Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:29:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2275.09 | 9791.95 | 9791.95 |
Net Site Energy | 2275.09 | 9791.95 | 9791.95 |
Total Source Energy | 3376.45 | 14532.19 | 14532.19 |
Net Source Energy | 3376.45 | 14532.19 | 14532.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1100.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 260.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 49.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 436.99 | 1838.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1100.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 260.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1100.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 260.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 49.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 278.95 | 5857.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1357.41 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1880.80 | 7911.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 244.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 278.95 | 5857.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1357.41 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1880.80 | 7911.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 436.992 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 436.992 | 100.00 |
Total On-Site and Utility Electric Sources | 436.992 | 100.00 |
Total Electricity End Uses | 436.992 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 35.33 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4854.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 6.7540 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 10.4679 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.7540 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.4679 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6110 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:20 | 12-JAN-11:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 162506.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5087.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1207.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14087.95 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1731.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24341.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 4327.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26441.87 | 213508.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 162506.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 5087.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1207.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13060.45 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 1731.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 24341.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3284.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1043.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1192.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 94.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 842.91 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 179.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 282.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 155.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1383.95 | 1992.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 404.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 773.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1216.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 671.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5956.51 | 8575.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 5132.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 404.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 369.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 773.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1216.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 671.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5956.51 | 8575.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.62 |
KITCHEN DIRECT AIR | 1.20 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.62 | 1.00 | 1.00 | 1.62 |
PSZ-AC_2:2 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.62 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.20 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.62 | 1737.11 |
PSZ-AC_2:2_ADDAQ FAN | 1.20 | 1332.60 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.62 | 1.62 | 1.62 | 1.07 | 29288.69 | 67916.31 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 0.794388 | 23200.71 | 112936.57 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.62 | 0.811699 | 1.08 | 29288.69 | 14644.34 | 0.800330 | 0.800330 |
PSZ-AC_2:2 COOLING COIL | 1.20 | 0.601809 | 0.802413 | 23200.71 | 11600.35 | 0.790730 | 0.790730 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 67916.31 |
PSZ-AC_2:2 HEATING COIL | 112936.57 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 6.754 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.541 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 10.468 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.547 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 784.620 | 6.754 | 8.963 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 784.620 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1216.076 | 10.468 | 193.849 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1216.076 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7461 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1870 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1870 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.272 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.272 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.30622557E-12 | 0.12606888E-14 | -0.97473019E-13 | 0.16287023E-15 |
34 | 6 | 0.29032672E-07 | 0.21068370E-09 | 0.66477549E-08 | -0.13713916E-12 |
35 | 5 | -0.19194025E-03 | 0.17986226E-05 | -0.98701398E-04 | 0.65705654E-08 |
36 | 4 | 0.29428936 | 0.87342649E-03 | 0.10045407 | -0.33873504E-04 |
37 | 3 | -7.3087568 | 0.27004109E-01 | -2.3515030 | 0.29216952E-01 |
38 | 2 | 41.011072 | 0.95822947E-01 | 15.316732 | -0.33489883 |
39 | 1 | -80.653014 | 0.43166794E-01 | -29.187976 | 1.0809043 |
40 | 0 | 46.824338 | 0.86691132E-03 | 16.290128 | |
41 | 7 | -0.22605942E-08 | -0.83801070E-15 | 0.53658694E-14 | -0.78225131E-16 |
42 | 6 | 0.52747590E-05 | 0.35786616E-08 | 0.31908477E-02 | -0.26767504E-04 |
43 | 5 | -0.37662132E-03 | 0.21179957E-05 | -0.22378015 | 0.19566408E-02 |
44 | 4 | 0.86460756E-02 | 0.96389694E-04 | 4.8304715 | -0.45273880E-01 |
45 | 3 | -0.75873005E-01 | 0.76630192E-03 | -38.026647 | 0.39871156 |
46 | 2 | 0.26933907 | 0.12746133E-02 | 116.49413 | -1.4180755 |
47 | 1 | -0.38870643 | 0.38815562E-03 | -143.91330 | 2.0491384 |
48 | 0 | 0.18950265 | 0.94317521E-05 | 60.838472 | |
49 | 7 | -0.22605942E-08 | -0.83801070E-15 | 0.53658694E-14 | -0.78225131E-16 |
50 | 6 | 0.52747590E-05 | 0.35786616E-08 | 0.31908477E-02 | -0.26767504E-04 |
51 | 5 | -0.37662132E-03 | 0.21179957E-05 | -0.22378015 | 0.19566408E-02 |
52 | 4 | 0.86460756E-02 | 0.96389694E-04 | 4.8304715 | -0.45273880E-01 |
53 | 3 | -0.75873005E-01 | 0.76630192E-03 | -38.026647 | 0.39871156 |
54 | 2 | 0.26933907 | 0.12746133E-02 | 116.49413 | -1.4180755 |
55 | 1 | -0.38870643 | 0.38815562E-03 | -143.91330 | 2.0491384 |
56 | 0 | 0.18950265 | 0.94317521E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.2917_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 3.7095E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.7088E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 3.7445E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.6216E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.5435E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.5126E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7806E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7796E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.4194E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.0066E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.8061E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.2716E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 3.9973E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 3.8954E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.9263E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.9263E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.2259E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.9049E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9167E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.5881E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9966E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0914E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7799E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7806E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18090.87316 | 21709.04779 | 1.35283 | 1.62340 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 9158.05913 | 10989.67095 | 0.39670 | 0.47604 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16092.72601 | 19311.27121 | 1.00302 | 1.20362 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 3263.10747 | 3915.72896 | 0.12665 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 23161.17 | 1.62340 | 1.62340 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 41947.79 | 0.47604 | 0.47604 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 19849.51 | 1.20362 | 1.20362 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 111347.57 | 1.14133 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62340 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.20362 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62340 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62340 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62340 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62340 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.62340 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.62340 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.20362 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.20362 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.20362 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20362 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20362 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20362 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.62340 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.20362 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.62340 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.62340 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1737.11288 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.62340 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.62340 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.62340 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07144 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.62340 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.81170 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08227 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29288.69000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14644.34500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80033 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80033 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29288.69000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67916.31382 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 67916.31382 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20362 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20362 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1332.59627 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20362 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20362 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20362 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79439 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20362 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60181 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80241 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23200.71000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11600.35500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79073 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79073 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23200.71000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112936.57251 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 112936.57251 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 28107.1 | 11.21 | 11.15 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22328.4 | 11.35 | 11.30 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | N/A | 1.657 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | N/A | 1.657 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | N/A | 1.657 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.187 | 0.179 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.746 | 0.671 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.187 | 0.179 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1251838059 | 0.5291921267 | Pass | Pass | 0.1282313044 | 0.3512085524 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1068307076 | 0.4972142970 | Pass | Pass | 6.5096283577E-002 | 0.2828034009 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 5.8656553806E-002 | 4.8772861033E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 306.66 | 343.32 | 1662.56 | 3.99 | 455.51 | 2772.04 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.181 | 0.187 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.671 | 0.746 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.181 | 0.187 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_EAST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2917_SHGC_SOUTH_0.45 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.2917_SHGC_WEST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.657 | 0.451 | 0.452 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 1.657 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 1.657 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.7540 | 116.17 | 784.62 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 71.43 | 0.0000 | Y | 10.52 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.4679 | 116.17 | 1216.08 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 19.16 |
