 | 40.78 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 2040.25 | AstronomicalClock | - | 83.63 | 83.63 | 32.03 | |
Exterior Lighting Total | 2040.25 | 32.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 49780.42 | 34900.06 | 14880.36 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32418.42 | 22727.91 | 9690.51 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 48355.6 | 11.29 | 11.15 | ||||
PSZ-AC_2:2 COOLING COIL | 31490.5 | 11.47 | 11.32 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 66628.69 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 91267.31 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 1.56 | 1211.87 | 778.12 | 1.00 | 0.64 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.00 | 2145.08 | 1070.05 | 1.00 | 1.31 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1445.38 | 1107.16 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 21658.33 | 25989.99 | 223.72 | 1.671 | 2.005 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.86 | 0.01157 | 31.20 | 0.01537 | 0.416 | 0.00 |
KITCHEN | 16957.08 | 20348.49 | 175.16 | 1.088 | 1.305 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01022 | 30.25 | 0.01536 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9079.07 | 10894.88 | 93.78 | 0.406 | 0.487 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00765 | -26.20 | 0.00036 | 0.416 | 0.00 |
KITCHEN | 2403.57 | 2884.29 | 24.83 | 0.096 | 1.141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00544 | -26.20 | 0.00036 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.00 | 2.00 | 0.49 | 0.49 | 2.0047 | 2.0047 | 2.0047 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.31 | 1.31 | 1.14 | 1.14 | 1.3055 | 1.3055 | 1.3055 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 49780.420 | 34900.057 | 2.004660 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 49780.42 | 29920.07 | 2.004660 | 25.38 | 19.41 | 0.01235447 | 11.89 | 11.30 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 20.7545 | 23.86 | 0.01156599 | 59.5799 | 21658.33 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 66628.691 | 66628.691 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 66628.69 | 66628.69 | 2.004658 | 11.20 | 8.52 | 0.00613515 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 20.7545 | 21.11 | 0.00764732 | 46.8691 | 9079.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 32418.420 | 22727.906 | 1.305490 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32418.42 | 17747.53 | 1.305490 | 29.72 | 22.31 | 0.01471630 | 11.87 | 11.29 | 0.00850000 | 30.25 | 0.01536331 | 22.87 | 87.4257 | 26.10 | 0.01021780 | 46.1755 | 16957.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 91267.308 | 91267.308 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 91267.31 | 91267.31 | 1.305490 | -20.57 | -20.57 | 0.00106127 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 87.4257 | 18.24 | 0.00592766 | 43.5374 | 762.38 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 49780.420 | 34900.057 | 2.004660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.8064 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.004658 | 2.30246108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 49780.42 | 29920.07 | 1.0000 | 2.30246393 | 2.004660 | 25.38 | 19.41 | 0.01235447 | 56986.7 | 11.89 | 11.30 | 0.00850000 | 33397.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49780.42 | 31.20 | 0.01536508 | 23.13 | 0.41605618 | 20.7545 | 23.86 | 0.01156599 | 23.86 | 0.01156599 | 59.5799 | 21658.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 66628.691 | 66628.691 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.004658 | 2.30246108 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 66628.69 | 66628.69 | 1.0000 | 2.30246108 | 2.004658 | 11.20 | 8.52 | 0.00613515 | 26727.5 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66628.69 | -26.20 | 0.00036134 | -26.20 | 0.41605618 | 20.7545 | 21.00 | 0.00764732 | 21.11 | 0.00764732 | 46.8691 | 9079.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32418.420 | 22727.906 | 1.305490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1032.1969 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.305490 | 1.49942796 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 32418.42 | 17747.53 | 1.0000 | 1.49942815 | 1.305490 | 29.72 | 22.31 | 0.01471630 | 67480.8 | 11.87 | 11.29 | 0.00850000 | 33369.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32418.42 | 30.25 | 0.01536331 | 22.87 | 1.14133354 | 87.4257 | 26.06 | 0.01021780 | 26.10 | 0.01021780 | 46.1755 | 16957.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91267.308 | 91267.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.305490 | 1.49942796 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | Sensible | 91267.31 | 91267.31 | 1.0000 | 1.49942796 | 1.305490 | -20.57 | -20.57 | 0.00106127 | -18059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91267.31 | -26.20 | 0.00036134 | -26.20 | 1.14133354 | 87.4257 | 18.54 | 0.00592766 | 18.24 | 0.00592766 | 43.5374 | 762.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.00 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.31 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4022.67 | 5609.00 | 2611.67 |
KITCHEN | 5227.33 | 6381.17 | 4568.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5247.83 | 6837.67 | 4597.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 62.67 | 1.00 | 10.83 | 0.00 |
KITCHEN | 0.00 | 127.67 | 0.00 | 21.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 62.67 | 128.67 | 10.83 | 21.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.563 | 4.425 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 12.032 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 11.202 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 14193605.87 | 0.00 | 14193605.87 | 11201784.37 | 25395390.24 | 13120747.55 | 1444.48 | 6016.93 | 1298.59 | 238.32 |
KITCHEN | 31045825.32 | 0.00 | 31045825.32 | 193741.04 | 31239566.37 | 35993094.65 | 1451.10 | 6049.65 | 1259.25 | 441.37 |
Total Facility | 45239431.19 | 0.00 | 45239431.19 | 11395525.42 | 56634956.61 | 49113842.20 | 1459.56 | 6342.86 | 1586.40 | 554.43 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5387 | 0.0000 | 0.5387 | 0.4298 | 0.9685 | 0.4161 | 0.00 | 5909.04 | 1277.96 |
KITCHEN | 1.1687 | 0.0000 | 1.1687 | 0.0043 | 1.1730 | 1.1413 | 0.00 | 5937.90 | 1249.10 |
Total Facility | 1.7074 | 0.0000 | 1.7074 | 0.4341 | 2.1415 | 1.5574 | 0.00 | 6217.46 | 1557.52 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 18723930.33 | 0.00 | 18723930.33 | 13120747.55 | 1442.63 | 0.12 | 7317.26 | 238.32 |
PSZ-AC_2:2 | 40955047.05 | 0.00 | 40955047.05 | 35993094.65 | 1443.55 | 0.70 | 7315.75 | 441.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7107 | 0.0000 | 0.7107 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.5417 | 0.0000 | 1.5417 | 1.1413 | 0.00 | 0.00 | 7187.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 742.93 | 668.41 | 6013.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 1403.87 | 6224.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.8513 | 1.0748 | 0.5489 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.7126 | 1.5058 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 370 |
Defaulted Fields | 263 |
Fields with Defaults | 871 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
Electricity:Building | 335.52 | 3013.54 | 01-JAN-01:10 | 19961.31 | 02-JAN-11:10 |
Electricity:Zone:DINING | 92.61 | 454.30 | 01-JAN-01:10 | 5032.19 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 317.66 | 2604.51 | 01-JAN-01:10 | 16445.21 | 02-JAN-11:10 |
InteriorLights:Electricity | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 22.19 | 182.95 | 01-JAN-01:10 | 1097.67 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 22.19 | 182.95 | 01-JAN-01:10 | 1097.67 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 40.78 | 336.20 | 01-JAN-01:10 | 2017.17 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 242.91 | 2559.25 | 01-JAN-01:10 | 14929.12 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.25 | 01-JAN-01:10 | 919.51 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 18.59 | 153.25 | 01-JAN-01:10 | 919.51 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 276.88 | 2268.30 | 01-JAN-01:10 | 14428.03 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 206.46 | 1996.96 | 01-JAN-01:10 | 10493.51 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 26.86 | 851.67 | 01-JAN-00:10 | 851.67 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.90 | 1035.59 | 03-APR-22:30 | 4592.33 | 18-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 17.86 | 255.65 | 01-JAN-23:30 | 3516.10 | 02-JAN-11:10 |
Electricity:Plant | 45.04 | 779.94 | 05-FEB-23:10 | 2586.47 | 04-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 16.05 | 0.00 | 01-JAN-11:10 | 1510.24 | 04-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.99 | 701.41 | 01-MAR-01:10 | 1076.23 | 10-APR-13:40 |
ElectricityPurchased:Facility | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
ElectricityPurchased:Plant | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
Cogeneration:ElectricityPurchased | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
General:Cogeneration:ElectricityPurchased | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
ElectricityNet:Plant | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
Cogeneration:ElectricityNet | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
General:Cogeneration:ElectricityNet | 581.85 | 6036.18 | 02-FEB-01:10 | 42352.40 | 04-AUG-11:20 |
Electricity:HVAC | 169.26 | 0.00 | 01-JAN-01:10 | 24564.10 | 04-AUG-13:00 |
Fans:Electricity | 128.56 | 0.00 | 01-JAN-01:10 | 4802.34 | 22-JAN-05:10 |
General:Fans:Electricity | 128.56 | 0.00 | 01-JAN-01:10 | 4802.34 | 22-JAN-05:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40.69 | 0.00 | 01-JAN-00:10 | 19761.76 | 04-AUG-13:00 |
General:Cooling:Electricity | 40.69 | 0.00 | 01-JAN-00:10 | 19761.76 | 04-AUG-13:00 |
ExteriorLights:Electricity | 32.03 | 0.00 | 01-JAN-08:00 | 2040.25 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 32.03 | 0.00 | 01-JAN-08:00 | 2040.25 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 02-FEB-21:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 02-FEB-21:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1371.42 | 2560.65 | 03-JAN-01:20 | 200627.80 | 02-FEB-13:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 662.73 | 0.00 | 01-JAN-01:10 | 163685.98 | 02-FEB-07:10 |
Heating:NaturalGas | 662.73 | 0.00 | 01-JAN-01:10 | 163685.98 | 02-FEB-07:10 |
General:Heating:NaturalGas | 662.73 | 0.00 | 01-JAN-01:10 | 163685.98 | 02-FEB-07:10 |
NaturalGas:Plant | 231.53 | 722.00 | 03-JAN-00:10 | 28548.75 | 18-FEB-14:00 |
WaterSystems:NaturalGas | 231.53 | 722.00 | 03-JAN-00:10 | 28548.75 | 18-FEB-14:00 |
Water Heater:WaterSystems:NaturalGas | 231.53 | 722.00 | 03-JAN-00:10 | 28548.75 | 18-FEB-14:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1445.70 | 2739.67 | 02-FEB-01:10 | 199390.31 | 02-FEB-13:20 |
EnergyTransfer:Building | 530.45 | 1369.84 | 02-FEB-01:10 | 60222.67 | 03-FEB-12:10 |
EnergyTransfer:Zone:KITCHEN | 342.40 | 1369.84 | 02-FEB-01:10 | 26056.04 | 15-SEP-04:10 |
Refrigeration:EnergyTransfer | 144.08 | 2699.62 | 03-APR-22:20 | 7834.84 | 18-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.04 | 1349.81 | 03-APR-22:20 | 3917.42 | 18-APR-03:30 |
General:Refrigeration:EnergyTransfer | 72.04 | 1349.81 | 03-APR-22:20 | 3917.42 | 18-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 72.04 | 1349.81 | 03-APR-22:20 | 3917.42 | 18-APR-03:30 |
EnergyTransfer:Plant | 231.76 | 1349.81 | 05-FEB-23:10 | 24227.64 | 19-MAR-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 16.28 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.76 | 1114.23 | 01-MAR-01:10 | 2238.70 | 10-APR-13:40 |
