Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:30:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1180.61 | 5081.31 | 5081.31 |
Net Site Energy | 1180.61 | 5081.31 | 5081.31 |
Total Source Energy | 2349.53 | 10112.35 | 10112.35 |
Net Source Energy | 2349.53 | 10112.35 | 10112.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 120.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 20.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 65.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 169.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 39.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 513.56 | 667.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 120.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 20.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 9.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 65.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 169.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 12.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 18.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 120.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 20.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252.09 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 65.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 169.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 39.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 802.14 | 817.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1253.37 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2210.37 | 2870.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 802.14 | 817.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1253.37 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 2210.37 | 2870.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 513.565 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 513.565 | 100.00 |
Total On-Site and Utility Electric Sources | 513.565 | 100.00 |
Total Electricity End Uses | 513.565 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 5.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4868.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:30 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 4.1965 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 8.9582 | 18.52 | 1067.3199 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 6.5774 | 2.48 | 592.0534 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 4.1965 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 8.9582 | 18.52 | 1067.3199 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Conditioned Total | 232.34 | 6.5774 | 1.24 | 592.0534 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 6.5774 | 2.48 | 592.0534 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUN-17:10 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:20 |
Heating | 0.00 | 35453.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 21230.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 11387.73 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4053.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7246.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1169.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 38747.98 | 56489.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 35453.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 21230.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 907.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 10796.93 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4053.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7246.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 373.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 601.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 22.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 382.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 65.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 48.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 798.38 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 183.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 123.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1626.46 | 723.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 96.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1645.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 894.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 789.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 533.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7000.26 | 3112.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 96.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1645.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 209.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3436.21 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 894.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 789.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 533.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 7000.26 | 3112.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.88 |
KITCHEN DIRECT AIR | 1.30 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.88 | 2.88 | 2.88 | 2.88 | 2.88 | 2.88 | 1.00 | 1.00 | 2.88 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.30 | 1.00 | 1.00 | 1.30 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.88 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.30 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.88 | 3082.74 |
PSZ-AC_2:2_ADDAQ FAN | 1.30 | 1438.10 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.88 | 2.88 | 2.88 | 1.90 | 52035.27 | 69201.48 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.30 | 1.30 | 1.30 | 0.857278 | 32254.94 | 56447.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.88 | 1.44 | 1.92 | 52035.27 | 26017.63 | 0.800950 | 0.800950 |
PSZ-AC_2:2 COOLING COIL | 1.30 | 0.649453 | 0.865940 | 32254.94 | 16127.47 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 69201.48 |
PSZ-AC_2:2 HEATING COIL | 56447.36 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 4.196 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 120.983 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 8.958 | 275.967 | 791.353 | 0.000 | 0.000 | 0.000 | 1076.278 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 487.511 | 4.196 | 5.569 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 487.511 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1040.691 | 8.958 | 165.892 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1040.691 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 277.500 | 2.389 | 44.235 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 313.300 | 2.697 | 49.942 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 313.300 | 313.300 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1579 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.9479 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3496 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.235 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8209 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.784 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.22189424E-16 | 0.18036394E-15 | 0.14382820E-13 | -0.35882886E-16 |
24 | 3 | -0.84544447E-08 | 0.11431503E-06 | -0.59212216E-04 | 0.16308097E-12 |
25 | 2 | 0.59356505E-04 | 0.24350950E-02 | 1.1796048 | -0.77969909E-04 |
26 | 1 | -0.55627393E-01 | 0.62087406E-01 | -17.347049 | 0.34328241 |
27 | 0 | 0.15925904 | 0.39168381E-01 | 16.271195 | |
28 | 4 | 0.14382820E-13 | 0.18036394E-15 | 0.22189424E-16 | -0.35882886E-16 |
29 | 3 | -0.59212216E-04 | 0.11431503E-06 | -0.84544447E-08 | 0.16308097E-12 |
30 | 2 | 1.1796048 | 0.24350950E-02 | 0.59356505E-04 | -0.77969909E-04 |
31 | 1 | -17.347049 | 0.62087406E-01 | -0.55627393E-01 | 0.34328241 |
32 | 0 | 16.271195 | 0.39168381E-01 | 0.15925904 | |
33 | 7 | -0.27625978E-12 | 0.12794163E-14 | -0.83972413E-13 | 0.81972452E-16 |
34 | 6 | 0.26625806E-07 | 0.26068043E-09 | 0.61165175E-08 | -0.12424864E-12 |
35 | 5 | -0.17966720E-03 | 0.22611036E-05 | -0.92543806E-04 | 0.60523213E-08 |
36 | 4 | 0.27985034 | 0.11135995E-02 | 0.95264974E-01 | -0.31844321E-04 |
37 | 3 | -7.0226191 | 0.34861830E-01 | -2.2666100 | 0.27815218E-01 |
38 | 2 | 40.067174 | 0.12507266 | 14.968070 | -0.32438733 |
39 | 1 | -79.929480 | 0.56884474E-01 | -28.875252 | 1.0654859 |
40 | 0 | 46.824343 | 0.11531802E-02 | 16.297708 | |
41 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
42 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
43 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
44 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
45 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
46 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
47 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
48 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 | |
49 | 7 | -0.11889135E-08 | -0.13101661E-15 | 0.72805024E-14 | -0.91252007E-16 |
50 | 6 | 0.97710136E-05 | 0.67347286E-08 | 0.31779875E-02 | -0.26659623E-04 |
51 | 5 | -0.70792317E-03 | 0.39963827E-05 | -0.22304912 | 0.19501884E-02 |
52 | 4 | 0.16314426E-01 | 0.18199987E-03 | 4.8182940 | -0.45156824E-01 |
53 | 3 | -0.14334616 | 0.14483103E-02 | -37.957847 | 0.39795111 |
54 | 2 | 0.50909124 | 0.24102133E-02 | 116.36021 | -1.4162842 |
55 | 1 | -0.73485211 | 0.73528917E-03 | -143.83447 | 2.0478426 |
56 | 0 | 0.35828816 | 0.17591693E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4532_SHGC_SOUTH_0.25 | 38 | 1 | VerySmooth | 2.576 | 2.576 | 1.000 | 0.251 | ||
2 | NONRESWINDOW_U_0.4532_SHGC_NORTH_0.25 | 39 | 1 | VerySmooth | 2.576 | 2.576 | 1.000 | 0.251 | ||
3 | NONRESWINDOW_U_0.4532_SHGC_EAST_0.25 | 40 | 1 | VerySmooth | 2.576 | 2.576 | 1.000 | 0.251 | ||
4 | NONRESWINDOW_U_0.4532_SHGC_WEST_0.25 | 41 | 1 | VerySmooth | 2.576 | 2.576 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.62661E-002 | 0.16139 | 0.61689 | 0.61689 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12093 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.62661E-002 | 0.16139 | 0.61689 | 0.61689 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12093 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.62661E-002 | 0.16139 | 0.61689 | 0.61689 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12093 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.62661E-002 | 0.16139 | 0.61689 | 0.61689 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12093 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.052 | 0.3089 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 1.323E-002 | 1.139E-004 | 1.424E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.903 | 7.772E-003 | 9.714E-003 | 9.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 1.323E-002 | 1.139E-004 | 1.395E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.5114E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.1508E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.3780E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.0228E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.2652E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.2157E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 9.9595E-004 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 9.8974E-003 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.1658E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.0889E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.7181E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.6253E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.8860E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.8472E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.0717E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.0717E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0255E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.3679E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 8.7263E-003 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1998E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.0537E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.1244E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 9.8988E-003 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 9.9596E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 29712.41565 | 35654.89878 | 2.40078 | 2.88094 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 3711.37524 | 4453.65029 | 0.17254 | 0.41606 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 0.50000 | 4.31558E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16060.96386 | 19273.15663 | 1.08242 | 1.29891 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 39.60300 | 5.62924E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | 00:10:00 | 0.50000 | 4.31558E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 42831.13 | 2.88094 | 2.88094 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 18053.08 | 0.41606 | 0.41606 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 35898.63 | 1.29891 | 1.29891 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 49523.57 | 1.14133 | 1.14133 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.88094 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.29891 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88094 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.88094 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.88094 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.88094 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.88094 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.88094 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.29891 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.29891 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.29891 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29891 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.29891 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.29891 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.88094 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.29891 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.88094 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.88094 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 3082.73980 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.88094 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.88094 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.88094 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.90142 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.88094 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.44047 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.92063 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 52035.27000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 26017.63500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80095 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80095 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 52035.27000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 69201.48381 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 69201.48381 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.29891 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.29891 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1438.09573 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.29891 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.29891 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.29891 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.85728 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.29891 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64945 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.86594 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32254.94000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16127.47000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32254.94000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56447.36375 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 56447.36375 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 49938.5 | 11.05 | 11.00 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 31331.7 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4532_SHGC_EAST_0.25 | N/A | 2.576 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4532_SHGC_SOUTH_0.25 | N/A | 2.576 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4532_SHGC_WEST_0.25 | N/A | 2.576 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.948 | 0.830 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.350 | 0.322 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.158 | 0.153 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.158 | 0.152 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.9830979722E-002 | 0.2260240930 | Pass | Pass | 0.3232094953 | 0.9869323929 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.2271483114 | 0.6570462920 | Pass | Pass | 2.5646044527E-002 | 8.5279458676E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.5056466926 | 0.4977055709 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 583.07 | 29.00 | 400.30 | 13.43 | 846.53 | 1872.