Interior Lighting Total | 8.6110 | 232.34 | 2000.70 | 29.68 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 784.62 | 298.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 784.62 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 164.64 | AstronomicalClock | - | 51.74 | 51.74 | 1.60 | |
EXTERIOR_LIGHTS_B | 1845.07 | AstronomicalClock | - | 83.06 | 73.66 | 25.51 | |
Exterior Lighting Total | 2009.71 | 27.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29288.69 | 23440.62 | 5848.07 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23200.71 | 18345.50 | 4855.21 | 0.79 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 28107.1 | 11.21 | 11.15 | ||||
PSZ-AC_2:2 COOLING COIL | 22328.4 | 11.35 | 11.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 67916.31 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 112936.57 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.62 | 1737.11 | 1070.05 | 1.00 | 1.35 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.20 | 1332.60 | 1107.16 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18090.87 | 21709.05 | 186.87 | 1.353 | 1.623 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.88 | 0.00780 | 27.30 | 0.00701 | 0.416 | 0.00 |
KITCHEN | 16092.73 | 19311.27 | 166.23 | 1.003 | 1.204 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00871 | 26.48 | 0.00701 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 9158.06 | 10989.67 | 94.60 | 0.397 | 0.476 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00798 | -41.90 | 0.00006 | 0.416 | 0.00 |
KITCHEN | 3263.11 | 3915.73 | 33.71 | 0.127 | 1.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00709 | -41.90 | 0.00006 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.62 | 1.62 | 0.48 | 0.48 | 1.6234 | 1.6234 | 1.6234 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.20 | 1.20 | 1.14 | 1.14 | 1.2036 | 1.2036 | 1.2036 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 29288.690 | 23440.617 | 1.623400 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 14644.34 | 13418.80 | 1.082267 | 24.78 | 15.72 | 0.00759432 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 38.4430 | 23.88 | 0.00779684 | 41.6567 | 18079.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 67916.314 | 67916.314 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 67916.31 | 67916.31 | 1.623398 | 4.88 | 4.88 | 0.00594972 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 25.6287 | 21.11 | 0.00797780 | 50.4320 | 9158.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23200.710 | 18345.497 | 1.203620 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 11600.35 | 11589.37 | 0.802413 | 27.40 | 16.15 | 0.00700714 | 11.88 | 10.02 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 142.2376 | 26.09 | 0.00893206 | 41.7590 | 16092.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 112936.573 | 112936.573 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 112936.57 | 112936.57 | 1.203618 | -38.77 | -38.77 | 0.00044075 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 94.8252 | 18.05 | 0.00733526 | 56.1320 | 912.73 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29288.690 | 23440.617 | 1.623400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9575 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.623398 | 1.92444009 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 14644.34 | 13418.80 | 1.0000 | 1.28296143 | 1.082267 | 24.78 | 15.72 | 0.00759432 | 44247.6 | 11.91 | 10.04 | 0.00700000 | 29633.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14644.34 | 27.40 | 0.00700714 | 16.15 | 0.41605618 | 38.4430 | 23.88 | 0.00779684 | 23.88 | 0.00779684 | 41.6567 | 18079.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67916.314 | 67916.314 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.623398 | 1.92444009 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 67916.31 | 67916.31 | 1.0000 | 1.92444009 | 1.623398 | 4.88 | 4.88 | 0.00594972 | 19836.7 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67916.31 | -41.90 | 0.00006450 | -41.90 | 0.41605618 | 25.6287 | 21.00 | 0.00797780 | 21.11 | 0.00797780 | 50.4320 | 9158.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23200.710 | 18345.497 | 1.203620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8659 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.203618 | 1.42681617 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 11600.35 | 11589.37 | 1.0000 | 0.95121230 | 0.802413 | 27.40 | 16.15 | 0.00700714 | 45414.0 | 11.88 | 10.02 | 0.00700000 | 29601.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11600.35 | 27.40 | 0.00700714 | 16.15 | 1.14133354 | 142.2376 | 26.04 | 0.00893206 | 26.09 | 0.00893206 | 41.7590 | 16092.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112936.573 | 112936.573 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.203618 | 1.42681617 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 112936.57 | 112936.57 | 1.0000 | 1.42681617 | 1.203618 | -38.77 | -38.77 | 0.00044075 | -37887.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112936.57 | -41.90 | 0.00006450 | -41.90 | 1.14133354 | 94.8252 | 18.58 | 0.00733526 | 18.05 | 0.00733526 | 56.1320 | 912.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.62 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.20 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 4159.00 | 6127.00 | 3359.33 |
KITCHEN | 5656.67 | 6148.67 | 4821.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5689.83 | 7116.00 | 4854.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 151.50 | 0.17 | 35.33 | 0.00 |
KITCHEN | 0.00 | 63.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 151.50 | 63.83 | 35.33 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.549 | 4.530 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.707 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.093 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.837 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11669904.10 | 0.00 | 11669904.10 | 11393557.54 | 23063461.64 | 13120747.55 | 1441.70 | 6676.75 | 641.55 | 286.00 |
KITCHEN | 22330912.00 | 0.00 | 22330912.00 | 85214.71 | 22416126.71 | 35993094.65 | 8759.26 | 0.39 | 0.35 | 314.98 |
Total Facility | 34000816.10 | 0.00 | 34000816.10 | 11478772.25 | 45479588.34 | 49113842.20 | 8759.55 | 6676.90 | 641.82 | 486.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4409 | 0.0000 | 0.4409 | 0.4390 | 0.8798 | 0.4161 | 0.00 | 6545.90 | 641.10 |
KITCHEN | 0.8453 | 0.0000 | 0.8453 | 0.0019 | 0.8472 | 1.1413 | 7186.68 | 0.25 | 0.07 |
Total Facility | 1.2862 | 0.0000 | 1.2862 | 0.4408 | 1.7270 | 1.5574 | 7186.68 | 6545.98 | 641.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16400051.66 | 0.00 | 16400051.66 | 13120747.55 | 1436.06 | 0.63 | 7323.31 | 286.00 |
PSZ-AC_2:2 | 31380878.90 | 0.00 | 31380878.90 | 35993094.65 | 4609.66 | 371.37 | 3778.97 | 314.98 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6196 | 0.0000 | 0.6196 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1879 | 0.0000 | 1.1879 | 1.1413 | 3112.33 | 364.15 | 3710.52 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 598.02 | 200.73 | 6674.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 50.00 | 881.97 | 6570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0560 | 0.8001 | 0.5848 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.1918 | 1.1876 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
Electricity:Building | 303.78 | 2304.83 | 03-JUN-03:00 | 18991.61 | 02-JAN-11:10 |
Electricity:Zone:DINING | 80.94 | 353.69 | 03-JUN-03:00 | 4596.19 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 295.84 | 2168.55 | 03-JUN-03:00 | 15697.56 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.68 | 226.37 | 06-MAY-04:50 | 1609.61 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 10.52 | 68.37 | 06-MAY-04:50 | 661.67 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.68 | 226.37 | 06-MAY-04:50 | 1609.61 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 29.68 | 226.37 | 06-MAY-04:50 | 1609.61 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.52 | 68.37 | 06-MAY-04:50 | 661.67 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.68 | 226.37 | 06-MAY-04:50 | 1609.61 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 222.84 | 1951.15 | 01-JAN-01:10 | 14395.42 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.74 | 1656.87 | 01-JAN-01:10 | 10153.43 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 49.23 | 849.95 | 06-FEB-23:30 | 4342.94 | 30-JUN-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 41.29 | 764.17 | 16-NOV-23:10 | 2593.37 | 14-JUL-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 13.67 | 0.00 | 01-JAN-11:10 | 1517.14 | 14-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 27.62 | 683.18 | 17-JAN-01:10 | 1076.23 | 02-JUN-03:50 |
ElectricityPurchased:Facility | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
ElectricityPurchased:Plant | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
Cogeneration:ElectricityPurchased | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
ElectricityNet:Plant | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
Cogeneration:ElectricityNet | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
General:Cogeneration:ElectricityNet | 436.99 | 3674.30 | 30-MAY-03:00 | 26441.87 | 22-JUL-10:20 |
Electricity:HVAC | 64.81 | 0.00 | 01-JAN-01:10 | 10591.43 | 29-JUL-17:10 |
Fans:Electricity | 56.75 | 0.00 | 01-JAN-01:10 | 3234.18 | 12-JAN-07:10 |
General:Fans:Electricity | 56.75 | 0.00 | 01-JAN-01:10 | 3234.18 | 12-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.07 | 0.00 | 01-JAN-00:10 | 8278.14 | 29-JUL-17:10 |
General:Cooling:Electricity | 8.07 | 0.00 | 01-JAN-00:10 | 8278.14 | 29-JUL-17:10 |
ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-11:20 | 2009.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 27.11 | 0.00 | 01-JAN-11:20 | 2009.71 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 15-DEC-12:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 15-DEC-12:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1838.10 | 2560.65 | 01-JAN-01:10 | 213508.87 | 12-JAN-11:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 1100.11 | 0.00 | 01-JAN-01:10 | 166719.51 | 12-JAN-07:10 |
Heating:NaturalGas | 1100.11 | 0.00 | 01-JAN-01:10 | 166719.51 | 12-JAN-07:10 |
General:Heating:NaturalGas | 1100.11 | 0.00 | 01-JAN-01:10 | 166719.51 | 12-JAN-07:10 |
NaturalGas:Plant | 260.83 | 722.00 | 01-JAN-01:10 | 33365.70 | 03-JAN-13:20 |
WaterSystems:NaturalGas | 260.83 | 722.00 | 01-JAN-01:10 | 33365.70 | 03-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 260.83 | 722.00 | 01-JAN-01:10 | 33365.70 | 03-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1734.55 | 2414.97 | 01-MAR-01:10 | 203513.13 | 12-JAN-13:10 |
EnergyTransfer:Building | 576.23 | 1207.48 | 01-MAR-01:10 | 61143.04 | 28-DEC-12:10 |
EnergyTransfer:Zone:KITCHEN | 298.19 | 1207.41 | 12-JAN-01:10 | 22789.50 | 29-AUG-04:10 |
Refrigeration:EnergyTransfer | 128.96 | 2414.80 | 12-JAN-01:00 | 7834.84 | 02-JUN-03:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.48 | 1207.40 | 12-JAN-01:00 | 3917.42 | 02-JUN-03:50 |
General:Refrigeration:EnergyTransfer | 64.48 | 1207.40 | 12-JAN-01:00 | 3917.42 | 02-JUN-03:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.48 | 1207.40 | 12-JAN-01:00 | 3917.42 | 02-JUN-03:50 |
EnergyTransfer:Plant | 247.66 | 1207.40 | 12-JAN-01:00 | 25694.31 | 08-MAY-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.83 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 51.65 | 1059.55 | 17-JAN-01:10 | 2238.70 | 02-JUN-03:50 |
EnergyTransfer:Zone:DINING | 278.03 | 0.00 | 01-JAN-01:10 | 47587.90 | 25-NOV-19:50 |
Heating:EnergyTransfer | 243.81 | 0.00 | 01-JAN-00:30 | 47587.90 | 25-NOV-19:50 |
Heating:EnergyTransfer:Zone:DINING | 243.74 | 0.00 | 01-JAN-00:30 | 47587.90 | 25-NOV-19:50 |