EnergyTransfer:Zone:DINING | 188.05 | 0.00 | 01-JAN-01:10 | 45948.72 | 03-FEB-18:10 |
Heating:EnergyTransfer | 131.89 | 0.00 | 01-JAN-00:10 | 45948.72 | 03-FEB-18:10 |
Heating:EnergyTransfer:Zone:DINING | 131.84 | 0.00 | 01-JAN-00:10 | 45948.72 | 03-FEB-18:10 |
General:Heating:EnergyTransfer | 131.89 | 0.00 | 01-JAN-00:10 | 45948.72 | 03-FEB-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 131.84 | 0.00 | 01-JAN-00:10 | 45948.72 | 03-FEB-18:10 |
Cooling:EnergyTransfer | 326.52 | 0.00 | 01-JAN-01:10 | 31392.40 | 26-JUN-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 56.21 | 0.00 | 01-JAN-01:10 | 17421.26 | 30-JAN-04:40 |
General:Cooling:EnergyTransfer | 326.52 | 0.00 | 01-JAN-01:10 | 31392.40 | 26-JUN-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 56.21 | 0.00 | 01-JAN-01:10 | 17421.26 | 30-JAN-04:40 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1866.15 | 23-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.05 | 0.00 | 01-JAN-00:10 | 1866.15 | 23-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 270.31 | 0.00 | 01-JAN-01:10 | 22138.62 | 15-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 270.31 | 0.00 | 01-JAN-01:10 | 22138.62 | 15-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
EnergyTransfer:HVAC | 683.49 | 0.00 | 01-JAN-01:10 | 130948.78 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 530.18 | 0.00 | 01-JAN-01:10 | 130948.78 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 153.31 | 0.00 | 01-JAN-00:10 | 82574.17 | 04-AUG-12:00 |
WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22009.65 | 20-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 131.842 | -56.211 | 0.000 | 0.000 | 72.314 | 22.190 | 52.814 | 24.872 | 0.000 | 3.770 | 0.001 | 0.000 | -15.763 | 0.000 | -202.749 | -33.080 |
KITCHEN | 0.000 | 0.000 | 0.052 | -270.300 | 0.000 | 0.000 | 5.220 | 18.589 | 212.059 | 0.000 | 0.000 | 0.014 | 38.563 | 0.000 | 0.000 | 0.000 | -4.197 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.212 | 9.614 | 0.000 | 0.000 | 0.000 | -12.826 | -0.000 |
Total Facility | 0.000 | 0.000 | 131.894 | -326.512 | 0.000 | 0.000 | 77.534 | 40.779 | 264.873 | 24.872 | 0.000 | 6.996 | 48.178 | 0.000 | -15.763 | 0.000 | -219.771 | -33.081 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-FEB-04:44 | 0.00 | 0.00 | 0.00 | -51290.09 | 0.00 | 0.00 | 0.00 | 182.95 | 508.77 | 0.00 | 0.00 | 0.00 | 53924.04 | 0.00 | -2385.39 | 0.00 | -940.28 | 0.00 |
KITCHEN | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | -59572.36 | 0.00 | 0.00 | 21.54 | 204.34 | 5273.28 | 0.00 | 0.00 | 0.00 | 54237.19 | 0.00 | -0.00 | 0.00 | -163.99 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-FEB-00:01 | 0.00 | 0.00 | 0.00 | -66110.91 | 0.00 | 0.00 | 388.31 | 336.20 | 2649.27 | 0.00 | 0.00 | 65.95 | 65701.88 | 0.00 | -2440.60 | 0.00 | -590.10 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 20-JAN-04:41 | 0.00 | 0.00 | 48333.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.95 | 508.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.13 | 0.00 | -690.42 | -46404.64 |
KITCHEN | 23-JAN-05:02 | 0.00 | 0.00 | 16779.53 | 0.00 | 0.00 | 0.00 | 22.98 | 204.34 | 5273.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -164.37 | -22115.76 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JAN-04:41 | 0.00 | 0.00 | 48333.47 | 0.00 | 0.00 | 0.00 | 0.00 | 336.20 | 3503.73 | 0.00 | 0.00 | 288.57 | 0.00 | 0.00 | -1930.13 | 0.00 | -1453.57 | -49078.27 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0047 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0047 | 0.2075 | 1.0000 | Not calculated | 0.4161 | 0.2075 | ||
PSZ-AC_2:2 | 1.3055 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3055 | 0.1159 | 1.0000 | Not calculated | 0.1513 | 0.1159 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0047 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0047 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2075 | ||
PSZ-AC_2:2 | 1.3055 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3055 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1159 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0047 | 2.0047 | 2.0047 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3055 | 1.3055 | 1.3055 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0047 | 2.0047 | 2.0047 | 2.0047 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3055 | 1.3055 | 1.3055 | 1.3055 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0047 | 2.0047 | 2.0047 | No | 0.4161 | 0.8541 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3055 | 1.3055 | 1.3055 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0047 | 2.0047 | 2.0047 | 2.0047 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3055 | 1.3055 | 1.3055 | 1.3055 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 10.83 |
Number of hours cooling loads not met | 21.00 |
Number of hours not met | 31.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 662.73 | 163685.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40.69 | 19761.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 40.78 | 2017.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 32.03 | 2040.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 26.86 | 851.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 128.56 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 231.53 | 28548.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 17.86 | 3516.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 16.05 | 1510.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.99 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 339.78 | 581.85 |
Natural Gas | 477.16 | 1371.42 |
Additional | 0.00 | 0.00 |
Total | 816.94 | 1953.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 175.51 |
Space Heating | 0.00 |
Space Cooling | 175.13 |
Fans (All) | 553.34 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1191.68 |
Miscellaneous (All) | 2504.26 |
Subtotal | 2504.26 |
Natural Gas [MJ/m2] | |
Space Heating | 2852.38 |
Service Water Heating | 996.51 |
Miscellaneous (All) | 5902.56 |
Subtotal | 5902.56 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.09 |
Space Heating | 33.93 |
Space Cooling | 2.08 |
Fans (All) | 6.58 |
Service Water Heating | 11.85 |
Receptacle Equipment | 38.60 |
Miscellaneous | 4.86 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4683. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 5084. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8705.83 | 54.17 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8071.83 | 669.33 | 18.83 | 0.00 | 0.00 |
ATTIC | 7260.67 | 420.83 | 413.00 | 505.67 | 159.83 |
Min | 7260.67 | 54.17 | 0.00 | 0.00 | 0.00 |
Max | 8705.83 | 669.33 | 413.00 | 505.67 | 159.83 |
Average | 8012.78 | 381.44 | 143.94 | 168.56 | 53.28 |
Sum | 24038.33 | 1144.33 | 431.83 | 505.67 | 159.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254698.33 | 26.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16167.67 | 90.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254698.33 | 90.33 | 0.00 | 0.00 | 0.00 |
Average | 90288.67 | 39.00 | 0.00 | 0.00 | 0.00 |
Sum | 270866.00 | 117.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7849.17 | 910.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6442.17 | 2315.33 | 2.50 | 0.00 | 0.00 |
ATTIC | 7198.67 | 727.00 | 278.33 | 220.17 | 335.83 |
Min | 6442.17 | 727.00 | 0.00 | 0.00 | 0.00 |
Max | 7849.17 | 2315.33 | 278.33 | 220.17 | 335.83 |
Average | 7163.33 | 1317.72 | 93.61 | 73.39 | 111.94 |
Sum | 21490.00 | 3953.17 | 280.83 | 220.17 | 335.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 233292.67 | 21432.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 12003.50 | 4254.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 233292.67 | 21432.33 | 0.00 | 0.00 | 0.00 |
Average | 81765.39 | 8562.28 | 0.00 | 0.00 | 0.00 |
Sum | 245296.17 | 25686.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:13
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.847416E+09 | 41790.87 | 31-JAN-04:08 | -31.0 | -31.2 | 0.444807E+10 | 3723.61 | 07-JAN-19:10 | -31.0 | -31.2 |
February | 0.738268E+09 | 51291.49 | 02-FEB-04:44 | -35.9 | -36.0 | 0.400715E+10 | 3723.61 | 04-FEB-19:10 | -20.0 | -20.6 |
March | 0.805012E+09 | 13025.86 | 06-MAR-00:01 | -16.3 | -16.8 | 0.452295E+10 | 4134.51 | 23-MAR-17:10 | 15.73 | 9.79 |
April | 0.236548E+10 | 12754.84 | 15-APR-17:03 | 29.72 | 18.80 | 0.450498E+10 | 4681.82 | 15-APR-18:30 | 26.95 | 18.27 |
May | 0.476929E+10 | 17170.23 | 31-MAY-04:01 | 16.60 | 15.22 | 0.497906E+10 | 4681.76 | 06-MAY-18:19 | 16.60 | 15.22 |
June | 0.102595E+11 | 27597.89 | 30-JUN-03:01 | 22.12 | 19.22 | 0.510807E+10 | 4681.83 | 17-JUN-18:00 | 22.12 | 19.22 |
July | 0.125521E+11 | 27168.72 | 26-JUL-03:01 | 23.12 | 19.53 | 0.539006E+10 | 4681.97 | 22-JUL-18:40 | 23.12 | 19.53 |
August | 0.121590E+11 | 24564.57 | 12-AUG-04:01 | 16.02 | 14.72 | 0.543099E+10 | 4682.14 | 19-AUG-18:10 | 19.90 | 18.81 |
September | 0.805175E+10 | 23883.69 | 17-SEP-04:01 | 16.60 | 13.31 | 0.488705E+10 | 4681.82 | 02-SEP-18:30 | 16.60 | 13.31 |
October | 0.195309E+10 | 6957.46 | 18-OCT-23:01 | -0.8 | -2.1 | 0.456914E+10 | 4414.30 | 20-OCT-11:00 | 21.10 | 12.25 |
November | 0.103313E+10 | 30088.91 | 26-NOV-04:08 | -25.0 | -25.3 | 0.432236E+10 | 4047.37 | 03-NOV-11:00 | -25.0 | -25.3 |
December | 0.677937E+09 | 25754.82 | 09-DEC-04:03 | -22.8 | -23.0 | 0.444721E+10 | 3723.61 | 02-DEC-19:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.562120E+11 | 0.566171E+11 | ||||||||
Minimum of Months | 0.677937E+09 | 6957.46 | -35.9 | -36.0 | 0.400715E+10 | 3723.61 | -31.0 | -31.2 | ||
Maximum of Months | 0.125521E+11 | 51291.49 | 29.72 | 19.53 | 0.543099E+10 | 4682.14 | 26.95 | 19.53 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191333E+11 | 59613.04 | 06-JAN-05:01 | -26.7 | -26.9 | 0.768475E+10 | 5039.33 | 03-JAN-11:00 | -26.7 | -26.9 |
February | 0.179832E+11 | 47703.65 | 16-FEB-05:01 | -17.3 | -17.7 | 0.694155E+10 | 5039.33 | 02-FEB-11:00 | -17.3 | -17.7 |
March | 0.213100E+11 | 45556.86 | 08-MAR-05:01 | -14.7 | -15.0 | 0.769629E+10 | 5074.98 | 28-MAR-10:00 | 12.80 | 7.63 |
April | 0.215197E+11 | 43175.78 | 18-APR-03:21 | 13.35 | 10.93 | 0.747656E+10 | 5138.40 | 18-APR-10:50 | 26.52 | 20.80 |
May | 0.233129E+11 | 44363.21 | 09-MAY-04:01 | 10.60 | 9.66 | 0.779767E+10 | 5138.43 | 15-MAY-10:00 | 19.40 | 15.32 |
June | 0.240303E+11 | 43259.68 | 23-JUN-03:11 | 11.50 | 9.76 | 0.758629E+10 | 5143.97 | 30-JUN-10:00 | 28.30 | 23.10 |
July | 0.253848E+11 | 40775.57 | 11-JUL-04:01 | 12.98 | 12.56 | 0.785820E+10 | 5145.17 | 03-JUL-10:00 | 12.98 | 12.56 |
August | 0.256578E+11 | 43300.94 | 08-AUG-03:11 | 11.83 | 9.78 | 0.786030E+10 | 5177.42 | 04-AUG-10:00 | 11.83 | 9.78 |
September | 0.247591E+11 | 49815.70 | 15-SEP-04:01 | 6.52 | 5.72 | 0.755263E+10 | 5138.44 | 13-SEP-10:00 | 6.52 | 5.72 |
October | 0.246009E+11 | 43826.30 | 22-OCT-04:01 | 10.27 | 7.25 | 0.771797E+10 | 5133.73 | 20-OCT-10:00 | 10.27 | 7.25 |
November | 0.219932E+11 | 54536.71 | 28-NOV-05:01 | -21.1 | -21.4 | 0.744926E+10 | 5105.28 | 08-NOV-11:50 | -21.1 | -21.4 |
December | 0.206214E+11 | 52020.86 | 12-DEC-05:01 | -20.0 | -20.3 | 0.768466E+10 | 5039.33 | 05-DEC-11:00 | -20.0 | -20.3 |
Annual Sum or Average | 0.270307E+12 | 0.913061E+11 | ||||||||
Minimum of Months | 0.179832E+11 | 40775.57 | -26.7 | -26.9 | 0.694155E+10 | 5039.33 | -26.7 | -26.9 | ||
Maximum of Months | 0.256578E+11 | 59613.04 | 13.35 | 12.56 | 0.786030E+10 | 5177.42 | 28.30 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -12.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 | -2.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 | 5.15 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 | 10.69 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 | 15.94 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 | 1.39 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 | -0.5 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352417E+11 | 48328.36 | 20-JAN-04:41 | -24.5 |