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.830 | 0.948 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.331 | 0.350 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.151 | 0.158 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4532_SHGC_EAST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.576 | 0.251 | 0.251 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4532_SHGC_SOUTH_0.25 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.576 | 0.251 | 0.251 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.4532_SHGC_WEST_0.25 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.576 | 0.251 | 0.251 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.576 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.576 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 4.1965 | 116.17 | 487.51 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 45.98 | 0.0000 | Y | 4.21 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 8.9582 | 116.17 | 1040.69 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 83.95 | 0.0000 | Y | 16.40 |
Interior Lighting Total | 6.5774 | 232.34 | 1528.20 | 20.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 487.51 | 185.25 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 166.91 | AstronomicalClock | - | 48.79 | 48.79 | 1.53 | |
EXTERIOR_LIGHTS_B | 1174.86 | AstronomicalClock | - | 83.79 | 62.79 | 13.85 | |
Exterior Lighting Total | 1341.77 | 15.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 52035.27 | 41677.65 | 10357.62 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32254.94 | 22613.29 | 9641.65 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 49938.5 | 11.05 | 11.00 | ||||
PSZ-AC_2:2 COOLING COIL | 31331.7 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 69201.48 | 0.81 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 56447.36 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.88 | 3082.74 | 1070.05 | 1.00 | 1.27 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.30 | 1438.10 | 1107.16 | 1.00 | 1.34 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 29712.42 | 35654.90 | 306.92 | 2.401 | 2.881 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00835 | 40.80 | 0.00563 | 0.416 | 0.00 |
KITCHEN | 16060.96 | 19273.16 | 165.90 | 1.082 | 1.299 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01021 | 39.60 | 0.00563 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 3711.38 | 4453.65 | 38.34 | 0.173 | 0.416 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00793 | 0.50 | 0.00432 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | 00:10:00 | 15.56 | 21.79 | 0.00187 | 0.50 | 0.00432 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.88 | 2.88 | 0.42 | 0.42 | 2.8809 | 2.8809 | 2.8809 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.30 | 1.30 | 1.14 | 1.14 | 1.2989 | 1.2989 | 1.2989 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 52035.270 | 41677.650 | 2.880940 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 26017.63 | 26017.63 | 1.920627 | 26.33 | 15.75 | 0.00795884 | 11.84 | 10.30 | 0.00795884 | 40.80 | 0.00563111 | 18.58 | 21.6625 | 23.89 | 0.00835174 | 41.0909 | 29712.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 69201.484 | 69201.484 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 69201.48 | 69201.48 | 2.880938 | 18.13 | 12.30 | 0.00742341 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 14.4417 | 20.37 | 0.00794799 | 48.5096 | 2068.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 32254.940 | 22613.293 | 1.298910 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 16127.47 | 16127.47 | 0.865940 | 37.96 | 18.12 | 0.00618533 | 11.80 | 8.44 | 0.00618533 | 39.60 | 0.00562924 | 18.21 | 131.8028 | 26.10 | 0.01021314 | 43.9289 | 16060.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 56447.364 | 56447.364 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 56447.36 | 56447.36 | 1.298907 | 0.44 | 0.05 | 0.00401926 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 87.8688 | 21.79 | 0.00187293 | 10.5774 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 52035.270 | 41677.650 | 2.880940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6351 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.880938 | 3.14942471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 26017.63 | 26017.63 | 1.0000 | 2.09961796 | 1.920627 | 26.33 | 15.75 | 0.00795884 | 46755.6 | 11.84 | 10.30 | 0.00795884 | 31977.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26017.63 | 40.80 | 0.00563111 | 18.58 | 0.41605618 | 21.6625 | 23.89 | 0.00835174 | 23.89 | 0.00835174 | 41.0909 | 29712.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 69201.484 | 69201.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.880938 | 3.14942471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 69201.48 | 69201.48 | 1.0000 | 3.14942471 | 2.880938 | 18.13 | 12.30 | 0.00742341 | 37037.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69201.48 | 0.50 | 0.00431558 | 0.50 | 0.41605618 | 14.4417 | 21.11 | 0.00794799 | 20.37 | 0.00794799 | 48.5096 | 2068.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32254.940 | 22613.293 | 1.298910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.3382 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.298907 | 1.41995712 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 16127.47 | 16127.47 | 1.0000 | 0.94664060 | 0.865940 | 37.96 | 18.12 | 0.00618533 | 54048.6 | 11.80 | 8.44 | 0.00618533 | 27465.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16127.47 | 39.60 | 0.00562924 | 18.21 | 1.14133354 | 131.8028 | 26.05 | 0.01021314 | 26.10 | 0.01021314 | 43.9289 | 16060.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56447.364 | 56447.364 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.298907 | 1.41995712 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 56447.36 | 56447.36 | 1.0000 | 1.41995712 | 1.298907 | 0.44 | 0.05 | 0.00401926 | 10496.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56447.36 | 0.50 | 0.00431558 | 0.50 | 1.14133354 | 87.8688 | 0.00 | 0.00187293 | 21.79 | 0.00187293 | 10.5774 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.88 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.30 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3505.17 | 2579.67 | 467.83 |
KITCHEN | 6056.00 | 5735.17 | 4842.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 6081.33 | 6886.33 | 4868.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 0.00 | 9.50 | 0.00 | 0.00 |
KITCHEN | 0.00 | 205.33 | 0.00 | 5.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 214.83 | 0.00 | 5.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.595 | 4.158 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.392 | 0.006 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.177 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.563 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 14319007.08 | 0.00 | 14319007.08 | 10416307.40 | 24735314.49 | 13120747.55 | 1443.54 | 5881.72 | 1434.74 | 187.68 |
KITCHEN | 24300788.60 | 0.00 | 24300788.60 | 25927.37 | 24326715.97 | 35993094.65 | 8251.34 | 505.18 | 3.48 | 643.53 |
Total Facility | 38619795.69 | 0.00 | 38619795.69 | 10442234.77 | 49062030.46 | 49113842.20 | 8252.20 | 5881.92 | 1436.85 | 684.49 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5409 | 0.0000 | 0.5409 | 0.4022 | 0.9431 | 0.4161 | 0.00 | 5801.74 | 1385.26 |
KITCHEN | 0.9015 | 0.0000 | 0.9015 | 0.0006 | 0.9021 | 1.1413 | 6680.01 | 504.99 | 2.01 |
Total Facility | 1.4424 | 0.0000 | 1.4424 | 0.4028 | 1.8451 | 1.5574 | 6680.01 | 5801.75 | 1386.39 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17112287.43 | 0.00 | 17112287.43 | 13120747.55 | 1442.89 | 0.02 | 7317.09 | 187.48 |
PSZ-AC_2:2 | 29039374.11 | 0.00 | 29039374.11 | 35993094.65 | 7397.50 | 110.98 | 1251.52 | 643.53 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6464 | 0.0000 | 0.6464 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.0773 | 0.0000 | 1.0773 | 1.1413 | 5828.44 | 110.86 | 1247.70 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 791.78 | 706.34 | 5876.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 404.47 | 1323.95 | 6102.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.5912 | 0.9356 | 0.4973 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0419 | 1.1924 | 1.0603 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 374 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
Electricity:Building | 280.64 | 1825.29 | 01-JAN-01:10 | 17838.45 | 02-JAN-11:10 |
Electricity:Zone:DINING | 74.54 | 336.73 | 01-JAN-01:10 | 4026.33 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 272.70 | 1689.01 | 01-JAN-01:10 | 14544.40 | 02-JAN-11:10 |
InteriorLights:Electricity | 20.61 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:30 |
InteriorLights:Electricity:Zone:DINING | 4.21 | 32.03 | 01-JAN-08:00 | 400.32 | 02-JAN-17:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 20.61 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity | 20.61 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 4.21 | 32.03 | 01-JAN-08:00 | 400.32 | 02-JAN-17:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 20.61 | 201.93 | 01-JAN-01:10 | 1211.55 | 02-JAN-17:30 |
Electricity:Zone:KITCHEN | 206.10 | 1488.56 | 01-JAN-01:10 | 13812.12 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 16.40 | 135.21 | 01-JAN-01:10 | 811.23 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 252.09 | 1487.08 | 01-JAN-01:10 | 13637.09 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 181.76 | 1217.07 | 01-JAN-01:10 | 9706.84 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 9.88 | 313.30 | 01-JAN-00:10 | 313.30 | 01-JAN-00:10 |
Refrigeration:Electricity | 39.12 | 583.58 | 07-DEC-23:30 | 3931.14 | 14-JUL-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 31.18 | 497.80 | 07-DEC-23:30 | 1652.86 | 28-APR-03:20 |
LowTempRefrigeration:Refrigeration:Electricity | 12.31 | 0.00 | 01-JAN-11:10 | 1015.77 | 28-APR-03:20 |
MedTempRefrigeration:Refrigeration:Electricity | 18.86 | 475.34 | 07-DEC-01:10 | 637.09 | 08-JAN-14:30 |
ElectricityPurchased:Facility | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
ElectricityPurchased:Plant | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
Cogeneration:ElectricityPurchased | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
General:Cogeneration:ElectricityPurchased | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
ElectricityNet:Plant | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
Cogeneration:ElectricityNet | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
General:Cogeneration:ElectricityNet | 513.56 | 3081.61 | 07-DEC-01:10 | 38747.98 | 28-JUN-17:10 |
Electricity:HVAC | 186.37 | 0.00 | 01-JAN-01:10 | 25283.90 | 28-JUN-17:10 |
Fans:Electricity | 65.65 | 0.00 | 01-JAN-01:10 | 4053.33 | 28-JUN-17:10 |
General:Fans:Electricity | 65.65 | 0.00 | 01-JAN-01:10 | 4053.33 | 28-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 120.72 | 0.00 | 01-JAN-00:10 | 21230.57 | 28-JUN-17:10 |
General:Cooling:Electricity | 120.72 | 0.00 | 01-JAN-00:10 | 21230.57 | 28-JUN-17:10 |
ExteriorLights:Electricity | 15.38 | 0.00 | 01-JAN-07:30 | 1341.77 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.38 | 0.00 | 01-JAN-07:30 | 1341.77 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-10:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-10:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 667.04 | 2560.65 | 07-JAN-01:10 | 56489.99 | 06-DEC-07:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 20.74 | 0.00 | 01-JAN-00:10 | 35453.87 | 06-DEC-07:10 |
Heating:NaturalGas | 20.74 | 0.00 | 01-JAN-00:10 | 35453.87 | 06-DEC-07:10 |
General:Heating:NaturalGas | 20.74 | 0.00 | 01-JAN-00:10 | 35453.87 | 06-DEC-07:10 |
NaturalGas:Plant | 169.14 | 722.00 | 07-JAN-01:10 | 25346.09 | 23-JAN-13:40 |
WaterSystems:NaturalGas | 169.14 | 722.00 | 07-JAN-01:10 | 25346.09 | 23-JAN-13:40 |
Water Heater:WaterSystems:NaturalGas | 169.14 | 722.00 | 07-JAN-01:10 | 25346.09 | 23-JAN-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUL-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1140.64 | 2416.91 | 07-DEC-01:10 | 119599.49 | 19-JUL-13:00 |
EnergyTransfer:Building | 491.44 | 1208.45 | 07-DEC-01:10 | 39781.65 | 28-JUN-11:10 |
EnergyTransfer:Zone:KITCHEN | 326.11 | 1208.45 | 07-DEC-01:10 | 20348.69 | 21-APR-04:10 |
Refrigeration:EnergyTransfer | 149.85 | 2416.91 | 07-DEC-01:10 | 7834.84 | 20-JAN-04:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 74.93 | 1208.45 | 07-DEC-01:10 | 3917.42 | 20-JAN-04:50 |
General:Refrigeration:EnergyTransfer | 74.93 | 1208.45 | 07-DEC-01:10 | 3917.42 | 20-JAN-04:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 74.93 | 1208.45 | 07-DEC-01:10 | 3917.42 | 20-JAN-04:50 |
EnergyTransfer:Plant | 185.09 | 1208.45 | 07-DEC-01:10 | 18435.90 | 21-JAN-13:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.28 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 61.65 | 1059.56 | 07-DEC-01:10 | 2238.70 | 08-JAN-14:30 |
EnergyTransfer:Zone:DINING | 165.33 | 0.00 | 01-JAN-01:10 | 24525.26 | 28-JUN-17:10 |