General:Heating:EnergyTransfer | 243.81 | 0.00 | 01-JAN-00:30 | 47587.90 | 25-NOV-19:50 |
General:Heating:EnergyTransfer:Zone:DINING | 243.74 | 0.00 | 01-JAN-00:30 | 47587.90 | 25-NOV-19:50 |
Cooling:EnergyTransfer | 267.94 | 0.00 | 01-JAN-01:10 | 24561.22 | 29-JUL-17:10 |
Cooling:EnergyTransfer:Zone:DINING | 34.30 | 0.00 | 01-JAN-01:10 | 16386.94 | 27-FEB-04:40 |
General:Cooling:EnergyTransfer | 267.94 | 0.00 | 01-JAN-01:10 | 24561.22 | 29-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 34.30 | 0.00 | 01-JAN-01:10 | 16386.94 | 27-FEB-04:40 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.07 | 0.00 | 01-JAN-00:10 | 1882.17 | 28-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.07 | 0.00 | 01-JAN-00:10 | 1882.17 | 28-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 233.64 | 0.00 | 01-JAN-01:10 | 18872.08 | 29-AUG-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 233.64 | 0.00 | 01-JAN-01:10 | 18872.08 | 29-AUG-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
PlantLoopHeatingDemand:Plant | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
EnergyTransfer:HVAC | 910.66 | 0.00 | 01-JAN-01:10 | 133375.61 | 12-JAN-07:10 |
HeatingCoils:EnergyTransfer | 880.09 | 0.00 | 01-JAN-01:10 | 133375.61 | 12-JAN-07:10 |
CoolingCoils:EnergyTransfer | 30.57 | 0.00 | 01-JAN-00:10 | 34658.80 | 29-JUL-17:10 |
WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23245.94 | 06-MAR-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 243.736 | -34.298 | 0.000 | 0.000 | 74.299 | 10.521 | 52.814 | 24.955 | 0.000 | 0.350 | 0.001 | 0.000 | -19.285 | 0.000 | -309.467 | -43.625 |
KITCHEN | 0.000 | 0.000 | 0.071 | -233.630 | 0.000 | 0.000 | 5.411 | 19.164 | 201.334 | 0.000 | 0.000 | 0.000 | 9.834 | 0.000 | 0.000 | 0.000 | -2.184 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.929 | 4.408 | 0.000 | 0.000 | 0.000 | -9.337 | -0.000 |
Total Facility | 0.000 | 0.000 | 243.807 | -267.929 | 0.000 | 0.000 | 79.711 | 29.684 | 254.148 | 24.955 | 0.000 | 5.280 | 14.244 | 0.000 | -19.285 | 0.000 | -320.989 | -43.625 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-04:59 | 0.00 | 0.00 | 0.00 | -36388.67 | 0.00 | 0.00 | 0.00 | 110.28 | 508.77 | 0.00 | 0.00 | 0.00 | 37742.04 | 0.00 | -1972.42 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | -50658.21 | 0.00 | 0.00 | 21.76 | 210.66 | 4933.19 | 0.00 | 0.00 | 0.00 | 45492.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-00:01 | 0.00 | 0.00 | 0.00 | -73046.45 | 0.00 | 0.00 | 388.30 | 268.27 | 2309.19 | 0.00 | 0.00 | 350.35 | 71984.62 | 0.00 | -2072.87 | 0.00 | -181.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 25-NOV-19:55 | 0.00 | 0.00 | 47592.36 | 0.00 | 0.00 | 0.00 | 6525.08 | 661.67 | 2238.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1564.18 | 0.00 | -52501.58 | -2951.95 |
KITCHEN | 14-DEC-05:02 | 0.00 | 0.00 | 16673.75 | 0.00 | 0.00 | 0.00 | 23.81 | 210.66 | 4933.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21841.41 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-NOV-19:55 | -8056.20 | 8056.20 | 47592.36 | -8056.20 | 0.00 | 0.00 | 7037.35 | 1609.61 | 10426.54 | 0.00 | 0.00 | 401.83 | 0.00 | 0.00 | -1564.18 | 0.00 | -52501.58 | -4945.73 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6234 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6234 | 0.2563 | 1.0000 | Not calculated | 0.4161 | 0.2563 | ||
PSZ-AC_2:2 | 1.2036 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2036 | 0.1257 | 1.0000 | Not calculated | 0.1513 | 0.1257 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.6234 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.6234 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2563 | ||
PSZ-AC_2:2 | 1.2036 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2036 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1257 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6234 | 1.6234 | 1.6234 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2036 | 1.2036 | 1.2036 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6234 | 1.6234 | 1.6234 | 1.6234 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2036 | 1.2036 | 1.2036 | 1.2036 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6234 | 1.6234 | 1.6234 | No | 0.4161 | 0.8740 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2036 | 1.2036 | 1.2036 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.6234 | 1.6234 | 1.6234 | 1.6234 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2036 | 1.2036 | 1.2036 | 1.2036 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 35.33 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 35.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1100.11 | 166719.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.07 | 8278.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.68 | 1609.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 27.11 | 2009.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 56.75 | 3234.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 260.83 | 33365.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.67 | 1517.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 27.62 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 315.38 | 436.99 |
Natural Gas | 477.16 | 1838.10 |
Additional | 0.00 | 0.00 |
Total | 792.54 | 2275.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 127.76 |
Space Heating | 0.00 |
Space Cooling | 34.71 |
Fans (All) | 244.24 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1145.52 |
Miscellaneous (All) | 1880.80 |
Subtotal | 1880.80 |
Natural Gas [MJ/m2] | |
Space Heating | 4734.86 |
Service Water Heating | 1122.61 |
Miscellaneous (All) | 7911.14 |
Subtotal | 7911.14 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.30 |
Space Heating | 48.35 |
Space Cooling | 0.35 |
Fans (All) | 2.49 |
Service Water Heating | 11.46 |
Receptacle Equipment | 32.67 |
Miscellaneous | 3.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8315.33 | 444.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7875.00 | 479.33 | 334.33 | 71.33 | 0.00 |
Min | 7875.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 479.33 | 334.33 | 71.33 | 0.00 |
Average | 8316.78 | 308.00 | 111.44 | 23.78 | 0.00 |
Sum | 24950.33 | 924.00 | 334.33 | 71.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7976.50 | 783.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 8007.83 | 616.17 | 110.00 | 24.33 | 1.67 |
Min | 7976.50 | 10.67 | 0.00 | 0.00 | 0.00 |
Max | 8749.33 | 783.50 | 110.00 | 24.33 | 1.67 |
Average | 8244.56 | 470.11 | 36.67 | 8.11 | 0.56 |
Sum | 24733.67 | 1410.33 | 110.00 | 24.33 | 1.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254718.67 | 6.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15039.83 | 1218.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254718.67 | 1218.17 | 0.00 | 0.00 | 0.00 |
Average | 89919.50 | 408.17 | 0.00 | 0.00 | 0.00 |
Sum | 269758.50 | 1224.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:26
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.653016E+09 | 36388.99 | 12-JAN-04:59 | -37.8 | -37.9 | 0.438756E+10 | 3724.41 | 14-JAN-19:49 | -22.1 | -22.3 |
February | 0.583032E+09 | 33330.84 | 27-FEB-04:50 | -35.8 | -35.9 | 0.402031E+10 | 3723.44 | 25-FEB-19:30 | -35.8 | -35.9 |
March | 0.626399E+09 | 21840.08 | 01-MAR-00:01 | -28.9 | -29.2 | 0.449264E+10 | 3723.57 | 18-MAR-18:40 | 2.03 | 0.19 |
April | 0.126969E+10 | 16013.70 | 02-APR-23:01 | -15.8 | -17.1 | 0.432872E+10 | 3763.27 | 21-APR-17:10 | 14.40 | 5.85 |
May | 0.394131E+10 | 8558.54 | 27-MAY-04:02 | 0.00 | -1.1 | 0.471474E+10 | 4681.62 | 13-MAY-18:00 | 0.00 | -1.1 |
June | 0.747484E+10 | 26473.04 | 22-JUN-04:01 | 13.90 | 11.43 | 0.498860E+10 | 4681.82 | 10-JUN-18:00 | 13.90 | 11.43 |
July | 0.914538E+10 | 25188.65 | 23-JUL-04:01 | 12.38 | 12.02 | 0.514911E+10 | 4682.24 | 08-JUL-18:30 | 12.38 | 12.02 |
August | 0.674280E+10 | 22038.61 | 12-AUG-04:01 | 14.90 | 10.60 | 0.501720E+10 | 4682.01 | 26-AUG-18:10 | 20.60 | 14.05 |
September | 0.191195E+10 | 9966.56 | 29-SEP-04:18 | -3.9 | -4.5 | 0.436237E+10 | 4378.93 | 02-SEP-18:10 | -3.9 | -4.5 |
October | 0.716594E+09 | 17511.63 | 22-OCT-04:02 | -18.6 | -18.8 | 0.444926E+10 | 3723.57 | 07-OCT-18:10 | -18.6 | -18.8 |
November | 0.602845E+09 | 21829.22 | 29-NOV-04:04 | -28.9 | -29.1 | 0.429100E+10 | 3723.78 | 25-NOV-19:19 | -28.9 | -29.1 |
December | 0.630978E+09 | 28567.63 | 15-DEC-04:41 | -33.1 | -33.2 | 0.443032E+10 | 3724.44 | 02-DEC-19:00 | -33.1 | -33.2 |
Annual Sum or Average | 0.342988E+11 | 0.546318E+11 | ||||||||
Minimum of Months | 0.583032E+09 | 8558.54 | -37.8 | -37.9 | 0.402031E+10 | 3723.44 | -35.8 | -35.9 | ||
Maximum of Months | 0.914538E+10 | 36388.99 | 14.90 | 12.02 | 0.514911E+10 | 4682.24 | 20.60 | 14.05 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163584E+11 | 49438.40 | 13-JAN-05:01 | -32.9 | -33.0 | 0.768473E+10 | 5039.33 | 18-JAN-11:00 | -10.6 | -10.8 |
February | 0.148892E+11 | 44094.21 | 28-FEB-05:01 | -26.1 | -26.3 | 0.694153E+10 | 5039.33 | 07-FEB-11:00 | -26.1 | -26.3 |
March | 0.178328E+11 | 43520.01 | 03-MAR-05:01 | -25.6 | -26.1 | 0.768720E+10 | 5041.00 | 20-MAR-10:00 | 5.00 | 1.39 |
April | 0.195883E+11 | 38626.65 | 03-APR-04:01 | -21.1 | -21.6 | 0.745299E+10 | 5082.85 | 20-APR-10:50 | 10.60 | 4.57 |
May | 0.212783E+11 | 42680.35 | 14-MAY-04:01 | 7.80 | 4.15 | 0.778452E+10 | 5138.40 | 31-MAY-10:50 | 18.62 | 10.48 |
June | 0.215412E+11 | 42820.95 | 16-JUN-04:01 | 8.48 | 7.31 | 0.759332E+10 | 5138.42 | 20-JUN-10:00 | 18.90 | 12.97 |
July | 0.229223E+11 | 40996.88 | 14-JUL-03:11 | 10.77 | 10.07 | 0.784495E+10 | 5138.44 | 24-JUL-10:30 | 19.45 | 15.35 |
August | 0.230568E+11 | 44212.95 | 29-AUG-03:21 | 7.20 | 6.36 | 0.783021E+10 | 5138.43 | 08-AUG-10:00 | 7.20 | 6.36 |
September | 0.219185E+11 | 29409.65 | 09-SEP-04:01 | 0.92 | 0.48 | 0.748396E+10 | 5101.17 | 19-SEP-10:00 | 11.70 | 6.96 |
October | 0.207496E+11 | 38111.39 | 31-OCT-04:01 | -17.9 | -18.4 | 0.769022E+10 | 5079.74 | 04-OCT-10:00 | -17.9 | -18.4 |
November | 0.169919E+11 | 46245.33 | 28-NOV-05:01 | -27.7 | -27.9 | 0.743670E+10 | 5039.33 | 02-NOV-10:09 | -27.7 | -27.9 |
December | 0.165106E+11 | 50685.50 | 15-DEC-05:01 | -33.2 | -33.3 | 0.768463E+10 | 5039.33 | 19-DEC-11:09 | -15.4 | -15.8 |
Annual Sum or Average | 0.233638E+12 | 0.911150E+11 | ||||||||
Minimum of Months | 0.148892E+11 | 29409.65 | -33.2 | -33.3 | 0.694153E+10 | 5039.33 | -27.7 | -27.9 | ||
Maximum of Months | 0.230568E+11 | 50685.50 | 10.77 | 10.07 | 0.784495E+10 | 5138.44 | 19.45 | 15.35 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454357E+11 | 46559.08 | 28-JAN-19:10 | -22.8 |
February | 0.368369E+11 | 47330.05 | 25-FEB-19:10 | -23.9 |
March | 0.306123E+11 | 45422.72 | 14-MAR-04:01 | -18.8 |
April | 0.118584E+11 | 44842.07 | 03-APR-04:01 | -21.1 |
May | 0.167964E+10 | 16746.87 | 27-MAY-04:01 | 0.00 |
June | 50952323.60 | 2766.22 | 02-JUN-06:03 | 7.15 |
July | 74787903.31 | 4196.99 | 27-JUL-06:55 | 10.60 |
August | 0.477174E+09 | 9346.66 | 31-AUG-06:10 | -1.5 |
September | 0.549058E+10 | 16238.46 | 28-SEP-04:01 | -1.8 |
October | 0.206099E+11 | 40657.86 | 22-OCT-04:01 | -18.6 |
November | 0.425458E+11 | 47592.18 | 25-NOV-19:55 | -23.9 |
December | 0.480635E+11 | 46775.55 | 12-DEC-21:00 | -26.1 |
Annual Sum or Average | 0.243736E+12 | |||
Minimum of Months | 50952323.60 | 2766.22 | -26.1 | |
Maximum of Months | 0.480635E+11 | 47592.18 | 10.60 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15558970.90 | 15916.60 | 12-JAN-00:02 | -36.1 |
February | 12398173.77 | 14924.35 | 18-FEB-05:02 | -23.9 |
March | 10399616.02 | 14342.30 | 15-MAR-04:02 | -22.5 |
April | 2390659.03 | 7919.89 | 05-APR-04:03 | -11.1 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 88960.45 | 1482.67 | 30-SEP-04:04 | -4.0 |
October | 4657866.77 | 10876.14 | 31-OCT-04:03 | -17.9 |
November | 11455400.75 | 14683.68 | 29-NOV-05:02 | -28.9 |
December | 13970172.37 | 16690.81 | 14-DEC-05:02 | -26.0 |
Annual Sum or Average | 70919820.06 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 15558970.90 | 16690.81 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105872E+10 | 661.67 | 02-JAN-10:09 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.874579E+09 | 661.67 | 01-FEB-15:09 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.896838E+09 | 661.67 | 01-MAR-17:19 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.774744E+09 | 661.67 | 01-APR-19:40 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.773512E+09 | 661.67 | 01-MAY-20:30 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.731216E+09 | 661.67 | 02-JUN-20:40 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.754791E+09 | 661.67 | 14-JUL-20:00 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.807417E+09 | 661.67 | 02-AUG-20:30 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.833134E+09 | 661.67 | 01-SEP-19:10 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.929342E+09 | 661.67 | 02-OCT-17:19 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.980863E+09 | 661.67 | 01-NOV-09:09 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.110566E+10 | 661.67 | 01-DEC-10:09 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.105208E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.731216E+09 | 661.67 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.110566E+10 | 661.67 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161928E+10 | 947.94 | 02-JAN-10:09 | 0.166241E+11 | 10153.43 | 01-JAN-11:09 |
