Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:29:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1495.23 | 6435.45 | 6435.45 |
Net Site Energy | 1495.23 | 6435.45 | 6435.45 |
Total Source Energy | 2610.86 | 11237.08 | 11237.08 |
Net Source Energy | 2610.86 | 11237.08 | 11237.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 29.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 216.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 51.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 475.29 | 1019.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 29.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.75 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 216.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 29.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 266.15 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 64.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 216.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 51.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 437.79 | 2336.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1365.41 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2045.63 | 4389.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 242.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 437.79 | 2336.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1365.41 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2045.63 | 4389.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 475.288 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 475.288 | 100.00 |
Total On-Site and Utility Electric Sources | 475.288 | 100.00 |
Total Electricity End Uses | 475.288 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3928.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 6.7540 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 10.4679 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.6110 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 6.7540 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 10.4679 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.6110 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.6110 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-16:10 | 21-DEC-20:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 105123.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15349.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12736.87 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3534.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12206.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1593.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34573.63 | 135716.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 105123.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 15349.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1358.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11709.37 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3534.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 12206.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 441.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 958.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 353.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 93.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 85.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 842.91 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 203.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 235.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 161.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1505.24 | 1105.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1520.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 510.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 367.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1012.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 696.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6478.51 | 4758.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1520.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 510.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 400.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 367.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3627.87 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 875.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1012.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 696.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6478.51 | 4758.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.44 |
KITCHEN DIRECT AIR | 1.48 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 2.44 | 1.00 | 1.00 | 2.44 |
PSZ-AC_2:2 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.48 | 1.00 | 1.00 | 1.48 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.44 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.48 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.44 | 2612.34 |
PSZ-AC_2:2_ADDAQ FAN | 1.48 | 1584.47 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.44 | 2.44 | 2.44 | 1.61 | 40412.75 | 61456.30 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.48 | 1.48 | 1.48 | 0.977293 | 29564.42 | 72142.19 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.44 | 1.22 | 1.63 | 40412.75 | 20206.38 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.48 | 0.740373 | 0.987167 | 29564.42 | 14782.21 | 0.776820 | 0.776820 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61456.30 |
PSZ-AC_2:2 HEATING COIL | 72142.19 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 6.754 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.541 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 10.468 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.547 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 784.620 | 6.754 | 8.963 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 784.620 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1216.076 | 10.468 | 193.849 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1216.076 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2550 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.845 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
42 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
43 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
44 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
45 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
46 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
47 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
48 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 | |
49 | 7 | -0.16459679E-08 | -0.32692664E-15 | 0.10422529E-13 | -0.14706702E-15 |
50 | 6 | 0.71279470E-05 | 0.48919389E-08 | 0.31855004E-02 | -0.26722647E-04 |
51 | 5 | -0.51387372E-03 | 0.28990711E-05 | -0.22347621 | 0.19539581E-02 |
52 | 4 | 0.11828338E-01 | 0.13198320E-03 | 4.8254089 | -0.45225216E-01 |
53 | 3 | -0.10389352 | 0.10497736E-02 | -37.998046 | 0.39839544 |
54 | 2 | 0.36893606 | 0.17465704E-02 | 116.43846 | -1.4173309 |
55 | 1 | -0.53252332 | 0.53234446E-03 | -143.88053 | 2.0485998 |
56 | 0 | 0.25963561 | 0.12843692E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.3815_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.3280E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7507E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0864E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5185E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9494E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8807E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5715E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5743E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.5635E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.6142E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.7673E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.8320E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.6854E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6988E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.7032E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7033E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7811E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.3657E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5559E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.1343E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9203E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.9834E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5745E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.5715E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 22440.21562 | 26928.25874 | 2.03445 | 2.44133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 7416.63187 | 8899.95825 | 0.38958 | 0.46750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -17.90000 | 9.55238E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16324.01262 | 19588.81515 | 1.23396 | 1.48075 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1446.85168 | 1736.22201 | 6.78128E-002 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -17.90000 | 9.55238E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 30676.32 | 2.44133 | 2.44133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 24620.50 | 0.46750 | 0.46750 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26577.89 | 1.48075 | 1.48075 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64906.04 | 1.14133 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.44133 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.48075 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44133 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.44133 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.44133 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.44133 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.44133 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.44133 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.48075 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48075 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.48075 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.48075 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.48075 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.48075 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.44133 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.48075 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.44133 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.44133 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2612.34327 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.44133 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.44133 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.44133 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.61128 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.44133 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.22067 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.62755 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40412.75000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20206.37500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40412.75000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61456.29960 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61456.29960 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.48075 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.48075 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1584.46852 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.48075 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.48075 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.48075 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97729 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.48075 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74037 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98717 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29564.42000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14782.21000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77682 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77682 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29564.42000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 72142.18629 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 72142.18629 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 38626.6 | 10.85 | 10.80 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 28493.8 | 11.42 | 11.37 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | N/A | 2.168 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | N/A | 2.168 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | N/A | 2.168 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.255 | 0.240 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.7047594003E-002 | 0.3500173516 | Pass | Pass | 0.2402929021 | 0.5966787416 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1326096303 | 0.6062070181 | Pass | Pass | 5.0329153506E-002 | 0.1942038918 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4381340379 | 0.5192410270 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 572.21 | 159.25 | 859.63 | 11.56 | 516.91 | 2119.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.245 | 0.255 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3815_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.3815_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.168 | 0.401 | 0.402 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 6.7540 | 116.17 | 784.62 | LightsWired | LTG_SCH_DINING | 91.35 | 168.00 | 69.51 | 0.0000 | Y | 10.24 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 10.4679 | 116.17 | 1216.08 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 19.16 |
Interior Lighting Total | 8.6110 | 232.34 | 2000.70 | 29.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 784.62 | 298.16 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.00 | 784.62 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 164.64 | AstronomicalClock | - | 49.26 | 49.26 | 1.52 | |
EXTERIOR_LIGHTS_B | 1845.07 | AstronomicalClock | - | 83.67 | 73.35 | 25.40 | |
Exterior Lighting Total | 2009.71 | 26.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40412.75 | 32356.87 | 8055.88 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29564.42 | 22966.23 | 6598.19 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 38626.6 | 10.85 | 10.80 | ||||