Heating:EnergyTransfer | 3.11 | 0.00 | 01-JAN-00:10 | 9329.01 | 26-MAR-06:10 |
Heating:EnergyTransfer:Zone:DINING | 3.10 | 0.00 | 01-JAN-00:10 | 9329.01 | 26-MAR-06:10 |
General:Heating:EnergyTransfer | 3.11 | 0.00 | 01-JAN-00:10 | 9329.01 | 26-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:DINING | 3.10 | 0.00 | 01-JAN-00:10 | 9329.01 | 26-MAR-06:10 |
Cooling:EnergyTransfer | 413.40 | 0.00 | 01-JAN-01:10 | 36004.48 | 28-JUN-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 162.24 | 0.00 | 01-JAN-01:10 | 24525.26 | 28-JUN-17:10 |
General:Cooling:EnergyTransfer | 413.40 | 0.00 | 01-JAN-01:10 | 36004.48 | 28-JUN-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 162.24 | 0.00 | 01-JAN-01:10 | 24525.26 | 28-JUN-17:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 700.22 | 13-AUG-23:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 700.22 | 13-AUG-23:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 251.17 | 0.00 | 01-JAN-01:10 | 16441.25 | 21-APR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 251.17 | 0.00 | 01-JAN-01:10 | 16441.25 | 21-APR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
PlantLoopHeatingDemand:Plant | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
WaterSystems:PlantLoopHeatingDemand | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
General:WaterSystems:PlantLoopHeatingDemand | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
EnergyTransfer:HVAC | 464.11 | 0.00 | 01-JAN-00:10 | 68576.80 | 21-JUL-11:10 |
HeatingCoils:EnergyTransfer | 16.77 | 0.00 | 01-JAN-00:10 | 28566.43 | 06-DEC-07:10 |
CoolingCoils:EnergyTransfer | 447.33 | 0.00 | 01-JAN-00:10 | 68576.80 | 21-JUL-11:10 |
WaterSystems:EnergyTransfer | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
WaterUse:WaterSystems:EnergyTransfer | 110.17 | 0.00 | 01-JAN-00:10 | 15968.58 | 22-JAN-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 3.096 | -162.234 | 0.000 | 0.000 | 67.245 | 4.207 | 52.748 | 27.496 | 0.000 | 41.752 | 11.571 | 0.000 | -7.875 | 0.000 | -38.006 | -0.000 |
KITCHEN | 0.000 | 0.000 | 0.017 | -251.159 | 0.000 | 0.000 | 4.187 | 16.400 | 187.472 | 0.000 | 0.000 | 0.046 | 43.237 | 0.000 | 0.000 | 0.000 | -0.200 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.784 | 10.939 | 0.000 | 0.000 | 0.000 | -15.722 | -0.000 |
Total Facility | 0.000 | 0.000 | 3.113 | -413.393 | 0.000 | 0.000 | 71.432 | 20.607 | 240.220 | 27.496 | 0.000 | 46.582 | 65.747 | 0.000 | -7.875 | 0.000 | -53.928 | -0.001 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-JUL-03:01 | 0.00 | 0.00 | 0.00 | -35541.81 | 0.00 | 0.00 | 0.00 | 66.72 | 506.27 | 0.00 | 0.00 | 0.00 | 35482.37 | 0.00 | -507.88 | 0.00 | -5.67 | 0.00 |
KITCHEN | 21-APR-04:01 | 0.00 | 0.00 | 0.00 | -47626.15 | 0.00 | 0.00 | 8.50 | 180.28 | 4494.65 | 0.00 | 0.00 | 0.00 | 42947.82 | 0.00 | -0.00 | 0.00 | -5.10 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-OCT-04:01 | 0.00 | 0.00 | 0.00 | -63770.17 | 0.00 | 0.00 | 272.23 | 269.24 | 5714.39 | 0.00 | 0.00 | 448.07 | 57858.39 | 0.00 | -778.50 | 0.00 | -13.65 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 26-MAR-06:10 | 0.00 | 0.00 | 9330.53 | 0.00 | 0.00 | 0.00 | 3600.12 | 133.44 | 1524.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1163.04 | 0.00 | -12047.75 | -1377.95 |
KITCHEN | 20-JUL-23:01 | 0.00 | 0.00 | 4695.49 | 0.00 | 0.00 | 0.00 | 16.72 | 135.21 | 1566.76 | 0.00 | 0.00 | 3.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6417.36 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-MAR-06:10 | -7373.39 | 7373.39 | 9330.53 | -7373.39 | 0.00 | 0.00 | 3884.71 | 403.85 | 6995.28 | 0.00 | 0.00 | 415.39 | 0.00 | 0.00 | -1163.04 | 0.00 | -12059.54 | -433.79 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8809 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.8809 | 0.1444 | 1.0000 | Not calculated | 0.4161 | 0.1444 | ||
PSZ-AC_2:2 | 1.2989 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2989 | 0.1165 | 1.0000 | Not calculated | 0.1513 | 0.1165 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.8809 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.8809 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.1444 | ||
PSZ-AC_2:2 | 1.2989 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2989 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1165 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8809 | 2.8809 | 2.8809 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2989 | 1.2989 | 1.2989 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8809 | 2.8809 | 2.8809 | 2.8809 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2989 | 1.2989 | 1.2989 | 1.2989 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.8809 | 2.8809 | 2.8809 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2989 | 1.2989 | 1.2989 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.8809 | 2.8809 | 2.8809 | 2.8809 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2989 | 1.2989 | 1.2989 | 1.2989 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 5.00 |
Number of hours not met | 5.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 20.74 | 35453.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 120.72 | 21230.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 20.61 | 1211.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.38 | 1341.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 9.88 | 313.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 65.65 | 4053.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 169.14 | 25346.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 12.31 | 1015.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 18.86 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 291.21 | 513.56 |
Natural Gas | 477.16 | 667.04 |
Additional | 0.00 | 0.00 |
Total | 768.37 | 1180.61 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 88.69 |
Space Heating | 0.00 |
Space Cooling | 519.56 |
Fans (All) | 282.57 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1085.00 |
Miscellaneous (All) | 2210.37 |
Subtotal | 2210.37 |
Natural Gas [MJ/m2] | |
Space Heating | 89.28 |
Service Water Heating | 727.97 |
Miscellaneous (All) | 2870.93 |
Subtotal | 2870.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.75 |
Space Heating | 1.76 |
Space Cooling | 10.22 |
Fans (All) | 5.56 |
Service Water Heating | 14.33 |
Receptacle Equipment | 61.77 |
Miscellaneous | 4.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | DINING DUAL SP CONTROL | July | 23.89 | 365 | 25.00 | 365 |
HTGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_YES_OPTIMUM_STARTSTOP | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 27.22 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8448.00 | 312.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 7484.50 | 1270.83 | 4.67 | 0.00 | 0.00 |
ATTIC | 5258.17 | 916.83 | 890.50 | 1364.50 | 330.00 |
Min | 5258.17 | 312.00 | 0.00 | 0.00 | 0.00 |
Max | 8448.00 | 1270.83 | 890.50 | 1364.50 | 330.00 |
Average | 7063.56 | 833.22 | 298.39 | 454.83 | 110.00 |
Sum | 21190.67 | 2499.67 | 895.17 | 1364.50 | 330.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254423.67 | 301.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16175.50 | 82.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254423.67 | 301.33 | 0.00 | 0.00 | 0.00 |
Average | 90199.72 | 127.94 | 0.00 | 0.00 | 0.00 |
Sum | 270599.17 | 383.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8272.33 | 487.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6712.83 | 2047.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 5411.67 | 1483.67 | 446.17 | 368.33 | 1050.17 |
Min | 5411.67 | 487.67 | 0.00 | 0.00 | 0.00 |
Max | 8272.33 | 2047.17 | 446.17 | 368.33 | 1050.17 |
Average | 6798.94 | 1339.50 | 148.72 | 122.78 | 350.06 |
Sum | 20396.83 | 4018.50 | 446.17 | 368.33 | 1050.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 249660.00 | 5065.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 13027.67 | 3230.33 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 249660.00 | 5065.00 | 0.00 | 0.00 | 0.00 |
Average | 87562.56 | 2765.11 | 0.00 | 0.00 | 0.00 |
Sum | 262687.67 | 8295.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:30:01
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.661285E+10 | 10963.09 | 31-JAN-14:00 | 28.00 | 11.03 | 0.505243E+10 | 4680.94 | 14-JAN-19:19 | 28.00 | 11.03 |
February | 0.306601E+10 | 6278.81 | 01-FEB-05:01 | 5.00 | 3.59 | 0.428643E+10 | 4413.05 | 16-FEB-12:00 | 19.00 | 13.01 |
March | 0.600582E+10 | 11734.12 | 20-MAR-17:05 | 28.53 | 14.26 | 0.511784E+10 | 4681.01 | 18-MAR-18:00 | 28.53 | 14.26 |
April | 0.144799E+11 | 31188.74 | 25-APR-03:01 | 24.00 | 12.37 | 0.521913E+10 | 4681.02 | 15-APR-18:00 | 24.00 | 12.37 |
May | 0.180144E+11 | 32631.13 | 08-MAY-03:01 | 22.83 | 10.14 | 0.544582E+10 | 4681.01 | 06-MAY-18:10 | 22.83 | 10.14 |
June | 0.235288E+11 | 34261.48 | 14-JUN-03:01 | 21.67 | 8.99 | 0.530541E+10 | 4681.16 | 17-JUN-18:00 | 37.00 | 20.23 |
July | 0.229596E+11 | 35549.23 | 04-JUL-03:01 | 21.00 | 8.68 | 0.542597E+10 | 4681.87 | 08-JUL-18:00 | 27.00 | 20.01 |
August | 0.227003E+11 | 35043.40 | 25-AUG-03:01 | 21.17 | 9.25 | 0.548544E+10 | 4681.25 | 19-AUG-18:10 | 21.17 | 9.25 |
September | 0.200018E+11 | 34251.71 | 17-SEP-03:01 | 22.20 | 12.79 | 0.527161E+10 | 4681.60 | 02-SEP-18:10 | 22.20 | 12.79 |
October | 0.132056E+11 | 31623.03 | 07-OCT-03:01 | 22.83 | 14.44 | 0.530275E+10 | 4681.44 | 21-OCT-18:49 | 22.00 | 14.16 |
November | 0.702167E+10 | 18699.26 | 02-NOV-04:01 | 15.17 | 11.52 | 0.492039E+10 | 4680.96 | 04-NOV-18:10 | 16.67 | 7.72 |
December | 0.463878E+10 | 9139.45 | 22-DEC-14:00 | 25.00 | 10.09 | 0.483092E+10 | 4680.82 | 02-DEC-19:40 | 25.00 | 10.09 |
Annual Sum or Average | 0.162236E+12 | 0.616641E+11 | ||||||||
Minimum of Months | 0.306601E+10 | 6278.81 | 5.00 | 3.59 | 0.428643E+10 | 4413.05 | 16.67 | 7.72 | ||
Maximum of Months | 0.235288E+11 | 35549.23 | 28.53 | 14.44 | 0.548544E+10 | 4681.87 | 37.00 | 20.23 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195633E+11 | 35788.50 | 07-JAN-05:01 | 14.00 | 8.28 | 0.781777E+10 | 5135.94 | 09-JAN-11:00 | 17.00 | 11.36 |
February | 0.175840E+11 | 28364.77 | 10-FEB-04:42 | 15.17 | 8.39 | 0.703563E+10 | 5135.96 | 17-FEB-11:00 | 18.00 | 14.26 |
March | 0.191648E+11 | 41568.92 | 21-MAR-04:01 | 15.22 | 8.64 | 0.782630E+10 | 5135.96 | 17-MAR-10:30 | 15.22 | 8.64 |
April | 0.200682E+11 | 47642.49 | 21-APR-04:01 | 8.00 | 0.42 | 0.760179E+10 | 5135.94 | 07-APR-10:00 | 8.00 | 0.42 |
May | 0.212685E+11 | 33052.77 | 11-MAY-04:01 | 22.00 | 12.62 | 0.786066E+10 | 5135.93 | 11-MAY-10:00 | 29.00 | 12.81 |
June | 0.221636E+11 | 41293.58 | 16-JUN-04:01 | 22.00 | 10.26 | 0.761098E+10 | 5135.94 | 30-JUN-10:50 | 35.67 | 19.30 |
July | 0.234442E+11 | 35788.78 | 04-JUL-04:01 | 20.83 | 8.39 | 0.785932E+10 | 5135.94 | 14-JUL-10:50 | 29.00 | 20.34 |
August | 0.234920E+11 | 37396.24 | 25-AUG-04:01 | 22.00 | 10.03 | 0.786477E+10 | 5135.94 | 03-AUG-10:00 | 22.00 | 10.03 |
September | 0.226034E+11 | 35937.78 | 19-SEP-04:01 | 26.10 | 12.72 | 0.760767E+10 | 5135.97 | 21-SEP-10:20 | 24.20 | 17.44 |
October | 0.216747E+11 | 46999.10 | 27-OCT-04:01 | 12.83 | 4.70 | 0.784635E+10 | 5135.96 | 23-OCT-10:00 | 12.83 | 4.70 |
November | 0.200092E+11 | 47352.07 | 10-NOV-05:01 | 12.33 | 5.33 | 0.757206E+10 | 5135.99 | 03-NOV-10:00 | 12.33 | 5.33 |
December | 0.201299E+11 | 31101.61 | 26-DEC-04:42 | 8.00 | 2.80 | 0.778582E+10 | 5135.93 | 27-DEC-11:00 | 18.00 | 8.61 |
Annual Sum or Average | 0.251166E+12 | 0.922891E+11 | ||||||||
Minimum of Months | 0.175840E+11 | 28364.77 | 8.00 | 0.42 | 0.703563E+10 | 5135.93 | 8.00 | 0.42 | ||
Maximum of Months | 0.234920E+11 | 47642.49 | 26.10 | 12.72 | 0.786477E+10 | 5135.99 | 35.67 | 20.34 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 | 1.81 | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 | 1.81 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 | 4.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 | 8.83 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 | 7.34 | 0.00 | 0.00 | 01-APR-00:10 | 15.28 | 7.34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 | 7.18 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 25.83 | 11.09 | 0.00 | 0.00 | 01-JUN-00:10 | 25.83 | 11.09 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 27.73 | 14.60 | 0.00 | 0.00 | 01-JUL-00:10 | 27.73 | 14.60 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 29.40 | 18.35 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.35 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 26.22 | 16.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 | 16.66 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 25.15 | 15.51 | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 | 15.51 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 | 10.27 | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 | 10.27 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 | 2.98 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.27 | 1.81 | 0.00 | 0.00 | 4.27 | 1.81 | ||
Maximum of Months | 0.00 | 0.00 | 29.40 | 18.35 | 0.00 | 0.00 | 29.40 | 18.35 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329231E+09 | 9006.76 | 01-JAN-08:00 | 0.50 |
February | 0.505225E+09 | 4894.32 | 25-FEB-07:10 | 6.50 |
March | 0.442758E+09 | 9329.01 | 26-MAR-06:10 | 0.78 |
April | 5471555.01 | 5874.59 | 15-APR-03:05 | 23.00 |
May | 14748211.45 | 1845.10 | 07-MAY-23:01 | 28.00 |
June | 0.117014E+09 | 4115.70 | 03-JUN-03:44 | 22.17 |
July | 0.107771E+09 | 3499.78 | 20-JUL-23:01 | 32.83 |
August | 82641701.35 | 3030.67 | 18-AUG-04:02 | 26.83 |
September | 29835937.16 | 2923.62 | 19-SEP-04:02 | 26.10 |
October | 45026334.39 | 2791.22 | 25-OCT-06:30 | 5.00 |
November | 0.215558E+09 | 7984.40 | 23-NOV-07:10 | 0.33 |
December | 0.120072E+10 | 8753.80 | 17-DEC-07:10 | 1.17 |
Annual Sum or Average | 0.309600E+10 | |||
Minimum of Months | 5471555.01 | 1845.10 | 0.33 | |
Maximum of Months | 0.120072E+10 | 9329.01 | 32.83 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 52921.43 | 617.42 | 07-MAY-23:01 | 28.00 |
June | 5354821.96 | 4681.55 | 29-JUN-23:01 | 32.83 |
July | 5783230.10 | 4695.36 | 20-JUL-23:01 | 32.83 |
August | 4449114.28 | 3140.94 | 13-AUG-23:01 | 31.00 |
September | 753466.05 | 2067.70 | 06-SEP-23:01 | 29.80 |
October | 19686.05 | 229.67 | 03-OCT-23:01 | 27.67 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 88942.51 | 1482.38 | 07-DEC-05:04 | -1.1 |