February | 0.146666E+10 | 947.94 | 01-FEB-10:09 | 0.150153E+11 | 10153.43 | 01-FEB-11:09 |
March | 0.164506E+10 | 947.94 | 01-MAR-10:09 | 0.166241E+11 | 10153.43 | 01-MAR-11:09 |
April | 0.157340E+10 | 947.94 | 01-APR-16:10 | 0.160878E+11 | 10153.43 | 01-APR-10:09 |
May | 0.163217E+10 | 947.94 | 01-MAY-09:09 | 0.166241E+11 | 10153.43 | 01-MAY-10:09 |
June | 0.159008E+10 | 947.94 | 01-JUN-09:09 | 0.160878E+11 | 10153.43 | 01-JUN-10:09 |
July | 0.161568E+10 | 947.94 | 01-JUL-16:10 | 0.166241E+11 | 10153.43 | 01-JUL-10:09 |
August | 0.164506E+10 | 947.94 | 01-AUG-09:09 | 0.166241E+11 | 10153.43 | 01-AUG-10:09 |
September | 0.157378E+10 | 947.94 | 01-SEP-09:09 | 0.160878E+11 | 10153.43 | 01-SEP-10:09 |
October | 0.161909E+10 | 947.94 | 02-OCT-09:09 | 0.166241E+11 | 10153.43 | 01-OCT-10:09 |
November | 0.156752E+10 | 947.94 | 01-NOV-09:09 | 0.160878E+11 | 10153.43 | 01-NOV-10:09 |
December | 0.161587E+10 | 947.94 | 01-DEC-10:09 | 0.166241E+11 | 10153.43 | 01-DEC-11:09 |
Annual Sum or Average | 0.191636E+11 | 0.195735E+12 | ||||
Minimum of Months | 0.146666E+10 | 947.94 | 0.150153E+11 | 10153.43 | ||
Maximum of Months | 0.164506E+10 | 947.94 | 0.166241E+11 | 10153.43 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.105872E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472756E+11 |
February | 0.852256E+10 | 0.874579E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393813E+11 |
March | 0.954557E+10 | 0.896838E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362920E+11 |
April | 0.915225E+10 | 0.774744E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204891E+11 |
May | 0.947560E+10 | 0.773512E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102217E+11 |
June | 0.922788E+10 | 0.731216E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102187E+09 | 0.575703E+10 |
July | 0.939996E+10 | 0.754791E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218960E+09 | 0.495212E+10 |
August | 0.954557E+10 | 0.807417E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29201104.98 | 0.755470E+10 |
September | 0.915225E+10 | 0.833134E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145665E+11 |
October | 0.940563E+10 | 0.929342E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278207E+11 |
November | 0.909363E+10 | 0.980863E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454956E+11 |
December | 0.939996E+10 | 0.110566E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496607E+11 |
Annual Sum or Average | 0.111326E+12 | 0.105208E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350348E+09 | 0.309467E+12 |
Minimum of Months | 0.852256E+10 | 0.731216E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495212E+10 |
Maximum of Months | 0.954557E+10 | 0.110566E+10 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218960E+09 | 0.496607E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.161928E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228015E+09 |
February | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188554E+09 |
March | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295789E+09 |
April | 0.655836E+09 | 0.157340E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292201E+09 |
May | 0.679007E+09 | 0.163217E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199698E+09 |
June | 0.661256E+09 | 0.159008E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 55020.17 | 0.127215E+09 |
July | 0.673587E+09 | 0.161568E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306457.67 | 94237968.49 |
August | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121119E+09 |
September | 0.655836E+09 | 0.157378E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117638E+09 |
October | 0.673993E+09 | 0.161909E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251820E+09 |
November | 0.651635E+09 | 0.156752E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91729919.77 |
December | 0.673587E+09 | 0.161587E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176407E+09 |
Annual Sum or Average | 0.797748E+10 | 0.191636E+11 | 0.146736E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 361477.84 | 0.218442E+10 |
Minimum of Months | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91729919.77 |
Maximum of Months | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306457.67 | 0.295789E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773651E+09 | 13184177.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553829E+09 | 0.180500E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401359E+09 | 0.778367E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278375E+09 | 0.131699E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182966E+09 | 0.158736E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93789514.22 | 0.168556E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112790E+09 | 0.158903E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190744E+09 | 0.122776E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308918E+09 | 0.638145E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369527E+09 | 0.271969E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821736E+09 | 47661922.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841309E+09 | 673374.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492900E+10 | 0.933720E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93789514.22 | 673374.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841309E+09 | 0.168556E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 661.67 | 02-JAN-10:09 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 62348.01 | 12-JAN-12:01 |
February | 9454.80 | 04-FEB-19:10 | 661.67 | 01-FEB-15:09 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 55171.27 | 27-FEB-12:02 |
March | 9454.80 | 04-MAR-19:10 | 661.67 | 01-MAR-17:19 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 46055.92 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 661.67 | 01-APR-19:40 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 30397.09 | 03-APR-11:02 |
May | 9454.80 | 06-MAY-18:10 | 661.67 | 01-MAY-20:30 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 16143.26 | 26-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 661.67 | 02-JUN-20:40 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2443.07 | 20-JUN-17:55 | 9598.10 | 24-JUN-19:00 |
July | 9454.80 | 01-JUL-18:10 | 661.67 | 14-JUL-20:00 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.04 | 29-JUL-17:03 | 9740.88 | 05-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 661.67 | 02-AUG-20:30 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.71 | 11-AUG-17:05 | 13723.28 | 30-AUG-20:00 |
September | 9454.80 | 02-SEP-18:10 | 661.67 | 01-SEP-19:10 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 23241.94 | 30-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 661.67 | 02-OCT-17:19 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 39874.18 | 30-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 661.67 | 01-NOV-09:09 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 52501.58 | 25-NOV-19:55 |
December | 9454.80 | 02-DEC-19:10 | 661.67 | 01-DEC-10:09 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 58455.78 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9598.10 | |||||
Maximum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 4373.04 | 62348.01 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 947.94 | 02-JAN-10:09 | 7415.65 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1481.79 | 29-JAN-01:10 |
February | 677.52 | 04-FEB-19:10 | 947.94 | 01-FEB-10:09 | 7415.65 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 997.78 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 947.94 | 01-MAR-10:09 | 7415.65 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 765.75 | 25-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 947.94 | 01-APR-16:10 | 7415.65 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 852.93 | 07-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 947.94 | 01-MAY-09:09 | 7415.65 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 594.90 | 26-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 947.94 | 01-JUN-09:09 | 7415.65 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 11.20 | 30-JUN-15:00 | 630.51 | 25-JUN-01:20 |
July | 677.52 | 01-JUL-18:10 | 947.94 | 01-JUL-16:10 | 7415.65 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.20 | 21-JUL-16:00 | 391.65 | 30-JUL-01:00 |
August | 677.52 | 05-AUG-18:10 | 947.94 | 01-AUG-09:09 | 7415.65 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 452.40 | 30-AUG-01:00 |
September | 677.52 | 02-SEP-18:10 | 947.94 | 01-SEP-09:09 | 7415.65 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 308.69 | 30-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 947.94 | 02-OCT-09:09 | 7415.65 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 751.52 | 21-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 947.94 | 01-NOV-09:09 | 7415.65 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 606.88 | 10-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 947.94 | 01-DEC-10:09 | 7415.65 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 608.36 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 308.69 | ||||||
Maximum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 33.20 | 1481.79 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.80 | 13-JAN-01:00 | 370.26 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.78 | 17-FEB-04:53 | 950.95 | 27-FEB-13:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.20 | 27-MAR-07:32 | 1831.06 | 26-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.68 | 01-APR-00:45 | 1856.76 | 27-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.46 | 22-MAY-03:30 | 1994.14 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.56 | 07-JUN-01:00 | 2037.72 | 08-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.41 | 11-JUL-24:00 | 2108.22 | 23-JUL-12:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.79 | 22-AUG-05:10 | 1904.34 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.23 | 19-SEP-01:55 | 1301.10 | 07-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.73 | 31-OCT-08:00 | 798.76 | 22-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.55 | 22-NOV-03:00 | 510.09 | 06-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795.29 | 28-DEC-10:00 | 123.07 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.41 | 123.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.20 | 2108.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36388.99 | 12-JAN-04:59 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33330.84 | 27-FEB-04:50 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21840.08 | 01-MAR-00:01 | 5252.67 | 1102.78 | 4070.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 |
April | 16013.70 | 02-APR-23:01 | 5252.67 | 1102.78 | 4070.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 |
May | 8558.54 | 27-MAY-04:02 | 0.00 | 963.10 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.28 |
June | 26473.04 | 22-JUN-04:01 | 5252.67 | 911.63 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 |
July | 25188.65 | 23-JUL-04:01 | 0.00 | 823.41 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22038.61 | 12-AUG-04:01 | 0.00 | 882.23 | 13024.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
September | 9966.56 | 29-SEP-04:18 | 2626.33 | 735.19 | 8140.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 |
October | 17511.63 | 22-OCT-04:02 | 0.00 | 1102.78 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.50 |
November | 21829.22 | 29-NOV-04:04 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28567.63 | 15-DEC-04:41 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8558.54 | 0.00 | 735.19 | 4070.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36388.99 | 5252.67 | 1102.78 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49438.40 | 13-JAN-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44094.21 | 28-FEB-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43520.01 | 03-MAR-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 93.85 |
April | 38626.65 | 03-APR-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 105.35 |
May | 42680.35 | 14-MAY-04:01 | 0.00 | 1579.93 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
June | 42820.95 | 16-JUN-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 |
July | 40996.88 | 14-JUL-03:11 | 0.00 | 1579.93 | 21289.05 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44212.95 | 29-AUG-03:21 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 |
September | 29409.65 | 09-SEP-04:01 | 0.00 | 1579.93 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 48.67 |
October | 38111.39 | 31-OCT-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 |