February | 0.247733E+11 | 48232.13 | 04-FEB-04:31 | -30.8 |
March | 0.154212E+11 | 28411.32 | 13-MAR-04:01 | -9.4 |
April | 0.772883E+10 | 25810.09 | 03-APR-04:01 | -6.8 |
May | 0.685155E+09 | 14561.75 | 02-MAY-04:01 | 2.70 |
June | 0.167080E+09 | 4942.48 | 03-JUN-06:03 | 6.78 |
July | 4768852.31 | 1727.40 | 25-JUL-23:01 | 25.00 |
August | 4590709.25 | 1417.05 | 02-AUG-23:01 | 24.40 |
September | 0.906007E+09 | 10716.76 | 30-SEP-04:01 | -0.5 |
October | 0.463742E+10 | 13212.69 | 31-OCT-20:00 | -0.7 |
November | 0.151438E+11 | 48127.41 | 26-NOV-04:41 | -25.0 |
December | 0.271280E+11 | 48172.50 | 09-DEC-04:51 | -22.8 |
Annual Sum or Average | 0.131842E+12 | |||
Minimum of Months | 4590709.25 | 1417.05 | -30.8 | |
Maximum of Months | 0.352417E+11 | 48328.36 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22045446.27 | 16795.32 | 23-JAN-05:02 | -17.9 |
February | 10318480.63 | 15708.31 | 03-FEB-05:02 | -33.9 |
March | 4083260.07 | 11650.75 | 06-MAR-05:02 | -15.4 |
April | 1542127.41 | 9173.10 | 06-APR-04:03 | -5.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 5375.35 | 89.59 | 14-OCT-04:04 | 0.03 |
November | 5064233.99 | 11373.65 | 26-NOV-05:02 | -25.2 |
December | 9136417.75 | 12022.00 | 11-DEC-05:02 | -22.2 |
Annual Sum or Average | 52195341.47 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 22045446.27 | 16795.32 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.187504E+10 | 1097.67 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.169832E+10 | 1097.67 | 01-FEB-10:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.190490E+10 | 1097.67 | 01-MAR-10:09 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.182191E+10 | 1097.67 | 01-APR-16:10 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.188997E+10 | 1097.67 | 01-MAY-09:09 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.184123E+10 | 1097.67 | 01-JUN-09:09 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.187087E+10 | 1097.67 | 01-JUL-16:10 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.190490E+10 | 1097.67 | 01-AUG-09:09 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.182235E+10 | 1097.67 | 01-SEP-09:09 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.187482E+10 | 1097.67 | 02-OCT-09:09 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.181511E+10 | 1097.67 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.187109E+10 | 1097.67 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.221905E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.169832E+10 | 1097.67 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.190490E+10 | 1097.67 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.157070E+10 | 919.51 | 02-JAN-10:09 | 0.175350E+11 | 10493.51 | 01-JAN-11:09 |
February | 0.142266E+10 | 919.51 | 01-FEB-10:09 | 0.158380E+11 | 10493.51 | 01-FEB-11:09 |
March | 0.159571E+10 | 919.51 | 01-MAR-10:09 | 0.175350E+11 | 10493.51 | 01-MAR-11:09 |
April | 0.152620E+10 | 919.51 | 01-APR-16:10 | 0.169693E+11 | 10493.51 | 01-APR-10:09 |
May | 0.158321E+10 | 919.51 | 01-MAY-09:09 | 0.175350E+11 | 10493.51 | 01-MAY-10:09 |
June | 0.154238E+10 | 919.51 | 01-JUN-09:09 | 0.169693E+11 | 10493.51 | 01-JUN-10:09 |
July | 0.156721E+10 | 919.51 | 01-JUL-16:10 | 0.175350E+11 | 10493.51 | 01-JUL-10:09 |
August | 0.159571E+10 | 919.51 | 01-AUG-09:09 | 0.175350E+11 | 10493.51 | 01-AUG-10:09 |
September | 0.152657E+10 | 919.51 | 01-SEP-09:09 | 0.169693E+11 | 10493.51 | 01-SEP-10:09 |
October | 0.157052E+10 | 919.51 | 02-OCT-09:09 | 0.175350E+11 | 10493.51 | 01-OCT-10:09 |
November | 0.152050E+10 | 919.51 | 01-NOV-09:09 | 0.169693E+11 | 10493.51 | 01-NOV-10:09 |
December | 0.156739E+10 | 919.51 | 01-DEC-10:09 | 0.175350E+11 | 10493.51 | 01-DEC-11:09 |
Annual Sum or Average | 0.185888E+11 | 0.206460E+12 | ||||
Minimum of Months | 0.142266E+10 | 919.51 | 0.158380E+11 | 10493.51 | ||
Maximum of Months | 0.159571E+10 | 919.51 | 0.175350E+11 | 10493.51 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.187504E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399998E+11 |
February | 0.852256E+10 | 0.169832E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302272E+11 |
March | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230226E+11 |
April | 0.915225E+10 | 0.182191E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160843E+09 | 0.149859E+11 |
May | 0.947560E+10 | 0.188997E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167890E+09 | 0.766356E+10 |
June | 0.922788E+10 | 0.184123E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111301E+10 | 0.388460E+10 |
July | 0.939996E+10 | 0.187087E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851852E+09 | 0.235893E+10 |
August | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872015E+09 | 0.309340E+10 |
September | 0.915225E+10 | 0.182235E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604709E+09 | 0.689519E+10 |
October | 0.940563E+10 | 0.187482E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144475E+11 |
November | 0.909363E+10 | 0.181511E+10 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229232E+11 |
December | 0.939996E+10 | 0.187109E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332471E+11 |
Annual Sum or Average | 0.111326E+12 | 0.221905E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377032E+10 | 0.202749E+12 |
Minimum of Months | 0.852256E+10 | 0.169832E+10 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235893E+10 |
Maximum of Months | 0.954557E+10 | 0.190490E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111301E+10 | 0.399998E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.157070E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723473E+09 |
February | 0.610713E+09 | 0.142266E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550250E+09 |
March | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484200E+09 |
April | 0.655836E+09 | 0.152620E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1353829.90 | 0.310687E+09 |
May | 0.679007E+09 | 0.158321E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 485105.94 | 0.194055E+09 |
June | 0.661256E+09 | 0.154238E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 5721268.32 | 0.127494E+09 |
July | 0.673587E+09 | 0.156721E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1743007.04 | 99048952.41 |
August | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2353336.76 | 0.129636E+09 |
September | 0.655836E+09 | 0.152657E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2150651.76 | 0.174342E+09 |
October | 0.673993E+09 | 0.157052E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288659E+09 |
November | 0.651635E+09 | 0.152050E+10 | 0.129420E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483251E+09 |
December | 0.673587E+09 | 0.156739E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631588E+09 |
Annual Sum or Average | 0.797748E+10 | 0.185888E+11 | 0.157461E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 13807199.72 | 0.419668E+10 |
Minimum of Months | 0.610713E+09 | 0.142266E+10 | 0.120792E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99048952.41 |
Maximum of Months | 0.684021E+09 | 0.159571E+10 | 0.133734E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 5721268.32 | 0.723473E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295613E+09 | 0.607558E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291977E+09 | 0.729804E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249318E+09 | 0.105833E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216122E+09 | 0.131325E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194745E+09 | 0.158941E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204780E+09 | 0.164368E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260475E+09 | 0.172135E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218392E+09 | 0.146651E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326171E+09 | 0.105507E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338752E+09 | 0.787463E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293015E+09 | 0.494837E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322719E+09 | 0.358503E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321208E+10 | 0.128258E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194745E+09 | 0.358503E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338752E+09 | 0.172135E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 1097.67 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 50550.43 | 30-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 1097.67 | 01-FEB-10:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 54980.75 | 02-FEB-12:02 |
March | 9454.80 | 04-MAR-19:10 | 1097.67 | 01-MAR-10:09 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 32119.16 | 05-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 1097.67 | 01-APR-16:10 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.32 | 15-APR-17:03 | 24508.02 | 03-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 1097.67 | 01-MAY-09:09 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4633.04 | 31-MAY-12:00 | 16053.14 | 01-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 1097.67 | 01-JUN-09:09 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5947.86 | 26-JUN-17:03 | 11889.44 | 01-JUN-18:00 |
July | 9454.80 | 01-JUL-18:10 | 1097.67 | 01-JUL-16:10 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4648.58 | 26-JUL-17:53 | 6799.02 | 10-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 1097.67 | 01-AUG-09:09 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6015.93 | 04-AUG-12:00 | 7347.98 | 06-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 1097.67 | 01-SEP-09:09 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5835.71 | 07-SEP-13:00 | 16547.24 | 29-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 1097.67 | 02-OCT-09:09 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 20634.58 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 1097.67 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 48862.96 | 25-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 1097.67 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 46320.16 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 1097.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6799.02 | |||||
Maximum of Months | 9454.80 | 1097.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 6015.93 | 54980.75 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 919.51 | 02-JAN-10:09 | 7755.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2047.86 | 29-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 919.51 | 01-FEB-10:09 | 7755.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1439.41 | 28-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 919.51 | 01-MAR-10:09 | 7755.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1345.10 | 21-MAR-03:10 |
April | 677.52 | 01-APR-18:10 | 919.51 | 01-APR-16:10 | 7755.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 42.81 | 15-APR-15:00 | 1011.16 | 03-APR-00:20 |
May | 677.52 | 06-MAY-18:10 | 919.51 | 01-MAY-09:09 | 7755.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.22 | 31-MAY-13:00 | 761.46 | 02-MAY-03:10 |
June | 677.52 | 03-JUN-18:10 | 919.51 | 01-JUN-09:09 | 7755.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 56.72 | 18-JUN-15:55 | 529.37 | 02-JUN-03:40 |
July | 677.52 | 01-JUL-18:10 | 919.51 | 01-JUL-16:10 | 7755.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 28.52 | 25-JUL-16:00 | 362.66 | 25-JUL-02:10 |
August | 677.52 | 05-AUG-18:10 | 919.51 | 01-AUG-09:09 | 7755.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 24.04 | 03-AUG-16:00 | 427.44 | 19-AUG-04:00 |