PSZ-AC_2:2 COOLING COIL | 28493.8 | 11.42 | 11.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61456.30 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 72142.19 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.44 | 2612.34 | 1070.05 | 1.00 | 1.29 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.48 | 1584.47 | 1070.05 | 1.00 | 1.36 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 22440.22 | 26928.26 | 231.80 | 2.034 | 2.441 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00729 | 33.90 | 0.00548 | 0.416 | 0.00 |
KITCHEN | 16324.01 | 19588.82 | 168.62 | 1.234 | 1.481 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00869 | 32.57 | 0.00547 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7416.63 | 8899.96 | 76.61 | 0.390 | 0.467 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00785 | -17.90 | 0.00096 | 0.416 | 0.00 |
KITCHEN | 1446.85 | 1736.22 | 14.95 | 0.068 | 1.141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 18.89 | 18.89 | 0.00532 | -17.90 | 0.00096 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.44 | 2.44 | 0.47 | 0.47 | 2.4413 | 2.4413 | 2.4413 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.48 | 1.48 | 1.14 | 1.14 | 1.4807 | 1.4807 | 1.4807 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 40412.750 | 32356.872 | 2.441330 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 20206.38 | 20206.38 | 1.627553 | 25.59 | 13.53 | 0.00697895 | 11.72 | 8.29 | 0.00697895 | 33.90 | 0.00547527 | 15.07 | 25.5633 | 23.89 | 0.00728785 | 32.1227 | 22440.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61456.300 | 61456.300 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 61456.30 | 61456.30 | 2.441334 | 14.37 | 9.07 | 0.00667517 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 17.0422 | 21.11 | 0.00785022 | 40.9281 | 7416.63 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 29564.420 | 22966.233 | 1.480750 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14782.21 | 14782.21 | 0.987167 | 31.07 | 14.74 | 0.00620966 | 11.72 | 7.50 | 0.00620966 | 32.57 | 0.00547322 | 14.64 | 115.6171 | 26.10 | 0.00868607 | 33.4875 | 16324.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 72142.186 | 72142.186 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 72142.19 | 72142.19 | 1.480746 | -9.60 | -9.60 | 0.00219278 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 77.0783 | 18.46 | 0.00635421 | 39.1516 | 486.26 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40412.750 | 32356.872 | 2.441330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8135 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.441334 | 2.38625212 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 20206.38 | 20206.38 | 1.0000 | 1.59083184 | 1.627553 | 25.59 | 13.53 | 0.00697895 | 43503.1 | 11.72 | 8.29 | 0.00697895 | 29387.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20206.38 | 33.90 | 0.00547527 | 15.07 | 0.41605618 | 25.5633 | 23.89 | 0.00728785 | 23.89 | 0.00728785 | 32.1227 | 22440.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61456.300 | 61456.300 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.441334 | 2.38625212 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | Sensible | 61456.30 | 61456.30 | 1.0000 | 2.38625212 | 2.441334 | 14.37 | 9.07 | 0.00667517 | 31312.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61456.30 | -17.90 | 0.00095524 | -17.90 | 0.41605618 | 17.0422 | 21.00 | 0.00785022 | 21.11 | 0.00785022 | 40.9281 | 7416.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29564.420 | 22966.233 | 1.480750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.3834 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.480746 | 1.44733711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14782.21 | 14782.21 | 1.0000 | 0.96489383 | 0.987167 | 31.07 | 14.74 | 0.00620966 | 47113.6 | 11.72 | 7.50 | 0.00620966 | 27444.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14782.21 | 32.57 | 0.00547322 | 14.64 | 1.14133354 | 115.6171 | 26.05 | 0.00868607 | 26.10 | 0.00868607 | 33.4875 | 16324.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 72142.186 | 72142.186 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.480746 | 1.44733711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 72142.19 | 72142.19 | 1.0000 | 1.44733711 | 1.480746 | -9.60 | -9.60 | 0.00219278 | -4205.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 72142.19 | -17.90 | 0.00095524 | -17.90 | 1.14133354 | 77.0783 | 18.29 | 0.00635421 | 18.46 | 0.00635421 | 39.1516 | 486.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.44 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3065.17 | 4701.17 | 1275.83 |
KITCHEN | 4833.00 | 6045.83 | 3881.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4877.50 | 6771.83 | 3928.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 35.17 | 0.83 | 0.17 | 0.00 |
KITCHEN | 0.00 | 112.83 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 35.17 | 113.67 | 0.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.266 | 4.350 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.385 | 0.030 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.104 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.631 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13521322.36 | 0.00 | 13521322.36 | 11048002.87 | 24569325.24 | 13120747.55 | 1455.09 | 5974.70 | 1330.20 | 199.79 |
KITCHEN | 26928596.19 | 0.00 | 26928596.19 | 134202.88 | 27062799.07 | 35993094.65 | 8236.86 | 520.37 | 2.77 | 459.49 |
Total Facility | 40449918.55 | 0.00 | 40449918.55 | 11182205.75 | 51632124.31 | 49113842.20 | 8238.07 | 5974.76 | 1332.15 | 538.32 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5140 | 0.0000 | 0.5140 | 0.4247 | 0.9387 | 0.4161 | 0.00 | 5868.65 | 1318.35 |
KITCHEN | 1.0126 | 0.0000 | 1.0126 | 0.0029 | 1.0155 | 1.1413 | 6677.33 | 508.28 | 1.39 |
Total Facility | 1.5266 | 0.0000 | 1.5266 | 0.4277 | 1.9543 | 1.5574 | 6677.33 | 5868.67 | 1319.05 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12918388.13 | 0.00 | 12918388.13 | 13120747.55 | 7442.60 | 11.50 | 1305.89 | 199.68 |
PSZ-AC_2:2 | 25726937.46 | 0.00 | 25726937.46 | 35993094.65 | 8757.33 | 0.25 | 2.42 | 459.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4911 | 0.0000 | 0.4911 | 0.4161 | 5881.06 | 11.38 | 1294.56 |
PSZ-AC_2:2 | 0.9674 | 0.0000 | 0.9674 | 1.1413 | 7185.62 | 0.18 | 1.19 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 846.71 | 569.63 | 5970.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 165.58 | 1325.03 | 6155.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0778 | 0.6725 | 0.3975 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0346 | 1.0166 | 0.9595 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
Electricity:Building | 303.50 | 2332.77 | 01-JAN-01:10 | 18740.18 | 02-JAN-11:10 |
Electricity:Zone:DINING | 80.66 | 381.62 | 01-JAN-01:10 | 4344.76 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 295.56 | 2196.49 | 01-JAN-01:10 | 15446.13 | 02-JAN-11:10 |
InteriorLights:Electricity | 29.40 | 240.33 | 20-MAY-05:00 | 1609.61 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 10.24 | 82.34 | 20-MAY-05:00 | 661.67 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 29.40 | 240.33 | 20-MAY-05:00 | 1609.61 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 29.40 | 240.33 | 20-MAY-05:00 | 1609.61 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 10.24 | 82.34 | 20-MAY-05:00 | 661.67 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 29.40 | 240.33 | 20-MAY-05:00 | 1609.61 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 222.84 | 1951.15 | 01-JAN-01:10 | 14395.42 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 19.16 | 157.99 | 01-JAN-01:10 | 947.94 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 266.15 | 1928.22 | 01-JAN-01:10 | 14087.95 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.42 | 271.35 | 01-JAN-01:10 | 3934.52 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.75 | 900.72 | 01-JAN-01:10 | 13060.45 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.74 | 1656.87 | 01-JAN-01:10 | 10153.43 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.33 | 629.37 | 01-JAN-01:10 | 9125.93 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 51.09 | 849.94 | 18-MAR-22:30 | 4346.07 | 28-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 43.15 | 764.16 | 23-DEC-23:10 | 2602.18 | 28-JUL-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 14.38 | 0.00 | 01-JAN-11:10 | 1525.94 | 28-JUL-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 28.77 | 683.15 | 06-JAN-01:00 | 1076.23 | 21-APR-03:30 |
ElectricityPurchased:Facility | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
ElectricityPurchased:Plant | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
Cogeneration:ElectricityPurchased | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
General:Cogeneration:ElectricityPurchased | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
ElectricityNet:Plant | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
Cogeneration:ElectricityNet | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
General:Cogeneration:ElectricityNet | 475.29 | 4532.18 | 24-DEC-01:10 | 34573.63 | 26-JUN-16:10 |
Electricity:HVAC | 101.72 | 0.00 | 01-JAN-01:10 | 19605.89 | 26-JUN-17:10 |
Fans:Electricity | 64.26 | 0.00 | 01-JAN-01:10 | 3890.90 | 21-DEC-18:10 |
General:Fans:Electricity | 64.26 | 0.00 | 01-JAN-01:10 | 3890.90 | 21-DEC-18:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 37.46 | 0.00 | 01-JAN-00:10 | 15833.01 | 26-JUN-17:10 |
General:Cooling:Electricity | 37.46 | 0.00 | 01-JAN-00:10 | 15833.01 | 26-JUN-17:10 |
ExteriorLights:Electricity | 26.93 | 0.00 | 01-JAN-07:30 | 2009.71 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 26.93 | 0.00 | 01-JAN-07:30 | 2009.71 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1019.94 | 2560.65 | 01-JAN-01:20 | 135716.94 | 21-DEC-20:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 325.80 | 0.00 | 01-JAN-01:10 | 105833.11 | 21-DEC-18:10 |
Heating:NaturalGas | 325.80 | 0.00 | 01-JAN-01:10 | 105833.11 | 21-DEC-18:10 |
General:Heating:NaturalGas | 325.80 | 0.00 | 01-JAN-01:10 | 105833.11 | 21-DEC-18:10 |
NaturalGas:Plant | 216.98 | 722.00 | 01-JAN-01:20 | 27776.96 | 11-FEB-13:40 |
WaterSystems:NaturalGas | 216.98 | 722.00 | 01-JAN-01:20 | 27776.96 | 11-FEB-13:40 |
Water Heater:WaterSystems:NaturalGas | 216.98 | 722.00 | 01-JAN-01:20 | 27776.96 | 11-FEB-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1077.06 | 2415.74 | 24-DEC-01:10 | 135759.52 | 21-DEC-20:40 |
EnergyTransfer:Building | 458.06 | 1207.87 | 24-DEC-01:10 | 43169.63 | 20-DEC-12:10 |
EnergyTransfer:Zone:KITCHEN | 323.43 | 1207.87 | 24-DEC-01:10 | 23116.00 | 05-MAY-04:10 |
Refrigeration:EnergyTransfer | 136.18 | 2415.74 | 24-DEC-01:10 | 7834.84 | 21-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.09 | 1207.87 | 24-DEC-01:10 | 3917.42 | 21-APR-03:30 |
General:Refrigeration:EnergyTransfer | 68.09 | 1207.87 | 24-DEC-01:10 | 3917.42 | 21-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.09 | 1207.87 | 24-DEC-01:10 | 3917.42 | 21-APR-03:30 |
EnergyTransfer:Plant | 216.22 | 1207.87 | 24-DEC-01:10 | 22559.16 | 18-FEB-14:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.99 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.10 | 1059.46 | 06-JAN-01:00 | 2238.70 | 21-APR-03:30 |
EnergyTransfer:Zone:DINING | 134.63 | 0.00 | 01-JAN-01:10 | 32874.97 | 21-DEC-18:10 |
Heating:EnergyTransfer | 60.89 | 0.00 | 01-JAN-00:10 | 32874.97 | 21-DEC-18:10 |
Heating:EnergyTransfer:Zone:DINING | 60.88 | 0.00 | 01-JAN-00:10 | 32874.97 | 21-DEC-18:10 |
General:Heating:EnergyTransfer | 60.89 | 0.00 | 01-JAN-00:10 | 32874.97 | 21-DEC-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 60.88 | 0.00 | 01-JAN-00:10 | 32874.97 | 21-DEC-18:10 |
Cooling:EnergyTransfer | 329.08 | 0.00 | 01-JAN-01:10 | 33769.83 | 16-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 73.75 | 0.00 | 01-JAN-01:10 | 20344.26 | 26-JUN-17:20 |
General:Cooling:EnergyTransfer | 329.08 | 0.00 | 01-JAN-01:10 | 33769.83 | 16-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 73.75 | 0.00 | 01-JAN-01:10 | 20344.26 | 26-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1223.90 | 20-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1223.90 | 20-DEC-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 255.33 | 0.00 | 01-JAN-01:10 | 19198.58 | 05-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 255.33 | 0.00 | 01-JAN-01:10 | 19198.58 | 05-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
EnergyTransfer:HVAC | 402.78 | 0.00 | 01-JAN-01:10 | 84666.49 | 21-DEC-18:10 |
HeatingCoils:EnergyTransfer | 260.64 | 0.00 | 01-JAN-01:10 | 84666.49 | 21-DEC-18:10 |
CoolingCoils:EnergyTransfer | 142.14 | 0.00 | 01-JAN-00:10 | 54443.04 | 26-JUN-17:10 |
WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 148.14 | 0.00 | 01-JAN-00:10 | 20160.19 | 12-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 60.877 | -73.749 | 0.000 | 0.000 | 71.421 | 10.238 | 52.814 | 34.894 | 0.000 | 7.879 | 0.000 | 0.000 | -14.203 | 0.000 | -128.015 | -22.156 |
KITCHEN | 0.000 | 0.000 | 0.012 | -255.317 | 0.000 | 0.000 | 4.993 | 19.164 | 201.334 | 0.000 | 0.000 | 0.030 | 31.806 | 0.000 | 0.000 | 0.000 | -2.021 | -0.003 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.153 | 10.507 | 0.000 | 0.000 | 0.000 | -13.660 | -0.000 |
Total Facility | 0.000 | 0.000 | 60.890 | -329.067 | 0.000 | 0.000 | 76.413 | 29.402 | 254.148 | 34.894 | 0.000 | 11.062 | 42.313 | 0.000 | -14.203 | 0.000 | -143.696 | -22.159 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 22-DEC-04:08 | 0.00 | 0.00 | 0.00 | -29504.30 | 0.00 | 0.00 | 0.00 | 110.28 | 508.77 | 0.00 | 0.00 | 0.00 | 31361.45 | 0.00 | -1913.22 | 0.00 | -562.99 | 0.00 |
KITCHEN | 05-MAY-03:21 | 0.00 | 0.00 | 0.00 | -51570.77 | 0.00 | 0.00 | 0.00 | 157.99 | 2654.87 | 0.00 | 0.00 | 0.00 | 48910.18 | 0.00 | -0.00 | 0.00 | -152.27 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JUN-04:01 | 0.00 | 0.00 | 0.00 | -63419.13 | 0.00 | 0.00 | 275.14 | 357.70 | 6154.25 | 0.00 | 0.00 | 330.13 | 56844.43 | 0.00 | -492.78 | 0.00 | -49.74 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-FEB-04:41 | 0.00 | 0.00 | 47776.99 | 0.00 | 0.00 | 0.00 | 0.00 | 110.28 | 508.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2229.82 | 0.00 | -454.55 | -45711.67 |