November | 46245.33 | 28-NOV-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50685.50 | 15-DEC-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29409.65 | 0.00 | 1263.94 | 17031.24 | 11031.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50685.50 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.34 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.28 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.87 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.54 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.96 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.46 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.01 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.50 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.54 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.38 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.17 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.389212E+11 | 24706.54 | 03-JAN-11:09 | 0.264527E+12 | 213508.87 | 12-JAN-11:09 |
February | 0.342367E+11 | 22647.25 | 27-FEB-11:09 | 0.221141E+12 | 195742.17 | 27-FEB-13:09 |
March | 0.367246E+11 | 22154.95 | 01-MAR-11:09 | 0.203315E+12 | 158383.72 | 01-MAR-20:40 |
April | 0.340444E+11 | 21987.22 | 03-APR-10:09 | 0.120344E+12 | 128278.59 | 03-APR-07:10 |
May | 0.346333E+11 | 21900.94 | 31-MAY-10:20 | 0.743489E+11 | 78677.65 | 27-MAY-10:09 |
June | 0.353834E+11 | 25992.18 | 30-JUN-10:00 | 0.620206E+11 | 56992.94 | 25-JUN-12:30 |
July | 0.381894E+11 | 26441.87 | 22-JUL-10:20 | 0.630911E+11 | 58732.98 | 05-JUL-10:20 |
August | 0.369653E+11 | 23408.89 | 05-AUG-10:20 | 0.658910E+11 | 61871.75 | 30-AUG-10:09 |
September | 0.344559E+11 | 21732.12 | 29-SEP-10:09 | 0.863452E+11 | 89755.37 | 29-SEP-10:09 |
October | 0.367650E+11 | 22125.79 | 31-OCT-10:09 | 0.152091E+12 | 136471.28 | 27-OCT-10:09 |
November | 0.373084E+11 | 22683.32 | 28-NOV-11:09 | 0.250658E+12 | 180383.79 | 28-NOV-13:09 |
December | 0.393640E+11 | 24941.19 | 15-DEC-11:09 | 0.274326E+12 | 200675.51 | 15-DEC-13:30 |
Annual Sum or Average | 0.436992E+12 | 0.183810E+13 | ||||
Minimum of Months | 0.340444E+11 | 21732.12 | 0.620206E+11 | 56992.94 | ||
Maximum of Months | 0.393640E+11 | 26441.87 | 0.274326E+12 | 213508.87 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.267800E+10 | 0.392336E+10 | 0.226048E+11 | 0.00 | 0.580494E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234124E+10 | 0.287328E+10 | 0.204173E+11 | 0.00 | 0.506736E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254190E+10 | 0.242210E+10 | 0.226048E+11 | 0.00 | 0.522404E+10 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.234814E+10 | 0.160586E+10 | 0.218757E+11 | 0.00 | 0.432611E+10 | 0.77 | 0.00 | 123007.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240568E+10 | 0.100868E+10 | 0.226048E+11 | 0.00 | 0.402600E+10 | 0.80 | 0.00 | 0.228719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.232130E+10 | 0.533470E+09 | 0.218757E+11 | 0.00 | 0.389850E+10 | 0.77 | 0.00 | 0.224169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237047E+10 | 0.756170E+09 | 0.226048E+11 | 0.00 | 0.405472E+10 | 0.79 | 0.00 | 0.370927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245248E+10 | 0.136418E+10 | 0.226048E+11 | 0.00 | 0.405113E+10 | 0.80 | 0.00 | 0.188033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240691E+10 | 0.202505E+10 | 0.218757E+11 | 0.00 | 0.405719E+10 | 0.77 | 0.00 | 4562563.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254843E+10 | 0.285379E+10 | 0.226048E+11 | 0.00 | 0.475726E+10 | 0.79 | 0.00 | 317250.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254838E+10 | 0.351545E+10 | 0.218757E+11 | 0.00 | 0.558064E+10 | 0.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272152E+10 | 0.422964E+10 | 0.226048E+11 | 0.00 | 0.589862E+10 | 0.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296845E+11 | 0.271110E+11 | 0.266154E+12 | 0.00 | 0.567465E+11 | 9.37 | 0.00 | 0.806501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.232130E+10 | 0.533470E+09 | 0.204173E+11 | 0.00 | 0.389850E+10 | 0.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.272152E+10 | 0.422964E+10 | 0.226048E+11 | 0.00 | 0.589862E+10 | 0.80 | 0.00 | 0.370927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.200959E+12 | 0.00 | 0.230428E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.163723E+12 | 0.00 | 0.208136E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.139705E+12 | 0.00 | 0.230841E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.588505E+11 | 0.00 | 0.222746E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.110021E+11 | 0.00 | 0.228211E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.148909E+10 | 0.00 | 0.213131E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.131780E+10 | 0.00 | 0.212476E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.449942E+10 | 0.00 | 0.208659E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.269497E+11 | 0.00 | 0.201770E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.903119E+11 | 0.00 | 0.212531E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.190206E+12 | 0.00 | 0.212328E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.211096E+12 | 0.00 | 0.227041E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.110011E+13 | 0.00 | 0.260830E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.131780E+10 | 0.00 | 0.201770E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.211096E+12 | 0.00 | 0.230841E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1609.61 | 02-JAN-10:09 | 2009.71 | 01-JAN-00:10 | 14087.95 | 01-JAN-11:09 | 0.00 | 3234.18 | 12-JAN-07:10 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1609.61 | 01-FEB-15:09 | 2009.71 | 01-FEB-00:10 | 14087.95 | 01-FEB-11:09 | 0.00 | 3124.52 | 27-FEB-12:30 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1609.61 | 01-MAR-17:19 | 2009.71 | 01-MAR-00:10 | 14087.95 | 01-MAR-11:09 | 0.00 | 2955.57 | 04-MAR-07:10 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1609.61 | 01-APR-19:40 | 2009.71 | 01-APR-05:10 | 14087.95 | 01-APR-10:09 | 0.00 | 2693.06 | 03-APR-06:10 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1609.61 | 01-MAY-20:30 | 2009.71 | 01-MAY-21:10 | 14087.95 | 01-MAY-10:09 | 0.00 | 2115.24 | 27-MAY-06:00 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1609.61 | 02-JUN-20:40 | 2009.71 | 01-JUN-22:49 | 14087.95 | 01-JUN-10:09 | 0.00 | 2075.29 | 30-JUN-12:20 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 1609.61 | 14-JUL-20:00 | 2009.71 | 01-JUL-23:19 | 14087.95 | 01-JUL-10:09 | 0.00 | 2313.29 | 29-JUL-17:10 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1609.61 | 02-AUG-20:30 | 2009.71 | 01-AUG-21:00 | 14087.95 | 01-AUG-10:09 | 0.00 | 2113.19 | 31-AUG-06:10 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1609.61 | 01-SEP-19:10 | 2009.71 | 01-SEP-05:10 | 14087.95 | 01-SEP-10:09 | 0.00 | 2264.18 | 30-SEP-06:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1609.61 | 02-OCT-17:19 | 2009.71 | 01-OCT-05:10 | 14087.95 | 01-OCT-10:09 | 0.00 | 2743.92 | 30-OCT-19:00 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1609.61 | 01-NOV-09:09 | 2009.71 | 01-NOV-05:10 | 14087.95 | 01-NOV-10:09 | 0.00 | 3100.22 | 30-NOV-20:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1609.61 | 01-DEC-10:09 | 2009.71 | 01-DEC-00:10 | 14087.95 | 01-DEC-11:09 | 0.00 | 3146.86 | 15-DEC-12:30 | 0.00 | 15-DEC-12:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 2075.29 | 0.00 | 0.00 | ||||||
Maximum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 3234.18 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 138.51 | 28-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3287.25 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7419.58 | 30-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8278.14 | 29-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5830.93 | 11-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 397.89 | 19-SEP-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 191.98 | 06-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8278.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 24706.54 | 03-JAN-11:09 | 1609.61 | 14087.95 | 2009.71 | 0.00 | 2879.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22647.25 | 27-FEB-11:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3081.59 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22154.95 | 01-MAR-11:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2589.29 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21987.22 | 03-APR-10:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2421.56 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21900.94 | 31-MAY-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 1731.52 | 0.00 | 0.00 | 415.24 | 0.00 |
June | 25992.18 | 30-JUN-10:00 | 1358.18 | 14087.95 | 0.00 | 0.00 | 1985.93 | 0.00 | 0.00 | 6003.16 | 0.00 |
July | 26441.87 | 22-JUL-10:20 | 1207.27 | 14087.95 | 0.00 | 0.00 | 1731.52 | 0.00 | 0.00 | 5087.32 | 0.00 |
August | 23408.89 | 05-AUG-10:20 | 1207.27 | 14087.95 | 0.00 | 0.00 | 1731.52 | 0.00 | 0.00 | 2059.89 | 0.00 |
September | 21732.12 | 29-SEP-10:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2145.80 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22125.79 | 31-OCT-10:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2560.14 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22683.32 | 28-NOV-11:09 | 1525.80 | 14087.95 | 0.00 | 0.00 | 2950.04 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24941.19 | 15-DEC-11:09 | 1609.61 | 14087.95 | 2009.71 | 0.00 | 3114.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21732.12 | 1207.27 | 14087.95 | 0.00 | 0.00 | 1731.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26441.87 | 1609.61 | 14087.95 | 2009.71 | 0.00 | 3114.39 | 0.00 | 0.00 | 6003.16 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 166719.51 | 12-JAN-07:10 | 0.00 | 33365.70 | 03-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 153267.03 | 27-FEB-07:10 | 0.00 | 33363.44 | 16-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 132376.85 | 04-MAR-07:10 | 0.00 | 33363.48 | 31-MAR-12:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 104996.40 | 03-APR-06:10 | 0.00 | 33362.49 | 05-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 38603.19 | 27-MAY-06:00 | 0.00 | 33243.90 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 11135.51 | 02-JUN-06:10 | 0.00 | 30097.55 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 10550.11 | 05-JUL-06:10 | 0.00 | 28424.21 | 01-JUL-12:20 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 38755.33 | 31-AUG-06:10 | 0.00 | 28132.05 | 01-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 55091.56 | 30-SEP-06:10 | 0.00 | 28102.67 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 106768.79 | 22-OCT-06:10 | 0.00 | 28353.87 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 142530.05 | 30-NOV-20:10 | 0.00 | 28761.93 | 27-NOV-13:30 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 150764.70 | 15-DEC-12:30 | 0.00 | 33362.26 | 29-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 10550.11 | 0.00 | 28102.67 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 166719.51 | 0.00 | 33365.70 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 16.91 | 15.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
February | 21.67 | 17.90 | 3.67 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
March | 14.50 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
April | 2.33 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.83 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
November | 32.33 | 18.11 | 7.83 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 35.67 | 17.62 | 8.33 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
Annual Sum or Average | 151.50 | 17.59 | 35.33 | 17.69 | 0.17 | 17.70 | 0.00 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.17 | 18.41 | 15.50 | 18.45 | 0.17 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 29.22 | 0.00 | 29.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 30.26 | 0.00 | 30.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 30.44 | 0.00 | 30.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 30.33 | 0.00 | 30.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.85 | 0.00 | 28.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.67 | 30.23 | 0.00 | 30.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 30.44 | 0.00 | 30.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.71 | 610.00 | 20.71 | 610.00 | 20.71 |
February | 551.00 | 20.82 | 539.50 | 20.82 | 539.50 | 20.82 |
March | 612.00 | 20.84 | 450.67 | 20.80 | 450.67 | 20.78 |
April | 590.00 | 20.89 | 188.33 | 20.76 | 188.33 | 20.68 |
May | 529.50 | 21.23 | 42.33 | 21.17 | 30.67 | 21.07 |
June | 271.50 | 21.56 | 231.00 | 22.62 | 1.17 | 22.62 |
July | 217.33 | 21.49 | 345.50 | 22.90 | 2.00 | 22.90 |
August | 352.33 | 21.35 | 219.50 | 22.26 | 4.83 | 22.23 |
September | 583.33 | 21.04 | 48.83 | 20.90 | 48.83 | 20.78 |
October | 610.00 | 20.86 | 284.50 | 20.77 | 284.50 | 20.72 |
November | 591.00 | 20.81 | 589.83 | 20.81 | 589.83 | 20.81 |
December | 609.00 | 20.80 | 609.00 | 20.80 | 609.00 | 20.80 |
Annual Sum or Average | 6127.00 | 20.96 | 4159.00 | 21.10 | 3359.33 | 21.00 |
Minimum of Months | 217.33 | 20.71 | 42.33 | 20.71 | 1.17 | 20.68 |
Maximum of Months | 612.00 | 21.56 | 610.00 | 22.90 | 610.00 | 22.90 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 610.00 | 18.72 | 610.00 | 18.72 |
February | 551.00 | 18.72 | 544.17 | 18.72 | 544.17 | 18.72 |
March | 612.00 | 18.73 | 564.50 | 18.72 | 564.50 | 18.72 |
April | 566.67 | 19.14 | 329.67 | 18.98 | 323.50 | 18.88 |
May | 363.67 | 21.05 | 289.33 | 22.40 | 103.67 | 22.49 |