September | 677.52 | 02-SEP-18:10 | 919.51 | 01-SEP-09:09 | 7755.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.10 | 06-SEP-14:00 | 473.80 | 27-SEP-04:00 |
October | 677.52 | 07-OCT-18:10 | 919.51 | 02-OCT-09:09 | 7755.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 860.96 | 24-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 919.51 | 01-NOV-09:09 | 7755.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1549.20 | 21-NOV-04:10 |
December | 677.52 | 02-DEC-19:10 | 919.51 | 01-DEC-10:09 | 7755.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2698.30 | 09-DEC-01:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 919.51 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 362.66 | ||||||
Maximum of Months | 677.52 | 919.51 | 7755.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 56.72 | 2698.30 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.49 | 25-JAN-04:52 | 1884.29 | 31-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.65 | 28-FEB-24:00 | 1986.94 | 02-FEB-14:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.99 | 01-MAR-00:12 | 2292.81 | 05-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.34 | 05-APR-23:10 | 2610.32 | 05-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.32 | 03-MAY-02:00 | 2618.32 | 21-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.21 | 07-JUN-23:00 | 2667.61 | 09-JUN-13:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.32 | 23-JUL-23:00 | 2471.69 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.59 | 05-AUG-05:00 | 2214.50 | 16-AUG-12:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.22 | 08-SEP-04:00 | 2107.22 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.58 | 20-OCT-07:03 | 1840.70 | 23-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.38 | 01-NOV-00:01 | 1488.77 | 25-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.57 | 04-DEC-07:55 | 1149.85 | 15-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.21 | 1149.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.22 | 2667.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41790.87 | 31-JAN-04:08 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.47 |
February | 51291.49 | 02-FEB-04:44 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 940.28 |
March | 13025.86 | 06-MAR-00:01 | 4727.40 | 1646.54 | 3663.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.66 |
April | 12754.84 | 15-APR-17:03 | 22061.20 | 3293.00 | 9768.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.32 | 0.00 |
May | 17170.23 | 31-MAY-04:01 | 5252.67 | 2439.28 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 |
June | 27597.89 | 30-JUN-03:01 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 |
July | 27168.72 | 26-JUL-03:01 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.73 |
August | 24564.57 | 12-AUG-04:01 | 0.00 | 1829.49 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.81 |
September | 23883.69 | 17-SEP-04:01 | 0.00 | 1829.49 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 |
October | 6957.46 | 18-OCT-23:01 | 3676.87 | 1280.64 | 2849.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.98 |
November | 30088.91 | 26-NOV-04:08 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939.37 |
December | 25754.82 | 09-DEC-04:03 | 0.00 | 1829.49 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1701.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6957.46 | 0.00 | 1280.64 | 2849.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51291.49 | 22061.20 | 3293.00 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.32 | 1701.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59613.04 | 06-JAN-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 163.99 |
February | 47703.65 | 16-FEB-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 143.93 |
March | 45556.86 | 08-MAR-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 79.21 |
April | 43175.78 | 18-APR-03:21 | 0.00 | 1379.28 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 318.24 |
May | 44363.21 | 09-MAY-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 98.55 |
June | 43259.68 | 23-JUN-03:11 | 0.00 | 1532.53 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 216.46 |
July | 40775.57 | 11-JUL-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 |
August | 43300.94 | 08-AUG-03:11 | 0.00 | 1532.53 | 24689.89 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 240.84 |
September | 49815.70 | 15-SEP-04:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 |
October | 43826.30 | 22-OCT-04:01 | 0.00 | 1532.53 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 92.76 |
November | 54536.71 | 28-NOV-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 69.21 |
December | 52020.86 | 12-DEC-05:01 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 201.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 40775.57 | 0.00 | 1379.28 | 22220.90 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | |
Maximum of Months | 59613.04 | 376.40 | 2043.41 | 40109.56 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 318.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.72 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.77 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.37 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.24 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.72 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.48 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.34 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.38 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.38 | 5.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.461647E+11 | 25638.60 | 13-JAN-11:20 | 0.234852E+12 | 181859.88 | 30-JAN-13:09 |
February | 0.414581E+11 | 25644.06 | 08-FEB-11:20 | 0.179107E+12 | 200627.80 | 02-FEB-13:09 |
March | 0.456564E+11 | 25665.68 | 29-MAR-10:20 | 0.140557E+12 | 129417.84 | 05-MAR-20:30 |
April | 0.452251E+11 | 36477.50 | 18-APR-10:00 | 0.984477E+11 | 103944.92 | 03-APR-10:20 |
May | 0.476874E+11 | 36731.71 | 31-MAY-10:20 | 0.652844E+11 | 63215.45 | 02-MAY-10:30 |
June | 0.536773E+11 | 39911.56 | 26-JUN-10:20 | 0.585094E+11 | 55472.65 | 05-JUN-10:30 |
July | 0.582356E+11 | 39451.65 | 03-JUL-10:20 | 0.582547E+11 | 49498.82 | 01-JUL-12:39 |
August | 0.572814E+11 | 42352.40 | 04-AUG-11:20 | 0.579364E+11 | 49018.02 | 01-AUG-12:50 |
September | 0.495764E+11 | 37504.84 | 11-SEP-10:00 | 0.619337E+11 | 62085.23 | 30-SEP-06:19 |
October | 0.460009E+11 | 25760.58 | 20-OCT-15:09 | 0.852532E+11 | 74190.50 | 31-OCT-19:00 |
November | 0.446534E+11 | 25746.34 | 08-NOV-11:09 | 0.135204E+12 | 160045.52 | 25-NOV-19:49 |
December | 0.462295E+11 | 25633.03 | 14-DEC-11:20 | 0.196079E+12 | 163682.70 | 08-DEC-20:40 |
Annual Sum or Average | 0.581846E+12 | 0.137142E+13 | ||||
Minimum of Months | 0.414581E+11 | 25633.03 | 0.579364E+11 | 49018.02 | ||
Maximum of Months | 0.582356E+11 | 42352.40 | 0.234852E+12 | 200627.80 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.344574E+10 | 0.338355E+10 | 0.235157E+11 | 0.00 | 0.108374E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312098E+10 | 0.281922E+10 | 0.212400E+11 | 0.00 | 0.975788E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350061E+10 | 0.279351E+10 | 0.235157E+11 | 0.00 | 0.107662E+11 | 0.80 | 0.00 | 278579.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.334811E+10 | 0.236751E+10 | 0.227571E+11 | 0.00 | 0.104375E+11 | 0.77 | 0.00 | 0.125993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.347318E+10 | 0.215328E+10 | 0.235157E+11 | 0.00 | 0.109006E+11 | 0.80 | 0.00 | 0.210103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338361E+10 | 0.193661E+10 | 0.227571E+11 | 0.00 | 0.107633E+11 | 0.77 | 0.00 | 0.928809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.343808E+10 | 0.206392E+10 | 0.235157E+11 | 0.00 | 0.112217E+11 | 0.79 | 0.00 | 0.121719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350061E+10 | 0.231732E+10 | 0.235157E+11 | 0.00 | 0.111909E+11 | 0.80 | 0.00 | 0.109440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.334892E+10 | 0.255358E+10 | 0.227571E+11 | 0.00 | 0.106712E+11 | 0.77 | 0.00 | 0.485757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344534E+10 | 0.298570E+10 | 0.235157E+11 | 0.00 | 0.107733E+11 | 0.79 | 0.00 | 66706549.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333560E+10 | 0.318891E+10 | 0.227571E+11 | 0.00 | 0.104332E+11 | 0.77 | 0.00 | 1846429.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.343848E+10 | 0.346557E+10 | 0.235157E+11 | 0.00 | 0.108108E+11 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.407793E+11 | 0.320287E+11 | 0.276879E+12 | 0.00 | 0.128564E+12 | 9.37 | 0.00 | 0.406913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312098E+10 | 0.193661E+10 | 0.212400E+11 | 0.00 | 0.975788E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350061E+10 | 0.346557E+10 | 0.235157E+11 | 0.00 | 0.112217E+11 | 0.80 | 0.00 | 0.121719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.172753E+12 | 0.00 | 0.215742E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.122672E+12 | 0.00 | 0.198312E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.782400E+11 | 0.00 | 0.217909E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.389254E+11 | 0.00 | 0.203039E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.489984E+10 | 0.00 | 0.198589E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.120650E+10 | 0.00 | 0.180845E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 2686541.15 | 0.00 | 0.177263E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 41542706.48 | 0.00 | 0.173692E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.570233E+10 | 0.00 | 0.170129E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.263120E+11 | 0.00 | 0.184155E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.770789E+11 | 0.00 | 0.189067E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.134896E+12 | 0.00 | 0.206572E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.662730E+12 | 0.00 | 0.231531E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 2686541.15 | 0.00 | 0.170129E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.172753E+12 | 0.00 | 0.217909E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 2017.17 | 02-JAN-10:09 | 2040.25 | 01-JAN-00:10 | 14428.03 | 01-JAN-11:09 | 0.00 | 4802.34 | 22-JAN-05:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 2017.17 | 01-FEB-10:09 | 2040.25 | 01-FEB-00:10 | 14428.03 | 01-FEB-11:09 | 0.00 | 4802.34 | 22-FEB-09:50 | 0.00 | 02-FEB-21:10 | 0.00 | 01-FEB-00:10 |
March | 2017.17 | 01-MAR-10:09 | 2040.25 | 01-MAR-00:10 | 14428.03 | 01-MAR-11:09 | 0.00 | 4802.34 | 06-MAR-23:10 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 2017.17 | 01-APR-16:10 | 2040.25 | 01-APR-00:10 | 14428.03 | 01-APR-10:09 | 0.00 | 4802.34 | 22-APR-04:10 | 0.00 | 12-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 2017.17 | 01-MAY-09:09 | 2040.25 | 01-MAY-00:10 | 14428.03 | 01-MAY-10:09 | 0.00 | 4802.34 | 01-MAY-14:30 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 2017.17 | 01-JUN-09:09 | 2040.25 | 01-JUN-00:10 | 14428.03 | 01-JUN-10:09 | 0.00 | 4802.34 | 05-JUN-13:00 | 0.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 2017.17 | 01-JUL-16:10 | 2040.25 | 01-JUL-00:10 | 14428.03 | 01-JUL-10:09 | 0.00 | 4802.34 | 01-JUL-04:10 | 0.00 | 04-JUL-13:20 | 0.00 | 01-JUL-00:10 |
August | 2017.17 | 01-AUG-09:09 | 2040.25 | 01-AUG-00:10 | 14428.03 | 01-AUG-10:09 | 0.00 | 4802.34 | 01-AUG-04:10 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 2017.17 | 01-SEP-09:09 | 2040.25 | 01-SEP-00:10 | 14428.03 | 01-SEP-10:09 | 0.00 | 4802.34 | 20-SEP-04:10 | 0.00 | 12-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 2017.17 | 02-OCT-09:09 | 2040.25 | 01-OCT-00:10 | 14428.03 | 01-OCT-10:09 | 0.00 | 4802.34 | 01-OCT-04:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 2017.17 | 01-NOV-09:09 | 2040.25 | 01-NOV-00:10 | 14428.03 | 01-NOV-10:09 | 0.00 | 4802.34 | 07-NOV-22:40 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 2017.17 | 01-DEC-10:09 | 2040.25 | 01-DEC-00:10 | 14428.03 | 01-DEC-11:09 | 0.00 | 4802.34 | 03-DEC-05:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 2017.17 | 2040.25 | 14428.03 | 0.00 | 4802.34 | 0.00 | 0.00 | ||||||