KITCHEN | 20-DEC-05:02 | 0.00 | 0.00 | 9778.05 | 0.00 | 0.00 | 0.00 | 24.14 | 210.66 | 4933.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.93 | -14831.10 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-04:41 | 0.00 | 0.00 | 47776.99 | 0.00 | 0.00 | 0.00 | 0.00 | 268.27 | 3163.65 | 0.00 | 0.00 | 13.99 | 0.00 | 0.00 | -2229.82 | 0.00 | -936.50 | -48056.58 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4413 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4413 | 0.1704 | 1.0000 | Not calculated | 0.4161 | 0.1704 | ||
PSZ-AC_2:2 | 1.4807 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4807 | 0.1022 | 1.0000 | Not calculated | 0.1513 | 0.1022 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4413 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.4413 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1704 | ||
PSZ-AC_2:2 | 1.4807 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4807 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1022 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4413 | 2.4413 | 2.4413 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4807 | 1.4807 | 1.4807 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4413 | 2.4413 | 2.4413 | 2.4413 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4807 | 1.4807 | 1.4807 | 1.4807 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4413 | 2.4413 | 2.4413 | No | 0.4161 | 0.8900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4807 | 1.4807 | 1.4807 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4413 | 2.4413 | 2.4413 | 2.4413 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4807 | 1.4807 | 1.4807 | 1.4807 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 325.80 | 105833.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 37.46 | 15833.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 29.40 | 1609.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 26.93 | 2009.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.75 | 13060.45 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 64.26 | 3890.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 216.98 | 27776.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.38 | 1525.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.77 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 317.24 | 475.29 |
Natural Gas | 477.16 | 1019.94 |
Additional | 0.00 | 0.00 |
Total | 794.40 | 1495.23 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 126.55 |
Space Heating | 0.00 |
Space Cooling | 161.23 |
Fans (All) | 276.56 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1145.52 |
Miscellaneous (All) | 2045.63 |
Subtotal | 2045.63 |
Natural Gas [MJ/m2] | |
Space Heating | 1402.25 |
Service Water Heating | 933.88 |
Miscellaneous (All) | 4389.82 |
Subtotal | 4389.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.97 |
Space Heating | 21.79 |
Space Cooling | 2.51 |
Fans (All) | 4.30 |
Service Water Heating | 14.51 |
Receptacle Equipment | 49.71 |
Miscellaneous | 5.22 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4763. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1442. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8135.67 | 624.17 | 0.17 | 0.00 | 0.00 |
ATTIC | 6765.33 | 605.67 | 571.00 | 804.50 | 13.50 |
Min | 6765.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 624.17 | 571.00 | 804.50 | 13.50 |
Average | 7887.00 | 409.94 | 190.39 | 268.17 | 4.50 |
Sum | 23661.00 | 1229.83 | 571.17 | 804.50 | 13.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8682.00 | 78.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8014.00 | 746.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7009.50 | 837.00 | 317.50 | 283.67 | 312.33 |
Min | 7009.50 | 78.00 | 0.00 | 0.00 | 0.00 |
Max | 8682.00 | 837.00 | 317.50 | 283.67 | 312.33 |
Average | 7901.83 | 553.67 | 105.83 | 94.56 | 104.11 |
Sum | 23705.50 | 1661.00 | 317.50 | 283.67 | 312.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 253809.33 | 915.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15355.00 | 903.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253809.33 | 915.67 | 0.00 | 0.00 | 0.00 |
Average | 89721.44 | 606.22 | 0.00 | 0.00 | 0.00 |
Sum | 269164.33 | 1818.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:29:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137404E+10 | 20487.35 | 14-JAN-04:54 | -17.0 | -17.0 | 0.450505E+10 | 4414.15 | 20-JAN-12:00 | 21.00 | 6.97 |
February | 0.112765E+10 | 26645.11 | 12-FEB-04:51 | -20.0 | -20.0 | 0.405810E+10 | 3954.04 | 27-FEB-12:09 | 14.00 | 4.76 |
March | 0.230176E+10 | 9882.84 | 05-MAR-04:56 | -12.0 | -12.0 | 0.465313E+10 | 4414.12 | 13-MAR-11:00 | 21.00 | 6.17 |
April | 0.205650E+10 | 10914.54 | 17-APR-04:02 | -8.0 | -8.7 | 0.449855E+10 | 4414.12 | 20-APR-11:09 | 20.00 | 8.69 |
May | 0.542174E+10 | 11457.12 | 17-MAY-12:55 | 29.00 | 11.92 | 0.498151E+10 | 4681.82 | 06-MAY-18:19 | 29.00 | 11.92 |
June | 0.138356E+11 | 20345.44 | 26-JUN-17:12 | 37.70 | 15.21 | 0.525787E+10 | 4682.42 | 17-JUN-18:00 | 37.70 | 15.21 |
July | 0.143670E+11 | 21359.61 | 11-JUL-04:01 | 18.00 | 10.47 | 0.538879E+10 | 4681.99 | 22-JUL-18:00 | 27.00 | 15.92 |
August | 0.143038E+11 | 22074.87 | 17-AUG-04:01 | 12.83 | 5.22 | 0.543218E+10 | 4682.28 | 05-AUG-18:30 | 12.83 | 5.22 |
September | 0.113036E+11 | 21332.94 | 01-SEP-04:01 | 11.28 | 10.55 | 0.511435E+10 | 4682.02 | 02-SEP-18:00 | 24.40 | 13.61 |
October | 0.404479E+10 | 12667.00 | 30-OCT-04:02 | -10.0 | -10.0 | 0.471360E+10 | 4681.72 | 07-OCT-18:30 | -10.0 | -10.0 |
November | 0.207581E+10 | 13441.80 | 30-NOV-04:11 | -13.7 | -14.2 | 0.439663E+10 | 4414.13 | 07-NOV-12:50 | -13.7 | -14.2 |
December | 0.153754E+10 | 29504.78 | 22-DEC-04:08 | -21.8 | -21.8 | 0.451059E+10 | 4414.12 | 04-DEC-12:00 | -21.8 | -21.8 |
Annual Sum or Average | 0.737499E+11 | 0.575103E+11 | ||||||||
Minimum of Months | 0.112765E+10 | 9882.84 | -21.8 | -21.8 | 0.405810E+10 | 3954.04 | -21.8 | -21.8 | ||
Maximum of Months | 0.143670E+11 | 29504.78 | 37.70 | 15.21 | 0.543218E+10 | 4682.42 | 37.70 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202319E+11 | 35362.84 | 14-JAN-05:01 | -16.5 | -16.5 | 0.770189E+10 | 5138.40 | 20-JAN-11:00 | 20.00 | 7.55 |
February | 0.178522E+11 | 31907.03 | 12-FEB-00:01 | -17.2 | -17.2 | 0.695210E+10 | 5119.28 | 18-FEB-11:00 | 18.00 | 6.83 |
March | 0.202013E+11 | 31429.30 | 14-MAR-03:42 | 7.17 | 1.10 | 0.773117E+10 | 5138.40 | 14-MAR-10:30 | 21.00 | 7.05 |
April | 0.201109E+11 | 47410.70 | 21-APR-03:21 | 8.00 | 5.64 | 0.748766E+10 | 5138.40 | 27-APR-10:00 | 18.00 | 8.14 |
May | 0.212123E+11 | 51560.19 | 05-MAY-03:21 | 6.00 | 3.35 | 0.781351E+10 | 5138.44 | 24-MAY-10:00 | 21.00 | 12.14 |
June | 0.225884E+11 | 45353.49 | 27-JUN-03:21 | 17.70 | 7.53 | 0.760991E+10 | 5138.44 | 02-JUN-10:39 | 17.70 | 7.53 |
July | 0.234003E+11 | 40625.58 | 11-JUL-04:01 | 18.00 | 10.47 | 0.785991E+10 | 5138.45 | 28-JUL-10:39 | 19.67 | 16.52 |
August | 0.236890E+11 | 38775.17 | 11-AUG-04:01 | 16.00 | 11.62 | 0.786343E+10 | 5138.44 | 28-AUG-10:39 | 20.67 | 15.18 |
September | 0.226861E+11 | 51020.79 | 15-SEP-03:11 | 10.13 | 4.71 | 0.759338E+10 | 5138.42 | 01-SEP-10:09 | 10.13 | 4.71 |
October | 0.223226E+11 | 47075.21 | 06-OCT-04:01 | 6.83 | 2.84 | 0.775419E+10 | 5138.40 | 05-OCT-10:00 | 6.83 | 2.84 |
November | 0.209024E+11 | 31703.61 | 30-NOV-05:01 | -12.8 | -13.4 | 0.746394E+10 | 5138.40 | 09-NOV-11:00 | -12.8 | -13.4 |
December | 0.201295E+11 | 39722.87 | 22-DEC-05:01 | -21.0 | -21.0 | 0.770260E+10 | 5138.40 | 04-DEC-11:00 | -21.0 | -21.0 |
Annual Sum or Average | 0.255327E+12 | 0.915337E+11 | ||||||||
Minimum of Months | 0.178522E+11 | 31429.30 | -21.0 | -21.0 | 0.695210E+10 | 5119.28 | -21.0 | -21.0 | ||
Maximum of Months | 0.236890E+11 | 51560.19 | 18.00 | 11.62 | 0.786343E+10 | 5138.45 | 21.00 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 | -1.8 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 | 2.10 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 | 4.75 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 | 11.26 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 | 10.91 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 | 15.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 | 10.64 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 | 8.03 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 | -5.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.5 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.00 | 0.00 | 22.27 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104739E+11 | 44622.56 | 14-JAN-05:01 | -16.5 |
February | 0.106578E+11 | 47767.38 | 12-FEB-04:41 | -19.8 |
March | 0.739507E+10 | 28944.65 | 19-MAR-04:01 | -8.7 |
April | 0.574559E+10 | 29538.27 | 17-APR-04:01 | -8.0 |
May | 0.543756E+09 | 13011.05 | 02-MAY-04:01 | 2.00 |
June | 200754.99 | 682.50 | 14-JUN-04:05 | 21.83 |
July | 315274.30 | 733.21 | 18-JUL-04:02 | 21.00 |
August | 8489.37 | 99.04 | 02-AUG-23:01 | 22.83 |
September | 0.251017E+09 | 9419.65 | 21-SEP-20:00 | 0.00 |
October | 0.475021E+10 | 37212.84 | 30-OCT-04:01 | -10.0 |
November | 0.754738E+10 | 39161.58 | 29-NOV-05:01 | -10.0 |
December | 0.135125E+11 | 46807.43 | 21-DEC-04:01 | -18.8 |
Annual Sum or Average | 0.608777E+11 | |||
Minimum of Months | 8489.37 | 99.04 | -19.8 | |
Maximum of Months | 0.135125E+11 | 47767.38 | 22.83 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1774481.89 | 8616.59 | 05-JAN-05:02 | -17.0 |
February | 3002616.82 | 7566.85 | 12-FEB-05:03 | -19.8 |
March | 1258252.99 | 5835.97 | 04-MAR-05:03 | -6.9 |
April | 1146054.77 | 6186.57 | 16-APR-04:03 | -5.0 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 340692.66 | 4649.19 | 30-OCT-04:03 | -10.0 |
November | 1158515.43 | 6889.28 | 27-NOV-05:03 | -7.0 |
December | 3760087.54 | 9791.21 | 20-DEC-05:02 | -19.0 |
Annual Sum or Average | 12440702.11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 3760087.54 | 9791.21 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.922160E+09 | 661.67 | 02-JAN-16:30 | 0.598074E+10 | 3934.52 | 01-JAN-11:09 |
February | 0.815944E+09 | 661.67 | 01-FEB-17:19 | 0.540196E+10 | 3934.52 | 01-FEB-11:09 |
March | 0.879026E+09 | 661.67 | 01-MAR-17:30 | 0.598074E+10 | 3934.52 | 01-MAR-11:09 |
April | 0.819281E+09 | 661.67 | 01-APR-17:49 | 0.578781E+10 | 3934.52 | 01-APR-10:09 |
May | 0.824727E+09 | 661.67 | 01-MAY-18:49 | 0.598074E+10 | 3934.52 | 01-MAY-10:09 |
June | 0.791806E+09 | 661.67 | 01-JUN-19:19 | 0.578781E+10 | 3934.52 | 01-JUN-10:09 |
July | 0.810345E+09 | 661.67 | 01-JUL-19:30 | 0.598074E+10 | 3934.52 | 01-JUL-10:09 |
August | 0.846479E+09 | 661.67 | 01-AUG-18:49 | 0.598074E+10 | 3934.52 | 01-AUG-10:09 |
September | 0.826731E+09 | 661.67 | 01-SEP-18:30 | 0.578781E+10 | 3934.52 | 01-SEP-10:09 |
October | 0.884844E+09 | 661.67 | 02-OCT-17:10 | 0.598074E+10 | 3934.52 | 01-OCT-10:09 |
November | 0.888559E+09 | 661.67 | 01-NOV-16:40 | 0.578781E+10 | 3934.52 | 01-NOV-10:09 |
December | 0.928361E+09 | 661.67 | 01-DEC-16:19 | 0.598074E+10 | 3934.52 | 01-DEC-11:09 |
Annual Sum or Average | 0.102383E+11 | 0.704184E+11 | ||||
Minimum of Months | 0.791806E+09 | 661.67 | 0.540196E+10 | 3934.52 | ||
Maximum of Months | 0.928361E+09 | 661.67 | 0.598074E+10 | 3934.52 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161928E+10 | 947.94 | 02-JAN-10:09 | 0.166241E+11 | 10153.43 | 01-JAN-11:09 |
February | 0.146666E+10 | 947.94 | 01-FEB-10:09 | 0.150153E+11 | 10153.43 | 01-FEB-11:09 |
March | 0.164506E+10 | 947.94 | 01-MAR-10:09 | 0.166241E+11 | 10153.43 | 01-MAR-11:09 |
April | 0.157340E+10 | 947.94 | 01-APR-16:10 | 0.160878E+11 | 10153.43 | 01-APR-10:09 |
May | 0.163217E+10 | 947.94 | 01-MAY-09:09 | 0.166241E+11 | 10153.43 | 01-MAY-10:09 |
June | 0.159008E+10 | 947.94 | 01-JUN-09:09 | 0.160878E+11 | 10153.43 | 01-JUN-10:09 |
July | 0.161568E+10 | 947.94 | 01-JUL-16:10 | 0.166241E+11 | 10153.43 | 01-JUL-10:09 |
August | 0.164506E+10 | 947.94 | 01-AUG-09:09 | 0.166241E+11 | 10153.43 | 01-AUG-10:09 |
September | 0.157378E+10 | 947.94 | 01-SEP-09:09 | 0.160878E+11 | 10153.43 | 01-SEP-10:09 |
October | 0.161909E+10 | 947.94 | 02-OCT-09:09 | 0.166241E+11 | 10153.43 | 01-OCT-10:09 |
November | 0.156752E+10 | 947.94 | 01-NOV-09:09 | 0.160878E+11 | 10153.43 | 01-NOV-10:09 |
December | 0.161587E+10 | 947.94 | 01-DEC-10:09 | 0.166241E+11 | 10153.43 | 01-DEC-11:09 |
Annual Sum or Average | 0.191636E+11 | 0.195735E+12 | ||||
Minimum of Months | 0.146666E+10 | 947.94 | 0.150153E+11 | 10153.43 | ||
Maximum of Months | 0.164506E+10 | 947.94 | 0.166241E+11 | 10153.43 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.922160E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183936E+11 |
February | 0.852256E+10 | 0.815944E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176010E+11 |
March | 0.954557E+10 | 0.879026E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43057.85 | 0.147101E+11 |
April | 0.915225E+10 | 0.819281E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127877E+11 |
May | 0.947560E+10 | 0.824727E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131920E+09 | 0.644040E+10 |
June | 0.922788E+10 | 0.791806E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234223E+10 | 0.163208E+10 |
July | 0.939996E+10 | 0.810345E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243587E+10 | 0.151813E+10 |
August | 0.954557E+10 | 0.846479E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202029E+10 | 0.197023E+10 |
September | 0.915225E+10 | 0.826731E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930650E+09 | 0.360793E+10 |
October | 0.940563E+10 | 0.884844E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18241603.76 | 0.125892E+11 |
November | 0.909363E+10 | 0.888559E+09 | 0.578781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158244E+11 |
December | 0.939996E+10 | 0.928361E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209404E+11 |
Annual Sum or Average | 0.111326E+12 | 0.102383E+11 | 0.704184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787924E+10 | 0.128015E+12 |
Minimum of Months | 0.852256E+10 | 0.791806E+09 | 0.540196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151813E+10 |
Maximum of Months | 0.954557E+10 | 0.928361E+09 | 0.598074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243587E+10 | 0.209404E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.161928E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141531E+09 |
February | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215239E+09 |
March | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245608E+09 |
April | 0.655836E+09 | 0.157340E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245273E+09 |
May | 0.679007E+09 | 0.163217E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 246235.35 | 0.154569E+09 |
June | 0.661256E+09 | 0.159008E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9923094.60 | 82924609.77 |
July | 0.673587E+09 | 0.161568E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493136.08 | 83046443.15 |
August | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6752265.59 | 82020846.93 |
September | 0.655836E+09 | 0.157378E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2569771.07 | 0.113861E+09 |
October | 0.673993E+09 | 0.161909E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9310.05 | 0.181158E+09 |
November | 0.651635E+09 | 0.156752E+10 | 0.120605E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169642E+09 |
December | 0.673587E+09 | 0.161587E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306454E+09 |
Annual Sum or Average | 0.797748E+10 | 0.191636E+11 | 0.146736E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 29993812.74 | 0.202133E+10 |
Minimum of Months | 0.610713E+09 | 0.146666E+10 | 0.112564E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82020846.93 |
Maximum of Months | 0.684021E+09 | 0.164506E+10 | 0.124625E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493136.08 | 0.306454E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353809E+09 | 0.747505E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282601E+09 | 0.901337E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258795E+09 | 0.115798E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176162E+09 | 0.119363E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180660E+09 | 0.150221E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217923E+09 | 0.164216E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197493E+09 | 0.147882E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222726E+09 | 0.151873E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299727E+09 | 0.115548E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306953E+09 | 0.975357E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300019E+09 | 0.801107E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356028E+09 | 0.585254E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315290E+10 | 0.136596E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176162E+09 | 0.585254E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356028E+09 | 0.164216E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 661.67 | 02-JAN-16:30 | 3934.52 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 33678.02 | 05-JAN-19:00 |
February | 9454.80 | 04-FEB-19:10 | 661.67 | 01-FEB-17:19 | 3934.52 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 32504.19 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 661.67 | 01-MAR-17:30 | 3934.52 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.76 | 14-MAR-13:00 | 27888.10 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 661.67 | 01-APR-17:49 | 3934.52 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 18716.44 | 15-APR-18:53 |
May | 9454.80 | 06-MAY-18:10 | 661.67 | 01-MAY-18:49 | 3934.52 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3312.10 | 17-MAY-13:00 | 12667.94 | 11-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 661.67 | 01-JUN-19:19 | 3934.52 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9758.55 | 26-JUN-17:03 | 5842.45 | 02-JUN-19:55 |
July | 9454.80 | 01-JUL-18:10 | 661.67 | 01-JUL-19:30 | 3934.52 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8635.73 | 17-JUL-11:55 | 5922.52 | 05-JUL-19:53 |
August | 9454.80 | 05-AUG-18:10 | 661.67 | 01-AUG-18:49 | 3934.52 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8364.44 | 16-AUG-17:03 | 6619.81 | 12-AUG-18:53 |
September | 9454.80 | 02-SEP-18:10 | 661.67 | 01-SEP-18:30 | 3934.52 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4669.17 | 08-SEP-12:55 | 16915.51 | 21-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 661.67 | 02-OCT-17:10 | 3934.52 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.07 | 11-OCT-13:00 | 23915.67 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 661.67 | 01-NOV-16:40 | 3934.52 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 30118.72 | 29-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 661.67 | 01-DEC-16:19 | 3934.52 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 37030.12 | 21-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5842.45 | |||||
Maximum of Months | 9454.80 | 661.67 | 3934.52 | 0.00 | 0.00 | 0.00 | 0.00 | 9758.55 | 37030.12 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 947.94 | 02-JAN-10:09 | 7415.65 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 558.79 | 13-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 947.94 | 01-FEB-10:09 | 7415.65 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 540.52 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 947.94 | 01-MAR-10:09 | 7415.65 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1147.93 | 19-MAR-01:55 |
April | 677.52 | 01-APR-18:10 | 947.94 | 01-APR-16:10 | 7415.65 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 773.94 | 10-APR-04:00 |
May | 677.52 | 06-MAY-18:10 | 947.94 | 01-MAY-09:09 | 7415.65 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 10.16 | 17-MAY-13:00 | 514.18 | 03-MAY-03:10 |
June | 677.52 | 03-JUN-18:10 | 947.94 | 01-JUN-09:09 | 7415.65 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 54.84 | 14-JUN-12:00 | 333.27 | 09-JUN-01:30 |
July | 677.52 | 01-JUL-18:10 | 947.94 | 01-JUL-16:10 | 7415.65 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 48.47 | 16-JUL-12:00 | 381.05 | 03-JUL-03:10 |
August | 677.52 | 05-AUG-18:10 | 947.94 | 01-AUG-09:09 | 7415.65 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.08 | 02-AUG-15:43 | 366.70 | 16-AUG-01:30 |
September | 677.52 | 02-SEP-18:10 | 947.94 | 01-SEP-09:09 | 7415.65 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.33 | 09-SEP-14:52 | 356.22 | 02-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 947.94 | 02-OCT-09:09 | 7415.65 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 2.83 | 11-OCT-14:00 | 495.43 | 29-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 947.94 | 01-NOV-09:09 | 7415.65 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 790.78 | 01-NOV-04:00 |
December | 677.52 | 02-DEC-19:10 | 947.94 | 01-DEC-10:09 | 7415.65 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 774.42 | 24-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 333.27 | ||||||
Maximum of Months | 677.52 | 947.94 | 7415.65 | 7998.14 | 0.00 | 0.00 | 0.00 | 54.84 | 1147.93 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.92 | 08-JAN-03:53 | 1662.19 | 16-JAN-12:40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.84 | 07-FEB-07:55 | 1979.97 | 12-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.28 | 23-MAR-06:53 | 2226.77 | 26-MAR-11:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.52 | 07-APR-03:55 | 2452.23 | 24-APR-12:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.61 | 13-MAY-05:23 | 2292.79 | 09-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.08 | 06-JUN-22:00 | 2168.66 | 22-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.27 | 01-JUL-05:23 | 2234.93 | 03-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.83 | 15-AUG-03:00 | 2144.67 | 13-AUG-11:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.71 | 28-SEP-06:42 | 1930.29 | 20-SEP-12:30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.32 | 14-OCT-07:12 | 1928.15 | 04-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.29 | 30-NOV-07:53 | 1814.34 | 12-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.30 | 23-DEC-08:41 | 1511.07 | 21-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.27 | 1511.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.92 | 2452.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20487.35 | 14-JAN-04:54 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.71 |
February | 26645.11 | 12-FEB-04:51 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.63 |
March | 9882.84 | 05-MAR-04:56 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.25 |
April | 10914.54 | 17-APR-04:02 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.00 |
May | 11457.12 | 17-MAY-12:55 | 14707.47 | 820.47 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 3312.09 | 0.00 |
June | 20345.44 | 26-JUN-17:12 | 33617.07 | 1640.94 | 13024.62 | 0.00 | 0.00 | 0.00 | 0.00 | 9756.16 | 0.00 |
July | 21359.61 | 11-JUL-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.08 |
August | 22074.87 | 17-AUG-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 |
September | 21332.94 | 01-SEP-04:01 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 |
October | 12667.00 | 30-OCT-04:02 | 5252.67 | 1470.38 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.70 |
November | 13441.80 | 30-NOV-04:11 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.59 |
December | 29504.78 | 22-DEC-04:08 | 0.00 | 1102.78 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9882.84 | 0.00 | 820.47 | 6783.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29504.78 | 33617.07 | 1640.94 | 16280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9756.16 | 562.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35362.84 | 14-JAN-05:01 | 0.00 | 1579.93 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 36.84 |
February | 31907.03 | 12-FEB-00:01 | 376.40 | 2106.61 | 16883.43 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.02 |
March | 31429.30 | 14-MAR-03:42 | 0.00 | 947.96 | 12773.43 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 244.55 |
April | 47410.70 | 21-APR-03:21 | 0.00 | 1421.93 | 19160.15 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 181.91 |
May | 51560.19 | 05-MAY-03:21 | 0.00 | 1421.93 | 19160.15 | 12410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 152.27 |
June | 45353.49 | 27-JUN-03:21 | 0.00 | 1579.93 | 21289.05 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 124.16 |
July | 40625.58 | 11-JUL-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 |
August | 38775.17 | 11-AUG-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.65 |
September | 51020.79 | 15-SEP-03:11 | 0.00 | 1579.93 | 21289.05 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 153.33 |
October | 47075.21 | 06-OCT-04:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 |
November | 31703.61 | 30-NOV-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 94.84 |
December | 39722.87 | 22-DEC-05:01 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 45.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 31429.30 | 0.00 | 947.96 | 12773.43 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | |
Maximum of Months | 51560.19 | 376.40 | 2106.61 | 36708.73 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 244.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.30 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.36 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.83 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.54 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.98 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.37 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.41 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.47 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.45 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.76 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.91 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.378497E+11 | 22995.38 | 05-JAN-11:09 | 0.116871E+12 | 132639.37 | 05-JAN-13:09 |
February | 0.340671E+11 | 22432.62 | 01-FEB-11:09 | 0.112920E+12 | 116595.78 | 12-FEB-07:10 |
March | 0.373713E+11 | 23569.55 | 14-MAR-10:20 | 0.997385E+11 | 105753.14 | 04-MAR-13:09 |
April | 0.356966E+11 | 22541.90 | 19-APR-10:00 | 0.879456E+11 | 88629.24 | 17-APR-03:30 |
May | 0.382267E+11 | 27670.05 | 17-MAY-10:20 | 0.633543E+11 | 57378.74 | 02-MAY-10:50 |
June | 0.449592E+11 | 34573.63 | 26-JUN-16:10 | 0.561087E+11 | 49290.34 | 01-JUN-12:39 |
July | 0.469174E+11 | 34457.79 | 17-JUL-11:09 | 0.572539E+11 | 48689.63 | 01-JUL-12:00 |
August | 0.460103E+11 | 34458.10 | 16-AUG-11:09 | 0.570673E+11 | 48323.21 | 29-AUG-12:20 |
September | 0.416915E+11 | 30476.00 | 09-SEP-10:00 | 0.570019E+11 | 54342.02 | 22-SEP-06:19 |
October | 0.378225E+11 | 26142.69 | 11-OCT-10:20 | 0.838974E+11 | 103540.93 | 30-OCT-12:50 |
November | 0.365267E+11 | 23047.20 | 09-NOV-11:20 | 0.984751E+11 | 110766.53 | 29-NOV-20:00 |
December | 0.381491E+11 | 23068.10 | 20-DEC-11:09 | 0.129310E+12 | 135716.94 | 21-DEC-20:10 |
Annual Sum or Average | 0.475288E+12 | 0.101994E+13 | ||||
Minimum of Months | 0.340671E+11 | 22432.62 | 0.561087E+11 | 48323.21 | ||