June | 385.67 | 25.52 | 522.33 | 25.44 | 344.00 | 25.61 |
July | 429.67 | 25.72 | 563.00 | 25.56 | 402.17 | 25.70 |
August | 396.00 | 24.59 | 483.83 | 24.87 | 304.50 | 25.12 |
September | 424.00 | 19.33 | 200.67 | 20.12 | 76.00 | 19.92 |
October | 610.00 | 18.95 | 353.17 | 18.83 | 353.17 | 18.78 |
November | 591.00 | 18.72 | 590.83 | 18.72 | 590.83 | 18.72 |
December | 609.00 | 18.72 | 605.17 | 18.72 | 605.17 | 18.72 |
Annual Sum or Average | 6148.67 | 20.26 | 5656.67 | 20.58 | 4821.67 | 20.52 |
Minimum of Months | 363.67 | 18.72 | 200.67 | 18.72 | 76.00 | 18.72 |
Maximum of Months | 612.00 | 25.72 | 610.00 | 25.56 | 610.00 | 25.70 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.70948 | 10.08459 | -0.8692 | 21.88986 |
February | 551.00000 | 20.82289 | 11.34326 | -0.8020 | 19.44554 |
March | 612.00000 | 20.83704 | 12.65029 | -0.6809 | 15.87781 |
April | 590.00000 | 20.89256 | 17.95249 | -0.4844 | 11.33651 |
May | 611.00000 | 21.57506 | 26.96427 | -1.2483 | 39.68483 |
June | 592.00000 | 22.74892 | 40.21960 | -0.7051 | 18.74501 |
July | 609.00000 | 22.92101 | 48.57914 | -0.5755 | 15.51024 |
August | 612.00000 | 22.35242 | 44.55836 | -0.8074 | 22.93191 |
September | 590.00000 | 21.06219 | 33.80904 | -1.4442 | 47.97065 |
October | 610.00000 | 20.85782 | 20.76001 | -0.5619 | 12.69031 |
November | 591.00000 | 20.81451 | 9.24409 | -0.8073 | 19.48101 |
December | 609.00000 | 20.80427 | 9.11665 | -0.8609 | 21.33132 |
Annual Sum or Average | 7187.00000 | 21.37116 | 23.86274 | -0.8203 | 22.24091 |
Minimum of Months | 551.00000 | 20.70948 | 9.11665 | -1.4442 | 11.33651 |
Maximum of Months | 612.00000 | 22.92101 | 48.57914 | -0.4844 | 47.97065 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72374 | 18.00977 | -0.8873 | 22.20082 |
February | 551.00000 | 18.72426 | 20.11038 | -0.8712 | 21.70939 |
March | 612.00000 | 18.72608 | 22.32363 | -0.8157 | 19.79103 |
April | 590.00000 | 19.30515 | 28.44518 | -0.5769 | 14.68556 |
May | 611.00000 | 22.33605 | 33.48919 | -0.7358 | 28.12488 |
June | 592.00000 | 24.93024 | 41.27630 | 0.22558 | 11.56501 |
July | 609.00000 | 25.12362 | 47.43698 | 0.35934 | 13.14126 |
August | 612.00000 | 24.21767 | 45.23745 | 0.03802 | 15.44029 |
September | 590.00000 | 20.52588 | 41.59237 | -1.2501 | 43.40816 |
October | 610.00000 | 18.95092 | 30.23160 | -0.6410 | 15.08268 |
November | 591.00000 | 18.72422 | 17.39898 | -0.8562 | 21.04822 |
December | 609.00000 | 18.72300 | 16.68609 | -0.8911 | 22.32144 |
Annual Sum or Average | 7187.00000 | 20.76738 | 30.25028 | -0.5721 | 20.67744 |
Minimum of Months | 551.00000 | 18.72300 | 16.68609 | -1.2501 | 11.56501 |
Maximum of Months | 612.00000 | 25.12362 | 47.43698 | 0.35934 | 43.40816 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 |
May | 0.157915E+09 | 46291931.26 | 23.83 | 0.157915E+09 | -0.0 | 0.00 | 0.46 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 | 5718.35 | 31-MAY-16:05 | 5718.35 | 31-MAY-16:05 | 0.00 | 31-MAY-15:45 | 1592.16 | 31-MAY-16:05 | 0.00 | 01-MAY-00:01 |
June | 0.289421E+10 | 0.782089E+09 | 176.64 | 0.275952E+10 | 0.134688E+09 | 0.00 | 1.00 | 21-JUN-04:01 | 0.00 | 01-JUN-00:01 | 22726.49 | 22-JUN-04:01 | 16685.01 | 22-JUN-04:01 | 6149.85 | 30-JUN-04:01 | 5449.81 | 22-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.553273E+10 | 0.145895E+10 | 227.92 | 0.508302E+10 | 0.449705E+09 | 0.00 | 1.00 | 08-JUL-04:01 | 0.00 | 01-JUL-00:01 | 23411.02 | 23-JUL-04:01 | 17375.29 | 29-JUL-17:10 | 10104.34 | 23-JUL-04:01 | 5613.79 | 23-JUL-04:01 | 0.00 | 01-JUL-00:01 |
August | 0.227209E+10 | 0.621610E+09 | 132.60 | 0.210029E+10 | 0.171801E+09 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 | 19530.06 | 03-AUG-04:01 | 14498.50 | 12-AUG-04:01 | 8324.47 | 13-AUG-04:01 | 4684.06 | 03-AUG-04:01 | 0.00 | 01-AUG-00:01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.108569E+11 | 0.290894E+10 | 560.99 | 0.101008E+11 | 0.756194E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.553273E+10 | 0.145895E+10 | 227.92 | 0.508302E+10 | 0.449705E+09 | 0.00 | 1.00 | 0.00 | 23411.02 | 17375.29 | 10104.34 | 5613.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 430859.45 | 123007.53 | 0.20 | 319466.41 | 111393.04 | 0.00 | 0.51 | 28-APR-04:01 | 0.00 | 01-APR-00:01 | 5032.96 | 28-APR-04:01 | 3704.19 | 28-APR-04:01 | 1328.76 | 28-APR-04:01 | 1385.13 | 28-APR-04:01 | 0.00 | 01-APR-00:01 |
May | 0.637728E+09 | 0.182427E+09 | 81.39 | 0.632968E+09 | 4759752.94 | 0.00 | 1.00 | 09-MAY-03:42 | 0.00 | 01-MAY-00:01 | 22888.59 | 31-MAY-04:01 | 18742.81 | 31-MAY-04:01 | 4145.78 | 31-MAY-04:01 | 5487.52 | 31-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.550344E+10 | 0.145960E+10 | 311.45 | 0.509628E+10 | 0.407153E+09 | 0.00 | 1.00 | 03-JUN-04:01 | 0.00 | 01-JUN-00:01 | 22888.59 | 06-JUN-04:01 | 18595.09 | 14-JUN-02:52 | 10896.87 | 28-JUN-04:01 | 5487.52 | 03-JUN-04:01 | 0.00 | 01-JUN-00:01 |
July | 0.880069E+10 | 0.225033E+10 | 362.55 | 0.753492E+10 | 0.126577E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 22888.59 | 01-JUL-04:01 | 17658.67 | 12-JUL-02:11 | 12192.63 | 25-JUL-03:31 | 5487.52 | 01-JUL-04:01 | 0.00 | 01-JUL-00:01 |
August | 0.475466E+10 | 0.125872E+10 | 249.84 | 0.397273E+10 | 0.781928E+09 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 22888.59 | 01-AUG-04:02 | 18206.02 | 12-AUG-02:52 | 11459.39 | 04-AUG-03:31 | 5487.52 | 01-AUG-04:01 | 0.00 | 01-AUG-00:01 |
September | 16476474.09 | 4562563.43 | 2.76 | 10714227.61 | 5762246.48 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:01 | 12034.65 | 01-SEP-04:01 | 7581.70 | 19-SEP-04:01 | 5040.33 | 01-SEP-04:01 | 2887.32 | 01-SEP-04:01 | 0.00 | 01-SEP-00:01 |
October | 1143476.08 | 317250.81 | 0.12 | 920857.76 | 222618.33 | 0.00 | 0.70 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 | 7346.41 | 06-OCT-04:01 | 6280.77 | 06-OCT-04:01 | 1768.91 | 03-OCT-04:01 | 1919.76 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.197146E+11 | 0.515607E+10 | 1008.31 | 0.172489E+11 | 0.246571E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.880069E+10 | 0.225033E+10 | 362.55 | 0.753492E+10 | 0.126577E+10 | 0.00 | 1.00 | 0.00 | 22888.59 | 18742.81 | 12192.63 | 5487.52 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.44 | 3.92 | 8.52 | 1.24 | 321.98 | 0.00 | 0.00 | 0.00 |
February | 68.74 | 32.81 | 35.93 | 37.20 | 266.88 | 0.00 | 0.00 | 0.00 |
March | 196.03 | 99.27 | 96.77 | 169.25 | 194.44 | 0.00 | 0.00 | 0.00 |
April | 269.45 | 136.30 | 133.15 | 258.52 | 103.00 | 0.00 | 0.00 | 0.00 |
May | 391.41 | 220.32 | 171.09 | 441.37 | 49.67 | 0.00 | 0.00 | 0.00 |
June | 360.13 | 167.76 | 192.37 | 415.94 | 25.37 | 0.00 | 0.00 | 0.00 |
July | 342.07 | 165.63 | 176.44 | 403.43 | 29.56 | 0.00 | 0.00 | 0.00 |
August | 270.93 | 131.74 | 139.19 | 307.47 | 46.98 | 0.00 | 0.00 | 0.00 |
September | 167.62 | 73.37 | 94.25 | 163.23 | 87.28 | 0.00 | 0.00 | 0.00 |
October | 88.55 | 35.53 | 53.01 | 65.24 | 169.99 | 0.00 | 0.00 | 0.00 |
November | 18.84 | 6.59 | 12.25 | 1.68 | 314.44 | 0.00 | 0.00 | 0.00 |
December | 2.69 | 0.65 | 2.05 | 0.00 | 348.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183.11 | 89.88 | 93.22 | 189.73 | 162.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.69 | 0.65 | 2.05 | 0.00 | 25.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 391.41 | 220.32 | 192.37 | 441.37 | 348.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.26 | 74.60 | 38.66 | 68.47 | 595.94 | 0.00 | 0.00 | 0.00 |
February | 389.77 | 271.08 | 118.68 | 337.10 | 474.69 | 0.00 | 0.00 | 0.00 |
March | 669.43 | 453.71 | 215.72 | 666.98 | 358.46 | 0.00 | 0.00 | 0.00 |
April | 816.82 | 508.15 | 308.67 | 908.86 | 222.08 | 0.00 | 0.00 | 0.00 |
May | 673.64 | 349.10 | 324.54 | 776.06 | 110.91 | 0.00 | 0.00 | 0.00 |
June | 615.07 | 252.16 | 362.91 | 723.24 | 62.07 | 0.00 | 0.00 | 0.00 |
July | 592.59 | 258.12 | 334.46 | 711.20 | 67.18 | 0.00 | 0.00 | 0.00 |
August | 613.62 | 338.19 | 275.43 | 725.07 | 99.82 | 0.00 | 0.00 | 0.00 |
September | 495.85 | 298.61 | 197.24 | 538.58 | 175.25 | 0.00 | 0.00 | 0.00 |
October | 356.95 | 226.45 | 130.51 | 332.13 | 312.17 | 0.00 | 0.00 | 0.00 |
November | 191.35 | 133.59 | 57.76 | 130.08 | 559.45 | 0.00 | 0.00 | 0.00 |
December | 33.96 | 23.93 | 10.03 | 6.74 | 666.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.41 | 265.24 | 198.17 | 494.10 | 307.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.96 | 23.93 | 10.03 | 6.74 | 62.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 816.82 | 508.15 | 362.91 | 908.86 | 666.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.55 | 1.17 | 5.38 | 0.00 | 328.04 | 0.00 | 0.00 | 0.00 |
February | 38.64 | 13.44 | 25.20 | 8.09 | 276.24 | 0.00 | 0.00 | 0.00 |
March | 115.95 | 49.85 | 66.10 | 68.60 | 198.07 | 0.00 | 0.00 | 0.00 |
April | 275.10 | 142.54 | 132.55 | 271.92 | 109.27 | 0.00 | 0.00 | 0.00 |
May | 267.49 | 121.80 | 145.69 | 282.91 | 51.77 | 0.00 | 0.00 | 0.00 |
June | 293.17 | 124.99 | 168.18 | 330.91 | 28.74 | 0.00 | 0.00 | 0.00 |
July | 245.30 | 92.78 | 152.52 | 278.96 | 31.92 | 0.00 | 0.00 | 0.00 |
August | 201.61 | 85.36 | 116.24 | 218.51 | 48.43 | 0.00 | 0.00 | 0.00 |
September | 122.02 | 51.10 | 70.92 | 105.76 | 89.01 | 0.00 | 0.00 | 0.00 |
October | 47.79 | 14.37 | 33.42 | 18.65 | 176.56 | 0.00 | 0.00 | 0.00 |
November | 19.12 | 6.95 | 12.17 | 2.15 | 313.55 | 0.00 | 0.00 | 0.00 |
December | 1.72 | 0.18 | 1.54 | 0.00 | 349.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.55 | 58.83 | 77.72 | 132.73 | 166.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.72 | 0.18 | 1.54 | 0.00 | 28.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 293.17 | 142.54 | 168.18 | 330.91 | 349.63 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33329763.45 | 10496894.43 | 22832869.01 | 3326732.38 | 0.862381E+09 |
February | 0.166297E+09 | 79364243.88 | 86932743.04 | 90000952.00 | 0.645633E+09 |
March | 0.525056E+09 | 0.265878E+09 | 0.259178E+09 | 0.453319E+09 | 0.520787E+09 |
April | 0.698407E+09 | 0.353284E+09 | 0.345122E+09 | 0.670087E+09 | 0.266975E+09 |
May | 0.104835E+10 | 0.590098E+09 | 0.458254E+09 | 0.118217E+10 | 0.133026E+09 |
June | 0.933456E+09 | 0.434829E+09 | 0.498627E+09 | 0.107811E+10 | 65767000.24 |
July | 0.916197E+09 | 0.443625E+09 | 0.472572E+09 | 0.108055E+10 | 79161162.97 |
August | 0.725671E+09 | 0.352861E+09 | 0.372810E+09 | 0.823521E+09 | 0.125841E+09 |
September | 0.434459E+09 | 0.190162E+09 | 0.244296E+09 | 0.423099E+09 | 0.226236E+09 |
October | 0.237161E+09 | 95167863.96 | 0.141993E+09 | 0.174729E+09 | 0.455291E+09 |
November | 48832550.85 | 17073161.93 | 31759388.92 | 4351585.20 | 0.815021E+09 |
December | 7210060.57 | 1728200.15 | 5481860.42 | 0.00 | 0.933412E+09 |
Annual Sum or Average | 0.577443E+10 | 0.283457E+10 | 0.293986E+10 | 0.598327E+10 | 0.512953E+10 |
Minimum of Months | 7210060.57 | 1728200.15 | 5481860.42 | 0.00 | 65767000.24 |
Maximum of Months | 0.104835E+10 | 0.590098E+09 | 0.498627E+09 | 0.118217E+10 | 0.933412E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303352E+09 | 0.199814E+09 | 0.103538E+09 | 0.183394E+09 | 0.159616E+10 |
February | 0.942924E+09 | 0.655803E+09 | 0.287121E+09 | 0.815511E+09 | 0.114836E+10 |
March | 0.179299E+10 | 0.121521E+10 | 0.577778E+09 | 0.178644E+10 | 0.960104E+09 |
April | 0.211721E+10 | 0.131713E+10 | 0.800083E+09 | 0.235578E+10 | 0.575631E+09 |
May | 0.180426E+10 | 0.935020E+09 | 0.869245E+09 | 0.207861E+10 | 0.297070E+09 |
June | 0.159426E+10 | 0.653606E+09 | 0.940651E+09 | 0.187464E+10 | 0.160889E+09 |
July | 0.158718E+10 | 0.691349E+09 | 0.895831E+09 | 0.190488E+10 | 0.179924E+09 |
August | 0.164353E+10 | 0.905810E+09 | 0.737718E+09 | 0.194204E+10 | 0.267357E+09 |
September | 0.128525E+10 | 0.774000E+09 | 0.511249E+09 | 0.139600E+10 | 0.454255E+09 |
October | 0.956068E+09 | 0.606511E+09 | 0.349557E+09 | 0.889567E+09 | 0.836103E+09 |
November | 0.495988E+09 | 0.346264E+09 | 0.149724E+09 | 0.337165E+09 | 0.145010E+10 |
December | 90969552.78 | 64107475.90 | 26862076.88 | 18060558.14 | 0.178401E+10 |
Annual Sum or Average | 0.146140E+11 | 0.836462E+10 | 0.624936E+10 | 0.155821E+11 | 0.970996E+10 |
Minimum of Months | 90969552.78 | 64107475.90 | 26862076.88 | 18060558.14 | 0.160889E+09 |
Maximum of Months | 0.211721E+10 | 0.131713E+10 | 0.940651E+09 | 0.235578E+10 | 0.178401E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 17531122.69 | 3132162.29 | 14398960.40 | 0.00 | 0.878624E+09 |
February | 93471118.92 | 32515746.87 | 60955372.05 | 19570596.40 | 0.668269E+09 |
March | 0.310564E+09 | 0.133517E+09 | 0.177047E+09 | 0.183742E+09 | 0.530518E+09 |
April | 0.713054E+09 | 0.369474E+09 | 0.343580E+09 | 0.704820E+09 | 0.283215E+09 |
May | 0.716449E+09 | 0.326235E+09 | 0.390213E+09 | 0.757753E+09 | 0.138655E+09 |
June | 0.759884E+09 | 0.323965E+09 | 0.435919E+09 | 0.857729E+09 | 74498488.92 |
July | 0.657003E+09 | 0.248504E+09 | 0.408499E+09 | 0.747170E+09 | 85489646.87 |
August | 0.539981E+09 | 0.228636E+09 | 0.311345E+09 | 0.585253E+09 | 0.129704E+09 |
September | 0.316269E+09 | 0.132438E+09 | 0.183831E+09 | 0.274118E+09 | 0.230727E+09 |
October | 0.128009E+09 | 38496497.14 | 89512770.21 | 49958662.93 | 0.472905E+09 |
November | 49571909.52 | 18020209.55 | 31551699.97 | 5576233.48 | 0.812711E+09 |
December | 4598434.10 | 484276.56 | 4114157.53 | 0.00 | 0.936445E+09 |