Maximum of Months | 2017.17 | 2040.25 | 14428.03 | 0.00 | 4802.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 278.07 | 24-MAR-03:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13186.98 | 18-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13502.86 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16740.96 | 11-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 18263.62 | 26-JUL-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19761.76 | 04-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14832.63 | 06-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4054.74 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 498.67 | 03-NOV-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19761.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 25638.60 | 13-JAN-11:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25644.06 | 08-FEB-11:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25665.68 | 29-MAR-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36477.50 | 18-APR-10:00 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 12295.16 | 0.00 |
May | 36731.71 | 31-MAY-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 10891.84 | 0.00 |
June | 39911.56 | 26-JUN-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 14071.68 | 0.00 |
July | 39451.65 | 03-JUL-10:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 13611.77 | 0.00 |
August | 42352.40 | 04-AUG-11:20 | 2017.17 | 13527.31 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 19003.23 | 0.00 |
September | 37504.84 | 11-SEP-10:00 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 13322.49 | 0.00 |
October | 25760.58 | 20-OCT-15:09 | 2017.17 | 13076.95 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 3827.66 | 0.00 |
November | 25746.34 | 08-NOV-11:09 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25633.03 | 14-DEC-11:20 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 25633.03 | 2017.17 | 13076.95 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42352.40 | 2017.17 | 14428.03 | 0.00 | 0.00 | 4802.34 | 0.00 | 0.00 | 19003.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 147985.20 | 30-JAN-20:10 | 0.00 | 28493.49 | 31-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 163685.98 | 02-FEB-07:10 | 0.00 | 28548.75 | 18-FEB-13:00 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 96880.68 | 05-MAR-20:00 | 0.00 | 28528.60 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 66491.67 | 03-APR-06:10 | 0.00 | 28307.88 | 01-APR-12:00 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 33818.29 | 02-MAY-06:10 | 0.00 | 27849.79 | 01-MAY-12:30 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 18706.39 | 03-JUN-06:10 | 0.00 | 27183.07 | 01-JUN-12:50 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 1469.34 | 23-JUL-06:10 | 0.00 | 26515.67 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 5777.91 | 07-AUG-06:10 | 0.00 | 26034.87 | 01-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 41095.42 | 30-SEP-06:10 | 0.00 | 26315.07 | 29-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 48473.97 | 23-OCT-06:10 | 0.00 | 26970.90 | 31-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 140064.39 | 26-NOV-07:10 | 0.00 | 27633.94 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 131261.01 | 08-DEC-20:00 | 0.00 | 28182.74 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1469.34 | 0.00 | 26034.87 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 163685.98 | 0.00 | 28548.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 17.48 | 0.50 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
February | 23.33 | 18.10 | 10.33 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
March | 4.83 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
April | 0.83 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.21 | 0.00 | 26.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.50 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
December | 11.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
Annual Sum or Average | 62.67 | 17.96 | 10.83 | 18.14 | 1.00 | 18.25 | 0.00 | 18.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.33 | 19.07 | 10.33 | 19.07 | 0.33 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.46 | 0.00 | 28.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 30.14 | 0.00 | 30.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 30.14 | 0.00 | 30.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 30.87 | 0.00 | 30.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 30.18 | 8.00 | 29.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 29.89 | 13.00 | 29.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 30.74 | 0.00 | 30.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 29.23 | 0.00 | 29.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 29.06 | 0.00 | 29.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 127.67 | 30.24 | 21.00 | 29.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 30.87 | 13.00 | 30.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 506.67 | 20.82 | 506.67 | 20.81 |
February | 551.00 | 20.82 | 339.50 | 20.75 | 339.50 | 20.72 |
March | 603.50 | 20.94 | 241.50 | 20.84 | 238.50 | 20.78 |
April | 512.83 | 21.12 | 188.17 | 21.26 | 129.33 | 21.17 |
May | 394.67 | 21.69 | 232.83 | 22.41 | 60.33 | 22.46 |
June | 295.00 | 22.76 | 430.00 | 23.45 | 147.83 | 23.54 |
July | 324.67 | 23.86 | 578.00 | 23.90 | 304.33 | 23.92 |
August | 300.00 | 23.68 | 548.33 | 23.82 | 257.17 | 23.85 |
September | 269.67 | 21.39 | 313.83 | 22.66 | 23.00 | 22.64 |
October | 555.83 | 21.09 | 78.17 | 21.14 | 42.00 | 21.04 |
November | 582.83 | 20.95 | 179.83 | 20.86 | 177.17 | 20.79 |
December | 609.00 | 20.85 | 385.83 | 20.79 | 385.83 | 20.76 |
Annual Sum or Average | 5609.00 | 21.42 | 4022.67 | 21.83 | 2611.67 | 21.79 |
Minimum of Months | 269.67 | 20.82 | 78.17 | 20.75 | 23.00 | 20.72 |
Maximum of Months | 610.00 | 23.86 | 578.00 | 23.90 | 506.67 | 23.92 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 572.00 | 18.72 | 572.00 | 18.72 |
February | 551.00 | 18.73 | 438.83 | 18.71 | 438.83 | 18.70 |
March | 587.67 | 18.91 | 394.33 | 18.90 | 377.50 | 18.83 |
April | 529.17 | 19.90 | 314.83 | 20.24 | 270.00 | 20.25 |
May | 406.33 | 22.82 | 390.50 | 23.66 | 223.50 | 23.98 |
June | 484.17 | 25.08 | 497.33 | 25.34 | 405.67 | 25.54 |
July | 555.67 | 26.01 | 603.33 | 25.92 | 551.83 | 25.96 |
August | 518.67 | 25.93 | 594.00 | 25.80 | 508.50 | 25.88 |
September | 451.17 | 23.39 | 397.67 | 24.15 | 282.17 | 24.47 |
October | 529.83 | 19.46 | 191.50 | 19.83 | 128.67 | 19.72 |
November | 548.50 | 19.00 | 302.50 | 18.99 | 279.50 | 18.90 |
December | 609.00 | 18.72 | 530.50 | 18.71 | 530.50 | 18.71 |
Annual Sum or Average | 6381.17 | 21.22 | 5227.33 | 21.63 | 4568.67 | 21.70 |
Minimum of Months | 406.33 | 18.72 | 191.50 | 18.71 | 128.67 | 18.70 |
Maximum of Months | 610.00 | 26.01 | 603.33 | 25.92 | 572.00 | 25.96 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.84276 | 13.49766 | -0.6987 | 16.29954 |
February | 551.00000 | 20.81621 | 18.12457 | -0.6298 | 14.64443 |
March | 612.00000 | 20.98039 | 24.61124 | -0.4971 | 11.80398 |
April | 590.00000 | 21.47112 | 33.36446 | -0.2672 | 10.13520 |
May | 611.00000 | 22.42772 | 48.55993 | -0.8618 | 25.30612 |
June | 592.00000 | 23.30706 | 56.04508 | -0.4184 | 13.18353 |
July | 609.00000 | 23.84989 | 61.62035 | -0.1494 | 6.30546 |
August | 612.00000 | 23.73741 | 59.55386 | -0.1939 | 7.22045 |
September | 590.00000 | 22.71696 | 43.14175 | -0.6874 | 21.34916 |
October | 610.00000 | 21.31760 | 33.12210 | -0.2290 | 7.82706 |
November | 591.00000 | 20.98690 | 26.79474 | -0.4484 | 10.76828 |
December | 609.00000 | 20.84637 | 16.33570 | -0.6366 | 14.57703 |
Annual Sum or Average | 7187.00000 | 21.94938 | 36.34787 | -0.4755 | 13.26746 |
Minimum of Months | 551.00000 | 20.81621 | 13.49766 | -0.8618 | 6.30546 |
Maximum of Months | 612.00000 | 23.84989 | 61.62035 | -0.1494 | 25.30612 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72396 | 20.06427 | -0.8276 | 20.14039 |
February | 551.00000 | 18.72611 | 25.20688 | -0.7793 | 18.63053 |
March | 612.00000 | 19.10216 | 31.67984 | -0.6166 | 15.41399 |
April | 590.00000 | 20.29871 | 39.13611 | -0.2649 | 15.80593 |
May | 611.00000 | 23.06023 | 49.34275 | -0.3735 | 22.35066 |
June | 592.00000 | 24.76572 | 54.20961 | 0.29423 | 18.52324 |
July | 609.00000 | 25.80331 | 56.94057 | 0.68959 | 17.43933 |
August | 612.00000 | 25.55176 | 55.45802 | 0.60348 | 17.02279 |
September | 590.00000 | 23.44241 | 44.44842 | -0.1929 | 23.86852 |
October | 610.00000 | 20.04429 | 39.15336 | -0.2677 | 11.72870 |
November | 591.00000 | 19.28174 | 33.09450 | -0.5283 | 14.03696 |
December | 609.00000 | 18.72491 | 22.93409 | -0.7702 | 18.16759 |
Annual Sum or Average | 7187.00000 | 21.47857 | 39.39029 | -0.2492 | 17.74972 |
Minimum of Months | 551.00000 | 18.72396 | 20.06427 | -0.8276 | 11.72870 |
Maximum of Months | 612.00000 | 25.80331 | 56.94057 | 0.68959 | 23.86852 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.222969E+10 | 0.628087E+09 | 46.14 | 0.146551E+10 | 0.764182E+09 | 0.00 | 0.59 | 18-APR-12:00 | 0.00 | 01-APR-00:01 | 27330.28 | 18-APR-12:00 | 17727.12 | 15-APR-17:03 | 10686.78 | 18-APR-12:00 | 7225.41 | 18-APR-12:00 | 0.00 | 01-APR-00:01 |
May | 0.335387E+10 | 0.963856E+09 | 94.56 | 0.224901E+10 | 0.110486E+10 | 0.00 | 0.61 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 | 27167.75 | 31-MAY-12:00 | 19238.90 | 31-MAY-12:00 | 8573.22 | 30-MAY-18:00 | 7349.54 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.161063E+11 | 0.446829E+10 | 293.85 | 0.100853E+11 | 0.602102E+10 | 0.00 | 1.00 | 30-JUN-03:01 | 0.00 | 01-JUN-00:01 | 52065.08 | 30-JUN-03:01 | 27112.01 | 30-JUN-03:01 | 24953.07 | 30-JUN-03:01 | 12184.90 | 30-JUN-03:01 | 0.00 | 01-JUN-00:01 |
July | 0.209182E+11 | 0.575481E+10 | 382.80 | 0.121448E+11 | 0.877345E+10 | 0.00 | 1.00 | 26-JUL-03:01 | 0.00 | 01-JUL-00:01 | 52450.38 | 26-JUL-03:01 | 27927.95 | 26-JUL-03:01 | 25715.79 | 26-JUL-03:51 | 12211.16 | 26-JUL-03:01 | 0.00 | 01-JUL-00:01 |
August | 0.188209E+11 | 0.518703E+10 | 340.97 | 0.111627E+11 | 0.765819E+10 | 0.00 | 1.00 | 03-AUG-03:01 | 0.00 | 01-AUG-00:01 | 54565.25 | 03-AUG-03:45 | 22672.73 | 04-AUG-12:00 | 35405.92 | 04-AUG-03:01 | 12361.77 | 03-AUG-03:01 | 0.00 | 01-AUG-00:01 |
September | 0.839972E+10 | 0.241037E+10 | 176.17 | 0.634945E+10 | 0.205027E+10 | 0.00 | 0.66 | 06-SEP-13:00 | 0.00 | 01-SEP-00:01 | 29936.88 | 06-SEP-12:00 | 23060.06 | 07-SEP-13:00 | 10843.19 | 11-SEP-12:00 | 8120.31 | 06-SEP-13:00 | 0.00 | 01-SEP-00:01 |
October | 97882436.20 | 29951159.18 | 6.33 | 87663778.13 | 10218658.06 | 0.00 | 0.20 | 20-OCT-15:00 | 0.00 | 01-OCT-00:01 | 7872.62 | 20-OCT-15:00 | 7227.03 | 20-OCT-14:55 | 679.60 | 20-OCT-15:10 | 2378.49 | 20-OCT-15:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.699266E+11 | 0.194424E+11 | 1340.81 | 0.435444E+11 | 0.263822E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.209182E+11 | 0.575481E+10 | 382.80 | 0.121448E+11 | 0.877345E+10 | 0.00 | 1.00 | 0.00 | 54565.25 | 27927.95 | 35405.92 | 12361.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 914159.03 | 278579.16 | 0.17 | 617673.11 | 296485.92 | 0.00 | 0.16 | 26-MAR-04:01 | 0.00 | 01-MAR-00:01 | 4006.15 | 26-MAR-04:01 | 2143.44 | 26-MAR-04:01 | 1862.71 | 26-MAR-04:01 | 1201.06 | 26-MAR-04:01 | 0.00 | 01-MAR-00:01 |
April | 0.244943E+10 | 0.631843E+09 | 53.46 | 0.161351E+10 | 0.835922E+09 | 0.00 | 1.00 | 16-APR-02:12 | 0.00 | 01-APR-00:01 | 31982.30 | 16-APR-03:32 | 19167.91 | 18-APR-03:21 | 15343.07 | 16-APR-02:52 | 7667.73 | 16-APR-02:12 | 0.00 | 01-APR-00:01 |