Annual Sum or Average | 16502182.36 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 5783230.10 | 4695.36 | 32.83 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:01 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.405118E+09 | 400.32 | 02-JAN-17:30 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.358982E+09 | 400.32 | 01-FEB-17:00 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.357032E+09 | 400.32 | 01-MAR-18:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.322136E+09 | 400.32 | 01-APR-18:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.320640E+09 | 400.32 | 01-MAY-18:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.292987E+09 | 400.32 | 01-JUN-19:19 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.304473E+09 | 400.32 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.335966E+09 | 400.32 | 01-AUG-19:19 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.335265E+09 | 400.32 | 01-SEP-18:49 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.370181E+09 | 400.32 | 02-OCT-17:00 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.388278E+09 | 400.32 | 01-NOV-17:30 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.416306E+09 | 400.32 | 01-DEC-16:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.420736E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.292987E+09 | 400.32 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.416306E+09 | 400.32 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138574E+10 | 811.23 | 02-JAN-10:09 | 0.154373E+11 | 9706.84 | 01-JAN-11:09 |
February | 0.125514E+10 | 811.23 | 01-FEB-10:09 | 0.139433E+11 | 9706.84 | 01-FEB-11:09 |
March | 0.140781E+10 | 811.23 | 01-MAR-10:09 | 0.154374E+11 | 9706.84 | 01-MAR-11:09 |
April | 0.134648E+10 | 811.23 | 01-APR-16:10 | 0.149393E+11 | 9706.84 | 01-APR-10:09 |
May | 0.139678E+10 | 811.23 | 01-MAY-09:09 | 0.154373E+11 | 9706.84 | 01-MAY-10:09 |
June | 0.136076E+10 | 811.23 | 01-JUN-09:09 | 0.149394E+11 | 9706.84 | 01-JUN-10:09 |
July | 0.138266E+10 | 811.23 | 01-JUL-16:10 | 0.154372E+11 | 9706.84 | 01-JUL-10:09 |
August | 0.140781E+10 | 811.23 | 01-AUG-09:09 | 0.154374E+11 | 9706.84 | 01-AUG-10:09 |
September | 0.134680E+10 | 811.23 | 01-SEP-09:09 | 0.149393E+11 | 9706.84 | 01-SEP-10:09 |
October | 0.138558E+10 | 811.23 | 02-OCT-09:09 | 0.154373E+11 | 9706.84 | 01-OCT-10:09 |
November | 0.134145E+10 | 811.23 | 01-NOV-09:09 | 0.149393E+11 | 9706.84 | 01-NOV-10:09 |
December | 0.138282E+10 | 811.23 | 01-DEC-10:09 | 0.154372E+11 | 9706.84 | 01-DEC-11:09 |
Annual Sum or Average | 0.163998E+11 | 0.181762E+12 | ||||
Minimum of Months | 0.125514E+10 | 811.23 | 0.139433E+11 | 9706.84 | ||
Maximum of Months | 0.140781E+10 | 811.23 | 0.154374E+11 | 9706.84 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.405118E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104495E+09 | 0.593708E+10 |
February | 0.852256E+10 | 0.358982E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729806E+10 |
March | 0.954557E+10 | 0.357032E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261537E+09 | 0.549336E+10 |
April | 0.915225E+10 | 0.322136E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315719E+10 | 0.118673E+10 |
May | 0.947560E+10 | 0.320640E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539289E+10 | 0.416268E+09 |
June | 0.922788E+10 | 0.292987E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928425E+10 | 51489430.87 |
July | 0.939996E+10 | 0.304473E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805821E+10 | 42715167.63 |
August | 0.954557E+10 | 0.335966E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760821E+10 | 0.149187E+09 |
September | 0.915225E+10 | 0.335265E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557433E+10 | 0.238760E+09 |
October | 0.940563E+10 | 0.370181E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209826E+10 | 0.284585E+10 |
November | 0.909363E+10 | 0.388278E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187562E+09 | 0.583887E+10 |
December | 0.939996E+10 | 0.416306E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24983600.81 | 0.850779E+10 |
Annual Sum or Average | 0.111326E+12 | 0.420736E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417519E+11 | 0.380062E+11 |
Minimum of Months | 0.852256E+10 | 0.292987E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42715167.63 |
Maximum of Months | 0.954557E+10 | 0.416306E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928425E+10 | 0.850779E+10 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.138574E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 23514.13 | 29623199.79 |
February | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21845527.35 |
March | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 81200.61 | 32161797.01 |
April | 0.655836E+09 | 0.134648E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2811302.28 | 13271983.96 |
May | 0.679007E+09 | 0.139678E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6145467.85 | 9420036.25 |
June | 0.661256E+09 | 0.136076E+10 | 0.109170E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 12227799.61 | 3724942.84 |
July | 0.673587E+09 | 0.138266E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10364767.73 | 3849800.67 |
August | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 7294914.04 | 5416743.03 |
September | 0.655836E+09 | 0.134680E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 5581838.34 | 8056661.30 |
October | 0.673993E+09 | 0.138558E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1848915.87 | 18258617.44 |
November | 0.651635E+09 | 0.134145E+10 | 0.109169E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 47869.27 | 27339929.82 |
December | 0.673587E+09 | 0.138282E+10 | 0.112808E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26588803.88 |
Annual Sum or Average | 0.797748E+10 | 0.163998E+11 | 0.132823E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 46427589.72 | 0.199558E+09 |
Minimum of Months | 0.610713E+09 | 0.125514E+10 | 0.101891E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3724942.84 |
Maximum of Months | 0.684021E+09 | 0.140781E+10 | 0.112809E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 12227799.61 | 32161797.01 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497831E+09 | 0.928099E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281360E+09 | 0.941952E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327263E+09 | 0.124914E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435133E+09 | 0.170585E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472050E+09 | 0.180619E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396262E+09 | 0.181014E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280287E+09 | 0.163193E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353159E+09 | 0.152859E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306387E+09 | 0.122791E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483728E+09 | 0.113406E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412569E+09 | 0.931124E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537630E+09 | 0.827503E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478366E+10 | 0.157225E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280287E+09 | 0.827503E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537630E+09 | 0.181014E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 400.32 | 02-JAN-17:30 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2959.93 | 31-JAN-14:00 | 12271.71 | 01-JAN-08:00 |
February | 9454.80 | 04-FEB-19:10 | 400.32 | 01-FEB-17:00 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11416.53 | 04-FEB-19:55 |
March | 9454.80 | 04-MAR-19:10 | 400.32 | 01-MAR-18:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.49 | 20-MAR-17:05 | 12047.75 | 26-MAR-06:10 |
April | 9454.80 | 01-APR-18:10 | 400.32 | 01-APR-18:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8551.85 | 14-APR-17:03 | 5676.62 | 06-APR-19:53 |
May | 9454.80 | 06-MAY-18:10 | 400.32 | 01-MAY-18:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10079.22 | 31-MAY-17:03 | 4107.98 | 13-MAY-06:05 |
June | 9454.80 | 03-JUN-18:10 | 400.32 | 01-JUN-19:19 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13755.55 | 28-JUN-17:10 | 2164.83 | 21-JUN-06:03 |
July | 9454.80 | 01-JUL-18:10 | 400.32 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11826.45 | 22-JUL-18:10 | 2821.46 | 01-JUL-06:05 |
August | 9454.80 | 05-AUG-18:10 | 400.32 | 01-AUG-19:19 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12974.62 | 25-AUG-17:10 | 6195.31 | 05-AUG-18:10 |
September | 9454.80 | 02-SEP-18:10 | 400.32 | 01-SEP-18:49 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10259.64 | 07-SEP-17:03 | 3099.75 | 22-SEP-06:10 |
October | 9454.80 | 07-OCT-18:10 | 400.32 | 02-OCT-17:00 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7964.91 | 02-OCT-12:00 | 7762.78 | 25-OCT-06:10 |
November | 9454.80 | 04-NOV-18:10 | 400.32 | 01-NOV-17:30 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2955.47 | 09-NOV-14:00 | 12532.46 | 23-NOV-20:55 |
December | 9454.80 | 02-DEC-19:10 | 400.32 | 01-DEC-16:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.41 | 25-DEC-14:00 | 14894.85 | 05-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2164.83 | |||||
Maximum of Months | 9454.80 | 400.32 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13755.55 | 14894.85 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 811.23 | 02-JAN-10:09 | 6972.03 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 1.19 | 31-JAN-15:40 | 89.40 | 01-JAN-02:00 |
February | 677.52 | 04-FEB-19:10 | 811.23 | 01-FEB-10:09 | 6972.03 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 83.44 | 05-FEB-04:00 |
March | 677.52 | 04-MAR-19:10 | 811.23 | 01-MAR-10:09 | 6972.03 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 2.14 | 15-MAR-15:00 | 101.25 | 28-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 811.23 | 01-APR-16:10 | 6972.03 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 12.03 | 30-APR-15:03 | 45.78 | 27-APR-00:20 |
May | 677.52 | 06-MAY-18:10 | 811.23 | 01-MAY-09:09 | 6972.03 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.96 | 20-MAY-14:00 | 40.40 | 14-MAY-02:50 |
June | 677.52 | 03-JUN-18:10 | 811.23 | 01-JUN-09:09 | 6972.03 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 26.81 | 19-JUN-13:55 | 27.34 | 13-JUN-03:30 |
July | 677.52 | 01-JUL-18:10 | 811.23 | 01-JUL-16:10 | 6972.03 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 26.00 | 22-JUL-16:00 | 49.26 | 27-JUL-00:50 |
August | 677.52 | 05-AUG-18:10 | 811.23 | 01-AUG-09:09 | 6972.03 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 20.50 | 13-AUG-16:00 | 53.93 | 19-AUG-02:00 |
September | 677.52 | 02-SEP-18:10 | 811.23 | 01-SEP-09:09 | 6972.03 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 15.48 | 01-SEP-16:00 | 41.76 | 16-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 811.23 | 02-OCT-09:09 | 6972.03 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 10.29 | 10-OCT-15:00 | 64.84 | 26-OCT-02:70 |
November | 677.52 | 04-NOV-18:10 | 811.23 | 01-NOV-09:09 | 6972.03 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 1.84 | 01-NOV-15:53 | 110.60 | 29-NOV-04:00 |
December | 677.52 | 02-DEC-19:10 | 811.23 | 01-DEC-10:09 | 6972.03 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 73.76 | 17-DEC-04:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | ||||||
Maximum of Months | 677.52 | 811.23 | 6972.03 | 7998.14 | 0.00 | 0.00 | 0.00 | 26.81 | 110.60 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.98 | 28-JAN-07:53 | 1774.81 | 09-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.12 | 02-FEB-06:00 | 2191.50 | 28-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.49 | 19-MAR-07:42 | 2355.73 | 26-MAR-12:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.10 | 22-APR-06:33 | 2472.42 | 27-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.11 | 14-MAY-06:23 | 2411.57 | 27-MAY-12:40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.05 | 20-JUN-05:53 | 2354.28 | 25-JUN-12:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.62 | 07-JUL-03:51 | 2380.85 | 27-JUL-13:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.02 | 25-AUG-06:42 | 2282.74 | 07-AUG-13:40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.79 | 17-SEP-04:55 | 2147.82 | 07-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.01 | 14-OCT-00:45 | 2079.21 | 26-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.65 | 19-NOV-04:55 | 1964.36 | 14-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.31 | 21-DEC-07:25 | 1637.01 | 14-DEC-12:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.12 | 1637.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.31 | 2472.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10963.09 | 31-JAN-14:00 | 7353.73 | 96.08 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2959.93 | 0.00 |
February | 6278.81 | 01-FEB-05:01 | 5252.67 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
March | 11734.12 | 20-MAR-17:05 | 16808.53 | 192.15 | 6505.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.49 | 0.00 |
April | 31188.74 | 25-APR-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
May | 32631.13 | 08-MAY-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
June | 34261.48 | 14-JUN-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
July | 35549.23 | 04-JUL-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
August | 35043.40 | 25-AUG-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
September | 34251.71 | 17-SEP-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
October | 31623.03 | 07-OCT-03:01 | 0.00 | 667.21 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
November | 18699.26 | 02-NOV-04:01 | 4727.40 | 800.65 | 14636.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
December | 9139.45 | 22-DEC-14:00 | 7353.73 | 96.08 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 804.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6278.81 | 0.00 | 96.08 | 3388.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35549.23 | 16808.53 | 889.61 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.49 | 11.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35788.50 | 07-JAN-05:01 | 0.00 | 1352.07 | 32211.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
February | 28364.77 | 10-FEB-04:42 | 0.00 | 811.24 | 10120.67 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 41.25 |
March | 41568.92 | 21-MAR-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
April | 47642.49 | 21-APR-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 |
May | 33052.77 | 11-MAY-04:01 | 301.12 | 1442.23 | 25850.46 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
June | 41293.58 | 16-JUN-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
July | 35788.78 | 04-JUL-04:01 | 0.00 | 1081.65 | 25769.18 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
August | 37396.24 | 25-AUG-04:01 | 301.12 | 1442.23 | 25850.46 | 26476.59 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
September | 35937.78 | 19-SEP-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
October | 46999.10 | 27-OCT-04:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 |
November | 47352.07 | 10-NOV-05:01 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
December | 31101.61 | 26-DEC-04:42 | 0.00 | 811.24 | 10120.67 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28364.77 | 0.00 | 811.24 | 10120.67 | 8273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | |
Maximum of Months | 47642.49 | 376.40 | 1802.79 | 32313.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.94 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.42 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.71 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.97 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.06 | 0.00 |
June | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.40 | 0.00 |
July | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.06 | 0.00 |
August | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.43 | 0.00 |
September | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.06 | 0.00 |
October | 0.00 | 01-OCT-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.08 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.77 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.77 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.354103E+11 | 23772.40 | 27-JAN-11:20 | 0.600204E+11 | 56269.87 | 01-JAN-07:00 |
February | 0.301537E+11 | 20779.86 | 24-FEB-11:09 | 0.555596E+11 | 50133.15 | 19-FEB-13:50 |
March | 0.353139E+11 | 24792.89 | 18-MAR-10:20 | 0.594853E+11 | 56027.42 | 26-MAR-06:10 |
April | 0.415589E+11 | 29172.33 | 14-APR-16:10 | 0.534872E+11 | 47014.57 | 03-APR-12:00 |
May | 0.465366E+11 | 31547.18 | 31-MAY-17:10 | 0.540769E+11 | 45705.86 | 02-MAY-12:20 |
June | 0.535455E+11 | 38747.98 | 28-JUN-17:10 | 0.514557E+11 | 44215.23 | 05-JUN-12:20 |
July | 0.555785E+11 | 38071.41 | 19-JUL-12:00 | 0.526894E+11 | 43287.30 | 01-JUL-12:20 |
August | 0.550235E+11 | 38000.54 | 25-AUG-11:00 | 0.528624E+11 | 43723.59 | 31-AUG-12:50 |
September | 0.500318E+11 | 34834.13 | 01-SEP-11:00 | 0.517899E+11 | 44938.78 | 28-SEP-12:39 |
October | 0.414712E+11 | 31931.52 | 03-OCT-10:20 | 0.550897E+11 | 46417.40 | 30-OCT-12:50 |
November | 0.347098E+11 | 26585.34 | 01-NOV-10:20 | 0.559745E+11 | 49851.09 | 23-NOV-07:19 |
December | 0.342313E+11 | 23481.07 | 22-DEC-11:20 | 0.645502E+11 | 56489.99 | 06-DEC-07:10 |
Annual Sum or Average | 0.513565E+12 | 0.667041E+12 | ||||
Minimum of Months | 0.301537E+11 | 20779.86 | 0.514557E+11 | 43287.30 | ||
Maximum of Months | 0.555785E+11 | 38747.98 | 0.645502E+11 | 56489.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.179086E+10 | 0.158012E+10 | 0.214106E+11 | 0.00 | 0.527331E+10 | 0.79 | 0.00 | 0.211075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161412E+10 | 0.133335E+10 | 0.193386E+11 | 0.00 | 0.477591E+10 | 0.72 | 0.00 | 0.186709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176484E+10 | 0.133618E+10 | 0.214107E+11 | 0.00 | 0.528655E+10 | 0.80 | 0.00 | 0.224735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166862E+10 | 0.114980E+10 | 0.207199E+11 | 0.00 | 0.520729E+10 | 0.77 | 0.00 | 0.957003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171742E+10 | 0.106488E+10 | 0.214107E+11 | 0.00 | 0.554846E+10 | 0.80 | 0.00 | 0.134262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165374E+10 | 0.979131E+09 | 0.207201E+11 | 0.00 | 0.594489E+10 | 0.77 | 0.00 | 0.209708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168713E+10 | 0.103106E+10 | 0.214105E+11 | 0.00 | 0.607152E+10 | 0.79 | 0.00 | 0.219731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174377E+10 | 0.113250E+10 | 0.214107E+11 | 0.00 | 0.604293E+10 | 0.80 | 0.00 | 0.212777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168207E+10 | 0.122950E+10 | 0.207199E+11 | 0.00 | 0.562399E+10 | 0.77 | 0.00 | 0.174718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175576E+10 | 0.141991E+10 | 0.214106E+11 | 0.00 | 0.541823E+10 | 0.79 | 0.00 | 0.812230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172973E+10 | 0.149920E+10 | 0.207200E+11 | 0.00 | 0.511749E+10 | 0.77 | 0.00 | 0.246976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179913E+10 | 0.161956E+10 | 0.214105E+11 | 0.00 | 0.534321E+10 | 0.79 | 0.00 | 0.890476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206072E+11 | 0.153752E+11 | 0.252093E+12 | 0.00 | 0.656538E+11 | 9.37 | 0.00 | 0.120717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161412E+10 | 0.979131E+09 | 0.193386E+11 | 0.00 | 0.477591E+10 | 0.72 | 0.00 | 0.186709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179913E+10 | 0.161956E+10 | 0.214107E+11 | 0.00 | 0.607152E+10 | 0.80 | 0.00 | 0.219731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.294405E+10 | 0.00 | 0.165506E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.410795E+10 | 0.00 | 0.148477E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.318720E+10 | 0.00 | 0.157724E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 72509964.21 | 0.00 | 0.141962E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.00 | 0.00 | 0.135512E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 533513.88 | 0.00 | 0.122367E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 506389.43 | 0.00 | 0.121632E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 237188.75 | 0.00 | 0.123364E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 171112.75 | 0.00 | 0.125713E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.507412E+09 | 0.00 | 0.140566E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.203022E+10 | 0.00 | 0.147258E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.789376E+10 | 0.00 | 0.161308E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.207446E+11 | 0.00 | 0.169139E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.00 | 0.00 | 0.121632E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.789376E+10 | 0.00 | 0.165506E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1211.55 | 02-JAN-17:30 | 1341.77 | 01-JAN-06:10 | 13637.09 | 01-JAN-11:09 | 0.00 | 2931.22 | 01-JAN-07:00 | 0.00 | 20-JAN-10:39 | 0.00 | 01-JAN-00:10 |
February | 1211.55 | 01-FEB-17:00 | 1341.77 | 01-FEB-06:10 | 13637.09 | 01-FEB-11:09 | 0.00 | 2643.59 | 28-FEB-07:10 | 0.00 | 23-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 1211.55 | 01-MAR-18:19 | 1341.77 | 01-MAR-06:10 | 13637.09 | 01-MAR-11:09 | 0.00 | 2929.33 | 26-MAR-06:10 | 0.00 | 06-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 1211.55 | 01-APR-18:40 | 1341.77 | 01-APR-05:10 | 13637.09 | 01-APR-10:09 | 0.00 | 2729.64 | 14-APR-12:00 | 0.00 | 22-APR-08:20 | 0.00 | 01-APR-00:10 |
May | 1211.55 | 01-MAY-18:30 | 1341.77 | 01-MAY-05:10 | 13637.09 | 01-MAY-10:09 | 0.00 | 3084.90 | 31-MAY-17:10 | 0.00 | 01-MAY-18:40 | 0.00 | 01-MAY-00:10 |
June | 1211.55 | 01-JUN-19:19 | 1341.77 | 01-JUN-05:10 | 13637.09 | 01-JUN-10:09 | 0.00 | 4053.33 | 28-JUN-17:10 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 1211.55 | 01-JUL-19:30 | 1341.77 | 01-JUL-05:10 | 13637.09 | 01-JUL-10:09 | 0.00 | 3991.29 | 19-JUL-12:00 | 0.00 | 07-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 1211.55 | 01-AUG-19:19 | 1341.77 | 01-AUG-05:10 | 13637.09 | 01-AUG-10:09 | 0.00 | 3926.63 | 25-AUG-17:10 | 0.00 | 02-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 1211.55 | 01-SEP-18:49 | 1341.77 | 01-SEP-05:10 | 13637.09 | 01-SEP-10:09 | 0.00 | 3562.95 | 01-SEP-11:00 | 0.00 | 03-SEP-12:20 | 0.00 | 01-SEP-00:10 |
October | 1211.55 | 02-OCT-17:00 | 1341.77 | 01-OCT-05:10 | 13637.09 | 01-OCT-10:09 | 0.00 | 2963.99 | 01-OCT-12:00 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1211.55 | 01-NOV-17:30 | 1341.77 | 01-NOV-05:10 | 13637.09 | 01-NOV-10:09 | 0.00 | 2863.26 | 23-NOV-07:10 | 0.00 | 07-NOV-10:30 | 0.00 | 01-NOV-00:10 |
December | 1211.55 | 01-DEC-16:30 | 1341.77 | 01-DEC-06:10 | 13637.09 | 01-DEC-11:09 | 0.00 | 2937.09 | 06-DEC-07:10 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 2643.59 | 0.00 | 0.00 | ||||||
Maximum of Months | 1211.55 | 1341.77 | 13637.09 | 0.00 | 4053.33 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 6928.45 | 31-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3183.03 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7156.86 | 20-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12792.38 | 14-APR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15026.37 | 31-MAY-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21230.57 | 28-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20138.38 | 19-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20306.44 | 25-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16549.72 | 01-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14528.30 | 01-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8586.97 | 01-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5663.00 | 25-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3183.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21230.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23772.40 | 27-JAN-11:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2311.97 | 0.00 | 0.00 | 3016.00 | 0.00 |
February | 20779.86 | 24-FEB-11:09 | 907.31 | 13637.09 | 0.00 | 0.00 | 2362.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24792.89 | 18-MAR-10:20 | 806.50 | 13637.09 | 0.00 | 0.00 | 2311.97 | 0.00 | 0.00 | 4133.63 | 0.00 |
April | 29172.33 | 14-APR-16:10 | 907.31 | 12287.48 | 0.00 | 0.00 | 2712.11 | 0.00 | 0.00 | 12120.92 | 0.00 |
May | 31547.18 | 31-MAY-17:10 | 907.31 | 11387.73 | 0.00 | 0.00 | 3084.90 | 0.00 | 0.00 | 15026.37 | 0.00 |
June | 38747.98 | 28-JUN-17:10 | 907.31 | 11387.73 | 0.00 | 0.00 | 4053.33 | 0.00 | 0.00 | 21230.57 | 0.00 |
July | 38071.41 | 19-JUL-12:00 | 907.31 | 11837.60 | 0.00 | 0.00 | 3991.29 | 0.00 | 0.00 | 20138.38 | 0.00 |
August | 38000.54 | 25-AUG-11:00 | 907.31 | 12737.35 | 0.00 | 0.00 | 3788.09 | 0.00 | 0.00 | 19401.41 | 0.00 |
September | 34834.13 | 01-SEP-11:00 | 907.31 | 12737.35 | 0.00 | 0.00 | 3562.95 | 0.00 | 0.00 | 16437.52 | 0.00 |
October | 31931.52 | 03-OCT-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2622.06 | 0.00 | 0.00 | 10843.76 | 0.00 |
November | 26585.34 | 01-NOV-10:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2311.97 | 0.00 | 0.00 | 5812.68 | 0.00 |
December | 23481.07 | 22-DEC-11:20 | 907.31 | 13637.09 | 0.00 | 0.00 | 2311.97 | 0.00 | 0.00 | 2723.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 20779.86 | 806.50 | 11387.73 | 0.00 | 0.00 | 2311.97 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38747.98 | 907.31 | 13637.09 | 0.00 | 0.00 | 4053.33 | 0.00 | 0.00 | 21230.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 34661.65 | 01-JAN-07:00 | 0.00 | 25346.09 | 23-JAN-13:39 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 17291.34 | 28-FEB-07:10 | 0.00 | 25333.72 | 01-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 34334.28 | 26-MAR-06:10 | 0.00 | 24969.87 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 5886.26 | 21-APR-06:10 | 0.00 | 24031.42 | 03-APR-12:00 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22722.71 | 02-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 889.19 | 03-JUN-03:49 | 0.00 | 21232.08 | 05-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 843.98 | 25-JUL-03:49 | 0.00 | 20304.15 | 01-JUL-12:20 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 395.31 | 23-AUG-03:49 | 0.00 | 20740.44 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 219.67 | 28-SEP-03:09 | 0.00 | 21955.63 | 28-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 11354.83 | 25-OCT-06:00 | 0.00 | 23434.25 | 30-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 29989.96 | 23-NOV-07:10 | 0.00 | 24551.29 | 30-NOV-13:30 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 35453.87 | 06-DEC-07:10 | 0.00 | 25184.13 | 30-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 0.00 | 0.00 | 20304.15 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 35453.87 | 0.00 | 25346.09 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.35 | 0.00 | 26.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.41 | 0.00 | 26.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.48 | 0.00 | 26.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.32 | 0.00 | 26.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.24 | 0.00 | 26.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.50 | 26.38 | 0.00 | 26.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.48 | 0.00 | 26.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 29.15 | 0.00 | 29.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.83 | 0.00 | 28.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 29.41 | 0.00 | 29.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 30.25 | 0.00 | 30.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 30.47 | 0.00 | 30.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 30.00 | 3.67 | 29.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 30.50 | 0.00 | 30.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 30.37 | 1.33 | 30.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.71 | 0.00 | 30.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 30.30 | 0.00 | 30.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 29.67 | 0.00 | 29.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.90 | 0.00 | 28.90 |
Annual Sum or Average | 0.00 | 0.00 | 205.33 | 30.24 | 5.00 | 30.16 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.83 | 0.00 | 28.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 30.71 | 3.67 | 30.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.50 | 21.51 | 63.67 | 21.79 | 13.50 | 21.77 |
February | 457.67 | 21.34 | 36.33 | 21.42 | 12.50 | 21.37 |
March | 368.00 | 21.72 | 75.67 | 21.95 | 15.17 | 21.89 |
April | 109.33 | 22.78 | 225.67 | 23.62 | 0.00 | 23.62 |
May | 51.50 | 23.45 | 274.00 | 24.04 | 0.00 | 24.04 |
June | 11.17 | 28.37 | 492.83 | 24.30 | 10.00 | 24.39 |
July | 98.00 | 25.01 | 576.00 | 24.29 | 97.17 | 24.38 |
August | 95.67 | 24.94 | 594.83 | 24.25 | 95.67 | 24.33 |
September | 105.83 | 24.46 | 578.83 | 24.16 | 105.83 | 24.20 |
October | 150.83 | 22.20 | 329.17 | 23.42 | 12.17 | 23.45 |
November | 318.17 | 21.83 | 194.50 | 22.53 | 57.33 | 22.59 |
December | 464.00 | 21.42 | 63.67 | 21.34 | 48.50 | 21.21 |
Annual Sum or Average | 2579.67 | 22.08 | 3505.17 | 23.17 | 467.83 | 23.22 |
Minimum of Months | 11.17 | 21.34 | 36.33 | 21.34 | 0.00 | 21.21 |
Maximum of Months | 464.00 | 28.37 | 594.83 | 24.30 | 105.83 | 24.39 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.83 | 23.58 | 395.67 | 24.45 | 240.33 | 24.75 |
February | 293.83 | 21.95 | 321.17 | 23.28 | 100.33 | 23.56 |
March | 391.00 | 23.87 | 434.00 | 24.65 | 249.83 | 24.91 |
April | 454.33 | 26.11 | 563.67 | 26.04 | 445.50 | 26.09 |
May | 518.67 | 26.27 | 607.83 | 26.22 | 518.67 | 26.23 |
June | 578.50 | 26.37 | 592.00 | 26.36 | 578.50 | 26.36 |
July | 600.83 | 26.34 | 609.00 | 26.34 | 600.83 | 26.34 |
August | 612.00 | 26.33 | 612.00 | 26.33 | 612.00 | 26.33 |
September | 590.00 | 26.30 | 590.00 | 26.30 | 590.00 | 26.30 |
October | 482.67 | 25.70 | 551.17 | 25.79 | 440.50 | 25.90 |
November | 418.33 | 24.39 | 439.50 | 24.92 | 304.00 | 25.16 |
December | 381.17 | 21.62 | 340.00 | 22.82 | 162.00 | 22.91 |
Annual Sum or Average | 5735.17 | 25.21 | 6056.00 | 25.53 | 4842.50 | 25.69 |
Minimum of Months | 293.83 | 21.62 | 321.17 | 22.82 | 100.33 | 22.91 |
Maximum of Months | 612.00 | 26.37 | 612.00 | 26.36 | 612.00 | 26.36 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 22.50764 | 26.92231 | 0.04700 | 7.39451 |
February | 551.00000 | 21.75050 | 42.77188 | -0.0858 | 6.73722 |
March | 612.00000 | 22.57452 | 31.55840 | 0.04766 | 7.29427 |
April | 590.00000 | 23.77949 | 20.53650 | 0.34684 | 8.28482 |