Annual Sum or Average | 0.430639E+10 | 0.185542E+10 | 0.245097E+10 | 0.418569E+10 | 0.524176E+10 |
Minimum of Months | 4598434.10 | 484276.56 | 4114157.53 | 0.00 | 74498488.92 |
Maximum of Months | 0.759884E+09 | 0.369474E+09 | 0.435919E+09 | 0.857729E+09 | 0.936445E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.97 | 1219.21 | 132.25 | 79.69 | 52.56 | 0.00 | 0.00 |
February | 329.00 | 964.41 | 497.14 | 317.33 | 179.82 | 0.00 | 0.00 |
March | 863.51 | 709.66 | 981.41 | 602.83 | 378.59 | 0.00 | 0.00 |
April | 1403.40 | 398.43 | 1361.37 | 786.99 | 574.38 | 0.00 | 0.00 |
May | 1479.25 | 191.24 | 1332.54 | 691.22 | 641.32 | 0.00 | 0.00 |
June | 1455.54 | 101.63 | 1268.36 | 544.91 | 723.46 | 0.00 | 0.00 |
July | 1383.41 | 118.47 | 1179.95 | 516.53 | 663.42 | 0.00 | 0.00 |
August | 1239.86 | 184.04 | 1086.16 | 555.30 | 530.87 | 0.00 | 0.00 |
September | 793.46 | 337.44 | 785.48 | 423.07 | 362.41 | 0.00 | 0.00 |
October | 388.30 | 631.00 | 493.29 | 276.35 | 216.94 | 0.00 | 0.00 |
November | 89.67 | 1143.19 | 229.32 | 147.13 | 82.19 | 0.00 | 0.00 |
December | 1.13 | 1358.59 | 38.37 | 24.76 | 13.61 | 0.00 | 0.00 |
Annual Sum or Average | 791.30 | 611.51 | 783.07 | 413.96 | 369.11 | 0.00 | 0.00 |
Minimum of Months | 1.13 | 101.63 | 38.37 | 24.76 | 13.61 | 0.00 | 0.00 |
Maximum of Months | 1479.25 | 1358.59 | 1361.37 | 786.99 | 723.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115093E+09 | 0.326553E+10 | 0.354213E+09 | 0.213443E+09 | 0.140770E+09 | 0.00 | 0.00 |
February | 0.795924E+09 | 0.233310E+10 | 0.120269E+10 | 0.767683E+09 | 0.435009E+09 | 0.00 | 0.00 |
March | 0.231284E+10 | 0.190074E+10 | 0.262861E+10 | 0.161461E+10 | 0.101400E+10 | 0.00 | 0.00 |
April | 0.363760E+10 | 0.103274E+10 | 0.352867E+10 | 0.203988E+10 | 0.148879E+10 | 0.00 | 0.00 |
May | 0.396201E+10 | 0.512222E+09 | 0.356906E+10 | 0.185135E+10 | 0.171771E+10 | 0.00 | 0.00 |
June | 0.377275E+10 | 0.263428E+09 | 0.328760E+10 | 0.141240E+10 | 0.187520E+10 | 0.00 | 0.00 |
July | 0.370534E+10 | 0.317308E+09 | 0.316038E+10 | 0.138348E+10 | 0.177690E+10 | 0.00 | 0.00 |
August | 0.332083E+10 | 0.492921E+09 | 0.290918E+10 | 0.148731E+10 | 0.142187E+10 | 0.00 | 0.00 |
September | 0.205665E+10 | 0.874655E+09 | 0.203598E+10 | 0.109660E+10 | 0.939376E+09 | 0.00 | 0.00 |
October | 0.104003E+10 | 0.169008E+10 | 0.132124E+10 | 0.740175E+09 | 0.581062E+09 | 0.00 | 0.00 |
November | 0.232416E+09 | 0.296316E+10 | 0.594393E+09 | 0.381358E+09 | 0.213035E+09 | 0.00 | 0.00 |
December | 3032678.71 | 0.363884E+10 | 0.102778E+09 | 66319952.62 | 36458094.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.249545E+11 | 0.192847E+11 | 0.246948E+11 | 0.130546E+11 | 0.116402E+11 | 0.00 | 0.00 |
Minimum of Months | 3032678.71 | 0.263428E+09 | 0.102778E+09 | 66319952.62 | 36458094.83 | 0.00 | 0.00 |
Maximum of Months | 0.396201E+10 | 0.363884E+10 | 0.356906E+10 | 0.203988E+10 | 0.187520E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.170562E+11 | -0.162503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -805927364.8 | 58.99 | 0.00 | 0.00 |
February | 0.154061E+11 | -0.146781E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -727990261.3 | 58.99 | 0.00 | 0.00 |
March | 0.170891E+11 | -0.162844E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -804662928.6 | 58.99 | 0.00 | 0.00 |
April | 0.164848E+11 | -0.157203E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -764517989.9 | 58.99 | 0.00 | 0.00 |
May | 0.168750E+11 | -0.161467E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -728341146.6 | 58.99 | 0.00 | 0.00 |
June | 0.157098E+11 | -0.150551E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -654731914.8 | 58.99 | 0.00 | 0.00 |
July | 0.156024E+11 | -0.149294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -673009264.4 | 58.99 | 0.00 | 0.00 |
August | 0.152953E+11 | -0.146062E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -689096533.3 | 58.99 | 0.00 | 0.00 |
September | 0.147918E+11 | -0.140556E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -736242954.3 | 59.00 | 0.00 | 0.00 |
October | 0.156099E+11 | -0.148149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -795063433.5 | 58.98 | 0.00 | 0.00 |
November | 0.156440E+11 | -0.148659E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -778103855.5 | 58.99 | 0.00 | 0.00 |
December | 0.167799E+11 | -0.159741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -805805551.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.192344E+12 | -0.183381E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.896349E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.147918E+11 | -0.162844E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -805927364.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.170891E+11 | -0.140556E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -654731914.8 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.62 | 08-JAN-11:30 | 284.19 | 12.27 | 0.00 | 61.83 | 288.74 | 12.21 | 0.00 | 64.50 |
February | 205.83 | 0.67 | 0.62 | 01-FEB-10:50 | 694.92 | 15.83 | 0.00 | 168.33 | 706.10 | 15.96 | 0.00 | 168.67 |
March | 329.50 | 0.65 | 0.62 | 01-MAR-09:20 | 4469.17 | 29.85 | 232.00 | 300.00 | 4344.08 | 29.62 | 217.17 | 302.33 |
April | 421.83 | 0.64 | 0.62 | 01-APR-07:10 | 2441.62 | 21.96 | 182.83 | 401.33 | 1981.09 | 20.76 | 134.83 | 404.17 |
May | 545.00 | 0.65 | 0.62 | 01-MAY-04:49 | 1842.87 | 17.98 | 80.67 | 486.33 | 2644.19 | 19.32 | 105.83 | 485.33 |
June | 583.50 | 0.65 | 0.62 | 01-JUN-03:39 | 1620.13 | 17.78 | 95.50 | 512.67 | 1795.70 | 17.79 | 61.00 | 510.33 |
July | 562.83 | 0.65 | 0.62 | 01-JUL-03:00 | 1759.80 | 17.96 | 92.50 | 502.83 | 1833.66 | 17.89 | 81.50 | 499.50 |
August | 467.17 | 0.64 | 0.62 | 01-AUG-04:49 | 2200.71 | 20.64 | 143.50 | 430.50 | 2232.77 | 20.53 | 125.00 | 425.83 |
September | 356.33 | 0.65 | 0.62 | 01-SEP-06:19 | 3713.46 | 28.68 | 241.67 | 324.83 | 3498.19 | 28.19 | 229.50 | 322.83 |
October | 265.50 | 0.66 | 0.62 | 01-OCT-07:40 | 1425.46 | 23.21 | 100.83 | 233.50 | 1451.78 | 23.03 | 100.33 | 234.50 |
November | 135.83 | 0.69 | 0.62 | 01-NOV-09:50 | 370.30 | 14.12 | 0.00 | 115.67 | 370.86 | 14.07 | 0.00 | 115.50 |
December | 71.17 | 0.89 | 0.62 | 04-DEC-11:20 | 94.74 | 7.67 | 0.00 | 4.50 | 95.73 | 7.57 | 0.00 | 5.00 |
Annual Sum or Average | 4053.17 | 0.66 | 2073.31 | 20.35 | 1169.50 | 3542.33 | 2145.71 | 20.31 | 1055.17 | 3538.50 | ||
Minimum of Months | 71.17 | 0.64 | 0.62 | 94.74 | 7.67 | 0.00 | 4.50 | 95.73 | 7.57 | 0.00 | 5.00 | |
Maximum of Months | 583.50 | 0.89 | 0.62 | 4469.17 | 29.85 | 241.67 | 512.67 | 4344.08 | 29.62 | 229.50 | 510.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.898576E+11 | 67916.31 | 01-JAN-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.734606E+11 | 67916.31 | 01-FEB-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.644798E+11 | 67916.31 | 01-MAR-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298203E+11 | 67916.31 | 03-APR-02:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.757678E+10 | 27441.55 | 27-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119014E+10 | 8908.53 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105424E+10 | 9021.09 | 27-JUL-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.322994E+10 | 19617.79 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167374E+11 | 28563.83 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.448528E+11 | 67916.31 | 22-OCT-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.855752E+11 | 67916.31 | 06-NOV-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942119E+11 | 67916.31 | 01-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.512047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.105424E+10 | 8908.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.942119E+11 | 67916.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.709093E+11 | 81986.37 | 12-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575180E+11 | 77172.64 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.472844E+11 | 68428.37 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172601E+11 | 52079.44 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122490E+10 | 15824.29 | 27-MAY-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1129158.82 | 5314.41 | 02-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.369601E+09 | 16075.42 | 31-AUG-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482241E+10 | 24990.01 | 30-SEP-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.273967E+11 | 53191.02 | 31-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.665900E+11 | 74050.00 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.746650E+11 | 73450.30 | 28-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.368042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.746650E+11 | 81986.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.157915E+09 | 0.157915E+09 | 5718.35 | 31-MAY-16:05 | 5718.35 | 0.00 |
June | 0.00 | 0.00 | 0.289421E+10 | 0.275952E+10 | 22726.49 | 22-JUN-04:01 | 16685.01 | 0.00 |
July | 0.00 | 0.00 | 0.553273E+10 | 0.508302E+10 | 23411.02 | 23-JUL-04:01 | 13306.68 | 0.00 |
August | 0.00 | 0.00 | 0.227209E+10 | 0.210029E+10 | 19530.06 | 03-AUG-04:01 | 12823.97 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108569E+11 | 0.101008E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.553273E+10 | 0.508302E+10 | 23411.02 | 16685.01 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 430859.45 | 319466.41 | 5032.96 | 28-APR-04:01 | 3704.19 | 0.00 |
May | 0.00 | 0.00 | 0.637728E+09 | 0.632968E+09 | 22888.59 | 31-MAY-04:01 | 18742.81 | 0.00 |
June | 0.00 | 0.00 | 0.550344E+10 | 0.509628E+10 | 22888.59 | 06-JUN-04:01 | 14086.61 | 0.00 |
July | 0.00 | 0.00 | 0.880069E+10 | 0.753492E+10 | 22888.59 | 01-JUL-04:01 | 13383.02 | 0.00 |
August | 0.00 | 0.00 | 0.475466E+10 | 0.397273E+10 | 22888.59 | 01-AUG-04:02 | 12187.86 | 0.00 |
September | 0.00 | 0.00 | 16476474.09 | 10714227.61 | 12034.65 | 01-SEP-04:01 | 6994.32 | 0.00 |
October | 0.00 | 0.00 | 1143476.08 | 920857.76 | 7346.41 | 06-OCT-04:01 | 6280.77 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197146E+11 | 0.172489E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.880069E+10 | 0.753492E+10 | 22888.59 | 18742.81 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6367.20 | 23784.62 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6367.07 | 23784.62 | 05-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6381.39 | 23784.98 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6363.65 | 23785.73 | 04-APR-12:28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6327.92 | 23785.60 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6106.36 | 23161.98 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5867.33 | 22208.02 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5749.33 | 21474.91 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5715.85 | 21341.56 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5825.65 | 21970.90 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6032.20 | 22879.23 | 30-NOV-13:15 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 6261.56 | 23782.66 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.36 | ||||
Minimum of Months | 0.00 | 0.00 | 5715.85 | 21341.56 | ||
Maximum of Months | 0.00 | 0.00 | 6381.39 | 23785.73 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112411E+10 | 0.23 | 503.64 | 01-JAN-00:01 | 0.27 |
February | 0.101533E+10 | 0.23 | 503.64 | 01-FEB-00:01 | 0.27 |
March | 0.112411E+10 | 0.22 | 503.64 | 01-MAR-00:01 | 0.27 |
April | 0.108846E+10 | 0.22 | 503.64 | 01-APR-04:01 | 0.27 |
May | 0.115630E+10 | 0.23 | 503.64 | 01-MAY-04:01 | 0.27 |
June | 0.120108E+10 | 0.25 | 503.64 | 01-JUN-01:50 | 0.27 |
July | 0.125497E+10 | 0.25 | 503.64 | 01-JUL-00:45 | 0.27 |
August | 0.123573E+10 | 0.24 | 503.64 | 01-AUG-00:50 | 0.27 |
September | 0.111148E+10 | 0.23 | 503.64 | 01-SEP-03:06 | 0.27 |
October | 0.112487E+10 | 0.22 | 503.64 | 01-OCT-04:01 | 0.27 |
November | 0.108785E+10 | 0.23 | 503.64 | 01-NOV-04:01 | 0.27 |
December | 0.112411E+10 | 0.23 | 503.64 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.136484E+11 | 0.23 | |||
Minimum of Months | 0.101533E+10 | 0.22 | 503.64 | 0.27 | |
Maximum of Months | 0.125497E+10 | 0.25 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298907E+10 | 0.68 | 1737.11 | 01-JAN-04:23 | 0.90 |
February | 0.257021E+10 | 0.66 | 1737.11 | 01-FEB-03:02 | 0.90 |
March | 0.257542E+10 | 0.63 | 1737.11 | 01-MAR-03:06 | 0.90 |
April | 0.196408E+10 | 0.54 | 1737.11 | 03-APR-02:53 | 0.90 |
May | 0.166720E+10 | 0.47 | 1115.97 | 27-MAY-04:01 | 0.72 |
June | 0.151962E+10 | 0.45 | 1292.63 | 22-JUN-04:01 | 0.77 |
July | 0.156939E+10 | 0.45 | 1341.96 | 23-JUL-04:01 | 0.79 |
August | 0.160064E+10 | 0.46 | 1062.30 | 03-AUG-04:01 | 0.70 |
September | 0.175774E+10 | 0.50 | 1133.20 | 30-SEP-04:01 | 0.72 |
October | 0.224862E+10 | 0.57 | 1737.11 | 22-OCT-03:03 | 0.90 |
November | 0.286998E+10 | 0.67 | 1737.11 | 06-NOV-04:08 | 0.90 |
December | 0.305616E+10 | 0.69 | 1737.11 | 01-DEC-03:02 | 0.90 |
Annual Sum or Average | 0.263881E+11 | 0.56 | |||
Minimum of Months | 0.151962E+10 | 0.45 | 1062.30 | 0.70 | |
Maximum of Months | 0.305616E+10 | 0.69 | 1737.11 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169176E+10 | 0.58 | 1113.48 | 12-JAN-00:02 | 0.86 |