Maximum of Months | 0.469174E+11 | 34573.63 | 0.129310E+12 | 135716.94 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.254144E+10 | 0.284173E+10 | 0.226048E+11 | 0.00 | 0.579156E+10 | 0.79 | 0.00 | 30669755.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228260E+10 | 0.236804E+10 | 0.204173E+11 | 0.00 | 0.536821E+10 | 0.72 | 0.00 | 10199546.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252409E+10 | 0.234131E+10 | 0.226048E+11 | 0.00 | 0.554985E+10 | 0.80 | 0.00 | 0.220430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.239268E+10 | 0.198164E+10 | 0.218757E+11 | 0.00 | 0.523778E+10 | 0.77 | 0.00 | 0.171310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245690E+10 | 0.182093E+10 | 0.226048E+11 | 0.00 | 0.502161E+10 | 0.80 | 0.00 | 0.183337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238189E+10 | 0.165144E+10 | 0.218757E+11 | 0.00 | 0.509258E+10 | 0.77 | 0.00 | 0.938197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242602E+10 | 0.174625E+10 | 0.226048E+11 | 0.00 | 0.527122E+10 | 0.79 | 0.00 | 0.101364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249154E+10 | 0.193857E+10 | 0.226048E+11 | 0.00 | 0.522394E+10 | 0.80 | 0.00 | 0.901382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240051E+10 | 0.214202E+10 | 0.218757E+11 | 0.00 | 0.494159E+10 | 0.77 | 0.00 | 0.584184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250393E+10 | 0.250651E+10 | 0.226048E+11 | 0.00 | 0.534364E+10 | 0.79 | 0.00 | 0.608231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245608E+10 | 0.267620E+10 | 0.218757E+11 | 0.00 | 0.540983E+10 | 0.77 | 0.00 | 0.146869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254423E+10 | 0.291167E+10 | 0.226048E+11 | 0.00 | 0.600447E+10 | 0.79 | 0.00 | 65612785.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294019E+11 | 0.269263E+11 | 0.266154E+12 | 0.00 | 0.642563E+11 | 9.37 | 0.00 | 0.374607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.228260E+10 | 0.165144E+10 | 0.204173E+11 | 0.00 | 0.494159E+10 | 0.72 | 0.00 | 10199546.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254423E+10 | 0.291167E+10 | 0.226048E+11 | 0.00 | 0.600447E+10 | 0.80 | 0.00 | 0.101364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.562287E+11 | 0.00 | 0.201165E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.579485E+11 | 0.00 | 0.183678E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.391297E+11 | 0.00 | 0.200831E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.299931E+11 | 0.00 | 0.187340E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.443990E+10 | 0.00 | 0.183887E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 29549825.34 | 0.00 | 0.168607E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 11324084.45 | 0.00 | 0.167168E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 8868019.40 | 0.00 | 0.165327E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.154740E+10 | 0.00 | 0.162360E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.258065E+11 | 0.00 | 0.175652E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.413118E+11 | 0.00 | 0.179448E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.693486E+11 | 0.00 | 0.194353E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.325804E+12 | 0.00 | 0.216982E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 8868019.40 | 0.00 | 0.162360E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.693486E+11 | 0.00 | 0.201165E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1609.61 | 02-JAN-16:30 | 2009.71 | 01-JAN-00:10 | 14087.95 | 01-JAN-11:09 | 0.00 | 3737.25 | 05-JAN-18:00 | 0.00 | 12-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 1609.61 | 01-FEB-17:19 | 2009.71 | 01-FEB-00:10 | 14087.95 | 01-FEB-11:09 | 0.00 | 3646.64 | 12-FEB-07:10 | 0.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 |
March | 1609.61 | 01-MAR-17:30 | 2009.71 | 01-MAR-00:10 | 14087.95 | 01-MAR-11:09 | 0.00 | 3468.54 | 19-MAR-06:00 | 0.00 | 05-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 1609.61 | 01-APR-17:49 | 2009.71 | 01-APR-05:10 | 14087.95 | 01-APR-10:09 | 0.00 | 3078.01 | 17-APR-06:10 | 0.00 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 1609.61 | 01-MAY-18:49 | 2009.71 | 01-MAY-18:49 | 14087.95 | 01-MAY-10:09 | 0.00 | 2696.92 | 02-MAY-06:10 | 0.00 | 02-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1609.61 | 01-JUN-19:19 | 2009.71 | 01-JUN-19:19 | 14087.95 | 01-JUN-10:09 | 0.00 | 3772.88 | 26-JUN-17:10 | 0.00 | 13-JUN-06:40 | 0.00 | 01-JUN-00:10 |
July | 1609.61 | 01-JUL-19:30 | 2009.71 | 01-JUL-19:30 | 14087.95 | 01-JUL-10:09 | 0.00 | 3438.06 | 17-JUL-11:09 | 0.00 | 03-JUL-08:30 | 0.00 | 01-JUL-00:10 |
August | 1609.61 | 01-AUG-18:49 | 2009.71 | 01-AUG-19:10 | 14087.95 | 01-AUG-10:09 | 0.00 | 3489.94 | 16-AUG-12:00 | 0.00 | 04-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 1609.61 | 01-SEP-18:30 | 2009.71 | 01-SEP-05:10 | 14087.95 | 01-SEP-10:09 | 0.00 | 2722.65 | 22-SEP-06:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1609.61 | 02-OCT-17:10 | 2009.71 | 01-OCT-05:10 | 14087.95 | 01-OCT-10:09 | 0.00 | 3207.80 | 31-OCT-19:10 | 0.00 | 04-OCT-07:49 | 0.00 | 01-OCT-00:10 |
November | 1609.61 | 01-NOV-16:40 | 2009.71 | 01-NOV-05:10 | 14087.95 | 01-NOV-10:09 | 0.00 | 3527.94 | 29-NOV-20:00 | 0.00 | 04-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 1609.61 | 01-DEC-16:19 | 2009.71 | 01-DEC-00:10 | 14087.95 | 01-DEC-11:09 | 0.00 | 3890.90 | 21-DEC-18:10 | 0.00 | 21-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 2696.92 | 0.00 | 0.00 | ||||||
Maximum of Months | 1609.61 | 2009.71 | 14087.95 | 0.00 | 3890.90 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 2428.95 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1358.31 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4966.73 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3478.97 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7598.18 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15833.01 | 26-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14068.60 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14316.40 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10659.24 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6588.47 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3701.39 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2911.95 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1358.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15833.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22995.38 | 05-JAN-11:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3429.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22432.62 | 01-FEB-11:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2853.87 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23569.55 | 14-MAR-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 1646.37 | 0.00 |
April | 22541.90 | 19-APR-10:00 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 2396.22 | 0.00 |
May | 27670.05 | 17-MAY-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 5739.69 | 0.00 |
June | 34573.63 | 26-JUN-16:10 | 1358.18 | 12736.87 | 0.00 | 0.00 | 3534.99 | 0.00 | 0.00 | 15349.62 | 0.00 |
July | 34457.79 | 17-JUL-11:09 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3438.06 | 0.00 | 0.00 | 13954.82 | 0.00 |
August | 34458.10 | 16-AUG-11:09 | 1358.18 | 13187.23 | 0.00 | 0.00 | 3451.50 | 0.00 | 0.00 | 13948.63 | 0.00 |
September | 30476.00 | 09-SEP-10:00 | 1207.27 | 14087.95 | 0.00 | 0.00 | 2709.35 | 0.00 | 0.00 | 9964.43 | 0.00 |
October | 26142.69 | 11-OCT-10:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 4219.51 | 0.00 |
November | 23047.20 | 09-NOV-11:20 | 1358.18 | 14087.95 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 1113.48 | 0.00 |
December | 23068.10 | 20-DEC-11:09 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3502.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 22432.62 | 1207.27 | 12736.87 | 0.00 | 0.00 | 2182.36 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34573.63 | 1358.18 | 14087.95 | 0.00 | 0.00 | 3534.99 | 0.00 | 0.00 | 15349.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 96548.28 | 05-JAN-18:00 | 0.00 | 27749.60 | 31-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 94715.10 | 12-FEB-07:10 | 0.00 | 27776.96 | 11-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 82833.11 | 19-MAR-06:00 | 0.00 | 27739.03 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 76820.37 | 03-APR-03:20 | 0.00 | 27464.46 | 01-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 32003.72 | 02-MAY-06:10 | 0.00 | 26967.14 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 3895.09 | 09-JUN-06:10 | 0.00 | 26307.19 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 1887.41 | 03-JUL-06:30 | 0.00 | 25706.48 | 01-JUL-12:00 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 2264.46 | 13-AUG-06:10 | 0.00 | 25340.06 | 29-AUG-12:20 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 33473.85 | 22-SEP-06:10 | 0.00 | 25743.45 | 30-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 76820.37 | 30-OCT-03:09 | 0.00 | 26396.10 | 31-OCT-12:39 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 82858.60 | 29-NOV-20:00 | 0.00 | 27011.26 | 30-NOV-13:20 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 105833.11 | 21-DEC-18:10 | 0.00 | 27500.75 | 31-DEC-13:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1887.41 | 0.00 | 25340.06 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 105833.11 | 0.00 | 27776.96 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
February | 10.67 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
March | 6.17 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
April | 2.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
October | 1.83 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
November | 3.50 | 18.35 | 0.17 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
December | 6.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 35.17 | 18.21 | 0.17 | 18.22 | 0.83 | 18.40 | 0.00 | 18.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 18.47 | 0.17 | 18.47 | 0.33 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.48 | 0.00 | 28.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.39 | 0.00 | 28.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 29.23 | 0.00 | 29.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 29.50 | 0.00 | 29.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 29.71 | 0.00 | 29.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 30.77 | 0.00 | 30.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 30.85 | 0.00 | 30.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 30.91 | 0.00 | 30.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 30.69 | 0.00 | 30.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 29.55 | 0.00 | 29.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.99 | 0.00 | 28.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.52 | 0.00 | 28.52 |
Annual Sum or Average | 0.00 | 0.00 | 112.83 | 30.64 | 0.00 | 30.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.39 | 0.00 | 28.39 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 30.91 | 0.00 | 30.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 592.83 | 20.96 | 166.67 | 20.81 | 166.67 | 20.72 |
February | 539.50 | 20.92 | 201.17 | 20.80 | 201.17 | 20.73 |
March | 548.67 | 21.03 | 161.67 | 20.89 | 161.67 | 20.80 |
April | 528.00 | 21.09 | 129.00 | 20.96 | 127.00 | 20.87 |
May | 395.67 | 21.51 | 106.00 | 21.88 | 16.83 | 21.82 |
June | 100.17 | 23.10 | 468.33 | 23.75 | 51.67 | 23.74 |
July | 137.50 | 23.47 | 514.83 | 23.80 | 107.50 | 23.80 |
August | 94.67 | 23.12 | 521.33 | 23.76 | 54.33 | 23.76 |
September | 141.83 | 21.79 | 352.67 | 23.26 | 2.00 | 23.24 |
October | 486.00 | 21.14 | 126.17 | 21.26 | 74.67 | 21.15 |
November | 551.33 | 21.00 | 107.33 | 20.87 | 102.33 | 20.76 |
December | 585.00 | 20.95 | 210.00 | 20.83 | 210.00 | 20.75 |
Annual Sum or Average | 4701.17 | 21.23 | 3065.17 | 21.80 | 1275.83 | 21.67 |
Minimum of Months | 94.67 | 20.92 | 106.00 | 20.80 | 2.00 | 20.72 |
Maximum of Months | 592.83 | 23.47 | 521.33 | 23.80 | 210.00 | 23.80 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 563.33 | 18.95 | 307.00 | 19.05 | 274.50 | 18.93 |
February | 523.67 | 18.93 | 330.00 | 18.95 | 311.33 | 18.86 |
March | 513.17 | 19.43 | 309.33 | 19.90 | 225.33 | 19.70 |
April | 476.17 | 19.59 | 271.83 | 20.25 | 178.00 | 20.11 |
May | 393.33 | 23.28 | 409.67 | 24.11 | 228.00 | 24.38 |
June | 504.00 | 26.04 | 585.50 | 25.95 | 499.83 | 25.99 |
July | 551.33 | 26.07 | 603.17 | 26.02 | 550.33 | 26.04 |
August | 529.17 | 26.05 | 608.67 | 25.95 | 528.50 | 25.99 |
September | 450.83 | 25.42 | 524.17 | 25.56 | 404.00 | 25.70 |
October | 457.00 | 20.39 | 282.67 | 21.30 | 168.33 | 21.34 |
November | 522.00 | 19.20 | 242.00 | 19.48 | 190.50 | 19.34 |
December | 561.83 | 18.98 | 359.00 | 19.10 | 323.00 | 18.97 |
Annual Sum or Average | 6045.83 | 21.80 | 4833.00 | 22.49 | 3881.67 | 22.62 |
Minimum of Months | 393.33 | 18.93 | 242.00 | 18.95 | 168.33 | 18.86 |
Maximum of Months | 563.33 | 26.07 | 608.67 | 26.02 | 550.33 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.03770 | 23.08476 | -0.4476 | 10.91342 |
February | 551.00000 | 20.98465 | 20.60624 | -0.4929 | 11.89948 |
March | 612.00000 | 21.32170 | 21.13621 | -0.3855 | 10.59769 |
April | 590.00000 | 21.38073 | 26.25962 | -0.3466 | 9.94702 |
May | 611.00000 | 22.33105 | 31.62994 | -1.0217 | 30.58453 |
June | 592.00000 | 23.74420 | 35.38341 | -0.3853 | 9.07648 |
July | 609.00000 | 23.80656 | 38.35517 | -0.3454 | 8.30702 |
August | 612.00000 | 23.75561 | 36.97875 | -0.3428 | 8.39218 |
September | 590.00000 | 23.35486 | 28.38512 | -0.5425 | 14.27829 |
October | 610.00000 | 21.67830 | 24.34847 | -0.1950 | 8.73996 |
November | 591.00000 | 21.18589 | 24.88665 | -0.3513 | 9.55729 |
December | 609.00000 | 21.06908 | 16.85863 | -0.4885 | 11.99308 |
Annual Sum or Average | 7187.00000 | 22.14437 | 27.36902 | -0.4455 | 12.04000 |
Minimum of Months | 551.00000 | 20.98465 | 16.85863 | -1.0217 | 8.30702 |
Maximum of Months | 612.00000 | 23.80656 | 38.35517 | -0.1950 | 30.58453 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.37001 | 31.22161 | -0.5534 | 14.84214 |
February | 551.00000 | 19.20390 | 28.76545 | -0.6159 | 15.78750 |
March | 612.00000 | 20.32252 | 28.55999 | -0.3393 | 14.37553 |
April | 590.00000 | 20.56119 | 33.36349 | -0.2425 | 13.87187 |
May | 611.00000 | 23.56407 | 34.71293 | -0.3192 | 19.87246 |
June | 592.00000 | 25.83321 | 35.36638 | 0.53135 | 12.82150 |
July | 609.00000 | 25.93046 | 37.51630 | 0.58114 | 13.59902 |
August | 612.00000 | 25.84215 | 36.91846 | 0.55581 | 13.15581 |
September | 590.00000 | 25.15269 | 30.36155 | 0.27078 | 14.12915 |
October | 610.00000 | 21.33554 | 30.63094 | -0.0321 | 13.72025 |
November | 591.00000 | 19.80908 | 32.83003 | -0.4037 | 13.43198 |
December | 609.00000 | 19.43610 | 24.37429 | -0.5740 | 15.88105 |
Annual Sum or Average | 7187.00000 | 22.21539 | 32.07052 | -0.0921 | 14.62583 |
Minimum of Months | 551.00000 | 19.20390 | 24.37429 | -0.6159 | 12.82150 |
Maximum of Months | 612.00000 | 25.93046 | 37.51630 | 0.58114 | 19.87246 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 32381693.66 | 9848076.58 | 4.62 | 32381693.66 | -0.0 | 0.00 | 0.23 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 | 3798.03 | 20-JAN-13:55 | 3798.03 | 20-JAN-13:55 | 0.00 | 20-JAN-13:40 | 1138.54 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 |