May | 611.00000 | 24.01647 | 18.74175 | -0.4305 | 9.44014 |
June | 592.00000 | 24.15202 | 25.97516 | -0.2688 | 7.29799 |
July | 609.00000 | 24.14858 | 44.83628 | -0.1284 | 6.25447 |
August | 612.00000 | 24.13222 | 47.04109 | -0.1102 | 5.98537 |
September | 590.00000 | 24.09889 | 47.45938 | -0.1164 | 5.88872 |
October | 610.00000 | 23.50969 | 29.95793 | 0.37491 | 9.70484 |
November | 591.00000 | 22.74296 | 32.16623 | 0.16696 | 8.23252 |
December | 609.00000 | 21.99709 | 19.86352 | -0.1302 | 7.95617 |
Annual Sum or Average | 7187.00000 | 23.29258 | 32.24233 | -0.0241 | 7.54701 |
Minimum of Months | 551.00000 | 21.75050 | 18.74175 | -0.4305 | 5.88872 |
Maximum of Months | 612.00000 | 24.15202 | 47.45938 | 0.37491 | 9.70484 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 23.83659 | 31.47496 | 0.55359 | 17.89728 |
February | 551.00000 | 22.86956 | 45.65144 | 0.40474 | 13.99279 |
March | 612.00000 | 24.05322 | 35.10642 | 0.62130 | 19.33876 |
April | 590.00000 | 25.82725 | 24.34044 | 1.01704 | 28.13342 |
May | 611.00000 | 26.16172 | 22.09339 | 0.53710 | 11.94286 |
June | 592.00000 | 26.35858 | 27.25444 | 0.69181 | 15.71059 |
July | 609.00000 | 26.33995 | 43.58379 | 0.82869 | 20.18272 |
August | 612.00000 | 26.33394 | 45.31238 | 0.83901 | 20.43028 |
September | 590.00000 | 26.29518 | 45.16873 | 0.82353 | 19.80480 |
October | 610.00000 | 25.43711 | 32.19737 | 1.00394 | 29.28890 |
November | 591.00000 | 24.31625 | 34.48800 | 0.72558 | 22.26013 |
December | 609.00000 | 22.68896 | 25.99441 | 0.25774 | 14.69195 |
Annual Sum or Average | 7187.00000 | 25.05438 | 34.31334 | 0.69305 | 19.49464 |
Minimum of Months | 551.00000 | 22.68896 | 22.09339 | 0.25774 | 11.94286 |
Maximum of Months | 612.00000 | 26.35858 | 45.65144 | 1.01704 | 29.28890 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.317051E+10 | 0.924815E+09 | 153.83 | 0.316746E+10 | 3046659.05 | 0.00 | 0.61 | 31-JAN-14:00 | 0.00 | 01-JAN-00:02 | 14076.02 | 31-JAN-14:00 | 14076.02 | 31-JAN-14:00 | 477.04 | 08-JAN-12:53 | 3833.50 | 31-JAN-14:00 | 0.00 | 01-JAN-00:02 |
February | 44340743.45 | 13776020.26 | 10.81 | 40853734.65 | 3487008.81 | 0.00 | 0.15 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 | 3072.31 | 18-FEB-14:00 | 2588.09 | 18-FEB-14:00 | 484.22 | 18-FEB-14:00 | 939.72 | 18-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 0.322966E+10 | 0.931527E+09 | 144.48 | 0.321086E+10 | 18794215.55 | 0.00 | 0.65 | 20-MAR-17:05 | 0.00 | 01-MAR-00:10 | 15104.12 | 20-MAR-17:05 | 15104.12 | 20-MAR-17:05 | 1041.47 | 17-MAR-11:01 | 4071.80 | 20-MAR-17:05 | 0.00 | 01-MAR-00:10 |
April | 0.172658E+11 | 0.483012E+10 | 415.63 | 0.172595E+11 | 6254570.91 | 0.00 | 1.00 | 14-APR-17:03 | 0.00 | 01-APR-00:01 | 51335.25 | 15-APR-03:02 | 51335.25 | 25-APR-03:01 | 1777.31 | 16-APR-04:01 | 12527.17 | 15-APR-03:02 | 0.00 | 01-APR-00:01 |
May | 0.238884E+11 | 0.671531E+10 | 500.71 | 0.238883E+11 | 160840.02 | 0.00 | 1.00 | 08-MAY-03:01 | 0.00 | 01-MAY-00:01 | 51335.25 | 11-MAY-03:01 | 51335.25 | 08-MAY-03:01 | 1645.90 | 11-MAY-03:01 | 12527.17 | 08-MAY-03:01 | 0.00 | 01-MAY-00:01 |
June | 0.342163E+11 | 0.999820E+10 | 560.27 | 0.340578E+11 | 0.158474E+09 | 0.00 | 1.00 | 01-JUN-03:01 | 0.00 | 01-JUN-00:02 | 51335.25 | 27-JUN-03:59 | 51335.25 | 05-JUN-03:18 | 5409.25 | 17-JUN-17:03 | 12527.17 | 01-JUN-03:01 | 0.00 | 01-JUN-00:02 |
July | 0.381598E+11 | 0.106220E+11 | 590.17 | 0.329694E+11 | 0.519032E+10 | 0.00 | 1.00 | 01-JUL-03:02 | 0.00 | 01-JUL-00:02 | 57001.03 | 14-JUL-03:01 | 51335.25 | 31-JUL-03:41 | 31214.10 | 14-JUL-03:01 | 12919.02 | 14-JUL-03:01 | 0.00 | 01-JUL-00:02 |
August | 0.369547E+11 | 0.103094E+11 | 583.18 | 0.319543E+11 | 0.500031E+10 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:02 | 55131.47 | 01-AUG-03:29 | 51335.25 | 25-AUG-03:01 | 21990.13 | 01-AUG-03:51 | 12785.25 | 01-AUG-03:29 | 0.00 | 01-AUG-00:02 |
September | 0.312067E+11 | 0.850139E+10 | 542.12 | 0.265638E+11 | 0.464291E+10 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:02 | 56472.24 | 04-SEP-03:01 | 51335.25 | 29-SEP-03:02 | 32130.42 | 04-SEP-03:01 | 12879.97 | 04-SEP-03:01 | 0.00 | 01-SEP-00:02 |
October | 0.140424E+11 | 0.389708E+10 | 340.67 | 0.131876E+11 | 0.854719E+09 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:02 | 55173.54 | 03-OCT-03:01 | 48161.49 | 07-OCT-03:01 | 25388.10 | 03-OCT-03:01 | 12788.15 | 03-OCT-03:01 | 0.00 | 01-OCT-00:02 |
November | 0.345518E+10 | 0.988794E+09 | 142.15 | 0.332736E+10 | 0.127822E+09 | 0.00 | 0.74 | 01-NOV-12:55 | 0.00 | 01-NOV-00:01 | 17571.70 | 01-NOV-12:55 | 15660.23 | 01-NOV-13:00 | 4549.92 | 12-NOV-05:01 | 4624.50 | 01-NOV-12:55 | 0.00 | 01-NOV-00:01 |
December | 0.118914E+10 | 0.349565E+09 | 70.75 | 0.118914E+10 | 0.41 | 0.00 | 0.49 | 22-DEC-14:00 | 0.00 | 01-DEC-00:10 | 10876.83 | 22-DEC-14:00 | 10876.83 | 22-DEC-14:00 | 0.00 | 12-DEC-12:45 | 3059.73 | 22-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.206823E+12 | 0.580820E+11 | 4054.78 | 0.190817E+12 | 0.160063E+11 | 0.00 | ||||||||||||||
Minimum of Months | 44340743.45 | 13776020.26 | 10.81 | 40853734.65 | 0.41 | 0.00 | 0.15 | 0.00 | 3072.31 | 2588.09 | 0.00 | 939.72 | 0.00 | |||||||
Maximum of Months | 0.381598E+11 | 0.106220E+11 | 590.17 | 0.340578E+11 | 0.519032E+10 | 0.00 | 1.00 | 0.00 | 57001.03 | 51335.25 | 32130.42 | 12919.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.427711E+10 | 0.118594E+10 | 245.68 | 0.412977E+10 | 0.147341E+09 | 0.00 | 1.00 | 06-JAN-04:42 | 0.00 | 01-JAN-00:02 | 31821.01 | 06-JAN-04:42 | 30364.69 | 27-JAN-04:31 | 5929.59 | 07-JAN-05:01 | 7629.06 | 06-JAN-04:42 | 0.00 | 01-JAN-00:02 |
February | 0.599899E+09 | 0.172933E+09 | 62.59 | 0.464164E+09 | 0.135735E+09 | 0.00 | 1.00 | 10-FEB-04:42 | 0.00 | 01-FEB-00:10 | 31821.01 | 10-FEB-04:42 | 26170.68 | 10-FEB-04:42 | 10688.53 | 18-FEB-05:01 | 7629.06 | 10-FEB-04:42 | 0.00 | 01-FEB-00:10 |
March | 0.482702E+10 | 0.131583E+10 | 250.41 | 0.454649E+10 | 0.280523E+09 | 0.00 | 1.00 | 06-MAR-05:01 | 0.00 | 01-MAR-00:10 | 31821.01 | 17-MAR-03:31 | 25739.98 | 21-MAR-04:01 | 10349.50 | 24-MAR-03:41 | 7629.06 | 17-MAR-03:31 | 0.00 | 01-MAR-00:10 |
April | 0.184094E+11 | 0.473990E+10 | 463.38 | 0.183078E+11 | 0.101545E+09 | 0.00 | 1.00 | 01-APR-12:45 | 0.00 | 01-APR-00:01 | 31821.01 | 13-APR-03:32 | 31821.01 | 14-APR-03:31 | 6702.00 | 07-APR-04:01 | 7629.06 | 02-APR-03:01 | 0.00 | 01-APR-00:01 |
May | 0.258473E+11 | 0.671086E+10 | 543.91 | 0.258143E+11 | 32994081.43 | 0.00 | 1.00 | 02-MAY-02:12 | 0.00 | 01-MAY-00:01 | 31821.01 | 30-MAY-02:12 | 31821.01 | 02-MAY-03:31 | 7817.06 | 26-MAY-02:53 | 7629.06 | 02-MAY-02:12 | 0.00 | 01-MAY-00:01 |
June | 0.398071E+11 | 0.109726E+11 | 616.77 | 0.396736E+11 | 0.133456E+09 | 0.00 | 1.00 | 01-JUN-00:42 | 0.00 | 01-JUN-00:02 | 32023.89 | 17-JUN-13:57 | 32023.89 | 17-JUN-13:57 | 4663.52 | 01-JUN-03:01 | 9960.64 | 16-JUN-16:00 | 0.00 | 01-JUN-00:02 |
July | 0.443268E+11 | 0.113511E+11 | 642.37 | 0.386646E+11 | 0.566221E+10 | 0.00 | 1.00 | 01-JUL-00:11 | 0.00 | 01-JUL-00:02 | 35355.24 | 14-JUL-00:42 | 32925.23 | 19-JUL-13:00 | 23382.10 | 14-JUL-00:42 | 9418.52 | 12-JUL-13:56 | 0.00 | 01-JUL-00:02 |
August | 0.426860E+11 | 0.109683E+11 | 637.11 | 0.371138E+11 | 0.557224E+10 | 0.00 | 1.00 | 01-AUG-00:11 | 0.00 | 01-AUG-00:02 | 34746.23 | 01-AUG-02:51 | 31821.01 | 25-AUG-00:42 | 18132.79 | 20-AUG-00:42 | 9781.29 | 25-AUG-14:30 | 0.00 | 01-AUG-00:02 |
September | 0.358829E+11 | 0.897043E+10 | 597.02 | 0.299543E+11 | 0.592863E+10 | 0.00 | 1.00 | 01-SEP-00:42 | 0.00 | 01-SEP-00:02 | 34837.87 | 04-SEP-00:42 | 31821.01 | 18-SEP-00:28 | 21907.25 | 04-SEP-03:45 | 8152.87 | 08-SEP-16:00 | 0.00 | 01-SEP-00:02 |
October | 0.164174E+11 | 0.422522E+10 | 434.52 | 0.150764E+11 | 0.134100E+10 | 0.00 | 1.00 | 01-OCT-00:42 | 0.00 | 01-OCT-00:02 | 34093.36 | 03-OCT-02:42 | 31821.01 | 15-OCT-03:42 | 18606.75 | 03-OCT-03:03 | 7780.77 | 03-OCT-02:42 | 0.00 | 01-OCT-00:02 |
November | 0.551058E+10 | 0.148097E+10 | 261.53 | 0.466533E+10 | 0.845247E+09 | 0.00 | 1.00 | 01-NOV-02:53 | 0.00 | 01-NOV-00:01 | 31821.01 | 03-NOV-03:01 | 28150.12 | 10-NOV-05:01 | 20050.88 | 13-NOV-04:02 | 7629.06 | 03-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 0.192061E+10 | 0.540911E+09 | 138.46 | 0.189310E+10 | 27508759.41 | 0.00 | 1.00 | 12-DEC-04:42 | 0.00 | 01-DEC-00:10 | 15892.26 | 12-DEC-04:42 | 15478.05 | 12-DEC-04:42 | 6492.40 | 13-DEC-05:01 | 3813.12 | 12-DEC-04:42 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.240512E+12 | 0.626350E+11 | 4893.76 | 0.220304E+12 | 0.202084E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.599899E+09 | 0.172933E+09 | 62.59 | 0.464164E+09 | 27508759.41 | 0.00 | 1.00 | 0.00 | 15892.26 | 15478.05 | 4663.52 | 3813.12 | 0.00 | |||||||
Maximum of Months | 0.443268E+11 | 0.113511E+11 | 642.37 | 0.396736E+11 | 0.592863E+10 | 0.00 | 1.00 | 0.00 | 35355.24 | 32925.23 | 23382.10 | 9960.64 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.56 | 57.44 | 34.12 | 121.90 | 106.78 | 0.00 | 0.00 | 0.00 |
February | 90.25 | 51.63 | 38.62 | 110.29 | 100.10 | 0.00 | 0.00 | 0.00 |
March | 112.95 | 58.10 | 54.85 | 156.47 | 89.43 | 0.00 | 0.00 | 0.00 |
April | 161.22 | 96.09 | 65.13 | 274.14 | 52.78 | 0.00 | 0.00 | 0.00 |
May | 167.09 | 99.05 | 68.04 | 302.92 | 37.45 | 0.00 | 0.00 | 0.00 |
June | 174.16 | 108.22 | 65.94 | 360.39 | 16.54 | 0.00 | 0.00 | 0.00 |
July | 147.09 | 82.94 | 64.15 | 307.58 | 12.96 | 0.00 | 0.00 | 0.00 |
August | 139.60 | 79.67 | 59.93 | 288.04 | 17.30 | 0.00 | 0.00 | 0.00 |
September | 114.55 | 55.21 | 59.33 | 227.11 | 24.64 | 0.00 | 0.00 | 0.00 |
October | 115.06 | 70.02 | 45.03 | 184.24 | 70.80 | 0.00 | 0.00 | 0.00 |
November | 88.47 | 53.11 | 35.36 | 115.98 | 101.47 | 0.00 | 0.00 | 0.00 |
December | 80.66 | 48.71 | 31.96 | 95.27 | 129.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.71 | 71.78 | 51.93 | 212.51 | 63.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 80.66 | 48.71 | 31.96 | 95.27 | 12.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 174.16 | 108.22 | 68.04 | 360.39 | 129.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 466.77 | 372.79 | 93.97 | 732.53 | 212.24 | 0.00 | 0.00 | 0.00 |
February | 295.13 | 199.05 | 96.08 | 424.45 | 197.51 | 0.00 | 0.00 | 0.00 |
March | 245.57 | 126.48 | 119.09 | 377.84 | 185.42 | 0.00 | 0.00 | 0.00 |
April | 209.05 | 84.47 | 124.57 | 402.52 | 114.38 | 0.00 | 0.00 | 0.00 |
May | 140.08 | 23.14 | 116.94 | 295.73 | 82.02 | 0.00 | 0.00 | 0.00 |
June | 119.95 | 9.25 | 110.70 | 333.18 | 35.80 | 0.00 | 0.00 | 0.00 |
July | 122.57 | 12.68 | 109.89 | 326.56 | 27.38 | 0.00 | 0.00 | 0.00 |
August | 149.04 | 41.19 | 107.85 | 375.86 | 35.98 | 0.00 | 0.00 | 0.00 |
September | 214.75 | 91.62 | 123.13 | 458.31 | 51.51 | 0.00 | 0.00 | 0.00 |
October | 342.18 | 236.84 | 105.34 | 585.57 | 142.99 | 0.00 | 0.00 | 0.00 |
November | 398.77 | 305.44 | 93.33 | 616.24 | 199.87 | 0.00 | 0.00 | 0.00 |
December | 433.96 | 343.53 | 90.42 | 652.64 | 253.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.49 | 153.84 | 107.65 | 465.59 | 127.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 119.95 | 9.25 | 90.42 | 295.73 | 27.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 466.77 | 372.79 | 124.57 | 732.53 | 253.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.74 | 59.51 | 36.24 | 138.83 | 113.94 | 0.00 | 0.00 | 0.00 |
February | 77.56 | 37.50 | 40.07 | 93.65 | 104.36 | 0.00 | 0.00 | 0.00 |
March | 102.73 | 48.97 | 53.76 | 143.42 | 93.38 | 0.00 | 0.00 | 0.00 |
April | 157.75 | 89.98 | 67.76 | 272.90 | 56.55 | 0.00 | 0.00 | 0.00 |
May | 158.15 | 88.68 | 69.48 | 292.23 | 40.94 | 0.00 | 0.00 | 0.00 |
June | 168.13 | 98.89 | 69.24 | 352.13 | 18.38 | 0.00 | 0.00 | 0.00 |
July | 122.37 | 57.12 | 65.25 | 265.20 | 14.03 | 0.00 | 0.00 | 0.00 |
August | 116.69 | 58.61 | 58.09 | 249.31 | 18.39 | 0.00 | 0.00 | 0.00 |
September | 101.72 | 42.74 | 58.98 | 206.59 | 26.15 | 0.00 | 0.00 | 0.00 |
October | 104.08 | 59.51 | 44.57 | 170.22 | 74.95 | 0.00 | 0.00 | 0.00 |
November | 95.86 | 57.88 | 37.98 | 135.41 | 106.60 | 0.00 | 0.00 | 0.00 |
December | 77.26 | 43.99 | 33.27 | 99.91 | 137.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 114.97 | 62.03 | 52.93 | 202.10 | 66.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.26 | 37.50 | 33.27 | 93.65 | 14.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.13 | 98.89 | 69.48 | 352.13 | 137.43 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245237E+09 | 0.153844E+09 | 91393269.40 | 0.326493E+09 | 0.285996E+09 |
February | 0.218336E+09 | 0.124898E+09 | 93437855.60 | 0.266820E+09 | 0.242170E+09 |
March | 0.302512E+09 | 0.155614E+09 | 0.146898E+09 | 0.419084E+09 | 0.239534E+09 |
April | 0.417890E+09 | 0.249068E+09 | 0.168823E+09 | 0.710572E+09 | 0.136793E+09 |
May | 0.447521E+09 | 0.265286E+09 | 0.182235E+09 | 0.811345E+09 | 0.100310E+09 |
June | 0.451415E+09 | 0.280502E+09 | 0.170913E+09 | 0.934136E+09 | 42868755.60 |
July | 0.393957E+09 | 0.222136E+09 | 0.171821E+09 | 0.823830E+09 | 34699973.57 |
August | 0.373899E+09 | 0.213384E+09 | 0.160516E+09 | 0.771479E+09 | 46345075.81 |
September | 0.296913E+09 | 0.143117E+09 | 0.153796E+09 | 0.588673E+09 | 63863131.93 |
October | 0.308172E+09 | 0.187551E+09 | 0.120621E+09 | 0.493473E+09 | 0.189631E+09 |
November | 0.229323E+09 | 0.137665E+09 | 91657637.17 | 0.300631E+09 | 0.263001E+09 |
December | 0.216052E+09 | 0.130458E+09 | 85593774.89 | 0.255182E+09 | 0.345591E+09 |
Annual Sum or Average | 0.390123E+10 | 0.226352E+10 | 0.163770E+10 | 0.670172E+10 | 0.199080E+10 |
Minimum of Months | 0.216052E+09 | 0.124898E+09 | 85593774.89 | 0.255182E+09 | 34699973.57 |
Maximum of Months | 0.451415E+09 | 0.280502E+09 | 0.182235E+09 | 0.934136E+09 | 0.345591E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125019E+10 | 0.998492E+09 | 0.251699E+09 | 0.196202E+10 | 0.568472E+09 |
February | 0.713981E+09 | 0.481533E+09 | 0.232448E+09 | 0.102684E+10 | 0.477810E+09 |
March | 0.657737E+09 | 0.338769E+09 | 0.318969E+09 | 0.101200E+10 | 0.496628E+09 |
April | 0.541846E+09 | 0.218958E+09 | 0.322888E+09 | 0.104333E+10 | 0.296476E+09 |
May | 0.375197E+09 | 61986563.75 | 0.313210E+09 | 0.792088E+09 | 0.219674E+09 |
June | 0.310914E+09 | 23967295.79 | 0.286946E+09 | 0.863591E+09 | 92802699.29 |
July | 0.328289E+09 | 33964074.41 | 0.294325E+09 | 0.874661E+09 | 73331759.28 |
August | 0.399183E+09 | 0.110314E+09 | 0.288869E+09 | 0.100670E+10 | 96369847.45 |
September | 0.556630E+09 | 0.237472E+09 | 0.319158E+09 | 0.118795E+10 | 0.133520E+09 |
October | 0.916495E+09 | 0.634351E+09 | 0.282144E+09 | 0.156838E+10 | 0.382986E+09 |
November | 0.103361E+10 | 0.791690E+09 | 0.241918E+09 | 0.159729E+10 | 0.518076E+09 |
December | 0.116231E+10 | 0.920121E+09 | 0.242185E+09 | 0.174803E+10 | 0.679239E+09 |
Annual Sum or Average | 0.824638E+10 | 0.485162E+10 | 0.339476E+10 | 0.146829E+11 | 0.403538E+10 |
Minimum of Months | 0.310914E+09 | 23967295.79 | 0.232448E+09 | 0.792088E+09 | 73331759.28 |
Maximum of Months | 0.125019E+10 | 0.998492E+09 | 0.322888E+09 | 0.196202E+10 | 0.679239E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256440E+09 | 0.159381E+09 | 97058531.82 | 0.371831E+09 | 0.305178E+09 |