May | 0.421525E+10 | 0.113717E+10 | 123.23 | 0.277351E+10 | 0.144174E+10 | 0.00 | 1.00 | 05-MAY-03:21 | 0.00 | 01-MAY-00:01 | 31982.30 | 16-MAY-04:01 | 20841.11 | 05-MAY-03:21 | 19113.76 | 12-MAY-03:11 | 7667.73 | 05-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.191150E+11 | 0.481981E+10 | 337.97 | 0.117501E+11 | 0.736490E+10 | 0.00 | 1.00 | 08-JUN-04:01 | 0.00 | 01-JUN-00:01 | 35534.44 | 27-JUN-10:50 | 23076.44 | 25-JUN-14:10 | 21133.83 | 26-JUN-04:01 | 8359.90 | 11-JUN-14:53 | 0.00 | 01-JUN-00:01 |
July | 0.255212E+11 | 0.641709E+10 | 438.22 | 0.139666E+11 | 0.115546E+11 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 35534.44 | 26-JUL-16:53 | 19858.58 | 02-JUL-11:07 | 23136.83 | 26-JUL-19:00 | 7999.65 | 03-JUL-14:55 | 0.00 | 01-JUL-00:01 |
August | 0.227902E+11 | 0.575696E+10 | 400.26 | 0.127116E+11 | 0.100786E+11 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 35534.44 | 03-AUG-11:47 | 21926.26 | 04-AUG-14:55 | 24508.86 | 04-AUG-04:13 | 8435.07 | 04-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.915890E+10 | 0.244719E+10 | 219.25 | 0.701580E+10 | 0.214310E+10 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 33087.58 | 12-SEP-02:52 | 23451.02 | 07-SEP-14:00 | 20578.57 | 12-SEP-02:52 | 7741.73 | 12-SEP-02:52 | 0.00 | 01-SEP-00:01 |
October | 0.123944E+09 | 36755390.35 | 10.08 | 0.102165E+09 | 21778893.73 | 0.00 | 1.00 | 21-OCT-04:01 | 0.00 | 01-OCT-00:01 | 31982.30 | 21-OCT-04:01 | 22599.25 | 22-OCT-04:01 | 11286.29 | 02-OCT-04:01 | 7667.73 | 21-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 6236359.43 | 1846429.42 | 0.54 | 3374112.48 | 2862246.94 | 0.00 | 0.44 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 | 12111.58 | 09-NOV-05:01 | 6483.56 | 09-NOV-05:01 | 5628.01 | 09-NOV-05:01 | 3385.41 | 09-NOV-05:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.833810E+11 | 0.212489E+11 | 1583.20 | 0.499372E+11 | 0.334438E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.255212E+11 | 0.641709E+10 | 438.22 | 0.139666E+11 | 0.115546E+11 | 0.00 | 1.00 | 0.00 | 35534.44 | 23451.02 | 24508.86 | 8435.07 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.29 | 34.27 | 49.02 | 36.32 | 289.89 | 0.00 | 0.00 | 0.00 |
February | 110.40 | 48.55 | 61.86 | 64.51 | 227.54 | 0.00 | 0.00 | 0.00 |
March | 150.00 | 59.54 | 90.46 | 120.31 | 146.05 | 0.00 | 0.00 | 0.00 |
April | 184.19 | 80.66 | 103.53 | 184.08 | 101.39 | 0.00 | 0.00 | 0.00 |
May | 231.33 | 101.08 | 130.25 | 270.15 | 59.15 | 0.00 | 0.00 | 0.00 |
June | 254.57 | 110.86 | 143.71 | 323.95 | 43.30 | 0.00 | 0.00 | 0.00 |
July | 257.30 | 118.73 | 138.58 | 332.66 | 39.95 | 0.00 | 0.00 | 0.00 |
August | 216.90 | 93.51 | 123.39 | 279.50 | 47.36 | 0.00 | 0.00 | 0.00 |
September | 193.46 | 91.42 | 102.04 | 232.35 | 75.71 | 0.00 | 0.00 | 0.00 |
October | 123.28 | 51.49 | 71.79 | 112.88 | 113.64 | 0.00 | 0.00 | 0.00 |
November | 72.74 | 23.63 | 49.11 | 39.38 | 179.69 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 24.20 | 32.15 | 24.97 | 262.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.40 | 69.93 | 91.47 | 168.99 | 131.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 23.63 | 32.15 | 24.97 | 39.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 257.30 | 118.73 | 143.71 | 332.66 | 289.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.48 | 330.85 | 152.62 | 435.23 | 520.83 | 0.00 | 0.00 | 0.00 |
February | 518.04 | 349.99 | 168.05 | 488.32 | 413.81 | 0.00 | 0.00 | 0.00 |
March | 450.81 | 237.38 | 213.43 | 452.29 | 290.83 | 0.00 | 0.00 | 0.00 |
April | 406.15 | 189.88 | 216.27 | 454.52 | 210.38 | 0.00 | 0.00 | 0.00 |
May | 336.48 | 91.22 | 245.26 | 403.68 | 126.11 | 0.00 | 0.00 | 0.00 |
June | 326.67 | 66.51 | 260.16 | 427.73 | 91.32 | 0.00 | 0.00 | 0.00 |
July | 345.81 | 87.13 | 258.67 | 467.73 | 83.72 | 0.00 | 0.00 | 0.00 |
August | 389.61 | 139.72 | 249.89 | 532.34 | 99.62 | 0.00 | 0.00 | 0.00 |
September | 472.12 | 248.77 | 223.35 | 606.21 | 155.42 | 0.00 | 0.00 | 0.00 |
October | 493.00 | 309.28 | 183.71 | 559.87 | 225.84 | 0.00 | 0.00 | 0.00 |
November | 371.96 | 232.86 | 139.11 | 357.92 | 337.45 | 0.00 | 0.00 | 0.00 |
December | 396.65 | 300.45 | 96.19 | 382.91 | 482.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 415.30 | 214.57 | 200.73 | 463.89 | 252.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.67 | 66.51 | 96.19 | 357.92 | 83.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.04 | 349.99 | 260.16 | 606.21 | 520.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 33.42 | 49.18 | 37.26 | 296.28 | 0.00 | 0.00 | 0.00 |
February | 121.12 | 59.69 | 61.44 | 79.22 | 234.43 | 0.00 | 0.00 | 0.00 |
March | 144.60 | 53.80 | 90.80 | 113.38 | 150.04 | 0.00 | 0.00 | 0.00 |
April | 210.92 | 104.30 | 106.63 | 222.28 | 103.42 | 0.00 | 0.00 | 0.00 |
May | 211.53 | 84.50 | 127.03 | 246.50 | 61.42 | 0.00 | 0.00 | 0.00 |
June | 248.21 | 107.57 | 140.64 | 316.38 | 45.00 | 0.00 | 0.00 | 0.00 |
July | 266.50 | 126.59 | 139.91 | 347.16 | 41.46 | 0.00 | 0.00 | 0.00 |
August | 232.99 | 106.93 | 126.06 | 303.63 | 49.16 | 0.00 | 0.00 | 0.00 |
September | 188.60 | 89.52 | 99.08 | 225.74 | 77.56 | 0.00 | 0.00 | 0.00 |
October | 131.42 | 58.43 | 72.99 | 125.11 | 117.59 | 0.00 | 0.00 | 0.00 |
November | 78.67 | 29.09 | 49.58 | 49.34 | 183.15 | 0.00 | 0.00 | 0.00 |
December | 60.50 | 28.52 | 31.98 | 32.37 | 267.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.98 | 73.54 | 91.44 | 175.34 | 135.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.50 | 28.52 | 31.98 | 32.37 | 41.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.50 | 126.59 | 140.64 | 347.16 | 296.28 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223086E+09 | 91800452.76 | 0.131286E+09 | 97285232.67 | 0.776445E+09 |
February | 0.267083E+09 | 0.117442E+09 | 0.149642E+09 | 0.156055E+09 | 0.550465E+09 |
March | 0.401765E+09 | 0.159472E+09 | 0.242293E+09 | 0.322235E+09 | 0.391190E+09 |
April | 0.477415E+09 | 0.209075E+09 | 0.268340E+09 | 0.477138E+09 | 0.262811E+09 |
May | 0.619582E+09 | 0.270729E+09 | 0.348853E+09 | 0.723564E+09 | 0.158417E+09 |
June | 0.659839E+09 | 0.287349E+09 | 0.372490E+09 | 0.839688E+09 | 0.112230E+09 |
July | 0.689159E+09 | 0.317993E+09 | 0.371166E+09 | 0.890999E+09 | 0.106991E+09 |
August | 0.580948E+09 | 0.250459E+09 | 0.330489E+09 | 0.748606E+09 | 0.126838E+09 |
September | 0.501438E+09 | 0.236955E+09 | 0.264483E+09 | 0.602256E+09 | 0.196248E+09 |
October | 0.330203E+09 | 0.137923E+09 | 0.192280E+09 | 0.302341E+09 | 0.304365E+09 |
November | 0.188538E+09 | 61240585.29 | 0.127298E+09 | 0.102074E+09 | 0.465745E+09 |
December | 0.150911E+09 | 64804922.64 | 86106467.03 | 66883518.69 | 0.703181E+09 |
Annual Sum or Average | 0.508997E+10 | 0.220524E+10 | 0.288472E+10 | 0.532913E+10 | 0.415493E+10 |
Minimum of Months | 0.150911E+09 | 61240585.29 | 86106467.03 | 66883518.69 | 0.106991E+09 |
Maximum of Months | 0.689159E+09 | 0.317993E+09 | 0.372490E+09 | 0.890999E+09 | 0.776445E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129495E+10 | 0.886161E+09 | 0.408788E+09 | 0.116571E+10 | 0.139499E+10 |
February | 0.125324E+10 | 0.846697E+09 | 0.406541E+09 | 0.118134E+10 | 0.100109E+10 |
March | 0.120745E+10 | 0.635802E+09 | 0.571647E+09 | 0.121141E+10 | 0.778963E+09 |
April | 0.105274E+10 | 0.492176E+09 | 0.560564E+09 | 0.117811E+10 | 0.545306E+09 |
May | 0.901232E+09 | 0.244336E+09 | 0.656896E+09 | 0.108122E+10 | 0.337779E+09 |
June | 0.846735E+09 | 0.172400E+09 | 0.674336E+09 | 0.110868E+10 | 0.236709E+09 |
July | 0.926207E+09 | 0.233379E+09 | 0.692828E+09 | 0.125278E+10 | 0.224239E+09 |
August | 0.104353E+10 | 0.374233E+09 | 0.669294E+09 | 0.142581E+10 | 0.266823E+09 |
September | 0.122374E+10 | 0.644811E+09 | 0.578931E+09 | 0.157129E+10 | 0.402861E+09 |
October | 0.132044E+10 | 0.828389E+09 | 0.492049E+09 | 0.149957E+10 | 0.604903E+09 |
November | 0.964130E+09 | 0.603563E+09 | 0.360567E+09 | 0.927741E+09 | 0.874661E+09 |
December | 0.106238E+10 | 0.804736E+09 | 0.257639E+09 | 0.102560E+10 | 0.129244E+10 |
Annual Sum or Average | 0.130968E+11 | 0.676668E+10 | 0.633008E+10 | 0.146293E+11 | 0.796076E+10 |
Minimum of Months | 0.846735E+09 | 0.172400E+09 | 0.257639E+09 | 0.927741E+09 | 0.224239E+09 |
Maximum of Months | 0.132044E+10 | 0.886161E+09 | 0.692828E+09 | 0.157129E+10 | 0.139499E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221247E+09 | 89518934.04 | 0.131728E+09 | 99788229.07 | 0.793563E+09 |
February | 0.293024E+09 | 0.144393E+09 | 0.148631E+09 | 0.191647E+09 | 0.567142E+09 |
March | 0.387289E+09 | 0.144093E+09 | 0.243197E+09 | 0.303674E+09 | 0.401860E+09 |
April | 0.546716E+09 | 0.270341E+09 | 0.276375E+09 | 0.576145E+09 | 0.268065E+09 |
May | 0.566574E+09 | 0.226333E+09 | 0.340242E+09 | 0.660222E+09 | 0.164515E+09 |
June | 0.643362E+09 | 0.278817E+09 | 0.364545E+09 | 0.820046E+09 | 0.116634E+09 |
July | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.929822E+09 | 0.111053E+09 |
August | 0.624042E+09 | 0.286394E+09 | 0.337648E+09 | 0.813255E+09 | 0.131675E+09 |
September | 0.488849E+09 | 0.232033E+09 | 0.256817E+09 | 0.585110E+09 | 0.201023E+09 |
October | 0.352005E+09 | 0.156497E+09 | 0.195508E+09 | 0.335086E+09 | 0.314957E+09 |
November | 0.203902E+09 | 75402587.82 | 0.128499E+09 | 0.127890E+09 | 0.474714E+09 |
December | 0.162038E+09 | 76386940.35 | 85651040.84 | 86708348.43 | 0.717449E+09 |
Annual Sum or Average | 0.520285E+10 | 0.231927E+10 | 0.288357E+10 | 0.552939E+10 | 0.426265E+10 |
Minimum of Months | 0.162038E+09 | 75402587.82 | 85651040.84 | 86708348.43 | 0.111053E+09 |
Maximum of Months | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.929822E+09 | 0.793563E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.03 | 1054.23 | 649.37 | 398.55 | 250.82 | 0.00 | 0.00 |
February | 585.49 | 829.23 | 749.56 | 458.22 | 291.34 | 0.00 | 0.00 |
March | 665.99 | 566.93 | 745.41 | 350.72 | 394.69 | 0.00 | 0.00 |
April | 845.26 | 399.57 | 801.26 | 374.84 | 426.42 | 0.00 | 0.00 |
May | 909.31 | 235.67 | 779.34 | 276.81 | 502.54 | 0.00 | 0.00 |
June | 1061.50 | 173.06 | 829.45 | 284.94 | 544.51 | 0.00 | 0.00 |
July | 1142.85 | 160.43 | 869.61 | 332.45 | 537.16 | 0.00 | 0.00 |
August | 1109.48 | 190.15 | 839.50 | 340.16 | 499.34 | 0.00 | 0.00 |
September | 1056.74 | 301.14 | 854.18 | 429.71 | 424.47 | 0.00 | 0.00 |
October | 788.11 | 447.32 | 747.70 | 419.21 | 328.49 | 0.00 | 0.00 |
November | 426.42 | 680.05 | 523.37 | 285.57 | 237.79 | 0.00 | 0.00 |
December | 405.09 | 977.78 | 513.49 | 353.17 | 160.32 | 0.00 | 0.00 |
Annual Sum or Average | 788.70 | 499.84 | 741.68 | 358.04 | 383.64 | 0.00 | 0.00 |
Minimum of Months | 405.09 | 160.43 | 513.49 | 276.81 | 160.32 | 0.00 | 0.00 |
Maximum of Months | 1142.85 | 1054.23 | 869.61 | 458.22 | 544.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122144E+10 | 0.282365E+10 | 0.173928E+10 | 0.106748E+10 | 0.671801E+09 | 0.00 | 0.00 |
February | 0.141642E+10 | 0.200606E+10 | 0.181335E+10 | 0.110853E+10 | 0.704813E+09 | 0.00 | 0.00 |
March | 0.178378E+10 | 0.151848E+10 | 0.199650E+10 | 0.939367E+09 | 0.105714E+10 | 0.00 | 0.00 |
April | 0.219090E+10 | 0.103569E+10 | 0.207687E+10 | 0.971592E+09 | 0.110528E+10 | 0.00 | 0.00 |
May | 0.243550E+10 | 0.631210E+09 | 0.208739E+10 | 0.741397E+09 | 0.134599E+10 | 0.00 | 0.00 |
June | 0.275141E+10 | 0.448568E+09 | 0.214994E+10 | 0.738566E+09 | 0.141137E+10 | 0.00 | 0.00 |
July | 0.306102E+10 | 0.429700E+09 | 0.232917E+10 | 0.890438E+09 | 0.143873E+10 | 0.00 | 0.00 |
August | 0.297164E+10 | 0.509298E+09 | 0.224852E+10 | 0.911086E+09 | 0.133743E+10 | 0.00 | 0.00 |
September | 0.273907E+10 | 0.780547E+09 | 0.221403E+10 | 0.111380E+10 | 0.110023E+10 | 0.00 | 0.00 |
October | 0.211089E+10 | 0.119811E+10 | 0.200265E+10 | 0.112281E+10 | 0.879837E+09 | 0.00 | 0.00 |