February | 6220122.54 | 1939296.40 | 2.00 | 6220122.54 | -0.0 | 0.00 | 0.09 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 1442.89 | 18-FEB-14:00 | 1442.89 | 18-FEB-14:00 | 0.00 | 18-FEB-13:30 | 447.41 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.307688E+09 | 90544137.10 | 22.39 | 0.307688E+09 | -0.0 | 0.00 | 0.54 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 9532.37 | 14-MAR-13:00 | 9532.37 | 14-MAR-13:00 | 0.00 | 14-MAR-14:42 | 2643.52 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.144771E+09 | 44189672.40 | 24.17 | 0.144756E+09 | 15837.43 | 0.00 | 0.32 | 20-APR-13:00 | 0.00 | 01-APR-00:01 | 5330.58 | 20-APR-13:00 | 5330.58 | 20-APR-13:00 | 9.38 | 27-APR-15:40 | 1564.11 | 20-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.252630E+10 | 0.720112E+09 | 131.92 | 0.248555E+10 | 40758524.31 | 0.00 | 0.78 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 | 14595.64 | 17-MAY-12:55 | 14595.64 | 17-MAY-12:55 | 1362.30 | 31-MAY-18:40 | 3796.62 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 |
June | 0.156755E+11 | 0.427239E+10 | 396.00 | 0.148007E+11 | 0.874835E+09 | 0.00 | 1.00 | 12-JUN-11:02 | 0.00 | 01-JUN-00:01 | 27795.79 | 26-JUN-17:17 | 27795.79 | 26-JUN-17:17 | 7552.15 | 21-JUN-04:01 | 8154.46 | 26-JUN-17:17 | 0.00 | 01-JUN-00:01 |
July | 0.168391E+11 | 0.455983E+10 | 425.82 | 0.156191E+11 | 0.122008E+10 | 0.00 | 1.00 | 10-JUL-12:53 | 0.00 | 01-JUL-00:01 | 25290.58 | 17-JUL-11:55 | 25290.58 | 17-JUL-11:55 | 6616.64 | 22-JUL-04:01 | 7126.23 | 17-JUL-11:55 | 0.00 | 01-JUL-00:01 |
August | 0.152808E+11 | 0.412573E+10 | 399.72 | 0.143668E+11 | 0.913984E+09 | 0.00 | 1.00 | 04-AUG-11:55 | 0.00 | 01-AUG-00:01 | 25761.51 | 16-AUG-17:03 | 25761.51 | 16-AUG-17:03 | 6937.97 | 26-AUG-04:01 | 7202.98 | 16-AUG-17:03 | 0.00 | 01-AUG-00:01 |
September | 0.972273E+10 | 0.265568E+10 | 310.28 | 0.953819E+10 | 0.184542E+09 | 0.00 | 0.97 | 09-SEP-13:00 | 0.00 | 01-SEP-00:01 | 18664.75 | 09-SEP-13:00 | 18664.75 | 09-SEP-13:00 | 5238.95 | 01-SEP-04:01 | 4941.23 | 09-SEP-13:00 | 0.00 | 01-SEP-00:01 |
October | 0.899506E+09 | 0.257027E+09 | 55.46 | 0.899506E+09 | 0.00 | 0.00 | 0.71 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 | 13125.40 | 11-OCT-13:00 | 13125.40 | 11-OCT-13:00 | 0.00 | 11-OCT-11:20 | 3476.80 | 11-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.190053E+09 | 56961036.04 | 19.33 | 0.190053E+09 | 0.00 | 0.00 | 0.39 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 | 6647.85 | 07-NOV-14:00 | 6647.85 | 07-NOV-14:00 | 0.00 | 07-NOV-14:10 | 1915.75 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 77431771.64 | 23459325.64 | 9.83 | 77431771.64 | 0.00 | 0.00 | 0.31 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 | 5131.04 | 01-DEC-14:00 | 5131.04 | 01-DEC-14:00 | 0.00 | 01-DEC-14:10 | 1509.72 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.617026E+11 | 0.168177E+11 | 1801.56 | 0.584684E+11 | 0.323421E+10 | 0.00 | ||||||||||||||
Minimum of Months | 6220122.54 | 1939296.40 | 2.00 | 6220122.54 | -0.0 | 0.00 | 0.09 | 0.00 | 1442.89 | 1442.89 | 0.00 | 447.41 | 0.00 | |||||||
Maximum of Months | 0.168391E+11 | 0.455983E+10 | 425.82 | 0.156191E+11 | 0.122008E+10 | 0.00 | 1.00 | 0.00 | 27795.79 | 27795.79 | 7552.15 | 8154.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 70859085.84 | 20821678.86 | 11.53 | 70760995.41 | 98090.43 | 0.00 | 0.37 | 20-JAN-14:00 | 0.00 | 01-JAN-00:01 | 4530.47 | 20-JAN-14:00 | 4530.47 | 20-JAN-14:00 | 238.19 | 20-JAN-05:01 | 1290.66 | 20-JAN-14:00 | 0.00 | 01-JAN-00:01 |
February | 27808029.74 | 8260250.28 | 4.53 | 27795629.17 | 12400.57 | 0.00 | 0.26 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 3112.83 | 18-FEB-14:00 | 3112.83 | 18-FEB-14:00 | 206.68 | 19-FEB-05:01 | 910.90 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.457971E+09 | 0.129886E+09 | 44.58 | 0.457012E+09 | 958835.65 | 0.00 | 1.00 | 14-MAR-03:42 | 0.00 | 01-MAR-00:01 | 14566.62 | 14-MAR-03:42 | 13097.34 | 14-MAR-03:42 | 4064.62 | 17-MAR-03:42 | 3495.06 | 14-MAR-03:42 | 0.00 | 01-MAR-00:01 |
April | 0.439992E+09 | 0.127120E+09 | 49.69 | 0.433064E+09 | 6927407.02 | 0.00 | 1.00 | 21-APR-03:21 | 0.00 | 01-APR-00:01 | 29166.69 | 21-APR-03:21 | 21124.51 | 21-APR-04:01 | 10602.30 | 21-APR-03:21 | 6992.69 | 21-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.413061E+10 | 0.111326E+10 | 213.71 | 0.395185E+10 | 0.178762E+09 | 0.00 | 1.00 | 05-MAY-03:21 | 0.00 | 01-MAY-00:01 | 29166.69 | 05-MAY-03:21 | 22373.61 | 05-MAY-04:01 | 14798.25 | 22-MAY-04:01 | 6992.69 | 05-MAY-03:21 | 0.00 | 01-MAY-00:01 |
June | 0.199633E+11 | 0.510957E+10 | 472.55 | 0.185128E+11 | 0.145048E+10 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:01 | 29166.69 | 27-JUN-00:42 | 29166.69 | 07-JUN-03:01 | 17196.70 | 21-JUN-03:11 | 8401.18 | 26-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.219353E+11 | 0.557653E+10 | 516.71 | 0.198654E+11 | 0.206988E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 29166.69 | 26-JUL-02:11 | 29166.69 | 01-JUL-02:61 | 17199.07 | 20-JUL-03:21 | 7771.32 | 16-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.192241E+11 | 0.488809E+10 | 479.72 | 0.177497E+11 | 0.147435E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 29166.69 | 03-AUG-03:21 | 29166.69 | 15-AUG-02:11 | 19342.29 | 04-AUG-03:31 | 7784.93 | 16-AUG-14:00 | 0.00 | 01-AUG-00:01 |
September | 0.124509E+11 | 0.318617E+10 | 390.23 | 0.120168E+11 | 0.434125E+09 | 0.00 | 1.00 | 01-SEP-03:31 | 0.00 | 01-SEP-00:01 | 29166.69 | 10-SEP-02:11 | 29166.69 | 30-SEP-02:11 | 14691.98 | 01-SEP-03:31 | 6992.69 | 02-SEP-03:21 | 0.00 | 01-SEP-00:01 |
October | 0.127565E+10 | 0.351204E+09 | 87.54 | 0.126240E+10 | 13250014.54 | 0.00 | 1.00 | 01-OCT-04:01 | 0.00 | 01-OCT-00:01 | 29166.69 | 06-OCT-04:01 | 24251.05 | 06-OCT-04:01 | 8443.53 | 10-OCT-03:21 | 6992.69 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 0.313473E+09 | 89908286.03 | 26.57 | 0.311725E+09 | 1748313.89 | 0.00 | 1.00 | 10-NOV-04:42 | 0.00 | 01-NOV-00:01 | 14566.62 | 10-NOV-04:42 | 8802.18 | 10-NOV-04:42 | 5764.44 | 10-NOV-04:42 | 3495.06 | 10-NOV-04:42 | 0.00 | 01-NOV-00:01 |
December | 0.144997E+09 | 42153459.65 | 16.45 | 0.144955E+09 | 41449.30 | 0.00 | 0.43 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 | 5416.82 | 02-DEC-15:00 | 5416.82 | 02-DEC-15:00 | 213.99 | 05-DEC-04:10 | 1518.05 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.804349E+11 | 0.206430E+11 | 2313.80 | 0.748043E+11 | 0.563063E+10 | 0.00 | ||||||||||||||
Minimum of Months | 27808029.74 | 8260250.28 | 4.53 | 27795629.17 | 12400.57 | 0.00 | 0.26 | 0.00 | 3112.83 | 3112.83 | 206.68 | 910.90 | 0.00 | |||||||
Maximum of Months | 0.219353E+11 | 0.557653E+10 | 516.71 | 0.198654E+11 | 0.206988E+10 | 0.00 | 1.00 | 0.00 | 29166.69 | 29166.69 | 19342.29 | 8401.18 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 129.31 | 79.25 | 50.07 | 118.16 | 180.40 | 0.00 | 0.00 | 0.00 |
February | 171.78 | 108.44 | 63.33 | 166.53 | 184.80 | 0.00 | 0.00 | 0.00 |
March | 207.33 | 120.93 | 86.40 | 216.97 | 137.90 | 0.00 | 0.00 | 0.00 |
April | 212.63 | 103.57 | 109.05 | 219.12 | 119.15 | 0.00 | 0.00 | 0.00 |
May | 248.56 | 103.82 | 144.74 | 292.48 | 69.88 | 0.00 | 0.00 | 0.00 |
June | 303.27 | 159.21 | 144.06 | 410.50 | 42.40 | 0.00 | 0.00 | 0.00 |
July | 275.69 | 131.28 | 144.42 | 377.21 | 39.60 | 0.00 | 0.00 | 0.00 |
August | 278.08 | 153.15 | 124.92 | 375.29 | 47.03 | 0.00 | 0.00 | 0.00 |
September | 231.37 | 125.69 | 105.68 | 296.67 | 68.96 | 0.00 | 0.00 | 0.00 |
October | 167.56 | 91.81 | 75.75 | 179.80 | 140.41 | 0.00 | 0.00 | 0.00 |
November | 130.42 | 73.64 | 56.79 | 125.25 | 166.86 | 0.00 | 0.00 | 0.00 |
December | 112.91 | 65.05 | 47.87 | 97.35 | 209.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 205.87 | 109.60 | 96.27 | 239.96 | 116.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.91 | 65.05 | 47.87 | 97.35 | 39.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 303.27 | 159.21 | 144.74 | 410.50 | 209.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 791.59 | 651.17 | 140.42 | 923.38 | 336.73 | 0.00 | 0.00 | 0.00 |
February | 759.28 | 605.34 | 153.93 | 880.59 | 351.04 | 0.00 | 0.00 | 0.00 |
March | 559.80 | 368.32 | 191.48 | 657.96 | 275.46 | 0.00 | 0.00 | 0.00 |
April | 362.57 | 145.79 | 216.78 | 392.06 | 248.74 | 0.00 | 0.00 | 0.00 |
May | 332.25 | 60.90 | 271.35 | 394.47 | 150.11 | 0.00 | 0.00 | 0.00 |
June | 306.33 | 55.99 | 250.34 | 443.46 | 91.60 | 0.00 | 0.00 | 0.00 |
July | 318.88 | 57.10 | 261.78 | 464.12 | 83.95 | 0.00 | 0.00 | 0.00 |
August | 406.00 | 169.72 | 236.28 | 589.76 | 97.78 | 0.00 | 0.00 | 0.00 |
September | 522.36 | 291.47 | 230.88 | 713.53 | 143.78 | 0.00 | 0.00 | 0.00 |
October | 624.58 | 443.16 | 181.43 | 767.79 | 276.82 | 0.00 | 0.00 | 0.00 |
November | 760.97 | 606.60 | 154.37 | 905.85 | 318.78 | 0.00 | 0.00 | 0.00 |
December | 727.68 | 588.98 | 138.71 | 828.79 | 387.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 538.11 | 335.52 | 202.59 | 662.24 | 229.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 306.33 | 55.99 | 138.71 | 392.06 | 83.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 791.59 | 651.17 | 271.35 | 923.38 | 387.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.56 | 87.16 | 50.39 | 132.75 | 183.07 | 0.00 | 0.00 | 0.00 |
February | 165.88 | 102.79 | 63.08 | 159.82 | 185.41 | 0.00 | 0.00 | 0.00 |
March | 194.23 | 107.16 | 87.07 | 199.38 | 139.00 | 0.00 | 0.00 | 0.00 |
April | 182.88 | 77.43 | 105.45 | 181.37 | 121.28 | 0.00 | 0.00 | 0.00 |
May | 223.52 | 78.80 | 144.72 | 262.17 | 72.96 | 0.00 | 0.00 | 0.00 |
June | 273.38 | 131.53 | 141.85 | 373.49 | 45.60 | 0.00 | 0.00 | 0.00 |
July | 222.74 | 81.59 | 141.16 | 305.89 | 41.74 | 0.00 | 0.00 | 0.00 |
August | 232.48 | 114.85 | 117.63 | 312.33 | 48.31 | 0.00 | 0.00 | 0.00 |
September | 206.14 | 98.86 | 107.28 | 264.41 | 71.79 | 0.00 | 0.00 | 0.00 |
October | 173.42 | 99.12 | 74.30 | 189.48 | 141.03 | 0.00 | 0.00 | 0.00 |
November | 142.30 | 86.39 | 55.91 | 140.64 | 167.00 | 0.00 | 0.00 | 0.00 |
December | 114.94 | 67.90 | 47.04 | 100.35 | 208.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 189.18 | 94.35 | 94.83 | 218.75 | 118.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 114.94 | 67.90 | 47.04 | 100.35 | 41.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 273.38 | 131.53 | 144.72 | 373.49 | 208.77 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.346350E+09 | 0.212253E+09 | 0.134096E+09 | 0.316478E+09 | 0.483176E+09 |
February | 0.415563E+09 | 0.262343E+09 | 0.153220E+09 | 0.402875E+09 | 0.447074E+09 |
March | 0.555313E+09 | 0.323908E+09 | 0.231404E+09 | 0.581131E+09 | 0.369362E+09 |
April | 0.551132E+09 | 0.268466E+09 | 0.282667E+09 | 0.567962E+09 | 0.308839E+09 |
May | 0.665741E+09 | 0.278082E+09 | 0.387659E+09 | 0.783381E+09 | 0.187164E+09 |
June | 0.786070E+09 | 0.412665E+09 | 0.373405E+09 | 0.106402E+10 | 0.109897E+09 |
July | 0.738420E+09 | 0.351617E+09 | 0.386803E+09 | 0.101032E+10 | 0.106063E+09 |
August | 0.744797E+09 | 0.410207E+09 | 0.334590E+09 | 0.100516E+10 | 0.125962E+09 |
September | 0.599719E+09 | 0.325784E+09 | 0.273935E+09 | 0.768976E+09 | 0.178754E+09 |
October | 0.448793E+09 | 0.245912E+09 | 0.202881E+09 | 0.481570E+09 | 0.376086E+09 |
November | 0.338059E+09 | 0.190871E+09 | 0.147188E+09 | 0.324644E+09 | 0.432513E+09 |
December | 0.302425E+09 | 0.174218E+09 | 0.128207E+09 | 0.260742E+09 | 0.560421E+09 |
Annual Sum or Average | 0.649238E+10 | 0.345633E+10 | 0.303605E+10 | 0.756726E+10 | 0.368531E+10 |
Minimum of Months | 0.302425E+09 | 0.174218E+09 | 0.128207E+09 | 0.260742E+09 | 0.106063E+09 |
Maximum of Months | 0.786070E+09 | 0.412665E+09 | 0.387659E+09 | 0.106402E+10 | 0.560421E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.212019E+10 | 0.174408E+10 | 0.376106E+09 | 0.247319E+10 | 0.901894E+09 |
February | 0.183685E+10 | 0.146445E+10 | 0.372398E+09 | 0.213033E+10 | 0.849229E+09 |
March | 0.149937E+10 | 0.986497E+09 | 0.512869E+09 | 0.176228E+10 | 0.737801E+09 |
April | 0.939776E+09 | 0.377887E+09 | 0.561889E+09 | 0.101621E+10 | 0.644736E+09 |
May | 0.889909E+09 | 0.163113E+09 | 0.726795E+09 | 0.105656E+10 | 0.402043E+09 |
June | 0.794000E+09 | 0.145120E+09 | 0.648880E+09 | 0.114946E+10 | 0.237429E+09 |
July | 0.854086E+09 | 0.152943E+09 | 0.701144E+09 | 0.124311E+10 | 0.224861E+09 |
August | 0.108743E+10 | 0.454584E+09 | 0.632841E+09 | 0.157962E+10 | 0.261893E+09 |
September | 0.135395E+10 | 0.755493E+09 | 0.598453E+09 | 0.184946E+10 | 0.372665E+09 |
October | 0.167289E+10 | 0.118695E+10 | 0.485937E+09 | 0.205644E+10 | 0.741437E+09 |
November | 0.197243E+10 | 0.157231E+10 | 0.400118E+09 | 0.234796E+10 | 0.826281E+09 |
December | 0.194903E+10 | 0.157752E+10 | 0.371512E+09 | 0.221982E+10 | 0.103763E+10 |
Annual Sum or Average | 0.169699E+11 | 0.105809E+11 | 0.638894E+10 | 0.208844E+11 | 0.723790E+10 |
Minimum of Months | 0.794000E+09 | 0.145120E+09 | 0.371512E+09 | 0.101621E+10 | 0.224861E+09 |
Maximum of Months | 0.212019E+10 | 0.174408E+10 | 0.726795E+09 | 0.247319E+10 | 0.103763E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.368439E+09 | 0.233462E+09 | 0.134976E+09 | 0.355549E+09 | 0.490327E+09 |
February | 0.401290E+09 | 0.248680E+09 | 0.152609E+09 | 0.386626E+09 | 0.448534E+09 |
March | 0.520229E+09 | 0.287021E+09 | 0.233207E+09 | 0.534026E+09 | 0.372296E+09 |
April | 0.474019E+09 | 0.200691E+09 | 0.273328E+09 | 0.470105E+09 | 0.314358E+09 |
May | 0.598685E+09 | 0.211058E+09 | 0.387627E+09 | 0.702206E+09 | 0.195412E+09 |
June | 0.708608E+09 | 0.340938E+09 | 0.367670E+09 | 0.968080E+09 | 0.118204E+09 |
July | 0.596593E+09 | 0.218521E+09 | 0.378073E+09 | 0.819295E+09 | 0.111798E+09 |
August | 0.622674E+09 | 0.307609E+09 | 0.315065E+09 | 0.836556E+09 | 0.129389E+09 |
September | 0.534315E+09 | 0.256239E+09 | 0.278076E+09 | 0.685361E+09 | 0.186073E+09 |
October | 0.464484E+09 | 0.265487E+09 | 0.198997E+09 | 0.507497E+09 | 0.377728E+09 |
November | 0.368839E+09 | 0.223930E+09 | 0.144908E+09 | 0.364530E+09 | 0.432852E+09 |
December | 0.307851E+09 | 0.181856E+09 | 0.125996E+09 | 0.268790E+09 | 0.559168E+09 |
Annual Sum or Average | 0.596603E+10 | 0.297549E+10 | 0.299053E+10 | 0.689862E+10 | 0.373614E+10 |
Minimum of Months | 0.307851E+09 | 0.181856E+09 | 0.125996E+09 | 0.268790E+09 | 0.111798E+09 |
Maximum of Months | 0.708608E+09 | 0.340938E+09 | 0.387627E+09 | 0.968080E+09 | 0.559168E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1147.54 | 673.44 | 1058.46 | 817.58 | 240.88 | 0.00 | 0.00 |
February | 1184.13 | 698.43 | 1096.93 | 816.58 | 280.35 | 0.00 | 0.00 |
March | 1057.84 | 535.89 | 961.36 | 596.41 | 364.95 | 0.00 | 0.00 |
April | 775.58 | 472.21 | 758.07 | 326.79 | 431.28 | 0.00 | 0.00 |
May | 936.48 | 280.30 | 804.34 | 243.52 | 560.81 | 0.00 | 0.00 |