February | 0.187637E+09 | 90710891.42 | 96926177.24 | 0.226549E+09 | 0.252464E+09 |
March | 0.275160E+09 | 0.131173E+09 | 0.143987E+09 | 0.384127E+09 | 0.250121E+09 |
April | 0.408887E+09 | 0.233241E+09 | 0.175646E+09 | 0.707366E+09 | 0.146589E+09 |
May | 0.423601E+09 | 0.237513E+09 | 0.186088E+09 | 0.782716E+09 | 0.109665E+09 |
June | 0.435803E+09 | 0.256322E+09 | 0.179481E+09 | 0.912733E+09 | 47651581.42 |
July | 0.327761E+09 | 0.152997E+09 | 0.174763E+09 | 0.710310E+09 | 37568808.87 |
August | 0.312549E+09 | 0.156968E+09 | 0.155581E+09 | 0.667756E+09 | 49263683.65 |
September | 0.263650E+09 | 0.110775E+09 | 0.152875E+09 | 0.535483E+09 | 67775773.02 |
October | 0.278761E+09 | 0.159394E+09 | 0.119366E+09 | 0.455920E+09 | 0.200755E+09 |
November | 0.248463E+09 | 0.150015E+09 | 98448681.06 | 0.350977E+09 | 0.276302E+09 |
December | 0.206926E+09 | 0.117817E+09 | 89108993.71 | 0.267591E+09 | 0.368079E+09 |
Annual Sum or Average | 0.362564E+10 | 0.195631E+10 | 0.166933E+10 | 0.637336E+10 | 0.211141E+10 |
Minimum of Months | 0.187637E+09 | 90710891.42 | 89108993.71 | 0.226549E+09 | 37568808.87 |
Maximum of Months | 0.435803E+09 | 0.256322E+09 | 0.186088E+09 | 0.912733E+09 | 0.368079E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 982.82 | 422.52 | 654.07 | 489.74 | 164.33 | 0.00 | 0.00 |
February | 618.55 | 392.13 | 462.94 | 288.17 | 174.77 | 0.00 | 0.00 |
March | 663.65 | 354.16 | 461.25 | 233.56 | 227.69 | 0.00 | 0.00 |
April | 936.37 | 210.52 | 528.02 | 270.55 | 257.47 | 0.00 | 0.00 |
May | 881.46 | 150.98 | 465.32 | 210.87 | 254.46 | 0.00 | 0.00 |
June | 1041.44 | 66.47 | 462.24 | 216.35 | 245.89 | 0.00 | 0.00 |
July | 897.43 | 52.45 | 392.03 | 152.74 | 239.29 | 0.00 | 0.00 |
August | 911.24 | 69.71 | 405.33 | 179.46 | 225.87 | 0.00 | 0.00 |
September | 889.40 | 99.68 | 431.02 | 189.57 | 241.45 | 0.00 | 0.00 |
October | 932.10 | 280.82 | 561.32 | 366.37 | 194.94 | 0.00 | 0.00 |
November | 857.64 | 397.95 | 583.10 | 416.42 | 166.68 | 0.00 | 0.00 |
December | 833.65 | 505.88 | 591.88 | 436.23 | 155.65 | 0.00 | 0.00 |
Annual Sum or Average | 871.89 | 249.73 | 500.17 | 287.65 | 212.51 | 0.00 | 0.00 |
Minimum of Months | 618.55 | 52.45 | 392.03 | 152.74 | 155.65 | 0.00 | 0.00 |
Maximum of Months | 1041.44 | 505.88 | 654.07 | 489.74 | 257.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.263239E+10 | 0.113169E+10 | 0.175187E+10 | 0.131172E+10 | 0.440151E+09 | 0.00 | 0.00 |
February | 0.149640E+10 | 0.948637E+09 | 0.111995E+10 | 0.697142E+09 | 0.422812E+09 | 0.00 | 0.00 |
March | 0.177752E+10 | 0.948593E+09 | 0.123541E+10 | 0.625556E+09 | 0.609853E+09 | 0.00 | 0.00 |
April | 0.242707E+10 | 0.545664E+09 | 0.136862E+10 | 0.701267E+09 | 0.667356E+09 | 0.00 | 0.00 |
May | 0.236090E+10 | 0.404396E+09 | 0.124632E+10 | 0.564786E+09 | 0.681533E+09 | 0.00 | 0.00 |
June | 0.269942E+10 | 0.172281E+09 | 0.119813E+10 | 0.560792E+09 | 0.637340E+09 | 0.00 | 0.00 |
July | 0.240369E+10 | 0.140488E+09 | 0.105001E+10 | 0.409097E+09 | 0.640909E+09 | 0.00 | 0.00 |
August | 0.244068E+10 | 0.186720E+09 | 0.108563E+10 | 0.480666E+09 | 0.604965E+09 | 0.00 | 0.00 |
September | 0.230532E+10 | 0.258375E+09 | 0.111719E+10 | 0.491363E+09 | 0.625829E+09 | 0.00 | 0.00 |
October | 0.249654E+10 | 0.752144E+09 | 0.150343E+10 | 0.981296E+09 | 0.522132E+09 | 0.00 | 0.00 |
November | 0.222300E+10 | 0.103148E+10 | 0.151140E+10 | 0.107937E+10 | 0.432024E+09 | 0.00 | 0.00 |
December | 0.223285E+10 | 0.135495E+10 | 0.158528E+10 | 0.116840E+10 | 0.416888E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.274958E+11 | 0.787542E+10 | 0.157732E+11 | 0.907145E+10 | 0.670179E+10 | 0.00 | 0.00 |
Minimum of Months | 0.149640E+10 | 0.140488E+09 | 0.105001E+10 | 0.409097E+09 | 0.416888E+09 | 0.00 | 0.00 |
Maximum of Months | 0.269942E+10 | 0.135495E+10 | 0.175187E+10 | 0.131172E+10 | 0.681533E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.118120E+11 | -0.111118E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -700158179.8 | 58.99 | 0.00 | 0.00 |
February | 0.105821E+11 | -0.993371E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -648408651.1 | 58.99 | 0.00 | 0.00 |
March | 0.111827E+11 | -0.104873E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -695375690.1 | 58.98 | 0.00 | 0.00 |
April | 0.995503E+10 | -0.931539E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -639647504.5 | 58.99 | 0.00 | 0.00 |
May | 0.938662E+10 | -0.873158E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -655034773.5 | 58.99 | 0.00 | 0.00 |
June | 0.837320E+10 | -0.774184E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -631365067.1 | 58.98 | 0.00 | 0.00 |
July | 0.826651E+10 | -0.761434E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -652169813.9 | 58.98 | 0.00 | 0.00 |
August | 0.840137E+10 | -0.774901E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -652354595.9 | 58.99 | 0.00 | 0.00 |
September | 0.864543E+10 | -0.801392E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -631510557.2 | 58.98 | 0.00 | 0.00 |
October | 0.979499E+10 | -0.912711E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -667883978.5 | 58.99 | 0.00 | 0.00 |
November | 0.103841E+11 | -0.971663E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667425763.7 | 58.98 | 0.00 | 0.00 |
December | 0.114696E+11 | -0.107468E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -722812809.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.118254E+12 | -0.110289E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.796415E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.826651E+10 | -0.111118E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -722812809.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.118120E+11 | -0.761434E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -631365067.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.29 | 0.24 | 01-JAN-07:00 | 2974.21 | 27.84 | 170.17 | 283.67 | 2282.79 | 25.29 | 140.17 | 283.33 |
February | 241.00 | 0.27 | 0.24 | 01-FEB-07:00 | 1339.46 | 22.89 | 80.00 | 264.17 | 1409.04 | 22.32 | 78.33 | 262.50 |
March | 344.33 | 0.27 | 0.24 | 01-MAR-07:30 | 1461.32 | 19.68 | 53.17 | 340.00 | 1594.37 | 19.77 | 55.67 | 340.67 |
April | 380.33 | 0.27 | 0.24 | 01-APR-06:00 | 1140.36 | 17.18 | 0.00 | 344.33 | 1209.74 | 17.19 | 0.00 | 348.67 |
May | 403.17 | 0.26 | 0.24 | 01-MAY-05:00 | 1214.03 | 16.97 | 0.00 | 391.83 | 1548.18 | 16.93 | 0.00 | 382.83 |
June | 418.17 | 0.27 | 0.24 | 01-JUN-06:10 | 1337.91 | 16.23 | 0.00 | 386.67 | 1534.65 | 16.28 | 0.00 | 389.50 |
July | 399.50 | 0.27 | 0.24 | 01-JUL-06:10 | 1048.75 | 16.71 | 0.00 | 385.50 | 1327.45 | 16.65 | 0.00 | 387.00 |
August | 361.83 | 0.27 | 0.24 | 01-AUG-06:40 | 1006.88 | 17.14 | 0.00 | 353.33 | 1148.51 | 16.89 | 0.00 | 355.83 |
September | 350.17 | 0.28 | 0.24 | 01-SEP-06:49 | 1254.88 | 17.81 | 5.50 | 327.17 | 1100.91 | 17.71 | 5.33 | 331.50 |
October | 348.00 | 0.28 | 0.24 | 01-OCT-06:00 | 1168.00 | 19.88 | 63.33 | 318.17 | 1166.86 | 20.00 | 63.83 | 312.83 |
November | 288.50 | 0.27 | 0.24 | 01-NOV-07:30 | 1585.68 | 23.78 | 106.50 | 282.67 | 1830.67 | 23.86 | 109.00 | 279.67 |
December | 290.67 | 0.27 | 0.24 | 01-DEC-07:49 | 3134.88 | 28.20 | 157.00 | 272.50 | 3421.63 | 29.45 | 177.83 | 274.50 |
Annual Sum or Average | 4135.50 | 0.27 | 1505.98 | 19.87 | 635.67 | 3950.00 | 1591.59 | 19.72 | 630.17 | 3948.83 | ||
Minimum of Months | 241.00 | 0.26 | 0.24 | 1006.88 | 16.23 | 0.00 | 264.17 | 1100.91 | 16.28 | 0.00 | 262.50 | |
Maximum of Months | 418.17 | 0.29 | 0.24 | 3134.88 | 28.20 | 170.17 | 391.83 | 3421.63 | 29.45 | 177.83 | 389.50 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210580E+10 | 16798.03 | 01-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308910E+10 | 10331.59 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216034E+10 | 17490.06 | 26-MAR-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58733071.01 | 4974.86 | 15-APR-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 432146.24 | 3601.22 | 03-JUN-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 410175.44 | 2050.88 | 25-JUL-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 192122.89 | 1601.02 | 23-AUG-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 138601.33 | 889.68 | 28-SEP-03:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409506E+09 | 8727.72 | 25-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145968E+10 | 15867.25 | 23-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501960E+10 | 16470.13 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.501960E+10 | 17490.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.275440E+09 | 15835.68 | 01-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235396E+09 | 7272.80 | 01-FEB-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416084E+09 | 15301.42 | 26-MAR-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1479877.10 | 3559.89 | 26-OCT-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182518E+09 | 11536.34 | 23-NOV-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135738E+10 | 23434.95 | 07-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135738E+10 | 23434.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.317051E+10 | 0.316746E+10 | 14076.02 | 31-JAN-14:00 | 14076.02 | 0.00 |
February | 0.00 | 0.00 | 44340743.45 | 40853734.65 | 3072.31 | 18-FEB-14:00 | 2588.09 | 0.00 |
March | 0.00 | 0.00 | 0.322966E+10 | 0.321086E+10 | 15104.12 | 20-MAR-17:05 | 15104.12 | 0.00 |
April | 0.00 | 0.00 | 0.172658E+11 | 0.172595E+11 | 51335.25 | 15-APR-03:02 | 51335.25 | 0.00 |
May | 0.00 | 0.00 | 0.238884E+11 | 0.238883E+11 | 51335.25 | 11-MAY-03:01 | 49689.35 | 0.00 |
June | 0.00 | 0.00 | 0.342163E+11 | 0.340578E+11 | 51335.25 | 27-JUN-03:59 | 51335.25 | 0.00 |
July | 0.00 | 0.00 | 0.381598E+11 | 0.329694E+11 | 57001.03 | 14-JUL-03:01 | 25786.94 | 0.00 |
August | 0.00 | 0.00 | 0.369547E+11 | 0.319543E+11 | 55131.47 | 01-AUG-03:29 | 33860.71 | 0.00 |
September | 0.00 | 0.00 | 0.312067E+11 | 0.265638E+11 | 56472.24 | 04-SEP-03:01 | 24341.82 | 0.00 |
October | 0.00 | 0.00 | 0.140424E+11 | 0.131876E+11 | 55173.54 | 03-OCT-03:01 | 29785.44 | 0.00 |
November | 0.00 | 0.00 | 0.345518E+10 | 0.332736E+10 | 17571.70 | 01-NOV-12:55 | 15659.44 | 0.00 |
December | 0.00 | 0.00 | 0.118914E+10 | 0.118914E+10 | 10876.83 | 22-DEC-14:00 | 10876.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206823E+12 | 0.190817E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 44340743.45 | 40853734.65 | 3072.31 | 2588.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.381598E+11 | 0.340578E+11 | 57001.03 | 51335.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.427711E+10 | 0.412977E+10 | 31821.01 | 06-JAN-04:42 | 26094.71 | 0.00 |
February | 0.00 | 0.00 | 0.599899E+09 | 0.464164E+09 | 31821.01 | 10-FEB-04:42 | 26170.68 | 0.00 |
March | 0.00 | 0.00 | 0.482702E+10 | 0.454649E+10 | 31821.01 | 17-MAR-03:31 | 22551.92 | 0.00 |
April | 0.00 | 0.00 | 0.184094E+11 | 0.183078E+11 | 31821.01 | 13-APR-03:32 | 30054.13 | 0.00 |
May | 0.00 | 0.00 | 0.258473E+11 | 0.258143E+11 | 31821.01 | 30-MAY-02:12 | 28517.99 | 0.00 |
June | 0.00 | 0.00 | 0.398071E+11 | 0.396736E+11 | 32023.89 | 17-JUN-13:57 | 32023.89 | 0.00 |
July | 0.00 | 0.00 | 0.443268E+11 | 0.386646E+11 | 35355.24 | 14-JUL-00:42 | 11973.13 | 0.00 |
August | 0.00 | 0.00 | 0.426860E+11 | 0.371138E+11 | 34746.23 | 01-AUG-02:51 | 18247.15 | 0.00 |
September | 0.00 | 0.00 | 0.358829E+11 | 0.299543E+11 | 34837.87 | 04-SEP-00:42 | 13903.09 | 0.00 |
October | 0.00 | 0.00 | 0.164174E+11 | 0.150764E+11 | 34093.36 | 03-OCT-02:42 | 15579.89 | 0.00 |
November | 0.00 | 0.00 | 0.551058E+10 | 0.466533E+10 | 31821.01 | 03-NOV-03:01 | 18548.59 | 0.00 |
December | 0.00 | 0.00 | 0.192061E+10 | 0.189310E+10 | 15892.26 | 12-DEC-04:42 | 15478.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.240512E+12 | 0.220304E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.599899E+09 | 0.464164E+09 | 15892.26 | 11973.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.443268E+11 | 0.396736E+11 | 35355.24 | 32023.89 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 4440.22 | 16321.62 | 23-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4398.13 | 16289.95 | 01-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 4209.60 | 15819.98 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 3885.56 | 14764.36 | 01-APR-12:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 3554.12 | 13478.70 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 3282.40 | 12237.63 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 3135.80 | 11437.91 | 01-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 3190.38 | 11741.05 | 31-AUG-12:58 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 3384.94 | 12758.22 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 3700.89 | 14082.47 | 31-OCT-12:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4041.64 | 15290.45 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4303.07 | 16121.39 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3790.52 | ||||
Minimum of Months | 0.00 | 0.00 | 3135.80 | 11437.91 | ||
Maximum of Months | 0.00 | 0.00 | 4440.22 | 16321.62 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:02 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116974E+10 | 0.25 | 503.64 | 01-JAN-00:02 | 0.29 |
February | 0.104041E+10 | 0.25 | 503.64 | 01-FEB-00:10 | 0.29 |
March | 0.117805E+10 | 0.25 | 503.64 | 01-MAR-00:10 | 0.29 |
April | 0.121941E+10 | 0.27 | 503.64 | 01-APR-03:02 | 0.29 |
May | 0.128551E+10 | 0.28 | 503.64 | 01-MAY-00:20 | 0.29 |
June | 0.124670E+10 | 0.28 | 503.64 | 01-JUN-00:08 | 0.29 |
July | 0.128859E+10 | 0.28 | 503.64 | 01-JUL-00:06 | 0.29 |
August | 0.128837E+10 | 0.28 | 503.64 | 01-AUG-00:06 | 0.29 |
September | 0.124658E+10 | 0.28 | 503.64 | 01-SEP-00:08 | 0.29 |
October | 0.124852E+10 | 0.27 | 503.64 | 01-OCT-00:08 | 0.29 |
November | 0.115675E+10 | 0.26 | 503.64 | 01-NOV-01:40 | 0.29 |
December | 0.114889E+10 | 0.25 | 503.64 | 01-DEC-00:10 | 0.29 |
Annual Sum or Average | 0.145175E+11 | 0.27 | |||
Minimum of Months | 0.104041E+10 | 0.25 | 503.64 | 0.29 | |
Maximum of Months | 0.128859E+10 | 0.28 | 503.64 | 0.29 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.280855E+10 | 0.49 | 1682.08 | 01-JAN-08:00 | 0.71 |
February | 0.256849E+10 | 0.50 | 1509.24 | 28-FEB-07:10 | 0.66 |
March | 0.281001E+10 | 0.49 | 1700.58 | 26-MAR-04:43 | 0.72 |
April | 0.266625E+10 | 0.49 | 1360.53 | 21-APR-06:10 | 0.63 |
May | 0.275569E+10 | 0.49 | 1428.47 | 31-MAY-17:05 | 0.65 |
June | 0.276543E+10 | 0.51 | 2111.86 | 28-JUN-17:07 | 0.80 |
July | 0.284936E+10 | 0.51 | 2324.80 | 14-JUL-04:01 | 0.83 |
August | 0.285970E+10 | 0.51 | 1993.24 | 13-AUG-03:01 | 0.77 |
September | 0.270999E+10 | 0.50 | 1910.74 | 07-SEP-03:01 | 0.75 |
October | 0.277193E+10 | 0.49 | 1466.37 | 25-OCT-06:30 | 0.66 |
November | 0.270257E+10 | 0.49 | 1657.20 | 23-NOV-07:10 | 0.71 |
December | 0.288644E+10 | 0.50 | 1673.32 | 06-DEC-07:10 | 0.71 |
Annual Sum or Average | 0.331544E+11 | 0.50 | |||
Minimum of Months | 0.256849E+10 | 0.49 | 1360.53 | 0.63 | |
Maximum of Months | 0.288644E+10 | 0.51 | 2324.80 | 0.83 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129501E+10 | 0.52 | 1164.14 | 07-JAN-05:01 | 0.91 |