November | 0.110528E+10 | 0.176269E+10 | 0.135657E+10 | 0.740207E+09 | 0.616364E+09 | 0.00 | 0.00 |
December | 0.108500E+10 | 0.261888E+10 | 0.137532E+10 | 0.945928E+09 | 0.429397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.248723E+11 | 0.157629E+11 | 0.233896E+11 | 0.112912E+11 | 0.120984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108500E+10 | 0.429700E+09 | 0.135657E+10 | 0.738566E+09 | 0.429397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.306102E+10 | 0.282365E+10 | 0.232917E+10 | 0.112281E+10 | 0.143873E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.158709E+11 | -0.150673E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -803554499.8 | 58.99 | 0.00 | 0.00 |
February | 0.146105E+11 | -0.138858E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -724684347.6 | 59.00 | 0.00 | 0.00 |
March | 0.160426E+11 | -0.152504E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -792197971.9 | 58.99 | 0.00 | 0.00 |
April | 0.148944E+11 | -0.141519E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -742425540.6 | 58.99 | 0.00 | 0.00 |
May | 0.144826E+11 | -0.137706E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -711985879.4 | 58.99 | 0.00 | 0.00 |
June | 0.130982E+11 | -0.124409E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -657252205.8 | 58.98 | 0.00 | 0.00 |
July | 0.127582E+11 | -0.120977E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -660500783.8 | 59.00 | 0.00 | 0.00 |
August | 0.124705E+11 | -0.118059E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -664606520.5 | 59.00 | 0.00 | 0.00 |
September | 0.122345E+11 | -0.115534E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -681140304.6 | 59.00 | 0.00 | 0.00 |
October | 0.133157E+11 | -0.125467E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -768969259.0 | 58.99 | 0.00 | 0.00 |
November | 0.137626E+11 | -0.130012E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -761417024.5 | 58.98 | 0.00 | 0.00 |
December | 0.151295E+11 | -0.143283E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -801189716.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.168670E+12 | -0.159900E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.876992E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.122345E+11 | -0.152504E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -803554499.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.160426E+11 | -0.115534E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -657252205.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686631E+11 | 66628.69 | 03-JAN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492550E+11 | 66628.69 | 01-FEB-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327171E+11 | 66628.69 | 04-MAR-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172329E+11 | 40622.30 | 03-APR-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.269301E+10 | 23363.27 | 02-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.822989E+09 | 9753.51 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2149232.92 | 1180.21 | 23-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33234165.18 | 4622.67 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.307010E+10 | 20502.43 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126565E+11 | 22799.14 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322146E+11 | 66628.69 | 21-NOV-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.546257E+11 | 66628.69 | 06-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2149232.92 | 1180.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686631E+11 | 66628.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.695389E+11 | 80333.49 | 31-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488829E+11 | 83745.78 | 03-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298749E+11 | 55412.26 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139074E+11 | 40295.32 | 01-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122686E+10 | 18317.54 | 03-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142213E+09 | 7646.94 | 01-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149176E+10 | 22798.76 | 30-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839308E+10 | 24023.28 | 23-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294485E+11 | 67980.86 | 26-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532910E+11 | 64700.97 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.695389E+11 | 83745.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222969E+10 | 0.146551E+10 | 27330.28 | 18-APR-12:00 | 16643.50 | 0.00 |
May | 0.00 | 0.00 | 0.335387E+10 | 0.224901E+10 | 27167.75 | 31-MAY-12:00 | 19238.90 | 0.00 |
June | 0.00 | 0.00 | 0.161063E+11 | 0.100853E+11 | 52065.08 | 30-JUN-03:01 | 27112.01 | 0.00 |
July | 0.00 | 0.00 | 0.209182E+11 | 0.121448E+11 | 52450.38 | 26-JUL-03:01 | 27927.95 | 0.00 |
August | 0.00 | 0.00 | 0.188209E+11 | 0.111627E+11 | 54565.25 | 03-AUG-03:45 | 22009.14 | 0.00 |
September | 0.00 | 0.00 | 0.839972E+10 | 0.634945E+10 | 29936.88 | 06-SEP-12:00 | 20532.43 | 0.00 |
October | 0.00 | 0.00 | 97882436.20 | 87663778.13 | 7872.62 | 20-OCT-15:00 | 7226.92 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.699266E+11 | 0.435444E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209182E+11 | 0.121448E+11 | 54565.25 | 27927.95 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 914159.03 | 617673.11 | 4006.15 | 26-MAR-04:01 | 2143.44 | 0.00 |
April | 0.00 | 0.00 | 0.244943E+10 | 0.161351E+10 | 31982.30 | 16-APR-03:32 | 16925.18 | 0.00 |
May | 0.00 | 0.00 | 0.421525E+10 | 0.277351E+10 | 31982.30 | 16-MAY-04:01 | 16561.41 | 0.00 |
June | 0.00 | 0.00 | 0.191150E+11 | 0.117501E+11 | 35534.44 | 27-JUN-10:50 | 19983.56 | 0.00 |
July | 0.00 | 0.00 | 0.255212E+11 | 0.139666E+11 | 35534.44 | 26-JUL-16:53 | 14944.21 | 0.00 |
August | 0.00 | 0.00 | 0.227902E+11 | 0.127116E+11 | 35534.44 | 03-AUG-11:47 | 16597.34 | 0.00 |
September | 0.00 | 0.00 | 0.915890E+10 | 0.701580E+10 | 33087.58 | 12-SEP-02:52 | 12509.01 | 0.00 |
October | 0.00 | 0.00 | 0.123944E+09 | 0.102165E+09 | 31982.30 | 21-OCT-04:01 | 20859.37 | 0.00 |
November | 0.00 | 0.00 | 6236359.43 | 3374112.48 | 12111.58 | 09-NOV-05:01 | 6483.56 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.833810E+11 | 0.499372E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.255212E+11 | 0.139666E+11 | 35534.44 | 20859.37 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5920.45 | 22339.92 | 31-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6035.63 | 22493.64 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5991.11 | 22457.15 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5752.94 | 21864.39 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5434.83 | 20758.77 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5093.18 | 19371.44 | 01-JUN-12:25 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4807.23 | 18146.59 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4701.23 | 17350.87 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4748.44 | 17791.34 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4975.93 | 18924.11 | 31-OCT-12:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5309.22 | 20267.23 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5642.26 | 21537.75 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.77 | ||||
Minimum of Months | 0.00 | 0.00 | 4701.23 | 17350.87 | ||
Maximum of Months | 0.00 | 0.00 | 6035.63 | 22493.64 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270490E+10 | 0.56 | 1211.87 | 01-JAN-00:01 | 0.67 |
February | 0.244314E+10 | 0.56 | 1211.87 | 01-FEB-00:01 | 0.67 |
March | 0.271254E+10 | 0.56 | 1211.87 | 01-MAR-00:01 | 0.67 |
April | 0.266727E+10 | 0.57 | 1211.87 | 01-APR-04:01 | 0.66 |
May | 0.286254E+10 | 0.58 | 1211.87 | 01-MAY-04:01 | 0.66 |
June | 0.292583E+10 | 0.62 | 1211.87 | 01-JUN-00:20 | 0.67 |
July | 0.308982E+10 | 0.63 | 1211.87 | 01-JUL-00:13 | 0.66 |
August | 0.307522E+10 | 0.63 | 1211.87 | 01-AUG-00:15 | 0.66 |
September | 0.285894E+10 | 0.60 | 1211.87 | 01-SEP-00:17 | 0.66 |
October | 0.275453E+10 | 0.57 | 1211.87 | 01-OCT-04:01 | 0.66 |
November | 0.263546E+10 | 0.56 | 1211.87 | 01-NOV-04:01 | 0.66 |
December | 0.270490E+10 | 0.56 | 1211.87 | 01-DEC-00:01 | 0.67 |
Annual Sum or Average | 0.334351E+11 | 0.58 | |||
Minimum of Months | 0.244314E+10 | 0.56 | 1211.87 | 0.66 | |
Maximum of Months | 0.308982E+10 | 0.63 | 1211.87 | 0.67 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.490644E+10 | 0.80 | 2145.08 | 02-JAN-00:20 | 0.92 |
February | 0.440085E+10 | 0.80 | 2145.08 | 22-FEB-09:45 | 0.92 |
March | 0.482720E+10 | 0.79 | 2145.08 | 20-MAR-13:20 | 0.92 |
April | 0.463990E+10 | 0.78 | 2145.08 | 09-APR-16:00 | 0.92 |
May | 0.478788E+10 | 0.76 | 2145.08 | 01-MAY-14:30 | 0.92 |
June | 0.463633E+10 | 0.76 | 2145.08 | 02-JUN-20:40 | 0.91 |
July | 0.479310E+10 | 0.77 | 2145.08 | 13-JUL-08:16 | 0.91 |
August | 0.479304E+10 | 0.76 | 2145.08 | 16-AUG-09:48 | 0.91 |
September | 0.463560E+10 | 0.77 | 2145.08 | 05-SEP-07:10 | 0.91 |
October | 0.478781E+10 | 0.77 | 2145.08 | 01-OCT-08:22 | 0.92 |
November | 0.467347E+10 | 0.78 | 2145.08 | 01-NOV-10:08 | 0.92 |
December | 0.487976E+10 | 0.80 | 2145.08 | 15-DEC-00:09 | 0.92 |
Annual Sum or Average | 0.567614E+11 | 0.78 | |||
Minimum of Months | 0.440085E+10 | 0.76 | 2145.08 | 0.91 | |
Maximum of Months | 0.490644E+10 | 0.80 | 2145.08 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.322610E+10 | 0.80 | 1445.38 | 01-JAN-00:07 | 0.95 |
February | 0.291390E+10 | 0.80 | 1445.38 | 14-FEB-06:10 | 0.95 |
March | 0.322652E+10 | 0.80 | 1445.38 | 06-MAR-23:10 | 0.96 |
April | 0.313033E+10 | 0.81 | 1445.38 | 01-APR-04:15 | 0.95 |
May | 0.325013E+10 | 0.83 | 1445.38 | 01-MAY-06:30 | 0.95 |
June | 0.320117E+10 | 0.87 | 1445.38 | 01-JUN-04:40 | 0.95 |
July | 0.333874E+10 | 0.89 | 1445.38 | 23-JUL-18:08 | 0.95 |
August | 0.332262E+10 | 0.88 | 1445.38 | 07-AUG-14:55 | 0.95 |
September | 0.317662E+10 | 0.86 | 1445.38 | 01-SEP-09:13 | 0.95 |
October | 0.323092E+10 | 0.81 | 1445.38 | 01-OCT-04:05 | 0.95 |
November | 0.312432E+10 | 0.80 | 1445.38 | 04-NOV-04:20 | 0.95 |
December | 0.322610E+10 | 0.80 | 1445.38 | 01-DEC-05:07 | 0.95 |
Annual Sum or Average | 0.383674E+11 | 0.83 | |||
Minimum of Months | 0.291390E+10 | 0.80 | 1445.38 | 0.95 | |
Maximum of Months | 0.333874E+10 | 0.89 | 1445.38 | 0.96 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.23 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.69 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.37 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.08 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.75 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.89 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.65 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.20 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:05 | 0.00 | 0.00 | 52.16 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.94 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 52.09 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.48 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.23 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.65 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 35.94 | 35.94 | 5920.45 | 22339.92 | 31-JAN-14:00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.86 | 50.86 | 6035.63 | 22493.64 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 50.66 | 50.66 | 5991.11 | 22457.15 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.05 | 51.05 | 5752.94 | 21864.39 | 01-APR-12:30 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 36.70 | 36.70 | 5434.83 | 20758.77 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.05 | 52.05 | 5093.18 | 19371.44 | 01-JUN-12:25 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.61 | 52.61 | 4807.23 | 18146.59 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.17 | 52.17 | 4701.23 | 17350.87 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.26 | 52.26 | 4748.44 | 17791.34 | 30-SEP-12:15 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 39.95 | 39.95 | 4975.93 | 18924.11 | 31-OCT-12:35 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.82 | 51.82 | 5309.22 | 20267.23 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.34 | 51.34 | 5642.26 | 21537.75 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.77 | ||||||