June | 1218.81 | 170.96 | 882.98 | 346.73 | 536.25 | 0.00 | 0.00 |
July | 1141.46 | 159.53 | 817.32 | 269.97 | 547.35 | 0.00 | 0.00 |
August | 1272.14 | 187.88 | 916.55 | 437.72 | 478.83 | 0.00 | 0.00 |
September | 1266.38 | 276.29 | 959.87 | 516.02 | 443.85 | 0.00 | 0.00 |
October | 1129.32 | 550.53 | 965.56 | 634.09 | 331.47 | 0.00 | 0.00 |
November | 1156.21 | 637.12 | 1033.69 | 766.63 | 267.06 | 0.00 | 0.00 |
December | 998.97 | 777.89 | 955.54 | 721.92 | 233.62 | 0.00 | 0.00 |
Annual Sum or Average | 1106.47 | 450.36 | 933.17 | 539.47 | 393.69 | 0.00 | 0.00 |
Minimum of Months | 775.58 | 159.53 | 758.07 | 243.52 | 233.62 | 0.00 | 0.00 |
Maximum of Months | 1272.14 | 777.89 | 1096.93 | 817.58 | 560.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.307357E+10 | 0.180375E+10 | 0.283498E+10 | 0.218980E+10 | 0.645178E+09 | 0.00 | 0.00 |
February | 0.286465E+10 | 0.168965E+10 | 0.265370E+10 | 0.197547E+10 | 0.678227E+09 | 0.00 | 0.00 |
March | 0.283331E+10 | 0.143533E+10 | 0.257491E+10 | 0.159743E+10 | 0.977481E+09 | 0.00 | 0.00 |
April | 0.201031E+10 | 0.122397E+10 | 0.196493E+10 | 0.847044E+09 | 0.111788E+10 | 0.00 | 0.00 |
May | 0.250827E+10 | 0.750747E+09 | 0.215433E+10 | 0.652254E+09 | 0.150208E+10 | 0.00 | 0.00 |
June | 0.315915E+10 | 0.443121E+09 | 0.228868E+10 | 0.898724E+09 | 0.138995E+10 | 0.00 | 0.00 |
July | 0.305729E+10 | 0.427287E+09 | 0.218910E+10 | 0.723080E+09 | 0.146602E+10 | 0.00 | 0.00 |
August | 0.340731E+10 | 0.503208E+09 | 0.245490E+10 | 0.117240E+10 | 0.128250E+10 | 0.00 | 0.00 |
September | 0.328245E+10 | 0.716137E+09 | 0.248798E+10 | 0.133752E+10 | 0.115046E+10 | 0.00 | 0.00 |
October | 0.302478E+10 | 0.147453E+10 | 0.258616E+10 | 0.169835E+10 | 0.887814E+09 | 0.00 | 0.00 |
November | 0.299690E+10 | 0.165141E+10 | 0.267933E+10 | 0.198711E+10 | 0.692214E+09 | 0.00 | 0.00 |
December | 0.267565E+10 | 0.208351E+10 | 0.255931E+10 | 0.193359E+10 | 0.625715E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348936E+11 | 0.142026E+11 | 0.294283E+11 | 0.170128E+11 | 0.124155E+11 | 0.00 | 0.00 |
Minimum of Months | 0.201031E+10 | 0.427287E+09 | 0.196493E+10 | 0.652254E+09 | 0.625715E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340731E+10 | 0.208351E+10 | 0.283498E+10 | 0.218980E+10 | 0.150208E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.146907E+11 | -0.139023E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -788436656.0 | 58.99 | 0.00 | 0.00 |
February | 0.134289E+11 | -0.127130E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -715902964.5 | 58.99 | 0.00 | 0.00 |
March | 0.146658E+11 | -0.138960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -769786395.1 | 58.99 | 0.00 | 0.00 |
April | 0.136237E+11 | -0.128844E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -739289203.2 | 58.99 | 0.00 | 0.00 |
May | 0.132930E+11 | -0.125885E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -704481703.0 | 58.99 | 0.00 | 0.00 |
June | 0.121112E+11 | -0.114722E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -638937049.4 | 59.00 | 0.00 | 0.00 |
July | 0.119440E+11 | -0.112855E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -658493460.9 | 58.99 | 0.00 | 0.00 |
August | 0.117924E+11 | -0.111329E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -659513321.5 | 58.98 | 0.00 | 0.00 |
September | 0.116069E+11 | -0.109558E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -651031015.9 | 58.99 | 0.00 | 0.00 |
October | 0.126295E+11 | -0.118832E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -746265431.5 | 58.99 | 0.00 | 0.00 |
November | 0.129851E+11 | -0.122320E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -753128754.9 | 58.99 | 0.00 | 0.00 |
December | 0.141402E+11 | -0.133522E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -787997459.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.156911E+12 | -0.148298E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.861326E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.116069E+11 | -0.139023E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -788436656.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.146907E+11 | -0.109558E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -638937049.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.62 | 01-JAN-07:00 | 7571.61 | 32.93 | 198.67 | 261.83 | 7765.11 | 33.43 | 199.83 | 262.33 |
February | 245.50 | 0.63 | 0.62 | 01-FEB-10:39 | 2816.87 | 25.75 | 108.83 | 264.83 | 3507.36 | 26.57 | 115.83 | 263.50 |
March | 296.17 | 0.63 | 0.62 | 01-MAR-06:00 | 1868.62 | 21.05 | 64.67 | 334.00 | 1878.02 | 21.19 | 73.17 | 331.83 |
April | 296.67 | 0.63 | 0.62 | 03-APR-09:39 | 1990.38 | 18.85 | 20.00 | 354.17 | 2358.40 | 18.78 | 18.67 | 354.67 |
May | 415.33 | 0.63 | 0.62 | 01-MAY-05:49 | 1420.31 | 18.91 | 12.50 | 404.83 | 1571.10 | 18.88 | 15.67 | 406.33 |
June | 421.50 | 0.63 | 0.62 | 01-JUN-05:19 | 1477.62 | 18.40 | 1.17 | 411.67 | 1642.53 | 18.36 | 1.50 | 411.83 |
July | 430.33 | 0.64 | 0.62 | 01-JUL-05:30 | 1418.11 | 18.58 | 5.67 | 412.50 | 1591.41 | 18.51 | 10.33 | 415.67 |
August | 394.50 | 0.64 | 0.62 | 01-AUG-05:00 | 2006.67 | 18.35 | 14.00 | 382.67 | 2365.65 | 18.25 | 9.33 | 380.17 |
September | 354.00 | 0.63 | 0.62 | 01-SEP-05:00 | 1727.23 | 18.96 | 36.00 | 345.00 | 1892.05 | 18.93 | 46.33 | 343.67 |
October | 262.67 | 0.63 | 0.62 | 01-OCT-06:30 | 2684.98 | 22.26 | 90.00 | 303.67 | 2279.68 | 21.92 | 67.50 | 302.33 |
November | 257.67 | 0.64 | 0.62 | 01-NOV-08:39 | 9903.06 | 36.62 | 224.33 | 261.67 | 8925.30 | 33.89 | 185.67 | 261.67 |
December | 251.17 | 0.64 | 0.62 | 01-DEC-07:49 | 7329.96 | 34.32 | 191.00 | 252.83 | 7230.89 | 34.66 | 193.17 | 253.17 |
Annual Sum or Average | 3902.00 | 0.63 | 3140.19 | 22.73 | 966.83 | 3989.67 | 3232.04 | 22.62 | 937.00 | 3987.17 | ||
Minimum of Months | 245.50 | 0.63 | 0.62 | 1418.11 | 18.35 | 1.17 | 252.83 | 1571.10 | 18.25 | 1.50 | 253.17 | |
Maximum of Months | 430.33 | 0.64 | 0.62 | 9903.06 | 36.62 | 224.33 | 412.50 | 8925.30 | 34.66 | 199.83 | 415.67 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251265E+11 | 61456.30 | 03-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259840E+11 | 61456.30 | 01-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187296E+11 | 61456.30 | 02-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150634E+11 | 61456.30 | 02-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294466E+10 | 20984.23 | 02-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23639860.27 | 3116.13 | 09-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9059267.56 | 1509.93 | 03-JUL-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7094415.52 | 1818.25 | 13-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.932146E+09 | 16640.91 | 21-SEP-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127259E+11 | 61456.30 | 30-OCT-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194639E+11 | 61456.30 | 02-NOV-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.303072E+11 | 61456.30 | 07-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 7094415.52 | 1509.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303072E+11 | 61456.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198564E+11 | 47629.18 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203747E+11 | 49749.73 | 12-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125742E+11 | 34078.58 | 19-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.893112E+10 | 32089.64 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.607263E+09 | 16686.50 | 03-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305776E+09 | 11576.21 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791926E+10 | 36066.95 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135855E+11 | 34944.60 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251717E+11 | 50996.91 | 20-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251717E+11 | 50996.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 32381693.66 | 32381693.66 | 3798.03 | 20-JAN-13:55 | 3798.03 | 0.00 |
February | 0.00 | 0.00 | 6220122.54 | 6220122.54 | 1442.89 | 18-FEB-14:00 | 1442.89 | 0.00 |
March | 0.00 | 0.00 | 0.307688E+09 | 0.307688E+09 | 9532.37 | 14-MAR-13:00 | 9532.37 | 0.00 |
April | 0.00 | 0.00 | 0.144771E+09 | 0.144756E+09 | 5330.58 | 20-APR-13:00 | 5330.58 | 0.00 |
May | 0.00 | 0.00 | 0.252630E+10 | 0.248555E+10 | 14595.64 | 17-MAY-12:55 | 14595.64 | 0.00 |
June | 0.00 | 0.00 | 0.156755E+11 | 0.148007E+11 | 27795.79 | 26-JUN-17:17 | 27795.79 | 0.00 |
July | 0.00 | 0.00 | 0.168391E+11 | 0.156191E+11 | 25290.58 | 17-JUL-11:55 | 25290.58 | 0.00 |
August | 0.00 | 0.00 | 0.152808E+11 | 0.143668E+11 | 25761.51 | 16-AUG-17:03 | 25761.51 | 0.00 |
September | 0.00 | 0.00 | 0.972273E+10 | 0.953819E+10 | 18664.75 | 09-SEP-13:00 | 18664.75 | 0.00 |
October | 0.00 | 0.00 | 0.899506E+09 | 0.899506E+09 | 13125.40 | 11-OCT-13:00 | 13125.40 | 0.00 |
November | 0.00 | 0.00 | 0.190053E+09 | 0.190053E+09 | 6647.85 | 07-NOV-14:00 | 6647.85 | 0.00 |
December | 0.00 | 0.00 | 77431771.64 | 77431771.64 | 5131.04 | 01-DEC-14:00 | 5131.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.617026E+11 | 0.584684E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6220122.54 | 6220122.54 | 1442.89 | 1442.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168391E+11 | 0.156191E+11 | 27795.79 | 27795.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 70859085.84 | 70760995.41 | 4530.47 | 20-JAN-14:00 | 4530.47 | 0.00 |
February | 0.00 | 0.00 | 27808029.74 | 27795629.17 | 3112.83 | 18-FEB-14:00 | 3112.83 | 0.00 |
March | 0.00 | 0.00 | 0.457971E+09 | 0.457012E+09 | 14566.62 | 14-MAR-03:42 | 13097.34 | 0.00 |
April | 0.00 | 0.00 | 0.439992E+09 | 0.433064E+09 | 29166.69 | 21-APR-03:21 | 18564.39 | 0.00 |
May | 0.00 | 0.00 | 0.413061E+10 | 0.395185E+10 | 29166.69 | 05-MAY-03:21 | 20263.82 | 0.00 |
June | 0.00 | 0.00 | 0.199633E+11 | 0.185128E+11 | 29166.69 | 27-JUN-00:42 | 29166.69 | 0.00 |
July | 0.00 | 0.00 | 0.219353E+11 | 0.198654E+11 | 29166.69 | 26-JUL-02:11 | 21521.71 | 0.00 |
August | 0.00 | 0.00 | 0.192241E+11 | 0.177497E+11 | 29166.69 | 03-AUG-03:21 | 17809.50 | 0.00 |
September | 0.00 | 0.00 | 0.124509E+11 | 0.120168E+11 | 29166.69 | 10-SEP-02:11 | 23518.03 | 0.00 |
October | 0.00 | 0.00 | 0.127565E+10 | 0.126240E+10 | 29166.69 | 06-OCT-04:01 | 24251.05 | 0.00 |
November | 0.00 | 0.00 | 0.313473E+09 | 0.311725E+09 | 14566.62 | 10-NOV-04:42 | 8802.18 | 0.00 |
December | 0.00 | 0.00 | 0.144997E+09 | 0.144955E+09 | 5416.82 | 02-DEC-15:00 | 5416.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.804349E+11 | 0.748043E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 27808029.74 | 27795629.17 | 3112.83 | 3112.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219353E+11 | 0.198654E+11 | 29166.69 | 29166.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5483.48 | 20523.16 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5548.19 | 20577.95 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5482.93 | 20496.15 | 01-MAR-13:33 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5262.73 | 19904.81 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4992.43 | 18934.15 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4719.10 | 17791.55 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4503.69 | 16849.28 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4449.87 | 16327.79 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4517.83 | 16894.95 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4728.25 | 17888.54 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5011.57 | 18995.49 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5276.67 | 19976.98 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.86 | ||||
Minimum of Months | 0.00 | 0.00 | 4449.87 | 16327.79 | ||
Maximum of Months | 0.00 | 0.00 | 5548.19 | 20577.95 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112563E+10 | 0.27 | 503.64 | 01-JAN-00:01 | 0.33 |
February | 0.101563E+10 | 0.27 | 503.64 | 01-FEB-00:01 | 0.33 |
March | 0.113511E+10 | 0.27 | 503.64 | 01-MAR-00:01 | 0.33 |
April | 0.109855E+10 | 0.27 | 503.64 | 01-APR-04:01 | 0.32 |
May | 0.118123E+10 | 0.28 | 503.64 | 01-MAY-04:01 | 0.32 |
June | 0.123414E+10 | 0.31 | 503.64 | 01-JUN-01:05 | 0.32 |
July | 0.127823E+10 | 0.31 | 503.64 | 01-JUL-00:10 | 0.33 |
August | 0.128080E+10 | 0.31 | 503.64 | 01-AUG-00:30 | 0.32 |
September | 0.121305E+10 | 0.30 | 503.64 | 01-SEP-00:14 | 0.33 |
October | 0.115651E+10 | 0.28 | 503.64 | 01-OCT-02:62 | 0.32 |
November | 0.109417E+10 | 0.27 | 503.64 | 01-NOV-04:01 | 0.32 |
December | 0.112538E+10 | 0.27 | 503.64 | 01-DEC-00:01 | 0.33 |
Annual Sum or Average | 0.139384E+11 | 0.29 | |||
Minimum of Months | 0.101563E+10 | 0.27 | 503.64 | 0.32 | |
Maximum of Months | 0.128080E+10 | 0.31 | 503.64 | 0.33 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.298954E+10 | 0.65 | 2612.34 | 03-JAN-05:00 | 1.08 |
February | 0.280635E+10 | 0.66 | 2612.34 | 01-FEB-04:03 | 1.08 |
March | 0.283278E+10 | 0.63 | 2612.34 | 02-MAR-04:03 | 1.08 |
April | 0.265101E+10 | 0.61 | 2612.34 | 02-APR-03:02 | 1.08 |
May | 0.240761E+10 | 0.56 | 1580.13 | 02-MAY-04:01 | 0.84 |
June | 0.227565E+10 | 0.55 | 1777.71 | 26-JUN-17:17 | 0.90 |
July | 0.234155E+10 | 0.55 | 1547.60 | 17-JUL-11:55 | 0.83 |
August | 0.234373E+10 | 0.55 | 1581.65 | 16-AUG-17:03 | 0.84 |
September | 0.228200E+10 | 0.55 | 1469.35 | 21-SEP-20:00 | 0.81 |
October | 0.266384E+10 | 0.59 | 2612.34 | 30-OCT-03:05 | 1.09 |
November | 0.276678E+10 | 0.62 | 2612.34 | 02-NOV-03:05 | 1.09 |
December | 0.313266E+10 | 0.66 | 2612.34 | 07-DEC-04:03 | 1.09 |
Annual Sum or Average | 0.314935E+11 | 0.60 | |||
Minimum of Months | 0.227565E+10 | 0.55 | 1469.35 | 0.81 | |
Maximum of Months | 0.313266E+10 | 0.66 | 2612.34 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167639E+10 | 0.61 | 1261.44 | 05-JAN-05:02 | 0.98 |
February | 0.154623E+10 | 0.61 | 1289.38 | 12-FEB-05:03 | 0.99 |
March | 0.158196E+10 | 0.59 | 1082.87 | 19-MAR-04:02 | 0.90 |
April | 0.148822E+10 | 0.58 | 1584.47 | 21-APR-03:21 | 1.08 |
May | 0.143278E+10 | 0.57 | 1584.47 | 05-MAY-03:21 | 1.08 |
June | 0.158279E+10 | 0.64 | 1584.47 | 02-JUN-04:01 | 1.08 |
July | 0.165144E+10 | 0.65 | 1584.47 | 11-JUL-04:01 | 1.08 |
August | 0.159941E+10 | 0.64 | 1584.47 | 03-AUG-03:21 | 1.07 |
September | 0.144653E+10 | 0.61 | 1584.47 | 02-SEP-04:01 | 1.08 |
October | 0.152329E+10 | 0.58 | 1584.47 | 06-OCT-04:01 | 1.08 |