February | 0.148182E+10 | 0.57 | 1079.40 | 27-FEB-05:03 | 0.84 |
March | 0.152450E+10 | 0.55 | 1017.49 | 04-MAR-05:02 | 0.82 |
April | 0.127358E+10 | 0.50 | 901.75 | 03-APR-04:02 | 0.77 |
May | 0.120251E+10 | 0.48 | 1332.60 | 31-MAY-04:01 | 0.92 |
June | 0.117780E+10 | 0.51 | 1332.60 | 03-JUN-04:01 | 0.92 |
July | 0.123037E+10 | 0.52 | 1332.60 | 01-JUL-04:01 | 0.92 |
August | 0.121476E+10 | 0.51 | 1332.60 | 01-AUG-04:01 | 0.92 |
September | 0.118797E+10 | 0.48 | 709.96 | 30-SEP-04:04 | 0.67 |
October | 0.138376E+10 | 0.51 | 909.62 | 31-OCT-04:03 | 0.77 |
November | 0.162280E+10 | 0.58 | 1057.29 | 29-NOV-05:02 | 0.83 |
December | 0.171835E+10 | 0.59 | 1053.05 | 28-DEC-05:02 | 0.83 |
Annual Sum or Average | 0.167100E+11 | 0.53 | |||
Minimum of Months | 0.117780E+10 | 0.48 | 709.96 | 0.67 | |
Maximum of Months | 0.171835E+10 | 0.59 | 1332.60 | 0.92 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.33 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.09 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.17 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 49.84 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:03 | 0.00 | 0.00 | 45.72 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:05 | 0.00 | 0.00 | 49.89 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 50.58 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 50.52 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:05 | 0.00 | 0.00 | 50.94 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 49.43 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 50.53 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.60 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 45.72 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 50.94 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 33.61 | 33.61 | 6367.20 | 23784.62 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 49.97 | 49.97 | 6367.07 | 23784.62 | 05-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.87 | 49.87 | 6381.39 | 23784.98 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.87 | 49.87 | 6363.65 | 23785.73 | 04-APR-12:28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 33.73 | 33.73 | 6327.92 | 23785.60 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.02 | 50.02 | 6106.36 | 23161.98 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.88 | 50.88 | 5867.33 | 22208.02 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.56 | 50.56 | 5749.33 | 21474.91 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 51.23 | 51.23 | 5715.85 | 21341.56 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 36.13 | 36.13 | 5825.65 | 21970.90 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.89 | 50.89 | 6032.20 | 22879.23 | 30-NOV-13:15 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 50.35 | 50.35 | 6261.56 | 23782.66 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 33.61 | 33.61 | 5715.85 | 21341.56 | ||
Maximum of Months | 0.00 | 0.00 | 51.23 | 51.23 | 6381.39 | 23785.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.298907E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.257021E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.257542E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.196408E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.171349E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.230171E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.302833E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.222225E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175774E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224862E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.286998E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.305616E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.292971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.305616E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.169176E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148182E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152450E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.127370E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.138494E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.263740E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.348069E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.247347E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119253E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.138408E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162280E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171835E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218660E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119253E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.348069E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.298907E+10 | 0.00 | 0.898576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257021E+10 | 0.00 | 0.734606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257542E+10 | 0.00 | 0.644798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196408E+10 | 0.00 | 0.298203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166720E+10 | 0.157915E+09 | 0.757678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151962E+10 | 0.289421E+10 | 0.119014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156939E+10 | 0.553273E+10 | 0.105424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160064E+10 | 0.227209E+10 | 0.322994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175774E+10 | 0.00 | 0.167374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.224862E+10 | 0.00 | 0.448528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286998E+10 | 0.00 | 0.855752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305616E+10 | 0.00 | 0.942119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263881E+11 | 0.108569E+11 | 0.512047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151962E+10 | 0.00 | 0.105424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.305616E+10 | 0.553273E+10 | 0.942119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169176E+10 | 0.00 | 0.709093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148182E+10 | 0.00 | 0.575180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152450E+10 | 0.00 | 0.472844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127358E+10 | 430859.45 | 0.172601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120251E+10 | 0.637728E+09 | 0.122490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117780E+10 | 0.549972E+10 | 1129158.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123037E+10 | 0.879791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121476E+10 | 0.475161E+10 | 0.369601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118797E+10 | 16476474.09 | 0.482241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138376E+10 | 1143476.08 | 0.273967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162280E+10 | 0.00 | 0.665900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171835E+10 | 0.00 | 0.746650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167100E+11 | 0.197050E+11 | 0.368042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171835E+10 | 0.879791E+10 | 0.746650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.298907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166720E+10 | 0.00 | 0.00 | 0.00 | 46291931.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151962E+10 | 0.00 | 0.00 | 0.00 | 0.782089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156939E+10 | 0.00 | 0.00 | 0.00 | 0.145895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160064E+10 | 0.00 | 0.00 | 0.00 | 0.621610E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.224862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.305616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263881E+11 | 0.00 | 0.00 | 0.00 | 0.290894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.305616E+10 | 0.00 | 0.00 | 0.00 | 0.145895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127358E+10 | 0.00 | 0.00 | 0.00 | 123007.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120251E+10 | 0.00 | 0.00 | 0.00 | 0.182427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117780E+10 | 0.00 | 0.00 | 0.00 | 0.145960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123037E+10 | 0.00 | 0.00 | 0.00 | 0.225033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121476E+10 | 0.00 | 0.00 | 0.00 | 0.125872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118797E+10 | 0.00 | 0.00 | 0.00 | 4562563.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138376E+10 | 0.00 | 0.00 | 0.00 | 317250.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167100E+11 | 0.00 | 0.00 | 0.00 | 0.515607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171835E+10 | 0.00 | 0.00 | 0.00 | 0.225033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483326E+11 | 0.00 | 0.00 | 3.66 |
February | 0.157934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400501E+11 | 0.00 | 0.00 | 3.62 |
March | 0.162798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375339E+11 | 0.00 | 0.00 | 3.60 |
April | 0.320982E+10 | 0.00 | 0.00 | 1471.85 | 0.00 | 0.200438E+11 | 15032947.89 | 0.00 | 3.59 |
May | 0.701555E+10 | 0.00 | 0.00 | 3071119.72 | 0.00 | 0.517501E+10 | 0.150473E+10 | 0.00 | 3.76 |
June | 0.533055E+10 | 11270858.72 | 0.00 | 15442542.22 | 0.00 | 0.369627E+09 | 0.426084E+10 | 0.00 | 4.43 |
July | 0.475652E+10 | 55200795.82 | 0.00 | 21426478.96 | 0.00 | 0.472159E+09 | 0.397326E+10 | 0.00 | 4.48 |
August | 0.629029E+10 | 0.00 | 0.00 | 12323324.83 | 0.00 | 0.184881E+10 | 0.341120E+10 | 0.00 | 4.20 |
September | 0.514071E+10 | 0.00 | 0.00 | 52439.43 | 0.00 | 0.118006E+11 | 0.129221E+09 | 0.00 | 3.58 |
October | 0.181485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275206E+11 | 0.00 | 0.00 | 3.59 |
November | 0.183699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466669E+11 | 0.00 | 0.00 | 3.62 |
December | 0.190013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499712E+11 | 0.00 | 0.00 | 3.65 |
Annual Sum or Average | 0.422614E+11 | 66471654.54 | 0.00 | 52317377.00 | 0.00 | 0.289785E+12 | 0.132943E+11 | 0.00 | 3.82 |
Minimum of Months | 0.157934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369627E+09 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.701555E+10 | 55200795.82 | 0.00 | 21426478.96 | 0.00 | 0.499712E+11 | 0.426084E+10 | 0.00 | 4.48 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.986837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123555E+09 | 0.00 | 0.00 | 7.80 |
February | 0.830018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104766E+09 | 0.00 | 0.00 | 7.62 |
March | 0.771005E+11 | 0.00 | 0.00 | 1221.14 | 0.00 | 88496939.61 | 2502994.20 | 0.00 | 7.39 |
April | 0.480462E+11 | 0.00 | 0.00 | 345971.83 | 0.00 | 36171018.35 | 0.796790E+09 | 0.00 | 7.04 |
May | 0.222003E+11 | 0.00 | 0.00 | 17404382.71 | 0.00 | 0.00 | 0.123523E+11 | 0.00 | 6.90 |
June | 0.736838E+10 | 0.00 | 0.00 | 51409869.60 | 0.00 | 0.00 | 0.206523E+11 | 0.00 | 7.06 |
July | 0.625483E+10 | 0.00 | 0.00 | 60704358.16 | 0.00 | 0.00 | 0.198296E+11 | 0.00 | 7.13 |
August | 0.115153E+11 | 0.00 | 0.00 | 43357055.75 | 0.00 | 0.00 | 0.191697E+11 | 0.00 | 6.99 |
September | 0.319083E+11 | 0.00 | 0.00 | 3643013.57 | 0.00 | 2181122.21 | 0.572875E+10 | 0.00 | 6.91 |
October | 0.588082E+11 | 0.00 | 0.00 | 251168.60 | 0.00 | 41286947.98 | 0.410097E+09 | 0.00 | 7.16 |
November | 0.948444E+11 | 0.00 | 0.00 | 1846.12 | 0.00 | 95771272.08 | 2768442.97 | 0.00 | 7.72 |
December | 0.102436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120137E+09 | 0.00 | 0.00 | 7.82 |
Annual Sum or Average | 0.642168E+12 | 0.00 | 0.00 | 0.177119E+09 | 0.00 | 0.612365E+09 | 0.789449E+11 | 0.00 | 7.29 |
Minimum of Months | 0.625483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
Maximum of Months | 0.102436E+12 | 0.00 | 0.00 | 60704358.16 | 0.00 | 0.123555E+09 | 0.206523E+11 | 0.00 | 7.82 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:26
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.527578E+10 | 0.490338E+11 | 0.216631E+12 | 0.00 | 0.524424E+11 |
February | 0.287021E+10 | 0.413141E+11 | 0.183986E+12 | 0.00 | 0.457399E+11 |
March | 0.238466E+11 | 0.394006E+11 | 0.176079E+12 | 0.00 | 0.439151E+11 |
April | 0.467760E+11 | 0.241546E+11 | 0.116308E+12 | 0.00 | 0.292633E+11 |
May | 0.607622E+11 | 0.143003E+11 | 0.852099E+11 | 0.366591E+09 | 0.236861E+11 |
June | 0.632834E+11 | 0.968446E+10 | 0.716304E+11 | 0.134897E+10 | 0.324806E+11 |
July | 0.572558E+11 | 0.846132E+10 | 0.679347E+11 | 0.126297E+10 | 0.410733E+11 |
August | 0.419875E+11 | 0.109979E+11 | 0.788596E+11 | 0.101325E+10 | 0.311751E+11 |
September | 0.182837E+11 | 0.172412E+11 | 0.935700E+11 | 0.00 | 0.210849E+11 |
October | 0.581478E+10 | 0.303253E+11 | 0.139383E+12 | 0.00 | 0.303948E+11 |
November | -0.209592E+10 | 0.470663E+11 | 0.209133E+12 | 0.00 | 0.502244E+11 |
December | -0.684689E+10 | 0.513396E+11 | 0.223834E+12 | 0.00 | 0.540299E+11 |
Annual Sum or Average | 0.306661E+12 | 0.343319E+12 | 0.166256E+13 | 0.399179E+10 | 0.455510E+12 |
Minimum of Months | -0.684689E+10 | 0.846132E+10 | 0.679347E+11 | 0.00 | 0.210849E+11 |
Maximum of Months | 0.632834E+11 | 0.513396E+11 | 0.223834E+12 | 0.134897E+10 | 0.540299E+11 |