Minimum of Months | 0.00 | 0.00 | 35.94 | 35.94 | 4701.23 | 17350.87 | ||
Maximum of Months | 0.00 | 0.00 | 52.61 | 52.61 | 6035.63 | 22493.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.490644E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.440085E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.482720E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.526798E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.575173E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.910461E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.105479E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.998007E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.704598E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.481777E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.467347E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.487976E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.762038E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.440085E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.105479E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.322610E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.291390E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.322680E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.376217E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.438730E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.802097E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.975583E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.907958E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.562381E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.326767E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.312617E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.322610E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.596164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.291390E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.975583E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.490644E+10 | 0.00 | 0.686631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440085E+10 | 0.00 | 0.492550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482720E+10 | 0.00 | 0.327171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463990E+10 | 0.222969E+10 | 0.172329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478788E+10 | 0.335387E+10 | 0.269301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463633E+10 | 0.161063E+11 | 0.822989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.479310E+10 | 0.209182E+11 | 2149232.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.479304E+10 | 0.188209E+11 | 33234165.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.463560E+10 | 0.839972E+10 | 0.307010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.478781E+10 | 97882436.20 | 0.126565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467347E+10 | 0.00 | 0.322146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487976E+10 | 0.00 | 0.546257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567614E+11 | 0.699266E+11 | 0.273986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.440085E+10 | 0.00 | 2149232.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.490644E+10 | 0.209182E+11 | 0.686631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.322610E+10 | 0.00 | 0.695389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291390E+10 | 0.00 | 0.488829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322652E+10 | 914159.03 | 0.298749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313033E+10 | 0.244943E+10 | 0.139074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.325013E+10 | 0.421525E+10 | 0.122686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320117E+10 | 0.191150E+11 | 0.142213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.333874E+10 | 0.255212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332262E+10 | 0.227902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317662E+10 | 0.915890E+10 | 0.149176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323092E+10 | 0.123944E+09 | 0.839308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312432E+10 | 6236359.43 | 0.294485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322610E+10 | 0.00 | 0.532910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383674E+11 | 0.833810E+11 | 0.256198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.291390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333874E+10 | 0.255212E+11 | 0.695389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.490644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.463990E+10 | 0.00 | 0.00 | 0.00 | 0.628087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478788E+10 | 0.00 | 0.00 | 0.00 | 0.963856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.463633E+10 | 0.00 | 0.00 | 0.00 | 0.446829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.479310E+10 | 0.00 | 0.00 | 0.00 | 0.575481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.479304E+10 | 0.00 | 0.00 | 0.00 | 0.518703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.463560E+10 | 0.00 | 0.00 | 0.00 | 0.241037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.478781E+10 | 0.00 | 0.00 | 0.00 | 29951159.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.487976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.567614E+11 | 0.00 | 0.00 | 0.00 | 0.194424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.440085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.490644E+10 | 0.00 | 0.00 | 0.00 | 0.575481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.322610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322652E+10 | 0.00 | 0.00 | 0.00 | 278579.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313033E+10 | 0.00 | 0.00 | 0.00 | 0.631843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.325013E+10 | 0.00 | 0.00 | 0.00 | 0.113717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.320117E+10 | 0.00 | 0.00 | 0.00 | 0.481981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.333874E+10 | 0.00 | 0.00 | 0.00 | 0.641709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.332262E+10 | 0.00 | 0.00 | 0.00 | 0.575696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317662E+10 | 0.00 | 0.00 | 0.00 | 0.244719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323092E+10 | 0.00 | 0.00 | 0.00 | 36755390.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.312432E+10 | 0.00 | 0.00 | 0.00 | 1846429.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383674E+11 | 0.00 | 0.00 | 0.00 | 0.212489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.291390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333874E+10 | 0.00 | 0.00 | 0.00 | 0.641709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396704E+11 | 0.00 | 0.00 | 3.60 |
February | 0.134252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301903E+11 | 0.00 | 0.00 | 3.61 |
March | 0.221026E+10 | 0.00 | 0.00 | 202690.99 | 0.00 | 0.226971E+11 | 0.190576E+09 | 0.00 | 3.61 |
April | 0.320409E+10 | 0.329398E+09 | 0.00 | 2483261.14 | 0.00 | 0.131251E+11 | 0.924562E+09 | 0.00 | 3.99 |
May | 0.590853E+10 | 0.290829E+09 | 0.00 | 8539278.33 | 0.00 | 0.235938E+10 | 0.343455E+10 | 0.00 | 4.87 |
June | 0.279442E+10 | 0.267214E+10 | 0.00 | 15182439.83 | 3500107.29 | 0.827160E+09 | 0.419934E+10 | 0.00 | 5.96 |
July | 0.109246E+10 | 0.315421E+10 | 0.00 | 21616322.07 | 1603899.93 | 0.00 | 0.567204E+10 | 0.00 | 7.06 |
August | 0.164869E+10 | 0.292819E+10 | 0.00 | 21031301.60 | 7418902.75 | 11073919.26 | 0.608653E+10 | 0.00 | 6.72 |
September | 0.433824E+10 | 0.859579E+09 | 0.00 | 14909618.74 | 0.00 | 0.254091E+10 | 0.415346E+10 | 0.00 | 5.33 |
October | 0.556974E+10 | 0.00 | 0.00 | 1519137.72 | 0.00 | 0.104955E+11 | 0.915337E+09 | 0.00 | 3.77 |
November | 0.301056E+10 | 0.00 | 0.00 | 95120.56 | 0.00 | 0.217380E+11 | 0.108430E+09 | 0.00 | 3.58 |
December | 0.140325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337462E+11 | 0.00 | 0.00 | 3.57 |
Annual Sum or Average | 0.341237E+11 | 0.102343E+11 | 0.00 | 85579170.98 | 12522909.97 | 0.177401E+12 | 0.256848E+11 | 0.00 | 4.65 |
Minimum of Months | 0.109246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
Maximum of Months | 0.590853E+10 | 0.315421E+10 | 0.00 | 21616322.07 | 7418902.75 | 0.396704E+11 | 0.608653E+10 | 0.00 | 7.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101524E+12 | 0.00 | 0.00 | 22653.20 | 0.00 | 0.142810E+09 | 6740788.55 | 0.00 | 9.65 |
February | 0.785099E+11 | 0.00 | 0.00 | 54270.10 | 0.00 | 74461374.25 | 15590406.53 | 0.00 | 9.68 |
March | 0.633143E+11 | 0.00 | 0.00 | 502559.48 | 0.00 | 34006175.41 | 0.843561E+09 | 0.00 | 9.73 |
April | 0.423964E+11 | 0.267976E+09 | 0.00 | 9601665.40 | 0.00 | 13322607.94 | 0.354888E+10 | 0.00 | 9.85 |
May | 0.188242E+11 | 0.159557E+09 | 0.00 | 31098853.97 | 0.00 | 0.00 | 0.147846E+11 | 0.00 | 10.20 |
June | 0.888626E+10 | 0.337935E+10 | 0.00 | 49824228.05 | 1384125.13 | 0.00 | 0.123589E+11 | 0.00 | 10.78 |
July | 0.250536E+10 | 0.389154E+10 | 0.00 | 72446242.09 | 1496383.33 | 0.00 | 0.144472E+11 | 0.00 | 11.17 |
August | 0.362331E+10 | 0.378038E+10 | 0.00 | 67685176.67 | 3712479.04 | 0.00 | 0.160616E+11 | 0.00 | 11.04 |
September | 0.159529E+11 | 0.448779E+09 | 0.00 | 47830766.40 | 0.00 | 0.00 | 0.145234E+11 | 0.00 | 10.44 |
October | 0.408510E+11 | 0.00 | 0.00 | 5369153.15 | 0.00 | 0.00 | 0.485478E+10 | 0.00 | 9.76 |
November | 0.617797E+11 | 0.00 | 0.00 | 1028783.46 | 0.00 | 37140018.35 | 0.180460E+10 | 0.00 | 9.71 |
December | 0.865101E+11 | 0.00 | 0.00 | 47784.76 | 0.00 | 66643104.05 | 23391604.74 | 0.00 | 9.61 |
Annual Sum or Average | 0.524677E+12 | 0.119276E+11 | 0.00 | 0.285512E+09 | 6592987.51 | 0.368384E+09 | 0.832732E+11 | 0.00 | 10.14 |
Minimum of Months | 0.250536E+10 | 0.00 | 0.00 | 22653.20 | 0.00 | 0.00 | 6740788.55 | 0.00 | 9.61 |
Maximum of Months | 0.101524E+12 | 0.389154E+10 | 0.00 | 72446242.09 | 3712479.04 | 0.142810E+09 | 0.160616E+11 | 0.00 | 11.17 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:13
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.221048E+11 | 0.434799E+11 | 0.182173E+12 | 0.00 | 0.512780E+11 |
February | 0.265315E+11 | 0.334075E+11 | 0.141360E+12 | 0.00 | 0.398095E+11 |
March | 0.427193E+11 | 0.267965E+11 | 0.116319E+12 | 35719357.02 | 0.334091E+11 |
April | 0.527426E+11 | 0.182106E+11 | 0.835166E+11 | 0.591936E+09 | 0.336753E+11 |
May | 0.622589E+11 | 0.109335E+11 | 0.628065E+11 | 0.201064E+10 | 0.346240E+11 |
June | 0.656370E+11 | 0.364024E+10 | 0.353588E+11 | 0.289677E+10 | 0.721329E+11 |
July | 0.661927E+11 | 0.982516E+09 | 0.271165E+11 | 0.350278E+10 | 0.887525E+11 |
August | 0.574160E+11 | 0.220541E+10 | 0.327783E+11 | 0.348435E+10 | 0.805292E+11 |
September | 0.391603E+11 | 0.840615E+10 | 0.568350E+11 | 0.278253E+10 | 0.479114E+11 |
October | 0.282727E+11 | 0.175996E+11 | 0.842838E+11 | 0.416153E+09 | 0.237093E+11 |
November | 0.158280E+11 | 0.259660E+11 | 0.115173E+12 | 8366815.34 | 0.305513E+11 |
December | 0.109437E+11 | 0.363437E+11 | 0.155568E+12 | 0.00 | 0.414237E+11 |
Annual Sum or Average | 0.489808E+12 | 0.227971E+12 | 0.109329E+13 | 0.157293E+11 | 0.577806E+12 |
Minimum of Months | 0.109437E+11 | 0.982516E+09 | 0.271165E+11 | 0.00 | 0.237093E+11 |
Maximum of Months | 0.661927E+11 | 0.434799E+11 | 0.182173E+12 | 0.350278E+10 | 0.887525E+11 |