November | 0.154888E+10 | 0.59 | 1094.28 | 27-NOV-05:03 | 0.91 |
December | 0.174643E+10 | 0.62 | 1305.82 | 20-DEC-05:02 | 0.99 |
Annual Sum or Average | 0.188243E+11 | 0.61 | |||
Minimum of Months | 0.143278E+10 | 0.57 | 1082.87 | 0.90 | |
Maximum of Months | 0.174643E+10 | 0.65 | 1584.47 | 1.08 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.90 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.50 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.54 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.39 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.41 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.09 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:02 | 0.00 | 0.00 | 52.99 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 53.14 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:05 | 0.00 | 0.00 | 52.70 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.29 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:05 | 0.00 | 0.00 | 52.35 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.79 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.90 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.14 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.61 | 37.61 | 5483.48 | 20523.16 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.10 | 51.10 | 5548.19 | 20577.95 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.10 | 51.10 | 5482.93 | 20496.15 | 01-MAR-13:33 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.69 | 51.69 | 5262.73 | 19904.81 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.66 | 38.66 | 4992.43 | 18934.15 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.99 | 51.99 | 4719.10 | 17791.55 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.96 | 52.96 | 4503.69 | 16849.28 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 53.05 | 53.05 | 4449.87 | 16327.79 | 31-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.73 | 52.73 | 4517.83 | 16894.95 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.99 | 40.99 | 4728.25 | 17888.54 | 31-OCT-13:00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.50 | 52.50 | 5011.57 | 18995.49 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.02 | 52.02 | 5276.67 | 19976.98 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.61 | 37.61 | 4449.87 | 16327.79 | ||
Maximum of Months | 0.00 | 0.00 | 53.05 | 53.05 | 5548.19 | 20577.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.299939E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.280829E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.292332E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.269520E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.312772E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.654804E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.690138E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.646946E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.493768E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.292087E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.282375E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.315612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.483112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.269520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.690138E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.169721E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.155449E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.171185E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161534E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.254603E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.669236E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.722797E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.648750E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.463269E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.187449E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.163879E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178858E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.394673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155449E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.722797E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.298954E+10 | 32381693.66 | 0.251265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280635E+10 | 6220122.54 | 0.259840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283278E+10 | 0.307688E+09 | 0.187296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265101E+10 | 0.144771E+09 | 0.150634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240761E+10 | 0.252630E+10 | 0.294466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227565E+10 | 0.156755E+11 | 23639860.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.234155E+10 | 0.168391E+11 | 9059267.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234373E+10 | 0.152808E+11 | 7094415.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228200E+10 | 0.972273E+10 | 0.932146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266384E+10 | 0.899506E+09 | 0.127259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276678E+10 | 0.190053E+09 | 0.194639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313266E+10 | 77431771.64 | 0.303072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314935E+11 | 0.617026E+11 | 0.151317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227565E+10 | 6220122.54 | 7094415.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.313266E+10 | 0.168391E+11 | 0.303072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167639E+10 | 70859085.84 | 0.198564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154623E+10 | 27808029.74 | 0.203747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158196E+10 | 0.457971E+09 | 0.125742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148822E+10 | 0.439992E+09 | 0.893112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143278E+10 | 0.413061E+10 | 0.607263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158279E+10 | 0.199373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165144E+10 | 0.218985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159941E+10 | 0.192038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144653E+10 | 0.124335E+11 | 0.305776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152329E+10 | 0.127499E+10 | 0.791926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154888E+10 | 0.313473E+09 | 0.135855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174643E+10 | 0.144997E+09 | 0.251717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188243E+11 | 0.803338E+11 | 0.109326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143278E+10 | 27808029.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174643E+10 | 0.218985E+11 | 0.251717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.298954E+10 | 0.00 | 0.00 | 0.00 | 9848076.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280635E+10 | 0.00 | 0.00 | 0.00 | 1939296.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283278E+10 | 0.00 | 0.00 | 0.00 | 90544137.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265101E+10 | 0.00 | 0.00 | 0.00 | 44189672.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240761E+10 | 0.00 | 0.00 | 0.00 | 0.720112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227565E+10 | 0.00 | 0.00 | 0.00 | 0.427239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.234155E+10 | 0.00 | 0.00 | 0.00 | 0.455983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234373E+10 | 0.00 | 0.00 | 0.00 | 0.412573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228200E+10 | 0.00 | 0.00 | 0.00 | 0.265568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266384E+10 | 0.00 | 0.00 | 0.00 | 0.257027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276678E+10 | 0.00 | 0.00 | 0.00 | 56961036.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313266E+10 | 0.00 | 0.00 | 0.00 | 23459325.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314935E+11 | 0.00 | 0.00 | 0.00 | 0.168177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227565E+10 | 0.00 | 0.00 | 0.00 | 1939296.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.313266E+10 | 0.00 | 0.00 | 0.00 | 0.455983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167639E+10 | 0.00 | 0.00 | 0.00 | 20821678.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154623E+10 | 0.00 | 0.00 | 0.00 | 8260250.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158196E+10 | 0.00 | 0.00 | 0.00 | 0.129886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148822E+10 | 0.00 | 0.00 | 0.00 | 0.127120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143278E+10 | 0.00 | 0.00 | 0.00 | 0.111326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158279E+10 | 0.00 | 0.00 | 0.00 | 0.510957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165144E+10 | 0.00 | 0.00 | 0.00 | 0.557653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159941E+10 | 0.00 | 0.00 | 0.00 | 0.488809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144653E+10 | 0.00 | 0.00 | 0.00 | 0.318617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152329E+10 | 0.00 | 0.00 | 0.00 | 0.351204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154888E+10 | 0.00 | 0.00 | 0.00 | 89908286.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174643E+10 | 0.00 | 0.00 | 0.00 | 42153459.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188243E+11 | 0.00 | 0.00 | 0.00 | 0.206430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143278E+10 | 0.00 | 0.00 | 0.00 | 8260250.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174643E+10 | 0.00 | 0.00 | 0.00 | 0.557653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295038E+10 | 0.00 | 0.00 | 996449.72 | 0.00 | 0.178291E+11 | 0.435920E+09 | 0.00 | 3.69 |
February | 0.259812E+10 | 0.00 | 0.00 | 609225.55 | 0.00 | 0.183679E+11 | 0.261078E+09 | 0.00 | 3.64 |
March | 0.353178E+10 | 0.00 | 0.00 | 4478548.58 | 0.00 | 0.137218E+11 | 0.123175E+10 | 0.00 | 3.92 |
April | 0.345834E+10 | 0.00 | 0.00 | 3687563.19 | 0.00 | 0.114422E+11 | 0.126305E+10 | 0.00 | 3.94 |
May | 0.531859E+10 | 18849260.21 | 0.00 | 14658524.57 | 0.00 | 0.207228E+10 | 0.306888E+10 | 0.00 | 4.66 |
June | 0.129502E+10 | 0.110724E+10 | 0.00 | 29478871.23 | 0.00 | 0.00 | 0.354494E+10 | 0.00 | 5.14 |
July | 0.948435E+09 | 0.125964E+10 | 0.00 | 27447964.56 | 0.00 | 0.00 | 0.363247E+10 | 0.00 | 5.17 |
August | 0.127910E+10 | 0.892263E+09 | 0.00 | 32421927.23 | 0.00 | 0.00 | 0.436241E+10 | 0.00 | 5.33 |
September | 0.249579E+10 | 0.274725E+09 | 0.00 | 35162839.78 | 0.00 | 0.581405E+09 | 0.472441E+10 | 0.00 | 5.44 |
October | 0.511570E+10 | 0.00 | 0.00 | 9622620.14 | 0.00 | 0.890230E+10 | 0.222735E+10 | 0.00 | 4.19 |
November | 0.396524E+10 | 0.00 | 0.00 | 2809752.04 | 0.00 | 0.140060E+11 | 0.817523E+09 | 0.00 | 3.82 |
December | 0.285251E+10 | 0.00 | 0.00 | 1338622.38 | 0.00 | 0.201633E+11 | 0.583958E+09 | 0.00 | 3.72 |
Annual Sum or Average | 0.358090E+11 | 0.355271E+10 | 0.00 | 0.162713E+09 | 0.00 | 0.107086E+12 | 0.261537E+11 | 0.00 | 4.39 |
Minimum of Months | 0.948435E+09 | 0.00 | 0.00 | 609225.55 | 0.00 | 0.00 | 0.261078E+09 | 0.00 | 3.64 |
Maximum of Months | 0.531859E+10 | 0.125964E+10 | 0.00 | 35162839.78 | 0.00 | 0.201633E+11 | 0.472441E+10 | 0.00 | 5.44 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.502494E+11 | 0.00 | 0.00 | 2283017.24 | 19697397.14 | 22990134.91 | 0.177406E+10 | 0.00 | 8.83 |
February | 0.477308E+11 | 0.00 | 0.00 | 1457941.92 | 54569622.97 | 34270525.38 | 0.115985E+10 | 0.00 | 8.88 |
March | 0.391669E+11 | 0.00 | 0.00 | 10841145.58 | 46784866.21 | 12957202.84 | 0.539532E+10 | 0.00 | 8.68 |
April | 0.349100E+11 | 0.00 | 0.00 | 12332123.20 | 3813556.54 | 11687208.66 | 0.580567E+10 | 0.00 | 8.59 |
May | 0.154491E+11 | 0.00 | 0.00 | 43813557.71 | 0.00 | 0.00 | 0.155784E+11 | 0.00 | 8.45 |
June | 0.215140E+10 | 0.108896E+10 | 0.00 | 95150949.40 | 0.00 | 0.00 | 0.142065E+11 | 0.00 | 8.95 |
July | 0.159571E+10 | 0.131661E+10 | 0.00 | 95754024.84 | 0.00 | 0.00 | 0.135626E+11 | 0.00 | 9.01 |
August | 0.181912E+10 | 0.786497E+09 | 0.00 | 0.107916E+09 | 0.00 | 0.00 | 0.163695E+11 | 0.00 | 8.94 |
September | 0.571898E+10 | 64583896.79 | 0.00 | 84626511.57 | 0.00 | 0.00 | 0.178197E+11 | 0.00 | 8.68 |
October | 0.323889E+11 | 0.00 | 0.00 | 20556845.51 | 26413827.59 | 5244715.27 | 0.903720E+10 | 0.00 | 8.55 |
November | 0.424001E+11 | 0.00 | 0.00 | 5707199.29 | 50367322.35 | 9934583.36 | 0.347491E+10 | 0.00 | 8.69 |
December | 0.553471E+11 | 0.00 | 0.00 | 2829751.63 | 38192185.04 | 38197170.84 | 0.186640E+10 | 0.00 | 8.85 |
Annual Sum or Average | 0.328928E+12 | 0.325664E+10 | 0.00 | 0.483269E+09 | 0.239839E+09 | 0.135282E+09 | 0.106050E+12 | 0.00 | 8.76 |
Minimum of Months | 0.159571E+10 | 0.00 | 0.00 | 1457941.92 | 0.00 | 0.00 | 0.115985E+10 | 0.00 | 8.45 |
Maximum of Months | 0.553471E+11 | 0.131661E+10 | 0.00 | 0.107916E+09 | 54569622.97 | 38197170.84 | 0.178197E+11 | 0.00 | 9.01 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:29:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.295058E+11 | 0.211843E+11 | 0.999605E+11 | 0.172075E+09 | 0.296312E+11 |
February | 0.380973E+11 | 0.205412E+11 | 0.938613E+11 | 91212244.52 | 0.285553E+11 |
March | 0.494225E+11 | 0.182582E+11 | 0.876180E+11 | 0.490193E+09 | 0.289774E+11 |
April | 0.530574E+11 | 0.163835E+11 | 0.802799E+11 | 0.529742E+09 | 0.270016E+11 |
May | 0.643121E+11 | 0.101477E+11 | 0.635071E+11 | 0.137569E+10 | 0.349434E+11 |
June | 0.697865E+11 | 0.283429E+10 | 0.342650E+11 | 0.154771E+10 | 0.741214E+11 |
July | 0.647067E+11 | 0.238323E+10 | 0.316622E+11 | 0.158600E+10 | 0.776441E+11 |
August | 0.634932E+11 | 0.337646E+10 | 0.379664E+11 | 0.199439E+10 | 0.737742E+11 |
September | 0.467069E+11 | 0.583426E+10 | 0.494258E+11 | 0.217248E+10 | 0.545889E+11 |
October | 0.378244E+11 | 0.157374E+11 | 0.830380E+11 | 0.985611E+09 | 0.288389E+11 |
November | 0.318031E+11 | 0.186828E+11 | 0.894809E+11 | 0.375081E+09 | 0.269877E+11 |
December | 0.234914E+11 | 0.238819E+11 | 0.108564E+12 | 0.241444E+09 | 0.318474E+11 |
Annual Sum or Average | 0.572207E+12 | 0.159245E+12 | 0.859629E+12 | 0.115616E+11 | 0.516911E+12 |
Minimum of Months | 0.234914E+11 | 0.238323E+10 | 0.316622E+11 | 91212244.52 | 0.269877E+11 |
Maximum of Months | 0.697865E+11 | 0.238819E+11 | 0.108564E+12 | 0.217248E+10 | 0.776441E+11 |