February | 0.116702E+10 | 0.52 | 722.95 | 18-FEB-05:01 | 0.70 |
March | 0.129848E+10 | 0.53 | 1438.10 | 21-MAR-04:01 | 1.00 |
April | 0.132162E+10 | 0.57 | 1438.10 | 07-APR-04:01 | 1.00 |
May | 0.150727E+10 | 0.60 | 1438.10 | 11-MAY-04:01 | 1.00 |
June | 0.193276E+10 | 0.68 | 1438.10 | 01-JUN-04:01 | 1.00 |
July | 0.193357E+10 | 0.67 | 1438.10 | 07-JUL-04:01 | 1.00 |
August | 0.189486E+10 | 0.66 | 1438.10 | 01-AUG-03:01 | 0.99 |
September | 0.166743E+10 | 0.63 | 1438.10 | 01-SEP-04:01 | 0.99 |
October | 0.139778E+10 | 0.57 | 1438.10 | 01-OCT-04:01 | 1.00 |
November | 0.125817E+10 | 0.53 | 1438.10 | 10-NOV-05:01 | 1.00 |
December | 0.130788E+10 | 0.52 | 933.47 | 07-DEC-05:04 | 0.82 |
Annual Sum or Average | 0.179818E+11 | 0.58 | |||
Minimum of Months | 0.116702E+10 | 0.52 | 722.95 | 0.70 | |
Maximum of Months | 0.193357E+10 | 0.68 | 1438.10 | 1.00 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 51.76 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 52.61 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 53.05 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 53.30 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 52.87 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 54.18 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:05 | 0.00 | 0.00 | 54.15 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 54.90 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 54.51 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 53.73 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 54.16 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 53.58 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 51.76 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 54.90 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 41.77 | 41.77 | 4440.22 | 16321.62 | 23-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 52.75 | 52.75 | 4398.13 | 16289.95 | 01-FEB-13:25 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 52.81 | 52.81 | 4209.60 | 15819.98 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 53.86 | 53.86 | 3885.56 | 14764.36 | 01-APR-12:55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 44.81 | 44.81 | 3554.12 | 13478.70 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 54.36 | 54.36 | 3282.40 | 12237.63 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 54.25 | 54.25 | 3135.80 | 11437.91 | 01-JUL-12:20 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 54.74 | 54.74 | 3190.38 | 11741.05 | 31-AUG-12:58 |
September | 0.00 | 0.00 | 01-SEP-00:02 | 54.50 | 54.50 | 3384.94 | 12758.22 | 30-SEP-12:25 |
October | 0.00 | 0.00 | 01-OCT-00:02 | 45.54 | 45.54 | 3700.89 | 14082.47 | 31-OCT-12:25 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 54.12 | 54.12 | 4041.64 | 15290.45 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 53.42 | 53.42 | 4303.07 | 16121.39 | 31-DEC-13:20 |
Annual Sum or Average | 0.00 | 3790.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 41.77 | 41.77 | 3135.80 | 11437.91 | ||
Maximum of Months | 0.00 | 0.00 | 54.74 | 54.74 | 4440.22 | 16321.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.373337E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.258226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.374154E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.749638E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.947101E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.127636E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.134713E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.131691E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112114E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.666901E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.369137E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.323600E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.912364E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.258226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.134713E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.248094E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133995E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.261431E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.606152E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.821812E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129054E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.132847E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.128631E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.106379E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.562299E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.273913E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.184880E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.806168E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.132847E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.280855E+10 | 0.317051E+10 | 0.210580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256849E+10 | 44340743.45 | 0.308910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281001E+10 | 0.322966E+10 | 0.216034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266625E+10 | 0.172577E+11 | 58733071.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275569E+10 | 0.238864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276543E+10 | 0.341705E+11 | 432146.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284936E+10 | 0.380836E+11 | 410175.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.285970E+10 | 0.368657E+11 | 192122.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.270999E+10 | 0.311361E+11 | 138601.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277193E+10 | 0.140267E+11 | 0.409506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270257E+10 | 0.345518E+10 | 0.145968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288644E+10 | 0.118914E+10 | 0.501960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331544E+11 | 0.206515E+12 | 0.143039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.256849E+10 | 44340743.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.288644E+10 | 0.380836E+11 | 0.501960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.129501E+10 | 0.427510E+10 | 0.275440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116702E+10 | 0.598817E+09 | 0.235396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129848E+10 | 0.482516E+10 | 0.416084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132162E+10 | 0.183756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150727E+10 | 0.257813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193276E+10 | 0.394790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193357E+10 | 0.438236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189486E+10 | 0.422047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166743E+10 | 0.355673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139778E+10 | 0.163462E+11 | 1479877.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125817E+10 | 0.550764E+10 | 0.182518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130788E+10 | 0.192061E+10 | 0.135738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179818E+11 | 0.238705E+12 | 0.246830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116702E+10 | 0.598817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193357E+10 | 0.438236E+11 | 0.135738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.280855E+10 | 0.00 | 0.00 | 0.00 | 0.924815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256849E+10 | 0.00 | 0.00 | 0.00 | 13776020.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.281001E+10 | 0.00 | 0.00 | 0.00 | 0.931527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266625E+10 | 0.00 | 0.00 | 0.00 | 0.483012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275569E+10 | 0.00 | 0.00 | 0.00 | 0.671531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276543E+10 | 0.00 | 0.00 | 0.00 | 0.999820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284936E+10 | 0.00 | 0.00 | 0.00 | 0.106220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.285970E+10 | 0.00 | 0.00 | 0.00 | 0.103094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.270999E+10 | 0.00 | 0.00 | 0.00 | 0.850139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277193E+10 | 0.00 | 0.00 | 0.00 | 0.389708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270257E+10 | 0.00 | 0.00 | 0.00 | 0.988794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288644E+10 | 0.00 | 0.00 | 0.00 | 0.349565E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331544E+11 | 0.00 | 0.00 | 0.00 | 0.580820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.256849E+10 | 0.00 | 0.00 | 0.00 | 13776020.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.288644E+10 | 0.00 | 0.00 | 0.00 | 0.106220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.129501E+10 | 0.00 | 0.00 | 0.00 | 0.118594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116702E+10 | 0.00 | 0.00 | 0.00 | 0.172933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129848E+10 | 0.00 | 0.00 | 0.00 | 0.131583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132162E+10 | 0.00 | 0.00 | 0.00 | 0.473990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150727E+10 | 0.00 | 0.00 | 0.00 | 0.671086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193276E+10 | 0.00 | 0.00 | 0.00 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193357E+10 | 0.00 | 0.00 | 0.00 | 0.113511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189486E+10 | 0.00 | 0.00 | 0.00 | 0.109683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166743E+10 | 0.00 | 0.00 | 0.00 | 0.897043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139778E+10 | 0.00 | 0.00 | 0.00 | 0.422522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125817E+10 | 0.00 | 0.00 | 0.00 | 0.148097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130788E+10 | 0.00 | 0.00 | 0.00 | 0.540911E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179818E+11 | 0.00 | 0.00 | 0.00 | 0.626350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.116702E+10 | 0.00 | 0.00 | 0.00 | 0.172933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.193357E+10 | 0.00 | 0.00 | 0.00 | 0.113511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.554159E+10 | 11712913.04 | 0.00 | 21380897.48 | 0.00 | 0.123559E+10 | 0.424297E+10 | 0.00 | 5.28 |
February | 0.658958E+10 | 0.00 | 0.00 | 3220005.83 | 246305.68 | 0.229455E+10 | 0.152796E+10 | 0.00 | 3.93 |
March | 0.504685E+10 | 38086215.10 | 0.00 | 18537343.51 | 0.00 | 0.150036E+10 | 0.372706E+10 | 0.00 | 5.09 |
April | 0.147472E+10 | 0.132026E+10 | 62637.21 | 27382084.56 | 1160398.55 | 14254406.42 | 0.255925E+10 | 8994.07 | 4.80 |
May | 0.447564E+09 | 0.269468E+10 | 0.00 | 17985898.32 | 2056172.71 | 0.00 | 0.187221E+10 | 0.00 | 4.41 |
June | 52948459.30 | 0.613985E+10 | 0.00 | 6532153.05 | 29663669.06 | 2845.40 | 0.767230E+09 | 0.00 | 4.27 |
July | 46512839.88 | 0.761677E+10 | 104144.33 | 2872102.76 | 59958896.38 | 0.00 | 0.361394E+09 | 2568.63 | 4.00 |
August | 68905209.69 | 0.702773E+10 | 0.00 | 4074409.39 | 47267430.46 | 13265.53 | 0.679206E+09 | 0.00 | 4.37 |
September | 0.136250E+09 | 0.499841E+10 | 0.00 | 7005207.35 | 18590386.25 | 1683.34 | 0.119760E+10 | 100.21 | 4.91 |
October | 0.250313E+10 | 0.131487E+10 | 0.00 | 25885500.05 | 4463709.85 | 0.232593E+09 | 0.429099E+10 | 0.00 | 5.49 |
November | 0.512992E+10 | 33443154.79 | 0.00 | 20576691.33 | 0.00 | 0.765456E+09 | 0.452624E+10 | 0.00 | 5.12 |
December | 0.606126E+10 | 84019.04 | 0.00 | 11403740.29 | 0.00 | 0.380420E+10 | 0.295624E+10 | 0.00 | 4.65 |
Annual Sum or Average | 0.330992E+11 | 0.311959E+11 | 166781.55 | 0.166856E+09 | 0.163407E+09 | 0.984702E+10 | 0.287083E+11 | 11662.91 | 4.70 |
Minimum of Months | 46512839.88 | 0.00 | 0.00 | 2872102.76 | 0.00 | 0.00 | 0.361394E+09 | 0.00 | 3.93 |
Maximum of Months | 0.658958E+10 | 0.761677E+10 | 104144.33 | 27382084.56 | 59958896.38 | 0.380420E+10 | 0.452624E+10 | 8994.07 | 5.49 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123647E+11 | 0.00 | 0.00 | 45419971.31 | 0.00 | 0.00 | 0.163602E+11 | 0.00 | 7.42 |
February | 0.156524E+11 | 0.00 | 0.00 | 17591256.51 | 0.00 | 0.00 | 0.125593E+11 | 0.00 | 7.45 |
March | 0.118971E+11 | 0.00 | 0.00 | 46059269.62 | 0.00 | 0.00 | 0.160121E+11 | 0.00 | 7.48 |
April | 0.267497E+10 | 0.164314E+09 | 0.00 | 94069549.52 | 0.00 | 0.00 | 0.128010E+11 | 0.00 | 7.73 |
May | 0.851303E+09 | 0.139731E+10 | 0.00 | 89491720.98 | 18410.34 | 0.00 | 0.100231E+11 | 0.00 | 8.08 |
June | 85926430.74 | 0.846617E+10 | 0.00 | 53172607.87 | 2490554.54 | 0.00 | 0.367954E+10 | 0.00 | 8.95 |
July | 0.100385E+09 | 0.100046E+11 | 0.00 | 27843735.51 | 13702024.72 | 0.00 | 0.159025E+10 | 0.00 | 8.96 |
August | 0.141206E+09 | 0.903616E+10 | 0.00 | 29254733.98 | 9964707.59 | 0.00 | 0.206471E+10 | 0.00 | 8.88 |
September | 0.296847E+09 | 0.520755E+10 | 0.00 | 47379796.71 | 4109038.19 | 0.00 | 0.362994E+10 | 0.00 | 8.64 |
October | 0.454030E+10 | 0.663013E+09 | 0.00 | 72014999.24 | 798291.69 | 0.00 | 0.147312E+11 | 0.00 | 7.82 |
November | 0.953686E+10 | 0.00 | 0.00 | 49287482.34 | 0.00 | 0.00 | 0.175040E+11 | 0.00 | 7.50 |
December | 0.197849E+11 | 0.00 | 0.00 | 27617705.09 | 0.00 | 2244506.75 | 0.130408E+11 | 0.00 | 7.42 |
Annual Sum or Average | 0.779268E+11 | 0.349391E+11 | 0.00 | 0.599203E+09 | 31083027.07 | 2244506.75 | 0.123996E+12 | 0.00 | 8.03 |
Minimum of Months | 85926430.74 | 0.00 | 0.00 | 17591256.51 | 0.00 | 0.00 | 0.159025E+10 | 0.00 | 7.42 |
Maximum of Months | 0.197849E+11 | 0.100046E+11 | 0.00 | 94069549.52 | 13702024.72 | 2244506.75 | 0.175040E+11 | 0.00 | 8.96 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:30:01
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.329400E+11 | 0.846729E+10 | 0.659293E+11 | 0.209819E+10 | 0.301720E+11 |
February | 0.348352E+11 | 0.999346E+10 | 0.641454E+11 | 0.490586E+09 | 0.181607E+11 |
March | 0.483064E+11 | 0.848035E+10 | 0.641797E+11 | 0.182379E+10 | 0.319711E+11 |
April | 0.647835E+11 | 0.178467E+10 | 0.359465E+11 | 0.117571E+10 | 0.701369E+11 |
May | 0.673565E+11 | -930317915.5 | 0.227655E+11 | 0.801537E+09 | 0.887266E+11 |
June | 0.698292E+11 | -0.520088E+10 | -0.567912E+10 | 0.449003E+09 | 0.121637E+12 |
July | 0.622281E+11 | -0.645066E+10 | -0.151677E+11 | 0.169696E+09 | 0.131802E+12 |
August | 0.554899E+11 | -0.592966E+10 | -0.116487E+11 | 0.383937E+09 | 0.128720E+12 |
September | 0.455737E+11 | -0.398247E+10 | -0.105162E+10 | 0.595916E+09 | 0.108601E+12 |
October | 0.415484E+11 | 0.335615E+10 | 0.436447E+11 | 0.215537E+10 | 0.613571E+11 |
November | 0.339092E+11 | 0.830971E+10 | 0.631415E+11 | 0.190198E+10 | 0.308812E+11 |
December | 0.262697E+11 | 0.111018E+11 | 0.740919E+11 | 0.138118E+10 | 0.243679E+11 |
Annual Sum or Average | 0.583070E+12 | 0.289995E+11 | 0.400297E+12 | 0.134269E+11 | 0.846533E+12 |
Minimum of Months | 0.262697E+11 | -0.645066E+10 | -0.151677E+11 | 0.169696E+09 | 0.181607E+11 |
Maximum of Months | 0.698292E+11 | 0.111018E+11 | 0.740919E+11 | 0.215537E+10 | 0.131802E+12 |